breaking. Est i mat es pri mary cont act wear( idt) Monitors arc duration. Auxiliary and control circuits Monitors operating coil continuity. Monitors auxiliary supply voltage. Monitors heater integrity. CBWatch-2 continuously monitors circuit breaker condition. It signals in real time any malfunction to maintenance services. Therefore, CBWatch-2 facilitates reduced maintenance cost and failure risk. CBWatch-2 Modular circuit breaker monitoring system Optional functions SF
Monitors gas pressure and temperature and calculates the SF or gas mixture density using the Beattie-Bridgeman algorithm. Detects liquefaction and inhibits false alarms in the event of liquefaction. Calculates SF leakage rates in order to give advance warning of alarm and lockout threshold levels. Mechanical operation Monitors close and open operating times. Allows the use of conventional auxiliary switches, static auxiliary switches or primary contact travel sensors. Monitors primary contacts separation speed, buffering and over travel. Detects deterioration in mechanical performance (friction, corrosion, breakage, spring fatigue and buffer defects). Monitors auxiliary switch timing.
Spring operating mechanism Monitors recharging motor operating time. Detects motor or motor limit switch defects. Hydraulic operating mechanism Monitors pump motor operating time. Detects internal and external leackage. Detects nitrogen loss from accumulator. Detects threshold pressure on hydraulic system. 6 6 6 Spring mechanism : Spring motor limit switch contacts. Hydraulic mechanism : Pump start contacts. Hydraulic pressure sensor. Auxiliary and control circuits : Temperature sensors. Coil supervision relays. Installation Dimensions 310mm x 280mm x 95mm 12 x 11 x 3 Installation in operating mechanism, local control cubicle or separate enclosure. Available versions Version for circuit breakers with one operating mechanism for all three poles. Version for circuit breakers with one operating mechanism for each of the three poles. Environment Ambiant temperature -40C to +55C (Option : -50C with heater) Electromagnetic compatibility according to standards : - IEC 255-5 - IEC 1000-4-4 - ANSI C37-90-1 - IEC 1000-4-12 - IEC 255-22-3 Power supply 48 - 125V DC ; 48 - 120V AC 150 - 250V DC ; 150 - 240V AC Tolerance : -30% to +15% Power consumption : 30 VA maximum. Dependability High reliability and high availability due to continuous self monitoring of electronic module and sensors. Local interface LCD display and keypad (option) 1 self monitoring status relay. 4 configurable output relays. 1 self monitoring status LED. 4 local indication LEDs. RS232 local communication port. Network interface Isolated RS485 communication port with MODBUS protocol.
SF : Pressure and temperature sensors. Operations : Coil signal sensors. Auxiliary contacts. Primary contact travel sensors. Primary current : Auxiliary current transformers. Example installation Circuit breaker with one operating mechanism per pole Sensors required for different options
Pole A sensors Pole B sensors Pole C sensors INTERFACE : Local RS232 port RS485 MODBUS port Output relay contacts 6 R e f
: