You are on page 1of 5

Fri Feb 15 10:52:33 2013 Settings (Enabled Features) PAGE 1

MOTOR 3
469 RELAY 1
DEVICE DEFINITION
ORDER CODE: 469-P5-HI-A20
VERSION: 2.6X
SERIAL NUMBER: A3090717
DESCRIPTION: (NONE)
INTERFACE:COM1: 9600 N 8 1
469 SETUP
Default Message Cycle Time
Trace Memory Buffers 8 x 14 cycles
Display Update Interval 0.4 s
Motor Load Filter Interval 0 cycles
MESSAGE SCRATCHPAD
First Scratchpad Message
MULTILIN SR469 Motor Management Relay
SYSTEM SETUP
CURRENT SENSING
Phase CT Primary
Phase Differential CT Primary 75 A
VOLTAGE SENSING
VoltageTransformer Connection Type
Nominal SystemFrequency
Starter Status Switch
Assignable Input 1 Function
Force R1 Operate Time
Force R4 Operate Time
Force R2 Output Operate Time
Force R3 Operate Time
Force R5 Operate Time
Curve Style
Hot/Cold Safe Stall Ratio 1.00
RTD Biasing On/Yes
RTD Bias Minimum 41 C
RTD Bias Center Point 130 C
RTD Bias Maximum 155 C
Thermal Capacity Alarm Unlatched
Thermal Capacity AlarmRelays Alarm
Fri Feb 15 10:52:33 2013 Settings (Enabled Features) PAGE 2
MOTOR 3
469 RELAY 1
DEVICE DEFINITION
ORDER CODE: 469-P5-HI-A20
VERSION: 2.6X
SERIAL NUMBER: A3090717
DESCRIPTION: (NONE)
INTERFACE:COM1: 9600 N 8 1
469 THERMAL MODEL (continued fromlast page)
Thermal Capacity AlarmLevel
Standard Overload Curve Number
Short Circuit Trip
Overload Alarm
Mechanical J amTrip
Block Undercurrent fromStart
Current Unbalance Alarm
Current Unbalance Trip Relays Trip
Current Unbalance Trip Pickup 20 %
Current Unbalance Trip Delay 30 s
GROUND FAULT
Ground Fault Alarm
Ground Fault Trip Relays Trip
Ground Fault Trip Pickup 0.40 CT
Intentional GF Trip Delay 40 ms
PHASE DIFFERENTIAL
Phase Differential Trip
0.10 CT
Differential Trip Delay While Running 0 ms
MOTOR STARTING
ACCELERATION TIMER
Accleration Timer Trip
Stator RTD Type
RTD #1 Application
RTD #1 Trip Unlatched
RTD #1 Trip Voting RTD #1
Fri Feb 15 10:52:33 2013 Settings (Enabled Features) PAGE 3
MOTOR 3
469 RELAY 1
DEVICE DEFINITION
ORDER CODE: 469-P5-HI-A20
VERSION: 2.6X
SERIAL NUMBER: A3090717
DESCRIPTION: (NONE)
INTERFACE:COM1: 9600 N 8 1
RTD #1 (continued fromlast page)
RTD #1 Trip Relays
RTD #2 Application
RTD #3 Application
RTD #4 Application
RTD #4 Trip Unlatched
RTD #4 Trip Voting RTD #4
RTD #4 Trip Relays Trip & Aux2
RTD #4 Trip Temperature 155 C
RTD #4 Hi Alarm Unlatched
RTD #4 Hi AlarmRelays Alarm
RTD #4 Hi AlarmLevel 145 C
RTD #5
RTD #5 Application
RTD #5 Trip Unlatched
RTD #5 Trip Voting RTD #5
RTD #5 Trip Relays Trip & Aux2
RTD #5 Trip Temperature 155 C
RTD #5 Hi Alarm Unlatched
RTD #5 Hi AlarmRelays Alarm
RTD #5 Hi AlarmLevel 145 C
RTD #6
RTD #6 Application
RTD #6 Trip Unlatched
RTD #6 Trip Voting RTD #6
RTD #6 Trip Relays Trip & Aux2
RTD #6 Trip Temperature 155 C
RTD #6 Hi Alarm Unlatched
RTD #6 Hi AlarmRelays Alarm
RTD #6 Hi AlarmLevel 145 C
RTD #7
RTD #7 Application
RTD #7 Trip Unlatched
RTD #7 Trip Voting RTD #7
RTD #7 Trip Relays Trip & Aux2
RTD #7 Trip Temperature 110 C
RTD #7 Hi Alarm Unlatched
RTD #7 Hi AlarmRelays Alarm
RTD #7 Hi AlarmLevel 100 C
RTD #8
RTD #8 Application
Fri Feb 15 10:52:33 2013 Settings (Enabled Features) PAGE 4
MOTOR 3
469 RELAY 1
DEVICE DEFINITION
ORDER CODE: 469-P5-HI-A20
VERSION: 2.6X
SERIAL NUMBER: A3090717
DESCRIPTION: (NONE)
INTERFACE:COM1: 9600 N 8 1
RTD #8 (continued fromlast page)
RTD #8 AlarmTemperature
110 C
RTD #8 Hi Alarm Unlatched
RTD #8 Hi AlarmRelays Alarm
RTD #8 Hi AlarmLevel 100 C
RTD #9
RTD #9 Application
RTD #9 Trip Unlatched
RTD #9 Trip Voting RTD #9
RTD #9 Trip Relays Trip & Aux2
RTD #9 Trip Temperature 110 C
RTD #9 Hi Alarm Unlatched
RTD #9 Hi AlarmRelays Alarm
RTD #9 Hi AlarmLevel 100 C
RTD #10
RTD #10 Application
RTD #11 Application
RTD #12 Application
Undervoltage Active Only If Bus Energized
Undervoltage AlarmDelay 5.0 s
Undervoltage AlarmEvents On/Yes
Undervoltage Trip Unlatched
Undervoltage Trip Relays Trip
Undervoltage Trip Pickup 0.75 Rated
Starting Undervoltage Trip Pickup 0.80 Rated
Undervoltage Trip Delay 5.0 s
OVERVOLTAGE
Overvoltage Alarm
Overvoltage Trip Relays Trip
Overvoltage Trip Pickup 1.10 Rated
Overvoltage Trip Delay 3.0 s
PHASE REVERSAL
Voltage Phase Reversal Trip
Block Power Factor Element fromStart
Block kvar Element fromStart
Block Underpower FromStart
Fri Feb 15 10:52:33 2013 Settings (Enabled Features) PAGE 5
MOTOR 3
469 RELAY 1
DEVICE DEFINITION
ORDER CODE: 469-P5-HI-A20
VERSION: 2.6X
SERIAL NUMBER: A3090717
DESCRIPTION: (NONE)
INTERFACE:COM1: 9600 N 8 1
REVERSE POWER (continued fromlast page)
Block Reverse Power FromStart
Stator Resistance
Overtorque AlarmRelays
Current Demand Period
kW Demand Period
kvar Demand Period
kVA Demand Period
Analog Output 1 Selection
Phase A Current Maximum 400 A
Phase B Current Minimum 0 A
Phase B Current Maximum 400 A
Phase C Current Minimum 0 A
Phase C Current Maximum 400 A
Average Line Voltage Minimum 100 V
Average Line Voltage Maximum 4160 V