SS-1 Position

SS-2 Position - - Manual Auto - -


SCMS Auto PFC OFF SCMS Auto PFC ON
Selection based actions * Power Factor controller
switched off.
* Stage switching
controlled manually
through Open/Close push
buttons.
* Local manual not
functional.
* Stage switching
controlled by Power Factor
controller.
* Power Factor controller
switched off.
* Auto Power Factor and Loal
Manual not Functional.
* Stage switching controlled
manually through SCMS
Open/Close.
* Loal Manual and SCMS
Manual not Functional.
* Stage switching
controlled by Power Factor
controller.
Protection based actions due to:
* Over voltage/Under voltage protection trip.
* Capacitor bank feeder circuit breaker open.
* 11 kV associated transfrmer incommer circuit
breaker open.
* 240 V AC supply failure.
* 110 V DC supply failure.
All Stage devices opened
and push button
OPEN/CLOSE ineffective
All Stage devices opened
and Power Factor controller
Switched OFF
All Stage devices opened and
SCMS OPEN/CLOSE
ineffective
* Stage over load and stage unbalance
protection trip.
* Stage over current and earth fault protection
trip.
* Stage HRC fuse operation.
Associated Stage device
opened push button
OPEN/CLOSE ineffective
Power Factor controller
remains Operative (i.e
Switched ON)
Associated Stage device
opened and SCMS
OPEN/CLOSE ineffective
OFF LOCAL SCMS
* All Stage devices opened.
* Power Factor controller
switched off.
* Local/Remote Controls not
functional.
SCMS Manual
All Stage devices opened and SCMS
OPEN/CLOSE ineffective
* Over voltage/Under voltage protection trip.
* Capacitor bank feeder circuit breaker open.
* 11 kV associated transfrmer incommer
circuit breaker open.
* 240 V AC supply failure.
* 110 V DC supply failure.
* SCMS Manual not selected.
SCMS Manual
Associated Stage device opened and
SCMS OPEN/CLOSE ineffective
* Stage over load and stage unbalance
protection trip.
* Stage over current and earth fault protection
trip.
* Stage HRC fuse operation.
Local Auto
All Stage devices opened and Power
Factor controller Switched OFF
* Over voltage/Under voltage protection trip.
* Capacitor bank feeder circuit breaker open.
* 11 kV associated transfrmer incommer
circuit breaker open.
* 240 V AC supply failure.
* 110 V DC supply failure.
* Auto Power Factor not selected.
Local Auto
Power Factor controller remains
Operative (i.e Switched ON)
* Stage over load and stage unbalance
protection trip.
* Stage over current and earth fault protection
trip.
* Stage HRC fuse operation.
Local Manual
All Stage devices opened and push
button OPEN/CLOSE ineffective
* Over voltage/Under voltage protection trip.
* Capacitor bank feeder circuit breaker open.
* 11 kV associated transfrmer incommer
circuit breaker open.
* 240 V AC supply failure.
* 110 V DC supply failure.
* Local Manual not selected.
Local Manual
Associated Stage device opened
push button OPEN/CLOSE ineffective
* Stage over load and stage unbalance
protection trip.
* Stage over current and earth fault protection
trip.
* Stage HRC fuse operation.
Observations
6C 1
6C 2
6D 3
6D 4
8 5
8 6
8 7
8 8
8 9
8 10
8 11
8 12
9 13
14
15
Observations
Contact multiplication of Trafo Incommers, Bus couplers and Tap change in progress status.
Status of Trafo Incommer breaker to their respective capacitor bank protection panel.
Connecting the CT from those transformer feeders to summation CT when their breaker is
closed and a path is available to that section.
Information to other capacitor bank control panels about the transformer feeder breakers and
about closed path to other bus sections.
Tap change in progress of all transformers.
AC fail supervision contactor is energized after delay of 10 mins.
Energizing of lockout contactor everytime the vaccum contactor is opened.
MV fuse monitoring.
AC MCBs monitorig.
Capacitor bank circuit breaker and earth switch status multiplication.
Relay healthiness contact multiplication.
Providing DC supply to access gate interlock circuitafter capacotor bank feeder is earthed.
Closing of vccum contactors 10 minues after earthing capaitor feeder.
Tripping of vaccum contactor on:
- Fuse failure
- Over load and unbalance
- Over current and earth fault
Test plug inserted indication.