Installation calculation report

New_project
Full

Page 2/28

Content

Project description.................................................................................................................. 4
1.1

Project general settings................................................................................................................... 4

1.2

Settings for wiring device calculation............................................................................................ 4

1.3

List of loads...................................................................................................................................... 4

Installation general design.....................................................................................................6


2.1

List of devices.................................................................................................................................. 6

Calculation notes.................................................................................................................. 14
3.1

Source circuits............................................................................................................................... 14

3.2

Generator circuits.......................................................................................................................... 23

3.3

LV Source circuits.......................................................................................................................... 23

3.4

UPS circuits.................................................................................................................................... 24

3.5

Capacitor bank circuits.................................................................................................................. 24

3.6

Feeder circuits................................................................................................................................ 24

3.7

LV Transformer circuits................................................................................................................. 25

3.8

Couplers circuits............................................................................................................................ 26

3.9

Generic load circuits...................................................................................................................... 27

3.10

Lighting load circuits................................................................................................................ 27

3.11

Power socket load circuits....................................................................................................... 28

3.12

Motor starter combination........................................................................................................ 28

3.13

Busbar circuits.......................................................................................................................... 29

3.14

Busbar trunking system circuits............................................................................................. 29

3.15

Busbar trunking system circuits............................................................................................. 29

3.16

Lighting Busbar trunking system circuits..............................................................................29

Project: New_project

04/09/2014

Page 3/28

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

300 mm

1.3 List of loads


Name
AA 3
AA 9
AA 14

1.3.1 Generic loads


Sr (kVA)
Pr (kW) Ir (A)
200
170
289
153
130
221
34.6
29.4
50
1.3.2

Name
AA 10

Sr (kVA)
4.62

Project: New_project

Cos
0.85
0.85
0.85

Nbr
1
1
10

Polarity
3Ph+N
3Ph+N
3Ph+N

Non linear load


No
No
No

THDi 3 (%)
0
0
0

Cos
0.85

Nbr
1

Polarity
1Ph+N

Non linear load THDi 3 (%)


No
0

Power sockets
Pr (kW)
3.93

Ir (A)
20

04/09/2014

Page 4/28

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Nbr Range
Insulation

Name
TA 0

Trihal

Dry-type

Sr (kVA)

ukrT (%) Connection U2 (V) SEA

630

2.1.2 LV switchboards and busbar


Switchboard name
Range
UC 2
No preference
UC 8
No preference
Busbar name

Switchboard
name
UC 2
UC 8

WC 1
WC 7

Name

2.1.3
Nbr

QA 0

QA 3

QA 6

QA 9

QA 10

QA 12

QA 14

10

Circuit breaker
Range Rating (A)
Designation
Masterpact 1000
NT - NT10H1
Compact
400
NSX NSX400F
Compact
250
NSX NSX250B
Compact
250
NSX NSX250B
Acti9 iC60 - 20
iC60H
Compact
400
NSX NSX400F
Acti9 iC60 - 50
iC60H

420

Rating (A)
0.00
0.00

IP
Undefined
Undefined

Ks

Polarity

SEA

Equipotential bounding

1
1

3Ph+N
3Ph+N

TN-S
TN-S

With
Without

Poles

Trip unit/Curve

4P4d

Micrologic 5.0 E

4P4d

Micrologic 2.3

4P4d

Micrologic 2.2

4P4d

Micrologic 2.2

2P1d

4P4d

Micrologic 2.3

4P4d

RCD

RCD class

Vigi MH

2.1.4 Power distribution busbar trunking system


Incomer
Nb of Feeder
L (m)
Range
WD 12
1
40
KSA

Name
WC 13

2.1.5

Insulation L (m)
XLPE
30

WD 6

XLPE

QA 6

Project: New_project

Rating (A)
400

Cable schedule

Name Nbr Incomer Feeder Type


WD 3 1
QA 3
AA 3
Multi-core
1

TN-S

Rb
(m)
10000

WC 7

Multi-core

25

L1/L2/L3
1x185
Copper
1x120

N
1x185
Copper
1x120

PE/PEN
1x95
Copper
1x70
04/09/2014

Page 5/28

WD 14 10
WD 12 1

QA 14
QA 12

AA 14
WC 13

Multi-core
Single-core

XLPE
XLPE

15
15

WD 10 1

QA 10

AA 10

Multi-core

XLPE

WD 9

QA 9

AA 9

Multi-core

XLPE

WD 0

TA 0

QA 0

Multi-core

XLPE

2.1.6 MV Cable
Name Nbr Designation CSA (mm) Icc (A)
MVWD 1
NA
1 x 185 Al 16.4
0

Project: New_project

In (A)
353

Copper
1x6 Copper
1x95
Copper
1x1.5
Copper
1x70
Copper
2x240
Copper

Copper
1x6 Copper
1x95
Copper
1x1.5
Copper
1x70
Copper
2x240
Copper

Copper
1x6 Copper
1x50
Copper
1x4 Copper
1x35
Copper
1x240
Copper

Un (kV)
24

04/09/2014

Page 6/28

3 Calculation notes
3.1 Source circuits
3.1.1 Circuit Source 0
MV power supply
W0
Max. upstream short circuit power 500 MVA
Min. upstream short circuit power 250 MVA
MV Cable
MVWD 0
Parameters
Length
10 m
Type of cable
Single core
Ib
18 A
Nb of conductor per phase
1
Cross section area
1 x 185 Al mm
Core
Aluminium
Short circuit withstand
16.4 kA
Assigned voltage
20 kV
Insulation voltage
24 kV
MV/LV transformer
Range
Technology
Rated power
ukrT
Type of losses
PkrT
System earthing arrangement
MV Connection
LV Connection
No load secondary voltage Ur0
Ur LV
Rb (neutral grounding)
Ra (mass grounding)
Sizing information
Cable
Parameters
Length
Max length
Installation method

TA 0
Trihal
Dry-type
630 kVA
6%
Normal
6.8 kW
TN-S
D
yn
420V
400V
NA
NA
UkrT and PkrT calculated by system
WD 0

5m
NA
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
909 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Project: New_project

04/09/2014

Page 7/28

1
A-52-14
1
A-52-16
1
D-52-1
0.88
A-52-20
1
0.88

Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

2x240 mm
Copper
947 A
2x240 mm
Copper
947 A
1x240 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 14.81
12.83

14.81

10.70

12.18

0.00 0.00

Operating mode Backup


(kA) 14.81
12.83

14.81

NA

NA

NA

10.70

12.18

0.00 0.00

Synthesis for all operating mode


(kA) 14.81
12.83
14.81

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Circuit breaker
QA 0
Ib
909 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Project: New_project

Sized by system
Masterpact NT
NT10H1
1000 A
42 kA
NA
NA
NA
4P4d
Micrologic 5.0 E
1000 A
920 A
24 s
04/09/2014

Page 8/28

Isd current
Tsd
Instantaneous tripping
Ii current

9200 A
0.08 s
12000 A

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 6
Circuit breaker
QA 6
Ib
221 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
NA
4P4d
Micrologic 2.2
250 A

RCD designation
Class
In
Break Time
t
Discrimination
Normative required break time
Normative required sensitivity

Vigi MH
A
30 mA
0.04 s
0s
NA
[0.00 ; 5.00] s
[0.03 ; 861.82] mA

Cable
Parameters
Length
Max length
Installation method

WD 6

225 A
16 s
2250 A
0.02 s
3000 A

25 m
NA
70
D
Multi-core cable in conduit or in cable
ducting in the ground
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Project: New_project

04/09/2014

Page 9/28

20 C
0%
221 A
Iz
Sized with Ir

Ground temperature
Level of third harmonic THDI
Ib
Sizing constraint
Sizing Information
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference

1
A-52-15
1
A-52-16
1
D-52-1
1
NA
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x120 mm
Copper
240 A
1x120 mm
Copper
240 A
1x70 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 14.61
12.66

14.42

9.00

8.61

8.07 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

9.00

8.61

8.07 0.00

Synthesis for all operating mode


(kA) 14.61
12.66
14.42

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
220.752
220.752

220.752

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
220.752
220.752

220.752

Project: New_project

04/09/2014

Page 10/28

Voltage drop
Cumulated from upstream

Circuit

Operating mode Normal


0.626
U3L (%)
0.723
UL1L2 (%)
0.723
UL2L3 (%)
0.723
UL3L1 (%)
0.626
UL1N (%)
0.626
UL2N (%)
0.626
UL3N (%)

0.502
0.579
0.579
0.579
0.502
0.502
0.502

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Project: New_project

04/09/2014

Page 11/28

3.2.2 Circuit Feeder circuit 12


Circuit breaker
QA 12
Ib
300 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX400F
400 A
36 kA
NA
NA
NA
4P4d
Micrologic 2.3
400 A

Cable
Parameters
Length
Max length
Installation method

WD 12

301 A
16 s
3008 A
0.02 s
4800 A

15 m
NA
31
F
Single-core cables on horizontal
perforated tray
Type of cable
Single-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
300 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
0.98
Standard table reference
A-52-21
User correction factor
1
Overall factor
0.98
Project: New_project

04/09/2014

Page 12/28

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x95 mm
Copper
335 A
1x95 mm
Copper
335 A
1x50 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 14.61
12.66

14.42

9.47

9.48

8.91 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

9.47

9.48

8.91 0.00

Synthesis for all operating mode


(kA) 14.61
12.66
14.42

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
300.000
300.000

300.000

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
300.000
300.000
300.000
Voltage drop
Cumulated from upstream

0
Circuit

Operating mode Normal


0.630
U3L (%)
0.727
UL1L2 (%)
0.727
UL2L3 (%)
0.727
UL3L1 (%)
0.630
UL1N (%)
0.630
UL2N (%)
0.630
UL3N (%)

0.505
0.584
0.584
0.584
0.505
0.505
0.505

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)

0.000
0.000
0.000
0.000
0.000

Project: New_project

04/09/2014

Page 13/28

UL2N (%)
UL3N (%)

Project: New_project

0.000
0.000

0.000
0.000

04/09/2014

Page 14/28

3.3 Generic load circuits


3.3.1 Circuit Load 3
Circuit breaker
QA 3
Ib
289 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX400F
400 A
36 kA
NA
NA
NA
4P4d
Micrologic 2.3
400 A

Cable
Parameters
Length
Max length
Installation method

WD 3

294 A
16 s
2944 A
0.02 s
4800 A

30 m
143 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
289 A
Sizing constraint
Iz
Sizing Information
Sized with In
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Project: New_project

04/09/2014

Page 15/28

1
A-52-20
1
1

Touching conductor factor


Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x185 mm
Copper
456 A
1x185 mm
Copper
456 A
1x95 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 14.61
12.66

14.42

9.01

8.74

8.24 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

9.01

8.74

8.24 0.00

Synthesis for all operating mode


(kA) 14.61
12.66
14.42

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
AA 3
U
400 V
S
200 kVA
P
170 kW
I
289 A
0.85
cos
Polarity
3Ph+N
Phase connection
Number of circuit
1
Ku (Normal)
1
Harmonic generator
No
THDI3
0%
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
288.675
288.675

288.675

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
288.675
288.675
288.675
Voltage drop
Cumulated from upstream
Project: New_project

0
Circuit
04/09/2014

Page 16/28

Operating mode Normal


0.690
U3L (%)
0.797
UL1L2 (%)
0.797
UL2L3 (%)
0.797
UL3L1 (%)
0.690
UL1N (%)
0.690
UL2N (%)
0.690
UL3N (%)

0.566
0.654
0.654
0.654
0.566
0.566
0.566

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


0.690
U3L (%)
0.797
UL1L2 (%)
0.797
UL2L3 (%)
0.797
UL3L1 (%)
0.690
UL1N (%)
0.690
UL2N (%)
0.690
UL3N (%)

Project: New_project

04/09/2014

Page 17/28

3.3.2 Circuit Load 9


Circuit breaker
QA 9
Ib
221 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX250B
250 A
25 kA
NA
NA
NA
4P4d
Micrologic 2.2
250 A

Cable
Parameters
Length
Max length
Installation method

WD 9

225 A
16 s
2250 A
0.02 s
3000 A

5m
103 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
221 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Project: New_project

04/09/2014

Page 18/28

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x70 mm
Copper
246 A
1x70 mm
Copper
246 A
1x35 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 12.48
10.81

10.57

8.56

7.82

6.91 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

8.56

7.82

6.91 0.00

Synthesis for all operating mode


(kA) 12.48
10.81
10.57

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
AA 9
U
400 V
S
153 kVA
P
130 kW
I
221 A
0.85
cos
Polarity
3Ph+N
Phase connection
Number of circuit
1
Ku (Normal)
1
Harmonic generator
No
THDI3
0%
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
220.752
220.752

220.752

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
220.752
220.752
220.752
Voltage drop
Cumulated from upstream
Operating mode Normal
0.783
U3L (%)
0.905
UL1L2 (%)
0.905
UL2L3 (%)
Project: New_project

0
Circuit
0.158
0.182
0.182
04/09/2014

Page 19/28

UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

0.905
0.783
0.783
0.783

0.182
0.158
0.158
0.158

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


0.783
U3L (%)
0.905
UL1L2 (%)
0.905
UL2L3 (%)
0.905
UL3L1 (%)
0.783
UL1N (%)
0.783
UL2N (%)
0.783
UL3N (%)

Project: New_project

04/09/2014

Page 20/28

3.3.3 Circuit Load 14


Circuit breaker
QA 14
Ib
50 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Acti9 iC60
iC60H
50 A
15 kA
NA
NA
NA
4P4d
C
50 A

Cable
Parameters
Length
Max length
Installation method

WD 14

50 A
NA
400 A
NA
NA

15 m
111 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
50 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Project: New_project

04/09/2014

Page 21/28

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x6 mm
Copper
54 A
1x6 mm
Copper
54 A
1x6 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 13.07
11.32

11.53

2.41

1.44

1.37 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

2.41

1.44

1.37 0.00

Synthesis for all operating mode


(kA) 13.07
11.32
11.53

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
AA 14
U
400 V
S
34.6 kVA
P
29.4 kW
I
50 A
0.85
cos
Polarity
3Ph+N
Phase connection
Number of circuit
10
Ku (Normal)
1
Harmonic generator
No
THDI3
0%
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
50.000
50.000

50.000

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
50.000
50.000
50.000
Voltage drop
Cumulated from upstream
Operating mode Normal
3.044
U3L (%)
3.515
UL1L2 (%)
3.515
UL2L3 (%)
Project: New_project

0
Circuit
1.104
1.274
1.274
04/09/2014

Page 22/28

UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.515
4.832
4.832
4.832

1.274
1.104
1.104
1.104

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


3.044
U3L (%)
3.515
UL1L2 (%)
3.515
UL2L3 (%)
3.515
UL3L1 (%)
4.832
UL1N (%)
4.832
UL2N (%)
4.832
UL3N (%)

Project: New_project

04/09/2014

Page 23/28

3.4 Power socket load circuits


3.4.1 Circuit Load 10
Circuit breaker
QA 10
Ib
20 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Acti9 iC60
iC60H
20 A
15 kA
NA
NA
NA
2P1d
C
20 A

Cable
Parameters
Length
Max length
Installation method

WD 10

20 A
NA
160 A
NA
NA

5m
20.5 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
XLPE
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
20 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Project: New_project

04/09/2014

Page 24/28

Standard table reference


User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-20
1
1

1x1.5 mm
Copper
26 A
1x1.5 mm
Copper
26 A
1x4 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 12.48
10.81

10.57

2.12

1.27

1.72 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

2.12

1.27

1.72 0.00

Synthesis for all operating mode


(kA) 12.48
10.81
10.57

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Charge
AA 10
U
400 V
S
4.62 kVA
P
3.93 kW
I
20 A
0.85
cos
Polarity
1Ph+N
Phase connection
L1-N
Number of circuit
1
Ku (Normal)
1
Harmonic generator
No
THDI3
0%
Design current
IL1
IL2
IL3
IN
Operating mode Normal
(A)
20.000
0.000

0.000

20

Operating mode Backup


(A)
0.000
0.000

0.000

Synthesis for all operating mode


(A)
20.000
0.000
0.000
Voltage drop
Cumulated from upstream

20
Circuit

Operating mode Normal


Project: New_project

04/09/2014

Page 25/28

U3L (%)
UL1L2 (%)
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

1.209
0.723
0.723
0.723
1.792
0.626
0.626

0.583
0.000
0.000
0.000
1.166
0.000
0.000

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Synthesis for all operating mode


1.209
U3L (%)
0.723
UL1L2 (%)
0.723
UL2L3 (%)
0.723
UL3L1 (%)
1.792
UL1N (%)
0.626
UL2N (%)
0.626
UL3N (%)

Project: New_project

04/09/2014

Page 26/28

3.5 Busbar circuits


3.5.1
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 1
WC 1
UC 2
No preference
0
Undefined
Protection name

Protection type

Load 3

QA 3

NSX400F

Feeder circuit 6

QA 6

NSX250B

Feeder circuit 12

QA 12

NSX400F

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 14.61
12.66

14.42

10.71

12.20

12.3 0.00
6

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

10.71

12.20

12.3 0.00
6

Synthesis for all operating mode


(kA) 14.61
12.66
14.42

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
3.5.2 Circuit WC 7
Busbar
WC 7
Parameters
Switchboard Name
UC 8
Switchboard Range
No preference
Rating (A)
0
IP
Undefined
Feeder
Circuit name
Protection name

Protection type

Load 9

QA 9

NSX250B

Load 10

QA 10

iC60H

Project: New_project

04/09/2014

Page 27/28

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 12.48
10.81

10.57

9.00

8.61

8.07 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

9.00

8.61

8.07 0.00

Synthesis for all operating mode


(kA) 12.48
10.81
10.57

Ief2min

NA

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.6 Busbar trunking system circuits


3.6.1 Circuit Distribution 13
Horizontal distribution
WC 13
Busway
Parameters
Length
40 m
Installation method
Standard
Ambiant temperature
35 C
Ib
300 A
System earthing arrangement
TN-S
Correction factor
Temperature factor
1
Installation factor
1
Protection factor
1
Chosen BTS
Designation
KSA400
Rating
400 A
Type of PE
Standard PE
IP
55
IK
08
Core
Aluminium
Icw
354000000 As
Ip
49.2 kA
Reinforced short circuit
NA
withstand
Feed unit position
End
Feeders
Distribution type
Uniform
Circuit
Protection Tap off unit

Protection type

Load 14

iC60H

QA 14

Withdrawable

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 13.07
11.32

11.53

6.58

4.72

4.29 0.00

Operating mode Backup


(kA) NA
NA

NA

NA

NA

NA

Project: New_project

Ief2min

NA
04/09/2014

Page 28/28

Synthesis for all operating mode


(kA) 13.07
11.32
11.53

6.58

4.72

4.29 0.00

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.
Voltage drop
Cumulated from upstream

Circuit

Operating mode Normal


1.940
U3L (%)
2.240
UL1L2 (%)
2.240
UL2L3 (%)
2.240
UL3L1 (%)
3.729
UL1N (%)
3.729
UL2N (%)
3.729
UL3N (%)

1.311
1.513
1.513
1.513
3.099
3.099
3.099

Operating mode Backup


0.000
U3L (%)
0.000
UL1L2 (%)
0.000
UL2L3 (%)
0.000
UL3L1 (%)
0.000
UL1N (%)
0.000
UL2N (%)
0.000
UL3N (%)

0.000
0.000
0.000
0.000
0.000
0.000
0.000

Project: New_project

04/09/2014