Chapter 29
Industrial Occupancies
First Revision No. 444:NFPA 5000-2012
[FR 8009: FileMaker]
FI
RS
DR
AF
FI
RS
DR
AF
(4)
Chapter 14, Safeguards During Construction
(5)
Chapter 31, Occupancies in Special Structures
(6)
Chapter 35, Structural Design
(7)
Chapter 36, Soils, Foundations, and Retaining Walls
(8)
Chapter 37, Exterior Wall Construction
(9)
Chapter 38, Roof Assemblies and Roof Structures
(10) Chapter 39, Flood-Resistant Design and Construction
(11) Chapter 40, Quality Assurance During Construction
29.1.6* Occupant Load. The occupant load, in number of persons for whom means of egress and
other provisions are required, shall be determined on the basis of the occupant load factors of Table
11.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum
probable population of the space under consideration, whichever is greater.
29.1.7 Accessibility. Accessibility shall be in accordance with Chapter 12.
29.1 General Requirements.
29.1.1 Application.
29.1.1.1* The requirements of this chapter shall apply to new buildings or portions thereof used as an
industrial occupancy.
29.1.1.2 Administration.Administration. The provisions of Chapter 1, Administration, shall apply.
29.1.1.3 General.29.1.1.3 General. The provisions of Chapter 4, General, shall apply.
29.1.1.4 Repairs, renovations, modifications, additions, and reconstruction of an industrial
occupancy, and changes of use, including change of occupancy classification to an industrial
occupancy, or correction of a damaged or unsafe portion of the building containing the industrial
occupancy, shall comply with one of the following:
(1)
Provisions of this chapter
(2)
Provisions of Chapter 15
29.1.2 Classification of Occupancy. Classification of occupancy shall be in accordance with
6.1.12.
29.1.2.1 Subclassification of Occupancy. Each industrial occupancy shall be subclassified
according to its use as described in 29.1.3.1.1 and 29.1.3.1.2.
29.1.2.1.1 General Industrial Occupancy. General industrial occupancies shall include all of the
following:
(1)
Industrial occupancies that conduct ordinary- and low-hazard industrial operations in buildings
of conventional design that are usable for various types of industrial processes
(2)
Industrial occupancies that include multistory buildings where floors are occupied by different
tenants or buildings that are usable for such occupancy and, therefore, are subject to possible use for
types of industrial processes with a high density of employee population
29.1.2.1.2 Special-Purpose Industrial Occupancy. Special-purpose industrial occupancies shall
include all of the following:
(1)
Industrial occupancies that conduct ordinary- and low-hazard industrial operations in buildings
designed for, and that are usable only for, particular types of operations
(2)
Industrial occupancies that are characterized by a relatively low density of employee
population, with much of the area occupied by machinery or equipment
29.1.2.2 Incidental Operations. Incidental high-hazard operations in low- or ordinary-hazard
occupancies that are protected in accordance with Section 8.15 and 29.3.2 shall not be the basis for
overall occupancy classification.
29.1.2.3 Change of Subclassification. A change from one subclassification of industrial occupancy
to another shall comply with Chapter 15.
RS
DR
AF
29.1.3 Multiple Occupancies. All multiple occupancies shall be in accordance with Section 6.2 and
29.1.2. Where there are differences in the specific requirements in this chapter and provisions for
mixed occupancies or separated occupancies as specified 6.2.3 and 6.2.4, the requirements of this
chapter shall apply. (See 4.3.2.3.)
29.1.4 Definitions
29.1.4.1 General. For definitions, see Chapter 3, definitions.
29.1.4.2 Special Definitions. Special terms application to this chapter are defined in Chapter 3.
29.1.4 Definitions
29.1.4.1 General. For definitions, see Chapter 3.
29.1.4.2 Special Definitions. Special terms applicable to this chapter are defined in Chapter 3.
29.1.5 Classification of Hazard of Contents.
29.1.5.1 Hazard of contents shall be classified in accordance with 6.3.2.
29.1.5.2 Buildings or areas in which high-hazard contents are stored, used, or handled shall comply
with Chapter 34.
29.1.6 Minimum Construction Requirements. Construction shall be in accordance with Chapters
78, 1314, 31, and 3540. all of the following:
(1)
Chapter 7, Construction Types and Height and Area Requirements
(2)
Chapter 8, Fire-Resistive Materials and Construction
(3)
Chapter 13, Encroachments into the Public Right-of-Way
(4)
Chapter 14, Safeguards During Construction
(5)
Chapter 31, Occupancies in Special Structures
(6)
Chapter 35, Structural Design
(7)
Chapter 36, Soils, Foundations, and Retaining Walls
(8)
Chapter 37, Exterior Wall Construction
(9)
Chapter 38, Roof Assemblies and Roof Structures
(10) Chapter 39, Flood-Resistant Design and Construction
(11) Chapter 40, Quality Assurance During Construction
29.1.7* Occupant Load. The occupant load, in number of persons for whom means of egress and
other provisions are required, shall be determined on the basis of the occupant load factors of Table
11.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum
probable population of the space under consideration, whichever is greater.
29.1.8 Accessibility. Accessibility shall be in accordance with Chapter 12.
FI
DR
AF
FI
RS
29.2.2.9 ReservedReserved.
29.2.2.910 Fire Escape Ladders.
29.2.2.910.1 Fire escape ladders in accordance with 11.2.9 shall be permitted.
29.2.2.910.2 Fixed industrial stairs in accordance with the minimum requirements for fixed stairs in
ANSI A1264.1, Safety Requirements for Workplace Floor and Wall Openings, Stairs and Railing
Systems, shall be permitted where fire escape ladders are permitted in accordance with 11.2.9.1.
29.2.2.1011 Slide Escapes. Approved slide escapes complying with 11.2.10 shall be permitted as
components in 100 percent of the required means of egress for high hazard industrial occupancies.
29.2.2.1112 Alternating Tread Devices. Alternating tread devices complying with 11.2.11 shall be
permitted.
29.2.2.1213 Areas of Refuge. Areas of refuge complying with 11.2.12 shall be permitted.
29.2.3 Capacity of Means of Egress. The capacity of means of egress shall comply with either of
the following:
(1)
The capacity of means of egress shall be in accordance with Section 11.3.
(2)
In special-purpose industrial occupancies, means of egress shall be sized to accommodate the
occupant load as determined in accordance with Table 11.3.1.2, and spaces not subject to human
occupancy because of the presence of machinery or equipment shall not be included.
First Revision No. 448:NFPA 5000-2012
[FR 8026: FileMaker]
29.2.4 Number of Means of Egress. See also 11.4.(See Section 11.4.)
29.2.4.1 The number of means of egress shall comply with 29.2.4.1.1 or 29.2.4.1.2.
29.2.4.1.1 Not less than two means of egress shall be provided from every story or section, and not
less than one exit shall be reached without traversing another story.
29.2.4.1.2 A single means of egress shall be permitted from any story or section in low and ordinary
hazard industrial occupancies, provided that the exit can be reached within the distance permitted as
common path of travel.
29.2.4.2 Floors, or portions thereof, with an occupant load of more than 500 shall have the minimum
number of separate and remote means of egress as specified by 11.4.1.2.
First Revision No. 448:NFPA 5000-2012
[FR 8027: FileMaker]
29.2.4.3 Areas with high-hazard contents shall comply with Section 11.11.
29.2.5 Arrangement of Means of Egress.
29.2.5.1 General. Means of egress shall be arranged in accordance with Section 11.5 and shall not
exceed that provided by Table 29.2.5.1.
AF
Low Hazard
Industrial
Occupancy
Industrial
Occupancy
Arrangement
ft
50
50
ft
15
50
15
15
50
15
30
100
30
DR
RS
100
FI
AF
Component
DR
Minimum horizontal
dimension of any walkway,
landing, or platform
RS
FI
Special-Purpose
Industrial
Occupancy
Arrangement
ft
ft
Protected throughout by an
approved, supervised
automatic sprinkler system in
accordance with NFPA 13 and
55.3.2
250
76
400
122
AF
DR
FI
RS
beyond the specified limits only where every floor level has direct access to one or more enclosed
stairs or other exits protected against obstruction by any fire or smoke in the open areas connected
by the unprotected vertical openings.
(23) Vertical Oopenings in accordance with 8.12.5.1 shall be permitted.
(3) Vertical Oopenings in accordance with 8.12.5.2 shall be permitted.
AF
DR
RS
FI
RS
DR
AF
(2)
It shall sound an audible and visible signal in a constantly attended location for the purposes of
initiating emergency action.
29.3.4.3.2 Positive alarm sequence in accordance with 55.2.3.4 shall be permitted.
29.3.5* Extinguishment Requirements.
29.3.5.1 Fire Sprinklers.
29.3.5.1.1 General. Industrial occupancies, other than low hazard industrial occupancies, shall be
protected by an approved automatic sprinkler system in accordance with NFPA 13 in any of the
following locations:
(1)
Throughout all industrial occupancies three or more stories in height
(2)
Throughout all industrial occupancies exceeding 12,000 ft2 (1115 m2) in fire area
(3)
Where the total area of all floors, including mezzanines, exceeds 24,000 ft2 (2230 m2)
29.3.5.1.2 Woodworking Operations. An approved automatic fire sprinkler system shall be
installed in buildings containing woodworking operations exceeding 2500 ft 2 (232 m2) that use
equipment, machinery, or appliances; that generate finely divided combustible waste; or that use
finely divided combustible materials.
29.3.5.1.3* Power-Generation Buildings. In lieu of providing sprinkler protection throughout in
accordance with 29.3.5.1, buildings of Type I or Type II construction used exclusively for the
enclosure of steam generators, steam turbines, gas turbines, heat recovery generators, and flue gas
treatment equipment shall not be required to be sprinklered throughout, provided that the special
hazards are protected by approved automatic suppression systems in accordance with NFPA 11,
NFPA 12, NFPA 13, NFPA 15, NFPA 16, NFPA 17, NFPA 750, or NFPA 2001.
29.3.5.1.4 Waterflow Alarms. Waterflow alarms shall be monitored in accordance with 55.3.2.2.
29.3.5.2 Standpipes. Standpipes shall be provided where required by 55.4.1.
29.3.5.3 Portable Fire Extinguishers. Portable fire extinguishers shall be installed in all industrial
occupancies in accordance with NFPA 1, Fire Code.
29.3.6 Corridors. The provisions of 11.1.3.1 shall not apply.
29.4 Special Provisions.
29.4.1 Limited Access or Underground Structures. Limited access or underground structures
shall comply with Chapter 31.
First Revision No. 456:NFPA 5000-2012
[FR 8031: FileMaker]
FI
10
Storage Occupancies
DR
Chapter 30
AF
29.6.1 The requirements of Sections 29.1 through 29.5 shall be met, except as modified by 29.6.2
through 29.6.4.
29.6.2 The requirements for exits from aircraft-servicing areas shall be as noted in 29.6.2.1 through
29.6.2.4.
29.6.12.1 Exits from aircraft-servicing areas shall be provided at intervals not exceeding 150 ft (46
m) on all exterior walls.
29.6.12.2 There shall be not less than two means of egress from each aircraft-servicing area.
29.6.12.3 If provided, horizontal exits shall be located at intervals not exceeding 100 ft (30 m).
29.6.12.4 If provided, dwarf, or smash, doors used in doors that accommodate aircraft shall be
permitted for compliance with the requirements of 29.6.1 through 29.6.2.3.
29.6.23 Requirements for means of egress from mezzanine floors in aircraft-servicing areas shall
be as noted in 29.6.3.1 and 29.6.3.2.
29.6.23.1 The means of egress shall be arranged so that the travel distance to the nearest exit from
any point on the mezzanine does not exceed 75 ft (23 m).
29.6.23.2 The means of egress shall lead directly to a properly enclosed stair discharging directly to
the exterior, to a suitable cutoff area, or to outside stairs.
29.6.34 Dead ends shall not exceed 50 ft (15 m) and shall not be permitted in areas containing
high-hazard contents exceeding the maximum allowable quantities (MAQ) per control area as set
forth in 34.1.3.
FI
RS
11
FI
RS
DR
AF
12
DR
AF
FI
RS
13
DR
AF
(1)
Noncombustible, grated stair treads and noncombustible, grated landing floors shall be
permitted.
(2)
Industrial equipment access in accordance with 29.2.5.3 shall be permitted.
30.2.2.3.2 Spiral stairs complying with 11.2.2.2.3 shall be permitted.
30.2.2.4 Smokeproof Enclosures. Smokeproof enclosures complying with 11.2.3 shall be
permitted.
30.2.2.5 Horizontal Exits.
30.2.2.5.1 Horizontal exits complying with 11.2.4 shall be permitted.
30.2.2.5.2* In horizontal exits, where the opening is protected by a fire door assembly on each side of
the wall in which it is located, one fire door shall be of the swinging type as provided in 11.2.4.3.8,
and the other shall be permitted to be an automatic-sliding fire door that shall be kept open whenever
the building is occupied.
30.2.2.6 Ramps. Ramps complying with any of the following shall be permitted:
(1)
Ramps in accordance with 11.2.5
(2)
Industrial equipment access in accordance with 29.2.5.3
30.2.2.7 Exit Passageways. Exit passageways complying with 11.2.6 shall be permitted.
30.2.2.8 Fire Escape Ladders.
30.2.2.8.1 Fire escape ladders in accordance with 11.2.9 shall be permitted.
30.2.2.8.2 Fixed industrial stairs in accordance with the minimum requirements for fixed stairs in
ANSI A1264.1, Safety Requirements for Workplace Floor and Wall Openings, Stairs and Railing
Systems, shall be permitted where fire escape ladders are permitted in accordance with 11.2.9.1.
30.2.2.9 Alternating Tread Devices. Alternating tread devices complying with 11.2.11 shall be
permitted.
30.2.2.10 Areas of Refuge. Areas of refuge complying with 11.2.12 shall be permitted.
30.2.3 Capacity of Means of Egress. The capacity of means of egress shall be in accordance with
Section 11.3.
FI
RS
14
Storage
Occupancy
Low Hazard
Storage
Occupancy
ft
Protected throughout by an
approved, supervised automatic
sprinkler system in accordance with
NFPA 13 and 55.3.2
No limits
100
30
No limits
50
15
Arrangement
100
30
AF
Protected throughout by an
approved, supervised automatic
sprinkler system in accordance with
NFPA 13 and 55.3.2
Dead-End Corridor
DR
ft
Unlimited
400
122
Unlimited
200
60
RS
Low Hazard
Storage
Occupancy
Arrangement
FI
Protected throughout by an
approved, supervised automatic
sprinkler system in accordance
with NFPA 13 and 55.3.2
Not protected throughout by an
approved, supervised automatic
sprinkler system in accordance
with NFPA 13 and 55.3.2
Storage Occupancy
15
AF
DR
FI
RS
16
FI
RS
DR
AF
30.3.4.3.1 The required fire alarm system shall meet one of the following criteria:
(1)
It shall provide occupant notification in accordance with 55.2.3.
(2)
It shall sound an audible and visible signal in a constantly attended location for the purposes of
initiating emergency action.
30.3.4.3.2 Positive alarm sequence in accordance with 55.2.3.4 shall be permitted.
30.3.5* Extinguishment Requirements.
30.3.5.1 Fire Sprinklers.
30.3.5.1.1 Storage occupancies, other than low hazard storage occupancies, shall be protected by
an approved, supervised automatic sprinkler system in accordance with NFPA 13, Standard for the
Installation of Sprinkler Systems, in any of the following locations:
(1)
Throughout all storage occupancies three or more stories in height
(2)
Throughout all storage occupancies exceeding 12,000 ft2 (1115 m2) in fire area
(3)
Where the total area of all floors, including mezzanines, exceeds 24,000 ft2 (2230 m2)
30.3.5.1.2 Waterflow alarms shall be monitored in accordance with 55.3.2.2.
30.3.5.2 Bulk Storage of Tires. Buildings and structures where the volume for the storage of tires
exceeds 20,000 ft3 (566 m3) shall be equipped throughout with an approved automatic fire sprinkler
system.
30.3.5.3 Mini-Storage Building. An automatic sprinkler system shall be installed throughout all
mini-storage buildings greater than 2500 ft2 (232 m2) and where any of the individual storage units
are separated by less than a 1-hour fire resistancerated barrier.
30.3.5.4 Standpipes. Standpipes shall be provided where required by 55.4.1.
30.3.5.5 Portable Fire Extinguishers. Portable fire extinguishers shall be installed in storage
occupancies in accordance with NFPA 1, Fire Code.
30.3.6 Corridors. Corridors shall not be required to comply with the provisions of 11.1.3.1.
30.4 Special Provisions.
30.4.1 Limited Access or Underground Structures. Limited access or underground structures
shall comply with Chapter 31.
30.4.2 High-Rise Buildings. High-rise buildings shall comply with the requirements of Chapter 33.
30.5 Building Services.
30.5.1 Utilities. Utilities shall comply with the provisions of Chapters 49, 52, and 53.
30.5.2 Heating, Ventilating, and Air-Conditioning. Heating, ventilating, and air-conditioning
equipment shall comply with the provisions of Chapters 50 and 51.
30.5.3 Elevators, Escalators, and Conveyors. Elevators, escalators, and conveyors shall comply
with the provisions of Chapter 54.
30.5.4 Rubbish Chutes, Incinerators, and Laundry Chutes. Rubbish chutes, incinerators, and
laundry chutes shall comply with the provisions of Section 8.17.
30.6* Special Provisions for Aircraft Storage Hangars.
30.6.1 The requirements of Sections 30.1 through 30.5 shall be met, except as modified by 30.6.2
through 30.6.4.
30.6.2 The requirements for exits from aircraft storage areas shall comply with 30.6.2.1 through
30.6.2.3.
30.6.2.1 There shall be not less than two means of egress serving each aircraft storage area.
30.6.2.2 Exits from aircraft storage areas shall be provided at intervals not exceeding 150 ft (46 m)
on all exterior walls.
30.6.2.3 If provided, horizontal exits through interior fire walls shall be located at intervals not
exceeding 100 ft (30 m).
30.6.2.4 If provided, dwarf, or smash, doors used in doors that accommodate aircraft shall be
permitted for compliance with the requirements of 30.6.1 through 30.6.3.
17
DR
AF
30.6.3 Means of egress from mezzanine floors in aircraft storage areas shall comply with all of the
following:
(1)
They shall be arranged so that the travel distance to the nearest exit from any point on the
mezzanine does not exceed 75 ft (23 m).
(2)
They shall lead directly to a properly enclosed stair discharging directly to the exterior, to a
suitable cutoff area, or to outside stairs.
30.6.4 Dead ends shall not exceed 50 ft (15 m), and dead ends shall not be permitted in areas
containing high hazard contents exceeding the maximum allowable quantities (MAQ) per control area
as set forth in 34.1.3.
30.7* Special Provisions for Grain or Other Bulk Storage Elevators.
30.7.1 General. The requirements of Section 30.1 through Section 30.5 shall be met, except as
modified by 30.7.2 through 30.7.4.
30.7.2 Number of Means of Egress. There shall be not less than two means of egress from all
working levels of the head house, as modified by 30.7.2.1 and 30.7.2.2.
30.7.2.1 One of the means of egress specified in 30.7.2 shall be a stair to the level of exit discharge,
and, if this means of egress is interior to the structure, it shall be enclosed by a dust-resistant, 1-hour
fire resistancerated enclosure in accordance with 11.1.3.2. Exterior stair means of egress shall be
protected from the structure by a 1-hour fire resistancerated wall that extends at least 10 ft (3050
mm) beyond the stair.
30.7.2.2 The second means of egress specified in 30.7.2 shall be one of the following:
(1)
Exterior stair or basket laddertype fire escape, accessible from all working levels of the
structure, that provides a passage to the finished ground level
(2)
Exterior stair or basket laddertype fire escape, accessible from all working levels of the
structure, that provides access to adjoining structures and that provides a continuous path to the
means of egress described in 30.7.3
30.7.2.3 Stair enclosures in existing structures shall be permitted to have non-fire-rated dustresistant enclosures.
30.7.3 Means of Egress to Finished Ground Level. An exterior stair or basket laddertype fire
escape shall provide passage to the finished ground level from the top of the end of an adjoining
structure, such as a silo, conveyor, gallery, or gantry.
FI
RS
18
ft
400
122
200
61
FI
RS
DR
AF
19
DR
AF
FI
RS
30.8.2.2.3 Stairs.
30.8.2.2.3.1 Stairs complying with 11.2.2 shall be permitted unless otherwise permitted by
30.8.2.2.3.2.
30.8.2.2.3.2 In open parking structures, stairs complying with 11.2.2.5.1 shall not be required.
30.8.2.2.3.23 The requirement of 11.2.2.4.6.3(2) shall not apply to guards for parking structures that
are accessible to the general public.
30.8.2.2.4 Smokeproof Enclosures. Smokeproof enclosures complying with 11.2.3 shall be
permitted.
30.8.2.2.5 Horizontal Exits. Horizontal exits complying with 11.2.4 shall be permitted.
30.8.2.2.6 Ramps.
30.8.2.2.6.1 Ramps shall be permitted in accordance with any of the following conditions:
(1)
Ramps complying with 11.2.5 and not subject to normal vehicular traffic where used as an exit
shall be permitted.
(2)
In a ramp-type open parking structure with open vehicle ramps not subject to closure, the ramp
shall be permitted to serve in lieu of the second means of egress from floors above the level of exit
discharge, provided that the ramp discharges directly outside at the street level.
(3)
For parking structures extending only one floor level below the level of exit discharge, a vehicle
ramp leading directly to the outside shall be permitted to serve in lieu of the second means of egress,
provided that no door or shutter is installed therein.
20
30.8.2.2.6.2 Paragraph 11.2.2.4.6.3(2) shall not apply to guards for parking garages that are
accessible to the general public.
30.8.2.2.7 Exit Passageways. Exit passageways complying with 11.2.6 shall be permitted.
First Revision No. 467:NFPA 5000-2012
[FR 8019: FileMaker]
30.8.2.2.8 Areas of Refuge.
30.8.2.2.8.1 Areas of refuge complying with 11.2.12 shall be permitted.
30.8.2.2.8.2 In open-air parking structures, the area of refuge requirements of 11.2.12.1.2(2) shall
not apply.
30.8.2.3 Capacity of Means of Egress. See also 30.8.2.4 and 30.8.2.5.
AF
FI
RS
DR
Enclosed
Parking
Structure
Arrangement
Protected
21
Open Parking
Structure
Parking
Structure
Open Not Less
than 50 Percent on
All Sides
ft
ft
ft
200
61
400
122
400
122
throughout by an
approved,
supervised
automatic sprinkler
system in
accordance with
NFPA 13 and 55.3.2
RS
DR
AF
Not protected
150
46
300
91
400
122
throughout by an
approved,
supervised
automatic sprinkler
system in
accordance with
NFPA 13 and 55.3.2
30.8.2.6.2 In open parking structures, travel distance shall comply with one of the following:
(1)
The travel distance to an exit shall not exceed the travel distance specified in Table 30.8.2.6.1.
(2)
The travel distance to a stair that does not meet the provisions for an exit enclosure shall not
exceed the travel distance specified in Table 30.8.2.6.1 and travel along the stair shall not be limited.
30.8.2.7 Discharge from Exits. Exit discharge shall comply with Section 11.7.
30.8.2.8 Illumination of Means of Egress. Means of egress shall be illuminated in accordance with
Section 11.8 or with natural lighting that provides the required level of illumination in structures
occupied only during daylight hours.
30.8.2.9 Emergency Lighting. Parking structures shall be provided with emergency lighting in
accordance with Section 11.9, except in structures occupied only during daylight hours and arranged
to provide the required level of illumination of all portions of the means of egress by natural means.
30.8.2.10 Marking of Means of Egress. Means of egress shall have signs in accordance with
Section 11.10.
30.8.2.11 Special Means of Egress Features. (Reserved)
30.8.3 Protection.
30.8.3.1 Protection of Vertical Openings.
FI
22
DR
AF
FI
RS
23
DR
AF
(3)
Approved, supervised automatic sprinkler system complying with Section 55.3 and 55.3.2 and
in accordance with 55.2.2(3) that provides protection throughout the building and in accordance with
55.2.2.1.6
30.8.3.4.3 Notification.
30.8.3.4.3.1 The required fire alarm system shall sound an audible alarm in a continuously attended
location for purposes of initiating emergency action.
30.8.3.4.3.2 Positive alarm sequence in accordance with 55.2.3.4 shall be permitted.
30.8.3.5 Extinguishment Requirements.
30.8.3.5.1 Automatic sprinkler systems, where required, shall conform to NFPA 13. Electronic
supervision of supervisory signals shall be provided in accordance with 55.3.2.1. Waterflow alarms
shall be monitored in accordance with 55.3.2.2.
30.8.3.5.2 Automatic sprinkler systems shall be installed in portions of enclosed parking structures,
the ceilings of which are less than 24 in. (610 mm) above grade, regardless of type of construction,
and in enclosed parking structures of Type III or Type IV construction over 50 ft (15 m) in height.
[88A:6.1.4]
30.8.3.5.3 Enclosed parking structures located at or above grade plane, within or immediately below
a building used for another occupancy, shall have an approved, automatic sprinkler system
throughout the parking structure.
30.8.3.5.4 Standpipes.
30.8.3.5.4.1 Class I standpipe systems shall be provided when required by 55.4.1, as modified by
30.8.3.5.4.2.
30.8.3.5.4.2 In open parking structures of any height, Class I standpipe systems of the manual, dry
type shall be permitted.
30.8.3.6 Corridors. Corridors shall not be required to comply with the provisions of 11.1.3.1.
FI
RS
24
31.1.2 Where there are differences in the specific requirements in this chapter and provisions for
mixed occupancies or separated occupancies as specified in 6.2.3 and 6.2.4, the requirements of this
chapter shall apply. (See 4.3.2.3.)
First Revision No. 504:NFPA 5000-2012
[FR 8037: FileMaker]
AF
31.1.3 Definitions.
31.1.3.1 General. For definitions see Chapter 3. Definitions.
31.1.3.2 Special Definitions. Special terms used in this chapter are located within each special
structure section.
31.1.4 Classification of Occupancy. Occupancies regulated by Chapters 15 through 31 that are in
special structures shall meet the requirements of those chapters, except as modified by this chapter.
31.1.5 Classification of Hazard of Contents. Classification of hazard of contents shall be in
accordance with Section 6.3.
31.1.6 Minimum Construction Requirements. Minimum construction requirements shall be in
accordance with the applicable occupancy chapter.
31.1.7 Occupant Load. The occupant load of special structures shall be based on the use of the
structure as regulated by Chapters 15 through 31.
31.2 Underground Structures.
DR
RS
31.2.1 3Where underground structures have an occupant load of more than 50 persons in the
underground portions of the structure, the underground portions, and all areas and floor levels
traversed in traveling to the exit discharge, shall be protected by an approved, supervised automatic
sprinkler system installed in accordance with NFPA 13, Standard for the Installation of Sprinkler
Systems, and 55.3.2.
31.2.24 Underground portions of structures, and all areas traversed in traveling to the exit discharge,
shall be provided with emergency lighting in accordance with Section 11.9.
FI
25
AF
below the lowest level of exit discharge, shall be provided with outside smoke-venting facilities or
other means to prevent the exits from becoming charged with smoke from any fire in the areas served
by the exits.
31.2.46 The underground portions of an underground structure shall be provided with approved,
automatic smoke control in accordance with Section 55.7 where the underground structure has all of
the following:
(1)
Occupant load of more than 100 persons in the underground portions of the structure
(2)
Floor level used for human occupancy of more than 30 ft (9.1 m) below or more than one level
below, the lowest level of exit discharge
(3)
Combustible contents, combustible interior finish, or combustible construction
31.2.57 Exit stair enclosures in underground structures having a floor level used for human
occupancy of more than 30 ft (9.1 m) below, or more than one level below, the lowest level of exit
discharge shall be provided with signage in accordance with 11.2.2.6 at each floor level landing
traversed in traveling to the exit discharge. The signs shall include a chevron-shaped indicator to
show direction to the exit discharge.
31.3 Limited Access Structures.
31.3.1 Special Provisions for Limited Access Structures.
FI
RS
DR
26
AF
DR
FI
RS
31.5.2.93 Protection.
31.5.2.93.1 Protection of Vertical Openings. Open structures shall be exempt from protection of
vertical opening requirements.
31.5.2.93.2 Hazardous Area Protection. Every open structure, other than structures with only
occasional occupancy, shall have automatic, manual, or other protection as appropriate for the
particular hazard that is designed to minimize danger to occupants in case of fire or other emergency
before the occupants have time to utilize the means of egress.
31.5.2.104 Detection, Alarm, and Communications Systems. Open structures shall be exempt
from requirements for detection, alarm, and communications systems.
31.6 Towers.
First Revision No. 510:NFPA 5000-2012
[FR 8042: FileMaker]
31.6.1 Application.
31.6.1.1 General. The provisions of Section 31.1 shall apply.
31.6.1.2 Special Definition Tower. See 3.3.xxx.(See 3.3.654.)
31.6.1.3 Use of Accessory Levels.31.6.1.3 Use of Accessory Levels.
31.6.1.131.6.3.1 Sprinklered Towers. In towers protected throughout by an automatic sprinkler
system in accordance with NFPA 13, the levels located below the observation level shall be permitted
to be occupied only for any of the following uses that support tower operations:
(1)
Electrical and mechanical equipment rooms, including emergency power
27 Balloting Version: First Draft Proposed 2015 Edition NFPA 5000
(2)
Radar, communications, and electronics rooms
(3)*(3)*
Incidental accessory uses
31.6.1.231.6.3.2 Electronic supervision of supervisory signals shall be provided in accordance with
55.3.2.1. Waterflow alarms shall be monitored in accordance with 55.3.2.2.
31.6.1.331.6.3.3 Nonsprinklered Towers. The levels located within a tower below the observation
level and equipment room for that level in nonsprinklered towers shall not be occupied.
First Revision No. 511:NFPA 5000-2012
[FR 8043: FileMaker]
FI
RS
DR
AF
28
FI
RS
DR
AF
31.6.6 Travel Distance to Exits. Towers in which ladders are permitted by 31.6.3.1 shall be exempt
from travel distance limitations.
31.6.7 Discharge from Exits. Towers permitted to have a single exit per 31.6.5.1 shall be permitted
to have 100 percent of the exit discharge through areas on the level of exit discharge.
31.6.8 Illumination of Means of Egress. Towers in which ladders are permitted per 31.6.3.1 shall
be exempt from illumination of means of egress requirements.
31.6.9 Emergency Lighting.
31.6.9.1 Towers in which ladders are permitted per 31.6.3.1 shall be exempt from emergency
lighting requirements.
31.6.9.2 Locations not routinely inhabited by humans shall be exempt from emergency lighting
requirements.
31.6.9.3 Structures occupied only during daylight hours, with windows arranged to provide the
required level of illumination of all portions of the means of egress during such hours, shall be exempt
from emergency lighting requirements where approved by the authority having jurisdiction.
31.6.10 Marking of Means of Egress.
31.6.10.1 Towers in which ladders are permitted per 31.6.3.1 shall be exempt from marking of
means of egress requirements.
31.6.10.2 Locations not routinely inhabited by humans shall be exempt from marking of means of
egress requirements.
31.6.11 Protection.
31.6.11.1 Protection of Vertical Openings.
31.6.11.1.1 Towers in which ladders are permitted per 31.6.3.1 shall be exempt from protection of
vertical opening requirements.
31.6.11.1.2 In towers where the support structure is open and no occupancy is located below the top
floor level, stairs shall be permitted to be open with no enclosure required, or fire escape stairs shall
be permitted.
31.6.11.2 Hazardous Area Protection. Every tower, other than towers with only occasional
occupancy, shall have automatic, manual, or other protection as appropriate for the particular hazard
that is designed to minimize danger to occupants in case of fire or other emergency before the
occupants have time to utilize the means of egress.
31.6.12 Detection, Alarm, and Communications Systems. Towers designed for occupancy by not
more than three persons shall be exempt from requirements for detection, alarm, and
communications systems.
31.6.13 Additional Requirements for Air Traffic Control Towers.
31.6.13.1 Definition Air Traffic Control Tower. See 3.3.654.1.
31.6.13.2 Use of Accessory Levels. The levels located below the observation level shall be
permitted to be occupied only for the following uses that support tower operations:
(1)
Use as electrical and mechanical equipment rooms, including emergency and standby power,
radar, communications, and electronics rooms
(2)* Incidental accessory uses
31.6.13.3 Minimum Construction Requirements. Air traffic control towers shall be of Type I or
Type II construction. (See 7.2.1.)
31.6.13.4 Means of Egress.
31.6.13.4.1 Number of Means of Egress. Air traffic control towers shall be permitted to have a
single exit, provided that the following conditions are met in addition to the requirements of 31.6.5:
(1)
Each level of air traffic control towers, served by a single exit, shall be subject to a calculated
occupant load of 15 or fewer persons.
29
DR
AF
(2)
Smoke detection shall be provided throughout air traffic control towers to meet the
requirements of partial coverage, as defined in 5.5.2.2 of NFPA 72, National Fire Alarm and Signaling
Code, and shall include coverage of all of the following:
(a)
Occupiable areas
(b)
Common areas
(c)
Work spaces
(d)
Equipment areas
(e)
Means of egress
(f)
Accessible utility shafts
(3)
The requirements of 31.6.5.1(5) shall not apply.
(4)
Rooms or spaces used for the storage, processing, or use of combustible supplies shall be
permitted in quantities deemed acceptable by the authority having jurisdiction.
31.6.13.4.2 Egress for Occupant Load. Means of egress for air traffic control towers shall be
provided for the occupant load, as determined in accordance with 11.3.1.
31.6.13.4.3 Areas Excluded from Occupant Load. Shafts, stairs, and spaces and floors not
subject to human occupancy shall be excluded from consideration in determining the total calculated
occupant load of the tower, as required by 31.6.5.1(1) and 31.6.13.4.1(1).
31.6.13.4.4 Single Means of Egress. A single means of egress shall be permitted from the
observation level of an air traffic control tower, as permitted by 31.6.5.2.
31.6.13.4.5 Smokeproof Enclosures. Smokeproof exit enclosures complying with 11.2.3 shall be
provided for all air traffic control tower exit stair enclosures.
31.6.13.4.6 Discharge from Exits.
31.6.13.4.6.1 Air traffic control towers shall comply with the requirements of 11.7.2, except as
permitted by 31.6.13.4.6.2.
FI
RS
30
31.6.13.5.3 Standpipe Requirements. New air traffic control towers where the floor of the cab is
greater than 30 ft (9.1 m) above the lowest level of fire department vehicle access shall be protected
throughout with a Class I standpipe system in accordance with Section 55.4. Class I standpipes shall
be permitted to be manual standpipes, as defined in NFPA 14, Standard for the Installation of Standpipe
and Hose Systems, where the authority having jurisdiction has been determined to have sufficient
capabilities to supply the system.
31.6.13.6 Prohibited Uses. Sleeping areas shall be prohibited in air traffic control towers.
31.7 Water-Surrounded Structures.
First Revision No. 515:NFPA 5000-2012
[FR 8048: FileMaker]
AF
31.7.1 Application.
31.7.1.1 General. The provisions of Sections 31.1 and 31.7 shall apply to those structures that are
not under the jurisdiction of the U.S. Coast Guard and are designed and arranged in accordance with
U.S. Coast Guard regulations.
31.7.1.2 Definition Water-Surrounded Structure. See 3.3.xxx.(See 3.3.632.17.)
31.7.2.1 General. The means of egress provisions of Chapter 11 shall apply, except as modified by
31.7.2.2 through 31.7.2.5.
RS
DR
FI
31.7.3 Protection.
31.7.3.1 Protection of Vertical Openings.
31.7.3.2 Hazardous Area Protection. Every water-surrounded structure, other than structures with
only occasional occupancy, shall have automatic, manual, or other protection as appropriate for the
particular hazard that is designed to minimize danger to occupants in case of fire or other emergency
before the occupants have time to use the means of egress.
31.8* Piers.
First Revision No. 522:NFPA 5000-2012
[FR 8051: FileMaker]
31.8.1 Application. The provisions of Section 31.1 shall apply.
31.8.12 Number of Means of Egress.
31.8.2.1 Piers used exclusively to moor cargo vessels and to store material shall be exempt from
number of means of egress requirements where provided with proper means of egress from
31
FI
RS
DR
AF
structures thereon to the pier and a single means of access to the mainland, as appropriate with the
pier's arrangement.
31.8.2 Arrangement of Means of Egress.
31.8.2.12 Piers not meeting the requirements of 31.8.1 and occupied for other than cargo handling
and storage shall have means of egress arranged in accordance with Chapter 11.
31.8.2.23 In addition to the requirement of 31.8.2.1, one of the following measures shall be provided
on piers extending over 150 ft (46 m) from shore to minimize the possibility that fire under or on the
pier will block escape of occupants to shore:
(1)
The pier shall be arranged to provide two separate ways to travel to shore, such as two wellseparated walkways or independent structures.
(2)
The pier deck shall be open, fire resistive, and set on noncombustible supports.
(3)
The pier shall be open and unobstructed and shall be 50 ft (15 m) or more in width if less than
500 ft (150 m) long, or its width shall be not less than 10 percent of its length if over 500 ft (150 m)
long.
(4)
The pier deck shall be provided with an approved automatic sprinkler system in accordance
with Section 55.3 that protects the combustible substructure and all superstructures, and the sprinkler
system shall be supervised if the applicable occupancy chapter requires supervision of sprinkler
systems.
31.9 Helistops.
31.9.1 Helistops shall comply with all of the following:
(1)
Helistops shall be permitted to be erected on buildings or at other locations where constructed
in accordance with the requirements of Section 31.9 and NFPA 418, Standard for Heliports.
(2)
Where erected on buildings, helistops shall be designed in accordance with Chapter 35 for
design live and dead loads and as specified in Chapter 7 for materials of construction.
31.9.2 Touchdown or landing areas for helicopters shall comply with all of the following:
(1)
The touchdown or landing area for helicopters weighing less than 3500 lb (1587.6 kg) shall be
a minimum of 20 ft 20 ft (6.1 m 6.1 m) in area.
(2)
The landing area shall be surrounded on all sides by a clear area having a minimum average
width at roof level of 15 ft (4.6 m), but with no width less than 5 ft (1.5 m).
(3)
For helicopters weighing more than 3500 lb (1587.6 kg), special requirements shall be met as
determined by the authority having jurisdiction.
31.9.3 Helicopter landing areas, and the supports thereof on the roof of a building, shall be of
noncombustible construction.
31.9.4 Landing areas shall be designed to confine any spillage of flammable liquid to the landing
area.
31.9.5 Provision shall be made to drain the spillage specified in 31.9.4 away from exits and
stairways.
31.9.6 Exits from helistops shall conform to the requirements of Chapter 11.
31.9.7 Guardrails shall be provided around all roofs or decks and shall comply with the requirements
of 11.2.2.4.
31.9.8 Before operating helicopters from rooftops is permitted, written approval of the Federal
Aviation Agency shall be presented to the authority having jurisdiction.
Chapter 34
32
FI
RS
DR
AF
34.1.1.2 Buildings, and portions thereof, containing high hazard contents limited to any of the
following shall not be required to comply with this chapter:
(1)
Flammable and combustible liquids associated with application of flammable finishes and
complying with NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials,
and NFPA 34, Standard for Dipping, Coating, and Printing Processes Using Flammable or
Combustible Liquids
(2)
Flammable and combustible liquids associated with wholesale and retail sales and storage in
mercantile occupancies and complying with NFPA 30, Flammable and Combustible Liquids Code
(3)
Class IIIA and Class IIIB combustible liquid solvents in closed systems employing listed
cleaning equipment complying with NFPA 32, Standard for Drycleaning Plants
(4)
Refrigerants and refrigerant oil contained within closed-cycle refrigeration systems complying
with NFPA 1, Fire Code, and the Uniform Mechanical Code, as referenced in Chapter 50
(5)
Flammable and combustible liquid beverages in liquor stores and distributors without bulk
storage
(6)
High hazard contents stored or used in farm buildings or similar occupancies for on-premise
agricultural use
(7)
Corrosive materials in stationary batteries utilized for facility emergency power, uninterrupted
power supply, or similar purposes, provided that the batteries are provided with safety venting caps
and ventilation is provided in accordance with NFPA 1
(8)
Corrosive materials displayed in original packaging in mercantile occupancies and intended for
personal or household use or as building materials
(9)
Aerosol products in storage or mercantile occupancies and complying with NFPA 30B, Code
for the Manufacture and Storage of Aerosol Products
(10) Flammable and combustible liquids storage tank buildings meeting the requirements of 2.3.4 of
NFPA 30
(11) Flammable and combustible liquids storage tank vaults meeting the requirements of 2.2.7 of
NFPA 30
(12) Flammable and combustible liquids process buildings meeting the requirements of Section 5.3
of NFPA 30
(13) Installation of fuel gas distribution systems and associated equipment in accordance with
NFPA 54, National Fuel Gas Code, and NFPA 58, Liquefied Petroleum Gas Code, as adopted by
Chapters 49 and 50
(14) Consumer fireworks, 1.4G, in mercantile occupancies complying with NFPA 1124, Code for
the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles
34.1.2 Material Classification.
34.1.2.1 General. Hazardous materials shall be classified in accordance with 6.3.2.4 and the
definitions in Chapter 3.
34.1.2.2 Multiple Hazards. Buildings, and portions thereof, containing high hazard contents that are
classified in more than one hazard level, as set forth in 6.3.2.4, shall conform to the code
requirements for each of the applicable protection levels specified in Section 34.3.
First Revision No. 474:NFPA 5000-2012
[FR 8033: FileMaker]
33
FI
RS
DR
AF
34.1.2.3.42* Highly Toxic Material. A material that produces a lethal dose or lethal concentration
that falls within any of the following categories: (1) a chemical that has a median lethal dose (LD50) of
50 mg/kg or less of body weight when administered orally to albino rats weighing between 200 g and
300 g each; (2) a chemical that has a median lethal dose (LD50) of 200 mg/kg or less of body weight
when administered by continuous contact for 24 hours, or less if death occurs within 24 hours, with
the bare skin of albino rabbits weighing between 2 kg and 3 kg each or albino rats weighing 200 g to
300 g each; (3) a chemical that has a median lethal concentration (LC50) in air of 200 parts per
million by volume or less of gas or vapor, or 2 mg/L or less of mist, fume, or dust, when administered
by continuous inhalation for 1 hour, or less if death occurs within 1 hour, to albino rats weighing
between 200 g and 300 g each. [400,400, 2013]
34.1.2.3.3* Incompatible Material. Materials that, when in contact with each other, have the
potential to react in a manner that generates heat, fumes, gases, or by-products that are hazardous
to life or property. [400,400, 2010 2013]
34.1.2.3.14 Physical Hazard Material. A chemical or substance classified as a combustible liquid,
explosive, flammable cryogen, flammable gas, flammable liquid, flammable solid, organic peroxide,
oxidizer, oxidizing cryogen, pyrophoric, unstable (reactive), or water-reactive material. [400,400,
2013]
34.1.2.3.65 Pyrophoric Material. A chemical with an autoignition temperature in air at or below
130F (54.4C). [400,400, 2013]
34.1.2.3.5* Toxic Material.34.1.2.3.6* Toxic Material. A material that produces a lethal dose or a
lethal concentration within any of the following categories: (1) a chemical or substance that has a
median lethal dose (LD50) of more than 50 mg/kg but not more than 500 mg/kg of body weight when
administered orally to albino rats weighing between 200 g and 300 g each; (2) a chemical or
substance that has a median lethal dose (LD50) of more than 200 mg/kg but not more than 1000
mg/kg of body weight when administered by continuous contact for 24 hours, or less if death occurs
within 24 hours, with the bare skin of albino rabbits weighing between 2 kg and 3 kg each, or albino
rats weighing 200 g to 300 g each; (3) a chemical or substance that has a median lethal
concentration (LC50) in air of more than 200 parts per million but not more than 2000 parts per million
by volume of gas or vapor, or more than 2 mg/L but not more than 20 mg/L, of mist, fume, or dust
when administered by continuous inhalation for 1 hour, or less if death occurs within 1 hour, to albino
rats weighing between 200 g and 300 g each. [400,400, 2013]
34.1.2.3.7* Water-Reactive Material. A material that explodes; violently reacts; produces flammable,
toxic, or other hazardous gases; or evolves enough heat to cause self-ignition or ignition of nearby
combustibles upon exposure to water or moisture. [400,400, 2013]
34.1.3 Quantity Limits.
34.1.3.1* General. Maximum allowable quantities (MAQ) of hazardous materials per control area
shall be as specified in Table 34.1.3.1, except as modified by 34.1.3.2, 34.1.3.3, or 34.1.3.4.
Table 34.1.3.1 Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Areaa
Storage
Material
34
Class
Use-Closed Systems
Use-Open
Systems
High
Hazard Solid Liquid
Solid Liquid Gasb Solid Liquid
Protectio Pound Gallon Gasb ft3 Pound Gallon ft3 (lb) Pound Gallon
n Level
s
s (lb) (lb) [gal]
s
s (lb) [gal] s (ft3) s (lb)
II
2 or 3
NA
120 g, h
NA
NA
120h
NA
NA
30h
III-A
2 or 3
NA
330 g, h
NA
NA
330h
NA
NA
80h
NA
NA
13,200g
,i
NA
NA
13,200i
NA
NA
3,300i
125g,
h, k
NA
NA
NA
NA
NA
NA
NA
45h t,
u
NA
NA
45t, u
III-B
Explosives
Flammable
, gas
flammable
NA
45h t, u
NA
NA
oxidizing
NA
45g, h
NA
NA
45g, h
NA
NA
NL
inert
NA
NA
NL
NA
NA
NL
NA
NA
NL
1g, l,
m, n
(1)g, l,
n
NA
1/4l
(1/4) l
NA
1/4l
(1/4)l
NA
1000g,
h
NA
NA
NA
NA
NA
Gaseous
Liquefied
NA
Liquefied
Petroleum
(LP)
I-A
2 or 3
NA
NA
NA
I-B and IC
Combinatio
n I-A, I-B,
I-C
Inert gas
Organic
peroxide
35
1000g, h
NA
NA
(150)g,h
NA
NA
(150)g,
h
NA
NA(300)o,
p
NA
NA
(300)
NA
NA
NA
NA
30h
NA
NA
10h
NA
NA
120g, h
NA
NA
30g, h
NA
NA
30h, r
30g, h
NA
120g, h
NA
120g, h,
r
NA
NA
120g,
h, r
NA
NA
25h
NA
NA
25g, h
NA
NA
125g,
h
Gaseous
NA
NA
NA
NL
NA
NA
NL
NA
NA
Liquefied
NA
NA
NA
NL
NA
NA
NL
NA
NA
UD
1g, l
(1)g, l
NA
(1/4)l
NA
(1/4)l
5g, h
(5)g, h
NA
1h
(1)h
NA
1h
(1)h
II
50g, h (50)g, h
NA
50h
(50)h
NA
10h
(10)h
FI
Flammable
solid
NA
RS
Flammable
liquidc, d, f,
q
AF
Cryogenic
fluid
1.4G
DR
Consumer
fireworks
Combustibl
e liquid c,
d, e, f
36
NL
NA
NL
NL
NA
NL
NL
NL
NL
NA
NL
NL
NA
NL
NL
1g, l
(1)g, l
NA
(1/4)l
NA
(1/4)l
10g, h (10)g, h
NA
2h
(2)h
NA
2h
(2)h
250g, (250)g,
h
h
NA
250h
(250)h
NA
50h
(50)h
NA
4,000g (4,000)
,i
g, i
NA
4,000g
(4,000)
g
NA
1,000g
(1,000)
g
NA
1,500g,
h
NA
NA
(150)g,
h
NA
NA
(1)l
NA
NA
3j
2 or 3
Gaseous
NA
NA
NA
4g, l
Gaseous
NA
Liquefied
NA
1 or 2
NA
(4)g, l
NA
(150)g, h
NA
NA
1l
DR
1,500g, h
AF
(25)h
NA
50g, l
NA
NA
50g, l
NA
NA
NA
(4)g, l
NA
NA
(4)g, l
NA
NA
1g, l
(1)g, l
NA
()l
NA
()h
5g, h
(5)g, h
NA
1h
(1)h
NA
1h
(1)h
NA
50h
(50)h
NA
10h
(10)h
50g, h (50)g, h
NL
NA
NL
NL
NA
NL
NL
RS
NL
Gaseous 4
or 3
detonable
NA
NA
10g,l
NA
NA
10g,l
NA
NA
3 nondetonable
NA
NA
50g,h
NA
NA
50g,h
NA
NA
FI
Unstable
(reactive)
Gas
25h
NL
Pyrophoric
Unstable
(reactive)
Gas
NA
NA
Liquefied
Unstable
(reactive)
(125)h
IV
Pyrophoric
Gas
125h
Oxidizing
gas
NA
III
Oxidizer
125g, (125)g,
h
h
NA
NA
750g, h
NA
NA
750g, h
NA
NA
NA
NA
NA
NL
NA
NA
NL
NA
NA
Liquefied 4
or 3
detonable
NA
NA
(1)g,l
NA
NA
(1)g,l
NA
NA
3 nondetonable
NA
NA
(2)g, h
NA
NA
(2)g, h
NA
NA
NA
NA
[30]g, h
NA
NA
[30]g, h
NA
NA
Highly
toxic
Highly
toxic gas
NA
NL
NA
NA
NL
NA
NA
5g, h
(5)g, h
NA
5h
(5)h
NA
1h
(1)h
50g, h (50)g, h
NA
50h
(50)h
NA
10h
(10)h
NA
NA
NL
NL
NA
NL
NL
NA
5,000h
500
NA
1,000h
100h
NA
810 g,
h
NA
NA
(150)g,
h
NA
NA
NA
Gaseous
NL
5,000g
,h
500g, h
NA
Toxic gas
NA
810 g, h
(150)g, h
Liquefied
NA
NA
NA
10 g, h
(10) g,
h
Gaseous
NA
NA
Liquefied
Toxic
NL
NA
Gaseous
Liquefied
NA
NA
NA
(4)h, s
NA
500h
(500)h
NA
125h
(125)h
810g, h
NA
NA
810g, h
NA
NA
NA
(150)g,
h
NA
NA
NA
10h
(10)h
NA
3h
(3)h
NA
20h, s
NA
NA
20h, s
NA
NA
NA
(4)h, s
NA
NA
NA
NA
500g, (500)g,
h
h
NA
NA
Corrosive
gas
NA
AF
Corrosive
NA
DR
Water
(reactive)
NA
NA
(150)g, h
NA
FI
RS
aSee 34.1.3.2 for exceptions to tabular amounts. For use of control areas, see 34.2.4. Table values in
parentheses correspond to the unit name in parentheses at the top of the column. The aggregate
quantity in use and storage is not permitted to exceed the quantity listed for storage. In addition,
quantities in specific occupancies are not permitted to exceed the limits in 34.1.3.2.
bMeasured at 70 F (21C) and 14.7 psi (30 kPa).
cInside a building, the maximum capacity of a combustible liquid storage system that is connected to
a fuel-oil piping system is permitted to be 660 gal (2,500L), provided that such system conforms to
NFPA 31, Standard for the Installation of Oil-Burning Equipment.
dFlammable and combustible liquids and flammable gases in the fuel tanks of mobile equipment or
vehicles are permitted to exceed the MAQ where the equipment is stored and operated in accordance
with the NFPA 1.
eIn storage, low, and ordinary hazard occupancies, the storage of Class II combustible liquids is
required to be limited to a maximum quantity of 1,375 gal (5204L); Class IIIA combustible liquids are
required to be limited to a maximum quantity of 13,750 gal (52,044 L) where stored in accordance
with all the requirements in NFPA 30 for general-purpose warehouses.
fThe quantity of fuel in aircraft in hangars is required to be in accordance with NFPA 409, Standard
on Aircraft Hangars.
37
FI
RS
DR
AF
gQuantities are permitted to be increased 100 percent where stored or used in approved cabinets,
gas cabinets, exhausted enclosures, gas rooms, explosives magazines, or safety cans, as
appropriate for the material stored, in accordance with NFPA 1. Where Footnote h also applies, the
increase for both footnotes is permitted to be applied accumulatively.
hMaximum quantities are permitted to be increased 100 percent in buildings equipped throughout
with an automatic sprinkler system in accordance with NFPA 13, Standard for the Installation of
Sprinkler Systems. Where Footnote g also applies, the increase for both footnotes is permitted to be
applied accumulatively.
iThe permitted quantities are not limited in a building equipped throughout with an automatic sprinkler
system in accordance with NFPA 13.
jA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizers is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
kUnless the actual weight of the pyrotechnic composition of the consumer fireworks, 1.4G, is known,
25 percent of the gross weight of the fireworks, including packaging, is permitted to be used to
determine the weight of the fireworks for the purpose of this table.
lPermitted only in buildings equipped throughout with an automatic sprinkler system in accordance
with NFPA 13.
mMaximum quantities of black powder, smokeless propellant, and small arms primers stored or
displayed in mercantile occupancies or stored in one- or two-family dwellings are permitted to exceed
the amount specified by this table where such storage complies with the requirements of NFPA 495,
Explosive Materials Code, Chapter 13.
nIn lieu of the maximum allowable quantity limit per control area, the maximum aggregate quantity
per building of special explosive devices in industrial, mercantile, and storage occupancies shall be
limited to 50 lb.
oAdditional storage locations are required to be separated by a minimum of 300 ft (92 m).
pIn mercantile occupancies, storage of LP-Gas is limited to a maximum of 200 lb (91 kg) in nominal 1
lb (0.45 kg) LP-Gas Containers.
qIn storage, low, and ordinary hazard occupancies, the storage of Class IA flammable liquids is not
permitted, and the combination storage of Class IB and Class IC flammable liquids is required to be
limited to a maximum quantity of 660 gal (2,500 L) where stored in accordance with all the
requirements in NFPA 30 for general-purpose warehouses.
rContaining not more than the maximum allowable quantity per control area of Class I-A, Class I-B, or
Class I-C flammable liquids.
sAllowed only where stored or used in gas rooms or in approved, gas cabinets or enclosures, as
specified in NFPA 1.
tNone allowed in unsprinklered buildings unless stored or used in gas rooms or in approved gas
cabinets or exhausted enclosures, as specified in NFPA 1.
uWith pressure-relief devices for stationary or portable containers vented directly outdoors or to an
exhaust hood.
34.1.3.2 Special Occupancy Limits. The MAQ of hazardous materials per control area in
assembly, ambulatory health care, business, educational, day-care, health care, detention and
correctional, and residential occupancies consisting of lodging or rooming houses, hotels, dormitories,
apartments, and residential board and care facilities shall be as specified in Table 34.1.3.2(a) through
Table 34.1.3.2(h).
38
Table 34.1.3.2(a) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control
Area in Assembly Occupancies
Solid
Liquid
I and II combined
NP
10 gal
NP
IIIA
NP
60 gal
NP
IIIB
NP
120 gal
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
NP
NP
Flammable and
combustible liquidb,c
Cryogenic liquid
Explosivesd,e,f,g
Flammable gasc,h
Gaseous
Liquefied
Liquefied petroleum
1.4G
NP
NP
NP
20 lb
NP
NP
20 lb
NP
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbi
1 gali
NP
250 lb
25 gal
NP
4000 lb
400 gal
NP
Gaseous
NP
NP
NP
Liquefied
NP
15 gal
NP
RS
Flammable solid
Unclassified
detonatable
NP
NP
NP
NP
NP
NP
II
NP
NP
NP
III
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
NL
NL
NP
NP
1 lb
1 lb
NP
lb
lb
NP
1 lb
1 lb
NP
10 lb
10 lb
NPh
NL
NL
NP
Oxidizers
Oxidizing gash
FI
Organic peroxides
Pyrophoric materials
Unstable reactives
39
NP
DR
Consumer fireworks
AF
Material
Class
Gasa
(at NTP)
Water-reactive
1 lb
1 lb
NP
10 lb
10 lb
NP
NL
NL
NP
Corrosives
NP
1000 lb
100 gal
NP
Highly toxic
NP
3 lb
3 lb
NPj
Toxic
NP
125 lb
125 lb
NPj
FI
RS
DR
AF
Material
Class
Solid
Liquid
Gasa
(at NTP)
Flammable and
combustible liquidb,c
I and II combined
IIIA
IIIB
NP
NP
NP
10 gal
60 gal
120 gald
NP
NP
NP
40
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
NP
NP
Gaseous
NP
NP
NP
Liquefied
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
1.4G
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbi
250 lb
Explosivese,f,g
Flammable gasc,h
Consumer fireworks
Flammable solid
Oxidizers
Flammable
1 gali
NP
25 gal
NP
AF
Cryogenic liquid
4000 lbd
400 gald
NP
NP
NP
NP
15 gal
NP
Unclassified detonatable
NP
NP
NA
NP
NP
NA
NP
NP
NA
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
NL
NL
NA
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
10 lb
10 lb
NPh
NL
NL
NP
1 lb
1 lb
NA
10 lb
10 lb
NA
NL
NL
NA
Corrosives
NP
1000 lb
100 gal
NP
Highly toxic
NP
3 lb
3 lb
NPj
Toxic
NP
125 lb
125 lb
NPj
Oxidizing gas
Gaseous
Organic peroxides
II
RS
Pyrophoric materials
III
DR
Liquefied
FI
Unstable reactives
Water-reactive
41
DR
AF
NTP: Normal temperature and pressure [measured at 70F (21C) and 14.7 psi (30 kPa)]. NP: Not
permitted. NA: Not applicable. NL: Not limited.
aUnlimited amounts of gas are permitted to be used for personal medical or emergency medical use.
bStorage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class
IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180
gal (681 L).
cFuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where
the equipment is operated in accordance with the fire code.
dThe permitted quantities are not limited in a building protected throughout by automatic sprinkler
systems in accordance with NFPA 13.
eThe use of explosive materials required by federal, state, or municipal agencies while engaged in
normal or emergency performance of duties is not required to be limited. The storage of explosive
materials is required to be in accordance with the requirements of NFPA 495.
fThe storage and use of explosive materials in medicines and medicinal agents in the forms
prescribed by the official United States Pharmacopoeia or the National Formulary are not required to
be limited.
gThe storage and use of propellant-actuated devices or propellant-actuated industrial tools
manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb
(23 kg) net explosive weight.
hFuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to
exceed 250 ft3 (7.1 m3).
iA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
jGas cylinders not exceeding 20 ft3 (0.57 m3) at NTP are permitted in gas cabinets or fume hoods.
RS
Table 34.1.3.2(c) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control
Area in Business Occupancies
Class
Solid
Liquid
I and II combined
IIIA
IIIB
NP
NP
NP
10 gal
60 gal
120 gal
NP
NP
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
Explosivesd,e,f,g
NP
lb
lb
NP
Flammable gasc
Gaseous
NP
NP
1000 ft3
Liquefied
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
1.4G
NP
NP
NP
FI
Material
Gasa
(at NTP)
Cryogenic liquid
Consumer fireworks
42
Oxidizing gas
Organic peroxides
5 lb
NP
NP
4
3
2
1
NP
10 lbh
250 lb
4000 lb
NP
1 galh
25 gal
400 gal
NP
NP
NP
NP
Gaseous
NP
NP
1500 ft3
Liquefied
NP
15 gal
NP
Unclassified
detonatable
NP
NP
NP
NP
NP
NP
II
NP
NP
NP
III
1 lb
1 lb
NP
IV
V
Pyrophoric materials
NP
4
Toxici
NP
NL
NL
NP
1 lb
1 lb
10 ft3
lb
lb
2 ft3
1 lb
1 lb
10 ft3
10 lb
10 lb
750 ft3
NL
NL
NL
1 lb
1 lb
NP
10 lb
10 lb
NP
NL
NL
NP
NP
1000 lb
100 gal
810 ft3
NP
3 lb
3 lb
20 ft3
NP
125 lb
125 lb
810 ft3
RS
Highly toxici
10 lb
Water-reactive
Corrosives
10 lb
DR
Unstable reactives
Oxidizers
NP
AF
Flammable solid
FI
43
eThe storage and use of explosive materials in medicines and medicinal agents in the forms
prescribed by the official United States Pharmacopoeia or the National Formulary are not required to
be limited.
fThe storage and use of propellant-actuated devices or propellant-actuated industrial tools
manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb
(23 kg) net explosive weight.
gThe storage and use of small arms ammunition, and components thereof, are permitted where in
accordance with NFPA 495.
hA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
iGas cylinders not exceeding 20 ft3 (0.57 m3) at NTP are permitted in gas cabinets or fume hoods.
Material
Class
Cryogenic liquid
I and II combined
Organic peroxides
44
NP
NP
IIIB
NP
120 gald
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
NP
NP
Gaseous
NP
NP
NP
Liquefiedj
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
1.4G
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbk
1 galk
NP
250 lb
25 gal
NP
4000 lbd
400 gald
NP
Gaseous
NP
NP
NP
Liquefied
NP
15 gal
NP
Unclassified detonatable
NP
NP
NP
NP
NP
NP
RS
Oxidizing gasi
10 gal
60 gal
FI
Oxidizers
NP
NP
Consumer fireworks
Flammable solid
Liquid
IIIA
Explosivese,f,g,h
Flammable gasc,i
Solid
Gasa
(at NTP)
DR
Flammable and
combustible liquidb,c
AF
Table 34.1.3.2(d) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control
Area in Educational Occupancies
Water-reactive
NP
NP
III
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
NL
NL
NP
NP
NP
NP
NP
NP
NP
2 ft3
NP
NP
NP
10 lb
10 lb
NPi
NL
NL
NP
1 lb
10 lb
1
NP
Highly toxic
NP
Toxic
NP
1 lb
NA
10 lb
NA
NL
NL
NA
1000 lb
100 gal
NP
3 lb
3 lb
NPl
125 lb
125 lb
NPl
DR
Corrosives
Unstable reactives
NP
AF
Pyrophoric materials
II
FI
RS
45
jStorage in laboratories only; additional 20 lb units (9.1 kg) where minimum 20 ft (6.1 m) separation is
provided.
kA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
lGas cylinders not exceeding 20 ft3 (0.57 m3) at NTP are permitted in gas cabinets or fume hoods.
Table 34.1.3.2(e) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control
Area in Day-Care Occupancies
I and II combined
NP
IIIA
NP
NP
120 gald
NP
NP
10 gal
NP
NP
10 gal
NP
NP
NP
NP
NP
Gaseous
NP
NP
NP
Liquefied
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
1.4G
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbd
1 gali
NP
250 lb
25 gal
NP
4000 lbd
400 gald
NP
Gaseous
NP
NP
NP
Liquefied
NP
15 gal
NP
Unclassified
detonatable
NP
NP
NP
NP
NP
NP
II
NP
NP
NP
III
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
Flammable
DR
Oxidizing
Explosivese,f,g
Flammable gasc,h
FI
Oxidizing gash
RS
Oxidizers
Organic peroxides
46
NP
60 gal
Cryogenic liquid
Flammable solid
10 gal
NP
IIIB
Consumer fireworks
Liquid
Solid
AF
Flammable and
combustible liquidb,c
Class
Material
Gasa
(at NTP)
NL
NL
NP
NA
NP
NP
NP
NP
NP
NP
NP
NP
NP
10 lb
10 lb
NPh
NL
NL
NP
1 lb
1 lb
NA
10 lb
10 lb
NA
NL
NL
NA
Corrosives
NP
1000 lb
100 gal
NP
Highly toxic
NP
3 lb
3 lb
NPj
Toxic
NP
Unstable reactives
Water-reactive
AF
Pyrophoric materials
125 lb
125 lb
NPj
FI
RS
DR
47
Table 34.1.3.2(f) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control Area
in Health Care Occupancies
Solid
Liquid
I and II combined
NP
10 gal
NP
IIIA
NP
60 gal
NP
IIIB
NP
120 gald
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
Gaseous
NP
Material
Cryogenic liquid
Explosivese,f,g
Flammable gasc,e,f,g,h
NP
NP
NP
NP
NP
20 lb
NP
NP
20 lb
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbj
1 galj
NP
250 lb
25 gal
NP
4000 lbd
400 gald
NP
Gaseous
NP
NP
per NFPA 99
Liquefied
NP
15 gal
NP
Unclassified
detonatable
NP
NP
NP
NP
NP
NP
II
NP
NP
NP
III
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
NL
NL
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
10 lb
10 lb
NPh
NL
NL
NP
Liquefiedi
Liquefied petroleum
Consumer fireworks
1.4G
NP
Oxidizers
4
3
2
Oxidizing gas
FI
RS
Organic peroxides
DR
Flammable solid
Pyrophoric materials
Unstable reactives
48
AF
Flammable and
combustible liquidb,c
Class
Gasa
(at NTP)
Water-reactive
1 lb
1 lb
NA
10 lb
10 lb
NA
NL
NL
NA
Corrosives
NP
1000 lb
100 gal
NP
Highly toxic
NP
3 lb
3 lb
NPk
Toxic
NP
125 lb
125 lb
NPk
FI
RS
DR
AF
Material
Flammable and
49
Class
Solid
Liquid
Gasa
(at NTP)
I and II combined
NP
10 gal
NP
NP
60 gal
NP
IIIB
NP
120 gal
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
NP
NP
Gaseous
NP
NP
NP
Liquefied
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
1.4G
NP
NP
NP
NP
5 lb
NP
Explosivesd,e,f,g
Flammable gasc,h
Consumer fireworks
Flammable solid
Oxidizers
Cryogenic liquid
IIIA
NP
NP
NP
NP
AF
combustible liquidb,c
10 lbi
1 gali
NP
250 lb
25 gal
NP
4000 lb
400 gal
NP
NA
NP
NP
Liquefied
NA
15 gal
NP
Unclassified detonatable
NP
NP
NP
NP
NP
NP
NP
NP
NP
1 lb
1 lb
NP
IV
10 lb
10 lb
NP
NL
NL
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
10 lb
10 lb
NPh
NL
NL
NP
1 lb
1 lb
NP
10 lb
10 lb
NP
NL
NL
NP
Corrosives
NP
1000 lb
100 gal
NP
Highly toxic
NP
3 lb
3 lb
NPj
Toxic
NP
125 lb
125 lb
NPj
2
1
Gaseous
Organic peroxides
II
DR
Oxidizing gash
RS
III
Pyrophoric materials
FI
Unstable reactives
Water-reactive
DR
AF
NTP: Normal temperature and pressure [measured at 70F (21C) and 14.7 psi (30 kPa)]. NP: Not
permitted. NA: Not applicable. NL: Not limited.
aUnlimited amounts of gas are permitted to be used for personal medical or emergency medical use.
bStorage in excess of 10 gal (38 L) of Class I and Class II liquids combined or 60 gal (227 L) of Class
IIIA liquids is permitted where stored in safety cabinets with an aggregate quantity not to exceed 180
gal (681 L).
cFuel in the tank of operating mobile equipment is permitted to exceed the specified quantity where
the equipment is operated in accordance with the fire code.
dThe use of explosive materials required by federal, state, or municipal agencies while engaged in
normal or emergency performance of duties is not required to be limited. The storage of explosive
materials is required to be in accordance with the requirements of NFPA 495.
eThe storage and use of explosive materials in medicines and medicinal agents in the forms
prescribed by the official United States Pharmacopoeia or the National Formulary are not required to
be limited.
fThe storage and use of propellant-actuated devices or propellant-actuated industrial tools
manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb
(23 kg) net explosive weight.
gThe storage and use of small arms ammunition, and components thereof, are permitted where in
accordance with NFPA 495.
hFuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to
exceed 250 ft3 (7.1 m3).
iA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
jGas cylinders not exceeding 20 ft3 (0.57 m3) at NTP are permitted in gas cabinets or fume hoods.
Material
RS
Table 34.1.3.2(h) Maximum Allowable Quantity (MAQ) of Hazardous Materials per Control
Area in Residential Occupancies Consisting of Lodging or Rooming Houses, Hotels,
Dormitories, Apartments, and Residential Board and Care Facilities
Solid
Liquid
I and II combined
NP
10 gal
NP
IIIA
NP
60 gal
NP
IIIB
NP
120 gal
NP
Flammable
NP
10 gal
NP
Oxidizing
NP
10 gal
NP
NP
NP
NP
NP
Gaseous
NP
NP
NP
Liquefiedi
NP
20 lb
NP
Liquefied petroleum
NP
20 lb
NP
FI
Flammable and
combustible liquidb,c
Class
Gasa
(at NTP)
Cryogenic liquid
Explosivesd,e,f,g
Flammable gasc,h
51
NP
NP
NP
NP
5 lb
NP
NP
NP
NP
NP
10 lbj
1 galj
NP
250 lb
25 gal
NP
4,000 lb
400 gal
NP
Gaseous
NP
NP
NP
Liquefied
NP
15 gal
NP
Unclassified detonatable
NP
NP
NP
NP
II
NP
Flammable solid
Oxidizers
Oxidizing gash
Organic peroxides
III
10 lb
NP
NL
NL
NP
1 lb
1 lb
NP
lb
lb
NP
1 lb
1 lb
NP
10 lb
10 lb
NPh
NL
NL
NP
1 lb
1 lb
NA
10 lb
10 lb
NA
NL
NL
NA
NP
1,000 lb
100 gal
NP
NP
3 lb
3 lb
NPk
NP
125 lb
125 lb
NPk
Toxic
RS
DR
4
2
Highly toxic
NP
10 lb
Corrosives
NP
NP
NP
Water-reactive
NP
1 lb
V
Unstable reactives
NP
1 lb
IV
Pyrophoric materials
1.4G
AF
Consumer fireworks
FI
DR
AF
eThe storage and use of explosive materials in medicines and medicinal agents in the forms
prescribed by the official United States Pharmacopoeia or the National Formulary are not required to
be limited.
fThe storage and use of propellant-actuated devices or propellant-actuated industrial tools
manufactured, imported, or distributed for their intended purposes are required to be limited to 50 lb
(23 kg) net explosive weight.
gThe storage and use of small arms ammunition, and components thereof, are permitted where in
accordance with NFPA 495.
hFuel or oxidizing gas used for maintenance, repair, and operation of equipment is not permitted to
exceed 250 ft3 (7.1 m3).
iStorage containers are not permitted to exceed 2.7 lb (1.2 kg) water capacity.
jA maximum quantity of 200 lb (91 kg) of solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted
where such materials are necessary for maintenance purposes, operation, or sanitation of equipment.
Storage containers and the manner of storage are required to be approved.
kGas cylinders not exceeding 20 ft3 (0.57 m3) at NTP are permitted in gas cabinets or fume hoods.
34.1.3.3 Mercantile, Storage, and Industrial Occupancies.
34.1.3.3.1 Maximum Allowable Quantity (MAQ) Increases for Mercantile, Storage, and
Industrial Occupancies. The aggregate quantity of nonflammable solid and nonflammable or
noncombustible liquid hazardous materials permitted within a single control area of a mercantile,
storage, or industrial occupancy shall be permitted to exceed the MAQ specified in Table 34.1.3.1,
without complying with Protection Level 2, Protection Level 3, or Protection Level 4, provided that the
quantities comply with Table 34.1.3.3.1(a) and Table 34.1.3.3.1(b) and that materials are displayed
and stored in accordance with the special limitations on storage height, storage density, and other
controls specified in NFPA 1 and NFPA 400, Hazardous Materials Code.
Table 34.1.3.3.1(a) Maximum Allowable Quantity (MAQ) per Control Area Increases for
Selected Hazard Categories in Mercantile, Storage, and Industrial Occupancies
RS
Solids
Hazard Category
lb
Liquids
kg
gal
FI
Oxidizers
1,150
522
115
435
2,250
1,022
225
852
18,000
8,172
1,800
6,813
Class 1c
Note: Maximum quantities for hazard categories not shown are required to be in accordance with
Table 34.1.3.1.
aMaximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in
accordance with NFPA 13. Where footnote b also applies, the increase for both footnote a and
footnote b is permitted to be applied.
53
bMaximum quantities are permitted to be increased 100 percent where stored in approved storage
cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1 or NFPA 400. Where
footnote a also applies, the increase for both footnote b and footnote a is permitted to be applied.
cQuantities are not limited in buildings protected by an automatic sprinkler system complying with
NFPA 13.
Table 34.1.3.3.1(b) Maximum Allowable Quantity (MAQ) per Control Area Increases for
Selected Hazard Categories in Mercantile and Storage Occupancies
Maximum Allowable Quantitya,b,c
Solids
lb
kg
gal
Hazard Category
Liquids
L
Unstable reactives
Class 3
550
Class 2
1,150
250
55
208
522
115
435
250
55
208
522
115
435
DR
Water-reactive
AF
Class 3
550
Class 2
1,150
10,000
4540
1,000
3785
Highly toxic
20
FI
RS
Toxic
1,000
454
100
379
NOTE: See table above.
aMaximum quantities are permitted to be increased 100 percent in buildings that are sprinklered in
accordance with NFPA 13. Where footnote c also applies, the increase for both footnote a and b is
permitted to be applied.
bMaximum quantities are permitted to be increased 100 percent where stored in approved storage
cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1. Where footnote b also
applies, the increase for both footnote b and footnote a is permitted to be applied.
cMaximum quantities are permitted to be increased 100 percent where stored in approved storage
cabinets, gas cabinets, or exhausted enclosures in accordance with NFPA 1. Where footnote a also
applies, the increase for both footnotes is permitted to be applied.
34.1.3.3.2 Maximum Allowable Quantity (MAQ) Increases for Sale of Alcoholic Beverages,
Medicines, Foodstuffs, and Cosmetics.
34.1.3.3.2.1 Quantities of alcoholic beverages shall not be limited in mercantile occupancies,
provided that the liquids are packaged in individual containers not exceeding 1.3 gal (4.9 L).
34.1.3.3.2.2 Quantities of medicines, foodstuffs, and cosmetics containing not more than 50 percent
by volume of water-miscible liquids, and with the remainder of the solutions not being flammable,
shall not be limited, provided that such materials are packaged in individual containers not exceeding
1 gal (3.78 L).
54
FI
RS
DR
AF
34.1.3.4 Gas Rooms. Where gas rooms are used to increase the maximum allowable quantity per
control area specified by Table 34.1.3.1, they shall be in accordance with 34.1.3.4.1 through
34.1.3.4.4.
34.1.3.4.1 Pressure Control. Gas rooms shall operate at a negative pressure in relationship to the
surrounding area. [55:6.4.1]
34.1.3.4.2 Exhaust Ventilation. Gas rooms shall be provided with an exhaust ventilation system.
[55:6.4.2]
34.1.3.4.3 Separation.
34.1.3.4.3.1 Gas rooms shall be separated from other occupancies by a minimum of 1-hour fire
resistancerated construction. [55:6.4.4]
34.1.3.4.3.2 Gas rooms required by this Code, NFPA 1, NFPA 55, or NFPA 400 for storage of toxic
or highly toxic gases shall be separated from other areas by not less than a 2-hour fire barrier wall or
a 2-hour horizontal assembly, where the area is 300 ft2 (27.9 m2) or more, and by not less than 1hour fire resistancerated construction where the area is less than 300 ft2 (27.9 m2).
34.1.3.4.4 Limitation on Contents. The function of compressed gas rooms shall be limited to
storage and use of compressed gases and associated equipment and supplies. [55:6.4.5]
34.1.4 Performance Alternative. In lieu of complying with Chapter 34 in its entirety, occupancies
containing high hazard Level 1 to high hazard Level 5 contents shall be permitted to comply with
34.1.4.1 and 34.1.4.2.
34.1.4.1 Goal. The goal of performance-based designs for facilities containing high hazard contents
shall be to protect people and property from the consequences of unauthorized discharges, fires, or
explosions involving hazardous materials.
34.1.4.1.1 The performance-based designs specified in 34.1.4.1 shall minimize the risk of events
described in 34.1.4.1 and shall minimize the consequences of such events if they occur.
34.1.4.1.2 Performance-based designs shall also comply with Chapters 4 and 5.
34.1.4.2 Objectives.
34.1.4.2.1 To satisfy the goal established in 34.1.4.1, performance-based designs for facilities
containing high hazard contents shall identify the properties of hazardous materials to be stored,
used, or handled and shall provide adequate and reliable safeguards to accomplish all of the
following objectives, considering both normal operations and possible abnormal conditions:
(1)
Minimize the potential occurrence of unwanted releases, fires, or other emergency incidents
resulting from the storage, use, or handling of hazardous materials
(2)
Minimize the potential failure of buildings, equipment, or processes involving hazardous
materials by ensuring that such buildings, equipment, or processes are reliably designed and are
suitable for the hazards present
(3)
Minimize the potential exposure of people or property to unsafe conditions or events involving
an unintended reaction or release of hazardous materials
(4)
Minimize the potential for an unintentional reaction that results in a fire, explosion, or other
dangerous condition
(5)
Provide a means to contain, treat, neutralize, or otherwise handle plausible releases of
hazardous materials to minimize the potential for adverse impacts to persons or property outside of
the immediate area of a release
(6)
Provide appropriate safeguards to minimize the risk of, and limit the damage and injury that
might result from, an explosion involving hazardous materials that present explosion hazards
(7)
Detect hazardous levels of gases or vapors that are dangerous to health, and alert appropriate
persons or mitigate the hazard when the physiological warning properties for such gases or vapors
are inadequate to warn of danger prior to personal injury
55
FI
RS
DR
AF
(8)
Maintain power to provide for continued operation of safeguards and important systems that
are relied on to prevent or control an emergency condition involving hazardous materials
(9)
Maintain ventilation where ventilation is relied on to minimize the risk of emergency conditions
involving hazardous materials
(10) Minimize the potential for exposing combustible hazardous materials to unintended sources of
ignition, and for exposing any hazardous material to fire or physical damage that can lead to
endangerment of people or property
34.1.4.2.2 As part of the design process, a process hazard analysis and off-site consequence
analysis shall be conducted where necessary to reasonably ensure that people and property are
satisfactorily protected from dangerous conditions involving hazardous materials.
34.1.4.2.3 The results of the analyses specified in 34.1.4.2.2 shall be considered when determining
active and passive mitigation measures used in accomplishing the objectives set forth in 34.1.4.2.1.
34.1.4.2.4 In addition to the requirement of 34.1.4.2.3, written procedures for pre-start-up safety
reviews, normal and emergency operations, management of change, emergency response, and
accident investigation and documentation shall be developed prior to beginning operations at a facility
designed in accordance with 34.1.4.
34.1.4.2.5 Procedures, as described in 34.1.4.2.4, shall be developed with the participation of
affected employees.
34.2 Requirements for All Occupancies Containing High Hazard Contents.
34.2.1 Applicability. Buildings, and portions thereof, containing hazardous materials regulated by
this Code shall comply with Section 34.2.
34.2.2 Fire Prevention Code. Buildings, and portions thereof, where hazardous materials are
stored, used, or handled shall also comply with NFPA 1.
34.2.3 Hazardous Materials Code. Buildings, and portions thereof, where hazardous materials
within the scope of NFPA 400, Hazardous Materials Code, are stored, used, or handled shall also
comply with the applicable requirements of NFPA 400.
34.2.4 Special Information for Permit Application.
34.2.4.1 Permit applications for buildings, and portions thereof, containing high hazard contents
shall be accompanied by all of the following:
(1)
Plan showing the location of storage and use areas
(2)
Information identifying the maximum quantity of each class of hazardous material stored and
used in each area
34.2.4.2 Where required by the authority having jurisdiction, the permit applicant shall provide,
without charge to the jurisdiction, a technical opinion and report prepared by a qualified engineer,
specialist, laboratory, or fire safety specialty organization that analyzes the fire safety and life safety
properties of the design, operation, or use of the building or facility and demonstrates compliance with
this Code.
34.2.5 Control Areas. Control areas shall be those spaces within a building where quantities of
hazardous contents not exceeding the maximum quantities allowed by this Code are stored,
dispensed, used, or handled.
34.2.5.1 Construction Requirements for Control Areas.
34.2.5.1.1 Control areas shall be separated from each other by fire barriers in accordance with
Table 34.2.5.1.1.
Table 34.2.5.1.1 Design and Number of Control Areas
Floor Level
56
Maximum
Allowable
Number of
Control
Fire
Resistance
Quantity per
Control Area
(%)
Rating for
Fire Barriers
(hr)
>9
5.0
79
5.0
46
12.5
50.0
75.0
100.0
75
50
AF
1
1
FI
RS
DR
Lower than 2
NA
NA
NA
NA: Not applicable.
Percentages represent the maximum allowable quantities per control area shown in Table 34.1.3.1,
with all of the increases permitted in the footnotes of that table.
Fire barriers are required to include floors and walls, as necessary, to provide a complete separation
from other control areas.
34.2.5.1.2 Where only one control area is present in a building, no special construction provisions
shall be required.
34.2.5.2 Number of Control Areas. The maximum number of control areas within a building shall
be in accordance with Table 34.2.5.1.1.
34.2.6 Weather Protection. Where weather protection is provided for sheltering outside hazardous
material storage or use areas, such storage or use areas shall be considered outside storage or use
areas, provided that all of the following conditions are met:
(1)
Supports and walls shall not obstruct more than one side or more than 25 percent of the
perimeter of the storage or use area.
(2)
The distance from the structure and the structural supports to buildings, lot lines, public ways,
or means of egress to a public way shall be not less than the distance required by NFPA 1 or NFPA
400 for an outside hazardous material storage or use area without weather protection.
(3)
Weather-protection structures constructed in accordance with 34.2.6 shall not contain
explosive or detonable materials.
34.3 Requirements for Occupancies Exceeding the Maximum Allowable Quantity (MAQ) per
Control Area for High Hazard Contents.
34.3.1 Protection Levels. Buildings, and portions thereof, where high hazard contents are stored,
used, or handled shall comply with the protection levels as set forth in Section 34.3.
34.3.1.1 Protection Level 1. Buildings containing quantities of hazardous materials exceeding the
MAQ of high hazard Level 1 contents permitted in control areas shall comply with applicable
regulations for Protection Level 1, as set forth in 34.3.3.
34.3.1.2 Protection Level 2. Buildings, and portions thereof, containing quantities of hazardous
materials exceeding the MAQ of high hazard Level 2 contents permitted in control areas shall comply
with applicable regulations for Protection Level 2, as set forth in 34.3.4.
57
RS
DR
AF
34.3.1.3 Protection Level 3. Buildings, and portions thereof, containing quantities of hazardous
materials exceeding the MAQ of high hazard Level 3 contents permitted in control areas shall comply
with applicable regulations for Protection Level 3, as set forth in 34.3.5.
34.3.1.4 Protection Level 4. Buildings, and portions thereof, containing quantities of hazardous
materials exceeding the MAQ of high hazard Level 4 contents permitted in control areas shall comply
with applicable regulations for Protection Level 4, as set forth in 34.3.6.
34.3.1.5 Protection Level 5. Buildings, and portions thereof, used for fabrication of semiconductors
or semiconductor research and development and containing quantities of hazardous materials
exceeding the MAQ of high hazard Level 5 contents permitted in control areas shall comply with
applicable regulations for Protection Level 5, as set forth in 34.3.7.
34.3.2 General Requirements. The requirements set forth in 34.3.2 shall apply to buildings, or
portions thereof, that are required to comply with Protection Level 1 through Protection Level 5 where
required by 34.3.1.1 through 34.3.1.5.
34.3.2.1 Fire Protection Systems. Buildings, or portions thereof, required to comply with Protection
Level 1 through Protection Level 5 shall be protected by an approved automatic fire sprinkler system
complying with Section 55.3.
34.3.2.1.1 Electronic supervision of supervisory signals shall be provided in accordance with
55.3.2.1.
34.3.2.1.2 Waterflow alarms shall be monitored in accordance with 55.3.2.2.
34.3.2.1.3 Rooms or areas that are of noncombustible construction with wholly noncombustible
contents shall not be required to comply with 34.3.2.1.
34.3.2.1.4 Portable magazines not exceeding 120 ft2 (11.2 m2) constructed in accordance with
NFPA 495 shall not be required to comply with 34.3.2.1.
34.3.2.2 Building Height Exception. The height of a one-story building, or portion thereof,
containing only tanks or industrial process equipment shall not be limited based on the type of
construction.
34.3.2.3 Separation of Occupancies Having High Hazards. The separation of areas containing
high hazard contents from each other and from other use areas shall be as required by Table
34.3.2.3 and shall not be permitted to be reduced with the installation of fire protection systems as
required by 34.3.2.1.
Table 34.3.2.3 Required Separation of Occupancies Containing High Hazard Contents (hr)
Protection
Level 1
Protection
Level 2
Protection
Level 3
Apartment buildings
NP
Assembly 300
NP
NP
Assembly> 1000
NP
NP
NP
Business
NP
Day care> 12
NP
Day-care homes
NP
FI
Occupancy
58
Protection Protection
Level 4
Level 5
NP
NP
Educational
NP
NP
NP
NP
NP
NP
NP
Mercantile, Class A
NP
Mercantile, Class B
NP
Mercantile, Class C
NP
NP
NP
Protection Level 1
NP
NP
NP
NP
Protection Level 2
NP
NP
NP
NP
DR
AF
Protection Level 3
Protection Level 4
Protection Level 5
FI
RS
59
Distance
Hazard
Level
ft
75
23
100
30
150
46
175
53
FI
RS
DR
AF
5
200
61
34.3.2.4.2 Capacity of Means of Egress. Egress capacity for high hazard contents areas shall be
based on 0.7 in. (18 mm) per person for stairs or 0.4 in. (10 mm) per person for level components and
ramps in accordance with 11.3.3.1.
34.3.2.4.3 Number of Means of Egress. Not less than two means of egress shall be provided from
each building, or portion thereof, required to comply with Section 34.3, unless rooms or spaces do not
exceed 200 ft2 (18.6 m2), have an occupant load not exceeding three persons, and have a travel
distance to the room door not exceeding 25 ft (7.6 m).
34.3.2.4.4 Dead Ends. Means of egress, for other than rooms or spaces that do not exceed 200 ft2
(18.6 m2), have an occupant load not exceeding three persons, and have a travel distance to the
room door not exceeding 25 ft (7.6 m), shall be arranged so that there are no dead ends in corridors.
34.3.2.4.5 Doors. Doors serving high hazard contents areas with occupant loads in excess of five
shall be permitted to be provided with a latch or lock only if the latch or lock is panic hardware or fire
exit hardware complying with 11.2.1.7.
34.3.2.5 Ventilation.
34.3.2.5.1 Buildings, or portions thereof, in which explosive, flammable, combustible, corrosive, or
highly toxic dusts, mists, fumes, vapors, or gases are, or might be, emitted shall be provided with
mechanical exhaust ventilation or natural ventilation where natural ventilation can be shown to be
acceptable for the materials as stored.
34.3.2.5.1.1 Flammable and combustible liquids stored in closed containers in compliance with
NFPA 30 shall not be required to comply with 34.3.2.5.1.
34.3.2.5.1.2 Solids and liquids, other than combustible or flammable liquids, stored in closed
containers shall not be required to comply with 34.3.2.5.1.
34.3.2.5.2 Mechanical exhaust systems shall comply with the Uniform Mechanical Code, as
referenced in Chapter 50.
34.3.2.5.3 Mechanical ventilation shall be at a rate of not less than 1 ft3/min/ft2 (5.1 L/s/m2) of floor
area over areas required to comply with Protection Level 1 through Protection Level 5.
34.3.2.5.4 Areas containing Class I liquids or Class II liquids at temperatures above their flash
points, or Class IIIA liquids at temperatures above their flash points, shall be ventilated at a rate
sufficient to maintain the concentration of vapors within the area at or below 25 percent of the lower
explosive limit.
34.3.2.5.5 Ventilation requirements shall be determined by calculations based on anticipated fugitive
emissions or by sampling of the actual vapor concentration levels under normal operating conditions.
34.3.2.5.6 Make-up air shall be provided, and provision shall be made for locating make-up air
openings to avoid short-circuiting the ventilation.
34.3.2.5.7 Ducts conveying explosives or flammable vapors, fumes, or dusts shall extend directly to
the exterior of the building without entering other spaces.
34.3.2.5.7.1 Exhaust ducts shall not extend into or through ducts and plenums.
34.3.2.5.7.2 Ducts conveying vapor or fumes having flammable constituents less than 25 percent of
their lower flammability limit shall be permitted to pass through other spaces.
34.3.2.5.8 Emissions generated at workstations shall be confined to the area in which they are
generated as specified in NFPA 1 or NFPA 400, as referenced in Chapter 50.
34.3.2.5.9 The location of supply and exhaust openings shall be in accordance with the Uniform
Mechanical Code, as referenced in Chapter 50.
34.3.2.5.10 Exhaust air contaminated by highly toxic material shall be treated where required by
NFPA 1 or NFPA 400.
60
DR
AF
34.3.2.5.11 Systems shall operate continuously unless alternate designs are approved.
34.3.2.5.12 A manual shutoff control for ventilation equipment required by 34.3.2.5 shall be provided
outside the room adjacent to the principal access door to the room.
34.3.2.5.13 The shutoff control described in 34.3.2.5.12 shall be of the break-glass type and shall be
labeled as follows:
VENTILATION SYSTEM EMERGENCY SHUTOFF
34.3.2.5.14 Exhaust ventilation shall be arranged to consider the density of the potential fumes or
vapors released.
34.3.2.5.14.1 For fumes or vapors that are heavier than air, exhaust shall be taken from a point
within 12 in. (305 mm) of the floor.
34.3.2.5.14.2 The location of both the exhaust and inlet air openings shall be arranged to provide air
movement across all portions of the floor or room to prevent the accumulation of vapors.
34.3.2.5.14.3 Exhaust ventilation shall not be recirculated within the room or building if the materials
stored are capable of emitting hazardous vapors.
34.3.2.5.14.4 Recirculation shall be permitted where it is monitored continuously using a fail-safe
system that is designed to automatically sound an alarm, stop recirculation, and provide full exhaust
to the outside in the event that vaporair mixtures in concentrations over one-fourth of the lower
flammable limit are detected.
34.3.2.6* Explosion Control. Buildings, or portions thereof, required to comply with Protection Level
1 through Protection Level 3 and containing materials shown in Table 34.3.2.6 shall be provided with
a means of explosion control.
Table 34.3.2.6 Explosion Control Requirements
Hazard Category
Class
Protection Method
NA
Explosion controla
Explosives
Detonating
Barricadeb
Deflagrating
Explosion controla
NA
Explosion controla
Flammable liquidc
Explosion controla
Explosion controla
Explosion controla
Unclassified
Barricadeb
Class I
Barricadeb
Class 4
Barricadeb
Pyrophoric gase
NA
Barricadeb
Explosion controla
Unstable reactives
Class 4
Barricadeb
Class 3 detonating
Barricadeb
FI
RS
Organic peroxides
61
Class 3 deflagrating
Explosion controla
Class 3
Explosion controla
Class 2 deflagrating
Explosion controla
FI
RS
DR
AF
62
FI
RS
DR
AF
34.3.2.8.2.3 Except for surfacing, the floors, sills, dikes, sumps, and collection systems shall be
constructed of noncombustible material, and the liquid-tight seal shall be compatible with the material
stored.
34.3.2.8.2.4 Where liquid-tight sills or dikes are provided, they shall not be required at perimeter
openings that are provided with an open-grate trench across the opening that connects to an
approved collection system.
34.3.2.8.3 Secondary Containment.
34.3.2.8.3.1 Buildings, or portions thereof, used for any of the following shall be provided with
secondary containment:
(1)
Storage of liquids where the capacity of an individual vessel exceeds 55 gal (208.2 L) or the
aggregate capacity of multiple vessels exceeds 1000 gal (3785 L)
(2)
Storage of solids where the capacity of an individual vessel exceeds 550 lb (248.8 kg) or the
aggregate capacity of multiple vessels exceeds 10,000 lb (4524.8 kg)
(3)
Open-use liquids where the capacity of an individual vessel or system exceeds 1.1 gal (4 L)
(4)
Open-use liquids where the capacity of multiple vessels or systems exceeds 5.3 gal (20 L)
34.3.2.8.3.2 Buildings, or portions thereof, containing only hazardous materials in listed secondary
containment tanks or systems shall not be required to comply with 34.3.2.8.3.1.
34.3.2.8.3.3 Buildings, or portions thereof, containing only flammable solids, explosive solids, or
corrosive solids shall not be required to comply with 34.3.2.8.3.1.
34.3.2.8.3.4 Secondary containment shall be achieved by means of drainage control where required
by NFPA 30.
34.3.2.8.3.5 The building, room, or area shall contain or drain the hazardous materials and fire
protection water through the use of one of the following methods:
(1)
Liquid-tight sloped or recessed floors in indoor locations or similar areas in outdoor locations
(2)
Liquid-tight floors in indoor locations or similar areas in outdoor locations provided with liquidtight raised or recessed sills or dikes
(3)
Sumps and collection systems
(4)
Drainage systems leading to an approved location
34.3.2.8.3.6 Where incompatible materials are present in open containers or systems, such
materials shall be separated from each other in the secondary containment system.
34.3.2.8.3.7 Secondary containment for indoor storage areas shall be designed to contain a spill
from the largest vessel plus the design flow volume of fire protection water calculated to discharge
from the fire-extinguishing system over the minimum required system design area, or area of the
room or area in which the storage is located, whichever is smaller, for a period of 20 minutes.
34.3.2.8.3.8 A monitoring method shall be provided to detect hazardous materials in the secondary
containment system.
34.3.2.8.3.9 The monitoring method shall be permitted to be visual inspection of the primary or
secondary containment, or other approved means.
34.3.2.8.3.10 Where secondary containment is subject to the intrusion of water, a monitoring
method for detecting water shall be provided.
34.3.2.8.3.11 Where monitoring devices are provided, they shall be connected to distinct visual or
audible alarms.
34.3.2.8.3.12 Where remote containment systems are provided, drainage systems shall be in
accordance with the Uniform Plumbing Code, as referenced in Chapter 53, and all of the following
provisions also shall be met:
(1)
The slope of floors in indoor locations to drains or similar areas in outdoor locations shall be
not less than 1 percent.
63
RS
DR
AF
(2)
Drains from indoor storage areas shall be sized to carry the volume of the fire protection water,
as determined by the design density discharged from the automatic fire-extinguishing system over the
minimum required system design area, or area of the room or area in which the storage is located,
whichever is smaller.
(3)
Materials of construction for drainage systems shall be compatible with the materials stored.
(4)
Separate drainage systems shall be provided to avoid mixing incompatible materials where
such materials are present in an open-use condition.
(5)
Drains shall terminate in an approved location away from buildings, valves, means of egress,
fire access roadways, adjoining property, and storm drains.
34.3.2.9 Floors in Storage Rooms. Floors in storage areas for organic peroxides, oxidizers,
pyrophoric materials, unstable (reactive) materials, water-reactive solids and liquids, corrosive
materials, and toxic and highly toxic materials shall be of liquid-tight, noncombustible construction.
34.3.2.10 Unprotected Vertical Openings.
34.3.2.10.1 In industrial occupancies required to comply with 34.3.3, where unprotected vertical
openings exist and are necessary to manufacturing operations, such openings shall be permitted
beyond the specified limits in 29.3.1(1).
34.3.2.10.2 The unprotected vertical openings described in 34.3.2.10.1 shall be permitted only
where every floor level has direct access to one or more enclosed stairs or other exits protected
against obstruction by any fire or smoke in the open areas connected by the unprotected vertical
openings.
34.3.3 Protection Level 1.
34.3.3.1 General. Buildings, or portions thereof, required to comply with Protection Level 1 shall
comply with 34.3.2, 34.3.3.2, and 34.3.3.3.
34.3.3.2 Detached Building Required.
34.3.3.2.1 Buildings required to comply with Protection Level 1 shall be used for no other purpose,
shall not exceed one story in height, and shall be without basements, crawl spaces, or other underfloor spaces.
34.3.3.2.2 Roofs of buildings described in 34.3.3.2.1 shall be of lightweight construction with suitable
thermal insulation to prevent sensitive material from reaching its decomposition temperature.
34.3.3.2.3 Buildings required to comply with both Protection Level 1 and Protection Level 4 shall
comply with the most restrictive requirements for both protection levels.
34.3.3.3 Minimum Distance to Property Lines or Horizontal Separation. Buildings required to
comply with Protection Level 1 shall be set back from property lines, or be provided with a horizontal
separation in accordance with 7.3.4.2, by a distance of not less than 75 ft (23 m) and of not less than
that required by Table 34.3.3.3.
FI
Quantity of
Explosive
Materials1,2,3,4
Pounds Pounds
Over
Not
64
Inhabited
Buildings9
Barri-
Unbarricaded
Distances in Feet
Passenger
Railways Public
Public Highways
Highways with
Traffic Volume of
Traffic Volume of
3,000 Vehicles/Day More Than 3,000
or Less11
Vehicles/Day10,11
Barri-
Unbarricaded
Barri-
Unbarricaded
Separation of
Magazines12
Barri-
Unbarricaded
caded6,7,8
caded6,7,8
caded6,7,8
70
140
30
60
51
102
12
10
90
180
35
70
64
128
16
10
20
110
220
45
90
81
162
10
20
20
30
125
250
50
100
93
186
11
22
30
40
140
280
55
110
103
206
12
24
40
50
150
300
60
120
110
220
14
28
50
75
170
340
70
140
127
254
15
30
75
100
190
380
75
150
139
278
16
32
100
125
200
400
80
160
150
300
18
36
125
150
215
430
85
170
159
318
19
38
150
200
235
470
95
200
250
255
510
105
250
300
270
540
110
300
400
295
590
120
400
500
320
640
500
600
340
680
600
700
355
710
700
800
375
750
800
900
390
780
900
1,000
400
1,000
1,200
425
1,200
1,400
450
1,400
1,600
1,600
1,800
1,800
2,000
2,000
2,500
AF
caded6,7,8
Over
175
350
21
42
210
189
378
23
46
220
201
402
24
48
240
221
442
27
54
DR
190
260
238
476
29
58
135
270
253
506
31
62
145
290
266
532
32
64
150
300
278
556
33
66
155
310
289
578
35
70
800
160
320
300
600
36
72
850
165
330
318
636
39
78
900
170
340
336
672
41
82
470
940
175
350
351
702
43
86
490
980
180
360
366
732
44
88
505
1,010
185
370
378
756
45
90
545
1,090
190
380
408
816
49
98
3,000
580
1,160
195
390
432
864
52
104
4,000
635
1,270
210
420
474
948
58
116
5,000
685
1,370
225
450
513
1,026
61
122
5,000
6,000
730
1,460
235
470
546
1,092
65
130
6,000
7,000
770
1,540
245
490
573
1,146
68
136
7,000
8,000
800
1,600
250
500
600
1,200
72
144
8,000
9,000
835
1,670
255
510
624
1,248
75
150
3,000
4,000
65
RS
FI
2,500
130
865
1,730
260
520
645
1,290
78
156
10,000 12,000
875
1,750
270
540
687
1,374
82
164
12,000 14,000
885
1,770
275
550
723
1,446
87
174
14,000 16,000
900
1,800
280
560
756
1,512
90
180
16,000 18,000
940
1,880
285
570
786
1,572
94
188
18,000 20,000
975
1,950
290
580
813
1,626
98
196
20,000 25,000
1,055
2,000
315
630
876
1,752
105
210
25,000 30,000
1,130
2,000
340
680
933
1,866
112
224
30,000 35,000
1,205
2,000
360
720
981
1,962
119
238
35,000 40,000
1,275
2,000
380
760
1,026
2,000
248
40,000 45,000
1,340
2,000
400
800
1,068
2,000
129
258
45,000 50,000
1,400
2,000
420
840
124
1,104
2,000
135
270
50,000 55,000
1,460
2,000
440
880
1,140
2,000
140
280
55,000 60,000
1,515
2,000
455
910
1,173
2,000
145
290
60,000 65,000
1,565
2,000
470
940
1,206
2,000
150
300
65,000 70,000
1,610
2,000
485
970
1,236
2,000
155
310
70,000 75,000
1,655
2,000
500
1,000
1,263
2,000
160
320
75,000 80,000
1,695
2,000
510
1,020
1,293
2,000
165
330
80,000 85,000
1,730
2,000
520
1,040
1,317
2,000
170
340
85,000 90,000
1,760
2,000
530
1,060
1,344
2,000
175
350
90,000 95,000
1,790
2,000
540
1,080
1,368
2,000
180
360
95,000 100,000
1,815
2,000
545
1,090
1,392
2,000
185
370
100,000 110,000
1,835
2,000
550
1,100
1,437
2,000
195
390
110,000 120,000
1,855
2,000
555
1,110
1,479
2,000
205
410
120,000 130,000
1,875
2,000
560
1,120
1,521
2,000
215
430
130,000 140,000
1,890
2,000
565
1,130
1,557
2,000
225
450
140,000 150,000
1,900
2,000
570
1,140
1,593
2,000
235
470
DR
FI
AF
10,000
RS
9,000
150,000 160,000
1,935
2,000
580
1,160
1,629
2,000
245
490
160,000 170,000
1,965
2,000
590
1,180
1,662
2,000
255
510
170,000 180,000
1,990
2,000
600
1,200
1,695
2,000
265
530
180,000 190,000
2,010
2,010
605
1,210
1,725
2,000
275
550
190,000 200,000
2,030
2,030
610
1,220
1,755
2,000
285
570
200,000 210,000
2,055
2,055
620
1,240
1,782
2,000
295
590
210,000 230,000
2,100
2,100
635
1,270
1,836
2,000
315
630
230,000 250,000
2,155
2,155
650
1,300
1,890
2,000
335
670
66
250,000 275,000
2,215
2,215
670
1,340
1,950
2,000
360
720
FI
RS
DR
AF
275,000 300,000
2,275
2,275
690
1,380
2,000
2,000
385
770
Superscript numerals refer to explanatory footnotes.
Explanatory Notes Essential to the Application of the American Table of Distances for Storage
of Explosives.
(1) Explosive materials means explosives, blasting agents, and detonators.
(2) Explosives means any chemical compound, mixture, or device, the primary or common purpose
of which is to function by explosion. A list of explosives determined to be within the coverage of Title
18, United States Code, Chapter 40, Importation, Manufacture, Distribution and Storage of Explosive
Materials, is issued at least annually by the Director of the Bureau of Alcohol, Tobacco, and Firearms
of the Department of the Treasury. For quantity and distance purposes, detonating cord of 50 grains
per foot should be calculated as equivalent to 8 lb (3.7 kg) of high explosives per 1000 ft (305 m).
Heavier or lighter core loads should be rated proportionately.
(3) Blasting agents means any material or mixture consisting of fuel and oxidizer, intended for
blasting, and not otherwise defined as an explosive, provided that the finished product, as mixed for
use or shipment, cannot be detonated by means of a No. 8 test blasting cap where unconfined.
(4) Detonator means any device containing any initiating or primary explosive that is used for
initiating detonation. A detonator may not be permitted to contain more than 10 g of total explosives
by weight, excluding ignition or delay charges. The term includes, but is not limited to, electric blasting
caps of instantaneous and delay types, blasting caps for use with safety fuses, detonating cord delay
connectors, and nonelectric instantaneous and delay blasting caps that use detonating cord, shock
tube, or any other replacement for electric leg wires. All types of detonators in strengths through No. 8
cap should be rated at 1 lb (0.7 kg) of explosives per 1000 caps.
(5) For strengths higher than No. 8 cap, the manufacturer should be consulted.
(6) Magazine means any building, structure, or container, other than an explosives manufacturing
building, approved for the storage of explosive materials.
(7) Natural barricade means natural features of the ground, such as hills, or timber of sufficient
density that the surrounding exposures that need protection cannot be seen from the magazine when
the trees are bare of leaves.
(8) Artificial barricade means an artificial mound or revetted wall of earth of a minimum thickness of
3 ft (0.9 m).
(9) Barricaded means the effective screening of a building containing explosive materials from the
magazine or another building, a railway, or a highway by a natural or an artificial barrier. A straight
line from the top of any sidewall of the building containing explosive materials to the eave line of any
magazine or other building or to a point 12 ft (3.7 m) above the center of a railway or highway shall
pass through such barrier.
(10) Inhabited building means a building regularly occupied in whole or part as a habitation for
human beings, or any church, schoolhouse, railroad station, store, or other structure where people
are accustomed to assemble, but does not include any building or structure occupied in connection
with the manufacture, transportation, storage, or use of explosive materials.
(11) Railway means any steam, electric, or other railroad or railway that carries passengers for hire.
(12) Public Highway means any road, street, or way, whether on public or private property, open to
public travel.
(13) Where two or more storage magazines are located on the same property, each magazine shall
comply with the minimum distances specified from inhabited buildings, railways, and highways, and,
in addition, they should be separated from each other by not less than the distances shown for
separation of magazines, except that the quantity of explosive materials contained in detonator
67
FI
RS
DR
AF
magazines shall govern with regard to the spacing of said detonator magazines from magazines
containing other explosive materials. If any two or more magazines are separated from each other by
less than the specified separation of magazines distances, such magazines, as a group, shall be
considered as one magazine, and the total quantity of explosive materials stored in such group shall
be treated as if stored in a single magazine located on the site of any magazine of the group, and
shall comply with the minimum specified distances from other magazines, inhabited buildings,
railways, and highways.
(14) Storage in excess of 300,000 lb (136,200 kg) of explosive materials in one magazine generally is
not necessary for commercial enterprises.
(15) This table applies only to the manufacture and permanent storage of commercial explosive
materials. It is not applicable to the transportation of explosives or any handling or temporary storage
necessary or incident thereto. It is not intended to apply to bombs, projectiles, or other heavily
encased explosives.
(16) Where a manufacturing building on an explosive materials plant site is designed to contain
explosive materials, the building shall be located at a distance from inhabited buildings, public
highways, and passenger railways in accordance with the American Table of Distances based on the
maximum quantity of explosive materials permitted to be in the building at one time.
Source: Reprinted from IME Safety Library Publication No. 2, with permission of the Institute of
Makers of Explosives, revised in June of 1991.
[495: Table 9.4.1(b)]
34.3.3.3.1 Explosives that are in accordance with NFPA 495 shall not be required to comply with
34.3.3.3.
34.3.3.3.2 Distances shall be measured from the perimeter wall to property lines, including those on
a public way.
34.3.3.3.3 Quantities of explosives used in applying Table 34.3.3.3 shall be based on equivalent
pounds (kilograms) of TNT.
34.3.3.4 Frangible Building. Frangible buildings complying with 7.4.1.4.5.3 shall not be required to
be protected with an automatic sprinkler system.
34.3.4 Protection Level 2.
34.3.4.1 General. Buildings, or portions thereof, required to comply with Protection Level 2 shall
comply with 34.3.2 and 34.3.4.2 through 34.3.4.5.
34.3.4.2 Exterior Wall Required.
34.3.4.2.1 Buildings, or portions thereof, required to comply with Protection Level 2 shall be located
on property such that not less than 25 percent of the perimeter wall is an exterior wall.
34.3.4.2.2 Rooms utilized for the use, dispensing, mixing, and storage of flammable and
combustible liquids having a floor area of not more than 500 ft2 (46.5 m2) shall not be required to be
located on the outer perimeter of the building where such rooms comply with NFPA 30.
34.3.4.3 Minimum Distance to Property Lines or Horizontal Separation.
34.3.4.3.1 Buildings, or portions thereof, required to comply with Protection Level 2 shall be set back
from property lines, or be provided with a horizontal separation in accordance with 7.3.4.2, at any of
the following distances:
(1)
Not less than 30 ft (9.1 m) where the area of the occupancy exceeds 1000 ft2 (93 m2) and a
detached building is not required
(2)
Not less than 50 ft (15 m) where a detached building is required by Table 34.3.4.4.1
(3)
Not less than the distances required by Table 34.3.3.3 for buildings containing materials with
explosive characteristics
68
34.3.4.3.2 Distances shall be measured from the walls enclosing the Protection Level 2 area to
property lines, including those on a public way, or in accordance with 7.3.4.2 for buildings on the
same lot.
34.3.4.4 Detached Building Required.
34.3.4.4.1 Buildings required to comply with Protection Level 2, and containing quantities of high
hazard contents exceeding the quantity limits set forth in Table 34.3.4.4.1, shall be used for
manufacturing, processing, dispensing, use, or storage of hazardous materials and no other purpose;
shall not exceed one story in height; and shall be without basements, crawl spaces, or other underfloor spaces.
Table 34.3.4.4.1 High Hazard Level 2 and High Hazard Level 3 MaterialsRequired Detached
Storage
Class 2
2,000
AF
NA
Class II
25
NA
Class III
50
NA
Class 3, nondetonable
2,000
Class 2
25
10,000
Class 3
NA
25
NA
NA
2,000
Material
Class
Class 3
Organic peroxides
Unstable reactives
Water-reactive
Class 2, deflagrating
1,200
NA
RS
Pyrophoric gases
Gases
(ft3)
DR
Oxidizers
Solids and
Liquids
(tons)
FI
69
FI
RS
DR
AF
34.3.4.5.2 Piping for conveying water, other than fire protection piping, shall not route over or
through areas containing Class 2 or Class 3 water-reactive materials, unless isolated by approved
liquid-tight construction.
34.3.5 Protection Level 3.
34.3.5.1 General. Buildings, or portions thereof, required to comply with Protection Level 3 shall
comply with 34.3.2 and 34.3.5.2 through 34.3.5.7.
34.3.5.2 Exterior Wall Required.
34.3.5.2.1 Buildings, or portions thereof, required to comply with Protection Level 3 shall be located
on property such that not less than 25 percent of the perimeter wall is an exterior wall.
34.3.5.2.2 Rooms utilized for the use, dispensing, mixing, and storage of flammable and
combustible liquids having a floor area of not more than 500 ft2 (46.5 m2) shall not be required to be
located on the outer perimeter of the building where such rooms are in accordance with NFPA 30.
34.3.5.3 Minimum Distance to Property Lines or Horizontal Separation.
34.3.5.3.1 Buildings, or portions thereof, required to comply with Protection Level 3 shall be set back
from property lines, or be provided with a horizontal separation in accordance with 7.3.4.2, at any of
the following distances:
(1)
Not less than 30 ft (9.1 m) where the area of the occupancy exceeds 1000 ft2 (93 m2) and a
detached building is not required
(2)
Not less than 50 ft (15 m) where a detached building is required by Table 34.3.4.4.1
(3)
Not less than the distances required by Table 34.3.3.3 for buildings containing materials with
explosive characteristics
34.3.5.3.2 Distances shall be measured from the walls enclosing the Protection Level 3 area to
property lines, including those on a public way, or in accordance with 7.3.4.2 for buildings on the
same lot.
34.3.5.4 Detached Building Required.
34.3.5.4.1 Buildings required to comply with Protection Level 3, and containing quantities of high
hazard contents exceeding the quantity limits set forth in Table 34.3.4.4.1, shall be used for
manufacturing, processing, dispensing, use, or storage of hazardous materials and no other purpose;
shall not exceed one story in height; and shall be without basements, crawl spaces, or other underfloor spaces.
34.3.5.4.2 Buildings that contain high hazard Level 3 contents also shall be permitted to contain high
hazard Level 2 or high hazard Level 4 contents, provided that incompatible materials are separated
as otherwise required by the provisions of this Code and NFPA 1.
34.3.5.4.2.1 Buildings required to comply with Protection Level 2, Protection Level 3, or Protection
Level 4 requirements shall comply with the most restrictive requirements for the applicable protection
levels.
34.3.5.4.2.2 Hazardous materials permitted in manufacturing, processing, dispensing, use, or
storage areas shall not be restricted to the materials listed in Table 34.3.4.4.1.
34.3.5.5 Detached Unprotected Building. Where acceptable to the authority having jurisdiction,
based on a determination that a protected building is not practical and an assessment of acceptable
risk, storage buildings required to comply with Protection Level 3 shall be permitted without fire
protection systems, provided that all of the following provisions are met:
(1)
The building, or portions thereof, shall comply with either of the following:
(a)
It shall have a horizontal separation of at least 200 ft (61 m) from exposed business, industrial,
mercantile, and storage occupancies on the same lot and from any property line that is or can be built
upon.
(b)
Where protection for exposures is provided in accordance with 34.3.5.5(9), the horizontal
separation shall be at least 100 ft (30 m).
70
FI
RS
DR
AF
(2)
The building, or portions thereof, shall comply with either of the following:
(a)
It shall have a horizontal separation of at least 1000 ft (305 m) from exposed occupancies
other than business, industrial, mercantile, and storage occupancies on the same lot and from any
property line that is or can be built upon.
(b)
Where protection for exposures is provided in accordance with 34.3.5.5(9), the horizontal
separation shall be at least 500 ft (150 m).
(3)
The building shall not exceed one story in height.
(4)
The building shall not have basements, crawl spaces, or other under-floor accessible spaces.
(5)
Egress from the building shall not exceed 50 percent of the distances listed in Table
34.3.2.4.1, measured as required in 11.6.3 and in compliance with 34.3.2.4.2 through 34.3.2.4.5.
(6)
The building shall comply with the requirements of all of the following:
(a)
34.3.2.2 for building height
(b)
34.3.2.5 for ventilation
(c)
34.3.2.6 for explosion control
(d)
34.3.2.7 for standby and emergency power
(e)
34.3.2.9 for floor construction
(f)
34.3.2.10 for unprotected vertical openings
(7)
Spill control shall comply with 34.3.2.8.2.
(8)
Secondary containment shall comply with 34.3.2.8.3, except that containment for fire
protection water shall not be required if the building is not provided with a fire protection sprinkler
system.
(9)
Where credit is taken for protection for exposures in accordance with 34.3.5.5(1) or (2),
protection of exposures shall consist of fire protection for structures on property adjacent to the
storage building that is provided by (1) a public fire department or (2) a private fire brigade maintained
on the property adjacent to the storage building, either of which shall be capable of providing cooling
water streams to protect the property adjacent to the storage building.
34.3.5.6 Roofs. The roofs of buildings specified in 34.3.5.4 and 34.3.5.5 shall be of lightweight
construction with suitable thermal insulation to prevent sensitive material from reaching its
decomposition temperature.
34.3.5.7 Water-Reactive Materials.
34.3.5.7.1 Rooms or areas containing Class 2 or Class 3 water-reactive materials shall be resistant
to water penetration.
34.3.5.7.2 Piping for conveying water, other than fire protection piping, shall not route over or
through areas containing Class 2 or Class 3 water-reactive materials, unless isolated by approved
liquid-tight construction.
34.3.5.8 Class I, Class II, and Class IIIA Flammable and Combustible Liquids.
34.3.5.8.1 Rooms used for the storage of Class I flammable liquids shall not be located in the
basement.
34.3.5.8.2 Rooms in excess of 500 ft2 (46.5 m2) shall have at least one exterior door approved for
fire department access.
34.3.6 Protection Level 4. Buildings, or portions thereof, required to comply with Protection Level 4
shall comply with 34.3.2, 34.3.6.1, and 34.3.6.2.
34.3.6.1 Gas Rooms. Exhaust ventilation for gas rooms shall be designed to operate at a negative
pressure in relation to the surrounding areas and shall direct the exhaust ventilation to an exhaust
system.
34.3.6.2 Highly Toxic Solids and Liquids. Highly toxic solids and liquids not stored in approved
hazardous materials storage cabinets shall be isolated from other hazardous materials storage by a
1-hour fire barrier.
71
RS
DR
AF
FI
Table 34.3.7.2.1.2(A) Quantity Limits for Hazardous Materials in a Single Fabrication Area a
Solids
(lb/ft2)
Liquids
(gal/ft2)
Gas
(ft3 at
NTP/ ft2)
II
NA
0.01
NA
IIIA
NA
0.02
NA
IIIB
NA
NL
NA
Hazard Category
Combustible liquid
72
NA
0.04
NA
Flammable
NA
NA
See footnote b.
Oxidizing
NA
NA
1.25
See footnote c.
See footnote c.
See footnote c.
Gaseous
NA
NA
See footnote b.
Liquefied
NA
NA
See footnote b.
IA
NA
0.0025
NA
IB
NA
0.025
NA
IC
NA
0.025
NA
0.025
NA
0.04
NA
Cryogenic
Explosives
NA
NA
DR
AF
Flammable liquid
Flammable gas
Flammable solid
0.001
NA
NA
See footnote c.
See footnote c.
NA
See footnote c.
See footnote c.
NA
II
0.025
0.0025
NA
0.1
0.01
NA
NL
NL
NA
NL
NL
NA
NA
NA
1.25
NA
NA
1.25
NA
NA
1.25
See footnote c.
See footnote c.
NA
0.003
0.003
NA
0.003
0.003
NA
NL
NL
NA
0.003
0.003
NA
Organic peroxide
Unclassified detonable
IV
V
Oxidizing gas
Gaseous
FI
Liquefied
RS
III
Combination of gaseous
and liquefied
Oxidizer
Combination oxidizer
73
Classes 1, 2, and 3
Pyrophoric
See footnote c.
0.00125
See footnote c.
See footnote c.
See footnote c.
0.025
0.0025
See footnote c.
0.1
0.01
See footnote c.
NL
NL
NL
See footnote c.
0.00125
NA
0.25
0.025
NA
NL
NL
NA
NL
NL
NL
See footnote b.
Unstable reactive
NL
Highly toxic
NL
Toxic
NL
AF
Corrosive
Water-reactive
FI
RS
DR
NL
See footnote b.
For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L; 1 ft2 = 0.093 m2; 1 ft3 = 0.0283 m3.
NTP: Normal temperature and pressure [measured at 70F (21C) and 14.7 psi (30 kPa)].
NA: Not applicable.
NL: Quantity of hazardous materials in a single fabrication area not limited.
a Hazardous materials within piping are not permitted to be included in the calculated quantities.
b The aggregate quantity of flammable, pyrophoric, toxic, and highly toxic gases is not permitted to
exceed 9000 ft3 (254.9 m3) at NTP.
c The quantity of hazardous materials in a single fabrication is not permitted to exceed the MAQ per
control area in Table 34.1.3.1.
d The aggregate quantity of pyrophoric gases in the building is not permitted to exceed quantity limits
set forth in Table 34.3.4.4.1.
(B) Storage of hazardous materials classified as HPM shall be further limited such that the quantity
stored within a single fabrication area does not exceed the MAQ per control area set forth in Table
34.1.3.1.
34.3.7.2.1.3 Fire-Resistive Separation. Fabrication areas shall be separated from other parts of the
building, including exit access corridors, by not less than 1-hour fire resistancerated assemblies.
(A) Doors within the assemblies specified in 34.3.7.2.1.3, including doors to corridors, shall be selfclosing fire door assemblies with a -hour or greater fire resistance rating.
(B) Windows between fabrication areas and exit access corridors shall be permitted to be fixed
glazing listed and labeled for a fire protection rating of at least hour.
(C) Where it is necessary to construct multiple adjoining fabrication areas to comply with the
hazardous materials quantity limits specified in 34.3.7.2.1.2(A), 1-hour fire resistancerated
assemblies shall be provided to separate the fabrication areas from each other in accordance with
Chapter 7.
34.3.7.2.1.4 Floors.
(A) Except for surfacing, floors within fabrication areas shall be of noncombustible construction.
(B) Floors of fabrication areas separating fabrication areas from other uses shall be liquid-tight.
74
FI
RS
DR
AF
34.3.7.2.1.5 Vertical Openings. Openings through floors of fabrication areas shall be permitted to
be unprotected in accordance with 8.12.5 where the interconnected levels are used solely for
mechanical equipment directly related to the fabrication areas.
(A) Mechanical, duct, and piping penetrations within a fabrication area shall not extend through
more than two floors.
(B) The annular space around equipment passing through the penetrations shall be sealed at the
floor level to restrict the movement of air.
(C) The fabrication area, including levels interconnected with ductwork and piping, shall be regulated
as a single conditioned environment.
34.3.7.2.1.6 Egress from Fabrication Areas. In areas required to comply with Protection Level 5,
the travel distance within a fabrication area to an exterior exit door, an exit access corridor, a
horizontal exit, an exit passageway, or an enclosed exit stairway shall not exceed 200 ft (61 m).
34.3.7.2.2 Exit Access Corridors.
34.3.7.2.2.1 Exit access corridors shall be separated from fabrication areas as specified in
34.3.7.2.1.3.
34.3.7.2.2.2 Exit access corridors shall not contain HPM and shall not be used for transporting HPM,
except through closed piping systems complying with 34.3.7.3.1.3.
34.3.7.2.3 Service Corridors. Service corridors shall be permitted to be regulated as part of the
Protection Level 5 area.
34.3.7.2.3.1 Minimum Width. The clear width of a service corridor shall be not less than 60 in.
(1525 mm) and shall be not less than 33 in. (840 mm) wider than the widest cart or truck used in the
corridor.
34.3.7.2.3.2 Fire-Resistive Separation. Service corridors shall be separated from exit access
corridors as required by 34.3.7.2.1.3.
34.3.7.2.3.3 Exiting.
(A) Service corridors shall not be used as a required exit access corridor.
(B) Service corridors shall be provided with two or more exits, and not more than one-half of the
required number of exits shall lead to the fabrication area.
(C) The travel distance within a service corridor to an exit or to a door into a fabrication area shall
not exceed 75 ft (23 m).
(D) Dead ends shall not exceed 48 in. (1220 mm).
(E) Doors from service corridors shall swing in the direction of exit travel and shall be self-closing.
34.3.7.2.4 Storage Areas for HPM.
34.3.7.2.4.1 General.
(A) The storage of HPM in fabrication areas in quantities not exceeding the limits set forth in Table
34.1.3.1 shall be within approved or listed storage cabinets, within gas cabinets, or within a
workstation.
(B) The storage of HPM in quantities greater than those specified in Table 34.1.3.1 shall be in gas
rooms complying with 34.3.6.1 or HPM rooms complying with 34.3.7.2.4.2, as appropriate for the
materials stored.
(C) The storage of hazardous materials other than HPM shall be in accordance with other applicable
provisions of this Code and NFPA 1.
34.3.7.2.4.2 HPM Rooms.
(A) HPM rooms shall be constructed as required for the applicable protection level, based on the
classification of hazardous materials stored therein.
(B) HPM rooms shall be separated from other areas by not less than a 2-hour fire barrier wall and
horizontal assembly, where the area is 300 ft2 (27.9 m2) or more, and by not less than 1-hour fire
resistancerated construction where the area is less than 300 ft2 (27.9 m2).
75
(C) Where two means of egress are required by 34.3.2.4.3 for an HPM room, or gas room, one
means of egress shall be directly to the outside of the building.
(D) Except for surfacing, floors of HPM rooms shall be of noncombustible liquid-tight construction.
(E) Raised grating over floors shall be of noncombustible materials.
34.3.7.2.4.3 Doors. Door openings to HPM rooms and gas rooms that penetrate a fire barrier wall,
including doors to corridors, shall be self-closing fire door assemblies having a fire protection rating of
not less than hour.
34.3.7.2.4.4 Ventilation. Ventilation for HPM rooms and gas rooms shall comply with 34.3.2.5.
34.3.7.2.4.5 Emergency Alarm System. Emergency alarms for HPM rooms and gas rooms shall
comply with 34.3.7.3.6.2.
34.3.7.2.4.6 Separation of HPM. HPM stored in HPM rooms and gas rooms shall be separated
from incompatible materials in accordance with Table 34.3.7.2.4.6.
Table 34.3.7.2.4.6 Minimum Separation of HPM
NR
1 hr 1 hr
Toxic
NR
Acid
1 hr
Base
1 hr
Flammable
1 hr
Oxidizer
1 hr
WaterReactive
1 hr
Pyrophoric
1 hr
Unstable
Reactives
1 hr
1 hr
RS
S
1 hr
1 hr
1 hr
1 hr
1 hr
DR
Highly
Toxic
AF
Highly
WaterUnstable Organic
Toxic Toxic Acid Base Flammable Oxidizer Reactive Pyrophoric Reactives Peroxide
Material
FI
Organic
1 hr
S
S
S
S
S
S
S
S
Peroxide
NR: Not required.
1 hr: 1-hour fire resistancerated construction.
S: Separation by a partial noncombustible partition extending not less than 18 in. (455 mm) above
and to the sides of the stored material.
R: Separate rooms, which are not required to have a fire resistance rating.
Note: HPM gases are required to be separated from HPM liquids and solids by 1-hour fire resistance
rated construction or are required to be kept in approved gas cabinets. HPM gases also are required
to be separated from gases in other HPM hazard categories, as required by Table 34.3.7.2.4.6, or are
required to be kept in approved gas cabinets.
Separation by not less than 20 ft (6.1 m) is permitted in lieu of a noncombustible partition.
34.3.7.2.5 Emergency Control Station.
76
FI
RS
DR
AF
77
FI
RS
DR
AF
34.3.7.3.2.2 The requirements for hazardous locations shall not be required to be applied where the
average air change is at least four times that set forth in 34.3.7.3.3 and where the number of air
changes at any location is not less than three times that required by 34.3.7.3.3.
34.3.7.3.2.3 The use of recirculated air shall be permitted.
34.3.7.3.2.4 Workstations shall not be energized without adequate exhaust ventilation. (See
34.3.7.3.3 for workstation exhaust ventilation requirements.)
34.3.7.3.3 Ventilation Systems.
34.3.7.3.3.1 Fabrication Area. Mechanical exhaust ventilation shall be provided throughout the
fabrication area at the rate of not less than 1 ft3/min/ft2 (0.044 L/s/m2) of floor area.
(A) The use of recirculated air shall be permitted to meet the average and minimum number of air
changes specified in 34.3.7.3.3.2.
(B) The exhaust air duct system of one fabrication area shall not connect to another duct system
outside that fabrication area within the building.
(C) Ventilation shall be provided to capture and exhaust fumes and vapors at workstations.
(D) Two or more operations at a workstation shall not be connected to the same exhaust system
where either one or the combination of the substances removed could constitute a fire, an explosion,
or a hazardous chemical reaction within the exhaust duct system.
(E) Exhaust ducts penetrating occupancy separations shall be contained in a shaft of equivalent fire
resistancerated construction.
(F) Exhaust ducts shall not penetrate fire walls.
(G) Fire dampers shall not be installed in exhaust ducts.
(H) The area below the raised floor in a fabrication area and the interstitial spaces above a
fabrication area, used solely for building or process systems directly related to the level above or
below a fabrication area, shall not be considered a plenum.
34.3.7.3.3.2 Ventilation of Service Corridors, HPM Rooms, and Gas Rooms. Service corridors,
HPM rooms, and gas rooms shall be mechanically ventilated at 1 ft3/min/ft2 (0.044 L/s/m2) or six air
changes per hour, whichever is greater.
34.3.7.3.4 Gas Detection Systems. A continuous gas detection system shall be provided in the
locations described in 34.3.7.3.4.1 through 34.3.7.3.4.4 for HPM gases where the physiological
warning properties of the gas are at a higher level than the accepted permissible exposure limit (PEL)
for the gas and for flammable gases.
34.3.7.3.4.1 Fabrication Areas. A continuous gas detection system shall be provided at locations in
fabrication areas where gas is used.
34.3.7.3.4.2 HPM Rooms. A continuous gas detection system shall be provided in HPM rooms that
do not comply with the requirements for gas rooms where gas is used in the room.
34.3.7.3.4.3 Gas Cabinets, Exhausted Enclosures, and Gas Rooms.
(A) A continuous gas detection system shall be provided in gas cabinets and exhausted enclosures.
(B) A continuous gas detection system shall be provided in gas rooms where gases are not located
in gas cabinets or exhausted enclosures.
34.3.7.3.4.4 Exit Access Corridors.
(A) Where gases are transported in piping placed within the space defined by the walls of an exit
access corridor and the floor or roof above the exit access corridor, a continuous gas detection
system shall be provided where piping is located and in the exit access corridor.
(B) The continuous gas detection system shall not be required for occasional transverse crossings
of the corridors by supply piping that is enclosed in a ferrous pipe or tube for the width of the corridor.
34.3.7.3.4.5 Gas Detection System Operation. The continuous gas detection system shall be
capable of monitoring the room, area, or equipment in which the gas is located for levels at or below
the following gas concentrations:
78
FI
RS
DR
AF
(1)
Immediately dangerous to life or health (IDLH) levels when the monitoring point is within an
exhausted enclosure
(2)
PEL levels when the monitoring point is in an area outside an exhausted enclosure
(3)
Twenty-five percent of LFL when the monitoring point is within or outside an exhausted
enclosure
(4)
In addition, monitoring for highly toxic and toxic gases in compliance with the requirements of
NFPA 1 for highly toxic and toxic material
34.3.7.3.4.6 Alarms. The gas detection system shall be provided with an emergency alarm
complying with 34.3.7.3.6.3.
34.3.7.3.4.7 Shutoff of Gas Supply.
(A) The gas detection system shall automatically close the shutoff valve at the source on gas supply
piping and tubing related to the system being monitored for which gas is detected when a short-term
hazard condition is detected.
(B) Where the gas detection sampling point initiating the gas detection system alarm is at the use
location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold,
the shutoff valve for the branch line located in the piping distribution manifold enclosure shall
automatically close.
(C) Automatic closure of shutoff valves shall comply with any one of the following:
(1)
Where the gas detection sampling point initiating the gas detection system alarm is within a
gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for
the specific gas detected shall automatically close.
(2)
Where the gas detection sampling point initiating the gas detection system alarm is within a
room, and compressed gas containers are not in gas cabinets or an exhausted enclosure, the shutoff
valves on all gas lines for the specific gas detected shall automatically close.
(3)
Where the gas detection sampling point initiating the gas detection system alarm is within a
piping distribution manifold enclosure, the shutoff valve for the compressed gas container of the
specific gas detected supplying the manifold shall automatically close.
34.3.7.3.5 Manual Fire Alarm System.
34.3.7.3.5.1 An approved manual fire alarm system shall be provided throughout buildings required
to comply with Protection Level 5.
34.3.7.3.5.2 Activation of the alarm system shall initiate a local alarm and transmit a signal to the
emergency control station.
34.3.7.3.5.3 The fire alarm system shall be designed and installed in accordance with NFPA 72,
National Fire Alarm and Signaling Code.
34.3.7.3.6 Emergency Alarm System.
34.3.7.3.6.1 Exit Access Corridors and Service Corridors.
(A) An approved emergency alarm system shall be provided for exit access corridors and service
corridors.
(B) Emergency alarm-initiating devices shall be installed in exit access corridors and service
corridors at not more than 150 ft (46 m) intervals and at each exit and exit access doorway.
34.3.7.3.6.2 HPM Rooms and Gas Rooms.
(A) An approved emergency alarm system shall be provided for HPM rooms and gas rooms.
(B) Emergency alarm-initiating devices shall be installed outside of each interior exit access door for
HPM rooms and gas rooms.
34.3.7.3.6.3 Gas Detection Systems.
(A) Gas detection systems shall initiate an alarm when a short-term hazard condition is detected.
(B) The local alarm shall be both visual and audible and shall provide warning both inside and
outside the area where the gas is detected.
79
FI
RS
DR
AF
(C) The audible alarm shall be distinct from all other alarms.
34.3.7.3.6.4 Alarm-Initiating Devices. An approved emergency telephone system, a local alarm
manual pull station, or other approved alarm-initiating devices shall be permitted to be used as
emergency alarm-initiating devices.
34.3.7.3.6.5 Alarm Notification. Activation of the emergency alarm system shall sound a local
alarm and notify the emergency control station.
34.3.7.3.7 Emergency Power System. An emergency power system shall be provided for
buildings, or portions thereof, required to comply with Protection Level 5 where required in
34.3.7.3.7.2.
34.3.7.3.7.1 Design. The emergency power system shall be designed to automatically supply power
to required electrical systems when the normal electrical supply system is interrupted.
34.3.7.3.7.2 Where Required. Emergency power shall be provided for electrically operated
equipment and connected control circuits for all of the following systems:
(1)
HPM exhaust ventilation systems
(2)
HPM gas cabinet ventilation systems
(3)
HPM exhausted enclosure ventilation systems
(4)
HPM gas room ventilation systems
(5)
HPM gas detection systems
(6)
Emergency alarm systems
(7)
Electrically operated systems required elsewhere in this Code applicable to the use, storage,
or handling of HPM
34.3.7.3.7.3 Emergency Power for Exhaust Ventilation Systems. Exhaust ventilation systems
shall be permitted to be designed to operate at not less than one-half the normal fan speed on the
emergency power system where it is demonstrated that the level of exhaust will maintain a safe
atmosphere.
34.3.7.3.7.4 Emergency Power for Detection, Alarm, and Communications Systems. Power for
detection, alarm, and communications systems shall be in accordance with NFPA 72.
34.3.7.3.8 Fire Sprinkler System Protection in Exhaust Ducts for HPM.
34.3.7.3.8.1 General. Automatic fire sprinkler system protection shall be provided in exhaust ducts
conveying vapors, fumes, mists, or dusts generated from HPM in accordance with 34.3.7.3.8.2
through 34.3.7.3.8.4 and the Uniform Mechanical Code, as referenced in Chapter 50.
34.3.7.3.8.2 Metallic Exhaust Ducts and Noncombustible Nonmetallic Exhaust Ducts.
Automatic fire sprinkler system protection shall be provided in metallic exhaust ducts and
noncombustible, nonmetallic exhaust ducts where all of the following conditions apply:
(1)
Where the largest cross-sectional diameter is equal to or greater than 10 in. (255 mm), or the
cross-sectional cylindrical or rectangular area is greater than or equal to 80 in.2 (516 cm2)
(2)
Where the ducts are within the building
(3)
Where the ducts are conveying flammable vapors or fumes
34.3.7.3.8.3 Combustible Nonmetallic Exhaust Ducts. Automatic fire sprinkler system protection
shall be provided in combustible nonmetallic exhaust ducts where the largest cross-sectional
diameter of the duct is equal to or greater than 10 in. (255 mm), or the cross-sectional cylindrical or
rectangular area is greater than or equal to 80 in.2 (516 cm2).
(A) Ducts that are listed or approved for applications without automatic fire sprinkler system
protection shall not be required to comply with 34.3.7.3.8.3.
(B) Ducts that are not more than 12 ft (3660 mm) in length and installed below ceiling level shall not
be required to comply with 34.3.7.3.8.3.
34.3.7.3.8.4* Automatic Sprinkler Locations.
80
DR
AF
(A) Sprinkler systems shall be installed at 12 ft (3660 mm) intervals in horizontal ducts and at
changes in direction.
(B) In vertical ducts, sprinklers shall be installed at the top and at alternate floor levels.
A.29.1.1.1 See A.6.1.12.1 for a list of uses that would be considered industrial low occupancies and
industrial occupancies.
A.29.1.67 In most cases, the requirements for maximum travel distance to exits will be the
determining factor rather than numbers of occupants, as exits provided to satisfy travel distance
requirements will be sufficient to provide egress capacity for all occupants, except in cases of unusual
arrangement of buildings or high occupant load of a general manufacturing occupancy.
A.29.2.1.2 Horizontal and vertical utility chases in large industrial buildings used for routing of piping,
ducts, and wiring must provide a reasonable level of access for occasional use by maintenance
workers but do not warrant compliance with the comprehensive egress requirements of Chapter 11.
Minimum access in these cases is governed by electrical and mechanical codes, 29.2.5.3, and the
Occupational Safety and Health Administration (OSHA) for facilities in the United States. Utility
chases governed by 29.2.1 might involve tunnels or large open spaces located above or below
occupied floors; however, they differ from mechanical equipment rooms, boiler rooms, and furnace
rooms based on the anticipated frequency of use by maintenance workers. Portions of utility chases
where the anticipated presence of maintenance workers is routine are not intended to be
encompassed by 29.2.1.
A.29.2.2.5.2 The customary building code requirement for fire doors on both sides of an opening in
a fire wall is permitted to be met by having an automatic-sliding fire door on one side and a selfclosing fire door swinging out from the other side of the wall. This arrangement qualifies only as a
horizontal exit from the side of the sliding door. For further information, see A.11.2.4.3.9.
FI
RS
81
AF
A.30.1.1.1 See A.6.1.13.1 for a list of uses that would be considered as low hazard storage
occupancies.
A.30.1.67 There is no occupant load factor specified for storage occupancies. Rather, the actual
probable maximum number of persons present needs to be considered in determining the occupant
load.
A.30.2.1.2 Horizontal and vertical utility chases in large industrial buildings used for routing of piping,
ducts, and wiring must provide a reasonable level of access for occasional use by maintenance
workers but do not warrant compliance with the comprehensive egress requirements of Chapter 11.
Minimum access in these cases is governed by electrical and mechanical codes, 29.2.5.3 of this
Code, and the Occupational Safety and Health Administration (OSHA) for facilities in the United
States. Utility chases governed by 30.2.1 might involve tunnels or large open spaces located above
or below occupied floors; however, they differ from mechanical equipment rooms, boiler rooms, and
furnace rooms based on the anticipated frequency of use by maintenance workers. Portions of utility
chases where the anticipated presence of maintenance workers is routine are not intended to be
encompassed by 30.2.1.
A.30.2.2.5.2 The customary building code requirement for fire doors on both sides of an opening in
a fire wall is permitted to be met by having an automatic-sliding fire door on one side and a selfclosing fire door swinging out from the other side of the wall. This arrangement qualifies only as a
horizontal exit from the side of the sliding door. For further information, see A.11.2.4.3.9.
DR
RS
FI
82
AF
DR
FI
RS
83
T
AF
DR
FI
RS
84
(3) Mixtures of toxic materials with ordinary materials, such as water, that might not warrant
classification as toxic
Any hazard evaluation that is required for the precise categorization of toxic material is required to be
performed by experienced, technically competent persons. [400,400, 2013]
FI
RS
DR
AF
85