You are on page 1of 9

Standards

Where can you order


IEC publications?
Central Offices of the International
Electrotechnical Commission
1, rue de Varemb Geneva - Switzerland.
The documentation department (Factory A2)
at Merlin Gerin can provide you with
information on the standards.

Schneider Electric

The standards mentioned


in this document

c International Electrotechnical Vocabulary

IEC 60 050

c High voltage alternating current


circuit breakers

IEC 60 056

c Current transformers

IEC 60 185

c Voltage transformers

IEC 60 186

c Alternating current disconnectors


and earthing disconnectors

IEC 60 129

c High voltage switches

IEC 60 265

c Metal-enclosed switchgear for alternating


current at rated voltage of over 1 kV and
less than or equal to 72.5 kV

IEC 60 298

c High-voltage alternating current


combined fuse-switches and combined
fuse-circuit breakers

IEC 60 420

c High-voltage alternating
current contactors

IEC 60 470

c Specifications common to highvoltage switchgear standards

IEC 60 694

c Calculation rules
in industrial installations

IEC 60 909

c Derating

ANSI C37 04

Merlin Gerin MV Design Guide

71

IEC - ANSI comparison

Standards

Overview of the main differences


The following comparison
is based on
different circuit breaker
characteristics.

Theme
asymmetrical breaking
capacity on faults
across the terminals
insulation level:
impulse wave

short-time withstand
current peak
value
Transient Recovery
voltage(1)
electrical endurance
mechanical endurance

ANSI

IEC

50%
with current
derating
imposes chopped waves
for outdoor equipment
115% Uw/3 s
129% Uw/2 s
2.7 Isc

30%
without derating

around twice
as severe
4 times K.S.Isc
1 500 to 10 000
according to Ua and Isc
no text

motor overvoltages

2.5Isc at 50 Hz
2.6Isc at 60 Hz
2.7Isc for special cases

3 times Isc
2 000
standard test circuit

(1) the

ANSI peak voltage is 10% greater than the voltage defined by the IEC.
The E2/t2 slope is 50% greater than the Uc/t3 slope.
However, the largest part of the graph is the initial part where the SF6 reconstitutes itself.
The two standards easily allow the SF6 to reconstitute itself.

Rated voltages
According to IEC
c Standardised values for Ur (kV): 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV

According to ANSI
c The ANSI standard defines a class and a voltage range factor K
which defines a range of rated voltages at constant power.
Standardised values for Ur (kV)
Indoor equipment

Outdoor equipment

class (kV)
4.16
7.2
13.8
38
15.5
25
38

Umax (kV)
4.76
8.25
15
38

Umin (kV)
3.85
6.6
11.5
23

K
1.24
1.25
1.3
1.65
1
1
1

Rated installation level


According to IEC
Rated
voltage
(kV)

Upeak (%)
100
90
50
1.2 s
t (s)

10
50 s

7.2
12
17.5
24
36

Rated lightning
withstand voltage
(kV)

Rated power frequency


withstand voltage
50 Hz 1 mm (kV)

60
75
95
125
170

20
28
38
50
70

Standardised wave 1.2/50 s

72

Merlin Gerin MV Design Guide

Schneider Electric

IEC - ANSI comparison

Standards

According to ANSI
Upeak (%)

Rated
voltage
(kV)

100
90
70
50
10

t (s)
tc

Onde coupe suivant ANSI


pour le matriel d'extrieur

Indoor equipment
4.16
7.2
13.8
38
Outdoor equipment
15.5
25.8
38

Rated lightning
withstand voltage
(kV)

Rated power frequency


withstand voltage
50 Hz 1 mm (kV)

60
95
95
150

19
36
36
80

110
125
150
150
200

50
60
80

N.B.
c BIL: Basic Insulation Level
The outdoor equipment is tested with chopped waves.
c The impulse withstand is equal to:
1.29 BIL for a duration of tc = 2 s
1.15 BIL for a duration tc = 3 s

Rated normal current


According to IEC
c Values of rated current: 400 - 630 - 1250 - 1600 - 2500 - 3150 A

According to ANSI
c Values of rated current: 1200 - 2000 - 3000 A

Short-time withstand current


According to IEC
c Values of short-circuit rated breaking capacity:
6.3 - 8 - 10 - 12.5 - 16 - 20 - 25 - 31.5 - 40 - 50 - 63 kA

According to ANSI
c Values of short-circuit rated breaking capacity:
v indoor equipment: 12.5 - 20 - 25 - 31.5 - 40 kA
v outdoor equipment:
Class (MVA)
250
350
500
750
1000
1500
2750

Schneider Electric

Merlin Gerin MV Design Guide

Breaking capacity (kA)


I at Umax
29
41
18
28
37
21
40

KI at Umin
36
49
23
36
46
35
40

73

Standards

IEC - ANSI comparison

Peak value of short-time current


and closing capacity
According to IEC
c The peak value of short-time withstand current is equal to:
v 2.5Isc at 50 Hz
v 2.6Isc at 60 Hz
v 2.7Isc for special cases.

According to ANSI
c The peak value of short-time withstand current is equal to:
v 2.7 K Isc at peak value
v 1.6 K Isc at rms. value.
(K : voltage factor)

Rated short-circuit duration


According to IEC
c The rated short-circuit duration is equal to 1 or 3 seconds.

According to ANSI
c The rated short-circuit duration is equal to 3 seconds.

Rated supply voltage


for closing and opening
devices and auxiliary circuits
According to IEC
c Supply voltage values for auxiliary circuits:
v for direct current (dc): 24 - 48 - 60 - 110 or 125 - 220 or 250 volts
v for alternating current (ac): 120 - 220 - 230 - 240 volts.
c Operating voltages must fall within the following ranges:
v Motor and closing release units:
-15% to +10% of Ur in dc et ac
v opening release units:
-15% to +10% of Ur in ac; -30% to +10% of Ur in dc
v undervoltage opening release units
the release unit gives
the command and
forbids closing

0%

35 %

the release unit


must not have
an action

70 %

100 %

(at 85%, the release unit must enable


the device to close)

According to ANSI
c Supply voltage values for auxiliary circuits:
v for direct current (dc): 24 - 48 - 125 - 250 volts.
v for alternating (ac): 120 - 240 volts

74

Merlin Gerin MV Design Guide

Schneider Electric

Standards

IEC - ANSI comparison

c Operating voltage must fall within the following ranges:


Voltage

Voltage range (V)

Motor and closing release units


48 Vsc
125 Vsc
250 Vsc
120 Vac
240 Vac

36 to 56
90 to 140
180 to 280
104 to 127
208 to 254

Opening release units


24 Vsc
48 Vsc
125 Vsc
250 Vsc
120 Vac
240 Vac

14 to 28
28 to 56
70 to 140
140 to 220
104 to 127
208 to 254

Rated frequency
According to IEC
c Rated frequency: 50 Hz.

According to ANSI
c Rated frequency: 60 Hz.

Short-circuit breaking capacity


at the rated operating sequence
c ANSI specifies 50% asymmetry and IEC 30%. In 95% of applications,
30% is sufficient. When 30% is too low, there are specific cases (proximity
of generators) for which the asymmetry may be greater than 50%.
c For both standard systems, the designer has to check the circuit breaker
breaking capacity. The difference is not important because without taking
account of the asymmetry factor "S", it is equal to 10%.

(1 + 2 A2) = 1.22 Isym (A = 50%)

ANSI: Iasym = Isym

(1 + 2 A2) = 1.08 Isym (A = 30%)

IEC: Iasym = Isym

According to IEC
c Short-circuit breaking tests must meet the following 5 test sequences:
Sequence n
% Isym
% aperiodic component
1
2
3
4
5*

10
20
60
100
100

20
20
20
20
30

* for circuit breakers opening at least 80 ms

Schneider Electric

Merlin Gerin MV Design Guide

75

Standards

IEC - ANSI comparison

According to ANSI
c The circuit breaker must be able to break:
v the rated short circuit current at the rated maximum voltage
v K times the rated short-circuit current (maxi symmetrical interrupting
capability with K: voltage range factor) at the operating voltage (maximum
voltage/K)
v between the two currents obtained by the equation:
maxi symetrical current
rated maxi voltage
=
=K
rated short-circuit current
rated voltage
We therefore have a constant breaking power (in MVA) over a given
voltage range. Moreover, the asymmetrical current will be a function of the
following table taking S = 1.1 for Merlin Gerin circuit breakers.
ratio S

1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1

Asymmetrical interrupting capability = S x symetrical interrupting capability.


Both at specified operating voltage

Symetrical interrupting capability at


specified operating voltage = 1.0

0
0

0.5
1
0.006 0.017

2
0.033

3
0.050

4
0.067

cycles
seconds

c Rated short-circuit breaking capacity (kA)


Sequence n
Example:
c Isc = 40 kA
c % asymmetry = 50%
c Iasym = 1.1 40 = 44 kA
44
44
c Isym =
=
= 36 kA
1,22
1 + 2(50%)2
Sequence 6 will therefore be tested at
36 kA + 50% asymmetry,
this being 44 kA of total current.

1
2
3
4
5
6
7
8
9/10
11
12
13/14

current broken

% aperiodic component

10
50 - 100
30
< 20
60
50 - 100
100
< 20
KI to V/K
< 20
SI to V
50 - 100
KSI to V/K
50 - 100
electrical endurance
reclosing cycle at ASI and AKSI
C - 2 s - O at KI
rated Isc duration = KI for 3 s
single phase testing at KI and KSI (0.58 V)

Short-circuit breaking testing must comply with the


14 test sequences above, with:
I
R

:
:

symmetrical breaking capacity at maximum voltage


reclosing cycle coefficient
(Reclosing factor)

voltage range factor:

K=

asymmetrical factor:

Iasym
= 1.1
Isym

Vmax
Vmin

for Merlin Gerin circuit breakers

76

Merlin Gerin MV Design Guide

maximum rated voltage

Schneider Electric

IEC - ANSI comparison

Standards

Coordination of rated values


According to IEC
Rated
voltage
Ur (kV)
3.6

7.2

12

17.5

24

36

Rated short-circuit
breaking current

Rated operating current

Isc (kA)
10
16
25
40
8
12.5
16
25
40
8
12.5
16
25
40
50
8
12.5
16
25
40
8
12.5
16
25
40
8
12.5
16
25
40

Ir (A)
400
630

400
400

400
400

630
630
630

630
630
630

400

630
630
630

400

630
630
630

1250
1250
1250

1600
1600

2500
2500

3150

1250
1250
1250
1250

1600
1600
1600

2500
2500

3150

1600
1600
1600
1600

2500
2500
2500

3150
3150

1600

2500

3150

1600
1600

2500
2500

3150

1600
1600
1600

2500
2500

3150

1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250

630
630
630

1250
1250
1250
1250

According to ANSI
Maximum
rated
voltage
Umax (kV)
4.76

8.25

15

15.5

25.8
38

Schneider Electric

Rated
short-circuit
breaking current
at Umax

Minimum
rated
voltage

Rated
short-circuit
breaking current
at Umin

Rated
operating
current

Isc (kA)
18
29
41
7
17
33
9.3
9.8
18
19
28
37
8.9
18
35
56
5.4
11
22
36

(kV)
3.5
3.85
4
2.3
4.6
6.6
6.6
4
11.5
6.6
11.5
11.5
5.8
12
12
12
12
12
23
24

Isc (kA)
24
36
49
25
30
41
21
37
23
43
36
48
24
23
45
73
12
24
36
57

Ir (A)

Merlin Gerin MV Design Guide

600

1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200

2000
3000
2000
2000

2000
2000
2000
3000

600
1200
1200
2000

3000

4000

600
1200
1200
1200

3000

77

Standards

IEC- ANSI comparison

Derating
According to IEC
c Refer to "Switchgear definition/Derating" chapter.

According to ANSI
c The ANSI standard C37 04 gives for altitudes greater than 1 000 metres:
v a correction factor for the applicable voltage on the rated insulation level
and on the rated maximum voltage,
v a correction factor for the rated operating current.
The table of correction factors according to altitude
(Altitude Corrections Factors: ACF).
Altitude
(ft)
3 300
5 000
10 000

(m)

ACF for:
voltage

continous current

1 000
1 500
3 000

1.00
0.95
0.8

1.00
0.99
0.96

N.B.: "sealed system" type circuit breakers,


it is not necessairy to apply the voltage ACF on the maximum rated voltage

Electrical endurance
Merlin Gerin circuit breakers can withstand Isc at least 15 times.
IEC and ANSI standards impose values well below this because they take
account of oil breaking circuit breakers.
These values are not very high and should the customer request it,
we must provide those for the device being considered.

According to IEC
c The electrical endurance is equal to 3 times Isc.

According to ANSI
c The electrical endurance is equal to 4 times K.S.Isc.
Isc
S
K

:
:
:

symmetrical breaking capacity at maximum voltage


asymmetrical factor
voltage range factor

Mechanical endurance
According to IEC
c Mechanical endurance is of 2 000 switching cycles.

According to ANSI
c Mechanical endurance is of between 1 500 and 10 000 switching cycles
according to the voltage and the breaking capacity.

Construction
According to IEC
c The IEC does not impose any particular constraints, however,
the manufacturer has responsibility of determining what is required in
terms of materials (thicknesses, etc) to meet performance requirements in
terms of strength.

According to ANSI
c ANSI imposes a thickness of 3 mm for sheet metal.

78

Merlin Gerin MV Design Guide

Schneider Electric

Standards

IEC - ANSI comparison

Normal operating conditions


Equipment is designed
to operate under the
following normal
conditions

Temperature
Standards
IEC

ANSI

0C
ambient instantaneous

Installation
indoor
outdoor

minimal
maximal
maximum average
daily value
minimal
maximal

- 5C
+ 40C
35C

- 25C
+ 40C
35C

- 30C
+ 40C

N.B.:
For all equipment operating under conditions other than those described above, derating must
be provided (see derating chapter).

Altitude
According to IEC
c The altitude must not exceed 1 000 metres, otherwise the equipment
should be derated.

According to ANSI
c The altitude must not exceed 3 300 feet (1 000 metres), otherwise the
equipment should be derated.

Humidity
According to IEC
Average relative humidity
value over a period
24 hours
1 month

Indoor equipment
95 %
90 %

According to ANSI
c No specific constraints.

Schneider Electric

Merlin Gerin MV Design Guide

79

You might also like