Model:

60RZG

190--600 V

Gas

Standard Features

Ratings Range
Standby:
Prime:

60 Hz
54--64
54--80
50--59
50--74

kW
kVA
kW
kVA

50 Hz
45--53
45--66
39--50
40--62

Generator Set Ratings


Alternator

4P10

4S7

4V7

Voltage
120/208
127/220
120/240
120/240
139/240
220/380
277/480
347/600
110/190
115/200
120/208
110/220
110/220
220/380
230/400
240/416
120/208
127/220
120/240
120/240
139/240
220/380
277/480
347/600
110/190
115/200
120/208
110/220
110/220
220/380
230/400
240/416
120/240
110/220

Ph
3
3
3
1
3
3
3
3
3
3
3
1
3
3
3
3
3
3
3
1
3
3
3
3
3
3
3
3
1
3
3
3
1
1

Hz
60
60
60
60
60
60
60
60
50
50
50
50
50
50
50
50
60
60
60
60
60
60
60
60
50
50
50
50
50
50
50
50
60
50

D Kohler Co. provides one-source responsibility for the generating


system and accessories.
D The generator set and its components are prototype-tested,
factory-built, and production-tested.
D The 60 Hz generator set offers a UL 2200 listing.
D The generator set accepts rated load in one step.
D The 60 Hz generator set meets NFPA 110, Level 1, when
equipped with the necessary accessories and installed per NFPA
standards.
D A one-year limited warranty covers all systems and components.
Two-, five-, and ten-year extended warranties are also available.
D Alternator features:
d The unique Fast-Responset II excitation system delivers
excellent voltage response and short circuit capability using a
permanent magnet (PM)-excited alternator.
d The brushless, rotating-field alternator has broadrange
reconnectability.
D Other features:
d Controllers are available for all applications. See controller
features inside.
d The electronic, isochronous governor incorporates an
integrated drive-by-wire throttle body actuator delivering
precise frequency regulation.

Natural Gas
130_C Rise
105_C Rise
Standby Rating
Prime Rating
kW/kVA
Amps
kW/kVA
Amps
60/75
208
55/69
191
60/75
197
55/69
180
60/75
180
55/69
165
54/54
225
50/50
208
60/75
180
53/66
159
60/75
114
55/69
104
60/75
90
53/66
80
60/75
72
53/66
64
49/61
185
45/56
170
47/59
170
42/52
150
45/56
155
39/49
136
45/45
205
40/40
182
49/61
160
45/56
147
49/61
93
45/56
85
47/59
85
42/52
75
45/56
78
39/49
68
60/75
208
55/69
191
60/75
197
55/69
180
60/75
180
55/69
165
54/54
225
50/50
208
60/75
180
55/69
165
60/75
114
55/69
104
60/75
90
55/69
83
60/75
72
55/69
66
48/60
182
45/56
170
49/61
176
45/56
162
49/61
169
45/56
155
48/60
157
45/56
147
45/45
205
41/41
186
48/60
91
45/56
85
48/60
87
45/56
81
49/61
85
45/56
78
57/57
238
51/51
213
47/47
214
42/42
191

LP Gas
130_C Rise
105_C Rise
Standby Rating
Prime Rating
kW/kVA
Amps
kW/kVA
Amps
62/78
215
57/71
198
61/76
200
55/69
180
63/79
189
59/74
177
54/54
225
50/50
208
60/75
180
53/66
159
60/75
114
56/70
106
60/75
90
53/66
80
60/75
72
53/66
64
50/63
191
46/57
173
47/59
170
42/52
150
45/56
155
39/49
136
45/45
205
40/40
182
51/64
168
46/57
150
50/63
96
46/57
87
47/59
85
42/52
75
45/56
78
39/49
68
63/79
219
59/74
205
63/79
207
59/74
194
63/79
189
59/74
177
57/57
238
53/53
221
64/80
192
59/74
177
63/79
120
59/74
112
64/80
96
59/74
89
64/80
77
59/74
71
53/66
201
49/61
184
53/66
191
50/62
179
53/66
183
50/62
172
53/66
173
49/61
160
47/47
214
44/44
200
53/66
100
49/61
92
53/66
95
50/62
89
53/66
92
50/62
86
61/61
254
55/55
229
51/51
232
46/46
209

RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source.
The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and
DIN 6271. Prime Power Ratings: Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A
10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running
time and base load ratings, consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the
right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 1.3% per 100 m (328 ft.) elevation
above 200 m (656 ft.). Temperature: Derate 3.0% per 10_C (18_F) temperature above 25_C (77_F). For units having a weather housing with roof-mounted silencer or an enclosure with enclosed silencer,
add 5_C (9_F) for 60 Hz and 10_C (18_F) for 50 Hz to the ambient temperature. Dual fuel engines are optimized to run on the primary fuel (natural gas) and, as a result, the LPG ratings may not be attained.
For dual fuel engines, use the natural gas ratings for both the primary and secondary fuels.
G4-77 (60RZG) 9/08s

Alternator Specifications
Specifications
Manufacturer
Type
Exciter type
Leads: quantity, type
4P10, 4S7
4V7
Voltage regulator
Insulation:
Material
Temperature rise
Bearing: quantity, type
Coupling
Amortisseur windings
Voltage regulation, no-load to full-load
Permanent magnet (PM) alternator
550 controller (with 0.5% drift
due to temperature variation)
Unbalanced load capability
One-step load acceptance
Peak motor starting kVA:
480 V, 380 V 4P10 (12 lead)
480 V, 380 V 4S7 (12 lead)
240 V, 220 V 4V7 (4 lead)

D NEMA MG1, IEEE, and ANSI standards compliance for


temperature rise and motor starting.

Alternator
Kohler
4-Pole, Rotating-Field
Brushless, PermanentMagnet

D Sustained short-circuit current of up to 300% of the rated


current for up to 10 seconds.
D Sustained short-circuit current enabling downstream circuit
breakers to trip without collapsing the alternator field.

12, Reconnectable
4, 110--120/220--240
Solid State, Volts/Hz
NEMA MG1
Class H
130_C, Standby
1, Sealed
Flexible Disc
Full

D Self-ventilated and dripproof construction.


D Vacuum-impregnated windings with fungus-resistant epoxy
varnish for dependability and long life.
D Superior voltage waveform from a two-thirds pitch stator and
skewed rotor.
D Fast-Responset II brushless alternator with brushless
exciter for excellent load response.

2% Average
3-Phase Sensing, 0.25%
100% of Rated Standby
Current
100% of Rating
(35% dip for voltages below)
255 (60Hz), 180 (50Hz)
270 (60Hz), 190 (50Hz)
215 (60Hz), 175 (50Hz)

Application Data
Engine
Engine Specifications
Manufacturer
Engine: model, type

Cylinder arrangement
Displacement, L (cu. in.)
Bore and stroke, mm (in.)
Compression ratio
Piston speed, m/min. (ft./min.)
Main bearings: quantity, type
Rated rpm
Max. power at rated rpm, kW (HP)
Cylinder head material
Piston type and material
Crankshaft material
Valve (exhaust) material
Governor type
Frequency regulation, no-load to full-load
Frequency regulation, steady state
Frequency
Air cleaner type, all models

Engine Electrical
60 Hz
50 Hz
General Motors
Industrial Powertrain
Vortec 5.7 L, 4-Cycle
Natural Aspiration
V-8
5.7 (350)
101.6 x 88.4 (4.00 x 3.48)
9.1:1
318 (1044)
265 (870)
5, M400 Copper Lead
1800
1500
78.3 (105)
65.6 (88)
Cast Iron
High Silicon Aluminum
Nodular Iron
Forged Steel
Electronic
Isochronous
0.5%
Field-Convertible
Dry

Exhaust
Exhaust System
Exhaust manifold type
Exhaust flow at rated kW, m3/min. (cfm)
Exhaust temperature at rated kW, dry
exhaust, _C (_F)
Maximum allowable back pressure,
kPa (in. Hg)
Exhaust outlet size at engine hookup,
mm (in.)

60 Hz

50 Hz
Dry

16.4 (580)

13.6 (480)

649 (1200)
10.2 (3.0)
76 (3.0) OD

Engine Electrical System


Ignition system
Battery charging alternator:
Ground (negative/positive)
Volts (DC)
Ampere rating
Starter motor rated voltage (DC)
Battery, recommended cold cranking
amps (CCA):
Qty., rating for --18_C (0F)
Battery voltage (DC)

60 Hz
50 Hz
Electronic, Distributor
Negative
12
70
12

One, 630
12

Fuel
Fuel System
Fuel type
Fuel supply line inlet
Natural gas/LPG fuel supply pressure,
measured at the generator set fuel inlet
downstream of any fuel system
equipment accessories, kPa (in. H2O)
Fuel Composition Limits *
Methane, % by volume
Ethane, % by volume
Propane, % by volume
Propene, % by volume
C4 and higher, % by volume
Sulfur, ppm mass
Lower heating value,
kJ/m3 (Btu/ft3), min.

60 Hz
50 Hz
LP Gas or
Natural Gas
1 NPTF

1.74--2.74 (7.0--11.0)
Nat. Gas
LP Gas
90 min.

4.0 max.

1.0 max.
85 min.
0.1 max.
5.0 max.
0.3 max.
2.5 max.
25 max.
26.6 (890)

67.5 (2260)

* Fuels with other compositions may be acceptable. If your fuel is


outside the listed specifications, contact your local distributor for
further analysis and advice.

G4-77 (60RZG) 9/08s

Application Data
Lubrication
Lubricating System
Type
Oil pan capacity, L (qt.)
Oil pan capacity with filter, L (qt.)
Oil filter: quantity, type

60 Hz
50 Hz
Full Pressure
4.7 (5.0)
6.2 (6.5)
1, Cartridge

Cooling
Radiator System
Ambient temperature, _C (_F) *
Engine jacket water capacity, L (gal.)
Radiator system capacity, including
engine, L (gal.)
Engine jacket water flow, Lpm (gpm)
Heat rejected to cooling water at rated
kW, dry exhaust, kW (Btu/min.)
Water pump type
Fan diameter, including blades, mm (in.)
Fan, kWm (HP)
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H2O)

60 Hz

50 Hz
50 (122)
6.8 (1.8)

LP Gas, m3/hr. (cfh) at % load


100%
75%
50%
25%
LP Gas, m3/hr. (cfh) at % load
100%
75%
50%
25%

Standby Rating
9.3 (330)
7.9 (280)
7.1 (250)
6.2 (220)
5.4 (190)
4.7 (165)
3.8 (135)
3.1 (110)
Prime Rating
8.4 (298)
7.2 (256)
6.6 (232)
5.8 (204)
5.1 (179)
4.4 (154)
3.7 (130)
3.0 (105)

w Fuel consumption is based on 1015 Btu/standard cu. ft. natural gas.

20.8 (5.5)
117.3 (31)
98.4 (26)
54.8 (3120) 45.7 (2600)
Centrifugal
533 (21)
4.5 (6.0)
2.6 (3.5)

LP vapor conversion factors:


8.58 ft.3 = 1 lb.
0.535 m3 = 1 kg.
36.39 ft.3 = 1 gal.

Controllers

0.125 (0.5)

* Weather housing with roof-mounted silencer and enclosure with


enclosed silencer reduce ambient temperature capability by 5_C
(9_F) for 60 Hz and 10_C (18_F) for 50 Hz.
Remote Radiator System[
Exhaust manifold type
Connection sizes:
Water inlet, ID hose, mm (in.)
Water outlet, ID hose, mm (in.)
Static head allowable
above engine, kPa (ft. H2O)

60 Hz

50 Hz
Dry

44.45 (1.75)
38.10 (1.50)
4.32 (17.0)

Decision-Makert 550 Controller


Audiovisual annunciation with NFPA 110 Level 1 capability.
Programmable microprocessor logic and digital display features.
Alternator safeguard circuit protection.
12- or 24-volt engine electrical system capability.
Remote start, remote annunciation, and remote communication options.
Refer to G6-46 for additional controller features and accessories.

[ Contact your local distributor for cooling system options and


specifications based on your specific requirements.

Operation Requirements
Air Requirements
60 Hz
Radiator-cooled cooling air,
m3/min. (scfm)]
170 (6000)
Cooling air required for generator set
when equipped with city water cooling or
remote radiator, based on 14_C (25_F)
rise and ambient temperature of 29_C
(85_F), m3/min. (cfm)
144 (5100)
Combustion air, m3/min. (cfm)
5.2 (185)
Heat rejected to ambient air:
Engine, kW (Btu/min.)
30.9 (1760)
Alternator, kW (Btu/min.)
7.7 (440)
] Air density = 1.20 kg/m3 (0.075 lbm/ft3)
Fuel Consumptionw
Natural Gas,
100%
75%
50%
25%

m3/hr.

(cfh) at % load

Natural Gas, m3/hr. (cfh) at % load


100%
75%
50%
25%

60 Hz

50 Hz
136 (4800)

125 (4400)
4.4 (155)
26.5 (1510)
6.9 (390)

50 Hz

Standby Rating
22.4 (790)
18.1 (640)
19.4 (685)
15.6 (550)
14.7 (520)
11.8 (415)
9.9 (350)
7.8 (275)
21.2
18.0
13.8
9.5

Decision-Makert 3+, 16-Light Controller


Audiovisual annunciation with NFPA 110 Level 1 capability.
Microprocessor logic, AC meters, and engine gauge features.
12- or 24-volt engine electrical system capability.
Remote start, prime power, and remote annunciation options.
Refer to G6-30 for additional controller features and accessories.

Prime Rating
(748)
17.1
(636)
14.4
(486)
11.0
(335)
7.4

(604)
(510)
(387)
(263)

Decision-Makert 1 Controller
Single-light annunciation and basic controls with NFPA capability.
Relay logic, AC meters, and engine gauge features.
12-volt engine electrical system capability only.
Remote or automatic start options.
Refer to G6-29 for additional controller features and accessories.
Note: Not available with 600-volt alternator.

G4-77 (60RZG) 9/08s

Kohler Power Systems


Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455

KOHLER CO., Kohler, Wisconsin 53044 USA


Phone 920-565-3381, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com

Additional Standard Features


D
D
D
D

Alternator Protection (standard with 550 controller)


Battery Rack and Cables
Electronic, Isochronous Governor
Gas Fuel System (includes fuel mixer, secondary gas regulator,
gas solenoid valve, and flexible fuel line between the engine
and the skid-mounted fuel system components)
D Integral Vibration Isolation
D Oil Drain Extension
D Operation and Installation Literature

Available Options
Approvals and Listings
- CSA Approval
- IBC Seismic Certification
- UL 2200 Listing
Enclosed Unit
- Sound Enclosure (with enclosed critical silencer)
- Weather Enclosure (with enclosed critical silencer)
- Weather Housing (with roof-mounted silencer)
Open Unit
- Exhaust Silencer, Critical (kits: PA-324468, PA-352663)
- Flexible Exhaust Connector, Stainless Steel
Fuel System
- Flexible Fuel Line
(required when the generator set skid is spring mounted)
- Gas Filter
- Secondary Gas Solenoid Valve
-

Controller (550 and 16-Light)


Common Failure Relay
Communication Products and PC Software (550 controller only)
Customer Connection
Dry Contact (isolated alarm)
Engine Prealarm Sender
Local Emergency Stop
Prime Power Switch (550 controller only)
Remote Annunciator Panel
Remote Audiovisual Alarm Panel
Remote Emergency Stop
Remote Mounting Cable
Run Relay

Miscellaneous
Air Cleaner Restrictor Indicator
Engine Fluids (oil and coolant) Added
Rated Power Factor Testing
Rodent Guards

Literature
General Maintenance
NFPA 110
Overhaul
Production

Warranty
2-Year Basic
2-Year Prime
5-Year Basic
5-Year Comprehensive

Other Options
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________
_______________________________________________

Dimensions and Weights


Overall Size, L x W x H, mm (in.) :
4P10/4V7: Wide Skid
2200 x 1040 x 1172 (86.6 x 40.9 x 46.1)
Narrow Skid
2200 x 865 x 1172 (86.6 x 34.0 x 46.1)
4S7:
Wide Skid
2200 x 1040 x 1211 (86.6 x 40.9 x 47.7)
Narrow Skid
2200 x 865 x 1211 (86.6 x 34.0 x 47.7)
Weight (radiator model), wet, kg (lb.):
4P10/4V7: 755 (1665)
4S7:
813 (1793)

Cooling System
- Block Heater
[recommended for ambient temperatures below 10C (50F)]
- City Water Cooling
- Radiator Duct Flange
- Remote Radiator Cooling
-

Electrical System
Alternator Strip Heater
Battery
Battery Charger, Equalize/Float Type
Battery Heater
Line Circuit Breaker (NEMA1 enclosure)
Line Circuit Breaker with Shunt Trip (NEMA1 enclosure)
Safeguard Breaker (available with 16-light controller)

NOTE: This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.

DISTRIBUTED BY:

2000, 2001, 2002, 2003, 2004, 2005, 2006, 2008 by Kohler Co. All rights reserved.
G4-77 (60RZG) 9/08s