You are on page 1of 14

CIRCUIT BREAKERS

Miniature circuit breakers C45, C60

TERMINAL

NON-FLAMMABLE COVER

JUMP KNUCKLE

HANDLE

LOCK KNACKLE

MOVABLE CONTACT

ARC CHAMBER

STATIC CONTACT

MAXIMUM CURRENT RELEASE

AUXILIARY CONTACT (accessory)

10

UNDER VOLTAGE RELEASE (accessory)

11

SHUNT RELEASE (accessory)

12

7
9

6
Characteristics

10

16

11

12

Circuit breakers are automatically-operated electrical switches, designed to protect electrical circuits from damage caused by overload or short circuit. They can also be used
as devices for commutation and control of electrical circuits. They differ in the following
characteristics:
* Operating voltage: 230, 400V
* Number of poles: 1, 2, 3, 4
* Breaking curve:
- curve B breaks between 3 and 5 In, used for low voltage short circuit currents (long
circuits and generators)
- curve C breaks between 5 and 10 In, used for protection of main power supply cables
and conventional consumers
- curve D breaks between 10 and 20 In, used for protection of industrial consumers with
KLJKLQLWLDOFXUUHQWRZ HOHFWULFPRWRUV
* Breaking capacity: 4.5, 6, 10kA

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C40N
[1
&[

constructive series
number of poles (1;2;3;4)
rated current
EUHDNLQJFXUYH

Documents corresponding
to the product:
Standard EN60898-1
EN 60947-2

Functions:
- protection of the electrical circuits from overload or short circuits of the outer circuit
- it can be used as a device for commutation and control of electrical circuits
- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit
- for mounting in housing and industrial buildings
- for mounting at a distance from the transformer post from 150 to 850 m
- allows protection of consumers generating short circuit currents up to 4500 A
Technical data:
* Rated voltage: 230/400V; 50/60Hz
* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 4500A
* Rated breaking capacity Ics= 75% Icu
,VRODWLQJYROWDJH9
* Electrical wear resistance (number of cycles): 4000
* Mechanical (number of cycles): 20000
* Class of current limiting:3
* IP code: IP>20
* Breaking curve:
B curve the overload and short-circuit protection is activated at 3-5 ln. Used for protection of big length cables and
power generators.
C the maximum current release breaks between 5 and 10 In; used to protect main power supply cables and conventional consumers
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDOZLWKFRPSRVLWLRQFROGO\GUDZSODWHGSODQH4$
* Plastic box not keeping the burning material nylon PA66, UV rays wear resistance
* Box permitivity strength: >18MV/m
$EQRUPDOKHDWLQJZHDUUHVLVWDQFHDQGUHRIWKHRXWHUSDUWV&V
* Maximum current release containing:
- copper coil - composition: pure copper T2 type
- resistance: from 0.6 to 180m
- welding effort: <150 000 N/mm
- bimetal plate composition: 5J158 to TB180 depending on the current
- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)
- magnetic core composition: coldly draw-plated metal wire (1Gr18Ni9)
WKLFNQHVVWRP
- drawing effort: from 200 to 400N/mm
- contact head of the movable contact composition: silver graphite CAg(5)
- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)
- static contact composition: pure copper T2Y2
- composition of the contact head: silver graphite CAg(5)
* Power supply (conducting)
- power supply busbar 1P63, 3P63
- rigid conductors up to 25 mm
H[LEOHFRQGXFWRUVXSWRPP
* Tightening moment:1.33Nm
Mounting:
* vertical
* DIN-rail
* for mounting in housing or industrial environment without serious interference
DPELHQWWHPSHUDWXUH&WR&&

Type

C41N / 2A
C41N / 4A
C41N / 6A
C41N / 10A
C41N / 16A
C41N / 20A
C41N / 25A
C41N / 32A
C41N / 40A
C41N / 50A
C41N / 63A

Rated current Breaking capacity


In (A)
(kA)

2
4
6
10
16
20
25
32
40
50
63

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve B

1.0
1.0
1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240













41460B
41461B
41451B
41452B
41453B
41454B
41455B
41456B
41457B
41458B
41459B

17

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C40N

Type

C42N / 6A
C42N / 10A
C42N / 16A
C42N / 20A
C42N / 25A
C42N / 32A
C42N / 40A
C42N / 50A
C42N / 63A

Type

C43N / 6A
C43N / 10A
C43N / 16A
C43N / 20A
C43N / 25A
C43N / 32A
C43N / 40A
C43N / 50A
C43N / 63A

Rated current Breaking capacity


In (A)
(kA)

6
10
16
20
25
32
40
50
63

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Rated current Breaking capacity


In (A)
(kA)

6
10
16
20
25
32
40
50
63

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

C40N, curve B

18

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve B

1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120











41470B
41471B
41472B
41473B
41474B
41475B
41476B
41477B
41478B

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve B

1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80











41541B
41542B
41543B
41544B
41545B
41546B
41547B
41548B
41549B

C40N, curve C

CIRCUIT BREAKERS
0LQLDWXUHFLUFXLWEUHDNHUV 0&% 1

[1
&[

constructive series
number of poles (1;2;3;4)
rated current
EUHDNLQJFXUYH

Documents corresponding to
the product:
Standard EN60898-1

72

45

35

81

50

Functions:
- protection of the electrical circuits from overload or short circuits of the outer circuit
- it can be used as a device for commutation and control of electrical circuits
- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit
- for mounting in industrial buildings with high contamination level of the electric system
- for mounting at a distance from the transformer post from 150 to 850 m
- allows protection of consumers generating short circuit currents up to 6000 A
Technical data:
* Rated voltage: 230/400V; 50/60Hz
* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 6000A
* Rated breaking capacity Ics= 75% Icu
,VRODWLQJYROWDJH9
* Electrical wear resistance (number of cycles): 8000
* Mechanical (number of cycles): 50000
* Class of current limiting:3
* IP code: IP>20
* Breaking curve:
B the maximum current release breaks between 3 and 5 In; used to protect long circuits and generators
C the maximum current release breaks between 5 and 10 In; used to protect main power supply cables and
conventional consumers
* Joining terminal: Combined screw clamp made of 1.5 cold extruded Q235-A material with additional coating
* Plastic box not keeping the burning material nylon PA66, UV rays wear resistance
Status indicator
* Box permitivity strength: >18MV/m
$EQRUPDOKHDWLQJZHDUUHVLVWDQFHDQGUHRIWKHRXWHUSDUWV&V
+HDWUHVLVWDQFHRILQWHUQDOQRQHOHFWULFDOFRPSRQHQWVV
* Maximum current release containing:
- copper coil - composition: pure copper T2 type
- resistance: from 0.6 to 180m
- welding effort: <150 000 N/mm
- bimetal plate composition: 5J158 to TB180 depending on the current
- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)
- magnetic core composition: coldly draw-plated metal wire (1Gr18Ni9)
WKLFNQHVVWRP
- drawing effort: from 200 to 400N/mm
- contact head of the movable contact composition: silver graphite CAg(5)
- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)
- static contact composition: pure copper T2Y2
- composition of the contact head: silver graphite CAg(5)
* Power supply (conducting)
- power supply busbar 1P63, 3P63
- rigid conductors up to 25 mm
H[LEOHFRQGXFWRUVXSWRPP
* Tightening moment:1.33Nm
Mounting:
* vertical
* DIN-rail
* for mounting in housing or industrial environment without serious interference
DPELHQWWHPSHUDWXUH&WR&&

Type

C61N / 1A
C61N / 2A
C61N / 4A
C61N / 6A
C61N / 10A
C61N / 16A
C61N / 20A
C61N / 25A
C61N / 32A
C61N / 40A
C61N / 50A
C61N / 63A

Rated current Breaking


In (A)
capacity (kA)

1
2
4
6
10
16
20
25
32
40
50
63

6
6
6
6
6
6
6
6
6
6
6
6

Recommended
sections of the
Packing/Box (pcs)
condmuocutonrtsin (g/mm2)

1.0
1.0
1.0
1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240
12 / 240

Catalogue number
Curve C

Catalogue number
Curve B

41100N
41102N
41104N
41106N
41110N
41116N
41120N
41125N
41132N
41140N
41150N
41163N

41501N
41502N
41504N
41506N
41510N
41516N
41520N
41525N
41532N
41540N
41550N
41563N

19

CIRCUIT BREAKERS
0LQLDWXUHFLUFXLWEUHDNHUV 0&% 1

Type

&1
C62N / 4A
C62N / 6A
C62N / 10A
C62N / 16A
C62N / 20A
C62N / 25A
C62N / 32A
C62N / 40A
C62N / 50A
C62N / 63A

Type

C63N/2A
C63N/4A
C63N / 6A
C63N / 10A
C63N / 16A
C63N / 20A
C63N / 25A
C63N / 32A
C63N / 40A
C63N / 50A
C63N / 63A

Type

C64N / 2A
C64N / 4A
C64N / 6A
C64N / 10A
C64N / 16A
C64N / 20A
C64N / 25A
C64N / 32A
C64N / 40A
C64N / 50A
C64N / 63A

Rated current Breaking


In (A)
capacity (kA)

2
4
6
10
16
20
25
32
40
50
63

Rated current Breaking


In (A)
capacity (kA)

2
4
6
10
16
20
25
32
40
50
63

6
6
6
6
6
6
6
6
6
6
6

Rated current Breaking


In (A)
capacity (kA)

2
4
6
10
16
20
25
32
40
50
63
C60N, curve B

20

6
6
6
6
6
6
6
6
6
6
6

6
6
6
6
6
6
6
6
6
6
6

Recommended
Packing/Box (pcs)
sections of the
condmuocutonrtsin (g/mm2)

1.0
1.0
1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120
6 / 120

Recommended
Packing/Box (pcs)
sections of the
condmuocutonrtsin (g/mm2)

1.0
1.0
1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80
4 / 80

Recommended
Packing/Box (pcs)
sections of the
condmuocutonrtsin (g/mm2)

1.0
1.0
1.0
1.5
2.5
2.5
4.0
6.0
10.0
10.0
16.0

3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60
3 / 60

Catalogue number
Curve C

Catalogue number
Curve B

41202N
41204N
41206N
41210N
41216N
41220N
41225N
41232N
41240N
41250N
41263N

41602N
41604N
41606N
41610N
41616N
41620N
41625N
41632N
41640N
41650N
41663N

Catalogue number
Curve C

Catalogue number
Curve B

41302N
41304N
41306N
41310N
41316N
41320N
41325N
41332N
41340N
41350N
41363N

41702N
41704N
41706N
41710N
41716N
41720N
41725N
41732N
41740N
41750N
41763N

Catalogue number
Curve C

Catalogue number
Curve B

41402N
41404N
41406N
41410N
41416N
41420N
41425N
41432N
41440N
41450N
41463N

41802N
41804N
41806N
41810N
41816N
41820N
41825N
41832N
41840N
41850N
41863N

C60N, curve C

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C100L

/ constructive series


number of poles (1;3)

&[

rated current
EUHDNLQJFXUYH

Documents corresponding to
the product:
Standard EN60898-1
EN 60947-2

Functions:
- protection of the electrical circuits from overload or short circuits of the outer circuit
- it can be used as a device for commutation and control of electrical circuits
- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit
Technical data:
* Rated voltage: 230/400V; 50/60Hz
* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 10000A
* Rated breaking capacity Ics= 75% Icu
,VRODWLQJYRODWDJH9PLQDWLPSXOVHZDYHV
(OHFWULFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
0HFKDQLFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
* Class of current limiting:3
* IP code: IP>20
* Breaking curve: C
Mounting:
* vertical
* DIN-rail
* possibility for labeling

Type

Rated current Breaking capacity


In (A)
(kA)

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

C101L/6A

10

1.0

12 / 240

41101

C101L/10A

10

10

1.5

12 / 240

41103

C101L/16A

16

10

2.5

12 / 240

41105

C101L/20A

20

10

2.5

12 / 240

41107

C101L/25A

25

10

4.0

12 / 240

41108

C101L/32A

32

10

6.0

12 / 240

41109

C101L/40A

40

10

10.0

12 / 240

41111

C101L/50A

50

10

10.0

12 / 240

41112

C101L/63A

63

10

16.0

12 / 240

41113

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

Type

Rated current Breaking capacity


In (A)
(kA)

C102L/6A

10

1.0

6/120

41201

C102L/10A

10

10

1.5

6/120

41203

C102L/16A

16

10

2.5

6/120

41205

C102L/20A

20

10

2.5

6/120

41207

C102L/25A

25

10

4.0

6/120

41208

C102L/32A

32

10

6.0

6/120

41209

C102L/40A

40

10

10.0

6/120

41211

C102L/50A

50

10

10.0

6/120

41212

C102L/63A

63

10

16.0

6/120

41213

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

Type

Rated current Breaking capacity


In (A)
(kA)

C103L/6A

10

1.0

4 / 80

41301

C103L/10A

10

10

1.5

4 / 80

41303

C103L/16A

16

10

2.5

4 / 80

41305

C103L/20A

20

10

2.5

4 / 80

41307

C103L/25A

25

10

4.0

4 / 80

41308

C103L/32A

32

10

6.0

4 / 80

41309

C103L/40A

40

10

10.0

4 / 80

41311

C103L/50A

50

10

10.0

4 / 80

41312

C103L/63A

63

10

16.0

4 / 80

41313

21

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C100M

0 constructive series


number of poles (1;2;3;4)

'[

rated current
EUHDNLQJFXUYH'

Documents corresponding to
the product:
Standard EN60898-1
EN 60947-2

22

Functions:
- protection of the electrical circuits from overload or short circuits of the outer circuit
- it can be used as a device for commutation and control of electrical circuits
- in combination with auxiliary devices it allows remote control, commutation or indication of the protected circuit
Technical data:
* Rated voltage: 230/400V; 50/60Hz
* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 10000A
* Rated breaking capacity Ics= 75% Icu
,VRODWLQJYRODWDJH9
(OHFWULFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
0HFKDQLFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
* Class of current limiting:3
* IP code: IP>20
* Breaking curve: C,D
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDOZLWKFRPSRVLWLRQFROGO\GUDZSODWHGSODQH4$
* Plastic box not keeping the burning material nylon PA66, UV rays wear resistance
* Box permitivity strength: >18MV/m
$EQRUPDOKHDWLQJZHDUUHVLVWDQFHDQGUHRIWKHRXWHUSDUWV&V
* Maximum current release containing:
- copper coil - composition: pure copper T2 type
- resistance: from 148 to 230m
- welding effort: <400 N/
- bimetal plate composition: TB180/0.5
- thickness: 0.8mm
- magnetic core composition: coldly draw-plated metal wire (1Gr18Ni9)
WKLFNQHVVWRP
- drawing effort: 20N/mm2
- contact head of the movable contact composition: silver graphite CAg(5)
- dimension 6x6x1
- static contact composition: pure copper T2Y2
- composition of the contact head: silver graphite CAg(5)
* Power supply (conducting)
- power supply busbar
- rigid conductors up to 50
H[LEOHFRQGXFWRUVXSWR
* Tightening moment:1.33Nm
Mounting:
* vertical
* DIN-rail
* possibility for labeling
* for mounting in industrial environment
DPELHQWWHPSHUDWXUH&WR&&

Type

Number of
poles

Rated current Breaking capacity


In (A)
(kA)

C100M

1P

80

C100M

1P

100

C100M

1P

125

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve D

10

9 / 180

41180

41180D

10

9 / 180

41190

41190D

10

9 / 180

41195

41195D

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C100M

Type

Number of
poles

Rated current Breaking capacity


In (A)
(kA)

C100M

2P

80

C100M

2P

100

Type

Number of
poles

C100M

3P

80

C100M

3P

100

Type

Number of
poles

C100M

4P

80

C100M

4P

100

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve D

10

6 / 120

41280

41281

10

6 / 120

41290

41291

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve D

10

4 / 60

41380

41381

10

4 / 60

41390

41391

Packing/Box (pcs)

Catalogue number
Curve C

Catalogue number
Curve D

10

3 / 60

41480

41481

10

3 / 60

41490

41491

Rated current Breaking capacity


In (A)
(kA)

Rated current Breaking capacity


In (A)
(kA)

(C curve)

(D curve)

t(s)

t(s)

1000

1000

5000

5000

2000

2000

Thermal release

1000

1000

500

500

200

200

100

100

50

50

20

20

10

Thermal release

10

Electromagnetic
release

2
1

5
2
0.5

0.2

0.2

0.1

0.1

0.05

0.05

0.02

Electromagnetic
release

0.5

0.02

0.01

0.01

0.005

0.005

0.002

0.002

0.001

0.001
0.5

3 4 5

7 10

20 30

50 70

100

200

i/in

0.5

3 4 5

7 10

20 30

50 70

100

200

i/in

23

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C60DC series

['& constructive series


number of poles (1;2)

&[

rated current
EUHDNLQJFXUYH

Documents corresponding to
the product:
Standard EN60898-1
EN 60898-2

24

Functions:
- for lowering constant current voltaic arc and use of the breaker at constant current consumer protection
- protection of the electrical circuits from overload or short circuit of the outer circuit at alternating current and
constant
current power supply circuits
- for commutation and control of electrical circuits
- in combination with auxiliary alternating current devices for remote control, commutation or indication of the
protected circuit
- for mounting in industrial buildings
- for protection of consumers generating short circuit currents to 6000 A at alternating current power supply
Technical data:
* Rated voltage: 240V; AC/DC
* Breaking capacity (cycle O -CO) in accordance with standard EN 60 898- 1: 6000A
* Rated breaking capacity Ics=75% Icu
,QVXODWLQJYROWDJH9
(OHFWULFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
0HFKDQLFDOZHDUUHVLVWDQFH QXPEHURIF\FOHV 
* Class of current limiting: 3
* IP code: IP>20
* Breaking curve: C the maximum current release breaks between 5 and 10 In; used to protect power supply
cables and conventional consumers
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDOZLWKFRPSRVLWLRQFROGO\GUDZSODWHGSODQH4$
* Plastic box not keeping the burning material nylon PA66, UV rays wear resistance
* Box permitivity strength: >18MV/m
$EQRUPDOKHDWLQJZHDUUHVLVWDQFHDQGUHRIWKHRXWHUSDUWV&V
* Maximum current release containing:
- copper coil - composition: pure copper T2 type
- resistance: from 0.6 to 180m
- welding effort: <150 000 N/mm
- bimetal plate composition: 5J158 to TB180 according to the current
- thickness: 0.6mm (up to 40A) and 0.8mm (up to 63A)
- magnetic core composition: coldly draw-plated metal wire (1Gr18Ni9)
WKLFNQHVVWRP
- drawing effort: from 200 to 400N/mm
- contact head of the movable contact composition: silver graphite CAg(5)
- dimension 3x3x0.8 (up to 40A) and 4x4x0.8 (up to 63A)
- static contact composition: pure copper T2Y2
- composition of the contact head: silver graphite CAg(5)
- metal magnetic plate for lowering the constant current arc
* Conducting:
- power supply busbar 1P63
- rigid conductors up to 25 mm
H[LEOHFRQGXFWRUVXSWRPP
* Tightening moment: 1.33Nm
Mounting
* vertical
* DIN-rail
* for mounting in housing or industrial environment without serious current interference
$PELHQWWHPSHUDWXUH&WR&&

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) C60DC series

Type

72

Rated current Breaking capacity


In (A)
(kA)

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

61DC / 1A

1.0

12 / 240

41164

61DC / 2A

1.0

12 / 240

41165

61DC / 4A

1.0

12 / 240

41166

61DC / 6A

1.0

12 / 240

41167

61DC / 10A

10

1.5

12 / 240

41168

61DC / 16A

16

2.5

12 / 240

41169

61DC / 20A

20

2.5

12 / 240

41170

61DC / 25A

25

4.0

12 / 240

41171

61DC / 32A

32

6.0

12 / 240

41172

61DC / 40A

40

10.0

12 / 240

41173

61DC / 50A

50

10.0

12 / 240

41174

61DC / 63A

63

16.0

12 / 240

41175

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

65
49

36

45

78

18

Type

Rated current Breaking capacity


In (A)
(kA)

62DC / 2A

1.0

6 / 120

41176

62DC / 4A

1.0

6 / 120

41177

62DC / 6A

1.0

6 / 120

41178

62DC / 10A

10

1.5

6 / 120

41179

62DC / 16A

16

2.5

6 / 120

41181

62DC / 20A

20

2.5

6 / 120

41182

62DC / 25A

25

4.0

6 / 120

41183

25

CIRCUIT BREAKERS
Miniature circuit breakers (MCB) DP1N (1P + N)

Functions:
- protection of the electrical circuits from overload or short circuit of the outer circuit
- it can be used as a device for commutation and control of electrical circuits
- it breaks simultaneously the lead and the neutral conductor as the heat protection is only at the lead conductor
Technical data:
* Rated voltage: 230V; 50/60Hz
* Breaking capacity (cycle O-CO) in accordance with standard EN 60 898-1: 4500 A
* Rated breaking capacity Ics = 50% Icu
,QVXODWLQJYROWDJH9
* IP code: IP>20
* Breaking curve: C the maximum current release breaks between 5 and 10 In; used to protect main power supply
cables and conventional consumers
Connecting:
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDO
* Power supply (conducting):
- power supply busbar DP1N
H[LEOHRUULJLGFRQGXFWRU
* Mounting: on DIN-rail

Circuit breakers DP1N (1P+N) - SIGMA design


Type

26

Rated current Breaking capacity


In (A)
(kA)

Recommended
sections of the
condmuocutonrtsin (g/mm2)

Packing/Box (pcs)

Catalogue number
Curve C

DP1N / 6

4.5

1.0

12 / 240

41006

DP1N / 10

10

4.5

1.5

12 / 240

41010

DP1N / 16

16

4.5

2.5

12 / 240

41016

DP1N / 20

20

4.5

2.5

12 / 240

41020

DP1N / 25

25

4.5

4.0

12 / 240

41025

DP1N / 32

32

4.5

6.0

12 / 240

41032

CIRCUIT BREAKERS
Auxiliary devices for circuit breakers

Type designation:
1FRQVWUXFWLYHVHULHV
number of poles - 1
Documents corresponding
to the product:
Standard EN60898-1

Type designation:
;FRQVWUXFWLYHVHULHV
number of poles - 1
Documents corresponding
to the product:
Standard EN60898-1

&RPELQHGYROWDJHFLUFXLWEUHDNHU1
Functions:
- when the voltage is reduced below 170V operation is initiated and the automatic switch is turned off
- when the voltage is increased above 270V operation is initiated and the automatic switch is turned off
- allows manual turning on of the switch after powering is restored
- indication of the position of the device
Technical characteristics:
* Rated voltage: 230/400V; 50/60Hz
,QVXODWLRQYROWDJH9
* Protection ratio: IP>20
Connection method:
'RXEOHFRQQHFWRUDW WXQQHO VFUHZFRQQHFWRU
* Feeding (conducting):
H[LEOHFRQGXFWRUVXSWRPP2
* Tightening moment of the screw: 1.33Nm
Mounting:
* vertical, by means of two pins attached to the rivets of the circuit-breaker, while the operating mechanism is connected to the switching off mechanism of the circuit breaker after the sealing lid is demounted
Type

Rated voltage

Type breaker

Packing/Box (pcs)

Catalogue number

ELMARK MN 2 60

230V



12 / 240

41909

Shunt release MX (independent release)


Functions:
- remote circuit breaker switching off at voltage feed
- allows manual switching on of the breaker at voltage recovery
- indication of the devices location
Technical data:
* Rated voltage: 230V; 50/60Hz
,VRODWLQJYROWDJH9
* IP code: IP>20
Connecting:
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDO
* Power supply (conducting):
H[LEOHFRQGXFWRUVXSWRPP2
* Tightening moment: 1.33Nm
* The power supply of the release is accomplished at the outlet of the breaker
Mounting:
* vertical, clamps with two pins to the breakers rivets and the executive mechanism is joined up to the switching
mechanism of the breaker after dismounting the seal cover
Type

Rated voltage

Type breaker

Packing/Box (pcs)

Catalogue number

ELMARK MX 60

230V



12 / 240

41902

$X[LOLDU\FRQWDFW2)
Functions:
-at circuit breaker switching off it sends a signal to the control or signalization system
-indication of the location of the auxiliary contact and the breaker
Technical data:
* Rated voltage: 230V
,VRODWLQJYROWDJH9
* Ingress protecting rating: IP>20
Connecting:
-RLQLQJWHUPLQDODW WXQQHO VFUHZWHUPLQDO
3RZHUVXSSO\ FRQGXFWLQJ H[LEOHFRQGXFWRUVXSWRPP
Mounting:
* vertical, clamps with two pins to breakers rivets, and the executive mechanism is joined up to the switching mechanism of the breaker after dismounting the seal cover
Type designation:
OF - constructive series
number of poles - 1
Documents corresponding
to the product:
Standard EN60898-1

Type

Rated voltage

Type breaker

Packing/Box (pcs)

Catalogue number

ELMARK OF 60
ELMARK SD100

230V



12 / 240

41901

230V

C100M

12 / 240

41905

27

You might also like