You are on page 1of 28

ELECTRICAL DESIGN

PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

ROLTA INDIA LIMITED

EDS ELECTRICAL DESIGN


PROCEDURES
Battery Sizing Calculations
Calculations
DTP-E-GEN-1003-00
Revision History
Revision
Level

Revision
Date

Revision
Description

Department Head
(Approver)

This Document and all contained herein are proprietary of ROLTA INDIA LIMITED and is subjected to confidentiality restrictions

between ROTLA INDIA LIMITED and the Recipient. Copyright Reserved.

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 1 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

Table of Contents
Sr. No
1
2
3
4

5
6

Description

Page no.

Purpose & Scope


Applicability
References
Procedure
4.1 General
4.2 Methodology of Calculation
4.3 Users Manual
4.4 Sample Output
Battery Sizing & Battery Charger Sizing
Sample Calculation of Battery Sizing

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

3
3
3
5
6
6
9
10
25

Page 2 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

1. Purpose & Scope


The purpose of this ETP is to describe the methods, which should be used to size, or to verify the
sizing of batteries and battery chargers and to determine the short circuit current available from the
battery and from the charger.
The purpose of this procedure is to provide:

A pre-approved calculation template to aid in calculating sizes and available short circuit
currents for battery and charger.

User instructions for EL-105 Battery Sizing, Battery Charger Sizing, and available Short
Circuit Current, for developing the user inputs and for performance of the calculation of
the size and short circuit current contribution for battery and battery.

2. Applicability
This procedure is applicable to all projects.
3. References
3.1 EL-105, Battery & Battery Charger Sizing & Available Short Circuit Current,
Version 00, Level 00.
3.2 Mathcad Version 7, Mathsoft Inc., Cambridge, MA
3.3 IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary
Applications, IEEE Standard 485-1997.
3.4 IEEE Recommended Practice for Design of the DC Auxiliary Power Systems for
Generating Stations, IEEE Standard 946-1992.
4. Procedure
4.1 General
The Electrical and Control Systems Engineer shall prepare a calculation to size batteries and
chargers and to determine available short circuit currents for all project procured DC
systems. DC components procured as part of a vendor supplied system (such as a fire alarm
system) where others are responsible for determining the electrical loads, do not require the
preparation of a calculation by the Engineer.

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 3 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

4.2 Methodology of Calculation

This ETP contains a pre-approved calculation EL-105, including battery sizing


methodology adapted from IEEE 485, battery charger sizing methodology adapted
from IEEE 946, and methodologies for calculating available short circuit current
from the battery adapted from IEEE 946, Annex B, and available short circuit
current from the battery charger adapted from IEEE 946, Annex D.

4.3 Users Manual


The EL-105 is divided into three sections:
a) Input
b) Calculation
c) Results
4.3.1 Input Data:
General:
The input section of the EL-105 Mathcad template should be completely filled in. All
input data necessary for this calculation shall be obtained from the project design
criteria, specifications, or IEEE referenced standards.
IEEE Standards 485-1997 and 946-1992 describe all necessary calculation procedures
for the selection or development of input data.
The user is prompted to input the battery duty cycle data, the design margins, battery
manufacturer and battery cell data, and battery charger design parameters. All
definition equations denoted by := shall be filled in.
The user can modify the information and text in the Input section.Text inputs shall be
contained in quotations (TEXT). The technical basis and source of the inputs shall
be properly documented in the body of the project calculation.
Note: When entering data or text be careful that the cursor encompasses the data or
text only and not the entire equation. Otherwise, the equation will be deleted when
using cut or backspace. and cannot be undone. Should this occur, either start
a new or copy the deleted formula from the original file and paste it in the working file.
Load Duty Cycle
The load duty cycle shall be developed following the instructions in IEEE 485.
Enter the loads for each step of the battery duty cycle in matrix A and associated
durations in matrix M.
The input matrices should be adjusted for the number of periods needed for the duty
cycle by using CTRL M and adjusting the number of rows in each matrix
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 4 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

accordingly.
MathCAD will not handle a single element matrix. If the load duty cycle is a
continuous value, such as for a UPS battery, use a 2 row by 1 column matrix and
assign the value of zero to the second row element
Enter random load, if required, and the associated time duration.
Design, Aging Margin, & Battery Room Temperature
Enter design margin, aging factor, and electrolyte temperature in degrees F.
Design margin and temperature are project-determined values. IEEE 485
recommends a design margin of 10-15%. The temperature should be the lowest
expected temperature for the battery room.
Provide reference for design temperature.
Battery Type
Select a battery manufacturer and cell type and enter this text as shown on the
template.
Enter the nominal cell voltage, typically 2.00 Volts-per-cell.
Enter the minimum cell voltage and total number of cells. Consult IEEE 485 or the
specialist for direction in determining these values.
Enter the values for time durations (all combinations) and lookup the associated
Amperes-per-positive-plate (R factors) for each time. Enter these into matrix R.
The user can look ahead to page 9 of the calculation to determine the needed values
of time from the calculated time matrix T, and then enter the values in matrix
R.
Enter the total number of plates in the TotalPlates matrix based on the selected
manufacturers cell data sheet. Enter the associated 8-hour Ampere-hour discharge
ratings in the BattSze_Ah, matrix. If additional sizes or a change in the cell type
needs to be made, this can be adjusted at any time.
From the manufacturers initial voltage curve for the chosen battery cell type select
two points and enter the voltage and Amperes-per-positive-plate values for each
point.
Battery Charger Design Parameters
The battery charger input data should be entered as follows:
8 to 24 hours recharge time.
Recharge efficiency factor of 1.1.
Continuous load Amperes that must be served by the charger during normal plant
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 5 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

operations (ac restored) while the battery is being recharged.


Largest combination of noncontinuous loads that would be likely to be connected
to the bus simultaneously during normal plant operations.
The StdCharger matrix lists the most commonly available charger sizes. If
necessary, the user can add sizes to this matrix by using CNTRL M.
4.3.2. Calculation
Template parameters are set. These parameters are not user adjustable without
removing the lock on the pre-approved calculation. Special functions are defined to
allow the creation of a graphical presentation of the load duty cycle entered.
Calculation of Battery Size
The template calculates the size of the battery using the positive plate method of
calculation for sizing lead-acid batteries taken from IEEE 485.
Temperature correction factors from IEEE 485 have been included in the template
for automatic lookup by Mathcad.
The number of positive plates is calculated using design margins from the input
and a lookup feature determines the Ampere-hour size of the battery based on the
input data.
Calculation of Battery Charger Size
The template calculates the size of the charger based on the calculation
methodology of IEEE 946. This method compares the Ampere-hours from the
battery with the sum of the continuous and non-continuous loads and selects the
larger sized charger.
The template calculates two charger sizes based on the IEEE 946 method
comparing the sum of the continuous and non-continuous loads with each of the
following:
1. The load duty Ampere-hours discharged from the battery.
2. The 8 hour Ampere-hour rating of the selected battery.
Calculation of Battery and Charger Short Circuit Current
Battery short circuit current is calculated automatically using the input data from
the initial voltage curve of the battery.
Battery charger short circuit current is calculated automatically using the input
data, and in accordance with Annex D of IEEE 946, is based on 1.5 times the full
load rated output.
The values of short circuit current for both battery and charger are calculated at
the nominal system voltage (typically 120 Vdc for a 60 cell battery) for use in the
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 6 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

DC system fault current analysis calculation.

4.3.3. Results
The Calculation and Results sections of the MathCAD template is locked
to prevent accidentally changing the equations from the qualified MathCAD
template. The password to unlock the calculation section is SW245. If the
calculation section is unlocked, the engineer shall review and check the entire
calculation including the pre-approved areas. The date when the qualified Mathcad
files were locked is Friday, September 4, 1998. In order to properly print the date
stamp for the locked area on page 6 of the program, a non-postscript print driver
must be used.
The Results section repeats the essential input data and then prints the results of
The template for each section of the calculation, Battery Size, Battery Charger
Size, and Short Circuit Current Available. This is done for convenience of
viewing the input data with the results.
4.3.4. Program Limitations and General Instructions
The methodology is based on sizing batteries of the lead-acid stationary battery
type, which includes Lead-Calcium, Lead-Antimony, and Lead-Selenium. It is
recommended to use the Lead-Calcium type for stationary battery use. It is not
suitable for use in sizing Nickel-Cadmium type batteries. Refer to IEEE
Standard 1115-1992 for guidance for this type of battery cell.
The template calculates battery charger size in the following two ways:
1. The larger of the Ampere-hours discharged from the battery or the
combination of continuous and non-continuous loads.
2. The larger of the rated Ampere-hour size of the selected battery or the
combination of continuous and non-continuous loads.
3. The more conservative approach using the Ampere-hour rating of
the battery is recommended in IEEE 946. The user should select the
method that satisfies the project specification requirements.
The template calculates the available short circuit currents for
batteries and chargers at their terminals. This data is intended for use as
input to a dc system fault analysis calculation. The value of charger short
circuit current should be selected based on the associated sizing method.
The calculation assumes the intercell connector resistance is included in the
manufacturers initial voltage curve. If the intercell connector resistance is
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 7 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

not included in the input data, the resulting short circuit current at the terminals

of the battery will be a conservatively higher value. The resistance values


of inter-rack and battery terminal cables shall be included in the DC
system fault current analysis calculation and are not included in this
calculation.
The heading and footer of the template can be modified, except that the left
hand section of the footer, EL 105 V00 L00 shall not be changed.
MathCAD Version 7.0 or later and Windows 95 operating system are
required to run EL-105.
The Page Setup feature for the Mathcad files is set to ensure proper
printing as follows:
a) Letter 8.5 x 11 inch
b) Portrait
c) Margins are set: Left and Right are 1.0 inch; Top is 1.5 inch; Bottom is
1.0 inch
4.4. Sample Output EL-105
The entire output of EL-105 should be included as an attachment to a project
calculation. In the Methodology section of the project calculation, the
following text shall be included to describe the methodology used in EL105.
Attachment A (Note: Attachment A should represent the actual battery and
charger sizes calculated and not the appendix A example attached to this
ETP) is the output of EL-105, Battery Sizing, Battery Charger Sizing, and
Available short Circuit Current, a MathCAD template.
Attachment A includes a run of sample battery sizing, charger sizing, and
short circuit calculations. The battery data used is taken from the sample
calculations in IEEE 485, Figures A1 and A4.

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 8 of 28

ELECTRICAL DESIGN
PROCEDURES

5.

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

BATTERY SIZING, BATTERY CHARGER SIZING


AND AVAILABLE SHORT CIRCUIT CURRENT
References:
1. IEEE 485 - 1997, IEEE Recommended Practice for Sizing Lead-Acid Batteries for

Stationary Applications.
2. IEEE 946 -1992, IEEE Recommended Practice for the Design of DC Auxiliary
Power Systems for Generating Stations.
I.

INPUT
A. Load Duty Cycle
The load duty cycle is developed per instructions contained in IEEE 485.
Loading of each section
of battery discharge, in
Amperes ( Column 2 in
IEEE 485, worksheet Figure A-4).

Time duration of each section


of battery discharge, in minutes
(Column 4 in IEEE 485,workshe
-et Figure A-4).

320
100
280

A=

1
29
30
B=

200
40
120

Copyright 2008. Rolta India


Limited. All Rights Reserved.

60
59
1

Issue Date:
Uncontrolled When Reproduced

Page 9 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

Note: Use CTRL "M" to insert or delete rows and columns in the above matrices.
.Random A := 100
Random Current, A
Random M :=1
Time duration of random
current, minutes
B. Design, Aging Margin, & Battery Room Temperature

DesignMargin ----------------AgingFactor ----------------Electrolutye temp Low-------C. Battery Type

1.15
1.25
65 F

(USER TO MODIFY - TEXT IN QUOTES)

The battery manufacturer's type of cell is selected as follows:


Reference -------------------- "ABC-123"
Manufacturer----------------- "ABC"
Cell Type-------------------"XYZ"
Cell Voltage-----------------2.00
Volts-per-cell, nominal open circuit.
Minimum_Cell_Voltage--1.75 ----- Volts-per-cell
Total Number Cells = 60
R factor for battery:
1 st Column is the time duration associated with a specific R factor.
2 nd Column is R factor (Item 6A of Column 6 discharge period in IEEE 485, Sample Worksheet
Figure A-4).

Cell Type ="XYZ"


Available battery sizes, in terms of the total number of plates and Ampere-hour ratings for an 8 hour .
1

R=

104

11

30 55.4

13

59 40

15

60 40

17

TotalPlates=

90 32.5
119 27.5

19
21

120

27.5

23

150

24.0

25

179

21.5

27

180

21.5

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 10 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

400

480
560

Batt Size_Ah=

640
720
800

880
960

64

1040

Note: Use CTRL "M" to insert or delet rows and columns in theabove matrices
Select two points on the manufacturer's initial voltage curve (V1,I1) and (V2, I2) that will be used for the
calculation of short circuit current: (Ref. IEEE 946-1992, Fig. B.1)
V1

1.90

V2

1.50

Volts

I1=60

Volts

I1=370

Amperes per positive plate


Amperes per positive plate

D. Battery Charger Design Parameters(Reference IEEE 946-1992, Sample A.3)


Tc8

Time to recharge the battery to approximately 95% of capacity (in hours)


(This is same as the symbol "T" in equation 1 of IEEE Std 946, which was
modified to avoid confusion with the use of "T" in battery sizing).

C=1.1

Constant that compensates for battery losses.

L c 50

Continuous dc load (Amperes), including future load growth (1.30


factor), in Amperes.

L n 60

The largest combination of noncontinuous loads in Amperes (as defined in


IEEE Std 485) that would likely be connected to the bus simultaneously
during normal plant operations.
3
6
12
25
50
75

StdCharger =
Copyright 2008. Rolta India
Limited. All Rights Reserved.

100
150

Standard Charger Sizes, Amperes DC

Issue Date:
Uncontrolled When Reproduced

Page 11 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

200
300
400
432
500
600
800
1000

II. Calculation
A. Template Parameters

the

see= rows A)

sec 6

i= 1 sec

j= 1 sec

m= 1 sec

n= 1 sec

Lookup num A1 A2) = for


return

ORIGIN=1

i 1 last A1)

This defines a function called Vector "A,"

A2 if

value in the is returned.If "A",then the messa


-ge "NF" (not found) is returned.

A1inum

i
"NF"

Replicate A s) =

0
for

i 1 last A)

Creates a function called


"Replicate" which doubles the
size of matrix A, repeating the
value of each element.

for j 1 s
TkjAi
k k 2

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 12 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

+
T

LookupCol Vector sF) = for

i 1 last Vector)

return

Similar to "Lookup" function,


except only the first column
is used.
Vector if

"Out of Range"

B Duty Cycle Curve Plot


CREATING THE "CURRENT" VECTOR
AA

= Replicate (A, 2)

Double the size of the current "A" matrix and call


it "AA" matrix.

AA rows (AA)+1 : = 0
q :=1 ( rows AA)+1 )

Add an additional element to "AA" matrix at the


end and set it equal to zero so that current curve
will return to zero.

AAAq :=if ( q =1,0,AA q-1

Current Vector"AAAq"

CREATING THE "TIME" VECTOR

r:= 2 rows (M)


time1 := M1

Set first element of "time" matrix to first element of


"M"
Add the next element of "M" matrix to the previous
element of "time" matrix.

timer : =Mr + time r-1


Dbl_time := Replicate (time ,2 )

q := 1 ( rows (Dbl_time)+1 )

Copyright 2008. Rolta India


Limited. All Rights Reserved.

"Time" matrix is now doubled and called "Dbl_time."

Add additional element to "Dbl_time" matrix at the


beginning, and set it equal to 0.

Issue Date:
Uncontrolled When Reproduced

Page 13 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

Dbl_timeplusq := if (q =1, 0

DTP-E-GEN-1003-00

Dbl_time q-1)

q := 1 ( rows (Dbl_timeplus) + 1 )

Repeat above step to add one additional 0

element.
DDbl_timeplusq := if (q= 1, 0Dbl_timeplus q-1)
C. Change in Load

Ai :=if [i = 1, Ai,Ai - A (i-1) ]


Change in load Amperes of present
section load compared with the previous
section load (Column 3 in IEEE 485 example.

320
-220

180

A =

-80

80

A_testi : = if (i= sec, Ai, Ai Ai+1)


220

Change in load Amperes of previous section load compared with present

A_test section

load.

160

-80
120

D. Time to End of Section (minutes)


T(i i) := 0
T1, j := if [ j= 1, M1Mj + T1(j -1)
Ti,j :=if [ i= 1 ,Ti,jT(i 1j) M (i-1)]
.
Tij := if ( Ti,j 0,0, Ti,j )
Ti,j := if ( - testj < 0,0,Ti,j )

Eliminates section calculation if load duration of

the next section is greater than present section,

i.e., Ai+1 is greater than Ai

1 0 60 120 0 180
ime to end of section, in minutes.
0 0 30 90 0 150
Columns represent each section;

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 14 of 28

ELECTRICAL DESIGN
PROCEDURES
T=

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

rows represent the period within


each section.

0 0 0 60 0 120
0 0 0 0
0 60
0 0 0 0
0 1

E. IEEE 485 Temperature Correction Factors


The first column is the electrolyte temperature in degrees F. The second column is the correction
factor from Table 1 of IEEE 485.

Table 1a =

Copyright 2008. Rolta India


Limited. All Rights Reserved.

25

1.520

78

0.980

30

1.430

79

0.987

35

1.350

80

0.980

40

1.300

81

0.976

45

1.250

82

0.972

50

1.190

83

0.968

55

1.150

84

0.964

60

1.110

85

0.960

65

1.080

86

0.956

66

1.072

87

0.952

67

1.064

88

0.948

Table 1b =

Issue Date:
Uncontrolled When Reproduced

Page 15 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS


68

1.056

89

0.944

69

1.048

90

0.940

70

1.040

95

0.930

71

1.034

100

0.910

72

1.029

105

0.890

73

1.023

110

0.880

74

1.017

115

0.870

75

1.011

120

0.860

76

1.006

125

0.850

77

1.000

DTP-E-GEN-1003-00

Table1 := stack (Table 1a,Table1b )


TempCorrFactor := Lookup ( ElectrolyteTempLow Table11 )
TempCorrFactor 1.11
F. Battery Size - Positive Plate Method (R Factor)
R1 : =R <1>
Rmatrix i,j

R2 := R <2>

Divides the 2 column matrix, "R," into two vectors.

: = if ( Ti,j = 0, 0,Lookup (Ti,j ,R1,R2 ))

This is matrix of R factor of each value of


time in the matrix T. If the time in T is
zero, then the value in RMatrix is set to
zero. If a value in T is not found in matrix
R, an input, then NF (Not Found) is
reported. The user has to then to correct his
input matrix R by inserting missing value(s).

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 16 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

This replicates DA into a matrix of identical columns.

This calculates the required section size (Column 7 in IEEE 485) , the number of positive plates for each
period in each section.

This is the section size of each section.The subtotal of each column of matrix Col 7 in
Ampere-hours.
MaximumSectionSize = max (SubtotalCol7) This is maximum section size, in positive plates.
MaximumSectionSize 7.1748

Positive plates, maximum section size

Random A

This is the number of positive plates

Random Section Size: =


Lookup (Random M R1R2)
Copyright 2008. Rolta India
Limited. All Rights Reserved.

required for the random load.

Issue Date:
Uncontrolled When Reproduced

Page 17 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

RandomSectionSize 0.962

DTP-E-GEN-1003-00

Positive plates, random load.

UncorrSizeRFactor: = MaximumSectionSize + RandomSectionSize


UncorrSizeRFactor: = 8.136
Uncorrected total number of positive plates.
PositivePlatesRq: = UncorrSizeRFactor X TempCorrFactor X DesignMargin X AgingFactor
PositivePlatesRq: = 12.63
PositivePlates: = ceil (PositivePlatesRq)
PositivePlates: = 13
Total number of positive plates required.
Plates: = (2 X PositivePlates) + 1
Plates = 27
Total number of plates required.
AmpHour_SizeR:= Lookup (Plates TotalPlates BattSze_Ah)
AmpHour_SizeR = 1040
Ampere-hour size of battery required (R factor)
G. Charger Size

Charger size based on Ampere-hours discharged from the battery:

Total ampere hours discharged from the battery during its specified duty cycle, Ampere-Hours.
I 1= L c + C Ah

I1 = 144.971

Minimum required charger size,Ampere

Tc
I 2 = Lc + L n

(Equation 1 from IEEE 946 ).


I2 = 21.78

I 3= if (I 1, I 2I 1 I 2 )

Sum of continuous and noncontinuous loads,


Amperes (Equation 2 from IEEE 946).
Larger of the two above sizes.

I3 = 144.971

Charger_Size:= LookupCol (StdCharger I 3 1)


Charger_Size 150

Amperes DC, based on Ampere-Hours


discharged from the battery.

Charger size based on the rated size of the


selected battery:
Minimum required charger size, based on
Ampere-hours size of selected battery
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 18 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

(Equation 1 from IEEE 946).

Sum of continuous & noncontinuous loads, Amperes (Equation 2 from IEEE 946)
Larger of the two above sizes.

Selected_Charger_Size:= LookupCol( StdCharger , I 5 , 1)


Selected_Charger_Size 200

Amperes DC, based on rated Ampere-hours of the


selected battery.

H. DC SOURCE SHORT CIRCUIT CONTRIBUTION


Battery (Based on IEEE Standard 946, Annex B):
The internal resistance of a cell is calculated from the slope of the initial volts line of the
Published discharge characteristic curve of the manufacturer. The internal resistance is
Determined as follows:
PositivePlates = 13
Rp=( V1
(I2

Number of positive plates

- V2)

Rp =1.29 x10-9

I1)
Rp=
Rp
Positive plates

Ohms per positive plate.

Rt =9.926 x10-5

Rb Rt Total_Number_Cells

Total internal resistance of cell

Rb 5.955 x10-3 Ohms,total battery resistance.

The short circuit current available at the cell terminals is found from Ohm's law as follows:
CellVoltage 2.00

Volts/cell, nominal cell voltage

Batt_Voltage = CellVoltage Total_Number_Cells


Batt_Voltage 120

Volts, nominal battery voltage

Ic1 20150

Amperes, available short circuit current

2. Battery Charger (Based on IEEE Standard 946, Annex D):


The maximum battery charger available continuous short circuit current is 1.5 times the full
load current rating of the charger.
Charger Voltage: = Batt_Voltage
Charger Voltage = 120 Volts, DC
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 19 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

Charger based on the larger of the the Ampere-hours discharged from the battery or the
combination of continuous and non-continuous loads:
Charger_Size 150 Amperes
Icharger_fault=1.5 charger_Size
Icharger_fault =225 Amperes
Charger based on the larger of the rated Ampere-hour size of the battery or the
combination of continuous and non-continuous loads:
Selected_Charger_Size = 200 Amperes
Icharger_Selected_fault:= 1.5 Selected_Charger_Size.
Icharger_Selected_fault = 300 Amperes

A. Battery Size:
1. Inputs: Load Duty Cycle
Section

Amperes Time (minutes)

320
1
100
29
280
A=

M=

30

200

60
59

40
1
120

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 20 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

For load duration curve see the following curve-----

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 21 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

DesignMargin =1.15
AgingFactor =1.25
ElectrolyteTempLow =65 Degrees F, lowest electrolyte temperature
TempCorrFactor =1.08
2. Results:

Minimum_Cell_Voltage =1.75

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Volts per cell end voltage

Issue Date:
Uncontrolled When Reproduced

Page 22 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

Total_Number_Cells =
60

DTP-E-GEN-1003-00

Total number of cells

PositivePlates =13

Number of positive plates

Plates =27

Total number of plates required.

AmpHour_SizeR =1040

Ampere-hours for an 8 hour discharge to the


specified Volts-per-cell end voltage.

Manufacturer ="ABC"

Cell_Type ="XYZ"

B. Battery Charger Size:


1. Inputs:
T c= 8

Hours, recharge time

C =1.1

Recharging efficiency constant

L c =50

Amperes, continuous DC load

L n= 60

Amperes, largest combination of noncontinuous loads

2. Results:
Charger_Size =150

Amperes DC, based on the larger of the the


Ampere-hours discharged from the battery or
the combination of continuous and non-continuous loads.

Selected_Charger_Size =200

Amperes DC, based on the larger of the rated


Ampere-hour size of the selected battery or the
combination of continuous and non-continuous loads.

C. Short Circuit Current Available


1. Inputs:
CellVoltage =2.00 Volts per cell, nominal

Initial Voltage Curve Data


V1 = 1.90

Volts

I1 = 60

Amperes per positive Plate.

V2 = 1.50

Volts

I2 = 370 Amperes per positive Plate.

2. Results :
Copyright 2008. Rolta India
Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 23 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

a. Battery Short Circuit Current


Batt Voltage = 120 Volts, DC, nominal battery short circuit voltage.
Ic1 = 20150

Amperes, available battey short circuit current

b. Battery Charger Short Circuit Current


Charger Voltage = 120 Volts, DC, nominal charger short circuit voltage.
Charger based on the larger of the Ampere-hours discharged from the battery or the
combination of continuous and non-continuous loads.
Icharger Fault = 225

Amperes, available charger short circuit current

Charger based on the larger of the rated Ampere-hour size of the battery or the
combination of continuous & non-continuous loads:
Icharger Selected Fault = 300 Amperes, available charger short circuit current.

6.SAMPLE CALCULATION OF BATTERY SIZING


1.0 Site and system Conditions
Ambient temp.
: Max: 46.6C, Min: -0.7C
Design ambient temp.
: Max: 45C, Min: 10C (for battery sizing)
Maximum voltage
: 220, +10% 242V (as per Bid package)

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 24 of 28

ELECTRICAL DESIGN
PROCEDURES
Minimum voltage
End cell voltage

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

: 220, -10% = 198 V (as per Bid. package)


: 1.16V (as per Bid package)

2.0. Battery sizing calculation


2.1 No of cells
Number of battery cells shall be based on the following
No.of cells : Maximum allowable system voltage/Float charging voltage per cell
=242V/ 1.41 = 171.63 = 172
Minimum system voltage No of cells x End cell voltage = 172 x 1.16= 199.52V
No of cells selected : 172
2.2 Calculation of load cycle
2.2.1 Calculation of continuous electrical loads (I2)

S.NO

DESCRIPTION

QTY

TOTAL
NO OF
PANEL

LOAD(W)
UNIT ITEM

TOTAL
LOAD(W)

Indicating lamps for HV sw.bd (6.6kV &


33kV)

3 per panel

34

2.5

255

Indicating lamps for MV sw.bd

3 per breaker feeder

70

2.5

525

86 relay

2 per sw.bd

10

3.0

60

Aux.relay

1 per bkr feeder

100

300

Motor protection relay

50% of HV and MV
motors

13

15

195

Motor diff. relay

As per project design


data

15

45

Under voltage relay

4nos per sw.bd

15

300

ELR for motors rated above 22KW

50% of motors

I2

36

Annunciation panel loads

As per design data

10

DC lighting load

As per plan layout

2200

11

Misc.loads such as EPABX,LCP etc.

Copyright 2008. Rolta India


Limited. All Rights Reserved.

As applicable

Issue Date:
Uncontrolled When Reproduced

Page 25 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

12

Owners load for critical lighting

1000

13

Owners DC load for Elect. Control

2000

14

ECS Load

15

Any other load

DTP-E-GEN-1003-00

2000
-

Total load = 8916 watts


TotaI current (I2) 40.55 Amps
2.2.2 Calculation of electrical load (I4)
S.NO

DESCRIPTION

QTY

TOTAL NO OF
PANEL

LOAD(W)
UNIT ITEM

TOTAL
LOAD(W)

HV incomer bkr tripping on


U/V

2 no. per swbd

300

600

MV incomer bkr tripping on


U/V

2 no. per swbd

200

1400

Breaker fed motor tripping


on U/V

50% HV and MV motors

13

6 nos. - 300W
(HV) & 7 nos.
200W(MV)

3200

Aux.relay

1 per HV panel + 4 per


PCC / EPMCC

46

138

Closing of EPMCC
incomer

1No.

200

200

Any other load

Total load = 5538 watts


TotaI current (I4) = 25.173 Amps
2.2.3 Calculation of electrical load (I5)

Copyright 2008. Rolta India


Limited. All Rights Reserved.

Issue Date:
Uncontrolled When Reproduced

Page 26 of 28

ELECTRICAL DESIGN
PROCEDURES

BATTERY SIZING CALCULATIONS

DTP-E-GEN-1003-00

DESCRIPTION

QTY

TOTAL NO OF
PANEL

LOAD(W)
UNIT ITEM

TOTAL
LOAD(W)

Closing of main HV
incomer bkr

2 nos. per substation

300

600

Closing of main MV
incomer bkr

2 nos. per substation

200

400

Breaker spring charging


motor

2 nos. per substation

400

800

Aux.relay

1 per HV panel + 4 per PCC


/ EPMCC

46

138

Any other load

S.NO

Total load = 1938 watts


TotaI current (I5) = 8.809 Amps
2.24 Calculation of random electrical load (IR)
IR = load expected during any period of the duty cycle
= NIL Amps.
Electrical Loads for various duty cycle are
First minute duty cycle I1 =I2 + I4 = 40.53 + 25.173 = 65.703 for duration of M 1 minutes
66A for 1 min.
Next duty cycle
I2 = I2 = 40.53 A for duration of M2 minutes
= Approx. 41A for 118 min
cycle
I3=I2+I5 = 40.53 + 8.809 = 49.339 for duration of M3 minutes
= Approx. 50A for 1 min
IR = lR for duration of MR minutes - NIL

= Approx.
Last minute duty
Random load if any

Loads and time duration is tabulated as shown below

2.3 Duty cycle diagram


S. NO

LOADS(A)

DURATION(MIN)

1.0

I1

66

Copyright 2008. Rolta India


Limited. All Rights Reserved.

REMARKS

Issue Date:
Uncontrolled When Reproduced

Page 27 of 28

ELECTRICAL DESIGN
PROCEDURES

Copyright 2008. Rolta India


Limited. All Rights Reserved.

BATTERY SIZING CALCULATIONS

Issue Date:
Uncontrolled When Reproduced

DTP-E-GEN-1003-00

Page 28 of 28

You might also like