xxxx TOWER
Location xxx
Kb 1
Hr 30 m
Reference height
He Hr
Sa 1 + 0.001 S
altitude factor
Sa = 1.1
Sd 1
Ss 1
Sp 1
Vs Vb Sa Sd Ss Sp
m
Vs = 27.5
s
for building heights larger that the width some reduction in wind loads may be obtained
by dividing the building into a number of parts - in our case the reduction is neglijable.
L 51 m
building length
W 25
building width
L
= 1.7
He
xxxx TOWER
Location xxx
Longitudinal coefficients
Cpe.winward.L 0.749
Cpe.leeward.L 0.249
W
1
= 0.833
He
m
Transversal coefficients
Cpe.winward.T 0.800
values in Table 5
Cpe.leeward.T 0.300
Ca.L 0.848
Ca.T 0.816
Dynamic pressure per BS 6399-2 Section 2.1.2
2
Ve
qs 0.613
Pa
m
s
3
qs = 1.781 10 Pa