Super Solution
Meta Solution
ACB
Super Solution
Overview
External configuration
14
Internal configuration
16
Ordering
18
Ratings
22
Trip relays
26
Accessories
52
Electrical diagram
80
Dimensions
82
Technical information
Contents
Insulation voltage
Temperature derating
Operating conditions
Installation recommendation
Protective coordination
104
105
106
107
113
119
Time chart
120
Ordering sheet
123
Premium Susol ACB meets your demands for high breaking capacity,
fully line-up, and optimized panel size.
Various accessories and connection methods realize user-friendly handling.
Susol ACB provides you with total solutions with an advanced trip relay
for measurement, diagnosis, analysis, and communication as well as protective
functions for absolute protective coordination and electric power monitoring system.
H = 430mm
W = 334mm
85kA
AH-06~20D
06
08
10
13
16
20
630AF
800AF
1000AF
1250AF
1600AF
2000AF
Icu=Ics=85kA/500Vac
W=334(3p), 419(4p)mm
W = 412mm
100kA
AH-06~40E
06
08
10
13
16
630AF
800AF
1000AF
1250AF
1600AF
Icu=Ics=100kA/500Vac
W=412(3p), 527(4p)mm
20
25
32
40
2000AF
2500AF
3200AF
4000AF
m
5m
37
=
D
W = 785mm
150kA
The highest breaking capacity:
T
150kA (6300AF at 500Vac)
3 ampere frame sizes:
3
2000/4000/6300AF
N phase current conducting capacity: 100%
N
AH-40~63G
40
50
63
4000AF
5000AF
6300AF
Icu=Ics=150kA/500Vac
W=785(3p), 1015(4p)mm
Trip Relay
(OCR)
Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism.
It makes the breaking capacity of ACB improved and ACBs life enhanced, and provides
advanced functions - measurement, diagnosis, analysis, and communication.
L/S/I/G/Thermal
Self Power
RTC Timer mounted
Fault information (LED)
A type
P/S type
L/S/I/G/Thermal
ZSI
Remote Reset
Modbus/RS-485
Profibus-DP
Self Power
AC/DC 100~250V
DC 24~60V
RTC Timer mounted
Fault Recording (10EA)
L/S/ I/G/Thermal(Continuous)
UV/OV/OF/UF/rP/Vun/Iun
Measurement: V/A/W/Wh/F/PF
Harmonics (63th), Waveform (S Type)
ZSI
Remote Reset
Modbus/RS-485
Profibus-DP
AC/DC 100~250V
DC 24~60V
RTC Timer mounted
Event Recording (256EA)
Fault Recording (256EA)
Fault Wave (S Type)
N Type (Normal)
P
type
A
type
A Type (Ammeter)
Current Meter + Current protection +
DO control + Communication
S
type
S Type (Supreme)
P type + Harmonics analysis (63 th) +
Fault wave recording
Accessories
ACB
Trip Relay (OCR)
Motor (M)
Counter (C)
MOC (Mechanical
Cradle
Other
Condenser Trip Device (CTD)
Manual Connector
Zero Arc Space (ZAS)
MOC (Mechanical
Dummy ACB
UVT Time Delay Controller (UDC)
Profibus-DP Communication module
Remote I/O
Temperature Alarm
Connection
and Installation
Diverisified terminal connection methods of the ACB main circuit for users.
Multiple connections
Various installation methods
Standard connection
Horizontal type
Vertical type
Front type
Mixed connection
The Front connection type can be connected to the main circuit of CB and is suitable for the
T
distribution panel that demands small space for installation.
The same kinds of Vertical and horizontal type terminals are alterable in fallowing case such as
T
AN-06~16D, AS-20E~32E, AH06D~20D, AH-06E~32E.
Note) AS-20D, AH-20D are vertical type terminals only.
Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.
External configuration
Fixed type ACB
Terms
Trip relay
Counter
OFF button
ON button
Series name
Charge handle
Cradle
Draw-out handle
Position indicator
Arc chute
Front cover
Fixed type bracket
14
Cradle (Internal)
Cradle (Rear)
Terms
Terminal cover of control circuit
Cradle finger
Cradle finger
Connecting terminal
Draw-out handle
Connecting terminal
Position indicator
[Secondary nameplate]
Explanation of terminologies
Motor charge
Control power and
Closing coil
terminal No.
Shunt tripping coil
Auxiliary switches: Contact specification
and terminal No.
Under voltage trip: UVT terminal No.
OCR control source: Trip relay control power
Alarm switch: Alarm and terminal No.
Digital trip relay: Switching diagram
Z.S.I: Input/Output terminal No.
Reset: LED/LCD reset
Communication: Communication and
terminal No.
Voltage module: Phase voltage and symbol
Earth/Leakage: Ground fault / Earth
leakage input terminal No.
15
Internal configuration
Terms
Arc chute
Aux. switch control terminal
Control power supply terminal
Carrying grip
Shunt coil
Mechanism
Main body
Counter
Shunt coil
Closing coil
Motor Assy
Aux. switch
ON button
OFF button
MTD base
Trip relay
Front cover
16
Terms
Trip relay
Front cover
Mechanism
Charge handle
Trip spring
Closing spring
Draw-in/out device
Arc chute
Moving contact
Fixed contact
Terminal on line side
Cradle finger
Cradle
Connecting terminal
Power supply CT
Terminal on load side
17
Ordering
ACB & Accessories
AH
10
Type
Ampere
frame
No. of pole
AH
10
3P/4P
AS
AN
06
630AF
Standard
type
3P(D)
RST(N)
AH
AN
AS
08
800AF
10
1000AF
13
1250AF
16
1600AF
20
2000AF
20
2000AF
Rated current
(CT Spec.)
00
02
200A
04
400A
06
630A
04
400A
06
630A
Draw-out type
J
A
Manual
connection
Automatic
connection
Fixed type
08
800A
Horizontal type
Reverse
10
1000A
Vertical type
13
1250A
16
1600A
20
2000A
3P/4P
06
630A
Standard
08
800A
10
1000A
13
1250A
16
1600A
20
2000A
25
2500A
phase type
4P(D, W)
type
3P(E)
RST(N)
AH AS
4P
Reverse
25
2500AF
32
3200AF
phase type
32
3200A
40
4000AF
NRST
40
4000A
Connections
4P
NRST
4P(E, X)
Mixed type
M
Horizontal
Vertical
Mixed type
Vertical
Horizontal
Front type
3P/4P
40
4000AF
Standard
3P(F)
40
4000A
4P(F, Y)
50
5000A
3P(G)
40
4000A
50
5000A
63
6300A
type RST(N)
AS
4P Reverse
50
5000AF
phase type
NRST
AH AS
40
4000AF
50
5000AF
63
6300AF
20
2000AF
40
4000AF
Standard
type RST(N)
4P Reverse
phase type
D
D
RST(N)
W Reverse NRST
E
RST(N)
Reverse NRST
* Rated short-circuit withstand current of the protective circuit in earthing product : 60kA/1s
18
4P(G, Z)
NRST
20
AT
Earthing
product
3P/4P
G
00
3P
4P
M1
D1
D1
NG0
AX
Without Motor
D0
M1
AC/DC 100V~130V
D1
AC/DC 100V~130V
M2
AC/DC 200V~250V
D2
AC/DC 200V~250V
M3
DC 125V
D3
DC 125V
M4
DC 24V~30V
D4
DC 24V~30V
M5
DC 48V~60V
D5
DC 48V~60V
M6
AC 380V~415V
D6
AC 380V~480V
M7
AC 440V~480V
D7
AC 48V
M8
AC 48V
Refer to 26page
D0
AX
U0
D1
AC/DC 100V~130V
AC
U1
AC/DC 100V~130V
D2
AC/DC 200V~250V
BX
U2
AC/DC 200V~250V
D3
DC 125V
BC
U3
DC 125V
D4
DC 24V~30V
HX
U4
DC 24V~30V
D5
DC 48V~60V
HC
U5
DC 48V~60V
D6
AC 380V~480V
CC
U6
AC 380V~480V
D7
AC 48V
JC
U7
AC 48V
TX
TC
3)
AL
Trip relay
MA
U1
Note)
Note)
Option
AL
A1
A2
A3
A4
A5
A6
A7
A8
A9
C
S 2)
B
M
Type name
AL1+MRB
AL1+MRB+RES (AC110~130V) *AC private use
AL1+AL2+MRB
AL1+MRB+RES (DC110~125V) *DC private use
AL1+MRB+RES (AC200~250V) *AC private use
AL1+MRB+Auto reset
AL1+AL2+MRB+Auto reset
AL1+MRB+RES (DC110~125V)+Auto reset *DC private use
AL1+MRB+RES (AC200~250V)+Auto reset *AC private use
AL1+MRB+RES (AC110~130V)+Auto reset *AC private use
C
Counter
CS2
Charge switch communication
B
On/Off Button lock
MI
Mechanical interlock **AN typenot applied
Option
Type name
DI or MOC
K
K2
K3
R 2)
T 3)
K1
K2
K3
RCS
TM
H1
H2
H3
H4
H5
H6
H7
1)
SHT2
19
Ordering
Cradle
AL
LS ACB cradle
N16D
AN-06~16D
S20D
AS-20D
No. of pole
3
3P
4P
H
V
S25E
Connections
Safety shutter
Horizontal type
(20D inapplicable)
Vertical type
AS-20~25E
E
F
Without
safety shutter
With safety
shutter
Mixed type
S32E
AS-32E
S40E
AS-40E
S50F
AS-40~50F
S50G
AS-40~50G
S63G
AS-63G
H16D
AH-06~16D
H20D
AH-20D
H32E
AH-20~32E
H40E
AH-40E
H50G
AH-40~50G
H63G
AH-63G
Terminal
connections
J
A
Line: Horizontal
Load: Vertical
Manual
(20D inapplicable)
connection
Mixed type
Automatic
Connection
Line: Vertical
Load: Horizontal
(20D inapplicable)
Front type
Option
55223460402
HANDLE ASS'Y, DRAW, LONG
20
55223460404
HANDLE ASS'Y, DRAW,
LONG, AL-D, E, F, G, HYX
Arc cover
(Zero Arc Space)
N
S
Without
Arc cover
With
Arc cover
Note)
AH Series:
S(with Arc cover) only.
Trip relay
N
Normal
Ground fault
A
A
Ammeter
Self-Power
60Hz
Self-Power
50Hz
Ground fault
Self-Power
60Hz
DC 24V~60V
60Hz
Self-Power
50Hz
DC 24V~60V
50Hz
P
P
Power meter
DC 24V~60V
DC 24V~60V
60Hz
50Hz
S
S
Supreme meter
Comm.
DC 24V~60V
DC 24V~60V
60Hz
50Hz
21
Ratings
Type
Ampere frame
(AF)
Rated current(A)
(In max)
at 40
22
63/74
70/85
61/72
68/83
29/32
33/40
34/44
38/47
32/42
36/45
430334375
430419375
300300295
300385295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
AH-06E
630
AH-08E
800
AH-10E
1000
AH-13E
1250
AH-16E
1600
AH-20E
2000
AH-25E
2500
AH-32E
3200
AH-40E
4000
AH-40G
4000
AH-50G
5000
AH-63G
6300
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
800
1000
1250
1600
2000
3200
4000
1,000
690
12
50/60
3/4
100
100
85
100%
220
220
187
85
75
65
40
80
15,000
5,000
87/103
85/101
44/55
44/55
42/53
430412375
430527375
300378295
300493295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
107/139
102/145
65/85
61/81
60/80
4000
5000
6300
1,000
690
12
50/60
3/4
150
150
100
100%
330
330
220
100
85
75
40
80
10,000
2,000
181/223
186/230
179/221
184/228
97/117
102/124
98/123
103/130
96/121
101/128
460785375
4601015375
300751295
300981295
N, A, P, S type
KS / KEMA / KERI / GOST / CCC
LR, ABS, DNV, KR, BV, GL, RINA, NK
Derating of the rated current is required according to the ambient temperature around the breaker in a panel
if it is higher than the reference value. (See pages 109 to 112)
23
Ratings
Type
Ampere frame
(AF)
Rated current(A)
(In max)
at 40
** : Standard, : Option
24
63/74
70/85
61/72
68/83
29/32
33/40
34/44
38/47
32/42
36/45
430334375
430419375
300300295
300385295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
AS-20E
2000
630, 800
1000, 1250
1600, 2000
AS-25E
2500
AS-32E
3200
AS-40E
4000
AS-40F
4000
AS-50F
5000
AS-40G
4000
AS-50G
5000
AS-63G
6300
2500
3200
4000
4000
5000
4000
5000
6300
2500
3200
1,000
690
12
50/60
3/4
85
85
85
100%
187
187
187
85
75
65
40
80
15,000
5,000
87/103
104/147
85/101
102/145
44/50
58/70
44/55
63/100
42/53
61/98
430412375
430527375
300378295
300493295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
4000
5000
1000
690
12
50/60
3/4
100
100
85
100%
220
220
187
85
75
65
40
80
10,000
2,000
107/139
102/145
65/85
61/81
60/80
460629375
460799375
300597295
300767295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
5000
6300
1,000
690
12
50/60
3/4
120
120
100
100%
264
264
220
100
85
75
40
80
10,000
2,000
181/223
186/230
179/221
184/228
97/117
102/124
98/123
103/130
96/121
101/128
460785375
4601015375
300751295
300981295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
25
Trip relay(OCR)
The trip relay of Susol ACB provides the additional protection functions for
voltage, frequency, unbalance, and others in addition to main protection
functions for over current, short-circuit, ground fault. It supports the
advanced measurement functions for voltage, current, power, electric energy,
harmonics, communication function, and others.
Analog trip function interlocked with mechanism enhanced a durability of
devices as well as the breaking capacity of ACB.
Zone selective interlocking function makes the protective coordination more
simple and thermal memory can be applied to various loads.
Contents
Trip relay types
27
type
N type:Normal
28
type
A type:Ammeter
30
type
P type:Power meter
32
type
S type:Supreme meter
34
Operation characteristic
36
Measurement function
38
39
40
41
Characteristic curves
42
45
46
Communication
47
48
System information
48
49
Trip relays
Trip relay types
Classification
N type
A type
P type
S type
L / S / I / G / Thermal(Continuous)
ZSI(Protective coordination)
Earth leakage(Option)
Over/Under current
Over/Under frequency
Unbalance(Voltage/Current)
Reverse power
3 Phase Voltage/Current
RMS/Vector
Power(P, Q, S), PF(3-Phase)
Energy(Positive/Negative)
Frequency, Demand
L / S / I / G / Thermal(Continuous)
ZSI(Protective coordination)
Earth leakage(Option)
Over/Under current
Over/Under frequency
Unbalance(Voltage/Current)
Reverse power
3 Phase Voltage/Current
RMS/Vector
Power(P, Q, S), PF(3-Phase)
Energy(Positive/Negative)
Frequency, Demand
Voltage/Current harmonics
(1st~63th)
3 Phase Waveforms
THD, TDD, K-Factor
Fine adjustment for long/short
time delay/instantaneous/ ground
Overload protection relays
: DO (Alarm)
(Ground fault is not available
when using Pre trip alarm)
3DO (Programmable)
Trip, Alarm, General
Compliance with IEC60255-3
SIT, VIT, EIT, DT
Modbus / RS-485
Profibus-DP
AC/DC 100~250V
DC 24~60V
Externals
Current
protection
Other
protection
L / S / I / G / Thermal
L / S / I / G / Thermal
ZSI(Protective coordination)
Earth leakage (Option)
Current (R / S / T / N)
Pre Trip Alarm
Measurement
function
Fine adjustment
Digital Output
3DO (Fixed)
L, S/I, G Alarm
IDMTL setting
Modbus/RS-485
Profibus-DP
Self Power
Self Power
- Power source works
- Power source works
over 20% of load current.
over 20% of load current.
Power supply
- External power source are
required for comm.
AC/DC 100~250V
DC 24~60V
RTC timer
Available
Long time delay
Long time delay
LED for
Short time delay/Instantaneous Short time delay/Instantaneous
trip info.
Ground fault
Ground fault
10 records
Fault recording
(Fault/Current/Date and Time)
Communication
Event recording
Operating
Reset button
button
Each OCR type has Battery in itself.
1. Battery lifespan
1) When turned off : 14~28years
2) When using 1 LED consecutively or turned off : 7~14days
Reset, Menu
Up/Down, Left/Right, Enter
Available
Long time delay
Short time delay/Instantaneous
Ground fault
256 records
Last fault wave form
recording (3 Phase)
256 records(Content, Status, Date) 256 records(Content, Status, Date)
Reset, Menu
Reset, Menu
Up/Down, Left/Right, Enter
Up/Down, Left/Right, Enter
27
Trip relays
type
N type:Normal
Optimized protection function
OCR, OCGR function according IEC60947-2
Overload protection
-Long-time delay
-Thermal
Short-circuit protection
-Short-time delay / Instantaneous
-I2t On/Off optional (for short-time delay)
Ground fault protection
-I2t On/Off optional
Self-Power
Alarm SP
Ir
Isd
Ii
Ig
Ig: Ground fault current setting, tg: Ground fault tripping delay setting
Test terminal: OCR test terminal (Connected with OCR tester)
28
Protection
Long time
Ir
tr
lsd
tsd
Ii
I
Iu = In...
0.5
0.6
Ir = Iu...
0.8
1.0
tr@(1.5lr)
12.5 25
50
100
200
300
400
500
Off
tr@(6.0lr)
0.5
12
16
20
Off
100ms
tr@(7.2lr)
5.5
8.3
11
13.8
Off
Isd = Ir...
1.5
10
Off
0.7
0.8
0.9
1.0
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
tsd
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
10
12
15
Off
0.4
0.5
0.6
0.7
0.8
1.0
Off
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
Instantaneous
Current setting (A)
Ii = In...
Tripping time
below 50ms
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
Ig = In...
0.2
0.3
20%(Ig0.4In)
Ig
tg
tg
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
29
Trip relays
type
A type:Ammeter
Fault recording
-Records Max. up to 10 fault information about fault type,
fault phase, fault data, occurrence time of fault
SBO (Select Before Operation)
-High reliability for control and setting change method
3 DO(Digital Output)
-Fixed
Communication
-Modbus/RS485
-Profibus-DP
Overload protection
-Long-time delay
-Thermal
Short-circuit protection
-Short-time delay / Instantaneous
-I2t On/Off optional (for short-time delay)
Ground fault protection
-I2t On/Off optional
Realization of protective coordination by ZSI
(Zone Selective Interlocking)
High-performance and high-speed MCU built-in
-Accurate measurement with tolerance of 1.0%
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
Isd: Short-time current setting, tsd: Short-time tripping delay setting
Ii: Instantaneous current setting
Ig: Ground fault current setting, tg: Ground fault tripping delay setting
Test terminal: OCR test terminal (Connected with OCR tester)
30
Protection
Long time
Ir
tr
lsd
tsd
Ii
I
Iu = In...
0.5
0.6
Ir = Iu...
0.8
1.0
tr@(1.5lr)
12.5 25
50
100
200
300
400
500
Off
tr@(6.0lr)
0.5
12
16
20
Off
100ms
tr@(7.2lr)
5.5
8.3
11
13.8
Off
Isd = Ir...
1.5
10
Off
0.7
0.8
0.9
1.0
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
tsd
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
10
12
15
Off
0.4
0.5
0.6
0.7
0.8
1.0
Off
10
20
30
Off
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
Instantaneous
Current setting (A)
Ii = In...
Tripping time
below 50ms
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
Ig = In...
0.2
0.3
20%(Ig0.4In)
Ig
tg
tg
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
0.5
140
230
350
800
950
140
230
350
800
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
In
Alarm
Accuracy: 15%
Time(ms)
Trip
Time(ms)
31
Trip relays
type
P type:Power meter
Overload protection
-Long-time delay
-Thermal
Short-circuit protection
-Short-time delay / Instantaneous
-I2t On/Off optional (for short-time delay)
Ground fault protection
-I2t On/Off optional
Protection for Over voltage/Under voltage/Over
frequency/Under frequency/Unbalance/Reverse power
Realization of protective coordination by ZSI
(Zone Selective Interlocking)
The fine-adjustable setting by knob and Key
IDMTL setting (SIT, VIT, EIT, DT curve)
- Basic setting : None. Thermal curve.
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
32
Protection
t
Ir
tr
lsd
tsd
Ii
I
Long time
Current setting (A)
Time delay (s)
Accuracy: 15% or below
100ms
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
Ir = In...
tr@(1.5lr)
tr@(6.0lr)
tr@(7.2lr)
0.4
12.5
0.5
0.34
0.5
25
1
0.69
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
8
5.5
0.9
300
12
8.3
1.0
400
16
11
500
20
13.8
Off
Off
Off
Isd = Ir...
1.5
10
Off
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
20%(Ig0.4In)
Ig
Ii = In...
2
3
4
below 50ms
10
12
15
Off
Ig = In...
0.2
0.7
0.8
1.0
Off
10
20
30
Off
tg
tg
I n
I2t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
(I2t Off)
In
0.3
0.4
0.5
0.6
0.05 0.1
I2t Off
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
230
350
800
950
230
350
800
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
Ip = Ir x
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
tp@(1.2Ip)
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
5%
5%
2.5% or (*10%)
10%
10%
2.5% or (*10%)
0.1Hz
0.1Hz
0.1Hz
0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
0.1sec
1.2~40sec
33
Trip relays
type
S type:Supreme meter
Overload protection
-Long-time delay
-Thermal
Short-circuit protection
-Short-time delay / Instantaneous
-I2t On/Off optional (for short-time delay)
Ground fault protection
-I2t On/Off optional
Protection for Over voltage/Under voltage/Over
frequency/Under frequency/Unbalance/Reverse power
Realization of protective coordination by ZSI
(Zone Selective Interlocking)
The fine-adjustable setting by knob and Key
IDMTL setting (SIT, VIT, EIT, DT curve)
- Basic setting : None. Thermal curve.
Measurement and Display Function
-High detailed measurement for 3 phase
current/Voltage/Power/Energy/
Phase angle/Frequency/PF/Demand
-128 x 128 Graphic LCD
-Indicates current/voltage Vector Diagram and
Waveform
Fault recording
-Records Max. up to 256 fault information about fault
type, fault phase, fault value, occurrence time of fault
-Fault wave recording: records the latest fault wave
Event recording
-Records events of device related to setting change,
operation and state change. (Max. up to 256)
SBO (Select Before Operation)
-High reliability for control and setting change method
Power quality analysis
-Measurement for 1st~63th harmonics
-THD, TDD, k-Factor
-Voltage/current waveform capture
3 DO(Digital output)
-Programmable for alarm, trip and general DO
Communication
-Modbus/RS485
-Profibus-DP
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
34
Protection
t
Ir
tr
lsd
tsd
Ii
I
Long time
Current setting (A)
Time delay (s)
Accuracy: 15% or below
100ms
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
Iu = In...
tr@(1.5lr)
tr@(6.0lr)
tr@(7.2lr)
0.4
12.5
0.5
0.34
0.5
25
1
0.69
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
6
5.5
0.9
300
12
8.3
1.0
400
16
11
500
20
13.8
Off
Off
Off
Isd = Ir...
1.5
10
Off
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
20%(Ig0.4In)
Ig
Ii = In...
2
3
4
below 50ms
10
12
15
Off
Ig = In...
0.2
0.7
0.8
1.0
Off
10
20
30
Off
tg
tg
I n
I2t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
(I2t Off)
In
0.3
0.4
0.5
0.6
I2t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
230
350
800
950
230
350
800
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
Ip = Ir x
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
tp@(1.2Ip)
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
5%
5%
2.5% or (*10%)
10%
10%
2.5% or (*10%)
0.1Hz
0.1Hz
0.1Hz
0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
0.1sec
1.2~40sec
35
Trip relays
Operation characteristics
Long-time delay (L)
Iu
N, A type
.8
Ir
.9
.7
.88
.9
tr
.6
.83
.5
Iong time
.8
In
.93
.85
.95
.98
P, S type
.7
.8
20
.5
.9
(S)
12
.5
16
20
1
.4
Ir
Iong time
.5
In
off
@6 Ir
tr
off
@6 Ir
tr
.6
Iu
Ir
tsd
6
3
2
1.5
(S)
.3
10
.2
.4
.4
off
.1
short time
.05
on 2 off
Ir
I t
Isd
tsd
Instantaneous (I)
The function for breaking fault current above the setting value within
Ii
12
15
2
off
instantaneous
In
Ii
36
.5
.6
tg
.7
.4
(S)
.4
.3
.4
.8
.3
.2
.3
.2
.1
.2
off
.1
ground fault
.05
on 2 off
In
I t
Ig
tg
(ms)
10
800
950
20
350
350
30
230
230
0.5
time delay to protect the circuit from earth leakage. (A, P, S type)
800
140
off
140
earth leakage trip alarm
I n
R S T N
ZCT or External
CT
- When using a standard ZCT provided by LS, the setting range is from 0.5 to 30A which is
based on its primary current. But ACB installed like A type (displayed on the left side)
should only be cable-connected and its rated current should be less than 1600A.
- When using other CT selected by customers, the setting range is from 0.5 to 5A based on
its secondary current.(Secondary output rating : 5A)
Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will
activate its operation (0.5A20 = 10A)
ZCT or External
CT
37
Trip relays
A type
Measurement function
Class.
Measurement
element
Line current
Ia,Ib,Ic
Current
Normal current
I1
Voltage
Angle
P type
Power
Reverse current
I2
Vab,Vbc,Vca
Phase voltage
Va,Vb,Vc
Normal voltage
V1
Freq.
Unbalance
S type
80A~65,535A
1%
60~690V
0~360
V2
Line-to-current
VabVbc, VabVca
Phase-to-phase
VaVb,VaVc
Phase-to-current
Active power
kW
1kW~99,999kW
3%
Reactive power
kVar
1kVar~99,999kVar
3%
Apparent power
kVA
1kVA~99,999kVA
3%
WHa(ab), WHb(bc),
kWh
WHc(ca), WH
MWh
1kWh~9999.99MWh
3%
1kVarh~9999.99MVarh
3%
1kWh ~9999.99MWh
3%
VARHa(ab), VARHb(bc),
kVarh
VARHc(ca), VARH
Mvarh
Reverse active
rWHa(ab), rWHb(bc),
kWh
energy
rWHc(ca), rWH
MWh
Frequency
Power factor(PF)
Unbalance rate
Iunbalance, Vunbalance
0.0~100.0
Peak demand
kW
1kW~99999kW
Current demand
Peak demand
80A~65,535A
Voltage
1st~63th harmonics of
harmonics
Va(ab),Vb(bc),Vc(ca)
60~690V
Current harmonics
Hz
45~65Hz
+: Lead, -: Lag
80A~65,535A
THD, TDD
0.0~100.0
K-Factor
0.0~100.0
Vr Vs Vt Vn
Vr Vs Vt
Voltage
module
3P4W wiring
38
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
1
2
3
4
5
6
7
8
9
10
11
12
1
1
Voltage module
1
2
3
4
5
6
7
8
9
10
11
12
1%
demand
Harmonics
Accuracy
Line-to-line
Active power
Demand
Display range
Reverse voltage
Reactive energy
Power factor
Unit
3%
Line voltage
Active energy
Energy
Detailed element
Voltage
module
3P3W wiring
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
Measurement display
Initial display
1000 A
Setting display
100%
50%
Initial display
1. H/W set
2. Relay set
1. Wiring
1. OCR
1. Event
2. Comm
2. OCGR
2. Clear All
3. Password
3. OVR/UVR
3. Fault
4. Time-RTC
4. Unbal
4. Clear All
5. RT Ratio
3. Events
5. L/R (L)
4. Sys info
5. rP/OPR
6. Demand
6. OFR/UFR
7. Data Rst
Max Power
Demand
Energy
CB Count
Run Time
8. DO Setup
9. Language
1000 A
1000 A
R
Ir
.7
.8
Ir =
.9
.6
100%
50%
.5
100%
.4
1000 A
In
50%
Ir adjustment
knob
Displayed screen when changing
Ir value into 1.0
(After 3 sec, return to initial display)
Initial display
tg
(S)
.4
.4
Tg =
.3
.3
.2
.1
.2
.1
.05
on 2 off
I t
200 ms
I2t [Off]
tg adjustment
knob
Displayed screen when changing
tg value into 0.2
(After 3sec, return to initial display)
39
Trip relays
Protection element setting
Initial display
1000 A
R
Setting display
100%
50%
PASSWORD
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
XXXX
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
Password input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
OCRL, S, I
I2T
[Off]
800 A
EIT .Os
6400 A
15000 A
OCRL, S, I
I2T
[Off]
OCRL, S, I
800 A
EIT
6400 A
I2T
[Off]
800 A
EIT
6400 A
15000 A
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
15000 A
Pick Up
Delay
Action
Pick Up
Delay
Action
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
OVR/UVR Set
: 724 V
: 1.2 s
: None
: 150 V
: 1.2 s
: D01
OVR/UVR setting
rPower
Pick Up
Delay
Action
Pick Up
Delay
Action
I2T
[Off]
800 A
EIT
6401 A
15000 A
1.OCR
2.OCGR
3.OVR/UVR
4.Unbal
5.rP/OPR
6.OFR/UFR
Unbal V/I
Pick Up
Delay
Action
Pick Up
Delay
Action
:100 kW
: 10.0 s
: D02
: 2400 kW
: 0.2 s
: TRIP
40
OCRL, S, I
: 6%
: 10.0 s
: D02
: 12 %
: 10.0 s
: D03
Unbalance setting
OFR/UFR Set
Pick Up
Delay
Action
Pick Up
Delay
Action
: 65 Hz
: 10.0 s
: D01
: 55 Hz
: 10.0 s
: None
Frequency setting
1000 A
R
100%
50%
Measurement
overview
Metering Overview
VR 220
V0.0
R :
1000
IR
1000
A330.0
S :
1000
2007/05/14
986
kW
T :
1000
10:00:00
589
kVar
PF 0.866 F 60.0
EP 56
kWh
2007/05/14
EQ 32
kVarh
11:15:00
Voltage/Current
vector diagram
Vector Diagram
Vt
It
Vr
Is
Ir
Vs
VOLTGAE [V]
VR :
220 0.0
VS :
220240.0
VT :
220120.0
V unbal 3Ph
Vpos : 220
Vneg :
Unbal :
0.0
CURRENT [A]
IR :
1000330.0
IS :
1000210.0
IT :
1000 90.0
IN :
0
I unbal 3Ph
Apparent [kVA]
R :
328
Total
R :
379
Total
S :
328
986
S :
379
1139
T :
379
Ipos : 1000
Ineg :
Unbal :
0.0
Power and
power factor
Power Diagram
P=986
Q=589
T :
328
Reactive [kVar]
kW
1000
kVar 2000
Power Factor
R :
189
Total
R :
0.87
Total
S :
189
589
S :
0.87
0.866
T :
189
T :
0.87
Energy
Forward Energy
Forward P [kWh]
Reverse P [kWh]
P+
R :
360
Total
R :
Total
S :
360
1080
S :
Q+
1051 kWh
607 kVarh
T :
T :
Reverse Energy
360
Forward Q [kVarh]
0
Reverse Q [kVarh]
P-
0 kWh
R :
210
Total
R :
Total
Q-
S :
210
630
S :
0 kVarh
T :
210
T :
Voltage/Current
harmonics
(S type)
I
R
S
H1
220 H8
H15
0 H22
H57
H2
0 H9
H16
0 H23
H58
H3
55 H10
H17
55 H24
H59
H4
0 H11
H18
0 H25
H60
H5
0 H12
H19
0 H26
H61
H6
0 H13
H20
0 H27
H62
H7
0 H14
H21
0 H28
H63
TDD 3Phase
H1 1000 H8
H15
1 H22
H57
R :
0.1 %
H2
0 H9
H16
0 H23
H58
S :
0.1 %
H3
15 H10
H17
1 H24
H59
T :
0.1 %
H4
0 H11
H18
0 H25
H60
Current K - Factor
H5
20 H12
H19
1 H26
H61
R :
1.2
H6
0 H13
H20
0 H27
H62
S :
1.2
H7
0 H14
H21
1 H28
H63
T :
1.3
41
Trip relays
Characteristics curves
5000
2000
Ir = 0.4...1 In
1000
500
200
100
50
40
30
tr = 0.5...20s
20
20
12
10
t(s)
5
4
3
4
2
1
1
0.5
0.4
0.3
0.2
0.1
0.05
Ir
42
20
10
0.7
0.01
0.5
0.02
5000
2000
1000
500
Isd = 1.5...10 Ir
200
100
50
40
30
20
10
t(s)
5
4
3
2
1
0.4
0.3
0.4
0.2
0.2
I2t ON
0.4
0.3
0.3
0.2
I2t OFF
0.1
0.1
0.1
0.05
0.05
20
10
0.01
0.7
0.02
0.5
Ir
43
Trip relays
Characteristics curves
Instantaneous (I)
Ground fault (G)
100
50
40
30
20
Ig = 0.2...1 In
10
5
4
3
2
t(s)
1
I2t ON
0.4
0.4
0.3
0.3
0.2
0.2
0.2
0.1
I2t OFF
0.1
0.1
0.4
0.3
0.05
0.05
Ii = 2...15 In
44
In
10
4
5
0.7
0.4
0.5
0.3
0.2
0.1
0.07
0.01
0.05
0.02
10000
5000
2000
EIT
1000
500
VIT
200
100
SIT
t(s)
50
20
DT
10
20
10
0.05
0.7
0.5
IDMTL
Ir
45
Trip relays
Characteristics curves
500
200
100
50
40
35
30
20
15
10
5
5
4
3
t(s)
2
1
1
0.4
0.3
0.2
0.1
0.05
Ip
46
30
20
10
0.7
0.01
0.5
0.02
Zone-selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machineries get under
fault conditions.
1. In case of that short time-delay or ground fault accident occurs at ZSI built in system,
the breaker at accident site sends ZSI signal to halt upstream breakers operation.
2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation
without time delay.
3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or
ground fault time-delay for protective coordination in the system.
However upstream breaker that did not receive its signal will trip instantaneously.
4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream
circuit breakers will react before upstream ones under overcurrent/short time delay/
ground fault situations.
5. ZSI connecting line needs to be Max. 3m.
Z4
Z3
Z2
Z1
ZSI input
Fault A
Z4
Z3
Z2
Z1
ZSI output
ZSI input
Fault B
Z4
Z4
Z4
Z3
Z3
Z3
Z2
Z2
Z2
Z1
Z1
Z1
1) Occurrence of fault A
- Only breaker performs instantaneous trip operation.
2) Occurrence of fault B
- Breaker performs instantaneous trip operation,
breaker performs trip operation after prearranged delay time
- But if breaker did not break the fault normally,
breaker performs instantaneous trip operation to protect system.
47
Trip relays
Remote reset and digital I/O (A, P, S type)
V2
V3
Vn
E1
Z3
Z1
Common
Reset
ZCT
V1
ZSI input
Voltage module
ZSI output
485+
R11
R22
513
544
534
524
Power supply
R2
R1
485-
Trip
Relay
48
Digital
Output
LTD
Z2
GTD
Z4
S/I
Trip relay
Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR
Alarm
time time
DO1(524)
P, S DO2(534)
type
DO3(544)
DO1(524)
A type DO2(534)
DO3(544)
Not available
Note
Programmable
Fixed
Communication
Modbus/RS-485
Operation mode: Differential
Distance: Max. 1.2km
Cable :
General RS-485 shielded twist
2-pair cable
Baud rate :
9600bps, 19200bps, 38400bps
Transmission method: Half-Duplex
Termination: 100
SCADA system
Modbus/RS-485
Profibus-DP
Profibus-DP module is installed
separately (Option)
Operation mode: Differential
Distance: Max. 1.2km
Cable :
Profibus-DP shielded twist 2-pair cable
Baud rate: 9600bps~12Mbps
Transmission method: Half-Duplex
Termination: 100
Standard: EN 50170 / DIN 19245
Ethernet/TCP/IP
Area
controller
TCP/IP/Ethernet
TCP/IP
CNC
Profibus-FMS
PC
DCS
PLC
Profibus-DP
Profibus-DP
communication module
(Option)
Profibus-DP
communication
module (Option)
PLC
Modbus/RS-485
49
Trip relays
Event & fault recording (P, S type)
When there are events such as setting change, Info. change, error of self-diagnose,
state change, P and S type record Max. up to 256 information of the events in accordance with
time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults
such as fault cause, fault phase, fault value and so on in accordance with time(ms).
Setting display
1000 A
R
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. EventL
2007/05/15
20:29:41
Sta Change
10. EventL
2007/04/15
10:11:24
Cfg Change
Power On
Comm Set up
Setting display
1000 A
R
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. Trip
2007/04/26
08:35:52
OCR-Short
9. Trip
2007/04/11
09:11:32
UVR
Phase T
Phase R
930A
System information
P and S type can indicate information as followings with the information of the ACB.
- Present time: year/month/date/hour/minute/ms
- ACB current ratings
- N-phase current ratings: 100%
- Frequency information: 60Hz / 50Hz
- Closing numbers of breaker: CB ON numbers
- Trip relay operating time: OCR ON time
- ON time of breaker: CB ON time
- F/W ver. information
Setting display
1000 A
R
100%
50%
50
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
Password
input
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
Freq
60 Hz
CB ON# 23
Ver-Arm 1.5
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
T-OPER 220 h
T-CB ON 180 h
Ver-Msp 4.01A
OV
N
ACB TRIP
ACB
Vcc
+5V
CPU
Output
Display
(LED,LCD)
Vcc/+5V/-5V
CN2-1
CN2-9
CN2-3
CN2-11
CN2-5
CN2-13
SIGNAL
CT
CN2-7
CN2-15
CN2-14
Filter
Amp.
Main PCB
Assy
Main PCB
Assy
Main PCB
Assy
+24V
CN2-10
Output
MTD
CN2-12
Setting
Part
GND 24V
CN2-4
Self power
Vcc
RY0 (K1)
CN4-2
LTD contact
+24V
POWER
CT
GND 24V
Main PCB
Assy
RY1 (K2)
CN4-4
STD/INST contact
+5 V
RY2 (K3)
-5 V
CN4-6
GTD contact
CN2-2
CN4-10
Power PCB
Assy
CN3-9
Voltage
input
(VDM)
Power PCB
Assy
SMPS
Trip relay
CN4-9
External Source
AC/DC 110~220V
DC 24~48V
CN3-10
CN3-11
CN3-1
ZSI output+
CN3-2
ZSI outputCN3-3
ZSI input+
CN3-4
ZSI input-
CN3-12
CN3-5
Remote reset+
CN3-6
Remote reset-
CN3-7
CN3-8
ZCT
(Earth leakage)
Tester input (R)
Tester input (S)
Tester input (T)
Tester input (N)
DC 24V
UTX0
URX0
GND 24V
AD GND
CN1-2
CN1-4
CN1-6
CN1-8
CN1-5
CN1-1
CN1-3
CN1-7/9
CN1-10
CN4-8
Common contact
CN3-7
Earth leakage+
CN3-8
Earth leakage-
Test
Port
Main PCB
Assy
Comm.
Power PCB
Assy
CN4-1
485+
CN4-3
485-
51
Accessories
Mounting
Accessories
SHT1 Shunt Coil
AH
54
55
56
Motor
57
Charge Switch
57
CS2
57
UVT
58
59
59
AL
RES
60
60
67
AX
Auxiliary Switch
61
TM
Temperature Alarm
78
K1
Key Lock
62
K2
62
K3
63
63
Lifting Hook
64
64
65
67
LH
CTD
ATS
DC
Counter
Automatic Transfer
Switch Controller
Dust Cover
DF
Door Frame
71
OT
OCR Tester
66
Manual Connector
Automatic Connector
* Seperate purchasing is not allowed. Each item should be purchased with the main body.
52
Closing Coil
External
Remark Page
CS1
Internal
AN
AS
Mounting
Accessories
N
Trip relay
AN
N type
Remark Page
*
28
A type
30
P type
32
S type
34
Voltage Module
**
38
SBC
73
MI
Mechanical Interlock
ST
Safety Shutter
STL
70
MIP
76
68
CEL
72
DI
ZAS
SC
BSP
Other
AS
VM
Cradle
AH
Cell Switch
Door Interlock
Zero Arc Space
Body Supporter
RI
Racking Interlock
PL
IB
Insulation Barrier
ADP
VAD
70
69
*
73
***
74
74
75
71
69
*
75
77
13
79
49
* Seperate purchasing is not allowed. Each item should be purchased with the main body.
** Voltage module should be purchased with P/S type trip relay.
*** It is available only when the control block is in the mode of auto-connection.
53
Accessories
Shunt Coil [SHT1]
Shunt coil 1
SHT1
C2
*
The dotted
to
Userline
be made by the
Wiring Diagram
customer
Wiring Diagram
DC [V]
AC [V]
24~30
0.7~1.1 Vn
48~60
48
0.7~1.1 Vn
100~130
100~130
0.7~1.1 Vn
200~250
200~250
0.7~1.1 Vn
380~480
0.7~1.1 Vn
Inrush
Steady-state
200
Less
than
40ms
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type
Operating
voltage
54
DC/AC 48 [V]
#14 AWG
Shunt coil 1
Shunt coil 2
SHT2
DC [V]
AC [V]
24~30
0.7~1.1 Vn
48~60
48
0.7~1.1 Vn
100~130
100~130
0.7~1.1 Vn
200~250
200~250
0.7~1.1 Vn
380~480
0.7~1.1 Vn
Inrush
Steady-state
200
Less
than
40ms
C12
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
Wiring Diagram
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type
Operating
voltage
DC/AC 48 [V]
#14 AWG
55
Accessories
Closing Coil [CC]
Closing coil
A1
CC
A2
Wiring Diagram
DC [V]
AC [V]
24~30
0.85~1.1 Vn
48~60
48
0.85~1.1 Vn
100~130
100~130
0.85~1.1 Vn
200~250
200~250
0.85~1.1 Vn
380~480
0.85~1.1 Vn
Inrush
Steady-state
200
Shunt time
[ms]
Less
than
80ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
Wire type
Operating
voltage
56
DC/AC 48 [V]
#14 AWG
Motor [M]
Motor
Gear
Main
axis
Input voltage(V)
Load current(max.)
3A
1A
0.5A
Starting current(Max.)
Load rpm(Motor)
Charge time
Dielectric strength
Using temperature range
Using humidity range
Endurance
Charge switch
AC 380V
AC 440~480V
0.3A
0.3A
It is a built-in contact which sends the signal to the outside, when motor charging is
completed. (2a)
It has a 1a contact for communication and the other 1a contact for complete charging.
When using an extra communication module (Remote I/O), the state of contacts
can be displayed through the network.
10A at 250VAC
57
Accessories
Under Voltage Trip device [UVT]
UVT coil
Shunt coil
Closing
coil
AC [V]
24~30
48~60
48
100~130
100~130
200~250
200~250
380~480
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.4~0.6 Vn
200
Less
than
50ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
#14 AWG
#16 AWG
(2.08mm2)
(1.31mm2)
(2.08mm2)
(1.31mm2)
100%
48.5m
30.5m
233.2m
143.9m
85%
13.4m
8.8m
62.5m
39.3m
Wire type
Operating
voltage
Note) In case of using UVT coil, the location of Shunt coil is changed.
58
DC/AC 48 [V]
#14 AWG
AL1, 1a
AL2, 1a
When a circuit breaker is tripped by OCR which operates against the fault current
(Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit
breaker by sending the electrical signal from the mechanical indicator on front cover of main
circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker)
When a circuit breaker tripped by fault current, a mechanical trip indicator
(MRB, Manual Reset Button) pops out from the front cover and the switch (AL) which sends
control signal electrically is conducted to output the information occurred from fault circuit
breaker.
MRB and AL can be operated only when tripping by OCR,
but doesnt be operated by Off button and OFF operation of trip coil.
To re-close a circuit breaker after a trip, press MRB to reset it for closing.
2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option)
Trip alarm contact and MRB(Manual reset bottom) need to be purchased together.
1. Electrical characteristics of trip alarm contact
Rated voltage [V]
lamp load
Inductive load(A)
Motor load
8V DC
11
30V DC
10
125V DC
0.6
0.1
0.6
0.1
250V DC
0.3
0.05
0.3
0.05
250V AC
11
1.5
Inrush current
MAX. 24A
59
Accessories
Remote Reset Switch [RES]
Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical
indicator(MRB) and enables circuit breaker closing.
Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load
In case of auto reset type circuit breaker
Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is
no longer required to enable circuit breaker closing.
The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset
button is pressed.
AL2 and RES are alternative.
1. Rated voltage and rated current of RES
Rated voltage
Reset
order
183
RES
AC/DC 100~130V
AC/DC 200~250V
Operating current(Max.)
AC
6A
DC
5A
AC
3A
DC
2.5A
Operating time
Wire spec.
#14 AWG (2.08 mm2)
Less 40ms
#16 AWG (1.31 mm2)
Connect to inner
micro switch
184
Connect to
AL2 / RES
Wiring Diagram
Standard
Remark
250/125 Vac 10 A
A contact
Contactor
Capacity
Contact part
60
250 Vdc
0.3 A
125 Vdc
0.6 A
48 Vdc
3A
24 Vdc
5A
Standard
AX
AC
BX
BC
HX
HC
CC
JC
TX
TC
High capacity
Standard classification
Standard
2000, 5000AF
Contact
capacity
DC
2000, 5000AF
Standard
Classification
AC
High capacity
4000, 6300AF
4000, 6300AF
High capacity
Resistive load
Inductive load
Resistive load
Inductive load
490V
5A
250V
10A
6A
5A
2.5A
6A
10A
125V
10A
10A
6A
10A
10A
250V
0.3A
0.3A
3A
1.5A
125V
0.5A
0.6A
10A
6A
30V
10A
6A
10A
10A
AX
3a3b
BX
5a5b
HX
5a5b
No. of Contact
AC
3a3b
BC
5a5b
CC
6a6b
HC
5a5b
JC
6a6b
Remark
Standard
charging
type
Rapid autoreclosing
charging type
61
Accessories
Key Lock [K1]
K1
ACB1
ACB2
ACB-2
ACB-3
LOAD1
LOAD2
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
: Release : Lock
ACB3
Load 1
62
Load 2
Status
ACB-1
63
Accessories
Lifting Hook [LH]
It is a device to
make an ACB easy to shift.
Please hang it to both handles
of the arc cover.
External dimension
131
118
Specification
Ratings
Model
CTD-100
CTD-200
AC 100/110
AC 200/220
)
Frequency (
50/60
50/60
140/155
280/310
Charging time
Within 5S
Within 5S
Over 3 min
Over 2 min
85~110
85~111
Condenser capacity
400
160
Circuit diagram
7.5
15
AC input
108
75
75
Side view
Rear view
64
Front view
DC output
Ratings
ATSC-110
ATSC-220
Rated voltage
Model type
AC 110V
AC 220V
Voltage range
AC 93.5(5%) ~126.5V(5%)
Frequency
AC 187(5%) ~ 253V(5%)
50Hz/60Hz
15.4W
Test function
T1: The delayed time from when UN (power supply of electric company) is tripped to when
generator start-up signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs)
T2: The delayed time from when UN is closed to when ACB2 is tripped.
(t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs)
T3: The delayed time from when ACB1 is tripped to when ACB2 is closed.
(t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
T4: The delayed time from when ACB2 is tripped to when ACB1 is closed.
(t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs)
T5: The delayed time when ACB1 is closed to when generator start-up signal contact is
opened. (t5: 60, 120, 180, 240, 300, 360, 420, 480, 540, 600secs)
Stop-mode: This mode is for compulsory trip of ACB1(electric power company) or
ACB2 (power station) when UN (power supply of electric power company) or UR (power supply
of power station) is available
*UN or UR should be kept in ON position
N-mode: This mode is for compulsory closing of ACB1 when UN is available.
* it does not matter to be ON or OFF position of UR and if converting to N-mode while using UR,
generator start-up signal contact is opened.
R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that
UN is available or not.
Auto-mode: This mode is for transferring a circuit breaker automatically to available power
supply of UN or UR. In short, it trips the circuit breaker where power supply is not available and it
close the circuit breaker where power supply is available.
65
Accessories
OCR Tester [OT]
OCR tester
Configuration
R
ENT.
ESC
START
STOP
Signal setting/Delete
Waveform generation/Stop
50Hz 60Hz
Hz
66
Select frequency
Panel
door
Dust cover
Door frame
Counter [C]
Counter
67
Accessories
Mechanical Operated Cell Switch [MOC]
a1 a2
a3
a4 a5
b1 b2
b3 b4
b5
a1 a2
a3
a4 a5
b1 b2
b3 b4
b5
13 23
33
43 53
11 21
31 41 51
13 23
33
43 53
11 21
31 41 51
14 24
34
44 54
12 22
32 42 52
14 24
34
44 54
12 22
32 42 52
AUX S/W
AUX S/W
68
It is used to interlock closing and trip between two or three breakers mechanically
so as to prevent unintended operation at the same time.
Wire type interlock can be applied upto 3 breakers
69
Accessories
Safety Shutter [ST]
4000/6300AF, 3P
2000/5000AF, 4P
4000/6300AF, 4P
Shutter plate
Guide shutter
Shutter lock
70
Key lock
Fixed type
Door frame
Panel door
Draw-out type
Fixed type
Draw-out type
Insulation barrier prevents the arc which may arise and result in short-circuit
between phases in advance
As C stands for CRADLE, install the insulation barrier in the direction of
C in case of Draw-out type.
As A stands for ACB main frame, install the insulation barrier in the direction
of A in case of Fixed type.
71
Accessories
Cell Switch [CEL]
Cell switch
ACB position
DISCONNECTED
CONNECTED
DISCONNECTED
TEST
CONNECTED
ON
CL-C
OFF
(Connected)
Contact
CL-T
operation
(Test)
ON
OFF
ON
CL-D
OFF
(Disconnected)
Voltage(V)
Resistive load
Inductive load
2.5
10
10
460V
AC
Contact
250V
125V
capacity
DC
250V
1.5
125V
10
10
30V
10
10
Contact number
4C
comm.
371
(341)
CL4
382
CL3
384
comm.
361
(331)
372
CL2
374
comm.
351
(321)
362
(311)
CL1
364
352
CL4
354
(342)
(344)
(332)
(334)
(322)
(324)
(312)
(314)
72
comm.
341
342
b
comm.
331
CL3
344
a
332
b
comm.
321
CL2
334
a
322
b
comm.
311
CL1
324
a
312
b
314
a
Shorting b
contact
contact)
Contact condition (Link between Axb and shortingb
ACB position
ACB condition
Connected position
(Shorting b contact : OFF)
Close position
[Auxiliary contact(Axb):OFF]
OFF
Open position
[Auxiliary contact(Axb):ON]
ON
OFF
ON
Test position
(Shorting b contact : ON)
2000AF 3P
281.4
2000AF 4P
366.4
4000AF 3P
359.4
4000AF 4P
474.4
5000AF 3P
576.4
5000AF 4P
746.4
6300AF 3P
732.4
6300AF 4P
962.4
73
Accessories
Safety Control Cover [SC]
Safety
control
cover
2000AF 3P
334
2000AF 4P
419
4000AF 3P
412
4000AF 4P
527
5000AF 3P
629
5000AF 4P
799
6300AF 3P
785
6300AF 4P
1015
Body supporter
74
Door plate
Racking interlock
Draw-in button
Pad lock
ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or
out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out.
As shown in the figure, if draw-in/out button pops out, it means locking is operating.
To continue Draw-in/out operation, release lock by pushing Draw-in/out button
In case it is locked as shown in the figure above, main body of ACB can not be drawn in or
out into the cradle.
For the lock device, user has to purchase it. (5 ~ 6)
75
Accessories
Miss Insertion Prevent Device [MIP]
C
E
G
A
B
Cradle
ACB body
When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with
cradle, it mechanically prevents ACB from being inserted into cradle of ACB.
The installation method is variable according to ratings.
76
Cradle
ACB
Cradle
ACB
Cradle
ACB
Cradle
ACB
ABCD
567
ADEF
237
ABEG
346
BCEG
146
ABCE
467
ADEG
236
ABFG
345
BDEF
137
ABCF
457
ADFG
235
ACDE
267
BDEG
136
ABCG
456
AEFG
234
ACDF
257
BDFG
135
ABDE
367
BCDE
167
ACDG
256
CDEF
127
ABDF
357
BCDF
157
ACEF
247
CDEG
126
ABDG
356
BCDG
156
ACEG
246
CEFG
124
ABEF
347
BCEF
147
ACFG
245
DEFG
123
AC [V]
48~60
48
100~130
100~130
200~250
200~250
380~480
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.4~0.6 5Vn
200
Trip time[s]
0.5, 1,
1.5, 3
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Wiring
1. Wiring for general type
Rated
voltage
(Vn)
Rated
voltage
(Vn)
Delay trip
function
14
16
14
16
D2
Instantaneous
trip
function
D1
D2
D1
ACB
ACB
Rated
voltage
(Vn)
Rated
voltage
(Vn)
77
Accessories
Temperature Alarm [TM]
Temperature
alarm
Control power
AC/DC 110/220V
1
2
Power
24V
24V GND
5V
5V GND
13
14
15
16
Temperature alarm
Relay 3
DO control
17
18
Temperature Alarm(+)
Temperature Alarm(-)
8
9
RS-485(-)
19
10
RS-485(+)
20
78
11
12
RS-485
MODBUS
Profibus-DP
Control Power
AC/DC 110/220V
Power
2
CB ON
CB OFF
General DI 1
General DI 2
DI_COM
Relay 0
CB close
24V
24V GND
5V
5V GND
13
14
CB ON(+)
CB ON(-)
15
Relay 1
CB open
CB OFF(+)
16
CB OFF(-)
5
6
7
RS-485(-)
19
RS-485(+)
20
10
11
RS-485
12
Alarm
MODBUS
Profibus-DP
Classification
CB control
Applied range
3680VA, 480W
AC230V 6A / DC25V 6A
1880VA, 150W
Remarks
Induction load
(cos=0.4, L/R=7ms)
LED
Status
DI1
DI2
DO ON
DO OFF
CB ON
CB OFF
RUN LED
CB ERROR
79
Electrical diagram
V2
V3
VN
E1
Z3
Z1
485+
R11
R22
513
R2
R1
251
83
183
/RES(+)
Trip relay
D1
C11
ON
OFF
Power supply
OFF
Common
Reset
ZCT
V1
ZSI Input
Voltage module
ZSI Output
This diagram is based on CONNECTED position of a circuit breaker and Opening, Motor charging, Releasing of locking plate
should be normal condition.
C1
A1
CC
Z2
485-
544
534
524
LTD
Z4
STD/Inst
E2
GTD
or
252
184
/RES(-)
D2
Fault trip
UVT
Main circuit
84
Ready to close
C12
C2
Electric operation
circuit
Secondary
trip coil
13
14 ~ 63
64
Auxiliary switch a
D1
D2
11
12 ~ 61
62
Auxiliary switch b
83
84
Alarm1 a
413 414
Charged signal
183 184
Alarm2 a
423 424
251 252
U1
U2
Motor charging
R1
Control power
A1
A2
Closing coil
513 ~ 544
Alarm contact
C1
C2
Shunt trip
R11 R22
485+ 485-
RS-485 communication
C11 C12
R2
Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position
2. Relay is normal condition and charging type is "OFF-Charging"
3. The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 48 page for more detail on auxiliary switches.
4. Option
- Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil
- Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI
5. Please consult us for the use of ZSI (Zone selective Interlocking).
6. Refer to the page 33 for the connection of Trip relay and the page 43 for UVT.
7. For connecting RS-485 verify if the polarity is correct
80
A2
Temperature
Module
41
31
21
53
11
43
33
23
13
T1
TC1
341
TC2
331
321
311
Temperature
Sensor-2
CL
Axa
Axa
Axa
Axa
Axa
Axb
Axb
Axb
Axb
Axb
Temperature
Sensor-1
T2
CL
51
CL
423
CL
413
Axb
U1
52
42
32
22
12
54
44
34
Charge
completion
contact
24
14
342
344
332
334
322
324
312
314
ON
424
OFF
414
Charged
U2
Charged
Thermal,
communication
remote control module
Auxiliary switch
Cell switch
Z2
ZSI input
Z3
Z4
ZSI output
E1
E2
ZCT
VN ~ V3
TC1 , TC2 ~ T1
311 ~ 344
Voltage module
,
T2
Temperature module
Position switch
Ax
LTD
STD/Inst
GTD
CL
M
Auxiliary switch
Internal wiring
External wiring
(by customer)
CC
Closing coil
SHT1
SHT2
UVT
UVT coil
81
Dimensions
Fixed type 2000AF
(630~1600A: AH/AN/AS-06~16D)
300
280
385
280
150
150
12
165
270
20
20
165
12
35
300
320
35
270
300
250
12
165
3P
85
12
439
354
Vertical type
320
Front view
4P
85
85
85
85
15
20
20
165
165
25
25
45
45
15
4- 14
Mounting hole
4- 14
Mounting hole
330
354
415
439
3P
4P
15
90
(Insulation
barrier)
35
Door Frame: DF
(AH/AN/AS-D/E)
20
165
295
<Conductor>
45
32.5
<Mounting hole>
<Side hole>
276
Door frame
109
278
350
<External size>
82
7
10
165
Cradle bottom
165
Din. "W"
330
415
408
523
304
128
120
39 21.5
170
352
266
388
120
D3
D4
E3
E4
Cradle bottom
11.5
65
50
133
2- 13
42 50
67
83
25
270
50
30
15
Horizontal
type
85
85
85
85
85
50
20
20
165
165
25
25
45
45
50
4- 14
Mounting hole
4- 14
Mounting hole
415
439
330
354
3P
4P
30
15
15
90
(Insulation
barrier)
20
85
50
32.5
85
85
85
85
50
20
20
165
165
230
25
25
45
45
50
4- 14
Mounting hole
4- 14
Mounting hole
330
354
415
439
3P
4P
25
15
55
19.5
25
483
270
50
200
15
2- 13
<Conductor>
108
200
35
Front
connection
type
25
<Conductor>
45
165
295
5.5
65
2- 13
67
35
59.5 15
118
133
270
15
65
20
165
295
45
5.5
83
Dimensions
Draw-out type 2000AF
(630~1600A: AH/AN/AS-06~16D)
Front view
167
167
430
430
42.5
85
260
334
260
419
4P
3P
Vertical type
85
85
85
15
85
85
200
200
115
115
15
260
334
85
260
345
3P
4P
50
15
35
60
10
200
375
6- 13 Mounting hole
84
8.5
Earthing Hole
97
41 18
2- 13
<Conductor>
115
38.5
10.4
20
10
50
25
133
350
270
50
15
Horizontal
type
85
85
85
85
85
50
200
200
115
115
50
85
260
334
260
345
3P
4P
(Insulation
barrier)
35
20
10
9
50
25
133
350
270
15
15
8.5
Earthing Hole
10.4
97
41 18
2- 13
<Conductor>
60
200
10
115
375
38.5
6- 13 Mounting hole
85
85
85
85
85
50
200
200
115
115
50
260
334
85
260
345
3P
4P
15
25
200
13.5
200
41 18
2- 13
60
10
200
375
8.5
Earthing Hole
10.4
<Conductor>
78
4- 13 Mounting hole
20
10
25
50
483
270
15
Front
connection
type
115
11.5
85
Dimensions
Fixed type 2000AF (2000A: AH/AS-20D)
Front view
300
280
385
280
150
150
165
12
Vertical
type
165
270
12
12
250
439
3P
4P
85
85
85
85
15
20
20
165
165
25
25
45
45
15
4- 14
Mounting hole
4- 14
Mounting hole
330
354
415
439
3P
4P
15
90
(Insulation
barrier)
35
75
25
133
67
75
58
25
270
75
30
15
20
165
295
3- 13
<Conductor>
45
32.5
29.5
65
86
12
165
354
85
320
35
300
20
20
35
270
320
300
167
430
430
167
260
85
260
334
419
3P
85
Vertical
type
4P
85
85
15
85
85
200
200
115
115
15
260
85
260
334
345
3P
4P
50
15
35
75
133
350
20
25
270
75
25
10
15
8.5
Earthing Hole
10.4
97
41 18
3- 13
60
10
200
375
<Conductor>
115
38.5
6- 13 Mounting hole
87
Dimensions
Fixed type 4000AF
(2000~3200A: AH/AN/AS-20~32E)
Front view
493
378
189
304
189
189
280
280
204
12
12
270
320
300
20
12
204
35
270
320
35
20
300
204
319
3P
Vertical
type
115
4P
115
115
115
115
20
45
20
20
165
165
25
25
45
20
4- 14
Mounting hole
4- 14
Mounting hole
408
432
523
547
3P
4P
15
90
(Insulation
barrier)
65
20
165
295
45
32.5
29.5
35
75
25
133
67
75
58
25
270
75
30
15
88
12
547
432
3- 13
<Conductor>
Horizontal
type
115
115
115
115
115
75
165
20
20
165
25
25
45
45
75
4- 14
Mounting hole
4- 14
Mounting hole
523
547
408
432
3P
4P
15
90
(Insulation
barrier)
75
25
133
32.5
115
115
115
115
75
45
20
20
165
165
25
25
45
75
5.5
115
4- 14
Mounting hole
4- 14
Mounting hole
408
432
523
3P
4P
547
25
212.5
15
55
19.5
25
483
75
270
25
15
3- 13
<Conductor>
108
212.5
35
Front
connection
type
<Conductor>
45
165
295
5.5
20
65
3- 13
67
35
57 20
113
25
270
20
30
15
65
20
165
295
45
5.5
89
Dimensions
Draw-out type 4000AF
(2000~3200A: AH/AN/AS-20~32E)
Front view
57.5
206
430
430
206
115
260
260
375
412
527
3P
Vertical type
4P
115
115
115
115
115
20
200
200
115
115
20
260
115
260
412
375
3P
4P
50
15
34
75
25
25
133
350
270
75
8.5
Earthing Hole
3- 13
97
41 18
<Conductor>
60
10
200
375
6- 13 Mounting hole
90
115
38.5
10.4
20
10
15
115
Horizontal
type
115
115
115
115
75
200
200
115
115
75
260
260
115
412
375
3P
4P
25
75
20
20
25
133
350
270
10
15
10.4
8.5
Earthing Hole
97
41 18
3- 13
60
200
10
<Conductor>
115
375
38.5
6- 13 Mounting hole
115
115
115
115
115
75
200
200
115
115
75
260
412
115
260
375
3P
Disconnected & Test
Connected
50
4P
ARC Chute surface
25
15
13.5
25
9
8.5
Earthing Hole
483
270
20
10
75
25
212.5
15
10.4
3- 13
212.5
41 18
<Conductor>
4- 13 Mounting hole
60
10
200
375
78
Front
connection
type
115
11.5
91
Dimensions
Fixed type 4000AF (4000A: AH/AS-40E)
Front view
378
493
189
304
189
189
280
280
204
204
300
20
270
320
270
320
35
319
12
3P
4P
150
150
17.5
10
150
150
17.5
15
10
15
165
20
20
4- 14
Mounting hole
408
432
3P
4- 14
Mounting hole
523
547
4P
15
90
(Insulation
barrier)
20
165
295
45
112.5
4.5
35
25 25
125
67
25
125
33
158
270
25
125
34
15
65
92
15
25
165
25
45
15
12
204
547
150
Vertical
type
12
432
45
12
35
20
300
5- 13
<Conductor>
Horizontal
type
140
140
140
140
100
140
100
165
25
20
20
165
25
45
45
12.5
4- 14
Mounting hole
4- 14
Mounting hole
408
432
523
3P
4P
547
15
90
(Insulation
barrier)
34
12.5
57
20
165
295
45
65.5
29.5
35
65
10 1010
25
55
25
100
98
153
25
270
55
12.5
15
4- 13
<Conductor>
93
Dimensions
Draw-out type 4000AF (4000A: AH/AS-40E)
Front view
57.5
206
430
430
206
260
412
115
260
375
527
3P
4P
10
150
15
150
150
10
40
15
150
40
200
200
115
115
Vertical
type
150
17.5
115
260
412
3P
260
375
4P
34
15
15 10 15
125*10t-3ea
10
125
94
22
84.5
41 18
6
60
10
200
375
6- 13 Mounting hole
115
98.5
20
125
25
25
350
33
158
270
25
125
25
M12*80L bolt
<Conductor>
10.4
Horizontal
type
140
140
140
12.5
140
140
100
200
200
115
115
100
115
260
412
260
375
3P
4P
12.5
50
15
10 1010
90
(Insulation
barrier)
34
10
25
6
10
200
375
4- 13 Mounting hole
10.4
4- 13
87
59.5
41 18
55
60
20
25
350
98
153
270
100
55
25
12.5
15
<Conductor>
115
66.5
95
Dimensions
Fixed type 5000AF (4000~5000A: AS-40~50F)
Front view
765
595
280
280
150
Operating panel center
460
Vertical
type
165
270
300
380
60 35
95
630
12
12
165
649
819
3P
4P
190
190
190
70
190
190
20
20
4- 14
Mounting hole
625
795
649
819
3P
4P
15
90
(Insulation
barrier)
96
165
295
25 25
125
25
39.5
125
102
20.5
95
58
183
25
270
125
34
15
20
5- 13
45
67.5
20
20
165
20
4- 14
Mounting hole
65
70
165
45
20
12
45
12
80
80
60 35
95
380
300
270
150
Operating panel center
<Conductor>
Horizontal
type
190
190
190
190
190
125
20
20
165
165
45
45
125
4- 14
Mounting
hole
625
649
4- 14
Mounting
hole
795
819
3P
4P
34
15
18
95
42 20
97
70
25
20
25 25
125
83
193
270
20
25
70
20
15
90
(Insulation
barrier)
65
20
165
295
Door Frame: DF
(AH-G, AS-F)
5- 13
45
<Conductor>
67.5
<Mounting hole>
<Side hole>
Rear Panel
10- 9
Door frame
Din. "W"
625
795
781
1011
<External size>
7
10
165
334
128
165
Cradle bottom
109
Cradle bottom
11.5
278
350
39 21.5
200
120
352
266
388
120
F3
F4
G3
G4
97
Dimensions
Draw-out type 5000AF (4000~5000A: AS-40~50F)
Front view
147.5
232.5
460
460
295
260
205
260
629
260
799
3P
4P
190
190
190
20
70
190
190
20
20
200
200
115
115
Vertical
type
295
260
260
205
3P
260
4P
10
200
375
98
20
40
25 25
125
25
183
380
5- 13
<Conductor>
115
6- 13 Mounting hole
9
8.5 Earthing Hole
102
39.5
36 41 18
125
58
270
25
125
34
15
53.5
10.4
70
20
Horizontal
type
190
190
190
190
190
125
200
115
125
295
260
260
205
3P
4P
34
15
20
40
25
25
83
193
380
270
20
25
25
70 20
110
(Insulation
barrier)
125
260
9
8.5 Earthing Hole
110
42
97
36 41 18
10
200
375
10.4
5- 13
<Conductor>
115
63.5
6- 13 Mounting hole
99
Dimensions
Fixed type 6300AF (4000A~6300A: AH/AS-40~50G)
Front view
981
751
792
189
562
189
280
280
380
300
270
577
204
12
12
60 35
95
80
12
60 35
95
80
380
300
270
807
204
12
1035
805
4P
3P
4000A~5000A
6300A
34
15
20
40
25
25
25
150
10.4
25
20
40
125
25
25
25
25
34
15
25
9
8.5 Earthing Hole
5- 13
10.4
6- 13
<Conductor>
<Conductor>
Vertical type
244
244
244
70
244
244
20
20
20
4- 14
Mounting
hole
1011
805
1035
3P
4P
4000A~5000A
6300A
90
(Insulation
barrier)
165
295
100
45
70
65
67.5
42 20
97
18
95
20.5
20
39.5
125
102
20
83
193
58
183
270
20
70
125
20
15
15
90
(Insulation
barrier)
270
95
65
20
165
165
20
4- 14
Mounting
hole
781
70
45
45
20
20
165
295
45
67.5
Horizontal type
4000A~5000A
244
244
244
244
244
125
20
20
165
165
45
45
125
4- 14
Mounting
hole
781
4- 14
Mounting
hole
1011
805
1035
3P
4P
6300A
244
244
244
244
150
20
20
165
165
45
45
150
4- 14
Mounting
hole
781
244
1011
805
1035
3P
4P
4- 14
Mounting
hole
18
95
42 20
97
70
20
83
193
270
20
70
20
15
90
(Insulation
barrier)
65
20
165
295
45
67.5
101
Dimensions
Draw-out type 6300AF (4000A~6300A: AH/AS-40~50G)
Front view
186.5
301.5
460
460
260
113
785
343
260
260
260
1015
3P
4P
Vertical type
244
244
244
70
244
244
20
20
200
200
115
115
20
260
113
343
260
260
3P
260
4P
4000A~5000A
6300A
15
90
(Insulation
barrier)
90
200
115
375
6- 13 Mounting hole
10
53.5
150
33
183
380
150
27
102
36 41 18
36 41 18
39.5
125
102
58
183
380
270
270
125
(Insulation
barrier)
200
375
10
115
53.5
6- 13 Mounting hole
34
15
20
40
25
25
25
150
10.4
25
20
40
125
25
25
25
25
34
15
25
102
5- 13
<Conductor>
6- 13
<Conductor>
10.4
70
20
Horizontal type
4000A~5000A
244
244
244
244
244
125
200
200
115
115
125
260
113
260
260
6300A
244
260
343
3P
4P
244
244
244
244
150
200
200
115
115
150
113
260
260
260
343
3P
4P
260
4000A~5000A
Arc chute surface
34
15
90
20
40
25
25
25
83
193
380
5- 13
<Conductor>
110
25
25
34
15
25
150
25
63.5
6300A
25
42
97
36 41 18
10
200
115
375
6- 13 Mounting hole
10.4
20
40
270
20
125
70 20
110
25
(Insulation
barrier)
10.4
6- 13
<Conductor>
103
Technical information
Insulation voltage
OPEN
B
(AN, AS)
B
(AH)
You should keep the isolation distance between ACB and panel as below table.
CLOSE
000001
Type
Fixed
Draw out
AN/AS
50
150
AH
50
150
AN/AS
50
150
AH
50
Note) When drawing the distribution panel, it is available to use regardless of the distance between
ACB and the wall of the panel because Susol ACB(draw-in/out type) extinguishes the arc
in the Arc Chute and Arc Cover clearly.
8 mm
1000V
14 mm
Bolt
Bolt
Washers
40-50Nm
600V
Bolt
Washers
Nut
Busher
25
Screw type
104
Tightening torque
Standard(kgfcm)
Tolerance
Standard(N.m)
Tolerance
M8
135
16
13.3
1.6
M10
270
32
26.5
3.2
M12
480
57
46.6
5.6
Temperature derating
The table below indicates the maximum current rating, for each connection type,
as a function of the ambient temperature around the circuit breaker and the busbars.
Circuit breakers with mixed connections have the same derating as horizontally connected breakers.
For ambient temperatures greater than 60C, consult us.
Temperature inside the switchboard around the circuit breaker and its connection: Ti(IEC 60947-2)
Frame
Rated
current
ACB terminal
Applicable
busbar size
Horizontal type
1600AF
AN-D
AS-D
AH-D
200A
400A
5t501EA
630A
800A
1,000A
15t501EA
1,250A
1,600A
2000AF
AS/AH-D
3200AF
AN-E
AS-E
AH-E
2,000A
15t751EA
630A
800A
1,000A
1,250A
20t751EA
1,600A
2,000A
2,500A
3,200A
4000AF
AS/AH-E
5000AF
AS-F
6300AF
AS-G
AH-G
4,000A
4,000A
5,000A
4,000A
5,000A
6,300A
10t1003EA
20t1252EA
20t1252EA
20t1502EA
5t502EA
10t601EA
6t502EA
10t601EA
8t502EA
6t752EA
8t602EA
10t502EA
6t753EA
10t602EA
8t603EA
8t753EA
10t1002EA
5t502EA
10t601EA
6t502EA
10t601EA
8t502EA
6t752EA
8t602EA
10t502EA
6t753EA
10t602EA
8t603EA
8t753EA
10t1002EA
10t753EA
8t754EA
10t1003EA
10t754EA
10t1004EA
10t755EA
10t1004EA
10t1254EA
10t1004EA
10t1254EA
10t1504EA
Vertical type
40C
200A
400A
45C
200A
400A
50C
200A
400A
55C
200A
400A
60C
200A
400A
40C
200A
400A
45C
200A
400A
50C
200A
400A
55C
200A
400A
60C
200A
400A
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A
1250A 1250A 1250A 1250A 1250A
1250A 1250A 1250A 1250A 1250A
-
630A
630A
630A
630A
630A
630A
630A
630A
630A
630A
800A
800A
800A
800A
800A
800A
800A
800A
800A
800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A
1250A 1250A 1250A 1250A 1250A
1250A 1250A 1250A 1250A 1250A
-
3200A
4000A
4000A
5000A
4000A
5000A
6300A
3100A
3900A
3920A
4900A
4000A
4900A
6170A
3000A
3800A
3860A
4800A
4000A
4820A
6040A
2900A
3640A
3800A
4700A
4000A
4750A
5900A
4000A
5000A
4000A
5000A
6300A
3960A
4950A
4000A
4950A
6220A
3900A
4900A
4000A
4870A
6160A
3880A
4850A
4000A
4850A
6100A
105
Technical information
Operating conditions
Ambient temperature
ACB devices can operate under the following temperature conditions
- The electrical and mechanical characteristics are stipulated for an ambient temperature of -5C to +40C
- The average temperature should be within + 35C
- Reduce the continuous conducting current when the temperature is over 45C (refer to temperature derating)
- Storage condition : -20C to + 60C is recommended.
Altitude
Susol ACB is designed for operation at altitudes under 2000m. At altitudes higher than 2000m,
emitting heat is lowered and operating voltage, continuous current capacity, and breaking capacity
will be reduced. Durability of the insulation is also reduced according to the atmosphere pressure.
According to the below table, change the ratings upon a service condition.
Altitude [m]
Item
Withstand voltage [V]
Average insulating voltage [v]
Max. using voltage [V]
Current compensation constant
2000m
3000m
4000m
5000m
3500
1000
690
1In
3150
900
590
0.98In
2500
700
520
0.96In
2100
600
460
0.94In
Environment
Under clean air;
Maximum temperature + 40C (relative humidity should be under 85%)
Maximum temperature + 20C (relative humidity should be under 90%)
Do not apply under corrosive or ammonia gas circumstances
(H2S 0.01ppm, SO2 0.01ppm, NH3 a few ppm)
* Extreme atmosphere conditions
Under high temperature and/or high humidity, the insulation durability, electrical and
mechanical features could be deteriorated. At this conditions, increasing corrosion-resistant
dealing needs. Corrosion-resistant parts need under this conditions.
AN-16D
AH/AS-20D
AH/AS-32E
AH/AS-40E
AS-50F
AH/AS-63G
106
Rated current
(A)
630
800
1,000
1,250
1,600
630
800
1,000
1,250
1,600
2,000
2,000
2,500
3,200
2,000
2,500
3,200
4,000
4,000
5,000
4,000
5,000
6,300
Draw-out type
Fixed type
24
38
60
94
154
18
29
45
70
115
156
120
188
307
120
188
307
384
384
600
288
450
595
Note) 1. Above power consumption is whole power consumption for each Rated current, 50/60Hz, 3/4pole.
2. This is inner assistant value per 1 pole.
0.04
0.04
0.04
0.04
0.04
0.03
0.03
0.03
0.03
0.03
0.027
0.02
0.02
0.02
0.02
0.02
0.02
0.011
0.011
0.011
0.009
0.009
0.007
3. Power factor = 1.0
48
77
120
188
307
36
58
90
141
230
324
240
375
614
240
375
614
528
528
825
432
675
833
Installation recommendation
BUS-BAR Connection
Cables connections
Make sure that no excessive mechanical force put on the rear terminals for cable connection.
Extension terminal is fixed such as B, C and cable is to fixed to the frame such as E
Bus-bar connection
For busbar connection, connect access parts with a provided torque and fix with parallel installing the support not to apply
terminal weight to circuit breaker.
In order to prevent the spread safety or secondary accidents, secure maximum safe distance A (Table 1) from the access area
to withstand the electrical force during the short circuit faults.
30
50
65
80
100
150
Length A (mm)
350
300
250
150
150
150
107
Technical information
Installation recommendation
Non-protected
Protected against solid foreign objects
of 50mm and greater
Protected against solid foreign objects
of 12.5mm and greater
Protected against solid foreign objects
of 2.5mm and greater
Protected against solid foreign objects
of 1.0mm and greater
Dust-protected
Dust-tight
Definition
The object probe sphere of 50mm ,
shall not fully penetrate
The object probe sphere of 12.5mm ,
shall not fully penetrate
The object probe sphere of 2.5mm ,
shall not penetrate at all
The object probe of 1.0mm ,
shall not penetrate at all
Ingress of dust is not totally prevented, but dust shall not
penetrate in a quantity to interfere with satisfactory
operation of the apparatus or to impair safety
No ingress of dust
Non-protected
Protected against vertically falling
water drops
Protected against vertically falling
water drops when enclosure tilted
up to 15
108
Definition
Vertically falling drops shall have no harmful effects
Vertically falling drops shall have no harmful effects
when the enclosure is tilted at any angle up to 15 on
either side of the vertical
Water sprayed at an angle up to 60 on wither side of
the vertical shall have no harmful effects
Water splashed against the enclosure from and
direction shall have no harmful effects
Water projected in powerful jets against the enclosure
from and direction shall have no harmful effects
Water projected in powerful jets against the enclosure
from any direction shall have no harmful effects
Ingress of water in quantities causing harmful effects shall
not be possible when the enclosure is temporarily immersed
in water under standardized conditions of pressure and time
Ingress of water in quantities causing harmful effects
shall not be possible when the enclosure is
continuously immersed in water under conditions which
shall be agreed between manufacturer and used but
which are more severs than for numeral 7
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4
3
2
1
(2300800900)
Connection type
Model type
AS/AH-10E, AN-10D
Busbar dimensions(mm)
2EA-506
2EA-508
Ventilated switchboard(IP31)
Ta=35
800
3
2
1
Ta=45
800
800
800
800
1000
800
800
800
1000
1000
800
800
800
1000
1000
4
3
2
1
Ta=55
800
800
800
800
1000
800
800
1000
1000
800
800
800
1000
1000
1
Ta=35
800
800
800
800
1000
800
800
1000
1000
800
800
800
1000
1000
800
800
800
2
1
800
800
800
800
1000
800
800
1000
1000
800
800
800
1000
1000
800
800
1000
800
800
800
1000
1000
800
800
800
800
1000
1000
800
800
1000
800
800
800
1000
1000
800
800
800
1000
1000
3
2
1
1000
800
Ta=55
1000
800
2
Ta=45
1000
800
1000
800
1000
800
3
2
1000
800
800
800
1000
1000
1000
1000
1000
1000
109
Technical information
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4
3
2
1
(2300800900)
Connection type
Model type
AS/AH-13E, AN-13D
AS/AH-16E, AN-16D
Busbar dimensions(mm)
2EA-756
2EA-6010
Ventilated switchboard(IP31)
Ta=35
4
3
1250
2
1
Ta=45
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1470
1500
1600
1600
1600
1600
1600
1600
1250
2
1
1250
1250
1500
1480
1600
1600
4
3
1250
2
1
110
1600
4
3
Ta=55
1600
1250
2
Ta=45
1600
4
3
1600
1250
2
Ta=35
1600
4
3
1600
1250
1600
4
3
Ta=55
1600
1250
1250
1400
1400
1520
1500
Switchboard compsition
4
3
2
1
(2300800900)
4
3
2
1
4
3
2
1
4
3
2
1
Connection type
Model type
AN/AS/AH-20E,
AN/AS/AH-25E
AN/AS/AH-32E
AS/AH-40E
Busbar dimensions(mm)
2EA-7510
3EA-7510
4EA-7510
4EA-7510
Ventilated switchboard(IP31)
Ta=35
4
3
2
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
1900
1960
1960
1800
1920
1920
2400
2500
3100
3200
3400
3750
2300
2400
2900
3100
3200
3550
2200
2300
2700
2900
3000
3300
2115
2275
2650
2850
3040
3320
2000
2150
2550
2700
2880
3120
1900
2020
2370
2530
2720
2960
1
Ta=45
4
3
2
2000
1
Ta=55
4
3
2
2000
1
Ta=35
4
3
2000
1
Ta=45
4
3
2
1900
1
Ta=55
4
3
2
1780
111
Technical information
Installation recommendation
Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)
Switchboard compsition
4
3
2
1
(2300800900)
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Connection type
Model type
Busbar dimensions(mm)
Ventilated switchboard(IP31)
Ta=35
AS-40F
AS-50F
AS/AH-63G
AS/AH-50G
AS/AH-63G
4EA-10010
4EA-12510
4EA-10010
4EA-12510
4EA-15010
4
3
2
3900
4000
4750
4800
4000
4000
4750
5000
5850
6300
3850
3900
4350
4650
4000
4000
4450
4850
5670
5850
3800
3850
4200
4400
4000
4000
4200
4600
5350
5670
3800
3900
4200
4550
4000
4000
4400
4650
5350
5000
3650
3800
3950
4250
4000
4000
4100
4400
5040
5350
3550
3650
3700
4050
3900
3950
3850
4150
4730
5040
1
Ta=45
4
3
2
1
Ta=55
4
3
2
1
Ta=35
4
3
2
1
Ta=45
4
3
2
1
Ta=55
4
3
2
1
112
AH-D,W
Protective coordination
AC 220/240V
Susol MCCB
Susol AH series
Upstream
breaker
AH-D,W
AH-06D
Downstream
breaker
Model
Product type
AH-08D
200
400
630
400
630
800
1000
1250
1600
2000
9.45
9.45
12
15
18.75
24
30
85
TD100N
100
85
TD100H
100
100
TD100L
100
200
TD160N
160
85
TD160H
160
100
TD160L
160
200
TS100N
100
100
TS100H
100
120
TS100L
100
200
TS160N
160
100
TS160H
160
120
Susol
TS160L
160
200
MCCB
TS250N
250
100
TS250H
250
120
TS250L
250
200
TS400N
400
100
TS400H
400
120
TS400L
400
200
TS630N
630
100
TS630H
630
120
TS630L
630
200
TS800N
800
100
TS800H
800
120
TS800L
800
200
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
113
Technical information
AH-E,X
AH-G,Z
Protective coordination
AC 220/240V
Susol MCCB
Susol AH series
Upstream
breaker
AH-E,X
AH-06E
Downstream
breaker
Model
Product
type
AH-G,Z
AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
400
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
9.45
12
15
18.75
24
30
37.5
48
60
60
75
94.5
100
150
TD100N
100
85
TD100H
100
100
TD100L
100
200
TD160N
160
85
TD160H
160
100
TD160L
160
200
TS100N
100
100
TS100H
100
120
TS100L
100
200
TS160N
160
100
TS160H
160
120
Susol TS160L
160
200
MCCB TS250N
250
100
TS250H
250
120
TS250L
250
200
TS400N
400
100
TS400H
400
120
TS400L
400
200
TS630N
630
100
TS630H
630
120
TS630L
630
200
TS800N
800
100
TS800H
800
120
TS800L
800
200
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
114
AH-D,W
AC 380/415V
Susol MCCB
Susol AH series
Upstream
breaker
AH-D,W
AH-06D
Downstream
breaker
Model
Product type
AH-08D
200
400
630
400
630
800
1000
1250
1600
2000
9.45
9.45
12
15
18.75
24
30
85
TD100N
100
50
TD100H
100
85
TD100L
100
150
TD160N
160
50
TD160H
160
85
TD160L
160
150
TS100N
100
50
TS100H
100
85
TS100L
100
150
TS160N
160
50
TS160H
160
85
Susol
TS160L
160
150
MCCB
TS250N
250
50
TS250H
250
85
TS250L
250
150
TS400N
400
65
TS400H
400
85
TS400L
400
150
TS630N
630
65
TS630H
630
85
TS630L
630
150
TS800N
800
65
TS800H
800
100
TS800L
800
150
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
115
Technical information
AH-E,X
AH-G,Z
Protective coordination
AC 380/415V
Susol MCCB
Susol AH series
Upstream
breaker
AH-E,X
AH-06E
Downstream
breaker
Model
Product
type
AH-G,Z
AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
400
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
9.45
12
15
18.75
24
30
37.5
48
60
60
75
94.5
100
150
TD100N
100
50
TD100H
100
85
TD100L
100
150
TD160N
160
50
TD160H
160
85
TD160L
160
150
TS100N
100
50
TS100H
100
85
TS100L
100
150
TS160N
160
50
TS160H
160
85
Susol TS160L
160
150
MCCB TS250N
250
50
TS250H
250
85
TS250L
250
150
TS400N
400
65
TS400H
400
85
TS400L
400
150
TS630N
630
65
TS630H
630
85
TS630L
630
150
TS800N
800
65
TS800H
800
100
TS800L
800
150
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
116
AH-D,W
AC 480/500V
Susol MCCB
Susol AH series
Upstream
breaker
AH-D,W
AH-06D
Downstream
breaker
Model
Product type
AH-08D
200
400
630
400
630
800
1000
1250
1600
2000
9.45
9.45
12
15
18.75
24
30
85
TD100N
100
30
TD100H
100
50
TD100L
100
65
TD160N
160
30
TD160H
160
50
TD160L
160
65
TS100N
100
42
TS100H
100
65
TS100L
100
85
TS160N
160
42
TS160H
160
65
Susol
TS160L
160
85
MCCB
TS250N
250
42
TS250H
250
65
TS250L
250
85
TS400N
400
42
TS400H
400
65
TS400L
400
85
TS630N
630
42
TS630H
630
65
TS630L
630
85
TS800N
800
42
TS800H
800
85
TS800L
800
100
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
117
Technical information
AH-E,X
AH-G,Z
AC 480/500V
Susol MCCB
Susol AH series
Upstream
breaker
AH-E,X
AH-06E
Downstream
breaker
Model
Product
type
AH-G,Z
AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
400
630
800
1000
1250
1600
2000
2500
3200
4000
4000
5000
6300
9.45
12
15
18.75
24
30
37.5
48
60
60
75
94.5
100
150
TD100N
100
30
TD100H
100
50
TD100L
100
65
TD160N
160
30
TD160H
160
50
TD160L
160
65
TS100N
100
42
TS100H
100
65
TS100L
100
85
TS160N
160
42
TS160H
160
65
Susol TS160L
160
85
MCCB TS250N
250
42
TS250H
250
65
TS250L
250
85
TS400N
400
42
TS400H
400
65
TS400L
400
85
TS630N
630
42
TS630H
630
65
TS630L
630
85
TS800N
800
42
TS800H
800
85
TS800L
800
100
Note) 1. On table, protective coordination is not available for areas where number is missing.
2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination.
3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breakers rated short breaking capacity.
118
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures. This prevents the Member States from limiting
the marketing and putting into service of products bearing the CE marking, unless this measure is
justified by the proved non-conformity of the product.
IECEE CB SCHEME
The IECEE CB Scheme is the world's first truly international system for acceptance of test reports
dealing with the safety of electrical and electronic products. It is a multilateral agreement among
participating countries and certification organizations. A manufacturer utilizing a CB test report
issued by one of these organizations can obtain national certification in all other member countries
of the CB Scheme.
The Scheme is based on the use of international (IEC) Standards. If some members' national
standards are not yet completely harmonized with IEC Standards, national differences are
permitted if clearly declared to all other members. The CB Scheme utilizes CB Test Certificates to
attest that product samples have successfully passed the appropriate tests and are in compliance
with the requirements of the relevant IEC Standard and with the declared national differences of
various member countries.
The main objective of the Scheme, is to facilitate trade by promoting harmonization of the national
standards with international Standards and cooperation among product certifiers worldwide in order
to bring product manufacturers a step closer to the ideal concept of "one product, one test, one
mark, where applicable'.
- LR, ABS, DNV, KR, BV, GL, RINA, NK
- GOST, TPC
119
Time chart
Long time
tr
Ir
1.11
1.15
1.20
1.25
1.30
1.35
1.40
1.45
1.50
1.55
1.60
1.65
1.70
1.75
1.80
1.85
1.90
1.95
2.00
2.05
2.10
2.15
2.20
2.25
2.30
2.35
2.40
2.45
2.50
2.55
2.60
2.65
2.70
2.75
2.80
2.85
2.90
2.95
3.00
3.05
3.10
3.15
3.20
3.25
3.30
3.35
3.40
3.45
3.50
3.55
3.60
3.65
3.70
3.75
3.80
3.85
3.90
120
0.5
12
16
20
tr
Ir
3.95
4.00
4.05
4.10
4.15
4.20
4.25
4.30
4.35
4.40
4.45
4.50
4.55
4.60
4.65
4.70
4.75
4.80
4.85
4.90
4.95
5.00
5.05
5.10
5.15
5.20
5.25
5.30
5.35
5.40
5.45
5.50
5.55
5.60
5.65
5.70
5.75
5.80
5.85
5.90
5.95
6.00
6.05
6.10
6.15
6.20
6.25
6.30
6.35
6.40
6.45
6.50
6.55
6.60
6.65
6.70
6.75
0.5
12
16
20
1181
1150
1121
1093
1065
1039
1014
990
966
944
922
901
881
861
842
824
806
789
772
756
741
726
711
697
683
670
657
644
632
620
608
597
586
575
565
555
545
536
526
517
509
500
492
483
476
468
460
453
446
439
432
425
418
412
406
400
394
2361
2300
2241
2185
2131
2079
2028
1980
1933
1888
1844
1802
1762
1722
1684
1648
1612
1578
1545
1513
1481
1451
1422
1393
1366
1339
1313
1288
1263
1240
1217
1194
1172
1151
1130
1110
1091
1071
1053
1035
1017
1000
983
967
951
936
920
906
891
877
863
850
837
824
811
799
787
4722
4600
4483
4370
4262
4157
4056
3959
3866
3776
3688
3604
3523
3445
3369
3295
3225
3156
3089
3025
2963
2902
2844
2787
2732
2678
2626
2576
2527
2479
2433
2388
2344
2302
2261
2220
2181
2143
2106
2070
2034
2000
1967
1934
1902
1871
1841
1811
1782
1754
1727
1700
1674
1648
1623
1598
1575
9445
9201
8966
8740
8523
8314
8113
7919
7731
7551
7377
7209
7046
6889
6738
6591
6449
6312
6179
6050
5925
5804
5687
5574
5463
5356
5252
5152
5054
4959
4866
4776
4689
4604
4521
4441
4362
4286
4212
4139
4069
4000
3933
3868
3804
3742
3682
3622
3565
3508
3453
3400
3347
3296
3246
3197
3149
18889
18401
17932
17481
17046
16628
16225
15837
15463
15102
14754
14417
14093
13779
13475
13182
12898
12624
12358
12100
11851
11609
11374
11147
10927
10713
10505
10303
10107
9917
9732
9552
9378
9207
9042
8881
8724
8572
8423
8279
8138
8000
7866
7736
7608
7484
7363
7245
7129
7017
6907
6799
6694
6592
6492
6394
6298
28334
27602
26898
26221
25569
24942
24338
23756
23194
22653
22131
21626
21139
20668
20213
19773
19347
18935
18536
18150
17776
17413
17062
16721
16390
16069
15757
15455
15161
14876
14598
14329
14066
13811
13563
13322
13087
12858
12635
12418
12206
12000
11799
11604
11413
11226
11045
10867
10694
10525
10360
10199
10042
9888
9738
9591
9447
37779
36802
35864
34961
34092
33256
32451
31674
30926
30204
29507
28835
28185
27557
26951
26364
25796
25247
24715
24200
23701
23218
22749
22294
21853
21425
21010
20607
20215
19834
19464
19105
18755
18415
18084
17762
17449
17144
16847
16557
16275
16000
15733
15471
15217
14968
14726
14490
14259
14034
13814
13599
13389
13184
12984
12788
12597
47223
46003
44830
43701
42615
41570
40563
39593
38657
37755
36884
36043
35231
34447
33688
32955
32245
31559
30894
30250
29627
29022
28436
27868
27317
26782
26262
25758
25268
24793
24330
23881
23444
23019
22605
22203
21811
21430
21058
20697
20344
20001
19666
19339
19021
18710
18408
18112
17823
17542
17267
16998
16736
16480
16230
15985
15746
tr
Ir
6.80
6.85
6.90
6.95
7.00
7.05
7.10
7.15
7.20
7.25
7.30
7.35
7.40
7.45
7.50
7.55
7.60
7.65
7.70
7.75
7.80
7.85
7.90
7.95
8.00
8.05
8.10
8.15
8.20
8.25
8.30
8.35
8.40
8.45
8.50
8.55
8.60
8.65
8.70
8.75
8.80
8.85
8.90
8.95
9.00
9.05
9.10
9.15
9.20
9.25
9.30
9.35
9.40
9.45
9.50
9.55
9.60
0.5
12
16
20
388
382
376
371
366
360
355
350
345
341
336
331
327
322
318
314
310
306
302
298
294
290
286
283
279
276
272
269
266
262
259
256
253
250
247
244
241
238
236
233
230
228
225
223
220
218
215
213
211
208
206
204
202
200
197
195
193
776
764
753
742
731
721
711
701
691
681
672
663
654
645
636
628
619
611
603
595
588
580
573
565
558
551
544
538
531
525
518
512
506
500
494
488
482
477
471
466
461
455
450
445
440
435
431
426
421
417
412
408
403
399
395
391
387
1551
1528
1506
1484
1463
1442
1421
1401
1382
1362
1344
1325
1307
1289
1272
1255
1239
1222
1206
1191
1175
1160
1145
1131
1117
1103
1089
1076
1062
1049
1037
1024
1012
1000
988
976
965
954
943
932
921
911
901
890
880
871
861
852
842
833
824
815
807
798
790
781
773
3102
3057
3012
2968
2925
2884
2843
2803
2763
2725
2687
2650
2614
2579
2544
2510
2477
2444
2412
2381
2350
2320
2291
2262
2233
2205
2178
2151
2125
2099
2073
2048
2024
2000
1976
1953
1930
1908
1886
1864
1843
1822
1801
1781
1761
1741
1722
1703
1685
1666
1648
1631
1613
1596
1579
1563
1546
6205
6113
6024
5936
5851
5767
5685
5605
5527
5450
5374
5301
5229
5158
5089
5021
4954
4889
4825
4762
4701
4640
4581
4523
4466
4411
4356
4302
4249
4197
4147
4097
4048
3999
3952
3906
3860
3815
3771
3728
3685
3643
3602
3562
3522
3483
3444
3407
3369
3333
3297
3261
3227
3192
3159
3125
3093
9307
9170
9036
8905
8776
8651
8528
8408
8290
8175
8062
7951
7843
7737
7633
7531
7431
7333
7237
7143
7051
6961
6872
6785
6700
6616
6534
6453
6374
6296
6220
6145
6071
5999
5928
5858
5790
5723
5657
5592
5528
5465
5403
5343
5283
5224
5167
5110
5054
4999
4945
4892
4840
4788
4738
4688
4639
12410
12227
12048
11873
11702
11534
11371
11210
11053
10899
10749
10601
10457
10316
10177
10041
9908
9778
9650
9524
9401
9281
9163
9047
8933
8821
8712
8604
8498
8395
8293
8193
8095
7999
7904
7811
7720
7630
7542
7455
7370
7287
7204
7123
7044
6966
6889
6813
6739
6666
6594
6523
6453
6384
6317
6251
6185
15512
15283
15060
14841
14627
14418
14213
14013
13816
13624
13436
13252
13071
12895
12721
12552
12385
12222
12062
11906
11752
11601
11453
11308
11166
11026
10889
10755
10623
10494
10366
10242
10119
9998
9880
9764
9650
9538
9428
9319
9213
9108
9005
8904
8805
8707
8611
8516
8423
8332
8242
8153
8066
7981
7896
7813
7732
tr
Ir
9.65
9.70
9.75
9.80
9.85
9.90
9.95
10.00
0.5
12
16
20
191
189
187
185
184
182
180
178
383
379
375
371
367
363
360
356
765
757
749
742
734
727
719
712
1530
1514
1499
1483
1468
1453
1439
1424
3060
3029
2998
2967
2937
2907
2878
2849
4591
4543
4496
4450
4405
4360
4316
4273
6121
6058
5995
5934
5873
5814
5755
5697
7651
7572
7494
7417
7342
7267
7194
7122
Short time
tsd
Ir
1.40
1.45
1.50
1.55
1.60
1.65
1.70
1.75
1.80
1.85
1.90
1.95
2.00
2.05
2.10
2.15
2.20
2.25
2.30
2.35
2.40
2.45
2.50
2.55
2.60
2.65
2.70
2.75
2.80
2.85
2.90
2.95
3.00
3.05
3.10
3.15
3.20
3.25
3.30
3.35
0.1
0.2
0.3
0.4
tsd
Ir
3.40
3.45
3.50
3.55
3.60
3.65
3.70
3.75
3.80
3.85
3.90
3.95
4.00
4.05
4.10
4.15
4.20
4.25
4.30
4.35
4.40
4.45
4.50
4.55
4.60
4.65
4.70
4.75
4.80
4.85
4.90
4.95
5.00
5.05
5.10
5.15
5.20
5.25
5.30
5.35
0.1
0.2
0.3
0.4
865
840
816
793
772
751
730
711
693
675
657
641
625
610
595
581
567
554
541
528
517
505
494
483
473
462
453
443
434
425
416
408
400
392
384
377
370
363
356
349
1730
1680
1633
1587
1543
1501
1461
1422
1385
1349
1315
1282
1250
1219
1190
1161
1134
1107
1082
1057
1033
1010
988
966
945
925
905
886
868
850
833
816
800
784
769
754
740
726
712
699
2595
2520
2449
2380
2315
2252
2191
2133
2078
2024
1972
1923
1875
1829
1785
1742
1701
1661
1622
1585
1550
1515
1481
1449
1418
1387
1358
1330
1302
1275
1249
1224
1200
1176
1153
1131
1109
1088
1068
1048
3460
3361
3265
3174
3086
3002
2922
2844
2770
2699
2630
2564
2500
2439
2380
2323
2268
2215
2163
2114
2066
2020
1975
1932
1890
1850
1811
1773
1736
1700
1666
1632
1600
1568
1538
1508
1479
1451
1424
1398
121
Time chart
Short time
tsd
Ir
5.40
5.45
5.50
5.55
5.60
5.65
5.70
5.75
5.80
5.85
5.90
5.95
6.00
6.05
6.10
6.15
6.20
6.25
6.30
6.35
6.40
6.45
6.50
6.55
6.60
6.65
6.70
6.75
6.80
6.85
6.90
6.95
7.00
7.05
7.10
7.15
7.20
7.25
7.30
7.35
7.40
7.45
7.50
7.55
7.60
7.65
7.70
7.75
7.80
7.85
7.90
7.95
8.00
8.05
8.10
8.15
8.20
122
0.1
343
337
331
325
319
313
308
302
297
292
287
282
278
273
269
264
260
256
252
248
244
240
237
233
230
226
223
219
216
213
210
207
204
201
198
196
193
190
188
185
183
180
178
175
173
171
169
166
164
162
160
158
156
154
152
151
149
0.2
686
673
661
649
638
627
616
605
595
584
575
565
556
546
537
529
520
512
504
496
488
481
473
466
459
452
446
439
433
426
420
414
408
402
397
391
386
380
375
370
365
360
356
351
346
342
337
333
329
325
320
316
312
309
305
301
297
Ground fault
0.3
1029
1010
992
974
957
940
923
907
892
877
862
847
833
820
806
793
780
768
756
744
732
721
710
699
689
678
668
658
649
639
630
621
612
604
595
587
579
571
563
555
548
541
533
526
519
513
506
499
493
487
481
475
469
463
457
452
446
0.4
1372
1347
1322
1299
1276
1253
1231
1210
1189
1169
1149
1130
1111
1093
1075
1058
1041
1024
1008
992
977
961
947
932
918
905
891
878
865
852
840
828
816
805
793
782
772
761
751
740
730
721
711
702
693
683
675
666
657
649
641
633
625
617
610
602
595
tsd
Ir
8.25
8.30
8.35
8.40
8.45
8.50
8.55
8.60
8.65
8.70
8.75
8.80
8.85
8.90
8.95
9.00
9.05
9.10
9.15
9.20
9.25
9.30
9.35
9.40
9.45
9.50
9.55
9.60
9.65
9.70
9.75
9.80
9.85
9.90
9.95
10.00
0.1
147
145
143
142
140
138
137
135
134
132
131
129
128
126
125
123
122
121
119
118
117
116
114
113
112
111
110
109
107
106
105
104
103
102
101
100
0.2
294
290
287
283
280
277
274
270
267
264
261
258
255
252
250
247
244
242
239
236
234
231
229
226
224
222
219
217
215
213
210
208
206
204
202
200
0.3
441
435
430
425
420
415
410
406
401
396
392
387
383
379
375
370
366
362
358
354
351
347
343
340
336
332
329
326
322
319
316
312
309
306
303
300
0.4
588
581
574
567
560
554
547
541
535
528
522
517
511
505
499
494
488
483
478
473
467
462
458
453
448
443
439
434
430
425
421
416
412
408
404
400
tg
In
0.20
0.21
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.43
0.44
0.45
0.46
0.47
0.48
0.49
0.50
0.51
0.52
0.53
0.54
0.55
0.56
0.57
0.58
0.59
0.60
0.61
0.62
0.63
0.64
0.65
0.66
0.67
0.68
0.69
0.70
0.71
0.72
0.73
0.74
0.75
0.76
0.1
2500
2268
2066
1890
1736
1600
1479
1372
1276
1189
1111
1041
977
918
865
816
772
730
693
657
625
595
567
541
517
494
473
453
434
416
400
384
370
356
343
331
319
308
297
287
278
269
260
252
244
237
230
223
216
210
204
198
193
188
183
178
173
0.2
5000
4535
4132
3781
3472
3200
2959
2743
2551
2378
2222
2081
1953
1837
1730
1633
1543
1461
1385
1315
1250
1190
1134
1082
1033
988
945
905
868
833
800
769
740
712
686
661
638
616
595
575
556
537
520
504
488
473
459
446
433
420
408
397
386
375
365
356
346
0.3
0.4
7500 10000
6803 9070
6198 8264
5671 7561
5208 6944
4800 6400
4438 5917
4115 5487
3827 5102
3567 4756
3333 4444
3122 4162
2930 3906
2755 3673
2595 3460
2449 3265
2315 3086
2191 2922
2078 2770
1972 2630
1875 2500
1785 2380
1701 2268
1622 2163
1550 2066
1481 1975
1418 1890
1358 1811
1302 1736
1249 1666
1200 1600
1153 1538
1109 1479
1068 1424
1029 1372
992 1322
957 1276
923 1231
892 1189
862 1149
833 1111
806 1075
780 1041
756 1008
732
977
710
947
689
918
668
891
649
865
630
840
612
816
595
793
579
772
563
751
548
730
533
711
519
693
tg
In
0.77
0.78
0.79
0.80
0.81
0.82
0.83
0.84
0.85
0.86
0.87
0.88
0.89
0.90
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
0.1
169
164
160
156
152
149
145
142
138
135
132
129
126
123
121
118
116
113
111
109
106
104
102
100
0.2
337
329
320
313
305
297
290
283
277
270
264
258
252
247
242
236
231
226
222
217
213
208
204
200
0.3
506
493
481
469
457
446
435
425
415
406
396
387
379
370
362
354
347
340
332
326
319
312
306
300
0.4
675
657
641
625
610
595
581
567
554
541
528
517
505
494
483
473
462
453
443
434
425
416
408
400
Ordering sheet
For faster quote processing, please use the following request for ordering sheet. For each section, check the applicable box or enter value cerresponding to your choice.
Receipt
Contractor
Delivery place
ACB
main body
Distributor name
Order date
Project
Delivery date
Type of ACB
Frame size
Ratings
Rated current (CT)
Trip relay
AH
AN Note 1)
D (630~2000AF) Note 1)
PNL Maker
AS
E (2000~4000AF)
Quantity
F (4000~5000AF)
G (4000~6300AF)
AF
A
NO
YES
Frequency
Type
Control voltage
Comm.
DC
AC/DC
No
100~250V 24~60V
Optional function
Frequency
Earth
External
No Yes leakage CT ground
detection
fault
Type
Control voltage
Optional function
External Pre-Trip
Comm. Earth
DC
AC/DC
leakage CT ground Alarm
100~250V 24~60V
fault
detection
60Hz
50Hz
NGO
NG5
PC1
PC6
AGO
AG5
PC2
PC7
AG1
AG6
PK1
PK6
AG2
AG7
Power
PK2
PK7
AZ0
AZ5
meter
PX1
PX6
AZ1
AZ6
PX2
PX7
AZ2
AZ7
PA1
PA6
AE0
AE5
PA2
PA7
A Ammeter AE1
AE6
SC1
SC6
AE2
AE7
SC2
SC7
AC1
AC6
SK1
SK6
AC2
AC7
Supreme SK2
SK7
AK1
AK6
SX1
SX6
AK2
AK7
SX2
SX7
AX1
AX6
SA1
SA6
AX2
AX7
SA2
SA7
Normal
60Hz
50Hz
meter
3-pole
4-pole
Installation type
Closing type
Draw-out type
Manual closing
Electrical closing
Fixed type
ACB cradle
Closing voltage
Trip voltage
Cradle type
Terminal connection
Connections
Standard
accessory
ACB
Cradle
Standard
accessory
Cradle
mounting
External
mounting
Note) 1. In case of D type of Metasol (AN), frame size is in the range of 630~1600AF
2. The standard accessory for Susol (AH).
3. Aux. contact with extended/high capacity type adopts the rapid auto-reclosing method and available up to 6a6b.
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
HEAD OFFICE
LS-ro 127 (Hogye-dong) Dongan-gu Anyang-si
Gyeonggi-do Korea
Tel. (82-2)2034-4840, 4911, 4914
Fax. (82-2)2034-4648
www.lsis.com
Global Network
LSIS USA Inc.
Chicago, America
Address: 2000 Millbrook Drive, Lincolnshire, Chicago, IL 60069, United States of America
Tel: 847-941-8240 Fax: 847-941-8259 e-mail: seungheonc@lsis.com
CHEONG-JU PLANT
Cheong-Ju Plant #1, 95 Baekbong-ro Heungdeok-gu
Cheongju-si Chungcheongbuk-do 361-720 Korea
2014. 03
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: tangyh@lsis.com.cn
SusolMetasol Air Circuit Breakers (E) 2007. 08/(17) 2014. 03 Printed in Korea STAFF