You are on page 1of 1118

Relion 670 series

Line differential protection RED670


Technical reference manual

Document ID: 1MRK 505 222-UEN


Issued: September 2011
Revision: B
Product version: 1.2

Copyright 2011 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.

Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.

Table of contents

Table of contents
Section 1

Introduction.....................................................................31
Introduction to the technical reference manual.................................31
About the complete set of manuals for an IED............................31
About the technical reference manual.........................................32
This manual.................................................................................33
Introduction.............................................................................33
Principle of operation..............................................................33
Input and output signals.........................................................36
Function block........................................................................36
Setting parameters.................................................................36
Technical data........................................................................37
Intended audience.......................................................................37
Related documents......................................................................37
Revision notes.............................................................................38

Section 2

Analog inputs..................................................................39
Introduction.......................................................................................39
Operation principle...........................................................................39
Function block..................................................................................40
Setting parameters...........................................................................41

Section 3

Local HMI.......................................................................47
Human machine interface ................................................................47
Small size HMI..................................................................................49
Small............................................................................................49
Design.........................................................................................49
Medium size graphic HMI.................................................................51
Medium........................................................................................51
Design.........................................................................................51
Keypad.............................................................................................53
LED...................................................................................................54
Introduction..................................................................................54
Status indication LEDs................................................................54
Indication LEDs...........................................................................54
Local HMI related functions..............................................................55
Introduction..................................................................................55
General setting parameters.........................................................56
Status LEDs.................................................................................56
Design....................................................................................56
Function block........................................................................56
1

Technical reference manual

Table of contents

Input and output signals.........................................................56


Indication LEDs...........................................................................57
Introduction.............................................................................57
Design....................................................................................57
Function block........................................................................64
Input and output signals.........................................................64
Setting parameters.................................................................64

Section 4

Basic IED functions........................................................67


Authorization.....................................................................................67
Principle of operation...................................................................67
Authorization handling in the IED...........................................68
Self supervision with internal event list.............................................69
Introduction..................................................................................69
Principle of operation...................................................................69
Internal signals.......................................................................71
Run-time model......................................................................73
Function block.............................................................................74
Output signals..............................................................................74
Setting parameters......................................................................74
Technical data.............................................................................75
Time synchronization........................................................................75
Introduction..................................................................................75
Principle of operation...................................................................75
General concepts...................................................................75
Real-time clock (RTC) operation............................................78
Synchronization alternatives..................................................79
Process bus IEC 61850-9-2LE synchronization.....................82
Function block.............................................................................82
Output signals..............................................................................82
Setting parameters......................................................................83
Technical data.............................................................................86
Parameter setting groups.................................................................86
Introduction..................................................................................86
Principle of operation...................................................................86
Function block.............................................................................87
Input and output signals..............................................................88
Setting parameters......................................................................88
ChangeLock function CHNGLCK.....................................................88
Introduction..................................................................................89
Principle of operation...................................................................89
Function block.............................................................................89
Input and output signals..............................................................89
Setting parameters......................................................................90

2
Technical reference manual

Table of contents

Test mode functionality TEST..........................................................90


Introduction..................................................................................90
Principle of operation...................................................................90
Function block.............................................................................92
Input and output signals..............................................................92
Setting parameters......................................................................93
IED identifiers...................................................................................93
Introduction..................................................................................93
Setting parameters......................................................................93
Product information..........................................................................94
Introduction..................................................................................94
Setting parameters......................................................................94
Factory defined settings..............................................................94
Signal matrix for binary inputs SMBI................................................95
Introduction..................................................................................95
Principle of operation...................................................................95
Function block.............................................................................95
Input and output signals..............................................................96
Signal matrix for binary outputs SMBO ...........................................96
Introduction..................................................................................96
Principle of operation...................................................................97
Function block.............................................................................97
Input and output signals..............................................................97
Signal matrix for mA inputs SMMI....................................................98
Introduction..................................................................................98
Principle of operation...................................................................98
Function block.............................................................................98
Input and output signals..............................................................98
Signal matrix for analog inputs SMAI...............................................99
Introduction..................................................................................99
Principle of operation...................................................................99
Frequency values........................................................................99
Function block...........................................................................100
Input and output signals............................................................101
Setting parameters....................................................................102
Summation block 3 phase 3PHSUM..............................................104
Introduction................................................................................104
Principle of operation.................................................................104
Function block...........................................................................105
Input and output signals............................................................105
Setting parameters....................................................................105
Authority status ATHSTAT.............................................................106
Introduction................................................................................106
3
Technical reference manual

Table of contents

Principle of operation.................................................................106
Function block...........................................................................106
Output signals............................................................................106
Setting parameters....................................................................107
Denial of service DOS....................................................................107
Introduction................................................................................107
Principle of operation.................................................................107
Function blocks..........................................................................107
Signals.......................................................................................108
Settings......................................................................................108

Section 5

Differential protection...................................................109
Line differential protection..............................................................109
Introduction................................................................................109
Line differential protection, 3 or 6 CT sets L3CPDIF,
L6CPDIF...............................................................................109
Line differential protection 3 or 6 CT sets, with in-zone
transformers LT3CPDIF, LT6CPDIF....................................111
Analog signal transfer for line differential protection............111
Principle of operation.................................................................112
Algorithm and logic...............................................................112
Time synchronization...........................................................118
Analog signal communication for line differential
protection..............................................................................120
Open CT detection feature...................................................123
Binary signal transfer............................................................124
Line differential coordination function LDLPDIF ..................125
Function block...........................................................................125
Input and output signals............................................................127
Setting parameters....................................................................133
Technical data...........................................................................143
1Ph High impedance differential protection HZPDIF .....................143
Identification..............................................................................143
Introduction................................................................................144
Principle of operation.................................................................144
Logic diagram.......................................................................144
Function block...........................................................................145
Input and output signals............................................................145
Setting parameters....................................................................145
Technical data...........................................................................146
Additional security logic for differential protection STSGGIO ........146
Introduction................................................................................146
Principle of operation.................................................................147
Function block...........................................................................151

4
Technical reference manual

Table of contents

Input and output signals............................................................151


Setting parameters....................................................................152
Technical data...........................................................................153

Section 6

Impedance protection ..................................................155


Distance measuring zones, quadrilateral characteristic
ZMQPDIS, ZMQAPDIS, ZDRDIR...................................................155
Identification..............................................................................155
Introduction................................................................................155
Principle of operation.................................................................156
Full scheme measurement...................................................156
Impedance characteristic.....................................................157
Minimum operating current...................................................161
Measuring principles............................................................161
Directional impedance element for quadrilateral
characteristics......................................................................164
Simplified logic diagrams......................................................166
Function block...........................................................................169
Input and output signals............................................................170
Setting parameters....................................................................172
Technical data...........................................................................174
Distance measuring zone, quadrilateral characteristic for
series compensated lines ZMCPDIS, ZMCAPDIS, ZDSRDIR.......174
Introduction................................................................................175
Principle of operation.................................................................176
Full scheme measurement...................................................176
Impedance characteristic.....................................................176
Minimum operating current...................................................180
Measuring principles............................................................180
Directionality for series compensation..................................183
Simplified logic diagrams......................................................185
Function block...........................................................................188
Input and output signals............................................................189
Setting parameters....................................................................191
Technical data...........................................................................194
Phase selection, quadrilateral characteristic with fixed angle
FDPSPDIS......................................................................................194
Identification..............................................................................194
Introduction................................................................................195
Principle of operation.................................................................195
Phase-to-earth fault..............................................................197
Phase-to-phase fault............................................................199
Three-phase faults...............................................................201
Load encroachment..............................................................201
5

Technical reference manual

Table of contents

Minimum operate currents....................................................206


Simplified logic diagrams......................................................206
Function block...........................................................................211
Input and output signals............................................................212
Setting parameters....................................................................213
Technical data...........................................................................214
Full-scheme distance measuring, Mho characteristic
ZMHPDIS ......................................................................................214
Introduction................................................................................214
Principle of operation.................................................................215
Full scheme measurement...................................................215
Impedance characteristic.....................................................216
Basic operation characteristics.............................................217
Theory of operation..............................................................218
Simplified logic diagrams......................................................227
Function block...........................................................................230
Input and output signals............................................................231
Setting parameters....................................................................232
Technical data...........................................................................233
Full-scheme distance protection, quadrilateral for earth faults
ZMMPDIS, ZMMAPDIS..................................................................234
Introduction................................................................................234
Principle of operation.................................................................235
Full scheme measurement...................................................235
Impedance characteristic.....................................................235
Minimum operating current...................................................237
Measuring principles............................................................238
Directional lines....................................................................240
Simplified logic diagrams......................................................242
Function block...........................................................................245
Input and output signals............................................................245
Setting parameters....................................................................246
Technical data...........................................................................248
Directional impedance element for mho characteristic and
additional distance protection directional function for earth
faults ZDMRDIR, ZDARDIR...........................................................248
Introduction................................................................................249
Principle of operation.................................................................249
Directional impedance element for mho characteristic
ZDMRDIR.............................................................................249
Additional distance protection directional function for
earth faults ZDARDIR ..........................................................252
Function block...........................................................................254
Input and output signals............................................................254
6
Technical reference manual

Table of contents

Setting parameters....................................................................255
Mho impedance supervision logic ZSMGAPC................................256
Introduction................................................................................256
Principle of operation.................................................................257
Fault inception detection......................................................257
Function block...........................................................................258
Input and output signals............................................................258
Setting parameters....................................................................259
Faulty phase identification with load encroachment
FMPSPDIS.....................................................................................259
Introduction................................................................................260
Principle of operation.................................................................260
The phase selection function................................................260
Function block...........................................................................271
Input and output signals............................................................272
Setting parameters....................................................................272
Technical data...........................................................................273
Distance protection zone, quadrilateral characteristic, separate
settings ZMRPDIS, ZMRAPDIS and ZDRDIR................................273
Introduction................................................................................274
Principle of operation.................................................................275
Full scheme measurement...................................................275
Impedance characteristic.....................................................275
Minimum operating current...................................................279
Measuring principles............................................................279
Directional impedance element for quadrilateral
characteristics......................................................................282
Simplified logic diagrams......................................................284
Function block...........................................................................287
Input and output signals............................................................288
Setting parameters....................................................................290
Technical data...........................................................................292
Phase selection, quadrilateral characteristic with settable
angle FRPSPDIS............................................................................292
Introduction................................................................................293
Principle of operation.................................................................293
Phase-to-earth fault..............................................................295
Phase-to-phase fault............................................................297
Three-phase faults...............................................................299
Load encroachment..............................................................299
Minimum operate currents....................................................304
Simplified logic diagrams......................................................305
Function block...........................................................................309
Input and output signals............................................................310
7
Technical reference manual

Table of contents

Setting parameters....................................................................311
Technical data...........................................................................312
Power swing detection ZMRPSB ...................................................312
Introduction................................................................................312
Principle of operation.................................................................312
Resistive reach in forward direction.....................................314
Resistive reach in reverse direction.....................................314
Reactive reach in forward and reverse direction..................315
Basic detection logic.............................................................315
Operating and inhibit conditions...........................................318
Function block...........................................................................319
Input and output signals............................................................319
Setting parameters....................................................................320
Technical data...........................................................................321
Power swing logic ZMRPSL ..........................................................321
Introduction................................................................................321
Principle of operation.................................................................321
Communication and tripping logic........................................321
Blocking logic.......................................................................322
Function block...........................................................................324
Input and output signals............................................................324
Setting parameters....................................................................325
Pole slip protection PSPPPAM ......................................................325
Introduction................................................................................325
Principle of operation.................................................................325
Function block...........................................................................329
Input and output signals............................................................329
Setting parameters....................................................................330
Technical data...........................................................................330
Automatic switch onto fault logic, voltage and current based
ZCVPSOF ......................................................................................331
Introduction................................................................................331
Principle of operation.................................................................331
Function block...........................................................................333
Input and output signals............................................................333
Setting parameters....................................................................333
Technical data...........................................................................334
Phase preference logic PPLPHIZ...................................................334
Introduction................................................................................334
Principle of operation.................................................................334
Function block...........................................................................337
Input and output signals............................................................337
Setting parameters....................................................................338
8
Technical reference manual

Table of contents

Section 7

Current protection.........................................................341
Instantaneous phase overcurrent protection PHPIOC ..................341
Introduction................................................................................341
Principle of operation.................................................................341
Function block...........................................................................342
Input and output signals............................................................342
Setting parameters....................................................................342
Technical data...........................................................................343
Four step phase overcurrent protection OC4PTOC ......................343
Introduction................................................................................343
Principle of operation.................................................................343
Function block...........................................................................348
Input and output signals............................................................348
Setting parameters....................................................................350
Technical data...........................................................................355
Instantaneous residual overcurrent protection EFPIOC ................356
Introduction................................................................................356
Principle of operation.................................................................356
Function block...........................................................................357
Input and output signals............................................................357
Setting parameters....................................................................357
Technical data...........................................................................358
Four step residual overcurrent protection EF4PTOC ....................358
Introduction................................................................................358
Principle of operation.................................................................359
Operating quantity within the function..................................359
Internal polarizing.................................................................360
External polarizing for earth-fault function............................362
Base quantities within the protection....................................362
Internal earth-fault protection structure................................362
Four residual overcurrent steps............................................363
Directional supervision element with integrated
directional comparison function............................................364
Second harmonic blocking element.....................................366
Switch on to fault feature......................................................368
Function block...........................................................................370
Input and output signals............................................................371
Setting parameters....................................................................372
Technical data...........................................................................377
Four step directional negative phase sequence overcurrent
protection NS4PTOC .....................................................................377
Introduction................................................................................378
Principle of operation.................................................................378
9

Technical reference manual

Table of contents

Operating quantity within the function..................................378


Internal polarizing facility of the function..............................379
External polarizing for negative sequence function..............380
Base quantities within the function.......................................380
Internal negative sequence protection structure..................381
Four negative sequence overcurrent stages........................381
Directional supervision element with integrated
directional comparison function............................................382
Function block...........................................................................385
Input and output signals............................................................385
Setting parameters....................................................................386
Technical data...........................................................................391
Sensitive directional residual overcurrent and power protection
SDEPSDE .....................................................................................391
Introduction................................................................................391
Principle of operation.................................................................393
Function inputs.....................................................................393
Function block...........................................................................399
Input and output signals............................................................400
Setting parameters....................................................................401
Technical data...........................................................................403
Thermal overload protection, one time constant LPTTR ...............404
Introduction................................................................................404
Principle of operation.................................................................404
Function block...........................................................................407
Input and output signals............................................................407
Setting parameters....................................................................407
Technical data...........................................................................408
Breaker failure protection CCRBRF ..............................................408
Introduction................................................................................409
Principle of operation.................................................................409
Function block...........................................................................412
Input and output signals............................................................413
Setting parameters....................................................................413
Technical data...........................................................................414
Stub protection STBPTOC ............................................................415
Introduction................................................................................415
Principle of operation.................................................................415
Function block...........................................................................416
Input and output signals............................................................416
Setting parameters....................................................................417
Technical data...........................................................................417
Pole discordance protection CCRPLD ..........................................417
Introduction................................................................................418
10
Technical reference manual

Table of contents

Principle of operation.................................................................418
Pole discordance signaling from circuit breaker...................421
Unsymmetrical current detection..........................................421
Function block...........................................................................421
Input and output signals............................................................422
Setting parameters....................................................................422
Technical data...........................................................................423
Directional underpower protection GUPPDUP...............................423
Introduction................................................................................423
Principle of operation.................................................................424
Low pass filtering..................................................................426
Calibration of analog inputs..................................................426
Function block...........................................................................427
Input and output signals............................................................428
Setting parameters....................................................................428
Technical data...........................................................................429
Directional overpower protection GOPPDOP ................................430
Introduction................................................................................430
Principle of operation.................................................................431
Low pass filtering..................................................................433
Calibration of analog inputs..................................................433
Function block...........................................................................434
Input and output signals............................................................435
Setting parameters....................................................................435
Technical data...........................................................................437
Broken conductor check BRCPTOC .............................................437
Introduction................................................................................437
Principle of operation.................................................................437
Function block...........................................................................438
Input and output signals............................................................439
Setting parameters....................................................................439
Technical data...........................................................................439

Section 8

Voltage protection........................................................441
Two step undervoltage protection UV2PTUV ................................441
Introduction................................................................................441
Principle of operation.................................................................441
Measurement principle.........................................................442
Time delay............................................................................442
Blocking................................................................................447
Design..................................................................................448
Function block...........................................................................450
Input and output signals............................................................450
Setting parameters....................................................................451
11

Technical reference manual

Table of contents

Technical data...........................................................................453
Two step overvoltage protection OV2PTOV ..................................454
Introduction................................................................................454
Principle of operation.................................................................454
Measurement principle.........................................................455
Time delay............................................................................455
Blocking................................................................................461
Design..................................................................................461
Function block...........................................................................463
Input and output signals............................................................463
Setting parameters....................................................................464
Technical data...........................................................................466
Two step residual overvoltage protection ROV2PTOV .................466
Introduction................................................................................466
Principle of operation.................................................................467
Measurement principle.........................................................467
Time delay............................................................................467
Blocking................................................................................472
Design..................................................................................472
Function block...........................................................................473
Input and output signals............................................................474
Setting parameters....................................................................474
Technical data...........................................................................476
Overexcitation protection OEXPVPH ............................................476
Introduction................................................................................476
Principle of operation.................................................................477
Measured voltage.................................................................479
Operate time of the overexcitation protection.......................480
Cooling.................................................................................484
Overexcitation protection function measurands...................484
Overexcitation alarm............................................................485
Logic diagram.......................................................................485
Function block...........................................................................486
Input and output signals............................................................486
Setting parameters....................................................................486
Technical data...........................................................................488
Voltage differential protection VDCPTOV ......................................488
Introduction................................................................................488
Principle of operation.................................................................488
Function block...........................................................................490
Input and output signals............................................................490
Setting parameters....................................................................490
Technical data...........................................................................491
12
Technical reference manual

Table of contents

Loss of voltage check LOVPTUV ..................................................491


Introduction................................................................................491
Principle of operation.................................................................492
Function block...........................................................................493
Input and output signals............................................................494
Setting parameters....................................................................494
Technical data...........................................................................494

Section 9

Frequency protection....................................................495
Underfrequency protection SAPTUF .............................................495
Introduction................................................................................495
Principle of operation.................................................................495
Measurement principle.........................................................496
Time delay............................................................................496
Voltage dependent time delay..............................................496
Blocking................................................................................498
Design..................................................................................498
Function block...........................................................................499
Input and output signals............................................................499
Setting parameters....................................................................499
Technical data...........................................................................500
Overfrequency protection SAPTOF ...............................................500
Introduction................................................................................501
Principle of operation.................................................................501
Measurement principle.........................................................501
Time delay............................................................................501
Blocking................................................................................502
Design..................................................................................502
Function block...........................................................................503
Input and output signals............................................................503
Setting parameters....................................................................503
Technical data...........................................................................504
Rate-of-change frequency protection SAPFRC .............................504
Introduction................................................................................504
Principle of operation.................................................................504
Measurement principle.........................................................505
Time delay............................................................................505
Blocking................................................................................505
Design..................................................................................506
Function block...........................................................................507
Input and output signals............................................................507
Setting parameters....................................................................507
Technical data...........................................................................508

13
Technical reference manual

Table of contents

Section 10 Multipurpose protection................................................509


General current and voltage protection CVGAPC..........................509
Introduction................................................................................509
Principle of operation.................................................................509
Measured quantities within CVGAPC...................................509
Base quantities for CVGAPC function..................................512
Built-in overcurrent protection steps.....................................512
Built-in undercurrent protection steps...................................517
Built-in overvoltage protection steps....................................518
Built-in undervoltage protection steps..................................518
Logic diagram.......................................................................518
Function block...........................................................................523
Input and output signals............................................................524
Setting parameters....................................................................525
Technical data...........................................................................533

Section 11 Secondary system supervision.....................................535


Current circuit supervision CCSRDIF ............................................535
Introduction................................................................................535
Principle of operation.................................................................535
Function block...........................................................................537
Input and output signals............................................................537
Setting parameters....................................................................538
Technical data...........................................................................538
Fuse failure supervision SDDRFUF...............................................538
Introduction................................................................................538
Principle of operation.................................................................539
Zero and negative sequence detection................................539
Delta current and delta voltage detection.............................543
Dead line detection...............................................................545
Main logic.............................................................................545
Function block...........................................................................549
Input and output signals............................................................549
Setting parameters....................................................................549
Technical data...........................................................................550

Section 12 Control..........................................................................553
Synchrocheck, energizing check, and synchronizing
SESRSYN......................................................................................553
Introduction................................................................................553
Principle of operation.................................................................554
Basic functionality.................................................................554
Logic diagrams.....................................................................554
14
Technical reference manual

Table of contents

Function block...........................................................................563
Input and output signals............................................................563
Setting parameters....................................................................566
Technical data...........................................................................569
Autorecloser SMBRREC ...............................................................569
Introduction................................................................................570
Principle of operation.................................................................570
Logic Diagrams....................................................................570
Auto-reclosing operation Off and On....................................570
Auto-reclosing mode selection.............................................570
Start auto-reclosing and conditions for start of a
reclosing cycle......................................................................571
Control of the auto-reclosing open time for shot 1...............572
Long trip signal.....................................................................572
Time sequence diagrams.....................................................579
Function block...........................................................................582
Input and output signals............................................................582
Setting parameters....................................................................584
Technical data...........................................................................586
Apparatus control APC...................................................................586
Introduction................................................................................586
Principle of operation.................................................................586
Error handling............................................................................587
Bay control QCBAY...................................................................589
Introduction...........................................................................589
Principle of operation............................................................589
Function block......................................................................591
Input and output signals.......................................................591
Setting parameters...............................................................592
Local/Remote switch.................................................................592
Introduction...........................................................................592
Principle of operation............................................................592
Function block......................................................................594
Input and output signals.......................................................594
Setting parameters...............................................................595
Switch controller SCSWI...........................................................595
Introduction...........................................................................596
Principle of operation............................................................596
Function block......................................................................601
Input and output signals.......................................................601
Setting parameters...............................................................602
Circuit breaker SXCBR..............................................................602
Introduction...........................................................................603
15
Technical reference manual

Table of contents

Principle of operation............................................................603
Function block......................................................................607
Input and output signals.......................................................607
Setting parameters...............................................................608
Circuit switch SXSWI.................................................................608
Introduction...........................................................................608
Principle of operation............................................................608
Function block......................................................................612
Input and output signals.......................................................612
Setting parameters...............................................................613
Bay reserve QCRSV..................................................................613
Introduction...........................................................................614
Principle of operation............................................................614
Function block......................................................................616
Input and output signals.......................................................617
Setting parameters...............................................................618
Reservation input RESIN...........................................................618
Introduction...........................................................................618
Principle of operation............................................................618
Function block......................................................................620
Input and output signals.......................................................621
Setting parameters...............................................................622
Interlocking ....................................................................................622
Introduction................................................................................622
Principle of operation.................................................................622
Logical node for interlocking SCILO .........................................625
Introduction...........................................................................625
Logic diagram.......................................................................625
Function block......................................................................626
Input and output signals.......................................................626
Interlocking for busbar earthing switch BB_ES .........................626
Introduction...........................................................................627
Function block......................................................................627
Logic diagram.......................................................................627
Input and output signals.......................................................627
Interlocking for bus-section breaker A1A2_BS..........................628
Introduction...........................................................................628
Function block......................................................................629
Logic diagram.......................................................................630
Input and output signals.......................................................631
Interlocking for bus-section disconnector A1A2_DC ................632
Introduction...........................................................................633
Function block......................................................................633
16
Technical reference manual

Table of contents

Logic diagram.......................................................................634
Input and output signals.......................................................634
Interlocking for bus-coupler bay ABC_BC ................................635
Introduction...........................................................................635
Function block......................................................................636
Logic diagram.......................................................................637
Input and output signals.......................................................639
Interlocking for 1 1/2 CB BH .....................................................642
Introduction...........................................................................642
Function blocks....................................................................643
Logic diagrams.....................................................................645
Input and output signals.......................................................650
Interlocking for double CB bay DB ...........................................654
Introduction...........................................................................654
Function block......................................................................655
Logic diagrams.....................................................................657
Input and output signals ......................................................660
Interlocking for line bay ABC_LINE ..........................................663
Introduction...........................................................................663
Function block......................................................................664
Logic diagram.......................................................................665
Input and output signals.......................................................670
Interlocking for transformer bay AB_TRAFO ............................672
Introduction...........................................................................673
Function block......................................................................674
Logic diagram.......................................................................675
Input and output signals.......................................................676
Position evaluation POS_EVAL.................................................678
Introduction...........................................................................678
Logic diagram.......................................................................678
Function block......................................................................679
Input and output signals.......................................................679
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................679
Introduction................................................................................679
Principle of operation.................................................................679
Functionality and behaviour ................................................681
Graphical display..................................................................681
Function block...........................................................................683
Input and output signals............................................................683
Setting parameters....................................................................684
Selector mini switch VSGGIO.........................................................685
Introduction................................................................................685
17
Technical reference manual

Table of contents

Principle of operation.................................................................685
Function block...........................................................................686
Input and output signals............................................................686
Setting parameters....................................................................687
Generic double point function block DPGGIO................................687
Introduction................................................................................687
Principle of operation.................................................................687
Function block...........................................................................688
Input and output signals............................................................688
Settings......................................................................................688
Single point generic control 8 signals SPC8GGIO.........................688
Introduction................................................................................688
Principle of operation.................................................................689
Function block...........................................................................689
Input and output signals............................................................689
Setting parameters....................................................................690
AutomationBits, command function for DNP3.0 AUTOBITS..........690
Introduction................................................................................691
Principle of operation.................................................................691
Function block...........................................................................692
Input and output signals............................................................692
Setting parameters....................................................................693
Single command, 16 signals SINGLECMD....................................707
Introduction................................................................................707
Principle of operation.................................................................707
Function block...........................................................................708
Input and output signals............................................................708
Setting parameters....................................................................709

Section 13 Scheme communication...............................................711


Scheme communication logic for distance or overcurrent
protection ZCPSCH .......................................................................711
Introduction................................................................................711
Principle of operation.................................................................712
Blocking scheme..................................................................712
Permissive underreaching scheme......................................712
Permissive overreaching scheme........................................713
Unblocking scheme..............................................................713
Intertrip scheme....................................................................714
Simplified logic diagram.......................................................714
Function block...........................................................................716
Input and output signals............................................................716
Setting parameters....................................................................717
Technical data...........................................................................717
18
Technical reference manual

Table of contents

Phase segregated scheme communication logic for distance


protection ZC1PPSCH ...................................................................718
Introduction................................................................................718
Principle of operation.................................................................718
Blocking scheme..................................................................719
Permissive underreach scheme...........................................719
Permissive overreach scheme.............................................720
Unblocking scheme..............................................................720
Intertrip scheme....................................................................720
Simplified logic diagram.......................................................721
Function block...........................................................................722
Input and output signals............................................................722
Setting parameters....................................................................724
Technical data...........................................................................724
Current reversal and weak-end infeed logic for distance
protection ZCRWPSCH .................................................................724
Introduction................................................................................724
Principle of operation.................................................................725
Current reversal logic...........................................................725
Weak-end infeed logic..........................................................725
Function block...........................................................................727
Input and output signals............................................................727
Setting parameters....................................................................728
Technical data...........................................................................728
Local acceleration logic ZCLCPLAL...............................................728
Introduction................................................................................729
Principle of operation.................................................................729
Zone extension.....................................................................729
Loss-of-Load acceleration....................................................730
Function block...........................................................................730
Input and output signals............................................................731
Setting parameters....................................................................731
Scheme communication logic for residual overcurrent
protection ECPSCH .......................................................................732
Introduction................................................................................732
Principle of operation.................................................................732
Blocking scheme..................................................................733
Permissive under/overreaching scheme..............................733
Unblocking scheme..............................................................735
Function block...........................................................................736
Input and output signals............................................................737
Setting parameters....................................................................737
Technical data...........................................................................738

19
Technical reference manual

Table of contents

Current reversal and weak-end infeed logic for residual


overcurrent protection ECRWPSCH...............................................738
Introduction................................................................................738
Principle of operation.................................................................739
Directional comparison logic function...................................739
Fault current reversal logic...................................................739
Weak-end infeed logic..........................................................740
Function block...........................................................................741
Input and output signals............................................................741
Setting parameters....................................................................742
Technical data...........................................................................742
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH ......................................743
Introduction................................................................................743
Principle of operation.................................................................743
Current reversal logic ..........................................................743
Function block...........................................................................745
Input and output signals............................................................746
Setting parameters....................................................................747
Technical data...........................................................................747
Direct transfer trip logic...................................................................747
Introduction................................................................................748
Low active power and power factor protection LAPPGAPC......749
Introduction...........................................................................749
Principle of operation............................................................750
Function block......................................................................752
Input and output signals.......................................................752
Setting parameters...............................................................753
Technical data......................................................................753
Compensated over and undervoltage protection
COUVGAPC..............................................................................754
Introduction...........................................................................754
Principle of operation............................................................754
Function block......................................................................756
Input and output signals.......................................................756
Setting parameters...............................................................757
Technical data......................................................................758
Sudden change in current variation SCCVPTOC......................758
Introduction...........................................................................759
Principle of operation............................................................759
Function block......................................................................760
Input and output signals.......................................................760
Setting parameters...............................................................760
Technical data......................................................................761
20
Technical reference manual

Table of contents

Carrier receive logic LCCRPTRC..............................................761


Introduction...........................................................................761
Principle of operation............................................................761
Function block......................................................................762
Input and output signals.......................................................762
Setting parameters...............................................................763
Technical data......................................................................763
Negative sequence overvoltage protection LCNSPTOV...........763
Introduction...........................................................................763
Principle of operation............................................................763
Function block......................................................................764
Input and output signals.......................................................764
Setting parameters...............................................................764
Technical data......................................................................765
Zero sequence overvoltage protection LCZSPTOV..................765
Introduction...........................................................................765
Principle of operation............................................................765
Function block......................................................................766
Input and output signals.......................................................766
Setting parameters...............................................................766
Technical data......................................................................767
Negative sequence overcurrent protection LCNSPTOC...........767
Introduction...........................................................................767
Principle of operation............................................................767
Function block......................................................................768
Input and output signals.......................................................768
Setting parameters...............................................................768
Technical data......................................................................769
Zero sequence overcurrent protection LCZSPTOC..................769
Introduction...........................................................................769
Principle of operation............................................................769
Function block......................................................................770
Input and output signals.......................................................770
Setting parameters...............................................................770
Technical data......................................................................771
Three phase overcurrent LCP3PTOC.......................................771
Introduction...........................................................................771
Principle of operation............................................................771
Function block......................................................................772
Input and output signals.......................................................772
Setting parameters...............................................................773
Technical data......................................................................773
Three phase undercurrent LCP3PTUC.....................................773
21
Technical reference manual

Table of contents

Introduction...........................................................................773
Principle of operation............................................................774
Function block......................................................................774
Input and output signals.......................................................774
Setting parameters...............................................................775
Technical data......................................................................775

Section 14 Logic.............................................................................777
Tripping logic SMPPTRC ...............................................................777
Introduction................................................................................777
Principle of operation.................................................................777
Logic diagram.......................................................................779
Function block...........................................................................782
Input and output signals............................................................782
Setting parameters....................................................................783
Technical data...........................................................................784
Trip matrix logic TMAGGIO............................................................784
Introduction................................................................................784
Principle of operation.................................................................784
Function block...........................................................................786
Input and output signals............................................................786
Setting parameters....................................................................787
Configurable logic blocks................................................................788
Introduction................................................................................788
Inverter function block INV........................................................788
OR function block OR................................................................789
AND function block AND...........................................................790
Timer function block TIMER......................................................790
Pulse timer function block PULSETIMER..................................791
Exclusive OR function block XOR.............................................791
Loop delay function block LOOPDELAY...................................792
Set-reset with memory function block SRMEMORY.................792
Reset-set with memory function block RSMEMORY.................793
Controllable gate function block GATE......................................794
Settable timer function block TIMERSET..................................795
Technical data...........................................................................796
Fixed signal function block FXDSIGN............................................796
Principle of operation.................................................................796
Function block...........................................................................797
Input and output signals............................................................797
Setting parameters....................................................................797
Boolean 16 to Integer conversion B16I..........................................798
Introduction................................................................................798
Principle of operation.................................................................798
22
Technical reference manual

Table of contents

Function block...........................................................................798
Input and output signals............................................................798
Setting parameters....................................................................799
Boolean 16 to Integer conversion with logic node
representation B16IFCVI................................................................799
Introduction................................................................................799
Principle of operation.................................................................800
Function block...........................................................................800
Input and output signals............................................................800
Setting parameters....................................................................801
Integer to Boolean 16 conversion IB16..........................................801
Introduction................................................................................801
Principle of operation.................................................................801
Function block...........................................................................802
Input and output signals............................................................802
Setting parameters....................................................................803
Integer to Boolean 16 conversion with logic node
representation IB16FCVB...............................................................803
Introduction................................................................................803
Principle of operation.................................................................803
Function block...........................................................................804
Input and output signals............................................................804
Setting parameters....................................................................805

Section 15 Monitoring.....................................................................807
Measurements................................................................................807
Introduction................................................................................808
Principle of operation.................................................................809
Measurement supervision....................................................809
Measurements CVMMXN.....................................................813
Phase current measurement CMMXU.................................818
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU..............................................................819
Voltage and current sequence measurements VMSQI,
CMSQI..................................................................................819
Function block...........................................................................819
Input and output signals............................................................821
Setting parameters....................................................................824
Technical data...........................................................................837
Event counter CNTGGIO................................................................837
Identification..............................................................................837
Introduction................................................................................837
Principle of operation.................................................................838
Reporting..............................................................................838
23
Technical reference manual

Table of contents

Design..................................................................................838
Function block...........................................................................839
Input signals..............................................................................839
Setting parameters....................................................................839
Technical data...........................................................................840
Event function EVENT....................................................................840
Introduction................................................................................840
Principle of operation.................................................................840
Function block...........................................................................842
Input and output signals............................................................842
Setting parameters....................................................................843
Logical signal status report BINSTATREP.....................................845
Introduction................................................................................845
Principle of operation.................................................................845
Function block...........................................................................846
Input and output signals............................................................846
Setting parameters....................................................................847
Fault locator LMBRFLO..................................................................847
Introduction................................................................................848
Principle of operation.................................................................848
Measuring Principle..............................................................849
Accurate algorithm for measurement of distance to fault.....849
The non-compensated impedance model............................853
IEC 60870-5-103..................................................................854
Function block...........................................................................854
Input and output signals............................................................854
Setting parameters....................................................................855
Technical data...........................................................................856
Measured value expander block RANGE_XP................................856
Introduction................................................................................856
Principle of operation.................................................................856
Function block...........................................................................857
Input and output signals............................................................857
Disturbance report DRPRDRE.......................................................857
Introduction................................................................................858
Principle of operation.................................................................858
Function block...........................................................................865
Input and output signals............................................................867
Setting parameters....................................................................868
Technical data...........................................................................878
Event list.........................................................................................878
Introduction................................................................................878
Principle of operation.................................................................878
24
Technical reference manual

Table of contents

Function block...........................................................................879
Input signals..............................................................................879
Technical data...........................................................................879
Indications......................................................................................879
Introduction................................................................................879
Principle of operation.................................................................880
Function block...........................................................................881
Input signals..............................................................................881
Technical data...........................................................................881
Event recorder ...............................................................................881
Introduction................................................................................881
Principle of operation.................................................................881
Function block...........................................................................882
Input signals..............................................................................882
Technical data...........................................................................882
Trip value recorder.........................................................................882
Introduction................................................................................882
Principle of operation.................................................................883
Function block...........................................................................883
Input signals..............................................................................884
Technical data...........................................................................884
Disturbance recorder......................................................................884
Introduction................................................................................884
Principle of operation.................................................................884
Memory and storage............................................................885
IEC 60870-5-103..................................................................886
Function block...........................................................................887
Input and output signals............................................................887
Setting parameters....................................................................887
Technical data...........................................................................887

Section 16 Metering.......................................................................889
Pulse-counter logic PCGGIO..........................................................889
Introduction................................................................................889
Principle of operation.................................................................889
Function block...........................................................................891
Input and output signals............................................................892
Setting parameters....................................................................892
Technical data...........................................................................893
Function for energy calculation and demand handling
ETPMMTR......................................................................................893
Introduction................................................................................893
Principle of operation.................................................................893
Function block...........................................................................894
25
Technical reference manual

Table of contents

Input and output signals............................................................894


Setting parameters....................................................................895

Section 17 Station communication.................................................897


Overview.........................................................................................897
IEC 61850-8-1 communication protocol.........................................897
Introduction................................................................................897
Setting parameters....................................................................898
Technical data...........................................................................898
IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO................................................................................898
Introduction...........................................................................898
Principle of operation............................................................898
Function block......................................................................898
Input and output signals.......................................................899
Setting parameters...............................................................900
IEC 61850 generic communication I/O functions MVGGIO.......900
Principle of operation............................................................900
Function block......................................................................900
Input and output signals.......................................................900
Setting parameters...............................................................901
IEC 61850-8-1 redundant station bus communication..............901
Introduction...........................................................................901
Principle of operation............................................................901
Function block......................................................................903
Output signals......................................................................903
Setting parameters...............................................................903
IEC 61850-9-2LE communication protocol.....................................903
Introduction................................................................................903
Principle of operation.................................................................903
Consequence on accuracy for power measurement
functions when using signals from IEC 61850-9-2LE
communication..........................................................................906
Function block...........................................................................907
Output signals............................................................................907
Setting parameters....................................................................908
Technical data...........................................................................908
LON communication protocol.........................................................908
Introduction................................................................................908
Principle of operation.................................................................909
Setting parameters....................................................................927
Technical data...........................................................................927
SPA communication protocol.........................................................927
Introduction................................................................................927
26
Technical reference manual

Table of contents

Principle of operation.................................................................928
Communication ports...........................................................935
Design.......................................................................................935
Setting parameters....................................................................936
Technical data...........................................................................936
IEC 60870-5-103 communication protocol.....................................936
Introduction................................................................................936
Principle of operation.................................................................936
General.................................................................................936
Communication ports...........................................................946
Function block...........................................................................946
Input and output signals............................................................949
Setting parameters....................................................................954
Technical data...........................................................................957
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV.........................................................................957
Function block...........................................................................957
Input and output signals............................................................958
Setting parameters....................................................................959
Goose binary receive GOOSEBINRCV..........................................960
Function block...........................................................................960
Input and output signals............................................................960
Setting parameters....................................................................961
Multiple command and transmit MULTICMDRCV,
MULTICMDSND.............................................................................961
Introduction................................................................................962
Principle of operation.................................................................962
Design.......................................................................................962
General.................................................................................962
Function block...........................................................................963
Input and output signals............................................................964
Setting parameters....................................................................965

Section 18 Remote communication................................................967


Binary signal transfer......................................................................967
Introduction................................................................................967
Principle of operation.................................................................967
Function block...........................................................................969
Input and output signals............................................................969
Setting parameters....................................................................971
Transmission of analog data from LDCM LDCMTransmit..............974
Function block...........................................................................974
Input and output signals............................................................974

27
Technical reference manual

Table of contents

Section 19 IED hardware...............................................................975


Overview.........................................................................................975
Variants of case and local HMI display size..............................975
Case from the rear side.............................................................978
Hardware modules.........................................................................982
Overview....................................................................................982
Combined backplane module (CBM).........................................983
Introduction...........................................................................983
Functionality.........................................................................983
Design..................................................................................984
Universal backplane module (UBM)..........................................986
Introduction...........................................................................986
Functionality.........................................................................986
Design..................................................................................986
Numeric processing module (NUM)..........................................988
Introduction...........................................................................988
Functionality.........................................................................988
Block diagram.......................................................................989
Power supply module (PSM).....................................................990
Introduction...........................................................................990
Design..................................................................................990
Technical data......................................................................990
Local human-machine interface (Local HMI).............................991
Transformer input module (TRM)..............................................991
Introduction...........................................................................991
Design..................................................................................991
Technical data......................................................................992
Analog digital conversion module, with time
synchronization (ADM) .............................................................993
Introduction...........................................................................993
Design..................................................................................993
Binary input module (BIM).........................................................995
Introduction...........................................................................995
Design..................................................................................995
Technical data......................................................................999
Binary output modules (BOM)...................................................999
Introduction...........................................................................999
Design..................................................................................999
Technical data....................................................................1001
Static binary output module (SOM).........................................1002
Introduction.........................................................................1002
Design................................................................................1002
Technical data....................................................................1004
28
Technical reference manual

Table of contents

Binary input/output module (IOM)............................................1005


Introduction.........................................................................1005
Design................................................................................1006
Technical data....................................................................1008
mA input module (MIM)...........................................................1009
Introduction.........................................................................1009
Design................................................................................1009
Technical data....................................................................1010
Serial and LON communication module (SLM) ......................1011
Introduction.........................................................................1011
Design................................................................................1011
Technical data....................................................................1012
Galvanic RS485 communication module.................................1013
Introduction.........................................................................1013
Design................................................................................1013
Technical data....................................................................1015
Optical ethernet module (OEM)...............................................1015
Introduction.........................................................................1015
Functionality.......................................................................1015
Design................................................................................1015
Technical data....................................................................1016
Line data communication module (LDCM)..............................1016
Introduction.........................................................................1016
Design................................................................................1017
Technical data....................................................................1018
Galvanic X.21 line data communication (X.21-LDCM)............1019
Introduction.........................................................................1019
Design................................................................................1019
Functionality.......................................................................1021
Technical data....................................................................1022
GPS time synchronization module (GTM)...............................1022
Introduction.........................................................................1022
Design................................................................................1022
Technical data....................................................................1023
GPS antenna...........................................................................1023
Introduction.........................................................................1023
Design................................................................................1023
Technical data....................................................................1025
IRIG-B time synchronization module IRIG-B...........................1026
Introduction.........................................................................1026
Design................................................................................1026
Technical data....................................................................1027
Dimensions...................................................................................1028
29
Technical reference manual

Table of contents

Case without rear cover...........................................................1028


Case with rear cover................................................................1030
Flush mounting dimensions.....................................................1032
Side-by-side flush mounting dimensions.................................1033
Wall mounting dimensions.......................................................1034
External resistor unit for high impedance differential
protection.................................................................................1034
Mounting alternatives...................................................................1035
Flush mounting........................................................................1035
Overview............................................................................1035
Mounting procedure for flush mounting..............................1037
19 panel rack mounting..........................................................1038
Overview............................................................................1038
Mounting procedure for 19 panel rack mounting...............1039
Wall mounting..........................................................................1039
Overview............................................................................1039
Mounting procedure for wall mounting...............................1040
How to reach the rear side of the IED................................1041
Side-by-side 19 rack mounting...............................................1041
Overview............................................................................1041
Mounting procedure for side-by-side rack mounting..........1042
IED in the 670 series mounted with a RHGS6 case...........1042
Side-by-side flush mounting....................................................1043
Overview............................................................................1043
Mounting procedure for side-by-side flush mounting.........1044
Technical data..............................................................................1044
Enclosure.................................................................................1044
Connection system..................................................................1045
Influencing factors...................................................................1045
Type tests according to standard............................................1046

Section 20 Labels.........................................................................1049
Labels on IED...............................................................................1049

Section 21 Connection diagrams.................................................1053


Section 22 Inverse time characteristics........................................1069
Application....................................................................................1069
Principle of operation....................................................................1072
Mode of operation....................................................................1072
Inverse characteristics..................................................................1077

Section 23 Glossary.....................................................................1103

30
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

Section 1

Introduction

About this chapter


This chapter explains concepts and conventions used in this manual and provides
information necessary to understand the contents of the manual.

1.1

Introduction to the technical reference manual

1.1.1

About the complete set of manuals for an IED

Decommissioning
deinstalling & disposal

Maintenance

Operation

Commissioning

Installing

Engineering

Planning & purchase

The users manual (UM) is a complete set of five different manuals:

Engineeringmanual
Installation and
Commissioning manual
Operators manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN

The Application Manual (AM) contains application descriptions, setting


guidelines and setting parameters sorted per function. The application manual
should be used to find out when and for what purpose a typical protection function
could be used. The manual should also be used when calculating settings.
The Technical Reference Manual (TRM) contains application and functionality
descriptions and it lists function blocks, logic diagrams, input and output signals,
setting parameters and technical data sorted per function. The technical reference
31
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

manual should be used as a technical reference during the engineering phase,


installation and commissioning phase, and during normal service.
The Installation and Commissioning Manual (ICM) contains instructions on
how to install and commission the protection IED. The manual can also be used as
a reference during periodic testing. The manual covers procedures for mechanical
and electrical installation, energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in the chronological order (indicated by chapter/section
numbers) in which the protection IED should be installed and commissioned.
The Operators Manual (OM) contains instructions on how to operate the
protection IED during normal service once it has been commissioned. The
operators manual can be used to find out how to handle disturbances or how to
view calculated and measured network data in order to determine the cause of a fault.
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.

1.1.2

About the technical reference manual


The following chapters are included in the technical reference manual.

Local HMI describes the control panel on the IED and explains display
characteristics, control keys and various local HMI features.
Basic IED functions presents functions for all protection types that are
included in all IEDs, for example, time synchronization, self supervision with
event list, test mode and other general functions.
Differential protection describes differential functions and restricted earth fault
protection.
Impedance protection describes functions for distance zones with their
quadrilateral characteristics, phase selection with load encroachment, power
swing detection and similar.
Current protection describes functions, for example, over current protection,
breaker failure protection and pole discordance.
Voltage protection describes functions for under voltage and over voltage
protection and residual over voltage protection.
Frequency protection describes functions for over frequency, under frequency
and rate of change of frequency protection.
Multipurpose protection describes the general protection function for current
and voltage.
Secondary system supervision describes current based functions for current
circuit supervision and fuse failure supervision.
Control describes control functions, for example, synchronization and
energizing check and other product specific functions.
Scheme communication describes functions related to current reversal and
weak end infeed logic.

32
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

1.1.3

Logic describes trip logic and related functions.


Monitoring describes measurement related functions that are used to provide
data regarding relevant quantities, events and faults, for example.
Metering describes pulse counter logic.
Station communication describes Ethernet based communication in general,
including the use of IEC 61850 and horizontal communication via GOOSE.
Remote communication describes binary and analog signal transfer, and the
associated hardware.
Hardware describes the IED and its components.
Connection diagrams provides terminal wiring diagrams and information
regarding connections to and from the IED.
Inverse time characteristics describes and explains inverse time delay, inverse
time curves and their effects.
Glossary is a list of terms, acronyms and abbreviations used in ABB technical
documentation.

This manual
The description of each IED related function follows the same structure (where
applicable). The different sections are outlined below.

1.1.3.1

Introduction
Outlines the implementation of a particular protection function.

1.1.3.2

Principle of operation
Describes how the function works, presents a general background to algorithms
and measurement techniques. Logic diagrams are used to illustrate functionality.

Logic diagrams

Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.
Signal names
Input and output logic signals consist of two groups of letters separated by two
dashes. The first group consists of up to four letters and presents the abbreviated
name for the corresponding function. The second group presents the functionality
of the particular signal. According to this explanation, the meaning of the signal
BLKTR in figure 4 is as follows:

BLKTR informs the user that the signal will BLOCK the TRIP command from
the under-voltage function, when its value is a logical one (1).

Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed.

33
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

Input and output signals


In a logic diagram, input and output signal paths are shown as a lines that touch the
outer border of the diagram.
Input and output signals can be configured using the ACT tool. They can be
connected to the inputs and outputs of other functions and to binary inputs and
outputs. Examples of input signals are BLKTR, BLOCK and VTSU. Examples
output signals are TRIP, START, STL1, STL2, STL3.
Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their
values are high (1) only when the corresponding setting parameter is set to the
symbolic value specified within the frame. Example is the signal Block TUV=Yes.
Their logical values correspond automatically to the selected setting value.
Internal signals
Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts and
continues, see figure 1.
BLKTR
TEST
TEST

&

Block TUV=Yes

>1

BLOCK-int.

BLOCK
VTSU
BLOCK-int.
STUL1N

&

BLOCK-int.
&

STUL2N
BLOCK-int.
STUL3N

&

>1

&

TRIP
START
STL1
STL2
STL3

xx04000375.vsd
IEC04000375 V1 EN

Figure 1:

Logic diagram example with -int signals

34
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix -cont., see figure 2 and figure 3.
STZMPP-cont.

>1

STCND

STNDL1L2-cont.

&

1L1L2

STNDL2L3-cont.

&

1L2L3
1L3L1
1L1N
1L2N

&

STNDL3L1-cont.

&

STNDL1N-cont.

&

STNDL2N-cont.
STNDL3N-cont.

&

1L3N

STNDPE-cont.

>1

>1
1--VTSZ

&

>1

1--BLOCK

1--STND
BLK-cont.
xx04000376.vsd

IEC04000376 V1 EN

Figure 2:

Logic diagram example with an outgoing -cont signal

STNDL1N-cont.

>1

STNDL2N-cont.
STNDL3N-cont.
STNDL1L2-cont.

>1

&

15 ms
t

STL1

&

15 ms
t

STL2

&

15 ms
t

STL3

&

15 ms
t

START

STNDL2L3-cont.
STNDL3L1-cont.

>1
>1

BLK-cont.
xx04000377.vsd
IEC04000377 V1 EN

Figure 3:

Logic diagram example with an incoming -cont signal

35
Technical reference manual

Section 1
Introduction
1.1.3.3

1MRK 505 222-UEN B

Input and output signals


Input and output signals are presented in two separate tables. Each table consists of
two columns. The first column contains the name of the signal and the second
column contains the description of the signal.

1.1.3.4

Function block
Each function block is illustrated graphically.
Input signals are always on the left hand side and output signals on the right hand
side. Settings are not displayed. Special kinds of settings are sometimes available.
These are supposed to be connected to constants in the configuration scheme and
are therefore depicted as inputs. Such signals will be found in the signal list but
described in the settings table.

The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set a signal name of
their own in PCM600.
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
IEC 61850 - 8 -1
Logical Node

Mandatory
signal (*)

Inputs

Outputs
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT

INVALID
RESTART
BLOCKED
NEW_VAL
^SCAL_VAL
en05000511-1-en.vsd

User defined
name (^)

Diagram
Number
IEC05000511 V2 EN

Figure 4:

1.1.3.5

Example of a function block

Setting parameters
These are presented in tables and include all parameters associated with the
function in question.

36
Technical reference manual

Section 1
Introduction

1MRK 505 222-UEN B

1.1.3.6

Technical data
The technical data section provides specific technical information about the
function or hardware described.

1.1.4

Intended audience
General
This manual addresses system engineers, installation and commissioning
personnel, who use technical data during engineering, installation and
commissioning, and in normal service.

Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in
the protective devices. The installation and commissioning personnel must have a
basic knowledge in the handling electronic equipment.

1.1.5

Related documents

Documents related to RED670

Identity number

Operators manual

1MRK 505 223-UEN

Installation and commissioning manual

1MRK 505 224-UEN

Technical reference manual

1MRK 505 222-UEN

Application manual

1MRK 505 225-UEN

Product guide customized

1MRK 505 226-BEN

Product guide pre-configured

1MRK 505 228-BEN

Product guide IEC 61850-9-2

1MRK 505 204-BEN

Sample specification

SA2005-001281

Connection and Installation components

1MRK 513 003-BEN

Test system, COMBITEST

1MRK 512 001-BEN

Accessories for 670 series IEDs

1MRK 514 012-BEN

670 series SPA and signal list

1MRK 500 092-WEN

IEC 61850 Data objects list for 670 series

1MRK 500 091-WEN

Engineering manual 670 series

1MRK 511 240-UEN

Communication set-up for Relion 670 series

1MRK 505 260-UEN

More information can be found on www.abb.com/substationautomation.

37
Technical reference manual

Section 1
Introduction
1.1.6

1MRK 505 222-UEN B

Revision notes
Revision

Description

Minor corrections made

Minor corrections made

38
Technical reference manual

Section 2
Analog inputs

1MRK 505 222-UEN B

Section 2

Analog inputs

2.1

Introduction
Analog input channels must be configured and set properly to get correct
measurement results and correct protection operations. For power measuring and
all directional and differential functions the directions of the input currents must be
defined properly. Measuring and protection algorithms in the IED use primary
system quantities. Set values are done in primary quantities as well and it is
important to set the data about the connected current and voltage transformers
properly.
A reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channels phase angle will always be fixed to zero degree and all other angle
information will be shown in relation to this analog input. During testing and
commissioning of the IED the reference channel can be changed to facilitate testing
and service values reading.
The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.

The availability of VT inputs depends on the ordered transformer


input module (TRM) type.

2.2

Operation principle
The direction of a current to the IED depends on the connection of the CT. The
main CTs are typically star connected and can be connected with the star point to
the object or from the object. This information must be set to the IED.
Directional conventions for current or power, for example

Positive value of current or power means quantity direction into the object.
Negative value of current or power means quantity direction out from the object.

Directional conventions for directional functions (see figure 5)

39
Technical reference manual

Section 2
Analog inputs

1MRK 505 222-UEN B

Forward means direction into the object.


Reverse means direction out from the object.
Definition of direction
for directional functions
Reverse

Definition of direction
for directional functions

Forward

Forward

Reverse

Protected Object
Line, transformer, etc
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object

e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object

Set parameter
CTStarPoint
Correct Setting is
"ToObject"

Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd

IEC05000456 V1 EN

Figure 5:

Internal convention of the directionality in the IED

The correct setting of the primary CT direction

CTStarPoint is set to FromObject or ToObject.


Positive quantities flow towards the object.
Direction is defined as Forward and looks towards the object.

The ratios of the main CTs and VTs must be known to use primary system
quantities for settings and calculation in the IED, The user has to set the rated
secondary and primary currents and voltages of the CTs and VTs to provide the
IED with this information.
The CT and VT ratio and the name on respective channel is done under Main
menu/Hardware/Analog modules in the Parameter Settings tool.

2.3

Function block
The function blocks are not represented in the configuration tool.
The signals appear only in the SMT tool when a TRM is included in
the configuration with the function selector tool. In the SMT tool
they can be mapped to the desired virtual input (SMAI) of the IED
and used internally in the configuration.

40
Technical reference manual

Section 2
Analog inputs

1MRK 505 222-UEN B

2.4

Setting parameters
Dependent on ordered IED type.

Table 1:

AISVBAS Non group settings (basic)

Name
PhaseAngleRef

Values (Range)
TRM40-Ch1
TRM40-Ch2
TRM40-Ch3
TRM40-Ch4
TRM40-Ch5
TRM40-Ch6
TRM40-Ch7
TRM40-Ch8
TRM40-Ch9
TRM40-Ch10
TRM40-Ch11
TRM40-Ch12
TRM41-Ch1
TRM41-Ch2
TRM41-Ch3
TRM41-Ch4
TRM41-Ch5
TRM41-Ch6
TRM41-Ch7
TRM41-Ch8
TRM41-Ch9
TRM41-Ch10
TRM41-Ch11
TRM41-Ch12
MU1-L1I
MU1-L2I
MU1-L3I
MU1-L4I
MU1-L1U
MU1-L2U
MU1-L3U
MU1-L4U
MU2-L1I
MU2-L2I
MU2-L3I
MU2-L4I
MU2-L1U
MU2-L2U
MU2-L3U
MU2-L4U
MU3-L1I
MU3-L2I
MU3-L3I
MU3-L4I
MU3-L1U
MU3-L2U
MU3-L3U
MU3-L4U

Unit
-

Step
-

Default
TRM40-Ch1

Description
Reference channel for phase angle
presentation

41
Technical reference manual

Section 2
Analog inputs

Table 2:
Name

1MRK 505 222-UEN B

TRM_12I Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CTStarPoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CTStarPoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CTStarPoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

CTStarPoint8

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec8

1 - 10

Rated CT secondary current

CTprim8

1 - 99999

3000

Rated CT primary current

CTStarPoint9

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec9

1 - 10

Rated CT secondary current

CTprim9

1 - 99999

3000

Rated CT primary current

CTStarPoint10

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec10

1 - 10

Rated CT secondary current

CTprim10

1 - 99999

3000

Rated CT primary current

CTStarPoint11

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec11

1 - 10

Rated CT secondary current

Table continues on next page


42
Technical reference manual

Section 2
Analog inputs

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

CTprim11

1 - 99999

3000

Rated CT primary current

CTStarPoint12

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec12

1 - 10

Rated CT secondary current

CTprim12

1 - 99999

3000

Rated CT primary current

Table 3:

TRM_6I_6U Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CTStarPoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CTStarPoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

VTsec7

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim7

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec8

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim8

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec9

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim9

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

Table continues on next page

43
Technical reference manual

Section 2
Analog inputs
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

Step

Default

Table 4:

TRM_6I Non group settings (basic)

Name

Values (Range)

Unit

Description

Description

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CTStarPoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CTStarPoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

Table 5:
Name

TRM_7I_5U Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

Table continues on next page

44
Technical reference manual

Section 2
Analog inputs

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CTStarPoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CTStarPoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CTStarPoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

VTsec8

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim8

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec9

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim9

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

Step

Default

Table 6:

TRM_9I_3U Non group settings (basic)

Name

Values (Range)

Unit

Description

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec1

1 - 10

Rated CT secondary current

CTprim1

1 - 99999

3000

Rated CT primary current

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec2

1 - 10

Rated CT secondary current

CTprim2

1 - 99999

3000

Rated CT primary current

Table continues on next page

45
Technical reference manual

Section 2
Analog inputs
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec3

1 - 10

Rated CT secondary current

CTprim3

1 - 99999

3000

Rated CT primary current

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec4

1 - 10

Rated CT secondary current

CTprim4

1 - 99999

3000

Rated CT primary current

CTStarPoint5

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec5

1 - 10

Rated CT secondary current

CTprim5

1 - 99999

3000

Rated CT primary current

CTStarPoint6

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec6

1 - 10

Rated CT secondary current

CTprim6

1 - 99999

3000

Rated CT primary current

CTStarPoint7

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec7

1 - 10

Rated CT secondary current

CTprim7

1 - 99999

3000

Rated CT primary current

CTStarPoint8

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec8

1 - 10

Rated CT secondary current

CTprim8

1 - 99999

3000

Rated CT primary current

CTStarPoint9

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTsec9

1 - 10

Rated CT secondary current

CTprim9

1 - 99999

3000

Rated CT primary current

VTsec10

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim10

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec11

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim11

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

VTsec12

0.001 - 999.999

0.001

110.000

Rated VT secondary voltage

VTprim12

0.05 - 2000.00

kV

0.05

400.00

Rated VT primary voltage

46
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Section 3

Local HMI

About this chapter


This chapter describes the structure and use of local HMI, which is the control
panel at the IED.

3.1

Human machine interface


The local human machine interface is available in a small and a medium sized
model. The difference between the two models is the size of the LCD. The small
size LCD can display seven lines of text and the medium size LCD can display the
single line diagram with up to 15 objects on each page. Up to 12 single line
diagram pages can be defined, depending on the product capability.
The local HMI is divided into zones with different functionality.

Status indication LEDs.


Alarm indication LEDs, which consist of 15 LEDs (6 red and 9 yellow) with
user printable label. All LEDs are configurable from PCM600.
Liquid crystal display (LCD).
Keypad with push buttons for control and navigation purposes, switch for
selection between local and remote control and reset.
Isolated RJ45 communication port.

47
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

IEC05000055-LITEN V1 EN

Figure 6:

Small, alpha numeric HMI

IEC05000056-LITEN V1 EN

Figure 7:

Medium graphic HMI, 15 controllable objects

48
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

3.2

Small size HMI

3.2.1

Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19 case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and
time. The remaining 5 lines are dynamic. This LCD has no graphic display potential.

3.2.2

Design
The local HMI is identical for both the 1/2, 3/4 and 1/1 cases. The different parts of
the small local HMI are shown in figure 8

49
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

en05000055.eps

IEC05000055-CALLOUT V1 EN

Figure 8:

Small graphic HMI

1 Status indication LEDs


2 LCD
3 Indication LEDs
4 Label
5 Local/Remote LEDs
6 RJ45 port
7 Communication indication LED
8 Keypad

50
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

3.3

Medium size graphic HMI

3.3.1

Medium
The following case sizes can be equipped with the medium size LCD:

1/2 x 19
3/4 x 19
1/1 x 19

This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD
is required.

3.3.2

Design
The different parts of the medium size local HMI are shown in figure 9. The local
HMI exists in an IEC version and in an ANSI version. The difference is on the
keypad operation buttons and the yellow LED designation.

51
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

en05000056.eps

IEC05000056-CALLOUT V1 EN

Figure 9:

Medium size graphic HMI

1 Status indication LEDs


2 LCD
3 Indication LEDs
4 Label
5 Local/Remote LEDs
6 RJ45 port
7 Communication indication LED
8 Keypad

52
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

3.4

Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.

IEC05000153 V1 EN

Figure 10:

The HMI keypad.

Table 7 describes the HMI keys that are used to operate the IED.
Table 7:
Key

HMI keys on the front of the IED


Function
Press to close or energize a breaker or disconnector.

IEC05000101 V1 EN

Press to open a breaker or disconnector.


IEC05000102 V1 EN

Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN

Press to clear entries, cancel commands or edit.


IEC05000104 V1 EN

Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN

Press to set the IED in local or remote control mode.


IEC05000106 V1 EN

Press to open the reset screen.


IEC05000107 V1 EN

Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN

Table continues on next page

53
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Key

Function
Press to navigate forward between screens and move right in editing mode.

IEC05000109 V1 EN

Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN

Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN

Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN

3.5

LED

3.5.1

Introduction
The LED module is a unidirectional means of communicating. This means that
events may occur that activate a LED in order to draw the operators attention to
something that has occurred and needs some sort of action.

3.5.2

Status indication LEDs


The three LEDs above the LCD provide information as shown in the table below.
LED Indication

Information

Green:
Steady

In service

Flashing

Internal failure

Dark

No power supply

Yellow:
Steady

Dist. rep. triggered

Flashing

Terminal in test mode

Red:
Steady

3.5.3

Trip command issued

Indication LEDs
The LED indication module comprising 15 LEDs is standard in 670 series. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.

54
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Alarm indication LEDs and hardware associated LEDs are located on the right
hand side of the front panel. Alarm LEDs are located on the right of the LCD
screen and show steady or flashing light.

Steady light indicates normal operation.


Flashing light indicates alarm.

Alarm LEDs can be configured in PCM600 and depend on the binary logic.
Therefore they can not be configured on the local HMI.
Typical examples of alarm LEDs

Bay controller failure


CB close blocked
Interlocking bypassed
Differential protection trip
SF6 Gas refill
Position error
CB spring charge alarm
Oil temperature alarm
Thermal overload trip

The RJ45 port has a yellow LED indicating that communication has been
established between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.

3.6

Local HMI related functions

3.6.1

Introduction
The local HMI can be adapted to the application configuration and to user preferences.

Function block LocalHMI


Function block LEDGEN
Setting parameters

55
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

3.6.2
Table 8:
Name

General setting parameters


SCREEN Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Language

English
OptionalLanguage

English

Local HMI language

DisplayTimeout

10 - 120

Min

10

60

Local HMI display timeout

AutoRepeat

Off
On

On

Activation of auto-repeat (On) or not (Off)

ContrastLevel

-10 - 20

Contrast level for display

DefaultScreen

0-0

Default screen

EvListSrtOrder

Latest on top
Oldest on top

Latest on top

Sort order of event list

SymbolFont

IEC
ANSI

IEC

Symbol font for Single Line Diagram

3.6.3

Status LEDs

3.6.3.1

Design
The function block LocalHMI controls and supplies information about the status of
the status indication LEDs. The input and output signals of local HMI are
configured with PCM600.
The function block can be used if any of the signals are required in a configuration
logic.
See section "Status indication LEDs" for information about the LEDs.

3.6.3.2

Function block
LocalHMI
CLRLEDS

HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
IEC05000773-2-en.vsd

IEC05000773 V2 EN

Figure 11:

3.6.3.3

LocalHMI function block

Input and output signals


Table 9:
Name
CLRLEDS

LocalHMI Input signals


Type
BOOLEAN

Default
0

Description
Input to clear the LCD-HMI LEDs

56
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Table 10:

LocalHMI Output signals

Name

Type

Description

HMI-ON

BOOLEAN

Backlight of the LCD display is active

RED-S

BOOLEAN

Red LED on the LCD-HMI is steady

YELLOW-S

BOOLEAN

Yellow LED on the LCD-HMI is steady

YELLOW-F

BOOLEAN

Yellow LED on the LCD-HMI is flashing

CLRPULSE

BOOLEAN

A pulse is provided when the LEDs on the LCDHMI are cleared

LEDSCLRD

BOOLEAN

Active when the LEDs on the LCD-HMI are not


active

3.6.4

Indication LEDs

3.6.4.1

Introduction
The function block LEDGEN controls and supplies information about the status of
the indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.

LEDs (number 16) for trip indications are red.


LEDs (number 715) for start indications are yellow.

Each indication LED on the local HMI can be set individually to operate in six
different sequences

Two sequences operate as follow type.


Four sequences operate as latch type.

Two of the latching sequence types are intended to be used as a


protection indication system, either in collecting or restarting mode, with
reset functionality.
Two of the latching sequence types are intended to be used as signaling
system in collecting (coll) mode with an acknowledgment functionality.

The light from the LEDs can be steady (-S) or flashing (-F). See the technical
reference manual for more information.

3.6.4.2

Design
The information on the LEDs is stored at loss of the auxiliary power to the IED in
some of the modes of LEDGEN. The latest LED picture appears immediately after
the IED is successfully restarted.

Operating modes

Collecting mode
57

Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

LEDs which are used in collecting mode of operation are accumulated


continuously until the unit is acknowledged manually. This mode is
suitable when the LEDs are used as a simplified alarm system.

Re-starting mode

In the re-starting mode of operation each new start resets all previous
active LEDs and activates only those which appear during one
disturbance. Only LEDs defined for re-starting mode with the latched
sequence type 6 (LatchedReset-S) will initiate a reset and a restart at a
new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has
elapsed.

Acknowledgment/reset

From local HMI

From function input

Active indications can be acknowledged or reset manually. Manual


acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function
is positive edge triggered, not level triggered. The acknowledged or reset
is performed via the reset button and menus on the local HMI. See the
operator's manual for more information.

Active indications can also be acknowledged or reset from an input,


RESET, to the function. This input can, for example, be configured to a
binary input operated from an external push button. The function is
positive edge triggered, not level triggered. This means that even if the
button is continuously pressed, the acknowledgment or reset only affects
indications active at the moment when the button is first pressed.

Automatic reset

Automatic reset can only be performed for indications defined for restarting mode with the latched sequence type 6 (LatchedReset-S). When
automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.

Operating sequences

The operating sequences can be of type Follow or Latched.

For the Follow type the LED follows the input signal completely.
For the Latched type each LED latches to the corresponding input signal until
it is reset.

58
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Figure 12 show the function of available sequences that are selectable for each
LED separately.

The acknowledgment or reset function is not applicable for sequence 1 and 2


(Follow type).
Sequence 3 and 4 (Latched type with acknowledgement) are only working in
collecting mode.
Sequence 5 is working according to Latched type and collecting mode.
Sequence 6 is working according to Latched type and re-starting mode.

The letters S and F in the sequence names have the meaning S = Steady and F =
Flashing.
At the activation of the input signal, the indication operates according to the
selected sequence diagrams.
In the sequence diagrams the LEDs have the characteristics as shown in figure 12.
= No indication

= Steady light

= Flash
en05000506.vsd

IEC05000506 V1 EN

Figure 12:

Symbols used in the sequence diagrams

Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Activating
signal

LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN

Figure 13:

Operating sequence 1 (Follow-S)

Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing
instead of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if

59
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

the signal is not present any more. If the signal is still present after
acknowledgment it gets a steady light.
Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN

Figure 14:

Operating sequence 3 (LatchedAck-F-S)

Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing
light have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the
activation of the input signal, the indication will light up with a steady light. The
difference to sequence 3 and 4 is that indications that are still activated will not be
affected by the reset that is, immediately after the positive edge of the reset has
been executed a new reading and storing of active signals is performed. Every LED
is independent of the other LEDs in its operation.
Activating
signal

LED

Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN

Figure 15:

Operating sequence 5 (LatchedColl-S)

Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the
positive edge of that the manual reset has been executed a new reading and storing

60
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

of active signals is performed. LEDs set for sequence 6 are completely independent
in its operation of LEDs set for other sequences.
Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is
activated until a settable time, tRestart, has elapsed after that all activating signals
for the LEDs set as LatchedReset-S have reset. However if all activating signals
have reset and some signal again becomes active before tRestart has elapsed, the
tRestart timer does not restart the timing sequence. A new disturbance start will be
issued first when all signals have reset after tRestart has elapsed. A diagram of this
functionality is shown in figure 16.
From
disturbance
length control
per LED
set to
sequence 6

New
disturbance

tRestart
t

&

&
1

&

en01000237.vsd
IEC01000237 V1 EN

Figure 16:

Activation of new disturbance

In order not to have a lock-up of the indications in the case of a persisting signal
each LED is provided with a timer, tMax, after which time the influence on the
definition of a disturbance of that specific LED is inhibited. This functionality is
shown i diagram in figure 17.
Activating signal

To LED

AND
tMax

To disturbance
length control

t
en05000507.vsd
IEC05000507 V1 EN

Figure 17:

Length control of activating signals

Timing diagram for sequence 6


Figure 18 shows the timing diagram for two indications within one disturbance.

61
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Disturbance
tRestart

Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset

IEC01000239_2-en.vsd

IEC01000239 V2 EN

Figure 18:

Operating sequence 6 (LatchedReset-S), two indications within


same disturbance

Figure 19 shows the timing diagram for a new indication after tRestart time has
elapsed.
Disturbance
tRestart

Disturbance
tRestart

Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN

Figure 19:

Operating sequence 6 (LatchedReset-S), two different disturbances

62
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Figure 20 shows the timing diagram when a new indication appears after the first
one has reset but before tRestart has elapsed.
Disturbance
tRestart
Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN

Figure 20:

Operating sequence 6 (LatchedReset-S), two indications within


same disturbance but with reset of activating signal between

Figure 21 shows the timing diagram for manual reset.


Disturbance
tRestart
Activating
signal 1
Activating
signal 2

LED 1

LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN

Figure 21:

Operating sequence 6 (LatchedReset-S), manual reset


63

Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

3.6.4.3

Function block
LEDGEN
BLOCK
RESET
LEDTEST

NEWIND
ACK

IEC05000508_2_en.vsd
IEC05000508 V2 EN

Figure 22:

3.6.4.4

LEDGEN function block

Input and output signals


Table 11:

LEDGEN Input signals

Name

Type

Input to block the operation of the LED-unit

RESET

BOOLEAN

Input to acknowledge/reset the indications of the


LED-unit

LEDTEST

BOOLEAN

Input for external LED test

LEDGEN Output signals

Name

Table 13:
Name

Description

BOOLEAN

Table 12:

3.6.4.5

Default

BLOCK

Type

Description

NEWIND

BOOLEAN

A new signal on any of the indication inputs occurs

ACK

BOOLEAN

A pulse is provided when the LEDs are


acknowledged

Setting parameters
LEDGEN Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation mode for the LED function

tRestart

0.0 - 100.0

0.1

0.0

Defines the disturbance length

tMax

0.0 - 100.0

0.1

0.0

Maximum time for the definition of a


disturbance

SeqTypeLED1

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 1

SeqTypeLED2

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 2

Table continues on next page

64
Technical reference manual

Section 3
Local HMI

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

SeqTypeLED3

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 3

SeqTypeLED4

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 4

SeqTypeLED5

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 5

SeqTypeLED6

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 6

SeqTypeLED7

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 7

SeqTypeLED8

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

sequence type for LED 8

SeqTypeLED9

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 9

SeqTypeLED10

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 10

SeqTypeLED11

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 11

Table continues on next page

65
Technical reference manual

Section 3
Local HMI
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

SeqTypeLED12

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 12

SeqTypeLED13

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 13

SeqTypeLED14

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 14

SeqTypeLED15

Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S

Follow-S

Sequence type for LED 15

66
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Section 4

Basic IED functions

About this chapter


This chapter presents functions that are basic to all 670 series IEDs. Typical
functions in this category are time synchronization, self supervision and test mode.

4.1

Authorization
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:

4.1.1

local, through the local HMI


remote, through the communication ports

Principle of operation
There are different levels (or types) of users that can access or operate different
areas of the IED and tools functionality. The pre-defined user types are given in
Table 14.
Be sure that the user logged on to the IED has the access required
when writing particular data to the IED from PCM600.
The meaning of the legends used in the table:

Table 14:

R= Read
W= Write
- = No access rights

Pre-defined user types

Access rights

Guest

Super User

SPA Guest

System
Operator

Protection
Engineer

Design
Engineer

User
Administrator

Basic setting possibilities (change


setting group, control settings,
limit supervision)

R/W

R/W

R/W

R/W

Advanced setting possibilities (for


example protection settings)

R/W

R/W

R/W

Basic control possibilities (process


control, no bypass)

R/W

R/W

R/W

R/W

R/W

Table continues on next page


67
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Access rights

Guest

Super User

SPA Guest

System
Operator

Protection
Engineer

Design
Engineer

User
Administrator

Advanced control possibilities


(process control including interlock
trigg)

R/W

R/W

R/W

R/W

R/W

Basic command handling (for


example clear LEDs, manual trigg)

R/W

R/W

R/W

R/W

Advanced command handling (for


example clear disturbance record)

R/W

R/W

R/W

R/W

Basic configuration possibilities (I/


O-configuration in SMT)

R/W

R/W

R/W

Advanced configuration
possibilities (application
configuration including SMT, GDE
and CMT)

R/W

R/W

R/W

File loading (database loading


from XML-file)

R/W

R/W

R/W

File dumping (database dumping


to XML-file)

R/W

R/W

R/W

File transfer (FTP file transfer)

R/W

R/W

R/W

R/W

R/W

File transfer (limited) (FTP file


transfer)

R/W

R/W

R/W

R/W

R/W

File Transfer (SPA File Transfer)

R/W

R/W

Database access for normal user

R/W

R/W

R/W

R/W

R/W

User administration (user


management FTP File Transfer)

R/W

R/W

User administration (user


management SPA File Transfer)

R/W

The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
Only characters A - Z, a - z and 0 - 9 should be used in user names
and passwords.

At least one user must be included in the UserAdministrator group


to be able to write users, created in PCM600, to IED.

4.1.1.1

Authorization handling in the IED


At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the User Management Tool.

68
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: No
user defined!
If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
60 minutes at delivery.
If there are one or more users created with the User Management Tool and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.
The cursor is focused on the User identity field, so upon pressing the E key, the
user can change the user name, by browsing the list of users, with the up and
down arrows. After choosing the right user name, the user must press the E
key again. When it comes to password, upon pressing the E key, the following
character will show up: $. The user must scroll for every letter in the password.
After all the letters are introduced (passwords are case sensitive) choose OK and
press the E key again.
If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses Cancel.

4.2

Self supervision with internal event list

4.2.1

Introduction
Self supervision with internal event list function listens and reacts to internal
system events, generated by the different built-in self-supervision elements. The
internal events are saved in an internal event list.

4.2.2

Principle of operation
The self-supervision operates continuously and includes:

Normal micro-processor watchdog function.


Checking of digitized measuring signals.
Other alarms, for example hardware and time synchronization.

69
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the selfsupervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/
General. The information from the self-supervision function is also available in the
Event Viewer in PCM600.
A self-supervision summary can be obtained by means of the potential free alarm
contact (INTERNAL FAIL) located on the power supply module. The function of
this output relay is an OR-function between the INT-FAIL signal see figure 24 and
a couple of more severe faults that can occur in the IED, see figure 23

IEC04000520 V1 EN

Figure 23:

Hardware self-supervision, potential-free alarm contact

70
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

IO fail

OR

IO stopped

Set
Reset

IO started

e.g. BIM 1 Error

e.g. IOM2 Error


e.g. IO (n) Error

OR

Internal
FAIL

OR

LON ERROR
FTF fatal error

OR

Watchdog

NUMFAIL

RTE fatal error


RTE Appl-fail
RTE OK

OR

Reset

IEC61850 not ready


RTCERROR

Internal
WARN

Set

OR

RTCERROR

Set

RTC OK

Reset

TIMESYNCHERROR
Time reset

OR

Set
Reset

SYNCH OK
Settings changed

NUMWARNING

TIMESYNCHERROR
SETCHGD

1 second pulse
en04000519-1.vsd

IEC04000519 V2 EN

Figure 24:

Software self-supervision, IES (IntErrorSign) function block

Some signals are available from the INTERRSIG function block. The signals from
this function block are sent as events to the station level of the control system. The
signals from the INTERRSIG function block can also be connected to binary
outputs for signalization via output relays or they can be used as conditions for
other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix tool. Error signals from time synchronization can be obtained
from the time synchronization block TIME.

4.2.2.1

Internal signals
Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal status of the IED, they are also
called internal signals. The internal signals can be divided into two groups.

Standard signals are always presented in the IED, see Table 15.
Hardware dependent internal signals are collected depending on the hardware
configuration, see Table 16.

Explanations of internal signals are listed in Table 17.

71
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 15:

Self-supervision's standard internal signals

Name of signal

Description

FAIL

Internal Fail status

WARNING

Internal Warning status

NUMFAIL

CPU module Fail status

NUMWARNING

CPU module Warning status

RTCERROR

Real Time Clock status

TIMESYNCHERROR

Time Synchronization status

RTEERROR

Runtime Execution Error status

IEC61850ERROR

IEC 61850 Error status

WATCHDOG

SW Watchdog Error status

LMDERROR

LON/Mip Device Error status

APPERROR

Runtime Application Error status

SETCHGD

Settings changed

SETGRPCHGD

Setting groups changed

FTFERROR

Fault Tolerant Filesystem status

Table 16:
Card

Self-supervision's hardware dependent internal signals


Name of signal

Description

PSM

PSM-Error

Power Supply Module Error status

ADOne

ADOne-Error

Analog In Module Error status

BIM

BIM-Error

Binary In Module Error status

BOM

BOM-Error

Binary Out Module Error status

IOM

IOM-Error

In/Out Module Error status

MIM

MIM-Error

Millampere Input Module Error status

LDCM

LDCM-Error

Line Differential Communication Error status

Table 17:

Explanations of internal signals

Name of signal

Reasons for activation

FAIL

This signal will be active if one or more of the following internal


signals are active; NUMFAIL, LMDERROR, WATCHDOG,
APPERROR, RTEERROR, FTFERROR, or any of the HW
dependent signals

WARNING

This signal will be active if one or more of the following internal


signals are active; RTCERROR, IEC61850ERROR,
TIMESYNCHERROR

NUMFAIL

This signal will be active if one or more of the following internal


signals are active; WATCHDOG, APPERROR, RTEERROR,
FTFERROR

NUMWARNING

This signal will be active if one or more of the following internal


signals are active; RTCERROR, IEC61850ERROR

RTCERROR

This signal will be active when there is a hardware error with the
real time clock.

Table continues on next page


72
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Name of signal

4.2.2.2

Reasons for activation

TIMESYNCHERROR

This signal will be active when the source of the time


synchronization is lost, or when the time system has to make a
time reset.

RTEERROR

This signal will be active if the Runtime Engine failed to do some


actions with the application threads. The actions can be loading
of settings or parameters for components, changing of setting
groups, loading or unloading of application threads.

IEC61850ERROR

This signal will be active if the IEC 61850 stack did not succeed
in some actions like reading IEC 61850 configuration, startup,
for example

WATCHDOG

This signal will be activated when the terminal has been under
too heavy load for at least 5 minutes. The operating systems
background task is used for the measurements.

LMDERROR

LON network interface, MIP/DPS, is in an unrecoverable error


state.

APPERROR

This signal will be active if one or more of the application threads


are not in the state that Runtime Engine expects. The states can
be CREATED, INITIALIZED, RUNNING, for example

SETCHGD

This signal will generate an Internal Event to the Internal Event


list if any settings are changed.

SETGRPCHGD

This signal will generate an Internal Event to the Internal Event


list if any setting groups are changed.

FTFERROR

This signal will be active if both the working file and the backup
file are corrupted and can not be recovered.

Run-time model
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see Figure
25.
ADx
Adx_Low
x1
u1
x2

Adx_High

Adx
Controller

x1
u1
x2

en05000296-2-en.vsd
IEC05000296 V2 EN

Figure 25:

Simplified drawing of A/D converter for the IED.

73
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

The technique to split the analog input signal into two A/D converters with
different amplification makes it possible to supervise the incoming signals under
normal conditions where the signals from the two converters should be identical.
An alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.
The self-supervision of the A/D conversion is controlled by the ADx_Controller
function. One of the tasks for the controller is to perform a validation of the input
signals. This is done in a validation filter which has mainly two objects: First is the
validation part that checks that the A/D conversion seems to work as expected.
Secondly, the filter chooses which of the two signals that shall be sent to the CPU,
that is the signal that has the most suitable level, the ADx_LO or the 16 times
higherADx_HI.
When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be
informed and an alarm will be given.
The ADx_Controller also supervise other parts of the A/D converter.

4.2.3

Function block

IEC09000787 V1 EN

Figure 26:

4.2.4

Output signals
Table 18:
Name

4.2.5

INTERRSIG function block

INTERRSIG Output signals


Type

Description

FAIL

BOOLEAN

Internal fail

WARNING

BOOLEAN

Internal warning

CPUFAIL

BOOLEAN

CPU fail

CPUWARN

BOOLEAN

CPU warning

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

74
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.2.6

Technical data
Table 19:

Self supervision with internal event list

Data

Value

Recording manner

Continuous, event controlled

List size

1000 events, first in-first out

4.3

Time synchronization

4.3.1

Introduction
The time synchronization source selector is used to select a common source of
absolute time for the IED when it is a part of a protection system. This makes it
possible to compare event- and disturbance data between all IEDs in a station
automation system possible. A common source shall be used for IED and merging
unit when IEC 61850-9-2LE process bus communication is used.
Micro SCADA OPC server should not be used as a time
synchronization source.

4.3.2

Principle of operation

4.3.2.1

General concepts
Time definitions

The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called
the clock accuracy and means how much the error increases, that is how much the
clock gains or loses time. A disciplined (trained) clock knows its own faults and
tries to compensate for them.

Design of the time system (clock synchronization)

The time system is based on a software clock, which can be adjusted from external
time sources and a hardware clock. The protection and control modules will be
timed from a hardware clock, which runs independently from the software clock.
See figure 27.

75
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

External
Synchronization
sources

Time tagging and general synchronisation

Off
LON
SPA
Min. pulse
GPS
SNTP
DNP

Communication

TimeRegulator
(Setting,
see
technical
reference
manual)

Events

Protection
and control
functions

SW-time
Connected when GPS-time is
used for differential protection

IRIG-B
PPS

Off
GPS
IRIG-B
PPS

TimeRegulator
(fast or slow)

Synchronization for differential protection


(ECHO-mode or GPS)
HW-time

A/D
converter

Diff.communication

Transducers*
*IEC 61850-9-2
IEC08000287-2-en.vsd

IEC08000287 V2 EN

Figure 27:

Design of time system (clock synchronization)

All time tagging is performed by the software clock. When for example a status
signal is changed in the protection system with the function based on free running
hardware clock, the event is time tagged by the software clock when it reaches the
event recorder. Thus the hardware clock can run independently.
The echo mode for the differential protection is based on the hardware clock. Thus,
there is no need to synchronize the hardware clock and the software clock.
The synchronization of the hardware clock and the software clock is necessary only
when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential
protection. The two clock systems are synchronized by a special clock
synchronization unit with two modes, fast and slow. A special feature, an
automatic fast clock time regulator is used. The automatic fast mode makes the
synchronization time as short as possible during start-up or at interruptions/
disturbances in the GPS timing. The setting fast or slow is also available on the
local HMI.
If a GPS clock is used for other 670 series IEDs than line differential RED670, the
hardware and software clocks are not synchronized

76
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Fast clock synchronization mode


At startup and after interruptions in the GPS or IRIG B time signal, the clock
deviation between the GPS time and the internal differential time system can be
substantial. A new startup is also required after for example maintenance of the
auxiliary voltage system.
When the time difference is >16us, the differential function is blocked and the time
regulator for the hardware clock is automatically using a fast mode to synchronize
the clock systems. The time adjustment is made with an exponential function, i.e.
big time adjustment steps in the beginning, then smaller steps until a time deviation
between the GPS time and the differential time system of >16us has been reached.
Then the differential function is enabled and the synchronization remains in fast
mode or switches to slow mode, depending on the setting.

Slow clock synchronization mode


During normal service, a setting with slow synchronization mode is normally used,
which prevents the hardware clock to make too big time steps, >16s, emanating
from the differential protection requirement of correct timing.

Synchronization principle

From a general point of view synchronization can be seen as a hierarchical


structure. A function is synchronized from a higher level and provides
synchronization to lower levels.

Synchronization from
a higher level

Function

Optional synchronization of
modules at a lower level

IEC09000342-1-en.vsd
IEC09000342 V1 EN

Figure 28:

Synchronization principle

A function is said to be synchronized when it periodically receives synchronization


messages from a higher level. As the level decreases, the accuracy of the
synchronization decreases as well. A function can have several potential sources of
synchronization, with different maximum errors, which give the function the
possibility to choose the source with the best quality, and to adjust its internal clock
after this source. The maximum error of a clock can be defined as:

77
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.3.2.2

The maximum error of the last used synchronization message


The time since the last used synchronization message
The rate accuracy of the internal clock in the function.

Real-time clock (RTC) operation


The IED has a built-in real-time clock (RTC) with a resolution of one second. The
clock has a built-in calendar that handles leap years through 2038.

Real-time clock at power off

During power off, the system time in the IED is kept by a capacitor-backed realtime clock that will provide 35 ppm accuracy for 5 days. This means that if the
power is off, the time in the IED may drift with 3 seconds per day, during 5 days,
and after this time the time will be lost completely.

Real-time clock at startup


Time synchronization startup procedure

The first message that contains the full time (as for instance LON, SNTP and GPS)
gives an accurate time to the IED. After the initial setting of the clock, one of three
things happens with each of the coming synchronization messages configured as
fine:

If the synchronization message, which is similar to the other messages, has an


offset compared to the internal time in the IED, the message is used directly
for synchronization, that is, for adjusting the internal clock to obtain zero
offset at the next coming time message.
If the synchronization message has an offset that is large compared to the other
messages, a spike-filter in the IED removes this time-message.
If the synchronization message has an offset that is large, and the following
message also has a large offset, the spike filter does not act and the offset in
the synchronization message is compared to a threshold that defaults to 100
milliseconds. If the offset is more than the threshold, the IED is brought into a
safe state and the clock is set to the correct time. If the offset is lower than the
threshold, the clock is adjusted with 1000 ppm until the offset is removed.
With an adjustment of 1000 ppm, it takes 100 seconds or 1.7 minutes to
remove an offset of 100 milliseconds.

Synchronization messages configured as coarse are only used for initial setting of
the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds resets the time.

Rate accuracy

In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized
for a while, the rate accuracy is approximately 1 ppm if the surrounding
temperature is constant. Normally, it takes 20 minutes to reach full accuracy.

78
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Time-out on synchronization sources

All synchronization interfaces has a time-out and a configured interface must


receive time-messages regularly in order not to give an error signal (TSYNCERR).
Normally, the time-out is set so that one message can be lost without getting a
TSYNCERR, but if more than one message is lost, a TSYNCERR is given.

4.3.2.3

Synchronization alternatives
Three main alternatives of external time synchronization are available. Either the
synchronization message is applied via any of the communication ports of the IED
as a telegram message including date and time or as a minute pulse, connected to a
binary input, or via GPS. The minute pulse is used to fine tune already existing
time in the IEDs.

Synchronization via SNTP

SNTP provides a ping-pong method of synchronization. A message is sent from an


IED to an SNTP server, and the SNTP server returns the message after filling in a
reception time and a transmission time. SNTP operates via the normal Ethernet
network that connects IEDs together in an IEC 61850 network. For SNTP to
operate properly, there must be an SNTP-server present, preferably in the same
station. The SNTP synchronization provides an accuracy that gives 1 ms accuracy
for binary inputs. The IED itself can be set as an SNTP-time server.
SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than
4-5 switches or routers away from the IED. The SNTP server is dedicated for its
task, or at least equipped with a real-time operating system, that is not a PC with
SNTP server software. The SNTP server should be stable, that is, either
synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server
in a redundant configuration is not recommended.

Synchronization via Serial Communication Module (SLM)

On the serial buses (both LON and SPA) two types of synchronization messages
are sent.

Coarse message is sent every minute and comprises complete date and time,
that is, year, month, day, hours, minutes, seconds and milliseconds.
Fine message is sent every second and comprises only seconds and milliseconds.

IEC60870-5-103 is not used to synchronize the IED, but instead the offset between
the local time in the IED and the time received from 103 is added to all times (in
events and so on) sent via 103. In this way the IED acts as it is synchronized from
various 103 sessions at the same time. Actually, there is a local time for each 103
session.
The SLM module is located on the AD conversion Module (ADM).

79
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Synchronization via Built-in-GPS

The built in GPS clock modules receives and decodes time information from the
global positioning system. The modules are located on the GPS time
synchronization Module (GTM).

Synchronization via binary input

The IED accepts minute pulses to a binary input. These minute pulses can be
generated from, for example station master clock. If the station master clock is not
synchronized from a world wide source, time will be a relative time valid for the
substation. Both positive and negative edge on the signal can be accepted. This
signal is also considered as a fine time synchronization signal.
The minute pulse is connected to any channel on any Binary Input Module in the
IED. The electrical characteristic is thereby the same as for any other binary input.
If the objective of synchronization is to achieve a relative time within the
substation and if no station master clock with minute pulse output is available, a
simple minute pulse generator can be designed and used for synchronization of the
IEDs. The minute pulse generator can be created using the logical elements and
timers available in the IED.
The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute
after the last flank.
Binary minute pulses are checked with reference to frequency.
Pulse data:

Period time (a) should be 60 seconds.


Pulse length (b):

Minimum pulse length should be >50 ms.


Maximum pulse length is optional.

Amplitude (c) - please refer to section "Binary input module (BIM)".

Deviations in the period time larger than 50 ms will cause TSYNCERR.

80
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

a
b

c
en05000251.vsd
IEC05000251 V1 EN

Figure 29:

Binary minute pulses

The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.
If contact bounces occurs, only the first pulse will be detected as a minute pulse.
The next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, for example, it is exactly 60 seconds between the
pulses, contact bounces might occur 49 ms after the actual minute pulse without
effecting the system. If contact bounces occurs more than 50 ms, for example, it is
less than 59950 ms between the two most adjacent positive (or negative) flanks, the
minute pulse will not be accepted.
Binary synchronization example
An IED is configured to use only binary input, and a valid binary input is applied
to a binary input card. The HMI is used to tell the IED the approximate time and
the minute pulse is used to synchronize the IED thereafter. The definition of a
minute pulse is that it occurs one minute after the previous minute pulse, so the
first minute pulse is not used at all. The second minute pulse will probably be
rejected due to the spike filter. The third pulse will give the IED a good time and
will reset the time so that the fourth minute pulse will occur on a minute border.
After the first three minutes, the time in the IED will be good if the coarse time is
set properly via the HMI or the RTC backup still keeps the time since last up-time.
If the minute pulse is removed for instance for an hour, the internal time will drift
by maximum the error rate in the internal clock. If the minute pulse is returned, the
first pulse automatically is rejected. The second pulse will possibly be rejected due
to the spike filter. The third pulse will either synchronize the time, if the time offset
is more than 100 ms, or adjust the time, if the time offset is small enough. If the
time is set, the application will be brought to a safe state before the time is set. If
the time is adjusted, the time will reach its destination within 1.7 minutes.
Synchronization via IRIG-B
IRIG-B is a protocol used only for time synchronization. A clock can provide local
time of the year in this format. The B in IRIG-B states that 100 bits per second
are transmitted, and the message is sent every second. After IRIG-B there numbers
stating if and how the signal is modulated and the information transmitted.

81
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

To receive IRIG-B there are two connectors in the IRIG-B module, one galvanic
BNC connector and one optical ST connector. IRIG-B 12x messages can be
supplied via the galvanic interface, and IRIG-B 00x messages can be supplied via
either the galvanic interface or the optical interface, where x (in 00x or 12x) means
a number in the range of 1-7.
00 means that a base band is used, and the information can be fed into the IRIGB module via the BNC contact or an optical fiber. 12 means that a 1 kHz
modulation is used. In this case the information must go into the module via the
BNC connector.
If the x in 00x or 12x is 4, 5, 6 or 7, the time message from IRIG-B contains
information of the year. If x is 0, 1, 2 or 3, the information contains only the time
within the year, and year information has to come from PCM600 or local HMI.
The IRIG-B module also takes care of IEEE1344 messages that are sent by IRIG-B
clocks, as IRIG-B previously did not have any year information. IEEE1344 is
compatible with IRIG-B and contains year information and information of the timezone.
It is recommended to use IEEE 1344 for supplying time information to the IRIG-B
module. In this case, send also the local time in the messages, as this local time
plus the TZ Offset supplied in the message equals UTC at all times.

4.3.2.4

Process bus IEC 61850-9-2LE synchronization


For the time synchronization of the process bus communication (IEC 61850-9-2LE
protocol) an optical PPS or IRIG-B signal can be used. This signal should emanate
from either an external GPS clock, or from the merging unit.
An optical PPS signal can be supplied to the optical interface of the IRIG-B module.

4.3.3

Function block
TIMEERR
TSYNCERR
RTCERR
IEC05000425-2-en.vsd
IEC05000425 V2 EN

Figure 30:

4.3.4

TIMEERR function block

Output signals
Table 20:
Name

TIMEERR Output signals


Type

Description

TSYNCERR

BOOLEAN

Time synchronization error

RTCERR

BOOLEAN

Real time clock error

82
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.3.5

Setting parameters
Path in the local HMI is located under Main menu/Setting/Time
Path in PCM600 is located under Main menu/Settings/Time/Synchronization

Table 21:

TIMESYNCHGEN Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

CoarseSyncSrc

Off
SPA
LON
SNTP
DNP

Off

Coarse time synchronization source

FineSyncSource

Off
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS

Off

Fine time synchronization source

SyncMaster

Off
SNTP-Server

Off

Activate IED as synchronization master

TimeAdjustRate

Slow
Fast

Fast

Adjust rate for time synchronization

HWSyncSrc

Off
GPS
IRIG-B
PPS

Off

Hardware time synchronization source

AppSynch

NoSynch
Synch

NoSynch

Time synchronization mode for


application

SyncAccLevel

Class T5 (1us)
Class T4 (4us)
Unspecified

Unspecified

Wanted time synchronization accuracy

Table 22:

SYNCHBIN Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

ModulePosition

3 - 16

Hardware position of IO module for time


synchronization

BinaryInput

1 - 16

Binary input number for time


synchronization

BinDetection

PositiveEdge
NegativeEdge

PositiveEdge

Positive or negative edge detection

83
Technical reference manual

Section 4
Basic IED functions

Table 23:
Name

1MRK 505 222-UEN B

SYNCHSNTP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ServerIP-Add

0 - 18

IP
Address

0.0.0.0

Server IP-address

RedServIP-Add

0 - 18

IP
Address

0.0.0.0

Redundant server IP-address

Table 24:
Name

DSTBEGIN Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

MonthInYear

January
February
March
April
May
June
July
August
September
October
November
December

March

Month in year when daylight time starts

DayInWeek

Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday

Sunday

Day in week when daylight time starts

WeekInMonth

Last
First
Second
Third
Fourth

Last

Week in month when daylight time starts

UTCTimeOfDay

0 - 172800

3600

UTC Time of day in seconds when


daylight time starts

84
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 25:

DSTEND Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

MonthInYear

January
February
March
April
May
June
July
August
September
October
November
December

October

Month in year when daylight time ends

DayInWeek

Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday

Sunday

Day in week when daylight time ends

WeekInMonth

Last
First
Second
Third
Fourth

Last

Week in month when daylight time ends

UTCTimeOfDay

0 - 172800

3600

UTC Time of day in seconds when


daylight time ends

Table 26:

TIMEZONE Non group settings (basic)

Name

Values (Range)

NoHalfHourUTC

Table 27:

-24 - 24

Unit
-

Step
1

Default
0

Description
Number of half-hours from UTC

SYNCHIRIG-B Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SynchType

BNC
Opto

Opto

Type of synchronization

TimeDomain

LocalTime
UTC

LocalTime

Time domain

Encoding

IRIG-B
1344
1344TZ

IRIG-B

Type of encoding

TimeZoneAs1344

MinusTZ
PlusTZ

PlusTZ

Time zone as in 1344 standard

85
Technical reference manual

Section 4
Basic IED functions
4.3.6

1MRK 505 222-UEN B

Technical data
Table 28:

Time synchronization, time tagging

Function

Value

Time tagging resolution, events and sampled measurement values

1 ms

Time tagging error with synchronization once/min (minute pulse


synchronization), events and sampled measurement values

1.0 ms typically

Time tagging error with SNTP synchronization, sampled


measurement values

1.0 ms typically

4.4

Parameter setting groups

4.4.1

Introduction
Use the six sets of settings to optimize the IED operation for different system
conditions. Creating and switching between fine-tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can
cope with a variety of system scenarios.

4.4.2

Principle of operation
Parameter setting groups ActiveGroup function has six functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of
these inputs changes the active setting group. Seven functional output signals are
available for configuration purposes, so that up to date information on the active
setting group is always available.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between.

86
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1

+RL2

IOx-Bly1
IOx-Bly2
IOx-Bly3
IOx-Bly4

ActiveGroup
ACTGRP1
GRP1
ACTGRP2

GRP2

ACTGRP3

GRP3

ACTGRP4

GRP4

IOx-Bly5

ACTGRP5

GRP5

IOx-Bly6

ACTGRP6

GRP6
SETCHGD

en05000119.vsd
IEC05000119 V2 EN

Figure 31:

Connection of the function to external circuits

The above example also includes seven output signals, for confirmation of which
group that is active.
SETGRPS function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used
will be shown on the Parameter Setting Tool.

4.4.3

Function block
ActiveGroup
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
SETCHGD
IEC05000433_2_en.vsd
IEC05000433 V2 EN

Figure 32:

ActiveGroup function block

SETGRPS
MAXSETGR
IEC05000716_2_en.vsd
IEC05000716 V2 EN

Figure 33:

SETGRPS function block

87
Technical reference manual

Section 4
Basic IED functions
4.4.4

1MRK 505 222-UEN B

Input and output signals


Table 29:

ActiveGroup Input signals

Name

Type
BOOLEAN

Selects setting group 1 as active

ACTGRP2

BOOLEAN

Selects setting group 2 as active

ACTGRP3

BOOLEAN

Selects setting group 3 as active

ACTGRP4

BOOLEAN

Selects setting group 4 as active

ACTGRP5

BOOLEAN

Selects setting group 5 as active

ACTGRP6

BOOLEAN

Selects setting group 6 as active

ActiveGroup Output signals

Name

Table 31:
Name
t

Table 32:
Name

Description

ACTGRP1

Table 30:

4.4.5

Default

Type

Description

GRP1

BOOLEAN

Setting group 1 is active

GRP2

BOOLEAN

Setting group 2 is active

GRP3

BOOLEAN

Setting group 3 is active

GRP4

BOOLEAN

Setting group 4 is active

GRP5

BOOLEAN

Setting group 5 is active

GRP6

BOOLEAN

Setting group 6 is active

SETCHGD

BOOLEAN

Pulse when setting changed

Setting parameters
ActiveGroup Non group settings (basic)
Values (Range)
0.0 - 10.0

Unit

Step

0.1

Default
1.0

Description
Pulse length of pulse when setting
changed

SETGRPS Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ActiveSetGrp

SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6

SettingGroup1

ActiveSettingGroup

MAXSETGR

1-6

No

Max number of setting groups 1-6

4.5

ChangeLock function CHNGLCK

88
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.5.1

Introduction
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.

4.5.2

Principle of operation
The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED
state that does not involve reconfiguring of the IED:

Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group

The binary input signal LOCK controlling the function is defined in ACT or SMT:
Binary input

4.5.3

Function

Activated

Deactivated

Function block
CHNGLCK
LOCK
IEC09000946-1-en.vsd
IEC09000946 V1 EN

Figure 34:

4.5.4

CHNGLCK function block

Input and output signals


Table 33:
Name
LOCK

CHNGLCK Input signals


Type
BOOLEAN

Default
0

Description
Parameter change lock

89
Technical reference manual

Section 4
Basic IED functions
4.5.5
Table 34:
Name
Operation

1MRK 505 222-UEN B

Setting parameters
CHNGLCK Non group settings (basic)
Values (Range)
LockHMI and Com
LockHMI,
EnableCom
EnableHMI,
LockCom

Unit
-

Step
-

Default
LockHMI and Com

4.6

Test mode functionality TEST

4.6.1

Introduction

Description
Operation mode of change lock

When the Test mode functionality TESTMODE function is activated, protection


functions in the IED are automatically blocked. It is then possible to unblock the
protection functions individually from the local HMI or the Parameter Setting tool
to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes
normal operation. However, if during TESTMODE operation, power is removed
and later restored, the IED will remain in TESTMODE with the same protection
functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be
changed, thus mistakes are avoided.

4.6.2

Principle of operation
Put the IED into test mode to test functions in the IED. Set the IED in test mode by

configuration, activating the input signal of the function block TESTMODE.


setting TestMode to On in the local HMI, under Main menu/TEST/IED test
mode.

While the IED is in test mode, the ACTIVE output of the function block
TESTMODE is activated. The other outputs of the function block TESTMODE
shows the generator of the Test mode: On state input from configuration
(OUTPUT output is activated) or setting from local HMI (SETTING output is
activated).
While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be unblocked individually regarding functionality
and event signalling.
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode
(output ACTIVE is activated), see example in figure 35. When leaving the test
90
Technical reference manual

1MRK 505 222-UEN B

Section 4
Basic IED functions

mode, that is entering normal mode, these blockings are disabled and everything is
set to normal operation. All testing will be done with actually set and configured
values within the IED. No settings will be changed, thus no mistakes are possible.
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.
When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the
IED will re-enter test mode and all functions will be blocked, also
functions that were unblocked before the change. During the reentering to test mode, all functions will be temporarily unblocked
for a short time, which might lead to unwanted operations. This is
only valid if the IED is put in TEST mode by a binary input, not by
local HMI.
The TESTMODE function block might be used to automatically block functions
when a test handle is inserted in a test switch. A contact in the test switch (RTXP24
contact 29-30) can supply a binary input which in turn is configured to the
TESTMODE function block.
Each of the protection functions includes the blocking from the TESTMODE
function block. A typical example from the undervoltage function is shown in
figure 35.
The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a maintenance test.

91
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Disconnection

Normal voltage
U1<
U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1

tBlkUV2 <
t2,t2Min

IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN

Figure 35:

4.6.3

Example of blocking the time delayed undervoltage protection


function.

Function block
TESTMODE
INPUT

ACTIVE
OUTPUT
SETTING
NOEVENT

IEC09000219-1.vsd
IEC09000219 V1 EN

Figure 36:

4.6.4

TESTMODE function block

Input and output signals


Table 35:
Name
INPUT

TESTMODE Input signals


Type
BOOLEAN

Default
0

Description
Sets terminal in test mode when active

92
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 36:

TESTMODE Output signals

Name

4.6.5
Table 37:

Type

Description

ACTIVE

BOOLEAN

Terminal in test mode when active

OUTPUT

BOOLEAN

Test input is active

SETTING

BOOLEAN

Test mode setting is (On) or not (Off)

NOEVENT

BOOLEAN

Event disabled during testmode

Setting parameters
TESTMODE Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

TestMode

Off
On

Off

Test mode in operation (On) or not (Off)

EventDisable

Off
On

Off

Event disable during testmode

CmdTestBit

Off
On

Off

Command bit for test required or not


during testmode

4.7

IED identifiers

4.7.1

Introduction
IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.

4.7.2
Table 38:

Setting parameters
TERMINALID Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

StationName

0 - 18

Station name

Station name

StationNumber

0 - 99999

Station number

ObjectName

0 - 18

Object name

Object name

ObjectNumber

0 - 99999

Object number

UnitName

0 - 18

Unit name

Unit name

UnitNumber

0 - 99999

Unit number

93
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.8

Product information

4.8.1

Introduction
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:

IEDProdType
ProductDef
FirmwareVer
SerialNo
OrderingNo
ProductionDate

The settings are visible on the local HMI , under Main menu/Diagnostics/IED
status/Product identifiers
They are very helpful in case of support process (such as repair or maintenance).

4.8.2

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

4.8.3

Factory defined settings


The factory defined settings are very useful for identifying a specific version and
very helpful in the case of maintenance, repair, interchanging IEDs between
different Substation Automation Systems and upgrading. The factory made settings
can not be changed by the customer. They can only be viewed. The settings are
found in the local HMI under Main menu/Diagnostics/IED status/Product
identifiers
The following identifiers are available:

IEDProdType

ProductDef

Describes the release number, from the production. Example: 1.2.2.0

FirmwareVer

Describes the type of the IED (like REL, REC or RET). Example: REL670

Describes the firmware version. Example: 1.4.51


Firmware versions numbers are running independently from the
release production numbers. For every release numbers (like 1.5.0.17)
there can be one or more firmware versions, depending on the small
issues corrected in between releases.

IEDMainFunType

94
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Main function type code according to IEC 60870-5-103. Example: 128


(meaning line protection).

SerialNo
OrderingNo
ProductionDate

4.9

Signal matrix for binary inputs SMBI

4.9.1

Introduction
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how binary inputs are brought
in for one IED configuration.

4.9.2

Principle of operation
The Signal matrix for binary inputs (SMBI) function , see figure 37, receives its
inputs from the real (hardware) binary inputs via the Signal Matrix Tool (SMT),
and makes them available to the rest of the configuration via its outputs, BI1 to
BI10. The inputs and outputs, as well as the whole block, can be given a user
defined name. These names will be represented in SMT as information which
signals shall be connected between physical IO and SMBI function. The input/
output user defined name will also appear on the respective output/input signal.

4.9.3

Function block
SMBI
^VIN1
^VIN2
^VIN3
^VIN4
^VIN5
^VIN6
^VIN7
^VIN8
^VIN9
^VIN10

^BI1
^BI2
^BI3
^BI4
^BI5
^BI6
^BI7
^BI8
^BI9
^BI10
IEC05000434-2-en.vsd

IEC05000434 V2 EN

Figure 37:

SMBI function block

95
Technical reference manual

Section 4
Basic IED functions
4.9.4

1MRK 505 222-UEN B

Input and output signals


Table 39:

SMBI Input signals

Name

Type

Default

Description

VIn1

BOOLEAN

SMT Connect input

VIn2

BOOLEAN

SMT Connect input

VIn3

BOOLEAN

SMT Connect input

VIn4

BOOLEAN

SMT Connect input

VIn5

BOOLEAN

SMT Connect input

VIn6

BOOLEAN

SMT Connect input

VIn7

BOOLEAN

SMT Connect input

VIn8

BOOLEAN

SMT Connect input

VIn9

BOOLEAN

SMT Connect input

VIn10

BOOLEAN

SMT Connect input

Table 40:

SMBI Output signals

Name

Type

Description

BI1

BOOLEAN

Binary input 1

BI2

BOOLEAN

Binary input 2

BI3

BOOLEAN

Binary input 3

BI4

BOOLEAN

Binary input 4

BI5

BOOLEAN

Binary input 5

BI6

BOOLEAN

Binary input 6

BI7

BOOLEAN

Binary input 7

BI8

BOOLEAN

Binary input 8

BI9

BOOLEAN

Binary input 9

BI10

BOOLEAN

Binary input 10

4.10

Signal matrix for binary outputs SMBO

4.10.1

Introduction
The Signal matrix for binary outputs (SMBO) function is used within the
Application Configuration Tool (ACT) in direct relation with the Signal Matrix
Tool (SMT), see the application manual to get information about how binary inputs
are sent from one IED configuration.

96
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.10.2

Principle of operation
The Signal matrix for binary outputs (SMBO) function , see figure 38, receives
logical signal from the IED configuration, which is transferring to the real
(hardware) outputs, via the Signal Matrix Tool (SMT). The inputs in SMBO are
BO1 to BO10 and they, as well as the whole function block, can be tag-named. The
name tags will appear in SMT as information which signals shall be connected
between physical IO and the SMBO.
It is important that SMBO inputs are connected when SMBOs
are connected to physical outputs through the Signal Matrix
Tool. If SMBOs are connected (in SMT) but their inputs not, all
the physical outputs will be set by default. This might cause
malfunction of primary equipment and/or injury to personnel.

4.10.3

Function block
SMBO
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10

^BO1
^BO2
^BO3
^BO4
^BO5
^BO6
^BO7
^BO8
^BO9
^BO10
IEC05000439-2-en.vsd

IEC05000439 V2 EN

Figure 38:

4.10.4

SMBO function block

Input and output signals


Table 41:
Name

SMBO Input signals


Type

Default

Description

BO1

BOOLEAN

Signal name for BO1 in Signal Matrix Tool

BO2

BOOLEAN

Signal name for BO2 in Signal Matrix Tool

BO3

BOOLEAN

Signal name for BO3 in Signal Matrix Tool

BO4

BOOLEAN

Signal name for BO4 in Signal Matrix Tool

BO5

BOOLEAN

Signal name for BO5 in Signal Matrix Tool

BO6

BOOLEAN

Signal name for BO6 in Signal Matrix Tool

BO7

BOOLEAN

Signal name for BO7 in Signal Matrix Tool

BO8

BOOLEAN

Signal name for BO8 in Signal Matrix Tool

BO9

BOOLEAN

Signal name for BO9 in Signal Matrix Tool

BO10

BOOLEAN

Signal name for BO10 in Signal Matrix Tool

97
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.11

Signal matrix for mA inputs SMMI

4.11.1

Introduction
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT),
see the application manual to get information about how milliamp (mA) inputs are
brought in for one IED configuration.

4.11.2

Principle of operation
The Signal matrix for mA inputs (SMMI) function, see figure 39, receives its
inputs from the real (hardware) mA inputs via the Signal Matrix Tool (SMT), and
makes them available to the rest of the configuration via its analog outputs, named
AI1 to AI6. The inputs, as well as the whole block, can be tag-named. These tags
will be represented in SMT.
The outputs on SMMI are normally connected to the IEC61850 generic
communication I/O functions (MVGGIO) function for further use of the mA signals.

4.11.3

Function block
SMMI
^VIN1
^VIN2
^VIN3
^VIN4
^VIN5
^VIN6

AI1
AI2
AI3
AI4
AI5
AI6
IEC05000440-2-en.vsd

IEC05000440 V2 EN

Figure 39:

4.11.4

SMMI function block

Input and output signals


Table 42:
Name

SMMI Input signals


Type

Default

Description

VIn1

REAL

SMT connected milliampere input

VIn2

REAL

SMT connected milliampere input

VIn3

REAL

SMT connected milliampere input

VIn4

REAL

SMT connected milliampere input

VIn5

REAL

SMT connected milliampere input

VIn6

REAL

SMT connected milliampere input

98
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 43:

SMMI Output signals

Name

Type

Description

AI1

REAL

Analog milliampere input 1

AI2

REAL

Analog milliampere input 2

AI3

REAL

Analog milliampere input 3

AI4

REAL

Analog milliampere input 4

AI5

REAL

Analog milliampere input 5

AI6

REAL

Analog milliampere input 6

4.12

Signal matrix for analog inputs SMAI

4.12.1

Introduction
Signal matrix for analog inputs function SMAI (or the pre-processing function) is
used within PCM600 in direct relation with the Signal Matrix tool or the
Application Configuration tool. Signal Matrix tool represents the way analog
inputs are brought in for one IED configuration.

4.12.2

Principle of operation
Every Signal matrix for analog inputs function (SMAI) can receive four analog
signals (three phases and one neutral value), either voltage or current, see figure 41
and figure 42. SMAI outputs give information about every aspect of the 3ph analog
signals acquired (phase angle, RMS value, frequency and frequency derivates etc.
244 values in total). The BLOCK input will reset all outputs to 0.
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. AIN is always the neutral
current, calculated residual sum or the signal connected to GRPxN. Note that
function block will always calculate the residual sum of current/voltage if the input
is not connected in SMT. Applications with a few exceptions shall always be
connected to AI3P.

4.12.3

Frequency values
The frequency functions includes a functionality based on level of positive
sequence voltage, IntBlockLevel, to validate if the frequency measurement is valid
or not. If positive sequence voltage is lower than IntBlockLevel the function is
blocked. IntBlockLevel, is set in % of UBase/3
If SMAI setting ConnectionType is Ph-Ph at least two of the inputs GRPxL1,
GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence
voltage. If SMAI setting ConnectionType is Ph-N, all three inputs GRPxL1,
99

Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

GRPxL2 and GRPxL3 must be connected in order to calculate positive sequence


voltage.
If only one phase-phase voltage is available and SMAI setting ConnectionType is
Ph-Ph the user is advised to connect two (not three) of the inputs GRPxL1,
GRPxL2 and GRPxL3 to the same voltage input as shown in figure 40 to make
SMAI calculating a positive sequence voltage (that is input voltage/3).

IEC10000060-1-en.vsd
IEC10000060 V1 EN

Figure 40:

Connection example

The above described scenario does not work if SMAI setting


ConnectionType is Ph-N. If only one phase-earth voltage is
available, the same type of connection can be used but the SMAI
ConnectionType setting must still be Ph-Ph and this has to be
accounted for when setting IntBlockLevel. If SMAI setting
ConnectionType is Ph-N and the same voltage is connected to all
three SMAI inputs, the positive sequence voltage will be zero and
the frequency functions will not work properly.

The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.

4.12.4

Function block
SMAI1
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE

SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
IEC05000705-2-en.vsd

IEC05000705 V2 EN

Figure 41:

SMAI1 function block

100
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
TYPE

AI3P
AI1
AI2
AI3
AI4
AIN
IEC07000130-2-en.vsd

IEC07000130 V2 EN

Figure 42:

4.12.5

SMAI2 function block

Input and output signals


Table 44:
Name

SMAI1 Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block group 1

DFTSPFC

REAL

20.0

Number of samples per fundamental cycle used


for DFT calculation

GRP1L1

STRING

Sample input to be used for group 1 phase L1


calculations

GRP1L2

STRING

Sample input to be used for group 1 phase L2


calculations

GRP1L3

STRING

Sample input to be used for group 1 phase L3


calculations

GRP1N

STRING

Sample input to be used for group 1 residual


calculations

Table 45:
Name

SMAI1 Output signals


Type

Description

SPFCOUT

REAL

Number of samples per fundamental cycle from


internal DFT reference function

AI3P

GROUP SIGNAL

Group 1 analog input 3-phase group

AI1

GROUP SIGNAL

Group 1 analog input 1

AI2

GROUP SIGNAL

Group 1 analog input 2

AI3

GROUP SIGNAL

Group 1 analog input 3

AI4

GROUP SIGNAL

Group 1 analog input 4

AIN

GROUP SIGNAL

Group 1 analog input residual for disturbance


recorder

101
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 46:
Name

Type

Default

Description

BLOCK

BOOLEAN

Block group 2

GRP2L1

STRING

Sample input to be used for group 2 phase L1


calculations

GRP2L2

STRING

Sample input to be used for group 2 phase L2


calculations

GRP2L3

STRING

Sample input to be used for group 2 phase L3


calculations

GRP2N

STRING

Sample input to be used for group 2 residual


calculations

Table 47:
Name

4.12.6

SMAI2 Input signals

SMAI2 Output signals


Type

Description

AI3P

GROUP SIGNAL

Group 2 analog input 3-phase group

AI1

GROUP SIGNAL

Group 2 analog input 1

AI2

GROUP SIGNAL

Group 2 analog input 2

AI3

GROUP SIGNAL

Group 2 analog input 3

AI4

GROUP SIGNAL

Group 2 analog input 4

AIN

GROUP SIGNAL

Group 2 analog input residual for disturbance


recorder

Setting parameters
Settings DFTRefExtOut and DFTReference shall be set to default
value InternalDFTRef if no VT inputs are available. Internal
nominal frequency DFT reference is then the reference.

102
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 48:

SMAI1 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

DFTRefExtOut

InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref

InternalDFTRef

DFT reference for external output

DFTReference

InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref

InternalDFTRef

DFT reference

ConnectionType

Ph-N
Ph-Ph

Ph-N

Input connection type

TYPE

1-2

Ch

1=Voltage, 2=Current

Table 49:

SMAI1 Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

Negation

Off
NegateN
Negate3Ph
Negate3Ph+N

Off

Negation

MinValFreqMeas

5 - 200

10

Limit for frequency calculation in % of


UBase

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

103
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

Table 50:

SMAI2 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

DFTReference

InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref

InternalDFTRef

DFT reference

ConnectionType

Ph-N
Ph-Ph

Ph-N

Input connection type

TYPE

1-2

Ch

1=Voltage, 2=Current

Table 51:
Name

SMAI2 Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

Negation

Off
NegateN
Negate3Ph
Negate3Ph+N

Off

Negation

MinValFreqMeas

5 - 200

10

Limit for frequency calculation in % of


UBase

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

4.13

Summation block 3 phase 3PHSUM

4.13.1

Introduction
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.

4.13.2

Principle of operation
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.

104
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.13.3

Function block
3PHSUM
BLOCK
DFTSPFC
G1AI3P*
G2AI3P*

AI3P
AI1
AI2
AI3
AI4
IEC05000441-2-en.vsd

IEC05000441 V2 EN

Figure 43:

4.13.4

3PHSUM function block

Input and output signals


Table 52:

3PHSUM Input signals

Name

Type

Description

BOOLEAN

Block

DFTSPFC

REAL

Number of samples per fundamental cycle used


for DFT calculation

G1AI3P

GROUP
SIGNAL

Group 1 analog input 3-phase group

G2AI3P

GROUP
SIGNAL

Group 2 analog input 3-phase group

Table 53:

3PHSUM Output signals

Name

4.13.5

Default

BLOCK

Type

Description

AI3P

GROUP SIGNAL

Group analog input 3-phase group

AI1

GROUP SIGNAL

Group 1 analog input

AI2

GROUP SIGNAL

Group 2 analog input

AI3

GROUP SIGNAL

Group 3 analog input

AI4

GROUP SIGNAL

Group 4 analog input

Setting parameters
Settings DFTRefExtOut and DFTReference shall be set to default
value InternalDFTRef if no VT inputs are available.

Table 54:

3PHSUM Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SummationType

Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)

Group1+Group2

Summation type

DFTReference

InternalDFTRef
AdDFTRefCh1
External DFT ref

InternalDFTRef

DFT reference

105
Technical reference manual

Section 4
Basic IED functions

Table 55:
Name

1MRK 505 222-UEN B

3PHSUM Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

FreqMeasMinVal

5 - 200

10

Amplitude limit for frequency calculation


in % of Ubase

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

4.14

Authority status ATHSTAT

4.14.1

Introduction
Authority status (ATHSTAT) function is an indication function block for user logon activity.

4.14.2

Principle of operation
Authority status (ATHSTAT) function informs about two events related to the IED
and the user authorization:

the fact that at least one user has tried to log on wrongly into the IED and it
was blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)

Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC
61850 station bus.

4.14.3

Function block
ATHSTAT
USRBLKED
LOGGEDON
IEC06000503-2-en.vsd
IEC06000503 V2 EN

Figure 44:

4.14.4

ATHSTAT function block

Output signals
Table 56:
Name

ATHSTAT Output signals


Type

Description

USRBLKED

BOOLEAN

At least one user is blocked by invalid password

LOGGEDON

BOOLEAN

At least one user is logged on

106
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

4.14.5

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

4.15

Denial of service DOS

4.15.1

Introduction
The Denial of service functions (DOSFRNT, DOSOEMAB and DOSOEMCD) are
designed to limit overload on the IED produced by heavy Ethernet network traffic.
The communication facilities must not be allowed to compromise the primary
functionality of the device. All inbound network traffic will be quota controlled so
that too heavy network loads can be controlled. Heavy network load might for
instance be the result of malfunctioning equipment connected to the network.

4.15.2

Principle of operation
The Denial of service functions (DOSFRNT, DOSOEMAB and DOSOEMCD)
measures the IED load from communication and, if necessary, limit it for not
jeopardizing the IEDs control and protection functionality due to high CPU load.
The function has the following outputs:

4.15.3

LINKUP indicates the Ethernet link status


WARNING indicates that communication (frame rate) is higher than normal
ALARM indicates that the IED limits communication

Function blocks
DOSFRNT
LINKUP
WARNING
ALARM
IEC09000749-1-en.vsd
IEC09000749 V1 EN

Figure 45:

DOSFRNT function block

DOSOEMAB
LINKUP
WARNING
ALARM
IEC09000750-1-en.vsd
IEC09000750 V1 EN

Figure 46:

DOSOEMAB function block

107
Technical reference manual

Section 4
Basic IED functions

1MRK 505 222-UEN B

DOSOEMCD
LINKUP
WARNING
ALARM
IEC09000751-1-en.vsd
IEC09000751 V1 EN

Figure 47:

4.15.4

Signals
Table 57:
Name

DOSFRNT Output signals


Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Table 58:
Name

DOSOEMAB Output signals


Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Table 59:
Name

4.15.5

DOSOEMCD function block

DOSOEMCD Output signals


Type

Description

LINKUP

BOOLEAN

Ethernet link status

WARNING

BOOLEAN

Frame rate is higher than normal state

ALARM

BOOLEAN

Frame rate is higher than throttle state

Settings
The function does not have any parameters available in the local HMI or PCM600.

108
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Section 5

Differential protection

About this chapter


This chapter describes the measuring principles, functions and parameters used in
differential protection.

5.1

Line differential protection


Function description

Line differential protection, 3 CT sets,


2-3 line ends

IEC 61850
identification

L3CPDIF

IEC 60617
identification

3Id/I>

ANSI/IEEE C37.2
device number

87L

SYMBOL-HH V1 EN

Line differential protection, 6 CT sets,


3-5 line ends

L6CPDIF

3Id/I>

87L

SYMBOL-HH V1 EN

Line differential protection 3 CT sets,


with in-zone transformers, 2-3 line ends

LT3CPDIF

3Id/I>

87LT

SYMBOL-HH V1 EN

Line differential protection 6 CT sets,


with in-zone transformers, 3-5 line ends

LT6CPDIF

Line differential logic

LDLPDIF

3Id/I>

87LT

SYMBOL-HH V1 EN

87L

5.1.1

Introduction

5.1.1.1

Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF


Line differential protection applies the Kirchhoff's law and compares the currents
entering and leaving the protected multi-terminal circuit, consisting of overhead
109

Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

power lines, power transformers and cables. It offers phase-segregated true current
differential protection with high sensitivity and provides phase selection
information for single-pole tripping.
The three terminal version is used for conventional two-terminal lines with or
without 1 1/2 circuit breaker arrangement in one end, as well as three terminal lines
with single breaker arrangements at all terminals.
Protected zone

Comm. Channel

IED

IED

IEC05000039_2_en.vsd
IEC05000039 V2 EN

Figure 48:

Example of application on a conventional two-terminal line

The six terminal versions are used for conventional two-terminal lines with 1 1/2
circuit breaker arrangements in both ends, as well as multi terminal lines with up to
five terminals.
Protected zone

Comm. Channel

IED

IED

Comm. Channel

Comm. Channel
IED

IEC05000040_2_en.vsd
IEC05000040 V2 EN

Figure 49:

Example of application on a three-terminal line with 1 1/2 breaker


arrangements

The current differential algorithm provides high sensitivity for internal faults, at the
same time as it has excellent stability for external faults. Current samples from all
CTs are exchanged between the IEDs in the line ends (master-master mode) or sent
to one IED (master-slave mode) for evaluation.
A restrained dual biased slope evaluation is made where the bias current is the
highest phase current in any line end giving a secure through fault stability even
with heavily saturated CTs. In addition to the restrained evaluation, an unrestrained
high differential current setting can be used for fast tripping of internal faults with
very high currents.
A special feature with this function is that applications with small power
transformers (rated current less than 50 % of the differential current setting)
connected as line taps (that is, as "shunt" power transformers), without
measurements of currents in the tap, can be handled. The normal load current is
110
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

here considered to be negligible, and special measures need only to be taken in the
event of a short circuit on the LV side of the transformer. In this application, the
tripping of the differential protection can be time delayed for low differential
currents to achieve coordination with down stream over current IEDs.
A line charging current compensation provides increased sensitivity of Line
differential protection.

5.1.1.2

Line differential protection 3 or 6 CT sets, with in-zone transformers


LT3CPDIF, LT6CPDIF
Two two-winding power transformers, or one three-winding power transformer,
can be included in the line differential protection zone. Both two- and threewinding transformers are correctly represented with vector group compensations
made in the algorithm. The function includes 2nd and 5th harmonic restraint and zerosequence current elimination.
Protected zone

Comm. Channel

IED

Comm. Channel

IED

Comm. Channel
IED
IEC05000042_2_en.vsd

IEC05000042 V2 EN

Figure 50:

5.1.1.3

Example of application on a three-terminal line with a power


transformer in the protection zone

Analog signal transfer for line differential protection


The line differential communication can be arranged as a master-master system or
a master-slave system alternatively. In the former, current samples are exchanged
between all IEDs, and an evaluation is made in each IED. This means that a 64 kbit/
s communication channel is needed between every IED included in the same line
differential protection zone. In the latter, current samples are sent from all slave
IEDs to one master IED where the evaluation is made, and trip signals are sent to
the remote ends when needed. In this system, a 64 kbit/s communication channel is
only needed between the master, and each one of the slave IEDs.

111
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Protected zone

IED

IED

Comm.
Channels
IED

IED

IED
IEC0500043_2_en.vsd

IEC05000043 V2 EN

Figure 51:

Five terminal lines with master-master system


Protected zone

RED
670

RED
670

Comm.
Channels
RED
670

RED
670

RED
670
en05000044.vsd

IEC05000044 V1 EN

Figure 52:

Five terminal line with master-slave system

Current samples from IEDs located geographically apart from each other, must be
time coordinated so that the current differential algorithm can be executed
correctly. In IED, it is possible to make this coordination in two different ways.
The echo method of time synchronizing is normally used whereas for applications
where transmit and receive times can differ, the optional built in GPS receivers can
be used.
The communication link is continuously monitored, and an automatic switchover
to a standby link is possible after a preset time.

5.1.2

Principle of operation

5.1.2.1

Algorithm and logic


In Line differential protection function, measured current values from local and
remote line ends are evaluated in order to distinguish between internal or external
faults, or undisturbed conditions.
The local currents are fed to the IED via the Analog Input Modules and thereafter
they pass the Analog to Digital Converter, as shown in figure 53.

112
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Remote end

Local end

Remote end IED

LDCM

Local end IED

Analog Input
Module

A/D
Converter

LDCM

Current
samples from
local end
Current
samples from
remote end

Pre-processing
Block

Calculation of

CH1IL2RE

fundamental
frequency
differential
currents (3x)
& bias current

CH1IL2IM
Currents from
all ends as
phasors

Magnitudes of
differential
currents
Bias current

Trip by unrestrained differential protection


Differential
and bias currents
applied to
operate / bias -,
and unrestrained

Start L2

St L1 low sens
St L2 low sens
St L3 low sens

CH1IL2SM
CH1IL3SM
CH2IL1SM
Curr. samples
from all ends

Calculation
of
instantaneous
differential
currents
(3x)

2nd h. block

[samples]

Instantaneous
differential
currents
(samples)

Harmonic
analysis
( 2nd and 5th)

Output logic:

Start L3

characteristics

CH1IL1SM

5th h. block

- 2nd
- 5th
-

CH1INSIM
CH1INSRE
CH1INSIM
Neg. seq.
currents from
all ends
as phasors

Two to six
contributions
to neg. seq.
differential
current as
phasors

High sensitive
internal/external fault
discriminator

Cross block logic

- Decreased
sensitivity for
external faults

Internal fault
External fault

harmonic block
harmonic block

- Enhanced trip for


internal faults

CH1INSRE
Calculation
of
negative-sequence
differential
current
(1x)

TRIP

Start L1

Conditional trip for


simultaneous external
and internal faults

Conditional extra time


delay for trip signals

TRL1
TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA

START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3

Information

[magnitude]

CH1IL1RE
CH1IL1IM

Trip commands

Line Diffferential Function

BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
INTFAULT
EXTFAULT

IEC05000294_2_en.vsd
IEC05000294 V2 EN

Figure 53:

The principle for the line differential protection

The remote currents are received to the IED as samples via a communication link.
When entering the IED, they are processed in the Line Differential Communication
Module (LDCM) where they are time coordinated with the local current samples,
and interpolated in order to be comparable with the local samples.
113
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

In the Pre-Processing Block, the real and imaginary parts of the fundamental
frequency phase currents and negative sequence currents are derived. Together
with the current samples, they are then forwarded to the differential function block
where three different analyses are carried out.
The first analysis is the classical differential and bias current evaluation with the
characteristic as seen in figure 54. Line differential protection is phase segregated
where the differential current is the vectorial sum of all measured currents taken
separately for each phase. The bias current, on the other hand, is considered as the
greatest phase current in any line end and it is common for all three phases. The
two slopes (SlopeSection1, SlopeSection2) and breakpoints (EndSection1,
EndSection2) can be set in PCM600 or via the local HMI.
Current values plotted above the characteristic formed by IdMin and the dual slope
will give a start in that phase. The level IdMinHigh is a setting value that is used to
temporarily decrease the sensitivity in situations when:

the line is energized


when a fault is classified as external
when a tap transformer is switched in

There is also an unrestrained high differential current setting that can be used for
fast tripping of internal faults with very high currents.

114
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Operate current
[ in pu of IBase]

Operate

unconditionally
UnrestrainedLimit

Operate

IdMinHigh

conditionally
A

2
Section 1

Section 2

Section 3
SlopeSection3

1
IdMin
SlopeSection2

Restrain

0
0

EndSection1
EndSection2

Restrain current
[ in pu of IBase]

en05000300.vsd
IEC05000300 V1 EN

Figure 54:

Description of the restrained-, and the unrestrained operate


characteristics

where:

slope = D Ioperate 100%


D Irestrain
EQUATION1246 V1 EN

and where the restrained characteristic is defined


by the settings:

1.

IdMin

2.

EndSection1

3.

EndSection2

4.
5.

SlopeSection2
SlopeSection3

The second analysis is the 2nd and 5th harmonic analysis on the differential current.
Occurrence of these harmonics over a level that is set separately for each one will
block tripping action from the biased slope evaluation.

115
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

The third analysis is the negative sequence current analysis. Effectively this is a
fault discriminator that distinguishes between internal and external faults. It works
such that the phase angle of the negative sequence current from the local end is
compared with the phase angle of the sum of the negative sequence currents from
the remote ends. The characteristic for this fault discriminator is shown in
figure 55, where the directional characteristic is defined by the two setting
parameters IminNegSeq and NegSeqRoa.
90 deg
120 deg
If one or the
other of
currents is too
low, then no
measurement
is done, and
120 degrees
is mapped

Internal/external
fault boundary

NegSeqROA
(Relay
Operate
Angle)

180 deg

0 deg

IMinNegSeq

External
fault
region

Internal
fault
region

270 deg

en05000188-2-en.vsd

IEC05000188 V2 EN

Figure 55:

Operating characteristic of the internal/external fault discriminator

Reference direction of currents is considered to be towards the line. Thus, when


both currents to be compared have this direction, the phase difference between
them will ideally be zero. In the opposite case, when one current is entering and the
other is leaving the protected object, the phase difference will ideally be 180
degree. In case either the local or the sum of the remote negative sequence currents
or both is below the set level, the fault discriminator will not make any fault
classification and the value 120 degree is set. This value is then an indication that
negative sequence directional comparison has not been possible to make, and it
does not mean classification as external fault.
When a fault is classified as internal by the negative sequence fault discriminator, a
trip is issued under the condition that the dual slope restrained function has started ,
while a classification as external fault results in an increase of the restrained
characteristic trip values IdMinHigh.

116
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

With reference to figure 53, the outputs from the three analysis blocks are fed to
the output logic. Figure 56 shows a simplified block diagram of this output logic
where only trip commands and no alarm signals are shown for simplicity.
Trip unrestrained L1
Trip unrestrained L2

OR

TRIP

Trip unrestrained L3
Start L1

AND

OR

Start L2

AND

TRL1

OR

Start L3

OR

AND

TRL2

AND

OR

OR
OR

AND
OR

St L1 IdMinHigh

OR

OR

St L2 IdMinHigh

TRL3

AND

St L3 IdMinHigh

Internal fault

AND

NegSeqDiffEn

tIdMinHigh
t

AND

External fault

OR

Line energizing

Diff curr L1 2nd harm

AND

OR

Diff curr L2 2nd harm


Diff curr L3 2nd harm

AND

OR

Diff curr L1 5th harm

OR

OR

AND

th

Diff curr L2 5 harm

OR

OR

Diff curr L3 5th harm

OR

AND

CrossBlockEn

IEC05000295-2-en.vsd
IEC05000295 V2 EN

Figure 56:

Simplified block diagram

Remembering that current values plotted above the characteristic formed by IdMin
and the dual slope in figure 55 are said to give a start, the output logic can be
summarized as follows:

A start in one phase, gives a trip under the condition that the content of 2nd and
5th harmonic is below the set level for these harmonics. Otherwise it is blocked
117

Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

as long as the harmonic is above the set level. However, when a line is
energized the current setting value IdMinHigh is used. Effectively this means
that the line A-B-C in figure 54 forms the characteristic.
Current values above the unrestrained limit gives a trip irrespective of any
presence of harmonics.
Classification of a fault as internal by the negative sequence fault
discriminator, will give a trip under the condition that a start has occurred in
that phase. This means that any harmonic blocking is then overridden.
However, occurrence of harmonics at the same time as the differential current
is below the level IdMinHigh, will block a trip even though the fault is
classified as internal. This latter condition is to prevent unwanted trips when
energizing a line tap transformer.
Classification of a fault as external by the negative sequence fault
discriminator will cause IdMinHigh to be used as the lower limit for the
restrained characteristic according to figure 54. Cross blocking will also be
activated in this situation.

Compensation for charging currents can be selected active or not by setting


ChargCurEnableYes or No. The compensation works such that the fundamental
frequency differential current that is measured under steady state undisturbed
conditions, is identified and then subtracted making the resulting differential
current zero (or close to zero). This action is made separately for each phase. The
magnitude of the subtracted pre-fault currents in Amperes can be read at any time
as the service value ICHARGE.
Values of the pre-fault differential currents are not updated under disturbance
conditions. The updating process is resumed 50 ms after normal conditions have
been restored. Normal conditions are only considered if there are no start signals,
neither internal nor external fault is declared, the power system is symmetrical and
so on.
It is thus obvious that the change in charging current that the fault causes by
decreasing the system voltage is not considered in the algorithm, a matter that is
further discussed in the application manual.
Note that all small pre-fault differential currents are subtracted, no matter what
their origin. Besides the true charging currents, the following currents are eliminated:

5.1.2.2

Small differential currents due to small errors (inequalities) of current


transformers.
Small differential currents because of off-nominal load tap changer positions
when a power transformer is included in the protected zone.
Load currents of tap loads included in the protected zone.

Time synchronization
In a numerical line differential protection, current samples from protections located
geographically apart from each other, must be time coordinated so that the currents

118
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

from the different line ends can be compared without introducing irrelevant errors.
Accuracy requirements on this time coordination are extremely high.
As an example, an inaccuracy of 0.1 ms in a 50 Hz system gives a maximum
amplitude error approximately around 3% whilst an inaccuracy of 1 ms gives a
maximum amplitude error of approximately 31%. The corresponding figures for a
60 Hz system are 4% and 38% respectively.
In Line differential protection, the time coordination is made with the so-called
echo method, which can be complemented with GPS synchronization as an option.
Each IED has an accurate local clock with a very small time drift. This clock
makes time tagging of telegrams, and the echo method is then used to find out the
time difference between the clocks in two ends of a power line.
Referring to figure 57, it works such that the transmission time to send a message
from station B to station A (T1 T2) and receive a message from A to B (T3
T4) is measured. The time instances T2 and T3 are taken with the local clock
reference of station A, and the time instances T1 and T4 are taken with the local
clock reference of station B.

T2

A
B

T1

T3

T4
en05000293.vsd

IEC05000293 V1 EN

Figure 57:

Measuring time differences

Calculation of the delay time one-way Td and the time difference t between the
clocks in A and B is then possible to do with equation 2 and equation 3, which are
only valid under the condition that the send and receive times are equal.
Td =

(T2 - T1 ) + (T4 - T3 )
2

EQUATION1358 V1 EN

Dt =

(Equation 2)

(T1 + T4 ) - (T2 + T3 )
2

EQUATION1359 V1 EN

(Equation 3)

t is calculated every time a telegram is received, and the time difference is then
used to adjust and interpolate the current measurements from the remote end before
the current differential algorithm is executed.

119
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

The echo method without GPS, can be used in telecommunications transmission


networks with varying signal propagation delay as long as there is delay symmetry,
that is, the send and receive delays are equal. The delay variation can depend on
the signal going different routes in the network from time to other.
When the delay symmetry is lost, the expression for t given above is no longer
valid, and GPS synchronization of the local IED clocks must be used.
Including the optional GPS, means that there will be one GPS receiver module in
each IED, synchronizing its local IED clock. As GPS synchronization is very
accurate, in the order of 1 s, all IEDs in the same line differential scheme will
have the same clock reference. It is then possible to detect asymmetric transmission
time delay and compensate for it.
When the IED is equipped with GPS, this hardware is integrated in the IED.
Besides the GPS receiver itself, it also consists of filters and regulators for post
processing of the GPS time synch pulse, which is necessary to achieve a reliable
GPS synchronization. Especially short interruptions and spurious out of synch GPS
signals are handled securely in this way.
When GPS synchronization is used, an interruption in the GPS signal leads to
freewheeling during 8 seconds that is, during this time the synchronization benefits
from the stability in the local clocks. If the interruption persists more than 8
seconds, either fall back to the echo synchronization method or blocking of Line
differential protection function is made, as selected through setting parameter
GPSSyncErr.
For a description of the time synchronization function, refer to section "Time
synchronization".

5.1.2.3

Analog signal communication for line differential protection


Communication principle

For a two-terminal line, the current from the local CT needs to be communicated
over a 64 kbit/s channel to the remote line end, and the remote end current
communicated back on the same channel. If there is, for example, a three terminal
line another 64 kbit/s channel will be needed to exchange the same local current
with the third line end current.
In one-and-a-half breaker arrangements, there are two local currents meaning two
64 kbit/s channels to each remote substation. Alternatively, it is possible to add
together the two local currents before sending them and in that way reduce the
number of communication channels needed. This is achieved by selecting proper
setting for parameter TransmCurr (CT-SUM, CT-DIFF1 or CT-DIFF2). However,
information about bias currents is reduced if the alternative option is followed. For
further information and discussions on this matter, refer to the Application manual.
The communication can be arranged as a master-master system or a master-slave
system alternatively. Figure 58 shows a master-master system for a five-terminal
line. Here current samples are exchanged between all IEDs, and an evaluation is
120
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

made in each IED. This means that a 64 kbit/s communication channel is needed
between every IED included in the same line differential protection zone.
Protected zone

IED

IED
Comm. Channels

IED

IED

IED
IEC05000292_2_en.vsd

IEC05000292 V2 EN

Figure 58:

5terminal line with master-master system

In the master-slave system, current samples are sent from all slave IEDs to one
master IED where the evaluation is made and trip signals are sent to the remote
ends when needed. In this system, a 64 kbit/s communication channel is only
needed between the master, and each one of the slave IEDs, as shown in figure 59.
Protected zone

IED

IED

Comm. Channels

IED

IED

IED
IEC05000291_2_en.vsd

IEC05000291 V2 EN

Figure 59:

5terminal line with master-slave system

The master-slave configuration is achieved by setting parameter Operation in the


slaves to Off for Line differential protection function, and setting parameter
ChannelMode to On for the LDCMs in the slaves.

Test mode

Line differential protection function in one IED can be set in test mode. This can
block the trip outputs on that IED, and set the remote IEDs in a remote test mode,
so that injected currents can be echoed back phase shifted and with a settable
amplitude. The trip outputs in the remote IEDs can also be blocked automatically.
For further information, refer to the installation and commissioning manual.

Communication of current sampled values

The currents are sampled twenty times per power system cycle in the protection
terminals, but the communication exchange is made only once every 5 ms. This
121
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

means that at in each telegram sent, 5 consecutive current samples in a 50 Hz


system and 6 consecutive current samples in a 60 Hz system (three phases each
sampling instant) are included. Figure 60 shows the principle.
Current
sample
telegram
sent

Current
sample
telegram
sent

Current
sample
telegram
sent

Current
sample
telegram
sent

Current
sample
telegram
sent

Current
sample
telegram
sent

Current
sample
telegram
sent

10

15

20

25

30

35

Current
sample
telegram
sent

Time
(ms)
en05000290.vsd

IEC05000290 V1 EN

Figure 60:

Communication of current sampled values.

where:
x

is the current sampling moment

Redundant communication channels

With redundant communication channels, as shown in figure 61, both channels are
in operation continuously but with one of them favoured as a primary channel.

Telecom. Network
LD
CM
LD
CM

IEC05000289 V1 EN

Figure 61:

Telecom. Network

Primary
channel
Secondary redundant
channel

LD
CM
LD
CM

en05000289.vsd

Direct fibre optical connection between two IEDs with LDOM over
longer distances.

If communication is lost on the primary channel, switchover to the secondary


channel is made after a settable time delay RedChSwTime. Return of the primary
channel will cause a switchback after another settable time delay RedChRturnTime.
For a three-, four- or five-terminals line in a master-master configuration, a loss of
one communication channel will not cause the line differential protection to be
122
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

unserviceable. Instead it will automatically revert to a partial master-slave mode


with the two IEDs that have an unserviceable communication link between them,
will serve as slaves.
For more details about the remote communication see section "Remote
communication" and the application manual.

5.1.2.4

Open CT detection feature


Line differential protection has a built-in, advanced open CT detection feature.
The open CT circuit condition creates unexpected operations for Line differential
protection under the normal load conditions. It is also possible to damage
secondary equipment due to high voltage produced from open CT circuit outputs.
Therefore, it is always a requirement from security and reliability points of view to
have open CT detection function to block Line differential protection function in
case of open CT conditions and at the same time, produce the alarm signal to the
operational personal to make quick remedy actions to correct the open CT condition.
The built-in open CT feature can be enabled or disabled by a setting parameter
OpenCTEnable (Off/On). When enabled, this feature prevents mal-operation when
a loaded main CT connected to Line differential protection is by mistake open
circuited on the secondary side. Note that this feature can only detect interruption
of one CT phase current at the time. If two or even all three-phase currents of one
set of CT are accidentally interrupted at the same time this feature cannot operate
and Line differential protection generates trip signal, if the false differential current
is sufficiently high. To ensure blocking of the differential protection for open CT
condition this algorithm must operate within 10 ms in order to be able to prevent
unwanted operation of Line differential protection under all loading conditions.
The principle applied to detect an open CT is a simple pattern recognition method,
similar to the waveform check which has been with advantage used by the Power
Transformer Differential Protection in order to detect the magnetizing inrush
condition. The open CT detection principle is based on the fact, that for an open
CT, the current in the phase with the open CT suddenly drops (at least
theoretically) to zero (that is, as seen by the protection), while the currents of the
other two phases continue as before.
The open CT function is supposed to detect an open CT under normal conditions,
that is, with the protected multi-terminal circuit under normal load. If the load
currents are very low or zero, the open CT condition cannot be detected. The open
CT algorithm only detects an open CT if the load on the power transformer is from
10% to 110% of the rated load. Outside this range an open CT condition is not
even looked for. The search for an open CT starts after 60 seconds (50 seconds in
60 Hz systems) since the bias current enters the 10110% range. The Open CT
detection feature can also be explicitly deactivated by setting: OpenCTEnable = 0
(Off).
If an open CT is detected and the output OPENCT set to 1, then all the differential
functions are blocked, except of the unrestrained (instantaneous) differential. An
123

Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

alarm signal is also produced after a settable delay (tOCTAlarmDelay) to report to


operational personal for quick remedy actions once the open CT is detected. When
the open CT condition is removed (that is, the previously open CT reconnected),
the functions remain blocked for a specified interval of time, which is also a setting
(tOCTResetDelay). The task of this measure is to prevent an eventual maloperation after the reconnection of the previously open CT secondary circuit.
The open CT feature works only during normal loading condition. Thus, the open
CT feature must be automatically disabled for all external faults, big overloads and
inrush conditions.
The open CT algorithm provides detailed information about the location of the
defective CT secondary circuit. The algorithm clearly indicates IED side, CT input
and phase in which open CT condition has been detected. These indications are
provided via the following outputs from Line differential protection function:
1.
2.
3.
4.

Output OPENCT provides instant information to indicate that open CT circuit


has been detected
Output OPENCTAL provides time delayed alarm that the open CT circuit has
been detected. Time delay is defined by setting parameter tOCTAlarmDelay.
Integer output OPENCTIN provides information on the local HMI regarding
which open CT circuit has been detected (1=CT input No 1; 2=CT input No 2)
Integer output OPENCTPH provides information on the local HMI regarding
in which phase open CT circuit has been detected (1=Phase L1; 2= Phase L2;
3= Phase L3)

Once the open CT condition is declared, the algorithm stops to search for further
open CT circuits. It waits until the first open CT circuit has been corrected. Note
that once the open CT condition has been detected, it can be automatically reset
within the differential function. It is not possible to externally reset open CT
condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:

Bias current is for at least one minute smaller than 110%


Open CT condition in defective CT circuit has been rectified (for example,
current asymmetry disappears)
Above two conditions are fulfilled for longer time than defined by the setting
parameter tOCTResetDelay

After the reset, the open CT detection algorithm starts again to search for any other
open CT circuit within the protected zone.

5.1.2.5

Binary signal transfer


There is space for eight binary signals integrated in the telegram of the line
differential analog communication. For further information, refer to section
"Binary signal transfer".

124
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

5.1.2.6

Line differential coordination function LDLPDIF


Line differential coordination function (LDLPDIF) is a support function to Line
differential protection functions L3CPDIF, L6CPDIF , LT3CPDIF and LT6CPDIF.
The function gathers and coordinates local IED signals and the signals from remote
IEDs between the Line differential protection functions and the LDCM
communication module.
The function acts as the interface to and from Line differential protection.

5.1.3

Function block
L3CPDIF
I3P1*
I3P2*
I3P3*

TRIP
TRL1
TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000252-2-en.vsd

IEC06000252 V2 EN

Figure 62:

L3CPDIF function block

125
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

L6CPDIF
I3P1*
I3P2*
I3P3*
I3P4*
I3P5*
I3P6*

TRIP
TRL1
TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000253-2-en.vsd

IEC06000253 V2 EN

Figure 63:

L6CPDIF function block

LT3CPDIF
I3P1*
I3P2*
I3P3*

TRIP
TRL1
TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000254_2_en.vsd

IEC06000254 V2 EN

Figure 64:

LT3CPDIF function block

126
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

LT6CPDIF
I3P1*
I3P2*
I3P3*
I3P4*
I3P5*
I3P6*

TRIP
TRL1
TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000255_2_en.vsd

IEC06000255 V2 EN

Figure 65:

LT6CPDIF function block


LDLPDIF

CTFAIL
OUTSERV
BLOCK

TRIP
TRL1
TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD
IEC05000394-2-en.vsd

IEC05000394 V3 EN

Figure 66:

5.1.4

LDLPDIF function block

Input and output signals


Table 60:
Name

L3CPDIF Input signals


Type

Default

Description

I3P1

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P2

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P3

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

127
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 61:
Name

L3CPDIF Output signals


Type

Description

TRIP

BOOLEAN

Common, main, trip output signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TRIPRES

BOOLEAN

Trip by restrained differential protection

TRIPUNRE

BOOLEAN

Trip by unrestrained differential protection

TRIPENHA

BOOLEAN

Trip by enhanced restrained differential protection

START

BOOLEAN

Common, main, start output signal

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

BLK2H

BOOLEAN

Common block signal, due to 2nd harmonic

BLK2HL1

BOOLEAN

Block signal due to 2nd harmonic, phase L1

BLK2HL2

BOOLEAN

Block signal due to 2nd harmonic, phase L2

BLK2HL3

BOOLEAN

Block signal due to 2nd harmonic, phase L3

BLK5H

BOOLEAN

Common block signal, due to 5-th harmonic

BLK5HL1

BOOLEAN

Block signal due to 5th harmonic, phase L1

BLK5HL2

BOOLEAN

Block signal due to 5th harmonic, phase L2

BLK5HL3

BOOLEAN

Block signal due to 5th harmonic, phase L3

OPENCT

BOOLEAN

An open CT was detected

ALARM

BOOLEAN

Alarm for sustained differential current

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a


delay ...

IDL1

REAL

Instantaneous differential current, phase L1

IDL2

REAL

Instantaneous differential current, phase L2

IDL3

REAL

Instantaneous differential current, phase L3

IDL1MAG

REAL

Magnitude of fund. freq. differential current,


phase L1

IDL2MAG

REAL

Magnitude of fund. freq. differential current,


phase L2

IDL3MAG

REAL

Magnitude of fund. freq. differential current,


phase L3

IBIAS

REAL

Magnitude of the bias current, common for L1,


L2, L3

IDNSMAG

REAL

Magnitude of the negative sequence differential


current

128
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 62:
Name

L6CPDIF Input signals


Type

Default

Description

I3P1

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P2

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P3

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P4

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P5

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P6

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

Table 63:
Name

L6CPDIF Output signals


Type

Description

TRIP

BOOLEAN

Common, main, trip output signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TRIPRES

BOOLEAN

Trip by restrained differential protection

TRIPUNRE

BOOLEAN

Trip by unrestrained differential protection

TRIPENHA

BOOLEAN

Trip by enhanced restrained differential protection

START

BOOLEAN

Common, main, start output signal

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

BLK2H

BOOLEAN

Common block signal, due to 2nd harmonic

BLK2HL1

BOOLEAN

Block signal due to 2nd harmonic, phase L1

BLK2HL2

BOOLEAN

Block signal due to 2nd harmonic, phase L2

BLK2HL3

BOOLEAN

Block signal due to 2nd harmonic, phase L3

BLK5H

BOOLEAN

Common block signal, due to 5-th harmonic

BLK5HL1

BOOLEAN

Block signal due to 5th harmonic, phase L1

BLK5HL2

BOOLEAN

Block signal due to 5th harmonic, phase L2

BLK5HL3

BOOLEAN

Block signal due to 5th harmonic, phase L3

OPENCT

BOOLEAN

An open CT was detected

ALARM

BOOLEAN

Alarm for sustained differential current

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a


delay ...

IDL1

REAL

Instantaneous differential current, phase L1

IDL2

REAL

Instantaneous differential current, phase L2

Table continues on next page

129
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

Type

Description

IDL3

REAL

Instantaneous differential current, phase L3

IDL1MAG

REAL

Magnitude of fund. freq. differential current,


phase L1

IDL2MAG

REAL

Magnitude of fund. freq. differential current,


phase L2

IDL3MAG

REAL

Magnitude of fund. freq. differential current,


phase L3

IBIAS

REAL

Magnitude of the bias current, common for L1,


L2, L3

IDNSMAG

REAL

Magnitude of the negative sequence differential


current

Table 64:
Name

LT3CPDIF Input signals


Type

Default

Description

I3P1

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P2

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P3

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

Table 65:
Name

LT3CPDIF Output signals


Type

Description

TRIP

BOOLEAN

Common, main, trip output signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TRIPRES

BOOLEAN

Trip by restrained differential protection

TRIPUNRE

BOOLEAN

Trip by unrestrained differential protection

TRIPENHA

BOOLEAN

Trip by enhanced restrained differential protection

START

BOOLEAN

Common, main, start output signal

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

BLK2H

BOOLEAN

Common block signal, due to 2nd harmonic

BLK2HL1

BOOLEAN

Block signal due to 2nd harmonic, phase L1

BLK2HL2

BOOLEAN

Block signal due to 2nd harmonic, phase L2

BLK2HL3

BOOLEAN

Block signal due to 2nd harmonic, phase L3

BLK5H

BOOLEAN

Common block signal, due to 5-th harmonic

BLK5HL1

BOOLEAN

Block signal due to 5th harmonic, phase L1

BLK5HL2

BOOLEAN

Block signal due to 5th harmonic, phase L2

Table continues on next page

130
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

Type

Description

BLK5HL3

BOOLEAN

Block signal due to 5th harmonic, phase L3

OPENCT

BOOLEAN

An open CT was detected

ALARM

BOOLEAN

Alarm for sustained differential current

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a


delay ...

IDL1

REAL

Instantaneous differential current, phase L1

IDL2

REAL

Instantaneous differential current, phase L2

IDL3

REAL

Instantaneous differential current, phase L3

IDL1MAG

REAL

Magnitude of fund. freq. differential current,


phase L1

IDL2MAG

REAL

Magnitude of fund. freq. differential current,


phase L2

IDL3MAG

REAL

Magnitude of fund. freq. differential current,


phase L3

IBIAS

REAL

Magnitude of the bias current, common for L1,


L2, L3

IDNSMAG

REAL

Magnitude of the negative sequence differential


current

Table 66:
Name

LT6CPDIF Input signals


Type

Default

Description

I3P1

GROUP
SIGNAL

Three phase current grp1 samples and DFT values

I3P2

GROUP
SIGNAL

Three phase current grp2 samples and DFT values

I3P3

GROUP
SIGNAL

Three phase current grp3 samples and DFT values

I3P4

GROUP
SIGNAL

Three phase current grp4 samples and DFT values

I3P5

GROUP
SIGNAL

Three phase current grp5 samples and DFT values

I3P6

GROUP
SIGNAL

Three phase current grp6 samples and DFT values

Table 67:
Name

LT6CPDIF Output signals


Type

Description

TRIP

BOOLEAN

Common, main, trip output signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TRIPRES

BOOLEAN

Trip by restrained differential protection

TRIPUNRE

BOOLEAN

Trip by unrestrained differential protection

TRIPENHA

BOOLEAN

Trip by enhanced restrained differential protection

Table continues on next page


131
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

Type

Description

START

BOOLEAN

Common, main, start output signal

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

BLK2H

BOOLEAN

Common block signal, due to 2nd harmonic

BLK2HL1

BOOLEAN

Block signal due to 2nd harmonic, phase L1

BLK2HL2

BOOLEAN

Block signal due to 2nd harmonic, phase L2

BLK2HL3

BOOLEAN

Block signal due to 2nd harmonic, phase L3

BLK5H

BOOLEAN

Common block signal, due to 5-th harmonic

BLK5HL1

BOOLEAN

Block signal due to 5th harmonic, phase L1

BLK5HL2

BOOLEAN

Block signal due to 5th harmonic, phase L2

BLK5HL3

BOOLEAN

Block signal due to 5th harmonic, phase L3

OPENCT

BOOLEAN

An open CT was detected

ALARM

BOOLEAN

Alarm for sustained differential current

OPENCTAL

BOOLEAN

Open CT Alarm output signal. Issued after a


delay ...

IDL1

REAL

Instantaneous differential current, phase L1

IDL2

REAL

Instantaneous differential current, phase L2

IDL3

REAL

Instantaneous differential current, phase L3

IDL1MAG

REAL

Magnitude of fund. freq. differential current,


phase L1

IDL2MAG

REAL

Magnitude of fund. freq. differential current,


phase L2

IDL3MAG

REAL

Magnitude of fund. freq. differential current,


phase L3

IBIAS

REAL

Magnitude of the bias current, common for L1,


L2, L3

IDNSMAG

REAL

Magnitude of the negative sequence differential


current

Table 68:
Name

LDLPDIF Input signals


Type

Default

Description

CTFAIL

BOOLEAN

CT failure indication from local CT supervision

OUTSERV

BOOLEAN

Input for indicating that the terminal is out of service

BLOCK

BOOLEAN

Block of function

Table 69:
Name

LDLPDIF Output signals


Type

Description

TRIP

BOOLEAN

General trip from differential protection system

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

Table continues on next page


132
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

5.1.5
Table 70:

Type

Description

TRL3

BOOLEAN

Trip signal from phase L3

TRLOCAL

BOOLEAN

Trip from local differential function

TRLOCL1

BOOLEAN

Trip from local differential function in phase L1

TRLOCL2

BOOLEAN

Trip from local differential function in phase L2

TRLOCL3

BOOLEAN

Trip from local differential function in phase L3

TRREMOTE

BOOLEAN

Trip from remote differential function

DIFLBLKD

BOOLEAN

Local line differential function blocked

Setting parameters
L3CPDIF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IdMin

0.20 - 2.00

IB

0.01

0.30

Oper - restr charact., section 1


sensitivity, multiple IBase

IdMinHigh

0.20 - 10.00

IB

0.01

0.80

Initial lower sensitivity, as multiple of


IBase

tIdMinHigh

0.000 - 60.000

0.001

1.000

Time interval of initial lower sensitivity, in


sec

IdUnre

1.00 - 50.00

IB

0.01

10.00

Unrestrained differential current limit,


multiple of IBase

NegSeqDiffEn

Off
On

On

Off/On selection for internal / external


fault discriminator

NegSeqROA

30.0 - 120.0

Deg

1.0

60.0

Internal/external fault discriminator


Operate Angle, degrees

IMinNegSeq

0.01 - 0.20

IB

0.01

0.04

Min. value of neg. seq. curr. as multiple


of IBase

CrossBlockEn

No
Yes

No

Off/On selection of the cross -block logic

ChargCurEnable

Off
On

Off

Off/On selection for compensation of


charging currents

AddDelay

Off
On

Off

Off/On selection for delayed diff. trip


command

IMaxAddDelay

0.20 - 5.00

IB

0.01

1.00

Below limit, extra delay can be applied,


multiple of IBase

tDefTime

0.000 - 6.000

0.001

0.000

Definite time additional delay in seconds

tMinInv

0.001 - 6.000

0.001

0.010

Inverse Delay Minimum Time. In seconds

Table continues on next page

133
Technical reference manual

Section 5
Differential protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

CurveType

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

IEC Def. Time

19 curve types. Example: 15 for definite


time delay.

0.05 - 1.10

0.01

1.00

Time Multiplier Setting (TMS) for inverse


delays

IdiffAlarm

0.05 - 1.00

IB

0.01

0.15

Sustained differential current alarm,


factor of IBase

tAlarmdelay

0.000 - 60.000

0.001

10.000

Delay for alarm due to sustained


differential current, in s

Table 71:
Name

L3CPDIF Group settings (advanced)


Unit

Step

Default

EndSection1

Values (Range)
0.20 - 1.50

IB

0.01

1.25

Description
End of section 1, as multiple of reference
current IBase

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, as multiple of reference


current IBase

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate- restrain


characteristic, in %

I2/I1Ratio

5.0 - 100.0

1.0

10.0

Max. ratio of 2nd harm. to fundamental


harm dif. curr. in %

I5/I1Ratio

5.0 - 100.0

1.0

25.0

Max. ratio of 5th harm. to fundamental


harm dif. curr. in %

0.01 - 1000.00

0.01

0.02

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

0.14

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

OpenCTEnable

Off
On

On

Open CTEnable Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

1.000

Open CT: time in s to alarm after an


open CT is detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff.


function is activated

134
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 72:

L3CPDIF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

NoOfTerminals

2
3

Number of current terminals of the


protected circuit

Chan2IsLocal

No
Yes

No

2-nd local current connected to input


channel 2, Yes/ No

IBase

50.0 - 9999.9

0.1

3000.0

Base (reference) current of the


differential protection

Table 73:

L6CPDIF Group settings (basic)


Unit

Step

Default

Name

Values (Range)

Description

Operation

Off
On

Off

Operation Off / On

IdMin

0.20 - 2.00

IB

0.01

0.30

Oper - restr charact., section 1


sensitivity, multiple IBase

IdMinHigh

0.20 - 10.00

IB

0.01

0.80

Initial lower sensitivity, as multiple of


IBase

tIdMinHigh

0.000 - 60.000

0.001

1.000

Time interval of initial lower sensitivity, in


sec

IdUnre

1.00 - 50.00

IB

0.01

10.00

Unrestrained differential current limit,


multiple of IBase

NegSeqDiffEn

Off
On

On

Off/On selection for internal / external


fault discriminator

NegSeqROA

30.0 - 120.0

Deg

1.0

60.0

Internal/external fault discriminator


Operate Angle, degrees

IMinNegSeq

0.01 - 0.20

IB

0.01

0.04

Min. value of neg. seq. curr. as multiple


of IBase

CrossBlockEn

No
Yes

No

Off/On selection of the cross -block logic

I2/I1Ratio

5.0 - 100.0

1.0

10.0

Max. ratio of 2nd harm. to fundamental


harm dif. curr. in %

I5/I1Ratio

5.0 - 100.0

1.0

25.0

Max. ratio of 5th harm. to fundamental


harm dif. curr. in %

ChargCurEnable

Off
On

Off

Off/On selection for compensation of


charging currents

AddDelay

Off
On

Off

Off/On selection for delayed diff. trip


command

IMaxAddDelay

0.20 - 5.00

IB

0.01

1.00

Below limit, extra delay can be applied,


multiple of IBase

tDefTime

0.000 - 6.000

0.001

0.000

Definite time additional delay in seconds

tMinInv

0.001 - 6.000

0.001

0.010

Inverse Delay Minimum Time. In seconds

Table continues on next page

135
Technical reference manual

Section 5
Differential protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

CurveType

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

IEC Def. Time

19 curve types. Example: 15 for definite


time delay.

0.05 - 1.10

0.01

1.00

Time Multiplier Setting (TMS) for inverse


delays

IdiffAlarm

0.05 - 1.00

IB

0.01

0.15

Sustained differential current alarm,


factor of IBase

tAlarmdelay

0.000 - 60.000

0.001

10.000

Delay for alarm due to sustained


differential current, in s

Table 74:
Name

L6CPDIF Group settings (advanced)


Unit

Step

Default

EndSection1

Values (Range)
0.20 - 1.50

IB

0.01

1.25

Description
End of section 1, as multiple of reference
current IBase

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, as multiple of reference


current IBase

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate- restrain


characteristic, in %

0.01 - 1000.00

0.01

0.02

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

0.14

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

OpenCTEnable

Off
On

On

Open CT detection feature. Open


CTEnable Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

1.000

Open CT: time in s to alarm after an


open CT is detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff.


function is activated

136
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 75:

L6CPDIF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

NoOfTerminals

2
3
4
5
6

Number of current terminals of the


protected circuit

Chan2IsLocal

No
Yes

No

2-nd local current connected to input


channel 2, Yes/ No

IBase

50.0 - 9999.9

0.1

3000.0

Base (reference) current of the


differential protection

Table 76:

LT3CPDIF Group settings (basic)

Name

Values (Range)

Step

Default

Unit

Description

Operation

Off
On

Off

Operation Off / On

IdMin

0.20 - 2.00

IB

0.01

0.30

Oper - restr charact., section 1


sensitivity, multiple IBase

IdMinHigh

0.20 - 10.00

IB

0.01

0.80

Initial lower sensitivity, as multiple of


IBase

tIdMinHigh

0.000 - 60.000

0.001

1.000

Time interval of initial lower sensitivity, in


sec

IdUnre

1.00 - 50.00

IB

0.01

10.00

Unrestrained differential current limit,


multiple of IBase

NegSeqDiffEn

Off
On

On

Off/On selection for internal / external


fault discriminator

NegSeqROA

30.0 - 120.0

Deg

1.0

60.0

Internal/external fault discriminator


Operate Angle, degrees

IMinNegSeq

0.01 - 0.20

IB

0.01

0.04

Min. value of neg. seq. curr. as multiple


of IBase

CrossBlockEn

No
Yes

No

Off/On selection of the cross -block logic

ChargCurEnable

Off
On

Off

Off/On selection for compensation of


charging currents

AddDelay

Off
On

Off

Off/On selection for delayed diff. trip


command

IMaxAddDelay

0.20 - 5.00

IB

0.01

1.00

Below limit, extra delay can be applied,


multiple of IBase

tDefTime

0.000 - 6.000

0.001

0.000

Definite time additional delay in seconds

tMinInv

0.001 - 6.000

0.001

0.010

Inverse Delay Minimum Time. In seconds

Table continues on next page

137
Technical reference manual

Section 5
Differential protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

CurveType

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

IEC Def. Time

19 curve types. Example: 15 for definite


time delay.

0.05 - 1.10

0.01

1.00

Time Multiplier Setting (TMS) for inverse


delays

IdiffAlarm

0.05 - 1.00

IB

0.01

0.15

Sustained differential current alarm,


factor of IBase

tAlarmdelay

0.000 - 60.000

0.001

10.000

Delay for alarm due to sustained


differential current, in s

Table 77:
Name

LT3CPDIF Group settings (advanced)


Unit

Step

Default

EndSection1

Values (Range)
0.20 - 1.50

IB

0.01

1.25

Description
End of section 1, as multiple of reference
current IBase

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, as multiple of reference


current IBase

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate- restrain


characteristic, in %

I2/I1Ratio

5.0 - 100.0

1.0

10.0

Max. ratio of 2nd harm. to fundamental


harm dif. curr. in %

I5/I1Ratio

5.0 - 100.0

1.0

25.0

Max. ratio of 5th harm. to fundamental


harm dif. curr. in %

0.01 - 1000.00

0.01

0.02

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

0.14

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

OpenCTEnable

Off
On

On

Open CT detection feature. Open


CTEnable Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

1.000

Open CT: time in s to alarm after an


open CT is detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff.


function is activated

138
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 78:

LT3CPDIF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

NoOfTerminals

2
3

Number of current terminals of the


protected circuit

Chan2IsLocal

No
Yes

No

2-nd local current connected to input


channel 2, Yes/ No

IBase

50.0 - 9999.9

0.1

3000.0

Base (reference) current of the


differential protection

ZerSeqCurSubtr

Off
On

Off

Off/On for elimination of zero seq. from


diff. and bias curr

TraAOnInpCh

No Transf A
1
2
3

No Transf A

Power transformer A applied on input


channel X

RatVoltW1TraA

1.0 - 9999.9

kV

0.1

130.0

Transformer A rated voltage (kV) on


winding 1 (HV winding)

RatVoltW2TraA

1.0 - 9999.9

kV

0.1

130.0

Transformer A rated voltage (kV) on


winding 2 (LV winding)

ClockNumTransA

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]

0 [0 deg]

Transf. A phase shift in multiples of 30


deg, 5 for 150 deg

ZerSeqPassTraA

No
Yes

No

Yes/No for capability of transf A to


transform zero seq curr

TraBOnInpCh

No Transf B
1
2
3

No Transf B

Power transformer B applied on input


channel X

RatVoltW1TraB

1.0 - 9999.9

kV

0.1

130.0

Transformer B rated voltage (kV) on


winding 1 (HV winding)

RatVoltW2TraB

1.0 - 9999.9

kV

0.1

130.0

Transformer B rated voltage (kV) on


winding 2 (LV winding)

ClockNumTransB

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]

0 [0 deg]

Transf. B phase shift in multiples of 30


deg, 2 for 60 deg

ZerSeqPassTraB

No
Yes

No

Yes/No for capability of transf B to


transform zero seq curr

139
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 79:

LT6CPDIF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IdMin

0.20 - 2.00

IB

0.01

0.30

Oper - restr charact., section 1


sensitivity, multiple IBase

IdMinHigh

0.20 - 10.00

IB

0.01

0.80

Initial lower sensitivity, as multiple of


IBase

tIdMinHigh

0.000 - 60.000

0.001

1.000

Time interval of initial lower sensitivity, in


sec

IdUnre

1.00 - 50.00

IB

0.01

10.00

Unrestrained differential current limit,


multiple of IBase

NegSeqDiffEn

Off
On

On

Off/On selection for internal / external


fault discriminator

NegSeqROA

30.0 - 120.0

Deg

1.0

60.0

Internal/external fault discriminator


Operate Angle, degrees

IMinNegSeq

0.01 - 0.20

IB

0.01

0.04

Min. value of neg. seq. curr. as multiple


of IBase

CrossBlockEn

No
Yes

No

Off/On selection of the cross -block logic

I2/I1Ratio

5.0 - 100.0

1.0

10.0

Max. ratio of 2nd harm. to fundamental


harm dif. curr. in %

I5/I1Ratio

5.0 - 100.0

1.0

25.0

Max. ratio of 5th harm. to fundamental


harm dif. curr. in %

ChargCurEnable

Off
On

Off

Off/On selection for compensation of


charging currents

AddDelay

Off
On

Off

On/Off selection for delayed diff. trip


command

IMaxAddDelay

0.20 - 5.00

IB

0.01

1.00

Below limit, extra delay can be applied,


multiple of IBase

tDefTime

0.000 - 6.000

0.001

0.000

Definite time additional delay in seconds

tMinInv

0.001 - 6.000

0.001

0.010

Inverse Delay Minimum Time. In seconds

CurveType

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

IEC Def. Time

19 curve types. Example: 15 for definite


time delay.

Table continues on next page

140
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

Step

Default

0.05 - 1.10

0.01

1.00

Time Multiplier Setting (TMS) for inverse


delays

IdiffAlarm

0.05 - 1.00

IB

0.01

0.15

Sustained differential current alarm,


factor of IBase

tAlarmdelay

0.000 - 60.000

0.001

10.000

Delay for alarm due to sustained


differential current, in s

Table 80:

Values (Range)

Unit

Description

LT6CPDIF Group settings (advanced)

Name

Unit

Step

Default

EndSection1

0.20 - 1.50

IB

0.01

1.25

End of section 1, as multiple of reference


current IBase

EndSection2

1.00 - 10.00

IB

0.01

3.00

End of section 2, as multiple of reference


current IBase

SlopeSection2

10.0 - 50.0

0.1

40.0

Slope in section 2 of operate-restrain


characteristic, in %

SlopeSection3

30.0 - 100.0

0.1

80.0

Slope in section 3 of operate- restrain


characteristic, in %

0.01 - 1000.00

0.01

0.02

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

0.14

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

0.01 - 1000.00

0.01

1.00

Settable curve parameter, userprogrammable curve type.

OpenCTEnable

Off
On

On

Open CTEnable Off/On

tOCTAlarmDelay

0.100 - 10.000

0.001

1.000

Open CT: time in s to alarm after an


open CT is detected

tOCTResetDelay

0.100 - 10.000

0.001

0.250

Reset delay in s. After delay, diff.


function is activated

Table 81:

Values (Range)

Description

LT6CPDIF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

NoOfTerminals

2
3
4
5
6

Number of current terminals of the


protected circuit

Chan2IsLocal

No
Yes

No

2-nd local current connected to input


channel 2, Yes/ No

IBase

50.0 - 9999.9

0.1

3000.0

Base (reference) current of the


differential protection

ZerSeqCurSubtr

Off
On

Off

Off/On for elimination of zero seq. from


diff. and bias curr

Table continues on next page

141
Technical reference manual

Section 5
Differential protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

TraAOnInpCh

No Transf A
1
2
3
4
5
6

No Transf A

Power transformer A applied on input


channel X

RatVoltW1TraA

1.0 - 9999.9

kV

0.1

130.0

Transformer A rated voltage (kV) on


winding 1 (HV winding)

RatVoltW2TraA

1.0 - 9999.9

kV

0.1

130.0

Transformer A rated voltage (kV) on


winding 2 (LV winding)

ClockNumTransA

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]

0 [0 deg]

Transf. A phase shift in multiples of 30


deg, 5 for 150 deg

ZerSeqPassTraA

No
Yes

No

Yes/No for capability of transf A to


transform zero seq curr

TraBOnInpCh

No Transf B
1
2
3
4
5
6

No Transf B

Power transformer B applied on input


channel X

RatVoltW1TraB

1.0 - 9999.9

kV

0.1

130.0

Transformer B rated voltage (kV) on


winding 1 (HV winding)

RatVoltW2TraB

1.0 - 9999.9

kV

0.1

130.0

Transformer B rated voltage (kV) on


winding 2 (LV winding)

ClockNumTransB

0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]

0 [0 deg]

Transf. B phase shift in multiples of 30


deg, 2 for 60 deg

ZerSeqPassTraB

No
Yes

No

Yes/No for capability of transf B to


transform zero seq curr

142
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 82:

LDLPDIF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

testModeSet

Off
On

Off

Test mode On/Off

ReleaseLocal

Block all
Release local

Block all

Release of local terminal for trip under


test mode

5.1.6

Technical data
Table 83:

L3CPDIF, L6CPDIF, LT3CPDIF, LT6CPDIF technical data

Function

Range or value

Accuracy

Minimum operate current

(20-200)% of IBase

1.0% of Ir at I Ir
1.0% of I at I >I r

SlopeSection2

(10.0-50.0)%

SlopeSection3

(30.0-100.0)%

EndSection 1

(20150)% of IBase

EndSection 2

(1001000)% of IBase

Unrestrained limit function

(1005000)% of IBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Second harmonic blocking

(5.0100.0)% of fundamental

2.0% of Ir

Fifth harmonic blocking

(5.0100.0)% of fundamental

6.0% of Ir

Inverse characteristics, see table


722, 723 and table 724

19 curve types

See table 722 and


table 723

Operate time

25 ms typically at 0 to 10 x Id

Reset time

15 ms typically at 10 to 0 x Id

Critical impulse time

2 ms typically at 0 to 10 x Id

Charging current compensation

On/Off

5.2

1Ph High impedance differential protection HZPDIF

5.2.1

Identification
Function description

1Ph High impedance differential


protection

IEC 61850
identification

HZPDIF

IEC 60617
identification

Id

ANSI/IEEE C37.2
device number

87

SYMBOL-CC V2 EN

143
Technical reference manual

Section 5
Differential protection
5.2.2

1MRK 505 222-UEN B

Introduction
The 1Ph High impedance differential protection (HZPDIF) function can be used
when the involved CT cores have the same turns ratio and similar magnetizing
characteristics. It utilizes an external CT current summation by wiring, a series
resistor, and a voltage dependent resistor which are mounted externally connected
to the IED.
HZPDIF can be used to protect tee-feeders or busbars. Six single phase function
blocks are available to allow application for two three-phase zones busbar protection.

5.2.3

Principle of operation
The 1Ph High impedance differential protection (HZPDIF) function is based on
one current input with external stabilizing resistors and voltage dependent resistors.
Three functions can be used to provide a three phase differential protection
function. The stabilizing resistor value is calculated from the IED function
operating value UR calculated to achieve through fault stability. The supplied
stabilizing resistor has a link to allow setting of the correct resistance value .
See the application manual for operating voltage and sensitivity calculation.

5.2.3.1

Logic diagram
The logic diagram shows the operation principles for the 1Ph High impedance
differential protection function HZPDIF, see figure 67. It is a simple one step IED
function with an additional lower alarm level. By activating inputs, the HZPDIF
function can either be blocked completely, or only the trip output.

IEC05000301 V1 EN

Figure 67:

Logic diagram for 1Ph High impedance differential protection


HZPDIF

144
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

5.2.4

Function block
HZPDIF
ISI*
BLOCK
BLKTR

TRIP
ALARM
MEASVOLT
IEC05000363-2-en.vsd

IEC05000363 V2 EN

Figure 68:

5.2.5

HZPDIF function block

Input and output signals


Table 84:

HZPDIF Input signals

Name

Type

Group signal for current input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

HZPDIF Output signals

Name

Table 86:

Description

GROUP
SIGNAL

Table 85:

5.2.6

Default

ISI

Type

Description

TRIP

BOOLEAN

Trip signal

ALARM

BOOLEAN

Alarm signal

MEASVOLT

REAL

Measured RMS voltage on CT secondary side

Setting parameters
HZPDIF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

U>Alarm

2 - 500

10

Alarm voltage level in volts on CT


secondary side

tAlarm

0.000 - 60.000

0.001

5.000

Time delay to activate alarm

U>Trip

5 - 900

100

Operate voltage level in volts on CT


secondary side

SeriesResistor

10 - 20000

ohm

250

Value of series resistor in Ohms

145
Technical reference manual

Section 5
Differential protection
5.2.7

1MRK 505 222-UEN B

Technical data
Table 87:

HZPDIF technical data

Function

5.3

Range or value

Operate voltage

(20-400) V
I=U/R

1.0% of Ir

Reset ratio

>95%

Maximum
continuous voltage

U>Trip2/series

Operate time

10 ms typically at 0 to 10 x Ud

Reset time

90 ms typically at 10 to 0 x Ud

Critical impulse time

2 ms typically at 0 to 10 x Ud

resistor 200 W

Additional security logic for differential protection


STSGGIO
Function description
Additional security logic for differential
protection

5.3.1

Accuracy

IEC 61850
identification
STSGGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
11

Introduction
Additional security logic for differential protection (STSGGIO ) can help the
security of the protection especially when the communication system is in
abnormal status or for example when there is unspecified asymmetry in the
communication link. It helps to reduce the probability for mal-operation of the
protection. STSGGIO is more sensitive than the main protection logic to always
release operation for all faults detected by the differential function. STSGGIO
consists of four sub functions:

Phase-to-phase current variation


Zero sequence current criterion
Low voltage criterion
Low current criterion

Phase-to-phase current variation takes the current samples as input and it calculates
the variation using the sampling value based algorithm. Phase-to-phase current
variation function is major one to fulfill the objectives of the startup element.
Zero sequence criterions takes the zero sequence current as input. It increases the
security of protection during the high impedance fault conditions.

146
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Low voltage criterion takes the phase voltages and phase-to-phase voltages as
inputs. It increases the security of protection when the three-phase fault occurred
on the weak end side.
Low current criterion takes the phase currents as inputs and it increases the
dependability during the switch onto fault case of unloaded line.
The differential function can be allowed to trip as no load is fed through the line
and protection is not working correctly.
Features:

5.3.2

Startup element is sensitive enough to detect the abnormal status of the


protected system
Startup element does not influence the operation speed of main protection
Startup element would detect the evolving faults, high impedance faults and
three phase fault on weak side
It is possible to block the each sub function of startup element
Startup signal has a settable pulse time

Principle of operation
Additional security logic for differential protection (STSGGIO) takes the current
samples, current RMS values, phase voltage values, phase-to-phase voltage values,
zero sequence current and remote side startup signals as inputs.
Startup signal becomes activated when any one of the current variation startup
signal, zero sequence current startup signal, voltage startup signal, and current
startup signal is activated.
Phase-to-phase current variation takes current samples and generates the startup
signal by comparing with the start value.
If the zero sequence current value is greater than the start value of zero sequence
current then the zero sequence current startup signal will be activated.
Voltage startup signal becomes activated when the any of phase voltage and line
voltage is less than the voltage start value and the remote startup signal has to be
activated.
Current startup signal becomes activated when the current value in all phases is
less than current start value.
Phase-to-phase current variation
Phase-to-phase current variation one is main startup element. It covers most of the
abnormal status of the system. The phase-to-phase current variation fails in high
impedance faults, three-phase fault on weak side and switch onto fault on unloaded
line because of low sensitivity in these cases.

147
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Phase-to-phase current variation takes the current samples as input and the signal is
evaluated using the sampling value based algorithm.
The phase-to-phase current variation criterion is shown below:

DiFF > 1.8DIT + DI ZD


EQUATION2255 V1 EN

Where:

sampling value of phase-to-phase current variation

IZD

setting of fixed threshold, which corresponds to setting ICV>. The default value for
the setting is 0.2IBase, where IBase is the base current.

IT

float threshold

It is the full-circle integral of the phase-to-phase current variation

1 2T -1
DIT = | DiFF (t - n) |
T n =T
EQUATION2256 V1 EN

Where:
T

count of sample values in one cycle

i is calculated using the below formula:

Di (k ) = [i ( k ) - i (k - N )] - [i (k - N ) - i (k - 2 N )]
= i ( k ) - 2i ( k - N ) + i (k - 2 N )
EQUATION2257 V1 EN

N is the number of samples in one cycle.

148
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

tCV

STCVL1L2

t
I3P

cont

tCV

Current variation
subfunction

STCVL2L3

tCV

STCVL3L1

OR

STCV
cont

IEC10000295-1-en.vsd
IEC10000295 V1 EN

Figure 69:

Current variation logic diagram

tCV is the time setting for the change of current criterion. Phase current samples
are included in input signal I3P.
Zero sequence current criterion
Zero sequence criterion is mainly for detection of remote IED high resistance faults
or some gradual faults. The criterion takes the zero sequence current as input. Zero
sequence current is compared with I3I0> for the t3I0 time to generate the zero
sequence current startup signal.
I3P

a
b

I3IO>

BLK3I0
BLOCK

a>b

AND

t3I0
t

ST3I0

OR

IEC09000778-2-en.vsd
IEC09000778 V2 EN

Figure 70:

Zero sequence current criterion logic diagram

Here I3I0> is the setting of the maximum possible non-faulted zero sequence
current for the protected line. The default value for this setting is 0.1 IBase where
IBase is the rated current of the CT.
t3I0 is the time setting for the zero sequence current criterion.
The zero sequence current criterion can be blocked by activating the BLK3I0 input
signal.
Low voltage criterion

149
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Low voltage criterion is mainly for detection of the three phase faults occurring on
weak side with pre fault no load condition. The low voltage criterion takes the
voltage phase values, voltage phase-to-phase values and remote startup signals as
inputs. The logic for low voltage criterion is shown below:
U3P (UPhN)

UPhN<

U3P (UPhPh)

UPhPh<

a<b

OR
a<b
tUV

REMSTUP (Recived)

AND

STUV

BLKUV
OR

BLOCK

IEC09000779-2-en.vsd
IEC09000779 V2 EN

Figure 71:

Low voltage criterion logic diagram

Voltage phase value is compared with the start value of voltage phase and voltage
phase-to-phase value is compared with the start value of voltage phase-to-phase. If
any of the phase voltage and phase-to-phase voltages is below the set voltage levels
for some time duration (tUV) then the low voltage START signal becomes
activated after receiving the remote startup signal. Low voltage criterion can be
blocked by activating BLKUV input signal.
If there are more than one remote IED, all the startup signals of the remote ends are
logically OR to obtain the REMSTUP signal from the remote side as input.
Low current criterion
The current in each phase is compared to the set current level. If all currents are
below setting IUC<, the STUC output is activated after the set delay tUC.
I3P

IUC<

BLKUC
BLOCK

a<b

tUC

AND

STUC

OR

IEC09000780-2-en.vsd
IEC09000780 V2 EN

Figure 72:

Low current criterion logic diagram

Security logic for differential protection

150
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

The configuration for the additional security logic for differential protection is
shown in fig 73. The function will release tripping of the line differential protection
up to the end of timer tStUpReset.
Phase-phase
current variation

STCV

Zero sequence
current criterion

ST3IO

I0 >

tStUpReset
t

Low voltage
criterion

STUV

Low current
criterion

STUC

START

OR

ULOW <

Local side start-up


Send signal to
remote side

I0 <

REMSTUP

IEC10000296-2-en.vsd
IEC10000296 V2 EN

Figure 73:

5.3.3

Additional security logic for differential protection. Logic diagram for


start up element.

Function block
STSGGIO
I3P*
U3P*
BLOCK
BLKCV
BLKUC
BLK3I0
BLKUV
REMSTUP

START
STCVL1L2
STCVL2L3
STCVL3L1
STUC
ST3I0
STUV

IEC09000781-1-en.vsd
IEC09000781 V1 EN

Figure 74:

5.3.4

STSGGIO function block

Input and output signals


Table 88:
Name

STSGGIO Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Common block signal

BLKCV

BOOLEAN

Block of ph to ph current variation criterion

BLKUC

BOOLEAN

Block of the low current criterion

Table continues on next page

151
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Name

Type

Description

BOOLEAN

Block of zero sequence current criterion

BLKUV

BOOLEAN

Block of under voltage criterion

REMSTUP

BOOLEAN

Startup signal of remote end

Table 89:

STSGGIO Output signals

Name

5.3.5

Default

BLK3I0

Type

Description

START

BOOLEAN

General startup signal

STCVL1L2

BOOLEAN

Start signal for current variation criterion for


phase L1L2

STCVL2L3

BOOLEAN

Start signal for current variation criterion for


phase L2L3

STCVL3L1

BOOLEAN

Start signal for current variation criterion for


phase L3L1

STUC

BOOLEAN

Start signal for low current criterion

ST3I0

BOOLEAN

Start signal for zero sequence current criterion

STUV

BOOLEAN

Start signal for under voltage criterion

Setting parameters

Table 90:

STSGGIO Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

IBase

1 - 99999

3000

Base setting for current in A

UBase

0.05 - 2000.00

kV

0.05

400

Base setting for voltage in kV

tStUpReset

0.000 - 60.000

0.001

7.000

Reset delay for startup signal

OperationCV

Off
On

On

Operation current variation Off/On

ICV>

1 - 100

%IB

20

Fixed threshold for ph to ph current


variation criterion

OperationUC

Off
On

On

Operation low current criterion Off/On

IUC<

0 - 100

%IB

Start value for low current operation in %


of IBase

Operation3I0

Off
On

On

Operation zero sequence current


criterion Off/On

I3I0>

1 - 100

%IB

10

Start value for zero sequence current


criterion in % of IBase

OperationUV

Off
On

On

Operation under voltage criterion Off/On

UPhN<

1 - 100

%UB

60

Start value for phase voltage criterion in


% of UBase

UPhPh<

1 - 100

%UB

60

Start value for ph to ph voltage criterion


in % of UBase

152
Technical reference manual

Section 5
Differential protection

1MRK 505 222-UEN B

Table 91:

STSGGIO Group settings (advanced)

Name

Values (Range)

Unit

tCV

0.000 - 0.005

0.001

0.002

Time delay for phase to phase current


variation

tUC

0.000 - 60.000

0.001

0.200

Time delay for low current criterion

t3I0

0.000 - 60.000

0.001

0.000

Time delay for zero sequence current


criterion

tUV

0.000 - 60.000

0.001

0.000

Time delay for low voltage criterion

HysAbsUV

0.0 - 100.0

%UB

0.1

0.5

Hysteresis absolute value for low voltage


criterion in % of UBase

5.3.6

Step

Default

Description

Technical data
Table 92:

STSGGIOtechnical data

Function

Range or value

Accuracy

Operate current, zero sequence

(1-100)% of lBase

1,0% of Ir

Operate current, low operation

(1-100)% of lBase

1,0% of Ir

Operate voltage, phase to neutral

(1-100)% of UBase

0,5% of Ur

Operate voltage, phase to phase

(1-100)% of UBase

0,5% of Ur

Timers, general

(0.000-60.000) s

0.5% 10 ms

Critical impulse time

10 ms typically at 0.5 to.2 x Iset

Impulse margin time

20 ms typically

Transient overreach

< 2% at = 100 ms

153
Technical reference manual

154

Section 6
Impedance protection

1MRK 505 222-UEN B

Section 6

Impedance protection

About this chapter


This chapter describes distance protection and associated functions. It includes
function blocks, logic diagrams and data tables with information about distance
protection, automatic switch onto fault, weak end in-feed and other associated
functions. Quadrilateral characteristics are also covered.

6.1

Distance measuring zones, quadrilateral


characteristic ZMQPDIS, ZMQAPDIS, ZDRDIR

6.1.1

Identification
Function description
Distance protection zone, quadrilateral
characteristic (zone 1)

IEC 61850
identification

IEC 60617
identification

ZMQPDIS

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

Distance protection zone, quadrilateral


characteristic (zone 2-5)

ZMQAPDIS

Directional impedance quadrilateral

ZDRDIR

21

S00346 V1 EN

21D

Z<->
IEC09000167 V1 EN

6.1.2

Introduction
The line distance protection is a, up to five zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth faults
for each of the independent zones. Individual settings for each zone in resistive and
reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.
ZMQPDIS together with Phase selection with load encroachment FDPSPDIS has
functionality for load encroachment, which increases the possibility to detect high
resistive faults on heavily loaded lines, as shown in figure75.

155
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X
Forward
operation

R
Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 75:

Typical quadrilateral distance protection zone with Phase selection


with load encroachment function FDPSPDIS activated

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built-in phase selection makes the function suitable in
applications with single-phase autoreclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at
load exporting end at phase-to-earth faults on heavily loaded power lines.
The distance protection zones can operate independently of each other in
directional (forward or reverse) or non-directional mode. This makes them suitable,
together with different communication schemes, for the protection of power lines
and cables in complex network configurations, such as parallel lines, multiterminal lines, and so on.

6.1.3

Principle of operation

6.1.3.1

Full scheme measurement


The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
for forward and reverse faults are executed in parallel.
Figure 76 presents an outline of the different measuring loops for up to five,
impedance-measuring zones. There are 3 to 5 zones depending on product type and
variant.

156
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 1

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 2

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 3

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 4

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 5

en05000458.vsd
IEC05000458 V1 EN

Figure 76:

The different measuring loops at phase-to-earth fault and phase-tophase fault.

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

6.1.3.2

Impedance characteristic
The distance measuring zone includes six impedance measuring loops; three
intended for phase-to-earth faults, and three intended for phase-to-phase as well as,
three-phase faults.
The distance measuring zone will essentially operate according to the nondirectional impedance characteristics presented in figure 77 and figure 78. The phaseto-earth characteristic is illustrated with the full loop reach while the phase-tophase characteristic presents the per phase reach.

157
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (Ohm/loop)

R1PE+Rn
RFPE

RFPE

X1PE+Xn

jN
RFPE

Xn =

X0PE-X1PE
3

Rn =

R0PE-R1PE
3

jN

R (Ohm/loop)

RFPE

X1PE+Xn

RFPE

RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN

Figure 77:

Characteristic for phase-to-earth measuring, ohm/loop domain

158
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RFPP

(Ohm/phase)

R1PP

RFPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
33
X
0
PE
--1X
11FWPE
X
0
PE
X 0 PG X
XFWPE
FWPG
XNFW
XNFW
XNFW===
3 33

X1PP

R (Ohm/phase)
RFPP

RFPP

X1PP

RFPP
2

R1PP

RFPP
2

en07000062.vsd

IEC07000062 V2 EN

Figure 78:

Characteristic for phase-to-phase measuring

The fault loop reach with respect to each fault type may also be presented as in
figure 79. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.

159
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

UL1

IL1

R1 + j X1

Phase-to-earth
fault in phase L1

Phase-to-earth
element

RFPE
(Arc + tower
resistance)
0

Phase-to-phase
fault in phase
L1-L2

UL1

IN

(R0-R1)/3 +
j (X0-X1)/3 )

IL1

R1 + j X1

Phase-to-phase
element L1-L2
RFPP

IL2

(Arc resistance)

UL2
R1 + j X1

UL1
Three-phase
fault

IL1

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

Phase-to-phase
element L1-L3

IL3
UL3
IEC08000282-2-en.vsd

IEC08000282 V2 EN

Figure 79:

Fault loop model

The R1 and jX1 in figure 79 represents the positive sequence impedance from the
measuring point to the fault location. The settings RFPE and RFPP are the
eventual fault resistances in the faulty place.
Regarding the illustration of three-phase fault in figure 79, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
The zone can be set to operate in Non-directional, Forward or Reverse direction
through the setting OperationDir. The result from respective set value is illustrated
in figure 80. The impedance reach is symmetric, in the sense that it conforms for
forward and reverse direction. Therefore, all reach settings apply to both directions.

160
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Non-directional

Forward

Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 80:

6.1.3.3

Directional operating modes of the distance measuring zones

Minimum operating current


The operation of Distance measuring zones, quadrilateral characteristic
(ZMQPDIS) is blocked if the magnitude of input currents fall below certain
threshold values.
The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three-phase currents, that is, residual current 3I0.
The phase-to-phase loop LmLn is blocked if ILmLn < IMinOpPP.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are
automatically reduced to 75% of regular set values if the zone is set
to operate in reverse direction, that is, OperationDir = Reverse.

6.1.3.4

Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

161
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

apparent impedances at phase-to-phase faults follow equation 4 (example for a


phase L1 to phase L2 fault).
UL1 UL2
Zapp = ------------------------I L1 IL2
(Equation 4)

EQUATION1222 V1 EN

Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3)
The earth return compensation applies in a conventional manner to phase-to-earth
faults (example for a phase L1 to earth fault) according to equation 5.
U L1
Z app = -----------------------------I L1 + I N KN
(Equation 5)

EQUATION1223 V1 EN

Where:
UL1, IL1 and IN

are the phase voltage, phase current and residual current present to the IED

KN is defined as:

KN =

Z0 - Z1
3 Z1

EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0

is setting of the resistive zero sequence reach

X0

is setting of the reactive zero sequence reach

R1

is setting of the resistive positive sequence reach

X1

is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and
reactance X.

162
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The formula given in equation 5 is only valid for radial feeder application without
load. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. The IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 6,
X Di
U = R i + ------ ----w 0 Dt
EQUATION1224 V1 EN

(Equation 6)

in complex notation, or:


X D Re ( I )
Re ( U ) = R Re ( I ) + ------ -----------------w0
Dt
EQUATION354 V1 EN

(Equation 7)

X DIm ( I )
Im ( U ) = R Im ( I ) + ------ ----------------w0
Dt
EQUATION355 V1 EN

(Equation 8)

with
w0 = 2 p f 0
EQUATION356 V1 EN

(Equation 9)

where:
Re

designates the real component of current and voltage,

Im

designates the imaginary component of current and voltage and

f0

designates the rated system frequency

The algorithm calculates Rmmeasured resistance from the equation for the real
value of the voltage and substitutes it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

163
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Im ( U ) DRe ( I ) Re ( U ) D Im ( I )
R m = -----------------------------------------------------------------------------------DRe ( I ) Im ( I ) D Im ( I ) Re ( I )
(Equation 10)

EQUATION357 V1 EN

Re ( U ) Im ( I ) Im ( U ) Re ( I )
Xm = w 0 Dt ------------------------------------------------------------------------------DRe ( I ) Im ( I ) DIm ( I ) Re ( I )
(Equation 11)

EQUATION358 V1 EN

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and
reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.1.3.5

Directional impedance element for quadrilateral characteristics


The evaluation of the directionality takes place in Directional impedance
quadrilateral function ZDRDIR. Equation 12 and equation 13 are used to classify
that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault.
- ArgDir < arg

0.8 U 1L1 + 0.2 U 1L1 M


I L1

< ArgNeg Re s
(Equation 12)

EQUATION725 V2 EN

For the L1-L2 element, the equation in forward direction is according to.
- ArgDir < arg

0.8 U 1L1 L 2 + 0.2 U 1L1 L 2 M


I L1 L 2

< ArgNeg Re s
(Equation 13)

EQUATION726 V2 EN

where:
ArgDir

is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and

ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 81.
U1L1

is positive sequence phase voltage in phase L1

U1L1M

is positive sequence memorized phase voltage in phase L1

IL1

is phase current in phase L1

U1L1L2

is voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M

is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2

is current difference between phase L1 and L2 (L2 lagging L1)

164
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure 81). It should not be changed unless
system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.
STDIR=

STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

ArgNegRes

ArgDir

en05000722.vsd
IEC05000722 V1 EN

Figure 81:

Setting angles for discrimination of forward and reverse fault in


Directional impedance quadrilateral function ZDRDIR

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds
5% of the set base voltage UBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
After 100ms the following occurs:
165
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.

6.1.3.6

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

Simplified logic diagrams


Distance protection zones

The design of the distance protection zones are presented for all measuring loops:
phase-to-earth as well as phase-to-phase.
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-tophase signals are designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described


above.
Group functional input signal (STCND), as presented in figure 82.

Two types of function block, ZMQPDIS and ZMQAPDIS, are used in the IED.
ZMQPDIS is used for zone 1 and ZMQAPDIS for zone 2 - 5.
The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FDPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FDPSPDIS function output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filters out the
relevant signals depending on the setting of the parameter OperationDir. It must be
configured to the STDIR output on ZDRDIR function.

166
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IEC99000557-TIFF V1 EN

Figure 82:

Conditioning by a group functional input signal STCND, external


start condition

Composition of the phase start signals for a case, when the zone operates in a nondirectional mode, is presented in figure 83.

IEC00000488-TIFF V1 EN

Figure 83:

Composition of starting signals in non-directional operating mode


167

Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 84.
STNDL1N
DIRL1N

AND
OR

STNDL2N
DIRL2N

AND

STNDL3N

OR

DIRL3N

AND

STNDL1L2
DIRL1L2

AND

STNDL2L3
DIRL2L3

AND

STNDL3L1
DIRL3L1

STZMPE.

AND

OR

OR

AND

15 ms
t

STL1

AND

15 ms
t

STL2

AND

15 ms
t

STL3

AND
OR

STZMPP

AND

BLK

OR

AND

15 ms
t

START

IEC09000888-1-en.vsd
IEC09000888 V1 EN

Figure 84:

Composition of start signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 85.

168
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Timer tPP=On

tPP
t

AND

STZMPP

OR

Timer tPE=On
AND

STZMPE

tPE
t

AND
OR
AND

15ms

TRIP

BLKTR

AND

STL1

AND

TRL1

STL2

AND

TRL2

STL3

AND

TRL3

en00000490.vsd
IEC09000887 V1 EN

Figure 85:

6.1.4

Tripping logic for the distance protection zone

Function block
ZMQPDIS
I3P*
U3P*
BLOCK
VTSZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC06000256-2-en.vsd

IEC06000256 V2 EN

Figure 86:

ZMQPDIS function block

169
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ZMQAPDIS
I3P*
U3P*
BLOCK
VTSZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC09000884-1-en.vsd

IEC09000884 V1 EN

Figure 87:

ZMQAPDIS function block (zone 2 - 5)


ZDRDIR

I3P*
U3P*

STDIRCND

IEC10000007-1-en.vsd
IEC10000007 V1 EN

Figure 88:

6.1.5

ZDRDIR function block

Input and output signals


Table 93:
Name

ZMQPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

VTSZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 94:
Name

ZMQPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

170
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 95:
Name

ZMQAPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

VTSZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 96:
Name

ZMQAPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

Table 97:

ZDRDIR Input signals

Name

Type

Default

Description

I3P

GROUP
SIGNAL

group connection for current abs 2

U3P

GROUP
SIGNAL

group connection for voltage abs 2

Table 98:
Name
STDIRCND

ZDRDIR Output signals


Type
INTEGER

Description
Binary coded directional information per
measuring loop

171
Technical reference manual

Section 6
Impedance protection
6.1.6

1MRK 505 222-UEN B

Setting parameters
Signals and settings for ZMQPDIS are valid for zone 1 while
signals and settings for ZMQAPDIS are valid for zone 2 - 5

Table 99:

ZMQPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach

R1

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for zone


characteristic angle

X0

0.10 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach

R0

0.01 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle

RFPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

RFPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

IMinOpIN

5 - 1000

%IB

Minimum operate residual current for


Phase-Earth loops

172
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 100:

ZMQAPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1

0.10 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach

R1

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for zone


characteristic angle

X0

0.10 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach

R0

0.01 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle

RFPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

RFPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

Table 101:

ZDRDIR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

IMinOpPP

5 - 30

%IB

10

Minimum operate delta current for PhasePhase loops

IMinOpPE

5 - 30

%IB

Minimum operate phase current for


Phase-Earth loops

ArgNegRes

90 - 175

Deg

115

Angle of blinder in second quadrant for


forward direction

ArgDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for


forward direction

173
Technical reference manual

Section 6
Impedance protection
6.1.7

1MRK 505 222-UEN B

Technical data
Table 102:

ZMQPDIS Technical data

Function

6.2

Range or value

Accuracy

Number of zones

Max 5 with selectable


direction

Minimum operate residual


current, zone 1

(5-1000)% of IBase

Minimum operate current, phaseto-phase and phase-to-earth

(10-1000)% of IBase

Positive sequence reactance

(0.10-3000.00) /
phase

Positive sequence resistance

(0.01-1000.00) /
phase

Zero sequence reactance

(0.10-9000.00) /
phase

2.0% static accuracy


2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees

Zero sequence resistance

(0.01-3000.00) /
phase

Fault resistance, phase-to-earth

(0.10-9000.00) /loop

Fault resistance, phase-to-phase

(0.10-3000.00) /loop

Dynamic overreach

<5% at 85 degrees
measured with CVTs
and 0.5<SIR<30

Impedance zone timers

(0.000-60.000) s

0.5% 10 ms

Operate time

24 ms typically

Reset ratio

105% typically

Reset time

30 ms typically

Distance measuring zone, quadrilateral


characteristic for series compensated lines
ZMCPDIS, ZMCAPDIS, ZDSRDIR

174
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Function description

IEC 61850
identification

Distance measuring zone, quadrilateral


characteristic for series compensated
lines (zone 1)

IEC 60617
identification

ZMCPDIS

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

Distance measuring zone, quadrilateral


characteristic for series compensated
lines (zone 2-5)

ZMCAPDIS

21

S00346 V1 EN

Directional impedance quadrilateral,


including series compensation

ZDSRDIR

21D

Z<->
IEC09000167 V1 EN

6.2.1

Introduction
The line distance protection is a, up to five zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone resistive and
reactive reach give flexibility for use on overhead lines and cables of different
types and lengths.
Quadrilateral characteristic is available.
ZMCPDIS function has functionality for load encroachment which increases the
possibility to detect high resistive faults on heavily loaded lines.
X
Forward
operation

R
Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 89:

Typical quadrilateral distance protection zone with load


encroachment function activated

175
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
Built-in adaptive load compensation algorithm for the quadrilateral function
prevents overreaching of zone1 at load exporting end at phase to earth-faults on
heavily loaded power lines.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.

6.2.2

Principle of operation

6.2.2.1

Full scheme measurement


The execution of the different fault loops within the IED are of full scheme type,
which means that earth fault loop for phase-to-earth faults and phase-to-phase
faults for forward and reverse faults are executed in parallel.
Figure 90 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones.
L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 1

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 2

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 3

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 4

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 5

en05000458.vsd
IEC05000458 V1 EN

Figure 90:

The different measuring loops at phase-to-earth fault and phase-tophase fault

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

6.2.2.2

Impedance characteristic
Distance measuring zone, quadrilateral characteristic for series compensated lines
(ZMCPDIS) include six impedance measuring loops; three intended for phase-toearth faults, and three intended for phase-to-phase as well as, three-phase faults.

176
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The distance measuring zone operates according to the non-directional impedance


characteristics presented in figure 91 and figure 92. The phase-to-earth
characteristic is illustrated with the full loop reach while the phase-to-phase
characteristic presents the per-phase reach.
X (Ohm/loop)

R1PE+RNFw
RFRvPE

RFFwPE

X 0 PE - X 1FwPE
3
X
1RvPE
X
0
PG
X
1
RVPG
X 0 PE =
- XXNFw
1RVPE
XNRV
XNRV XNRv
==
33
X 1FwPE
XNFw =

XX0 PE
- X-1X
FWPE
0 PG
1FWPG
XNFW
XNFW==
3 3

X1FwPE+XNFw

jN

jN

RNFw =

R0 PE - R1PE
3

R (Ohm/loop)
RFRvPE

RFFwPE

X1RvPE+XNRv

jN
RFRvPE

RFFwPE
IEC09000625-1-en.vsd

IEC09000625 V1 EN

Figure 91:

Characteristic for the phase-to-earth measuring loops, ohm/loop


domain

177
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RFRvPP

(Ohm/phase)

R1PP

RFFwPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
33
X
0
PE
--1X
11FWPE
X
0
PE
X 0 PG X
XFWPE
FWPG
XNFW
XNFW
XNFW===
3 33

X1FwPP

j
jN
RFRvPP

RFFwPP

j
R (Ohm/phase)

X1RvPP

jN
RFRvPP

RFFwPP

IEC09000632-1-en.vsd

IEC09000632 V1 EN

Figure 92:

Characteristic for the phase-to-phase measuring loops

The fault loop reach with respect to each fault type may also be presented as in
figure 93. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.

178
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

UL1

IL1

R1 + j X1

Phase-to-earth
fault in phase L1

Phase-to-earth
element

RFPE
(Arc + tower
resistance)
0

Phase-to-phase
fault in phase
L1-L2

UL1

IN

(R0-R1)/3 +
j (X0-X1)/3 )

IL1

R1 + j X1

Phase-to-phase
element L1-L2
RFPP

IL2

(Arc resistance)

UL2
R1 + j X1

UL1
Three-phase
fault

IL1

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

Phase-to-phase
element L1-L3

IL3
UL3
IEC08000282-2-en.vsd

IEC08000282 V2 EN

Figure 93:

Fault loop model

The R1 and jX1 in figure 93 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE and RFPP is the eventual fault
resistance in the fault place.
Regarding the illustration of three-phase fault in figure 93, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
The zone may be set to operate in Non-directional, Forward or Reverse direction
through the setting OperationDir. The result from respective set value is illustrated
in figure 94. It may be convenient to once again mention that the impedance reach
is symmetric, forward and reverse direction. Therefore, all reach settings apply to
both directions.

179
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Non-directional

Forward

Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 94:

6.2.2.3

Directional operating modes of the distance measuring zone

Minimum operating current


The operation of Distance measuring zone, quadrilateral characteristic for series
compensated lines (ZMCPDIS,ZMCAPDIS) is blocked if the magnitude of input
currents fall below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.
The phase-to-phase loop LmLn is blocked if ILmLnAB (BC or CA)< IMinOpPP.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are
automatically reduced to 75% of regular set values if the zone is set
to operate in reverse direction, that is, OperationDir=Reverse.

6.2.2.4

Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

180
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

calculation of the apparent impedances at ph-ph faults follows equation 14


(example for a phase L1 to phase L2 fault).
UL1 UL2
Zapp = ------------------------I L1 IL2
(Equation 14)

EQUATION1222 V1 EN

Here U and I represent the corresponding voltage and current phasors in the
respective phase.
The earth return compensation applies in a conventional manner to ph-E faults
(example for a phase L1 to earth fault) according to equation 15.
U L1
Z app = -----------------------------I L1 + I N KN
(Equation 15)

EQUATION1223 V1 EN

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN

KN =

is defined as:

Z0 - Z1
3 Z1

EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0

is setting of the resistive zero sequence reach

X0

is setting of the reactive zero sequence reach

R1

is setting of the resistive positive sequence reach

X1

is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current at the IED point. This results in the same
reach along the line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and
reactance X.

181
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The formula given in equation 15 is only valid for no loaded radial feeder
applications. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 16,
X Di
U = R i + ------ ----w 0 Dt
EQUATION1224 V1 EN

(Equation 16)

in complex notation, or:


X D Re ( I )
Re ( U ) = R Re ( I ) + ------ -----------------w0
Dt
EQUATION354 V1 EN

(Equation 17)

X DIm ( I )
Im ( U ) = R Im ( I ) + ------ ----------------w0
Dt
EQUATION355 V1 EN

(Equation 18)

with
w0 = 2 p f 0
EQUATION356 V1 EN

(Equation 19)

where:
Re

designates the real component of current and voltage,

Im

designates the imaginary component of current and voltage and

f0

designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

182
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Im ( U ) DRe ( I ) Re ( U ) D Im ( I )
R m = -----------------------------------------------------------------------------------DRe ( I ) Im ( I ) D Im ( I ) Re ( I )
EQUATION357 V1 EN

(Equation 20)

Re ( U ) Im ( I ) Im ( U ) Re ( I )
Xm = w 0 Dt ------------------------------------------------------------------------------DRe ( I ) Im ( I ) DIm ( I ) Re ( I )
EQUATION358 V1 EN

(Equation 21)

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and
reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.2.2.5

Directionality for series compensation


In the basic distance protection function, the control of the memory for polarizing
voltage is performed by an under voltage control. In case of series compensated
line, a voltage reversal can occur with a relatively high voltage also when the
memory must be locked. Thus, a simple undervoltage type of voltage memory
control can not be used in case of voltage reversal. In the option for series
compensated network the polarizing quantity and memory are controlled by an
impedance measurement criterion.
The polarizing voltage is a memorized positive sequence voltage. The memory is
continuously synchronized via a positive sequence filter. The memory is starting to
run freely instantaneously when a voltage change is detected in any phase. A nondirectional impedance measurement is used to detect a fault and identify the faulty
phase or phases.
At a three phase fault when no positive sequence voltage remains (all three phases
are disconnected) the memory is used for direction polarization during 100 ms.
The memory predicts the phase of the positive sequence voltage with the pre-fault
frequency. This extrapolation is made with a high accuracy and it is not the
accuracy of the memory that limits the time the memory can be used. The network
is at a three phase fault under way to a new equilibrium and the post-fault condition
can only be predicted accurately for a limited time from the pre-fault condition.
In case of a three phase fault after 100 ms the phase of the memorized voltage can
not be relied upon and the directional measurement has to be blocked. The
achieved direction criteria are sealed-in when the directional measurement is
blocked and kept until the impedance fault criteria is reset (the direction is stored
until the fault is cleared).
183

Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

This memory control allows in the time domain unlimited correct directional
measurement for all unsymmetrical faults also at voltage reversal. Only at three
phase fault within the range of the set impedance reach of the criteria for control of
the polarization voltage the memory has to be used and the measurement is limited
to 100 ms and thereafter the direction is sealed-in. The special impedance
measurement to control the polarization voltage is set separately and has only to
cover (with some margin) the impedance to fault that can cause the voltage reversal.
The evaluation of the directionality takes place in Directional impedance
quadrilateral, including series compensation (ZDSRDIR) function. Equation 22 and
equation 23 are used to classify that the fault is in forward direction for phase-toearth fault and phase-to-phase fault.
- ArgDir < arg

U 1L1M
< ArgNeg Re s
I L1
(Equation 22)

EQUATION2004 V2 EN

For the L1-L2 element, the equation in forward direction is according to:
- ArgDir < arg

U 1L1L 2 M
< ArgNeg Re s
I L1L 2
(Equation 23)

EQUATION2006 V2 EN

where:

ArgDir

is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and

ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 95.
U1L1M

is positive sequence memorized phase voltage in phase L1

IL1

is phase current in phase L1

U1L1L2M

is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2

is current difference between phase L1 and L2 (L2 lagging L1)

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively, see figure 95, and it should not be changed unless system
studies have shown the necessity.
ZDSRDIR generates a binary coded signal on the output STDIR depending on the
evaluation where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4.

184
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ArgNegRes

ArgDir

en05000722.vsd
IEC05000722 V1 EN

Figure 95:

Setting angles for discrimination of forward and reverse fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.

6.2.2.6

Simplified logic diagrams


Distance protection zones

The design of distance protection zones are presented for all measuring loops: phaseto-earth as well as phase-to-phase.
Phase-to-earth related signals are designated by Ln, where n represents the
corresponding phase number (L1, L2, and L3). The phase-to-phase signals are
designated by LnLm, where n and m represent the corresponding phase numbers
(L1L2, L2L3, and L3L1).
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described


above.
Group functional input signal (STCND), as presented in figure 96.

Two types of function block, ZMCPDIS and ZMCAPDIS, are used in the IED.
ZMCPDIS is used for zone 1 and ZMCAPDIS for zone 2 - 5.

185
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to Phase selection with load enchroachment,
quadrilateral characteristic (FDPSPDIS) function output STCNDZ.

IEC99000557-TIFF V1 EN

Figure 96:

Conditioning by a group functional input signal STCND

Composition of the phase starting signals for a case, when the zone operates in a nondirectional mode, is presented in figure 97.

186
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IEC00000488-TIFF V1 EN

Figure 97:

Composition of starting signals in non-directional operating mode

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 98.
STNDL1N
DIRL1N

AND
OR

STNDL2N
DIRL2N

AND

STNDL3N

OR

DIRL3N

AND

STNDL1L2
DIRL1L2

AND

STNDL2L3
DIRL2L3

AND

STNDL3L1
DIRL3L1

STZMPE.

AND

OR

OR

AND

15 ms
t

STL1

AND

15 ms
t

STL2

AND

15 ms
t

STL3

AND
OR

STZMPP

AND

BLK

OR

AND

15 ms
t

START

IEC09000888-1-en.vsd
IEC09000888 V1 EN

Figure 98:

Composition of starting signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 99.

187
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Timer tPP=On
STZMPP

AND

tPP
t

AND

tPE
t

Timer tPE=On
STZMPE
BLKTR
BLK

OR

15ms
OR

AND

TRIP

STL1

AND

TRL1

STL2

AND

TRL2

STL3

AND

TRL3

en00000490-3.vsd
IEC00000490 2 V1 EN

Figure 99:

6.2.3

Tripping logic for the distance protection zone one

Function block
ZMCPDIS
I3P*
U3P*
BLOCK
VTSZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC07000036-2-en.vsd

IEC07000036 V2 EN

Figure 100:

ZMCPDIS function block

ZMCAPDIS
I3P*
U3P*
BLOCK
VTSZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC09000890-1-en.vsd

IEC09000890 V1 EN

Figure 101:

ZMCAPDIS function block

188
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ZDSRDIR
I3P*
U3P*

STFW
STRV
STDIRCND
IEC07000035-2-en.vsd

IEC07000035 V2 EN

Figure 102:

6.2.4

ZDSRDIR function block

Input and output signals


Input and output signals is shown for zone 1, zone 2 - 5 are equal.

Table 103:
Name

ZMCPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

VTSZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 104:
Name

ZMCPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

189
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 105:
Name

ZMCAPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

VTSZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 106:
Name

ZMCAPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

Table 107:

ZDSRDIR Input signals

Name

Type

Default

Description

I3P

GROUP
SIGNAL

Group connection for current

U3P

GROUP
SIGNAL

Group connection for voltage

Table 108:
Name

ZDSRDIR Output signals


Type

Description

STFW

BOOLEAN

Start in forward direction

STRV

BOOLEAN

Start in reverse direction

STDIRCND

INTEGER

Binary coded directional information per


measuring loop

190
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.2.5

Setting parameters
Settings for ZMCPDIS are valid for zone 1, while settings for
ZMCAPDIS are valid for zone 2 - 5

Table 109:

ZMCPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

X1FwPP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhPh, forward

R1PP

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

RFFwPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

X1RvPP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhPh, reverse

RFRvPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

X1FwPE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhE, forward

R1PE

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-E

X0PE

0.10 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-E

R0PE

0.01 - 3000.00

ohm/p

0.01

47.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFFwPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, forward

X1RvPE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhE, reverse

RFRvPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, reverse

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

Table continues on next page

191
Technical reference manual

Section 6
Impedance protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

IMinOpIN

5 - 1000

%IB

Minimum operate residual current for


Phase-Earth loops

Table 110:
Name

ZMCAPDIS Group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

X1FwPP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhPh, forward

R1PP

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

RFFwPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

X1RvPP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhPh, reverse

RFRvPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

X1FwPE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhE, forward

R1PE

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-E

X0PE

0.10 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-E

R0PE

0.01 - 3000.00

ohm/p

0.01

47.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFFwPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, forward

X1RvPE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach, PhE, reverse

RFRvPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, reverse

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

Table continues on next page

192
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

Table 111:

Step

Default

Description

ZDSRDIR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

OperationSC

NoSeriesComp
SeriesComp

SeriesComp

Special directional criteria for voltage


reversal

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

IMinOpPE

5 - 30

%IB

Minimum operate phase current for


Phase-Earth loops

IMinOpPP

5 - 30

%IB

10

Minimum operate delta current for PhasePhase loops

ArgNegRes

90 - 175

Deg

130

Angle of blinder in second quadrant for


forward direction

ArgDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for


forward direction

INReleasePE

10 - 100

%IPh

20

3I0 limit for releasing phase-to-earth


measuring loops

INBlockPP

10 - 100

%IPh

40

3I0 limit for blocking phase-to-phase


measuring loops

OperationLdCh

Off
On

On

Operation of load discrimination


characteristic

RLdFw

1.00 - 3000.00

ohm/p

0.01

80.00

Forward resistive reach within the load


impedance area

RLdRv

1.00 - 3000.00

ohm/p

0.01

80.00

Reverse resistive reach within the load


impedance area

ArgLd

5 - 70

Deg

30

Load angle determining the load


impedance area

X1FwPP

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach, PhPh, forward

R1PP

0.10 - 1000.00

ohm/p

0.01

7.00

Positive seq. resistance for characteristic


angle, Ph-Ph

RFFwPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

X1RvPP

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach, PhPh, reverse

RFRvPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

X1FwPE

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach, PhE, forward

R1PE

0.10 - 1000.00

ohm/p

0.01

7.00

Positive seq. resistance for characteristic


angle, Ph-E

X0FwPE

0.50 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach, Ph-E,


forward

Table continues on next page

193
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Name

Values (Range)

Step

Default

R0PE

0.50 - 3000.00

ohm/p

0.01

20.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFFwPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, forward

X1RvPE

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach, PhE, reverse

X0RvPE

0.50 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach, Ph-E,


reverse

RFRvPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, reverse

6.2.6

Unit

Description

Technical data
Table 112:

ZMCPDIS, ZMCAPDIS Technical data

Function

Range or value

Accuracy

Number of zones

Max 5 with selectable direction

Minimum operate residual


current, zone 1

(5-1000)% of IBase

Minimum operate current, Ph-Ph


and Ph-E

(10-1000)% of IBase

Positive sequence reactance

(0.10-3000.00) /phase

Positive sequence resistance

(0.10-1000.00) /phase

Zero sequence reactance

(0.01-9000.00) /phase

Zero sequence resistance

(0.01-3000.00) /phase

Fault resistance, Ph-E

(0.10-9000.00) /loop

Fault resistance, Ph-Ph

(0.10-3000.00) /loop

2.0% static accuracy


2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85
degrees

Dynamic overreach

<5% at 85 degrees measured


with CCVTs and 0.5<SIR<30

Impedance zone timers

(0.000-60.000) s

0.5% 10 ms

Operate time

24 ms typically

Reset ratio

105% typically

Reset time

30 ms typically

6.3

Phase selection, quadrilateral characteristic with


fixed angle FDPSPDIS

6.3.1

Identification
Function description
Phase selection with load
encroachment, quadrilateral
characteristic

IEC 61850
identification

IEC 60617
identification

FDPSPDIS

ANSI/IEEE C37.2
device number
21

Z<phs
SYMBOL-DD V1 EN

194
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.3.2

Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations, the rate of expansion and
reinforcement of the power system is reduced, for example, difficulties to get
permission to build new power lines. The ability to accurately and reliably classify
the different types of fault, so that single pole tripping and autoreclosing can be
used plays an important role in this matter.Phase selection, quadrilateral
characteristic with fixed angle FDPSPDIS is designed to accurately select the
proper fault loop in the distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may make
fault resistance coverage difficult to achieve. Therefore, FDPSPDIS has a built-in
algorithm for load encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring zones without
interfering with the load.
The extensive output signals from the phase selection gives also important
information about faulty phase(s), which can be used for fault analysis.
A current-based phase selection is also included. The measuring elements
continuously measure three phase currents and the residual current and, compare
them with the set values.

6.3.3

Principle of operation
The basic impedance algorithm for the operation of the phase selection measuring
elements is the same as for the distance zone measuring function. Phase selection
with load encroachment, quadrilateral characteristic FDPSPDIS includes six
impedance measuring loops; three intended for phase-to-earth faults, and three
intended for phase-to-phase faults as well as for three-phase faults.
The difference, compared to the distance zone measuring function, is in the
combination of the measuring quantities (currents and voltages) for different types
of faults.
A current-based phase selection is also included. The measuring elements
continuously measure three phase currents and the residual current, and compare
them with the set values. The current signals are filtered by Fourier's recursive
filter, and separate trip counter prevents too high overreaching of the measuring
elements.
The characteristic is basically non-directional, but FDPSPDIS uses information
from the directional function to discriminate whether the fault is in forward or
reverse direction.
The start condition STCNDZ is essentially based on the following criteria:

195
Technical reference manual

Section 6
Impedance protection

1.
2.
3.

1MRK 505 222-UEN B

Residual current criteria, that is, separation of faults with and without earth
connection
Regular quadrilateral impedance characteristic
Load encroachment characteristics is always active but can be switched off by
selecting a high setting.

The current start condition STCNDLE is based on the following criteria:


1.
2.
3.

Residual current criteria


No quadrilateral impedance characteristic. The impedance reach outside the
load area is theoretically infinite. The practical reach, however, will be
determined by the minimum operating current limits.
Load encroachment characteristic is always active, but can be switched off by
selecting a high setting.

The STCNDLE output is non-directional. The directionality is determined by the


distance zones directional function. There are outputs from FDPSPDIS that
indicate whether a start is in forward or reverse direction or non-directional, for
example STFWL1, STRVL1 and STNDL1.
These directional indications are based on the sector boundaries of the directional
function and the impedance setting of FDPSPDIS function. Their operating
characteristics are illustrated in figure 103.
X

Non-directional (ND)

Forward (FW)

Reverse (RV)
en08000286.vsd

IEC08000286 V1 EN

Figure 103:

Characteristics for non-directional, forward and reverse operation


of Phase selection with load encroachment, quadrilateral
characteristic FDPSPDIS

The setting of the load encroachment function may influence the total operating
characteristic, (for more information, refer to section "Load encroachment").
The input DIRCND contains binary coded information about the directional
coming from the directional function . It shall be connected to the STDIR output on
196
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ZDRDIR, directional measuring block. This information is also transferred to the


input DIRCND on the distance measuring zones, that is, the ZMQPDIS, distance
measuring block.
The code built up for the directionality is as follows:
STDIR=

STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

If the binary information is 1 then it will be considered that we have start in


forward direction in phase L1. If the binary code is 3 then we have start in forward
direction in phase L1 and L2, binary code 192 means start in reverse direction in
phase L1 and L2A and B etc.
The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary
coded information, in this case information about the condition for opening correct
fault loop in the distance measuring element. It shall be connected to the STCND
input on the ZMQPDIS, distance measuring block.
The code built up for release of the measuring fault loops is as follows:
STCND = L1N*1 + L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

6.3.3.1

Phase-to-earth fault
For a phase-to-earth fault, the measured impedance by FDPSPDIS will be
according to equation 24.
Index PHS in images and equations reference settings for Phase
selection with load encroachment function FDPSPDIS.

ZPHSn =

ULn
ILn

EQUATION1255 V1 EN

(Equation 24)

where:
n

corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FDPSPDIS function at phase-to-earth fault is according to


figure 104. The characteristic has a fixed angle for the resistive boundary in the
first quadrant of 60.
The resistance RN and reactance XN are the impedance in the earth-return path
defined according to equation 25 and equation 26.
197
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RN =

R0 - R1
3
(Equation 25)

EQUATION1256 V1 EN

XN =

X 0 - X1
3
(Equation 26)

EQUATION1257 V1 EN

X (ohm/loop)
Kr(X1+XN)
RFRvPE

RFFwPE

X1+XN
RFFwPE

R (Ohm/loop)

RFRvPE

60 deg

60 deg

X1+XN
Kr =

1
tan(60deg)

RFFwPE

RFRvPE
Kr(X1+XN)

en06000396.vsd
IEC06000396 V2 EN

Figure 104:

Characteristic of FDPSPDIS for phase-to-earth fault (setting


parameters in italic), ohm/loop domain (directional lines are drawn
as "line-dot-dot-line")

Besides this, the 3I0 residual current must fulfil the conditions according to
equation 27 and equation 28.
3 I0 0.5 IMinOpPE
EQUATION2108 V1 EN

(Equation 27)

198
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

3 I0 INReleasePE
------------------------------------ Iphmax
100
(Equation 28)

EQUATION766 V1 EN

where:

IMinOpPE

is the minimum operation current for forward zones

INReleasePE is the setting for the minimum residual current needed to enable operation in the phaseto-earth fault loops (in %).
Iphmax

6.3.3.2

is the maximum phase current in any of three phases.

Phase-to-phase fault
For a phase-to-phase fault, the measured impedance by FDPSPDIS will be
according to equation 29.
ZPHS =

ULm - ULn
-2 ILn

EQUATION1258 V1 EN

(Equation 29)

ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the
phase current in the lagging phase n.
The operation characteristic is shown in figure 105.

199
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (W /

phase)
0.5RFFwPP

0.5RFRvPP
KrX1

X1

0.5RFFwPP
60 deg

60 deg

R (W /
0.5RFRvPP

phase)

X1
Kr =

1
tan(60 deg)

KrX1
0.5RFRvPP

0.5RFFwPP
IEC09000047-2-en.vsd

IEC09000047 V2 EN

Figure 105:

The operation characteristics for FDPSPDIS at phase-to-phase


fault (setting parameters in italic, directional lines drawn as "line-dotdot-line"), ohm/phase domain

In the same way as the condition for phase-to-earth fault, there are current
conditions that have to be fulfilled in order to release the phase-to-phase loop.
Those are according to equation 30 or equation 31.

3I 0 < IMinOpPE
(Equation 30)

EQUATION2109 V1 EN

3I 0 <

INBlockPP
Iph max
100

(Equation 31)

EQUATION2110 V1 EN

where:

IMinOpPE

is the minimum operation current for earth measuring loops,

INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and


Iphmax

is maximal magnitude of the phase currents.

200
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.3.3.3

Three-phase faults
The operation conditions for three-phase faults are the same as for phase-to-phase
fault, that is equation 29, equation 30 and equation 31 are used to release the
operation of the function.
However, the reach is expanded by a factor 2/3 (approximately 1.1547) in all
directions. At the same time the characteristic is rotated 30 degrees, counterclockwise. The characteristic is shown in figure 106.
X (O/phase)
4 X1
3
90 deg
0.5RFFwPPK3
X1K3

4 RFFwPP
6

R (O/phase)
0.5RFRvPPK3
K3 = 2 / v(3)

30 deg

IEC05000671-3-en.vsd
IEC05000671 V3 EN

Figure 106:

6.3.3.4

The characteristic of FDPSPDIS for three-phase fault (setting


parameters in italic)

Load encroachment
Each of the six measuring loops has its own load encroachment characteristic based
on the corresponding loop impedance. The load encroachment functionality is
always active, but can be switched off by selecting a high setting.
The outline of the characteristic is presented in figure 107. As illustrated, the
resistive blinders are set individually in forward and reverse direction while the
angle of the sector is the same in all four quadrants.

201
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RLdFw
ArgLd

ArgLd

ArgLd

RLdRv

ArgLd

IEC09000042-1-en.vsd
IEC09000042 V1 EN

Figure 107:

Characteristic of load encroachment function

The influence of load encroachment function on the operation characteristic is


dependent on the chosen operation mode of FDPSPDIS function. When output
signal STCNDZ is selected, the characteristic for FDPSPDIS (and also zone
measurement depending on settings) will be reduced by the load encroachment
characteristic (see figure 108, left illustration).
When output signal STCNDLE is selected, the operation characteristic will be as
the right illustration in figure 108. The reach will in this case be limit by the
minimum operation current and the distance measuring zones.

202
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STCNDZ

STCNDLE
IEC10000099-1en.vsd

IEC10000099 V1 EN

Figure 108:

Difference in operating characteristic depending on operation


mode when load encroachment is activated

When FDPSPDIS is set to operate together with a distance measuring zone the
resultant operate characteristic could look like in figure 109. The figure shows a
distance measuring zone operating in forward direction. Thus, the operating area is
highlighted in black.

203
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X
"Phase selection"
"quadrilateral" zone
Distance measuring zone

Load encroachment
characteristic
R
Directional line

en05000673.vsd
IEC05000673 V1 EN

Figure 109:

Operating characteristic in forward direction when load


encroachment is activated

Figure 109 is valid for phase-to-earth. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation
the operate area is transformed according to figure 110. Notice in particular what
happens with the resistive blinders of the "phase selection" "quadrilateral" zone.
Due to the 30-degree rotation, the angle of the blinder in quadrant one is now 90
degrees instead of the original 60 degrees. The blinder that is nominally located to
quadrant four will at the same time tilt outwards and increase the resistive reach
around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.

204
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (W /

phase)

Phase selection
Quadrilateral zone

Distance measuring zone

R (W /

phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN

Figure 110:

Operating characteristic for FDPSPDIS in forward direction for threephase fault, ohm/phase domain

The result from rotation of the load characteristic at a fault between two phases is
presented in fig 111. Since the load characteristic is based on the same
measurement as the quadrilateral characteristic, it will rotate with the quadrilateral
characteristic clockwise by 30 degrees when subject to a pure phase-to-phase fault.
At the same time the characteristic will "shrink" by 2/3, from the full RLdFw and
RLdRv reach, which is valid at load or three-phase fault.

205
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IEC08000437.vsd
IEC08000437 V1 EN

Figure 111:

Rotation of load characteristic for a fault between two phases

There is a gain in selectivity by using the same measurement as for the


quadrilateral characteristic since not all phase-to-phase loops will be fully affected
by a fault between two phases. It should also provide better fault resistive coverage
in quadrant one. The relative loss of fault resistive coverage in quadrant four
should not be a problem even for applications on series compensated lines.

6.3.3.5

Minimum operate currents


The operation of the Phase selection with load encroachment function (FDPSPDIS)
is blocked if the magnitude of input currents falls below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS
value of the current in phase Ln.
The phase-to-phase loop LmLn is blocked if (2ILn<IMinOpPP).

6.3.3.6

Simplified logic diagrams


Figure 112 presents schematically the creation of the phase-to-phase and phase-toearth operating conditions. Consider only the corresponding part of measuring and

206
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

logic circuits, when only a phase-to-earth or phase-to-phase measurement is


available within the IED.
Load encroachment block

3I 0 0.5 IMinOpPE
&
INReleasePE
3I 0
Iphmax
100

IRELPE
15 ms
t

&

&

Bool to
integer

BLOCK

3I 0 < IMinOpPE

OR
INBlockPP
3I 0 <
Iphmax
100

STPE

&

10 ms 20 ms
t
t

&

15 ms
t

STCNDLE

STPP
IRELPP

IEC09000149_1_en.vsd
IEC09000149 V1 EN

Figure 112:

Phase-to-phase and phase-to-earth operating conditions (residual


current criteria)

A special attention is paid to correct phase selection at evolving faults. A


STCNDLE output signal is created as a combination of the load encroachment
characteristic and current criteria, refer to figure 112. This signal can be configured
to STCND functional input signals of the distance protection zone and this way
influence the operation of the phase-to-phase and phase-to-earth zone measuring
elements and their phase related starting and tripping signals.
Figure 113 presents schematically the composition of non-directional phase
selective signals STNDLn. Internal signals ZMLnN and ZMLmLn (m and n
change between one and three according to the phase number) represent the
fulfilled operating criteria for each separate loop measuring element, that is, within
the characteristic.

207
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

INDL1N
INDL2N
INDL3N

OR

15 ms
t

STNDPE

OR

15 ms
t

STNDL1

OR

15 ms
t

STNDL2

AND

OR

15 ms
t

STNDL3

AND

INDL1L2

IRELPE
ZML1N
ZML2N
ZML3N
ZML1L2
ZML2L3
ZML3L1
IRELPP

AND
AND
AND

INDL2L3
AND

INDL3L1
OR

15 ms
t

STNDPP

IEC00000545_2_en.vsd
IEC00000545-TIFF V2 EN

Figure 113:

Composition on non-directional phase selection signals

Composition of the directional (forward and reverse) phase selective signals is


presented schematically in figure 115 and figure 114. The directional criteria
appears as a condition for the correct phase selection in order to secure a high
phase selectivity for simultaneous and evolving faults on lines within the complex
network configurations. Internal signals DFWLn and DFWLnLm present the
corresponding directional signals for measuring loops with phases Ln and Lm.
Designation FW (figure 115) represents the forward direction as well as the
designation RV (figure 114) represents the reverse direction. All directional signals
are derived within the corresponding digital signal processor.
Figure 114 presents additionally a composition of a STCNDZ output signal, which
is created on the basis of impedance measuring conditions. This signal can be
configured to STCND functional input signals of the distance protection zone and
this way influence the operation of the phase-to-phase and phase-to-earth zone
measuring elements and their phase related starting and tripping signals.

208
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

INDL1N
DRVL1N

AND

INDL1L2
DRVL1L2

AND

OR

15 ms
t

STRVL1

OR

15 ms
t

STRVPE

OR

15 ms
t

STRVL2

INDL3L1
DRVL3L1

AND

INDL2N
DRVL2N

AND

INDL1L2
AND
INDL2L3
DRVL2L3

INDL1N
INDL2N
INDL3N
INDL1L2
INDL2L3
INDL3L1

AND

INDL3N
DRVL3N

AND

INDL2L3

Bool to
integer

15 ms
AND

OR

INDL3L1
AND

15 ms
OR

STCNDZ

STRVL3

STRVPP

IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN

Figure 114:

Composition of phase selection signals for reverse direction

209
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

AND
INDL1N
DFWL1N

AND

AND

OR

15 ms
t

INDL1L2
DFWL1L2

AND

OR

INDL3L1
DFWL3L1

DFWL2N

OR

15 ms
t

STFWL1

15 ms
t

STFWPE

15 ms
t

STFWL2

15 ms
t

STFW2PH

AND
AND

INDL1L2
AND

OR

INDL2L3
DFWL2L3

STFW1PH

AND

AND

INDL2N

15 ms
t

AND

OR

15 ms
t

AND

INDL3N
DFWL3N

AND

AND

INDL2L3
AND

15 ms
t

STFWL3

15 ms
t

STFW3PH

15 ms
t

STFWPP

OR

INDL3L1

AND
AND

OR

IEC05000201_2_en.vsd
IEC05000201 V2 EN

Figure 115:

Composition of phase selection signals for forward direction

Figure 116 presents the composition of output signals TRIP and START, where
internal signals STNDPP, STFWPP and STRVPP are the equivalent to internal
signals STNDPE, STFWPE and STRVPE, but for the phase-to-phase loops.

210
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

TimerPP=Off

tPP
t

AND
OR

TimerPE=Off

tPE
t

AND

AND
OR

TRIP

AND

STNDPP
STFWPP

OR

STRVPP
OR

STNDPE
STFWPE

START

OR

STRVPE

IEC08000441_2_en.vsd
IEC08000441 1 V2 EN

Figure 116:

6.3.4

TRIP and START signal logic

Function block
FDPSPDIS
I3P*
U3P*
BLOCK
DIRCND

TRIP
START
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE
IEC10000047-1-en.vsd

IEC10000047 V1 EN

Figure 117:

FDPSPDIS function block


211

Technical reference manual

Section 6
Impedance protection
6.3.5

1MRK 505 222-UEN B

Input and output signals


Table 113:
Name

FDPSPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

DIRCND

INTEGER

External directional condition

Table 114:
Name

FDPSPDIS Output signals


Type

Description

TRIP

BOOLEAN

Trip output

START

BOOLEAN

Start in any phase or loop

STFWL1

BOOLEAN

Fault detected in phase L1 - forward direction

STFWL2

BOOLEAN

Fault detected in phase L2 - forward direction

STFWL3

BOOLEAN

Fault detected in phase L3 - forward direction

STFWPE

BOOLEAN

Earth fault detected in forward direction

STRVL1

BOOLEAN

Fault detected in phase L1 - reverse direction

STRVL2

BOOLEAN

Fault detected in phase L2 - reverse direction

STRVL3

BOOLEAN

Fault detected in phase L3 - reverse direction

STRVPE

BOOLEAN

Earth fault detected in reverse direction

STNDL1

BOOLEAN

Non directional start in L1

STNDL2

BOOLEAN

Non directional start in L2

STNDL3

BOOLEAN

Non directional start in L3

STNDPE

BOOLEAN

Non directional start, phase-earth

STFW1PH

BOOLEAN

Start in forward direction for single-phase fault

STFW2PH

BOOLEAN

Start in forward direction for two- phase fault

STFW3PH

BOOLEAN

Start in forward direction for thre-phase fault

STPE

BOOLEAN

Current conditions release of phase-earth


measuring elements

STPP

BOOLEAN

Current conditions release of phase-phase


measuring elements

STCNDZ

INTEGER

Start condition (Z< with LE and 3I0 E/F detection)

STCNDLE

INTEGER

Start condition (only LE and 3I0 E/F detection)

212
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.3.6
Table 115:

Setting parameters
FDPSPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.01

400.00

Base voltage, i.e. rated voltage

INBlockPP

10 - 100

%IPh

40

3I0 limit for blocking phase-to-phase


measuring loops

INReleasePE

10 - 100

%IPh

20

3I0 limit for releasing phase-to-earth


measuring loops

RLdFw

1.00 - 3000.00

ohm/p

0.01

80.00

Forward resistive reach within the load


impedance area

RLdRv

1.00 - 3000.00

ohm/p

0.01

80.00

Reverse resistive reach within the load


impedance area

ArgLd

5 - 70

Deg

30

Load angle determining the load


impedance area

X1

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach

X0

0.50 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach

RFFwPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

RFRvPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

RFFwPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, forward

RFRvPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, reverse

IMinOpPP

5 - 500

%IB

10

Minimum operate delta current for PhasePhase loops

IMinOpPE

5 - 500

%IB

Minimum operate phase current for


Phase-Earth loops

Table 116:

FDPSPDIS Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

OperationZ<

Off
On

On

Operation of impedance based


measurement

OperationI>

Off
On

Off

Operation of current based measurement

IPh>

10 - 2500

%IB

120

Start value for phase over-current


element

IN>

10 - 2500

%IB

20

Start value for trip from 3I0 over-current


element

TimerPP

Off
On

Off

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-Ph

TimerPE

Off
On

Off

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-E

213
Technical reference manual

Section 6
Impedance protection
6.3.7

1MRK 505 222-UEN B

Technical data
Table 117:

FDPSPDIS technical data

Function

6.4

Range or value

Accuracy

Minimum operate current

(5-500)% of IBase

Reactive reach, positive


sequence

(0.503000.00) /phase

Resistive reach, positive


sequence

(0.101000.00) /phase

Reactive reach, zero sequence

(0.509000.00) /phase

Resistive reach, zero sequence

(0.503000.00) /phase

2.0% static accuracy


2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85
degrees

Fault resistance, phase-to-earth


faults, forward and reverse

(1.009000.00) /loop

Fault resistance, phase-tophase faults, forward and reverse

(0.503000.00) /loop

Load encroachment criteria:


Load resistance, forward and
reverse
Safety load impedance angle

(1.003000.00) /phase
(5-70) degrees

Reset ratio

105% typically

Full-scheme distance measuring, Mho


characteristic ZMHPDIS
Function description

Full-scheme distance protection, mho


characteristic

IEC 61850
identification

IEC 60617 identification

ZMHPDIS

ANSI/IEEE
C37.2 device
number
21

S00346 V1 EN

6.4.1

Introduction
The numerical mho line distance protection is a, up to five zone full scheme
protection for back-up detection of short circuit and earth faults. The full scheme
technique provides back-up protection of power lines with high sensitivity and low
requirement on remote end communication. The five zones have fully independent
measuring and settings, which gives high flexibility for all types of lines.
The IED can be used up to the highest voltage levels. It is suitable for the
protection of heavily loaded lines and multi-terminal lines where the requirement
for tripping is one-, two- and/or three-pole.

214
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase autoreclosing.
Built-in adaptive load compensation algorithm prevents overreaching at phase-toearth faults on heavily loaded power lines, see figure 118.
jX

Operation area

Operation area

Operation area

No operation area

No operation area

en07000117.vsd
IEC07000117 V1 EN

Figure 118:

Load encroachment influence on the offset mho characteristic

The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode (offset). This makes them suitable,
together with different communication schemes, for the protection of power lines
and cables in complex network configurations, such as parallel lines, multiterminal lines and so on.
The possibility to use the phase-to-earth quadrilateral impedance characteristic
together with the mho characteristic increases the possibility to overcome eventual
lack of sensitivity of the mho element due to the shaping of the curve at remote end
faults.
The integrated control and monitoring functions offer effective solutions for
operating and monitoring all types of transmission and sub-transmission lines.

6.4.2

Principle of operation

6.4.2.1

Full scheme measurement


The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
are executed in parallel.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current

215
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.

6.4.2.2

Impedance characteristic
The distance function consists of five instances. Each instance can be selected to be
either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The
operating characteristic is in accordance to figure 119 where zone 5 is selected
offset mho.
jx
X
Mho, zone4
Mho, zone3
Zs=0
Mho, zone2
R

Mho, zone1

Zs=Z1

Zs=2Z1

Offset mho, zone5

IEC09000143-1-en.vsd
IEC09000143 V1 EN

Figure 119:

Mho, offset mho characteristic and the source impedance influence on the mho characteristic

The mho characteristic has a dynamic expansion due to the source impedance.
Instead of crossing the origin as for the mho to the left of figure 119, which is only
valid where the source impedance is zero, the crossing point is moved to the
coordinates of the negative source impedance given an expansion of the circle
shown to the right of figure 119.
The polarization quantities used for the mho circle are 100% memorized positive
sequence voltages. This will give a somewhat less dynamic expansion of the mho
circle during faults. However, if the source impedance is high, the dynamic
expansion of the mho circle might lower the security of the function too much with
high loading and mild power swing conditions.
The mho distance element has a load encroachment function which cuts off a
section of the characteristic when enabled. The function is enabled by setting the
setting parameter LoadEnchMode to On. Enabling of the load encroachment
216
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

function increases the possibility to detect high resistive faults without interfering
with the load impedance. The algorithm for the load encroachment is located in the
Faulty phase identification with load encroachment for mho function FMPSPDIS,
where also the relevant settings can be found. Information about the load
encroachment from FMPSPDIS to the zone measurement is given in binary format
to the input signal LDCND.

6.4.2.3

Basic operation characteristics


Each impedance zone can be switched On and Off by the setting parameter
Operation.
Each zone can also be set to Non-directional, Forward or Reverse by setting the
parameter DirMode.
The operation for phase-to-earth and phase-to-phase fault can be individually
switched On and Off by the setting parameter OpModePE and OpModePP.
For critical applications such as for lines with high SIRs as well as CVTs, it is
possible to improve the security by setting the parameter ReachMode to
Underreach. In this mode the reach for faults close to the zone reach is reduced by
20% and the filtering is also introduced to increase the accuracy in the measuring.
If the ReachMode is set to Overreach no reduction of the reach is introduced and
no extra filtering introduced. The latter setting is recommended for overreaching
pilot zone, zone 2 or zone 3 elements and reverse zone where overreaching on
transients is not a major issue either because of less likelihood of overreach with
higher settings or the fact that these elements do not initiate tripping unconditionally.
The offset mho characteristic can be set in Non-directional, Forward or Reverse by
the setting parameter OffsetMhoDir. When Forward or Reverse is selected a
directional line is introduced. Information about the directional line is given from
the directional element and given to the measuring element as binary coded signal
to the input DIRCND.
The zone reach for phase-to-earth fault and phase-to-phase fault is set individually
in polar coordinates.
The impedance is set by the parameters ZPE and ZPP and the corresponding
arguments by the parameters ZAngPE and ZAngPP.
Compensation for earth-return path for faults involving earth is done by setting the
parameter KNMag and KNAng where KNMag is the magnitude of the earth-return
path and KNAng is the difference of angles between KNMag and ZPE.
KNMag =
EQUATION1579 V1 EN

Z0-Z1
3 Z1
(Equation 32)

217
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

KNAng = arg

Z 0 - Z1
3 Z1

)
(Equation 33)

EQUATION1580 V1 EN

where
Z0

is the complex zero sequence impedance of the line in /phase

Z1

is the complex positive sequence impedance of the line in /phase

The phase-to-earth and phase-to-phase measuring loops can be time delayed


individually by setting the parameter tPE and tPP respectively. To release the time
delay, the operation mode for the timers, OpModetPE and OpModetPP, has to be
set to On. This is also the case for instantaneous operation.
The function can be blocked in the following ways:

activating of input BLOCK blocks the whole function


activating of the input BLKZ (fuse failure) blocks all output signals
activating of the input BLKZMTD blocks the delta based algorithm
activating of the input BLKHSIR blocks the instantaneous part of the
algorithm for high SIR values
activating of the input BLKTRIP blocks all output signals
activating the input BLKPE blocks the phase-to-earth fault loop outputs
activating the input BLKPP blocks the phase-to-phase fault loop outputs

The activation of input signal BLKZ can be made by external fuse failure function
or from the loss of voltage check in the Mho supervision logic (ZSMGAPC). In
both cases the output BLKZ in the Mho supervision logic shall be connected to the
input BLKZ in the Mho distance function block (ZMHPDIS)
The input signal BLKZMTD is activated during some ms after fault has been
detected by ZSMGAPC to avoid unwanted operations due to transients. It shall be
connected to the BLKZMTD output signal of ZSMGAPC function.
At SIR values >10, the use of electronic CVT might cause overreach due to the builtin resonance circuit in the CVT, which reduce the secondary voltage for a while.
The input BLKHSIR shall be connected to the output signal HSIR on ZSMGAPC
for increasing of the filtering and high SIR values. This is valid only when
permissive underreach scheme is selected by setting ReachMode=Underreach.

6.4.2.4

Theory of operation
The mho algorithm is based on the phase comparison of a operating phasor and a
polarizing phasor. When the operating phasor leads the reference polarizing phasor
by more than 90 degrees, the function operates and gives a trip output.

218
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Phase-to-phase fault
Mho
The plain mho circle has the characteristic as in figure 120. The condition for
deriving the angle is according to equation 34.

b = arg(U L1 L 2 - I L1 L 2 ZPP ) - arg(U pol )


(Equation 34)

EQUATION1789 V1 EN

where

U L1L2

is the voltage vector difference between phases L1 and L2

EQUATION1790 V2
EN

I L1L2

is the current vector difference between phases L1 and L2

EQUATION1791 V2
EN

ZPP

is the positive sequence impedance setting for phase-to-phase fault

Upol

is the polarizing voltage

The polarized voltage consists of 100% memorized positive sequence voltage


(UL1L2 for phase L1 to L2 fault). The memorized voltage will prevent collapse of
the mho circle for close in faults.
Operation occurs if 90270

219
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IL1L2X

Ucomp = UL1L2 - IL1L2 ZPP


IL1L2 ZPP

Upol
UL1L2

IL1L2R

en07000109.vsd
IEC07000109 V1 EN

Figure 120:

Simplified mho characteristic and vector diagram for phase L1-toL2 fault

Offset Mho
The characteristic for offset mho is a circle where two points on the circle are the
setting parameters ZPP and ZRevPP. The vector ZPP in the impedance plane has
the settable angle AngZPP and the angle for ZRevPP is AngZPP+180.
The condition for operation at phase-to-phase fault is that the angle between the
two compensated voltages Ucomp1 and Ucomp2 is greater than or equal to 90
(figure 121). The angle will be 90 for fault location on the boundary of the circle.
The angle for L1-to-L2 fault can be defined according to equation 35.

U-(-IL1L2 ZRevPP)

b = arg

U -IL1L2 ZPP

(Equation 35)

EQUATION1792 V1 EN

where

is the UL1L2 voltage

EQUATION1800 V1 EN

ZRevPP

is the positive sequence impedance setting for phase-to-phase fault in reverse direction

220
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IL1L2jX

Ucomp1 = UL1L2 - IL1L2 ZPP


IL1L2 ZPP

U
Ucomp2 = U = IFZF=UL1L2
IL1L2R

- IL1L2 Z RevPP
en07000110.vsd
IEC07000110 V1 EN

Figure 121:

Simplified offset mho characteristic and voltage vectors for phase


L1-to-L2 fault.

Operation occurs if 90270.


Offset mho, forward direction
When forward direction has been selected for the offset mho, an extra criteria
beside the one for offset mho (90<<270) is introduced, that is the angle between
the voltage and the current must lie between the blinders in second quadrant and
fourth quadrant. See figure 122. Operation occurs if 90270 and
ArgDirArgNegRes.
where

ArgDir

is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.

ArgNegRes

is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.

is calculated according to equation 35

The directional information is brought to the mho distance measurement from the
mho directional element as binary coded information to the input DIRCND. See
Directional impedance element for mho characteristic (ZDMRDIR) for information
about the mho directional element.

221
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IL1L2jX

ZPP

UL1L2

ArgNegRes

IL1L2
ArgDir

en07000111.vsd
IEC07000111 V1 EN

Figure 122:

Simplified offset mho characteristic in forward direction for phase


L1-to-L2 fault

Offset mho, reverse direction


The operation area for offset mho in reverse direction is according to figure 123.
The operation area in second quadrant is ArgNegRes+180.
Operation occurs if 90270 and 180 - ArgDir ArgNegRes + 180
The is derived according to equation 35 for the mho circle and is the angle
between the voltage and current.

222
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X
ZPP

ArgNegRes

IL1L2

ArgDir

UL1L2

ZRevPP
en06000469.eps
IEC06000469 V1 EN

Figure 123:

Operation characteristic for reverse phase L1-to-L2 fault

Phase-to-earth fault
Mho
The measuring of earth faults uses earth-return compensation applied in a
conventional way. The compensation voltage is derived by considering the
influence from the earth-return path.
For an earth fault in phase L1, the compensation voltage Ucomp can be derived, as
shown in figure 124.

Ucomp = U pol - I L1 Z loop


(Equation 36)

EQUATION1793 V1 EN

where
Upol

is the polarizing voltage (memorized UL1 for Phase L1-to- earth fault)

Zloop

is the loop impedance, which in general terms can be expressed as

Z1+ZN = Z 1 1 + KN
EQUATION1799 V1 EN

)
(Equation 37)

Table continues on next page

223
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

where
Z1

is the positive sequence impedance of the line (Ohm/phase)

KN

is the zero-sequence compensator factor

The angle between the Ucomp and the polarize voltage Upol for a L1-to-earth
fault is
b = arg [UL1 -(IL1 +3I0 KN ) ZPE ] - arg( Upol)
(Equation 38)

GUID-A9492CDF-D3B7-4DC5-8E06-6638BEE2540B V1 EN

where
UL1

is the phase voltage in faulty phase L1

IL1

is the phase current in faulty phase L1

IA

is the phase current in faulty phase A

3I0

is the zero-sequence current in faulty phase L1

Z0-Z1
3 Z1

KN
EQUATION1593 V1 EN

EQUATION1594 V1 EN

the setting parameter for the zero sequence compensation consisting of the
magnitude KN and the angle KNAng.
Upol

is the 100% of positive sequence memorized voltage UL1

Vpol

is the 100% of positive sequence memorized voltage VA

IL1X
IL1ZN

Ucomp

IL1 Zloop
IL1ZPE
Upol
f
IL1 (Ref)

IL1R

en06000472_2.vsd
IEC06000472 V2 EN

Figure 124:

Simplified offset mho characteristic and vector diagram for phase


L1-to-earth fault

224
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Operation occurs if 90270.


Offset mho
The characteristic for offset mho at earth fault is a circle containing the two vectors
from the origin ZPE and ZRevPE where ZPE and ZrevPE are the setting reach for
the positive sequence impedance in forward respective reverse direction. The
vector ZPE in the impedance plane has the settable angle AngZPE and the angle for
ZRevPP is AngZPE+180.
The condition for operation at phase-to-earth fault is that the angle between the
two compensated voltages Ucomp1 and Ucomp2 is greater or equal to 90 see
figure 125. The angle will be 90 for fault location on the boundary of the circle.
The angle for L1-to-earth fault can be defined as

UL1-(- IL1 Z Re vPE )

b = arg

UL1- IL1L ZPE

(Equation 41)

EQUATION1802 V1 EN

U L1

is the phase L1 voltage

EQUATION1
805 V1 EN

IL1L 2 jX

U comp1 = UL1 - I L1 ZPE

IL1 ZPE

UL1

U comp2 = UL1 - (-IL1 ZRevPE)


IL1L2 R

- I L1 Z Re vPe
en 06000465.vsd
IEC06000465 V1 EN

Figure 125:

Simplified offset mho characteristic and voltage vector for phase L1to-L2 fault

Operation occurs if 90270.


225
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Offset mho, forward direction


In the same way as for phase-to-phase fault, selection of forward direction of offset
mho will introduce an extra criterion for operation. Beside the basic criteria for
offset mho according to equation 41 and 90270, also the criteria that the angle
between the voltage and the current must lie between the blinders in second and
fourth quadrant. See figure 126. Operation occurs if 90270 and
ArgDirArgNegRes.
where

ArgDir

is the setting parameter for directional line in fourth quadrant in the directional element,
ZDMRDIR.

ArgNegRes

is the setting parameter for directional line in second quadrant in the directional element,
ZDMRDIR.

is calculated according to equation 41

IL1 jX

UL1

ArgNegRes

IL1R

IL1
ArgDir

en 06000466.vsd
IEC06000466 V1 EN

Figure 126:

Simplified characteristic for offset mho in forward direction for L1-toearth fault

Offset mho, reverse direction


In the same way as for offset in forward direction, the selection of offset mho in
reverse direction will introduce an extra criterion for operation compare to the
normal offset mho. The extra is that the angle between the fault voltage and the
fault current shall lie between the blinders in second and fourth quadrant. The
operation area in second quadrant is limited by the blinder defined as 180 -ArgDir
and in fourth quadrant ArgNegRes+180, see figure 127.
The conditions for operation of offset mho in reverse direction for L1-to-earth fault
is 90270 and 180-ArgdirArgNegRes+180.
226
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The is derived according to equation 41 for the offset mho circle and is the
angle between the voltage and current.
X
ZPE

ArgNegRes

IL
1
ArgDir

UL1
ZRevPE

en06000470.eps
IEC06000470 V1 EN

Figure 127:

6.4.2.5

Simplified characteristic for offset mho in reverse direction for L1-toearth fault

Simplified logic diagrams


Distance protection zones
The design of the distance protection zones are presented for all measuring loops:
phase-to-earth as well as phase-to-phase.
Phase-to-earth related signals are designated by L1N, L2N and L3N. The phase-tophase signals are designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described


above.
Group functional input signal (STCND), as presented in figure 128.

One type of function block, ZMHPDIS are used in the IED for zone 1 - 5.
227
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FMPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FMPSPDIS function output signal
STCNDPHS.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filters out the
relevant signals depending on the setting of the parameter DirMode. Input signal
DIRCND must be configured to the STDIRCND output signal on ZDMRDIR
function.
OffsetMhoDir=
Non-directional

AND

AND

DirMode=Offset
STCND

T
F

AND

AND
LoadEnchMode=
On/Off
LDCND

T
F

True

AND

Release

DIRCND
OffsetMhoDir=
Forward/Reverse
DirMode=
Forward/Reverse

AND

BLKZ
BLOCK

OR

IEC11000216-1-en.vsd
IEC11000216 V1 EN

Figure 128:

Simplified logic for release start signal

When load encroachment mode is switched on (LoadEnchMode=On) then start


signal STCND is also checked against LDCND signal.
Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 128.
Composition of the phase start signals is presented in figure 83.

228
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Release

STL1N
STL2N
STL3N

STPE

OR

AND

STL1

OR
AND
AND

STL2

OR
STL1L2
STL2L3

AND
AND
STL3

OR
STL3L1

AND

OR

OR

START

STPP

IEC11000217-1-en.vsd
IEC11000217 V1 EN

Figure 129:

Composition of starting signals

Tripping conditions for the distance protection zone one are symbolically presented
in figure 85.

229
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Timer tPP=On
AND

STPP

tPP
t
OR

Timer tPE=On
AND

STPE

tPE
t

15ms
AND

BLKTRIP

TRIP

STL1

AND

TRL1

STL2

AND

TRL2

STL3

AND

TRL3

IEC11000218-1-en.vsd
IEC11000218 V1 EN

Figure 130:

6.4.3

Tripping logic for the distance protection zone

Function block
ZMHPDIS
I3P*
U3P*
CURR_INP*
VOLT_INP*
POL_VOLT*
BLOCK
BLKZ
BLKZMTD
BLKHSIR
BLKTRIP
BLKPE
BLKPP
DIRCND
STCND
LDCND

TRIP
TRL1
TRL2
TRL3
TRPE
TRPP
START
STL1
STL2
STL3
STPE
STPP

IEC06000423_2_en.vsd
IEC06000423 V2 EN

Figure 131:

ZMHPDIS function block

230
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.4.4

Input and output signals


Table 118:
Name

ZMHPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Connection for current sample signals

U3P

GROUP
SIGNAL

Connection for voltage sample signals

CURR_INP

GROUP
SIGNAL

Connection for current signals

VOLT_INP

GROUP
SIGNAL

Connection for voltage signals

POL_VOLT

GROUP
SIGNAL

Connection for polarizing voltage

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Block due to fuse failure

BLKZMTD

BOOLEAN

Block signal for blocking of time domaine function

BLKHSIR

BOOLEAN

Blocks time domain function at high SIR

BLKTRIP

BOOLEAN

Blocks all operate output signals

BLKPE

BOOLEAN

Blocks phase-to-earth operation

BLKPP

BOOLEAN

Blocks phase-to-phase operation

DIRCND

INTEGER

External directional condition

STCND

INTEGER

External start condition (loop enabler)

LDCND

INTEGER

External load condition (loop enabler)

Table 119:
Name

ZMHPDIS Output signals


Type

Description

TRIP

BOOLEAN

Trip General

TRL1

BOOLEAN

Trip phase L1

TRL2

BOOLEAN

Trip phase L2

TRL3

BOOLEAN

Trip phase L3

TRPE

BOOLEAN

Trip phase-to-earth

TRPP

BOOLEAN

Trip phase-to-phase

START

BOOLEAN

Start General

STL1

BOOLEAN

Start phase L1

STL2

BOOLEAN

Start phase L2

STL3

BOOLEAN

Start phase L3

STPE

BOOLEAN

Start phase-to-earth

STPP

BOOLEAN

Start phase-to-phase

231
Technical reference manual

Section 6
Impedance protection
6.4.5
Table 120:
Name

1MRK 505 222-UEN B

Setting parameters
ZMHPDIS Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off/On

IBase

1 - 99999

3000

Base current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

DirMode

Off
Offset
Forward
Reverse

Forward

Direction mode

LoadEncMode

Off
On

Off

Load encroachment mode Off/On

ReachMode

Overreach
Underreach

Overreach

Reach mode Over/Underreach

OpModePE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

ZPE

0.005 - 3000.000

ohm/p

0.001

30.000

Positive sequence impedance setting for


Phase-Earth loop

ZAngPE

10 - 90

Deg

80

Angle for positive sequence line


impedance for Phase-Earth loop

KN

0.00 - 3.00

0.01

0.80

Magnitud of earth return compensation


factor KN

KNAng

-180 - 180

Deg

-15

Angle for earth return compensation


factor KN

ZRevPE

0.005 - 3000.000

ohm/p

0.001

30.000

Reverse reach of the phase to earth


loop(magnitude)

tPE

0.000 - 60.000

0.001

0.000

Delay time for operation of phase to


earth elements

IMinOpPE

10 - 30

%IB

20

Minimum operation phase to earth current

OpModePP

Off
On

On

Operation mode Off / On of PhasePhase loops

ZPP

0.005 - 3000.000

ohm/p

0.001

30.000

Impedance setting reach for phase to


phase elements

ZAngPP

10 - 90

Deg

85

Angle for positive sequence line


impedance for Phase-Phase elements

ZRevPP

0.005 - 3000.000

ohm/p

0.001

30.000

Reverse reach of the phase to phase


loop(magnitude)

tPP

0.000 - 60.000

0.001

0.000

Delay time for operation of phase to phase

IMinOpPP

10 - 30

%IB

20

Minimum operation phase to phase


current

232
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 121:

ZMHPDIS Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

OffsetMhoDir

Non-directional
Forward
Reverse

Non-directional

Direction mode for offset mho

OpModetPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

OpModetPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-ph

6.4.6

Technical data
Table 122:

ZMHPDIS technical data

Function

Range or value

Accuracy

Number of zones with selectable


directions

Max 5 with selectable direction

Minimum operate current

(1030)% of IBase

Positive sequence impedance,


phase-to-earth loop

(0.0053000.000) W/phase

Positive sequence impedance


angle, phase-to-earth loop

(1090) degrees

Reverse reach, phase-to-earth


loop (Magnitude)

(0.0053000.000) /phase

2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85
degrees

Magnitude of earth return


compensation factor KN

(0.003.00)

Angle for earth compensation


factor KN

(-180180) degrees

Dynamic overreach

<5% at 85 degrees measured


with CVTs and 0.5<SIR<30

Timers

(0.000-60.000) s

0.5% 10 ms

Operate time

20 ms typically (with static


outputs)

Reset ratio

105% typically

Reset time

30 ms typically

233
Technical reference manual

Section 6
Impedance protection

6.5

1MRK 505 222-UEN B

Full-scheme distance protection, quadrilateral for


earth faults ZMMPDIS, ZMMAPDIS
Function description

IEC 61850
identification

Fullscheme distance protection,


quadrilateral for earth faults (zone 1)

IEC 60617
identification

ZMMPDIS

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

Fullscheme distance protection,


quadrilateral for earth faults (zone 2-5)

ZMMAPDIS

21

S00346 V1 EN

6.5.1

Introduction
The line distance protection is a , up to five zone protection with three fault loops
for phase-to-earth fault for each of the independent zones. Individual settings for
each zone resistive and reactive reach give flexibility for use on overhead lines and
cables of different types and lengths.
The Full-scheme distance protection, quadrilateral for earth faults functions
ZMMDPIS and ZMMAPDIS have functionality for load encroachment, which
increases the possibility to detect high resistive faults on heavily loaded lines , see
figure 75.
X
Forward
operation

R
Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 132:

Typical quadrilateral distance protection zone with Phase selection,


quadrilateral characteristic with settable angle function FRPSPDIS
activated

234
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone1 at
load exporting end at phase to earth faults on heavily loaded power lines.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together
with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines.

6.5.2

Principle of operation

6.5.2.1

Full scheme measurement


The different fault loops within the IED are operating in parallel in the same
principle as a full scheme measurement.
Figure 133 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones l.
L1-N

L2-N

L3-N

Zone 1

L1-N

L2-N

L3-N

Zone 2

L1-N

L2-N

L3-N

Zone 3

L1-N

L2-N

L3-N

Zone 4

L1-N

L2-N

L3-N

Zone 5

en07000080.vsd
IEC07000080 V1 EN

Figure 133:

6.5.2.2

The different measuring loops at line-earth fault and phase-phase


fault.

Impedance characteristic
The distance measuring zone include three impedance measuring loops; one fault
loop for each phase.
The distance measuring zone will essentially operate according to the nondirectional impedance characteristics presented in figure 134. The characteristic is
illustrated with the full loop reach.

235
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (Ohm/loop)

R1PE+Rn
RFPE

RFPE

X1PE+Xn

jN
RFPE

Xn =

X0PE-X1PE
3

Rn =

R0PE-R1PE
3

jN

R (Ohm/loop)

RFPE

X1PE+Xn

RFPE

RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN

Figure 134:

Characteristic for the phase-to-earth measuring loops, ohm/loop


domain.

The fault loop reach may also be presented as in figure 135.


UL1

ILn

R1 + j X1

Phase-to-earth
fault in phase L1

Phase-to-earth
element

RFPE
(Arc + tower
resistance)
0
IN

(R0-R1)/3 +
j (X0-X1)/3 )

en06000412.vsd

IEC06000412 V1 EN

Figure 135:

Fault loop model

236
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The R1 and jX1 in figure 135 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE is presented in order to convey
the fault resistance reach.
The zone may be set to operate in Non-directional, Forward, Off or Reverse
direction through the setting OperationDir. The result from respective set value is
illustrated in figure 136. It may be convenient to once again mention that the
impedance reach is symmetric, in the sense that it is conform for forward and
reverse direction. Therefore, all reach settings apply to both directions.
X

Non-directional

Forward

Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 136:

6.5.2.3

Directional operating modes of the distance measuring zone

Minimum operating current


The operation of the distance measuring zone is blocked if the magnitude of input
currents fall below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, that is, residual current 3I0.
Both current limits IMinOpPE and IMinOpIN are automatically
reduced to 75% of regular set values if the zone is set to operate in
reverse direction, that is, OperationDir=Reverse.

237
Technical reference manual

Section 6
Impedance protection
6.5.2.4

1MRK 505 222-UEN B

Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits.
Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3).
The calculation of the apparant impedances at phase-to-earth fault follow equation
42
The earth return compensation applies in a conventional manner.
U L1
Z app = -----------------------------I L1 + I N KN
(Equation 42)

EQUATION1223 V1 EN

Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN

KN =

is defined as:

Z0 - Z1
3 Z1

EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0

is setting of the resistive zero sequence reach

X0

is setting of the reactive zero sequence reach

R1

is setting of the resistive positive sequence reach

X1

is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and
reactance X.
The formula given in equation 42 is only valid for no loaded radial feeder
applications. When load is considered in the case of single line-to-earth fault,

238
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

conventional distance protection might overreach at exporting end and underreach


at importing end. IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 43,
X Di
U = R i + ------ ----w 0 Dt
EQUATION1224 V1 EN

(Equation 43)

in complex notation, or:


X D Re ( I )
Re ( U ) = R Re ( I ) + ------ -----------------w0
Dt
EQUATION354 V1 EN

(Equation 44)

X DIm ( I )
Im ( U ) = R Im ( I ) + ------ ----------------w0
Dt
EQUATION355 V1 EN

(Equation 45)

with
w0 = 2 p f 0
EQUATION356 V1 EN

(Equation 46)

where:
Re

designates the real component of current and voltage,

Im

designates the imaginary component of current and voltage and

f0

designates the rated system frequency

The algorithm calculates Rm measured resistance from the equation for the real
value of the voltage and substitute it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:
Im ( U ) DRe ( I ) Re ( U ) D Im ( I )
R m = -----------------------------------------------------------------------------------DRe ( I ) Im ( I ) D Im ( I ) Re ( I )
EQUATION357 V1 EN

(Equation 47)

239
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Re ( U ) Im ( I ) Im ( U ) Re ( I )
Xm = w 0 Dt ------------------------------------------------------------------------------DRe ( I ) Im ( I ) DIm ( I ) Re ( I )
(Equation 48)

EQUATION358 V1 EN

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and
reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.5.2.5

Directional lines
The evaluation of the directionality takes place in the Directional impedance
element for mho characteristic ZDMRDIR function. Equation 49 is used to classify
that the fault is in forward direction for line-to-earth fault.

- ArgDir < arg

0.85 U1L1 + 0.15 U1L1M


I L1

< ArgNeg Re s
(Equation 49)

EQUATION1617 V1 EN

where:

ArgDir

is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and

ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 137.
U1L1

is positive sequence phase voltage in phase L1

U1L1M

is positive sequence memorized phase voltage in phase L1

IL1

is phase current in phase L1

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (see figure 137) and it should not be changed unless system
studies have shown the necessity.
ZDMRDIR gives a binary coded signal on the output STDIRCND depending on
the evaluation where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1
adds 4 etc.

240
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ArgNegRes

ArgDir

en05000722.vsd
IEC05000722 V1 EN

Figure 137:

Setting angles for discrimination of forward and reverse fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.
The polarizing voltage is available as long as the positive-sequence voltage
exceeds 5% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
After 100 ms, the following occurs:

If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

241
Technical reference manual

Section 6
Impedance protection
6.5.2.6

1MRK 505 222-UEN B

Simplified logic diagrams


Distance protection zones

The design of distance protection zone 1 is presented for all measuring: phase-toearth loops.
Phase-to-earth related signals are designated by LnE, where n represents the
corresponding phase number (L1E, L2E, and L3E).
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described


above.
Group functional input signal (STCND), as presented in figure 138.

The STCND input signal represents a connection of six different integer values
from the phase selection function within the IED, which are converted within the
zone measuring function into corresponding boolean expressions for each
condition separately. It is connected to the Phase selection with load
enchroachment, quadrilateral characteristic (FDPSPDIS) function output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filter out the
relevant signals on the DIRCND input depending on the setting of the parameter
OperationDir. It shall be configured to the DIRCND output on the Directional
impedance element for mho characteristic (ZDMRDIR) function.

242
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STCND

L1N

AND

STNDL1N

L2N

AND

STNDL2N

L3N

AND

STNDL3N
STNDPE

OR

OR
VTSZ
BLOCK

AND

OR

STND
BLK
en06000408.vsd

IEC06000408 V1 EN

Figure 138:

Conditioning by a group functional input signal STCND

Composition of the phase starting signals for a case, when the zone operates in a nondirectional mode, is presented in figure 139.
STNDL1N
AND

15 ms
t

STL1

AND

15 ms
t

STL2

AND

15 ms
t

STL3

AND

15 ms
t

START

STNDL2N
STNDL3N

OR
BLK

en06000409.vsd
IEC06000409 V1 EN

Figure 139:

Composition of starting signals in non-directional operating mode

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, see figure 140.

243
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STNDL1N
DIRL1N

AND
OR

STNDL2N
DIRL2N
STNDL3N
DIRL3N

STZMPE.

&

AND

AND

&

15 ms
t

STL1

&

15 ms
t

STL2

&

15 ms
t

STL3

&

15 ms
t

START

BLK
OR

en07000081.vsd
IEC07000081 V1 EN

Figure 140:

Composition of starting signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 141.

Timer tPE=On
STZMPE

AND

tPE
t
15ms

TRIP

BLKTR

AND

STL1

AND

TRL1

STL2

AND

TRL2

STL3

AND

TRL3

en07000082.vsd
IEC07000082 V1 EN

Figure 141:

Tripping logic for the distance protection zone one

244
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.5.3

Function block
ZMMPDIS
I3P*
U3P*
BLOCK
BLKZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC06000454-2-en.vsd

IEC06000454 V2 EN

Figure 142:

ZMMPDIS function block

ZMMAPDIS
I3P*
U3P*
BLOCK
BLKZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC09000947-1-en.vsd

IEC09000947 V1 EN

Figure 143:

6.5.4

ZMMAPDIS function block

Input and output signals


Table 123:
Name

ZMMPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 124:
Name

ZMMPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

Table continues on next page

245
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Name

Type
BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

Table 125:

ZMMAPDIS Input signals

Name

Type

Name

Description

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

ZMMAPDIS Output signals

Name

Table 127:

Default

I3P

Table 126:

6.5.5

Description

START

Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

Setting parameters
ZMMPDIS Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

Table continues on next page


246
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1

0.50 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach

R1

0.10 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for zone


characteristic angle

X0

0.50 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach

R0

0.50 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle

RFPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPE

10 - 30

%IB

20

Minimum operate phase current for


Phase-Earth loops

IMinOpIN

5 - 30

%IB

Minimum operate residual current for


Phase-Earth loops

Table 128:

ZMMAPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach

R1

0.10 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for zone


characteristic angle

X0

0.50 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach

R0

0.50 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle

RFPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPE

10 - 30

%IB

20

Minimum operate phase current for


Phase-Earth loops

247
Technical reference manual

Section 6
Impedance protection
6.5.6

1MRK 505 222-UEN B

Technical data
Table 129:

ZMMPDIS technical data

Function

6.6

Range or value

Accuracy

Number of zones

Max 5 with selectable direction

Minimum operate current

(10-30)% of IBase

Positive sequence reactance

(0.50-3000.00) W/phase

Positive sequence resistance

(0.10-1000.00) /phase

Zero sequence reactance

(0.50-9000.00) /phase

Zero sequence resistance

(0.50-3000.00) /phase

Fault resistance, Ph-E

(1.00-9000.00) W/loop

2.0% static accuracy


2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85
degrees

Dynamic overreach

<5% at 85 degrees measured


with CCVTs and 0.5<SIR<30

Impedance zone timers

(0.000-60.000) s

0.5% 10 ms

Operate time

24 ms typically

Reset ratio

105% typically

Reset time

30 ms typically

Directional impedance element for mho


characteristic and additional distance protection
directional function for earth faults ZDMRDIR,
ZDARDIR
Function description
Directional impedance element for mho
characteristic

IEC 61850
identification

IEC 60617
identification

ZDMRDIR

ANSI/IEEE C37.2
device number
21D

S00346 V1 EN

Function description
Additional distance protection
directional function for earth faults

IEC 61850
identification

IEC 60617
identification

ZDARDIR

ANSI/IEEE C37.2
device number
-

S00346 V1 EN

248
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.6.1

Introduction
The phase-to-earth impedance elements can be optionally supervised by a phase
unselective directional function based on symmetrical components.

6.6.2

Principle of operation

6.6.2.1

Directional impedance element for mho characteristic ZDMRDIR


The evaluation of the directionality takes place in Directional impedance element
for mho characteristic (ZDMRDIR). Equation 50 and equation 51 are used to
classify that the fault is in the forward direction for phase-to-earth fault and phaseto-phase fault respectively.

- ArgDir < arg

0.85 U1L1 + 0.15 U1L1M


I L1

< ArgNeg Re s
(Equation 50)

EQUATION1617 V1 EN

- ArgDir < arg

0.85 U1L1L 2 + 0.15 U1L1L 2 M


I L1L 2

< ArgNeg Re s
(Equation 51)

EQUATION1619 V1 EN

Where:
ArgDir

Setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees)

ArgNegRes

Setting for the upper boundary of the forward directional characteristic, by default set to
115 degrees, see figure 144 for mho characteristics.

U1L1

Positive sequence phase voltage in phase L1

U1L1M

Positive sequence memorized phase voltage in phase L1

IL1

Phase current in phase L1

U1L1L2

Voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M

Memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2

Current difference between phase L1 and L2 (L2 lagging L1)

The default settings for ArgDir and ArgNegRes are 15 (= -15) and 115 degrees
respectively (see figure 144) and they should not be changed unless system studies
show the necessity.
If one sets DirEvalType to Comparator (which is recommended when using the
mho characteristic) then the directional lines are computed by means of a comparatortype calculation, meaning that the directional lines are based on mho-circles (of
infinite radius). The default setting value Impedance otherwise means that the

249
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

directional lines are implemented based on an impedance calculation equivalent to


the one used for the quadrilateral impedance characteristics.
When Directional impedance element for mho characteristic
(ZDMRDIR) is used together with Fullscheme distance protection,
mho characteristic (ZMHPDIS) the following settings for
parameter DirEvalType is vital:

alternative Comparator is strongly recommended


alternative Imp/Comp should generally not be used
alternative Impedance should not be used. This altenative is
intended for use together with Distance protection zone,
quadrilateral characteristic (ZMQPDIS)

X
Zset reach point

ArgNegRes

-ArgDir

-Zs
en06000416.vsd
IEC06000416 V1 EN

Figure 144:

Setting angles for discrimination of forward fault

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.
The polarizing voltage is available as long as the positive-sequence voltage
exceeds 5% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100ms or until the positive sequence voltage is
restored. After 100ms, the following occurs:

250
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

If the current is still above the set value of the minimum operating current the
condition seals in.

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.

If the current decreases below the minimum operating value, no directional


indications will be given until the positive sequence voltage exceeds 10% of
its rated value.

The Directional impedance element for mho characteristic (ZDMRDIR) function


has the following output signals:
The STDIRCND output provides an integer signal that depends on the evaluation
and is derived from a binary coded signal as follows:
bit 11
(2048)

bit 10
(1024)

bit 9
(512)

bit 8
(256)

bit 7
(128)

bit 6
(64)

STRVL3L1=
1

STRVL2L3=
1

STRVL1L2=
1

STRVL3N=1

STRVL2N=1

STRVL1N=1

bit 5
(32)

bit 4
(16)

bit 3
(8)

bit 2
(4)

bit 1
(2)

bit 0
(1)

STFWL3L1=
1

STFWL2L3=
1

STFWL1L2=
1

STFWL3N=1

STFWL2N=1

STFWL1N=1

The STFW output is a logical signal with value 1 or 0. It is made up as an ORfunction of all the forward starting conditions, that is, STFWL1N, STFWL2N,
STFWL3N, STFWL1L2, STFWL2L3 and STFWL3L1. The STRV output is
similar to the STFW output, the only difference being that it is made up as an ORfunction of all the reverse starting conditions, that is, STRVL1N, STRVL2N,
STRVL3N, STRVL1L2, STRVL2L3 and STRVL3L1.
Values for the following parameters are calculated, and may be viewed as service
values:

resistance phase L1
reactance phase L1
resistance phase L2
reactance phase L2
resistance phase L3
reactance phase L3
direction phase L1
direction phase L2
direction phase L3

251
Technical reference manual

Section 6
Impedance protection
6.6.2.2

1MRK 505 222-UEN B

Additional distance protection directional function for earth faults


ZDARDIR
A Mho element needs a polarizing voltage for its operation. The positive-sequence
memory-polarized elements are generally preferred. The benefits include:

The greatest amount of expansion for improved resistive coverage. These


elements always expand back to the source.
Memory action for all fault types. This is very important for close-in threephase faults.
A common polarizing reference for all six distance-measuring loops. This is
important for single-pole tripping, during a pole-open period.

There are however some situations that can cause security problems like reverse
phase to phase faults and double phase-to-earth faults during high load periods. To
solve these, additional directional element is used.
For phase-to-earth faults, directional elements using sequence components are very
reliable for directional discrimination. The directional element can be based on one
of following types of polarization:

Zero-sequence voltage
Negative-sequence voltage
Zero-sequence current

These additional directional criteria are evaluated in the Additional distance


protection directional function for earth faults (ZDARDIR).
Zero-sequence voltage polarization is utilizing the phase relation between the zerosequence voltage and the zero-sequence current at the location of the protection.
The measurement principle is illustrated in figure 145.

252
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

- 3U 0
AngleOp
AngleRCA

3I 0
en06000417.vsd
IEC06000417 V1 EN

Figure 145:

Principle for zero-sequence voltage polarized additional directional


element

Negative-sequence voltage polarization is utilizing the phase relation between the


negative-sequence voltage and the negative-sequence current at the location of the
protection.
Zero-sequence current polarization is utilizing the phase relation between the zerosequence current at the location of the protection and some reference zerosequence current, for example, the current in the neutral of a power transformer.
The principle of zero-sequence voltage polarization with zero-sequence current
compensation is described in figure 146. The same also applies for the negativesequence function.

Z0 SA

I0

I0

Z0 SB

Z0 Line

Charac te ris tic


ang le

U0

U0

K*I0
U0 + K*I0
IF
en06000418.vsd

IEC06000418 V1 EN

Figure 146:

Principle for zero sequence compensation

Note that the sequence based additional directional element cannot give per phase
information about direction to fault. This is why it is an AND-function with the
normal directional element that works on a per phase base. The release signals are
per phase and to have a release of a measuring element in a specific phase both the
additional directional element, and the normal directional element, for that phase
must indicate correct direction.
253
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Normal
directional
element
L1N, L2N, L3N

AND

Release of distance
measuring element
L1N, L2N, L3N

Additional
directional
element

AND per
phase
en06000419.vsd

IEC06000419 V1 EN

Figure 147:

6.6.3

Earth distance element directional supervision

Function block
ZDMRDIR
I3P*
U3P*

DIR_CURR
DIR_VOLT
DIR_POL
STFW
STRV
STDIRCND
IEC06000422_2_en.vsd

IEC06000422 V2 EN

Figure 148:

ZDMRDIR function block

ZDARDIR
I3P*
U3P*
I3PPOL*
DIRCND

STFWPE
STRVPE
DIREFCND

IEC06000425-2-en.vsd
IEC06000425 V2 EN

Figure 149:

6.6.4

ZDARDIR function block

Input and output signals


Table 130:
Name

ZDMRDIR Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

group connection for current abs 1

U3P

GROUP
SIGNAL

group connection for voltage abs 1

254
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 131:

ZDMRDIR Output signals

Name

Type

DIR_CURR

GROUP SIGNAL

Group connection

DIR_VOLT

GROUP SIGNAL

Group connection

DIR_POL

GROUP SIGNAL

Group connection

STFW

BOOLEAN

Start in forward direction

STRV

BOOLEAN

Start in reverse direction

STDIRCND

INTEGER

Binary coded directional information per


measuring loop

Table 132:

ZDARDIR Input signals

Name

Type

Description

GROUP
SIGNAL

Current signals

U3P

GROUP
SIGNAL

Voltage signals

I3PPOL

GROUP
SIGNAL

Polarisation current signals

DIRCND

INTEGER

Binary coded directional signal

ZDARDIR Output signals

Name

Table 134:

Default

I3P

Table 133:

6.6.5

Description

Type

Description

STFWPE

BOOLEAN

Forward start signal from phase-to-ground


directional element

STRVPE

BOOLEAN

Reverse start signal from phase-to-ground


directional element

DIREFCND

INTEGER

Start direction Binary coded

Setting parameters
ZDMRDIR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

0.05

400.00

Base setting for voltage level

DirEvalType

Impedance
Comparator
Imp/Comp

Comparator

Directional evaluation mode Impedance /


Comparator

ArgNegRes

90 - 175

Deg

115

Angle of blinder in second quadrant for


forward direction

ArgDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for


forward direction

IMinOpPE

5 - 30

%IB

Minimum operate phase current for


Phase-Earth loops

IMinOpPP

5 - 30

%IB

10

Minimum operate delta current for PhasePhase loops


255

Technical reference manual

Section 6
Impedance protection

Table 135:
Name

1MRK 505 222-UEN B

ZDARDIR Group settings (basic)


Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current values

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level in kV

PolMode

-3U0
-U2
IPol
Dual
-3U0Comp
-U2comp

-3U0

Polarization quantity for opt dir function


for P-E faults

AngleRCA

-90 - 90

Deg

75

Characteristic relay angle (= MTA or


base angle)

I>

1 - 200

%IB

Minimum operation current in % of IBase

UPol>

1 - 100

%UB

Minimum polarizing voltage in % of UBase

IPol>

5 - 100

%IB

10

Minimum polarizing current in % of IBase

Table 136:
Name

ZDARDIR Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AngleOp

90 - 180

Deg

160

Operation sector angle

Kmag

0.50 - 3000.00

ohm

0.01

40.00

Boost-factor in -U0comp and -U2comp


polarization

6.7

Mho impedance supervision logic ZSMGAPC


Function description
Mho Impedance supervision logic

6.7.1

IEC 61850
identification
ZSMGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The Mho impedance supervision logic (ZSMGAPC) includes features for fault
inception detection and high SIR detection. It also includes the functionality for
loss of potential logic as well as for the pilot channel blocking scheme.
ZSMGAPC can mainly be decomposed in two different parts:
1.
2.

A fault inception detection logic


High SIR detection logic

256
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.7.2

Principle of operation

6.7.2.1

Fault inception detection


The aim for the fault inception detector is to detect quickly that a fault has occurred
on the system.
The fault inception detection detects instantaneous changes in any phase currents
or zero sequence current in combination with a change in the corresponding phase
voltage or zero sequence voltage. If the change of any phase current and
corresponding phase voltage or 3U0 and 3I0 exceeds the settings DeltaI and
DeltaU respectively. Delta3U0 and Delta3I0 and the input signal BLOCK is not
activated, the output signal FLTDET is activated indicating that a system fault has
occurred.
If the setting PilotMode is set to On in blocking scheme and the fault inception
function has detected a system fault, a block signal BLKCHST will be issued and
send to remote end in order to block the overreaching zones. Different criteria has
to be fulfilled for sending the BLKCHST signal:
1.
2.
3.

The setting PilotMode has to be set to On


The breaker has to be closed, that is, the input signal CBOPEN has to be
deactivated
A reverse fault should have been detected while the carrier send signal is not
blocked, that is, input signal REVSTART is activated and input signal
BLOCKCS is not activated

Or
A fault inception is detected
If it is later detected that it was an internal fault that made the function issue the
BLKCHST signal, the function will issue a CHSTOP signal to unblock the remote
end. The criteria that have to be fulfilled for this are:
1.
2.
3.

The function has to be in pilot mode, that is, the setting PilotMode has to be
set to On
The carrier send signal should be blocked, that is, input signal BLOCKCS is
On and,
A reverse fault should not have been detected while the carrier send signal was
not blocked, that is, input signals REVSTART and BLOCKCS is not activated.

ZSMGAPC function has a built in loss of voltage detection based on the evaluation
of the change in phase voltage or the change in zero sequence voltage (3U0). It
operates if the change in phase voltages exceeds the setting DeltaU or 3U0 exceeds
the setting Delta3U0.
If loss of voltage is detected, but not a fault inception, the distance protection
function will be blocked. This is also the case if a fuse failure is detected by the
257
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

external fuse failure function and activate the input FUSEFAIL. Those blocks are
generated by activating the output BLKZ, which shall be connected to the input
BLKZ on the distance Mho function block.
During fault inception a lot of transients will be developed which in turn might
cause the distance function to overreach. The Mho supervision logic (ZSMGAPC)
will increase the filtering during the most transient period of the fault. This is done
by activating the output BLKZMD, which shall be connected to the input
BLKZMTD on mho distance function block.

High SIR detection

High SIR values increases the likelihood that CVT will introduce a prolonged and
distorted transient, increasing the risk for overreach of the distance function.
The SIR function calculates the SIR value as the source impedance divided by the
setting Zreach and activates the output signal HSIR if the calculated value for any
of the six basic shunt faults exceed the setting SIRLevel. The HSIR signal is
intended to block the delta based mho impedance function.

6.7.3

Function block
ZSMGAPC
I3P*
BLKZMTD
U3P*
BLKCHST
BLOCK
CHSTOP
REVSTART
HSIR
BLOCKCS
CBOPEN
IEC06000426-2-en.vsd
IEC06000426 V2 EN

Figure 150:

6.7.4

ZSMGAPC function block

Input and output signals


Table 137:
Name

ZSMGAPC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase current samples and DFT magnitude

U3P

GROUP
SIGNAL

Three phase phase-neutral voltage samples and


DFT magnitude

BLOCK

BOOLEAN

Block of the function

REVSTART

BOOLEAN

Indication of reverse start

BLOCKCS

BOOLEAN

Blocks the blocking carrier signal to remote end

CBOPEN

BOOLEAN

Indicates that the breaker is open

258
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 138:

ZSMGAPC Output signals

Name

6.7.5
Table 139:

Type

Description

BLKZMTD

BOOLEAN

Block signal for blocking of time domained mho

BLKCHST

BOOLEAN

Blocking signal to remote end to block


overreaching zone

CHSTOP

BOOLEAN

Stops the blocking signal to remote end

HSIR

BOOLEAN

Indication of source impedance ratio above set limit

Setting parameters
ZSMGAPC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base value for current measurement

UBase

0.05 - 2000.00

kV

0.05

400.00

Base value for voltage measurement

PilotMode

Off
On

Off

Pilot mode Off/On

Zreach

0.1 - 3000.0

ohm

0.1

38.0

Line impedance

IMinOp

10 - 30

%IB

20

Minimum operating current for SIR


measurement

Table 140:

ZSMGAPC Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

DeltaI

0 - 200

%IB

10

Current change level in %IB for fault


inception detection

Delta3I0

0 - 200

%IB

10

Zero seq current change level in % of IB

DeltaU

0 - 100

%UB

Voltage change level in %UB for fault


inception detection

Delta3U0

0 - 100

%UB

Zero seq voltage change level in % of UB

SIRLevel

5 - 15

10

Settable level for source impedance ratio

6.8

Faulty phase identification with load encroachment


FMPSPDIS
Function description
Faulty phase identification with load
encroachment for mho

IEC 61850
identification

IEC 60617
identification

FMPSPDIS

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

259
Technical reference manual

Section 6
Impedance protection
6.8.1

1MRK 505 222-UEN B

Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement
of the power system is reduced, for example difficulties to get permission to build
new power lines. The ability to accurate and reliable classifying the different types
of fault so that single phase tripping and autoreclosing can be used plays an
important roll in this matter.
The phase selection function is design to accurately select the proper fault loop(s)
in the distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in
some cases interfere with the distance protection zone reach and cause unwanted
operation. Therefore the function has a built in algorithm for load encroachment,
which gives the possibility to enlarge the resistive setting of the measuring zones
without interfering with the load.
The output signals from the phase selection function produce important
information about faulty phase(s), which can be used for fault analysis as well.

6.8.2

Principle of operation

6.8.2.1

The phase selection function


Faulty phase identification with load encroachment for mho (FMPSPDIS) function
can be decomposed into six different parts:
1.
2.
3.
4.
5.
6.

A high speed delta based current phase selector


A high speed delta based voltage phase selector
A symmetrical components based phase selector
Fault evaluation and selection logic
A load encroachment logic
A blinder logic

The total function can be blocked by activating the input BLOCK.

Delta based current and voltages

The delta based fault detection function uses adaptive technique and is based on
patent US4409636.
The aim of the delta based phase selector is to provide very fast and reliable phase
selection for releasing of tripping from the high speed Mho measuring element and
is essential to Directional Comparison Blocking scheme (DCB), which uses Power
Line Carrier (PLC) communication system across the protected line.
The current and voltage samples for each phase passes through a notch filter that
filters out the fundamental components. Under steady state load conditions or when
no fault is present, the output of the filter is zero or close to zero. When a fault
260
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

occurs, currents and voltages change resulting in sudden changes in the currents
and voltages resulting in non-fundamental waveforms being introduced on the line.
At this point the notch filter produces significant non-zero output. The filter output
is processed by the delta function. The algorithm uses an adaptive relationship
between phases to determine if a fault has occurred, and determines the faulty phases.
The current and voltage delta based phase selector gives a real output signal if the
following criterion is fulfilled (only phase L1 shown):
Max(UL1,UL2,UL3)>DeltaUMinOp
Max(IL1,IL2,IL3)>DeltaIMinOp
where:
UL1, UL2 and UL3

are the voltage change between sample t and sample t-1

DeltaUMinOp and DeltaIMinOp

are the minimum harmonic level settings for the voltage and current
filters to decide that a fault has occurred. A slow evolving fault may not
produce sufficient harmonics to detect the fault; however, in such a
case speed is no longer the issue and the sequence components
phase selector will operate.

The delta voltages ULn and delta current ILn (n prefix for phase order) are the
voltage and current between sample t and sample t-1.
The delta phase selector employs adaptive techniques to determine the fault type.
The logic determines the fault type by summing up all phase values and dividing
by the largest value. Both voltages and currents are filtered out and evaluated. The
condition for fault type classification for the voltages and currents can be expressed
as:

FaulType =

( UL1, UL2, UL3)


MAX ( UL1, UL 2, UL3)
(Equation 52)

EQUATION1621 V2 EN

FaulType =

( IL1, IL2, IL3)


MAX ( IL1, IL 2, IL3)
(Equation 53)

EQUATION1622 V2 EN

The value of FaultType for different shunt faults are as follows:


Under ideal conditions: (Patent pending)
Single phase-to-earth;

FaultType=1

Phase-to-phase fault

FaultType=2

Three-phase fault;

FaultType=3

261
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The output signal is 1 for single phase-to-earth fault, 2 for phase-to-phase fault and
3 for three-phase fault. At this point the filter does not know if earth was involved
or not.
Typically there are induced harmonics in the non-faulted lines that will affect the
result. This method allows for a significant tolerance in the evaluation of FaultType
over its entire range.
When a single phase-to-earth fault has been detected, the logic determines the
largest quantity, and asserts that phase. If phase-to-phase fault is detected, the two
largest phase quantities will be detected and asserted as outputs.
The faults detected by the delta based phase selector are coordinated in a separate
block. Different phases of faults may be detected at slightly different times due to
differences in the angles of incidence of fault on the wave shape. Therefore the
output is forced to wait a certain time by means of a timer. If the timer expires, and
a fault is detected in one phase only, the fault is deemed as phase-to-earth. This
way a premature single phase-to-earth fault detection is not released for a phase-tophase fault. If, however, earth current is detected before the timer expires, the phaseto-earth fault is released sooner.
If another phase picks up during the time delay, the wait time is reduced by a
certain amount. Each detection of either earth-to-phase or additional phases further
reduce the initial time delay and allow the delta phase selector output to be faster.
There is no time delay, if for example, all three phases are faulty.
The delta function is released if the input DELTAREL is activated at the same time
as input DELTABLK is not activated. Activating the DELTABLK input will block
the delta function. The release signal has an internal pulse timer of 100 ms. When
the DELTAREL signal has disappeared the delta logic is reset. In order not to get
too abrupt change, the reset is decayed in pre-defined steps.

Symmetrical component based phase selector

The symmetrical component phase selector uses preprocessed calculated sequence


voltages and currents as inputs. It also uses sampled values of the phase currents.
All the symmetrical quantities mentioned further in this section are with reference
to phase L1.
The function is made up of four main parts:
A

Detection of the presence of earth fault

A phase-to-phase logic block based on U1/U2 angle relationship

A phase-to-earth component based on patent US5390067 where the angle relationships


between U2/I0 and U2/U1 is evaluated to determine earth fault or phase- to-phase to earth fault

Logic for detection of three-phase fault

262
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Presence of earth-fault detection


This detection of earth fault is performed in two levels, first by evaluation of the
magnitude of zero sequence current, and secondly by the evaluation of the zero and
negative sequence voltage. It is a complement to the earth-fault signal built-in in
the Symmetrical component based phase selector.
The complementary based zero-sequence current function evaluates the presence of
earth fault by calculating the 3I0 and comparing the result with the setting
parameter INRelPE. The output signal is used to release the earth-fault loop. It is a
complement to the earth-fault signal built-in in the sequence based phase selector.
The condition for releasing the phase-to-earth loop is as follows:
The output from this detection is used to release the earth-fault loop.
|3I0|>maxIph: INRelPE
where:
|3I0|

is the magnitude of the zero sequence current 3I0

maxIph

is the maximum magnitude of the phase currents

INRelPE

is a setting parameter for the relation between the magnitude of 3I0 and the
maximum phase current

The earth-fault loop is also released if the evaluation of the zero sequence current
by the main sequence function meets the following conditions:
|3I0|>IBase 0.5
|3I0|>maxIph INRelPE
where:
maxIph

is the maximal current magnitude found in any of the three phases

INRelPE

is the setting of 3I0 limit for release of phase-to-earth measuring loop in % of IBase

IBase

is the global setting of the base current (A)

In systems where the source impedance for zero sequence is high the change of
zero sequence current may not be significant and the above detection may fail. In
those cases the detection enters the second level, with evaluation of zero and
negative sequence voltage. The release of the earth-fault loops can then be
achieved if all of the following conditions are fulfilled:
|3U0|>|U2| 0.5
|3U0|>|U1| 0.2
|U1|> UBase 0.2/(3)
and
263
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

3I0> 0.1 IBase


or
3I0<maxIph INRelPE
where:
3U0

is the magnitude of the zero sequence voltage

U2

is the magnitude of the negative sequence voltage at the relay measuring point of
phase L1

k5

is design parameter

ILmax

is the maximal phase current

IMinOp

is the setting of minimum operate phase current in % of IBase

Phase-to-phase fault detection


The detection of phase-to-phase fault is performed by evaluation of the angle
difference between the sequence voltages U2 and U1.

UL3

60

L3-L1 sector
180

UL2
L2-L3 sector

U1L1 (Ref)

L1-L2 sector
UL1
300
en06000383.vsd
IEC06000383 V1 EN

Figure 151:

Definition of fault sectors for phase-to-phase fault

The phase-to-phase loop for the faulty phases will be determined if the angle
between the sequence voltages U2 and U1 lies within the sector defined according
to figure 151 and the following conditions are fulfilled:
|U1|>U1MinOP
|U2|>U2MinOp
where:

U1MinOP and U2MinOp

are the setting parameters for positive sequence and negative sequence
minimum operate voltages

264
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The positive sequence voltage U1L1 in figure 151 above is reference.


If there is a three-phase fault, there will not be any release of the individual phase
signals, even if the general conditions for U2 and U1 are fulfilled.
Phase-to-earth and phase-to-phase-to-earth-fault detection
The detection of phase-to-earth and phase-to-phase-to-earth fault (US patent
5390067) is based on two conditions:
1. Angle relationship between U2 and I0
2. Angle relationship between U2 and U1
The condition 1 determines faulty phase at single phase-to-earth fault by determine
the argument between U2 and I0.

80

L2-E sector

200

L3-E sector

L1-E sector
320

IEC06000384-2-en.vsd
IEC06000384 V2 EN

Figure 152:

Condition 1: Definition of faulty phase sector as angle between U2


and I0

The angle is calculated in a directional function block and gives the angle in
radians as input to the U2 and I0 function block. The input angle is released only if
the fault is in forward direction. This is done by the directional element. The fault
is classified as forward direction if the angle between U0 and I0 lies between 20 to
200 degrees, see figure 153.

265
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Forward

200

20

Reverse

en06000385.vsd

IEC06000385 V1 EN

Figure 153:

Directional element used to release the measured angle between


Uo and I0

The input radians are summarized with an offset angle and the result evaluated. If
the angle is within the boundaries for a specific sector, the phase indication for that
sector will be active see figure 152. Only one sector signal is allowed to be
activated at the same time.
The sector function for condition 1 has an internal release signal which is active if
the main sequence function has classified the angle between U0 and I0 as valid. The
following conditions must be fulfilled for activating the release signals:
|U2|>U2MinOp
|3I0|> 0.05 IBase
|3I0|>maxIph INRelPE
where:
U2 and IN

are the magnitude of the negative sequence voltage and zerosequence current (3I0)

U2MinOp

is the setting parameter for minimum operating negative sequence


voltage

maxIph

is the maximum phase current

INRelPE

is the setting parameter for 3I0 limit for releasing phase-to-earth loop

The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.
The condition 2 looks at the angle relationship between the negative sequence
voltage U2 and the positive sequence voltage U1. Since this is a phase-to-phase
voltage relationship, there is no need for shifting phases if the fault is in reverse
direction. A phase shift is introduced so that the fault sectors will have the same
angle boarders as for condition 1. If the calculated angle between U2 and U1 lies
266
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

within one sector, the corresponding phase for that sector will be activated. The
condition 2 is released if both the following conditions are fulfilled:
|U2|>U2MinOp
|U1|>U1MinOP
where:
|U1| and |U2|

are the magnitude of the positive and negative sequence voltages.

U1MinOP and U2MinOp

are the setting parameters for positive sequence and negative sequence
minimum operating voltages.

140

L3-E sector
20

L1-E sector

U1L1
(Ref)

L2-E sector

260

IEC06000413_2_en.vsd

IEC06000413 V2 EN

Figure 154:

Condition 2: U2 and U1 angle relationship

If both conditions are true and there is sector match, the fault is deemed as single
phase-to-earth. If the sectors, however, do not match the fault is determined to be
the complement of the second condition, that is, a phase-to-phase-to- earth fault.
Condition 1 and

Condition 2

Fault type

L3-E

L3-E

L3-E

L2-E

L1-E

L2-L3-E

The sequence phase selector is blocked when earth is not involved or if a threephase fault is detected.
Three-phase fault detection
Unless it has been categorized as a single or two-phase fault, the function classifies
it as a three-phase fault if the following conditions are fulfilled:
|U1|<U1Level

267
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

and
|I1|>I1LowLevel
or
|I1|>IMaxLoad
where:
|U1| and |I1|

are the positive sequence voltage and current magnitude

U1Level ,
I1LowLevel

are the setting of limits for positive sequence voltage and current

IMaxLoad

is the setting of the maximum load current

The output signal for detection of three-phase fault is only released if not earth
fault and phase-to-phase fault in the main sequence function is detected.
The conditions for not detecting earth fault are the inverse of equation 5 to 10.
The condition for not detecting phase-to-phase faults is determined by three
conditions. Each of them gives condition for not detecting phase-to-phase fault.
Those are:
1:
earth fault is detected
or
|3I0IN|> 0.05 IBase
and
|3I0IN|>maxIph INRelPE
2:
phase-to-earth and phase-to-phase faults are not fulfilled
and
maxIph<0.1 IBase
and
|I2|<0.1 maxIph
3:
|3I0IN|>maxIph INBlockPP
or
|I2|<maxIph I2maxIL

where:
maxIph

is the maximum of the phase currents IL1, IL2 and IL3

INRelPE

is the setting parameter for 3I0 limit for release of phase-to-earth fault loops

Table continues on next page


268
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

|I2|

is the magnitude of the negative sequence current

I2ILmax

is the setting parameter for the relation between negative sequence current
to the maximum phase current in percent of IBase

INBlockPP

is the setting parameter for 3I0 limit for blocking phase to phase measuring
loops

Fault evaluation and selection logic

The phase selection logic has an evaluation procedure that can be simplified
according to figure 155. Only phase L1 is shown in the figure. If the internal signal
3 Phase fault is activated, all four outputs START, STL1, STL2 and STL3 gets
activated.

DeltaIL1

DeltaUL1
Sequence based
function

L1L2 fault

a
OR

a>b
then c=a
else c=b

a<b
then c=b
else c=a

FaultPriority
Adaptive release
dependent on result
from Delta logic

OR

L1N fault
3 Phase fault
STL1

&

IL1Valid
BLOCK

IEC06000386-2-en.vsd
IEC06000386 V2 EN

Figure 155:

Simplified diagram for fault evaluation, phase L1

Load encroachment logic

Each of the six measuring loops has its own load (encroachment) characteristic
based on the corresponding loop impedance. The load encroachment functionality
is always activated in faulty phase identification with load encroachment for mho
(FMPSPDIS) function but the influence on the zone measurement can be switched
On/Offin the respective impedance measuring function.
The outline of the characteristic is presented in figure 156. As illustrated, the
resistive reach in forward and reverse direction and the angle of the sector is the
same in all four quadrants. The reach for the phase selector will be reduced by the
load encroachment function, as shown in figure 156.

269
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Blinder
Blinder provides a mean to discriminate high load from a fault. The operating
characteristic is illustrated in figure 156. There are six individual measuring loops
with the blinder functionality. Three phase-to-earth loops which estimate the
impedance according to
Zn = Uph / Iph
and three phase-to-phase loops according to
Zph-ph = Uph-ph / Iph-ph
The start operations from respective loop are binary coded into one word and
provides an output signal STCNDPLE.
X

jX

Operation area

Operation area

RLd
ArgLd

ArgLd

R
R

ArgLd

ArgLd
RLd

Operation area

No operation area

No operation area

en06000414.vsd
IEC06000414 V1 EN

Figure 156:

Influence on the characteristic by load encroachment logic

Outputs

The output of the sequence components based phase selector and the delta logic
phase selector activates the output signals STL1, STL2 and STL3. If an earth fault
is detected the signal STPE gets activated.
The phase selector also gives binary coded signals that are connected to the zone
measuring element for opening the correct measuring loop(s). This is done by the
signal STCNDPHS. If only one phase is started (L1, L2 or L3), the corresponding
phase-to- element is enabled. STPE is expected to be made available for two-phase
and three-phase faults for the correct output to be selected. The fault loop is
indicated by one of the decimal numbers below.
The output STCNDPHS provides release information from the phase selection part
only. STCNDLE provides release information from the load encroachment part
only. STCNDPLE provides release information from the phase selection part and
270
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

the load encroachment part combined, that is, both parts have to issue a release at
the same time (this signal is normally not used in the zone measuring element). In
these signals, each fault type has an associated value, which represents the
corresponding zone measuring loop to be released. The values are presented in
table 140.
0=

no faulted phases

1=

L1E

2=

L2E

3=

L3E

4=

-L1L2E

5=

-L2L3E

6=

-L3L1E

7=

-L1L2L3E

8=

-L1L2

9=

-L2L3

10=

-L3L1

11=

L1L2L3

An additional logic is applied to handle the cases when phase-to-earth outputs are
to be asserted when the earth input G is not asserted.
The output signal STCNDPLE is activated when the load encroachment is operating.
STCNDPLE is connected to the input STCND for selected quadrilateral impedance
measuring zones to be blocked. The signal must be connected to the input LDCND
for selected mho impedance measuring zones .
The load encroachment at the measuring zone must be activated to
release the blocking from the load encroachment function.

6.8.3

Function block
FMPSPDIS
I3P*
U3P*
BLOCK
ZSTART
TR3PH
1POLEAR

STL1
STL2
STL3
STPE
STCNDPHS
STCNDPLE
STCNDLE
START
IEC06000429-2-en.vsd

IEC06000429 V2 EN

Figure 157:

FMPSPDIS function block

271
Technical reference manual

Section 6
Impedance protection
6.8.4

1MRK 505 222-UEN B

Input and output signals


Table 141:

FMPSPDIS Input signals

Name

Type
GROUP
SIGNAL

Group signal for current

U3P

GROUP
SIGNAL

Group signal for voltage

BLOCK

BOOLEAN

Block of function

ZSTART

BOOLEAN

Start from underimpdeance function

TR3PH

BOOLEAN

Three phase tripping initiated

1POLEAR

BOOLEAN

Single pole autoreclosing in progress

FMPSPDIS Output signals

Name

Table 143:
Name

Description

I3P

Table 142:

6.8.5

Default

Type

Description

STL1

BOOLEAN

Fault detected in phase L1

STL2

BOOLEAN

Fault detected in phase L2

STL3

BOOLEAN

Fault detected in phase L3

STPE

BOOLEAN

Earth fault detected

STCNDPHS

INTEGER

Binary coded starts from phase selection

STCNDPLE

INTEGER

Binary coded starts from ph sel with load


encroachment

STCNDLE

INTEGER

Binary coded starts from load encroachment only

START

BOOLEAN

Indicates that something has started

Setting parameters
FMPSPDIS Group settings (basic)
Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

IMaxLoad

10 - 5000

%IB

200

Maximum load for identification of three


phase fault in % of IBase

RLd

1.00 - 3000.00

ohm/p

0.01

80.00

Load encroachment resistive reach in


ohm/phase

ArgLd

5 - 70

Deg

20

Load encroachment inclination of load


angular sector

272
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 144:

FMPSPDIS Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

DeltaIMinOp

5 - 100

%IB

10

Delta current level in % of IBase

DeltaUMinOp

5 - 100

%UB

20

Delta voltage level in % of UBase

U1Level

5 - 100

%UB

80

Pos seq voltage limit for identification of 3ph fault

I1LowLevel

5 - 200

%IB

10

Pos seq current level for identification of


3-ph fault in % of IBase

U1MinOp

5 - 100

%UB

20

Minimum operate positive sequence


voltage for ph sel

U2MinOp

1 - 100

%UB

Minimum operate negative sequence


voltage for ph sel

INRelPE

10 - 100

%IB

20

3I0 limit for release ph-e measuring


loops in % of max phase current

INBlockPP

10 - 100

%IB

40

3I0 limit for blocking phase-to-phase


measuring loops in % of max phase
current

6.8.6

Technical data
Table 145:

FMPSPDIS technical data

Function

6.9

Range or value

Accuracy

Minimum operate current

(5-30)% of IBase

1.0% of Ir

Load encroachment criteria:


Load resistance, forward and
reverse

(0.53000) W/phase
(570) degrees

2.0% static accuracy


Conditions:
Voltage range: (0.11.1) x Ur
Current range: (0.530) x Ir
Angle: at 0 degrees and 85 degrees

Distance protection zone, quadrilateral


characteristic, separate settings ZMRPDIS,
ZMRAPDIS and ZDRDIR
Function description

IEC 61850
identification

Distance protection zone, quadrilateral


characteristic, separate settings (zone
1)

ZMRPDIS

Distance protection zone, quadrilateral


characteristic, separate settings (zone
2-5)

ZMRAPDIS

IEC 60617
identification

ANSI/IEEE C37.2
device number
21

S00346 V1 EN

21

S00346 V1 EN

273
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Function description

IEC 61850
identification

Directional impedance quadrilateral

6.9.1

ZDRDIR

IEC 60617
identification
Z<->

ANSI/IEEE C37.2
device number
21D

Introduction
The line distance protection is up to five zone full scheme protection with three
fault loops for phase-to-phase faults and three fault loops for phase-to-earth fault
for each of the independent zones. Individual settings for each zone in resistive and
reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.
Mho alternative quadrilateral characteristic is available.
ZMRPDIS together with Phase selection, quadrilateral characteristic with settable
angle FRPSPDIS has functionality for load encroachment, which increases the
possibility to detect high resistive faults on heavily loaded lines, as shown in figure
75.
X
Forward
operation

R
Reverse
operation

en05000034.vsd
IEC05000034 V1 EN

Figure 158:

Typical quadrilateral distance protection zone with Phase selection,


quadrilateral characteristic with settable angle function FRPSPDIS
activated

The independent measurement of impedance for each fault loop together with a
sensitive and reliable built-in phase selection makes the function suitable in
applications with single pole tripping and autoreclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at
load exporting end at phase-to-earth faults on heavily loaded power lines.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together

274
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

with different communication schemes, for the protection of power lines and cables
in complex network configurations, such as parallel lines, multi-terminal lines and
so on.

6.9.2

Principle of operation

6.9.2.1

Full scheme measurement


The execution of the different fault loops within the IED are of full scheme type,
which means that each fault loop for phase-to-earth faults and phase-to-phase faults
for forward and reverse faults are executed in parallel.
Figure 76 presents an outline of the different measuring loops for up to five,
impedance-measuring zones. There are 3 to 5 zones depending on product type and
variant.
L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 1

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 2

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 3

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 4

L1-N

L2-N

L3-N

L1-L2

L2-L3

L3-L1

Zone 5

en05000458.vsd
IEC05000458 V1 EN

Figure 159:

The different measuring loops at phase-to-earth fault and phase-tophase fault.

The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one
independent distance protection IED with six measuring elements.

6.9.2.2

Impedance characteristic
The distance measuring zone includes six impedance measuring loops; three
intended for phase-to-earth faults, and three intended for phase-to-phase as well as,
three-phase faults.
The distance measuring zone will essentially operate according to the nondirectional impedance characteristics presented in figure 77 and figure 78. The phaseto-earth characteristic is illustrated with the full loop reach while the phase-tophase characteristic presents the per phase reach.

275
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (Ohm/loop)

R1PE+Rn
RFPE

RFPE

X1PE+Xn

jN
RFPE

Xn =

X0PE-X1PE
3

Rn =

R0PE-R1PE
3

jN

R (Ohm/loop)

RFPE

X1PE+Xn

RFPE

RFPE
en08000280-2-en.vsd

R1PE+Rn
IEC08000280 V1 EN

Figure 160:

Characteristic for phase-to-earth measuring , ohm/loop domain

276
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RFPP

(Ohm/phase)

R1PP

RFPP

X 0 PE - X 1RVPE
XNRV =XX00PE
PG- 1RVPG
X3
1XRVPE
XNRV
=
XNRV =
33
X
0
PE
--1X
11FWPE
X
0
PE
X 0 PG X
XFWPE
FWPG
XNFW
XNFW
XNFW===
3 33

X1PP

R (Ohm/phase)
RFPP

RFPP

X1PP

RFPP
2

R1PP

RFPP
2

en07000062.vsd

IEC07000062 V2 EN

Figure 161:

Characteristic for phase-to-phase measuring

The fault loop reach with respect to each fault type may also be presented as in
figure 79. Note in particular the difference in definition regarding the (fault)
resistive reach for phase-to-phase faults and three-phase faults.

277
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

UL1

IL1

R1 + j X1

Phase-to-earth
fault in phase L1

Phase-to-earth
element

RFPE
(Arc + tower
resistance)
0

Phase-to-phase
fault in phase
L1-L2

UL1

IN

(R0-R1)/3 +
j (X0-X1)/3 )

IL1

R1 + j X1

Phase-to-phase
element L1-L2
RFPP

IL2

(Arc resistance)

UL2
R1 + j X1

UL1
Three-phase
fault

IL1

R1 + j X1

0.5RFPP

R1 + j X1

0.5RFPP

Phase-to-phase
element L1-L3

IL3
UL3
IEC08000282-2-en.vsd

IEC08000282 V2 EN

Figure 162:

Fault loop model

The R1 and jX1 in figure 79 represents the positive sequence impedance from the
measuring point to the fault location. The settings RFPE and RFPP are the
eventual fault resistances in the faulty place.
Regarding the illustration of three-phase fault in figure 79, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
The zone can be set to operate in Non-directional, Forward or Reverse direction
through the setting OperationDir. The result from respective set value is illustrated
in figure 80. The impedance reach is symmetric, in the sense that it conforms for
forward and reverse direction. Therefore, all reach settings apply to both directions.

278
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Non-directional

Forward

Reverse

en05000182.vsd
IEC05000182 V1 EN

Figure 163:

6.9.2.3

Directional operating modes of the distance measuring zones

Minimum operating current


The operation of Distance measuring zones, quadrilateral characteristic
(ZMRPDIS) is blocked if the magnitude of input currents fall below certain
threshold values.
The phase-to-earth loop Ln is blocked if ILn < IMinOpPE.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops can be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three-phase currents, that is residual current 3I0.
The phase-to-phase loop LmLn is blocked if ILmLn< IMinOpPP.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
All three current limits IMinOpPE, IMinOpIN and IMinOpPP are
automatically reduced to 75% of regular set values if the zone is set
to operate in reverse direction, that is OperationDir=Reverse

6.9.2.4

Measuring principles
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The

279
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

apparent impedances at phase-to-phase faults follow equation 4 (example for a


phase L1 to phase L2 fault).
UL1 UL2
Zapp = ------------------------I L1 IL2
(Equation 54)

EQUATION1222 V1 EN

Here U and I represent the corresponding voltage and current phasors in the
respective phase Ln (n = 1, 2, 3)
The earth return compensation applies in a conventional manner to phase-to-earth
faults (example for a phase L1 to earth fault) according to equation 5.
U L1
Z app = -----------------------------I L1 + I N KN
(Equation 55)

EQUATION1223 V1 EN

Where:
UL1, IL1 and IN

are the phase voltage, phase current and residual current present to the IED

KN is defined as:

KN =

Z0 - Z1
3 Z1

EQUATION 2105 V1 EN

Z 0 = R0 + jX 0
EQUATION2106 V1 EN

Z1 = R1 + jX 1
EQUATION2107 V1 EN

Where
R0

is setting of the resistive zero sequence reach

X0

is setting of the reactive zero sequence reach

R1

is setting of the resistive positive sequence reach

X1

is setting of the reactive positive sequence reach

Here IN is a phasor of the residual current in IED point. This results in the same
reach along the line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and
reactance X.

280
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The formula given in equation 5 is only valid for radial feeder application without
load. When load is considered in the case of single phase-to-earth fault,
conventional distance protection might overreach at exporting end and underreach
at importing end. The IED has an adaptive load compensation which increases the
security in such applications.
Measuring elements receive current and voltage information from the A/D
converter. The check sums are calculated and compared, and the information is
distributed into memory locations. For each of the six supervised fault loops,
sampled values of voltage (U), current (I), and changes in current between samples
(DI) are brought from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related
to the loop impedance according to equation 6,
X Di
U = R i + ------ ----w 0 Dt
EQUATION1224 V1 EN

(Equation 56)

in complex notation, or:


X D Re ( I )
Re ( U ) = R Re ( I ) + ------ -----------------w0
Dt
EQUATION354 V1 EN

(Equation 57)

X DIm ( I )
Im ( U ) = R Im ( I ) + ------ ----------------w0
Dt
EQUATION355 V1 EN

(Equation 58)

with
w0 = 2 p f 0
EQUATION356 V1 EN

(Equation 59)

where:
Re

designates the real component of current and voltage,

Im

designates the imaginary component of current and voltage and

f0

designates the rated system frequency

The algorithm calculates Rmmeasured resistance from the equation for the real
value of the voltage and substitutes it in the equation for the imaginary part. The
equation for the Xm measured reactance can then be solved. The final result is
equal to:

281
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Im ( U ) DRe ( I ) Re ( U ) D Im ( I )
R m = -----------------------------------------------------------------------------------DRe ( I ) Im ( I ) D Im ( I ) Re ( I )
(Equation 60)

EQUATION357 V1 EN

Re ( U ) Im ( I ) Im ( U ) Re ( I )
Xm = w 0 Dt ------------------------------------------------------------------------------DRe ( I ) Im ( I ) DIm ( I ) Re ( I )
(Equation 61)

EQUATION358 V1 EN

The calculated Rm and Xm values are updated each sample and compared with the
set zone reach. The adaptive tripping counter counts the number of permissive
tripping results. This effectively removes any influence of errors introduced by the
capacitive voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and
reverse directions, and in all six fault loops. Positive sequence voltage and a phase
locked positive sequence memory voltage are used as a reference. This ensures
unlimited directional sensitivity for faults close to the IED point.

6.9.2.5

Directional impedance element for quadrilateral characteristics


The evaluation of the directionality takes place in Directional impedance
quadrilateral function ZDRDIR. Equation 12 and equation 13 are used to classify
that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault.
- ArgDir < arg

0.8 U 1L1 + 0.2 U 1L1 M


I L1

< ArgNeg Re s
(Equation 62)

EQUATION725 V2 EN

For the L1-L2 element, the equation in forward direction is according to.
- ArgDir < arg

0.8 U 1L1 L 2 + 0.2 U 1L1 L 2 M


I L1 L 2

< ArgNeg Re s
(Equation 63)

EQUATION726 V2 EN

where:
ArgDir

is the setting for the lower boundary of the forward directional characteristic, by default
set to 15 (= -15 degrees) and

ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 81.
U1L1

is positive sequence phase voltage in phase L1

U1L1M

is positive sequence memorized phase voltage in phase L1

IL1

is phase current in phase L1

U1L1L2

is voltage difference between phase L1 and L2 (L2 lagging L1)

U1L1L2M

is memorized voltage difference between phase L1 and L2 (L2 lagging L1)

IL1L2

is current difference between phase L1 and L2 (L2 lagging L1)

282
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115
degrees respectively (as shown in figure 81). It should not be changed unless
system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the
output STDIRCND.
STDIR=

STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

ArgNegRes

ArgDir

en05000722.vsd
IEC05000722 V1 EN

Figure 164:

Setting angles for discrimination of forward and reverse fault in


Directional impedance quadrilateral function ZDRDIR

The reverse directional characteristic is equal to the forward characteristic rotated


by 180 degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds
5% of the set base voltage UBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
After 100ms the following occurs:
283
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set IED rated current IBase), the condition seals in.

6.9.2.6

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

Simplified logic diagrams


Distance protection zones

The design of the distance protection zones are presented for all measuring loops:
phase-to-earth as well as phase-to-phase.
Phase-to-earth related signals are designated by L1N, L2N and L3N.. The phase-tophase signals are designated by L1L2, L2L3, and L3L1.
Fulfillment of two different measuring conditions is necessary to obtain the one
logical signal for each separate measuring loop:

Zone measuring condition, which follows the operating equations described


above.
Group functional input signal (STCND), as presented in figure 82.

The STCND input signal represents a connection of six different integer values
from Phase selection with load encroachment, quadrilateral characteristic function
FRPSPDIS within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately.
Input signal STCND is connected to FRPSPDISfunction output STCNDZ.
The input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filter out the
relevant signals depending on the setting of the parameter OperationDir. It must be
configured to the STDIRCND output on directional function ZDRDIR function.

284
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IEC99000557-TIFF V1 EN

Figure 165:

Conditioning by a group functional input signal STCND, external


start condition

Composition of the phase start signals for a case, when the zone operates in a nondirectional mode, is presented in figure 83.

IEC00000488-TIFF V1 EN

Figure 166:

Composition of starting signals in non-directional operating mode


285

Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Results of the directional measurement enter the logic circuits, when the zone
operates in directional (forward or reverse) mode, as shown in figure 84.
STNDL1N
DIRL1N

AND
OR

STNDL2N
DIRL2N

AND

STNDL3N

OR

DIRL3N

AND

STNDL1L2
DIRL1L2

AND

STNDL2L3
DIRL2L3

AND

STNDL3L1
DIRL3L1

STZMPE.

AND

OR

OR

AND

15 ms
t

STL1

AND

15 ms
t

STL2

AND

15 ms
t

STL3

AND
OR

STZMPP

AND

BLK

OR

AND

15 ms
t

START

IEC09000888-1-en.vsd
IEC09000888 V1 EN

Figure 167:

Composition of start signals in directional operating mode

Tripping conditions for the distance protection zone one are symbolically presented
in figure 85.

286
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Timer tPP=On

tPP
t

AND

STZMPP

OR

Timer tPE=On
AND

STZMPE

tPE
t

AND
OR
AND

15ms

TRIP

BLKTR

AND

STL1

AND

TRL1

STL2

AND

TRL2

STL3

AND

TRL3

en00000490.vsd
IEC09000887 V1 EN

Figure 168:

6.9.3

Tripping logic for the distance protection zone

Function block
ZMRPDIS
I3P*
U3P*
BLOCK
BLKZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC08000248-1-en.vsd

IEC08000248 V1 EN

Figure 169:

ZMRPDIS function block

287
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ZMRAPDIS
I3P*
U3P*
BLOCK
BLKZ
BLKTR
STCND
DIRCND

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STND
IEC08000290_1_en.vsd

IEC08000290 V1 EN

Figure 170:

ZMRAPDIS function block


ZDRDIR

I3P*
U3P*

STDIRCND

IEC09000639-1-en.vsd
IEC09000639 V1 EN

6.9.4

Input and output signals


Table 146:
Name

ZMRPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 147:
Name

ZMRPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

288
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 148:
Name

ZMRAPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Blocks all output by fuse failure signal

BLKTR

BOOLEAN

Blocks all trip outputs

STCND

INTEGER

External start condition (loop enabler)

DIRCND

INTEGER

External directional condition

Table 149:
Name

ZMRAPDIS Output signals


Type

Description

TRIP

BOOLEAN

General Trip, issued from any phase or loop

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

General Start, issued from any phase or loop

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

STND

BOOLEAN

Non-directional start, issued from any phase or


loop

Table 150:

ZDRDIR Input signals

Name

Type

Default

Description

I3P

GROUP
SIGNAL

group connection for current abs 2

U3P

GROUP
SIGNAL

group connection for voltage abs 2

Table 151:
Name
STDIRCND

ZDRDIR Output signals


Type
INTEGER

Description
Binary coded directional information per
measuring loop

289
Technical reference manual

Section 6
Impedance protection
6.9.5
Table 152:
Name

1MRK 505 222-UEN B

Setting parameters
ZMRPDIS Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1PP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach PhPh

R1PP

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

RFPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

X1PE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach Ph-E

R1PE

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-E

X0PE

0.10 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-E

R0PE

0.01 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

IMinOpIN

5 - 1000

%IB

Minimum operate residual current for


Phase-Earth loops

290
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 153:

ZMRAPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage, i.e. rated voltage

OperationDir

Off
Non-directional
Forward
Reverse

Forward

Operation mode of directionality NonDir /


Forw / Rev

X1PP

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach PhPh

R1PP

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-Ph

RFPP

0.10 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach in ohm/loop, Ph-Ph

X1PE

0.10 - 3000.00

ohm/p

0.01

30.00

Positive sequence reactance reach Ph-E

R1PE

0.01 - 1000.00

ohm/p

0.01

5.00

Positive seq. resistance for characteristic


angle, Ph-E

X0PE

0.10 - 9000.00

ohm/p

0.01

100.00

Zero sequence reactance reach, Ph-E

R0PE

0.01 - 3000.00

ohm/p

0.01

15.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFPE

0.10 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach in ohm/loop, Ph-E

OperationPP

Off
On

On

Operation mode Off / On of PhasePhase loops

Timer tPP

Off
On

On

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-Ph

OperationPE

Off
On

On

Operation mode Off / On of Phase-Earth


loops

Timer tPE

Off
On

On

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

0.000

Time delay of trip, Ph-E

IMinOpPP

10 - 1000

%IB

20

Minimum operate delta current for PhasePhase loops

IMinOpPE

10 - 1000

%IB

20

Minimum operate phase current for


Phase-Earth loops

Table 154:

ZDRDIR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

IMinOpPP

5 - 30

%IB

10

Minimum operate delta current for PhasePhase loops

Table continues on next page

291
Technical reference manual

Section 6
Impedance protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

IMinOpPE

5 - 30

%IB

Minimum operate phase current for


Phase-Earth loops

ArgNegRes

90 - 175

Deg

115

Angle of blinder in second quadrant for


forward direction

ArgDir

5 - 45

Deg

15

Angle of blinder in fourth quadrant for


forward direction

6.9.6

Technical data
Table 155:

ZMRPDIS, ZMRAPDIS technical data

Function

6.10

Range or value

Accuracy

Number of zones

Max 5 with selectable


direction

Minimum operate residual


current, zone 1

(5-1000)% of IBase

Minimum operate current, phaseto-phase and phase-to-earth

(10-1000)% of IBase

Positive sequence reactance

(0.10-3000.00) /
phase

Positive sequence resistance

(0.01-1000.00) /
phase

Zero sequence reactance

(0.10-9000.00) /
phase

2.0% static accuracy


2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85 degrees

Zero sequence resistance

(0.01-3000.00) /
phase

Fault resistance, phase-to-earth

(0.10-9000.00) /loop

Fault resistance, phase-to-phase

(0.10-3000.00) /loop

Dynamic overreach

<5% at 85 degrees
measured with CVTs
and 0.5<SIR<30

Impedance zone timers

(0.000-60.000) s

0.5% 10 ms

Operate time

24 ms typically

Reset ratio

105% typically

Reset time

30 ms typically

Phase selection, quadrilateral characteristic with


settable angle FRPSPDIS
Function description
Phase selection, quadrilateral
characteristic with settable angle

IEC 61850
identification

IEC 60617
identification

FRPSPDIS

ANSI/IEEE C37.2
device number
21

Z<phs
SYMBOL-DD V1 EN

292
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.10.1

Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations, the rate of expansion and
reinforcement of the power system is reduced, for example, difficulties to get
permission to build new power lines. The ability to accurately and reliably classify
the different types of fault, so that single pole tripping and autoreclosing can be
used plays an important role in this matter. Phase selection, quadrilateral
characteristic with settable angle FRPSPDIS is designed to accurately select the
proper fault loop in the distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may make
fault resistance coverage difficult to achieve. Therefore, FRPSPDIS has a built-in
algorithm for load encroachment, which gives the possibility to enlarge the
resistive setting of both the phase selection and the measuring zones without
interfering with the load.
The extensive output signals from the phase selection gives also important
information about faulty phase(s) which can be used for fault analysis.
A current-based phase selection is also included. The measuring elements
continuously measure three phase currents and the residual current and, compare
them with the set values.

6.10.2

Principle of operation
The basic impedance algorithm for the operation of the phase selection measuring
elements is the same as for the distance zone measuring function. Phase selection,
quadrilateral characteristic with settable angle (FRPSPDIS) includes six impedance
measuring loops; three intended for phase-to-earth faults, and three intended for
phase-to-phase as well as for three-phase faults.
The difference, compared to the distance zone measuring function, is in the
combination of the measuring quantities (currents and voltages) for different types
of faults.
The characteristic is basically non-directional, but FRPSPDIS uses information
from the directional function ZDRDIR to discriminate whether the fault is in
forward or reverse direction.
The start condition STCNDZ is essentially based on the following criteria:

Residual current criteria, that is, separation of faults with and without earth
connection
Regular quadrilateral impedance characteristic
Load encroachment characteristics is always active but can be switched off by
selecting a high setting.

293
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The current start condition STCNDLE is based on the following criteria:

Residual current criteria


No quadrilateral impedance characteristic. The impedance reach outside the
load area is theoretically infinite. The practical reach, however, will be
determined by the minimum operating current limits.
Load encroachment characteristic is always active, but can be switched off by
selecting a high setting.

The STCNDLE output is non-directional. The directionality is determined by the


distance zones directional function ZDRDIR.
There are output from FRPSPDIS that indicate whether a start is in forward or
reverse direction or non-directional, for example STFWL1, STRVL1 and STNDL1.
These directional indications are based on the sector boundaries of the directional
function and the impedance setting of FRPSPDIS function. Their operating
characteristics are illustrated in figure 103.
X

Non-directional (ND)

Forward (FW)

Reverse (RV)
en08000286.vsd

IEC08000286 V1 EN

Figure 171:

Characteristics for non-directional, forward and reverse operation


of Phase selection, quadrilateral characteristic with settable angle
(FRPSPDIS)

The setting of the load encroachment function may influence the total operating
characteristic, for more information, refer to section "Load encroachment".
The input DIRCND contains binary coded information about the directional
coming from the directional function ZDRDIR. It shall be connected to the STDIR
output on ZDRDIR. This information is also transferred to the input DIRCND on
the distance measuring zones, that is, the ZMRPDIS block.
The code built up for the directionality is as follows:

294
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STDIR=

STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048

If the binary information is 1 then it will be considered that we have start in


forward direction in phase L1. If the binary code is 3 then we have start in forward
direction in phase L1 and L2 etc.
The STCNDZ or STCNDLE output contains, in a similar way as DIRCND, binary
coded information, in this case information about the condition for opening correct
fault loop in the distance measuring element. It shall be connected to the STCND
input on the ZMRPDIS distance measuring zones block.
The code built up for release of the measuring fault loops is as follows:
STCNDZ = L1N*1 + L2N*2 + L3N*4 + L1L2*8 + L2L3*16 + L3L1*32

6.10.2.1

Phase-to-earth fault
For a phase-to-earth fault, the measured impedance by FRPSPDIS is according to
equation 24.
Index PHS in images and equations reference settings for Phase
selection, quadrilateral characteristic with settable angle
(FRPSPDIS).

ZPHSn =

ULn
ILn

EQUATION1255 V1 EN

(Equation 64)

where:
n

corresponds to the particular phase (n=1, 2 or 3)

The characteristic for FRPSPDIS function at phase-to-earth fault is according to


figure 104. The characteristic has a settable angle for the resistive boundary in the
first quadrant of 70.
The resistance RN and reactance XN are the impedance in the earth-return path
defined according to equation 27 and equation 28.

295
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RN =

R 0 PE - R1PE
3

(Equation 65)

EQUATION 2125 V1 EN

RN =

R0 - R1
3
(Equation 65)

EQUATION1256 V1 EN

XN =

X 0 - X1
3
(Equation 66)

EQUATION1257 V1 EN

X (ohm/loop)
R1PE+RN
RFRvPE

RFFwPE

X1+XN
RFFwPE
R (Ohm/loop)

RFRvPE

X1+XN

RFFwPE

RFRvPE
R1PE+RN

IEC09000633-1-en.vsd
IEC09000633 V1 EN

Figure 172:

Characteristic of FRPSPDIS for phase to earth fault (directional


lines are drawn as "line-dot-dot-line")

Besides this, the 3I0 residual current must fulfil the conditions according to
equation 27 and equation 28.
3 I0 0.5 IMinOpPE
EQUATION2108 V1 EN

(Equation 67)

296
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

3 I0 INReleasePE
------------------------------------ Iphmax
100
(Equation 68)

EQUATION766 V1 EN

where:

IMinOpPE

is the minimum operation current for forward zones

INReleasePE is the setting for the minimum residual current needed to enable operation in the phaseto-earth fault loops (in %).
Iphmax

6.10.2.2

is the maximum phase current in any of three phases.

Phase-to-phase fault
For a phase-to-phase fault, the measured impedance by FRPSPDIS is according to
equation 29.
ZPHS =

ULm - ULn
-2 ILn

EQUATION1258 V1 EN

(Equation 69)

ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the
phase current in the lagging phase n.
The operation characteristic is shown in figure 105.

297
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (ohm/phase)
0.5FRvPP

R1PP 0.5RFFwPP

X1

0.5RFFwPP

R (ohm/phase)
0.5RFRvPP

0.5RFRvPP

R1PP

X1

0.5RFFwPP

IEC09000634-1-en.vsd

IEC09000634 V1 EN

Figure 173:

The operation characteristic for FRPSPDIS at phase-to-phase fault


(directional lines are drawn as "line-dot-dot-line")

In the same way as the condition for phase-to-earth fault, there are current
conditions that have to be fulfilled in order to release the phase-to-phase loop.
Those are according to equation 30 or equation 31.

3I 0 < IMinOpPE
(Equation 70)

EQUATION2109 V1 EN

3I 0 <

INBlockPP
Iph max
100
(Equation 71)

EQUATION2110 V1 EN

where:

IMinOpPE

is the minimum operation current for forward earth measuring loops,

INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and


Iphmax

is maximal magnitude of the phase currents.

298
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.10.2.3

Three-phase faults
The operation conditions for three-phase faults are the same as for phase-to-phase
fault, that is equation 29, equation 30 and equation 31 are used to release the
operation of the function.
However, the reach is expanded by a factor 2/3 (approximately 1.1547) in all
directions. At the same time the characteristic is rotated 30 degrees, counterclockwise. The characteristic is shown in figure 106.
X (ohm/phase)
4 X1PP
3

0.5RFFwPPK3
X1K3

30 deg

RFwPP

2
3

R (ohm/phase)
0.5RFRvPPK3
K3 = 2 / sqrt(3)

30 deg

IEC09000635-1-en.vsd
IEC09000635 V2 EN

Figure 174:

6.10.2.4

The characteristic of FRPSPDIS for three-phase fault (set angle 70)

Load encroachment
Each of the six measuring loops has its own load encroachment characteristic based
on the corresponding loop impedance. The load encroachment functionality is
always active, but can be switched off by selecting a high setting.

299
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The outline of the characteristic is presented in figure 108. As illustrated, the


resistive blinders are set individually in forward and reverse direction while the
angle of the sector is the same in all four quadrants.
X

RLdFw
ArgLd

ArgLd

ArgLd

RLdRv

ArgLd

IEC09000042-1-en.vsd
IEC09000042 V1 EN

Figure 175:

Characteristic of load encroachment function

The influence of load encroachment function on the operation characteristic is


dependent on the chosen operation mode of FRPSPDIS function. When output
signal STCNDZ is selected, the characteristic for FRPSPDIS (and also zone
measurement depending on settings) will be reduced by the load encroachment
characteristic, see figure 109.
When output signal STCNDI is selected, the operation characteristic will be as in
figure 108. The reach will in this case be limit by the minimum operation current
and the distance measuring zones.

300
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STCNDZ

STCNDLE
IEC10000099-1en.vsd

IEC10000099 V1 EN

Figure 176:

Difference in operating characteristic depending on operation


mode when load encroachment is activated

When FRPSPDIS is set to operate together with a distance measuring zone the
resultant operate characteristic could look like in figure 109. The figure shows a
distance measuring zone operating in forward direction. Thus, the operating area of
the zone together with the load encroachment is highlighted in black.

301
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X
"Phase selection"
"quadrilateral" zone
Distance measuring zone

Load encroachment
characteristic
R
Directional line

en05000673.vsd
IEC05000673 V1 EN

Figure 177:

Operating characteristic in forward direction when load


encroachment is activated

Figure 109 is valid for phase-to-earth. During a three-phase fault, or load, when the
quadrilateral phase-to-phase characteristic is subject to enlargement and rotation
the operate area is transformed according to figure 110. Notice in particular what
happens with the resistive blinders of the "phase selection" "quadrilateral" zone.
Due to the 30-degree rotation, the angle of the blinder in quadrant one is now 100
degrees instead of the original 70 degrees (if the angle setting is 70 degrees). The
blinder that is nominally located to quadrant four will at the same time tilt outwards
and increase the resistive reach around the R-axis. Consequently, it will be more or
less necessary to use the load encroachment characteristic in order to secure a
margin to the load impedance.

302
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

X (W /

phase)

Phase selection
Quadrilateral zone

Distance measuring zone

R (W /

phase)

IEC09000049-1-en.vsd
IEC09000049 V1 EN

Figure 178:

Operating characteristic for FRPSPDIS in forward direction for threephase fault, ohm/phase domain

The result from rotation of the load characteristic at a fault between two phases is
presented in fig 111. Since the load characteristic is based on the same
measurement as the quadrilateral characteristic, it will rotate with the quadrilateral
characteristic clockwise by 30 degrees when subject to a pure phase-to-phase fault.
At the same time the characteristic will "shrink" by 2/3, from the full RLdFw and
RLdRv reach, which is valid at load or three-phase fault.

303
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

IEC08000437.vsd
IEC08000437 V1 EN

Figure 179:

Rotation of load characteristic for a fault between two phases

There is a gain in selectivity by using the same measurement as for the


quadrilateral characteristic since not all phase-to-phase loops will be fully affected
by a fault between two phases. It should also provide better fault resistive coverage
in quadrant one. The relative loss of fault resistive coverage in quadrant four
should not be a problem even for applications on series compensated lines.

6.10.2.5

Minimum operate currents


The operation of Phase selection, quadrilateral characteristic with settable angle
(FRPSPDIS) is blocked if the magnitude of input currents falls below certain
threshold values.
The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS
value of the current in phase Ln.
The phase-to-phase loop LmLn is blocked if (2ILn<IMinOpPP).

304
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.10.2.6

Simplified logic diagrams


Figure 112 presents schematically the creation of the phase-to-phase and phase-toearth operating conditions. Consider only the corresponding part of measuring and
logic circuits, when only a phase-to-earth or phase-to-phase measurement is
available within the IED.
Load encroachment block

3I 0 0.5 IMinOpPE
&
INReleasePE
3I 0
Iphmax
100

IRELPE
15 ms
t

&

&

Bool to
integer

BLOCK

3I 0 < IMinOpPE

OR
INBlockPP
3I 0 <
Iphmax
100

STPE

&

10 ms 20 ms
t
t

&

15 ms
t

STCNDLE

STPP
IRELPP

IEC09000149_1_en.vsd
IEC09000149 V1 EN

Figure 180:

Phase-to-phase and phase-to-earth operating conditions (residual


current criteria)

A special attention is paid to correct phase selection at evolving faults. A


STCNDLE output signal is created as a combination of the load encroachment
characteristic and current criteria, refer to figure 112. This signal can be configured
to STCND functional input signals of the distance protection zone and this way
influence the operation of the phase-to-phase and phase-to-earth zone measuring
elements and their phase related starting and tripping signals.
Figure 113 presents schematically the composition of non-directional phase
selective signals STNDLn. Internal signals ZMLnN and ZMLmLn (m and n
change between one and three according to the phase number) represent the
fulfilled operating criteria for each separate loop measuring element, that is within
the characteristic.

305
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

INDL1N
INDL2N
INDL3N

OR

15 ms
t

STNDPE

OR

15 ms
t

STNDL1

OR

15 ms
t

STNDL2

AND

OR

15 ms
t

STNDL3

AND

INDL1L2

IRELPE
ZML1N
ZML2N
ZML3N
ZML1L2
ZML2L3
ZML3L1
IRELPP

AND
AND
AND

INDL2L3
AND

INDL3L1
OR

15 ms
t

STNDPP

IEC00000545_2_en.vsd
IEC00000545-TIFF V2 EN

Figure 181:

Composition on non-directional phase selection signals

Composition of the directional (forward and reverse) phase selective signals is


presented schematically in figure 114 and figure 115. The directional criteria
appears as a condition for the correct phase selection in order to secure a high
phase selectivity for simultaneous and evolving faults on lines within the complex
network configurations. Internal signals DFWLn and DFWLnLm present the
corresponding directional signals for measuring loops with phases Ln and Lm.
Designation FW (figure 115) represents the forward direction as well as the
designation RV (figure 114) represents the reverse direction. All directional signals
are derived within the corresponding digital signal processor.
Figure 114 presents additionally a composition of a STCNDZ output signal, which
is created on the basis of impedance measuring conditions. This signal can be
configured to STCND functional input signals of the distance protection zone and
this way influence the operation of the phase-to-phase and phase-to-earth zone
measuring elements and their phase related starting and tripping signals.

306
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

INDL1N
DRVL1N

AND

INDL1L2
DRVL1L2

AND

OR

15 ms
t

STRVL1

OR

15 ms
t

STRVPE

OR

15 ms
t

STRVL2

INDL3L1
DRVL3L1

AND

INDL2N
DRVL2N

AND

INDL1L2
AND
INDL2L3
DRVL2L3

INDL1N
INDL2N
INDL3N
INDL1L2
INDL2L3
INDL3L1

AND

INDL3N
DRVL3N

AND

INDL2L3

Bool to
integer

15 ms
AND

OR

INDL3L1
AND

15 ms
OR

STCNDZ

STRVL3

STRVPP

IEC00000546_2_en.vsd
IEC00000546-TIFF V2 EN

Figure 182:

Composition of phase selection signals for reverse direction

307
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

AND
INDL1N
DFWL1N

AND

AND

OR

15 ms
t

INDL1L2
DFWL1L2

AND

OR

INDL3L1
DFWL3L1

DFWL2N

OR

15 ms
t

STFWL1

15 ms
t

STFWPE

15 ms
t

STFWL2

15 ms
t

STFW2PH

AND
AND

INDL1L2
AND

OR

INDL2L3
DFWL2L3

STFW1PH

AND

AND

INDL2N

15 ms
t

AND

OR

15 ms
t

AND

INDL3N
DFWL3N

AND

AND

INDL2L3
AND

15 ms
t

STFWL3

15 ms
t

STFW3PH

15 ms
t

STFWPP

OR

INDL3L1

AND
AND

OR

IEC05000201_2_en.vsd
IEC05000201 V2 EN

Figure 183:

Composition of phase selection signals for forward direction

Figure116 presents the composition of output signals TRIP and START, where
internal signals STNDPP, STFWPP and STRVPP are the equivalent to internal
signals STNDPE, STFWPE and STRVPE, but for the phase-to-phase loops.

308
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

TimerPP=Off

tPP
t

AND
OR

TimerPE=Off

tPE
t

AND

AND
OR

TRIP

AND

STNDPP
STFWPP

OR

STRVPP
OR

STNDPE
STFWPE

START

OR

STRVPE

IEC08000441_2_en.vsd
IEC08000441 1 V2 EN

Figure 184:

6.10.3

TRIP and START signal logic

Function block
FRPSPDIS
I3P*
U3P*
BLOCK
DIRCND

TRIP
START
STFWL1
STFWL2
STFWL3
STFWPE
STRVL1
STRVL2
STRVL3
STRVPE
STNDL1
STNDL2
STNDL3
STNDPE
STFW1PH
STFW2PH
STFW3PH
STPE
STPP
STCNDZ
STCNDLE
IEC08000430-2-en.vsd

IEC08000430 V2 EN

Figure 185:

FRPSPDIS function block


309

Technical reference manual

Section 6
Impedance protection
6.10.4

1MRK 505 222-UEN B

Input and output signals


Table 156:
Name

FRPSPDIS Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

DIRCND

INTEGER

External directional condition

Table 157:
Name

FRPSPDIS Output signals


Type

Description

TRIP

BOOLEAN

Trip output

START

BOOLEAN

Start in any phase or loop

STFWL1

BOOLEAN

Fault detected in phase L1 - forward direction

STFWL2

BOOLEAN

Fault detected in phase L2 - forward direction

STFWL3

BOOLEAN

Fault detected in phase L3 - forward direction

STFWPE

BOOLEAN

Earth fault detected in forward direction

STRVL1

BOOLEAN

Fault detected in phase L1 - reverse direction

STRVL2

BOOLEAN

Fault detected in phase L2 - reverse direction

STRVL3

BOOLEAN

Fault detected in phase L3 - reverse direction

STRVPE

BOOLEAN

Earth fault detected in reverse direction

STNDL1

BOOLEAN

Non directional start in L1

STNDL2

BOOLEAN

Non directional start in L2

STNDL3

BOOLEAN

Non directional start in L3

STNDPE

BOOLEAN

Non directional start, phase-earth

STFW1PH

BOOLEAN

Start in forward direction for single-phase fault

STFW2PH

BOOLEAN

Start in forward direction for two- phase fault

STFW3PH

BOOLEAN

Start in forward direction for thre-phase fault

STPE

BOOLEAN

Current conditions release of phase-earth


measuring elements

STPP

BOOLEAN

Current conditions release of phase-phase


measuring elements

STCNDZ

INTEGER

Start condition (Z< with LE and 3I0 E/F detection)

STCNDLE

INTEGER

Start condition (only LE and 3I0 E/F detection)

310
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.10.5
Table 158:

Setting parameters
FRPSPDIS Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base current, i.e. rated current

UBase

0.05 - 2000.00

kV

0.01

400.00

Base voltage, i.e. rated voltage

INBlockPP

10 - 100

%IPh

40

3I0 limit for blocking phase-to-phase


measuring loops

INReleasePE

10 - 100

%IPh

20

3I0 limit for releasing phase-to-earth


measuring loops

RLdFw

1.00 - 3000.00

ohm/p

0.01

80.00

Forward resistive reach within the load


impedance area

RLdRv

1.00 - 3000.00

ohm/p

0.01

80.00

Reverse resistive reach within the load


impedance area

ArgLd

5 - 70

Deg

30

Load angle determining the load


impedance area

X1

0.50 - 3000.00

ohm/p

0.01

40.00

Positive sequence reactance reach

R1PP

0.10 - 1000.00

ohm/p

0.01

15.00

Positive seq. resistance for characteristic


angle, Ph-Ph

R1PE

0.10 - 1000.00

ohm/p

0.01

1.50

Positive seq. resistance for characteristic


angle, Ph-E

X0

0.50 - 9000.00

ohm/p

0.01

120.00

Zero sequence reactance reach

R0PE

0.50 - 3000.00

ohm/p

0.01

5.00

Zero seq. resistance for zone


characteristic angle, Ph-E

RFFwPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, forward

RFRvPP

0.50 - 3000.00

ohm/l

0.01

30.00

Fault resistance reach, Ph-Ph, reverse

RFFwPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, forward

RFRvPE

1.00 - 9000.00

ohm/l

0.01

100.00

Fault resistance reach, Ph-E, reverse

IMinOpPP

5 - 500

%IB

10

Minimum operate delta current for PhasePhase loops

IMinOpPE

5 - 500

%IB

Minimum operate phase current for


Phase-Earth loops

Table 159:

FRPSPDIS Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

TimerPP

Off
On

Off

Operation mode Off / On of Zone timer,


Ph-Ph

tPP

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-Ph

TimerPE

Off
On

Off

Operation mode Off / On of Zone timer,


Ph-E

tPE

0.000 - 60.000

0.001

3.000

Time delay to trip, Ph-E

311
Technical reference manual

Section 6
Impedance protection
6.10.6

1MRK 505 222-UEN B

Technical data
Table 160:

FRPSPDIS technical data

Function

6.11

Range or value

Accuracy

Minimum operate current

(5-500)% of IBase

Reactive reach, positive


sequence

(0.503000.00) /phase

Resistive reach, positive


sequence

(0.101000.00) /phase

Reactive reach, zero sequence

(0.509000.00) /phase

Resistive reach, zero sequence

(0.503000.00) /phase

Fault resistance, phase-to-earth


faults, forward and reverse

(1.009000.00) /loop

2.0% static accuracy


2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x Ir
Current range: (0.5-30) x
IBase
Angle: at 0 degrees and 85
degrees

Fault resistance, phase-tophase faults, forward and reverse

(0.503000.00) /loop

Load encroachment criteria:


Load resistance, forward and
reverse
Safety load impedance angle

(1.003000.00) /phase
(5-70) degrees

Reset ratio

105% typically

Power swing detection ZMRPSB


Function description
Power swing detection

IEC 61850
identification

IEC 60617
identification

ZMRPSB

ANSI/IEEE C37.2
device number
68

Zpsb
SYMBOL-EE V1 EN

6.11.1

Introduction
Power swings may occur after disconnection of heavy loads or trip of big
generation plants.
Power swing detection function (ZMRPSB) is used to detect power swings and
initiate block of selected distance protection zones. Occurrence of earth-fault
currents during a power swing inhibits the ZMRPSB function to allow fault clearance.

6.11.2

Principle of operation
Power swing detection (ZMRPSB ) function comprises an inner and an outer
quadrilateral measurement characteristic with load encroachment, as shown in
figure 186.

312
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Its principle of operation is based on the measurement of the time it takes for a
power swing transient impedance to pass through the impedance area between the
outer and the inner characteristics. Power swings are identified by transition times
longer than a transition time set on corresponding timers. The impedance
measuring principle is the same as that used for the distance protection zones. The
impedance and the characteristic passing times are measured in all three phases
separately.
One-out-of-three or two-out-of-three operating modes can be selected according to
the specific system operating conditions.

jX

X1OutFw
X1InFw

DRv

R1LIn

ZL

DFw
j

R1FInRv

R1FInFw

DFw

ArgLd

DRv

ArgLd

DFw
DFw

R
DFw

DRv

DFw

RLdInRv RLdInFw

DRv
j

RLdOutRv RLdOutFw

DRv

X1InRv
X1OutRv
IEC09000222_1_en.vsd

IEC09000222 V1 EN

Figure 186:

Operating characteristic for ZMRPSB function (setting parameters


in italic)

The impedance measurement within ZMRPSB function is performed by solving


equation 72 and equation 73 (n = 1, 2, 3 for each corresponding phase L1, L2 and
L3).

ULn
Rset
Re
ILn
EQUATION1183 V2 EN

(Equation 72)

313
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

ULn
Im
Xset
n
I
L

EQUATION1184 V2 EN

(Equation 73)

The Rset and Xset are R and X boundaries.

6.11.2.1

Resistive reach in forward direction


To avoid load encroachment, the resistive reach is limited in forward direction by
setting the parameter RLdOutFw which is the outer resistive load boundary value
while the inner resistive boundary is calculated according to equation 74.

RLdInFw = kLdRFwRLdOutFw
EQUATION1185 V2 EN

(Equation 74)

where:

kLdRFw is a settable multiplication factor less than 1

The slope of the load encroachment inner and outer boundary is defined by setting
the parameter ArgLd.
The load encroachment in the fourth quadrant uses the same settings as in the first
quadrant (same ArgLd and RLdOutFw and calculated value RLdInFw).
The quadrilateral characteristic in the first quadrant is tilted to get a better
adaptation to the distance measuring zones. The angle is the same as the line angle
and derived from the setting of the reactive reach inner boundary X1InFw and the
line resistance for the inner boundary R1LIn. The fault resistance coverage for the
inner boundary is set by the parameter R1FInFw.
From the setting parameter RLdOutFw and the calculated value RLdInFw a
distance between the inner and outer boundary, DFw, is calculated. This value is
valid for R direction in first and fourth quadrant and for X direction in first and
second quadrant.

6.11.2.2

Resistive reach in reverse direction


To avoid load encroachment in reverse direction, the resistive reach is limited by
setting the parameter RLdOutRv for the outer boundary of the load encroachment
zone. The distance to the inner resistive load boundary RLdInRv is determined by
using the setting parameter kLdRRv in equation 75.

314
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

RLdInRv = kLdRRvRLdOutRv
EQUATION1187 V2 EN

(Equation 75)

where:

kLdRRv is a settable multiplication factor less than 1

From the setting parameter RLdOutRv and the calculated value RLdInRv, a
distance between the inner and outer boundary, DRv, is calculated. This value is
valid for R direction in second and third quadrant and for X direction in third and
fourth quadrant.
The inner resistive characteristic in the second quadrant outside the load
encroachment part corresponds to the setting parameter R1FInRv for the inner
boundary. The outer boundary is internally calculated as the sum of DRv+R1FInRv.
The inner resistive characteristic in the third quadrant outside the load
encroachment zone consist of the sum of the settings R1FInRv and the line
resistance R1LIn. The argument of the tilted lines outside the load encroachment is
the same as the tilted lines in the first quadrant. The distance between the inner and
outer boundary is the same as for the load encroachment in reverse direction, that is
DRv.

6.11.2.3

Reactive reach in forward and reverse direction


The inner characteristic for the reactive reach in forward direction correspond to
the setting parameter X1InFw and the outer boundary is defined as X1InFw + DFw,
where:
DFw = RLdOutFw - KLdRFw RLdOutFw

The inner characteristic for the reactive reach in reverse direction correspond to the
setting parameter X1InRv for the inner boundary and the outer boundary is defined
as X1InRv + DRv.
where:
DRv = RLdOutRv - KLdRRv RLdOutRv

6.11.2.4

Basic detection logic


The operation of the Power swing detection ZMRPSB is only released if the
magnitude of the current is above the setting of the min operating current,
IMinOpPE.
ZMRPSB function can operate in two operating modes:
315

Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The 1 out of 3 operating mode is based on detection of power swing in any of


the three phases. Figure 187 presents a composition of an internal detection
signal DET-L1 in this particular phase.
The 2 out of 3 operating mode is based on detection of power swing in at least
two out of three phases. Figure 188 presents a composition of the detection
signals DET1of3 and DET2of3.

Signals ZOUTLn (outer boundary) and ZINLn (inner boundary) in figure 187 are
related to the operation of the impedance measuring elements in each phase
separately (n represents the corresponding L1, L2 and L3). They are internal
signals, calculated by ZMRPSB function.
The tP1 timer in figure 187 serve as detection of initial power swings, which are
usually not as fast as the later swings are. The tP2 timer become activated for the
detection of the consecutive swings, if the measured impedance exit the operate
area and returns within the time delay, set on the tW waiting timer. The upper part
of figure 187 (internal input signal ZOUTL1, ZINL1, AND-gates and tP-timers)
are duplicated for phase L2 and L3. All tP1 and tP2 timers in the figure have the
same settings.
ZOUTL1
ZINL1

0-tP1
0

AND

AND

0-tP2
0

OR
-loop
AND

ZOUTL2
ZOUTL3

detected

-loop
OR

AND

DET-L1

OR

0
0-tW
IEC05000113-2-en.vsd

IEC05000113 V2 EN

Figure 187:

Detection of power swing in phase L1

316
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

DET-L1
DET-L2
DET-L3

DET1of3 - int.

>1

&
>1

&

DET2of3 - int.

&
IEC01000057-2-en.vsd
IEC01000057-TIFF V2 EN

Figure 188:

Detection of power swing for 1-of-3 and 2-of-3 operating mode

ZOUTL1

ZOUT

OR

ZOUTL2

ZINL1

ZOUTL3

TRSP

ZIN

OR

ZINL2

AND

ZINL3

tEF
AND

I0CHECK
AND

BLKI02

10 ms
t

OR
tR1

AND

INHIBIT

OR

-loop
tR2
AND

BLKI01

BLOCK
-loop
DET1of3 - int.
REL1PH
BLK1PH
DET2of3 - int.
REL2PH
BLK2PH

AND
tH
OR
AND

t
OR

AND

START

EXTERNAL
en05000114.vsd
IEC05000114 V1 EN

Figure 189:

Simplified block diagram for ZMRPSB function

317
Technical reference manual

Section 6
Impedance protection
6.11.2.5

1MRK 505 222-UEN B

Operating and inhibit conditions


Figure 189 presents a simplified logic diagram for the Power swing detection
function ZMRPSB. The internal signals DET1of3 and DET2of3 relate to the
detailed logic diagrams in figure 187 and figure 188 respectively.
Selection of the operating mode is possible by the proper configuration of the
functional input signals REL1PH, BLK1PH, REL2PH, and BLK2PH.
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated from
RLdOutFw and RLdOutRv. The characteristic will in this case be only quadrilateral.
There are four different ways to form the internal INHIBIT signal:

Logical 1 on functional input BLOCK inhibits the output START signal


instantaneously.
The INHIBIT internal signal is activated, if the power swing has been detected
and the measured impedance remains within its operate characteristic for the
time, which is longer than the time delay set on tR2 timer. It is possible to
disable this condition by connecting the logical 1 signal to the BLKI01
functional input.
The INHIBIT internal signal is activated after the time delay, set on tR1 timer,
if an earth-fault appears during the power swing (input IOCHECK is high) and
the power swing has been detected before the earth-fault (activation of the
signal I0CHECK). It is possible to disable this condition by connecting the
logical 1 signal to the BLKI02 functional input.
The INHIBIT logical signals becomes logical 1, if the functional input
I0CHECK appears within the time delay, set on tEF timer and the impedance
has been seen within the outer characteristic of ZMRPSB operate
characteristic in all three phases. This function prevents the operation of
ZMRPSB function in cases, when the circuit breaker closes onto persistent
single-phase fault after single-phase autoreclosing dead time, if the initial singlephase fault and single-phase opening of the circuit breaker causes the power
swing in the remaining two phases.

318
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.11.3

Function block
ZMRPSB
I3P*
U3P*
BLOCK
BLKI01
BLKI02
BLK1PH
REL1PH
BLK2PH
REL2PH
I0CHECK
TRSP
EXTERNAL

START
ZOUT
ZIN

IEC06000264-2-en.vsd
IEC06000264 V2 EN

Figure 190:

6.11.4

ZMRPSB function block

Input and output signals


Table 161:
Name

ZMRPSB Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKI01

BOOLEAN

Block inhibit of start output for slow swing condition

BLKI02

BOOLEAN

Block inhibit of start output for subsequent


residual current detection

BLK1PH

BOOLEAN

Block one-out-of-three-phase operating mode

REL1PH

BOOLEAN

Release one-out-of-three-phase operating mode

BLK2PH

BOOLEAN

Block two-out-of-three-phase operating mode

REL2PH

BOOLEAN

Release two-out-of-three-phase operating mode

I0CHECK

BOOLEAN

Residual current (3I0) detection used to inhibit


start output

TRSP

BOOLEAN

Single-pole tripping command issued by tripping


function

EXTERNAL

BOOLEAN

Input for external detection of power swing

Table 162:
Name

ZMRPSB Output signals


Type

Description

START

BOOLEAN

Power swing detected

ZOUT

BOOLEAN

Measured impedance within outer impedance


boundary

ZIN

BOOLEAN

Measured impedance within inner impedance


boundary

319
Technical reference manual

Section 6
Impedance protection
6.11.5
Table 163:
Name

1MRK 505 222-UEN B

Setting parameters
ZMRPSB Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Mode On / Off

X1InFw

0.10 - 3000.00

ohm

0.01

30.00

Inner reactive boundary, forward

R1LIn

0.10 - 1000.00

ohm

0.01

30.00

Line resistance for inner characteristic


angle

R1FInFw

0.10 - 1000.00

ohm

0.01

30.00

Fault resistance coverage to inner


resistive line, forward

X1InRv

0.10 - 3000.00

ohm

0.01

30.00

Inner reactive boundary, reverse

R1FInRv

0.10 - 1000.00

ohm

0.01

30.00

Fault resistance line to inner resistive


boundary, reverse

OperationLdCh

Off
On

On

Operation of load discrimination


characteristic

RLdOutFw

0.10 - 3000.00

ohm

0.01

30.00

Outer resistive load boundary, forward

ArgLd

5 - 70

Deg

25

Load angle determining load impedance


area

RLdOutRv

0.10 - 3000.00

ohm

0.01

30.00

Outer resistive load boundary, reverse

kLdRFw

0.50 - 0.90

Mult

0.01

0.75

Multiplication factor for inner resistive


load boundary, forward

kLdRRv

0.50 - 0.90

Mult

0.01

0.75

Multiplication factor for inner resistive


load boundary, reverse

tEF

0.000 - 60.000

0.001

3.000

Timer for overcoming single-pole


reclosing dead time

IMinOpPE

5 - 30

%IB

10

Minimum operate current in % of IBase

IBase

1 - 99999

3000

Base setting for current level settings

Table 164:

ZMRPSB Group settings (advanced)

Name

Values (Range)

Unit

tP1

0.000 - 60.000

0.001

0.045

Timer for detection of initial power swing

tP2

0.000 - 60.000

0.001

0.015

Timer for detection of subsequent power


swings

tW

0.000 - 60.000

0.001

0.250

Waiting timer for activation of tP2 timer

tH

0.000 - 60.000

0.001

0.500

Timer for holding power swing START


output

tR1

0.000 - 60.000

0.001

0.300

Timer giving delay to inhibit by the


residual current

tR2

0.000 - 60.000

0.001

2.000

Timer giving delay to inhibit at very slow


swing

Step

Default

Description

320
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.11.6

Technical data
Table 165:

ZMRPSB technical data

Function

6.12

Range or value

Reactive reach

(0.10-3000.00) W/phase

Resistive reach

(0.101000.00)W/loop

Timers

(0.000-60.000) s

2.0% static accuracy


Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir
Angle: at 0 degrees and 85
degrees
0.5% 10 ms

Power swing logic ZMRPSL


Function description
Power swing logic

6.12.1

Accuracy

IEC 61850
identification
ZMRPSL

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Power Swing Logic (ZMRPSL) is a complementary function to Power Swing
Detection (ZMRPSB) function. It provides possibility for selective tripping of
faults on power lines during system oscillations (power swings or pole slips), when
the distance protection function should normally be blocked. The complete logic
consists of two different parts:

Communication and tripping part: provides selective tripping on the basis of


special distance protection zones and a scheme communication logic, which
are not blocked during the system oscillations.
Blocking part: blocks unwanted operation of instantaneous distance protection
zone 1 for oscillations, which are initiated by faults and their clearing on the
adjacent power lines and other primary elements.

6.12.2

Principle of operation

6.12.2.1

Communication and tripping logic


Communication and tripping logic as used by the power swing distance protection
zones is schematically presented in figure 191.

321
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

STDEF
AR1P1

&

STPSD
BLOCK

&

tCS
t

&

tTrip

tBlkTr
t

CS

CSUR

&

BLKZMPS

t
CACC
CR

&

>1

TRIP

en06000236.vsd
IEC06000236 V1 EN

Figure 191:

Simplified logic diagram power swing communication and tripping


logic

The complete logic remains blocked as long as there is a logical one on the
BLOCK functional input signal. Presence of the logical one on the STDEF
functional input signal also blocks the logic as long as this block is not released by
the logical one on the AR1P1 functional input signal. The functional output signal
BLKZMPS remains logical one as long as the function is not blocked externally
(BLOCK is logical zero) and the earth-fault is detected on protected line (STDEF
is logical one), which is connected in three-phase mode (AR1P1 is logical zero).
Timer tBlkTr prolongs the duration of this blocking condition, if the measured
impedance remains within the operate area of the Power Swing Detection
(ZMRPSB) function (STPSD input active). The BLKZMPS can be used to block
the operation of the power-swing zones.
Logical one on functional input CSUR, which is normally connected to the TRIP
functional output of a power swing carrier sending zone, activates functional output
CS, if the function is not blocked by one of the above conditions. It also activates
the TRIP functional output.
Initiation of the CS functional output is possible only, if the STPSD input has been
active longer than the time delay set on the security timer tCS.
Simultaneous presence of the functional input signals PLTR_CRD and CR (local
trip condition) also activates the TRIP functional output, if the function is not
blocked by one of the above conditions and the STPSD signal has been present
longer then the time delay set on the trip timer tTrip.

6.12.2.2

Blocking logic
Figure 192 presents the logical circuits, which control the operation of the
underreaching zone (zone 1) at power swings, caused by the faults and their
clearance on the remote power lines.

322
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

&
BLKZMH

&
STZML
BLOCK
STMZH
STZMPSD
STPSD

tZL
t

&
&

tDZ
t

&

>1

STZMLL

>1

&
-loop

en06000237.vsd
IEC06000237 V1 EN

Figure 192:

Control of underreaching distance protection (Zone 1) at power


swings caused by the faults and their clearance on adjacent lines
and other system elements

The logic is disabled by a logical one on functional input BLOCK. It can start only
if the following conditions are simultaneously fulfilled:

STPSD functional input signal must be a logical zero. This means, that Power
swing detection (ZMRPSB) function must not detect power swinging over the
protected power line.
STZMPSD functional input must be a logical one. This means that the
impedance must be detected within the external boundary of ZMRPSB function.
STZMOR functional input must be a logical one. This means that the fault
must be detected by the overreaching distance protection zone, for example
zone 2.

The STZMURPS functional output, which can be used in complete terminal logic
instead of a normal distance protection zone 1, becomes active under the following
conditions:

If the STZMUR signal appears at the same time as the STZMOR or if it


appears with a time delay, which is shorter than the time delay set on timer
tDZ.
If the STZMUR signal appears after the STZMOR signal with a time delay
longer than the delay set on the tDZ timer, and remains active longer than the
time delay set on the tZL timer.

The BLKZMOR functional output signal can be used to block the operation of the
higher distance protection zone, if the fault has moved into the zone 1 operate area
after tDZ time delay.

323
Technical reference manual

Section 6
Impedance protection
6.12.3

1MRK 505 222-UEN B

Function block
ZMRPSL
BLOCK
STZMUR
STZMOR
STPSD
STDEF
STZMPSD
CACC
AR1P1
CSUR
CR

TRIP
STZMURPS
BLKZMUR
BLKZMOR
CS

IEC07000026-2-en.vsd
IEC07000026 V2 EN

Figure 193:

6.12.4

ZMRPSL function block

Input and output signals


Table 166:
Name

ZMRPSL Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

STZMUR

BOOLEAN

Start of the underreaching zone

STZMOR

BOOLEAN

Start of the overreaching zone

STPSD

BOOLEAN

Power swing detected

STDEF

BOOLEAN

Start from Earth Fault Protection in forward or


reverse direction

STZMPSD

BOOLEAN

Operation of Power Swing Detection external


characteristic

CACC

BOOLEAN

Overreaching ZM zone to be accelerated

AR1P1

BOOLEAN

Single pole auto-reclosing in progress

CSUR

BOOLEAN

Carrier send by the underreaching power-swing


zone

CR

BOOLEAN

Carrier receive signal during power swing


detection operation

Table 167:
Name

ZMRPSL Output signals


Type

Description

TRIP

BOOLEAN

Trip through Power Swing Logic

STZMURPS

BOOLEAN

Start of Underreaching zone controlled by PSL to


be used in configuration

BLKZMUR

BOOLEAN

Block trip of underreaching impedance zone

BLKZMOR

BOOLEAN

Block trip of overreaching distance protection


zones

CS

BOOLEAN

Carrier send signal controlled by the power swing

324
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.12.5
Table 168:

Setting parameters
ZMRPSL Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

tDZ

0.000 - 60.000

0.001

0.050

Permitted max oper time diff between


higher and lower zone

tDZMUR

0.000 - 60.000

0.001

0.200

Delay for oper of underreach zone with


detected diff in oper time

tCS

0.000 - 60.000

0.001

0.100

Conditional timer for sending the CS at


power swings

tTrip

0.000 - 60.000

0.001

0.100

Conditional timer for tripping at power


swings

tBlkTr

0.000 - 60.000

0.001

0.300

Timer for blocking the overreaching


zones trip

6.13

6.13.1

Pole slip protection PSPPPAM


Function description

IEC 61850
identification

Pole slip protection

PSPPPAM

IEC 60617
identification
Ucos

ANSI/IEEE C37.2
device number
78

Introduction
Sudden events in an electrical power system such as large changes in load, fault
occurrence or fault clearance, can cause power oscillations referred to as power
swings. In a non-recoverable situation, the power swings become so severe that the
synchronism is lost, a condition referred to as pole slipping. The main purpose of
the pole slip protection (PSPPPAM) is to detect, evaluate, and take the required
action for pole slipping occurrences in the power system. The electrical system
parts swinging to each other can be separated with the line/s closest to the centre of
the power swing allowing the two systems to be stable as separated islands.

6.13.2

Principle of operation
If the generator is faster than the power system, the rotor movement in the
impedance and voltage diagram is from right to left and generating is signalled. If
the generator is slower than the power system, the rotor movement is from left to
right and motoring is signalled (the power system drives the generator as if it were
a motor).

325
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

The movements in the impedance plain can be seen in figure 194. The transient
behaviour is described by the transient EMF's EA and EB, and by X'd, XT and the
transient system impedance ZS.
Zone 1
EB

Zone 2

Xd

XT

XS

IED

EA

jX

A
XS

Pole slip
impedance
movement

XT

Apparent generator
impedance

Xd
B

IEC06000437_2_en.vsd
IEC06000437 V2 EN

Figure 194:

Movements in the impedance plain

where:
X'd

= transient reactance of the generator

XT

= short-circuit reactance of the step-up transformer

ZS

= impedance of the power system A

The detection of rotor angle is enabled when:

326
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

the minimum current exceeds 0.10 IN (IN is IBase parameter set under general
setting).
the maximum voltage falls below 0.92 UBase
the voltage Ucos (the voltage in phase with the generator current) has an
angular velocity of 0.2...8 Hz and
the corresponding direction is not blocked.

en07000004.vsd
IEC07000004 V1 EN

Figure 195:

Different generator quantities as function of the angle between the


equivalent generators

An alarm is given when movement of the rotor is detected and the rotor angle
exceeds the angle set for 'WarnAngle'.
Slipping is detected when:

a change of rotor angle of min. 50 ms is recognized


the slip line is crossed between ZA and ZB.

When the impedance crosses the slip line between ZB and ZC it counts as being in
zone 1 and between ZC and ZA in zone 2. The entire distance ZA-ZB becomes zone
1 when signal EXTZONE1 is high (external device detects the direction of the
centre of slipping).
After the first slip, the signals ZONE1 or ZONE2 and depending on the direction
of slip - either GEN or MOTOR are issued.

327
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Every time pole slipping is detected, the impedance of the point where the slip line
is crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of
rotor movement has reduced in relation to the preceding slip or the slip line is
crossed in the opposite direction outside ZA-ZB. A further slip in the opposite
direction within ZA-ZB resets all the signals and is then signalled itself as a first slip.
The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than TripAngle. The TRIP2 signal is generated
after N2 slips in zone 2, providing the rotor angle is less than TripAngle.
All signals are reset if:

the direction of movement reverses


the rotor angle detector resets without a slip being counted or
no rotor relative movement was detected during the time ResetTime.

Imin > 0.10 IBase

Ucosj < 0.92 UBase

AND
START

AND

0.2 Slip.Freq. 8 Hz

d startAngle
ZONE1

AND

Z cross line ZA - ZC

ZONE2

AND

Z cross line ZC - ZB

Counter
N1Limit

a
b

ab

d tripAngle

OR
Counter

N2Limit

TRIP1

AND

a
b ab

AND

TRIP

TRIP2

en07000005.vsd
IEC07000005 V1 EN

Figure 196:

Simplified logic diagram for pole slip protection PSPPPAM

328
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.13.3

Function block
PSPPPAM
I3P*
U3P*
BLOCK
BLKGEN
BLKMOTOR
EXTZONE1

TRIP
TRIP1
TRIP2
START
ZONE1
ZONE2
GEN
MOTOR
SFREQ
SLIPZOHM
SLIPZPER
UCOS
UCOSPER

IEC10000045-1-en.vsd
IEC10000045 V1 EN

Figure 197:

6.13.4

PSPPPAM function block

Input and output signals


Table 169:
Name

PSPPPAM Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Current group connection

U3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLKGEN

BOOLEAN

Block operation in generating direction

BLKMOTOR

BOOLEAN

Block operation in motor direction

EXTZONE1

BOOLEAN

Extension of zone1 with zone2 region

Table 170:
Name

PSPPPAM Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip1 after the N1Limit slip in zone1

TRIP2

BOOLEAN

Trip2 after the N2Limit slip in zone2

START

BOOLEAN

Common start signal

ZONE1

BOOLEAN

First slip in zone1 region

ZONE2

BOOLEAN

First slip in zone2 region

GEN

BOOLEAN

Generator is faster than the system

MOTOR

BOOLEAN

Generator is slower than the system

SFREQ

REAL

Slip frequency

SLIPZOHM

REAL

Slip impedance in ohms

SLIPZPER

REAL

Slip impedance in percent of ZBase

UCOS

REAL

UCosPhi voltage

UCOSPER

REAL

UCosPhi voltage in percent of UBase

329
Technical reference manual

Section 6
Impedance protection
6.13.5
Table 171:
Name

1MRK 505 222-UEN B

Setting parameters
PSPPPAM Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation On / Off

OperationZ1

Off
On

On

Operation Zone1 On / Off

OperationZ2

Off
On

On

Operation Zone2 On / Off

ImpedanceZA

0.00 - 1000.00

0.01

10.00

Forward impedance in % of Zbase

ImpedanceZB

0.00 - 1000.00

0.01

10.00

Reverse impedance in % of Zbase

ImpedanceZC

0.00 - 1000.00

0.01

10.00

Impedance of zone1 limit in % of Zbase

AnglePhi

72.00 - 90.00

Deg

0.01

85.00

Angle of the slip impedance line

StartAngle

0.0 - 180.0

Deg

0.1

110.0

Rotor angle for the start signal

TripAngle

0.0 - 180.0

Deg

0.1

90.0

Rotor angle for the trip1 and trip2 signals

N1Limit

1 - 20

Count limit for the trip1 signal

N2Limit

1 - 20

Count limit for the trip2 signal

Table 172:
Name
ResetTime

Table 173:

PSPPPAM Group settings (advanced)


Values (Range)

Unit

0.000 - 60.000

Step
0.001

Default
5.000

Description
Time without slip to reset all signals

PSPPPAM Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

IBase

0.1 - 99999.9

0.1

3000.0

Base Current (primary phase current in


Amperes)

UBase

0.1 - 9999.9

kV

0.1

20.0

Base Voltage (primary phase-to-phase


voltage in kV)

MeasureMode

PosSeq
L1L2
L2L3
L3L1

PosSeq

Measuring mode (PosSeq, L1L2, L2L3,


L3L1)

InvertCTcurr

No
Yes

No

Invert current direction

6.13.6

Description

Technical data
Table 174:

PSPPPAM technical data

Function

Range or value

Accuracy

Impedance reach

(0.001000.00)% of Zbase

2.0% of Ur/Ir

Characteristic angle

(72.0090.00) degrees

5.0 degrees

Start and trip angles

(0.0180.0) degrees

5.0 degrees

Zone 1 and Zone 2 trip counters

(1-20)

330
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.14

Automatic switch onto fault logic, voltage and


current based ZCVPSOF
Function description
Automatic switch onto fault logic,
voltage and current based

6.14.1

IEC 61850
identification
ZCVPSOF

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Automatic switch onto fault logic, voltage and current based (ZCVPSOF) is a
function that gives an instantaneous trip at closing of breaker onto a fault. A dead
line detection check is provided to activate the function when the line is dead.
Mho distance protections can not operate for switch onto fault condition when the
phase voltages are close to zero. An additional logic based on UI Level is used for
this purpose.

6.14.2

Principle of operation
Automatic switch onto fault logic, voltage and current based function (ZCVPSOF)
can be activated externally by Breaker Closed Input or internally (automatically)
by using UI Level Based Logic see figure 198.
The activation from the Dead line detection function is released if the internal
signal deadLine from the UILevel function is activated at the same time as the
input ZACC is not activated during at least for a duration tDLD and the setting
parameter AutoInit is set to On.
When the setting AutoInit is Off, the function is activated by an external binary
input BC. To get a trip one of the following operation modes must also be selected
by the parameter Mode:
Mode = Impedance; trip is released if the input ZACC is activated (normal
connected to non directional distance protection zone).
Mode = UILevel; trip is released if UILevel detector is activated.
Mode = UILvl&Imp; trip is initiated based on impedance measured criteria or
UILevel detection.
The internal signal deadLine from the UILevel detector is activated if all three
phase currents and voltages are below the setting IPh< and UPh<.
UI Level based measurement detects the switch onto fault condition even though
the voltage is very low. The logic is based on current and voltage levels. The
internal signal SOTF UILevel is activated if a phase voltage is below the setting
331

Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

UPh< and corresponding phase current is above the setting IPh< longer than the
time tDuration.
ZCVPSOF can be activated externally from input BC and thus setting AutoInit is
bypassed.
The function is released during a settable time tSOTF.
The function can be blocked by activating the input BLOCK.
BLOCK

15

AND

TRIP

BC

AutiInit=On
1000

200

ZACC

AND

IL1

OR

deadLine

IL2
IL3
UL1

UILevel detector

UL2
UL3
Iph<

SOTFU ILevel

Uph<

AND

Mode = Impedance

AND

Mode = UILevel

OR

OR

Mode = UILvl&Imp

AND

en07000084.vsd

IEC07000084 V2 EN

Figure 198:

Simplified logic diagram for Automatic switch onto fault logic,


voltage and current based.

332
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

6.14.3

Function block
ZCVPSOF
I3P*
U3P*
BLOCK
BC
ZACC

TRIP

IEC06000459-2-en.vsd
IEC06000459 V2 EN

Figure 199:

6.14.4

ZCVPSOF function block

Input and output signals


Table 175:

ZCVPSOF Input signals

Name

Type
GROUP
SIGNAL

Current DFT

U3P

GROUP
SIGNAL

Voltage DFT

BLOCK

BOOLEAN

Block of function

BC

BOOLEAN

External enabling of SOTF

ZACC

BOOLEAN

Distance zone to be accelerated by SOTF

ZCVPSOF Output signals

Name

Type

TRIP

Table 177:

Description

I3P

Table 176:

6.14.5

Default

Description

BOOLEAN

Trip output

Setting parameters
ZCVPSOF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current (A)

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage L-L (kV)

Mode

Impedance
UILevel
UILvl&Imp

UILevel

Mode of operation of SOTF Function

AutoInit

Off
On

Off

Automatic switch onto fault initialization

IPh<

1 - 100

%IB

20

Current level for detection of dead line in


% of IBase

UPh<

1 - 100

%UB

70

Voltage level for detection of dead line in


% of UBase

Table continues on next page

333
Technical reference manual

Section 6
Impedance protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

tDuration

0.000 - 60.000

0.001

0.020

Time delay for UI detection (s)

tSOTF

0.000 - 60.000

0.001

1.000

Drop off delay time of switch onto fault


function

tDLD

0.000 - 60.000

0.001

0.200

Delay time for activation of dead line


detection

6.14.6

Step

Default

Technical data
Table 178:

ZCVPSOF technical data

Parameter

6.15

Range or value

Accuracy

Operate voltage, detection of dead line

(1100)% of

0.5% of Ur

Operate current, detection of dead line

(1100)% of

1.0% of Ir

Delay following dead line detection input before


Automatic switch into fault logic function is
automatically turned On

(0.00060.000) s

0.5% 10 ms

Time period after circuit breaker closure in which


Automatic switch into fault logic function is active

(0.00060.000) s

0.5% 10 ms

UBase
IBase

Phase preference logic PPLPHIZ


Function description
Phase preference logic

6.15.1

Description

IEC 61850
identification
PPLPHIZ

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Phase preference logic function PPLPHIZ is intended to be used in isolated or high
impedance earthed networks where there is a requirement to trip only one of the
faulty lines at cross-country fault.
Phase preference logic inhibits tripping for single phase-to-earth faults in isolated
and high impedance earthed networks, where such faults are not to be cleared by
distance protection. For cross-country faults, the logic selects either the leading or
the lagging phase-earth loop for measurement and initiates tripping of the preferred
fault based on the selected phase preference. A number of different phase
preference combinations are available for selection.

6.15.2

Principle of operation
Phase preference logic PPLPHIZ has 10 operation modes, which can be set by the
parameter OperMode. The different modes and their explanation are shown in

334
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

table 179 below. The difference between cyclic and acyclic operation can be
explained by the following example. Assume a L1 fault on one line and a L3 fault
on another line. For OperMode = 1231c the line with L3 fault will be tripped (L3
before L1) while for OperMode = 123a the line with L1 1 fault will be tripped (L1
before L3).
Table 179:
OperMode

Operation modes for Phase preference logic


Description

No filter

No filter, phase-to-phase measuring loops are not blocked during single phase-toearth faults. Tripping is allowed without any particular phase preference at crosscountry faults

No pref

No preference, trip is blocked during single phase-to-earth faults, trip is allowed


without any particular phase preference at cross-country fault

1231 c

Cyclic 1231c; L1 before L2 before L3 before L1

1321 c

Cyclic 1321c; L1 before L3 before L2 before L1

123 a

Acyclic 123a; L1 before L2before L3

132 a

Acyclic 132a; L1 before L3 before L2

213 a

Acyclic 213a; L2 before L1 before L3

231 a

Acyclic 231a; L2 before L3 before L1

312 a

Acyclic 312a; L3 before L1 before L2

321 a

Acyclic 321a; L3 before L2 before L1

The function can be divided into two parts; one labeled voltage and current
discrimination and the second one labeled phase preference evaluation, see
figure 200.
The aim with the voltage and current discrimination part is to discriminate faulty
phases and to determine if there is a cross-country fault. If cross-country fault is
detected, an internal signal Detected cross-country fault is created and sent to the
phase preference part to be used in the evaluation process for determining the
condition for trip.
The voltage and current discrimination part gives phase segregated start signals if
the respective measured phase voltage is below the setting parameter UPN< at the
same time as the zero sequence voltage is above the setting parameter 3U0>. If
there is a start in any phase the START output signal will be activated.
The internal signal for detection of cross-country fault, DetectCrossCountry, that
come from the voltage and current discrimination part of the function can be
achieved in three different ways:

335
Technical reference manual

Section 6
Impedance protection

1.
2.

3.

1MRK 505 222-UEN B

The magnitude of 3I0 has been above the setting parameter IN> for a time
longer than the setting of pick-up timer tIN.
The magnitude of 3I0 has been above the setting parameter IN> at the same
time as the magnitude of 3U0 has been above the setting parameter 3U0>
during a time longer than the setting of pick-up timer tUN.
The magnitude of 3I0 has been above the setting parameter IN> at the same
time as one of the following conditions are fulfilled:

the measured phase-to-phase voltage in at least one of the phase


combinations has been below the setting parameter UPP< for more than
20 ms.
At least two of the phase voltages are below the setting parameter UPN<
for more than 20 ms.

The second part, phase preference evaluation, uses the internal signal
DetectCrossCountry from the voltage and current evaluation together with the
input signal STCND together with phase selection start condition (from phase
selection functions) connected to input STCND, and the information from the
setting parameter OperMode are used to determine the condition for trip. To
release the Phase preference logic, at least two out of three phases must be faulty.
The fault classification whether it is a single phase-to-earth, two-phase or crosscountry fault and which phase to be tripped at cross-country fault is converted into
a binary coded signal and sent to the distance protection measuring zone to release
the correct measuring zone according to the setting of OperMode. This is done by
activating the output ZREL and it shall be connected to the input STCND on the
distance zone measuring element.
The release signals from phase selection will only be gated with the cross-country
check from IN and UN but without time delay. If no phase selection start has
occurred, the release is based on current and voltage discriminating part only.
The input signal STCND consist of binary information of fault type and is
connected to the output STCND on phase selection function. The fault must be
activated in at least two phases to be classified as a cross-country fault in the phase
preference part of the logic.
The input signals RELxxx are additional fault release signals that can be connected
to external protection functions through binary input.
The output START and trip signals can be blocked by activating the input BLOCK

336
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

UL1
UL2
UL3

UL1UL2
UL2UL3
UL3UL1
IN

Voltage and
Current
Discrimination

UN
UPN<

START

AND

UPP<
IN>

Detect CrossCountry fault

UN0>

OperMode
RELL1N

Phase Preference
Evaluation

RELL2N

ZREL

AND

RELL3N
STCND

BLOCK

IEC09000220_1_en.vsd
IEC09000220 V2 EN

Figure 200:

6.15.3

Simplified block diagram for Phase preference logic

Function block
PPLPHIZ
I3P*
U3P*
BLOCK
RELL1N
RELL2N
RELL3N
STCND

START
ZREL

IEC07000029-2-en.vsd
IEC07000029 V2 EN

Figure 201:

6.15.4

PPLPHIZ function block

Input and output signals


Table 180:
Name

PPLPHIZ Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

Table continues on next page


337
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Name

Type

Release condition for the L1 to earth loop

RELL2N

BOOLEAN

Release condition for the L2 to earth loop

RELL3N

BOOLEAN

Release condition for the L3 to earth loop

STCND

INTEGER

Integer coded external release signals

PPLPHIZ Output signals

Name

Table 182:
Name

Description

BOOLEAN

Table 181:

6.15.5

Default

RELL1N

Type

Description

START

BOOLEAN

Indicates start for earth fault(s), regardless of


direction

ZREL

INTEGER

Integer coded output release signal

Setting parameters
PPLPHIZ Group settings (basic)
Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base current

UBase

0.05 - 2000.00

kV

0.01

400.00

Base voltage

OperMode

No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a

No Filter

Operating mode (c=cyclic,a=acyclic)

UPN<

10 - 100

%UB

70

Operate value of phase undervoltage in


% of UBase/sqrt(3)

UPP<

10 - 100

%UB

50

Operate value of line to line


undervoltage (% of UBase)

3U0>

5 - 300

%UB

20

Operate value of residual voltage in % of


UBase/sqrt(3)

IN>

10 - 200

%IB

20

Operate value of residual current (% of


IBase)

tUN

0.000 - 60.000

0.001

0.100

Pickup-delay for residual voltage

tOffUN

0.000 - 60.000

0.001

0.100

Dropoff-delay for residual voltage

tIN

0.000 - 60.000

0.001

0.150

Pickup-delay for residual current

338
Technical reference manual

Section 6
Impedance protection

1MRK 505 222-UEN B

Table 183:

PPLPHIZ technical data

Function

Range or value

Accuracy

Operate value, phase-to-phase


and phase-to-neutral
undervoltage

(10.0 - 100.0)% of UBase

0,5% of Ur

Reset ratio, undervoltage

< 105%

Operate value, residual voltage

(5.0 - 70.0)% of UBase

0,5% of Ur

Reset ratio, residual voltage

> 95%

Operate value, residual current

(10 - 200)% of IBase

1,0% of Ir for I < Ir


1,0% of I for I > Ir

Reset ratio, residual current

> 95%

Timers

(0.000 - 60.000) s

0,5% 10 ms

Operating mode

No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a,
312a, 321a

339
Technical reference manual

340

Section 7
Current protection

1MRK 505 222-UEN B

Section 7

Current protection

About this chapter


This chapter describes current protection functions. These include functions like
Instantaneous phase overcurrent protection, Four step phase overcurrent protection,
Pole discordance protection and Residual overcurrent protection.

7.1

Instantaneous phase overcurrent protection PHPIOC


Function description
Instantaneous phase overcurrent
protection

IEC 61850
identification

IEC 60617
identification

PHPIOC

ANSI/IEEE C37.2
device number
50

3I>>
SYMBOL-Z V1 EN

7.1.1

Introduction
The instantaneous three phase overcurrent function has a low transient overreach
and short tripping time to allow use as a high set short-circuit protection function.

7.1.2

Principle of operation
The sampled analogue phase currents are pre-processed in a discrete Fourier filter
(DFT) block. The RMS value of each phase current is derived from the
fundamental frequency components, as well as sampled values of each phase
current. These phase current values are fed to the instantaneous phase overcurrent
protection function PHPIOC. In a comparator the RMS values are compared to the
set operation current value of the function (IP>>). If a phase current is larger than
the set operation current a signal from the comparator for this phase is set to true.
This signal will, without delay, activate the output signal TRLn (n=1,2,3) for this
phase and the TRIP signal that is common for all three phases.
There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the
parameter is set to 1 out of 3 any phase trip signal will be activated. If the
parameter is set to 2 out of 3 at least two phase signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current
(StValMult) via a binary input (ENMULT). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.
341

Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

PHPIOC can be blocked from the binary input BLOCK.

7.1.3

Function block
PHPIOC
I3P*
BLOCK
ENMULT

TRIP
TRL1
TRL2
TRL3
IEC04000391-2-en.vsd

IEC04000391 V2 EN

Figure 202:

7.1.4

PHPIOC function block

Input and output signals


Table 184:

PHPIOC Input signals

Name

Type

Three phase current

BLOCK

BOOLEAN

Block of function

ENMULT

BOOLEAN

Enable current start value multiplier

PHPIOC Output signals

Name

Table 186:
Name

Description

GROUP
SIGNAL

Table 185:

7.1.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip signal from any phase

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

Setting parameters
PHPIOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

OpMode

2 out of 3
1 out of 3

1 out of 3

Select operation mode 2-out of 3 / 1-out


of 3

IP>>

1 - 2500

%IB

200

Operate phase current level in % of IBase

Table 187:
Name
StValMult

PHPIOC Group settings (advanced)


Values (Range)
0.5 - 5.0

Unit
-

Step
0.1

Default
1.0

Description
Multiplier for operate current level

342
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.1.6

Technical data
Table 188:

PHPIOC technical data

Function

7.2

Range or value

Accuracy

Operate current

(1-2500)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Operate time

25 ms typically at 0 to 2 x Iset

Reset time

25 ms typically at 2 to 0 x Iset

Critical impulse time

10 ms typically at 0 to 2 x Iset

Operate time

10 ms typically at 0 to 10 x Iset

Reset time

35 ms typically at 10 to 0 x Iset

Critical impulse time

2 ms typically at 0 to 10 x Iset

Dynamic overreach

< 5% at t = 100 ms

Four step phase overcurrent protection OC4PTOC


Function description
Four step phase overcurrent protection

IEC 61850
identification

IEC 60617
identification

OC4PTOC

3I>
4
4

ANSI/IEEE C37.2
device number
51/67

alt

TOC-REVA V1 EN

7.2.1

Introduction
The four step phase overcurrent protection function OC4PTOC has an inverse or
definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always
definite time delayed.
All IEC and ANSI inverse time characteristics are available together with an
optional user defined time characteristic.
The directional function is voltage polarized with memory. The function can be set
to be directional or non-directional independently for each of the steps.
A 2nd harmonic blocking can be set individually for each step.

7.2.2

Principle of operation
The Four step overcurrent protection function OC4PTOC is divided into four
different sub-functions, one for each step. For each step x , where x is step 1, 2, 3
343

Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

and 4, an operation mode is set by DirModex: Off/Non-directional/Forward/


Reverse.
The protection design can be decomposed in four parts:

The direction element


The harmonic Restraint Blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModex shall be left to default value, Non-directional.

faultState

Direction
Element

I3P

dirPh1Flt
dirPh2Flt
dirPh3Flt

4 step over current


element
One element for each
step

faultState

START

U3P

TRIP

I3P

Harmonic
Restraint
Element

harmRestrBlock

enableDir
Mode Selection

enableStep1-4
DirectionalMode1-4

en05000740.vsd
IEC05000740 V1 EN

Figure 203:

Functional overview of OC4PTOC

A common setting for all steps, StartPhSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out
of 3 or 3 out of 3.

344
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

The sampled analogue phase currents are processed in a pre-processing function


block. Using a parameter setting MeasType within the general settings for the four
step phase overcurrent protection function OC4PTOC, it is possible to select the
type of the measurement used for all overcurrent stages. It is possible to select
either discrete Fourier filter (DFT) or true RMS filter (RMS).
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component
and higher harmonic current components are almost completely suppressed. If
RMS option is selected then the true RMS values is used. The true RMS value in
addition to the fundamental frequency component includes the contribution from
the current DC component as well as from higher current harmonic. The selected
current values are fed to OC4PTOC.
In a comparator, for each phase current, the DFT or RMS values are compared to
the set operation current value of the function (I1>, I2>, I3> or I4>). If a phase
current is larger than the set operation current, outputs START, STx, STL1, STL2
and STL3 are, without delay, activated. Output signals STL1, STL2 and STL3 are
common for all steps. This means that the lowest set step will initiate the
activation. The START signal is common for all three phases and all steps. It shall
be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.
Service value for individually measured phase currents are also available on the
local HMI for OC4PTOC function, which simplifies testing, commissioning and in
service operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and the relation is compared to a set
restrain current level.
The function can be directional. The direction of the fault current is given as
current angle in relation to the voltage angle. The fault current and fault voltage for
the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
voltage is a combination of the apparent voltage (85%) and a memory voltage
(15%). The following combinations are used.
Phase-phase short circuit:

U refL1L 2 = U L1 - U L 2

I dirL1L 2 = I L1 - I L 2
(Equation 76)

EQUATION1449 V1 EN

U refL 2 L 3 = U L 2 - U L 3

I dirL 2 L 3 = I L 2 - I L 3
(Equation 77)

EQUATION1450 V1 EN

U refL 3 L1 = U L 3 - U L1
EQUATION1451 V1 EN

I dirL 3 L1 = I L 3 - I L1
(Equation 78)

Table continues on next page

345
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Phase-earth short circuit:

U refL1 = U L1

I dirL1 = I L1
(Equation 79)

EQUATION1452 V1 EN

U refL 2 = U L 2

I dirL 2 = I L 2
(Equation 80)

EQUATION1453 V1 EN

U refL 3 = U L 3

I dirL 3 = I L 3

EQUATION1454 V1 EN

(Equation 81)

The polarizing voltage is available as long as the positive-sequence voltage


exceeds 4% of the set base voltage UBase. So the directional element can use it for
all unsymmetrical faults including close-in faults.
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
After 100 ms, the following occurs:

If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition
seals in.

If the fault has caused tripping, the trip endures.


If the fault was detected in the reverse direction, the measuring element
in the reverse direction remains in operation.

If the current decreases below the minimum operating value, the memory
resets until the positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function
and an angle window AngleROA.

346
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Reverse

Uref
RCA

ROA

ROA

Forward

Idir

en05000745.vsd
IEC05000745 V1 EN

Figure 204:

Directional characteristic of the phase overcurrent protection

The default value of AngleRCA is 65. The parameters AngleROA gives the angle
sector from AngleRCA for directional borders.
A minimum current for directional phase start current signal can be set:
IminOpPhSel.
If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is
available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in section "Inverse
characteristics".
All four steps in OC4PTOC can be blocked from the binary input BLOCK. The
binary input BLKSTx (x=1, 2, 3 or 4) blocks the operation of respective step.
Different types of reset time can be selected as described in section "Inverse
characteristics".
There is also a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the
set operation current via a binary input (enable multiplier). In some applications the
operation value needs to be changed, for example due to changed network
switching state. The function can be blocked from the binary input BLOCK. The
start signals from the function can be blocked from the binary input BLKST. The
trip signals from the function can be blocked from the binary input BLKTR.
347
Technical reference manual

Section 7
Current protection
7.2.3

1MRK 505 222-UEN B

Function block
OC4PTOC
I3P*
U3P*
BLOCK
BLKTR
BLKST1
BLKST2
BLKST3
BLKST4
ENMULT1
ENMULT2
ENMULT3
ENMULT4

TRIP
TR1
TR2
TR3
TR4
TRL1
TRL2
TRL3
TR1L1
TR1L2
TR1L3
TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
2NDHARM
DIRL1
DIRL2
DIRL3
IEC06000187-2-en.vsd

IEC06000187 V2 EN

Figure 205:

7.2.4

OC4PTOC function block

Input and output signals


Table 189:
Name

OC4PTOC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

BLKST1

BOOLEAN

Block of Step1

BLKST2

BOOLEAN

Block of Step2

Table continues on next page

348
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Type

Default

Description

BLKST3

BOOLEAN

Block of Step3

BLKST4

BOOLEAN

Block of Step4

ENMULT1

BOOLEAN

When activated, the current multiplier is in use for


step1

ENMULT2

BOOLEAN

When activated, the current multiplier is in use for


step2

ENMULT3

BOOLEAN

When activated, the current multiplier is in use for


step3

ENMULT4

BOOLEAN

When activated, the current multiplier is in use for


step4

Table 190:
Name

OC4PTOC Output signals


Type

Description

TRIP

BOOLEAN

Trip

TR1

BOOLEAN

Common trip signal from step1

TR2

BOOLEAN

Common trip signal from step2

TR3

BOOLEAN

Common trip signal from step3

TR4

BOOLEAN

Common trip signal from step4

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TR1L1

BOOLEAN

Trip signal from step1 phase L1

TR1L2

BOOLEAN

Trip signal from step1 phase L2

TR1L3

BOOLEAN

Trip signal from step1 phase L3

TR2L1

BOOLEAN

Trip signal from step2 phase L1

TR2L2

BOOLEAN

Trip signal from step2 phase L2

TR2L3

BOOLEAN

Trip signal from step2 phase L3

TR3L1

BOOLEAN

Trip signal from step3 phase L1

TR3L2

BOOLEAN

Trip signal from step3 phase L2

TR3L3

BOOLEAN

Trip signal from step3 phase L3

TR4L1

BOOLEAN

Trip signal from step4 phase L1

TR4L2

BOOLEAN

Trip signal from step4 phase L2

TR4L3

BOOLEAN

Trip signal from step4 phase L3

START

BOOLEAN

General start signal

ST1

BOOLEAN

Common start signal from step1

ST2

BOOLEAN

Common start signal from step2

ST3

BOOLEAN

Common start signal from step3

ST4

BOOLEAN

Common start signal from step4

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

Table continues on next page

349
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

7.2.5
Table 191:
Name

Type

Description

STL3

BOOLEAN

Start signal from phase L3

ST1L1

BOOLEAN

Start signal from step1 phase L1

ST1L2

BOOLEAN

Start signal from step1 phase L2

ST1L3

BOOLEAN

Start signal from step1 phase L3

ST2L1

BOOLEAN

Start signal from step2 phase L1

ST2L2

BOOLEAN

Start signal from step2 phase L2

ST2L3

BOOLEAN

Start signal from step2 phase L3

ST3L1

BOOLEAN

Start signal from step3 phase L1

ST3L2

BOOLEAN

Start signal from step3 phase L2

ST3L3

BOOLEAN

Start signal from step3 phase L3

ST4L1

BOOLEAN

Start signal from step4 phase L1

ST4L2

BOOLEAN

Start signal from step4 phase L2

ST4L3

BOOLEAN

Start signal from step4 phase L3

2NDHARM

BOOLEAN

Block from second harmonic detection

DIRL1

INTEGER

Direction for phase1

DIRL2

INTEGER

Direction for phase2

DIRL3

INTEGER

Direction for phase3

Setting parameters
OC4PTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

AngleRCA

40 - 65

Deg

55

Relay characteristic angle (RCA)

AngleROA

40 - 89

Deg

80

Relay operation angle (ROA)

StartPhSel

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of


3, 2 of 3, 3 of 3)

DirMode1

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (off, nodir,


forward, reverse)

Table continues on next page

350
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for


step 1

I1>

1 - 2500

%IB

1000

Phase current operate level for step1 in


% of IBase

t1

0.000 - 60.000

0.001

0.000

Definitive time delay of step 1

k1

0.05 - 999.00

0.01

0.05

Time multiplier for the inverse time delay


for step 1

IMin1

1 - 10000

%IB

100

Minimum operate current for step1 in %


of IBase

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 1

I1Mult

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for


step 1

DirMode2

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (off, nodir,


forward, reverse)

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for


step 2

I2>

1 - 2500

%IB

500

Phase current operate level for step2 in


% of IBase

t2

0.000 - 60.000

0.001

0.400

Definitive time delay of step 2

Table continues on next page

351
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Step

Default

k2

0.05 - 999.00

Unit
-

0.01

0.05

Description
Time multiplier for the inverse time delay
for step 2

IMin2

1 - 10000

%IB

50

Minimum operate current for step2 in %


of IBase

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 2

I2Mult

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for


step 2

DirMode3

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (off, nodir,


forward, reverse)

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for


step 3

I3>

1 - 2500

%IB

250

Phase current operate level for step3 in


% of IBase

t3

0.000 - 60.000

0.001

0.800

Definitive time delay of step 3

k3

0.05 - 999.00

0.01

0.05

Time multiplier for the inverse time delay


for step 3

IMin3

1 - 10000

%IB

33

Minimum operate current for step3 in %


of IBase

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 3

I3Mult

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for


step 3

DirMode4

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (off, nodir,


forward, reverse)

Table continues on next page

352
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for


step 4

I4>

1 - 2500

%IB

175

Phase current operate level for step4 in


% of IBase

t4

0.000 - 60.000

0.001

2.000

Definitive time delay of step 4

k4

0.05 - 999.00

0.01

0.05

Time multiplier for the inverse time delay


for step 4

IMin4

1 - 10000

%IB

17

Minimum operate current for step4 in %


of IBase

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 4

I4Mult

1.0 - 10.0

0.1

2.0

Multiplier for current operate level for


step 4

Table 192:

OC4PTOC Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

IMinOpPhSel

1 - 100

%IB

Minimum current for phase selection in


% of IBase

2ndHarmStab

5 - 100

%IB

20

Operate level of 2nd harm restrain op in


% of Fundamental

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 1

tReset1

0.000 - 60.000

0.001

0.020

Reset time delay used in IEC Definite


Time curve step 1

tPCrv1

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 1

tPRCrv1

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 1

Table continues on next page

353
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

tTRCrv1

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 1

tCRCrv1

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 1

HarmRestrain1

Off
On

Off

Enable block of step 1 from harmonic


restrain

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 2

tReset2

0.000 - 60.000

0.001

0.020

Reset time delay used in IEC Definite


Time curve step 2

tPCrv2

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 2

tCCrv2

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 2

tPRCrv2

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 2

HarmRestrain2

Off
On

Off

Enable block of step 2 from harmonic


restrain

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 3

tReset3

0.000 - 60.000

0.001

0.020

Reset time delay used in IEC Definite


Time curve step 3

tPCrv3

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 3

tPRCrv3

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 3

HarmRestrain3

Off
On

Off

Enable block of step3 from harmonic


restrain

Table continues on next page

354
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for step 4

tReset4

0.000 - 60.000

0.001

0.020

Reset time delay used in IEC Definite


Time curve step 4

tPCrv4

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 4

tCCrv4

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 4

HarmRestrain4

Off
On

Off

Enable block of step 4 from harmonic


restrain

Table 193:

OC4PTOC Non group settings (basic)

Name
MeasType

7.2.6

Values (Range)
DFT
RMS

Unit

Step

Default
DFT

Description
Selection between DFT and RMS
measurement

Technical data
Table 194:

OC4PTOC technical data

Function

Setting range

Accuracy

Operate current

(1-2500)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Min. operating current

(1-100)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Relay characteristic angle (RCA)

(-70.0 -50.0) degrees

2.0 degrees

Maximum forward angle

(40.070.0) degrees

2.0 degrees

Minimum forward angle

(75.090.0) degrees

2.0 degrees

2nd harmonic blocking

(5100)% of fundamental

2.0% of Ir

Independent time delay

(0.000-60.000) s

0.5% 10 ms

Minimum operate time

(0.000-60.000) s

0.5% 10 ms

Table continues on next page

355
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Function

7.3

Setting range

Accuracy

Inverse characteristics, see


table 722, table 723 and table
724

19 curve types

See table 722, table 723 and


table 724

Operate time, start function

25 ms typically at 0 to 2 x Iset

Reset time, start function

25 ms typically at 2 to 0 x Iset

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Instantaneous residual overcurrent protection


EFPIOC
Function description
Instantaneous residual overcurrent
protection

IEC 61850
identification

IEC 60617
identification

EFPIOC

ANSI/IEEE C37.2
device number
50N

IN>>
IEF V1 EN

7.3.1

Introduction
The Instantaneous residual overcurrent protection EFPIOC has a low transient
overreach and short tripping times to allow the use for instantaneous earth-fault
protection, with the reach limited to less than the typical eighty percent of the line
at minimum source impedance. EFPIOC can be configured to measure the residual
current from the three-phase current inputs or the current from a separate current
input. EFPIOC can be blocked by activating the input BLOCK.

7.3.2

Principle of operation
The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current,
as well as from the sample values the equivalent RMS value is derived. This
current value is fed to the Instantaneous residual overcurrent protection (EFPIOC).
In a comparator the RMS value is compared to the set operation current value of
the function (IN>>). If the residual current is larger than the set operation current a
signal from the comparator is set to true. This signal will, without delay, activate
the output signal TRIP.
There is also a possibility to activate a preset change of the set operation current
via a binary input (enable multiplier MULTEN). In some applications the operation
value needs to be changed, for example due to transformer inrush currents.

356
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

EFPIOC function can be blocked from the binary input BLOCK. The trip signals
from the function can be blocked from the binary input BLKAR, that can be
activated during single pole trip and autoreclosing sequences.

7.3.3

Function block
EFPIOC
I3P*
BLOCK
BLKAR
MULTEN

TRIP

IEC06000269-2-en.vsd
IEC06000269 V2 EN

Figure 206:

7.3.4

EFPIOC function block

Input and output signals


Table 195:

EFPIOC Input signals

Name

Type

Three phase currents

BLOCK

BOOLEAN

Block of function

BLKAR

BOOLEAN

Block input for auto reclose

MULTEN

BOOLEAN

Enable current multiplier

EFPIOC Output signals

Name

Type

TRIP

Table 197:

Description

GROUP
SIGNAL

Table 196:

7.3.5

Default

I3P

Description

BOOLEAN

Trip signal

Setting parameters
EFPIOC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

IN>>

1 - 2500

%IB

200

Operate residual current level in % of


IBase

Table 198:

EFPIOC Group settings (advanced)

Name
StValMult

Values (Range)
0.5 - 5.0

Unit
-

Step
0.1

Default
1.0

Description
Multiplier for operate current level

357
Technical reference manual

Section 7
Current protection
7.3.6

1MRK 505 222-UEN B

Technical data
Table 199:

EFPIOC technical data

Function

7.4

Range or value

Accuracy

Operate current

(1-2500)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Operate time

25 ms typically at 0 to 2 x Iset

Reset time

25 ms typically at 2 to 0 x Iset

Critical impulse time

10 ms typically at 0 to 2 x Iset

Operate time

10 ms typically at 0 to 10 x Iset

Reset time

35 ms typically at 10 to 0 x Iset

Critical impulse time

2 ms typically at 0 to 10 x Iset

Dynamic overreach

< 5% at t = 100 ms

Four step residual overcurrent protection EF4PTOC


Function description
Four step residual overcurrent
protection

IEC 61850
identification

IEC 60617
identification

EF4PTOC

51N/67N

IN
4
4

ANSI/IEEE C37.2
device number

alt

TEF-REVA V1 EN

7.4.1

Introduction
The four step residual overcurrent protection EF4PTOC has an inverse or definite
time delay independent for each step separately.
All IEC and ANSI time-delayed characteristics are available together with an
optional user defined characteristic.
The directional function includes 3 options

voltage polarized
current polarized
dual polarized

EF4PTOC can be set directional or non-directional independently for each of the


steps.
Second harmonic blocking can be set individually for each step.

358
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

EF4PTOC can be used as main protection for phase-to-earth faults.


EF4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.
Directional operation can be combined together with corresponding
communication logic in permissive or blocking teleprotection scheme. Current
reversal and weak-end infeed functionality are available as well.
EF4PTOC can be configured to measure the residual current from the three-phase
current inputs or the current from a separate current input.

7.4.2

Principle of operation
This function has the following three Analog Inputs on its function block in the
configuration tool:
1.
2.
3.

I3P, input used for Operating Quantity.


U3P, input used for Voltage Polarizing Quantity.
I3PPOL, input used for Current Polarizing Quantity.

These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.

7.4.2.1

Operating quantity within the function


The function always uses Residual Current (3I0) for its operating quantity. The
residual current can be:
1.

directly measured (when a dedicated CT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input I3P). This dedicated IED CT input can be for
example, connected to:

2.

parallel connection of current instrument transformers in all three phases


(Holm-Green connection).
one single core balance, current instrument transformer (cable CT).
one single current instrument transformer located between power system
star point and earth (that is, current transformer located in the star point
of a star connected transformer winding).
one single current instrument transformer located between two parts of a
protected object (that is, current transformer located between two star
points of double star shunt capacitor bank).

calculated from three-phase current input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC function
Analog Input I3P is not connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I0 from the
first three inputs into the pre-processing block by using the following formula:
359

Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Iop = 3I0 = IL1 + IL2 + IL3


(Equation 82)

EQUATION1874 V2 EN

where:
IL1, IL2 and IL3

are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of
the fundamental frequency component of the residual current is derived. The
phasor magnitude is used within the EF4PTOC protection to compare it with the
set operation current value of the four steps (IN1>, IN2>, IN3> or IN4>). If the
residual current is larger than the set operation current and the step is used in nondirectional mode a signal from the comparator for this step is set to true. This
signal will, without delay, activate the output signal STINx (x=step 1-4) for this
step and a common START signal.

7.4.2.2

Internal polarizing
A polarizing quantity is used within the protection in order to determine the
direction to the earth fault (Forward/Reverse).
The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected the protection will use the residual voltage
-3U0 as polarizing quantity U3P. This voltage can be:
1.

2.

directly measured (when a dedicated VT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input U3P). This dedicated IED VT input shall be then
connected to open delta winding of a three phase main VT.
calculated from three phase voltage input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC analog
function input U3P is NOT connected to a dedicated VT input of the IED in
PCM600). In such case the pre-processing block will calculate -3U0 from the
first three inputs into the pre-processing block by using the following formula:

UPol = -3U 0 = -(UL1 + UL2 + UL3)


EQUATION1875 V2 EN

(Equation 83)

where:
UL1, UL2 and UL3

are fundamental frequency phasors of three individual phase voltages.

Note! In order to use this all three phase-to-earth voltages must be connected to three IED VT inputs.

360
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor
of the fundamental frequency component of the residual voltage is derived. This
phasor is used together with the phasor of the operating current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable
voltage polarizing the magnitude of polarizing voltage shall be bigger than a
minimum level defined by setting parameter UpolMin.
It shall be noted that 3U0 is used to determine the location of the earth fault. This
insures the required inversion of the polarizing voltage within the earth-fault function.

Current polarizing
When current polarizing is selected the function will use the residual current (3I0)
as polarizing quantity IPol. This current can be:
1.

directly measured (when a dedicated CT input of the IED is connected in


PCM600 to the fourth analog input of the pre-processing block connected to
EF4PTOC function input I3PPOL). This dedicated IED CT input is then
typically connected to one single current transformer located between power
system star point and earth (current transformer located in the star point of a
star connected transformer winding).

2.

For some special line protection applications this dedicated IED CT


input can be connected to parallel connection of current transformers in
all three phases (Holm-Green connection)

calculated from three phase current input within the IED (when the fourth
analog input into the pre-processing block connected to EF4PTOC function
analog input I3PPOL is NOT connected to a dedicated CT input of the IED in
PCM600). In such case the pre-processing block will calculate 3I0 from the
first three inputs into the pre-processing block by using the following formula:

IPol = 3I0 = IL1 + IL2 + IL3


EQUATION2018 V2 EN

(Equation 84)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual polarizing current is pre-processed by a discrete fourier filter. Thus


the phasor of the fundamental frequency component of the residual current is
derived. This phasor is then multiplied with pre-set equivalent zero-sequence
source Impedance in order to calculate equivalent polarizing voltage UIPol in
accordance with the following formula:
UIPol = Z 0s IPol = (RNPol + j XNPol) IPol
EQUATION1877 V2 EN

(Equation 85)

361
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

which will be then used, together with the phasor of the operating current, in order
to determine the direction to the earth fault (Forward/Reverse). In order to enable
current polarizing the magnitude of polarizing current shall be bigger than a
minimum level defined by setting parameter IPolMin.

Dual polarizing
When dual polarizing is selected the function will use the vectorial sum of the
voltage based and current based polarizing in accordance with the following formula:
UTotPol = UUPol + UIPol = -3U 0 + Z 0 s IPol = -3U 0 + ( RNPol + jXNPol ) IPol
EQUATION1878 V3 EN

(Equation 86)

Then the phasor of the total polarizing voltage UTotPol will be used, together with
the phasor of the operating current, to determine the direction of the earth fault
(Forward/Reverse).

7.4.2.3

External polarizing for earth-fault function


The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx to provide
external directional control (that is, torque control) by for example using one of the
following functions if available in the IED:
1.
2.

7.4.2.4

Distance protection directional function.


Negative sequence polarized General current and voltage multi purpose
protection function.

Base quantities within the protection


The base quantities shall be entered as setting parameters for every earth-fault
function. Base current (IBase) shall be entered as rated phase current of the
protected object in primary amperes. Base voltage (UBase) shall be entered as
rated phase-to-phase voltage of the protected object in primary kV.

7.4.2.5

Internal earth-fault protection structure


The protection is internally divided into the following parts:
1.
2.
3.
4.

Four residual overcurrent steps.


Directional supervision element for residual overcurrent steps with integrated
directional comparison step for communication based earth-fault protection
schemes (permissive or blocking).
Second harmonic blocking element with additional feature for sealed-in
blocking during switching of parallel transformers.
Switch on to fault feature with integrated Under-Time logic for detection of
breaker problems during breaker opening or closing sequence.

362
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Each part is described separately in the following sections.

7.4.2.6

Four residual overcurrent steps


Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:

Directional mode can be set to Off/Non-directional/Forward/Reverse. By this


parameter setting the directional mode of the step is selected. It shall be noted
that the directional decision (Forward/Reverse) is not made within the residual
overcurrent step itself. The direction of the fault is determined in common
directional supervision element.
Residual current start value.
Type of operating characteristic (inverse or definite time). By this parameter
setting it is possible to select inverse or definite time delay for the earth-fault
protection. Most of the standard IEC and ANSI inverse characteristics are
available. For the complete list of available inverse curves please refer to
section "Inverse characteristics".
Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this
parameter setting it is possible to select the reset characteristic of the step. For
the complete list of available reset curves please refer to section "Inverse time
characteristics".
Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves, reset time
delay and parameters to define user programmable inverse curve are defined.
Supervision by second harmonic blocking feature (On/Off). By this parameter
setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
Multiplier for scaling of the set residual current pickup value by external
binary signal. By this parameter setting it is possible to increase residual
current pickup value when function binary input ENMULTx has logical value
1.

Simplified logic diagram for one residual overcurrent step is shown in figure 207.

363
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

BLKTR
IMinx

Characteristx=DefTime

a>b

tx

|IOP|

AND

TRINx

OR

a>b

INxMult

STINx

AND

T
F

INx>

AND

Inverse

tMin

BLKSTx
BLOCK

Characteristx=Inverse
2ndHarm_BLOCK_Int

OR

HarmRestrainx=Off
DirModex=Off

OR

STEPx_DIR_Int

DirModex=Non-directional
DirModex=Forward
DirModex=Reverse

FORWARD_Int

REVERSE_Int

AND

OR

AND

IEC10000008-1-en.vsd

IEC10000008 V1 EN

Figure 207:

Simplified logic diagram for residual overcurrent step x, where x =


step 1, 2, 3 or 4

The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, STINx and TRINx, can be blocked from the binary
input BLKSTx. The trip signals from the function can be blocked from the binary
input BLKTR.

7.4.2.7

Directional supervision element with integrated directional


comparison function
It shall be noted that at least one of the four residual overcurrent
steps shall be set as directional in order to enable execution of the
directional supervision element and the integrated directional
comparison function.
The protection has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the parameter setting
polMethod. The polarizing quantity will be selected by the function in one of the
following three ways:
1.
2.
3.

When polMethod = Voltage, UPol will be used as polarizing quantity.


When polMethod = Current, IPol will be used as polarizing quantity.
WhenpolMethod = Dual, UPol + IPol ZNPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element,
as shown in figure 208, in order to determine the direction of the earth fault.

364
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Operating area

STRV
0.6 * IN>DIR

Characteristic for reverse


release of measuring steps
-RCA -85 deg

Characteristic
for STRV

40% of
IN>DIR

RCA +85 deg

RCA
65

Upol = -3U 0

-RCA +85 deg

RCA -85 deg

Characteristic for forward


release of measuring steps

IN>DIR

STFW
I op = 3I0
Operating area
Characteristic
for STFW

IEC11000243-1-en.ai

IEC11000243 V1 EN

Figure 208:

Operating characteristic for earth-fault directional element

Two relevant setting parameters for directional supervision element are:

Directional element will be internally enabled to operate as soon as Iop is


bigger than 40% of IN>Dir and directional condition is fulfilled in set direction.
Relay characteristic angle AngleRCA, which defines the position of forward
and reverse areas in the operating characteristic.

Directional comparison step, built-in within directional supervision element, will


set EF4PTOC function output binary signals:
1.
2.

STFW=1 when operating quantity magnitude Iop x cos( - AngleRCA) is


bigger than setting parameterIN>Dir and directional supervision element
detects fault in forward direction.
STRV=1 when operating quantity magnitude Iop x cos( - AngleRCA) is
bigger than 60% of setting parameter IN>Dir and directional supervision
element detects fault in reverse direction.

These signals shall be used for communication based earth-fault teleprotection


communication schemes (permissive or blocking).

365
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Simplified logic diagram for directional supervision element with integrated


directional comparison step is shown in figure 209:
|Iop|

a
b

0.6

a>b

REVERSE_Int

X
a

IN>Dir

0.4

STRV

AND

a>b

FORWARD_Int

STFW

AND

FWD
polMethod=Voltage

OR

polMethod=Dual

UPolMin
UPol

polMethod=Current

OR
IPol
0.0
RNPol
XNPol

T
0.0 F

IPolMin
Iop
UTotPol

T
F

Complex
Number

RVS

UIPol
0.0

T
F

AND

FORWARD_Int

AND

REVERSE_Int

Directional
Characteristic

AngleRCA

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int
STAGE4_DIR_Int

OR
AND

BLOCK

IEC07000067-4-en.vsd
IEC07000067 V4 EN

Figure 209:

7.4.2.8

Simplified logic diagram for directional supervision element with integrated directional
comparison step

Second harmonic blocking element


A harmonic restrain of the Four step residual overcurrent protection function
EF4PTOC can be chosen. If the ratio of the 2nd harmonic component in relation to
the fundamental frequency component in the residual current exceeds the pre-set
level (defined by parameter setting 2ndHarmStab) any of the four residual
overcurrent stages can be selectively blocked by a parameter setting
HarmRestrainx. When 2nd harmonic restraint feature is active the EF4PTOC
function output signal 2NDHARMD will be set to logical value one.
In addition to the basic functionality explained above the 2nd harmonic blocking
can be set in such way to seal-in until residual current disappears. This feature

366
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

might be required to stabilize EF4PTOC during switching of parallel transformers


in the station. In case of parallel transformers there is a risk of sympathetic inrush
current. If one of the transformers is in operation, and the parallel transformer is
switched in, the asymmetric inrush current of the switched in transformer will
cause partial saturation of the transformer already in service. This is called
transferred saturation. The 2nd harmonic of the inrush currents of the two
transformers will be in phase opposition. The summation of the two currents will
thus give a small 2nd harmonic current. The residual fundamental current will
however be significant. The inrush current of the transformer in service before the
parallel transformer energizing, will be a little delayed compared to the first
transformer. Therefore we will have high 2nd harmonic current component initially.
After a short period this current will however be small and the normal 2nd
harmonic blocking will reset. If the BlkParTransf function is activated the 2nd
harmonic restrain signal will be latched as long as the residual current measured by
the relay is larger than a selected step current level.
This feature has been called Block for Parallel Transformers. This 2nd harmonic sealin feature will be activated when all of the following three conditions are
simultaneously fulfilled:
1.
2.
3.

Feature is enabled by entering setting parameter BlkParTransf = On.


Basic 2nd harmonic restraint feature has been active for at least 70ms.
Residual current magnitude is higher than the set start value for one of the four
residual overcurrent stages. By a parameter setting UseStartValue it is possible
to select which one of the four start values that will be used (IN1> or IN2> or
IN3> or IN4>).

Once Block for Parallel Transformers is activated the basic 2nd harmonic blocking
signal will be sealed-in until the residual current magnitude falls below a value
defined by parameter setting UseStartValue (see condition 3 above).
Simplified logic diagram for 2nd harmonic blocking feature is shown in figure 210.

367
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

BLOCK

Extract second
harmonic current
component

IOP

2ndHarmStab

2NDHARMD

OR

a>b

Extract
fundamental
current component

q-1

t=70ms
t

OR

AN
D

OR

2ndH_BLOCK_Int

BlkParTransf=On
|IOP|

UseStartValue

a>b

IN1>
IN2>
IN3>
IN4>
en07000068-2.vsd
IEC07000068 V2 EN

Figure 210:

7.4.2.9

Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel Transformers
feature

Switch on to fault feature


Integrated in the four step residual overcurrent protection are Switch on to fault
logic (SOTF) and Under-Time logic. The setting parameter SOTF is set to activate
either SOTF or Under-Time logic or both. When the circuit breaker is closing there
is a risk to close it onto a permanent fault, for example during an autoreclosing
sequence. The SOTF logic will enable fast fault clearance during such situations.
The time during which SOTF and Under-Time logics will be active after activation
is defined by the setting parameter t4U.
The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected
by setting parameter StepForSOTF. The SOTF logic can be activated either from
change in circuit breaker position or from circuit breaker close command pulse.
The setting parameter ActivationSOTF can be set for activation of CB position
open change, CB position closed change or CB close command. In case of a
residual current start from step 2 or 3 (dependent on setting) the function will give
a trip after a set delay tSOTF. This delay is normally set to a short time (default 200
ms).
The Under-Time logic always uses the start signal from the step 4. The UnderTime logic will normally be set to operate for a lower current level than the SOTF

368
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

function. The Under-Time logic can also be blocked by the 2nd harmonic restraint
feature. This enables high sensitivity even if power transformer inrush currents can
occur at breaker closing. This logic is typically used to detect asymmetry of CB
poles immediately after switching of the circuit breaker. The Under-Time logic is
activated either from change in circuit breaker position or from circuit breaker
close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set
delay tUnderTime. This delay is normally set to a relatively short time (default 300
ms). Practically the Under-Time logic acts as circuit breaker pole-discordance
protection, but it is only active immediately after breaker switching. The UnderTime logic can only be used in solidly or low impedance grounded systems.
SOTF

Open
tPulse
Closed

ActivationSOTF

Close command

tSOTF
AND

STIN2

AND

StepForSOTF

STIN3

OperationMode
BLOCK

OFF
SOTF

UNDERTIME

TRIP

UnderTime
tUnderTime

2nd Harmonic

HarmResSOFT

AND

SOTF or
UnderTime

OR

Open
OR

Close

tPulse
Close command

ActUnderTime

AND

STIN4
IEC06000643-2-en.vsd
IEC06000643 V2 EN

Figure 211:

Simplified logic diagram for SOTF and Under-Time features

EF4PTOC Logic Diagram Simplified logic diagram for the complete EF4PTOC
function is shown in figure 212:

369
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

signal to
communication
scheme

Directional Check
Element

INPol

Direction
Element

3U0

4 step over current


element
One element for each
step

operatingCurrent
earthFaultDirection

3I0

TRIP

angleValid

DirMode
enableDir

3I0

Harmonic
Restraint
Element

harmRestrBlock

start step 2, 3 and


4
Blocking at parallel
transformers
SwitchOnToFault

Mode
Selection

DirMode
enableDir

TRIP

CB
pos
or cmd

enableStep1-4
DirectionalMode1-4
en06000376.vsd

IEC06000376 V1 EN

Figure 212:

7.4.3

Functional overview of EF4PTOC

Function block
EF4PTOC
I3P*
U3P*
I3PPOL*
BLOCK
BLKTR
BLKST1
BLKST2
BLKST3
BLKST4
ENMULT1
ENMULT2
ENMULT3
ENMULT4
CBPOS
CLOSECB
OPENCB

TRIP
TRIN1
TRIN2
TRIN3
TRIN4
TRSOTF
START
STIN1
STIN2
STIN3
STIN4
STSOTF
STFW
STRV
2NDHARMD

IEC06000424-2-en.vsd
IEC06000424 V2 EN

Figure 213:

EF4PTOC function block

370
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.4.4

Input and output signals


Table 200:
Name

EF4PTOC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three Phase Current Group Connection

U3P

GROUP
SIGNAL

Three Phase Voltage Group Connection

I3PPOL

GROUP
SIGNAL

Three Phase Polarisation Current

BLOCK

BOOLEAN

General block

BLKTR

BOOLEAN

Block of trip

BLKST1

BOOLEAN

Block of step 1 (Start and trip)

BLKST2

BOOLEAN

Block of step 2 (Start and trip)

BLKST3

BOOLEAN

Block of step 3 (Start and trip)

BLKST4

BOOLEAN

Block of step 4 (Start and trip)

ENMULT1

BOOLEAN

When activated, the current multiplier is in use for


step1

ENMULT2

BOOLEAN

When activated, the current multiplier is in use for


step2

ENMULT3

BOOLEAN

When activated, the current multiplier is in use for


step3

ENMULT4

BOOLEAN

When activated, the current multiplier is in use for


step4

CBPOS

BOOLEAN

Breaker position

CLOSECB

BOOLEAN

Breaker close command

OPENCB

BOOLEAN

Breaker open command

Table 201:
Name

EF4PTOC Output signals


Type

Description

TRIP

BOOLEAN

Trip

TRIN1

BOOLEAN

Trip signal from step 1

TRIN2

BOOLEAN

Trip signal from step 2

TRIN3

BOOLEAN

Trip signal from step 3

TRIN4

BOOLEAN

Trip signal from step 4

TRSOTF

BOOLEAN

Trip signal from earth fault switch onto fault function

START

BOOLEAN

General start signal

STIN1

BOOLEAN

Start signal step 1

STIN2

BOOLEAN

Start signal step 2

STIN3

BOOLEAN

Start signal step 3

STIN4

BOOLEAN

Start signal step 4

STSOTF

BOOLEAN

Start signal from earth fault switch onto fault


function

Table continues on next page

371
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

7.4.5
Table 202:
Name

Type

Description

STFW

BOOLEAN

Forward directional start signal

STRV

BOOLEAN

Reverse directional start signal

2NDHARMD

BOOLEAN

2nd harmonic block signal

Setting parameters
EF4PTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base value for current settings

UBase

0.05 - 2000.00

kV

0.05

400

Base value for voltage settings

AngleRCA

-180 - 180

Deg

65

Relay characteristic angle (RCA)

polMethod

Voltage
Current
Dual

Voltage

Type of polarization

UPolMin

1 - 100

%UB

Minimum voltage level for polarization in


% of UBase

IPolMin

2 - 100

%IB

Minimum current level for polarization in


% of IBase

RNPol

0.50 - 1000.00

ohm

0.01

5.00

Real part of source Z to be used for


current polarisation

XNPol

0.50 - 3000.00

ohm

0.01

40.00

Imaginary part of source Z to be used for


current polarisation

IN>Dir

1 - 100

%IB

10

Residual current level for Direction


release in % of IBase

2ndHarmStab

5 - 100

20

Second harmonic restrain operation in %


of IN amplitude

BlkParTransf

Off
On

Off

Enable blocking at parallel transformers

UseStartValue

IN1>
IN2>
IN3>
IN4>

IN4>

Current level blk at parallel transf (step1,


2, 3 or 4)

SOTF

Off
SOTF
UnderTime
SOTF&UnderTime

Off

SOTF operation mode (Off/SOTF/


Undertime/SOTF&Undertime)

ActivationSOTF

Open
Closed
CloseCommand

Open

Select signal that shall activate SOTF

StepForSOTF

Step 2
Step 3

Step 2

Selection of step used for SOTF

HarmResSOTF

Off
On

Off

Enable harmonic restrain function in


SOTF

tSOTF

0.000 - 60.000

0.001

0.200

Time delay for SOTF

t4U

0.000 - 60.000

0.001

1.000

Switch-onto-fault active time

Table continues on next page


372
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

ActUnderTime

CB position
CB command

CB position

Select signal to activate under time (CB


Pos/CBCommand)

tUnderTime

0.000 - 60.000

0.001

0.300

Time delay for under time

DirMode1

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (off, nodir,


forward, reverse)

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 1

IN1>

1 - 2500

%IB

100

Operate residual current level for step 1


in % of IBase

t1

0.000 - 60.000

0.001

0.000

Independent (defenite) time delay of step


1

k1

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 1

IMin1

1.00 - 10000.00

%IB

1.00

100.00

Minimum current for step 1

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 1

IN1Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 1

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 1

tReset1

0.000 - 60.000

0.001

0.020

Reset time delay for step 1

HarmRestrain1

Off
On

On

Enable block of step 1 from harmonic


restrain

tPCrv1

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 1

tPRCrv1

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 1

Table continues on next page

373
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

tTRCrv1

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 1

tCRCrv1

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 1

DirMode2

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (off, nodir,


forward, reverse)

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 2

IN2>

1 - 2500

%IB

50

Operate residual current level for step 2


in % of IBase

t2

0.000 - 60.000

0.001

0.400

Independent (definitive) time delay of


step 2

k2

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 2

IMin2

1.00 - 10000.00

%IB

1.00

50

Minimum current for step 2

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


step 2

IN2Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 2

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 2

tReset2

0.000 - 60.000

0.001

0.020

Reset time delay for step 2

HarmRestrain2

Off
On

On

Enable block of step 2 from harmonic


restrain

tPCrv2

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 2

tCCrv2

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 2

Table continues on next page

374
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

tPRCrv2

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 2

DirMode3

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (off, nodir,


forward, reverse)

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 3

IN3>

1 - 2500

%IB

33

Operate residual current level for step 3


in % of IBase

t3

0.000 - 60.000

0.001

0.800

Independent time delay of step 3

k3

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 3

IMin3

1.00 - 10000.00

%IB

1.00

33

Minimum current for step 3

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 3

IN3Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 3

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 3

tReset3

0.000 - 60.000

0.001

0.020

Reset time delay for step 3

HarmRestrain3

Off
On

On

Enable block of step 3 from harmonic


restrain

tPCrv3

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve step 3

Table continues on next page

375
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

tPRCrv3

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 3

DirMode4

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (off, nodir,


forward, reverse)

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 4

IN4>

1 - 2500

%IB

17

Operate residual current level for step 4


in % of IBase

t4

0.000 - 60.000

0.001

1.200

Independent (definitive) time delay of


step 4

k4

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 4

IMin4

1.00 - 10000.00

%IB

1.00

17

Minimum current for step 4

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time in inverse curves


step 4

IN4Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 4

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 4

tReset4

0.000 - 60.000

0.001

0.020

Reset time delay for step 4

HarmRestrain4

Off
On

On

Enable block of step 4 from harmonic


restrain

tPCrv4

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 4

Table continues on next page

376
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

tCCrv4

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve step 4

7.4.6

Technical data
Table 203:

EF4PTOC technical data

Function

7.5

Range or value

Accuracy

Operate current

(1-2500)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Operate current for directional


comparison

(1100)% of lBase

1.0% of Ir

Timers

(0.000-60.000) s

0.5% 10 ms

Inverse characteristics, see


table 722, table 723 and table 724

18 curve types

See table 722, table 723 and


table 724

Second harmonic restrain


operation

(5100)% of fundamental

2.0% of Ir

Relay characteristic angle

(-180 to 180) degrees

2.0 degrees

Minimum polarizing voltage

(1100)% of UBase

0.5% of Ur

Minimum polarizing current

(1-30)% of IBase

0.25% of Ir

Real part of source Z used for


current polarization

(0.50-1000.00) W/phase

Imaginary part of source Z used


for current polarization

(0.503000.00) W/phase

Operate time, start function

25 ms typically at 0 to 2 x Iset

Reset time, start function

25 ms typically at 2 to 0 x Iset

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Four step directional negative phase sequence


overcurrent protection NS4PTOC

377
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Function description
Four step negative sequence
overcurrent protection

IEC 61850
identification

IEC 60617 identification ANSI/IEEE C37.2


device number

NS4PTOC

46I2

I2
4
4

alt

IEC10000053 V1 EN

7.5.1

Introduction
Four step negative sequence overcurrent protection (NS4PTOC) has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an
optional user defined characteristic.
The directional function is voltage polarized or dual polarized.
NS4PTOC can be set directional or non-directional independently for each of the
steps.
NS4PTOC can be used as main protection for unsymmetrical fault; phase-phase
short circuits, phase-phase-earth short circuits and single phase earth faults.
NS4PTOC can also be used to provide a system back-up for example, in the case of
the primary protection being out of service due to communication or voltage
transformer circuit failure.
Directional operation can be combined together with corresponding
communication logic in permissive or blocking teleprotection scheme. The same
logic as for directional zero sequence current can be used. Current reversal and weakend infeed functionality are available.

7.5.2

Principle of operation
Four step negative sequence overcurrent protection NS4PTOC function has the
following three Analog Inputs on its function block in the configuration tool:
1.
2.
3.

I3P, input used for Operating Quantity.


U3P, input used for Voltage Polarizing Quantity.
I3PPOL, input used for Polarizing Quantity.

These inputs are connected from the corresponding pre-processing function blocks
in the Configuration Tool within PCM600.

7.5.2.1

Operating quantity within the function


Four step negative sequence overcurrent protection NS4PTOC function always
uses negative sequence current (I2) for its operating quantity. The negative

378
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

sequence current is calculated from three-phase current input within the IED. The
pre-processing block calculates I2 from the first three inputs into the preprocessing block by using the following formula:

I op = I 2 =

1
3

IL1 + a IL 2 + a IL3
2

)
(Equation 87)

EQUATION2266 V1 EN

where:
IL1, IL2 and IL3

are fundamental frequency phasors of three individual phase currents.

is so called operator which gives a phase shift of 120 deg, that is, a = 1120 deg

a2

similarly gives a phase shift of 240 deg, that is, a2 = 1240 deg

The negative sequence current is pre-processed by a discrete Fourier filter. Thus,


the phasor of the fundamental frequency component of the negative sequence
current is derived. The phasor magnitude is used within the NS4PTOC protection
to compare it with the set operation current value of the four steps (I1>, I2>, I3>
or I4>). If the negative sequence current is larger than the set operation current and
the step is used in non-directional mode a signal from the comparator for this step
is set to true. This signal, without delay, activates the output signal STx (x=1 - 4)
for this step and a common START signal.

7.5.2.2

Internal polarizing facility of the function


A polarizing quantity is used within the protection to determine the direction to the
fault (Forward/Reverse).
Four step negative sequence overcurrent protection NS4PTOC function can be set
to use voltage polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected, NS4PTOC uses the negative sequence voltage
-U2 as polarizing quantity U3P. This voltage is calculated from three phase voltage
input within the IED. The pre-processing block calculates -U2 from the first three
inputs into the pre-processing block by using the following formula:

UPol = -U 2 = EQUATION2267 V1 EN

1
(UL1 + a UL 2 + a 2 UL3)
3
(Equation 88)

379
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

where:
UL1, UL2 and UL3

are fundamental frequency phasors of three individual phase voltages.


To use this all three phase-to-earth voltages must be connected to three IED VT inputs.

The negative sequence voltage is pre-processed by a discrete fourier filter. Thus,


the phasor of the fundamental frequency component of the negative sequence
voltage is derived. This phasor is used together with the phasor of the operating
current, in order to determine the direction to the fault (Forward/Reverse).To
enable voltage polarizing the magnitude of polarizing voltage must be bigger than a
minimum level defined by setting UpolMin.
Note that U2 is used to determine the location of the fault. This ensures the
required inversion of the polarizing voltage within the function.

Dual polarizing
When dual polarizing is selected, the function uses the vectorial sum of the voltage
based and current based polarizing in accordance with the following formula:
UTotPol = UUPol + UIPol = -U 2 + ZPol IPol = -U 2 + ( RPol + jXPol ) IPol
IECEQUATION2315 V1 EN

(Equation 89)

Then the phasor of the total polarizing voltage UTotPol is used, together with the
phasor of the operating current, to determine the direction to the fault (Forward/
Reverse).

7.5.2.3

External polarizing for negative sequence function


The individual steps within the protection can be set as non-directional. When this
setting is selected it is then possible via function binary input BLKSTx (where x
indicates the relevant step within the protection) to provide external directional
control (that is, torque control) by for example using one of the following functions
if available in the IED:

7.5.2.4

Distance protection directional function


Negative sequence polarized general current and voltage multi purpose
protection function

Base quantities within the function


The base quantities must be entered as setting parameters for every function. Base
current (IBase) must be entered as rated phase current of the protected object in
primary amperes. In line protections the primary rated current of the CT is chosen.

380
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Base voltage UBase must be entered as rated phase-to-phase voltage of the


protected object in primary kV. In line protections the primary rated voltage of the
VT is chosen.

7.5.2.5

Internal negative sequence protection structure


The protection is internally divided into the following parts:

Four negative sequence overcurrent steps


Directional supervision element for negative sequence overcurrent steps with
integrated directional comparison step for communication based negative
sequence protection schemes (permissive or blocking)

Each part is described separately in the following sections.

7.5.2.6

Four negative sequence overcurrent stages


Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as
measuring quantity. Every of the four overcurrent stage has the following built-in
facilities:

Operating mode (Off/ Non-directional /Forward / Reverse). By this parameter


setting the operating mode of the stage is selected. Note that the directional
decision (Forward/Reverse) is not made within the overcurrent stage itself.
The direction of the fault is determined in common Directional Supervision
Element described in the next paragraph.
Negative sequence current pickup value.
Type of operating characteristic (Inverse or Definite Time). By this parameter
setting it is possible to select Inverse or definite time delay for negative
sequence overcurrent function. Most of the standard IEC and ANSI inverse
characteristics are available. For the complete list of available inverse curves,
refer to Chapter "Inverse time characteristics"
Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this
parameter setting it is possible to select the reset characteristic of the stage. For
the complete list of available reset curves, refer to Chapter "Inverse time
characteristics"
Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves, reset time
delay and parameters to define user programmable inverse curve are defined.
Multiplier for scaling of the set negative sequence current pickup value by
external binary signal. By this parameter setting it is possible to increase
negative sequence current pickup value when function binary input
ENMULTx has logical value 1.

Simplified logic diagram for one negative sequence overcurrent stage is shown in
the following figure:

381
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

BLKTR
Characteristx=DefTime

|IOP|

ENMULTx
IxMult

tx

AND

TRx

OR

a>b

STx

AND

T
F

Ix>

Inverse

BLKSTx
BLOCK

Characteristx=Inverse

OR

DirModex=Off

STAGEx_DIR_Int

DirModex=Non-directional
DirModex=Forward
FORWARD_Int

DirModex=Reverse

REVERSE_Int

AND

OR

AND

IEC09000683-2-en.vsd
IEC09000683 V1 EN

Figure 214:

Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4

NS4PTOC can be completely blocked from the binary input BLOCK. The start
signals from NS4PTOC for each stage can be blocked from the binary input
BLKSTx. The trip signals from NS4PTOC can be blocked from the binary input
BLKTR.

7.5.2.7

Directional supervision element with integrated directional


comparison function
At least one of the four negative sequence overcurrent steps must
be set as directional in order to enable execution of the directional
supervision element and the integrated directional comparison
function.
NS4PTOC has integrated directional feature. As the operating quantity current Iop
is always used. The polarizing method is determined by the setting polMethod. The
polarizing quantity can be selected by NS4PTOC in one of the following two ways:

When polMethod=Voltage, UVPol is used as polarizing quantity


When polMethod=Dual, UTotPol is used as polarizing quantity

The operating and polarizing quantity are then used inside the directional element,
as shown in figure 208, to determine the direction of the fault.

382
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Reverse
Area

Upol=-U2

AngleRCA

Forward
Area
Iop = I2

IEC10000031-1-en.vsd
IEC10000031 V1 EN

Figure 215:

Operating characteristic for fault directional element

Two relevant setting parameters for directional supervision element are:

Directional element is internally enable to operate as soon as IOp is bigger than


40% of I>Dir and the directional condition is fulfilled in set direction.
Relay characteristic angle AngleRCA which defines the position of forward
and reverse areas in the operating characteristic.

Directional comparison step, built-in within directional supervision element, set


NS4PTOC output binary signals:
1.
2.

STFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward


area, see fig 208 (Operating quantity magnitude is bigger than setting I>Dir)
STRV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse
area, see fig 208. (Operating quantity magnitude is bigger than 60% of setting
I>Dir)

These signals must be used for communication based fault teleprotection


communication schemes (permissive or blocking).

383
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Simplified logic diagram for directional supervision element with integrated


directional comparison step is shown in figure 209:
|Iop|

0.6

a a>
b b

REVERSE_Int

X
a a>
b b

I>Dir
0.4

STRV

AND

FORWARD_Int

STFW

AND

polMethod=Voltage

OR

polMethod=Dual

UPolMin
UPol

T
0.0 F

IPolMin
Iop
UTotPol

IPol

RVS
RNPol
XNPol

BLOCK

Complex
Number

AND

FORWARD_Int

AND

REVERSE_Int

D i r e c ti o n a l
t
C h a r a c e ri s ti c

FWD
AngleRCA

UIPol
0.0

T
F

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int
STAGE4_DIR_Int

OR
AND

IEC07000067-4-en.vsd
IEC07000067-4 V1 EN

Figure 216:

Simplified logic diagram for directional supervision element with integrated directional
comparison step

384
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.5.3

Function block
NS4PTOC
I3P*
U3P*
I3PPOL*
BLOCK
BLKTR
BLKST1
BLKST2
BLKST3
BLKST4
ENMULT1
ENMULT2
ENMULT3
ENMULT4

TRIP
TR1
TR2
TR3
TR4
START
ST1
ST2
ST3
ST4
STFW
STRV
IEC10000054-1-en.vsd

IEC10000054 V1 EN

Figure 217:

7.5.4

NS4PTOC function block

Input and output signals


Table 204:
Name

NS4PTOC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Negative Sequence 3 phase current

U3P

GROUP
SIGNAL

Negative Sequence 3 phase voltage

I3PPOL

GROUP
SIGNAL

Negative Sequence 3 phase polarisation current

BLOCK

BOOLEAN

General block

BLKTR

BOOLEAN

Block of trip

BLKST1

BOOLEAN

Block of step 1 (Start and trip)

BLKST2

BOOLEAN

Block of step 2 (Start and trip)

BLKST3

BOOLEAN

Block of step 3 (Start and trip)

BLKST4

BOOLEAN

Block of step 4 (Start and trip)

ENMULT1

BOOLEAN

When activated, the current multiplier is in use for


step1

ENMULT2

BOOLEAN

When activated, the current multiplier is in use for


step2

ENMULT3

BOOLEAN

When activated, the current multiplier is in use for


step3

ENMULT4

BOOLEAN

When activated, the current multiplier is in use for


step4

385
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Table 205:

NS4PTOC Output signals

Name

7.5.5
Table 206:
Name

Type

Description

TRIP

BOOLEAN

Trip

TR1

BOOLEAN

Trip signal from step 1

TR2

BOOLEAN

Trip signal from step 2

TR3

BOOLEAN

Trip signal from step 3

TR4

BOOLEAN

Trip signal from step 4

START

BOOLEAN

General start signal

ST1

BOOLEAN

Start signal step 1

ST2

BOOLEAN

Start signal step 2

ST3

BOOLEAN

Start signal step 3

ST4

BOOLEAN

Start signal step 4

STFW

BOOLEAN

Forward directional start signal

STRV

BOOLEAN

Reverse directional start signal

Setting parameters
NS4PTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base value for current settings

UBase

0.05 - 2000.00

kV

0.05

400

Base value for voltage settings

AngleRCA

-180 - 180

Deg

65

Relay characteristic angle (RCA)

polMethod

Voltage
Dual

Voltage

Type of polarization

UPolMin

1 - 100

%UB

Minimum voltage level for polarization in


% of UBase

IPolMin

2 - 100

%IB

Minimum current level for polarization in


% of IBase

RPol

0.50 - 1000.00

ohm

0.01

5.00

Real part of neg. seq. source imp. to be


used for current polarisation

XPol

0.50 - 3000.00

ohm

0.01

40.00

Imaginary part of neg. seq. source imp.


to be used for current polarisation

I>Dir

1 - 100

%IB

10

Neg. seq. curr. I2 level for Direction


release in % of IBase

DirMode1

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 1 (off, nodir,


forward, reverse)

Table continues on next page

386
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Characterist1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 1

I1>

1 - 2500

%IB

100

Operate neg. seq. curr. I2 level for step 1


in % of IBase

t1

0.000 - 60.000

0.001

0.000

Independent (defenite) time delay of step


1

k1

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 1

IMin1

1.00 - 10000.00

%IB

1.00

100.00

Minimum current for step 1

t1Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 1

I1Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 1

ResetTypeCrv1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 1

tReset1

0.000 - 60.000

0.001

0.020

Reset time delay for step 1

tPCrv1

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

tACrv1

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 1

tBCrv1

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 1

tCCrv1

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 1

tPRCrv1

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 1

tTRCrv1

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 1

tCRCrv1

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 1

DirMode2

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 2 (off, nodir,


forward, reverse)

Table continues on next page

387
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

Characterist2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 2

I2>

1 - 2500

%IB

50

Operate neg. seq. curr. I2 level for step 2


in % of IBase

t2

0.000 - 60.000

0.001

0.400

Independent (definitive) time delay of


step 2

k2

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 2

IMin2

1.00 - 10000.00

%IB

1.00

50

Minimum current for step 2

t2Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


step 2

I2Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 2

ResetTypeCrv2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 2

tReset2

0.000 - 60.000

0.001

0.020

Reset time delay for step 2

tPCrv2

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

tACrv2

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 2

tBCrv2

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 2

tCCrv2

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve for step 2

tPRCrv2

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for step 2

tTRCrv2

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve for step 2

tCRCrv2

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 2

DirMode3

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 3 (off, nodir,


forward, reverse)

Table continues on next page

388
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Characterist3

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 3

I3>

1 - 2500

%IB

33

Operate neg. seq. curr. I2 level for step 3


in % of IBase

t3

0.000 - 60.000

0.001

0.800

Independent time delay of step 3

k3

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 3

IMin3

1.00 - 10000.00

%IB

1.00

33

Minimum current for step 3

t3Min

0.000 - 60.000

0.001

0.000

Minimum operate time for inverse curves


for step 3

I3Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 3

ResetTypeCrv3

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 3

tReset3

0.000 - 60.000

0.001

0.020

Reset time delay for step 3

tPCrv3

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 3

tACrv3

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve for step 3

tBCrv3

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 3

tCCrv3

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve step 3

tPRCrv3

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve step 3

tTRCrv3

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve step 3

tCRCrv3

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for step 3

DirMode4

Off
Non-directional
Forward
Reverse

Non-directional

Directional mode of step 4 (off, nodir,


forward, reverse)

Table continues on next page

389
Technical reference manual

Section 7
Current protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

Characterist4

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

ANSI Def. Time

Time delay curve type for step 4

I4>

1 - 2500

%IB

17

Operate neg. seq. curr. I2 level for step 4


in % of IBase

t4

0.000 - 60.000

0.001

1.200

Independent (definitive) time delay of


step 4

k4

0.05 - 999.00

0.01

0.05

Time multiplier for the dependent time


delay for step 4

IMin4

1.00 - 10000.00

%IB

1.00

17

Minimum current for step 4

t4Min

0.000 - 60.000

0.001

0.000

Minimum operate time in inverse curves


step 4

I4Mult

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for step 4

ResetTypeCrv4

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Reset curve type for step 4

tReset4

0.000 - 60.000

0.001

0.020

Reset time delay for step 4

tPCrv4

0.005 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 4

tACrv4

0.005 - 200.000

0.001

13.500

Parameter A for customer programmable


curve step 4

tBCrv4

0.00 - 20.00

0.01

0.00

Parameter B for customer programmable


curve for step 4

tCCrv4

0.1 - 10.0

0.1

1.0

Parameter C for customer


programmable curve step 4

tPRCrv4

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve step 4

tTRCrv4

0.005 - 100.000

0.001

13.500

Parameter TR for customer


programmable curve step 4

tCRCrv4

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve step 4

390
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.5.6

Technical data
Table 207:

NS4PTOC technical data

Function

7.6

Accuracy

Operate value, negative


sequence current, step 1-4

(1-2500)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Timers

(0.000-60.000) s

0.5% 10 ms

Inverse characteristics, see


table 722, table 723 and table 724

18 curve types

See table 722, table 723 and


table 724

Minimum operate current for


step 1 - 4

(1.00 - 10000.00)% of IBase

1.0% of Ir at I < Ir
1.0% of I at I > Ir

Operate value, negative current


for directional release

(1100)% of IBase

1.0% of Ir

Relay characteristic angle

(-180 to 180) degrees

2.0 degrees

Minimum polarizing voltage

(1100)% of UBase

0.5% of Ur

Minimum polarizing current

(2-100)% of IBase

1.0% of Ir

Real part of negative sequence


source impedance used for
current polarization

(0.50-1000.00) W/phase

Imaginary part of negative


sequence source impedance
used for current polarization

(0.503000.00) W/phase

Operate time, start function

25 ms typically at 0.5 to 2 x Iset

Reset time, start function

25 ms typically at 2 to 0.5 x Iset

Critical impulse time, start


function

10 ms typically at 0 to 2 x Iset

Impulse margin time, start


function

15 ms typically

Transient overreach

<10% at = 100 ms

Sensitive directional residual overcurrent and power


protection SDEPSDE
Function description
Sensitive directional residual over
current and power protection

7.6.1

Range or value

IEC 61850
identification
SDEPSDE

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
67N

Introduction
In networks with high impedance earthing, the phase-to-earth fault current is
significantly smaller than the short circuit currents. Another difficulty for earth391

Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

fault protection is that the magnitude of the phase-to-earth fault current is almost
independent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-toearth faults in high impedance earthed networks. The protection uses the residual
current component 3I0 cos , where is the angle between the residual current
and the residual voltage (-3U0), compensated with a characteristic angle.
Alternatively, the function can be set to strict 3I0 level with an check of angle 3I0
and cos .
Directional residual power can also be used to detect and give selective trip of phaseto-earth faults in high impedance earthed networks. The protection uses the
residual power component 3I0 3U0 cos , where is the angle between the
residual current and the reference residual voltage, compensated with a
characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
A back-up neutral point voltage function is also available for non-directional
sensitive back-up protection.
In an isolated network, that is, the network is only coupled to earth via the
capacitances between the phase conductors and earth, the residual current always
has -90 phase shift compared to the reference residual voltage. The characteristic
angle is chosen to -90 in such a network.
In resistance earthed networks or in Petersen coil earthed, with a parallel resistor,
the active residual current component (in phase with the residual voltage) should be
used for the earth-fault detection. In such networks the characteristic angle is
chosen to 0.
As the amplitude of the residual current is independent of the fault location the
selectivity of the earth-fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used and
when should the sensitive directional residual power protection be used? Consider
the following facts:

Sensitive directional residual overcurrent protection gives possibility for better


sensitivity
Sensitive directional residual power protection gives possibility to use inverse
time characteristics. This is applicable in large high impedance earthed
networks, with large capacitive earth-fault current
In some power systems a medium size neutral point resistor is used, for
example, in low impedance earthed system. Such a resistor will give a resistive
earth-fault current component of about 200 - 400 A at a zero resistive phase-toearth fault. In such a system the directional residual power protection gives
better possibilities for selectivity enabled by inverse time power characteristics.

392
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.6.2

Principle of operation

7.6.2.1

Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from preprocessor blocks.
The sensitive directional earth fault protection has the following sub-functions
included:

Directional residual current protection measuring 3I0cos


is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (=ang(3I0)-ang(Uref) ).
Uref = -3U0 ejRCADIr. RCADir is normally set equal to 0 in a high impedance
earthed network with a neutral point resistor as the active current component is
appearing out on the faulted feeder only. RCADir is set equal to -90 in an isolated
network as all currents are mainly capacitive. The function operates when 3I0cos
gets larger than the set value.
RCADir = 0 , ROADir = 0

3I0

= ang(3I0 ) ang(3Uref )

3I0 cos

3U0 = Uref

IEC06000648-3-en.vsd
IEC06000648 V3 EN

Figure 218:

RCADir set to 0

393
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Uref

RCADir = 90 , ROADir = 90

3I0

3I0 cos
= ang (3I0 ) ang (Uref )

3U0

IEC06000649_3_en.vsd
IEC06000649 V3 EN

Figure 219:

RCADir set to -90

For trip, both the residual current 3I0cos and the release voltage 3U0, must be
larger than the set levels: INCosPhi> and UNRel>.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated. The trip from this sub-function has definite time
delay.
There is a possibility to increase the operate level for currents where the angle is
larger than a set value as shown in figure 220. This is equivalent to blocking of the
function if > ROADir. This option is used to handle angle error for the instrument
transformers.

394
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

RCADir = 0o

3I0

Operate area

j
3I0 cos j

-3U0 = Uref

ROADir

IEC06000650_2_en.vsd
IEC06000650 V2 EN

Figure 220:

Characteristic with ROADir restriction

The function indicates forward/reverse direction to the fault. Reverse direction is


defined as 3I0cos ( + 180) the set value.
It is also possible to tilt the characteristic to compensate for current transformer
angle error with a setting RCAComp as shown in the figure 221:

395
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

RCADir = 0

Operate area

-3U0 =Uref

Instrument
transformer
angle error

RCAcomp
Characteristic after
angle compensation

3I0 (prim)

3I0 (to prot)

en06000651.vsd
IEC06000651 V2 EN

Figure 221:

Explanation of RCAComp

Directional residual power protection measuring 3I0 3U0 cos


is defined as the angle between the residual current 3I0 and the reference voltage
compensated with the set characteristic angle RCADir (=ang(3I0)ang(Uref) ).
Uref = -3U0 e-jRCA. The function operates when 3I0 3U0 cos gets larger than
the set value.
For trip, both the residual power 3I0 3U0 cos , the residual current 3I0 and the
release voltage 3U0, shall be larger than the set levels (SN>, INRel> and UNRel>).
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef or after the inverse time
delay (setting kSN) the binary output signals TRIP and TRDIRIN are activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction
is defined as 3I0 3U0cos ( + 180) the set value.
This variant has the possibility of choice between definite time delay and inverse
time delay.

396
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

The inverse time delay is defined as:


t inv =

kSN (3I0 3U 0 cos j(reference))


3I0 3U 0 cos j(measured)
(Equation 90)

EQUATION1942 V2 EN

Directional residual current protection measuring 3I0 and


The function will operate if the residual current is larger that the set value and the
angle = ang(3I0)-ang(Uref) is within the sector RCADir ROADir
RCADir = 0
ROADir = 80

Operate area
3I0
80

-3U0

en06000652.vsd
IEC06000652 V2 EN

Figure 222:

Example of characteristic

For trip, both the residual current 3I0 and the release voltage 3U0, shall be larger
than the set levels INDir> and UNREL> and the angle shall be in the set sector
ROADir and RCADir.
Trip from this function can be blocked from the binary input BLKTRDIR.
When the function is activated binary output signals START and STDIRIN are
activated. If the activation is active after the set delay tDef the binary output signals
TRIP and TRDIRIN are activated.
The function indicate forward/reverse direction to the fault. Reverse direction is
defined as is within the angle sector: RCADir + 180 ROADir
This variant shall have definite time delay.

397
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Directional functions

For all the directional functions there are directional start signals STFW: fault in
the forward direction, and STRV: start in the reverse direction. Even if the
directional function is set to operate for faults in the forward direction a fault in the
reverse direction will give the start signal STRV. Also if the directional function is
set to operate for faults in the reverse direction a fault in the forward direction will
give the start signal STFW.

Non-directional earth fault current protection

This function will measure the residual current without checking the phase angle.
The function will be used to detect cross-country faults. This function can serve as
alternative or back-up to distance protection with phase preference logic. To assure
selectivity the distance protection can block the non-directional earth fault current
function via the input BLKNDN.
If available the non-directional function is using the calculated residual current,
derived as sum of the phase currents. This will give a better ability to detect crosscountry faults with high residual current, also when dedicated core balance CT for
the sensitive earth fault protection will saturate.
This variant shall have the possibility of choice between definite time delay and
inverse time delay. The inverse time delay shall be according to IEC 60255-3.
For trip, the residual current 3I0 shall be larger than the set levels (INNonDir>).
Trip from this function can be blocked from the binary input BLKNDN.
When the function is activated binary output signal STNDIN is activated. If the
activation is active after the set delay tINNonDir or after the inverse time delay the
binary output signals TRIP and TRNDIN are activated.

Residual overvoltage release and protection

The directional function shall be released when the residual voltage gets higher
than a set level.
There shall also be a separate trip, with its own definite time delay, from this set
voltage level.
For trip, the residual voltage 3U0 shall be larger than the set levels (UN>).
Trip from this function can be blocked from the binary input BLKUN.
When the function is activated binary output signal STUN is activated. If the
activation is active after the set delay tUNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 223.

398
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

STNDIN

INNonDir>
t

TRNDIN

TRUN

STUN

UN>
OpMODE=3I0cosfi

IN>

&

INcosPhi>
OpMODE=3I03U0cosfi

&

STARTDIRIN

&

INUNcosPhi>

SN

Phi in RCA +- ROA

&

TRDIRIN

TimeChar = InvTime

&

OpMODE=3I0 and fi

TimeChar = DefTime

DirMode = Forward

&

&

1
STFW

Forward
DirMode = Reverse

&
STRV

Reverse

en06000653.vsd
IEC06000653 V2 EN

Figure 223:

Simplified logical diagram of the sensitive earth-fault current protection

7.6.3

Function block
SDEPSDE
I3P*
U3P*
BLOCK
BLKTR
BLKTRDIR
BLKNDN
BLKUN

TRIP
TRDIRIN
TRNDIN
TRUN
START
STDIRIN
STNDIN
STUN
STFW
STRV
STDIR
UNREL
IEC07000032-2-en.vsd

IEC07000032 V2 EN

Figure 224:

SDEPSDE function block

399
Technical reference manual

Section 7
Current protection
7.6.4

1MRK 505 222-UEN B

Input and output signals


Table 208:
Name

SDEPSDE Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current

U3P

GROUP
SIGNAL

Group signal for voltage

BLOCK

BOOLEAN

Blocks all the outputs of the function

BLKTR

BOOLEAN

Blocks the operate outputs of the function

BLKTRDIR

BOOLEAN

Blocks the directional operate outputs of the


function

BLKNDN

BOOLEAN

Blocks the Non directional current residual outputs

BLKUN

BOOLEAN

Blocks the Non directional voltage residual outputs

Table 209:
Name

SDEPSDE Output signals


Type

Description

TRIP

BOOLEAN

General trip of the function

TRDIRIN

BOOLEAN

Trip of the directional residual over current function

TRNDIN

BOOLEAN

Trip of non directional residual over current

TRUN

BOOLEAN

Trip of non directional residual over voltage

START

BOOLEAN

General start of the function

STDIRIN

BOOLEAN

Start of the directional residual over current


function

STNDIN

BOOLEAN

Start of non directional residual over current

STUN

BOOLEAN

Start of non directional residual over voltage

STFW

BOOLEAN

Start of directional function for a fault in forward


direction

STRV

BOOLEAN

Start of directional function for a fault in reverse


direction

STDIR

INTEGER

Direction of fault. A general signal common to all


three mode of residual over current protection

UNREL

BOOLEAN

Residual voltage release of operation of all


directional modes

400
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.6.5
Table 210:

Setting parameters
SDEPSDE Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

OpMode

3I0Cosfi
3I03U0Cosfi
3I0 and fi

3I0Cosfi

Selection of operation mode for protection

DirMode

Forward
Reverse

Forward

Direction of operation forward or reverse

RCADir

-179 - 180

Deg

-90

Relay characteristic angle RCA, in deg

RCAComp

-10.0 - 10.0

Deg

0.1

0.0

Relay characteristic angle compensation

ROADir

0 - 90

Deg

90

Relay open angle ROA used as release


in phase mode, in deg

INCosPhi>

0.25 - 200.00

%IB

0.01

1.00

Set level for 3I0cosFi, directional res


over current, in %Ib

SN>

0.25 - 200.00

%SB

0.01

10.00

Set level for 3I03U0cosFi, starting inv


time count, in %Sb

INDir>

0.25 - 200.00

%IB

0.01

5.00

Set level for directional residual over


current prot, in %Ib

tDef

0.000 - 60.000

0.001

0.100

Definite time delay directional residual


overcurrent, in sec

SRef

0.03 - 200.00

%SB

0.01

10.00

Reference value of res power for inverse


time count, in %Sb

kSN

0.00 - 2.00

0.01

0.10

Time multiplier setting for directional


residual power mode

OpINNonDir>

Off
On

Off

Operation of non-directional residual


overcurrent protection

INNonDir>

1.00 - 400.00

%IB

0.01

10.00

Set level for non directional residual over


current, in %Ib

tINNonDir

0.000 - 60.000

0.001

1.000

Time delay for non-directional residual


over current, in sec

TimeChar

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type

IEC Norm. inv.

Operation curve selection for IDMT


operation

Table continues on next page

401
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

tMin

0.000 - 60.000

0.001

0.040

Minimum operate time for IEC IDMT


curves, in sec

kIN

0.00 - 2.00

0.01

1.00

IDMT time mult for non-dir res over


current protection

OpUN>

Off
On

Off

Operation of non-directional residual


overvoltage protection

UN>

1.00 - 200.00

%UB

0.01

20.00

Set level for non-directional residual over


voltage, in %Ub

tUN

0.000 - 60.000

0.001

0.100

Time delay for non-directional residual


over voltage, in sec

INRel>

0.25 - 200.00

%IB

0.01

1.00

Residual release current for all


directional modes, in %Ib

UNRel>

0.01 - 200.00

%UB

0.01

3.00

Residual release voltage for all direction


modes, in %Ub

Step

Default

Table 211:
Name

Step

Default

Description

SDEPSDE Group settings (advanced)


Values (Range)

Unit

tReset

0.000 - 60.000

0.001

0.040

Time delay used for reset of definite


timers, in sec

tPCrv

0.005 - 3.000

0.001

1.000

Setting P for customer programmable


curve

tACrv

0.005 - 200.000

0.001

13.500

Setting A for customer programmable


curve

tBCrv

0.00 - 20.00

0.01

0.00

Setting B for customer programmable


curve

tCCrv

0.1 - 10.0

0.1

1.0

Setting C for customer programmable


curve

ResetTypeCrv

Immediate
IEC Reset
ANSI reset

IEC Reset

Reset mode when current drops off.

tPRCrv

0.005 - 3.000

0.001

0.500

Setting PR for customer programmable


curve

tTRCrv

0.005 - 100.000

0.001

13.500

Setting TR for customer programmable


curve

tCRCrv

0.1 - 10.0

0.1

1.0

Setting CR for customer programmable


curve

Table 212:
Name

Description

SDEPSDE Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

100

Base Current, in A

UBase

0.05 - 2000.00

kV

0.05

63.50

Base Voltage, in kV Phase to Neutral

SBase

0.05 200000000.00

kVA

0.05

6350.00

Base Power, in kVA. IBase*Ubase

402
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Table 213:

SDEPSDE Non group settings (advanced)

Name
RotResU

7.6.6

Values (Range)
0 deg
180 deg

Unit

Step

Default

Description

180 deg

Setting for rotating polarizing quantity if


necessary

Technical data
Table 214:

SDEPSDE technical data

Function
Operate level for 3I0cosj
directional residual overcurrent

Operate level for 3I03U0 cosj


directional residual power

Operate level for 3I0 and j


residual overcurrent

Operate level for non-directional


overcurrent

Range or value
(0.25-200.00)% of lBase
At low setting:
(2.5-10) mA
(10-50) mA
(0.25-200.00)% of SBase
At low setting:
(0.25-5.00)% of SBase
(0.25-200.00)% of lBase
At low setting:
(2.5-10) mA
(10-50) mA
(1.00-400.00)% of lBase
At low setting:
(10-50) mA

Accuracy
1.0% of Ir at I Ir
1.0% of I at I > Ir
0.5 mA
1.0 mA
1.0% of Sr at S Sr
1.0% of S at S > Sr
10% of set value
1.0% of Ir at Ir
1.0% of I at I > Ir
0.5 mA
1.0 mA
1.0% of Ir at I Ir
1.0% of I at I > Ir
1.0 mA

Operate level for non-directional


residual overvoltage

(1.00-200.00)% of UBase

0.5% of Ur at UUr
0.5% of U at U > Ur

Residual release current for all


directional modes

(0.25-200.00)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

At low setting:
(2.5-10) mA
(10-50) mA

0.5 mA
1.0 mA

Residual release voltage for all


directional modes

(0.01-200.00)% of UBase

0.5% of Ur at UUr
0.5% of U at U > Ur

Reset ratio

> 95%

Timers

(0.000-60.000) s

0.5% 10 ms

Inverse characteristics, see


table 722, table 723 and table
724

19 curve types

See table 722, table 723 and


table 724

Relay characteristic angle RCA

(-179 to 180) degrees

2.0 degrees

Relay open angle ROA

(0-90) degrees

2.0 degrees

Operate time, non-directional


residual over current

60 ms typically at 0 to 2 x Iset

Reset time, non-directional


residual over current

60 ms typically at 2 to 0 x Iset

Operate time, start function

150 ms typically at 0 to 2 x Iset

Reset time, start function

50 ms typically at 2 to 0 x Iset

403
Technical reference manual

Section 7
Current protection

7.7

1MRK 505 222-UEN B

Thermal overload protection, one time constant


LPTTR
Function description
Thermal overload protection, one time
constant

IEC 61850
identification

IEC 60617
identification

LPTTR

ANSI/IEEE C37.2
device number
26

SYMBOL-A V1 EN

7.7.1

Introduction
The increasing utilizing of the power system closer to the thermal limits has
generated a need of a thermal overload protection also for power lines.
A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload protection can allow the protected circuit to
operate closer to the thermal limits.
The three-phase current measuring protection has an I2t characteristic with settable
time constant and a thermal memory.
An alarm level gives early warning to allow operators to take action well before the
line is tripped.

7.7.2

Principle of operation
The sampled analog phase currents are pre-processed and for each phase current
the RMS value is derived. These phase current values are fed to the thermal
overload protection, one time constant function LPTTR.
From the largest of the three-phase currents a final temperature is calculated
according to the expression:

Q final

I
=
I ref

Tref

EQUATION1167 V1 EN

(Equation 91)

where:
I

is the largest phase current,

Iref

is a given reference current and

Tref

is steady state temperature corresponding to Iref

404
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

The ambient temperature is added to the calculated final temperature. If this


temperature is larger than the set operate temperature level, TripTemp, a START
output signal is activated.
The actual temperature at the actual execution cycle is calculated as:
Dt

Qn = Qn -1 + ( Q final - Q n-1 ) 1 - e t

EQUATION1168 V1 EN

(Equation 92)

where:
Qn

is the calculated present temperature,

Qn-1

is the calculated temperature at the previous time step,

Qfinal

is the calculated final temperature with the actual current,

Dt

is the time step between calculation of the actual temperature and

is the set thermal time constant for the protected device (line or cable)

The actual temperature of the protected component (line or cable) is calculated by


adding the ambient temperature to the calculated temperature, as shown above. The
ambient temperature can be taken from a separate sensor or can be given a constant
value. The calculated component temperature is available as a real figure signal,
TEMP.
When the component temperature reaches the set alarm level AlarmTemp the
output signal ALARM is set. When the component temperature reaches the set trip
level TripTemp the output signal TRIP is set.
There is also a calculation of the present time to operate with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:

Q
- Qoperate
toperate = -t ln final
Q final - Q n

EQUATION1169 V1 EN

(Equation 93)

The calculated time to trip is available as a real figure signal, TTRIP.


After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the device temperature is above the set lockout release temperature setting
ReclTemp.
The time to lockout release is calculated that is, a calculation of the cooling time to
a set value. The thermal content of the function can be reset with input RESET.

405
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Q
- Qlockout _ release
tlockout _ release = -t ln final

Q final - Q n

(Equation 94)

EQUATION1170 V1 EN

Here the final temperature is equal to the set or measured ambient temperature. The
calculated time to reset of lockout is available as a real figure signal, TENRECL.
In some applications the measured current can involve a number of parallel lines.
This is often used for cable lines where one bay connects several parallel cables.
By setting the parameter IMult to the number of parallel lines (cables) the actual
current on one line is used in the protection algorithm. To activate this option the
input ENMULT must be activated.
The protection has a reset input: RESET. By activating this input the calculated
temperature is reset to its default initial value. This is useful during testing when
secondary injected current has given a calculated false temperature level.
START

Final Temp
> TripTemp

actual temperature

Calculation
of actual
temperature

IL1, IL2, IL3

Calculation
of final
temperature
Actual Temp >
AlarmTemp

ALARM

TRIP
Actual Temp
> TripTemp

Lockout
logic

LOCKOUT

Actual Temp
< Recl Temp

Calculation
of time to
trip

Calculation
of time to
reset of
lockout

TTRIP

TENRECL

IEC09000637_1_en.vsd
IEC09000637 V1 EN

Figure 225:

Functional overview of LPTTR

406
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.7.3

Function block
LPTTR
I3P*
BLOCK
BLKTR
ENMULT
AMBTEMP
SENSFLT
RESET

TRIP
START
ALARM
LOCKOUT

IEC04000396-2-en.vsd
IEC04000396 V3 EN

Figure 226:

7.7.4

LPTTR function block

Input and output signals


Table 215:

LPTTR Input signals

Name

Type

Table 217:

Description

GROUP
SIGNAL

Group connection

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

ENMULT

BOOLEAN

Current multiplyer used when THOL is for two or


more lines

AMBTEMP

REAL

Ambient temperature from external temperature


sensor

SENSFLT

BOOLEAN

Validity status of ambient temperature sensor

RESET

BOOLEAN

Reset of internal thermal load counter

Table 216:

LPTTR Output signals

Name

7.7.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip

START

BOOLEAN

Start Signal

ALARM

BOOLEAN

Alarm signal

LOCKOUT

BOOLEAN

Lockout signal

Setting parameters
LPTTR Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

0 - 99999

3000

Base current in A

TRef

0 - 600

Deg

90

End temperature rise above ambient of


the line when loaded with IRef

Table continues on next page

407
Technical reference manual

Section 7
Current protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

IRef

0 - 400

%IB

100

The load current (in %of IBase) leading


to TRef temperature

IMult

1-5

Current multiplier when function is used


for two or more lines

Tau

0 - 1000

Min

45

Time constant of the line in minutes.

AlarmTemp

0 - 200

Deg

80

Temperature level for start (alarm)

TripTemp

0 - 600

Deg

90

Temperature level for trip

ReclTemp

0 - 600

Deg

75

Temperature for reset of lockout after trip

tPulse

0.05 - 0.30

0.01

0.1

Operate pulse length. Minimum one


execution cycle

AmbiSens

Off
On

Off

External temperature sensor availiable

DefaultAmbTemp

-50 - 250

Deg

20

Ambient temperature used when


AmbiSens is set to Off.

DefaultTemp

-50 - 600

Deg

50

Temperature raise above ambient


temperature at startup

7.7.6

Technical data
Table 218:

LPTTR technical data

Function

Range or value

Accuracy

Reference current

(0-400)% of IBase

1.0% of Ir

Reference temperature

(0-400)C

1.0C

Operate time:

Time constant t = (01000)


minutes

IEC 60255-8, class 5 + 200 ms

Alarm temperature

(0-200)C

2.0% of heat content trip

Trip temperature

(0-400)C

2.0% of heat content trip

Reset level temperature

(0-400)C

2.0% of heat content trip

I 2 - I p2
t = t ln 2
I - Ib 2

EQUATION1356 V1 EN

(Equation 95)

I = actual measured current


Ip = load current before overload
occurs
Ib = base current, IBase

7.8

Breaker failure protection CCRBRF

408
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Function description
Breaker failure protection

IEC 61850
identification

IEC 60617
identification

CCRBRF

ANSI/IEEE C37.2
device number
50BF

3I>BF
SYMBOL-U V1 EN

7.8.1

Introduction
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case the own breaker fails to open. CCRBRF can be current based,
contact based, or an adaptive combination of these two conditions.
Current check with extremely short reset time is used as check criterion to achieve
high security against unnecessary operation.
Contact check criteria can be used where the fault current through the breaker is small.
CCRBRF can be single- or three-phase initiated to allow use with single phase
tripping applications. For the three-phase version of CCRBRF the current criteria
can be set to operate only if two out of four for example, two phases or one phase
plus the residual current start. This gives a higher security to the back-up trip
command.
CCRBRF function can be programmed to give a single- or three-phase re-trip of
the own breaker to avoid unnecessary tripping of surrounding breakers at an
incorrect initiation due to mistakes during testing.

7.8.2

Principle of operation
Breaker failure protection CCRBRF is initiated from protection trip command,
either from protection functions within the IED or from external protection devices.
The start signal can be phase selective or general (for all three phases). Phase
selective start signals enable single pole re-trip function. This means that a second
attempt to open the breaker is done. The re-trip attempt can be made after a set
time delay. For transmission lines single pole trip and autoreclosing is often used.
The re-trip function can be phase selective if it is initiated from phase selective line
protection. The re-trip function can be done with or without current check. With
the current check the re-trip is only performed if the current through the circuit
breaker is larger than the operate current level.
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, by detection of either low current through RMS
evaluation and a special adapted current algorithm or by open contact indication.
The special algorithm enables a very fast detection of successful breaker opening,
that is, fast resetting of the current measurement. If the current and/or contact

409
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

detection has not detected breaker opening before the back-up timer has run its
time a back-up trip is initiated.
Further the following possibilities are available:

The minimum length of the re-trip pulse, the back-up trip pulse and the backup trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the backup trip pulse 2 will however sustain as long as there is an indication of closed
breaker.
In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out
of 4 where it is sufficient to detect failure to open (high current) in one pole or
high residual current and 2 out of 4 where at least two current (phase current and/
or residual current) shall be high for breaker failure detection.
The current detection level for the residual current can be set different from the
setting of phase current detection.
It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is insufficient to clear faults, for example at low gas pressure.
START
STL1

30 ms
OR

BFP Started L1
150 ms
AND

S
R

BLOCK
Reset L1

SR

AND

Time out L1

OR

Retrip Time Out L1


BackupTrip L1

OR

IEC09000976-1-en.vsd
IEC09000976 V1 EN

Figure 227:

Simplified logic scheme of the CCRBRF starting logic

410
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

IP>
a
b

FunctionMode

a>b

Current

OR

AND

Reset L1

OR

Contact

Time out L1
OR

Current and Contact

IL1

AND

Current High L1
CB Closed L1

AND

OR

BFP Started L1
a

I>BlkCont

AND

a>b

AND

OR

AND

CBCLDL1

Contact Closed L1

AND

IEC09000977-1-en.vsd
IEC09000977 V1 EN

Figure 228:

BFP Started L1

RetripMode

Simplified logic scheme of the CCRBRF, CB position evaluation

t1
t

From other
phases

Retrip Time Out L1


AND

No CBPos Check
1

CBFLT

OR

CB Pos Check
CB Closed L1

TRRETL3
TRRETL2

OR

tPulse
OR

TRRET
TRRETL1

OR

AND

AND

IEC09000978-1-en.vsd

IEC09000978 V1 EN

Figure 229:

Simplified logic scheme of the retrip logic function

411
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

IN

IN>

BUTripMode
1

From other
phases

a>b

AND

Contact Closed L1

2 out of 4
1 out of 4
1 out of 3
Current High L2
Current High L3

OR
OR

Current High L1
CBFLT

AND

AND

t2

BFP Started L1

t2MPh
AND

OR

From other
phases

BFP Started L2

AND

OR

AND

Backup Trip L1

OR

tPulse

From other Backup Trip L2


phases Backup Trip L3

OR

2 of 3

OR

TRBU

tPulse

BFP Started L3

t3
S
AND

SR

OR

TRBU2

IEC09000979-1-en.vsd

IEC09000979 V1 EN

Figure 230:

Simplified logic scheme of the back-up trip logic function

Internal logical signals Current High L1, Current High L2, Current High L3 have
logical value 1 when current in respective phase has magnitude larger than setting
parameter IP>.

7.8.3

Function block
CCRBRF
I3P*
BLOCK
START
STL1
STL2
STL3
CBCLDL1
CBCLDL2
CBCLDL3
CBFLT

TRBU
TRBU2
TRRET
TRRETL1
TRRETL2
TRRETL3
CBALARM

IEC06000188-2-en.vsd
IEC06000188 V2 EN

Figure 231:

CCRBRF function block

412
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.8.4

Input and output signals


Table 219:

CCRBRF Input signals

Name

Type
GROUP
SIGNAL

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block of function

START

BOOLEAN

Three phase start of breaker failure protection


function

STL1

BOOLEAN

Start signal of phase L1

STL2

BOOLEAN

Start signal of phase L2

STL3

BOOLEAN

Start signal of phase L3

CBCLDL1

BOOLEAN

Circuit breaker closed in phase L1

CBCLDL2

BOOLEAN

Circuit breaker closed in phase L2

CBCLDL3

BOOLEAN

Circuit breaker closed in phase L3

CBFLT

BOOLEAN

CB faulty, unable to trip. Back-up trip


instantaneously

CCRBRF Output signals

Name

Table 221:

Description

I3P

Table 220:

7.8.5

Default

Type

Description

TRBU

BOOLEAN

Back-up trip by breaker failure protection function

TRBU2

BOOLEAN

Second back-up trip by breaker failure protection


function

TRRET

BOOLEAN

Retrip by breaker failure protection function

TRRETL1

BOOLEAN

Retrip by breaker failure protection function


phase L1

TRRETL2

BOOLEAN

Retrip by breaker failure protection function


phase L2

TRRETL3

BOOLEAN

Retrip by breaker failure protection function


phase L3

CBALARM

BOOLEAN

Alarm for faulty circuit breaker

Setting parameters
CCRBRF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

FunctionMode

Current
Contact
Current&Contact

Current

Detection principle for back-up trip

Table continues on next page

413
Technical reference manual

Section 7
Current protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

BuTripMode

2 out of 4
1 out of 3
1 out of 4

1 out of 3

Back-up trip mode

RetripMode

Retrip Off
CB Pos Check
No CBPos Check

Retrip Off

Operation mode of re-trip logic

IP>

5 - 200

%IB

10

Operate phase current level in % of IBase

IN>

2 - 200

%IB

10

Operate residual current level in % of


IBase

t1

0.000 - 60.000

0.001

0.000

Time delay of re-trip

t2

0.000 - 60.000

0.001

0.150

Time delay of back-up trip

t2MPh

0.000 - 60.000

0.001

0.150

Time delay of back-up trip at multi-phase


start

tPulse

0.000 - 60.000

0.001

0.200

Trip pulse duration

Table 222:
Name

CCRBRF Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

I>BlkCont

5 - 200

%IB

20

Current for blocking of CB contact


operation in % of IBase

t3

0.000 - 60.000

0.001

0.030

Additional time delay to t2 for a second


back-up trip

tCBAlarm

0.000 - 60.000

0.001

5.000

Time delay for CB faulty signal

7.8.6

Technical data
Table 223:

CCRBRF technical data

Function

Range or value

Accuracy

Operate phase
current

(5-200)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio, phase


current

> 95%

Operate residual
current

(2-200)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio, residual


current

> 95%

Phase current level


for blocking of
contact function

(5-200)% of lBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Timers

(0.000-60.000) s

0.5% 10 ms

Operate time for


current detection

10 ms typically

Reset time for


current detection

15 ms maximum

414
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.9

Stub protection STBPTOC


Function description
Stub protection

IEC 61850
identification

IEC 60617
identification

STBPTOC

ANSI/IEEE C37.2
device number
50STB

3I>STUB
SYMBOL-T V1 EN

7.9.1

Introduction
When a power line is taken out of service for maintenance and the line
disconnector is opened in multi-breaker arrangements the voltage transformers will
mostly be outside on the disconnected part. The primary line distance protection
will thus not be able to operate and must be blocked.
The stub protection STBPTOC covers the zone between the current transformers
and the open disconnector. The three-phase instantaneous overcurrent function is
released from a normally open, NO (b) auxiliary contact on the line disconnector.

7.9.2

Principle of operation
The sampled analog phase currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of each phase current
the RMS value of each phase current is derived. These phase current values are fed
to a comparator in the stub protection function STBPTOC. In a comparator the
RMS values are compared to the set operating current value of the function I>.
If a phase current is larger than the set operating current the signal from the
comparator for this phase is activated. This signal will, in combination with the
release signal from line disconnection (RELEASE input), activate the timer for the
TRIP signal. If the fault current remains during the timer delay t, the TRIP output
signal is activated. The function can be blocked by activation of the BLOCK input.

415
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

STUB PROTECTION FUNCTION

BLOCK
TRIP

AND

STIL1
OR

STIL2
STIL3
RELEASE

en05000731.vsd
IEC05000731 V1 EN

Figure 232:

7.9.3

Simplified logic diagram for Stub protection

Function block
STBPTOC
I3P*
BLOCK
BLKTR
RELEASE

TRIP
START

IEC05000678-2-en.vsd
IEC05000678 V2 EN

Figure 233:

7.9.4

STBPTOC function block

Input and output signals


Table 224:
Name

STBPTOC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase currents

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block of trip

RELEASE

BOOLEAN

Release of stub protection

Table 225:
Name

STBPTOC Output signals


Type

Description

TRIP

BOOLEAN

Trip

START

BOOLEAN

General start

416
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.9.5
Table 226:

Setting parameters
STBPTOC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

ReleaseMode

Release
Continuous

Release

Release of stub protection

I>

1 - 2500

%IB

200

Operate current level in % of IBase

Table 227:

STBPTOC Group settings (advanced)

Name
t

7.9.6

7.10

Values (Range)

Unit

0.000 - 60.000

Step
0.001

Default

Description

0.000

Time delay

Technical data
Table 228:

STBPTOC technical data

Function

Range or value

Accuracy

Operating current

(1-2500)% of IBase

1.0% of Ir at I Ir
1.0% of I at I > Ir

Reset ratio

> 95%

Definite time

(0.000-60.000) s

0.5% 10 ms

Operating time, start


function

20 ms typically at 0 to 2 x Iset

Resetting time,
startfunction

25 ms typically at 2 to 0 x Iset

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Pole discordance protection CCRPLD


Function description
Pole discordance protection

IEC 61850
identification

IEC 60617
identification

CCRPLD

ANSI/IEEE C37.2
device number
52PD

PD
SYMBOL-S V1 EN

417
Technical reference manual

Section 7
Current protection
7.10.1

1MRK 505 222-UEN B

Introduction
An open phase can cause negative and zero sequence currents which cause thermal
stress on rotating machines and can cause unwanted operation of zero sequence or
negative sequence current functions.
Normally the own breaker is tripped to correct such a situation. If the situation
persists the surrounding breakers should be tripped to clear the unsymmetrical load
situation.
The Polediscordance protection function CCRPLD operates based on information
from auxiliary contacts of the circuit breaker for the three phases with additional
criteria from unsymmetrical phase currents when required.

7.10.2

Principle of operation
The detection of pole discordance can be made in two different ways. If the contact
based function is used an external logic can be made by connecting the auxiliary
contacts of the circuit breaker so that a pole discordance is indicated, see figure 234.
circuit breaker

Pole discordance signal from circuit breaker


en05000287.vsd
IEC05000287 V2 EN

Figure 234:

Pole discordance external detection logic

This binary signal is connected to a binary input of the IED. The appearance of this
signal will start a timer that will give a trip signal after the set time delay.
There is also a possibility to connect all phase selective auxiliary contacts (phase
contact open and phase contact closed) to binary inputs of the IED, see figure 235.

418
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

C.B.

poleOneClosed from C.B.


poleTwoClosed from C.B.
poleThreeClosed from C.B.
+

poleOneOpened from C.B.


poleTwoOpened from C.B.
poleThreeOpened from C.B.
en05000288.vsd

IEC05000288 V1 EN

Figure 235:

Pole discordance signals for internal logic

In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set
delay.
Pole discordance can also be detected by means of phase selective current
measurement. The sampled analog phase currents are pre-processed in a discrete
Fourier filter (DFT) block. From the fundamental frequency components of each
phase current the RMS value of each phase current is derived. The smallest and the
largest phase current are derived. If the smallest phase current is lower than the
setting CurrUnsymLevel times the largest phase current the settable trip timer
(tTrip) is started. The tTrip timer gives a trip signal after the set delay. The TRIP
signal is a pulse 150 ms long. The current based pole discordance function can be
set to be active either continuously or only directly in connection to breaker open
or close command.
The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discordance function can be blocked during sequences
with a single pole open if single pole autoreclosing is used.
The simplified block diagram of the current and contact based Pole discordance
protection function CCRPLD is shown in figure 236.

419
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

BLOCK
OR

BLKDBYAR

PolPosAuxCont
AND

POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL

Discordance
detection
AND

t
t

150 ms
TRIP

OR
PD Signal from CB
AND

EXTPDIND
CLOSECMD

t+200 ms
OR

OPENCMD

AND
Unsymmetry current
detection
en05000747.vsd
IEC05000747 V1 EN

Figure 236:

Simplified block diagram of pole discordance function CCRPLD contact and current based

CCRPLDis blocked if:

The IED is in TEST mode and CCRPLD has been blocked from the local HMI
The input signal BLOCK is high
The input signal BLKDBYAR is high

The BLOCK signal is a general purpose blocking signal of the pole discordance
protection. It can be connected to a binary input in the IED in order to receive a
block command from external devices or can be software connected to other
internal functions in the IED itself in order to receive a block command from
internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The BLKDBYAR signal blocks the pole discordance operation when a single
phase autoreclosing cycle is in progress. It can be connected to the output signal
1PT1 on SMBRRECfunction block. If the autoreclosing function is an external
device, then BLKDBYAR has to be connected to a binary input in the IED and this
binary input is connected to a signalization 1phase autoreclosing in progress
from the external autoreclosing device.
If the pole discordance protection is enabled, then two different criteria can
generate a trip signal TRIP:

Pole discordance signaling from the circuit breaker.


Unsymmetrical current detection.

420
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.10.2.1

Pole discordance signaling from circuit breaker


If one or two poles of the circuit breaker have failed to open or to close the pole
discordance status, then the function input EXTPDIND is activated from the pole
discordance signal derived from the circuit breaker auxiliary contacts (one NO
contact for each phase connected in parallel, and in series with one NC contact for
each phase connected in parallel) and, after a settable time interval tTrip (0-60 s), a
150 ms trip pulse command TRIP is generated by the Polediscordance function.

7.10.2.2

Unsymmetrical current detection


Unsymmetrical current indicated if:

any phase current is lower than CurrUnsymLevel of the highest current in the
three phases.
the highest phase current is greater than CurrRelLevel of IBase.

If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set
time delay tTrip if the detection occurs in the next 200 ms after the circuit breaker
has received a command to open trip or close and if the unbalance persists. The 200
ms limitation is for avoiding unwanted operation during unsymmetrical load
conditions.
The pole discordance protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs
can be connected to terminal binary inputs if the information are generated from
the field (that is from auxiliary contacts of the close and open push buttons) or may
be software connected to the outputs of other integrated functions (that is close
command from a control function or a general trip from integrated protections).

7.10.3

Function block
CCRPLD
I3P*
BLOCK
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
POLE1OPN
POLE1CL
POLE2OPN
POLE2CL
POLE3OPN
POLE3CL

TRIP
START

IEC06000275-2-en.vsd
IEC06000275 V2 EN

Figure 237:

CCRPLD function block

421
Technical reference manual

Section 7
Current protection
7.10.4

1MRK 505 222-UEN B

Input and output signals


Table 229:

CCRPLD Input signals

Name

Type
GROUP
SIGNAL

Three phase currents

BLOCK

BOOLEAN

Block of function

BLKDBYAR

BOOLEAN

Block of function at CB single phase auto reclosing cycle

CLOSECMD

BOOLEAN

Close order to CB

OPENCMD

BOOLEAN

Open order to CB

EXTPDIND

BOOLEAN

Pole discordance signal from CB logic

POLE1OPN

BOOLEAN

Pole one opened indication from CB

POLE1CL

BOOLEAN

Pole one closed indication from CB

POLE2OPN

BOOLEAN

Pole two opened indication from CB

POLE2CL

BOOLEAN

Pole two closed indication from CB

POLE3OPN

BOOLEAN

Pole three opened indication from CB

POLE3CL

BOOLEAN

Pole three closed indication from CB

CCRPLD Output signals

Name

Table 231:
Name

Description

I3P

Table 230:

7.10.5

Default

Type

Description

TRIP

BOOLEAN

Trip signal to CB

START

BOOLEAN

Trip condition TRUE, waiting for time delay

Setting parameters
CCRPLD Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current

tTrip

0.000 - 60.000

0.001

0.300

Time delay between trip condition and


trip signal

ContSel

Off
PD signal from CB
Pole pos aux cont.

Off

Contact function selection

CurrSel

Off
CB oper monitor
Continuous monitor

Off

Current function selection

CurrUnsymLevel

0 - 100

80

Unsym magn of lowest phase current


compared to the highest.

CurrRelLevel

0 - 100

%IB

10

Current magnitude for release of the


function in % of IBase

422
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.10.6

Technical data
Table 232:

CCRPLD technical data

Function

7.11

Range or value

Accuracy

Operate current

(0100)% of IBase

1.0% of Ir

Time delay

(0.000-60.000) s

0.5% 10 ms

Directional underpower protection GUPPDUP


Function description
Directional underpower protection

IEC 61850
identification
GUPPDUP

IEC 60617
identification

P<

ANSI/IEEE C37.2
device number
37

SYMBOL-LL V1 EN

7.11.1

Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 238 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a
higher margin and should provide better dependability. On the other hand, the risk
for unwanted operation immediately after synchronization may be higher. One
should set the underpower IED to trip if the active power from the generator is less
than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1% depending on the type of turbine.
When IED with a metering class input CTs is used pickup can be set to more
sensitive value (e.g.0,5% or even to 0,2%).

423
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Underpower IED

Operate
Line

Overpower IED

Operate
Line

Margin

Margin

Operating point
without
turbine torque

Operating point
without
turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN

Figure 238:

7.11.2

Protection with underpower IED and overpower IED

Principle of operation
A simplified scheme showing the principle of the power protection function is
shown in figure 239. The function has two stages with individual settings.

Chosen current
phasors

Chosen voltage
phasors

P
Complex
power
calculation

Derivation of
S(composant)
in Char angle

S(angle)

S(angle) <
Power1

TRIP1
START1

S(angle) <
Power2

TRIP2
START2

P = POWRE
Q = POWIM

IEC09000018-2-en.vsd
IEC09000018 V2 EN

Figure 239:

Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 233.

424
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Table 233:
Set value: Mode
L1, L2, L3

Complex power calculation


Formula used for complex power calculation

S = U L1 I L1* + U L 2 I L 2* + U L 3 I L 3*
(Equation 96)

EQUATION1697 V1 EN

Arone

S = U L1L 2 I L1* - U L 2 L 3 I L 3*
EQUATION1698 V1 EN

PosSeq

S = 3 U PosSeq I PosSeq *
EQUATION1699 V1 EN

L1L2

(Equation 102)

S = 3 U L 2 I L 2*
EQUATION1704 V1 EN

L3

(Equation 101)

S = 3 U L1 I L1*
EQUATION1703 V1 EN

L2

(Equation 100)

S = U L 3 L1 ( I L 3* - I L1* )
EQUATION1702 V1 EN

L1

(Equation 99)

S = U L 2 L 3 ( I L 2* - I L 3* )
EQUATION1701 V1 EN

L3L1

(Equation 98)

S = U L1L 2 ( I L1* - I L 2* )
EQUATION1700 V1 EN

L2L3

(Equation 97)

(Equation 103)

S = 3 U L 3 I L 3*
EQUATION1705 V1 EN

(Equation 104)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is
calculated. If this angle is 0 the active power component P is calculated. If this
angle is 90 the reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting
Power1(2). For directional underpower protection, a start signal START1(2) is
activated if the calculated power component is smaller than the pick up value. For
directional overpower protection, a start signal START1(2) is activated if the
calculated power component is larger than the pick up value. After a set time delay
TripDelay1(2) a trip TRIP1(2) signal is activated if the start signal is still active. At
activation of any of the two stages a common signal START will be activated. At
trip from any of the two stages also a common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The
absolute hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) + droppower1(2)). For generator low forward power protection the power setting is very

425
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

low, normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be
calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2) +
Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the droppower1(2) would be too small. In such cases, the hysteresis1 greater than (0.5
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value, the function will
reset after a set time DropDelay1(2). The reset means that the start signal will drop
out and that the timer of the stage will reset.

7.11.2.1

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is
possible to introduce the recursive, low pass filtering of the measured values for S
(P, Q). This will make slower measurement response to the step changes in the
measured quantity. Filtering is performed in accordance with the following
recursive formula:
S = k SOld + (1 - k ) SCalculated
(Equation 105)

EQUATION1959 V1 EN

Where
S

is a new measured value to be used for the protection function

Sold

is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle


k
TD

is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for
k=0.92 in case of slow operating functions.

7.11.2.2

Calibration of analog inputs


Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
240.

426
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

IEC05000652 V2 EN

Figure 240:

Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values
or in the disturbance report. The active power is provided as MW value: P, or in
percent of base power: PPERCENT. The reactive power is provided as Mvar value:
Q, or in percent of base power: QPERCENT.

7.11.3

Function block
GUPPDUP
I3P*
U3P*
BLOCK
BLOCK1
BLOCK2

TRIP
TRIP1
TRIP2
START
START1
START2
P
PPERCENT
Q
QPERCENT
IEC07000027-2-en.vsd

IEC07000027 V2 EN

Figure 241:

GUPPDUP function block

427
Technical reference manual

Section 7
Current protection
7.11.4

1MRK 505 222-UEN B

Input and output signals


Table 234:

GUPPDUP Input signals

Name

Type
GROUP
SIGNAL

Current group connection

U3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLOCK1

BOOLEAN

Block of stage 1

BLOCK2

BOOLEAN

Block of stage 2

GUPPDUP Output signals

Name

Table 236:
Name

Description

I3P

Table 235:

7.11.5

Default

Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip of stage 1

TRIP2

BOOLEAN

Trip of stage 2

START

BOOLEAN

Common start

START1

BOOLEAN

Start of stage 1

START2

BOOLEAN

Start of stage 2

REAL

Active Power in MW

PPERCENT

REAL

Active power in % of SBASE

REAL

Reactive power in Mvar

QPERCENT

REAL

Reactive power in % of SBASE

Setting parameters
GUPPDUP Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

OpMode1

Off
UnderPower

UnderPower

Operation mode 1

Power1

0.0 - 500.0

%SB

0.1

1.0

Power setting for stage 1 in % of Sbase

Angle1

-180.0 - 180.0

Deg

0.1

0.0

Angle for stage 1

TripDelay1

0.010 - 6000.000

0.001

1.000

Trip delay for stage 1

DropDelay1

0.010 - 6000.000

0.001

0.060

Drop delay for stage 1

OpMode2

Off
UnderPower

UnderPower

Operation mode 2

Power2

0.0 - 500.0

%SB

0.1

1.0

Power setting for stage 2 in % of Sbase

Angle2

-180.0 - 180.0

Deg

0.1

0.0

Angle for stage 2

TripDelay2

0.010 - 6000.000

0.001

1.000

Trip delay for stage 2

DropDelay2

0.010 - 6000.000

0.001

0.060

Drop delay for stage 2

428
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Table 237:

GUPPDUP Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

0.000 - 0.999

0.001

0.000

Low pass filter coefficient for power


measurement, P and Q

Hysteresis1

0.2 - 5.0

pu

0.1

0.5

Absolute hysteresis of stage 1 in % Sbase

Hysteresis2

0.2 - 5.0

pu

0.1

0.5

Absolute hysteresis of stage 2 in % Sbase

IAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


5% of Ir

IAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


30% of Ir

IAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


100% of Ir

UAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


5% of Ur

UAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


30% of Ur

UAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


100% of Ur

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of Ir

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of Ir

Table 238:

GUPPDUP Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

Mode

L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

Pos Seq

Selection of measured current and


voltage

7.11.6

Technical data
Table 239:

GUPPDUP technical data

Function
Power level

Range or value
(0.0500.0)% of SBase
At low setting:
(0.5-2.0)% of SBase
(2.0-10)% of SBase

Accuracy
1.0% of Sr at S < Sr
1.0% of S at S > Sr
< 50% of set value
< 20% of set value

Characteristic angle

(-180.0180.0) degrees

2 degrees

Timers

(0.00-6000.00) s

0.5% 10 ms

429
Technical reference manual

Section 7
Current protection

7.12

1MRK 505 222-UEN B

Directional overpower protection GOPPDOP


Function description
Directional overpower protection

IEC 61850
identification
GOPPDOP

IEC 60617
identification

ANSI/IEEE C37.2
device number
32

P>
DOCUMENT172362-IMG158942
V1 EN

7.12.1

Introduction
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
Figure 242 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a
higher margin and should provide better dependability. On the other hand, the risk
for unwanted operation immediately after synchronization may be higher. One
should set the underpower IED to trip if the active power from the generator is less
than about 2%. One should set the overpower IED to trip if the power flow from
the network to the generator is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more
sensitive value (e.g.0,5% or even to 0,2%).

430
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Underpower IED

Operate
Line

Overpower IED

Operate
Line

Margin

Margin

Operating point
without
turbine torque

Operating point
without
turbine torque

IEC06000315-2-en.vsd
IEC06000315 V2 EN

Figure 242:

7.12.2

Reverse power protection with underpower IED and overpower IED

Principle of operation
A simplified scheme showing the principle of the power protection function is
shown in figure 243. The function has two stages with individual settings.

Chosen current
phasors

Chosen voltage
phasors

P
Complex
power
calculation

Derivation of
S(composant)
in Char angle

S(angle)

S(angle) >
Power1

TRIP1
START1

S(angle) >
Power2

TRIP2
START2

P = POWRE
Q = POWIM

IEC06000567-2-en.vsd
IEC06000567 V2 EN

Figure 243:

Simplified logic diagram of the power protection function

The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 240.

431
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

Table 240:
Set value: Mode
L1, L2, L3

Complex power calculation


Formula used for complex power calculation

S = U L1 I L1* + U L 2 I L 2* + U L 3 I L 3*
(Equation 106)

EQUATION1697 V1 EN

Arone

S = U L1L 2 I L1* - U L 2 L 3 I L 3*
(Equation 107)

EQUATION1698 V1 EN

PosSeq

S = 3 U PosSeq I PosSeq *
(Equation 108)

EQUATION1699 V1 EN

L1L2

S = U L1L 2 ( I L1* - I L 2* )
(Equation 109)

EQUATION1700 V1 EN

L2L3

S = U L 2 L 3 ( I L 2* - I L 3* )
(Equation 110)

EQUATION1701 V1 EN

L3L1

S = U L 3 L1 ( I L 3* - I L1* )
EQUATION1702 V1 EN

L1

S = 3 U L1 I L1*
EQUATION1703 V1 EN

L2

(Equation 112)

S = 3 U L 2 I L 2*
EQUATION1704 V1 EN

L3

(Equation 111)

(Equation 113)

S = 3 U L 3 I L 3*
EQUATION1705 V1 EN

(Equation 114)

The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is
calculated. If this angle is 0 the active power component P is calculated. If this
angle is 90 the reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting
Power1(2). A start signal START1(2) is activated if the calculated power
component is larger than the pick up value. After a set time delay TripDelay1(2) a
trip TRIP1(2) signal is activated if the start signal is still active. At activation of
any of the two stages a common signal START will be activated. At trip from any
of the two stages also a common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The
absolute hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) droppower1(2)). For generator reverse power protection the power setting is very low,
normally down to 0.02 p.u. of rated generator power. The hysteresis should
therefore be set to a smaller value. The drop-power value of stage1 can be

432
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

calculated with the Power1(2), Hysteresis1(2): drop-power1(2) = Power1(2)


Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the droppower1(2) would be too small. In such cases, the hysteresis1 greater than (0.5
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the start signal will drop out
ant that the timer of the stage will reset.

7.12.2.1

Low pass filtering


In order to minimize the influence of the noise signal on the measurement it is
possible to introduce the recursive, low pass filtering of the measured values for S
(P, Q). This will make slower measurement response to the step changes in the
measured quantity. Filtering is performed in accordance with the following
recursive formula:
S = k SOld + (1 - k ) SCalculated
(Equation 115)

EQUATION1959 V1 EN

Where
S

is a new measured value to be used for the protection function

Sold

is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle


k

is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k =
0.92 in case of slow operating functions.

7.12.2.2

Calibration of analog inputs


Measured currents and voltages used in the Power function can be calibrated to get
class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in figure
244.

433
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

IEC05000652 V2 EN

Figure 244:

Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the
disturbance report. The active power is provided as MW value: P, or in percent of
base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.

7.12.3

Function block
GOPPDOP
I3P*
U3P*
BLOCK
BLOCK1
BLOCK2

TRIP
TRIP1
TRIP2
START
START1
START2
P
PPERCENT
Q
QPERCENT
IEC07000028-2-en.vsd

IEC07000028 V2 EN

Figure 245:

GOPPDOP function block

434
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.12.4

Input and output signals


Table 241:

GOPPDOP Input signals

Name

Type
GROUP
SIGNAL

Current group connection

U3P

GROUP
SIGNAL

Voltage group connection

BLOCK

BOOLEAN

Block of function

BLOCK1

BOOLEAN

Block of stage 1

BLOCK2

BOOLEAN

Block of stage 2

GOPPDOP Output signals

Name

Table 243:

Description

I3P

Table 242:

7.12.5

Default

Type

Description

TRIP

BOOLEAN

Common trip signal

TRIP1

BOOLEAN

Trip of stage 1

TRIP2

BOOLEAN

Trip of stage 2

START

BOOLEAN

Common start

START1

BOOLEAN

Start of stage 1

START2

BOOLEAN

Start of stage 2

REAL

Active Power in MW

PPERCENT

REAL

Active power in % of SBASE

REAL

Reactive power in Mvar

QPERCENT

REAL

Reactive power in % of SBASE

Setting parameters
GOPPDOP Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

OpMode1

Off
OverPower

OverPower

Operation mode 1

Power1

0.0 - 500.0

%SB

0.1

120.0

Power setting for stage 1 in % of Sbase

Angle1

-180.0 - 180.0

Deg

0.1

0.0

Angle for stage 1

TripDelay1

0.010 - 6000.000

0.001

1.000

Trip delay for stage 1

DropDelay1

0.010 - 6000.000

0.001

0.060

Drop delay for stage 1

OpMode2

Off
OverPower

OverPower

Operation mode 2

Power2

0.0 - 500.0

%SB

0.1

120.0

Power setting for stage 2 in % of Sbase

Angle2

-180.0 - 180.0

Deg

0.1

0.0

Angle for stage 2

TripDelay2

0.010 - 6000.000

0.001

1.000

Trip delay for stage 2

DropDelay2

0.010 - 6000.000

0.001

0.060

Drop delay for stage 2


435

Technical reference manual

Section 7
Current protection

Table 244:
Name

1MRK 505 222-UEN B

GOPPDOP Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

0.000 - 0.999

0.001

0.000

Low pass filter coefficient for power


measurement, P and Q

Hysteresis1

0.2 - 5.0

pu

0.1

0.5

Absolute hysteresis of stage 1 in % of


Sbase

Hysteresis2

0.2 - 5.0

pu

0.1

0.5

Absolute hysteresis of stage 2 in % of


Sbase

IAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


5% of Ir

IAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


30% of Ir

IAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


100% of Ir

UAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


5% of Ur

UAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


30% of Ur

UAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


100% of Ur

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of Ir

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of Ir

Table 245:
Name

GOPPDOP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

IBase

1 - 99999

3000

Base setting for current level

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

Mode

L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

Pos Seq

Selection of measured current and


voltage

436
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.12.6

Technical data
Table 246:

GOPPDOP technical data

Function

Range or value

Power level

Accuracy

(0.0500.0)% of Sbase

1.0% of Sr at S < Sr
1.0% of S at S > Sr

At low setting:
(0.5-2.0)% of Sbase
(2.0-10)% of Sbase

7.13

Characteristic angle

(-180.0180.0) degrees

2 degrees

Timers

(0.00-6000.00) s

0.5% 10 ms

Broken conductor check BRCPTOC


Function description
Broken conductor check

7.13.1

< 50% of set value


< 20% of set value

IEC 61850
identification
BRCPTOC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
46

Introduction
Conventional protection functions can not detect the broken conductor condition.
Broken conductor check (BRCPTOC) function, consisting of continuous current
unsymmetrical check on the line where the IED is connected will give alarm or trip
at detecting broken conductors.

7.13.2

Principle of operation
Broken conductor check (BRCPTOC) detects a broken conductor condition by
detecting the asymmetry between currents in the three phases. The currentmeasuring elements continuously measure the three-phase currents.
The current asymmetry signal output START is set on if:

The difference in currents between the phase with the lowest current and the
phase with the highest current is greater than set percentage Iub> of the
highest phase current
The highest phase current is greater than the minimum setting value IP>.
The lowest phase current is below 50% of the minimum setting value IP>

The third condition is included to avoid problems in systems involving parallel


lines. If a conductor breaks in one phase on one line, the parallel line will
experience an increase in current in the same phase. This might result in the first
two conditions being satisfied. If the unsymmetrical detection lasts for a period
longer than the set time tOper the TRIP output is activated.
437
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

The simplified logic diagram of the broken conductor check function is shown in
figure 246
BRCPTOC is disabled (blocked) if:

The IED is in TEST status and the function has been blocked from the local
HMI test menu (BlockBRC=Yes).
The input signal BLOCK is high.

The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices, or can be software connected to other
internal functions of the IED itself to receive a block command from internal
functions.
The output trip signal TRIP is a three-phase trip. It can be used to command a trip
to the circuit breaker or for alarm purpose only.
TEST
TEST-ACTIVE

&
Block BRCPTOC=Yes
START

=1

BLOCK

Function Enable
&

Unsymmetrical
Current Detection

t
t

TRIP

STI
IL1<50%IP>
IL2<50%IP>

=1

IL3<50%IP>
IEC09000158-1-en.vsd
IEC09000158 V1 EN

Figure 246:

7.13.3

Simplified logic diagram for Broken conductor check BRCPTOC

Function block
BRCPTOC
I3P*
BLOCK
BLKTR

TRIP
START

IEC07000034-2-en.vsd
IEC07000034 V2 EN

Figure 247:

BRCPTOC function block

438
Technical reference manual

Section 7
Current protection

1MRK 505 222-UEN B

7.13.4

Input and output signals


Table 247:

BRCPTOC Input signals

Name

Type
GROUP
SIGNAL

Group signal for current input

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Blocks the operate output

BRCPTOC Output signals

Name

Table 249:

Description

I3P

Table 248:

7.13.5

Default

Type

Description

TRIP

BOOLEAN

Operate signal of the protection logic

START

BOOLEAN

Start signal of the protection logic

Setting parameters
BRCPTOC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

0 - 99999

3000

IBase

Iub>

50 - 90

%IM

50

Unbalance current operation value in


percent of max current

IP>

5 - 100

%IB

20

Minimum phase current for operation of


Iub> in % of Ibase

tOper

0.000 - 60.000

0.001

5.000

Operate time delay

Table 250:

BRCPTOC Group settings (advanced)

Name
tReset

7.13.6

Values (Range)

Unit

0.010 - 60.000

Step
0.001

Default

Description

0.100

Time delay in reset

Technical data
Table 251:

BRCPTOC technical data

Function

Range or value

Accuracy

Minimum phase current for operation

(5100)% of IBase

0.1% of Ir

Unbalance current operation

(0100)% of maximum current

0.1% of Ir

Timer

(0.00-6000.00) s

0.5% 10 ms

439
Technical reference manual

440

Section 8
Voltage protection

1MRK 505 222-UEN B

Section 8

Voltage protection

About this chapter


This chapter describes voltage related protection functions. The way the functions
work, their setting parameters, function blocks, input and output signals and
technical data are included for each function.

8.1

Two step undervoltage protection UV2PTUV


Function description
Two step undervoltage protection

IEC 61850
identification

IEC 60617
identification

UV2PTUV

ANSI/IEEE C37.2
device number
27

2U<
SYMBOL-R-2U-GREATER THAN
V1 EN

8.1.1

Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed
back-up to primary protection.
UV2PTUV has two voltage steps, each with inverse or definite time delay.

8.1.2

Principle of operation
Two-step undervoltage protection (UV2PTUV) is used to detect low power system
voltage. UV2PTUV has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding
START signal is generated. UV2PTUV can be set to START/TRIP based on 1 out
of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being below the set point. If
the voltage remains below the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued. To avoid an unwanted
trip due to disconnection of the related high voltage equipment, a voltage
controlled blocking of the function is available, that is, if the voltage is lower than
the set blocking level the function is blocked and no START or TRIP signal is
generated.The time delay characteristic is individually chosen for each step and can
be either definite time delay or inverse time delay.

441
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

UV2PTUV can be set to measure phase-to-earth fundamental value, phase-to-phase


fundamental value, phase-to-earth true RMS value or phase-to-phase true RMS
value. The choice of the measuring is done by the parameter ConnType. The
voltage related settings are made in percent of base voltage which is set in kV phaseto-phase voltage. This means operation for phase-to-earth voltage under:

U < (%) UBase(kV )


3
(Equation 116)

EQUATION1429 V2 EN

and operation for phase-to-phase voltage under:


U < (%) UBase(kV)
(Equation 117)

EQUATION1990 V1 EN

When phase-to-earth voltage measurement is selected the function


automatically introduces division of the base value by the square
root of three.

8.1.2.1

Measurement principle
Depending on the set ConnType value, UV2PTUV measures phase-to-earth or phaseto-phase voltages and compare against set values, U1< and U2<. The parameters
OpMode1 and OpMode2 influence the requirements to activate the START
outputs. Either 1 out of 3, 2 out of 3, or 3 out of 3 measured voltages have to be
lower than the corresponding set point to issue the corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.

8.1.2.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay three different modes are available:

inverse curve A
inverse curve B
customer programmable inverse curve

The type A curve is described as:

t=

k
U < -U

U<

EQUATION1431 V1 EN

(Equation 118)

442
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

The type B curve is described as:

t=

k 480
U < -U

- 0.5
32
U<

2.0

+ 0.055

EQUATION1432 V1 EN

(Equation 119)

The customer programmable curve can be created as:

kA

+D
t=
p
U < -U

-C
B
U<

EQUATION1433 V1 EN

(Equation 120)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U<
down to U< (1.0 CrvSatn/100) the used voltage will be: U< (1.0 CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100

EQUATION1435 V1 EN

(Equation 121)

The lowest voltage is always used for the inverse time delay integration. The
details of the different inverse time characteristics are shown in section 22.3
"Inverse characteristics".
Trip signal issuing requires that the undervoltage condition continues for at least
the user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by some special voltage level dependent time curves for the
inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and
tIReset2pickup for the inverse time) the corresponding start output is reset. Here it
should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Note that for the undervoltage function the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 248 and figure 249.

443
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

tReset1
Voltage

tReset1
START
Hysteresis

Measured
Voltage

TRIP

U1<

Time
t1

START
TRIP

Time
Integrator

Frozen Timer

t1

Instantaneous
Reset

Time
Linear Decrease

IEC05000010-3-en.vsd

IEC05000010 V3 EN

Figure 248:

Voltage profile not causing a reset of the start signal for step 1, and inverse time delay

444
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

tReset1

Voltage
START

START

tReset1
Hysteresis

Measured Voltage
TRIP

U1<

Time
t1

START

TRIP

Time Integrator

Frozen Timer

t1

Time
Instantaneous
Reset

Linear Decrease
IEC05000011-en-2.vsd

IEC05000011 V2 EN

Figure 249:

Voltage profile causing a reset of the start signal for step 1, and inverse time delay

Definite timer delay


When definite time delay is selected the function will operate as shown in figure
250. Detailed information about individual stage reset/operation behavior is shown
in figure 251 and figure 252 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured.

445
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

ST1

a
b>a

U1<

tReset1

t1

TR1

AND
OFF
Delay

ON
Delay

IEC09000785-1-en.vsd
IEC09000785 V1 EN

Figure 250:

Detailed logic diagram for step 1, DT operation

Un<

START

TRIP
tResetn

tn

IEC10000039-1-en.vsd
IEC10000039 V1 EN

Figure 251:

Example for Definite Time Delay stage rest

446
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Un<

START

TRIP

tResetn

tn

IEC10000040-1-en.vsd
IEC10000040 V1 EN

Figure 252:

8.1.2.3

Example for Definite Time Delay stage operation

Blocking
It is possible to block Two step undervoltage protection UV2PTUV partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLKST1:

blocks all start and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLKST2:

blocks all start and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Off resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure 253. The delay of the blocking function must
be set less than the time delay of under voltage function.

447
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Disconnection

Normal voltage
U1<
U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1

tBlkUV2 <
t2,t2Min

IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
IEC05000466 V1 EN

Figure 253:

8.1.2.4

Blocking function

Design
The voltage measuring elements continuously measure the three phase-to-neutral
voltages or the three phase-to-phase voltages. Recursive fourier filters or true RMS
filters of input voltage signals are used. The voltages are individually compared to
the set value, and the lowest voltage is used for the inverse time characteristic
integration. A special logic is included to achieve the 1 out of 3, 2 out of 3 and 3
out of 3 criteria to fulfill the START condition. The design of Two step
undervoltage protection UV2PTUV is schematically shown in Figure 254.

448
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

UL1

Comparator
UL1 < U1<

UL2

Comparator
UL2 < U1<

UL3

Comparator
UL3 < U1<

ST1L1
Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3

Phase 1

ST1L2
Phase 2
Phase 3

START

MinVoltSelect
or

Time integrator
t1
tReset1
ResetTypeCrv1

Start
&
Trip
Output
Logic

ST1L3
ST1

OR

TR1L1

Step 1

TR1L2

TRIP

TR1L3
TR1

OR

Comparator
UL1 < U2<
Comparator
UL2 < U2<
Comparator
UL3 < U2<

Voltage Phase
Selector
OpMode2
1 out of 3
2 outof 3
3 out of 3

Time integrator
t2
tReset2
ResetTypeCrv2

ST2L2

Phase 2
Phase 3

START

MinVoltSelect
or

ST2L1

Phase 1

Start
&
Trip
Output
Logic

ST2L3
ST2

OR

TR2L1

Step 2

TR2L2

TRIP
TR2L3

TR2

OR

OR START

OR

TRIP

en05000012.vsd
IEC05000834 V1 EN

Figure 254:

Schematic design of Two step undervoltage protection UV2PTUV

449
Technical reference manual

Section 8
Voltage protection
8.1.3

1MRK 505 222-UEN B

Function block
UV2PTUV
U3P*
BLOCK
BLKTR1
BLKST1
BLKTR2
BLKST2

TRIP
TR1
TR1L1
TR1L2
TR1L3
TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3
IEC06000276-2-en.vsd

IEC06000276 V2 EN

Figure 255:

8.1.4

UV2PTUV function block

Input and output signals


Table 252:
Name

UV2PTUV Input signals


Type

Default

Description

U3P

GROUP
SIGNAL

Three phase voltages

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of operate signal, step 1

BLKST1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of operate signal, step 2

BLKST2

BOOLEAN

Block of step 2

Table 253:
Name

UV2PTUV Output signals


Type

Description

TRIP

BOOLEAN

Trip

TR1

BOOLEAN

Common trip signal from step1

TR1L1

BOOLEAN

Trip signal from step1 phase L1

TR1L2

BOOLEAN

Trip signal from step1 phase L2

TR1L3

BOOLEAN

Trip signal from step1 phase L3

TR2

BOOLEAN

Common trip signal from step2

TR2L1

BOOLEAN

Trip signal from step2 phase L1

TR2L2

BOOLEAN

Trip signal from step2 phase L2

TR2L3

BOOLEAN

Trip signal from step2 phase L3

START

BOOLEAN

General start signal

Table continues on next page

450
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

8.1.5
Table 254:

Type

Description

ST1

BOOLEAN

Common start signal from step1

ST1L1

BOOLEAN

Start signal from step1 phase L1

ST1L2

BOOLEAN

Start signal from step1 phase L2

ST1L3

BOOLEAN

Start signal from step1 phase L3

ST2

BOOLEAN

Common start signal from step2

ST2L1

BOOLEAN

Start signal from step2 phase L1

ST2L2

BOOLEAN

Start signal from step2 phase L2

ST2L3

BOOLEAN

Start signal from step2 phase L3

Setting parameters
UV2PTUV Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

OperationStep1

Off
On

On

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 1

OpMode1

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of


3, 2 of 3, 3 of 3) from step 1

U1<

1 - 100

%UB

70

Voltage setting/start val (DT & IDMT) in


% of UBase, step 1

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 1

k1

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 1

IntBlkSel1

Off
Block of trip
Block all

Off

Internal (low level) blocking mode, step 1

IntBlkStVal1

1 - 100

%UB

20

Voltage setting for internal blocking in %


of UBase, step 1

tBlkUV1

0.000 - 60.000

0.001

0.000

Time delay of internal (low level)


blocking for step 1

HystAbs1

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 1

OperationStep2

Off
On

On

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 2

Table continues on next page

451
Technical reference manual

Section 8
Voltage protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

OpMode2

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of


3, 2 of 3, 3 of 3) from step 2

U2<

1 - 100

%UB

50

Voltage setting/start val (DT & IDMT) in


% of UBase, step 2

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 2

k2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 2

IntBlkSel2

Off
Block of trip
Block all

Off

Internal (low level) blocking mode, step 2

IntBlkStVal2

1 - 100

%UB

20

Voltage setting for internal blocking in %


of UBase, step 2

tBlkUV2

0.000 - 60.000

0.001

0.000

Time delay of internal (low level)


blocking for step 2

HystAbs2

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 2

Table 255:
Name

UV2PTUV Group settings (advanced)


Values (Range)

Unit

tReset1

0.000 - 60.000

Step
0.001

Default
0.025

Description
Reset time delay used in IEC Definite
Time curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

CrvSat1

0 - 100

Tuning param for prog. under voltage


IDMT curve, step 1

tReset2

0.000 - 60.000

0.001

0.025

Reset time delay used in IEC Definite


Time curve step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

Table continues on next page

452
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

Step

Default

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 2

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for prog. under voltage


IDMT curve, step 2

Table 256:

Values (Range)

Unit

Description

UV2PTUV Non group settings (basic)

Name
ConnType

8.1.6

Values (Range)
PhN DFT
PhPh RMS
PhN RMS
PhPh DFT

Unit

Step

Default
PhN DFT

Description
Group selector for connection type

Technical data
Table 257:

UV2PTUV technical data

Function

Range or value

Accuracy

Operate voltage, low


and high step

(1100)% of UBase

0.5% of Ur

Absolute hysteresis

(0100)% of UBase

0.5% of Ur

Internal blocking
level, low and high
step

(1100)% of UBase

0.5% of Ur

Inverse time
characteristics for
low and high step,
see table 726

See table 726

Definite time delays

(0.000-60.000) s

0.5% 10 ms

Minimum operate
time, inverse
characteristics

(0.00060.000) s

0.5% 10 ms

Operate time, start


function

25 ms typically at 2 to 0 x Uset

Reset time, start


function

25 ms typically at 0 to 2 x Uset

Critical impulse time

10 ms typically at 1.2 to 0.8 x Uset

Impulse margin time

15 ms typically

453
Technical reference manual

Section 8
Voltage protection

8.2

1MRK 505 222-UEN B

Two step overvoltage protection OV2PTOV


Function description
Two step overvoltage protection

IEC 61850
identification

IEC 60617
identification

OV2PTOV

ANSI/IEEE C37.2
device number
59

2U>
SYMBOL-C-2U SMALLER THAN
V1 EN

8.2.1

Introduction
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines etc.
Two step overvoltage protection (OV2PTOV) function can be used to detect open
line ends, normally then combined with a directional reactive over-power function
to supervise the system voltage. When triggered, the function will cause an alarm,
switch in reactors, or switch out capacitor banks.
OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV has an extremely high reset ratio to allow settings close to system
service voltage.

8.2.2

Principle of operation
Two step overvoltage protection OV2PTOV is used to detect high power system
voltage. OV2PTOV has two steps with separate time delays. If one-, two- or threephase voltages increase above the set value, a corresponding START signal is
issued. OV2PTOV can be set to START/TRIP, based on 1 out of 3, 2 out of 3 or 3
out of 3 of the measured voltages, being above the set point. If the voltage remains
above the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the global set base voltage
UBase, which is set in kV, phase-to-phase.
OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase
fundamental value, phase-to-earth RMS value or phase-to-phase RMS value. The
choice of measuring is done by the parameter ConnType.
The setting of the analog inputs are given as primary phase-to-earth or phase-tophase voltage. OV2PTOV will operate if the voltage gets higher than the set

454
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

percentage of the set base voltage UBase. This means operation for phase-to-earth
voltage over:

U > (%) UBase( kV )


3
(Equation 122)

EQUATION1434 V1 EN

and operation for phase-to-phase voltage over:


U > (%) UBase(kV)
(Equation 123)

EQUATION1993 V1 EN

When phase-to-earth voltage measurement is selected the function


automatically introduces division of the base value by the square
root of three.

8.2.2.1

Measurement principle
All the three voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of
3 measured voltages have to be higher than the corresponding set point to issue the
corresponding START signal.
To avoid oscillations of the output START signal, a hysteresis has been included.

8.2.2.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:

inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve

The type A curve is described as:

t=

k
U -U >

U>

IEC09000051 V1 EN

(Equation 124)

The type B curve is described as:

455
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

t=

k 480

32 U - U > - 0.5

U >

2.0

- 0.035

(Equation 125)

IECEQUATION2287 V1 EN

The type C curve is described as:


t=

k 480

32 U - U > - 0.5

U >

3.0

+ 0.035

(Equation 126)

IECEQUATION2288 V1 EN

The customer programmable curve can be created as:

t=

kA
U -U >

-C
B
U>

EQUATION1439 V1 EN

+D

(Equation 127)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore, a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U< down
to U< (1.0 CrvSatn/100) the used voltage will be: U< (1.0 CrvSatn/100). If
the programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100

EQUATION1435 V1 EN

(Equation 128)

The highest phase (or phase-to-phase) voltage is always used for the inverse time
delay integration, see figure 256. The details of the different inverse time
characteristics are shown in section "Inverse characteristics"

456
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Voltage
IDMT Voltage

UL1
UL2
UL3

Time
en05000016.vsd
IEC05000016 V1 EN

Figure 256:

Voltage used for the inverse time characteristic integration

Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite
time mode (DT) and by selected voltage level dependent time curves for the
inverse time mode (IDMT). If the START condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for
the inverse time) the corresponding START output is reset, after that the defined
reset time has elapsed. Here it should be noted that after leaving the hysteresis area,
the START condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area. The hysteresis value for each step is settable
(HystAbs2) to allow an high and accurate reset of the function. It should be noted
that for Two step overvoltage protection OV2PTOV the IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time..

457
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

tReset
1
tReset1

Voltage
START

TRIP

U1>

Hysteresis

Measured
Voltage

Time
t1

START

TRIP

Time
Integrator

Linear Decrease
Frozen Timer

t1

Instantaneous
Reset

Time
IEC09000055-en-1.vsd

IEC09000055 V1 EN

Figure 257:

Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

458
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

tReset1

Voltage
START

START

tReset1
Hysteresis

TRIP

U1>
Measured Voltage

Time
t1

START

TRIP

Time Integrator

Frozen Timer

t1

Time
Instantaneous
Reset

Linear Decrease

IEC05000020-en-2.vsd

IEC05000020 V2 EN

Figure 258:

Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Definite time delay


When definite time delay is selected the function will operate as shown in figure
259. Detailed information about individual stage reset/operation behavior is shown
in figure 251 and figure 252 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured

459
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

ST1

a
b<a

U1>

tReset1

t1

TR1

AND
OFF
Delay

ON
Delay

IEC10000100-1-en.vsd
IEC10000100 V1 EN

Figure 259:

Detailed logic diagram for step 1, DT operation

Un>

START

TRIP
tResetn

tn

IEC10000037-1-en.vsd
IEC10000037 V1 EN

Figure 260:

Example for Definite Time Delay stage rest

460
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Un>

START

TRIP

tResetn

tn

IEC10000038-1-en.vsd
IEC10000038 V1 EN

Figure 261:

8.2.2.3

Example for Definite Time Delay stage operation

Blocking
It is possible to block Two step overvoltage protection OV2PTOV partially or
completely, by binary input signals where:

8.2.2.4

BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLKST1:

blocks all start and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLKST2:

blocks all start and trip outputs related to step 2

Design
The voltage measuring elements continuously measure the three phase-to-earth
voltages or the three phase-to-phase voltages. Recursive Fourier filters filter the
input voltage signals. The phase voltages are individually compared to the set
value, and the highest voltage is used for the inverse time characteristic integration.
A special logic is included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria
to fulfill the START condition. The design of Two step overvoltage protection
(OV2PTOV) is schematically described in figure 262.

461
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

UL1

Comparator
UL1 > U1>

UL2

Comparator
UL2 > U1>

UL3

Comparator
UL3 > U1>

ST1L1
Voltage Phase
Selector
OpMode1
1 out of 3
2 outof 3
3 out of 3

Phase 1

ST1L2
Phase 2
Phase 3

START

MaxVoltSelect
or

Time integrator
t1
tReset1
ResetTypeCrv1

Start
&
Trip
Output
Logic

ST1L3
ST1

OR

TR1L1

Step 1
TR1L2

TRIP

TR1L3
TR1

OR

Comparator
UL1 > U2>
Comparator
UL2 > U2>
Comparator
UL3 > U2>

Voltage Phase
Selector
OpMode2
1 out of 3
2 outof 3
3 out of 3

Time integrator
t2
tReset2
ResetTypeCrv2

ST2L2

Phase 2
Phase 3

START

MaxVoltSelect
or

ST2L1

Phase 1

Start
&
Trip
Output
Logic

ST2L3
ST2

OR

TR2L1

Step 2
TR2L2
TRIP
TR2L3
TR2

OR
OR

OR

START

TRIP

en05000013.vsd
IEC05000013-WMF V1 EN

Figure 262:

Schematic design of Two step overvoltage protection OV2PTOV

462
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

8.2.3

Function block
OV2PTOV
U3P*
BLOCK
BLKTR1
BLKST1
BLKTR2
BLKST2

TRIP
TR1
TR1L1
TR1L2
TR1L3
TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3
IEC06000277-2-en.vsd

IEC06000277 V2 EN

Figure 263:

8.2.4

OV2PTOV function block

Input and output signals


Table 258:
Name

OV2PTOV Input signals


Type

Default

Description

U3P

GROUP
SIGNAL

Group signal for three phase voltage input

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of operate signal, step 1

BLKST1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of operate signal, step 2

BLKST2

BOOLEAN

Block of step 2

Table 259:
Name

OV2PTOV Output signals


Type

Description

TRIP

BOOLEAN

Trip

TR1

BOOLEAN

Common trip signal from step1

TR1L1

BOOLEAN

Trip signal from step1 phase L1

TR1L2

BOOLEAN

Trip signal from step1 phase L2

TR1L3

BOOLEAN

Trip signal from step1 phase L3

TR2

BOOLEAN

Common trip signal from step2

TR2L1

BOOLEAN

Trip signal from step2 phase L1

TR2L2

BOOLEAN

Trip signal from step2 phase L2

TR2L3

BOOLEAN

Trip signal from step2 phase L3

START

BOOLEAN

General start signal

Table continues on next page

463
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

8.2.5
Table 260:
Name

Type

Description

ST1

BOOLEAN

Common start signal from step1

ST1L1

BOOLEAN

Start signal from step1 phase L1

ST1L2

BOOLEAN

Start signal from step1 phase L2

ST1L3

BOOLEAN

Start signal from step1 phase L3

ST2

BOOLEAN

Common start signal from step2

ST2L1

BOOLEAN

Start signal from step2 phase L1

ST2L2

BOOLEAN

Start signal from step2 phase L2

ST2L3

BOOLEAN

Start signal from step2 phase L3

Setting parameters
OV2PTOV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

OperationStep1

Off
On

On

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 1

OpMode1

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of


3, 2 of 3, 3 of 3) from step 1

U1>

1 - 200

%UB

120

Voltage setting/start val (DT & IDMT) in


% of UBase, step 1

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 1

k1

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 1

HystAbs1

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 1

OperationStep2

Off
On

On

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 2

OpMode2

1 out of 3
2 out of 3
3 out of 3

1 out of 3

Number of phases required for op (1 of


3, 2 of 3, 3 of 3) from step 2

U2>

1 - 200

%UB

150

Voltage setting/start val (DT & IDMT) in


% of UBase, step 2

Table continues on next page

464
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 2

k2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 2

HystAbs2

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 2

Table 261:

Step

Default

Description

OV2PTOV Group settings (advanced)

Name

Values (Range)

Unit

tReset1

0.000 - 60.000

Step
0.001

Default
0.025

Description
Reset time delay used in IEC Definite
Time curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

CrvSat1

0 - 100

Tuning param for prog. over voltage


IDMT curve, step 1

tReset2

0.000 - 60.000

0.001

0.025

Reset time delay used in IEC Definite


Time curve step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 2

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for prog. over voltage


IDMT curve, step 2

465
Technical reference manual

Section 8
Voltage protection

Table 262:
Name
ConnType

8.2.6

8.3

1MRK 505 222-UEN B

OV2PTOV Non group settings (basic)


Values (Range)
PhN DFT
PhPh DFT
PhN RMS
PhPh RMS

Unit

Step

Default
PhN DFT

Description
Group selector for connection type

Technical data
Table 263:

OV2PTOV technical data

Function

Range or value

Accuracy

Operate voltage, low


and high step

(1-200)% of UBase

0.5% of Ur at U < Ur
0.5% of U at U > Ur

Absolute hysteresis

(0100)% of UBase

0.5% of Ur at U < Ur
0.5% of U at U > Ur

Inverse time
characteristics for
low and high step,
see table 725

See table 725

Definite time delays

(0.000-60.000) s

0.5% 10 ms

Minimum operate
time, Inverse
characteristics

(0.000-60.000) s

0.5% 10 ms

Operate time, start


function

25 ms typically at 0 to 2 x Uset

Reset time, start


function

25 ms typically at 2 to 0 x Uset

Critical impulse time

10 ms typically at 0 to 2 x Uset

Impulse margin time

15 ms typically

Two step residual overvoltage protection


ROV2PTOV
Function description
Two step residual overvoltage
protection

IEC 61850
identification

IEC 60617
identification

ROV2PTOV

ANSI/IEEE C37.2
device number
59N

3U0
TRV V1 EN

8.3.1

Introduction
Residual voltages may occur in the power system during earth faults.

466
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Two step residual overvoltage protection ROV2PTOV function calculates the


residual voltage from the three-phase voltage input transformers or measures it
from a single voltage input transformer fed from an open delta or neutral point
voltage transformer.
ROV2PTOV has two voltage steps, each with inverse or definite time delay.
Reset delay ensures operation for intermittent earth faults.

8.3.2

Principle of operation
Two step residual overvoltage protection ROV2PTOV is used to detect high singlephase voltage, such as high residual voltage, also called 3U0. The residual voltage
can be measured directly from a voltage transformer in the neutral of a power
transformer or from a three-phase voltage transformer, where the secondary
windings are connected in an open delta. Another possibility is to measure the threephase voltages and internally in the IED calculate the corresponding residual
voltage and connect this calculated residual voltage to ROV2PTOV. ROV2PTOV
has two steps with separate time delays. If the single-phase (residual) voltage
remains above the set value for a time period corresponding to the chosen time
delay, the corresponding TRIP signal is issued.
The time delay characteristic is individually chosen for the two steps and can be
either, definite time delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.

8.3.2.1

Measurement principle
The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.
To avoid oscillations of the output START signal, a hysteresis has been included.

8.3.2.2

Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse
time delay (IDMT). For the inverse time delay four different modes are available:

inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve

The type A curve is described as:

467
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

t=

k
U -U >

U>
(Equation 129)

IEC09000051 V1 EN

The type B curve is described as:


t=

k 480

32

- 0.5

U >

U -U >

2.0

- 0.035

(Equation 130)

IECEQUATION2287 V1 EN

The type C curve is described as:


t=

k 480

32 U - U > - 0.5

U >

3.0

+ 0.035

(Equation 131)

IECEQUATION2288 V1 EN

The customer programmable curve can be created as:

t=

kA
U -U >

-C
B
U>

EQUATION1439 V1 EN

+D

(Equation 132)

When the denominator in the expression is equal to zero the time delay will be
infinity. There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn is set to compensate for this phenomenon. In the voltage interval U> up to
U> (1.0 + CrvSatn/100) the used voltage will be: U> (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:

CrvSatn
-C > 0
100

EQUATION1440 V1 EN

(Equation 133)

The details of the different inverse time characteristics are shown in section
"Inverse characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves
for the inverse time mode (IDMT).

468
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

If the START condition, with respect to the measured voltage ceases during the
delay time, and is not fulfilled again within a user defined reset time (tReset1 and
tReset2 for the definite time and tIReset1 and tIReset2 for the inverse time) the
corresponding START output is reset, after that the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to
the hysteresis area. Also notice that for the overvoltage function IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off
period. However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 257 and figure 258.
tReset
1
tReset1

Voltage
START

TRIP

U1>

Hysteresis

Measured
Voltage

Time
t1

START

TRIP

Time
Integrator

Linear Decrease
Frozen Timer

t1

Instantaneous
Reset

Time
IEC09000055-en-1.vsd

IEC09000055 V1 EN

Figure 264:

Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

469
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

tReset1

Voltage
START

START

tReset1
Hysteresis

TRIP

U1>
Measured Voltage

Time
t1

START

TRIP

Time Integrator

Frozen Timer

t1

Time
Instantaneous
Reset

Linear Decrease

IEC05000020-en-2.vsd

IEC05000020 V2 EN

Figure 265:

Voltage profile causing a reset of the START signal for step 1, and inverse time delay

Definite timer delay


When definite time delay is selected the function will operate as shown in figure
266. Detailed information about individual stage reset/operation behavior is shown
in figure 251 and figure 252 receptively. Note that by setting tResetn = 0.0s
instantaneous reset of the definite time delayed stage is ensured

470
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

ST1

a
b<a

U1>

tReset1

t1

TR1
AND

OFF
Delay

ON
Delay

IEC10000100-1-en.vsd
IEC10000100 V1 EN

Figure 266:

Detailed logic diagram for step 1, DT operation

Un<

START

TRIP
tResetn

tn

IEC10000039-1-en.vsd
IEC10000039 V1 EN

Figure 267:

Example for Definite Time Delay stage rest

471
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Un<

START

TRIP

tResetn

tn

IEC10000040-1-en.vsd
IEC10000040 V1 EN

Figure 268:

8.3.2.3

Example for Definite Time Delay stage operation

Blocking
It is possible to block Two step residual overvoltage protection ROV2PTOV
partially or completely, by binary input signals where:

8.3.2.4

BLOCK:

blocks all outputs

BLKTR1:

blocks all trip outputs of step 1

BLKST1:

blocks all start and trip outputs related to step 1

BLKTR2:

blocks all trip outputs of step 2

BLKST2:

blocks all START and trip inputs related to step 2

Design
The voltage measuring elements continuously measure the residual voltage.
Recursive Fourier filters filter the input voltage signal. The single input voltage is
compared to the set value, and is also used for the inverse time characteristic
integration. The design of Two step residual overvoltage protection (ROV2PTOV)
is schematically described in figure 269.

472
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

UN

Comparator
UN > U1>

TR1

START

Time integrator
t1
tReset1
ResetTypeCrv1

Comparator
UN > U2>

TRIP

Start
&
Trip
Output
Logic
Step 1

ST2

Phase 1

TR2

START
Time integrator
t2
tReset2
ResetTypeCrv2

ST1

Phase 1

TRIP

Start
&
Trip
Output
Logic

OR

Step 2
OR

START

TRIP

en05000748.vsd
IEC05000748 V1 EN

Figure 269:

8.3.3

Schematic design of Two step residual overvoltage protection


ROV2PTOV

Function block
ROV2PTOV
U3P*
BLOCK
BLKTR1
BLKST1
BLKTR2
BLKST2

TRIP
TR1
TR2
START
ST1
ST2
IEC06000278-2-en.vsd

IEC06000278 V2 EN

Figure 270:

ROV2PTOV function block

473
Technical reference manual

Section 8
Voltage protection
8.3.4

1MRK 505 222-UEN B

Input and output signals


Table 264:

ROV2PTOV Input signals

Name

Type
GROUP
SIGNAL

Three phase voltages

BLOCK

BOOLEAN

Block of function

BLKTR1

BOOLEAN

Block of operate signal, step 1

BLKST1

BOOLEAN

Block of step 1

BLKTR2

BOOLEAN

Block of operate signal, step 2

BLKST2

BOOLEAN

Block of step 2

ROV2PTOV Output signals

Name

Table 266:
Name

Description

U3P

Table 265:

8.3.5

Default

Type

Description

TRIP

BOOLEAN

Trip

TR1

BOOLEAN

Common trip signal from step1

TR2

BOOLEAN

Common trip signal from step2

START

BOOLEAN

General start signal

ST1

BOOLEAN

Common start signal from step1

ST2

BOOLEAN

Common start signal from step2

Setting parameters
ROV2PTOV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

OperationStep1

Off
On

On

Enable execution of step 1

Characterist1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 1

U1>

1 - 200

%UB

30

Voltage setting/start val (DT & IDMT),


step 1 in % of UBase

t1

0.00 - 6000.00

0.01

5.00

Definitive time delay of step 1

t1Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 1

k1

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 1

HystAbs1

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 1

Table continues on next page

474
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

OperationStep2

Off
On

On

Enable execution of step 2

Characterist2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for


step 2

U2>

1 - 100

%UB

45

Voltage setting/start val (DT & IDMT),


step 2 in % of UBase

t2

0.000 - 60.000

0.001

5.000

Definitive time delay of step 2

t2Min

0.000 - 60.000

0.001

5.000

Minimum operate time for inverse curves


for step 2

k2

0.05 - 1.10

0.01

0.05

Time multiplier for the inverse time delay


for step 2

HystAbs2

0.0 - 100.0

%UB

0.1

0.5

Absolute hysteresis in % of UBase, step 2

Table 267:

ROV2PTOV Group settings (advanced)

Name

Values (Range)

Unit

tReset1

0.000 - 60.000

Step
0.001

Default
0.025

Description
Reset time delay used in IEC Definite
Time curve step 1

ResetTypeCrv1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 1

tIReset1

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 1

ACrv1

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 1

BCrv1

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 1

CCrv1

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 1

DCrv1

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 1

PCrv1

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 1

CrvSat1

0 - 100

Tuning param for prog. over voltage


IDMT curve, step 1

tReset2

0.000 - 60.000

0.001

0.025

Time delay in DT reset (s), step 2

ResetTypeCrv2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of used IDMT reset curve type


for step 2

tIReset2

0.000 - 60.000

0.001

0.025

Time delay in IDMT reset (s), step 2

ACrv2

0.005 - 200.000

0.001

1.000

Parameter A for customer programmable


curve for step 2

BCrv2

0.50 - 100.00

0.01

1.00

Parameter B for customer programmable


curve for step 2

CCrv2

0.0 - 1.0

0.1

0.0

Parameter C for customer


programmable curve for step 2

Table continues on next page

475
Technical reference manual

Section 8
Voltage protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

DCrv2

0.000 - 60.000

0.001

0.000

Parameter D for customer


programmable curve for step 2

PCrv2

0.000 - 3.000

0.001

1.000

Parameter P for customer programmable


curve for step 2

CrvSat2

0 - 100

Tuning param for prog. over voltage


IDMT curve, step 2

8.3.6

8.4

Technical data
Table 268:

ROV2PTOV technical data

Function

Range or value

Accuracy

Operate voltage, low


and high step

(1-200)% of UBase

0.5% of Ur at U < Ur
1.0% of U at U > Ur

Absolute hysteresis

(0100)% of UBase

0.5% of Ur at U < Ur
1.0% of U at U > Ur

Inverse time
characteristics for
low and high step,
see table 727

See table 727

Definite time setting

(0.00060.000) s

0.5% 10 ms

Minimum operate
time

(0.000-60.000) s

0.5% 10 ms

Operate time, start


function

25 ms typically at 0 to 2 x Uset

Reset time, start


function

25 ms typically at 2 to 0 x Uset

Critical impulse time

10 ms typically at 0 to 2 x Uset

Impulse margin time

15 ms typically

Overexcitation protection OEXPVPH


Function description
Overexcitation protection

IEC 61850
identification

IEC 60617
identification

OEXPVPH

ANSI/IEEE C37.2
device number
24

U/f >
SYMBOL-Q V1 EN

8.4.1

Introduction
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into nonlaminated components not designed to carry flux and cause eddy currents to flow.

476
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

The eddy currents can cause excessive heating and severe damage to insulation and
adjacent parts in a relatively short time. The function has settable inverse operating
curves and independent alarm stages.

8.4.2

Principle of operation
The importance of Overexcitation protection (OEXPVPH) function is growing as
the power transformers as well as other power system elements today operate most
of the time near their designated limits.
Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
emergency that includes overexcitation does occur, transformers may be damaged
unless corrective action is promptly taken. Transformer manufacturers recommend
an overexcitation protection as a part of the transformer protection system.
Overexcitation results from excessive applied voltage, possibly in combination
with below-normal frequency. Such condition may occur when a transformer unit
is on load, but are more likely to arise when it is on open circuit, or at a loss of load
occurrence. Transformers directly connected to generators are in particular danger
to experience overexcitation condition. It follows from the fundamental
transformer equation, see equation 134, that peak flux density Bmax is directly
proportional to induced voltage E, and inversely proportional to frequency f, and
turns n.
E = 4.44 f n Bmax A
(Equation 134)

EQUATION898 V2 EN

The relative excitation M is therefore according to equation 135.


M ( p.u.) =

E f

( Ur ) ( fr )

IECEQUATION2296 V1 EN

(Equation 135)

Disproportional variations in quantities E and f may give rise to core overfluxing.


If the core flux density Bmax increases to a point above saturation level (typically
1.9 Tesla), the flux will no longer be contained within the core, but will extend into
other (non-laminated) parts of the power transformer and give rise to eddy current
circulations.
Overexcitation will result in:

overheating of the non-laminated metal parts


a large increase in magnetizing currents
an increase in core and winding temperature
an increase in transformer vibration and noise

477
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Protection against overexcitation is based on calculation of the relative volt per


hertz (V/Hz) ratio. Protection initiates a reduction of excitation, and if this fails, or
is not possible, the TRIP signal will disconnect the transformer from the source
after a delay ranging from seconds to minutes, typically 5-10 seconds.
Overexcitation protection may be of particular concern on directly connected
generator unit transformers. Directly connected generator-transformers are
subjected to a wide range of frequencies during the acceleration and deceleration of
the turbine. In such cases, OEXPVPH (24) may trip the field breaker during a startup of a machine, by means of the overexcitation ALARM signal. If this is not
possible, the power transformer can be disconnected from the source, after a delay,
by the TRIP signal.
The IEC 60076 - 1 standard requires that transformers operate continuously at 10%
above rated voltage at no load, and rated frequency. At no load, the ratio of the
actual generator terminal voltage to the actual frequency should not exceed 1.1
times the ratio of transformer rated voltage to the rated frequency on a sustained
basis, see equation 136.
E
--------- 1.1 Ur
fr
f
(Equation 136)

EQUATION900 V1 EN

or equivalently, with 1.1 Ur = V/Hz> according to equation 137.


E
f

V Hz >
fr
(Equation 137)

IECEQUATION2297 V2 EN

where:

V/Hz>

is the maximum continuously allowed voltage at no load, and rated frequency.

V/Hz> is a setting parameter. The setting range is 100% to 180%. If the user does
not know exactly what to set, then the default value for V/Hz> = 110 % for the
standard IEC 60076-1 shall be used.
In OEXPVPH, the relative excitation M is expressed according to equation 138.
M ( p.u. ) =
IECEQUATION2299 V1 EN

E f
Ur fr
(Equation 138)

It is clear from the above formula that, for an unloaded power transformer, M = 1
for any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M V/Hz>, V/Hz> expressed in %
of Ur/fr.
478
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

The overexcitation protection algorithm is fed with an input voltage U which is in


general not the induced voltage E from the fundamental transformer equation. For
no load condition, these two voltages are the same, but for a loaded power
transformer the internally induced voltage E may be lower or higher than the
voltage U which is measured and fed to OEXPVPH , depending on the direction of
the power flow through the power transformer, the power transformer side where
OEXPVPH is applied, and the power transformer leakage reactance of the winding.
It is important to specify in the application configuration on which side of the
power transformer OEXPVPH is placed.
As an example, at a transformer with a 15% short circuit impedance Xsc, the full
load, 0.8 power factor, 105% voltage on the load side, the actual flux level in the
transformer core, will not be significantly different from that at the 110% voltage,
no load, rated frequency, provided that the short circuit impedance X can be
equally divided between the primary and the secondary winding: Xleak = Xleak1 =
Xleak2 = Xsc / 2 = 0.075 pu.
OEXPVPH calculates the internal induced voltage E if Xleak (meaning the leakage
reactance of the winding where OEXPVPH is connected) is known to the user. The
assumption taken for two-winding power transformers that Xleak = Xsc / 2 is
unfortunately most often not true. For a two-winding power transformer the
leakage reactances of the two windings depend on how the windings are located on
the core with respect to each other. In the case of three-winding power transformers
the situation is still more complex. If a user has the knowledge on the leakage
reactance, then it should applied. If a user has no idea about it, Xleak can be set to
Xc/2. OEXPVPH protection will then take the given measured voltage U, as the
induced voltage E.
It is assumed that overexcitation is a symmetrical phenomenon, caused by events
such as loss-of-load, etc. It will be observed that a high phase-to-earth voltage does
not mean overexcitation. For example, in an unearthed power system, a single phaseto-earth fault means high voltages of the healthy two phases-to-earth, but no
overexcitation on any winding. The phase-to-phase voltages will remain essentially
unchanged. The important voltage is the voltage between the two ends of each
winding.

8.4.2.1

Measured voltage
If one phase-to-phase voltage is available from the side where overexcitation
protection is applied, then Overexcitation protection OEXPVPH shall be set to
measure this voltage, MeasuredU. The particular voltage which is used determines
the two currents that must be used. This must be chosen with the setting MeasuredI.
It is extremely important that MeasuredU and MeasuredI are set to
same value.
If, for example, voltage UL1L2 is fed to OEXPVPH, then currents IL1, and IL2
must be applied. From these two input currents, current IL1L2 = IL1 - IL2 is
479

Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

calculated internally by the OEXPVPH algorithm. The phase-to-phase voltage


must be higher than 70% of the rated value, otherwise the protection algorithm
exits without calculating the excitation. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.
If three phase-to-earth voltages are available from the side where overexcitation is
connected, then OEXPVPH shall be set to measure positive sequence voltage and
current. In this case the positive sequence voltage and the positive sequence current
are used by OEXPVPH. A check is made if the positive sequence voltage is higher
than 70% of rated phase-to-earth voltage, when below this value, OEXPVPH exits
immediately, and no excitation is calculated. ERROR output is set to 1, and the
displayed value of relative excitation V/Hz shows 0.000.
The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 Hz
and 60 Hz respectively.

OEXPVPH can be connected to any power transformer side, independent from


the power flow.
The side with a possible load tap changer must not be used.

8.4.2.2

Operate time of the overexcitation protection


The operate time of OEXPVPH is a function of the relative overexcitation.
Basically there are two different delay laws available to choose between:

the so called IEEE law, and


a tailor-made law.

The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers overexcitation capability characteristics. They
can match the transformer core capability well.
The square law is according to equation 139.
top =

0.18 k

V Hz> - 1

0.18 k
overexcitation

IECEQUATION2298 V2 EN

(Equation 139)

where:
M

the relative excitation

V/Hz>

is maximum continuously allowed voltage at no load, and rated frequency, in pu and

is time multiplier for inverse time functions, see figure 272.


Parameter k (time multiplier setting) selects one delay curve from the family of curves.

480
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

The relative excitation M is calculated using equation270

Umeasured

fmeasured
=

UBase

frated

Umeasured

frated

UBase fmeasured

IECEQUATION2404 V1 EN

An analog overexcitation relay would have to evaluate the following integral


expression, which means to look for the instant of time t = top according to
equation 140.
top

(M (t) - V

Hz > ) dt 0.18 k
2

(Equation 140)

IECEQUATION2300 V1 EN

A digital, numerical relay will instead look for the lowest j (that is, j = n) where it
becomes true that:
n

Dt

( M(j)

V/Hz> ) 0.18 k

j=k

(Equation 141)

EQUATION906 V1 EN

where:
Dt

is the time interval between two successive executions of OEXPVPH and

M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is
given as Ur/fr.

As long as M > V/Hz> (that is, overexcitation condition), the above sum can only
be larger with time, and if the overexcitation persists, the protected transformer will
be tripped at j = n.
Inverse delays as per figure 272, can be modified (limited) by two special definite
delay settings, namely tMax and tMin, see figure 271.

481
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

delay in s
tMax

under excitation

inverse delay law

overexcitation
tMin
0
M=V/Hz>
V/Hz>

Mmax - V/Hz> Overexcitation M-V/Hz>


Mmax
Emax

Excitation M
E (only if f = fr = const)
99001067.vsd

IEC99001067 V1 EN

Figure 271:

Restrictions imposed on inverse delays by tMax and tMin

A definite maximum time, tMax, can be used to limit the operate time at low
degrees of overexcitation. Inverse delays longer than tMax will not be allowed. In
case the inverse delay is longer than tMax, OEXPVPH trips after tMax seconds.
A definite minimum time, tMin, can be used to limit the operate time at high
degrees of overexcitation. In case the inverse delay is shorter than tMin,
OEXPVPH function trips after tMin seconds. The inverse delay law is not valid for
values exceeding Mmax. The delay will be tMin, irrespective of the overexcitation
level, when values exceed Mmax (that is, M>V/Hz>).

482
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

IEEE OVEREXCITATION CURVES

Time (s)

1000

100
k = 60

k = 20

k = 10
k=9
k=8
k=7
k=6
k=5

10

k=4
k=3
k=2

k=1
1

10

20

OVEREXCITATION IN %

30

40

(M-Emaxcont)*100)
en01000373.vsd

IEC01000373 V1 EN

Figure 272:

Delays inversely proportional to the square of the overexcitation

The critical value of excitation M is determined indirectly via OEXPVPH setting V/


Hz>>. V/Hz>> can be thought of as a no-load-rated-frequency voltage, where the
inverse law should be replaced by a short definite delay, tMin. If, for example, V/
Hz>> = 140 %, then M is according to equation 142.
M=

(V

Hz>> ) / f
Ur/fr

IECEQUATION2286 V1 EN

= 1.40
(Equation 142)

The Tailor-Made law allows a user to design an arbitrary delay characteristic. In


this case the interval between M = V/Hz>, and M = Mmax is automatically divided
into five equal subintervals, with six delays. (settings t1, t2, t3, t4, t5 and t6) as
shown in figure 273. These times should be set so that t1 => t2 => t3 => t4 => t5
=> t6.

483
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

delay in s

tMax

tMin

underexcitation

Overexcitation M-Emaxcont
0

Mmax - Emaxcont Excitation M


Mmax

Emaxcont

99001068.vsd
IEC99001068 V1 EN

Figure 273:

An example of a Tailor-Made delay characteristic

Delays between two consecutive points, for example t3 and t4, are obtained by
linear interpolation.
Should it happen that tMax be lower than, for example, delays t1, and t2, the actual
delay would be tMax. Above Mmax, the delay can only be tMin.

8.4.2.3

Cooling
Overexcitation protection OEXPVPH is basically a thermal protection; therefore a
cooling process has been introduced. Exponential cooling process is applied.
Parameter Setting tool is an OEXPVPH setting, with a default time constant
tCooling of 20 minutes. This means that if the voltage and frequency return to their
previous normal values (no more overexcitation), the normal temperature is
assumed to be reached not before approximately 5 times tCooling minutes. If an
overexcitation condition would return before that, the time to trip will be shorter
than it would be otherwise.

8.4.2.4

Overexcitation protection function measurands


A monitored data value, TMTOTRIP, is available on the local HMI and in
PCM600. This value is an estimation of the remaining time to trip (in seconds), if
the overexcitation remained on the level it had when the estimation was done. This
information can be useful with small or moderate overexcitations.
If the overexcitation is so low that the valid delay is tMax, then the estimation of
the remaining time to trip is done against tMax.
The relative excitation M, shown on the local HMI and in PCM600 has a
monitored data value VPERHZ, is calculated from the expression:
M ( p.u. ) =
IECEQUATION2299 V1 EN

E f
Ur fr
(Equation 143)

484
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

If VPERHZ value is less than setting V/Hz> (in %), the power transformer is
underexcited. If VPERHZ is equal to V/Hz> (in %), the excitation is exactly equal
to the power transformer continuous capability. If VPERHZ is higher than V/Hz>,
the protected power transformer is overexcited. For example, if VPERHZ = 1.100,
while V/Hz> = 110 %, then the power transformer is exactly on its maximum
continuous excitation limit.
Monitored data value THERMSTA shows the thermal status of the protected
power transformer iron core. THERMSTA gives the thermal status in % of the trip
value which corresponds to 100%. THERMSTA should reach 100% at the same
time, as TMTOTRIP reaches 0 seconds. If the protected power transformer is then
for some reason not switched off, THERMSTA shall go over 100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or tMin,
then the Thermal status will generally not reach 100% at the same time, when
tTRIP reaches 0 seconds. For example, if, at low degrees of overexcitation, the
very long delay is limited by tMax, then the OEXPVPH TRIP output signal will be
set to 1 before the Thermal status reaches 100%.

8.4.2.5

Overexcitation alarm
A separate step, AlarmLevel, is provided for alarming purpose. It is normally set
2% lower than (V/Hz>) and has a definite time delay, tAlarm. This will give the
operator an early abnormal voltages warning.

8.4.2.6

Logic diagram
BLOCK
AlarmLevel

t
V/Hz>

I3P

Calculation
of internal
induced
voltage Ei

Ei

M=
(Ei / f)
(Ur / fr)

ALARM

t>tMin

&

TRIP

tMin
k

&

tAlarm

M>V/Hz>

U3P

t>tAlarm

IEEE law

M
Tailor-made law
M>V/Hz>>

tMax

Xleak
V/Hz>>

M = relative V/Hz as service value


IEC05000162-2-en.vsd
IEC05000162 V2 EN

Figure 274:

A simplified logic diagram of the Overexcitation protection


OEXPVPH

485
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and
frequency are separately checked against their respective limit values.

8.4.3

Function block
OEXPVPH
I3P*
U3P*
BLOCK
RESET

TRIP
START
ALARM

IEC05000329-2-en.vsd
IEC05000329 V3 EN

Figure 275:

8.4.4

OEXPVPH function block

Input and output signals


Table 269:

OEXPVPH Input signals

Name

Type

Current connection

U3P

GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block of function

RESET

BOOLEAN

Reset operation

OEXPVPH Output signals

Name

Table 271:
Name

Description

GROUP
SIGNAL

Table 270:

8.4.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip from overexcitation function

START

BOOLEAN

Overexcitation above set operate level


(instantaneous)

ALARM

BOOLEAN

Overexcitation above set alarm level (delayed)

Setting parameters
OEXPVPH Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base current (rated phase current) in A

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage (main voltage) in kV

V/Hz>

100.0 - 180.0

%UB/f

0.1

110.0

Operate level of V/Hz at no load and


rated freq in % of (Ubase/frated)

Table continues on next page

486
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

Step

Default

V/Hz>>

100.0 - 200.0

%UB/f

0.1

140.0

High level of V/Hz above which tMin is


used, in % of (Ubase/frated)

XLeak

0.000 - 200.000

ohm

0.001

0.000

Winding leakage reactance in primary


ohms

TrPulse

0.000 - 60.000

0.001

0.100

Length of the pulse for trip signal (in sec)

tMin

0.000 - 60.000

0.001

7.000

Minimum trip delay for V/Hz inverse


curve, in sec

tMax

0.00 - 9000.00

0.01

1800.00

Maximum trip delay for V/Hz inverse


curve, in sec

tCooling

0.10 - 9000.00

0.01

1200.00

Transformer magnetic core cooling time


constant, in sec

CurveType

IEEE
Tailor made

IEEE

Inverse time curve selection, IEEE/Tailor


made

kForIEEE

1 - 60

Time multiplier for IEEE inverse type


curve

AlarmLevel

50.0 - 120.0

0.1

100.0

Alarm operate level as % of operate level

tAlarm

0.00 - 9000.00

0.01

5.00

Alarm time delay, in sec

Default

Table 272:

Values (Range)

Unit

Description

OEXPVPH Group settings (advanced)

Name

Values (Range)

Unit

Step

t1Tailor

0.00 - 9000.00

0.01

7200.00

Time delay t1 (longest) for tailor made


curve, in sec

t2Tailor

0.00 - 9000.00

0.01

3600.00

Time delay t2 for tailor made curve, in sec

t3Tailor

0.00 - 9000.00

0.01

1800.00

Time delay t3 for tailor made curve, in sec

t4Tailor

0.00 - 9000.00

0.01

900.00

Time delay t4 for tailor made curve, in sec

t5Tailor

0.00 - 9000.00

0.01

450.00

Time delay t5 for tailor made curve, in sec

t6Tailor

0.00 - 9000.00

0.01

225.00

Time delay t6 (shortest) for tailor made


curve, in sec

Step

Default

Table 273:

Description

OEXPVPH Non group settings (basic)

Name

Values (Range)

Unit

Description

MeasuredU

PosSeq
L1L2
L2L3
L3L1

L1L2

Selection of measured voltage

MeasuredI

L1L2
L2L3
L3L1
PosSeq

L1L2

Selection of measured current

487
Technical reference manual

Section 8
Voltage protection
8.4.6

1MRK 505 222-UEN B

Technical data
Table 274:

OEXPVPH technical data

Function

Range or value

Accuracy

Operate value, start

(100180)% of (UBase/frated)

0.5% of U

Operate value, alarm

(50120)% of start level

0.5% of Ur at U Ur
0.5% of U at U > Ur

Operate value, high level

(100200)% of (UBase/frated)

0.5% of U

Curve type

IEEE or customer defined

Class 5 + 40 ms

IEEE : t =

(0.18 k )
( M - 1) 2

EQUATION1319 V1 EN

(Equation 144)

where M = (E/f)/(Ur/fr)

8.5

Minimum time delay for inverse


function

(0.00060.000) s

0.5% 10 ms

Maximum time delay for inverse


function

(0.009000.00) s

0.5% 10 ms

Alarm time delay

(0.00060.000) s

0.5% 10 ms

Voltage differential protection VDCPTOV


Function description
Voltage differential protection

8.5.1

IEC 61850
identification
VDCPTOV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
60

Introduction
A voltage differential monitoring function is available. It compares the voltages
from two three phase sets of voltage transformers and has one sensitive alarm step
and one trip step.

8.5.2

Principle of operation
The Voltage differential protection function VDCPTOV (60) is based on
comparison of the amplitudes of the two voltages connected in each phase.
Possible differences between the ratios of the two Voltage/Capacitive voltage
transformers can be compensated for with a ratio correction factors RFLx. The
voltage difference is evaluated and if it exceeds the alarm level UDAlarm or trip
level UDATrip signals for alarm (ALARM output) or trip (TRIP output) is given
after definite time delay tAlarm respectively tTrip. The two three phase voltage
supplies are also supervised with undervoltage settings U1Low and U2Low. The
outputs for loss of voltage U1LOW resp U2LOW will be activated. The U1 voltage

488
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

is supervised for loss of individual phases whereas the U2 voltage is supervised for
loss of all three phases.
Loss of all U1or all U2 voltages will block the differential measurement. This
blocking can be switched off with setting BlkDiffAtULow = No.
VDCPTOV function can be blocked from an external condition with the binary
BLOCK input. It can for example, be activated from Fuse failure supervision
function SDDRFUF.
To allow easy commissioning the measured differential voltage is available as
service value. This allows simple setting of the ratio correction factor to achieve
full balance in normal service.
The principle logic diagram is shown in figure 276.
UDTripL1>

AND

UDTripL2>

AND

UDTripL3>

O
R

tReset tTrip
t
t

AND

AND
AND

UDAlarmL1>

TRIP

START

AND

UDAlarmL2>

AND

UDAlarmL3>

O
R

tAlarm

AND

ALARM

AND

U1LOW

AND

U1<L1
AND

U1<L2

tAlarm
t
AND

U1<L3
OR

BlkDiffAtULow
U2<L1
AND

U2<L2

t1
t

AND

U2LOW

U2<L3
BLOCK

en06000382-2.vsd
IEC06000382 V3 EN

Figure 276:

Principle logic for Voltage differential function VDCPTOV

489
Technical reference manual

Section 8
Voltage protection
8.5.3

1MRK 505 222-UEN B

Function block
VDCPTOV
U3P1*
U3P2*
BLOCK

TRIP
START
ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF
IEC06000528-2-en.vsd

IEC06000528 V2 EN

Figure 277:

8.5.4

VDCPTOV function block

Input and output signals


Table 275:

VDCPTOV Input signals

Name

Type
GROUP
SIGNAL

Bus voltage

U3P2

GROUP
SIGNAL

Capacitor voltage

BLOCK

BOOLEAN

Block of function

VDCPTOV Output signals

Name

Table 277:
Name

Description

U3P1

Table 276:

8.5.5

Default

Type

Description

TRIP

BOOLEAN

Voltage differential protection operated

START

BOOLEAN

Start of voltage differential protection

ALARM

BOOLEAN

Voltage differential protection alarm

U1LOW

BOOLEAN

Loss of U1 voltage

U2LOW

BOOLEAN

Loss of U2 voltage

UL1DIFF

REAL

Differential Voltage phase L1

UL2DIFF

REAL

Differential Voltage phase L2

UL3DIFF

REAL

Differential Voltage phase L3

Setting parameters
VDCPTOV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

UBase

0.50 - 2000.00

kV

0.01

400.00

Base Voltage

BlkDiffAtULow

No
Yes

Yes

Block operation at low voltage

Table continues on next page

490
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

UDTrip

0.0 - 100.0

%UB

0.1

5.0

Operate level, in % of UBase

tTrip

0.000 - 60.000

0.001

1.000

Time delay for voltage differential


operate, in milliseconds

tReset

0.000 - 60.000

0.001

0.000

Time delay for voltage differential reset,


in seconds

U1Low

0.0 - 100.0

%UB

0.1

70.0

Input 1 undervoltage level, in % of UBase

U2Low

0.0 - 100.0

%UB

0.1

70.0

Input 2 undervoltage level, in % of UBase

tBlock

0.000 - 60.000

0.001

0.000

Reset time for undervoltage block

UDAlarm

0.0 - 100.0

%UB

0.1

2.0

Alarm level, in % of UBase

tAlarm

0.000 - 60.000

0.001

2.000

Time delay for voltage differential alarm,


in seconds

Table 278:

VDCPTOV Group settings (advanced)

Name

Values (Range)

RFL1

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L1


U2L1*RFL1=U1L1

RFL2

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L2


U2L2*RFL2=U1L2

RFL3

0.000 - 3.000

0.001

1.000

Ratio compensation factor phase L3


U2L3*RFL3=U1L3

8.5.6

Unit

Step

VDCPTOV technical data

Function

Range or value

Accuracy

Voltage difference for alarm and


trip

(0.0100.0) % of UBase

0.5 % of Ur

Under voltage level

(0.0100.0) % of UBase

0.5% of Ur

Timers

(0.00060.000)s

0.5% 10 ms

Loss of voltage check LOVPTUV


Function description
Loss of voltage check

8.6.1

Description

Technical data
Table 279:

8.6

Default

IEC 61850
identification
LOVPTUV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
27

Introduction
Loss of voltage check (LOVPTUV) is suitable for use in networks with an
automatic system restoration function. LOVPTUV issues a three-pole trip

491
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

command to the circuit breaker, if all three phase voltages fall below the set value
for a time longer than the set time and the circuit breaker remains closed.

8.6.2

Principle of operation
The operation of Loss of voltage check LOVPTUV is based on line voltage
measurement. LOVPTUV is provided with a logic, which automatically recognises
if the line was restored for at least tRestore before starting the tTrip timer. All three
phases are required to be low before the output TRIP is activated. The START
output signal indicates start.
Additionally, LOVPTUV is automatically blocked if only one or two phase
voltages have been detected low for more than tBlock.
LOVPTUV operates again only if the line has been restored to full voltage for at
least tRestore. Operation of the function is also inhibited by fuse failure and open
circuit breaker information signals, by their connection to dedicated inputs of the
function block.
Due to undervoltage conditions being continuous the trip pulse is limited to a
length set by setting tPulse.
The operation of LOVPTUV is supervised by the fuse-failure function (BLKU
input) and the information about the open position (CBOPEN) of the associated
circuit breaker.
The BLOCK input can be connected to a binary input of the IED in order to receive
a block command from external devices or can be software connected to other
internal functions of the IED itself in order to receive a block command from
internal functions. LOVPTUV is also blocked when the IED is in TEST status and
the function has been blocked from the HMI test menu. (Blocked=Yes).

492
Technical reference manual

Section 8
Voltage protection

1MRK 505 222-UEN B

TEST
TEST-ACTIVE

&
Blocked = Yes

BLOCK

START

>1
Function Enable

tTrip

&

STUL1N

tPulse

TRIP

&

STUL2N

only 1 or 2 phases are low for


at least 10 s (not three)

Latched
Enable

STUL3N

&

tBlock

>1

CBOPEN

Reset Enable

>1

&

VTSU

>1

tRestore

Set Enable

>1

Line restored for


at least 3 s

IEC07000089_2_en.vsd
IEC07000089 V2 EN

Figure 278:

Simplified diagram of Loss of voltage check LOVPTUV

8.6.3

Function block
LOVPTUV
U3P*
BLOCK
CBOPEN
VTSU

TRIP
START

IEC07000039-2-en.vsd
IEC07000039 V2 EN

Figure 279:

LOVPTUV function block

493
Technical reference manual

Section 8
Voltage protection
8.6.4

1MRK 505 222-UEN B

Input and output signals


Table 280:

LOVPTUV Input signals

Name

Type
GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block the all outputs

CBOPEN

BOOLEAN

Circuit breaker open

VTSU

BOOLEAN

Block from voltage circuit supervision

LOVPTUV Output signals

Name

Table 282:
Name

Description

U3P

Table 281:

8.6.5

Default

Type

Description

TRIP

BOOLEAN

Trip signal

START

BOOLEAN

Start signal

Setting parameters
LOVPTUV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

UBase

0.1 - 9999.9

kV

0.1

400.0

Base voltage

UPE

1 - 100

%UB

70

Operate voltagein% of base voltage


Ubase

tTrip

0.000 - 60.000

0.001

7.000

Operate time delay

Table 283:
Name

LOVPTUV Group settings (advanced)


Values (Range)

Unit

tPulse

0.050 - 60.000

0.001

0.150

Duration of TRIP pulse

tBlock

0.000 - 60.000

0.001

5.000

Time delay to block when all 3ph


voltages are not low

tRestore

0.000 - 60.000

0.001

3.000

Time delay for enable the function after


restoration

8.6.6

Step

Default

Description

Technical data
Table 284:
Function

LOVPTUV technical data


Range or value

Accuracy

Operate voltage

(0100)% of UBase

0.5% of Ur

Pulse timer

(0.05060.000) s

0.5% 10 ms

Timers

(0.00060.000) s

0.5% 10 ms

494
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

Section 9

Frequency protection

About this chapter


This chapter describes the frequency protection functions. The way the functions
work, their setting parameters, function blocks, input and output signals and
technical data are included for each function.

9.1

Underfrequency protection SAPTUF


Function description
Underfrequency protection

IEC 61850
identification

IEC 60617
identification

SAPTUF

ANSI/IEEE C37.2
device number
81

f<
SYMBOL-P V1 EN

9.1.1

Introduction
Underfrequency occurs as a result of lack of generation in the network.
Underfrequency protection SAPTUF is used for load shedding systems, remedial
action schemes, gas turbine startup and so on.
SAPTUF is provided with an undervoltage blocking.
The operation is based on positive sequence voltage measurement and requires two
phase-phase or three phase-neutral voltages to be connected. For information about
how to connect analog inputs, refer to Application manual/IED application/
Analog inputs/Setting guidelines

9.1.2

Principle of operation
Underfrequency protection SAPTUF is used to detect low power system frequency.
SAPTUF can either have a definite time delay or a voltage magnitude dependent
time delay. If the voltage magnitude dependent time delay is applied, the time
delay will be longer if the voltage is higher, and the delay will be shorter if the
voltage is lower. If the frequency remains below the set value for a time period
corresponding to the chosen time delay, the corresponding trip signal is issued. To
avoid an unwanted trip due to uncertain frequency measurement at low voltage

495
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

magnitude, a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage IntBlockLevel the function is blocked
and no START or TRIP signal is issued.

9.1.2.1

Measurement principle
The fundamental frequency of the measured input voltage is measured
continuously, and compared with the set value, StartFrequency. The frequency
function is dependent on the voltage magnitude. If the voltage magnitude decreases
the setting IntBlockLevel, SAPTUF gets blocked, and the output BLKDMAGN is
issued. All voltage settings are made in percent of the setting UBase, which should
be set as a phase-phase voltage in kV.
To avoid oscillations of the output START signal, a hysteresis has been included.

9.1.2.2

Time delay
The time delay for underfrequency protection SAPTUF can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time
delay depends on the voltage level; a high voltage level gives a longer time delay
and a low voltage level causes a short time delay. For the definite time delay, the
setting TimeDlyOperate sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings
UNom, UMin, Exponent, tMax and tMin set the time delay according to figure 280
and equation 145. The setting TimerOperation is used to decide what type of time
delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least
the user set time delay TimeDlyOperate. If the START condition, with respect to
the measured frequency ceases during this user set delay time, and is not fulfilled
again within a user defined reset time, TimeDlyReset, the START output is reset,
after that the defined reset time has elapsed. Here it should be noted that after
leaving the hysteresis area, the START condition must be fulfilled again and it is
not sufficient for the signal to only return back to the hysteresis area.
On the output of SAPTUF a 100ms pulse is issued, after a time delay
corresponding to the setting of TimeDlyRestore, when the measured frequency
returns to the level corresponding to the setting RestoreFreq.

9.1.2.3

Voltage dependent time delay


Since the fundamental frequency in a power system is the same all over the system,
except some deviations during power oscillations, another criterion is needed to
decide, where to take actions, based on low frequency. In many applications the
voltage level is very suitable, and in most cases is load shedding preferable in areas
with low voltage. Therefore, a voltage dependent time delay has been introduced,
to make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to

496
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

equation 145. At non-constant voltage, the actual time delay is integrated in a


similar way as for the inverse time characteristic for the undervoltage and
overvoltage functions.
U - UMin
t=
UNom - UMin

Exponent

( tMax - tMin ) + tMin

(Equation 145)

EQUATION1182 V1 EN

where:
t

is the voltage dependent time delay (at constant voltage),

is the measured voltage

Exponent

is a setting,

UMin, UNom are voltage settings corresponding to


tMax, tMin

are time settings.

The inverse time characteristics are shown in figure 280, for:


UMin

= 90%

UNom

= 100%

tMax

= 1.0 s

tMin

= 0.0 s

Exponent

= 0, 1, 2, 3 and 4

TimeDlyOperate [s]

0
Exponenent

1
2

3
0.5

90

95

100

U [% of UBase]
en05000075.vsd
IEC05000075 V1 EN

Figure 280:

Voltage dependent inverse time characteristics for underfrequency


protection SAPTUF. The time delay to operate is plotted as a
function of the measured voltage, for the Exponent = 0, 1, 2, 3, 4
respectively.

497
Technical reference manual

Section 9
Frequency protection
9.1.2.4

1MRK 505 222-UEN B

Blocking
It is possible to block underfrequency protection SAPTUF partially or completely,
by binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

BLKREST:

blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.1.2.5

Design
The frequency measuring element continuously measures the frequency of the
positive sequence voltage and compares it to the setting StartFrequency. The
frequency signal is filtered to avoid transients due to switchings and faults. The
time integrator can operate either due to a definite delay time or to the special
voltage dependent delay time. When the frequency has returned back to the setting
of RestoreFreq, the RESTORE output is issued after the time delay
TimeDlyRestore. The design of underfrequency protection SAPTUF is
schematically described in figure 281.

Block
OR

BLKDMAGN

BLOCK

Comparator
U < IntBlockLevel

Voltage

Frequency

Time integrator

Comparator
f < StartFrequency

TimerOperation Mode
Selector

START

TimeDlyOperate

TRIP

Start
&
Trip
Output
Logic

START

TimeDlyReset

TRIP

100 ms
Comparator
f > RestoreFreq

TimeDlyRestore

RESTORE

en05000726.vsd

IEC05000726 V1 EN

Figure 281:

Simplified logic diagram for SAPTUF

498
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

9.1.3

Function block
SAPTUF
U3P*
BLOCK
BLKTRIP
BLKREST

TRIP
START
RESTORE
BLKDMAGN
FREQ
IEC06000279_2_en.vsd

IEC06000279 V2 EN

Figure 282:

9.1.4

SAPTUF function block

Input and output signals


Table 285:

SAPTUF Input signals

Name

Type

Voltage connection

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output.

BLKREST

BOOLEAN

Blocking restore output.

SAPTUF Output signals

Name

Table 287:

Description

GROUP
SIGNAL

Table 286:

9.1.5

Default

U3P

Type

Description

TRIP

BOOLEAN

Operate/trip signal for frequency.

START

BOOLEAN

Start/pick-up signal for frequency.

RESTORE

BOOLEAN

Restore signal for load restoring purposes.

BLKDMAGN

BOOLEAN

Blocking indication due to low amplitude.

FREQ

REAL

Measured frequency

Setting parameters
SAPTUF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

StartFrequency

35.00 - 75.00

Hz

0.01

48.80

Frequency setting/start value.

IntBlockLevel

0 - 100

%UB

50

Internal blocking level in % of UBase.

TimeDlyOperate

0.000 - 60.000

0.001

0.200

Operate time delay in over/underfrequency mode.

TimeDlyReset

0.000 - 60.000

0.001

0.000

Time delay for reset.

TimeDlyRestore

0.000 - 60.000

0.001

0.000

Restore time delay.

Table continues on next page

499
Technical reference manual

Section 9
Frequency protection
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

RestoreFreq

45.00 - 65.00

Hz

0.01

50.10

Restore frequency if frequency is above


frequency value.

TimerOperation

Definite timer
Volt based timer

Definite timer

Setting for choosing timer mode.

UNom

50 - 150

%UB

100

Nominal voltage in % of UBase for


voltage based timer.

UMin

50 - 150

%UB

90

Lower operation limit in % of UBase for


voltage based timer.

Exponent

0.0 - 5.0

0.1

1.0

For calculation of the curve form for


voltage based timer.

tMax

0.010 - 60.000

0.001

1.000

Maximum time operation limit for voltage


based timer.

tMin

0.010 - 60.000

0.001

1.000

Minimum time operation limit for voltage


based timer.

9.1.6

Description

Technical data
Table 288:

SAPTUF technical data

Function

Range or value

Accuracy

Operate value, start function

(35.00-75.00) Hz

2.0 mHz

Operate time, start function

100 ms typically

Reset time, start function

100 ms typically

Operate time, definite time function

(0.000-60.000)s

0.5%
10 ms

Reset time, definite time function

(0.000-60.000)s

0.5%
10 ms

Voltage dependent time delay

Settings:
UNom=(50-150)% of Ubase
UMin=(50-150)% of Ubase
Exponent=0.0-5.0
tMax=(0.000-60.000)s
tMin=(0.000-60.000)s

Class 5 +
200 ms

U - UMin
t=
UNom - UMin

Exponent

( tMax - tMin ) + tMin

EQUATION1182 V1 EN

(Equation 146)

U=Umeasured

9.2

Overfrequency protection SAPTOF


Function description
Overfrequency protection

IEC 61850
identification

IEC 60617
identification

SAPTOF

ANSI/IEEE C37.2
device number
81

f>
SYMBOL-O V1 EN

500
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

9.2.1

Introduction
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs at sudden load drops or shunt faults in the power network.
Close to the generating plant, generator governor problems can also cause over
frequency.
SAPTOF is used mainly for generation shedding and remedial action schemes. It is
also used as a frequency stage initiating load restoring.
SAPTOF is provided with an undervoltage blocking.
The operation is based on positive sequence voltage measurement and requires two
phase-phase or three phase-neutral voltages to be connected. For information about
how to connect analog inputs, refer to Application manual/IED application/
Analog inputs/Setting guidelines

9.2.2

Principle of operation
Overfrequency protection SAPTOF is used to detect high power system frequency.
SAPTOF has a settable definite time delay. If the frequency remains above the set
value for a time period corresponding to the chosen time delay, the corresponding
TRIP signal is issued. To avoid an unwanted TRIP due to uncertain frequency
measurement at low voltage magnitude, a voltage controlled blocking of the
function is available from the preprocessing function, that is, if the voltage is lower
than the set blocking voltage in the preprocessing function, the function is blocked
and no START or TRIP signal is issued.

9.2.2.1

Measurement principle
The fundamental frequency of the positive sequence voltage is measured
continuously, and compared with the set value, StartFrequency. Overfrequency
protection SAPTOF is dependent on the voltage magnitude. If the voltage
magnitude decreases below the setting IntBlockLevel, SAPTOF is blocked, and the
output BLKDMAGN is issued. All voltage settings are made in percent of the
UBase, which should be set as a phase-phase voltage in kV. To avoid oscillations
of the output START signal, a hysteresis has been included.

9.2.2.2

Time delay
The time delay for Overfrequency protection SAPTOF (81) is a settable definite
time delay, specified by the setting TimeDlyOperate.
TRIP signal issuing requires that the overfrequency condition continues for at least
the user set time delay, TimeDlyReset. If the START condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
501

Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

within a user defined reset time, TimeDlyReset, the START output is reset, after
that the defined reset time has elapsed. It is to be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.

9.2.2.3

Blocking
It is possible to block overfrequency protection SAPTOF partially or completely,
by binary input signals or by parameter settings, where:
BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.2.2.4

Design
The frequency measuring element continuously measures the frequency of the
positive sequence voltage and compares it to the setting StartFrequency. The
frequency signal is filtered to avoid transients due to switchings and faults in the
power system. The time integrator operates due to a definite delay time. The design
of overfrequency protection SAPTOF is schematically described in figure 283.

BLOCK
BLKTRIP

BLOCK
Comparator
U < IntBlockLevel

Voltage

Time integrator
Definite Time Delay

Frequency

Comparator
f > StartFrequency

BLKDMAGN

OR

START

Start
&
Trip
Output
Logic

START

TimeDlyOperate
TRIP
TimeDlyReset
TRIP

en05000735.vsd

IEC05000735 V1 EN

Figure 283:

Schematic design of overfrequency protection SAPTOF

502
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

9.2.3

Function block
SAPTOF
U3P*
BLOCK
BLKTRIP

TRIP
START
BLKDMAGN
FREQ
IEC06000280_2_en.vsd

IEC06000280 V2 EN

Figure 284:

9.2.4

SAPTOF function block

Input and output signals


Table 289:

SAPTOF Input signals

Name

Type
GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output.

SAPTOF Output signals

Name

Table 291:

Description

U3P

Table 290:

9.2.5

Default

Type

Description

TRIP

BOOLEAN

Operate/trip signal for frequency.

START

BOOLEAN

Start/pick-up signal for frequency.

BLKDMAGN

BOOLEAN

Blocking indication due to low amplitude.

FREQ

REAL

Measured frequency

Setting parameters
SAPTOF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

StartFrequency

35.00 - 75.00

Hz

0.01

51.20

Frequency setting/start value.

IntBlockLevel

0 - 100

%UB

50

Internal blocking level in % of UBase.

TimeDlyOperate

0.000 - 60.000

0.001

0.000

Operate time delay in over/underfrequency mode.

TimeDlyReset

0.000 - 60.000

0.001

0.000

Time delay for reset.

503
Technical reference manual

Section 9
Frequency protection
9.2.6

1MRK 505 222-UEN B

Technical data
Table 292:

SAPTOF technical data

Function

9.3

Range or value

Accuracy

Operate value, start function

(35.00-75.00) Hz

2.0 mHz at
symmetrical threephase voltage

Operate time, start function

100 ms typically at fset -0.5 Hz to fset +0.5 Hz

Reset time, start function

100 ms typically

Operate time, definite time


function

(0.000-60.000)s

0.5% 10 ms

Reset time, definite time


function

(0.000-60.000)s

0.5% 10 ms

Rate-of-change frequency protection SAPFRC


Function description
Rate-of-change frequency protection

IEC 61850
identification

IEC 60617
identification

SAPFRC

ANSI/IEEE C37.2
device number
81

df/dt >
<
SYMBOL-N V1 EN

9.3.1

Introduction
Rate-of-change frequency protection function (SAPFRC) gives an early indication
of a main disturbance in the system. SAPFRC can be used for generation shedding,
load shedding and remedial action schemes. SAPFRC can discriminate between
positive or negative change of frequency.
SAPFRC is provided with an undervoltage blocking. The operation is based on
positive sequence voltage measurement and requires two phase-phase or three phaseneutral voltages to be connected. For information about how to connect analog
inputs, refer to Application manual/IED application/Analog inputs/Setting
guidelines.

9.3.2

Principle of operation
Rate-of-change frequency protection SAPFRC is used to detect fast power system
frequency changes, increase as well as, decrease at an early stage. SAPFRC has a
settable definite time delay. If the rate-of-change of frequency remains below the
set value, for negative rate-of-change, for a time period equal to the chosen time
delay, the TRIP signal is issued. If the rate-of-change of frequency remains above
the set value, for positive rate-of-change, for a time period equal to the chosen time

504
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

delay, the TRIP signal is issued. To avoid an unwanted TRIP due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of
the function is available, that is if the voltage is lower than the set blocking voltage
IntBlockLevel, the function is blocked and no START or TRIP signal is issued. If
the frequency recovers, after a frequency decrease, a restore signal is issued.

9.3.2.1

Measurement principle
The rate-of-change of the fundamental frequency of the selected voltage is
measured continuously, and compared with the set value, StartFreqGrad. Rate-ofchange frequency protection SAPFRC is also dependent on the voltage magnitude.
If the voltage magnitude decreases below the setting IntBlockLevel, SAPFRC is
blocked, and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad, controls if SAPFRC reacts on a positive or on a negative change in
frequency. If SAPFRC is used for decreasing frequency that is, the setting
StartFreqGrad has been given a negative value, and a trip signal has been issued,
then a 100 ms pulse is issued on the RESTORE output, when the frequency
recovers to a value higher than the setting RestoreFreq. A positive setting of
StartFreqGrad, sets SAPFRC to START and TRIP for frequency increases.
To avoid oscillations of the output START signal, a hysteresis has been included.

9.3.2.2

Time delay
Rate-of-change frequency protection SAPFRC has a settable definite time delay,
tTrip. .
Trip signal issuing requires that the rate-of-change of frequency condition
continues for at least the user set time delay, tTrip. If the START condition, with
respect to the measured frequency ceases during the delay time, and is not fulfilled
again within a user defined reset time, tReset, the START output is reset, after that
the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient
for the signal to only return back into the hysteresis area.
The RESTORE output of SAPFRC is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s
the restore functionality is disabled, and no output will be given. The restore
functionality is only active for lowering frequency conditions and the restore
sequence is disabled if a new negative frequency gradient is detected during the
restore period, defined by the settings RestoreFreq and tRestore.

9.3.2.3

Blocking
Rate-of-change frequency protection (SAPFRC) can be partially or totally blocked,
by binary input signals or by parameter settings, where:

505
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

BLOCK:

blocks all outputs

BLKTRIP:

blocks the TRIP output

BLKREST:

blocks the RESTORE output

If the measured voltage level decreases below the setting of IntBlockLevel, both the
START and the TRIP outputs, are blocked.

9.3.2.4

Design
Rate-of-change frequency protection (SAPFRC) measuring element continuously
measures the frequency of the selected voltage and compares it to the setting
StartFreqGrad. The frequency signal is filtered to avoid transients due to power
system switchings and faults. The time integrator operates with a definite delay
time. When the frequency has returned back to the setting of RestoreFreq, the
RESTORE output is issued after the time delay tRestore, if the TRIP signal has
earlier been issued. The sign of the setting StartFreqGrad is essential, and controls
if the function is used for raising or lowering frequency conditions. The design of
SAPFRC is schematically described in figure 285.

BLOCK
BLKTRIP
BLKRESET

Voltage

OR

BLOCK
BLKDMAGN

Comparator
U < IntBlockLevel

Rate-of-Change
of Frequency

Comparator
If
[StartFreqGrad<0
START
AND
df/dt < StartFreqGrad]
OR
[StartFreqGrad>0
AND
df/dt > StartFreqGrad]
Then
START

Time integrator
Definite Time Delay
TimeDlyOperate

Start
&
Trip
Output
Logic

START

TimeDlyReset
TRIP

100 ms
Frequency

Comparator
f > RestoreFreq

TimeDlyRestore

RESTORE

en05000835.vsd
IEC05000835 V1 EN

Figure 285:

Schematic design of Rate-of-change frequency protection SAPFRC

506
Technical reference manual

Section 9
Frequency protection

1MRK 505 222-UEN B

9.3.3

Function block
SAPFRC
U3P*
BLOCK
BLKTRIP
BLKREST

TRIP
START
RESTORE
BLKDMAGN
IEC06000281-2-en.vsd

IEC06000281 V2 EN

Figure 286:

9.3.4

SAPFRC function block

Input and output signals


Table 293:

SAPFRC Input signals

Name

Type
GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKTRIP

BOOLEAN

Blocking operate output.

BLKREST

BOOLEAN

Blocking restore output.

SAPFRC Output signals

Name

Table 295:

Description

U3P

Table 294:

9.3.5

Default

Type

Description

TRIP

BOOLEAN

Operate/trip signal for frequencyGradient

START

BOOLEAN

Start/pick-up signal for frequencyGradient

RESTORE

BOOLEAN

Restore signal for load restoring purposes.

BLKDMAGN

BOOLEAN

Blocking indication due to low amplitude.

Setting parameters
SAPFRC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for the phase-phase voltage


in kV

StartFreqGrad

-10.00 - 10.00

Hz/s

0.01

0.50

Frequency gradient start value. Sign


defines direction.

IntBlockLevel

0 - 100

%UB

50

Internal blocking level in % of UBase.

tTrip

0.000 - 60.000

0.001

0.200

Operate time delay in pos./neg.


frequency gradient mode.

RestoreFreq

45.00 - 65.00

Hz

0.01

49.90

Restore frequency if frequency is above


frequency value (Hz)

tRestore

0.000 - 60.000

0.001

0.000

Restore time delay.

tReset

0.000 - 60.000

0.001

0.000

Time delay for reset.

507
Technical reference manual

Section 9
Frequency protection
9.3.6

1MRK 505 222-UEN B

Technical data
Table 296:

SAPFRC Technical data

Function

Range or value

Accuracy

Operate value, start function

(-10.00-10.00) Hz/s

10.0 mHz/s

Operate value, internal


blocking level

(0-100)% of UBase

0.5% of Ur

Operate time, start function

100 ms typically

508
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Section 10

Multipurpose protection

About this chapter


This chapter describes Multipurpose protection and includes the General current
and voltage function. The way the functions work, their setting parameters,
function blocks, input and output signals and technical data are included for each
function.

10.1

General current and voltage protection CVGAPC


Function description
General current and voltage protection

10.1.1

IEC 61850
identification
CVGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The General current and voltage protection (CVGAPC) can be utilized as a
negative sequence current protection detecting unsymmetrical conditions such as
open phase or unsymmetrical faults.
CVGAPC can also be used to improve phase selection for high resistive earth
faults, outside the distance protection reach, for the transmission line. Three
functions are used, which measures the neutral current and each of the three phase
voltages. This will give an independence from load currents and this phase
selection will be used in conjunction with the detection of the earth fault from the
directional earth fault protection function.

10.1.2

Principle of operation

10.1.2.1

Measured quantities within CVGAPC


General current and voltage protection (CVGAPC) function is always connected to
three-phase current and three-phase voltage input in the configuration tool, but it
will always measure only one current and one voltage quantity selected by the end
user in the setting tool.
The user can select to measure one of the current quantities shown in table 297.

509
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Table 297:

Current selection for CVGAPC function

Set value for the


parameter

CurrentInput

Comment

Phase1

CVGAPC function will measure the phase L1 current phasor

Phase2

CVGAPC function will measure the phase L2 current phasor

Phase3

CVGAPC function will measure the phase L3 current phasor

PosSeq

CVGAPC function will measure internally calculated positive sequence


current phasor

NegSeq

CVGAPC function will measure internally calculated negative


sequence current phasor

3ZeroSeq

CVGAPC function will measure internally calculated zero sequence


current phasor multiplied by factor 3

MaxPh

CVGAPC function will measure current phasor of the phase with


maximum magnitude

MinPh

CVGAPC function will measure current phasor of the phase with


minimum magnitude

UnbalancePh

CVGAPC function will measure magnitude of unbalance current, which


is internally calculated as the algebraic magnitude difference between
the current phasor of the phase with maximum magnitude and current
phasor of the phase with minimum magnitude. Phase angle will be set
to 0 all the time

10

Phase1-Phase2

CVGAPC function will measure the current phasor internally calculated


as the vector difference between the phase L1 current phasor and
phase L2 current phasor (IL1-IL2)

11

Phase2-Phase3

CVGAPC function will measure the current phasor internally calculated


as the vector difference between the phase L2 current phasor and
phase L3 current phasor (IL2-IL3)

12

Phase3-Phase1

CVGAPC function will measure the current phasor internally calculated


as the vector difference between the phase L3 current phasor and
phase L1 current phasor ( IL3-IL1)

13

MaxPh-Ph

CVGAPC function will measure ph-ph current phasor with the


maximum magnitude

14

MinPh-Ph

CVGAPC function will measure ph-ph current phasor with the


minimum magnitude

15

UnbalancePh-Ph

CVGAPC function will measure magnitude of unbalance current, which


is internally calculated as the algebraic magnitude difference between
the ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0 all the
time

The user can select to measure one of the voltage quantities shown in table 298:
Table 298:

Voltage selection for CVGAPC function

Set value for the


parameter

VoltageInput

Comment

Phase1

CVGAPC function will measure the phase L1 voltage phasor

Phase2

CVGAPC function will measure the phase L2 voltage phasor

Phase3

CVGAPC function will measure the phase L3 voltage phasor

Table continues on next page


510
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Set value for the


parameter

VoltageInput

Comment

PosSeq

CVGAPC function will measure internally calculated positive sequence


voltage phasor

-NegSeq

CVGAPC function will measure internally calculated negative


sequence voltage phasor. This voltage phasor will be intentionally
rotated for 180 in order to enable easier settings for the directional
feature when used.

-3ZeroSeq

CVGAPC function will measure internally calculated zero sequence


voltage phasor multiplied by factor 3. This voltage phasor will be
intentionally rotated for 180 in order to enable easier settings for the
directional feature when used.

MaxPh

CVGAPC function will measure voltage phasor of the phase with


maximum magnitude

MinPh

CVGAPC function will measure voltage phasor of the phase with


minimum magnitude

UnbalancePh

CVGAPC function will measure magnitude of unbalance voltage,


which is internally calculated as the algebraic magnitude difference
between the voltage phasor of the phase with maximum magnitude
and voltage phasor of the phase with minimum magnitude. Phase
angle will be set to 0 all the time

10

Phase1-Phase2

CVGAPC function will measure the voltage phasor internally


calculated as the vector difference between the phase L1 voltage
phasor and phase L2 voltage phasor (UL1-UL2)

11

Phase2-Phase3

CVGAPC function will measure the voltage phasor internally


calculated as the vector difference between the phase L2 voltage
phasor and phase L3 voltage phasor (UL2-UL3)

12

Phase3-Phase1

CVGAPC function will measure the voltage phasor internally


calculated as the vector difference between the phase L3 voltage
phasor and phase L1 voltage phasor ( UL3-UL1)

13

MaxPh-Ph

CVGAPC function will measure ph-ph voltage phasor with the


maximum magnitude

14

MinPh-Ph

CVGAPC function will measure ph-ph voltage phasor with the


minimum magnitude

15

UnbalancePh-Ph

CVGAPC function will measure magnitude of unbalance voltage,


which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and phph voltage phasor with minimum magnitude. Phase angle will be set to
0 all the time

It is important to notice that the voltage selection from table 298 is always
applicable regardless the actual external VT connections. The three-phase VT
inputs can be connected to IED as either three phase-to-ground voltages UL1, UL2
& UL3 or three phase-to-phase voltages UL1L2, UL2L3 & UL3L1). This information
about actual VT connection is entered as a setting parameter for the pre-processing
block, which will then take automatic care about it.
The user can select one of the current quantities shown in table 299 for built-in
current restraint feature:

511
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Table 299:

Restraint current selection for CVGAPC function

Set value for the


parameter RestrCurr

10.1.2.2

Comment

PosSeq

CVGAPC function will measure internally calculated positive sequence


current phasor

NegSeq

CVGAPC function will measure internally calculated negative


sequence current phasor

3ZeroSeq

CVGAPC function will measure internally calculated zero sequence


current phasor multiplied by factor 3

MaxPh

CVGAPC function will measure current phasor of the phase with


maximum magnitude

Base quantities for CVGAPC function


The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages, shall be entered as setting parameters for
every CVGAPC function.
Base current shall be entered as:
1.
2.

rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 297.
rated phase current of the protected object in primary amperes multiplied by
3 (1.732 Iphase), when the measured Current Quantity is selected from 10
to 15, as shown in table 297.

Base voltage shall be entered as:


1.
2.

10.1.2.3

rated phase-to-earth voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 298.
rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 298.

Built-in overcurrent protection steps


Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity
(see table 297) with the set pickup level. Non-directional overcurrent step will
pickup if the magnitude of the measured current quantity is bigger than this set
level. Reset ratio is settable, with default value of 0.96. However depending on
other enabled built-in features this overcurrent pickup might not cause the
overcurrent step start signal. Start signal will only come if all of the enabled builtin features in the overcurrent step are fulfilled at the same time.

512
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Second harmonic feature

The overcurrent protection step can be restrained by a second harmonic component


in the measured current quantity (see table 297). However it shall be noted that this
feature is not applicable when one of the following measured currents is selected:

PosSeq (positive sequence current)


NegSeq (negative sequence current)
UnbalancePh (unbalance phase current)
UnbalancePh-Ph (unbalance ph-ph current)

This feature will simple prevent overcurrent step start if the second-to-first
harmonic ratio in the measured current exceeds the set level.

Directional feature

The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 297) and
measured voltage phasor (see table 298). In protection terminology it means that
the General currrent and voltage protection (CVGAPC) function can be made
directional by enabling this built-in feature. In that case overcurrent protection step
will only operate if the current flow is in accordance with the set direction
(Forward, which means towards the protected object, or Reverse, which means
from the protected object). For this feature it is of the outmost importance to
understand that the measured voltage phasor (see table 298) and measured current
phasor (see table 297) will be used for directional decision. Therefore it is the sole
responsibility of the end user to select the appropriate current and voltage signals in
order to get a proper directional decision. CVGAPC function will NOT do this
automatically. It will just simply use the current and voltage phasors selected by
the end user to check for the directional criteria.
Table 300 gives an overview of the typical choices (but not the only possible ones)
for these two quantities for traditional directional relays.
Table 300:
Set value for the
parameter

CurrentInput

Typical current and voltage choices for directional feature


Set value for the
parameter

VoltageInput

Comment

PosSeq

PosSeq

Directional positive sequence overcurrent function is


obtained. Typical setting for RCADir is from -45 to
-90 depending on the power

NegSeq

-NegSeq

Directional negative sequence overcurrent function is


obtained. Typical setting for RCADir is from -45 to
-90 depending on the power system voltage level (X/
R ratio)

3ZeroSeq

-3ZeroSeq

Directional zero sequence overcurrent function is


obtained. Typical setting for RCADir is from 0 to
-90 depending on the power system earthing (that
is, solidly earthed, earthed via resistor)

Table continues on next page

513
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Set value for the


parameter

CurrentInput

Set value for the


parameter

Comment

VoltageInput

Phase1

Phase2-Phase3

Directional overcurrent function for the first phase is


obtained. Typical setting for RCADir is +30 or +45

Phase2

Phase3-Phase1

Directional overcurrent function for the second phase


is obtained. Typical setting for RCADir is +30 or +45

Phase3

Phase1-Phase2

Directional overcurrent function for the third phase is


obtained. Typical setting for RCADir is +30 or +45

Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
Two types of directional measurement principles are available, I & U and
IcosPhi&U. The first principle, referred to as "I & U" in the parameter setting tool,
checks that:

the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by
the relay operate angle, ROADir parameter setting; see figure 287).

U=-3U0

RCADir
Ipickup

ROADir

I=3Io

Operate region
mta line
en05000252.vsd
IEC05000252 V1 EN

Figure 287:

I & U directional operating principle for CVGAPC function

where:

RCADir is -75
ROADir is 50

The second principle, referred to as "IcosPhi&U" in the parameter setting tool,


checks that:

514
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

that the product Icos() is bigger than the set pick-up level, where is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined
by the Icos() straight line and the relay operate angle, ROADir parameter
setting; see figure 287).

U=-3U0

RCADir
Ipickup

ROADir

I=3Io

Operate region
mta line

en05000253.vsd
IEC05000253 V1 EN

Figure 288:

CVGAPC, IcosPhi&U directional operating principle

where:

RCADir is -75
ROADir is 50

Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the preset value. User can select one of the following three options:

Non-directional (operation allowed for low magnitude of the reference voltage)


Block (operation prevented for low magnitude of the reference voltage)
Memory (memory voltage shall be used to determine direction of the current)

It shall also be noted that the memory duration is limited in the algorithm to 100
ms. After that time the current direction will be locked to the one determined
during memory time and it will re-set only if the current fails below set pickup
level or voltage goes above set voltage memory limit.

Voltage restraint/control feature

The overcurrent protection step operation can be can be made dependent of a


measured voltage quantity (see table 298). Practically then the pickup level of the
overcurrent step is not constant but instead decreases with the decrease in the
magnitude of the measured voltage quantity. Two different types of dependencies
are available:

Voltage restraint overcurrent (when setting parameter VDepMode_OC1=Slope)


515

Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

ULowLimit_OC1

UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd

IEC05000324 V1 EN

Figure 289:

Example for OC1 step current pickup level variation as function of


measured voltage magnitude in Slope mode of operation

Voltage controlled overcurrent (when setting parameter


VDepMode_OC1=Step)
OC1 Stage Pickup Level

StartCurr_OC1

VDepFact_OC1 * StartCurr_OC1

UHighLimit_OC1

Selected Voltage Magnitude


en05000323.vsd

IEC05000323 V1 EN

Figure 290:

Example for OC1 step current pickup level variation as function of


measured voltage magnitude in Step mode of operation

This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will
as well affect the pickup current value for calculation of operate times for IDMT

516
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

curves (overcurrent with IDMT curve will operate faster during low voltage
conditions).

Current restraint feature

The overcurrent protection step operation can be made dependent of a restraining


current quantity (see table 299). Practically then the pickup level of the overcurrent
step is not constant but instead increases with the increase in the magnitude of the
restraining current.

IMeasured
te
ra
pe
O

ea
ar

IsetHigh

tr
es
*I r
f
f
e
Co
s tr
e
I>R

ain

IsetLow

atan(RestrCoeff)
Restraint
en05000255.vsd
IEC05000255 V1 EN

Figure 291:

Current pickup variation with restraint current magnitude

This feature will simply prevent overcurrent step to start if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for
calculation of operate times for IDMT curves. This means that the IDMT curve
operate time will not be influenced by the restrain current magnitude.
When set, the start signal will start definite time delay or inverse (IDMT) time
delay in accordance with the end user setting. If the start signal has value one for
longer time than the set time delay, the overcurrent step will set its trip signal to
one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the end user setting.

10.1.2.4

Built-in undercurrent protection steps


Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 297) with the set pickup
level. The undercurrent step will pickup and set its start signal to one if the
magnitude of the measured current quantity is smaller than this set level. The start
signal will start definite time delay with set time delay. If the start signal has value
one for longer time than the set time delay the undercurrent step will set its trip
517

Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

signal to one. Reset of the start and trip signal can be instantaneous or time delay in
accordance with the setting.

10.1.2.5

Built-in overvoltage protection steps


Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity
(see table 298) with the set pickup level. The overvoltage step will pickup if the
magnitude of the measured voltage quantity is bigger than this set level. Reset ratio
is settable, with default value of 0.99.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the overvoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.

10.1.2.6

Built-in undervoltage protection steps


Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Undervoltage step simply compares the magnitude of the measured voltage
quantity (see table 298) with the set pickup level. The undervoltage step will
pickup if the magnitude of the measured voltage quantity is smaller than this set
level. Reset ratio is settable, with default value of 1.01.
The start signal will start definite time delay or inverse (IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer
time than the set time delay, the undervoltage step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.

10.1.2.7

Logic diagram
The simplified internal logics, for CVGAPC function are shown in the following
figures.

518
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

IED

Phasors &
samples

Current and voltage selection


settings

Selection of which current


and voltage shall be given to
the built-in protection
elements

Selected current
Selected voltage

Restraint current selection

Selection of restraint current

Selected restraint current

Phasors &
samples

Phasor calculation of
individual currents

CVGAPC function

Phasor calculation of
individual voltages

A/D conversion scaling


with CT ratio

A/D conversion
scaling with CT ratio

ADM

IEC05000169_2_en.vsd
IEC05000169 V2 EN

Figure 292:

Treatment of measured currents within IED for CVGAPC function

Figure 292 shows how internal treatment of measured currents is done for
multipurpose protection function
The following currents and voltages are inputs to the multipurpose protection
function. They must all be expressed in true power system (primary) Amperes and
kilovolts.
1.
2.
3.

Instantaneous values (samples) of currents & voltages from one three-phase


current and one three-phase voltage input.
Fundamental frequency phasors from one three-phase current and one threephase voltage input calculated by the pre-processing modules.
Sequence currents & voltages from one three-phase current and one threephase voltage input calculated by the pre-processing modules.

The multipurpose protection function:


1.
2.
3.

Selects one current from the three-phase input system (see table 297) for
internally measured current.
Selects one voltage from the three-phase input system (see table 298) for
internally measured voltage.
Selects one current from the three-phase input system (see table 299) for
internally measured restraint current.

519
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

CURRENT

UC1
2
Selected current

TRUC1

nd

Harmonic
restraint

STUC2

UC2
2nd Harmonic
restraint

TRUC2

STOC1

OC1

Selected restraint current

2nd Harmonic
restraint

TROC1

Current restraint

BLK2ND
DIROC1

Directionality
Voltage control /
restraint

STOC2
TROC2

OC2
2nd Harmonic
restraint
Current restraint
Directionality

UDIRLOW
DIROC2

Voltage control /
restraint

STOV1

OV1

TROV1

OV2

TROV2

UV1

TRUV1

STOV2

Selected voltage

STUV1

STUV2

UV2

TRUV2

VOLTAGE

en05000170.vsd
IEC05000170 V1 EN

Figure 293:

CVGAPC function main logic diagram for built-in protection elements

520
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Logic in figure 293 can be summarized as follows:


1.
2.
3.

Enable
second
harmonic

The selected currents and voltage are given to built-in protection elements.
Each protection element and step makes independent decision about status of
its START and TRIP output signals.
More detailed internal logic for every protection element is given in the
following four figures
Common START and TRIP signals from all built-in protection elements &
steps (internal OR logic) are available from multipurpose function as well.

Second
harmonic check

DEF time
selected

BLKTROC
1

DEF

AND

TROC1

OR

Selected current

a
b

StartCurr_OC1

a>b

OC1=On
BLKOC1

STOC1

AND

Inverse
Voltage
control or
restraint
feature

Selected voltage

Selected restrain current

Directionality
check

DIR_OK

Inverse
time
selected

Current
Restraint
Feature
Imeasured > k Irestraint

en05000831.vsd

IEC05000831 V1 EN

Figure 294:

Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)

521
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Bin input: BLKUC1TR

Selected current

b>a

DEF

TRUC1

AND

AND

StartCurr_UC1

Operation_UC1=On

STUC1

Bin input: BLKUC1

en05000750.vsd
IEC05000750 V1 EN

Figure 295:

Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has
the same internal logic)

DEF time
selected

BLKTROV1

DEF

AND

TROV1

OR
Selected voltage

a
b

StartVolt_OV1

a>b

STOV1

AND
Inverse

Operation_OV1=On
BLKOV1

Inverse time
selected

en05000751.vsd
IEC05000751 V1 EN

Figure 296:

Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)

522
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

DEF time
selected

BLKTRUV
1

DEF

AND

TRUV1

OR
Selected voltage

b>a

STUV1

AND

StartVolt_UV1

Inverse
Operation_UV1=On
Inverse time
selected

BLKUV1

en05000752.vsd
IEC05000752 V1 EN

Figure 297:

Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)

10.1.3

Function block
CVGAPC
I3P*
U3P*
BLOCK
BLKOC1
BLKOC1TR
ENMLTOC1
BLKOC2
BLKOC2TR
ENMLTOC2
BLKUC1
BLKUC1TR
BLKUC2
BLKUC2TR
BLKOV1
BLKOV1TR
BLKOV2
BLKOV2TR
BLKUV1
BLKUV1TR
BLKUV2
BLKUV2TR

TRIP
TROC1
TROC2
TRUC1
TRUC2
TROV1
TROV2
TRUV1
TRUV2
START
STOC1
STOC2
STUC1
STUC2
STOV1
STOV2
STUV1
STUV2
BLK2ND
DIROC1
DIROC2
UDIRLOW
CURRENT
ICOSFI
VOLTAGE
UIANGLE
IEC05000372-2-en.vsd

IEC05000372 V2 EN

Figure 298:

CVGAPC function block

523
Technical reference manual

Section 10
Multipurpose protection
10.1.4

1MRK 505 222-UEN B

Input and output signals


Table 301:
Name

CVGAPC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

BLKOC1

BOOLEAN

Block of over current function OC1

BLKOC1TR

BOOLEAN

Block of trip for over current function OC1

ENMLTOC1

BOOLEAN

When activated, the current multiplier is in use for


OC1

BLKOC2

BOOLEAN

Block of over current function OC2

BLKOC2TR

BOOLEAN

Block of trip for over current function OC2

ENMLTOC2

BOOLEAN

When activated, the current multiplier is in use for


OC2

BLKUC1

BOOLEAN

Block of under current function UC1

BLKUC1TR

BOOLEAN

Block of trip for under current function UC1

BLKUC2

BOOLEAN

Block of under current function UC2

BLKUC2TR

BOOLEAN

Block of trip for under current function UC2

BLKOV1

BOOLEAN

Block of over voltage function OV1

BLKOV1TR

BOOLEAN

Block of trip for over voltage function OV1

BLKOV2

BOOLEAN

Block of over voltage function OV2

BLKOV2TR

BOOLEAN

Block of trip for over voltage function OV2

BLKUV1

BOOLEAN

Block of under voltage function UV1

BLKUV1TR

BOOLEAN

Block of trip for under voltage function UV1

BLKUV2

BOOLEAN

Block of under voltage function UV2

BLKUV2TR

BOOLEAN

Block of trip for under voltage function UV2

Table 302:
Name

CVGAPC Output signals


Type

Description

TRIP

BOOLEAN

General trip signal

TROC1

BOOLEAN

Trip signal from overcurrent function OC1

TROC2

BOOLEAN

Trip signal from overcurrent function OC2

TRUC1

BOOLEAN

Trip signal from undercurrent function UC1

TRUC2

BOOLEAN

Trip signal from undercurrent function UC2

TROV1

BOOLEAN

Trip signal from overvoltage function OV1

TROV2

BOOLEAN

Trip signal from overvoltage function OV2

TRUV1

BOOLEAN

Trip signal from undervoltage function UV1

TRUV2

BOOLEAN

Trip signal from undervoltage function UV2

Table continues on next page

524
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Name

10.1.5
Table 303:

Type

Description

START

BOOLEAN

General start signal

STOC1

BOOLEAN

Start signal from overcurrent function OC1

STOC2

BOOLEAN

Start signal from overcurrent function OC2

STUC1

BOOLEAN

Start signal from undercurrent function UC1

STUC2

BOOLEAN

Start signal from undercurrent function UC2

STOV1

BOOLEAN

Start signal from overvoltage function OV1

STOV2

BOOLEAN

Start signal from overvoltage function OV2

STUV1

BOOLEAN

Start signal from undervoltage function UV1

STUV2

BOOLEAN

Start signal from undervoltage function UV2

BLK2ND

BOOLEAN

Block from second harmonic detection

DIROC1

INTEGER

Directional mode of OC1 (nondir, forward,reverse)

DIROC2

INTEGER

Directional mode of OC2 (nondir, forward,reverse)

UDIRLOW

BOOLEAN

Low voltage for directional polarization

CURRENT

REAL

Measured current value

ICOSFI

REAL

Measured current multiplied with cos (Phi)

VOLTAGE

REAL

Measured voltage value

UIANGLE

REAL

Angle between voltage and current

Setting parameters
CVGAPC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

CurrentInput

phase1
phase2
phase3
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph

MaxPh

Select current signal which will be


measured inside function

IBase

1 - 99999

3000

Base Current

Table continues on next page

525
Technical reference manual

Section 10
Multipurpose protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

VoltageInput

phase1
phase2
phase3
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph

MaxPh

Select voltage signal which will be


measured inside function

UBase

0.05 - 2000.00

kV

0.05

400.00

Base Voltage

OperHarmRestr

Off
On

Off

Operation of 2nd harmonic restrain Off /


On

l_2nd/l_fund

10.0 - 50.0

1.0

20.0

Ratio of second to fundamental current


harmonic in %

EnRestrainCurr

Off
On

Off

Enable current restrain function On / Off

RestrCurrInput

PosSeq
NegSeq
3*ZeroSeq
Max

PosSeq

Select current signal which will be used


for curr restrain

RestrCurrCoeff

0.00 - 5.00

0.01

0.00

Restraining current coefficient

RCADir

-180 - 180

Deg

-75

Relay Characteristic Angle

ROADir

1 - 90

Deg

75

Relay Operate Angle

LowVolt_VM

0.0 - 5.0

%UB

0.1

0.5

Below this level in % of Ubase setting


ActLowVolt takes over

Operation_OC1

Off
On

Off

Operation OC1 Off / On

StartCurr_OC1

2.0 - 5000.0

%IB

1.0

120.0

Operate current level for OC1 in % of


Ibase

CurveType_OC1

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for OC1

tDef_OC1

0.00 - 6000.00

0.01

0.50

Independent (definitive) time delay of


OC1

Table continues on next page

526
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Name

Step

Default

k_OC1

Values (Range)
0.05 - 999.00

Unit
-

0.01

0.30

Description
Time multiplier for the dependent time
delay for OC1

IMin1

1 - 10000

%IB

100

Minimum operate current for step1 in %


of IBase

tMin_OC1

0.00 - 6000.00

0.01

0.05

Minimum operate time for IEC IDMT


curves for OC1

VCntrlMode_OC1

Voltage control
Input control
Volt/Input control
Off

Off

Control mode for voltage controlled OC1


function

VDepMode_OC1

Step
Slope

Step

Voltage dependent mode OC1 (step,


slope)

VDepFact_OC1

0.02 - 5.00

0.01

1.00

Multiplying factor for I pickup when OC1


is U dependent

ULowLimit_OC1

1.0 - 200.0

%UB

0.1

50.0

Voltage low limit setting OC1 in % of


Ubase

UHighLimit_OC1

1.0 - 200.0

%UB

0.1

100.0

Voltage high limit setting OC1 in % of


Ubase

HarmRestr_OC1

Off
On

Off

Enable block of OC1 by 2nd harmonic


restrain

DirMode_OC1

Non-directional
Forward
Reverse

Non-directional

Directional mode of OC1 (nondir,


forward,reverse)

DirPrinc_OC1

I&U
IcosPhi&U

I&U

Measuring on IandU or IcosPhiandU for


OC1

ActLowVolt1_VM

Non-directional
Block
Memory

Non-directional

Low voltage level action for Dir_OC1


(Nodir, Blk, Mem)

Operation_OC2

Off
On

Off

Operation OC2 Off / On

StartCurr_OC2

2.0 - 5000.0

%IB

1.0

120.0

Operate current level for OC2 in % of


Ibase

CurveType_OC2

ANSI Ext. inv.


ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type

ANSI Def. Time

Selection of time delay curve type for OC2

tDef_OC2

0.00 - 6000.00

0.01

0.50

Independent (definitive) time delay of


OC2

k_OC2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time


delay for OC2

Table continues on next page


527
Technical reference manual

Section 10
Multipurpose protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

IMin2

1 - 10000

%IB

50

Minimum operate current for step2 in %


of IBase

tMin_OC2

0.00 - 6000.00

0.01

0.05

Minimum operate time for IEC IDMT


curves for OC2

VCntrlMode_OC2

Voltage control
Input control
Volt/Input control
Off

Off

Control mode for voltage controlled OC2


function

VDepMode_OC2

Step
Slope

Step

Voltage dependent mode OC2 (step,


slope)

VDepFact_OC2

0.02 - 5.00

0.01

1.00

Multiplying factor for I pickup when OC2


is U dependent

ULowLimit_OC2

1.0 - 200.0

%UB

0.1

50.0

Voltage low limit setting OC2 in % of


Ubase

UHighLimit_OC2

1.0 - 200.0

%UB

0.1

100.0

Voltage high limit setting OC2 in % of


Ubase

HarmRestr_OC2

Off
On

Off

Enable block of OC2 by 2nd harmonic


restrain

DirMode_OC2

Non-directional
Forward
Reverse

Non-directional

Directional mode of OC2 (nondir,


forward,reverse)

DirPrinc_OC2

I&U
IcosPhi&U

I&U

Measuring on IandU or IcosPhiandU for


OC2

ActLowVolt2_VM

Non-directional
Block
Memory

Non-directional

Low voltage level action for Dir_OC2


(Nodir, Blk, Mem)

Operation_UC1

Off
On

Off

Operation UC1 Off / On

EnBlkLowI_UC1

Off
On

Off

Enable internal low current level blocking


for UC1

BlkLowCurr_UC1

0 - 150

%IB

20

Internal low current blocking level for


UC1 in % of Ibase

StartCurr_UC1

2.0 - 150.0

%IB

1.0

70.0

Operate undercurrent level for UC1 in %


of Ibase

tDef_UC1

0.00 - 6000.00

0.01

0.50

Independent (definitive) time delay of UC1

tResetDef_UC1

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite


Time curve UC1

HarmRestr_UC1

Off
On

Off

Enable block of UC1 by 2nd harmonic


restrain

Operation_UC2

Off
On

Off

Operation UC2 Off / On

EnBlkLowI_UC2

Off
On

Off

Enable internal low current level blocking


for UC2

BlkLowCurr_UC2

0 - 150

%IB

20

Internal low current blocking level for


UC2 in % of Ibase

StartCurr_UC2

2.0 - 150.0

%IB

1.0

70.0

Operate undercurrent level for UC2 in %


of Ibase

tDef_UC2

0.00 - 6000.00

0.01

0.50

Independent (definitive) time delay of UC2

HarmRestr_UC2

Off
On

Off

Enable block of UC2 by 2nd harmonic


restrain

Table continues on next page


528
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Operation_OV1

Off
On

Off

Operation OV1 Off / On

StartVolt_OV1

2.0 - 200.0

%UB

0.1

150.0

Operate voltage level for OV1 in % of


Ubase

CurveType_OV1

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for OV1

tDef_OV1

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite


time use of OV1

tMin_OV1

0.00 - 6000.00

0.01

0.05

Minimum operate time for IDMT curves


for OV1

k_OV1

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time


delay for OV1

Operation_OV2

Off
On

Off

Operation OV2 Off / On

StartVolt_OV2

2.0 - 200.0

%UB

0.1

150.0

Operate voltage level for OV2 in % of


Ubase

CurveType_OV2

Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve

Definite time

Selection of time delay curve type for OV2

tDef_OV2

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite


time use of OV2

tMin_OV2

0.00 - 6000.00

0.01

0.05

Minimum operate time for IDMT curves


for OV2

k_OV2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time


delay for OV2

Operation_UV1

Off
On

Off

Operation UV1 Off / On

StartVolt_UV1

2.0 - 150.0

%UB

0.1

50.0

Operate undervoltage level for UV1 in %


of Ubase

CurveType_UV1

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for UV1

tDef_UV1

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite


time use of UV1

tMin_UV1

0.00 - 6000.00

0.01

0.05

Minimum operate time for IDMT curves


for UV1

k_UV1

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time


delay for UV1

EnBlkLowV_UV1

Off
On

On

Enable internal low voltage level


blocking for UV1

BlkLowVolt_UV1

0.0 - 5.0

%UB

0.1

0.5

Internal low voltage blocking level for


UV1 in % of Ubase

Operation_UV2

Off
On

Off

Operation UV2 Off / On

Table continues on next page

529
Technical reference manual

Section 10
Multipurpose protection
Name

Step

Default

StartVolt_UV2

2.0 - 150.0

%UB

0.1

50.0

Operate undervoltage level for UV2 in %


of Ubase

CurveType_UV2

Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve

Definite time

Selection of time delay curve type for UV2

tDef_UV2

0.00 - 6000.00

0.01

1.00

Operate time delay in sec for definite


time use of UV2

tMin_UV2

0.00 - 6000.00

0.01

0.05

Minimum operate time for IDMT curves


for UV2

k_UV2

0.05 - 999.00

0.01

0.30

Time multiplier for the dependent time


delay for UV2

EnBlkLowV_UV2

Off
On

On

Enable internal low voltage level


blocking for UV2

BlkLowVolt_UV2

0.0 - 5.0

%UB

0.1

0.5

Internal low voltage blocking level for


UV2 in % of Ubase

Table 304:

Values (Range)

1MRK 505 222-UEN B

Unit

Description

CVGAPC Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

CurrMult_OC1

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for OC1

ResCrvType_OC1

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for OC1

tResetDef_OC1

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite


Time curve OC1

P_OC1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OC1

A_OC1

0.000 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OC1

B_OC1

0.000 - 99.000

0.001

0.000

Parameter B for customer programmable


curve for OC1

C_OC1

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for OC1

PR_OC1

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for OC1

TR_OC1

0.005 - 600.000

0.001

13.500

Parameter TR for customer


programmable curve for OC1

CR_OC1

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for OC1

CurrMult_OC2

1.0 - 10.0

0.1

2.0

Multiplier for scaling the current setting


value for OC2

ResCrvType_OC2

Instantaneous
IEC Reset
ANSI reset

Instantaneous

Selection of reset curve type for OC2

tResetDef_OC2

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite


Time curve OC2

P_OC2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OC2

Table continues on next page


530
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

A_OC2

0.000 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OC2

B_OC2

0.000 - 99.000

0.001

0.000

Parameter B for customer programmable


curve for OC2

C_OC2

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for OC2

PR_OC2

0.005 - 3.000

0.001

0.500

Parameter PR for customer


programmable curve for OC2

TR_OC2

0.005 - 600.000

0.001

13.500

Parameter TR for customer


programmable curve for OC2

CR_OC2

0.1 - 10.0

0.1

1.0

Parameter CR for customer


programmable curve for OC2

tResetDef_UC2

0.00 - 6000.00

0.01

0.00

Reset time delay used in IEC Definite


Time curve UC2

ResCrvType_OV1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for OV1

tResetDef_OV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time


use of OV1

tResetIDMT_OV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for IDMT curves


for OV1

A_OV1

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OV1

B_OV1

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for OV1

C_OV1

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for OV1

D_OV1

0.000 - 10.000

0.001

0.000

Parameter D for customer


programmable curve for OV1

P_OV1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OV1

ResCrvType_OV2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for OV2

tResetDef_OV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time


use of OV2

tResetIDMT_OV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for IDMT curves


for OV2

A_OV2

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for OV2

B_OV2

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for OV2

C_OV2

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for OV2

D_OV2

0.000 - 10.000

0.001

0.000

Parameter D for customer


programmable curve for OV2

P_OV2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for OV2

Table continues on next page

531
Technical reference manual

Section 10
Multipurpose protection
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

ResCrvType_UV1

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for UV1

tResetDef_UV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time


use of UV1

tResetIDMT_UV1

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for IDMT curves


for UV1

A_UV1

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for UV1

B_UV1

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for UV1

C_UV1

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for UV1

D_UV1

0.000 - 10.000

0.001

0.000

Parameter D for customer


programmable curve for UV1

P_UV1

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for UV1

ResCrvType_UV2

Instantaneous
Frozen timer
Linearly decreased

Instantaneous

Selection of reset curve type for UV2

tResetDef_UV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for definite time


use of UV2

tResetIDMT_UV2

0.00 - 6000.00

0.01

0.00

Reset time delay in sec for IDMT curves


for UV2

A_UV2

0.005 - 999.000

0.001

0.140

Parameter A for customer programmable


curve for UV2

B_UV2

0.500 - 99.000

0.001

1.000

Parameter B for customer programmable


curve for UV2

C_UV2

0.000 - 1.000

0.001

1.000

Parameter C for customer


programmable curve for UV2

D_UV2

0.000 - 10.000

0.001

0.000

Parameter D for customer


programmable curve for UV2

P_UV2

0.001 - 10.000

0.001

0.020

Parameter P for customer programmable


curve for UV2

532
Technical reference manual

Section 10
Multipurpose protection

1MRK 505 222-UEN B

10.1.6

Technical data
Table 305:

CVGAPC technical data

Function

Range or value

Accuracy

Measuring current
input

phase1, phase2, phase3, PosSeq,


NegSeq, 3*ZeroSeq, MaxPh, MinPh,
UnbalancePh, phase1-phase2, phase2phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Base current

(1 - 99999) A

Measuring voltage
input

phase1, phase2, phase3, PosSeq, NegSeq, -3*ZeroSeq, MaxPh, MinPh,


UnbalancePh, phase1-phase2, phase2phase3, phase3-phase1, MaxPh-Ph,
MinPh-Ph, UnbalancePh-Ph

Base voltage

(0.05 - 2000.00) kV

Start overcurrent,
step 1 and 2

(2 - 5000)% of IBase

1.0% of Ir for I<Ir


1.0% of I for I>Ir

Start undercurrent,
step 1 and 2

(2 - 150)% of IBase

1.0% of Ir for I<Ir


1.0% of I for I>Ir

Definite time delay

(0.00 - 6000.00) s

0.5% 10 ms

Operate time start


overcurrent

25 ms typically at 0 to 2 x Iset

Reset time start


overcurrent

25 ms typically at 2 to 0 x Iset

Operate time start


undercurrent

25 ms typically at 2 to 0 x Iset

Reset time start


undercurrent

25 ms typically at 0 to 2 x Iset

See table 722 and


table 723

Parameter ranges for customer defined


characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0

See table 722 and table 723

Voltage level where


voltage memory
takes over

(0.0 - 5.0)% of UBase

0.5% of Ur

Start overvoltage,
step 1 and 2

(2.0 - 200.0)% of UBase

0.5% of Ur for U<Ur


0.5% of U for U>Ur

Start undervoltage,
step 1 and 2

(2.0 - 150.0)% of UBase

0.5% of Ur for U<Ur


0.5% of U for U>Ur

Operate time, start


overvoltage

25 ms typically at 0 to 2 x Uset

Reset time, start


overvoltage

25 ms typically at 2 to 0 x Uset

Operate time start


undervoltage

25 ms typically 2 to 0 x Uset

Table continues on next page


533
Technical reference manual

Section 10
Multipurpose protection
Function

1MRK 505 222-UEN B

Range or value

Accuracy

Reset time start


undervoltage

25 ms typically at 0 to 2 x Uset

High and low voltage


limit, voltage
dependent operation

(1.0 - 200.0)% of UBase

1.0% of Ur for U<Ur


1.0% of U for U>Ur

Directional function

Settable: NonDir, forward and reverse

Relay characteristic
angle

(-180 to +180) degrees

2.0 degrees

Relay operate angle

(1 to 90) degrees

2.0 degrees

Reset ratio,
overcurrent

> 95%

Reset ratio,
undercurrent

< 105%

Reset ratio,
overvoltage

> 95%

Reset ratio,
undervoltage

< 105%

Critical impulse time

10 ms typically at 0 to 2 x Iset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 2 to 0 x Iset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 0 to 2 x Uset

Impulse margin time

15 ms typically

Critical impulse time

10 ms typically at 2 to 0 x Uset

Impulse margin time

15 ms typically

Overcurrent:

Undercurrent:

Overvoltage:

Undervoltage:

534
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

Section 11

Secondary system supervision

About this chapter


This chapter describes functions like Current circuit supervision and Fuse failure
supervision. The way the functions work, their setting parameters, function blocks,
input and output signals and technical data are included for each function.

11.1

Current circuit supervision CCSRDIF


Function description
Current circuit supervision

11.1.1

IEC 61850
identification
CCSRDIF

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
87

Introduction
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negativesequence current functions.
It must be remembered that a blocking of protection functions at an occurrence of
open CT circuit will mean that the situation will remain and extremely high
voltages will stress the secondary circuit.
Current circuit supervision (CCSRDIF) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to
block protection functions expected to give unwanted tripping.

11.1.2

Principle of operation
Current circuit supervision CCSRDIF compares the absolute value of the vectorial
sum of the three phase currents |Iphase| and the numerical value of the residual
current |Iref| from another current transformer set, see figure 299.
The FAIL output will be set to a logical one when the following criteria are fulfilled:

535
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

The numerical value of the difference |Iphase| |Iref| is higher than 80% of
the numerical value of the sum |Iphase| + |Iref|.
The numerical value of the current |Iphase| |Iref| is equal to or higher than
the set operate value IMinOp.
No phase current has exceeded Ip>Block during the last 10 ms.
CCSRDIF is enabled by setting Operation = On.

The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM
will be issued. In this case the FAIL and ALARM will remain activated 1 s after
the AND-gate resets. This prevents unwanted resetting of the blocking function
when phase current supervision element(s) operate, for example, during a fault.

IEC05000463 V1 EN

Figure 299:

Simplified logic diagram for Current circuit supervision CCSRDIF

The operate characteristic is percentage restrained, see figure 300.

536
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

| I phase | - | I ref |

Slope = 1

Slope = 0.8

Operation
area

I MinOp
| I phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN

Figure 300:

Operate characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 2.

11.1.3

Function block
CCSRDIF
I3P*
IREF*
BLOCK

FAIL
ALARM

IEC05000389-2-en.vsd
IEC05000389 V2 EN

Figure 301:

11.1.4

CCSRDIF function block

Input and output signals


Table 306:
Name

CCSRDIF Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for three phase current input

IREF

GROUP
SIGNAL

TBD

BLOCK

BOOLEAN

Block of function

537
Technical reference manual

Section 11
Secondary system supervision

Table 307:

1MRK 505 222-UEN B

CCSRDIF Output signals

Name

11.1.5
Table 308:
Name

Type

Description

FAIL

BOOLEAN

Detection of current circuit failure

ALARM

BOOLEAN

Alarm for current circuit failure

Setting parameters
CCSRDIF Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

IBase value for current level detectors

IMinOp

5 - 200

%IB

20

Minimum operate current differential


level in % of IBase

Table 309:
Name
Ip>Block

11.1.6

CCSRDIF Group settings (advanced)


Values (Range)
5 - 500

Unit

Step

%IB

150

Description
Block of the function at high phase
current, in % of IBase

CCSRDIF technical data

Function

Range or value

Accuracy

Operate current

(5-200)% of Ir

10.0% of Ir at I Ir
10.0% of I at I > Ir

Block current

(5-500)% of Ir

5.0% of Ir at I Ir
5.0% of I at I > Ir

Fuse failure supervision SDDRFUF


Function description
Fuse failure supervision

11.2.1

Default

Technical data
Table 310:

11.2

IEC 61850
identification
SDDRFUF

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage

538
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

transformer and the IED in order to avoid unwanted operations that otherwise
might occur.
The fuse failure supervision function basically has three different algorithms,
negative sequence and zero sequence based algorithms and an additional delta
voltage and delta current algorithm.
The negative sequence detection algorithm is recommended for IEDs used in
isolated or high-impedance earthed networks. It is based on the negative-sequence
measuring quantities, a high value of voltage 3U2 without the presence of the
negative-sequence current 3I2.
The zero sequence detection algorithm is recommended for IEDs used in directly
or low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3U0 without the presence of the residual current
3I0.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
modes makes it possible to choose different interaction possibilities between the
negative sequence and zero sequence based algorithm.
A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure,
which in practice is more associated with voltage transformer switching during
station operations.

11.2.2

Principle of operation

11.2.2.1

Zero and negative sequence detection


The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure 302:

the zero-sequence voltage 3U0


the zero-sequence current 3I0
the negative sequence current 3I2
the negative sequence voltage 3U2

The measured signals are compared with their respective set values 3U0< and
3I0>, 3U2< and 3I2>.
The function enable the internal signal FuseFailDetZeroSeq if the measured zerosequence voltage is higher than the set value 3U0> and the measured zerosequence current is below the set value 3I0<.

539
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

The function enable the internal signal FuseFailDetNegSeq if the measured


negative sequence voltage is higher than the set value 3U2> and the measured
negative sequence current is below the set value 3I2<.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Sequence Detection
3I0<

CurrZeroSeq

IL1

Zero
sequence
filter

IL2

3I0
a
b

a>b

100 ms
t

3I2

Negative
sequence
filter

IL3

a
b

3I2<

CurrNegSeq

a>b

100 ms
t

AND

AND

3U0>

FuseFailDetZeroSeq

FuseFailDetNegSeq
VoltZeroSeq

UL1

Zero
sequence
filter

UL2

Negative
sequence
filter

UL3

a
b

3U0

a>b
VoltNegSeq

a
b

3U2

a>b

3U2>

IEC10000036-1-en.vsd
IEC10000036 V1 EN

Figure 302:

Simplified logic diagram for sequence detection part

The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local
HMI and monitoring tool in PCM600.

Input and output signals

The output signals 3PH, BLKU and BLKZ can be blocked in the following conditions:

The input BLOCK is activated


The input BLKTRIP is activated at the same time as the internal signal
fufailStarted is not present
The operation mode selector OpMode is set to Off.
The IED is in TEST status (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED itself in order to receive a block command from

540
Technical reference manual

1MRK 505 222-UEN B

Section 11
Secondary system supervision

internal functions. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The input BLKSP is intended to be connected to the trip output at any of the
protection functions included in the IED. When activated for more than 20 ms, the
operation of the fuse failure is blocked during a fixed time of 100 ms. The aim is to
increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-out time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode selector. The additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of
voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function is not affected by the
position of the line disconnector since there will be no line currents that can cause
malfunction of the distance protection. If DISCPOS=0 it signifies that the line is
connected to the system and when the DISCPOS=1 it signifies that the line is
disconnected from the system and the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check and so on) except for the impedance
protection.
The function output BLKZ shall be used for blocking the impedance protection
function.

541
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

Fuse failure detection


Main logic
TEST
TEST ACTIVE

AND

BlocFuse = Yes
BLOCK

intBlock

OR
20 ms
t

BLKTRIP
AND

100 ms
t

All UL < USealIn<


OR

AND

AND

AND

SealIn = On

3PH

AND
Any UL < UsealIn<
FuseFailDetDUDI
AND

OpDUDI = On

OR

5s
t

FuseFailDetZeroSeq
AND

AND
FuseFailDetNegSeq
AND
UNsINs

OR

UZsIZs
UZsIZs OR UNsINs

OpMode

CurrZeroSeq
CurrNegSeq

UZsIZs AND UNsINs


OptimZsNs
a
b

OR

OR

AND

a>b

AND
200 ms
t

DeadLineDet1Ph

AND
150 ms
t

MCBOP

All UL > UsealIn<

60 sec
t

VoltZeroSeq
VoltNegSeq

OR

OR

OR

OR

AND

AND

BLKZ

BLKU

AND
5 sec
t

AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-1-en.vsd
IEC10000033 V1 EN

Figure 303:

Simplified logic diagram for main logic of Fuse failure function

542
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

11.2.2.2

Delta current and delta voltage detection


A simplified diagram for the functionality is found in figure 304. The calculation of
the change is based on vector change which means that it detects both amplitude
and phase angle changes. The calculated delta quantities are compared with their
respective set values DI< and DU> and the algorithm, detects a fuse failure if a
sufficient change in voltage without a sufficient change in current is detected in
each phase separately. The following quantities are calculated in all three phases:

The change in voltage DU


The change in current DI

The internal FuseFailDetDUDI signal is activated if the following conditions are


fulfilled for a phase:

The magnitude of the phase-ground voltage has been above UPh> for more
than 1.5 cycle
The magnitude of DU is higher than the corresponding setting DU>
The magnitude of DI is below the setting DI>

and at least one of the following conditions are fulfilled:

The magnitude of the phase current in the same phase is higher than the setting
IPh>
The circuit breaker is closed (CBCLOSED = True)

The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used
to reduce the risk of false fuse failure detection. If the current on the protected line
is low, a voltage drop in the system (not caused by fuse failure) is not by certain
followed by current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase
at the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way
only the first criterion can activate the delta function.

543
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

DUDI Detection
DUDI detection Phase 1
IL1

One cycle
delay
|DI|

a
b

DI<
UL1

a>b

One cycle
delay
|DU|

a
b

DU>
a
b

UPh>
IL2

a>b

20 ms
t

a>b

AND

1.5 cycle
t

DUDI detection Phase 2

UL2

Same logic as for phase 1

IL3

DUDI detection Phase 3

UL3

Same logic as for phase 1

UL1

a
b

IL1
IPh>

a
b

a<b

a>b

AND

CBCLOSED
UL2

a
b

IL2

AND

a
b

a
b

IL3

a
b

OR

AND

a<b

a>b

AND

AND
UL3

OR

OR

OR

AND

a<b

a>b

AND

AND

OR

OR

AND
OR

FuseFailDetDUDI

IEC10000034-1-en.vsd
IEC10000034 V1 EN

Figure 304:

Simplified logic diagram for DU/DI detection part

544
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

11.2.2.3

Dead line detection


A simplified diagram for the functionality is found in figure 305. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values UDLD< and IDLD<. If at least one phase is considered to
be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated.
If all three phases are considered to be dead the output DLD3PH is activated
Dead Line Detection
IL1

a
b

IL2

a
b

IL3

a
b

a<b

AllCurrLow

AND
a<b
a<b

IDLD<
UL1

DeadLineDet1Ph
a
b

UL2

a
b

UL3

a
b

a<b
a<b

AND
OR

AND

AND
AND

a<b

DLD1PH

AND

AND

DLD3PH

UDLD<
intBlock

IEC10000035-1-en.vsd
IEC10000035 V1 EN

Figure 305:

11.2.2.4

Simplified logic diagram for Dead Line detection part

Main logic
A simplified diagram for the functionality is found in figure 306. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting
parameter Operation to On or Off.
For increased flexibility and adaptation to system requirements an operation mode
selector, OpMode, has been introduced to make it possible to select different
operating modes for the negative and zero sequence based algorithms. The
different operation modes are:

Off; The negative and zero sequence function is switched off


UNsINs; Negative sequence is selected
UZsIZs; Zero sequence is selected

545
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

UZsIZs OR UNsINs; Both negative and zero sequence is activated and working
in parallel in an OR-condition
UZsIZs AND UNsINs; Both negative and zero sequence is activated and
working in series (AND-condition for operation)
OptimZsNs; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be
activated)

The delta function can be activated by setting the parameter OpDUDI to On. When
selected it operates in parallel with the sequence based algorithms.
As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,
FuseFailDetNegSeq or FuseFailDetDUDI, and the specific functionality is
released, the function will activate the output signal BLKU. The output signal
BLKZ will be activated as well if not the internal dead phase detection,
DeadLineDet1Ph, is activated at the same time. The output BLKU can be used for
blocking voltage related measuring functions (under voltage protection, synchrocheck, and so on). For blocking of impedance protection functions output BLKZ
shall be used.
If the fuse failure situation is present for more than 5 seconds and the setting
parameter SealIn is set to On it will be sealed in as long as at least one phase
voltages is below the set value USealIn<. This will keep the BLKU and BLKZ
signals activated as long as any phase voltage is below the set value USealIn<. If
all three phase voltages drop below the set value USealIn< and the setting
parameter SealIn is set to On also the output signal 3PH will be activated. The
signals 3PH, BLKU and BLKZ signals will now be active as long as any phase
voltage is below the set value USealIn<.
If SealIn is set to On fuse failure condition is stored in the non volatile memory in
the IED. At start-up (due to auxiliary power interruption or re-start due to
configuration change) the IED checks the stored value in its non volatile memory
and re-establishes the conditions present before the shut down. All phase voltages
must became above USealIn< before fuse failure is de-activated and inhibits the
block of different protection functions.
The output signal BLKU will also be active if all phase voltages have been above
the setting USealIn< for more than 60 seconds, the zero or negative sequence
voltage has been above the set value 3U0> and 3U2> for more than 5 seconds, all
phase currents are below the setting IDLD< (operate level for dead line detection)
and the circuit breaker is closed (input CBCLOSED is activated).
The input signal MCBOP is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKU and BLKZ in
order to block all the voltage related functions when the MCB is open independent
of the setting of OpMode or OpDUDI. An additional drop-out timer of 150 ms
prolongs the presence of MCBOP signal to prevent the unwanted operation of

546
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

voltage dependent function due to non simultaneous closing of the main contacts of
the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function does not have to be
affected since there will be no line currents that can cause malfunction of the
distance protection.
The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions
occur:

The operation mode selector OpMode is set to Off


The input BLOCK is activated
The input BLKTRIP is activated at the same time as no fuse failure indication
is present
The IED is in TEST status (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockFUSE=Yes)

The input BLOCK is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to
other internal functions of the IED. Through OR gate it can be connected to both
binary inputs and internal function outputs.
The input BLKTRIP is intended to be connected to the trip output of any of the
protection functions included in the IED and/or trip from external equipments via
binary inputs. When activated for more than 20 ms without any fuse fail detected,
the operation of the fuse failure is blocked during a fixed time of 100 ms. The aim
is to increase the security against unwanted operations during the opening of the
breaker, which might cause unbalance conditions for which the fuse failure might
operate.

547
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

Fuse failure detection


Main logic
TEST
TEST ACTIVE

AND

BlocFuse = Yes
BLOCK

intBlock

OR
20 ms
t

BLKTRIP
AND

100 ms
t

All UL < USealIn<


OR

AND

AND

AND

SealIn = On

3PH

AND
Any UL < UsealIn<
FuseFailDetDUDI
AND

OpDUDI = On

OR

5s
t

FuseFailDetZeroSeq
AND

AND
FuseFailDetNegSeq
AND
UNsINs

OR

UZsIZs
UZsIZs OR UNsINs

OpMode

CurrZeroSeq
CurrNegSeq

UZsIZs AND UNsINs


OptimZsNs
a
b

OR

OR

AND

a>b

AND
200 ms
t

DeadLineDet1Ph

AND
150 ms
t

MCBOP

All UL > UsealIn<

60 sec
t

VoltZeroSeq
VoltNegSeq

OR

OR

OR

OR

AND

AND

BLKZ

BLKU

AND
5 sec
t

AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-1-en.vsd
IEC10000033 V1 EN

Figure 306:

Simplified logic diagram for fuse failure supervision function, Main


logic

548
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

11.2.3

Function block
SDDRFUF
I3P*
U3P*
BLOCK
CBCLOSED
MCBOP
DISCPOS
BLKTRIP

BLKZ
BLKU
3PH
DLD1PH
DLD3PH

IEC05000700-2-en.vsd
IEC05000700 V3 EN

Figure 307:

11.2.4

SDDRFUF function block

Input and output signals


Table 311:

SDDRFUF Input signals

Name

Type
GROUP
SIGNAL

Current connection

U3P

GROUP
SIGNAL

Voltage connection

BLOCK

BOOLEAN

Block of function

CBCLOSED

BOOLEAN

Active when circuit breaker is closed

MCBOP

BOOLEAN

Active when external MCB opens protected


voltage circuit

DISCPOS

BOOLEAN

Active when line disconnector is open

BLKTRIP

BOOLEAN

Blocks operation of function when active

SDDRFUF Output signals

Name

Table 313:

Description

I3P

Table 312:

11.2.5

Default

Type

Description

BLKZ

BOOLEAN

Start of current and voltage controlled function

BLKU

BOOLEAN

General start of function

3PH

BOOLEAN

Three-phase start of function

DLD1PH

BOOLEAN

Dead line condition in at least one phase

DLD3PH

BOOLEAN

Dead line condition in all three phases

Setting parameters
SDDRFUF Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

IBase

1 - 99999

3000

Base current

UBase

0.05 - 2000.00

kV

0.05

400.00

Base voltage

Table continues on next page


549
Technical reference manual

Section 11
Secondary system supervision
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

OpMode

Off
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs

UZsIZs

Operating mode selection

3U0>

1 - 100

%UB

30

Operate level of residual overvoltage


element in % of UBase

3I0<

1 - 100

%IB

10

Operate level of residual undercurrent


element in % of IBase

3U2>

1 - 100

%UB

30

Operate level of neg seq overvoltage


element in % of UBase

3I2<

1 - 100

%IB

10

Operate level of neg seq undercurrent


element in % of IBase

OpDUDI

Off
On

Off

Operation of change based function Off/


On

DU>

1 - 100

%UB

60

Operate level of change in phase voltage


in % of UBase

DI<

1 - 100

%IB

15

Operate level of change in phase current


in % of IBase

UPh>

1 - 100

%UB

70

Operate level of phase voltage in % of


UBase

IPh>

1 - 100

%IB

10

Operate level of phase current in % of


IBase

SealIn

Off
On

On

Seal in functionality Off/On

USealln<

1 - 100

%UB

70

Operate level of seal-in phase voltage in


% of UBase

IDLD<

1 - 100

%IB

Operate level for open phase current


detection in % of IBase

UDLD<

1 - 100

%UB

60

Operate level for open phase voltage


detection in % of UBase

11.2.6

Technical data
Table 314:

SDDRFUF technical data

Function

Range or value

Accuracy

Operate voltage, zero sequence

(1-100)% of UBase

1.0% of Ur

Operate current, zero sequence

(1100)% of IBase

1.0% of Ir

Operate voltage, negative sequence

(1100)% of UBase

0.5% of Ur

Operate current, negative sequence

(1100)% of IBase

1.0% of Ir

Operate voltage change level

(1100)% of UBase

5.0% of Ur

Operate current change level

(1100)% of IBase

5.0% of Ir

Operate phase voltage

(1-100)% of UBase

0.5% of Ur

Operate phase current

(1-100)% of IBase

1.0% of Ir

Table continues on next page


550
Technical reference manual

Section 11
Secondary system supervision

1MRK 505 222-UEN B

Function

Range or value

Accuracy

Operate phase dead line voltage

(1-100)% of UBase

0.5% of Ur

Operate phase dead line current

(1-100)% of IBase

1.0% of Ir

Operate time, start function

25 ms typically at 1 to 0 Ubase

Reset time, start function

35 ms typically at 0 to 1 Ubase

551
Technical reference manual

552

Section 12
Control

1MRK 505 222-UEN B

Section 12

Control

About this chapter


This chapter describes the control functions. The way the functions work, their
setting parameters, function blocks, input and output signals and technical data are
included for each function.

12.1

Synchrocheck, energizing check, and synchronizing


SESRSYN
Function description
Synchrocheck, energizing check, and
synchronizing

IEC 61850
identification

IEC 60617
identification

SESRSYN

ANSI/IEEE C37.2
device number
25

sc/vc
SYMBOL-M V1 EN

12.1.1

Introduction
The Synchronizing function allows closing of asynchronous networks at the correct
moment including the breaker closing time, which improves the network stability.
Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks
that the voltages on both sides of the circuit breaker are in synchronism, or with at
least one side dead to ensure that closing can be done safely.
SESRSYN function includes a built-in voltage selection scheme for double bus and
1 breaker or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and
can have different settings.
For systems which are running asynchronous a synchronizing function is provided.
The main purpose of the synchronizing function is to provide controlled closing of
circuit breakers when two asynchronous systems are going to be connected. It is
used for slip frequencies that are larger than those for synchrocheck and lower than
a set maximum level for the synchronizing function.

553
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.1.2

Principle of operation

12.1.2.1

Basic functionality
The synchrocheck function measures the conditions across the circuit breaker and
compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares
them to both high and low threshold detectors. The output is given only when the
actual measured quantities match the set conditions.
The synchronizing function measures the conditions across the circuit breaker, and
also determines the angle change occurring during the closing delay of the circuit
breaker, from the measured slip frequency. The output is given only when all
measured conditions are simultaneously within their set limits. The issue of the
output is timed to give closure at the optimal time including the time for the circuit
breaker and the closing circuit.
For single circuit breaker and 1 breaker circuit breaker arrangements, the
SESRSYN function blocks have the capability to make the necessary voltage
selection. For single circuit breaker arrangements, selection of the correct voltage
is made using auxiliary contacts of the bus disconnectors. For 1 breaker circuit
breaker arrangements, correct voltage selection is made using auxiliary contacts of
the bus disconnectors as well as the circuit breakers.
The internal logic for each function block as well as, the input and outputs, and the
setting parameters with default setting and setting ranges is described in this
document. For application related information, please refer to the application manual.

12.1.2.2

Logic diagrams
Logic diagrams

The logic diagrams that follow illustrate the main principles of the synchronizing
function components such as Synchrocheck, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.

Synchrocheck

The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.
When the function is set to OperationSC = On, the measuring will start.
The function will compare the bus and line voltage values with the set values for
UHighBusSC and UHighLineSC.

554
Technical reference manual

1MRK 505 222-UEN B

Section 12
Control

If both sides are higher than the set values, the measured values are compared with
the set values for acceptable frequency, phase angle and voltage difference:
FreqDiff, PhaseDiff and UDiff. If a compensation factor is set due to the use of
different voltages on the bus and line, the factor is deducted from the line voltage
before the comparison of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The
frequency difference between the bus frequency and the line frequency is measured
and may not exceed the set value.
Two sets of settings for frequency difference and phase angle difference are
available and used for the manual closing and autoreclose functions respectively, as
required.
The inputs BLOCK and BLKSC are available for total block of the complete
SESRSYN function and block of the Synchrocheck function respectively. Input
TSTSC will allow testing of the function where the fulfilled conditions are
connected to a separate test output.
The outputs MANSYOK and AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK and AUTOSYOK conditions.
A number of outputs are available as information about fulfilled checking
conditions. UOKSC shows that the voltages are high, UDIFFSC, FRDIFFA,
FRDIFFM, PHDIFFA, PHDIFFM shows when the voltage difference, frequency
difference and phase angle difference conditions are met.
Output INADVCLS, inadvertent circuit breaker closing, indicate that the circuit
breaker has been closed by some other equipment or function than SESRSYN. The
output is activated, if the voltage condition is fulfilled at the same time the phase
angle difference between bus and line is suddenly changed from being larger than
60 degrees to smaller than 5 degrees.

555
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Note! Similar logic for Manual Synchrocheck.


OperationSC = On
AND

AND

TSTAUTSY

TSTSC
BLKSC
BLOCK

AND
OR
AND

AUTOSYOK

0-60 s
t

AND

tSCA

UDiffSC
AND

50 ms
t

UHighBusSC
UOKSC

AND

UHighLineSC

FreqDiffA

PhaseDiffA

UDIFFSC
FRDIFFA
PHDIFFA
UDIFFME

voltageDifferenceValue

FRDIFFME

frequencyDifferenceValue

PHDIFFME

phaseAngleDifferenceValue

PhDiff > 60

AND

32 ms
t

100 ms
AND

INADVCLS

PhDiff < 5

IEC07000114-3-en.vsd
IEC07000114 V3 EN

Figure 308:

Simplified logic diagram for the Synchrocheck function

Synchronizing

When the function is set to OperationSynch = On the measuring will be performed.


The function will compare the values for the bus and line voltage with the set
values for UHighBusSynch and UHighLineSynch, which is a supervision that the
voltages are both live. If both sides are higher than the set values the measured
values are compared with the set values for acceptable frequency, rate of change of
frequency, phase angle and voltage difference FreqDiffMax, FreqDiffMin and
UDiffSynch.
Measured frequencies between the settings for the maximum and minimum
frequency will initiate the measuring and the evaluation of the angle change to
allow operation to be sent in the right moment including the set tBreaker time.

556
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

There is a phase angle release internally to block any incorrect closing pulses. At
operation the SYNOK output will be activated with a pulse tClosePulse and the
function reset. The function will also reset if the synchronizing conditions are not
fulfilled within the set tMaxSynch time. This prevents that the functions are, by
mistake, maintained in operation for a long time, waiting for conditions to be fulfilled.
The inputs BLOCK and BLKSYNCH are available for total block of the complete
function respective of the synchronizing part. TSTSYNCH will allow testing of the
function where the fulfilled conditions are connected to a separate output.
SYN1
OPERATION SYNCH
OFF
ON
TEST MODE
OFF
ON
STARTSYN
AND

BLKSYNCH
OR

AND

S
R

UDiffSynch
50 ms

UHighBusSynch

AND

SYNOK

AND

UHighLineSynch

OR

FreqDiffMax

AND

FreqDiffMin

OR

FreqRateChange
fBus&fLine 5 Hz
PhaseDiff < 15 deg

SYNPROGR

AND
AND

TSTSYNOK

tClose
Pulse

tMax
Synch

SYNFAIL

PhaseDiff=closing angle

IEC06000636-2-en.vsd
IEC06000636 V2 EN

Figure 309:

Simplified logic diagram for the synchronizing function

Energizing check

Voltage values are measured in the IED centrally and are available for evaluation
by the Energizing check function.
The function measures voltages on the busbar and the line to verify whether they
are live or dead. This is done by comparing with the set values UHighBusEnerg
and ULowBusEnerg for bus energizing and UHighLineEnerg and ULowLineEnerg
for line energizing.
The frequency on both sides of the circuit breaker is also measured. The
frequencies must not deviate from the rated frequency more than +/-5Hz. The

557
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

frequency difference between the bus frequency and the line frequency is measured
and shall not exceed a set value.
The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse
supervision conditions are fulfilled. The output signal can be delayed
independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective
MENMODE, which for example, can be connected to a Binary to Integer function
block (B16I). Integers supplied shall be 1=off, 2=DLLB, 3=DBLL and 4= Both.
Not connected input with connection of INTZERO output from Fixed Signals
(FIXDSIGN) function block will mean that the setting is done from Parameter
Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.
The inputs BLOCK and BLKENERG are available for total block of the complete
SESRSYN function respective block of the Energizing check function.
TSTENERG will allow testing of the function where the fulfilled conditions are
connected to a separate test output.

Voltage selection

The voltage selection module including supervision of included voltage


transformer fuses for the different arrangements is a basic part of the SESRSYN
function and determines the parameters fed to the Synchronizing, Synchrocheck
and Energizing check functions. This includes the selection of the appropriate Line
and Bus voltages and fuse supervision.
The voltage selection type to be used is set with the parameter CBConfig.
If No voltage sel. is set the default voltages used will be ULine1 and UBus1. This
is also the case when external voltage selection is provided. Fuse failure
supervision for the used inputs must also be connected.
The voltage selection function, selected voltages, and fuse conditions are the
Synchronizing, Synchrocheck and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type
contacts to supply Disconnector Open and Closed positions but, it is also possible
to use an inverter for one of the positions.

Voltage selection for a single circuit breaker with double busbars

This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select
between bus 1 and bus 2 voltages. If the disconnector connected to bus 1 is closed
and the disconnector connected to bus 2 is opened the bus 1 voltage is used. All
other combinations use the bus 2 voltage. The Outputs B1SEL and B2SEL
respectively indicate the selected Bus voltage.

558
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The function checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1 and UB2OKUB2FF supervises the fuse for Bus 2. ULNOK and ULNFF supervises the fuse for
the Line voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively
be used dependent on the available signal. If a fuse-failure is detected in the
selected voltage source an output signal USELFAIL is set. This output signal is
true if the selected bus or line voltages have a fuse failure. This output as well as
the function can be blocked with the input signal BLOCK. The function logic
diagram is shown in figure 310.
B1QOPEN

B1SEL

AND

B1QCLD
B2QOPEN

B2SEL

AND

B2QCLD

AND

bus1Voltage

invalidSelection
busVoltage

bus2Voltage

UB1OK
UB1FF

OR

UB2OK
UB2FF

OR

ULN1OK
ULN1FF

OR

AND
OR

AND

selectedFuseOK

AND
AND

USELFAIL

BLOCK

en05000779.vsd
IEC05000779 V1 EN

Figure 310:

Logic diagram for the voltage selection function of a single circuit breaker with double busbars

Voltage selection for a 1 1/2 circuit breaker arrangement

Note that with 1 breaker schemes two Synchrocheck functions must be used in
the IED (three for two IEDs in a complete bay). Below, the scheme for one Bus
breaker and the Tie breakers is described.
This voltage selection function uses the binary inputs from the disconnectors and
circuit breakers auxiliary contacts to select the right voltage for the Synchrocheck
(Synchronism and Energizing check) function. For the bus circuit breaker one side

559
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

of the circuit breaker is connected to the busbar and the other side is connected
either to line 1, line 2 or the other busbar depending on the arrangement.
Inputs LN1QOPEN-LN1QCLD, B1QOPEN-B1QCLD, B2QOPEN-B2QCLD,
LN2QOPEN-LN2QCLD are inputs for the position of the Line disconnectors
respectively the Bus and Tie breakers. The Outputs LN1SEL, LN2SEL and B2SEL
will give indication of the selected Line voltage as a reference to the fixed Bus 1
voltage.
The fuse supervision is connected to ULNOK-ULNFF, and with alternative
Healthy or Failing fuse signals depending on what is available for each of fuse (MCB).
The tie circuit breaker is connected either to bus 1 or line 1 on one side and the
other side is connected either to bus 2 or line 2. Four different output combinations
are possible, bus to bus, bus to line, line to bus and line to line.

The line 1 voltage is selected if the line 1 disconnector is closed.


The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1
circuit breaker is closed.
The line 2 voltage is selected if the line 2 disconnector is closed.
The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2
Circuit breaker is closed.

The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2.
If a fuse-failure is detected in the selected voltage an output signal USELFAIL is
set. This output signal is true if the selected bus or line voltages have a fuse failure.
This output as well as the function can be blocked with the input signal BLOCK.
The function block diagram for the voltage selection of a bus circuit breaker is
shown in figure 311 and for the tie circuit breaker in figure 312

560
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

LN1QOPEN
LN1QCLD

LN1SEL

AND

B1QOPEN
B1QCLD

LN2SEL

AND

AND

LN2QCLD

AND

invalidSelection

AND
AND

B2QOPEN
B2QCLD

B2SEL

OR

LN2QOPEN

AND

line1Voltage

lineVoltage

line2Voltage
bus2Voltage
UB1OK
UB1FF

OR

UB2OK
UB2FF

OR

OR

ULN1OK
ULN1FF

OR

ULN2OK
ULN2FF

OR

AND

AND

AND

AND

selectedFuseOK
USELFAIL

AND

BLOCK

en05000780.vsd
IEC05000780 V1 EN

Figure 311:

Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement

561
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

LN1QOPEN
LN1QCLD

LN1SEL

AND

B1SEL

1
B1QOPEN
B1QCLD

AND

AND

AND

line1Voltage

busVoltage

bus1Voltage
LN2QOPEN
LN2QCLD

LN2SEL

AND

B2SEL

1
B2QOPEN
B2QCLD

AND

AND

AND

OR

line2Voltage

invalidSelection

lineVoltage

bus2Voltage
UB1OK
UB1FF
UB2OK
UB2FF

OR

AND
OR

OR

ULN1OK
ULN1FF

OR

ULN2OK
ULN2FF

OR

AND

AND

AND

AND

selectedFuseOK
USELFAIL

AND

BLOCK

en05000781.vsd
IEC05000781 V1 EN

Figure 312:

Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.

Fuse failure supervision

External fuse failure signals or signals from a tripped fuse switch/MCB are
connected to binary inputs that are configured to the inputs of SESRSYN functions
in the IED. Alternatively, the internal signals from fuse failure supervision can be
used when available. There are two alternative connection possibilities. Inputs
labelled OK must be connected if the available contact indicates that the voltage
circuit is healthy. Inputs labelled FF must be connected if the available contact
indicates that the voltage circuit is faulty.
562
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage
and the ULNOK and ULNFF inputs are related to the line voltage. Configure them
to the binary input or function outputs that indicate the status of the external fuse
failure of the busbar and line voltages. In the event of a fuse failure, the energizing
check function is blocked. The synchronizing and the synchrocheck function
requires full voltage on both sides and will be blocked automatically in the event of
fuse failures.

12.1.3

Function block
SESRSYN
U3PBB1*
SYNOK
U3PBB2*
AUTOSYOK
U3PLN1*
AUTOENOK
U3PLN2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
B1QOPEN
TSTENOK
B1QCLD
USELFAIL
B2QOPEN
B1SEL
B2QCLD
B2SEL
LN1QOPEN
LN1SEL
LN1QCLD
LN2SEL
LN2QOPEN
SYNPROGR
LN2QCLD
SYNFAIL
UB1OK
UOKSYN
UB1FF
UDIFFSYN
UB2OK
FRDIFSYN
UB2FF
FRDIFFOK
ULN1OK
FRDERIVA
ULN1FF
UOKSC
ULN2OK
UDIFFSC
ULN2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
UDIFFME
MENMODE
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
IEC10000046-1-en.vsd
IEC10000046 V1 EN

Figure 313:

12.1.4

SESRSYN function block

Input and output signals


Table 315:
Name

SESRSYN Input signals


Type

Default

Description

U3PBB1

GROUP
SIGNAL

Group signal for phase to earth voltage input L1,


busbar 1

U3PBB2

GROUP
SIGNAL

Group signal for phase to earth voltage input L1,


busbar 2

U3PLN1

GROUP
SIGNAL

Group signal for phase to earth voltage input L1,


line 1

Table continues on next page


563
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

U3PLN2

GROUP
SIGNAL

Group signal for phase to earth voltage input L1,


line 2

BLOCK

BOOLEAN

General block

BLKSYNCH

BOOLEAN

Block synchronizing

BLKSC

BOOLEAN

Block synchro check

BLKENERG

BOOLEAN

Block energizing check

B1QOPEN

BOOLEAN

Open status for CB or disconnector connected to


bus1

B1QCLD

BOOLEAN

Close status for CB or disconnector connected to


bus1

B2QOPEN

BOOLEAN

Open status for CB or disconnector connected to


bus2

B2QCLD

BOOLEAN

Close status for CB or disconnector connected to


bus2

LN1QOPEN

BOOLEAN

Open status for CB or disconnector connected to


line1

LN1QCLD

BOOLEAN

Close status for CB or disconnector connected to


line1

LN2QOPEN

BOOLEAN

Open status for CB or disconnector connected to


line2

LN2QCLD

BOOLEAN

Close status for CB or disconnector connected to


line2

UB1OK

BOOLEAN

Bus1 voltage transformer OK

UB1FF

BOOLEAN

Bus1 voltage transformer fuse failure

UB2OK

BOOLEAN

Bus2 voltage transformer OK

UB2FF

BOOLEAN

Bus2 voltage transformer fuse failure

ULN1OK

BOOLEAN

Line1 voltage transformer OK

ULN1FF

BOOLEAN

Line1 voltage transformer fuse failure

ULN2OK

BOOLEAN

Line2 voltage transformer OK

ULN2FF

BOOLEAN

Line2 voltage transformer fuse failure

STARTSYN

BOOLEAN

Start synchronizing

TSTSYNCH

BOOLEAN

Set synchronizing in test mode

TSTSC

BOOLEAN

Set synchro check in test mode

TSTENERG

BOOLEAN

Set energizing check in test mode

AENMODE

INTEGER

Input for setting of automatic energizing mode

MENMODE

INTEGER

Input for setting of manual energizing mode

Table 316:
Name

SESRSYN Output signals


Type

Description

SYNOK

BOOLEAN

Synchronizing OK output

AUTOSYOK

BOOLEAN

Auto synchro check OK

AUTOENOK

BOOLEAN

Automatic energizing check OK

Table continues on next page

564
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Description

MANSYOK

BOOLEAN

Manual synchro check OK

MANENOK

BOOLEAN

Manual energizing check OK

TSTSYNOK

BOOLEAN

Synchronizing OK test output

TSTAUTSY

BOOLEAN

Auto synchro check OK test output

TSTMANSY

BOOLEAN

Manual synchro check OK test output

TSTENOK

BOOLEAN

Energizing check OK test output

USELFAIL

BOOLEAN

Selected voltage transformer fuse failed

B1SEL

BOOLEAN

Bus1 selected

B2SEL

BOOLEAN

Bus2 selected

LN1SEL

BOOLEAN

Line1 selected

LN2SEL

BOOLEAN

Line2 selected

SYNPROGR

BOOLEAN

Synchronizing in progress

SYNFAIL

BOOLEAN

Synchronizing failed

UOKSYN

BOOLEAN

Voltage amplitudes for synchronizing above set


limits

UDIFFSYN

BOOLEAN

Voltage difference out of limit for synchronizing

FRDIFSYN

BOOLEAN

Frequency difference out of limit for synchronizing

FRDIFFOK

BOOLEAN

Frequency difference in band for synchronizing

FRDERIVA

BOOLEAN

Frequency derivative out of limit for synchronizing

UOKSC

BOOLEAN

Voltage amplitudes above set limits

UDIFFSC

BOOLEAN

Voltage difference out of limit

FRDIFFA

BOOLEAN

Frequency difference out of limit for Auto operation

PHDIFFA

BOOLEAN

Phase angle difference out of limit for Auto


operation

FRDIFFM

BOOLEAN

Frequency difference out of limit for Manual


operation

PHDIFFM

BOOLEAN

Phase angle difference out of limit for Manual


Operation

INADVCLS

BOOLEAN

Inadvertent circuit breaker closing

UDIFFME

REAL

Calculated difference of voltage in p.u

FRDIFFME

REAL

Calculated difference of frequency

PHDIFFME

REAL

Calculated difference of phase angle

UBUS

REAL

Bus voltage

ULINE

REAL

Line voltage

MODEAEN

INTEGER

Selected mode for automatic energizing

MODEMEN

INTEGER

Selected mode for manual energizing

565
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.1.5
Table 317:
Name

Setting parameters
SESRSYN Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

CBConfig

No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB

No voltage sel.

Select CB configuration

UBaseBus

0.001 - 9999.999

kV

0.001

400.000

Base value for busbar voltage settings

UBaseLine

0.001 - 9999.999

kV

0.001

400.000

Base value for line voltage settings

PhaseShift

-180 - 180

Deg

Phase shift

URatio

0.040 - 25.000

0.001

1.000

Voltage ratio

OperationSynch

Off
On

Off

Operation for synchronizing function Off/


On

UHighBusSynch

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for synchronizing


in % of UBaseBus

UHighLineSynch

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for synchronizing


in % of UBaseLine

UDiffSynch

0.02 - 0.50

pu

0.01

0.10

Voltage difference limit for synchronizing


in p.u

FreqDiffMin

0.003 - 0.250

Hz

0.001

0.010

Minimum frequency difference limit for


synchronizing

FreqDiffMax

0.050 - 0.250

Hz

0.001

0.200

Maximum frequency difference limit for


synchronizing

FreqRateChange

0.000 - 0.500

Hz/s

0.001

0.300

Maximum allowed frequency rate of


change

tBreaker

0.000 - 60.000

0.001

0.080

Closing time of the breaker

tClosePulse

0.050 - 60.000

0.001

0.200

Breaker closing pulse duration

tMaxSynch

0.00 - 6000.00

0.01

600.00

Resets synch if no close has been made


before set time

tMinSynch

0.000 - 60.000

0.001

2.000

Minimum time to accept synchronizing


conditions

OperationSC

Off
On

On

Operation for synchronism check


function Off/On

UHighBusSC

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for synchrocheck


in % of UBaseBus

UHighLineSC

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for synchrocheck


in % of UBaseLine

UDiffSC

0.02 - 0.50

pu

0.01

0.15

Voltage difference limit in p.u

FreqDiffA

0.003 - 1.000

Hz

0.001

0.010

Frequency difference limit between bus


and line Auto

FreqDiffM

0.003 - 1.000

Hz

0.001

0.010

Frequency difference limit between bus


and line Manual

PhaseDiffA

5.0 - 90.0

Deg

1.0

25.0

Phase angle difference limit between


bus and line Auto

Table continues on next page

566
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Step

Default

PhaseDiffM

Values (Range)
5.0 - 90.0

Unit
Deg

1.0

25.0

Description
Phase angle difference limit between
bus and line Manual

tSCA

0.000 - 60.000

0.001

0.100

Time delay output for synchrocheck Auto

tSCM

0.000 - 60.000

0.001

0.100

Time delay output for synchrocheck


Manual

AutoEnerg

Off
DLLB
DBLL
Both

DBLL

Automatic energizing check mode

ManEnerg

Off
DLLB
DBLL
Both

Both

Manual energizing check mode

ManEnergDBDL

Off
On

Off

Manual dead bus, dead line energizing

UHighBusEnerg

50.0 - 120.0

%UBB

1.0

80.0

Voltage high limit bus for energizing


check in % of UBaseBus

UHighLineEnerg

50.0 - 120.0

%UBL

1.0

80.0

Voltage high limit line for energizing


check in % of UBaseLine

ULowBusEnerg

10.0 - 80.0

%UBB

1.0

40.0

Voltage low limit bus for energizing


check in % of UBaseBus

ULowLineEnerg

10.0 - 80.0

%UBL

1.0

40.0

Voltage low limit line for energizing


check in % of UBaseLine

UMaxEnerg

50.0 - 180.0

%UB

1.0

115.0

Maximum voltage for energizing in % of


UBase, Line and/or Bus

tAutoEnerg

0.000 - 60.000

0.001

0.100

Time delay for automatic energizing


check

tManEnerg

0.000 - 60.000

0.001

0.100

Time delay for manual energizing check

567
Technical reference manual

Section 12
Control

Table 318:
Name

1MRK 505 222-UEN B

SESRSYN Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

SelPhaseBus1

Phase L1 for
busbar1
Phase L2 for
busbar1
Phase L3 for
busbar1
Phase L1L2 for
busbar1
Phase L2L3 for
busbar1
Phase L3L1 for
busbar1
Pos. sequence for
busbar1

Phase L1 for
busbar1

Select phase for busbar1

SelPhaseBus2

Phase L1 for
busbar2
Phase L2 for
busbar2
Phase L3 for
busbar2
Phase L1L2 for
busbar2
Phase L2L3 for
busbar2
Phase L3L1 for
busbar2
Pos. sequence for
busbar2

Phase L1 for
busbar2

Select phase for busbar2

SelPhaseLine1

Phase L1 for line1


Phase L2 for line1
Phase L3 for line1
Phase L1L2 for
line1
Phase L2L3 for
line1
Phase L3L1 for
line1
Pos. sequence for
line1

Phase L1 for line1

Select phase for line1

SelPhaseLine2

Phase L1 for line2


Phase L2 for line2
Phase L3 for line2
Phase L1L2 for
line2
Phase L2L3 for
line2
Phase L3L1 for
line2
Pos. sequence for
line2

Phase L1 for line2

Select phase for line2

568
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.1.6

Technical data
Table 319:

SESRSYN technical data

Function

12.2

Range or value

Accuracy

Phase shift, jline - jbus

(-180 to 180) degrees

Voltage ratio, Ubus/Uline

(0.40-25.000) % of UBaseBus

Voltage high limit for


synchronizing and
synchrocheck

(50.0-120.0)% of UBaseBus and


UBaseLIne

0.5% of Ur at U Ur
0.5% of U at U >Ur

Reset ratio, synchrocheck

> 95%

Frequency difference limit


between bus and line

(0.003-1.000) Hz

2.0 mHz

Phase angle difference limit


between bus and line

(5.0-90.0) degrees

2.0 degrees

Voltage difference limit


between bus and line

(0.02-0.5) p.u

0.5% of Ur

Time delay output for


synchrocheck

(0.000-60.000) s

0.5% 10 ms

Voltage high limit for


energizing check

(50.0-120.0)% of UBaseBus and


UBaseLIne

0.5% of Ur at U Ur
0.5% of U at U >Ur

Reset ratio, voltage high limit

> 95%

Voltage low limit for


energizing check

(10.0-80.0)% of UBase

0.5% of Ur

Reset ratio, voltage low limit

< 105%

Maximum voltage for


energizing

(50.0-180.0)% of UBaseBus and/


or UBaseLIne

0.5% of Ur at U Ur
0.5% of U at U >Ur

Time delay for energizing


check

(0.000-60.000) s

0.5% 10 ms

Operate time for


synchrocheck function

160 ms typically

Operate time for energizing


function

80 ms typically

and UBaseLIne

Autorecloser SMBRREC
Function Description
Autorecloser

IEC 61850
identification

IEC 60617
identification

SMBRREC

ANSI/IEEE C37.2
device number
79

O->I
SYMBOL-L V1 EN

569
Technical reference manual

Section 12
Control
12.2.1

1MRK 505 222-UEN B

Introduction
The autorecloser (SMBRREC) function provides high-speed and/or delayed autoreclosing for single or multi-breaker applications.
Up to five reclosing attempts can be included by parameter setting. The first
attempt can be single-, two and/or three phase for single phase or multi-phase faults
respectively.
Multiple autoreclosing functions are provided for multi-breaker arrangements. A
priority circuit allows one circuit breaker to close first and the second will only
close if the fault proved to be transient.
Each autoreclosing function can be configured to co-operate with a synchrocheck
function.

12.2.2

Principle of operation

12.2.2.1

Logic Diagrams
The logic diagrams below illustrate the principles applicable in the understanding
of the functionality.

12.2.2.2

Auto-reclosing operation Off and On


Operation of the automatic reclosing can be set to Off or On via the setting
parameters and through external control. With the setting Operation = On, the
function is activated while with the setting Operation = Off the function is
deactivated. With the setting Operation = External ctrl, the activation/deactivation
is made by input signal pulses, for example, from a control system.
When the function is set On and is operative the output SETON is activated (high).
Other input conditions such as CBPOS and CBREADY must also be fulfilled. At
this point the automatic recloser is prepared to start the reclosing cycle and the
output signal READY on the SMBRREC function block is activated (high).

12.2.2.3

Auto-reclosing mode selection


The Auto-reclosing mode is selected with setting ARMode = 3phase(0), 1/2/3ph(1),
1/2ph(2), 1ph+1*2ph(3), 1/2ph+1*3ph(4), 1ph+1*2/3ph(5). The selected mode
can be read as integer as per above list on output MODE.
As an alternative to setting the mode can be selected by connecting an integer, for
example from function block B16I to input MODEINT.
Following integers shall be used: 1=3phase, 2=1/2/3ph, 3=1/2ph, 4=1ph+1*2ph,
5=1/2ph+1*3ph or 6=1ph+1*2/3ph.

570
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

When INTZERO from Fixed signal function block is connected to the input
MODEINT the parameter setting selected will be valid.

12.2.2.4

Start auto-reclosing and conditions for start of a reclosing cycle


The usual way in which to start a reclosing cycle, or sequence, is to start it when a
line protection tripping has occurred, by applying a signal to the START input. It
should be necessary to adjust three-phase auto-reclosing open time, (dead time) for
different power system configurations or during tripping at different protection
stages, the input STARTHS (start high-speed reclosing) can also be used.
For a new auto-reclosing cycle to be started, a number of conditions need to be
met. They are linked to dedicated inputs. The inputs are:

CBREADY: CB ready for a reclosing cycle, for example, charged operating gear
CBPOS: to ensure that the CB was closed when the line fault occurred and
start was applied
No blocking or inhibit signal shall be present.

After the start has been accepted, it is latched in and an internal signal Started is
set. It can be interrupted by certain events, like an inhibit signal.
To start auto-reclosing by CB position Open instead of from protection trip signals,
one has to configure the CB Open position signal to inputs CBPOS and START
and set a parameter StartByCBOpen = On and CBAuxContType = NormClosed
(normally closed). One also has to configure and connect signals from manual trip
commands to input INHIBIT.
The logic for switching the auto-recloser On/Off and the starting of the reclosing is
shown in figure 314. The following should be considered:

Setting Operation can be set to Off, External ctrl or On. External ctrl offers
the possibility of switching by external switches to inputs ON and OFF,
communication commands to the same inputs, and so on.
SMBRREC is normally started by tripping. It is either a Zone 1 and
Communication aided trip, or a general trip. If the general trip is used the
function must be blocked from all back-up tripping connected to INHIBIT. In
both alternatives the breaker failure function must be connected to inhibit the
function. START makes a first attempt with synchrocheck, STARTHS makes
its first attempt without synchrocheck. TRSOTF starts shots 2-5.
Circuit breaker checks that the breaker was closed for a certain length of time
before the starting occurred and that the CB has sufficient stored energy to
perform an auto-reclosing sequence and is connected to inputs CBPOS and
CBREADY.

571
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Operation:On
Operation:Off
Operation:External Ctrl
AND

ON

AND

OFF
START
STARTHS

OR

OR

CBREADY
CBPOS

initiate

OR

autoInitiate
TRSOTF

SETON

AND S
OR

Additional conditions

AND
start

120 ms
t
CB Closed

AND

AND S

AND

tCBClosedMin
R

t
AND

Blocking conditions

OR

AND

READY

Inhibit condistions
count 0
en05000782.vsd

IEC05000782 V1 EN

Figure 314:

12.2.2.5

Auto-reclosing Off/On and start

Control of the auto-reclosing open time for shot 1


It is possible to use up to four different time settings for the first shot, and one
extension time. There are separate settings for single- , two- and three-phase autoreclosing open times, t1 1Ph, t1 2Ph, t1 3Ph. If no particular input signal is applied,
and an auto-reclosing program with single-phase reclosing is selected, the autoreclosing open time t1 1Ph will be used. If one of the inputs TR2P or TR3P is
activated in connection with the input START, the auto-reclosing open time for twophase or three-phase reclosing is used. There is also a separate time setting facility
for three-phase high-speed auto-reclosing, t1 3PhHS available for use when
required. It is activated by input STARTHS.
An auto-reclosing open time extension delay, tExtended t1, can be added to the
normal shot 1 delay. It is intended to come into use if the communication channel
for permissive line protection is lost. In a case like this there can be a significant
time difference in fault clearance at the two line ends. A longer auto-reclosing open
time can then be useful. This extension time is controlled by setting parameter
Extended t1 = On and the input PLCLOST.

12.2.2.6

Long trip signal


In normal circumstances the trip command resets quickly due to fault clearing. The
user can set a maximum trip pulse duration tTrip. When trip signals are longer, the

572
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

auto-reclosing open time is extended by tExtended t1. If Extended t1 = Off, a long


trip signal interrupts the reclosing sequence in the same way as a signal to input
INHIBIT.

Extended t1

PLCLOST
initiate

AND

OR

AND

AND

Extend t1

tTrip
t

start

AND

AND

long duration
(block SMBRREC)
IEC05000783_2_en.vsd

IEC05000783 V2 EN

Figure 315:

Control of extended auto-reclosing open time and long trip pulse detection

Reclosing checks and the reclaim timer

When dead time has elapsed during the auto-reclosing procedure certain conditions
must be fulfilled before the CB closing command is issued. To achieve this, signals
are exchanged between program modules to check that these conditions are met. In
three-phase reclosing a synchronizing and/or energizing check can be used. It is
possible to use a synchrocheck function in the same physical device or an external
one. The release signal is configured by connecting to the auto-reclosing function
input SYNC. If reclosing without checking is preferred the SYNC input can be set
to TRUE (set high). Another possibility is to set the output of the synchro-check
function to a permanently activated state. At confirmation from the synchro-check,
or if the reclosing is of single-phase or two-phase type, the signal passes on. At singlephase, two-phase reclosing and at three-phase high-speed reclosing started by
STARTHS, synchronization is not checked, and the state of the SYNC input is
disregarded.
By choosing CBReadyType = CO (CB ready for a Close-Open sequence) the
readiness of the circuit breaker is also checked before issuing the CB closing
command. If the CB has a readiness contact of type CBReadyType = OCO (CB
ready for an Open-Close-Open sequence) this condition may not be complied with
after the tripping and at the moment of reclosure. The Open-Close-Open condition
was however checked at the start of the reclosing cycle and it is then likely that the
CB is prepared for a Close-Open sequence.

573
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The synchro-check or energizing check must be fulfilled within a set time interval,
tSync. If it is not, or if other conditions are not met, the reclosing is interrupted and
blocked.
The reclaim timer defines a time from the issue of the reclosing command, after
which the reclosing function resets. Should a new trip occur during this time, it is
treated as a continuation of the first fault. The reclaim timer is started when the CB
closing command is given.
A number of outputs for Autoreclosing state control keeps track of the actual state
in the reclosing sequence.

574
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

t1 1Ph
t

From logic for


reclosing
programs

1P2PTO
3PHSTO
3PT1TO
3PT2TO
3PT3TO
3PT4TO
3PT5TO
SYNC
initiate
CBREADY

OR

"SMBRREC Open time" timers

t1 2Ph
t

1P2PTO

OR

t1 3Ph HS
t

3PHSTO

t1 3Ph
t

3PT1TO

AND
OR

Pulse AR

AND

AND

AND

OR

SMRREC State
Control

tSync
t

AND

Blocking out

COUNTER

CL

Pulse SMBRREC (above)


OR

LOGIC
reclosing
programs

TR2P
TR3P
start
initiate

AND

tReclaim
t

Reclaim Timer On

0
1
2
3
4
5

1PT1
2PT1
3PHS
3PT1

Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5

Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5

INPROGR
OR

3PT2
3PT3
3PT4

PERMIT1P

3PT5

PREP3P

1
Blocking out
OR

INHIBIT

tInhibit
t

Inhibit (internal)

IEC05000784_2_en.vsd
IEC05000784 V2 EN

Figure 316:

Reclosing Reclaim and Inhibit timers

Pulsing of the CB closing command

The CB closing command, CLOSECB is a pulse with a duration set by parameter


tPulse. For circuit-breakers without anti-pumping function, the close pulse cutting
described below can be used. This is done by selecting the parameter
575
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

CutPulse=On. In case of a new trip pulse, the closing command pulse is cut
(interrupted). The minimum duration of the pulse is always 50 ms. See figure 317
When a reclosing command is issued, the appropriate reclosing operation counter is
incremented. There is a counter for each type of reclosing and one for the total
number of reclosing commands issued.

pulse

tPulse
**)

initiate

AND

CLOSECB

OR

50 ms

1PT1

AND

2PT1

AND

3PT1

AND

3PT2

AND

3PT3

AND

3PT4

AND

3PT5

AND

RSTCOUNT

counter

COUNT1P

counter

COUNT2P

counter

COUNT3P1

counter

COUNT3P2

counter

COUNT3P3

counter

COUNT3P4

counter

COUNT3P5

counter

COUNTAR

**) Only if "CutPulse" = On


en05000785.vsd
IEC05000785 V1 EN

Figure 317:

Pulsing of closing command and driving the operation counters

Transient fault

After the reclosing command the reclaim timer tReclaim starts running for the set
time. If no tripping occurs within this time, the auto-reclosing will reset.

Permanent fault and reclosing unsuccessful signal

If a new trip occurs after the CB closing command, and a new input signal START
or TRSOTF appears, the output UNSUCCL (unsuccessful closing) is set high. The
timers for the first shot can no longer be started. Depending on the setting for the
number of reclosing shots, further shots may be made or the reclosing sequence
576
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

will be ended. After the reclaim time has elapsed, the auto-reclosing function resets
but the CB remains open. The CB closed data at the CBPOS input will be missing.
Because of this, the reclosing function will not be ready for a new reclosing cycle.
Normally the signal UNSUCCL appears when a new trip and start is received after
the last reclosing shot has been made and the auto-reclosing function is blocked.
The signal resets once the reclaim time has elapsed. The unsuccessful signal can
also be made to depend on CB position input. The parameter UnsucClByCBChk
should then be set to CBCheck, and a timer tUnsucCl should also be set. If the CB
does not respond to the closing command and does not close, but remains open, the
output UNSUCCL is set high after time tUnsucCl.
initiate
block start

AND

OR

AND

shot 0

UNSUCCL

UnsucClByCBchk = CBcheck

Pulse AR (Closing)
CBPOS

OR

CBclosed

tUnsucCl
AND

AND

eno5000786.vsd
IEC05000786 V1 EN

Figure 318:

Issue of signal UNSUCCL, unsuccessful reclosing

Automatic continuation of the reclosing sequence

The auto-reclosing function can be programmed to proceed to the following


reclosing shots (if selected) even if the start signals are not received from the
protection functions, but the breaker is still not closed. This is done by setting
parameter AutoCont = On and tAutoContWait to the required delay for the function
to proceed without a new start.

577
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

tAutoContWait
t

AND

CLOSECB
AND

S Q
R

AND

CBPOS

CBClosed

OR

START

OR

initiate

en05000787.vsd
IEC05000787 V1 EN

Figure 319:

Automatic proceeding of shot 2 to 5

Start of reclosing from CB open information

If a user wants to apply starting of auto-reclosing from CB open position instead of


from protection trip signals, the function offers such a possibility. This starting
mode is selected by a setting parameter StartByCBOpen = On. One needs then to
block reclosing at all manual trip operations. Typically, one also set
CBAuxContType = NormClosed and connect a CB auxiliary contact of type NC
(normally closed) to inputs CBPOS and START. When the signal changes from
CB closed to CB open an auto-reclosing start pulse of limited length is generated
and latched in the function, subject to the usual checks. Then the reclosing
sequence continues as usual. One needs to connect signals from manual tripping
and other functions, which shall prevent reclosing, to the input INHIBIT.

578
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

StartByCBOpen = On
1
START

AND

STARTHS

AND
100 ms

start

AND
100 ms
AND

en05000788.vsd
IEC05000788 V1 EN

Figure 320:

12.2.2.7

Pulsing of the start inputs

Time sequence diagrams


Some examples of the timing of internal and external signals at typical transient
and permanent faults are shown below in figures 321 to 324.
Fault
CB POS

Closed

Open

Closed

CB READY
START
SYNC

(Trip)
tReclaim

READY
INPROG
1PT1
ACTIVE
CLOSE CB

t1 1Ph

tPulse

PREP3P
SUCCL
Time

en04000196-2-en.vsd
IEC04000196 V2 EN

Figure 321:

Transient single-phase fault. Single -phase reclosing

579
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Fault
CB POS

Closed

Open

START

Open

CB READY

(Trip)

TR3P
SYNC
READY
INPROGR
3PT1

t1 3Ph

3PT2

t2 3Ph
tReclaim

ACTIVE
CLOSE CB

tPulse

tPulse

PREP3P
UNSUCCL
Time

en04000197.vsd
IEC04000197 V1 EN

Figure 322:

Permanent fault. Three-phase trip. Two-shot reclosing

580
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
t1s

AR01-CLOSECB
AR01-P3P
AR01-UNSUC

tReclaim

en04000198.vsd
IEC04000198 V1 EN

Figure 323:

Permanent single-phase fault. Program 1/2/3ph, single-phase


single-shot reclosing

Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
AR01-CLOSECB

t1s

t2

AR01-P3P
AR01-UNSUC

tReclaim

en04000199.vsd
IEC04000199 V1 EN

Figure 324:

Permanent single-phase fault. Program 1ph + 3ph or 1/2ph + 3ph,


two-shot reclosing
581

Technical reference manual

Section 12
Control
12.2.3

1MRK 505 222-UEN B

Function block
SMBRREC
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
START
INPROGR
STARTHS
1PT1
TRSOTF
2PT1
SKIPHS
3PT1
ZONESTEP
3PT2
TR2P
3PT3
TR3P
3PT4
THOLHOLD
3PT5
CBREADY
PERMIT1P
CBPOS
PREP3P
PLCLOST
CLOSECB
SYNC
WFMASTER
WAIT
COUNT1P
RSTCOUNT
COUNT2P
MODEINT
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
IEC06000189-2-en.vsd
IEC06000189 V2 EN

Figure 325:

12.2.4

SMBRREC function block

Input and output signals


Table 320:
Name

SMBRREC Input signals


Type

Default

Description

ON

BOOLEAN

Switches the AR On (at Operation = ExternalCtrl)

OFF

BOOLEAN

Switches the AR Off (at Operation = ExternalCtrl)

BLKON

BOOLEAN

Sets the AR in blocked state

BLKOFF

BOOLEAN

Releases the AR from the blocked state

RESET

BOOLEAN

Resets the AR to initial conditions

INHIBIT

BOOLEAN

Interrupts and inhibits reclosing sequence

START

BOOLEAN

Reclosing sequence starts by a protection trip


signal

STARTHS

BOOLEAN

Start HS reclosing without SC: t13PhHS

TRSOTF

BOOLEAN

Makes AR to continue to shots 2-5 at a trip from


SOTF

SKIPHS

BOOLEAN

Will skip the high speed shot and continue on


delayed shots

ZONESTEP

BOOLEAN

Coordination between local AR and down stream


devices

TR2P

BOOLEAN

Signal to the AR that a two-phase tripping occurred

TR3P

BOOLEAN

Signal to the AR that a three-phase tripping


occurred

Table continues on next page

582
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

THOLHOLD

BOOLEAN

Hold the AR in wait state

CBREADY

BOOLEAN

CB must be ready for CO/OCO operation to allow


start / close

CBPOS

BOOLEAN

Status of the circuit breaker Closed/Open

PLCLOST

BOOLEAN

Power line carrier or other form of permissive sig


nal lost

SYNC

BOOLEAN

Synchronizing check fulfilled (for 3Ph attempts)

WAIT

BOOLEAN

Wait for master (in Multi-breaker arrangements)

RSTCOUNT

BOOLEAN

Resets all counters

MODEINT

INTEGER

Integer input used to set the reclosingMode,


alternative to setting

Table 321:
Name

SMBRREC Output signals


Type

Description

BLOCKED

BOOLEAN

The AR is in blocked state

SETON

BOOLEAN

The AR operation is switched on, operative

READY

BOOLEAN

Indicates that the AR function is ready for a new


sequence

ACTIVE

BOOLEAN

Reclosing sequence in progress

SUCCL

BOOLEAN

Activated if CB closes during the time tUnsucCl

UNSUCCL

BOOLEAN

Reclosing unsuccessful, signal resets after the


reclaim time

INPROGR

BOOLEAN

Reclosing shot in progress, activated during open


time

1PT1

BOOLEAN

Single-phase reclosing is in progress, shot 1

2PT1

BOOLEAN

Two-phase reclosing is in progress, shot 1

3PT1

BOOLEAN

Three-phase reclosing in progress, shot 1

3PT2

BOOLEAN

Three-phase reclosing in progress, shot 2

3PT3

BOOLEAN

Three-phase reclosing in progress, shot 3

3PT4

BOOLEAN

Three-phase reclosing in progress, shot 4

3PT5

BOOLEAN

Three-phase reclosing in progress, shot 5

PERMIT1P

BOOLEAN

Permit single-phase trip, inverse signal to PREP3P

PREP3P

BOOLEAN

Prepare three-phase trip, control of the next trip


operation

CLOSECB

BOOLEAN

Closing command for CB

WFMASTER

BOOLEAN

Signal to Slave issued by Master for sequential


reclosing

COUNT1P

INTEGER

Counting the number of single-phase reclosing


shots

COUNT2P

INTEGER

Counting the number of two-phase reclosing shots

COUNT3P1

INTEGER

Counting the number of three-phase reclosing


shot 1

Table continues on next page

583
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.2.5
Table 322:
Name

Type

Description

COUNT3P2

INTEGER

Counting the number of three-phase reclosing


shot 2

COUNT3P3

INTEGER

Counting the number of three-phase reclosing


shot 3

COUNT3P4

INTEGER

Counting the number of three-phase reclosing


shot 4

COUNT3P5

INTEGER

Counting the number of three-phase reclosing


shot 5

COUNTAR

INTEGER

Counting total number of reclosing shots

MODE

INTEGER

Integer output for reclosing mode

Setting parameters
SMBRREC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
External ctrl
On

External ctrl

Off, ExternalCtrl, On

ARMode

3 phase
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph

1/2/3ph

The AR mode selection e.g. 3ph, 1/3ph

t1 1Ph

0.000 - 60.000

0.001

1.000

Open time for shot 1, single-phase

t1 3Ph

0.000 - 60.000

0.001

6.000

Open time for shot 1, delayed reclosing


3ph

t1 3PhHS

0.000 - 60.000

0.001

0.400

Open time for shot 1, high speed


reclosing 3ph

tReclaim

0.00 - 6000.00

0.01

60.00

Duration of the reclaim time

tSync

0.00 - 6000.00

0.01

30.00

Maximum wait time for synchrocheck OK

tTrip

0.000 - 60.000

0.001

0.200

Maximum trip pulse duration

tPulse

0.000 - 60.000

0.001

0.200

Duration of the circuit breaker closing


pulse

tCBClosedMin

0.00 - 6000.00

0.01

5.00

Min time that CB must be closed before


new sequence allows

tUnsucCl

0.00 - 6000.00

0.01

30.00

Wait time for CB before indicating


Unsuccessful/Successful

Priority

None
Low
High

None

Priority selection between adjacent


terminals None/Low/High

tWaitForMaster

0.00 - 6000.00

0.01

60.00

Maximum wait time for release from


Master

584
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 323:

SMBRREC Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

NoOfShots

1
2
3
4
5

Max number of reclosing shots 1-5

StartByCBOpen

Off
On

Off

To be set ON if AR is to be started by
CB open position

CBAuxContType

NormClosed
NormOpen

NormOpen

Select the CB aux contact type NC/NO


for CBPOS input

CBReadyType

CO
OCO

CO

Select type of circuit breaker ready


signal CO/OCO

t1 2Ph

0.000 - 60.000

0.001

1.000

Open time for shot 1, two-phase

t2 3Ph

0.00 - 6000.00

0.01

30.00

Open time for shot 2, three-phase

t3 3Ph

0.00 - 6000.00

0.01

30.00

Open time for shot 3, three-phase

t4 3Ph

0.00 - 6000.00

0.01

30.00

Open time for shot 4, three-phase

t5 3Ph

0.00 - 6000.00

0.01

30.00

Open time for shot 5, three-phase

Extended t1

Off
On

Off

Extended open time at loss of


permissive channel Off/On

tExtended t1

0.000 - 60.000

0.001

0.500

3Ph Dead time is extended with this


value at loss of perm ch

tInhibit

0.000 - 60.000

0.001

5.000

Inhibit reclosing reset time

CutPulse

Off
On

Off

Shorten closing pulse at a new trip Off/On

Follow CB

Off
On

Off

Advance to next shot if CB has been


closed during dead time

AutoCont

Off
On

Off

Continue with next reclosing-shot if


breaker did not close

tAutoContWait

0.000 - 60.000

0.001

2.000

Wait time after close command before


proceeding to next shot

UnsucClByCBChk

NoCBCheck
CB check

NoCBCheck

Unsuccessful closing signal obtained by


checking CB position

BlockByUnsucCl

Off
On

Off

Block AR at unsuccessful reclosing

ZoneSeqCoord

Off
On

Off

Coordination of down stream devices to


local prot units AR

585
Technical reference manual

Section 12
Control
12.2.6

1MRK 505 222-UEN B

Technical data
Table 324:

SMBRREC technical data

Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld

Range or value
1-5

(0.000-60.000) s

0.5% 10 ms

shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5

(0.00-6000.00) s

Extended autorecloser open time

(0.000-60.000) s

Autorecloser maximum wait time for sync

(0.00-6000.00) s

Maximum trip pulse duration

(0.000-60.000) s

Inhibit reset time

(0.000-60.000) s

Reclaim time

(0.00-6000.00) s

Minimum time CB must be closed before AR


becomes ready for autoreclosing cycle

(0.00-6000.00) s

Circuit breaker closing pulse length

(0.000-60.000) s

CB check time before unsuccessful

(0.00-6000.00) s

Wait for master release

(0.00-6000.00) s

Wait time after close command before


proceeding to next shot

(0.000-60.000) s

12.3

Apparatus control APC

12.3.1

Introduction

Accuracy

The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and earthing switches within a bay. Permission to operate
is given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.

12.3.2

Principle of operation
A bay can handle, for example a power line, a transformer, a reactor, or a capacitor
bank. The different primary apparatuses within the bay can be controlled via the

586
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

apparatus control function directly by the operator or indirectly by automatic


sequences.
Because a primary apparatus can be allocated to many functions within a
Substation Automation system, the object-oriented approach with a function
module that handles the interaction and status of each process object ensures
consistency in the process information used by higher-level control functions.
Primary apparatuses such as breakers and disconnectors are controlled and
supervised by one software module (SCSWI) each. Because the number and type
of signals connected to a breaker and a disconnector are almost the same, the same
software is used to handle these two types of apparatuses.
The software module is connected to the physical process in the switchyard via an
interface module by means of a number of digital inputs and outputs. One type of
interface module is intended for a circuit breaker (SXCBR) and another type is
intended for a disconnector or earthing switch (SXSWI). Four types of function
blocks are available to cover most of the control and supervision within the bay.
These function blocks are interconnected to form a control function reflecting the
switchyard configuration. The total number used depends on the switchyard
configuration. These four types are:

Bay control QCBAY


Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI

The three latter functions are logical nodes according to IEC 61850. The functions
Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle
the local/remote switch, and the functions Bay reserve (QCRSV) and Reservation
input (RESIN), for the reservation function, also belong to the apparatus control
function. The principles of operation, function block, input and output signals and
setting parameters for all these functions are described below.

12.3.3

Error handling
Depending on the error that occurs during the command sequence the error signal
will be set with a value. Table 325 describes vendor specific cause values in
addition to these specified in IEC 61850-8-1 standard. The list of values of the
cause are in order of priority. The values are available over the IEC 61850. An
output L_CAUSE on the function block for Switch controller (SCSWI), Circuit
breaker (SXCBR) and Circuit switch (SXSWI) indicates the latest value of the
error during the command.

587
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 325:

Values for "cause" signal in priority order


Attribute value

Defined in IEC 61850

Description

Supported

no error

serviceError-type

blocked-by-switchinghierarchy

select-failed

invalid-position

position-reached

parameter-change-inexecution

step-limit

blocked-by-mode

blocked-by-process

10

blocked-by-interlocking

11

blocked-bysynchrocheck

12

command-already-inexecution

13

blocked-by-health

14

1-of-n-control

15

abortion-by-cancel

16

time-limit-over

17

abortion-by-trip

18

object-not-selected

19

Not in use

Table continues on next page

588
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Attribute value

Description

-20

Not in use

-21

Not in use

-23

blocked-for-command

-24

blocked-for-opencommand

-25

blocked-for-closecommand

-26

Not in use

-27

Not in use

-28

Not in use

-29

Not in use

-30

long-operation-time

-31

switch-not-start-moving

-32

persisting-intermediatestate

-33

switch-returned-to-initialposition

-34

switch-in-bad-state

-35

not-expected-finalposition

Vendor specific

12.3.4

Bay control QCBAY

12.3.4.1

Introduction

Supported

The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay.
QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay.

12.3.4.2

Principle of operation
The functionality of the Bay control (QCBAY) function is not defined in the IEC
6185081 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO)
and blocking conditions to other functions within the bay for example, switch
control functions, voltage control functions and measurement functions.

Local panel switch

The local panel switch is a switch that defines the operator place selection. The
switch connected to this function can have three positions remote/local/off. The
positions are here defined so that remote means that operation is allowed from station/
remote level and local from the IED level. The local/remote switch is normally
589
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

situated on the control/protection IED itself, which means that the position of the
switch and its validity information are connected internally, and not via I/O boards.
When the switch is mounted separately on the IED the signals are connected to the
function via I/O boards.
When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the
PSTO output will always be set to faulty state (3), which means no possibility to
operate.
To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.

Permitted Source To Operate (PSTO)

The actual state of the operator place is presented by the value of the Permitted
Source To Operate, PSTO signal. The PSTO value is evaluated from the local/
remote switch position according to table 326. In addition, there is one
configuration parameter that affects the value of the PSTO signal. If the parameter
AllPSTOValid is set and LR-switch position is in Local or Remote state, the PSTO
value is set to 5 (all), that is, it is permitted to operate from both local and remote
level without any priority. When the external panel switch is in Off position the
PSTO value shows the actual state of switch that is, 0. In this case it is not possible
to control anything.
Table 326:
Local panel switch
positions

PSTO values for different Local panel switch positions


PSTO value

AllPSTOValid
(configuration
parameter)

Possible locations that shall be able to


operate

0 = Off

--

Not possible to operate

1 = Local

FALSE

Local Panel

1 = Local

TRUE

Local or Remote level without any


priority

2 = Remote

FALSE

Remote level

2 = Remote

TRUE

Local or Remote level without any


priority

3 = Faulty

--

Not possible to operate

Blockings

The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:

590
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
6185081). If DO Behavior is set to "blocked" it means that the function is
active, but no outputs are generated, no reporting, control commands are
rejected and functional and configuration data is visible.

The switching of the Local/Remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.

12.3.4.3

Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD

PSTO
UPD_BLKD
CMD_BLKD
LOC
REM

IEC10000048-1-en.vsd
IEC10000048 V1 EN

Figure 326:

12.3.4.4

QCBAY function block

Input and output signals


Table 327:
Name

QCBAY Input signals


Type

Default

Description

LR_OFF

BOOLEAN

External Local/Remote switch is in Off position

LR_LOC

BOOLEAN

External Local/Remote switch is in Local position

LR_REM

BOOLEAN

External Local/Remote switch is in Remote


position

LR_VALID

BOOLEAN

Data representing the L/R switch position is valid

BL_UPD

BOOLEAN

Steady signal to block the position updates

BL_CMD

BOOLEAN

Steady signal to block the command

Table 328:
Name

QCBAY Output signals


Type

Description

PSTO

INTEGER

Value for the operator place allocation

UPD_BLKD

BOOLEAN

Update of position is blocked

CMD_BLKD

BOOLEAN

Function is blocked for commands

LOC

BOOLEAN

Local operation allowed

REM

BOOLEAN

Remote operation allowed

591
Technical reference manual

Section 12
Control
12.3.4.5
Table 329:
Name
AllPSTOValid

1MRK 505 222-UEN B

Setting parameters
QCBAY Non group settings (basic)
Values (Range)
Priority
No priority

Unit
-

Step
-

12.3.5

Local/Remote switch

12.3.5.1

Introduction

Default
Priority

Description
Priority of originators

The signals from the local HMI or from an external local/remote switch are applied
via the function blocks LOCREM and LOCREMCTRL to the Bay control
(QCBAY) function block. A parameter in function block LOCREM is set to
choose if the switch signals are coming from the local HMI or from an external
hardware switch connected via binary inputs.

12.3.5.2

Principle of operation
The function block Local remote (LOCREM) handles the signals coming from the
local/remote switch. The connections are seen in figure 327, where the inputs on
function block LOCREM are connected to binary inputs if an external switch is
used. When a local HMI is used, the inputs are not used and are set to FALSE in
the configuration. The outputs from the LOCREM function block control the
output PSTO (Permitted Source To Operate) on Bay control (QCBAY).

592
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID

QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
REM
BL_ UPD
BL_ CMD

LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID

QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
REM
BL_ UPD
BL_ CMD

LOCREMCTRL
PSTO1
HMICTR1
PSTO2
HMICTR2
PSTO3
HMICTR3
PSTO4
HMICTR4
PSTO5
HMICTR5
PSTO6
HMICTR6
PSTO7
HMICTR7
PSTO8
HMICTR8
PSTO9
HMICTR9
PSTO 10
HMICTR 10
PSTO 11
HMICTR 11
PSTO 12
HMICTR 12
IEC10000052-1-en.vsd
IEC10000052 V1 EN

Figure 327:

Configuration for the local/remote handling for a local HMI with two
bays and two screen pages

If the IED contains control functions for several bays, the local/remote position can
be different for the included bays. When the local HMI is used the position of the
local/remote switch can be different depending on which single line diagram screen
page that is presented on the local HMI. The function block Local remote control
(LOCREMCTRL) controls the presentation of the LEDs for the local/remote
position to applicable bay and screen page.
The switching of the local/remote switch requires at least system operator level.
The password will be requested at an attempt to operate if authority levels have
been defined in the IED. Otherwise the default authority level, SuperUser, can
handle the control without LogOn. The users and passwords are defined in PCM600.

593
Technical reference manual

Section 12
Control
12.3.5.3

1MRK 505 222-UEN B

Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL

OFF
LOCAL
REMOTE
VALID
IEC05000360-2-en.vsd

IEC05000360 V2 EN

Figure 328:

PSTO1
PSTO2
PSTO3
PSTO4
PSTO5
PSTO6
PSTO7
PSTO8
PSTO9
PSTO10
PSTO11
PSTO12

LOCREM function block

LOCREMCTRL
HMICTR1
HMICTR2
HMICTR3
HMICTR4
HMICTR5
HMICTR6
HMICTR7
HMICTR8
HMICTR9
HMICTR10
HMICTR11
HMICTR12
IEC05000361-2-en.vsd

IEC05000361 V2 EN

Figure 329:

12.3.5.4

LOCREMCTRL function block

Input and output signals


Table 330:
Name

LOCREM Input signals


Type

Default

Description

CTRLOFF

BOOLEAN

Disable control

LOCCTRL

BOOLEAN

Local in control

REMCTRL

BOOLEAN

Remote in control

LHMICTRL

INTEGER

LHMI control

Table 331:
Name

LOCREM Output signals


Type

Description

OFF

BOOLEAN

Control is disabled

LOCAL

BOOLEAN

Local control is activated

REMOTE

BOOLEAN

Remote control is activated

VALID

BOOLEAN

Outputs are valid

594
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 332:

LOCREMCTRL Input signals

Name

Type
INTEGER

PSTO input channel 1

PSTO2

INTEGER

PSTO input channel 2

PSTO3

INTEGER

PSTO input channel 3

PSTO4

INTEGER

PSTO input channel 4

PSTO5

INTEGER

PSTO input channel 5

PSTO6

INTEGER

PSTO input channel 6

PSTO7

INTEGER

PSTO input channel 7

PSTO8

INTEGER

PSTO input channel 8

PSTO9

INTEGER

PSTO input channel 9

PSTO10

INTEGER

PSTO input channel 10

PSTO11

INTEGER

PSTO input channel 11

PSTO12

INTEGER

PSTO input channel 12

LOCREMCTRL Output signals

Name

Table 334:

Description

PSTO1

Table 333:

12.3.5.5

Default

Type

Description

HMICTR1

INTEGER

Bitmask output 1 to local remote LHMI input

HMICTR2

INTEGER

Bitmask output 2 to local remote LHMI input

HMICTR3

INTEGER

Bitmask output 3 to local remote LHMI input

HMICTR4

INTEGER

Bitmask output 4 to local remote LHMI input

HMICTR5

INTEGER

Bitmask output 5 to local remote LHMI input

HMICTR6

INTEGER

Bitmask output 6 to local remote LHMI input

HMICTR7

INTEGER

Bitmask output 7 to local remote LHMI input

HMICTR8

INTEGER

Bitmask output 8 to local remote LHMI input

HMICTR9

INTEGER

Bitmask output 9 to local remote LHMI input

HMICTR10

INTEGER

Bitmask output 10 to local remote LHMI input

HMICTR11

INTEGER

Bitmask output 11 to local remote LHMI input

HMICTR12

INTEGER

Bitmask output 12 to local remote LHMI input

Setting parameters
LOCREM Non group settings (basic)

Name
ControlMode

12.3.6

Values (Range)
Internal LR-switch
External LR-switch

Unit
-

Step
-

Default
Internal LR-switch

Description
Control mode for internal/external LRswitch

Switch controller SCSWI

595
Technical reference manual

Section 12
Control
12.3.6.1

1MRK 505 222-UEN B

Introduction
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may
handle and operate on one three-phase device.

12.3.6.2

Principle of operation
The Switch controller (SCSWI) is provided with verification checks for the select execute sequence, that is, checks the conditions prior each step of the operation.
The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.

Control handling
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.
Normal security means that only the command is evaluated and the resulting
position is not supervised. Enhanced security means that the command sequence is
supervised in three steps, the selection, command evaluation and the supervision of
position. Each step ends up with a pulsed signal to indicate that the respective step
in the command sequence is finished. If an error occurs in one of the steps in the
command sequence, the sequence is terminated and the error is mapped into the
enumerated variable "cause" attribute belonging to the pulsed response signal for
the IEC 61850 communication. The last cause L_CAUSE can be read from the
function block and used for example at commissioning.
There is no relation between the command direction and the actual
position. For example, if the switch is in close position it is possible
to execute a close command.
Before an execution command, an evaluation of the position is done. If the
parameter PosDependent is true and the position is in intermediate state or in bad
state no execution command is sent. If the parameter is false the execution
command is sent independent of the position value.

Evaluation of position

In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the onephase switches, following principles will be applied:

596
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The position output from switch (SXCBR or SXSWI) is connected to SCSWI.


With the group signal connection the SCSWI obtains the position, time stamps and
quality attributes of the position which is used for further evaluation.
All switches in open position:

switch control position = open

All switches in close position:

switch control position = close

One switch =open, two switches= close (or


inversely):

switch control position = intermediate

Any switch in intermediate position:

switch control position = intermediate

Any switch in bad state:

switch control position = bad state

The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will
change position at any time due to a trip. Such situation is here called pole
discordance and is supervised by this function. In case of a pole discordance
situation, that is, the position of the one-phase switches are not equal for a time
longer than the setting tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause"
values from the switch modules Circuit breaker (SXCBR)/ Circuit switch
(SXSWI). At error the "cause" value with highest priority is shown.

Blocking principles

The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC 61850 communication from the operator place.
The different blocking possibilities are:

Block/deblock of command. It is used to block command for operation of


position.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.
The different block conditions will only affect the operation of this
function, that is, no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.

Interaction with synchrocheck and synchronizing functions

The Switch controller (SCSWI) works in conjunction with the synchrocheck and
the synchronizing function (SESRSYN). It is assumed that the synchrocheck
597
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

function is continuously in operation and gives the result to SCSWI. The result
from the synchrocheck function is evaluated during the close execution. If the
operator performs an override of the synchrocheck, the evaluation of the
synchrocheck state is omitted. When there is a positive confirmation from the
synchrocheck function, SCSWI will send the close signal EXE_CL to the switch
function Circuit breaker (SXCBR).
When there is no positive confirmation from the synchrocheck function, SCSWI
will send a start signal START_SY to the synchronizing function, which will send
the closing command to SXCBR when the synchronizing conditions are fulfilled,
see figure 330. If no synchronizing function is included, the timer for supervision
of the "synchronizing in progress signal" is set to 0, which means no start of the
synchronizing function. SCSWI will then set the attribute "blocked-bysynchrocheck" in the "cause" signal. See also the time diagram in figure 334.
SCSWI
EXE_CL

SXCBR
OR

CLOSE

SYNC_OK
START_SY
SY_INPRO
SESRSYN
CLOSECB
Synchro
check

Synchronizing
function

IEC09000209_1_en.vsd
IEC09000209 V1 EN

Figure 330:

Example of interaction between SCSWI, SESRSYN (synchrocheck


and synchronizing function) and SXCBR function

Time diagrams

The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer tSelect is used for supervising the time between the select and the
execute command signal, that is, the time the operator has to perform the command
execution after the selection of the object to operate.

598
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

select
execute command
tSelect
timer

t1

t1>tSelect, then longoperation-time in 'cause'


is set
en05000092.vsd

IEC05000092 V1 EN

Figure 331:

tSelect

The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback
reservation granted from all bays involved in the reservation function.
select
reservation request RES_RQ
reservation granted RES_GRT
command termination
tResResponse
timer

t1

t1>tResResponse, then
1-of-n-control in 'cause'
is set
en05000093.vsd

IEC05000093 V1 EN

Figure 332:

tResResponse

The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 333.

599
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

execute command
position L1 open
close
position L2 open
close
position L3 open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position

open
close

tExecutionFB
timer

t1>tExecutionFB, then
long-operation-time in
'cause' is set

t1

* The cmd termination will be delayed one execution sample.


en05000094.vsd
IEC05000094 V1 EN

Figure 333:

tExecutionFB

The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
execute command
SYNC_OK
tSynchrocheck
START_SY

t1

SY_INPRO
tSynchronizing
t2

t2>tSynchronizing, then
blocked-by-synchrocheck in
'cause' is set
en05000095.vsd

IEC05000095 V1 EN

Figure 334:

tSynchroCheck and tSynchronizing

600
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.3.6.3

Function block
SCSWI
BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_GRT
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS1
XPOS2
XPOS3

EXE_OP
EXE_CL
SELECTED
RES_RQ
START_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
XOUT
POS_INTR

IEC05000337-2-en.vsd
IEC05000337 V2 EN

Figure 335:

12.3.6.4

SCSWI function block

Input and output signals


Table 335:
Name

SCSWI Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

L_SEL

BOOLEAN

Select signal from local panel

L_OPEN

BOOLEAN

Open signal from local panel

L_CLOSE

BOOLEAN

Close signal from local panel

AU_OPEN

BOOLEAN

Used for local automation function

AU_CLOSE

BOOLEAN

Used for local automation function

BL_CMD

BOOLEAN

Steady signal for block of the command

RES_GRT

BOOLEAN

Positive acknowledge that all reservations are


made

RES_EXT

BOOLEAN

Reservation is made externally

SY_INPRO

BOOLEAN

Synchronizing function in progress

SYNC_OK

BOOLEAN

Closing is permitted at set to true by the


synchrocheck

EN_OPEN

BOOLEAN

Enables open operation

EN_CLOSE

BOOLEAN

Enables close operation

XPOS1

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

XPOS2

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

XPOS3

GROUP
SIGNAL

Group signal from XCBR/XSWI per phase

601
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 336:

SCSWI Output signals

Name

12.3.6.5
Table 337:
Name

Type

Description

EXE_OP

BOOLEAN

Execute command for open direction

EXE_CL

BOOLEAN

Execute command for close direction

SELECTED

BOOLEAN

Select conditions are fulfilled

RES_RQ

BOOLEAN

Request signal to the reservation function

START_SY

BOOLEAN

Starts the synchronizing function

POSITION

INTEGER

Position indication

OPENPOS

BOOLEAN

Open position indication

CLOSEPOS

BOOLEAN

Closed position indication

POLEDISC

BOOLEAN

The positions for poles L1-L3 are not equal after


a set time

CMD_BLK

BOOLEAN

Commands are blocked

L_CAUSE

INTEGER

Latest value of the error indication during command

XOUT

BOOLEAN

Execution information to XCBR/XSWI

POS_INTR

BOOLEAN

Stopped in intermediate position

Setting parameters
SCSWI Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

CtlModel

Dir Norm
SBO Enh

SBO Enh

Specifies control model type

PosDependent

Always permitted
Not perm at 00/11

Always permitted

Permission to operate depending on the


position

tSelect

0.00 - 600.00

0.01

30.00

Maximum time between select and


execute signals

tResResponse

0.000 - 60.000

0.001

5.000

Allowed time from reservation request to


reservation granted

tSynchrocheck

0.00 - 600.00

0.01

10.00

Allowed time for synchrocheck to fulfil


close conditions

tSynchronizing

0.00 - 600.00

0.01

0.00

Supervision time to get the signal


synchronizing in progress

tExecutionFB

0.00 - 600.00

0.01

30.00

Maximum time from command execution


to termination

tPoleDiscord

0.000 - 60.000

0.001

2.000

Allowed time to have discrepancy


between the poles

12.3.7

Circuit breaker SXCBR

602
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.3.7.1

Introduction
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of circuit breakers via output boards and to supervise the
switching operation and position.

12.3.7.2

Principle of operation
The users of the Circuit breaker function (SXCBR) is other functions such as for
example, switch controller, protection functions, autorecloser function or an IEC
61850 client residing in another IED or the operator place. This switch function
executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate a switch operation to be
allowed, the function performs the execution command. In case of erroneous
conditions, the function indicates an appropriate "cause" value.
SXCBR has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.

Local/Remote switch

One binary input signal LR_SWI is included in SXCBR to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard
level. If the signal is set to FALSE it means that command from IED or higher
level is permitted. When the signal is set to TRUE all commands (for change of
position) from internal IED clients are rejected, even trip commands from
protection functions are rejected. The functionality of the local/remote switch is
described in figure 336.

From I/O

E
RU

Local= Operation at
switch yard level

switchLR
FAL

SE

Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN

Figure 336:

Local/Remote switch

Blocking principles

SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autoreclosure and so on.

603
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The blocking possibilities are:

Block/deblock for open command. It is used to block operation for open


command. Note that this block signal also affects the input OPEN for
immediate command.
Block/deblock for close command. It is used to block operation for close
command. Note that this block signal also affects the input CLOSE for
immediate command.
Update block/deblock of positions. It is used to block the updating of position
values. Other signals related to the position will be reset.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution

The substitution part in SXCBR is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous for some reason. SXCBR will then
use the manually entered value instead of the value for positions determined by the
process.
It is always possible to make a substitution, independently of the
position indication and the status information of the I/O board.
When substitution is enabled, the position values are blocked for
updating and other signals related to the position are reset. The
substituted values are stored in a non-volatile memory.

Time diagrams

There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 337 explains these two timers during the execute phase.

604
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

AdaptivePulse = TRUE

EXE_CL
Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


"switch-not-start-moving"
attribute in 'cause' is set

tStartMove timer
t1
tStartMove

tIntermediate timer
t2

if t2 > tIntermediate then


"persisting-intermediate-state"
attribute in 'cause' is set

tIntermediate
en05000097.vsd
IEC05000097 V1 EN

Figure 337:

The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 338 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.
OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_CL
tClosePulse

AdaptivePulse=TRUE

EXE_CL
tClosePulse

en05000098.vsd
IEC05000098 V1 EN

Figure 338:

Execute output pulse

If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
The execute output pulses are reset when:

605
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.

There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and
CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has elapsed.
An example of when a primary device is open and an open command is executed is
shown in figure 339 .
OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_OP
tOpenPulse

AdaptivePulse=TRUE

EXE_OP
tOpenPulse
tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 339:

Open command with open position indication

606
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.3.7.3

Function block
SXCBR
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
TR_OPEN
TR_CLOSE
RS_CNT
XIN

XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE
IEC05000338-2-en.vsd

IEC05000338 V2 EN

Figure 340:

12.3.7.4

SXCBR function block

Input and output signals


Table 338:
Name

SXCBR Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

LR_SWI

BOOLEAN

Local/Remote switch indication from switchyard

OPEN

BOOLEAN

Pulsed signal used to immediately open the switch

CLOSE

BOOLEAN

Pulsed signal used to immediately close the switch

BL_OPEN

BOOLEAN

Signal to block the open command

BL_CLOSE

BOOLEAN

Signal to block the close command

BL_UPD

BOOLEAN

Steady signal for block of the position updating

POSOPEN

BOOLEAN

Signal for open position of apparatus from I/O

POSCLOSE

BOOLEAN

Signal for close position of apparatus from I/O

TR_OPEN

BOOLEAN

Signal for open position of truck from I/O

TR_CLOSE

BOOLEAN

Signal for close position of truck from I/O

RS_CNT

BOOLEAN

Resets the operation counter

XIN

BOOLEAN

Execution information from CSWI

Table 339:
Name

SXCBR Output signals


Type

Description

XPOS

GROUP SIGNAL

Group signal for XCBR output

EXE_OP

BOOLEAN

Executes the command for open direction

EXE_CL

BOOLEAN

Executes the command for close direction

SUBSTED

BOOLEAN

Indication that the position is substituted

OP_BLKD

BOOLEAN

Indication that the function is blocked for open


commands

CL_BLKD

BOOLEAN

Indication that the function is blocked for close


commands

Table continues on next page


607
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.3.7.5
Table 340:
Name

Type

Description

UPD_BLKD

BOOLEAN

Update of position indication is blocked

POSITION

INTEGER

Apparatus position indication

OPENPOS

BOOLEAN

Apparatus open position

CLOSEPOS

BOOLEAN

Apparatus closed position

TR_POS

INTEGER

Truck position indication

CNT_VAL

INTEGER

Operation counter value

L_CAUSE

INTEGER

Latest value of the error indication during command

Setting parameters
SXCBR Non group settings (basic)
Values (Range)

Unit

tStartMove

0.000 - 60.000

Step
0.001

0.100

Supervision time for the apparatus to


move after a command

tIntermediate

0.000 - 60.000

0.001

0.150

Allowed time for intermediate position

AdaptivePulse

Not adaptive
Adaptive

Not adaptive

Output resets when a new correct end


position is reached

tOpenPulse

0.000 - 60.000

0.001

0.200

Output pulse length for open command

tClosePulse

0.000 - 60.000

0.001

0.200

Output pulse length for close command

SuppressMidPos

Off
On

On

Mid-position is suppressed during the


time tIntermediate

12.3.8

Circuit switch SXSWI

12.3.8.1

Introduction

Default

Description

The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or earthing switches via output
boards and to supervise the switching operation and position.

12.3.8.2

Principle of operation
The users of the Circuit switch (SXSWI) is other functions such as for example,
switch controller, protection functions, autorecloser function, or a 61850 client
residing in another IED or the operator place. SXSWI executes commands,
evaluates block conditions and evaluates different time supervision conditions.
Only if all conditions indicate a switch operation to be allowed, SXSWI performs
the execution command. In case of erroneous conditions, the function indicates an
appropriate "cause" value.

608
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a
binary input or remotely from the operator place by configuring a signal from the
Single Point Generic Control 8 signals (SPC8GGIO) for example.

Local/Remote switch

One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If
the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in
figure 341.

From I/O

E
RU

Local= Operation at
switch yard level

switchLR
FAL

SE

Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN

Figure 341:

Local/Remote switch

Blocking principles

SXSWI includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example,
operators place, protection functions, autorecloser and so on.
The blocking possibilities are:

Block/deblock for open command. It is used to block operation for open


command. Note that this block signal also affects the input OPEN for
immediate command.
Block/deblock for close command. It is used to block operation for close
command. Note that this block signal also affects the input CLOSE for
immediate command.
Update block/deblock of positions. It is used to block the updating of position
values. Other signals related to the position will be reset.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850). If DO Behavior is set to "blocked" it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

609
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Substitution

The substitution part in SXSWI is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because the real process value is erroneous of some reason. SXSWI will then use
the manually entered value instead of the value for positions determined by the
process.
It is always possible to make a substitution, independently of the
position indication and the status information of the I/O board.
When substitution is enabled, the position values are blocked for
updating and other signals related to the position are reset. The
substituted values are stored in a non-volatile memory.

Time diagrams

There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 342 explains these two timers during the execute phase.
AdaptivePulse = TRUE

EXE_CL
Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


"switch-not-start-moving"
attribute in 'cause' is set

tStartMove timer
t1
tStartMove

tIntermediate timer
t2

if t2 > tIntermediate then


"persisting-intermediate-state"
attribute in 'cause' is set

tIntermediate
en05000097.vsd
IEC05000097 V1 EN

Figure 342:

The timers tStartMove and tIntermediate

The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be
adaptive with the configuration parameter AdaptivePulse. Figure 343 shows the
principle of the execute output pulse. The AdaptivePulse parameter will have affect
on both execute output pulses.

610
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_CL
tClosePulse

AdaptivePulse=TRUE

EXE_CL
tClosePulse

en05000098.vsd
IEC05000098 V1 EN

Figure 343:

Execute output pulse

If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
The execute output pulses are reset when:
If the start position indicates bad state (OPENPOS=1 and
CLOSEPOS =1) when a command is executed the execute output
pulse resets only when timer tOpenPulse or tClosePulse has elapsed.

the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.

There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close
position and a close command is executed. In these cases, with the additional
condition that the configuration parameter AdaptivePulse is true, the execute output
pulse is always activated and resets when tStartMove has elapsed. If the
configuration parameter AdaptivePulse is set to false the execution output remains
active until the pulse duration timer has elapsed.
An example when a primary device is open and an open command is executed is
shown in figure 344.

611
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE

EXE_OP
tOpenPulse

AdaptivePulse=TRUE

EXE_OP
tOpenPulse
tStartMove timer

en05000099.vsd
IEC05000099 V1 EN

Figure 344:

12.3.8.3

Open command with open position indication

Function block
SXSWI
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
RS_CNT
XIN

XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
IEC05000339-2-en.vsd

IEC05000339 V2 EN

Figure 345:

12.3.8.4

SXSWI function block

Input and output signals


Table 341:
Name

SXSWI Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

LR_SWI

BOOLEAN

Local/Remote switch indication from switchyard

OPEN

BOOLEAN

Pulsed signal used to immediately open the switch

CLOSE

BOOLEAN

Pulsed signal used to immediately close the switch

BL_OPEN

BOOLEAN

Signal to block the open command

BL_CLOSE

BOOLEAN

Signal to block the close command

BL_UPD

BOOLEAN

Steady signal for block of the position updating

POSOPEN

BOOLEAN

Signal for open position of apparatus from I/O

Table continues on next page


612
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Signal for close position of apparatus from I/O

RS_CNT

BOOLEAN

Resets the operation counter

XIN

BOOLEAN

Execution information from CSWI

SXSWI Output signals

Name

Table 343:

Description

BOOLEAN

Table 342:

12.3.8.5

Default

POSCLOSE

Type

Description

XPOS

GROUP SIGNAL

Group signal for XSWI output

EXE_OP

BOOLEAN

Executes the command for open direction

EXE_CL

BOOLEAN

Executes the command for close direction

SUBSTED

BOOLEAN

Indication that the position is substituted

OP_BLKD

BOOLEAN

Indication that the function is blocked for open


commands

CL_BLKD

BOOLEAN

Indication that the function is blocked for close


commands

UPD_BLKD

BOOLEAN

Update of position indication is blocked

POSITION

INTEGER

Apparatus position indication

OPENPOS

BOOLEAN

Apparatus open position

CLOSEPOS

BOOLEAN

Apparatus closed position

CNT_VAL

INTEGER

Operation counter value

L_CAUSE

INTEGER

Latest value of the error indication during command

Setting parameters
SXSWI Non group settings (basic)

Name

Values (Range)

Unit

tStartMove

0.000 - 60.000

0.001

3.000

Supervision time for the apparatus to


move after a command

tIntermediate

0.000 - 60.000

0.001

15.000

Allowed time for intermediate position

AdaptivePulse

Not adaptive
Adaptive

Not adaptive

Output resets when a new correct end


position is reached

tOpenPulse

0.000 - 60.000

0.001

0.200

Output pulse length for open command

tClosePulse

0.000 - 60.000

0.001

0.200

Output pulse length for close command

SwitchType

Load Break
Disconnector
Earthing Switch
HS Earthing Switch

Disconnector

1=LoadBreak,2=Disconnector,
3=EarthSw,4=HighSpeedEarthSw

SuppressMidPos

Off
On

On

Mid-position is suppressed during the


time tIntermediate

12.3.9

Step

Default

Description

Bay reserve QCRSV

613
Technical reference manual

Section 12
Control
12.3.9.1

1MRK 505 222-UEN B

Introduction
The purpose of the reservation function is primarily to transfer interlocking
information between IEDs in a safe way and to prevent double operation in a bay,
switchyard part, or complete substation.

12.3.9.2

Principle of operation
The Bay reserve (QCRSV) function handles the reservation. QCRSV function
starts to operate in two ways. It starts when there is a request for reservation of the
own bay or if there is a request for reservation from another bay. It is only possible
to reserve the function if it is not currently reserved. The signal that can reserve the
own bay is the input signal RES_RQx (x=1-8) coming from switch controller
(SCWI). The signals for request from another bay are the outputs RE_RQ_B and
V_RE_RQ from function block RESIN. These signals are included in signal
EXCH_OUT from RESIN and are connected to RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay
only (TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.

Reservation request of own bay

If the reservation request comes from the own bay, the function QCRSV has to
know which apparatus the request comes from. This information is available with
the input signal RES_RQx and parameter ParamRequestx (where x=1-8 is the
number of the requesting apparatus). In order to decide if a reservation request of
the current bay can be permitted QCRSV has to know whether the own bay already
is reserved by itself or another bay. This information is available in the output
signal RESERVED.
If the RESERVED output is not set, the selection is made with the output
RES_GRTx (where x=1-8 is the number of the requesting apparatus), which is
connected to switch controller SCSWI. If the bay already is reserved the command
sequence will be reset and the SCSWI will set the attribute "1-of-n-control" in the
"cause" signal.

Reservation of other bays

When the function QCRSV receives a request from an apparatus in the own bay
that requires other bays to be reserved as well, it checks if it already is reserved. If
not, it will send a request to the other bays that are predefined (to be reserved) and
wait for their response (acknowledge). The request of reserving other bays is done
by activating the output RES_BAYS.
When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-ncontrol" in the "cause" signal.

614
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Reservation request from another bay

When another bay requests for reservation, the input BAY_RES in corresponding
function block RESIN is activated. The signal for reservation request is grouped
into the output signal EXCH_OUT in RESIN, which is connected to input
RES_DATA in QCRSV. If the bay is not reserved, the bay will be reserved and the
acknowledgment from output ACK_T_B is sent back to the requested bay. If the
bay already is reserved the reservation is kept and no acknowledgment is sent.

Blocking and overriding of reservation

If QCRSV function is blocked (input BLK_RES is set to true) the reservation is


blocked. That is, no reservation can be made from the own bay or any other bay.
This can be set, for example, via a binary input from an external device to prevent
operations from another operator place at the same time.
The reservation function can also be overridden in the own bay with the
OVERRIDE input signal, that is, reserving the own bay without waiting for the
external acknowledge.

Bay with more than eight apparatuses

If only one instance of QCRSV is used for a bay that is, use of up to eight
apparatuses, the input EXCH_IN must be set to FALSE.
If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The two QCRSV functions have to communicate and this is done through
the input EXCH_IN and EXCH_OUT according to figure 346. If more then one
QCRSV are used, the execution order is very important. The execution order must
be in the way that the first QCRSV has a lower number than the next one.

615
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QCRSV
EXCH_IN
RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES
ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

QCRSV
EXCH_IN
RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES
ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT

RES_BAYS

ACK_TO_B

RESERVED

IEC05000088_2_en.vsd
IEC05000088 V2 EN

Figure 346:

12.3.9.3

Connection of two QCRSV function blocks

Function block
QCRSV
EXCH_IN
RES_RQ1
RES_RQ2
RES_RQ3
RES_RQ4
RES_RQ5
RES_RQ6
RES_RQ7
RES_RQ8
BLK_RES
OVERRIDE
RES_DATA

RES_GRT1
RES_GRT2
RES_GRT3
RES_GRT4
RES_GRT5
RES_GRT6
RES_GRT7
RES_GRT8
RES_BAYS
ACK_TO_B
RESERVED
EXCH_OUT
IEC05000340-2-en.vsd

IEC05000340 V2 EN

Figure 347:

QCRSV function block

616
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.3.9.4

Input and output signals


Table 344:
Name

QCRSV Input signals


Type

Default

Description

EXCH_IN

INTEGER

Used for exchange signals between different


BayRes blocks

RES_RQ1

BOOLEAN

Signal for app. 1 that requests to do a reservation

RES_RQ2

BOOLEAN

Signal for app. 2 that requests to do a reservation

RES_RQ3

BOOLEAN

Signal for app. 3 that requests to do a reservation

RES_RQ4

BOOLEAN

Signal for app. 4 that requests to do a reservation

RES_RQ5

BOOLEAN

Signal for app. 5 that requests to do a reservation

RES_RQ6

BOOLEAN

Signal for app. 6 that requests to do a reservation

RES_RQ7

BOOLEAN

Signal for app. 7 that requests to do a reservation

RES_RQ8

BOOLEAN

Signal for app. 8 that requests to do a reservation

BLK_RES

BOOLEAN

Reservation is not possible and the output signals


are reset

OVERRIDE

BOOLEAN

Signal to override the reservation

RES_DATA

INTEGER

Reservation data coming from function block ResIn

Table 345:
Name

QCRSV Output signals


Type

Description

RES_GRT1

BOOLEAN

Reservation is made and the app. 1 is allowed to


operate

RES_GRT2

BOOLEAN

Reservation is made and the app. 2 is allowed to


operate

RES_GRT3

BOOLEAN

Reservation is made and the app. 3 is allowed to


operate

RES_GRT4

BOOLEAN

Reservation is made and the app. 4 is allowed to


operate

RES_GRT5

BOOLEAN

Reservation is made and the app. 5 is allowed to


operate

RES_GRT6

BOOLEAN

Reservation is made and the app. 6 is allowed to


operate

RES_GRT7

BOOLEAN

Reservation is made and the app. 7 is allowed to


operate

RES_GRT8

BOOLEAN

Reservation is made and the app. 8 is allowed to


operate

RES_BAYS

BOOLEAN

Request for reservation of other bays

ACK_TO_B

BOOLEAN

Acknowledge to other bays that this bay is reserved

RESERVED

BOOLEAN

Indicates that the bay is reserved

EXCH_OUT

INTEGER

Used for exchange signals between different


BayRes blocks

617
Technical reference manual

Section 12
Control
12.3.9.5
Table 346:
Name

1MRK 505 222-UEN B

Setting parameters
QCRSV Non group settings (basic)
Values (Range)

Unit

tCancelRes

0.000 - 60.000

Step
0.001

Default
10.000

Supervision time for canceling the


reservation

ParamRequest1

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 1

ParamRequest2

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 2

ParamRequest3

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 3

ParamRequest4

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 4

ParamRequest5

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 5

ParamRequest6

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 6

ParamRequest7

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 7

ParamRequest8

Other bays res.


Only own bay res.

Only own bay res.

Reservation of the own bay only, at


selection of apparatus 8

12.3.10

Reservation input RESIN

12.3.10.1

Introduction

Description

The Reservation input (RESIN) function receives the reservation information from
other bays. The number of instances is the same as the number of involved bays
(up to 60 instances are available).

12.3.10.2

Principle of operation
The reservation input (RESIN) function is based purely on Boolean logic
conditions. The logic diagram in figure 348 shows how the output signals are
created. The inputs of the function block are connected to a receive function block
representing signals transferred over the station bus from another bay.

618
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

EXCH_IN

INT
BIN

ACK_F_B

&
FutureUse

BAY_ACK

1
ANY_ACK

VALID_TX

&
BAY_VAL

1
RE_RQ_B

BAY_RES

&
V _RE_RQ

BIN

EXCH_OUT
INT

en05000089.vsd
IEC05000089 V1 EN

Figure 348:

Logic diagram for RESIN

Figure 349 describes the principle of the data exchange between all RESIN
modules in the current bay. There is one RESIN function block per "other bay"
used in the reservation mechanism. The output signal EXCH_OUT in the last
RESIN functions are connected to the module bay reserve (QCRSV) that handles
the reservation function in the own bay. The value to the input EXCH_IN on the
first RESIN module in the chain has the integer value 5. This is provided by the use
of instance number one of the function block RESIN, where the input EXCH_IN is
set to #5, but is hidden for the user.

619
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

RESIN
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT

Bay 1

Bay 2

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

Bay n

RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT

QCRSV
RES_DATA

en05000090.vsd
IEC05000090 V2 EN

Figure 349:

12.3.10.3

Diagram of the chaining principle for RESIN

Function block
RESIN1
BAY_ACK
BAY_VAL
BAY_RES

ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC05000341-2-en.vsd

IEC05000341 V2 EN

Figure 350:

RESIN1 function block

RESIN2
EXCH_IN
BAY_ACK
BAY_VAL
BAY_RES

ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd

IEC09000807 V1 EN

Figure 351:

RESIN2 function block

620
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.3.10.4

Input and output signals


Table 347:
Name

RESIN1 Input signals


Type

Default

Description

BAY_ACK

BOOLEAN

Another bay has acknow. the reservation req.


from this bay

BAY_VAL

BOOLEAN

The reserv. and acknow. signals from another


bay are valid

BAY_RES

BOOLEAN

Request from other bay to reserve this bay

Table 348:
Name

RESIN1 Output signals


Type

Description

ACK_F_B

BOOLEAN

All other bays have acknow. the reserv. req. from


this bay

ANY_ACK

BOOLEAN

Any other bay has acknow. the reserv. req. from


this bay

VALID_TX

BOOLEAN

The reserv. and acknow. signals from other bays


are valid

RE_RQ_B

BOOLEAN

Request from other bay to reserve this bay

V_RE_RQ

BOOLEAN

Check if the request of reserving this bay is valid

EXCH_OUT

INTEGER

Used for exchange signals between different


ResIn blocks

Table 349:
Name

RESIN2 Input signals


Type

Default

Description

EXCH_IN

INTEGER

Used for exchange signals between different


ResIn blocks

BAY_ACK

BOOLEAN

Another bay has acknow. the reservation req.


from this bay

BAY_VAL

BOOLEAN

The reserv. and acknow. signals from another


bay are valid

BAY_RES

BOOLEAN

Request from other bay to reserve this bay

Table 350:
Name

RESIN2 Output signals


Type

Description

ACK_F_B

BOOLEAN

All other bays have acknow. the reserv. req. from


this bay

ANY_ACK

BOOLEAN

Any other bay has acknow. the reserv. req. from


this bay

VALID_TX

BOOLEAN

The reserv. and acknow. signals from other bays


are valid

RE_RQ_B

BOOLEAN

Request from other bay to reserve this bay

V_RE_RQ

BOOLEAN

Check if the request of reserving this bay is valid

EXCH_OUT

INTEGER

Used for exchange signals between different


ResIn blocks

621
Technical reference manual

Section 12
Control
12.3.10.5
Table 351:
Name
FutureUse

Table 352:
Name
FutureUse

1MRK 505 222-UEN B

Setting parameters
RESIN1 Non group settings (basic)
Values (Range)
Bay in use
Bay future use

Unit
-

Step
-

Default
Bay in use

Description
The bay for this ResIn block is for future
use

RESIN2 Non group settings (basic)


Values (Range)
Bay in use
Bay future use

Unit
-

12.4

Interlocking

12.4.1

Introduction

Step
-

Default
Bay in use

Description
The bay for this ResIn block is for future
use

The interlocking functionality blocks the possibility to operate high-voltage


switching devices, for instance when a disconnector is under load, in order to
prevent material damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The interlocking functionality in each
IED is not dependent on any central function. For the station-wide interlocking, the
IEDs communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the
system at any given time.

12.4.2

Principle of operation
The interlocking function consists of software modules located in each control
IED. The function is distributed and not dependent on any central function.
Communication between modules in different bays is performed via the station bus.
The reservation function (see section "Introduction") is used to ensure that HV
apparatuses that might affect the interlock are blocked during the time gap, which
arises between position updates. This can be done by means of the communication
system, reserving all HV apparatuses that might influence the interlocking
condition of the intended operation. The reservation is maintained until the
operation is performed.
After the selection and reservation of an apparatus, the function has complete data
on the status of all apparatuses in the switchyard that are affected by the selection.
Other operators cannot interfere with the reserved apparatus or the status of
switching devices that may affect it.

622
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a
bay. The interlocking logic in a module is different, depending on the bay function
and the switchyard arrangements, that is, double-breaker or 1 1/2 breaker bays have
different modules. Specific interlocking conditions and connections between
standard interlocking modules are performed with an engineering tool. Bay-level
interlocking signals can include the following kind of information:

Positions of HV apparatuses (sometimes per phase)


Valid positions (if evaluated in the control module)
External release (to add special conditions for release)
Line voltage (to block operation of line earthing switch)
Output signals to release the HV apparatus

The interlocking module is connected to the surrounding functions within a bay as


shown in figure 352.
Interlocking
modules in
other bays

Interlocking
module

Apparatus control
modules
SCILO

SCSWI

SXSWI

Apparatus control
modules
SCILO

SCSWI

SXCBR

Apparatus control
modules
en04000526.vsd

SCILO

SCSWI

SXSWI

IEC04000526 V1 EN

Figure 352:

Interlocking module on bay level

Bays communicate via the station bus and can convey information regarding the
following:

Unearthed busbars
Busbars connected together
Other bays connected to a busbar
Received data from other bays is valid

Figure 353 illustrates the data exchange principle.

623
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Station bus
Bay 1

Bay n

WA1 not earthed


WA2 not earthed
WA1 and WA2 interconn

Bus coupler

Disc QB1 and QB2 closed

Disc QB1 and QB2 closed

...
..

WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn

WA1 not earthed


WA2 not earthed
WA1 and WA2 interconn

WA1 and WA2 interconn


in other bay

WA1
WA2
QB1

QB2

QB1

QB2

QA1

QA1

QB9

QB9

QB2

QB1

QC1

QC2

QA1

en05000494.vsd
IEC05000494 V1 EN

Figure 353:

Data exchange between interlocking modules

When invalid data such as intermediate position, loss of a control IED, or input
board error are used as conditions for the interlocking condition in a bay, a release
for execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
For all interlocking modules these general rules apply:

The interlocking conditions for opening or closing of disconnectors and


earthing switches are always identical.
Earthing switches on the line feeder end, for example, rapid earthing switches,
are normally interlocked only with reference to the conditions in the bay where
they are located, not with reference to switches on the other side of the line. So
a line voltage indication may be included into line interlocking modules. If
there is no line voltage supervision within the bay, then the appropriate inputs
must be set to no voltage, and the operator must consider this when operating.
Earthing switches can only be operated on isolated sections for example,
without load/voltage. Circuit breaker contacts cannot be used to isolate a
section, that is, the status of the circuit breaker is irrelevant as far as the
earthing switch operation is concerned.
Disconnectors cannot break power current or connect different voltage
systems. Disconnectors in series with a circuit breaker can only be operated if
the circuit breaker is open, or if the disconnectors operate in parallel with other
closed connections. Other disconnectors can be operated if one side is
completely isolated, or if the disconnectors operate in parallel to other closed
connections, or if they are earthed on both sides.
Circuit breaker closing is only interlocked against running disconnectors in its
bay or additionally in a transformer bay against the disconnectors and earthing

624
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

switch on the other side of the transformer, if there is no disconnector between


CB and transformer.
Circuit breaker opening is only interlocked in a bus-coupler bay, if a bus bar
transfer is in progress.

To make the implementation of the interlocking function easier, a number of


standardized and tested software interlocking modules containing logic for the
interlocking conditions are available:

Line for double and transfer busbars, ABC_LINE


Bus for double and transfer busbars, ABC_BC
Transformer bay for double busbars, AB_TRAFO
Bus-section breaker for double busbars, A1A2_BS
Bus-section disconnector for double busbars, A1A2_DC
Busbar earthing switch, BB_ES
Double CB Bay, DB_BUS_A, DB_LINE, DB_BUS_B
1 1/2-CB diameter, BH_LINE_A, BH_CONN, BH_LINE_B

The interlocking conditions can be altered, to meet the customer specific


requirements, by adding configurable logic by means of the graphical configuration
tool PCM600. The inputs Qx_EXy on the interlocking modules are used to add
these specific conditions.
The input signals EXDU_xx shall be set to true if there is no transmission error at
the transfer of information from other bays. Required signals with designations
ending in TR are intended for transfer to other bays.

12.4.3

Logical node for interlocking SCILO

12.4.3.1

Introduction
The Logical node for interlocking SCILO function is used to enable a switching
operation if the interlocking conditions permit. SCILO function itself does not
provide any interlocking functionality. The interlocking conditions are generated in
separate function blocks containing the interlocking logic.

12.4.3.2

Logic diagram
The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals

625
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.
SCILO

POSOPEN
POSCLOSE

=1

EN_OPEN

&

>1
&

OPEN_EN
CLOSE_EN

&

EN_CLOSE

>1

&

en04000525.vsd

IEC04000525 V1 EN

Figure 354:

12.4.3.3

SCILO function logic diagram

Function block
SCILO
POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN

EN_OPEN
EN_CLOSE

IEC05000359-2-en.vsd
IEC05000359 V2 EN

Figure 355:

12.4.3.4

Input and output signals


Table 353:
Name

SCILO Input signals


Type

Default

Description

POSOPEN

BOOLEAN

Open position of switch device

POSCLOSE

BOOLEAN

Closed position of switch device

OPEN_EN

BOOLEAN

Open operation from interlocking logic is enabled

CLOSE_EN

BOOLEAN

Close operation from interlocking logic is enabled

Table 354:
Name

12.4.4

SCILO function block

SCILO Output signals


Type

Description

EN_OPEN

BOOLEAN

Open operation at closed or interm. or bad pos. is


enabled

EN_CLOSE

BOOLEAN

Close operation at open or interm. or bad pos. is


enabled

Interlocking for busbar earthing switch BB_ES

626
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.4.1

Introduction
The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure 356.

QC

en04000504.vsd
IEC04000504 V1 EN

Figure 356:

12.4.4.2

Switchyard layout BB_ES

Function block
BB_ES
QC_OP
QC_CL
BB_DC_OP
VP_BB_DC
EXDU_BB

QCREL
QCITL
BBESOPTR
BBESCLTR

IEC05000347-2-en.vsd
IEC05000347 V2 EN

Figure 357:

12.4.4.3

BB_ES function block

Logic diagram
BB_ES
VP_BB_DC
BB_DC_OP
EXDU_BB

&

QCREL
QCITL

QC_OP
QC_CL

BBESOPTR
BBESCLTR
en04000546.vsd

IEC04000546 V1 EN

12.4.4.4

Input and output signals


Table 355:
Name

BB_ES Input signals


Type

Default

Description

QC_OP

BOOLEAN

Busbar earthing switch QC is in open position

QC_CL

BOOLEAN

Busbar earthing switch QC is in closed position

BB_DC_OP

BOOLEAN

All disconnectors on this busbar part are open

VP_BB_DC

BOOLEAN

Status for all disconnectors on this busbar part


are valid

EXDU_BB

BOOLEAN

No transm error from bays with disc on this


busbar part

627
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 356:

BB_ES Output signals

Name

Type

Description

QCREL

BOOLEAN

Switching of QC is allowed

QCITL

BOOLEAN

Switching of QC is forbidden

BBESOPTR

BOOLEAN

QC on this busbar part is in open position

BBESCLTR

BOOLEAN

QC on this busbar part is in closed position

12.4.5

Interlocking for bus-section breaker A1A2_BS

12.4.5.1

Introduction
The interlocking for bus-section breaker (A1A2_BS) function is used for one bussection circuit breaker between section 1 and 2 according to figure 358. The
function can be used for different busbars, which includes a bus-section circuit
breaker.
WA2 (A2)

WA1 (A1)

QC1

QB1

QB2

QC2

QA1

QC3

QC4

A1A2_BS

en04000516.vsd

IEC04000516 V1 EN

Figure 358:

Switchyard layout A1A2_BS

628
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.5.2

Function block
QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QC3_OP
QC3_CL
QC4_OP
QC4_CL
S1QC1_OP
S1QC1_CL
S2QC2_OP
S2QC2_CL
BBTR_OP
VP_BBTR
EXDU_12
EXDU_ES
QA1O_EX1
QA1O_EX2
QA1O_EX3
QB1_EX1
QB1_EX2
QB2_EX1
QB2_EX2

A1A2_BS
QA1OPREL
QA1OPITL
QA1CLREL
QA1CLITL
QB1REL
QB1ITL
QB2REL
QB2ITL
QC3REL
QC3ITL
QC4REL
QC4ITL
S1S2OPTR
S1S2CLTR
QB1OPTR
QB1CLTR
QB2OPTR
QB2CLTR
VPS1S2TR
VPQB1TR
VPQB2TR

IEC05000348-2-en.vsd
IEC05000348 V2 EN

Figure 359:

A1A2_BS function block

629
Technical reference manual

Section 12
Control
12.4.5.3

1MRK 505 222-UEN B

Logic diagram
QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QC3_OP
QC3_CL
QC4_OP
QC4_CL
S1QC1_OP
S1QC1_CL
S2QC2_OP
S2QC2_CL
VPQB1
QB1_OP
QA1O_EX1
VPQB2
QB2_OP
QA1O_EX2
VP_BBTR
BBTR_OP
EXDU_12
QA1O_EX3
VPQB1
VPQB2
VPQA1
VPQC3
VPQC4
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1
VPQC3
VPS1QC1
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2

A1A2_BS
=1

VPQA1

=1

VPQB1

=1

VPQB2

=1

VPQC3

=1

VPQC4

=1

VPS1QC1

=1

VPS2QC2

&

>1
1

QA1OPREL
QA1OPITL

&
&

&
&

>1
1

QA1CLREL
QA1CLITL
QB1REL
QB1ITL

&

en04000542.vsd

IEC04000542 V1 EN

630
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQC3
VPQC4
VPS2QC2
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2
VPQB1
VPQB2
QB1_OP
QB2_OP

&

>1
1

QB2REL
QB2ITL

&

&

1
1

QC3REL
QC3ITL
QC4REL
QC4ITL

QB1_OP
QB1_CL
VPQB1

QB1OPTR
QB1CLTR
VPQB1TR

QB2_OP
QB2_CL
VPQB2

QB2OPTR
QB2CLTR
VPQB2TR

QB1_OP
QB2_OP
QA1_OP
VPQB1
VPQB2
VPQA1

>1

S1S2OPTR
S1S2CLTR
VPS1S2TR

&

en04000543.vsd

IEC04000543 V1 EN

12.4.5.4

Input and output signals


Table 357:
Name

A1A2_BS Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QC4_OP

BOOLEAN

QC4 is in open position

QC4_CL

BOOLEAN

QC4 is in closed position

S1QC1_OP

BOOLEAN

QC1 on bus section 1 is in open position

S1QC1_CL

BOOLEAN

QC1 on bus section 1 is in closed position

S2QC2_OP

BOOLEAN

QC2 on bus section 2 is in open position

S2QC2_CL

BOOLEAN

QC2 on bus section 2 is in closed position

BBTR_OP

BOOLEAN

No busbar transfer is in progress

VP_BBTR

BOOLEAN

Status are valid for app. involved in the busbar


transfer

Table continues on next page

631
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Default

Description

BOOLEAN

No transm error from any bay connected to


busbar 1 and 2

EXDU_ES

BOOLEAN

No transm error from bays containing earth. sw.


QC1 or QC2

QA1O_EX1

BOOLEAN

External open condition for apparatus QA1

QA1O_EX2

BOOLEAN

External open condition for apparatus QA1

QA1O_EX3

BOOLEAN

External open condition for apparatus QA1

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

Table 358:
Name

12.4.6

Type

EXDU_12

A1A2_BS Output signals


Type

Description

QA1OPREL

BOOLEAN

Opening of QA1 is allowed

QA1OPITL

BOOLEAN

Opening of QA1 is forbidden

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB1REL

BOOLEAN

Switching of QB1 is allowed

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QC3REL

BOOLEAN

Switching of QC3 is allowed

QC3ITL

BOOLEAN

Switching of QC3 is forbidden

QC4REL

BOOLEAN

Switching of QC4 is allowed

QC4ITL

BOOLEAN

Switching of QC4 is forbidden

S1S2OPTR

BOOLEAN

No bus section connection between bus section 1


and 2

S1S2CLTR

BOOLEAN

Bus coupler connection between bus section 1


and 2 exists

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

QB2OPTR

BOOLEAN

QB2 is in open position

QB2CLTR

BOOLEAN

QB2 is in closed position

VPS1S2TR

BOOLEAN

Status of the app. between bus section 1 and 2


are valid

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

VPQB2TR

BOOLEAN

Switch status of QB2 is valid (open or closed)

Interlocking for bus-section disconnector A1A2_DC

632
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.6.1

Introduction
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure 360.
A1A2_DC function can be used for different busbars, which includes a bus-section
disconnector.
QB
WA1 (A1)

WA2 (A2)

QC1

QC2

A1A2_DC

en04000492.vsd

IEC04000492 V1 EN

Figure 360:

12.4.6.2

Switchyard layout A1A2_DC

Function block
A1A2_DC
QB_OP
QBOPREL
QB_CL
QBOPITL
S1QC1_OP
QBCLREL
S1QC1_CL
QBCLITL
S2QC2_OP
DCOPTR
S2QC2_CL
DCCLTR
S1DC_OP
VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_ES
EXDU_BB
QBCL_EX1
QBCL_EX2
QBOP_EX1
QBOP_EX2
QBOP_EX3
IEC05000349-2-en.vsd
IEC05000349 V2 EN

Figure 361:

A1A2_DC function block

633
Technical reference manual

Section 12
Control
12.4.6.3

1MRK 505 222-UEN B

Logic diagram
A1A2_DC
QB_OP
QB_CL

=1

VPQB

VPDCTR
DCOPTR
DCCLTR

S1QC1_OP
S1QC1_CL
S2QC2_OP
S2QC2_CL
VPS1QC1
VPS2QC2
VPS1_DC
S1QC1_OP
S2QC2_OP
S1DC_OP
EXDU_ES

VPS1QC1

=1

VPS2QC2

=1

&

>1
1

QBOPREL
QBOPITL

EXDU_BB
QBOP_EX1
VPS1QC1
VPS2QC2
VPS2_DC
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES

&

EXDU_BB
QBOP_EX2
VPS1QC1
VPS2QC2
S1QC1_CL
S2QC2_CL
EXDU_ES
QBOP_EX3

&

en04000544.vsd

IEC04000544 V1 EN

IEC04000545 V1 EN

12.4.6.4

Input and output signals


Table 359:
Name

A1A2_DC Input signals


Type

Default

Description

QB_OP

BOOLEAN

QB is in open position

QB_CL

BOOLEAN

QB is in closed position

S1QC1_OP

BOOLEAN

QC1 on bus section 1 is in open position

S1QC1_CL

BOOLEAN

QC1 on bus section 1 is in closed position

Table continues on next page


634
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

S2QC2_OP

BOOLEAN

QC2 on bus section 2 is in open position

S2QC2_CL

BOOLEAN

QC2 on bus section 2 is in closed position

S1DC_OP

BOOLEAN

All disconnectors on bus section 1 are in open


position

S2DC_OP

BOOLEAN

All disconnectors on bus section 2 are in open


position

VPS1_DC

BOOLEAN

Switch status of disconnectors on bus section 1


are valid

VPS2_DC

BOOLEAN

Switch status of disconnectors on bus section 2


are valid

EXDU_ES

BOOLEAN

No transm error from bays containing earth. sw.


QC1 or QC2

EXDU_BB

BOOLEAN

No transm error from bays with disc conn to


section 1 and 2

QBCL_EX1

BOOLEAN

External close condition for section disconnector


QB

QBCL_EX2

BOOLEAN

External close condition for section disconnector


QB

QBOP_EX1

BOOLEAN

External open condition for section disconnector


QB

QBOP_EX2

BOOLEAN

External open condition for section disconnector


QB

QBOP_EX3

BOOLEAN

External open condition for section disconnector


QB

Table 360:
Name

A1A2_DC Output signals


Type

Description

QBOPREL

BOOLEAN

Opening of QB is allowed

QBOPITL

BOOLEAN

Opening of QB is forbidden

QBCLREL

BOOLEAN

Closing of QB is allowed

QBCLITL

BOOLEAN

Closing of QB is forbidden

DCOPTR

BOOLEAN

The bus section disconnector is in open position

DCCLTR

BOOLEAN

The bus section disconnector is in closed position

VPDCTR

BOOLEAN

Switch status of QB is valid (open or closed)

12.4.7

Interlocking for bus-coupler bay ABC_BC

12.4.7.1

Introduction
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 362. The
function can also be used for a single busbar arrangement with transfer busbar or
double busbar arrangement without transfer busbar.
635

Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

WA1 (A)
WA2 (B)
WA7 (C)
QB1

QB2

QB20

QB7

QC1
QA1

QC2

en04000514.vsd
IEC04000514 V1 EN

Figure 362:

12.4.7.2

Switchyard layout ABC_BC

Function block
ABC_BC
QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QB7_OP
QB7_CL
QB20_OP
QB20_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC11_OP
QC11_CL
QC21_OP
QC21_CL
QC71_OP
QC71_CL
BBTR_OP
BC_12_CL
VP_BBTR
VP_BC_12
EXDU_ES
EXDU_12
EXDU_BC
QA1O_EX1
QA1O_EX2
QA1O_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB20_EX1
QB20_EX2
QB7_EX1
QB7_EX2

QA1OPREL
QA1OPITL
QA1CLREL
QA1CLITL
QB1REL
QB1ITL
QB2REL
QB2ITL
QB7REL
QB7ITL
QB20REL
QB20ITL
QC1REL
QC1ITL
QC2REL
QC2ITL
QB1OPTR
QB1CLTR
QB220OTR
QB220CTR
QB7OPTR
QB7CLTR
QB12OPTR
QB12CLTR
BC12OPTR
BC12CLTR
BC17OPTR
BC17CLTR
BC27OPTR
BC27CLTR
VPQB1TR
VQB220TR
VPQB7TR
VPQB12TR
VPBC12TR
VPBC17TR
VPBC27TR

IEC05000350-2-en.vsd
IEC05000350 V2 EN

Figure 363:

ABC_BC function block

636
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.7.3

Logic diagram
QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB20_OP
QB20_CL
QB7_OP
QB7_CL
QB2_OP
QB2_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC11_OP
QC11_CL
QC21_OP
QC21_CL
QC71_OP
QC71_CL
VPQB1
QB1_OP
QA1O_EX1
VPQB20
QB20_OP
QA1O_EX2
VP_BBTR
BBTR_OP
EXDU_12

ABC_BC
=1

VPQA1

=1

VPQB1

=1

VPQB20

=1

VPQB7

=1

VPQB2

=1

VPQC1

=1

VPQC2

=1

VPQC11

=1

VPQC21

=1

VPQC71

&

QA1OPREL
QA1OPITL

>1
1

&
&

QA1O_EX3
VPQB1
VPQB2
VPQB7
VPQB20

&

QA1CLREL
QA1CLITL

en04000533.vsd

IEC04000533 V1 EN

VPQA1
VPQB2
VPQC1
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3

&

>1
1

QB1REL
QB1ITL

&

&

en04000534.vsd

IEC04000534 V1 EN

637
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQB1
VPQC1
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3

&

>1
1

QB2REL
QB2ITL

&

&

en04000535.vsd

IEC04000535 V1 EN

VPQA1
VPQB20
VPQC1
VPQC2
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7
VPQC1
VPQC2
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2

&

>1
1

QB7REL
QB7ITL

&

&

>1
1

QB20REL
QB20ITL

&

en04000536.vsd

IEC04000536 V1 EN

638
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQB1
VPQB20
VPQB7
VPQB2
QB1_OP
QB20_OP
QB7_OP
QB2_OP
QB1_OP
QB1_CL
VPQB1
QB20_OP
QB2_OP
VPQB20
VPQB2
QB7_OP
QB7_CL
VPQB7
QB1_OP
QB2_OP
VPQB1
VPQB2
QA1_OP
QB1_OP
QB20_OP
VPQA1
VPQB1
VPQB20
QA1_OP
QB1_OP
QB7_OP
VPQA1
VPQB1
VPQB7
QA1_OP
QB2_OP
QB7_OP
VPQA1
VPQB2
VPQB7

&

1
1

&

&

>1

&
>1

QC1REL
QC1ITL
QC2REL
QC2ITL

QB1OPTR
QB1CLTR
VPQB1TR
QB220OTR
QB220CTR
VQB220TR
QB7OPTR
QB7CLTR
VPQB7TR
QB12OPTR
QB12CLTR
VPQB12TR
BC12OPTR
BC12CLTR
VPBC12TR

&
>1

BC17OPTR
BC17CLTR
VPBC17TR

&
>1

BC27OPTR
BC27CLTR
VPBC27TR

&

en04000537.vsd

IEC04000537 V1 EN

12.4.7.4

Input and output signals


Table 361:
Name

ABC_BC Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QB7_OP

BOOLEAN

QB7 is in open position

QB7_CL

BOOLEAN

QB7 is in closed position

QB20_OP

BOOLEAN

QB20 is in open position

QB20_CL

BOOLEAN

QB20 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QC11_OP

BOOLEAN

Earthing switch QC11 on busbar WA1 is in open


position

Table continues on next page

639
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QC11_CL

BOOLEAN

Earthing switch QC11 on busbar WA1 is in closed


position

QC21_OP

BOOLEAN

Earthing switch QC21 on busbar WA2 is in open


position

QC21_CL

BOOLEAN

Earthing switch QC21 on busbar WA2 is in closed


position

QC71_OP

BOOLEAN

Earthing switch QC71 on busbar WA7 is in open


position

QC71_CL

BOOLEAN

Earthing switch QC71 on busbar WA7 is in closed


position

BBTR_OP

BOOLEAN

No busbar transfer is in progress

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar


WA1 and WA2

VP_BBTR

BOOLEAN

Status are valid for app. involved in the busbar


transfer

VP_BC_12

BOOLEAN

Status of the bus coupler app. between WA1 and


WA2 are valid

EXDU_ES

BOOLEAN

No transm error from any bay containing earthing


switches

EXDU_12

BOOLEAN

No transm error from any bay connected to WA1/


WA2 busbars

EXDU_BC

BOOLEAN

No transmission error from any other bus coupler


bay

QA1O_EX1

BOOLEAN

External open condition for apparatus QA1

QA1O_EX2

BOOLEAN

External open condition for apparatus QA1

QA1O_EX3

BOOLEAN

External open condition for apparatus QA1

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

QB1_EX3

BOOLEAN

External condition for apparatus QB1

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

QB2_EX3

BOOLEAN

External condition for apparatus QB2

QB20_EX1

BOOLEAN

External condition for apparatus QB20

QB20_EX2

BOOLEAN

External condition for apparatus QB20

QB7_EX1

BOOLEAN

External condition for apparatus QB7

QB7_EX2

BOOLEAN

External condition for apparatus QB7

Table 362:
Name

ABC_BC Output signals


Type

Description

QA1OPREL

BOOLEAN

Opening of QA1 is allowed

QA1OPITL

BOOLEAN

Opening of QA1 is forbidden

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

Table continues on next page

640
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Description

QB1REL

BOOLEAN

Switching of QB1 is allowed

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QB7REL

BOOLEAN

Switching of QB7 is allowed

QB7ITL

BOOLEAN

Switching of QB7 is forbidden

QB20REL

BOOLEAN

Switching of QB20 is allowed

QB20ITL

BOOLEAN

Switching of QB20 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

QB220OTR

BOOLEAN

QB2 and QB20 are in open position

QB220CTR

BOOLEAN

QB2 or QB20 or both are not in open position

QB7OPTR

BOOLEAN

QB7 is in open position

QB7CLTR

BOOLEAN

QB7 is in closed position

QB12OPTR

BOOLEAN

QB1 or QB2 or both are in open position

QB12CLTR

BOOLEAN

QB1 and QB2 are not in open position

BC12OPTR

BOOLEAN

No connection via the own bus coupler between


WA1 and WA2

BC12CLTR

BOOLEAN

Conn. exists via the own bus coupler between


WA1 and WA2

BC17OPTR

BOOLEAN

No connection via the own bus coupler between


WA1 and WA7

BC17CLTR

BOOLEAN

Conn. exists via the own bus coupler between


WA1 and WA7

BC27OPTR

BOOLEAN

No connection via the own bus coupler between


WA2 and WA7

BC27CLTR

BOOLEAN

Conn. exists via the own bus coupler between


WA2 and WA7

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

VQB220TR

BOOLEAN

Switch status of QB2 and QB20 are valid (open


or closed)

VPQB7TR

BOOLEAN

Switch status of QB7 is valid (open or closed)

VPQB12TR

BOOLEAN

Switch status of QB1 and QB2 are valid (open or


closed)

VPBC12TR

BOOLEAN

Status of the bus coupler app. between WA1 and


WA2 are valid

VPBC17TR

BOOLEAN

Status of the bus coupler app. between WA1 and


WA7 are valid

VPBC27TR

BOOLEAN

Status of the bus coupler app. between WA2 and


WA7 are valid

641
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.8

Interlocking for 1 1/2 CB BH

12.4.8.1

Introduction
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,
BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter
according to figure 364.
WA1 (A)
WA2 (B)
QB2

QB1
QC1

QC1

QA1

QA1
QC2

QC2

QB6

QB6
QC3

BH_LINE_A

QC3

QB61

QA1

BH_LINE_B

QB62

QB9

QB9
QC1

QC2

QC9

QC9

BH_CONN
en04000513.vsd
IEC04000513 V1 EN

Figure 364:

Switchyard layout 1 1/2 breaker

Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the 1 1/2 breaker switchyard
layout.

642
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.8.2

Function blocks
BH_LINE_A
QA1_OP
QA1CLREL
QA1_CL
QA1CLITL
QB6_OP
QB6REL
QB6_CL
QB6ITL
QB1_OP
QB1REL
QB1_CL
QB1ITL
QC1_OP
QC1REL
QC1_CL
QC1ITL
QC2_OP
QC2REL
QC2_CL
QC2ITL
QC3_OP
QC3REL
QC3_CL
QC3ITL
QB9_OP
QB9REL
QB9_CL
QB9ITL
QC9_OP
QC9REL
QC9_CL
QC9ITL
CQA1_OP
QB1OPTR
CQA1_CL
QB1CLTR
CQB61_OP
VPQB1TR
CQB61_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB1_EX1
QB1_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000352-2-en.vsd
IEC05000352 V2 EN

Figure 365:

BH_LINE_A function block

643
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

BH_LINE_B
QA1_OP
QA1CLREL
QA1_CL
QA1CLITL
QB6_OP
QB6REL
QB6_CL
QB6ITL
QB2_OP
QB2REL
QB2_CL
QB2ITL
QC1_OP
QC1REL
QC1_CL
QC1ITL
QC2_OP
QC2REL
QC2_CL
QC2ITL
QC3_OP
QC3REL
QC3_CL
QC3ITL
QB9_OP
QB9REL
QB9_CL
QB9ITL
QC9_OP
QC9REL
QC9_CL
QC9ITL
CQA1_OP
QB2OPTR
CQA1_CL
QB2CLTR
CQB62_OP
VPQB2TR
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
IEC05000353-2-en.vsd
IEC05000353 V2 EN

Figure 366:

QA1_OP
QA1_CL
QB61_OP
QB61_CL
QB62_OP
QB62_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2

BH_LINE_B function block

BH_CONN
QA1CLREL
QA1CLITL
QB61REL
QB61ITL
QB62REL
QB62ITL
QC1REL
QC1ITL
QC2REL
QC2ITL

IEC05000351-2-en.vsd
IEC05000351 V2 EN

Figure 367:

BH_CONN function block

644
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.8.3

Logic diagrams
QA1_OP
QA1_CL
QB61_OP
QB61_CL
QB62_OP
QB62_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
VPQB61
VPQB62
VPQA1
VPQC1
VPQC2
VP1QC3
QA1_OP
QC1_OP
QC2_OP
1QC3_OP
QB61_EX1
VPQC1
VP1QC3
QC1_CL
1QC3_CL
QB61_EX2
VPQA1
VPQC1
VPQC2
VP2QC3
QA1_OP
QC1_OP
QC2_OP
2QC3_OP
QB62_EX1
VPQC2
VP2QC3
QC2_CL
2QC3_CL
QB62_EX2
VPQB61
VPQB62
QB61_OP
QB62_OP

BH_CONN
=1

VPQA1

=1

VPQB61

=1

VPQB62

=1

VPQC1

=1

VPQC2

=1

VP1QC3

=1

VP2QC3
QA1CLREL
QA1CLITL

&
&

>1
1

QB61REL
QB61ITL

&

&

>1
1

QB62REL
QB62ITL

&

&

1
1

QC1REL
QC1ITL
QC2REL
QC2ITL
en04000560.vsd

IEC04000560 V1 EN

645
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB6_OP
QB6_CL
QC9_OP
QC9_CL
QB9_OP
QB9_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC3_OP
QC3_CL
CQA1_OP
CQA1_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
CQB61_OP
CQB61_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
VPQB1
VPQB6
VPQB9
VPQA1
VPQC1
VPQC2
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
QC2_CL
QC3_CL
QB6_EX2

BH_LINE_A
=1

VPQA1

=1

VPQB1

=1

VPQB6

=1

VPQC9

=1

VPQB9

=1

VPQC1

=1

VPQC2

=1

VPQC3

=1

VPCQA1

=1

VPCQC1

=1

VPCQC2

=1

VPCQB61

=1

VPQC11

=1

VPVOLT
QA1CLREL
QA1CLITL

&
&

>1
1

QB6REL
QB6ITL

&

en04000554.vsd

IEC04000554 V1 EN

646
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQC1
VPQC2
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
VPQB1
VPQB6
QB1_OP
QB6_OP
VPQB6
VPQB9
VPCQB61
QB6_OP
QB9_OP
CQB61_OP
VPQA1
VPQB6
VPQC9
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
QA1_OP
QC1_OP
QC2_OP
QB9_EX3

&

QB1REL
QB1ITL

>1
1

&

&

QC1REL
QC1ITL
QC2REL
QC2ITL

1
1

QC3REL
QC3ITL

&
1

&

>1

QB9REL
QB9ITL

>1
&

en04000555.vsd

IEC04000555 V1 EN

CQB61_OP
QB9_EX4
CQA1_OP
CQC1_OP
CQC2_OP
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
QC9_CL
QC3_CL
QB9_EX7
VPQB9
VPVOLT
QB9_OP
VOLT_OFF
QB1_OP
QB1_CL
VPQB1

>1

&

>1

&

&

&

QC9REL
QC9ITL
QB1OPTR
QB1CLTR
VPQB1TR
en04000556.vsd

IEC04000556 V1 EN

647
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QA1_OP
QA1_CL
QB2_OP
QB2_CL
QB6_OP
QB6_CL
QC9_OP
QC9_CL
QB9_OP
QB9_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC3_OP
QC3_CL
CQA1_OP
CQA1_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
CQB62_OP
CQB62_CL
QC21_OP
QC21_CL
VOLT_OFF
VOLT_ON
VPQB2
VPQB6
VPQB9
VPQA1
VPQC1
VPQC2
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
QC2_CL
QC3_CL
QB6_EX2

BH_LINE_B
=1

VPQA1

=1

VPQB2

=1

VPQB6

=1

VPQC9

=1

VPQB9

=1

VPQC1

=1

VPQC2

=1

VPQC3

=1

VPCQA1

=1

VPCQC1

=1

VPCQC2

=1

VPCQB62

=1

VPQC21

=1

VPVOLT
QA1CLREL
QA1CLITL

&
&

>1
1

QB6REL
QB6ITL

&

en04000557.vsd

IEC04000557 V1 EN

648
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQC1
VPQC2
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC1
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2
VPQB2
VPQB6
QB2_OP
QB6_OP
VPQB6
VPQB9
VPCQB62
QB6_OP
QB9_OP
CQB62_OP
VPQA1
VPQB6
VPQC9
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
QA1_OP
QC1_OP
QC2_OP
QB9_EX3

&

QB2REL
QB2ITL

>1
1

&

&

QC1REL
QC1ITL
QC2REL
QC2ITL

1
1

QC3REL
QC3ITL

&
1

&

>1

QB9REL
QB9ITL

>1
&

en04000558.vsd

IEC04000558 V1 EN

CQB62_OP
QB9_EX4
CQA1_OP
CQC1_OP
CQC2_OP
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
QC9_CL
QC3_CL
QB9_EX7
VPQB9
VPVOLT
QB9_OP
VOLT_OFF
QB2_OP
QB2_CL
VPQB2

>1

&

>1

&

&

&

QC9REL
QC9ITL
QB2OPTR
QB2CLTR
VPQB2TR
en04000559.vsd

IEC04000559 V1 EN

649
Technical reference manual

Section 12
Control
12.4.8.4

1MRK 505 222-UEN B

Input and output signals


Table 363:
Name

BH_LINE_A Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB6_OP

BOOLEAN

QB6 is in open position

QB6_CL

BOOLEAN

QB6 is in close position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QB9_OP

BOOLEAN

QB9 is in open position

QB9_CL

BOOLEAN

QB9 is in closed position

QC9_OP

BOOLEAN

QC9 is in open position

QC9_CL

BOOLEAN

QC9 is in closed position

CQA1_OP

BOOLEAN

QA1 in module BH_CONN is in open position

CQA1_CL

BOOLEAN

QA1 in module BH_CONN is in closed position

CQB61_OP

BOOLEAN

QB61 in module BH_CONN is in open position

CQB61_CL

BOOLEAN

QB61 in module BH_CONN is in closed position

CQC1_OP

BOOLEAN

QC1 in module BH_CONN is in open position

CQC1_CL

BOOLEAN

QC1 in module BH_CONN is in closed position

CQC2_OP

BOOLEAN

QC2 in module BH_CONN is in open position

CQC2_CL

BOOLEAN

QC2 in module BH_CONN is in closed position

QC11_OP

BOOLEAN

Earthing switch QC11 on busbar WA1 is in open


position

QC11_CL

BOOLEAN

Earthing switch QC11 on busbar WA1 is in closed


position

VOLT_OFF

BOOLEAN

There is no voltage on line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse)


failure

EXDU_ES

BOOLEAN

No transm error from bay containing earthing


switch QC11

QB6_EX1

BOOLEAN

External condition for apparatus QB6

QB6_EX2

BOOLEAN

External condition for apparatus QB6

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

QB9_EX1

BOOLEAN

External condition for apparatus QB9

Table continues on next page

650
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QB9_EX2

BOOLEAN

External condition for apparatus QB9

QB9_EX3

BOOLEAN

External condition for apparatus QB9

QB9_EX4

BOOLEAN

External condition for apparatus QB9

QB9_EX5

BOOLEAN

External condition for apparatus QB9

QB9_EX6

BOOLEAN

External condition for apparatus QB9

QB9_EX7

BOOLEAN

External condition for apparatus QB9

Table 364:
Name

BH_LINE_A Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB6REL

BOOLEAN

Switching of QB6 is allowed

QB6ITL

BOOLEAN

Switching of QB6 is forbidden

QB1REL

BOOLEAN

Switching of QB1 is allowed

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QC3REL

BOOLEAN

Switching of QC3 is allowed

QC3ITL

BOOLEAN

Switching of QC3 is forbidden

QB9REL

BOOLEAN

Switching of QB9 is allowed

QB9ITL

BOOLEAN

Switching of QB9 is forbidden

QC9REL

BOOLEAN

Switching of QC9 is allowed

QC9ITL

BOOLEAN

Switching of QC9 is forbidden

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

Table 365:
Name

BH_LINE_B Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB6_OP

BOOLEAN

QB6 is in open position

QB6_CL

BOOLEAN

QB6 is in close position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

Table continues on next page

651
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QB9_OP

BOOLEAN

QB9 is in open position

QB9_CL

BOOLEAN

QB9 is in closed position

QC9_OP

BOOLEAN

QC9 is in open position

QC9_CL

BOOLEAN

QC9 is in closed position

CQA1_OP

BOOLEAN

QA1 in module BH_CONN is in open position

CQA1_CL

BOOLEAN

QA1 in module BH_CONN is in closed position

CQB62_OP

BOOLEAN

QB62 in module BH_CONN is in open position

CQB62_CL

BOOLEAN

QB62 in module BH_CONN is in closed position

CQC1_OP

BOOLEAN

QC1 in module BH_CONN is in open position

CQC1_CL

BOOLEAN

QC1 in module BH_CONN is in closed position

CQC2_OP

BOOLEAN

QC2 in module BH_CONN is in open position

CQC2_CL

BOOLEAN

QC2 in module BH_CONN is in closed position

QC21_OP

BOOLEAN

Earthing switch QC21 on busbar WA2 is in open


position

QC21_CL

BOOLEAN

Earthing switch QC21 on busbar WA2 is in closed


position

VOLT_OFF

BOOLEAN

There is no voltage on line and not VT (fuse) failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse)


failure

EXDU_ES

BOOLEAN

No transm error from bay containing earthing


switch QC21

QB6_EX1

BOOLEAN

External condition for apparatus QB6

QB6_EX2

BOOLEAN

External condition for apparatus QB6

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

QB9_EX1

BOOLEAN

External condition for apparatus QB9

QB9_EX2

BOOLEAN

External condition for apparatus QB9

QB9_EX3

BOOLEAN

External condition for apparatus QB9

QB9_EX4

BOOLEAN

External condition for apparatus QB9

QB9_EX5

BOOLEAN

External condition for apparatus QB9

QB9_EX6

BOOLEAN

External condition for apparatus QB9

QB9_EX7

BOOLEAN

External condition for apparatus QB9

652
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 366:
Name

BH_LINE_B Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB6REL

BOOLEAN

Switching of QB6 is allowed

QB6ITL

BOOLEAN

Switching of QB6 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QC3REL

BOOLEAN

Switching of QC3 is allowed

QC3ITL

BOOLEAN

Switching of QC3 is forbidden

QB9REL

BOOLEAN

Switching of QB9 is allowed

QB9ITL

BOOLEAN

Switching of QB9 is forbidden

QC9REL

BOOLEAN

Switching of QC9 is allowed

QC9ITL

BOOLEAN

Switching of QC9 is forbidden

QB2OPTR

BOOLEAN

QB2 is in open position

QB2CLTR

BOOLEAN

QB2 is in closed position

VPQB2TR

BOOLEAN

Switch status of QB2 is valid (open or closed)

Table 367:
Name

BH_CONN Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB61_OP

BOOLEAN

QB61 is in open position

QB61_CL

BOOLEAN

QB61 is in closed position

QB62_OP

BOOLEAN

QB62 is in open position

QB62_CL

BOOLEAN

QB62 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

1QC3_OP

BOOLEAN

QC3 on line 1 is in open position

1QC3_CL

BOOLEAN

QC3 on line 1 is in closed position

2QC3_OP

BOOLEAN

QC3 on line 2 is in open position

2QC3_CL

BOOLEAN

QC3 on line 2 is in closed position

QB61_EX1

BOOLEAN

External condition for apparatus QB61

Table continues on next page

653
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QB61_EX2

BOOLEAN

External condition for apparatus QB61

QB62_EX1

BOOLEAN

External condition for apparatus QB62

QB62_EX2

BOOLEAN

External condition for apparatus QB62

Table 368:
Name

BH_CONN Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB61REL

BOOLEAN

Switching of QB61 is allowed

QB61ITL

BOOLEAN

Switching of QB61 is forbidden

QB62REL

BOOLEAN

Switching of QB62 is allowed

QB62ITL

BOOLEAN

Switching of QB62 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

12.4.9

Interlocking for double CB bay DB

12.4.9.1

Introduction
The interlocking for 1 1/2 breaker diameter including DB_BUS_A, DB_BUS_B,
DB_LINEfunctions are used for a line connected to a double circuit breaker
arrangement according to figure 368.

654
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

WA1 (A)
WA2 (B)
QB1

QB2
QC1

QA1

QC4
QA2
DB_BUS_B

DB_BUS_A
QC2
QB61

QC5
QB62
QC3

QB9

DB_LINE
QC9

en04000518.vsd
IEC04000518 V1 EN

Figure 368:

Switchyard layout double circuit breaker

Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A and DB_BUS_B are the connections from
the line to the busbars.

12.4.9.2

Function block
DB_BUS_A
QA1_OP
QA1CLREL
QA1_CL
QA1CLITL
QB1_OP
QB61REL
QB1_CL
QB61ITL
QB61_OP
QB1REL
QB61_CL
QB1ITL
QC1_OP
QC1REL
QC1_CL
QC1ITL
QC2_OP
QC2REL
QC2_CL
QC2ITL
QC3_OP
QB1OPTR
QC3_CL
QB1CLTR
QC11_OP
VPQB1TR
QC11_CL
EXDU_ES
QB61_EX1
QB61_EX2
QB1_EX1
QB1_EX2
IEC05000354-2-en.vsd
IEC05000354 V2 EN

Figure 369:

DB_BUS_A function block

655
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

DB_LINE
QA1_OP
QA1_CL
QA2_OP
QA2_CL
QB61_OP
QB61_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5

QB9REL
QB9ITL
QC3REL
QC3ITL
QC9REL
QC9ITL

IEC05000356-2-en.vsd
IEC05000356 V2 EN

Figure 370:

DB_LINE function block

DB_BUS_B
QA2_OP
QA2CLREL
QA2_CL
QA2CLITL
QB2_OP
QB62REL
QB2_CL
QB62ITL
QB62_OP
QB2REL
QB62_CL
QB2ITL
QC4_OP
QC4REL
QC4_CL
QC4ITL
QC5_OP
QC5REL
QC5_CL
QC5ITL
QC3_OP
QB2OPTR
QC3_CL
QB2CLTR
QC21_OP
VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2
IEC05000355-2-en.vsd
IEC05000355 V2 EN

Figure 371:

DB_BUS_B function block

656
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.9.3

Logic diagrams
QA1_OP
QA1_CL
QB61_OP
QB61_CL
QB1_OP
QB1_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC3_OP
QC3_CL
QC11_OP
QC11_CL
VPQB61
VPQB1
VPQA1
VPQC1
VPQC2
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB61_EX1
VPQC2
VPQC3
QC2_CL
QC3_CL
QB61_EX2
VPQA1
VPQC1
VPQC2
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2

DB_BUS_A
=1

VPQA1

=1

VPQB61

=1

VPQB1

=1

VPQC1

=1

VPQC2

=1

VPQC3

=1
&
&

>1
1

VPQC11
QA1CLREL
QA1CLITL
QB61REL
QB61ITL

&

&

>1
1

QB1REL
QB1ITL

&

en04000547.vsd

IEC04000547 V1 EN

VPQB61
VPQB1
QB61_OP
QB1_OP
QB1_OP
QB1_CL
VPQB1

&

1
1

QC1REL
QC1ITL
QC2REL
QC2ITL
QB1OPTR
QB1CLTR
VPQB1TR
en04000548.vsd

IEC04000548 V1 EN

657
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QA2_OP
QA2_CL
QB62_OP
QB62_CL
QB2_OP
QB2_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QC3_OP
QC3_CL
QC21_OP
QC21_CL
VPQB62
VPQB2
VPQA2
VPQC4
VPQC5
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4
VPQC5
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC4
VPQC21
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2

DB_BUS_B
=1

VPQA2

=1

VPQB62

=1

VPQB2

=1

VPQC4

=1

VPQC5
VPQC3

=1
=1
&
&

>1
1

VPQC21
QA2CLREL
QA2CLITL
QB62REL
QB62ITL

&

&

>1
1

QB2REL
QB2ITL

&

en04000552.vsd

IEC04000552 V1 EN

VPQB62
VPQB2
QB62_OP
QB2_OP
QB2_OP
QB2_CL
VPQB2

&

1
1

QC4REL
QC4ITL
QC5REL
QC5ITL
QB2OPTR
QB2CLTR
VPQB2TR
en04000553.vsd

IEC04000553 V1 EN

658
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QA1_OP
QA1_CL
QA2_OP
QA2_CL
QB61_OP
QB61_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
VPQA1
VPQA2
VPQC1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1

DB_LINE
=1

VPQA1

=1

VPQA2

=1

VPQB61

=1

VPQC1

=1

VPQC2

=1

VPQB62

=1

VPQC4

=1

VPQC5

=1

VPQB9

=1

VPQC3

=1

VPQC9

=1
&

VPVOLT
>1
1

&

QB9REL
QB9ITL

en04000549.vsd

IEC04000549 V1 EN

VPQA1
VPQC1
VPQC2
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
QC3_CL
QC9_CL
QB9_EX5

&

>1

&

&

&

en04000550.vsd

IEC04000550 V1 EN

659
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQB61
VPQB62
VPQB9
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT
QB9_OP
VOLT_OFF

&
1

&
1

QC3REL
QC3ITL

QC9REL
QC9ITL
en04000551.vsd

IEC04000551 V1 EN

12.4.9.4

Input and output signals


Table 369:
Name

DB_BUS_A Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QB61_OP

BOOLEAN

QB61 is in open position

QB61_CL

BOOLEAN

QB61 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QC11_OP

BOOLEAN

Earthing switch QC11 on busbar WA1 is in open


position

QC11_CL

BOOLEAN

Earthing switch QC11 on busbar WA1 is in closed


position

EXDU_ES

BOOLEAN

No transm error from bay containing earthing


switch QC11

QB61_EX1

BOOLEAN

External condition for apparatus QB61

QB61_EX2

BOOLEAN

External condition for apparatus QB61

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

Table 370:
Name

DB_BUS_A Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB61REL

BOOLEAN

Switching of QB61 is allowed

QB61ITL

BOOLEAN

Switching of QB61 is forbidden

QB1REL

BOOLEAN

Switching of QB1 is allowed

Table continues on next page


660
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Description

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

Table 371:
Name

DB_LINE Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QA2_OP

BOOLEAN

QA2 is in open position

QA2_CL

BOOLEAN

QA2 is in closed position

QB61_OP

BOOLEAN

QB61 is in open position

QB61_CL

BOOLEAN

QB61 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QB62_OP

BOOLEAN

QB62 is in open position

QB62_CL

BOOLEAN

QB62 is in closed position

QC4_OP

BOOLEAN

QC4 is in open position

QC4_CL

BOOLEAN

QC4 is in closed position

QC5_OP

BOOLEAN

QC5 is in open position

QC5_CL

BOOLEAN

QC5 is in closed position

QB9_OP

BOOLEAN

QB9 is in open position

QB9_CL

BOOLEAN

QB9 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QC9_OP

BOOLEAN

QC9 is in open position

QC9_CL

BOOLEAN

QC9 is in closed position

VOLT_OFF

BOOLEAN

There is no voltage on the line and not VT (fuse)


failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse)


failure

QB9_EX1

BOOLEAN

External condition for apparatus QB9

QB9_EX2

BOOLEAN

External condition for apparatus QB9

Table continues on next page

661
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QB9_EX3

BOOLEAN

External condition for apparatus QB9

QB9_EX4

BOOLEAN

External condition for apparatus QB9

QB9_EX5

BOOLEAN

External condition for apparatus QB9

Table 372:
Name

DB_LINE Output signals


Type

Description

QB9REL

BOOLEAN

Switching of QB9 is allowed

QB9ITL

BOOLEAN

Switching of QB9 is forbidden

QC3REL

BOOLEAN

Switching of QC3 is allowed

QC3ITL

BOOLEAN

Switching of QC3 is forbidden

QC9REL

BOOLEAN

Switching of QC9 is allowed

QC9ITL

BOOLEAN

Switching of QC9 is forbidden

Table 373:
Name

DB_BUS_B Input signals


Type

Default

Description

QA2_OP

BOOLEAN

QA2 is in open position

QA2_CL

BOOLEAN

QA2 is in closed position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QB62_OP

BOOLEAN

QB62 is in open position

QB62_CL

BOOLEAN

QB62 is in closed position

QC4_OP

BOOLEAN

QC4 is in open position

QC4_CL

BOOLEAN

QC4 is in closed position

QC5_OP

BOOLEAN

QC5 is in open position

QC5_CL

BOOLEAN

QC5 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QC21_OP

BOOLEAN

Earthing switch QC21 on busbar WA2 is in open


position

QC21_CL

BOOLEAN

Earthing switch QC21 on busbar WA2 is in closed


position

EXDU_ES

BOOLEAN

No transm error from bay containing earthing


switch QC21

QB62_EX1

BOOLEAN

External condition for apparatus QB62

QB62_EX2

BOOLEAN

External condition for apparatus QB62

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

662
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 374:

DB_BUS_B Output signals

Name

Type

Description

QA2CLREL

BOOLEAN

Closing of QA2 is allowed

QA2CLITL

BOOLEAN

Closing of QA2 is forbidden

QB62REL

BOOLEAN

Switching of QB62 is allowed

QB62ITL

BOOLEAN

Switching of QB62 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QC4REL

BOOLEAN

Switching of QC4 is allowed

QC4ITL

BOOLEAN

Switching of QC4 is forbidden

QC5REL

BOOLEAN

Switching of QC5 is allowed

QC5ITL

BOOLEAN

Switching of QC5 is forbidden

QB2OPTR

BOOLEAN

QB2 is in open position

QB2CLTR

BOOLEAN

QB2 is in closed position

VPQB2TR

BOOLEAN

Switch status of QB2 is valid (open or closed)

12.4.10

Interlocking for line bay ABC_LINE

12.4.10.1

Introduction
The interlocking for line bay (ABC_LINE) function is used for a line connected to
a double busbar arrangement with a transfer busbar according to figure 372. The
function can also be used for a double busbar arrangement without transfer busbar
or a single busbar arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1

QB2

QB7
QC1

QA1
QC2
QB9
QC9

en04000478.vsd
IEC04000478 V1 EN

Figure 372:

Switchyard layout ABC_LINE

663
Technical reference manual

Section 12
Control
12.4.10.2

1MRK 505 222-UEN B

Function block
ABC_LINE
QA1CLREL
QA1_OP
QA1_CL
QA1CLITL
QB9_OP
QB9REL
QB9_CL
QB9ITL
QB1_OP
QB1REL
QB1_CL
QB1ITL
QB2_OP
QB2REL
QB2_CL
QB2ITL
QB7_OP
QB7REL
QB7_CL
QB7ITL
QC1_OP
QC1REL
QC1_CL
QC1ITL
QC2_OP
QC2REL
QC2_CL
QC2ITL
QC9_OP
QC9REL
QC9_CL
QC9ITL
QC11_OP
QB1OPTR
QC11_CL
QB1CLTR
QC21_OP
QB2OPTR
QC21_CL
QB2CLTR
QC71_OP
QB7OPTR
QC71_CL
QB7CLTR
BB7_D_OP
QB12OPTR
BC_12_CL
QB12CLTR
BC_17_OP
VPQB1TR
BC_17_CL
VPQB2TR
BC_27_OP
VPQB7TR
BC_27_CL
VPQB12TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4
IEC05000357-2-en.vsd
IEC05000357 V2 EN

Figure 373:

ABC_LINE function block

664
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.10.3

Logic diagram
QA1_OP
QA1_CL
QB9_OP
QB9_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QB7_OP
QB7_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC9_OP
QC9_CL
QC11_OP
QC11_CL
QC21_OP
QC21_CL
QC71_OP
QC71_CL
VOLT_OFF
VOLT_ON
VPQA1
VPQC1
VPQC2
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
QC2_CL
QC9_CL
QB9_EX2

ABC_LINE
=1

VPQA1

=1

VPQB9

=1

VPQB1

=1

VPQB2

=1

VPQB7

=1

VPQC1

=1

VPQC2

=1

VPQC9

=1

VPQC11

=1

VPQC21

=1

VPQC71

=1

VPVOLT
&

&

QA1CLREL
QA1CLITL

QB9REL
QB9ITL

>1
1

&

en04000527.vsd
IEC04000527 V1 EN

665
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQB2
VPQC1
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP

&

VPQB2

&

QB1REL

1
1

QB1ITL

EXDU_ES
QB1_EX1

VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2

VPQC1
VPQC11
QC1_CL
QC11_CL
EXDU_ES

&

QB1EX3

en04000528.vsd
IEC04000528 V1 EN

666
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQB1
VPQC1
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES

&

VPQB1
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC

&

VPQC1
VPQC21
QC1_CL
QC21_CL
EXDU_ES

&

QB2REL

1
1

QB2ITL

QB2_EX1

QB2_EX2

QB2_EX3

en04000529.vsd
IEC04000529 V1 EN

667
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQC9
VPQC71

&

VP_BB7_D

QB7REL

>1
1

QB7ITL

VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1
VPQA1
VPQB1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

&

BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
QB7_EX2

IEC04000530 V1 EN

668
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQB2
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES

&

>1

BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1
VPQB2
VPQB9
QB1_OP
QB2_OP
QB9_OP
VPQB7
VPQB9
VPVOLT
QB7_OP
QB9_OP
VOLT_OFF

&

&

1
1

&
1

QC1REL
QC1ITL
QC2REL
QC2ITL

QC9REL
QC9ITL

en04000531.vsd
IEC04000531 V1 EN

669
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

QB1_OP
QB1_CL
VPQB1

QB1OPTR
QB1CLTR
VPQB1TR

QB2_OP
QB2_CL
VPQB2

QB2OPTR
QB2CLTR
VPQB2TR

QB7_OP
QB7_CL
VPQB7

QB7OPTR
QB7CLTR
VPQB7TR

QB1_OP
QB2_OP
VPQB1
VPQB2

>1

&

QB12OPTR
QB12CLTR
VPQB12TR
en04000532.vsd

IEC04000532 V1 EN

12.4.10.4

Input and output signals


Table 375:
Name

ABC_LINE Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB9_OP

BOOLEAN

QB9 is in open position

QB9_CL

BOOLEAN

QB9 is in closed position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QB7_OP

BOOLEAN

QB7 is in open position

QB7_CL

BOOLEAN

QB7 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QC9_OP

BOOLEAN

QC9 is in open position

QC9_CL

BOOLEAN

QC9 is in closed position

QC11_OP

BOOLEAN

Earthing switch QC11 on busbar WA1 is in open


position

QC11_CL

BOOLEAN

Earthing switch QC11 on busbar WA1 is in closed


position

QC21_OP

BOOLEAN

Earthing switch QC21 on busbar WA2 is in open


position

Table continues on next page

670
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QC21_CL

BOOLEAN

Earthing switch QC21 on busbar WA2 is in closed


position

QC71_OP

BOOLEAN

Earthing switch QC71 on busbar WA7 is in open


position

QC71_CL

BOOLEAN

Earthing switch QC71 on busbar WA7 is in closed


position

BB7_D_OP

BOOLEAN

Disconnectors on busbar WA7 except in the own


bay are open

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar


WA1 and WA2

BC_17_OP

BOOLEAN

No bus coupler connection exists between busbar


WA1 and WA7

BC_17_CL

BOOLEAN

A bus coupler connection exists between busbar


WA1 and WA7

BC_27_OP

BOOLEAN

No bus coupler connection exists between busbar


WA2 and WA7

BC_27_CL

BOOLEAN

A bus coupler connection exists between busbar


WA2 and WA7

VOLT_OFF

BOOLEAN

There is no voltage on the line and not VT (fuse)


failure

VOLT_ON

BOOLEAN

There is voltage on the line or there is a VT (fuse)


failure

VP_BB7_D

BOOLEAN

Switch status of the disconnectors on busbar


WA7 are valid

VP_BC_12

BOOLEAN

Status of the bus coupler app. between WA1 and


WA2 are valid

VP_BC_17

BOOLEAN

Status of the bus coupler app. between WA1 and


WA7 are valid

VP_BC_27

BOOLEAN

Status of the bus coupler app. between WA2 and


WA7 are valid

EXDU_ES

BOOLEAN

No transm error from any bay containing earthing


switches

EXDU_BPB

BOOLEAN

No transm error from any bay with disconnectors


on WA7

EXDU_BC

BOOLEAN

No transmission error from any bus coupler bay

QB9_EX1

BOOLEAN

External condition for apparatus QB9

QB9_EX2

BOOLEAN

External condition for apparatus QB9

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

QB1_EX3

BOOLEAN

External condition for apparatus QB1

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

QB2_EX3

BOOLEAN

External condition for apparatus QB2

QB7_EX1

BOOLEAN

External condition for apparatus QB7

Table continues on next page

671
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Default

Description

BOOLEAN

External condition for apparatus QB7

QB7_EX3

BOOLEAN

External condition for apparatus QB7

QB7_EX4

BOOLEAN

External condition for apparatus QB7

Table 376:
Name

12.4.11

Type

QB7_EX2

ABC_LINE Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB9REL

BOOLEAN

Switching of QB9 is allowed

QB9ITL

BOOLEAN

Switching of QB9 is forbidden

QB1REL

BOOLEAN

Switching of QB1 is allowed

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QB7REL

BOOLEAN

Switching of QB7 is allowed

QB7ITL

BOOLEAN

Switching of QB7 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QC9REL

BOOLEAN

Switching of QC9 is allowed

QC9ITL

BOOLEAN

Switching of QC9 is forbidden

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

QB2OPTR

BOOLEAN

QB2 is in open position

QB2CLTR

BOOLEAN

QB2 is in closed position

QB7OPTR

BOOLEAN

QB7 is in open position

QB7CLTR

BOOLEAN

QB7 is in closed position

QB12OPTR

BOOLEAN

QB1 or QB2 or both are in open position

QB12CLTR

BOOLEAN

QB1 and QB2 are not in open position

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

VPQB2TR

BOOLEAN

Switch status of QB2 is valid (open or closed)

VPQB7TR

BOOLEAN

Switch status of QB7 is valid (open or closed)

VPQB12TR

BOOLEAN

Switch status of QB1 and QB2 are valid (open or


closed)

Interlocking for transformer bay AB_TRAFO

672
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.11.1

Introduction
The interlocking for transformer bay (AB_TRAFO) function is used for a
transformer bay connected to a double busbar arrangement according to figure 374.
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be
used. This function can also be used in single busbar arrangements.
WA1 (A)
WA2 (B)
QB1

QB2
QC1

QA1
AB_TRAFO
QC2

T
QC3
QA2
QC4
QB3

QA2 and QC4 are not


used in this interlocking

QB4

en04000515.vsd
IEC04000515 V1 EN

Figure 374:

Switchyard layout AB_TRAFO

673
Technical reference manual

Section 12
Control
12.4.11.2

1MRK 505 222-UEN B

Function block
AB_TRAFO
QA1_OP
QA1CLREL
QA1_CL
QA1CLITL
QB1_OP
QB1REL
QB1_CL
QB1ITL
QB2_OP
QB2REL
QB2_CL
QB2ITL
QC1_OP
QC1REL
QC1_CL
QC1ITL
QC2_OP
QC2REL
QC2_CL
QC2ITL
QB3_OP
QB1OPTR
QB3_CL
QB1CLTR
QB4_OP
QB2OPTR
QB4_CL
QB2CLTR
QC3_OP
QB12OPTR
QC3_CL
QB12CLTR
QC11_OP
VPQB1TR
QC11_CL
VPQB2TR
QC21_OP
VPQB12TR
QC21_CL
BC_12_CL
VP_BC_12
EXDU_ES
EXDU_BC
QA1_EX1
QA1_EX2
QA1_EX3
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
IEC05000358-2-en.vsd
IEC05000358 V2 EN

Figure 375:

AB_TRAFO function block

674
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.11.3

Logic diagram
QA1_OP
QA1_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB3_OP
QB3_CL
QB4_OP
QB4_CL
QC3_OP
QC3_CL
QC11_OP
QC11_CL
QC21_OP
QC21_CL
VPQB1
VPQB2
VPQC1
VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL
QC2_CL
QC3_CL
QA1_EX1

AB_TRAFO
=1

VPQA1

=1

VPQB1

=1

VPQB2

=1

VPQC1

=1

VPQC2

=1

VPQB3

=1

VPQB4

=1

VPQC3

=1

VPQC11

=1

VPQC21
QA1CLREL
QA1CLITL

&

>1
&

en04000538.vsd

IEC04000538 V1 EN

VPQA1
VPQB2
VPQC1
VPQC2
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3

&

>1
1

QB1REL
QB1ITL

&

&

en04000539.vsd

IEC04000539 V1 EN

675
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

VPQA1
VPQB1
VPQC1
VPQC2
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3

&

>1
1

QB2REL
QB2ITL

&

&

en04000540.vsd

IEC04000540 V1 EN

VPQB1
VPQB2
VPQB3
VPQB4
QB1_OP
QB2_OP
QB3_OP
QB4_OP

&

1
1

QC1REL
QC1ITL
QC2REL
QC2ITL

QB1_OP
QB1_CL
VPQB1

QB1OPTR
QB1CLTR
VPQB1TR

QB2_OP
QB2_CL
VPQB2
QB1_OP
QB2_OP
VPQB1
VPQB2

QB2OPTR
QB2CLTR
VPQB2TR
QB12OPTR
QB12CLTR
VPQB12TR

>1

&

en04000541.vsd

IEC04000541 V1 EN

12.4.11.4

Input and output signals


Table 377:
Name

AB_TRAFO Input signals


Type

Default

Description

QA1_OP

BOOLEAN

QA1 is in open position

QA1_CL

BOOLEAN

QA1 is in closed position

QB1_OP

BOOLEAN

QB1 is in open position

QB1_CL

BOOLEAN

QB1 is in closed position

QB2_OP

BOOLEAN

QB2 is in open position

QB2_CL

BOOLEAN

QB2 is in closed position

QC1_OP

BOOLEAN

QC1 is in open position

QC1_CL

BOOLEAN

QC1 is in closed position

Table continues on next page


676
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Default

Description

QC2_OP

BOOLEAN

QC2 is in open position

QC2_CL

BOOLEAN

QC2 is in closed position

QB3_OP

BOOLEAN

QB3 is in open position

QB3_CL

BOOLEAN

QB3 is in closed position

QB4_OP

BOOLEAN

QB4 is in open position

QB4_CL

BOOLEAN

QB4 is in closed position

QC3_OP

BOOLEAN

QC3 is in open position

QC3_CL

BOOLEAN

QC3 is in closed position

QC11_OP

BOOLEAN

QC11 on busbar WA1 is in open position

QC11_CL

BOOLEAN

QC11 on busbar WA1 is in closed position

QC21_OP

BOOLEAN

QC21 on busbar WA2 is in open position

QC21_CL

BOOLEAN

QC21 on busbar WA2 is in closed position

BC_12_CL

BOOLEAN

A bus coupler connection exists between busbar


WA1 and WA2

VP_BC_12

BOOLEAN

Status of the bus coupler app. between WA1 and


WA2 are valid

EXDU_ES

BOOLEAN

No transm error from any bay containing earthing


switches

EXDU_BC

BOOLEAN

No transmission error from any bus coupler bay

QA1_EX1

BOOLEAN

External condition for apparatus QA1

QA1_EX2

BOOLEAN

External condition for apparatus QA1

QA1_EX3

BOOLEAN

External condition for apparatus QA1

QB1_EX1

BOOLEAN

External condition for apparatus QB1

QB1_EX2

BOOLEAN

External condition for apparatus QB1

QB1_EX3

BOOLEAN

External condition for apparatus QB1

QB2_EX1

BOOLEAN

External condition for apparatus QB2

QB2_EX2

BOOLEAN

External condition for apparatus QB2

QB2_EX3

BOOLEAN

External condition for apparatus QB2

Table 378:
Name

AB_TRAFO Output signals


Type

Description

QA1CLREL

BOOLEAN

Closing of QA1 is allowed

QA1CLITL

BOOLEAN

Closing of QA1 is forbidden

QB1REL

BOOLEAN

Switching of QB1 is allowed

QB1ITL

BOOLEAN

Switching of QB1 is forbidden

QB2REL

BOOLEAN

Switching of QB2 is allowed

QB2ITL

BOOLEAN

Switching of QB2 is forbidden

QC1REL

BOOLEAN

Switching of QC1 is allowed

QC1ITL

BOOLEAN

Switching of QC1 is forbidden

QC2REL

BOOLEAN

Switching of QC2 is allowed

Table continues on next page


677
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Type

Description

QC2ITL

BOOLEAN

Switching of QC2 is forbidden

QB1OPTR

BOOLEAN

QB1 is in open position

QB1CLTR

BOOLEAN

QB1 is in closed position

QB2OPTR

BOOLEAN

QB2 is in open position

QB2CLTR

BOOLEAN

QB2 is in closed position

QB12OPTR

BOOLEAN

QB1 or QB2 or both are in open position

QB12CLTR

BOOLEAN

QB1 and QB2 are not in open position

VPQB1TR

BOOLEAN

Switch status of QB1 is valid (open or closed)

VPQB2TR

BOOLEAN

Switch status of QB2 is valid (open or closed)

VPQB12TR

BOOLEAN

Switch status of QB1 and QB2 are valid (open or


closed)

12.4.12

Position evaluation POS_EVAL

12.4.12.1

Introduction
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals
OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.

12.4.12.2

Logic diagram
Position including quality

POSITION

POS_EVAL
OPENPOS
CLOSEPOS

Open/close position of
switch device

IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN

Only the value, open/close, and status is used in this function. Time information is
not used.
Input position (Value)

Signal quality

Output OPENPOS

Output CLOSEPOS

0 (Breaker
intermediate)

Good

1 (Breaker open)

Good

2 (Breaker closed)

Good

3 (Breaker faulty)

Good

Any

Invalid

Any

Oscillatory

678
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.4.12.3

Function block
POSITION

POS_EVAL
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd

IEC09000079 V1 EN

Figure 376:

12.4.12.4

POS_EVAL function block

Input and output signals


Table 379:

POS_EVAL Input signals

Name

Type

POSITION

Table 380:

INTEGER

Position status including quality

Type

Description

OPENPOS

BOOLEAN

Open position

CLOSEPOS

BOOLEAN

Close position

Logic rotating switch for function selection and


LHMI presentation SLGGIO
Function description
Logic rotating switch for function
selection and LHMI presentation

12.5.1

Description

POS_EVAL Output signals

Name

12.5

Default

IEC 61850
identification
SLGGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The logic rotating switch for function selection and LHMI presentation function
(SLGGIO) (or the selector switch function block) is used to get a selector switch
functionality similar to the one provided by a hardware selector switch. Hardware
selector switches are used extensively by utilities, in order to have different
functions operating on pre-set values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended purchase portfolio.
The logic selector switches eliminate all these problems.

12.5.2

Principle of operation
The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs UP and DOWN. When a signal is received on
the UP input, the block will activate the output next to the present activated output,
679

Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

in ascending order (if the present activated output is 3 for example and one
operates the UP input, then the output 4 will be activated). When a signal is
received on the DOWN input, the block will activate the output next to the present
activated output, in descending order (if the present activated output is 3 for
example and one operates the DOWN input, then the output 2 will be activated).
Depending on the output settings the output signals can be steady or pulsed. In case
of steady signals, in case of UP or DOWN operation, the previously active output
will be deactivated. Also, depending on the settings one can have a time delay
between the UP or DOWN activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the
desired position directly (without activating the intermediate positions), either
locally or remotely, using a select before execute dialog. One can block the
function operation, by activating the BLOCK input. In this case, the present
position will be kept and further operation will be blocked. The operator place
(local or remote) is specified through the PSTO input. If any operation is allowed
the signal INTONE from the Fixed signal function block can be connected.
SLGGIO function block has also an integer value output, that generates the actual
position number. The positions and the block names are fully settable by the user.
These names will appear in the menu, so the user can see the position names
instead of a number.

680
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.5.2.1

Functionality and behaviour


Control
Single Line Diagram
Commands

Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language

Ctrl/Com
Single Command
Selector Switch (GGIO)

3
../Com/Sel Sw/
SLGGIO3
Damage ctrl

../Ctrl/Com/Sel Sw
SLGGIO1
SLGGIO2
..
..
SLGGIO15

../Com/Sel Sw/
SLGGIO3
Damage ctrl

P:Disc All
OK

N: Disc Fe
Cancel

4
5
../Com/Sel Sw/
DmgCtrl
Damage ctrl:

The dialog window that appears


shows the present position (P:)
and the new position (N:), both
in clear names, given by the
user (max. 13 characters).

Modify the position with arrows.


The pos will not be modified (outputs
will not be activated) until you press
the E-button for O.K.

IEC06000420-2-en.vsd

IEC06000420 V2 EN

Figure 377:
Example 1 on handling the switch from the local HMI.
From the local HMI:
1 SLGGIO instances in the ACT application configuration
2 Switch name given by the user (max 13 characters)
3 Position number, up to 32 positions
4 Change position
5 New position

12.5.2.2

Graphical display
There are two possibilities for SLGGIO

681
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
if it is used for control, the switches will be listed with their actual positions,
but only the first three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it
when building the Graphical Display Editor, under the "Caption". If used for the
control, the following sequence of commands will ensure:

From the graphical display:

Change to the "Switches" page


of the SLD by left-right arrows.
Select switch by up-down
arrows

../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DAL

Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language

Select switch. Press the


I or O key. A dialog box
appears.

E
The pos will not be modified
(outputs will not be activated) until
you press the E-button for O.K.

Control
Single Line Diagram
Commands

../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
P: Disc
OK

N: Disc Fe
Cancel

../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DFW
IEC06000421-2-en.vsd
IEC06000421 V2 EN

Figure 378:
Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

682
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

12.5.3

Function block
SLGGIO
BLOCK
PSTO
UP
DOWN

^SWPOS01
^SWPOS02
^SWPOS03
^SWPOS04
^SWPOS05
^SWPOS06
^SWPOS07
^SWPOS08
^SWPOS09
^SWPOS10
^SWPOS11
^SWPOS12
^SWPOS13
^SWPOS14
^SWPOS15
^SWPOS16
^SWPOS17
^SWPOS18
^SWPOS19
^SWPOS20
^SWPOS21
^SWPOS22
^SWPOS23
^SWPOS24
^SWPOS25
^SWPOS26
^SWPOS27
^SWPOS28
^SWPOS29
^SWPOS30
^SWPOS31
^SWPOS32
SWPOSN
IEC05000658-2-en.vsd

IEC05000658 V2 EN

Figure 379:

12.5.4

SLGGIO function block

Input and output signals


Table 381:
Name

SLGGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

UP

BOOLEAN

Binary "UP" command

DOWN

BOOLEAN

Binary "DOWN" command

Table 382:

SLGGIO Output signals

Name

Type

Description

SWPOS01

BOOLEAN

Selector switch position 1

SWPOS02

BOOLEAN

Selector switch position 2

SWPOS03

BOOLEAN

Selector switch position 3

SWPOS04

BOOLEAN

Selector switch position 4

SWPOS05

BOOLEAN

Selector switch position 5

Table continues on next page

683
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.5.5
Table 383:
Name

Type

Description

SWPOS06

BOOLEAN

Selector switch position 6

SWPOS07

BOOLEAN

Selector switch position 7

SWPOS08

BOOLEAN

Selector switch position 8

SWPOS09

BOOLEAN

Selector switch position 9

SWPOS10

BOOLEAN

Selector switch position 10

SWPOS11

BOOLEAN

Selector switch position 11

SWPOS12

BOOLEAN

Selector switch position 12

SWPOS13

BOOLEAN

Selector switch position 13

SWPOS14

BOOLEAN

Selector switch position 14

SWPOS15

BOOLEAN

Selector switch position 15

SWPOS16

BOOLEAN

Selector switch position 16

SWPOS17

BOOLEAN

Selector switch position 17

SWPOS18

BOOLEAN

Selector switch position 18

SWPOS19

BOOLEAN

Selector switch position 19

SWPOS20

BOOLEAN

Selector switch position 20

SWPOS21

BOOLEAN

Selector switch position 21

SWPOS22

BOOLEAN

Selector switch position 22

SWPOS23

BOOLEAN

Selector switch position 23

SWPOS24

BOOLEAN

Selector switch position 24

SWPOS25

BOOLEAN

Selector switch position 25

SWPOS26

BOOLEAN

Selector switch position 26

SWPOS27

BOOLEAN

Selector switch position 27

SWPOS28

BOOLEAN

Selector switch position 28

SWPOS29

BOOLEAN

Selector switch position 29

SWPOS30

BOOLEAN

Selector switch position 30

SWPOS31

BOOLEAN

Selector switch position 31

SWPOS32

BOOLEAN

Selector switch position 32

SWPOSN

INTEGER

Switch position (integer)

Setting parameters
SLGGIO Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

NrPos

2 - 32

32

Number of positions in the switch

OutType

Pulsed
Steady

Steady

Output type, steady or pulse

Table continues on next page

684
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Values (Range)

Unit

tPulse

0.000 - 60.000

0.001

0.200

Operate pulse duration, in [s]

tDelay

0.000 - 60000.000

0.010

0.000

Time delay on the output, in [s]

StopAtExtremes

Disabled
Enabled

Disabled

Stop when min or max position is reached

12.6

Step

Description

Selector mini switch VSGGIO


Function description
Selector mini switch

12.6.1

Default

IEC 61850
identification
VSGGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The Selector mini switch VSGGIO function block is a multipurpose function used
for a variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line
diagram (SLD) on the local HMI.

12.6.2

Principle of operation
Selector mini switch (VSGGIO) function can be used for double purpose, in the
same way as switch controller (SCSWI) functions are used:

for indication on the single line diagram (SLD). Position is received through
the IPOS1 and IPOS2 inputs and distributed in the configuration through the
POS1 and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and
distributed in the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that the a symbol is
associated with a controllable object, otherwise the symbol won't be
displayed on the screen. A symbol is created and configured in
GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of
operators place , operation from local HMI (Local) or through IEC 61850

685
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

(Remote). An INTONE connection from Fixed signal function block (FXDSIGN)


will allow operation from local HMI.
As it can be seen, both indications and commands are done in double-bit
representation, where a combination of signals on both inputs/outputs generate the
desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the
name of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1

12.6.3

IPOS2

Name of displayed string Default string value

PosUndefined

P00

Position1

P01

Position2

P10

PosBadState

P11

Function block
VSGGIO
BLOCK
PSTO
IPOS1
IPOS2

BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
IEC06000508-2-en.vsd

IEC06000508 V3 EN

Figure 380:

12.6.4

VSGGIO function block

Input and output signals


Table 384:
Name

VSGGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

IPOS1

BOOLEAN

Position 1 indicating input

IPOS2

BOOLEAN

Position 2 indicating input

Table 385:

VSGGIO Output signals

Name

Type

Description

BLOCKED

BOOLEAN

The function is active but the functionality is


blocked

POSITION

INTEGER

Position indication, integer

POS1

BOOLEAN

Position 1 indication, logical signal

Table continues on next page

686
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.6.5
Table 386:

Type

Description

POS2

BOOLEAN

Position 2 indication, logical signal

CMDPOS12

BOOLEAN

Execute command from position 1 to position 2

CMDPOS21

BOOLEAN

Execute command from position 2 to position 1

Setting parameters
VSGGIO Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

CtlModel

Dir Norm
SBO Enh

Dir Norm

Specifies the type for control model


according to IEC 61850

Mode

Steady
Pulsed

Pulsed

Operation mode

tSelect

0.000 - 60.000

0.001

30.000

Max time between select and execute


signals

tPulse

0.000 - 60.000

0.001

0.200

Command pulse lenght

12.7

Generic double point function block DPGGIO


Function description
IEC 61850 generic communication I/O
functions

12.7.1

IEC 61850
identification
DPGGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It
is especially used in the interlocking and reservation station-wide logics.

12.7.2

Principle of operation
Upon receiving the input signals, the IEC 61850 generic communication I/O
functions (DPGGIO) function block will send the signals over IEC 61850-8-1 to
the equipment or system that requests these signals. To be able to get the signals,
other tools must be used, as described in the application manual, to PCM600 must
be used to define which function block in which equipment or system should
receive this information.

687
Technical reference manual

Section 12
Control
12.7.3

1MRK 505 222-UEN B

Function block
DPGGIO
OPEN
CLOSE
VALID

POSITION

IEC07000200-2-en.vsd
IEC07000200 V2 EN

Figure 381:

12.7.4

DPGGIO function block

Input and output signals


Table 387:

DPGGIO Input signals

Name

Type

Description

BOOLEAN

Open indication

CLOSE

BOOLEAN

Close indication

VALID

BOOLEAN

Valid indication

Table 388:

DPGGIO Output signals

Name
POSITION

12.7.5

Default

OPEN

Type
INTEGER

Description
Double point indication

Settings
The function does not have any parameters available in the local HMI or PCM600.

12.8

Single point generic control 8 signals SPC8GGIO


Function description
Single point generic control 8 signals

12.8.1

IEC 61850
identification
SPC8GGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The Single point generic control 8 signals (SPC8GGIO) function block is a
collection of 8 single point commands, designed to bring in commands from
REMOTE (SCADA) to those parts of the logic configuration that do not need
extensive command receiving functionality (for example, SCSWI). In this way,
simple commands can be sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is supposed to be achieved by

688
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

other means, such as binary inputs and SPGGIO function blocks. The commands
can be pulsed or steady.

12.8.2

Principle of operation
The PSTO input will determine which the allowed position for the operator
(LOCAL, REMOTE, ALL) is. Upon sending a command from an allowed operator
position, one of the 8 outputs will be activated. The settings Latchedx and tPulsex
(where x is the respective output) will determine if the signal will be pulsed (and
how long the pulse is) or latched (steady). BLOCK will block the operation of the
function in case a command is sent, no output will be activated.
PSTO is the universal operator place selector for all control
functions. Even if PSTO can be configured to allow LOCAL or
ALL operator positions, the only functional position usable with the
SPC8GGIO function block is REMOTE.

12.8.3

Function block
SPC8GGIO
BLOCK
PSTO

^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC07000143-2-en.vsd

IEC07000143 V2 EN

Figure 382:

12.8.4

SPC8GGIO function block

Input and output signals


Table 389:
Name

SPC8GGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Blocks the function operation

PSTO

INTEGER

Operator place selection

Table 390:
Name

SPC8GGIO Output signals


Type

Description

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output2

OUT3

BOOLEAN

Output3

OUT4

BOOLEAN

Output4

Table continues on next page


689
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.8.5
Table 391:
Name

Type

Description

OUT5

BOOLEAN

Output5

OUT6

BOOLEAN

Output6

OUT7

BOOLEAN

Output7

OUT8

BOOLEAN

Output8

Setting parameters
SPC8GGIO Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

Latched1

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 1

tPulse1

0.01 - 6000.00

0.01

0.10

Output1 Pulse Time

Latched2

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 2

tPulse2

0.01 - 6000.00

0.01

0.10

Output2 Pulse Time

Latched3

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 3

tPulse3

0.01 - 6000.00

0.01

0.10

Output3 Pulse Time

Latched4

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 4

tPulse4

0.01 - 6000.00

0.01

0.10

Output4 Pulse Time

Latched5

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 5

tPulse5

0.01 - 6000.00

0.01

0.10

Output5 Pulse Time

Latched6

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 6

tPulse6

0.01 - 6000.00

0.01

0.10

Output6 Pulse Time

Latched7

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 7

tPulse7

0.01 - 6000.00

0.01

0.10

Output7 Pulse Time

Latched8

Pulsed
Latched

Pulsed

Setting for pulsed/latched mode for


output 8

tPulse8

0.01 - 6000.00

0.01

0.10

Output8 pulse time

12.9

AutomationBits, command function for DNP3.0


AUTOBITS

690
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Function description
AutomationBits, command function for
DNP3

12.9.1

IEC 61850
identification
AUTOBITS

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get
into the configuration of the commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).

12.9.2

Principle of operation
AutomationBits function (AUTOBITS) has 32 individual outputs which each can
be mapped as a Binary Output point in DNP3. The output is operated by a "Object
12" in DNP3. This object contains parameters for control-code, count, on-time and
off-time. To operate an AUTOBITS output point, send a control-code of latch-On,
latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining parameters will be
regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in
the same way the setting Operation: On/Off does. That means that, upon activation
of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The BLOCK acts
like an overriding, the function still receives data from the DNP3 master. Upon
deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in Remote. If
PSTO is in Local then no change is applied to the outputs.

691
Technical reference manual

Section 12
Control
12.9.3

1MRK 505 222-UEN B

Function block
AUTOBITS
BLOCK
PSTO

^CMDBIT1
^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32
IEC09000925-1-en.vsd

IEC09000925 V1 EN

Figure 383:

12.9.4

AUTOBITS function block

Input and output signals


Table 392:
Name

AUTOBITS Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

Table 393:
Name

AUTOBITS Output signals


Type

Description

CMDBIT1

BOOLEAN

Command out bit 1

CMDBIT2

BOOLEAN

Command out bit 2

CMDBIT3

BOOLEAN

Command out bit 3

CMDBIT4

BOOLEAN

Command out bit 4

CMDBIT5

BOOLEAN

Command out bit 5

CMDBIT6

BOOLEAN

Command out bit 6

CMDBIT7

BOOLEAN

Command out bit 7

CMDBIT8

BOOLEAN

Command out bit 8

Table continues on next page


692
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.9.5
Table 394:

Description

BOOLEAN

Command out bit 9

CMDBIT10

BOOLEAN

Command out bit 10

CMDBIT11

BOOLEAN

Command out bit 11

CMDBIT12

BOOLEAN

Command out bit 12

CMDBIT13

BOOLEAN

Command out bit 13

CMDBIT14

BOOLEAN

Command out bit 14

CMDBIT15

BOOLEAN

Command out bit 15

CMDBIT16

BOOLEAN

Command out bit 16

CMDBIT17

BOOLEAN

Command out bit 17

CMDBIT18

BOOLEAN

Command out bit 18

CMDBIT19

BOOLEAN

Command out bit 19

CMDBIT20

BOOLEAN

Command out bit 20

CMDBIT21

BOOLEAN

Command out bit 21

CMDBIT22

BOOLEAN

Command out bit 22

CMDBIT23

BOOLEAN

Command out bit 23

CMDBIT24

BOOLEAN

Command out bit 24

CMDBIT25

BOOLEAN

Command out bit 25

CMDBIT26

BOOLEAN

Command out bit 26

CMDBIT27

BOOLEAN

Command out bit 27

CMDBIT28

BOOLEAN

Command out bit 28

CMDBIT29

BOOLEAN

Command out bit 29

CMDBIT30

BOOLEAN

Command out bit 30

CMDBIT31

BOOLEAN

Command out bit 31

CMDBIT32

BOOLEAN

Command out bit 32

Setting parameters
AUTOBITS Non group settings (basic)

Name

Values (Range)

Operation

Table 395:

Type

CMDBIT9

Off
On

Unit
-

Step
-

Default
Off

Description
Operation Off / On

DNPGEN Non group settings (basic)

Name
Operation

Values (Range)
Off
On

Unit
-

Step
-

Default
Off

Description
Operation mode Off / On

693
Technical reference manual

Section 12
Control

Table 396:
Name

1MRK 505 222-UEN B

CHSERRS485 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
Serial-Mode

Off

Operation mode

BaudRate

300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd

9600 Bd

Baud-rate for serial port

WireMode

Four-wire
Two-wire

Two-wire

RS485 wire mode

Table 397:
Name

CHSERRS485 Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

DLinkConfirm

Never
Sometimes
Always

Never

Data-link confirm

tDLinkTimeout

0.000 - 60.000

0.001

2.000

Data-link confirm timeout in s

DLinkRetries

0 - 255

Data-link maximum retries

tRxToTxMinDel

0.000 - 60.000

0.001

0.000

Rx to Tx minimum delay in s

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment


size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment


size

StopBits

1-2

Stop bits

Parity

No
Even
Odd

Even

Parity

tRTSWarmUp

0.000 - 60.000

0.001

0.000

RTS warm-up in s

tRTSWarmDown

0.000 - 60.000

0.001

0.000

RTS warm-down in s

tBackOffDelay

0.000 - 60.000

0.001

0.050

RS485 back-off delay in s

tMaxRndDelBkOf

0.000 - 60.000

0.001

0.100

RS485 maximum back-off random delay


in s

Table 398:
Name

CH2TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
TCP/IP
UDP-Only

Off

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

694
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 399:

CH2TCP Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment


size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment


size

Table 400:

CH3TCP Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
TCP/IP
UDP-Only

Off

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 401:

CH3TCP Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment


size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment


size

Table 402:

CH4TCP Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
TCP/IP
UDP-Only

Off

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 403:

CH4TCP Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment


size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment


size

695
Technical reference manual

Section 12
Control

Table 404:
Name

1MRK 505 222-UEN B

CH5TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
TCP/IP
UDP-Only

Off

Operation mode

TCPIPLisPort

1 - 65535

20000

TCP/IP listen port

UDPPortAccData

1 - 65535

20000

UDP port to accept UDP datagrams from


master

UDPPortInitNUL

1 - 65535

20000

UDP port for initial NULL response

UDPPortCliMast

0 - 65535

UDP port to remote client/master

Table 405:
Name

CH5TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

ApLayMaxRxSize

20 - 2048

2048

Application layer maximum Rx fragment


size

ApLayMaxTxSize

20 - 2048

2048

Application layer maximum Tx fragment


size

Table 406:
Name

MSTRS485 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Table continues on next page

696
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 407:

MSTRS485 Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

ValMasterAddr

No
Yes

Yes

Validate source (master) address

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

URSendOnline

No
Yes

No

Unsolicited response sends when on-line

UREvClassMask

Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Off

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before offline retry mode

tURRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tUROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay


in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

Table continues on next page


697
Technical reference manual

Section 12
Control
Name

1MRK 505 222-UEN B

Unit

Step

Default

tUREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event


buffer timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tUREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event


buffer timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tUREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event


buffer timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after


timeout

DNPToSetTime

No
Yes

Yes

Allow DNP to set time in IED

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

Step

Default

Table 408:
Name

Values (Range)

Description

MST1TCP Non group settings (basic)


Values (Range)

Unit

Description

Operation

Off
On

Off

Operation Off / On

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Table continues on next page

698
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 409:

MST1TCP Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Off

Unsolicited response, event class mask

Table continues on next page

699
Technical reference manual

Section 12
Control
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

UROfflineRetry

0 - 10

Unsolicited response retries before offline retry mode

tURRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tUROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay


in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tUREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event


buffer timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tUREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event


buffer timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tUREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event


buffer timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after


timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

Table 410:
Name

MST2TCP Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

Table continues on next page

700
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 411:

MST2TCP Non group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

Table continues on next page

701
Technical reference manual

Section 12
Control
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Off

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before offline retry mode

tURRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tUROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay


in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tUREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event


buffer timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tUREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event


buffer timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tUREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event


buffer timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after


timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

702
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Table 412:

MST3TCP Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

703
Technical reference manual

Section 12
Control

Table 413:
Name

1MRK 505 222-UEN B

MST3TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Off

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before offline retry mode

tURRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tUROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay


in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tUREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event


buffer timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

tUREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event


buffer timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tUREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event


buffer timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after


timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

Table continues on next page

704
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Unit

Step

Default

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

Table 414:

Values (Range)

Description

MST4TCP Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SlaveAddress

0 - 65519

Slave address

MasterAddres

0 - 65519

Master address

ValMasterAddr

No
Yes

Yes

Validate source (master) address

MasterIP-Addr

0 - 18

IP
Address

0.0.0.0

Master IP-address

MasterIPNetMsk

0 - 18

IP
Address

255.255.255.255

Master IP net mask

Obj1DefVar

1:BISingleBit
2:BIWithStatus

1:BISingleBit

Object 1, default variation

Obj2DefVar

1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e

3:BIChWithRelTim
e

Object 2, default variation

Obj3DefVar

1:DIWithoutFlag
2:DIWithFlag

1:DIWithoutFlag

Object 3, default variation

Obj4DefVar

1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e

3:DIChWithRelTim
e

Object 4, default variation

Obj10DefVar

1:BO
2:BOStatus

2:BOStatus

Object 10, default variation

Obj20DefVar

1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF

5:BinCnt32WoutF

Object 20, default variation

Table continues on next page

705
Technical reference manual

Section 12
Control
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

Obj22DefVar

1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T

1:BinCnt32EvWou
tT

Object 22, default variation

Obj30DefVar

1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF

3:AI32IntWithoutF

Object 30, default variation

Obj32DefVar

1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT

1:AI32IntEvWoutF

Object 32, default variation

Table 415:
Name

MST4TCP Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

AddrQueryEnbl

No
Yes

Yes

Address query enable

tApplConfTout

0.00 - 300.00

0.01

10.00

Application layer confim timeout

ApplMultFrgRes

No
Yes

Yes

Enable application for multiple fragment


response

ConfMultFrag

No
Yes

Yes

Confirm each multiple fragment

UREnable

No
Yes

Yes

Unsolicited response enabled

UREvClassMask

Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3

Off

Unsolicited response, event class mask

UROfflineRetry

0 - 10

Unsolicited response retries before offline retry mode

tURRetryDelay

0.00 - 60.00

0.01

5.00

Unsolicited response retry delay in s

tUROfflRtryDel

0.00 - 60.00

0.01

30.00

Unsolicited response off-line retry delay


in s

UREvCntThold1

1 - 100

Unsolicited response class 1 event count


report treshold

tUREvBufTout1

0.00 - 60.00

0.01

5.00

Unsolicited response class 1 event


buffer timeout

UREvCntThold2

1 - 100

Unsolicited response class 2 event count


report treshold

Table continues on next page


706
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

Unit

Step

Default

tUREvBufTout2

0.00 - 60.00

0.01

5.00

Unsolicited response class 2 event


buffer timeout

UREvCntThold3

1 - 100

Unsolicited response class 3 event count


report treshold

tUREvBufTout3

0.00 - 60.00

0.01

5.00

Unsolicited response class 3 event


buffer timeout

DelOldBufFull

No
Yes

No

Delete oldest event when buffer is full

ExtTimeFormat

LocalTime
UTC

UTC

External time format

DNPToSetTime

No
Yes

No

Allow DNP to set time in IED

tSynchTimeout

30 - 3600

1800

Time synch timeout before error status is


generated

TSyncReqAfTout

No
Yes

No

Time synchronization request after


timeout

Averag3TimeReq

No
Yes

No

Use average of 3 time requests

PairedPoint

No
Yes

Yes

Enable paired point

tSelectTimeout

1.0 - 60.0

0.1

30.0

Select timeout

tBrokenConTout

0 - 3600

Broken connection timeout

tKeepAliveT

0 - 3600

10

Keep-Alive timer

12.10

Values (Range)

Single command, 16 signals SINGLECMD


Function description
Single command, 16 signals

12.10.1

Description

IEC 61850
identification
SINGLECMD

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The IEDs can receive commands either from a substation automation system or
from the local HMI. The command function block has outputs that can be used, for
example, to control high voltage apparatuses or for other user defined functionality.

12.10.2

Principle of operation
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of
13 characters in PCM600.

707
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

The output signals can be of the types Off, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole
function block. The length of the output pulses are 100 ms. In steady mode,
SINGLECMD function has a memory to remember the output values at power
interruption of the IED. Also a BLOCK input is available used to block the
updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.

12.10.3

Function block
SINGLECMD
BLOCK

^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
IEC05000698-2-en.vsd

IEC05000698 V3 EN

Figure 384:

12.10.4

SINGLECMD function block

Input and output signals


Table 416:
Name
BLOCK

Table 417:
Name

SINGLECMD Input signals


Type
BOOLEAN

Default
0

Description
Block single command function

SINGLECMD Output signals


Type

Description

OUT1

BOOLEAN

Single command output 1

OUT2

BOOLEAN

Single command output 2

OUT3

BOOLEAN

Single command output 3

OUT4

BOOLEAN

Single command output 4

OUT5

BOOLEAN

Single command output 5

OUT6

BOOLEAN

Single command output 6

OUT7

BOOLEAN

Single command output 7

OUT8

BOOLEAN

Single command output 8

OUT9

BOOLEAN

Single command output 9

Table continues on next page


708
Technical reference manual

Section 12
Control

1MRK 505 222-UEN B

Name

12.10.5
Table 418:

Type

Description

OUT10

BOOLEAN

Single command output 10

OUT11

BOOLEAN

Single command output 11

OUT12

BOOLEAN

Single command output 12

OUT13

BOOLEAN

Single command output 13

OUT14

BOOLEAN

Single command output 14

OUT15

BOOLEAN

Single command output 15

OUT16

BOOLEAN

Single command output 16

Setting parameters
SINGLECMD Non group settings (basic)

Name
Mode

Values (Range)
Off
Steady
Pulsed

Unit
-

Step
-

Default
Off

Description
Operation mode

709
Technical reference manual

710

Section 13
Scheme communication

1MRK 505 222-UEN B

Section 13

Scheme communication

About this chapter


This chapter describes the scheme communication logic that is used in distance and
earth fault protection function to obtain almost instantaneous fault clearance for
faults on the protected line. The chapter considers scheme communication logic
(ZCPSCH), current reversal and weak-end in-feed logic (ZCRWPSCH) for the
distance protection function and scheme communication logic for residual
overcurrent protection (ECPSCH) and current reversal and weak-end in-feed logic
(ECRWPSCH) for the residual overcurrent function.
Also Local acceleration logic (ZCLCPLAL) is discussed which is a function that
can generate instantaneous tripping as a result of remote end faults without any
telecommunication.
The chapter contains a short description of the design, simplified logical block
diagrams, figure of the function block, input and output signals and setting
parameters.

13.1

Scheme communication logic for distance or


overcurrent protection ZCPSCH
Function description
Scheme communication logic for
distance or overcurrent protection

13.1.1

IEC 61850
identification
ZCPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
To achieve instantaneous fault clearance for all line faults, a scheme
communication logic is provided. All types of communication schemes for
example, permissive underreaching, permissive overreaching, blocking,
unblocking, intertrip are available.
The built-in communication module (LDCM) can be used for scheme
communication signaling when included.
Phase segregated communication is also available for correct operation at
simultaneous faults when three distance protection communication channels are
available between the line ends.

711
Technical reference manual

Section 13
Scheme communication
13.1.2

1MRK 505 222-UEN B

Principle of operation
Depending on whether a reverse or forward directed impedance zone is used to
issue the send signal, the communication schemes are divided into Blocking and
Permissive schemes, respectively.
A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.

13.1.2.1

Blocking scheme
The principle of operation for a blocking scheme is that an overreaching zone is
allowed to trip instantaneously after the settable co-ordination time tCoord has
elapsed, when no signal is received from the remote IED.
The received signal, which shall be connected to CR, is used to not release the zone
to be accelerated to clear the fault instantaneously (after time tCoord). The
overreaching zone to be accelerated is connected to the input CACC, see figure 385.
In case of external faults, the blocking signal (CR) must be received before the
settable timer tCoord elapses, to prevent a false trip, see figure 385.
The function can be totally blocked by activating the input BLOCK, block of trip
by activating the input BLKTR, Block of signal send by activating the input BLKCS.
tCoord

CACC
CR

AND

TRIP

en05000512.vsd
IEC05000512 V1 EN

Figure 385:

Basic logic for trip signal in blocking scheme

Channels for communication in each direction must be available.

13.1.2.2

Permissive underreaching scheme


In a permissive underreaching scheme, a forward directed underreach measuring
element (normally zone1) sends a permissive signal CS to the remote end if a fault
is detected in forward direction. The received signal CR is used to allow an
overreaching zone to trip after the tCoord timer has elapsed. The tCoord in
permissive underreaching schemes is normally set to zero.
The logic for trip signal in permissive scheme is shown in figure 386.

712
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

tCoord

CACC
CR

AND

TRIP

en05000513.vsd
IEC05000513 V1 EN

Figure 386:

Logic for trip signal in permissive scheme

The permissive underreaching scheme has the same blocking possibilities as


mentioned for blocking scheme.

13.1.2.3

Permissive overreaching scheme


In a permissive overreaching scheme, a forward directed overreach measuring
element (normally zone2) sends a permissive signal CS to the remote end if a fault
is detected in forward direction. The received signal CR is used to allow an
overreaching zone to trip after the settable tCoord timer has elapsed. The tCoord in
permissive overreaching schemes is normally set to zero.
The logic for trip signal is the same as for permissive underreaching, as in
figure 386.
The permissive overreaching scheme has the same blocking possibilities as
mentioned for blocking scheme.

13.1.2.4

Unblocking scheme
In unblocking scheme, the lower dependability in permissive scheme is overcome
by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable, power-line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 387. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.

713
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

CR
1

tSecurity
t

CRG
200 ms
t

CRL

>1
150 ms

AND

OR

AND
LCG

en05000746.vsd
IEC05000746 V1 EN

Figure 387:

Guard signal logic with unblocking scheme

The unblocking function can be set in three operation modes (setting Unblock):
Off

The unblocking function is out of operation

No restart

Communication failure shorter than tSecurity will be ignored


If CRG disappears a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)

Restart

Communication failure shorter than tSecurity will be ignored


It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be recurrent
signalling

13.1.2.5

Intertrip scheme
In the direct intertrip scheme, the send signal CS is sent from an underreaching
zone that is tripping the line.
The received signal CR is directly transferred to a TRIP for tripping without local
criteria. The signal is further processed in the tripping logic.
In case of single-pole tripping in multi-phase systems, a phase selection is performed.

13.1.2.6

Simplified logic diagram


The simplified logic diagram for the complete logic is shown in figure 388.

714
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Unblock =Off
CR
Unblock =
NoRestart
Unblock =
Restart
CRG

CRL
CRL

OR

AND
tSecurit
y

1
200 ms
t

AND
150 ms

OR

AND

LCG

AND

SchemeType =
Intertrip
CSUR
tSendMi
n

BLOCK
CSBLK
CRL

AND

OR

AND

OR

Schemetype =
Permissive UR

AND

AND
CACC

CS

OR

tCoord

OR

25 ms
t

TRIP

Schemetype =
Permissive OR

OR

CSOR

AND

AND
tSendMin

OR
AND
SchemeType =
Blocking
BLKCS

AND

IEC05000515-2-en.vsd
IEC05000515 V2 EN

Figure 388:

Scheme communication logic for distance or overcurrent


protection, simplified logic diagram

715
Technical reference manual

Section 13
Scheme communication
13.1.3

1MRK 505 222-UEN B

Function block
ZCPSCH
BLOCK
BLKTR
BLKCS
CSBLK
CACC
CSOR
CSUR
CR
CRG

TRIP
CS
CRL
LCG

IEC06000286-2-en.vsd
IEC06000286 V2 EN

Figure 389:

13.1.4

ZCPSCH function block

Input and output signals


Table 419:
Name

ZCPSCH Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Signal for block of trip output from communication


logic

BLKCS

BOOLEAN

Block of carrier send in permissive OR and


blocking schemes

CSBLK

BOOLEAN

Reverse directed distance protection zone signal

CACC

BOOLEAN

Permissive distance protection zone signal

CSOR

BOOLEAN

Overreaching distance protection zone signal

CSUR

BOOLEAN

Underreaching distance protection zone signal

CR

BOOLEAN

Carrier Signal Received

CRG

BOOLEAN

Carrier guard signal received

Table 420:
Name

ZCPSCH Output signals


Type

Description

TRIP

BOOLEAN

Trip output

CS

BOOLEAN

Carrier Send signal

CRL

BOOLEAN

Carrier signal received or missing carrier guard


signal

LCG

BOOLEAN

Loss of carrier guard signal

716
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.1.5
Table 421:

Setting parameters
ZCPSCH Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SchemeType

Off
Intertrip
Permissive UR
Permissive OR
Blocking

Permissive UR

Scheme type

tCoord

0.000 - 60.000

0.001

0.035

Co-ordination time for blocking


communication scheme

tSendMin

0.000 - 60.000

0.001

0.100

Minimum duration of a carrier send signal

Table 422:

ZCPSCH Group settings (advanced)

Name

Values (Range)

Unit

Step

Default

Description

Unblock

Off
NoRestart
Restart

Off

Operation mode of unblocking logic

tSecurity

0.000 - 60.000

0.001

0.035

Security timer for loss of carrier guard


detection

13.1.6

Technical data
Table 423:

ZCPSCH technical data

Function

Range or value

Accuracy

Scheme type

Intertrip
Permissive Underreach
Permissive Overreach
Blocking

Co-ordination time for blocking


communication scheme

(0.000-60.000) s

0.5% 10 ms

Minimum duration of a send signal

(0.000-60.000) s

0.5% 10 ms

Security timer for loss of guard


signal detection

(0.000-60.000) s

0.5% 10 ms

Operation mode of unblocking logic

Off
NoRestart
Restart

717
Technical reference manual

Section 13
Scheme communication

13.2

Phase segregated scheme communication logic for


distance protection ZC1PPSCH
Function description
Phase segregated Scheme
communication logic for distance
protection

13.2.1

1MRK 505 222-UEN B

IEC 61850
identification
ZC1PPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
Communication between line ends is used to achieve fault clearance for all faults
on a power line. All possible types of communication schemes for example,
permissive underreach, permissive overreach and blocking schemes are available.
To manage problems with simultaneous faults on parallel power lines phase
segregated communication is needed. This will then replace the standard Scheme
communication logic for distance or Overcurrent protection (ZCPSCH) on
important lines where three communication channels (in each subsystem) are
available for the distance protection communication.
The main purpose of the Phase segregated scheme communication logic for
distance protection (ZC1PPSCH) function is to supplement the distance protection
function such that:

fast clearance of faults is also achieved at the line end for which the faults are
on the part of the line not covered by its underreaching zone.
correct phase selection can be maintained to support single-pole tripping for
faults occurring anywhere on the entire length of a double circuit line.

To accomplish this, three separate communication channels, that is, one per phase,
each capable of transmitting a signal in each direction is required.
ZC1PPSCH can be completed with the current reversal and WEI logic for phase
segregated communication, when found necessary in Blocking and Permissive
overreaching schemes.

13.2.2

Principle of operation
Depending on whether a reverse or forward directed impedance zone is used to
issue the send signal, the communication schemes are divided into Blocking and
Permissive schemes, respectively.
A permissive scheme is inherently faster and has better security against false
tripping than a blocking scheme. On the other hand, a permissive scheme depends
on a received signal for a fast trip, so its dependability is lower than that of a
blocking scheme.

718
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

The Phase segregated scheme communication logic for distance protection


(ZC1PPSCH) function is a logical function built-up from logical elements. It is a
supplementary function to the distance protection, requiring for its operation inputs
from the distance protection and the communication equipment.
The type of communication-aided scheme to be used can be selected by way of the
settings.
The ability to select which distance protection zone is assigned to which input of
ZC1PPSCH makes this logic able to support practically any scheme
communication requirements regardless of their basic operating principle. The
outputs to initiate tripping and sending of the teleprotection signal are given in
accordance with the type of communication-aided scheme selected and the zone(s)
and phase(s) of the distance protection which have operated.
When power line carrier communication channels are used for permissive schemes
communication, unblocking logic which uses the loss of guard signal as a receive
criteria is provided. This logic compensates for the lack of dependability due to the
transmission of the command signal over the faulted line.

13.2.2.1

Blocking scheme
The principle of operation for a blocking scheme is that an overreaching zone is
allowed to trip instantaneously after the settable co-ordination time tCoord has
elapsed, when no signal is received from the remote IED. The received signal (sent
by a reverse looking element in the remote IED), which shall be connected to
CRLx, is used to not release the zone to be accelerated to clear the fault
instantaneously (after time tCoord). The overreaching zone to be accelerated is
connected to the input CACCLx, see figure 390. In case of external faults, the
blocking signal (CRLx) must be received before the settable timer tCoord elapses,
to prevent an unneccesary trip, see figure 390.
ZC1PPSCH can be totally blocked by activating the input BLOCK, block of trip is
achieved by activating the input BLKTRLx, Block of carrier send is done by
activating the input BLKCSLx.
CACCLx
CRLx

tCoord

AND

25 ms

TRLx

IEC06000310_2_en.vsd
IEC06000310 V2 EN

Figure 390:

13.2.2.2

Basic logic for trip carrier in one phase of a blocking scheme

Permissive underreach scheme


In a permissive underreach scheme, a forward directed underreach measuring
element (normally zone1) sends a permissive signal CSLx to the remote end if a
fault is detected in forward direction. The received signal CRLx is used to allow an
719

Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

overreaching zone (connected to CACCLx) to trip after the tCoord timer has
elapsed. The tCoord is in permissive underreach schemes normally set to zero. The
logic for trip carrier in permissive scheme is shown in figure 391. Three channels
for communication in each direction must be available.
CACCLx
CRLx

AND

tCoord
t

25 ms
t

TRLx

IEC07000088_2_en.vsd
IEC07000088 V2 EN

Figure 391:

13.2.2.3

Basic logic for trip carrier in one phase of a permissive underreach


scheme

Permissive overreach scheme


In a permissive overreach scheme, a forward directed overreach measuring element
(normally zone2) sends a permissive signal CSLx to the remote end if a fault is
detected in forward direction. The received signal CRLx is used to allow an
overreaching zone to trip after the settable tCoord timer has elapsed. The tCoord is
in permissive overreach schemes normally set to zero. The logic for trip carrier is
the same as for permissive underreach, see figure 390.
The permissive overreach scheme has the same blocking possibilities as mentioned
for blocking scheme above. The blocking inputs are activated from the current
reversal logic when this function is included.
Three channels for communication in each direction must be available.

13.2.2.4

Unblocking scheme
In an unblocking scheme, the lower dependability in permissive scheme is
overcome by using the loss of guard signal from the communication equipment to
locally create a carrier receive signal. It is common or suitable to use the function
when older, less reliable, power-line carrier (PLC) communication is used. As
phase segregated communication schemes uses phases individually and the PLC is
typically connected single-phase or phase-to-phase it is not possible to evaluate
which of the phases to release and the unblocking scheme has thus not been supported.

13.2.2.5

Intertrip scheme
In the direct intertrip scheme, the carrier send signal CS is sent from an
underreaching zone that is tripping the line.
The received signal per phase is directly transferred to the trip function block for
tripping without local criteria. The signal is not further processed in the phase
segregated communication logic. In case of single-pole tripping the phase selection
and logic for tripping the three phases is performed in the trip function block.

720
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.2.2.6

Simplified logic diagram


The simplified logic diagram for one phase is shown in figure 392.
SchemeType =
Intertrip
CSURLx
tSendMin

BLOCK
CSBLKLx
CRLx

AND

OR

AND

OR

Scheme Type =
Permissive UR

AND

AND
CACCLx

CSLx

OR

OR

tCoord
t

25 ms
t

TRLx

Scheme Type =
Permissive OR
OR

CSORLx

AND

AND
tSendMin
OR
AND

Scheme Type =
Blocking
BLKCSx

AND

CSL1
CSL2

AND

CSL2
CSL3

AND

OR

CSMPH

CSL3
CSL1

AND

CSL1
CSL2

OR

GENERAL

CSL3

IEC06000311_2_en.vsd
IEC06000311 V2 EN

Figure 392:

Simplified logic diagram for one phase

721
Technical reference manual

Section 13
Scheme communication
13.2.3

1MRK 505 222-UEN B

Function block
ZC1PPSCH
BLOCK
BLKTR
BLKTRL1
BLKTRL2
BLKTRL3
CACCL1
CACCL2
CACCL3
CSURL1
CSURL2
CSURL3
CSORL1
CSORL2
CSORL3
CSBLKL1
CSBLKL2
CSBLKL3
BLKCSL1
BLKCSL2
BLKCSL3
CRL1
CRL2
CRL3
CRMPH

TRIP
TRL1
TRL2
TRL3
CSL1
CSL2
CSL3
CSMPH
CRLL1
CRLL2
CRLL3

IEC06000427-2-en.vsd
IEC06000427 V2 EN

Figure 393:

13.2.4

ZC1PPSCH function block

Input and output signals


Table 424:
Name

ZC1PPSCH Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Common signal for block of trip output from


communication logic in all phases

BLKTRL1

BOOLEAN

Signal for block of trip output from communication


logic in Phase L1

BLKTRL2

BOOLEAN

Signal for block of trip output from communication


logic in Phase L2

BLKTRL3

BOOLEAN

Signal for block of trip output from communication


logic in Phase L3

CACCL1

BOOLEAN

Accelerated Distance protection zone start in


Phase L1

CACCL2

BOOLEAN

Accelerated Distance protection zone signal in


Phase L2

CACCL3

BOOLEAN

Accelerated Distance protection zone signal in


Phase L3

CSURL1

BOOLEAN

Underreaching distance protection zone signal in


Phase L1

CSURL2

BOOLEAN

Underreaching distance protection zone signal in


Phase L2

CSURL3

BOOLEAN

Underreaching distance protection zone signal in


Phase L3

Table continues on next page

722
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Name

Type

Default

Description

CSORL1

BOOLEAN

Overreaching distance protection zone signal in


Phase L1

CSORL2

BOOLEAN

Overreaching distance protection zone signal in


Phase L2

CSORL3

BOOLEAN

Overreaching distance protection zone signal in


Phase L3

CSBLKL1

BOOLEAN

Reverse directed distance protection zone signal


in Phase L1

CSBLKL2

BOOLEAN

Reverse directed distance protection zone signal


in Phase L2

CSBLKL3

BOOLEAN

Reverse directed distance protection zone signal


in Phase L3

BLKCSL1

BOOLEAN

Block of carrier send in POR and Blocking


schemes in Phase L1

BLKCSL2

BOOLEAN

Block of carrier send in POR and Blocking


schemes in Phase L2

BLKCSL3

BOOLEAN

Block of carrier send in POR and Blocking


schemes in Phase L3

CRL1

BOOLEAN

Carrier signal received in Phase L1

CRL2

BOOLEAN

Carrier signal received in Phase L2

CRL3

BOOLEAN

Carrier signal received in Phase L3

CRMPH

BOOLEAN

Carrier Signal received for multiphase fault

Table 425:
Name

ZC1PPSCH Output signals


Type

Description

TRIP

BOOLEAN

Common trip output in any of the phase

TRL1

BOOLEAN

Trip output in Phase L1

TRL2

BOOLEAN

Trip output in Phase L2

TRL3

BOOLEAN

Trip output in Phase L3

CSL1

BOOLEAN

Carrier Send in phase L1

CSL2

BOOLEAN

Carrier Send in phase L2

CSL3

BOOLEAN

Carrier Send in phase L3

CSMPH

BOOLEAN

carrier Send for multi phase fault

CRLL1

BOOLEAN

Carrier signal received in Phase L1

CRLL2

BOOLEAN

Carrier signal received in Phase L2

CRLL3

BOOLEAN

Carrier signal received in Phase L3

723
Technical reference manual

Section 13
Scheme communication
13.2.5
Table 426:
Name

1MRK 505 222-UEN B

Setting parameters
ZC1PPSCH Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation On / Off

Scheme Type

Off
Intertrip
Permissive UR
Permissive OR
Blocking

Permissive UR

Scheme type

tCoord

0.000 - 60.000

0.001

0.000

Trip coordinate time

tSendMin

0.000 - 60.000

0.001

0.100

Minimum duration of Carrier Send signal

13.2.6

Technical data
Table 427:

ZC1PPSCH technical data

Function

13.3

Accuracy

Intertrip
Permissive UR
Permissive OR
Blocking

Co-ordination time for blocking


communication scheme

(0.000-60.000) s

0.5% 10 ms

Minimum duration of a carrier send


signal

(0.000-60.000) s

0.5% 10 ms

Security timer for loss of carrier


guard detection

(0.000-60.000) s

0.5% 10 ms

Operation mode of unblocking logic

Off
NoRestart
Restart

Current reversal and weak-end infeed logic for


distance protection ZCRWPSCH
Function description
Current reversal and weak-end infeed
logic for distance protection

13.3.1

Range or value

Scheme type

IEC 61850
identification
ZCRWPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlap on the parallel line.

724
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.
Three phase or phase segregated scheme logic is available.

13.3.2

Principle of operation

13.3.2.1

Current reversal logic


The current reversal logic uses a reverse zone connected to the input IRV to
recognize the fault on the parallel line in any of the phases. When the reverse zone
has been activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the receive signal to reset before the trip signal is
activated due to the current reversal by the forward directed zone, see figure 394.

IRV

tPickUpRev 10 ms tPickUpRev
t
t
t
AND

IRVBLK

tDelayRev
t

IRVL

en05000122_2_en.vsd
IEC05000122 V2 EN

Figure 394:

Current reversal logic

The preventing of sending the send signal CS and activating of the TRIP in the
scheme communication block ZCPSCH is carried out by connecting the IRVL
signal to input BLOCK in the ZCPSCH function.
The function has an internal 10 ms drop-off timer which secure that the current
reversal logic will be activated for short input signals even if the pick-up timer is
set to zero.

13.3.2.2

Weak-end infeed logic


The weak-end infeed logic (WEI) function sends back (echoes) the received signal
under the condition that no fault has been detected on the weak-end by different
fault detection elements (distance protection in forward and reverse direction).
The WEI function returns the received signal, see figure 395, when:

725
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

No active signal present on the input BLOCK.


The functional input CRL is active. This input is usually connected to the CRL
output on the scheme communication logic ZCPSCH .
The WEI function is not blocked by the active signal connected to the
WEIBLK1 functional input or to the VTSZ functional input. The later is
usually configured to the BLOCK functional output of the fuse-failure function.
No active signal has been present for at least 200 ms on the WEIBLK2
functional input. An OR combination of all fault detection functions (not
undervoltage) as present within the IED is usually used for this purpose.

IEC05000123 V1 EN

Figure 395:

Echo of a received signal by the WEI function

When an echo function is used in both IEDs (should generally be avoided), a


spurious signal can be looped round by the echo logics. To avoid a continuous lockup of the system, the duration of the echoed signal is limited to 200 ms.
An undervoltage criteria is used as an additional tripping criteria, when the tripping
of the local breaker is selected, setting WEI = Echo&Trip, together with the WEI
function and ECHO signal has been issued by the echo logic, see figure 396.

IEC00000551-TIFF V1 EN

Figure 396:

Tripping part of the WEI logic, simplified diagram

726
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.3.3

Function block
ZCRWPSCH
U3P*
BLOCK
IRVBLK
IRV
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL

IRVL
TRWEI
TRWEIL1
TRWEIL2
TRWEIL3
ECHO

IEC06000287-2-en.vsd
IEC06000287 V2 EN

Figure 397:

13.3.4

ZCRWPSCH function block

Input and output signals


Table 428:
Name

ZCRWPSCH Input signals


Type

Default

Description

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

IRVBLK

BOOLEAN

Block of current reversal function

IRV

BOOLEAN

Activation of current reversal logic

WEIBLK1

BOOLEAN

Block of WEI logic

WEIBLK2

BOOLEAN

Block of WEI logic due to operation of other


protections

VTSZ

BOOLEAN

Block of trip from WEI logic through fuse-failure


function

CBOPEN

BOOLEAN

Block of trip from WEI logic by an open breaker

CRL

BOOLEAN

POR Carrier receive for WEI logic

Table 429:
Name

ZCRWPSCH Output signals


Type

Description

IRVL

BOOLEAN

Operation of current reversal logic

TRWEI

BOOLEAN

Trip of WEI logic

TRWEIL1

BOOLEAN

Trip of WEI logic in phase L1

TRWEIL2

BOOLEAN

Trip of WEI logic in phase L2

TRWEIL3

BOOLEAN

Trip of WEI logic in phase L3

ECHO

BOOLEAN

Carrier send by WEI logic

727
Technical reference manual

Section 13
Scheme communication
13.3.5
Table 430:
Name

1MRK 505 222-UEN B

Setting parameters
ZCRWPSCH Group settings (basic)
Values (Range)

Unit

Step

Default

Description

CurrRev

Off
On

Off

Operating mode of Current Reversal


Logic

tPickUpRev

0.000 - 60.000

0.001

0.020

Pickup time for current reversal logic

tDelayRev

0.000 - 60.000

0.001

0.060

Time Delay to prevent Carrier send and


local trip

WEI

Off
Echo
Echo & Trip

Off

Operating mode of WEI logic

tPickUpWEI

0.000 - 60.000

0.001

0.010

Coordination time for the WEI logic

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

UPP<

10 - 90

%UB

70

Phase to Phase voltage for detection of


fault condition

UPN<

10 - 90

%UB

70

Phase to Neutral voltage for detection of


fault condition

13.3.6

Technical data
Table 431:

ZCRWPSCH technical data

Function

13.4

Range or value

Accuracy

Detection level phase-to-neutral


voltage

(10-90)% of UBase

0.5% of Ur

Detection level phase-to-phase


voltage

(10-90)% of UBase

0.5% of Ur

Reset ratio

<105%

Operate time for current reversal


logic

(0.000-60.000) s

0.5% 10 ms

Delay time for current reversal

(0.000-60.000) s

0.5% 10 ms

Coordination time for weak-end


infeed logic

(0.000-60.000) s

0.5% 10 ms

Local acceleration logic ZCLCPLAL


Function description
Local acceleration logic

IEC 61850
identification
ZCLCPLAL

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

728
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.4.1

Introduction
To achieve fast clearing of faults on the whole line, when no communication
channel is available, local acceleration logic (ZCLCPLAL) can be used. This logic
enables fast fault clearing during certain conditions, but naturally, it can not fully
replace a communication channel.
The logic can be controlled either by the autorecloser (zone extension) or by the lossof-load current (loss-of-load acceleration).

13.4.2

Principle of operation

13.4.2.1

Zone extension
The overreaching zone is connected to the input EXACC. For this reason,
configure the ARREADY functional input to a READY functional output of a used
autoreclosing function or via the selected binary input to an external autoreclosing
device, see figure 398.
This will allow the overreaching zone to trip instantaneously.

IEC05000157 V1 EN

Figure 398:

Simplified logic diagram for local acceleration logic

After the autorecloser initiates the close command and remains in the reclaim state,
there will be no ARREADY signal, and the protection will trip normally with step
distance time functions.
In case of a fault on the adjacent line within the overreaching zone range, an
unwanted autoreclosing cycle will occur. The step distance function at the
reclosing attempt will prevent an unwanted retrip when the breaker is reclosed.
On the other hand, at a persistent line fault on line section not covered by
instantaneous zone (normally zone 1) only the first trip will be "instantaneous".
The function will be blocked if the input BLOCK is activated (common with loss-ofload acceleration).

729
Technical reference manual

Section 13
Scheme communication
13.4.2.2

1MRK 505 222-UEN B

Loss-of-Load acceleration
When the "acceleration" is controlled by a loss-of-load, the overreaching zone used
for "acceleration" connected to input LLACC is not allowed to trip
"instantaneously" during normal non-fault system conditions. When all three-phase
currents have been above the set value MinCurr for more than setting tLowCurr, an
overreaching zone will be allowed to trip "instantaneously" during a fault condition
when one or two of the phase currents will become low due to a three-phase trip at
the opposite IED, see figure 399. The current measurement is performed internally
and the internal STILL signal becomes logical one under the described conditions.
The load current in a healthy phase is in this way used to indicate the tripping at the
opposite IED. Note that this function will not operate in case of three-phase faults,
because none of the phase currents will be low when the opposite IED is tripped.

IEC05000158 V1 EN

Figure 399:

Loss-of-load acceleration - simplified logic diagram

Breaker closing signals can if decided be connected to block the function during
normal closing.

13.4.3

Function block
ZCLCPLAL
I3P*
BLOCK
ARREADY
NDST
EXACC
BC
LLACC

TRZE
TRLL

IEC05000333-2-en.vsd
IEC05000333 V2 EN

Figure 400:

ZCLCPLAL function block

730
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.4.4

Input and output signals


Table 432:

ZCLCPLAL Input signals

Name

Type
GROUP
SIGNAL

Group signal for current input

BLOCK

BOOLEAN

Block of function

ARREADY

BOOLEAN

Autoreclosure ready, releases function used for


fast trip

NDST

BOOLEAN

Non directional criteria used to prevent


instantaneous trip

EXACC

BOOLEAN

Connected to function used for tripping at zone


extension

BC

BOOLEAN

Breaker Close

LLACC

BOOLEAN

Connected to function used for tripping at loss of


load

ZCLCPLAL Output signals

Name

Table 434:

Description

I3P

Table 433:

13.4.5

Default

Type

Description

TRZE

BOOLEAN

Trip by zone extension

TRLL

BOOLEAN

Trip by loss of load

Setting parameters
ZCLCPLAL Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base setting for current values

LoadCurr

1 - 100

%IB

10

Load current before disturbance in % of


IBase

LossOfLoad

Off
On

Off

Enable/Disable operation of Loss of load.

ZoneExtension

Off
On

Off

Enable/Disable operation of Zone


extension

MinCurr

1 - 100

%IB

Lev taken as curr loss due to remote CB


trip in % of IBase

tLowCurr

0.000 - 60.000

0.001

0.200

Time delay on pick-up for MINCURR


value

tLoadOn

0.000 - 60.000

0.001

0.000

Time delay on pick-up for load current


release

tLoadOff

0.000 - 60.000

0.001

0.300

Time delay on drop off for load current


release

731
Technical reference manual

Section 13
Scheme communication

13.5

Scheme communication logic for residual


overcurrent protection ECPSCH
Function description
Scheme communication logic for
residual overcurrent protection

13.5.1

1MRK 505 222-UEN B

IEC 61850
identification
ECPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
To achieve fast fault clearance of earth faults on the part of the line not covered by
the instantaneous step of the residual overcurrent protection, the directional
residual overcurrent protection can be supported with a logic that uses
communication channels.
In the directional scheme, information of the fault current direction must be
transmitted to the other line end. With directional comparison, a short operate time
of the protection including a channel transmission time, can be achieved. This short
operate time enables rapid autoreclosing function after the fault clearance.
The communication logic module for directional residual current protection
enables blocking as well as permissive under/overreaching schemes. The logic can
also be supported by additional logic for weak-end infeed and current reversal,
included in Current reversal and weak-end infeed logic for residual overcurrent
protection (ECRWPSCH) function.

13.5.2

Principle of operation
The four step directional residual overcurrent protection EF4PTOC is configured to
give input information, that is directional fault detection signals, to the ECPSCH
logic:

Input signal CACC is used for tripping of the communication scheme,


normally the start signal of a forward overreaching step of STFW.
Input signal CSBLK is used for sending block signal in the blocking
communication scheme, normally the start signal of a reverse overreaching
step of STRV.
Input signal CSUR is used for sending permissive signal in the underreaching
permissive communication scheme, normally the start signal of a forward
underreaching step of STINn, where n corresponds to the underreaching step.
Input signal CSOR is used for sending permissive signal in the overreaching
permissive communication scheme, normally the start signal of a forward
overreaching step of STINn, where n corresponds to the overreaching step.

In addition to this a signal from the autoreclosing function should be configured to


the BLKCS input for blocking of the function at a single phase reclosing cycle.
732
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.5.2.1

Blocking scheme
In the blocking scheme a signal is sent to the other line end if the directional
element detects an earth fault in the reverse direction. When the forward directional
element operates, it trips after a short time delay if no blocking signal is received
from the opposite line end. The time delay, normally 30 40 ms, depends on the
communication transmission time and a chosen safety margin.
One advantage of the blocking scheme is that only one channel (carrier frequency)
is needed if the ratio of source impedances at both end is approximately equal for
zero and positive sequence source impedances, the channel can be shared with the
impedance measuring system, if that system also works in the blocking mode. The
communication signal is transmitted on a healthy line and no signal attenuation will
occur due to the fault.
Blocking schemes are particular favorable for three-terminal applications if there is
no zero-sequence outfeed from the tapping. The blocking scheme is immune to
current reversals because the received signal is maintained long enough to avoid
unwanted operation due to current reversal. There is never any need for weak-end
infeed logic, because the strong end trips for an internal fault when no blocking
signal is received from the weak end. The fault clearing time is however generally
longer for a blocking scheme than for a permissive scheme.
If the fault is on the line, the forward direction measuring element operates. If no
blocking signal comes from the other line end via the CR binary input (received
signal) the TRIP output is activated after the tCoord set time delay.

IEC05000448 V1 EN

Figure 401:

13.5.2.2

Simplified logic diagram for blocking scheme

Permissive under/overreaching scheme


In the permissive scheme the forward directed earth-fault measuring element sends
a permissive signal to the other end, if an earth fault is detected in the forward
733

Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

direction. The directional element at the other line end must wait for a permissive
signal before activating a trip signal. Independent channels must be available for
the communication in each direction.
An impedance measuring IED, which works in the same type of permissive mode,
with one channel in each direction, can share the channels with the communication
scheme for residual overcurrent protection. If the impedance measuring IED works
in the permissive overreaching mode, common channels can be used in single line
applications. In case of double lines connected to a common bus at both ends, use
common channels only if the ratio Z1S/Z0S (positive through zero-sequence source
impedance) is about equal at both ends. If the ratio is different, the impedance
measuring and the directional earth-fault current system of the healthy line may
detect a fault in different directions, which could result in unwanted tripping.
Common channels cannot be used when the weak-end infeed function is used in
the distance or earth-fault protection.
In case of an internal earth-fault, the forward directed measuring element operates
and sends a permissive signal to the remote end via the CS output (sent signal).
Local tripping is permitted when the forward direction measuring element operates
and a permissive signal is received via the CR binary input (received signal).
The permissive scheme can be of either underreaching or overreaching type. In the
underreaching alternative, an underreaching directional residual overcurrent
measurement element will be used as sending criterion of the permissive input
signal CSUR.
In the overreaching alternative, an overreaching directional residual overcurrent
measurement element will be used as sending criterion of the permissive input
signal CSOR. Also the underreaching input signal CSUR can initiate sending.

734
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

BLOCK

CRL

AND

CR

25 ms
0 - 60 s
AND

CACC

AND

t
tCoord

TRIP

t
50 ms
t

AND
BLKCS
AND
Overreach
CSOR

OR

CS

AND

CSUR

OR

en05000280_2_en.vsd
IEC05000280 V2 EN

13.5.2.3

Unblocking scheme
In unblocking scheme, the lower dependability in permissive scheme is overcome
by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable, power line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 402. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signaling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.

735
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

CR
1

tSecurity
t

CRG
200 ms
t

CRL

>1
150 ms

AND

OR

AND
LCG

en05000746.vsd
IEC05000746 V1 EN

Figure 402:

Guard signal logic with unblocking scheme

The unblocking function can be set in three operation modes (setting Unblock):
Off:

The unblocking function is out of operation

No restart:

Communication failure shorter than tSecurity will be ignored


If CRG disappears, a CRL signal will be transferred to the trip logic
There will not be any information in case of communication failure (LCG)
Communication failure shorter than tSecurity will be ignored

Restart

It sends a defined (150 ms) CRL after the disappearance of the CRG signal
The function will activate LCG output in case of communication failure
If the communication failure comes and goes (<200 ms) there will not be recurrent
signaling

13.5.3

Function block
ECPSCH
BLOCK
BLKTR
BLKCS
CSBLK
CACC
CSOR
CSUR
CR
CRG

TRIP
CS
CRL
LCG

IEC06000288-2-en.vsd
IEC06000288 V2 EN

Figure 403:

ECPSCH function block

736
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.5.4

Input and output signals


Table 435:

ECPSCH Input signals

Name

Type
BOOLEAN

Block of function

BLKTR

BOOLEAN

Signal for blocking trip due to communication logic

BLKCS

BOOLEAN

Signal for blocking CS in Overreach and Blocking


schemes

CSBLK

BOOLEAN

Reverse residual overcurrent signal for Carrier


Send

CACC

BOOLEAN

Signal to be used for tripping by Communication


Scheme

CSOR

BOOLEAN

Overreaching residual overcurrent signal for


Carrier Send

CSUR

BOOLEAN

Underreaching residual overcurrent signal for


Carrier Send

CR

BOOLEAN

Carrier Receive for Communication Scheme Logic

CRG

BOOLEAN

Carrier guard signal received

ECPSCH Output signals

Name

Table 437:

Description

BLOCK

Table 436:

13.5.5

Default

Type

Description

TRIP

BOOLEAN

Trip by Communication Scheme Logic

CS

BOOLEAN

Carrier Send by Communication Scheme Logic

CRL

BOOLEAN

Carrier Receive from Communication Scheme


Logic

LCG

BOOLEAN

loss of carrier guard signal

Setting parameters
ECPSCH Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

SchemeType

Off
Intertrip
Permissive UR
Permissive OR
Blocking

Permissive UR

Scheme type, Mode of Operation

tCoord

0.000 - 60.000

0.001

0.035

Communication scheme coordination


time

tSendMin

0.000 - 60.000

0.001

0.100

Minimum duration of a carrier send signal

737
Technical reference manual

Section 13
Scheme communication

Table 438:
Name

1MRK 505 222-UEN B

ECPSCH Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

Unblock

Off
NoRestart
Restart

Off

Operation mode of unblocking logic

tSecurity

0.000 - 60.000

0.001

0.035

Security timer for loss of carrier guard


detection

13.5.6

Technical data
Table 439:

ECPSCH technical data

Function

13.6

Range or value
Permissive Underreaching
Permissive Overreaching
Blocking

Communication scheme
coordination time

(0.000-60.000) s

0.5% 10 ms

Current reversal and weak-end infeed logic for


residual overcurrent protection ECRWPSCH
Function description
Current reversal and weak-end infeed
logic for residual overcurrent protection

13.6.1

Accuracy

Scheme type

IEC 61850
identification
ECRWPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
The Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH is a supplement to Scheme communication logic for residual
overcurrent protection ECPSCH.
To achieve fast fault clearing for all earth faults on the line, the directional earthfault protection function can be supported with logic that uses communication
channels.
The 670 series IEDs have for this reason available additions to scheme
communication logic.
If parallel lines are connected to common busbars at both terminals, overreaching
permissive communication schemes can trip unselectively due to fault current
reversal. This unwanted tripping affects the healthy line when a fault is cleared on
the other line. This lack of security can result in a total loss of interconnection
between the two buses. To avoid this type of disturbance, a fault current reversal
logic (transient blocking logic) can be used.

738
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Permissive communication schemes for residual overcurrent protection can


basically operate only when the protection in the remote IED can detect the fault.
The detection requires a sufficient minimum residual fault current, out from this
IED. The fault current can be too low due to an opened breaker or high-positive and/
or zero-sequence source impedance behind this IED. To overcome these
conditions, weak-end infeed (WEI) echo logic is used.

13.6.2

Principle of operation

13.6.2.1

Directional comparison logic function


The directional comparison function contains logic for blocking overreaching and
permissive overreaching schemes.
The circuits for the permissive overreaching scheme contain logic for current
reversal and weak-end infeed functions. These functions are not required for the
blocking overreaching scheme.
Use the independent or inverse time functions in the directional earth-fault
protection module to get back-up tripping in case the communication equipment
malfunctions and prevents operation of the directional comparison logic.
Figure 404 and figure 405 show the logic circuits.
Connect the necessary signal from the autorecloser for blocking of the directional
comparison scheme, during a single-phase autoreclosing cycle, to the BLOCK
input of the directional comparison module.

13.6.2.2

Fault current reversal logic


The fault current reversal logic uses a reverse directed element, connected to input
signal IRV, which recognizes that the fault is in reverse direction. When the
reverse direction element is activated during the tPickUpRev time, the output signal
IRVL is activated, see figure 404. The logic is now ready to handle a current
reversal without tripping. Output signal IRVL will be connected to the block input
on the permissive overreaching scheme.
When the fault current is reversed on the non faulty line, IRV is deactivated and
IRVBLK is activated. The reset of IRVL is delayed by the tDelayRev time, see
figure 404. This ensures the reset of the received CR signal.

739
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

BLOCK
0-60 s
t

IRV
IRVBLK

tPickUpRev

10 ms
t

0-60 s
t

AND

tPickUpRev

0-60 s
t

IRVL

tDelayRev

IEC09000031-1-en.vsd
IEC09000031 V1 EN

Figure 404:

13.6.2.3

Simplified logic diagram, current reversal

Weak-end infeed logic


The weak-end infeed function can be set to send only an echo signal (WEI=Echo)
or an echo signal and a trip signal (WEI=Echo & Trip). See figure 405 and figure
406.
The weak-end infeed logic uses normally a reverse and a forward direction
element, connected to WEIBLK1 via an OR-gate. See figure 405. If neither the
forward nor the reverse directional measuring element is activated during the last
200 ms, the weak-end infeed logic echoes back the received permissive signal. See
figure 405.
If the forward or the reverse directional measuring element is activated during the
last 200 ms, the fault current is sufficient for the IED to detect the fault with the
earth-fault function that is in operation.
BLOCK
200 ms
t

WEIBLK1
CRL

&

50 ms
t

200 ms
t

AND

ECHO

WEI = Echo
IEC09000032-1-en.vsd
IEC09000032 V1 EN

Figure 405:

Simplified logic diagram, weak-end infeed - Echo

With the Echo & Trip setting, the logic sends an echo according to above. Further,
it activates the TRWEI signal to trip the breaker if the echo conditions are fulfilled
and the neutral point voltage is above the set operate value for 3U0>.
The voltage signal that is used to calculate the zero sequence voltage is set in the
earth-fault function that is in operation.

740
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

BLOCK
200 ms
t

WEIBLK1
CRL

50 ms
t

AND

200 ms
t

ECHO

AND

AND

WEI = Echo&Trip
ST3U0

TRWEI

AND

CBOPEN
IEC09000020-1-en.vsd
IEC09000020 V1 EN

Figure 406:

Simplified logic diagram, weak-end infeed - Echo & Trip

The weak-end infeed echo sent to the strong line end has a maximum duration of
200 ms. When this time period has elapsed, the conditions that enable the echo
signal to be sent are set to zero for a time period of 50 ms. This avoids ringing
action if the weak-end echo is selected for both line ends.

13.6.3

Function block
ECRWPSCH
U3P*
BLOCK
IRVBLK
IRV
WEIBLK1
WEIBLK2
VTSZ
CBOPEN
CRL

IRVL
TRWEI
ECHO
CR

IEC06000289-2-en.vsd
IEC06000289 V2 EN

Figure 407:

13.6.4

ECRWPSCH function block

Input and output signals


Table 440:
Name

ECRWPSCH Input signals


Type

Default

Description

U3P

GROUP
SIGNAL

Group signal for voltage input

BLOCK

BOOLEAN

Block of function

IRVBLK

BOOLEAN

Block of current reversal function

IRV

BOOLEAN

Activation of current reversal logic

WEIBLK1

BOOLEAN

Block of WEI Logic

WEIBLK2

BOOLEAN

Block of WEI logic due to operation of other


protections

VTSZ

BOOLEAN

Block of trip from WEI logic through fuse-failure


function

CBOPEN

BOOLEAN

Block of trip from WEI logic by an open breaker

CRL

BOOLEAN

POR Carrier receive for WEI logic


741

Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Table 441:

ECRWPSCH Output signals

Name

13.6.5
Table 442:
Name

Type

Description

IRVL

BOOLEAN

Operation of current reversal logic

TRWEI

BOOLEAN

Trip of WEI logic

ECHO

BOOLEAN

Carrier send by WEI logic

CR

BOOLEAN

POR Carrier signal received from remote end

Setting parameters
ECRWPSCH Group settings (basic)
Values (Range)

Unit

Step

Default

Description

CurrRev

Off
On

Off

Operating mode of Current Reversal


Logic

tPickUpRev

0.000 - 60.000

0.001

0.020

Pickup time for current reversal logic

tDelayRev

0.000 - 60.000

0.001

0.060

Time Delay to prevent Carrier send and


local trip

WEI

Off
Echo
Echo & Trip

Off

Operating mode of WEI logic

tPickUpWEI

0.000 - 60.000

0.001

0.000

Coordination time for the WEI logic

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level

3U0>

5 - 70

%UB

25

Neutral voltage setting for fault


conditions measurement

13.6.6

Technical data
Table 443:

ECRWPSCH technical data

Function

Range or value

Accuracy

Operating mode of WEI logic

Off
Echo
Echo & Trip

Operate voltage 3Uo for WEI trip

(5-70)% of UBase

0.5% of Ur

Reset ratio

>95%

Operate time for current reversal


logic

(0.000-60.000) s

0.5% 10 ms

Delay time for current reversal

(0.000-60.000) s

0.5% 10 ms

Coordination time for weak-end


infeed logic

(0.00060.000) s

0.5% 10 ms

742
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.7

Current reversal and weak-end infeed logic for


phase segregated communication ZC1WPSCH
Function description
Current reversal and weak-end infeed
logic for phase segregated
communication

13.7.1

IEC 61850
identification
ZC1WPSCH

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
85

Introduction
Current reversal and weak-end infeed logic for phase segregated communication
(ZC1WPSCH) function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlaps on the parallel line.
The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When
activated, received carrier signal together with local under voltage criteria and no
reverse zone operation gives an instantaneous trip. The received signal is also
echoed back to accelerate the sending end.

13.7.2

Principle of operation

13.7.2.1

Current reversal logic


The current reversal logic uses a reverse zone connected to the input IRVLx to
recognize the fault on the parallel line in phase Lx. When the reverse zone has been
activated for a certain settable time tPickUpRev it prevents sending of a
communication signal and activation of trip signal for a predefined time tDelayRev.
This makes it possible for the carrier receive signal to reset before the carrier aided
trip signal is activated due to the current reversal by the forward directed zone, see
figure 408.

IRVLn

tPickUpRev 10 ms
t
t

tPickUpRev
t
&

IRVBLKLn

tDelayRev
t

IRVOPLn

IEC06000474_2_en.vsd
IEC06000474 V2 EN

Figure 408:

Current reversal logic

The preventing of sending carrier send signal CSLn and activating of the TRIPLn
in the Scheme communication logic for distance or Overcurrent protection
743
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

(ZCPSCH) is carried out by connecting the IRVOPLn signal to input BLOCKLn in


ZCPSCH function.
The Current reversal and weak-end infeed logic for phase segregated
communication (ZC1WPSCH) function has an internal 10 ms drop-off timer which
secure that the current reversal logic will be activated for short input signals even if
the pick-up timer is set to zero.
Weak-end infeed logic
The WEI function sends back (echoes) the received carrier signal under the
condition that no fault has been detected at the weak end by different fault
detection elements (distance protection in forward and reverse direction).
VTSZ
BLOCK
CRLn

>1
tWEI
t

&

50 ms
t

ECHOLn - cont.

200 ms
t
&

WEIBLKL1

200 ms
t

WEIBLKL2

200 ms
t

ECHOLn

IEC07000085_2_en.vsd
IEC07000085 V2 EN

Figure 409:

Weak-end infeed logic

The WEI function returns the received carrier signal, see figure 409, when:

The input CRLx is active. This input is usually connected to the CRLx output
on the scheme communication logic for distance or Overcurrent protection
(ZCPSCH).
The WEI function is not blocked by the active signal connected to the
WEIBLKLx input or to the VTSZ input. The later is usually configured to the
STGEN output of the fuse-failure function.
No active signal has been present for at least 200 ms on the WEIBLK2 input.
An OR combination of all fault detection functions (not undervoltage) as
present within the IED is usually used for this purpose.

When an echo function is used in both IEDs (should generally be avoided), a


spurious signal can be looped round by the echo logics. To avoid a continuous lockup of the system, the duration of the echoed signal is limited to 200 ms. An
undervoltage criteria is used as an additional tripping criteria, when the tripping of
the local breaker is selected, setting WEI = Echo &Trip, together with the WEI
function and ECHO signal has been issued by the echo logic, see figure 410.

744
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

WEI = Echo&Trip

ECHOLn - cont.

CBOPEN
STUL1N
STUL2N

AND

100 ms
t

OR

STUL3N

OR

TRWEI

AND

15 ms
t

TRWEIL1

AND

15 ms
t

TRWEIL2

AND

15 ms
t

TRWEIL3

en00000551.vsd
IEC00000551-WMF V1 EN

Figure 410:

13.7.3

Tripping part of the WEI logic, simplified diagram

Function block
ZC1WPSCH
U3P*
TRPWEI
BLOCK
TRPWEIL1
BLKZ
TRPWEIL2
CBOPEN
TRPWEIL3
CRL1
IRVOP
CRL2
IRVOPL1
CRL3
IRVOPL2
IRVL1
IRVOPL3
IRVL2
ECHO
IRVL3
ECHOL1
IRVBLKL1
ECHOL2
IRVBLKL2
ECHOL3
IRVBLKL3
WEIBLK
WEIBLKL1
WEIBLKL2
WEIBLKL3
WEIBLKOP
WEIBLKO1
WEIBLKO2
WEIBLKO3
IEC06000477-2-en.vsd
IEC06000477 V2 EN

Figure 411:

ZC1WPSCH function block

745
Technical reference manual

Section 13
Scheme communication
13.7.4

1MRK 505 222-UEN B

Input and output signals


Table 444:
Name

ZC1WPSCH Input signals


Type

Default

Description

U3P

GROUP
SIGNAL

Voltage

BLOCK

BOOLEAN

Block of function

BLKZ

BOOLEAN

Block of trip from WEI logic by the fuse-failure


function

CBOPEN

BOOLEAN

Block of trip from WEI logic by an open breaker

CRL1

BOOLEAN

Carrier receive for WEI logic in Phase L1

CRL2

BOOLEAN

Carrier receive for WEI logic in Phase L2

CRL3

BOOLEAN

Carrier receive for WEI logic in Phase L3

IRVL1

BOOLEAN

Activation of current reversal logic in Phase L1

IRVL2

BOOLEAN

Activation of current reversal logic in Phase L2

IRVL3

BOOLEAN

Activation of current reversal logic in phase L3

IRVBLKL1

BOOLEAN

Block of current reversal function in Phase L1

IRVBLKL2

BOOLEAN

Block of current reversal function in Phase L2

IRVBLKL3

BOOLEAN

Block of current reversal function in Phase L3

WEIBLK

BOOLEAN

Block of WEI logic

WEIBLKL1

BOOLEAN

Block of WEI logic in Phase L1

WEIBLKL2

BOOLEAN

Block of WEI logic in Phase L2

WEIBLKL3

BOOLEAN

Block of WEI logic in Phase L3

WEIBLKOP

BOOLEAN

Block of WEI logic due to operation of other


protection

WEIBLKO1

BOOLEAN

Block of WEI logic in Phase L1 due to operation


of other protection

WEIBLKO2

BOOLEAN

Block of WEI logic in Phase L2 due to operation


of other protections

WEIBLKO3

BOOLEAN

Block of WEI logic in Phase L3 due to operation


of other protections

Table 445:
Name

ZC1WPSCH Output signals


Type

Description

TRPWEI

BOOLEAN

Trip of WEI logic

TRPWEIL1

BOOLEAN

Trip of WEI logic in Phase L1

TRPWEIL2

BOOLEAN

Trip of WEI logic in Phase L2

TRPWEIL3

BOOLEAN

Trip of WEI logic in Phase L3

IRVOP

BOOLEAN

Operation of current reversal logic

IRVOPL1

BOOLEAN

Operation of current reversal logic in Phase L1

IRVOPL2

BOOLEAN

Operation of current reversal logic in Phase L2

IRVOPL3

BOOLEAN

Operation of current reversal logic in Phase L3

Table continues on next page

746
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Name

13.7.5
Table 446:

Type

Description

ECHO

BOOLEAN

Carrier Send by WEI logic

ECHOL1

BOOLEAN

Carrier Send by WEI logic in Phase L1

ECHOL2

BOOLEAN

Carrier Send by WEI logic in Phase L2

ECHOL3

BOOLEAN

Carrier Send by WEI logic in Phase L3

Setting parameters
ZC1WPSCH Group settings (basic)

Name

Values (Range)

Unit

Step

Default

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for Voltage level

OperCurrRev

Off
On

Off

Operating mode of Current Reversal


Logic

tPickUpRev

0.000 - 60.000

0.001

0.020

Pickup time for current reversal logic

tDelayRev

0.000 - 60.000

0.001

0.060

Time Delay to prevent Carrier send and


local trip

OperationWEI

Off
Echo
Echo & Trip

Off

Operating mode of WEI logic

UPE<

10 - 90

%UB

70

Phase to Earth voltage for detection of


fault condition

UPP<

10 - 90

%UB

70

Phase to Phase voltage for detection of


fault condition

tPickUpWEI

0.000 - 60.000

0.001

0.010

Coordination time for the WEI logic

13.7.6

Technical data
Table 447:

ZC1WPSCH technical data

Function

13.8

Description

Range or value

Accuracy

Detection level phase to neutral


voltage

(10-90)% of UBase

0.5% of Ur

Detection level phase to phase


voltage

(10-90)% of UBase

0.5% of Ur

Reset ratio

<105%

Operate time for current reversal

(0.000-60.000) s

0.5% 10 ms

Delay time for current reversal

(0.000-60.000) s

0.5% 10 ms

Coordination time for weak-end


infeed logic

(0.000-60.000) s

0.5% 10 ms

Direct transfer trip logic

747
Technical reference manual

Section 13
Scheme communication
13.8.1

1MRK 505 222-UEN B

Introduction
Direct transfer trip (DTT) logic is used together with Line distance protection
function or other type of line protection. One typical example for use of transfer
trip is given below. When Line distance protection function is extended to cover
power lines feeding the transformer directly and there is a fault in transformer
differential area, the transformer differential protection operates faster than line
protection. A trip command is sent to the remote end of the line. On remote end,
before sending a trip command to the circuit breaker, the certainty of a fault
condition is ensured by checking local criterion in DTT logic.
CR
TRIP

CS

DTT

TRIP
IDIFF>

VT1

Xsource

Line
CT1

CT2

CT3
Power
Transformer

Source

Load
en03000120.vsd

IEC03000120 V1 EN

Figure 412:

Direct transfer trip

On receiving the CR signal from remote end, Direct transfer trip logic needs to
check additional local criterion, before sending the trip signal to circuit breaker.
DTT logic can be handled in the following separate application functions:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Low active power and power factor protection LAPPGAPC


Sudden change in current variation SCCVPTOC
Compensated over and undervoltage protection COUVGAPC
Carrier receive logic LCCRPTRC
Zero sequence overvoltage protection LCZSPTOV
Negative sequence overvoltage protection LCNSPTOV
Zero sequence overcurrent protection LCZSPTOC
Negative sequence overcurrent protection LCNSPTOC
Three-phase overcurrent LCP3PTOC
Three-phase undercurrent LCP3PTUC

A composite scheme of these functions must be configured in PCM600


configuration tool, to make a complete DTT scheme as shown in Figure 413. The
different individual local criteria functions can also be used as direct tripping
protections, normally with a time delay.

748
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

CR1
CR2

Impedance protection
Low impedance protection

Breaker Failure

Backup trip of breaker failure


protection

Three phase overcurrent


CarrierReceiveLogic

CR1
CR2
Zero sequence overcurrent
protection

Analog input

I3P

LocalCheck
Negative sequence overcurrent
protection

CB Trip output

LCCRPTRC

Three phase undercurrent

U3P

OR

Zero sequence overvoltage


protection

Negative sequence overvoltage


protection

Compensated over and


undervoltage protection

Low active power and power


factor protection

Sudden change in current


variation

IEC09000773-1-en.vsd
IEC09000773 V1 EN

Figure 413:

13.8.2

Direct transfer trip scheme

Low active power and power factor protection LAPPGAPC


Function description
Low active power and power factor
protection

13.8.2.1

IEC 61850
identification
LAPPGAPC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
37_55

Introduction
Low active power and power factor protection (LAPPGAPC) function measures
power flow. It can be used for protection and monitoring of:

749
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

phase wise low active power


phase wise low power factor
phase wise reactive power and apparent power as service values

Following features are available:

13.8.2.2

Definite time stage for low active power protection


Definite time stage for low power factor protection
Individual enabling of Low active power and Low power factor functions
Low active power trip with 2 selection modes '1 out of 3' and '2 out of 3'
Phase wise calculated values of apparent power, reactive power, active power
and power factor are available as service values
Insensitive to small variations in voltage and current

Principle of operation
Low active power and low power factor protection (LAPPGAPC) calculates power
and power factor from voltage and current values. Trip signal must be set
independently for low active power and low power factor condition after definite
time delay.
Active power calculation
LAPPGAPC calculates single phase complex power of L1, L2 and L3 loop by
following equations. From this complex apparent power, the real and imaginary
parts can be respective active and reactive power values of respective phases. All
the apparent power values given out of the function are absolute values. The active
power is the real part of the calculated apparent power.

S L1 = U L1 I L1
EQUATION2243 V1 EN

(Equation 147)

S L2 = U L2 IL2
EQUATION2244 V1 EN

(Equation 148)

S L3 = U L3 I L3
EQUATION2245 V1 EN

(Equation 149)

Power factor calculation


Power factor is a ratio of active power to apparent power. The function calculates
power factor from the calculated values of active power and apparent power of L1,
L2 and L3 loop by following equation:

pf L1

PL1
S L1

EQUATION2246 V1 EN

(Equation 150)

750
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

pf L 2

PL 2
SL2
(Equation 151)

EQUATION2247 V1 EN

pf L 3

PL 3
SL3
(Equation 152)

EQUATION2248 V1 EN

Active power trip mode


The low active power functionality has a trip mode setting. According to this
setting, trip is activated if the low active power is detected in one out of three
phases or two out of three phases respectively. These two modes are user settable
through setting OpMode.
Zero clamping filtering
The function will do zero clamping to disable the calculation if the current and
voltage values of a particular phase are less than 30% of UBase for voltage and 3%
of IBase for current value.
Calculation
The active power setting value used for detection of under power must be given as
a three-phase value. The design starts to calculate internally the per phase value
from this setting and detect phase wise under power condition individually. The
power factor start value is common for all the three phases.
Phase wise analog values apparent power, active power, reactive power and power
factor are available as service values.
STLAPLx
P < LAP<

I3P

TRLAP

Calculation P and
pf
U3P

STLPFLx
pf < pf<

TRLPFLx

IEC10000011-1-en.vsd
IEC10000011 V1 EN

Figure 414:

Logic diagram of Low active power and low power factor protection
(LAPPGAPC)

751
Technical reference manual

Section 13
Scheme communication
13.8.2.3

1MRK 505 222-UEN B

Function block
LAPPGAPC
I3P*
U3P*
BLOCK
BLKTR

TRLAP
TRLPF
TRLPFL1
TRLPFL2
TRLPFL3
STLAP
STLPF
STLAPL1
STLAPL2
STLAPL3
STLPFL1
STLPFL2
STLPFL3
IEC09000763-1-en.vsd

IEC09000763 V1 EN

Figure 415:

13.8.2.4

LAPPGAPC function block

Input and output signals


Table 448:
Name

LAPPGAPC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase group signal for current

U3P

GROUP
SIGNAL

Three phase group signal for voltage

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block all trip signals of the funtction

Table 449:
Name

LAPPGAPC Output signals


Type

Description

TRLAP

BOOLEAN

Trip low active power

TRLPF

BOOLEAN

Trip low power factor

TRLPFL1

BOOLEAN

Trip low power factor phase 1

TRLPFL2

BOOLEAN

Trip low power factor phase 2

TRLPFL3

BOOLEAN

Trip low power factor phase 3

STLAP

BOOLEAN

Start low active power

STLPF

BOOLEAN

Start low power factor

STLAPL1

BOOLEAN

Start low active power phase 1

STLAPL2

BOOLEAN

Start low active power phase 2

STLAPL3

BOOLEAN

Start low active power phase 3

STLPFL1

BOOLEAN

Start low power factor phase 1

STLPFL2

BOOLEAN

Start low power factor phase 2

STLPFL3

BOOLEAN

Start low power factor phase 3

752
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.2.5
Table 450:

Setting parameters
LAPPGAPC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

IBase

1 - 99999

3000

Base Setting for current in A

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage in kV

SBase

1 - 50000

MVA

1200

Base Setting for power in MVA

OperationLAP

Off
On

Off

Operation low active power Off/On

OpMode

2 out of 3
1 out of 3

2 out of 3

Trip mode low active power 2out of 3 or


1 out of 3

LAP<

2.0 - 100.0

%SB

0.1

5.0

3 Phase start value for low active power


in % of SBase

tOpLAP

0.000 - 60.000

0.001

0.010

Time delay to operate for low active power

OperationLPF

Off
On

Off

Operation low power factor Off/On

LPF<

0.00 - 1.00

0.01

0.40

Start value for low power factor

tOpLPF

0.000 - 60.000

0.001

0.010

Time delay to operate for low power factor

13.8.2.6

Technical data
Table 451:

LAPPGAPC technical data

Function

Range or value

Accuracy

Operate value, low


active power

(2.0-100.0)% of SBase

1,0% of Sr

Reset ratio, low


active power

<105%

Transient overreach,
low active power

<20 % at = 100 ms

Operate value, low


power factor

0.00-1.00

1,0% of Sr

Reset ratio, low


power factor

<105%

Transient overreach,
low power factor

<20 % at = 100 ms

Timers

(0.000-60.000) s

0.5% 10 ms

Critical impulse time,


low active power

10 ms typically at 1.2 to 0.8xPset

Impulse margin time,


low active power

10 ms typically

753
Technical reference manual

Section 13
Scheme communication
13.8.3

1MRK 505 222-UEN B

Compensated over and undervoltage protection


COUVGAPC
Function description

IEC 61850
identification

Compensated over and undervoltage


protection

13.8.3.1

IEC 60617
identification

COUVGAPC

ANSI/IEEE C37.2
device number
59_27

Introduction
Compensated over and undervoltage protection (COUVGAPC) function calculates
the remote end voltage of the transmission line utilizing local measured voltage,
current and with the help of transmission line parameters, that is, line resistance,
reactance, capacitance and local shunt reactor. For protection of long transmission
line for in zone faults, COUVGAPCcan be incorporated with local criteria within
direct transfer trip logic to ensure tripping of the line only under abnormal conditions.

13.8.3.2

Principle of operation
Compensated over and undervoltage protection (COUVGAPC) function is phase
segregated and mainly used for local criteria check in Direct transfer trip. The
principle is to utilize local measured voltage and current to calculate the voltage at
the remote end of the line.
The main measured inputs to COUVGAPC are three-phase voltage and current
signals. COUVGAPCuses line resistance, reactance and line charging capacitance
to calculate the remote end voltage. It also takes the input for local shunt reactor,
connected at the line side of the line breaker, reactance value. The calculated
voltage is referred to as compensated voltage.
STOV
TROV

Over voltage
U3P

t
Compensated
voltage calculation

SWIPOS
EnShuntReactor

STOVLx

comparator

I3P

TRIPOVLx

STUVLx

&
Under voltage
comparator

TRIPUVLx
TRUV
STUV

IEC09000782-1-en.vsd
IEC09000782 V1 EN

Figure 416:

Logic diagram of Compensated over and undervoltage protection


(COUVGAPC)

754
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

The formula used for calculation of compensated voltage is as follows:


Uremote = Ulocal (Ilocal j x Ulocal/Xsr + j x Ulocal/Xcp) x Zsetting
Where:
Uremote

calculated voltage at the opposite side of line

Ulocal

measured local voltage

Ilocal

measured local current

Xsr

reactance of local line connected shunt reactor, if applicable

Xcp

half of equivalent reactance of line distributed capacitor

Above calculated compensated voltage is compared to preset over and under


voltage levels set as percentage of base voltage UBase. If the calculated voltage
exceeds setting in any phase, COUVGAPC generates start and trip signals for that
phase and common start and trip signals. Independent enabling for overvoltage and
undervoltage are available with definite time delay. If shunt reactor is not present
in the system, COUVGAPC does not include any effect of shunt reactor while
calculating the compensated voltage. This shunt reactor calculation is enabled
when both input SWIPOS is 1 and setting parameter EnShuntReactor is On. Run
time change in EnShuntReactor setting parameter restarts the IED and SWIPOS
input signal is used to enable/disable the shunt reactor calculations.
Calculations

All resistance and reactance considered in compensated voltage calculation are


primary side values.
Calculation of shunt reactor reactance in ohms from given MVAr rating:
2

X sr =

UN
QN
(Equation 153)

EQUATION2249 V1 EN

Where:

UN

line to line voltage

QN

is total three phase MVAr of shunt reactor

If total line capacitance (Ctotal) is known then half line capacitive reactance:

X cp

2
wCtotal

EQUATION2250 V1 EN

(Equation 154)

and if total line capacitive reactance XcTotal is known:

X cp

= 2 X cTotal

EQUATION2251 V1 EN

(Equation 155)

755
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Compensated voltage for all three phases is available as service values.

13.8.3.3

Function block
COUVGAPC
I3P*
U3P*
BLOCK
BLKTR
SWIPOS

TRUV
TROV
TRUVL1
TRUVL2
TRUVL3
TROVL1
TROVL2
TROVL3
STUV
STOV
STUVL1
STUVL2
STUVL3
STOVL1
STOVL2
STOVL3
IEC09000764-1-en.vsd

IEC09000764 V1 EN

Figure 417:

13.8.3.4

COUVGAPC function block

Input and output signals


Table 452:
Name

COUVGAPC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current inputs

U3P

GROUP
SIGNAL

Group signal for voltage inputs

BLOCK

BOOLEAN

Block of the function

BLKTR

BOOLEAN

Blocks all operate outputs

SWIPOS

BOOLEAN

Local shunt reactor connected or not

Table 453:
Name

COUVGAPC Output signals


Type

Description

TRUV

BOOLEAN

Common trip signal for compensated under voltage

TROV

BOOLEAN

Common trip signal for compensated over voltage

TRUVL1

BOOLEAN

Trip signal for compensated under voltage of


phase 1

TRUVL2

BOOLEAN

Trip signal for compensated under voltage of


phase 2

TRUVL3

BOOLEAN

Trip signal for compensated under voltage of


phase 3

TROVL1

BOOLEAN

Trip signal for compensated over voltage of


phase 1

Table continues on next page

756
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Name

13.8.3.5
Table 454:

Type

Description

TROVL2

BOOLEAN

Trip signal for compensated over voltage of


phase 2

TROVL3

BOOLEAN

Trip signal for compensated over voltage of


phase 3

STUV

BOOLEAN

Common start signal for compensated under


voltage

STOV

BOOLEAN

Common start signal for compensated over voltage

STUVL1

BOOLEAN

Start signal for compensated under voltage of


phase 1

STUVL2

BOOLEAN

Start signal for compensated under voltage of


phase 2

STUVL3

BOOLEAN

Start signal for compensated under voltage of


phase 3

STOVL1

BOOLEAN

Start signal for compensated over voltage of


phase 1

STOVL2

BOOLEAN

Start signal for compensated over voltage of


phase 2

STOVL3

BOOLEAN

Start signal for compensated over voltage of


phase 3

Setting parameters
COUVGAPC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage in kV

OperationUV

Off
On

On

Operation compensated under voltage


Off/On

U<

1 - 100

%UB

70

Compensated under voltage level in %


of UBase

tUV

0.000 - 60.000

0.001

1.000

Time delay to trip under voltage

OperationOV

Off
On

On

Operation compensated over voltage Off/


On

U>

1 - 200

%UB

120

Compensated over voltage level in % of


UBase

tOV

0.000 - 60.000

0.001

5.000

Time delay to trip over voltage

Table 455:

COUVGAPC Group settings (advanced)

Name
HystAbs

Values (Range)
0.0 - 100.0

Unit
%UB

Step
0.1

Default
0.5

Description
Hysteresis absolute for compensated
over/under voltage in % of UBase

757
Technical reference manual

Section 13
Scheme communication

Table 456:
Name

1MRK 505 222-UEN B

COUVGAPC Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

R1

0.01 - 3000.00

ohm

0.01

5.00

Positive sequence resistance per phase


for the line in ohm

X1

0.01 - 3000.00

ohm

0.01

40.00

Positive sequence reactance per phase


for the line in ohm

Xc

1.00 - 10000.00

ohm

0.01

1000.00

Half of equivalent capacitive reactance


per phase in ohm

EnShuntReactor

Off
On

On

Enable setting if shunt reactor connected


in line

Xsh

1.00 - 10000.00

ohm

0.01

1500.00

Per phase reactance of local Shunt


Reactor in ohm

13.8.3.6

Technical data
Table 457:

COUVGAPC technical data

Function

13.8.4

Range or value

Accuracy

Operate value,
undervoltage

(1-100)% of UBase

0,5% of Ur

Reset ratio,
undervoltage

<105%

Critical impulse time,


undervoltage

5 ms typically at 1.2 to 0.8xUset

Impulse margin time,


undervoltage

15 ms typically

Operate value,
overvoltage

(1-200)% of UBase

0.5% of Ur at U<Ur
0.5% of U at U>Ur

Reset ratio,
overvoltage

>95%

Critical impulse time,


overvoltage

2 ms typically at 0.8 to 1.2xUset

Impulse margin time,


overvoltage

10 ms typically

Timers

(0.000-60.000) s

0.5% 10 ms

Sudden change in current variation SCCVPTOC


Function description
Sudden change in current variation

IEC 61850
identification
SCCVPTOC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
51

758
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.4.1

Introduction
Sudden change in current variation (SCCVPTOC) function is a fast way of finding
any abnormality in line currents. When there is a fault in the system, the current
changes faster than the voltage. SCCVPTOC finds abnormal condition based on
phase-to-phase current variation. The main application is as a local criterion to
increase security when transfer trips are used.

13.8.4.2

Principle of operation
Sudden change in current variation (SCCVPTOC) function calculates the variation
in phase-to-phase current and gives the START output when this variation crosses
the sum of start level and float threshold for a time of tDelay. The variation is
calculated for all the three phase-to-phase currents.
The variation in the current is calculated using the following equation:

Di = i ( t ) - 2 i ( t - T ) + i ( t - 2T )
EQUATION2252 V1 EN

Where:

i(t)

Amplitude of the current at the present instant

i(t-T)

Amplitude of the current at the instant exactly one cycle time before

i(t-2T)

Amplitude of the current at the instant exactly two cycle time before

Criteria:

Di > i (1.8 DIT

+ I >)

EQUATION2253 V1 EN

(Equation 156)

I>: start level


It is the full-circle integral of the phase-to-phase current variation

DIT

1 2T -1
Di ( t - n )
T n =T

EQUATION2254 V1 EN

(Equation 157)

T: the count of the sampling value in one cycle


If the above criteria becomes true for a time of tDelay, then respective START
output is activated provided the BLOCK input is false, and the respective TRIP
outputs is activated for the time of tHold provided the BLKTR and BLOCK input
is false.

759
Technical reference manual

Section 13
Scheme communication
13.8.4.3

1MRK 505 222-UEN B

Function block
SCCVPTOC
I3P*
BLOCK
BLKTR

TRIP
START

IEC09000765-1-en.vsd
IEC09000765 V1 EN

Figure 418:

13.8.4.4

SCCVPTOC function block

Input and output signals


Table 458:

SCCVPTOC Input signals

Name

Type

Three phase to phase current samples group

BLOCK

BOOLEAN

Block of function

BLKTR

BOOLEAN

Block trip signals

SCCVPTOC Output signals

Name

Table 460:
Name

Description

GROUP
SIGNAL

Table 459:

13.8.4.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Common trip signal

START

BOOLEAN

Common start signal

Setting parameters
SCCVPTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

IBase

1 - 99999

3000

Base setting for current in A

I>

0 - 100

%IB

20

Fixed threshold setting in % of IBase

tHold

0.000 - 60.000

0.001

0.500

Hold time for operate signals

Table 461:
Name
tDelay

SCCVPTOC Group settings (advanced)


Values (Range)

Unit

0.000 - 0.005

Step
0.001

Default
0.002

Description
Time delay for start and trip signals

760
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.4.6

Technical data
Table 462:

SCCVPTOC technical data

Function

13.8.5

13.8.5.1

Range or value

Accuracy

Operate value,
overcurrent

(0 - 100)% of IBase

1,0% of Ir

Reset ratio,
overcurrent

>95%

Timers

(0.000-60.000) s

0.5% 10 ms

Carrier receive logic LCCRPTRC


Function description

IEC 61850
identification

Carrier receive logic

LCCRPTRC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
94

Introduction
In Direct transfer trip (DTT) scheme, the received CR signal gives the trip to the
circuit breaker after checking certain local criteria functions in order to increase the
security of the overall tripping functionality. Carrier receive logic (LCCRPTRC)
function gives final trip output of the DTT scheme.
Features:

13.8.5.2

Carrier redundancy to ensure security in DTT scheme


Blocking function output on CR Channel Error
Phase wise trip outputs

Principle of operation
The functionality of the Carrier receive logic (LCCRPTRC) is to release the TRIP
signal for DTT scheme based on the LOCTRL1, LOCTRL2, LOCTRL3, and
LOCTR signals coming from local criterion, and the Carrier receive signals CR1
and CR2. There are two modes of operation 1 out of 2 and 2 out of 2. In the case of
the 1 out of 2 mode if any one of the carrier signal is received then the trip signals
will be released, and in 2 out of 2 mode both the CRs should be high to release trip
signal. If any one of the channel error signals is high in 2 out of 2 mode, then logic
automatically switches to 1 out of 2 mode after a time delay of 200 ms. After
switching to 1/2 mode under channel error condition and if channel error gets
cleared the mode will switch back only after a time delay of 200 ms.
If the input channel error signal is high then the respective carrier receive signal
will be blocked.

761
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

The complete function can be blocked by setting the BLOCK input high.

13.8.5.3

Function block
LCCRPTRC
BLOCK
LOCTR
LOCTRL1
LOCTRL2
LOCTRL3
CHERR1
CHERR2
CR1
CR2

TRIP
TRL1
TRL2
TRL3

IEC09000766-1-en.vsd
IEC09000766 V1 EN

Figure 419:

13.8.5.4

LCCRPTRC function block

Input and output signals


Table 463:
Name

LCCRPTRC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

LOCTR

BOOLEAN

Local common trip signal coming from DTT

LOCTRL1

BOOLEAN

Local trip signal for phase 1 coming from DTT

LOCTRL2

BOOLEAN

Local trip signal for phase 2 coming from DTT

LOCTRL3

BOOLEAN

Local trip signal for phase 3 coming from DTT

CHERR1

BOOLEAN

Channel error indication flag for carrier receive 1

CHERR2

BOOLEAN

Channel error indication flag for carrier receive 2

CR1

BOOLEAN

Carrier receive 1

CR2

BOOLEAN

Carrier receive 2

Table 464:
Name

LCCRPTRC Output signals


Type

Description

TRIP

BOOLEAN

Common trip

TRL1

BOOLEAN

Trip phase 1

TRL2

BOOLEAN

Trip phase 2

TRL3

BOOLEAN

Trip phase 3

762
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.5.5
Table 465:

Setting parameters
LCCRPTRC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

ChMode

2 Out Of 2
1 Out Of 2

2 Out Of 2

Setting to select 1/2 or 2/2 mode

tOperate

0.000 - 60.000

0.001

0.100

Time delay to operate

13.8.5.6

13.8.6

Technical data
Table 466:

LCCRPTRC technical data

Function

Range or value
1 Out Of 2
2 Out Of 2

Timer

(0.000-60.000) s

0.5% 10 ms

Negative sequence overvoltage protection LCNSPTOV


Function description
Negative sequence overvoltage
protection

13.8.6.1

Accuracy

Operation mode

IEC 61850
identification
LCNSPTOV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
47

Introduction
Negative sequence components are present in all types of fault condition. Negative
sequence voltage and current get high values during unsymmetrical faults.

13.8.6.2

Principle of operation
Negative sequence over voltage protection (LCNSPTOV) is a definite time stage
comparator function. The negative sequence input voltage from the SMAI block is
connected as input to the function through a group connection U3P in PCM600.
This voltage is compared against the preset value and a start signal will be set high
if the input negative sequence voltage is greater than the preset value U2>. Trip
signal will be set high after a time delay setting of tU2. There is a BLOCK input
which will block the complete function. BLKTR will block the trip output. The
negative sequence voltage is also available as service value output U2.

763
Technical reference manual

Section 13
Scheme communication
13.8.6.3

1MRK 505 222-UEN B

Function block
LCNSPTOV
U3P*
BLOCK
BLKTR

TRIP
START

IEC09000767-1-en.vsd
IEC09000767 V1 EN

Figure 420:

13.8.6.4

LCNSPTOV Function block

Input and output signals


Table 467:

LCNSPTOV Input signals

Name

Type

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block overall function

BLKTR

BOOLEAN

Block trip output

LCNSPTOV Output signals

Name

Table 469:
Name

Description

GROUP
SIGNAL

Table 468:

13.8.6.5

Default

U3P

Type

Description

TRIP

BOOLEAN

Trip signal for negative sequence over voltage

START

BOOLEAN

Start signal for negative sequence over voltage

Setting parameters
LCNSPTOV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

UBase

0.05 - 2000.00

kV

0.05

400

Base setting for voltage in kV

U2>

1 - 200

%UB

10

Negative sequence over voltage start


value in %UBase

tU2

0.000 - 120.000

0.001

2.000

Time delay to operate

764
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.6.6

13.8.7

Technical data
Table 470:

LCNSPTOV technical data

Function

Range or value
(1-200)% of UBase

0.5% of Ur at U<Ur
0.5% of U at U>Ur

Reset ratio, negative


sequence
overvoltage

>95%

Operate time, start

20 ms typically at 0 to 2xUset

Reset time, start

25 ms typically at 2 to 0xUset

Critical impulse time,


negative sequence
overvoltage

10 ms typically at 0 to 2xUset

Impulse margin time,


negative sequence
overvoltage

15 ms typically

Timers

(0.000-120.000) s

0.5% 10 ms

Zero sequence overvoltage protection LCZSPTOV


Function description
Zero sequence overvoltage protection

13.8.7.1

Accuracy

Operate value,
negative sequence
overvoltage

IEC 61850
identification
LCZSPTOV

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
59N

Introduction
Zero sequence components are present in all abnormal conditions involving earth.
They can reach considerably high values during earth faults.

13.8.7.2

Principle of operation
Zero sequence over voltage protection (LCZSPTOV) is a definite time stage
comparator function. The zero sequence input voltage from the SMAI block is
connected as input to the function through a group connection U3P in PCM600.
This voltage is compared against the preset value and a start signal will be set high
if the input zero sequence voltage is greater than the preset value 3U0>. Trip signal
will be set high after a time delay setting of t3U0. BLOCK input will block the
complete function. BLKTR will block the trip output. The zero sequence voltage
will be available as service value output as 3U0.

765
Technical reference manual

Section 13
Scheme communication
13.8.7.3

1MRK 505 222-UEN B

Function block
LCZSPTOV
U3P*
BLOCK
BLKTR

TRIP
START

IEC09000768-1-en.vsd
IEC09000768 V1 EN

Figure 421:

13.8.7.4

LCZSPTOV function block

Input and output signals


Table 471:

LCZSPTOV Input signals

Name

Type

Three phase group signal for voltage inputs

BLOCK

BOOLEAN

Block overall function

BLKTR

BOOLEAN

Block TRIP output

LCZSPTOV Output signals

Name

Table 473:
Name

Description

GROUP
SIGNAL

Table 472:

13.8.7.5

Default

U3P

Type

Description

TRIP

BOOLEAN

TRIP signal for zero sequence over voltage

START

BOOLEAN

Start signal for zero sequence over voltage

Setting parameters
LCZSPTOV Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

UBase

0.05 - 2000.00

kV

0.05

400

Base setting for voltage in kV

3U0>

1 - 200

%UB

10

Zero sequence voltage start value in %


of UBase

t3U0

0.000 - 120.000

0.001

2.000

Time delay to operate

766
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.7.6

13.8.8

Technical data
Table 474:

LCZSPTOV technical data

Function

Range or value
(1-200)% of UBase

0.5% of Ur at U<Ur
0.5% of U at U>Ur

Reset ratio, zero


sequence
overvoltage

>95%

Operate time, start

25 ms typically at 0 to 1.5xUset

Reset time, start

25 ms typically at 1.5 to 0xUset

Critical impulse time,


zero sequence
overvoltage

10 ms typically at 0 to 1.5xUset

Timers

(0.000-120.000) s

0.5% 10 ms

Negative sequence overcurrent protection LCNSPTOC


Function description
Negative sequence overcurrent
protection

13.8.8.1

Accuracy

Operate value, zero


sequence
overvoltage

IEC 61850
identification
LCNSPTOC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
46

Introduction
Negative sequence components are present in all types of fault condition. They can
reach considerably high values during abnormal operation.

13.8.8.2

Principle of operation
Negative sequence overcurrent protection (LCNSPTOC) is a definite time stage
comparator function. The negative sequence input current from the SMAI block is
connected as input to the function through a group connection I3P in PCM600.
This current is compared against the preset value and a start signal will be set high
if the input negative sequence current is greater than the preset value I2>. Trip
signal will be set high after a time delay setting of tI2. BLOCK input will block the
complete function. BLKTR will block the trip output. The negative sequence
current is available as service value output I2.

767
Technical reference manual

Section 13
Scheme communication
13.8.8.3

1MRK 505 222-UEN B

Function block
LCNSPTOC
I3P*
BLOCK
BLKTR

TRIP
START

IEC09000769-1-en.vsd
IEC09000769 V1 EN

Figure 422:

13.8.8.4

LCNSPTOC Function block

Input and output signals


Table 475:

LCNSPTOC Input signals

Name

Type

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block overall function

BLKTR

BOOLEAN

Block trip signal

LCNSPTOC Output signals

Name

Table 477:
Name

Description

GROUP
SIGNAL

Table 476:

13.8.8.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip signal negative sequence over current


protection

START

BOOLEAN

Start signal for negative sequence over current


protection

Setting parameters
LCNSPTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

IBase

1 - 99999

3000

Base setting for current in A

I2>

1 - 2500

%IB

100

Negative sequence over current start


value in % of IBase

tI2

0.000 - 60.000

0.001

0.000

Time delay to operate

768
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.8.6

13.8.9

Technical data
Table 478:

LCNSPTOC technical data

Function

Range or value
(1 - 2500)% of IBase

1.0% of Ir at I < Ir
1.0% of I at I > Ir

Reset ratio, negative


sequence
overcurrent

>95%

Operate time, start

20 ms typically at 0 to 2xIset
15 ms typically at 0 to 10xIset

Reset time, start

25 ms typically at 2 to 0xIset

Critical impulse time,


negative sequence
overcurrent

10 ms typically at 0 to 2xIset
2 ms typically at 0 to 10xIset

Impulse margin time,


negative sequence
overcurrent

10 ms typically

Timer

(0.000-60.000) s

0.5% 10 ms

Transient overreach,
start function

<5% at = 100 ms

Zero sequence overcurrent protection LCZSPTOC


Function description
Zero sequence overcurrent protection

13.8.9.1

Accuracy

Operate value,
negative sequence
overcurrent

IEC 61850
identification
LCZSPTOC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
51N

Introduction
Zero sequence components are present in all abnormal conditions involving earth.
They have a considerably high value during earth faults.

13.8.9.2

Principle of operation
Zero sequence overcurrent protection (LCZSPTOC) is a definite time stage
comparator function. The zero sequence input current from the SMAI block is
connected as input to the function through a group connection I3P in PCM600.
This current is compared against the preset value and a start signal will be set high
if the input zero sequence current is greater than the preset value 3I0>. Trip signal
will be set high after a time delay setting of t3I0. BLOCK input will block the
complete function. BLKTR will block the trip output. The zero sequence current is
available as service value output 3I0.

769
Technical reference manual

Section 13
Scheme communication
13.8.9.3

1MRK 505 222-UEN B

Function block
LCZSPTOC
I3P*
BLOCK
BLKTR

TRIP
START

IEC09000770-1-en.vsd
IEC09000770 V1 EN

Figure 423:

13.8.9.4

LCZSPTOC Function block

Input and output signals


Table 479:

LCZSPTOC Input signals

Name

Type

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block overall function

BLKTR

BOOLEAN

Block trip output

LCZSPTOC Output signals

Name

Table 481:
Name

Description

GROUP
SIGNAL

Table 480:

13.8.9.5

Default

I3P

Type

Description

TRIP

BOOLEAN

Trip signal for zero sequence over current


protection

START

BOOLEAN

Start signal for zero sequence over current


protection

Setting parameters
LCZSPTOC Group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

IBase

1 - 99999

3000

Base setting for current in A

3I0>

1 - 2500

%IB

100

Zero sequence over current start value


in % of IBase

t3I0

0.000 - 60.000

0.001

0.000

Time delay to operate

770
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.9.6

13.8.10

Technical data
Table 482:

LCZSPTOC technical data

Function

Range or value
(1-2500)% of IBase

1.0% of Ir at I<Ir
1.0% of I at I>Ir

Reset ratio, zero


sequence
overcurrent

>95%

Operate time, start

20 ms typically at 0 to 2xIset
15 ms typically at 0 to 10xIset

Reset time, start

30 ms typically at 2 to 0xIset

Critical impulse time,


zero sequence
overcurrent

10 ms typically at 0 to 2xIset
2 ms typically at 0 to 10xIset

Impulse margin time,


zero sequence
overcurrent

15 ms typically

Timer

(0.000-60.000) s

0.5% 10 ms

Three phase overcurrent LCP3PTOC


Function description
Three phase overcurrent

13.8.10.1

Accuracy

Operate value, zero


sequence
overcurrent

IEC 61850
identification

IEC 60617
identification

LCP3PTOC

ANSI/IEEE C37.2
device number
51

Introduction
Three phase overcurrent (LCP3PTOC) is designed for overcurrent conditions.
Features:

13.8.10.2

Phase wise start and trip signals


Overcurrent protection
Phase wise RMS current is available as service values
Single definite time stage trip function.

Principle of operation
Three phase overcurrent (LCP3PTOC) is used for detecting over current
conditions. LCP3PTOC starts when the current exceeds the set limit IOC>. It
operates with definite time (DT) characteristics, that is, the function operates after a
predefined time tOC and resets when the fault current disappears. The function

771
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

contains a blocking functionality. It is possible to block the function output, timer


or the function itself, if desired.

13.8.10.3

Function block
LCP3PTOC
I3P*
BLOCK
BLKTR

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
IEC09000771-1-en.vsd

IEC09000771 V1 EN

Figure 424:

13.8.10.4

LCP3PTOC Function block

Input and output signals


Table 483:
Name

LCP3PTOC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block all binary outputs by resetting timers

BLKTR

BOOLEAN

Block trip of the function

Table 484:
Name

LCP3PTOC Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

Common start signal

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

772
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

13.8.10.5
Table 485:

Setting parameters
LCP3PTOC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation On / Off

IBase

0 - 99999

3000

Base setting for current in A

IOC>

5 - 2500

%IB

1000

Start value for 3 phase over current in %


IBase

tOC

0.000 - 60.000

0.001

0.020

Time delay to operate

13.8.10.6

13.8.11

Technical data
Table 486:

LCP3PTOC technical data

Function

Range or value
(5-2500)% of IBase

1.0% of Ir at I < Ir
1.0% of I at I > Ir

Reset ratio,
overcurrent

>95%

Operate time, start

20 ms typically at 0 to 2xIset
15 ms typically at 0 to 10xIset

Reset time, start

30 ms typically at 2 to 0xIset

Critical impulse time,


overcurrent

5 ms typically at 0 to 2xIset
2 ms typically at 0 to 10xIset

Impulse margin time,


overcurrent

10 ms typically

Timers

(0.000-60.000) s

0.5% 10 ms

Three phase undercurrent LCP3PTUC


Function description
Three phase undercurrent

13.8.11.1

Accuracy

Operate value,
overcurrent

IEC 61850
identification
LCP3PTUC

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
37

Introduction
Three phase undercurrent function (LCP3PTUC) is designed for detecting loss of
load conditions.
Features:

773
Technical reference manual

Section 13
Scheme communication

13.8.11.2

1MRK 505 222-UEN B

Phase wise start and trip signals


Phase wise RMS current is available as service values
Single definite time stage trip function

Principle of operation
Three phase undercurrent (LCP3PTUC) is used for detecting sudden load loss
which is considered as fault condition. LCP3PTUC starts when the current is less
than the set limit IUC<. It operates with definite time (DT) characteristics, that is,
the function operates after a predefined time tUC and resets when the load current
restores. The function contains a blocking functionality. It is possible to block the
function output, timer or the function itself, if desired.

13.8.11.3

Function block
LCP3PTUC
I3P*
BLOCK
BLKTR

TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
IEC09000772-1-en.vsd

IEC09000772 V1 EN

Figure 425:

13.8.11.4

LCP3PTUC Function block

Input and output signals


Table 487:
Name

LCP3PTUC Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Three phase group signal for current inputs

BLOCK

BOOLEAN

Block all binary outputs by resetting timers

BLKTR

BOOLEAN

Block trip of the function

Table 488:
Name

LCP3PTUC Output signals


Type

Description

TRIP

BOOLEAN

Common trip signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

START

BOOLEAN

Common start signal

Table continues on next page

774
Technical reference manual

Section 13
Scheme communication

1MRK 505 222-UEN B

Name

13.8.11.5
Table 489:

Type

Description

STL1

BOOLEAN

Start signal from phase L1

STL2

BOOLEAN

Start signal from phase L2

STL3

BOOLEAN

Start signal from phase L3

Setting parameters
LCP3PTUC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation On / Off

IBase

0 - 99999

3000

Current Base

IUC<

1.00 - 100.00

%IB

0.01

50.00

Start value for 3 phase under current in


% IBase

tUC

0.000 - 60.000

0.001

0.000

Time delay to operate

13.8.11.6

Technical data
Table 490:

LCP3TUC technical data

Function

Range or value

Accuracy

Operate value,
undercurrent

(1.00-100.00)% of IBase

1.0% of Ir

Reset ratio,
undercurrent

>105%

Operate time, start

20 ms typically at 2 to 0xIset

Reset time, start

30 ms typically at 0 to 2xIset

Critical impulse time,


undercurrent

10 ms typically at 2 to 0xIset

Impulse margin time,


undercurrent

10 ms typically

Timers

(0.000-60.000) s

0.5% 10 ms

775
Technical reference manual

776

Section 14
Logic

1MRK 505 222-UEN B

Section 14

Logic

About this chapter


This chapter describes primarily tripping and trip logic functions. The way the
functions work, their setting parameters, function blocks, input and output signals
and technical data are included for each function.

14.1

Tripping logic SMPPTRC


Function description
Tripping logic

IEC 61850
identification

IEC 60617
identification

SMPPTRC

ANSI/IEEE C37.2
device number
94

I->O
SYMBOL-K V1 EN

14.1.1

Introduction
A function block for protection tripping is provided for each circuit breaker
involved in the tripping of the fault. It provides pulse prolongation to ensure a trip
pulse of sufficient length, as well as all functionality necessary for correct cooperation with autoreclosing functions.
The trip function block includes functionality for evolving faults and breaker lockout.

14.1.2

Principle of operation
The duration of a trip output signal from tripping logic SMPPTRC is settable
(tTripMin). The pulse length should be long enough to secure the breaker opening.
For three-phase tripping, SMPPTRC has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.

777
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

BLOCK
tTripMin

TRIN

AND

TRIP

OR

Operation Mode = On
Program = 3Ph

en05000789.vsd
IEC05000789 V1 EN

Figure 426:

Simplified logic diagram for three phase trip

SMPPTRC function for single-phase and two-phase tripping has additional phase
segregated inputs for this, as well as inputs for faulted phase selection. The latter
inputs enable single- phase and two-phase tripping for those functions which do not
have their own phase selection capability, and therefore which have just a single
trip output and not phase segregated trip outputs for routing through the phase
segregated trip inputs of the expanded SMPPTRC function. Examples of such
protection functions are the residual overcurrent protections. The expanded
SMPPTRC function has two inputs for these functions, one for impedance tripping
(for example, carrier-aided tripping commands from the scheme communication
logic), and one for earth fault tripping (for example, tripping output from a residual
overcurrent protection).
Additional logic, including a timer tWaitForPHS, secures a three-phase trip
command for these protection functions in the absence of the required phase
selection signals.
The expanded SMPPTRC function has three trip outputs TRL1, TRL2, TRL3
(besides the trip output TRIP), one per phase, for connection to one or more of the
IEDs binary outputs, as well as to other functions within the IED requiring these
signals. There are also separate output signals indicating single-phase, two-phase or
three-phase trip. These signals are important for cooperation with the autorecloser
SMBRREC function.
The expanded SMPPTRC function is equipped with logic which secures correct
operation for evolving faults as well as for reclosing on to persistent faults. A
special input is also provided which disables single- phase and two-phase tripping,
forcing all tripping to be three-phase.
In multi-breaker arrangements, one SMPPTRC function block is used for each
breaker. This can be the case if single pole tripping and autoreclosing is used.
The breaker close lockout function can be activated from an external trip signal
from another protection function via input (SETLKOUT) or internally at a threephase trip, if desired.
It is possible to lockout seal in the tripping output signals or use blocking of
closing only the choice is by setting TripLockout.

778
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

14.1.2.1

Logic diagram
TRINL1
TRINL2

OR

TRINL3

OR

1PTRZ
1PTREF

OR

TRIN

AND

RSTTRIP - cont.

Program = 3ph

en05000517.vsd
IEC05000517 V1 EN

Figure 427:

Three-phase front logic simplified logic diagram

TRINP_3P
TRINP_A
PS_A

OR

AND

ATRIP

TRINP_B
PS_B

OR

AND

BTRIP

TRINP_C
PS_C

OR

AND

CTRIP

OR

OR

OR
-loop
-loop

OR
AND
1PTRGF

AND
AND

tWaitForPHS

OR

1PTRZ

AND

t
IEC10000056-1-en.vsd

IEC10000056 V1 EN

Figure 428:

Phase segregated front logic

779
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

L1TRIP

150 ms

OR

RTRIP

OR

2000 ms
t

OR

L2TRIP

150 ms

AND

OR

STRIP

OR

2000 ms
t

OR

L3TRIP

150 ms

AND

OR

TTRIP

OR

2000 ms
t

OR

AND

OR

OR

P3PTR

AND

OR
-loop
en05000519.vsd
IEC05000519-WMF V1 EN

Figure 429:

Additional logic for the 1ph/3ph operating mode

780
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

L1TRIP - cont.

150 ms

OR

RTRIP

OR

2000 ms
t

AND

L2TRIP

150 ms

OR

STRIP

OR

2000 ms
t

AND
AND

L3TRIP

150 ms

OR

TTRIP

OR

2000 ms
t

AND

OR
AND

OR

TRIP

OR
-loop
en05000520.vsd
IEC05000520-WMF V1 EN

Figure 430:

Additional logic for the 1ph/2ph/3ph operating mode

781
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

BLOCK
RTRIP

TRL1

AND

OR
STRIP

TRL2

AND

OR
TTRIP

TRL3

AND

OR
RSTTRIP

TRIP

OR

AND

OR

TR3P

AND
-loop
10 ms

AND

AND

AND

5 ms

AND
AND

TR1P

TR2P

OR

-loop
en05000521.vsd
IEC05000521-WMF V1 EN

Figure 431:

14.1.3

Final tripping circuits

Function block
SMPPTRC
BLOCK
TRIP
BLKLKOUT
TRL1
TRIN
TRL2
TRINL1
TRL3
TRINL2
TR1P
TRINL3
TR2P
PSL1
TR3P
PSL2
CLLKOUT
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
IEC05000707-2-en.vsd
IEC05000707 V2 EN

Figure 432:

14.1.4

SMPPTRC function block

Input and output signals


Table 491:
Name

SMPPTRC Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

BLKLKOUT

BOOLEAN

Blocks circuit breaker lockout output (CLLKOUT)

TRIN

BOOLEAN

Trip all phases

Table continues on next page

782
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Name

Type

Trip phase 1

TRINL2

BOOLEAN

Trip phase 2

TRINL3

BOOLEAN

Trip phase 3

PSL1

BOOLEAN

Functional input for phase selection in phase L1

PSL2

BOOLEAN

Functional input for phase selection in phase L2

PSL3

BOOLEAN

Functional input for phase selection in phase L3

1PTRZ

BOOLEAN

Zone Trip with a separate phase selection

1PTREF

BOOLEAN

Single phase DEF Trip for separate phase


selection

P3PTR

BOOLEAN

Prepare all tripping to be three-phase

SETLKOUT

BOOLEAN

Input for setting the circuit breaker lockout function

RSTLKOUT

BOOLEAN

Input for resetting the circuit breaker lockout


function

SMPPTRC Output signals

Name

Table 493:

Description

BOOLEAN

Table 492:

14.1.5

Default

TRINL1

Type

Description

TRIP

BOOLEAN

General trip output signal

TRL1

BOOLEAN

Trip signal from phase L1

TRL2

BOOLEAN

Trip signal from phase L2

TRL3

BOOLEAN

Trip signal from phase L3

TR1P

BOOLEAN

Tripping single-pole

TR2P

BOOLEAN

Tripping two-pole

TR3P

BOOLEAN

Tripping three-pole

CLLKOUT

BOOLEAN

Circuit breaker lockout output (set until reset)

Setting parameters
SMPPTRC Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

Program

3 phase
1ph/3ph
1ph/2ph/3ph

1ph/3ph

Three ph; single or three ph; single, two


or three ph trip

tTripMin

0.000 - 60.000

0.001

0.150

Minimum duration of trip output signal

tWaitForPHS

0.020 - 0.500

0.001

0.050

Secures 3-pole trip when phase


selection failed

783
Technical reference manual

Section 14
Logic

Table 494:
Name

1MRK 505 222-UEN B

SMPPTRC Group settings (advanced)


Values (Range)

Unit

Step

Default

Description

TripLockout

Off
On

Off

On: activate output (CLLKOUT) and trip


latch, Off: only outp

AutoLock

Off
On

Off

On: lockout from input (SETLKOUT) and


trip, Off: only inp

14.1.6

Technical data
Table 495:

SMPPTRC technical data

Function

14.2

Range or value
3-ph, 1/3-ph, 1/2/3-ph

Minimum trip pulse length

(0.000-60.000) s

0.5% 10 ms

Timers

(0.000-60.000) s

0.5% 10 ms

Trip matrix logic TMAGGIO


Function description
Trip matrix logic

14.2.1

Accuracy

Trip action

IEC 61850
identification
TMAGGIO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Trip matrix logic TMAGGIO function is used to route trip signals and other logical
output signals to different output contacts on the IED.
TMAGGIO output signals and the physical outputs allows the user to adapt the
signals to the physical tripping outputs according to the specific application needs.

14.2.2

Principle of operation
Trip matrix logic (TMAGGIO) block is provided with 32 input signals and 3
output signals. The function block incorporates internal logic OR gates in order to
provide the necessary grouping of connected input signals (for example, for
tripping and alarming purposes) to the three output signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:

784
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

1.
2.
3.

when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical
value 1 (TRUE) the first output signal (OUTPUT1) will get logical value 1
(TRUE).
when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 (TRUE) the second output signal (OUTPUT2) will get logical value 1
(TRUE).
when any one of all 32 input signals (INPUT1 to INPUT32) has logical value
1 (TRUE) the third output signal (OUTPUT3) will get logical value 1 (TRUE).

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime,


OnDelay and OffDelay the behavior of each output can be customized. The
OnDelay is always active and will delay the input to output transition by the set
time. The ModeOutput for respective output decides wether the output shall be
steady with an drop-off delay as set by OffDelay or if it shall give a pulse with
duration set by PulseTime. Note that for pulsed operation since the inputs are
connected in an OR-function a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. And for steady operation
the of delay will start when all related inputs have reset. Detailed logical diagram is
shown in figure 433
PulseTime

&

ModeOutput1

Input 1
Ondelay

Offdelay

&

Output 1

Output 2

Output 3

Input 16

PulseTime

&

ModeOutput2

Input 17
Ondelay

Offdelay

&

Input 32

PulseTime

&

ModeOutput3
Ondelay

Offdelay

&

IEC09000612_1_en.vsd
IEC09000612 V1 EN

Figure 433:

Trip matrix internal logic

Output signals from TMAGGIO are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay shall be set to approximately 0.150 seconds in order
to obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip
coils.
785
Technical reference manual

Section 14
Logic
14.2.3

1MRK 505 222-UEN B

Function block
TMAGGIO
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

OUTPUT1
OUTPUT2
OUTPUT3

IEC09000830-1-en.vsd

IEC09000830 V1 EN

Figure 434:

14.2.4

TMAGGIO function block

Input and output signals


Table 496:
Name

TMAGGIO Input signals


Type

Default

Description

INPUT1

BOOLEAN

Binary input 1

INPUT2

BOOLEAN

Binary input 2

INPUT3

BOOLEAN

Binary input 3

INPUT4

BOOLEAN

Binary input 4

INPUT5

BOOLEAN

Binary input 5

INPUT6

BOOLEAN

Binary input 6

INPUT7

BOOLEAN

Binary input 7

INPUT8

BOOLEAN

Binary input 8

INPUT9

BOOLEAN

Binary input 9

INPUT10

BOOLEAN

Binary input 10

INPUT11

BOOLEAN

Binary input 11

INPUT12

BOOLEAN

Binary input 12

INPUT13

BOOLEAN

Binary input 13

INPUT14

BOOLEAN

Binary input 14

INPUT15

BOOLEAN

Binary input 15

INPUT16

BOOLEAN

Binary input 16

INPUT17

BOOLEAN

Binary input 17

INPUT18

BOOLEAN

Binary input 18

INPUT19

BOOLEAN

Binary input 19

INPUT20

BOOLEAN

Binary input 20

Table continues on next page


786
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Name

Type

Binary input 21

INPUT22

BOOLEAN

Binary input 22

INPUT23

BOOLEAN

Binary input 23

INPUT24

BOOLEAN

Binary input 24

INPUT25

BOOLEAN

Binary input 25

INPUT26

BOOLEAN

Binary input 26

INPUT27

BOOLEAN

Binary input 27

INPUT28

BOOLEAN

Binary input 28

INPUT29

BOOLEAN

Binary input 29

INPUT30

BOOLEAN

Binary input 30

INPUT31

BOOLEAN

Binary input 31

INPUT32

BOOLEAN

Binary input 32

TMAGGIO Output signals

Name

Table 498:

Description

BOOLEAN

Table 497:

14.2.5

Default

INPUT21

Type

Description

OUTPUT1

BOOLEAN

OR function betweeen inputs 1 to 16

OUTPUT2

BOOLEAN

OR function between inputs 17 to 32

OUTPUT3

BOOLEAN

OR function between inputs 1 to 32

Setting parameters
TMAGGIO Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

On

Operation Off / On

PulseTime

0.050 - 60.000

0.001

0.150

Output pulse time

OnDelay

0.000 - 60.000

0.001

0.000

Output on delay time

OffDelay

0.000 - 60.000

0.001

0.000

Output off delay time

ModeOutput1

Steady
Pulsed

Steady

Mode for output ,1 steady or pulsed

ModeOutput2

Steady
Pulsed

Steady

Mode for output 2, steady or pulsed

ModeOutput3

Steady
Pulsed

Steady

Mode for output 3, steady or pulsed

787
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

14.3

Configurable logic blocks

14.3.1

Introduction
A number of logic blocks and timers are available for the user to adapt the
configuration to the specific application needs.

14.3.2

OR function block.

INVERTER function blocks that inverts the input signal.

PULSETIMER function block can be used, for example, for pulse extensions
or limiting of operation of outputs.

GATE function block is used for whether or not a signal should be able to
pass from the input to the output.

XOR function block.

LOOPDELAY function block used to delay the output signal one execution
cycle.

TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.

AND function block.

SRMEMORY function block is a flip-flop that can set or reset an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block's output should reset or return to the state
it was, after a power interruption. Set input has priority.

RSMEMORY function block is a flip-flop that can reset or set an output from
two inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block's output should reset or return to the state
it was, after a power interruption. Reset input has priority.

Inverter function block INV


INV
INPUT

OUT
IEC04000404_2_en.vsd

IEC04000404 V2 EN

Figure 435:

INV function block

788
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Table 499:

INV Input signals

Name

Type

INPUT

BOOLEAN

Table 500:

Description
Input

INV Output signals

Name

Type

OUT

14.3.3

Default

Description

BOOLEAN

Output

OR function block OR
The OR function is used to form general combinatory expressions with boolean
variables. The OR function block has six inputs and two outputs. One of the
outputs is inverted.
OR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6

OUT
NOUT

IEC04000405_2_en.vsd
IEC04000405 V2 EN

Figure 436:

OR function block

Table 501:

OR Input signals

Name

Type

Default

Description

INPUT1

BOOLEAN

Input 1 to OR gate

INPUT2

BOOLEAN

Input 2 to OR gate

INPUT3

BOOLEAN

Input 3 to OR gate

INPUT4

BOOLEAN

Input 4 to OR gate

INPUT5

BOOLEAN

Input 5 to OR gate

INPUT6

BOOLEAN

Input 6 to OR gate

Table 502:
Name

OR Output signals
Type

Description

OUT

BOOLEAN

Output from OR gate

NOUT

BOOLEAN

Inverted output from OR gate

789
Technical reference manual

Section 14
Logic
14.3.4

1MRK 505 222-UEN B

AND function block AND


The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs. One of the
outputs are inverted.
AND
INPUT1
INPUT2
INPUT3
INPUT4N

OUT
NOUT

IEC04000406_2_en.vsd
IEC04000406 V2 EN

Figure 437:

AND function block

Table 503:

AND Input signals

Name

Type

Description

BOOLEAN

Input 1

INPUT2

BOOLEAN

Input 2

INPUT3

BOOLEAN

Input 3

INPUT4N

BOOLEAN

Input 4 inverted

Table 504:

AND Output signals

Name

14.3.5

Default

INPUT1

Type

Description

OUT

BOOLEAN

Output

NOUT

BOOLEAN

Output inverted

Timer function block TIMER


The function block TIMER has drop-out and pick-up delayed outputs related to the
input signal. The timer has a settable time delay (T).
TIMER
INPUT
T

ON
OFF
IEC04000378_2_en.vsd

IEC04000378 V2 EN

Figure 438:

TIMER function block

Table 505:

TIMER Input signals

Name
INPUT

Type
BOOLEAN

Default
0

Description
Input to timer

790
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Table 506:

TIMER Output signals

Name

Table 507:

Type

Description

ON

BOOLEAN

Output from timer , pick-up delayed

OFF

BOOLEAN

Output from timer, drop-out delayed

TIMER Non group settings (basic)

Name

Values (Range)

Unit

0.000 - 90000.000

14.3.6

Step

0.001

Default

Description

0.000

Time delay of function

Pulse timer function block PULSETIMER


The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting of operation of outputs. The pulse timer TP has a settable length.
PULSETIMER
INPUT
T

OUT

IEC04000407-2-en.vsd
IEC04000407 V2 EN

Figure 439:

PULSETIMER function block

Table 508:

PULSETIMER Input signals

Name

Type

INPUT

BOOLEAN

Table 509:

Description
Input to pulse timer

PULSETIMER Output signals

Name

Type

OUT

Table 510:

Default

Description

BOOLEAN

Output from pulse timer

PULSETIMER Non group settings (basic)

Name
T

14.3.7

Values (Range)
0.000 - 90000.000

Unit
s

Step
0.001

Default
0.010

Description
Time delay of function

Exclusive OR function block XOR


The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal is 1 if the input signals are different and 0 if they are equal.

791
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

XOR
INPUT1
INPUT2

OUT
NOUT
IEC04000409-2-en.vsd

IEC04000409 V2 EN

Figure 440:

XOR function block

Table 511:

XOR Input signals

Name

Type

Description

BOOLEAN

Input 1 to XOR gate

INPUT2

BOOLEAN

Input 2 to XOR gate

Table 512:

XOR Output signals

Name

14.3.8

Default

INPUT1

Type

Description

OUT

BOOLEAN

Output from XOR gate

NOUT

BOOLEAN

Inverted output from XOR gate

Loop delay function block LOOPDELAY


The Logic loop delay function block (LOOPDELAY) function is used to delay the
output signal one execution cycle.
LOOPDELAY
INPUT

OUT
IEC09000296-1-en.vsd

IEC09000296 V1 EN

Figure 441:

LOOPDELAY function block

Table 513:

LOOPDELAY Input signals

Name
INPUT

Table 514:
Name
OUT

14.3.9

Type
BOOLEAN

Default
0

Description
Input signal

LOOPDELAY Output signals


Type
BOOLEAN

Description
Output signal, signal is delayed one execution
cycle

Set-reset with memory function block SRMEMORY


The Set-reset with memory function block (SRMEMORY) is a flip-flop with
memory that can set or reset an output from two inputs respectively. Each
SRMEMORY function block has two outputs, where one is inverted. The memory

792
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset.
Table 515:
SET

Truth table for SRMEMORY function block


RESET

OUT

NOUT

Last
value

Inverted
last value

SRMEMORY
SET
OUT
RESET
NOUT
IEC04000408_2_en.vsd
IEC04000408 V2 EN

Figure 442:

SRMEMORY function block

Table 516:

SRMEMORY Input signals

Name

Type

Description

BOOLEAN

Input signal to set

RESET

BOOLEAN

Input signal to reset

Table 517:

SRMEMORY Output signals

Name

Table 518:

Default

SET

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

SRMEMORY Group settings (basic)

Name
Memory

14.3.10

Values (Range)
Off
On

Unit
-

Step
-

Default
On

Description
Operating mode of the memory function

Reset-set with memory function block RSMEMORY


The Reset-set with memory function block (RSMEMORY) is a flip-flop with
memory that can reset or set an output from two inputs respectively. Each
RSMEMORY function block has two outputs, where one is inverted. The memory
setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset. For a Reset-Set flip-flop, RESET input has higher
priority over SET input.

793
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Table 519:

Truth table for RSMEMORY function block

RESET

SET

OUT

NOUT

Last
value

Inverted last
value

RSMEMORY
SET
RESET

OUT
NOUT
IEC09000294-1-en.vsd

IEC09000294 V1 EN

Figure 443:

RSMEMORY function block

Table 520:

RSMEMORY Input signals

Name

Type

Input signal to set

RESET

BOOLEAN

Input signal to reset

RSMEMORY Output signals

Name

Name
Memory

14.3.11

Description

BOOLEAN

Table 521:

Table 522:

Default

SET

Type

Description

OUT

BOOLEAN

Output signal

NOUT

BOOLEAN

Inverted output signal

RSMEMORY Group settings (basic)


Values (Range)

Unit

Off
On

Step
-

Default
On

Description
Operating mode of the memory function

Controllable gate function block GATE


The Controllable gate function block (GATE) is used for controlling if a signal
should be able to pass from the input to the output or not depending on a setting.
GATE
INPUT

OUT
IEC04000410-2-en.vsd

IEC04000410 V2 EN

Figure 444:

GATE function block

794
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Table 523:

GATE Input signals

Name

Type

INPUT

BOOLEAN

Table 524:

Description
Input to gate

GATE Output signals

Name

Type

OUT

Table 525:

Default

Description

BOOLEAN

Output from gate

GATE Group settings (basic)

Name

Values (Range)

Operation

Unit

Off
On

14.3.12

Step

Default
Off

Description
Operation Off/On

Settable timer function block TIMERSET


The Settable timer function block (TIMERSET) timer has outputs for delayed input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an
Operation setting On/, Off/ that controls the operation of the timer.
TIMERSET
INPUT

ON
OFF
IEC04000411-2-en.vsd

IEC04000411 V2 EN

Figure 445:

TIMERSET function block

Table 526:

TIMERSET Input signals

Name

Type

INPUT

BOOLEAN

Table 527:

Description
Input to timer

TIMERSET Output signals

Name

Table 528:

Default

Type

Description

ON

BOOLEAN

Output from timer, pick-up delayed

OFF

BOOLEAN

Output from timer, drop-out delayed

TIMERSET Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

0.000 - 90000.000

0.001

0.000

Delay for settable timer n

795
Technical reference manual

Section 14
Logic
14.3.13

1MRK 505 222-UEN B

Technical data
Table 529:

Configurable logic blocks

Logic block

14.4

Quantity with cycle time


fast
medium

Range or
value

normal

Accuracy

LogicAND

60

60

160

LogicOR

60

60

160

LogicXOR

10

10

20

LogicInverter

30

30

80

LogicSRMemory

10

10

20

LogicRSMemory

10

10

20

LogicGate

10

10

20

LogicTimer

10

10

20

(0.000
90000.000) s

0.5% 10 ms

LogicPulseTimer

10

10

20

(0.000
90000.000) s

0.5% 10 ms

LogicTimerSet

10

10

20

(0.000
90000.000) s

0.5% 10 ms

LogicLoopDelay

10

10

20

(0.000
90000.000) s

0.5% 10 ms

Trip Matrix Logic

Boolean 16 to Integer

Boolean 16 to
integer with Logic
Node

Integer to Boolean 16

Integer to Boolean
16 with Logic Node

Fixed signal function block FXDSIGN


Function description
Fixed signals

IEC 61850
identification
FXDSIGN

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed)


signals that can be used in the configuration of an IED, either for forcing the
unused inputs in other function blocks to a certain level/value, or for creating
certain logic.

14.4.1

Principle of operation
There are eight outputs from FXDSIGN function block:

796
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

14.4.2

OFF is a boolean signal, fixed to OFF (boolean 0) value


ON is a boolean signal, fixed to ON (boolean 1) value
INTZERO is an integer number, fixed to integer value 0
INTONE is an integer number, fixed to integer value 1
INTALONE is an integer value FFFF (hex)
REALZERO is a floating point real number, fixed to 0.0 value
STRNULL is a string, fixed to an empty string (null) value
ZEROSMPL is a channel index, fixed to 0 value
GRP_OFF is a group signal, fixed to 0 value

Function block
FXDSIGN
OFF
ON
INTZERO
INTONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF
IEC05000445-2-en.vsd
IEC05000445 V2 EN

Figure 446:

14.4.3

Input and output signals


Table 530:
Name

14.4.4

FXDSIGN function block

FXDSIGN Output signals


Type

Description

OFF

BOOLEAN

Boolean signal fixed off

ON

BOOLEAN

Boolean signal fixed on

INTZERO

INTEGER

Integer signal fixed zero

INTONE

INTEGER

Integer signal fixed one

INTALONE

INTEGER

Integer signal fixed all ones

REALZERO

REAL

Real signal fixed zero

STRNULL

STRING

String signal with no characters

ZEROSMPL

GROUP SIGNAL

Channel id for zero sample

GRP_OFF

GROUP SIGNAL

Group signal fixed off

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

797
Technical reference manual

Section 14
Logic

14.5

1MRK 505 222-UEN B

Boolean 16 to Integer conversion B16I


Function description

IEC 61850
identification

Boolean 16 to integer conversion

14.5.1

IEC 60617
identification

B16I

ANSI/IEEE C37.2
device number
-

Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.

14.5.2

Principle of operation
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer. The BLOCK input will freeze the output at
the last value.

14.5.3

Function block
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

OUT

IEC07000128-2-en.vsd
IEC07000128 V2 EN

Figure 447:

14.5.4

B16I function block

Input and output signals


Table 531:
Name

B16I Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

Table continues on next page

798
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Name

Type

Description

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

IN6

BOOLEAN

Input 6

IN7

BOOLEAN

Input 7

IN8

BOOLEAN

Input 8

IN9

BOOLEAN

Input 9

IN10

BOOLEAN

Input 10

IN11

BOOLEAN

Input 11

IN12

BOOLEAN

Input 12

IN13

BOOLEAN

Input 13

IN14

BOOLEAN

Input 14

IN15

BOOLEAN

Input 15

IN16

BOOLEAN

Input 16

Table 532:

B16I Output signals

Name
OUT

14.5.5

Default

IN4

Type
INTEGER

Description
Output value

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

14.6

Boolean 16 to Integer conversion with logic node


representation B16IFCVI
Function description
Boolean 16 to integer conversion with
logic node representation

14.6.1

IEC 61850
identification
B16IFCVI

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) is used to transform a set of 16 binary (logical) signals into an integer.
B16IFCVI can receive remote values via IEC 61850 depending on the operator
position input (PSTO).

799
Technical reference manual

Section 14
Logic
14.6.2

1MRK 505 222-UEN B

Principle of operation
Boolean 16 to integer conversion with logic node representation function
(B16IFCVI) is used to transform a set of 16 binary (logical) signals into an integer.
The BLOCK input will freeze the output at the last value.

14.6.3

Function block
B16IFCVI
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

OUT

IEC09000624-1-en.vsd
IEC09000624 V1 EN

Figure 448:

14.6.4

B16IFCVI function block

Input and output signals


Table 533:
Name

B16IFCVI Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1

IN2

BOOLEAN

Input 2

IN3

BOOLEAN

Input 3

IN4

BOOLEAN

Input 4

IN5

BOOLEAN

Input 5

IN6

BOOLEAN

Input 6

IN7

BOOLEAN

Input 7

IN8

BOOLEAN

Input 8

IN9

BOOLEAN

Input 9

IN10

BOOLEAN

Input 10

IN11

BOOLEAN

Input 11

IN12

BOOLEAN

Input 12

IN13

BOOLEAN

Input 13

Table continues on next page


800
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

Name

Type

Description

BOOLEAN

Input 14

IN15

BOOLEAN

Input 15

IN16

BOOLEAN

Input 16

Table 534:

B16IFCVI Output signals

Name
OUT

14.6.5

Default

IN14

Type

Description

INTEGER

Output value

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

14.7

Integer to Boolean 16 conversion IB16


Function description
Integer to boolean 16 conversion

14.7.1

IEC 61850
identification
IB16

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals.

14.7.2

Principle of operation
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals. IB16 function is designed for receiving the
integer input locally. The BLOCK input will freeze the logical outputs at the last
value.

801
Technical reference manual

Section 14
Logic
14.7.3

1MRK 505 222-UEN B

Function block
IB16
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC06000501-2-en.vsd
IEC06000501 V2 EN

Figure 449:

14.7.4

IB16 function block

Input and output signals


Table 535:
Name

IB16 Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INP

INTEGER

Integer Input

Table 536:
Name

IB16 Output signals


Type

Description

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

OUT6

BOOLEAN

Output 6

OUT7

BOOLEAN

Output 7

OUT8

BOOLEAN

Output 8

OUT9

BOOLEAN

Output 9

OUT10

BOOLEAN

Output 10

OUT11

BOOLEAN

Output 11

OUT12

BOOLEAN

Output 12

OUT13

BOOLEAN

Output 13

OUT14

BOOLEAN

Output 14

OUT15

BOOLEAN

Output 15

OUT16

BOOLEAN

Output 16

802
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

14.7.5

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

14.8

Integer to Boolean 16 conversion with logic node


representation IB16FCVB
Function description
Integer to boolean 16 conversion with
logic node representation

14.8.1

IEC 61850
identification
IB16FCVB

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
Integer to boolean conversion with logic node representation function (IB16FCVB)
is used to transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over IEC61850 depending on the
operator position input (PSTO).

14.8.2

Principle of operation
Integer to boolean conversion with logic node representation function (IB16FCVB)
is used to transform an integer into a set of 16 binary (logical) signals. IB16FCVB
function can receive an integer from a station computer for example, over IEC
61850. The BLOCK input will freeze the logical outputs at the last value.
The operator position input (PSTO) determines the operator place. The integer
number can be written to the block while in Remote. If PSTO is in Off
or Local, then no change is applied to the outputs.

803
Technical reference manual

Section 14
Logic
14.8.3

1MRK 505 222-UEN B

Function block
IB16FCVB
BLOCK
PSTO

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC09000399-1-en.vsd

IEC09000399 V1 EN

Figure 450:

14.8.4

IB16FCVB function block

Input and output signals


Table 537:
Name

IB16FCVB Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

PSTO

INTEGER

Operator place selection

Table 538:
Name

IB16FCVB Output signals


Type

Description

OUT1

BOOLEAN

Output 1

OUT2

BOOLEAN

Output 2

OUT3

BOOLEAN

Output 3

OUT4

BOOLEAN

Output 4

OUT5

BOOLEAN

Output 5

OUT6

BOOLEAN

Output 6

OUT7

BOOLEAN

Output 7

OUT8

BOOLEAN

Output 8

OUT9

BOOLEAN

Output 9

OUT10

BOOLEAN

Output 10

OUT11

BOOLEAN

Output 11

OUT12

BOOLEAN

Output 12

OUT13

BOOLEAN

Output 13

OUT14

BOOLEAN

Output 14

OUT15

BOOLEAN

Output 15

OUT16

BOOLEAN

Output 16

804
Technical reference manual

Section 14
Logic

1MRK 505 222-UEN B

14.8.5

Setting parameters
This function does not have any setting parameters.

805
Technical reference manual

806

Section 15
Monitoring

1MRK 505 222-UEN B

Section 15

Monitoring

About this chapter


This chapter describes the functions that handle measurements, events and
disturbances. The way the functions work, their setting parameters, function
blocks, input and output signals, and technical data are included for each function.

15.1

Measurements
Function description
Measurements

IEC 61850
identification

IEC 60617
identification

CVMMXN

ANSI/IEEE C37.2
device number
-

P, Q, S, I, U, f

SYMBOL-RR V1 EN

Phase current measurement

CMMXU

I
SYMBOL-SS V1 EN

Phase-phase voltage measurement

VMMXU

U
SYMBOL-UU V1 EN

Current sequence component


measurement

CMSQI

Voltage sequence measurement

VMSQI

I1, I2, I0
SYMBOL-VV V1 EN

U1, U2, U0

SYMBOL-TT V1 EN

Phase-neutral voltage measurement

VNMMXU

U
SYMBOL-UU V1 EN

807
Technical reference manual

Section 15
Monitoring
15.1.1

1MRK 505 222-UEN B

Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values
of active power, reactive power, currents, voltages, frequency, power factor etc. is
vital for efficient production, transmission and distribution of electrical energy. It
provides to the system operator fast and easy overview of the present status of the
power system. Additionally, it can be used during testing and commissioning of
protection and control IEDs in order to verify proper operation and connection of
instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the
proper operation of the IED analog measurement chain can be verified. Finally, it
can be used to verify proper direction orientation for distance or directional
overcurrent protection function.
The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in PCM600.
All measured values can be supervised with four settable limits that is, low-low
limit, low limit, high limit and high-high limit. A zero clamping reduction is also
supported, that is, the measured value below a settable limit is forced to zero which
reduces the impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure
value can also be based on periodic reporting.
The measurement function, CVMMXN, provides the following power system
quantities:

P, Q and S: three phase active, reactive and apparent power


PF: power factor
U: phase-to-phase voltage amplitude
I: phase current amplitude
F: power system frequency

Main menu/Measurement/Monitoring/Service values/CVMMXN


The measuring functions CMMXU, VNMMXU and VMMXU provide physical
quantities:

I: phase currents (amplitude and angle) (CMMXU)


U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)
(VMMXU, VNMMXU)

808
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30
and 100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual
hardware, (TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequential quantities:

I: sequence currents (positive, zero, negative sequence, amplitude and angle)


U: sequence voltages (positive, zero and negative sequence, amplitude and
angle).

The CVMMXN function calculates three-phase power quantities by using


fundamental frequency phasors (DFT values) of the measured current respectively
voltage signals. The measured power quantities are available either, as
instantaneously calculated quantities or, averaged values over a period of time (low
pass filtered) depending on the selected settings.

15.1.2

Principle of operation

15.1.2.1

Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the preprocessing blocks. The number of processed alternate measuring quantities
depends on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:

Locally by means of the local HMI


Remotely using the monitoring tool within PCM600 or over the station bus
Internally by connecting the analogue output signals to the Disturbance Report
function

Phase angle reference

All phase angles are presented in relation to a defined reference channel. The
General setting parameter PhaseAngleRef defines the reference, see section
"Analog inputs".

Zero point clamping

Measured value below zero point clamping limit is forced to zero. This allows the
noise in the input signal to be ignored. The zero point clamping limit is a general
setting (XZeroDb where X equals S, P, Q, PF, U, I, F, IL1-3, UL1-3, UL12-31, I1,
I2, 3I0, U1, U2 or 3U0). Observe that this measurement supervision zero point
clamping might be overridden by the zero point clamping used for the
measurement values within CVMMXU.
809
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Continuous monitoring of the measured quantity

Users can continuously monitor the measured quantity available in each function
block by means of four defined operating thresholds, see figure 451. The
monitoring has two different modes of operating:

Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 451.


Y
X_RANGE = 3

High-high limit

X_RANGE= 1

Hysteresis

High limit
X_RANGE=0

X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4

en05000657.vsd
IEC05000657 V1 EN

Figure 451:

Presentation of operating limits

Each analogue output has one corresponding supervision level output


(X_RANGE). The output signal is an integer in the interval 0-4 (0: Normal, 1:
High limit exceeded, 3: High-high limit exceeded, 2: below Low limit and 4: below
Low-low limit). The output may be connected to a measurement expander block
(XP (RANGE_XP)) to get measurement supervision as binary signals.
The logical value of the functional output signals changes according to figure 451.
The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.

Actual value of the measured quantity

The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting
of the value to the higher levels depends on the selected reporting mode. The
following basic reporting modes are available:

810
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Cyclic reporting (Cyclic)


Amplitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)

Cyclic reporting

The cyclic reporting of measured value is performed according to chosen setting


(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
Y
Value Reported
(1st)

Value Reported

Value Reported

Value Reported

Value Reported

Y3
Y2

Y4

Y1

Y5

(*)Set value for t: XDbRepInt

t (*)

Value 5

Value 4

t (*)

Value 3

t (*)

Value 2

Value 1

t (*)

en05000500.vsd

IEC05000500 V1 EN

Figure 452:

Periodic reporting

Amplitude dead-band supervision

If a measuring value is changed, compared to the last reported value, and the
change is larger than the Y pre-defined limits that are set by user (XZeroDb),
then the measuring channel reports the new value to a higher level, if this is
detected by a new measured value. This limits the information flow to a minimum
necessary. Figure 453 shows an example with the amplitude dead-band
supervision. The picture is simplified: the process is not continuous but the values
are evaluated with a time interval of one execution cycle from each other.

811
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Value Reported

Y
Value Reported
(1st)

Value Reported
Y3
Y2

Y1

Value Reported
DY
DY

DY
DY

DY
DY

t
99000529.vsd

IEC99000529 V1 EN

Figure 453:

Amplitude dead-band supervision reporting

After the new value is reported, the Y limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more
than defined by the Y set limits. Even if amplitude dead-band reporting is
selected, there will be a 30 s "back-ground" cyclic reporting as well.

Integral dead-band reporting

The measured value is reported if the time integral of all changes exceeds the preset limit (XZeroDb), figure 454, where an example of reporting with integral deadband supervision is shown. The picture is simplified: the process is not continuous
but the values are evaluated with a time interval of one execution cycle from each
other.
The last value reported, Y1 in figure 454 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is
exceeded. This occurs with the value Y2 that is reported and set as a new base for
the following measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals
with small variations that can last for relatively long periods. Even if integral deadband reporting is selected, there will be a 30 s "back-ground" cyclic reporting as well.

812
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

A1 >=
pre-set value

Y
A >=
pre-set value

A2 >=
pre-set value
Y3

Y2
Value Reported
(1st)

A1

A2
Y4

Value
Reported

Value
Reported

A3 + A4 + A5 + A6 + A7 >=
pre-set value
A4
A3

A7

Y5

Value
Reported

Y1

A6

A5

Value
Reported
t
99000530.vsd

IEC99000530 V1 EN

Figure 454:

Reporting with integral dead-band supervision

15.1.2.2

Measurements CVMMXN
Mode of operation

The measurement function must be connected to three-phase current and threephase voltage input in the configuration tool (group signals), but it is capable to
measure and calculate above mentioned quantities in nine different ways depending
on the available VT inputs connected to the IED. The end user can freely select by
a parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, threeparameter
phase power calculation
Mode
1

L1, L2, L3

S = U L1 I L1 + U L 2 I L 2 + U L 3 I L 3
EQUATION1385 V1 EN

Formula used for voltage and


current magnitude calculation

U = ( U L1 + U L 2 + U L 3 ) / 3
I = ( I L1 + I L 2 + I L 3 ) / 3
EQUATION1386 V1 EN

Arone

S = U L1 L 2 I L1 - U L 2 L 3 I L 3
*

EQUATION1387 V1 EN

(Equation 158)

U = ( U L1 L 2 + U L 2 L 3 ) / 2
I = ( I L1 + I L 3 ) / 2
EQUATION1388 V1 EN

PosSeq

S = 3 U PosSeq I PosSeq
*

EQUATION1389 V1 EN

(Equation 160)

U =

(Equation 159)

3 U PosSeq

I = I PosSeq
EQUATION1390 V1 EN

(Equation 161)

Comment

Used when
three phaseto-earth
voltages are
available
Used when
three two
phase-tophase
voltages are
available
Used when
only
symmetrical
three phase
power shall
be measured

Table continues on next page

813
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Set value for Formula used for complex, threeparameter


phase power calculation
Mode
4

L1L2

S = U L1 L 2 ( I L*1 - I L* 2 )
(Equation 162)

EQUATION1391 V1 EN

Formula used for voltage and


current magnitude calculation

U = U L1 L 2
I = ( I L1 + I L 2 ) / 2
EQUATION1392 V1 EN

L2L3

S = U L 2 L3 ( I L 2 - I L3 )
*

(Equation 164)

EQUATION1393 V1 EN

U = U L2 L3
I = ( I L2 + I L3 ) / 2
EQUATION1394 V1 EN

L3L1

S = U L 3 L1 ( I L 3 - I L1 )
*

(Equation 166)

EQUATION1395 V1 EN

L1

S = 3 U L1 I L1
*

(Equation 168)

EQUATION1397 V1 EN

I = ( I L 3 + I L1 ) / 2

U =

L2

S = 3 U L2 I L2
*

(Equation 170)

EQUATION1399 V1 EN

U =

L3

S = 3 U L3 I L3
*

EQUATION1401 V1 EN

(Equation 172)

Used when
only UL3L1
phase-tophase
voltage is
available

Used when
only UL2
phase-toearth voltage
is available

3 U L2

(Equation 171)
Used when
only UL3
phase-toearth voltage
is available

3 U L3

I = I L3
EQUATION1402 V1 EN

Used when
only UL2L3
phase-tophase
voltage is
available

(Equation 169)

I = IL2

U =

Used when
only UL1L2
phase-tophase
voltage is
available

Used when
only UL1
phase-toearth voltage
is available

I = I L1

EQUATION1400 V1 EN

(Equation 167)

3 U L1

EQUATION1398 V1 EN

(Equation 165)

U = U L 3 L1

EQUATION1396 V1 EN

(Equation 163)

Comment

(Equation 173)

* means complex conjugated value

It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating
modes that is, from 3 to 9 it calculates the three-phase power under assumption that
the power system is fully symmetrical. Once the complex apparent power is
calculated then the P, Q, S, & PF are calculated in accordance with the following
formulas:
P = Re( S )
EQUATION1403 V1 EN

(Equation 174)

814
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Q = Im( S )
(Equation 175)

EQUATION1404 V1 EN

S = S =

P +Q
2

EQUATION1405 V1 EN

(Equation 176)

PF = cosj = P
S
EQUATION1406 V1 EN

(Equation 177)

Additionally to the power factor value the two binary output signals from the
function are provided which indicates the angular relationship between current and
voltage phasors. Binary output signal ILAG is set to one when current phasor is
lagging behind voltage phasor. Binary output signal ILEAD is set to one when
current phasor is leading the voltage phasor.
Each analogue output has a corresponding supervision level output (X_RANGE).
The output signal is an integer in the interval 0-4, see section "Measurement
supervision".

Calibration of analog inputs

Measured currents and voltages used in the CVMMXN function can be calibrated
to get class 0.5 measuring accuracy. This is achieved by amplitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation
below 5% and above 100% is constant and linear in between, see example in
figure 455.

815
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

IEC05000652 V2 EN

Figure 455:

Calibration curves

The first current and voltage phase in the group signals will be used as reference
and the amplitude and angle compensation will be used for related input signals.

Low pass filtering

In order to minimize the influence of the noise signal on the measurement it is


possible to introduce the recursive, low pass filtering of the measured values for P,
Q, S, U, I and power factor. This will make slower measurement response to the
step changes in the measured quantity. Filtering is performed in accordance with
the following recursive formula:
X = k X Old + (1 - k ) X Calculated
(Equation 178)

EQUATION1407 V1 EN

where:
X

is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function

XOld

is the measured value given from the measurement function in previous execution cycle

XCalculated is the new calculated value in the present execution cycle


k

is settable parameter by the end user which influence the filter properties

816
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.

Zero point clamping

In order to avoid erroneous measurements when either current or voltage signal is


not present, it is possible for the end user to set the amplitudeIGenZeroDb level for
current and voltage measurement UGenZeroDb is forced to zero. When either
current or voltage measurement is forced to zero automatically the measured values
for power (P, Q and S) and power factor are forced to zero as well. Since the
measurement supervision functionality, included in CVMMXN, is using these
values the zero clamping will influence the subsequent supervision (observe the
possibility to do zero point clamping within measurement supervision, see section
"Measurement supervision").

Compensation facility

In order to compensate for small amplitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it
is possible to perform on site calibration of the power measurement. This is
achieved by setting the complex constant which is then internally used within the
function to multiply the calculated complex apparent power S. This constant is set
as amplitude (setting parameter PowAmpFact, default value 1.000) and angle
(setting parameter PowAngComp, default value 0.0 degrees). Default values for
these two parameters are done in such way that they do not influence internally
calculated value (complex constant has default value 1). In this way calibration, for
specific operating range (for example, around rated power) can be done at site.
However, to perform this calibration it is necessary to have an external power
meter with high accuracy class available.

Directionality

If CT earthing parameter is set as described in section "Analog inputs", active and


reactive power will be measured always towards the protected object. This is
shown in the following figure 456.

817
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Busbar

IED

Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN

Figure 456:

Internal IED directionality convention for P & Q measurements

Practically, it means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.

Frequency

Frequency is actually not calculated within measurement block. It is simply


obtained from the pre-processing block and then just given out from the
measurement block as an output.

15.1.2.3

Phase current measurement CMMXU


The Phase current measurement (CMMXU) function must be connected to threephase current input in the configuration tool to be operable. Currents handled in the
function can be calibrated to get better then class 0.5 measuring accuracy for
internal use, on the outputs and IEC 61850. This is achieved by amplitude and

818
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

angle compensation at 5, 30 and 100% of rated current. The compensation below


5% and above 100% is constant and linear in between, see figure 455.
Phase currents (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ILx_RANG). The
supervision output signal is an integer in the interval 0-4, see section
"Measurement supervision".

15.1.2.4

Phase-phase and phase-neutral voltage measurements VMMXU,


VNMMXU
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".

15.1.2.5

Voltage and current sequence measurements VMSQI, CMSQI


The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, but
XRANG, are calculated within the measuring block and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an
integer in the interval 0-4, see section "Measurement supervision".

15.1.3

Function block
The available function blocks of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.

819
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

CVMMXN
I3P*
U3P*

S
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC10000016-1-en.vsd

IEC10000016 V1 EN

Figure 457:

CVMMXN function block

CMMXU
I3P*

IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC05000699-2-en.vsd

IEC05000699 V2 EN

Figure 458:

CMMXU function block

VNMMXU
U3P*

UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC09000850-1-en.vsd

IEC09000850 V1 EN

Figure 459:

VNMMXU function block

820
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

VMMXU
U3P*

UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL
IEC05000701-2-en.vsd

IEC05000701 V2 EN

Figure 460:

VMMXU function block

CMSQI
I3P*

3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703-2-en.vsd

IEC05000703 V2 EN

Figure 461:

CMSQI function block

VMSQI
U3P*

3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL
IEC05000704-2-en.vsd

IEC05000704 V2 EN

Figure 462:

15.1.4

VMSQI function block

Input and output signals


Table 539:
Name

CVMMXN Input signals


Type

Default

Description

I3P

GROUP
SIGNAL

Group signal for current input

U3P

GROUP
SIGNAL

Group signal for voltage input

821
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Table 540:
Name

CVMMXN Output signals


Type

Description

REAL

Apparent Power magnitude of deadband value

S_RANGE

INTEGER

Apparent Power range

P_INST

REAL

Active Power

REAL

Active Power magnitude of deadband value

P_RANGE

INTEGER

Active Power range

Q_INST

REAL

Reactive Power

REAL

Reactive Power magnitude of deadband value

Q_RANGE

INTEGER

Reactive Power range

PF

REAL

Power Factor magnitude of deadband value

PF_RANGE

INTEGER

Power Factor range

ILAG

BOOLEAN

Current is lagging voltage

ILEAD

BOOLEAN

Current is leading voltage

REAL

Calculate voltage magnitude of deadband value

U_RANGE

INTEGER

Calcuate voltage range

REAL

Calculated current magnitude of deadband value

I_RANGE

INTEGER

Calculated current range

REAL

System frequency magnitude of deadband value

F_RANGE

INTEGER

System frequency range

Table 541:
Name
I3P

Table 542:
Name

CMMXU Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 1

CMMXU Output signals


Type

Description

IL1

REAL

IL1 Amplitude, magnitude of reported value

IL1RANG

INTEGER

IL1 Amplitude range

IL1ANGL

REAL

IL1 Angle, magnitude of reported value

IL2

REAL

IL2 Amplitude, magnitude of reported value

IL2RANG

INTEGER

IL2 Amplitude range

IL2ANGL

REAL

IL2 Angle, magnitude of reported value

IL3

REAL

IL3 Amplitude, magnitude of reported value

IL3RANG

INTEGER

IL3 Amplitude range

IL3ANGL

REAL

IL3 Angle, magnitude of reported value

822
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Table 543:
Name
U3P

Table 544:
Name

VNMMXU Input signals


Type

Default

GROUP
SIGNAL

Description
Group connection abstract block 5

VNMMXU Output signals


Type

Description

UL1

REAL

UL1 Amplitude, magnitude of reported value

UL1RANG

INTEGER

UL1 Amplitude range

UL1ANGL

REAL

UL1 Angle, magnitude of reported value

UL2

REAL

UL2 Amplitude, magnitude of reported value

UL2RANG

INTEGER

UL2 Amplitude range

UL2ANGL

REAL

UL2 Angle, magnitude of reported value

UL3

REAL

UL3 Amplitude, magnitude of reported value

UL3RANG

INTEGER

UL3 Amplitude range

UL3ANGL

REAL

UL3 Angle, magnitude of reported value

Table 545:
Name
U3P

Table 546:
Name

VMMXU Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 2

VMMXU Output signals


Type

Description

UL12

REAL

UL12 Amplitude, magnitude of reported value

UL12RANG

INTEGER

UL12 Amplitude range

UL12ANGL

REAL

UL12 Angle, magnitude of reported value

UL23

REAL

UL23 Amplitude, magnitude of reported value

UL23RANG

INTEGER

UL23 Amplitude range

UL23ANGL

REAL

UL23 Angle, magnitude of reported value

UL31

REAL

UL31 Amplitude, magnitude of reported value

UL31RANG

INTEGER

UL31 Amplitude range

UL31ANGL

REAL

UL31 Angle, magnitude of reported value

Table 547:
Name
I3P

CMSQI Input signals


Type
GROUP
SIGNAL

Default
-

Description
Group connection abstract block 3

823
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Table 548:

CMSQI Output signals

Name

Type

3I0

REAL

3I0 Amplitude, magnitude of reported value

3I0RANG

INTEGER

3I0 Amplitude range

3I0ANGL

REAL

3I0 Angle, magnitude of reported value

I1

REAL

I1 Amplitude, magnitude of reported value

I1RANG

INTEGER

I1 Amplitude range

I1ANGL

REAL

I1 Angle, magnitude of reported value

I2

REAL

I2 Amplitude, magnitude of reported value

I2RANG

INTEGER

I2 Amplitude range

I2ANGL

REAL

I2 Angle, magnitude of reported value

Table 549:

VMSQI Input signals

Name

Type

U3P

GROUP
SIGNAL

Table 550:

Default
-

Description
Group connection abstract block 4

VMSQI Output signals

Name

15.1.5

Description

Type

Description

3U0

REAL

3U0 Amplitude, magnitude of reported value

3U0RANG

INTEGER

3U0 Amplitude range

3U0ANGL

REAL

3U0 Angle, magnitude of reported value

U1

REAL

U1 Amplitude, magnitude of reported value

U1RANG

INTEGER

U1 Amplitude range

U1ANGL

REAL

U1 Angle, magnitude of reported value

U2

REAL

U2 Amplitude, magnitude of reported value

U2RANG

INTEGER

U2 Amplitude range

U2ANGL

REAL

U2 Angle, magnitude of reported value

Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in
PCM600.

Table 551:
Name

CVMMXN Non group settings (basic)


Step

Default

SLowLim

Values (Range)
0.0 - 2000.0

Unit
%SB

0.1

80.0

Description
Low limit in % of SBase

SLowLowLim

0.0 - 2000.0

%SB

0.1

60.0

Low Low limit in % of SBase

SMin

0.0 - 2000.0

%SB

0.1

50.0

Minimum value in % of SBase

Table continues on next page

824
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Step

Default

SMax

Values (Range)
0.0 - 2000.0

Unit
%SB

0.1

200.0

Description
Maximum value in % of SBase

SRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

PMin

-2000.0 - 2000.0

%SB

0.1

-200.0

Minimum value in % of SBase

PMax

-2000.0 - 2000.0

%SB

0.1

200.0

Maximum value in % of SBase

PRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

QMin

-2000.0 - 2000.0

%SB

0.1

-200.0

Minimum value in % of SBase

QMax

-2000.0 - 2000.0

%SB

0.1

200.0

Maximum value in % of SBase

QRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

PFMin

-1.000 - 1.000

0.001

-1.000

Minimum value

PFMax

-1.000 - 1.000

0.001

1.000

Maximum value

PFRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UMin

0.0 - 200.0

%UB

0.1

50.0

Minimum value in % of UBase

UMax

0.0 - 200.0

%UB

0.1

200.0

Maximum value in % of UBase

URepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IMin

0.0 - 500.0

%IB

0.1

50.0

Minimum value in % of IBase

IMax

0.0 - 500.0

%IB

0.1

200.0

Maximum value in % of IBase

IRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

FrMin

0.000 - 100.000

Hz

0.001

0.000

Minimum value

FrMax

0.000 - 100.000

Hz

0.001

70.000

Maximum value

FrRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

Operation

Off
On

Off

Operation Off / On

IBase

1 - 99999

3000

Base setting for current values in A

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage value in kV

SBase

0.05 - 200000.00

MVA

0.05

2080.00

Base setting for power values in MVA

Mode

L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

L1, L2, L3

Selection of measured current and


voltage

Table continues on next page

825
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

PowAmpFact

0.000 - 6.000

0.001

1.000

Amplitude factor to scale power


calculations

PowAngComp

-180.0 - 180.0

Deg

0.1

0.0

Angle compensation for phase shift


between measured I & U

0.000 - 1.000

0.001

0.000

Low pass filter coefficient for power


measurement, U and I

Table 552:
Name

CVMMXN Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

SDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

SZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

SHiHiLim

0.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

SHiLim

0.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

SLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

PDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

PZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

PHiHiLim

-2000.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

PHiLim

-2000.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

PLowLim

-2000.0 - 2000.0

%SB

0.1

-120.0

Low limit in % of SBase

PLowLowLim

-2000.0 - 2000.0

%SB

0.1

-150.0

Low Low limit in % of SBase

PLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

QDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

QZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

QHiHiLim

-2000.0 - 2000.0

%SB

0.1

150.0

High High limit in % of SBase

QHiLim

-2000.0 - 2000.0

%SB

0.1

120.0

High limit in % of SBase

QLowLim

-2000.0 - 2000.0

%SB

0.1

-120.0

Low limit in % of SBase

QLowLowLim

-2000.0 - 2000.0

%SB

0.1

-150.0

Low Low limit in % of SBase

QLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

PFDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

PFZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

PFHiHiLim

-1.000 - 1.000

0.001

1.000

High High limit (physical value)

PFHiLim

-1.000 - 1.000

0.001

0.800

High limit (physical value)

PFLowLim

-1.000 - 1.000

0.001

-0.800

Low limit (physical value)

PFLowLowLim

-1.000 - 1.000

0.001

-1.000

Low Low limit (physical value)

PFLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

Table continues on next page

826
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

UDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

UHiHiLim

0.0 - 200.0

%UB

0.1

150.0

High High limit in % of UBase

UHiLim

0.0 - 200.0

%UB

0.1

120.0

High limit in % of UBase

ULowLim

0.0 - 200.0

%UB

0.1

80.0

Low limit in % of UBase

ULowLowLim

0.0 - 200.0

%UB

0.1

60.0

Low Low limit in % of UBase

ULimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

IDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

IZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

IHiHiLim

0.0 - 500.0

%IB

0.1

150.0

High High limit in % of IBase

IHiLim

0.0 - 500.0

%IB

0.1

120.0

High limit in % of IBase

ILowLim

0.0 - 500.0

%IB

0.1

80.0

Low limit in % of IBase

ILowLowLim

0.0 - 500.0

%IB

0.1

60.0

Low Low limit in % of IBase

ILimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

FrDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

FrZeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

FrHiHiLim

0.000 - 100.000

Hz

0.001

65.000

High High limit (physical value)

FrHiLim

0.000 - 100.000

Hz

0.001

63.000

High limit (physical value)

FrLowLim

0.000 - 100.000

Hz

0.001

47.000

Low limit (physical value)

FrLowLowLim

0.000 - 100.000

Hz

0.001

45.000

Low Low limit (physical value)

FrLimHyst

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

UGenZeroDb

1 - 100

%UB

Zero point clamping in % of Ubase

IGenZeroDb

1 - 100

%IB

Zero point clamping in % of Ibase

UAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


5% of Ur

UAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


30% of Ur

UAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


100% of Ur

IAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


5% of Ir

IAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


30% of Ir

IAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


100% of Ir

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of Ir

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of Ir

827
Technical reference manual

Section 15
Monitoring

Table 553:
Name

1MRK 505 222-UEN B

CMMXU Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

IL1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Operation

Off
On

Off

Operation Mode On / Off

IBase

1 - 99999

3000

Base setting for current level in A

IL1Max

0.000 10000000000.000

0.001

1000.000

Maximum value

IL1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IL1AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

IL2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

IL2Max

0.000 10000000000.000

0.001

1000.000

Maximum value

IL2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IL2AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

IL3DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

IL3Max

0.000 10000000000.000

0.001

1000.000

Maximum value

IL3RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

IL3AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Table 554:
Name

CMMXU Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

IL1ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

IL1HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

IL1HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

IAmpComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


5% of Ir

IAmpComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


30% of Ir

IL1LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

IL1LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

Table continues on next page

828
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

IAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate current at


100% of Ir

IAngComp5

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 5% of Ir

IL1Min

0.000 10000000000.000

0.001

0.000

Minimum value

IAngComp30

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 30% of Ir

IAngComp100

-10.000 - 10.000

Deg

0.001

0.000

Angle calibration for current at 100% of Ir

IL1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

IL2ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

IL2HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

IL2HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

IL2LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

IL2LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

IL2Min

0.000 10000000000.000

0.001

0.000

Minimum value

IL2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

IL3ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

IL3HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

IL3HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

IL3LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

IL3LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

IL3Min

0.000 10000000000.000

0.001

0.000

Minimum value

IL3LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

Table 555:

VNMMXU Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

UL1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Operation

Off
On

Off

Operation Mode On / Off

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level in kV

UL1Max

0.000 10000000000.000

0.001

300000.000

Maximum value

Table continues on next page

829
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

UL1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

UL1AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL2Max

0.000 10000000000.000

0.001

300000.000

Maximum value

UL2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

UL2AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL3DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL3Max

0.000 10000000000.000

0.001

300000.000

Maximum value

UL3RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL3LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

UL3AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Table 556:
Name

VNMMXU Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

UL1ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL1HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

UL1HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

UL1LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

UL1LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

UAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


100% of Ur

UL1Min

0.000 10000000000.000

0.001

0.000

Minimum value

UL2ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL2HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

Table continues on next page


830
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

UL2HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

UL2LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

UL2LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

UL2Min

0.000 10000000000.000

0.001

0.000

Minimum value

UL3ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL3HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

UL3HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

UL3LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

UL3LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

UL3Min

0.000 10000000000.000

0.001

0.000

Minimum value

Table 557:

VMMXU Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

UL12DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Operation

Off
On

Off

Operation Mode On / Off

UBase

0.05 - 2000.00

kV

0.05

400.00

Base setting for voltage level in kV

UL12Max

0.000 10000000000.000

0.001

500000.000

Maximum value

UL12RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL12AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL23DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL23Max

0.000 10000000000.000

0.001

500000.000

Maximum value

UL23RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL23AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

UL31DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Table continues on next page

831
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

UL31Max

0.000 10000000000.000

0.001

500000.000

Maximum value

UL31RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UL31AnDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Table 558:
Name

VMMXU Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

UL12ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL12HiHiLim

0.000 10000000000.000

0.001

450000.000

High High limit (physical value)

UL12HiLim

0.000 10000000000.000

0.001

420000.000

High limit (physical value)

UL12LowLim

0.000 10000000000.000

0.001

380000.000

Low limit (physical value)

UL12LowLowLim

0.000 10000000000.000

0.001

350000.000

Low Low limit (physical value)

UAmpComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to calibrate voltage at


100% of Ur

UL12Min

0.000 10000000000.000

0.001

0.000

Minimum value

UL12LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

UL23ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL23HiHiLim

0.000 10000000000.000

0.001

450000.000

High High limit (physical value)

UL23HiLim

0.000 10000000000.000

0.001

420000.000

High limit (physical value)

UL23LowLim

0.000 10000000000.000

0.001

380000.000

Low limit (physical value)

UL23LowLowLim

0.000 10000000000.000

0.001

350000.000

Low Low limit (physical value)

UL23Min

0.000 10000000000.000

0.001

0.000

Minimum value

UL23LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

UL31ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

UL31HiHiLim

0.000 10000000000.000

0.001

450000.000

High High limit (physical value)

UL31HiLim

0.000 10000000000.000

0.001

420000.000

High limit (physical value)

UL31LowLim

0.000 10000000000.000

0.001

380000.000

Low limit (physical value)

Table continues on next page

832
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

UL31LowLowLim

0.000 10000000000.000

0.001

350000.000

Low Low limit (physical value)

UL31Min

0.000 10000000000.000

0.001

0.000

Minimum value

UL31LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

Table 559:

CMSQI Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

3I0DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

3I0Min

0.000 10000000000.000

0.001

0.000

Minimum value

3I0Max

0.000 10000000000.000

0.001

1000.000

Maximum value

3I0RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

3I0LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

3I0AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Operation

Off
On

Off

Operation Mode On / Off

3I0AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

3I0AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

3I0AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

I1Min

0.000 10000000000.000

0.001

0.000

Minimum value

I1Max

0.000 10000000000.000

0.001

1000.000

Maximum value

I1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I1AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

I1AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

I1AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

I2Min

0.000 10000000000.000

0.001

0.000

Minimum value

Table continues on next page


833
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

I2Max

0.000 10000000000.000

0.001

1000.000

Maximum value

I2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

I2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

I2AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

I2AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

I2AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

Table 560:
Name

CMSQI Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

3I0ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

3I0HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

3I0HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

3I0LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

3I0LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

3I0AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

I1ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

I1HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

I1HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

I1LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

I1LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

I1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

I1AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

I1AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

I2ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

I2HiHiLim

0.000 10000000000.000

0.001

900.000

High High limit (physical value)

I2HiLim

0.000 10000000000.000

0.001

800.000

High limit (physical value)

I2LowLim

0.000 10000000000.000

0.001

0.000

Low limit (physical value)

Table continues on next page

834
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

I2LowLowLim

0.000 10000000000.000

0.001

0.000

Low Low limit (physical value)

I2AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

I2AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

Table 561:

VMSQI Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

3U0DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

3U0Min

0.000 10000000000.000

0.001

0.000

Minimum value

3U0Max

0.000 10000000000.000

0.001

300000.000

Maximum value

3U0RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

3U0LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

3U0AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

Operation

Off
On

Off

Operation Mode On / Off

3U0AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

3U0AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

3U0AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

3U0AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

U1DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

U1Min

0.000 10000000000.000

0.001

0.000

Minimum value

U1Max

0.000 10000000000.000

0.001

300000.000

Maximum value

U1RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

U1LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

U1AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

U2DbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

U2Min

0.000 10000000000.000

0.001

0.000

Minimum value

U2Max

0.000 10000000000.000

0.001

300000.000

Maximum value

Table continues on next page


835
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

U2RepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

U2LimHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range and is


common for all limits

U2AngDbRepInt

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

U2AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

U2AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

U2AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

UAmpPreComp5

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage


at 5% of Ir

UAmpPreComp30

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage


at 30% of Ir

UAmpPreComp100

-10.000 - 10.000

0.001

0.000

Amplitude factor to pre-calibrate voltage


at 100% of Ir

Table 562:
Name

VMSQI Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

3U0ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

3U0HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

3U0HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

3U0LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

3U0LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

U1ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

U1HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

U1HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

U1LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

U1LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

U1AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

U1AngMin

-180.000 - 180.000

Deg

0.001

-180.000

Minimum value

U1AngMax

-180.000 - 180.000

Deg

0.001

180.000

Maximum value

U1AngRepTyp

Cyclic
Dead band
Int deadband

Cyclic

Reporting type

U2ZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

Table continues on next page

836
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

U2HiHiLim

0.000 10000000000.000

0.001

260000.000

High High limit (physical value)

U2HiLim

0.000 10000000000.000

0.001

240000.000

High limit (physical value)

U2LowLim

0.000 10000000000.000

0.001

220000.000

Low limit (physical value)

U2LowLowLim

0.000 10000000000.000

0.001

200000.000

Low Low limit (physical value)

U2AngZeroDb

0 - 100000

m%

Zero point clamping in 0,001% of range

15.1.6

Technical data
Table 563:

CVMMXN technical data

Function

Range or value

Accuracy

Frequency

(0.95-1.05) fr

2.0 mHz

Voltage

(0.1-1.5) Ur

0.5% of Ur at UUr
0.5% of U at U > Ur

Connected current

(0.2-4.0) Ir

0.5% of Ir at I Ir
0.5% of I at I > Ir

Active power, P

0.1 x Ur< U < 1.5 x Ur


0.2 x Ir < I < 4.0 x Ir

Reactive power, Q

0.1 x Ur< U < 1.5 x Ur


0.2 x Ir < I < 4.0 x Ir

1.0% of Sr at S Sr
1.0% of S at S > Sr
Conditions:
0.8 x Ur < U < 1.2 Ur
0.2 x Ir < I < 1.2 Ir

Apparent power, S

0.1 x Ur < U < 1.5 x Ur


0.2 x Ir< I < 4.0 x Ir

Power factor, cos ()

0.1 x Ur < U < 1.5 x Ur


0.2 x Ir< I < 4.0 x Ir

15.2

Event counter CNTGGIO

15.2.1

Identification
Function description
Event counter

IEC 61850
identification

0.02

IEC 60617
identification

CNTGGIO

ANSI/IEEE C37.2
device number
-

S00946 V1 EN

15.2.2

Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.
837

Technical reference manual

Section 15
Monitoring
15.2.3

1MRK 505 222-UEN B

Principle of operation
Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many
times each of the inputs has been activated. The counter memory for each of the six
inputs is updated, giving the total number of times the input has been activated, as
soon as an input is activated. The maximum count up speed is 10 pulses per
second. The maximum counter value is 10 000. For counts above 10 000 the
counter will stop at 10 000 and no restart will take place.
To not risk that the flash memory is worn out due to too many writings, a
mechanism for limiting the number of writings per time period is included in the
product. This however gives as a result that it can take long time, up to several
minutes, before a new value is stored in the flash memory. And if a new
CNTGGIO value is not stored before auxiliary power interruption, it will be lost.
CNTGGIO stored values in flash memory will however not be lost at an auxiliary
power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters
at testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
All inputs are configured via PCM600.

15.2.3.1

Reporting
The content of the counters can be read in the local HMI.
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.

15.2.3.2

Design
The function block has six inputs for increasing the counter values for each of the
six counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked and are not updated. Valid number is held.
The function block has an input RESET. At activation of this input all six counters
are set to 0.

838
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

15.2.4

Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET

VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6

IEC05000345-2-en.vsd
IEC05000345 V2 EN

Figure 463:

15.2.5

CNTGGIO function block

Input signals
Table 564:

CNTGGIO Input signals

Name

Type
BOOLEAN

Block of function

COUNTER1

BOOLEAN

Input for counter1

COUNTER2

BOOLEAN

Input for counter2

COUNTER3

BOOLEAN

Input for counter3

COUNTER4

BOOLEAN

Input for counter4

COUNTER5

BOOLEAN

Input for counter5

COUNTER6

BOOLEAN

Input for counter6

RESET

BOOLEAN

Reset of function

CNTGGIO Output signals

Name

Table 566:

Description

BLOCK

Table 565:

15.2.6

Default

Type

Description

VALUE1

INTEGER

Output of counter1

VALUE2

INTEGER

Output of counter2

VALUE3

INTEGER

Output of counter3

VALUE4

INTEGER

Output of counter4

VALUE5

INTEGER

Output of counter5

VALUE6

INTEGER

Output of counter6

Setting parameters
CNTGGIO Group settings (basic)

Name
Operation

Values (Range)
Off
On

Unit
-

Step
-

Default
Off

Description
Operation Off / On

839
Technical reference manual

Section 15
Monitoring
15.2.7

1MRK 505 222-UEN B

Technical data
Table 567:

CNTGGIO technical data

Function

15.3

Range or value

Accuracy

Counter value

0-10000

Max. count up speed

10 pulses/s

Event function EVENT


Function description
Event function

IEC 61850
identification

IEC 60617
identification

EVENT

ANSI/IEEE C37.2
device number
-

S00946 V1 EN

15.3.1

Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is
connected to the Event function (EVENT). The event function block is used for
LON and SPA communication.
Analog and double indication values are also transferred through EVENT function.

15.3.2

Principle of operation
The main purpose of the event function (EVENT) is to generate events when the
state or value of any of the connected input signals is in a state, or is undergoing a
state transition, for which event generation is enabled.
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given
a name from the Application Configuration tool. The inputs are normally used to
create single events, but are also intended for double indication events.
EVENT function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical
signals and binary input channels. The internal signals are time-tagged in the main
processing module, while the binary input channels are time-tagged directly on the
input module. The time-tagging of the events that are originated from internal
logical signals have a resolution corresponding to the execution cyclicity of
EVENT function. The time-tagging of the events that are originated from binary
input signals have a resolution of 1 ms.

840
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each
input is intended to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are
treated commonly for both the LON and SPA communication. The EventMask can
be set individually for each input channel. These settings are available:

NoEvents
OnSet
OnReset
OnChange
AutoDetect

It is possible to define which part of EVENT function generates the events. This
can be performed individually for the SPAChannelMask and LONChannelMask
respectively. For each communication type these settings are available:

Off
Channel 1-8
Channel 9-16
Channel 1-16

For LON communication the events normally are sent to station level at change. It
is possibly also to set a time for cyclic sending of the events individually for each
input channel.
To protect the SA system from signals with a high change rate that can easily
saturate the event system or the communication subsystems behind it, a quota
limiter is implemented. If an input creates events at a rate that completely consume
the granted quota then further events from the channel will be blocked. This block
will be removed when the input calms down and the accumulated quota reach 66%
of the maximum burst quota. The maximum burst quota per input channel is 45
events per second.

841
Technical reference manual

Section 15
Monitoring
15.3.3

1MRK 505 222-UEN B

Function block
EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000697-2-en.vsd
IEC05000697 V2 EN

Figure 464:

15.3.4

EVENT function block

Input and output signals


Table 568:
Name

EVENT Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

GROUP
SIGNAL

Input 1

INPUT2

GROUP
SIGNAL

Input 2

INPUT3

GROUP
SIGNAL

Input 3

INPUT4

GROUP
SIGNAL

Input 4

INPUT5

GROUP
SIGNAL

Input 5

INPUT6

GROUP
SIGNAL

Input 6

INPUT7

GROUP
SIGNAL

Input 7

INPUT8

GROUP
SIGNAL

Input 8

INPUT9

GROUP
SIGNAL

Input 9

INPUT10

GROUP
SIGNAL

Input 10

INPUT11

GROUP
SIGNAL

Input 11

INPUT12

GROUP
SIGNAL

Input 12

Table continues on next page

842
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

15.3.5
Table 569:

Type

Default

Description

INPUT13

GROUP
SIGNAL

Input 13

INPUT14

GROUP
SIGNAL

Input 14

INPUT15

GROUP
SIGNAL

Input 15

INPUT16

GROUP
SIGNAL

Input 16

Setting parameters
EVENT Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SPAChannelMask

Off
Channel 1-8
Channel 9-16
Channel 1-16

Off

SPA channel mask

LONChannelMask

Off
Channel 1-8
Channel 9-16
Channel 1-16

Off

LON channel mask

EventMask1

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 1

EventMask2

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 2

EventMask3

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 3

EventMask4

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 4

EventMask5

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 5

EventMask6

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 6

Table continues on next page

843
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

EventMask7

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 7

EventMask8

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 8

EventMask9

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 9

EventMask10

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 10

EventMask11

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 11

EventMask12

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 12

EventMask13

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 13

EventMask14

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 14

EventMask15

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 15

EventMask16

NoEvents
OnSet
OnReset
OnChange
AutoDetect

AutoDetect

Reporting criteria for input 16

MinRepIntVal1

0 - 3600

Minimum reporting interval input 1

MinRepIntVal2

0 - 3600

Minimum reporting interval input 2

MinRepIntVal3

0 - 3600

Minimum reporting interval input 3

MinRepIntVal4

0 - 3600

Minimum reporting interval input 4

MinRepIntVal5

0 - 3600

Minimum reporting interval input 5

Table continues on next page


844
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

MinRepIntVal6

0 - 3600

Minimum reporting interval input 6

MinRepIntVal7

0 - 3600

Minimum reporting interval input 7

MinRepIntVal8

0 - 3600

Minimum reporting interval input 8

MinRepIntVal9

0 - 3600

Minimum reporting interval input 9

MinRepIntVal10

0 - 3600

Minimum reporting interval input 10

MinRepIntVal11

0 - 3600

Minimum reporting interval input 11

MinRepIntVal12

0 - 3600

Minimum reporting interval input 12

MinRepIntVal13

0 - 3600

Minimum reporting interval input 13

MinRepIntVal14

0 - 3600

Minimum reporting interval input 14

MinRepIntVal15

0 - 3600

Minimum reporting interval input 15

MinRepIntVal16

0 - 3600

Minimum reporting interval input 16

15.4

Logical signal status report BINSTATREP


Function description
Logical signal status report

15.4.1

IEC 61850
identification
BINSTATREP

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The Logical signal status report (BINSTATREP) function makes it possible for a
SPA master to poll signals from various other functions.

15.4.2

Principle of operation
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or
via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.

845
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

INPUTn
OUTPUTn
t

t
IEC09000732-1-en.vsd

IEC09000732 V1 EN

Figure 465:

15.4.3

BINSTATREP logical diagram

Function block
BINSTATREP
OUTPUT1
BLOCK
^INPUT1
OUTPUT2
^INPUT2
OUTPUT3
^INPUT3
OUTPUT4
^INPUT4
OUTPUT5
^INPUT5
OUTPUT6
^INPUT6
OUTPUT7
^INPUT7
OUTPUT8
^INPUT8
OUTPUT9
^INPUT9
OUTPUT10
^INPUT10
OUTPUT11
^INPUT11
OUTPUT12
^INPUT12
OUTPUT13
^INPUT13
OUTPUT14
^INPUT14
OUTPUT15
^INPUT15
OUTPUT16
^INPUT16
IEC09000730-1-en.vsd
IEC09000730 V1 EN

Figure 466:

15.4.4

BINSTATREP function block

Input and output signals


Table 570:
Name

BINSTATREP Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Single status report input 1

INPUT2

BOOLEAN

Single status report input 2

INPUT3

BOOLEAN

Single status report input 3

INPUT4

BOOLEAN

Single status report input 4

INPUT5

BOOLEAN

Single status report input 5

INPUT6

BOOLEAN

Single status report input 6

INPUT7

BOOLEAN

Single status report input 7

INPUT8

BOOLEAN

Single status report input 8

INPUT9

BOOLEAN

Single status report input 9

Table continues on next page


846
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Type

Single status report input 10

INPUT11

BOOLEAN

Single status report input 11

INPUT12

BOOLEAN

Single status report input 12

INPUT13

BOOLEAN

Single status report input 13

INPUT14

BOOLEAN

Single status report input 14

INPUT15

BOOLEAN

Single status report input 15

INPUT16

BOOLEAN

Single status report input 16

BINSTATREP Output signals

Name

Table 572:

Description

BOOLEAN

Table 571:

15.4.5

Default

INPUT10

Type

Description

OUTPUT1

BOOLEAN

Logical status report output 1

OUTPUT2

BOOLEAN

Logical status report output 2

OUTPUT3

BOOLEAN

Logical status report output 3

OUTPUT4

BOOLEAN

Logical status report output 4

OUTPUT5

BOOLEAN

Logical status report output 5

OUTPUT6

BOOLEAN

Logical status report output 6

OUTPUT7

BOOLEAN

Logical status report output 7

OUTPUT8

BOOLEAN

Logical status report output 8

OUTPUT9

BOOLEAN

Logical status report output 9

OUTPUT10

BOOLEAN

Logical status report output 10

OUTPUT11

BOOLEAN

Logical status report output 11

OUTPUT12

BOOLEAN

Logical status report output 12

OUTPUT13

BOOLEAN

Logical status report output 13

OUTPUT14

BOOLEAN

Logical status report output 14

OUTPUT15

BOOLEAN

Logical status report output 15

OUTPUT16

BOOLEAN

Logical status report output 16

Setting parameters
BINSTATREP Non group settings (basic)

Name
t

15.5

Values (Range)
0.000 - 60000.000

Unit
s

Step
0.001

Default
10.000

Description
Time delay of function

Fault locator LMBRFLO


Function description
Fault locator

IEC 61850
identification
LMBRFLO

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

847
Technical reference manual

Section 15
Monitoring
15.5.1

1MRK 505 222-UEN B

Introduction
The accurate fault locator is an essential component to minimize the outages after a
persistent fault and/or to pin-point a weak spot on the line.
The fault locator is an impedance measuring function giving the distance to the
fault in percent, km or miles. The main advantage is the high accuracy achieved by
compensating for load current and for the mutual zero-sequence effect on double
circuit lines.
The compensation includes setting of the remote and local sources and calculation
of the distribution of fault currents from each side. This distribution of fault
current, together with recorded load (pre-fault) currents, is used to exactly calculate
the fault position. The fault can be recalculated with new source data at the actual
fault to further increase the accuracy.
Especially on heavily loaded long lines (where the fault locator is most important)
where the source voltage angles can be up to 35-40 degrees apart the accuracy can
be still maintained with the advanced compensation included in fault locator.

15.5.2

Principle of operation
The Fault locator (LMBRFLO) in the IED is an essential complement to other
monitoring functions, since it measures and indicates the distance to the fault with
great accuracy.
When calculating distance to fault, pre-fault and fault phasors of currents and
voltages are selected from the Trip value recorder data, thus the analog signals used
by the fault locator must be among those connected to the disturbance report
function. The analog configuration (channel selection) is performed using the
parameter setting tool within PCM600.
The calculation algorithm considers the effect of load currents, double-end infeed
and additional fault resistance.
R0L+jX0L
R1L+jX1L
R1A+jX1A

Z0m=Z0m+jX0m

R1B+jX1B

R0L+jX0L
R1L+jX1L
DRPRDRE
LMBRFLO
IEC05000045_2_en.vsd
IEC05000045 V2 EN

Figure 467:

Simplified network configuration with network data, required for


settings of the fault location-measuring function

848
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

If source impedance in the near and far end of the protected line have changed in a
significant manner relative to the set values at fault location calculation time (due
to exceptional switching state in the immediate network, power generation out of
order, and so on), new values can be entered via the local HMI and a recalculation
of the distance to the fault can be ordered using the algorithm described below. Its
also possible to change fault loop. In this way, a more accurate location of the fault
can be achieved.
The function indicates the distance to the fault as a percentage of the line length, in
kilometers or miles as selected on the local HMI. The fault location is stored as a
part of the disturbance report information (ER, DR, IND, TVR and FL) and
managed via the local HMI or PCM600.

15.5.2.1

Measuring Principle
For transmission lines with voltage sources at both line ends, the effect of doubleend infeed and additional fault resistance must be considered when calculating the
distance to the fault from the currents and voltages at one line end. If this is not
done, the accuracy of the calculated figure will vary with the load flow and the
amount of additional fault resistance.
The calculation algorithm used in the fault locator in compensates for the effect of
double-end infeed, additional fault resistance and load current.

15.5.2.2

Accurate algorithm for measurement of distance to fault


Figure 468 shows a single-line diagram of a single transmission line, that is fed
from both ends with source impedances ZA and ZB. Assume that the fault occurs at
a distance F from IED A on a line with the length L and impedance ZL. The fault
resistance is defined as RF. A single-line model is used for better clarification of
the algorithm.

849
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

L
F

ZA

A
IA

pZL

IB

(1-p).ZL

ZB

IF
UA

RF

xx01000171.vsd
IEC01000171 V1 EN

Figure 468:

Fault on transmission line fed from both ends

From figure 468 it is evident that:


U A = I A p Z L + IF R F
(Equation 179)

EQUATION95 V1 EN

Where:
IA

is the line current after the fault, that is, pre-fault current plus current change due to the fault,

IF

is the fault current and

is a relative distance to the fault

The fault current is expressed in measurable quantities by:


IF A
IF = -------DA
(Equation 180)

EQUATION96 V1 EN

Where:
IFA

is the change in current at the point of measurement, IED A and

DA

is a fault current-distribution factor, that is, the ratio between the fault current at line end A
and the total fault current.

For a single line, the value is equal to:


( 1 p ) Z L + ZB
DA = ----------------------------------------Z A + Z L + ZB
EQUATION97 V1 EN

(Equation 181)

850
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Thus, the general fault location equation for a single line is:
I FA
- RF
U A = I A p Z L + ------DA
(Equation 182)

EQUATION98 V1 EN

Table 573:

Expressions for UA, IA and IFA for different types of faults

Fault type:
L1-N

UA
UL1A

IA
IL1A + KN x INA

IFA

3
--- D ( I L1A I 0A )
2
EQUATION110 V1 EN

L2-N

UL2A

IL2A + KN x INA

L3-N

UL3A

IL3A + KN x INA

3
--- D ( I L2A I 0A )
2
EQUATION111 V1 EN

3
--- D ( I L3A I0A )
2
EQUATION112 V1 EN

L1-L2-L3, L1-L2,L1-L2N

UL1A-UL2A

IL1A - IL2A

L2-L3, L2-L3-N

UL2A-UL3A

IL2A - IL3A

L3-L1, L3-L1-N

UL3A-UL1A

IL3A - IL1A

DIL 1 L 2 A
EQUATION113 V1 EN

DIL2L3A
EQUATION114 V1 EN

DIL3L1A
EQUATION115 V1 EN

The KN complex quantity for zero-sequence compensation for the single line is
equal to:
Z0L Z 1L
K N = -----------------------3 Z1L
EQUATION99 V1 EN

(Equation 183)

DI is the change in current, that is the current after the fault minus the current
before the fault.
In the following, the positive sequence impedance for ZA, ZB and ZL is inserted
into the equations, because this is the value used in the algorithm.
For double lines, the fault equation is:

851
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

I FA
U A = I A p Z 1L + -------- RF + I 0P Z 0M
DA
(Equation 184)

EQUATION100 V1 EN

Where:
I0P

is a zero sequence current of the parallel line,

Z0M

is a mutual zero sequence impedance and

DA

is the distribution factor of the parallel line, which is:

( 1 p ) ( ZA + ZA L + ZB ) + Z B
DA = ---------------------------------------------------------------------------2 ZA + Z L + 2 Z B
EQUATION101 V1 EN

The KN compensation factor for the double line becomes:


Z0L Z 1L
Z 0M I 0P
- + ---------------- ------K N = ----------------------3 Z1L
3 Z1L I 0A
EQUATION102 V1 EN

(Equation 185)

From these equations it can be seen, that, if Z0m = 0, then the general fault location
equation for a single line is obtained. Only the distribution factor differs in these
two cases.
Because the DA distribution factor according to equation 182 or 184 is a function
of p, the general equation 184 can be written in the form:
2

p p K1 + K2 K3 RF = 0
EQUATION103 V1 EN

(Equation 186)

Where:
UA
ZB
- + --------------------------+1
K 1 = --------------I A ZL Z L + ZA DD
EQUATION104 V1 EN

(Equation 187)

UA
ZB
K2 = --------------- --------------------------- + 1
IA Z L Z L + Z A DD
EQUATION105 V1 EN

(Equation 188)

IF A ZA + ZB
- --------------------------- + 1
K 3 = --------------
I A Z L Z 1 + ZA DD
EQUATION106 V1 EN

(Equation 189)

and:
852
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

ZADD = ZA + ZB for parallel lines.


IA, IFA and UA are given in the above table.
KN is calculated automatically according to equation 185.
ZA, ZB, ZL, Z0L and Z0M are setting parameters.

For a single line, Z0M = 0 and ZADD = 0. Thus, equation 186 applies to both single
and parallel lines.
Equation 186 can be divided into real and imaginary parts:
2

p p Re ( K 1 ) + Re ( K 2 ) R F Re ( K 3 ) = 0
EQUATION107 V1 EN

(Equation 190)

p Im ( K1 ) + Im ( K 2 ) R F Im ( K3 ) = 0
EQUATION108 V1 EN

(Equation 191)

If the imaginary part of K3 is not zero, RF can be solved according to equation 191,
and then inserted to equation 190. According to equation 190, the relative distance
to the fault is solved as the root of a quadratic equation.
Equation 190 gives two different values for the relative distance to the fault as a
solution. A simplified load compensated algorithm, which gives an unequivocal
figure for the relative distance to the fault, is used to establish the value that should
be selected.
If the load compensated algorithms according to the above do not give a reliable
solution, a less accurate, non-compensated impedance model is used to calculate
the relative distance to the fault.

15.5.2.3

The non-compensated impedance model


In the non-compensated impedance model, IA line current is used instead of IFA
fault current:
U A = p Z 1 L IA + R F IA
EQUATION109 V1 EN

(Equation 192)

Where:
IA

is according to table 573.

The accuracy of the distance-to-fault calculation, using the non-compensated


impedance model, is influenced by the pre-fault load current. So, this method is
only used if the load compensated models do not function.

853
Technical reference manual

Section 15
Monitoring
15.5.2.4

1MRK 505 222-UEN B

IEC 60870-5-103
The communication protocol IEC 60870-5-103 may be used to poll fault location
information from the IED to a master (that is station HSI). There are two outputs
that must be connected to appropriate inputs on the function block I103StatFltDis,
FLTDISTX gives distance to fault (reactance, according the standard) and
CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX
output.

15.5.3

Function block
LMBRFLO
PHSELL1*
FLTDISTX
PHSELL2*
CALCMADE
PHSELL3*
BCD_80
CALCDIST*
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
IEC05000679-2-en.vsd
IEC05000679 V3 EN

Figure 469:

15.5.4

FLO function block

Input and output signals


Table 574:
Name

LMBRFLO Input signals


Type

Default

Description

PHSELL1

BOOLEAN

Phase selecton L1

PHSELL2

BOOLEAN

Phase selecton L2

PHSELL3

BOOLEAN

Phase selecton L3

CALCDIST

BOOLEAN

Do calculate fault distance (release)

Table 575:
Name

LMBRFLO Output signals


Type

Description

FLTDISTX

REAL

Reactive distance to fault

CALCMADE

BOOLEAN

Fault calculation made

BCD_80

BOOLEAN

Distance in binary coded data, bit represents 80%

BCD_40

BOOLEAN

Distance in binary coded data, bit represents 40%

BCD_20

BOOLEAN

Distance in binary coded data, bit represents 20%

BCD_10

BOOLEAN

Distance in binary coded data, bit represents 10%

BCD_8

BOOLEAN

Distance in binary coded data, bit represents 8%

BCD_4

BOOLEAN

Distance in binary coded data, bit represents 4%

BCD_2

BOOLEAN

Distance in binary coded data, bit represents 2%

BCD_1

BOOLEAN

Distance in binary coded data, bit represents 1%

854
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

15.5.5
Table 576:

Setting parameters
LMBRFLO Group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

R1A

0.001 - 1500.000

ohm/p

0.001

2.000

Source resistance A (near end)

X1A

0.001 - 1500.000

ohm/p

0.001

12.000

Source reactance A (near end)

R1B

0.001 - 1500.000

ohm/p

0.001

2.000

Source resistance B (far end)

X1B

0.001 - 1500.000

ohm/p

0.001

12.000

Source reactance B (far end)

R1L

0.001 - 1500.000

ohm/p

0.001

2.000

Positive sequence line resistance

X1L

0.001 - 1500.000

ohm/p

0.001

12.500

Positive sequence line reactance

R0L

0.001 - 1500.000

ohm/p

0.001

8.750

Zero sequence line resistance

X0L

0.001 - 1500.000

ohm/p

0.001

50.000

Zero sequence line reactance

R0M

0.000 - 1500.000

ohm/p

0.001

0.000

Zero sequence mutual resistance

X0M

0.000 - 1500.000

ohm/p

0.001

0.000

Zero sequence mutual reactance

LineLength

0.0 - 10000.0

0.1

40.0

Length of line

Step

Default

Table 577:

LMBRFLO Non group settings (basic)

Name

Values (Range)

Unit

Description

DrepChNoIL1

1 - 30

Ch

Recorder input number recording phase


current, IL1

DrepChNoIL2

1 - 30

Ch

Recorder input number recording phase


current, IL2

DrepChNoIL3

1 - 30

Ch

Recorder input number recording phase


current, IL3

DrepChNoIN

0 - 30

Ch

Recorder input number recording


residual current, IN

DrepChNoIP

0 - 30

Ch

Recorder input number recording 3I0 on


parallel line

DrepChNoUL1

1 - 30

Ch

Recorder input number recording phase


voltage, UL1

DrepChNoUL2

1 - 30

Ch

Recorder input number recording phase


voltage, UL2

DrepChNoUL3

1 - 30

Ch

Recorder input number recording phase


voltage, UL3

855
Technical reference manual

Section 15
Monitoring
15.5.6

1MRK 505 222-UEN B

Technical data
Table 578:

LMBRFLO technical data

Function

15.6

Value or range

Reactive and resistive reach

(0.001-1500.000) /phase

2.0% static accuracy


2.0% degrees static
angular accuracy
Conditions:
Voltage range: (0.1-1.1) x Ur
Current range: (0.5-30) x Ir

Phase selection

According to input signals

Maximum number of fault


locations

100

Measured value expander block RANGE_XP


Function description
Measured value expander block

15.6.1

Accuracy

IEC 61850
identification
RANGE_XP

IEC 60617
identification
-

ANSI/IEEE C37.2
device number
-

Introduction
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI
and VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and highhigh limit. The measure value expander block (RANGE_XP) has been introduced
to enable translating the integer output signal from the measuring functions to 5
binary signals: below low-low limit, below low limit, normal, above high-high
limit or above high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose.

15.6.2

Principle of operation
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO).
The function block converts the input integer value to five binary output signals
according to table 579.

856
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Table 579:

Input integer value converted to binary output signals

Measured supervised
value is:
Output:

below low-low between low


limit
low and low
limit

LOWLOW

between low
and high limit

between high- above highhigh and high high limit


limit

High

LOW

High

NORMAL

High

HIGH

High

HIGHHIGH

15.6.3

High

Function block
RANGE*

RANGE_XP
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346-2-en.vsd

IEC05000346 V2 EN

Figure 470:

15.6.4

Input and output signals


Table 580:
Name
RANGE

Table 581:
Name

15.7

RANGE_XP function block

RANGE_XP Input signals


Type
INTEGER

Default
0

Description
Measured value range

RANGE_XP Output signals


Type

Description

HIGHHIGH

BOOLEAN

Measured value is above high-high limit

HIGH

BOOLEAN

Measured value is between high and high-high limit

NORMAL

BOOLEAN

Measured value is between high and low limit

LOW

BOOLEAN

Measured value is between low and low-low limit

LOWLOW

BOOLEAN

Measured value is below low-low limit

Disturbance report DRPRDRE

857
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Function description

15.7.1

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Analog input signals

A41RADR

Disturbance report

DRPRDRE

Disturbance report

A1RADR

Disturbance report

A4RADR

Disturbance report

B1RBDR

Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data
of all selected analog input and binary signals connected to the function block with
a, maximum of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:

Event list
Indications
Event recorder
Trip value recorder
Disturbance recorder
Fault locator

The Disturbance report function is characterized by great flexibility regarding


configuration, starting conditions, recording times, and large storage capacity.
A disturbance is defined as an activation of an input to the AxRADR or BxRBDR
function blocks, which are set to trigger the disturbance recorder. All signals from
start of pre-fault time to the end of post-fault time will be included in the recording.
Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ringbuffer. The local HMI is used to get information about the recordings. The
disturbance report files may be uploaded to PCM600 for further analysis using the
disturbance handling tool.

15.7.2

Principle of operation
Disturbance report DRPRDRE is a common name for several functions to supply
the operator, analysis engineer, and so on, with sufficient information about events
in the system.
The functions included in the disturbance report are:

858
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Event list (EL)


Indications (IND)
Event recorder (ER)
Trip value recorder(TVR)
Disturbance recorder (DR)

Figure 471 shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.
Disturbance Report

A1-4RADR

A4RADR

DRPRDRE

FL

Analog signals
Trip value rec

B1-6RBDR

Binary signals

Fault locator

Disturbance
recorder

B6RBDR
Event list
Event recorder
Indications

IEC09000336-2-en.vsd
IEC09000336 V2 EN

Figure 471:

Disturbance report functions and related function blocks

The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile
flash memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.

859
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Disturbance report

Record no. N

General dist.
information

Record no. N+1

Trip
values

Indications

Record no. N+100

Event
recordings

Disturbance
recording

Fault locator

Event list

en05000125.vsd
IEC05000125 V1 EN

Figure 472:

Disturbance report structure

Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded


when the memory is full, the oldest disturbance report is overwritten by the new
one. The total recording capacity for the disturbance recorder is depending of
sampling frequency, number of analog and binary channels and recording time.
Figure 473 shows the number of recordings versus the total recording time tested
for a typical configuration, that is, in a 50 Hz system it is possible to record 100
where the average recording time is 3.4 seconds. The memory limit does not affect
the rest of the disturbance report (Event list (EL), Event recorder (ER), Indications
(IND) and Trip value recorder (TVR)).

Number of recordings
100

3,4 s
20 analog
96 binary

3,4 s

80

40 analog
96 binary

60

6,3 s

6,3 s
50 Hz

6,3 s

40

60 Hz

Total recording time


250

300

350

400 s
en05000488.vsd

IEC05000488 V1 EN

Figure 473:

Example of number of recordings versus the total recording time

860
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

The maximum number of recordings depend on each recordings


total recording time. Long recording time will reduce the number of
recordings to less than 100.

The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.

Disturbance information

Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP
or MMS (over 61850) client. The PC can be connected to the IED front, rear or
remotely via the station bus (Ethernet ports).

Indications (IND)

Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged), see section "Indications" for more detailed
information.

Event recorder (ER)

The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see section "Event recorder" for more detailed information.

Event list (EL)

The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see section "Event list" for more detailed information.

Trip value recorder (TVR)

The recorded trip values include phasors of selected analog signals before the fault
and during the fault, see section "Trip value recorder" for more detailed information.

Disturbance recorder (DR)

Disturbance recorder records analog and binary signal data before, during and after
the fault, see section "Disturbance recorder" for more detailed information.

Fault locator (FL)

The fault location function calculates the distance to fault, see section "Fault
locator LMBRFLO" for more detailed information.

Time tagging

The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report
861
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Recording times

Disturbance report DRPRDRE records information about a disturbance during a


settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.
The total recording time, tRecording, of a recorded disturbance is:
PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on
which criterion stops the current disturbance recording

tRecording =

Trig point
TimeLimit
PreFaultRecT

PostFaultRecT

3
en05000487.vsd

IEC05000487 V1 EN

Figure 474:

The recording times definition

PreFaultRecT, 1

Pre-fault or pre-trigger recording time. The time before the fault including the
operate time of the trigger. Use the setting PreFaultRecT to set this time.

tFault, 2

Fault time of the recording. The fault time cannot be set. It continues as long as
any valid trigger condition, binary or analog, persists (unless limited by TimeLimit
the limit time).

PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit

Limit time. The maximum allowed recording time after the disturbance recording
was triggered. The limit time is used to eliminate the consequences of a trigger
that does not reset within a reasonable time interval. It limits the maximum
recording time of a recording and prevents subsequent overwriting of already
stored disturbances. Use the setting TimeLimit to set this time.

Analog signals

Up to 40 analog signals can be selected for recording by the Disturbance recorder


and triggering of the Disturbance report function. Out of these 40, 30 are reserved
for external analog signals from analog input modules (TRM) and line data
communication module (LDCM) via preprocessing function blocks (SMAI) and
summation block (3PHSUM). The last 10 channels may be connected to internally
calculated analog signals available as function block output signals (mA input
signals, phase differential currents, bias currents and so on).

862
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

A1RADR

SMAI
External
analogue
signals

Block
^GRP2L1

AI3P
AI1

^GRP2L2
^GRP2L3

AI2
AI3

INPUT2

^GRP2N
Type

AI4
AIN

INPUT4

A2RADR
INPUT1

A3RADR

INPUT3
INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32

Internal analogue signals

INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
IEC10000029-1-en.vsd

IEC10000029 V1 EN

Figure 475:

Analog input function blocks

The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used).SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.

863
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

If Operation = Off, no waveform (samples) will be recorded and reported in graph.


However, Trip value, pre-fault and fault value will be recorded and reported. The
input channel can still be used to trig the disturbance recorder.
If Operation = On, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.

Binary signals

Up to 96 binary signals can be selected to be handled by disturbance report. The


signals can be selected from internal logical and binary input signals. A binary
signal is selected to be recorded when:

the corresponding function block is included in the configuration


the signal is connected to the input of the function block

Each of the 96 signals can be selected as a trigger of the disturbance report


(Operation = Off). A binary signal can be selected to activate the red LED on the
local HMI (SetLED = On/Off).
The selected signals are presented in the event recorder, event list and the
disturbance recording. But they affect the whole disturbance report when they are
used as triggers. The indications are also selected from these 96 signals with local
HMI IndicationMask=Show/Hide.

Trigger signals

The trigger conditions affect the entire disturbance report, except the event list,
which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition
is fulfilled, there is no disturbance report, no indications, and so on. This implies
the importance of choosing the right signals as trigger conditions.
A trigger can be of type:

Manual trigger
Binary-signal trigger
Analog-signal trigger (over/under function)

Manual trigger

A disturbance report can be manually triggered from the local HMI, PCM600 or
via station bus (IEC 61850). When the trigger is activated, the manual trigger
signal is generated. This feature is especially useful for testing. Refer to the
operator's manual for procedure.

Binary-signal trigger

Any binary signal state (logic one or a logic zero) can be selected to generate a
trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to

864
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

generate a trigger from a logic zero, the selected signal will not be listed in the
indications list of the disturbance report.

Analog-signal trigger

All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the
average value is above the threshold level for an overvoltage or overcurrent trigger,
this trigger is indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.
This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in
the range of one cycle, 20 ms for a 50 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.

Post Retrigger

Disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering
(PostRetrig = On) during the post-fault time. In this case a new, complete
recording will start and, during a period, run in parallel with the initial recording.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be fetched.
Disturbance report function can handle maximum 3 simultaneous disturbance
recordings.

15.7.3

Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC05000406-3-en.vsd
IEC05000406 V3 EN

Figure 476:

DRPRDRE function block

865
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

A1RADR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
IEC05000430-3-en.vsd
IEC05000430 V3 EN

Figure 477:

A1RADR function block

A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC05000431-3-en.vsd
IEC05000431 V3 EN

Figure 478:

A4RADR function block, derived analog inputs

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432-3-en.vsd
IEC05000432 V3 EN

Figure 479:

B1RBDR function block, binary inputs, example for B1RBDR B6RBDR

866
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

15.7.4

Input and output signals


Table 582:
Name

DRPRDRE Output signals


Type

Description

DRPOFF

BOOLEAN

Disturbance report function turned off

RECSTART

BOOLEAN

Disturbance recording started

RECMADE

BOOLEAN

Disturbance recording made

CLEARED

BOOLEAN

All disturbances in the disturbance report cleared

MEMUSED

BOOLEAN

More than 80% of memory used

Table 583:
Name

A1RADR Input signals


Type

Default

Description

INPUT1

GROUP
SIGNAL

Group signal for input 1

INPUT2

GROUP
SIGNAL

Group signal for input 2

INPUT3

GROUP
SIGNAL

Group signal for input 3

INPUT4

GROUP
SIGNAL

Group signal for input 4

INPUT5

GROUP
SIGNAL

Group signal for input 5

INPUT6

GROUP
SIGNAL

Group signal for input 6

INPUT7

GROUP
SIGNAL

Group signal for input 7

INPUT8

GROUP
SIGNAL

Group signal for input 8

INPUT9

GROUP
SIGNAL

Group signal for input 9

INPUT10

GROUP
SIGNAL

Group signal for input 10

Table 584:
Name

A4RADR Input signals


Type

Default

Description

INPUT31

REAL

Analogue channel 31

INPUT32

REAL

Analogue channel 32

INPUT33

REAL

Analogue channel 33

INPUT34

REAL

Analogue channel 34

INPUT35

REAL

Analogue channel 35

INPUT36

REAL

Analogue channel 36

INPUT37

REAL

Analogue channel 37

Table continues on next page

867
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Type

Analogue channel 38

INPUT39

REAL

Analogue channel 39

INPUT40

REAL

Analogue channel 40

B1RBDR Input signals

Name

Table 586:
Name

Description

REAL

Table 585:

15.7.5

Default

INPUT38

Type

Default

Description

INPUT1

BOOLEAN

Binary channel 1

INPUT2

BOOLEAN

Binary channel 2

INPUT3

BOOLEAN

Binary channel 3

INPUT4

BOOLEAN

Binary channel 4

INPUT5

BOOLEAN

Binary channel 5

INPUT6

BOOLEAN

Binary channel 6

INPUT7

BOOLEAN

Binary channel 7

INPUT8

BOOLEAN

Binary channel 8

INPUT9

BOOLEAN

Binary channel 9

INPUT10

BOOLEAN

Binary channel 10

INPUT11

BOOLEAN

Binary channel 11

INPUT12

BOOLEAN

Binary channel 12

INPUT13

BOOLEAN

Binary channel 13

INPUT14

BOOLEAN

Binary channel 14

INPUT15

BOOLEAN

Binary channel 15

INPUT16

BOOLEAN

Binary channel 16

Setting parameters
DRPRDRE Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

PreFaultRecT

0.05 - 9.90

0.01

0.10

Pre-fault recording time

PostFaultRecT

0.1 - 10.0

0.1

0.5

Post-fault recording time

TimeLimit

0.5 - 10.0

0.1

1.0

Fault recording time limit

PostRetrig

Off
On

Off

Post-fault retrig enabled (On) or not (Off)

ZeroAngleRef

1 - 30

Ch

Reference channel (voltage), phasors,


frequency measurement

OpModeTest

Off
On

Off

Operation mode during test mode

868
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Table 587:

A1RADR Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation01

Off
On

Off

Operation On/Off

NomValue01

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 1

UnderTrigOp01

Off
On

Off

Use under level trig for analogue cha 1


(on) or not (off)

UnderTrigLe01

0 - 200

50

Under trigger level for analogue cha 1 in


% of signal

OverTrigOp01

Off
On

Off

Use over level trig for analogue cha 1


(on) or not (off)

OverTrigLe01

0 - 5000

200

Over trigger level for analogue cha 1 in


% of signal

Operation02

Off
On

Off

Operation On/Off

NomValue02

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 2

UnderTrigOp02

Off
On

Off

Use under level trig for analogue cha 2


(on) or not (off)

UnderTrigLe02

0 - 200

50

Under trigger level for analogue cha 2 in


% of signal

OverTrigOp02

Off
On

Off

Use over level trig for analogue cha 2


(on) or not (off)

OverTrigLe02

0 - 5000

200

Over trigger level for analogue cha 2 in


% of signal

Operation03

Off
On

Off

Operation On/Off

NomValue03

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 3

UnderTrigOp03

Off
On

Off

Use under level trig for analogue cha 3


(on) or not (off)

UnderTrigLe03

0 - 200

50

Under trigger level for analogue cha 3 in


% of signal

OverTrigOp03

Off
On

Off

Use over level trig for analogue cha 3


(on) or not (off)

OverTrigLe03

0 - 5000

200

Overtrigger level for analogue cha 3 in %


of signal

Operation04

Off
On

Off

Operation On/Off

NomValue04

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 4

UnderTrigOp04

Off
On

Off

Use under level trig for analogue cha 4


(on) or not (off)

UnderTrigLe04

0 - 200

50

Under trigger level for analogue cha 4 in


% of signal

OverTrigOp04

Off
On

Off

Use over level trig for analogue cha 4


(on) or not (off)

OverTrigLe04

0 - 5000

200

Over trigger level for analogue cha 4 in


% of signal

Operation05

Off
On

Off

Operation On/Off

Table continues on next page

869
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

NomValue05

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 5

UnderTrigOp05

Off
On

Off

Use under level trig for analogue cha 5


(on) or not (off)

UnderTrigLe05

0 - 200

50

Under trigger level for analogue cha 5 in


% of signal

OverTrigOp05

Off
On

Off

Use over level trig for analogue cha 5


(on) or not (off)

OverTrigLe05

0 - 5000

200

Over trigger level for analogue cha 5 in


% of signal

Operation06

Off
On

Off

Operation On/Off

NomValue06

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 6

UnderTrigOp06

Off
On

Off

Use under level trig for analogue cha 6


(on) or not (off)

UnderTrigLe06

0 - 200

50

Under trigger level for analogue cha 6 in


% of signal

OverTrigOp06

Off
On

Off

Use over level trig for analogue cha 6


(on) or not (off)

OverTrigLe06

0 - 5000

200

Over trigger level for analogue cha 6 in


% of signal

Operation07

Off
On

Off

Operation On/Off

NomValue07

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 7

UnderTrigOp07

Off
On

Off

Use under level trig for analogue cha 7


(on) or not (off)

UnderTrigLe07

0 - 200

50

Under trigger level for analogue cha 7 in


% of signal

OverTrigOp07

Off
On

Off

Use over level trig for analogue cha 7


(on) or not (off)

OverTrigLe07

0 - 5000

200

Over trigger level for analogue cha 7 in


% of signal

Operation08

Off
On

Off

Operation On/Off

NomValue08

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 8

UnderTrigOp08

Off
On

Off

Use under level trig for analogue cha 8


(on) or not (off)

UnderTrigLe08

0 - 200

50

Under trigger level for analogue cha 8 in


% of signal

OverTrigOp08

Off
On

Off

Use over level trig for analogue cha 8


(on) or not (off)

OverTrigLe08

0 - 5000

200

Over trigger level for analogue cha 8 in


% of signal

Operation09

Off
On

Off

Operation On/Off

NomValue09

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 9

UnderTrigOp09

Off
On

Off

Use under level trig for analogue cha 9


(on) or not (off)

Table continues on next page

870
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

UnderTrigLe09

0 - 200

50

Under trigger level for analogue cha 9 in


% of signal

OverTrigOp09

Off
On

Off

Use over level trig for analogue cha 9


(on) or not (off)

OverTrigLe09

0 - 5000

200

Over trigger level for analogue cha 9 in


% of signal

Operation10

Off
On

Off

Operation On/Off

NomValue10

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 10

UnderTrigOp10

Off
On

Off

Use under level trig for analogue cha 10


(on) or not (off)

UnderTrigLe10

0 - 200

50

Under trigger level for analogue cha 10


in % of signal

OverTrigOp10

Off
On

Off

Use over level trig for analogue cha 10


(on) or not (off)

OverTrigLe10

0 - 5000

200

Over trigger level for analogue cha 10 in


% of signal

Table 588:

A4RADR Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation31

Off
On

Off

Operation On/off

NomValue31

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 31

UnderTrigOp31

Off
On

Off

Use under level trig for analogue cha 31


(on) or not (off)

UnderTrigLe31

0 - 200

50

Under trigger level for analogue cha 31


in % of signal

OverTrigOp31

Off
On

Off

Use over level trig for analogue cha 31


(on) or not (off)

OverTrigLe31

0 - 5000

200

Over trigger level for analogue cha 31 in


% of signal

Operation32

Off
On

Off

Operation On/off

NomValue32

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 32

UnderTrigOp32

Off
On

Off

Use under level trig for analogue cha 32


(on) or not (off)

UnderTrigLe32

0 - 200

50

Under trigger level for analogue cha 32


in % of signal

OverTrigOp32

Off
On

Off

Use over level trig for analogue cha 32


(on) or not (off)

OverTrigLe32

0 - 5000

200

Over trigger level for analogue cha 32 in


% of signal

Operation33

Off
On

Off

Operation On/off

NomValue33

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 33

UnderTrigOp33

Off
On

Off

Use under level trig for analogue cha 33


(on) or not (off)

Table continues on next page


871
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

UnderTrigLe33

0 - 200

50

Under trigger level for analogue cha 33


in % of signal

OverTrigOp33

Off
On

Off

Use over level trig for analogue cha 33


(on) or not (off)

OverTrigLe33

0 - 5000

200

Overtrigger level for analogue cha 33 in


% of signal

Operation34

Off
On

Off

Operation On/off

NomValue34

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 34

UnderTrigOp34

Off
On

Off

Use under level trig for analogue cha 34


(on) or not (off)

UnderTrigLe34

0 - 200

50

Under trigger level for analogue cha 34


in % of signal

OverTrigOp34

Off
On

Off

Use over level trig for analogue cha 34


(on) or not (off)

OverTrigLe34

0 - 5000

200

Over trigger level for analogue cha 34 in


% of signal

Operation35

Off
On

Off

Operation On/off

NomValue35

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 35

UnderTrigOp35

Off
On

Off

Use under level trig for analogue cha 35


(on) or not (off)

UnderTrigLe35

0 - 200

50

Under trigger level for analogue cha 35


in % of signal

OverTrigOp35

Off
On

Off

Use over level trig for analogue cha 35


(on) or not (off)

OverTrigLe35

0 - 5000

200

Over trigger level for analogue cha 35 in


% of signal

Operation36

Off
On

Off

Operation On/off

NomValue36

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 36

UnderTrigOp36

Off
On

Off

Use under level trig for analogue cha 36


(on) or not (off)

UnderTrigLe36

0 - 200

50

Under trigger level for analogue cha 36


in % of signal

OverTrigOp36

Off
On

Off

Use over level trig for analogue cha 36


(on) or not (off)

OverTrigLe36

0 - 5000

200

Over trigger level for analogue cha 36 in


% of signal

Operation37

Off
On

Off

Operation On/off

NomValue37

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 37

UnderTrigOp37

Off
On

Off

Use under level trig for analogue cha 37


(on) or not (off)

UnderTrigLe37

0 - 200

50

Under trigger level for analogue cha 37


in % of signal

OverTrigOp37

Off
On

Off

Use over level trig for analogue cha 37


(on) or not (off)

Table continues on next page


872
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

OverTrigLe37

0 - 5000

200

Over trigger level for analogue cha 37 in


% of signal

Operation38

Off
On

Off

Operation On/off

NomValue38

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 38

UnderTrigOp38

Off
On

Off

Use under level trig for analogue cha 38


(on) or not (off)

UnderTrigLe38

0 - 200

50

Under trigger level for analogue cha 38


in % of signal

OverTrigOp38

Off
On

Off

Use over level trig for analogue cha 38


(on) or not (off)

OverTrigLe38

0 - 5000

200

Over trigger level for analogue cha 38 in


% of signal

Operation39

Off
On

Off

Operation On/off

NomValue39

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 39

UnderTrigOp39

Off
On

Off

Use under level trig for analogue cha 39


(on) or not (off)

UnderTrigLe39

0 - 200

50

Under trigger level for analogue cha 39


in % of signal

OverTrigOp39

Off
On

Off

Use over level trig for analogue cha 39


(on) or not (off)

OverTrigLe39

0 - 5000

200

Over trigger level for analogue cha 39 in


% of signal

Operation40

Off
On

Off

Operation On/off

NomValue40

0.0 - 999999.9

0.1

0.0

Nominal value for analogue channel 40

UnderTrigOp40

Off
On

Off

Use under level trig for analogue cha 40


(on) or not (off)

UnderTrigLe40

0 - 200

50

Under trigger level for analogue cha 40


in % of signal

OverTrigOp40

Off
On

Off

Use over level trig for analogue cha 40


(on) or not (off)

OverTrigLe40

0 - 5000

200

Over trigger level for analogue cha 40 in


% of signal

Table 589:

B1RBDR Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation01

Off
On

Off

Trigger operation On/Off

TrigLevel01

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 1

IndicationMa01

Hide
Show

Hide

Indication mask for binary channel 1

SetLED01

Off
On

Off

Set red-LED on HMI for binary channel 1

Table continues on next page

873
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

Operation02

Off
On

Off

Trigger operation On/Off

TrigLevel02

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 2

IndicationMa02

Hide
Show

Hide

Indication mask for binary channel 2

SetLED02

Off
On

Off

Set red-LED on HMI for binary channel 2

Operation03

Off
On

Off

Trigger operation On/Off

TrigLevel03

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 3

IndicationMa03

Hide
Show

Hide

Indication mask for binary channel 3

SetLED03

Off
On

Off

Set red-LED on HMI for binary channel 3

Operation04

Off
On

Off

Trigger operation On/Off

TrigLevel04

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 4

IndicationMa04

Hide
Show

Hide

Indication mask for binary channel 4

SetLED04

Off
On

Off

Set red-LED on HMI for binary channel 4

Operation05

Off
On

Off

Trigger operation On/Off

TrigLevel05

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 5

IndicationMa05

Hide
Show

Hide

Indication mask for binary channel 5

SetLED05

Off
On

Off

Set red-LED on HMI for binary channel 5

Operation06

Off
On

Off

Trigger operation On/Off

TrigLevel06

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 6

IndicationMa06

Hide
Show

Hide

Indication mask for binary channel 6

SetLED06

Off
On

Off

Set red-LED on HMI for binary channel 6

Operation07

Off
On

Off

Trigger operation On/Off

TrigLevel07

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 7

IndicationMa07

Hide
Show

Hide

Indication mask for binary channel 7

SetLED07

Off
On

Off

Set red-LED on HMI for binary channel 7

Table continues on next page

874
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

Operation08

Off
On

Off

Trigger operation On/Off

TrigLevel08

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 8

IndicationMa08

Hide
Show

Hide

Indication mask for binary channel 8

SetLED08

Off
On

Off

Set red-LED on HMI for binary channel 8

Operation09

Off
On

Off

Trigger operation On/Off

TrigLevel09

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 9

IndicationMa09

Hide
Show

Hide

Indication mask for binary channel 9

SetLED09

Off
On

Off

Set red-LED on HMI for binary channel 9

Operation10

Off
On

Off

Trigger operation On/Off

TrigLevel10

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 10

IndicationMa10

Hide
Show

Hide

Indication mask for binary channel 10

SetLED10

Off
On

Off

Set red-LED on HMI for binary channel 10

Operation11

Off
On

Off

Trigger operation On/Off

TrigLevel11

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 11

IndicationMa11

Hide
Show

Hide

Indication mask for binary channel 11

SetLED11

Off
On

Off

Set red-LED on HMI for binary channel 11

Operation12

Off
On

Off

Trigger operation On/Off

TrigLevel12

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 12

IndicationMa12

Hide
Show

Hide

Indication mask for binary channel 12

SetLED12

Off
On

Off

Set red-LED on HMI for binary input 12

Operation13

Off
On

Off

Trigger operation On/Off

TrigLevel13

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 13

IndicationMa13

Hide
Show

Hide

Indication mask for binary channel 13

SetLED13

Off
On

Off

Set red-LED on HMI for binary channel 13

Table continues on next page

875
Technical reference manual

Section 15
Monitoring
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

Operation14

Off
On

Off

Trigger operation On/Off

TrigLevel14

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 14

IndicationMa14

Hide
Show

Hide

Indication mask for binary channel 14

SetLED14

Off
On

Off

Set red-LED on HMI for binary channel 14

Operation15

Off
On

Off

Trigger operation On/Off

TrigLevel15

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 15

IndicationMa15

Hide
Show

Hide

Indication mask for binary channel 15

SetLED15

Off
On

Off

Set red-LED on HMI for binary channel 15

Operation16

Off
On

Off

Trigger operation On/Off

TrigLevel16

Trig on 0
Trig on 1

Trig on 1

Trig on positiv (1) or negative (0) slope


for binary inp 16

IndicationMa16

Hide
Show

Hide

Indication mask for binary channel 16

SetLED16

Off
On

Off

Set red-LED on HMI for binary channel 16

FUNT1

0 - 255

FunT

Function type for binary channel 1 (IEC


-60870-5-103)

FUNT2

0 - 255

FunT

Function type for binary channel 2 (IEC


-60870-5-103)

FUNT3

0 - 255

FunT

Function type for binary channel 3 (IEC


-60870-5-103)

FUNT4

0 - 255

FunT

Function type for binary channel 4 (IEC


-60870-5-103)

FUNT5

0 - 255

FunT

Function type for binary channel 5 (IEC


-60870-5-103)

FUNT6

0 - 255

FunT

Function type for binary channel 6 (IEC


-60870-5-103)

FUNT7

0 - 255

FunT

Function type for binary channel 7 (IEC


-60870-5-103)

FUNT8

0 - 255

FunT

Function type for binary channel 8 (IEC


-60870-5-103)

FUNT9

0 - 255

FunT

Function type for binary channel 9 (IEC


-60870-5-103)

FUNT10

0 - 255

FunT

Function type for binary channel 10 (IEC


-60870-5-103)

FUNT11

0 - 255

FunT

Function type for binary channel 11 (IEC


-60870-5-103)

FUNT12

0 - 255

FunT

Function type for binary channel 12 (IEC


-60870-5-103)

Table continues on next page

876
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

FUNT13

0 - 255

FunT

Function type for binary channel 13 (IEC


-60870-5-103)

FUNT14

0 - 255

FunT

Function type for binary channel 14 (IEC


-60870-5-103)

FUNT15

0 - 255

FunT

Function type for binary channel 15 (IEC


-60870-5-103)

FUNT16

0 - 255

FunT

Function type for binary channel 16 (IEC


-60870-5-103)

INFNO1

0 - 255

InfNo

Information number for binary channel 1


(IEC -60870-5-103)

INFNO2

0 - 255

InfNo

Information number for binary channel 2


(IEC -60870-5-103)

INFNO3

0 - 255

InfNo

Information number for binary channel 3


(IEC -60870-5-103)

INFNO4

0 - 255

InfNo

Information number for binary channel 4


(IEC -60870-5-103)

INFNO5

0 - 255

InfNo

Information number for binary channel 5


(IEC -60870-5-103)

INFNO6

0 - 255

InfNo

Information number for binary channel 6


(IEC -60870-5-103)

INFNO7

0 - 255

InfNo

Information number for binary channel 7


(IEC -60870-5-103)

INFNO8

0 - 255

InfNo

Information number for binary channel 8


(IEC -60870-5-103)

INFNO9

0 - 255

InfNo

Information number for binary channel 9


(IEC -60870-5-103)

INFNO10

0 - 255

InfNo

Information number for binary channel


10 (IEC -60870-5-103)

INFNO11

0 - 255

InfNo

Information number for binary channel


11 (IEC -60870-5-103)

INFNO12

0 - 255

InfNo

Information number for binary channel


12 (IEC -60870-5-103)

INFNO13

0 - 255

InfNo

Information number for binary channel


13 (IEC -60870-5-103)

INFNO14

0 - 255

InfNo

Information number for binary channel


14 (IEC -60870-5-103)

INFNO15

0 - 255

InfNo

Information number for binary channel


15 (IEC -60870-5-103)

INFNO16

0 - 255

InfNo

Information number for binary channel


16 (IEC -60870-5-103)

877
Technical reference manual

Section 15
Monitoring
15.7.6

1MRK 505 222-UEN B

Technical data
Table 590:

DRPRDRE technical data

Function

Range or value

Accuracy

Pre-fault time

(0.059.90) s

Post-fault time

(0.110.0) s

Limit time

(0.510.0) s

Maximum number of recordings

100, first in - first out

Time tagging resolution

1 ms

See table 28

Maximum number of analog inputs

30 + 10 (external + internally
derived)

Maximum number of binary inputs

96

Maximum number of phasors in the


Trip Value recorder per recording

30

Maximum number of indications in a


disturbance report

96

Maximum number of events in the


Event recording per recording

150

Maximum number of events in the


Event list

1000, first in - first out

Maximum total recording time (3.4 s


recording time and maximum number
of channels, typical value)

340 seconds (100 recordings)


at 50 Hz, 280 seconds (80
recordings) at 60 Hz

Sampling rate

1 kHz at 50 Hz
1.2 kHz at 60 Hz

Recording bandwidth

(5-300) Hz

15.8

Event list

15.8.1

Introduction
Continuous event-logging is useful for monitoring the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the Disturbance report
function. The list may contain up to 1000 time-tagged events stored in a ring-buffer.

15.8.2

Principle of operation
When a binary signal, connected to the disturbance report function, changes status,
the event list function stores input name, status and time in the event list in
chronological order. The list can contain up to 1000 events from both internal logic
signals and binary input channels. If the list is full, the oldest event is overwritten
when a new event arrives.

878
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

The list can be configured to show oldest or newest events first with a setting on
the local HMI.
The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.
The name of the binary input signal that appears in the event recording is the userdefined name assigned when the IED is configured. The same name is used in the
disturbance recorder function (DR), indications (IND)and the event recorder
function (ER).
The event list is stored and managed separate from the disturbance report
information (ER, DR, IND, TVR and FL).

15.8.3

Function block
The Event list has no function block of its own.It is included in the DRPRDRE
block and uses information from the BxRBDR block.

15.8.4

Input signals
The Event list logs the same binary input signals as configured for the Disturbance
report function.

15.8.5

Technical data
Table 591:

technical data

Function
Buffer capacity

Value
Maximum number of events in the list

1000

Resolution

1 ms

Accuracy

Depending on time
synchronizing

15.9

Indications

15.9.1

Introduction
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know, for example binary signals
that have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (trigged).

879
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.

15.9.2

Principle of operation
The LED indications display this information:
Green LED:
Steady light

In Service

Flashing light

Internal fail

Dark

No power supply

Yellow LED:
Steady light

A disturbance report is triggered

Flashing light

The IED is in test mode or in configuration mode

Red LED:
Steady light

Trigged on binary signal N with SetLEDN=On

Indication list:
The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:

the signal must be connected to binary input(DRB1-6)


the DRPparameter Operation must be set On
the DRP must be trigged (binary or analog)

Indications are selected with the indication mask (IndicationMask) when


configuring the binary inputs.
The name of the binary input signal that appears in the Indication function is the userdefined name assigned at configuration of the IED. The same name is used in
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).

880
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

15.9.3

Function block
The Indications function has no function block of its own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

15.9.4

Input signals
The Indications function may log the same binary input signals as the Disturbance
report function.

15.9.5

Technical data
Table 592:

technical data

Function
Buffer capacity

15.10

Event recorder

15.10.1

Introduction

Value
Maximum number of indications
presented for single disturbance

96

Maximum number of recorded


disturbances

100

Quick, complete and reliable information about disturbances in the primary and/or
in the secondary system is vital, for example, time-tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example functional analysis).
The event recorder logs all selected binary input signals connected to the
Disturbance report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
The event recording information is an integrated part of the disturbance record
(Comtrade file).

15.10.2

Principle of operation
When one of the trig conditions for the disturbance report is activated, the event
recorder logs every status change in the 96 selected binary signals. The events can
be generated by both internal logical signals and binary input channels. The
internal signals are time-tagged in the main processor module, while the binary
input channels are time-tagged directly in each I/O module. The events are
collected during the total recording time (pre-, post-fault and limit time), and are
stored in the disturbance report flash memory at the end of each recording.

881
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

In case of overlapping recordings, due to PostRetrig = On and a new trig signal


appears during post-fault time, events will be saved in both recording files.
The name of the binary input signal that appears in the event recording is the userdefined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder
function(ER).
The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the local HMI or PCM600.
Events can not be read from the IED if more than one user is
accessing the IED simultaneously.

15.10.3

Function block
The Event recorder has no function block of its own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

15.10.4

Input signals
The Event recorder function logs the same binary input signals as the Disturbance
report function.

15.10.5

Technical data
Table 593:

technical data

Function
Buffer capacity

Value
Maximum number of events in disturbance
report

150

Maximum number of disturbance reports

100

Resolution

1 ms

Accuracy

Depending on time
synchronizing

15.11

Trip value recorder

15.11.1

Introduction
Information about the pre-fault and fault values for currents and voltages are vital
for the disturbance evaluation.

882
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase
angle before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the
IED.
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).

15.11.2

Principle of operation
Trip value recorder (TVR)calculates and presents both fault and pre-fault
amplitudes as well as the phase angles of all the selected analog input signals. The
parameter ZeroAngleRef points out which input signal is used as the angle
reference. The calculated data is input information to the fault locator (FL).
When the disturbance report function is triggered the sample for the fault
interception is searched for, by checking the non-periodic changes in the analog
input signals. The channel search order is consecutive, starting with the analog
input with the lowest number.
When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated
using the Recursive Least Squares (RLS) method. The calculation starts a few
samples after the fault sample and uses samples during 1/2 - 2 cycles depending on
the shape of the signals.
If no starting point is found in the recording, the disturbance report trig sample is
used as the start sample for the Fourier estimation. The estimation uses samples
during one cycle before the trig sample. In this case the calculated values are used
both as pre-fault and fault values.
The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function (DR).
The trip value record is stored as a part of the disturbance report information (ER,
DR, IND, TVR and fault locator) and managed in via the local HMI or PCM600.

15.11.3

Function block
The Trip value recorder has no function block of its own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.

883
Technical reference manual

Section 15
Monitoring
15.11.4

1MRK 505 222-UEN B

Input signals
The trip value recorder function uses analog input signals connected to A1RADR
to A3RADR (not A4RADR).

15.11.5

Technical data
Table 594:

technical data

Function
Buffer capacity

Value
Maximum number of analog inputs

30

Maximum number of disturbance reports

100

15.12

Disturbance recorder

15.12.1

Introduction
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system
behavior and related primary and secondary equipment during and after a
disturbance. Recorded information is used for different purposes in the short
perspective (for example corrective actions) and long perspective (for example
functional analysis).
The Disturbance recorder acquires sampled data from selected analog- and binary
signals connected to the Disturbance report function (maximum 40 analog and 96
binary signals). The binary signals available are the same as for the event recorder
function.
The function is characterized by great flexibility and is not dependent on the
operation of protection functions. It can record disturbances not detected by
protection functions. Up to ten seconds of data before the trigger instant can be
saved in the disturbance file.
The disturbance recorder information for up to 100 disturbances are saved in the
IED and the local HMI is used to view the list of recordings.

15.12.2

Principle of operation
Disturbance recording (DR) is based on the acquisition of binary and analog
signals. The binary signals can be either true binary input signals or internal logical
signals generated by the functions in the IED. The analog signals to be recorded are
input channels from the Transformer Input Module (TRM), Line Differential
communication Module (LDCM) through the Signal Matrix Analog Input (SMAI)
and possible summation (Sum3Ph) function blocks and some internally derived
analog signals.For details, refer to section "Disturbance report DRPRDRE".

884
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

Disturbance recorder collects analog values and binary signals continuously, in a


cyclic buffer. The pre-fault buffer operates according to the FIFO principle; old
data will continuously be overwritten as new data arrives when the buffer is full.
The size of this buffer is determined by the set pre-fault recording time.
Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as
long as the fault condition prevails - plus a certain additional time. This is called
the post-fault time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common
for all functions within the disturbance report functionality.

15.12.2.1

Memory and storage


The maximum number of recordings depend on each recordings
total recording time. Long recording time will reduce the number of
recordings to less than 100.

The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
When a recording is completed, a post recording processing occurs.
This post-recording processing comprises:

Saving the data for analog channels with corresponding data for binary signals
Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
Compression of the data, which is performed without losing any data accuracy
Storing the compressed data in a non-volatile memory (flash memory)

The recorded disturbance is now ready for retrieval and evaluation.


The recording files comply with the Comtrade standard IEC 60255-24 and are
divided into three files; a header file (HDR), a configuration file (CFG) and a data
file (DAT).
The header file (optional in the standard) contains basic information about the
disturbance, that is, information from the Disturbance report sub-functions (ER,
885
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

TVR and FL). The Disturbance handling tool use this information and present the
recording in a user-friendly way.
General:

Station name, object name and unit name


Date and time for the trig of the disturbance
Record number
Sampling rate
Time synchronization source
Recording times
Activated trig signal
Active setting group

Analog:

Signal names for selected analog channels


Information e.g. trig on analog inputs
Primary and secondary instrument transformer rating
Over- or Undertrig: level and operation
Over- or Undertrig status at time of trig
CT direction

Binary:

Signal names
Status of binary input signals

The configuration file is a mandatory file containing information needed to


interpret the data file. For example sampling rate, number of channels, system
frequency, channel info etc.
The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.

15.12.2.2

IEC 60870-5-103
The communication protocol IEC 60870-5-103 may be used to poll disturbance
recordings from the IED to a master (station HSI). The standard describes how to
handle 8 disturbance recordings, 8 analog channels (4 currents and 4 voltages)
using the public range and binary signals.
The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).
To be able to report 40 analog channels from the IED using IEC 60870-5-103 the
first 8 channels are placed in the public range and the next 32 are placed in the

886
Technical reference manual

Section 15
Monitoring

1MRK 505 222-UEN B

private range. To comply the standard the first 8 must be configured according to
table 595.
Table 595:
Signal

Configuration of analog channels


Disturbance recorder

IL1

A1RADR

INPUT1

IL2

A1RADR

INPUT2

IL3

A1RADR

INPUT3

IN

A1RADR

INPUT4

UL1

A1RADR

INPUT5

UL2

A1RADR

INPUT6

UL3

A1RADR

INPUT7

UN

A1RADR

INPUT8

The binary signals connected to BxRBDR are reported by polling. The function
blocks include function type and information number.

15.12.3

Function block
The Disturbance recorder has no function block of its own. It is included in the
DRPRDRE, AxRADR and BxRBDR block.

15.12.4

Input and output signals


For signals see section, in Disturbance report, "Input and output signals".

15.12.5

Setting parameters
For Setting parameters see section "Disturbance report DRPRDRE".

15.12.6

Technical data
Table 596:

technical data

Function
Buffer capacity

Value
Maximum number of analog inputs

40

Maximum number of binary inputs

96

Maximum number of disturbance reports

100

Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)

340 seconds (100


recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz

887
Technical reference manual

888

Section 16
Metering

1MRK 505 222-UEN B

Section 16

Metering

About this chapter


This chapter describes among others, Pulse counter logic which is a function used
to meter externally generated binary pulses. The way the functions work, their
setting parameters, function blocks, input and output signals, and technical data are
included for each function.

16.1

Pulse-counter logic PCGGIO


Function description
Pulse-counter logic

IEC 61850
identification

IEC 60617
identification

PCGGIO

ANSI/IEEE C37.2
device number
-

S00947 V1 EN

16.1.1

Introduction
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then
read by the function. A scaled service value is available over the station bus. The
special Binary input module with enhanced pulse counting capabilities must be
ordered to achieve this functionality.

16.1.2

Principle of operation
The registration of pulses is done for positive transitions (0->1) on one of the 16
binary input channels located on the Binary Input Module (BIM). Pulse counter
values are sent to the station HMI with predefined cyclicity without reset.
The reporting time period can be set in the range from 1 second to 60 minutes and
is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by the LON General Interrogation
command (GI) or IEC 61850.

889
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

Pulse counter (PCGGIO) function in the IED supports unidirectional incremental


counters. That means only positive values are possible. The counter uses a 32 bit
format, that is, the reported value is a 32-bit, signed integer with a range
0...+2147483647. The counter is reset at initialization of the IED.
The reported value to station HMI over the station bus contains Identity, Scaled
Value (pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter
Quality consists of:

Invalid (board hardware error or configuration error)


Wrapped around
Blocked
Adjusted

The transmission of the counter value by SPA can be done as a service value, that
is, the value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can
be connected to an Event function block, be time tagged, and transmitted to the
station HMI. This time corresponds to the time when the value was frozen by the
function.
The pulse counter function requires a binary input card, BIMp, that
is specially adapted to the pulse counter function.
Figure 480 shows the pulse counter function block with connections of the inputs
and outputs.
SingleCmdFunc
OUTx
SingleCmdFunc
OUTx
I/O-module

Pulse
INPUT OUT
Pulse length >1s
Reset counter

PulseCounter
BLOCK
INVALID
RESTART
READ_VAL
BLOCKED
NEW_VAL
BI_PULSE
RS_CNT
NAME
SCAL_VAL

SMS settings
1.Operation = Off/On
2.tReporting = 0s...60min
3.Event Mask = No Events/Report Events
4.Scale = 1-90000

EVENT
INPUT1
INPUT2
INPUT3
INPUT4

IEC EVENT

Database
Pulse counter value:
0...2147483647
en05000744.vsd

IEC05000744 V1 EN

Figure 480:

Overview of the pulse counter function

890
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

The BLOCK and READ_VAL inputs can be connected to Single Command


blocks, which are intended to be controlled either from the station HMI or/and the
local HMI. As long as the BLOCK signal is set, the pulse counter is blocked. The
signal connected to READ_VAL performs one additional reading per positive
flank. The signal must be a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
The RS_CNT input is used for resetting the counter.
Each pulse counter function block has four binary output signals that can be
connected to an Event function block for event recording: INVALID, RESTART,
BLOCKED and NEW_VAL. The SCAL_VAL signal can be connected to the IEC
Event function block.
The INVALID signal is a steady signal and is set if the Binary Input Module,
where the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED startup, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked.
There are two reasons why the counter is blocked:

The BLOCK input is set, or


The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
The SCAL_VAL signal consists of scaled value (according to parameter Scale),
time and status information.

16.1.3

Function block
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT

INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC05000709-2-en.vsd

IEC05000709 V3 EN

Figure 481:

PCGGIO function block

891
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

16.1.4

Input and output signals


Table 597:

PCGGIO Input signals

Name

Type
BOOLEAN

Block of function

READ_VAL

BOOLEAN

Initiates an additional pulse counter reading

BI_PULSE

BOOLEAN

Connect binary input channel for metering

RS_CNT

BOOLEAN

Resets pulse counter value

PCGGIO Output signals

Name

Table 599:
Name

Description

BLOCK

Table 598:

16.1.5

Default

Type

Description

INVALID

BOOLEAN

The pulse counter value is invalid

RESTART

BOOLEAN

The reported value does not comprise a complete


integration cycle

BLOCKED

BOOLEAN

The pulse counter function is blocked

NEW_VAL

BOOLEAN

A new pulse counter value is generated

SCAL_VAL

REAL

Scaled value with time and status information

Setting parameters
PCGGIO Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

EventMask

NoEvents
ReportEvents

NoEvents

Report mask for analog events from


pulse counter

CountCriteria

Off
RisingEdge
Falling edge
OnChange

RisingEdge

Pulse counter criteria

Scale

1.000 - 90000.000

0.001

1.000

Scaling value for SCAL_VAL output to


unit per counted value

Quantity

Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy

Count

Measured quantity for SCAL_VAL output

tReporting

0 - 3600

60

Cycle time for reporting of counter value

892
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

16.1.6

Technical data
Table 600:

PCGGIO technical data

Function

16.2

Setting range

Input frequency

See Binary Input Module (BIM)

Cycle time for report of


counter value

(13600) s

Function for energy calculation and demand


handling ETPMMTR
Function description
Energy calculation and demand
handling

16.2.1

Accuracy

IEC 61850
identification
ETPMMTR

IEC 60617
identification

ANSI/IEEE C37.2
device number
-

Introduction
Outputs from the Measurements (CVMMXN) function can be used to calculate
energy consumption. Active as well as reactive values are calculated in import and
export direction. Values can be read or generated as pulses. Maximum demand
power values are also calculated by the function.

16.2.2

Principle of operation
The instantaneous output values of active and reactive power from the
Measurements (CVMMXN) function block are used and integrated over a selected
time tEnergy to measure the integrated energy. The energy values (in MWh and
MVarh) are available as output signals and also as pulsed output which can be
connected to a pulse counter. Outputs are available for forward as well as reverse
direction. The accumulated energy values can be reset from the local HMI reset
menu or with input signal RSTACC.
The maximum demand values for active and reactive power are calculated for the
set time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until
reset with input signal RSTDMD or from the local HMI reset menu.

893
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

CVMMXN

P_INST
Q_INST

ETPMMTR

P
Q

TRUE
FALSE
FALSE

STACC
RSTACC
RSTDMD

IEC09000106.vsd
IEC09000106 V1 EN

Figure 482:

16.2.3

Connection of Energy calculation and demand handling function


(ETPMMTR) to the Measurements function (CVMMXN)

Function block
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD

ACCST
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC07000120-2-en.vsd

IEC07000120 V2 EN

Figure 483:

16.2.4

ETPMMTR function block

Input and output signals


Table 601:
Name

ETPMMTR Input signals


Type

Default

Description

REAL

Measured active power

REAL

Measured reactive power

STACC

BOOLEAN

Start to accumulate energy values

RSTACC

BOOLEAN

Reset of accumulated enery reading

RSTDMD

BOOLEAN

Reset of maximum demand reading

Table 602:
Name

ETPMMTR Output signals


Type

Description

ACCST

BOOLEAN

Start of accumulating energy values.

EAFPULSE

BOOLEAN

Accumulated forward active energy pulse

EARPULSE

BOOLEAN

Accumulated reverse active energy pulse

Table continues on next page


894
Technical reference manual

Section 16
Metering

1MRK 505 222-UEN B

Name

16.2.5
Table 603:

Type

Description

ERFPULSE

BOOLEAN

Accumulated forward reactive energy pulse

ERRPULSE

BOOLEAN

Accumulated reverse reactive energy pulse

EAFALM

BOOLEAN

Alarm for active forward energy exceed limit in


set interval

EARALM

BOOLEAN

Alarm for active reverse energy exceed limit in


set interval

ERFALM

BOOLEAN

Alarm for reactive forward energy exceed limit in


set interval

ERRALM

BOOLEAN

Alarm for reactive reverse energy exceed limit in


set interval

EAFACC

REAL

Accumulated forward active energy value in Ws

EARACC

REAL

Accumulated reverse active energy value in Ws

ERFACC

REAL

Accumulated forward reactive energy value in


VArS

ERRACC

REAL

Accumulated reverse reactive energy value in


VArS

MAXPAFD

REAL

Maximum forward active power demand value for


set interval

MAXPARD

REAL

Maximum reverse active power demand value for


set interval

MAXPRFD

REAL

Maximum forward reactive power demand value


for set interval

MAXPRRD

REAL

Maximum reactive power demand value in


reverse direction

Setting parameters
ETPMMTR Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

StartAcc

Off
On

Off

Activate the accumulation of energy


values

tEnergy

1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes

1 Minute

Time interval for energy calculation

tEnergyOnPls

0.000 - 60.000

0.001

1.000

Energy accumulated pulse ON time in


secs

tEnergyOffPls

0.000 - 60.000

0.001

0.500

Energy accumulated pulse OFF time in


secs

EAFAccPlsQty

0.001 - 10000.000

MWh

0.001

100.000

Pulse quantity for active forward


accumulated energy value

Table continues on next page

895
Technical reference manual

Section 16
Metering
Name

1MRK 505 222-UEN B

Values (Range)

Unit

Step

Default

Description

EARAccPlsQty

0.001 - 10000.000

MWh

0.001

100.000

Pulse quantity for active reverse


accumulated energy value

ERFAccPlsQty

0.001 - 10000.000

MVArh

0.001

100.000

Pulse quantity for reactive forward


accumulated energy value

ERVAccPlsQty

0.001 - 10000.000

MVArh

0.001

100.000

Pulse quantity for reactive reverse


accumulated energy value

Table 604:
Name

ETPMMTR Non group settings (advanced)


Values (Range)

Unit

Step

Default

Description

EALim

0.001 10000000000.000

MWh

0.001

1000000.000

Active energy limit

ERLim

0.001 10000000000.000

MVArh

0.001

1000.000

Reactive energy limit

DirEnergyAct

Forward
Reverse

Forward

Direction of active energy flow Forward/


Reverse

DirEnergyReac

Forward
Reverse

Forward

Direction of reactive energy flow Forward/


Reverse

EnZeroClamp

Off
On

On

Enable of zero point clamping detection


function

LevZeroClampP

0.001 - 10000.000

MW

0.001

10.000

Zero point clamping level at active Power

LevZeroClampQ

0.001 - 10000.000

MVAr

0.001

10.000

Zero point clamping level at reactive


Power

EAFPrestVal

0.000 - 10000.000

MWh

0.001

0.000

Preset Initial value for forward active


energy

EARPrestVal

0.000 - 10000.000

MWh

0.001

0.000

Preset Initial value for reverse active


energy

ERFPresetVal

0.000 - 10000.000

MVArh

0.001

0.000

Preset Initial value for forward reactive


energy

ERVPresetVal

0.000 - 10000.000

MVArh

0.001

0.000

Preset Initial value for reverse reactive


energy

896
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Section 17

Station communication

About this chapter


This chapter describes the functions and protocols used on the interfaces to the
substation automation and substation monitoring buses. The way these work, their
setting parameters, function blocks, input and output signals and technical data are
included for each function.

17.1

Overview
Each IED is provided with a communication interface, enabling it to connect to one
or many substation level systems or equipment, either on the Substation
Automation (SA) bus or Substation Monitoring (SM) bus.
Following communication protocols are available:

IEC 61850-8-1 communication protocol


IEC 61850-9-2LE communication protocol
LON communication protocol
SPA or IEC 60870-5-103 communication protocol
DNP3.0 communication protocol

Theoretically, several protocols can be combined in the same IED.

17.2

IEC 61850-8-1 communication protocol

17.2.1

Introduction
The IED is equipped with single or double optical Ethernet rear ports (order
dependent) for IEC 61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different vendors to
exchange information and simplifies system engineering. Peer-to-peer
communication according to GOOSE is part of the standard. Disturbance files
uploading is provided.

897
Technical reference manual

Section 17
Station communication
17.2.2
Table 605:
Name

1MRK 505 222-UEN B

Setting parameters
IEC61850-8-1 Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off/On

GOOSE

Front
OEM311_AB
OEM311_CD

OEM311_AB

Port for GOOSE communication

17.2.3

Technical data
Table 606:

IEC 61850-8-1 communication protocol

Function

Value

Protocol

IEC 61850-8-1

Communication speed for the IEDs

100BASE-FX

17.2.4

IEC 61850 generic communication I/O functions SPGGIO,


SP16GGIO

17.2.4.1

Introduction
IEC61850 generic communication I/O functions (SPGGIO) is used to send one
single logical signal to other systems or equipment in the substation.

17.2.4.2

Principle of operation
Upon receiving a signal at its input, IEC61850 generic communication I/O
functions (SPGGIO) function sends the signal over IEC 61850-8-1 to the
equipment or system that requests this signal. To get the signal, PCM600 must be
used to define which function block in which equipment or system should receive
this information.

17.2.4.3

Function block
SPGGIO
BLOCK
^IN
IEC07000124-2-en.vsd
IEC07000124 V2 EN

Figure 484:

SPGGIO function block

898
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

SP16GGIO
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC07000125-2-en.vsd
IEC07000125 V2 EN

Figure 485:

17.2.4.4

SP16GGIO function block

Input and output signals


Table 607:
Name

SPGGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN

BOOLEAN

Input status

Table 608:
Name

SP16GGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN1

BOOLEAN

Input 1 status

IN2

BOOLEAN

Input 2 status

IN3

BOOLEAN

Input 3 status

IN4

BOOLEAN

Input 4 status

IN5

BOOLEAN

Input 5 status

IN6

BOOLEAN

Input 6 status

IN7

BOOLEAN

Input 7 status

IN8

BOOLEAN

Input 8 status

IN9

BOOLEAN

Input 9 status

IN10

BOOLEAN

Input 10 status

IN11

BOOLEAN

Input 11 status

IN12

BOOLEAN

Input 12 status

IN13

BOOLEAN

Input 13 status

IN14

BOOLEAN

Input 14 status

IN15

BOOLEAN

Input 15 status

IN16

BOOLEAN

Input 16 status

899
Technical reference manual

Section 17
Station communication
17.2.4.5

1MRK 505 222-UEN B

Setting parameters
The function does not have any parameters available in the local HMI or PCM600.

17.2.5

IEC 61850 generic communication I/O functions MVGGIO


IEC61850 generic communication I/O functions (MVGGIO) function is used to
send the instantaneous value of an analog output to other systems or equipment in
the substation. It can also be used inside the same IED, to attach a RANGE aspect
to an analog value and to permit measurement supervision on that value.

17.2.5.1

Principle of operation
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range,
as output values. In the same time, it will send over IEC 61850-8-1 the value, to
other IEC 61850 clients in the substation.

17.2.5.2

Function block
MVGGIO
BLOCK
^IN

^VALUE
RANGE
IEC05000408-2-en.vsd

IEC05000408 V2 EN

Figure 486:

17.2.5.3

MVGGIO function block

Input and output signals


Table 609:
Name

MVGGIO Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

IN

REAL

Analogue input value

Table 610:
Name

MVGGIO Output signals


Type

Description

VALUE

REAL

Magnitude of deadband value

RANGE

INTEGER

Range

900
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

17.2.5.4
Table 611:

Setting parameters
MVGGIO Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

MV db

1 - 300

Type

10

Cycl: Report interval (s), Db: In % of


range, Int Db: In %s

MV zeroDb

0 - 100000

m%

500

Zero point clamping in 0,001% of range

MV hhLim

-10000000000.000
- 10000000000.000

0.001

90.000

High High limit

MV hLim

-10000000000.000
- 10000000000.000

0.001

80.000

High limit

MV lLim

-10000000000.000
- 10000000000.000

0.001

-80.000

Low limit

MV llLim

-10000000000.000
- 10000000000.000

0.001

-90.000

Low Low limit

MV min

-10000000000.000
- 10000000000.000

0.001

-100.000

Minimum value

MV max

-10000000000.000
- 10000000000.000

0.001

100.000

Maximum value

MV dbType

Cyclic
Dead band
Int deadband

Dead band

Reporting type

MV limHys

0.000 - 100.000

0.001

5.000

Hysteresis value in % of range (common


for all limits)

17.2.6

IEC 61850-8-1 redundant station bus communication


Function description

17.2.6.1

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Parallel Redundancy Protocol Status

PRPSTATUS

Duo driver configuration

DUODRV

Introduction
Redundant station bus communication is used to assure communication, even
though one communication channels might not be available for some reason.
Redundant communication over station bus running IEC 61850-8-1 use both port
AB and CD on OEM module and IEC 62439-PRP protocol.

17.2.6.2

Principle of operation
The redundant station bus communication (DUODRV) is configured using the
local HMI. The settings for DUODRV are also visible in PST in PCM600.
The communication is performed in parallel, that is the same data package is
transmitted on both channels simultaneously. The received package identity from
901

Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

one channel is compared with data package identity from the other channel, if the
same, the last package is discarded.
PRPSTATUS function block supervise the redundant communication on the two
channels. If no data package has been received on one (or both) channels within the
last 10 s, the output LAN-A-STATUS and/or LAN-B-STATUS is set to indicate error.
Station Control System
Redundancy
Supervision
Duo

Data

Data

Switch A

Switch B

1 2

1 2

Data

Data

AB
Configuration

CD

IED

OEM

DUODRV

PRPSTATUS

IEC09000758-2-en.vsd
IEC09000758 V2 EN

Figure 487:

Redundant station bus

902
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

17.2.6.3

Function block
PRPSTATUS
LAN-A-Status
LAN-B-Status
IEC09000757-1-en.vsd
IEC09000757 V1 EN

Figure 488:

17.2.6.4

PRPSTATUS function block

Output signals
Table 612:

PRPSTATUS Output signals

Name

17.2.6.5
Table 613:

Type

Description

LAN-A-Status

BOOLEAN

Channel A status

LAN-B-Status

BOOLEAN

Channel B status

Setting parameters
DUODRV Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation Off / On

IPAddress

0 - 18

IP
Address

192.168.7.10

IP-Address

IPMask

0 - 18

IP
Address

255.255.255.0

IP-Mask

17.3

IEC 61850-9-2LE communication protocol

17.3.1

Introduction
The IEC 61850-9-2LE process bus communication protocol enables an IED to
communicate with devices providing measured values in digital format, commonly
known as Merging Units (MU). The physical interface in the IED that is used for
the communication is the OEM modules (the two port module version) "CD" port.

17.3.2

Principle of operation
The ABB merging units (MUs) are situated close to primary equipment, like circuit
breakers, isolators, etc. The MUs have the capability to gather measured values
from measuring transformers, non-conventional transducers or both. The gathered
data are then transmitted to subscribers over the process bus, utilizing the IEC
61850-9-2LE protocol.

903
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

ABB "physical MU" contains up to 3 logical MUs, each capable of sampling 4


currents and 4 voltages.
The IED communicates with the MUs over the process bus via the OEM module
port "CD". For the user, the MU appears in the IED as a normal analogue input
module and is engineered in the very same way.
IED
Application

Station Wide
GPS Clock
IRIG-B
1344

SMAI1
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
TYPE

SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN

Preprocessing blocks
SMAI

Splitter
Electrical-toOptical Converter

MU1 (Logic MU) MU2 (Logic MU)

OEM Module
CD

IEC61850-9-2LE

Ethernet Switch
IEC61850-9-2LE
IEC61850-9-2LE

ABB
Merging
Unit

Combi
Sensor

1PPS

ABB
Merging
Unit

1PPS

Combi
Sensor

en08000212-2.vsd
IEC08000212 V2 EN

Figure 489:

Example of signal path for sampled analog values from MU with


IRIG-B synchronization

904
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

IED
Application

Preprocessing blocks
SMAI

Station Wide
GPS Clock

Preprocessing blocks
SMAI

MU1

MU2

Splitter
Electrical-toOptical Converter

1PPS
TRM module

OEM Module
CD

110 V

1A

1A

IEC61850-9-2LE

Ethernet Switch
IEC61850-9-2LE
IEC61850-9-2LE

ABB
Merging
Unit

CT

ABB
Merging
Unit

1PPS

Combi
Sensor

CT

1PPS

Combi
Sensor

Conventional VT
en08000072-2.vsd
IEC08000072 V2 EN

Figure 490:

Example of signal path for sampled analogue values from MU and


conventional CT/VT

The function has the following alarm signals:

905
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

MUDATA: Indicates when sample sequence needs to be realigned. that is the


application soon needs to be restarted. The signal is raised to 2 s before the
application is restarted.
SYNCH: Indicates that the time quality of the hardware is out of the set value
from parameter synchAccLevel (1 s, 4 s or unspecified) and the parameter
AppSynch is set to Synch. In case of AppSynch is set to NoSynch the SYNCH
output will never go high.
SMPLLOST: Indicates that more than one sample has been lost/been marked
invalid/ overflow/ been marked failed, and the sample has thereafter been
substituted. When SMPLLOST is high, protection is blocked.
MUSYNCH: Indicates that the MU connected is not synchronized. Received
from quality flag in datastream. No IED setting affects this signal.
TESTMODE: Indicates that the MU connected is in TestMode. Received from
quality flag in datastream. No IED setting affects this signal.

Timeout
TSYNCERR Indicates that there is some timeout on any configured time source or
the time quality is worse than specified in SynchAccLevel. The timeout is
individually specified per time source (PPS, IRIG-B, SNTP etc.) See section
"Time synchronization"
Blocking condition
Blocking of protection functions is indicated by (SAMPLOST is high) or
(MUSYNCH is high and AppSynch is set to Synch) or (SYNCH is high)
Application synch is not required for differential protection based on ECHO mode.
A missing PPS however will lead to a drift between MU and IED. Therefore
protection functions in this case will be blocked.

17.3.3

Consequence on accuracy for power measurement


functions when using signals from IEC 61850-9-2LE
communication
The Power measurement functions (CVMMXN, CMMXU, VMMXU and
VNMMXU) contains correction factors to account for the non-linearity in the input
circuits, mainly in the input transformers, when using direct analogue connection to
the IED.
The IED will use the same correction factors also when feeding the IED with
analog signals over IEC 61850-9-2LE. Since the signals via IEC 61850-9-2LE are
not subject to the same non-linearity errors this will cause an inaccuracy in the
measured values.
For voltage signals the correction factors are less than 0.05% of the measured value
and no angle compensation why the impact on reported value can be ignored.

906
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

For current signals the correction factors will cause a not insignificant impact on
the reported values at low currents. The correction factors are +2.4% and -3.6
degrees at signal levels below 5% of set base current, +0.6% and -1.12 degrees at
signal level 30% of set base current and 0% and -0.44 degrees at signal levels
above 100% of set base current. Between the calibration points 5%, 30% and 100%
of set base current, linear interpolation is used. Since the output from the Power
measurement function is used as an input for the Energy measuring function
(ETPMMTR) the above described impact will also be valid for the output values
for ETPMMTR.

17.3.4

Function block
The function blocks are not represented in the configuration tool.
The signals appear only in the SMT tool when merging units (MU)
are included in the configuration with the function selector tool. In
the SMT tool they can be mapped to the desired virtual input
(SMAI) of the IED and used internally in the configuration.

17.3.5

Output signals
Table 614:
Name

MU1_4I_4U Output signals


Type

Description

I1

STRING

Analogue input I1

I2

STRING

Analogue input I2

I3

STRING

Analogue input I3

I4

STRING

Analogue input I4

U1

STRING

Analogue input U1

U2

STRING

Analogue input U2

U3

STRING

Analogue input U3

U4

STRING

Analogue input U4

MUDATA

BOOLEAN

Fatal error, serious data loss

SYNCH

BOOLEAN

MU clock synchronized to same clock as IED

SMPLLOST

BOOLEAN

Sample lost

MUSYNCH

BOOLEAN

Synchronization lost in MU

TESTMODE

BOOLEAN

MU in test mode

907
Technical reference manual

Section 17
Station communication
17.3.6
Table 615:
Name

1MRK 505 222-UEN B

Setting parameters
MU1_4I_4U Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

SVId

0 - 35

ABB_MU0101

MU identifier

SmplGrp

0 - 65535

Sampling group

CTStarPoint1

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTStarPoint2

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTStarPoint3

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

CTStarPoint4

FromObject
ToObject

ToObject

ToObject= towards protected object,


FromObject= the opposite

Table 616:
Name
SynchMode

17.3.7

MU1_4I_4U Non group settings (advanced)


Values (Range)
NoSynch
Init
Operation

Unit

Step

Default

Description

Operation

Synchronization mode

Technical data
Table 617:

IEC 61850-9-2LE communication protocol

Functions

Value

Protocol

IEC 61850-9-2LE

Communication speed for the IEDs

100BASE-FX

17.4

LON communication protocol

17.4.1

Introduction
An optical network can be used within the substation automation system. This
enables communication with the IED through the LON bus from the operators
workplace, from the control center and also from other terminals.
LON communication protocol is specified in LonTalkProtocol Specification
Version 3 from Echelon Corporation and is designed for communication in control
networks. These networks are characterized by high speed for data transfer, short
messages (few bytes), peer-to-peer communication, multiple communication
media, low maintenance, multivendor equipment, and low support costs. LonTalk
supports the needs of applications that cover a range of requirements. The protocol

908
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

follows the reference model for open system interconnection (OSI) designed by the
International Standardization Organization (ISO).
In this document the most common addresses for commands and events are
available. For other addresses, refer to section "Related documents".
It is assumed that the reader is familiar with LON communication protocol in general.

17.4.2

Principle of operation
The speed of the network depends on the medium and transceiver design. With
protection and control devices, fibre optic media is used, which enables the use of
the maximum speed of 1.25 Mbits/s. The protocol is a peer-to-peer protocol where
all the devices connected to the network can communicate with each other. The
own subnet and node number are identifying the nodes (max. 255 subnets, 127
nodes per one subnet).
The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent
to the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for
example, interlocking information among the terminals without the need of a bus
master.
The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short
messages, such as measuring values, status information, and interlocking/blocking
signals. Explicit messages are used to transfer longer pieces of information, such as
events and explicit read and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for
multi-master implementations. The LON bus also has an open concept, so that the
terminals can communicate with external devices using the same standard of
network variables.

Introduction of LON protocol

For more information, refer to LON bus, LonWorks Network in Protection and
Control, Users manual and Technical description.

LON protocol
Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a
LonWorks network, is easily accessible on a single tool program. For more
information, refer to the operator's manual.

909
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Activate LON Communication


Activate LON communication in the Parameter Setting tool under Main menu/
Communication/ SLM configuration/ Rear optical LON port/ Horizontal
communication, where Operation must be set to ON.
Add LON Device Types LNT
A new device is added to LON Network Tool from the Device menu or by
installing the device from the ABB LON Device Types package for LNT 505, with
the SLDT 670 series package version 1p2 r03.
LON net address
To establish a LON connection with the 670 series IEDs, the IED has to be given a
unique net address. The net address consists of a subnet and node number. This is
accomplished with the LON Network Tool by creating one device for each IED.
Vertical communication
Vertical communication describes communication between the monitoring devices
and protection and control IEDs. This communication includes sending of changed
process data to monitoring devices as events and transfer of commands, parameter
data and disturbance recorder files. This communication is implemented using
explicit messages.
Events and indications
Events sent to the monitoring devices are using explicit messages (message code
44H) with unacknowledged transport service of the LonTalk protocol. When a
signal is changed in the IED, one message with the value, quality and time is
transmitted from terminal.
Binary events
Binary events are generated in event function blocks EVENT:1 to EVENT:20 in
the 670 series IEDs. The event function blocks have predefined LON addresses.
table 618 shows the LON addresses to the first input on the event function blocks.
The addresses to the other inputs on the event function block are consecutive after
the first input. For example, input 15 on event block EVENT:17 has the address
1280 + 14 (15-1) = 1294.
For double indications only the first eight inputs 18 must be used. Inputs 916 can
be used for other type of events at the same event block.
As basic, three event function blocks EVENT:1 to EVENT:3 running with a fast
loop time (3 ms) is available in the 670 series IEDs. The remaining event function
blocks EVENT:4 to EVENT:9 runs with a loop time on 8 ms and EVENT:10 to
EVENT:20 runs with a loop time on 100 ms. The event blocks are used to send
binary signals, integers, real time values like analogue data from measuring
functions and mA input modules as well as pulse counter signals.
16 pulse counter value function blocks PCGGIO:1 to PCGGIO:16 and 24 mA input
service values function blocks SMMI1_In1 to 6 SMMI4_In1 to 6 are available in
the 670 series IEDs.

910
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

The first LON address in every event function block is found in table 618
Table 618:
Function block

LON adresses for Event functions


First LON address in
function block

EVENT:1

1024

EVENT:2

1040

EVENT:3

1056

EVENT:4

1072

EVENT:5

1088

EVENT:6

1104

EVENT:7

1120

EVENT:8

1136

EVENT:9

1152

EVENT:10

1168

EVENT:11

1184

EVENT:12

1200

EVENT:13

1216

EVENT:14

1232

EVENT:15

1248

EVENT:16

1264

EVENT:17

1280

EVENT:18

1296

EVENT:19

1312

EVENT:20

1328

Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:

No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)

The following type of signals from application functions can be connected to the
event function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is
always reported on change, no changed detection is done in the event function

911
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

block. Other Boolean signals, for example a start or a trip signal from a protection
function is event masked in the event function block.
Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for
the first 8 inputs on an event function block.

00 generates an intermediate event with the read status 0


01 generates an open event with the read status 1
10 generates a close event with the read status 2
11 generates an undefined event with the read status 3

Analog value
All analog values are reported cyclic, the reporting interval is taken from the
connected function if there is a limit supervised signal, otherwise it is taken from
the event function block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent
SPA-bus message is an explicit LON message, which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or
N) are sent using the same message code. It is mandatory that one device sends out
only one SPA-bus message at a time to one node and waits for the reply before
sending the next message.
For commands from the operator workplace to the IED for apparatus control, That
is, the function blocks type SCSWI 1 to 32, SXCBR 1 to 18 and SXSWI 1 to 28;
the SPA addresses are according to table 619.

Horizontal communication

Network variables are used for communication between 500 series and 670 series
IEDs. The supported network variable type is SNVT_state (NV type 83).
SNVT_state is used to communicate the state of a set of 1 to 16 Boolean values.
Multiple command send function block (MULTICMDSND) is used to pack the
information to one value. This value is transmitted to the receiving node and
presented for the application by a multiple command function block
(MULTICMDRCV). At horizontal communication the input BOUND on the event
function block (MULTICMDSND) must be set to 1. There are 10
MULTICMDSND and 60 MULTICMDRCV function blocks available. The

912
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

MULTICMDSND and MULTICMDRCV function blocks are connected using Lon


Network Tool (LNT 505). This tool also defines the service and addressing on LON.
This is an overview for configuring the network variables for 670 series IEDs.
Configuration of LON network variables
Configure the Network variables according to the specific application using the
LON network Tool. For more information, refer to LNT 505 in Operation manual.
The following is an example of how to configure network variables concerning, for
example, interlocking between two IEDs.
LON
BAY E1

BAY E3

MULTICMDSND: 7

MULTICMDSND: 9

BAY E4
MULTICMDSND: 9

en05000718.vsd
IEC05000718 V2 EN

Figure 491:

Examples connections between MULTICMDSND and


MULTICMDRCV function blocks in three IEDs

The network variable connections are done from the NV Connection window.
From LNT window select Connections/ NVConnections/ New.

913
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

en05000719.vsd
IEC05000719 V1 EN

Figure 492:

The network variables window in LNT

There are two ways of downloading NV connections. Either the users can use the
drag-and-drop method where they can select all nodes in the device window, drag
them to the Download area in the bottom of the program window and drop them
there; or, they can perform it by selecting the traditional menu, Configuration/
Download.

914
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

en05000720.vsd
IEC05000720 V1 EN

Figure 493:

The download configuration window in LNT

Communication ports

The serial communication module (SLM) is used for SPA/IEC60870-5-103/DNP


and LON communication. This module is a mezzanine module, and can be placed
on the Main Processing Module (NUM). The serial communication module can
have connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are
available depending on type of fibre. The incoming optical fibre is connected to the
RX receiver input, and the outgoing optical fibre to the TX transmitter output.
When the fibre optic cables are laid out, pay special attention to the instructions
concerning the handling and connection of the optical fibres. The module is
identified with a number on the label on the module.
Table 619:

SPA addresses for commands from the operator workplace to the IED for apparatus
control

Name

Function
block

SPA
address

Description

BL_CMD

SCSWI01

1 I 5115

SPA parameters for block


command

BL_CMD

SCSWI02

1 I 5139

SPA parameters for block


command

BL_CMD

SCSWI02

1 I 5161

SPA parameters for block


command

BL_CMD

SCSWI04

1 I 5186

SPA parameters for block


command

BL_CMD

SCSWI05

1 I 5210

SPA parameters for block


command

BL_CMD

SCSWI06

1 I 5234

SPA parameters for block


command

Table continues on next page


915
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

BL_CMD

SCSWI07

1 I 5258

SPA parameters for block


command

BL_CMD

SCSWI08

1 I 5283

SPA parameters for block


command

BL_CMD

SCSWI09

1 I 5307

SPA parameters for block


command

BL_CMD

SCSWI10

1 I 5331

SPA parameters for block


command

BL_CMD

SCSWI11

1 I 5355

SPA parameters for block


command

BL_CMD

SCSWI12

1 I 5379

SPA parameters for block


command

BL_CMD

SCSWI13

1 I 5403

SPA parameters for block


command

BL_CMD

SCSWI14

1 I 5427

SPA parameters for block


command

BL_CMD

SCSWI15

1 I 5451

SPA parameters for block


command

BL_CMD

SCSWI16

1 I 5475

SPA parameters for block


command

BL_CMD

SCSWI17

1 I 5499

SPA parameters for block


command

BL_CMD

SCSWI18

1 I 5523

SPA parameters for block


command

BL_CMD

SCSWI19

1 I 5545

SPA parameters for block


command

BL_CMD

SCSWI20

1 I 5571

SPA parameters for block


command

BL_CMD

SCSWI21

1 I 5594

SPA parameters for block


command

BL_CMD

SCSWI22

1 I 5619

SPA parameters for block


command

BL_CMD

SCSWI23

1 I 5643

SPA parameters for block


command

BL_CMD

SCSWI24

1 I 5667

SPA parameters for block


command

BL_CMD

SCSWI25

1 I 5691

SPA parameters for block


command

BL_CMD

SCSWI26

1 I 5715

SPA parameters for block


command

BL_CMD

SCSWI27

1 I 5739

SPA parameters for block


command

BL_CMD

SCSWI28

1 I 5763

SPA parameters for block


command

BL_CMD

SCSWI29

1 I 5787

SPA parameters for block


command

BL_CMD

SCSWI30

1 I 5811

SPA parameters for block


command

Table continues on next page

916
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Function
block

SPA
address

Description

BL_CMD

SCSWI31

1 I 5835

SPA parameters for block


command

BL_CMD

SCSWI32

1 I 5859

SPA parameters for block


command

CANCEL

SCSWI01

1 I 5107

SPA parameters for cancel


command

CANCEL

SCSWI02

1 I 5131

SPA parameters for cancel


command

CANCEL

SCSWI03

1 I 5153

SPA parameters for cancel


command

CANCEL

SCSWI04

1 I 5178

SPA parameters for cancel


command

CANCEL

SCSWI05

1 I 5202

SPA parameters for cancel


command

CANCEL

SCSWI06

1 I 5226

SPA parameters for cancel


command

CANCEL

SCSWI07

1 I 5250

SPA parameters for cancel


command

CANCEL

SCSWI08

1 I 5275

SPA parameters for cancel


command

CANCEL

SCSWI09

1 I 5299

SPA parameters for cancel


command

CANCEL

SCSWI10

1 I 5323

SPA parameters for cancel


command

CANCEL

SCSWI11

1 I 5347

SPA parameters for cancel


command

CANCEL

SCSWI12

1 I 5371

SPA parameters for cancel


command

CANCEL

SCSWI13

1 I 5395

SPA parameters for cancel


command

CANCEL

SCSWI14

1 I 5419

SPA parameters for cancel


command

CANCEL

SCSWI15

1 I 5443

SPA parameters for cancel


command

CANCEL

SCSWI16

1 I 5467

SPA parameters for cancel


command

CANCEL

SCSWI17

1 I 5491

SPA parameters for cancel


command

CANCEL

SCSWI18

1 I 5515

SPA parameters for cancel


command

CANCEL

SCSWI19

1 I 5537

SPA parameters for cancel


command

CANCEL

SCSWI20

1 I 5563

SPA parameters for cancel


command

CANCEL

SCSWI21

1 I 5586

SPA parameters for cancel


command

CANCEL

SCSWI22

1 I 5611

SPA parameters for cancel


command

Table continues on next page

917
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

CANCEL

SCSWI23

1 I 5635

SPA parameters for cancel


command

CANCEL

SCSWI24

1 I 5659

SPA parameters for cancel


command

CANCEL

SCSWI25

1 I 5683

SPA parameters for cancel


command

CANCEL

SCSWI26

1 I 5707

SPA parameters for cancel


command

CANCEL

SCSWI27

1 I 5731

SPA parameters for cancel


command

CANCEL

SCSWI28

1 I 5755

SPA parameters for cancel


command

CANCEL

SCSWI29

1 I 5779

SPA parameters for cancel


command

CANCEL

SCSWI30

1 I 5803

SPA parameters for cancel


command

CANCEL

SCSWI31

1 I 5827

SPA parameters for cancel


command

CANCEL

SCSWI32

1 I 5851

SPA parameters for cancel


command

SELECTOpen=00,
SELECTClose=01,
SELOpen+ILO=10,
SELClose+ILO=11,
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31

SCSWI01

1 I 5105

SPA parameters for select (Open/


Close) command
Note: Send select command
before operate command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI02

1 I 5129

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI03

1 I 5151

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI04

1 I 5176

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI05

1 I 5200

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI06

1 I 5224

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI07

1 I 5248

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI08

1 I 5273

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI09

1 I 5297

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI10

1 I 5321

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI11

1 I 5345

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI12

1 I 5369

SPA parameters for select (Open/


Close) command

Table continues on next page


918
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Function
block

SPA
address

Description

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI13

1 I 5393

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI14

1 I 5417

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI15

1 I 5441

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI16

1 I 5465

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI17

1 I 5489

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI18

1 I 5513

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI19

1 I 5535

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI20

1 I 5561

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI21

1 I 5584

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI22

1 I 5609

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI23

1 I 5633

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI24

1 I 5657

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI25

1 I 5681

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI26

1 I 5705

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI27

1 I 5729

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI28

1 I 5753

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI29

1 I 5777

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI30

1 I 5801

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI31

1 I 5825

SPA parameters for select (Open/


Close) command

SELECTOpen=00,
SELECTClose=01, so on.

SCSWI32

1 I 5849

SPA parameters for select (Open/


Close) command

ExcOpen=00,
ExcClose=01,
ExcOpen+ILO=10,
ExcClose+ILO=11,
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31

SCSWI01

1 I 5106

SPA parameters for operate (Open/


Close) command
Note: Send select command
before operate command

ExcOpen=00,
ExcClose=01, so on.

SCSWI02

1 I 5130

SPA parameters for operate (Open/


Close) command

Table continues on next page


919
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

ExcOpen=00,
ExcClose=01, so on.

SCSWI02

1 I 5152

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI04

1 I 5177

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI05

1 I 5201

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI06

1 I 5225

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI07

1 I 5249

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI08

1 I 5274

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI09

1 I 5298

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI10

1 I 5322

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI11

1 I 5346

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI12

1 I 5370

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI13

1 I 5394

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI14

1 I 5418

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI15

1 I 5442

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI16

1 I 5466

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI17

1 I 5490

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI18

1 I 5514

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI19

1 I 5536

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI20

1 I 5562

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI21

1 I 5585

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI22

1 I 5610

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI23

1 I 5634

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI24

1 I 5658

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI25

1 I 5682

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI26

1 I 5706

SPA parameters for operate (Open/


Close) command

Table continues on next page

920
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Function
block

SPA
address

Description

ExcOpen=00,
ExcClose=01, so on.

SCSWI27

1 I 5730

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI28

1 I 5754

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI29

1 I 5778

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI30

1 I 5802

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI31

1 I 5826

SPA parameters for operate (Open/


Close) command

ExcOpen=00,
ExcClose=01, so on.

SCSWI32

1 I 5850

SPA parameters for operate (Open/


Close) command

Sub Value

SXCBR01

2 I 7854

SPA parameter for position to be


substituted
Note: Send the value before Enable

Sub Value

SXCBR02

2 I 7866

SPA parameter for position to be


substituted

Sub Value

SXCBR03

2 I 7884

SPA parameter for position to be


substituted

Sub Value

SXCBR04

2 I 7904

SPA parameter for position to be


substituted

Sub Value

SXCBR05

2 I 7923

SPA parameter for position to be


substituted

Sub Value

SXCBR06

2 I 7942

SPA parameter for position to be


substituted

Sub Value

SXCBR07

2 I 7961

SPA parameter for position to be


substituted

Sub Value

SXCBR08

2 I 7980

SPA parameter for position to be


substituted

Sub Value

SXCBR09

3I7

SPA parameter for position to be


substituted

Sub Value

SXCBR10

3 I 26

SPA parameter for position to be


substituted

Sub Value

SXCBR11

3 I 45

SPA parameter for position to be


substituted

Sub Value

SXCBR12

3 I 56

SPA parameter for position to be


substituted

Sub Value

SXCBR13

3 I 74

SPA parameter for position to be


substituted

Sub Value

SXCBR14

3 I 94

SPA parameter for position to be


substituted

Sub Value

SXCBR15

3 I 120

SPA parameter for position to be


substituted

Sub Value

SXCBR16

3 I 133

SPA parameter for position to be


substituted

Sub Value

SXCBR17

3 I 158

SPA parameter for position to be


substituted

Sub Value

SXCBR18

3 I 179

SPA parameter for position to be


substituted

Table continues on next page


921
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

Sub Value

SXSWI01

3 I 196

SPA parameter for position to be


substituted

Sub Value

SXSWI02

3 I 216

SPA parameter for position to be


substituted

Sub Value

SXSWI03

3 I 235

SPA parameter for position to be


substituted

Sub Value

SXSWI04

3 I 254

SPA parameter for position to be


substituted

Sub Value

SXSWI05

3 I 272

SPA parameter for position to be


substituted

Sub Value

SXSWI06

3 I 292

SPA parameter for position to be


substituted

Sub Value

SXSWI07

3 I 310

SPA parameter for position to be


substituted

Sub Value

SXSWI08

3 I 330

SPA parameter for position to be


substituted

Sub Value

SXSWI09

3 I 348

SPA parameter for position to be


substituted

Sub Value

SXSWI10

3 I 359

SPA parameter for position to be


substituted

Sub Value

SXSWI11

3 I 378

SPA parameter for position to be


substituted

Sub Value

SXSWI12

3 I 397

SPA parameter for position to be


substituted

Sub Value

SXSWI13

3 I 416

SPA parameter for position to be


substituted

Sub Value

SXSWI14

3 I 435

SPA parameter for position to be


substituted

Sub Value

SXSWI15

3 I 454

SPA parameter for position to be


substituted

Sub Value

SXSWI16

3 I 473

SPA parameter for position to be


substituted

Sub Value

SXSWI17

3 I 492

SPA parameter for position to be


substituted

Sub Value

SXSWI18

3 I 511

SPA parameter for position to be


substituted

Sub Value

SXSWI19

3 I 530

SPA parameter for position to be


substituted

Sub Value

SXSWI20

3 I 549

SPA parameter for position to be


substituted

Sub Value

SXSWI21

3 I 568

SPA parameter for position to be


substituted

Sub Value

SXSWI22

3 I 587

SPA parameter for position to be


substituted

Sub Value

SXSWI23

3 I 606

SPA parameter for position to be


substituted

Sub Value

SXSWI24

3 I 625

SPA parameter for position to be


substituted

Table continues on next page

922
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Function
block

SPA
address

Description

Sub Value

SXSWI25

3 I 644

SPA parameter for position to be


substituted

Sub Value

SXSWI26

3 I 663

SPA parameter for position to be


substituted

Sub Value

SXSWI27

3 I 682

SPA parameter for position to be


substituted

Sub Value

SXSWI28

3 I 701

SPA parameter for position to be


substituted

Sub Enable

SXCBR01

2 I 7855

SPA parameter for substitute


enable command
Note: Send the Value before
Enable

Sub Enable

SXCBR02

2 I 7865

SPA parameter for substitute


enable command

Sub Enable

SXCBR03

2 I 7885

SPA parameter for substitute


enable command

Sub Enable

SXCBR04

2 I 7903

SPA parameter for substitute


enable command

Sub Enable

SXCBR05

2 I 7924

SPA parameter for substitute


enable command

Sub Enable

SXCBR06

2 I 7941

SPA parameter for substitute


enable command

Sub Enable

SXCBR07

2 I 7962

SPA parameter for substitute


enable command

Sub Enable

SXCBR08

2 I 7979

SPA parameter for substitute


enable command

Sub Enable

SXCBR09

3I8

SPA parameter for substitute


enable command

Sub Enable

SXCBR10

3 I 25

SPA parameter for substitute


enable command

Sub Enable

SXCBR11

3 I 46

SPA parameter for substitute


enable command

Sub Enable

SXCBR12

3 I 55

SPA parameter for substitute


enable command

Sub Enable

SXCBR13

3 I 75

SPA parameter for substitute


enable command

Sub Enable

SXCBR14

3 I 93

SPA parameter for substitute


enable command

Sub Enable

SXCBR15

3 I 121

SPA parameter for substitute


enable command

Sub Enable

SXCBR16

3 I 132

SPA parameter for substitute


enable command

Sub Enable

SXCBR17

3 I 159

SPA parameter for substitute


enable command

Sub Enable

SXCBR18

3 I 178

SPA parameter for substitute


enable command

Sub Enable

SXSWI01

3 I 197

SPA parameter for substitute


enable command

Table continues on next page

923
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

Sub Enable

SXSWI02

3 I 215

SPA parameter for substitute


enable command

Sub Enable

SXSWI03

3 I 234

SPA parameter for substitute


enable command

Sub Enable

SXSWI04

3 I 252

SPA parameter for substitute


enable command

Sub Enable

SXSWI05

3 I 271

SPA parameter for substitute


enable command

Sub Enable

SXSWI06

3 I 290

SPA parameter for substitute


enable command

Sub Enable

SXSWI07

3 I 309

SPA parameter for substitute


enable command

Sub Enable

SXSWI08

3 I 328

SPA parameter for substitute


enable command

Sub Enable

SXSWI09

3 I 347

SPA parameter for substitute


enable command

Sub Enable

SXSWI10

3 I 360

SPA parameter for substitute


enable command

Sub Enable

SXSWI11

3I 379

SPA parameter for substitute


enable command

Sub Enable

SXSWI12

3 I 398

SPA parameter for substitute


enable command

Sub Enable

SXSWI13

3 I 417

SPA parameter for substitute


enable command

Sub Enable

SXSWI14

3 I 436

SPA parameter for substitute


enable command

Sub Enable

SXSWI15

3 I 455

SPA parameter for substitute


enable command

Sub Enable

SXSWI16

3 I 474

SPA parameter for substitute


enable command

Sub Enable

SXSWI17

3 I 493

SPA parameter for substitute


enable command

Sub Enable

SXSWI18

3 I 512

SPA parameter for substitute


enable command

Sub Enable

SXSWI19

3 I 531

SPA parameter for substitute


enable command

Sub Enable

SXSWI20

3 I 550

SPA parameter for substitute


enable command

Sub Enable

SXSWI21

3 I 569

SPA parameter for substitute


enable command

Sub Enable

SXSWI22

3 I 588

SPA parameter for substitute


enable command

Sub Enable

SXSWI23

3 I 607

SPA parameter for substitute


enable command

Sub Enable

SXSWI24

3 I 626

SPA parameter for substitute


enable command

Sub Enable

SXSWI25

3 I 645

SPA parameter for substitute


enable command

Table continues on next page

924
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Function
block

SPA
address

Description

Sub Enable

SXSWI26

3 I 664

SPA parameter for substitute


enable command

Sub Enable

SXSWI27

3 I 683

SPA parameter for substitute


enable command

Sub Enable

SXSWI28

3 I 702

SPA parameter for substitute


enable command

Update Block

SXCBR01

2 I 7853

SPA parameter for update block


command

Update Block

SXCBR02

2 I 7864

SPA parameter for update block


command

Update Block

SXCBR03

2 I 7883

SPA parameter for update block


command

Update Block

SXCBR04

2 I 7905

SPA parameter for update block


command

Update Block

SXCBR05

2 I 7922

SPA parameter for update block


command

Update Block

SXCBR06

2 I 7943

SPA parameter for update block


command

Update Block

SXCBR07

2 I 7960

SPA parameter for update block


command

Update Block

SXCBR08

2 I 7981

SPA parameter for update block


command

Update Block

SXCBR09

3I6

SPA parameter for update block


command

Update Block

SXCBR10

3 I 27

SPA parameter for update block


command

Update Block

SXCBR11

3 I 44

SPA parameter for update block


command

Update Block

SXCBR12

3 I 57

SPA parameter for update block


command

Update Block

SXCBR13

3 I 73

SPA parameter for update block


command

Update Block

SXCBR14

3 I 92

SPA parameter for update block


command

Update Block

SXCBR15

3 I 122

SPA parameter for update block


command

Update Block

SXCBR16

3 I 131

SPA parameter for update block


command

Update Block

SXCBR17

3 I 160

SPA parameter for update block


command

Update Block

SXCBR18

3 I 177

SPA parameter for update block


command

Update Block

SXSWI01

3 I 198

SPA parameter for update block


command

Update Block

SXSWI02

3 I 214

SPA parameter for update block


command

Update Block

SXSWI03

3 I 236

SPA parameter for update block


command

Table continues on next page

925
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Function
block

SPA
address

Description

Update Block

SXSWI04

3 I 253

SPA parameter for update block


command

Update Block

SXSWI05

3 I 273

SPA parameter for update block


command

Update Block

SXSWI06

3 I 291

SPA parameter for update block


command

Update Block

SXSWI07

3 I 311

SPA parameter for update block


command

Update Block

SXSWI08

3 I 329

SPA parameter for update block


command

Update Block

SXSWI09

3 I 349

SPA parameter for update block


command

Update Block

SXSWI10

3 I 358

SPA parameter for update block


command

Update Block

SXSWI11

3 I 377

SPA parameter for update block


command

Update Block

SXSWI12

3 I 396

SPA parameter for update block


command

Update Block

SXSWI13

3 I 415

SPA parameter for update block


command

Update Block

SXSWI14

3 I 434

SPA parameter for update block


command

Update Block

SXSWI15

3 I 453

SPA parameter for update block


command

Update Block

SXSWI16

3 I 472

SPA parameter for update block


command

Update Block

SXSWI17

3 I 491

SPA parameter for update block


command

Update Block

SXSWI18

3 I 510

SPA parameter for update block


command

Update Block

SXSWI19

3 I 529

SPA parameter for update block


command

Update Block

SXSWI20

3 I 548

SPA parameter for update block


command

Update Block

SXSWI21

3 I 567

SPA parameter for update block


command

Update Block

SXSWI22

3 I 586

SPA parameter for update block


command

Update Block

SXSWI23

3 I 605

SPA parameter for update block


command

Update Block

SXSWI24

3 I 624

SPA parameter for update block


command

Update Block

SXSWI25

3 I 643

SPA parameter for update block


command

Table continues on next page

926
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

17.4.3
Table 620:

SPA
address

Description

Update Block

SXSWI26

3 I 662

SPA parameter for update block


command

Update Block

SXSWI27

3 I 681

SPA parameter for update block


command

Update Block

SXSWI28

3 I 700

SPA parameter for update block


command

Setting parameters
HORZCOMM Non group settings (basic)

Name

Values (Range)

Operation

Table 621:

Function
block

Unit

Off
On

Step

Default

Description

Off

Operation

ADE Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation

TimerClass

Slow
Normal
Fast

Slow

Timer class

17.4.4

Technical data
Table 622:

LON communication protocol

Function

Value

Protocol

LON

Communication speed

1.25 Mbit/s

17.5

SPA communication protocol

17.5.1

Introduction
In this section the most common addresses for commands and events are available.
For other addresses, refer to section "Related documents".
It is assumed that the reader is familiar with the SPA communication protocol in
general.

927
Technical reference manual

Section 17
Station communication
17.5.2

1MRK 505 222-UEN B

Principle of operation
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7
data bits + even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For
more information on recommended baud rate for each type of IED, refer to
Technical reference manual. Messages on the bus consist of ASCII characters.

Introduction of SPA protocol

The basic construction of the protocol assumes that the slave has no self-initiated
need to talk to the master but the master is aware of the data contained in the slaves
and, consequently, can request required data. In addition, the master can send data
to the slave. Requesting by the master can be performed either by sequenced
polling (for example, for event information) or only on demand.
The master requests slave information using request messages and sends
information to the slave in write messages. Furthermore, the master can send all
slaves in common a broadcast message containing time or other data. The inactive
state of bus transmit and receive lines is a logical "1".

SPA protocol

The tables below specify the SPA addresses for reading data from and writing data
to an IED with the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MIM3 to MIM16) are found
in table 623.
Table 623:

SPA addresses for the MIM function

Function block

SPA address

MIM3-CH1

4-O-6508

MIM3-CH2

4-O-6511

MIM3-CH3

4-O-6512

MIM3-CH4

4-O-6515

MIM3-CH5

4-O-6516

MIM3-CH6

4-O-6519

MIM4-CH1

4-O-6527

MIM4-CH2

4-O-6530

MIM4-CH3

4-O-6531

MIM4-CH4

4-O-6534

MIM4-CH5

4-O-6535

MIM4-CH6

4-O-6538

MIM5-CH1

4-O-6546

MIM5-CH2

4-O-6549

MIM5-CH3

4-O-6550

MIM5-CH4

4-O-6553

MIM5-CH5

4-O-6554

Table continues on next page

928
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function block

SPA address

MIM5-CH6

4-O-6557

MIM6-CH1

4-O-6565

MIM6-CH2

4-O-6568

MIM6-CH3

4-O-6569

MIM6-CH4

4-O-6572

MIM6-CH5

4-O-6573

MIM6-CH6

4-O-6576

MIM7-CH1

4-O-6584

MIM7-CH2

4-O-6587

MIM7-CH3

4-O-6588

MIM7-CH4

4-O-6591

MIM7-CH5

4-O-6592

MIM7-CH6

4-O-6595

MIM8-CH1

4-O-6603

MIM8-CH2

4-O-6606

MIM8-CH3

4-O-6607

MIM8-CH4

4-O-6610

MIM8-CH5

4-O-6611

MIM8-CH6

4-O-6614

MIM9-CH1

4-O-6622

MIM9-CH2

4-O-6625

MIM9-CH3

4-O-6626

MIM9-CH4

4-O-6629

MIM9-CH5

4-O-6630

MIM9-CH6

4-O-6633

MIM10-CH1

4-O-6641

MIM10-CH2

4-O-6644

MIM10-CH3

4-O-6645

MIM10-CH4

4-O-6648

MIM10-CH5

4-O-6649

MIM10-CH6

4-O-6652

MIM11-CH1

4-O-6660

MIM11-CH2

4-O-6663

MIM11-CH3

4-O-6664

MIM11-CH4

4-O-6667

MIM11-CH5

4-O-6668

MIM11-CH6

4-O-6671

MIM12-CH1

4-O-6679

MIM12-CH2

4-O-6682

Table continues on next page

929
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function block

SPA address

MIM12-CH3

4-O-6683

MIM12-CH4

4-O-6686

MIM12-CH5

4-O-6687

MIM12-CH6

4-O-6690

MIM13-CH1

4-O-6698

MIM13-CH2

4-O-6701

MIM13-CH3

4-O-6702

MIM13-CH4

4-O-6705

MIM13-CH5

4-O-6706

MIM13-CH6

4-O-6709

MIM14-CH1

4-O-6717

MIM14-CH2

4-O-6720

MIM14-CH3

4-O-6721

MIM14-CH4

4-O-6724

MIM14-CH5

4-O-6725

MIM14-CH6

4-O-6728

MIM15-CH1

4-O-6736

MIM15-CH2

4-O-6739

MIM15-CH3

4-O-6740

MIM15-CH4

4-O-6743

MIM15-CH5

4-O-6744

MIM15-CH6

4-O-6747

MIM16-CH1

4-O-6755

MIM16-CH2

4-O-6758

MIM16-CH3

4-O-6759

MIM16-CH4

4-O-6762

MIM16-CH5

4-O-6763

MIM16-CH6

4-O-6766

The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are
found in table 624.
Table 624:
Function block

SPA addresses for the PCGGIO function


SPA address CNT_VAL

SPA address NEW_VAL

PCGGIO:1

3-O-5834

3-O-5833

PCGGIO:2

3-O-5840

3-O-5839

PCGGIO:3

3-O-5846

3-O-5845

PCGGIO:4

3-O-5852

3-O-5851

PCGGIO:5

3-O-5858

3-O-5857

PCGGIO:6

3-O-5864

3-O-5863

Table continues on next page


930
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function block

SPA address CNT_VAL

SPA address NEW_VAL

PCGGIO:7

3-O-5870

3-O-5869

PCGGIO:8

3-O-5876

3-O-5875

PCGGIO:9

3-O-5882

3-O-5881

PCGGIO:10

3-O-5888

3-O-5887

PCGGIO:11

3-O-5894

3-O-5893

PCGGIO:12

3-O-5900

3-O-5899

PCGGIO:13

3-O-5906

3-O-5905

PCGGIO:14

3-O-5912

3-O-5911

PCGGIO:15

3-O-5918

3-O-5917

PCGGIO:16

3-O-5924

3-O-5923

I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module
function block are used, that is, the addresses for BI1 BI16. For SPA addresses,
refer to section "Related documents".
Single command, 16 signals
The IEDs can be provided with a function to receive signals either from a
substation automation system or from the local HMI. That receiving function block
has 16 outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.
Single command, 16 signals function consists of three function blocks;
SINGLECMD:1 to SINGLECMD:3 for 16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals
function block, SINGLECMD:1 to SINGLECMD:3, the address is for the first
output. The other outputs follow consecutively after the first one. For example,
output 7 on the SINGLECMD:2 function block has the 5O533 address.
The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to
SINGLECMD:3 are found in table 625.
Table 625:

SPA addresses for SINGLECMD function

Function block

SPA address CMD Input

SPA address CMD output

SINGLECMD1-Cmd1

4-S-4639

5-O-511

SINGLECMD1-Cmd2

4-S-4640

5-O-512

SINGLECMD1-Cmd3

4-S-4641

5-O-513

SINGLECMD1-Cmd4

4-S-4642

5-O-514

SINGLECMD1-Cmd5

4-S-4643

5-O-515

SINGLECMD1-Cmd6

4-S-4644

5-O-516

SINGLECMD1-Cmd7

4-S-4645

5-O-517

Table continues on next page


931
Technical reference manual

Section 17
Station communication
Function block

1MRK 505 222-UEN B

SPA address CMD Input

SPA address CMD output

SINGLECMD1-Cmd8

4-S-4646

5-O-518

SINGLECMD1-Cmd9

4-S-4647

5-O-519

SINGLECMD1-Cmd10

4-S-4648

5-O-520

SINGLECMD1-Cmd11

4-S-4649

5-O-521

SINGLECMD1-Cmd12

4-S-4650

5-O-522

SINGLECMD1-Cmdt13

4-S-4651

5-O-523

SINGLECMD1-Cmd14

4-S-4652

5-O-524

SINGLECMD1-Cmd15

4-S-4653

5-O-525

SINGLECMD1-Cmd16

4-S-4654

5-O-526

SINGLECMD2-Cmd1

4-S-4672

5-O-527

SINGLECMD2-Cmd2

4-S-4673

5-O-528

SINGLECMD2-Cmdt3

4-S-4674

5-O-529

SINGLECMD2-Cmd4

4-S-4675

5-O-530

SINGLECMD2-Cmd5

4-S-4676

5-O-531

SINGLECMD2-Cmd6

4-S-4677

5-O-532

SINGLECMD2-Cmd7

4-S-4678

5-O-533

SINGLECMD2-Cmd8

4-S-4679

5-O-534

SINGLECMD2-Cmd9

4-S-4680

5-O-535

SINGLECMD2-Cmd10

4-S-4681

5-O-536

SINGLECMD2-Cmd11

4-S-4682

5-O-537

SINGLECMD2-Cmd12

4-S-4683

5-O-538

SINGLECMD2-Cmd13

4-S-4684

5-O-539

SINGLECMD2-Cmd14

4-S-4685

5-O-540

SINGLECMD2-Cmd15

4-S-4686

5-O-541

SINGLECMD2-Cmd16

4-S-4687

5-O-542

SINGLECMD3-Cmd1

4-S-4705

5-O-543

SINGLECMD3-Cmd2

4-S-4706

5-O-544

SINGLECMD3-Cmd3

4-S-4707

5-O-545

SINGLECMD3-Cmd4

4-S-4708

5-O-546

SINGLECMD3-Cmd5

4-S-4709

5-O-547

SINGLECMD3-Cmd6

4-S-4710

5-O-548

SINGLECMD3-Cmd7

4-S-4711

5-O-549

SINGLECMD3-Cmd8

4-S-4712

5-O-550

SINGLECMD3-Cmd9

4-S-4713

5-O-551

SINGLECMD3-Cmd10

4-S-4714

5-O-552

SINGLECMD3-Cmd11

4-S-4715

5-O-553

SINGLECMD3-Cmd12

4-S-4716

5-O-554

SINGLECMD3-Cmd13

4-S-4717

5-O-555

Table continues on next page

932
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function block

SPA address CMD Input

SPA address CMD output

SINGLECMD3-Cmd14

4-S-4718

5-O-556

SINGLECMD3-Cmd15

4-S-4719

5-O-557

SINGLECMD3-Cmd16

4-S-4720

5-O-558

Figure 494 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
IED for control of a circuit breaker.
A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 OUT16 in SINGLECMD:
1 are shown in table 625.
PULSETIMER

SINGLECMD
BLOCK

INPUT

^OUT1
^OUT2

#1.000

OUT

To output board, CLOSE

^OUT3
^OUT4
^OUT5
^OUT6
^OUT8
^OUT9
^OUT10
^OUT11

PULSETIMER

AND

^OUT7
INPUT1
INPUT2
INPUT3
INPUT4N

OUT
NOUT

INPUT
#1.000

OUT

To output board, OPEN

^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

SYNCH OK

IEC05000717-2-en.vsd
IEC05000717 V2 EN

Figure 494:

Application example showing a simplified logic diagram for control


of a circuit breaker

The MODE input defines if the output signals from SINGLECMD:1 is off, steady
or pulsed signals. This is set in Parameter Setting Tool (PST) under: Setting /
General Settings / Control / Commands / Single Command.
Event function
Event function is intended to send time-tagged events to the station level (for
example, operator workplace) over the station bus. The events are there presented
in an event list. The events can be created from both internal logical signals and
binary input channels. All the internal signals are time tagged in the main
processing module, while the binary input channels are time tagged directly on
each I/O module. The events are produced according to the set event masks. The
event masks are treated commonly for both the LON and SPA channels. All events
according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest
event is overwritten and an overflow alarm appears.
Two special signals for event registration purposes are available in the IED,
Terminal Restarted (0E50) and Event buffer overflow (0E51).
933
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

The input parameters can be set individually from the Parameter Setting Tool
(PST) under: Setting / General Setting / Monitoring / Event Function as follows:

No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)

The Status and event codes for the Event functions are found in table 626.
Table 626:
Event block

Status and event codes


Status

Single indication1)
Set event
Reset
event

Double indication
Intermedi Closed 10 Open 01 Undefined
ate 00
11

EVENT:1
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16

22O1
22O2
22O3
22O4
22O5
22O6
22O7
22O8
22O9
22O10
22O11
22O12
22O13
22O14
22O15
22O16

22E33
22E35
22E37
22E39
22E41
22E43
22E45
22E47
22E49
22E51
22E53
22E55
22E57
22E59
22E61
22E63

22E32
22E34
22E36
22E38
22E40
22E42
22E44
22E46
22E48
22E50
22E52
22E54
22E56
22E58
22E60
22E62

22E0
22E4
22E8
22E12
22E16
22E20
22E24
22E28
-

22E1
22E5
22E9
22E13
22E17
22E21
22E25
22E29
-

22E2
22E6
22E10
22E14
22E18
22E22
22E26
22E30
-

22E3
22E7
22E11
22E15
22E19
22E23
22E27
22E31
-

EVENT:2
EVENT:3
EVENT:20

230..
240..
410..

23E..
24E..
41E..

23E..
24E..
41E..

23E..
24E..
41E..

23E..
23E..
41E..

23E..
24E..
41E..

23E..
24E..
41E..

These values are only applicable if the Event mask is masked OFF.
Connection of signals as events
Signals coming from different protection and control functions and must be sent as
events to the station level over the SPA-bus (or LON-bus) are connected to the
Event function block according to figure 495.

934
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

EVENT
Block
ILRANG
PSTO
UL12RANG
UL23RANG
UL31RANG
3I0RANG
3U0RANG
FALSE

BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC07000065-2-en.vsd
IEC07000065 V2 EN

Figure 495:

17.5.2.1

Connection of protection signals for event handling

Communication ports
The serial communication module (SLM) is used for SPA /IEC 60870-5-103/DNP
and LON communication. This module is a mezzanine module, and can be placed
on the Analog/Digital conversion module (ADM). The serial communication
module can have connectors for two plastic fibre cables (snap-in) or two glass fibre
cables (ST, bayonet) or a combination of plastic and glass fibre. Three different
types are available depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.
The procedure to set the transfer rate and slave number can be found in the
Installation and commissioning manual for respective IEDs.

17.5.3

Design
When communicating locally with a computer (PC) in the station, using the rear
SPA port, the only hardware needed for a station monitoring system is:

Optical fibres
Opto/electrical converter for the PC
PC

When communicating remotely with a PC using the rear SPA port, the same
hardware and telephone modems are needed.
The software needed in the PC, either local or remote, is PCM600.
When communicating between the local HMI and a PC, the only hardware required
is a front-connection cable.
935
Technical reference manual

Section 17
Station communication
17.5.4
Table 627:
Name

1MRK 505 222-UEN B

Setting parameters
SPA Non group settings (basic)
Values (Range)

Unit

Step

Default

Description

SlaveAddress

1 - 899

30

Slave address

BaudRate

300 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

9600 Bd

Baudrate on serial line

Table 628:
Name

LONSPA Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

Operation

Off
On

Off

Operation

SlaveAddress

1 - 899

30

Slave address

17.5.5

Technical data
Table 629:

SPA communication protocol

Function

Value

Protocol

SPA

Communication speed

300, 1200, 2400, 4800, 9600, 19200 or 38400


Bd

Slave number

1 to 899

17.6

IEC 60870-5-103 communication protocol

17.6.1

Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.

17.6.2

Principle of operation

17.6.2.1

General
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data
transfer rate up to 38400 bit/s. In IEC terminology, a primary station is a master

936
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

and a secondary station is a slave. The communication is based on a point-to-point


principle. The master must have software that can interpret IEC 60870-5-103
communication messages.

Introduction to IEC 608705103 protocol

IEC 60870-5-103 protocol functionality consists of the following functions:

Event handling
Report of analog service values (measurements)
Fault location
Command handling

Autorecloser ON/OFF
Teleprotection ON/OFF
Protection ON/OFF
LED reset
Characteristics 1 - 4 (Setting groups)

File transfer (disturbance files)


Time synchronization

For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard
part 5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.

IEC 60870-5-103 vendor specific implementation

The signal and setting tables specify the information types supported by the IEDs
with the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in
the protection and control IED.
Commands in control direction
Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Info. no

Message

Supported

19

LED Reset

Yes

23

Activate setting group 1

Yes

24

Activate setting group 2

Yes

25

Activate setting group 3

Yes

26

Activate setting group 4

Yes

937
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function commands in control direction, pre-defined I103CMD


Function command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signals.
Info. no.

Message

Supported

16

Auto-recloser on/off

Yes

17

Teleprotection on/off

Yes

18

Protection on/off

Yes

Function commands in control direction, user-defined, I103UserCMD


Function command blocks in control direction with user-defined output signals.
Number of instances: 4
Function type for each function block instance in private range is selected with
parameter FunctionType. Default values are defined in private range 1 - 4. One for
each instance.
Information number must be selected for each output signal. Default values are 1 - 8.
Info. no.

Message

Supported

Output signal 01

Yes

Output signal 02

Yes

Output signal 03

Yes

Output signal 04

Yes

Output signal 05

Yes

Output signal 06

Yes

Output signal 07

Yes

Output signal 08

Yes

Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signals.

938
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Info. no.

Message

Supported

19

LED reset

Yes

20

Monitor direction blocked

No

21

TestMode

22

Local Parameter setting

23

Setting group 1 active

Yes

24

Setting group 2 active

Yes

25

Setting group 3 active

Yes

26

Setting group 4 active

Yes

Function status indications in monitor direction, user-defined, I103UserDef


Function indication blocks in monitor direction with user-defined input signals.
Number of instances: 20
Function type is selected with parameter FunctionType for each function block
instance in private range. Default values are defined in private range 5 - 24. One
for each instance.
Information number is required for each input signal. Default values are defined in
range 1 - 8.
Supervision indications in monitor direction, I103Superv
Indication block for supervision in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for output signals.
Earth fault indications in monitor direction, I103EF
Indication block for earth fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Info. no.

Message

Supported

48

Earth fault L1

No

49

Earth fault L2

No

50

Earth fault L3

No

51

Earth fault forward

Yes

52

Earth fault reverse

Yes

Fault indications in monitor direction, type 1, I103FltDis


939
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for distance protection function.
FUNCTION TYPE parameter for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.

Message

Supported

64

Start L1

Yes

65

Start L2

Yes

66

Start L3

Yes

67

Start IN

Yes

84

General start

Yes

69

Trip L1

Yes

70

Trip L2

Yes

71

Trip L3

Yes

68

General trip

Yes

74

Fault forward/line

Yes

75

Fault reverse/busbar

Yes

78

Zone 1

Yes

79

Zone 2

Yes

80

Zone 3

Yes

81

Zone 4

Yes

82

Zone 5

Yes

76

Signal transmitted

Yes

77

Signal received

Yes

73

SCL, Fault location in ohm

Yes

Fault indications in monitor direction, type 2, I103FltStd


Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for line differential, transformer differential,
overcurrent and earth fault protection functions.
FUNCTION TYPE setting for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1

940
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Info. no.

Message

Supported

64

Start L1

Yes

65

Start L2

Yes

66

Start L3

Yes

67

Start IN

Yes

84

General start

Yes

69

Trip L1

Yes

70

Trip L2

Yes

71

Trip L3

Yes

68

General trip

Yes

74

Fault forward/line

Yes

75

Fault reverse/busbar

Yes

85

Breaker failure

Yes

86

Trip measuring system L1

Yes

87

Trip measuring system L2

Yes

88

Trip measuring system L3

Yes

89

Trip measuring system N

Yes

90

Over current trip I>

Yes

91

Over current trip I>>

Yes

92

Earth fault trip IN>

Yes

93

Earth fault trip IN>>

Yes

Autorecloser indications in monitor direction, I103AR


Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Info. no.

Message

Supported

16

Autorecloser active

Yes

17

Teleprotection active

No

18

Protection active

No

128

CB on by Autorecloser

Yes

129

CB on by long-time AR

No

130

Autorecloser blocked

Yes

Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.

941
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Measurands in public range, I103Meas


Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no.

Message

Supported

148

IL1

Yes

144, 145,
148

IL2

Yes

148

IL3

Yes

147

IN, Neutral current

Yes

148

UL1

Yes

148

UL2

Yes

148

UL3

Yes

145, 146

UL1-UL2

Yes

147

UN, Neutral voltage

Yes

146, 148

P, active power

Yes

146, 148

Q, reactive power

Yes

148

f, frequency

Yes

Measurands in private range, I103MeasUsr


Number of instances: 3
Function type parameter for each block in private range. Default values are defined
in private range 25 27. One for each instance.
Information number must be selected for measurands.
Info.

Message

*1)

Meas1

Yes

Meas2

Yes

Meas3

Yes

Meas4

Yes

Meas5

Yes

Meas6

Yes

Meas7

Yes

Meas8

Yes

Meas9

Yes

Supported

1) * User defined information number

942
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be
specified. Channels used in the public range are 1 to 8 and with:

IL1 connected to channel 1 on disturbance function block A1RADR


IL2 connected to channel 2 on disturbance function block A1RADR
IL3 connected to channel 3 on disturbance function block A1RADR
IN connected to channel 4 on disturbance function block A1RADR
VL1E connected to channel 5 on disturbance function block A1RADR
VL2E connected to channel 6 on disturbance function block A1RADR
VL3E connected to channel 7 on disturbance function block A1RADR
VEN connected to channel 8 on disturbance function block A1RADR

Channel number used for the remaining 32 analog signals are numbers in the
private range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available
for transfer to the master. A successfully transferred disturbance (acknowledged by
the master) will not be reported to the master again.
When a new disturbance is recorded by the IED a list of available recorded
disturbances will be sent to the master, an updated list of available disturbances can
be sent whenever something has happened to disturbances in this list. For example,
when a disturbance is deteceted (by other client, for example, SPA) or when a new
disturbance has been recorded or when the master has uploaded a disturbance.
Deviations from the standard
Information sent in the disturbance upload is specified by the standard; however,
some of the information are adapted to information available in disturbance
recorder in 670 series.
This section describes all data that is not exactly as specified in the standard.
ASDU23
In list of recorded disturbances (ASDU23) an information element named SOF
(status of fault) exists. This information element consists of 4 bits and indicates
whether:

943
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Bit TP: the protection equipment has tripped during the fault
Bit TM: the disturbance data are currently being transmitted
Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
Bit OTEV: the disturbance data recording has been initiated by another event
than start

The only information that is easily available is test-mode status. The other
information is always set (hard coded) to:
TP

Recorded fault with trip. [1]

TM

Disturbance data waiting for transmission [0]

OTEV

Disturbance data initiated by other events [1]

Another information element in ASDU23 is the FAN (fault number). According to


the standard this is a number that is incremented when a protection function takes
action. In 670 series FAN is equal to disturbance number, which is incremented for
each disturbance.
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault
number in the power system,that is, a fault in the power system with several trip
and auto-reclosing has the same NOF (while the FAN must be incremented). NOF
is in 670 series, just as FAN, equal to disturbance number.
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever
he connects to the corresponding input.

Interoperability, physical layer


Supported
Electrical Interface
EIA RS-485

No

number of loads

No

Optical interface
glass fibre

Yes

plastic fibre
Transmission speed
9600 bit/s

Yes

19200 bit/s

Yes

Link Layer
DFC-bit used

Yes

Table continues on next page


944
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Supported
Connectors
connector F-SMA

No

connector BFOC/2.5

Yes

Interoperability, application layer


Supported
Selection of standard ASDUs in monitoring direction
ASDU

Yes

Time-tagged message

Yes

Time-tagged message with rel. time

Yes

Measurands I

Yes

Time-tagged message with rel. time

Yes

Identification

Yes

Time synchronization

Yes

End of general interrogation

Yes

Measurands II

Yes

10

Generic data

No

11

Generic identification

No

23

List of recorded disturbances

Yes

26

Ready for transm. of disturbance data

Yes

27

Ready for transm. of a channel

Yes

28

Ready for transm of tags

Yes

29

Transmission of tags

Yes

30

Transmission fo disturbance data

Yes

31

End of transmission

Yes

Selection of standard ASDUs in control direction


ASDU

Yes

Time synchronization

Yes

General interrogation

Yes

10

Generic data

No

20

General command

Yes

21

Generic command

No

24

Order for disturbance data transmission

Yes

25

Acknowledgement for distance data transmission

Yes

Selection of basic application functions


Test mode

No

Blocking of monitoring direction

Yes

Table continues on next page

945
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Supported

17.6.2.2

Disturbance data

Yes

Private data

Yes

Generic services

No

Communication ports
The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP
and LON communication. This module is a mezzanine module, and can be placed
on the Analog/Digital conversion module (ADM). The serial communication
module can have connectors for two plastic fibre cables (snap-in) or two glass fibre
cables (ST, bayonet) or a combination of plastic and glass fibre. Three different
types are available depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out,
pay special attention to the instructions concerning the handling and connection of
the optical fibres. The module is identified with a number on the label on the module.

17.6.3

Function block
BLOCK
FUNTYPE

I103IEDCMD
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC05000689-2-en.vsd

IEC05000689 V2 EN

I103CMD
BLOCK
FUNTYPE

16-AR
17-DIFF
18-PROT
IEC05000684-2-en.vsd

IEC05000684 V2 EN

I103USRCMD
BLOCK
OUTPUT1
PULSEMOD
OUTPUT2
T
OUTPUT3
FUNTYPE
OUTPUT4
INFNO_1
OUTPUT5
INFNO_2
OUTPUT6
INFNO_3
OUTPUT7
INFNO_4
OUTPUT8
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000693-2-en.vsd
IEC05000693 V2 EN

946
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
FUNTYPE
IEC05000688-2-en.vsd
IEC05000688 V2 EN

I103USRDEF
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
FUNTYPE
INFNO_1
INFNO_2
INFNO_3
INFNO_4
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000694-2-en.vsd
IEC05000694 V2 EN

I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
FUNTYPE
IEC05000692-2-en.vsd
IEC05000692 V2 EN

I103EF
BLOCK
51_EFFW
52_EFREV
FUNTYPE
IEC05000685-2-en.vsd
IEC05000685 V2 EN

947
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

I103FLTDIS
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
FUNTYPE
IEC05000686-2-en.vsd
IEC05000686 V2 EN

I103FLTSTD
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FUNTYPE
IEC05000687-2-en.vsd
IEC05000687 V2 EN

I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
FUNTYPE
IEC05000683-2-en.vsd
IEC05000683 V2 EN

948
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
FUNTYPE
IEC05000690-2-en.vsd
IEC05000690 V2 EN

I103MEASUSR
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
FUNTYPE
INFNO
IEC05000691-2-en.vsd
IEC05000691 V2 EN

17.6.4

Input and output signals


Table 630:
Name
BLOCK

Table 631:
Name

I103IEDCMD Input signals


Type
BOOLEAN

Default
0

Description
Block of commands

I103IEDCMD Output signals


Type

Description

19-LEDRS

BOOLEAN

Information number 19, reset LEDs

23-GRP1

BOOLEAN

Information number 23, activate setting group 1

24-GRP2

BOOLEAN

Information number 24, activate setting group 2

25-GRP3

BOOLEAN

Information number 25, activate setting group 3

26-GRP4

BOOLEAN

Information number 26, activate setting group 4

Table 632:
Name
BLOCK

I103CMD Input signals


Type
BOOLEAN

Default
0

Description
Block of commands

949
Technical reference manual

Section 17
Station communication

Table 633:
Name

1MRK 505 222-UEN B

I103CMD Output signals


Type

Description

16-AR

BOOLEAN

Information number 16, block of autorecloser

17-DIFF

BOOLEAN

Information number 17, block of differential


protection

18-PROT

BOOLEAN

Information number 18, block of protection

Table 634:
Name
BLOCK

Table 635:
Name

I103USRCMD Input signals


Type

Default

BOOLEAN

Description
Block of commands

I103USRCMD Output signals


Type

Description

OUTPUT1

BOOLEAN

Command output 1

OUTPUT2

BOOLEAN

Command output 2

OUTPUT3

BOOLEAN

Command output 3

OUTPUT4

BOOLEAN

Command output 4

OUTPUT5

BOOLEAN

Command output 5

OUTPUT6

BOOLEAN

Command output 6

OUTPUT7

BOOLEAN

Command output 7

OUTPUT8

BOOLEAN

Command output 8

Table 636:
Name

I103IED Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

19_LEDRS

BOOLEAN

Information number 19, reset LEDs

23_GRP1

BOOLEAN

Information number 23, setting group 1 is active

24_GRP2

BOOLEAN

Information number 24, setting group 2 is active

25_GRP3

BOOLEAN

Information number 25, setting group 3 is active

26_GRP4

BOOLEAN

Information number 26, setting group 4 is active

21_TESTM

BOOLEAN

Information number 21, test mode is active

Table 637:
Name

I103USRDEF Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

INPUT1

BOOLEAN

Binary signal Input 1

INPUT2

BOOLEAN

Binary signal input 2

INPUT3

BOOLEAN

Binary signal input 3

Table continues on next page

950
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Type

Default

Description

INPUT4

BOOLEAN

Binary signal input 4

INPUT5

BOOLEAN

Binary signal input 5

INPUT6

BOOLEAN

Binary signal input 6

INPUT7

BOOLEAN

Binary signal input 7

INPUT8

BOOLEAN

Binary signal input 8

Table 638:
Name

I103SUPERV Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

32_MEASI

BOOLEAN

Information number 32, measurand supervision of


I

33_MEASU

BOOLEAN

Information number 33, measurand supervision of


U

37_IBKUP

BOOLEAN

Information number 37, I high-high back-up


protection

38_VTFF

BOOLEAN

Information number 38, fuse failure VT

46_GRWA

BOOLEAN

Information number 46, group warning

47_GRAL

BOOLEAN

Information number 47, group alarm

Table 639:
Name

I103EF Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

51_EFFW

BOOLEAN

Information number 51, earth-fault forward

52_EFREV

BOOLEAN

Information number 52, earth-fault reverse

Table 640:
Name

I103FLTDIS Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

64_STL1

BOOLEAN

Information number 64, start phase L1

65_STL2

BOOLEAN

Information number 65, start phase L2

66_STL3

BOOLEAN

Information number 66, start phase L3

67_STIN

BOOLEAN

Information number 67, start residual current IN

84_STGEN

BOOLEAN

Information number 84, start general

69_TRL1

BOOLEAN

Information number 69, trip phase L1

70_TRL2

BOOLEAN

Information number 70, trip phase L2

71_TRL3

BOOLEAN

Information number 71, trip phase L3

68_TRGEN

BOOLEAN

Information number 68, trip general

74_FW

BOOLEAN

Information number 74, forward/line

75_REV

BOOLEAN

Information number 75, reverse/bus

Table continues on next page


951
Technical reference manual

Section 17
Station communication
Name

1MRK 505 222-UEN B

Type

Default

Description

78_ZONE1

BOOLEAN

Information number 78, zone 1

79_ZONE2

BOOLEAN

Information number 79, zone 2

80_ZONE3

BOOLEAN

Information number 79, zone 3

81_ZONE4

BOOLEAN

Information number 79, zone 4

82_ZONE5

BOOLEAN

Information number 79, zone 5

76_TRANS

BOOLEAN

Information number 76, signal transmitted

77_RECEV

BOOLEAN

Information number 77, signal recevied

73_SCL

REAL

Information number 73, fault location in ohm

FLTLOC

BOOLEAN

Faultlocator faultlocation valid (LMBRFLOCALCMADE)

ARINPROG

BOOLEAN

Autorecloser in progress (SMBRREC- INPROGR)

Table 641:
Name

I103FLTSTD Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

64_STL1

BOOLEAN

Information number 64, start phase L1

65_STL2

BOOLEAN

Information number 65, start phase L2

66_STL3

BOOLEAN

Information number 66, start phase L3

67_STIN

BOOLEAN

Information number 67, start residual curent IN

84_STGEN

BOOLEAN

Information number 84, start general

69_TRL1

BOOLEAN

Information number 69, trip phase L1

70_TRL2

BOOLEAN

Information number 70, trip phase L2

71_TRL3

BOOLEAN

Information number 71, trip phase L3

68_TRGEN

BOOLEAN

Information number 68, trip general

74_FW

BOOLEAN

Information number 74, forward/line

75_REV

BOOLEAN

Information number 75, reverse/bus

85_BFP

BOOLEAN

Information number 85, breaker failure

86_MTRL1

BOOLEAN

Information number 86, trip measuring system


phase L1

87_MTRL2

BOOLEAN

Information number 87, trip measuring system


phase L2

88_MTRL3

BOOLEAN

Information number 88, trip measuring system


phase L3

89_MTRN

BOOLEAN

Information number 89, trip measuring system


neutral N

90_IOC

BOOLEAN

Information number 90, over current trip, stage low

91_IOC

BOOLEAN

Information number 91, over current trip, stage high

92_IEF

BOOLEAN

Information number 92, earth-fault trip, stage low

93_IEF

BOOLEAN

Information number 93, earth-fault trip, stage high

ARINPROG

BOOLEAN

Autorecloser in progress (SMBRREC- INPROGR)

952
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Table 642:
Name

I103AR Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of status reporting

16_ARACT

BOOLEAN

Information number 16, auto-recloser active

128_CBON

BOOLEAN

Information number 128, circuit breaker on by autorecloser

130_UNSU

BOOLEAN

Information number 130, unsuccessful reclosing

Table 643:
Name

I103MEAS Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of service value reporting

IL1

REAL

0.0

Service value for current phase L1

IL2

REAL

0.0

Service value for current phase L2

IL3

REAL

0.0

Service value for current phase L3

IN

REAL

0.0

Service value for residual current IN

UL1

REAL

0.0

Service value for voltage phase L1

UL2

REAL

0.0

Service value for voltage phase L2

UL3

REAL

0.0

Service value for voltage phase L3

UL1L2

REAL

0.0

Service value for voltage phase-phase L1-L2

UN

REAL

0.0

Service value for residual voltage UN

REAL

0.0

Service value for active power

REAL

0.0

Service value for reactive power

REAL

0.0

Service value for system frequency

Table 644:
Name

I103MEASUSR Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of service value reporting

INPUT1

REAL

0.0

Service value for measurement on input 1

INPUT2

REAL

0.0

Service value for measurement on input 2

INPUT3

REAL

0.0

Service value for measurement on input 3

INPUT4

REAL

0.0

Service value for measurement on input 4

INPUT5

REAL

0.0

Service value for measurement on input 5

INPUT6

REAL

0.0

Service value for measurement on input 6

INPUT7

REAL

0.0

Service value for measurement on input 7

INPUT8

REAL

0.0

Service value for measurement on input 8

INPUT9

REAL

0.0

Service value for measurement on input 9

953
Technical reference manual

Section 17
Station communication
17.6.5
Table 645:

1MRK 505 222-UEN B

Setting parameters
IEC60870-5-103 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SlaveAddress

0 - 255

30

Slave address

BaudRate

9600 Bd
19200 Bd

9600 Bd

Baudrate on serial line

RevPolarity

Off
On

On

Invert polarity

CycMeasRepTime

1.0 - 3600.0

0.1

5.0

Cyclic reporting time of measurments

Table 646:
Name
FUNTYPE

Table 647:
Name
FUNTYPE

Table 648:
Name

I103IEDCMD Non group settings (basic)


Values (Range)
1 - 255

Unit
FunT

Step
1

Default
255

Description
Function type (1-255)

I103CMD Non group settings (basic)


Values (Range)
1 - 255

Unit
FunT

Step
1

Default
1

Description
Function type (1-255)

I103USRCMD Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

PULSEMOD

0-1

Mode

Pulse mode 0=Steady, 1=Pulsed

0.200 - 60.000

0.001

0.400

Pulse length

FUNTYPE

1 - 255

FunT

Function type (1-255)

INFNO_1

1 - 255

InfNo

Information number for output 1 (1-255)

INFNO_2

1 - 255

InfNo

Information number for output 2 (1-255)

INFNO_3

1 - 255

InfNo

Information number for output 3 (1-255)

INFNO_4

1 - 255

InfNo

Information number for output 4 (1-255)

INFNO_5

1 - 255

InfNo

Information number for output 5 (1-255)

INFNO_6

1 - 255

InfNo

Information number for output 6 (1-255)

INFNO_7

1 - 255

InfNo

Information number for output 7 (1-255)

INFNO_8

1 - 255

InfNo

Information number for output 8 (1-255)

Table 649:
Name
FUNTYPE

I103IED Non group settings (basic)


Values (Range)
1 - 255

Unit
FunT

Step
1

Default
1

Description
Function type (1-255)

954
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Table 650:

I103USRDEF Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

FUNTYPE

1 - 255

FunT

Function type (1-255)

INFNO_1

1 - 255

InfNo

Information number for binary input 1


(1-255)

INFNO_2

1 - 255

InfNo

Information number for binary input 2


(1-255)

INFNO_3

1 - 255

InfNo

Information number for binary input 3


(1-255)

INFNO_4

1 - 255

InfNo

Information number for binary input 4


(1-255)

INFNO_5

1 - 255

InfNo

Information number for binary input 5


(1-255)

INFNO_6

1 - 255

InfNo

Information number for binary input 6


(1-255)

INFNO_7

1 - 255

InfNo

Information number for binary input 7


(1-255)

INFNO_8

1 - 255

InfNo

Information number for binary input 8


(1-255)

Table 651:

I103SUPERV Non group settings (basic)

Name

Values (Range)

FUNTYPE

Table 652:

1 - 255

Values (Range)

FUNTYPE

1 - 255

Values (Range)

FUNTYPE

1 - 255

Default
1

Description
Function type (1-255)

Unit
FunT

Step
1

Default
160

Description
Function type (1-255)

Unit
FunT

Step
1

Default
128

Description
Function type (1-255)

I103FLTSTD Non group settings (basic)

Name

Values (Range)

FUNTYPE

Table 655:

Step

I103FLTDIS Non group settings (basic)

Name

Table 654:

FunT

I103EF Non group settings (basic)

Name

Table 653:

Unit

1 - 255

Unit
FunT

Step
1

Default
1

Description
Function type (1-255)

I103AR Non group settings (basic)

Name
FUNTYPE

Values (Range)
1 - 255

Unit
FunT

Step
1

Default
1

Description
Function type (1-255)

955
Technical reference manual

Section 17
Station communication

Table 656:
Name

1MRK 505 222-UEN B

I103MEAS Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

RatedIL1

1 - 99999

3000

Rated current phase L1

RatedIL2

1 - 99999

3000

Rated current phase L2

RatedIL3

1 - 99999

3000

Rated current phase L3

RatedIN

1 - 99999

3000

Rated residual current IN

RatedUL1

0.05 - 2000.00

kV

0.05

230.00

Rated voltage for phase L1

RatedUL2

0.05 - 2000.00

kV

0.05

230.00

Rated voltage for phase L2

RatedUL3

0.05 - 2000.00

kV

0.05

230.00

Rated voltage for phase L3

RatedUL1-UL2

0.05 - 2000.00

kV

0.05

400.00

Rated voltage for phase-phase L1-L2

RatedUN

0.05 - 2000.00

kV

0.05

230.00

Rated residual voltage UN

RatedP

0.00 - 2000.00

MW

0.05

1200.00

Rated value for active power

RatedQ

0.00 - 2000.00

MVA

0.05

1200.00

Rated value for reactive power

RatedF

50.0 - 60.0

Hz

10.0

50.0

Rated system frequency

FUNTYPE

1 - 255

FunT

Function type (1-255)

Table 657:
Name

I103MEASUSR Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

FUNTYPE

1 - 255

FunT

25

Function type (1-255)

INFNO

1 - 255

InfNo

Information number for measurands


(1-255)

RatedMeasur1

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 1

RatedMeasur2

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 2

RatedMeasur3

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 3

RatedMeasur4

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 4

RatedMeasur5

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 5

RatedMeasur6

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 6

RatedMeasur7

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 7

RatedMeasur8

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 8

RatedMeasur9

0.05 10000000000.00

0.05

1000.00

Rated value for measurement on input 9

956
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

17.6.6

Technical data
Table 658:

IEC60870-5-103 communication protocol

Function

Value

Protocol

IEC 60870-5-103

Communication speed

9600, 19200 Bd

17.7

Horizontal communication via GOOSE for


interlocking GOOSEINTLKRCV

17.7.1

Function block
GOOSEINTLKRCV
BLOCK
^RESREQ
^RESGRANT
^APP1_OP
^APP1_CL
APP1VAL
^APP2_OP
^APP2_CL
APP2VAL
^APP3_OP
^APP3_CL
APP3VAL
^APP4_OP
^APP4_CL
APP4VAL
^APP5_OP
^APP5_CL
APP5VAL
^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COM_VAL
IEC07000048-2-en.vsd
IEC07000048 V2 EN

Figure 496:

GOOSEINTLKRCV function block


957

Technical reference manual

Section 17
Station communication
17.7.2

1MRK 505 222-UEN B

Input and output signals


Table 659:
Name
BLOCK

Table 660:
Name

GOOSEINTLKRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of output signals

GOOSEINTLKRCV Output signals


Type

Description

RESREQ

BOOLEAN

Reservation request

RESGRANT

BOOLEAN

Reservation granted

APP1_OP

BOOLEAN

Apparatus 1 position is open

APP1_CL

BOOLEAN

Apparatus 1 position is closed

APP1VAL

BOOLEAN

Apparatus 1 position is valid

APP2_OP

BOOLEAN

Apparatus 2 position is open

APP2_CL

BOOLEAN

Apparatus 2 position is closed

APP2VAL

BOOLEAN

Apparatus 2 position is valid

APP3_OP

BOOLEAN

Apparatus 3 position is open

APP3_CL

BOOLEAN

Apparatus 3 position is closed

APP3VAL

BOOLEAN

Apparatus 3 position is valid

APP4_OP

BOOLEAN

Apparatus 4 position is open

APP4_CL

BOOLEAN

Apparatus 4 position is closed

APP4VAL

BOOLEAN

Apparatus 4 position is valid

APP5_OP

BOOLEAN

Apparatus 5 position is open

APP5_CL

BOOLEAN

Apparatus 5 position is closed

APP5VAL

BOOLEAN

Apparatus 5 position is valid

APP6_OP

BOOLEAN

Apparatus 6 position is open

APP6_CL

BOOLEAN

Apparatus 6 position is closed

APP6VAL

BOOLEAN

Apparatus 6 position is valid

APP7_OP

BOOLEAN

Apparatus 7 position is open

APP7_CL

BOOLEAN

Apparatus 7 position is closed

APP7VAL

BOOLEAN

Apparatus 7 position is valid

APP8_OP

BOOLEAN

Apparatus 8 position is open

APP8_CL

BOOLEAN

Apparatus 8 position is closed

APP8VAL

BOOLEAN

Apparatus 8 position is valid

APP9_OP

BOOLEAN

Apparatus 9 position is open

APP9_CL

BOOLEAN

Apparatus 9 position is closed

APP9VAL

BOOLEAN

Apparatus 9 position is valid

APP10_OP

BOOLEAN

Apparatus 10 position is open

APP10_CL

BOOLEAN

Apparatus 10 position is closed

APP10VAL

BOOLEAN

Apparatus 10 position is valid

Table continues on next page


958
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

17.7.3
Table 661:

Type

Description

APP11_OP

BOOLEAN

Apparatus 11 position is open

APP11_CL

BOOLEAN

Apparatus 11 position is closed

APP11VAL

BOOLEAN

Apparatus 11 position is valid

APP12_OP

BOOLEAN

Apparatus 12 position is open

APP12_CL

BOOLEAN

Apparatus 12 position is closed

APP12VAL

BOOLEAN

Apparatus 12 position is valid

APP13_OP

BOOLEAN

Apparatus 13 position is open

APP13_CL

BOOLEAN

Apparatus 13 position is closed

APP13VAL

BOOLEAN

Apparatus 13 position is valid

APP14_OP

BOOLEAN

Apparatus 14 position is open

APP14_CL

BOOLEAN

Apparatus 14 position is closed

APP14VAL

BOOLEAN

Apparatus 14 position is valid

APP15_OP

BOOLEAN

Apparatus 15 position is open

APP15_CL

BOOLEAN

Apparatus 15 position is closed

APP15VAL

BOOLEAN

Apparatus 15 position is valid

COM_VAL

BOOLEAN

Receive communication status is valid

Setting parameters
GOOSEINTLKRCV Non group settings (basic)

Name
Operation

Values (Range)
Off
On

Unit
-

Step
-

Default
Off

Description
Operation Off/On

959
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

17.8

Goose binary receive GOOSEBINRCV

17.8.1

Function block
GOOSEBINRCV
BLOCK

^OUT1
OUT1VAL
^OUT2
OUT2VAL
^OUT3
OUT3VAL
^OUT4
OUT4VAL
^OUT5
OUT5VAL
^OUT6
OUT6VAL
^OUT7
OUT7VAL
^OUT8
OUT8VAL
^OUT9
OUT9VAL
^OUT10
OUT10VAL
^OUT11
OUT11VAL
^OUT12
OUT12VAL
^OUT13
OUT13VAL
^OUT14
OUT14VAL
^OUT15
OUT15VAL
^OUT16
OUT16VAL
IEC07000047-2-en.vsd

IEC07000047 V2 EN

Figure 497:

17.8.2

GOOSEBINRCV function block

Input and output signals


Table 662:
Name
BLOCK

Table 663:
Name

GOOSEBINRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of output signals

GOOSEBINRCV Output signals


Type

Description

OUT1

BOOLEAN

Binary output 1

OUT1VAL

BOOLEAN

Valid data on binary output 1

OUT2

BOOLEAN

Binary output 2

OUT2VAL

BOOLEAN

Valid data on binary output 2

OUT3

BOOLEAN

Binary output 3

OUT3VAL

BOOLEAN

Valid data on binary output 3

Table continues on next page

960
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

17.8.3
Table 664:

Type

Description

OUT4

BOOLEAN

Binary output 4

OUT4VAL

BOOLEAN

Valid data on binary output 4

OUT5

BOOLEAN

Binary output 5

OUT5VAL

BOOLEAN

Valid data on binary output 5

OUT6

BOOLEAN

Binary output 6

OUT6VAL

BOOLEAN

Valid data on binary output 6

OUT7

BOOLEAN

Binary output 7

OUT7VAL

BOOLEAN

Valid data on binary output 7

OUT8

BOOLEAN

Binary output 8

OUT8VAL

BOOLEAN

Valid data on binary output 8

OUT9

BOOLEAN

Binary output 9

OUT9VAL

BOOLEAN

Valid data on binary output 9

OUT10

BOOLEAN

Binary output 10

OUT10VAL

BOOLEAN

Valid data on binary output 10

OUT11

BOOLEAN

Binary output 11

OUT11VAL

BOOLEAN

Valid data on binary output 11

OUT12

BOOLEAN

Binary output 12

OUT12VAL

BOOLEAN

Valid data on binary output 12

OUT13

BOOLEAN

Binary output 13

OUT13VAL

BOOLEAN

Valid data on binary output 13

OUT14

BOOLEAN

Binary output 14

OUT14VAL

BOOLEAN

Valid data on binary output 14

OUT15

BOOLEAN

Binary output 15

OUT15VAL

BOOLEAN

Valid data on binary output 15

OUT16

BOOLEAN

Binary output 16

OUT16VAL

BOOLEAN

Valid data on binary output 16

Setting parameters
GOOSEBINRCV Non group settings (basic)

Name
Operation

17.9

Values (Range)
Off
On

Unit
-

Step
-

Default
Off

Description
Operation Off/On

Multiple command and transmit MULTICMDRCV,


MULTICMDSND

961
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Function description

17.9.1

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Multiple command and transmit

MULTICMDRCV

Multiple command and transmit

MULTICMDSND

Introduction
The IED can be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate
with other IEDs, these IEDs have a corresponding Multiple transmit function block
with 16 outputs to send the information received by the command block.

17.9.2

Principle of operation
Two multiple transmit function blocks MULTICMDSND:1 and MULTICMDSND:
2 and 8 slow multiple transmit function blocks MULTICMDSND:3 to
MULTICMDSND:10 are available in the IED.
Sixteen signals can be connected and they will then be sent to the multiple
command block in the other IED. The connections are set with the LON Network
Tool (LNT).
Twelve multiple command function blocks MULTICMDRCV:1 to
MULTICMDRCV:12 with fast execution time and 48 multiple command function
blocks MULTICMDRCV:13 to MULTICMDRCV:60 with slower execution time
are available in the IED.
Multiple command function block MULTICMDRCV has 16 outputs combined in
one block, which can be controlled from other IEDs.
The output signals, here OUTPUT1 to OUTPUT16, are then available for
configuration to built-in functions or via the configuration logic circuits to the
binary outputs of the IED.
MULTICMDRCV also has a supervision function, which sets the output VALID to
0 if the block does not receive data within set maximum time.

17.9.3

Design

17.9.3.1

General
The output signals can be of the types Off, Steady, or Pulse. The setting is done on
the MODE settings, common for the whole block, from PCM600.

962
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

17.9.4

0 = Off sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values
sent from the station level.
2 = Pulse gives a pulse with one execution cycle duration, if a value sent from
the station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer
than the execution cycle time for the command function block.

Function block
MULTICMDRCV
BLOCK

ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
IEC06000007-2-en.vsd

IEC06000007 V2 EN

Figure 498:

MULTICMDRCV function block

MULTICMDSND
BLOCK
ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC06000008-2-en.vsd
IEC06000008 V2 EN

Figure 499:

MULTICMDSND function block

963
Technical reference manual

Section 17
Station communication
17.9.5

1MRK 505 222-UEN B

Input and output signals


Table 665:
Name
BLOCK

Table 666:
Name

MULTICMDRCV Input signals


Type
BOOLEAN

Default
0

Description
Block of function

MULTICMDSND Input signals


Type

Default

Description

BLOCK

BOOLEAN

Block of function

INPUT1

BOOLEAN

Input 1

INPUT2

BOOLEAN

Input 2

INPUT3

BOOLEAN

Input 3

INPUT4

BOOLEAN

Input 4

INPUT5

BOOLEAN

Input 5

INPUT6

BOOLEAN

Input 6

INPUT7

BOOLEAN

Input 7

INPUT8

BOOLEAN

Input 8

INPUT9

BOOLEAN

Input 9

INPUT10

BOOLEAN

Input 10

INPUT11

BOOLEAN

Input 11

INPUT12

BOOLEAN

Input 12

INPUT13

BOOLEAN

Input 13

INPUT14

BOOLEAN

Input 14

INPUT15

BOOLEAN

Input 15

INPUT16

BOOLEAN

Input 16

Table 667:
Name

MULTICMDRCV Output signals


Type

Description

ERROR

BOOLEAN

MultiReceive error

NEWDATA

BOOLEAN

New data is received

OUTPUT1

BOOLEAN

Output 1

OUTPUT2

BOOLEAN

Output 2

OUTPUT3

BOOLEAN

Output 3

OUTPUT4

BOOLEAN

Output 4

OUTPUT5

BOOLEAN

Output 5

OUTPUT6

BOOLEAN

Output 6

OUTPUT7

BOOLEAN

Output 7

OUTPUT8

BOOLEAN

Output 8

OUTPUT9

BOOLEAN

Output 9

Table continues on next page

964
Technical reference manual

Section 17
Station communication

1MRK 505 222-UEN B

Name

Type
BOOLEAN

Output 10

OUTPUT11

BOOLEAN

Output 11

OUTPUT12

BOOLEAN

Output 12

OUTPUT13

BOOLEAN

Output 13

OUTPUT14

BOOLEAN

Output 14

OUTPUT15

BOOLEAN

Output 15

OUTPUT16

BOOLEAN

Output 16

VALID

BOOLEAN

Output data is valid

Table 668:

MULTICMDSND Output signals

Name

Type

ERROR

17.9.6
Table 669:

Description

OUTPUT10

Description

BOOLEAN

MultiSend error

Setting parameters
MULTICMDRCV Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

tMaxCycleTime

0.050 - 200.000

0.001

11.000

Maximum cycle time between receptions


of input data

tMinCycleTime

0.000 - 200.000

0.001

0.000

Minimum cycle time between receptions


of input data

Mode

Steady
Pulsed

Steady

Mode for output signals

tPulseTime

0.000 - 60.000

0.001

0.200

Pulse length for multi command outputs

Table 670:

MULTICMDSND Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

tMaxCycleTime

0.000 - 200.000

0.001

5.000

Maximum time interval between


transmission of output data

tMinCycleTime

0.000 - 200.000

0.001

0.000

Minimum time interval between


transmission of output data

965
Technical reference manual

966

Section 18
Remote communication

1MRK 505 222-UEN B

Section 18

Remote communication

About this chapter


This chapter describes the Binary signal transfer function and associated hardware
functionality. The way the functions work, their setting parameters, function
blocks, input and output signals, and technical data are included for each function.

18.1

Binary signal transfer


Function description

18.1.1

IEC 61850
identification

IEC 60617
identification

ANSI/IEEE C37.2
device number

Binary signal transfer

BinSignReceive

Binary signal transfer

BinSignTransm

Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection,
or for transmission of only binary signals, up to 192 signals, in the other 670 series
IEDs. The binary signals are freely configurable and can, thus, be used for any
purpose, for example, communication scheme related signals, transfer trip and/or
other binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with an
LDCM (Line Data Communication Module). The LDCMs are then interfaces to a
64 kbit/s communication channel for duplex communication between the IEDs.
The IED can be equipped with up to four short range, medium range or long range
LDCM.

18.1.2

Principle of operation
The communication is made on standard ITU (CCITT) PCM digital 64 kbit/s
channels. It is a two-way communication where telegrams are sent every 5 ms
(same in 50 Hz and 60 Hz), exchanging information between two IEDs. The format
used is C37.94 and one telegram consists of start and stop flags, address, data to be
transmitted, Cyclic Redundancy Check (CRC) and Yellow bit (which is associated
with C37.94).

967
Technical reference manual

Section 18
Remote communication

Start
flag
8 bits

1MRK 505 222-UEN B

Information
n x 16 bits

CRC

Stop
flag

16 bits

8 bits

en01000134.vsd
IEC01000134 V1 EN

Figure 500:

Data message structure

The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in
the HDLC standard. The CRC is designed according to the standard CRC16
definition. The optional address field in the HDLC frame is not used instead a
separate addressing is included in the data field.
The address field is used for checking that the received message originates from
the correct equipment. There is always a risk that multiplexers occasionally mix the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC
function detects a faulty message, the message is thrown away and not used in the
evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and
eight binary signals which can be used for any purpose. The three currents are
represented as sampled values.
When the communication is used exclusively for binary signals, the full data
capacity of the communication channel is used for the binary signal purpose which
gives the capacity of 192 signals.

968
Technical reference manual

Section 18
Remote communication

1MRK 505 222-UEN B

18.1.3

Function block
LDCMRecBinStat1
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL
IEC07000043-2-en.vsd
IEC07000043 V2 EN

LDCMRecBinStat2
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC07000044-2-en.vsd
IEC07000044 V2 EN

Figure 501:

LDCMRecBinStat function blocks

LDCMRecBinStat3
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC05000451-2-en.vsd
IEC05000451 V2 EN

Figure 502:

18.1.4

LDCMRecBinStat function block

Input and output signals


Table 671:
Name

LDCMRecBinStat1 Output signals


Type

Description

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming


message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

Table continues on next page

969
Technical reference manual

Section 18
Remote communication
Name

1MRK 505 222-UEN B

Type

Description

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from a wrong terminal

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

LOWLEVEL

BOOLEAN

Low signal level on the receive link

Table 672:
Name

LDCMRecBinStat2 Output signals


Type

Description

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming


message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from a wrong terminal

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

TRDELERR

BOOLEAN

Transmission time is longer than permitted

SYNCERR

BOOLEAN

Indicates when echo synchronication is used

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

REMGPSER

BOOLEAN

Remote terminal indicates problem with GPS


synchronization

SUBSTITU

BOOLEAN

Link error, values are substituted

LOWLEVEL

BOOLEAN

Low signal level on the receive link

Table 673:
Name

LDCMRecBinStat3 Output signals


Type

Description

COMFAIL

BOOLEAN

Detected error in the differential communication

YBIT

BOOLEAN

Detected error in remote end with incoming


message

NOCARR

BOOLEAN

No carrier is detected in the incoming message

NOMESS

BOOLEAN

No start and stop flags identified for the incoming


message

ADDRERR

BOOLEAN

Incoming message from a wrong terminal

LNGTHERR

BOOLEAN

Wrong length of the incoming message

CRCERROR

BOOLEAN

Identified error by CRC check in incoming message

TRDELERR

BOOLEAN

Transmission time is longer than permitted

Table continues on next page

970
Technical reference manual

Section 18
Remote communication

1MRK 505 222-UEN B

Name

18.1.5
Table 674:

Type

Description

SYNCERR

BOOLEAN

Indicates when echo synchronication is used

REMCOMF

BOOLEAN

Remote terminal indicates problem with received


message

REMGPSER

BOOLEAN

Remote terminal indicates problem with GPS


synchronization

SUBSTITU

BOOLEAN

Link error, values are substituted

LOWLEVEL

BOOLEAN

Low signal level on the receive link

Setting parameters
LDCMRecBinStat1 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

ChannelMode

Off
On
OutOfService

On

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low,


1=High

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error


signal is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error


signal is reset

InvertPolX21

Off
On

Off

Invert polarization for X21 communication

Table 675:

LDCMRecBinStat2 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

ChannelMode

Off
On
OutOfService

On

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

NAMECH1

0 - 13

LDCM#-CH1

User define string for analogue input 1

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

NAMECH2

0 - 13

LDCM#-CH2

User define string for analogue input 2

DiffSync

Echo
GPS

Echo

Diff Synchronization mode of LDCM,


0=ECHO, 1=GPS

GPSSyncErr

Block
Echo

Block

Operation mode when GPS


synchroniation signal is lost

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

Table continues on next page


971
Technical reference manual

Section 18
Remote communication
Name

Values (Range)

1MRK 505 222-UEN B

Unit

Step

Default

Description

NAMECH3

0 - 13

LDCM#-CH3

User define string for analogue input 3

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low,


1=High

NAMECH4

0 - 13

LDCM#-CH4

User define string for analogue input 4

TransmCurr

CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2

CT-GRP1

Summation mode for transmitted current


values

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error


signal is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error


signal is reset

RedChSwTime

5 - 500

ms

Time delay before switching in


redundant channel

RedChRturnTime

5 - 500

ms

100

Time delay before switching back from


redundant channel

AsymDelay

-20.00 - 20.00

ms

0.01

0.00

Asymmetric delay when communication


use echo synch.

AnalogLatency

2 - 20

Latency between local analogue data


and transmitted

remAinLatency

2 - 20

Analog latency of remote terminal

MaxTransmDelay

0 - 40

ms

20

Max allowed transmission delay

CompRange

0-10kA
0-25kA
0-50kA
0-150kA

0-25kA

Compression range

MaxtDiffLevel

200 - 2000

us

600

Maximum time diff for ECHO back-up

DeadbandtDiff

200 - 1000

us

300

Deadband for t Diff

InvertPolX21

Off
On

Off

Invert polarization for X21 communication

Table 676:
Name

LDCMRecBinStat3 Non group settings (basic)


Values (Range)

Unit

Step

Default

Description

ChannelMode

Off
On
OutOfService

On

Channel mode of LDCM, 0=OFF, 1=ON,


2=OutOfService

NAMECH1

0 - 13

LDCM#-CH1

User define string for analogue input 1

TerminalNo

0 - 255

Terminal number used for line differential


communication

RemoteTermNo

0 - 255

Terminal number on remote terminal

NAMECH2

0 - 13

LDCM#-CH2

User define string for analogue input 2

DiffSync

Echo
GPS

Echo

Diff Synchronization mode of LDCM,


0=ECHO, 1=GPS

GPSSyncErr

Block
Echo

Block

Operation mode when GPS


synchroniation signal is lost

Table continues on next page

972
Technical reference manual

Section 18
Remote communication

1MRK 505 222-UEN B

Name

Values (Range)

Unit

Step

Default

Description

CommSync

Slave
Master

Slave

Com Synchronization mode of LDCM,


0=Slave, 1=Master

NAMECH3

0 - 13

LDCM#-CH3

User define string for analogue input 3

OptoPower

LowPower
HighPower

LowPower

Transmission power for LDCM, 0=Low,


1=High

NAMECH4

0 - 13

LDCM#-CH4

User define string for analogue input 4

TransmCurr

CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel

CT-GRP1

Summation mode for transmitted current


values

ComFailAlrmDel

5 - 500

ms

100

Time delay before communication error


signal is activated

ComFailResDel

5 - 500

ms

100

Reset delay before communication error


signal is reset

RedChSwTime

5 - 500

ms

Time delay before switching in


redundant channel

RedChRturnTime

5 - 500

ms

100

Time delay before switching back from


redundant channel

AsymDelay

-20.00 - 20.00

ms

0.01

0.00

Asymmetric delay when communication


use echo synch.

AnalogLatency

2 - 20

Latency between local analogue data


and transmitted

remAinLatency

2 - 20

Analog latency of remote terminal

MaxTransmDelay

0 - 40

ms

20

Max allowed transmission delay

CompRange

0-10kA
0-25kA
0-50kA
0-150kA

0-25kA

Compression range

MaxtDiffLevel

200 - 2000

us

600

Maximum time diff for ECHO back-up

DeadbandtDiff

200 - 1000

us

300

Deadband for t Diff

InvertPolX21

Off
On

Off

Invert polarization for X21 communication

973
Technical reference manual

Section 18
Remote communication

1MRK 505 222-UEN B

18.2

Transmission of analog data from LDCM


LDCMTransmit

18.2.1

Function block
LDCMTRN
^CT1L1
^CT1L2
^CT1L3
^CT1N
^CT2L1
^CT2L2
^CT2L3
^CT2N
IEC10000017-1-en.vsd
IEC10000017 V1 EN

Figure 503:

LDCMTransmit function block

The function blocks are not represented in the Application


Configuration tool except for the LDCMTRN function block that is
visible in ACT. The signals appear only in the Signal Matrix tool
when a LDCM is included in the configuration with the function
selector tool.

18.2.2

Input and output signals


Table 677:
Name

LDCMTRN Input signals


Type

Default

Description

CT1L1

STRING

Input to be used for transmit CT-group1 line L1 to


remote end

CT1L2

STRING

Input to be used for transmit CT-group1 line L2 to


remote end

CT1L3

STRING

Input to be used for transmit CT-group1 line L3 to


remote end

CT1N

STRING

Input to be used for transmit CT-group1 neutral N


to remote end

CT2L1

STRING

Input to be used for transmit CT-group2 line L1 to


remote end

CT2L2

STRING

Input to be used for transmit CT-group2 line L2 to


remote end

CT2L3

STRING

Input to be used for transmit CT-group2 line L3 to


remote end

CT2N

STRING

Input to be used for transmit CT-group2 neutral N


to remote end

974
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Section 19

IED hardware

About this chapter


This chapter describes the different hardware modules available in the IED. The
descriptions includes diagrams from different elevations indicating the location of
connection terminals and modules.

19.1

Overview

19.1.1

Variants of case and local HMI display size

xx04000458.ep
IEC04000458 V1 EN

Figure 504:

1/2 19 case with medium local HMI display.

975
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

xx04000459.ep
IEC04000459 V1 EN

Figure 505:

1/2 19 case with small local HMI display.

IEC05000762 V1 EN

Figure 506:

3/4 19 case with medium local HMI display.

xx05000763.eps
IEC05000763 V1 EN

Figure 507:

3/4 19 case with small local HMI display.

976
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

xx04000460.ep
IEC04000460 V1 EN

Figure 508:

1/1 19 case with medium local HMI display.

xx04000461.eps
IEC04000461 V1 EN

Figure 509:

1/1 19 case with small local HMI display.

977
Technical reference manual

Section 19
IED hardware
19.1.2
Table 678:

1MRK 505 222-UEN B

Case from the rear side


Designations for 1/2 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to X51


and X52

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or GTM

X312, 313

TRM

X401

1MRK002801-AC 2 670 1.2 PG V1 EN

978
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 679:

Designations for 3/4 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to


X101 and X102

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or GTM

X312, X313

TRM

X401

1MRK002801-AC 3 670 1.2 PG V1 EN

979
Technical reference manual

Section 19
IED hardware

Table 680:

1MRK 505 222-UEN B

Designations for 3/4 x 19 casing with 2 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM, SOM, IOM or


MIM

X31 and X32 etc. to X71 and


X72

SLM

X301:A, B, C, D

LDCM, IRIG-B or RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or GTM

X312, X313, X322, X323

TRM 1

X401

TRM 2

X411

1MRK002801-AC 4 670 1.2 PG V1 EN

980
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 681:

Designations for 1/1 x 19 casing with 1 TRM slot

Module

Rear Positions

PSM

X11

BIM, BOM,
SOM, IOM or
MIM

X31 and X32 etc. to X161


and X162

SLM

X301:A, B, C, D

LDCM, IRIG-B or
RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM,RS485 or
GTM

X312, X313

TRM

X401

1MRK002801-AC 5 670 1.2 PG V1 EN

981
Technical reference manual

Section 19
IED hardware

Table 682:

1MRK 505 222-UEN B

Designations for 1/1 x 19 casing with 2 TRM slots

Module

Rear Positions

PSM

X11

BIM, BOM,
SOM, IOM or
MIM

X31 and X32 etc. to X131


and X132

SLM

X301:A, B, C, D

LDCM, IRIG-B or
RS485

X302

LDCM or RS485

X303

OEM

X311:A, B, C, D

LDCM, RS485 or
GTM

X312, X313, X322, X323

TRM 1

X401

TRM 2

X411

1MRK002801-AC 6 670 1.2 PG V1 EN

19.2

Hardware modules

19.2.1

Overview
Table 683:

Basic modules

Module

Description

Combined backplane module (CBM)

A backplane PCB that carries all internal signals


between modules in an IED. Only the TRM (when
included) is not connected directly to this board.

Universal backplane module (UBM)

A backplane PCB that forms part of the IED


backplane with connectors for TRM (when
included), ADM etc.

Power supply module (PSM)

Including a regulated DC/DC converter that


supplies auxiliary voltage to all static circuits.

Numerical module (NUM)

An internal fail alarm output is available.

Module for overall application control. All


information is processed or passed through this
module, such as configuration, settings and
communication.

Table continues on next page

982
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Module

Description

Local Human machine interface (LHMI)

The module consists of LED:s, an LCD, a push


button keyboard and an ethernet connector used
to connect a PC to the IED.

Transformer input module (TRM)

Transformer module that galvanically separates


the internal circuits from the VT and CT circuits. It
has 12 analog inputs.

Analog digital conversion module (ADM)

Slot mounted PCB with A/D conversion.

Table 684:

Application specific modules

Module

Description

Binary input module (BIM)

Module with 16 optically isolated binary inputs

Binary output module (BOM)

Module with 24 single outputs or 12 double-pole


command outputs including supervision function

Binary I/O module (IOM)

Module with 8 optically isolated binary inputs, 10


outputs and 2 fast signalling outputs.

Line data communication modules (LDCM),


short range, medium range, long range, X21

Modules used for digital communication to remote


terminal.

Serial SPA/LON/IEC 60870-5-103/DNP3


communication modules (SLM)

Used for SPA/LON/IEC 608705103/DNP3


communication

Optical ethernet module (OEM)

PMC board for IEC 61850 based communication.

mA input module (MIM)

Analog input module with 6 independent,


galvanically separated channels.

GPS time synchronization module (GTM)

Used to provide the IED with GPS time


synchronization.

Static output module (SOM)

Module with 6 fast static outputs and 6 change


over output relays.

IRIG-B Time synchronization module (IRIG-B)

Module with 2 inputs. One is used for handling


both pulse-width modulated signals and
amplitude modulated signals and one is used for
optical input type ST for PPS time synchronization.

19.2.2

Combined backplane module (CBM)

19.2.2.1

Introduction
The combined backplane module (CBM) carries signals between modules in an IED.

19.2.2.2

Functionality
The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The
CBM backplane and connected modules are 5V PCI-compatible.
Some pins on the Compact PCI connector are connected to the CAN bus, to be able
to communicate with CAN based modules.

983
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

If a modules self test discovers an error it informs other modules using the Internal
Fail signal IRF.

19.2.2.3

Design
There are two basic versions of the CBM:

with 3 Compact PCI connectors and a number of euro connectors depending


on the IED case size. One Compact PCI connector is used by NUM and two
are used by other PCI modules, for example two ADMs in IEDs with two
TRMs. See figure 511
with 2 Compact PCI connectors and a number of euro connectors depending
on the IED case size. One Compact PCI connector is used by NUM and one is
used by for example an ADM in IEDs with one TRM. See figure 510

Each PCI connector consists of 2 compact PCI receptacles. The euro connectors
are connected to the CAN bus and used for I/O modules and power supply.

2
en05000516.vsd

IEC05000516 V1 EN

Figure 510:

CBM for 1 TRM.

Pos Description
1

CAN slots

CPCI slots

984
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

en05000755.vsd
IEC05000755 V1 EN

Figure 511:

CBM for 2 TRM.

Pos Description
1

CAN slots

CPCI slots

en05000756.vsd
IEC05000756 V1 EN

Figure 512:

CBM position, rear view.

Pos Description
1

CBM

985
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.3

Universal backplane module (UBM)

19.2.3.1

Introduction
The Universal Backplane Module (UBM) is part of the IED backplane and is
mounted above the CBM. It connects the Transformer input module (TRM) to the
Analog digital conversion module (ADM) and the Numerical module (NUM).

19.2.3.2

Functionality
The Universal Backplane Module connects the CT and VT analog signals from the
transformer input module to the analog digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on
the front panel as well as the internal ethernet contacts are connected to the UBM
which provides the signal path to the NUM board.

19.2.3.3

Design
It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).
The UBM exists in 2 versions.

for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and
one 96 pin euro connector, see figure 514
for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and
one 96 pin euro connector, see figure 515.

The 96 pin euro connector is used to connect the NUM board to the backplane. The
48 pin connectors are used to connect the TRM and ADM.

986
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

TRM

ADM

NUM

AD Data
X1

X2

X3

X4

RS485
X10

X10

Ethernet

Front

LHMI connection
port

Ethernet

X5

en05000489.vsd
IEC05000489 V1 EN

Figure 513:

UBM block diagram.

en05000757.vsd
IEC05000757 V1 EN

Figure 514:

UBM for 1 TRM.

en05000758.vsd
IEC05000758 V1 EN

Figure 515:

UBM for 2 TRM.

987
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

en05000759.vsd
IEC05000759 V1 EN

Figure 516:

UBM position, rear view.

Pos Description
1

UBM

19.2.4

Numeric processing module (NUM)

19.2.4.1

Introduction
The Numeric processing module (NUM), is a CPU-module that handles all
protection functions and logic.
For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM
is the compact PCI system card i.e. it controls bus mastering, clock distribution and
receives interrupts.

19.2.4.2

Functionality
The NUM, Numeric processing module is a high performance, standard off-theshelf compact-PCI CPU module. It is 6U high and occupies one slot. Contact with
the backplane is via two compact PCI connectors and an euro connector.

988
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP
slots onto which mezzanine cards such as SLM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC/PC-MIP slots and external PCI
accesses through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a
flash file system.
The NUM is equipped with a real time clock. It uses a capacitor for power backup
of the real time clock.
No forced cooling is used on this standard module because of the low power
dissipation.

19.2.4.3

Block diagram

Compact
Flash

Logic

PMC
connector

Memory

Ethernet

UBM
connector

PC-MIP

PCI-PCIbridge

Backplane
connector

North
bridge

CPU

en04000473.vsd
IEC04000473 V1 EN

Figure 517:

Numeric processing module block diagram


989

Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.5

Power supply module (PSM)

19.2.5.1

Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output
is available.

19.2.5.2

Design
There are two types of the power supply module. They are designed for different
DC input voltage ranges see table 685. The power supply module contains a builtin, self-regulated DC/DC converter that provides full isolation between the
terminal and the external battery system.

Power
supply

Filter

Backplane connector

Input connector

Block diagram

Supervision

99000516.vsd
IEC99000516 V1 EN

Figure 518:

19.2.5.3

PSM Block diagram.

Technical data
Table 685:

PSM - Power supply module

Quantity

Rated value

Nominal range

Auxiliary dc voltage, EL (input)

EL = (24 - 60) V
EL = (90 - 250) V

EL 20%
EL 20%

Power consumption

50 W typically

Auxiliary DC power in-rush

< 5 A during 0.1 s

990
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.6

Local human-machine interface (Local HMI)


Refer to section "Local HMI" for information.

19.2.7

Transformer input module (TRM)

19.2.7.1

Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The
module has twelve inputs in different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can be ordered.

19.2.7.2

Design
The transformer module has 12 input transformers. There are several versions of
the module, each with a different combination of voltage and current input
transformers.
Basic versions:

6 current channels and 6 voltage channels


7 current channels and 5 voltage channels
9 current channels and 3 voltage channels
12 current channels
6 current channels

The rated values and channel type, measurement or protection, of the current inputs
are selected at order.
Transformer input module for measuring should not be used with
current transformers intended for protection purposes, due to
limitations in overload characteristics.
The TRM is connected to the ADM and NUM via the UBM.
For configuration of the input and output signals, refer to section "Signal matrix
for analog inputs SMAI".

991
Technical reference manual

Section 19
IED hardware
19.2.7.3

1MRK 505 222-UEN B

Technical data
Table 686:

TRM - Energizing quantities, rated values and limits for protection transformer
modules

Quantity

Rated value

Current

Ir = 1 or 5 A

Operative range

(0-100) x Ir

Permissive overload

4 Ir cont.
100 Ir for 1 s *)

Burden

< 150 mVA at Ir = 5 A


< 20 mVA at Ir = 1 A

Ac voltage

Ur = 110 V

Operative range

(0340) V

Permissive overload

420 V cont.
450 V 10 s

Burden

< 20 mVA at 110 V

Frequency

fr = 50/60 Hz

*)

Nominal range
(0.2-40) Ir

0.5288 V

5%

max. 350 A for 1 s when COMBITEST test switch is included.

Table 687:

TRM - Energizing quantities, rated values and limits for measuring transformer
modules

Quantity

Rated value

Current

Ir = 1 or 5 A

Permissive overload

1.1 Ir cont.
1.8 Ir for 30 min at Ir = 1 A
1.6 Ir for 30 min at Ir = 5 A

Burden

< 350 mVA at Ir = 5 A


< 200 mVA at Ir = 1 A

Ac voltage

Ur = 110 V

Operative range

(0340) V

Permissive overload

420 V cont.
450 V 10 s

Burden

< 20 mVA at 110 V

Frequency

fr = 50/60 Hz

Nominal range
(0-1.8) Irat Ir = 1 A
(0-1.6) Irat Ir = 5 A

0.5288 V

5%

992
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.8

Analog digital conversion module, with time


synchronization (ADM)

19.2.8.1

Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC
slot. The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards
according to table 688. The OEM card should always be mounted on the ADM
board. The UBM connects the ADM to the transformer input module (TRM).
Table 688:
PC-MIP cards

PC-MIP cards and PMC cards


PMC cards

LDCM

SLM

LR-LDCM

OEM 1 ch

MR-LDCM

OEM 2 ch

X21-LDCM
IRIG-B
RS485

19.2.8.2

Design
The Analog digital conversion module input signals are voltage and current from
the transformer module. Shunts are used to adapt the current signals to the
electronic voltage level. To gain dynamic range for the current inputs, two shunts
with separate A\D channels are used for each input current. In this way a 20 bit
dynamic range is obtained with a 16 bit A\D converter.
Input signals are sampled with a sampling freqency of 5 kHz at 50 Hz system
frequency and 6 kHz at 60 Hz system frequency.
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz
and are reported to the numerical module (NUM) with 1 kHz at 50 Hz system
frequency and 1,2 kHz at 60 Hz system frequency.

993
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
Channel 11
Channel 12

AD1
AD2
1.2v

AD3
AD4

PMC

level shift

PC-MIP
2.5v

PCI to PCI
PC-MIP

en05000474.vsd
IEC05000474 V1 EN

Figure 519:

The ADM layout

994
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.9

Binary input module (BIM)

19.2.9.1

Introduction
The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the
inputs to be used with the pulse counter function. The binary inputs are freely
programmable and can be used for the input of logical signals to any of the
functions. They can also be included in the disturbance recording and eventrecording functions. This enables extensive monitoring and evaluation of operation
of the IED and for all associated electrical circuits.

19.2.9.2

Design
The Binary input module contains 16 optical isolated binary inputs. The voltage
level of the binary input is selected at order.
For configuration of the input signals, refer to section "Signal matrix for binary
inputs SMBI".
A signal discriminator detects and blocks oscillating signals. When blocked, a
hysteresis function may be set to release the input at a chosen frequency, making it
possible to use the input for pulse counting. The blocking frequency may also be set.
Figure 520 shows the operating characteristics of the binary inputs of the four
voltage levels.
The standard version of binary inputs gives an improved capability to withstand
disturbances and should generally be used when pulse counting is not required.

995
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

[V]
300

176
144
88
72
38
32
19
18
24/30V

48/60V

110/125V

220/250V
xx06000391.vsd

IEC06000391 V1 EN

Figure 520:

Voltage dependence for the binary inputs


Guaranteed operation
Operation uncertain
No operation

IEC99000517-ABC V1 EN

This binary input module communicates with the Numerical module (NUM) via
the CAN-bus on the backplane.
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 521 and 522.

996
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

[mA]
30 / 50

1
35

70

[ms]
en07000104-2.vsd

IEC07000104 V2 EN

Figure 521:

Approximate binary input inrush current for the two standard


versions of BIM.

[mA]
30

1
3.5

7.0

[ms]
en07000105.vsd

IEC07000105 V1 EN

Figure 522:

Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.

997
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Process connector

Opto isolated input


Opto isolated input
Opto isolated input
Opto isolated input
Opto isolated input
Opto isolated input
Opto isolated input
Opto isolated input

Microcontroller

Opto isolated input

Memory

Opto isolated input


Opto isolated input
Opto isolated input
Opto isolated input

Backplane connector

Opto isolated input

CAN

Process connector

Opto isolated input

Opto isolated input

99000503.vsd
IEC99000503 V1 EN

Figure 523:

Block diagram of the Binary input module.

998
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.9.3

Technical data
Table 689:

BIM - Binary input module

Quantity

Rated value

Nominal range

Binary inputs

16

DC voltage, RL

24/30 V
48/60 V
110/125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V
48/60 V
110/125 V
220/250 V

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input

Counter input frequency

10 pulses/s max

Oscillating signal discriminator

Blocking settable 140 Hz


Release settable 130 Hz

Table 690:

BIM - Binary input module with enhanced pulse counting capabilities

Quantity

Rated value

Nominal range

Binary inputs

16

DC voltage, RL

24/30 V
48/60 V
110/125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V
48/60 V
110/125 V
220/250 V

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input

Counter input frequency

10 pulses/s max

Balanced counter input frequency

40 pulses/s max

Oscillating signal discriminator

Blocking settable 140 Hz


Release settable 130 Hz

19.2.10

Binary output modules (BOM)

19.2.10.1

Introduction
The binary output module has 24 independent output relays and is used for trip
output or any signaling purpose.

19.2.10.2

Design
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 524.

999
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

This should be considered when connecting the wiring to the connection terminal
on the back of the IED.
The high closing and carrying current capability allows connection directly to
breaker trip and closing coils. If breaking capability is required to manage fail of
the breaker auxiliary contacts normally breaking the trip coil current, a parallel
reinforcement is required.
For configuration of the output signals, refer to section "Signal matrix for binary
outputs SMBO".
Output module

3
xx00000299.vsd
IEC00000299 V1 EN

Figure 524:

Relay pair example

1 Output connection from relay 1


2 Output signal power source connection
3 Output connection from relay 2

1000
Technical reference manual

Section 19
IED hardware

Relay

Relay

Relay

Process connector

Relay

Relay

Relay

1MRK 505 222-UEN B

Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay

Relay

Microcontroller

Relay
Relay
Relay
Relay

Memory

Relay

Backplane connector

Relay

CAN

Process connector

Relay

Relay

99000505.vsd
IEC99000505 V1 EN

Figure 525:

19.2.10.3

Block diagram of the Binary Output Module

Technical data
Table 691:

BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity

Trip and Signal relays

Binary outputs

24

Max system voltage

250 V AC, DC

Test voltage across open contact, 1 min

1000 V rms

Current carrying capacity


Continuous
1s

8A
10 A

Table continues on next page

1001
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Function or quantity

Trip and Signal relays

Making capacity at inductive load with L/R>10 ms


0.2 s
1.0 s

30 A
10 A

Breaking capacity for AC, cos j>0.4

250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

19.2.11

Static binary output module (SOM)

19.2.11.1

Introduction
The static binary output module has six fast static outputs and six change over
output relays for use in applications with high speed requirements.

19.2.11.2

Design
The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.
The SOM consists mainly of:

An MCU
A CAN-driver
6 static relays outputs
6 electromechanical relay outputs
A DC/DC converter
Connectors interfacing

CAN-bus to backplane CBM


IO-connectors to binary outputs (2 pcs.)

The following parts are supervised:

Interruption in relay coil


Short circuit of relay coil
Driver failure

1002
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Drive &
Read back

Process connector

Drive &
Read back

Drive &
Read back
Drive &
Read back

Codeflash

Drive &
Read back

MCU

Drive &
Read back

CANdriver

Drive &
Read back

DC/DC
Drive &
Read back

Drive &
Read back

Internal_fail_n
AC_fail_n
RCAN_ID
Sync

Drive &
Read back

Backplane connector

Process connector

Drive &
Read back

Reset
Drive &
Read back

en07000115.vsd
IEC07000115 V1 EN

Figure 526:

Block diagram of the static output module

1003
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

IEC09000974-1-en.vsd

IEC09000974 V1 EN

Figure 527:

SOM Static output principle

IEC09000975 V1 EN

Figure 528:

19.2.11.3

Connection diagram of the static output module

Technical data
Table 692:

SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs

Function of quantity

Static binary output trip

Rated voltage

48 - 60 VDC

110 - 250 VDC

Number of outputs

Impedance open state

~300 k

~810 k

Test voltage across open contact,


1 min

No galvanic separation

No galvanic separation

Current carrying capacity:


Table continues on next page
1004
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Function of quantity

Static binary output trip

Continuous

5A

5A

1.0s

10A

10A

0.2s

30A

30A

1.0s

10A

10A

Breaking capacity for DC with L/R


40ms

48V / 1A

110V / 0.4A

60V / 0,75A

125V / 0.35A

Making capacity at capacitive load


with the maximum capacitance of
0.2 F :

220V / 0.2A
250V / 0.15A
Operating time

Table 693:

<1ms

<1ms

SOM - Static Output module data (reference standard: IEC 61810-2):


Electromechanical relay outputs

Function of quantity

Trip and signal relays

Max system voltage

250V AC/DC

Number of outputs

Test voltage across open contact, 1 min

1000V rms

Current carrying capacity:


Continuous

8A

1.0s

10A

Making capacity at capacitive load with the


maximum capacitance of 0.2 F:
0.2s

30A

1.0s

10A

Breaking capacity for DC with L/R 40ms

48V / 1A
110V / 0.4A
125V / 0,35A
220V / 0,2A
250V / 0.15A

19.2.12

Binary input/output module (IOM)

19.2.12.1

Introduction
The binary input/output module is used when only a few input and output channels
are needed. The ten standard output channels are used for trip output or any
signaling purpose. The two high speed signal output channels are used for
applications where short operating time is essential. Eight optically isolated binary
inputs cater for required binary input information.
1005

Technical reference manual

Section 19
IED hardware
19.2.12.2

1MRK 505 222-UEN B

Design
The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase
the disturbance immunity during normal protection operate times. This is achieved
with a high peak inrush current while having a low steady-state current, see figure
521. Inputs are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure 520.
The voltage level of the inputs is selected when ordering.
I/O events are time stamped locally on each module for minimum time deviance
and stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output
relays. One of the outputs has a change-over contact. The nine remaining output
contacts are connected in two groups. One group has five contacts with a common
and the other group has four contacts with a common, to be used as single-output
channels, see figure 529.
The binary I/O module also has two high speed output channels where a reed relay
is connected in parallel to the standard output relay.
For configuration of the input and output signals, refer to sections "Signal matrix
for binary inputs SMBI" and "Signal matrix for binary outputs SMBO".
The making capacity of the reed relays are limited.

1006
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

IEC1MRK002801-AA11-UTAN-RAM V1 EN

Figure 529:

Binary in/out module (IOM), input contacts named XA corresponds


to rear position X31, X41, and so on, and output contacts named
XB to rear position X32, X42, and so on

The binary input/output module version with MOV protected contacts can for
example be used in applications where breaking high inductive load would cause
excessive wear of the contacts.
The test voltage across open contact is lower for this version of the
binary input/output module.

1007
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

xx04000069.vsd
IEC04000069 V1 EN

Figure 530:

19.2.12.3

IOM with MOV protection, relay example

Technical data
Table 694:

IOM - Binary input/output module

Quantity

Rated value

Nominal range

Binary inputs

DC voltage, RL

24/30 V
48/60 V
110/125 V
220/250 V

RL 20%
RL 20%
RL 20%
RL 20%

Power consumption
24/30 V
48/60 V
110/125 V
220/250 V

Table 695:

max. 0.05 W/input


max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input

IOM - Binary input/output module contact data (reference standard: IEC 61810-2)

Function or quantity

Trip and signal relays

Fast signal relays (parallel reed


relay)

Binary outputs

10

Max system voltage

250 V AC, DC

250 V AC, DC

Test voltage across open contact,


1 min

1000 V rms

800 V DC

Current carrying capacity


Continuous
1s

8A
10 A

8A
10 A

Making capacity at inductive load


with L/R>10 ms
0.2 s
1.0 s

30 A
10 A

0.4 A
0.4 A

Breaking capacity for AC, cos >


0.4

250 V/8.0 A

250 V/8.0 A

Breaking capacity for DC with L/R


< 40 ms

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A

Maximum capacitive load

10 nF

1008
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 696:

IOM with MOV - contact data (reference standard: IEC 60255-23)

Function or quantity

Trip and Signal relays

Fast signal relays (parallel


reed relay)

Binary outputs

IOM: 10

IOM: 2

Max system voltage

250 V AC, DC

250 V AC, DC

Test voltage across open


contact, 1 min

250 V rms

250 V DC

Current carrying capacity


Continuous
1s

8A
10 A

8A
10 A

Making capacity at inductive


loadwith L/R>10 ms
0.2 s
1.0 s

30 A
10 A

0.4 A
0.4 A

Breaking capacity for AC, cos


j>0.4

250 V/8.0 A

250 V/8.0 A

Breaking capacity for DC with L/


R < 40 ms

48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A

Maximum capacitive load

10 nF

19.2.13

mA input module (MIM)

19.2.13.1

Introduction
The milli-ampere input module is used to interface transducer signals in the 20 to
+20 mA range from for example OLTC position, temperature or pressure
transducers. The module has six independent, galvanically separated channels.

19.2.13.2

Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, refer to section "Signal matrix for mA
inputs SMMI".
The analog inputs measure DC current in the range of +/- 20 mA. The A/D
converter has a digital filter with selectable filter frequency. All inputs are
calibrated separately The filter parameters and the calibration factors are stored in a
non-volatile memory on the module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The
module communicates, like the other I/O-modules on the serial CAN-bus.

1009
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Protection
& filter

Protection
& filter

Volt-ref

DC/DC

Volt-ref

DC/DC

Volt-ref

DC/DC

Volt-ref

DC/DC

Optoisolation
DC/DC

Optoisolation

A/D Converter
Volt-ref

Memory

Optoisolation

A/D Converter

Volt-ref

Protection
& filter

Optoisolation

A/D Converter

A/D Converter

Protection
& filter

Optoisolation

A/D Converter

DC/DC

Microcontroller

Backplane connector

Protection
& filter

Optoisolation

A/D Converter

CAN

Process connector

Protection
& filter

99000504.vsd
IEC99000504 V1 EN

Figure 531:

19.2.13.3

MIM block diagram

Technical data
Table 697:

MIM - mA input module

Quantity:

Rated value:

Nominal range:

Input resistance

Rin = 194 Ohm

Input range

5, 10, 20mA
0-5, 0-10, 0-20, 4-20mA

Power consumption
each mA-board
each mA input

2W
0.1 W

1010
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.14

Serial and LON communication module (SLM)

19.2.14.1

Introduction
The serial and LON communication module (SLM) is used for SPA, IEC
60870-5-103, DNP3 and LON communication. The module has two optical
communication ports for plastic/plastic, plastic/glass or glass/glass. One port is
used for serial communication (SPA, IEC 60870-5-103 and DNP3 port or
dedicated IEC 60870-5-103 port depending on ordered SLM module) and one port
is dedicated for LON communication.

19.2.14.2

Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. Three variants of the SLM is available with different combinations
of optical fiber connectors, see figure 532. The plastic fiber connectors are of snapin type and the glass fiber connectors are of ST type.

IEC05000760 V1 EN

Figure 532:

The SLM variants, component side view

Snap in connector for plastic fiber

ST connector for glass fiber

LON port

SPA/IEC 60870-5-103/DNP3 port or dedicated IEC 60870-5-103 port depending on


ordered SLM module

1011
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

IEC05000761 V1 EN

Figure 533:

The SLM layout overview, component side view

Receiver, LON

Transmitter, LON

Receiver, SPA/IEC 60870-5-103/DNP3

Transmitter, SPA/IEC 60870-5-103/DNP3

Observe that when the SLM connectors are viewed from the rear
side of the IED, contact 4 above is in the uppermost position and
contact 1 in the lowest position.

19.2.14.3

Technical data
Table 698:

SLM LON port

Quantity

Range or value

Optical connector

Glass fibre: type ST


Plastic fibre: type HFBR snap-in

Fibre, optical budget

Glass fibre: 11 dB (1000 m typically *)


Plastic fibre: 7 dB (10 m typically *)

Fibre diameter

Glass fibre: 62.5/125 mm


Plastic fibre: 1 mm

*) depending on optical budget calculation

1012
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 699:

SLM SPA/IEC 60870-5-103/DNP3 port

Quantity

Range or value

Optical connector

Glass fibre: type ST


Plastic fibre: type HFBR snap-in

Fibre, optical budget

Glass fibre: 11 dB (3000ft/1000 m typically *)


Plastic fibre: 7 dB (80ft/25 m typically *)

Fibre diameter

Glass fibre: 62.5/125 mm


Plastic fibre: 1 mm

*) depending on optical budget calculation

19.2.15

Galvanic RS485 communication module

19.2.15.1

Introduction
The Galvanic RS485 communication module (RS485) is used for DNP3.0
communication. The module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2-wire or 4-wire
connections. A 2-wire connection uses the same signal for RX and TX and is a
multidrop communication with no dedicated Master or slave. This variant requires
however a control of the output. The 4-wire connection has separated signals for
RX and TX multidrop communication with a dedicated Master and the rest are
slaves. No special control signal is needed in this case.

19.2.15.2

Design
The RS485 is a PMC card and it is factory mounted as a mezzanine card on the
NUM module. The internal structure of the RS485 can be seen in figure 534:

PCI-con

PCIController

Local bus
to
wishbone
Status
Register

ID-chip

Control
Register

UART

RS485
tranceiver
Isolation

Rx

6-pole-connector

PCI-bus

Tx

Isolation

Isolation
Termination

Info
Register
Isolated
DC/DC

Soft
ground

2-pole
connector

PCI-con

Internal
bus

Wishbone interconnect switch

FPGA
32 MHz

IEC06000516 V1 EN

Figure 534:

The internal structure of the RS485 card

RS485 connector pinouts

The arrangement for the pins in the RS485 connector (figure 535) are presented in
table 700:
1013
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 700:

The arrangement for the pins

Pin

Name 2-wire

Name 4-wire

Description

RS485+

TX+

Receive/transmit high or transmit high

RS485

TX

Receive/transmit

Term

T-Term

Termination resistor for transmitter (and receiver


in 2wir case) (connect to TX+)

N.A.

R-Term

Termination resistor for receiver (connect to RX


+)

N.A.

RX

Receive low

N.A.

RX+

Receive high

Angle
bracket

Screw
terminal
X3

Screw
terminal
X1

1
2
1
2
3
4
5
6

RS485
PWB

Backplane

IEC06000517 V1 EN

Figure 535:

RS485 connector

2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5

Termination (2-wire): Connect pin 1 to pin 3

Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6

Soft ground connector pinouts

A second 2-pole screw connector is used for the connection of IO-ground. It can be
used in two combinations like:

Unconnected: No ground of the IO-part .

Soft grounded: The IO is connected to the GND with an RC net parallel with a
MOV

1014
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.15.3

Technical data
Table 701:

Galvanic RS485 communication module

Quantity

Range or value

Communication speed

240019200 bauds

External connectors

RS-485 6-pole connector


Soft ground 2-pole connector

19.2.16

Optical ethernet module (OEM)

19.2.16.1

Introduction
The optical fast-ethernet module is used to connect an IED to the communication
buses (like the station bus) that use the IEC 61850-8-1 protocol (OEM rear port A,
B). The process bus use the IEC 61850-9-2LE protocol (OEM rear port C, D). The
module has one or two optical ports with ST connectors.

19.2.16.2

Functionality
The Optical Ethernet module (OEM) is used when communication systems
according to IEC6185081 have been implemented.

19.2.16.3

Design
The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine
card on the ADM. The OEM is a 100base Fx module and available as a single
channel or double channel unit.
PCI - bus Connector

100Base-FX
Transmitter

EEPROM
Ethernet Controller

ST fiber optic
connectors

100Base-FX
Receiver
PCI - PCI Bridge

100Base-FX
Transmitter

ID chip

Ethernet Controller
EEPROM

IO - bus Connector

100Base-FX
Receiver

ST fiber optic
connectors

en04000472.vsd
IEC04000472 V1 EN

Figure 536:

OEM block diagram.

1015
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

ID chip

LED

Transmitter

IO bus

Receiver

Ethernet cont.

25MHz oscillator

LED

Transmitter

Ethernet cont.

25MHz oscillator

PCI to PCI
bridge

PCI bus

Receiver

en05000472.vsd
IEC05000472 V1 EN

Figure 537:

19.2.16.4

OEM layout, standard PMC format 2 channels

Technical data
Table 702:

OEM - Optical ethernet module

Quantity

Rated value

Number of channels

1 or 2 (port A, B for IEC61850-8-1 and port C, D


for IEC 61850-9-2LE)

Standard

IEEE 802.3u 100BASE-FX

Type of fiber

62.5/125 mm multimode fibre

Wave length

1300 nm

Optical connector

Type ST

Communication speed

Fast Ethernet 100 MB

19.2.17

Line data communication module (LDCM)

19.2.17.1

Introduction
The line data communication module (LDCM) is used for communication between
the IEDs situated at distances <110 km or from the IED to optical to electrical
converter with G.703 interface located on a distances <3 km away. The LDCM
module sends and rereceives data, to and from another LDCM module. The IEEE/
ANSI standard format is used.
The line data communication module is used for binary signal transfer. The module
has one optical port with ST connectors see figure 538.

Line data communication module LDCM

Each module has one optical port, one for each remote end to which the IED
communicates.
1016
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm
single mode) and Short range (850 nm multi mode) are available.
Class 1 laser product. Take adequate measures to protect the eyes.
Never look into the laser beam.

19.2.17.2

Design
The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:

the ADM
the NUM

ID

16.000
MHz
32,768
MHz

ST

IO-connector

ST

en07000087.vsd
IEC07000087 V1 EN

Figure 538:

The SR-LDCM layout. PCMIP type II single width format with two
PCI connectors and one I/O ST type connector

1017
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

X1
2.5V

ADN
2841

DS
3904

PCI9054
TQ176

FPGA
256 FBGA

MAX
3645

DS
3904

ID

3
2

en06000393.vsd
IEC06000393 V1 EN

Figure 539:

19.2.17.3

The MR-LDCM and LR-LDCM layout. PCMIP type II single width


format with two PCI connectors and one I/O FC/PC type connector

Technical data
Table 703:

Line data communication module

Characteristic
Type of LDCM

Range or value
Short range (SR)

Type of fibre

Graded-index
multimode
62.5/125 m or
50/125 m

Singlemode 9/125
m

Singlemode 9/125 m

Wave length

850 nm

1310 nm

1550 nm

Optical budget
Graded-index
multimode 62.5/125
mm,

13 dB (typical
distance about 3
km *)
9 dB (typical
distance about 2
km *)

22 dB (typical
distance 80 km *)

26 dB (typical distance 110 km *)

Optical connector

Type ST

Type FC/PC

Type FC/PC

Protocol

C37.94

C37.94
implementation **)

C37.94 implementation **)

Data transmission

Synchronous

Synchronous

Synchronous

Transmission rate /
Data rate

2 Mb/s / 64 kbit/s

2 Mb/s / 64 kbit/s

2 Mb/s / 64 kbit/s

Clock source

Internal or
derived from
received signal

Internal or derived
from received signal

Internal or derived from received


signal

Graded-index
multimode 50/125
mm

Medium range (MR)

Long range (LR)

*) depending on optical budget calculation


**) C37.94 originally defined just for multimode; using same header, configuration and data format as
C37.94

1018
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.18

Galvanic X.21 line data communication (X.21-LDCM)

19.2.18.1

Introduction
The galvanic X.21 line data communication module is used for connection to
telecommunication equipment, for example leased telephone lines. The module
supports 64 kbit/s data communication between IEDs.
Examples of applications:

19.2.18.2

Line differential protection


Binary signal transfer

Design

The galvanic X.21 line data communication module uses a ABB specific PC*MIP
Type II format.

en07000196.vsd
IEC07000196 V1 EN

Figure 540:

Overview of the X.21 LDCM module

1019
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

1
1

15

en07000239.wmf

IEC07000239 V1 EN

Figure 541:

1.
2.
3.
4.

The X.21 LDCM module external connectors

Ground selection connector for IO, screw terminals, 2-pole


Ground pin
Soft ground pin, see figure 542
X.21 Micro D-sub 15 pole male connector according to the V11 (X:27)
balanced version

I/O

100kW

100nF

Soft ground
en07000242.vsd
IEC07000242 V1 EN

Figure 542:

Schematic view of soft ground

Grounding
At special problems with ground loops, the soft ground connection for the IOground can be tested.
Three different kinds of grounding principles can be set (used for fault tracing):
1.
2.
3.

Direct ground - The normal grounding is direct ground, connect terminal 2


direct to the chassi.
No ground - Leave the connector without any connection.
Soft ground - Connect soft ground pin (3), see figure 541

1020
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

X.21 connector
Table 704:

19.2.18.3

Pinout for the X.21 communication connector

Pin number

Signal

Shield (ground)

TXD A

Control A

RXD A

Signal timing A

Ground

TXD B

10

Control B

11

RXD B

13

Signal timing B

5,7,12,14,15

Not used

Functionality
The data format is HDLC. The speed for the transmission of the messages used is
64 kbit/s.
A maximum of 100 meter of cable is allowed to ensure the quality of the data
(deviation from X.21 standard cable length).
Synchronization
The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally
expecting synchronization from the DCE (Data Circuit Equipment). The
transmission is normally synchronized to the Signal Element Timing signal when a
device is a DTE. When the signal is high it will read the data at the receiver and
when the signal is low it will write data to the transmitter. This behaviour can be
inverted in the control register.
Normally an external multiplexer is used and it should act like the master.
When two X.21 LDCM is directly communicating with each other one must be set
as a master generating the synchronization for the other (the slave). The DTE
Signal Element Timing is created from the internal 64 kHz clock.
The Byte Timing signal is not used in ABB devices.

1021
Technical reference manual

Section 19
IED hardware
19.2.18.4

1MRK 505 222-UEN B

Technical data
Table 705:

Galvanic X.21 line data communication module (X.21-LDCM)

Quantity

Range or value

Connector, X.21

Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch

Connector, ground selection

2 pole screw terminal

Standard

CCITT X21

Communication speed

64 kbit/s

Insulation

1 kV

Maximum cable length

100 m

19.2.19

GPS time synchronization module (GTM)

19.2.19.1

Introduction
This module includes a GPS receiver used for time synchronization. The GPS has
one SMA contact for connection to an antenna. It also includes an optical PPS STconnector output.

19.2.19.2

Design
The GTM is a PCMIP-format card and is placed only on one of the ADM slots.
The antenna input connector is shielded and directly attached to a grounded plate to
eliminate the risk of electromagnetic interference.
All communication between the GCM and the NUM is via the PCI-bus. PPS time
data is sent from the GCM to the rest of the time system to provide 1s accuracy at
sampling level. An optical transmitter for PPS output is available for time
synchronization of another relay with an optical PPS input. The PPS output
connector is of ST-type for multimode fibre and could be used up to 1 km.

1022
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Controller

Selector

PCI

GPS- receiver

UART-core
PCI- core

FPGA
PCI
Antenna
connector

Receiver
memory
Stripline( 50 Ohms)

Wishbone bus

Registers
Optical
PPS
transmitter

TSU
IO

Transmitter
Driver
JTAG
connector

Configmemory

OSC

ID- chip

IEC09000980-1-en.vsd
IEC09000980 V1 EN

Figure 543:

19.2.19.3

Block diagram of the GCM

Technical data
Table 706:

GPS time synchronization module (GTM)

Function

Range or value

Accuracy

Receiver

1s relative UTC

Time to reliable time reference with antenna in new


position or after power loss longer than 1 month

<30 minutes

Time to reliable time reference after a power loss


longer than 48 hours

<15 minutes

Time to reliable time reference after a power loss


shorter than 48 hours

<5 minutes

19.2.20

GPS antenna

19.2.20.1

Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.

19.2.20.2

Design
The antenna with a console for mounting on a horizontal or vertical flat surface or
on an antenna mast. See figure 544

1023
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

2
3

xx04000155.vsd
IEC04000155 V2 EN

Figure 544:

Antenna with console

where:
1

GPS antenna

TNC connector

Console, 78x150 mm

Mounting holes 5.5 mm

Tab for securing of antenna cable

Vertical mounting position

Horizontal mounting position

Always position the antenna and its console so that a continuous clear line-of-sight
visibility to all directions is obtained, preferably more than 75%. A minimum of
50% clear line-of-sight visibility is required for un-interrupted operation.

1024
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

99001046.vsd
IEC99001046 V1 EN

Figure 545:

Antenna line-of-sight

Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a
male SMA connector in the receiver end to connect the antenna to GTM. Choose
cable type and length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to
the antenna or to the receiver. Short-circuit the end of the antenna
cable with some metal device, when first connected to the antenna.
When the antenna is connected to the cable, connect the cable to the
receiver. REx670 must be switched off when the antenna cable is
connected.

19.2.20.3

Technical data
Table 707:

GPS Antenna and cable

Function

Value

Max antenna cable attenuation

26 db @ 1.6 GHz

Antenna cable impedance

50 ohm

Lightning protection

Must be provided externally

Antenna cable connector

SMA in receiver end


TNC in antenna end

1025
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.2.21

IRIG-B time synchronization module IRIG-B

19.2.21.1

Introduction
The IRIG-B time synchronizing module is used for accurate time synchronizing of
the IED from a station clock.
The Pulse Per Second (PPS) input shall be used for synchronizing when IEC
61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
Optical connection (ST) for 1344 IRIG-B support.

19.2.21.2

Design
The IRIG-B module have two inputs. One input is for the IRIG-B that can handle
both a pulse-width modulated signal (also called unmodulated) and an amplitude
modulated signal (also called sine wave modulated). The other is an optical input
type ST for PPS to synchronize the time between several protections.
STconnector

FPGA

PCI-con

32 MHz

OPTO_INPUT
PCI-bus

Registers

PCI-con

PCI-Controller

IRIGDecoder

ID-chip
Capture1

IRIG_INPUT
ZXING

Amplitude
modulator
Isolated
receiver

IO-con

Capture2

BNCconnector

4 mm barrier

Zero-cross
detector

MPPS
PPS

TSU

CMPPS

Isolated
DC/DC
5 to +- 12V

en06000303.vsd
IEC06000303 V1 EN

Figure 546:

IRIG-B block diagram

1026
Technical reference manual

Section 19
IED hardware

A1

C
C

Y2

DC//DC

ST

A1

1MRK 505 222-UEN B

3
2

en06000304.vsd
IEC06000304 V1 EN

Figure 547:

19.2.21.3

IRIG-B PC-MIP board with top left ST connector for PPS 820 nm
multimode fibre optic signal input and lower left BNC connector for
IRIG-B signal input

Technical data
Table 708:

IRIG-B

Quantity

Rated value

Number of channels IRIG-B

Number of channels PPS

Electrical connector IRIG-B

BNC

Optical connector PPS and IRIG-B

Type ST

Type of fibre

62.5/125 m multimode fibre

Pulse-width modulated

5 Vpp

Amplitude modulated
low level
high level

1-3 Vpp
3 x low level, max 9 Vpp

1027
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.3

Dimensions

19.3.1

Case without rear cover

A
D

C
xx08000164.vsd

IEC08000164 V1 EN

Figure 548:

Case without rear cover

1028
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

K
F

G
H

J
xx08000166.vsd

IEC08000166 V1 EN

Figure 549:
Case size (mm) A

Case without rear cover with 19 rack mounting kit


E

6U, 1/2 x 19

265.9

223.7

201.1

252.9

205.7

190.5

203.7

187.6

6U, 3/4 x 19

265.9

336.0

201.1

252.9

318.0

190.5

316.0

187.6

6U, 1/1 x 19

265.9

448.3

201.1

252.9

430.3

190.5

428.3

465.1

187.6

482.6

The H and K dimensions are defined by the 19 rack mounting kit

1029
Technical reference manual

Section 19
IED hardware
19.3.2

1MRK 505 222-UEN B

Case with rear cover

C
xx08000163.vsd

IEC08000163 V1 EN

Figure 550:

Case with rear cover

1030
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

K
F

G
H

J
xx08000165.vsd

IEC08000165 V1 EN

Figure 551:

Case with rear cover and 19 rack mounting kit

xx05000503.vsd
IEC05000503 V1 EN

Figure 552:
Case size (mm) A

Rear cover case with details


E

6U, 1/2 x 19

265.9

223.7

242.1

255.8

205.7

190.5

203.7

228.6

6U, 3/4 x 19

265.9

336.0

242.1

255.8

318.0

190.5

316.0

228.6

6U, 1/1 x 19

265.9

448.3

242.1

255.8

430.3

190.5

428.3

465.1

228.6

482.6

The H and K dimensions are defined by the 19 rack mounting kit.

1031
Technical reference manual

Section 19
IED hardware
19.3.3

1MRK 505 222-UEN B

Flush mounting dimensions

E
D
xx08000162.vsd
IEC08000162 V1 EN

Figure 553:

Case size
Tolerance

Flush mounting
Cut-out dimensions (mm)
A
+/-1

B
+/-1

6U, 1/2 x 19"

210.1

254.3

4.0-10.0

12.5

6U, 3/4 x 19"

322.4

254.3

4.0-10.0

12.5

6U, 1/1 x 19"

434.7

254.3

4.0-10.0

12.5

E = 188.6 mm without rear protection cover, 229.6 mm with rear protection cover

1032
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.3.4

Side-by-side flush mounting dimensions

xx06000182.vsd
IEC06000182 V1 EN

Figure 554:

A 1/2 x 19 size 670 series IED side-by-side with RHGS6.

C
xx05000505.vsd
IEC05000505 V1 EN

Figure 555:

Case size (mm) A


Tolerance
1

B
1

Panel-cut out dimensions for side-by-side flush mounting

C
1

D
1

E
1

F
1

G
1

6U, 1/2 x 19

214.0

259.3

240.4

190.5

34.4

13.2

6.4 diam

6U, 3/4 x 19

326.4

259.3

352.8

190.5

34.4

13.2

6.4 diam

6U, 1/1 x 19

438.7

259.3

465.1

190.5

34.4

13.2

6.4 diam

1033
Technical reference manual

Section 19
IED hardware
19.3.5

1MRK 505 222-UEN B

Wall mounting dimensions

A
B
E

en04000471.vsd
IEC04000471 V1 EN

Figure 556:

Case size (mm)

Wall mounting

6U, 1/2 x 19

292.0

267.1

272.8

390.0

243.0

6U, 3/4 x 19

404.3

379.4

272.8

390.0

243.0

6U, 1/1 x 19

516.0

491.1

272.8

390.0

243.0

19.3.6

External resistor unit for high impedance differential


protection
WARNING! - USE EXTREME CAUTION!Dangerously high
voltages might be present on this equipment, especially on the plate
with resistors. Do any maintenance ONLY if the primary object
protected with this equipment is de-energized. If required by
national low/standard enclose the plate with resistors with a
protective cover or in a separate box!

1034
Technical reference manual

Section 19
IED hardware

[6.97]

[4.02]

[1.48

1MRK 505 222-UEN B

[18.31]

[0.33]

[0.79]

[7.68]

[18.98]

Dimension
mm [inches]

xx06000232.eps

IEC06000232 V1 EN

Dimension drawing of a one phase impedance resistor unit

[7.50]

[10.47]

[1.50]

Figure 557:

[18.31]

[0.33]

[0.79]

[7.68]

[18.98]

[inches]

en06000234.eps

IEC06000234 V1 EN

Figure 558:

Dimension drawing of a three phase high impedance resistor unit

19.4

Mounting alternatives

19.4.1

Flush mounting

19.4.1.1

Overview
The flush mounting kit are utilized for case sizes:

1/2 x 19
3/4 x 19
1/1 x 19
1/4 x 19 (RHGS6 6U)

1035
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Only a single case can be mounted in each cut-out on the cubicle panel, for class
IP54 protection.
Flush mounting cannot be used for side-by-side mounted IEDs
when IP54 class must be fulfilled. Only IP20 class can be obtained
when mounting two cases side-by-side in one (1) cut-out.

To obtain IP54 class protection, an additional factory mounted


sealing must be ordered when ordering the IED.

1036
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.4.1.2

Mounting procedure for flush mounting


1

5
2

6
3

xx08000161.vsd
IEC08000161 V1 EN

Figure 559:

Flush mounting details.

PosNo Description

Quantity Type

Sealing strip, used to obtain IP54 class. The sealing strip is factory
mounted between the case and front plate.

Fastener

Groove

Screw, self tapping

2.9x9.5 mm

Joining point of sealing strip

Panel

1037
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.4.2

19 panel rack mounting

19.4.2.1

Overview
All IED sizes can be mounted in a standard 19 cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening
screws for the angles.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19
or 3/4 x 19 either to the left or right side of the cubicle.
Please note that the separately ordered rack mounting kit for side-byside mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19.

When mounting the mounting angles, be sure to use screws that


follows the recommended dimensions. Using screws with other
dimensions than the original may damage the PCBs inside the IED.

1038
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.4.2.2

Mounting procedure for 19 panel rack mounting


2
1a

1b

xx08000160.vsd
IEC08000160 V1 EN

Figure 560:
Pos

19 panel rack mounting details

Description

Quantity

Type

1a, 1b

Mounting angels, which can be mounted, either to


the left or right side of the case.

Screw

M4x6

19.4.3

Wall mounting

19.4.3.1

Overview
All case sizes, 1/2 x 19, 3/4 x 19 and 1/1 x 19, can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.

1039
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

When mounting the side plates, be sure to use screws that follows
the recommended dimensions. Using screws with other dimensions
than the original may damage the PCBs inside the IED.

If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication
modules with fiber connection; Serial SPA/IEC 60870-5-103,
DNP3 and LON communication module (SLM), Optical Ethernet
module (OEM) and Line data communication module (LDCM).

19.4.3.2

Mounting procedure for wall mounting


3
4

2
1

5
6

xx04000453.vs d

DOCUMENT127716-IMG2265 V1 EN

Figure 561:

Wall mounting details.

PosNo

Description

Quantity

Type

Bushing

Screw

M4x10

Screw

M6x12 or
corresponding

Table continues on next page

1040
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

19.4.3.3

Mounting bar

Screw

M5x8

Side plate

How to reach the rear side of the IED


The IED can be equipped with a rear protection cover, which is recommended to
use with this type of mounting. See figure 562.
To reach the rear side of the IED, a free space of 80 mmis required on the unhinged
side.
View from above
3

80 mm

en06000135.vsd
IEC06000135 V1 EN

Figure 562:

How to reach the connectors on the rear side of the IED.

PosNo

Description

Type

Screw

M4x10

Screw

M5x8

Rear protection cover

19.4.4

Side-by-side 19 rack mounting

19.4.4.1

Overview
IED case sizes, 1/2 x 19 or 3/4 x 19 and RHGS cases, can be mounted side-byside up to a maximum size of 19. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19 rack panel mounting kit must be used. The
mounting kit has to be ordered separately.

1041
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.

19.4.4.2

Mounting procedure for side-by-side rack mounting


2
1

xx04000456.vsd
IEC04000456 V1 EN

Figure 563:

19.4.4.3

Side-by-side rack mounting details.

PosNo

Description

Quantity

Type

Mounting plate

2, 3

Screw

16

M4x6

Mounting angle

IED in the 670 series mounted with a RHGS6 case


An 1/2 x 19 or 3/4 x 19 size IED can be mounted with a RHGS (6 or 12
depending on IED size) case. The RHGS case can be used for mounting a test
switch of type RTXP 24. It also has enough space for a terminal base of RX 2 type
for mounting of, for example, a DC-switch or two trip IEDs.

1042
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

xx06000180.vsd
IEC06000180 V1 EN

Figure 564:

IED in the 670 series (1/2 x 19) mounted with a RHGS6 case
containing a test switch module equipped with only a test switch
and a RX2 terminal base

19.4.5

Side-by-side flush mounting

19.4.5.1

Overview
It is not recommended to flush mount side by side mounted cases if IP54 is
required. If your application demands side-by-side flush mounting, the side-by-side
mounting details kit and the 19 panel rack mounting kit must be used. The
mounting kit has to be ordered separately. The maximum size of the panel cut out
is 19.
With side-by-side flush mounting installation, only IP class 20 is
obtained. To reach IP class 54, it is recommended to mount the
IEDs separately. For cut out dimensions of separately mounted
IEDs, see section "Flush mounting".

When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws
with other dimensions than the original may damage the PCBs
inside the IED.

1043
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Please contact factory for special add on plates for mounting FT


switches on the side (for 1/2 19" case) or bottom of the relay.

19.4.5.2

Mounting procedure for side-by-side flush mounting


1

3
4

xx06000181.vsd
IEC06000181 V1 EN

Figure 565:

Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x


19 IED).

PosNo

Description

Quantity

Type

Mounting plate

2, 3

Screw

16

M4x6

Mounting angle

19.5

Technical data

19.5.1

Enclosure
Table 709:
Material

Case
Steel sheet

Front plate

Steel sheet profile with cut-out for HMI

Surface treatment

Aluzink preplated steel

Finish

Light grey (RAL 7035)

1044
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 710:

Water and dust protection level according to IEC 60529

Front

IP40 (IP54 with sealing strip)

Rear, sides, top and


bottom

IP20

Table 711:

Weight

Case size

19.5.2

Weight

6U, 1/2 x 19

10 kg

6U, 3/4 x 19

15 kg

6U, 1/1 x 19

18 kg

Connection system
Table 712:

CT and VT circuit connectors

Connector type

Rated voltage and current

Maximum conductor area

Screw compression type

250 V AC, 20 A

4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)

Terminal blocks suitable for


ring lug terminals

250 V AC, 20 A

4 mm2 (AWG12)

Table 713:

Binary I/O connection system

Connector type

Rated voltage

Maximum conductor area

Screw compression type

250 V AC

2.5 mm2 (AWG14)


2 1 mm2 (2 x AWG18)

Terminal blocks suitable for


ring lug terminals

300 V AC

3 mm2 (AWG14)

Because of limitations of space, when ring lug terminal is ordered


for Binary I/O connections, one blank slot is necessary between two
adjacent IO cards. Please refer to the ordering particulars for details.

19.5.3

Influencing factors
Table 714:

Temperature and humidity influence

Parameter

Reference value

Nominal range

Influence

Ambient temperature,
operate value

+20 C

-10 C to +55 C

0.02% /C

Relative humidity
Operative range

10%-90%
0%-95%

10%-90%

Storage temperature

-40 C to +70 C

1045
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 715:

Auxiliary DC supply voltage influence on functionality during operation

Dependence on

Reference value

Ripple, in DC auxiliary voltage


Operative range

max. 2%
Full wave rectified

Within nominal range Influence


15% of EL

0.01% /%

Auxiliary voltage dependence, operate


value

20% of EL

0.01% /%

Interrupted auxiliary DC voltage

24-60 V DC 20%
90-250 V DC 20%

Interruption
interval
050 ms

Table 716:

0 s

Correct
behaviour at
power down

Restart time

<180 s

Frequency influence (reference standard: IEC 602551)

Dependence on

19.5.4

No restart

Within nominal range

Influence

Frequency dependence,
operate value

fr 2.5 Hz for 50 Hz
fr 3.0 Hz for 60 Hz

1.0% / Hz

Frequency dependence
for distance protection
operate value

fr 2.5 Hz for 50 Hz
fr 3.0 Hz for 60 Hz

2.0% / Hz

Harmonic frequency
dependence (20%
content)

2nd, 3rd and 5th harmonic of fr

1.0%

Harmonic frequency
dependence for distance
protection (10% content)

2nd, 3rd and 5th harmonic of fr

6.0%

Harmonic frequency
dependence for high
impedance differential
protection (10% content)

2nd, 3rd and 5th harmonic of fr

5.0%

Type tests according to standard


Table 717:

Electromagnetic compatibility

Test

Type test values

Reference standards

1 MHz burst disturbance

2.5 kV

IEC 60255-22-1

100 kHz slow damped


oscillatory wave immunity
test

2.5 kV

IEC 61000-4-18, Class III

Ring wave immunity test,


100 kHz

2-4 kV

IEC 61000-4-12, Class IV

Surge withstand capability


test

2.5 kV, oscillatory


4.0 kV, fast transient

IEEE/ANSI C37.90.1

Table continues on next page

1046
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Test

Type test values

Reference standards

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEC 60255-22-2, Class IV

Electrostatic discharge
Direct application
Indirect application

15 kV air discharge
8 kV contact discharge
8 kV contact discharge

IEEE/ANSI C37.90.1

Fast transient disturbance

4 kV

IEC 60255-22-4, Class A

Surge immunity test

1-2 kV, 1.2/50 ms


high energy

IEC 60255-22-5

Power frequency immunity


test

150-300 V, 50 Hz

IEC 60255-22-7, Class A

Conducted common mode


immunity test

15 Hz-150 kHz

IEC 61000-4-16, Class IV

Power frequency magnetic


field test

1000 A/m, 3 s
100 A/m, cont.

IEC 61000-4-8, Class V

Damped oscillatory magnetic


field test

100 A/m

IEC 61000-4-10, Class V

Radiated electromagnetic
field disturbance

20 V/m, 80-1000 MHz

IEC 60255-22-3

Radiated electromagnetic
field disturbance

35 V/m
26-1000 MHz

IEEE/ANSI C37.90.2

Conducted electromagnetic
field disturbance

10 V, 0.15-80 MHz

IEC 60255-22-6

Radiated emission

30-1000 MHz

IEC 60255-25

Conducted emission

0.15-30 MHz

IEC 60255-25

Table 718:

1.4-2.7 GHz

Insulation

Test

Type test values

Dielectric test

2.0 kV AC, 1 min.

Impulse voltage test

5 kV, 1.2/50 ms, 0.5 J

Insulation resistance

>100 MW at 500 VDC

Table 719:

IEC 61000-4-2, Class IV

Reference standard
IEC 60255-5

Environmental tests

Test

Type test value

Reference standard

Cold test

Test Ad for 16 h at -25C

IEC 60068-2-1

Storage test

Test Ad for 16 h at -40C

IEC 60068-2-1

Dry heat test

Test Bd for 16 h at +70C

IEC 60068-2-2

Damp heat test, steady state

Test Ca for 4 days at +40 C


and humidity 93%

IEC 60068-2-78

Damp heat test, cyclic

Test Db for 6 cycles at +25


to +55 C and humidity 93 to
95% (1 cycle = 24 hours)

IEC 60068-2-30

1047
Technical reference manual

Section 19
IED hardware

1MRK 505 222-UEN B

Table 720:

CE compliance

Test

According to

Immunity

EN 50263

Emissivity

EN 50263

Low voltage directive

EN 50178

Table 721:

Mechanical tests

Test

Type test values

Reference standards

Vibration response test

Class II

IEC 60255-21-1

Vibration endurance test

Class I

IEC 60255-21-1

Shock response test

Class II

IEC 60255-21-2

Shock withstand test

Class I

IEC 60255-21-2

Bump test

Class I

IEC 60255-21-2

Seismic test

Class II

IEC 60255-21-3

1048
Technical reference manual

Section 20
Labels

1MRK 505 222-UEN B

Section 20

Labels

About this chapter


This chapter includes descriptions of the different labels and where to find them.

20.1

Labels on IED
Front view of IED

1
2
3
4
5
6
6

7
xx06000574.ep
IEC06000574 V1 EN

1049
Technical reference manual

Section 20
Labels

1MRK 505 222-UEN B

Product type, description and serial number

Order number, dc supply voltage and rated


frequency

Optional, customer specific information

Manufacturer

Transformer input module, rated currents


and voltages

Transformer designations

Ordering and serial number

IEC06000577-CUSTOMER-SPECIFIC V1 EN

IEC06000576-POS-NO V1 EN

1050
Technical reference manual

Section 20
Labels

1MRK 505 222-UEN B

Rear view of IED

1
2
3

4
en06000573.ep
IEC06000573 V1 EN

Warning label

Caution label

Class 1 laser product label

IEC06000575 V1 EN

Warning label

1051
Technical reference manual

1052

Section 21
Connection diagrams

1MRK 505 222-UEN B

Section 21

Connection diagrams

This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.

1053
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 1 V1 EN

1054
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 2 670 1.2 V1 EN

1055
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 3 670 1.2 V1 EN

1056
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 4 670 1.2 V1 EN

1057
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 5 670 1.2 V1 EN

1058
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 6 670 1.2 V1 EN

1059
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 7 670 1.2 V1 EN

1060
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 8 670 1.2 V1 EN

1061
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 9 670 1.2 V1 EN

1062
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 10 670 1.2 V1 EN

1063
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 11 670 1.2 V1 EN

1064
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 12 670 1.2 V1 EN

1065
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 13 670 1.2 V1 EN

1066
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 14 670 1.2 V1 EN

1067
Technical reference manual

Section 21
Connection diagrams

1MRK 505 222-UEN B

1MRK002801-AC 15 670 1.2 V1 EN

1068
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Section 22

Inverse time characteristics

About this chapter


This chapter describes current and voltage dependant time functionality. Both
ANSI and IEC Inverse time curves and tables are included.

22.1

Application
In order to assure time selectivity between different overcurrent protections at
different points in the network different time delays for the different protections are
normally used. The simplest way to do this is to use definite time-lag. In more
sophisticated applications current dependent time characteristics are used. Both
alternatives are shown in a simple application with three overcurrent protections
operating in series.

I>

I>

I>
xx05000129.vsd

IEC05000129 V1 EN

Figure 566:

Three overcurrent protections operating in series


Stage 3

Time
Stage 2

Stage 1

Stage 2

Stage 1

Stage 1

Fault point
position

en05000130.vsd
IEC05000130 V1 EN

Figure 567:

Definite time overcurrent characteristics

1069
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Time

Fault point
position
en05000131.vsd
IEC05000131 V1 EN

Figure 568:

Inverse time overcurrent characteristics with inst. function

The inverse time characteristic makes it possible to minimize the fault clearance
time and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of
following factors, in a simple case with two protections in series:

Difference between pickup time of the protections to be co-ordinated


Opening time of the breaker closest to the studied fault
Reset times of the protections
Margin dependent of the time delay inaccuracy of the protections

Assume we have the following network case.

1070
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A1

B1

I>

I>

Feeder

Time axis

t=0

t=t1

t=t2

t=t3
en05000132.vsd

IEC05000132 V1 EN

Figure 569:

Selectivity steps for a fault on feeder B1

where:
t=0

is The fault occurs

t=t1

is Protection B1 trips

t=t2

is Breaker at B1 opens

t=t3

is Protection A1 resets

In the case protection B1 shall operate without any intentional delay


(instantaneous). When the fault occurs the protections start to detect the fault
current. After the time t1 the protection B1 send a trip signal to the circuit breaker.
The protection A1 starts its delay timer at the same time, with some deviation in
time due to differences between the two protections. There is a possibility that A1
will start before the trip is sent to the B1 circuit breaker. At the time t2 the circuit
breaker B1 has opened its primary contacts and thus the fault current is interrupted.
The breaker time (t2 - t1) can differ between different faults. The maximum
opening time can be given from manuals and test protocols. Still at t2 the timer of
protection A1 is active. At time t3 the protection A1 is reset, that is the timer is stopped.
In most applications it is required that the times shall reset as fast as possible when
the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type
of delayed reset time of the overcurrent function. This can be the case in the
following applications:

1071
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

If there is a risk of intermittent faults. If the current IED, close to the faults,
starts and resets there is a risk of unselective trip from other protections in the
system.
Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
Overcurrent protection functions are sometimes used as release criterion for
other protection functions. It can often be valuable to have a reset delay to
assure the release function.

22.2

Principle of operation

22.2.1

Mode of operation
The function can operate in a definite time-lag mode or in a current definite inverse
time mode. For the inverse time characteristic both ANSI and IEC based standard
curves are available. Also programmable curve types are supported via the
component inputs: p, A, B, C pr, tr, and cr.
Different characteristics for reset delay can also be chosen.
If current in any phase exceeds the set start current value (here internal signal
startValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the
current level used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is
reached or until the current drops below the reset value (start value minus the
hysteresis) and the reset time has elapsed.
For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are
chosen.
The general expression for inverse time curves is according to equation 193.

A
k
t[ s ] =
+
B
i p

-C

in >

(Equation 193)

EQUATION1189 V1 EN

where:
p, A, B, C

are constants defined for each curve type,

in>

is the set start current for step n,

is set time multiplier for step n and

is the measured current.

1072
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can
be seen:

i p

(top - B k )
- C = Ak
in >

(Equation 194)

EQUATION1190 V1 EN

where:
top

is the operating time of the protection

The time elapsed to the moment of trip is reached when the integral fulfils
according to equation 195, in addition to the constant time delay:

i p

in > - C dt A k
0

(Equation 195)

EQUATION1191 V1 EN

For the numerical protection the sum below must fulfil the equation for trip.

i( j ) p

- C A k
j =1 in >

Dt

(Equation 196)

EQUATION1192 V1 EN

where:
j=1

is the first protection execution cycle when a fault has been


detected, that is, when

i
in >

>1

EQUATION1193 V1 EN

Dt

is the time interval between two consecutive executions of the


protection algorithm,

is the number of the execution of the algorithm when the trip


time equation is fulfilled, that is, when a trip is given and

i (j)

is the fault current at time j

For inverse time operation, the inverse time characteristic is selectable. Both the
IEC and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 570.

1073
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Operate
time

tMin

IMin

Current
IEC05000133-3-en.vsd

IEC05000133 V2 EN

Figure 570:

Minimum time-lag operation for the IEC curves

In order to fully comply with IEC curves definition setting parameter tMin shall be
set to the value which is equal to the operating time of the selected IEC inverse
time curve for measured current of twenty times the set current start value. Note
that the operating time value is dependent on the selected setting value for time
multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
The RI inverse time curve emulates the characteristic of the electromechanical
ASEA relay RI. The curve is described by equation 198:

k
t[ s ] =
in >
0.339 - 0.235

i
EQUATION1194 V1 EN

(Equation 198)

where:
in>

is the set start current for step n

is set time multiplier for step n

is the measured current

1074
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

The RD inverse curve gives a logarithmic delay, as used in the Combiflex


protection RXIDG. The curve enables a high degree of selectivity required for
sensitive residual earth-fault current protection, with ability to detect high-resistive
earth faults. The curve is described by equation 199:

k in >

t[ s ] = 5.8 - 1.35 ln
EQUATION1195 V1 EN

(Equation 199)

where:
in>

is the set start current for step n,

is set time multiplier for step n and

is the measured current

If the curve type programmable is chosen, the user can make a tailor made inverse
time curve according to the general equation 200.

t[ s ] =
+ Bk
i p

-C

in >

EQUATION1196 V1 EN

(Equation 200)

Also the reset time of the delayed function can be controlled. There is the
possibility to choose between three different reset time-lags.

Instantaneous Reset
IEC Reset
ANSI Reset.

If instantaneous reset is chosen the timer will be reset directly when the current
drops below the set start current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the
current drops below the set start current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after
fault clearance (when the current drops below the start current level minus the
hysteresis). The timer will reset according to equation 201.

1075
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

tr
k
t [s] =
2
i

-1
in >

(Equation 201)

EQUATION1197 V2 EN

where:
The set value tr is the reset time in case of zero current after fault clearance.

The possibility of choice of reset characteristics is to some extent dependent of the


choice of time delay characteristic.
For the definite time delay characteristics the possible reset time settings are
instantaneous and IEC constant time reset.
For ANSI inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time.
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous and IEC set constant time reset).
For the programmable inverse time delay characteristics all three types of reset
time characteristics are available; instantaneous, IEC constant time reset and ANSI
current dependent reset time. If the current dependent type is used settings pr, tr
and cr must be given, see equation 202:

tr
k
t [s] =
pr
i

- cr
in >

EQUATION1198 V2 EN

(Equation 202)

For RI and RD inverse time delay characteristics the possible delay time settings
are instantaneous and IEC constant time reset.
When inverse time overcurrent characteristic is selected, the
operate time of the stage will be the sum of the inverse time delay
and the set definite time delay. Thus, if only the inverse time delay
is required, it is of utmost importance to set the definite time delay
for that stage to zero.

1076
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

22.3

Inverse characteristics
Table 722:

ANSI Inverse time characteristics

Function

Range or value

Operating characteristic:

Accuracy

k = (0.05-999) in steps of
0.01 unless otherwise stated

ANSI Extremely Inverse

A=28.2, B=0.1217, P=2.0 ,


tr=29.1

ANSI/IEEE C37.112,
class 5 + 40 ms

ANSI Very inverse

A=19.61, B=0.491, P=2.0 ,


tr=21.6

ANSI Normal Inverse

A=0.0086, B=0.0185,
P=0.02, tr=0.46

ANSI Moderately Inverse

A=0.0515, B=0.1140,
P=0.02, tr=4.85

ANSI Long Time Extremely Inverse

A=64.07, B=0.250, P=2.0,


tr=30

ANSI Long Time Very Inverse

A=28.55, B=0.712, P=2.0,


tr=13.46

ANSI Long Time Inverse

k=(0.05-999) in steps of 0.01


A=0.086, B=0.185, P=0.02,
tr=4.6

t =

A
P
( I - 1)

+ B k

EQUATION1249-SMALL V1 EN

Reset characteristic:
t =

(I

tr
2

-1

EQUATION1250-SMALL V1 EN

I = Imeasured/Iset

1077
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Table 723:

IEC Inverse time characteristics

Function

Range or value

Operating characteristic:

Accuracy

k = (0.05-999) in steps of 0.01

Time delay to reset, IEC inverse time

(0.000-60.000) s

0.5% of set time 10


ms

IEC Normal Inverse

A=0.14, P=0.02

IEC Very inverse

A=13.5, P=1.0

IEC 60255-3, class 5 +


40 ms

IEC Inverse

A=0.14, P=0.02

IEC Extremely inverse

A=80.0, P=2.0

IEC Short time inverse

A=0.05, P=0.04

IEC Long time inverse

A=120, P=1.0

Programmable characteristic
Operate characteristic:

k = (0.05-999) in steps of 0.01


A=(0.005-200.000) in steps
of 0.001
B=(0.00-20.00) in steps of
0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of
0.001
TR=(0.005-100.000) in steps
of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of
0.001

t =

A
P
k
( I - 1)

EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

t =

A
P
(I - C )

+ B k

EQUATION1370-SMALL V1 EN

Reset characteristic:
t =

(I

TR
PR

- CR

IEC 60255, class 5 + 40


ms

EQUATION1253-SMALL V1 EN

I = Imeasured/Iset

Table 724:

RI and RD type inverse time characteristics

Function

Range or value

RI type inverse characteristic


1

t =

0.339 -

Accuracy

k = (0.05-999) in steps of 0.01

IEC 60255-3, class 5 +


40 ms

k = (0.05-999) in steps of 0.01

IEC 60255-3, class 5 +


40 ms

0.236
I

EQUATION1137-SMALL V1 EN

I = Imeasured/Iset
RD type logarithmic inverse characteristic

t = 5.8 - 1.35 In

I
k

EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

1078
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Table 725:

Inverse time characteristics for overvoltage protection

Function

Range or value

Type A curve:
t =

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated

Accuracy
Class 5 +40 ms

U -U >

U>

EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured
Type B curve:
t =

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated

k 480

32 U - U > - 0.5

U >

2.0

- 0.035

EQUATION1437-SMALL V1 EN

Type C curve:
t =

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated

k 480

32 U - U > - 0.5

U >

3.0

- 0.035

EQUATION1438-SMALL V1 EN

Programmable curve:
t =

kA

B U - U >

U >

EQUATION1439-SMALL V1 EN

-C

+D

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated
A = (0.005-200.000)
in steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in
steps of 0.1
D = (0.000-60.000)
in steps of 0.001
P = (0.000-3.000) in
steps of 0.001

1079
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Table 726:

Inverse time characteristics for undervoltage protection

Function

Range or value

Type A curve:

t =

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated

Accuracy
Class 5 +40 ms

U < -U

U<

EQUATION1431-SMALL V1 EN

U< = Uset
U = UVmeasured
Type B curve:

t =

k 480

32 U < -U - 0.5

U <

2.0

+ 0.055

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated

EQUATION1432-SMALL V1 EN

U< = Uset
U = Umeasured
Programmable curve:

kA
+D
t =
P
U < -U

-C
B
U <


EQUATION1433-SMALL V1 EN

U< = Uset
U = Umeasured

k = (0.05-1.10) in
steps of 0.01 unless
otherwise stated
A = (0.005-200.000)
in steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in
steps of 0.1
D = (0.000-60.000)
in steps of 0.001
P = (0.000-3.000) in
steps of 0.001

1080
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

Table 727:

Inverse time characteristics for residual overvoltage protection

Function

Range or value

Type A curve:
t =

k = (0.05-1.10) in steps of
0.01

Accuracy
Class 5 +40 ms

U -U >

U>

EQUATION1436-SMALL V1 EN

U> = Uset
U = Umeasured
Type B curve:
t =

k = (0.05-1.10) in steps of
0.01
k 480

32 U - U > - 0.5

U >

2.0

- 0.035

EQUATION1437-SMALL V1 EN

Type C curve:
t =

k = (0.05-1.10) in steps of
0.01
k 480

32 U - U > - 0.5

U >

3.0

- 0.035

EQUATION1438-SMALL V1 EN

Programmable curve:

t =

kA

B U - U >

U >

EQUATION1439-SMALL V1 EN

-C

+D

k = (0.05-1.10) in steps of
0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001

1081
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070750 V2 EN

Figure 571:

ANSI Extremely inverse time characteristics

1082
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070751 V2 EN

Figure 572:

ANSI Very inverse time characteristics

1083
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070752 V2 EN

Figure 573:

ANSI Normal inverse time characteristics

1084
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070753 V2 EN

Figure 574:

ANSI Moderately inverse time characteristics

1085
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070817 V2 EN

Figure 575:

ANSI Long time extremely inverse time characteristics

1086
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070818 V2 EN

Figure 576:

ANSI Long time very inverse time characteristics

1087
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070819 V2 EN

Figure 577:

ANSI Long time inverse time characteristics

1088
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070820 V2 EN

Figure 578:

IEC Normal inverse time characteristics

1089
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070821 V2 EN

Figure 579:

IEC Very inverse time characteristics

1090
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070822 V2 EN

Figure 580:

IEC Inverse time characteristics

1091
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070823 V2 EN

Figure 581:

IEC Extremely inverse time characteristics

1092
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070824 V2 EN

Figure 582:

IEC Short time inverse time characteristics

1093
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070825 V2 EN

Figure 583:

IEC Long time inverse time characteristics

1094
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070826 V2 EN

Figure 584:

RI-type inverse time characteristics

1095
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

A070827 V2 EN

Figure 585:

RD-type inverse time characteristics

1096
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN

Figure 586:

Inverse curve A characteristic of overvoltage protection

1097
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN

Figure 587:

Inverse curve B characteristic of overvoltage protection

1098
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN

Figure 588:

Inverse curve C characteristic of overvoltage protection

1099
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN

Figure 589:

Inverse curve A characteristic of undervoltage protection

1100
Technical reference manual

Section 22
Inverse time characteristics

1MRK 505 222-UEN B

GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN

Figure 590:

Inverse curve B characteristic of undervoltage protection

1101
Technical reference manual

1102

Section 23
Glossary

1MRK 505 222-UEN B

Section 23

Glossary

About this chapter


This chapter contains a glossary with terms, acronyms and abbreviations used in
ABB technical documentation.
AC

Alternating current

ACT

Application configuration tool within PCM600

A/D converter

Analog-to-digital converter

ADBS

Amplitude deadband supervision

ADM

Analog digital conversion module, with time synchronization

AI

Analog input

ANSI

American National Standards Institute

AR

Autoreclosing

ArgNegRes

Setting parameter/ZD/

ArgDir

Setting parameter/ZD/

ASCT

Auxiliary summation current transformer

ASD

Adaptive signal detection

AWG

American Wire Gauge standard

BBP

Busbar protection

BFP

Breaker failure protection

BI

Binary input

BIM

Binary input module

BOM

Binary output module

BOS

Binary outputs status

BR

External bistable relay

BS

British Standards

BSR

Binary signal transfer function, receiver blocks

BST

Binary signal transfer function, transmit blocks

C37.94

IEEE/ANSI protocol used when sending binary signals


between IEDs

CAN

Controller Area Network. ISO standard (ISO 11898) for


serial communication

CB

Circuit breaker
1103

Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

CBM

Combined backplane module

CCITT

Consultative Committee for International Telegraph and


Telephony. A United Nations-sponsored standards body
within the International Telecommunications Union.

CCM

CAN carrier module

CCVT

Capacitive Coupled Voltage Transformer

Class C

Protection Current Transformer class as per IEEE/ ANSI

CMPPS

Combined megapulses per second

CMT

Communication Management tool in PCM600

CO cycle

Close-open cycle

Codirectional

Way of transmitting G.703 over a balanced line. Involves


two twisted pairs making it possible to transmit information
in both directions

COMTRADE

Standard format according to IEC 60255-24

Contra-directional

Way of transmitting G.703 over a balanced line. Involves


four twisted pairs, two of which are used for transmitting
data in both directions and two for transmitting clock signals

CPU

Central processor unit

CR

Carrier receive

CRC

Cyclic redundancy check

CROB

Control relay output block

CS

Carrier send

CT

Current transformer

CVT

Capacitive voltage transformer

DAR

Delayed autoreclosing

DARPA

Defense Advanced Research Projects Agency (The US


developer of the TCP/IP protocol etc.)

DBDL

Dead bus dead line

DBLL

Dead bus live line

DC

Direct current

DFC

Data flow control

DFT

Discrete Fourier transform

DHCP

Dynamic Host Configuration Protocol

DIP-switch

Small switch mounted on a printed circuit board

DI

Digital input

DLLB

Dead line live bus

1104
Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

DNP

Distributed Network Protocol as per IEEE/ANSI Std.


1379-2000

DR

Disturbance recorder

DRAM

Dynamic random access memory

DRH

Disturbance report handler

DSP

Digital signal processor

DTT

Direct transfer trip scheme

EHV network

Extra high voltage network

EIA

Electronic Industries Association

EMC

Electromagnetic compatibility

EMF

(Electric Motive Force)

EMI

Electromagnetic interference

EnFP

End fault protection

EPA

Enhanced performance architecture

ESD

Electrostatic discharge

FCB

Flow control bit; Frame count bit

FOX 20

Modular 20 channel telecommunication system for speech,


data and protection signals

FOX 512/515

Access multiplexer

FOX 6Plus

Compact time-division multiplexer for the transmission of


up to seven duplex channels of digital data over optical fibers

G.703

Electrical and functional description for digital lines used by


local telephone companies. Can be transported over
balanced and unbalanced lines

GCM

Communication interface module with carrier of GPS


receiver module

GDE

Graphical display editor within PCM600

GI

General interrogation command

GIS

Gas-insulated switchgear

GOOSE

Generic object-oriented substation event

GPS

Global positioning system

GTM

GPS Time Module

HDLC protocol

High-level data link control, protocol based on the HDLC


standard

HFBR connector
type

Plastic fiber connector

HMI

Human-machine interface
1105

Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

HSAR

High speed autoreclosing

HV

High-voltage

HVDC

High-voltage direct current

IDBS

Integrating deadband supervision

IEC

International Electrical Committee

IEC 60044-6

IEC Standard, Instrument transformers Part 6:


Requirements for protective current transformers for
transient performance

IEC 60870-5-103

Communication standard for protective equipment. A serial


master/slave protocol for point-to-point communication

IEC 61850

Substation automation communication standard

IEEE

Institute of Electrical and Electronics Engineers

IEEE 802.12

A network technology standard that provides 100 Mbits/s on


twisted-pair or optical fiber cable

IEEE P1386.1

PCI Mezzanine Card (PMC) standard for local bus modules.


References the CMC (IEEE P1386, also known as Common
Mezzanine Card) standard for the mechanics and the PCI
specifications from the PCI SIG (Special Interest Group) for
the electrical EMF (Electromotive force).

IED

Intelligent electronic device

I-GIS

Intelligent gas-insulated switchgear

IOM

Binary input/output module

Instance

When several occurrences of the same function are available


in the IED, they are referred to as instances of that function.
One instance of a function is identical to another of the same
kind but has a different number in the IED user interfaces.
The word "instance" is sometimes defined as an item of
information that is representative of a type. In the same way
an instance of a function in the IED is representative of a
type of function.

IP

1. Internet protocol. The network layer for the TCP/IP


protocol suite widely used on Ethernet networks. IP is a
connectionless, best-effort packet-switching protocol. It
provides packet routing, fragmentation and reassembly
through the data link layer.
2. Ingression protection, according to IEC standard

IP 20

Ingression protection, according to IEC standard, level 20

IP 40

Ingression protection, according to IEC standard, level 40

IP 54

Ingression protection, according to IEC standard, level 54

IRF

Internal failure signal

1106
Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

IRIG-B:

InterRange Instrumentation Group Time code format B,


standard 200

ITU

International Telecommunications Union

LAN

Local area network

LIB 520

High-voltage software module

LCD

Liquid crystal display

LDCM

Line differential communication module

LDD

Local detection device

LED

Light-emitting diode

LNT

LON network tool

LON

Local operating network

MCB

Miniature circuit breaker

MCM

Mezzanine carrier module

MIM

Milli-ampere module

MPM

Main processing module

MVB

Multifunction vehicle bus. Standardized serial bus originally


developed for use in trains.

NCC

National Control Centre

NUM

Numerical module

OCO cycle

Open-close-open cycle

OCP

Overcurrent protection

OEM

Optical ethernet module

OLTC

On-load tap changer

OV

Over-voltage

Overreach

A term used to describe how the relay behaves during a fault


condition. For example, a distance relay is overreaching
when the impedance presented to it is smaller than the
apparent impedance to the fault applied to the balance point,
that is, the set reach. The relay sees the fault but perhaps it
should not have seen it.

PCI

Peripheral component interconnect, a local data bus

PCM

Pulse code modulation

PCM600

Protection and control IED manager

PC-MIP

Mezzanine card standard

PISA

Process interface for sensors & actuators

PMC

PCI Mezzanine card


1107

Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

POR

Permissive overreach

POTT

Permissive overreach transfer trip

Process bus

Bus or LAN used at the process level, that is, in near


proximity to the measured and/or controlled components

PSM

Power supply module

PST

Parameter setting tool within PCM600

PT ratio

Potential transformer or voltage transformer ratio

PUTT

Permissive underreach transfer trip

RASC

Synchrocheck relay, COMBIFLEX

RCA

Relay characteristic angle

RFPP

Resistance for phase-to-phase faults

RFPE

Resistance for phase-to-earth faults

RISC

Reduced instruction set computer

RMS value

Root mean square value

RS422

A balanced serial interface for the transmission of digital


data in point-to-point connections

RS485

Serial link according to EIA standard RS485

RTC

Real-time clock

RTU

Remote terminal unit

SA

Substation Automation

SBO

Select-before-operate

SC

Switch or push button to close

SCS

Station control system

SCADA

Supervision, control and data acquisition

SCT

System configuration tool according to standard IEC 61850

SDU

Service data unit

SLM

Serial communication module. Used for SPA/LON/IEC/


DNP3 communication.

SMA connector

Subminiature version A, A threaded connector with constant


impedance.

SMT

Signal matrix tool within PCM600

SMS

Station monitoring system

SNTP

Simple network time protocol is used to synchronize


computer clocks on local area networks. This reduces the
requirement to have accurate hardware clocks in every
embedded system in a network. Each embedded node can

1108
Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

instead synchronize with a remote clock, providing the


required accuracy.
SPA

Strmberg protection acquisition, a serial master/slave


protocol for point-to-point communication

SRY

Switch for CB ready condition

ST

Switch or push button to trip

Starpoint

Neutral point of transformer or generator

SVC

Static VAr compensation

TC

Trip coil

TCS

Trip circuit supervision

TCP

Transmission control protocol. The most common transport


layer protocol used on Ethernet and the Internet.

TCP/IP

Transmission control protocol over Internet Protocol. The de


facto standard Ethernet protocols incorporated into 4.2BSD
Unix. TCP/IP was developed by DARPA for Internet
working and encompasses both network layer and transport
layer protocols. While TCP and IP specify two protocols at
specific protocol layers, TCP/IP is often used to refer to the
entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.

TEF

Time delayed earth-fault protection function

TNC connector

Threaded Neill-Concelman, a threaded constant impedance


version of a BNC connector

TPZ, TPY, TPX,


TPS

Current transformer class according to IEC

UMT

User management tool

Underreach

A term used to describe how the relay behaves during a fault


condition. For example, a distance relay is underreaching
when the impedance presented to it is greater than the
apparent impedance to the fault applied to the balance point,
that is, the set reach. The relay does not see the fault but
perhaps it should have seen it. See also Overreach.

U/I-PISA

Process interface components that deliver measured voltage


and current values

UTC

Coordinated Universal Time. A coordinated time scale,


maintained by the Bureau International des Poids et Mesures
(BIPM), which forms the basis of a coordinated
dissemination of standard frequencies and time signals. UTC
is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize
it with Universal Time 1 (UT1), thus allowing for the
eccentricity of the Earth's orbit, the rotational axis tilt (23.5
1109

Technical reference manual

Section 23
Glossary

1MRK 505 222-UEN B

degrees), but still showing the Earth's irregular rotation, on


which UT1 is based. The Coordinated Universal Time is
expressed using a 24-hour clock, and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where
it is also sometimes known by the military name, "Zulu
time." "Zulu" in the phonetic alphabet stands for "Z", which
stands for longitude zero.
UV

Undervoltage

WEI

Weak end infeed logic

VT

Voltage transformer

X.21

A digital signalling interface primarily used for telecom


equipment

3IO

Three times zero-sequence current. Often referred to as the


residual or the earth-fault current

3UO

Three times the zero sequence voltage. Often referred to as


the residual voltage or the neutral point voltage

1110
Technical reference manual

1111

ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone
+46 (0) 21 32 50 00
Fax
+46 (0) 21 14 69 18
www.abb.com/substationautomation

1MRK 505 222-UEN B Copyright 2011 ABB. All rights reserved.

Contact us

You might also like