You are on page 1of 29

ANUPPUR THERMAL POWER PROJECT

PHASE-I (2X600MW)
AT ANUPPUR, MADHYA PRADESH (INDIA)
Owner:

MB POWER (MADHYA PRADESH) LTD.


235-B, OKHLA INDUSTRIAL ESTATE, PHASE-III
NEW DELHI 110 020

Owners
Consultant:

EPC
Contractor:

LANCO INFRATECH LTD. (EPC DIVISION)


PLOT NO. 404-405, UDYOG VIHAR PHASE-III
GURGAON, HARYANA, INDIA

Vendor:

KEC INTERNATIONAL LIMITED

TCE.5657B-EL-CO-700-601

12-07-2013

Document Title: Technical Data Sheet

LITL Document No.:


LITL-020-ELV-320-S-71933-R3

Vendor Doc. No.

JB / GVC

12-07-2013

LANCO INFRATECH LTD. (EPC DIVISION)


PLOT NO. 404-405, UDYOG VIHAR PHASE-III
GURGAON, HARYANA (INDIA)

ANUPPUR THERMAL POWER PROJECT


PHASE-I (2X600MW)
AT ANUPPUR, MADHYA PRADESH (INDIA)
LITL Document No.

R3
REV
NO.

DATE

STATUS

INTLS

SGN

PRPD. BY

INTLS

SGN

CHKD. BY

INTLS

SGN

APPR. BY

INTLS

SGN

ISSUE
AUTHORISATION

(This document is a property of LIT Ltd. This is not transferable and shall not
be used for any purpose other than for which it is supplied)

GUARANTEED TECHNICAL PARTICULARS


Make

Country of Manufacturer

KEC International Ltd


'RPG-Cables'

KEC International
Ltd 'RPG-Cables'

KEC International
Ltd 'RPG-Cables'

India

India

India

Type Designation

A2XFY(P):FRLS

A2XFY(P):FRLS

A2XFY(P):FRLS

Applicable Standard

IS:7098 pt(1)/88

IS:7098 pt(1)/88

IS:7098 pt(1)/88

Cable size

3C x 16 Sq.mm

3C x 35 Sq.mm

3C x 70 Sq.mm

No. of core

Rated voltage
Continuous current rating
for
max.
conductor
temperature:

1100 V

1100 V

1100 V

When laid in air at an


ambient Temp. of 50 deg. C
When buried in soil having
thermal Resistivity of 150
deg. C Cm/W at a depth of
1000 mm in ground amb.
Temp. of 40 deg. C.
Short circuit withstand
capacity and duration for
one second

62

104

158

65

102

146

1.51

3.31

6.61

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

H4 Grade
Aluminium ( Class-2
) to IS: 8130/1984

H4 Grade Aluminium
( Class-2 ) to IS:
8130/1984

8
a.

b.

9
a.
9

Conductor
Conductor
Material

a.
b.

No.
of
strand/Approx
diameter of each strand

7/1.72

7/2.52

19/2.14

c.

Shape of Conductor

Sector

Sector

Sector

d.

Diameter of conductor

4.1

6.1

8.6

16

35

70

1.91

0.868

0.443

90

90

90

250

250

250
Cross Linked
Polyethylene(XLPE)
as per
IS:7098/I/1988
1.10

g.

Nominal
cross
section
areain sq. mm.
Max. D. C. resistance at 20
deg. C
Conductor temperature

h.

S/C conductor temprature

e.
f.

10

Insulation

b.

Nominal thickness (in mm)

0.70

Cross Linked
Polyethylene(XLPE)
as per
IS:7098/I/1988
0.90

c.

Minimum thickness(in mm)

0.53

0.71

0.89

d.

Identification of cores

Red,Yellow & Blue

Red,Yellow & Blue

Red,Yellow & Blue

e.

Insulation temperature

90

90

90

Sioplas single
Extrusion & Hot Water
Curing

Sioplas single
Extrusion & Hot
Water Curing

Sioplas single
Extrusion & Hot
Water Curing

5.5

7.9

10.8

0.30

0.30

0.40

Material
a.

f.

Type of extrusion & curing


process

g.

Diameter over insulation

a.

Inner sheath
Min. thichkness

11

Cross Linked
Polyethylene(XLPE) as
per IS:7098/I/1988

b.

Wrapped or Extruded

c.

Colour
Approx. dia. Over inner
sheath
Material and Type of inner
sheath (if required)

d.
e.

f.

12

Filler material

Extruded

Extruded

Extruded

Black

Black

Black

13.0

17.9

24.0

PVC Type `ST2' to


IS:5831/84

PVC Type `ST2' to


IS:5831/84

PVC Type `ST2' to


IS:5831/84

Gaps can be filled by


PVC during the
extruded PVC
innersheathing
wherever applicable.

Gaps can be filled by


PVC during the
extruded PVC
innersheathing
wherever applicable.

Gaps can be filled by


PVC during the
extruded PVC
innersheathing
wherever applicable.

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Extruded "FRLS"
PVC Type 'ST2' as
per IS:5831/84

Extruded "FRLS"
PVC Type 'ST2' as
per IS:5831/84

Black

Black

Black

1.24

1.40

1.56

2 mm

2 mm

2 mm

Galvanised Steel Flat


Strip as per IS:3975

Galvanised Steel Flat


Strip as per IS:3975

Galvanised Steel Flat


Strip as per IS:3975

4.0 x 0.8

4.0 x 0.8

4.0 x 0.8

Yes

Yes

Yes

15.0

19.9

25.9

Outer sheath
a.

b.
c.
d.
e.
13

Type of Outer sheath


Material
Colour
Min. thickness of Outer
sheath
Tolerance on diameter
Armour

a.

Material & shape

b.

Diameter of wire
:
Whether
galvanized:(Yes/No)
Diameter of cable over
armouring
mm):

c.
d.

e.

Armour coverage area (%)

90%

90%

90%

f.

Maximum DC resistance at
20C (ohm/km)

4.77

4.16

3.12

11

15

1.91

0.868

0.443

2.44

1.11

0.567

0.0815

0.0794

0.0752

0.401

0.464

0.490

2.4414

1.1128

0.572

12.7

18.4

25.1

g.

14
a.
b.

No of wires/Strips required
Electrical
Parameter
at
maximum
Operating
temperature
Max. DC resistance at
20degC
A.C resistance at 90degC

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

a.

Finished Cable
Diameter over laid up core
(Calculated)

b.

Diameter under armor in


mm
(Claculated)

13.3

19.0

25.9

c.

Diameter over armor in mm


(Calculated)

14.9

20.6

27.5

3 kg/mm of
Aluminium area

3 kg/mm of
Aluminium area

3 kg/mm of
Aluminium area

Wooden

Wooden

Wooden

950 x 300 x 650

1400 x 600 x 650

1200 x 575 x 650

608

1088

886.5

15

16

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

c.

Shipping Weight(App)

d.
e.

Drum
Weight(Without
cable) (App)
Cable pulling eye yes/No
bending

105

270

220

No

No

No

12 times Overall
diameter

12 times Overall
diameter

12 times Overall
diameter

18

Recommended
radius

19

Derating Factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

20

Group rating factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

18

24

30

503

818

1333

1000

1000

500

Min. 29%

Min. 29%

Min. 29%

Min. 2500C

Min. 2500C

Min. 2500C

Max. 60%

Max. 60%

Max. 60%

20% Max.

20% Max.

20% Max.

As per IEC-603321/SS-424-1475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."
As per IS:7098
part(1)/88
PVC End Caps

As per IEC-603321/SS-424-1475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."
As per IS:7098
part(1)/88
PVC End Caps

As per IEC-603321/SS-424-1475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."
As per IS:7098
part(1)/88
PVC End Caps

23

Overall dia. of cable (in


mm)( 2mm tolerance)
Weight per 1000 metre (in
Kg.)
Standard
drum
length
offered

24

FRLS Properties on outer

25

25c

Oxygen index in room (%)


Minimum
temperature
index(C)
Maximum smoke density
rating(%)
Maximum
acid
gas
generation(%)

25d.

Flammability test

21
22

25a.
25b.

26

Embossing on outer
Sheath

27

Marking on Drums

28

Type of end sealing

GUARANTEED TECHNICAL PARTICULARS


Make

Country of Manufacturer

KEC International
Ltd 'RPG-Cables'

KEC International
Ltd 'RPG-Cables'

KEC International Ltd


'RPG-Cables'

India

India

India

Type Designation

A2XWaY:FRLS

A2XWaY:FRLS

A2XWaY:FRLS

Applicable Standard

IS:7098 pt(1)/88

IS:7098 pt(1)/88

IS:7098 pt(1)/88

Cable size

1C x 16 Sq.mm

1C x 35 Sq.mm

1C x 70 Sq.mm

No. of core

1100 V

1100 V

1100 V

65

109

169

68

102

148

Rated voltage
Continuous
current
rating
for
max.
conductor temperature:
When laid in air at an
ambient Temp. of 50
deg. C
When buried in soil
having
thermal
Resistivity of 150 deg. C
Cm/W at a depth of
1000 mm in ground
amb. Temp. of 40 deg. C.
Short circuit withstand
capacity and duration
for one second

a.

Conductor

1.51

3.31

6.61

H4 Grade
Aluminium ( Class2 ) to IS:
8130/1984

H4 Grade Aluminium
( Class-2 ) to IS:
8130/1984

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

7/1.72

7/2.52

19/2.14

Compacted Circular

Compacted Circular

Compacted Circular

5.0

6.8

9.6

16

35

70

1.91

0.868

0.443

90

90

90

250

250

250

Cross Linked
Polyethylene(XLPE)
as per
IS:7098/I/1988

Cross Linked
Polyethylene(XLPE)
as per
IS:7098/I/1988

Cross Linked
Polyethylene(XLPE) as
per IS:7098/I/1988

1.00

1.20

1.40

0.80

0.98

1.16

Black

Black

Black

90

90

90

Sioplas single
Extrusion & Hot
Water Curing

Sioplas single
Extrusion & Hot
Water Curing

Sioplas single Extrusion


& Hot Water Curing

a.

b.

Conductor
Material
a.
b.

No. of strand/Approx
diameter of each strand

c.

Shape of Conductor

d.

Diameter of conductor

e.
f.
g.
h.
10

Nominal cross section


areain sq. mm.
Max. D. C. resistance at
20 deg. C
Conductor temperature
S/C
conductor
temprature
Insulation
Material

a.

d.

Nominal thickness (in


mm)
Minimum
thickness(in
mm)
Identification of cores

e.

Insulation temperature

b.
c.

f.

Type of extrusion &


curing process

g.

Diameter over insulation

7.0

9.2

12.4

a.

Inner sheath
Min. thichkness

N.A

N.A

N.A

b.

Wrapped or Extruded

N.A

N.A

N.A

c.

Colour
Approx. dia. Over inner
sheath
Material and Type of
inner sheath (if required)

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

N.A

Filler material

N.A

N.A

N.A

Extruded "FRLS"
PVC Type 'ST2' as
per IS:5831/84

Extruded "FRLS"
PVC Type 'ST2' as
per IS:5831/84

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Black

Black

Black

1.24

1.24

1.24

2 mm

2 mm

2 mm

Hard Drawn
Aluminium Round
Wire as per IS:8130

Hard Drawn
Aluminium Round
Wire as per IS:8130

Hard Drawn Aluminium


Round Wire as per
IS:8130

1.4

1.4

1.4

N.A

N.A

N.A

10.2

12.3

15.4

90%

90%

90%

1.35

0.76

0.99

14.0

19.0

25.0

1.91

0.868

0.443

2.44

1.11

0.567

0.101

0.097

0.091

11

d.
e.
f.
12

Outer sheath
a.
b.
c.
d.
e.

13

Type of Outer sheath


Material
Colour
Min. thickness of Outer
sheath
Tolerance on diameter
Armour

a.

Material & shape

b.

b.

Diameter of wire
:
Whether
galvanized:(Yes/No)
Diameter of cable over
armouring
mm):
Armour coverage area
(%)
Maximum DC resistance
at 20C (ohm/km)
No
of
wires/Strips
required
Electrical Parameter at
maximum
Operating
temperature
Max. DC resistance at
20degC
A.C resistance at 90degC

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

a.

Finished Cable
Diameter over laid up
core (Calculated)

b.
c.

c.
d.
e.
f.
g.

14
a.

15

16

0.371

0.45

0.512

2.4421

1.1142

0.5743

N.A

N.A

N.A

Diameter under armor in


mm
(Claculated)

6.5

9.1

12.2

Diameter over armor in


mm
(Calculated)

9.3

11.9

15

3 kg/mm of
Aluminium area

3 kg/mm of
Aluminium area

3 kg/mm of Aluminium
area

Wooden

Wooden

Wooden

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

950 x 300 x 650

950 x 300 x 650

950 x 300 x 650

c.

Shipping Weight(App)
Drum
Weight(Without
cable) (App)
Cable pulling eye yes/No

316

408

559

105

105

105

d.
e.

No

No

15 times Overall
diameter

15 times Overall
diameter

18

Recommended
radius

19

Derating Factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

20

Group rating factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

13

16

19

211

303

454

1000

1000

1000

Min. 29%

Min. 29%

Min. 29%

Min. 2500C

Min. 2500C

Min. 2500C

Max. 60%

Max. 60%

Max. 60%

20% Max.

20% Max.

20% Max.

21
22
23
24

bending

No
15 times Overall
diameter

Overall dia. of cable (in


mm)( 2mm tolerance)
Weight per 1000 metre
(in Kg.)
Standard drum length
offered

25c

FRLS Properties on outer


Oxygen index in room
(%)
Minimum
temperature
index(C)
Maximum smoke density
rating(%)
Maximum
acid
gas
generation(%)

25d.

Flammability test

As per IEC-603321/SS-424-1475

As per IEC-603321/SS-424-1475

As per IEC-60332-1/SS424-1475

Embossing on outer
Sheath

" KEC INTL. LTD.,


'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."

" KEC INTL. LTD.,


'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."

" KEC INTL. LTD., 'RPGCABLES' , 1100V,


ELECTRIC CABLE, NO.
OF CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER LTD"
YEAR."

27

Marking on Drums

28

Type of end sealing

As per IS:7098
part(1)/88
PVC End Caps

As per IS:7098
part(1)/88
PVC End Caps

As per IS:7098
part(1)/88
PVC End Caps

25
25a.
25b.

26

GUARANTEED TECHNICAL PARTICULARS


KEC International
Ltd 'RPG-Cables'

Make

KEC International
Ltd 'RPG-Cables'

Country of Manufacturer

Type Designation

Applicable Standard

IS:7098 pt(1)/88

IS:7098 pt(1)/88

Cable size

1C x 300 Sq.mm

1C x 630 Sq.mm

No. of core

Rated voltage

Continuous current
temperature:

rating

for

max.

When laid in air at an ambient Temp. of 50 deg. C

b.

When buried in soil having thermal Resistivity of 150


deg. C Cm/W at a depth of 1000 mm in ground amb.
Temp. of 40 deg. C.

Short circuit withstand capacity and duration for


one second
Conductor

a.

c.
d.
e.

1100 V

1100 V

457

732

337

499

28.34

59.52

H4 Grade
Aluminium (
Class-2 ) to IS:
8130/1984

H4 Grade
Aluminium (
Class-2 ) to IS:
8130/1984

37/3.18

55/3.84

Compacted
Circular
20.0

Compacted
Circular
29.4

300

630

0.100

0.0469

Conductor
Material

b.

India
A2XFaY:FRLS

conductor

a.

a.
9

India
A2XFaY:FRLS

No. of strand/Approx diameter of each strand


Shape of Conductor
Diameter of conductor
Nominal cross section area in sq. mm.

f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

90

90

h.

S/C conductor temprature

250

250

Cross Linked
Polyethylene(XLP
E) as per
IS:7098/I/1988
2.10

Cross Linked
Polyethylene(XLP
E) as per
IS:7098/I/1988
2.80

10

Insulation
Material

a.
b.

Nominal thickness (in mm)

c.

Minimum thickness(in mm)

1.79

2.42

d.

Identification of cores

Black

Black

e.

Insulation temperature
Type of extrusion & curing process

f.

90

90

Sioplas single
Extrusion & Hot
Water Curing

Sioplas single
Extrusion & Hot
Water Curing

f.

Diameter over insulation

24.2

35.0

a.

Inner sheath
Min. thichkness

N.A

N.A

b.

Wrapped or Extruded

N.A

N.A

11

c.

Colour

N.A

N.A

d.

Approx. dia. Over inner sheath

N.A

N.A

Material and Type of inner sheath (if required)

N.A

N.A

Filler material

N.A

N.A

Extruded "FRLS"
PVC Type 'ST2'
as per IS:5831/84

Extruded "FRLS"
PVC Type 'ST2'
as per IS:5831/84

Black

Black

e.
f.
12

Outer sheath

a.

Type of Outer sheath

b.

Material

c.

Colour

d.
e.
13

Min. thickness of Outer sheath

1.56

1.72

2 mm

2 mm

Hard Drawn
Aluminium Flat
Strip as per
IS:8130
4.0 x 0.8

Hard Drawn
Aluminium Flat
Strip as per
IS:8130
4.0 x 0.8

N.A

N.A

26.4

37.4

Armour coverage area (%)

90%

90%

Maximum DC resistance at 20C (ohm/km)

0.74

0.51

16

23

Tolerance on diameter
Armour

a.

Material & shape

b.

Diameter of wire

c.

Whether galvanized:(Yes/No)

d.
e.
f.
g.
14
a.

:
:

Diameter of cable over armouring

mm):

No of wires/Strips required
Electrical Parameter at maximum
temperature
Max. DC resistance at 20degC

b.

A.C resistance at 90degC

Operating
0.10

0.0469

0.128

0.06

c.

Reactance at 50Hz(App)

0.0857

0.0843

d.

Capacitance (App)

0.693

0.766

e.

Impedance(App)

0.154

0.1034

Diameter over laid up core (Calculated)

N.A

N.A

Diameter under armor in mm

23.7

33.9

25.3

35.5

3 kg/mm of
Aluminium area

3 kg/mm of
Aluminium area

Wooden

Wooden

15
a.
b.
c.

Finished Cable

Diameter over armor in mm

16

Max. Pulling force

17

Cable Drum
Material

a.

(Claculated)
(Calculated)

b.

Dimension of drum(App)

1200 x 575 x 650

1500 x 700 x 800

c.

Shipping Weight(App)

859

1538

d.

Drum Weight(Without cable) (App)

220

300

e.

Cable pulling eye yes/No

No

No

18

Recommended bending radius

15 times Overall
diameter

15 times Overall
diameter

19

Derating Factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

Refer Catalogue

30

42

Weight per 1000 metre (in Kg.)

1277

2475

23

Standard drum length offered

500

500

24

FRLS Properties on outer

25
25a
.
25b
.

Oxygen index in room (%)

Min. 29%

Min. 29%

Minimum temperature index(C)

Min. 2500C

Min. 2500C

Max. 60%

Max. 60%

25c

Maximum acid gas generation(%)

25d
.

Flammability test

20% Max.
As per IEC60332-1/SS-4241475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V,
ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,I
SI Mark, "MB
POWER LTD",
YEAR."
As per IS:7098
part(1)/88
PVC End Caps

20% Max.
As per IEC60332-1/SS-4241475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V,
ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,I
SI Mark, "MB
POWER LTD",
YEAR."
As per IS:7098
part(1)/88
PVC End Caps

20

Group rating factor

21

Overall dia. of cable (in mm)( 2mm tolerance)

22

26

Maximum smoke density rating(%)

Embossing on outer Sheath

27

Marking on Drums

28

Type of end sealing

GUARANTEED TECHNICAL PARTICULARS

KEC International Ltd


'RPG-Cables'

Make

KEC International Ltd


'RPG-Cables'

Country of Manufacturer

Type Designation

India

India

A2XFY(P):FRLS

A2XFY(P):FRLS

Applicable Standard

IS:7098 pt(1)/88

IS:7098 pt(1)/88

Cable size

3C x 150 Sq.mm

3C x 240 Sq.mm

No. of core

1100 V

1100 V

Rated voltage

Continuous current rating


conductor temperature:

a.

When laid in air at an ambient Temp. of


50 deg. C

261

357

222

291

b.

When buried in soil having thermal


Resistivity of 150 deg. C Cm/W at a depth
of 1000 mm in ground amb. Temp. of 40
deg. C.

14.17

22.68

H4 Grade Aluminium
( Class-2 ) to IS:
8130/1984

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

19/3.18

36/2.94

Sector

Sector

9
a.
9

Short circuit withstand


duration for one second

for

capacity

max.

and

Conductor
Conductor
Material

a.
b.

No. of strand/Approx diameter of each


strand

c.

Shape of Conductor

d.

Diameter of conductor

12.0

15.4

Nominal cross section areain sq. mm.

150

240

0.206

0.125

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

90

90

250

250

Cross Linked
Polyethylene(XLPE) as
per IS:7098/I/1988

Cross Linked
Polyethylene(XLPE) as per
IS:7098/I/1988

Insulation
Material

a.
b.

Nominal thickness (in mm)

1.40

1.70

c.

Minimum thickness(in mm)

1.16

1.43

d.

Identification of cores

Red,Yellow & Blue

Red,Yellow & Blue

e.

Insulation temperature

90

90

Sioplas single
Extrusion & Hot
Water Curing

Sioplas single Extrusion &


Hot Water Curing

Diameter over insulation

14.8

18.8

a.

Inner sheath
Min. thichkness

0.50

0.60

b.

Wrapped or Extruded

Extruded

Extruded

c.

Colour

Black

Black

Type of extrusion & curing process


f.
g.
11

d.

Approx. dia. Over inner sheath

e.

Material and Type of inner sheath (if


required)

f.

12

Filler material

Type of Outer sheath

b.

Material

c.

Colour

e.
13

Min. thickness of Outer sheath


Tolerance on diameter

Material & shape

b.

Diameter of wire

c.

Whether galvanized:(Yes/No)
Diameter of cable over
mm):

:
:

e.

Armour coverage area (%)

f.

Maximum
(ohm/km)

g.

No of wires/Strips required

14
a.

Gaps can be filled by


PVC during the
extruded PVC
innersheathing
wherever applicable.

Gaps can be filled by PVC


during the extruded PVC
innersheathing wherever
applicable.

Extruded "FRLS"
PVC Type 'ST2' as
per IS:5831/84

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Black

Black

1.72

2.04

2 mm

2 mm

Galvanised Steel Flat


Strip as per IS:3975

Galvanised Steel Flat


Strip as per IS:3975

4.0 x 0.8

4.0 x 0.8

Yes

Yes

34.8

43.5

90%

90%

2.19

1.78

21

27

0.206

0.125

0.264

0.16

Armour

a.

d.

41.5
PVC Type `ST2' to
IS:5831/84

Outer sheath

a.

d.

32.9
PVC Type `ST2' to
IS:5831/84

DC

resistance

Electrical
Parameter
at
Operating temperature
Max. DC resistance at 20degC

b.

A.C resistance at 90degC

armouring

at

20C

maximum

c.

Reactance at 50Hz(App)

0.0732

0.0719

d.

Capacitance (App)

0.569

0.594

e.

Impedance(App)

0.274

0.1754

35.9

45.1

36.9

46.3

38.5

47.9

3 kg/mm of
Aluminium area

3 kg/mm of Aluminium
area

Wooden

Wooden

1500 x 700 x 800

1800 x 700 x 800

1479

2287

15
a.

Finished Cable
Diameter over laid up core (Calculated)

b.

Diameter
under
(Claculated)

c.

Diameter
over
(Calculated)

armor
armor

in

mm

in

mm

16

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

c.

Shipping Weight(App)

d.

Drum Weight(Without cable) (App)

300

500

e.

Cable pulling eye yes/No

No

No

12 times Overall
diameter

12 times Overall diameter

18

Recommended bending radius

19

Derating Factor

Refer Catalogue

Refer Catalogue

Refer Catalogue

Refer Catalogue

39

49

20

Group rating factor

21

Overall dia. of cable (in mm)(


tolerance)

22

Weight per 1000 metre (in Kg.)

2358

3574

23

Standard drum length offered

500

500

24

FRLS Properties on outer

25
25
a.
25
b.
25
c
25
d.

Oxygen index in room (%)

Min. 29%

Min. 29%

Minimum temperature index(C)


Maximum smoke density rating(%)
Maximum acid gas generation(%)
Flammability test

26

Embossing on outer Sheath

27

Marking on Drums

28

Type of end sealing

2mm

Min.

2500C

Min. 2500C

Max. 60%

Max. 60%

20% Max.

20% Max.

As per IEC-603321/SS-424-1475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER
LTD" YEAR."
As per IS:7098
part(1)/88
PVC End Caps

As per IEC-60332-1/SS424-1475
" KEC INTL. LTD., 'RPGCABLES' , 1100V,
ELECTRIC CABLE, NO.
OF CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI Mark,
"MB POWER LTD" YEAR."
As per IS:7098 part(1)/88
PVC End Caps

GUARANTEED TECHNICAL PARTICULARS

Make

Country of Manufacturer

Type Designation

Applicable Standard

Cable size

No. of core

KEC International Ltd


'RPG-Cables'

KEC International Ltd 'RPGCables'

India

India

A2XFY(P):FRLS

A2XFY(P):FRLS

IS:7098 pt(1)/88

IS:7098 pt(1)/88

3.5C x 35 Sq.mm

3.5C x 70Sq.mm

3.5

3.5

1100 V

1100 V

Rated voltage

Continuous current rating for max.


conductor temperature:

a.

When laid in air at an ambient Temp. of


50 deg. C

104

158

102

146

b.

When buried in soil having thermal


Resistivity of 150 deg. C Cm/W at a
depth of 1000 mm in ground amb.
Temp. of 40 deg. C.

Short circuit withstand capacity and


duration for one second
3.31

6.61

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

H4 Grade Aluminium (
Class-2 ) to IS: 8130/1984

a.
9

Conductor
Conductor
Material

a.
b.

No. of strand/Approx diameter of each


strand

7/2.52

19/2.14

c.

Shape of Conductor

Sector

Sector

d.

Diameter of conductor

6.8

9.6

Nominal cross section areain sq. mm.

35

70

0.868

0.443

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

90

90

250

250

Cross Linked
Polyethylene(XLPE) as
per IS:7098/I/1988

Cross Linked
Polyethylene(XLPE) as per
IS:7098/I/1988

Insulation
Material

a.
b.

Nominal thickness (in mm)

0.90

1.10

c.

Minimum thickness(in mm)

0.71

0.89

Red,Yellow,Blue & Black

Red,Yellow,Blue & Black

90

90

Sioplas single Extrusion


& Hot Water Curing

Sioplas single Extrusion &


Hot Water Curing

Diameter over insulation

8.6

11.8

Inner sheath
Min. thichkness

0.30

0.40

Extruded

Extruded

Black

Black

d.

Identification of cores

e.

Insulation temperature
Type of extrusion & curing process

f.
g.
11
a.
b.

Wrapped or Extruded

c.

Colour

d.

Approx. dia. Over inner sheath

e.

Material and Type of inner sheath (if


required)

f.

12

Filler material

20.3

27.5

PVC Type `ST2' to


IS:5831/84

PVC Type `ST2' to


IS:5831/84

Gaps can be filled by


PVC during the extruded
PVC innersheathing
wherever applicable.

Gaps can be filled by PVC


during the extruded PVC
innersheathing wherever
applicable.

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Extruded "FRLS" PVC Type


'ST2' as per IS:5831/84

Black

Black

Outer sheath

a.

Type of Outer sheath

b.

Material

c.

Colour

1.40

1.56

2 mm

2 mm

Galvanised Steel Flat


Strip as per IS:3975

Galvanised Steel Flat Strip


as per IS:3975

4.0 x 0.8

4.0 x 0.8

Yes

Yes

22.3

29.5

90%

90%

3.6

2.7

12

17

0.868

0.443

1.11

0.567

0.0794

0.0752

0.464

0.49

1.1128

0.572

Diameter over laid up core (Calculated)

19.0

26.2

b.

Diameter
under
(Claculated)

19.6

27.0

c.

Diameter
over
(Calculated)

21.2

28.6

3 kg/mm of Aluminium
area

3 kg/mm of Aluminium
area

Wooden

Wooden

1400 x 600 x 650

1400 x 600 x 650

1220

1035.5

d.
e.
13

Min. thickness of Outer sheath


Tolerance on diameter
Armour

a.

Material & shape

b.

Diameter of wire

c.
d.

Whether galvanized:(Yes/No)
Diameter of cable over armouring
mm):

e.

Armour coverage area (%)

f.

Maximum
(ohm/km)

g.

No of wires/Strips required

14
a.

DC

:
:

resistance

A.C resistance at 90degC

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

a.

Finished Cable

16

Max. Pulling force

17

Cable Drum
Material

a.

20C

Electrical Parameter at maximum


Operating temperature
Max. DC resistance at 20degC

b.

15

at

armor
armor

b.

Dimension of drum(App)

c.

Shipping Weight(App)

in

mm

in

mm

d.

Drum Weight(Without cable) (App)

270

270

e.

Cable pulling eye yes/No

No

No

12 times Overall
diameter

12 times Overall diameter

18

Recommended bending radius

Refer Catalogue

Refer Catalogue

Refer Catalogue

Refer Catalogue

26

33

Weight per 1000 metre (in Kg.)

950

1531

23

Standard drum length offered

1000

500

24

FRLS Properties on outer

25
25
a.
25
b.
25
c
25
d.

Oxygen index in room (%)

Min. 29%

Min. 29%

19

Derating Factor

20

Group rating factor

21

Overall dia. of cable (in mm)(


tolerance)

22

Minimum temperature index(C)

2mm

Min.

2500C

Min. 2500C

Max. 60%

Max. 60%

20% Max.

20% Max.

Flammability test

As per IEC-60332-1/SS424-1475

As per IEC-60332-1/SS424-1475

26

Embossing on outer Sheath

" KEC INTL. LTD., 'RPGCABLES' , 1100V,


ELECTRIC CABLE, NO.
OF CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, "MB POWER LTD"
YEAR."

" KEC INTL. LTD., 'RPGCABLES' , 1100V,


ELECTRIC CABLE, NO. OF
CORES X SIZE Sq.mm.,Type
of Insulation,FRLS,ISI Mark,
"MB POWER LTD" YEAR."

27

Marking on Drums

28

Type of end sealing

Maximum smoke density rating(%)


Maximum acid gas generation(%)

As per IS:7098
part(1)/88
PVC End Caps

As per IS:7098 part(1)/88


PVC End Caps

GUARANTEED TECHNICAL PARTICULARS



Make

KEC International Ltd 'RPG-Cables'

Country of Manufacturer

Type Designation

Applicable Standard

IS:7098 pt(1)/88

Cable size

4C x 16Sq.mm

No. of core

Rated voltage

Continuous
current
temperature:

India
A2XFY(P):FRLS

4
1100 V
rating

for

max.

conductor

a.

When laid in air at an ambient Temp. of 50 deg. C

b.

When buried in soil having thermal Resistivity of 150 deg.


C Cm/W at a depth of 1000 mm in ground amb. Temp. of
40 deg. C.

Short circuit withstand capacity and duration for one


second

a.
9

Conductor

62

65

1.51

Conductor
Material

a.

H4 Grade Aluminium ( Class-2 ) to


IS: 8130/1984

No. of strand/Approx diameter of each strand

7/1.72

c.

Shape of Conductor

Sector

d.

Diameter of conductor

4.6

Nominal cross section areain sq. mm.

16

b.

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

1.91
90
250

Insulation
Material
a.

Cross Linked Polyethylene(XLPE)


as per IS:7098/I/1988

b.

Nominal thickness (in mm)

0.70

c.

Minimum thickness(in mm)

0.53

d.

Identification of cores

e.

Insulation temperature
Type of extrusion & curing process

f.
g.

Diameter over insulation

a.

Inner sheath
Min. thichkness

b.

Wrapped or Extruded

c.

Colour

11

Red,Yellow,Blue & Black


90
Sioplas single Extrusion & Hot
Water Curing
6.0
0.30
Extruded
Black

d.
e.

f.

12

Approx. dia. Over inner sheath

14.9

Material and Type of inner sheath (if required)

PVC Type `ST2' to IS:5831/84

Gaps can be filled by PVC during


the extruded PVC innersheathing
wherever applicable.

Filler material

Outer sheath
a.

Type of Outer sheath

b.

Material

c.

Colour

d.
e.
13

Extruded "FRLS" PVC Type 'ST2'


as per IS:5831/84
Black

Min. thickness of Outer sheath

1.40
2 mm

Tolerance on diameter
Armour

Galvanised Steel Flat Strip as per


IS:3975

a.

Material & shape

b.

Diameter of wire

c.

Whether galvanized:(Yes/No)

d.
e.
f.

4.0 x 0.8

Yes

Diameter of cable over armouring

mm):

16.9

Armour coverage area (%)

90%

Maximum DC resistance at 20C (ohm/km)

4.32

g.

No of wires/Strips required

a.

Electrical Parameter at maximum Operating temperature


Max. DC resistance at 20degC

1.91

b.

A.C resistance at 90degC

2.44

14

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

15

0.0815
0.401
2.4414

Finished Cable
a.

b.
c.

Diameter over laid up core (Calculated)

14.3

Diameter under armor in mm

14.9

Diameter over armor in mm

(Claculated)
(Calculated)

16.5

16

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

c.

Shipping Weight(App)

837

d.

Drum Weight(Without cable) (App)

220

e.

Cable pulling eye yes/No

No

18

Recommended bending radius

3 kg/mm of Aluminium area

Wooden
1200 x 575 x 650

12 times Overall diameter

19

Derating Factor

Refer Catalogue

20

Group rating factor

Refer Catalogue

21

Overall dia. of cable (in mm)( 2mm tolerance)

22

Weight per 1000 metre (in Kg.)

617

23

Standard drum length offered

1000

24

FRLS Properties on outer

25
25a.

Oxygen index in room (%)


Minimum temperature index(C)

21

Min. 29%
Min. 2500C

25b.

Maximum smoke density rating(%)

Max. 60%

25c

Maximum acid gas generation(%)

20% Max.

25d.

Flammability test

As per IEC-60332-1/SS-424-1475

Embossing on outer Sheath

" KEC INTL. LTD., 'RPG-CABLES' ,


1100V, ELECTRIC CABLE, NO. OF
CORES X SIZE Sq.mm.,Type of
Insulation,FRLS,ISI Mark, "MB
POWER LTD" YEAR."

26

27

Marking on Drums

As per IS:7098 part(1)/88

28

Type of end sealing

PVC End Caps




GUARANTEED TECHNICAL PARTICULARS



KEC International Ltd
'RPG-Cables'

Make

1
2

Country of Manufacturer

Type Designation

KEC International Ltd


'RPG-Cables'

India

India

Str. A2XWY(P):FRLS

Str. A2XWY(P):FRLS

Applicable Standard

IS:7098 pt(1)/88

IS:7098 pt(1)/88

Cable size

3C x 10Sq.mm

4C x 10Sq.mm

No. of core

Rated voltage

Continuous current rating


conductor temperature:

for

1100 V

1100 V

max.

a.

When laid in air at an ambient Temp. of 50


deg. C

59

59

80

80

b.

When buried in soil having thermal


Resistivity of 150 deg. C Cm/W at a depth
of 1000 mm in ground amb. Temp. of 40
deg. C.

0.94

0.94

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

H4 Grade Aluminium (
Class-2 ) to IS:
8130/1984

7/1.35

7/1.35

Circular

Circular

9
a.
9

Short circuit withstand


duration for one second

capacity

and

Conductor
Conductor
Material

a.
b.

No. of strand/Approx diameter of each


strand

c.

Shape of Conductor

d.

Diameter of conductor

4.1

4.1

Nominal cross section areain sq. mm.

10

10

3.08

3.08

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

90

90

250

250

Cross Linked
Polyethylene(XLPE) as per
IS:7098/I/1988

Cross Linked
Polyethylene(XLPE) as
per IS:7098/I/1988

Insulation
Material
a.

b.

Nominal thickness (in mm)

0.70

0.70

c.

Minimum thickness(in mm)

0.53

0.53
Red, Yellow, Blue &
Black
90
Sioplas single
Extrusion & Hot Water
Curing
5.5

d.
e.

Identification of cores
Insulation temperature
Type of extrusion & curing process

f.
g.

Diameter over insulation

a.

Inner sheath
Min. thichkness

b.

Wrapped or Extruded

c.

Colour

11

Red, Yellow & Blue


90
Sioplas single Extrusion &
Hot Water Curing
5.5
0.30

0.30

Extruded

Extruded

Black

Black

d.

Approx. dia. Over inner sheath

e.

Material and Type of inner sheath (if


required)

f.

12

13.4

15.0

PVC Type `ST2' to


IS:5831/84

PVC Type `ST2' to


IS:5831/84
Gaps can be filled by
PVC during the
extruded PVC
innersheathing
wherever applicable.

Gaps can be filled by PVC


during the extruded PVC
innersheathing wherever
applicable.

Filler material

Outer sheath
a.

b.
c.
d.
e.
13

Type of Outer sheath


Material
Colour
Min. thickness of Outer sheath
Tolerance on diameter

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Extruded "FRLS" PVC


Type 'ST2' as per
IS:5831/84

Black

Black

1.24

1.40

2 mm

2 mm

Armour

1.4

Galvanised Steel
Round Wire as per
IS:3975
1.4

Yes

Yes

16.2

17.8

Armour coverage area (%)

90%

90%

Maximum DC resistance at 20C (ohm/km)

3.57

3.20

26

29

3.08

3.08

3.94

3.94

0.0852

0.0852

0.347

0.347

3.9409

3.9409

10.8

12.1

11.4

12.7

14.2

15.5

3 kg/mm of Al. area

3 kg/mm of Al. area

Wooden

Wooden

Galvanised Steel Round


Wire as per IS:3975

a.

Material & shape

b.

Diameter of wire

c.
d.

Whether galvanized:(Yes/No)
Diameter
of
cable
over
mm):

e.
f.

:
:
armouring

g.

Approx. No of wires/Strips required

a.

Electrical
Parameter
at
Operating temperature
Max. DC resistance at 20degC

b.

A.C resistance at 90degC

14

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

15

maximum

Finished Cable
a.

Diameter over laid up core (Calculated)

b.

Diameter
under
(Claculated)

c.

Diameter
over
(Calculated)

armor
armor

in

mm

in

mm

16

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

1000 x 300 x 600

1200 x 575 x 650

c.

Shipping Weight(App)

817

1027

d.

Drum Weight(Without cable) (App)

130

220

e.

Cable pulling eye yes/No

No

No
12 times Overall
diameter
Refer Catalogue

18
19

Recommended bending radius


Derating Factor

12 times Overall diameter


Refer Catalogue

Refer Catalogue

Refer Catalogue

19

21

Weight per 1000 metre (in Kg.)

687

807

23

Standard drum length offered

1000

1000

24

FRLS Properties on outer

25

Oxygen index in room (%)

Min. 29%

Min. 29%

20

Group rating factor

21

Overall dia.
tolerance)

22

of

cable

(in

mm)(

25a.

Minimum temperature index(C)

25b.

Maximum smoke density rating(%)

25c

Maximum acid gas generation(%)

25d.

26

Flammability test

Embossing on outer Sheath

27

Marking on Drums

28

Type of end sealing

2mm

Min.

2500C

Max. 60%

Min. 2500C
Max. 60%

20% Max.

20% Max.

As per IEC-60332-1/SS424-1475

As per IEC-603321/SS-424-1475
" KEC INTL. LTD.,
'RPG-CABLES' ,
1100V, ELECTRIC
CABLE, NO. OF
CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI
Mark, YEAR."
As per IS:7098
part(1)/88
PVC End Caps

" KEC INTL. LTD., 'RPGCABLES' , 1100V,


ELECTRIC CABLE, NO.
OF CORES X SIZE
Sq.mm.,Type of
Insulation,FRLS,ISI Mark,
YEAR."
As per IS:7098 part(1)/88
PVC End Caps

GUARANTEED TECHNICAL
PARTICULARS
Make

Country of Manufacturer

KEC International Ltd 'RPG-Cables'


India

Type Designation

Applicable Standard

IS:7098 pt(1)/88

Cable size

2C x 2.5 Sq.mm

No. of core

Rated voltage

Continuous current rating for max. conductor


temperature:

a.

When laid in air at an ambient Temp. of 50 deg. C

b.

When buried in soil having thermal Resistivity of


150 deg. C Cm/W at a depth of 1000 mm in
ground amb. Temp. of 40 deg. C.

Short circuit withstand capacity and duration for


one second

a.
9

Conductor

1100 V

35

38

0.36

Conductor
Material

a.
b.

Str. 2XWY(P):FRLS

No. of strand/Approx diameter of each strand

Annealed Stranded Copper ( Class-2 ) to


IS:8130/84
7/0.67

c.

Shape of Conductor

d.

Diameter of conductor

2.0

Nominal cross section areain sq. mm.

2.5

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

Circular

7.41
90
250

Insulation
Material
a.

b.

Nominal thickness (in mm)

c.

Minimum thickness(in mm)

d.

Identification of cores

e.

Insulation temperature
Type of extrusion & curing process

Cross Linked Polyethylene(XLPE) as per


IS:7098/I/1988
0.70
0.53
Red & Black
90
Sioplas single Extrusion & Hot Water Curing

f.
g.

Diameter over insulation

a.

Inner sheath
Min. thichkness

b.

Wrapped or Extruded

11

3.4
0.30
Extruded

c.

Colour

d.

Approx. dia. Over inner sheath

e.
f.

12

Black
8.4

Material and Type of inner sheath (if required)

PVC Type `ST2' to IS:5831/84


Gaps can be filled by PVC during the
extruded PVC inner sheathing wherever
applicable.

Filler material

Outer sheath
a.

Type of Outer sheath

b.

Material

c.

Colour

d.
e.
13

Extruded "FRLS" PVC Type 'ST2' as per


IS:5831/84
Black
1.24

Min. thickness of Outer sheath

2 mm

Tolerance on diameter
Armour

a.

Material & shape

b.

Diameter of wire

c.
d.
e.
f.

Galvanised Steel Round Wire as per IS:3975

Diameter of cable over armouring

mm):

11.2

Armour coverage area (%)

90%

Maximum DC resistance at 20C (ohm/km)

6.07

No of wires/Strips required

a.

Electrical Parameter at maximum


temperature
Max. DC resistance at 20degC

b.

A.C resistance at 90degC

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

15

Yes

Whether galvanized:(Yes/No)

g.
14

1.4

15
Operating
7.41
9.48
0.1007
0.071
9.4805

Finished Cable
a.

b.
c.
16

Diameter over laid up core (Calculated)

6.4

Diameter under armor in mm (Claculated)

7.0

Diameter over armor in mm (Calculated)

9.8

Max. Pulling force

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

5 kg/mm of Copper area

Wooden
950 x 300 x 650

c.

Shipping Weight(App)

508

d.

Drum Weight(Without cable) (App)

105

e.

Cable pulling eye yes/No

No

18

Recommended bending radius

12 times Overall diameter

19

Derating Factor

Refer Catalogue

20

Group rating factor

Refer Catalogue

21

Overall dia. of cable (in mm)( 2mm tolerance)

22

Weight per 1000 metre (in Kg.)

403

23

Standard drum length offered

1000

24

FRLS Properties on outer

25
25a.

Oxygen index in room (%)


Minimum temperature index(C)

14

Min. 29%
Min. 2500C

25b.

Maximum smoke density rating(%)

Max. 60%

25c

Maximum acid gas generation(%)

20% Max.

25d.

Flammability test

26

Embossing on outer Sheath

As per IEC-60332-1/SS-424-1475
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X SIZE
Sq.mm.,Type of Insulation,FRLS,ISI
Mark,"MB POWER LTD" YEAR."

27

Marking on Drums

As per IS:7098 part(1)/88

28

Type of end sealing

PVC End Caps

GUARANTEED TECHNICAL PARTICULARS


Make

KEC International Ltd 'RPG-Cables'

Country of Manufacturer

Type Designation

Applicable Standard

IS:7098 pt(1)/88

Cable size

1C x 120 Sq.mm

No. of core

Rated voltage

Continuous current
temperature:

India
A2XFaY:FRLS

1
1100 V
rating

for

max.

conductor

a.

When laid in air at an ambient Temp. of 50 deg. C

b.

When buried in soil having thermal Resistivity of 150


deg. C Cm/W at a depth of 1000 mm in ground amb.
Temp. of 40 deg. C.

Short circuit withstand capacity and duration for one


second

a.
9

Conductor

206

11.34

Conductor
Material

a.
b.

245

No. of strand/Approx diameter of each strand

H4 Grade Aluminium ( Class-2 ) to IS:


8130/1984
19/2.94

c.

Shape of Conductor

d.

Diameter of conductor

12.8

Nominal cross section area in sq. mm.

120

e.
f.

Max. D. C. resistance at 20 deg. C

g.

Conductor temperature

h.

S/C conductor temprature

10

Compacted Circular

0.253
90
250

Insulation
Material
a.

Cross Linked Polyethylene(XLPE) as per


IS:7098/I/1988

b.

Nominal thickness (in mm)

1.50

c.

Minimum thickness(in mm)

1.25

d.

Identification of cores

Black

e.

Insulation temperature
Type of extrusion & curing process

f.

90
Sioplas single Extrusion & Hot Water
Curing

f.

Diameter over insulation

15.8

a.

Inner sheath
Min. thichkness

N.A

b.

Wrapped or Extruded

N.A

c.

Colour

N.A

11

d.
e.
f.
12

Approx. dia. Over inner sheath

N.A

Material and Type of inner sheath (if required)

N.A

Filler material

N.A

Outer sheath
a.

Type of Outer sheath

b.

Material

c.

Colour

d.
e.
13

Extruded "FRLS" PVC Type 'ST2' as per


IS:5831/84
Black

Min. thickness of Outer sheath

1.40
2 mm

Tolerance on diameter
Armour

Hard Drawn Aluminium Flat Strip as per


IS:8130

a.

Material & shape

b.

Diameter of wire

c.

Whether galvanized:(Yes/No)

d.
e.
f.

4.0 x 0.8

N.A

Diameter of cable over armouring

mm):

18.0

Armour coverage area (%)

90%

Maximum DC resistance at 20C (ohm/km)

1.18

g.

No of wires/Strips required

10

a.

Electrical Parameter at maximum


temperature
Max. DC resistance at 20degC

b.

A.C resistance at 90degC

0.324
0.0879

14

c.

Reactance at 50Hz(App)

d.

Capacitance (App)

e.

Impedance(App)

15

Operating
0.253

0.641
0.3357

Finished Cable
a.

b.
c.

Diameter over laid up core (Calculated)

N.A

Diameter under armor in mm

15.4

Diameter over armor in mm

(Claculated)
(Calculated)

17

16

Max. Pulling force

3 kg/mm of Aluminium area

17
a.

Cable Drum
Material

b.

Dimension of drum(App)

c.

Shipping Weight(App)

821

d.

Drum Weight(Without cable) (App)

220

e.

Cable pulling eye yes/No

No

Wooden
1200 x 575 x 650

15 times Overall diameter

18

Recommended bending radius

19

Derating Factor

Refer Catalogue

20

Group rating factor

Refer Catalogue

22

21

Overall dia. of cable (in mm)( 2mm tolerance)

22

Weight per 1000 metre (in Kg.)

601

23

Standard drum length offered

1000

24

FRLS Properties on outer

25
25a.

Oxygen index in room (%)


Minimum temperature index(C)

Min. 29%
Min. 2500C

25b.

Maximum smoke density rating(%)

Max. 60%

25c

Maximum acid gas generation(%)

20% Max.

25d.

Flammability test

26

Embossing on outer Sheath

As per IEC-60332-1/SS-424-1475
" KEC INTL. LTD., 'RPG-CABLES' , 1100V,
ELECTRIC CABLE, NO. OF CORES X
SIZE Sq.mm.,Type of Insulation,FRLS,ISI
Mark, "MB POWER LTD", YEAR."

27

Marking on Drums

As per IS:7098 part(1)/88

28

Type of end sealing

PVC End Caps