You are on page 1of 147

Product Manual

1HYB 800001-52 Rev. A

EDF SKS 1-1


with operating mechanism
Type FSA

Product Manual

1
2
3
4
5
6
7
8
9
10
11
12

HIGH VOLTAGE CIRCUIT-BREAKER-TYPE


ED 1 H Y B 8 0 0 0 0 1 - 2 6

FUNCTIONAL VALUES
1 H Y B 8 0 0 0 0 1 - 53

LUBRICANTS
1HYB800001-28

LOCKING LIQUID FOR THREADS


1HYB800001-29

GENERAL INSTRUCTIONS FOR


MAINTENANCE, TRANSPORT & STORAGE
1HYB800001-30

GOODS MARKING AND TRANSPORT


1HYB800001-31

STORAGE PRIOR TO ERECTION


1HYB800001-32

INFORMATION
SF6 GAS AND GAS MIXTURES
1HYB800001-33

SAFETY REGULATIONS
1HYB800001-35

DISPOSAL AND RECYCLING


1HYB800001-36

INSTRUCTIONS FOR ERECTION,


OPERATION AND MAINTENANCE
1 H Y B 8 0 0 0 0 1 - 54

INSTRUCTIONS FOR OPERATION


AND MAINTENANCE OPERATING
MECHANISM TYPE FSA 1HYB800001-38

1HYB800001-26 Rev. A
Page 1

HIGH VOLTAGE CIRCUIT-BREAKER TYPE ED


The high voltage circuit-breaker type ED is a detached SF6 circuit-breaker for outdoor
erection in open substations.
The circuit-breaker is built up of three separate poles, which consist of three main
parts. At the bottom, the mechanism housing is made of aluminium. The hollow post
insulators, through which operating insulators run and on top, the breaking units.
Each breaking unit consists of a hollow insulator which together with an upper and a
lower flange constitute the casing and a lower and an upper current path with a
contact system. The moving contacts are assembled on the lower current path
whereas the fixed contacts are assembled on the upper one.
The circuit-breaker poles to ED SK are permanently filled with SF6 - gas, normally to
the pressure 0.7 MPa absolute at 200C. For monitoring the pressure the circuitbreaker is equipped with a density monitor. The poles are mounted on a common
supporting frame, consisting of a front and a rear pole beam. The latter is mounted
on two supports which are anchored to the foundations. The beams and supports are
hot-dip galvanized.
The pressure rise and gas flow which are necessary for extinguishing the arc during
the course of breaking are produced partly by compression of the gas, partly by the
energy given from the arc.
At the opening operation, the moving contact is pulled downwards over the fixed
piston and the confined quantity of gas is compressed and at high speed forced out
through the springs in the upper end of the cylinder. At the same stage the arcing
contacts are separated and an arc occurs. A specially formed nozzle leads the
outflowing gas towards the arc. The gas is allowed to pass both downwards through
the moving arcing contact and upwards past the fixed arcing contact.
For the continuous current there are separate contacts which are not affected by the
arc at breaking.
At closing operation, the moving contact is pushed upwards at which time the contacts engage and the cylinder is filled with gas again.
The ED SK circuit-breaker is operated by a motor-operated spring closing device
type FSA.

1HYB800001-53 Rev. A
Page 1

Functional Values
SF6 BREAKER TYPE ED-SKS 1-1 (72.5 kV) WITH OPERATING DEVICE TYPE FSA 1
Closing time
Opening time
ON-OFF time *)

max. 60 ms
max. 35 ms
max. 40 ms

Demand of time difference between poles.


Unearthed capacitor bank.
Pole C1
Closing time 50 Hz
Closing time 60 Hz

ts
ts

Pole B1

Pole A1

ts 0.5
ts 0.5

ts + 5.0 +1.0/-0.5
ts + 4.2 +1.0 -0.5

Pole B1

Pole A1

ts +3.3 0.7
ts +2.8 0.7

ts + 6.7 0.7
ts + 5.6 0.7

Earthed capacitor bank.


Pole C1
Closing time 50 Hz
Closing time 60 Hz

ts
ts

Resistance of the main circuit across a breaking unit: Max. 50 at rated current 2000
A/1600 A.
*)

ON-OFF time means the time during which the main contacts are closed at a
closing operation when the tripping impulse is connected in simultaneously, via
the auxiliary contact.

1HYB800001-28 Rev. A
Page 1

Types of Lubricants for Switching Devices


As a guide to the selection of Lubricants and oils, a description is given below of the
range of applications.
Oil A :
Thin lubricating oil for precision parts in operating mechanisms and air-blast circuitbreakers. Also for relubricating of bearing, which can not be lubricated with grease
G without dismounting -e.g. links and link gears. Viscosity at 400C: 62-65 cSt.
Oil C:
Circuit-breaker oil with viscosity~17 cSt at +200C. Suitable only for temperature > 100.
Oil D :
Circuit-breaker oil with viscosity~6.0 cSt. at +20 0C. Shall also be used as oil in
dashpots. For dashpots with the letter S stamped on the cover - oil S shall be
used.
Oil S :
Silicon oil intended for oil dashpots in heavy operating mechanisms. Only dashpots
with the letter S stamped on the cover shall be filled with this oil.

1HYB800001-28 Rev. A
Page 2
Grease G :
Low temperature grease for all types of bearings, gears and worm gears as well as
valves in air-blast circuit-breakers. Also suitable for lubrication of silverplated contacts in air (e.g. contacts in disconnectors).
Also used when greasing O-rings made from nitrile rubber and as a crevice corrosion
prevention.
Grease N :
For lubrication of moving contacts in SF6-insulated circuit breakers (e.g. puffer
cylinders). A very thin layer of the grease shall be rubbed on the sliding surface of
the contacts.
Grease L :
Low temperature grease specially suitable for lubricating of fine mechanics-e.g. catch
devices in operating mechanism which shall operate in strong cold.
Grease M :
Low temperature grease for long-duration and permanent lubrication of worm gears
and other machine elements. Prevents wear and corrosion.
Grease P :
Vaseline for treatment of contact surfaces in current conductor joints.
Grease R :
EP-grease for heavily-loaded roller bearings, slide bearings, cam discs and catches
(Lithium grease. Solvent refined mineral oil with lithium soaps and molybdenum
disulphide) in operating mechanisms type FSA.
Grease S :
Fluoro-silicone grease for greasing of O-ring made from EPDM and as a corrosion
prevention of gaps in circuit-breakers type ED.
Grease SV
Grease for lubricating moving contacts, silver plated connections and brushed
aluminium surfaces in fixed joints outdoors.

1HYB800001-28 Rev. A
Page 3

1HYB800001-29 Rev. A
Page 1

Locking Liquid For Threads


As a guide to selection of locking liquids, a description is given below of the range of
applications.
Pre-treatment of surfaces : The surfaces shall be free from oil, grease, wax, paint and
rust-preventive. Locking Liquids A, B and C are designed for use in only surfaces
also.
Locking Liquid A

Weak locking and setting of set screws.

Locking Liquid B

Medium strong locking of threads and sealing of screws and


nuts.

Locking Liquid C

Strong locking and sealing of studs and bolts up to M36.


Difficult to dismantle.

Locking Liquid D

Locking of fasteners after assembly or adjustment. Sealing


of porous weld joints, castings and sintered materials. The
sealing is very resistant against pressure, solvent and
chemicals. Can be used only on clean, dry surfaces. Oily
goods to be washed with trichloroethylene, preferably steamwashing.

Locking Liquid E

To pre-treat PTFE at locking of a thread connection PTFE/


metal

LOCTITE Ltd.

LOCTITE Ltd.

1HYB800001-30 Rev. A

General Instructions for Maintenance,


Transport & Storage

Contents :

1.

Safety precautions

2.

Cleanliness

3.

Cleaning

4.

Waste disposal

5.

Emptying of gas

1HYB800001-30 Rev. A
Page 1

1. Safety precautions
Follow the local high-voltage safety regulations. Put the breaker in the OPEN
position.
Disconnect and earth the high voltage side.
Disconnect the operating and heating voltage.
Work on the insulators of the breaker or live parts as well as transport and
dismounting of complete breaking poles may not be done before the breaker is
emptied to a max. pressure of 0.15 MPa abs. Before the opening of the normally
pressurised vessel, it shall be emptied completely to atmospheric pressure. If the
gas is emptied into the free air, this shall be done through a dust and absorption filter.
See under clause Emptying of gas.

2. Cleanliness
Very high dielectric requirements are placed on the SF6 gas and on the insulating
parts and correspondingly also on their cleanliness and dryness.
On all work on the open circuit breaker, be aware that not only dirt but also air
moisture and hand perspiration are deleterious.
If for any reason gas spaces or parts thereof are exposed to air for longer than 24
hours, the gas spaces are to be closed temporarily and filled with SF 6 gas to Pabs =
120 kPa (1.2 bar). Single parts are to be sealed in plastic bags and kept in storage.
Unused SF6 gas is non-poisonous, odourless and colourless. However, it is heavier
than air and with substantial outflow, it gathers easily in low situated spaces like
cable trenches, tanks and such.
With large amount of SF 6 in these spaces, there is a risk of suffocation due to lack
of oxygen.
-

Perform overhaul work only with adequate room ventilation.

The decomposition products which are formed in the breaking elements are in
combination with humidity corrosive and can cause skin, eye and mucous
membrane irritation. During the opening and internal cleaning of the breaker, a
close fitted mask with a filter against fine dust and acid gases, protective
plastic or rubber gloves and a long sleeved overall shall be used.

The dust (decomposition products), that is formed in the breaker, shall be sucked
with a vacuum cleaner provided with a dust filter and wiped off with a cloth that is
sprinkled with ethanol or toluol.
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear
protective gloves.
Drying cloths, protective gloves and vacuum cleaner bags shall be rinsed carefully
with plenty of water.

1HYB800001-30 Rev. A
Page 2

3. Cleaning
A. Insulator with paint-treated plastic outside surface, silicon rubber sheds or porcelain insulator.
Rinse the outside surfaces thoroughly with water and let it dry well before the
breaker is opened.
The end and inside surfaces are cleaned with a non fluffy drying cloth soaked with
ethanol.
Cleaned insulators must be touched only with clean protective gloves (plastic or
rubber).
Cover the end surfaces of the insulators with a strong plastic foil to protect from
recontamination.
B. Single parts
Vacuum immediately after disassembly with a vacuum cleaner with a fine dust
filter. Wipe off persistent dust with a non fluffy cloth.
Remove stubbornly adhering dust with a cloth soaked with ethanol.
Cover cleaned details with plastic foil or put in plastic bag.
Details from spaces not filled with SF6 shall be cleaned with ethanol and then left
to dry in air. Then they are packed in plastic bags.

4. Waste disposal
All the dust as well as the used absorption agent is stored in a sealed container and
is disposed off as chemical waste according to the valid provisions. During waste
disposal and handling with decomposition products, it is necessary to wear protective
gloves.

5. Emptying of gas
The breaker is evacuated by means of the gas treatment equipment, that purifies and
compresses the gas, so that it can be reapplied.
Mixed gas - SF 6 + N2 - can only be reapplied if the mixing conditions are under
control.
After the evacuation, the breaker is filled with nitrogen up to atmospheric pressure
and after this, evacuated again. In this way, the eventual free drifting dust in the
breaker is removed.
Finally the breaker is filled again with dry nitrogen up to atmospheric pressure after
which it is ready for dismounting and transport to the workshop.
NOTE
If work on the circuit-breaker only affects the outside of the breaker, for example
cleaning of the insulators, it is sufficient to empty the breaker down to a pressure of
0.15 MPa abs, normal working pressure.

1HYB800001-31 Rev. A
Page 1

GOODS MARKING AND TRANSPORT


General
Each case is marked with markings as per Packing list.
In addition they are marked with following :

DO NOT TILT
MORE THAN 45

Glass, porcelain, handle carefully

Up

Put the lifting slings here

It is not allowed to tilt the transport unit more than 45 degrees

Centre of gravity

Must be protected from moisture and rain

Figure 1 Transport unit


The circuit-breaker should be transported in their transport units, and particularly
never be transported unpacked. While choosing conveying equipment, the
following should be observed :

Packing case markings


The distance and road conditions

The units should be transported in such a way that they are


-

Prevented from standing in water


Not exposed to rough handling and damages
Covered by at least tarpaulin, protected against water

Every transport unit must be fixed during the transport. The tying must be so
arranged that the transport units can not move in any direction. Velocity should be
adapted to the road conditions. Violent acceleration or retardation can cause damage
to the contents without damaging the packing.

1HYB800001-31 Rev. A
Page 2

Lifting
Before lifting, the symbols on the transport unit (such as centre of gravity, weight
etc.) should be observed. The transport units should be lifted with a lifting machine
provided with forks of slings (see fig. 2). If a crane is utilised slings should be used.
The units may not be rolled or dropped from the conveying or lifting equipment.

Figure 2 Lifting a transport unit


Lifting the operating mechanism out of the transport unit
The operating mechanisms FSA should be lifted by the lifting devices on top of the
cubicle. Lifting slings should never be used around the operating mechanism (see fig.
3)

Figure 3 Lifting the operating mechanism


Lifting the breakers out of the transport units
Lifting the breakers out of the transport units is only necessary just before erection
(see product information, which can be found in the cubicle of the operating
mechanism). If they are going to be stored, see Storage prior to erection.

1HYB800001-31 Rev. A
Page 3

Stacking
Transport units with different widths may not be stacked (the pressure may break the
cover of the lower transport units. It should be noted that stacking causes sideways
instability, and therefore the load has to be fixed, i.e. prevented from dropping, rolling
or falling. It is not allowed to stack more than three transport units.

Figure 4 Stacking

1HYB800001-32 Rev. A
Page 1

Storage prior to erection


General
Circuit breakers intended for outdoor operation are generally delivered in units which
are determined for transport reasons. Intermediate storage of these units should be
avoided. If it is not possible to avoid intermediate storage, they should be stored
indoors or under a roof. They must also be stored above ground level to prevent
water damage. On arrival, it is important that plastic sheets are removed in order to
prevent corrosion by condensate water (except for the spare parts).
Storage in a humid climate without proper ventilation may lead to discoloration of the
galvanised surface. This discoloration is commonly known as white rust, consisting
mainly of zinc oxide and zinc hydroxide and is a result of a chemical process
between the pure zinc on the surface and moisture.
The long term corrosion protection is not influenced, since the iron-zinc layer below
the surface remains unaffected. The presence of white rust is no reason for rejection
of goods.
On arrival, each unit should be checked in the following way :
-

delivery is in accordance with order and delivery documents

any damage in delivery, and material loss

In cases where damages are detected or suspected, the units should be opened and
damages should be photographed. Both damages and shortages should be reported.
All details should be rationally stored so that they are always available. In general, all
material should be stored in an approved storage (note 1), exceptions are given in
the text below. The ambient air should not be heavily contaminated by dust, smoke,
corrosive or combustible gases, vapours or salt, otherwise the equipment has to be
cleaned before erection.
For storage the original transport unit may be used, but the plastic sheeting should
be removed. The coupling joints of the assemblies, as well as all connections, are
fitted with transport covers or protective caps which shall not be removed until
immediately before erection.
Operating mechanism (for circuit breakers)
The operating mechanism should be unpacked on arrival. If it is not going to be
stored in an approved storage (note 1), the heating elements must be connected and
supplied permanently with power to protect the control equipment from corrosion or
freezing damages.
Circuit Breakers
The breakers should be stored in their original transport unit, where they are well
protected from damages. The units shall be prevented from standing in water. The
breakers may be stored outdoors, except for the EDI-breaker, which should be stored
in an approved store. If the breakers are stored outdoors they should be covered with
a tarpaulin. (Note 1)

1HYB800001-32 Rev. A
Page 2

The tarpaulin should not be placed directly on the galvanised surface. An air gap
should be left to prevent condensation. Condensation that may occur should be selfdraining.
For the outdoor breakers, the minimum ambient temperature allowed is -300C. For the
indoor breakers, the minimum ambient temperature allowed is -50C.
Spare parts
The spare parts shall be stored indoors in an approved storage (note 1), in their
original units. This is in particular valid for rubber parts (sealings etc.), which also
have to be protected against light and sun, in order to prevent them from ageing.
Gaskets can be stored only for limited periods, so avoid storage of these parts.
Structures may be stored outdoors.
Notes 1 :
We define an approved storage as a storage with
-

roof
solid ground
relative humidity less than 50%
temperature 20 0C (+/-100C)

1HYB800001-33 Rev. A

Information on SF6 Gas and Gas mixture types SF 6/CF4


and SF 6/N2 when used as breaking and insulation media

Contents :

1.

Introduction

2.

Thermal and dielectric breaking capacity

3.

Chemical reactions in Circuit Breakers

4.

Criteria for choice of mixed gas

5.

Filling mixed gas

6.

Measuring gas mixing proportions

7.

Technical data for SF 6, CF4 and N2 gases

8.

Safety regulations

9.

8.1

Safety regulations for SF 6 gas

8.2

Safety regulations for CF4

8.3

Safety regulations for SF6 and CF 4 gases which


are exposed to arcs

Environmental effect.

1HYB800001-33 Rev. A
Page 1

1.

Introduction
SF6 gas has become the predominant breaking and insulation media for circuitbreakers of puffer and Auto-PufferTM types.
At low ambient temperatures, below - 300 or -400C (depending on filling pressure),
there is a risk of condensation of SF6 gas resulting in drastic density changes. The
temporary condensation at low temperatures is not dangerous but can cause
problems in density monitoring and, temporarily, some reduction of breaking capacity.
One way of avoiding this is to fill sulphur hexafluoride SF6 to a lower density and fill
up to rated density with nitrogen N2 or tetrafluormethane CF4.
Information on characteristics and regulations for SF6 gas, N2 gas and CF4 gas is
stated in this product information.

2.

Thermal and Dielectric Breaking Capacity


When breaking short-circuit currents the circuit-breaker must withstand two separate
stresses at somewhat different times, See Figure A.
2. Dielectric region

Figure A.
Stress on a circuit-breaker at breaking moment
Gas flow

Figure B.
Cooling SF6 arc by cold gas mixture

1HYB800001-33 Rev. A
Page 2

These stresses are :


1.

Thermal range

At current zero the hot arc channel shall be cooled down quickly to a temperature
which makes it electrically non-conductive, Figure B. Cooling capacity depends on
how quickly the current decreases towards zero, di/dt, and on the rate-of-rise of the
recovery voltage after current zero, du/dt, Figure A.
2.

Dielectric range

After current zero the circuit-breaker must, for a short moment, withstand the full top
value of the transient recovery voltage without dielectric breakdown.
Breaking of terminal fault often gives low rate-of-rise of the recovery voltage and is
often a problem in the dielectric range.
Breaking of distance fault is a problem usually concentrated to the thermal area.
SF6 is an electronegative gas of high density with good characteristics in both the
thermal and dielectric ranges.
Mixed gas filling of SF6 and N 2 gives a somewhat deteriorated thermal breaking
capacity as well as a slightly deteriorated dielectric breaking capacity compared with
only SF6 gas filling. Mixed gas filling with nitrogen often results in a reduction of
breaking capacity, e.g., a rated breaking current of 40 kA is reduced one step to 31.5
kA. The deteriorated dielectric characteristics can be compensated by nitrogen gas
filling to a slightly higher pressure than with only SF6 gas.
Mixed gas filling of SF6 and CF6 results in practically unchanged thermal and
dielectric breaking characteristics. A mixed gas filled circuit-breaker with SF 6/CF4
often retains its breaking capacity down to the lowest ambient temperature.

3.

Chemical Reactions in Circuit-Breakers


When an arc burns in the arc chamber, part of the SF 6 gas decomposes but is
quickly restored to SF6 gas when the temperature falls. Heat from the arc added to
gas, contact material, nozzle material, as well as small amounts of moisture residue,
give chemical reactions. The most important of these are :
Arc in teflon nozzle
Teflon is degraded to pure carbon and CF 4 gas.
heat
CF3-(CF 2)N - CF3

CF 2

(1)

C + CF 4

(2)

S + 6F

(3)

heat
2CF2

Arc in SF 6 gas
heat
SF 6

1HYB800001-33 Rev. A
Page 3

The carbon which is formed according to (2) reacts with fluorine atoms which are
produced according to (3) and form CF4 gas, whereby the carbon is bound and
carbonisation is avoided.
4F + C

CF 4

(4)

CF 4, which is an electronegative gas, is therefore formed when the arc affects the
teflon nozzle and SF 6 gas.
Chemical reactions between gas formation and possible moisture residue on surfaces
in breaking units.

SF 4 + 2H 2O
SOF 2 + H2O

SOF2 + 2HF
SO 2 + 2HF

(5)
(6)

Reactions between hydrofluoric acid and porcelain


SiO 2 + 4HF

SiF4 + 2H2O

(7)

Reactions at copper-tungsten contacts

SF6 + Cu
3SF6 + W

heat
SF 4 + CuF2

(8)

heat
3SF4 + WF6

(9)

Degraded gases which can appear in SF6 breakers after a number of years service
are SOF2, CF4, SiF 4 and SO2.
The powder which remains in the breaker poles consists of formation of fluorides.
In the gas analysis of mixed gas circuit-breakers with SF6/N2 and SF6/CF4 no other
degraded products than the above mentioned have been identified.

4.

Criteria for choice of mixed Gas


By mixed gas is always understood a mixture of SF6 and nitrogen gas or SF6 and CF4.
Nitrogen gas and CF4 are both easily available at gas suppliers. CF4 is comparatively
expensive but it is a natural choice since this gas is formed already when the arc
erodes teflon nozzles in SF6 circuit-breakers. See formulae (2) and (4).
Criteria for choice of gas :
SF6 gas is chosen for ambient temperatures down to -300C or -400C
Gas

Lowest
ambient

Filling pressure at +200C


absolute pressure
temperature

Breaking data

SF 6
SF 6

-300C
-400C

0.7 MPa
0.5 MPa

Depends on type of circuitbreaker

1HYB800001-33 Rev. A
Page 4

Mixed gas is chosen for ambient temperatures down to -550C


Gas
Lowest
mixture ambient

SF6/N2

-550C

SF 6/CF4 -550C

Filling pressure at +200C


absolute pressure
temperature

Breaking data in
comparison
with SF6 filling

0.36 MPa SF6+0.34 MPa N2=0.7 MPa

Reduction one
breaking current step

0.36 MPa SF6+0.34 MPa CF4=0.7 MPa Retains breaking capacity

This table is only for information. It is always the relevant product information for
respective circuit breakers which is valid.

5.

Filling mixed Gas


Mixed gas is always filled in such a sequence that SF6 is filled first and then CF4 or
nitrogen gas is filled up to rated pressure at +20 0C according to the rating plate.
By filling SF 6 first a satisfactory gas mixture, without layers of gas, is always
obtained. Otherwise, the mixing process takes a long time since it is based on
diffusion and convection. At gas loss, for example due to leakage, refill with correct
mixing proportions and always with SF 6 gas first.

6.

Measuring Mixing Proportions


Mixing proportions for mixed filling can be measured by DILO SF6 Percentage
Measuring Device 3-027.
The instrument measures the sound velocity of the gas mixture and it is calibrated for
SF6/N2 gas. The instrument shows directly on the display the volume of the SF6 part.
If the instrument is used to measure SF6/CF4 gas mixture, the result shown on the
display must be corrected according to figure C. (Example: If 51% is read on the
instrument, the SF 6 part is 0% and the CF4 part 100%)
100
SF6 (%)
In
SF6/CF4

90
80
70
60
50
40
30
20
10

DILO

0
50
60
70
Figure C.
SF 6 part in SF6/CF4 gas as a function of
the shown result on the display of DILO 3-027.

80

90

100

DISPLAY

1HYB800001-33 Rev. A
Page 5

7.

Technical Data for SF 6, CF4 and N2 Gases


General
information:

SF 6

CF4

2.3 MPa

13.7 MPa

20 MPa

Valve thread (local


& national deviations
can occur)

G5/8A-RH

CGA580

G5/8A-RH

Material recommendation

No restrictions

Avoid
zinc
magnesium

None

Hygienic limit:

1000 ppm

Characteristics:

No colour
or smell

No colour
or smell

No colour
or smell

Health risks :

Suffocating

Suffocating

Suffocating

Transport:

ADR
Class 2.5(a)

ADR
Class 2.1(a)

ADR
Class 2.1(a)

Storage:

Group 1A

Group 1A

Molecular weight

146.05

88.01

28.01

Boiling point
at 1.013 bar 0C

-63.8

-127.94

-195.8

Density
(1.013 bar 150C)kg/m3

6.25

3.74

1.185

Vapour pressure
at 00C MPa

1.26

Vapour pressure
at 200C MPa

2.3

Physical data:

Max. bottle pressure


at 200C

Combustible
range in air

Non-combust. Non-combust. Non-combust.

Specific volume m 3/kg


(1.013 bar, 150C)
0.160
Critical temperature 0C 46
Critical pressure MPa

N2

3.7

0.268

0.844

1HYB800001-33 Rev. A
Page 6

8.

Safety Regulations
8.1

Safety Regulations for SF 6


SAFETY REGULATIONS FOR SULPHURHEXAFLUORIDE
HEALTH RISK
Sulphurhexafluoride is considered to be an inert gas.
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
SPECIAL CHARACTERISTICS AND RISKS
At high temperatures degraded products, which cause irritation, can be formed.
PREVENTIVE MEASURES
Good ventilation.
Safeguard gas bottles with chains.
PERSONAL PROTECTIVE EQUIPMENT
Inhalation apparatus for use at suffocating gas content.
FIRST AID
Inhalation: fresh air, rest
SPILLAGE AND DEGASSING
Airing
MEASURES AT FIRE
Gas containers near the fire must be removed immediately or cooled with
water.

8.2

Safety Regulations for CF 4 gas


SAFETY REGULATIONS FOR TETRAFLUORMETHANE
HEALTH RISK
Tetrafluormethane is considered to be an inert gas.
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
SPECIAL CHARACTERISTICS AND RISKS
At high temperatures degraded products, which cause irritation, can be formed.
PREVENTIVE MEASURES
Good ventilation.
Safeguard standing gas bottles with chains.

1HYB800001-33 Rev. A
Page 7

PERSONAL PROTECTIVE EQUIPMENT


Inhalation apparatus for use at suffocating gas content.
FIRST AID
Inhalation: fresh air, rest.
SPILLAGE AND DEGASSING
Airing
MEASURES AT FIRE
Gas containers near the fire shall be removed immediately or cooled with
water.

8.3

Safety Regulations for SF6 and CF4 gases which are exposed to arc
HEALTH RISK
Air humidity together with degraded products can cause irritation of skin,
eyes, and mucous membranes.
INHALATION of very high gas content can cause headache, giddiness and
risk of unconsciousness and suffocation due to lack of oxygen.
SPECIAL CHARACTERISTICS AND RISKS
Since the gas has been exposed to high temperatures degraded products,
which cause irritation, have been formed.
PREVENTIVE MEASURES
Good ventilation.
Gas from circuit-breakers can be recovered in gas treatment equipment and reused.
PERSONAL PROTECTIVE EQUIPMENT
Fresh air mask or mask with filter against fine dust and gases with acid content.
Plastic or rubber gloves.
Overalls with long sleeves.
Vacuum cleaner with filter for fine dust.
FIRST AID
Inhalation: fresh air, rest.
Skin and eyes: rinsing with water.

1HYB800001-33 Rev. A
Page 8

SPILLAGE AND DEGASSING


Airing
Dust and filters shall be stored sealed and handled as chemical refuse according to
local regulations.
MEASURES AT FIRE
Gas containers near the fire must be removed immediately or cooled with
water.

9.

Environmental Effect
SF6 and CF4 gases can leak out into the surrounding environment due to leakage in
the circuit-breaker.
CF 4 and SF6 are very stable gases and make no detectable contribution to ozone
destruction and photochemical smog, and they have negligible influence on the green
house effect. The latter applies especially when used in circuit-breakers where, from
the global point of view, gas volumes are small.

1HYB800001-35 Rev. A
Page 1

Safety Provision and Assembly Instructions for CircuitBreakers with Operating Device.
Read carefully the entire Assembly Instruction before starting assembly work.
WARNING TEXTS
Warning texts are stated in 5 different degrees of urgency which should be carefully
observed. These are described below :

DANGER indicates an immediate risk situation that can lead to death or serious
personal injury if not avoided.
DANGER

Warning indicates a risk situation that can lead to death or serious personal injury if
not avoided.
Warning

Caution indicates a risk situation that can lead to small or moderate damage.
Caution

Note

Important

Note is used when there is danger that can lead to equipment damage only.

Important indicates an operation or a suggestion for handling.

1HYB800001-35 Rev. A
Page 2

1.

Safety Regulations
When working on high-voltage circuit-breakers the below-mentioned risks must be
taken into consideration and corresponding safety measures taken.

RISK

1.

MEASURE

Work next to high-voltage

Warning plate placed inside the door to the


operating device
Disconnect and earth near the workplace. If work
must be carried out near energized parts of the
plant, it has to follow local safety regulations of the
organisation responsible for the circuit-breaker.

2.

Work on ladders and platforms

The work shall follow the directions of the Authority


for occupational safety and health. Avoid work in
severe weather conditions which entails a great
deal of climbing for short periods.

3.

Work with low-voltage.


Both D. C. and A. C. voltage may have been
connected on the operating device.

Do not connect control or heating voltage until all


connection work is completed.

4.

Squeezing risk in operating device and


link system.

Warning plate is placed on the supporting frame.

The spring operated device has energy


stored in the closing spring. The opening
spring, which is on the mechanism housing of
pole C1, or on every pole for one-pole
operation, has energy stored. The device can
be activated by heavy vibrations or
unintentional slight touch on mechanical latch
parts.

5.

Work on pressurized porcelain insulators.


Normally, the work pressure is up to 0.7 MPa.
Damage in the porcelain can cause the
porcelain to break,

No work must be carried out unless the closing and


opening springs are uncharged and the circuitbreaker in position OFF O disconnect voltage to
the motor.
-

The operating device must not be operated


unless it is connected to the circuit-breaker
and the electric cables are connected. The
circuit-breaker shall be filled with SF 6 gas to
a pressure of 0.7 MPa. The closing springs
should for safety reasons be uncharged
during transport and when the circuit-breaker
is off duty.

Work close to the insulators of the circuit-breaker,


which entails risk to damage the porcelain, must
not be carried out until the gas pressure has been
lowered to 0.125 MPa absolute pressure.

1HYB800001-35 Rev. A
Page 3

2.

Unpacking
Place the case hoizontally on a flat surface before opening the cover.
Check that all parts are included in the delivery. Check-off on the accompanying
packing list.
Check that no parts have been damaged during transport, especially the porcelain
insulators.
Report any faults immediately to the ABB Representative.

1HYB800001-36 Rev. A

Disposal and Recycling

Information

The information in this document is subject to alteration without prior notice and should not be regarded as an
undertaking from ABB Limited. ABB Limited takes no responsibility for errors that can occur in the documentation.
ABB Limited is not responsible for damage incurred due to the misuse of this document.
The document, or parts thereof, may not be reproduced or copied without prior permission from ABB Limited.
It may not either be imparted to third pary or otherwise be used without authorisation. Infringement hereof will
be subject to action in accordance with applicable laws.

ABB Limited

1HYB800001-36 Rev. A

Contents

1.

Disposal and recycling


1.1

General

1.2

Taking care of spent equipment

1.3

The circuit-breakers component parts

1.4

SF6-gas

1.5

Porcelain

1.6

Electronics

1.7

Metals

1.8

Plastics

1.9

Oils and greases

1.10 Rubber
1.11 Other materials

1HYB800001-36 Rev. A
Page 1

1.

Disposal and recycling

1.1

General
ABB Limited attempts to minimize environmental impact during the entire products
service life. Environment aspects are held in focus during technical and product
development. We always try to consider the eco-cycle while the materials impact on
the environment and possibilities of recycling are observed. Manufacturing processes
are selected that are as gentle as possible on the environment.

1.2

Taking care of spent equipment


Spent products should be taken out of service in an environmentally correct manner
according to the following instructions.
When discarding used equipment a great deal of material and the energy content of
the material can, after sorting and cleaning, be recycled. The degree of material that
can be recycled varies depending on the technical resources and experience
available in respective countries.
Non-recyclable components shall be left at an approved recycling centre for
destruction or disposal.

1.3

The circuit-breakers component parts


A circuit-breaker contains approximately 30 weight % metal, primarily iron, steel and
aluminium. Rubber and different plastics make up approximately 0.5% each and
chemicals and gas less than 0.5%. The greatest weight share in a circuit-breaker,
virtually 70%, is made up of porcelain.

1.4

SF 6-gas
The SF6-gas must be emptied before discarding a circuit-breaker. Care shall be
exercised in accordance with applicable regulations with all handling of SF 6-gas, to
prevent gas leakage. The gas can be taken care of in different ways depending on
the circumstances :

Regenerated on site, and reused in other equipment

Sent to a gas supplier for regeneration

Sent for destruction at a special waste disposal centre

In those cases where the circuit-breaker is filled with mixed gas, the SF6-gas is
separated from the mixture for continued handling as set out above. Alternatively, the
gas mixture can be sent for destruction without being separated.
ABB Limited will willingly take care of the gas when the circuit-breaker is to be
discarded.

1HYB800001-36 Rev. A
Page 2

1.5

Porcelain
Porcelain can, after cleaning, be left for disposal or used for other purposes, for
example, as a filling material.

1.6

Electronics
Leave electronic equipment at an approved recycling company or sort out its
component parts and take care of them accordingly.

1.7

Metals
Sort metals according to type and surface finish and leave at an approved recycling
company. After the removal of any paint or other surface treatment, the metal can
generally be melted down and used in new products. Many iron, steel and aluminium
parts are large and easy to identify, for example, the frame and mechanism housing.
ABB Limited aims for a reduction in the use of noble metal, or with discharge
environmentally hazardous metals. Recycling of these is extremely important.
Noble metals such as copper and silver are expensive and only occur is small
quantities in the earths crust. Copper is primarily used in the current paths, puffer,
contactors and cables. Silver plating of contactors can occur. Some metals can cause
damage if discharged. This applies, among others, to copper, but also to zinc and
nickel which are used sparingly in the form of surface treatment.

1.8

Plastics
Separate different types of plastic and leave at an approval recycling centre or
recycling company. The energy content in thermoplastics and thermosetting plastics
can frequently be recovered through combustion in purpose built installations.
Generally, thermoplastics can be melted down and used again without degrading
quality too much. Composites can be fractionised and used as filling agent in other
materials or be left for disposal.
Composites found in small quantities in isolators, pipes and cable glands consist of
thermosetting plastic. Thermoplastics can be found in components such as guide
rings, belts bushings and support rings. Thermoplastic in ferrules, nozzles, pipes and
collars contains fluorine and is not suitable for recycling, however, it can be disposed
of without the risk of leaking hazardous substances.

1HYB800001-36 Rev. A
Page 3

1.9

Oils and greases


Empty oils, grease and the like before discarding and leave at an approved recycling
centre or at a recycling company. Oil waste can be separated into oil, water and
different contamination through the use of gravimetric forces. In many cases the oil
can be reused. Alternatively, the oils energy content can be recovered through
combustion in purpose built installations.
Oil can be found in dashpots and grease is used as a lubricant.

1.10 Rubber
Rubber can be left at an approved recycling centre either for disposal or reused for
different purpose.
Rubber can be found in seals.

1.11 Other materials


Sort and leave other materials at an approved recycling centre.

1HYB800001-54 Rev. A

SF6 CIRCUIT-BREAKER type EDF SKS 1-1


Rated voltage 52-72.5 kV
With operating mechanism type FSA 1(F)

INSTRUCTIONS FOR ERECTION,


OPERATION AND MAINTENANCE

CONTENTS

1. GENERAL
2. DESIGN
3 . FUNCTION
4. ERECTION
5. COMMISSIONING
6. TROUBLESHOOTING
7. MAINTENANCE
8. SPARE PARTS AND MATERIAL FOR OVERHAUL
11 APPENDIX

1HYB800001-54 Rev. A

Contents

Page

1.

GENERAL

1.1
1.2
1.3
1.4
1.5

Validity
Type designation
Technical data
Masses
Storage

1
1
1
1
1

2.

DESIGN

2.1
2.2

Breaker pole
SF6 gas system

2
2

3.

FUNCTION

3.1
3.2
3.2.1
3.2.2
3.2.3

Control and monitoring


Switching operations
Starting conditions
CLOSING operation
OPENING operation

2
3
3
3
3

4.

ERECTION

4.1
4.1.1
4.2
4.2.1

General
Preparation for erection
Erection procedure
Fitting motor-operated
spring-closing mechanism
4.2.2 Fitting the connecting rod
4.2.3 Fitting density monitor and cables
4.2.4 High-voltage connections

3
3
4
4
4
4
4

5.

COMMISSIONING

5.1
5.2.1
5.2.2
5.3
5.3.1
5.3.2
5.3.3
5.4
5.5

Starting conditions
Filling SF6 gas to rated pressure
Filling mixed gas to rated pressure
Function test
Trial switching operations
Anti-pumping device
Control of heater
Concluding work
Checklist for Assembly and Commissioning

5
5
6
6
7
7
8
8
9

TROUBLESHOOTING

13

6.1
6.2

SF 6 gas system
Control circuits

13
13

7.
7.1
7.2
7.3
7.4
7.5
7.6

MAINTENANCE (OVERHAUL)
Maintenance Summary
Maintenance category A
Maintenance category B
Maintenance category C
Maintenance category D
Table of parts to be serviced

14
15
16
17
19
24
25

7.7 Tools, Jigs, Fixtures & Accessories


7.8 Maintenance Procedures
7.9 Preparation for overhaul
7.9.1 Taking Circuit Breaker out of Service
7.10.1 Dismantling of SF6 gas lines
7.10.2 Removal of breaker poles & mechanism
housing
7.11.1 Disassembly of breaker pole B1
7.11.2 Disassembly of fixed contact
7.11.3 Disassembly of moving contact
7.11.4 Cleaning
7.12
Overhaul of component groups
7.12.1 Overhaul of fixed contact
7.12.2 Overhaul of moving contact
7.12.3 Overhaul of link gear
7.13 Assembly of breaker pole
7.14 Erection of breaker poles
7.15 Overhaul of spring operating mechanism
8.

SPARE PARTS AND MATERIAL


FOR OVERHAUL

26
26
26
26
26
26
27
28
28
28
28
28
29
30
30
32
33

33

8.1 General
33
8.1.1 Important directions
33
8.1.2 Ordering spare parts and material
for overhaul
33
8.2 Spare part lists for overhaul
33
8.2.1 Set of contacts for one breaking unit
33
8.2.2 Set of gaskets, springs, fasteners for one
breaker pole
33
8.2.3 Complete set of gaskets for gas
monitoring system
34
8.2.4 Set of gaskets for one link gear
34
8.2.5 Spare parts for FSA-1
34
8.2.6 Overhaul tools for EDP SK
35
8.2.7 Gas filling equipment
35
8.2.8 Safety disc unit
36
11.

APPENDIX

11.1 Figure sheets

37
37

1HYB800001-54 Rev. A
Page 1

GENERAL
1.1 Validity
This document covers high-voltage circuit-breakers, type EDF SKS.
Type designation EDF SKS means that the circuit-breaker has been adapted to
synchronous coupling. The adaptation is carried out in the mechanical arm and link
system in the circuit-breaker mechanism housing, so that there is a time difference in
contact closing or contact opening.
When connecting capacitor stacks, for example, the following time differences can occur.
Earthed capacitor stack
Pole A1
+6.66 ms
(after pole C1)

Pole B1
+3.33 ms
(after pole C1)

Pole C1
0 for 50 Hz

Unearthed capacitor stack


Pole A1
Pole B1
+5 ms
0
(after poles Bl and C1)

1.2 Type designation

Pole C1
0 at 50 Hz

F SK

1 - 1

SF 6 gas insulation
Generation
Outdoor design
Type of arcing chamber
Synchronous coupling
Circuit-breaker design
Insulation BIL Rated voltage
1 ~ 325 kV ~ 52/72.5 kV
Number of breaker chambers

1.3 Technical data


Technical data can be seen in order-related documentation and rating plate (fig.1/1). The
diagrams in this instruction are mainly intended to explain the functional principles.

1.4

Masses
Information about masses for a three-pole circuit-breaker can be found in the order
documentation and delivery documents. For internal transport, see fig. 1/2.

1.5

Storage
The circuit-breakers intended for outdoor operation are usually dismantled in suitable
units for delivery. Before erection, these units should as far as possible be stored
indoors or under roof. If the units are to be stored outdoors, they shall be blocked up so
that they do not stand in water. If the units are to be stored outdoors for a long time,
they should be covered with tarpaulins and have their heating elements switched on.

1HYB800001-54 Rev. A
Page 2

DESIGN (fig. 2/1)


- Circuit-breaker type EDF SKS 1-1 is a three-pole SF6 circuit-breaker.
The circuit-breaker consists mainly of:
-

2.1

three breaker poles 10171 with rating plates A1, B1 and C1


support frame 10172
control cubicle with spring operating mechanism and connecting rod 10173
density monitor 10112
breaker support 10174

Breaker pole (fig. 3/la, b:1,2,3)


The breaker pole consists mainly of:
-

upper terminal flange 10099 *)


breaker chamber insulator 10106
fixed contact compl. 10030
moving contact compl. 10013
lower terminal flange 10108
post insulator
link gear
10185

*) On this flange there is a cover which can easily be exchanged by a safety disc
unit, if the customer so wishes.
The poles are filled with SF6 gas (transport pressure) and connected to a header
block via tubes (fig. 4/la,c).

2.2

SF 6 gas system (fig. 4/1a,c)


The gas system consists of:
- an SF6 gas density monitor 10112 with header block 10118
- check valve 00112 (fig. 7/5)
- SF6 connection line L10177/a, L10177/b and L10178

FUNCTION
3.1

Control and monitoring (Fig. 3/2)


The electrical principle drawing shows how the switching commands enter the control
circuit of the circuit-breaker, the monitoring units which are built in to sense any
interference which might occur, and the signals which are then triggered.
The control circuit itself can be seen in the order-related circuit diagram.
Monitoring unit:
-

Gas density
The density monitor 10112 (temperature compensated pressure monitor)
monitors the insulation gas pressure in the breaker poles and sends, via its
auxiliary contactor, the signal filling of SF6 gas if gas losses have occurred. If
the gas pressure decreases to a value below that shown in the blocking
pressure curve, fig. 5/1, the CLOSE and OPEN operations are blocked and
simultaneously an alarm signal is given.

1HYB800001-54 Rev. A
Page 3

3.2

Switching operations (fig. 3/1a, b)


3.2.1 Starting Conditions
-

SF6 gas is filled to the rated pressure


The operating mechanism is in breaking position b2 (fig. 2/1), i.e. closing spring
charged and in OPEN position.

3.2.2 CLOSING operation (fig.3/1b)


-

The switching command is issued via a control element CLOSE. The


operating mechanism is then tripped and operates the moving contacts upwards
via the mechanical transmission. Thereby first arc contact g-h is closed and,
thereafter, the rated current contact k-l.

3.2.3 OPENING operation (fig. 3/1a)


-

The switching command is issued via a control element OPEN. The


operating mechanism is then tripped and operates the moving contacts
downwards via the mechanical transmission. Thereby, first the operating current
contact k-l is opened and, thereafter, the arc contact g-h. During this
movement the piston compresses the gas in the cylinder. The arc which rises
between the contacts increases the compression pressure. In the zero current
area a gas flow occurs, which blows intensively on the arc and extinguishes it.

ERECTION
4.1 General
-

All adjustments have been carried out in the works.


All moving parts which shall be assembled together have already been adjusted
and fixed in correct position in the works.

Transport packing for breaker poles should be suitably kept to facilitate transport,
if necessary, at later overhaul.

Breaker poles are filled with insulation gas Pabs. = 150 kPa (~ 1.5 bar) in order to
prevent any moisture absorption.

4.1.1 Preparation for erection


The following shall be prepared and procured before erection:
-

Crane with a lifting capacity of approx. 850 kg and a hoist height of at least 4 m
above floor level.

Lifting ropes

Dimension drawing, erection drawings and circuit diagram.

Circuit-breaker material according to erection drawings.

Torque wrench 6...200 Nm with socket 24 mm (connection 3/8").

Open-end/ring type wrenches for M6-16 and 1/2" UNC as well as open-end wrench
for 36 mm.

Normal thermometer for ambient temperature.

Gas filling equipment and an SF6 gas cylinder

SF6 leak detection instrument

1HYB800001-54 Rev. A
Page 4

4.2 Erection procedure


-

Lift the completely assembled circuit-breaker by crane according to fig. 4/2.

- Check the SF 6 gas pressure by pressing the disc of the check valve inwards
with a 5 pin. A distinct blow-off sound from the pole shall be heard. If there is no
blow-off sound, the pole has a leak which must be repaired.
Place frame support 10174 on the foundation. The top supporting surfaces, where the pole
beam is mounted, must be at the same level (horizontally). Screw the frame support to the
foundation. Observe tightening torque MD, fig. 2/1. The exact location is shown on the
installation layout. Observe the location of the holes for the earthing clamp (fig. 2/1).
Mount the frame 10172, with assembled poles 10171, on the support 10174 with
screw, nut and washer, 49069, 49622 and 89027. Observe the tightening torque
MD=190 Nm, fig. 4/1a:1, 2.
4.2.1 Fitting motor-operated spring closing mechanism (fig. 4/1a:1,2)
Place the mechanism on a wooden structure in correct position for mounting between
the frames.
-

Lift up the operating mechanism by the four upper eyes, place the bolts for the
operating mechanism in the holes intended for them and fasten with enclosed
fasteners h (note the MD). Make sure the middle pole is not damaged by the sling.

CAUTION
During lifting the upper joint head of the connecting rod must be fitted into the fork on
the actuating lever 10154.
4.2.2 Fitting the connecting rod
- Starting condition: Indication of circuit-breaker position and spring charging shows
positions b1 and uncharged, respectively, (fig. 2/1).
- Couple the operating mechanism and circuit-breaker to each other in OPEN
position, i.e. turn the actuating lever on the circuit-breaker towards the operating
mechanism until the actuating lever, 10154, stops and the hole in the connecting
rod, f, correspond (fig. 4/1b).
-

However, if holes do not correspond, the operating rod length must be adjusted.

This is done by releasing the lower fasteners g (fig. 4/1a) and by lowering the cubicle.

Release locknuts h and k of the operating rod (fig. 4/1b) , turn operating rod to
adjust length. Tighten locknuts by holding the operating rod (Observe MD)

4.2.3 Fitting density monitor and cables


Connect the density monitor 10112, density monitor cables and pressure gauge, if
any, according to fig. 2/1, 4/1:1,2.
4.2.4 High-voltage connections (fig. 4/1:1,2)
The assembly parts for high-voltage connections consist of screw M12 (8.8) and at
least 1 washer 13/28x3 mm, 1 locking washer 13.5/28x1.6 mm on each side of the
screw. (Observe the tightening torque MD)

1HYB800001-54 Rev. A
Page 5

5. Commissioning
All data which are checked or measured are to be entered in a commissioning record
and preserved for comparisons.
The SF 6 gas pressure can be seen on the circuit breaker nameplate.

5.1 Starting conditions


The erected circuit breaker is isolated from the high-voltage system and earthed according to regulations. The control current circuits are connected to the low-voltage system.
5.2.1 Filling of SF 6 gas to nominal filling pressure (Fig. 5/1)
As the circuit-breaker poles are delivered vacuum processed and filled with SF6 gas
at a transport pressure of 0.150 MPa abs (200C), during commissioning only one
filling of SF6 gas is required, to top up pressure up to the filling pressure given on the
rating plate.
It is appropriate to carry out pressuring directly from an SF 6 gas bottle. In order to
avoid risks at the first filling, due to possible transport damages to the porcelain, the
gas bottle with filling equipment shall be placed as far from the circuit-breaker as
possible, and preferably behind some shield. Pole columns are connected to the
header block by pipes. Connect the hose from the gas filling equipment to the SF 6
gas filling valve on the header block L10118 (Fig. 4/1c).
-

SF6 gas filling (Fig. 4/1d)

Place gas cylinder (1) in a protected area.


Check the filling pressure and any gas mixture (at ambient temperature lower
than -300C) on the circuit breakers rating plate.
Fit the regulator (3) on the gas cylinder using appropriate coupling (2) supplied
with gas filling device. Use the pressure gauge (9) for filing gas in circuit breaker.

Lubricate the sealing rings supplied with density monitor (7) with grease G.

Fit the density monitor on the gas valve (8) on the breaker.

Connect coupling (4) supplied loose with gas filling bag to the non-return valve
on the hose of gas filling device.

Connect above assembly to the circuit breakers gas valve (5).

Open regulator to fill gas in circuit breaker to rated pressure as per fig. 5/1.

Allow the pressure to stabilise in the circuit breaker for some time. Check the
pressure and adjust if necessary.

Dismantle the hose coupling assembly from the gas valve on the circuit breaker.

Close the valve on the gas cylinder.

Disconnect regulator with hose from gas cylinder. Breaker is now ready for
functional test as per section 5.3.

In the filling process the dependence of the nominal pressure on temperature (Fig. 5/
1) must definitely be taken into account. After a temperature equalization period of
approx. 1 hour, check the pressure and correct if necessary by adding or releasing
gas. Check all sealing joints on the breaker poles and the gas supply system for
leaks with a leak detector. Repair any leaks found according to chapter 6.

1HYB800001-54 Rev. A
Page 6

5.2.2 Filling mixed gas to rated pressure


When the circuit-breaker is erected in a climate with temperatures below -30C, fill
mixed gas instead of pure SF6.
In order to avoid condensation at temperatures below -30C, mix the SF6 gas
with CF4 (carbon tetrafluoride) or N2 (nitrogen gas). The CF 4 gas has good breaking
capabilities, like SF6, while N2 gas often reduces the breaking capacity.
Choice of gas mixture:
Gas mixture

Breaking data
Rated breaking
current

Network frequency

SF6/N2

25 kA
20 kA

50 Hz
60 Hz

SF6/CF4

25 kA
25 kA

50 Hz
60 Hz

The rating plate states the total filling pressure for mixed gas. The breaker poles are
delivered vacuum processed or filled to pressure 0.15 MPa abs. (20C). When
commissioning, first fill the SF 6 gas proportion, 0.36 MPa abs. at 20C, and thereafter N2 or CF4 proportions up to the total filling pressure according to the
rating plate.
Normally, gas filling is:
with SF6/N2 at 20C
0.36 MPa SF6 + 0.34 MPa N2 = 0.7 MPa abs.
with SF6/CF4
0.36 MPa SF6 + 0.34 MPa CF4 = 0.7 MPa abs.
When filling gas after possible leakage, refill with SF6 and N2 or CF4, respectively,
in the proportions stated above. For example, leakage to blocking level 0.6 MPa
abs. entails refilling with SF6/N2.
SF6 gas 0.36 0.1 ~ 0.051 Mpa SF6 at 20C
0.7
N2 gas 0. 34 0 .1~ 0 . 04 9 Mpa N2 at 20 C
0.7
At gas filling observe the influence of temperature on pressure. Fig. 5/1, curve 4, for
SF6 filling, and continued filling up to curve 1 for N2 or CF4 gases.

5.3 Function test


Before function testing, check with order-related circuit diagram. Check also the
connections. Thereafter, trial switching can be run from a sheltered place.
This trial switching shall take place only if:
-

the circuit-breaker is disconnected from the high-voltage network and earthed


according to regulations

SF6 gas or mixed gas pressure is at rated pressure

spring charging indicator on the spring operated mechanism is in position b2 (fig.


2/1) charged

1HYB800001-54 Rev. A
Page 7

5.3.1 Trial switching operation (fig. 5/2a,b)


Measure the function times. Fig. 5/2a shows the principle diagram for such a
measurement. Thereby, each breaker pole has its own measuring circuit. The time
diagram in fig. 5/2b is solely intended as an explanation of the time expression used.
-

CLOSING operation (C) (fig. 5/2b) Closing time t1. 60 ms is the time from
switching command issue to contact closing in the arcing chamber. This shall be
measured on each breaker pole.

The time differences between the poles are:


For earthed capacitor stack
Pole A1
+6.66 ms +2/-0.5 ms
(after pole C1)

Pole B1
3.33 ms 1 ms
(after pole C1).

Pole C1
0

For unearthed capacitor stack


Pole A1
+5 ms +2/-0.5 ms
after pole C1

Pole B1
0 1 ms
after pole C1

Pole C1
0

or depending on the application.


-

OPENING operation (O) (fig. 5/2b)


Opening time t2 35 ms is the time from switching command issue to contact
opening in the arcing chamber. This shall be measured on each breaker pole.
The time differences between the poles are:
For earthed capacitor stack:
Pole A1
+6.66 ms +2/-0.5 ms
(after pole C1)

Pole B1
3.33 ms 1 ms
(after pole C1)

Pole C1
0

For unearthed capacitor stack:


Pole Al
+5 ms +2/-0.5 ms
after pole C1

Pole B1
0 ms 1 ms
after pole C1

Pole C1
0

or depending on application.
-

CLOSE-OPEN switching (C-0) (fig. 5/2b)


Close-Open time t3 40 ms is the time from contact closing to contact
opening in the arcing chamber at a switching cycle CLOSE-OPEN.
For measuring, short-circuit terminals K1 and K2 on the close-open switch
M3 (fig. 5/2a).

Rapid reclosing (O-C-O)


Rapid reclosing can only be controlled together with the monitoring equipment
for the plant.

5.3.2 Anti-pumping device (fig. 5/2a)


-

CLOSE command is issued by connecting control voltage to terminal 2. The


voltage prevails.

- OPEN command is issued by connecting control voltage to terminal 6.


The circuit-breaker is in position OPEN and despite the prevailing CLOSE command
remains in position OPEN.

1HYB800001-54 Rev. A
Page 8

5.3.3 Control of heater

Measure the resistance or apply voltage and measure the current.

When the thermostat controlled additional heater is installed, check the thermostat
setting.

5.4 Concluding work


-

Remove all test and measuring equipment.

Connect the circuit-breaker to the high-voltage network.

Check that the safety regulations are followed. Put the circuit-breaker into service.

1HYB800001-54 Rev. A
Page 9

5.5

Checklist for assembly and commissioning

DATE

PLATE OF INSTALLATION

SERIAL NUMBER
3

NAME PLATE DETAILS

Circuit breaker type

e.g. EDF SKS 1-1

Rated voltage

kV

Sr No :

Normal Current

Gas Pressure SF6 / 20 deg.C. (abs):

Lightning Impulse withstand voltage

kV

Short circuit breaking current

kA

Short time withstand current

3s

Line charging breaking current

Closing & Opening supply voltage

VDC

Operating sequence

O - 0.3 s - CO - 3 min - CO

First pole to clear factor

1.5

Complete material is available as per packing list ?


If NO mention the shortages :

Instruction manual available ?

G.A. and erection drawing available ?

Schematic drawing available ?

Operating drives box stored indoor ?

Accessories box stored indoor ?

Was the outdoor equipment stored above HFL (Highest flood level ) ?

Any equipment damaged during re-transportation / unloading at site ?

ERECTION
1

Is foundation and location of equipment as per G.A. drawing ?

STRUCTURE ERECTION
a

Is length of the foundation bolts (projecting outside) sufficient to put checknuts ?

Is there levelling nut available below structure ?

Is the top side of the structure base plate as per G.A.. Drawing ?

Is direction of the structure as per G.A. drawing ?

Is the structure levelled in x , y and z axis as per G.A. drawing ?

bar

kA

STORAGE
1

X = Pole to pole distance (Measuring tape)


Y = Structure Height (Water tube level)
Z = Alignment of all the structures in one line (Line thread)
f

Tightness of the nuts and checknuts done ?

Are the foundation bolts filled with mortar ?

Are the serial nos. of all the equipment matching with the serial numbers
mentioned in the packing list ?

YES

NO

YES

NO

1HYB800001-54 Rev. A
Page 10

YES

BREAKER POLES ERECTION :


a

Is there any chipping on the sheds of insulators ?


If YES what is the size of chipping ?
Can erection work proceed further ?
DO NOT PROCEED FURTHER , IF CHIPPING IS UNACCEPTABLE

Is 0.5 bar positive pressure verified in the breaker poles?


Verification to be done by pressing the gas valve after opening the cover.

Any damage observed on gas pipe while mounting the breaker poles
on the structure ?

Any washers left in between the breaker pole channels and the structure ?
DO NOT PROCEED FURTHER BEFORE REMOVING THE WASHERS

Application of Torque on all the mounting bolts ?


If YES , mention the values :
1. Foundation bolts
2. Structure hardware
3. Pole mounting bolts

Nm
Nm
Nm

FIXING OF OPERATING MECHANISM


a

Is there any ingress of water found inside the mechanism?


If YES : DO NOT PROCEED FURTHER BEFORE OVERHAULING OF THE MECHANISM.

Is following procedure adopted for fixing the mechanism?


Ensure that breaker poles are in fully OPEN position.
Lift the mechanism and fix the 04 mounting bolts with the pole beam.
Match the Eye-bolt of the mechanism connecting rod with the lever on pole.
Apply thin layer of grease on the pin before inserting in the eye bolt.
After insertion of pin, tighten the locking screw with locking washers.
GAS FILLING AND LEAKAGE TEST :
Prerequisite for SF6 gas filling :
Thermometer
Temperature v/s pressure chart
SF6 gas cylinder
Gas filling kit
Suitable right / left adaptor (Gas cylinder)
Spanners
Cloth
Cleaning agent

Presence of positive pressure checked in breaker poles.


If NO , Fill the pressure in that particular pole upto 2.0 bar absolute and sniff
all the pole including gas pipe with the leak detector and find the leakage.
If no leakage is found , continue gas filling and if any leakage is found ,
first ATTEND the leakage point before proceeding further.

Is the gas monitoring system fixed as per G.A. drawing ?

CALIBRATION OF DENSITY MONITOR / SWITCH.


AMBIENT TEMPERATURE AT SITE DURING CALIBRATION OF
DENSITY SWITCH & SF6 GAS FILLING IN POLES>
DEG.C.
IS THERMOMETER AVAILABLE?
IS GAS FILLING KIT AVAILABLE?
BLOCKING
CONTACT / SETTING VALUES IN ABS.BAR

DEBLOCKING

NO

1HYB800001-54 Rev. A
Page 11

REFILL ALARM
OP. BLOCK I
OP.BLOCK II
TIME AT WHICH CALIBRATION DONE :
e

AM

PM

SF6 GAS PRESSURE FILLED AFTER CALIBRATION OF DENSITY SWITCH


SF6 gas filled in the breaker
:
Bar
Temperature at which gas filled .
degree C
Time at which gas filled
AM /
PM
SF6 GAS LEAKAGE TEST :
Is Leak detector available?
If NO , do not proceed further till leak detector is arranged.
Is the complete SF6 gas system in the breaker (which includes pole,
gas pipes & density switch / monitor ) free from any SF6 gas leakage ?
If NO , describe leakage found from which joints :

YES

COMMISSIONING :
a

Connection of density switch cables :


Density switch cable
closing circuit terminals :
trip 1 circuit terminals
:
trip 2 circuit terminals
:

Control coil resistance :


CLOSE COIL :
TRIP COIL - 1
TRIP COIL - 2

W
W
W

Requirement of DC control voltage in ideal condition :


Measured control voltage
SWITCH ON AC / DC supply.

Local operation of the breaker ( electrically) :


Local closing operation
Local tripping operation for trip coil 1
Antipumping function
* Open command provided directly on terminal number :

dc
dc

OK
OK
OK

Remote operations :
Close command given on terminal number :
Open command (T1) given on terminal number :
Open command (T2) given on terminal number :
SPARE CONTACTS OF AUXILIARY SWITCH :
Position of the breaker
:
Serial number of contacts found NC :
Serial number of contacts found NO :
Position of the breaker
:
Serial number of contacts found NC :
Serial number of contacts found NO :

TRIP

&__
&__
&__

CLOSE

BREAKER OPERATING TIMES


OPERATION
CLOSING

LIMIT
< 60 milliseconds

PHASE

Measured value

ms

ms

ms

NO

1HYB800001-54 Rev. A
Page 12

OPENING ( T1 )

OPENING ( T2 )

< 35 milliseconds

< 35 milliseconds

CO ( through T1 ) < 40 milliseconds

CO ( through T2 ) < 45 milliseconds

ms

ms

ms

ms

ms

ms

ms

ms

ms

ms

ms

ms

Are all the space Heaters in operating mechanism working?

Tightness of all the electrical terminals verified?

Is GAS leakage once again verified after timing and operation?


SF6 GAS PRESSURE AFTER COMPLETION OF JOB :
TIME AT WHICH THE FINAL PRESSURE NOTED
:

Operational counter readings as on DATE :

Are insulators, operating mechanism, pole beam thoroughly cleaned and free
from dust and dirt?
* If NO , clean it thoroughly with dry cloth , before charging.

Check carried out by :

If points 1-7 as set out above have been completed, the circuit-breaker
can be commissioned.

YES

NO

AM /

BAR
PM

1HYB800001-54 Rev. A
Page 13

Troubleshooting
Before any activity is started, the circuit breaker has to be isolated from the highvoltage system and earthed according to regulations. The control and heating
currents are to be interrupted.

6.1

SF 6 gas supply system


-

When the signal Replenishment of SF6 gas is given the gas pressure has to
be checked and insulating gas added. The correction can also be done while
the breaker is in service. If the density monitor responds inspite of nominal
pressure being present, the density monitor has to be checked.

If leaks are suspected in the SF6 system, proceed as follows :


-

SF6 gas lines :


Check all screwed and brazed joints with a leak detector. Replace faulty
brazings and fittings. Tighten leaking screwed connections.

Casing details (mechanism housing, flanges etc) :


In the case of minor leaks all sealing joints are to be checked with a leak
detector. In the case of major leaks, it is recommended that the leaks are
located using soapy water.

Crank Mechanism seals :


Leaking crankshaft seals must be replaced according to section 7.12.3.

6.2

Check SF 6 gas humidity (dew point).

Control Circuits
If a switching command is delayed, or executed only partially or not at all, proceed
as follows:
-

Switch off control and auxiliary current circuit.

Check the electrical terminals in the control circuits for tightness and proper
connection.

Compare wiring with wiring diagrams and correct if necessary.

Check coils of solenoid valve 10006, 10007 and if necessary change defective
coils. The cause of the overload has to be established and eliminated.

Switch on and check control voltage.

Switching or blocking occurs in the wrong pressure range.

Check the function of the circuit breaker when the density monitor is
disconnected. When it is confirmed that the density monitor is defective, it has
to be replaced.

1HYB800001-54 Rev. A
Page 14

7.

Inspection intervals
Important checkpoints, acceptable tolerances, certain functional values for
adjustments, and recommended inspection intervals can be found in the following
inspection chart.
In corrosive or polluted air and in climates with a high relative humidity, it can be
necessary to halve the inspection intervals.
The specified inspection intervals should be considered as recommended guide
values, which can be increased or decreased depending on local conditions.

1HYB800001-54 Rev. A
Page 15

7.1 Maintenance summary

Type of measure

Inspection interval

Ocular inspection

Preventive maintenance
Intermediate inspection
Operation testing including
time checks
Heat measurements

Explanation

1-2 years

Preventive maintenance
General inspection of the
circuit-breaker and
operating mechanism.

Overhaul
Overhaul of the breaker
chamber
Line breaker
Transformer breaker
Capacitor battery breaker
Reactor breaker
Filter breaker
Non-synchronised
Synchronised
Complete overhaul.

Condition of
circuitbreaker
during work

Competence
requirements

a1

a2

3-6 years, 2 000 mech.


oper.

1)

b1

b2

After 15 years or 5 000


mech. oper.

1), 3)

b1

b2

2)

c1

c2

nxI2=8 000
nxI2=8 000

2 000 el. oper.


4 000 el. oper.
after 30 years or
10 000 mech oper.

Explanation:
1)

Mech. oper. =Mechanical Close-Open operations.

2)

El. oper.= Close-Open operations with electrical load

3)

Special demands on resistance inspections for circuit-breakers operated


> 100 Close and Open operations/year.

1HYB800001-54 Rev. A
Page 16

Condition of the circuit-breaker during work :


a1)

Circuit-breaker in operation.

b1)

Closing spring untensioned, circuit-breaker open, disconnected and earthed.


Circuit-breaker poles removed and transported indoors.

c1)

Closing spring untensioned, circuit-breaker open, disconnected and earthed.


Poles/breaking unit dismantled and transported to the workshop.

d1)

Closing spring untensioned, circuit-breaker open, disconnected and earthed.


Complete circuit-breaker including operating mechanism transported to the
workshop.

Competence requirements :

a2)

Substation personnel with no special training.

b2)

Personnel authorised by ABB to carry out assembly, commissioning and


maintenance work.

c2)

Personnel authorised by ABB to carry out assembly, commissioning and


maintenance work. In certain cases, with instructions from ABB.

1HYB800001-54 Rev. A
Page 17

See Maintenance of the operating


mechanism

1HYB800001-54 Rev. A
Page 18

1HYB800001-54 Rev. A
Page 19

1HYB800001-54 Rev. A
Page 20

1HYB800001-54 Rev. A
Page 21

1HYB800001-54 Rev. A
Page 22

1HYB800001-54 Rev. A
Page 23

1HYB800001-54 Rev. A
Page 24

1HYB800001-54 Rev. A
Page 25

7.6

Table of parts to be serviced


Inspection / Maintenance
Part
No.

Part which
must be
Inspected/
replaced

see
section

Activity after*)
number of
switching
operations

7.11.1
7.11.1
7.11.1
7.11.1
7.11.1
7.11.1
7.11.3
7.12.1
7.12.1
7.11.3
7.11.3
7.11.1
7.12.2
7.12.2
7.12.2
7.12.2
7.12.2
7.12.2
7.12.2
7.11.3
7.12.2
7.12.3
7.12.3
7.12.3
7.12.3

replace
replace
replace
replace
replace
replace
replace
replace
replace
inspect
inspect
replace
replace
replace
replace
replace
replace
replace
replace
inspect
replace
replace
replace
replace
replace

Breaker pole type EDF


10036
10038/1
10038/2
10038/3
10038/4
10045
10047
10056
10059
10060
10061
10064
10065
10066
10067
10068
10072
10073
10074
10076
10077
10082
10090
10091
10182

Lockwasher
Sealing ring
Sealing ring
Sealing ring
Sealing ring
Alumina container
Lockwasher
Fixed contact pin
Finger, complete
Piston
Flow direction tube
Lockwasher
Contract ring
Insulating nozzle
Auxiliary nozzle
Erosion finger
Compression spring
Piston guide ring
Multi-contact ring
Cylinder
Cylinder guide ring
Sealing ring
Sealing ring
Sealing washer
Sealing ring

Spring stored-energy actuator FSA-1(F)


10006
10166
10167
10168

Coil OPEN
Motor brushes
Switching element
Switching element

inspect
inspect
inspect
inspect

*)

Number of switching operations according to Fig. 7/1 of these instructions.

Parts marked as can be replaced by piston assembly 1HYN400069R1,


which is the part of moving contact (part no. 10013, fig. 7/4)

Replace means :
As a general rule replace the part when the permissible number of switching
operations according to fig7/1 of these instructions has been reached.

Inspect means :
Inspect the part thoroughly for wear and replace if necessary. It is not
necessary to replace the part if at the endangered points it exhibits no or only
slight wear and if silver plating is not damaged.

1HYB800001-54 Rev. A
Page 26

7.7 Tools, jigs, fixtures and accessories


Besides tools for erection according to section 4.1.1 the following are required:
-

Circlip pliers C8 (straight)

Open end wrenches 10-43 mm

Set of hexagon sockets 5-10 mm ((connection 3/8") and special tools, jigs and
fixtures as per fig 7/2b.

7.8 Maintenance procedure


7.8.1 General
Maintenance includes inspection and overhaul according to that described in sections
7.1 to 7.5 of this Instruction. Maintenance work in general, and contact overhaul in
particular, shall be carried out in closed and as dust-free premises as possible.
In principle, all sealing units, spring washers and locking rings which are dismantled
during maintenance work shall be replaced by new such parts.

7.9 Preparation for overhaul


7.9.1 Taking the circuit-breaker out of service
-

Operate the circuit-breaker to position b1 (uncharged and position OPEN) (fig. 2/1).
Open the disconnectors on both sides of the circuit-breaker.
Switch off control, signal, motor, and heating voltages.

Earth the high-voltage cables on both sides of the circuit-breaker according to


local regulations and disconnect them from the circuit-breaker.
Disconnect control, signal, motor and heater circuits.
Reduce the SF6 gas pressure to pabs = 150 kPa (= 1.5 bar) before transport to
the assembly shop.

7.10 Removal of breaker poles


7.10.1 Dismantling SF, gas lines
Loosen the fastening bolts of the gas system so that it can be moved lengthwise.
Remove the cap nuts on the check valves so that the groove in its threads is
visible. Move the gas tube as far as possible to the side so that it comes against the
cap nut. In this position, all three check valves are closed and the cap nuts can be
completely loosened while moving the tube system further to the side.
7.10.2 Removal of breaker poles (10171) and mechanism housing
Remove outer poles:
-

Fasten lifting ropes under the upper flange of the breaker chamber insulator and
tension them slightly. Remove screw, washer and nut, 49621, 49063, 89026 (fig. 4/
1a:1,2).

Move out the breaker poles to the side. Thereby, the coupling shaft 10005 (fig. 4/
1:1,2) slides out of its coupling sleeve 10180. Transport the breaker poles to the
assembly shop and place them on an assembly block (supplied by the customer).

1HYB800001-54 Rev. A
Page 27

Dismantling middle pole:


-

Pull out the coupling shaft 10005.

Dismantle connecting rod f (fig. 4/la:1,2).

Fasten the lifting rope under the flange and tension it slightly. Remove screw,
washer and nut, 49621, 49063, 89026.

Lift the breaker pole upwards and transport it to the assembly shop.

7.11 Disassembly of breaker poles 10171 (fig. 7/2:1, :2, :3)


-

Clean the breaker poles on the outside.

Empty SF6 gas through a connected dust filter.

Observe meticulous cleanliness in all following work.

Parts from the various poles must not be interchanged. This is important since
parts in the arm and link systems are not identical.

7.11.1 Disassembly of breaker pole B1


The following description applies for pole B1, shown in fig. 7/2a:2. All poles are
disassembled in the same way.
-

Place the breaker pole on the assembly table. Fastening points are the post and
breaker chamber insulators upper flanges and the adapter plate 10098.

Remove screws 49756/2 and the washers 89026/1 and lift the cover 10056/1.
Then lift out the desiccant container. Treat this according to prevailing local
regulations.
Remove screw, nut and washers 49756, 49621/2, 89026/2, and carefully lift off the
flange 10099/2 with the fixed contact.
-

Place the flange on a sturdy base taking care of the O-ring groove.

Support the mechanism housing, included in the link gear 10185/2, with a suitable
wooden base. Unscrew and pull it out as far as possible.

Hold firmly the socket of the operating insulator 10042/2 with wrench SW28, loosen
the locking nuts 49695/1, 49586, and turn the set screw 10041/2, until the operating
insulator socket 10042/2 and the linkage joint 10043/2, are free. Take out the
mechanism housing completely. Remove O-rings 10038/3 and 10038/4.

Disassemble the screw joint which holds together the support and breaker
chamber insulator, with the intermediate connector flanges (49333, 49621, 89026/
2) Lift off the breaker chamber insulator 10106

Now lift off the moving contact and place it on a wooden base.

Remove the pin 10050 and operating insulator socket 10042/2 from the operating
insulator 10049.

Thread off the set screw in 10051 with its locking nut 49505 from adjusting ring
10053.

Knock out the flow direction tube base with dismantling rod and adapter 00104 (fig.
7/2b). Remove pin 10029.

1HYB800001-54 Rev. A
Page 28

Unscrew the post insulator from the adapter plate 10098.

Do not damage the sealing surfaces on the insulators and mechanism housing. Be
careful also with the O-ring grooves in the flanges.

7.11.2 Disassembly of fixed contact 10030 (fig. 7/3)


-

Remove screw 49756/2 with washer 89006/2 and separate the flange from the
contact holder.

Loosen hexagon screws 10057 from contact finger cage 10058. Lift off the finger
cage. Thereby, the fingers 10059 fall out.

Unscrew the fixed contact pin 10056 with socket wrench 00103.

As a general rule, change the fixed contact pin 10056, countersunk screws 10057,
and all contact fingers 10059 .

7.11.3 Disassembly of moving contact 10013 (fig. 7/4)


-

Remove screw 49332 and lift off the flange.

Carefully take out the moving middle part.

Clamp the piston 10060 in wooden jaws or prisms. Push flow direction tube base
10054 out of flow direction tube 10061 and unscrew the piston base 10062 with the
special torque wrench 00106 (fig. 7/2b).

Remove the socket head screw 49318 and lock washer 10064. Take out the
contact ring 10065 with nozzle 10066 and disassemble them.

Unscrew sleeve 10067.

Unscrew erosion finger 10068 with torque wrench socket 00102.

Remove the long screw 10069 from the cylinder base 10070, and pressure relief
flap 10071 with compression springs 10072.

Check the piston 10060, flow direction tube 10061 and cylinder 10076, with regard
to damage.

Replace all piston guide rings 10073, cylinder guide ring 10077, multi-contact rings
10074, compression springs 10072, insulating nozzle 10066, auxiliary nozzle
10067, erosion finger 10068, contact ring 10065 and spring washers 10064.

7.11.4 Cleaning
-

All parts shall be cleaned according to prevailing Maintenance and Storage


Instructions 1HYB800001-30.

7.12 Overhaul of component groups


7.12.1 Overhaul of fixed contact 10030 (fig. 7/3)
-

Treat the contact surfaces of the fixed contact pins with polishing cloth and grease
N, and the contact fingers with grease N but no polishing cloth.

Screw the fixed contact pin 10056 with hexagon wrench 00103 (fig. 7/2b) and
secure with locking fluid B (see 1HYB800001-29). Observe the tightening torque.

NOTE
Only the last two threads of the fixed contact holder 10097 are to be treated with
locking fluid. There must be no locking fluid on the contact surfaces, see fig. 7/3, 2*).

1HYB800001-54 Rev. A
Page 29

When changing contact fingers, proceed as follows:


Slide the finger cage 10058 over the fixed contact holder 10097 up to 15 mm
before the end position. Insert fingers 10059, including springs, and then push the
finger cage to the end position. Screw in the countersunk screws 10057 and
secure with locking fluid B. NOTE: Only on the last four threads. Observe the
tightening torque.

Screw the assembled contact 10030 to the connection flange and do not forget to
lubricate the contact surface at 3*) (fig. 7/3) with grease N.

7.12.2 Overhaul of moving contact 10013 (fig. 7/4)


NOTE
- Clamp the piston 10060 in wooden jaws or prisms.
-

Treat the fixed contact surfaces on erosion finger and piston with polishing cloth
and grease N, 2*.

Mount the erosion finger 10068 by special wrench 00102 (fig. 7/2b) and secure
with locking fluid B. Observe the tightening torque.
Apply fluid E on the thread on sleeve 10067. Mount by hand and secure with
locking fluid C.
Note
Only the last thread shall be treated with locking liquid (fig. 7/4, *).
Remember to remove the inside catch piece of the special wrench 00102.

Clean and grease the fixed contact surfaces between the contact ring 10065
and piston 10060 with grease N. Mount the contact ring, including insulating
nozzle 10066, screw and washer, 49318, 10064, on the piston. Observe the
tightening torque and locking.

Mount the piston base 10062 with torque wrench 00106 (fig. 7/2b) and secure with
locking fluid B
NOTE
Apply locking agent to the last two threads only.

Replace cylinder guide rind 10077 in the cylinder base 10070, piston guide rinds
10073, and multi-contact rings 10074 in the piston 10060. Observe, when doing so,
the direction of the multi-contact firings.

Clean and grease the moving contact surface on cylinder 10076 and the piston in
the area of the multi-contact rings with grease N, see 2*) (fig. 7/4).

Insert carefully the assembled middle part into cylinder 10076 and flow direction
tube 10061, in cylinder base 10070. Note that there shall be an angle of 90 between
the flow direction tube window and the cylinder base window. Thereby, the middle part
must not be turned, but if so happens only in the direction of the arrow.

Mount the long screws 10069, with pressure relief flap 10071 and compression
springs 10072. Secure with locking fluid B. Observe the tightening torque.

1HYB800001-54 Rev. A
Page 30

7.12.3.
-

Overhaul of link gear 10185/2 (fig. 4/1a:2, 7/5:2)

Remove screw and washer 49705 and 89025, or 49701 and 89154, with shaft
guard 10179 , and disassemble completely. Pull out the crankshaft 10083 and
lever 10084/2 with linkage joint 10085/2. Unscrew socket head screw 10086
with washers 10088 and 89004, and pull out the joint pin 10087.
Replace the following parts:
O-ring 10090.
X-ring10081
Sealing ring 10182

Clean the metal parts that are not changed. Reassemble in reverse order. Grease
X-rings 10081 with grease Sand sealing ring 10182, pack with grease G (Mobile
Grease 28). Be careful that the sealing rings are not damaged by the splines.
Apply grease G on joint pin 10087.
Observe the tightening torque.
NOTE
For the relative positions of the punch marks, see e in fig. 7/5:2. Apply
grease (fluor-silicone grease) S on the outer diameter c and assembly surface
a on shaft guard 10179 10179.

7.13

Assembly of breaker pole (fig. 7/2a)


Mounting the operating insulator 10049 on the moving contact:
-

Place the snap ring 10055 in the groove on the flow direction tube base 10054.

Push in the flow direction tube base 10054 and retaining ring 10055 so far into the
flow direction tube 10061 that the pin 10029 can be inserted.

Push in the ring 10053 over flow direction tube 10061.

Slide the operating insulator 10049 with screen 10095 over the flow direction tube.
Insert pin 10029 so that the bore in the bolt is in line with the centre-line of
the operating insulator. Insert the flow direction tube base 10054 through the
bore in pin 10029 until it reaches stop. Check that the rear blow-off hole is completely open.

Place the ring 10053 so that the set screw 10051 can be screwed into the bore in
the flow direction tube 10061. Insert set screw 10051, tighten lock nut 49505 and
secure with locking fluid B. Observe the tightening torque.

Assemble the operating insulator socket 10042 and pin 10050 on the operating
insulator. At this assembly the bore in the pin must be in line with the centre-line
of the operating insulator.

Assembly of the moving contact 10013 on the terminal flange 10108:


-

Clean the contact surface on the terminal flange. Rub the fixed contact surface on
the cylinder base with a polishing cloth. Apply grease N on the rubbed surfaces.
Mount with screw and washers, 49332, 10047 and 89006/1, and secure with
locking fluid B. Observe the tightening torque.

Apply grease N, Fomblin, on the marked moving contact surface of contact ring
10065 (fig. 7/4).

1HYB800001-54 Rev. A
Page 31

Apply grease S, fluor-silicone grease on 0-rings 10038/1 and 10038/2 and the
grooves for the terminal flanges 10108. Place the O-rings in the grooves.

Place the breaker chamber insulator on the flange and thereby try to locate the
moving contact as far as possible in the middle of the insulator.
Place the post insulator over the operating insulator and screw both the insulators
to the flange with screw, nut and washers, 49333, 49621 and 89026/3 (fig. 7/2a:2)

Apply grease S on the O-rings and the groove for these in the adapter plate, and
put the O-rings in the groove.

Screw the adapter plate against the flange on the post insulator with screw and
washer, 49726/1 and 89026/1.

Determination of the adjusting measurement A between the operating insulator


socket 10042 and linkage joint 10043 (fig. 7/2c:2):
-

Place the depth gauge 00109 on the flange 10016 of the breaker chamber
insulator. Push the operating insulator 10049 upwards to stop. Place the straight
edge 00114 on the lower insulator flange. Measure the X measurement.

Calculation formula for the measurement A: A = X + 32.5 mm (~ 45.5)

Set the measurement A on compass 00115.

Remove the depth gauge 00109 and straight edge 00114.

The setting values of the two remaining poles are measured in the same manner but
the calculation formula for the measurement A is:
for pole marked A1: X - 29 mm (~ 51.5 mm)
for pole marked C1: X - 14 mm (~ 66.5 mm)
At unearthed capacitor stack, the circuit-breaker consists of one pole marked A1(Fig.
7/2a:1), and two poles, marked B1 and C1 (7/2a:3). B1 and C1 have the same setting
value A.
For assembly of the complete fixed contact 10030, see fig. 7/2a:2.
-

Apply grease S in the 0-ring groove on the upper terminal flange 10099/2 and the
two O-rings, before placing them in the groove.

Now mount the contact 10030 with flange on the upper flange of the breaker
chamber insulator and try to place the contact as far as possible in the middle of
the insulator. Use screw, washers and nut, 49756, 49621/2 and 89026/2.Observe
tightening torque 79 Nm.

Install the desiccant container filled with desiccant (see fig. 7/2a:1,2,3).

Finally, treat the O-rings and groove on the upper connection flange with grease
S and mount the cover 10056/1 with screw and washer 49756/2 and 89026/2.
(MD = 45 Nm).

Assembly of link gear 10185/2 (fig. 7/2a:2):


-

Move the operating insulator 10049 to position OPEN.

Apply S grease in the O-ring groove of the adapter plate and on the O-rings.
Place the O-rings in their grooves.

1HYB800001-54 Rev. A
Page 32

Place the link gear 10185/2 at a distance of 50 mm in front of the lower flange on
the post insulator.

Place the adjusting screw 10041/2 (with only one tightening turn), with hexagon
nuts 49586 and 49695 fully backed off on their threads, on the operating insulator
socket 10042/2 and the linkage joint 10043/2.

Tighten the adjusting screw 10041/2 to the measurement A by means of pre-set


compass 00115, according to fig. 7/2c:2, and secure on both sides with locking
fluid B. Observe the tightening torque.

Apply grease S (fluor-silicone) on the sealing surfaces.

Mount the link gear 10185/2 with hexagon nuts 49621/2 and 89026/2 and secure
as above. Observe the tightening torque 79 Nm.

Filling gas :
After the circuit-breaker has been dismantled for overhaul or repair it shall (before
trial switching operation) be filled with SF6.
Evacuate down to the pressure 1 mbar and continue to pump at least one hour
after that pressure has been reached.
Stop evacuating and fill the circuit-breaker with dry and pure nitrogen gas to the
atmospheric pressure. Let it stand two hours at this pressure.
Evacuate again to 1 mbar and fill with pure SF6 gas to 0.15 MPa abs. Observe
thereby the safety regulations for gas filling.

7.14

Erection of breaker poles (fig. 4/1a,b)


-

Set the middle breaker pole at max. OPEN position, and place the actuating lever
10154 in correct position according to punch marking a (fig.4/ib). Lower the pole
on support frames 10161 and place the connecting rod joint head in the actuating
lever fork. The operating mechanism must be in position OPEN. Insert the
hexagon screws 49063. Fit nut 49621 with washer 89026 and tighten slightly so
that the pole can be turned easily. Apply grease G ( Mobile Grease 28 ) on joint
pin 10158. Mount the spring washer, spacer and hexagon screw, 10064, 89224 and
49215. Place coupling shaft 10005 in the coupling sleeve and actuating lever.
Apply grease G on the splines.

Set the outer poles in OPEN position and push them from the outside with
coupling sleeves as far as possible over the coupling shafts. Insert the hexagon
screws 49063, fit the nuts 49621 and spacers 89026, and then tighten after
adjusting the breaker poles into correct position. The joint heads on the connecting
rod must be moveable, and the coupling shafts must be moveable axially.

Apply grease G (Mobile Grease 28, see 1*), (fig. 4/lc), on the flange surfaces of
the gas nipples.
Clean the gas system by blowing SF6, gas via the. header block for approx. 3 min.
Allow the gas to continue to flow while the system is connected to the check
valves of the mechanism housing, according to fig. 4/1c. Screw on all cap
nuts up to the groove. Then tighten all cap nuts fully while moving the complete tube system to the side. Lock all fastening bolts. If the connections of the
gas system to the header block have been dismantled, they shall be secured
with locking fluid B when re-installed. Observe the tightening torque 45 Nm.
Fill with pure gas to normal working pressure 0.7 MPa abs. After conclusion of
gas treatment, fit the nut and , O-ring L10112/c.

1HYB800001-54 Rev. A
Page 33

7.15 Overhaul of spring operating mechanism 10173 (fig.7/6)

8.

Clean the transfer roller A shaft, worm wheel G, and worm screw H, and apply
grease on the machined surfaces without dismantling.

Clean and grease sparingly the transfer cam disc B, latches C and D, levers
E and F. Use grease G.

After 5000 switching cycles, the spring operating mechanism shall be overhauled.
Contact ABB.

Spare parts
8.1

General
8.1.1 Important notes
-

Replace all uncovered sealing rings of the insulating gas space.

Unpacking : shortly before use.

8.1.2 Ordering of spare parts


For ordering, the following data are essential :
-

8.2

Order no 1.........
Type designation
Serial number
Publication number
Part number
Part designation

See order documentation


See nameplate
See nameplate
See end paper
See spare parts list
See spare parts list

Spare parts
8.2.1 Set of contacts for 1 breaking unit
Comp. No.

Art No.

Name of Item

Fig.

Number

10056
10059
10065
10066
10067
10068
10074
10073
10077
10045

HATH408148R1
HATH401095R1
HATH306969P3
HATH307413P1
HATH407749P1
HATH307654R1
HAGS301276P24
HATH408678P1
HATH408677P1
HAMT401304R1

Fixed contact pin


Finger Compl.
Contact Ring
Insulating Nozzle
Auxiliary Nozzle
Erosion finger
Multi-contact Ring
Piston guide Ring
Cylinder guide Ring
Desiccant Cont.

7.3
7/3
7/4
7/4
7/4
7/4
7/4
7/4
7/4
7/2a

1
27
1
1
1
1
1
2
1
1

8.2.2

Gaskets, springs, fasteners for 1 breaker pole.

Comp. No.

Art No.

Name of Item

Fig.

Number

10038/2
10038/3
10038/1
10047
10057
10064
10072

1HML400410P170
1HML400063P145
1HML400410P610
MT430575P14
STD430017P2205
1HYN400575P1
HATH407739P2

O-ring
O-ring
O-ring
Disc Spring
Countersunk screw
Disc Spring
Compression Spring

7/2a
7/2a
7/2a
7/2a
7/3
7/4
7/4

5
1
6
16
2
12
3

1HYB800001-54 Rev. A
Page 34

8.2.3

Complete set of gaskets for gas supervision

Comp. No.

Art No.

Name of Item

Fig.

Number

L 00110/a

1HML400063P20

O-ring

4/1c

10

L 10112/c

1HML400063P28

O-ring

4/1c

L 10118

1HML400063P40

O-ring

4/1c

12

L 00110/b

1HML400063P16

O-ring

4/1c

L 10112/b

SWT431154P1

Gasket

4/1c

8.2.4

Set of gaskets for 1 crank mechanism

Comp. No.

Art No.

Name of Item

Fig.

Number

10081

1HYN400061P1

X-ring

7/5

10090

AG434301P52

O-ring

7/5

10091

1HML400063P25

O-ring

7/5

10182

HAMT400593P6

Sealing ring

7/5

8.2.5

Spare parts for spring operated mechanism FSA -11

Comp. No.

Art No.

Name of Item

Fig.

Number

10166

--

Motor brushes motor

7/6

10168

HAGT444559P2

Limit switch

7/6

10168

HAGT444559P5

Limit switchT

7/6

10066

Close / Tripping

as per table given below

10020

Motor

as per table given below

1HYB800001-54 Rev. A
Page 35

8.2.6

Tools for EDF SK

8.2.7
Gas Equipment
Gas filling equipment
Gas filling and evacuation equipment
Gas leak detector

1HYN300349R3
1HYN300189R1
LS790A

1HYB800001-54 Rev. A
Page 36

8.2.8

Safety Disc Unit

Item No.

Qty.

Name of Item

Article No.

Safety Disk Unit

1HYN400578P1

O-ring

1HML400063P75

O-ring

1HML400063P90

1HYB800001-54 Rev. A
Page 37

11. Appendix
11.1 Figures
Fig.

Designation

1/1
1/2
2/1
3/1a:1,2,3
3/1b:1,2,3
3/2
4/1a:1,2
4/1b
4/1c
4/1d
4/2
5/1
5/2a
5/2b
7/1
7/2a:1,2,3
7/2b
7/2c:1,2,3
7/3
7/4
7/5:1,2,3
7/6

Nameplate
Tabulated masses
Circuit breaker
Breaker Pole (OPEN Position)
Breaker Pole (CLOSED position)
Schematic control diagram
Circuit breaker, complete
Connecting rod securement
SF6 gas line
Gas filling with SF6
Transport instructions
SF6 filling pressure diagram
Measurement layout for function tests
Simultaneity monitoring
Admissible switching cycles for contact overhaul
Breaker pole, complete
Tools and overhaul tools
Length adjustment of moving contact
Fixed contact
Moving contact
Link Gear
Spring stored-energy actuator

1HYB800001-54 Rev. A
Page 38

Fig. 1/1

1HYB800001-54 Rev. A
Page 39

Type

Designation

EDF
Mass per citruit breaker (net)
kg (approx.)

lb (approx.)

Operating mechanism incl. control

160

396

Breaker poles, pole supports


with actuator transmission

475

1045

Total mass including


Supports

815

1793

Supports

180

352
Mass

Breaker pole, complete

per pole

kg

lb

125

275

Fig. 1/2

1HYB800001-54 Rev. A
Page 40

Legend to Fig. 2/1


10112

Density monitor

10126

Density monitor cable, compl.

10170

Circuit breaker, type EDF

10171

Breaker pole

10172

Support frame

10173

Control cubicle with stored-energy spring operating mechanism and connecting rod

10174

Support

Position indicator CLOSED-OPEN

b1

Breaker position OPEN and springs untensioned (not ready for switching)

b2

Breaker position OPEN and springs tensioned (ready for CO switching)

b3

Breaker position CLOSED and springs tensioned (ready for O-CO Switching)

Earthing connection

Fig. 2/1

1HYB800001-54 Rev. A
Page 42

Legend to Fig. 3/1a,b:1


10013

Moving contact

10017

Cover

10030

Fixed contact

10041/1

Adjusting screw

10049

Operating insulator

10098

Adapter plate

10099

Upper terminal flange

10106

Insulator for breaking chamber

10108

Lower terminal flange

10171

Breaker pole

10185/1

Link gear

g-h

Arcing contact

k-l

Main current contact

Circuit breaker in OPEN position

Circuit breaker in CLOSED position

10017
10099

10106

10030
10165

k-l

g-h

10013

C
10108

10171

10049
10157

10041/1
10098
10185/1

Fig. 3/1a:1

Fig. 3/1b:1

Fig. 3/1 a,b:1

1HYB800001-54 Rev. A
Page 44

Legend to Fig. 3/1a,b:2


10013

Moving contact

10017

Cover

10030

Fixed contact

10041/2

Adjusting screw

10049

Operating insulator

10098

Adapter plate

10099

Upper terminal flange

10106

Insulator for breaking chamber

10108

Lower terminal flange

10171

Breaker pole

10185/2

Link gear

g-h

Arcing contact

k-l

Main current contact

Circuit breaker in OPEN position

Circuit breaker in CLOSED position

10017
10099

10106

10030
10165

k-l
g-h
10013

C
10108

10171

10049
10157

10041/2
10098

10185/2

Fig. 3/1a:2

Fig. 3/1b:2

Fig. 3/1 a,b:2

1HYB800001-54 Rev. A
Page 46

Legend to Fig. 3/1a,b:3


10013

Moving contact

10017

Cover

10030

Fixed contact

10041/3

Adjusting screw

10049

Operating insulator

10098

Adapter plate

10099

Upper terminal flange

10106

Insulator for breaking chamber

10108

Lower terminal flange

10171

Breaker pole

10185/3

Link gear

g-h

Arcing contact

k-l

Main current contact

Circuit breaker in OPEN position

Circuit breaker in CLOSED position

10017
10099

10106

10030
10165

k-l
g-h
10013

C
10108

10171

10049
10157

10041/3

10098

10185/3

Fig. 3/1a:3

Fig. 3/1b:3

Fig. 3/1 a,b:3

1HYB800001-54 Rev. A
Page 48

Legend to Fig. 3/2


10006

Opening coil OPEN

10007

Closing coil CLOSE

10008

Auxiliary switch (S1)

10009

Auxiliary switch (K1 or K2)

10018

Motor limit switch (S3)

10019

Motor operated spring closing mech.

10020

Spring tensioning motor

10112

Density monitor (F2)

10171

Breaker pole

F3

Miniature circuit breaker

F12

Selector switch

S13

Control switch CLOSE-OPEN

1)

Remote control

10171

10171

10171

S13

Fig. 3/2

1HYB800001-54 Rev. A
Page 50

Legend to Fig. 4/1a:1


Coupling Shaft
Density monitor
Header block
Density monitor cable compl.
Actuating Lever
Support frame
Operating mechanism
Support
Coupling Shaft
SF6 gas pipe
SF6 gas pipe
Shaft guard
Coupling Sleeve
Sealing ring
Cover
Hex screw M12x45 mm
Hex screw M16x50 mm
Hex nut M12x0.8D
Hex nut M16x0.8D
Socket head screw M10x20 mm
Socket head screw M10x40 mm
Washer
Washer
Washer
Washer
High-Voltage terminal:
Per screw fastener at least
1 washer13/28x3 and
1 Lock washer 13.5/28x1.6
on each side of the fastener
Coupling, coupling sleeves
Coupling shaft and guard
Connecting rod (component of sping
operated mechanism)
Fasteners
Fasteners
Torque

10005
10112
10118
10126
10154
10161
10173
10174
10176
L10177
L10178
10179
10180
10182
10183
49063
49069
49621
49622
49701
49705
89025
89026
89027
89154
D

E
F
f
g
h
MD

Nm ft. lbf
13
45
79
190

10
33
58
141

*) Rotation by 1800

h
MD=190Nm

10126

10173

10005
10112

L10178

10154

10118

C1

B1

A1

L10177/a

Fig 7/2a:3

Fig 7/2a:2

Fig 7/2a:1

49069
49622
89027

10174

L10177/b

10161

49063
49621
89026
MD=79Nm

Installation of breaker poles with grounded capacitor bank

MD=79Nm

10182

OPE

101

Fig. 4/1a:1

A-A

49701
89154
10183

10180

10179

10176

49705
89025
MD=38 Nm

A1, B1 and C1 are markings of


respective pole mechanisms

1HYB800001-54 Rev. A
Page 52

Legend to Fig. 4/1a:2


10005

Coupling Shaft

10112

Density monitor

10118

Header block

10126

Density monitor cable compl.

10154

Actuating Lever

10161

Support frame

10173

Operating mechanism

10174

Support

10176

Coupling Shaft

L10177

SF6 gas pipe

L10178

SF6 gas pipe

10179

Shaft guard

10180

Coupling Sleeve

10182

Sealing ring

10183

Cover

49063

Hex screw M12x45 mm

49069

Hex screw M16x50 mm

49621

Hex nut M12x0.8D

49622

Hex nut M16x0.8D

49701

Socket head screw M10x20 mm

49705

Socket head screw M10x40 mm

89025

Washer

89026

Washer

89027

Washer

89154

Washer

High-Voltage terminal:
Per screw fasterner at least
1 washer13/28x3 and
1 Lock washer 13.5/28x1.6
on each side of the fastener

Coupling, coupling sleeves

Coupling shaft and guard

Connecting rod (component of sping


operated mechanism)

Fasteners

Fasteners

MD

Torque

Nm ft. lbf
13
45
79
190

10
33
58
141

*) Rotation by 1800

h
MD=190Nm

L10177/a
E

10126

10173

10118

10005
10112

L10178

10154

C1

B1

A1

Fig 7/2a:3

Fig 7/2a:3

Fig 7/2a:1

10174

49069
49622
89027

L10177/b

10161

49063
49621
89026
MD=79Nm

Installation of breaker poles with ungrounded capacitor bank

D
MD=79Nm

49701
89154
10183

A-A

10182

Fig. 4/1a:2

10180

10179

10176

49705
89025
MD=38 Nm

A1, B1 and C1 are markings


respective pole mechanisms

1HYB800001-54 Rev. A
Page 54

Legend to Fig. 4/1b


10064

Lockwasher

10083

Crankshaft

10154

Actuating lever compl.

10158

Joint pin

49215

Hex screw M 6 x 10 mm

89224

Washer

Location of punch marks

Installation location

Rubber collar *)

Clamp *)

Connecting rod, compl. *)

Punch mark unimportant for type EDF

h,k

Locknuts

Operating mechanism component

MD

Torque

Nm ft. lbf
6

c=360

Fig. 4/1b

1HYB800001-54 Rev. A
Page 56

Legend to Fig. 4/1c


L 00110/a

O-ring 15.3 x 2.4

L 00110/b

O-ring 12.3x2.4

L 10177/a

SF6 gas pipe

L 10177/b

SF6 gas pipe

L 10178

SF6 gas pipe

L 10164

Non-return valve

L 00111

Washer

L 10118

Header block

L 10112/a

Density monitor

L 10112/b

Manometer *)

L 10112/c

Hex. nut and sealing ring

*)

At request of customer

1 *)

To be greased with greases G,


Mobil Grease 28

Fig. 4/1c

1HYB800001-54 Rev. A
Page 58

Legend to Fig. 4/1d


1

SF6 Gas cylinder

Coupling

Regulator

Coupling

Gas Valve

Density Switch

Gas Valve

Pressure Gauge

Fig. 4/1d

1HYB800001-54 Rev. A
Page 60

Legend to Fig. 4/2


10186

Pole support with poles

Supporting timber

Fig. 4/2

1HYB800001-54 Rev. A
Page 62

Legend to Fig. 5/1


1

Nominal filling pressure curve

Replenishment pressure curve (signal Replenish SF6 gas)

Blocking pressure curve (Signal OPEN operation blocked)

Filling of SF6 gas at mixed gas filling

Conversion of pressure units


100 kPa = 14.5 lbf/in2 = 1 bar
Conversion of :
Pabs (kPa) to Pe (gauge) lbf/in2
Pabs - 100 x 0.145 (kPa) = Pe (gauge) lbf/in2
Example : Rated filling pressure 1 at 200C (=680F) according to
table = 700 kPa (700-100) x 0.145 = 87 (gauge) lbf / in2

ibf/in2

kPa

bar
Pabs

Pabs

1000
9

130.5

900

116

800

101.5

700

87

600

72.5

500

58

400

43.5

300

29.0

200

1
2
3

100
0
-30 -20

-5

10

20

30

40

50

60

70

80

t0C

Pabs
kPa

-30

500

-20

-5

10

20

30

40

50

60

70

80

580

625

640

670

700

730

760

790

820

850

880

490

520

555

570

590

620

650

670

700

730

750

770

470

500

540

550

580

600

630

650

680

700

720

750

290

300

330

340

350

360

370

380

400

420

430

440

30

40

50

60

70

80

t0C

Pabs
bar

-30

5.0

-20

-5

10

20

5.8

6.2

6.4

6.7

7.0

7.3

7.6

7.9

8.2

8.5

8.8

4.9

5.2

5.6

5.7

5.9

6.2

6.5

6.7

7.0

7.3

7.5

7.7

4.7

5.0

5.4

5.5

5.8

6.0

6.3

6.5

6.8

7.0

7.2

7.5

2.9

3.0

3.3

3.4

3.5

3.6

3.7

3.8

4.0

4.2

4.3

4.4

Pabs
lbf/in2 -30/-22 -20/-4

t0C / F
-5/23

0/32

10/50

20/68

30/86

40/104 50/122 60/140 70/158 80/176

72.5

84.1

90.7

92.3

97.2

101.5

105.9

110.2

114.5

118.9

123.3

127.6

71.1

75.4

80.5

82.7

85.6

89.9

94.3

97.2

101.5

105.9

108.8

111.2

68.2

72.5

78.4

79.3

84.1

87.0

91.4

94.3

98.6

101.5

104.4

108.8

42.1

43.5

47.9

49.3

50.8

52.2

53.7

55.1

58.0

60.9

62.4

63.8

Fig. 5/1

1HYB800001-54 Rev. A
Page 64

Legend to Fig. 5/2a,b


Fig. 5/2a

Measurement layout for function tests

10171

Breaker pole

Y2, Y3

Coils OPEN

Y1

Coil CLOSE

Auxiliary switch

Terminal 1 in control cubicle

Terminal 2 in control cubicle

Terminal 3 in control cubicle

Terminal 4 in control cubicle

Terminal 5 in control cubicle

Terminal 6 in control cubicle

A,B,C

Pole coluomn

M1

Time recorder

M2

Main switch of test gear

M3

Control switch of test gear

K1

Terminal 1 on M3

K2

Terminal 2 on M3

UM

Measurement voltage

US

Control Voltage

CLOSED

OPEN

Fig. 5/2b

Time diagram of CLOSE-OPEN operation

A,B,C

Pole column

Coil current

t1

Closing time

Dt 1

Closing tolerance of the pole column

t2

Opening time

Dt 2

Opening tolerance of the pole column

t3

Close-open time

Fig. 5/2b

Fig. 5/2a,b

1HYB800001-54 Rev. A
Page 66

Legend to Fig. 7/1


I

Breaking current

Number of switching operations

Fig. 7/1

1HYB800001-54 Rev. A
Page 68

10056/1
10013
10099/2
10029
10030
10038/1
10038/2
10038/3
10038/4
10041/1
10042/1
10043/1
10045
10047
10049
10050
10051
10053
10054
10055
10061
10095
10106
10108
10171
10172
10098
10185/1
49017
49332
49333
49505
49586
49621/2
49695/1
89006/1
49726/2
49756/2
89026/2
49756
49333
49726/1
89006/2
MD
Nm ft. lbf
6
4
20
15
45
33
79
58

Legend to Fig. 7/2a:1


Cover
Moving contact
Upper terminal flange
Pin
Fixed contact, compl.
O-ring
O-ring
O-ring
O-ring
Adjusting screw
Operating socket insulator
Linkage joint
Desiccant container
Lock washer
Operating insulator
Pin
Set screw
Adjusting ring
Flow direction tube base
Retaining ring
Flow direction tube
Screen
Insulator for breaking chamber
Lower terminal flange
Breaking pole
Support frames
Adapter plate
Link gear
Socket screw M 6 x 20 mm
Socket screw M 10 x 50 mm
Hex screw M 12 x 70 mm
Hex nut M 8x0.5D
Hex nut M 16x0.5D
Hex nut M 12 x 0.8 D
Hex nut M 16 x 0.8 D
Washer M 12 x 40 mm
Hex screw M 12 x 50 mm
Hex head bolt M 10 x 30 mm
Washer
Hex Head bolt M 12x60
Hex Head bolt M 12x70
Hex Head bolt M 12x45
Washer 10.5x20x2
Torque

10056/1
49756/2
89006/2
10099/2

10038/1
10038/2
49756
89026/2

10016

49621/2

10045
10030
10106

10013

10171

10054
10061
10055
10038/1
10038/2
49333
89026/2
49621
M D =79Nm
89006/1
10047
49332
MD =40Nm

10108
10053
10051
49505
10029
10095
10049

10050
10042/1
49695/1
10041/1
49586
10098
49726/2
89026/2
10043/1

10038/1
10038/2
49726/1
89026/2
10038/4
10038/3
49621/2
89026/2

10185/1

10172

Fig. 7/2a:1

1HYB800001-54 Rev. A
Page 70

10056/1
10013
10099/2
10029
10030
10038/1
10038/2
10038/3
10038/4
10041/2
10042/2
10043/2
10045
10047
10049
10050
10051
10053
10054
10055
10061
10095
10106
10108
10171
10172
10098
10185/2
49017
49332
49333
49505
49586
49621/2
49695/1
89006/1
49726/2
49756/2
89026/2
49756
49333
49726/1
89006/2
MD
Nm ft. lbf
6
4
20
15
45
33
79
58

Legend to Fig. 7/2a:2


Cover
Moving contact
Upper terminal flange
Pin
Fixed contact, compl.
O-ring
O-ring
O-ring
O-ring
Adjusting screw
Operating socket insulator
Linkage joint
Desiccant container
Lock washer
Operating insulator
Pin
Set screw
Adjusting ring
Flow direction tube base
Retaining ring
Flow direction tube
Screen
Insulator for breaking chamber
Lower terminal flange
Breaking pole
Support frames
Adapter plate
Link gear
Socket screw M 6 x 20 mm
Socket screw M 10 x 50 mm
Hex screw M 12 x 70 mm
Hex nut M 8x0.5D
Hex nut M 16x0.5D
Hex nut M 12 x 0.8 D
Hex nut M 16 x 0.8 D
Washer M 12 x 40 mm
Hex screw M 12 x 50 mm
Hex head bolt M 10 x 30 mm
Washer
Hex Head bolt M 12x60
Hex Head bolt M 12x70
Hex Head bolt M 12x45
Washer 10.5x20x2
Torque

10056/1
49756/2
89006/2
10099/2
10016

10038/1
10038/2
49756
89026/2
49621/2

10045
10030
10106

10013

10171

10054
10061
10055
10038/1
10038/2
49333
89026/2
49621
M D =79Nm
89006/1
10047
49332
MD=40Nm

10108
10053
10051
49505
10029
10095
10049

10050
10042/2
49695/1
10041/2
49586
10098
49726/2
89026/2
10043/2

10038/1
10038/2
49726/1
89026/2
10038/4
10038/3
49621/2
89026/2

10185/2

10172

Fig. 7/2a:2

1HYB800001-54 Rev. A
Page 72

10056/1
10013
10099/2
10029
10030
10038/1
10038/2
10038/3
10038/4
10041/3
10042/3
10043/3
10045
10047
10049
10050
10051
10053
10054
10055
10061
10095
10106
10108
10171
10172
10098
10185/3
49017
49332
49333
49505
49586
49621/2
49695/1
89006/1
49726/2
49756/2
89026/2
49756
49333
49726/1
89006/2
MD
Nm ft. lbf
6
4
20
15
45
33
79
58

Legend to Fig. 7/2a:3


Cover
Moving contact
Upper terminal flange
Pin
Fixed contact, compl.
O-ring
O-ring
O-ring
O-ring
Adjusting screw
Operating socket insulator
Linkage joint
Desiccant container
Lock washer
Operating insulator
Pin
Set screw
Adjusting ring
Flow direction tube base
Retaining ring
Flow direction tube
Screen
Insulator for breaking chamber
Lower terminal flange
Breaking pole
Support frames
Adapter plate
Link gear
Socket screw M 6 x 20 mm
Socket screw M 10 x 50 mm
Hex screw M 12 x 70 mm
Hex nut M 8x0.5D
Hex nut M 16x0.5D
Hex nut M 12 x 0.8 D
Hex nut M 16 x 0.8 D
Washer M 12 x 40 mm
Hex screw M 12 x 50 mm
Hex head bolt M 10 x 30 mm
Washer
Hex Head bolt M 12x60
Hex Head bolt M 12x70
Hex Head bolt M 12x45
Washer 10.5x20x2
Torque

10056/1
49756/2
89006/2
10099/2
10016

10038/1
10038/2
49756
89026/2
49621/2

10045
10030
10106

10013

10054

10171
10038/1
10038/2
49333
89026/2
49621
MD=79Nm
89006/1
10047
49332
MD=40Nm

10061
10055
10108
10053
10051
49505
10029
10095
10049

10050
10042/3
49695/1
10041/3
49586
10098
49726/2
89026/2
10043/3

10038/1
10038/2
49726/1
89026/2
10038/4
10038/3
49621/2
89026/2

10185/3

10172

Fig. 7/2a:3

1HYB800001-54 Rev. A
Page 74

Legend to Fig. 7/2b


00100

Guide pin

00102

Special Wrench

00103

Socket Wrench

00104

Disassembly Rod with adapter

00105

Set of Wrenches

00106

Special torque Wrench

00107

Measuring kit

00109

Depth Gauge

00114

Straight edge

00115

Compass

00117

Torque wrench

Fig. 7/2b

1HYB800001-54 Rev. A
Page 76

Legend to Fig. 7/2c:1


00109

Depth gauge

00114

Straight edge

10016

Upper flange

10049

Actuating rod

10185/1

Link gear

49621

Hex nut M12x0.8D

49756

Socket head screw M12x70 mm

89026/2

Washer

89026/3

Washer

Setting dimension x-29 mm=A (~51.5) for compass 00115 (Fig. 7/2b)

Upper Limit stop

Actual dimension from actuating rod to outer edge of straightedge

mm
50

in
1.97

Fig. 7/2c:1

00109

49756
89026/2/3
49621

10042/1

10016

10043/1

10049
X

10185/1

001

1HYB800001-54 Rev. A
Page 78

Legend to Fig. 7/2c:2


00109

Depth gauge

00114

Straight edge

10016

Upper flange

10049

Actuating rod

10185/2

Link gear

49621

Hex nut M12x0.8D

49756

Socket head screw M12x70 mm

89026/2

Washer

89026/3

Washer

Setting dimension x+32.5 mm=A (~45.5) for compass 00115 (Fig. 7/2b)

Upper Limit stop

Actual dimension from actuating rod to outer edge of straightedge

mm
50

in
1.97

Fig. 7/2c:2

00109

49756
89026/2/3
49621

10042/2

10016

10043/2

10049

10185/2

1HYB800001-54 Rev. A
Page 80

Legend to Fig. 7/2c:3


00109

Depth gauge

00114

Straight edge

10016

Upper flange

10049

Actuating rod

10185/3

Link gear

49621

Hex nut M12x0.8D

49756

Socket head screw M12x70 mm

89026/2

Washer

89026/3

Washer

Setting dimension x-14 mm=A (~66.5) for compass 00115 (Fig. 7/2b)

Upper Limit stop

Actual dimension from actuating rod to outer edge of straightedge

mm
50

in
1.97

Fig. 7/2c:3

00109

49756
89026/2/3
49621

10042/3

10016

10043/3

10049

10185/3

1HYB800001-54 Rev. A
Page 82

Legend to Fig. 7/3


10099/2

Upper terminal flange

49756/2

Hex head bolt

89006/2

Washer

10030

Fixed contact

10056

Fixed contact pin

10057

Countersunk screw M 6 x 16 mm

10058

Finger cage

10059

Finger complete

10097

Fixed contact support

10188

Finger spacing

MD

Torque

*)

Thread turns (2 turns) to be treated with locking agent

2*)

Contact sufrace which must remian free of locking agent

3*)

Contact surfaces, greased with grease N

Nm ft. lbf
6
26
49

4
19
36

10099/2

10097

10059

Fig. 7/3

1HYB800001-54 Rev. A
Page 84

Legend to Fig. 7/4


10108

Lower terminal flange

49332

Socket screw, M10x40

10047

Disk spring

89006/1

Washer

10013

Moving contact

10060

Piston

10061

Flow direction tube

10062

Piston base

10064

Lock washer

10065

Contact ring

10066

Insulating nozzle

10067

Auxiliary nozzle

10068

Erosion finger

10069

Long screw

10070

Cylinder base

10071

Pressure relief flap

10072

Compression spring

10073

Piston guide ring

10074

Multi-contact ring

10076

Cylinder

10077

Cylinder guide ring

49318

Socket head screw M6x25 mm

MD

Torque

Inside thread (2 turns) to be treated with locking agent

2 *)

Contact surface which must remain free of locking agent

3 *)

Contact surface, greased with grease N

Note ! Observe carefully that the direction of rotation given in the figure is kept. If it is not
followed, the lamella of the multi-contact will be destroyed.

Nm ft. lbf
6
11
79

4
8
58

Fig. 7/4

1HYB800001-54 Rev. A
Page 86

Legend to Fig. 7/5:1


00112

Non-return valve

10080

Ball bearing

10081

X-ring

10083

Crankshaft

10084/1

Lever

10085/1

Linkage joint

10086

Socket head screw

10087

Joint pin

10088

Washer

10090

Sealing ring

10091

Sealing ring

10092

Gas connection

10182

Sealing ring

10183

Cover

10185

Link gear

49701

Socket head screw M10x20 mm

49705

Socket head screw M10x40 mm

89004

Washer

89025

Washer

89154

Washer

MD

Torque

a....e

See section 7.7.3

Nm ft. lbf
6
45
110

4
33
81

10183

89154
49701

10182

10080

10083

Fig. 7/5:1

10090

10081

10091

10185

10092

49705
89025
MD=45Nm

00112

1HYB800001-54 Rev. A
Page 88

Legend to Fig. 7/5:2


00112

Non-return valve

10080

Ball bearing

10081

X-ring

10083

Crankshaft

10084/2

Lever

10085/2

Linkage joint

10086

Socket head screw

10087

Joint pin

10088

Washer

10090

Sealing ring

10091

Sealing ring

10092

Gas connection

10182

Sealing ring

10183

Cover

10185

Link gear

49701

Socket head screw M10x20 mm

49705

Socket head screw M10x40 mm

89004

Washer

89025

Washer

89154

Washer

MD

Torque

a....e

See section 7.7.3

Nm ft. lbf
6
45
110

4
33
81

10083

Fig. 7/5:2

89154
49701

10182

10080

10183

10090

10081

10091

10092

10185
49705
89025
MD=45Nm

00112

1HYB800001-54 Rev. A
Page 90

Legend to Fig. 7/5:3


00112

Non-return valve

10080

Ball bearing

10081

X-ring

10083

Crankshaft

10084/3

Lever

10085/3

Linkage joint

10086

Socket head screw

10087

Joint pin

10088

Washer

10090

Sealing ring

10091

Sealing ring

10092

Gas connection

10182

Sealing ring

10183

Cover

10185

Link gear

49701

Socket head screw M10x20 mm

49705

Socket head screw M10x40 mm

89004

Washer

89025

Washer

89154

Washer

MD

Torque

a....e

See section 7.7.3

Nm ft. lbf
6
45
110

4
33
81

89154
49701

10182

10183

10080

10083

Fig. 7/5:3

10090

10081

10091

10092

10185
49705
89025
MD=45Nm

00112

1HYB800001-54 Rev. A
Page 92

Legend to Fig. 7/6


10006

Coil CLOSE, OPEN (Y1,2,3)

10020

Spring tensioning motor

10144

Hand crank

10166

Motor brushes

10167

Switching element (S1)

10168

Switching element (S3)

Transmission roller

Transmission cam

Locking pawl

Locking pawl

Level

Lever

Worm wheel

Worm
Possible breaker positions according to Fig. 2/1a...c

Lubricating points of spring retaining pin

10144

Fig. 7/6

1HYB800001-38 Rev. A

Operating mechanism type FSA 1

Instructions for Operation


and Maintenance

Contents :

1.

General

2.

Construction

3.

Function

4.

Erection

5.

Commissioning

6.

Maintenance

7.

Spare Parts

8.

Appendix

1HYB800001-38 Rev. A
Page 1

Contents

Page

1.
1.1
1.2
1.3

GENERAL
Validity
Specification
Masses

1
1
1
1

2.
2.1
2.2
2.3
2.4

CONSTRUCTION
Operating mechanism cubicle
Drive mechanics
Driving units
Electrical components

1
1
1
2
3

3.
3.1
3.2
3.3
3.4

FUNCTION
Functions of the basic mechanism
Charging the closing spring
Closing - operation
Opening - operation

3
3
3
4
5

4.
4.1
4.2

ERECTION
Delivery
Installation

5
5
5

5.
5.1
5.1.1
5.1.2

COMMISSIONING
Function tests
Manual operation
Motor operation

5
5
5
5

6
6.1

MAINTENANCE (Overhaul)
Duty-related overhaul

6
6

7
7.1
7.2

SPARE PARTS
Storage instructions
Spare parts list

7
7
7

8
8.1

APPENDIX
Figures

8
8

1HYB800001-38 Rev. A
Page 2

1.

General
1.1

Validity
This operating instruction applies for stored-energy spring operating mechanisms to
SF 6 circuit-breakers of type EDF
- Operating mechanism type FSA 1 (outdoor)

1.2

Specifications
Specifications are contained in the order documentation and on the rating plate.

1.3

Masses
The masses (kg/lb) can be obtained from the order documentation and the shipping
documents. For internal transport and assembly see the instructions for erection and
operation of the circuit breaker, Fig. 1/2

2.

Construction
The stored-energy spring operating mechanism comprises the following main parts :

2.1

Operating mechanism cubicle compl.

Basic mechanism

Driving unit

Electrical components

Operating mechanism cubicle (Fig. 2/1)


In the operating mechanism FSA 1 (outdoor), the electrical components and the
basic mechanism are placed in the operating mechanism cubicle EV 11851.
There is a door with an inspection window for reading the position indicator
EV11825 and the spring charge indicator EV11824 on the operating mechanism
front. The door can be locked with a padlock. When the door is opened, the
electrical panel with its electrical components becomes accessible and the hand
crank can be inserted.
The operating mechanism cubicle is designed so that the basic mechanism and the
electrical components are hermetically protected against the effects of the weather.
The outdoor circuit breaker type EDF has the cubicle mounted below the pole
beams of the breaker. The connecting rod projects upwards.

1HYB800001-38 Rev. A
Page 3

2.2

Drive mechanics (Fig. 2/1, 7/1)


The basic mechanism EV 11852 is assembled in a chassis EV 11855 in which the
shaft bearings, the spring suspension points and the switchgear panel are fastened.
Their
-

2.3

major parts are :


Main shaft EV 11815
Output shaft EV 11816
Motor EV 11843 with reducer gear EV 11842
Worm gear EV 11819
Closing spring EV 11813
Opening spring EV 11814
Opening unit EV 11810
Closing unit EV 11811
Auxiliary switch EV 11838
Hydraulic shock absorber EV 11840

Driving units (Fig. 2/1, 7/1)


Stored-energy spring operating mechanism type FSA 1 (outdoor)

2.4

Lever EV 11848 is located on the output shaft and when it rotates, it transmits
the rotary movement to the connecting rod.

Connecting rod compl EV 11822 (FSA 1) constitutes the connection between


the operating mechanism and the circuit breaker. Bellows EV 11781 seals the
operating mechanism cubicle at the connecting rod.

Electrical components
In the operating mechanism, the auxiliary switches EV 11838, microswitches EV
11826 (motor limit switches), counters EV 11860 and CLOSE and OPEN magnet
coils are integrated in the basic mechanism.
In the mechanism type FSA 1, the electrical control and monitoring elements
necessary for the control of the circuit breaker are additionally arranged on the
switchgear panel.
These are essentially :
LOCAL-REMOTE selector switch
ON-OFF-switch
Motor protection switch
Auxiliary contacts
Miniature circuit breakers
The operating mechanism is equipped with a permanently turned-on heating resistor
to avoid the condensation inside the operating mechanism.
If the operating mechanism is to be stored outdoors for periods longer than four
weeks, the heater should be connected.

1HYB800001-38 Rev. A
Page 4

3.

Function
3.1

3.2

Function of the basic mechanism (Fig. 7/1)


-

The main shaft EV 11815 serves as the drive shaft for charging the closing spring.

By means of lever EV 11848, the output shaft EV 11816 transmits the closing
or opening movement to the connecting rod, and hence to the circuit breaker.

The motor EV 11843 with reducer gear EV 11842 charges the operating
mechanism mechanically (tensions the closing spring). The motor limit switch,
EV 11826, opens when the closing spring is tensioned.

Hand crank EV 11812 (FSA 1) is used to charge the closing springs by hand
(e.g. on power failure).

On discharging, closing spring EV 11813 release uses the energy to charge


the opening spring via the output shaft, at the same time closing the breaker.

On discharging, opening spring EV 11814 release uses the energy to open the
breaker.

Closing unit EV 11811 holds the closing spring in the charged condition or it
releases it on command electrically via the CLOSE magnet coil or
mechanically (by hand).

Opening unit EV 11810 holds the opening spring in the charged condition or
releases it on command electrically via the OPEN magnet coil or mechanically
(by hand).

Hydraulic shock absorber EV 11840 is double acting. It assures a dampened


opening and closing operation.

Auxiliary switch EV 11838 is controlled by the position of the circuit breaker.


CLOSE and OPEN magnet coils are controlled by its contacts, i.e. the
commands for charging or discharging of the springs are tripped. They also
prevent the CLOSE magnet coils from being excited when the circuit breaker
is closed or the closing spring is not fully charged, or they prevent the OPEN
magnet coils from being energized when the circuit breaker is opened.

Heater EV 11854 (Fig.2/1) is provided in operating mechanism. The heating


resistor prevents condensation in the operating mechanism cubicle. The
heating resistor remains permanently turned on.

Charging the closing spring (Fig. 7/1)


In Fig. 7/1 the basic mechanism is shown with the circuit breaker in the position
OPEN (O) and with the springs in the discharged condition.
The closing spring EV 11813 is charged electrically by motor EV 11843 with
flanged-on reducing gear EV 11842, leading via coupling shaft EV 11841 to worm
gear EV 11819. The hand crank coupling EV 11817 prevents the hand crank from
turning during the electrical charging of the spring. The motor EV 11843 is also
decoupled (by coupling shaft EV 11841) when the spring is charged by hand.

1HYB800001-38 Rev. A
Page 5

As an emergency charging feature the closing spring EV 11813 is charged with hand
crank EV 11812 via bevel gear EV 11818 and worm gear EV 11819 by turning the
main shaft EV 11815. The main shaft EV 11815 is turned via worm wheel and pull
hook EV 11830 which engages the coupling ring EV 11829.
For charging the closing spring approx. 30 rotations of the hand crank are necessary.
On a 1800 rotation the crank EV 11828 runs through top dead center.
The pawl on the control disk EV 11820 is held by lever EV 11832, and the blocking
hook EV 11834 of the closing unit.
The switching cam of crank EV 11828 simultaneously reaches the motor limit switch
EV 11826 and cam follower lever EV 11827 is lifted.
The following functions are thereby initiated :
-

Turning off the power supply to the motor by the motor limit switch.

Preparation of the closing operation by the motor limit switch.

Spring charge indicator indicates Spring charged.

Time necessary for charging the spring at nominal tension : < 15 seconds.

3.3

Closing-operation

(the circuit breaker is closed)

When the engagement lever EV 11837 or the closing coil EV 11839 are actuated by
hand or electrically, the lever 11832 and the blocking hook EV 11834 of the closing
unit release the control disk pawl EV 11820.
By releasing the closing spring EV 11813, the main shaft EV 11815 rotates in the
direction shown on fig. 7/1 and in turn the control disk EV 11820 transmits the
rotational movement to the cam follower EV 11836 and operating lever EV 11835.
The output shaft EV 11816 is thereby rotated and the circuit breaker is closed via
operating lever EV 11848 and connecting rod compl. EV 11780/EV 11822.
Simultaneously, opening spring EV 11814 is charged.
When the output shaft has rotated by 60 o, the control disk pawl passes over the cam
follower EV 11836 and then the output shaft is released and can rotate in the
opposite direction.
However, this is not possible as long as holding cam EV 11847 is held by lever EV
11832 and blocking hook EV 11834 of the opening unit. The closing spring EV
11813 is automatically recharged again.
At power failure the closing spring can be recharged by hand with hand crank EV
11812 (FSA 1).
In this position the following indications are visible :
-

Position indicator : I (circuit breaker in closed position)

Spring charge indicator : Spring charged

1HYB800001-38 Rev. A
Page 6

The operating mechanism is ready for another rapid closing operation but the
interlock hook EV 11833 prevents the execution of a closing operation, while the
circuit breaker is closed. Both springs (EV 11813 and EV 11814) remain charged
and both shafts are blocked by the two blocking units (EV 111810 and EV 11811).

3.4

Opening-operation

(the circuit breaker is open)

The holding cam EV 11847 is released from lever EV 11832 and the opening unit
blocking hook EV 11834, when disengagement lever EV 11845 and opening coil EV
11846 and/or EV 11839 are actuated manually or electrically.
By discharging the opening spring EV 11814, the output shaft EV 11816 rotates 600,
thereby opening the circuit breaker via the connecting rod.
The interlock hook EV 11833 of the closing block is released at the end of the
opening operation and a new closing operation can be executed.

4.

Erection
4.1

Delivery
Each circuit breaker is delivered with its corresponding operating mechanism which
is packed separately or already mounted on the circuit breaker pole beams. At
delivery, both springs are uncharged and the circuit breaker is in open position.

4.2

Installation (Fig. 2/1)


If the operating mechanism is delivered separately, the following must be noted :
Mount the operating mechanism or operating mechanisms (which 1-pole operating
mechanism type) on the circuit-breaker pole beams. Make sure that the number of the
circuit breaker corresponds with the number on the operating mechanism rating plate.
The operating mechanism must be mounted on the circuit breaker according to the
instruction for erection and operation of the circuit breaker.
Connect electrical connections according to valid circuit diagram.
Never operate the operating mechanism if it is not connected to the circuit breaker (filled
with SF6-gas to 0.7 MPa) and the electrical connecting lines are not connected.

5.

Commissioning
5.1

Function tests
Function tests are performed after the commissioning work and immediately before
the circuit breaker is taken into service, as well as after overhaul work.
Function tests may only be performed with the circuit breaker disconnected from the
high-voltage system and filled with SF6-gas to 0.7 MPa (abs).
5.1.1 Manual operation
For this purpose hand crank EV 11812 is used for charging the closing spring. When
the closing spring has reached the desired tension, it automatically uncouples the
pull hook (EV 11830) of the main shaft, thereby releasing the hand crank.
During these trial switching operations, the position indicators (EV 11824 and EV
11825) and the counter must be tested for proper functioning.

1HYB800001-38 Rev. A
Page 7

5.1.2 Motor operation


The motor should be turned on only after the hand crank has been removed, even
though it is uncoupled automatically when the motor is started.
The charging of the closing springs starts as soon as the motor supply is switched
on. The supply of power to the motor is turned off automatically (by microswitch EV
11826) when the closing spring is adequately charged.

6.

Proper functioning of the operation mechanism should be tested by several


CLOSE and OPEN switching operations.

Also a test for correct functioning of the selector switch LOCAL-REMOTE


should be performed.

Motor running time for charging springs at rated voltage : < 15 seconds.

Maintenance
6.1

Duty-related overhaul (Fig. 7/1)


After 2000 CO Switching operations, the following parts must be cleaned and
lubricated without being disassembled :
Cam follower EV 11836 with roller shaft, greased with grease G, (Mobile
Grease 28*)
Worm gearing EV 11819 (worm and worm wheel), grease G (Mobile Grease 28)
Rollers of levers EV 11832 of closing and opening units, grease L (Aseol
Sylitea 4-018)
Clean and lubricate the machined surfaces of the following cams :
Control disk with pawl EV 11820, grease L (Aseol Sylitea 4-108)
Holding cam EV 11847, grease L (Aseol sylitea 4-108)
Treat the worm surfaces of the following pins or cranks with :
Crank pin EV 11853, grease L (Aseol sylitea 4-108)
Spring fixation pin EV 11856, grease L(Aseol sylitea 4-108)
Spring fixation pin EV 11857, grease L(Aseol sylitea 4-108)
Crank with switching cams EV 11828, grease L(Aseol sylitea 4-108)
Change the following details of the connection rod if required (Fig. 2/2):
Rod end joint EV 11858 or EV 11782 (in case of obvious wear)
Bellows EV11781 when there are cracks in material, leaks.
Treat rod end joint with grease G (Mobile Grease 28)
Disassembly and assembly as described in the instructions for erection and
operation of the circuit breaker.
No work is allowed to be carried out until the closing and opening springs are
discharged, and the circuit breaker is in the OPEN O position. The power to the
motor must be disconnected.
After 5000 CO switching operations, a general overhaul must be performed by
specialized staff. Please contact the manufacturer or his representative.
*As an alternative to Mobile Grease 28, Molykote Long term 2 plus or Aseol Sylitea
4-108 may be used.

1HYB800001-38 Rev. A
Page 8

7.

Spare parts
For ordering, the following data are essential :
-

7.1

Order number
Type designation
Serial number
Publication number
Part number
Design
Part designation

See order documentation


See rating plate
See rating plate
See spare parts list
See spare parts list
Outdoor
See spare parts list

Storage instruction
Before the erection, the operating mechanisms shall be stored indoors or under a
roof as long as possible. If the units are stored outdoors, they must be prevented
from standing in water pools. With outdoor storage for long periods, the units shall be
covered with tarpaulin and the heating elements of the operating mechanism shall be
connected.

7.2

Spare parts list


Overhaul parts :
Part No.

EV 11781
EV 11782
EV 11858
EV 11859

Part designation Number/Type of operating mechanism

Bellows
Rod end joint
Rod end joint
Motor brush

FSA 1 (1)

FSA 1 (F)

1
2

1
1
2

Figure

2/1,2/2a,b
2/1,2/2b
2/1,2/2a
7/1

Reserve parts :
Part Number Part designation

Number/type of operating mechanism Figure/section


FSA 1 (1)

EV
EV
EV
EV
EV
EV
EV
EV
EV
EV
EV
EV
EV
EV
EV

11810
11811
11813
11814
11823
11826
11836
11838
11839
11840
11842
11843
11844
11846
11854

Opening unit
1
Closing unit
1
Closing spring
1
Opening spring
1
Pin
1
Motor limit switch
2
Cam follower
1
Auxiliary switch
1
Coil CLOSE, OPEN 1
1
Hydraulic shock absorber 1
Reducer gear
1
Motor
1
Switching element (yellow) 2
Coil OPEN 2
1
Heater
1

FSA 1 (F)
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1

7/1 (legend)/3.1
7/1 (legend)/3.1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
7/1
2/1

1HYB800001-38 Rev. A
Page 9

Appendix
8.1

Figures
Fig. Title
2/1

Stored-energy spring operating mechanism compl. FSA 1

2/2a Connecting rod compl. FSA (outdoor)


7/1

Drive mechanics (schematic representation)

1HYB800001-38 Rev. A
Page 10

1HYB800001-38 Rev. A
Page 11

Legend to Fig. 2/1


EV 11781

Bellows

EV 11812

Hand crank (FSA 1)

EV 11822

Connecting rod compl. (FSA 1)

EV 11824

Spring charge indicator

EV 11825

Breaker position indicator

EV 11849

Rotational movement lever

EV 11851

Drive assembly cubicle compl.

EV 11854

Heater

EV 11855

Chassis

EV 11858

Rod end joint (FSA 1)

Breaker position indicators

b1

Breaker position OPEN O, springs


discharged (not ready for switching)

b2

Breaker position OPEN O, springs


charged (ready for CO Switching operation)

b3

Breaker position CLOSED I, springs


charged (ready for O-CO switching operation)

11812

Fig. 2/1

1HYB800001-38 Rev. A
Page 13

Legend to fig. 2/2a


EV11781

Bellow

EV11822

Connection rod compl. (FSA 1)

EV11858

Rod end joint (FSA 1)

84638

Hex nut M20 x 1.5 mm/0.5d

MD

Torque

Fig. 2/2a

1HYB800001-38 Rev. A
Page 15

EV11812
EV11813
EV11814
EV11815
EV11816
EV11817
EV11818
EV11819
EV11820
EV11822
EV11823
EV11824
EV11825
EV11826
EV11827
EV11828
EV11829
EV11830
EV11831
EV11832
EV11833
EV11834
EV11835
EV11836
EV11837
EV11838
EV11839
EV11840
EV11841
EV11842
EV11843
EV11844
EV11845
EV11846
EV11847
EV11848
EV11850
EV11852
EV11853
EV11856
EV11857
EV11859
EV11860

*)
2*)

Legend to fig. 7/1


Hand crank (FSA 1)
Closing spring
Opening spring
Main shaft
Output shaft
Handcrank coupling
Bevel gearing
Worm gearing
Control disk with pawl
Connecting rod compl. (FSA 1)
Pin
Spring charge indicator
Position indicator
Microswitch (motor limit switch)
Cam follower lever
Crank with switching cams
Coupling ring
Pull hook
Adjusting screw
Lever (closing/opening block)*),2*)
Interlock hook*)
Blocking hook*),2*)
cam follower lever
Cam follower
Engagement lever (closing lever)*)
Auxiliary switch
Coil CLOSE, OPEN 1*),2*)
Hydraulic shock absorber
Coupling shaft
Reducer gear
Motor
Switching element (yellow)
Disengagement lever (opening lever)2*)
Coil OPEN 2, 2*)
Holding cam
Rotational movement lever (FSA 1, outdoor)
Auxiliary switch lever
Drive mechanism
Crank pin
Spring fixation pin
Spring fixation pin
Motor brush
Switching operation counting meter

Part of closing block EV11811


Part of opening block EV11810

Fig. 7/1

1HYB800001-52 Rev.A

ABB Ltd.
Maneja, Vadodara
Gujarat, (INDIA)
Tel. : +91 265 2642141
Fax : +91 265 2638918, 2638911
visit us at : www.abb.com

You might also like