You are on page 1of 6

HEAT LOAD FORMAT - FILL THE YELOW SECTION

CONSULTANT

JOB NAME
SPACE FOR
AREA

DUAA DESIGN
Maulana Mohd Ali Jauhar
Medical College , Rampur
Corridor C1
1877

DATE

1/12/2014

Estimated By

S.M.Raza

Occupancy
Lighting
Eq. Load
Height
Fresh Air
N - Glass
NE - Glass
E - Glass
SE - Glass
S - Glass
SW - Glass
W - Glass
NW - Glass
Sky light
N - Wall
NE - Wall
E - Wall
SE - Wall
S - Wall
SW - Wall
W - Wall
NW - Wall
Roof Sun
Roof Shaded

SQ FT

NOS

WATT/SQ FT

KW

12

FT

15

CFM PER PERSON

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

144

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

SQ FT

1692

SQ FT

SQ FT

SQ FT

SQ FT

Partition
Ceiling
Floor
ir Change per hour

147

SQ FT

SQ FT

SQ FT

OUTSIDE DB (F)

115

OUTSIDE 'WB (F)

79

OUTSIDE % RH

26

OUTSIDE GR/LB

90

ROOM DB (F)

75

To be filled by
psychometric chart

ROOM 'WB (F)


ROOM % RH

50

ROOM GR/LB

56

RESULT

SUMMER
GRAND TOTAL HEAT

92819

BTU/HR

DEHUMIDIFIED CFM

2925

CFM

CAPACITY

7.73

TR

CHECK FIGURE

378

CFM PER TON

CHECK FIGURE

243

SQ FT PER TON

375

CFM

GRAND TOTAL HEAT

87913

BTU/HR

DEHUMIDIFIED CFM

2925

CFM

CAPACITY

8.56

TR

CHECK FIGURE

262

CFM PER TON

CHECK FIGURE

219

SQ FT PER TON

GRAND TOTAL HEAT

-29774

BTU/HR

DEHUMIDIFIED CFM

-916

CFM

CAPACITY

-8.71

KW

VENTLATION CFM

MONSOON

WINTER

CHECK FIGURE

105

CFM PER KW

CHECK FIGURE

-216

SQ FT PER KW

DUAA DESIGN
JOB NAME:

Maulana Mohd Ali Jauhar Medical College , Rampur

SPACE FOR:
Corridor C1
SIZE:
1877 Sq ft
SOLAR GAIN GLASS
ITEM

1/12/2014 Rev: 0
Estimated By: S.M.Raza
Estimate for: SUMMER
DATE:

22524 Cu ft
HEAT GAIN
Btu/hour

DB (F) WB (F)

OUTSIDE

115

ROOM

75

% RH

(Sq ft)

(Btu/h.sq ft)

N - Glass

14

0.56

0 DIFFERENCE

NE - Glass

12

0.56

E - Glass
SE - Glass
S - Glass
SW - Glass

0
0
0
0

12
12
12
100

0.56
0.56
0.56
0.56

0 OUTSIDE AIR (VENTILATION)


0
8 People X
15.0
CFM/Person
0
22524 Cu ft X
1.0 Air change per hour
0
CFM VENTILATION

W - Glass
NW - Glass

144
0

164
123

0.56
0.56

12

Eq. temp. diff.

58 F

DEHUMIDIFIED CFM =

2925

(F)

(Btu/h.sq ft)

29

0.35

NE - Wall

35

0.35

E - Wall

43

0.35

SE - Wall

18

0.35

S - Wall

41

0.35

SW - Wall

39

0.35

1692

37

0.35

21911

NW - Wall

31

0.35

Roof Sun

60

0.52

Roof Shaded

33

0.12

0 NOTES

TRANS. GAIN EXCEPT WALLS & ROOF

7.3124263669

Occupancy =

Area

Temp. diff.

52.1 F
20.15 F

ITEM

XXXX

Dehum. temp rise =

(Sq ft)

W - Wall

XXXX

Indicated ADP =

N - Wall

Lighting =
Eq. Load =

Nos

1.0

W/Sq ft

(Sq ft)

(F)

(Btu/h.sq ft)

0.0

KW

All Glass

144

40

1.13

6509 Height =

12.00

FT

Partition

147

35

0.40

2058 Fresh Air=

15.0

Cfm per person

Ceiling

35

0.40

1.0

Air chnages per hour

Floor

35

0.42

0 Internal Heat - People

INTERNAL HEAT GAIN


People
Light
Eq. Load

8 Nos X

245

1960

1877 W X 1.25

3.41

8001

0.0 W X

3.41

ROOM SENSIBLE HEAT (RSH)


Supply duct heat Supply duct Heat gain from
gain +
leak. loss + fan HP(%)

Safety factor (%)

15.0

=
Sensible Heat =

245

Latent Heat =

205

0
53664
0
8050

OUTSIDE AIR
CFM

BF

FACTOR

375

40

0.12

1.08

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People

Nos X

1946
63660

205

ROOM LATENT HEAT (RLH)


Supply duct leakage loss + Safety factor %

10.0

1640
164

OUTSIDE AIR
CFM

GR/LB

BF

FACTOR

375

34

0.12

0.67

EFFECTIVE ROOM LATENT HEAT (ERLH)


EFFECTIVE ROOM TOTAL HEAT (ERTH)
OUTSIDE AIR HEAT (SENSIBLE)
CFM

1 - BF

FACTOR

375

40

0.88

1.08

OUTSIDE AIR HEAT (LATENT)


CFM

GR/LB

1 - BF

FACTOR

375

34

0.88

0.68
HEAT SUB TOTAL

Return duct heat HP Pump +


gain & leak. loss +

TR

7.73

Dehum. & Pipe


loss (%)

5.0

GRAND TOTAL HEAT

1026
2830
66490

CHECK FIGURES
Btu/h/ Sq ft =

49.5

14271 CFM / Sq ft =
Sq ft / TR =

1.56
243

CFM/ TR
7638
88399
4420

92819

378

90

50

Selected ADP =

Area

26

13225
0 EFF. SENSIBLE HEAT FACTOR (ESHF) =

SOLAR & TRANS. GAIN WALLS & ROOF


ITEM

40

79

DP (F) GR/LB

Sun Gain

Sky light

Factor

CONDITION

Area

56
XXXX

0.96

34

120
375
375

DUAA DESIGN
JOB NAME:

Maulana Mohd Ali Jauhar Medical College , Rampur

Corridor C1
SPACE FOR:
SIZE:
1877 Sq ft
SOLAR GAIN GLASS
ITEM

DATE:
41651
Rev: 0
Estimated By:
S.M.Raza

22524 Cu ft

Estimate for: MONSOON

HEAT GAIN

(Sq ft)

(Btu/h.sq ft)

N - Glass

11

0.56

0 DIFFERENCE

NE - Glass

11

0.56

E - Glass

11

0.56

0 OUTSIDE AIR (VENTILATION)

SE - Glass

11

0.56

People X

15

S - Glass

13

0.56

22524

Cu ft X

SW - Glass

127

0.56

144

165

0.56

13306

100

0.56

Sky light

OUTSIDE

95

ROOM

75

ITEM

(Sq ft)

(F)

(Btu/h.sq ft)

N - Wall

16

0.35

NE - Wall

22

0.35

E - Wall

30

0.35

SE - Wall

30

0.35

S - Wall

28

0.35

SW - Wall

26

0.35

1692

24

0.35

14213

NW - Wall

18

0.35

Roof Sun

47

0.52

Roof Shaded

10

0.12

W - Wall

TRANS. GAIN EXCEPT WALLS & ROOF


ITEM

Temp. diff.

(Sq ft)

(F)

(Btu/h.sq ft)

All Glass

144

20

1.13

Partition

147

15

0.4

Ceiling

15

0.4

Floor

15

0.42

8 Nos X

245

1960

1877 W X 1.25

3.41

8001

0 WX

3.41

INTERNAL HEAT GAIN


Light
Eq. Load

ROOM SENSIBLE HEAT (RSH)


duct

52 F

DEHUMIDIFIED CFM =

2244

Nos
W/Sq ft
KW
Ft.
Cfm per person
Air change/ hour

Safety factor (%)

15

6242

OUTSIDE AIR
F

BF

FACTOR

375

20

0.12

1.08

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People

Nos X

973
48831

205

ROOM LATENT HEAT (RLH)


Supply duct leakage loss + Safety factor%

10

1640
82

OUTSIDE AIR
CFM

GR/LB

BF

FACTOR

375

102

0.12

0.68

EFFECTIVE ROOM LATENT HEAT (ERLH)


EFFECTIVE ROOM TOTAL HEAT (ERTH)
OUTSIDE AIR HEAT (SENSIBLE)
CFM

1 - BF

FACTOR

375

20

0.88

1.08

CHECK FIGURES
3125 Btu/h/ Sq ft =

54.7

4847 CFM / Sq ft =

1.20

53677 Sq ft / TR =

219

CFM/ TR

262

7136

OUTSIDE AIR HEAT (LATENT)


CFM

GR/LB

1 - BF

FACTOR

375

102

0.88

0.68

HEAT SUB TOTAL


Return duct heat HP Pump +
gain & leak. loss +

TR

8.56

Dehum. & Pipe


loss (%)

5.0

TOTAL HEAT

CFM/Person

20.15 F

22913
83726
4186

87913

56
XXXX

Air change per hour

58 F

41616

heat Supply duct Heat gain from


leak. loss + fan HP(%)

CFM

XXXX

Dehum. temp rise =

8
1.0
0.0
12.0
15.0
Fresh air=
1.0
=
Internal Heat - People
245
Sensible Heat =
205
Latent Heat =

REHEAT

1 TR

GR/LB
158

XXXX

Indicated ADP =

NOTES
Occupancy =
Lighting =
Eq. Load =
3254
Height=
882

Area

People

20

Selected ADP =

Eq. temp. diff.

DP (F)

50

0 EFF. SENSIBLE HEAT FACTOR (ESHF) =


0

Area

% RH

83

CFM VENTILATION

SOLAR & TRANS. GAIN WALLS & ROOF

Supply
gain +

WB (F)

Sun Gain

NW - Glass

Btu/hour

DB (F)

Area

W - Glass

Factor

CONDITION

0.91

102

120
375
375

DUAA DESIGN
JOB NAME:

Maulana Mohd Ali Jauhar Medical College , Rampur


Corridor C1

SPACE FOR:

SIZE:
SOLAR GAIN GLASS

1877 Sq ft

22524

Cu ft
HEAT GAIN

ITEM

Area

Sun Gain

(Sq ft)

(Btu/h.sq ft)

Factor

Btu/hr

N - Glass

0.56

NE - Glass

0.56

E - Glass

0.56

SE - Glass

0.56

S - Glass

64

0.56

SW - Glass

114

0.56

W - Glass
NW - Glass
Sky light

0
0

92
10

0.56
0.56

0
0
0

SOLAR & TRANS. GAIN WALLS & ROOF


ITEM

Eq. temp. diff.


(F)

U
(Btu/h.sq ft)

-40

0.35

-34

0.35

E - Wall

-26

0.35

SE - Wall

-26

0.35

S - Wall
SW - Wall

0
0

-28
-30

0.35
0.35

0
0

1692

-32

0.35

-18950

NW - Wall

-38

0.35

Roof Sun

-9

0.52

Roof Shaded

-30

0.20

TRANS. GAIN EXCEPT WALLS & ROOF


ITEM

Area

Temp. diff.

(Sq ft)

(F)

(Btu/h.sq ft)

All Glass

144

-30

1.13

-4882

Partition

147

-35

0.32

-1646

Ceiling

-35

0.38

Floor

-35

0.38

8 Nos X

245

1960

1877 W X 1.25

3.41

8001

0 WX

3.41

INTERNAL HEAT GAIN


People
Light
Eq. Load

DB (F)

OUTSIDE

45

ROOM

75

DIFFERENCE

-30

ROOM SENSIBLE HEAT (RSH)


Supply duct heat gain Supply duct Heat gain from
+
leak. loss + fan HP(%)

8 People X
22524 Cu ft X

NOTES
Occupancy =
8
Lighting =
1.0
Eq. Load =
0.0
Height=
12.0
Fresh air =
15.0
=
1.0
Internal Heat - People
245
Sensible Heat =
205
Latent Heat =

0
-15518

-2328

OUTSIDE AIR
CFM

BF

FACTOR

375

-30

0.12

1.08

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)

-1460

-19926

LATENT HEAT
People

8 Nos X

205.0

ROOM LATENT HEAT (RLH)


Supply duct leakage loss + Safety factor %

5.0

1640
82

OUTSIDE AIR
CFM

GR/LB

BF

FACTOR

375

0.12

0.68

EFFECTIVE ROOM LATENT HEAT (ERLH)


EFFECTIVE ROOM TOTAL HEAT (ERTH)
OUTSIDE AIR HEAT (SENSIBLE)
CFM

1 - BF

FACTOR

375

-30

0.88

1.08

GR/LB

1 - BF

FACTOR

0.88

0
1722

-18204

-10703

OUTSIDE AIR HEAT (LATENT)


CFM

0.68

HEAT SUB TOTAL


Return duct heat gain HP Pump +
& leak. loss +

kW

-8.71

Dehum. & Pipe


loss (%)

3.0

GRAND TOTAL HEAT

-28907
-867
SQFT/KW =

-29774

% RH

DP (F)

41

GR/LB
32

30
XXXX

XXXX

15

XXXX

CFM/Person

1 Air change per hour

EFF. SENSIBLE HEAT FACTOR (ESHF) =


Indicated ADP =
F

-621
15.0

WB (F)

CFM VENTILATION

Safety factor (%)

Rev: 0
S.M.Raza

OUTSIDE AIR (VENTILATION)

Dehum. temp rise =


DEHUMIDIFIED CFM =

N - Wall

41651

Estimate for: WINTER


CONDITION

Selected ADP =

Area
(Sq ft)

NE - Wall

W - Wall

DATE:
Estimated By:

-216

52 F
20.15 F
-916

Nos
W/Sq ft
KW
Ft.
Cfm per person
Air changes per hour

120
375
375