You are on page 1of 37

AWG Copper Wire Table

AWG Diam. (mils) Circular mils Ohms/1000ft Current Carrying Fusing Current Feet per Pound
0000

460

212000

0.050

1.56

000

410

168000

0.063

1.96

00

365

133000

0.077

2.4826

324.85

105531

0.096

3.1305

289.3

83694

0.1264

119.6

3.947

257.6

66358

0.1593

94.8

4.977

229.4

52624

0.2009

75.2

6.276

204.3

41738

0.2533

59.6

7.914

181.9

33088

0.3915

47.3

9.980

162

26244

0.4028

37.5

668

12.58

144.3

20822

0.5080

29.7

561

15.87

128.5

16512

0.6405

23.6

472

20.01

114.4

13087

0.8077

18.7

396

25.23

10

101.9

10384

1.018

14.8

333

31.82

11

90.7

8226

1.284

11.8

280

40.12

12

80.8

6529

1.619

9.33

235

50.59

13

72.0

5184

2.042

7.40

197

63.80

14

64.1

4109

2.575

5.87

166

80.44

15

57.1

3260

3.247

4.65

140

101.4

16

50.8

2581

4.094

3.69

117

127.9

17

45.3

2052

5.163

2.93

98.4

161.3

18

40.3

1624

6.510

2.32

82.9

203.4

19

35.9

1289

8.210

1.84

69.7

256.5

20

32.0

1024

10.35

1.46

58.4

323.4

21

28.5

812

13.05

1.16

407.8

22

25.3

640

16.46

.918

41.2

514.12

23

22.6

511

20.76

.728

648.4

24

20.1

404

26.17

.577

29.2

817.7

25

17.9

320

33.0

.458

1031

26

15.9

253

41.62

.363

20.5

1300

27

14.2

202

52.48

.288

1639

28

12.6

159

66.17

.228

14.4

2067

29

11.3

128

83.44

.181

2607

30

10.0

100

105.2

.144

10.2

3287

31

8.9

79

132.7

.114

4145

32

8.0

64

167.3

.090

5227

33

7.1

50.125

211.0

.072

6591

34

6.3

39.75

266.0

.057

5.12

8310

35

5.6

31.5

335

.045

4.28

10480

36

5.0

25.0

423

.036

3.62

13210

37

4.45

19.83

533

.028

16660

38

3.97

15.7

673

.022

2.5

21010

39

3.5

12.47

848

.018

26500

40

3.14

9.89

1070

.014

1.77

33410

41

2.8

7.842

1.52

42

2.494

6.219

1.28

43

2.221

4.932

1.060

44

1.978

3.911

0.916

45

1.761

3.102

46

1.568

2.460

47

1.397

1.951

48

1.244

1.547

49

1.107

1.227

50

0.986

0.973

Table of Bare Copper Wire


General Notes:
The wire size is different between the American Wire Gage [AWG] and the British standard. The table above only lists the AWG
standard.
AWG [American Wire Gauge] may also be called the Brown and Sharpe (B&S) Wire Gauge.
The Birmingham Wire Gauge [BWG] is used for steel armor wire.
Watch for round-off errors, as many numbers were rounded. Use the table as a guide.
The weight [pound per foot] does not include wire insulation. The weight of the wire is critical in some applications.
Circular mils is the diameter squared in mils.
The editor has never seen the American Wire Gauge [AWG]
Current Notes:
The current shown per wire size listed above is based on 1 amp/ 700 Circular mils, other tables provide different current per wire size,
and different current for open air ~ check your local electrical code for the correct current capacity [Ampacity]. The 1 amp/ 700
Circular mils seems to be the most conservative, other sites provide/allow for 1 amp per 200 or 300 Circular mil. For shot wire lengths
use 1A/200 Circular mil, for longer wire runs use 300 Circular mil, and for very long wire runs use the table above, 1 amp / 700
Circular mil.
The current rating is listed based on permissible voltage drop and not conductor heating.
The ability of a wire to carry a given amount of current is affected by a number of additional factors, which are not accounted for in
the AWG table above. The ambient temperature of the surrounding air, wire insulation, and number of other wires bundled together
[provided below].
Ampacity relates to the ability of the conductor to carry current [amps] before the cable over heats. There are hundreds of Ampacity
tables for many different conditions. The numbers above are but one example. Ampacity Tables for many conditions:
IEEE Standard 835, IEEE Standard Power Cable Ampacity Tables
IEEE Standard 848, Procedure for the Determination of the Ampacity Derating of Fire Protected Cables
ICEA P-54-440, NEMA Pub. No. WC 51 - Ampacities of Cables in Open-Top Trays.
The National Electrical Code [NEC] requires their own cable sizing for premises wiring. Refer to the NEC rules to determine building

wiring, as this page relates to electronic equipment wiring. For reference, the ampacity of copper wire at 30 0C for common wire sizes
14 AWG may carry a maximum of 20 Amps in free air, or 15 Amps as part of a 3 conductor cable.
12 AWG may carry a maximum of 25 Amps in free air, or 20 Amps as part of a 3 conductor cable.
10 AWG may carry a maximum of 40 Amps in free air, or 30 Amps as part of a 3 conductor cable.
8 AWG may carry a maximum of 70 Amps in free air, or 50 Amps as part of a 3 conductor cable.
The wire fusing [melting] current is based on the material the wire is made of, the diameter of the wire and the melting point of the the
material. The wire fusing current of a wire is provided in tables as constant current or as [a larger] current for some given amount of
time.
This formula is used on a few different sites [un-verified]; I=Ad(3/2) @ d is in inches, A is a constant: A = 10,244 for Copper. A = 7,585
for Aluminum.
I have listed a number of values for fusing current in the table above, for selected AWG sizes.

Aluminum wire properties are listed under on the Aluminum electrical Wire page
Manufacturers listing for electrical Wire and Cable {This Web Site}

Cable manufacturers will provide different numbers based on the insulation used for the wire.
Use the table below to off-set the conservative current carrying numbers in the table above, and the fusing current. The table below
lists copper wire with a Teflon [TFE] insulation. Teflon insulation has a higher operation temperature range then other insulators, for
example PVC. The table below is based on data derived from MIL-STD-975, using 700C as the operating temperature. To derate based
on number of wires in a bundle:
IBW = ISW x (29 - #wire) / 28 @ [1 to 15 Bundled wires]
IBW = ISW x (0.5) @ [more then 15 Bundled wires]
ISW = Single wire
IBW = Bundled wires
To derate by temperature use; derate by 80% at 1500C, 70% at 1350C, or 50% at 1050C (per MIL-STD-975)

Copper Wire TFE Insulated


AWG

Current Carrying

AWG

Current Carrying

00

169

147

108

81

60

44

10

33

12

25

14

19

16

13

18

9.2

20

6.5

22

4.5

24

3.3

26

2.5

28

1.8

30

1.3

DC Wire Table

Wire Loss Tables for Solar Electric Systems


Includes 12, 24, and 120 volt charts and a
Metric to AWG size conversion table.

This is a five percent table which means at these amperage ratings at the listed distances, 5% of
the power would be lost to resistance. Five percent is normally acceptable in low voltage systems,
but if you want a 2% figure, divide the given distances by 2.5. For a 10% loss multiply the
distance by 2. For distances at 48 volts, double the 24 volt distances for a 5 percent loss figure. For
240 volt 5% loss, double the 120 volt distances. These distances include the NEC requirement for
current over sizing of 25%.
Example: For a pump drawing 9 amperes at 24 volts, located 88 feet from the battery bank: look at
the center table for 24 volts. In the far left column find the next number higher than 9 (which is 10)
and follow that line across the table until you find a distance figure greater than 88. At the top of
the column find the gauge of wire (#8) that should be used. This method insures that wire losses
are kept to an acceptable level without spending too much money on extra-heavy cable. Using a
heavier wire than indicated, however, will result in even higher efficiencies and we do sometimes
invest in the next larger gauge. Wire can get expensive, and it may not be worth the money to get
that last 1% if you have to go to a much larger wire size.

Some of the newer grid tie systems inverters, such as the Sunny Boy, use up to 600 volts DC. Generally in these
systems loss in wire is nothing to worry about. HOWEVER - you will have to be more careful about selecting and
installing the wiring - high voltage DC is not something you want to do a 2nd rate wiring job on. Make sure the
insulation is rated for 600 volts, and that there is no damage to the wire or insulation.

We have also included a wire chart for converting Metric to AWG (American Wire gauge)
sizes.
All distances are in FEET
Do not use any wire sizes that might fall into the red zone - this would exceed the amperage rating of the wire
and it may overheat and burn.

120 Volt AC or DC chart


Amps in Watts at
Wire
120V

#14

#12

#10

#8

240

422

656

480

187

328

516

720

141

225

328

562

960

103

159

272

422

#6

666

#4

#2

1/0

2/0

3/0

10

1200

84

131

216

337

534

15

1800

56

84

131

225

356

562

20

2400

65

103

1-8

272

422

675

25

3000

84

131

216

337

543

30

3600

65.63

112

178

281

450

722

40

4800

84

131

216

337

543

675

50

6000

67

103

171

272

431

543

684

24 Volt DC chart
Amps
in Wire

Watts
at 24V

#14

#12

#10

#8

#6

#4

#2

1/0

2/0

3/0

24

169

262

412

675

48

84

131

207

337

532

96

37

66

103

169

267

144

28

45

66

112

178

282

192

21

32

54

84

133

216

10

240

17

26

43

67

107

169

270

15

360

11

17

26

45

71

112

180

289

20

480

13

21

37

54

84

135

217

270

343

25

600

17

26

43

67

108

172

217

274

30

720

13

22

36

56

90

144

180

228

40

960

17

26

43

67

108

135

171

50

1200

13

21

34

54

86

108

137

12 Volt DC chart
Amps in Watts at
Wire
12V

#14

#12

#10

#8

#6

#4

#2

1/0

2/0

3/0

12

84

131

206

337

532

24

42

66

103

168

266

432

675

48

18

33

52

84

133

216

337

543

675

72

14

22

33

56

89

141

225

360

450

570

96

10

16

27

42

66

108

168

272

338

427

10

120

8.5

13

22

33

53

84

135

218

270

342

15

180

8.5

13

22

35

56

90

144

180

228

20

240

6.6

10

16

27

42

67

108

135

171

25

300

13

22

33

54

86

108

137

30

360

40

480

6.6

11

18

28

45

72

90

114

13

21

33

54

67

85

These are one-way distances, measured from point A to point B. The out and
back nature of electrical circuits has already been included. For PV arrays,
figure the entire run, from the panels to the charge controller to the batteries

Cross reference of AWG (American Wire Gauge) sizes to metric (mm)


AWG

mm2

AWG

mm2

AWG

mm2

AWG

mm2

30

0.05

18

0.75

16

4/0

120

28

0.08

17

1.0

25

300MCM

150

26

0.14

16

1.5

35

350MCM

185

24

0.25

14

2.5

50

500MCM

240

22

0.34

12

4.0

1/0

55

600MCM

300

21

0.38

10

6.0

2/0

70

750MCM

400

20

0.50

10

3/0

95

1000MCM

500

WIRE GAUGE TABLES


American Wire Gauge (AWG) sizes may be determined by measuring the diameter of the
conductor (the bare wire) with the insulation removed. Refer to the Wire gauge Diameter
Table for dimensions. When choosing wire gauge, the distance the wire must run and the
amperage it will be expected to carry must be determined first. Refer to the Wire gauge
Selection Table. Note that you can always use thicker wire (lower gauge number) than is
recommended.

METRIC-TO-AWG CONVERSION TABLE

Metric Size
AWG Size
mm2

0.5

20

0.8

18

1.0

16

2.0

14

3.0

12

5.0

10

8.0

13.0

19.0

32.0

52.0

WIRE GAUGE DIAMETER TABLE

American Wire gauge

Wire Diameter in inches

20

0.03196118

18

0.040303

16

0.0508214

14

0.064084

12

0.08080810

10

0.10189

0.128496

0.16202

0.18194

0.20431

0.22942

0.25763

0.2893

0.32486

00

0.3648

WIRE GAUGE SELECTION TABLE

Circuit
Amperes

Circuit Watts

Wire gauge (for length in feet)

6V

12V

6V

12V

3'

5'

7'

10'

15'

20'

25'

0 to
2.5

0 to 5

15

30

18

18

18

18

18

18

18

3.0

18

36

18

18

18

18

18

18

16

3.5

21

42

18

18

18

18

18

18

16

4.0

24

48

18

18

18

18

18

16

16

5.0

10

30

60

18

18

18

18

16

16

16

5.5

11

33

66

18

18

18

18

16

16

14

6.0

12

36

72

18

18

18

18

16

16

14

7.5

15

45

90

18

18

18

18

14

14

12

9.0

18

54

108

18

18

16

16

14

14

12

10

20

60

120

18

18

16

16

14

12

10

11

22

66

132

18

18

16

16

12

12

10

12

24

72

144

18

18

16

16

12

12

10

15

30

90

180

18

16

16

14

10

10

10

20

40

120

240

18

16

14

12

10

10

25

50

150

300

16

14

12

12

10

10

50

100

300

600

12

12

10

10

75

150

450

900

10

10

100

200

600

1200

10

Find the amperes or watts the circuit is expected to carry on the left and the distance the
wiring must run at the top - follow the columns until they intersect - for example, a 12
volt circuit which is 15 feet long and carries 10 amperes should use at least 16 gauge
wire.

WIRE GAUGE AND CURRENT LIMITS

AWG Wire Sizes (see table below)


AWG: In the American Wire Gauge (AWG), diameters can be calculated by applying the
formula D(AWG)=.00592((36-AWG)/39) inch. For the 00, 000, 0000 etc. gauges you use -1,
-2, -3, which makes more sense mathematically than "double nought." This means that in
American wire gage every 6 gauge decrease gives a doubling of the wire diameter, and
every 3 gauge decrease doubles the wire cross sectional area. Similar to dB in signal and
power levels. An approximate form of this formula contributed by Mario Rodriguez is D
= .460 * (57/64)(awg +3) or D = .460 * (0.890625)(awg +3).
Metric Wire Gauges (see table below)
Metric Gauge: In the Metric Gauge scale, the gauge is 10 times the diameter in
millimeters, so a 50 gauge metric wire would be 5 mm in diameter. Note that in AWG the
diameter goes up as the gauge goes down, but for metric gauges it is the opposite.
Probably because of this confusion, most of the time metric sized wire is specified in
millimeters rather than metric gauges.
Load Carrying Capacities (see table below)
The following chart is a guideline of ampacity or copper wire current carrying capacity
following theHandbook of Electronic Tables and Formulas for American Wire Gauge. As
you might guess, the rated ampacities are just a rule of thumb. In careful engineering the
voltage drop, insulation temperature limit, thickness, thermal conductivity, and air
convection and temperature should all be taken into account. The Maximum Amps for
Power Transmission uses the 700 circular mils per amp rule, which is very very
conservative. The Maximum Amps for Chassis Wiring is also a conservative rating, but is
meant for wiring in air, and not in a bundle. For short lengths of wire, such as is used in
battery packs you should trade off the resistance and load with size, weight, and
flexibility. NOTE: For installations that need to conform to the National Electrical Code,
you must use their guidelines. Contact your local electrician to find out what is legal!
AWG Conductor Conductor Ohms Ohms per Maximum Maximum Maximum
gauge Diameter Diameter per
km
amps for amps for
frequency
Inches
mm
1000 ft.
chassis
power
for
wiring
transmission 100% skin
depth for

solid
conductor
copper
OOOO 0.46

11.684

0.049

0.16072 380

302

125 Hz

OOO

0.4096

10.40384 0.0618 0.202704 328

239

160 Hz

OO

0.3648

9.26592

0.0779 0.255512 283

190

200 Hz

0.3249

8.25246

0.0983 0.322424 245

150

250 Hz

0.2893

7.34822

0.1239 0.406392 211

119

325 Hz

0.2576

6.54304

0.1563 0.512664 181

94

410 Hz

0.2294

5.82676

0.197

0.64616 158

75

500 Hz

0.2043

5.18922

0.2485 0.81508 135

60

650 Hz

0.1819

4.62026

0.3133 1.027624 118

47

810 Hz

0.162

4.1148

0.3951 1.295928 101

37

1100 Hz

0.1443

3.66522

0.4982 1.634096 89

30

1300 Hz

0.1285

3.2639

0.6282 2.060496 73

24

1650 Hz

0.1144

2.90576

0.7921 2.598088 64

19

2050 Hz

10

0.1019

2.58826

0.9989 3.276392 55

15

2600 Hz

11

0.0907

2.30378

1.26

4.1328

47

12

3200 Hz

12

0.0808

2.05232

1.588

5.20864 41

9.3

4150 Hz

13

0.072

1.8288

2.003

6.56984 35

7.4

5300 Hz

14

0.0641

1.62814

2.525

8.282

32

5.9

6700 Hz

15

0.0571

1.45034

3.184

10.44352 28

4.7

8250 Hz

16

0.0508

1.29032

4.016

13.17248 22

3.7

11 k Hz

17

0.0453

1.15062

5.064

16.60992 19

2.9

13 k Hz

18

0.0403

1.02362

6.385

20.9428 16

2.3

17 kHz

19

0.0359

0.91186

8.051

26.40728 14

1.8

21 kHz

20

0.032

0.8128

10.15

33.292

11

1.5

27 kHz

21

0.0285

0.7239

12.8

41.984

1.2

33 kHz

22

0.0254

0.64516

16.14

52.9392 7

0.92

42 kHz

23

0.0226

0.57404

20.36

66.7808 4.7

0.729

53 kHz

24

0.0201

0.51054

25.67

84.1976 3.5

0.577

68 kHz

25

0.0179

0.45466

32.37

106.1736 2.7

0.457

85 kHz

26

0.0159

0.40386

40.81

133.8568 2.2

0.361

107 kH

27

0.0142

0.36068

51.47

168.8216 1.7

0.288

130 kHz

28

0.0126

0.32004

64.9

212.872 1.4

0.226

170 kHz

29

0.0113

0.28702

81.83

268.4024 1.2

0.182

210 kHz

30

0.01

0.254

103.2

338.496 0.86

0.142

270 kHz

31

0.0089

0.22606

130.1

426.728 0.7

0.113

340 kHz

32

0.008

0.2032

164.1

538.248 0.53

0.091

430 kHz

Metric
0.00787
2.0

0.200

169.39 555.61

33

0.18034

Metric
0.00709
1.8
34

0.51

0.088

440 kHz

206.9

678.632 0.43

0.072

540 kHz

0.180

207.5

680.55

0.43

0.072

540 kHz

0.0063

0.16002

260.9

855.752 0.33

0.056

690 kHz

Metric
0.0063
1.6

0.16002

260.9

855.752 0.33

0.056

690 kHz

35

0.14224

329

1079.12 0.27

0.044

870 kHz

Metric
.00551
1.4

.140

339

1114

0.26

0.043

900 kHz

36

0.127

414.8

1360

0.21

0.035

1100 kHz

Metric
.00492
1.25

0.125

428.2

1404

0.20

0.034

1150 kHz

37

0.1143

523.1

1715

0.17

0.0289

1350 kHz

Metric
.00441
1.12

0.112

533.8

1750

0.163

0.0277

1400 kHz

38

0.1016

659.6

2163

0.13

0.0228

1750 kHz

Metric
.00394
1

0.1000

670.2

2198

0.126

0.0225

1750 kHz

39

0.0035

0.0889

831.8

2728

0.11

0.0175

2250 kHz

40

0.0031

0.07874

1049

3440

0.09

0.0137

2900 kHz

0.0071

0.0056

0.005

0.0045

0.004

Voltage Drop Calculator by Gerald Newton http://www.electrician2.com


The following calculator calculates the voltage drop, and voltage at the end of the wire
for American Wire Gauge from 4/0 AWG to 30 AWG, aluminum or copper wire. (Note:
It just calculates the voltage drop, consult the above table for rules-of-thumb, or your
local or national electrical code or your electrician to decide what is legal!) Note that the
voltage drop does not depend on the input voltage, just on the resistance of the wire and
the load in amps.
Select Copper or Aluminum
Copper

Select American Wire Gauge (AWG) Size

18 AWG

Select Voltage

120 Volts 1-phase

Enter 1-way circuit


length in feet (the calculation is for the round trip distance)

Enter Load
in amps

Voltage drop

Voltage at load end of circuit

Per Cent voltage drop

Wire cross section in circular mils

This chart of American Wire Gauge (AWG) wire sizes and rated ampacities is data intended for the
pleasure of our readers only. Typographical errors, etc. are probable, since the typist is not a
professional (our CEO). Please point out errors. The data listed are incomplete and should be used
as a guideline only. Please contact manufacturers for the latest data.

Conductor size
It should be common-sense knowledge that liquids flow through large-diameter pipes easier than they do through small-diameter pipes (if you would
like a practical illustration, try drinking a liquid through straws of different diameters). The same general principle holds for the flow of electrons through
conductors: the broader the cross-sectional area (thickness) of the conductor, the more room for electrons to flow, and consequently, the easier it is for
flow to occur (less resistance).
Electrical wire is usually round in cross-section (although there are some unique exceptions to this rule), and comes in two basic varieties: solid and
stranded. Solid copper wire is just as it sounds: a single, solid strand of copper the whole length of the wire. Stranded wire is composed of smaller
strands of solid copper wire twisted together to form a single, larger conductor. The greatest benefit of stranded wire is its mechanical flexibility, being
able to withstand repeated bending and twisting much better than solid copper (which tends to fatigue and break after time).
Wire size can be measured in several ways. We could speak of a wire's diameter, but since its really the cross-sectional area that matters most
regarding the flow of electrons, we are better off designating wire size in terms of area.

The wire cross-section picture shown above is, of course, not drawn to scale. The diameter is shown as being 0.1019 inches. Calculating the area of the
cross-section with the formula Area = r2, we get an area of 0.008155 square inches:

These are fairly small numbers to work with, so wire sizes are often expressed in measures of thousandths-of-an-inch, or mils. For the illustrated
example, we would say that the diameter of the wire was 101.9 mils (0.1019 inch times 1000). We could also, if we wanted, express the area of
the wire in the unit of square mils, calculating that value with the same circle-area formula, Area = r 2:

However, electricians and others frequently concerned with wire size use another unit of area measurement tailored specifically for wire's circular crosssection. This special unit is called the circular mil (sometimes abbreviated cmil). The sole purpose for having this special unit of measurement is to
eliminate the need to invoke the factor (3.1415927 . . .) in the formula for calculating area, plus the need to figure wireradius when you've been
given diameter. The formula for calculating the circular-mil area of a circular wire is very simple:

Because this is a unit of area measurement, the mathematical power of 2 is still in effect (doubling the width of a circle will always quadruple its area,
no matter what units are used, or if the width of that circle is expressed in terms of radius or diameter). To illustrate the difference between
measurements in square mils and measurements in circular mils, I will compare a circle with a square, showing the area of each shape in both unit
measures:

And for another size of wire:

Obviously, the circle of a given diameter has less cross-sectional area than a square of width and height equal to the circle's diameter: both units of
area measurement reflect that. However, it should be clear that the unit of "square mil" is really tailored for the convenient determination of a square's
area, while "circular mil" is tailored for the convenient determination of a circle's area: the respective formula for each is simpler to work with. It must
be understood that both units are valid for measuring the area of a shape, no matter what shape that may be. The conversion between circular mils and
square mils is a simple ratio: there are (3.1415927 . . .) square mils to every 4 circular mils.
Another measure of cross-sectional wire area is the gauge. The gauge scale is based on whole numbers rather than fractional or decimal inches. The
larger the gauge number, the skinnier the wire; the smaller the gauge number, the fatter the wire. For those acquainted with shotguns, this inverselyproportional measurement scale should sound familiar.
The table at the end of this section equates gauge with inch diameter, circular mils, and square inches for solid wire. The larger sizes of wirereach an
end of the common gauge scale (which naturally tops out at a value of 1), and are represented by a series of zeros. "3/0" is another way to represent

"000," and is pronounced "triple-ought." Again, those acquainted with shotguns should recognize the terminology, strange as it may sound. To make
matters even more confusing, there is more than one gauge "standard" in use around the world. For electrical conductorsizing,
the American Wire Gauge (AWG), also known as the Brown and Sharpe (B&S) gauge, is the measurement system of choice. In Canada and Great
Britain, the British Standard Wire Gauge (SWG) is the legal measurement system for electrical conductors. Other wire gauge systems exist in the world
for classifying wire diameter, such as the Stubs steel wire gauge and the Steel Music Wire Gauge (MWG), but these measurement systems apply to nonelectrical wire use.
The American Wire Gauge (AWG) measurement system, despite its oddities, was designed with a purpose: for every three steps in the gauge
scale, wire area (and weight per unit length) approximately doubles. This is a handy rule to remember when making rough wire size estimations!
For very large wire sizes (fatter than 4/0), the wire gauge system is typically abandoned for cross-sectional area measurement in thousands of circular
mils (MCM), borrowing the old Roman numeral "M" to denote a multiple of "thousand" in front of "CM" for "circular mils." The following tableof wire sizes
does not show any sizes bigger than 4/0 gauge, because solid copper wire becomes impractical to handle at those sizes. Strandedwire construction is
favored, instead.

WIRE TABLE FOR SOLID, ROUND COPPER CONDUCTORS


Size
Diameter
Cross-sectional area
Weight
AWG
inches
cir. mils
sq. inches lb/1000 ft
===============================================================
4/0 -------- 0.4600 ------- 211,600 ------ 0.1662 ------ 640.5
3/0 -------- 0.4096 ------- 167,800 ------ 0.1318 ------ 507.9
2/0 -------- 0.3648 ------- 133,100 ------ 0.1045 ------ 402.8
1/0 -------- 0.3249 ------- 105,500 ----- 0.08289 ------ 319.5
1
-------- 0.2893 ------- 83,690 ------ 0.06573 ------ 253.5
2
-------- 0.2576 ------- 66,370 ------ 0.05213 ------ 200.9
3
-------- 0.2294 ------- 52,630 ------ 0.04134 ------ 159.3
4
-------- 0.2043 ------- 41,740 ------ 0.03278 ------ 126.4
5
-------- 0.1819 ------- 33,100 ------ 0.02600 ------ 100.2
6
-------- 0.1620 ------- 26,250 ------ 0.02062 ------ 79.46
7
-------- 0.1443 ------- 20,820 ------ 0.01635 ------ 63.02
8
-------- 0.1285 ------- 16,510 ------ 0.01297 ------ 49.97
9
-------- 0.1144 ------- 13,090 ------ 0.01028 ------ 39.63
10 -------- 0.1019 ------- 10,380 ------ 0.008155 ----- 31.43
11 -------- 0.09074 ------- 8,234 ------ 0.006467 ----- 24.92
12 -------- 0.08081 ------- 6,530 ------ 0.005129 ----- 19.77
13 -------- 0.07196 ------- 5,178 ------ 0.004067 ----- 15.68
14 -------- 0.06408 ------- 4,107 ------ 0.003225 ----- 12.43
15 -------- 0.05707 ------- 3,257 ------ 0.002558 ----- 9.858
16 -------- 0.05082 ------- 2,583 ------ 0.002028 ----- 7.818
17 -------- 0.04526 ------- 2,048 ------ 0.001609 ----- 6.200
18 -------- 0.04030 ------- 1,624 ------ 0.001276 ----- 4.917
19 -------- 0.03589 ------- 1,288 ------ 0.001012 ----- 3.899
20 -------- 0.03196 ------- 1,022 ----- 0.0008023 ----- 3.092
21 -------- 0.02846 ------- 810.1 ----- 0.0006363 ----- 2.452
22 -------- 0.02535 ------- 642.5 ----- 0.0005046 ----- 1.945
23 -------- 0.02257 ------- 509.5 ----- 0.0004001 ----- 1.542
24 -------- 0.02010 ------- 404.0 ----- 0.0003173 ----- 1.233
25 -------- 0.01790 ------- 320.4 ----- 0.0002517 ----- 0.9699
26 -------- 0.01594 ------- 254.1 ----- 0.0001996 ----- 0.7692
27 -------- 0.01420 ------- 201.5 ----- 0.0001583 ----- 0.6100
28 -------- 0.01264 ------- 159.8 ----- 0.0001255 ----- 0.4837
29 -------- 0.01126 ------- 126.7 ----- 0.00009954 ---- 0.3836
30 -------- 0.01003 ------- 100.5 ----- 0.00007894 ---- 0.3042
31 ------- 0.008928 ------- 79.70 ----- 0.00006260 ---- 0.2413
32 ------- 0.007950 ------- 63.21 ----- 0.00004964 ---- 0.1913
33 ------- 0.007080 ------- 50.13 ----- 0.00003937 ---- 0.1517
34 ------- 0.006305 ------- 39.75 ----- 0.00003122 ---- 0.1203
35 ------- 0.005615 ------- 31.52 ----- 0.00002476 0.09542
36 ------- 0.005000 ------- 25.00 ----- 0.00001963 0.07567
37 ------- 0.004453 ------- 19.83 ----- 0.00001557 0.06001
38 ------- 0.003965 ------- 15.72 ----- 0.00001235 0.04759

39
40
41
42
43
44

-------------------------------------

0.003531
0.003145
0.002800
0.002494
0.002221
0.001978

-------------------------------------

12.47
9.888
7.842
6.219
4.932
3.911

-------------------

0.000009793
0.000007766
0.000006159
0.000004884
0.000003873
0.000003072

0.03774
0.02993
0.02374
0.01882
0.01493
0.01184

For some high-current applications, conductor sizes beyond the practical size limit of round wire are required. In these instances, thick bars of solid
metal called busbars are used as conductors. Busbars are usually made of copper or aluminum, and are most often uninsulated. They are physically
supported away from whatever framework or structure is holding them by insulator standoff mounts. Although a square or rectangular cross-section is
very common for busbar shape, other shapes are used as well. Cross-sectional area for busbars is typically rated in terms of circular mils (even for
square and rectangular bars!), most likely for the convenience of being able to directly equate busbar size with round wire.

REVIEW:
Electrons flow through large-diameter wires easier than small-diameter wires, due to the greater cross-sectional area they have in which to
move.
Rather than measure small wire sizes in inches, the unit of "mil" (1/1000 of an inch) is often employed.
The cross-sectional area of a wire can be expressed in terms of square units (square inches or square mils), circular mils, or "gauge" scale.
Calculating square-unit wire area for a circular wire involves the circle area formula:

Calculating circular-mil wire area for a circular wire is much simpler, due to the fact that the unit of "circular mil" was sized just for this
purpose: to eliminate the "pi" and the d/2 (radius) factors in the formula.

There are (3.1416) square mils for every 4 circular mils.


The gauge system of wire sizing is based on whole numbers, larger numbers representing smaller-area wires and vice versa. Wires thicker
than 1 gauge are represented by zeros: 0, 00, 000, and 0000 (spoken "single-ought," "double-ought," "triple-ought," and "quadruple-ought."
Very large wire sizes are rated in thousands of circular mils (MCM's), typical for busbars and wire sizes beyond 4/0.
Busbars are solid bars of copper or aluminum used in high-current circuit construction. Connections made to busbars are usually welded or
bolted, and the busbars are often bare (uninsulated), supported away from metal frames through the use of insulating standoffs.

Wire Size
Recently, there has been numerous questions on this board concerning the proper type or size of AC power
cable to use with different amounts of equipment. It is very important to use the correct size cable to insure
all the power will be available to your equipment and there is no danger of a fire or short from your cables.
Here is a Cable/Current table to help you select the proper one to use in your application.
Wire Size (AWG) 2 Conductor 3 Conductor 4 Conductor
10
30Amp
25
20
12
25
20
16
14
18
15
12
16
13
10
8
18
10
7
6
Notice that the smaller the AWG number, the more current it can handle. All Extension Cords are required to
list the wire gauge. That will tell you the amount of current they can safely handle.
The wire in the above example is Copper type and of the same temperature rating. All currents listed are for
Ambient temperature. Keep in mind that there are also many different type of insulation material that will
determine the temperature rating. The wire may not be pure copper but an alloyed of aluminum, nickel, tin
and copper.

Standard cable, as used in home and general construction, is classified by the wire size, number of wires,
insulation type and dampness condition of the wire environment.
Example: a cable with the code "12/2 with Ground Type UF 600V (UL)" has the following
specifications:
1. Wire size is 12 gauge (minimum required size for homes today).
2. The "/2" indicates there are two wires in the cable.
3. "Ground" indicates there is a third wire in the cable to be used as a grounding
wire.
4. "Type UF" indicates the insulation type and acceptable dampness rating.
5. "600V" means the wire is rated at 600 volts maximum.
6. "UL" indicates the wire has been certified by Underwriters Laboratory to be
safe.
Standard wire color codes are very different between electronic circuitry and
household 110 Volt AC wiring.
Household wiring (or other AC applications in the 100+ volt range) use the following color codes:
BLACK "Hot" wire. Connected to Brass colored terminal.
GREEEN "Ground" wire. Also called chassis ground.
RED "Traveler" wire. Used for 3-ways switches.
WHITE "Neutral" wire. Connected to silver colored terminal.
VOLTAGE DROP vs. WIRE SIZE
Voltage drop is the amount of voltage lost over the length of a circuit. Voltage drop changes as a function of
the resistance of the wire and should be less than 2% if possible. If the drop is greater than 2%, efficiency of
the equipment in the circuit is severely decreased and life of the equipment will be decreased. As an
example, if the voltage drop on an incandescent light bulb is 10%, the light output of the bulb decreases over
30%!
Voltage drop can be calculated using Ohmss Law, which is:
Voltage Drop = Current in amperes x Resistance in ohms.
For example, the voltage drop over a 200 foot long, #14 copper wire, power line supplying a 1000 watt
floodlight is calculated as follows:
Current = 1000watts/120volts = 8.33 amperes
Resistance of #14 copper wire = 2.58ohms/1000feet
Resistance of powerline=2 x 200ft x 0.00258ohms/ft=1.032ohms
Voltage drop = 8.33 amperes x 1.032 ohms = 8.60 volts
Percent voltage drop = 8.60volts/120volts = 7.2%
The 7.2% drop is over the maximum 2% so either the wattage of the bulb must be decreased or the diameter
of the wire must be increased (a decrease in wire gauge number). If #9 copper wire were used in the above
example, the voltage drop would have only been 2.2%.
A more commonly used method of calculating voltage drop is as follows:
Voltage Drop =

K x 2 x Wire length in ft. x Current in amperes


------------------------------------------------Wire area in circular mils

K = Specific resistivity in ohm circular mils/foot


K = 11 for copper wire loaded at 50% of capacity.

K = 12 for copper wire loaded to 50-100% capacity.


K = 18 for aluminum wire
Using values from the Ohms Law example above: #14 copper wire has an area of 4110 circular mils, then
voltage drop = (11 x 2 x 200 x 8.33) / 4110 = 8.92volts = 8.92volts/120volts = 7.4%.
An interesting corollary to the above example is that if the line voltage doubles (240 volts instead of
120volts), the voltage drop decreased by a factor of 4. That means that a line can carry the same power 4
times further! Higher voltage lines are more efficient. Thats why voltage is so high (50,000volts) for power
transmission lines.
I hope this help explain many questions about AC power and cables.

WIRING TABLE NEC


AWG American Wire Gauge to mm2 WIRING

Short Table

AWG

mm2

AWG

mm2

AWG

mm2

AWG

mm2

30

0.05

18

0.75

16

4/0

120

28

0.08

17

1.0

25

300MCM

150

26

0.14

16

1.5

35

350MCM

185

24

0.25

14

2.5

50

500MCM

240

22

0.34

12

4.0

1/0

55

600MCM

300

21

0.38

10

6.0

2/0

70

750MCM

400

20

0.50

10

3/0

95

1000MCM

500

AWG American Wire Gauge / Diameter / Resistance


Used in the United States and other countries as a standard method of denoting wire diameter. The higher the number the thinner the wire. Thicker wire is generally capable of
carrying larger amount of current over greater distances with less loss (though there are other things that cause current loss in wire). Sometimes the loss of cables is rated in
Ohms per one thousand feet and for a particular type of wire the lower gauges (larger wires) have less resistance to current flow. (Sweetwater Archive)
See: Maximum current load

AWG American Wire Gauge Table

AWG

Diameter

Diameter

mm

inch

Square

mm2

Resistance

Resistance

ohm/km

ohm/1000 feet

46

0,04

0,0013

13700

44

0,05

0,0020

8750

42

0,06

0,0028

6070

41

0,07

0,0039

4460

40

0,08

0,0050

3420

39

0,09

0,0064

2700

Basic wire sizing guide for US 120 and 240 volts


Useful info:
# = American Wire Gauge (AWG), the lower the number the larger the wire guage.
"Service cable" is large insulated stranded copper cable (usually refers to single #4 wire and up).
Most house hold circuits (Typically 15 - 30 amp) can safely handle 95% to 100% of its max rating - but only for an hour or so at a time. Loads that require long
periods of 'on' time (like an air conditioner, ballasts, etc) should not exceed 80% to 85% of the max rated load of the wire/cable. The known safe capacity that the
National Electric Code (NEC) recommends at 100%, is actually 80% of load.
99.9% of the time when you get into "insulated" #8 and bigger wire, its most likely going to be stranded (just like its big sister "Service cable"). You can usually get
your basic sheathed xx/2 and xx/3 cable up to 6 guage. If you need larger than #8 or #6 though, you will have to buy service or "service type" cable. This can
cause two problems. One: very high cost on long runs. Two: the cable might not fit the appropriately-sized breaker on a long run. This is why its wise to opt for
putting your ballast on 240V when 2400+ watts of light power is needed on a single circuit.
#4 and above = Cable
1/0 and 2/0 are Service cable
120V (US) (@ 80% max load)
(50ft run or less)
Gauge

Amps

Watts

#16

1080

#14

12

1440

#12

16

1920

#10

24

2880

#8

32

3840

#6

40

4800

#4

48

5760

Gauge

Amps

Watts

#16

2160

#14

12

2880

#12

16

3840

#10

24

5760

#8

32

7680

#6

40

9600

#4

48

11520

240V (US) (@ 80% max load)


(50ft run or less)

Run Length
Amps

100

150

150' - 200'

200- 250'

250'

250' - 300'

300

400'

400-500

500'

300' - 400'
12

#12

#10

#8

#6

16

#10

#8

#6

24

#8

#6

#4

32

#6

#4

#2

40

#6

#4

#4
#4

#2

#2
#2
#1

#1

#1/0

#1/0

#2/0

Note:
For every extra 50 feet of cable/wire up to #8 normally you upgrade to the next size, consult you local codes if your unsure about double and triple length runs.
Ex: #6 is sometimes mandatory for a 200 foot 12 amp run but can be used up to 300 feet on a 12 amp circuit.
Note:
Each time an additional plug is used in line of the run using 80% safe load, subtract an additional 2% from the over all power usage (80% to 78%).
Ex: One plug into the wall counts as your one 'free' plug.
WARNING: extension cords ARE included into the total length from breaker box (+25 feet and one gauge up), if intended for continuous use at said MAX safe
power usage.
In addition, you need to make sure you getting what is actually equal to said gauge (if your making you own cord from something like SJO cable).
Recently, I have found that some places go by size and not current. A 12 gauge standard wire is actually the size of 10 gauge solid. This is to make up for it not
being a solid connector. Bring something with you to compare wire size with what's printed/stamped on the sheeting. It should be one gauge bigger in size than
what's on the sheeting.
Ex: If you have a 1000W light and are using a 12 amp circuit, you should use a 15amp #12 extension cord no longer than 25 feet.

This info isnt complete and probably doesnt apply to many, cuz if your thinking this big you should already have a general understanding of codes and loads.
#4 (approx 65-75A each) used for 100-115 amp service
#2 (approx 90A each) used for 125-150 amp service
#1/0 (approx 150A each) used for 200 amp service
#2/0 (approx 175A each) typically for industrial or vary long run with a large load. 300-350 amp service
#0/3 (approx 200A each) typically for industrial or vary long run with a large load. 400 amp service
Service cable is specifically designed for extra service lines and or extra long (In structure or over-head) runs. 1/0 Gauge I believe is the only service cable (or
cable) sold connected as x/3 (retail), provides a path fore both hots, the neutral and ground.
Please specify wire / insulation /cable type. Tables fairly meaningless without.
There is no accurate rule of thumb for distance / wire upsizing. I'm afraid one must do the math here, particularly with the price of wire what it is.
"Recently, I have found that some places go by size and not current. A 12 gauge standard wire is actually the size of 10 gauge solid. This is to make up for it not
being a solid connector. Bring something with you to compare wire size with what's printed/stamped on the sheeting. It should be one gauge bigger in size than
what's on the sheeting."
Stranded wire is physically larger, but uses the same amount of copper. Carries the same amount of current. Solid wire dimension gauges are fairly worthless for
measuring stranded wire.
Stranded wire exhibits better electrical performance in AC circuits.

This page is to provide a single place to look to for what the safe rated capacities of various size
wires in general use. These are general guidelines - check with the wire manufacturer or standards
body controlling your installation for any additional specifications. Keep in mind that temperature
and environment have a dramatic effect on these ratings, and that for wiring it's much better to err
on the side of too large a wire than too small.
This page started as a page for 12V DC automotive use, but has grown over time to include a more
general set of information on wire sizing. I've tried to add some basic explanations of what matters
when sizing a wire and to avoid using too many details specific to certain applications. The actual
formulas used to figure this out can be very complex - for example the National Electrical Code
specifies the wire sizes to be used in excruciating detail based on years of actual research on what
happens to wires in The Real World. Keeping up with all those details can be very hard, but the
basic principles are pretty straightforward. My goal for this page is to expose you to those basic
concepts, and at the end to give a basic "rule of thumb" chart for folks to start out with.
This page was created to help explain concepts and give an overview of wire capacity and what is
factored into deciding on the wire size to use in a given application. This page should not to be
considered an authoritative source of exact numbers on what wire size to use. Consult other
sources such as wiring codes and manufacturers recommendations on the piece of equipment you
are installing for more details. I am not telling you what wire size to use - the information here is
provided as-is and without any guarantee as to it's accuracy or completeness. Any issues caused by
the use of this information are not my fault - be smart, use common sense, and use this
information at your own risk.

Measuring Wire Capacity


The amount of power a wire can safely carry is related to how hot it can safely get. All wires have
resistance, and as power flows through a wire that resistance causes heat - and it can be quite a
bit of heat. The more power you put through a wire, the hotter it gets. Insulation breaks down as it
gets hot, and at some point it will melt away leaving the wire exposed to whatever is around it other wires, grounded metal, people, etc. The heat can even be enough to start a fire in the

surrounding material in some cases. Electrical fires are nasty and tend to start in the hardest to
reach places - where the most heat builds up back in dark corners and tight spaces. This is why
using the right size wires is important for your safety and for safety of others using your wiring
work.
In some respects, the capacity of a wire is actually best measured in watts, not amperage. Why?
Because a watt is a unit or power that is a combination of amperage (volume), voltage (pressure),
and resistance to the power flowing through that wire. Watts measure the amount of power (aka,
heat) a wire can safely dissipate. However, most wire charts are done in amps. This is unfortunate
because it means the wire chart is sort of assumed to be at a single voltage level. For most usage,
this is fine because the chart has an assumed usage. As an example, charts for amperage ratings of
of various sizes wires for 110V AC house current charts are popular and reasonably well-known. On
the other hand, the amperage ratings are very different for common/typical 12V DC automotive
usage. For example, a 12 gauge wire is commonly rated at 20A for 110V AC home usage, but in
automotive 12V DC use 12 gauge wire is commonly used for circuits carrying 60A! A prime example
would be the main charging wire from the alternator to the battery and out to the main electrical
circuits of the car. I thought I had a satisfactory explanation posted here previously, but a few folks
took aim at it and blew gaping holes in my understanding - without actually explaining what I was
trying to understand or explain here. As of yet, I have not gotten a satisfactory explanation for this
discrepancy. No one I've talked to as of yet has been able to explain it to me, but if you think you
know the magic answer, please let me know. Maybe I'm missing something obvious. Maybe I'm just
not understanding this as well I as think I am. Who knows... At any rate, the chart below reflects
the difference in 110V AC vs. 12V DC usage, even though I'm still at a loss to explain the details.
Remember, if in doubt, it's always better to put in too big of a wire than too small of a wire.

Stranded vs. Solid Wire


This one is a bit of a mind-boggler, but it's important. When electricity flows through a wire, it
mostly flows on the surface of the wire, not through the middle. This effect is more pronounced on
high frequency AC than it is on DC or low frequency AC. This means that a "wire" of a given size
that made up of many smaller strands can carry more power than a solid wire - simply because the
stranded wire has more surface area. This is one reason why battery cables in your car and welding
cables are made up of many very fine strands of smaller wire - it allows them to safely carry more
power with less of that power being dissipated as heat. However, this "skin" effect is not as
pronounced in a typical 12V DC automotive application, and the wire and cable used there is
stranded for flexibility reasons.
When looking at a chart or description of wire capacity, take note of whether it is referring to
stranded or solid wire - some charts may not specify but instead assume a default based on the
typical wiring used in a given application. For example, almost all automotive wiring is stranded
while almost all home wiring is solid. For most applications, flexibility or the lack thereof will be
more important, but for very high frequency AC applications, stranded wire might be a

requirement.

Open Air vs. Bundles and/or Conduits


Heat is the primary determiner of the maximum amount of power any wire can carry, and the
ability of that wire to dissipate that heat has a large impact on the final rating. Wires that are run
in bundles (such as in a wiring harness or wiring conduit) cannot dissipate heat as easily as a single
wire run in "open air", and as such must be "de-rated" to less than their maximum value to account
for this. Also, wires that are run in areas that are unusually hot (such as in an attic or in an engine
compartment) may need similar de-ratings. If both situations are encountered together (bundled
wires in an unusually hot environment) then you need to de-rate for both factors and the capacity
is further reduced.
In a car, almost all wiring is run in a bundle, and much of it runs near the engine. In a house, a lot
of wiring typically runs through the attic, often in a bundle/group and sometimes in a conduit. Pay
attention to this and size your wires appropriately.

Wire Length
Since all wires have resistance, the longer the wire, the greater the resistance. This means that for
longer wiring runs you need to use a larger wire to compensate. This phenomenon is often referred
to as "voltage drop", and for lower voltage automotive systems, the loss of 2V or even 1V can be
significant. On longer wire runs, plan on using a larger size wire. There are specific voltage drop
calculations that depend on the wire size in use, the length of the wire, the load applied, and the
voltage in use. The National Electric Code has tons of charts for this, but there's a nifty online
voltage drop calculator that one of my readers pointed out to me that does 120V AC as well as 12V
DC - and even 6V DC. You'd be surprised at some of the voltage drops you can find just form the
wiring in use, so experiment with the calculator a bit to see if it's worth going to the next highest
size wire in your application. On automotive applications of only 12V, losing a single volt of power
in the wire is a whopping 8% loss, so it can be a big deal for voltage critical applications like your
headlights where more voltage = more light. Kudos to Ron White for providing me with the link to
that calculator, and kudos to the folks over at PowerStream.com for putting that calculator and
other data online.

Duration of Usage
Some electrical loads are continuous for long periods of times (like a light in your house or the
headlights on your car) and some are much more intermittent (like a garbage disposal in your house
or the starter in your car). This affects the wire size used - the longer a wire is in use, the more
heat it will tend to retain. A wire for something that is only used for short periods (like the starter
in your car) does not need quite as large of a wire as something that will be in use for very long
periods of time. This means that for long-duration uses, you must de-rate the wire even further

and use a larger size.

Electrical Calculations
There are four basic units of measurement for electricity:

Power, measured in Watts, commonly referred to as "P"

Current, measured in Amps, commonly referred to as "I"

Voltage, measured in Volts, commonly referred to as "V"

Resistance, measured in Ohms, commonly referred to as "R"

There are a number of formulas that relate each of these four things - they all change in
relationship to one another such that if you know any two you can calculate the other two. Lots of
folks on the Internet have easy-to use calculators that allow you to do this online
- http://www.sengpielaudio.com/calculator-ohm.htm is one. The formula wheel below was on
their website and presents the info in a pretty easy to understand format.

Capacity Chart
This chart is a simple "max capacity" chart for a short wire run. Increase the wire size for long runs
- for example the wires running to the back of a vehicle to power the taillights may need to be one
size larger to account for the length.
Gauge

110V

12V

22

5A

5A

20

7.5A

8A

18

10A

10A

16

13A

20A

14

17A

40A

12

23A

60A

10

33A

100A

46A

150A

60A

??A

80A

??A

100A

??A

125A

??A

150A

??A

Chart Notes

This 110V column in this chart was provided by one of my readers and according to him it is based on
the data in The Howard W. Sams Engineering Staff fifth edition 1983 for stranded copper wire when
used in a conduit or bundle. (Open air ratings would be higher, solid copper wire ratings might be
slightly lower.) This data seems in line with commonly accepted usage for 120/220V home electrical
wiring.

The 12V column is based on various sources I have found across the Internet combined with the
accepted usage in various vehicles I have worked on. I am generally a bit skeptical of the max
capacity the sources I found claimed for some of the smaller wire sizes. For example, 16 gauge wire
is mighty thin to run 20A through for even a short distance, and this chart is
a conservative interpretation of the data I found out there. Some data had the max capacity even
higher than this - yikes!

The values here for 12V usage are not yet certified to be correct/valid/safe - they are my ballpark
figures based on what I believe to be true based on what I have learned. Consult other sources of
information for your specific application for more details.

Wire Type and Sizing Considerations


Written by Richard
Friday, 10 August 2007

Wire Type and Sizing Considerations

When a professional electrician looks at a job to wire a house or a new circuit


in any structure the primary consideration in the wiring job is the size and type
of wire to be used for job. The same for a plumber when looking at a job the
plumber will size the pipes based on the number of gallons needed to carry the
proper amount of water to its destination. If the pipe is too small then the water
needed will not reach its destination. This is almost the same for electrical wire
except under-sizing electrical wire is dangerous. Electrical wire carries voltage
but it is the current rating of the power loads which is the primary factor in
determining the size and type of wire to be used for the job. The current or
amps, like the water pipe, is measured by how much flow there is in the wire.
If the wire is too small and the flow too fast then wire gets hot. If it gets too
hot then the insulation melts and a dangerous condition exists. If the wire runs
for a prolonged period of time at a higher than rated temperature there are also
corrosive effects at terminal connections. Eventually the corrosion and the
excessive heat will cause the wire to become brittle. Solid wire will become
brittle enough to eventually break off completely while stranded wire will lose
strands one strand at a time from this effect. This causes the wire to become
smaller and the heat increases. Eventually the current becomes too much for
the wire and it breaks off again creating a dangerous condition. The equipment
or device being supplied electricity from this wire, when it breaks, ceases to
function while a live wire is hanging inside a control panel or other panel. This
is why it is very important to properly size electrical wires for any type of
electrical work and not to overload existing circuits in homes and businesses.
Imagine a wire inside of a wall getting too hot and the insulation melting. This
creates a dangerous electrical situation and also is a fire hazard.

Wire Type for the Application

One other consideration in electrical wiring is choosing the right wire type.
This usually refers to the insulation of the wire and its temperature rating.
Selecting the approapiate insulation type and temperature rating is important
and depnds on the environment and application of where the wire will be used.
Romex is an all purpose wire almost used exclusively in residential wiring
where the heat is not excessive and the wire is not subject to damage. Each
specific type of wire has its own application and temperature rating and must
be used in accordance with the NEC (National Electrical Code). Some wire is
rated for direct burial underground while other wire is not rated for direct
burial and must be used on conduit when run underground. Always refer to the
NEC or your local electrical inspector for rules pertaining to the type of wire
and the application.

Wire Sizing Chart

The following chart shows the proper wire size or wire guage ( awg ) for the
desired current or amperage.
* The national electric code (NEC) specifies that the over-current protection
device (breaker, fuse, or motor over-load) not exceed 15A for 14 AWG wire,
20A for 12 AGW wire, and 30A for 10 AGW wire.

Maximum Ampacity for Copper


and Aluminum Wire
Copper

Aluminum

Wire Size
167 (75C) 194 (90C) 167 (75C) 194 (90C)

*14

20 (*15)

25

*12

25 (*20)

30

20

25

*10

35 (*30)

40

30

35

50

55

40

45

65

75

50

60

85

95

65

75

115

130

90

100

Wire Size and Amp Ratings

Copper

Wire Gauge
Size

Aluminum

60C
(140F)

75C
(167F)

90C
(194F)

75C
(167F)

90C
(194F)

NM-B

THW

THWN-2

THW

XHHW-2

UF-B

THWN

THHN

THWN

THHN

SE

XHHW-2

SE

THWN-2

USE

USE-2

USE

XHHW

XHHW

14

15

15

15

---

---

12

20

20

20

15

15

10

30

30

30

25

25

40

50

55

40

45

55

65

75

50

60

70

85

95

65

75

85

100

110

75

85

95

115

130

90

100

---

130

150

100

115

1/0

---

150

170

120

135

2/0

---

175

195

135

150

3/0

---

200

225

155

175

4/0

---

230

260

180

205

250

---

255

290

205

230

300

---

285

320

230

255

350

---

310

350

250

280

500

---

380

430

310

350

600

---

420

475

340

385

750

---

475

535

385

435

1000

---

545

615

445

500

WARNING! Installation of electrical wire can be hazardous, if done


improperly, can result in personal injury or property damage. For
safe wiring practices, consult the National Electrical Code and
your local building inspector.

American Wire Gauge Chart

AWG

DIAMETER

AREA

WEIGHT
(KILOGRAMS PER METER)

TURNS OF WIRE
(PER INCH)

0000 (4/0)

0.46" (11.7mm)

212 kcmil (107mm)

0.953

2.17

000 (3/0)

0.41" (10.4mm)

168 kcmil (85 mm)

0.756

2.44

00 (2/0)

0.365" (9.27mm)

133 kcmil (67.4 mm)

0.599

2.74

0.325" (8.25 mm)

106 kcmil (53.5 mm)

0.475

3.08

0.289" (7.35 mm)

83.7 kcmil (42.4 mm)

0.377

3.46

0.258" (6.54 mm)

66.4 kcmil (33.6 mm)

0.299

3.88

0.229" (5.83 mm)

52.6 kcmil (26.7 mm)

0.237

4.36

0.204" (5.19 mm)

41.7 kcmil (21.2 mm)

0.188

4.89

0.182" (4.62 mm)

33.1 kcmil (16.8 mm)

0.149

5.5

0.162" (4.12 mm)

26.3 kcmil (13.3 mm)

0.118

6.17

0.144" (3.66 mm)

20.8 kcmil (10.5 mm)

0.0938

6.93

0.128" (3.26 mm)

16.5 kcmil (8.37 mm)

0.0744

7.78

0.114" (2.91 mm)

13.1 kcmil (6.63 mm)

0.059

8.74

10

0.102" (2.59 mm)

10.4 kcmil (5.26 mm)

0.0468

9.81

11

0.0907" (2.30 mm)

8.23 kcmil (4.17 mm)

0.0371

11

12

0.0808" (2.05 mm)

6.53 kcmil (3.31 mm)

0.0294

12.4

13

0.0720" (1.83 mm)

5.18 kcmil (2.62 mm)

0.0234

13.9

14

0.0641" (1.63 mm)

4.11 kcmil (2.08 mm)

0.0185

15.6

15

0.0571" (1.45 mm)

3.26 kcmil (1.65 mm)

0.0147

17.5

16

0.0508" (1.29 mm)

2.58 kcmil (1.31 mm)

0.0116

19.7

17

0.0453" (1.15 mm)

2.05 kcmil (1.04 mm)

0.00922

22.1

18

0.0403" (1.02 mm)

1.62 kcmil (0.823 mm)

0.00732

24.8

19

0.0359" (0.912 mm)

1.29 kcmil 0.653 mm)

0.0058

27.9

20

0.032" (0.812 mm)

1.02 kcmil 0.518 mm)

0.0046

31.3

21

0.0285" (0.723 mm)

0.810 kcmil (0.410 mm)

0.00365

35.1

22

0.0253" (0.644 mm)

0.642 kcmil (0.326 mm)

0.00289

39.5

23

0.0226" (0.573 mm)

0.509 kcmil (0.258 mm)

0.00229

44.3

24

0.0201" (0.511 mm)

0.404 kcmil (0.205 mm)

0.00182

49.7

25

0.0179" (0.455 mm)

0.320 kcmil (0.162 mm)

0.00144

55.9

26

0.0159" (0.405 mm)

0.254 kcmil (0.129 mm)

0.00114

62.7

27

0.0142" (0.361 mm)

0.202 kcmil (0.102 mm)

0.000908

70.4

28

0.0126" ( 0.321 mm)

0.16 kcmil (0.081 mm)

0.00072

79.1

29

0.0113" (0.286 mm)

0.127 kcmil (0.0642 mm)

0.000571

88.8

30

0.01" (0.255 mm)

0.101 kcmil (0.0509 mm)

0.000453

99.7

31

0.00893" (0.227 mm)

0.0797 kcmil (0.0404 mm)

0.000359

112

32

0.00795" (0.202 mm)

0.0632 kcmil (0.032 mm)

0.000285

126

33

0.00708" (0.18 mm)

0.0501 kcmil (0.0254 mm)

0.000226

141

34

0.00630" (0.16 mm)

0.0398 kcmil (0.0201 mm)

0.000179

159

35

0.00561" (0.143 mm)

0.0315 kcmil (0.0160 mm)

0.000142

178

36

0.005" (0.127mm)

0.025 kcmil (0.0127 mm)

0.000113

200

37

0.00445" (0.113 mm)

0.0198 kcmil (0.01 mm)

0.0000893

225

38

0.00397" (0.101 mm)

0.0157 kcmil (0.00797 mm)

0.0000708

252

39

0.00353" (0.0897 mm)

0.0125 kcmil (0.00632 mm)

0.0000562

283

40

0.00314" (0.0799 mm)

0.00989 kcmil (0.00501 mm)

0.0000445

318

Which wire gauges am I most likely to encounter?


Even though 44 different wire diameters are recognized within the AWG standard, theyre not all widely used, and most people are likely to
encounter only a small range of them. Below are a few common cable types we use ever day, as well as the AWG sizes that correspond to
them:

Speaker Cable: 14 and 16 AWG

Coaxial Cable (for cable TV and a few Ethernet applications): 18 and 20 AWG

Cat 5, Cat 5e, and Cat 6 cables (for LANs and Ethernet): 24 AWG

Telephone Cable: 22 28 AWG

For more great information on American Wire Gauge, including wire diameter formula, check out Wikipedia's section on AWG.

You might also like