Hyamat VP

Type Series Booklet


1953.52-10

Interference suppression Class B

Pressure Boosting Units/Fire-fighting Systems


with Continuously Variable Speed Adjustment
Using Frequency Inverters for each Pump
to DIN 1988

EMC-tested
DIN EN ISO 9001
Illustration shows variant without acoustic cladding

Hyamat VP with Movitec

Fields of Application





Residential buildings
Hospitals
Office buildings
Hotels

Design
 Department stores
 Industry
 and other applications

Fluid Handled

Drinking water, utility water, fire-fighting water, cooling water, where


there is no chemical and mechanical corrosive action on the
system materials.

Operating Data
Capacity Q
Discharge head H
Temperature of
fluid handled
Ambient temperature
System discharge
pressure pd
Inlet pressure pinlet
Supply voltage

*)

up to 200 m3/h, 55 l/s with max. 4 pumps *)


up to 130 m
up to 70 oC
up to 25 oC to DIN 1988 (DVGW)
up to 40 oC
up to 16 bar
up to 10 bar
3/N/PE, AC 400 V, 50 Hz
5-wire system < 2.2 kW

with stand-by pump as peak load pump

Materials
Pumps
Suction/discharge casing
Hydraulic system
Mechanical seal
Spring-loaded ring
Seat ring
Elastomer
Hydraulic Design:
Distributor pipe
Valves
Accumulator
Membrane

stainless steel
stainless steel
to EN 12756
silicon carbide
hard carbon
EPDM

stainless steel
copper-base alloy/brass,
DVGW-approved
connection made of stainless steel
approved for drinking water to
DIN 4807-5

Drive
Electric motor 50 Hz, 2-pole, special KSB model, for three-phase
mains. Standard IEC motors can only be used after consultation with
KSB.

Fully automatic pressure boosting package unit, with 2 to 4 vertical


high-pressure pumps, with continuously variable speed adjustment of
each pump for fully electronic control to ensure the required supply
pressure, with standard volt-free contact for lack of water indication,
general fault indication or reporting of systems availability as well as
live-zero monitoring of the connected sensors.
Design and function as per DIN 1988, Part 5.
Hyamat VP System Equipment (Standard)
- 2- 4 vertical high-pressure centrifugal pumps (standard pumps)
Movitec 2, 4 und 10 with oval flange/
Movitec 18 und 32 with round flange
- Hydraulic components made of stainless steel
- 1 check valve and shut-off element for each pump to DIN / DVGW
- Membrane-type accumulator on the discharge side as control tank
(direct flow) to DIN 4807-5, approved for drinking water
- Pressure transmitter on the discharge pressure side
- Pressure indication via pressure gauge
- Steel baseplate powder-coated/epoxy resin-coated
- Pump sizes 2, 4 and 10 are fixed to the baseplate on
anti-vibration mounts
- Pump sizes 18 and 32 are supplied with level-adjustable feet and
anti-vibration pads (supplied, but not fitted)
- Control cabinet IP 54, EMC interference suppression class B
- Pressure transmitter on the inlet pressure side (dry-running
protection and energy-optimized cut-out of PBU)
- CE certificate
Control cabinet equipment (Standard)
- Manual-0-automatic selector switch
- PLC
- LEDs indicating operational availability and fault of the system
- Frequency inverter for each pump
- Motor protection switch or
safety cut-out for each pump
- Master switch, lockable (repair switch)
- Terminals with identification for all connections
- Circuit diagram acc. to VDE, settings for frequency inverter (FI)
and parts list for electrical parts
- Emergency OFF connection
For supplementary equipment and special designs
see pages 16 to 18.

Hyamat VP

Settings
Set pressure

Standard scope

Extended scope
cf. supplementary equipment

Hyamat VP
with control panel

Hyamat VP
with display and keyboard

Potentiometer on the PLC

Display: Set value in plain language

Inlet pressure >0.5 bar

Pressure transmitter on inlet pressure


side (dry running protection and
energy-optimized cut-out of PBU)

Pressure transmitter on inlet pressure


side (dry running protection and
energy-optimized cut-out of PBU)

Second set value

Activation via customer-provided volt-free Activation via timer in the display set accontact or timer
cordingly or activation via customer-provided volt-free contact or timer
All other values are set at the factory in accordance with the purchase order specifications for
water supply applications.

Reporting
Actual value
Inlet pressure >0.5 bar

Reporting via display, multi-line


(using keyboard)
Pressure gauge
Pressure gauge

Pressure gauge and display


Pressure gauge and display

Operational availability of the system Green lamp


General fault
Red lamp
is triggered in the case of:
- Pump fault
- FI fault (for each pump)
- Sensor fault (live zero)
- Lack of water

Green lamp
Red lamp and plain language

Operation/fault, each pump


Operating hours counter per pump

Indication of flow rate

Display: Status indication


Display: Operating hours with reset
facility
Display: Actual value (approximate)

Reporting via volt-free contacts on isolating terminals


Operational availability of the system NO contact
(trouble-free operation of the system)

NO contact

General fault
is triggered in the case of:
- Pump fault
- FI fault (for each pump)
- Sensor fault (live zero)
- Lack of water
- Power failure
Lack of water
Operation per pump

NC contact

NC contact

NC contact
NO contact, optional

NC contact
NO contact, optional

Fault per pump

NC contact, optional

NC contact, optional

Fault acknowledgement:

Via reset key

Display and keyboard

Supplementary equipment, via timer


Base load pump change-over, this function is triggered via a customer-provided
volt-free contact or timer
(supplementary equipment)
Supplementary equipment - via timer
With optional manual-0-automatic selector switch or operating on the frequency
inverter with open control cabinet

Display: may be set to daily or weekly


Display: may be set to daily or weekly

Miscellaneous
Functional check run
Pump change-over

Second set value


Manual mode

Remote control from control


station

Automatic ON-OFF
Second set value
Emergency OFF
Remote acknowledgement
Functional check run
Pump change-over

Display: may be set to daily or weekly


With optional manual-0-automatic selector switch or manual mode via display
Automatic ON-OFF
Second set value
Emergency OFF
Remote acknowledgement
Functional check run
Pump change-over

Hyamat VP

Dry-running protection if inlet tank is used /


for suction lift operation

Pump / FI

Operation message

Emergency OFF

Pressure switch,
discharge pressure

Flow monitoring,
suction side

Immersion electrodes

Functional check run

Pump change-over

Pressure or float switch,


suction side

Remote acknowledgement

Automatic ON/OFF

Set value change-over

Signal, inlet pressure

Signal, discharge pressure

Terminal Connections

Optional

Optional

Designation

3,2 Hyamat

VP

4 / 0408 / 1,2 - 3,5

Type series
Number of pumps
Pump size
Number of stages
Minimum inlet pressure, bar
Max. effective inlet pressure, bar

Function

Two to four pumps are controlled and monitored by a PLC.


Each pump is connected to a frequency inverter and controlled
by the PLC in order to ensure a constant system discharge
pressure.
As the demand increases or decreases, the peak load pumps
will be switched on and off automatically.
As soon as the demand increases after one pump has been
switched off, another pump which has not been in operation
before is switched on.
After the last pump has been switched off and the demand
increases again, the next pump in line is switched on and
connected to the frequency inverter.
The stand-by pump is also part of the alternating cycle but is
switched on only in case of need.
As a standard, the system is switched on automatically
depending on the pressure; the actual pressure is measured by
an analog pressure measuring device (pressure transmitter).
The function of this pressure transmitter is monitored
(live-zero).
As long as the system is in operation, the pumps are switched
on and off depending on the demand (standard setting).
In this way it is ensured that the individual pumps operate only
in line with the actual demand. The use of speed-controlled
pumps reduces wear as well as the pumps switching frequency

in parallel operation. If a duty pump fails, the next pump will be


switched on immediately. There will a general fault indication
which can be reported via volt-free contacts (e..g. to the control
station).
If the demand drops towards 0, the system slowly approaches
the switch-off point.

Manual Mode

A manual-0-automatic selector switch is available for each


pump installed.
In manual mode, the pumps are operated on the frequency
inverter independently of the installed PLC and run at a
constant speed chosen by the operator. As a standard, they run
at full speed.
For this mode of operation no pressure control and no
lack-of-water monitoring will be effected.
Caution!
Please observe minimum flow rates!
In the case of closed consumer installations, the pumps
produce the max. pressure acc. to the characteristic curve
when running at full speed in manual mode.

Commissioning / Start-up
Commissioning by specialist KSB staff is effected against
extra charge.

Hyamat VP
System Features with Movitec 2, 4 and 10
Equal distribution of
pump operating hours by
automatic pump
change-over

Acoustic cladding
(supplementary equipment)
- Retrofittable and
easy to service
- Protects against
contamination
- Appealing design

Manual-0-automatic
selector switch per pump
Display
(supplementary equipment)
- Operating hours counter
- Flow rate indicator
General fault reporting
via volt-free contact

Automatic matching
to the demand
thanks to a continuously
speed-controlled
base load pump

High operating reliability


thanks to continuous
functional monitoring
of the connected
sensors

Accumulator
to DIN 4807-5,
DVGW-approved

DVGW-tested
valves
Corrosion-resistant
stainless steel piping

Installation free from solid-borne


sound transmission due to antivibration mounts

Movitec Features

Reliable, service-friendly
shaft seal
- Standardised mechanical
seal to EN 12756
- High-alloy steel shaft

Low noise,
since the flow noise is damped
by water-filled shroud

Corrosion resistant
All wetted components, hydraulic
components and pump shroud
are made of high-alloy stainless
steel

Hyamat VP
System Features with Movitec 18, 32 and 45
Equal distribution of
pump operating hours by
automatic pump
change-over

Acoustic cladding
(supplementary equipment)
- Retrofittable and
easy to service
- Protects against
contamination
- Appealing design
- Low-noise operation

Manual-0-automatic
selector switch per pump
Display
(supplementary equipment)
- Operating hours counter
- Flow rate indicator
General fault reporting
via volt-free contact

Automatic matching
to the demand
thanks to a continuously
speed-controlled
base-load pump

High operating reliability


thanks to continuous
functional monitoring
of the connected
sensors

Accumulator
to DIN 4807-5,
DVGW-approved

Corrosion-resistant
stainless steel piping

Installation free from solid-borne


sound transmission due to antivibration mounts

Movitec Features

Reliable, service-friendly
shaft seal
- Standardised mechanical
seal to EN 12756
- High-alloy steel shaft

Low noise,
since the flow noise is damped
by water-filled shroud

Corrosion resistant
All wetted components, hydraulic components and pump shroud are made of
high-alloy stainless steel

Hyamat VP
Modes of Operation
Cascade: Hyamat K

Variable: Hyamat V

Variable: Hyamat VP

Other combinations
and control modes

Two to six pumps are started up


and switched off by the PLC in
line with the actual demand.

A base load pump is continuously controlled, with the peak


load pumps being started up and
switched off in line with the demand.

All pumps are continuously controlled. The peak load pumps


are started up and switched off
in line with the demand.
All pumps run at the same
speed.

Available upon request.


(Example: 1 or 2 jockey pumps
as low load pumps)

Set value

Set value

Standard Pressure Boosting Units (PBU)


1 Pump
2 Ball valve
3 Combined non-return/
shut-off valve
4 Pressure gauge
5 Pressure transmitter
6 Accumulator
7 Control cabinet

Modes of Connection:
Direct

Indirect

Indirect

Unpressurized inlet tank at the same or


at a higher level

Unpressurized inlet tank at a lower level


(suction-lift operation) 1)

Inlet pressure monitoring by pressure transmitter fitted on the inlet pressure side
at pvor >0.5 bar (min. 1 bar; DIN 1988)
- pressure sensor (standard)
at pvor <0.5 bar
- flow monitoring

1)

- float switch
- set of electrodes and relay
- dry running protection set for
PE-inlet tank
- flow monitoring

Non-self-priming pumps; suitable for suction-lift operation (for selection, please consult KSB)

flow monitoring
float switch
set of electrodes and relay
dry running protection set for
PE inlet tank

Hyamat VP
Work sheet for selection
Basic
H
pE
Qsoll
H
pE

data:
= (pE - pvor)  10
m
= pvor + (H : 10)
bar
= PBU capacity at pE
m3/h
m
= PBU discharge head at Qsoll
= Start - up pressure for PBU at Qsoll
including inlet pressure pvor
pvor
= inlet pressure upstream of PBU
= PBU discharge head at Q = 0
H0
p0max = PBU discharge pressure at Q = 0 (=H0 + pvor)

H m PBU discharge head


at Qsoll

Catalogue data always refer to inlet pressure = 0.

Selection example
Requirement
Q = 18 m3/h, pE = 5 bar, pvor = 0
Found solution to DIN 1988, Part 5

Characteristic curves
and tolerances to ISO 9906

1. Hyamat VP 3/0409
The pvor value can be read directly from
the table by drawing a vertical line from
the design point to the pvor axis of the
pump.

5 bar

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor
max.
in bar
referred to
the characteristic
curve

Hyamat VP
Hyamat VP Performance Chart (Complete Overview)

Systems with higher power ratings are available on request.

Hyamat VP
Movitec 2

Movitec 4

Movitec 10

Movitec 18

n = 2900 1/min

Hyamat VP
Movitec 32

10

n = 2900 1/min

Hyamat VP
Characteristic curves Movitec 2
pvor = 0
p0 max = 16 bar
pA = max. switch-off pressure

Characteristic curves
and tolerances to ISO 9906

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor max.
in bar
referred
to the characteristic
curve

Systems with higher power ratings are available on request.


11

Hyamat VP
Characteristic curves Movitec 4
pvor = 0
p0 max = 16 bar
pA = max. switch-off pressure

Characteristic curves
and tolerances to ISO 9906

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor max.
in bar
referred
to the characteristic
curve

Systems with higher power ratings are available on request.


12

Hyamat VP
Characteristic curves Movitec 10
pvor = 0
p0 max = 16 bar
pA = max. switch-off pressure

Characteristic curves
and tolerances to ISO 9906

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor max.
in bar
referred to
the characteristic
curve

Systems with higher power ratings are available on request.


13

Hyamat VP
Characteristic curves Movitec 18
pvor = 0
p0 max = 16 bar
pA = max. switch-off pressure

Characteristic curves
and tolerances to ISO 9906

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor max.
in bar
referred to
the characteristic
curve

Systems with higher power ratings are available on request.


14

Hyamat VP
Characteristic curves Movitec 32
pvor = 0
p0 max = 16 bar
pA = max. switch-off pressure

Characteristic curves
and tolerances to ISO 9906

Pumps per system


without
stand-by
pump

including a
stand-by
pump to
DIN 1988

Max.
effective
inlet
pressure
increase
pvor max.
in bar
referred to
the characteristic
curve

Systems with higher power ratings are available on request.


15

Hyamat VP
Accessories / Supplementary Equipment *) Hyamat VP
Dry Running Protection
1)

Part No.

Ident. No.

Dry running protection for suction lift operation


(flow monitoring)
IFM sensor with tripping electronics

Retrofit option
as separate
switchgear

E 201

19 070 923

Set of electrodes and relay


Relay fitted in the control cabinet
Electrodes with 1.5 m cable
and fastening element

Retrofit option 1) E 420


if sufficient
space is available in control
cabinet

00 198 098
00 533 947

(Both ident. nos. are required)


Dry running protection, float switch1)
with H 07 RN-F cable 3x1.5 mm2
for lack-of-water monitoring in combination with a
reservoir provided by the customer, KTW-approved
Cable length
5m
10 m
20 m
Scope of supply:
- Float switch with connection cable

11 037 630
11 037 631
11 037 632

Dry running protection, float switch1)


with H 07 RN-F cable 3x1.5 mm2
for lack-of-water monitoring in combination with a
reservoir provided by the customer
Cable length
5m
10 m
20 m
Scope of supply:
- Float switch with connection cable
Dry running protection
with weight and PG cable gland,
KTW-approved
Special lengths upon request

11 037 743
11 037 744
11 037 746

5m
10 m
20 m

19 071 650
19 070 395
19 071 651
18 040 615

Weight for adjusting the float switch level


Scope of supply:
- Weight with mounting elements
1)

As accessory. A trained electrician must effect additional wiring.

Accessories / Supplementary Equipment *)


Part No.
Display, multi-line
E 511
Reporting and value setting using the keyboard
(Timer function - battery service life, i. e. backup for approx. 10 years)

76

76

Ammeter per pump

E 340

Voltmeter per system

E 341

always combined

*) Accessories (Ident. No.) are included in the scope of supply but not fitted.
Supplementary equipment / options (E No.) come fitted to the unit.

16

Ident. No.
19 072 447

Hyamat VP
Accessories / Supplementary Equipment *) (continued)
Part No.

Ident. No.

Operating hours counter per pump

E 330

Functional check run, pump change-over or second set value:


Timer for daily functional check run

E 040

18 040 617

Functional check run, pump change-over or second set value:


Digital timer for weekly programme

E 050

18 040 618

Reporting via volt-free contacts on isolating terminals


Operation per pump
Fault/malfunction per pump (frequency inverter)

E 051

Equipment for temperature monitoring


of fluid pumped at hydraulic section for each pump

E 360

19 071 510

Acoustic cladding for Hyamat 2 / 4 / 10


- Protects against contamination
- Appealing design
- Low-noise operation

Number of pumps
2 E 120
3 E 121

18 040 610
18 040 611

Acoustic cladding for Hyamat 18 / 32


Hyamat 18 up to 5.5 kW
Hyamat 32 up to 7.5 kW

Number of pumps
2 E 123
3 E 124
4 E 125

19 071 633
19 071 634
19 071 635

2 E 128
3 E 129
4 E 130

19 071 663
19 071 664
19 071 665

Telecommunications module,
for fault signalling via telephone lines, with battery buffer

E 043

19 072 308

Emergency power connection on second terminal strip


External activation

E 058

Control cabinet lighting with 230 V socket


for cabinets sized 1000 x 600 x 250 and above

E 059

Control cabinet heating for special climatic conditions


(high air humidity)

E 039

Phase monitoring relay incl. direction of rotation monitoring


and phase failure safety device

E 320

Over-voltage protection

E 060

24

36

Hyamat 18 up to 7.5 kW
Hyamat 32 up to 15.0 kW
- Protects against contamination
- Appealing design
- Noise-reduced operation

Thermistor connection for PTC thermistors in motor winding if


available.
*) Accessories (Ident. No.) are included in the scope of supply but not fitted.
Supplementary equipment / options (E No.) come fitted to the unit.

17

Hyamat VP
Supplementary Equipment (upon request)
Control cabinet equipment
Individual indications via volt-free contacts on special isolating terminals
Emergency power connection with automatic activation
Motor with PTC thermistors and PTC thermistor trip device in the control cabinet
Switch position indication (master switch or manual-0-automatic selector switch)
Control cabinet with cylinder lock
Special painting
Extra space in control cabinet
Control cabinet air-conditioning
Communication via an RS 232C interface
Profibus / LON bus interface
Indications for control station (on isolating terminals)
Operating pressure, analog 4 - 20 mA
Operating pressure, digital, volt-free
Inlet pressure, analog 4 - 20 mA
Power input for each pump, analog (for example, signal 0/4 - 20 mA / 0 - 10 V)
Position of manual-0-automatic selector switch per pump, volt-free
Special designs
Other special designs not documented are available upon request, e. g.:
1. Different frequency
2. Different connection diameters
3. System discharge pressure pd up to 40 bar
4. Systems for industry (for example, also for other fluids)
5. Systems for suction-lift operation
6. Jockey pumps: low-flow operation (on weekends, in case of extremely fluctuating demand etc.)
7. Combined systems (drinking water and fire-fighting systems), booster systems
8. Customer-specific special circuit diagrams

Remote control from control station


Basic set value is set via alert (0 - 10 V)
Please note:
Separate control cabinet installation is possible. Max distance pump-frequency inverter = 15 m.
A transfer control unit must not be used.

18

Hyamat VP
Electrical Performance Data
Hyamat VP
with pumps
Movitec

Rated power
per motor (P2)
kW

Rated current
per motor for
3~400 V
A

Total rated power requirement


in kVA Hyamat VP
Number of pumps (motors)
2
3
4

0202
0203
0204
0205
0206
0207
0208
0209
0210
0212
0213
0215

0.37
0.37
0.55
0.55
0.75
0.75
1.1
1.1
1.1
1.1
1.5
1.5

1.4
1.4
1.5
1.5
2.1
2.1
2.9
2.9
2.9
2.9
4.4
4.4

2.72
3.96
3.96
3.96
3.96
3.96
6.16
6.16
6.16
6.16
8.76
8.76

3.74
5.94
5.94
5.94
5.94
5.94
9.24
9.24
9.24
9.24
13.14
13.14

4.76
7.92
7.92
7.92
7.92
7.92
12.32
12.32
12.32
12.32
17.52
17.52

0402
0403
0404
0405
0406
0407
0408
0409
0410
0411
0413
0415

0.37
0.55
0.75
0.75
1.1
1.1
1.5
1.5
1.5
2.2
2.2
2.2

1.4
1.5
2.1
2.1
2.9
2.9
4.4
4.4
4.4
6.0
6.0
6.0

3.96
3.96
3.96
3.96
6.16
6.16
8.76
8.76
8.76
8.76
8.76
8.76

5.94
5.94
5.94
5.94
9.24
9.24
13.14
13.14
13.14
13.14
13.14
13.14

7.92
7.92
7.92
7.92
12.32
12.32
17.52
17.52
17.52
17.52
17.52
17.52

1002
1003
1004
1005
1006
1007
1008
1009
1010

0.75
1.1
1.5
2.2
2.2
3.0
3.0
4.0
4.0

2.1
2.9
4.4
6.0
6.0
7.0
7.0
9.0
9.0

3.96
6.16
8.76
8.76
8.76
12.56
12.56
13.76
13.76

5.94
9.24
13.14
13.14
13.14
18.84
18.84
20.64
20.64

7.92
12.32
17.52
17.52
17.52
25.12
25.12
27.52
27.52

1802
1803
1804
1805
1806
1807
1808

2.2
3.0
4.0
5.5
5.5
7.5
7.5

6.0
7.0
9.0
11.8
11.8
14.3
14.3

8.76
8.76
12.56
13.76
13.76
25.56
25.56

13.14
13.14
18.84
20.64
20.64
38.34
38.34

17.52
17.52
25.12
27.52
27.52
51.12
51.12

3202
3203
3204

4.0
5.0
7.5

9.0
11.8
14.3

13.76
20.76
25.56

20.64
31.14
38.34

27.52
41.52
51.12

19

Hyamat VP
Weight of units in kg (approx.)
Hyamat VP

Number of stages
07
08
09

02

03

04

05

06

10

11

2/02../.
3/02../.
4/02../.

121
154
179

125
160
187

127
163
191

131
169
199

133
172
203

143
187
223

145
190
227

145
190
227

153
202
243

153
202
243

155
205
247

173
232
283

2/04../.
3/04../.
4/04../.

121
154
179

125
160
187

127
163
191

129
166
195

133
172
203

133
172
203

145
190
227

145
190
227

147
193
231

153
202
243

155
205
247

157
208
251

2/10../.
3/10../.
4/10../.

137
178
211

141
184
219

153
202
243

161
214
259

161
214
259

181
244
299

183
247
303

197
268
331

197
268
331

2/18../.
3/18../.
4/18../.

279
371
493

301
404
537

321
434
577

378
497
651

380
500
655

390
515
675

392
518
679

--

2/32../.
3/32../.
4/32../.

374
516
708

433
582
786

447
603
814

Noise levels of units 2 / 4 / 10


Hyamat VP
with pumps

without
acoustic cladding

with
acoustic cladding

Movitec 2

60 - 65 dB(A)

51 - 56 dB(A)

Movitec 4

60 - 67 dB(A)

51 - 56 dB(A)

Movitec 10

65 - 69 dB(A)

56 - 61 dB(A)

Noise levels for units with Movitec 18 / 32 on request.

20

13

15

Hyamat VP
Dimensions Hyamat VP with Movitec 2, 4 und 10

Control cabinet door


hinged on the left

Acoustic cladding
(supplementary equipment)

Plan view
Suction
side

Discharge
side

Dimension Table (in mm)


Number of pumps
with Movitec

3/4

2 and 4

10

2 and 4

770

875

770

875

B1

630

735

630

7354

H1

115

145

115

145

770

L1

645

DN external thread
Painting:
Baseplate
Control cabinet

10

1270
1145
R2

1/

(DN 65)

RAL 5002
RAL 7032

21

Hyamat VP
Dimensions Hyamat VP with Movitec 18 and 32
see control cabinets

Control cabinet door


hinged on the left
Acoustic cladding
(supplementary equipment)

Plan view
Suction
side

Discharge
side

Movitec 18/.. and 32/..


Number of
pumps
B
B1
B2
B3
L1

Pump

1085

1085

1085

1085

1238

18/..

1105

1105

1255

1255

1255

32/..

865

865

865

865

953

18/..

885

885

970

970

970

32/..

405

405

405

405

448

18/..

415

415

458

458

458

32/..

460

460

460

460

505

18/..
32/..

470

470

515

515

515

886

1296

1706

2116

2526

L2

820

820

1230

L3

820

1230

820

1230

1230

L4

820

1230

1640

2050

2460

DN

100

100

100

100

150

150

150

DN
H1

32/..

287

287

287

287

287

18/..

302

302

302

302

302

32/..

Flanges drilled to EN 1092-1 PN 16


22

18/..

Hyamat VP
Control Cabinets Dimensions
1000 x 600 x 250

1200 x 800 x 300


Control
cabinet door
hinged on the left

Control
cabinet door
hinged on the left

Hyamat

Power

Design

Hyamat

Power

Design

VP 2 - VP 3

up to 4 kW

Standard
Timer
Reporting via volt-free
contacts
Manual-0-automatic selector
switch
Operating hours counter
PTC thermistor analysis
Temperature monitoring
Ammeter and voltmeter

VP 4

up to 7.5 kW

VP 2 - VP 4

5.5 to 7.5 kW
4 kW *)

Timer
Reporting via volt-free
contacts
Manual-0-automatic selector
switch
Operating hours counter
PTC thermistor analysis
Temperature monitoring
Ammeter and voltmeter

VP 4

up to 4 kW

Standard
Ammeter and voltmeter
Display

*) Units with Movitec 1010

23

1953.52-10

1.11.2004

Subject to technical modification without prior notice.