PRODUCT SPECIFICATIONS

Product XLPE-PVC Power Cable (CV)


Voltage

600V

No.

3121010325

Version

1/5

Specification No3121010325

1. Scope
The specification is suitable for the cable with cross-linked polyethylene (XLPE)
insulation and polyvinyl chloride (PVC) sheath used for distribution networks with
nominal voltage not exceeding 600 V. Under normal use, the conductor temperature can
reach 90. Under emergency situation, the conductor temperature can reach
130 (not more than 3 times in consecutive 12 months, in average not more than 36
hours each time). Under short-circuit situation, the conductor temperature can reach
250. (The maximum short-circuit duration is 5 seconds)
2. Cable Construction
2.1 Conductor
The conductor shall be annealed copper wire complying with CNS 1364
C2030, Annealed Electrical Copper Wire. The conductors more than 8
mm 2 shall be compact round. The pitch length on the outermost layer
shall be less than 20 times of the outer diameter of the conductor. The
lay direction of outermost layer shall be S lay.
2.2 Insulation
The insulation shall be cross-linked polyethylene (XLPE) material. The
physical properties of insulation layer shall meet the requirements of the
Clause 4, and its minimum thickness of each point shall be not less than
90% of the appropriate value in the Attached Tables.
2.3 Identification of cores
It shall be made by colors of insulation surface. The color shall be as
follows:
Single core: primary.
Two cores: black and primary.
Three cores: black, primary, and red.
Four cores: black, primary, red, and green.
2.4 Stranding of cores
For multiple-core cable, cores shall be stranded in S lay. The gap may
be filled with appropriate material. The stranded cores shall be wrapped
with appropriate material into cylindrical with pitch conforming to
following table.
Number of cores

Maximum pitch

Outer diameter of core 30

Outer diameter of core 35

Outer diameter of core 40

2/8

Specification No3121010325

2.5 Sheath
The sheath shall be black polyvinyl chloride (PVC) material. The
physical properties shall meet the requirements of the Clause 4, and its
minimum thickness of each point shall be not less than 80% of the
appropriate value in the Attached Tables.

3. Identification
The following identification shall be printed with white ink on the cable
surface at intervals not more than 350 mm.
5044

600V

XLPE

number of core(s) nominal

cross-sectional area of conductor HONG TAI

Year of manufacture

LF

For symbol in the Attached Table shall be printed


600V XLPE number of core(s) nominal cross-sectional area of conductor
HONG TAI Year of manufacture LF
4. Physical Properties of Insulation and Sheath
NO.

1.

Test Item
Tensile
strength
and
elongation
before aging

Characteristics
Tensile strength

1.27 kgf/mm2

Elongation

250%

Tensile strength

1.057 kgf/mm2

Elongation

100%

Tensile strength

75% of unaged valued

Insulation

Sheath

Thermal aging
Sheath

3.

4.

Oil resistance Sheath

Heat
deformation

Insulation

CNS 2655
C2047

Elongation

CNS 2655
C2047
(1212/168hr)
75% of unaged valued

Tensile strength

85% of unaged valued

Elongation

60% of unaged valued

Tensile strength

80% of unaged valued

Elongation

60% of unaged valued

Elongation

175%

Hot set

10%

Insulation
2.

Test method

3/8

CNS 2655
C2047
(1002/120hr)
CNS 2655
C2047
(702/4hr)
CNS 2655
C2047

Specification No3121010325

5. Inspection Item
5.1 Inspection of dimension.
5.2 D.C. resistance test of conductor.
5.3 Insulation resistance test.
5.4 A.C. withstand voltage test.

6. Reference Standard: CNS 2655 C2407


7.Cable Construction Drawing
Single core
Conductor
Insulation
Sheath

2 cores

2 cores (filling type)


Conductor
Insulation
Filler
Wrapping tape
Sheath

Conductor
Insulation
Sheath

3 cores (filling type)


Conductor
Insulation
Filler
Wrapping Tape
Sheath

3 cores
Conductor
Insulation
Sheath

4 cores

4 cores (filling type)


Conductor
Insulation
Filler
Wrapping Tape
Sheath

Conductor
Insulation
Sheath

4/8

Specification No3121010325

Attached Table 1 600V Single core


Conductor
Nominal
crosssectional Construction Outer
diameter
area

Minimum
Minimum Minimum Finished Maximum
average average overall conductor Test insulation Standard
insulation sheath diameter resistance voltage resistance length
(20)
(20)
thickness thickness (Ref.)

mm2

No./mm

mm

mm

mm

mm

/km

---

1/1.6

1.6

0.76

0.38

4.1

8.92

3.5

2500

---

1/2.0

2.0

0.76

0.38

4.5

5.65

3.5

2000

2.0

7/0.6

1.8

0.76

0.38

4.3

9.24

3.5

2500

3.5

7/0.8

2.4

0.76

0.38

4.9

5.20

3.5

2000

5.5

7/1.0

3.0

0.76

0.38

5.5

3.33

3.5

2000

7/1.2

3.6

1.14

0.38

7.0

2.31

5.5

1500

14

4.4

1.14

0.76

8.5

1.30

5.5

1500

22

5.5

1.14

0.76

9.6

0.824

5.5

1500

6.4

1.40

0.76

11.0

0.606

7.0

1000

7.1

1.40

0.76

11.7

0.487

7.0

1000

8.2

1.40

1.14

13.7

0.368

7.0

1000

9.1

1.40

1.14

14.6

0.303

7.0

1000

10.5

1.40

1.14

16.0

0.223

7.0

800

11.8

1.40

1.14

17.3

0.180

7.0

800

13.2

1.65

1.65

20.4

0.140

8.0

800

150

14.7

1.65

1.65

21.9

0.118

8.0

800

200

16.6

1.65

1.65

23.8

0.0992

8.0

800

250

18.9

1.65

1.65

26.1

0.0722

8.0

600

325

21.3

2.03

1.65

29.2

0.0565

10.0

600

400

24.0

2.03

1.65

31.9

0.0454

10.0

600

500

26.7

2.03

1.65

34.6

0.0373

10.0

600

600

31.9

2.41

2.41

40.0

0.0304

10.0

600

30

38
50

60
80

100
125

Compact
round

5/8

kV/5 min Mkm

300

200

150

Specification No3121010325

Attached Table 2 600V 2cores


Conductor
Minimum
Minimum Minimum Finished Maximum
Nominal
average average overall conductor Test insulation Standard
crosssectional Construction Outer insulation sheath diameter resistance voltage resistance length
diameter thickness thickness (Ref.)
(20)
(20)
area
mm2

No./mm

mm

mm

mm

mm

/km

kV/5 min

Mkm

---

1/1.6

1.6

0.76

1.14

8.9

9.10

3.5

2500

---

1/2.0

2.0

0.76

1.14

9.7

5.76

3.5

2000

2.0

7/0.6

1.8

0.76

1.14

9.3

9.42

3.5

2500

3.5

7/0.8

2.4

0.76

1.14

10.5

5.3

3.5

2000

5.5

7/1.0

3.0

0.76

1.14

11.7

3.4

3.5

2000

7/1.2

3.6

1.14

1.52

15.5

2.36

5.5

1500

14

4.4

1.14

1.52

17.1

1.33

5.5

1500

22

5.5

1.14

1.52

19.4

0.840

5.5

1500

6.4

1.40

2.03

23.1

0.618

7.0

1000

7.1

1.40

2.03

24.5

0.497

7.0

1000

8.2

1.40

2.03

27.2

0.375

7.0

1000

9.1

1.40

2.03

29.0

0.319

7.0

1000

10.5

1.40

2.03

31.8

0.233

7.0

800

11.8

1.40

2.03

34.4

0.189

7.0

800

13.2

1.65

2.03

38.4

0.146

8.0

800

150

14.7

1.65

2.03

41.4

0.123

8.0

800

200

16.6

1.65

2.79

46.9

0.0970

8.0

800

250

18.9

1.65

2.79

51.4

0.0759

8.0

600

30

38
50

60
80

100
125

Compact
round

300

200
325

21.3

2.03

2.79

6/8

57.7

0.0594

10.0

600

Specification No3121010325

Attached Table 3 600V 3cores


Conductor
Minimum
Minimum Minimum Finished Maximum
Nominal
average average overall conductor Test insulation Standard
crosssectional Construction Outer insulation sheath diameter resistance voltage resistance length
diameter thickness thickness (Ref.)
(20)
(20)
area
mm2

No./mm

mm

mm

mm

mm

/km

kV/5 min

Mkm

---

1/1.6

1.6

0.76

1.14

9.4

9.10

3.5

2500

---

1/2.0

2.0

0.76

1.14

10.3

5.76

3.5

2000

2.0

7/0.6

1.8

0.76

1.14

9.83

9.42

3.5

2500

3.5

7/0.8

2.4

0.76

1.14

11.1

5.3

3.5

2000

5.5

7/1.0

3.0

0.76

1.14

12.4

3.4

3.5

2000

7/1.2

3.6

1.14

1.52

16.4

2.36

3.5

1500

14

4.4

1.14

1.52

18.2

1.33

5.5

1500

22

5.5

1.14

2.03

22.0

0.840

5.5

1500

6.4

1.40

2.03

24.9

0.618

7.0

1000

7.1

1.40

2.03

26.4

0.497

7.0

1000

8.2

1.40

2.03

28.9

0.375

7.0

1000

9.1

1.40

2.03

30.8

0.309

7.0

1000

10.5

1.40

2.03

33.9

0.227

7.0

800

11.8

1.40

2.03

36.7

0.184

7.0

800

13.2

1.65

2.03

42.7

0.143

8.0

800

150

14.7

1.65

2.79

45.9

0.120

8.0

800

200

16.6

1.65

2.79

50.0

0.0940

8.0

800

250

18.9

1.65

2.79

55.0

0.0736

8.0

600

325

21.3

2.03

2.79

61.6

0.0576

10.0

600

300
30

38
50

60
80

100
125

Compact
round

7/8

200

Specification No3121010325

Attached Table 4 600V 4cores


Conductor
Minimum
Minimum Minimum Finished Maximum
Nominal
average average overall conductor Test insulation Standard
crosssectional Construction Outer insulation sheath diameter resistance voltage resistance length
diameter thickness thickness (Ref.)
(20)
(20)
area
mm2

No./mm

mm

mm

mm

mm

/km

kV/5 min

Mkm

---

1/1.6

1.6

0.76

1.14

10.2

9.10

3.5

2500

---

1/2.0

2.0

0.76

1.14

11.2

5.76

3.5

2000

2.0

7/0.6

1.8

0.76

1.14

10.7

9.42

3.5

2500

3.5

7/0.8

2.4

0.76

1.15

12.2

5.3

3.5

2000

5.5

7/1.0

3.0

0.76

1.53

14.4

3.4

3.5

2000

7/1.2

3.6

1.15

1.53

18.0

2.36

5.5

1500

300
14

4.4

1.15

1.53

20.0

1.33

5.5

1500

22

5.5

1.15

2.03

24.0

0.840

5.5

1500

6.4

1.40

2.03

27.4

0.618

7.0

1000

7.1

1.40

2.03

29.0

0.497

7.0

1000

8.2

1.40

2.03

31.8

0.375

7.0

1000

9.1

1.40

2.03

34.0

0.309

7.0

1000

10.5

1.40

2.79

37.3

0.227

7.0

1000

11.8

1.40

2.79

42.2

0.184

7.0

800

13.2

1.65

2.79

47.0

0.143

8.0

800

150

14.7

1.65

2.79

50.6

0.120

8.0

800

200

16.6

1.65

2.79

55.2

0.0940

8.0

800

250

18.9

1.65

2.79

60.7

0.0736

8.0

600

325

21.3

2.03

3.56

69.9

0.0576

10.0

600

30

38
50

60
80

100
125

Compact
round

8/8

200