Datapoints Profiles

PACiS Technical Training Level 2


CS&P Support Team

PCL

Content
 Generalities
 Inputs Profiles
 Outputs Profiles

Schneider Electric - CS&P Datapoints Profiles E01

Content
 Generalities
 Inputs Profiles
 Outputs Profiles

Schneider Electric - CS&P Datapoints Profiles E01

SCE Profiles : Input Profiles


Supervision Profiles What are Supervision DataPoint?
xPS

SPS,
DPS,
MPS,

FSS, SBMC dependency


Few acquisition options

SPS_Profile
DPS_Profile
MPS_Profile

State labels

MV
MV,

MV_Profile
FOR

Archive&Logging / state

xCT
Counter, Counter_Profile

Interlock Boolean / state


Alarm / state

Schneider Electric - CS&P Datapoints Profiles E01

SCE Profiles : Output Profiles


Control Profiles What are Control DataPoint?
xPC

SPC,
DPC,

DE / SBO
Few acquisition options

SPC_Profile
DPC_Profile

State labels

SetPoint
SetPoint, SetPoint_Profile
FOR

Archive&Logging on event
Interlock Boolean / state
Alarm on Negative Ack.

Schneider Electric - CS&P Datapoints Profiles E01

Content
 Generalities
 Inputs Profiles
 Outputs Profiles

Schneider Electric - CS&P Datapoints Profiles E01

xPS Profiles (1)


Single, Double, Multi Point Status : General Tab
Allow FSS on DP

No

Yes/No

Allow SBMC on DP

No

(Yes/No)
when bay has SBMC ON :
SBMC Substitutes values to RCP by:
- SPS : Set/Reset/Suppressed
- DPS : Jammed/Open/Close/Suppressed
- MPS : Undefined/Suppressed

Toggling Filtering for SPS, DPS


Yes/No

Initial Status
For software info => status at start-up Never use Motion
Schneider Electric - CS&P Datapoints Profiles E01

xPS Profiles (2)


Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print
SPS : Set/Reset
DPS : Jammed/Open/Close/Undefined
MPS : 1 among N(<16) State0..State15/
Undefined

All Invalid States or FSS Label


1) Labels are Business Language
dependant
2) On OI : printer and viewers labels are concatenation of
Force/Substitute & Value (open/close) : forced open
3) Profile is linked to DP then words can change
DPS
MPS

Switch gear
=> Open/Close
R/L
=> Remote/Local
N and associate DP impact labels

Schneider Electric - CS&P Datapoints Profiles E01

xPS Profiles (3)


Single, Double, Multi Point Status : State Treatment Tab
State by State, archiving policy
For OI :

For C264 :
- Archive & Logging = Archive
means stored in event list (2048
events in memory) & Logging
means displayed in event list of
front face (200 events).

- No Archive, No logging = nothing in SQL


Historian database
- Archive only = all states in VTQ
(states/values) SQL Historian database
tables (Trend Viewer)
- Archive & Logging = all states in VTQ
(states/values) SQL Historian database
tables + states marked with Logging in
Events SQL database table (Event Viewer
+ Archive viewer + printer)

Relation has events logged on for SOE


printing
Schneider Electric - CS&P Datapoints Profiles E01

xPS Profiles (4)


Single, Double, Multi Point Status : Interlock tab : Boolean value by state
SPS Set and Reset Boolean value in all PSL and
interlocking :
convention : SET=TRUE, RESET=FALSE

DPS Jammed, Open and Closed Boolean value


in all PSL and interlocking :
convention : CLOSED=TRUE, OPEN=FALSE,
JAMMED=INVALID,UNDEFINED=INVALID

Note : For MPS, no convention => depends on context of use


Schneider Electric - CS&P Datapoints Profiles E01

10

xPS Profiles (5)


Single, Double, Multi Point Status : Alarm tab, Alarm definition state by state
Alarm Generation
Appearance/Appearance disappearance
1
/
2 alarms

Alarmed state or not


Spurious SPS is Set and never reset
Alarm not generated
if state follow control (RFI SBUS)
Delay before alarm generation
(if DP reset for example)
Gravity 1->5
Audibility (klaxon)

Relation has alarm events


logged on for alarm printing
Schneider Electric - CS&P Datapoints Profiles E01

Alarms are acknowledged by


operator, but clearing can be
manual or automatic
11

MV Profile (1)
Measurement Values : General tab
Allow FSS on MV

No

Yes/No

Allow SBMC on MV

No

(Yes/No)
when bay in SBMC ON:
Substitutes values by Suppressed

MV value display on OI
Mimic
No # after decimal.
U to display unit

Schneider Electric - CS&P Datapoints Profiles E01

12

MV Profile (2)
Measurement Values : State Labels tab

Alarms
Log Print
IED disconnected
Board acquisition saturated
Digital Measurement coding
error
4-20mA DC input when
under 4mA
Threshold violation

Schneider Electric - CS&P Datapoints Profiles E01

13

MV Profile (3)
Measurement Values : State Treatment Tab
State by State, archiving policy
For OI :
- No Archive, No logging = nothing in SQL
Historian database
- Archive only = all states in VTQ
(states/values) SQL Historian database
tables (Trend Viewer)
- Archive & Logging = all states in VTQ
(states/values) SQL Historian database
tables + states marked with Logging in
Events SQL database table (Event Viewer
+ Archive viewer + printer)

Note :
- Archive only for valid => value will be available for trend viewer
- Archive & Logging for SelfCheckFault and Unknown to store acquisition errors
Schneider Electric - CS&P Datapoints Profiles E01

14

MV Profile (4)
Measurement Values :

Interlocking tab

Note : Goal is use MV associated status in PSL.


No convention => depends on context of use

Schneider Electric - CS&P Datapoints Profiles E01

15

MV Profile (5)
Measurement Values :

Alarm Management tab


Alarm Generation
Appearance/Appearance disappearance
1
/
2 alarms

Alarmed state or not

Delay before alarm generation


Gravity 1->5
Audibility (klaxon)

Alarms are acknowledged by


operator, but clearing can be
manual or automatic
Schneider Electric - CS&P Datapoints Profiles E01

16

MV Profile (6)
Measurement Values :

Mean Value tab cf. PS06


Reference hour :
- Hour of day for min/max/average values
calculation
- Daily mean values stored in monthly
VTQ table for 15 months

Reference day :
- Day of month for min/max/average
values calculation
- Monthly mean values stored in yearly
VTQ table for about 5 years

.csv VTQ tables


SQL
HISTORIAN
VTQ
SQL
HISTORIAN
Event

Daily

Monthly

Yearly

Schneider Electric - CS&P Datapoints Profiles E01

35 days storing

15 months storing

5 years storing

17

Counter Profile
Single, Double CounTer: Status

Like MV Except

Pulse value
multiplicative coefficient

Counter over max value

Double Counter invalidity


Schneider Electric - CS&P Datapoints Profiles E01

18

Content
 Generalities
 Inputs Profiles
 Outputs Profiles

Schneider Electric - CS&P Datapoints Profiles E01

19

xPC Profiles (1)


Single, Double Point Control: General tab

Define SBUS control sequence


in one or two steps :
In DE :
Client send control to Server
Server send back Ack to Client
In SBO :
- Step Selection
kept by Server with Time Out
[0..600](s)
- Step Execution
SBO Many => transformer
Note : At PACiS OI Level, DE/SBO pop-up.
DE with SBO popup = Control is DE appearing in SBO-like popup
Schneider Electric - CS&P Datapoints Profiles E01

20

xPC Profiles (2)


Single, Double Point Control:
Set Point => no order

use and labels

Usage :
Some controls are using only one
channel e.g. Master Trip Reset

Labels status for control send


logging, alarms, popup buttons

On Control
Schneider Electric - CS&P Datapoints Profiles E01

21

xPC Profiles (3)


Single, Double Point Control:

interlocking and FBD tab

PSL status on control False/True

Note : Goal is use xPC associated status in PSL.

Schneider Electric - CS&P Datapoints Profiles E01

22

xPC Profiles (4)


Single, Double Point Control:

Alarm on NACK

Alarm on control Yes/No


Delay [0..120]
Gravity [1..5]
Klaxon [Yes/No] + Relation
Clearing Acknowledged alarms

V4.7

Schneider Electric - CS&P Datapoints Profiles E01

23