C1306-D MANUAL

1. General Introduction
C1306-D is an item of microcomputer instrument used to control humidity. The input and output
function is as follows,
l Humidity Probe(HP)
l Dehumidifying relay K1 (16A 250VAC)
l Humidifying relay K2 (10A 250VAC)

2. Error Status:
1EEE Sensor Error
2PrE Paramter Error. Ener paramter menu to choose dFu, and choose 1 to restore parameter to be
factory set default value. Then reset parameter.
3. LLA Humidity is lower than Lower alarm humidity(LS), and the duration time surpasses alarm
delay( At).
4. HHA Humidity is higher than Upper alarm humidity(US),and the duration time surpasses the alarm
delay(At).

3. 1 Front Panel
Dehumidify
Humdify
Set
SET

In the mode of programming,it can be used to choose the parameter to be programmed or to


confirm the operation of program.
Press SET key to display the set humidity(sp);
Press SET key for 6 seconds to set the humidity set value(sp);
(UP): In the mode of programming, it is used to browse parameters or increase parameter value.
(DOWN): In the mode of programming, it is used to browse parameters or decrease parameter value
Combination key:
+
Lock the keyboard or remove the keyboard locking.
SET +
Press the keys for 6 seconds at the same time to enter the state to parameter set.
3.2 LED Status
LED
Status
Function
On
The dehumidifying relay(K1) is on
Flashing Dehumidifying delay
On
The humidifying relay(K2) is on
Flashing Humidifying delay
SET
On
Status of setting
3.3 How to inquire and modify humidity target set value(SP)
1. Press SET and release immediately, it will display SP;
2. Press SET for 6 seconds, it will display set value(SP) and start to flash;
3. Modify SP by the key of or
4. Press SET key again and save SP and return to humidity display. It will return to humidity display
if there is no key-pressing in 10 seconds.
3.4 How to change the parameter value
1. Press combination key SET+ for 6 seconds to enter parameter operation;
2. Use or to choose the parameter to be modified;
3. Press SET key to display the parameter value;
4. Use or to change parameter value;
5. Press SET key to store new parameter value and return to interface of parameter operation;
Page 1/3
WWW.HONGYIINC.COM

C1306-D MANUAL
6. Choose END or if there is no key-pressing in 10 seconds, it will exit from set and return to status
of humidity display.
3.5 How to lock keyboard or remove keyboard locking
1. Press the combination key and for over 3 seconds at the same time to lock keyboard or
remove the keyboard locking.
2. When keyboard is locked, it will display OFF, and it will show ON when the keyboard locking is
removed.
4. Parameter list
Us:
Alarm against upper humidity
Range: 0.1-100%RH, Factory-set value: 100%RH.
Ls:
Alarm against lower humidity
Range: 0-99.9%RH, Factory-set value: 0%RH.
CAL: Sensor compensation. Range: -10-10%RH Factory-set value: 0%RH
HSC: Dehumidifying magnetic hysteresis Range: 0-20%RH Factory-set value: 2.0%RH
HSH: Humidifying magnetic hysteresis Range: 0-20%RH
Factory-set value: 2.0%RH
Dbd: Deadzone, There is no humidifying and dehumidifying output when the humidity is in
between the range: SP dbd/2 ~ SP + dbd/2
Range: -19.9 ~ 20%RH Factory-set value: 0.0%RH
* If dbd is lower than 0, dbd must be higher than 2(-HSC + 1) and 2(-HSH + 1)
rt: The minimum close time of the instrument Range: 0-255minutes, Factory-set value0
minute.
At: Humidity alarm delay Range: 0-255 minutes, Factory-set value: 60 minutes
C-H: Working mode, Range:0-2 Factory-set value:0
0 Humidifying and dehumidifying mode
1 Dehumidifying mode
2 Humidifying mode
dFu: Range:0-1
1 Return to factory set
0 No changes
END: Exit to parameter set

* If C-H is set to be 0 or 1;When humidity is higher than sp + HSC + dbd/2, dehumidifying


relay(K1) will be open; When the humidity decreases to sp + dbd/2, the dehumidifying relay will
be closed
* If C-H is set to be 0 or 2; When humidity is lower than sp HSH dbd/2, the humidifying
relay(K2) will be open; When the humidity increases to sp dEd/2, dehumidifying relay will be
closed.
5. Installation drawing
Panel
Sealing
Controller

Bracket

6. Technical data:
Case Material:
Dimension:

ABS,Black
753870

Page 2/3
WWW.HONGYIINC.COM

C1306-D MANUAL
Mounting
Waterproof
Connection method:
Working Condition:
Storage Condition:
Measurement Range:
Display Accuracy:
Power:
Power Consumption:
Relay

7129.5
Front panel,IP54
Screw
-1055RH85no defrosting
-1070RH85no defrosting
0~100%RH(10~90%RH ,2% Others 3%)
0.1%RH
220VAC,10,50/60Hz
No more than 2W
K1 250VAC 16A
K2 250VAC, 10A
Digital humidity sensor, DHT6X
Three keys
2 channels of always-on relay
3-digit LED

Sensor:
Input:
Output:
Display

Connection Fig.
CONTROLLER
10A(MAX)
250VAC

16A(MAX)
250VAC

HP

K2
1

K1
4

VCC

data

6 4 75

sck

Humi
COM

Dehumid

Power
220VAC/50Hz

Page 3/3
WWW.HONGYIINC.COM

DHT6X

Gnd