You are on page 1of 16

Product selection guide

Kabeldon cable cabinet, 1236 kV


Document name

Kabeldon cable cabinet for 1236 kV, HDC-A


A robust and safe solution

Application area
Kabeldon HDC-A offers unique capabilities for jointing and
branching cable grids. Due to connections being made
above ground, improved flexibility is gained when working in
the grids.
As necessary, selected cables can be sectionalized for
e.g. maintenance. Disconnected cables can be earthed with
special earthing devices and tools. The rest of the cable grid
can then be energized, thus limiting the number of subscribers affected by a temporary interruption to service.
HDC-A is excellent for use in applications such as consumer
grids and wind power farms.

Design
The cable cabinet consists of:
An enclosure constructed of hot-dip galvanized sheet
steel with additional corrosion protection on the
foundation under ground.
Screened separable cable connectors that are connected
together with coupling pieces mounted in the cabinet.
Standards
Enclosures: impact testing according to international
standard IEC 60439-5.
Screened separable cable connectors: electrical
requirements according to European standard
CENELEC HD 629.1 S2.

In wind parks, the cable cabinets can be used as branching


points so that separate cables do not need to be run from
each wind turbine to the substations. This means lower
costs for among other things excavation and cabling.
HDC-A is connected in the cable grid so that power can
be disconnected before beginning work in a cabinet.

General diagram for wind power parks with 36 kV cabinets serving


as junction points.

General diagram for cable grid with HDC-A

Substation with
disconnection
capabilities

HDC-A

2 | Kabeldon cable cabinets 1236 kV | Selection guide

HDC-A

HDC-A

Configuration

HDC-A is supplied in five configurations as follows:


HDC-A 12250
Voltage:
Rated current:
Cable cross section:
Total variants:

See pages 45
12 kV
250 A
2595 mm
1

HDC-A 24250
Voltage:
Rated current:
Cable cross section:
Total variants:

See pages 67
24 kV
250 A
2595 mm
1

HDC-A 12630
Voltage:
Rated current:
Cable cross section:
Total variants:

See pages 89
12 kV
630 A
25630 mm
3

HDC-A 24630
Voltage:
Rated current:
Cable cross section:
Total variants:

See pages 1011


24 kV
630 A
25630 mm
3

HDC-A 36630
Voltage:
Rated current:
Cable cross section:
Total variants:

See pages 1213


36 kV
630 A
50630 mm
3

Accessories and optional


equipment

See pages 1415

Kabeldon cable cabinet for 36 kV.

HDC-A 24250

HDC-A 24630

HDC-A 36630

Selection guide | Kabeldon cable cabinets 1236 kV | 3

Kabeldon cable cabinet, 12 kV, 250 A


HDC-A 12250

12 kV
250 A
2595 mm
9

312 mm
996 mm

Optional
The cabinet needs to be supplemented depending on the
cable type used, the number of cables to be connected
or whether cables need to be sectionalized. Available
accessories are shown on page 5, 14 and 15.

Overall height 1293 mm


Height above ground level, 993 mm

Basic configuration
Voltage level:
Rated current:
Cable size:
Qty. cable connectors:

HDC-A 12250 is available in the following variants


Insulation diameter

Conductor cross section in basic configuration Variant

mm

mm

1322

2595*

HDC-A 12250

ID number
2GPJ 63301170

* For cables smaller than 25 mm, contact us.

Following components are included in HDC-A 12250


Product

Designation

Application area/content

Enclosure

HDC-A 250

312 mm depth, installed with coupling pieces, earth bar and labels,
SE or triangular lock in door

Quantity
1

Foundation kit (Choose between


MARK-S 73 and GOLV-S 73)

MARK-S 73*

280 mm depth, incl. 2 protection plates with anchor bar, 2 base supports

GOLV-S 73**

280 mm depth, incl. 2 protection plates with anchor bar

Transversal anchor bar

KA 250

Cable restraint

Cable clamp

UKRA 90

Attachment of cable to anchor bar

Screened separable cable connector


with capacitive test point

CSE-A 12250

Screened separable cable connectors for


branching, 3-phase kits

Connector

AD 350

Connection of cable screen

Connector

AD 70

Connection of earth wire

Key

NK 30 or NK 3

Installation instructions

* For installation in the ground.


** For installation on the floor.

4 | Kabeldon cable cabinets 1236 kV | Selection guide

2
9
3 kits
3

Accessories for cable cabinet


HDC-A 12250

Accessories for installation of 3-core cables,


screen separation kit (choose an alternative)
Screen separation kit

PSSK 1 L*

Type
ID number

PSSK 2 L*

Heat-shrink
2GPJ 62341197

Length

2GPJ 62341198

2m

2m

Voltage level

12 kV

12 kV

3 x 25 mm

3 x 35 mm

3 x 50 mm

3 x 70 mm

3 x 95 mm

* Reinforced configuration that permits underground branching. For cables


with copper or aluminium screen wires.
For cables with Cu-tape screen, contact us.

Other accessories
Application area

Description

Designation

ID number

Quantity

When connecting only two cables

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

When earthing a disconnected connector

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

For measuring, e.g. when phase marking

Measurement adapter

MA 250

2GPJ 52340475

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

Insulating plug

IP 250

2GPJ 62341181

When energizing disconnected connector

Selection guide | Kabeldon cable cabinets 1236 kV | 5

Kabeldon cable cabinet, 24 kV, 250 A


HDC-A 24250

24 kV
250 A
2595 mm
9

312 mm
996 mm

Optional
The cabinet needs to be supplemented depending on the
cable type used, the number of cables to be connected
or whether cables need to be sectionalized. Available
accessories are shown on page 7, 14 and 15.

Overall height 1293 mm


Height above ground level, 993 mm

Basic configuration
Voltage level:
Rated current:
Cable size:
Qty. cable connectors:

HDC-A 24250 is available in the following variants


Insulation diameter

Conductor cross section in basic configuration

mm

mm

1725.5

2595*

Variant

ID Number

HDC-A 24250

2GPJ 63301171

* For cables smaller than 25 mm, contact us.

Following components are included in HDC-A 24250


Product

Designation

Application area/content

Enclosure

HDC-A 250

312 mm depth, installed with coupling pieces, earth bar and labels,
SE or triangular lock in door

Quantity
1

Foundation kit (Choose between


MARK-S 73 and GOLV-S 73)

MARK-S 73*

280 mm depth, incl. 2 protection plates with anchor bar, 2 base supports

GOLV-S 73**

280 mm depth, incl. 2 protection plates with anchor bar

Transversal anchor bar

KA 250

Cable restraint

Cable clamp

UKRA 90

Attachment of cable to anchor bar

Screened separable cable connector


with capacitive test point

CSE-A 24250

Screened separable cable connectors for branching, 3-phase kits

Connector

AD 350

Connection of cable screen

Connector

AD 70

Connection of earth wire

Key

NK 30 or NK 3

Installation instructions

* For installation in the ground.


** For installation on the floor.

6 | Kabeldon cable cabinets 1236 kV | Selection guide

3 kits
3

Accessories for cable cabinet


HDC-A 24250

Accessories for installation of 3-core cables,


screen separation kit (choose an alternative)
Screen separation kit

PSSK 1 L*

Type
ID number

PSSK 2 L*
Heat-shrink

2GPJ 62341197

2GPJ 62341198

Length

2m

2m

Voltage

24 kV

24 kV

3 x 25 mm

3 x 35 mm

3 x 50 mm

3 x 70 mm

3 x 95 mm

* Reinforced configuration that permits underground branching. For cables with copper
or aluminium screen wires.
For cables with Cu-tape screen, contact us.

Other accessories
Application area

Description

Designation

ID number

Quantity

When connecting only two cables

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

When earthing a disconnected cable connector

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

For measuring, e.g. when phase marking

Measurement adapter

MA 250

2GPJ 52340475

Insulating hood

IH-A 24250

2GPJ 62341150

3 per kit

Insulating plug

IP 250

2GPJ 62341181

When energizing a disconnected cable connector

Selection guide | Kabeldon cable cabinets 1236 kV | 7

Kabeldon cable cabinet, 12 kV, 630 A


HDC-A 12630

Basic configuration
Voltage level:
Rated current:
Cable size:
Qty. cable connectors:

522 mm

12 kV
630 A
25630 mm
6

996 mm

Optional
The cabinet needs to be supplemented depending on the
cable type used, the number of cables to be connected
or whether cables need to be sectionalized. Available
accessories are shown on pages 9, 14 and 15.

Overall height 1293 mm


Height above ground level, 993 mm

The third cable connector kit is ordered separately.

HDC-A 12630 is available in the following variants


Insulation diameter

Conductor cross section in basic configuration

mm

mm

Variant

ID number

1320

2570

HDC-A 12630-01

2GPJ 63301175

95300

HDC-A 12630-02

2GPJ 63301176

400630

HDC-A 12630-03

2GPJ 63301177

18.530.5
30.545

The following components are included in HDC-A 12630


Product

Designation

Application area/content

Enclosure

HDC-A 630

Depth 522 mm, installed with coupling piece, earth bar and lables, SE or
triangular lock in door

Quantity
1

Foundation kit (Choose between


MARK HDC-A and GOLV HDC-A)

MARK HDC-A*

Depth 430 mm, incl 2 protection plates with anchor bar, 2 base supports

GOLV HDC-A**

Depth 430 mm, incl 2 protection plates with anchor bar

Transversal anchor bar

KA 630

Cable restraint

Cable clamp

UKRA 90

Attachment of cable to anchor bar

Connector

AD 350

Connection of cable screen

Connector

AD 70

Connection of earth wire

Screened separable cable connector


with capacitive test point

CSE-A 12630

Screened separable cable connector for branching, 3-phase kit

Key

NK 30 or NK 3

Installation instructions

* For installation in the ground.


** For installation on the floor.

8 | Kabeldon cable cabinets 1236 kV | Selection guide

1
2 kits

Accessories for cable cabinet


HDC-A 12630

Accessories for branching of third and possibly fourth cable


Application area

Rated
current

Insulationdiameter

Conductor
Voltage Description
cross section

mm

mm

kV

When connecting
CSE-A 630 and
CSE-A 250 in parallel

250

1322

2595

12

When connecting
cables

630

When connecting
cables

When connecting
cables

630

630

1320

18.530.5

30.545

2570

95300

400630

12

12

12

Product
designation

ID number

Quantity
per kit

Screened separable cable


connector

CSE-A 12250-02

2GPJ 62341213

Screened separable cable


connector including screened separable kit

CSE-A 12250-02 P 2GPJ 62350307

Parallel coupling piece

PC 630/250

2GPJ 52340480

Screened separable cable


connector

CSE-A 12630-01

2GPJ 62341227

Screened separable cable


connector including screened separable kit

CSE-A 12630-01 P 2GPJ 62350310

Parallel coupling piece

PC 630-3

2GPJ 52340517

Screened separable cable


connector

CSE-A 12630-02

2GPJ 62341228

Screened separable cable


connector including screened separable kit

CSE-A 12630-02 P 2GPJ 62350311

Parallel coupling piece

PC 630-3

2GPJ 52340517

Screened separable cable


connector

CSE-A 12630-03

2GPJ 62341229

Parallel coupling piece

PC 630-3

2GPJ 52340517

Other accessories
Application area

Description

For voltage testing

Bushing for voltage testing PG 630

2GPJ 52340414

For measuring, e.g. when phase marking

Measurement adapter

MA-A 630

2GPJ 52340436

3 per kit

IH-A 24630

2GPJ 62341242

3 per kit

IP 630

2GPJ 52341108

When energizing a disconnected cable connector Insulating hood


Insulating plug

Designation

ID number

Quantity

Selection guide | Kabeldon cable cabinets 1236 kV | 9

Kabeldon cable cabinet, 24 kV, 630 A


HDC-A 24630

Basic configuration
Voltage level:
Rated current:
Cable size:
Qty. cable connectors:

522 mm

24 kV
630 A
25630 mm
6

996 mm

Optional
The cabinet needs to be supplemented depending on the
cable type used, the number of cables to be connected
or whether cables need to be sectionalized. Available
accessories are shown on pages 11, 14 and 15.

Overall height 1293 mm


Height above ground level, 993 mm

The third cable connector kit is ordered separately.

HDC-A 24630 is available in the following variants


Insulation diameter

Conductor cross section in basic configuration Variant

mm

ID number

mm

1724

2595

HDC-A 24630-1

2GPJ 63301180

22.535

95300

HDC-A 24630-2

2GPJ 63301181

30.545

400630

HDC-A 24630-3

2GPJ 63301182

Following components are included in HDC-A 24630


Product

Designation

Application area/content

Enclosure

HDC-A 630

522 mm depth, installed with coupling pieces,


earth bar and labels, SE or triangular lock in door

Quantity
1

Foundation kit (Choose between


MARK HDC-A and GOLV HDC-A)

MARK HDC-A*

Depth 430 mm, incl 2 protection plates with anchor bar, 2 base supports

GOLV HDC-A**

Depth 430 mm, incl 2 protection plates with anchor bar

Transversal anchor bar

KA 630

Cable restraint

Cable clamp

UKRA 90

Attachment of cable to anchor bar

Connector

AD 350

Connection of cable screen

Connector

AD 70

Connection of ground wire

Screened separable cable connector CSE-A 24630


with capacitive test point

Screened separable cable connectors for


branching, 3-phase kits

Key

NK 30 or NK 3

Installation instructions

* For installation in the ground.


** For installation on the floor.

10 | Kabeldon cable cabinets 1236 kV | Selection guide

2 kits

Accessories for cable cabinet


HDC-A 24630

Accessories for branching of third and possibly fourth cable


Application area

Rated
current

InsulationConductor Voltage Description


diameter cross section

mm

mm

kV

When connecting
CSE-A 630 and
CSE-A 250 in parallel

250

1725.5

2595

24

When connecting
cables

630

When connecting
cables

When connecting
cables

630

630

1724

22.535

30.545

2570

95300

400630

24

24

24

Product
designation

ID number

Quantity
per kit

Screened separable cable


connector

CSE-A 24250-02

2GPJ 62341215

Screened separable cable


connector including screened
separable kit

CSE-A 24250-02 P 2GPJ 62350309

Parallel coupling piece

PC 630/250

2GPJ 52340480

Screened separable cable


connector

CSE-A 24630-01

2GPJ 62341230

Screened separable cable


connector including screened
separable kit

CSE-A 24630-01 P 2GPJ 62350312

Parallel coupling piece

PC 630-3

2GPJ 52340517

Screened separable cable


connector

CSE-A 24630-02

2GPJ 62341231

Screened separable cable


connector including screened
separable kit

CSE-A 24630-02 P 2GPJ 62350313

Parallel coupling piece

PC 630-3

2GPJ 52340517

Screened separable cable


connector

CSE-A 24630-03

2GPJ 62341232

Parallel coupling piece

PC 630-3

2GPJ 52340517

Other accessories
Application area

Description

For voltage testing

Bushing for voltage testing PG 630

2GPJ 52340414

For measuring, e.g. when phase marking

Measurement adapter

MA-A 630

2GPJ 52340436

3 per kit

Insulating hood

IH-A 24630

2GPJ 62341242

3 per kit

Insulating plug

IP 630

2GPJ 62341108

When energizing a disconnected cable connector

Designation

ID number

Quantity

Selection guide | Kabeldon cable cabinets 1236 kV | 11

Kabeldon cable cabinet, 36 kV, 630 A


HDC-A 36630

Basic configuration
Voltage level:
Rated current:
Cable size:
Qty. cable connectors:

522 mm

36 kV
630 A
50630 mm
6

996 mm

Optional
The cabinet needs to be supplemented depending on the
cable type used, the number of cables to be connected
or whether cables need to be sectionalized. Available
accessories are shown on pages 13, 14 and 15.

Overall height 1293 mm


Height above ground level, 993 mm

The third cable connector kit is ordered separately.

Always select products by insulation diameter.

HDC-A 36630 is available in following variants


Insulation diameter

Conductor cross section in basic configuration

mm

mm

Variant

ID number

24.534

5095

HDC-A 36630-01

2GPJ 63301185

27.542

95300

HDC-A 36630-02

2GPJ 63301186

3855

400630

HDC-A 36630-03

2GPJ 63301187

The following components are included in HDC-A 36630


Product

Designation

Application area /content

Enclosure

HDC-A 630

522 mm depth, installed with coupling pieces, earth bar and labels, SE or
triangular lock in door

Quantity
1

Foundation kit (Choose between


MARK HDC-A and GOLV HDC-A)

MARK HDC-A*

Depth 430 mm, incl 2 protection plates with anchor bar, 2 base supports

GOLV HDC-A**

Depth 430 mm, incl 2 protection plates with anchor bar

Transversal anchor bar

KA 630

Cable restraint

Cable clamp

UKRA 90

Attachment of cable to anchor bar

Connector

AD 350

Connection of cable screen

Connector

AD 70

Connection of ground wire

Screened separable cable connector CSE-A 36630


with capacitive test point

Screened separable cable connectors for


branching, 3-phase kits

Key

NK 30 or NK 3

Installation instructions

* For installation in the ground.


** For installation on the floor.

12 | Kabeldon cable cabinets 1236 kV | Selection guide

2 kits

Accessories for cable cabinet


HDC-A 36630

Accessories for branching of third and possibly fourth cable


Application area

Rated
current
A

mm

mm

kV

When connecting
cables

630

2334

5095

36

When connecting
cables

When connecting
cables

630

630

Insulationdiameter

27.542

3855

Conductor
Voltage Description
cross section

95300

400630

36

36

Designation

ID number

CSE-A 36630-01

2GPJ 63350287

Screened separable cable


CSE-A 36630-01 P 2GPJ 62350314
connector including screened
separable kit

Screened separable cable


connector

Quantity
per kit

Parallel coupling piece

PC 630-3 L

2GPJ 52340480

Screened separable cable


connector

CSE-A 36630-02

2GPJ 63350288

Screened separable cable


CSE-A 36630-02 P 2GPJ 62350315
connector including screened
separable kit

Parallel coupling piece

PC 630-3 L

2GPJ 52340480

Screened separable cable


connector

CSE-A 36630-03

2GPJ 63350289

Parallel coupling piece

PC 630-3 L

2GPJ 52340480

Other accessories
Application area

Description

For voltage testing

Bushing for voltage testing PG-A 630

Designation

ID number
2GPJ 52340522

Quantity
1

For measuring, e.g. when phase marking

Measurement adapter

MA-A 630

2GPJ 52340436

3 per kit

When energizing a disconnected cable


connector

Insulating hood

IH-A 42630

2GPJ 62341244

3 per kit

Insulating plug

IP 630

2GPJ 62341108

Selection guide | Kabeldon cable cabinets 1236 kV | 13

Accessories and optional equipment


Picture

Description

Designation

ID Number

Parallel coupling piece, 630/250 A,


1224 kV

PC 630/250

2GPJ 52340480

3 per kit including


installation tool

Parallel coupling piece, 630 A, 1224 kV

PC 630-3

2GPJ 52340517

3 per kit including


installation tool

Parallel coupling piece, 630 A, 36 kV

PC 630-3 L

2GPJ 52340518

3 per kit including


installation tool

Screened insulating plug, 250 A, 1224 kV IP 250

2GPJ 62340081

1 per kit

Screened insulating plug, 630 A, 1236 kV IP 630

2GPJ 62341108

1 per kit

Measurement adapter, 250 A

MA 250

2GPJ 52340475

1 per kit

Measurement adapter, 630 A

MA-A 630

2GPJ 52340436

3 per kit

Screened separable cable connector


12 24 kV, 250 A

CSE-A 12250-02
CSE-A 24250-02

2GPJ 62341213
2GPJ 62341215

3 per kit

Screened separable cable connector


12 24 kV, 630 A

CSE-A
CSE-A
CSE-A
CSE-A
CSE-A
CSE-A

2GPJ
2GPJ
2GPJ
2GPJ
2GPJ
2GPJ

62341227
62341228
62341229
62341230
62341231
62341232

3 per kit

Screened separable cable connector


36 kV, 630 A

CSE-A 36630-01
CSE-A 36630-02
CSE-A 36630-03

2GPJ 62350287
2GPJ 62350288
2GPJ 62350289

3 per kit

14 | Kabeldon cable cabinets 1236 kV | Selection guide

12630-01
12630-02
12630-03
24630-01
24630-02
24630-03

Quantity

Accessories and optional equipment


Picture

Description

Designation

CSE-A 12250-02 P
Screened separable cable connector
including screen separation kit, heat-shrink CSE-A 24250-02 P
for 3-core cable 1236 kV, 250 and 630 A CSE-A 12630-01 P
CSE-A 12630-02 P
CSE-A 24630-01 P
CSE-A 24630-02 P
CSE-A 36630-01 P
CSE-A 36630-02 P

ID Number

Quantity

2GPJ
2GPJ
2GPJ
2GPJ
2GPJ
2GPJ
2GPJ
2GPJ

62350307
62350309
62350310
62350311
62350312
62350313
62350314
62350315

3 per kit

Insulating hood, 12 24 kV, 250 A

IH-A 24250

2GPJ 62341150

3 per kit

Insulating hood, 1224 kV, 630 A

IH-A 24630

2GPJ 62341242

3 per kit

Insulating hood, 36 kV, 630 A

IH-A 42630

2GPJ 62341244

3 per kit

Screen separation kit, heat-shrink


for 3-core cable

PSSK 1 L
PSSK 2 L
PSSK 3 L

2GPJ 62341197
2GPJ 62341198
2GPJ 62341199

1 per kit

Branch seal

TSH 1 L
TSH 2 L

2GPJ 62341153
2GPJ 62341155

1 per kit

Bushing for voltage testing, 1224 kV

PG 630

2GPJ 52340414

1 per kit

Bushing for voltage testing, 36 kV

PG-A 630

2GPJ 52340522

1 per kit

Clamp for fixing cables

UKRA 90

2GPJ 65300013

1 per kit

Selection guide | Kabeldon cable cabinets 1236 kV | 15

ABB AB
Cable Accessories
Box 531
SE-441 15 Alingss, Sweden
Tel: +46 21 32 50 00
e-mail: info.sedon@se.abb.com
www.abb.com/cableaccessories

Copyright 2015 ABB. All rights reserved.

Document ID: 7ABA125772

Contact us

You might also like