Features
Low burden
Trip circuit can be supervised with
breaker open or closed
Mis-tripping of breaker by
accidental short-circuits avoided
No false alarms given due to
protection operation
Application
The Type MVAX relay supervises the
trip circuit of a circuit breaker,
initiating audible alarm and visual
indication if the trip circuit fails or the
mechanism does not operate.
Four types are available giving
supervision as follows:
Relay type
Faults detected
MVAX 12
Failure of trip
supply only
MVAX 21,
MVAX 31 and
MVAX 91
Failure of trip
supply
Description
Failure of circuit
breaker tripping
mechanism
Type MVAX 31 gives supervision with
the circuit breaker in either state, and
type MVAX 21 with circuit breaker
closed only.
If required, the alarm units of types
MVAX 21 and MVAX 31 can be
operated via pilot wires.
Type MVAX 91, three seperate
MVAX 31s in a size 8 case.
Case earth
1
Vx
2
4
R ext
13
R1
13
1
3
14
RL1
2
14
C1
21
R2
22
Note 1 (a)
27
28
(b)
(c)
Long terminals
Module terminal
block viewed from rear
CB Aux
switch
52-b
28
RL1
3
Rext (1)
RL2-1
Rext (2)
13
Trip coil
52-a
Trip relay
52
T
CB Aux
switch
14
RL2
RL1-1
RL1-2
RL1-3
Alarm
contacts
Rext (2)
13
RL2
52-a
14
Rext (3)
21
RL3
CB Aux
switches
22
52-b
+
27
RL3-1
RL1
3
RL2-1
1
RL1-1
RL1-2
RL1-3
28
52
T
Rext (1)
Alarm
contacts
Note: Contact arrangement shown is typical only.
Phase A
+
52-a
CB Aux
switches
Rext (2)
47
48
Rext (3)
45
RL2
52
T
29
RL1-1
31
30
RL1-2
32
33
RL1-3
35
37
RL1-1
39
38
RL1-2
40
41
RL1-3
43
RL1-1
RL1-2
RL1-3
46
Alarm
contacts
RL3
52-b
+
49
RL3-1
RL1
3
RL2-1
50
Rext (1)
Phase B
+
52-a
CB Aux
switches
Rext (2)
53
54
Rext (3)
52
51
RL2
52
T
Alarm
contacts
RL3
52-b
+
55
RL3-1
RL1
3
RL2-1
56
Rext (1)
Phase C
+
52-a
CB Aux
switches
Rext (2)
25
26
Rext (3)
RL2
23
24
RL3
52-b
+
27
RL3-1
RL2-1
52
T
RL1
3
28
Rext (1)
Alarm
contacts
Case earth
1
10
11
12
13
14
22
27
28
Note 1
(a)
14
ZGO891
21
Vx +
R1
13
Vx +
R2
(c)
Long terminals
28
ZGO891
RL1
3
RL2
ZGO891
1
3
5
7
2
4
22
21
27
Vx +
RL2-A
RL3-A
Combinations of
output contacts
Output contacts to
module terminals
1 3 5 7 2 4
3M
M M M
2M
1B
B M M
1M
2B
B M B
Figure 2(e): MVAX 31 Trip circuit supervision relay with preclosing supervision (ac)
RL2
46
V
47
Vx +
50
ZGO891
R1
29
31
33
35
RL1
3
48
ZGO891
ZGO891
45
Vx +
30
32
RL3
Phase A
R2
49
Vx +
RL2-A
RL3-A
RL2
52
V
53
Vx +
56
ZGO891
R1
37
39
41
43
RL1
3
54
ZGO891
ZGO891
51
Vx +
38
40
RL3
Phase B
R2
55
Vx +
RL2-A
RL3-A
Phase C
RL2
24
RL1
3
26
ZGO891
V
R1
R2
28
ZGO891
V
25
Vx +
1
3
5
7
2
4
ZGO891
23
Vx +
27
Vx +
RL2-A
RL3-A
Case earth
Case earth
29
30
31
32
33
34
35
36
10
37
38
11
12
39
40
13
14
41
42
15
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
52
23
24
51
25
26
53
54
27
28
55
56
Combination of
output contacts
Note 1
(a)
(b)
(c)
Long terminals
Note 2
For 30 110V/125V only
Figure 2(f): MVAX 91 Trip circuit supervision relay with preclosing supervision (ac)
A Phase
3M
2M
1M
3B
B Phase
3M
2M
1M
3B
C Phase
3M
2M
1M
3B
1B
2B
1B
2B
1B
2B
-
33-35
M
M
M
N/A
41-43
M
M
M
N/A
5-7
M
M
M
N/A
30-32
M
M
B
B
38-40
M
M
B
B
2-4
M
M
B
B
34-36
N/A
N/A
N/A
B
42-44
N/A
N/A
N/A
B
6-8
N/A
N/A
N/A
B
Technical Data
Note: For ac supervision relays, the technical information is the same as for
dc versions
Voltage ratings (Vx)
Operative range
(V dc)
24/27
30/34
48/54
110/125
220/250
19 30
24 37.5
37.5 60
87.5 137.5
175 275
mA
Trip
mA
Alarm
mA
45
36
23
15
9
1.23
1.22
1.25
1.9
2.3
55
35
20
20
20
1.5
1.5
1
2.5
4.5
80
80
80
63
60
2.5
3
4
8
15
Rating (V dc)
24/27
30/34
48/54
110/125
220/250
Notes:
1. All the burdens are at the maximum rated value
2. All burdens are less than the figures quoted
3. With the circuit breaker open the trip supply burden of the MVAX 21 is zero
4. MVAX 91 = 3 x MVAX 31mA/W, 3 seperate units
Maximum pilot loop resistance
of alarm supply
Rating
(V dc)
Maximum pilot
loop resistance
in ohms
24/27
30/34
48/54
110/125
220/250
100
200
400
400
400
MVAX 12
MVAX 21, 31, 91
< 20ms
< 70ms
MVAX 12
MVAX 21, 31, 91
>100 ms
> 400 ms
Operation indicator
Contacts
MVAX 12
Contact ratings
Current
Break
ac
1250VA with
maxima of
5A and 660V
7500VA with
maxima of
30A and 660V
1250VA with
maxima of
5A and 660V
dc
1250W with
maxima of
5A and 660V
7500VA with
maxima of
30A and 660V
100W (resistive)
50W (inductive
with maxima of
5A and 660V
Voltage withstand
Insulation
IEC 255 5
Environmental withstand
Temperature
IEC 68 2 1/IEC 68 2 2
Humidity
IEC 68 2 3
Enclosure protection
IEC 529
IP 50 (dust protected)
Vibration
IEC 255 211
Mechanical durability
Loaded contact
Unloaded contact
Cases
Type MVAX 12 is available in a size
2 case, see Figure 3. Types MVAX 21
and MVAX 31 are available in size 3
cases see Figure 4. Type MVAX 91 is
available in a size 8 case, see
Figure 5.
45
13
4 holes 4.4
24
168
Push button
projection 10 max
48
Panel cut-out:
Flush mounting fixing details
Relay type
Alarm and trip supply voltages
159
32
25 min.
212
Contact combination
Operation indicator required
177
157 max.
Reset
51
Flush mounting
All dimensions in mm
4 holes 4.4
71
26
23.5
168
Push button
projection 10 max
159
73
Panel cut-out:
Flush mounting fixing details
32
212
177
25 min.
157 max.
Reset
77
Flush mounting
All dimensions in mm
4 holes 4.4
200
155.4
24
168
Push button
projection 10 max
159
203
Panel cut-out:
Flush mounting fixing details
32
212
177
25 min.
157 max.
Reset
206
All dimensions in mm
10
Flush mounting
11