DATA SHEET:

ACCC Helsinki
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-003)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
150.6
mm2
5.97
mm
28.0
mm2
15.65
mm
178.6
mm2
68.9
kN
60.4
kN
54
kg/km
471.2
kg/km
417.2
kg/km
o
180
C
o
1.61E-06
/C
1.74E-05
/oC
112.3
GPa
66.5
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
297.2
kcmil
0.235
in.
0.043
in2
0.616
in.
0.277
in2
15.5
kips
13.6
kips
36
lb/kft
316.7
lb/kft
280.4
lb/kft
o
356
F
o
8.94E-07
/F
9.65E-06
/oF
16.3
Msi
9.6
Msi

Metric
Imperial
0.1862
ohm/km
0.2997
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1902
ohm/km
0.3062
ohm/mile
0.2277
ohm/km
0.3665
ohm/mile
0.3064
ohm/km
0.4931
ohm/mile
519
@ 100C & 50 Hz
765
@ 180C & 50 Hz
0.006
m
0.021
ft
0.242
ohm/km
0.468
ohm/mile
0.210
Mohm-km
0.109
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 155 sq. mm (305.9 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-081-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Copenhagen
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-003)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
219.9
mm2
5.97
mm
28.0
mm2
18.29
mm
247.9
mm2
72.8
kN
60.4
kN
54
kg/km
661.0
kg/km
607.0
kg/km
o
180
C
o
1.61E-06
/C
1.88E-05
/oC
112.3
GPa
64.1
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
434.0
kcmil
0.235
in.
0.043
in2
0.720
in.
0.384
in2
16.4
kips
13.6
kips
36
lb/kft
444.2
lb/kft
407.9
lb/kft
o
356
F
o
8.94E-07
/F
1.04E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.1272
ohm/km
0.2047
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1301
ohm/km
0.2097
ohm/mile
0.1557
ohm/km
0.2508
ohm/mile
0.2094
ohm/km
0.3371
ohm/mile
656
@ 100C & 50 Hz
971
@ 180C & 50 Hz
0.007
m
0.024
ft
0.233
ohm/km
0.451
ohm/mile
0.201
Mohm-km
0.104
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 226.4 sq. mm (446.7 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-083-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Glasgow
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-005)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
236.7
mm2
7.75
mm
47.1
mm2
19.53
mm
283.8
mm2
115.0
kN
101.7
kN
86
kg/km
731.3
kg/km
645.3
kg/km
o
180
C
o
1.61E-06
/C
1.71E-05
/oC
112.3
GPa
67.0
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
467.1
kcmil
0.305
in.
0.073
in2
0.769
in.
0.440
in2
25.9
kips
22.9
kips
58
lb/kft
491.5
lb/kft
433.7
lb/kft
o
356
F
o
8.94E-07
/F
9.49E-06
/oF
16.3
Msi
9.7
Msi

Metric
Imperial
0.1184
ohm/km
0.1905
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1211
ohm/km
0.1951
ohm/mile
0.1449
ohm/km
0.2334
ohm/mile
0.1949
ohm/km
0.3138
ohm/mile
692
@ 100C & 50 Hz
1027
@ 180C & 50 Hz
0.008
m
0.026
ft
0.228
ohm/km
0.441
ohm/mile
0.197
Mohm-km
0.102
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 243.7 sq. mm (480.9 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-084-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Casablanca
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-004)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
273.6
mm2
7.11
mm
39.7
mm2
20.50
mm
313.3
mm2
101.1
kN
85.7
kN
76
kg/km
834.4
kg/km
758.4
kg/km
o
180
C
o
1.61E-06
/C
1.83E-05
/oC
112.3
GPa
64.9
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
539.9
kcmil
0.280
in.
0.062
in2
0.807
in.
0.486
in2
22.7
kips
19.3
kips
51
lb/kft
560.8
lb/kft
509.7
lb/kft
o
356
F
o
8.94E-07
/F
1.02E-05
/oF
16.3
Msi
9.4
Msi

Metric
Imperial
0.1024
ohm/km
0.1648
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1049
ohm/km
0.1691
ohm/mile
0.1255
ohm/km
0.2022
ohm/mile
0.1686
ohm/km
0.2716
ohm/mile
754
@ 100C & 50 Hz
1120
@ 180C & 50 Hz
0.008
m
0.027
ft
0.226
ohm/km
0.436
ohm/mile
0.194
Mohm-km
0.101
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 281.6 sq. mm (555.8 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-085-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Reykjavik
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-004)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
223.1
mm2
7.11
mm
39.7
mm2
18.82
mm
262.8
mm2
98.3
kN
85.7
kN
76
kg/km
693.6
kg/km
617.6
kg/km
o
180
C
o
1.61E-06
/C
1.75E-05
/oC
112.3
GPa
66.2
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
440.3
kcmil
0.280
in.
0.062
in2
0.741
in.
0.407
in2
22.1
kips
19.3
kips
51
lb/kft
466.2
lb/kft
415.1
lb/kft
o
356
F
o
8.94E-07
/F
9.75E-06
/oF
16.3
Msi
9.6
Msi

Metric
Imperial
0.1256
ohm/km
0.2021
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1285
ohm/km
0.2070
ohm/mile
0.1537
ohm/km
0.2476
ohm/mile
0.2067
ohm/km
0.3328
ohm/mile
665
@ 100C & 50 Hz
986
@ 180C & 50 Hz
0.008
m
0.025
ft
0.231
ohm/km
0.446
ohm/mile
0.199
Mohm-km
0.103
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 229.7 sq. mm (453.2 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-087-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Lisbon
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-004)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
315.5
mm2
7.11
mm
39.7
mm2
21.79
mm
355.2
mm2
103.4
kN
85.7
kN
76
kg/km
947.6
kg/km
871.6
kg/km
o
180
C
o
1.61E-06
/C
1.88E-05
/oC
112.3
GPa
64.1
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
622.6
kcmil
0.280
in.
0.062
in2
0.858
in.
0.551
in2
23.2
kips
19.3
kips
51
lb/kft
636.9
lb/kft
585.8
lb/kft
o
356
F
o
8.94E-07
/F
1.05E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.0887
ohm/km
0.1427
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0910
ohm/km
0.1469
ohm/mile
0.1088
ohm/km
0.1754
ohm/mile
0.1461
ohm/km
0.2354
ohm/mile
823
@ 100C & 50 Hz
1227
@ 180C & 50 Hz
0.009
m
0.029
ft
0.222
ohm/km
0.430
ohm/mile
0.191
Mohm-km
0.099
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 324.8 sq. mm (640.9 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-089-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Amsterdam
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-005)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
367.4
mm2
7.75
mm
47.1
mm2
23.55
mm
414.5
mm2
122.4
kN
101.7
kN
86
kg/km
1101.6
kg/km
1015.6
kg/km
o
180
C
o
1.61E-06
/C
1.88E-05
/oC
112.3
GPa
64.2
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
725.1
kcmil
0.305
in.
0.073
in2
0.927
in.
0.642
in2
27.5
kips
22.9
kips
58
lb/kft
740.4
lb/kft
682.6
lb/kft
o
356
F
o
8.94E-07
/F
1.04E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.0762
ohm/km
0.1226
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0784
ohm/km
0.1265
ohm/mile
0.0936
ohm/km
0.1510
ohm/mile
0.1256
ohm/km
0.2024
ohm/mile
907
@ 100C & 50 Hz
1355
@ 180C & 50 Hz
0.010
m
0.031
ft
0.217
ohm/km
0.420
ohm/mile
0.186
Mohm-km
0.097
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 378.2 sq. mm (746.4 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-091-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Brussels
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-006)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
421.4
mm2
8.13
mm
51.9
mm2
25.15
mm
473.3
mm2
135.7
kN
112.0
kN
98
kg/km
1264.8
kg/km
1166.8
kg/km
o
180
C
o
1.61E-06
/C
1.89E-05
/oC
112.3
GPa
64.0
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
831.6
kcmil
0.320
in.
0.080
in2
0.990
in.
0.734
in2
30.5
kips
25.2
kips
66
lb/kft
850.1
lb/kft
784.2
lb/kft
o
356
F
o
8.94E-07
/F
1.05E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.0666
ohm/km
0.1072
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0687
ohm/km
0.1110
ohm/mile
0.0820
ohm/km
0.1323
ohm/mile
0.1099
ohm/km
0.1771
ohm/mile
987
@ 100C & 50 Hz
1479
@ 180C & 50 Hz
0.010
m
0.033
ft
0.213
ohm/km
0.412
ohm/mile
0.183
Mohm-km
0.095
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 433.8 sq. mm (856.1 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-093-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Oslo
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
313.8
mm2
8.76
mm
60.3
mm2
22.40
mm
374.1
mm2
147.9
kN
130.2
kN
113
kg/km
980.2
kg/km
867.2
kg/km
o
180
C
o
1.45E-06
/C
1.70E-05
/oC
116.0
GPa
67.4
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
619.3
kcmil
0.345
in.
0.093
in2
0.882
in.
0.580
in2
33.2
kips
29.3
kips
76
lb/kft
658.8
lb/kft
582.8
lb/kft
o
356
F
o
8.06E-07
/F
9.47E-06
/oF
16.8
Msi
9.8
Msi

Metric
Imperial
0.0893
ohm/km
0.1437
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0911
ohm/km
0.1476
ohm/mile
0.1091
ohm/km
0.1764
ohm/mile
0.1469
ohm/km
0.2369
ohm/mile
828
@ 100C & 50 Hz
1234
@ 180C & 50 Hz
0.009
m
0.030
ft
0.220
ohm/km
0.424
ohm/mile
0.189
Mohm-km
0.098
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 323 sq. mm (637.5 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-094-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Stockholm 2L
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
463.3
mm2
8.76
mm
60.3
mm2
26.40
mm
523.6
mm2
156.3
kN
130.2
kN
113
kg/km
1394.3
kg/km
1281.3
kg/km
o
180
C
o
1.45E-06
/C
1.86E-05
/oC
116.0
GPa
64.7
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
914.3
kcmil
0.345
in.
0.093
in2
1.039
in.
0.812
in2
35.1
kips
29.3
kips
76
lb/kft
937.1
lb/kft
861.2
lb/kft
o
356
F
o
8.06E-07
/F
1.03E-05
/oF
16.8
Msi
9.4
Msi

Metric
Imperial
0.0605
ohm/km
0.0974
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0625
ohm/km
0.1011
ohm/mile
0.0746
ohm/km
0.1205
ohm/mile
0.0999
ohm/km
0.1610
ohm/mile
1049
@ 100C & 50 Hz
1576
@ 180C & 50 Hz
0.011
m
0.035
ft
0.210
ohm/km
0.406
ohm/mile
0.180
Mohm-km
0.093
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 476.9 sq. mm (941.2 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-095-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Warsaw
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
507.5
mm2
8.76
mm
60.3
mm2
27.72
mm
567.8
mm2
158.7
kN
130.2
kN
113
kg/km
1519.8
kg/km
1406.8
kg/km
o
180
C
o
1.45E-06
/C
1.89E-05
/oC
116.0
GPa
64.2
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1001.5
kcmil
0.345
in.
0.093
in2
1.091
in.
0.880
in2
35.7
kips
29.3
kips
76
lb/kft
1021.4
lb/kft
945.5
lb/kft
o
356
F
o
8.06E-07
/F
1.05E-05
/oF
16.8
Msi
9.3
Msi

Metric
Imperial
0.0553
ohm/km
0.0890
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0573
ohm/km
0.0928
ohm/mile
0.0683
ohm/km
0.1104
ohm/mile
0.0914
ohm/km
0.1474
ohm/mile
1112
@ 100C & 50 Hz
1673
@ 180C & 50 Hz
0.011
m
0.037
ft
0.207
ohm/km
0.401
ohm/mile
0.177
Mohm-km
0.092
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 522.4 sq. mm (1031 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-096-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Dublin
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
524.5
mm2
9.53
mm
71.3
mm2
28.14
mm
595.8
mm2
183.3
kN
153.8
kN
132
kg/km
1583.0
kg/km
1451.0
kg/km
o
180
C
o
1.61E-06
/C
1.86E-05
/oC
112.3
GPa
64.5
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1035.1
kcmil
0.375
in.
0.111
in2
1.108
in.
0.923
in2
41.2
kips
34.6
kips
89
lb/kft
1063.9
lb/kft
975.2
lb/kft
o
356
F
o
8.94E-07
/F
1.03E-05
/oF
16.3
Msi
9.4
Msi

Metric
Imperial
0.0534
ohm/km
0.0859
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0553
ohm/km
0.0897
ohm/mile
0.0660
ohm/km
0.1067
ohm/mile
0.0883
ohm/km
0.1423
ohm/mile
1136
@ 100C & 50 Hz
1711
@ 180C & 50 Hz
0.011
m
0.038
ft
0.206
ohm/km
0.398
ohm/mile
0.176
Mohm-km
0.091
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 539.9 sq. mm (1065.5 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-098-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Hamburg
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
546.4
mm2
8.76
mm
60.3
mm2
28.62
mm
606.7
mm2
160.9
kN
130.2
kN
113
kg/km
1626.9
kg/km
1513.9
kg/km
o
180
C
o
1.45E-06
/C
1.91E-05
/oC
116.0
GPa
63.8
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1078.3
kcmil
0.345
in.
0.093
in2
1.127
in.
0.940
in2
36.2
kips
29.3
kips
76
lb/kft
1093.4
lb/kft
1017.5
lb/kft
o
356
F
o
8.06E-07
/F
1.06E-05
/oF
16.8
Msi
9.2
Msi

Metric
Imperial
0.0514
ohm/km
0.0827
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0534
ohm/km
0.0866
ohm/mile
0.0636
ohm/km
0.1030
ohm/mile
0.0850
ohm/km
0.1372
ohm/mile
1163
@ 100C & 50 Hz
1752
@ 180C & 50 Hz
0.012
m
0.038
ft
0.206
ohm/km
0.397
ohm/mile
0.175
Mohm-km
0.091
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 562.5 sq. mm (1110 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-099-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Milan
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
567.7
mm2
8.76
mm
60.3
mm2
29.10
mm
628.0
mm2
162.1
kN
130.2
kN
113
kg/km
1686.1
kg/km
1573.1
kg/km
o
180
C
o
1.45E-06
/C
1.93E-05
/oC
116.0
GPa
63.6
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1120.3
kcmil
0.345
in.
0.093
in2
1.146
in.
0.973
in2
36.4
kips
29.3
kips
76
lb/kft
1133.2
lb/kft
1057.2
lb/kft
o
356
F
o
8.06E-07
/F
1.07E-05
/oF
16.8
Msi
9.2
Msi

Metric
Imperial
0.0494
ohm/km
0.0795
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0514
ohm/km
0.0835
ohm/mile
0.0612
ohm/km
0.0991
ohm/mile
0.0818
ohm/km
0.1320
ohm/mile
1191
@ 100C & 50 Hz
1797
@ 180C & 50 Hz
0.012
m
0.039
ft
0.205
ohm/km
0.395
ohm/mile
0.174
Mohm-km
0.090
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 584.4 sq. mm (1153.3 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-100-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Rome
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
592.5
mm2
9.53
mm
71.3
mm2
29.89
mm
663.8
mm2
187.1
kN
153.8
kN
132
kg/km
1773.8
kg/km
1641.8
kg/km
o
180
C
o
1.61E-06
/C
1.90E-05
/oC
112.3
GPa
63.8
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1169.3
kcmil
0.375
in.
0.111
in2
1.177
in.
1.029
in2
42.1
kips
34.6
kips
89
lb/kft
1192.1
lb/kft
1103.4
lb/kft
o
356
F
o
8.94E-07
/F
1.06E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.0474
ohm/km
0.0763
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0494
ohm/km
0.0802
ohm/mile
0.0588
ohm/km
0.0952
ohm/mile
0.0785
ohm/km
0.1267
ohm/mile
1225
@ 100C & 50 Hz
1850
@ 180C & 50 Hz
0.012
m
0.040
ft
0.203
ohm/km
0.391
ohm/mile
0.173
Mohm-km
0.089
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 609.9 sq. mm (1203.7 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-101-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Vienna
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
629.2
mm2
8.76
mm
60.3
mm2
30.42
mm
689.5
mm2
165.6
kN
130.2
kN
113
kg/km
1852.3
kg/km
1739.3
kg/km
o
180
C
o
1.45E-06
/C
1.96E-05
/oC
115.9
GPa
63.1
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1241.7
kcmil
0.345
in.
0.093
in2
1.198
in.
1.069
in2
37.2
kips
29.3
kips
76
lb/kft
1244.9
lb/kft
1169.0
lb/kft
o
356
F
o
8.06E-07
/F
1.09E-05
/oF
16.8
Msi
9.1
Msi

Metric
Imperial
0.0445
ohm/km
0.0716
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0466
ohm/km
0.0758
ohm/mile
0.0554
ohm/km
0.0898
ohm/mile
0.0738
ohm/km
0.1192
ohm/mile
1269
@ 100C & 50 Hz
1918
@ 180C & 50 Hz
0.012
m
0.040
ft
0.202
ohm/km
0.390
ohm/mile
0.172
Mohm-km
0.089
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 647.7 sq. mm (1278.2 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-103-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Budapest
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
668.3
mm2
9.53
mm
71.3
mm2
31.50
mm
739.6
mm2
191.4
kN
153.8
kN
132
kg/km
1983.9
kg/km
1851.9
kg/km
o
180
C
o
1.61E-06
/C
1.94E-05
/oC
112.3
GPa
63.2
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1318.9
kcmil
0.375
in.
0.111
in2
1.240
in.
1.146
in2
43.0
kips
34.6
kips
89
lb/kft
1333.3
lb/kft
1244.6
lb/kft
o
356
F
o
8.94E-07
/F
1.08E-05
/oF
16.3
Msi
9.2
Msi

Metric
Imperial
0.0420
ohm/km
0.0676
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0440
ohm/km
0.0717
ohm/mile
0.0523
ohm/km
0.0849
ohm/mile
0.0697
ohm/km
0.1126
ohm/mile
1318
@ 100C & 50 Hz
1996
@ 180C & 50 Hz
0.013
m
0.042
ft
0.200
ohm/km
0.385
ohm/mile
0.170
Mohm-km
0.088
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 688 sq. mm (1357.7 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-104-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Prague
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
690.7
mm2
8.76
mm
60.3
mm2
31.77
mm
751.0
mm2
169.1
kN
130.2
kN
113
kg/km
2029.8
kg/km
1916.8
kg/km
o
180
C
o
1.45E-06
/C
1.98E-05
/oC
116.0
GPa
62.7
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1363.1
kcmil
0.345
in.
0.093
in2
1.251
in.
1.164
in2
38.0
kips
29.3
kips
76
lb/kft
1364.2
lb/kft
1288.3
lb/kft
o
356
F
o
8.06E-07
/F
1.10E-05
/oF
16.8
Msi
9.1
Msi

Metric
Imperial
0.0407
ohm/km
0.0655
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0428
ohm/km
0.0699
ohm/mile
0.0508
ohm/km
0.0826
ohm/mile
0.0676
ohm/km
0.1093
ohm/mile
1340
@ 100C & 50 Hz
2032
@ 180C & 50 Hz
0.013
m
0.042
ft
0.199
ohm/km
0.385
ohm/mile
0.169
Mohm-km
0.088
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 711 sq. mm (1403.2 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-105-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Munich
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
733.2
mm2
9.53
mm
71.3
mm2
32.85
mm
804.5
mm2
195.0
kN
153.8
kN
132
kg/km
2169.5
kg/km
2037.5
kg/km
o
180
C
o
1.61E-06
/C
1.96E-05
/oC
112.3
GPa
62.8
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1446.9
kcmil
0.375
in.
0.111
in2
1.293
in.
1.247
in2
43.8
kips
34.6
kips
89
lb/kft
1458.1
lb/kft
1369.4
lb/kft
o
356
F
o
8.94E-07
/F
1.09E-05
/oF
16.3
Msi
9.1
Msi

Metric
Imperial
0.0384
ohm/km
0.0618
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0405
ohm/km
0.0661
ohm/mile
0.0480
ohm/km
0.0781
ohm/mile
0.0638
ohm/km
0.1032
ohm/mile
1392
@ 100C & 50 Hz
2113
@ 180C & 50 Hz
0.013
m
0.043
ft
0.197
ohm/km
0.381
ohm/mile
0.167
Mohm-km
0.087
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 754.8 sq. mm (1489.5 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-106-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC London
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-009)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
759.0
mm2
9.78
mm
75.1
mm2
33.40
mm
834.1
mm2
204.8
kN
162.1
kN
143
kg/km
2248.1
kg/km
2105.1
kg/km
o
180
C
o
1.61E-06
/C
1.96E-05
/oC
112.3
GPa
62.9
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1497.9
kcmil
0.385
in.
0.116
in2
1.315
in.
1.293
in2
46.0
kips
36.4
kips
96
lb/kft
1510.9
lb/kft
1414.8
lb/kft
o
356
F
o
8.94E-07
/F
1.09E-05
/oF
16.3
Msi
9.1
Msi

Metric
Imperial
0.0370
ohm/km
0.0595
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0391
ohm/km
0.0639
ohm/mile
0.0464
ohm/km
0.0754
ohm/mile
0.0616
ohm/km
0.0996
ohm/mile
1424
@ 100C & 50 Hz
2164
@ 180C & 50 Hz
0.013
m
0.044
ft
0.196
ohm/km
0.379
ohm/mile
0.166
Mohm-km
0.086
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 781.3 sq. mm (1541.9 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-107-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Paris
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
813.7
mm2
8.76
mm
60.3
mm2
34.16
mm
874.0
mm2
176.0
kN
130.2
kN
113
kg/km
2365.4
kg/km
2252.4
kg/km
o
180
C
o
1.45E-06
/C
2.03E-05
/oC
116.0
GPa
62.0
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1605.8
kcmil
0.345
in.
0.093
in2
1.345
in.
1.355
in2
39.6
kips
29.3
kips
76
lb/kft
1589.7
lb/kft
1513.8
lb/kft
o
356
F
o
8.06E-07
/F
1.13E-05
/oF
16.8
Msi
9.0
Msi

Metric
Imperial
0.0345
ohm/km
0.0555
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0368
ohm/km
0.0604
ohm/mile
0.0435
ohm/km
0.0710
ohm/mile
0.0576
ohm/km
0.0933
ohm/mile
1480
@ 100C & 50 Hz
2254
@ 180C & 50 Hz
0.014
m
0.045
ft
0.195
ohm/km
0.377
ohm/mile
0.165
Mohm-km
0.085
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 837.6 sq. mm (1653 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-109-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Antwerp
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-009)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
944.9
mm2
9.78
mm
75.1
mm2
36.85
mm
1020.0
mm2
215.3
kN
162.1
kN
143
kg/km
2759.1
kg/km
2616.1
kg/km
o
180
C
o
1.61E-06
/C
2.02E-05
/oC
112.3
GPa
62.0
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1864.7
kcmil
0.385
in.
0.116
in2
1.451
in.
1.581
in2
48.4
kips
36.4
kips
96
lb/kft
1854.3
lb/kft
1758.2
lb/kft
o
356
F
o
8.94E-07
/F
1.12E-05
/oF
16.3
Msi
9.0
Msi

Metric
Imperial
0.0297
ohm/km
0.0478
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0321
ohm/km
0.0529
ohm/mile
0.0378
ohm/km
0.0619
ohm/mile
0.0498
ohm/km
0.0808
ohm/mile
1623
@ 100C & 50 Hz
2483
@ 180C & 50 Hz
0.015
m
0.048
ft
0.190
ohm/km
0.367
ohm/mile
0.161
Mohm-km
0.083
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 972.7 sq. mm (1919.6 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-110-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Berlin (Madrid Ice)


NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-011)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
1006.5
mm2
10.54
mm
87.3
mm2
38.20
mm
1093.8
mm2
244.9
kN
188.3
kN
164
kg/km
2948.8
kg/km
2784.8
kg/km
o
180
C
o
1.61E-06
/C
2.00E-05
/oC
112.3
GPa
62.3
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1986.3
kcmil
0.415
in.
0.135
in2
1.504
in.
1.695
in2
55.1
kips
42.3
kips
110
lb/kft
1981.9
lb/kft
1871.6
lb/kft
o
356
F
o
8.94E-07
/F
1.11E-05
/oF
16.3
Msi
9.0
Msi

Metric
Imperial
0.0278
ohm/km
0.0447
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0303
ohm/km
0.0499
ohm/mile
0.0356
ohm/km
0.0583
ohm/mile
0.0467
ohm/km
0.0759
ohm/mile
1692
@ 100C & 50 Hz
2594
@ 180C & 50 Hz
0.015
m
0.050
ft
0.188
ohm/km
0.363
ohm/mile
0.159
Mohm-km
0.082
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1036.1 sq. mm (2044.7 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-112-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Madrid
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-009)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
1013.1
mm2
9.78
mm
75.1
mm2
38.20
mm
1088.2
mm2
219.1
kN
162.1
kN
143
kg/km
2947.8
kg/km
2804.8
kg/km
o
180
C
o
1.61E-06
/C
2.04E-05
/oC
112.3
GPa
61.8
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1999.3
kcmil
0.385
in.
0.116
in2
1.504
in.
1.687
in2
49.3
kips
36.4
kips
96
lb/kft
1981.2
lb/kft
1885.1
lb/kft
o
356
F
o
8.94E-07
/F
1.13E-05
/oF
16.3
Msi
9.0
Msi

Metric
Imperial
0.0276
ohm/km
0.0444
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0302
ohm/km
0.0498
ohm/mile
0.0354
ohm/km
0.0581
ohm/mile
0.0464
ohm/km
0.0755
ohm/mile
1696
@ 100C & 50 Hz
2602
@ 180C & 50 Hz
0.015
m
0.050
ft
0.188
ohm/km
0.363
ohm/mile
0.159
Mohm-km
0.082
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1042.9 sq. mm (2058.1 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-113-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Monte Carlo


NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-011)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
228.5
mm2
10.54
mm
87.3
mm2
20.78
mm
315.8
mm2
201.2
kN
188.3
kN
164
kg/km
798.7
kg/km
634.7
kg/km
o
180
C
o
1.61E-06
/C
1.39E-05
/oC
112.3
GPa
73.0
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
450.9
kcmil
0.415
in.
0.135
in2
0.818
in.
0.489
in2
45.2
kips
42.3
kips
110
lb/kft
536.8
lb/kft
426.5
lb/kft
o
356
F
o
8.94E-07
/F
7.74E-06
/oF
16.3
Msi
10.6
Msi

Metric
Imperial
0.1230
ohm/km
0.1979
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.1257
ohm/km
0.2024
ohm/mile
0.1504
ohm/km
0.2422
ohm/mile
0.2024
ohm/km
0.3258
ohm/mile
691
@ 100C & 50 Hz
1027
@ 180C & 50 Hz
0.009
m
0.029
ft
0.222
ohm/km
0.429
ohm/mile
0.194
Mohm-km
0.100
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 235.2 sq. mm (464.2 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-133-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Stockholm 3L
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-008)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
453.7
mm2
8.76
mm
60.3
mm2
26.40
mm
514.0
mm2
155.7
kN
130.2
kN
113
kg/km
1367.8
kg/km
1254.8
kg/km
o
180
C
o
1.45E-06
/C
1.85E-05
/oC
116.0
GPa
64.8
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
895.4
kcmil
0.345
in.
0.093
in2
1.039
in.
0.797
in2
35.0
kips
29.3
kips
76
lb/kft
919.3
lb/kft
843.3
lb/kft
o
356
F
o
8.06E-07
/F
1.03E-05
/oF
16.8
Msi
9.4
Msi

Metric
Imperial
0.0617
ohm/km
0.0993
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0637
ohm/km
0.1031
ohm/mile
0.0760
ohm/km
0.1228
ohm/mile
0.1019
ohm/km
0.1642
ohm/mile
1039
@ 100C & 50 Hz
1560
@ 180C & 50 Hz
0.011
m
0.035
ft
0.210
ohm/km
0.406
ohm/mile
0.180
Mohm-km
0.093
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 467 sq. mm (921.7 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-134-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Kolkata
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
543.5
mm2
9.53
mm
71.3
mm2
28.62
mm
614.8
mm2
184.4
kN
153.8
kN
132
kg/km
1643.2
kg/km
1511.2
kg/km
o
180
C
o
1.61E-06
/C
1.87E-05
/oC
112.3
GPa
64.3
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1072.6
kcmil
0.375
in.
0.111
in2
1.127
in.
0.953
in2
41.5
kips
34.6
kips
89
lb/kft
1104.4
lb/kft
1015.7
lb/kft
o
356
F
o
8.94E-07
/F
1.04E-05
/oF
16.3
Msi
9.3
Msi

Metric
Imperial
0.0517
ohm/km
0.0832
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0536
ohm/km
0.0870
ohm/mile
0.0639
ohm/km
0.1034
ohm/mile
0.0855
ohm/km
0.1378
ohm/mile
1160
@ 100C & 50 Hz
1748
@ 180C & 50 Hz
0.012
m
0.038
ft
0.205
ohm/km
0.396
ohm/mile
0.175
Mohm-km
0.091
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 559.5 sq. mm (1104.1 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-135-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Mumbai
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
685.4
mm2
9.53
mm
71.3
mm2
31.77
mm
756.7
mm2
192.4
kN
153.8
kN
132
kg/km
2034.9
kg/km
1902.9
kg/km
o
180
C
o
1.61E-06
/C
1.94E-05
/oC
112.3
GPa
63.1
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1352.6
kcmil
0.375
in.
0.111
in2
1.251
in.
1.173
in2
43.3
kips
34.6
kips
89
lb/kft
1367.6
lb/kft
1278.9
lb/kft
o
356
F
o
8.94E-07
/F
1.08E-05
/oF
16.3
Msi
9.2
Msi

Metric
Imperial
0.0410
ohm/km
0.0660
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0431
ohm/km
0.0701
ohm/mile
0.0511
ohm/km
0.0830
ohm/mile
0.0681
ohm/km
0.1101
ohm/mile
1336
@ 100C & 50 Hz
2025
@ 180C & 50 Hz
0.013
m
0.042
ft
0.199
ohm/km
0.384
ohm/mile
0.169
Mohm-km
0.088
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 705.6 sq. mm (1392.4 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-136-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Athens
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-011)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
1409.7
mm2
10.54
mm
87.3
mm2
44.75
mm
1497.0
mm2
267.6
kN
188.3
kN
164
kg/km
4065.7
kg/km
3901.7
kg/km
o
180
C
o
1.61E-06
/C
2.07E-05
/oC
112.3
GPa
61.2
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
2782.0
kcmil
0.415
in.
0.135
in2
1.762
in.
2.320
in2
60.2
kips
42.3
kips
110
lb/kft
2732.5
lb/kft
2622.3
lb/kft
o
356
F
o
8.94E-07
/F
1.15E-05
/oF
16.3
Msi
8.9
Msi

Metric
Imperial
0.0199
ohm/km
0.0320
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0231
ohm/km
0.0388
ohm/mile
0.0267
ohm/km
0.0402
ohm/mile
0.0343
ohm/km
0.0432
ohm/mile
2050
@ 100C & 50 Hz
3189
@ 180C & 50 Hz
0.018
m
0.058
ft
0.178
ohm/km
0.345
ohm/mile
0.150
Mohm-km
0.077
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1451.2 sq. mm (2863.8 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-137-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATA SHEET:

ACCC Bordeaux
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 200-011)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor1,2
Rated Strength of Core - 313 ksi (2158 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint

Metric
880.9
mm2
10.54
mm
87.3
mm2
35.76
mm
968.2
mm2
237.9
kN
188.3
kN
164
kg/km
2766.2
kg/km
2602.2
kg/km
o
180
C
o
1.61E-06
/C
1.96E-05
/oC
112.3
GPa
62.9
GPa

Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Imperial
1738.4
kcmil
0.415
in.
0.135
in2
1.408
in.
1.501
in2
53.5
kips
42.3
kips
110
lb/kft
1859.1
lb/kft
1748.9
lb/kft
o
356
F
o
8.94E-07
/F
1.09E-05
/oF
16.3
Msi
9.1
Msi

Metric
Imperial
0.0318
ohm/km
0.0512
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0340
ohm/km
0.0559
ohm/mile
0.0402
ohm/km
0.0656
ohm/mile
0.0531
ohm/km
0.0861
ohm/mile
1560
@ 100C & 50 Hz
2381
@ 180C & 50 Hz
0.014
m
0.047
ft
0.192
ohm/km
0.370
ohm/mile
0.162
Mohm-km
0.084
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 906.8 sq. mm (1789.6 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-138-D

www.ctcglobal.com

Date Produced:

8/28/2012

DATASHEET:

ACCCULSLiepzig(ULSBrusselsIce)
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com
Governing Units: Metric
Mechanical Specifications
Nominal Aluminum Cross-sectional Area*
Nominal Diameter of Composite Core (CTC Part Number 210-007)
Nominal Cross-sectional Area of Core
Overall Diameter of Conductor
Nominal Cross-sectional Area of the Conductor
Ultimate Tensile Strength of Conductor 1,2
Rated Strength of Core - 375 ksi (2586 MPa)
Core Nominal Mass per unit length
Conductor Nominal Mass per unit length
Aluminum Nominal Mass per unit length**
Maximum Allowable Operating Temperature at Surface4
Coefficient of Linear Expansion Above Thermal Kneepoint
Coefficient of Linear Expansion Below Thermal Kneepoint
Final Modulus of Elasticity Above Thermal Kneepoint
Final Modulus of Elasticity Below Thermal Kneepoint
Electrical Specifications
Nominal Resistivity of Aluminum at 20C, DC 63% IACS
Temperature Coefficient of Resistance
Frequency
AC Nominal Resistance at 25C
AC Nominal Resistance at 75C
AC Nominal Resistance at 180C
AC Current Rating at Given Temperature3
GMR (estimated)
Inductive Reactance
Capacitive Reactance

Metric
406.4
mm2
9.53
mm
71.3
mm2
25.14
mm
477.7
mm2
207.1
kN
184.2
kN
128
kg/km
1253.6
kg/km
1125.6
kg/km
o
180
C
o
7.51E-07
/C
1.62E-05
/oC
146.7
GPa
71.2
GPa

Imperial
802.0
kcmil
0.375
in.
0.111
in2
0.990
in.
0.740
in2
46.6
kips
41.4
kips
86
lb/kft
842.5
lb/kft
756.5
lb/kft
o
356
F
o
4.17E-07
/F
8.99E-06
/oF
21.3
Msi
10.3
Msi

Metric
Imperial
0.0690
ohm/km
0.1110
ohm/mile
0.00403
0.00403
50
Hz
60
Hz
0.0710
ohm/km
0.0000
ohm/mile
0.0848
ohm/km
0.0000
ohm/mile
0.1138
ohm/km
0.0000
ohm/mile
1145
@ 100C & 50 Hz
1506
@ 180C & 50 Hz
0.010
m
0.034
ft
0.213
ohm/km
0.411
ohm/mile
0.183
Mohm-km
0.095
Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 418.4 sq. mm (825.6 kcmil)
**ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.
1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540.
2) Strength at ambient temperature
3) Conditions: 1.6 ft/s (0.477 m/s) wind, 2624.7 ft (800 m) Elevation, 0.5 Emis. 0.5 absorp. 5C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor).
The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight
variations in some of the indicated values.

F-730-145-D

www.ctcglobal.com