You are on page 1of 5

WPS750D6/S

EP Series

Features:

Rotate speed governor: Electronic


Excitation system: AREP
A.V.R model: R450
Emergency stop switch
ATS (automatic transfer switch) receptacle
4x12V sealed for life maintenance free battery
Lockable battery isolator switch
Powder coated canopy
(Only for Soundproofed sets)
50radiator
Oil pump on the engine
Steel base frame with fork holes
Vibration isolators between the engine/alternator and
base frame
Dry type air filter
Base fuel tank for daily running
Drain points for fuel tank
Operation Manual / Specifications

Output Ratings
GeneratingSet
PrimePower*
Model
WPS750D6
675kW/844kVA
WPS750D6S
675kW/844kVA

StandbyPower**
743kW/928kVA
743kW/928kVA

Ratingsat0.8powerfactor

Dimensions and Weights

Ratings and Performance Data

Model
WPS750D6
WPS750D6S

Length (L)
mm

Width (W)
mm

Height (H)
mm

Dry Weight
kg

4278
6058

1907
2438

2272
2725

6996
11157

Engine Make & Model:

Perkins

4006-23TAG3A

Alternator Brand:

Leroy somer

Alternator Model:

LSA49.1M75

Control System:

Auto Gen

Circuit Breaker Type:

3 Pole MCCB

Frequency & Phase:

60HZ & 3PH

Engine Speed: RPM

1800

Notes:
***
*Prime
Power

Continuous
duty operation, under variable load 24/24h-10% over load

permissible
1 hour/12 hours;

**Standby
Power

Standby
duty, operation under variable load, without over load;

Fuel Tank Capacity: litres


WPS750D6
WPS750D6S
Fuel Consumption: l/hr
(100% Load)
- Prime Power
-Standby Power

Standard Reference Conditions

Note: Standard reference conditions 25C (77F) Air Inlet Temp, 100m(328

ft) A.S.L. 30% relative humidity.

Fuel
consumption data at full load with diesel fuel with specific gravity of

0.85
and conforming to BS2869: 1998, Class A2.

www.powerlinkworld.com

1100
1150

175
203

1/5

WPS750D6/S

EP Series

Engine model:4006-23TAG3A

EngineTechnicalData

CoolingSystem

6/Vertical, in-line

Cooling System Capacity: l

105

Cycle:

4 Stroke

Capacity without Radiator: l

N/A

Bore / Stroke: mm

160/190

Energy to Water & Lube Oil:

No. of Cylinders / Alignment:

Induction:

Turbocharged

Cooling Method:

Water cooled

Governing Type:

Electronic

kW

Compression Ratio:

13.6:1

Displacement:

22.92L

Moment of Inertia: kg m
Engine Electrical System:
- Voltage / Ground
- Battery Charger Amps
Weight: kg

- Dry
- Wet

- Prime 80
- Standby 90
Energy to Cooling Fan: kW

4.59

38

Radiator Cooling Airflow: m/min

960/960

External Restriction to
Cooling Airflow: Pa

28/Insulated return
28/40
2524
2663

309
330

Energy to Radiation:
kW

N/A

Governing Class:

- Prime
- Standby

N/A

Designed to operate in ambient conditions up to 50C (122F).


Contact your local PowerLink Dealer for power ratings at specific site
conditions

Performance

1800

Fuel Filter Type: Replaceable Element

- Prime

759

Recommended Fuel: Diesel Class A2

- Standby

839

- Prime

2200

- Standby

2432

Engine Speed: rpm


Gross Engine Power: kW

FuelSystem

BMEP: kPa

Fuel Consumption: l/hr


Prime

110%
Load

100%
Load

75%
Load

50%
Load

WPS750D6

203

175

132

88

WPS750D6
S

203

175

132

88

LubricationSystem

Oil Filter Type:


Total Oil Capacity: l
Minimum: l
Oil Type:

Spin-On, Full Flow


113.4
90.7
API-CG4 15W/40

(Based on diesel fuel with a specific gravity of 0.85 and


conforming to BS2869,Class A2)

Oil Cooling Method:

Water-cooled

ExhaustSystem

AirSystems

Silencer Type:
Exhaust Outlet Size(internal):

Industrial
Air Filter Type:

2*152.4mm

Silencer Noise Reduction Level:

N/A

Maximum Allowable Back


Pressure: kPa

3.0

Combustion Air Flow: m/min


- Prime
- Standby

Exhaust Gas Flow: m/min


- Prime
- Standby

209
209

Max. Air Intake Restriction:


-clean filter
-dirty filter

Exhaust Gas Temperature: C


- Prime
- Standby

500
500

www.powerlinkworld.com

Dry-paper

76
78
127 mm H2O
380 mm H2O

The weights are approximate and without fuel.

2/5

WPS750D6/S

EP Series

Alternator model: LSA49.1M75

Alternator Physical Data

Alternator Operating Data

Manufactured by:

Leroy somer

Model:

LSA49.1M75

Overspeed: rpm
Voltage Regulation: (Steady state)

Single

No. of Bearings:

IP23

Ingress Protection Rating:


Excitation System:

<2%

Total Harmonic content LL/LN:

Wires:

<50

Wave Form IEC = THF:

2/3

Winding Pitch Code:

0.5%

Wave Form NEMA = TIF:

Insulation Class:

2250min1

Noload<4%onload<4%

Radio Interference:

Radiant Heat: kW (Btu/min)

AREPorPMG

-WPS750D6

R450

AVR Model:

-WPS750D6S

Alternator

WPS750D6

Performance Data:

WPS750D6S

Data Item

1985

1985

0.39

0.39

Xd

332

332

X'd

16.2

16.2

Motor Starting
Capability* kVA
Short Circuit
Ratio** %
Reactances: Per Unit

X"d

12.9

12.9

Voltage Technical Data WPS750D6

Voltage Technical Data WPS750D6S

Voltage

Prime:

kVA
380/220V 866

kW
693

Standby:

kVA
910

Voltage

kW
728

Prime:

Standby:

kVA
866

kW
693

kVA
910

728

kW

416/240V 936

749

983

786

380/220V

440V

960

768

1008

806

416/240V

936

749

983

786

480V

960

768

1008

806

440V

960

768

1008

806

480V

960

768

1008

806

www.powerlinkworld.com

3/5

WPS750D6/S

EP Series

Control System

PLC-7420

FEATURES

Microprocessor control, with high


stability and

credibility .

Mains supply and generator operation


monitoring.

Indicating operation status and fault conditions.

Multiple protections; multiple parameters


display,
such as pressure, temperature.

Manual and automatic work mode


selectable.

Real time clock for time and date display, overall


runtime display, 99 log entries

.
Overall power output display.

Integral speed/frequency detecting,


telling status
of start, rated operation, overspeed.

Communication with PC via RS485


or RS232

interface, using MODBUS protocol.

Engine ECU is available.

Common USB cable is usable for parameter

configuration.

Multi-language is available.

PLC-8610 (Optional)

FEATURES

By using inbuilt device with synchronization,

power matching and paralleling


functions, the

controller can be synchronized with the mains,


uninterruptedly returning when reaching the peak;

Can parallel up to 16 generator


sets;

Multiple languages display;

Root mean square value voltage measurement;

Optional power measurement device;

Optional communication ability function, automatic

synchronization indication function;

Inbuilt or expansion relay outputs.

www.powerlinkworld.com

4/5

WPS750D6/S

EP Series

Optional

Engine
Water Jacket
Preheater
Oil Preheater

z
z

Alternator
Winding Temperature
Measuring Instrument
Alternator Preheater
PMG
Anti-damp and
anti-corrosion
treatment
Anti-condensation
heater

z
z
z
z
z

LubricatingSystem
Oil with the
machine

GeneratorSet
z

Protection board from


hotness

z
z
z

ExhaustSystem
z

Tools with the


machine

FuelSystem

CoolingSystem
z
z

Front heat
protection
Coolant (-30C)

Low fuel level


alarm
Automatic fuel
feeding system
Fuel T-valves

Canopy
z

ControlSystem
z
z
z

Remote control
panel
PLC-8610
ATS

Weatherproof
canopy

Voltages
z
z
z
z
z

415/240V
400/230V
380/220V
220/127V
200-115V

The following lists are optional by the needs of customers.

Minor Repair / 1000 hrs optional


No.

Part Name

Part No.

1
2

FuelFilter

SE429B/4

Qty
6

Remark

OilFilter

SE111B

AirFilter

S551/4

ALTERNATORBELT

541/398

FANBELT

541/439

SEALROCKERBOXCOVER

SE478

GASKETCYLINDERHEAD

SE2H

THERMOSTAT

SE573/1

FRONTOILSEAL

554/126

10

SEALREARENDOIL

554/127

Local Distributor
If you have any question or inquiry, please contact
PowerLink sales organization or contact:
info@powerlinkworld.com
Specification may change without prior notice.
For more info, please contact PowerLink or your local
distributors.
EP Series/2013 1st Edition

www.powerlinkworld.com

5/5