Instruction Manual
For
Riken Combustible Gas Monitor
Model GP 641A

Operational Precautions:
a) Read and understand this instruction manual before operating instrument.
b) This manual should be kept in a convenient place for all persons to borrow as
needed for operation or maintenance. Return manual to storage location after each
use.
c) Maintenance procedures or parts used that are not in accordance with this
instruction manual may cause unsafe or failed operation of this monitor. Riken
assumes no responsibility for accidents that may occur as a result of improper
maintenance procedures, or procedures not in agreement with this manual.
d) Since this monitor is safety equipment, it is important to make this daily checks as
outlined in this manual. If any trouble or abnormality is found, contact Riken or the
nearest Riken agent for assistance.
e) To assure safe operation, maintenance and calibration checks must be made in
accordance with local regulations. If not regulated by local law, then routine
calibration and maintenance must be done at least every 6 months.

2-7-6 Azusawa Itabashi-ku Tokyo, 174-8744,Japan

INS-1509E (REV1.0)

Contents
1. PRODUCT OUTLINE
1-1. In the beginning

1-2. Operation purpose

*. NOTE

1-3.

DANGER

WARNING

CAUTION

2. IMPORTANT INSTRUCTION FOR SAFETY


2-1.

Warning items

2-2.

Cautionary items

3. PRODUCT FUNCTION
3-1. Outer drawing

3-2. Detector composition

3-3. Mount drawing

3-4. Name of each part and function

10

3-5. Block diagram

11

4. OPERATION
4-1. Before operation

12

4-2. Installation place

12

4-3. Caution at system installation

13

4-4. Ground construction

17

4-5. Wiring construction

18

5. OPERATION METHOD
5-1. Start-up

19

5-2. Basic run flow

19

5-3. Start-up method

20

5-3-1.

Power on

20

5-4. Detection mode

21

5-4-1.

Display

21

5-4-2.

External output

23

5-5. Maintenance and adjustment

24

5-6.

5-5-1.

Maintenance mode

24

5-5-2.

Zero adjustment

25

5-5-3.

Alarm point confirmation

26

5-5-4.

Alarm point change

26

5-5-5.

Peak hold value confirmation

27

5-5-6.

Alarm test

28

How to finish operation

28

INS-1509E (REV1.0)

6. KINDS OF ALARM AND PERFORMANCE


6-1. Kinds of alarm

29

6-2. Gas alarm

29

6-2-1.

Gas alarm performance

29

6-2-2.

Action at gas alarm

30

6-2-3.

Gas alarm possibility except the case of gas detection

31

7. MAINTENANCE CHECK
7-1. Frequency of maintenance work and check items

32

7-1-1.

Daily check

32

7-1-2.

Regular maintenance check

32

7-1-3.

Maintenance contract at regular maintenance check

33

7-2. Calibration method (Gas calibration etc.)

33

7-2-1.

Sensor heater voltage adjustment

35

7-2-2.

Zero adjustment

35

7-2-3.

Span adjustment

36

7-2-4.

Sensor start set

37

7-2-5.

One man span adjustment

38

7-2-6.

External output contact setting

39

7-3. Sensor and parts replacement

40

7-4. Treatment at operation finish and installation place change

40

7-4-1.

Operation finish

40

7-4-2.

Installation place change

40

7-5. Treatment at long time no use and start to reuse

40

8. SCRAP OF PRODUCTS AND SENSORS

41

9. TREATMENT AT ABNORMAL CASE

42

9-1. Trouble alarm

42

9-2. Measures at trouble alarm

42

9-3. Before trouble to be considered

42

9-4. Trouble shooting

43

10. DEFINISION OF WORD

45

11. SPECIFICATIONS
11-1. Specifications

46

WARRANTY

48

INS-1509E (REV1.0)

1. PRODUCT OUTLINE
1-1. In the beginning
This is important manual to operate the gas monitor model GP-641A to keep the performance of the unit, to
increase the reliability of the unit. The record of the checking result and the treatment of this should be kept
and, use them for next checking, planning for repair and improvement of the equipment. It is kindly requested
to keep the safety enough consideration at instrumentation even when the work failure or accidents etc takes
place by inadvertent factors and disconnection of power and signal cables.
Identification of each cautionary marks

DANGER

WARNING

This is non explosion-proof equipment. Do not use for gas detection above
LEL.
When the safety caution for electric equipment is not kept, it makes serious
damage on the human body or equipment.

CAUTION

1) When the operation and treatment are not performed as on the manual, it
may make the damage on the human body or equipment. When modified or
genuine parts are not used for repair, they do harm on the detector. If
cause accidents by them, this is far from our responsibility.
2) Follow the operation purpose of 1-2.
3) Take advance treatment so that any operation error and damage taken
place by the cut of power supply cable and/or unexpected accident.
4) As this is electrical applied product, these are the rare case affected by
electric noise, static and electro-magnetic noise and take care of it. In
such place installation, take advance treatment for protection in advance.

INS-1509E (REV1.0)

1-2. Operation purpose


l This is single channel type combustible gas monitor applied to gas detector head which is using combustible
gas sensor.
l The leakage in air shall be detected by combustible gas detector head connected to this monitor and the
measuring result is shown in 4-digit LED.
l GP-641A will give gas detection information to the senior system by 4-20mA signal. (Standard *1)
l One external gas alarm contact is equipped. (Standard *1)
*. Standard output combination is 4-20mA gas detection information and one external gas alarm contact. As
option, following combination is available.
1) 4-20mA gas detection information/One external trouble alarm contact
2) Two external gas alarm contact
3) One external gas alarm contact/One external trouble alarm contact

1-3.

DANGER

DANGER

WARNING

CAUTION

NOTE

WRNING

CAUTION

* NOTE

This mark means the matter makes serious damage on the human body or life
directly.
When the operation and treatment are not performed as on the maintenance
manual, it makes serious damage on the human body or equipment.
When the operation and treatment are not performed as on the maintenance
manual, it may make the damage on the human body or equipment.
It means the advice on the operation procedure.

INS-1509E (REV1.0)

2. IMPORTANT INSTRUCTION FOR SAFETY


2-1. Warning items
WARNING

Detector head
Do not use any detector head except specified detector head. Gas detection can not be done. This
monitor or detector head shall be damaged.

Power source
Before power on, check that the power source voltage is within the given voltage and then,
make power on.

Necessity of protection grounding


Do not cut the protection ground wire inside and outside of monitor and do not remove the wire of
protection ground terminal. It makes the unit dangerous condition.

Fault of protection function


When there is a fault for protection function such as grounding and fuse, do not operate and before
start-up, check that there is no fault on protection function.

Fuse
For protection of security, use the designated rating (power current, power voltage, type) fuse. The
replacement of fuse shall be done after turning power switch (POWER switch) off. Do not use other fuse
than the specified or make short-circuit fuse holder.

Operation in gas
Do not operate in the place where combustible gas or explosive gas vapors should exist. It is very
dangerous to operate in such an atmosphere.

External connection
After making sure protection ground, connect to external control circuit or detection objective.

Maintenance of instruments inside


Any work with removing cover such as replacement of internal parts should be done after turning power
switch off.

Measures at gas alarm


When detect gas more than alarm preset point, it is very dangerous. It is required to take appropriate
measures by customers decision.

INS-1509E (REV1.0)

2-2. Cautionary items


CAUTION

Do not use walky-talky near this gas detector.


When this detector receives the electric waves by walky-talky etc near from this instrument and/or the
cable, this will affect the reading. When use the walky-talky, operate it at the place where there is no
influence of electric wave ejection.

When make power on again, make it after an interval of over 5 seconds.


When make power on within 5 seconds, there may be no normal operation.

INS-1509E (REV1.0)

3. PRODUCT FUNCTION
3-1. Outer drawing
125

215

67

Cable inlet

INS-1509E (REV1.0)

3-2. Detector composition

Composed by the following units.

Indicator/alarm unit

Slide cover

INS-1509E (REV1.0)

3-3. Mount drawing


Maintenance space
Keep the space for mounting in the oblique part.

Installation hole

Body
Angle

Frame
Body
Screw hole

Maintenance space
Maintenance space

Panel mounting type

Wall mounting type

*. NOTE
l

Maintenance space over 100mm below the instrument is to be secured so that slide cover
can be opened.

For wall mounting type, maintenance space over 20mm above the instrument is to be
secured so that the angle can be installed.

INS-1509E (REV1.0)

3-4. Name of each part and function

LED display
POWER switch
Fuse
Terminal
PW/TR lamp

AL1 lamp
AL2 lamp
MIANTENANCE lamp
RESET switch
MODE switch

UP/DOWN switch

SET switch
Buzzer window
Volume (VR1)

Shows the gas density


Power switch used for power ON/OFF
This is power fuse 5.2 x 20mm, 250V/1A
Connect the cable from outside
Lamp for power and trouble
Light on : Power ON, Normal operation
Flicker : Trouble
Flicker (1st alarm) at gas alarm
Flicker (2nd alarm) at gas alarm (AL1 is flickering condition)
*. Alarm lamp become continuous light on after pressing reset switch.
Flickering at maintenance mode
Stop buzzer at alarming
This is the switch when changed over from detection mode to
maintenance mode. While in maintenance mode, it is used to escape
from the mode.
When select item by maintenance mode, or when increase up or
decrease down the reading by span and zero adjustment or increase
up or decrease down the reading by alarm test, this is used.
This is the switch when changed over to alarm test mode. During
maintenance mode, it is used to set the mode.
Beep at alarm
Adjust sensor heater voltage
10

INS-1509E (REV1.0)

3-5. Block diagram

GP-641A
Display part
(PW/TR) (AL1) (AL2) (MAINTENANCE)
Power source unit
POWER INPUT
(100VAC 220VAC)

Operation part
(MODE) (UP) (DOWN) (SET)
(RESET)

Control unit

Alarm contact control unit


Gas alarm contact (AL1, AL2)
Trouble alarm contact
(TROUBLE)
*. Standard set of contact run
l Non-excitation
(Non-excite normally)
l ON-ALAM
(Contact close at alarm)

Buzzer
Amplifier

4-20mA transmission

Transmission

Detector (sensor)

11

INS-1509E (REV1.0)

4. OPERATION
4-1. Before operation
Not only a first experienced client but also an experienced client shall keep the cautionary items. If not kept,
the trouble may cause and could not make normal gas detection.

4-2. Installation place

CAUTION
Do not install where direct sun beam is given or there is drastic change of temperature

When install, avoid the direct sun beam place or that of drastic change of temperature. Because dew
takes place inside of instrument and it may not follow the drastic change of temperature.
Do not install where the vibration or shock may take place.

As this is composed of fine electronics parts, install where the vibration and shock should not
take place and be stable.
Separate the detector from the noise generating source (Main unit and cable).

Avoid to installing at the place where high frequency is generated around.


l Do not put detector side by side or near with the noise source.
l Do not make cable at parallel wiring nor be near.
Do not install at the place where the detection gas is deposited around.

Do not install and make gas detection at the place where the sample gas is deposited. In this
case, make as detection by extending the sampling hose etc.
Dangerous place at maintenance service such as high voltage cable

This instrument is required to make maintenance regularly. Then do not install at the place
where there is danger at maintenance time.
The place where unable to make maintenance

When required to stop the system at maintenance time, unable to maintain if not remove a
part of system or unable to detach the case due to the pipe or rack etc, do not install such
place.

12

INS-1509E (REV1.0)

Machine that grounding construction is not

Be sure to make grounding of any machine when install.

4-3. Caution at system installation

CAUTION

Unstable power and noise may cause error of performance and alarm.
For the system to use this detector, it is required to make design based on this
manual description.

(1) Use stable power


While the system gets stable at power on and power failure, the external output and alarm contact may be on
and the care for it must be taken. In such case, use the standby battery or take an appropriate action in the
receiver side. Supply the following power to this detector.
Power voltage

100VAC-15% to 220VAC+20% (50/60Hz)

Power failure

Approx. 100msec.

tolerance time

(For power failure of over 100msec, it re-starts.)


To warrant the continuous operation, install the standby
battery outside.

Others

Do not connect with power involving high power load and high
frequency noise.
According to requirement, use line filter and separate it from
noise source.

(2) Designing to consider heat radiation


When install the closed self-standing control panel, mount the fans in the upper and lower part.

13

INS-1509E (REV1.0)

(3) Lightning measures


Lightning surge

Lightning measures

Grounding

There is the problem point Lightning when make outdoor wiring


of cable at factory or plants etc or when make a parallel wiring in
the same duct with the cable in from outdoor even at the indoor
wiring.
If the lightning is a huge generation source, the cable is a
reception antenna and there is the case that cable connecting
instrument is broken.
It is impossible to prevent the generation of lightning.
If the cable should put in metal tube, laid in the underground, it is
impossible to prevent the inductive lightning surge generating
from the thunder.
There is not the complete countermeasure for it but the following
method can be considered.
Make the suitable treatment accordingly.
a) The transmission signal route is arranged for connection by
the optical fiber cable etc.
b) Countermeasure by the lightning arrester
(Cable safety retainer)
There is the way to install the lightning arrester just before
the field apparatus and the central control station. The
position of the lightning arrester installation is at each point
of cable laid out from the outdoor to the indoor.
The lightning arrester builds in the circuit to remove the
surge voltage to be the source for the damage of field
apparatus (Protection resistor, zero diode etc and is designed
to protect the apparatus. But as the signal may be
attenuated due to the lightning arrester, check the action and
it is required to use.
Regarding detail, contact a
manufacturer of lighting arrester.
Surge noise shall be generated from the thunder lightning or
except it. To protect instrument from these cause, be sure to
make grounding.

*.In the lightning rod, there is the circuit to remove the surge voltage to be a cause of damage
from field instruments. By installing the lightning rod, the signal may be attenuated. When
install the lightning rod, it is required to check the performance in advance.

14

INS-1509E (REV1.0)

(4) Alarm contact


Alarm contacts shall be used only for external buzzer and alarm light, and do not use it for the
controlling use (such as solenoid valve control etc).
When control the external load, the bad influence may be given to the system according to the load
characteristics. In such case, the following countermeasure shall be taken to stabilize the action and
protect the contacts.
l

Relayed by the low voltage relay and operate by connecting CR circuit


(Spark Killer : SK) (Diode etc for DC) suited for relay coil directly to relay

Add CR circuit to the load side of relay relayed on the request.

15

INS-1509E (REV1.0)

Reference :

By the condition of load, CR circuit may be better to install in the contact side but it is
required to put in by checking the action of load.
SK: Filter for surge absorption

SK

Load

Coil

SK

Alarm contact
Power supply
GP-641A

Power supply
Relay
(Low pressure relay)

<How to consider alarm contacts against inductive load>


The spec for alarm contact of GP-641A is described by the conditions of resistance load.
When use the inductive load for alarm contacts, the very high reverse electromotive voltage may be
generated and the following trouble tends to be produced.
l
l
l
l

Contact part of relay is melted adhesively and the contacts can no work.
High voltage is put inside of indicator/alarm unit and then, unspecific electrical parts may be
damaged.
As it is big noise, the trouble action may be taken by the reckless drive of CPU.
Irrespective of inductive load, there is the possibility of unforeseeable noise intrusion for contacts.
Above trouble may be generated.
CAUTION

l
l

The inductive load shall not be used in principle (Do not use fluorescent lamp and motor).
When use the inductive load, make the contact amplification outside, but the outside relay coil
belongs to the inductive load, use the relay driven by the low voltage (within AC100V) and it is
protected by an appropriate surge killer.

*. As the inductive load, there are following samples.


Patlight, External relay, Buzzer, Siren, Fan, Fluorescent lamp, Motor etc.
16

INS-1509E (REV1.0)

4-4. Ground construction


By use of external

, make grounding to client terminals.

WARNING

Before power on, be sure to make grounding.

Terminal

*. Be sure make grounding for safety operation of detector and safety. Then, do not connect grounding
wire to the gas tube. For ground, carry out the division 3 grounding equipment (Grounding resistance
below 100).

17

4-5. Wiring construction

L
N

100VAC 15% to 220VAC+20% (50/60Hz)

Indicator/alarm unit

Earth
Pump power output

CVV (4C)

Detector head (sensor)

FG

Pump power input

TN1

External output 1 (OUT1)


External output 2 (OUT2)

TN2

Standard external output


OUT1 Terminal TN2 No. 7

No. 8 : Electrical current transmission 4-20mA DC

Gas concentration signal

4-20mA (Linear up to 22mA)

Initial clear

2.5mA

Maintenance mode

2.5mA

Trouble signal

0.5mA, Non-isolated (Load resistance under 300)

OUT2 Terminal TN2 No. 9

No. 10 : Contact output


nd

Gas alarm (2 )

Dry contact 1a

Latched

Automatically recovers after reset

Contact capacity

60W or 125VA, MAX 1A load resistance

Applicable detector head cable & max distance


HC (i-C4H10) : 500m with cable CVV, 4-core, 2.0mm2
CH4/LNG

: 200m with cable CVV, 4-core, 2.0mm2

18a

INS-1509E (REV1.0)
Variation of external output
1. Standard

OUT1 : 4-20mA & OUT2 : 2nd Gas Alarm

2. Option

OUT1 : 1st Gas Alarm & OUT2 : 2nd Gas Alarm

3. Option

OUT1 : 1st Gas Alarm & OUT2 : Trouble Alarm

4. Option

OUT1 : Trouble Alarm & OUT2 : 2nd Gas Alarm


OUT2

2nd Gas Alarm

Trouble Alarm

4-20mA

1st Gas Alarm

Option

Option

Not Available

Trouble Alarm

Option

Not Available Not Available

4-20mA

Standard

Not Available Not Available

OUT1

*. Refer to Page 39 about how to set.

CAUTION

When make wiring construction, make caution not to damage the internal electronics circuit.

Applicable cable between indicator/alarm unit and detector head is CVV 1.25sq or 2sq (4C). In
case of using other cable than specified, it is out of warranty.

For power input cable, pump power cable, external output signal cable, they should be used
separately and should not put in same core.

For power cable, detector cable, signal cable, they should not be laid out with motive power cable
such as motor etc.

Power output for pump of detector head should not be used for other instruments.

And,

applicable power supply voltage of pump of detector head should be same as the one of
indicator/alarm unit. For different power supply voltage of pump, separate power supply is
required.

18b

INS-1509E (REV1.0)

5. OPERATION METHOD
5-1. Start-up
l

Before making power on


Before making power on, take caution of the following.

If do not keep this, there is the danger of

electrical shock danger and damage of detector.


(1) Make grounding.
(2) Check that the wire with the external is made correctly.
(3) Check that the power voltage is within the rating.
(4) During adjustment, there is the case of external alarm contact to be worked. Arrange not to affect the
outside even if the contact work.
(5) For security purpose, check that it is rating fuse designated or not.

5-2. Basic run flow


Normally this is used by detection mode after making power on.

Start-up preparation

Power on

Initial clear (Approx 25 sec.)

SET switch (Press for about 3 seconds)


Alarm test mode

Detection mode

MODE switch (Press for about 3 seconds.)


Maintenance mode
l

Zero adjustment

Alarm point change (AL1, AL2)

Sensor heater voltage indication

External relay contact output setting.

19

INS-1509E (REV1.0)

CAUTION
When use maintenance mode, there is the exclusive service man. Do not operate it without
permission.

5-3. Start-up method


5-3-1. Power on
l

Before making power on, check that this instrument connected correctly.

The position of power switch is located inside of instrument (Open slide cover).

When turn the power switch ON/OFF to the right ( | ), it gets ON and when turn to left (), it gets
OFF.

Power switch

Slide down the cover.

When make power switchON, the POWER lamp lights on.

Initial clear (Approx. 25 sec.)


1) Instrument system check
2) External output : Approx. 2.5mA (4-20mA spec.)
3) Alarm, trouble action shut-off (Lamp, contact)

20

INS-1509E (REV1.0)

5-4. Detection mode


5-4-1. Display
For this work display, there are following two kinds display.
(1) LED display

: Shows the gas density etc.

(2) LED lamp

: Shows Power/Trouble (PW/TR), 1st gas alarm (AL1), 2nd gas alarm (AL2) and
maintenance (MAINTENANCE) condition.

*. LED display and LED lamp shows differently depending on instrument condition.
LED lamp function
Light off

Preparation

Light on

Flicker

POWER ON

Initial clear (Approx. 25sec.)

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Detection mode

At detection mode, only PW/TR


lamp lights on and it shows sample
gas density at LED display.

21

INS-1509E (REV1.0)

Gas alarm condition


When detect gas above AL1, AL2,
AL1 and AL2 alarm lamps light on
as well as sampling gas density
shows.

The right -0 displays when it


gets down to minus (-) side at

PW/TR

AL1
AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

above +10% of full scale.

WARNING

When it shows -0, the accurate gas reading is impossible and make
zero adjustment.

Trouble condition
When any of trouble arises on instrument, any
indication of trouble is shown.
[LED display]
E-00
E-01

[Trouble meaning]
System trouble
Sensor disconnection
/not yet connected

22

PW/TR

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)

5-4-2. External output


4-20mA output specification
(1) Signal transmission method

: Electrical current transmission (Non isolated)

(2) Transmission path

: CVVS

(3) Transmission distance

: Below 1km

(4) Load resistance

: Below 300

(5) Condition signal level

Detection mode

: 4-20mA (By gas density)

Gas alarm

: 4-20mA (By gas density)

Initial clear

: 2.5mA (Fixed)

Maintenance mode

: 2.5mA (Fixed)

Alarm test

: 4-20mA (By gas density)

Trouble alarm

: 0.5mA (Fixed)

Point skip

: 2.5mA (Fixed)

(6) Power shut down

: 0mA

Gas density and external output are shown below.


External output

22mA
20mA

4mA
2.5mA
Gas density

Full scale
Detection mode
Maintenance mode

CAUTION

4-20mA is already adjusted. When require readjustment after installation,


there is exclusive service man and do not tamper without permission.

23

INS-1509E (REV1.0)

5-5. Maintenance and adjustment


5-5-1. Maintenance mode
When make each adjustment, make it on maintenance mode.

Press MODE switch for 3 sec.

PW/TR

AL1 AL2

MAINTENANCE

Maintenance mode starts

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

*. Menu content
1-1 : Zero adjustment
Select by UP/DOWN switch
1-2 : Alarm point set
Select by UP/DOWN switch
1-3 : Regular maintenance mode

CAUTION

Do not operate 1-3 : Regular maintenance mode and contact RIKEN KEIKI or
nearest agent.

WARNING

When maintenance mode starts at gas alarm, alarm contact and external output
signal (Gas alarm signal) will be cancelled.

24

INS-1509E (REV1.0)

5-5-2. Zero adjustment


When adjust zero level, this is used.

*. NOTE
When make zero adjustment, supply zero adjustment gas and make it after zero
point gets stable.
PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

After this adjustment, press MODE switch,


return to MENU.

PW/TR

AL1 AL2

MAINTENANCE

When return to detection mode, press MODE


switch for over 3 sec. and return to detection
mode. MAINTENANCE lamp lights off and
this shows that it is detection mode.

PW/TR

AL1 AL2

MAINTENANCE

Press MODE switch for over 3 sec. and maintenance


mode starts.

Press SET switch and over again press it. The


display gets flickering and it can be zeroed.

*. NOTE
There is the case that zero point reading is deviated. At that time,
by pressing UP/DOWN switch, make fine zero adjustment. After
this UP/DOWN switch adjustment, press SET switch. Zero is
set by pressing it.

WARNING
After this adjustment finish, press MODE switch and return to detection
mode. (only PW/TR lamp lights on)

CAUTION
Gas alarm cannot start except detection mode. When leave it alone on
maintenance mode, this returns to detection mode automatically after 10
hours.

25

INS-1509E (REV1.0)

5-5-3. Alarm point confirmation


When confirm alarm point, this is used.
st

On detection mode, 1 alarm point value


(AL1) is shown by pressing UP switch. And
2nd alarm point value (AL2) is shown by
pressing DOWN switch.

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

5-5-4. Alarm point change


When change alarm point, this is used.
Press MODE switch for over 3 seconds and the
maintenance mode starts.

Select 1-2 by UP/DOWN switch.

When press SET switch, this can check 1st alarm


point (AL1). Press it again and 2nd alarm point
(AL2) can be checked.

When change alarm set point value (AL1, AL2),


change the value by UP/DOWN switch and press
SET switch. Alarm point is set by pressing it.
When return to detection mode, press MODE
switch for over 3 sec. and be returned to
detection mode. MAINTENANCE lamp lights off
and this shows that it is detection mode.

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

WARNING
After this adjustment finish, press MODE switch and return to detection mode. (only PW/TR lamp
lights on)
CAUTION
Gas alarm cannot start except detection mode. When leave it alone on maintenance mode, this
returns to detection mode automatically after 10 hours.

26

INS-1509E (REV1.0)
5-5-5. Peak hold value confirmation
When detecting gas of higher density than alarm point at detection mode, the highest gas density over alarm
point (peak value) is memorized.
Press MODE switch and maintenance mode starts.

PW/TR

AL1 AL2

MAINTENANCE

Select 1-P by UP/DOWN switch.

PW/TR

AL1 AL2

MAINTENANCE

By pressing SET switch, peak value is shown and


can be confirmed.

PW/TR

AL1 AL2

MAINTENANCE

By pressing SET switch for over 3 sec, the


peak value is cancelled.

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

By pressing SET switch, the cancellation


can be checked.

PW/TR

AL1 AL2

MAINTENANCE

When return to detection mode, press MODE


switch for over 3 sec. and return to detection
mode. MAINTENANCE lamp light off and this
shows that it is detection mode.

PW/TR

AL1 AL2

MAINTENANCE

WARNING
After finishing peak value confirmation and/or cancellation, it must return to detection mode (only
PW/TR lamp lights on) by pressing MODE switch.

CAUTION
Gas alarm cannot start except detection mode. When leave it alone on maintenance mode, this
returns to detection mode automatically after 10 hours.

27

INS-1509E (REV1.0)

5-5-6. Alarm test


This is used when confirm the action of alarm lamp, alarm buzzer and alarm contact, and confirm transmission
condition by giving same signal output as gas density (in case of 4-20mA specification) from this instrument to
external unit.
WARNING
When make alarm test (Transmission test), announce it to the concerned department beforehand. Carry it
out not to take it abnormally by the concerned department. (External output signal, alarm contact)
Press SET switch for over 3 sec. and alarm test
mode starts. MAINTENANCE lamp and display
gets flickering.

PW/TR

AL1 AL2

MAINTENANCE

Increase up the reading by pressing UP switch.


When it reaches to 1st alarm, AL1 lamp starts to
light on and buzzer starts beeping (alarm contact
activates). When it reaches to 2nd alarm, AL2
lamp starts light on and buzzer starts beeping
(alarm contact activates).

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

To stop buzzer beeping, press RESET switch.


By doing this, alarm lamp change over from
flickering to continuous light on, and change to
non-latched mode. By pressing DOWN switch
to decrease down the reading below alarm point,
alarm lamp and alarm contact are cancelled.

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Press SET switch for over 3 sec. and return to


detection mode. MAINTENANCE lamp lights off
and this shows that it is detection mode.

PW/TR

AL1 AL2

MAINTENANCE

5-6. How to finish operation


When finish this operation, turn off power switch (inside of instruments) first and turn off the main power
(100VAC

220VAC).
WARNING

When finish operation of this instrument, do it after making point skip at the top system if connected.
When finishing, check the external output and function of external equipments connected with external contact
terminal. Then judge whether power can be shut off or not.
When alarm contact is designed on excitation (option), make the only power switch off. When make power off
(100VAC 220VAC), alarm contact works.

28

INS-1509E (REV1.0)

6. KINDS OF ALARM AND PERFORMANCE


6-1. Kinds of alarm
There are two kinds of alarm, gas alarm and trouble alarm.
l

Gas alarm : When the detection gas reaches to preset alarm point or exceeds it, this starts to
perform. [Latched mode performance, Non latched mode performance after reset]

*. NOTE
Alarm point (standard) is preset at 1/4 (1st alarm AL1), 1/2 (2nd alarm AL2) of full scale. To prevent error of
performance, this is provided with 3 seconds alarm delay time.

Trouble alarm : Trouble is detected in the instrument and it gives alarm as trouble alarm. Except
system trouble E-00, it is non latched mode. When return to normal from trouble condition, this
instrument starts again from the performanceInitial clear same as after power on. [Refer to 9.
TREATMENT AT ABNORMAL CASE.]

6-2. Gas alarm


6-2-1. Gas alarm performance
(1) Display
Gas density display
When exceed detection range, it shows LED display .
Power lamp (Power : Green)
It keeps continuous light on.
Alarm lamp (AL1 : Orange), (AL2 : Red)
Alarm point is two alarm levels. When reading goes to alarm preset point or exceeds it, it gets to light
on.
(2) External output
4-20mA output
The output in directly proportion to gas density is shown. In case of over-scale, it can not give
output over approx 22mA.
Alarm contact
When gas density reaches alarm preset point or exceeds it, the alarm contact works. For contact
work, it will be non latched mode after reset when gas density gets under alarm point.

29

INS-1509E (REV1.0)

[Alarm pattern]

Gas density

AL2 alarm point


AL1 alarm point

Alarm lamp (AL1)


Alarm contact (Terminal No. 5, 6)
Alarm delay time (3sec)

Alarm lamp (AL2)


Alarm contact (Terminal No. 7, 8)

Alarm delay time (3sec)

6-2-2. Action at gas alarm


Reaction to leak gas
The action at gas alarm shall follow to the client rule and immediate refuge shall be required. Generally, the
following action is taken.
Confirmation of reading at this monitor.

*. NOTE
Instantaneous gas leak may get lower at confirmation time. Except gas alarm, it gets alarm
condition temporarily by noise or any other accidental conditions.
Based on gas alarm control density, it keeps the safety by keeping away people from the monitoring area.
When gas density display shows, close the gas valve and confirm that gas density gets lower enough.
Suppose that the leak gas is to remain and provide yourself with protection attire and tool away from
danger, go to the leak site and check the gas residual condition by portable leak detector.
After checking that there is no danger, the treatment for gas leak shall be taken.

30

INS-1509E (REV1.0)

6-2-3. Gas alarm possibility except the case of gas detection


It may respond to interference gas.
For interference gases, contact the nearest agent or RIKEN KEIKI.
It may be caused by drifting due to the change by time elapsing of sensor.
Check the reading by daily check and make calibration through authorized service agent whenever necessary.
It may be caused by the noise generated from machines near around this instrument.
Revision of installation location, wirings and addition of noise measure parts etc. between instrument and
detector shall be required. This specific measures shall differ from the condition of each site.
It may receive a temporarily noise such as by thunder lighting etc.
understood, the measure for surge according to the condition can be taken.

31

When the cause and effects are

INS-1509E (REV1.0)

MAINTENANCE CHECK
This is an important instrument at security and safety. To maintain the security and enhance the reliability of
safety, the regular maintenance check for it shall be absolutely necessary.

7-1. Frequency of maintenance work and check items.


7-7-1. Daily check
This is the check items carried out by customer.
Check of PW/TR lamp
In normal operation, the lamp is at light on condition.
Check of LED reading
Check that LED reading is zero0. If it is not zero 0, check that gas is free around gas detector and
make zero adjustment after turning on the maintenance mode.
CAUTION
For the accurate zero point adjustment, check it by 1-1. Zero adjustment of
maintenance mode.

Alarm test
Check alarm lamp flicker and buzzer beeps normally.
CAUTION
For alarm test, carry out with reference to5-5-5. Alarm test.

7-1-2. Regular maintenance check


The following items shall be checked at regular check.
Daily check
Instrument cleaning
Calibration
Function check
Parts replacement
Others

32

INS-1509E (REV1.0)
7-1-3. Maintenance contract at regular maintenance check
To maintain the safety operation of detector, it is recommended to have the maintenance contract with
service agent for regular maintenance, adjustment and overhaul etc including the gas sensitivity calibration.
For the detail of maintenance contract, contact our nearest service agent or RIKEN KEIKI.

7-2. Calibration method (Gas calibration etc.)


CAUTION
Do not operate 7-2. Calibration method without permission.
nearest agent or RIKEN KEIKI.

Contact our

When adjust and calibrate gas detector connected with this instrument, this is used.
Preparation : Prepare calibration gas known gas density. Proper gas density is 1.6 times of alarm point (can
check the function of alarm delay).
CAUTION
The gas used for calibration should contain fresh air with oxygen over 10%, and same
level humidity as atmosphere where gas detector is installed.

When make gas calibration, make it on maintenance mode.


Press MODE switch for 3 sec.

Maintenance mode starts

33

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)
*. Menu content
1-1 : Zero adjustment
Select by UP/DOWN switch
1-2 : Alarm point set

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Select by UP/DOWN switch


1-3 : Regular maintenance mode

Press SET switch for 3 sec.


Press SET switch for 3 sec.

PW/TR

AL1 AL2

MAINTENANCE

2-1 : Sensor heater voltage a djustment

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1
AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Select by UP/DOWN switch


2-2 : Zero adjustment
Select by UP/DOWN switch
2-3 : Span adjustment
Select by UP/DOWN switch
2-4 : Sensor start set
Select by UP/DOWN switch
2-5 : One man gas calibration
Select by UP/DOWN switch
2-6 : External output contact set

WARNING

When maintenance mode starts at gas alarm, alarm contact and external output
signal (Gas alarm signal) will be cancelled.

34

INS-1509E (REV1.0)

CAUTION
Gas alarm cannot start except detection mode. When leave it alone on
maintenance mode, this returns to detection mode automatically after 10 hours.

7-2-1. Sensor heater voltage adjustment


[Sensor heater voltage : 148mV]
PW/TR

AL1 AL2

MAINTENANCE

Press SET switch

PW/TR

AL1 AL2

MAINTENANCE
Adjust to rating sensor
heater voltage by volume
VR1.

Select 2-1 by UP/DOWN switch and press


SET switch.

AL1 AL2

MAINTENANCE

Display shows sensor heater voltage at the time.


In case that the value is deviated from rating
sensor heater voltage, adjust to the rating with
by volume VR1(unit : mV).

PW/TR

Return to menu by pressing MODE switch.

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Return to menu by pressing MODE switch.

7-2-2. Zero adjustment


PW/TR

Press SET switch


AL1 AL2

MAINTENANCE

Press SET switch

Select 2-2 by UP/DOWN switch. By pressing SET


switch, zero point reading at the time is shown.
Press SET switch and over again press it. The display
gets flickering and it can be zeroed.

PW/TR

*. NOTE
There is the case that zero point reading is deviated. At that time, by
pressing UP/DOWN switch, make a fine zero adjustment. After this
UP/DOWN switch adjustment, press SET switch. Zero is set by

PW/TR

pressing it.

AL1 AL2

MAINTENANCE
After display flickering, adjusted
to zero 0 automatically
AL1 AL2

MAINTENANCE
Return to menu by pressing MODE switch

After this adjustment, press MODE switch


and return it to menu.

PW/TR

35

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)
7-2-3. Span adjustment
PW/TR

AL1 AL2
Press SET switch

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE
Introduce calibration gas

Select 2-3 by UP/DOWN switch and press SET


switch. Gas calibration is ready by pressing it.
Introduce calibration gas and wait until the reading
become stable. After that, adjust the reading to the
known calibration gas density by UP/DOWN switch
and press SET switch.

*. NOTE
When introducing calibration gas and the reading exceeding alarm
point, alarm lamp (AL1, AL2) lights on so that alarm delay time can be
checked.
By pressing SET switch, the display gets flickering
and return to menu. It is adjusted.

*. NOTE
SET switch must be pressed after span adjusting to calibration
gas density. Without pressing SET switch, the adjustment can not
be memorized. And calibration gas is to be kept introduced until
the display return to menu after flickering.
Return to detection mode by pressing MODE
switch for 3 sec.

PW/TR

AL1 AL2

MAINTENANCE
After reading become stable, adjust
it to known calibration gas density
and press SET switch.

PW/TR

AL1 AL2

MAINTENANCE
The display gets flickering
and return to menu.

PW/TR

AL1 AL2

MAINTENANCE
Press MODE switch for 3 sec.

PW/TR

CAUTION
Calibration gas density for span adjustment must be over 10% of full scale
value. Span adjustment can not be done with lower density than 10% of full
scale.

36

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)

7-2-4. Sensor start set


PW/TR

AL1 AL2 Press SET switch

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Select 2-4 by UPDOWN switch and press SET


switch. Sensor start set (S. Set) is ready by
pressing it.
By pressing SET switch for over 3 sec, the display
gets flickering. Sensor start set is completed by this
and return to menu2-4 after flickering.

The display gets flickering


and return to menu

*. NOTE
<Sensor start set>
Sensor start set determines the limitation value of sensor life (tolerance
value of sensor sensitivity deterioration). When replacing sensor, the
limitation value is set by this sensor start set. By this set, sensor can be
used stably, and can avoid unstable operation because of abnormal
sensitivity deterioration. This set is applicable to only new sensor, and do
not set for the one used currently.
Return to detection mode by pressing MODE
switch for over 3 sec.

PW/TR

AL1 AL2

MAINTENANCE
Press MODE switch
for 3 sec.

PW/TR

CAUTION
When it reaches the limitation value of sensor life, span adjustment can
not be done. Replace the sensor with new one.

37

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)

7-2-5. One man span adjustment


PW/TR

Press SET switch


AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

PW/TR

AL1 AL2

MAINTENANCE

Select 2-5 by UP/DOWN switch and press SET switch.


One man span adjustment is ready by pressing it.

Adjust the indication value on the LED to calibration gas


density by UPDOWN switch and press SET switch.
The display shows zero0 after pressing SET switch.

Adjust the indication value to calibration


gas density by UP/DOWN switch and
press SET switch. The displ ay shows
zero 0 after pressing SET switch.
PW/TR

AL1 AL2

MAINTENANCE

Go to the place where gas detector head to be calibrated


is installed and introduce calibration gas. The gas is to
be introduced for 1 minute as standard. (Except special
gas.
Contact nearest agent or RIKEN KEIKI).
Indication value starts to increase, and indicator shows
current gas density value (peak value) before span
adjustment just like as right operation flow chart.
Calibration is automatically done by installed
microcomputer, with adjusting the current gas density
value (peak value) to the pre-memorized value of
calibration gas density.

PW/TR

AL1 AL2

MAINTENANCE
Exhaust calibration gas

PW/TR

After retuning from the place where gas detector head is


installed, check alarm response time and gas density value
before adjustment.
By pressing SET switch, it shows alarm response time.
By pressing UP switch after alarm response time check, it
shows gas density value before adjustment. Alarm
response time can be shown again by pressing DOWN
switch.

AL1 AL2

MAINTENANCE
Press SET switch and
check the response time

PW/TR

AL1 AL2

MAINTENANCE

CAUTION
One man span adjustment is done by the calculation
based on the increasing output curve of detector head
and its peak value. Because of this, one man span
adjustment can not be done correctly because of bent
piping, getting out of joint, running out of calibration gas
while introducing calibration gas to gas detector head.
Make caution for these.
After span adjustment, press MODE switch and return to
menu 2-5. And return to detection mode by pressing
MODE switch for over 3 sec.

38

Introduce calibration gas

Press UP switch and check the gas


density value before span adjustment
PW/TR

AL1 AL2

MAINTENANCE

INS-1509E (REV1.0)

7-2-6. External output contact setting


External output contact can be changed to the following three variation as option.
1st Gas alarm (AL1) + 2nd Gas alarm (AL2)
1st Gas alarm (AL1) + Trouble alarm (TROUBLE)
Trouble alarm (TROUBLE) + 2nd Gas alarm (AL2)
PW/TR

AL1
AL2

MAINTENANCE

Press SET switch

PW/TR

Select 2-6 by UPDOWN switch. Press SET


switch and shows current setting. (By pressing
SET switch, AL1 and AL2 is shown in turn.)
Select [1. AL1 (1st Gas alarm) or [1. trb (Trouble
alarm) by UPDOWN switch.

AL1 AL2

MAINTENANCE
Select AL1 trb by
UP/DOWN switch

PW/TR

AL1 AL2

MAINTENANCE
By pressing SET switch and
shows AL2 setting

Press SET switch and shows AL2 setting.


Select [2. AL2 (2nd Gas alarm) or [2. trb
(Trouble alarm)].

PW/TR

AL1 AL2

MAINTENANCE
Select AL2 by
UP/DOWN switch.

PW/TR

AL1 AL2

MAINTENANCE
Return to menu by pressing
MODE switch

Return to menu by pressing MODE switch.

PW/TR

AL1 AL2

MAINTENANCE
Press MODE switch
for over 3 sec.

Press MODE switch for over 3 sec.


and return to detection mode.

PW/TR

AL1 AL2

MAINTENANCE

CAUTION
Standard setting of external output is [4-20mA output + 2nd Gas alarm (AL2)]. When 2 kinds of
external output are used as both two contacts, jumper setting on PCB is necessary.

39

INS-1509E (REV1.0)

7-3. Sensor and parts replacement

CAUTION
For sensor and parts replacement, contact nearest agent or RIKENKEIKI.

7-4. Treatment at operation finish and installation place change


7-4-1. Operation finish
When finish operation of this instrument, turn off POWER switch (inside of instrument) first and turn off the
main power (100VAC

220VAC).

7-4-2. Installation place change


When change installation place, refer to 4-2. Installation place. And for wiring construction, refer to 4-5.
Caution at wiring construction.

CAUTION
After installation place change, make gas calibration. For readjusting work including
gas calibration, contact nearest agent or RIKEN KEIKI.

7-5. Treatment at long time no use and start to reuse


Keep this instrument under following condition.
Temperature

: 0 - 40

Humidity

: 45%RH

70%RH

Environmental condition : Place where gas, solvent gas, vapor (steam) do not exist.

CAUTION
When start to reuse, make gas calibration. For readjusting work including gas
calibration, contact nearest agent or RIKEN KEIKI.

40

INS-1509E (REV1.0)

8. SCRAP OF PRODUCTS AND SENSORS


Scrap of products
Regarding indicator/alarm unit and sensor, treat it in the same as industrial scrap (Non-flammable goods).

41

INS-1509E (REV-1.0)

9. TREATMENT AT ABNORMAL CASE


9-1 . T r o u b l e a l a r m
Flickering of PW/TR lamp
l

When PW/TR lamp is flickering, it is the condition that the following trouble may be caused.
Research its cause and take an appropriate action.

The output of detector at trouble shall be as follows.


GP-641A (4-20mA output specification) : 0.5mA (fixed)
LED display

Trouble content

Main cause

E-00

System trouble

Memory trouble in the indicator

E-01

NO connection of sensor

Connector contact failure


Sensor cable disconnection

9-2. Measures at trouble alarm


When any trouble was found on this instrument and gas detector head, contact our nearest agent or
RIKEN KEIKI. If trouble should take place, we try best to search its cause and prevent its cause.

9-3. Before trouble to be considered


It may be originated from disconnection and short circuit between units.
l

Check the wirings including equipment near around as well as this instrument.
There is the case that operation of instrument is not correct including piping work etc.

Re-check the gas detection system and contact our nearest agent or RIKEN KEIKI.
There is the case of electrical line trouble such as shut-off of power.

This will be treated by the re-check of stand-by battery, electrical line filter, insulation
transformer etc or those addition.

42

INS-1509E (REV-1.0)
9-4. Trouble shooting
(1) No light on for PW/TR lamp
<Cause and action>
l

Is it OK with power cable connection?


Connect power cable.

Is fuse disconnected?
Search the cause of disconnection and replace it after taking counter-measures.

Is power voltage normal?


Supply the rating power voltage.

Is this power switch turned on?


Make power switch ON.

(2) Abnormal performance


<Cause and action>
l

Sudden surge noise can be considered. When recover it, turn off the power and turn on
the power again for re-start of operation. When such takes place often times, take
appropriate action for noise.

(3) No calibration available


<Cause and action>
l

Is the calibration gas density correct?


Prepare the appropriate density gas.

There is the possibility for sensor sensitivity drop.


The sensor replacement is required.

(4) PW/TR lamp flickering


<Cause and action>
System trouble E-00
l

Memory trouble inside of indicator.


Contact our nearest agent or RIKEN KEIKI.

Sensor connection trouble E-01


l

Non-connection of sensor, contact failure of connector and disconnection of sensor cable.

Checkwhether sensor is connected orthe sensor cable connector is connected to the


sensor. If can not be recovered, contact nearest agent or RIKEN KEIKI.

43

INS-1509E (REV-1.0)
(5) Fuse disconnection
<Performance>
l

This instrument can not work.

<Cause and action>


l

The trouble of instrument or trouble of external power source can be considered.


this cause and after taking its measures, replace the fuse with the designated one.

*. NOTE
The fuse rating for this instrument is 250V/1A.

44

Search

INS-1509E (REV-1.0)

10. DEFINITION OF WORD


External output signal
External output of this instrument is as follows.
Gas density signal output : Electrical current transmission (4-20mA)
Standard setting is [4-20mA + 2nd Gas alarm (AL2)].
Or, following variation are selectable.
Alarm contact output ; 1 st Gas alarm (AL1) + 2nd Gas alarm (AL2)
1 st Gas alarm (AL1) + Trouble alarm (TROUBLE)
Trouble alarm (TROUBLE) + 2nd Gas alarm (AL2)
LEL
Abbreviation of Lower Explosion Limit.
Lower Explosion Limit
The lowest combustible gas density that combustible gas mixed with air and explode by ignition.
Calibration
By using calibration gas etc, it seeks for instrument reading, display value and set value or true
value.
Maintenance mode
When make maintenance of instrument, it shuts off the alarm and outputs the signal showing the
maintenance mode condition. By this, the maintenance is carried out independently on this
instrument. Press MODE switch for over 3 seconds and the maintenance mode starts.
Initial clear
The reading will be unstable for a few seconds after power on. In this moment, to prevent the
error of running, the alarm contact shall be cut off. Then, signal output showing initial clear
condition is given on external output.
Alarm delay time
To prevent the alarm error by noise intruded from the outside, this is the function to suspend the
running temporarily.
Response time
It is time until the alarm beeps by giving 1.6 times the calibration gas density of alarm preset point.
(This does not involve the time when connect suction pipe outside.) Response time of this
instrument is 30 seconds.
45

INS-1509E (REV1.0)

11. SPECIFICATOINS

11-1. Specifications
Model

GP-641A

Structure

Wall mounting type


Panel mounting type/Connection type(Simple weather proof type)

Detection principle

Catalytic combustion

Measuring gas

HC in air (i-C4H10 cal.) as standard, or CH4 in air (CH4 cal.)

Measuring range

0-100%LEL

Alarm accuracy

Within 25% (at alarm set value) under same condition

Response time

Within 30 sec. When exposed to gas concentration of 1.6 times alarm value
(Same as T60) (Excluding piping)

Self diagnosis function


Content

System trouble, sensor disconnection

Trouble indication

POWER lamp flickering, Showing the content of trouble (LED display)

Display
Gas density

Gas density indication on LED (4 digits, 7 segments)

Condition

LED lamp
Power/Trouble

PW/TR (Continuous/Flicker)

Normal (Green/Continuous), Trouble (Green/Flicker)


Gas alarm

1st : AL1 Flicker (Orange)


2nd : AL2 Flicker (Red)

Normal (Off), Gas alarm (Orange, Red/Flicker)


Continuous light on after resetting/Light off below alarm point
Maintenance mode

MAINTENANCE lamp Flicker (Green)

Output signal (standard)


1. Terminal TN2 No. 7

No. 8

: Electrical current transmission DC4-20mA

Gas density signal

: 4-20mA (Linear up to 22mA)

Initial clear

: 2.5mA

Maintenance mode

: 2.5mA

Trouble signal

: 0.5mA Non-isolated (Load resistance below 300)

2. Terminal TN2 No. 9

No. 10

: Contact output

Gas alarm (2nd)

: Dry contact 1a

Latched mode

: Automatically recover (Non latched mode) after resetting

Contact capacity

: 60W or 125VA, MAX 1A load resistance

*. 4 20mA output is option. Changeable to 1st alarm contact or trouble alarm contact
Other setting

Set by PC (with original cable)

46

INS-1509E (REV1.0)
Power

Power supply

: 100VAC-15% to 220VAC+20% (50/60Hz)

Power consumption

: Approx. 10VA

Cable

: CVV 1.25sq 3c

Applicable detector head cable & max distance

Operating condition

HC (i-C4H10)

: 500m with cable CVV, 4-core, 2.0mm2

CH4/LNG

: 200m with cable CVV, 4-core, 2.0mm2

Temperature

: -10 - +50

Humidity

: Below 90%RH (Non-condensing)

Outer dimension

125 (W) x 215 (H) x 67 (D) mm

Weight

Approx. 1.0kg

*. Specification subject to change without notice

47

INS-1509E (REV1.0)

RIKEN KEIKI STANDARD WARRANTY


GAS DETECTION INSTRUMENTS
RIKEN KEIKI CO., LTD. warrants gas alarm equipment manufactured and sold by us to be free from
defects in materials and workmanship for a period of one year from date of shipment from RIKEN
KEIKI CO., LTD. Any parts found defective within that per iod will be repaired or replaced, at our
option, free of charge, F.O.B. Factory. This warranty does not apply to those items which by their
nature are subject to deterioration or consumption in normal service, and which must be cleaned,
repaired or replaced on a routine basis. Such items may include :
a)
b)
c)
d)
e)

Lamp bulbs and fuses


Pump diaphragms and valves
Absorbent cartridges
Filter elements
Batteries

Warranty is voided by abuse including rough handling, mechanical damage, operation, alteration or
repair procedures not in accordance with instruction manual. This warranty indicates the full extent
of our liability, and we are not responsible for removal or replacement costs, local repair costs,
transportation costs, or contingent expenses incurred without our prior approval.
THIS WARRNTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND
REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES
ON THE PART OF RIKEN KEIKI CO., LTD. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RIKEN
KEIKI CO., LTD. BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL LOSS OR
DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS
PRODUCT TO FUNCTION OR OPERATE P ROPERLY.
This warranty covers instruments and parts sold (to users) only by authorized distributors, dealers and
representatives as appointed by RIKEN KEIKI CO., LTD.
We do not assume the indemnification for any accident or damage caused by the operation of this gas
monitor and our warranty is limited to the replacement of parts or our complete goods.