You are on page 1of 131

Catalog KT 10.

1 2002

Catalog KT 10.1 2002


SITOP Power supplies

sitop

Siemens AG
Automation and Drives
Systems Engineering
Sales Power Supplies, System Cables

www.siemens.com

Order No.: E86060-K2410-A101-A4-7600

Power supplies
SITOP power
LOGO!Power

Related catalogs:
System cables
SIMATIC TOP connect

KT 10.2

Order No.:
E86060-K2410-A201-A3-7600
Power supplies
SITOP power, LOGO!Power, SIDAC-S1)

PD 20

Order No.:
E86060-K2802-A101-A1

Switchgear
Low-Voltage Control Gear,
Switchgear and Systems

NSK

Order No.:
E86060-K1002-A101-A2-7600
SIMATIC
Totally Integrated Automation

ST 70

Order No.:
E86060-K4670-A101-A7-7600
SINUMERIK & SIMODRIVE
Automation Systems for
Machine Tools

NC 60

Order No.:
E86060-K4460-A101-A8-7600
Communication & Field Devices
Industrial Communication and
Field Devices

IK PI

Order No.:
E86060-K4660-B101-B1-7600
Information and Training
for Automation and
Drives Technology1)

ITC

Order No.:
E86060-K6850-A101-B1
Automation and Drives Technology
The entire spectrum
on CD ROM

CA 01

Order No.:
E86060-D4001-A110-B5-7600
1)

Available in German only.


Get in touch with your local Siemens partner for further information.

Trademarks
LOGO!, SIMATIC and SITOP are Siemens registered
trademarks.
All other products and systems are (registered) trademarks of
their respective owners and must be treated accordingly.

Catalogs of the

Automation and Drives Group (A&D)


Further information can be obtained from our branch
offices listed in the appendix of this catalog
Automation & Drives
Interactive catalogs on CD-ROM
Components for Automation & Drives

Catalog

Systems Engineering
Power supplies SITOP power

CA 01

System cables SIMATIC TOP connect

Electrical Installation Technology

ET 01

MOBY Identification Systems

Analysis Systems
Gas Analysis Equipment for the Process Industry

PA 10

Process Analysis, Components for Sample Preparation

PA 11

SIPAN Liquid Analysis

PA 20

Drive Systems
Variable-Speed Drives

Industrial Microcomputers SICOMP

Catalog
KT 10.1
KT 10.2
KT 21
KT 51

Industrial Communication and Field Devices

IK PI

Low-Voltage Controls and Distribution


Low-Voltage Controlgear, Switchgear and Systems

NS K

DC Motors

DA 12

DC Drives Preferred Series up to 500 kW

DA 12.1

DC Drives Preferred Series 215 kW to 1500 kW

DA 12.2

SIMOREG Chassis Converters

DA 21

SIMOREG Converter Cabinet Units

DA 22

Communication-Capable SIRIUS NET Controlgear,


Controlgear, SIGUARD Safety Systems,
Control and Signalling Devices, Switchgear,
Transformers and DC Power Supplies,
Main- and EMERGENCY-STOP Switches,
Control Switches, Terminal Blocks

SIMOVERT PM Modular Converter Systems

DA 45

BERO - Sensors for Automation

NS BERO

SIEMOSYN Motors

DA 48

NS PS

MICROMASTER 420/440 Inverters

DA 51.2

Products and Systems


for Low-Voltage Power Distribution

SIMOVERT A Current-Source DC Link Converters

DA 62

SENTRON WL

NS WL

SIMOVERT MV Medium-Voltage Drives

DA 63

MICROMASTER, MIDIMASTER

DA 64

Low-Voltage Motors for Variable-Speed Drives

DA 65.3

SIMOVERT MASTERDRIVES Vector Control

DA 65.10

TELEPERM M Process Control System


AS 235, AS 235H and AS 235K automation systems PLT 111

SIMOVERT MASTERDRIVES Motion Control

DA 65.11

AS 388/TM and AS 488/TM automation systems

PLT 112

SIMADYN D Control System

DA 99

OS 525 operating and monitoring system

PLT 122

Automation Systems for Machine Tools SIMODRIVE

NC 60

Operating and monitoring with WinCC/TM

PLT 123

CS 275 bus system

PLT 130

AC Main Spindle Motors 1FE1, 1PH2, 1PH3, 1PH4,


1PH7
AC Servomotors 1FK6, 1FT5, 1FT6

Process Engineering
Field Instruments for Process Automation
Measuring Instruments for Pressure,
Differential Pressure, Flow, Level and Temperature,
Positioners and Liquid Meters

AC Linear motors 1FN1, 1FN3


Converter System SIMODRIVE 611
Converter Systems SIMODRIVE POSMO A/CD/CA/SI
Low-Voltage Three-Phase-Motors

FI 01

Project Manual

M 10

SIWAREX Weighing Systems

WT 01

Squirrel-Cage Motors, Totally Enclosed, Fan-Cooled

M 11

Process Recorders and Accessories

MP 20

Drive and Control Components for Hoisting Equipment

HE 1

SIPART, Controllers and Software

MP 31

Automation Systems for Machine Tools


SINUMERIK & SIMODRIVE

NC 60

Cables, Connectors and System Components

NC Z

Vacuum Pumps/Compressors
Oil-Free Vacuum Pumps, Compressors (Blowers),
Radial Blowers, Liquid Pumps

PV

Human Machine Interface Products/Systems


SIMATIC HMI

ST 80
Pumps
Vacuum Pumps and Compressors, System ELMO-F Cat. Sheets PF

SIMATIC Industrial Automation Systems


SIMATIC PCS Process Control System

ST 45

SIMATIC S5/PC/505 Automation Systems

ST 50

Components for Totally Integrated Automation

ST 70

Supplementary Components

ST 71

SIMATIC PCS 7 Process Control System

ST PCS 7

Vacuum Pumps and Compressors, System ELMO-G Cat. Sheets PG

SIPOS Electric Actuators


Electric Rotary, Linear and Part-turn Actuators

MP 35

Electric Rotary Actuators for Nuclear Plants

MP 35.1/.2

SL 01

Electrical Installation Technology


Protective Switching and Fuse Systems
Building Management Systems with instabus EIB

I 2.1

Program Overview Modular Devices

I 2.11

System Solutions
Applications, Products and Services for Industry

STAB Wall-Mounting Distribution Boards

I 2.31

Automation Solutions in the Plastic Industry

SIKUS Floor-Mounting Distribution Boards

I 2.32

with SIMATIC S7

SL 10

8PU Busway System

I 2.36

with SIMATIC S5

ST 58

A&D/3U/En 06.11.01

Introduction

Overview,
Selection guide

SITOP power

Single-phase,
output currents up to 2 A

Standard 24 V

Single-phase,
output currents 2.5 to 4 A

SITOP

Single-phase,
output current 5 A

Power supplies
SITOP power
LOGO!Power

Single-phase,
output current 10 A

Single-phase/two-phase,
output current 20 A

Three-phase,
output currents 10 to 40 A

Catalog KT 10.1 2002


Supersedes: Catalog KT 10.1 1999

Uninterruptible
power supplies

Accessories
The products contained in this
catalog are also available from
CD ROM catalog CA 01
Order No.:
E86060-D4001-A110-B5-7600

SITOP power

Please contact
your local
Siemens representative

SITOP power

Alternative voltages

Customized
SITOP power

Further information and news on SITOP


can also be found on the internet at:
http://www.siemens.com/sitop

AS interface power supplies


LOGO!Power

Technical information
and configuring notes
The products and systems decribed
in this catalog are manufactured
under application of a quality
management system certified
by DQS in accordance with
DIN EN ISO 9001 (Certificate
Registration No.: 1108).
The DQS Certificate is recognized in all EQ Net countries
(Reg. No.: 1108).
Siemens AG 2002

Dimension drawings

Appendix

Service & Support


Indexes
Contact persons
Conditions of sale/delivery

SITOP power
Introduction
Power supplies
Unstabilized power supplies
The AC line voltage is transformed into a low voltage by
means of a 50 Hz (60 Hz)
transformer and rectified.
The DC voltage varies
according to supply voltage
and current load.
Stabilized power supplies
(switched-mode)
A rectified and filtered line
voltage is switched at a high
frequency.
The generated pulse train is
then again rectified and filtered.
The output voltage can be
regulated via the duty factor
or switching frequency.
The switching operation takes
place either on the mains side
(primary switched-mode regulator) or on the low-voltage
side (secondary switchedmode regulator).
The SITOP 24 V DC power
supplies are switched on the
primary side. The output voltage is stabilized via the duty
factor, the switching frequency is constant.

1/2

Siemens KT 10.1 2002

SITOP power

Features
High efficiency
The efficiency of approximately 90 % keeps current
consumption low and the
cabinet cool.
Simple installation
The low weight and mounting assistance allow for rapid and inexpensive
installation.
Low space requirement
With their high power density, the units take up little
space in the cabinet or in
machines, etc.
Precise output voltage
The precise output voltage
of 24 V DC is available even
with severe AC supply fluctuations. The loads are protected against overload
peaks. This extends the service life and reduces downtimes.
Low residual ripple
The low residual ripple
of < 0.4 % allows even voltage sensitive loads to be operated.
Integrated short-circuit protection
Additional protection of the
lines in the 24 V DC circuit is
not required.
Safe electrical isolation
The Vout output is isolated
from the input galvanically.
This electric isolation ensures that no dangerous
voltages can develop at the
output.
Compliance with national
and international standards,
such as
EMC according to
EN 50081-1/-2 and
EN 50082-1/-2
Output voltage SELV according to EN 60950
UL/cUL approval
No release of silicone
FM (American standard for
process engineering sectors)

Unstabilized power supply (basic connection diagram)


Line isolation

50 Hz
~

Rectification

Filtering

Vout

G_KT01_en_00067

SITOP power
Introduction
Power supplies
Stabilized power supply (basic connection diagram)
Line isolation Rectification

50 Hz
~

... kHz
+

Filtering

PWM
Vout
G_KT01_en_00068

Siemens KT 10.1 2002

1/3

SITOP power
Introduction
Selection guide
In order to assist you in finding the right stabilized power supply
for each application as quickly as possible, we have assembled
the following table as an overview listing all power supplies con-

tained in this catalog sorted according to input voltage, output


voltage and output current. For more details on each device
please refer to the cited pages in the catalog.

Selection guide
Input voltage
Output
voltage

Output
current

Order No.

Alternating voltage
120 to 230 V 500 to 600 V
AC
two-phase
AC

5 V DC

3A

6EP1 311-1SH01

page 13/2

6.3 A

6EP1 311-1SH11

page 13/6

12 V DC

1.9 A

6EP1 321-1SH01

page 13/2

4.5 A

6EP1 322-1SH01

page 13/6

15 V DC

1.85 A

6EP1 351-1SH01

page 13/2

24 V DC

4A

6EP1 352-1SH01

page 13/6

2 x 3.5 A

6EP1 353-0AA00

page 10/4

0.375 A

6EP1 731-2BA00

0.5 A

6EP1 331-2BA10

page 2/2

1.3 A

6EP1 331-1SH01

page 13/3

2A

6EP1 331-2BA00
page 2/2
6ES7 307-1BA00-0AA0 page 2/3
6ES7 305-1BA80-0AA0
6EP1 732-0AA00
6EP1 332-1SH12
6EP1 332-1SH41

page 3/2
page 13/7

3.5 A

6EP1 332-1SH31

page 3/2

4A

6EP1 332-1SH22

page 3/2

5A

6EP1 333-2BA00
6EP1 333-2AA00
6ES7 307-1EA80-0AA0
6ES7 307-1EA00-0AA0
6EP1 333-1AL11

page 4/2
page 4/2
page 4/3
page 4/2
page 4/3

10 A

6EP1 334-2BA00
6EP1 334-2AA00
6EP1 334-2CA00
6ES7 307-1KA00-0AA0
6EP1 334-1AL11
6EP1 334-1SH01
6EP1 434-2BA00

page 5/2
page 5/2
page 5/2
page 5/3
page 5/3
page 5/3

6EP1 336-2BA00
6EP1 536-2AA00
6EP1 436-3BA00
6EP1 436-2BA00

page 6/2

page 3/2

page 3/2

page 5/3
page 7/6
page 6/2
page 7/2
page 7/6

6EP1 437-2BA00

page 7/7

40 A

6EP1 437-3BA00
6EP1 437-2BA10

page 7/2
page 7/7

24 V DC UPS 15 A

6EP1 931-2EC01
6EP1 931-2EC11
6EP1 931-2FC01

page 8/6

2.5 Ah

6EP1 935-6MD31

page 8/10

3.2 Ah

6EP1 935-6MD11

page 8/11

7 Ah

6EP1 935-6ME21

page 8/12

12 Ah

3-52 V DC

1/4

page 8/2
page 8/2

40 A

30 V DC (ASi) 2.4 A

6EP1 935-6MF01

page 8/13

6EP1 632-1AL01

page 12/3

7A

6EP1 354-1AL01

page 12/2

0.65 A

6EP1 351-1SH11

page 13/3

1.25 A

6EP1 352-1SH11

page 13/7

10 A/120 W

6EP1 353-2BA00

page 10/2

Siemens KT 10.1 2002

120 to 230 V
DC

page 2/3
page 2/3

30 A

48 V DC

Direct voltage
24 V DC
48 to 110 V
DC

page 2/2

2.5 A

20 A

400 to 500 V
three-phase
AC

Output currents up to 2 A

SITOP power
Standard 24 V
Single-phase

2/2

The smallest types

2/2

The standard type

2/3

The classical type

2/3

The outdoor version

2/3

The DC/DC converter

Siemens KT 10.1 2002

2/1

SITOP power Standard 24 V


Single-phase
Output currents up to 2 A

SITOP power Standard 24 V

Overview

The smallest types

The standard type

Application

The power supply for operation worldwide for all applications in


classical industrial automation; with a wide input voltage range
for AC or DC voltages and compact dimensions (slim design),
suitable for systems in the lowest power ranges.

Standard power supply suitable for operation worldwide


in every conceivable field of
application.

Technical specifications
Power supply, Type

0.5 A

0.375 A

2A

Order No.

6EP1 331-2BA10

6EP1 731-2BA00

6EP1 331-2BA00

Input
Rated voltage Vin rated

Single-phase AC
120 - 230 V AC
Wide-range input

Direct voltage
48 -220 V DC
Wide-range input

Single-phase AC
120/230 V AC
Settable via jumper wire

Voltage range

93 to 264 V AC

30 to 264 V DC (30 to 187 V AC)

93 to 132 V/187 to 264 V AC

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 10 ms at Vin = 230 V


50/60 Hz; 47 to 63 Hz
0.22 - 0.13 A
< 23 A, typ. 1 ms

> 10 ms at Vin = 220 V

0.3 - 0.06 A
< 35 A, typ. 3 ms

> 10 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
0.9 - 0.6 A
< 14 A, typ. 3 ms

I2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

0.3 A2s
T 2 A/250 V (not accessible)
from 3 A, Characteristic C

1.2 A2s
F 4 A/250 V (not accessible)
from 6 A, Characteristic C,
DC-capable

< 0.3 A2s


T 1.6 A/250 V (not accessible)
from 3 A, Characteristic C

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
3 %
Approx. 0.2 %
Approx. 0.7 %

Stabilized, floating direct voltage


24 V DC
3 %
Approx. 0.1 %
Approx. 0.1 %

Stabilized, floating direct voltage


24 V DC
3 %
Approx. 0.1 %
Approx. 0.8 %

Residual ripple
(modulation freq.: approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 150 mVpp (50 mVpp typ.)

< 150 mVpp (50 mVpp typ.)

< 150 mVpp

< 240 mVpp (150 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 240 mVpp (50 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 240 mVpp


22.8 to 26.4 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +60 C

< 1.5 s/20 ms typ.


0.5 A

< 2.5 s/90 ms typ.


0.375 A

< 3 s/80 ms typ.


2A

0 to 0.5 A
0 to 0.5 A (up to +70 C)

0 to 0.375 A
0 to 0.375 A

0 to 2 A
0 to 2 A

Constant current approx. 0.6 A


Constant current approx. 0.6 A

2.7 A for 200 ms, typ.

7 A for 300 ms, typ.

Not permissible

Not permissible

Yes, 2 pieces

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output
Continued on page 2/4.

2/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output currents up to 2 A
The classical type

The outdoor version

The DC/DC converter

The well-proven power supply in the SIMATIC S7-300


design, for snap-mounting
on the S7 rail; with PS-CPU
power connector.

The power supply for extreme


ambient conditions in the
SIMATIC S7-300 design, for
snap-mounting on the S7 rail;
with PS-CPU power connector.

The DC/DC converter for supplying power from battery and


DC systems, with a wide input
voltage range of 38 to 121 V
DC.

2A

2A

2A

6ES7 307-1BA00-0AA0

6ES7 305-1BA80-0AA0

6EP1 732-0AA00

Single-phase AC
120/230 V AC
Switch-selectable on the unit

Direct voltage
24 - 110 V DC
Wide-range input

Direct voltage
48 - 110 V DC
Wide-range input

93 to 132 V/187 to 264 V AC

16.8 to 138 V DC

38 to 121 V DC

> 20 ms at Vin = 93/187 V


50/60 Hz, 47 to 63 Hz
0.8/0.45 A
< 20 A, < 3 ms

>10 ms at Vin rated

2.7 - 0.6 A (4 - 0.9 A)


< 20 A, < 10 ms

> 5 ms at Vin = 48 V

1.2 - 0.5 A
< 33 A

< 1.0 A2s (0.3 A2s typ.)


T 1.5 A/250 V (not accessible)
from 6 A, Characteristic C or
from 3 A, Characteristic D

< 5 As
T 6.3 A/250 V (not accessible)
from 10 A, Characteristic C,
DC-capable

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.2 %
Approx. 0.4 %

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.2 %
Approx. 0.4 %

Stabilized, floating direct voltage


24 V DC
1%
Approx. 0.1 %
Approx. 0.4 %

< 150 mVpp (130 mVpp typ.)

< 150 mVpp ( < 30 mVpp typ.)

< 100 mVpp

< 240 mVpp (150 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 240 mVpp ( < 150 mV typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 300 mVpp

Green LED for 24 V O.K.


Overshoot when switching on:
max. 25 V

< 3 s/60 ms typ.


2A

< 3 s (7 ms typ.)/5 ms typ.


2 A (3 A at Vin > 24 V)

< 3 s/30 ms typ.


2A

0 to 2 A
0 to 2 A

0 to 2 A (3 A)
0 to 2 A (3 A)

0 to 2 A
0 to 2 A (up to +70 C)

5 A for 50 ms, typ.


Almost immediate interruption
(approx. 0.5 ms)
Not permissible

9 A for 270 ms, typ.


9 A for 270 ms, typ.
Yes, 2 pieces

T 2.5 A (not accessible)


10 to 25 A, Char. B, or
6 to 25 A, Char. C,
DC-capable

Yes, 2 pieces

Continued on page 2/5.

Siemens KT 10.1 2002

2/3

SITOP power Standard 24 V


Single-phase
Output currents up to 2 A
Technical specifications (continued)
Power supply
Type

0.5 A

0.375 A

2A

Order No.

6EP1 331-2BA10

6EP1 731-2BA00

6EP1 331-2BA00

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 74 %
Approx. 4.2 W

Approx. 66 %
Approx. 4.6 W

Approx. 82 %
Approx.11 W

Control
Dyn. mains compensation (Vin rated 15 %) Approx. 0.3 % Vout
Dyn. load compensation (Iout: 50/100/50 %) 0.7 % Vout

Approx. 0.3 % Vout


0.4 % Vout

Approx. 0.3 % Vout


2 % Vout

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

1.5 ms typ.
1.5 ms typ.

2 ms typ.
2 ms typ.

0.5 ms typ.
0.5 ms typ.

Protection and monitoring


Output overvoltage protection

Yes, acc. to EN 60950

Yes, acc. to EN 60950

Yes, acc. to EN 60950

Current limitation

0.55 to 0.65 A

0.41 to 0.49 A

2.2 to 2.6 A typ.

Short-circuit protection

Constant current characteristic


to 0 V
< 0.65 A

Electronic interruption,
automatic restart
< 0.9 A

Electronic interruption,
automatic restart
<4A

Yes, SELV output voltage Vout


acc. to EN 60950 and EN 50178

Yes, SELV output voltage Vout


acc. to EN 60950 and EN 50178

Yes, SELV output voltage Vout


acc. to EN 60950

Protective class (IEC 536; VDE 0106 P1) Class I


Discharge current
< 3.5 mA

Class I
< 3.5 mA

Class I
< 3.5 mA (0.17 mA typ.)

Technical Inspectorate type testing


CE marking
UL/cUL (CSA) approval

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes; CB scheme
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

FM approval

IP 20

IP 20

EN 50081-1, EN 55022 Class B


Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022 Class B


Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022 Class B


Not applicable
EN 50082-2,
IEC 801-2, -3, -4, -5

20 to +70 C
with natural convection

20 to +70 C with natural convection, derating from 60 C

0 to +60 C
with natural convection

40 to +70 C

40 to +70 C

25 to +85 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

Dimensions (W x H x D) in mm
Weight approx.
Mounting

22.5 x 80 x 91
0.11 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

22.5 x 80 x 91
0.14 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

50 x 125 x 125
0.38 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Accessories

RMS sustained short-cct current


Overload/short-circuit indicator
Safety
Electrical isolation primary/secondary

Appr. for use in marine vessels

Deg. of prot. (EN 60529; VDE 0470 P 1) IP 20


EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating

Mechanical specifications
Connections
Mains input L, N, PE
(DC input: L+1, M1, PE)
Output L+
Output M

2/4

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output currents up to 2 A

2A

2A

2A

6ES7 307-1BA00-0AA0

6ES7 305-1BA80-0AA0

6EP1 732-0AA00

Approx. 83 %
Approx.10 W

Approx. 75 %
Approx. 16 W (24 W)

Approx. 84 %
Approx. 9 W

0.3 % Vout
0.8 % Vout

0.3 % Vout
2.5 % Vout

0.3 % Vout
0.8 % Vout

< 5 ms (2.5 ms typ.)


< 5 ms (2.5 ms typ.)

< 5 ms (2.5 ms typ.)


< 5 ms (2.5 ms typ.)

< 5 ms (2.5 ms typ.)


< 5 ms (2.5 ms typ.)

Additional control circuit,


interruption at approx. 30 V,
automatic restart
2.2 to 2.6 A

Additional control circuit,


interruption at approx. 30 V,
automatic restart
3.3 to 3.9 A

Yes, suppressor diode at output


2.1 to 3 A typ.

Electronic interruption,
automatic restart
<2A

Electronic interruption,
automatic restart
<2A

Electronic interruption,
automatic restart
<2A

Yes, SELV output voltage Vout


acc. to EN and EN 60950,
clearances in air and leakage
paths > 8 mm
Class I
< 3.5 mA (0.7 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950 and EN 50178,
clearances in air and leakage
paths > 5 mm
Class I
< 3.5 mA (0.7 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950
Class I
< 3.5 mA (0.7 mA typ.)

Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E179336

Yes, Class I Div. 2


Group A, B, C, D Part 4
Yes, Germanischer Lloyd
IP 20

Yes, GL, ABS, DNV, LRS


IP 20

IP 20

EN 50081-2, EN 55011 Class A


Not applicable
EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55011 Class A


Not applicable
EN 50082-2, IEC 801-2, -3, -4, -5,
prEN 50 121-3, -2

EN 50081-1, EN 55022 Class B


Not applicable
EN 50082-2, IEC 801-2, -3, -4, -5

0 to +60 C
with natural convection

25 to +70 C
with natural convection

0 to +70 C
with natural convection

25 to +85 C

25 to +85 C

40 to +70 C

Climate category 3K3 acc. to EN


60721

Climate category 3K5 acc. to EN


60721,short-term condensation
permissible

F acc. to DIN 40040: rel. humidity up to 75 % mean value, 95 %


on 30 days/year; no condens.

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm2
3 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
1 screw-type terminal for
0.5 to 2.5 mm2

50 x 125 x 120
0.42 kg
Snap-mounting on S7 rail

80 x 125 x 120
0.75 kg
Snap-mounting on S7 rail

80 x 135 x 120
0.5 kg
Snap-mounting on DIN rail
EN 50022-35 x 15, wall-mounting

Mounting adapter for DIN rail


and power connector PS-CPU
see section 9

Mounting adapter for DIN rail


and power connector PS-CPU
see section 9

Siemens KT 10.1 2002

2/5

SITOP power Standard 24 V


Single-phase
Notes

2/6

Siemens KT 10.1 2002

Output currents 2.5 to 4 A

SITOP power
Standard 24 V
Single-phase

3/2

The universal types

3/2

The S7-200 type

Siemens KT 10.1 2002

3/1

SITOP power Standard 24 V


Single-phase
Output currents 2.5 to 4 A

SITOP power Standard 24 V

Overview

The universal types

The S7-200 type

Application

The universal power supplies for all supply systems, with a


wide-range input from 93 to 264 V AC and 110 to 350 V DC for
supplying power from all typical systems. The design matches
the SIMATIC S5 95/100.

Design and functionality are


perfectly matched to the
SIMATIC S7-200 micro PLC;
the slim design is particularly
suitable for low cabinet
depths.

Technical specifications
Power supply type

2.5 A

4A

3.5 A

Order No.

6EP1 332-1SH12

6EP1 332-1SH22

6EP1 332-1SH31

Input
Rated voltage Vin rated

Single-phase AC or DC
120 - 230 V AC
Wide-range input

Single-phase AC or DC
120 - 230 V AC
Wide-range input

Single-phase AC
120/230 V AC
Settable via jumper wire

Voltage range

93 to 264 V AC or
110 to 350 V DC

93 to 264 V AC or
110 to 350 V DC

93 to 132 V/187 to 264 V AC

Mains buffering at Iout rated

> 20 ms at Vin = 120 V, > 80 ms


(100 ms typ.) at Vin = 187 V
0/50/60 Hz; 47 to 63 Hz
1.3 - 0.7 A
< 33 A, < 3 ms (Vin = 230 V)

> 20 ms at Vin = 120 V, > 80 ms


(100 ms typ.) at Vin = 187 V
0/50/60 Hz; 47 to 63 Hz
1.8 - 1.1 A
< 33 A, < 3 ms (Vin = 230 V)

> 20 ms at Vin = 187 V

Rated line frequency; range


Rated current Iin rated
Inrush current limitation (+25 C)

50/60 Hz; 47 to 63 Hz
1.65/0.95 A
< 33 A, < 3 ms (Vin = 230 V)

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

< 3.5 A2s


< 3.5 A2s
< 1.0 A2s
T 3.15 A (not accessible)
T 3.15 A (not accessible)
T 2.5 A (not accessible)
Two-pole circuit-breaker, from 10 A, Characteristic C or from 6 A, Characteristic D

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
1%
0.1 %
0.2 %

24 V DC
1%
0.1 %
0.2 %

24 V DC
5 % ( 2 % typ.)
0.1 %
0.2 %

Residual ripple
(modulation freq.: approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 50 mVpp (40 mVpp typ.)

< 50 mVpp (40 mVpp typ.)

< 150 mVpp (30 mVpp typ.)

< 100 mVpp (40 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 100 mVpp (40 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 240 mVpp (110 mVpp typ.)

No overshoot of Vout
(soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +60 C

< 0.6 s/20 ms typ.


2.5 A

< 0.6 s/20 ms typ.


4A

< 1 s/80 ms typ.


3.5 A

0 to 2.5 A
0 to 2.5 A

0 to 4 A
0 to 2.5 A

0 to 3.5 A
0 to 3.5 A

Constant current 2.8 A


Constant current 2.8 A

Constant current 4.4 A


Constant current 4.4 A

5 A for 100 ms, typ.


5 A for 100 ms, typ.

Yes, up to 10

Yes, up to 10

Yes, up to 5

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output
Continued on page 3/3.

3/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output currents 2.5 to 4 A
Technical specifications (continued)
Power supply type

2.5 A

4A

3.5 A

Order No.

6EP1 332-1SH12

6EP1 332-1SH22

6EP1 332-1SH31

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 85 %
Approx. 11 W

Approx. 85 %
Approx. 17 W

Approx. 84 %
Approx. 16 W

Control
Dyn. mains compensation (Vin rated 15 %) 0.3 % Vout
Dyn. load compensation (Iout: 50/100/50 %) 0.5 % Vout typ.

0.3 % Vout
0.5 % Vout typ.

0.3 % Vout
< 10 % Vout ( 2.1 % Vout typ.)

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

< 2 ms (1 ms typ.)
< 2 ms (1 ms typ.)

< 2 ms (1 ms typ.)
< 2 ms (1 ms typ.)

< 5ms
< 5ms

Protection and monitoring


Output overvoltage protection
Current limitation

2.8 A

4.4 A

3.8 A

Short-circuit protection

Constant current characteristic


to 0 V

Constant current characteristic


to 0 V

RMS sustained short-cct current


Overload/short-circuit indicator

<3A

<5A

Constant current characteristic


up to 14 V typ., below electronic
interruption, automatic restart
<4A

Safety
Electrical isolation primary/secondary Yes, SELV output voltage Vout
acc. to EN 60950

Yes, SELV output voltage Vout


acc. to EN 60950

Yes, SELV output voltage Vout


acc. to EN 60950

Protective class (IEC 536; VDE 0106 P1) Class I


Discharge current
< 3.5 mA

Class I
< 3.5 mA

Class I
< 3.5 mA

Technical Inspectorate type testing


CE marking
UL/cUL (CSA) approval

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

FM approval
Approved for use in marine
vessels
Degree of protection (EN 60529;
VDE 0470 Part 1)

IP 20

IP 20

IP 20

EN 50081-1, EN 55022 Class B


Not applicable
EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55022 Class B

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55022 Class B

EN 50082-2, IEC 801-2, -3, -4, -5

0 to +60 C
with natural convection

0 to +50 C
with natural convection

0 to +60 C
with natural convection

25 to +85 C

25 to +85 C

25 to +85 C

EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating
Mechanical specifications
Connections
Mains input L, N, PE

Output L+
Output M

F acc. to DIN 40040: rel. humidity up to 75 % mean value, 95 % on 30 days/year; no condensation

One screw-type terminal each for 2 0.5 to 1.5 mm2 finely stranded,
2 0.5 to 2.5 mm2 single-core
1 screw-type terminal for
2 0.5 to 2.5 mm2
1 screw-type terminal for
2 0.5 to 2.5 mm2

1 screw-type terminal for


2 0.5 to 2.5 mm2
1 screw-type terminal for
2 0.5 to 2.5 mm2

One screw-type terminal each


for
0.5 to 1.0 mm2 finely stranded,
0.5 to 1.5 mm2 single-core
1 screw-type terminal for
0.5 to 1.0 mm2
1 screw-type terminal for
0.5 to 1.0 mm2

Dimensions (W x H x D) in mm
Weight approx.
Mounting

80 x 135 x 120
80 x 135 x 120
0.5 kg
0.5 kg
Snap-mounting on DIN rail EN 50022-35 x 15, wall-mounting

160 x 80 x 62
0.5 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5,
wall-mounting

Accessories

Fixing angle see section 9

Siemens KT 10.1 2002

3/3

SITOP power Standard 24 V


Single-phase
Notes

3/4

Siemens KT 10.1 2002

Output current 5 A

SITOP power
Standard 24 V
Single-phase

4/2

The standard type

4/2

The industrial version

4/2

The classical type

4/3

The outdoor version

4/3

The flat design

Siemens KT 10.1 2002

4/1

SITOP power Standard 24 V


Single-phase
Output current 5 A

SITOP power Standard 24 V

Overview

The standard type

The industrial version

The classical type

Application

Standard power supply suitable for operation worldwide


in every conceivable field of
application; with limiting of
the input current harmonics
according to EN 61000-3-2.

Power supply like 6EP13332BA00, but for operation in


industry; without limiting of
the input current harmonics
according to EN 61000-3-2.

The well-proven power supply in the SIMATIC S7-300


design, for snap-mounting on
the S7 rail; with PS-CPU
power connector.

Technical specifications
Power supply type

5A

5A

5A

Order No.

6EP1 333-2BA00

6EP1 333-2AA00

6ES7 307-1EA00-0AA0

Input
Rated voltage Vin rated

Single-phase AC
120/230 V AC
Settable via jumper wire

Single-phase AC
120/230 V AC
Settable via jumper wire

Single-phase AC
120/230 V AC
Switch-selectable on the unit

Voltage range

93 to 132 V/187 to 264 V AC

93 to 132 V/187 to 264 V AC

93 to 132 V/187 to 264 V AC

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 10 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.2/0.9 A
< 32 A, 3 ms typ.

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.2/1.3 A
< 32 A, 3 ms typ.

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.0/1.0 A
< 45 A, < 3 ms

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

< 0.8 A2s


T 3.15 A/250 V (not accessible)
from 6 A, Characteristic C

< 0.8 A2s


T 3.15 A/250 V (not accessible)
from 6 A, Characteristic C

< 1.2 A2s (0.8 A2s typ.)


F 4 A/250 V (not accessible)
from 10 A, Characteristic C or
from 6 A, Characteristic D

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.1 %
Approx. 0.2 %

24 V DC
3%
Approx. 0.1 %
Approx. 0.2 %

24 V DC
3%
0.2 %
0.4 %

Residual ripple
(modulation freq.: approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 150 mVpp

< 150 mVpp

< 150 mVpp (40 mVpp typ.)

< 240 mVpp


22.8 to 26.4 V
Green LED for 24 V O.K.
No overshoot of Vout (soft start)

< 240 mVpp


22.8 to 26.4 V
Green LED for 24 V O.K.
No overshoot of Vout (soft start)

< 240 mVpp (90 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout (soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +60 C

< 3 s/80 ms typ.


5A

< 3 s/80 ms typ.


5A

< 3 s/100 ms typ.


5A

0 to 5 A
0 to 5 A

0 to 5 A
0 to 5 A

0 to 5 A
0 to 5 A

Dyn.V/I with
Starting on short circuit
Short-circuit in operation

20 A for 350 ms, typ.

20 A for 350 ms, typ.

14 A for 50 ms
Almost immediate interruption
(approx. 0.5 ms)

Parallel connection for increased


output

Yes, 2 pieces

Yes, 2 pieces

Not permissible

Continued on page 4/4.

4/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output current 5 A
The outdoor version

The flat design

The power supply for extreme


ambient conditions in the
SIMATIC S7-300 design, for
snap-mounting on the S7 rail;
with PS-CPU power connector.

The flat design with the big


performance wherever there
are only minimum mounting
depths, such as in operation
with a distributed arrangement, in machine banks or
recesses. The design
matches the SIMATIC
ET200B.

5A

5A

6ES7 307-1EA80-0AA0

6EP1 333-1AL11

Single-phase AC
120/230 V AC
Switch-selectable on the unit

Single-phase AC
120/230 V AC
Switch-selectable on the unit

93 to 132 V/187 to 264 V AC

93 to 132 V/187 to 264 V AC

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.2/1.2 A
< 45 A, < 3 ms

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.0/1.0 A
< 51 A, < 3 ms

< 1.8 A2s (1.2 A2s typ.)


T 3.15 A/250 V (not accessible)
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 4.7 A2s (2.6 A2s typ.)


F 4 A/250 V (not accessible)
from 10 A, Characteristic C or
from 6 A, Characteristic D

Stabilized, floating direct voltage


24 V DC
3%
0.2 %
0.4 %

24 V DC
3%
0.2 %
0.4 %

< 150 mVpp (40 mVpp typ.)

< 150 mVpp (40 mVpp typ.)

< 240 mVpp (90 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout (soft start)

< 240 mVpp (160 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout (soft start)

< 3 s/100 ms typ.


5A

< 3 s/100 ms typ.


5A

0 to 5 A
0 to 5 A

0 to 5 A
0 to 5 A

20 A for 180 ms
20 A for 80 ms

14 A for 50 ms
Almost immediate interruption
(approx. 0.5 ms)

Not permissible

Not permissible

Continued on page 4/5.

Siemens KT 10.1 2002

4/3

SITOP power Standard 24 V


Single-phase
Output current 5 A
Technical specifications (continued)
Type

5A

5A

5A

Order No.

6EP1 333-2BA00

6EP1 333-2AA00

6ES7 307-1EA00-0AA0

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 87 %
Approx. 18 W

Approx. 87 %
Approx. 18 W

Approx. 88 %
Approx. 17 W

Control
Dyn. mains compens. (Vin rated 15 %) Approx. 0.3 % Vout
Dyn. load compens. (Iout: 50/100/50 %) 2.5 % Vout

Approx. 0.3 % Vout


2.5 % Vout

0.3 % Vout
2.5 % Vout

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

0.2 ms typ
0.2 ms typ

0.2 ms typ
0.2 ms typ

< 5 ms (0.1 ms typ.)


< 5 ms (0.1 ms typ.)

Protection and monitoring


Output overvoltage protection

Yes, acc. to EN 60 950

Yes, acc. to EN 60 950

Current limitation

5.5 to 6.5 A typ.

5.5 to 6.5 A typ.

Additional control circuit,


interruption at approx. 30 V,
automatic restart
5.5 to 6.5 A

Short-circuit protection
RMS sustained short-cct current
Overload/short-circuit indicator

Electr. interr., automatic restart


< 17 A

Electr. interr., automatic restart


< 17 A

Electr. interr., automatic restart


<5A

Safety
Electrical isolation
primary/secondary

Yes, SELV output voltage Vout


acc. to EN 60950

Yes, SELV output voltage Vout


acc. to EN 60950

Protective class (IEC 536; VDE 0106 P1) Class I


Discharge current
< 3.5 mA (0.4 mA typ.)

Class I
3.5 mA (0.4 mA typ.)

Yes, SELV output voltage Vout


acc. to EN and EN 60950, clearances in air and leakage paths >
8 mm
Class I
< 3.5 mA (0.3 mA typ.)

Technical Inspectorate type testing


CE marking
UL/cUL (CSA) approval

Yes; CB scheme
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes; CB scheme
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

FM approval
Appr. for use in marine vessels
Degree of protection
(EN 60529; VDE 0470 Part 1)

IP 20

IP 20

Yes, Class I Div. 2 Gr. A, B, C, D Part 4


Yes, Germanischer Lloyd
IP 20

EMC
Interference emission
Line harmonics limitation
Interference immunity

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55022 Class B

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-2, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

Operating specifications
Ambient temperature range

0 to +60 C with nat. convection

0 to +60 C with nat. convection

0 to +60 C with nat. convection

25 to +85 C

25 to +85 C

25 to +85 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm2
3 screw-type terminals for
0.5 to 2.5 mm2

Dimensions (W x H x D) in mm
Weight approx.
Mounting

75 x 125 x 125
0.75 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

75 x 125 x 125
0.57 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

80 x 125 x 120
0.74 kg
Snap-mounting on S7 rail

Accessories

Mounting adapter for DIN rail


and power connector PS-CPU
see section 9

Transportation and storage


temperature range
Humidity rating

Mechanical specifications
Connections
Mains input L, N, PE
Output L+
Output M

4/4

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output current 5 A

5A

5A

6ES7 307-1EA80-0AA0

6EP1 333-1AL11

Approx. 84 %
Approx. 23 W

Approx. 88 %
Approx. 17 W

0.3 % Vout
3 % Vout

0.3 % Vout
2.1 % Vout

< 5 ms (0.2 ms typ.)


< 5 ms (0.2 ms typ.)

< 5 ms (0.1 ms typ.)


< 5 ms (0.1 ms typ.)

Additional control circuit,


interruption at approx. 30 V,
automatic restart
5.5 to 6.5 A

Additional control circuit,


interruption at approx. 30 V,
automatic restart
5.5 to 6.5 A

Electr. interr., automatic restart


<5A

Electr. interr., automatic restart


<5A

Yes, SELV output voltage Vout


acc. to EN 60950 and EN 50178,
clearances in air and leakage
paths > 8 mm
Class I
< 3.5 mA (0.3 mA typ.)

Yes, SELV output voltage Vout


acc. to EN and EN 60950, clearances in air and leakage paths >
8 mm
Class I
< 3.5 mA (2.6 mA typ.)

Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes, GL, ABS, DNV, LRS


IP 20

IP 20

EN 50081-2, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-2, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

25 to +70 C w. nat. convection

0 to +60 C with nat. convection

25 to +85 C

25 to +85 C

Rel. humidity up to 75%


mean value, 95 %
on 30 days/year,
short-term condens. permissible

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm2
3 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm2
3 screw-type terminals for
0.5 to 2.5 mm2

80 x 125 x 120
0.75 kg
Snap-mounting on S7 rail

160 x 130 x 60
0.74 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Mounting adapter for DIN rail


and power connector PS-CPU
see section 9

Fixing angle see section 9

Siemens KT 10.1 2002

4/5

SITOP power Standard 24 V


Single-phase
Notes

4/6

Siemens KT 10.1 2002

Output current 10 A

SITOP power
Standard 24 V
Single-phase

5/2

The standard type

5/2

The industrial version

5/2

The IP 65 version

5/3

The classical type

5/3

The flat design

5/3

The universal type

Siemens KT 10.1 2002

5/1

SITOP power Standard 24 V


Single-phase
Output current 10 A

Application

SITOP power Standard 24 V

The standard type

The industrial version

The IP 65 version

Standard power supply suitable for operation worldwide


in every conceivable field of
application; with limiting of
the input current harmonics
according to EN 61000-3-2.

Power supply like 6EP13342BA00, but for operation in


industry; without limiting of
the input current harmonics
according to EN 61000-3-2.

Power supply in degree of


protection IP 65, design and
functionality are perfectly
matched to the ET 200X distributed I/O device. When
operated without the ET 200X,
connector seals are required
as accessories.

Technical specifications
Power supply type

10 A

10 A

10 A

Order No.

6EP1 334-2BA00

6EP1 334-2AA00

6EP1 334-2CA00

Input
Rated voltage Vin rated

Single-phase AC
120/230 V AC
Settable via jumper wire

Single-phase AC
120/230 V AC
Settable via jumper wire

Single-phase AC
120/230 V AC
Settable via jumper wire

Voltage range

85 to 132 V/187 to 264 V AC

85 to 132 V/187 to 264 V AC

93 to 132 V/187 to 264 V AC

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 10 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
5.5/2.1 A
< 65 A, 3 ms typ.

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
5.5/3.2 A
< 65 A, 3 ms typ.

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
4.3/2.6 A
< 65 A, 3 ms typ.

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

< 3.3 A2s


T 6.3 A/250 V (not accessible)
from 10 A, Characteristic C

< 3.3 A2s


T 6.3 A/250 V (not accessible)
from 10 A, Characteristic C

< 2.5 A2s


T 6.3 A/250 V (not accessible)
from 16 A, Characteristic C

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.2 %
Approx. 1 %

24 V DC
3%
Approx. 0.2 %
Approx. 1 %

24 V DC
3%
Approx. 0.2 %
Approx. 1 %

Residual ripple
(modulation freq.: approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 150 mVpp

< 150 mVpp

< 150 mVpp

< 240 mVpp


22.8 to 28.8 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

< 240 mVpp


22.8 to 28.8 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

< 240 mVpp


22.8 to 25.2 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +60 C

< 3 s/80 ms typ.


10 A

< 3 s/80 ms typ.


10 A

< 3 s/80 ms typ.


10 A

0 to 12 A
0 to 10 A

0 to 12 A
0 to 10 A

0 to 10 A (up to +40 C)
0 to 8 A (up to +55 C)

38 A for 200 ms, typ.

38 A for 200 ms, typ.

38 A for 200 ms, typ.

Yes, 2 pieces

Yes, 2 pieces

Yes, 2 pieces

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output
Continued on page 5/4.

5/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase
Output current 10 A
The classical type

The flat design

The universal type

The well-proven power supply in the SIMATIC S7-300


design, for snap-mounting on
the S7 rail; with PS-CPU
power connector.

The flat design with the big


performance wherever there
are only minimum mounting
depths, such as in operation
with a distributed arrangement, in machine banks or
recesses. The design matches the SIMATIC ET 200B.

The universal power supply


for all supply systems, with a
wide-range input from 93 to
264 V AC and 110 to 350 V
DC for supplying power from
all typical systems. The
design matches the SIMATIC
S7-300.

10 A

10 A

10 A

6ES7 307-1KA00-0AA0

6EP1 334-1AL11

6EP1 334-1SH01

Single-phase AC
120/230 V AC
Switch-selectable on the unit

Single-phase AC
120/230 V AC
Switch-selectable on the unit

Single-phase AC or DC
120 - 230 V AC
Wide-range input

93 to 132 V/187 to 264 V AC

93 to 132 V/187 to 264 V AC

93 to 264 V AC or 110 to 350


V DC

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
3.5/1.7 A
< 55 A, < 3 ms

> 20 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
3.5/1.7 A
< 55 A, < 3 ms

> 20 ms at Vin = 93/187 V


0/50/60 Hz; 47 to 63 Hz
2.5 - 1.3 A
< 20 A, < 3 ms

< 8.9 A2s


T 5 A/250 V (not accessible)
from 16 A, Characteristic C or
from 8 A, Characteristic D

< 8.9 A2s


T 5 A/250 V (not accessible)
from 16 A, Characteristic C or
from 8 A, Characteristic D

< 1.5 A2s


T 6.3 A (not accessible)
from 10 (16) A, Characteristic C
or
from 6 (8) A, Characteristic D

Stabilized, floating direct voltage


24 V DC
3%
< 0.1 %
< 0.2 %

24 V DC
3%
< 0.2 %
< 0.4 %

24 V DC
1%
< 0.1 %
< 0.2 %

< 150 mVpp (80 mVpp typ.)

< 150 mVpp (80 mVpp typ.)

< 100 mVpp

< 240 mVpp (120 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 240 mVpp (120 mVpp typ.)

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 100 mVpp

Green LED for 24 V O.K.


No overshoot of Vout
(soft start)

< 3 s/150 ms typ.


10 A

< 3 s/150 ms typ.


10 A

< 3 s/100 ms typ.


10 A

0 to 10 A
0 to 10 A

0 to 10 A
0 to 10 A

0 to 10 A
0 to 10 A

22 A for 150 ms, typ.


Almost immediate interruption
(approx. 0.5 ms)
Not permissible

22 A for 150 ms, typ.


Almost immediate interruption
(approx. 0.5 ms)
Not permissible

Constant current approx. 11 A


Constant current approx. 11 A
Yes, 2 pieces

Continued on page 5/5.

Siemens KT 10.1 2002

5/3

SITOP power Standard 24 V


Single-phase
Output current 10 A
Technical specifications (continued)
Type

10 A

10 A

10 A

Order No.

6EP1 334-2BA00

6EP1 334-2AA00

6EP1 334-2CA00

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 89 %
Approx. 30 W

Approx. 89 %
Approx. 30 W

Approx. 87 %
Approx. 36 W

Control
Dyn. mains compensation (Vin rated 15 %) Approx. 0.3 % Vout
Dyn. load compensation (Iout: 50/100/50 %) 5 % Vout

Approx. 0.3 % Vout


5 % Vout

Approx. 0.3 % Vout


5 % Vout

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

0.2 ms typ
0.2 ms typ

0.2 ms typ
0.2 ms typ

0.2 ms typ
0.2 ms typ

Protection and monitoring


Output overvoltage protection

Yes, acc. to EN 60950

Yes, acc. to EN 60950

Yes, acc. to EN 60950

Current limitation

13 to 15 A typ.

13 to 15 A typ.

9 to 11 A typ.

Short-circuit protection

Electronic interruption, automatic


restart
< 21 A

Electronic interruption, automatic


restart
< 21 A

Choice of automatic restart or


latching interruption
< 21 A
Red LED for overtemp. tripping

Yes, SELV output voltage Vout


acc. to EN 60950
Class I
< 3.5 mA (0.4 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950
Class I
< 3.5 mA (0.9 mA typ.)

RMS sustained short-cct current


Overload/short-circuit indicator

Safety
Electrical isolation primary/secondary Yes, SELV output voltage Vout
acc. to EN 60950
Protective class (IEC 536; VDE 0106 T1) Class I
Discharge current
< 3.5 mA (0.4 mA typ.)
Techn. Inspectorate type testing
CE marking
UL/cUL (CSA) approval

Yes; CB scheme
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes; CB scheme
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

FM approval

IP 20

IP 65

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55022 Class B

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

0 to +60 C with natural convection

0 to +60 C with natural convection

25 to +55 C
(power derating from +40 C)

25 to +85 C

25 to +85 C

40 to +70 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.5 to 2.5 mm2
2 screw-type terminals for
0.5 to 2.5 mm2

Screw-type terminals for 0.5 to


2.5 mm2 (PG11 connection)

Dimensions (W x H x D) in mm
Weight approx.
Mounting

100 x 125 x 135


1.08 kg
Snap-mounting on DIN rail
EN 50 022-35 x 15/7.5

100 x 125 x 135


0.78 kg
Snap-mounting on DIN rail
EN 50 022-35 x 15/7.5

140 x 270 x 126


1.7 kg
Wall-mounting, any position

Accessories

Connector seals IP 65
see section 9

Appr. for use in marine vessels

Degree of protection (EN 60529; VDE IP 20


0470 Part 1)
EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating

Mechanical specifications
Connections
Mains input L, N, PE
Output L+
Output M

5/4

Siemens KT 10.1 2002

Screw-type terminal or via expansion interface to backplane bus of


ET 200X

SITOP power Standard 24 V


Single-phase
Output current 10 A

10 A

10 A

10 A

6ES7 307-1KA00-0AA0

6EP1 334-1AL11

6EP1 334-1SH01

Approx. 87 %
Approx. 36 W

Approx. 87 %
Approx. 36 W

Approx. 85 %
Approx. 42 W

0.3 % Vout
0.6 % Vout

0.3 % Vout
0.6 % Vout

0.3 % Vout
1.5 % Vout

< 5 ms (0.1 ms typ.)


< 5 ms (0.2 ms typ.)

< 5 ms (0.1 ms typ.)


< 5 ms (0.2 ms typ.)

< 20 ms (10 ms typ.)


< 20 ms (10 ms typ.)

Additional control circuit,


interruption at approx. 30 V,
automatic restart
11 to 13 A

Additional control circuit,


interruption at approx. 30 V,
automatic restart
11 to 13 A

Yes, acc. to EN 60950

Electronic interruption, automatic


restart
< 10 A, (7 A typ.)

Electronic interruption, automatic


restart
< 10 A, (7 A typ.)

Constant current characteristic


up to 0 V
< 14 A

Yes, SELV output voltage


Vout acc. to EN 60950
Class I
< 3.5 mA (2.4 mA typ.)

Yes, SELV output voltage


Vout acc. to EN 60950
Class I
< 3.5 mA (2.4 mA typ.)

Yes, SELV output voltage


Vout acc. to EN 60950
Class I
< 3.5 mA

Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes, Class I Div. 2, A, B, C, D


Part 4
Yes, Germanischer Lloyd
IP 20

IP 20

IP 20

EN 50081-2, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-2, EN 55011 Class A

EN 50082-2, IEC 801-2, -3, -4, -5

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2, IEC 801-2, -3, -4, -5

0 to +60 C with natural convection

0 to +60 C with natural convection

0 to +60 C with natural convection

25 to +85 C

25 to +85 C

25 to +85 C

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
4 screw-type terminals for
0.5 to 2.5 mm
4 screw-type terminals for
0.5 to 2.5 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm
3 screw-type terminals for
0.5 to 2.5 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
3 screw-type terminals for
0.5 to 2.5 mm
3 screw-type terminals for
0.5 to 2.5 mm

200 x 125 x 120


1.2 kg
Snap-mounting on S7 rail

220 x 130 x 60
1.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

200 x 125 x 135


1.8 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/
or on S7 rail

Mounting adapter for DIN rail


and power connector PS-CPU
see section 9

Fixing angle see section 9

11 to 13 A

Siemens KT 10.1 2002

5/5

SITOP power Standard 24 V


Single-phase
Notes

5/6

Siemens KT 10.1 2002

Output current 20 A

SITOP power
Standard 24 V
Single-phase/twophase

6/2

The standard type

6/2

The two-phase version

Siemens KT 10.1 2002

6/1

SITOP power Standard 24 V


Single-phase/two-phase
Output current 20 A

Application

SITOP power Standard 24 V

The standard type

The two-phase version

This power supply - developed to the latest standards is suitable for operation
worldwide in every conceivable field of application.

Power supply with a widerange two-phase input for


highly variable supply systems (> 550 V) as well as for
industrial systems in Canada
and the USA.

Technical specifications
Type

20 A

20 A

Order No.

6EP1 336-2BA00

6EP1 536-2AA00

Input
Rated voltage Vin rated

Single-phase AC
120/230 V AC
Settable via jumper wire

Two-phase AC
500 to 600 V two-phase AC
wide-range input

Voltage range

93 to 132 V/187 to 264 V AC

two-phase AC 420 to 682 V

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iout rated
Inrush current limitation (+25 C)
I 2t

> 10 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
8.0/3.3 A
< 81 A
< 8 A2s

6/30 ms at Vin = 420/600 V


50/60 Hz; 47 to 63 Hz
1.82 A (at 420 V)
25 A typ.
< 1.0 A2s

Integrated line-side fuse


Required circuit-breaker (IEC
898) in mains supply cable

T 10 A (not accessible)
from 16 A, Characteristic C

None
Two-phase coupled circuitbreaker Char. C 4 to 10 A or
motor circuit-breaker
3VU1300-0MJ00 or
3RV1021-1DA10, set to 3 A

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
3%

24 V DC
2%

Residual ripple (modulation frequency: approx. 50 kHz)


Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 150 mVpp

< 150 mVpp

< 240 mVpp


22.8 to 26.4 V 1)
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

< 240 mVpp


22.8 to 28.8 V 2)
Green LED for 24 V O.K.
Slight overshoot of Vout
(< 2 V for max. 500 ms)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +60 C

< 3 s/80 ms typ.


20 A

20 A

0 to 20 A
0 to 20 A (+55 C)

0 to 20 A
0 to 20 A

Constant current approx. 20 A


Constant current approx. 20 A
Yes, 2 pieces 1)

Constant current approx. 25 A


Constant current approx. 28 A
Yes, 2 pieces 2)

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output

1) Only permissible for ambient temperatures from 0 to +45 C.


2) Only permissible for ambient temperatures from 0 to +50 C.

6/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Single-phase/two-phase
Output current 20 A
Technical specifications (continued)
Type

20 A

20 A

Order No.

6EP1 336-2BA00

6EP1 536-2AA00

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 87 %
Approx. 72 W

Approx. 89 %
Approx. 60 W

Approx. 0.3 % Vout

1 % Vout

1 % Vout

4%, +2 % Vout

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

Vout remains within tolerance


Vout remains within tolance

< 3ms
< 3ms

Protection and monitoring


Output overvoltage protection

Yes, acc. to EN 60950

Yes, acc. to EN 60950

22 A typ.
Constant current characteristic
to 0 V
< 22 A

21 to 26 A typ.
Constant current approx. 28 A

Control
Dyn. mains compensation, typ.
(Vout rated 15 %)
Dyn. load compensation, typ.
(Iout 50/100/50 %)

Current limitation
Short-circuit protection
RMS sustained short-cct current
Overload/short-circuit indicator

Safety
Electrical isolation primary/secondary Yes, SELV output voltage Vout
acc. to EN 60950
Protective class (IEC 536; VDE 0106 T1) Class I
Discharge current
< 3.5 mA
Technical Inspectorate type test
CE marking
UL/cUL (CSA) approval

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

FM approval

Appr. for use in marine vessels

Degree of protection (EN 60529; VDE IP 20


0470 Part 1)
EMC
Interference emission
Line harmonics limitation
Interference immunity

Approx. 28 A

Yes, SELV output voltage Vout


acc. to EN 60950
Class I
< 0.78 mA (550 V/60 Hz)
Yes
Yes
Yes, UL/CSA listed (UL 508,
CSA 22.2), File E143289

IP 20

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2,
EN 61000-4-2, -3, -4, -6

EN 50081-2, EN 55011 Class A


EN 61000-3-2
EN 50082-2, IEC 801

0 to +55 C with natural convection

0 to +60 C with natural convection

25 to +85 C

25 to +85 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm2
2 screw-type terminals for
0.33 to 10 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm2
2 screw-type terminals for
0.33 to 10 mm2

Dimensions (W x H x D) in mm
Weight, approx.
Mounting

280 x 125 x 92
2.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

280 x 180 x 92
3.3 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Accessories

Fixing angle 90 see section 9

Fixing angle 90 see section 9

Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating
Mechanical specifications
Connections
Mains input L, N, PE
Output L+
Output M

Siemens KT 10.1 2002

6/3

SITOP power Standard 24 V


Single-phase/two-phase
Notes

6/4

Siemens KT 10.1 2002

Output currents
10 to 40 A

SITOP power
Standard 24 V
Three-phase

7/2

SITOP modular 20 A and 40 A

7/4

SITOP modular buffer module

7/4

SITOP modular signaling module

7/6

10 A and 20 A version

7/7

30 A and 40 A version

Siemens KT 10.1 2002

7/1

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A

SITOP power Standard 24 V

SITOP modular 20 A und 40 A

Application

Modular power supply with 24 V/20 A and 24 V/40 A basic


devices, suitable for operation worldwide in every conceivable
field of application; with wide-range 320 to 550 V three-phase
AC input, radio interference suppression level class B, limiting
of the input current harmonics acc. to EN 61000-3-2, three LED
operating displays, selectable short-circuit response: constant
current or latching interruption; extended functions with optional
additional buffer module (6EP1961-3BA00) and module for output of status signals (6EP1961-3BA10).

Technical specifications
Type

20 A

40 A

Order No.

6EP1 436-3BA00

6EP1 437-3BA00

Input
Rated voltage Vin rated

Three-phase AC
400 - 500 V three-phase AC
Wide-range input

Three-phase AC
400 to 500 V three-phase AC
Wide-range input

Voltage range

320 to 550 V

320 to 550 V

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)
I2t

> 6 ms at Vin = 400 V


50/60 Hz; 47 to 63 Hz
1.1 A (Vin = 400 V)
< 35 A
< 0.7 A2s

> 6 ms at Vin = 400 V


50/60 Hz; 47 to 63 Hz
2.2 A (Vin = 400 V)
< 70 A
< 2.8 A2s

Integrated line-side fuse


Required circuit-breaker (IEC 898)
in mains supply cable

None
Three-phase coupled circuitbreaker 6 to 16 A Char. C or
motor circuit-breaker 3VU13000MJ00 or 3RV1021-1DA10, set
to 3 A

None
Three-phase coupled circuitbreaker 10 to 16 A Char. C or
motor circuit-breaker 3VU13000MJ00 or 3RV1021-1DA10, set
to 3 A

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.1 %
Approx. 0.2 %

Residual ripple
(modulation frequency:
approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 100 mVpp

< 100 mVpp

< 200 mVpp


24 to 28.8 V (max. 480 W)
Green LED for 24 V O.K.
No overshoot of Vout (soft start)

< 200 mVpp


24 to 28.8 V (max. 960 W)
Green LED for 24 V O.K.
No overshoot of Vout (soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range up to +60 C

< 2.5 s / < 500 ms


20 A
0 to 20 A

< 2.5 s / < 500 ms


40 A
0 to 40 A

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output

Approx. 23 A
60 A for 25 ms, typ.
Yes, 2 pieces (selectable current characteristic)

Approx. 46 A
100 A for 25 ms, typ.
Yes, 2 pieces (selectable current characteristic)

7/2

Siemens KT 10.1 2002

24 V DC
3%
Approx. 0.1 %
Approx. 0.2 %

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
Technical specifications (continued)
Type

20 A

40 A

Order No.

6EP1 436-3BA00

6EP1 437-3BA00

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 90 %
Approx. 53 W

Approx. 90 %
Approx.106 W

Control
Dyn. mains comp., Vin rated 15 %)
Dyn. load compensation, Iout 50/100/50 %)

< 1 % Vout
Approx. 2 % Vout

< 1 % Vout
Approx. 2 % Vout

Settling time
load step from 50 to 100%
load step from 100 to 50%

< 10 ms (4 ms typ.)
< 10 ms (4 ms typ.)

< 10 ms (4 ms typ.)
< 10 ms (4 ms typ.)

Protection and monitoring


Output overvoltage protection

< 35 V

< 35 V

23 A typ.
Choice of constant current characteristic approx. 23 A or latching shutdown
Approx. 23 A
Yellow LED for "overload"
Red LED for "latching shutdown

46 A typ.
Choice of constant current characteristic approx. 46 A or latching shutdown
Approx. 46 A
Yellow LED for "overload"
Red LED for "latching shutdown

Safety
Electrical isolation primary/secondary Yes, SELV output voltage Vout
acc. to EN 60950 and EN 50178
Protective class (IEC 536; VDE 0106 P1) Class I
Discharge current
< 3.5 mA

Yes, SELV output voltage Vout


acc. to EN 60950 and EN 50178
Class I
< 3.5 mA

Current limitation
Short-circuit protection
RMS sustained short-cct current
Overload/short-circuit indicator

Technical Inspectorate type test


CE marking
UL/cUL (CSA) approval

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E197259

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E197259

FM approval
Appr. for use in marine vessels
Degree of protection
(EN 60529; VDE 0470 Part 1)

IP 20

IP 20

EN 50081-2, EN 55022 Class B


EN 61000-3-2
EN 61000-6-2,
EN 61000-4-2, -3, -4, -5, -6, -11

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 61000-6-2,
EN 61000-4-2, -3, -4, -5, -6, -11

0 to +60 C with natural convection

0 to +60 C with natural convection

25 to +85 C

25 to +85 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
2 screw-type terminals for
0.5 to 4 mm2
2 screw-type terminals for
0.5 to 4 mm2

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
2 screw-type terminals for
0.5 to 10 mm2
2 screw-type terminals for
0.5 to 10 mm2

Dimensions (W x H x D) in mm
Weight approx.
Mounting

160 x 125 x 125


2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

240 x 125 x 125


3.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Accessories

Buffer module (6EP1961-3BA00)


Signaling module (6EP19613BA10)

Buffer module (6EP1961-3BA00)


Signaling module (6EP19613BA10)

EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating
Mechanical specifications
Connections
Mains input L, N, PE
Output +
Output

Siemens KT 10.1 2002

7/3

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
Overview

SITOP modular
buffer module

SITOP modular
signaling module

Application

The buffer module, combined with the SITOP 20 A


(6EP1436-3BA00) or SITOP 40
A (6EP1437-3BA00) stabilized 24 V load current supply, serves for buffering the
load current during short-term
power outages. The buffering
module is connected in parallel to the output of the power
supply.

The signaling module, combined with the SITOP 20 A


(6EP1436-3BA00) or the SITOP
40 A (6EP1437-3BA00) stabilized 24 V load current power
supply, serves for producing
status signals representing the
operating status of the power
supply and for remote-activating/deactivating the power
supply; connecting to the
power supply automatically.

Technical specifications
Order No.

6EP1 961-3BA00

6EP1 961-3BA10

Input/output
Rated input voltage Vin rated

Stabilized, floating direct voltage


24 V DC

Input voltage range


Control input

24 to 28.8 V

Rated output voltage Vout rated


Rated current Iout rated
Mains buffering

Vin approx. 1 V
40 A
100 ms at 40 A or
200 ms at 20 A load current
3s

Non-floating input for remote


activating/deactivating the
power supply

Max. buffer time


Parallel connection for
increased output
Protection and monitoring
Static current limitation
Short-circuit protection
Displays/status signals
Operating display
24 V DC O.K.
Ready for operation
Power supply OK
Safety
Electrical isolation (EN 60950)
Protective class
(IEC 536; VDE 0106 P1)
Technical Inspectorate type test
CE marking
UL/cUL (CSA) approval
FM approval
Appr. for use in marine vessels
Degree of protection
(EN 60529; VDE 0470 Part 1)

7/4

Siemens KT 10.1 2002

Yes, 2 pieces

40 A typ.
Electronic
Green LED for supply voltage
> 20.5 V

Floating relay contact (CO contact), rating 6 A/240 VAC


Floating relay contact (CO contact), rating 6 A/240 VAC

Yes, SELV
Class I

Yes, SELV
Class I

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E197259

IP 20

Yes
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E197259

IP 20

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
Technical specifications (continued)
Order No.
EMC
Interference emission
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating
Mechanical specifications
Connections

Dimensions (W x H x D) in mm
Weight approx.
Mounting

6EP1 961-3BA00

6EP1 961-3BA10

EN 50081-1, EN 55022 Class B


EN 61000-6-2,
EN 61000-4-2, -3, -4, -5, -6, -11

EN 50081-1, EN 55022 Class B


EN 61000-6-2,
EN 61000-4-2, -3, -4, -5, -6, -11

0 to +60 C with natural convection

0 to +60 C with natural convection

25 to +85 C

25 to +85 C

Climate category 3K3 acc. to EN


60721

Climate category 3K3 acc. to EN


60721

One screw-type terminal each


for + and for 0.5 to 10 mm2
single-core/finely stranded

Screw-type terminals for


0.14 to 2.5 mm2 single-core/
finely stranded

70 x 125 x 125
1.2 kg
Snap-mounting on DIN rail
EN 50022-35x5/7.5

26 x 125 x 116
0.15 kg
Snapped directly onto side of
basic unit

Siemens KT 10.1 2002

7/5

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
10 A version

Application

20 A version

These 24 V/10 A and 24 V/20 A power supplies, developed


according to the latest standards, are suitable for operation
worldwide in every conceivable field of application; with a widerange input of 360 to 550 V three-phase AC and limiting of the
input current harmonics according to EN 61000-3-2.

Technical specifications
Type

10 A

20 A

Order No.

6EP1 434-2BA00

6EP1 436-2BA00

Input
Rated voltage Vin rated

Three-phase AC
400 to 500 V three-phase AC
Wide-range input

Three-phase AC
400 to 500 V three-phase AC
Wide-range input

Voltage range

360 to 550 V three-phase AC


(340 to 360 V for max. 2 s or
at max. 0.9 x Iout rated)

360 to 550 V three-phase AC


(340 to 360 V for max. 2 s or
at max. 0.9 x Iout rated)

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated at 400 V
Inrush current limitation (+25 C)

> 6 ms at Vin = 360 V


50/60 Hz; 47 to 63 Hz
0.65 A
< 25 A

> 3 ms at Vin = 360 V


50/60 Hz; 47 to 63 Hz
1.2 A
< 25 A

I t
Integrated line-side fuse
Required circuit breaker in mains
supply cable

< 1.0 As
None
Three-phase coupled circuitbreaker Char. C up to 25 A
(recomm. 6 A) or motor circuitbreaker 3VU1300-0MJ00 or
3RV1021-1DA10, set to 3 A

< 1.0 As
None
Three-phase coupled circuitbreaker Char. C up to 25 A
(recomm. 6 A) or motor circuitbreaker 3VU1300-0MJ00 or
3RV1021-1DA10, set to 3 A

Output
Rated voltage Vout rated
Total tolerance

Stabilized, floating direct voltage


24 V DC
3%

24 V DC
3%

Residual ripple
(modulation freq.: approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range 1)
Operation indicator
Power ON/OFF behavior

< 150 mVpp (60 mVpp typ.)

< 150 mVpp (60 mVpp typ.)

< 240 mVpp (120 mVpp typ.)


22.8 to 26.4 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

< 240 mVpp (120 mVpp typ.)


22.8 to 26.4 V
Green LED for 24 V O.K.
No overshoot of Vout
(soft start)

Starting delay/voltage rise


Rated current Iout rated
Current range
up to +45 C
up to +55 C

< 3 s/40 ms typ.


10 A

< 3 s/40 ms typ.


20 A

0 to 10 A
0 to 10 A

0 to 20 A
0 to 20 A

Constant current approx. 18 A


Constant current approx. 18 A
Yes, 2 pieces

Constant current approx. 30 A


Constant current approx. 30 A
Yes, 2 pieces

Dyn.V/I with
Starting on short circuit
Short-circuit in operation
Parallel connection for
increased output 1)
Continued on page 7/8.

1) Only permissible for ambient temperatures from 0 to +45 C.

7/6

Siemens KT 10.1 2002

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
30 A version

40 A version

These 24 V/30 A and 24 V/40 A power supplies, developed


according to the latest standards, are suitable for operation
worldwide in every conceivable field of application; with a wide
input range of 360 to 550 V three-phase AC and limiting of the
input current harmonics according to EN 61 000-3-2.

30 A

40 A

6EP1 437-2BA00

6EP1 437-2BA10

Three-phase AC
400 to 500 V three-phase AC
Wide-range input

Three-phase AC
400 to 500 V three-phase AC
Wide-range input

360 to 550 V three-phase AC


(340 to 360 V for max. 2 s or at
max. 0.9 x Iout rated)

360 to 550 V three-phase AC


(340 to 360 V for max. 2 s or at
max. 0.9 x Iout rated)

> 4.5 ms at Vin = 360 V


50/60 Hz; 47 to 63 Hz
1.4 A
< 25 A

> 3 ms at Vin = 360 V


50/60 Hz; 47 to 63 Hz
1.9 A
< 25 A

< 1.0 As
None
Three-phase coupled circuitbreaker Char. C up to 25 A (recommended: 6 A) or motor circuitbreaker 3VU1300-0MJ00 or
3RV1021-1DA10, set to 3 A

< 1.0 As
None
Three-phase coupled circuitbreaker Char. C up to 25 A (recommended: 6 A) or motor circuitbreaker 3VU1300-0MJ00 or
3RV1021-1DA10, set to 3 A

Stabilized, floating direct voltage


24 V DC
3%

24 V DC
3%

< 150 mVpp (50 mVpp typ.)

< 150 mVpp (50 mVpp typ.)

< 240 mVpp (200 mVpp typ.)


22.8 to 26.4 V
Green LED for 24 V O.K.
Slight overshoot of Vout (< 2 V for
max. 500 ms)

< 240 mVpp (200 mVpp typ.)


22.8 to 26.4 V
Green LED for 24 V O.K.
Slight overshoot of Vout (< 2 V for
max. 500 ms)

< 3 s/40 ms typ.


30 A

< 3 s/40 ms typ.


40 A

0 to 30 A
0 to 30 A

0 to 40 A
0 to 40 A

Approx. 60 A for 600 ms


Approx. 60 A for 600 ms
Yes, 2 pieces

Approx. 70 A for 600 ms


Approx. 70 A for 600 ms
Yes, 2 pieces

Continued on page 7/9.

Siemens KT 10.1 2002

7/7

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A
Technical specifications (continued)
Type

10 A

20 A

Order No.

6EP1 434-2BA00

6EP1 436-2BA00

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 89 %
Approx. 30 W

Approx. 89 %
Approx. 59 W

Control
Dyn. mains compensation (Vin rated 15 %) < 1 % Vout
Dyn. load compensation (Iout: 50/100/50 %) 1 % Vout

< 1 % Vout
1 % Vout

Settling time
Load step from 50 to 100 %
Load step from 100 to 50 %

< 4ms
< 4ms

< 4ms
< 4ms

Protection and monitoring


Output overvoltage protection
Current limitation

Yes, acc. to EN 60 950


10.5 to 13 A typ.

Yes, acc. to EN 60 950


21 to 26 A typ.

Constant current characteristic


to 0 V
< 20 A

Constant current characteristic


to 0 V
< 30 A

Yes, SELV output voltage Vout


acc. to EN 60950
Class I

Yes, SELV output voltage Vout


acc. to EN 60950
Class I

< 0.35 mA (550 V/60 Hz)

< 0.35 mA (550 V/60 Hz)

Technical Inspectorate type test


CE marking
UL/cUL (CSA) approval

Yes; CB scheme
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes; CB scheme
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

FM approval
Appr. for use in marine vessels
Degree of protection
(EN 60 529; VDE 0470 T1)

IP 20

IP 20

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2,
EN 61000-4-2, -3, -4, -5

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2,
EN 61000-4-2, -3, -4, -5

0 to +55 C with natural convection

0 to +55 C with natural convection

25 to +85 C

25 to +85 C

Climate category 3K3


acc. to EN 60721

Climate category 3K3


acc. to EN 60721

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm
2 screw-type terminals for
0.33 to 10 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm
2 screw-type terminals for
0.33 to 10 mm

Dimensions (W x H x D) in mm
Mounting surface requirement
in mm
Weight approx.
Mounting

280 x 125 x 92
320 x 225

280 x 125 x 92
320 x 225

2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Accessories

Fixing angle 90 see section 9

Fixing angle 90 see section 9

Short-circuit protection
RMS sustained short-cct current
Overload/short-circuit indicator
Safety
Electrical isolation primary/
secondary
Protective class
(IEC 536; VDE 0106 P1)
Discharge current

EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating
Mechanical specifications
Connections
Mains input L, N, PE
Output L+
Output M

7/8

Siemens KT 10.1 2002

SITOP power Standard 24 V


Three-phase
Output currents 10 to 40 A

30 A

40 A

6EP1 437-2BA00

6EP1 437-2BA10

Approx. 90 %
Approx.80 W

Approx. 90 %
Approx.107 W

< 1 % Vout
4%, +2 % Vout

< 1 % Vout
4%, +2 % Vout

< 3ms
< 3ms

< 3ms
< 3ms

Yes, acc. to EN 60950


31.5 to 39 A typ.

Yes, acc. to EN 60950


42 to 52 A typ.

Electronic interruption, automatic


restart
< 42 A

Electronic interruption, automatic


restart
< 54 A

Yes, SELV output voltage Vout


acc. to EN 60950
Class I

Yes, SELV output voltage Vout


acc. to EN 60950
Class I

< 0.78 mA (550 V/60 Hz)

< 0.78 mA (550 V/60 Hz)

Yes; CB scheme
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

Yes; CB scheme
Yes
Yes, UL/cUL listed (UL 508,
CSA 22.2), File E143289

IP 20

IP 20

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2,
EN 61000-4-2, -3, -4, -5

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2,
EN 61000-4-2, -3, -4, -5

0 to +55 C with natural convection

0 to +55 C with natural convection

25 to +85 C

25 to +85 C

Climate category 3K3


acc. to EN 60721

Climate category 3K3


acc. to EN 60721

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm
2 screw-type terminals for
0.33 to 10 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
1 screw-type terminal for
0.33 to 10 mm
2 screw-type terminals for
0.33 to 10 mm

280 x 180 x 92
320 x 280

280 x 180 x 92
320 x 280

3.6 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

3.6 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Fixing angle 90 see section 9

Fixing angle 90 see section 9

Siemens KT 10.1 2002

7/9

SITOP power Standard 24 V


Three-phase
Notes

7/10

Siemens KT 10.1 2002

Uninterruptible
power supplies

SITOP power
Standard 24 V
Uninterruptible
power supplies

8/2

DC UPS module 15 A

8/6

DC UPS module 40 A

8/10

Battery module 2.5 Ah

8/11

Battery module 3.2 Ah

8/12

Battery module 7 Ah

8/13

Battery module 12 Ah

8/14

DC UPS Software

Siemens KT 10.1 2002

8/1

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 15 A

SITOP power Standard 24 V

Application
Long power outages can be
buffered with absolutely no
interruption by combining the
DC UPS module with at least
one 24 V battery module and
a SITOP power supply.

This combination is used for


example in machine tool construction, in the textiles industry and with all types of
production lines and filling
plants. The frequently occurring negative results of supply
interruptions can thus be
avoided.

Uninterruptible power supply 24 V/15 A


and battery module 24 V/3.2 Ah

Features
Compact design

7
7

24 V DC input voltage
(supplied by SITOP power
with at least 5 A rated current)

360 W rated output power

High efficiency of approx.


96 %

Absolutely uninterrupted
buffering of power outages

Battery is immediately
placed into circuit as soon
as the load voltage or the
voltage between the L+/M
terminals of the

8/2

Siemens KT 10.1 2002

DC UPS module drops


below the set value of the
connected threshold
(18 to 26 V).
7

Buffer time can be set between 5 and 315 s using the


DIP switch or forced interruption by exhaustive discharge protection.
For increased load current
demand (e. g. turning on of
incandescent lamps,
switching contactors with
DC economy winding, DC
motors, DC/DC converters,

electronic modules with


high input capacitance)
high, electronically limited
peak currents are supplied
automatically.
7

After a power outage the


battery module is automatically electronically disconnected from the loads and
rapidly recharged at a constant current of 0.7 A (V/I
characteristic with 27 V
end-of-charge voltage)

Exhaustive discharge protection

ON/OFF control circuit

Signaling
Green LED/yellow LED
and floating changeover
contact for AC/battery
operation
Red LED and floating
changeover contact for
buffer readiness (LED off)/
alarm (LED on)

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 15 A

Available battery modules and mains buffering times


Load current

Battery module 2.5 Ah


(6EP1935-6MD31)

Battery module 3.2 Ah


(6EP1935-6MD11)

Battery module 7 Ah
(6EP1935-6ME21)

Battery module 12 Ah
(6EP1935-6MF01)

6h

10 h

1A

2h

2.5 h

2A

45 min

45 min

2.5 h

4A

20 min

20 min

45 min

6A

13 min

10 min

30 min

1h

8A

9 min

4 min

20 min

40 min

10 A

7 min

1.5 min

15 min

30 min

1 min

4h
2.5 h

12 A

5.5 min

10 min

25 min

14 A

4.5 min

50 s

8 min

20 min

16 A

4 min

40 s

6 min

15 min

20 A

2 min

11 min

Note:
The mains buffering times were calculated on the basis of the discharge time of a fully loaded battery module until the battery voltage
dropped to 21 V; ambient temperature of 25 C

Basic connection diagram


DC UPS Module 15
DC

Battery module
X1.5 + Bat

DC
X1.6 - Bat

L+

X1.1

L-

X1.2

X1.3 L+

SITOP
power

Load
X1.4 LX2.1
X2.2
X2.3
X2.4
X2.5
X2.6
X2.7

Monitoring

Bat
24V DC o.k.
Alarm
Backup readiness

X2.8 ON/OFF
X2.9
24 V DC o.k. Alarm
(green)
(red)

Bat
(yellow)

Controls

DIP switch to
preselect
buffering time

Connection End-of-charge
threshold voltage

Siemens KT 10.1 2002

8/3

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 15 A
DC UPS module 15 A

Technical specifications
DC UPS module 15 A
Order No.

6EP1 931-2EC01
6EP1 931-2EC11 (with RS 232 interface)

Input L+/M with AC operation


Rated voltage Vin rated 1)

Stabilized direct voltage


24 V DC

Voltage range
Threshold for battery to connect

22 to 27.5 V DC
22.5 V DC 0.1 V (default setting),
settable between 18 and 26 V
15 A + approx. 1 A for charging the battery

Rated current Iin rated


Mains buffering
Mains buffering
On/Off control circuit
Buffer time

Output L+/M with AC operation


Rated voltage Vout rated
Voltage range
Output current
Dyn. V/I in case of short-circuit
Dyn. V/I in case of overload
Output L+/M with battery operation
Rated voltage Vout rated
Voltage range
Output current
Dyn. V/I in case of short-circuit
Dyn. V/I in case of overload
Output +bat/-bat with normal operation
End-of-charge voltage
Charging current

Settable
Depending on the connected battery (see table on page 8/3)
External NO contact (rated at max. 15 V DC/max. 10 mA). When control circuit is interrupted, the
battery is disconnected from output L+ and thus mains buffering is interrupted.
Selectable with DIP-switch: max. buffer time until forced interruption by exhaustive discharge protection (at approx. 18.5 V) or limited buffer time between 5 and 315s (settable in increments of
10s)
24 V DC (SITOP power output voltage)
Input voltage less approx. 0.5 V DC
0 to 15 A
By automatic connection of the battery approx. 30 A for approx. 2 ms, then electronic interruption
of the battery with automatic restart attempts (approx. 20 s between the attempts)
According to integrated 20 A line-side fuse type FKS (20 A for 150 ms up to 5 s), as long as the
power supply provides this excess current
24 V DC (from battery module)
27 V DC (no load) down to approx. 22 V (rated current) down to approx. 18.5 V (turn-off threshold
for exhaustive discharge protection)
0 to 15 A (continuously permissible)
Battery short-circuit current electronically limited to approx. 30 A, electronic interruption after
approx. 2 ms with automatic restart attempts (approx. 20 s between the attempts)
According to 15 A battery fuse type FKS
V/I charging characteristic
27.0 V DC 0.1 V (default setting),
settable between 26.6 and 29.2 V
Approx. 0.7 A (default setting)
settable between 0.3 and 0.7 A
(charging with closed and open On/Off circuit)

1) All 24 V DC SITOP power supplies with at least 5 A rated current may be used as supply units without restrictions.

8/4

Siemens KT 10.1 2002

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 15 A
Technical specifications (continued)
DC UPS module 15 A
Order No.
Efficiency/power loss
at Vout rated, Iout rated approx.
for battery operation approx.
Displays/status signals 2)
Normal operation
Battery operation (battery supplying load
alone or in addition to PS in case of overload)
Alarm (no buffer readiness or warning when
battery voltage drops below 20.4 V)

RS 232 interface
Safety
Electrical isolation primary/secondary
Protective class
Techn. Inspectorate type testing/CE marking
UL/cUL (CSA) approval
Protection and monitoring
Exhaustive discharge protection
Short-circuit protection
Overload protection
Open-circuit monitoring of battery circuit
Battery service life monitoring
Degree of protection
(EN 60529; VDE 0470 Part 1)
EMC
Interference emission
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage temperature range
Humidity rating

6EP1 931-2EC01
6EP1 931-2EC11(with RS 232 interface)
97 %/7.5 W with charged battery and 96 %/11 W with discharged battery
96.5 %/8.5 W
Green LED and signaling contact O.K./Bat.
(floating CO contact) set to O.K. 1)
Yellow LED and signaling contact O.K./Bat.
(floating CO contact) set to Bat. (= normal position)
Red LED and signaling contact Alarm (floating CO contact) set to Alarm (= normal position)
at Vout < 20.4 V with battery operation, interruption by exhaustive discharge protection, reversed
battery connections, open On/Off circuit, battery circuit not closed or opened during operation as
well as interruption in battery operation caused by overload, short-circuit or elapsing of buffer
time set via the DIP-switch.
only for 6EP1 931-2EC11:
serial status signal output, further processing with DC UPS software (see page 8/14)
No
Class III (ext. circuit, power supply: SELV voltage acc. to EN 60950)
Yes/Yes
Yes, UL/cUL listed (UL 508, CSA 22.2), File E143289
Automatic interruption when battery voltage drops below 18.5 V,
Battery short-circuit current electronically limited to approx. 30 A, electronic interruption after
approx. 2 ms with automatic restart attempts
Accessible 20 A line-side fuse type FKS (vehicle flat fuse with blade contacts) and battery fuse
Alarm signal if battery circuit is not closed or opened during operation (checked every 20 s)
Alarm signal at approx. 1/3 Hz (checked every 4 h)
IP 20

EN 50081-1, EN 55022 Class B


EN 50082-2
0 to +60 C with natural convection
40 to +70 C
3K3 acc. to DIN 60721 (rel. humidity up to 75 % mean value, 95 % on 30 days/year;
no condensation)

Mechanical specifications
Connections
Input L+, M
Output L+, M
+ Bat./- Bat.
Control circuit and status signals
Dimensions (W x H x D) in mm
Weight
Mounting

2 screw-type terminals for 1 to 4 mm2 single-core/finely stranded


2 screw-type terminals for 1 to 4 mm2 single-core/finely stranded
2 screw-type terminals for 1 to 4 mm2 single-core/finely stranded
9 screw-type terminals for 0.5 to 2.5 mm2 single-core/finely stranded
75 x125 x approx. 125
Approx. 0.4 kg (0.45 kg)
Snap-mounting on 35 mm DIN rail EN 50022-35 x 15/7.5

Accessories

Battery modules see pages 8/10 to 8/13

1)"O.K." means: voltage of power supply exceeds the threshold for battery to connect set on the DC UPS module 15 A.
2) permissible contact rating: 60 V DC/1 A or 30 V AC/1 A.

Siemens KT 10.1 2002

8/5

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 40 A
Application
Long power outages can be
buffered with absolutely no
interruption by combining the
DC UPS module with at least
one 24 V battery module and
a SITOP power supply.

This combination is used for


example in machine tool construction, in the textiles industry and with all types of
production lines and filling
plants. The frequently occurring negative results of supply
interruptions can thus be
avoided.

Uninterruptible power supply 24 V/40 A


and battery module 24 V/7 Ah

Features
Very small mounting depth
of approx. 65 mm

24 V DC input voltage
supplied by SITOP power:
10 A
(6EP1334-2AA00,
6EP1334-2BA00 or
6EP1434-2BA00)
20 A
(6EP1336-2BA00,
6EP1436-2BA00 or
6EP1436-3BA00)
30 A
(6EP1437-2BA00)
40 A
(6EP1437-2BA10 or
6EP1437-3BA00)

480 W rated output power


with one battery module,
960 W with two battery
modules

Extremely high efficiency of


approx. 99 % thanks to the
patented circuit principle

Absolutely uninterrupted
buffering of power outages

Battery is immediately
placed into circuit as soon
as the load voltage or the
voltage between the L+/M
terminals of the DC UPS
module drops below the set
value of 22.5 V DC.

The load voltage drops to a


minimum of 22 V DC for
max. 1 ms.
7

8/6

Siemens KT 10.1 2002

For increased load current


demand (e. g. turning on of
incandescent lamps,
switching contactors with
DC economy winding, DC
motors, DC/DC converters,
electronic modules with
high input capacitance),
high, electronically limited
peak currents are supplied
automatically (120 A for approx. 12 ms to 40 A for several minutes)
After a power outage, the
battery module

is automatically electronically disconnected from the


loads and rapidly
recharged at a constant
current of 2 A (V/I characteristic with 27.3 V end-ofcharge voltage)
7

Exhaustive discharge protection

ON/OFF control circuit

Signaling
Green LED/yellow LED
and floating changeover
contact for AC/battery
operation
Red LED and floating
changeover contact for
buffer readiness (LED off)/
alarm (LED on)

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 40 A
Voltage curve between the
terminals L+/M of the DC UPS
module when one 24 V/7 Ah
battery module is connected
in dependence on time and
load current.
Parameters:
load current 20 A/10 A/5 A/
2.5 A/1.3 A;
two battery modules 24 V/
7Ah:
load current 40 A/20 A/10 A/
5 A/2.5 A

voltage
L+/M in V
28.0
26.0
24.0
22.0
20.0
18.0
16.0

01 2

4 6 8 10

20

min

40

4 6 8 10

20

40

Battery module 24 V/7 Ah, discharge curves at 20 C

Siemens KT 10.1 2002

8/7

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 40 A
DC UPS module 40 A

Technical specifications
DC UPS module 40 A
Order No.

6EP1 931-2FC01

Input L+/M with AC operation


Rated voltage Vin rated 1)

Stabilized direct voltage


24 V DC

Voltage range
Overvoltage strength
Mains buffering at Iout rated
Rated current Iin rated

23.5 to 26 V DC (< 22.5 V: battery operation)


VDE 0160 A1 (April 1989), limit curve B2 (2 x Vrated, 0.4 ms)
Depending on the connected battery (see discharge curves on page 8/7 and table on page 8/3)
40 A

Output L+/M with AC operation


Rated voltage Vout rated
Voltage range
Output current w. battery discharged/charged

24 V DC (SITOP power output voltage)


23.5 to 26 V DC
0 to 37 A (max. 3 A required for charging the battery)/0 to 40 A

Output L+/M with battery operation


Rated voltage Vout rated
Voltage range
Output current with one battery module
Output current with two battery modules
Dyn. V/I with short-circuit in operation, typ.

24 V DC (from battery module)


27.3 V DC (no load) down to approx. 25 V DC (rated current) down to approx. 18.5 V DC
(turn-off threshold for exhaustive discharge protection)
0 to 25 A
0 to 40 A
120 A for approx. 12 ms

Output +bat/-bat with AC operation


End-of-charge voltage
Charging current

V/I charging characteristic


27.3 V 0.3 V
0 to 2.5 A (2 A typ.)

Efficiency/power loss
at Vout rated, Iout rated and with charged battery
for battery operation

Approx. 99 %/approx. 7 W
Approx. 97 %/approx. 30 W

Protection and monitoring


Exhaustive discharge protection
Short-circuit protection

Automatic interruption when battery voltage drops below 18.5 V,


Temperature monitoring of circuit-breaker, electronic interruption with automatic restart

Displays/status signals
On/Off (battery interruption)
AC operation
Battery operation (battery supplying load
alone or in addition to PS in case of overload)
Alarm (no buffer readiness or warning when
battery voltage drops below 20.4 V)

External NO contact (contact rating 12 V DC/5 mA)


Green LED + AC/Bat. signal (floating changeover contact AC/Bat. set to AC) 2)
Yellow LED + AC/Bat. signal (floating changeover contact AC/Bat. set to Bat.)2)
Red LED + Alarm-Signal (floating changeover contact Alarm) 2)

1) The following supplies are permissible: single-phase SITOP power 10 A (Order No. 6EP1334-2AA00 and 6EP1334-2BA00), SITOP power 20 A
(Order No. 6EP1336-2BA00) and three-phase SITOP power 10 A to 40 A (Order No. 6EP1434-2BA00, 6EP1436-2BA00, 6EP1436-3BA00,
6EP1437-2BA00, 6EP1437-2BA10 and 6EP1437-3BA00) if their output voltage is set between 25.0 and 25.5 V DC. After power recovery, the loads
are supplied for approx. 3 to 15 seconds from the battery, then the power supply resumes its load supply function. Both at power failure and power
recovery absolutely uninterruptible power supply of the loads is assured. Not permissible are single-phase SITOP power supplies up to 10 A (Order
No. 6EP13..-1...)
2) permissible contact rating: 60 V DC/1 A

8/8

Siemens KT 10.1 2002

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS module 40 A
Technical specifications (continued)
DC UPS module 40 A
Order No.
Safety
Electrical isolation primary/secondary
Protective class (IEC 536; VDE 0106 P1)
Technical Inspectorate type testing/
CE marking
UL/cUL (CSA) approval 1)
Degree of protection
(EN 60529; VDE 0470 Part 1)

6EP1 931-2FC01
No
Class III
Yes/Yes
Yes, UL/cUL recognized (UL 1950), File E172952
IP 20

EMC
Interference emission
Interference immunity

EN 50081-1, EN 55022 Class B


EN 50082-2, IEC 801-2, -3, -4, -5

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Humidity rating

0 to +60 C with natural convection


25 to +85 C
F acc. to DIN 40040: rel. humidity up to 75 % mean value, 95 % on 30 days/year; no condensation

Mechanical specifications
Terminals input 2) L+, M
Terminals output 2) L+, M
Terminals + Bat./- Bat.
Terminals signals On/Off, AC/Bat., Alarm,
Shield S
Dimensions (W x H x D) in mm
Weight, approx.
Mounting
Accessories

2 screw-type terminals for 0.5 to 10 mm2 single-core/finely stranded


2 screw-type terminals for 0.5 to 10 mm2 single-core/finely stranded
2 screw-type terminals for 0.5 to 10 mm2 single-core/finely stranded
9 screw-type terminals for 0.5 to 2.5 mm2 single-core/finely stranded
220 x130 x approx. 65
1.2 kg
Snap-mounting on 35 mm DIN rail EN 50022-35 x 15/7.5
Fixing angle see section 9
Battery modules see pages 8/12 to 8/13

1) Approval only in combination with battery module 7 Ah (6EP1935-6ME01); UL approval for combinations with battery module 7 Ah (6EP1935-6ME21)
and battery module 12 Ah (6EP1935-6MF01) available soon.
2) Both L+ and M terminals are electrically connected in the unit. Therefore, no distinction must be made between input/output terminals.

Siemens KT 10.1 2002

8/9

SITOP power Standard 24 V


Uninterruptible power supplies
Battery module 2.5 Ah
Application/features
High temperature battery
for DC UPS module 15 A

Battery module 2.5 Ah

Contains two maintenance-free lead accumulators connected in series

Completely wired with battery fuse holder and connection terminals

Low self-discharge rate of approx. 3 %


each month (at +20 C)

Technical specifications
Battery module 2.5 Ah
Order No.

6EP1 935-6MD31

Battery type, charging current/voltage


Recommended end-of-charge voltage
(standby use)
at +25 C battery temperature
at other battery temperatures

Maintenance-free lead accumulators 1)

Recommended charging current

27.7 V DC
29.0 V for 10 C; 28.6 V for 0 C; 28.3 V for +10 C; 27.9 V for +20 C; 27.5 V for +30 C;
27.2 V for +40 C; 26.8 V for +50 C; 26.4 V for +60 C
Approx. 3 A

Protection
Short-circuit protection
Battery protection

Battery fuse 15 A/32 V (FKS flat fuse + holder)


Valve controlled

Safety
Protective class (IEC 536; VDE 0106 P1)
UL/cUL (CSA) approval
Degree of protection (EN 60529;
VDE 0470 Part 1)
Operating specifications
Ambient temperature range
Transportation and storage temperature range
Self-discharge rate
Mechanical specifications
Connection
Provided accessories
Dimensions (W x H x D) in mm
Weight
Mounting

Class III
Yes, UL/cUL recognized (UL 1778, CSA 22.2 No 107.1-95), File E219627
IP 00

40 to +60 C with natural convection


40 to +60 C
Approx. 3 % each month at 20 C battery temperature (increases with rising temperature)
One screw-type terminal each for 0.08 to 2.5 mm2 for +Bat. and -Bat.
Accessories pack with FKS 15 A fuse
Approx. 265 x 151 x 91
Approx. 3.8 kg
Snap-mounting on 35 mm DIN rail EN 50 022-35 x 15/7.5 or keyhole mounting for hooking onto
M4 screws

1) Specifications as in VDE 0510 and relevant national regulations must be observed when storing, mounting or operating the lead accumulators. Sufficient
ventilation for the battery must be provided. Potential ignition sources must be at a minimum distance of 50 cm.

8/10

Siemens KT 10.1 2002

SITOP power Standard 24 V


Uninterruptible power supplies
Battery module 3.2 Ah
Application/features
Battery module for DC UPS module 15 A

Battery module 3.2 Ah

7
7

Contains two sealed maintenance-free


lead accumulators from one batch connected in series

Including battery fuse holder and connection terminals

Low self-discharge rate of approx. 3 %


each month (at +20 C)

Technical specifications
Battery module 3.2 Ah
Order No.

6EP1 935-6MD11

Battery type, charging current/voltage


Recommended end-of-charge voltage
(stand-by use)
at +25 C battery temperature
at other battery temperatures

Sealed maintenance-free lead accumulators 1)

Recommended charging current

27.0 V DC
27.8 V for +10 C; 27.3 V for +20 C; 27.0 V for +25 C; 26.8 V for +30 C; 26.7 V for +35 C;
26.6 V for +40 C
0.7 A

Protection
Short-circuit protection
Battery protection

Battery fuse 15 A/32 V (FKS flat fuse + holder)


Valve controlled

Safety
Protective class (IEC 536; VDE 0106 P1)
UL/cUL (CSA) approval
Degree of protection
(EN 60529; VDE 0470 Part 1)

Class III
Yes, UL/cUL recognized (UL 1778, CSA 22.2 No 107.1-95), File E219627
IP 00

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Self-discharge rate

+5 to +40 C with natural convection


20 to +50 C
Approx. 3 % each month at 20 C battery temperature (increases with rising temperature)

Mechanical specifications
Connection
Provided accessories
Dimensions (W x H x D) in mm
Weight
Mounting

One screw-type terminal each for 0.08 to 2.5 mm2 for +Bat. and -Bat.
Accessories pack with FK2 15 A fuse
190 x151 x approx. 82
Approx. 3.2 kg
Snap-mounting on 35 mm DIN rail EN 50022-35 x 15/7.5

1) Specifications as in VDE 0510 and relevant national regulations must be observed when storing, mounting or operating the lead accumulators. Sufficient
ventilation for the battery must be provided. Potential ignition sources must be at a minimum distance of 50 cm.
Siemens KT 10.1 2002

8/11

SITOP power Standard 24 V


Uninterruptible power supplies
Battery module 7 Ah
Application/features
Battery for DC UPS module 15 A
and DC UPS module 40 A

Battery module 7 Ah

Contains two sealed maintenance-free


lead accumulators from one batch connected in series

Completely wired with battery fuse holder and connection terminals

Accessories pack with spare FKS 15


and 25 A fuses

Low self-discharge rate of approx. 3 %


each month (at +20 C)

Technical specifications
Battery module 7 Ah
Order No.

6EP1 935-6ME21

Battery type, charging current/voltage


End-of-charge voltage
at +25 C battery temperature
at other battery temperatures

Sealed maintenance-free lead accumulators 1)

Recommended charging current

27.0 V DC
27.8 V DC for +10 C; 27.3 V DC for +20 C; 26.8 V DC for +30 C; 26.7 V DC for +35 C;
26.6 V DC for +40 C
max. 1.7 A

Protection
Short-circuit protection
Battery protection

Battery fuse 15 A/32 V (FKS flat fuse + holder)


Valve controlled

Safety
Protective class (IEC 536; VDE 0106 P1)
UL/cUL (CSA) approval
Degree of protection
(EN 60529; VDE 0470 Part 1)

Class III
Yes, UL/cUL recognized (UL 1778, CSA 22.2 No 107.1-95), File E219627
IP 00

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Self-discharge rate

+5 to +40 C
20 to +50 C
Approx. 3 % each month at 20 C battery temperature

Mechanical specifications
Connection
Provided accessories
Dimensions (W x H x D) in mm
Weight
Mounting

One screw-type terminal each for 0.08 to 4 mm2 for +Bat. and -Bat.
Accessories pack with FKS 15 and 25 A fuses
Approx. 186 x 168 x 121
Approx. 6.0 kg
Can be screwed onto level surface (keyhole mounting for hooking onto M4 screw)

1) Specifications as in VDE 0510 and relevant national regulations must be observed when storing, mounting or operating the lead accumulators. Sufficient
ventilation for the battery must be provided. Potential ignition sources must be at a minimum distance of 50 cm.

8/12

Siemens KT 10.1 2002

SITOP power Standard 24 V


Uninterruptible power supplies
Battery module 12 Ah
Application/features
Battery module for DC UPS module 15 A
and DC UPS module 40 A

Battery module 12 Ah

Contains two sealed maintenance-free


lead accumulators from one batch connected in series

Completely wired with battery fuse holder and connection terminals

Accessories pack with spare FKS 15


and 25 A fuses

Low self-discharge rate of approx. 3 %


each month (at +20 C)

Technical specifications
Battery module 12 Ah
Order No.

6EP1 935-6MF01

Battery type, charging current/voltage


End-of-charge voltage
at +25 C battery temperature
at other battery temperatures

Sealed maintenance-free lead accumulators 1)

Recommended charging current

27.0 V DC
27.8 V DC for +10 C; 27.3 V DC for +20 C; 26.8 V DC for +30 C; 26.7 V DC for +35 C;
26.6 V DC for +40 C
max. 3 A

Protection
Short-circuit protection
Battery protection

Battery fuse 15 A/32 V (FKS flat fuse + holder)


Valve controlled

Safety
Protective class (IEC 536; VDE 0106 P1)
UL/cUL (CSA) approval
Degree of protection
(EN 60529; VDE 0470 Part 1)

Class III
Yes, UL/cUL recognized (UL 1778, CSA 22.2 No 107.1-95), File E219627
IP 00

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Self-discharge rate

+5 to +40 C
20 to +50 C
Approx. 3 % each month at 20 C battery temperature

Mechanical specifications
Connection
Provided accessories
Dimensions (W x H x D) in mm
Weight
Mounting

One screw-type terminal each for 0.08 to 4 mm2 for +Bat. and -Bat.
Accessories pack with spare FKS 15 and 25 A fuses
Approx. 253 x 118 x 121
Approx. 9.0 kg
Can be screwed onto level surface (keyhole mounting for hooking onto M4 screw)

1) Specifications as in VDE 0510 and relevant national regulations must be observed when storing, mounting or operating the lead accumulators. Sufficient
ventilation for the battery must be provided. Potential ignition sources must be at a minimum distance of 50 cm.
Siemens KT 10.1 2002

8/13

SITOP power Standard 24 V


Uninterruptible power supplies
DC UPS Software

DC UPS Software
With the SITOP DC UPS Software, the user has access to a convenient software tool with which the signals sent from the DC
UPS module 15 A with an RS 232 interface (6EP1931-2EC11)
can be further processed. In monitoring mode the state of the
DC UPS module is visualized on the PC. Furthermore it is possible to define a certain reaction to each operating status of the
DC UPS module providing for very flexible integration into various applications.
The software runs under the operating systems Win95, Win98,
WinME, WinNT 4.0 and Win2000. It can be downloaded free of
charge from the SITOP homepage www.siemens.de/sitop.

Monitoring window of the SITOP DC UPS Software

Configuring window of the SITOP DC UPS Software.


Reactions to each operating status of the DC UPS module can be configured here.

8/14

Siemens KT 10.1 2002

SITOP power
Standard 24 V
Accessories

9/2

Diagnosis module SITOP select

9/4

Fixing angle

9/5

Mounting adapter for S7 rail and


power connector PS-CPU

9/5

Connector seal IP 65

9/5

Circular input connector and AS


interface Pg connection module

Siemens KT 10.1 2002

9/1

SITOP power Standard 24 V


Accessories
Diagnosis module SITOP select

SITOP power Standard 24 V

SITOP select

Application

The diagnosis module in combination with 24 V power supplies serves for distributing
the load current on several arms of the circuit and for monitoring the individual component currents. Malfunctions in the individual arms caused by overload or a short-circuit
are detected and interrupted; other load current paths are not affected. This ensures
quick diagnosis of malfunctions, downtimes are minimized.

Technical specifications
Type

Module 4 x 10 A

Order No.

6EP1 961-2BA00

Input
Rated voltage Vin rated

Direct voltage
24 V DC

Voltage range
Overvoltage strength

22 to 30 V
35 V; 100ms

Output
Rated voltage Vin rated
Total tolerance/residual ripple
Number of output channels
Rated current Iout rated up to +60 C
Setting range
Parallel connection of several channels

Direct voltage
Vin 0.5 V
Depending on the input voltage
4
10 A per channel
2 to 10 A per channel
Not permissible

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

Approx. 97 %
Approx. 30 W

Interruption characteristic for each channel


Excess current
Current limitation
Immediate interruption
Reset

I = 1.0...1.3 x set value, interruption after approx. 5 s


I = 1.3 x set value, interruption after approx. 50 ...100 ms
I > set value and Vin <20 V
With switch on module

Protection and monitoring


Power protection
Operation indicator
Signaling contact
Safety
Protective class (IEC 536; VDE 0106 P1)
Degree of protection (EN 60529; VDE 0470
Part 1)
Technical Inspectorate type testing
CE marking
UL/cUL (CSA) approval

FK2 flat fuse 15 A per channel


Two color LED for each channel
green: output through connected
red: output interrupted because of overload/short-circuit
Overall signaling contact (NO contact)
Class III
IP 20
Yes
Yes
available soon

EMC
Interference emission
Interference immunity

EN 50081-2, EN 55022 Class B


EN 50082-2

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Humidity rating

0 to +60 C with natural convection


25 to +85 C
Climate category 3K3 acc. to EN 60721

9/2

Siemens KT 10.1 2002

SITOP power Standard 24 V


Accessories
Diagnosis module SITOP select
Technical specifications (continued)
Type

Module 4 x 10 A

Order No.

6EP1 961-2BA00

Mechanical specifications
Connections
Input +24 V
Input 0 V
Output 1 to 4
Signaling contacts
Dimensions (W x H x D) in mm
Weight
Mounting

2 screw-type terminals for 0.33 to 10 mm2


2 screw-type terminals for 0.22 to 4 mm2
1 screw-type terminal each for 0.22 to 4 mm2
2 screw-type terminals for 0.22 to 4 mm2
72 x 90 x 90
0.4 kg
Snap-mounting on DIN rail EN 50022-35 x 15/7.5

Circuit principle
Power supply, e.g. SITOP power
+

~
=

24 V

SITOP

+ 24 V

select

Reset

13

14

0V

Floating
signaling
contact

Load 1

Load 2

Load 3

Load 4

G_KT01_en_00063a

Control logics

Interruption characteristic (typical)


G_KT01_en_00062

100.0

Release time

s
10.0

5.0 s

1.0
0.10 s

0.1
0.0

20

40

60

80

100

Load current

120 % 140
rated

I rated settable between 2 A and 10 A.


Current demand behavior for each output circuit
from 0 A up to set value (I/I rated = 100 %)
no interruption
from set value up to 130 %
interruption after approx. 5 s
above 130 % of set value
current limitation to 130 % for 50 ... 100 ms,
then interruption
above set value with simultaneous drop from 24 V below 20 V
immediate interruption

Siemens KT 10.1 2002

9/3

SITOP power Standard 24 V


Accessories

Fixing angle 90

Application

Fixing angle 90

Combining a SITOP power supply with a fixing angle 90 provides for minimum space requirement on the rear panel of the
cabinet (the width of the power supply is then the depth and
vice versa). The fixing angle is suitable for cabinets with a
depth of at least 240 mm, 320 mm respectively.

Technical specifications

Order No.
Mechanical specifications
Dimensions (W x H x D) in mm
Sheet thickness
Integrated mounting rail
Weight
Mounting

Provided accessories
suitable for
SITOP 24 V/3.5 A
SITOP 24 V/5 A
SITOP 24 V/10 A
SITOP DC UPS module
SITOP 24 V/10 A
SITOP 24 V/20 A
SITOP 24 V/20 A
SITOP 24 V/20 A
SITOP 24 V/20 A
SITOP 24 V/30 A
SITOP 24 V/40 A
SITOP 24 V/40 A

9/4

Siemens KT 10.1 2002

Fixing angle 90

Fixing angle 90

6EP1 971-1AA01

6EP1 971-2BA00

50 x 159 x 236
2 mm
DIN rail EN 50022-35x7.5
0.9 kg
Can be screwed onto level surface (keyhole mounting for hooking onto M5 screws, hole
spacing 147.5 mm vertically)

100 x 150 x 320


1.5 mm
DIN rail EN 50022-35x15
0.9 kg
Can be screwed onto level surface (keyhole mounting for hooking onto M6 screws, hole
spacing 90 mm vertically
50 mm horizontally)
4 x M6 combination screw

2 x M5 combination screw and 2


x M5 self-tapping screw
6EP1 332-1SH31 (see page 3/2)
6EP1 333-1AL11 (see page 4/3)
6EP1 334-1AL11 (see page 5/3)
6EP1 931-2FC01 (see page 8/8)

6EP1 434-2BA00 (see page 7/6)


6EP1 336-2BA00 (see page 6/2)
6EP1 536-2AA00 (see page 6/2)
6EP1 436-2BA00 (see page 7/6)
6EP1 436-3BA00 (see page 7/2)
6EP1 437-2BA00 (see page 7/7)
6EP1 437-2BA10 (see page 7/7)
6EP1 437-3BA00 (see page 7/2)

SITOP power Standard 24 V


Accessories
Mounting adapter for S7 rail and PS CPU power connector
Power supplies SITOP power
single-phase 24 V/2 A
(6ES7307-1BA00-0AA0,
6ES7305-1BA80-0AA0),
24 V/5 A (6ES7307-1EA000AA0, 6ES7307-1EA80-0AA0)
and 24 V/10 A (6ES73071KA00-0AA0) are special
mechanical versions for
SIMATIC S7-300.

They can be snap-mounted


onto an S7 rail and easily connected to the CPU with the
provided power connector.
Power supplies of the same
design provided with a
mounting adapter for DIN rail
EN 50022-35x15 mounting
instead of a power connector
are also available under the
following order numbers:

6EP1331-1SL11 (24 V/2 A),


6EP1333-1SL11 (24 V/5 A)
and 6EP1334-1SL11
(24 V/10 A).

it can be flush mounted into


the modular assembly with no
special wiring. If the power
supply is operated outside
the ET 200X system as an
independent power supply
with the degree of protection
IP 65,

the following connector seals


are required for sealing the
integrated connectors:

Both the power connector


and the mounting adapter are
also available separately as
accessories.
Order No.

PS CPU power connector


Mounting adapter for DIN rail EN
50022-35x15

6ES7 390-7BA00-0AA0
6ES7 390-6BA00-0AA0

IP 65 connector seals
The design and functionality
of the SITOP power supply
single-phase 24 V/10 A in IP
65 (6EP1334-2CA00) are perfectly matched to the distributed arrangement ET 200X.
With its integrated connectors,

Order No.
Connector seal, IP 65, for
power supply
6EP1 334-2CA00

6EP1 971-2CA00

Circular input connector and AS interface Pg connection module


The ASi power supply 30 V/
2.4 A in IP 65 (6EP16321AL01) requires a 6-pin circular connector with female
insert to connect the input
side.

The ASi power supply is connected to the ASi network via


the Pg connection module.

Order No.
6-pin circular input connector
with female insert
AS interface Pg connection
module

6ES5 760-2CA11
3RG9 220-0AA00

Siemens KT 10.1 2002

9/5

SITOP power Standard 24 V


Accessories
Notes

9/6

Siemens KT 10.1 2002

10/2

SITOP power flexi 120 W

10/4

SITOP power dual15 V

SITOP power
Alternative
voltages

Siemens KT 10.1 2002

10/1

SITOP power
Alternative voltages
SITOP power flexi 120 W
Application

SITOP power

SITOP power flexi 120 W

This power supply, developed according to the latest standards, is suitable for
operation worldwide in every conceivable field of application requiring voltages other than 24 V DC; output voltage
settable between 3 and 52 V DC.

Technical specifications
Type

120 W

Order No.

6EP1 353-2BA00

Input
Rated voltage Vin rated

Single-phase AC
120/230 V AC Settable via jumper wire

Voltage range

93 to 132 V/187 to 264 V AC

Mains buffering at Pout = 120 W


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 10 ms at Vin = 93/187 V


50/60 Hz; 47 to 63 Hz
2.2/0.9 A
< 32 A

I2t
Integrated line-side fuse
Required circuit-breaker (IEC 898) in mains
supply cable

< 0.8 A2s


T 3.15 A/250 V (not accessible)
from 6 A, Characteristic C

Output
Output voltage Vout
Stat. total tolerance
Mains compensation
Load compensation
Sense-line connection

Stabilized, floating direct voltage


3 to 52 V DC
1%
Approx. 0.1 %
Approx. 0.2 %
Yes, max. voltage regulation 0.5 V per line

Residual ripple (modulation frequency:


approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Output voltage set
Operation indicator
Signaling
Power ON/OFF behavior

< 50 mVpp

Starting delay/voltage rise


Output current/power
Current limitation
Power limitation
Parallel connection for increased output

< 3 s/80 ms typ.


Current limitation in the range of Vout = 312 V and power limitation in the range of Vout = 12-52 V
max. 10 A
max. 120 W
Yes, 2 pieces

Efficiency
Efficiency at 24 V/5 A
Power loss at 24 V/5 A

Approx. 84 %
Approx. 23 W

Protection and monitoring


Output overvoltage protection
Current limitation
Power limitation
Overload/short-circuit indicator

Yes, acc. to EN 60 950


2 to 10 A, settable via potentiometer or analog control voltage signal of 0 to 2.5 V
Automatic, max.120 W
Red LED for current/power limitation

10/2

Siemens KT 10.1 2002

< 100 mVpp


via potentiometer or analog control voltage signal of 0 to 2.5 V
Green LED for output voltage O.K.
Power good via relay contact, current monitor signal
No overshoot of Vout (soft start)

SITOP power
Alternative voltages
SITOP power flexi 120 W
Technical specifications (continued)
Type

120 W

Order No.

6EP1 353-2BA00

Safety
Electrical isolation primary/secondary
Protective class (IEC 536; VDE 0106 P1)
Discharge current
Technical Inspectorate type test
CE marking
UL/cUL (CSA) approval
FM approval
Approved for use in marine vessels
Degree of protection
(EN 60529; VDE 0470 Part 1)

Yes, SELV output voltage Vout acc. to EN 60950 and EN 50178


Class I
< 3.5 mA
Yes
Yes
Yes, UL/cUL listed (UL 508, CSA 22.2), File E143289

IP 20

EMC
Interference emission
Line harmonics limitation
Interference immunity

EN 50081-1, EN 55022 Class B


EN 61000-3-2
EN 50082-2, EN 61000-4-2, -3, -4, -5, -6

Operating specifications
Ambient temperature range
Transportation and storage temperature range
Humidity rating

0 to +60 C with natural convection


25 to +85 C
Climate category 3K3 acc. to EN 60 721

Mechanical specifications
Connections
Mains input L, N, PE
Output L+
Output M
Status signals, control inputs

One screw-type terminal each for 0.5 to 2.5 mm2 single-core/finely stranded
1 screw-type terminal for 0.5 to 2.5 mm2
2 screw-type terminals for 0.5 to 2.5 mm2
1 screw-type terminal each for 0.14 to 1.5 mm2

Dimensions (W x H x D) in mm
Weight
Mounting

75 x 125 x 125
Approx. 0.9 kg
Snap-mounting on DIN rail EN 50022-35 x 15/7.5

Accessories

Siemens KT 10.1 2002

10/3

SITOP power
Alternative voltages
SITOP power dual 15 V
Application

SITOP power dual

This power supply developed according


to the latest standards is suitable for
operation worldwide in every conceivable field of application in electronic supply; output 2 15 V/3.5 A, in parallel and
in series connection possible.

Technical specifications
Type

2 15 V/3.5 A

Order No.

6EP1 353-0AA00

Input
Rated voltage Vin rated

Single-phase AC
120 - 230 V AC

Voltage range
Overvoltage strength
Mains buffering at Iout rated
Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

93 to 264 V AC
Surge voltage acc. to EN 61000-6-2 table 4
> 10/40 ms at Vin = 120/187 V
50/60 Hz; 47 to 63 Hz
1.9 - 1.15 A
< 30 A, 3 ms typ.

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898) in mains
supply cable

< 3 A2s
T 4 A (not accessible)
from 10 A, Characteristic C or from 16 A, Characteristic B

Output
Rated voltage Vout rated
Total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


2 x 15 V DC
2%
Approx. 0.2 %
Approx. 0.2 %

Residual ripple (modulation frequency:


approx. 50 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 50 mVpp (20 mVpp typ.)

Starting delay/voltage rise


Rated current I out rated
Current range
up to +45 C
up to +60 C
Parallel connection for increased output

<1s
2 x 3.5 A

< 150 mVpp (50 mVpp typ.)


14.5 to 17 V
Green LED (displayed total > 10 V)
Overshoot of Vout < 3 %

2 x 0 to 3.5 A
2 x 0 to 2.5 A
Yes

Efficiency
Efficiency at Vout rated , I out rated
Power loss at Vout rated , I our rated

> 80 %
< 27 W

Control
Dyn. load compensation (Iout: 10/90/10 %)
Settling time

Approx. 2 % Vout
2 ms

Protection and monitoring


Output overvoltage protection
Current limitation
Short-circuit protection
Overload/short-circuit indicator

Yes, acc. to EN 60950


Limitation starts < 4.9 A; interruption at < 6 A
Electronic interruption, automatic restart

10/4

Siemens KT 10.1 2002

SITOP power
Alternative voltages
SITOP power dual 15 V
Technical specifications (continued)
Type

2 15 V/3.5 A

Order No.

6EP1 353-0AA00

Safety
Electrical isolation primary/secondary
Protective class (IEC 536; VDE 0106 P1)
Discharge current
Technical Inspectorate type test
CE marking
UL/cUL (CSA) approval
FM approval
Approved for use in marine vessels
Degree of protection
(EN 60529; VDE 0470 Part 1)

Yes, SELV output voltage Vout acc. to EN 60950


Class I
< 3.5 mA

Yes
Yes, UL/cUL listed (UL 508, CSA 22.2), File E179336

IP 20

EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating

EN 50081-2, EN 55011 Class A

EN 50082-2
0 to +60 C with natural convection, derating from +45 C
40 to +70 C
5 to 95 %, no condensation

Mechanical specifications
Connections
Mains input L, N, PE
Output P15_1, GND1, GND2
Output P15_2

One screw-type terminal each for 0.5 to 2.5 mm2 single-core/finely stranded
1 screw-type terminal each for 0.5 to 2.5 mm2
2 screw-type terminals for 0.5 to 2.5 mm2

Dimensions (W x H x D) in mm
Weight
Mounting

75 x 125 x 125
Approx. 0.75 kg
Snap-mounting on DIN rail EN 50022-35 x 15/7.5

Accessories

Siemens KT 10.1 2002

10/5

SITOP power
Alternative voltages
Notes

10/6

Siemens KT 10.1 2002

11/2

Description

11/3

Specification sheet

SITOP power
Customized

Siemens KT 10.1 2002

11/1

SITOP power
Customized
SITOP power

Description
Our well-proven standard
power supplies can of course
not cover every special application. Does yours need a
voltage level other than 24 V?
Is a 19" or open-frame version
required? Do the ambient
conditions for your system go
beyond normal ranges? With
SITOP power, you have the
possibility of optimally realizing application-specific matters. The experience and
know-how of our development teams enable us to offer
you a tailor-made solution
based on the modular power
supply principle. Your specific requirements are met by
modifying existing units or
developing completely new
components on the basis of
pre-developed standard
components. Your advantages are obvious:
Adapting the power supply to
your application needs and
not vice versa
High flexibility for electric parameters
AC or DC input
Possibility of several output
voltages
High reliability by implementing standard components
Versatile design possibilities
Adaptable mechanical specifications

11/2

Siemens KT 10.1 2002

You benefit from the competence of industrial scale manufacturing, but decide on
maximum development reliability and quality. Other decisive criteria for the success of
your application on the market are:
High availability due to short
development cycles
Short period between development and start of the
batch due to a well-established introduction process
for production
Market-oriented pricing
At present, our customized
solutions are in operation in
many sectors of mechanical
engineering, automation,
vehicle electronics, equipment construction and industrial measurement, among
others. The examples on the
right show an extract from our
versatile spectrum.

19 power supplies with different output power for application in subracks

Our product range is open to


any application. If you are
interested and require further
information, please copy the
following page, fill in the
parameters of your specific
requirement and fax it to the
stated number. We will contact you without delay.
Open-frame power supply with 45 W output power and 3 outputs
(5 V, 15 V)

SITOP power
Customized
FAX reply
Specification sheet for customized power supplies
Recipient:

Sender:

SIEMENS AG
A&D SE PSBD
Wrzburger Strae 121
90766 Frth
Germany
FAX: +49 911 (-750) 750-9991

Company:

Phone:+49 911 (-750) 750-9990

City:

Department:
Name:

FAX:
Phone:
Application:
Electrical requirements:
Input voltage:

Vin:

Tolerance D Vin :

Frequency:

fin:

Tolerance D fin :

Mains buffering time:

Tin:

Output voltage:

Vout1:

Vout2:

Vout3:

Vout4:

Output current

Iout1:

Iout2:

Iout3:

Iout4:

Other:

Mechanical requirements:
Design/dimensions:
(attach drawing if necessary)

Enclosure:

Connections:

Other:

General requirements:
Efficiency:
Ambient temperature:
Standards:

Quantity/year:

Signaling:
EN 60950

UL

EN 50081-1/2

EN 50082-1/2

cUL (CSA)

Delivery:

Price expectations:
Remarks:

Siemens KT 10.1 2002

11/3

SITOP power
Customized
Notes

11/4

Siemens KT 10.1 2002

12/2

The IP 65 version

12/2

The IP 20 version

SITOP power
AS interface power
supplies

Note:
More AS interface power
supplies in catalog PD 20 2001.
Siemens KT 10.1 2002

12/1

SITOP power
AS interface power supplies
Single-phase ASi power supplies, stabilized
The IP 65 version

SITOP power

The IP 20 version

Technical specifications
Type

2.4 A

Order No.

6EP1 632-1AL01

6EP1 354-1AL01

Input
Rated input voltage Vin rated
Range switched by
Input voltage range
Overvoltage strength
Mains buffering at Iout rated
Rated line frequency, range
Rated input current Iin rated
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

Direct voltage
24 V DC

20.4 to 28.8 V DC
35 V DC for max. 500 ms
> 10ms

3.6 A
T 6.3 A (not accessible)
from 10 A, Characteristic C or
from 6 A, Characteristic D

Single-phase AC
120 - 230 V AC
Wide-range input
93 to 264 V AC/110 to 350 V DC
VDE 0160 limit curve W2
> 20 ms at 93/187 V
0/50/60 Hz; 47 to 63 Hz
2.2 - 1.2 A
T 6.3 A (not accessible)
from 16 A, Characteristic C or
from 8 A, Characteristic D

Output
Stabilized, floating direct voltage
Rated output voltage Vout rated
Total tolerance
Residual ripple
Spikes
Operation indicator
Rated output current Iout rated

Yes
30 V DC (AS interface)
29.5 to 31.6 V DC
< 300 mVpp
< 50 mVpp
Green LED
2.4 A DC

Yes
30 V DC
29.5 to 31.6 V DC
< 300 mVpp
< 50 mVpp
Green LED
7 A DC

Efficiency/power loss
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

> 81 %
< 17 W

> 85 %
< 37 W

Protection and monitoring


Output overvoltage protection
Current limitation
Short-circuit protection

from approx. 2.9 A


Const. current charact. approx. 2.9 A

Yes
from approx. 7.4 A
Const. current charact. approx. 7.4 A

Yes, SELV acc. to EN 60950


Class I
IP 65 1)
CE, UL (UL 508) File E179336,
CSA (CSA 22.2)

Yes, SELV acc. to EN 60950


Class I
IP 20
CE, UL/cUL (UL 508, CSA 22.2),
File E143289

EMC
Interference emission
Interference immunity

EN 50081-1, EN 55022 Class B


EN 50082-2

EN 50081-1, EN 55022 Class B


EN 50082-2

Operating specifications
Ambient temperature range
Transp. and stor. temperature range
Humidity rating

25 to +55 C
25 to +85 C
F acc. to DIN 40040

0 to +55 C
25 to +85 C
F acc. to DIN 40040

Mechanical specifications
Connections
Input
Output ASi +
Output ASi
Output Ground
Dimensions (W x H x D) in mm
Weight, approx.
Mounting

Circular connector 0.5 to 2.5 mm2 1) 2)


500 mm three-core cable AWG 14 1)
500 mm three-core cable AWG 14 1)
500 mm three-core cable AWG 14 1)
224 80 57
1.0 kg
Wall-mounting, any position

1 screw-type term. ea. for 0.5 to 2.5 mm2


3 screw-type term. for 0.5 to 2.5 mm2
3 screw-type term. for 0.5 to 2.5 mm2
2 screw-type term. for 0.5 to 2.5 mm2
200 125 135
1.8 kg
Snap-mounting on DIN rail EN
50022-35 x 15 mm and on S7 rail

Safety
Electrical isolation primary/secondary
Protective class (IEC 536)
Degree of protection (EN 60529)
Approvals

7A

6-pin circular input connector (6ES5 760


2CA11) and AS interface Pg connection
module (3RG9 220-0AA00) see section 9
1) On request with screw-type terminals to degree of protection IP 20.
2) The counterpart must be ordered separately (not included); see accessories

Accessories

12/2

Siemens KT 10.1 2002

72 mm series

LOGO!Power

13/2

5 V/3 A DC

13/2

12 V/1.9 A DC

13/2

15 V/1.85 A DC

13/3

24 V/1.3 A DC

13/3

48 V/0.65 A DC
126 mm series

13/6

5 V/6.3 A DC

13/6

12 V/4.5 A DC

13/6

15 V/4 A DC

13/7

24 V/2.5 A DC

13/7

48 V/1.25 A DC

Siemens KT 10.1 2002

13/1

LOGO!Power
72 mm series

LOGO!Power

LOGO!Power

Application

LOGO!Power supplies are primary switched-mode power supplies perfectly matched to the LOGO! logic modules in functionality and design. Their wide-range 85 V to 264 V AC input, their
RI level B and their facility for mounting in small distribution
boards make them universally suitable for every conceivable
field of application in the lower power region.

Technical specifications
Type

5 V/3 A

12 V/1.9 A

15 V/1.85 A

Order No.

6EP1 311-1SH01

6EP1 321-1SH01

6EP1 351-1SH01

Input

Single-phase AC

Single-phase AC

Single-phase AC

Rated voltage Vin rated

120 - 230 V AC
Wide-range input

120 - 230 V AC
Wide-range input

120 - 230 V AC
Wide-range input

Voltage range

85 to 264 V AC

85 to 264 V AC

85 to 264 V AC

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.23 - 0.13 A
< 15 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.34 - 0.18 A
< 15 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.41 - 0.22 A
< 15 A

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

< 0.8 A2s


Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 0.8 A2s


Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 0.8 A2s


Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

Output
Rated voltage Vout rated
Stat. total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


5 V DC
3%
Approx. 0.2 %
Approx. 1.5 %

12 V DC
3%
Approx. 0.2 %
Approx. 1.5 %

15 V DC
3%
Approx. 0.1 %
Approx. 1.5 %

Residual ripple
(mod. freq.: approx. 90 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 100 mVpp

< 200 mVpp

< 200 mVpp

< 100 mVpp


4.6 to 5.4 V

No overshoot of Vout
(soft start)

< 300 mVpp


11.1 to 12.9 V

No overshoot of Vout
(soft start)

< 300 mVpp


13.9 to 16.1 V

Starting delay/voltage rise

< 0.5 s/15 ms typ.

< 0.5 s/15 ms typ.

< 0.5 s/15 ms typ.

Rated current Iout rated


Current range up to +55 C
Parallel connection for
increased output

3A
0 to 3 A
Yes, 2 pieces

1.9 A
0 to 1.9 A
Yes, 2 pieces

1.85 A
0 to 1.85 A
Yes, 2 pieces

Continued on page 13/4.

13/2

Siemens KT 10.1 2002

No overshoot of Vout
(soft start)

LOGO!Power
72 mm series

24 V/1.3 A

48 V/0.65 A

6EP1 331-1SH01

6EP1 351-1SH11

Single-phase AC

Single-phase AC

120 - 230 V AC
Wide-range input

120 - 230 V AC
Wide-range input

85 to 264 V AC

85 to 264 V AC
(Derating at < 93 V)

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.48 - 0.3 A
< 15 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.36 - 0.19 A
< 15 A

< 0.8 A2s


Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 0.8 A2s


Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.1 %
Approx. 1.5 %

48 V DC
3%
Approx. 0.1 %
Approx. 1 %

< 200 mVpp

< 200 mVpp

< 300 mVpp


22.2 to 25.8 V

< 300 mVpp


44.2 to 51.8 V

No overshoot of Vout
(soft start)

No overshoot of Vout
(soft start)

< 0.5 s/15 ms typ.

< 1 s/20 ms typ.

1.3 A
0 to 1.3 A
Yes, 2 pieces

0.65 A
0 to 0.65 A
Yes, 2 pieces

Continued on page 13/5.

Siemens KT 10.1 2002

13/3

LOGO!Power
72 mm series
Technical specifications (continued)
Type

5 V/3 A

12 V/1.9 A

15 V/1.85 A

Order No.

6EP1 311-1SH01

6EP1 321-1SH01

6EP1 351-1SH01

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

> 75 %
<5W

> 80 %
<6W

> 80 %
<7W

Control
Dyn. mains compensation (Vin rated 15 %) < 0.2 % Vout
Dyn. load compensation (Iout: 10/90/10 %) 4 % Vout

< 0.2 % Vout


3 % Vout

< 0.2 % Vout


2.8 % Vout

Settling time
Load step from 10 to 90 %
Load step from 90 to 10 %

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

Protection and monitoring


Output overvoltage protection
Current limitation

3.5 A typ.

2.4 A typ.

2.4 A typ.

RMS sustained short-cct current


Overload/short-circuit indicator

Electronic interruption,
automatic restart
<5A

Electronic interruption,
automatic restart
<4A

Electronic interruption,
automatic restart
<4A

Safety
Electrical isolation primary/
secondary
Protective class (IEC 536)
Discharge current

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA (0.28 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA (0.28 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA (0.28 mA typ.)

Short-circuit protection

CE marking
UL/CSA approval

Yes
Yes
Yes
Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2)
File E179336
File E179336
File E179336

FM approval

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

20 to +55 C with natural convection

20 to +55 C with natural convection

20 to +55 C with natural convection

40 to +70 C

40 to +70 C

40 to +70 C

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity


up to 75 % mean value,
95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm
72 x 90 x 55
0.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm
72 x 90 x 55
0.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

One screw-type terminal each for


0.5 to 2.5 mm2 single-core/finely
stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm
72 x 90 x 55
0.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Approved for use in marine vessels


Degree of protection (EN 60529)
EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating

Mechanical specifications
Connections
Mains input L1, N
Output +
Output
Dimensions (W x H x D) in mm
Weight
Mounting

13/4

Siemens KT 10.1 2002

LOGO!Power
72 mm series

24 V/1.3 A

48 V/0.65 A

6EP1 331-1SH01

6EP1 351-1SH11

> 80 %
<8W

> 80 %
<8W

< 0.2 % Vout


1.5 % Vout

< 0.2 % Vout


1.5 % Vout

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

1.6 A typ.

0.8 A typ.

Electronic interruption,
automatic restart
<4A

Electronic interruption,
automatic restart
< 2.5 A

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA (0.28 mA typ.)

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA (0.28 mA typ.)

Yes
Yes
Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2)
File E179336
File E179336
Yes, Class I Div. 2, Group A, B,
C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, acc. to GL, LR, ABS and


DNV
IP 20

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

20 to +55 C with natural convection

20 to +55 C with natural convection

40 to +70 C

40 to +70 C

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm
72 x 90 x 55
0.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

One screw-type terminal each


for 0.5 to 2.5 mm2 single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm
72 x 90 x 55
0.2 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Siemens KT 10.1 2002

13/5

LOGO!Power
126 mm series
LOGO!Power

Application

LOGO!Power supplies are primary switched-mode power supplies perfectly matched to the LOGO! logic modules in functionality and design. Their wide-range 85 V to 264 V AC input, their
RI level B and their facility for mounting in small distribution
boards make them universally suitable for every conceivable
field of application in the lower power region.

Technical specifications
Type

5 V/6.3 A

12 V/4.5 A

15 V/4 A

Order No.

6EP1 311-1SH11

6EP1 322-1SH01

6EP1 352-1SH01

Input
Rated voltage Vin rated

Single-phase AC
120 - 230 V AC
Wide-range input

Single-phase AC
120 - 230 V AC
Wide-range input

Single-phase AC
120 - 230 V AC
Wide-range input

Voltage range

85 to 264 V AC

85 to 264 V AC

85 to 264 V AC

Mains buffering at Iout rated


Rated line frequency; range
Rated current Iin rated
Inrush current limitation (+25 C)

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.48 - 0.3 A
< 30 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.73 - 0.43 A
< 30 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.8 - 0.48 A
< 30 A

I 2t
Integrated line-side fuse
Required circuit-breaker (IEC 898)
in mains supply cable

< 3 A2s
Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 3 A2s
Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 3 A2s
Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

Output
Rated voltage Vout rated
Stat. total tolerance
Stat. mains compensation
Stat. load compensation

Stabilized, floating direct voltage


5 V DC
3%
Approx. 0.1 %
Approx. 2 %

12 V DC
3%
Approx. 0.1 %
Approx. 1.5 %

15 V DC
3%
Approx. 0.1 %
Approx. 1.5 %

Residual ripple
(modulation frequency:
approx. 90 kHz)
Spikes (bandwidth: 20 MHz)
Setting range
Operation indicator
Power ON/OFF behavior

< 100 mVpp

< 200 mVpp

< 200 mVpp

< 100 mVpp


4.6 to 5.4 V

No overshoot of Vout
(soft start)

< 300 mVpp


11.1 to 12.9 V

No overshoot of Vout
(soft start)

< 300 mVpp


13.9 to 16.1 V

No overshoot of Vout
(soft start)

Starting delay/voltage rise

< 0.5 s/10 ms typ.

< 0.5 s/10 ms typ.

< 0.5 s/10 ms typ.

Rated current Iout rated


Current range up to +55 C
Parallel connection for
increased output

6.3 A
0 to 6.3 A
Yes, 2 pieces

4.5 A
0 to 4.5 A
Yes, 2 pieces

4A
0 to 4 A
Yes, 2 pieces

Continued on page 13/8.

13/6

Siemens KT 10.1 2002

LOGO!Power
126 mm series

24 V/2.5 A

48 V/1.25 A

6EP1 332-1SH41

6EP1 352-1SH11

Single-phase AC
120 - 230 V AC
Wide-range input

Single-phase AC
120 - 230 V AC
Wide-range input

85 to 264 V AC

85 to 264 V AC

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.85 - 0.5 A
< 30 A

> 40 ms at Vin = 187 V


50/60 Hz; 47 to 63 Hz
0.69 - 0.36 A
< 30 A

< 3 A2s
Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

< 3 A2s
Internal
from 10 A, Characteristic C or
from 6 A, Characteristic D

Stabilized, floating direct voltage


24 V DC
3%
Approx. 0.1 %
Approx. 1.5 %

48 V DC
3%
Approx. 0.1 %
Approx. 1 %

< 200 mVpp

< 200 mVpp

< 300 mVpp


22.2 to 25.8 V

No overshoot of Vout
(soft start)

< 300 mVpp


44.2 to 51.8 V

No overshoot of Vout
(soft start)

< 0.5 s/10 ms typ.

< 1 s/20 ms typ.

2.5 A
0 to 2.5 A
Yes, 2 pieces

2.5 A
0 to 2.5 A
Yes, 2 pieces

Continued on page 13/9.

Siemens KT 10.1 2002

13/7

LOGO!Power
126 mm series
Technical specifications (continued)
5 V/6.3 A

12 V/4.5 A

15 V/4 A

Order No.

6EP1 311-1SH11

6EP1 322-1SH01

6EP1 352-1SH01

Efficiency
Efficiency at Vout rated, Iout rated
Power loss at Vout rated, Iout rated

> 75 %
< 11 W

> 80 %
< 14 W

> 80 %
< 15 W

Control
Dyn. mains compensation (Vin rated 15 %) < 0.2 % Vout
Dyn. load compensation (Iout: 10/90/10 %) 6.5 % Vout

< 0.2 % Vout


4.2 % Vout

< 0.2 % Vout


3.3 % Vout

Settling time
Load step from 10 to 90 %
Load step from 90 to 10 %

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

Protection and monitoring


Output overvoltage protection
Current limitation

8 A typ.

5.4 A typ.

5 A typ.

RMS sustained short-cct current


Overload/short-circuit indicator

Electronic interruption,
automatic restart
< 10 A

Electronic interruption,
automatic restart
<8A

Electronic interruption,
automatic restart
<8A

Safety
Electrical isolation primary/
secondary
Protective class (IEC 536)
Discharge current

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA

Short-circuit protection

CE marking
UL/CSA approval

Yes
Yes
Yes
Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2)
File E179336
File E179336
File E179336

FM approval

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, Class I Div. 2, Group A, B,


C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

20 to +55 C with natural convection

20 to +55 C with natural convection

20 to +55 C with natural convection

40 to +70 C

40 to +70 C

40 to +70 C

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity


up to 75 % mean value,
95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm

One screw-type terminal each for


0.5 to 2.5 mm single-core/finely
stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm

126 x 90 x 55
0.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

126 x 90 x 55
0.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

126 x 90 x 55
0.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Appr. for use in marine vessels


Degree of protection (EN 60 529)
EMC
Interference emission
Line harmonics limitation
Interference immunity
Operating specifications
Ambient temperature range
Transportation and storage
temperature range
Humidity rating

Mechanical specifications
Connections
Mains input L1, N
Output +
Output
Dimensions (W x H x D) in mm
Weight
Mounting

13/8

Siemens KT 10.1 2002

LOGO!Power
126 mm series

24 V/2.5 A

48 V/1.25 A

6EP1 332-1SH41

6EP1 352-1SH11

> 80 %
< 15 W

> 80 %
< 15 W

< 0.2 % Vout


1.5 % Vout

< 0.2 % Vout


1 % Vout

20 ms typ.
20 ms typ.

20 ms typ.
20 ms typ.

3.1 A typ.

1.6 A typ.

Electronic interruption,
automatic restart
<8A

Electronic interruption,
automatic restart
<4A

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA

Yes, SELV output voltage Vout


acc. to EN 60950
Class II
< 3.5 mA

Yes
Yes
Yes, UL/CSA listed (UL 508, CSA 22.2) Yes, UL/CSA listed (UL 508, CSA 22.2)
File E179336
File E179336
Yes, Class I Div. 2, Group A, B,
C, D Part 4
Yes, acc. to GL, LR, ABS and
DNV
IP 20

Yes, acc. to GL, LR, ABS and


DNV
IP 20

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

EN 50081-1, EN 55022
Class B
Not applicable
EN 50082-2,
EN 61000-4-2, -3, -4, -5, -6

20 to +55 C with natural convection

20 to +55 C with natural convection

40 to +70 C

40 to +70 C

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

F acc. to DIN 40040: rel. humidity up to 75 % mean value,


95 % on 30 days/year;
no condensation

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm

One screw-type terminal each


for 0.5 to 2.5 mm single-core/
finely stranded
2 screw-type terminals for
0.5 to 2.5 mm
2 screw-type terminals for
0.5 to 2.5 mm

126 x 90 x 55
0.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

126 x 90 x 55
0.4 kg
Snap-mounting on DIN rail
EN 50022-35 x 15/7.5

Siemens KT 10.1 2002

13/9

LOGO!Power
Notes

13/10

Siemens KT 10.1 2002

ary
Second ode
d-m
switche tor
regula

g
Filterin
ation
Rectific

Switc

nsistor
hing tra

Vout
d
stabilize

mer
Transfor

Load
ilized
Unstab
mains
l
Contro

0003
PD60_0

Technical
information and
configuring
notes

14/2

Power supplies general

14/2

Stabilized DC power supply

14/5

Mains specifications, international


mains voltages and frequencies in
low-voltage mains

14/8

Line-side connection and fusing

14/9

Potential mains interference factors and their sources

14/10

Mounting instructions, spaces and


fixing options

14/11

Planning and design aids, parallel


connection

14/13

Connection in series, battery


charging

14/14

Circuit-breakers in the 24 V DC
output circuit, selectivity

Siemens KT 10.1 2002

14/1

Technical information and configuring notes


Power supplies general
Technical information and configuring notes

Power supplies
Whether in facility or mechanical engineering, wherever electric
controls are implemented a safe and reliable power supply is
needed to provide the process with energy.
Uninterrupted function of electric controls and reliable operation
of automated facilities is closely linked to a fail-safe load power
supply. Only if its uninterrupted operation is ensured, actuators
as well as input and output components execute commands
properly.

EMC

Interference phenomenon

Interference
emission

Influencing television and radio reception

Interference
immunity

Interference on the mains supply cable caused


by switching processes on non-ohmic loads
such as motors or contactors
Static discharge caused by lightning stroke

In addition to usual requirements such as safety, the electromagnetic compatibility (EMC) of the power supply must meet
special requirements concerning output voltage tolerance ranges and fundamental ripple.

Electrostatic discharge caused by the human


body
Line-connected interference induced by radio
frequencies

Particularly important for unproblematic implementation are:


Current consumption low in harmonics

Disturbances on data or power supply lines

Table 1

Selection of interference phenomena

Low interference emission and


Sufficient interference immunity to disturbances

DC power supplies general


A DC power supply is a static device with one or more inputs and
one or more outputs converting a system of alternating voltage
and alternating current and/or direct voltage and direct current
into a system of direct voltage and direct current - usually with

different values - by electromagnetic induction for transmitting


electric power.
The differences in design of DC power supplies are mainly determined by their intended application.

Unstabilized DC power supply


The AC line voltage is transformed into safety extra-low voltage
with 50 Hz/60 Hz safety isolating transformers and consecutively
smoothed by rectification and capacitor filtering.
With unstabilized DC power supplies, the DC output voltage is
not stabilized to a certain value, but the value changes depending on the fluctuation of the (mains) input voltage and the load.

Line isolation

Rectification

50 Hz
~

The ripple is within Volt range and depends on the load. The ripple is usually expressed in percent, proportional to the DC output voltage value. Characteristic for unstabilized DC power supplies is their design: rugged, simple, limited to the essentials and
built to last.

Filtering

Vout

G_KT01_en_00067

Fig. 1 Basic connection diagram of an unstabilized power supply

Stabilized DC supply
Stabilized DC supplies feature electronic control circuits to keep
the value of the direct output voltage on approximately one
particular value. Influences such as input voltage fluctuations or
varying load on the output are electrically compensated within
the assigned function range.
The output voltage ripple of stabilized DC power supplies is
within the millivolt range and depends to a large extend on the
load at the output.

14/2

Siemens KT 10.1 2002

Stabilized DC power supplies can be realized with various functional principles. The most common circuit types are:
In-phase controlled power supplies
Magnetic voltage regulators
Secondary switched-mode power supplies
Primary switched-mode power supplies
It depends on the field of application, which of the circuit principles described in the following is best suited for the application.
The aim is to reproduce a good direct voltage for supplying the
respective loads as inexpensively as possible.

Technical information and configuring notes


Stabilized DC power supply

Stabilized DC power supply (continued)


In-phase controlled power supplies
Rectifier

The complete converter is composed of two components: the


so-called ferroresonator and an additional controller connected
in series. The input winding and the resonance winding of the
magnetic regulator are almost completely isolated from each
other by leakage air gaps. The magnetic regulator alone supplies a well stabilized alternating voltage. It is rectified and filtered. The converter itself is operated in the saturation region.

Filtering
Actuator
electrolytic capacitor

Transformer

Unstabilized
mains

Stabilized
Vout

Load

Often an in-phase regulator or a secondary switched-mode regulator is connected in series to the ferroresonator to reach higher
control precision.

PD60_00001

Fig. 2 Basic circuit diagram in-phase regulator

The in-phase regulator, also called linear controller, functions on


a conventional principle. It is supplied by an AC system (single,
two or three-wire system).
The supply voltage is matched to the secondary voltage with a
transformer.
A controller transforms the rectified and filtered secondary
voltage into a stabilized voltage at the output. The controller
consists of an actuator and the control amplifier. The difference
between stabilized output voltage and unstabilized voltage at
the filter capacitor is transformed into heat loss at the actuator.
In this process the actuator functions as a quickly variable ohmic
resistor. The produced heat loss is the product of output current
and voltage drop on the actuator.
This system is very variable. Several output voltages can be realized with no effort. In general, the individual secondary circuits
are generated from separate secondary windings of the input
transformer if several output voltages are to be produced. Some
applications can only be carried out according to this circuit
principle. Especially when precise control, low residual ripple
and short settling times are required.
However, the efficiency is quite low and weight and volume are
high. Therefore, the in-phase controller is an inexpensive alternative only for small performances.
Advantages:
Simple well-proven circuit principle
Good to best control properties
Short settling time
Disadvantages:
Comparatively high weight and large volume due to the 50 Hz
transformer
Short storage time
in case of
readjustment

Stabilized output
voltage

Vout stabilized

PD30_00003

Load

Fig. 3 Basic connection diagram magnetic regulator

Considerably higher efficiency than in-phase regulators alone


Disadvantages:
Ferroresonator is frequency-dependent
Power supplies are large and heavy due to magnetic components

Secondary switched-mode power supplies:


Filtering
Rectification

Switching transistor

Secondary
switched-mode
regulator

Transformer
Unstabilized
mains

Vout
stabilized

Load
Control

PD60_00003

Fig. 4 Basic connection diagram secondary switched-mode power


supply

The circuits are separated by a 50 Hz transformer. After the power has been rectified and filtered, it is switched impulsive at the
output via a switching transistor into the filtering and storing circuit. Mains pollution is low due to the transformer at the input
functioning as a filter.
Efficiency of this circuit is very high.

The connected loads, however, must be protected against the


situation that the switching transistor fails and all of the unstabilized direct voltage of the filtering capacitor is applied. This
danger, however, is also applicable for linear controller power
supplies.

Magnetic regulator

Unstabilized
mains

Advantages:
Good to best control properties in combination with in-phase
regulators connected in series

On the whole this principle offers great advantages for power


supplies with many different output voltages.

Low efficiency, cooling problems

Ferroresonator

The technology of the magnetic regulator is reliable and rugged,


but also large, heavy and rather expensive.

Advantages:
Simple design and high efficiency
Multiple outputs, also electrically isolated from each other, are
easily realized by using several secondary windings
Less problems with interference than with primary switchedmode regulators

Siemens KT 10.1 2002

14/3

Technical information and configuring notes


Stabilized DC power supply

Stabilized DC power supply (continued)


Disadvantages:
Comparatively large and heavy due to 50 Hz transformer
Output ripple (spikes) is equal to that of a primary switchedmode power supply

Advantages:
Small magnetic components (transformer, storage choke, filter) due to the high operating frequency
High efficiency due to pulse-width control
Compact components

Primary switched-mode power supplies:

No forced cooling required even in the range of kW

You will also often find the abbreviation SMPS or the term primary switched-mode regulator.

High storage times in case of supply interruption by increasing


the capacitance in the intermediate sector.
Wide input voltage range possible

Single-ended forward

Disadvantages:
Complex circuit, many active components

Vout
stabilized

PD60_00002

Fig. 5

Large extent of interference suppression required


Load

Unstabilized
mains

Control

Primary switched-mode power supplies have gained high


acceptance over the last years compared to other circuit principles, primary reasons for this being their small size, low weight,
high efficiency and good cost-performance ratio.

Basic connection diagram single-ended forward converter

There are many circuit principles for a primary switched-mode


regulator. The most significant basic circuits are single-ended
forward converters, flyback converters, half-bridge converters,
full-bridge converters, push-pull converters and resonance
converters.
The basic connection diagram of the single-ended forward converter explains the basic principle of a primary switched-mode
regulator:
First, the unstabilized mains voltage is rectified and filtered. The
capacitance of the capacitor in the intermediate sector determines the storage time of the power supply in case of input voltage failure. With a 230 V mains, the voltage in the intermediate
sector is approx. 320 V DC. This direct voltage supplies a singleended converter which, in connection with a pulse-width regulator and with a high switching frequency, transmits the primary
power via a transformer to the secondary circuit. In its function
as a switch, the switching transistor has a low power loss so that
the overall efficiency is in the range of > 70 % up to approx. 90
% depending on output voltage and current.
The size of the transformer is small compared to a 50 Hz transformer due to the high switching frequency as the size of a transformer decreases with increasing switching frequency. With
modern semi-conductors, modulation frequencies of 100 kHz
and more can easily be reached. However, with increasing
modulation frequency, switching losses also increase. Thus,
some applications will be a compromise between high efficiency
and highest possible modulation frequency. For most applications modulation frequencies of approx. 20 - 250 kHz are
reached depending on the output power.
The voltage of the secondary winding is rectified and filtered.
Deviations at the output are fed back to the primary circuit via
opto couplers. By controlling the pulse width (conducting phase
of the switching transistor in the primary circuit) the required
power is transmitted to the secondary circuit and the output voltage is stabilized. During the non-conducting phase of the
switching transistor, the transformer is demagnetized via an auxiliary winding. Only the amount of power taken from the output is
transmitted. The maximum pulse width for the duty factor is < 50
% for these circuits.

14/4

Mechanical specifications must meet HF requirements

Siemens KT 10.1 2002

Summary
Table 2 gives an overview of the properties of the mentioned circuits that are most significant to the user.

Circuit types
Comparison
criteria

Primary Secondary In-phase


switched switched- regulator
-mode
mode

Magnetic
regulator

Input voltage
range

very
wide

medium

very small

wide

Reaction

medium

medium

very fast

slow

Storage time
after supply
interruption

very
long

long

very short

long

Residual ripple

medium

medium

very low

medium

Power loss

very low

low

high

very low

Size

very low

medium

very large

large

Weight

very light

medium

heavy

very
heavy

medium

small

medium

Extent of interfer- very


ence suppreslarge
sion
Table 2

Comparison criteria for basic circuit types

Technical information and configuring notes


Mains specifications, international mains voltages
and frequencies in low-voltage mains

Mains specifications
When designing and choosing facility components, mains specifications, mains statuses as well as operating purposes for
which the components should be implemented must be taken
into consideration.
Rated voltage and frequency are significant specifications of a
system. This supply system data is referred to as rated values
according to international agreements.

Rated voltages and rated frequencies


Since May 1987, the standard DIN IEC 60038 "IEC-Normspannungen (IEC standard voltages) is valid in the Federal Republic
of Germany.
This standard contains exactly the international standard IEC
60038, revision 6, 1983, "IEC standard voltages.
The standard IEC 60038 is the result of international agreements
to reduce the number of standard voltage values for electric
power supply and traction systems, for consumer's installations
and units.

Conversion of low-voltage mains


For low-voltage mains, the standard IEC 60038 replaces the voltage values 220/380 V and 240/415 V for three-phase mains of
electric power supply by the single worldwide standard value of
230/400 V.
For the transitional period until the year 2003, tolerances are allowed for the operating voltages of the mains. This is to ensure
safe operation of components built for the previously valid standard voltages.
Year

Standard voltage

Tolerance range

before 1987

220/380 V

-10 % to +10 %

from 1988 until


2003

230/400 V

-10 % to + 6 %

from 2003 on

230/400 V

-10 % to +10 %

Table 3

Conversion of low-voltage mains

The IEC recommendations have been adopted as national regulations by the most significant countries as far as the conditions
in the respective country allow for adoption.

International mains voltages and frequencies in low-voltage mains


Country

Mains voltage

Western Europe:
Belgium

50 Hz 230/400 127-220 V

Denmark

50 Hz 230/400 V

Germany

50 Hz 230/400 V

Finland

50 Hz 230/400-5001) 6601) V

France

50 Hz 127/220 230/400 5001) 380/6601) 525/9101) V

Greece

50 Hz 230/400 127/2202) V

Great Britain

50 Hz (230/400 V)3)

Ireland

50 Hz 230/400 V

Iceland

50 Hz 127/2202) 230/400 V

Italy

50 Hz 127/220 230/400 V

Luxembourg

50 Hz 230/400 V

Netherlands

50 Hz 230/400 6601) V

Northern Ireland

50 Hz 230/400 Belfast 220/380 V

Norway

50 Hz 230-230/400-5001) 6901) V

Austria

50 Hz 230/400 5001) 6901) V

Portugal

50 Hz 230/400 V

Sweden

50 Hz 230/400 V

Switzerland

50 Hz 230/400 5002) V

Spain

50 Hz 230/400 V

Eastern Europe:
Albania

50 Hz 230/400 V

Bulgaria

50 Hz 230/400 V

Croatia

50 Hz 230/400 V

Slovenia

50 Hz 230/400 V

Serbia

50 Hz 230/400 V

Czech Republic

50 Hz 230/400 5001) 6901) V

Slovakia

50 Hz 230/400 5001) 6901) V

Countries of former Soviet Union

50 Hz 230/400 6901) V

Poland

50 Hz 230/400 V

Romania

50 Hz 230/400 V

Hungary

50 Hz 230/400 V

Siemens KT 10.1 2002

14/5

Technical information and configuring notes


International mains voltages and frequencies
in low-voltage mains

International mains voltages and frequencies in low-voltage mains (continued)


Country

Mains voltage

Near East:
Afghanistan

50 Hz 220/380 V

Bahrain

50 Hz 230/400 V

Cyprus

50 Hz 240/415 V

Iraq

50 Hz 220/380 V

Israel

50 Hz 230/400 V

Jordan

50 Hz 220/380 V

Kuwait

50 Hz 240/415 V

Lebanon

50 Hz 110/190 220/380 V

Oman

50 Hz 220/380 240/415 V

Qatar

50 Hz 240/415 V

Saudi Arabia

60 Hz 127/220 220/380 4801) V (220/380 240/415 V 50 Hz: only remains)

Syria

50 Hz 115/200 220-380 4001) V

Turkey

50 Hz 220/380 V (parts of Istanbul: 110/190 V)

United Arab Emirates


(Abu Dhabi; Ajman; Dubai; Fujairah;
Ras al Khaimah; Sharjah; Umm al-Quwain)

50 Hz 220/380 240/415 V

Yemen (North)

50 Hz 220/380 V

Yemen (South)

50 Hz 230/400 V

Far East:
Bangladesh

50 Hz 230/400 V

Burma

50 Hz 230/400 V

Peoples Republic of China

50 Hz 127/220 220/380 V (for mining: 1140 V)

Hong Kong

50 Hz 200/346 V

India

50 Hz 220/380 230/400 240/415 V

Indonesia

50 Hz 127/220 220/380 4001) V

Japan

50 Hz 100/200 4001) V

Southern part of Honshu, Shikoku, Kyushu, Hokkaido, Northern part of Honshu

60 Hz 110/220 4401) V

Cambodia

50 Hz 120/208 V Phnom Penh 220/238 V

North Corea

60 Hz 220/380 V

South Corea

60 Hz 100/2002) 220/380 4401) V

Malaysia

50 Hz 240/415 V

Mongolia

50 Hz 220/380 V

Pakistan

50 Hz 230/400 V

Philippines

60 Hz 110/220 440 V

Singapore

50 Hz 240/415 V

Sri Lanka

50 Hz 230/400 V

Taiwan

60 Hz 110/220 220 440 V

Thailand

50 Hz 220/380 V

Vietnam

50 Hz 220/380 V

North America:
Canada

60 Hz 600 120/240 460 575 V

USA

60 Hz 120/208 120/240 277/480 6001) V

Central America:
Bahamas

60 Hz 115/200 120/208 V

Barbados

50 Hz 110/190 120/208 V

Belize

60 Hz 110/220 220/440 V

Costa Rica

60 Hz 120/2082) 120/240 127/220 254/4402) 227/4801) V

Dominican Republic

60 Hz 120/208 120/240 4801) V

Guatemala

60 Hz 120/208 120/240 127/220 277/4801) 4801) 5501) V

Haiti

50 Hz 220/380 V (Jacmel),
60 Hz 110/220 V

1) only for industrial purposes

14/6

Siemens KT 10.1 2002

2) no further expansion

3) from 2003 on

Technical information and configuring notes


International mains voltages and frequencies
in low-voltage mains

International mains voltages and frequencies in low-voltage mains (continued)


Country

Mains voltage

Central America (continued):


Honduras

60 Hz 110/220 127/220 277/480 V

Jamaica

50 Hz 110/220 4401) V

Cuba

60 Hz 120/240 220/380 277/4801) 4401) V

Mexico

60 Hz 127/220 4401) V

Nicaragua

60 Hz 110/220 120/240 127/220 220/440 254/401) V

Panama

60 Hz 120/2081) 120/240 254/4401) 277/4801) V

Puerto Rico

60 Hz 120/208 480 V

El Salvador

60 Hz 110/220 120/208 127/220 220/440 240/4801) 254/4401) V

Trinidad

60 Hz 110/220 120/240 230/400 V

South America:
Argentina

50 Hz 220/380 V

Bolivia

60 Hz 220/380 480 V
50 Hz 110/220 220/380 V (exception)

Brazil

60 Hz 110/220 220/440 127/220 220/380 V

Chile

50 Hz 220/380 V

Ecuador

60 Hz 120/208 127/220 V

Guyane

50 Hz 110/220 V (Georgetown)
60 Hz 110/220 240/480 V

Colombia

60 Hz 110/220 150/260 440 V

Paraguay

60 Hz 220/380 220/440 V

Peru

60 Hz 220 220/380/440 V

Surinam

60 Hz 115/230 127/220 V

Uruguay

50 Hz 220 V

Venezuela

60 Hz 120/208 120/240 208/416 240/480 V

Africa:
Egypt

50 Hz 110/220 220/380 V

Ethiopia

50 Hz 220/380 V

Algeria

50 Hz 127/220 220/380 V

Angola

50 Hz 220/380 V

Benin

50 Hz 220/380 V

Ivory Coast

50 Hz 220/380 V

Gabon

50 Hz 220/380 V

Ghana

50 Hz 127/220 220/380 V

Guinea

50 Hz 220/380 V

Kenya

50 Hz 220/380 V

Cameroon

50 Hz 127/220 220/380 V

Congo

50 Hz 220/380 V

Liberia

60 Hz 120/208 120/240 V

Libya

50 Hz 127/2202) 220/380 V

Madagascar

50 Hz 127/220 220/380 V

Malawi

50 Hz 220/380 V

Mali

50 Hz 220/380 V

Morocco

50 Hz 115/200 127/220 220/380 5001) V

Mauritius

50 Hz 240/415 V

Mozambique

50 Hz 220/380 V

Namibia

50 Hz 220/380 V

Niger

50 Hz 220/380 V

Nigeria

50 Hz 220/415 V

Rwanda

50 Hz 220/380 V

1) only for industrial purposes

2) no further expansion

3) from 2003 on

Siemens KT 10.1 2002

14/7

Technical information and configuring notes


International mains voltages and frequencies in
low-voltage mains, line-side connection

International mains voltages and frequencies in low-voltage mains (continued)


Country

Mains voltage

Africa (continued):
Zambia

50 Hz 220/380 V 415 5501) V

Senegal

50 Hz 127/220 220/380 V

Sierra Leone

50 Hz 220/380 V

Somalia

50 Hz 220-220/440 V

Sudan

50 Hz 240/415 V

South Africa

50 Hz 220/380 5001) 550/9501) V

Swaziland

50 Hz 220/380 V

Tanzania

50 Hz 230/400 V

Togo

50 Hz 127/220 220/380 V

Tunisia

50 Hz 115/200 220/380 V

Uganda

50 Hz 240/415 V

Zaire

50 Hz 220/380 V

Zimbabwe

50 Hz 220/380 V

1) only for industrial purposes

Line-side connection and fusing


All SITOP power and LOGO!Power supplies are built-in units.
When installing the units, the pertinent DIN/VDE or national regulations must be observed. The supply voltage must be connected according to VDE 0100 and VDE 0160. For the installation, a protective device and an isolating device must be
provided for safety isolation of the power supply.
Immediately after the input voltage has been applied, power
supplies cause an inrush current as the capacitor charges up.
This current declines to the rated input current after a few milliseconds. Apart from the internal impedances of the power supply, the inrush current depends to a large extent on the magnitude of the applied input voltage as well as on the source
impedance of the supply system and on the line impedance of
the cable. The maximum inrush current of SITOP power supplies
is listed in the relevant technical specifications. It is significant
for the design rating of protective devices on the line side.

14/8

Siemens KT 10.1 2002

Single-phase SITOP power and LOGO!Power supplies feature


internal protection (a fuse). For the AC line connection it is merely necessary to provide a protective device (fuse or circuitbreaker) for line protection depending on the permissible rated
current for the installed cable. The circuit-breakers recommended in the data sheets and instruction manuals have been chosen
so that not even the maximum inrush current that could occur
under the most unfavorable conditions when the supply voltage
is applied would trip the circuit-breaker.
Three-phase SITOP power supplies feature no internal protection. The line-side protective device (three-phase coupled circuit-breaker or motor circuit-breaker) provides cable and equipment protection. Protective devices specified in the data sheets
and instruction manuals are perfectly matched to the characteristics of the corresponding power supplies.

Technical information and configuring notes


Potential mains interference factors
and their sources

Potential mains interference factors and their sources


For highly sensitive electronic facilities and devices (computers,
industrial controls, measuring technology etc.), the mains voltage quality has become a decisive factor for their proper functioning, reliability, need for maintenance and lasting service life.
Mains interference causes system failures and impedes the
function of facilities as well as of electronic loads. Mains interference may lead to complete failure of facilities or devices.

Long supply interruption


Mains interference may have different causes, e. g.:
Switching operations in the system
Long lines in the system
Environmental causes such as thunderstorms
Overloads

Long-term undervoltage

Typical causes for internally created mains interference


are e. g.:
Thyristor-controlled drives

Interfering impulses and transients

Elevators, air conditions, copiers

Voltage dip and voltage surge

Motors, compensation equipment

Electric noise

Electric welding, large machines

Brief supply interruption

Switching of lights

The most frequent types of interference are:


Long-term overvoltage

The mentioned types of mains voltage interference may occur separately or as a combination of several. Possible causes for interference and effects may be:
Mains interference

Percentage of
Effect
total interference

Overvoltage
Mains voltage is long-term exceeded by more than +6%
(acc. to DIN IEC 60038)

Approx. 15 - 20 % May lead to overheating or even thermal destruction of


components. Causes complete failure.

Undervoltage
Mains voltage falls long-term short of at least -10%
(acc. to DIN IEC 60038)

Approx. 20 - 30 % May lead to undefined operating statuses of the loads.


Causes data failures.

Interfering impulses
High-energy pulses (e. g. 700 V/1 ms) and low-energy transients (e. Approx. 30 - 35 % May lead to undefined operating statuses of the loads and
g. 2500 V/20s) are produced by switching operations in the syscause destruction of components.
tem
Voltage dip and voltage surge
The voltage level changes briefly and uncontrolled, e. g. caused by Approx. 15 - 30 % May lead to undefined operating statuses and to destrucload change and long lines
tion of components. Causes data failures.
Electric noise
Frequency spectrum interfering the mains caused by bad grounding and/or strong sources of HF noise, such as radio transmitters,
thunderstorms

Approx. 20 - 35 % May lead to undefined operating statuses of the loads.


Causes data failures.

Voltage interruption
Brief interruption of mains voltage (no more than approx. 10 ms),
caused by short-circuit in neighboring systems or starting of large
electric machines.

Approx. 8 - 10 %

May lead to undefined operating statuses of the loads, in


particular of those lacking mains buffering. Causes data
failures.

Approx. 2 - 5 %

May lead to undefined operating statuses of the loads, in


particular of those lacking mains buffering. Causes data
failures.

Voltage interruption
Long interruption of mains voltage (more than approx. 10 ms)

Table 4

Types of mains interference and effects

The product range SITOP power offers multiple possibilities to minimize or eliminate risks of mains interference in the preliminary
stage.

Siemens KT 10.1 2002

14/9

Technical information and configuring notes


Mounting instructions, spaces and fixing options

Mounting instructions
All SITOP power and LOGO!Power supplies are built-in units.
Except for versions in degree of protection IP 65 they should
be mounted vertically so that air can flow unimpeded from
below through the ventilation slots at the bottom of the unit out
through the ventilation slots at the top. In case of mounting orientations other than vertical (at user's own risk), the ambient

temperature should not exceed +45 C and the load current


should remain below approx. 50 % of the rated current. For
versions in degree of protection IP 65, any mounting position is
permissible. The minimum clearances above, below and to the
side of each unit specified in the relevant instruction manual
must be observed to ensure free air convection.

Mounting spaces and fixing options


Power supply

Order No.

Required mounting
space in
mm (W x H)

Mounting on DIN rail EN 50022


35 x 7.5 mm

35 x 15 mm

22.5 x 180
22.5 x 180

X
X

X
X

Wall
mounting

SITOP power supplies


SITOP power 24 V/0.5 A
SITOP power 24 V/0.375 A

6EP1331-2BA10
6EP1731-2BA00

SITOP power 24 V/2 A

6EP1331-2BA00
6ES7307-1BA00-0AA0
6ES7305-1BA80-0AA0
6EP1732-0AA00

50
50
80
80

x 225
x 325
x 325
x 235

SITOP power 24 V/2.5 A


SITOP power 24 V/3.5 A
SITOP power 24 V/4 A

6EP1332-1SH12
6EP1332-1SH31
6EP1332-1SH22

80 x 335
160 x 280
80 x 335

SITOP power 24 V/5 A

6EP1333-2BA00
6EP1333-2AA00
6ES7307-1EA80-0AA0
6ES7305-1EA00-0AA0
6EP1333-1AL11

75
75
80
80
260

x 225
x 225
x 325
x 325
x 330

6EP1334-2BA00
6EP1334-2AA00
6EP1334-2CA00
6ES7307-1KA00-0AA0
6EP1334-1AL11
6EP1334-1SH01

100
100
160
200
320
200

SITOP power 24 V/20 A


SITOP power 24 V/10 A
SITOP power 24 V/20 A

SITOP power 24 V/10 A

SITOP power 24 V/30 A


SITOP power 24 V/40 A
SITOP power buffer module

X
1)
1)

X
X
X

X
X
X

X
X
X

X
X
1)
1)
X

x 225
x 225
x 290
x 325
x 330
x 325

X
X

X
X

X
X

6EP1336-2BA00
6EP1536-2AA00

320 x 225
320 x 280

X
X

X
X

6EP1434-2BA00
6EP1436-2BA00
6EP1436-3BA00
6EP1437-2BA00
6EP1437-2BA10
6EP1437-3BA00
6EP1961-3BA00

320
320
160
320
320
240
70

x 225
x 225
x 225
x 280
x 280
x 225
x 225

X
X
X
X
X
X
X

X
X
X
X
X
X
X

X
1)

SITOP power DC UPS 15


SITOP power DC UPS 15
with RS 232
SITOP power DC UPS 40

6EP1931-2EC01
6EP1931-2EC11

75 x 225
75 x 225

X
X

X
X

6EP1931-2FC01

280 x 290

SITOP power battery module 2.5 Ah


SITOP power battery module 3.2 Ah
SITOP power battery module 7 Ah
SITOP power battery module 12 Ah

6EP1935-6MD31
6EP1935-6MD11
6EP1935-6ME21
6EP1935-6MF01

285
210
206
273

x 171
x 171
x 188
x 138

X
X

X
X

SITOP power 3 -52 V/120 W


SITOP power 2 x 15 V/3.5 A

6EP1353-2BA00
6EP1353-0AA00

75 x 225
75 x 325

X
X

X
X

SITOP power 30 V/2.4 A


SITOP power 30 V/7 A

6EP1632-1AL01
6EP1354-1AL01

260 x 80
200 x 325

19

1) with additional mounting adapter

14/10

Siemens KT 10.1 2002

X
X
X
X

X
X

Technical information and configuring notes


Mounting spaces and fixing options, planning and
design aids, parallel connection

Mounting spaces and fixing options (continued)


Power supply

Order No.

Required mounting
space in
mm (W x H)

Mounting on DIN rail EN 50022


35 x 7.5 mm

35 x 15 mm

x 110
x 110
x 110
x 110
x 110

X
X
X
X
X

X
X
X
X
X

126 x 110
126 x 110
126 x 110
126 x 110
126 x 110

X
X
X
X
X

X
X
X
X
X

Wall
mounting

LOGO!Power supplies
SITOP power 5 V/3 A
12 V/1.9 A
15 V/1.85 A
24 V/1.3 A
48 V/0.65 A

6EP1311-1SH01
6EP1321-1SH01
6EP1351-1SH01
6EP1331-1SH01
6EP1351-1SH11

SITOP power 5 V/6.3 A


12 V/4.5 A
15 V/4 A
24 V/2.5 A
48 V/1.25 A

6EP1311-1SH11
6EP1322-1SH01
6EP1352-1SH01
6EP1332-1SH41
6EP1352-1SH11

72
72
72
72
72

Planning and design aids


Instruction manuals containing mounting instructions,
dimension drawings and basic connection diagrams with
terminal markings are available for planning and design as
downloads from the internet in different file formats (also for

CAD applications). You can find the SITOP power homepage at:
SITOP
www.siemens.de/sitop

Parallel connection for redundancy


Two SITOP power supplies of the same type can be connected in parallel via diodes (see figure: V1, V2) to achieve
redundancy. 100 % redundancy of two SITOP power supplies can only be achieved if the total load current is not
higher than the current one SITOP power can supply by
itself and the supply at the primary side is also configured
with redundancy (i. e. a primary-side short-circuit of the
power supply does not trip a common circuit-breaker and
thus disconnects both power supplies from the system).
Parallel connection with decoupling diodes for redundancy
is permissible for all SITOP power supplies. The diodes V1
and V2 are used for decoupling. They should have a
reverse voltage rating of at least 40 V and a current rating of
at least the maximum output current of the connected
SITOP power.

V1

V2

Two SITOP power supplies connected in parallel for redundancy

Parallel connection for increased output


For increased output, most of the SITOP power supplies can directly, i. e. without decoupling diodes, be connected in parallel
to supplies of the same type (same principle as for connection
in parallel for redundancy, but without decoupling diodes).
Advantage
Mechanical mounting of the diodes on heatsinks and considerable power loss of the decoupling diodes (current x diode conducting-state voltage drop) are avoided.
Types approved for direct connection in parallel can be found in
the relevant technical specifications under "Output, parallel connection for increased output".

Prerequisite
7

The output conductors connected to each SITOP power supply at the terminal L+ and M should feature the same length
and cross-section (or same impedance) up to the external
point of common coupling, if possible.

SITOP power supplies connected in parallel should be


switched on simultaneously with a common switch in the
mains supply cable (e. g. with the main switch provided in
control cabinets).

The SITOP power output voltages measured with no load of


supplies not yet connected in parallel must not differ by more
than 50 mV.
This usually corresponds to the default settings.
In case the output voltage is changed on an adjustable SITOP
power supply, the M terminals should be connected and the
voltage difference measured with no load between the SITOP
power output terminals L+, which are not yet connected.
This voltage difference must not exceed 50 mV.

Siemens KT 10.1 2002

14/11

Technical information and configuring notes


Parallel connection,
General notes on the diodes

Parallel connection for redundancy and increased power


Almost 100 % redundancy
With the types permissible for direct parallel connection (refer to
the relevant technical specifications under "Output, parallel connection for increased output"), the power output can be increased without decoupling diodes whilst simultaneously
achieving almost 100 % redundancy. This is done by directly
connecting an additional SITOP power supply of the same type
in parallel to the SITOP power supply of the required rating, i. e.
at least one SITOP power supply more than required for the total
of all load currents.
The purpose of the decoupling diode usually required for redundancy is to prevent short-circuiting of the intact power supplies
in the event of a power supply failure caused by a short-circuit
at the output (especially a short-circuit of the output electrolytic
capacitor).

However, this theoretical case is not to be expected with SITOP


power in practice. Therefore, almost 100 % redundancy can be
achieved with this circuit principle.

Example
Load current of up to 40 A is required. The power supply must
be capable of operating in a three-phase 400 V as well as a 500
V system (without system transfer).
The three-phase SITOP power 20 A (Order No.: 6EP14362BA00) is suitable. For load currents of up to 40 A, direct parallel
connection of two SITOP power 20 is required. By connecting a
single additional SITOP power 20, increased output and redundancy are achieved at the same time (if one of the three power
supplies no longer supplies an output voltage, the remaining two
20 A power supplies are sufficient to provide a total load current
of 40 A).

General notes on the diodes


The diodes should be intended for maximum dynamic current.
This may be the dynamic current for starting on short-circuit or
the dynamic current in case of short-circuit in operation (the
higher value of both should be taken from the relevant technical
specifications).

Example 2
Two SITOP power with 40 A rated output current (Order No.:
6EP1437-2BA10) are connected in parallel. The dynamic current in case of short-circuit in operation is approx. 70 A
for 600 ms, the RMS value is < 54 A.

To be able to dissipate the considerable power loss of the decoupling diodes (current x diode conducting-state voltage
drop), the diodes must be equipped with adequately dimensioned heatsinks.

Thus, for safety reasons, the diodes should feature a current rating of 100 A, the heatsink should be rated at the maximum possible continuous current (see technical specifications: current
limitation) of 54 A x diode conducting-state voltage.

An additional safety reserve is useful, because the output capacitor in the SITOP power supply provides an additional peak
current in case of a short-circuit. This additional current, however, lasts only for a few milliseconds and is therefore within a time
range (< 8.3 ms, permissible surge current for diodes), during
which diodes may be subjected to a multiple of their rated current.

Diode type
For SITOP power 40 (also for SITOP power 10 A, 20 A and
30 A), for example, the ISOTOP module BYV 54V-50 (50 V reverse voltage) is suitable.
7 Manufacturer: SGS Thomson

Example 1
Two single-phase SITOP power with 10 A rated output current
(Order No.: 6EP1334-2BA00) are connected in parallel. The dynamic current for starting on short-circuit is approx. 38 A for 200
ms.

Advantage:
Each module contains two diodes isolated from each other and
from the baseplate with a DC current rating I F AV of 50 A each;
the RMS value I F RMS is 100 A. For current load of 55 A the voltage drop is only approx. 0.8 V.

Thus, for safety reasons the diodes should feature a current rating of 40 A, the heatsink should be rated at the maximum possible current of 21 A (RMS sustained short-circuit current) x diode
conducting-state voltage.

Note:
The ISOTOP module
BYV 54V-200 (200 V reverse voltage), usually available from distributors, is also suitable.

14/12

Siemens KT 10.1 2002

Distributor: e. g. Spoerle

Technical information and configuring notes


Connection in series
Battery charging

Connection in series for increased voltage


To produce a load voltage of 48 V DC, up to two 24 V SITOP
power supplies of the same type can be connected in series.
The SITOP power outputs L+ and M are isolated from PE at a
minimum of 60 V DC (clearances in air and leakage paths as
well as RI suppression capacitors at L+ and M with respect to
PE), so that there is a choice of grounding the following points
for this type of series connection (see figure):
7

M of the lower SITOP power (results in + 48 V DC in respect to


PE)

The middle M/L+ between both SITOP power


(results in 24 V DC in respect to PE)

L+ of the upper SITOP power (results in - 48 V DC in respect


to PE)

Note:
In case of malfunctions, the continuously permissible SELV of a
maximum of 60 V DC cannot be ensured for an in-series connection of two units.
The purpose of the diodes V1 and V2 is to protect the output
electrolytic capacitor in the SITOP power from a reverse voltage
> 1 V.
On account of the rise times which are not absolutely simultaneous (even when the units are activated with a common power
switch, usually starting delay differences of some 10 ms may occur) the faster SITOP power unit supplies current from its L+ output to the M input of the slower unit, thus theoretically reversing
the charge of its output electrolytic capacitor unacceptably.
Due to internal LC filters, the internal rectifier diode on the secondary side of the slower SITOP power receives this current a
few milliseconds later so that the external diode of each SITOP
power with its anode connected to M and cathode connected to
L+ may never be omitted. These diodes, however, are only subjected to dynamic load so that the surge current rating of 8.3 ms
(specified in the data sheets of suitable diodes) can serve as a
basis for design rating and cooling of the diodes with heatsinks
is usually not required.

Two SITOP power supplies connected in series for doubled voltage

Example
Two single-phase SITOP power supplies with 10 A rated output
current (Order No.: 6EP1334-2BA00) are to be connected in series for increased output. They supply a dynamic current of approx. 38 A for 200 ms when starting on short-circuit (or e. g. load
with high-capacitance input capacitor which initially represents
a short-circuit).
An example for suitable diodes V1 and V2 is the SB 340 type1)
(Schottky diode with axial leads, case DO-201AD with approx.
5.3 mm in diameter and approx. 9.5 mm case length).
The permissible reverse voltage is 40 V, the stationary DC current rating I F AV is 3 A, the dynamic surge current rating I F SM
decisive in this case is above 100 A for 8.3 ms and therefore sufficient for SITOP power 10.
This diode 1) may also be used for SITOP power supplies with
lower rated output current (then, however, overrated).
7
7

Manufacturer: General Instrument


Distributor: e. g. RS Components Spoerle

Battery charging with SITOP power


In case of overload (e. g. discharged 24 V lead accumulator),
the three-phase SITOP power 40 (Order No. 6EP1437-3BA00)
with stabilized output voltage settable in the range of 24.0 to
28.8 V supplies a constant output current of approx. 43 A. If the
V-I-current characteristic is set to parallel operation, the battery
is charged with approx. 43 A constant current until approx. 95 %
of the set SITOP output voltage is reached. Then the charging
current decreases continuously from 43 A at 95 % of the set output voltage to approx. 0 A (or self-discharging current of the battery) at 100 % of the set output voltage (i. e. load line in this
range).

We recommend to use a diode suitable for 43 A with at least 40


reverse voltage in series (anode connected to the +output of SITOP power, cathode to positive pole of the battery) for countervoltage and reverse battery protection.
For an end-of-charge voltage of 27.0 V DC (usually at 20 C to
30 C battery temperature; however, manufacturer's specifications must be observed!) and e. g. 0.8 V voltage drop at the diode SITOP power has to be set to 27.8 V with no load.

General notes on using SITOP power as battery charger


When implementing SITOP power as battery charging device,
the specifications of VDE 0510 or relevant national regulations
must be observed. Furthermore, sufficient ventilation must be
provided for the battery. SITOP power is designed as a built-in
unit. It must therefore be mounted in an appropriate enclosure to
provide protection.

The end-of-charge voltage should be set to the value recommended by the manufacturer (depending on the battery temperature). The ideal lead accumulator temperature is between +20
and 30 C, the recommended end-of-charge voltage is then usually approx. 27 V.

1) We cannot take any responsibility for the diode recommendations set forth above.

Siemens KT 10.1 2002

14/13

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

Examples
With unstabilized rectifiers (power transformer equipped with
rectifier) the output usually had to be protected with a suitable
fuse so that its rectifier diodes would not fail in the event of an
overload or a short-circuit (this would destroy the DC loads due
to the resulting alternating voltage and lead to serious damage
in most cases). Stabilized SITOP power supplies are equipped
with an integrated electronic short-circuit protection complying
with DIN VDE 0113 Part 1, Section 7.2.9 (November 1998) or EN
60204-1 relating to electric equipment of machines. In case of
overload or a short-circuit it protects the SITOP power and the
24 V DC loads it automatically supplies against excess current.

Example 1: No fusing
Fusing the secondary side (24 V DC) for protecting the load circuits and lines is not required with SITOP power if the cross-sections are selected for the maximum possible RMS value of the
SITOP power output current. Depending on the event (short-circuit or overload) this may either be the short-circuit RMS value
or the current limitation value.
7

Example SITOP power 20 (Order No.: 6EP1336-2BA00)


Rated current 20 A
Short-circuit RMS value < 22 A
Current limitation approx. 22 A

The technical specifications usually specify typical values, maximum values are approx. 2 A above the typical value.
7

The example is calculated on the basis of approx. 22 A + 2 A


= 24 A instead of the exact short-circuit RMS value/currentlimitation value.

Example 2: Reduced cross-sections


If smaller cross-sections are used than specified in DIN VDE
0113 Part 1 or EN 60204-1, the 24 V loads must be provided with
appropriate line protection (see DIN VDE 0113 Part 1 or EN
60204-1).
It is then of no importance whether SITOP power changes into
switched-mode (low-impedance short-circuit) or not (overload
only), because the load supply is reliably protected against an
overload by the circuit-breaker in the line.
Example 3: Selectivity in case of malfunctions
In cases in which, for example, a load failing due to a short-circuit has to be detected quickly or interrupted selectively in any
event before SITOP power changes to switched-mode operation
(in switched-mode operation voltage would automatically be interrupted for all other 24 V DC loads for a few seconds until automatic restart) the electronic diagnosing module SITOP select
(Order No.: 6EP1961-2BA00, see section 9) or suitable circuit
breakers may be connected in series to the loads.
The basis for selecting the circuit-breaker is the short-circuit current - which is above the rated current - supplied by SITOP power in case of a short-circuit during operation for at least 100 ms
without interruption (values can be found in the relevant technical specifications under "Output, dyn. V/I for short-circuit in operation").
It is not easy to specify the amount of the SITOP power short-circuit current flowing into the usually not ideal "short-circuit" and
the amount flowing into the remaining loads.

14/14

Siemens KT 10.1 2002

Example 3a
The ideal case is a very low-impedance short-circuit, because
almost the entire short-circuit current flows through the circuitbreaker and only a low current through the remaining loads.
Example 3b
The opposite is a rather high-impedance "short-circuit" or small
overload, because the SITOP power output voltage does not
drop considerably and therefore the remaining loads continue to
consume almost the same current. Only the difference resulting
from dyn. V/I minus rated current of the remaining loads is available for tripping the circuit-breaker.
Example 3c
The most common case in practice will usually be between case
3a (low-impedance short-circuit) and case 3b (small overload).
For an approximation it can be assumed that the SITOP power
output voltage drops to approx. 8 V during the "short-circuit" (this
does not apply to particularly long load cables with small crosssection; in this case the resulting SITOP power output voltage
should be calculated by multiplying I dyn. V/I x R total. R total results
from the parallel connection of all connected load resistances
with the conductor resistance of the short-circuit or from the reciprocal of all added load conductivity values).
Knowing the resulting SITOP power output voltage during the
short-circuit, it is still not easy to specify the amount of current
consumed by the remaining loads at the reduced voltage as at
least three different cases must be distinguished:
7

Ohmic loads
They consume less current in proportion to the voltage, i. e.
half the rated current at half the voltage, one third of the rated
current at one third of the rated voltage.

Inductive loads
Even though the short-circuit causes the voltage to drop from
24 DC to e. g. 8 V DC, the current consumption initially remains the same, because the current cannot change suddenly in an inductive load. In practice inductive loads (e. g.
contactors, solenoid valves etc.) have a copper wire resistance of the coil as resistive component reducing the current
according to the known function i (t) = D V/R x e-t/ . The resistance can be calculated with the rated current consumption (R
= V/I rated), the time constant is the ratio of inductance L/R. The
inductance of such loads is usually not known (ask the manufacturer if necessary), most common are values in the 10 mH
range.
Typical example
1.2 A rated current at 24 V DC R = 24 V/1.2 A = 20 O.
Inductance approx. 20 mH time constant t = 20 mH/20 O =
1 ms. Voltage step of e. g. 24 V (low-impedance short-circuit)
after a time of e. g. 3 ms, the current in the inductive loads
has dropped to the value = D V/R x e-t/ = 24 V/20 O x
e-t/ = 1.2 A x e-3 ms/1 ms = I rated x e-3 N 0.05 x I rated, or only
5 %.

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

Examples (continued)
A delay of 3 ms can be neglected for the tripping of circuitbreakers so that typical ohmic-inductive loads can be treated
as ohmic loads by approximation.
If, for example, the SITOP power output voltage drops from 24
V to 8 V, a typical ohmic-inductive resistor consumes only one
third of the rated current after a few milliseconds.
7

Capacitive/electronic loads
Almost every electronic 24 V DC load (e. g. DC/DC converter
24 V DC to 5 V DC) features a capacitor in its input circuit for
smoothing the input voltage and serving as a back-up capacitor or energy storage (usually some 100 to 10.000 mF aluminum electrolytic capacitors).
If a short-circuit causes the SITOP power output voltage to
drop suddenly, these electronic loads usually consume no
current for approx. 10 to 20 ms, because the load back-up capacitor supplies the load. Typical circuit-breakers complying
with IEC 898 (Siemens types) usually trip after approx. 12 ms
(IEC 898 prescribes tripping after less than 100 ms) with corresponding excess current (10 times rated AC or approx. 14
times DC with Characteristic C, 5 times rated AC or approx. 7
times DC with Characteristic B, 3 times rated AC or approx. 5
times DC with Characteristic A). Thus, such electronic 24 V
DC loads can almost be neglected. If, however, this n times
rated current does not flow through the circuit-breaker to be
tripped, such loads can by no means be neglected for the following reason. Up to the minimum permissible input voltage
(usually approx. 18 V DC, in some cases approx. 10 V DC),
electronic 24 V DC loads show static behavior like negative resistors; at half the input voltage they do not consume half the
current (like a resistor), but twice the current.

Estimation for example 3c


The following values are assumed by approximation:
7

SITOP power is loaded with the rated current or 100 % of the


rated output power before the short-circuit (an additional safety reserve of 0.3 x rated output current for tripping circuit
breakers is provided if the usual average of approx. 70 % of
the rated output power is supplied).

SITOP power output voltage drops to approx. 8 V during the


short-circuit.

An estimated 60 % of the loads are ohmic or ohmic-inductive.


At approx. 8 V they consume only one third of their rated current so that approx. 20 % of the SITOP power rated output current still flow into these loads in case of a short-circuit.

An estimated 40 % of the loads are electronic 24 V DC loads.


If the current required for immediate tripping (typ. 12 ms tripping time with 14 times rated tripping DC in circuit-breakers of
Characteristic C according to IEC 898 or 7 times rated tripping
DC in circuit-breakers of Characteristic B or 5 times rated tripping DC in circuit-breakers of Characteristic A) starts to flow,
these loads consume considerably less current on average
during the first 12 ms.
For safety reasons 30 % of the SITOP power rated output current are assumed for this calculation. Together with the 20 %
assumed above for ohmic or ohmic-inductive loads, a total of
50 % of the SITOP power rated output current do not flow
through the circuit-breaker to be tripped.
Note: If the current required for immediate tripping (typ. 12
ms) does not reliably start to flow, these electronic loads consume up to twice the rated current (at 12 V) on average, so
that for safety reasons 80 % of the SITOP power rated output
current are assumed for the calculation in this case. Together
with the 20 % assumed above for ohmic or ohmic-inductive
loads, the total of 100 % of the SITOP power rated output current does not flow through the circuit-breaker to be tripped. As
in example 3b, only the difference dyn. V/I minus rated current
of the remaining loads is available for tripping the circuitbreaker.

Result for example 3c


(average case in practice)
7

With immediate tripping (typ.12 ms tripping time at 14 times


rated tripping DC in circuit-breakers of Characteristic C according to IEC 898 or 7 times rated tripping DC in circuitbreakers of Characteristic B or 5 times rated tripping DC in circuit-breakers of Characteristic A), the difference dyn. V/I minus 50 % of the SITOP power rated output current is available
for tripping the circuit-breaker.

With lower short-circuit current flowing through the circuitbreaker, only the difference dyn. V/I minus 100 % of the SITOP
power rated output current should be taken as a basis for selecting the circuit-breaker for safety reasons.
The same applies to rather high-impedance "short-circuits"
(see example 3b).

Siemens KT 10.1 2002

14/15

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

Selection
Procedure for selecting circuit-breakers for the 24 V DC output circuit
7

The rated current of circuit-breakers according to IEC 898


should be as close as possible to or just above the maximum
static load input current (see DIN VDE 0113 Part 1 or EN
60204-1).
Example
Rated load current = 2.2 A,
Maximum load input current = 2.8 A:
3 A circuit-breaker.
Note
The current consumed by 24 V DC loads on unstabilized
power supplies can usually deviate by approx. 25 % from the
rated value. By implementing SITOP power, this fluctuation
range is reduced to only a few percent allowing for considerably better calculation. With SITOP power, the current consumption of most loads usually deviates by no more than 5
% from the rated value.

14/16

Siemens KT 10.1 2002

Expected excess load currents should be covered by selecting the suitable tripping characteristic. For circuit-breakers
according to IEC 898/EN 60898 (DIN VDE 0641 Part 11) the
following applies in principle:
Low excess inrush load current = Characteristic A to B
High excess inrush load current = Characteristic
C to D
Immediate tripping (< 100 ms, typ. 12 ms) should always be
aimed at. In general, the difference dyn. V/I minus 50 % of
the SITOP power rated output current is available for this
purpose. Please refer to the following tables for suitable circuit-breakers.

Important
If the short-circuit current required for immediate tripping is not
achieved, only the difference dyn. V/I minus 100 % of the SITOP
power rated output current should be taken as the basis for safety reasons, in particular when connected electronic 24 V DC
loads (e. g. DC/DC converter) consume a total of more than 30
% of the SITOP power rated output current. If this difference dyn.
V/I minus 100 % of the SITOP power rated output current is not
sufficient to trip the circuit-breaker within the time during which
SITOP power supplies the current dyn. V/I without interruption
(or switched-mode operation), there is no selectivity.

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

Order specifications and tripping characteristics for single-pole circuit-breakers 5SX2


According to IEC 898/EN 60898 (DIN VDE 0641 Part 11), suitable for up to 55 V DC (250 V AC, rated breaking capacity 6,000 A)
Rated current Tripping
characteristic

Order No.

Range of immediate tripping < 100 ms for


operation with DC (AC)

Required DC for immedi- Required DC for immediate tripping in


ate tripping in
< 100 ms
approx. 12 ms

Type A

5SX2 101-5

DC: 2 to 5 (AC: 2 to 3) x Irated

to

Type C

5SX2 101-7

DC: 5 to 14 (AC: 5 to 10) x Irated

to 14

Type A

5SX2 115-5

DC: 2 to 5 (AC: 2 to 3) x Irated

3.2 to

1.6 A

A DC

A DC

A DC

14

A DC

A DC

A DC

1.6 A

Type C

5SX2 115-7

DC: 5 to 14 (AC: 5 to 10) x Irated

to 22.4 A DC

22.4 A DC

Type A

5SX2 102-5

DC: 2 to 5 (AC: 2 to 3) x Irated

to 10

A DC

10

A DC

Type C

5SX2 102-7

DC: 5 to 14 (AC: 5 to 10) x Irated

10

to 28

A DC

28

A DC

Type A

5SX2 103-5

DC: 2 to 5 (AC: 2 to 3) x Irated

to 15

A DC

15

A DC

Type C

5SX2 103-7

DC: 5 to 14 (AC: 5 to 10) x Irated

15

to 42

A DC

42

A DC

Type A

5SX2 104-5

DC: 2 to 5 (AC: 2 to 3) x Irated

to 20

A DC

20

A DC

Type C

5SX2 104-7

DC: 5 to 14 (AC: 5 to 10) x Irated

20

to 56

A DC

56

A DC

Type A

5SX2 106-5

DC: 2 to 5 (AC: 2 to 3) x Irated

12

to 30

A DC

30

A DC

Type B

5SX2 106-6

DC: 3 to 7 (AC: 3 to 5) x Irated

18

to 42

A DC

42

A DC

Type C

5SX2 106-7

DC: 5 to 14 (AC: 5 to 10) x Irated

30

to 84

A DC

84

A DC

10

Type A

5SX2 110-5

DC: 2 to 5 (AC: 2 to 3) x Irated

20

to 50

A DC

50

A DC

10

Type B

5SX2 110-6

DC: 3 to 7 (AC: 3 to 5) x Irated

30

to 70

A DC

70

A DC

10

Type C

5SX2 110-7

DC: 5 to 14 (AC: 5 to 10) x Irated

50

to 140

A DC

140

A DC

16

Type A

5SX2 116-5

DC: 2 to 5 (AC: 2 to 3) x Irated

32

to 80

A DC

80

A DC

16

Type B

5SX2 116-6

DC: 3 to 7 (AC: 3 to 5) x Irated

48

to 112

A DC

112

A DC

16

Type C

5SX2 116-7

DC: 5 to 14 (AC: 5 to 10) x Irated

80

to 224

A DC

224

A DC

Ordering specifications and tripping characteristic of Siemens single-pole circuit-breaker terminals type 8WA1 011-...
Suitable for up to 60 V DC (250 V AC)
The following space-saving circuit-breaker terminals for mere
short-circuit protection can only be snap-mounted on DIN rail EN
50022-35x15. They are also available with an auxiliary switch
(1 NO contact and 1 NC contact) and feature higher sensitivity
than circuit breakers according to IEC 898 (EN 60898), type B.

The circuit-breaker rated value must therefore be above the load


inrush current peak value. In general, however, the first three milliseconds of the load inrush current may be ignored, because no
less than 20 to 100 times the rated current is required to trip the
circuit-breaker terminals during this period of time.

Tripping times/ranges are within narrower tolerances than those


of circuit breakers. When operated with DC, these circuit-breaker terminals do not trip at currents below the rated current, from
1.1 times the rated current, the circuit-breaker terminal may trip
after as little as 100 ms.

The circuit-breaker terminals already trip after 40 ms at 1.2 to


1.9 times of the rated DC.

The circuit-breaker terminals already trip after 20 ms at 1.7 to


2.6 times of the rated DC.

The circuit-breaker terminals already trip after 12 ms at 2.2 to


3.8 times of the rated DC.

For more detailed specifications refer to catalog NS K.


Rated current DC

Order No.
without auxiliary switch

2A
4A
6A
10 A

8WA1 011-1SF25
8WA1 011-1SF26
8WA1 011-1SF27
8WA1 011-1SF28

Order No.
with auxiliary switch
1NO + 1NC
8WA1 011-6SF25
8WA1 011-6SF26
8WA1 011-6SF27
8WA1 011-6SF28

Required DC for immediate tripping in


40 ms
2.4 to 3.8 A DC
4.8 to 7.6 A DC
7.2 to 11.4 A DC
12 to 19 A DC

Required DC for immediate tripping in


20 ms
3.4 to 5.2 A DC
6.8 to 10.4 A DC
10.2 to 15.6 A DC
17 to 26 A DC

Required DC for immediate tripping in approx.


12 ms
4.4 to 7.6 A DC
8.8 to 15.2 A DC
13.2 to 22.8 A DC
22 to 38 A DC

Note:
The electronic diagnosis module SITOP select (Order No.
6EP1961-2BA00, see section 9) is also suitable for selective fusing of 24 V DC load circuits.

Siemens KT 10.1 2002

14/17

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

SITOP power/trippable circuit-breakers in the 24 V DC output circuit


Technical specifications

Type
Order No.
Input
Rated voltage Vin rated
Output
Rated voltage Vout rated
Rated current Iout rated
Dyn. V/I with short-circuit in operation, typ.
Tripping of output m.c.b
SITOP, dyn. V/I 50 % Iout rated, typ.
CBs to IEC 898, type 5SX2 1.., selectively trippable in approx. 12 ms

5A
6EP1 333-2BA00/
6EP1 333-2AA00
Single-phase
120/230 V AC
Stabilized, floating direct voltage
24 V DC
5A
20 A for 350 ms

10 A
6EP1 334-2BA00/
6EP1 334-2AA00

24 V DC
10 A
38 A for 200 ms

The following are usually available for selective tripping in practice:


17.5 A for 350 ms
33 A for 200 ms
1 A Type A (trips at 5 A DC typ. after 12 ms)
1 A Type C (trips at 14 A DC typ. after 12 ms)
1.6 A Type A (trips at 8 A DC typ. after 12 ms)

1.6 A Type C (trips at 22.4 A DC


typ. after 12 ms)
2 A Type A (trips at 10 A DC typ. after 12 ms)

2 A Type C (trips at 28 A DC typ.


after 12 ms)
3 A Type A (trips at 15 A DC typ. after 12 ms)

4 A Type A (trips at 20 A DC typ.


after 12 ms)
6 A Type A (trips at 30 A DC typ.
after 12 ms)

SIEMENS CB terminals, type


8WA1 011..., selectively trippable in approx. 12 ms

2 A Order No. 8WA1 011-1SF25


(trips at 7.6 A DC after 12 ms max.)
4 A Order No. 8WA1 011-1SF26
(trips at 15.2 A DC after 12 ms max.)

6 A Order No. 8WA1 011-1SF27


(trips at 22.8 A DC after
12 ms max.)

in 20 ms

Note
The electronic diagnosis module SITOP select (Order No.
6EP1961-2BA00, see section 9) is also suitable for selective fusing of 24 V DC load circuits.

14/18

Siemens KT 10.1 2002

10 A Order No. 8WA1 011-1SF28


(trips at 26 A DC after
20 ms max.)

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

SITOP power/trippable circuit-breakers in the 24 V DC output circuit


Technical specifications
Type
Order No.
Input
Rated voltage Vin rated
Output

20 A
6EP1 436-2BA00
Three-phase
400 to 500 V three-phase AC
Stabilized, floating direct voltage

40 A
6EP1 437-2BA10
Three-phase
400 to 500 V three-phase AC

Rated voltage Vout rated


Rated current Iout rated
Dyn. V/I with short-circuit in operation, typ.
Tripping of output m.c.b
SITOP, dyn. V/I 50 % Iout rated, typ.
CBs to IEC 898, type 5SX2 1.., selectively trippable in approx. 12 ms

24 V DC
20 A
Constant current approx. 30 A

24 V DC
40 A
70 A for 600 ms

SIEMENS CB terminals, Type


8WA1 011..., selectively trippable in approx. 12 ms

The following are usually available for selective tripping in practice:


20 A (without interruption)
50 A for 600 ms
1 A Type A (trips at 5 A DC typ. after 12 ms)
1 A Type C (trips at 14 A DC typ. after 12 ms)
1.6 A Type A (trips at 8 A DC typ. after 12 ms)

1.6 A Type C (trips at 22.4 A DC


typ. after 12 ms)
2 A Type A (trips at 10 A DC typ. after 12 ms)

2 A Type C (trips at 28 A DC typ.


after 12 ms)
3 A Type A (trips at 15 A DC typ. after 12 ms)

3 A Type C (trips at 42 A DC typ.


after 12 ms)
4 A Type A (trips at 20 A DC typ. after 12 ms)

6 A Type A (trips at 30 A DC typ.


after 12 ms)

6 A Type A (trips at 42 A DC typ.


after 12 ms)

10 A Type A (trips at 50 A DC
typ. after 12 ms)
2 A Order No. 8WA1 011-1SF25
(trips at 7.6 A DC after 12 ms max.)
4 A Order No. 8WA1 011-1SF26
(trips at 15.2 A DC after 12 ms max.)

6 A Order No. 8WA1 011-1SF27


(trips at 22.8 A DC after
12 ms max.)

10 A Order No. 8WA1 011-1SF28


(trips at 38 A DC after
12 ms max.)

Note
The electronic diagnosis module SITOP select (Order No.
6EP1961-2BA00, see section 9) is also suitable for selective fusing of 24 V DC load circuits.

Siemens KT 10.1 2002

14/19

Technical information and configuring notes


Circuit-breakers in the 24 V DC output circuit,
selectivity

SITOP power/trippable circuit-breakers in the 24 V DC output circuit


Technical specifications
Type
Order No.
Input
Rated voltage Vin rated
Output

20 A
6EP1 436-3BA00
Three-phase
400 to 500 V three-phase AC
Stabilized, floating direct voltage

40 A
6EP1 437-3BA00
Three-phase
400 to 500 V three-phase AC

Rated voltage Vout rated


Rated current Iout rated
Dyn. V/I with short-circuit in operation, typ.
Tripping of output m.c.b
SITOP, dyn. V/I 50 % Iout rated, typ.
CBs to IEC 898, type 5SX2 1.., selectively trippable in approx. 12 ms

24 V DC
20 A
Approx. 60 A for 25 ms

24 V DC
40 A
Approx. 100 A for 25 ms

SIEMENS CB terminals, Type


8WA1 011..., selectively trippable in approx. 12 ms

The following are usually available for selective tripping in practice:


50 A for 25 ms
80 A for 25 ms
1 A Type A (trips at 5 A DC typ. after 12 ms)
1 A Type C (trips at 14 A DC typ. after 12 ms)
1.6 A Type A (trips at 8 A DC typ. after 12 ms)
1.6 A Type C (trips at 22.4 A DC typ. after 12 ms)
2 A Type A (trips at 10 A DC typ. after 12 ms)
2 A Type C (trips at 28 A DC typ. after 12 ms)
3 A Type A (trips at 15 A DC typ. after 12 ms)
3 A Type C (trips at 42 A DC typ. after 12 ms)
4 A Type A (trips at 20 A DC typ. after 12 ms)

4 A Type C (trips at 56 A DC typ.


after 12 ms)
6 A Type A (trips at 30 A DC typ. after 12 ms)
6 A Type B (trips at 42 A DC typ. after 12 ms)
10 A Type A (trips at 50 A DC typ. after 12 ms)

10 A Type B (trips at 70 A DC
typ. after 12 ms)

16 A Type A (trips at 80 A DC
typ. after 12 ms)
2 A Order No. 8WA1 011-1SF25
(trips at 7.6 A DC after 12 ms max.)
4 A Order No. 8WA1 011-1SF26
(trips at 15.2 A DC after 12 ms max.)
6 A Order No. 8WA1 011-1SF27
(trips at 22.8 A DC after 22,8 ms max.)
10 A Order No. 8WA1 011-1SF28
(trips at 38 A DC after 12 ms max.)

Note
The electronic diagnosis module SITOP select (Order No.
6EP1961-2BA00, see section 9) is also suitable for selective fusing of 24 V DC load circuits.

14/20

Siemens KT 10.1 2002

125

124
130

Dimension drawings

15/2

SITOP power single-phase

15/7

SITOP power two-phase

15/7

SITOP power three-phase

15/10

SITOP power
Uninterruptible
power supply

15/11

SITOP power, battery module

15/12

Alternative voltages
AS interface power supplies

15/13

LOGO!Power

15/14

Accessories

Siemens KT 10.1 2002

15/1

Dimension drawings
SITOP power single-phase

Dimension drawings

Dimensions (in mm)


6EP1 331-2BA10
6EP1 731-2BA00

7.5

1 2 3
L1 N PE

G_KT01_en_00008

ca 86.6

80

35

SITOP
power
6EP1331-2BA00
1 2

Q6MH

OK

(L+)(M) (M)
4 5 6

22.5

91
6EP1 331-2BA00

53 - 53.5

50

SITOP
power

125

129.6

6EP1331-2BA00

1 2 3 4 5

L1
N
PE

G_KT01_en_00069

120V
AC
L+
M
M
OK

124
130

6ES7 307-1BA00-0AA0
135

50

36

125

1)

1) Mounting adapter for


DIN rail optional

15/2

Siemens KT 10.1 2002

Dimension drawings
SITOP power single-phase
Dimensions (in mm)
6EP1 732-0AA00
6EP1 332-1SH12
6EP1 332-1SH22
80

120

36

G_KT01_en_00070

164

135

149

65

6EP1 332-1SH31

G_KT01_en_00071

67.3

62

80

147.4

160

Siemens KT 10.1 2002

15/3

Dimension drawings
SITOP power single-phase
Dimensions (in mm)
6EP1 333-2BA00
6EP1 333-2AA00

53 - 53.5

75

SITOP

125

129.6

power

6EP1333-2BA00

1 2 3 4 5

L1
N
PE

G_KT01_en_00072

120V
AC
L+
M
M
OK

124
130

6ES7 305-1BA80-0AA0
6ES7 307-1EA00-0AA0
6ES7 307-1EA80-0AA0
80

135

36

G_KT01_en_00073

125

1)

1) Mounting adapter for


DIN rail optional

6EP1 333-1AL11
164

69
2

54

130
35.25

G_KT01_en_00074

60

15/4

Siemens KT 10.1 2002

136.5

160

DIN rail EN 50022 35 x 7.5

Dimension drawings
SITOP power single-phase
Dimensions (in mm)
6EP1 334-2BA00
6EP1 334-2AA00
100

SITOP
power

129.6

6EP1334-2AA00

1 2 3 4 5

L1
N
PE

G_KT01_en_00075

120V
AC
L+
M
M
OK

6EP1 334-2CA00
8,8

110

133.5

103.5
53.5

126.5

G_KT01_en_00066

197

1)
265

ia.

4 ...10 d

283
10.2

dia.

158.4

1)

5.5

dia

134.6

140
5.4

145.4

1) Clips
(only in connection with accessory
connector seal 6EP1971-2CA00)

22.8

160.5
214

Siemens KT 10.1 2002

15/5

Dimension drawings
SITOP power single-phase
Dimensions (in mm)
6ES7 307-1KA00-0AA0
6EP1 334-1SH01
135

200

36

G_KT01_en_00077

125

1)

1) For 6ES7307-1KA00-0AA0
Mounting adapter for DIN rail optional

6EP1 334-1AL11
224

54

15/6

Siemens KT 10.1 2002

130
35.25

G_KT01_en_00078

DIN rail EN 50022 35 x 7.5

220

60

136.5

69

Dimension drawings
SITOP power, single-phase,
two-phase, three-phase
Dimensions (in mm)
6EP1 336-2BA00
6EP1 434-2BA00
6EP1 436-2BA00
92
9

280

L2

L3

3-ph. 400V - 500V AC

PE

53 - 53.5

L1

50 / 60 Hz

L2

INPUT

L3
PE

125

3-ph. 400V - 500V AC

6EP1 436-2BA00
1 2 3 4 5 6

OUTPUT
22,8V - 26,4V

CAUTION !
READ INSTRUCTION MANUAL !

24V DC / 20A
L+ M M
OK
- Adjust +
24V - 26,4V

6.2

L1

power

G_KT01_en_00079

SITOP

6EP1 437-2BA00
6EP1 437-2BA10
6EP1 536-2AA00
280

92
8.8
L2

L3

3-ph. 400V - 500V AC

PE

53 - 53.5

L1

50 / 60 Hz

INPUT

SITOP

22,8V - 26,4V

CAUTION !
READ INSTRUCTION MANUAL !

24V DC / 40A
L+ M M
OK
- Adjust +
22,8V - 26,4V

4.9

6EP1437-2BA10
1 2 3 4 5 6

OUTPUT

G_KT01_en_00080

180

power

6.2

Siemens KT 10.1 2002

15/7

Dimension drawings
SITOP power three-phase
Dimensions (in mm)
6EP1 436-3BA00

160

120,5

SITOP

Q6XX

DC 24V/20A

... - ... V

24V OK
OVERLOAD

L1

L2

L3

50/60Hz

PE

SHUT DOWN

26,87

3AC 400V - 500V

G_KT01_de_00064a

INPUT

OUTPUT

125

6EP1 436-3BA00
1 2 3 4 5
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

6,1

6EP1 437-3BA00

240

120,5

SITOP

6EP1 437-3BA00

Q6XX

24V OK
OVERLOAD

L1

L2

L3

50/60Hz

PE

SHUT DOWN

15/8

Siemens KT 10.1 2002

26,87

3AC 400V - 500V

G_KT01_de_00065

INPUT

OUTPUT
DC 24V/40A

125

1 2 3 4 5
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

6,1

Dimension drawings
SITOP power three-phase
Dimensions (in mm)
6EP1 961-3BA10

70

120,5

6EP1 961-3BA00
1 2 3 4 5
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII

G_KT01_de_00060a

Q6XX

125

SITOP

6EP1 961-3BA00

116

G_KT01_de_00061a

125

26

Siemens KT 10.1 2002

15/9

Dimension drawings
SITOP power DC UPS module
Dimensions (in mm)
6EP1 931-2EC01
6EP1 931-2EC11
75

o.k.

Bat
Alarm

129

power
On / Off

n.c.

Alarm

DC-USV-Modul 50
6EP1 931-2DC01
1 2 3 4 5

UBat

125

SITOP

t max.

o.k.

t
+160s
+80s
+40s
+20s
+10s
5s

Bat

UL+
X2.1 2.2

2.3 2.4 2.5

2.6 2.7 2.8 2.9

15A

G_KT01_en_00081

In

L+

X1.1

X1.2

L+

X1.3

X1.4

+Bat

X1.5

-Bat

X1.6

Out

124
130

6EP1 931-2FC01
220

60

20

52

130

power DC UPS Module 40

27.5

15/10

Siemens KT 10.1 2002

Dimension drawings
SITOP power, battery module
Drilling jigs
6EP1 935-6MD31
249

+
or

bl

84

Attention!
Fullcharged battery.
Fuse F1 must
not to fit into before
commissioning.
After assembling to top-hat-rail
2 screws M4 must be tighten.
Before disassembling
from top-hat-rail
2 screws M4 must be loosend.
G_KT01_en_00004

6EP1 935-6MD11

6EP1 935-6ME21
170

174

or bl
Attention!
Fullcharged battery.
Fuse F1 must not to fit into
before commissioning.

101

84

or bl
Attention!
Fullcharged battery.
Fuse F1 must
not to fit into before
commissioning.

15A Batterymodul-fuse F1 only in combination with


DC-USV-Modul 15 permissible.

After assembling to top-hat-rail


2 screws M4 must be tighten.

25A Batterymodul-fuse F1 only in combination with


DC-USV-Modul 40 permissible.

Before disassembling
from top-hat-rail
2 screws M4 must be loosend.

G_KT01_en_00005
G_KT01_en_00006

6EP1 935-6MF01
237

F1

101

or bl
Attention!
Fullcharged battery.
Fuse F1 must not to fit into
before commissioning.

15A Batterymodul-fuse F1 only in combination with


DC-USV-Modul 15 permissible.

12 Ah

25A Batterymodul-fuse F1 only in combination with


DC-USV-Modul 40 permissible.

G_KT01_en_00007

Siemens KT 10.1 2002

15/11

Dimension drawings
Alternative voltages, AS interface power supplies
Dimensions (in mm)
6EP1 353-0AA00
6EP1 353-2BA00

53 - 53.5

75

SITOP

125

129.6

power

1 2 3 4 5

L1
N
PE

G_KT01_en_00086

120V
AC
L+
M
M
OK

124
130

6EP1 354-1AL01

OK

125

VOLTAGE
SELECTOR

6EP1 354-1AL01

135

200

6EP1 632-1AL01
1

NSA00118a

P30
RD
BU
M30
Schirm BK

INPUT
24 V/4,2 A

14

P30
M30
Schirm
OUTPUT
30 V/2,8 A
6EP1632-1AL01 1 2 3 4 5 6

1
163

175
224

a Fixing screws:
socket head cap screws
M4x16, 8.8 to DIN 912

15/12

Siemens KT 10.1 2002

500

80

1 PE
2 P24
3 M24

52

AS-Interface
power RUN

SIEMENS

NSA00124a

SITOP
power AS-I

36

SIEMENS

Dimension drawings
LOGO!Power
Dimensions (in mm)
6EP1 311-1SH01
6EP1 321-1SH01
6EP1 331-1SH01
6EP1 351-1SH01
6EP1 351-1SH11
72

L1 N

+ +
Output
24 V/1.3 A DC

90

Input
120/230 V AC

52

LOGO!Power
G_KT01_en_00082

X 2
3 4

6EP1 311-1SH11
6EP1 322-1SH01
6EP1 332-1SH41
6EP1 352-1SH01
6EP1 352-1SH11
126

L1 N

+ +
Output
24 V/2.5 A DC

90

Input
120/230 V AC

52

X 2
3 4

G_KT01_en_00083

LOGO!Power

Siemens KT 10.1 2002

15/13

Dimension drawings
Accessories
Dimensions (in mm)
6EP1 971-1AA01
236
50

200

25

159

5.75

G_KT01_en_00084

135

147.5

25

50

100

6EP1 971-2BA00

25

G_KT01_en_00085

320

75

6.2

30

320

90

30

28

20

75

10

146

150

13

15/14

Siemens KT 10.1 2002

50
100

25

280

Service & support

Appendix

16/2

Information and
order service on the
internet and on CD ROM

16/3

Customer support

16/4

Order No. index

16/5

Subject index

16/6

SITOP contact persons

16/12

Conditions of sale and delivery

Siemens KT 10.1 2002

16/1

Appendix
Service & support
Information and order service
on the internet and on CD ROM

Appendix

A & D on the world wide web


When planning and designing
automation systems, detailed
knowledge of products to be
implemented and available
services is required. It is obvious that this information always needs to be up to date.

allowing for easy and convenient access to all required information.

The Siemens division Automation and Drives (A & D) therefore offers extensive information on the world wide web,

you will find everything you


need to know about products,
systems and services.

Extensive information combined with convenient interactive functions:


Our interactive catalogs
CA 01 and ET 01 with more
than 80 000 products give a
comprehensive overview of
the range of Siemens Automation and Drives.

After you have chosen the


products you need, simply
click for fax or online ordering.

Here, you will find everything


you need for solving problems
in automation, circuit, installation and drives engineering.
All information is integrated
into a user interface making
work easy and intuitive.

or on CD ROM:

The Siemens Mall is the virtual


Siemens AG shopping center
on the internet. Here, you
have access to an enormous
number of products presented in electronic catalogs clearly laid out with lots of information.

Efficient search options help


you to find the products you
are looking for. You can immediately check their availability.
Customized rebates and offers can be requested online.
Tracking and tracing of your
order is also possible.

Data transfer with EDIFACT


enables the whole process from selecting the products
you need to ordering to tracking your order - online on the
internet.

You will find the Siemens Mall


at:

At

http://www.siemens.de/automation

Products in our interactive catalogs

Information on the interactive


catalogs is available on the internet at

http://www.siemens.de/ automation/ca01

Automation and drives engineering, CA 01 Order No.:


E86060-D4001-A100-B5
Installation engineering, ET 01
Order No.:
E86060-D8200-A107-A2

Easy shopping in the Siemens Mall

Extensive functions support


you throughout the whole process.

16/2

Siemens KT 10.1 2002

http://www.siemens.de/ automation/mall

Appendix
Service & support
Customer support
Customer support Automation and Drives
Whether you need a service
specialist or a spare part, an
expert for support or just have
a simple question: contact the
service & support team
The team for your success.

Helpline for service and support


You need help, but are uncertain about whom to contact?
We take care that you get help
quickly.

The helplines ensure that the


right specialist near you offers
his expert support. The helpline for Germany offers support on 365 days around the
clock in German and English.

Phone: 0180 50 50 111

FAQs, tips and tricks, downloads, news

http://www.siemens.de/
automation/service&
support

Online support
Our online support offers quick
and efficient help - around the
clock, worldwide, in five languages.
Our online support offers multiple technical information:

Free manuals
Helpful programs and software
payment with SIMATIC Card

Spare parts and repair


Our worldwide network of local
spare part stockrooms reacts
quickly and reliably with modern logistics.

If you have repair or spare


part requests please contact
(in Germany):

Outside office times and on


weekends you can reach our
spare parts emergency service under this number.

Technical support is available


in German and English.

under the following numbers:

phone: 0180 50 50 446

Technical support

SITOP power hotline


The hotline for products of the
SITOP power range can be
reached
Monday to Friday
8:00 a.m. to 17:00 p.m.
(CET)

Outside these hours you can


reach our technical support
Phone: +49 (0)911 750 9990
under the following numFax: +49 (0)911 750 9991
bers:
E-mail:
sitop.hotline@fthw.siemens.de Phone: +49 (0)180 50 50 222
Fax: +49 (0)180 50 50 223
E-mail:
techsupport@ad.siemens.de

http://www.siemens.de/
automation/service&
support

Siemens KT 10.1 2002

16/3

Appendix

Order No. index


Type
3RG9
3RG9220-0AA00

page

Type
6EP1333-2BA00

9/5
6EP1334-1AL11

5SX2
5SX2...

14/17

6EP1
6EP1311-1SH01
6EP1311-1SH11
6EP1321-1SH01

13/2, 5/13
13/6, 15/13
13/2, 15/13

6EP1334-2BA00
6EP1334-2CA00

5/3, 15/6
5/2, 14/8
15/5
5/2, 14/8
15/5
5/2, 15/5

6EP1322-1SH01
6EP1331-1SH01
6EP1331-2BA00

13/6, 15/13
13/3, 15/13
2/2, 15/2

6EP1336-2BA00
6EP1351-1SH01
6EP1351-1SH11

6/2, 15/7
13/2, 15/13
13/3, 15/13

6EP1331-2BA10
6EP1332-1SH12
6EP1332-1SH22

2/2, 15/2
3/2, 15/3
3/2, 15/3

6EP1352-1SH01
6EP1352-1SH11
6EP1353-0AA00

13/6, 15/13
13/7, 15/13
10/4, 15/12

6EP1332-1SH31
6EP1332-1SH51
6EP1333-1AL11
6EP1333-2AA00

3/2, 15/3
13/7,15/13
4/3, 15/4
4/2, 14/18
15/4

6EP1353-2BA00
6EP1354-1AL01
6EP1434-2BA00
6EP1436-2BA00

10/2, 15/12
12/2, 15/12
7/6, 15/7
7/6, 14/19
15/7

16/4

6EP1334-1SH01
6EP1334-2AA00

page
4/2, 14/18
15/4
5/3, 15/6

Siemens KT 10.1 2002

Type
6EP1436-3BA00
6EP1437-2BA00
6EP1437-2BA10

page
7/2, 15/8
7/7, 15/7
7/7, 14/19
15/7

6EP1437-3BA00
7/2, 15/8
6EP1536-2AA00
6/2, 15/7
6EP1632-1AL01 12/2, 15/12
6EP1731-2BA00
6EP1732-0AA00
6EP1931-2EC01

2/2, 15/2
2/3, 15/3
8/4, 15/10

6EP1931-2EC11
8/4, 15/10
6EP1931-2FC01
8/8, 15/10
6EP1935-5MF01 8/13, 15/11
6EP1935-6MD11 8/11, 15/11
6EP1935-6MD21 8/12, 15/11
6EP1935-6MD31 8/10, 15/11
6EP1961-2BA00
9/2

Type
6EP1

page

6EP1961-3BA00
6EP1961-3BA10
6EP1971-1AA01
6EP1971-2BA00
6EP1971-2CA00

7/4, 15/9
7/4, 15/9
9/4, 15/14
9/4, 15/14
9/5

6ES5
6ES5760-2CA11

9/5

6ES7
6ES7305-1BA80-... 2/3, 15/4
6ES7307-1BA00-... 2/3, 15/2
6ES7307-1EA00-... 4/2, 15/4
6ES7307-1EA80-... 4/3, 15/4
6ES7307-1KA00-... 5/3, 15/6
6ES7390-6BA00-...
9/5
6ES7390-7BA00-...
9/5

Appendix

Subject index
Type
A
Alternative voltages
AS interface PG connection module

page
10/2
9/5

B
Battery charging with SITOP power
Battery module 12 Ah
Battery module 2.5 Ah
Battery module 3.2 Ah
Battery module 7 Ah

14/13
8/13
8/10
8/11
8/12

C
Circuit-breakers in the 24 V DC output circuit,
selectivity
Connection in parallel
Connection in series
Circular input connector, 6-pin
Customer support

14/14
14/11
14/13
9/5
16/3

D
DC power supplies, stabilized
DC power supplies, unstabilized
DC UPS module 15 A
DC UPS module 40 A
DC UPS software
Diagnosing module SITOP select
Dimension drawings
F
Fixing angle
G
General notes on the diodes
I
Information and order service on the
internet and on CD ROM
International mains voltages
in low-voltage mains
Introduction

14/2
14/2
8/2
8/6
8/14
9/2
section 15
9/4
14/12

Type
L
Line-side connection and fusing
LOGO!Power
M
Mains specifications
Mounting adapter for S7 rail
Mounting instructions
Mounting spaces and fixing options

page
14/8
13/2
14,5/5
9/5
14/10
14/10

P
Parallel connection
14/11
Planning and design aids
14/11
Potential mains interference factors and their sources
14/9
Power connector PS-CPU
9/5
Power supplies, single-phase
2/2, 3/2, 4/2, 5/2
Power supplies, three-phase
7/2
Power supplies, two-phase
6/2
S
Selection guide
Single-phase ASi power supplies, stabilized
SITOP contact persons
SITOP power dual 15 V
SITOP power flexi 120 W
SITOP power customized
Specification sheet for customized
power supplies
T
Terms of sale and delivery

1/4
12/2
16/6
10/4
10/2
11/2
11/3
16/8

U
Uninterruptible power supplies

8/2

16/2
14/5
1/2

Siemens KT 10.1 2002

16/5

Appendix
SITOP contact persons
in Europe
Austria
Bregenz
Siemens AG
Mr. Madlener
Josef-Huter-Str.6
A-6901 Bregenz
Phone +43 (0) 51707-682
Fax +43 (0) 51707 522
Email guenter.madlener@
siemens.at
Graz
Siemens AG
Mr. Krll
Straganger Str. 315
A-8054 Graz
Phone +43 (0) 51707 63922
Fax +43 (0) 51707 58672
Email josef.kroell@siemens.at
Innsbruck
Siemens AG
Mr. Hampel
Siemensstr. 24
A-6063 Rum bei Innsbruck
Phone +43 (0) 51707 67398
Fax +43 (0) 51707 54925
Email johann-georg.hampel@
siemens.at
Klagenfurt
Siemens AG
Mr. Weber
Werner v. Siemens Park 1
A-9020 Klagenfurt
Phone +43 (0) 51707 64243
Fax +43 (0) 51707 54418
Email richard.r.weber@
siemens.at
Linz
Siemens AG
Mr. Schmidt
Wolfgang-Pauli-Str. 2
A-4020 Linz
Phone +43 (0) 51707 65295
Fax +43 (0) 51707 59601
Email erich.e.schmidt@
siemens.at
Salzburg
Siemens AG
Mr. Mariacher
Innsbrucker-Bundesstr. 35
A-5020 Salzburg
Phone +43 (0) 51707 66350
Fax +43 (0) 51707 53229
Email josef.mariacher@
siemens.at
Vienna
Siemens AG
Mr. Strasser
Siemensstr. 88-92
A-1210 Wien
Phone +43 (0) 51707 23788
Fax +43 (0) 51707 53940
Email josef.strasser@siemens.at
Belarus
Minsk
Mr. Gbecke
ul. Surganova 24, Off. 405
222 012 Minsk
Tel +375 (17) 210-0396
Fax +375 (17) 210-0395
Email alexander.goebecke@
mch35.siemens.de

16/6

Belgium
Huizingen
Mr. De Coninck
Predslawinka Str. 11-13
3150 Kiew
Tel +32 (2) 536 9539
Fax +32 (2) 536 2387
Email Geert.De-Coninck@
siemens.be

Finland
Helsinki
Siemens Osakeyhti, Espoo(en)
Mr. Laajava
Majurinkatu 6
2601 Espoo
Te +358 (0) 10 511 3419
Fax +358 (0) 10 511 3474
Email jukka.laajava@siemens.fi

Bremen
Siemens AG
Mr. Krger
Universittsallee 16
28359 Bremen
Tel +49 (421) 364 2185
Fax +49 (421) 364 2249
Email Helmut.Kroeger@brm.
siemens.de

Bosnia-Herzegovina
Sarajevo
Siemens d.o.o.
Mr. Ganic
Dubrovacka 6
71000 Sarajevo
Tel +387 (33) 27 66 41
Fax +387 (33) 27 66 10
Email sadudin.ganic@siemens.ba

France
Paris
Mr. Rouault
39-47, Boulevard Ornano
93527 Saint-Denis CEDEX 2
Tel +33 (1) 4922 9309
Fax +33 (1) 4922 3951
Email Jean-Marie.Rouault@
siemens.fr

Chemnitz
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de

Bulgaria
Sofia
Mr. Ganev
Blvd. Nikola Vaptzarov 36
BG-1407 Sofia
Tel +359 (2) 965 9631
Fax +359 (2) 965 9662
Email Ivan.Ganev@siemens.bg

Germany
Aachen
Siemens AG
Mr. Schauenberg
Franz-Geuer-Str. 10
50823 Kln
Tel +49 (221) 576 2536
Fax +49 (221) 576 3151
Email Frank.Schauenberg@
koe.siemens.de

Dresden
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de

Croatia
Zagreb
Mrs. Ilic
Heinzelova 70a
10000 Zagreb
Tel +385 (1) 6105 337
Fax +385 (1) 6105 621
Email ivana.ilic@siemens.hr
Czech Republic
Brno
Siemens s.r.o.
Mr. Bocek
Technicka 15
CZ-61600 Brno
Tel +420 (5) 4119-1731
Fax +420 (5) 4119-1749
Email petr.bocek@
brno.siemens.cz
Prague
Mr. Pmmerl
Evropsk 33a
Praha 6
Te +420 (2) 3303-2410
Fax +420 (2) 3303-2492
Email werner.poemmerl@
rg.siemens.cz
Denmark
Kopenhagen
Mr. Limkilde
Borupvang 3
2750 Ballerup
Tel +45 4477 4883
Fax +45 4477 4002
Email LLK@siemens.dk
Estonia
Tallinn
Siemens AS
Mr. Kaljume
Prnu mnt. 139 C
11317 Tallinn
Tel +372 (6) 304-751
Fax +372 (6) 406-778
Email aldo.kaljumae@siemens.fi

Siemens KT 10.1 2002

Augsburg
Siemens AG
Mr. Borchert
Werner v. Siemens Str. 6
86159 Augsburg
Tel +49 (821) 2595-562
Fax +49 (821) 2595-412
Email hans-dieter.borchert@
mchr1.siemens.de
Bayreuth
Siemens AG
Mr. Fiedler
Von-der-Tann-Str. 30
90439 Nrnberg
Tel +49 (911) 654 3413
Fax +49 (911) 654 3596
Email Wolfram.Fiedler@nbg.
siemens.de
Berlin
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de
Bielefeld
Siemens AG
Mr. Knauth
Frankfurter Strasse 3d
38112 Braunschweig
Tel +49 (531) 2712 314
Fax +49 (531) 2712 416
Email bernd.knauth@bwga.
siemens.de
Braunschweig
Siemens AG
Mr. Knauth
Frankfurter Strasse 3d
38112 Braunschweig
Te +49 (531) 2712 314
Fax +49 (531) 2712 416
Email bernd.knauth@bwga.
siemens.de

Duesseldorf
Siemens AG
Mr. Schauenberg
Franz-Geuer-Str. 10
50823 Kln
Tel +49 (221) 576 2536
Fax +49 (221) 576 3151
Email Frank.Schauenberg@
koe.siemens.de
Erfurt
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de
Essen
Siemens AG
Mr. Lange
Kruppstr. 16
45128 Essen
Tel +49 (201) 816 2128
Fax +49 (201) 816 2624
Email Dieter.Lange@esn.
siemens.de
Frankfurt a. M.
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com
Freiburg
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Appendix
SITOP contact persons
in Europe (continued)
Hamburg
Siemens AG
Mr. Krger
Universittsallee 16
28359 Bremen
Tel +49 (421) 364 2185
Fax +49 (421) 364 2249
Email Helmut.Kroeger@brm.
siemens.de

Cologne
Siemens AG
Mr. Schauenberg
Franz-Geuer-Str. 10
50823 Kln
Tel +49 (221) 576 2536
Fax +49 (221) 576 3151
Email Frank.Schauenberg@
koe.siemens.de

Osnabrueck
Siemens AG
Mr. Lange
Kruppstr. 16
45128 Essen
Tel +49 (201) 816 2128
Fax +49 (201) 816 2624
Email Dieter.Lange@esn.
siemens.de

Weingarten
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Hanover
Siemens AG
Mr. Knauth
Frankfurter Strasse 3d
38112 Braunschweig
Tel +49 (531) 2712 314
Fax +49 (531) 2712 416
Email bernd.knauth@bwga.
siemens.de

Konstanz
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Regensburg
Siemens AG
Mr. Fiedler
Von-der-Tann-Str. 30
90439 Nrnberg
Tel +49 (911) 654 3413
Fax +49 (911) 654 3596
Email Wolfram.Fiedler@nbg.
siemens.de

Wetzlar
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com

Heilbronn
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Leipzig
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de

Rostock
Siemens AG
Mr. Krger
Universittsallee 16
28359 Bremen
Tel +49 (421) 364 2185
Fax +49 (421) 364 2249
Email Helmut.Kroeger@brm.
siemens.de

Wuerzburg
Siemens AG
Mr. Fiedler
Von-der-Tann-Str. 30
90439 Nrnberg
Tel +49 (911) 654 3413
Fax +49 (911) 654 3596
Email Wolfram.Fiedler@nbg.
siemens.de

Karlsruhe
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com

Magdeburg
Siemens AG
Mr. Frster
Wernerwerkdamm 5
13629 Berlin
Tel +49 (30) 386 32 303
Fax +49 (30) 386 32 543
Email Martin.Foerster@bln.
siemens.de

Saarbruecken
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com

Wuppertal
Siemens AG
Mr. Lange
Kruppstr. 16
45128 Essen
Tel +49 (201) 816 2128
Fax +49 (201) 816 2624
Email Dieter.Lange@esn.
siemens.de

Kassel
Siemens AG
Mr. Knauth
Frankfurter Strasse 3d
38112 Braunschweig
Tel +49 (531) 2712 314
Fax +49 (531) 2712 416
Email bernd.knauth@bwga.
siemens.de

Mannheim
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com

Siegen
Siemens AG
Mr. Schauenberg
Franz-Geuer-Str. 10
50823 Kln
Tel +49 (221) 576 2536
Fax +49 (221) 576 3151
Email Frank.Schauenberg@
koe.siemens.de

Great Britain
Manchester
Mr. Higham
Sir William Siemens House/
Princess Road
Manchester M20 2UR
Tel +44 (161) 446 5249
Fax +44 (161) 446 5522
Email Highamm@plcman.
siemens.co.uk

Kempten
Siemens AG
Mr. Borchert
Richard-Strauss-Str.76
81679 Mnchen
Tel +49 (89) 9221-3877
Fax +49 (89) 9221-2053
Email hans-dieter.borchert@
mchr1.siemens.de

Munich
Siemens AG
Mr. Borchert
Richard-Strauss-Str.76
81679 Mnchen
Tel +49 (89) 9221-3877
Fax +49 (89) 9221-2053
Email hans-dieter.borchert@
mchr1.siemens.de

Stuttgart
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Kiel
Siemens AG
Mr. Krger
Universittsallee 16
28359 Bremen
Tel +49 (421) 364 2185
Fax +49 (421) 364 2249
Email Helmut.Kroeger@brm.
siemens.de

Muenster
Siemens AG
Mr. Lange
Kruppstr. 16
45128 Essen
Tel +49 (201) 816 2128
Fax +49 (201) 816 2624
Email Dieter.Lange@esn.
siemens.de

Trier
Siemens AG
Mr. Wulle
Dynamostr. 4
68165 Mannheim
Tel +49 (621) 456 2661
Fax +49 (621) 456 2747
Email thomas.wulle@
siemens.com

Hungary
Budapest
Mr. Solt
Gizella ut 51-57
1143 Budapest
Tel +36 (1) 471-1717
Fax +36 (1) 471-1704
Email attila.solt@siemens.hu

Koblenz
Siemens AG
Mr. Schauenberg
Franz-Geuer-Str. 10
50823 Kln
Tel +49 (221) 576 2536
Fax +49 (221) 576 3151
Email Frank.Schauenberg@
koe.siemens.de

Nuremberg
Siemens AG
Mr. Fiedler
Von-der-Tann-Str. 30
90439 Nrnberg
Tel +49 (911) 654 3413
Fax +49 (911) 654 3596
Email Wolfram.Fiedler@nbg.
siemens.de

Ulm
Siemens AG
Mr. Rder
Weissacher Str.11
70499 Stuttgart
Tel +49 (711) 137-4059
Fax +49 (711) 137-2070
Email bernd.roeder@stgt.
siemens.de

Ireland
Dublin
Siemens Ltd.
Mr. McPhillips
8 Slaney Road
11 Dublin
Tel +353 (1) 216 2436
Fax +353 (1) 216 2499
Email john.mcphillips@siemens.ie

Greece
Athens
Mr. Marantidis
Artemidos 8
GR-15125 Amaroussio/Athen
Tel +30 (1) 6864 564
Fax +30 (1) 6864 556
Email nikolaos.marantidis@
siemens.gr

Siemens KT 10.1 2002

16/7

Appendix
SITOP contact persons
in Europe (continued)
Dublin
Siemens Ltd.
Mr. Feeley
8, Slaney Road, Glasnevin
Industrial Estate
11 Dublin
Tel +353 (1) 216 2441
Fax +353 (1) 216 2499
Email martin.feeley@siemens.ie
Italy
Bari
Mr. Gabellone
Via Lucarelli, 10/b
70124 Bari
Tel +39 (080) 50 24068
Email luca.gabellone@siemens.it
Bologna
Mr. Tosatti
Via del Gomito, 1
40127 Bologna
Tel +39 (051) 6384509
Email davide.tosatti@siemens.it
Bologna
Mr. Forghieri
Via del Gomito, 1
40127 Bologna
Tel +39 (051) 6384608
Email mauro.forghieri@siemens.it
Florence
Mr. Vessio
Via Odorico da Pordenone, 26
50127 Firenze
Tel +39 (055) 3392 201
Email domenico.vessio@
siemens.it
Milan
Mr. Bischetti
Viale Piero e Alberto Pirelli 10
20126 Milano
Tel +39 (02) 6676 3321
Fax armando.bischetti@
siemens.it
Milan
Mr. Berti
Viale Piero e Alberto Pirelli 10
20126 Milano
Tel +39 (02) 6676 2836
Email gualtiero.berti@siemens.it
Milan
Mr. Gaspari
Viale Piero e Alberto Pirelli 10
20126 Milano
Tel +39 (02) 6676 2067
Email adolfo.gaspari@siemens.it
Naples
Mr. De Sio
Via G. Quagliarello, 35/E
80146 Napoli
Tel +39 (081) 5454237
Email maurizio.desio@siemens.it
Padova
Mr. Millevoi
Viale dell Industria, 19
35129 Padova
Tel +39 (049) 8291336
Email piero.millevoi@siemens.it
Padova
Mr. Maffioli
Viale dell Industria, 19
35129 Padova
Tel +39 (049) 8291359
Email andrea.maffioli@siemens.it

16/8

Rome
Mr. D Innocenti
Via Laurentina 455
142 Roma
Tel +39 (06) 59692 285
Email dario.dinnocenti@
siemens.it
Torino
Mr. Montoli
Via Pio VII, 127
10127 Torino
Tel +39 (011) 6173 275
Email daniele.montoli@siemens.it
Latvia
Riga
Siemens SIA
Mr. Tumpelis
Vilandes iela 3
1010 Riga
Tel +371 (701) 55 18
Fax +371 (701) 55 11
Email ugis.tumpelis@siemens.fi
Lithuania
Vilnius
Siemens UAB
Mr. Laurinaitis
V. Kudirkos g.6
2009 Vilnius
Tel +370 (2) 39 1515
Fax +370 (2) 39 1579
Email rimas.laurinaitis@siemens.fi
Luxembourg
Luxembourg
Siemens S.A.
Mr. Koch
20, rue des Peupliers
2328 Luxembourg-Hamm
Tel +352 (43) 8 43-403
Fax +352 (43) 8 43-449
Email edmond.koch@siemens.lu
Netherlands
The Hague
Siemens Nederland N.V.,
Den Haag
Mr. Brunott
Prinses Beatrixlaan 26
2595 AL Den Haag
Tel +31 (0)70 333 3905
Fax +31 (0)70 333 3885
Email herm.brunott@siemens.nl
Norway
Oslo
Mr. Otterstad
stre Aker vei 90
0518 Oslo
Tel +47 2263 4164
Fax +47 2263 3390
Email dag.otterstad@siemens.no
Poland
Gdansk Sales North
Siemens Sp.z o.o.
Mr. Skicki
ul. Batorego 28-32
Gdansk Sales North
Tel +48 (58) 785 8490
Fax +48 (58) 785 8499
Email andrzej.Skicki@siemens.pl
Katowice Sales South
Siemens Sp.z o.o.
Mr. Mezydlo
ul. Dolnych Walow 7
Katowice Sales South
Tel +48 (32) 208 4130
Fax +48 (32) 208 4139
Email Tomasz.Mezydlo@
siemens.pl

Siemens KT 10.1 2002

Poznan Sales West


Siemens Sp.z o.o.
Mr. Kaysiewicz
ul. Romana Maya 1
Poznan Sales West
Tel +48 (61) 650 2823
Fax +48 (61) 650 2824
Email Maciej.Kaysiewicz@
siemens.pl
Warsaw Sales East
Siemens Sp.z o.o.
Mr. Zielinski
ul. Zupnicza 11
Warszawa Sales East
Tel +48 (22) 870 9862
Fax +48 (22) 870 9119
Email andrzej.Zielinski@
siemens.pl
Warsaw
Siemens Sp.z o.o.
Mr. Ciuk
ul. Zupnicza 11
3821 Warszawa
Tel +48 (22) 870 9145
Fax +48 (22) 870 9169
Email andrzej.ciuk@waw1.
siemens.pl
Portugal
Amadora
Siemens S. A.
Mr. Filipe
Rua Irmos de Siemens, 1
2720093 Amadora
Tel +351 (21) 417 8838
Fax +351 (21) 417 8050
Email sergio.filipe@lis1.
siemens.pt
Romania
Bukarest
Siemens S.R.L.
Mr. Razvan
Calea Pleavei Nr. 139,
Corp C, sector 6
RO 77131 Bucuresti
Tel +40 (1) 223-4296
Fax +40 (1) 223-4569
Email razvan.ioachim@
siemens.ro

Spain
Madrid
Mr. Ramn Romero
Ronda de Europa, 5
Tres Cantos (Madrid)
Tel +34 (91) 514 4761
Fax +34 (91) 514 7019
Email pssitop@ssa.siemens.es
Sweden
Stockholm
Siemens AB
Mr. Naglitsch
Johanneslundsvgen 12-14
Upplands Vsby
Tel +46 (8) 728 1872
Fax +46 (8) 728 1290
Email Peter.Naglitsch@
siemens.se
Switzerland
Basel
Siemens Schweiz AG
Mr. Neeser
Viaduktstr. 40
CH-4051 Basel
Phone +41 (0) 1 495 5096
Fax +41 (0) 1 495 4869
Email Roland.Neeser@
siemens.ch
Lausanne
Siemens Suisse SA
Mr. Neeser
Avenue des Baumettes 5
CH-1020 Renens
Phone +41 (0) 1 495 5096
Fax +41 (0) 1 495 4869
Email Roland.Neeser@
siemens.ch
Zrich
Siemens Schweiz AG
Mr. Neeser
Freilagerstr. 40
CH-8047 Zrich
Phone +41 (0) 1 495 5096
Fax +41 (0) 1 495 4869
Email Roland.Neeser@
siemens.ch

Russia
Moscow
Mr. Iwanow
Ul. Malaja Kaluzhskaja, 17/19
117071 Moscow
Tel +7 (095) 737 2492
Fax +7 (095) 737 2483
Email Pawel.Iwanow@mow.
siemens.ru

Turkey
Istanbul
Siemens Sanayi ve Ticaret A.S.,
Istanbul
Mrs. nan
Yakacik Yolu No. 111
81430 Kartal-Istanbul
Tel +90 (216) 459 3706
Fax +90 (216) 459 3079
Email sevtap.inan@
siemens.com.tr

Slovakia
Bratislava
Siemens s.r.o.
Mr. Patoprsty
Stromova 9
83796 Bratislava
Tel +421 (2) 5968-2426
Fax +421 (2) 5968 5240
Email radomir.patoprsty@
siemens.sk

Ukraine
Kiew
Siemens AG
Mr. Fadejew
Uliza Worowskowo 27
252054 Kiew 54
Tel +380 (44) 201-2461
Fax +380 (44) 201-2466
Email wladimir.fadejew@
iev.siemens.com.ua

Slovenia
Ljubljana
Siemens d.o.o.
Mr. Mlinsek
Dunajska 22
1511 Ljubljana
Tel +386 (1) 4746-152
Fax +386 (1) 4746-138
Email matjaz.mlinsek@siemens.si

Yugoslavia
Belgrade
Siemens d.o.o., Belgrad
Mr. Rajic
Knez Mihailova 30
11000 Belgrad
Tel +381 (11) 633 487
Fax +381 (11) 630 050
Email milan.rajic@siemens.co.yu

Appendix
SITOP contact persons
outside Europe
Africa
Algeria
Hydra
Siemens Burau dAlger
Mr. Bennour
44, rue Abri Areski
16035 Algier
Tel +213 (21) 69 22 94
Fax +213 (21) 69 12 88
Email Hamid.bennour@
tun.siemens.de
Egypt
Cairo
Siemens Limites
Mr. Loka
26, El Batal Ahmed Abdel Aziz
Street
Cairo
Tel +20 (2) 3333624
Fax +20 (2) 3333607
Email Hany.loka@siemens.com.eg
Samouha-Alexandria
Siemens Limites
Mr. Lotfy
27, Victor Emmanuel Street
Samouha-Alexandria
Tel +20 (3) 4251007
Fax +20 (3) 4251009
Email mina.lotfy@
siemens.com.eg
Morocco
Casablanca
Siemens Maroc
Mr. Rhouzli
km 1, Route de Rabat, An-Seba
20250 Casablanca
Tel +212 (22) 66 92 70
Fax +212 (22) 34 01 51
Email azzedine.rhouzli@
siemens.co.ma

America
Argentina
San Martin
Siemens S.A.
Mr. Gorenberg
Calle 122 (ex Gral. Roca) 4785,
Ruta 8, km 18 Casilla de Correo 32
RA-B1653 JXA San Martin
Tel +54 (11) 4738-7154
Fax +54 (11) 4738-7271
Email Andres.Gorenberg@
siemens.com.ar
Brazil
So Paulo
Siemens Ltda.
Mr. Lehnert
Rua Coronel Bento Bicudo,
111-Lapa
05069-900 So Paulo - Sp
Tel +55 (11) 3833 4901
Fax +55 (11) 3833 4959
Email Lehnert@siemens.com.br
So Paulo
Siemens Ltda.
Mr. Monteiro
Rua Coronel Bento Bicudo,
111-Lapa
05069 900 So Paulo - SP
Tel +55 (11) 3833-4115
Fax +55 (11) 3833-4651
Email monteiro@siemens.com.br
Canada
Mississauga
Siemens Canada Ltd.
Mr. Chronis
2185 Derry Road West
L5N 7A6 Mississauga
Tel +1 (905) 819 5800 (2360)
Fax +1 (905) 819 5719
Email Peter.Chronis@siemens.ca

South Africa
Halfway House 1685
Siemens Ltd.
Mr. Luckin
300 Janadel Avenue
1685 Halfway House
Tel +27 (11) 652-3672
Fax +27 (11) 652-3697
Email steve.luckin@
siemens.co.za

Chile
Santiago de Chile
Siemens S.A.
Mr. Silva
Avenida Holanda 64
Santiago de Chile
Tel +56 (2) 3614 208
Fax +56 (2) 3614 293
Email cesar.silva@siemens.cl

Tunesia
L'Aouina
Siemens S.A.
Mr. Ben Othman
5eme etage, Immeuble Mark
Crown
2025 L'Aouina
Tel +216 (1) 771 149
Fax +216 (1) 771 620
Email faze@planet.tn

Columbia
Santaf de Bogot D.C.
Siemens S.A.
Mr. Mejia
Carrera 65 No. 11-83
Santaf de Bogot D.C.
Tel +57 (1) 4253 710
Fax +57 (1) 2942 600
Email Jorge.Mejia@
siemens.com.co
Costa Rica
San Jos
Siemens SA de CV
Mr. Salas
La Uruca, Apartado 10022, San
Jose 1000
1000 San Jos
Tel +506 287 5125
Fax +506 233 5422
Email Jonathan.Salas@
siemens.com.mx

Asia
El Salvador
01 137 San Salvador
Mr. Callejas
Antiguo Cuscatln,
Apartado 1525
Tel +503 278 3333
Fax +503 278 3334
Email victor.callejas@
siemens.com.mx
Guatemala
Ciudad de Guatemala
Siemens SA
Mr. Mendez
2a. Calle 6-76, Zona 10
Ciudad de Guatemala
Tel +502 360 7080
Fax +502 334 3670
Email mario.mendez@
siemens.com.mx
Mexico
Colonial Industrial Vallejo
Siemens SA
Mrs. Almanza
Poniente 116 No. 560
Colonial Industrial Vallejo
Tel +52 (5) 328-2114 bis 2117
Fax +52 (5) 328-2096
Email norma.almanza@
siemens.com.mx
Colonial Industrial Vallejo
Siemens SA
Mr. Snchez
Poniente 116 No. 560
Colonial Industrial Vallejo
Tel +52 (5) 328-2112
Fax +52 (5) 328-2097
Email Gregorio.Sanchez@
siemens.com.mx
Colonial Industrial Vallejo
Siemens SA
Mrs. Almanza
Poniente 116 No. 560
Colonial Industrial Vallejo
Tel +52 (5) 328-2114 bis 2117
Fax +52 (5) 328-2096
Email norma.almanza@
siemens.com.mx
Peru
Lima
SIEMSA
Mr. Magallanes
Av. Repblica de Panam
3972-78 Casilla 44 - Lima 34
Email LMagallanes@
siemsa.com.pe
USA

Batavia
Siemens Energy&Automation, Inc.
Mr. Bronzel
1000 McKee Street
IL 60510 Batavia
Tel +1 (630) 262 7567
Fax +1 (630) 262 6018
Email kai.bronzel@
sea.siemens.com
Venezuela
Urbanizacin, Los Ruices
Siemens s.a.
Mr. Cruz
Av. Don Diego Disneros
(1010-A-Aptdo.3616) =Pf
Urbanizacin, Los Ruices
Tel +58 (2) 203 8663
Fax +58 (2) 203 8912
Email enrique.cruz@
siemens.com.ve

China
Beijing
Siemens Limited
Mr. Shi
7, Wangjing Zhonghuan Nanlu
100015 Beijing
Tel +86 (10) 6472 1888 (3374)
Fax +86 (10) 6473 9213
Email lin.shi@
pek1.siemens.com.cn
Beijing
Siemens Limited
Mr. Zhang
7, Wangjing Zhonghuan Nanlu
100015 Beijing
Tel +86 (10) 6472 1888 (3907)
Fax +86 (10) 64377103
Email fan.zhang@
pek1.siemens.com.cn
Hong Kong
Siemens Ltd.
Mr. Lam
58/F, Central Plaza,
18 Harbour Road
Wanchai, Hong Kong
Tel +86 (852) 2583 3228
Fax +86 (852) 2824 9196
Email Jacky.Lam@
siemens.com.hk
India
Thane
Siemens Limited
Mr. Apte
Kalwa Works, Thane Belapur Road
400 601 Thane (Maharashtra)
Tel +91 (22) 760 0153
Fax +91(22) 760 0067
Email Hemant.Apte@
krg1.siemens.co.in
Indonesia
Jakarta 13210
P.T. Siemens Indonesia
Mr. Young
Jalan Jendral Ahmad Yani
Kav. B 67-68
Pulo Mas
13210 Jakarta
Tel +62 (21) 4729-339
Fax +62 (21) 27509-200
Email Greig.Young@
ptsi.siemens.co.id
Iran
Teheran
Siemens Sherkate Sahami Khass
Mr. Assadzadeh
venue Ayatollah Taleghani 32
Teheran
Tel +98 (21) 614 2239
Fax +98 (21) 640 2389
Email h.assadzadeh@
siemens.co.ir

Siemens KT 10.1 2002

16/9

Appendix
SITOP contact persons
outside Europe (continued)
Australia
Israel
Tel-Aviv
ARDAN
Production & Industrial
Control Ltd.
Mr. Bauer
32, Habanay Street
Holon 58856
Tel +972 (3) 6 50 70 00
Fax +972 (3) 5 58 13 11
Email bauer@ardan-pic.co.il

Kuwait
Hawalli
NGEECO
Mr. Sundaran
Shuwaikh, Al-Shaya Complex,
Jahra Road
32041 Hawalli
Tel +965 (483) 1544 (220)
Fax +965 (483) 0156
Email saravanan.sundaran@
siemens.com.kw

Philippines
Makati City
Siemens Inc.
Mr. Salud
169 H.V. De la Costa Street,
Salcedo Village
1227 Makati City
Tel +63 (2) 814 9678
Fax +63 (2) 814 9894
Email bernard.salud@
siemens.com.ph

Japan
Shinagawa-ku, Tokyo 141-8614
Siemens K.K.
Mr. Ishida
20-14, Higashi-Gotanda 3-chome
141-8614 Shinagawa-ku, Tokyo
Tel +81 (3) 5423 8594
Fax +81 (3) 5423 8734
Email toshikazu.ishida@
skk.siemens.co.jp

Korea
Seoul
Siemens Limited
Mr. Song
726, Asia Building 10th floor
Yeoksam-dong, Kangnam-gu
135 925 Seoul
Tel +82 (2) 3420 4897
Fax +82 (2) 527 7785
Email songss@siemens.co.kr

Thailand
Bangkok
Siemens Limited
Mr. Suphot
2922/283 New Petchburi Road,
Bangkapi, Huaykwang
Bangkok
Tel +66 2715-4864
Fax +66 2715-4841
Email SuphotP@siemens.co.th

Jordan

Malaysia
Kuala Lumpur
Mrs. Leong
11 section 16/11,
Jalan Damansara
46350 Petaling Jaya,
Selangor Darul Ehsan
Tel +60 (3) 7952 5366
Fax +60 (3) 7955 2282
Email therese.leong@
see.siemens.com.my

Taiwan
Taipei
Siemens Limited
Mr. Wang
333, Tun-Hua S. Road Sec.2
Taipei
Tel +886 (2) 2378 8900
Fax +886 (2) 2378 8958
Email jacky.wang@
siemens.com.tw

Amman 11118
F.A. Kettaneh & Co.Ltd.
Mr. Rami
Al Quds Streeet, P.O. Box 485
11118 Amman
Tel +962 (6) 439 8642/7173
Fax +962 (6) 439 2582
Email al-naqa.rami@
kettaneh.com.jo
Lebanon
Mar-Mikhael-Beirut
Kettaneh S.A.
Mr. Markarian
Nahr Street
Mar-Mikhael- Beirut
Tel 00961 1 444560/3
Fax 00961 1 4446284
Email avedis.markarian@
kettaneh.com
Kazakhstan
Almaty
Siemens TOO
Mr. Kokoulin
20, Zharokov St.
480008 Almaty
Tel +7 3272 50 92-68/69
Email andrej.kokoulin@
ala.siemens.kz

Pakistan
Karachi
Siemens Pakistan
Engineering Co. Ltd.
Mr. Naukhez
B-72, Estate Avenue, S.I.T.E.
75700 Karachi
Tel +92 (21) 2574 910 19-4387
Fax +92 (21) 257 6200,
+92 (21) 256 3563
Email naukhez.arslan@
siemens.com.pk

Bayswater Victoria 3153


Siemens Limited
Mr. Avellino
885 Mountain Highway
3153 Bayswater Victoria
Tel +61 3 9721 7592
Fax +61 3 9721-7583
Email Mark.Avellino@
siemens.com.au

Uzbekistan
Taschkent
Siemens AG
Mr. Dobrev
K. Yarmatov Str. 6
Taschkent
Tel +998 (71) 120 6403
Fax +998 (71) 120 6402
Email evgeniy.dobrev@
siemens.com.uz
Vietnam
Hanoi
Siemens AG
Mr. Phuong
239 Xuan Thuy Road,
Cau Giay District
Hanoi
Tel +84 (4) 8334 400
Fax +84 (4) 8334 371
Email nguyen-ngoc.phuong@
siemens.com

Die Adressen der Ansprechpartner weltweit


finden Sie auch im Internet unter
http.//www.siemens.com/automation/partner

16/10

Siemens KT 10.1 2002

Appendix

Notes

Siemens KT 10.1 2002

16/11

Appendix

Conditions of sale and delivery


In Germany
Subject to the General Conditions of Sale as well as the General
Conditions of Supply and Delivery for Products and Services of
the Electrical and Electronics Industry.
For export
Subject to the General Conditions of Supply and Delivery for
Products and Services of the Electrical and Electronics Industry
and to any other conditions agreed upon with the recipients of
catalogs.
Software products are subject to the General Licence Conditions for Software Products for Automation and Drives.

Siemens AG
Automation and Drives
Systems Engineering
Sales Power Supplies, System Cables
P. O. Box 2355, 90713 Frth
Germany
16/12

Siemens KT 10.1 2002

Prices are listed in (Euro) ex delivery point, excluding


packaging.
Turnover tax (VAT) is not included in the prices. It will be added
according to legal provisions at the applicable rate.
We reserve the right to adjust prices and shall charge the prices
applying on the date of delivery.
All dimensions in this catalog are in mm. The illustrations are for
reference only.
We reserve the right to make changes, in particular to the
specified values, dimensions and weights, unless specified
otherwise on the individual pages of this catalog.

Order No.
E86060-K2410-A101-A4-7600
Printed in the Federal Republic of Germany
KG K 0302 9.0 Wen 132 DE/222 223

You might also like