sivacon8PS
Busbar trunking
systems LXA/LXC
from 800 A
Catalogue LV 72 2005
u
al
n
r
e
int
e
g
a
/9BHQB8IP6HLWH0LWWZRFK$SULO
4GNCVGFECVCNQIU
.QY8QNVCIG
Controlgear for Industry
Order No.:
E86060-K1002-A101-A4-7600
%QPVGPVU
LV 10
2QYGT&KUVTKDWVKQP
Products and Systems for
Power Distribution
Order No.:
E86060-K1801-A101-A4-7600
LV 30
5+8#%1025
Busbar Trunking Systems CD,
BD01, BD2 up to 1250 A
Order No.:
E86060-K1870-A101-A1-7600
LV 70
5+8#%1025
Busbar Trunking Systems
CD, BD01, BD2 up to 1250 A
Order No.:
E86060-P1870-A101-A2-7600
LV 70 P
Price List
System CD (25 A up to 40 A) System BD01 (40 A up to
160 A) System BD02 (160 A up to1250 A)
5+8#%1025
Busbar Trunking Systems
BD2A/BD2C, LDA/LDC
from 160 A to 5000 A
Order No.:
E86060-T1871-A101-A1-7600
LV 71 T
Technical Information
System Overview BD2A/BD2C System
LDA/LDC System Further Information
5+8#%1025
Busbar Trunking Systems
LXA/LXC over 800 A
Order No.:
E86060-T1872-A101-A1-7600
LV 72 T
Technical Information
System Overview LXA/LXC System
Further Information
#WVQOCVKQPCPF&TKXGU
CA 01
The Offline Mall for A&D
Order No.:
E86060-D4001-A110-C3-7600
#&/CNN
Internet:
http://www.siemens.com/automation/mall
4GIKUVGTGFVTCFGOCTMU
'ZRNCPCVKQPU
Catalogs of the
Automation and Drives Group (A&D)
Further information can be obtained from our branch offices listed
in the appendix or at www.siemens.com/automation/partner
Automation and Drives
Interactive catalog on CD-ROM
Catalog
Catalog
LV 10
CA 01
LV 30
LV 60
NC 60
LV 70
LV 90
PM 10
Drive Systems
Variable-Speed Drives
SINAMICS G130 Drive Converter Chassis Units,
SINAMICS G150 Drive Converter Cabinet Units
D 11
D 11.1
D 21.2
D 21.3
DC Motors
DA 12
DA 21.1
MP 12
MP 20
DA 21.2
MP 31
DA 22
WT 01
DA 45
WT 02
SIEMOSYN Motors
DA 48
PA 10
DA 51.2
PA 11
DA 51.3
PA 20
DA 63
DA 65.10
DA 65.11
ST 45
DA 65.3
ST 50
ST 70
DA 65.4
Low-Voltage Three-Phase-Motors
FI 01
ST PCS 7
ST PCS 7.A
pc-based Automation
ST PC
Feed Motors
ST DA
MP 35
MP 35.1/.2
M 11
NC 60
HE 1
ET A1
ET A5
Systems Engineering
Power supplies SITOP power
KT 10.1
ET B1
KT 10.2
ET D1
ET G1
FS 10
ST 80
IK PI
System Solutions
Applications and Products for Industry are part of the
interactive catalog CA 01
TELEPERM M Process Control System
AS 235, AS 235H and AS 235K automation systems
PLT 111
PLT 112
PLT 123
PLT 130
Siemens AG
Automation and Drives
Low-Voltage Controls and Distribution
Postfach 48 48
90327 NRNBERG
FEDERAL REPUBLIC OF GERMANY
www.siemens.com/lowvoltage
Catalogue LV 72 2005
SIVACON 8PS
Busbar trunking
systems LXA/LXC
from 800 A
Catalogue LV 72 2005
Introduction
System overview
Siemens AG 2005
Annex
Siemens LV 72 2005
Introduction
1/2
1/3
1/4
1/6
1/8
SIVACON 8PS
Busbar Trunking Systems in Action
1/10
SIVACON 8PS
Engineering Tools for precisely
dimensioned, economical solutions
Siemens LV 72 2005
Welcome to
Automation and Drives
1/2
Everyday life would be unimaginable without electric power. Competence and innovations
in switching and electrical installation technology are prerequisites so that power can be
used without danger and user-friendly in industrial facilities and buildings. We have been
providing you with these prerequisites for more than 110 years and are permanently developing new features innovations which permit you to use power more safely and economically.
Low-voltage switchgear from Siemens offers a comprehensive and innovative range of
products covering switching devices for load feeders or the distribution of power, control
and signaling devices as well as complete cabinet systems. Multi-functional, uniform concepts such as Totally Integrated Power, Safety Integrated or ECOFAST additionally permit
our product portfolio to be combined into optimized systems.
All in all, we can provide you with innovative components for switching and electrical installation technology which utilize state-of-the-art features such as integration and communication as the basis for advanced and uniform solutions which provide you with many
benefits.
1/3
ERP
Enterprise
Resource
Planning
MES
Manufacturing
Execution
Systems
Control
SIMATIC NET
Industrial
Communication
Ethernet
Ethernet
Production
Order
Management
Material
Management
Production
Operations
Recording
Equipment
Management
SINAUT Telecontrol
System
SIMATIC
Software
Industrial
Ethernet
SIMATIC
Machine Vision
Industrial
Ethernet
Industrial Wireless
Communication/
MOBIC
Safety Integrated
PROCESS FIELD
PROFIBUS
AS-Interface
GAMMA instabus
1/4
SIMATIC
PC-based Automation
Building
Technology
Micro-Automation
and
Actuator-Sensor
Interface Level
ECOFAST IP65
Decentral
Automation System
Plant
Information
Management
Product Specification
Management System
Detailed
Production
Scheduling
Laboratory Information
Management System
SIMATIC IT Framework
Production Modeler
SENTRON
Circuit
Breakers
SIMATIC
Controller/
Automation
System
SIMATIC
Distributed
I/O
Field Instrumentation/
Analytics
SINUMERIK
Numeric
Control
SIMOTION
Motion Control
System
SIMODRIVE
SINAMICS
SIMATIC HMI
Human Machine
Interface
SIMATIC PCS 7
Process Control
System
Sensor
Technology
IQ-Sense
HART
PROFIBUS PA
SIMOCODE-DP
Motor
Protection
and Control
Drive Systems
1/5
Communications
HMI
Process/production
automation
Load
management
U
I
coso
P
W
110 kV
1/6
Graphs
Prognoses
Maintenance
Substation
Distribution
Maintenance
task
Message/
error
management
Selective
protection
Protocols
Power
quality
DATE:
EMPLOYEE
Cost center
COST CENTER
PAY PERIOD BEGINNING
PAY PERIOD ENDING
DATE
SUN
MON
TUE
WED
THUR
FRI
SUN
MON
TUE
WED
THUR
FRI
SAT
SUN
TOTAL
IN
OUT
IN
OUT
OVERTIME
TOTAL HOURS
DATE
SAT
SUN
TOTAL
IN
Building
automation
OUT
IN
Hall 1
Distribution 3
Infeed II
OUT
OVERTIME
TOTAL HOURS
central ON
OFF
local ON
OFF
tripped
DATE
SUN
MON
TUE
WED
THUR
FRI
SAT
SUN
TOTAL
IN
OUT
IN
OUT
OVERTIME
TOTAL HOURS
CODES
V=VACATION
H=HOLIDAY
S=SICK
REGULAR
HOLIDAY
OTHER
SICK
VACATION
instabus EIB
1/7
All these systems are Type-tested LV switchgear assemblies (TTA) to IEC 60439-1 and -2. This
ensures that they offer a standard of safety and
reliability that meets the particularly high performance expectations of automated production
and for building services provision.
Performance characteristics:
Clear network structure
Unproblematic retrofitting in the event of load
changes
Low operating costs due to uninterrupted serviceability
Simple planning and installation
Room-covering systems for lighting installations and small loads
The CD system (up to 40 A) allows you to supply
lighting installations covering the whole expanse of, say, furniture showrooms, supermarkets
or greenhouses with power, and also provides
the means to easily fix them in position.
Due to its pleasing appearance, the equipment
is well suited for use in sales rooms visited by
the public. On the other hand, its high degree of
protection, to IP54, allows the CD system to be
used even in harsh environments.
The power source for loads with no fixed
location
The BD01 system is ideally suited for the power
supply (up to 160 A) in workshops and trade
premises. The trunking units are easily and
quickly to put together. The anti-rotation feature
on the tap-off units makes sure that the units are
correctly fitted and allows for easy retrofitting
even while the production is running.
Other benefits: minimum stock holding and uncomplicated planning due to one standard
frame size for five different current ratings.
1/8
The LX busbar trunking system is the perfect equipment for multistorey buildings where large quantities of power need to be transported, uninfluenced by the mounting position of the system.
1/9
BusbarSelect
Selection aid for generating quotations, invitations to tender and orders for busbar trunking
systems up to 1250 A; available in several
languages.
Quotation texts
Prepared texts (in German) for generating
customer specifications in the formats: Architext
excellent, GAEB 81 and Word 97.
Should you have any queries concerning installation, functionality or application options
please mail us at
sbts.tool_support@siemens.com
We will be pleased to assist you.
In BusbarSelect, you select the trunking units for your system from a menu,
and then transfer them into an order or quotation list.
1/10
System Overview
2/2
2/4
2/4
2/5
2/8
Basics of planning
busbar trunking systems
Overview
Benefits
Application
System selection criteria
Application
Technical specifications
Siemens LV 72 2005
System Overview
Basics of planning busbar trunking systems
Overview
Developing a power distribution concept, including system and
component configurations, involves finding an effective solution
based on customer requirements and supplier technology. This
design information brochure for the LX busbar trunking system
for rated currents ranging from 800 A to 6300 A, is designed to
help with this task.
2/2
Siemens LV 72 2005
There will always be more than one possible solution which will
have to be assessed in terms of its technical and economic
advantages and disadvantages. In making this assessment, the
following requirements should be a priority:
Simple and transparent design
Long service life
High availability
Low fire load
Flexible adaptation to building modifications.
These requirements are generally easy to meet with appropriate
busbar trunking systems. For this reason, engineers increasingly
favour busbar trunking systems over cable installations for
power transmission and distribution applications. Siemens offers busbar trunking systems for rated currents ranging from 25
to 6300 A:
The CD busbar trunking system from 25 to 40 A is ideal for supplying lights and small consumers
The BD01 busbar trunking system from 40 to 160 A is designed for supplying workshops with tap-offs up to 63 A
The BD2 busbar trunking systems from 160 to 1250 A is designed for supplying medium-sized consumers in buildings
and in industry
The ventilated LD busbar trunking system is designed for supplying consumers with a high power consumption in industrial
applications
The LX sandwich system is designed for supplying large
power requirements in buildings
The design information brochure LV 71.T is available for designing the BD2 and LD busbar trunking systems.
System Overview
Basics of planning busbar trunking systems
BD2
B
1-K
BD0
BD01
01
BD
B
1-K
BD0
LX
CD
LD
LX
LD
Siemens LV 72 2005
2/3
System Overview
Basics of planning busbar trunking systems
Benefits
Application
Busbar trunking systems meet these demands for an economical power distribution system with simple design, fast installation, optimum flexibility and safety by offering:
Straightforward network structures
Minimum space requirements
Easy retrofitting with sudden changes in location and consumer ratings
High short-circuit rating and low fire load
The LX busbar trunking system is a type-tested low-voltage assembly (TTA) in accordance with IEC/EN 60439-1 and 2 in the
form of an aluminium enclosed sandwich system. The LX sandwich system consists of busbars, insulation, the aluminium enclosure and the fastening and connection elements.
2/4
Siemens LV 72 2005
System Overview
System selection criteria
Application
Building applications
Industrial applications
2
LXA/LXC and LDA/LDC systems are available for distributing
large power requirements in buildings. For this type of application busbar trunking systems frequently have to meet the following requirements:
Flexible power distribution in high-rise buildings
Safe power supply for electronic consumers
To meet these requirements the LXA/LXC systems have very
favourable features in terms of design, high load capacity of the
neutral conductor as well as an additional isolated PE conductor.
Nevertheless, there are applications for which the use of the
LDA/LDC system is recommended. LD systems are ideally used
in applications with primarily horizontal busbar runs and required protection to IP34.
Sector
Selection criteria
LX
LD
Building applications
Banks,
insurance companies
Internet providers, IT centres, broadcasting
buildings
Shopping centres, furniture stores, trade
fairs, airports, hospitals, clinics, offices
Industrial applications
Automotive, metalworking, machine building, computers, microchips,
telecommunications, chemical,
pharmaceutical, food processing industries
Siemens LV 72 2005
2/5
System Overview
System selection criteria
Conductor configurations
IEC 364 stipulates that electrical equipment must be selected
according to the type of system at hand in order to determine the
protective measures required. For the LX system this selection is
based on the appropriate conductor configuration.
System type
Conductor configuration
TN-C
LX...41
TN-C-S
1)
TN-S
LX...51
LX...52
LX...53
LX...54
LX...61
LX...62
TT
LX...51
LX...52
LX...53
LX...54
IT
LX...30
Clean Earth
2/6
Siemens LV 72 2005
System Overview
System selection criteria
Cross-sections for PEN, N, PE conductors compared to the
conductor cross-section
The following tables compare the conductor cross-sections
L1, L2, L3, PEN, N, PE and Clean Earth of different conductor
configurations. The appropriate values in mm2 are contained in
the Technical Data.
System
Cross-sections
L1, L2, L3
PEN
PE
Clean Earth
LX..30
LX..41
LX..51
LX..52
100 %
100 %
100 %
100 %
100 % + Enclosure
100 %
200 %
Enclosure
Enclosure
Enclosure
LXC.531)
LXC.541)
LX..61
LX..62
100 %
100 %
100 %
100 %
100 %
200 %
100 %
200 %
100 % + Enclosure
100 % + Enclosure
Enclosure
Enclosure
100 %
100 %
1) Each conductor configuration contains an additional busbar as PE conductor. The PE conductor is electrically connected to the enclosure.
Enclosure cross-section
LXA(C)01..
LXA(C)02..
324 %
245 %
LXC03..
LX(C)A04..
LXA(C)05..
LXA(C)06..
230 %
173 %
119 %
113 %
LXA(C)07..
LXA(C)08..
LXA(C)09..
LXA10..
84 %
119 %
113 %
84 %
Example:
What are the cross-sections of systems for:
a) LXA0461
L1, L2, L3, N, Clean Earth: 100 %
PE (enclosure): 173 % in Cu equivalent
b) LXC0554
L1, L2, L3: 100 %
N: 200 %
PE (enclosure + busbar): 219 % in Cu equivalent
Siemens LV 72 2005
2/7
System Overview
System selection criteria
Technical specifications
LXA/LXC
690
LDA/LDC
1000
IP54
IP341)
800 6300
1100 5000
%
%
%
%
100
100
100
100
100
59 68
76 88
64 82
kA
25 150
55 116
k
k
k
k
k
k
k
k
k
k
k
mm
mm
mm
mm
mm
mm
145 x 137
145 x 162
145 x 207
145 x 287
145 x 439
145 x 599
180 x 180
180 x 180
180 x 180
240 x 180
240 x 180
240 x 180
kWh/m
kWh/m
1,83 16,32
2,9
4,16 8,83
7,8 10,8
mV/A/m
mV/A/m
mV/A/m
mV/A/m
mV/A/m
0,127
0,051
0,03
0,064
0,02
0,116
0,068
0,043
0,089
0,03
T
T
T
T
T
10,84
20,54
30,62
11,66
37,22
10,60
9,00
13,00
9,70
14,40
Al systems
Cu systems
m
m
23
23
56
23
80 630
80 1250
A
A
A
6
4
0
3
3
2
A
kA
100 630
100 (80)
k
k
k
80 630
120
k
80 1250
80 1250
kA
kA
kA
65
65
85 (100)
k
100
100
100
k
k
VAC
Rated current Ie
Fire load
Tap-off unit without tap-off point
Per tap-off point
Voltage drop3)
Al systems/1250 A
Al systems/2500 A
Al systems/4000 A
Cu systems/2000 A
Cu systems/5000 A
Magnetic fields4)
Al systems/1600 A
Al systems/2500 A
Al systems/4000 A
Cu systems/2000 A
Cu systems/5000 A
1) Taking current reduction into account also available with IP54 degree of protection
2) (PE) = Additional insulated PE conductor (Clean Earth)
3) Voltage drop in millivolts per 1 m per ampere, 3-phase 50 Hz, p. f. = 0.9, with a fully symmetrical load,
concentrated load tap-off and supply from one end
4) Magnetic field values given in microtesla with a fully symmetrical load at a distance of 0.5 m from the busbar system
(the measuring points are in the axis from direction 3 and direction 7, see Catalog LV 72.T 2004 Further Information)
2/8
Siemens LV 72 2005
System Overview
System selection criteria
Rated currents and short-circuit currents of standard transformers
Rated voltage UN
400/230 V
690/400 V
4 %1)
6 %2)
4 %1)
Rated power
Rated current
Rated current
6 %2)
kVA
Short-circuit current3)
I"k
A
Short-circuit current3)
I"k
A
50
100
160
200
72
144
230
288
1805
3610
5776
7220
2406
3850
4812
42
84
133
168
1042
2084
3325
4168
1392
2230
2784
250
315
400
500
360
455
578
722
9025
11375
14450
18050
6015
7583
9630
12030
210
263
336
420
5220
6650
8336
10440
3560
4380
5568
7120
630
800
1000
1250
909
1156
1444
1805
22750
28900
36100
45125
15166
19260
24060
30080
526
672
840
1050
13300
16672
20840
26060
8760
11136
13920
17480
1600
2000
2500
3150
2312
2888
3612
4546
57800
72200
90300
113650
38530
48120
60200
75780
1330
1680
2094
2636
33300
41680
52350
65893
22300
27840
34900
43933
Approximation formula
Rated current of transformer
400 V: k = 1.45
690 V: k = 0.84
Siemens LV 72 2005
2/9
System Overview
System selection criteria
LXA/LXC selection depending on transformer rated values
Transformer rated values
Rated current
Rel. shortcircuit
voltage
LX-System
uk
UninterPeak shortType
rupted short- circuit current
circuit current
I"k
Ipk
kAeff
kA
910
15.15
38.58
1155
19.25
49.00
1444
24.06
61.24
1805
30.07
76.57
2310
38.50
98.00
2887
48.11
122.50
3609
60.11
153.10
4546
75.78
192.90
LXA02
LXC01
LXA04
LXC02
LXA05
LXC04
LXA06
LXC05
LXA07
LXC06
LXA08
LXC07
LXC09
LXC08
LXC09
Rated current
Rated short-time
withstand current
Rated impulse
withstand current
Ie
Icw
Ipk
kAeff
kA
1000
1000
1250
1250
1600
1600
2000
2000
2500
2500
3200
3200
4000
4000
5000
35
38
50
50
60
60
75
75
86
86
100
100
140
150
150
70
80
110
110
132
132
158
165
194
189
220
220
220
255
255
7
2/10
Siemens LV 72 2005
3/1
3/6
3/21
3/22
3/25
3/28
3/33
3/46
3/50
3/53
3/58
3/65
3/66
3/76
3/79
System components
Overview
Technical specifications
- Trunking units
- Tap-off units
- Weights
Selection and ordering data
- Straight trunking units
- Angle and branch units
- Connection units
- Tap-off units
Accessories
- for mounting and fixing
Dimensional drawings
- Trunking units
- Universal-connection units
- Cable feeder units
- Connection to distribution boards
- Tap-off units
- Accessories
Siemens LV 72 2005
Overview
1
2
2
6
6
3/2
Siemens LV 72 2005
Siemens LV 72 2005
3/3
Code No.
30
Conductor configuration:
L1 + L2 + L3 + PE1)
800
1000
01
41
L1 + L2 + L3 + PEN/PEN4)
1000
1250
02
51
L1 + L2 + L3 + N + PE1)
1400
03
52
L1 + L2 + L3 + N + N3) + PE1)
1250
1600
04
535)
L1 + L2 + L3 + N + PE/PE4)
1600
2000
05
545)
L1 + L2 + L3 + N + N3) + PE/PE4)
2000
2500
06
61
L1 + L2 + L3 + N + (PE)2) + PE1)
2500
3200
07
62
3200
4000
4000
5000
08
09
4500
63007)
10
Fire barrier
Positioning X*
(see Engineering)
Conductor material
A
Al
C
Cu
3
LX
. .. ..
-.... +LX
Type
. .. ..
Type suffix
-S120-X..
Cu
Code No.
Code No.
30
Conductor configuration:
L1 + L2 + L3 + PE1)
800
C 01
1000
01
41
L1 + L2 + L3 + PEN/PEN4)
1000
C 02
1250
02
51
L1 + L2 + L3 + N + PE1)
1400
03
52
L1 + L2 + L3 + N + N3) + PE1)
1250
C 04
1600
04
53
L1 + L2 + L3 + N + PE/PE4)
1600
A 056)
2000
05
54
L1 + L2 + L3 + N + N3) + PE/PE4)
2000
C 06
2500
06
61
L1 + L2 + L3 + N + (PE)2) + PE1)
2500
C 07
3200
07
62
3200
4000
4500
C 08
C 09
A 106)
4000
5000
63007)
08
09
10
LX
... ..
-..
Type
1) PE conductor = Enclosure
2) Separate PE conductor by means of an insulated busbar (Clean Earth)
3) Double cross-section of neutral conductor (200%) by means of additional
busbar
4) PE(PEN) conductor = busbar and enclosure
5) Only available as copper system (LXC)
6) These types have copper conductors
7) Technical clarification required before offer is submitted
3/4
Siemens LV 72 2005
Designation
Distance centre tap-off unit to centre clamp terminal
Length expansion compensation unit
Standard length
Optional length
Length of X limb
Length of Y limb
Length of Z limb
Siemens LV 72 2005
3/5
Technical specifications
LX..... Busbar trunking units
Standards
resistance to climate
Ambient temperature Min./Max./mean level over 24 hours
Degree of protection
Nm
Material
Colour
Dimensions
Weights
Rated operational voltage Ui
acc. to DIN VDE 0110, IEC 909
Overvoltage category/pollution degree
Rated operational voltage Ue
Rated frequency
3/6
Siemens LV 72 2005
V~
VV~
Hz
IP54
Ie
LXA
A
0130
800
0230
1000
0430
1250
0530
1600
0630
2000
0730
2500
0830
3200
0930
4000
1030
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.174
0.084
0.193
0.084
0.031
0.090
0.106
0.031
0.110
0.154
0.085
0.175
0.056
0.024
0.061
0.070
0.024
0.074
0.123
0.069
0.141
0.036
0.017
0.040
0.043
0.017
0.046
0.079
0.056
0.096
0.027
0.009
0.029
0.034
0.009
0.029
0.072
0.040
0.082
0.023
0.011
0.025
0.028
0.011
0.025
0.069
0.044
0.081
0.018
0.009
0.020
0.022
0.008
0.024
0.055
0.040
0.068
0.014
0.005
0.015
0.017
0.005
0.018
0.040
0.025
0.047
0.011
0.012
0.006
0.014
0.006
0.015
0.040
0.028
0.048
Resistance
Reactance
Impedance
R'0
X'0
Z'0
m/m
m/m
m/m
0.297
0.216
0.367
0.274
0.200
0.339
0.251
0.184
0.311
0.228
0.168
0.283
0.204
0.152
0.254
0.181
0.136
0.226
0.158
0.119
0.197
0.135
0.103
0.169
0.111
0.088
0.141
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
IPK
kA
kA
kA
25
35
15
21
53
70
Aluminium
3
3
292
386
948
948
50
30
110
60
36
132
75
45
158
86
51.6
194
100
60
220
140
60
255
150
70
255
3
586
1018
3
946
1135
3
1192
1348
3
1586
1348
6
1892
2270
6
2384
2694
6
3172
2696
L1, L2, L3
PE = Enclosure
Combustive energy
Trunking unit
without tap-off point
per tap-off point
mm2
mm2
kWh/m 1.83
2.9
kWh
1.91
2.9
2.37
2.9
3.32
2.9
5.01
2.9
5.09
2.9
6.84
2.9
10.22
2.9
10.4
2.9
m
m
kg/m
2
2
10.6
2
2
13.3
3
2
17.8
3
2
21.8
3
2
26.3
3
2
35.5
3
2
43.4
3
2
52.1
Weights
2
2
9.6
Note:
For further information, see chapter Planning and Engineering Basic technical information.
Siemens LV 72 2005
3/7
IP54
Ie
LXA
A
0141
800
0241
1000
0441
1250
0541
1600
0641
2000
0741
2500
0841
3200
0941
4000
1041
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.158
0.074
0.175
0.084
0.031
0.090
0.106
0.031
0.110
0.126
0.083
0.150
0.056
0.024
0.061
0.070
0.024
0.074
0.093
0.064
0.113
0.036
0.017
0.040
0.043
0.017
0.046
0.063
0.050
0.080
0.027
0.009
0.029
0.034
0.009
0.035
0.048
0.032
0.058
0.023
0.011
0.025
0.028
0.011
0.030
0.043
0.035
0.055
0.018
0.008
0.020
0.022
0.008
0.024
0.036
0.032
0.048
0.014
0.005
0.015
0.017
0.005
0.018
0.025
0.018
0.030
0.011
0.006
0.012
0.014
0.006
0.015
0.022
0.018
0.028
Resistance
Reactance
Impedance
R'0
X'0
Z'0
m/m
m/m
m/m
0.227
0.132
0.263
0.190
0.133
0.232
0.145
0.101
0.177
0.102
0.080
0.129
0.081
0.047
0.094
0.073
0.057
0.093
0.063
0.050
0.080
0.041
0.026
0.049
0.036
0.026
0.044
rms value t = 1 s
Peak value
ICW
IPK
kA
kA
25
35
53
70
Aluminium
4
4
292
386
1109
1161
50
110
60
132
75
158
86
194
100
220
140
255
150
255
4
586
1341
4
946
1657
4
1192
2006
4
1586
2223
8
1892
3314
8
2384
4011
8
3172
4446
L1, L2, L3
PEN
Combustive energy
Trunking unit
without tap-off point
per tap-off point
mm2
mm2
kWh/m 1.95
kWh
2.9
2.04
2.9
2.53
2.9
3.54
2.9
5.33
2.9
5.42
2.9
7.28
2.9
10.88
2.9
11.07
2.9
m
m
kg/m
2
2
12
2
2
15.2
3
2
20.8
3
2
25.6
3
2
31.3
3
2
42
3
2
51.3
3
2
62.6
Weights
3/8
Siemens LV 72 2005
2
2
10.6
IP54
Ie
LXA
A
0151
800
0251
1000
0451
1250
0551
1600
0651
2000
0751
2500
0851
3200
0951
4000
1051
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.174
0.084
0.193
0.249
0.113
0.273
0.084
0.031
0.090
0.106
0.031
0.110
0.154
0.085
0.176
0.192
0.122
0.227
0.056
0.024
0.061
0.070
0.024
0.074
0.123
0.069
0.141
0.133
0.095
0.163
0.036
0.017
0.040
0.043
0.017
0.046
0.079
0.056
0.097
0.086
0.072
0.112
0.027
0.009
0.029
0.034
0.009
0.035
0.072
0.040
0.082
0.064
0.046
0.079
0.023
0.011
0.025
0.028
0.011
0.030
0.069
0.044
0.082
0.055
0.047
0.072
0.018
0.009
0.020
0.022
0.008
0.024
0.055
0.040
0.068
0.047
0.043
0.064
0.014
0.005
0.015
0.017
0.005
0.018
0.040
0.025
0.048
0.032
0.023
0.039
0.011
0.012
0.006
0.014
0.006
0.015
0.040
0.028
0.049
0.028
0.023
0.036
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.281
0.198
0.344
0.484
0.175
0.515
0.274
0.200
0.339
0.377
0.177
0.417
0.240
0.161
0.289
0.260
0.134
0.293
0.159
0.130
0.205
0.167
0.095
0.192
0.153
0.094
0.179
0.128
0.061
0.142
0.154
0.101
0.184
0.106
0.065
0.125
0.121
0.097
0.155
0.095
0.060
0.112
0.092
0.063
0.111
0.062
0.030
0.069
0.095
0.069
0.117
0.052
0.030
0.060
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
25
15
15
53
35
21
21
70
50
30
30
110
60
36
36
132
75
45
45
158
86
51.6
51.6
194
100
60
60
220
140
70
60
255
150
70
70
255
mm2
mm2
mm2
Aluminium
4
4
292
386
292
386
948
948
4
586
586
1018
4
946
946
1135
4
1192
1192
1348
4
1586
1586
1348
8
1892
1892
2270
8
2384
2384
2694
8
3172
3172
2696
L1, L2, L3
N
PE = Enclosure
Combustive energy
Trunking unit
without tap-off point
per tap-off point
kWh/m 1.95
2.9
kWh
2.04
2.9
2.53
2.9
3.54
2.9
5.33
2.9
5.42
2.9
7.28
2.9
10.88
2.9
11.07
2.9
m
m
kg/m
2
2
12
2
2
15.2
3
2
20.8
3
2
25.6
3
2
31.3
3
2
42
3
2
51.3
3
2
62.6
2
2
10.6
Siemens LV 72 2005
3/9
Short-circuit rating
Rated short-time withstand current
for phase conductors
for neutral conductor
of the 5th conductor
Rated impulse withstand current
Conductor material
Number of busbars
Conductor cross-section
Equivalent copper cross-section
IP54
Ie
LXA
A
0152
800
0252
1000
0452
1250
0552
1600
0652
2000
0752
2500
0852
3200
0952
4000
1052
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.174
0.084
0.193
0.187
0.133
0.229
0.084
0.031
0.090
0.106
0.031
0.110
0.154
0.085
0.175
0.166
0.122
0.206
0.056
0.024
0.061
0.070
0.024
0.074
0.123
0.069
0.141
0.146
0.110
0.182
0.036
0.017
0.040
0.043
0.017
0.046
0.079
0.056
0.096
0.125
0.099
0.159
0.027
0.009
0.029
0.034
0.009
0.029
0.072
0.040
0.082
0.104
0.088
0.136
0.023
0.011
0.025
0.028
0.011
0.025
0.069
0.044
0.081
0.083
0.077
0.113
0.018
0.009
0.020
0.022
0.008
0.024
0.055
0.040
0.068
0.062
0.065
0.089
0.014
0.005
0.015
0.017
0.005
0.018
0.040
0.025
0.047
0.042
0.054
0.068
0.011
0.012
0.006
0.014
0.006
0.015
0.040
0.028
0.048
0.021
0.043
0.047
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.297
0.216
0.367
0.100
0.195
0.219
0.274
0.200
0.339
0.092
0.177
0.199
0.251
0.184
0.311
0.083
0.159
0.179
0.228
0.168
0.283
0.074
0.141
0.159
0.204
0.152
0.254
0.066
0.123
0.139
0.181
0.136
0.226
0.058
0.105
0.119
0.158
0.119
0.197
0.049
0.087
0.099
0.135
0.103
0.169
0.041
0.068
0.079
0.111
0.088
0.141
0.032
0.050
0.059
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
25
35
15
21
15
21
53
70
Aluminium
5
5
292
386
584
772
948
948
50
30
30
110
60
36
36
132
75
45
45
158
86
51.6
51.6
194
100
60
60
220
140
70
60
255
150
70
70
255
5
586
1172
1018
5
946
1892
1135
5
1192
2384
1348
5
1586
3172
1348
10
1892
3784
2270
10
2384
4768
2694
10
3172
6344
2696
L1, L2, L3
N
PE = Enclosure
mm2
mm2
mm2
Combustive energy
Trunking unit
without tap-off point
per tap-off point
kWh/m 2.43
2.9
kWh
2.55
2.9
3.16
2.9
4.42
2.9
6.66
2.9
6.77
2.9
9.1
2.9
13.6
2.9
13.83
2.9
m
m
kg/m
2
2
13.3
2
2
17
3
2
23.8
3
2
29.3
3
2
36.3
3
2
48.5
3
2
59.2
3
2
73.2
3/10
Siemens LV 72 2005
2
2
11.6
IP54
Ie
LXA
A
0161
800
0261
1000
0461
1250
0561
1600
0661
2000
0761
2500
0861
3200
0961
4000
1061
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.174
0.084
0.193
0.249
0.133
0.282
0.084
0.031
0.090
0.106
0.031
0.110
0.154
0.085
0.175
0.221
0.122
0.252
0.056
0.024
0.061
0.070
0.024
0.074
0.123
0.069
0.141
0.194
0.110
0.223
0.036
0.017
0.040
0.043
0.017
0.046
0.079
0.056
0.096
0.166
0.099
0.193
0.027
0.009
0.029
0.034
0.009
0.029
0.072
0.040
0.082
0.138
0.088
0.163
0.023
0.011
0.025
0.028
0.011
0.025
0.069
0.044
0.081
0.111
0.077
0.135
0.018
0.009
0.020
0.022
0.008
0.024
0.055
0.040
0.068
0.083
0.065
0.105
0.014
0.005
0.015
0.017
0.005
0.018
0.040
0.025
0.047
0.056
0.054
0.077
0.011
0.012
0.016
0.014
0.006
0.015
0.040
0.028
0.048
0.028
0.043
0.051
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.297
0.216
0.367
0.484
0.195
0.521
0.274
0.200
0.339
0.430
0.177
0.465
0.251
0.184
0.311
0.376
0.159
0.408
0.228
0.168
0.283
0.322
0.141
0.351
0.204
0.152
0.254
0.268
0.123
0.294
0.181
0.136
0.226
0.214
0.105
0.238
0.158
0.119
0.197
0.160
0.087
0.182
0.135
0.103
0.169
0.106
0.068
0.125
0.111
0.088
0.141
0.052
0.050
0.072
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
25
35
15
21
15
21
53
70
Aluminium
5
5
292
386
292
386
948
948
50
30
30
110
60
36
36
132
75
45
45
158
86
51.6
51.6
194
100
60
60
220
140
70
60
255
150
70
70
255
5
586
586
1018
5
946
946
1135
5
1192
1192
1348
5
1586
1586
1348
10
1892
1892
2270
10
2384
2384
2694
10
3172
3172
2696
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
mm2
mm2
mm2
kWh/m 2.43
2.9
kWh
2.55
2.9
3.16
2.9
4.42
2.9
6.66
2.9
6.77
2.9
9.1
2.9
13.6
2.9
13.83
2.9
m
m
kg/m
2
2
13.3
2
2
17
3
2
23.8
3
2
29.3
3
2
36.3
3
2
48.5
3
2
59.2
3
2
73.2
2
2
11.6
1) Insulated PE conductor
Siemens LV 72 2005
3/11
Short-circuit rating
Rated short-time withstand current
for phase conductors
for neutral conductor
of the 5th conductor
Rated impulse withstand current
Conductor material
Number of busbars
Conductor cross-section
Equivalent copper cross-section
IP54
Ie
LXA
A
0162
800
0262
1000
0462
1250
0562
1600
0662
2000
0762
2500
0862
3200
0962
4000
1062
4500
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.117
0.028
0.120
0.146
0.028
0.149
0.174
0.084
0.193
0.187
0.133
0.229
0.084
0.031
0.090
0.106
0.031
0.110
0.154
0.085
0.175
0.166
0.122
0.206
0.056
0.024
0.061
0.070
0.024
0.074
0.123
0.069
0.141
0.146
0.110
0.182
0.036
0.017
0.040
0.043
0.017
0.046
0.079
0.056
0.096
0.125
0.099
0.159
0.027
0.009
0.029
0.034
0.009
0.029
0.072
0.040
0.082
0.104
0.088
0.136
0.023
0.011
0.025
0.028
0.011
0.025
0.069
0.044
0.081
0.083
0.077
0.113
0.018
0.009
0.020
0.022
0.008
0.024
0.055
0.040
0.068
0.062
0.065
0.089
0.014
0.005
0.015
0.017
0.005
0.018
0.040
0.025
0.047
0.042
0.054
0.068
0.011
0.012
0.016
0.014
0.006
0.015
0.040
0.028
0.048
0.021
0.043
0.047
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.297
0.216
0.367
0.100
0.195
0.219
0.274
0.200
0.339
0.092
0.177
0.199
0.251
0.184
0.311
0.083
0.159
0.179
0.228
0.168
0.283
0.074
0.141
0.159
0.204
0.152
0.254
0.066
0.123
0.139
0.181
0.136
0.226
0.058
0.105
0.119
0.158
0.119
0.197
0.049
0.087
0.099
0.135
0.103
0.169
0.041
0.068
0.079
0.111
0.088
0.141
0.032
0.050
0.059
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
25
35
15
21
15
21
53
70
Aluminium
6
6
292
386
584
772
948
948
50
30
30
110
60
36
36
132
75
45
45
158
86
51.6
51.6
194
100
60
60
220
140
70
60
255
150
70
70
255
6
586
1172
1018
6
946
1892
1135
6
1192
2384
1348
6
1586
3172
1348
12
1892
3784
2270
12
2384
4768
2694
12
3172
6344
2696
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
1) Insulated PE conductor
3/12
Siemens LV 72 2005
mm2
mm2
mm2
kWh/m 2.92
2.9
kWh
3.06
2.9
3.79
2.9
5.31
2.9
7.99
2.9
8.13
2.9
10.92
2.9
16.32
2.9
16.6
2.9
m
m
kg/m
2
2
14.7
2
2
18.9
3
2
26.8
3
2
33.1
3
2
41.3
3
2
55
3
2
67.2
3
2
83.7
2
2
12.6
IP54
Ie
LXC
A
0130
1000
0230
1250
0330
1400
0430
1600
0530
2000
0630
2500
0730
3200
0830
4000
0930
5000
1030
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.137
0.092
0.165
0.051
0.031
0.059
0.065
0.031
0.072
0.125
0.085
0.151
0.044
0.020
0.048
0.055
0.020
0.059
0.113
0.078
0.137
0.037
0.026
0.045
0.045
0.026
0.051
0.101
0.070
0.122
0.027
0.013
0.030
0.035
0.013
0.037
0.089
0.063
0.109
0.017
0.009
0.019
0.021
0.009
0.022
0.077
0.056
0.095
0.013
0.011
0.017
0.016
0.011
0.019
0.065
0.049
0.081
0.011
0.008
0.014
0.014
0.008
0.016
0.053
0.041
0.067
0.009
0.005
0.010
0.011
0.005
0.012
0.041
0.034
0.053
Resistance
Reactance
Impedance
R'0
X'0
Z'0
m/m
m/m
m/m
0.274
0.207
0.343
0.254
0.191
0.317
0.233
0.175
0.291
0.213
0.160
0.266
0.193
0.144
0.240
0.172
0.128
0.214
0.152
0.113
0.189
0.132
0.097
0.163
0.111
0.082
0.138
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
IPK
kA
kA
kA
38
50
23
30
80
110
Copper
3
3
292
386
948
948
57
34
125
60
36
132
75
45
165
86
51
189
100
60
220
150
70
255
150
70
255
3
442
1018
3
586
1018
3
712
1135
3
1192
1348
3
1586
1348
6
1892
2270
6
2384
2696
L1, L2, L3
PE = Enclosure
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
mm2
mm2
kWh/m 1.83
2.9
kWh
1.91
2.9
2.27
2.9
2.37
2.9
3.27
2.9
5.01
2.9
5.09
2.9
6.84
2.9
10.22
2.9
m
m
kg/m
2
2
17.8
2
2
19.9
2
2
24.2
3
2
28.6
3
2
44.0
3
2
55.8
3
2
70.7
3
2
87.8
2
2
15.0
Siemens LV 72 2005
3/13
IP54
Ie
LXC
A
0141
1000
0241
1250
0341
1400
0441
1600
0541
2000
0641
2500
0741
3200
0841
4000
0941
5000
1041
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.107
0.079
0.133
0.051
0.031
0.059
0.065
0.031
0.072
0.090
0.081
0.121
0.044
0.020
0.048
0.055
0.020
0.059
0.076
0.060
0.097
0.037
0.026
0.045
0.045
0.026
0.051
0.070
0.065
0.095
0.027
0.013
0.030
0.035
0.013
0.037
0.052
0.047
0.070
0.017
0.009
0.019
0.021
0.009
0.022
0.036
0.033
0.049
0.013
0.011
0.017
0.016
0.011
0.020
0.032
0.037
0.049
0.011
0.008
0.014
0.014
0.008
0.016
0.025
0.029
0.038
0.009
0.005
0.010
0.011
0.005
0.012
0.018
0.018
0.026
Resistance
Reactance
Impedance
R'0
X'0
Z'0
m/m
m/m
m/m
0.172
0.121
0.210
0.147
0.127
0.194
0.121
0.092
0.152
0.114
0.095
0.148
0.089
0.067
0.111
0.064
0.046
0.079
0.054
0.049
0.073
0.047
0.043
0.064
0.032
0.026
0.042
rms value t = 1 s
Peak value
ICW
IPK
kA
kA
38
50
80
110
Copper
4
4
292
386
1240 1334
57
125
60
132
75
165
86
189
100
220
150
255
150
255
4
442
1460
4
586
1604
4
712
1847
4
1192
2540
4
1586
2934
8
1892
4162
8
2384
5080
L1, L2, L3
PEN
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
3/14
Siemens LV 72 2005
mm2
mm2
kWh/m 1.95
2.9
kWh
2.04
2.9
2.42
2.9
2.53
2.9
3.48
2.9
5.33
2.9
5.42
2.9
7.28
2.9
10.88
2.9
m
m
kg/m
2
2
21.5
2
2
24.1
2
2
29.7
3
2
35.3
3
2
55.2
3
2
70.6
3
2
88.9
3
2
110.5
2
2
17.9
IP54
Ie
LXC
A
0151
1000
0251
1250
0351
1400
0451
1600
0551
2000
0651
2500
0751
3200
0851
4000
0951
5000
1051
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.132
0.084
0.156
0.149
0.109
0.184
0.051
0.031
0.059
0.065
0.031
0.072
0.119
0.085
0.146
0.127
0.118
0.174
0.044
0.020
0.048
0.055
0.020
0.059
0.101
0.070
0.123
0.104
0.084
0.134
0.037
0.026
0.045
0.045
0.026
0.051
0.101
0.070
0.123
0.090
0.091
0.128
0.027
0.013
0.030
0.035
0.013
0.037
0.082
0.056
0.099
0.065
0.062
0.090
0.017
0.009
0.019
0.021
0.009
0.022
0.065
0.040
0.076
0.042
0.041
0.058
0.013
0.011
0.017
0.016
0.011
0.019
0.063
0.042
0.075
0.039
0.050
0.064
0.011
0.008
0.014
0.014
0.008
0.016
0.046
0.033
0.056
0.030
0.036
0.047
0.009
0.005
0.010
0.011
0.005
0.012
0.036
0.026
0.044
0.021
0.022
0.030
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.252
0.192
0.317
0.293
0.153
0.330
0.245
0.191
0.310
0.244
0.161
0.292
0.203
0.161
0.259
0.204
0.112
0.233
0.213
0.157
0.264
0.173
0.119
0.210
0.181
0.132
0.224
0.129
0.080
0.152
0.156
0.096
0.183
0.082
0.053
0.098
0.152
0.096
0.180
0.074
0.062
0.096
0.108
0.079
0.134
0.061
0.049
0.078
0.089
0.067
0.111
0.043
0.030
0.053
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
4
4
292
386
292
386
948
948
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
4
442
442
1018
4
586
586
1018
4
712
712
1135
4
1192
1192
1348
4
1586
1586
1348
8
1892
1892
2270
8
2384
2384
2696
L1, L2, L3
N
PE = Enclosure
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
mm2
mm2
mm2
kWh/m 1.95
2.9
kWh
2.04
2.9
2.42
2.9
2.53
2.9
3.48
2.9
5.33
2.9
5.42
2.9
7.28
2.9
10.88
2.9
m
m
kg/m
2
2
21.5
2
2
24.1
2
2
29.7
3
2
35.3
3
2
55.2
3
2
70.6
3
2
88.9
3
2
110.5
2
2
17.9
Siemens LV 72 2005
3/15
Short-circuit rating
Rated short-time withstand current
for phase conductors
for neutral conductor
of the 5th conductor
Rated impulse withstand current
Conductor material
Number of busbars
Conductor cross-section
Equivalent copper cross-section
IP54
Ie
LXC
A
0152
1000
0252
1250
0352
1400
0452
1600
0552
2000
0652
2500
0752
3200
0852
4000
0952
5000
1052
Resistance
Reactance
Impedance
R'20
X'20
Z'20
m/m
m/m
m/m
0.065
0.027
0.071
0.051
0.031
0.059
0.044
0.020
0.048
0.037
0.026
0.045
0.027
0.013
0.030
0.017
0.009
0.019
0.013
0.011
0.017
0.011
0.008
0.014
0.009
0.005
0.010
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.083
0.027
0.087
0.137
0.092
0.165
0.112
0.129
0.170
0.065
0.031
0.072
0.125
0.085
0.151
0.100
0.118
0.154
0.055
0.020
0.059
0.113
0.078
0.137
0.088
0.107
0.138
0.045
0.026
0.051
0.101
0.070
0.122
0.076
0.096
0.122
0.035
0.013
0.037
0.089
0.063
0.109
0.064
0.085
0.106
0.021
0.009
0.022
0.077
0.056
0.095
0.052
0.074
0.090
0.016
0.011
0.019
0.065
0.049
0.081
0.040
0.063
0.074
0.014
0.008
0.016
0.053
0.041
0.067
0.028
0.052
0.059
0.011
0.005
0.012
0.041
0.034
0.053
0.016
0.042
0.044
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.274
0.207
0.343
0.220
0.177
0.282
0.254
0.191
0.317
0.197
0.162
0.255
0.233
0.175
0.291
0.173
0.146
0.226
0.213
0.160
0.266
0.149
0.131
0.198
0.193
0.144
0.240
0.126
0.115
0.170
0.172
0.128
0.214
0.103
0.100
0.143
0.152
0.113
0.189
0.079
0.084
0.115
0.132
0.097
0.163
0.056
0.069
0.088
0.111
0.082
0.138
0.032
0.053
0.061
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
5
5
292
386
584
772
948
948
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
5
442
884
1018
5
586
1172
1018
5
712
1424
1135
5
1192
2384
1348
5
1586
3172
1348
10
1892
3784
2270
10
2384
4768
2696
L1, L2, L3
N
PE = Enclosure
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
3/16
Siemens LV 72 2005
mm2
mm2
mm2
kWh/m 2.43
kWh
2.9
2.55
2.9
3.02
2.9
3.16
2.9
4.35
2.9
6.66
2.9
6.77
2.9
9.1
2.9
13.6
2.9
m
m
kg/m
2
2
25.3
2
2
28.2
2
2
35.2
3
2
41.9
3
2
66.3
3
2
85.5
3
2
107.2
3
2
133.2
2
2
20.7
IP54
Ie
LXC
A
0153
1000
0253
1250
0353
1400
0453
1600
0553
2000
0653
2500
0753
3200
0853
4000
0953
5000
1053
Resistance
Reactance
Impedance
R'20
X'20
Z'20
m/m
m/m
m/m
0.065
0.027
0.071
0.051
0.031
0.059
0.044
0.020
0.048
0.037
0.026
0.045
0.027
0.013
0.030
0.017
0.009
0.019
0.013
0.011
0.017
0.011
0.008
0.014
0.009
0.005
0.010
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.083
0.027
0.087
0.116
0.088
0.145
0.149
0.129
0.197
0.065
0.031
0.072
0.104
0.081
0.131
0.133
0.118
0.177
0.055
0.020
0.059
0.091
0.073
0.116
0.117
0.107
0.158
0.045
0.026
0.051
0.079
0.066
0.102
0.101
0.096
0.139
0.035
0.013
0.037
0.067
0.058
0.088
0.085
0.085
0.120
0.021
0.009
0.022
0.055
0.050
0.074
0.069
0.074
0.101
0.016
0.011
0.019
0.043
0.043
0.060
0.053
0.063
0.082
0.014
0.008
0.016
0.031
0.035
0.046
0.037
0.052
0.063
0.011
0.005
0.012
0.020
0.027
0.033
0.021
0.042
0.046
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.203
0.187
0.276
0.293
0.177
0.342
0.183
0.171
0.250
0.262
0.162
0.308
0.162
0.155
0.224
0.230
0.146
0.272
0.142
0.139
0.198
0.199
0.131
0.238
0.120
0.122
0.171
0.168
0.115
0.203
0.100
0.106
0.145
0.137
0.100
0.169
0.079
0.090
0.119
0.105
0.084
0.134
0.059
0.074
0.094
0.074
0.069
0.101
0.038
0.058
0.069
0.043
0.053
0.068
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
5
5
292
386
292
386
948
948
292
386
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
5
442
442
1018
442
5
586
586
1018
586
5
712
712
1135
712
5
1192
1192
1348
1192
5
1586
1586
1348
1586
10
1892
1892
2270
1892
10
2384
2384
2696
2384
L1, L2, L3
N
PE = Enclosure
+ busbar
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
mm2
mm2
mm2
mm2
kWh/m 2.43
2.9
kWh
2.55
2.9
3.02
2.9
3.16
2.9
4.35
2.9
6.66
2.9
6.77
2.9
9.1
2.9
13.6
2.9
m
m
kg/m
2
2
25.3
2
2
28.2
2
2
35.2
3
2
41.9
3
2
66.3
3
2
85.5
3
2
107.2
3
2
133.2
2
2
20.7
Siemens LV 72 2005
3/17
Short-circuit rating
Rated short-time withstand current
for phase conductors
for neutral conductor
of the 5th conductor
Rated impulse withstand current
Conductor material
Number of busbars
Conductor cross-section
Equivalent copper cross-section
IP54
Ie
LXC
A
0154
1000
0254
1250
0354
1400
0454
1600
0554
2000
0654
2500
0754
3200
0854
4000
0954
5000
1054
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.116
0.088
0.145
0.112
0.129
0.170
0.051
0.031
0.059
0.065
0.031
0.072
0.104
0.081
0.131
0.100
0.118
0.154
0.044
0.020
0.048
0.055
0.020
0.059
0.091
0.073
0.116
0.088
0.107
0.138
0.037
0.026
0.045
0.045
0.026
0.051
0.079
0.066
0.102
0.076
0.096
0.122
0.027
0.013
0.030
0.035
0.013
0.037
0.067
0.058
0.088
0.064
0.085
0.106
0.017
0.009
0.019
0.021
0.009
0.022
0.055
0.050
0.074
0.052
0.074
0.090
0.013
0.011
0.017
0.016
0.011
0.019
0.043
0.043
0.060
0.040
0.063
0.074
0.011
0.008
0.014
0.014
0.008
0.016
0.031
0.035
0.046
0.028
0.052
0.059
0.009
0.005
0.010
0.011
0.005
0.012
0.020
0.027
0.033
0.016
0.042
0.044
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.203
0.187
0.276
0.220
0.177
0.282
0.183
0.171
0.250
0.197
0.162
0.255
0.162
0.155
0.224
0.173
0.146
0.226
0.142
0.139
0.198
0.149
0.131
0.198
0.120
0.122
0.171
0.126
0.115
0.170
0.100
0.106
0.145
0.103
0.100
0.143
0.079
0.090
0.119
0.079
0.084
0.115
0.059
0.074
0.094
0.056
0.069
0.088
0.038
0.058
0.069
0.032
0.053
0.061
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
6
6
292
386
584
772
948
948
292
386
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
6
442
884
1018
442
6
586
1172
1018
586
6
712
1424
1135
712
6
1192
2384
1348
1192
6
1586
3172
1348
1586
12
1892
3784
2270
1872
12
2384
4768
2696
2384
L1, L2, L3
N
PE = Enclosure
+ busbar
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
3/18
Siemens LV 72 2005
mm2
mm2
mm2
mm2
kWh/m 2.92
2.9
kWh
3.06
2.9
3.63
2.9
3.79
2.9
5.22
2.9
7.99
2.9
8.13
2.9
10.92
2.9
16.32
2.9
m
m
kg/m
2
2
29
2
2
32.4
2
2
40.8
3
2
48.6
3
2
77.5
3
2
100.4
3
2
125.4
3
2
155.9
2
2
23.5
IP54
Ie
LXC
A
0161
1000
0261
1250
0361
1400
0461
1600
0561
2000
0661
2500
0761
3200
0861
4000
0961
5000
1061
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.137
0.092
0.165
0.149
0.129
0.197
0.051
0.031
0.059
0.065
0.031
0.072
0.125
0.085
0.151
0.133
0.118
0.177
0.044
0.020
0.048
0.055
0.020
0.059
0.113
0.078
0.137
0.117
0.107
0.158
0.037
0.026
0.045
0.045
0.026
0.051
0.101
0.070
0.122
0.101
0.096
0.139
0.027
0.013
0.030
0.035
0.013
0.037
0.089
0.063
0.109
0.085
0.085
0.120
0.017
0.009
0.019
0.021
0.009
0.022
0.077
0.056
0.095
0.069
0.074
0.101
0.013
0.011
0.017
0.016
0.011
0.019
0.065
0.049
0.081
0.053
0.063
0.082
0.011
0.008
0.014
0.014
0.008
0.016
0.053
0.041
0.067
0.037
0.052
0.063
0.009
0.005
0.010
0.011
0.005
0.012
0.041
0.034
0.053
0.021
0.042
0.046
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.274
0.207
0.343
0.293
0.177
0.342
0.254
0.191
0.317
0.262
0.162
0.308
0.233
0.175
0.291
0.230
0.146
0.272
0.213
0.160
0.266
0.199
0.131
0.238
0.193
0.144
0.240
0.168
0.115
0.203
0.172
0.128
0.214
0.137
0.100
0.169
0.152
0.113
0.189
0.105
0.084
0.134
0.132
0.097
0.163
0.074
0.069
0.101
0.111
0.082
0.138
0.043
0.053
0.068
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
5
5
292
386
292
386
948
948
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
5
442
442
1018
5
586
586
1018
5
712
712
1135
5
1192
1192
1348
5
1586
1586
1348
10
1892
1892
2270
10
2384
2384
2696
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
mm2
mm2
mm2
kWh/m 2.43
2.9
kWh
2.55
2.9
3.02
2.9
3.16
2.9
4.35
2.9
6.66
2.9
6.77
2.9
9.1
2.9
13.6
2.9
m
m
kg/m
2
2
25.3
2
2
28.2
2
2
35.2
3
2
41.9
3
2
66.3
3
2
85.5
3
2
107.2
3
2
133.2
2
2
20.7
1) Insulated PE conductor
Siemens LV 72 2005
3/19
Short-circuit rating
Rated short-time withstand current
for phase conductors
for neutral conductor
of the 5th conductor
Rated impulse withstand current
Conductor material
Number of busbars
Conductor cross-section
Equivalent copper cross-section
IP54
Ie
LXC
A
0162
1000
0262
1250
0362
1400
0462
1600
0562
2000
0662
2500
0762
3200
0862
4000
0962
5000
1062
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'20
X'20
Z'20
R'
X'
Z'
R'F
X'F
Z'F
R'F
X'F
Z'F
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
m/m
0.065
0.027
0.071
0.083
0.027
0.087
0.137
0.092
0.165
0.112
0.129
0.170
0.051
0.031
0.059
0.065
0.031
0.072
0.125
0.085
0.151
0.100
0.118
0.154
0.044
0.020
0.048
0.055
0.020
0.059
0.113
0.078
0.137
0.088
0.107
0.138
0.037
0.026
0.045
0.045
0.026
0.051
0.101
0.070
0.122
0.076
0.096
0.122
0.027
0.013
0.030
0.035
0.013
0.037
0.089
0.063
0.109
0.064
0.085
0.106
0.017
0.009
0.019
0.021
0.009
0.022
0.077
0.056
0.095
0.052
0.074
0.090
0.013
0.011
0.017
0.016
0.011
0.019
0.065
0.049
0.081
0.040
0.063
0.074
0.011
0.008
0.014
0.014
0.008
0.016
0.053
0.041
0.067
0.028
0.052
0.059
0.009
0.005
0.010
0.011
0.005
0.012
0.041
0.034
0.053
0.016
0.042
0.044
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
R'0
X'0
Z'0
R'0
X'0
Z'0
m/m
m/m
m/m
m/m
m/m
m/m
0.274
0.207
0.343
0.220
0.177
0.282
0.254
0.191
0.317
0.197
0.162
0.255
0.233
0.175
0.291
0.173
0.146
0.226
0.213
0.160
0.266
0.149
0.131
0.198
0.193
0.144
0.240
0.126
0.115
0.170
0.172
0.128
0.214
0.103
0.100
0.143
0.152
0.113
0.189
0.079
0.084
0.115
0.132
0.097
0.163
0.056
0.069
0.088
0.111
0.082
0.138
0.032
0.053
0.061
rms value t = 1 s
rms value t = 1 s
rms value t = 1 s
Peak value
ICW
ICW
ICW
IPK
kA
kA
kA
kA
38
50
23
30
23
30
80
110
Copper
6
6
292
386
584
772
948
948
57
34
34
125
60
36
36
132
75
45
45
165
86
51
51
189
100
60
60
220
150
70
70
255
150
70
70
255
6
442
884
1018
6
586
1172
1018
6
712
1424
1135
6
1192
2384
1348
6
1586
3172
1348
12
1892
3784
2270
12
2384
4768
2696
Combustive energy
Trunking unit
without tap-off point
per tap-off point
Max. fixing intervals
for normal mechanical load
Busbar position: horizontal, edgewise
Busbar position: horizontal, flat
Weights
1) Insulated PE conductor
3/20
Siemens LV 72 2005
mm2
mm2
mm2
kWh/m 2.92
2.9
kWh
3.06
2.9
3.63
2.9
3.79
2.9
5.22
2.9
7.99
2.9
8.13
2.9
10.92
2.9
16.32
2.9
m
m
kg/m
2
2
29
2
2
32.4
2
2
40.8
3
2
48.6
3
2
77.5
3
2
100.4
3
2
125.4
3
2
155.9
2
2
23.5
Hz
V
IEC/EN 60439 Parts 1 and 2, VDE 0660 Parts 500 and 502
Damp heat, constant, acc. to IEC 60068 Part-2-78
Damp heat, cyclic, acc. to IEC 60068 Part-2-30
-5/40/35
IP54
RAL 7035, light grey
see page 3/53 Dimensional drawings
see page 3/22 Weights
Paint finished steel enclosure
690
800
III/3, acc. to EN 604971
50
400
A
A
A
kA
80
160
400
630
100
200
125
250
8001)
10001)
12501)
mm2
1 x 25 ... 185
N, PE, ISO-PE
mm2
1 x 16 ... 35
V~
V-
3)
Terminal bolt
Cable entry
at the end
at the side
Multi-core cable
Cable grommets
Cable diameter (mm)
Single-core cable2), ALU plate, without apertures
M8
1 x 25 ... 185
2 x 25 ... 70
1 x 50 ... 150
2 x 25 ... 70
M8
1 x 25 ... 240
2 x 25 ... 240
1 x 70 ... 240
2 x 70 ... 120
M12
1 x 25 ... 240
2 x 25 ... 240
1 x 70 ... 240
2 x 70 ... 120
M12
Yes
No
Yes
Yes
Yes
Yes
No
Yes
No
Yes
1 x M63
34 ... 48
2 x KT4
14 ... 68
12 x M40
2 x KT4
14 ... 68
12 x M40
2 x KT4
14 ... 68
12 x M40
4 x KT4
14 ... 68
24 x M40
A
A
kA
100
160
400
630
125
250
L1, L2, L3
mm2
1 x 35 ... 95
N, PE, ISO-PE
mm2
1 x 16 ... 35
Terminal bolt
Cable entry
at the end
at the side
Multi-core cable
Cable grommets
Cable diameter (mm)
Single-core cable2), ALU plate, without apertures
1 x 95 ... 240
2 x 95 ... 120
1 x 95 ... 240
2 x 95 ... 120
M12
1 x 95 ... 240
2 x 95 ... 120
1 x 95 ... 240
2 x 95 ... 120
M12
M8
1 x 50 ... 240
2 x 50 ... 120
1 x 50 ... 240
2 x 50 ... 120
M8
Yes
No
Yes
Yes
Yes
Yes
No
Yes
1 x M63
34 ... 48
2 x KT4
14 ... 68
12 x M40
2 x KT4
14 ... 68
12 x M40
2 x KT4
14 ... 68
12 x M40
Siemens LV 72 2005
3/21
Type
LXA0152
LXA0252
LXA0452
LXA0552
LXA0652
LXA0752
LXA0852
LXA0952
LXA1052
LXC0152
LXC0252
LXC0352
LXC0452
LXC0552
LXC0652
LXC0752
LXC0852
LXC0952
LXC10521)
LXC0153
LXC0253
LXC0353
LXC0453
LXC0553
LXC0653
LXC0753
LXC0853
LXC0953
LXC10531)
LXC0154
LXC0254
LXC0354
LXC0454
LXC0554
LXC0654
LXC0754
LXC0854
LXC0954
LXC1054
Run
kg/m
10.6
12.0
15.2
20.8
25.6
31.3
42.0
51.3
62.6
17.9
21.6
24.1
29.7
35.3
55.2
70.6
88.9
110.5
Expansion unit
kg/m
44.6
137.9
20.7
24.0
26.4
31.5
36.6
54.7
68.8
90.1
109.8
Run
kg/m
11.6
13.3
17.0
23.8
29.3
36.3
48.5
59.2
73.2
20.7
25.3
28.2
35.2
41.9
66.3
85.5
107.2
133.2
20.7
25.3
28.2
35.2
41.9
66.3
85.5
107.2
133.2
23.5
29.0
32.4
40.8
48.6
77.5
100.4
125.4
155.9
Expansion unit1)
kg/m
59.5
184.0
27.6
32.0
35.2
42.0
48.8
73.0
92.0
120.0
146.4
27.6
32.0
35.2
42.0
48.8
73.0
92.0
120.0
146.4
37.6
43.6
48.0
57.3
66.5
99.5
125.0
163.8
200.0
3/22
Siemens LV 72 2005
-FA
PS/kg
30.4
89.6
13.4
15.6
17.1
20.5
23.4
35.6
44.7
58.6
71.4
-FA1)
PS/kg
40.5
119.5
17.9
20.8
22.8
27.3
31.2
47.5
59.6
78.1
95.2
17.9
20.8
22.8
27.3
31.2
47.5
59.6
78.1
95.2
24.3
28.4
31.0
37.3
42.5
64.7
81.2
106.0
129.0
-AS1
kg/m
14.6
15.7
18.4
20.5
27.3
31.9
46.9
54.9
64.2
22.4
26.0
28.6
34.1
39.6
59.3
74.6
97.7
119.1
-AS2
kg/m
14.4
15.5
18.2
20.3
27.0
31.5
46.3
54.3
63.4
22.1
25.7
28.2
33.7
39.2
58.7
73.7
96.6
117.7
Type
LXA0161
LXA0261
LXA0461
LXA0561
LXA0661
LXA0761
LXA0861
LXA0961
LXA1061
LXC0161
LXC0261
LXC0361
LXC0461
LXC0561
LXC0661
LXC0761
LXC0861
LXC0961
LXC10611)
LXA0162
LXA0262
LXA0462
LXA0562
LXA0662
LXA0762
LXA0862
LXA0962
LXA1062
LXC0162
LXC0262
LXC0362
LXC0462
LXC0562
LXC0662
LXC0762
LXC0862
LXC0962
LXC1062
-AS3
kg/m
14.2
15.3
18.0
20.0
26.7
31.2
45.8
53.8
62.8
21.9
25.5
28.0
33.4
38.8
58.1
72.9
95.6
116.5
-AS1-T
kg/m
17.4
18.7
21.9
24.5
32.6
38.1
56.0
65.7
76.4
26.7
31.1
34.2
40.8
47.3
70.9
89.0
116.7
142.2
Run
kg/m
11.6
13.3
17.0
23.8
29.3
36.3
48.5
59.2
73.2
20.7
25.3
28.2
35.2
41.9
66.3
85.5
107.2
133.2
12.6
14.7
18.9
26.8
33.1
41.3
55.0
67.2
83.7
23.5
29.0
32.4
40.8
48.6
77.5
100.4
125.4
155.9
-AS2-T
kg/m
16.8
18.1
21.2
23.6
31.5
36.8
54.0
63.4
74.3
25.8
30.0
33.0
39.3
45.7
68.4
86.0
112.7
137.2
-AS3-T
kg/m
16.3
17.5
20.5
22.9
30.5
35.7
52.0
61.4
71.7
25.1
29.1
31.9
38.1
44.3
66.4
83.3
109.3
133.1
Expansion unit1)
kg/m
59.5
184.0
27.6
32.0
35.2
42.0
48.8
73.0
92.0
120.0
146.4
37.6
43.6
48.0
57.3
66.5
99.5
125.0
163.8
200.0
-KE
PS/kg
130
120
120
122
122
128
134
134
-FA1)
PS/kg
40.5
119.5
17.9
20.8
22.8
27.3
31.2
47.5
59.6
78.1
95.2
24.3
28.4
31.0
37.3
42.5
64.7
81.2
106.0
129.0
Run
kg/m
9.6
10.6
13.3
17.8
21.8
26.3
35.5
43.4
52.1
15.0
17.8
19.9
24.2
28.6
44.0
55.8
70.7
87.8
Expansion unit
kg/m
33.5
103.4
15.6
18.0
19.8
23.7
27.5
41.0
51.6
67.6
82.4
-FA
PS/kg
22.8
67.2
10.0
11.7
13.0
15.4
17.6
26.7
33.5
44.0
53.5
-KB
kg/PS
4.1
4.8
5.3
6.3
8.7
7.3
10.9
13.8
18.0
22.0
27.6
-KB-AK1)
kg/PS
-EF
kg/PS
2.8
2.8
3.3
3.3
4.2
5.8
5.8
8.4
11.4
11.4
Weight
kg/PS
1.0
1.0
1.1
1.2
1.3
1.6
1.9
2.0
2.0
2.2
2.4
2.6
3.2
3.8
0.4
7.6
7.6
2.7
3.3
3.3
3.0
Siemens LV 72 2005
3/23
Weight
kg
9.5
9.5
9.5
19.0
19.0
19.0
37.2
37.2
4-pole
Type
LX-AK5(6)/LSH-80S-4
LX-AK5(6)/LSH-100S-4
LX-AK5(6)/LSH-125S-4
LX-AK5(6)/LSH-160S-4
LX-K5(6)/LSH-200S-4
LX-AK5(6)/LSH-250S-4
LX-AK(6)/LS-400S-4
LX-AK(6)/LS-630S-4
Weight
kg
11.0
11.0
11.0
20.5
20.5
20.5
40.0
40.0
Weight
kg
4-pole
Type
LX-AK5(6)/LS-EC50-H(L)S
LX-AK5(6)/LS-EC63-H(L)S
LX-AK5(6)/LS-EC80-H(L)S
LX-AK5(6)/LS-EC100-H(L)S
LX-AK5(6)/LS-EC125-H(L)S
LX-AK5(6)/LS-EC160-H(L)S
LX-AK5(6)/LS-EC200-H(L)S
LX-AK5(6)/LS-EC250-H(L)S
LX-AK5(6)/LS-EC315-H(L)S
LX-AK5(6)/LS-EC400-H(L)S
LX-AK5(6)/LS-EC630-H(L)S
LX-AK5(6)/LS-BE800-LS
LX-AK5(6)/LS-BE1000-LS
LX-AK5(6)/LS-BE1250-LS
Weight
kg
4-pole
Type
LX-AK5(6)/FSH-100NF-4
LX-AK5(6)/FSH-160NF-4
LX-AK5(6)/FSH-125IEC-4
LX-AK5(6)/FSH-125BS-4
LX-AK5(6)/FSH-250IEC-4
LX-AK5(6)/FSH-250BS-4
LX-AK(6)/FS400IEC-4
LX-AK(6)/FS400BS-4
LX-AK(6)/FS630IEC-4
LX-AK(6)/FS630BS-4
Weight
kg
9.8
19.6
10.1
10.1
21.8
21.8
34.2
34.2
3-pole
Type
LX-AK5(6)/LS-DC50-H(L)S
LX-AK5(6)/LS-AE(DC)63-H(L)S
LX-AK5(6)/LS-DC80-H(L)S
LX-AK5(6)/LS-AE(DC)100-H(L)S
LX-AK5(6)/LS-DC125-H(L)S
LX-AK5(6)/LS-AE(DC)160-H(L)S
LX-AK5(6)/LS-AE(DC)200-H(L)S
LX-AK5(6)/LS-AE(DC)250-H(L)S
LX-AK5(6)/LS-AE(DC)315-H(L)S
LX-AK5(6)/LS-AE(DC)400-H(L)S
LX-AK5(6)/LS-AE(DC)630-H(L)S
LX-AK5(6)/LS-AE800-LS
LX-AK5(6)/LS-AE1000-LS
LX-AK5(6)/LS-AE1250-LS
1) Details on request
Weight
kg
9.3
19.1
9.6
9.6
20.5
20.5
32.9
32.9
Weight
kg
0.3
0.4
LX-PEN400
LX-PEN630
3/24
Siemens LV 72 2005
Type
3.0
LX.....-3
+LX.....-S120-X*
2.0
LX.....-2
+LX.....-S120-X*
1.0
LX.....-1
0.35 - 0.99
LX.....-1W*
1.01 - 1.99
LX.....-2W*
+LX.....-S120-X*
2.01 - 2.99
LX.....-3W*
+LX.....-S120-X*
Type suffix
Fire barrier
Optional lengths
3
Phase sequence reversal unit
on request
1.25
Expansion unit1)
LX.....-P
&
1.0
LX.....-D
Expansion =
Note:
Fire barrier is possible for optional lengths from 1.04 m.
Siemens LV 72 2005
3/25
Type
3.0
0.67
LX.....-3-ADO-U
Type suffix
Tap-off point
AD
+LX-A
1.17
+LX-B
1.67
+LX-C
2.17
+LX-D
2.67
+LX-E
3.0
AD
AD
AD
AD
0.67
LX.....-3-AD
+LX-F
1.17
+LX-G
1.67
+LX-H
2.17
+LX-I
2.67
+LX-K
AD
2.0
1.17
LX.....-2-1AD
AD
Note:
When engineering the tap-off point(s) take into account the dimensions of the tap-off units, see chapter Planning and
Engineering.
3/26
Siemens LV 72 2005
Type
Type suffix
Fire barrier
Position of the
tap-off point
AD
m
3.0
2.17
LX.....-3-1AD
+LX.....-S120-X*
1.5 2.0
0.67 1.67
LX.....-1W*-1AD*
+LX.....-S120-X*
2.01 2.5
0.67 2.17
LX.....-2W*-1AD*
+LX.....-S120-X*
2.51 3.0
0.67 2.67
LX.....-3W*-1AD*
+LX.....-S120-X*
AD
3
0.3
AD
Note:
For positioning of fire barrier, see chapter Planning and
Engineering.
Siemens LV 72 2005
3/27
Length X
Length Y
Type
Type suffix
Fire barrier
Elbow
Left
LX.01 - 10
0.35
0.35
LX.....-LL
LX.01 - 10
0.35
0.71 - 1.22)
LX.....-LL-YB*
+LX.....-S120-X*
LX.01 - 10
0.71 - 1.21)
0.35
LX.....-LL-XB*
+LX.....-S120-X*
LX.01 - 10
0.35
0.35-0.7
LX.....-LL-Y*
LX.01 - 10
0.35-0.7
0.35
LX.....-LL-X*
Right
0.35
0.35
LX.....-LR
LX.01 - 10
0.35
0.71 - 1.22)
LX.....-LR-YB*
+LX.....-S120-X*
LX.01 - 10
0.71 - 1.21)
0.35
LX.....-LR-XB*
+LX.....-S120-X*
LX.01 - 10
0.35
0.35 - 0.7
LX.....-LR-Y*
LX.01 - 10
0.35 - 0.7
0.35
LX.....-LR-X*
LX.01 - 04
0.35
0.35
LX.....-LV
LX.05 - 07
0.5
0.5
Knee
Front
LX.08 - 10
0.8
0.8
LX.01 - 04
0.35
0.71 - 1.22)
LX.05 - 07
0.5
0.86 - 1.32)
LX.08 - 10
0.8
1.16 - 1.62)
LX.01 - 04
0.35
0.35 - 0.7
LX.05 - 07
0.5
0.5 - 0.85
LX.08 - 10
0.8
0.8 - 1.15
LX.01 - 04
0.71 - 1.21)
0.35
LX.05 - 07
0.86 - 1.31)
0.5
LX.08 - 10
1.16 - 1.61)
0.8
LX.01 - 04
0.35 - 0.7
0.35
LX.05 - 07
0.5 - 0.85
0.5
LX.08 - 10
0.8 - 1.15
0.8
LX.01 - 04
0.35
0.35
LX.05 - 07
0.5
0.5
LX.....-LV-YB*
+LX.....-S120-X*
LX.....-LV-Y*
LX.....-LV-XB*
+LX.....-S120-X*
LX.....-LV-X*
Rear
X
Y
LX.01 - 10
LX.08 - 10
0.8
0.8
LX.01 - 04
0.35
0.71 - 1.22)
LX.05 - 07
0.5
0.86 - 1.32)
LX.08 - 10
0.8
1.16 - 1.62)
LX.01 - 04
0.35
0.35 - 0.7
LX.05 - 07
0.5
0.5 - 0.85
LX.08 - 10
0.8
0.71 - 1.2
LX.05 - 07
0.86 - 1.31)
LX.08 - 10
1.16 - 1.61)
0.8
LX.01 - 04
0.35 - 0.7
0.35
LX.05 - 07
0.5 - 0.85
0.5
LX.08 - 10
0.8 - 1.15
0.8
3/28
Siemens LV 72 2005
LX.....-LH-YB*
+LX.....-S120-X*
LX.....-LH-Y*
0.8 - 1.15
1)
LX.01 - 04
LX.....-LH
0.35
LX.....-LH-XB*
+LX.....-S120-X*
0.5
LX.....-LH-X*
Length X
m
LX.01 - 04
0.35
LX.05 - 07
0.5
Length Y
m
Length Z
m
Type
0.35
0.4
LX.....-LLV
0.35
0.52
Elbow offset
Left, front
LX.08 - 10
0.8
0.35
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.35 - 0.7
0.52 - 0.85
LX.08 - 10
0.8 - 1.15
0.35 - 0.7
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.5
0.35
0.52
LX.....-LLV-X*/Y*/Z*
Left, rear
LX.....-LLH
LX.08 - 10
0.8
0.35
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.35 - 0.7
0.52 - 0.85
LX.08 - 10
0.8 - 1.15
0.35 - 0.7
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.5
0.35
0.52
LX.08 - 10
0.8
0.35
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.35 - 0.7
0.52 - 0.85
LX.08 - 10
0.8 - 1.15
0.35 - 0.7
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.5
0.35
0.52
LX.....-LLH-X*/Y*/Z*
Right, front
LX.....-LRV
LX.....-LRV-X*/Y*/Z*
Right, rear
LX.....-LRH
LX.08 - 10
0.8
0.35
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.35 - 0.7
0.52 - 0.85
LX.08 - 10
0.8 - 1.15
0.35 - 0.7
0.84 - 1.15
LX.....-LRH-X*/Y*/Z*
Siemens LV 72 2005
3/29
Length X
m
Length Y
m
Length Z
m
Type
LX.01 - 04
0.35
LX.05 - 07
0.35
0.35
0.4
LX.....-LHL
0.5
0.52
Knee, offset
Rear, left
LX.08 - 10
0.35
0.8
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.35 - 0.7
0.5 - 0.85
0.52 - 0.85
LX.08 - 10
0.35 - 0.7
0.8 - 1.15
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.35
0.5
0.52
LX.....-LHL-X*/Y*/Z*
Rear, right
LX.08 - 10
0.35
0.8
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.35 - 0.7
0.5 - 0.85
0.52 - 0.85
LX.08 - 10
0.35 - 0.7
0.8 - 1.15
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.35
0.5
0.52
LX.08 - 10
0.35
0.8
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.35 - 0.7
0.5 - 0.85
0.52 - 0.85
LX.08 - 10
0.35 - 0.7
0.8 - 1.15
0.84 - 1.15
LX.01 - 04
0.35
0.35
0.4
LX.05 - 07
0.35
0.5
0.52
LX.08 - 10
0.35
0.8
0.84
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.35 - 0.7
0.5 - 0.85
0.52 - 0.85
LX.08 - 10
0.35 - 0.7
0.8 - 1.15
0.84 - 1.15
LX.....-LHR
LX.....-LHR-X*/Y*/Z*
Front, left
LX.....-LVL
LX.....-LVL-X*/Y*/Z*
Front, right
3/30
Siemens LV 72 2005
LX.....-LVR
LX.....-LVR-X*/Y*/Z*
Length X
m
Length Y
m
Length Z
m
Type
LX.01 - 04
0.35
LX.05 - 07
0.5
0.35
0.4-0.7
LX.....-ZV-Z*
0.5
0.7-1.0
1.33-1.6
Z units, edgewise
Front
LX.08 - 10
0.8
0.8
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
0.7 - 1.0
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
1.33 - 1.6
LX.01 - 04
0.35
0.35
0.4-0.7
LX.05 - 07
0.5
0.5
0.7-1.0
1.33-1.6
LX.....-ZV-X*/Y*/Z*
Rear
LX.08 - 10
0.8
0.8
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
0.7 - 1.0
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
1.33 - 1.6
LX.....-ZH-Z*
LX.....-ZH-X*/Y*/Z*
Z units, flat
Left
LX.01 - 10
0.35
0.35
0.4 - 0.7
LX.....-ZL-Z*
LX.01 - 10
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.....-ZL-X*/Y*/Z*
LX.01 - 10
0.35
0.35
0.4 - 0.7
LX.....-ZR-Z*
LX.01 - 10
0.35 - 0.7
0.35 - 0.7
0.4 - 0.7
LX.....-ZR-X*/Y*/Z*
Right
X
Y
Siemens LV 72 2005
3/31
Length X
m
Length Y
m
Length Z
m
Type
LX.01 - 04
0.35
0.35
0.35
LX.....-TV
LX.05 - 07
0.5
0.5
0.5
T units, edgewise
T branch, above
LX.08 - 10
0.8
0.8
0.8
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.35 - 0.7
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
0.5 - 0.85
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
0.8 - 1.15
LX.01 - 04
0.35
0.35
0.35
LX.05 - 07
0.5
0.5
0.5
LX.....-TV-X*/Y*/Z*
Y
X
T branch, below
LX.08 - 10
0.8
0.8
0.8
LX.01 - 04
0.35 - 0.7
0.35 - 0.7
0.35 - 0.7
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
0.5 - 0.85
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
0.8 - 1.15
3/32
Siemens LV 72 2005
LX.....-TH
LX.....-TH-X*/Y*/Z*
1400
04
1250
1600
05
1600
2000
06
2000
2500
07
2500
3200
08
3200
4000
09
4000
5000
10
4500
63002)
Code No.1):
Conductor configurations:
41
51
L1 + L2 + L3 + PEN
L1 + L2 + L3 + N + PE
Lug spacing:
Code No. Lug spacing
1
Conductor
material
A
Al
C
Cu
LX . ..
m
L1/L2/L3/PEN(N)
LXA(C)01 to 02: 0.11 0.40
LXA(C)03 to 05: 0.14 0.40
LXA(C)06 to 07: 0.16 0.40
LXA(C)08 to 10: 0.28 0.40
L1/L2/L3
0.45 0.75
L1/L2/L3
0.41 0.75
m
see left
PEN(N)-L2
LXA(C)01 to 05: 0.15 0.40
LXA(C)06 to 07: 0.16 0.40
LXA(C)08 to 10: 0.28 0.40
PEN(N)-L1(L3)
LXA(C)01 to 05: 0.15 0.40
LXA(C)06 to 07: 0.16 0.40
LXA(C)08 to 10: 0.28 0.40
.. -AS.(-T)
1) Universal connection units of systems with code number 30, 52, 53, 54,
61 and 62 are only available on request
2) Technical clarification required before offer is submitted
Siemens LV 72 2005
3/33
Phase sequence
LX connection
L1/L2/L3/PEN(N)
PEN(N)/L3/L2/L1
1
2
+LX- ..
Flange plate
+LX-FLP
3/34
Siemens LV 72 2005
..
AS1/AS3
A
B
C
D
AS2
E
F
G
H
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX connection
Type suffix
Lug spacing
L1/L2/L3/PEN(N)
up to 0.40
L1/L2/L3
PEN(N)-L1(L3)
0.41 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.
+LX-1A
+LX-P*(/N*)
PEN(N)
L3
L2
L1
(PE)
a
(PE)
(PE)
L1
L2
L3
PEN(N)
L3
L2
LX.....-AS.
+LX-2A
+LX-P*(/N*)
LX.....-AS.
+LX-1B
+LX-P*(/N*)
LX.....-AS.
+LX-2B
+LX-P*(/N*)
PEN(N)
L1
L1
L2
L3
PEN(N)
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
Siemens LV 72 2005
3/35
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3/PEN(N)
up to 0.40
L1/L2/L3
PEN(N)-L1(L3)
0.41 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.
+LX-1C
+LX-P*(/N*)
LX.....-AS.
+LX-2C
+LX-P*(/N*)
LX.....-AS.
+LX-1D
+LX-P*(/N*)
LX.....-AS.
+LX-2D
+LX-P*(/N*)
PEN(N)
L1
L2
L3
(PE)
PEN(N)
L1
L2
L3
(PE)
L3
L2
L1
PEN(N)
(PE)
L3
L2
L1
PEN(N)
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
3/36
Siemens LV 72 2005
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3
PEN(N)-L2
0.45 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS2
+LX-1E
+LX-P*(/N*)
L3
PEN(N)
L2
L1
(PE)
LX.....-AS2
+LX-2E
+LX-P*(/N*)
LX.....-AS2
+LX-1F
+LX-P*(/N*)
LX.....-AS2
+LX-2F
+LX-P*(/N*)
L3
PEN(N)
L2
L1
(PE)
L1
L2
PEN(N)
L3
(PE)
L1
L2
PEN(N)
L3
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
Siemens LV 72 2005
3/37
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3
PEN(N)-L2
0.45 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS2
+LX-1G
+LX-P*(/N*)
LX.....-AS2
+LX-2G
+LX-P*(/N*)
LX.....-AS2
+LX-1H
+LX-P*(/N*)
LX.....-AS2
+LX-2H
+LX-P*(/N*)
L1
PEN(N)
L2
L3
(PE)
(PE)
L3
L2
L1
PEN(N)
L3
L2
PEN(N)
L1
(PE)
L3
L2
PEN(N)
L1
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
3/38
Siemens LV 72 2005
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3/PEN(N)
up to 0.40
L1/L2/L3
PEN(N)-L1(L3)
0.41 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.-T
+LX-1A
+LX-P*(/N*)
PEN(N)
L3
L2
L1
(PE)
LX.....-AS.-T
+LX-2A
+LX-P*(/N*)
LX.....-AS.-T
+LX-1B
+LX-P*(/N*)
LX.....-AS.-T
+LX-2B
+LX-P*(/N*)
PEN(N)
L3
L2
L1
(PE)
L1
L2
L3
PEN(N)
(PE)
L1
L2
L3
PEN(N)
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
Siemens LV 72 2005
3/39
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3/PEN(N)
up to 0.40
L1/L2/L3
PEN(N)-L1(L3)
0.41 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.-T
+LX-1C
+LX-P*(/N*)
LX.....-AS.-T
+LX-2C
+LX-P*(/N*)
LX.....-AS.-T
+LX-1D
+LX-P*(/N*)
LX.....-AS.-T
+LX-2D
+LX-P*(/N*)
PEN(N)
L1
L2
L3
(PE)
PEN(N)
L1
L2
L3
(PE)
L3
L2
L1
PEN(N)
(PE)
L3
L2
L1
PEN(N)
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
3/40
Siemens LV 72 2005
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3
PEN(N)-L2
0.45 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.-T
+LX-1E
+LX-P*(/N*)
L3
PEN(N)
L2
L1
(PE)
LX.....-AS.-T
+LX-2E
+LX-P*(/N*)
LX.....-AS.-T
+LX-1F
+LX-P*(/N*)
LX.....-AS.-T
+LX-2F
+LX-P*(/N*)
L3
PEN(N)
L2
L1
(PE)
L1
L2
PEN(N)
L3
(PE)
L1
L2
PEN(N)
L3
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
Siemens LV 72 2005
3/41
Note:
Figures in brackets and dotted items apply to
the 5-conductor system.
Type suffix
Phase sequence/
LX-connection
Type suffix
Lug spacing
L1/L2/L3
PEN(N)-L2
0.45 0.75
LXA(C)01 to 05:
0.15 0.40
LXA(C)06 to 07:
0.16 0.40
LXA(C)08 to 10:
0.28 0.40
LX.....-AS.-T
+LX-1G
+LX-P*(/N*)
LX.....-AS.-T
+LX-2G
+LX-P*(/N*)
LX.....-AS.-T
+LX-1H
+LX-P*(/N*)
LX.....-AS.-T
+LX-2H
+LX-P*(/N*)
L1
PEN(N)
L2
L3
(PE)
(PE)
L3
L2
L1
PEN(N)
L3
L2
PEN(N)
L1
(PE)
L3
L2
PEN(N)
L1
(PE)
Note:
Fitting an aluminium flange plate (Type suffix +LX-FLP) allows
the connection unit to be attached to a distribution board/transformer enclosure.
3/42
Siemens LV 72 2005
Version
Type suffix1)
Aluminium
baseplate
Type
Code No.
Cu
Code No.
Conductor configurations:
800
C01
1000
Code No.
C01
41
L1 + L2 + L3 + PEN
1000
C02
1250
C02
51
L1 + L2 + L3 + N + PE
1400
C03
1250
C04
1600
C04
1600
A052)
2000
C05
System
max. mm2
2000
C06
2500
C06
LX.01 02
4 300
2500
C07
3200
C07
LX.03 05
6 300
LX.06 07
8 300
... ..
IP54
LX.....-KE1
IP55
LX.....-KE1-IP55
IP54
LX.....-KE2
IP55
LX.....-KE2-IP55
+LX-BPAL
+LX-BPAL
1) It is essential that the type suffix LX-BPAL aluminium baseplate be specified for single-conductor cable entries.
2) All cable feeder units are made of copper.
Siemens LV 72 2005
3/43
Code No.
Cu
800
C01
1000
Code No.
Conductor configurations:
30
L1 + L2 + L3 + PE1)
C01
41
L1 + L2 + L3 + PEN/PEN4)
L1 + L2 + L3 + N + PE1)
Code No.
1000
C02
1250
C02
51
1400
C03
52
L1 + L2 + L3 + N + N3) + PE1)
1250
C04
1600
C04
535)
L1 + L2 + L3 + N + PE/PE4)
1600
A056)
2000
C05
545)
L1 + L2 + L3 + N + N3) + PE/PE4)
2000
C06
2500
C06
61
L1 + L2 + L3 + N + (PE)2) + PE1)
2500
C07
3200
C07
62
3200
C08
4000
C08
4000
C09
5000
C09
4500
A106)
63007)
C10
... ..
LX.....-FA
1) PE conductor = Enclosure
2) Separate PE conductor by means of an insulated busbar (Clean Earth)
3) Double cross-section of neutral conductor (200%) by means of additional
busbar
4) PE(PEN) conductor = busbar and enclosure
5) Only available as copper system (LXC)
6) These types have copper conductors
7) Technical clarification required before offer is submitted
Note:
When connections to non-Siemens connection units are used
in distribution board installations, it is necessary to ensure
that the permissible temperature limit of 135 C for the busbars
is not exceeded at an average ambient temperature of 35 C
over a mean time of 24 hours.
The rated current specifications stated in the table apply to the
limit temperature of 135 C.
The short-circuit rating of connections to non-Siemens distribution boards depends on the copper connections in the distribution board installation.
3/44
Siemens LV 72 2005
Length X
m
Length Y
m
Type
LX.01 - 10
0.35 - 0.70
0.2 - 0.55
LX.....-FLL-X*/Y*
LX.01 - 10
0.35 - 0.70
0.2 - 0.55
LX.....-FLR-X*/Y*
&
Extension terminal
Left
Right
3
Connection knee
Rear
0.35 - 0.70
0.35 - 0.70
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
LX.01 - 04
0.35 - 0.70
0.35 - 0.70
LX.05 - 07
0.5 - 0.85
0.5 - 0.85
LX.08 - 10
0.8 - 1.15
0.8 - 1.15
LX.....-FLH-X*/Y*
LX.01 - 04
Front
LX.....-FLV-X*/Y*
Siemens LV 72 2005
3/45
Equipment features
Can be fitted/removed while the system is live
Power tap-off via tap-off point
Degree of protection IP54
Tap-off units LX-AK/... and LX-AK5/...
- Can only be fitted on LX ... 3., LX ... 4. and LX ... 5. systems
LX-AK6/... tap-off units
- Connection device for insulated PE conductor
- Can only be fitted on LX ... 6. systems
Circuit-breaker
3-pole circuit-breaker
4-pole circuit-breaker
Rated current Ie [A]
at Ue = 400 V and IP54
80
100
125
160
200
250
LX system conductor
configuration
LX...30(41)(51)(52)(53)(54)
LX...61(62)
Cable connection
- Single-core1) and multi-core connection
- Maximum cross-section only up to 100 % neutral conductor
for the LX ... 52, LX ... 54 and LX ... 62 systems
Cable entry
- From the end: tap-off units up to 125 A
- At the side and end: tap-off units from 160 to 400 A
- At the side: tap-off units 630 A
3
4
80S
100S
125S
160S
200S
250S
up to125 A
Code No.
5
6
LX-AK./LSH-....-.
160 - 250 A
630 A (without end entry opening)
Circuit-breaker
3
3-pole circuit-breaker
4
4-pole circuit-breaker
LX-AK/LS-400S-.
LK-AK6/LS-400S-.
630
LX-AK/LS-630S-.
LK-AK6/LS-630S-.
LX-PEN400
630 A
LX-PEN630
400 A
3/46
Siemens LV 72 2005
Equipment features
Circuit-breakers (3- and 4-pole versions) in H version
Mount and dismount when live
IP54 degree of protection as standard
Tap-off units LX-AK5/LS-...
- Can only be fitted on LX ... 3., LX ... 4. and LX ... 5. systems
Tap-off units LX-AK6/LS-...
- Connection device for insulated PE conductor
- Can only be fitted on LX ... 6. systems
Cable connection for multi-core or single core cables1)
- Maximum cross-section up to 100 % neutral conductor for the
LX ... 52, LX ... 54 and LX ... 62 systems
Cable entry
- From the end: tap-off units up to 125 A
- At the side and end: tap-off units from 160 to 400 A
- At the side: tap-off units 630 A
Circuit-breaker
release for system and line protection as
Electronic release, for time selectivity, 3 pole
Thermomagnetic release, 4 pole
Thermomagnetic release, 3 pole
With handle
4-pole circuit-breakers (EC release) feature 100% release
(% 100 A) and 60% release (. 100 A) on neutral pole.
With adjustable electronic overload and fixed short-circuit releases with AE version (3 pole)
With adjustable thermal overload and adjustable short-circuit
releases with EC version (4 pole)
With adjustable thermal overload and adjustable short-circuit
releases with DC version (3 pole)
Predefined locations for the installation of three current converters and max. 20 of 2.5 mm2 control current terminals
50
63
80
100
125
160
200
250
315
400
630
up to 125 A
Circuit-breaker with manual operation LX-AK./LSH-. . . . .-.HS
Circuit-breaker with motor drive
LX-AK./LSM-. . . . .-.HS
LX-PEN400
630 A
LX-PEN630
160 - 630 A
1) Undrilled aluminium plate, cable glands to be provided by user,
see Technical specifications.
2) The PEN jumpers for use in tap-off units with TN-C grids must be ordered
separately.
Siemens LV 72 2005
3/47
Equipment features
Can be fitted/removed while the system is live
Power tap-off via tap-off point
Degree of protection IP54
Tap-off units LX-AK(5)/FS...
- Can only be fitted on LX ... 3., LX ... 4. and LX ... 5. systems
Tap-off units LX-AK6/FS...
- Connection device for insulated PE conductor
- Can only be fitted on LX ... 6. systems
Cable connection
- Single-core1) and multi-core connection
- Maximum cross-section only up to 100% neutral conductor
for the LX ... 52, LX ... 54 and LX ... 62 systems
Cable entry
- From the end: tap-off units up to 125 A
- At the side and end: tap-off units from 160 to 400 A
- At the side: tap-off units 630 A
125...
250...
Code No.
Switch type
3
3-pole circuit-breaker
4
4-pole circuit-breaker
5
6
LX...30(41)(51)(52)(53)(54)
LX...61(62)
IEC standard
BS standard
up to 125 A
LX-AK./FSH-......-.
Fuses to
IEC
BS
Rated current Ie [A] at Ue = 400 V and IP54
400
630
IEC-Standard
BS-Standard
400...
630...
Switch type
3
3-pole circuit-breaker
4
4-pole circuit-breaker
160 A up to 250 A
630 A (without end entry opening)
LX-AK/FS-......-.
LX-AK6/FS-......-.
Code No.
LX...30(41)(51)(52)(53)(54)
LX...61(62)
5
6
Switch type
3
3-pole circuit-breaker
4
4-pole circuit-breaker
LX-AK./FSH-......-.
PEN-jumper for TN-C grids2)
up to 400 A
630 A
400 A
LX-PEN400
LX-PEN630
3/48
Siemens LV 72 2005
Equipment features
Circuit-breakers (3- and 4-pole versions) in L version
Permanently installed, cannot be fitted or removed when the
system is live
Tap-off via joint block
IP54 degree of protection as standard
Tap-off units can only be installed on LXA05... to LXA10... and
LXC05... to LXC10... systems
Tap-off units LX-AK5/LS-...
- Can only be fitted on LX ... 3., LX ... 4. and LX ... 5. systems
Tap-off units LX-AK6/LS-...
- Connection device for insulated PE conductor
- Can only be fitted on LX ... 6. systems
Circuit-breaker
release for system and line protection as
AE
Electronic release, selective, 3 pole
BE
Electronic release, selective, 4 pole
LX system conductor
configuration
LX...30(41)(51)(52)(53)(54)
LX...61(62)
Code No.
5
6
800
1000
1250
800
1000
1250
&
Circuit-breaker with manual operation
Circuit-breaker with motor drive
LX-AK./LSH-. . . . . -LS
LX-AK./LSM-. . . . . -LS
LX. . . . .-KB-AK
Siemens LV 72 2005
3/49
Accessories
for mounting and fixing
Length
for
system
Type
all
LX....-KB
L = 140
all in IP54
LX....-EF
x = 25
all in IP55
LX....-EF-IP55
L = 700
all
LX....-S120-MOS
LX02-IP55
LX04-IP55
LX.05..
LX05-IP55
LX07-IP55
LX.08..
LX08-IP55
LX10-IP55
LX02-6-IP55
LX04-6-IP55
LX.05..
LX05-6-IP55
LX07-6-IP55
LX.08..
LX08-6-IP55
LX10-6-IP55
mm
&
End flange
x = joint block centre
3
Fire barrier
For installation on site with fire protective plates,
mineral wool, Mylar film and fixing screws
Only available for LX.01... to LX.07... single systems
3/50
Siemens LV 72 2005
Type
flexible
LX-BH
LX-BHF
Cu
LXA01
LXC01
Code No.
LXA02
LXC02
LXC03
LXA04
LXC04
LXA05
LXC05
05
LXA06
LXC06
07
LXA07
LXC07
LXA08
LXC08
08
LXA09
LXC09
10
LXA10
LXC10
02
04
3
flexible
LX..-BF
LX..-BFF
LX-K
LX-KF
Clamping bracket
Comes as a pair
Siemens LV 72 2005
3/51
Type
power transmission
LX....-BV
power distribution
LX....-BV-AK
3
Fixing bracket for vertical installation with fixed point
LX.01 - 07
LX-BVFP1
LX.08 - 10
LX-BVFP2
Connection tool
LX-V
3/52
Siemens LV 72 2005
Dimensional drawings
Straight trunking units without tap-off points
PEN(N)
L1
L2
L3
NSV0_00334
LXA(C)01 to 07
NSV0_00335
320
145
l
LXA(C)08 to 10
NSV0_00336
System
LXA(C)01
LXA(C)02
LXC03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA10
l
350 3000
145
a
137
137
162
162
207
287
287
439
599
599
Siemens LV 72 2005
3/53
PEN(N)
L1
L2
L3
NSV0_00332
LXA(C)01 to 07
NSV0_00369
320
145
330
330
l
LXA(C)08 to 10
NSV0_00333
330
330
l
System
LXA(C)01
LXA(C)02
LXC03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA10
3/54
l
350 3000
Siemens LV 72 2005
a
137
137
162
162
207
287
287
439
599
599
145
1000
LXA(C)01 to 07
NSV0_00368
320
253.5
493
253.5
1000
LXA(C)08 to 10
NSV0_00331
253.5
493
253.5
1000
System
LXA(C)01
LXA(C)02
LXC03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA10
a
190
190
215
215
260
340
340
492
652
652
b
205
205
205
205
205
205
205
205
205
205
Siemens LV 72 2005
3/55
NSV0_00327
L1 L2 L3 PEN(N)
y
NSV0_00328
LXA(C)01 to 07
145
NSV 0_00330
LXA(C)08 to 10
145
System
LXA(C)01
LXA(C)02
LXC03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA10
3/56
x
350 700 (1100)
Siemens LV 72 2005
y
350 700 (1100)
a
137
137
162
162
207
287
287
439
599
599
NSV0_00325
LXA(C)01 to 07
L1 L2 L3 PEN(N)
145
NSV0_00326
LXA(C)08 to 10
L1 L2 L3 PEN(N)
System
LXA(C)01
LXA(C)02
LXC03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA10
145
x
350 700 (1100)
y
350 700 (1100)
a
137
137
162
162
207
287
287
439
599
599
Siemens LV 72 2005
3/57
h2
h1
PE
L1(L3)
PEN(N)
b1
b2
b2
NSV0_00358
a1)
8
l 2)
PE
PEN(N)
L1(L3)
a1)
8
b1
p
l 2)
1) Reference dimension for engineering = centre joint block to centre of first connection lug.
For further details: see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
b1
b2
h1
h2
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
255
255
255
255
255
255
255
315
315
315
140
140
140
140
140
140
140
200
200
200
140
140
140
140
140
140
140
200
200
200
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
137
137
162
162
207
287
287
439
599
599
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
3/58
Siemens LV 72 2005
p
min.
115
115
135
135
135
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
NSV0_00359
h2
h1
h2
h1
LX .....-AS3(+LX-.A)/(+LX-.C)
L1(L3)
PEN(N)
a1)
n
b1
NSV0_00370
PE
b2
l 2)
h1
LX .....-AS3(+LX-.B)/(+LX-.D)
h2
L1(L3)
PEN(N)
a1)
8
b1
b2
l 2)
NSV0_00360
PE
1) Reference dimension for engineering = centre joint block to centre of first connection lug.
For further details: see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
a
255
255
255
255
255
255
255
315
315
315
b1
140
140
140
140
140
140
140
200
200
200
b2
140
140
140
140
140
140
140
200
200
200
h
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
h1
137
137
162
162
207
287
287
439
599
599
h2
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
p
min.
405
405
405
405
405
405
405
405
405
405
max.
750
750
750
750
750
750
750
750
750
750
n
min.
150
150
150
150
150
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
Siemens LV 72 2005
3/59
h2
h1
LX.....-AS2(+LX-.E)/(+LX-.G)
PEN(N)
L2
PE
a1)
b1
b2
NSV0_00361
L1(L3)
p
l 2)
h2
PE
L1(L3)
PEN(N)
L2
a1)
b1
b2
p
l 2)
1) Reference dimension for engineering = centre joint block to centre of first connection lug.
For further details see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
3/60
a
255
255
255
255
255
255
255
315
315
315
b1
140
140
140
140
140
140
140
200
200
200
b2
140
140
140
140
140
140
140
200
200
200
Siemens LV 72 2005
h
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
h1
137
137
162
162
207
287
287
439
599
599
h2
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
p
min.
450
450
450
450
450
450
450
550
550
550
max.
750
750
750
750
750
750
750
750
750
750
n
min.
150
150
150
150
150
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
NSV0_00362
h1
LX.....-AS2(+LX-.F)/(+LX-.H)
h2
h1
a1)
L1(L3) PEN(N)
PE
b1
p
l
NSV0_00363
8
b2
2)
LX.....-AS1-T(+LX-.B)/(+LX-.D)
h2
h1
a1)
PEN(N)
8
L1(L3)
b1
p
l
b2
2)
NSV0_00364
PE
1) Reference dimension for engineering = centre joint block to centre of first connection lug. (PEN(N) front)
For further details see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
b1
b2
h1
h2
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
1.5 x p
143
143
143
143
143
143
143
203
203
203
143
143
143
143
143
143
143
203
203
203
213
213
188
188
293
213
213
361
201
201
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
137
137
162
162
207
287
287
439
599
599
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
p
min.
115
115
135
135
135
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
Siemens LV 72 2005
3/61
h2
h1
a1)
PEN(N)
b2
8
b1
NSV0_00365
L1(L3)
PE
p
l 2)
LX.....-AS3-T(+LX-.B)/(+LX-.D)
h2
h1
a1)
L1(L3)
PEN(N)
8
b1
b2
l 2)
1) Reference dimension for engineering = centre joint block to centre of first connection lug. (PEN(N) front)
For further details see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
3/62
a
(2p + n)/2
b1
143
143
143
143
143
143
143
203
203
203
Siemens LV 72 2005
b2
143
143
143
143
143
143
143
203
203
203
c
213
213
188
188
293
213
213
361
201
201
h
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
h1
137
137
162
162
207
287
287
439
599
599
h2
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
p
min.
405
405
405
405
405
405
405
405
405
405
max.
750
750
750
750
750
750
750
750
750
750
n
min.
150
150
150
150
150
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
NSV0_00395
PE
h2
h1
a1)
PEN(N)
L1(L3)
n
b1
b2
NSV0_00366
L2
PE
p
l 2)
LX.....-AS2-T(+LX-.F)/(+LX-.H)
h2
h1
a1)
L1(L3)
L2
PEN(N)
n
b1
p
l
b2
2)
NSV0_00367
PE
1) Reference dimension for engineering = centre joint block to centre of first connection lug. (PEN(N) front)
For further details see Planning and Engineering Feeder units section.
2) The length l of the connection unit depends on the engineered connection lug spacings.
System
LXA(C)01
LXA(C)02
LXA(C)03
LXA(C)04
LXA(C)05
LXA(C)06
LXA(C)07
LXA(C)08
LXA(C)09
LXA(C)10
a=p
min.
450
450
450
450
450
450
450
450
450
450
max.
750
750
750
750
750
750
750
750
750
750
b1
b2
h1
h2
143
143
143
143
143
143
143
203
203
203
143
143
143
143
143
143
143
203
203
203
213
213
188
188
293
213
213
361
201
201
298.5
298.5
323.5
323.5
368.5
448.5
448.5
600.5
760.5
760.5
137
137
162
162
207
287
287
439
599
599
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
161.5
n
min.
150
150
150
150
150
155
155
275
275
275
max.
400
400
400
400
400
400
400
400
400
400
Siemens LV 72 2005
3/63
LXC03..
LXC04..
LXA05..
LXC05..
LXA06..
Material thickness 10 mm
185
40
85
14
185
20
60
120
Material thickness 15 mm
NSV0_00357
50
100
NSV0_00356
60
Material thickness 15 mm
LXA08..
LXC08..
LXA09..
LXC09..
LXA10..
60
120
Material thickness 15 mm
3/64
Siemens LV 72 2005
60
60
120
60
120
85
14
40
20
NSV0_00372
20
40
14
185
185
PE connection lugs
LXA(C)01.. up to10
NSV0_00371
85
14
40
20
20
40
14
185
NSV0_00376
LXC06..
LXA07..
LXC07
Side view
c
22
36.5
PEN(N) L3 L2 L1
L1 L2 L3
KE1
230
NSV0_00345
NSV0_00346
550
KE2
87
NSV0_00355
280
470
a+120
60
40
NSV0_00347
35
View Z
9
40
120
320
470
LXC01.. - KE.
LXC02.. - KE.
LXC03.. - KE.
LXC04.. - KE.
LXA05.. - KE.
LXC05.. - KE.
LXC06.. - KE.
LX07.. - KE.
450
450
650
650
650
650
800
800
3 x 90
3 x 90
5 x 90
5 x 90
5 x 90
5 x 90
7 x 90
7 x 90
137
137
162
162
207
207
287
287
420
420
620
620
620
620
770
770
NSV0_00390
435
Siemens LV 72 2005
3/65
e
=
=
L1
LX.0830 to 1030
L2
75
L3
75
PE
PE
NSV0_00379
NSV0_00378
NSV0_00384
n
q
3
Adapter, straight
Type
LXC0130-FA
LXC0230-FA
LXC0330-FA
LXC0430-FA
LXC0530-FA
LXA0530-FA
LXC0630-FA
LXC0730-FA
LXC0830-FA
LXC0930-FA
LXA1030-FA
LXC1030-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
h
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
h
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
n
145
145
145
145
145
145
145
145
145
145
145
q
400
400
400
400
400
400
400
400
400
400
400
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0130-FLL(R)(H)(V)-X*/Y*
LXC0230-FLL(R)(H)(V)-X*/Y*
LXC0330-FLL(R)(H)(V)-X*/Y*
LXC0430-FLL(R)(H)(V)-X*/Y*
LXC0530-FLL(R)(H)(V)-X*/Y*
LXA0530-FLL(R)(H)(V)-X*/Y*
LXC0630-FLL(R)(H)(V)-X*/Y*
LXC0730-FLL(R)(H)(V)-X*/Y*
LXC0830-FLL(R)(H)(V)-X*/Y*
LXC0930-FLL(R)(H)(V)-X*/Y*
LXA1030-FLL(R)(H)(V)-X*/Y*
LXC1030-FLL(R)(H)(V)-X*/Y*2)
3/66
Siemens LV 72 2005
q
400
400
400
400
400
400
400
400
400
400
400
L1
e
=
75
L2
LX.084(5)1 to 104(5)1
PEN(N)
L3
PE
PE
NSV0_00379
NSV0_00378
NSV0_00377
75
LX.014(5)1 to 074(51)
Adapter, straight
Type
LXC0141(51)-FA
LXC0241(51)-FA
LXC0341(51)-FA
LXC0441(51)-FA
LXC0541(51)-FA
LXA0541(51)-FA
LXC0641(51)-FA
LXC0741(51)-FA
LXC0841(51)-FA
LXC0941(51)-FA
LXA1041(51)-FA
LXC1041(51)-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
n
145
145
145
145
145
145
145
145
145
145
145
q
400
400
400
400
400
400
400
400
400
400
400
q
400
400
400
400
400
400
400
400
400
400
400
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0141(51)-FLL(R)(H)(V)-X*/Y*
LXC0241(51)-FLL(R)(H)(V)-X*/Y*
LXC0341(51)-FLL(R)(H)(V)-X*/Y*
LXC0441(51)-FLL(R)(H)(V)-X*/Y*
LXC0541(51)-FLL(R)(H)(V)-X*/Y*
LXA0541(51)-FLL(R)(H)(V)-X*/Y*
LXC0641(51)-FLL(R)(H)(V)-X*/Y*
LXC0741(51)-FLL(R)(H)(V)-X*/Y*
LXC0841(51)-FLL(R)(H)(V)-X*/Y*
LXC0941(51)-FLL(R)(H)(V)-X*/Y*
LXA1041(51)-FLL(R)(H)(V)-X*/Y*
LXC1041(51)-FLL(R)(H)(V)-X*/Y*2)
Siemens LV 72 2005
3/67
75
N
L3
L2
LX.0852 to 1052
f
=
=
L1
LX.0152 to 0752
PE
PE
NSV0_00379
NSV0_00378
NSV0_00380
75
n
q
Adapter, straight
Type
LXC0152-FA
LXC0252-FA
LXC0352-FA
LXC0452-FA
LXC0552-FA
LXA0552-FA
LXC0652-FA
LXC0752-FA
LXC0852-FA
LXC0952-FA
LXA1052-FA
LXC1052-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
103.5
104.5
103.5
104.5
103.5
104.5
103.5
104.5
104.5
103.5
104.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
103.5
104.5
103.5
104.5
103.5
104.5
103.5
104.5
104.5
103.5
104.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
n
145
145
145
145
145
145
145
145
145
145
145
q
400
400
400
400
400
400
400
400
400
400
400
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0152-FLL(R)(H)(V)-X*/Y*
LXC0252-FLL(R)(H)(V)-X*/Y*
LXC0352-FLL(R)(H)(V)-X*/Y*
LXC0452-FLL(R)(H)(V)-X*/Y*
LXC0552-FLL(R)(H)(V)-X*/Y*
LXA0552-FLL(R)(H)(V)-X*/Y*
LXC0652-FLL(R)(H)(V)-X*/Y*
LXC0752-FLL(R)(H)(V)-X*/Y*
LXC0852-FLL(R)(H)(V)-X*/Y*
LXC0952-FLL(R)(H)(V)-X*/Y*
LXA1052-FLL(R)(H)(V)-X*/Y*
LXC1052-FLL(R)(H)(V)-X*/Y*2)
3/68
Siemens LV 72 2005
q
400
400
400
400
400
400
400
400
400
400
400
75
N
L3
L2
LX.0853 to 1053
f
=
=
L1
LX.0153 to 0753
PE
PE
NSV0_00379
NSV0_00378
NSV0_00380
75
Adapter, straight
Type
LXC0153-FA
LXC0253-FA
LXC0353-FA
LXC0453-FA
LXC0553-FA
LXA0553-FA
LXC0653-FA
LXC0753-FA
LXC0853-FA
LXC0953-FA
LXA1053-FA
LXC1053-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
120
120
120
120
120
120
120
120
120
120
120
g
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
120
120
120
120
120
120
120
120
120
120
120
g
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
n
145
145
145
145
145
145
145
145
145
145
145
q
400
400
400
400
400
400
400
400
400
400
400
q
520
520
520
520
520
520
520
520
520
520
520
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0153-FLL(R)(H)(V)-X*/Y*
LXC0253-FLL(R)(H)(V)-X*/Y*
LXC0353-FLL(R)(H)(V)-X*/Y*
LXC0453-FLL(R)(H)(V)-X*/Y*
LXC0553-FLL(R)(H)(V)-X*/Y*
LXA0553-FLL(R)(H)(V)-X*/Y*
LXC0653-FLL(R)(H)(V)-X*/Y*
LXC0753-FLL(R)(H)(V)-X*/Y*
LXC0853-FLL(R)(H)(V)-X*/Y*
LXC0953-FLL(R)(H)(V)-X*/Y*
LXA1053-FLL(R)(H)(V)-X*/Y*
LXC1053-FLL(R)(H)(V)-X*/Y*2)
Siemens LV 72 2005
3/69
L3
(PE)
j
NSV0_00392
NSV0_00393
NSV0_00396
L2
LX.0854 to 1054
=
L1
LX.0154 to 0754
n
q
Adapter, straight
Type
LXC0154-FA
LXC0254-FA
LXC0354-FA
LXC0454-FA
LXC0554-FA
LXA0554-FA
LXC0654-FA
LXC0754-FA
LXC0854-FA
LXC0954-FA
LXA1054-FA
LXC1054-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
123.5
124.5
123.5
124.5
123.5
124.5
123.5
124.5
124.5
123.5
124.5
g
96.5
95.5
96.5
95.5
96.5
95.5
96.5
95.5
95.5
96.5
95.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
j
6
8
6
8
6
8
6
8
8
6
8
k1) l
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
123.5
124.5
123.5
124.5
123.5
124.5
123.5
124.5
124.5
123.5
124.5
g
96.5
95.5
96.5
95.5
96.5
95.5
96.5
95.5
95.5
96.5
95.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
n
145
145
145
145
145
145
145
145
145
145
145
q
520
520
520
520
520
520
520
520
520
520
520
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0154-FLL(R)(H)(V)-X*/Y*
LXC0254-FLL(R)(H)(V)-X*/Y*
LXC0354-FLL(R)(H)(V)-X*/Y*
LXC0454-FLL(R)(H)(V)-X*/Y*
LXC0554-FLL(R)(H)(V)-X*/Y*
LXA0554-FLL(R)(H)(V)-X*/Y*
LXC0654-FLL(R)(H)(V)-X*/Y*
LXC0754-FLL(R)(H)(V)-X*/Y*
LXC0854-FLL(R)(H)(V)-X*/Y*
LXC0954-FLL(R)(H)(V)-X*/Y*
LXA1054-FLL(R)(H)(V)-X*/Y*
LXC1054-FLL(R)(H)(V)-X*/Y*2)
3/70
Siemens LV 72 2005
l
200
200
200
200
200
200
200
200
200
200
200
q
520
520
520
520
520
520
520
520
520
520
520
L3
(PE)
j
PE
PE
n
q
NSV0_00378
NSV0_00379
NSV0_00382
75
L2
75
LX.0861 to 1061
f
=
=
L1
LX.0161 to 0761
Adapter, straight
Type
LXC0161-FA
LXC0261-FA
LXC0361-FA
LXC0461-FA
LXC0561-FA
LXA0561-FA
LXC0661-FA
LXC0761-FA
LXC0861-FA
LXC0961-FA
LXA1061-FA
LXC1061-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
120
120
120
120
120
120
120
120
120
120
120
g
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
120
120
120
120
120
120
120
120
120
120
120
g
100
100
100
100
100
100
100
100
100
100
100
h
6
8
6
8
6
8
6
8
8
6
8
i
6
8
6
8
6
8
6
8
8
6
8
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
l
200
200
200
200
200
200
200
200
200
200
200
n
145
145
145
145
145
145
145
145
145
145
145
q
520
520
520
520
520
520
520
520
520
520
520
q
520
520
520
520
520
520
520
520
520
520
520
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0161-FLL(R)(H)(V)-X*/Y*
LXC0261-FLL(R)(H)(V)-X*/Y*
LXC0361-FLL(R)(H)(V)-X*/Y*
LXC0461-FLL(R)(H)(V)-X*/Y*
LXC0561-FLL(R)(H)(V)-X*/Y*
LXA0561-FLL(R)(H)(V)-X*/Y*
LXC0661-FLL(R)(H)(V)-X*/Y*
LXC0761-FLL(R)(H)(V)-X*/Y*
LXC0861-FLL(R)(H)(V)-X*/Y*
LXC0961-FLL(R)(H)(V)-X*/Y*
LXA1061-FLL(R)(H)(V)-X*/Y*
LXC1061-FLL(R)(H)(V)-X*/Y*2)
Siemens LV 72 2005
3/71
L3
(PE)
j
PE
PE
NSV0_00379
NSV0_00378
NSV0_00396
75
L2
75
LX.0862 to 1062
f
=
=
L1
LX.0162 to 0762
n
q
Adapter, straight
Type
LXC0162-FA
LXC0262-FA
LXC0362-FA
LXC0462-FA
LXC0562-FA
LXA0562-FA
LXC0662-FA
LXC0762-FA
LXC0862-FA
LXC0962-FA
LXA1062-FA
LXC1062-FA2)
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
123.5
124.5
123.5
124.5
123.5
124.5
123.5
124.5
124.5
123.5
124.5
g
96.5
95.5
96.5
95.5
96.5
95.5
96.5
95.5
95.5
96.5
95.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
j
6
8
6
8
6
8
6
8
8
6
8
k1) l
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
85 200
m
230
230
230
230
230
230
230
230
230
230
230
n
145
145
145
145
145
145
145
145
145
145
145
a
50
50
75
75
120
120
200
200
120
200
200
b
137
137
162
162
207
207
287
287
439
599
599
c
280
280
305
305
350
350
430
430
582
742
742
d
100
100
100
100
100
100
100
100
100
100
100
e
120
120
120
120
120
120
120
120
120
120
120
f
123.5
124.5
123.5
124.5
123.5
124.5
123.5
124.5
124.5
123.5
124.5
g
96.5
95.5
96.5
95.5
96.5
95.5
96.5
95.5
95.5
96.5
95.5
h
6
8
6
8
6
8
6
8
8
6
8
i
12
16
12
16
12
16
12
16
16
12
16
j
6
8
6
8
6
8
6
8
8
6
8
k1)
85
85
85
85
85
85
85
85
85
85
85
n
145
145
145
145
145
145
145
145
145
145
145
FLL(R)(H)(V)-X*/Y*, angle
Type
LXC0162-FLL(R)(H)(V)-X*/Y*
LXC0262-FLL(R)(H)(V)-X*/Y*
LXC0362-FLL(R)(H)(V)-X*/Y*
LXC0462-FLL(R)(H)(V)-X*/Y*
LXC0562-FLL(R)(H)(V)-X*/Y*
LXA0562-FLL(R)(H)(V)-X*/Y*
LXC0662-FLL(R)(H)(V)-X*/Y*
LXC0762-FLL(R)(H)(V)-X*/Y*
LXC0862-FLL(R)(H)(V)-X*/Y*
LXC0962-FLL(R)(H)(V)-X*/Y*
LXA1062-FLL(R)(H)(V)-X*/Y*
LXC1062-FLL(R)(H)(V)-X*/Y*2)
3/72
Siemens LV 72 2005
l
200
200
200
200
200
200
200
200
200
200
200
520
520
520
520
520
520
520
520
520
520
520
q
520
520
520
520
520
520
520
520
520
520
520
LX.08.. - FA
LX.09 (10).. - FA
Type1)
LXC01..-FA
LXC02..-FA
LXC03..-FA
LXC04..-FA
LXA05..-FA
LXC05..-FA
LXC06..-FA
LXC07..-FA
LXC08..-FA
LXC09..-FA
LXA10..-FA
a
210
210
235
235
280
280
360
360
512
672
672
b
125
125
137.5
137.5
160
160
200
200
c
280
280
305
305
350
350
430
430
582
742
742
d
145
145
155
155
180
180
220
220
295
375
375
e
200
200
215
215
235
235
275
275
350
430
430
Siemens LV 72 2005
3/73
LX.08.. - FA
LX.09 (10).. - FA
Type1)
LXC01..-FA
LXC02..-FA
LXC03..-FA
LXC04..-FA
LXA05..-FA
LXC05..-FA
LXC06..-FA
LXC07..-FA
LXC08..-FA
LXC09..-FA
LXA10..-FA
a
210
210
235
235
280
280
360
360
512
672
672
b
125
125
137.5
137.5
160
160
200
200
c
280
280
305
305
350
350
430
430
582
742
742
d
145
145
155
155
180
180
220
220
295
375
375
e
200
200
215
215
235
235
275
275
350
430
430
3/74
Siemens LV 72 2005
LXC03..-FA
LXC04..-FA
75
50
17,5
40
120
17,5 18
30 60 30
LXC06..-FA
LXC07..-FA
20
18
230
40
230
NSV0_00341
NSV0_00340
230
40
40
20
20
= 18
NSV0_00389
LXA05..-FA
LXC05..-FA
LXC08..-FA
352
232
120
=
30 60 30
200
18
233
40
NSV0_00339
230
40
NSV0_00342
200
20
18
80
50 50 25
20
25 50
LXC09..-FA
LXA10..-FA
200
25 50 50 50 25
50
25 18
40
200
NSV0_00344
233
NSV0_00343
197
80
40
20
18
20
100
25
Siemens LV 72 2005
3/75
75
72,5
375
NSV0_00405
519
3
LX-AK5(6)/LS-AE(EC)(DC)50(63)(80)(100)(125)-H(L)S
LX-AK5(6)/LSH-80(100)(125)S-3(4)
1)
1)
191
338.5
1) on request
75
60,5
375
NSV0_00406
519
LX-AK5(6)/FSH-125IEC(BS)-3(4)
LX-AK5(6)/FSH-100NF-3(4)
3/76
Siemens LV 72 2005
a
226
226
b
361.5
361.5
Installed device
3VL...
NZM7
72,5
375
75
NSV0_00403
102,2
729
LX-AK5(6)/LS-AE(EC)(DC)160(200)(250)-H(L)S
LX-AK5(6)/LSH-160(200)(250)S-3(4)
1)
1)
191.2
338.5
Installed device
3VL...
NZM7
1) on request
60,5
375
75
NSV0_00404
102,2
729
LX-AK5(6)/FSH-250IEC(BS)-3(4)
LX-AK5(6)/FSH-160NF-3(4)
a
226.2
226.2
b
361.7
361.7
Siemens LV 72 2005
3/77
27
x. 1
194
ma
790
90
990
LX-AK(6)/FS-400IEC(BS)-3(4)
NSV0_00337
163
562,5
30
a
325.5
328.5
Installed device
NZM10
NH2
418
NSV0_00338
855
15
870
LX-AK(6)/FS-630IEC(BS)-3(4)
329
LX-AK(6)/LS-630S-3(4)
LX-AK6/FS-630IEC(BS)-3(4)
75,05
533
NSV0_00388
86
LX-AK(6)/LS-400S-3(4)
LX-AK(6)/FS-400IEC(BS)-3(4)
66
36
3/78
Siemens LV 72 2005
910
a
64.5
47
Installed device
NZM10
NH3
NSV0_00374
NSV0_00375
On request
Accessories
IP55 flange for degree of protection enhancement
LX-02(4)(5)(7)-IP55
LX02-IP55
LX04-IP55
LX05-IP55
LX07-IP55
NSV0_00407
7,5
60
380
60
LX-08(10)-IP55
a
LX08-IP55
LX10-IP55
NSV0_00402
7,5
60
380
b
60
Siemens LV 72 2005
3/79
153
153
LX.01 to 05
NSV0_00350
153
Type
LX.01..-KB
LX.02..-KB
LX.03..-KB
LX.04..-KB
LX.05..-KB
LX.06..-KB
LX.07..-KB
LX.08..-KB
LX.09..-KB
LX.10..-KB
154
320
a
137
137
162
162
207
287
287
439
599
599
Note:
Dimensions of the joint blocks for tap-off units (800 1250 A) on
request.
3/80
154
154
320
320
NSV0_00348
Siemens LV 72 2005
50
NSV0_00351
a
285
285
285
307
307
362
432
432
584
744
744
b
172
172
172
194
194
239
319
319
471
631
631
80
14
NSV0_00352
Type
LX-BH(F)
LX01..-BH(F)
LX02..-BH(F)
LX03..-BH(F)
LX04..-BH(F)
LX05..-BH(F)
LX06..-BH(F)
LX07..-BH(F)
LX08..-BH(F)
LX09..-BH(F)
LX10..-BH(F)
50
14
14
42,5
42,5
Clamping brackets
LX-KF
LX-K
58,5
10
NSV0_00400
2,5
15
60
51
60
35
10
NSV0_00401
24
40
11
50
40
30
2
12
12
55
30
8,5
14
24,5 16
20
165
130
LX-BVFP1(2)
57
11
42,5
NSV0_00353
12,5
90
15
100
Siemens LV 72 2005
3/81
13,5
42
156
42
101
18
220
NSV0_00391
300
336
NSV0_00398
240
156
42
100
101
158
100
220
13,5
57
NSV0_00399
20
42
180
400
580
7
3/82
Siemens LV 72 2005
4/2
4/3
4/7
4/9
4/9
4/11
4/11
4/12
4/12
4/12
4/13
Basics
Project handling, order processing
Overview
Basic technical information
Design
Clearance from structural bodies
Design
Feeder Units
Universal connection units
Application
Design
Universal connection units
with T branch
Application
Design
Cable feeder units
Application
Design
Connection to non-Siemens
distribution boards
Overview
Connection to Siemens 8PV/8PT
power distribution systems
Overview
4/25
Busbar runs
Reference dimensions for engineering
Design
Consumer tap-offs for
straight trunking units
Design
Fire barrier
Overview
Design
Expansion unit and fixed point
Overview
Design
Horizontal busbar runs
Design
Vertical busbar runs
Design
4/28
4/28
Tap-offs
Tap-off units
Overview
Design
4/14
4/14
4/15
4/16
4/16
4/19
4/19
4/24
4/30
4/30
4/30
4/30
Special cases
Functional endurance (on request)
Overview
Application
Phase sequence reversal units
Overview
Application
Siemens LV 72 2005
Overview
Project handling
Engineering is performed in six stages:
Determine and check building dimensions
Procure floor plans to scale.
Check drawing dimensions on site.
Record dimensions on site if no floor plans are available.
Convert them into binding documentation.
Immediately after receipt of order, make the order reservation
in the production factory.
Decide on and draw busbar runs
Draw a scale plan view of the busbar layout on the floor plans.
Co-ordinate the busbar runs with other equipment installations.
Take minimum clearances into consideration.
Transfer the dimensions decided on to an isometric representation.
Ensure that the tap-off points are useful and accessible.
Note the minimum clearances to the jointing points between
trunking units when the respective tap-off units are fitted.
Take busbar runs and building expansion into consideration
when engineering expansion compensation. External influences resulting from building expansions can be compensated with expansion compensation.
When engineering the horizontal busbar runs, pay attention to
the PE(N) position for vertical mounting.
4/2
Siemens LV 72 2005
Sequence to be followed:
Enter the dimensions of the feeder units, straight trunking units,
angle and branch units, and tap-off points etc. for the run.
Define types
Create parts lists
Order processing
If appropriate, agree staged deliveries for large orders.
Always mark parts with the Drawing Item No., in order to ensure
identification at the installation site.
When drawing up the orders
- Match delivery dates to the construction phases/to construction progress.
- Ensure delivery for installation at different points on the construction site by structured busbar run designation or staggered ordering.
Customer-specific non-standard solutions (on request)
Immediately after the order has been placed, request the ordering data from the technical department responsible.
Note:
Customized solutions always have longer lead times.
Optional lengths
After determining exact dimensions place order in a separate
order.
Order documents (send to factory)
Binding order
Parts list
Engineering drawings.
Design
Conductor material
The conductor materials used in LX systems are aluminium for
(LXA) and copper for (LXC).
Busbar trunking systems with aluminium conductors are preferable due to their lower weight and lower costs.
a Aluminium busbar
s Tin-on-nickel plated
d Insulation with high thermal stability
Exceptions:
LXA07..: Rated current 2300 A
with busbar position horizontal, flat
LXA09..: Rated current 3800 A
with busbar position horizontal, flat
LXC01..: Rated current 900 A
with busbar position horizontal, flat
The busbar system has IP54 degree of protection as standard.
Enhancement of the degree of protection by fitting additional
components on site is only possible for power transmission (on
request).
Sizes, single systems and double systems
The size depends on the current rating and the conductor material. A total of 10 sizes are available. 7 sizes are single systems
and 3 sizes are double systems. The single system consists of
an enclosure each with 3 to 6 aluminium or copper busbars. The
double systems feature 6 to 12 busbars each in two enclosures.
The exact numbers of busbars depends on the required conductor configuration. There are eight different types of conductor
configurations.
145
145
a Copper busbar
s Tin plated
d Insulation with high thermal stability
Sizes (H x W1))
Height H
LX System
mm
137
LXA(C)01
LXA(C)02
137
LXC 03
162
LXA(C)04
162
LXA(C)05
207
LXA(C)06
287
LXA(C)07
287
LXA(C)08
439
LXA(C)09
599
LXA(C)10
599
1) Width W always 145 mm
Siemens LV 72 2005
4/3
Busbars
Enclosures
LX...30
L1
L2
L3
Busbars
Enclosures
LX...41
LX...51
L1
L1
L2
L2
L3
L3
PEN
N
Busbars
Enclosures
LX...52
LX...53
LX...61
L1
L1
L1
L2
L2
L2
L3
L3
L3
N
N
N
N
PE
(PE)
Busbars
Enclosures
LX...54
LX...62
4/4
L1
L1
L2
L2
Siemens LV 72 2005
L3
L3
N
N
N
N
PE
(PE)
L
R
In individual steps: The first screw head shears off as soon as the
defined torque is attained. Below this, a second screw head is
located which actually releases the clamp connection. When reusing the trunking unit (joint block), it must be retightened to the
defined torque of 120 10 Nm.
The joint block is fixed to the trunking unit. It does not compensate for longitudinal expansion of the trunking unit. The expansion unit must therefore be engineered in accordance with the
applicable engineering rules, see Expansion unit and fixed
point.
Type definition
General information
Tap-off points
a Joint block
d
b
d
Type reference
LXA(C)....-3-ADO-U
+LX-A+LX-B+LX-C
+LX-D+LX-E
LXA(C)....-3-AD
+LX-B+LX-D
LXA(C)....-2-1AD
LXA(C)....-3W2,80-1AD1,0
+LX..-S120-X0,60
Note:
Tap-off units may not be fitted in the joint block (flange cover)
connection area. The usability of the tap-off point therefore depends on the position and the dimensions of the tap-off point selected.
Details of all selectable dimensions in m.
Note a change in position of the tap-off points when the trunking
unit is rotated.
Siemens LV 72 2005
4/5
Limb designations
The limbs of angle and branch units have a fixed designation:
Limb without joint block fitted
= X limb
Limb with joint block fitted
= Y limb
Limb in between (where present)
= Z limb.
V
Z
Z unit (front)
e.g.: LXA(C).... -ZV
4/6
Siemens LV 72 2005
Design
Installation of horizontal busbar runs
0.25 m
The busbar run is assembled by fitting the trunking units together end to end (standard assembly).
230
230
a
a Busbar trunking unit with joint block
s Trunking unit without joint block
Note:
Use only the horizontal fixing brackets shown on the selection
pages for fixing the trunking units. These brackets ensure a safe
measure of play for the busbar run during operation. The clamping bracket can be secured to the fixing material on site.
Siemens LV 72 2005
4/7
W2 min
W1 min
Wmin = 0.1 m
Dmin = 0.1 m
4/8
Siemens LV 72 2005
Note:
The fixing screws for the vertical fixing brackets must always remain accessible.
The minimum wall clearance W2min depends on:
Fixing material required on site to compensate for uneven wall
surfaces or angles. The choice of the fixing material is dictated
by the load to be supported. The fixing brackets can be secured directly on the walls where there is no unevenness or angles.
Application
LX universal connection units are used as feeder units for transformers and for distribution board connection (with type suffix
+LD-FLP). A connection with the LX system can be established
via any of the trunking units or junction units listed in the catalogue.
Design
+LX-.A
+LX-.B
+LX-.C
+LX-.D
L1
PEN(N)
L3
PEN(N)
L2
L3
L2
L1
L3
L2
L1
L2
PEN(N)
L1
PEN(N)
L3
Lug spacing
(PE)
L3
PEN(N)
L2
+LX-1.
a Viewing direction
L1
a
(PE)
L1
L2
L3
PEN(N)
min.
max.
+LX-2.
115
400
115
400
115
400
+LX-.E
+LX-.F
+LX-.G
+LX-.H
L1
L3
L3
L1
L2
PEN(N)
L2
PEN(N)
PEN(N)
L2
PEN(N)
L2
L3
L1
L1
L3
450 750
150 405
Siemens LV 72 2005
4/9
Phase sequence
Note:
The type-related dimensions for a are listed in chapter
LXA/LXC busbar trunking system - Dimensional drawings.
+LX-.A
+LX-.B
+LX-.C
+LX-.D
L1
PEN(N)
L3
PEN(N)
L2
L3
L2
L1
L3
L2
L1
L2
PEN(N)
L1
PEN(N)
L3
200 mm
a
PEN (N)
450 750
150 400
4/10
Siemens LV 72 2005
Application
Design
The AS universal connection unit is supplied fitted
with connection lugs in fixed positions as specified by the
customer
with a connection (positioned centrally on the AS connection
unit) suitable for any of the trunking units or angle and branch
units listed in the catalogue (without joint block).
When engineering the phase sequence and lug spacing, it is important to note the direction of viewing:
Mounting position of the busbars within the trunking unit
edgewise
Direction of viewing from the AS trunking unit end with PEN(N)
on the right and T branch unit at the top.
Beyond this, the same rules regarding the relative phase sequences and lug spacings apply as for the universal connection unit without T branch.
200 mm
PEN (N)
+LX-1.
+LX-2.
a Viewing direction
s T branch
d PEN(N) location
Siemens LV 72 2005
4/11
Application
For feeding LX busbar systems when a cable connection is unavoidable.
Design
Rated currents of 800 A 3200 A, copper conductors only
Degree of protection IP54
Select the desired cable connection unit from the selection
pages
Cable connection unit supplied without joint block
Cable connection directly to the connection busbars of the
cable connection unit (bolt connection) for connection of:
4 multi-core or single-core
cables (up to 300 mm2)
6 multi-core or single-core
cables (up to 300 mm2)
8 multi-core or single core
cables (up to 300 mm2)
LXC01...-KE. to
LXC02...-KE.
LXC03...-KE. to
LXA(C)05...-KE.
LXC06...-KE. to
LXC07...-KE.
for
for
for
LXA(C)01... to
LXA(C)02...
LXA(C)03... to
LXA(C)05...
LXA(C)06... to
LXA(C)07...
LXC01...-KE. to
LXC02...-KE.
LXC03...-KE. to
LXA(C)05...-KE.
LXC06...-KE. to
LXC07...-KE.
for
for
for
LXA(C)01... to
LXA(C)02
LXA(C)03... to
LXA(C)05
LXA(C)06... to
LXA(C)07
Note:
M12 bolts for the cable connection are supplied with the unit.
Cable clamps for cable support must be provided on site.
No standard types are available for the LX...30, LX...52, LX...53,
LX...54, LX...61 and LX...62 systems. Please contact product
support if required.
Connection to
non-Siemens distribution boards
Overview
Short-circuit rating
Versions
The non-Siemens distribution board connection units feature
copper conductors. They are supplied without joint blocks.
Refer to the selection and ordering data for type references.
The short-circuit rating of connections to non-Siemens distribution boards is governed by the copper connections in the distribution board installation. Only the manufacturer of the distribution board installation can provide verification of the short-circuit
rating of the dropper bars.
The unit for connection to non-Siemens distribution boards is
supplied as a type-tested unit.
The rating of the copper connections must be matched to the required short-circuit level.
Connection to the SIVACON system
Version
Connection options
Since these units are used for customized solutions, early agreement with the distribution board manufacturer is necessary.
Whoever designs and installs the connections between the distribution board connection unit (Siemens product) and the distribution busbars of the non-Siemens distribution board, as a rule
the distribution board manufacturer, is responsible for this work.
Rated currents
The rated currents can be taken from the key to type references
in the selection pages. These specifications conform to
IEC/EN 60 439-1 and -2 for an ambient temperature of 35 C on
a 24 h mean. The limit temperature of the copper busbars insulated with a highly thermally stable material is 135 C.
When using non-Siemens connection units in distribution board
installations, it is necessary to ensure that the temperature limit
is not exceeded.
Terminal capacity for the copper connections see Chapter
LXA/LXC Busbar Truncking System Dimension drawings.
4/12
Siemens LV 72 2005
Overview
Connection possibilities
112
LX ...-KB
N L1 L2 L3 PE
(PEN)
LX .....-FA3(4)A
Rated currents
During engineering it has to be taken into account that the rated
currents of the distribution boards are not necessarily the same
as the ones of the busbar system selected.
a Front view
Fixed point
Dimensions b and d exactly determine the centre of the busbar
system above the distribution board. With this dimension as a
fixed point, engineering of the trunking unit can be carried out.
LX...
LX...-KB
NSV0_00528
LX.....-FA3(4)A
System type
SIVACON 8PV
LXA(C)..41(51)
Circuit-breaker type
Field width
1
mm 400.00
500.00
600.00
2
600.00
800.00
3
800.00
1000.00
d
b
mm 221.25
mm 200.00
221.25
250.00
221.25
300.00
214.251)
300.00
219.25
400.00
219.25
420.00
219.25
520.00
mm 842.75
mm 200.00
842.75
335.00
1011.252)
330.00
1011.252)
460.00
1016.25
400.00
1016.25
605.00
mm 842.75
mm 200.00
842.75
335.00
811.253)
330.00
811.253)
460.00
1016.25
400.00
1016.25
605.00
mm 295.25
mm 200.00
295.25
335.00
292.254)
320.00
292.254)
450.00
SIVACON 8PT,
Main busbar top
Main distribution board
LXA(C)..41(51)
d
b
Subdistribution board
LXA(C)..41(51)
d
b
SIVACON 8PT,
Main busbar at the rear
LXA(C)..41(51)
d
b
Siemens LV 72 2005
4/13
Design
Straight trunking units, standard lengths
Reference for engineering is the dimension from centre of joint
block to centre of joint block.
Dimensions of the tap-off point(s): Originating from trunking unit
end without joint block (designated by ).
Example: Standard length with tap-off points
Side view
e
Plan view
f Engineering dimensions middle tap-off point
g Engineering dimension of straight trunking unit
Side view
a
Plan view
a Trunking unit end without joint block
s Trunking unit end with joint block
4/14
Siemens LV 72 2005
Design
In order to install consumer tap-offs, suitable tap-offs from the
trunking unit have to be decided upon.
LX system dimensions:
Consumer tap-off
up to 630 A
Joint block
Trunking unit
Straight lengths with
tap-off points
Straight lengths without tap-off points
99.5
99.5
a Size 3 (400 A)
s Size 2 (160 A 250 A)
d Size 1 (80 A 125 A)
f Straight length with 3 tap-off
points:
LX....-3ADO-U+LX-A
+LX-C+LX-E
g Size 4 (630 A)
h Fixing side for joint block located at front.
92
870
765
545
d
f
325
1000
1000
675
99.5
910
c
b
d
Wmin = 2000
Siemens LV 72 2005
4/15
Overview
Where the busbar trunking system penetrates a fire wall or fire
ceiling, it must be fitted with a fire barrier.
The fire barrier can be fully fitted on the trunking unit ex-works if
required or supplied separately as an individual type for mounting on site. The engineering guidelines in this chapter apply for
both versions.
The instructions below apply to the engineering, ordering and
fitting of the fire barrier:
Engineering
Order type
Fitting
The fire barrier meets the requirements of the IEC/EN60439-2 and fire resistance class S120
to DIN 4102 Part 9, ISO 834.
1) Fire barrier for on site fitting only possible for LX.01.. to LX.07.. single systems.
Dimensions
Straight trunking units
LY
W
LX
LK
Design
L
LK
a
b
a Fire barrier
s Fire wall thickness up to 0.7 m.
Fire barrier for greater wall thickness on request.
Designation
Description
LX
LY
LK
4/16
Siemens LV 72 2005
Length
m
1.04 (1.14)1)
0.52 (0,57)1)
0.52 (0,57)1)
0.17
0.01
0.7 (0.8)1)
Fire barrier centre = fire wall/ceiling centre is not absolutely necessary. Ending the fire barrier flush with fire wall (ceiling) is permissible (see case 1). The fire barrier may not be only partly
positioned in the fire wall (ceiling) (see case 3).
Case 1: The fire barrier ends flush with the fire wall or ceiling.
W
LX
Application
The current busbar element with fire protection block may be fitted in minimum 15 cm thick walls of masonry or concrete and
steel or foam mortar as well as in minimum 15 cm thick ceilings
of concrete and steel or foam mortar with fire resistance class
F120 (fire resistant), designation (short designation) F120-AB, to
DIN4102-2.
Z
Apart from the positioning, the following points must be observed for fitting the trunking units with the fire barrier:
The opening between the busbar system elements and the
component must be fitted with mineral mortar or ZZ TS 90 fire
barrier compound.
The spaces between Promatect-H(L) panels and the trunking
elements, as well as components must be closed with ZZ
TS 90 fire barrier sealant (part of delivery).
The installation must be carried out according to the requirements of the general code of building practice (part of the
delivery).
Siemens LV 72 2005
4/17
100
1.22 (1.32)1)
0.7 (0.8)1)
PEN(N)
a After mounting of the busbar run in the fire wall/ceiling, any gaps must be
filled with mortar or concrete.
The mortar or concrete must conform to the valid standards for maintaining
the fire resistance class of the wall or the ceiling, e.g. DIN 1045 and
DIN 1053 part 1, as well as EN206-1 and EN998-2.
AD
0.33
0.52 (0.57)1)
Wmin
a Fire barrier
s Trunking unit
d Tap-off unit
f Space requirement for the tap-off unit (Note size!)
a After mounting of the busbar run in the fire wall, any gaps must be filled with
mortar or concrete. The mortar or concrete must conform to the valid standards for maintaining the fire resistance class of the wall or the ceiling, e.g.
DIN 1045 and DIN 1053 part 1, as well as EN206-1 and EN998-2.
3 und 4
2.40 (2.50)1)
2.07 (2.17)1)
1.20 (1.25)1)
4/18
mm
mm
mm
mm
430
430
430
430
430
430
430
430
430
430
420
420
450
450
490
570
570
720
880
880
200
200
200
200
200
200
200
200
200
200
190
190
220
220
260
340
340
490
650
650
Siemens LV 72 2005
Note:
Tap-off units must not be fitted above a fire barrier or a connection flange.
Fixing intervals
The first fixing brackets on systems with fire barrier must be fitted
with a maximum clearance of 820 mm on both sides from the fire
wall or fire ceiling.
More information
ZZ TS 90 fire barrier sealant can be obtained from:
Fa. Diederich Brandschutztechnik GmbH,
Unnauer Weg 3
50767 Kln
Tel.: +49 (221) 9 66 52-0;
Fax: +49 (221) 9 66 52-2
E-Mail: j.diederich@diederich-brandschutztechnik.de
Overview
The busbar pack and enclosure expand due to the heat losses
arising when the busbars are under load.
The lengthwise expansion of the busbar pack depends on:
The conductor material used in the busbar systems
The mode of installation of the busbar run
(horizontal or vertical)
Whether used for power transmission or distribution.
Design
Horizontal busbar run
Between a junction unit and end flange
L3
a
L2
L1
a Fixed points
L1 = max. 15 m
L2 = max. 30 m
L3 = max. 40 m
Number of fixed
points
0
1
2
Number of expansion
units
0
0
1
A distinction is made between fixed points for horizontal and vertical installations (see Selection and ordering data).
A fixed point must be attached to the following busbar components:
Universal connection units (AS and AS-T)
Cable connection units (KE)
Connection units for non-Siemens distribution boards (FA).
Depending on busbar run and lengths, also straight trunking
units and angle/branch units
Engineering for horizontal busbar runs
General procedure
Note the following for busbar runs:
Determine the busbar elements: feeder units, angle and
branch units, end flange
Determine the run lengths between busbar elements
Provide feeder units with fixed points
Use fixed points to divide up large busbar runs into partial busbar runs
Place the expansion unit centrally between two fixed points
a
L1
a
L2
L1
a Fixed points
Number of fixed
points
0
2
3
Number of expansion
units
0
1
2
Note:
The following applies to horizontal run lengths with expansion
compensation between two fixed points: max. permissible run
length = 30 m.
Siemens LV 72 2005
4/19
Lw6m
L w 15 m
a Fixed point
4/20
Siemens LV 72 2005
Power distribution1)
L1 w 60 m
L1 w 50 m
Siemens LV 72 2005
4/21
L1
L1
FP
L1
L1
FP
FP
FP
FP
L1 =
L =
D =
FP =
EF =
Examples:
For power transmission with LXA...., (LXC....)
Run length
Number of expansion
units (D)
Run length
L [m]
Number of fixed
points (FP)
L [m]
Number of fixed
points (FP)
Number of expansion
units (D)
w 6 (w6)
w 25 (w40)
w 50 (w80)
w 75 (w120)
2
2
3
4
0
1
2
3
w 50
w 100
w 150
w 200
1
2
3
4
0
1
2
3
Run length
Number of expansion
units (D)
Run length
L [m]
Number of fixed
points (FP)
L [m]
Number of fixed
points (FP)
Number of expansion
units (D)
w 6 (w6)
w 50 (w60)
w 100 (w120)
w 150 (w180)
2
2
3
4
0
1
2
4
w 60
w 120
w 180
w 240
1
2
3
4
0
1
2
3
4/22
Siemens LV 72 2005
L1
L1
FP
L1
L
L1
L
FP
FP
FP
L2
L2
FP
L1 =
L2 =
L =
D =
FP =
EF =
Examples:
For power transmission with LXA...., (LXC....)
Run length
L [m]
w 6 (w6)
w 12,5 (w20)
w 37,5 (w60)
w 62,5 (w100)
Run length
L [m]
w6
w 25
w 75
w 125
Number of fixed
points (FP)
Number of expansion
units (D)
1
1
2
3
0
1
2
3
Number of fixed
points (FP)
Number of expansion
units (D)
0
0
1
2
0
1
1
2
Run length
L [m]
w 6 (w6)
w 25 (w30)
w 75 (w90)
w 125 (w150)
Run length
L [m]
w6
w 30
w 90
w 150
Number of fixed
points (FP)
Number of expansion
units (D)
1
1
2
3
0
1
2
3
Number of fixed
points (FP)
Number of expansion
units (D)
0
0
1
2
0
1
1
2
Siemens LV 72 2005
4/23
Design
Fixing
The busbar run is secured using special fixing brackets (LX-BH,
LX..-BF or LX-K) that allow for a certain amount of slippage of the
busbar run when it is expanding under load.
Details about fixing intervals are to be found in Chapter
LXA/LXC Busbar Trunking System Technical Data. Each trunking unit must be supported by at least one fixing bracket.
Fixing intervals
Maximum distance between two fixing points on trunking unit
Minimum distance between fixing point and the centre of the
joint block.
horizontal, edgewise
250
mm
)m
3 (2
LX-BH(F)
horizontal, flat
250
mm
2m
4/24
Siemens LV 72 2005
LX...-BF(F)
Design
Mounting position
Due to the limited permissible mounting position of the overload
and short-circuit protective devices in the tap-off unit and the
easy mounting of the trunking units, the mounting position for the
vertical installation of busbar runs is fixed
Power transmission
Power
distribution1)
Size
LX.01 to LX.07
(single systems)
LX.08 to LX.10
(double systems)
LX.01 to LX.07
(single systems)
LX.08 to LX.10
(double systems)
Quantity
1
Type
LX.....-BV
LX.....-BV
LX.....-BV-AK
LX.....-BV-AK
The type designation of the fixed point depends on whether single systems or double systems are mounted:
c
d
Size:
LX.01 to LX.07 (single systems)
LX.08 to LX.10 (double systems)
Type:
LX-BVFP1
LX-BVFP2
f
a Compensate for uneven walls using material provided on site.
The specified minimum clearance for the vertical fixing bracket is 10 cm.
s Here: centre fire barrier = centre fire ceiling.
(tolerance range for positioning see page 4/16
Fire barrier)
d One or two vertical fixing brackets required per floor (floor height 3.40 m to
3.90 m). Please observe: min./max. loading
f Tap-off unit (for positioning of tap-off point relative to the fire barrier,
see page 4/16 Fire barrier)
g PEN (L3, N or PE)1) always on the right
h The trunking unit end without joint block is always positioned at the bottom.
The joint block should always be tightened at the end with phase L1.
1) The PEN, L3, N or PE conductor is on the right depending on the conductor configuration.
Siemens LV 72 2005
4/25
Busbar runs
Engineering example
Details required
Number and height of the floors
Ratings per floor and types of load
Utilization and rated load factors
Feed transformers (characteristic data, position)
Special requirements (degree of protection, fire barrier etc.)
Required number and positioning of tap-off points.
Given
11 floors each with 8 residential units
Rating of 38 kW per residential unit
Ue = 400 V, p. f. = 0,8, 5-conductor system,
degree of protection IP54
Rated load/utilization factor:
= 0,7 / = 0,45
Incoming supply from non-Siemens distribution board via LX
connection unit
Transformer rating = 1600 kVA
Details and construction plans required for engineering the
trunking layout
Tap-off units to be positioned at eye level.
Rated current
The rated current per floor is calculated using the following formula. The formula also allows the rated current for the tap-off
units to be defined.
P inst
3
I NB = -------------------------------------- 10
3 U e cos
INB
Ue
cos
Pinst
1)
0.9
0.8
0.7
0.6
Notes
The current rating is unaffected by the mounting position (horizontal or vertical). The standard degree of protection is IP54. The
floor height is 3.40 m.
Since this is a single-trunking system, one fixing bracket is to be
fitted for a vertical installation.
The expansion compensation must be engineered for the beginning of the busbar run. It must be attached to the lower end.
(For further details: see page 4/16 Engineering of Expansion
Compensation and Fixed Point.)
3
8 38 0, 7
I NB = ------------------------------------- 10 = 384 A
3 4 00 0, 8
IB =
INB
IB
2)
= Rated current
= Utilization factor for the total number of loads
IB =
1) If is not stated, the values from the Number of main circuits table can
be used. If the power factor is not stated, it may assumed to be = 1 for
purely residential high-rise buildings.
2) The local utility companies have good empirical values for utilization factors; they differ from region to region. The Type of load table provides
good average values.
4/26
Siemens LV 72 2005
/5
2480
3400
f
c
e
c
e
g
d
41575
250
c
e
3400
/4
/3
/2
b
a Non-Siemens ground floor distribution board
s Expansion unit
d Vertical fixing bracket for power distribution
f Fire barrier (positioning see page 4/16 Fire barrier.
Here: fire barrier positioned centrally in the fire ceiling)
g Tap-off unit
h End flange
j Fixed point
k 1st floor
l 2nd floor
; 11th floor.
2000
4175
/1
LXC0651-FA
LXC0651-D
LXA0651-2W1,40
+LX06-S120-X0,95
LXA0651-1W2,0-1AD1,40
5
6
7
8
LX06-EF
LX-BHF
LXA07-BV-AK
LX-AK5/LS-EC250-HS
Description
Quantity
1
1
11
2000
11
250
Siemens LV 72 2005
1
1
11
11
4/27
Overview
Horizontal installation
Looking at the trunking unit end without joint block mounted and
with the PEN (L1, N or PE) located on the right. The cable entry
is from the front end without mounted joint block or from the side.
Design
Sizes and cable entry sides
Five sizes are available depending on the rated current:
Size I
Up to 125 A with circuit-breaker or fuse switch-disconnector
Cable entry at the end.
Size II
Up to 250 A with circuit-breaker or fuse switch-disconnector
Cable entry at the end or at the side.
Vertical installation
Size III
Up to 400 A with circuit-breaker or fuse switch-disconnector
Cable entry at the end or at the side.
When the trunking units are installed vertically, the PEN (L3, N or
PE) must always be located on the right.
The trunking unit end without joint block is at the bottom.
Size IV
Up to 630 A with circuit-breaker or fuse switch-disconnector
Cable entry at the side.
Size V
up to 1250 A only with circuit-breaker
Cable entry at the side.
Power tap-off, mounting and safety features
4/28
Siemens LV 72 2005
Size
Overload release
A
80
100
125
160
200
250
400
6301)
I
I
I
II
II
II
III
IV
A
63 80
80 100
100 125
125 160
160 200
200 250
200 400
300 630
Icu at
Ue = 400 V
kA
Circuit-breaker
Type
Tap-off unit
Type
Icc at
Ue = 400 V
kA
65
65
65
65
65
65
65
65
NZM7(4)-80S
NZM7(4)-100S
NZM7(4)-125S
NZM7(4)-160S
NZM7(4)-200S
NZM7(4)-250S
NZM10(4)-400S/ZM400
NZM10(4)-630S/ZM630
LX-AK5(6)/LSH-80S-3(4)
LX-AK5(6)/LSH)-100S-3(4)
LX-AK5(6)/LSH-125S-3(4)
LX-AK5(6)/LSH-160S-3(4)
LX-AK5(6)/LSH-200S-3(4)
LX-AK5(6)/LSH-250S-3(4)
LX-AK(6)/LS-400S-3(4)
LX-AK(6)/LS-630S-3(4)
65
65
65
65
65
65
65
65
1) The specifications only apply if a rated load factor of 0.8 is taken into
account, i.e. the rated uninterrupted current is 20 % lower.
Valid for average ambient temperature of 35 C over 24 h.
Size
Fuses
NF
Cylindrical fuses 22 x 58
Icf
kA
100
125
125
160
250
250
400
400
630
630
I
I
II
II
II
III
III
IV
IV
IEC
BS
NF
IEC
BS
IEC
BS
IEC
BS88
NH00
BS88
NH0
NH1
BS88
NH2
BS88
NH3
BS88
100
80
100
100
80
100
80
100
80
3) The specifications only apply if a rated load factor of 0.8 is taken into
account, i.e. the rated uninterrupted current is 20 % lower.
Valid for average ambient temperature of 35 C over 24 h
NF = Norme Francaise
IEC= International European Comittee
BS = British Standard
Siemens LV 72 2005
4/29
Overview
Standards
In Germany, the official certification of functional endurance in
the event of fire must be provided to DIN 4102 Part 12.
Verification which applies are the test certificates and approvals
for the respective positions issued by the material test institute
for buildings in Braunschweig.
Application
For certain applications, VDE 0108 requires that functional endurance of busbar trunking systems for supplying power to parts
of installations be provided for an adequate time period, e.g.:
E 90 = fire resistance period 90 min.
Overview
Application
When transmitting power over long distances with LXA(C) busbar trunking systems, a voltage drop which varies in magnitude
occurs. The voltage drop is influenced by the by the arrangement of the conductors.
The use of three phase sequence reversal units has the effect
that the magnitude of the voltage drop on all three phases corresponds to the mean value. This means, that one phase sequence reversal unit must be positioned after each third of the
total length of the busbar run.
Phase sequence reversal units are available on request.
L
1/6 L
1/3 L
L3
L1
L2
PEN (N)
L1
L2
L3
PEN (N)
1/3 L
L2
L3
L1
PEN (N)
1/6 L
L1
L2
L3
PEN (N)
L1
L2
L3
PEN (N)
L = Total length
7
4/30
Siemens LV 72 2005
Annex
5/2
Glossary
5/4
Ordering notes
5/5
Siemens contacts
5/6
5/7
Customer support
5/8
5/10
Siemens LV 72 2005
Annex
Glossary
In accordance with IEC/EN 60439-1, rated values are supplied by
the manufacturers of low-voltage switchgear and controlgear assemblies. These rated values apply for the specified operating
conditions and characterise the usability of a switchgear assembly. The rated values should be used as a basis for
co-ordination of equipment or engineering the switchgear assemblies.
The operational power that an equipment is capable of switching at the associated rated operational voltage in accordance
with the utilization category, e.g. contactor utilization category
AC-3: 37 kW at 400 V.
Rated frequency
IEC/EN 60947-1; 4.3.3
Measures the stability of the internal clearances inside a switchgear against overvoltage peaks. The utilization of suitable
switchgear can ensure that overvoltages are prevented from
transfering from the mains to deenergized system sections within it.
The voltage to which insulation tests and creepage distances refer. Under no circumstances is the highest rated operational voltage permitted to exceed the rated insulation voltage.
see Rated operational voltage
5/2
Siemens LV 72 2005
Annex
Glossary
Rated peak short-circuit withstand current (Ipk)
IEC/EN 60439-1; 4.4
The maximum value of current which a switchgear unit is capable of switching off at rated operational voltage and rated frequency without sustaining damage. It is expressed as r.m.s.
value.
see Rated operational voltage
The maximum value of current which a switchgear unit is capable of switching on at a specific rated operational voltage and
rated frequency without sustaining damage. Unlike other characteristics values, this is expressed as a peak value.
see Rated operational voltage
The rated short-circuit withstand current describes, as the effective value of the short-circuit current, the thermal strength of a
circuit in a switchgear assembly during transient loading. The
rated short-time withstand current is normally determined for the
duration of 1 s, and any divergent times must be stated. The rated short-time withstand current is specified for the distribution
system and/or main busbars of a switchgear assembly.
Maximum short-circuit current, which a circuit-breaker is capable of interrupting (test cycle: O-CO, previously P-1). After interrupting this current value the circuit-breaker is capable, with
increased tolerances, of disconnecting in the event of overloading.
Siemens LV 72 2005
5/3
Annex
Ordering notes
Al and Cu surcharges
Surcharges for copper (Cu) and aluminium (Al) will be added to
the product prices; these surcharges will take the form of percentages of the list prices. Calculation of the surcharges will be
governed by the official Al quotation for aluminium and by the
Cu-DEL quotation applying on the date of receipt of order or of
call-off.
For the products in this catalog, aluminum and copper are included in the prices on the basis of 150,-- /100 kg. Aluminum and
copper quotations above that amount are calculated on the basis of the month previous to invoicing.
Calculation formula for Al/Cu surcharges:
Cu-DEL quotation or Al quotation 150
---------------------------------------------------------- Cu/Al weight (kg)
100 kg
Small orders
When small orders are placed, the costs associated with order
processing are greater than the order value. We recommend
therefore that you combine several small orders. Where this is
not possible, we unfortunately find it necessary to charge a
processing supplement of 20.-- to cover our costs for order
processing and invoicing for all orders with a net goods value
of less than 250.--.
5/4
Siemens LV 72 2005
Annex
Siemens contacts
Siemens LV 72 2005
5/5
Annex
A&D Online services
Data transfer via EDIFACT allows the whole procedure from selection through ordering to tracking of the order to be carried out
online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the
required products, which can be immediately checked for availability. Customer-specific discounts and preparation of quotes
can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.de/automation/mall
5/6
Siemens LV 72 2005
Annex
Customer support
Technical Support
In the face of harsh competition you need optimum conditions to
keep ahead all the time.
A strong starting position, a sophisticated strategy and team for
the necessary support - in every phase.
Service & Support from Siemens provides this support; with a
complete range of different services for automation and drives.
E-Mail: ad.support@siemens.com
Our specialists know when and where to act to keep the productivity and cost-effectiveness of your system running in top form.
Online support
Service on site
With Service on site we offer services for startup and maintenance, essential for ensuring
system availability.
Tel.: +49 (180) 50 50 444 2)
http://www.siemens.com/
automation/service&support
Technical Consulting
Technical Assistance
Support in the planning and designing of your project from detailed actual-state analysis,
target definition and consulting
on product and system questions right up to the creation of
the automation solution.2)
Siemens LV 72 2005
5/7
Annex
Subject and order number index
Page
A
Application
Building
Industrial
Accessories
for mounting and fixing
Angle and branch units
Elbow
Elbow offset
Knee
Knee, offset
T units, edgewise
Z units, edgewise
Z units, flat
B
Busbar runs
Horizontal
Fire barrier
Vertical
Busbar trunking system
BD 01
BD2
CD
LD
Busbar trunking units
LX...
LXA..
LXC..
2/5
2/5
3/50
3/28
3/28
3/29
3/28
3/30
3/32
3/31
3/31
4/24
4/16
4/25
2/2
2/2
2/2
2/2
3/6
3/7
3/13
C
Cable feeder units
3/43
Clean Earth
2/6
Clearance from structural bodies
4/7
Conductor configurations
2/8
Conductor material
4/3
Connection knee
3/45
Connection to non-Siemens distribution boards
4/12
Connection units
AS1
3/35
AS2
3/37
AS3
3/35
Connection units with T branch
AS1
3/40
AS2
3/41
AS3
3/40
Consumer tap-offs for straight trunking units 4/15
D
Degree of protection
Dimensional drawings
4/3
3/53
Page
E
Elbow
offset
Expansion unit
Extension terminal
F
Feeder units
Fire barrier
Positioning and fitting
Fixed point
I
Installation of busbar runs
horizontal
vertical
5/8
Siemens LV 72 2005
3/33
4/17
4/19
4/7
4/8
K
Kabeleinfhrungsseiten
Kabeleinspeisung
Knee
offset
4/28
4/12
3/28
3/30
L
Lug spacings
LX busbar trunking system
LXA/LXC selection
4/9
3/3
2/10
M
Magnetic fields
Maximum fixing intervals
Measuring custom lengths
Mounting position
2/8
2/8
4/14
4/3
N
Non-Siemens connection units
angled
straight
3/45
3/44
O
Order processing
4/2
P
PE conductor cross-section
2/6
Phase sequence
4/9
Phase sequence reversal units
4/30
Planning and Engineering
Busbar runs
4/14
Infeeds
4/9
Universal connection units
4/9
Universal connection units with T branch
4/11
Project handling
4/2
R
Rated current
Rated currents of standard transformers
Reference dimensions for engineering
Reference keys LXA/LXC
3/28
3/29
4/19
3/45
4/3
2/9
4/14
3/4
Page
S
Sandwich system
LX
2/2
Short-circuit current
2/9
Short-circuit currents of standard transformers 2/9
Sizes
4/28
Standard transformers
Rated currents
2/9
Short-circuit currents
2/9
Standards
4/30
Straight trunking units
3/25
Optional lengths
4/14
Standard lengths
4/14
with tap-off points
3/26
with tap-off points and adaptable
fire barrier
3/27
without tap-off points
3/25
T
Tap-off units
2/4, 3/21, 3/46, 4/28
with fuse switch disconnector up to 630 A
3/48
with NZM7 and NZM10 circuit-breakers
up to 630 A
3/46
with SENTRON 3VL circuit-breaker
800 A to 1250 A
3/49
with SENTRON 3VL circuit-breaker
up to 630 A
3/47
Tap-offs
4/28
Transformer rated values
2/10
T units
edgewise
3/32
Type definition
Angle and branch units
4/6
Straight trunking units
4/5
Type reference key
IEC/BS
3/48
Type reference key for
LX-AS.(-T)
3/34
U
Universal connection unit AS(-T)
V
Voltage drop
3/33
2/8
W
Weights
3/22
Z
Z units
edgewise
flat
3/31
3/31
Annex
Subject and order number index
Type
Page
LK-A
LK-AK6/LS-400S-.
LK-AK6/LS-630S-.
3/46
3/46
LX.....-K
LX.....-KB-AK
3/49
LX.....-1
LX.....-1
LX.....-1W*
LX.....-1W*-1AD*+LX.....-S120-X*
3/25
3/25
3/27
LX.....-2
LX.....-2+LX.....-S120-X*
LX.....-2-1AD
LX.....-2W*+LX.....-S120-X*
LX.....-2W*-1AD*+LX.....-S120-X*
3/25
3/26
3/25
3/27
LX.....-3
LX.....-3+LX.....-S120-X*
LX.....-3-1AD+LX.....-S120-X*
LX.....-3-AD+LX-F
LX.....-3-AD+LX-G
LX.....-3-AD+LX-H
LX.....-3-AD+LX-I
LX.....-3-AD+LX-K
LX.....-3-ADO-U+LX-A
LX.....-3-ADO-U+LX-B
LX.....-3-ADO-U+LX-C
LX.....-3-ADO-U+LX-D
LX.....-3-ADO-U+LX-E
LX.....-3W*+LX.....-S120-X*
LX.....-3W*-1AD*+LX.....-S120-X*
3/25
3/27
3/26
3/26
3/26
3/26
3/26
3/26
3/26
3/26
3/26
3/26
3/25
3/27
LX.....-A
LX.....-AS.+LX-1A+LX-P*(/N*)
LX.....-AS.+LX-1B+LX-P*(/N*)
LX.....-AS.+LX-1C+LX-P*(/N*)
LX.....-AS.+LX-1D+LX-P*(/N*)
LX.....-AS.+LX-2A+LX-P*(/N*)
LX.....-AS.+LX-2B+LX-P*(/N*)
LX.....-AS.+LX-2C+LX-P*(/N*)
LX.....-AS.+LX-2D+LX-P*(/N*)
LX.....-AS.-T+LX-1A+LX-P*(/N*)
LX.....-AS.-T+LX-1B+LX-P*(/N*)
LX.....-AS.-T+LX-1C+LX-P*(/N*)
LX.....-AS.-T+LX-1D+LX-P*(/N*)
LX.....-AS.-T+LX-1E+LX-P*(/N*)
LX.....-AS.-T+LX-1F+LX-P*(/N*)
LX.....-AS.-T+LX-1G+LX-P*(/N*)
LX.....-AS.-T+LX-1H+LX-P*(/N*)
LX.....-AS.-T+LX-2A+LX-P*(/N*)
LX.....-AS.-T+LX-2B+LX-P*(/N*)
LX.....-AS.-T+LX-2C+LX-P*(/N*)
LX.....-AS.-T+LX-2D+LX-P*(/N*)
LX.....-AS.-T+LX-2E+LX-P*(/N*)
LX.....-AS.-T+LX-2F+LX-P*(/N*)
LX.....-AS.-T+LX-2G+LX-P*(/N*)
LX.....-AS.-T+LX-2H+LX-P*(/N*)
LX.....-AS2+LX-1E+LX-P*(/N*)
LX.....-AS2+LX-1F+LX-P*(/N*)
LX.....-AS2+LX-1G+LX-P*(/N*)
LX.....-AS2+LX-1H+LX-P*(/N*)
LX.....-AS2+LX-2E+LX-P*(/N*)
LX.....-AS2+LX-2F+LX-P*(/N*)
LX.....-AS2+LX-2G+LX-P*(/N*)
LX.....-AS2+LX-2H+LX-P*(/N*)
3/35
3/35
3/36
3/36
3/35
3/35
3/36
3/36
3/39
3/39
3/40
3/40
3/41
3/41
3/42
3/42
3/39
3/39
3/40
3/40
3/41
3/41
3/42
3/42
3/37
3/37
3/38
3/38
3/37
3/37
3/38
3/38
LX.....-D
LX.....-D
3/25
LX.....-F
LX.....-FA 4
LX.....-FLH-X*/Y*
LX.....-FLL-X*/Y*
LX.....-FLR-X*/Y*
LX.....-FLV-X*/Y*
3/4
3/45
3/45
3/45
3/45
Type
Page
LX.....-K
LX.....-KE1+LX-BPAL
LX.....-KE1-IP55
LX.....-KE2+LX-BPAL
LX.....-KE2-IP55
3/43
3/43
3/43
3/43
LX.....-L
LX.....-LH
LX.....-LHL
LX.....-LHL-X*/Y*/Z*
LX.....-LHR
LX.....-LHR-X*/Y*/Z*
LX.....-LH-X*
LX.....-LH-XB*+LX.....-S120-X*
LX.....-LH-Y*
LX.....-LH-YB*+LX.....-S120-X*
LX.....-LL
LX.....-LLH
LX.....-LLH-X*/Y*/Z*
LX.....-LLV
LX.....-LLV-X*/Y*/Z*
LX.....-LL-X*
LX.....-LL-XB*+LX.....-S120-X*
LX.....-LL-Y*
LX.....-LL-YB*+LX.....-S120-X*
LX.....-LR
LX.....-LRH
LX.....-LRH-X*/Y*/Z*
LX.....-LRV
LX.....-LRV-X*/Y*/Z*
LX.....-LR-X*
LX.....-LR-XB*+LX.....-S120-X*
LX.....-LR-Y*
LX.....-LR-YB*+LX.....-S120-X*
LX.....-LV
LX.....-LVL
LX.....-LVL-X*/Y*/Z*
LX.....-LVR
LX.....-LVR-X*/Y*/Z*
LX.....-LV-X*
LX.....-LV-XB*+LX.....-S120-X*
LX.....-LV-Y*
LX.....-LV-YB*+LX.....-S120-X*
3/28
3/30
3/30
3/30
3/30
3/28
3/28
3/28
3/28
3/28
3/29
3/29
3/29
3/29
3/28
3/28
3/28
3/28
3/28
3/29
3/29
3/29
3/29
3/28
3/28
3/28
3/28
3/28
3/30
3/30
3/30
3/30
3/28
3/28
3/28
3/28
LX.....-P
LX.....-P
3/25
LX.....-T
LX.....-TH 32
LX.....-TH-X*/Y*/Z*
LX.....-TV
LX.....-TV-X*/Y*/Z*
3/32
3/32
3/32
LX.....-Z
LX.....-ZH-X*/Y*/Z*
LX.....-ZH-Z*
LX.....-ZL-X*/Y*/Z*
LX.....-ZL-Z*
LX.....-ZR-X*/Y*/Z*
LX.....-ZR-Z*
LX.....-ZV-X*/Y*/Z*
LX.....-ZV-Z*
3/31
3/31
3/31
3/31
3/31
3/31
3/31
3/31
LX....-B
LX....-BV
LX....-BV-AK
3/52
3/52
LX....-E
LX....-EF
LX....-EF-IP55
3/50
3/50
LX....-K
LX....-KB
3/50
LX....-S
LX....-S120-MOS
3/50
LX..-B
LX..-BF
LX..-BFF
3/51
3/51
Type
Page
LX0
LX02-6-IP55
LX02-IP55
LX04-6-IP55
LX04-IP55
LX05-6-IP55
LX05-IP55
LX07-6-IP55
LX07-IP55
LX08-6-IP55
LX08-IP55
3/50
3/50
3/50
3/50
3/50
3/50
3/50
3/50
3/50
3/50
LX1
LX10-6-IP55
LX10-IP55
3/50
3/50
LX-A
LX-AK./FSH-......-.
LX-AK./LS-......-LS
LX-AK./LS-.....-.S
LX-AK./LSH-....-.
LX-AK/FS-......-.
LX-AK/LS-400S-.
LX-AK/LS-630S-.
LX-AK6/FS-......-.
3/48
3/49
3/47
3/46
3/48
3/46
3/46
3/48
LX-B
LX-BH
LX-BHF
LX-BVFP1
LX-BVFP2
3/51
3/51
3/52
3/52
LX-K
LX-K
LX-KF
3/51
3/51
LX-P
LX-PEN400
LX-PEN630
3/46 - 3/48
3/46 - 3/48
LX-V
LX-V
3/52
Siemens LV 72 2005
5/9
Annex
Conditions of sale and delivery,
Export regulations
Export regulations
The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
Therefore, any export requiring a license is subject to approval
by the competent authorities.
According to current provisions, the following export regulations
must be observed with respect to the products featured in this
catalog / price list:
AL
ECCN
Even without a label or with an AL: N or ECCN: N, authorization may be required due to the final destination and purpose for
which the goods are to be used.
The deciding factors are the AL or ECCN export authorization
indicated on order confirmations, delivery notes and invoices.
Errors excepted and subject to change without prior notice.
Siemens AG
Automation and Drives
Low-Voltage Controls and Distribution
Postfach 48 48
90327 NRNBERG
FEDERAL REPUBLIC OF GERMANY
5/10
Siemens LV 72 2005
Order No.
E86060-K1872-A101-A1-7600
KG K 0305 1.0 BD 144 En/503085
Printed in the Federal Republic of Germany