You are on page 1of 2

+ e_mail:sales@sitalklima.

it

AIR HANDLING UNITS


FAN HEATER UNITS

sito web : www.sitalklima.it

COOLING TOWER

Sital CTS 1.1


Page 1 of 2

SOUND ATTENUATORS

TECHNICAL DATA
OFFER N. =
ITEM

REVISION
REFERENCE

AMBIENT
CTA 18

AIR HANDLING UNITS

Model

CTS 02

Double skin galvanized steel

Of

Execution

Profile

PA 211

4/6/2007

Altitude [m]

35

a.s.l.

Panel thickness

23

GALVANIZED steel sheet


GALVANIZED steel sheet
Injected Polyurethane with density > 45 Kg/m3. Fire reaction : Class 1 according to CSE,
M1 according to NF P 92-501 ASTM ISO 3580, B1 according to DIN 4102
Extruded ALUMINIUM, ANTICORODAL 63 alloy, UNI 9006/1

INTERNAL panel :
EXTERNAL panel
Insulation:
Profiles:

FRONT DAMPER
FRONT DAMPER, aluminium aerofoil profile opposite blades and ABS gears, suitable for manual or motorized control.

FILTER SECTION
FILTER SECTION with SYNTHETIC PLEATED CELLS , 100 mm thickness. Arrestance 90% according to ASHRAE
52/76 - EUROVENT EU4/G4

HEATING COIL
Heat exchanger with Cupper tubes and Aluminium fins, steel or cupper headers.
Model
Dimensions
Kcal/h
KW

Fluid Water

PT60AC 2R 9T 450A 2.5P 1NC Cu-Al


Capacity
540Hx450
16.512
19,2

air side
1.700
1.94
-5.0 (80%)
25.9 (10%)
-0,1
31,0
16

Air flow (m/h)


Tin (C-%HR)
Hin (KJ/Kg)
pressure drop

fluid side
0,85

V (m/s)
Tout (C-%HR)
Hout (KJ/Kg)
Pa

80,0
60,0
28

m/h
Tin (C)
Tout (C)
KPa

COOLING COIL
Heat exchanger with Cupper tubes and Aluminium fins, steel or cupper headers.
Model
Dimensions
Kcal/h
KW
Sens/Tot

Fluid Water

PT60AF 2R 9T 450A 2.0P 2NC Cu-Al


Capacity
540Hx450
6.235
7,3
0,68

air side
1.700
1.94
32.0 (50%)
22.8 (77%)
70,7
57,2
27

Air flow (m/h)


Tin (C-%HR)
Hin (KJ/Kg)
pressure drop

V (m/s)
Tout (C-%HR)
Hout (KJ/Kg)
Pa

fluid side
1,24

7,0
12,0
10

m/h
Tin (C)
Tout (C)
KPa

DROP ELIMINATOR SECTION


Galvanized steel DROP ELIMINATOR with 2 folds and 3 faces

SUPPLY FAN SECTION


FAN SECTION including fan-motor assembly put on antivibration-mountings and inspection door equipped with safety
microswitch. DIDW centrifugal fan, IP55 F Class motor. Belt drive with one variable pitch pulley ( up to 11 kW).
Fan size PAT 7-7 forward blades statically and dynamically balanced
Flow rate
1,700 m/h

RPM
1,642 rpm

Efficiency [%]
57
Installed motor

Abs.P. [kW]
0.37 kW
0,55 kW

E.S.P. [Pa]
160 Pa
4 POLES

Tot. S. P. [Pa]
326 Pa
230/400/3/50

Total P [Pa]
441 Pa

Lw dB(A)
79 dB(A)

Octave band spectrum


Frequency
Lw

Hz
dB

63
65,0

125
67,0

250
78,4

500
68,9

1000
72,7

2000
73,5

Sound pressure level at 1 [m] of distance from unit in the duct dB(A): 71

EXPANSION PLENUM
SUPPLY FAN EXPANSION PLENUM including diffuser
Radox - Bd. Timisoara - 7000 Bucuresti Tehnic - tel. 0724393533 Fax 4440741

4000
70,1

8000
67,2

+ e_mail:sales@sitalklima.it

AIR HANDLING UNITS


FAN HEATER UNITS

sito web : www.sitalklima.it

COOLING TOWER

Sital CTS 1.1


Page 2 of 2

SOUND ATTENUATORS

TECHNICAL DATA
OFFER N. =
ITEM

AIR HANDLING UNITS

Double skin galvanized steel


INTERNAL panel :
EXTERNAL panel
Insulation:
Profiles:

REVISION
REFERENCE

AMBIENT
CTA 18
Model

CTS 02

Of

Execution

Profile

PA 211

35

4/6/2007

Altitude [m]

a.s.l.

Panel thickness

23

GALVANIZED steel sheet


GALVANIZED steel sheet
Injected Polyurethane with density > 45 Kg/m3. Fire reaction : Class 1 according to CSE,
M1 according to NF P 92-501 ASTM ISO 3580, B1 according to DIN 4102
Extruded ALUMINIUM, ANTICORODAL 63 alloy, UNI 9006/1

FRONT DAMPER
FRONT DAMPER, aluminium aerofoil profile opposite blades and ABS gears, suitable for manual or motorized control.

Preliminary dimensions that could be varied in the costruction stage.


A [mm]
Total weight [kg]

730
359

H [mm]
H1 [mm]
Hr [mm]

Delivery terms
Delivery time
Packaging
Payment
Guaranty
Offer validity
Notes:

List price
Discount
Net price

4.158,10 EURO
0,00 %
4.158,10 EURO

Radox - Bd. Timisoara - 7000 Bucuresti Tehnic - tel. 0724393533 Fax 4440741