Safety Shut-Off Valve RMG 711

Product information

serving the gas industry


worldwide

safety shut-off valve rmg 711


Application, Features, Technical Data

Application
safety device for gas pressure regulating stations
suitable for natural gas according to G260 other gases on request

Features

easy maintenance; easy replacement of internal parts without dismantling the valve from the line, few parts only
integrated pressure compensating valve
low pressure drop due to in-line flow
manual release as a standard feature
electric release and electric remote indication of valve position as special features
high response accuracy and short response time
max. flow rate should not exceed 80 m/sec
also available according to SIL-norm IEC 61508
technical data
max. operating pressure PSmax

100 bar (depending on flange rating)

sizes

DN 25, DN 50, DN 80, DN 100, DN 150, DN 200, DN 250, DN 300


DIN-flanges PN 25, PN 40, and flanges according

connections

to ANSI 300, 600 RF, RTJ

materials

temperature range, class 2

main valve

A 352 LCC / G20Mn5 QT

switch device

aluminium forging alloy

measuring unit

aluminium forging alloy

internal parts

aluminium, stainless steel, brass, steel

O-rings

NBR, other materials on request

closing spring

spring steel

-20 C bis +60 C (other temperature ranges on request)


0,5 s (depending on service pressure, valve size and

response time ta

measuring unit)

function and tightness

DIN EN 14382 (DIN 3381)


standard SSV do not apply to ATEX 95
(available electronic accessories fully comply with the ATEX

Ex-protection

requirements).
CE-sign acc. to PED

pressure drop p

flowrate coefficient KG

based on the following formula:

Qn2
pu . KG2

pressure for the formulas to be inserted in


absolute values!

sizes DN

KG-value in m3/h

25

1200

50

4790

80

12260

100

19160

150

43110

200

76650

250

119750

300

130400

safety shut-off valve rmg 711


Application, Features, Technical Data

adjustable ranges
control element

setpoint spring

K10a

K11a/1

K11a/2

K16

K17

overpressure release

wire-

range

min. differential
between rsponse
pressure and
service pressure

in mm

Wdso (bar)

pw (bar)

spec.
No. colour
1

bright red

3.2

0.08

dark red

3.6

white

4.75

underpressure release

range

min. differential
between
response
pressure and
service pressure

Wdsu (bar)

pw (bar)

spec.

minimum
redifferential
between over-/ sponse
underpressure precision
response points category
with spring no.:
4
5
6
AG*

... 0.25

0.05

0.09 0.13

10/5

0.2

...

0.5

0.10

0.15 0.18

5/2.5

0.4

...

1.5

0.25

0.30 0.34

5/2.5

white

1.2

0.01

...

0.04

0.03

black

1.4

0.035

...

0.12

0.06

bright red

3.2

0.4

...

0.8

0.1

0.17 0.20 0.22

10/5

dark red

3.6

0.6

...

1.6

0.2

0.28 0.31 0.33

10/5

white

4.75

1.5

...

4.5

0.3

0.39 0.42 0.44

5/2.5

light blue

1.1

0.06

...

0.15

0.05

20/5

black

1.4

0.12

...

0.40

0.08

red

2.25

0.35

...

1.00

0.10

white

4.75
2.25

2.5

...

8.0

0.5

20/5
5

5
1.0

0.8

10/5

red

black

4.5

...

0.2

2.5/1

grey

5.0

...

10

0.4

brown

6.3

...

20

0.8

red

7.0

10

...

40

1.2

...

2.2

0.4

20/5

grey

5.0

...

10

0.4

brown

6.3

...

20

0.8

red

7.0

10

...

40

1.2

K18

9.0

K19

9.0

20

...

90

1.5

1
20

...

90

1.5

*) The higher response category is valid for the first half, the lower response category is valid for the second half of the setting range.

safety shut-off valve rmg 711


Design and Operation
RMG 711 DN 25 - DN 150
cover
valve body

valve flap lever


valve flap

pressure compensating valve


by-pass pressure gauge

operating lever

proximity sensor
manual release button

switching device
switching ring

valve flap shaft

closing springs
(flat spiral springs)

spring cover
hand lever for
reengagement
inlet pressure
outlet pressure

indication

safety shut-off valve rmg 711


Design and Operation
RMG 711 DN 200 - DN 300

measuring unit K 18
setpoint spring

tripping device rod


arresting sleeve
ball mechanism
lever release system

vent/bleed line
valve latch
measuringline

valve flap
valve flap shaft

pressure transformer

inlet pressure
outlet pressure
atmosphere

safety shut-off valve rmg 711


Aufbau und Arbeitsweise

operation with control element K16, K17, K18, K19

The pressure to be monitored (service pressure) at the double diaphragm system has to be compared with
a setpoint value (response pressure setpoint) which is determined by the setpoint spring. When the upper
response pressure is reached, the overpressure at the control element K16 or K 18 causes the amplifying valve
to open. When the lower response pressure is reached, the underpressure at the control element K 17/K 19
equally causes the amplifying valve to open. In both cases gas flows from the monitoring system to the
pressure/force transformer. The pressure increase does move the piston into the direction of the switch
gear and causes that the valve flap shaft releases. The actuator springs cause the SAV to close.
control element (K16 for upper setting range)
setpoint
adjuster
valve flap shaft
setpoint spring

switching device
switching ring

vent/bleed line
retaining pipe
throttle
switching pin
SSV-measuring
line
double diaphragm
system

manual release
switching stem
pressure/ force transformer

amplifying valve

control element (released - K17 for lower setting range)

outlet pressure
atmosphere

safety shut-off valve rmg 711


Design and Operation

operation with controlelements K10a, K11a


The control element is a release mechanism with a diaphragm measuring or piston measuring unit (K 10a/K 11a),
which is kept in position by the setpoint springs. Both setpoint values (response pressure setpoints) for
overpressure and underpressure release can be adjusted without influencing each other. When the upper or lower
response pressure is reached, the release movement in the control element is transmitted via the switch stem
to the switching ring of the switching device. This releases the valve flap shaft and the SAV valve flap stops
the gas flow.

7
operation with magnetic switch (electric release)
closing on current failure
The magnetic rod is brought into opening position by means of a stroke movement of the magnet against the force
of the closing spring. In operating condition the magnet is under current, should the current supply fail the closing
spring operates the switch stem.
closing on current supply
The stroke movement of the magnet is transmitted to the release mechanism of the switching device via a switch
stem. This causes the SAV to close.

pneumatic release with control element


(K 11a/2 for upper and lower setting range)

electric release with magnetic switch


(closing on current failure)

valve flap shaft


switching stem
SSV-measuring line
vent/bleed line

setpoint
adjuster

pressure spring
magnetic switch
setpoint springs
switching stem

switching device

switching ring
retaining pipe
switching pin

outlet pressure
manual release
atmosphere

safety shut-off valve rmg 711


Dimensions
RMG 711 DN 25 - DN 150

vent line E12

measuring line E12 (M16 x 1,5)

safety shut-off valve RMG 711 with control element K10a / K11a
measuring line E12 (M14 x 1,5)

vent/bleed line E12

safety shut-off valve RMG 711 with control element K16 / K17 / K18 / K19
dimensions in mm
size

A
PN

ANSI 300

ANSI 600

K 10a

K16

K18

RF

RTJ

K 10a

DN

25, 40

RF

RTJ

K 11a

K17

K19

25

170

170

180

180

260

295

415

160

110

K 11a
235

150

50

230

230

240

250

260

295

415

160

125

220

175

80

280

290

300

310

295

330

450

190

150

205

185

100

320

330

340

350

305

345

465

205

170

195

195

150

430

440

450

470

355

390

510

275

235

175

230

safety shut-off valve rmg 711


Dimensions

UN-thread bolts dimensions of the screw joint SSV/SSV

A
B

dimensions in mm
DN

25

50

80

100

150

UN-thread bolts dimensions G

flange

type

[mm]

[mm]

PN 25 and 40

18

1/2 x

70

ANSI 300 RF

18

5/8 x

80

ANSI 300 RTJ

22.5

5/8 x

90

xL

number of thread bolts

[Zoll x mm]

ANSI 600 RF

24

5/8 x

90

ANSI 600 RTJ

24

5/8 x

90

PN 25 and 40

23

5/8 x

85

ANSI 300 RF

23

5/8 x

90

ANSI 300 RTJ

29

5/8 x

100

ANSI 600 RF

33

5/8 x

110

ANSI 600 RTJ

34

5/8 x

110

PN 25 and 40

27

5/8 x

95

ANSI 300 RF

29

3/4 x

110

ANSI 300 RTJ

36

3/4 x

125

ANSI 600 RF

38.5

3/4 x

130

ANSI 600 RTJ

40

3/4 x

130

PN 25 and 40

27

3/4 x

105

ANSI 300 RF

32

3/4 x

115

ANSI 300 RTJ

38

3/4 x

130

ANSI 600 RF

45

7/8 x

150

ANSI 600 RTJ

46

7/8 x

150

PN 25 and 40

31

7/8 x

120

ANSI 300 RF

37

3/4 x

125

12

ANSI 300 RTJ

44

3/4 x

140

12

ANSI 600 RF

55

1 x

175

12

ANSI 600 RTJ

56

1 x

180

12

When using ductile screw bolts according to DIN 2510 a spacer between the two SSVs is required!

safety shut-off valve rmg 711


Dimensions, Weights, Connections
RMG 711 DN 200 - DN 300
F

DN

DN

10

20

20
J

H
B

325

dimensions in mm
size

pressure stage

max

DN

max

max

J
approx.

PN 25
200

PN 40

725

ANSI 300 RF/RJ

650

750

420

230

350

242

310

380

650

775

420

230

350

312

370

390

173

ANSI 600 RF/RJ


PN 25
250

730

PN 40
ANSI 300 RF/RJ

171

775

ANSI 600 RF/RJ

193

PN 25
300

PN 40

800

ANSI 300 RF/RJ

650

775

420

230

350

312

370

390

206

ANSI 600 RF/RJ

weights in kg
size
DN

weight in kg

25

50

80

100

150

200

250

300

20

26

56

85

200

430

500

700

connections
lines

measuring lines

vent lines

bleed lines

connection

E12

E12

E12

safety shut-off valve rmg 711


Type description

25
50
80
100
150
200
250
300
SSV-control element
Wdo [bar]

Wdu [bar]

control element

0,08 ... 1,50

0,01 ... 0,12

K10a

0,40 ... 4,50

0,06 ... 1,00

K11a/1

2,50 ... 8,00

0,80 ... 2,20

K11a/2
K16

1,00 ... 40,0


2,00 ... 40,0

K17
K18

20,0 ... 90,0


20,0 ... 90,0

K19

additional components
release by
manual release

HA

current supply

E1

loss of current

E2

remote indication
F
outdoortype
FA
special version
to be described in detail

So

FA

So
special version

HA

outdoor type

remote indication

K10a

additional components

DN

SSV-control element

size

size

RMG 711 - 50
type

example

11

For More Information


To learn more about RMGs
advanced gas solutions, contact
your RMG account manager or visit
www.rmg.com
GERMANY

ENGLAND

Honeywell Process Solutions

Honeywell Process Solutions

RMG Regel + Messtechnik GmbH

Bryan Donkin RMG Gas Controls Ltd.

Osterholzstrasse 45

Enterprise Drive, Holmewood

34123 Kassel, Germany

Chesterfield S42 5UZ, England

Tel: +49 (0)561 5007-0

Tel: +44 (0)1246 501-501

Fax: +49 (0)561 5007-107

Fax: +44 (0)1246 501-500

Honeywell Process Solutions

CANADA

RMG Messtechnik GmbH

Honeywell Process Solutions

Otto-Hahn-Strasse 5

Bryan Donkin RMG Canada Ltd.

35510 Butzbach, Germany

50 Clarke Street South, Woodstock

Tel: +49 (0)6033 897-0

Ontario N4S 0A8, Canada

Fax: +49 (0)6033 897-130

Tel: +1 (0)519 5398531


Fax: +1 (0)519 5373339

Honeywell Process Solutions


RMG Gaselan Regel + Messtechnik GmbH

USA

Julius-Pintsch-Ring 3

Honeywell Process Solutions

15517 Frstenwalde, Germany

Mercury Instruments LLC

Tel: +49 (0)3361 356-60

3940 Virginia Avenue

Fax: +49 (0)3361 356-836

Cincinnati, Ohio 45227, USA


Tel: +1 (0)513 272-1111

Honeywell Process Solutions

Fax: +1 (0)513 272-0211

WGA Wrme-Gastechnik GmbH


Osterholzstrasse 45

TURKEY

34123 Kassel, Germany

Honeywell Process Solutions

Tel: +49 (0)561 5007-0

RMG GAZ KONT. SIS. ITH. IHR. LTD. STI.

Fax: +49 (0)561 5007-207

Birlik Sanayi Sitesi, 6.


Cd. 62. Sokak No: 7-8-9-10

POLAND

TR - Sasmaz / Ankara, Turkey

Honeywell Process Solutions

Tel: +90 (0)312 27810-80

Gazomet Sp. z o.o.

Fax: +90 (0)312 27828-23

ul. Sarnowska 2
63-900 Rawicz, Poland
Tel: +48 (0)65 5462401
Fax: +48 (0)65 5462408

RMG 711.00
2007-07
2010 Honeywell International Inc.

You might also like