You are on page 1of 757

Estudio energtico con EnergyPlus e

implementacin del sistema de


climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

AUTOR: Fernando Pallars Cepero


DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

0. INDICE GENERAL
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

ndice general

ndice memoria descriptiva


0

HOJA DE IDENTIFICACIN........................................................................................................... 13

INTRODUCCIN ............................................................................................................................... 14

OBJETO ............................................................................................................................................... 15

ALCANCE............................................................................................................................................ 16

ANTECEDENTES............................................................................................................................... 16

NORMAS Y REFERENCIAS ............................................................................................................ 17

5.1

DISPOSICIONES LEGALES Y NORMAS APLICADAS ........................................................................... 17

5.2

BIBLIOGRAFA WEB ...................................................................................................................... 17

5.3

PROGRAMAS DE CLCULO Y SIMULACIN ..................................................................................... 18

5.4

PLAN DE GESTIN DE LA CALIDAD APLICADA DURANTE LA REDACCIN DEL PROYECTO ............... 18

DEFINICIONES Y ACRNIMOS .................................................................................................... 18


6.1

DEFINICIONES ............................................................................................................................... 18

6.2

ACRNIMOS .................................................................................................................................. 21

DESCRIPCIN DEL PROCESO ...................................................................................................... 22


7.1

REQUISITOS DE DISEO Y CUMPLIMIENTO DE NORMATIVA ............................................................ 23

7.1.1

Localizacin, condiciones exteriores y vecindario .................................................................. 23

7.1.2

Informacin sobre el uso del edificio ...................................................................................... 24

7.1.3

Datos constructivos del edificio............................................................................................... 26

7.1.4

Descripcin geomtrica del edificio ........................................................................................ 28

7.1.5

Cargas trmicas por ocupacin humana................................................................................. 29

7.1.6

Cargas trmicas por iluminacin y equipos ............................................................................ 32

7.1.7

Zona ocupada .......................................................................................................................... 33

7.1.8

Temperatura del aire y temperatura operativa ....................................................................... 33

7.1.9

Velocidad del aire y molestia por corriente de aire ................................................................ 34

7.1.10

Calidad del aire interior ..................................................................................................... 35

7.1.11

Estudio de mejoras. Acristalamiento doble ........................................................................ 37

7.1.12

Estudio de mejoras. Voladizo ............................................................................................. 40

7.1.13

Exigencia de recuperacin de energa................................................................................ 41

7.1.13.1

Recuperacin del aire exterior....................................................................................................... 41

7.1.14

Zonificacin ........................................................................................................................ 42

7.1.15

Exigencia de limitacin de la utilizacin de energa .......................................................... 42

7.1.16

Eficiencia energtica en las redes de tuberas y conductos................................................ 42

7.1.16.1

7.1.17

Eficiencia energtica de los equipos para el transporte de fluidos................................................. 42

Control................................................................................................................................ 43

ndice general
7.1.17.1

Control de las instalaciones de climatizacin ................................................................................ 43

7.1.17.2

Control de las condiciones termo-higromtricas ........................................................................... 43

7.1.17.3

Control de la calidad de aire interior en las instalaciones de climatizacin................................... 44

7.2

ESTUDIO DE VIABILIDAD ENERGTICA CON ENERGYPLUS............................................................. 45

7.2.1

Diseo del modelo con Google SketchUp y OpenStudio ......................................................... 45

7.2.1.1

Introduccin .................................................................................................................................. 45

7.2.1.2

Interfaz de Google SketchUp ........................................................................................................ 45

7.2.1.3

Funcionamiento............................................................................................................................. 55

7.2.1.4

Configuracin inicial y ejes de coordenadas ................................................................................. 55

7.2.1.5

Herramientas para la creacin del modelo .................................................................................... 56

7.2.1.6

Herramientas de acabado .............................................................................................................. 58

7.2.1.7

Plugin OpenStudio ........................................................................................................................ 63

7.2.1.8

Diseo del edificio de oficinas INEF Lleida ................................................................................. 67

7.2.1.9

Resultados finales de la creacin del modelo del edificio de oficinas INEF Lleida ...................... 71

7.2.2

Simulacin del modelo del edificio con EnergyPlus................................................................ 73

7.2.2.1

Introduccin .................................................................................................................................. 73

7.2.2.2

EP-Launch..................................................................................................................................... 75

7.2.2.3

Seleccin de archivos meteorolgicos y de entrada ...................................................................... 76

7.2.2.4

Simulacin de un archivo de entrada............................................................................................. 76

7.2.2.5

Resultados de una simulacin ....................................................................................................... 76

7.2.2.6

Visualizacin de parmetros ......................................................................................................... 77

7.2.2.7

IDF Editor ..................................................................................................................................... 82

7.2.2.8

Introduccin de parmetros comunes del edificio ......................................................................... 82

7.2.2.9

Introduccin de parmetros individuales del edificio.................................................................... 95

7.2.3

Rediseo del modelo con las mejoras y simulacin............................................................... 100

7.2.3.1

Acristalamiento doble ................................................................................................................. 100

7.2.3.2

Voladizo...................................................................................................................................... 101

7.2.4

Anlisis energtico ................................................................................................................ 104

7.2.4.1

Resultados de simulacin. Necesidades actuales del edificio...................................................... 104

7.2.4.2

Resultados de simulacin. Acristalamiento doble ....................................................................... 108

7.2.4.3

Resultados de simulacin. Condiciones actuales y voladizo ....................................................... 112

7.2.4.4

Resultados de simulacin. Acristalamiento doble y voladizo...................................................... 116

7.2.4.5

Comparativa de resultados. Condiciones actuales y acristalamiento doble ................................. 120

7.2.4.6

Comparativa de resultados. Condiciones actuales y voladizo ..................................................... 122

7.2.4.7

Comparativa de resultados. Voladizo y acristalamiento doble .................................................... 124

7.2.4.8

Comparativa de resultados. Condiciones actuales y ambas mejoras ........................................... 126

7.2.5

Optimizacin energtica........................................................................................................ 128

ndice general
7.3

INSTALACIN DEL SISTEMA DE CLIMATIZACIN CON CYPE INGENIEROS ................................... 129

7.3.1

Tipos de climatizaciones........................................................................................................ 130

7.3.2

Tipos de UTA ......................................................................................................................... 130

7.3.3

Solucin adoptada ................................................................................................................. 133

7.3.3.1

Climatizacin aire aire ............................................................................................................. 133

7.3.3.2

Caractersticas tcnicas de las UTAs seleccionadas................................................................... 135

7.3.3.3

Caractersticas de los conductos y rejillas seleccionadas ............................................................ 137

7.3.3.4

Modelo esquemtico de la instalacin......................................................................................... 139

7.3.4

Fase 1. Edificio...................................................................................................................... 146

7.3.4.1

Creacin de la obra...................................................................................................................... 146

7.3.4.2

Introduccin de los datos generales de la obra ............................................................................ 146

7.3.4.3

Importacin de ficheros............................................................................................................... 147

7.3.4.4

Determinacin de la orientacin.................................................................................................. 148

7.3.4.5

Descripcin de puentes trmicos lineales .................................................................................... 148

7.3.4.6

Introduccin de cerramientos de fachada .................................................................................... 149

7.3.4.7

Introduccin de tabiquera........................................................................................................... 151

7.3.4.8

Introduccin de forjados.............................................................................................................. 153

7.3.4.9

Introduccin de huecos en cerramientos y tabiqueras ................................................................ 156

7.3.4.10

Listado de resultados................................................................................................................... 159

7.3.5

Fase 2. Cargas trmicas ........................................................................................................ 159

7.3.5.1

Da de proyecto ........................................................................................................................... 160

7.3.5.2

Definicin de recintos ................................................................................................................. 160

7.3.5.3

Obtencin de los listados de resultados....................................................................................... 165

7.3.5.4

Resumen de los resultados de clculo de cargas de los recintos.................................................. 166

7.3.5.5

Resumen de los resultados para el conjunto del recinto INEF .................................................... 169

7.3.6

Fase 3. Climatizacin ............................................................................................................ 169

7.3.6.1

Introduccin de los splits conducidos.......................................................................................... 169

7.3.6.2

Introduccin de la unidad recuperadora de calor......................................................................... 170

7.3.6.3

Introduccin de la unidad exterior de aire acondicionado ........................................................... 171

7.3.6.4

Introduccin de lneas frigorficas............................................................................................... 172

7.3.6.5

Introduccin de conductos de aire............................................................................................... 172

7.3.6.6

Introduccin de rejillas y difusores ............................................................................................. 173

7.3.6.7

Introduccin de rejillas de toma y extraccin de aire .................................................................. 174

7.3.6.8

Obtencin de los resultados del clculo de la instalacin............................................................ 175

PLANIFICACIN............................................................................................................................. 176

ORDEN DE PRIORIDAD DE LOS DOCUMENTOS ................................................................... 179

ndice general

ndice anexos
0

HOJA DE IDENTIFICACIN............................................................................................................. 4

ENERGYPLUS ...................................................................................................................................... 5
1.1

CARACTERSTICAS DEL EDIFICIO ..................................................................................................... 5

1.1.1

General ...................................................................................................................................... 5

1.1.2

WindowWall Ratio Summary................................................................................................... 5

1.1.3

Zone Summary ........................................................................................................................... 5

1.1.4

Opaque Exterior Summary ........................................................................................................ 6

1.1.5

Fenestration Summary............................................................................................................... 7

1.1.6

Interior Lighting Summary ........................................................................................................ 7

1.1.7

Average Outdoor Air During Occupied Hours.......................................................................... 8

1.1.8

Surfaces By Class ...................................................................................................................... 8

1.1.9

HVAC......................................................................................................................................... 9

1.1.10
1.2

Input Fields........................................................................................................................... 9

CARGAS TRMICAS ......................................................................................................................... 9

1.2.1

Determinacin de las cargas trmicas del edificio.................................................................... 9

1.2.1.1

Tipos de cargas trmicas ................................................................................................................. 9

1.2.2

Hojas trmicas de calefaccin y refrigeracin ........................................................................ 11

1.2.3

Resultados simulacin del edificio en condiciones actuales ................................................... 12

1.2.3.1

Enero ............................................................................................................................................. 12

1.2.3.2

Febrero .......................................................................................................................................... 14

1.2.3.3

Marzo ............................................................................................................................................ 16

1.2.3.4

Abril .............................................................................................................................................. 18

1.2.3.5

Mayo ............................................................................................................................................. 20

1.2.3.6

Junio.............................................................................................................................................. 22

1.2.3.7

Julio............................................................................................................................................... 24

1.2.3.8

Septiembre .................................................................................................................................... 26

1.2.3.9

Octubre.......................................................................................................................................... 28

1.2.3.10

Noviembre..................................................................................................................................... 30

1.2.3.11

Diciembre...................................................................................................................................... 32

1.2.4

Resultados simulacin del edificio con la mejora de acristalamiento doble........................... 34

1.2.4.1

Enero ............................................................................................................................................. 34

1.2.4.2

Febrero .......................................................................................................................................... 36

1.2.4.3

Marzo ............................................................................................................................................ 38

1.2.4.4

Abril .............................................................................................................................................. 40

1.2.4.5

Mayo ............................................................................................................................................. 42

ndice general

1.2.4.6

Junio.............................................................................................................................................. 44

1.2.4.7

Julio............................................................................................................................................... 46

1.2.4.8

Septiembre .................................................................................................................................... 48

1.2.4.9

Octubre.......................................................................................................................................... 50

1.2.4.10

Noviembre..................................................................................................................................... 52

1.2.4.11

Diciembre...................................................................................................................................... 54

1.2.5

1.2.5.1

Enero ............................................................................................................................................. 56

1.2.5.2

Febrero .......................................................................................................................................... 58

1.2.5.3

Marzo ............................................................................................................................................ 60

1.2.5.4

Abril .............................................................................................................................................. 62

1.2.5.5

Mayo ............................................................................................................................................. 64

1.2.5.6

Junio.............................................................................................................................................. 66

1.2.5.7

Julio............................................................................................................................................... 68

1.2.5.8

Septiembre .................................................................................................................................... 70

1.2.5.9

Octubre.......................................................................................................................................... 72

1.2.5.10

Noviembre..................................................................................................................................... 74

1.2.5.11

Diciembre...................................................................................................................................... 76

1.2.6

Resultados simulacin del edificio con la mejora de voladizo ................................................ 56

Resultados de simulacin del edificio con las mejoras de acristalamiento doble y voladizo.. 78

1.2.6.1

Enero ............................................................................................................................................. 78

1.2.6.2

Febrero .......................................................................................................................................... 80

1.2.6.3

Marzo ............................................................................................................................................ 82

1.2.6.4

Abril .............................................................................................................................................. 84

1.2.6.5

Mayo ............................................................................................................................................. 86

1.2.6.6

Junio.............................................................................................................................................. 88

1.2.6.7

Julio............................................................................................................................................... 90

1.2.6.8

Septiembre .................................................................................................................................... 92

1.2.6.9

Octubre.......................................................................................................................................... 94

1.2.6.10

Noviembre..................................................................................................................................... 96

1.2.6.11

Diciembre...................................................................................................................................... 98

CYPE INGENIEROS ........................................................................................................................ 100


2.1

DESCRIPCIN DE MATERIALES Y ELEMENTOS CONSTRUCTIVOS................................................... 100

2.1.1

Sistema envolvente................................................................................................................. 100

2.1.1.1

Cerramientos exteriores............................................................................................................... 100

2.1.1.2

Suelos.......................................................................................................................................... 100

2.1.1.3

Cubiertas ..................................................................................................................................... 101

2.1.1.4

Huecos verticales ........................................................................................................................ 105

ndice general

2.1.2

Sistema de compartimentacin .............................................................................................. 107

2.1.2.1

Particiones verticales................................................................................................................... 107

2.1.2.2

Forjado entre pisos ...................................................................................................................... 107

2.1.2.3

Huecos verticales interiores......................................................................................................... 108

2.1.3

Materiales.............................................................................................................................. 109

2.1.4

Puentes trmicos.................................................................................................................... 110

2.2

LISTADO COMPLETO DE CARGAS TRMICAS ................................................................................ 111

2.2.1

Parmetros generales ........................................................................................................... 111

2.2.2

Resultados de clculo de los recintos ................................................................................... 112

2.2.2.1

Refrigeracin ............................................................................................................................... 112

2.2.2.2

Calefaccin ................................................................................................................................. 190

2.2.3

Resumen de los resultados de clculo de los recintos .......................................................... 268

2.2.4

Resumen de los resultados para conjuntos de recintos ........................................................ 271

2.3

CLCULO DE LA INSTALACIN .................................................................................................... 272

2.3.1

Sistemas de conduccin de aire. Conductos.......................................................................... 272

2.3.2

Sistemas de conduccin de aire. Difusores y rejillas ............................................................ 278

ndice general

ndice planos
0

HOJA DE IDENTIFICACIN..................................................................................................................2

SITUACIN Y EMPLAZAMIENTO.......................................................................................................3

OFICINAS. PLANTA BAJA .....................................................................................................................4

OFICINAS. PLANTA ALTA.....................................................................................................................5

SECCIN ALZADO Y POSTERIOR ......................................................................................................6

SECCIN INTERIOR ...............................................................................................................................7

INSTALACIN DE CLIMATIZACIN. PLANTA 0............................................................................8

INSTALACIN DE CLIMATIZACIN. PLANTA 1............................................................................9

INSTALACIN DEL EDIFICIO. VISTA 3D........................................................................................10

ndice general

ndice pliego de condiciones


0

HOJA DE IDENTIFICACIN .................................................................................................................. 3

GENERALIDADES .................................................................................................................................... 4

PLIEGO DE CLUSULAS ADMINISTRATIVAS................................................................................. 5


2.1

DISPOSICIONES GENERALES ................................................................................................................. 5

2.2

DISPOSICIONES FACULTATIVAS ............................................................................................................ 5

2.2.1

Definicin y atribuciones de los agentes de la edificacin ............................................................. 5

2.2.1.1

El Promotor ........................................................................................................................................... 5

2.2.1.2

El Proyectista......................................................................................................................................... 5

2.2.1.3

El Constructor o Contratista .................................................................................................................. 6

2.2.1.4

El Director de Obra ............................................................................................................................... 6

2.2.1.5

El Director de la Ejecucin de la Obra .................................................................................................. 6

2.2.1.6

Las entidades y los laboratorios de control de calidad de la edificacin................................................ 6

2.2.1.7

Los suministradores de productos ......................................................................................................... 7

2.2.2

Agentes que intervienen en la obra segn Ley 38/99 (L.O.E.) ........................................................ 7

2.2.3

Agentes en materia de seguridad y salud segn R.D. 1627/97 ....................................................... 7

2.2.4

Agentes en materia de gestin de residuos segn R.D. 105/08. ...................................................... 7

2.2.5

La Direccin Facultativa ................................................................................................................ 7

2.2.6

Visitas facultativas .......................................................................................................................... 8

2.2.7

Obligaciones de los agentes intervinientes ..................................................................................... 8

2.2.7.1

El Promotor ........................................................................................................................................... 8

2.2.7.2

El Proyectista......................................................................................................................................... 9

2.2.7.3

El Constructor o Contratista ................................................................................................................ 10

2.2.7.4

El Director de Obra ............................................................................................................................. 12

2.2.7.5

El Director de la Ejecucin de la Obra ................................................................................................ 13

2.2.7.6

Las entidades y los laboratorios de control de calidad de la edificacin.............................................. 15

2.2.7.7

Los suministradores de productos ....................................................................................................... 16

2.2.7.8

Los propietarios y los usuarios ............................................................................................................ 16

ndice general

2.2.8

Documentacin final de obra: Libro del Edificio ......................................................................... 16

2.2.8.1

2.3
3

Los propietarios y los usuarios ............................................................................................................ 16

DISPOSICIONES ECONMICAS ............................................................................................................. 17

PLIEGO DE CONDICIONES TCNICAS PARTICULARES............................................................ 17


3.1

PRESCRIPCIONES SOBRE LOS MATERIALES .......................................................................................... 17

3.1.1

Garantas de calidad (Marcado CE)............................................................................................. 18

3.1.2

Aislantes e impermeabilizantes ..................................................................................................... 21

3.1.2.1

3.2
3.2.1
3.3

Aislantes de lana mineral..................................................................................................................... 21

PRESCRIPCIONES EN CUANTO A LA EJECUCIN POR UNIDAD DE OBRA ............................................... 22


Instalaciones ................................................................................................................................. 27
PRESCRIPCIONES SOBRE VERIFICACIONES EN EL EDIFICIO TERMINADO ............................................... 66

ndice general

ndice presupuesto y medicin


0

HOJA DE IDENTIFICACIN................................................................................................................ 2

JUSTIFICACIN DE PRECIOS............................................................................................................ 3
1.1

CUADRO DE PRECIOS UNITARIOS. MANO DE OBRA ............................................................................ 3

1.2

CUADRO DE PRECIOS UNITARIOS. MATERIALES ................................................................................ 4

1.3

CUADRO DE PRECIOS AUXILIARES Y DESCOMPUESTOS...................................................................... 6

1.4

CUADRO DE PRECIOS N 1. EN LETRA ............................................................................................... 20

1.5

CUADRO DE PRECIOS N 2. MANO DE OBRA, MATERIALES, RESTOS DE OBRA, COSTES INDIRECTOS 25

PRESUPUESTO Y MEDICIN ........................................................................................................... 34

RESUMEN DE PRESUPUESTO .......................................................................................................... 41

PRESUPUESTO DE EJECUCIN POR CONTRATA ..................................................................... 42

ndice General

ndice estudio de seguridad y salud


0

HOJA DE IDENTIFICACIN............................................................................................................. 5

OBJETO DEL ESTUDIO DE SEGURIDAD Y SALUD.................................................................... 6

PROMOTOR PROPIETARIO ......................................................................................................... 6

AUTOR / ES DEL ESTUDIO DE SEGURIDAD Y SALUD ............................................................. 6

DATOS DEL PROYECTO ................................................................................................................... 7

4.1

AUTOR / ES DEL PROYECTO ............................................................................................................. 7

4.2

COORDINADOR DE SEGURIDAD DURANTE LA ELABORACIN DEL PROYECTO................................... 7

4.3

TIPOLOGA DE LA OBRA................................................................................................................... 7

4.4

SITUACIN ...................................................................................................................................... 7

4.5

PRESUPUESTO DE EJECUCIN MATERIAL DEL PROYECTO................................................................. 7

4.6

PLAZO DE EJECUCIN ...................................................................................................................... 7

4.7

MANO DE OBRA PREVISTA ............................................................................................................... 7

4.8

OFICIOS QUE INTERVIENEN EN EL DESARROLLO DE LA OBRA .......................................................... 8

4.9

TIPOLOGA DE LOS MATERIALES A UTILIZAR EN LA OBRA ............................................................... 8

INSTALACIONES PROVISIONALES............................................................................................. 12
5.1
5.1.1

Acometida ................................................................................................................................ 12

5.1.2

Cuadro General....................................................................................................................... 13

5.1.3

Conductores............................................................................................................................. 13

5.1.4

Conexiones de corriente .......................................................................................................... 13

5.1.5

Maquinaria elctrica ............................................................................................................... 13

5.1.6

Alumbrado provisional ............................................................................................................ 14

5.1.7

Alumbrado porttil .................................................................................................................. 14

5.2
5.2.1
6

INSTALACIN ELCTRICA PROVISIONAL DE OBRA ......................................................................... 12

OTRAS INSTALACIONES. PREVENCIN Y PROTECCIN CONTRA INCENDIOS ................................... 14


Emplazamiento y distribucin de los extintores obra.............................................................. 16

SERVICIOS DE SALUBRIDAD Y CONFORT DEL PERSONAL ............................................... 16


6.1

SERVICIOS HIGINICOS .................................................................................................................. 16

6.2

VESTUARIOS ................................................................................................................................. 17

6.3

COMEDOR ..................................................................................................................................... 17

6.4

LOCAL DE DESCANSO .................................................................................................................... 17

6.5

LOCAL DE ASISTENCIA A ACCIDENTADOS ...................................................................................... 17

ndice General

REAS AUXILIARES........................................................................................................................ 18
7.1

CENTRALES Y PLANTAS ................................................................................................................. 18

7.2

TALLERES ..................................................................................................................................... 19

7.3

ZONAS DE ACOPIO. ALMACENES ................................................................................................... 20

TRATAMIENTO DE RESIDUOS ..................................................................................................... 20

TRATAMIENTO DE MATERIALES Y / O SUSTANCIAS PELIGROSAS................................ 21

10

9.1

MANIPULACIN ............................................................................................................................ 21

9.2

DELIMITACIN / ACONDICIONAMIENTO DE ZONAS DE ACOPIO....................................................... 21

9.2.1

Txicos, muy txicos, nocivos, carcingenos, mutagnicos, txicos para la reproduccin .... 22

9.2.2

Corrosivos, Irritantes .............................................................................................................. 22

CONDICIONES DEL ENTORNO..................................................................................................... 22


10.1

EMPLEO DEL CIERRE DE LA OBRA .................................................................................................. 22

10.2

SITUACIN DE CASETAS Y CONTENEDORES ................................................................................... 23

10.3

SERVICIOS AFECTADOS ................................................................................................................. 23

10.4

NECESIDADES ............................................................................................................................... 23

10.5

CARACTERSTICAS DEL ENTORNO ................................................................................................. 24

11

UNIDADES CONSTRUCTIVAS ....................................................................................................... 24

12

DETERMINACIN DEL PROCESO CONSTRUCTIVO ............................................................. 24


12.1

PROCEDIMIENTOS DE EJECUCIN .................................................................................................. 24

12.2

ORDEN DE EJECUCIN DE LOS TRABAJOS ...................................................................................... 24

12.3

DETERMINACIN DEL TIEMPO EFECTIVO DE DURACIN. PLAN DE EJECUCIN ............................... 25

13 SISTEMAS Y / O ELEMENTOS DE SEGURIDAD Y SALUD INHERENTES O


INCORPORADOS AL MISMO PROCESO CONSTRUCTIVO............................................................. 25
14

15

MEDIO AMBIENTE LABORAL ...................................................................................................... 25


14.1

AGENTES ATMOSFRICOS .............................................................................................................. 25

14.2

ILUMINACIN ................................................................................................................................ 25

14.3

RUIDO ........................................................................................................................................... 26

14.4

POLVO ........................................................................................................................................... 27

14.5

ORDEN Y LIMPIEZA........................................................................................................................ 29

MANIPULACIN DE MATERIALES............................................................................................. 30
15.1

LOS PRINCIPIOS BSICOS DE LA MANIPULACIN DE MATERIALES .................................................. 31

15.2

MANEJO DE CARGAS SIN MEDIOS MECNICOS ............................................................................... 31

16

MEDIOS AUXILIARES DE UTILIDAD PREVENTIVA (MAUP) ............................................... 32

17

SISTEMAS DE PROTECCIN COLECTIVA (SPC)..................................................................... 34

18

CONDICIONES DE LOS EQUIPOS DE PROTECCIN INDIVIDUAL (EPI) .......................... 35

19

RECURSOS PREVENTIVOS ............................................................................................................ 35

ndice General

20

SEALIZACIN Y BALIZAMIENTO ............................................................................................ 37

21

CONDICIONES DE ACCESO DE LA VA PUBLICA................................................................... 38

22

NORMAS DE POLICA ..................................................................................................................... 39


22.1

CONTROL DE ACCESOS .................................................................................................................. 39

22.2

COORDINACIN DE INTERFERENCIAS Y SEGURIDAD A PIE DE OBRA ............................................... 39

22.3

MBITO DE OCUPACIN DE LA VA PUBLICA ................................................................................. 39

22.3.1

Empleo del cierre de la obra .............................................................................................. 39

22.3.2

Situacin de casetas y contenedores................................................................................... 40

22.3.3

Cambios de la Zona Ocupada............................................................................................. 40

22.4

22.4.1

Vallas .................................................................................................................................. 40

22.4.2

Acceso a la obra ................................................................................................................. 41

22.5

OPERACIONES QUE AFECTAN EL MBITO PBLICO ........................................................................ 41

22.5.1

Entradas y salidas de vehculos y maquinaria.................................................................... 41

22.5.2

Carga y descarga................................................................................................................ 41

22.5.3

Descarga, acopio y evacuacin de tierras y escombros ..................................................... 42

22.5.4

Protecciones para evitar la cada de objetos en la va pblica .......................................... 42

22.6

LIMPIEZA E INCIDENCIA SOBRE EL AMBIENTE QUE AFECTA EL MBITO PBLICO ........................... 43

22.6.1

Limpieza.............................................................................................................................. 43

22.6.2

Ruidos. Horario de trabajo................................................................................................. 43

22.6.3

Polvo ................................................................................................................................... 44

22.7

RESIDUOS QUE AFECTAN AL MBITO PUBLICO .............................................................................. 44

22.8

CIRCULACIN DE VEHCULOS Y PEATONES QUE AFECTAN EL MBITO PUBLICO ............................ 44

22.8.1

Sealizacin y proteccin ................................................................................................... 44

22.8.2

Dimensiones mnimas de itinerarios y pasos para peatones .............................................. 44

22.8.3

Elementos de proteccin ..................................................................................................... 44

22.8.4

Alumbrado y balizamiento luminoso................................................................................... 45

22.8.5

Balizamiento y defensa ....................................................................................................... 45

22.8.6

Accesibilidad de personas con movilidad reducida............................................................ 46

22.8.7

Retirada de sealizacin y balizamiento ............................................................................ 46

22.9

23

CERRAMIENTOS DE LA OBRA QUE AFECTAN EL MBITO PBLICO .................................................. 40

PROTECCIN Y TRASLADO DE ELEMENTOS EMPLAZADOS EN LA VA PBLICA ............................... 46

22.9.1

rboles y jardines ............................................................................................................... 46

22.9.2

Paradas de autobs ............................................................................................................ 47

RIESGOS DE DAOS A TERCEROS Y MEDIDAS DE PROTECCIN.................................... 47


23.1

RIESGOS DE DAOS A TERCEROS ................................................................................................... 47

23.2

MEDIDAS DE PROTECCIN A TERCEROS ......................................................................................... 47

ndice General

24

PREVENCIN DE RIESGOS CATASTRFICOS ........................................................................ 48

25

PREVISIONES DE SEGURIDAD POR TRABAJOS POSTERIORES ........................................ 48

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

1. MEMORIA DESCRIPTIVA
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Memoria descriptiva

ndice
0

HOJA DE IDENTIFICACIN........................................................................................................... 13

INTRODUCCIN ............................................................................................................................... 14

OBJETO ............................................................................................................................................... 15

ALCANCE............................................................................................................................................ 16

ANTECEDENTES............................................................................................................................... 16

NORMAS Y REFERENCIAS ............................................................................................................ 17

5.1

DISPOSICIONES LEGALES Y NORMAS APLICADAS ........................................................................... 17

5.2

BIBLIOGRAFA WEB ...................................................................................................................... 17

5.3

PROGRAMAS DE CLCULO Y SIMULACIN ..................................................................................... 18

5.4

PLAN DE GESTIN DE LA CALIDAD APLICADA DURANTE LA REDACCIN DEL PROYECTO ............... 18

DEFINICIONES Y ACRNIMOS .................................................................................................... 18


6.1

DEFINICIONES ............................................................................................................................... 18

6.2

ACRNIMOS .................................................................................................................................. 21

DESCRIPCIN DEL PROCESO ...................................................................................................... 22


7.1

REQUISITOS DE DISEO Y CUMPLIMIENTO DE NORMATIVA ............................................................ 23

7.1.1

Localizacin, condiciones exteriores y vecindario .................................................................. 23

7.1.2

Informacin sobre el uso del edificio ...................................................................................... 24

7.1.3

Datos constructivos del edificio............................................................................................... 26

7.1.4

Descripcin geomtrica del edificio ........................................................................................ 28

7.1.5

Cargas trmicas por ocupacin humana................................................................................. 29

7.1.6

Cargas trmicas por iluminacin y equipos ............................................................................ 32

7.1.7

Zona ocupada .......................................................................................................................... 33

7.1.8

Temperatura del aire y temperatura operativa ....................................................................... 33

7.1.9

Velocidad del aire y molestia por corriente de aire ................................................................ 34

7.1.10

Calidad del aire interior ..................................................................................................... 35

7.1.11

Estudio de mejoras. Acristalamiento doble ........................................................................ 37

7.1.12

Estudio de mejoras. Voladizo ............................................................................................. 40

7.1.13

Exigencia de recuperacin de energa................................................................................ 41

7.1.13.1

Recuperacin del aire exterior....................................................................................................... 41

7.1.14

Zonificacin ........................................................................................................................ 42

7.1.15

Exigencia de limitacin de la utilizacin de energa .......................................................... 42

7.1.16

Eficiencia energtica en las redes de tuberas y conductos................................................ 42

7.1.16.1

7.1.17

Eficiencia energtica de los equipos para el transporte de fluidos................................................. 42

Control................................................................................................................................ 43

Memoria descriptiva
7.1.17.1

Control de las instalaciones de climatizacin ................................................................................ 43

7.1.17.2

Control de las condiciones termo-higromtricas ........................................................................... 43

7.1.17.3

Control de la calidad de aire interior en las instalaciones de climatizacin................................... 44

7.2

ESTUDIO DE VIABILIDAD ENERGTICA CON ENERGYPLUS............................................................. 45

7.2.1

Diseo del modelo con Google SketchUp y OpenStudio ......................................................... 45

7.2.1.1

Introduccin .................................................................................................................................. 45

7.2.1.2

Interfaz de Google SketchUp ........................................................................................................ 45

7.2.1.3

Funcionamiento............................................................................................................................. 55

7.2.1.4

Configuracin inicial y ejes de coordenadas ................................................................................. 55

7.2.1.5

Herramientas para la creacin del modelo .................................................................................... 56

7.2.1.6

Herramientas de acabado .............................................................................................................. 58

7.2.1.7

Plugin OpenStudio ........................................................................................................................ 63

7.2.1.8

Diseo del edificio de oficinas INEF Lleida ................................................................................. 67

7.2.1.9

Resultados finales de la creacin del modelo del edificio de oficinas INEF Lleida ...................... 71

7.2.2

Simulacin del modelo del edificio con EnergyPlus................................................................ 73

7.2.2.1

Introduccin .................................................................................................................................. 73

7.2.2.2

EP-Launch..................................................................................................................................... 75

7.2.2.3

Seleccin de archivos meteorolgicos y de entrada ...................................................................... 76

7.2.2.4

Simulacin de un archivo de entrada............................................................................................. 76

7.2.2.5

Resultados de una simulacin ....................................................................................................... 76

7.2.2.6

Visualizacin de parmetros ......................................................................................................... 77

7.2.2.7

IDF Editor ..................................................................................................................................... 82

7.2.2.8

Introduccin de parmetros comunes del edificio ......................................................................... 82

7.2.2.9

Introduccin de parmetros individuales del edificio.................................................................... 95

7.2.3

Rediseo del modelo con las mejoras y simulacin............................................................... 100

7.2.3.1

Acristalamiento doble ................................................................................................................. 100

7.2.3.2

Voladizo...................................................................................................................................... 101

7.2.4

Anlisis energtico ................................................................................................................ 104

7.2.4.1

Resultados de simulacin. Necesidades actuales del edificio...................................................... 104

7.2.4.2

Resultados de simulacin. Acristalamiento doble ....................................................................... 108

7.2.4.3

Resultados de simulacin. Condiciones actuales y voladizo ....................................................... 112

7.2.4.4

Resultados de simulacin. Acristalamiento doble y voladizo...................................................... 116

7.2.4.5

Comparativa de resultados. Condiciones actuales y acristalamiento doble ................................. 120

7.2.4.6

Comparativa de resultados. Condiciones actuales y voladizo ..................................................... 122

7.2.4.7

Comparativa de resultados. Voladizo y acristalamiento doble .................................................... 124

7.2.4.8

Comparativa de resultados. Condiciones actuales y ambas mejoras ........................................... 126

7.2.5

Optimizacin energtica........................................................................................................ 128

Memoria descriptiva
7.3

INSTALACIN DEL SISTEMA DE CLIMATIZACIN CON CYPE INGENIEROS ................................... 129

7.3.1

Tipos de climatizaciones........................................................................................................ 130

7.3.2

Tipos de UTA ......................................................................................................................... 130

7.3.3

Solucin adoptada ................................................................................................................. 133

7.3.3.1

Climatizacin aire aire ............................................................................................................. 133

7.3.3.2

Caractersticas tcnicas de las UTAs seleccionadas................................................................... 135

7.3.3.3

Caractersticas de los conductos y rejillas seleccionadas ............................................................ 137

7.3.3.4

Modelo esquemtico de la instalacin......................................................................................... 139

7.3.4

Fase 1. Edificio...................................................................................................................... 146

7.3.4.1

Creacin de la obra...................................................................................................................... 146

7.3.4.2

Introduccin de los datos generales de la obra ............................................................................ 146

7.3.4.3

Importacin de ficheros............................................................................................................... 147

7.3.4.4

Determinacin de la orientacin.................................................................................................. 148

7.3.4.5

Descripcin de puentes trmicos lineales .................................................................................... 148

7.3.4.6

Introduccin de cerramientos de fachada .................................................................................... 149

7.3.4.7

Introduccin de tabiquera........................................................................................................... 151

7.3.4.8

Introduccin de forjados.............................................................................................................. 153

7.3.4.9

Introduccin de huecos en cerramientos y tabiqueras ................................................................ 156

7.3.4.10

Listado de resultados................................................................................................................... 159

7.3.5

Fase 2. Cargas trmicas ........................................................................................................ 159

7.3.5.1

Da de proyecto ........................................................................................................................... 160

7.3.5.2

Definicin de recintos ................................................................................................................. 160

7.3.5.3

Obtencin de los listados de resultados....................................................................................... 165

7.3.5.4

Resumen de los resultados de clculo de cargas de los recintos.................................................. 166

7.3.5.5

Resumen de los resultados para el conjunto del recinto INEF .................................................... 169

7.3.6

Fase 3. Climatizacin ............................................................................................................ 169

7.3.6.1

Introduccin de los splits conducidos.......................................................................................... 169

7.3.6.2

Introduccin de la unidad recuperadora de calor......................................................................... 170

7.3.6.3

Introduccin de la unidad exterior de aire acondicionado ........................................................... 171

7.3.6.4

Introduccin de lneas frigorficas............................................................................................... 172

7.3.6.5

Introduccin de conductos de aire............................................................................................... 172

7.3.6.6

Introduccin de rejillas y difusores ............................................................................................. 173

7.3.6.7

Introduccin de rejillas de toma y extraccin de aire .................................................................. 174

7.3.6.8

Obtencin de los resultados del clculo de la instalacin............................................................ 175

PLANIFICACIN............................................................................................................................. 176

ORDEN DE PRIORIDAD DE LOS DOCUMENTOS ................................................................... 179

Memoria descriptiva

ndice de figuras
FIGURA 1. DIAGRAMA DE BLOQUES ................................................................................................................. 22
FIGURA 2. CALENDARIO ANUAL DE LA UNIVERSIDAD (FUENTE: WEB INEF LLEIDA) ...................................... 25
FIGURA 3. ZONA OCUPADA (FUENTE: UNE EN 13779).................................................................................... 33
FIGURA 4. CAPAS DEL ACRISTALAMIENTO DOBLE ............................................................................................ 37
FIGURA 5. EDIFICIO CON VOLADIZO ................................................................................................................. 41
FIGURA 6. VENTANA INICIAL DE GOOGLE SKETCHUP ...................................................................................... 45
FIGURA 7. PANTALLA LISTA PARA DIBUJAR DE GOOGLE SKETCHUP ................................................................ 46
FIGURA 8. EJES................................................................................................................................................. 46
FIGURA 9. BARRA DE ESTADO .......................................................................................................................... 47
FIGURA 10. PESTAA DE ARCHIVO ................................................................................................................... 47
FIGURA 11. PESTAA DE EDICIN .................................................................................................................... 48
FIGURA 12. PESTAA DE VER ........................................................................................................................... 48
FIGURA 13. PESTAA DE CMARA ................................................................................................................... 49
FIGURA 14. PESTAA DE DIBUJO ...................................................................................................................... 49
FIGURA 15. PESTAA DE HERRAMIENTAS......................................................................................................... 49
FIGURA 16. PESTAA DE VENTANA .................................................................................................................. 50
FIGURA 17. PESTAA DE PLUGINS .................................................................................................................... 50
FIGURA 18. PESTAA DE AYUDA ...................................................................................................................... 50
FIGURA 19. PRIMEROS PASOS ........................................................................................................................... 51
FIGURA 20. CONJUNTO GRANDE DE HERRAMIENTAS ........................................................................................ 51
FIGURA 21. BARRA DE HERRAMIENTAS ESTNDAR .......................................................................................... 51
FIGURA 22. BARRA DE HERRAMIENTAS PRINCIPALES ....................................................................................... 52
FIGURA 23. BARRA DE HERRAMIENTAS DE DIBUJO ........................................................................................... 52
FIGURA 24. BARRA DE HERRAMIENTAS DE MODIFICACIN............................................................................... 52
FIGURA 25. BARRA DE HERRAMIENTAS AUXILIARES ........................................................................................ 52
FIGURA 26. BARRA DE HERRAMIENTAS DE CMARA ........................................................................................ 52
FIGURA 27. BARRA DE HERRAMIENTAS DE PASEO ............................................................................................ 52
FIGURA 28. BARRA DE HERRAMIENTAS ESTILO DE CARA ............................................................................. 52
FIGURA 29. BARRA DE HERRAMIENTAS DE VISTAS ........................................................................................... 53
FIGURA 30. BARRA DE HERRAMIENTAS DE SOMBRA......................................................................................... 53
FIGURA 31. BARRA DE HERRAMIENTAS DE SECCIN ........................................................................................ 53
FIGURA 32. BARRA GOOGLE ............................................................................................................................ 53
FIGURA 33. TIPOS DE PUNTOS .......................................................................................................................... 54
FIGURA 34. TIPOS DE LNEA ............................................................................................................................. 54

Memoria descriptiva
FIGURA 35. PANTALLA PARA SELECCIONAR LAS UNIDADES ............................................................................. 56
FIGURA 36. ICONO DE RECTNGULO ................................................................................................................ 56
FIGURA 37. ORIGEN DE COORDENADAS ............................................................................................................ 56
FIGURA 38. RECINTO CONSTRUIDO EN 2 EJES ................................................................................................... 56
FIGURA 39. ICONOS DE LA HERRAMIENTA DEL CONJUNTO GRANDE ................................................................. 57
FIGURA 40. PASO PARA DAR VOLUMEN AL RECINTO ........................................................................................ 57
FIGURA 41. RECINTO LEVANTADO ................................................................................................................... 57
FIGURA 42. BARRA HERRAMIENTAS DE MEDICIN ........................................................................................... 57
FIGURA 43. MEDICIN DE DOS PUNTOS ............................................................................................................ 57
FIGURA 44. SECCIN DE LA FIGURA ................................................................................................................. 58
FIGURA 45. ICONOS DE LA HERRAMIENTA DE CMARA .................................................................................... 58
FIGURA 46. CUERPO 3D MARCADO ENTERO ..................................................................................................... 59
FIGURA 47. ROTACIN DE LA COPIA ................................................................................................................. 60
FIGURA 48. ROTACIN DE LA FIGURA .............................................................................................................. 60
FIGURA 49. ICONOS DE MODIFICACIN............................................................................................................. 61
FIGURA 50. TRASLACIN DE UN OBJETO POR LOS EJES ..................................................................................... 61
FIGURA 51. PASOS PARA MOVER UNA CARA DEL OBJETO ................................................................................. 61
FIGURA 52. CASA CON CSPED ......................................................................................................................... 62
FIGURA 53. MATERIALES ................................................................................................................................. 62
FIGURA 54. CASA CON SOMBRA ....................................................................................................................... 63
FIGURA 55. ICONOS DEL PLUGIN OPENSTUDIO ................................................................................................. 63
FIGURA 56. VENTANA DE ERRORES Y ADVERTENCIAS ...................................................................................... 64
FIGURA 57. ZONA DEL GOOGLE SKETCHUP ..................................................................................................... 64
FIGURA 58. INFORMACIN DE OBJETOS ............................................................................................................ 65
FIGURA 59. VENTANA DE SIMULACIN ............................................................................................................ 66
FIGURA 60. VISTA 1 PASO ............................................................................................................................... 67
FIGURA 61. VISTA 2 PASO ............................................................................................................................... 68
FIGURA 62. VISTA 3 PASO ............................................................................................................................... 68
FIGURA 63. VISTA 4 PASO ............................................................................................................................... 69
FIGURA 64. VISTA 5 PASO ............................................................................................................................... 69
FIGURA 65. VISTA 6 PASO ............................................................................................................................... 70
FIGURA 66. VISTA 7 PASO ............................................................................................................................... 71
FIGURA 67. VISTA DEL ALZADO EN CONDICIONES ACTUALES........................................................................... 71
FIGURA 68. VISTA DE LA PLANTA EN CONDICIONES ACTUALES ........................................................................ 72
FIGURA 69. VISTA DEL PERFIL IZQUIERDO EN CONDICIONES ACTUALES ........................................................... 72
FIGURA 70. VISTA DEL PERFIL DERECHO EN CONDICIONES ACTUALES ............................................................. 72

Memoria descriptiva
FIGURA 71. VISTA DEL POSTERIOR EN CONDICIONES ACTUALES ...................................................................... 72
FIGURA 72. VISTA ISOMTRICA EN CONDICIONES ACTUALES ........................................................................... 73
FIGURA 73. ENERGYPLUS ESTRUCTURA SIMPLIFICADA .................................................................................... 75
FIGURA 74. VENTANA EP-LAUNCH.................................................................................................................. 75
FIGURA 75. RESULTADOS SIMULACIN ............................................................................................................ 76
FIGURA 76. PANEL RPIDO DE RESULTADOS .................................................................................................... 76
FIGURA 77. ASIGNACIN DE SALIDAS AL ARCHIVO IDF ................................................................................... 77
FIGURA 78. MUESTRA DEL ARCHIVO CSV ....................................................................................................... 78
FIGURA 79. LADO IZQUIERDO DE LA VENTANA DE XESOVIEW ......................................................................... 78
FIGURA 80. LADO DERECHO DE LA VENTANA DE XESOVIEW ........................................................................... 79
FIGURA 81. VENTANA DE DVIEW ..................................................................................................................... 80
FIGURA 82. PESTAA PROFILE DE DVIEW......................................................................................................... 81
FIGURA 83. MAPA TRMICO DVIEW ................................................................................................................. 81
FIGURA 84. BOXPLOT DVIEW ........................................................................................................................... 82
FIGURA 85. VENTANA INICIAL IDF EDITOR ..................................................................................................... 83
FIGURA 86. SIMULATIONCONTROL IDF EDITOR .............................................................................................. 83
FIGURA 87. BUILDING IDF EDITOR .................................................................................................................. 84
FIGURA 88. SIMULATION PARAMETERS IDF EDITOR ....................................................................................... 84
FIGURA 89. TIMESTEP IDF EDITOR .................................................................................................................. 84
FIGURA 90. SITE:LOCATION IDF EDITOR ......................................................................................................... 85
FIGURA 91. RUNPERIOD IDF EDITOR ............................................................................................................... 85
FIGURA 92. SURFACE CONSTRUCTION ELEMENTS IDF EDITOR ....................................................................... 86
FIGURA 93. MATERIAL IDF EDITOR ................................................................................................................. 86
FIGURA 94. SIMPLEGLAZINGSYSTEM IDF EDITOR .......................................................................................... 86
FIGURA 95. GLAZING IDF EDITOR ................................................................................................................... 87
FIGURA 96. SOLAR DIFFUSING ......................................................................................................................... 88
FIGURA 97. GAS IDF EDITOR ........................................................................................................................... 88
FIGURA 98. EJEMPLO CONSTRUCCIN DE SUELO IDF EDITOR .......................................................................... 89
FIGURA 99. EJEMPLO CONSTRUCCIN DE VENTANA IDF EDITOR ..................................................................... 89
FIGURA 100. CONSTRUCTION IDF EDITOR ....................................................................................................... 89
FIGURA 101. GLOBALGEOMETRYRULES IDF EDITOR...................................................................................... 90
FIGURA 102. SISTEMA DE COORDENADAS IDF EDITOR .................................................................................... 90
FIGURA 103. BUILDING SURFACES IDF EDITOR ............................................................................................... 90
FIGURA 104. FRAME AND DIVIDER 1 IDF EDITOR ............................................................................................ 91
FIGURA 105. FRAME AND DIVIDER 2 IDF EDITOR ............................................................................................ 92
FIGURA 106. FRAME AND DIVIDER 3 IDF EDITOR ............................................................................................ 92

Memoria descriptiva
FIGURA 107. FRAME AND DIVIDER IDF EDITOR ............................................................................................... 93
FIGURA 108. VARIABLES DE VENTILACIN ...................................................................................................... 94
FIGURA 109. TERMOSTATO EN IDF EDITOR...................................................................................................... 94
FIGURA 110. HVAC IDEALLOADSAIRSYSTEM IDF EDITOR ............................................................................ 95
FIGURA 111. GANANCIA INTERNA .................................................................................................................... 95
FIGURA 112. OCUPACIN ................................................................................................................................. 96
FIGURA 113. HORARIO OFICINAS...................................................................................................................... 96
FIGURA 114. ACTIVIDAD OCUPACIN HUMANA ............................................................................................... 96
FIGURA 115. ILUMINACIN .............................................................................................................................. 97
FIGURA 116. EQUIPO ELCTRICO...................................................................................................................... 97
FIGURA 117. GANANCIA INTERNA SALA DE REUNIONES ................................................................................... 97
FIGURA 118. ACTIVIDAD METABLICA SALA DE REUNIONES ........................................................................... 98
FIGURA 119. ILUMINACIN SALA DE REUNIONES ............................................................................................. 98
FIGURA 120. EQUIPO ELCTRICO SALA DE REUNIONES ..................................................................................... 98
FIGURA 121. OCUPACIN RESTAURANTE ......................................................................................................... 99
FIGURA 122. HORARIO RESTAURANTES ........................................................................................................... 99
FIGURA 123. ILUMINACIN RESTAURANTE .................................................................................................... 100
FIGURA 124. ACRISTALAMIENTO DOBLE DESDE EL IDF EDITOR..................................................................... 100
FIGURA 125. CONSTRUCCIN PARA EL ACRISTALAMIENTO DOBLE EN EL IDF EDITOR ................................... 101
FIGURA 126. EDIFICIO VISTO POR GOOGLE SKETCHUP .................................................................................. 101
FIGURA 127. VISTA DEL ALZADO CON LA MEJORA DEL VOLADIZO ................................................................. 102
FIGURA 128. VISTA DE LA PLANTA CON LA MEJORA DEL VOLADIZO............................................................... 102
FIGURA 129. VISTA ISOMTRICA DE LA MEJORA DEL VOLADIZO .................................................................... 103
FIGURA 130. EDIFICIO CON VOLADIZO OCTUBRE 12:00H ............................................................................... 103
FIGURA 131. EDIFICIO CON VOLADIZO JULIO 12:00H ..................................................................................... 103
FIGURA 132. GRFICA DE POTENCIA (W) PLANTA 0....................................................................................... 105
FIGURA 133. GRFICA DE POTENCIA (W) PLANTA 1....................................................................................... 106
FIGURA 134. GRFICA DE POTENCIA (W) CONDICIONES NORMALES .............................................................. 107
FIGURA 135. GRFICA DE POTENCIA (W) PLANTA 0....................................................................................... 109
FIGURA 136. GRFICA DE POTENCIA (W) PLANTA 1....................................................................................... 110
FIGURA 137. GRFICA DE POTENCIA (W) ACRISTALAMIENTO DOBLE ............................................................ 111
FIGURA 138. GRFICA DE POTENCIA (W) PLANTA 0 VOLADIZO ..................................................................... 113
FIGURA 139. GRFICA DE POTENCIA (W) PLANTA 1 VOLADIZO ..................................................................... 114
FIGURA 140. GRFICA DE POTENCIA (W) VOLADIZO...................................................................................... 115
FIGURA 141. GRFICA DE POTENCIA (W) PLANTA 0 MIXTA ........................................................................... 117
FIGURA 142. GRFICA DE POTENCIA (W) PLANTA 1 MIXTA ........................................................................... 118

Memoria descriptiva
FIGURA 143. GRFICA DE POTENCIA (W) MIXTA............................................................................................ 119
FIGURA 144. GRFICA DE POTENCIA DE CALEFACCIN (W ) COMPARATIVA C.N. Y A.D ............................... 120
FIGURA 145. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA C.N. Y A.D............................. 120
FIGURA 146. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA PICOS C.N. Y A.D...................... 121
FIGURA 147. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA PICOS C.N. Y A.D................... 121
FIGURA 148. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA C.N. Y VOLADIZO ..................... 122
FIGURA 149. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA C.N. Y VOLADIZO .................. 122
FIGURA 150. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA PICOS C.N. Y VOLADIZO ............ 123
FIGURA 151. POTENCIA DE REFRIGERACIN (W) COMPARATIVA PICOS C.N. Y VOLADIZO ............................ 123
FIGURA 152. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA VOLADIZO Y A.D. ..................... 124
FIGURA 153. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA VOLADIZO Y A.D. .................. 125
FIGURA 154. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA PICOS VOLADIZO Y A.D. ........... 125
FIGURA 155. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA PICOS VOLADIZO Y A.D.......... 126
FIGURA 156. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA C.N. Y MIXTA ........................... 126
FIGURA 157. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA C.N. Y MIXTA ........................ 127
FIGURA 158. GRFICA DE POTENCIA DE CALEFACCIN (W) COMPARATIVA PICOS C.N. Y MIXTA.................. 127
FIGURA 159. GRFICA DE POTENCIA DE REFRIGERACIN (W) COMPARATIVA PICOS C.N. Y MIXTA .............. 128
FIGURA 160. CONFIGURACIN 1 .................................................................................................................... 131
FIGURA 161. CONFIGURACIN 2 .................................................................................................................... 131
FIGURA 162. CONFIGURACIN 3 .................................................................................................................... 131
FIGURA 163. CONFIGURACIN 4 Y 5............................................................................................................... 131
FIGURA 164. MODOS UTA............................................................................................................................. 133
FIGURA 165. PARTES UTA............................................................................................................................. 134
FIGURA 166. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 0 SECCIN 1 ............................................ 140
FIGURA 167. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 0 SECCIN 2 ............................................ 141
FIGURA 168. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 0 SECCIN 3 ............................................ 142
FIGURA 169. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 0 SECCIN 4 ............................................ 143
FIGURA 170. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 1 SECCIN 1 ............................................ 144
FIGURA 171. MODELO ESQUEMTICO DE CLIMATIZACIN PLANTA 1 SECCIN 2 ............................................ 145
FIGURA 172. CREACIN DE NUEVA OBRA ....................................................................................................... 146
FIGURA 173. CREACIN DE NUEVA OBRA VACA ............................................................................................ 146
FIGURA 174. INTRODUCCIN DE DATOS GENERALES DE LA OBRA .................................................................. 147
FIGURA 175. TIPO DE EDIFICIO ....................................................................................................................... 147
FIGURA 176. TIPO DE PROYECTO .................................................................................................................... 147
FIGURA 177. IMPORTACIN DE FICHEROS ...................................................................................................... 148
FIGURA 178. PUENTES TRMICOS LINEALES ................................................................................................... 149

Memoria descriptiva
FIGURA 179. MUROS Y PARTICIONES ............................................................................................................. 149
FIGURA 180. INTRODUCCIN DE NUEVO MATERIAL ....................................................................................... 149
FIGURA 181. CREACIN CERRAMIENTO DE FACHADA .................................................................................... 150
FIGURA 182. VENTANA GRAFICA DE CREACIN DE CERRAMIENTO................................................................. 150
FIGURA 183. CERRAMIENTO DE FACHADA PLANTA 0 EDIFICIO INEF ............................................................. 151
FIGURA 184. CERRAMIENTO DE FACHADA PLANTA 1 EDIFICIO INEF ............................................................. 151
FIGURA 185. MUROS Y PARTICIONES ............................................................................................................. 151
FIGURA 186. MATERIALES USADOS PARA LA TABIQUERA ............................................................................. 152
FIGURA 187. TABIQUERA PLANTA 0 EDIFICIO INEF ...................................................................................... 152
FIGURA 188. TABIQUERA PLANTA 1 EDIFICIO INEF ...................................................................................... 153
FIGURA 189. FORJADOS ................................................................................................................................. 153
FIGURA 190. INTRODUCCIN DE MATERIALES EN FORJADOS PARA LOS CIMIENTOS ........................................ 153
FIGURA 191. CIMIENTOS EDIFICIO INEF ........................................................................................................ 154
FIGURA 192. INTRODUCCIN DE MATERIALES EN FORJADOS PARA LA ENTREPLANTA .................................... 154
FIGURA 193. ENTREPLANTA EDIFICIO INEF................................................................................................... 155
FIGURA 194. INTRODUCCIN DE MATERIALES EN FORJADOS PARA LA CUBIERTA ........................................... 155
FIGURA 195. CUBIERTA EDIFICIO INEF.......................................................................................................... 156
FIGURA 196. HUECOS ..................................................................................................................................... 156
FIGURA 197. CARACTERSTICAS DE LAS PUERTAS .......................................................................................... 156
FIGURA 198. CAPTURAS ................................................................................................................................. 157
FIGURA 199. COLOCACIN DE PUERTA .......................................................................................................... 157
FIGURA 200. CARACTERSTICAS DEL MARCO DE VENTANA ............................................................................ 158
FIGURA 201. ALTURA DE VENTANA ............................................................................................................... 158
FIGURA 202. COLOCACIN DE VENTANA ....................................................................................................... 158
FIGURA 203. CONSTRUCCIN FINAL EDIFICIO INEF LLEIDA .......................................................................... 159
FIGURA 204. USO DE RECINTO ....................................................................................................................... 160
FIGURA 205. DESCRIPCIN DE RECINTO ......................................................................................................... 161
FIGURA 206. TEMPERATURA DE RECINTO ...................................................................................................... 161
FIGURA 207. OCUPACIN DE RECINTO ........................................................................................................... 162
FIGURA 208. ILUMINACIN DE RECINTO ......................................................................................................... 162
FIGURA 209. VENTILACIN DE RECINTO ........................................................................................................ 163
FIGURA 210. SUELO DE RECINTO .................................................................................................................... 163
FIGURA 211. TECHO DE RECINTO ................................................................................................................... 163
FIGURA 212. FALSO TECHO DE RECINTO......................................................................................................... 164
FIGURA 213. NOMBRE DE RECINTO ................................................................................................................ 164
FIGURA 214. SISTEMA DE EXPANSIN DIRECTA.............................................................................................. 169

Memoria descriptiva
FIGURA 215. SELECCIN SPLIT CONDUCIDO ................................................................................................... 170
FIGURA 216. SPLIT CONDUCIDO ..................................................................................................................... 170
FIGURA 217. SELECCIN UNIDAD RECUPERADORA DE CALOR ........................................................................ 171
FIGURA 218. UNIDAD RECUPERADORA DE CALOR .......................................................................................... 171
FIGURA 219. SELECCIN LNEA FRIGORFICA ................................................................................................. 172
FIGURA 220. SISTEMAS DE CONDUCCIN DE AIRE .......................................................................................... 172
FIGURA 221. SELECCIN CONDUCTO HORIZONTAL ........................................................................................ 173
FIGURA 222. CONDUCTO HORIZONTAL........................................................................................................... 173
FIGURA 223. SISTEMAS DE CONDUCCIN DE AIRE .......................................................................................... 173
FIGURA 224. SELECCIN DIFUSOR .................................................................................................................. 174
FIGURA 225. REJILLAS DE TOMA Y EXTRACCIN DE AIRE .............................................................................. 174
FIGURA 226. CALCULANDO............................................................................................................................ 175

10

Memoria descriptiva

ndice de tablas
TABLA 1. CLASIFICACIN DEL AIRE EXTERIOR (FUENTE: NORMA UNE EN 13779)...................................... 24
TABLA 2. MATERIALES USADOS PARA EL FORJADO DEL EDIFICIO (FUENTE: CTE) ........................................... 26
TABLA 3. MATERIALES USADOS PARA LOS CERRAMIENTOS DE FACHADA DEL EDIFICIO (FUENTE: CTE) ......... 27
TABLA 4. MATERIALES USADOS PARA LOS CERRAMIENTOS INTERIORES DEL EDIFICIO (FUENTE: CTE) ........... 27
TABLA 5. MATERIALES USADOS PARA LA CUBIERTA DEL EDIFICIO (FUENTE: CTE) ......................................... 28
TABLA 6. MATERIALES USADOS PARA ENTREPLANTA DEL EDIFICIO (FUENTE: CTE) ....................................... 28
TABLA 7. SUPERFICIE TIL RECINTOS EDIFICIO OFICINAS INEF LLEIDA .......................................................... 29
TABLA 8. VALORES DE AISLAMIENTO TRMICO DE VESTIMENTA (FUENTE: UNE EN 13779) .......................... 29
TABLA 9. ACTIVIDADES METABLICAS (FUENTE: UNE EN 13779) ................................................................. 30
TABLA 10. SUPERFICIE DE SUELO POR PERSONA (FUENTE: RITE).................................................................... 30
TABLA 11. TIPO DE USO DE CADA RECINTO A CLIMATIZAR EN PLANTA 0 ......................................................... 30
TABLA 12. NUMERO DE PERSONAS EN CADA RECINTO A CLIMATIZAR EN PLANTA 0......................................... 31
TABLA 13. NUMERO DE PERSONAS EN CADA RECINTO A CLIMATIZAR EN PLANTA 1......................................... 31
TABLA 14. HORARIO DE OCUPACIN DE OFICINAS Y SALAS DE REUNIONES...................................................... 32
TABLA 15. HORARIO DE OCUPACIN DE SALAS DE RESTAURACIN.................................................................. 32
TABLA 16. NIVELES DE ILUMINACIN EN LUX (FUENTE: UNE EN 13779)....................................................... 32
TABLA 17. NIVELES DE ALTA EFICIENCIA ENERGTICA EN ILUMINACIN (FUENTE: UNE EN 13779).............. 32
TABLA 18. DISTANCIAS DE LA ZONA OCUPADA (FUENTE: UNE EN 13779) ..................................................... 33
TABLA 19. INTERVALOS DE TEMPERATURA OPERATIVA (FUENTE: UNE EN 13779) ........................................ 34
TABLA 20. VELOCIDAD DEL AIRE (FUENTE: RITE) .......................................................................................... 35
TABLA 21. CAUDAL DE AIRE POR PERSONA (FUENTE: RITE) ........................................................................... 35
TABLA 22. CAUDAL DE VENTILACIN EDIFICIO OFICINAS PLANTA 0 INEF LLEIDA .......................................... 36
TABLA 23. CAUDAL DE VENTILACIN EDIFICIO OFICINAS PLANTA 0 INEF LLEIDA .......................................... 36
TABLA 24. CARACTERSTICAS ACRISTALAMIENTO DOBLE (FUENTE: CTE) ...................................................... 39
TABLA 25. EFICIENCIA DE LA RECUPERACIN (FUENTE: RITE) ....................................................................... 41
TABLA 26. POTENCIA ESPECIFICA DE VENTILADORES (FUENTE: RITE)............................................................ 42
TABLA 27. CONTROL DE LAS CONDICIONES TERMO-HIDROMTRICAS (FUENTE: RITE) ................................... 44
TABLA 28. CONTROL DE LA CALIDAD DEL AIRE INTERIOR (FUENTE: RITE) ..................................................... 44
TABLA 29. SUPERFICIE PASO 1 ......................................................................................................................... 68
TABLA 30. SUPERFICIE PASO 2 ......................................................................................................................... 68
TABLA 31. SUPERFICIE PASO 3 ......................................................................................................................... 69
TABLA 32. SUPERFICIE PASO 4 ......................................................................................................................... 69
TABLA 33. SUPERFICIE PASO 5 ......................................................................................................................... 70
TABLA 34. SUPERFICIE PASO 6 ......................................................................................................................... 70

11

Memoria descriptiva
TABLA 35. SUPERFICIE PASO 7 ......................................................................................................................... 71
TABLA 36. RESUMEN MENSUAL PLANTA 0 CONDICIONES NORMALES ............................................................. 104
TABLA 37. RESUMEN ANUAL PLANTA 0 CONDICIONES NORMALES ................................................................. 105
TABLA 38. RESUMEN MENSUAL PLANTA 1 CONDICIONES NORMALES ............................................................. 106
TABLA 39. RESUMEN ANUAL PLANTA 1 CONDICIONES NORMALES ................................................................. 106
TABLA 40. RESUMEN MENSUAL CONDICIONES NORMALES ............................................................................. 107
TABLA 41. RESUMEN ANUAL CONDICIONES NORMALES ................................................................................ 108
TABLA 42. RESUMEN MENSUAL PLANTA 0 ACRISTALAMIENTO DOBLE ........................................................... 108
TABLA 43. RESUMEN ANUAL PLANTA 0 ACRISTALAMIENTO DOBLE .............................................................. 109
TABLA 44. RESUMEN MENSUAL PLANTA 1 ACRISTALAMIENTO DOBLE ........................................................... 110
TABLA 45. RESUMEN ANUAL PLANTA 1 ACRISTALAMIENTO DOBLE .............................................................. 110
TABLA 46. RESUMEN MENSUAL ACRISTALAMIENTO DOBLE ........................................................................... 111
TABLA 47. RESUMEN ANUAL ACRISTALAMIENTO DOBLE ............................................................................... 111
TABLA 48. RESUMEN MENSUAL PLANTA 0 VOLADIZO .................................................................................... 112
TABLA 49. RESUMEN ANUAL PLANTA 0 VOLADIZO ....................................................................................... 112
TABLA 50. RESUMEN MENSUAL PLANTA 1 VOLADIZO ................................................................................... 113
TABLA 51. RESUMEN ANUAL PLANTA 1 VOLADIZO ....................................................................................... 113
TABLA 52. RESUMEN MENSUAL VOLADIZO .................................................................................................... 115
TABLA 53. RESUMEN ANUAL VOLADIZO ........................................................................................................ 115
TABLA 54. RESUMEN MENSUAL PLANTA 0 MIXTA .......................................................................................... 116
TABLA 55. RESUMEN ANUAL PLANTA 0 MIXTA .............................................................................................. 116
TABLA 56. RESUMEN MENSUAL PLANTA 1 MIXTA .......................................................................................... 117
TABLA 57. RESUMEN ANUAL PLANTA 1 MIXTA .............................................................................................. 118
TABLA 58. RESUMEN MENSUAL MIXTO .......................................................................................................... 119
TABLA 59. RESUMEN ANUAL MIXTA .............................................................................................................. 119
TABLA 60. COMPARATIVA POTENCIA RESPECTO CONDICIONES ACTUALES .................................................... 128
TABLA 61. RESUMEN DEL LISTADO DE CARGAS TRMICAS PARA EDIFICIO INEF ........................................... 167
TABLA 62. RESUMEN DEL LISTADO DE CARGAS TRMICAS PARA EDIFICIO INEF ........................................... 168
TABLA 63. RESUMEN RESULTADOS REFRIGERACIN PARA EL EDIFICIO INEF ................................................ 169
TABLA 64. RESUMEN RESULTADOS CALEFACCIN PARA EL EDIFICIO INEF ................................................... 169

12

Memoria descriptiva

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con
CYPE Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01

Data y firmas de los anteriormente citados

Reus, Mayo de 2011

13

Memoria descriptiva

Introduccin

En el presente proyecto se realiza el estudio energtico del edificio de oficinas del


complejo INEF Lleida mediante EnergyPlus, programa motor de clculo para simulacin
energtica, y se implementa la instalacin de climatizacin de dicho edificio mediante el
programa CYPE Ingenieros.
El presente proyecto se divide en tres bloques.
En el primer bloque, se caracteriza el edificio, y se especifica toda la informacin relativa a
meteorologa, precipitaciones, datos climticos, radiacin solar, etc. Tambin se detalla el
nivel de ocupacin del edificio y se definen las caractersticas constructivas del mismo as
como los materiales que lo componen, los cuales estn descritos en el apartado del
Catlogo de Elementos Constructivos dentro del Cdigo Tcnico de la Edificacin (CTE).
Una vez se enumeran los diferentes elementos constructivos del edificio, a continuacin se
detalla la geometra interior del edificio indicando la superficie til de cada recinto que
constituye cada una de las plantas. Seguidamente se determinan las condiciones de
funcionamiento de cada recinto, es decir, rango de temperatura operativa, ventilacin,
ocupacin, etc., segn nos especifica el Reglamento de Instalaciones Trmicas de los
Edificios (RITE) y la Norma Espaola de Ventilacin en edificios no residenciales
procedente de la Normativa Europea 13779. Dentro de este bloque tambin se proponen
algunas mejoras en la constitucin del edifico para minimizar el impacto de cargas
trmicas en el edificio.
El segundo bloque trata sobre el balance energtico del edificio donde se utiliza el
programa Google SketchUp para el diseo tridimensional del edificio y el motor de calculo
EnergyPlus en el cual introduciremos los valores que se han recopilado en el bloque
anterior. Una vez introducidos los datos en EnergyPlus y realizado el modelo con Google
SketchUp. El modelo del edificio se somete a cuatro tipos de simulacin la primera de ellas
corresponde a la situacin actual del edificio, las tres restantes corresponden a cada una de
las propuestas de mejora que se incluyen en este proyecto (voladizo, acristalamiento doble,
y ambas mejoras combinadas). Una vez se han realizado las simulaciones y se han
obtenido los resultados, se procede a la evaluacin y comparacin de dichos resultados
para cada una de las tres alternativas de mejora propuestas para disminuir el clculo de
cargas.
Para iniciar el bloque numero tres, se realiza un estudio de los sistemas de climatizacin
existentes en el mercado dependiendo de su elemento de transmisin (aire o agua). Se elige
el sistema ms adecuado para nuestra climatizacin y seguidamente se crea un modelo
esquemtico de la instalacin para conductos, elementos interiores, difusores, etc.
Posteriormente se disea e implementa la instalacin de climatizacin mediante el
programa CYPE Ingenieros. Este bloque se compone de tres fases: la fase numero uno es el
diseo del modelo del edificio con CYPE Ingenieros en el cual se insertan los datos de
construccin, orientacin, puentes trmicos, etc., todos ellos recopilados en el bloque uno
especificado anteriormente. La segunda fase hace referencia al clculo de cargas trmicas,
por un lado se define el da de proyecto con las condiciones trmicas ms desfavorables y
por otro lado se asignan los recintos que se van a climatizar dependiendo de su uso real.
Como ultima fase de este tercer bloque se disea y realiza la instalacin de climatizacin.
Una vez se han finalizado las tres fases se procede a comprobar si cumple de manera
estricta las normativas vigentes y se generan los diferentes anexos del presente proyecto.

14

Memoria descriptiva

Objeto

El principal objetivo del presente proyecto es el estudio energtico con motivo de


disminuir el consumo energtico y la implementacin del sistema de climatizacin en el
edificio de oficinas de INEF Lleida, para ello se han adquirido conocimientos de:
I. Bsqueda y uso de normativas para obtener informacin: Ventilacin de edificios no
residenciales, Reglamento de Instalaciones Trmicas de los Edificios, Cdigo
Tcnico de la Edificacin, etc.
II. Climatizacin y acondicionamiento del aire, creando as unas condiciones de
temperatura, humedad y limpieza del aire adecuadas para la comodidad de los
espacios habitados.
III. Diseo de edificios tridimensional con Google SketchUp.
IV. Uso del motor de clculo para cargas trmicas en edificios EnergyPlus.
V. Funcionamiento del programa de diseo, simulacin y clculo de instalaciones en
edificios CYPE Ingenieros.

15

Memoria descriptiva

Alcance

Con la ayuda de este proyecto podemos optimizar de forma considerable los costes
energticos del edificio objeto de estudio. Esta instalacin se encuentra situada en el centro
de estudios universitarios INEF Lleida, situado en un terreno propiedad del ayuntamiento
de Lleida, con direccin calle Caparrella y con cdigo postal 25192.
La instalacin de climatizacin se montar en dependencias reservadas para su uso,
situadas en la cubierta del edificio, constituido por dos plantas con una superficie
construida til de 2218,25 m2.

Antecedentes

En los edificios, la climatizacin representa alrededor de un 60% del consumo energtico


de un pas (segn el Instituto de Energa Espaola). De este dato se desprende la
importancia de realizar un estudio completo de la instalacin, pues cualquier pequea
mejora puede suponer un ahorro importante en la factura energtica. La climatizacin de
un edificio depende de varios factores. Entre ellos, destaca la ubicacin, la orientacin, los
elementos arquitectnicos, las fuentes de energa de las que dispone, etc. Esto hace que sea
especialmente difcil encontrar un sistema de climatizacin universal que permita tratar
trmicamente todos los edificios de la mejor manera posible. Sin embargo, s que se puede
encontrar el tipo de instalacin que ms se adecua a cada edificacin. Para ello hace falta
un estudio orientativo de cargas trmicas y otro estudio de los sistemas de climatizacin
que existen en el mercado.
Actualmente hay muchos edificios que podran ser ms eficientes energticamente si
gestionaran mejor la instalacin de climatizacin. Se decide llevar a cabo el presente
proyecto, para realizar el balance energtico y la implementacin de la instalacin del
sistema de climatizacin del edificio de oficinas del complejo INEF Lleida.

16

Memoria descriptiva

Normas y referencias

5.1

Disposiciones legales y normas aplicadas

Real Decreto 314/2006, de 17 de marzo, por el cual se aprueba el Cdigo Tcnico de la


Edificacin (CTE).
Real Decreto 1027/2007, de 20 de julio, por el cual se aprueba el Reglamento de
Instalaciones Trmicas en los Edificios (RITE).
Real Decreto 216/99, de 8 de noviembre, de Prevencin de Riesgos Laborales (PRL).
UNE 157001 Criterios generales para la elaboracin de proyectos.
UNE EN 673/2003 Vidrio en la construccin. Determinacin del coeficiente de
transmisin trmica (valor U). Mtodo de clculo.
UNE EN 13779/2005 Ventilacin de edificios no residenciales. Requisitos de
prestaciones de los sistemas de ventilacin y condicionamiento de recintos.
UNE EN 15251/2008 Parmetros de ambiente interior a considerar en el diseo y la
evaluacin de la eficiencia energtica de edificios incluyendo la calidad del aire interior,
condiciones trmicas, iluminacin y ruido.
UNE EN ISO 1751/99 Ventilacin de edificios. Unidades terminales de aire. Ensayos
aerodinmicos de compuertas y vlvulas.
UNE EN 12097/98 Ventilacin de edificios. Conductos. Requisitos relativos a los
componentes destinados a facilitar el mantenimiento de los sistemas de conductos.
UNE EN 14336/2005 Ventilacin de edificios. Unidades de tratamiento de aire (UTA).

5.2
[1]

Bibliografa Web
Documento bsico HE
http://www.codigotecnico.org

[2]

Energy Plus 4.0


http://apps1.eere.energy.gov/buildings/EnergyPlus

[3]

Google SketchUp 7.0


http://SketchUp.google.com/intl/es/

[4]

Open Studio
http://apps1.eere.energy.gov/buildings/EnergyPlus/openstudio.cfm

[5]

RITE

17

Memoria descriptiva

http://www.mityc.es/energia/desarrollo/EficienciaEnergetica/RITE/Reconocidos/Re
conocidos/8Guia_7.pdf
[6]

Ministerio de Industria, Turismo y Comercio


http://www.mityc.es/ENERGIA/DESARROLLO/EFICIENCIAENERGETICA/CERTI
FICACIONENERGETICA/Paginas/certificacion.aspx

[7]

Mejora del voladizo


http://www.toldos.info/toldos/brazos_articulados/monobloc/

[8]

Mejora del acristalamiento doble


http://www.climalit.es

5.3

Programas de clculo y simulacin

GOOGLE SKETCHUP

Programa de diseo grafico tridimensional.

ENERGYPLUS

Motor grafico para realizar simulaciones de cargas


energticas.

CYPE INGENIEROS

Programa de diseo y calculo para realizar instalaciones


de climatizacin en edificios.

5.4

Plan de gestin de la calidad aplicada durante la redaccin del


proyecto

El presente proyecto ha sido elaborado por Fernando Pallars Cepero, siguiendo la


normativa vigente por la redaccin y elaboracin de proyectos (UNE 175001).

Definiciones y acrnimos

6.1

Definiciones

Aire del ambiente Es el aire del espacio interior de un edificio.


Aire exterior Es el aire de la atmsfera exterior (a un edificio).
Aire de recirculacin Es el aire de retorno que, nuevamente tratado en la unidad, se
vuelve a poner en el circuito del sistema para impulsarlo a los locales acondicionados.
Caldera El conjunto formado por el cuerpo de la caldera y el quemador, destinado a
transmitir al agua el calor liberado por la combustin.
Calefaccin Proceso por el que se controla solamente la temperatura del aire de los
espacios con carga negativa.

18

Memoria descriptiva

Calor latente Es el calor de cambio de estado, la energa requerida por una sustancia para
cambiar de estado, de slido a lquido (calor de fusin) o de lquido a gaseoso (calor de
vaporizacin). Al cambiar de gaseoso a lquido y de lquido a slido se libera la misma
cantidad de energa.
Calor sensible Es la energa calorfica que, aplicada a una sustancia, aumenta su
temperatura. La oposicin a calor latente.
Capacidad Usada con los adjetivos calorficos y frigorficos y referidos a una mquina
frigorfica es sinnimo de potencia, es decir, energa dividido por la unidad de tiempo (del
ingls capacity). As la capacidad frigorfica es la cantidad de calor cedida por el fluido
portador que circula por el evaporador al fluido refrigerante en la unidad de tiempo,
mientras que la capacidad calorfica es la cantidad de calor captada por el fluido portador
que circula por el condensador al fluido refrigerante en la unidad de tiempo.
Cerramiento Conjunto de elementos del edificio o local que separan su interior del
ambiente exterior. Existe cerramiento interior y exterior. Los primeros no se encuentran
expuestos a factores exteriores tales como lluvia, granizo, calor, fro, etc; pero s poseen
grandes caractersticas acsticas. Mientras que los cerramientos exteriores son los que
enfrentan las adversidades del exterior: su cara exterior es de tipo impermeable y tiene
como funcin disminuir el ruido y reflejar la luz.
Climatizacin Accin y efecto de climatizar, es decir, de dar a un espacio cerrado las
condiciones de temperatura, humedad relativa, pureza del aire y, a veces, tambin de
presin, necesarias para el bienestar de las personas y/o la conservacin de las cosas.
Conduccin trmica Es un mecanismo de transferencia de energa trmica entre dos
sistemas basado en el contacto directo de sus partculas sin flujo neto de materia y que
tiende a igualar la temperatura dentro de un cuerpo y entre diferentes cuerpos en contacto
por medio de ondas.
Conveccin Es una de las tres formas de transferencia de calor y se caracteriza porque se
produce por intermedio de un fluido (aire, agua) que transporta el calor entre zonas con
diferentes temperaturas. La conveccin se produce nicamente por medio de materiales
fluidos. stos, al calentarse, aumentan de volumen y, por lo tanto, su densidad disminuye y
ascienden desplazando el fluido que se encuentra en la parte superior y que est a menor
temperatura. Lo que se llama conveccin en s, es el transporte de calor por medio de las
corrientes ascendente y descendente del fluido.
GTM (Greenwich Mean Time) Es el tiempo solar medio en el Observatorio Real de
Greenwich, en Greenwich, cerca de Londres, Inglaterra, que por convencin est a 0
grados de longitud. Durante muchos aos los relojes ms precisos que existan eran el
movimiento de la Tierra alrededor de su eje y alrededor del Sol. A partir de ellos se defina
todo lo dems relacionado con el tiempo.
Humedad relativa Cantidad de vapor de agua presente en el aire. Se puede expresar de
forma absoluta mediante la humedad absoluta, o de forma relativa mediante la humedad
relativa o grado de humedad. La humedad relativa es la relacin porcentual entre la
cantidad de vapor de agua real que contiene el aire y la que necesitara contener para
saturarse a idntica temperatura, por ejemplo, una humedad relativa del 70% quiere decir

19

Memoria descriptiva

que de la totalidad de vapor de agua (el 100%) que podra contener el aire a esta
temperatura, solo tiene el 70%.
Infiltracin Es la migracin de aire desde el exterior de un espacio hacia el mismo
espacio a travs de discontinuidades en los elementos de cerramientos por efecto de una
diferencia de presin.
Instalacin unitaria Es aquella en la que la produccin de fro y/o calor es independiente
para cada local.
Local tcnico Espacio destinado nicamente a albergar maquinaria de las instalaciones.
Mantenimiento Conjunto de operaciones necesarias para asegurar un elevado
rendimiento energtico, seguridad de servicio y defensa del medio ambiente durante el
funcionamiento de una instalacin.
Prdida de carga Cada de presin de un fluido, distribuida y localizada, en su paso a
travs de un aparato o desde un punto a otro de una canalizacin.
Potencia absorbida A los efectos de este Reglamento, se entender por potencia
absorbida, en el caso de compresores hermticos o semihermticos, la mxima potencia
elctrica consumida por el motor en el campo de condiciones de aspiracin y descarga
permitidas por el fabricante en su catlogo. En el caso de compresores abiertos, se
computar como potencia absorbida la potencia nominal del motor elctrico.
Radiacin Propagacin de energa en forma de ondas electromagnticas o partculas
subatmicas a travs del vaco o de un medio material.
Refrigeracin En climatizacin, proceso que controla solamente la temperatura del aire
de los espacios con carga positiva.
Renovaciones Relacin entre el caudal de aire exterior introducido en el local y el
volumen neto de ste; la unidad de tiempo suele ser la hora (empleando un lenguaje
apropiado, debera utilizarse la expresin caudal especifico de aire impulsado).
Sala de mquinas Local tcnico donde se alojan los equipos de produccin de fro o calor
y equipos accesorios.
Temperatura de bulbo seco O temperatura seca es la medida con un termmetro
convencional de mercurio o similar cuyo bulbo se encuentra seco. Esta temperatura junto a
la temperatura de bulbo hmedo es utilizada en la valoracin del confort higrotrmico, en
la determinacin de la humedad relativa, en la determinacin del punto de roco, en
psicrometra para el estudio y determinacin del comportamiento de mezclas de aire.
Transferencia de calor Paso de energa trmica desde un cuerpo de mayor temperatura a
otro de menor temperatura. Cuando un cuerpo, por ejemplo, un objeto slido o un fluido,
est a una temperatura diferente de la de su entorno u otro cuerpo, la transferencia de
energa trmica, tambin conocida como transferencia de calor o intercambio de calor,
ocurre de tal manera que el cuerpo y su entorno alcancen equilibrio trmico. La
transferencia de calor siempre ocurre desde un cuerpo ms caliente a uno ms fro, como
resultado de la ley cero de la termodinmica. Cuando existe una diferencia de temperatura

20

Memoria descriptiva

entre dos objetos en proximidad uno del otro, la transferencia de calor no puede ser
detenida; solo puede hacerse ms lenta.
Ventilacin natural Proceso de renovacin del aire de los locales por medios naturales
(accin del viento y/o tiro trmico), la accin de los cuales puede verse favorecida con
apertura de elementos de los cerramientos.
Volumen especfico Es el volumen ocupado por unidad de masa de un material. Es la
inversa de la densidad. No dependen de la cantidad de materia. Ejemplos: dos pedazos de
hierro de distinto tamao tienen diferente peso y volumen pero el peso especfico de ambos
ser igual. Este es independiente de la cantidad de materia considerada para calcularlo. A
las propiedades que no dependen de la cantidad de materia se las llama "Propiedades
Intensivas". Dentro de estas estn tambin por ejemplo el punto de ebullicin, el brillo, el
color, la dureza y el punto de fusin.
Zona Grupo de espacios climatizados cuya carga trmica vara de manera uniforme en el
tiempo y, en general, de forma diferente a otras zonas.
Zona de bienestar Parte del diagrama del aire hmedo definida por unas condiciones
termo higromtricas que satisfacen a la mayora de los ocupantes.
Zona ocupada Zona normalmente ocupada por las personas.

6.2

Acrnimos

BMS Building Management System.


COP Coefficient Of Performance.
CTE Cdigo Tcnico de la Edificacin
EER Energy Efficiency Ratio.
HR Heat Recovery.
HR Humedad Relativa.
IDA Calidad de aire interior.
IT Intensidad de Turbulencia.
ODA Calidad de aire exterior.
OMD Oscilacin Media Diaria.
PPD Porcentaje Previsible de Insatisfechos.
PRL Prevencin de riesgos laborales
RITE Reglamento de Instalaciones Trmicas en los Edificios
UTA Unidad de Tratamiento de Aire.

21

Memoria descriptiva

Descripcin del proceso

A continuacin se muestra la estructura de la descripcin del proceso del presente proyecto


en forma de diagrama de bloques, posteriormente se procede a comentar las fases y
bloques ms importantes.

Figura 1. Diagrama de bloques

22

Memoria descriptiva

I. Requisitos de diseo y cumplimiento de normativa


En este bloque se encuentra toda la informacin para la correcta realizacin del presente
proyecto, se realiza una recopilacin de los valores dentro de las normativas para realizar
una correcta simulacin de las condiciones tanto interiores del edificio como las exteriores
de la localidad donde se ubica el presente.
II. Estudio de viabilidad energtica
En el siguiente bloque se usarn dos de los tres programas que se han empleado para la
realizacin del presente proyecto, estos dos programas son:
a. Google SketchUp
b. EnergyPlus
Mediante Google SketchUp disearemos de manera tridimensional el edificio de oficinas
del complejo INEF Lleida. Una vez terminada la creacin del edificio, usaremos el
programa EnergyPlus, para someter el edificio a diferentes simulaciones y generar los
diferentes resultados.
III. Instalacin del sistema de climatizacin
En este bloque se emplea el programa CYPE Ingenieros, que es el ltimo que se utiliza en
la realizacin del presente proyecto. Con dicho programa se realiza la implementacin de
la instalacin de climatizacin, la cual se divide en tres fases:
a. La primera fase es la creacin del modelo del edificio, donde se debe
introducir de manera correcta los valores de construccin.
b. La segunda fase es la obtencin del listado de cargas trmicas, para el
posterior dimensionado de la instalacin de climatizacin.
c. La tercera fase y ultima, es la colocacin de la instalacin en el edificio.

7.1

Requisitos de diseo y cumplimiento de normativa

7.1.1

Localizacin, condiciones exteriores y vecindario

El edificio de estudio pertenece a la universidad INEF, ubicada en la localidad de Lleida,


ciudad espaola, capital de comarca y situada en la comunidad autnoma de Catalua. La
ciudad est bien comunicada por carreteras, autopista y autovas. La A-2 y la AP-2 la unen
con Madrid y Barcelona. Lleida tambin tiene una importante estacin ferroviaria de la que
parten trenes de alta velocidad, larga distancia, etc. En cuanto a movilidad interna, Lleida
tiene con una red de autobuses urbanos de 23 lneas. Desde enero de 2010, adems, est en
funcionamiento el Aeropuerto de Lleida, ubicado a 15 Km. de la ciudad.
Una vez ofrecida la informacin ms significativa tal como vecindario, edificios,
carreteras, campos de aviacin, y cualquier otro dato importante que pueda influir en el
diseo, se pasa a definir la categora del aire exterior de acuerdo con la tabla nmero 1 de
la normativa UNE EN 13779 de ventilacin en edificios no residenciales.

23

Memoria descriptiva

Categora
ODA 1
ODA 2
ODA 3
ODA 4
ODA 5

Descripcin
Aire puro que solo puede ensuciarse temporalmente (por ejemplo polen).
Aire exterior con altas concentraciones de partculas.
Aire exterior con altas concentraciones de gases contaminantes.
Aire exterior con altas concentraciones de gases contaminantes y de partculas.
Aire exterior con muy altas concentraciones de gases contaminantes o de
partculas.
Tabla 1. Clasificacin del aire exterior (Fuente: Norma UNE EN 13779)

7.1.2

Informacin sobre el uso del edificio

Para obtener una informacin lo ms fiable posible acudimos a la pgina Web de INEF
Lleida, donde se podrn encontrar los horarios y calendarios del curso, es decir el uso
potencial de las instalaciones. Se establecer la ocupacin durante los das tpicos y los
periodos anuales no-ocupados. En cuanto al uso general durante la noche y los fines de
semana, se establece que no hay paso de personas por el edificio.
Se define como periodo lectivo el nmero de das comprometidos entre el da 7 de
Septiembre donde se acogen los alumnos que cursan el primer ao de grado hasta el 23 de
Julio, que es el da donde se entregan las actas por parte de los profesores.
Es decir se tiene un periodo del ao donde no hay ocupacin en el edificio, se puede definir
el mes de Agosto como el mes donde no existe ningn tipo de ocupacin. A continuacin
se adjunta dicho calendario de donde se ha extrado esta informacin.

24

Memoria descriptiva

Figura 2. Calendario anual de la universidad (Fuente: Web INEF Lleida)

25

Memoria descriptiva

7.1.3

Datos constructivos del edificio

En este apartado se detallarn los aspectos constructivos del edificio con los datos
caractersticos de las mismas, y de los materiales que las componen. Todos ellos cumplen
estrictamente el CTE, Cdigo Tcnico de la Edificacin. Los materiales y la constitucin
de estas construcciones son facilitadas por la propiedad.

Cimientos o forjado inferior


Se define como forjado la parte de un edificio que queda enterrada y que sostiene toda la
construccin, dicho forjado est formado por las siguientes capas:
I. Losa Maciza d=2500 (200 mm.)
II. URSA XPS (70 mm.)
III. Mortero de cemento y para revoco/enlucido 1000 < d < 1250
IV. Plaqueta o baldosa cermica
Se accede al Catalogo de Elementos Constructivos del CTE y se anotan las caractersticas
de los elementos escritos, las cuales citan a continuacin en la siguiente tabla:
Nombre

Losa Maciza
d=2500

URSA XPS

Mortero de cemento y
para revoco/enlucido
1000 < d < 1250
Espesor (m)
0.2
0.07
0.02
Conductividad (W/m-K)
2.5
0.034
1
Densidad (kg/m3)
2500
35
1525
Calor Especifico (J/kg-K)
1000
800
1000
Tabla 2. Materiales usados para el forjado del edificio (Fuente: CTE)

Plaqueta
o baldosa
cermica
0.02
1
2000
800

Cerramientos exteriores o de fachada


Un cerramiento de fachada es el conjunto de elementos del edificio el cual enfrentan las
adversidades del exterior: su cara exterior es de tipo impermeable y tiene como funcin
disminuir el ruido y reflejar la luz para evitar el sobrecalentamiento del interior del edificio
y sus recintos.
La construccin es la siguiente,
I. Ladrillo cermico perforado (12 cm.)
II. XPS Polestireno 0.038 (4 cm.)
III. Ladrillo cermico hueco (11 cm.)
IV. Enlucido de yeso d < 1000 (1 cm.)
Una vez se ha identificado los materiales de la construccin se debe obtener las
caractersticas de cada uno de ellos, como la conductividad, rugosidad, densidad, etc. Para
ello se acude al CTE (Cdigo tcnico de la Edificacin) y se entra dentro del Catalogo de
Elementos Constructivos. Siguiendo el ndice de dicho documento se mueve y se dirige al
apartado nmero 3 de Materiales y Productos y all se busca los apartados de Enlucidos,
Fabrica de ladrillo cermico y aislantes trmicos.

26

Memoria descriptiva

Una vez obtenidos los materiales con todas sus caractersticas, se citan a continuacin en
una tabla:
Nombre

Ladrillo cermico
perforado cataln

XPS
Polestireno

Ladrillo
cermico hueco

Enlucido de
yeso
d < 1000
Espesor (m)
0.12
0.04
0.11
0.01
Conductividad (W/m-K)
0.567
0.038
0.435
0.4
3
Densidad (kg/m )
1020
30
920
900
Calor especifico (J/kg-K)
1000
1000
1000
100
Tabla 3. Materiales usados para los cerramientos de fachada del edificio (Fuente: CTE)

Cerramientos interiores o tabiquera


Un cerramiento interior es un muro que separa dos espacios y que comnmente no soporta
cargas de la estructura y poseen grandes caractersticas acsticas.
Donde,
I. Enlucido de yeso d < 1000 (20 mm.)
II. Tabique de LH sencillo (40 mm.)
III. Enlucido de yeso d < 1000 (20 mm.)
De la misma forma que se han obtenido los valores para los cerramientos exteriores se
busca dentro del Catalogo de Elementos Constructivos del CTE los materiales y se anotan
sus caractersticas, y se citan a continuacin:
Nombre

Enlucido de yeso
Tabique de LH sencillo
Enlucido de yeso
d < 1000
d < 1000
Espesor (m)
0.02
0.04
0.02
Conductividad (W/m-K)
0.4
0.444
0.4
Densidad (kg/m3)
900
1000
900
Calor especifico (J/kg-K)
100
1000
100
Tabla 4. Materiales usados para los cerramientos interiores del edificio (Fuente: CTE)

Cubierta o tejado
Se define como cubierta al sistema de cierre en la parte superior de una construccin. La
capa exterior est formada por las distintas partes.
I. Arena y grava (1700 < d < 2200) (20 mm.)
II. URSA XPS (80 mm.)
III. Asfalto (20 mm.)
IV. Hormign con ridos ligeros 1800 < d < 2000 (20 mm.)
V. Entrevigado de hormign aligerado (300 mm.)
VI. Enlucido de yeso d < 1000 (20 mm.)
De la misma forma que se han obtenido los valores para los cerramientos y los forjados se
busca dentro del Catalogo de Elementos Constructivos del CTE los materiales y se anotan
sus caractersticas, y se citan en la tabla siguiente:

27

Memoria descriptiva
Nombre

Espesor (m)
Conductividad (W/m-K)
Densidad (kg/m3)
Calor especifico (J/kg-K)

Arena y
grava

URSA
XPS

Asfalto

0.02
2
1950
1050

0.08
0.034
35
800

0.02
0.7
2100
1000

Hormign
con ridos
ligeros
0.02
1.35
1900
1000

Entrevigado
de hormign
aligerado
0.3
1.128
1090
1000

Enlucido
de yeso d
< 1000
0.02
0.4
900
100

Tabla 5. Materiales usados para la cubierta del edificio (Fuente: CTE)

Entreplanta o forjado entre pisos


Se define entreplanta como la planta que se construye entre una planta inferior y una planta
superior, los materiales son los siguientes:
Donde,
I. Enlucido de yeso d < 1000.
II. Entrevigado de hormign aligerado.
III. Mortero de cemento y para revoco/enlucido 1600 < d < 1800.
IV. Plaqueta o baldosa cermica.
De la misma forma que se han obtenido los valores para los cerramientos se busca dentro
del Catlogo de Elementos Constructivos del Cdigo Tcnico de la Edificacin los
materiales y se anotan sus caractersticas, y se citan a continuacin:
Nombre

Entrevigado
Mortero de cemento y
hormign
para revoco/enlucido
aligerado 300 mm.
1600 < d < 1800
Espesor (m)
0.02
0.3
0.02
Conductividad (W/m-K)
0.4
1.128
1
Densidad (kg/m3)
900
1090
1525
Calor especifico (J/kg-K)
100
1000
1000
Tabla 6. Materiales usados para entreplanta del edificio (Fuente: CTE)

7.1.4

Enlucido de
yeso d < 1000

Plaqueta
o baldosa
cermica
0.02
1
2000
800

Descripcin geomtrica del edificio

El edificio consta de dos plantas siendo la planta baja la de ms superficie, donde hay
despachos destinados a los distintos profesores que trabajan en la universidad. La planta
baja consta de siete oficinas, una sala de honor, una sala de audiovisuales, una sala de
juntas, una sala club y una sala de espera. Aparte se dispone de una cafetera con cocina y
un comedor para profesores. En su entrada principal se dispone de recepcin, secretaria,
servicio de reprografa, sala para la gestin acadmica y otra para la gestin econmica. La
planta alta consta de veintids despachos, una terraza de noventa 97 m2, de ocho servicios
y de las escaleras de 14 m2 que comunican con la planta inferior.
Se adjunta el plano de planta del edificio dentro del apartado de planos, donde se especifica
la superficie til de cada local.

28

Memoria descriptiva

A modo resumen, se especifican las superficies tiles del edificio en la tabla siguiente:
Edificio oficinas INEF Lleida
Superficie til (m2)
Porche
Archivo
Gestin econmica
Gestin de postgrado
Gestin acadmica
Atencin
Atencin informacin
Acceso
Secretara administrativa
Sala de espera
Subdireccin de estudios
Subdireccin de actividades
Secretaria direccin
Direccin
Subdireccin de Postgrado
Gerencia
Direccin OA
Sala Honor
Sala de Juntas
Cafetera
Sala audiovisuales
Comedor
Cocina

47.53
14.04
35.02
34.61
115.49
36.5
112.99
14.4
26.37
22.79
27.34
28.32
28.26
28.95
19.86
13.53
25.37
89.74
77.08
260.54
96.21
36.14
84.02

Superficie til (m2)

Limpieza
Despacho 101
Despacho 102
Despacho 103 104
Despacho 105
Despacho 106
Despacho 107
Despacho 108
Despacho 109
Despacho 110
Despacho 111
Despacho 112
Despacho 113
Despacho 115
Despacho 116
Despacho 117
Despacho 118
Despacho 119
Despacho 120
Despacho 121
Despacho 122
Despacho 123
Despacho 124

15.11
16.34
13.74
26.14
13.41
12.69
14.72
12.37
27.85
27.56
14.13
13.7
27.75
11.38
15.06
41.66
25.1
17.92
41.75
12.38
13.89
18.65
12.85

Tabla 7. Superficie til recintos edificio oficinas INEF Lleida

7.1.5

Cargas trmicas por ocupacin humana

Se especifican el nmero de personas que pueden estar en un recinto por un periodo largo
de tiempo, conforme la tabla nmero 13 de la norma UNE EN 13779. La tasa de
ventilacin deber disearse para este nivel de ocupacin calculado. Tambin se deber
poner atencin a la tabla nmero 14, la cual habla de la actividad y vestimenta.
Primeramente se analizar el cumplimiento de la tabla siguiente, la cual determina los
valores tpicos de clo (valores de aislamiento trmico de la vestimenta) en funcin de la
actividad descrita en met (actividad metablica, 1.2 met = 125 Watts).
Parmetro
Vestimenta

Intervalo tpico (clo) Valor por defecto para diseo


Verano: de 0.5 a 0.7
Verano: 0.5 clo
Invierno: de 0.8 a 1.0
Invierno: 1.9 clo
Actividad
1.0 a 1.4 met
1.2 met
Tabla 8. Valores de aislamiento trmico de vestimenta (Fuente: UNE EN 13779)

Otro aspecto importante a tener en cuenta en el diseo es la definicin de la actividad


metablica de las personas, para ello la norma UNE EN 13779 contiene la tabla en la cual
se puede ver valores de diferentes actividades con su desgaste en Watts.

29

Memoria descriptiva
Calor total
met
W/persona
0.8
80
1
100
1.2
125
1.6
170
2
210

Actividad

Acostado
Sentado, relajado
Actividad sedentaria (oficina, colegio)
De pie, actividad ligera (compras, industria ligera)
De pie, actividad media (dependiente, trabajo
mecnico)
Andando a 5 km/h
3.4
360
Tabla 9. Actividades metablicas (Fuente: UNE EN 13779)

Calor sensible
W/persona
55
70
75
85
105
120

De la tabla anterior, se deduce que el valor de la actividad metablica para una actividad
sedentaria (oficina, colegio) como es el caso la actividad metablica ser 1.2 met o, que es
lo mismo, 125 W/persona.
Posteriormente de tener los datos de la vestimenta en funcin de la actividad de 125 W,
equivalente a una persona sentada, como puede ser una tarea de oficina, se procede a
calcular el aforo de cada recinto, detallados en las tablas siguientes:
Superficie de suelo por persona en m2/persona
Valor por defecto
Oficinas paisaje
12
Oficinas pequeas
10
Salas de reuniones
3
Centros comerciales
4
Aulas
2.5
Salas de hospital
10
Habitaciones de hotel
10
Restaurantes
1.5
Tabla 10. Superficie de suelo por persona (Fuente: RITE)
Tipo de uso

A partir de la tabla y los datos obtenidos anteriormente de superficie de cada local se


obtiene el nmero de personas por local.
Planta 0 INEF Lleida
Nombre local
Tipo de uso Superficie til (m2)
Juntas
Reuniones
77.08
Honor
Reuniones
98.78
Direccin
Of. pequea
28.95
Secretaria Direccin
Of. pequea
28.26
Subsecretaria Actividades y Servicios Of. pequea
28.32
Subdireccin de Estudios
Of. pequea
27.34
Subdireccin Postgrado
Of. pequea
19.86
Gerencia
Of. pequea
13.53
Direccin OA
Of. pequea
25.37
Cafetera Restaurante
Restaurantes
260.54
Sala Audiovisuales
Reuniones
96.21
Comedor
Restaurantes
36.14
Servicio de Reprografita
Of. pequea
51.74
Sala de Espera
Reuniones
27.3
Secretaria admin.
Of. pequea
26.37
Gestin
Of. pequea
220.81
Tabla 11. Tipo de uso de cada recinto a climatizar en planta 0

30

Memoria descriptiva

A partir de las dos tablas anteriores se determina el nmero de aforo de cada recinto.
Planta 0 INEF Lleida
Nombre local

Tipo de uso

Superficie til (m2)

Nmero de personas

Juntas
Honor
Direccin
Secretaria Direccin
Subsecretaria Actividades y Servicios
Subdireccin de Estudios
Subdireccin Postgrado
Gerencia
Direccin OA
Cafetera Restaurante
Sala Audiovisuales
Comedor
Servicio de Reprografita
Sala de Espera
Secretaria admin.
Gestin

Reuniones
Reuniones
Of. pequea
Of. pequea
Of. pequea
Of. pequea
Of. pequea
Of. pequea
Of. pequea
Restaurantes
Reuniones
Restaurantes
Of. pequea
Reuniones
Of. pequea
Of. pequea

77.08
98.78
28.95
28.26
28.32
27.34
19.86
13.53
25.37
260.54
96.21
36.14
51.74
27.3
26.37
220.81

26
33
3
3
3
3
2
2
3
173
32
24
5
9
3
22

Tabla 12. Numero de personas en cada recinto a climatizar en planta 0

De la misma manera a partir de los datos de la descripcin geomtrica se calcular para la


planta 1, a continuacin se muestra la tabla resultante.

Nombre local
Despacho 101
Despacho 102
Despacho 103
104
Despacho 105
Despacho 106
Despacho 107
Despacho 108
Despacho 109
Despacho 110
Despacho 111
Despacho 112

Superficie
til (m2)
16.34
13.74
26.14
13.41
12.69
14.72
12.37
27.85
27.56
14.13
13.7

Planta 1 INEF Lleida


Nmero de
Nombre local
personas
2
Despacho 113
2
Despacho 115
3
Despacho 116
2
2
2
2
3
3
2
2

Despacho 117
Despacho 118
Despacho 119
Despacho 120
Despacho 121
Despacho 122
Despacho 123
Despacho 124

Superficie
til (m2)
27.75
11.38
15.06

Nmero de
personas
3
2
2

41.66
25.1
17.92
41.75
12.38
13.89
18.65
12.85

5
3
2
5
2
2
2
2

Tabla 13. Numero de personas en cada recinto a climatizar en planta 1

Una vez calculado el aforo por local, y definido su uso, se procede a definir el calendario
del perfil de ocupacin de cada uno de los locales, como se ha visto anteriormente solo se
han usado tres de los grupos a la hora de calcular el aforo, oficinas pequeas, salas de
reuniones y restaurantes. Se junta el calendario de ocupacin para oficinas pequeas y
salas de reuniones dentro de un mismo objeto llamado el calendario de oficina.
El calendario de oficina para oficinas pequeas y salas de reuniones queda definido de la
siguiente manera:

31

Memoria descriptiva
Nivel de ocupacin
09 00 13 00
100%
13 00 15 00
0%
15 00 18 00
100%
Tabla 14. Horario de ocupacin de oficinas y salas de reuniones

De la misma manera que se ha definido las horas de trabajo para los empleados de oficina
y salas de reuniones, se define el horario de la cafetera desde las 8:00 h de la maana hasta
las 20:00 h.
Nivel de ocupacin
08 00 11 00
20%
12 00 14 00
100%
15 00 19 00
20%
Tabla 15. Horario de ocupacin de salas de restauracin

7.1.6

Cargas trmicas por iluminacin y equipos

Se especifica las otras cargas del sistema, se ha nombrado anteriormente las cargas
trmicas internas respecto a las personas, otras cargas internas dentro del sistema son la
iluminacin y los equipos electrnicos y elctricos. Para el estudio y simulacin de un
sistema de climatizacin, ventilacin y acondicionamiento de aire (HVAC) es esencial
definir claramente unas cargas internas de diseo realistas con un horario programado, y
similar al de ocupacin.

Iluminacin
El sistema de ventilacin debe disearse teniendo en cuenta la carga trmica interna
causada por el sistema de iluminacin segn los niveles de iluminacin se determinan unos
valores tpicos de diseo que se dan en la tabla siguiente de la normativa UNE EN 13779,
estos son valores promediados en funcin del la superficie del recinto.
Tipo de uso

Nivel de iluminacin en lux


Intervalo tpico Valor por defecto
Sala de oficina con ventana
300 a 500
400
Sala de oficina sin ventana
400 a 600
500
Aula
300 a 500
400
Restaurante
200 a 300
200
Sala no habitable
50 a 100
50
Tabla 16. Niveles de iluminacin en lux (Fuente: UNE EN 13779)

Los valores tpicos para los sistemas de alta eficiencia energtica se dan en la tabla
siguiente de la misma norma UNE EN 13779.
Potencia de iluminacin especifica en W/m2
Intervalo tpico
Valor por defecto
50
2.5 a 3.2
3
100
3.5 a 4.5
4
200
5.5 a 7
6
300
7.5 a 7.5
8
400
9.0 a12.5
10
500
11.0 a 15.0
12
Tabla 17. Niveles de alta eficiencia energtica en iluminacin (Fuente: UNE EN 13779)
Nivel de iluminacin en lux

32

Memoria descriptiva

Por lo tanto la solucin adoptada ser un valor de 400 lux para las oficinas, que por su
equivalencia en la tabla anterior su valor por defecto ser de 10 W/m2. Para las salas de
restauracin, se escoger un valor de 6 W/m2, a partir de la tabla anteriores.

Equipos
En los edificios de oficinas, la carga de calor debida al equipamiento est habitualmente
comprendida entre 25 W/persona y 200 W/persona, promediado durante el periodo de
utilizacin. Un valor por defecto para los edificios de oficinas sera de 100 W/persona
durante 8 horas al da.

7.1.7

Zona ocupada

Los requisitos ambientales de los interiores del edifico deben satisfacerse en la zona
ocupada. Esto significa que todas las medidas que tratan los criterios de confort deben
relacionarse con la zona. Cabe recordar que el criterio de confort no est garantizado mas
all de la zona ocupada.
Las dimensiones de la zona ocupada se dan en la tabla siguiente de la normativa para
ventilacin de edificios no residenciales y se indican en la siguiente figura:

Figura 3. Zona ocupada (Fuente: UNE EN 13779)

La siguiente tabla hace referencia al valor que se ha de coger por defecto dependiendo de
la distancia desde la superficie interior.
Distancia desde la superficie interior
Intervalo tipo (m) Valor por defecto (m)
A Suelos (lmite inferior)
0.00 a 0.20
0.05
B Suelos (lmite superior)
1.30 a 2.00
1.80
C Ventanas y puertas exteriores
0.50 a 1.50
1.00
D Aparatos de sistemas de ventilacin y climatizacin
0.50 a 1.50
1.00
E Paredes exteriores
0.15 a 0.75
0.50
F Paredes interiores
0.15 a 0.75
0.50
G Puertas, zonas de transito, etc.
Acuerdo especial

Tabla 18. Distancias de la zona ocupada (Fuente: UNE EN 13779)

7.1.8

Temperatura del aire y temperatura operativa

La temperatura del aire influye de la manera puede subir o bajar la temperatura interior o
operativa del edifico dependiendo de su temperatura.

33

Memoria descriptiva

Dentro del campo de aplicacin de este documento se tienen bajas velocidades (< 0.2 m/s)
y pequeas diferencias entre la temperatura del aire y la temperatura radiante media en el
recinto (< 4 C). Por lo tanto la temperatura operativa en el recinto se define como:

o =

a + r
2

(1)

Donde,
o, es la temperatura operativa en la zona considerada recinto.
a, es la temperatura del aire en el recinto.
r, es la temperatura radiante media de todas las superficies (paredes, suelos, techos,
ventanas, radiadores, etc.) con respecto a la situacin considerada en el recinto.
Considerando los valores por defecto para los edificios de oficinas, la temperatura
operativa ptima es de 26 C en condiciones estivales y de 21 C en condiciones invernales
obtenidos de la tabla siguiente, donde se especifican los valores de diseo. Es decir el
sistema debe basarse en los valores dados en la siguiente tabla:
Situacin
Intervalo tpico (C) Valores por defecto para el diseo (C)
Periodo invernal con calefaccin
o = 19 a 24
o = 21
Periodo estival con refrigeracin
o = 23 a 26
o = 26
Tabla 19. Intervalos de temperatura operativa (Fuente: UNE EN 13779)

7.1.9

Velocidad del aire y molestia por corriente de aire

La velocidad del aire influye de manera que por la ventilacin natural puede verse ms
afectada la temperatura interior. La velocidad media admisible del aire depende de RITE:
v=

t
0.07 m / s
100

(2)

Donde,
I. v, velocidad admisible del aire en m/s.
II. t, temperatura operativa.
La molestia de aire se describe en la Norma EN ISO 7730 y en el Informe CEN CR 1752 y
se determina segn la siguiente expresin:

DR = (34 a ) (v 0.05)

0.62

(0.37 v TU + 3.14)

(3)

Donde,
I. DR, es la molestia por corriente de aire en %
II. a, es la temperatura del aire en el recinto en C (21 C 26 C)
III. v, velocidad admisible del aire en m/s

34

Memoria descriptiva

IV. TU, es la intensidad local de turbulencia en % (30% a 60% con distribucin de flujo
de aire mezclado)
Sin un acuerdo especifico, en base a los principios anteriormente mencionados, las
temperaturas de diseo del aire de acuerdo con el apartado anterior de la definicin de la
temperatura operativa, una molestia por corriente del 10% y asumiendo una intensidad de
turbulencias del 40% se puede utilizar los valores dados en la siguiente tabla:
Temperatura local del aire (C) Intervalo tpico Valores por defecto (DR = 15%)
a = 20
0.10 a 0.16
v 0.13
a = 21
0.10 a 0.17
v 0.14
a = 22
0.11 a 0.18
v 0.15
a = 24
0.13 a 0.21
v 0.17
a = 26
0.15 a 0.25
v 0.2
Tabla 20. Velocidad del aire (Fuente: RITE)

7.1.10 Calidad del aire interior


Para determinar la calidad del aire del edificio se tendr en cuenta el nuevo RITE y la
norma UNE EN 13779.
De acuerdo con el Reglamento de Instalaciones Trmicas de los Edificios (RITE) y
haciendo referencia a su IT 1.1.4.2.3 Caudal mnimo del aire exterior de ventilacin, hay
cinco mtodos para alcanzar dicha calidad de aire. Como en el edificio existe la ocupacin
humana permanente se debe acudir al mtodo indirecto de caudal de aire exterior por
persona.
En dicho mtodo se emplearan los valores de la tabla 1.4.2.1 de RITE.
Categora dm3/s por persona
IDA 1
20
IDA 2
12.5
IDA 3
8
IDA 4
5
Tabla 21. Caudal de aire por persona (Fuente: RITE)

Analizando ms en profundidad se define el IDA para cada local:


I. IDA 1, aire de optima calidad para hospitales, clnicas, laboratorios y guarderas.
II. IDA 2, aire de buena calidad para oficinas, residencias, hoteles, salas de lectura,
museos, aulas de enseanza, piscinas, etc.
III. IDA 3, aire de calidad media para edificios comerciales, cines, teatros, salones de
actos, habitaciones de hoteles, restaurantes, cafeteras, bares, salas de fiesta,
gimnasios, salas de ordenadores, etc.
IV. IDA 4, aire de baja calidad.
Por lo tanto, se establecer un caudal de ventilacin para el recinto de IDA 2. Conocidos
los clculos realizados para determinar el aforo de cada recinto y sabiendo el uso de cada
local, se especifica en la tabla siguiente la ventilacin en m3/h:

35

Memoria descriptiva

Planta 0 INEF Lleida


Nombre local

Tipo de uso

Ventilacin (m3/h)

Nmero de personas

Juntas
Honor
Direccin
Secretaria Direccin
Subsecretaria Actividades
y Servicios
Subdireccin de Estudios
Subdireccin Postgrado
Gerencia
Direccin OA
Cafetera Restaurante
Sala Audiovisuales
Comedor
Servicio de Reprografia
Sala de Espera
Secretaria admin.
Gestin

Reuniones
Reuniones
Of. pequea
Of. pequea
Of. pequea

1170
1485
135
135
135

26
33
3
3
3

Of. pequea
Of. pequea
Of. pequea
Of. pequea
Restaurantes
Reuniones
Restaurantes
Of. pequea
Of. pequea
Of. pequea
Of. pequea

135
90
90
135
1392
1755
192
225
409
135
990

3
2
2
3
173
39
24
5
9
3
22

Tabla 22. Caudal de ventilacin edificio oficinas planta 0 INEF Lleida

De igual forma que en la planta 0, la ventilacin para la planta 1, la cual todos sus locales
son oficinas pequeas, y por ese motivo se omite la columna de tipo de uso del local.

Nombre local
Despacho 101
Despacho 102
Despacho 103 104
Despacho 105
Despacho 106
Despacho 107
Despacho 108
Despacho 109
Despacho 110
Despacho 111
Despacho 112
Despacho 113
Despacho 115
Despacho 116
Despacho 117
Despacho 118
Despacho 119
Despacho 120
Despacho 121
Despacho 122
Despacho 123
Despacho 124

Planta 1 INEF Lleida


Ventilacin (m3/h)
Nmero de personas
90
2
90
2
135
3
90
2
90
2
90
2
90
2
135
3
135
3
90
2
90
2
135
3
90
2
90
2
225
5
135
3
90
2
225
5
90
2
90
2
90
2
90
2

Tabla 23. Caudal de ventilacin edificio oficinas planta 0 INEF Lleida

36

Memoria descriptiva

7.1.11 Estudio de mejoras. Acristalamiento doble


A continuacin se explica con detalle en qu consiste las mejoras que se realizarn en el
edificio de cara a obtener una mejora energtica de manera terica, es decir, el propsito
que se tiene con dichas mejoras en la simulacin del edificio. Las mejoras son las
siguientes:
I. Acristalamiento doble
II. Voladizo
El nuevo RITE, establece las exigencias de eficiencia energtica y seguridad que deben
cumplir las instalaciones trmicas en los edificios para atender la demanda de bienestar e
higiene de las personas tanto en las fases de diseo, dimensionado y montaje, como
durante su uso y mantenimiento, un elemento para conseguir dicho confort es el
acristalamiento doble.
El doble acristalamiento est formado por dos o ms lunas separadas entre s por cmaras
de aire deshidratado resultando un eficaz aislante, proporcionando confort trmico pues
elimina el efecto pared fra en zonas cercanas al cristal.
Tiene la gran ventaja de no condensar, lo que ofrece mejor esttica y fcil mantenimiento.
La separacin entre lunas se define por un perfil metlico entre ellas, en cuyo interior se
introduce un producto desecante y se asegura la estanqueidad con doble sellado
perimetral; el primero a base de butilo y el segundo con un polisulfuro. Para claraboyas se
utiliza el sellado con siliconas. Se fabrica con doble y triple acristalamiento. Puede
fabricarse con mayor nmero de cmaras, segn el grado de aislamiento y el destino.
El sistema de doble acristalamiento es una solucin eficaz porque reduce el flujo de
energa lumnica, trmica y sonora al atravesar el acristalamiento, as disminuye los
coeficientes de transmisin energtica y de ruidos.
Donde,
I. Tamiz molecular como desecante.
II. Cristal de 4 mm.
III. Cmara de aire sellada.
IV. Esquina de nylon.
V. Separador de aluminio.
VI. Tamiz molecular como desecante.
VII. Sellador de poliisobutileno.
Figura 4. Capas del acristalamiento doble

El desecante es una sustancia que se usa para eliminar humedad del aire o de alguna otra
sustancia, como combustibles orgnicos.

37

Memoria descriptiva

El poliisobutileno es un caucho sinttico, o elastmero. Es especial porque es el nico


caucho impermeable a los gases, es decir, es el nico caucho que puede mantener el aire
por largos perodos.
El doble acristalamiento tiene las siguientes aplicaciones:
I. Ofrece iluminacin y visibilidad con confort. Permite resolver acristalamientos con
mejores condiciones trmicas, acsticas y ahorro energtico.
II. Posee control solar, regulando los aportes energticos excesivos sin renunciar al
aislamiento trmico en pocas invernales o de menor ndice solar, siendo posible el
uso de vidrios de baja emisividad.
III. Disminuye las consecuencias en accidentes por el empleo de vidrios de seguridad.
A continuacin se explica cmo seleccionar los vidrios para alcanzar un buen control
trmico.

Seleccin de los vidrios


Para seleccionar los vidrios se debe analizar los distintos tipos de cargas trmicas que
actan a travs de las ventanas:
I. Diferencias de temperaturas
La diferencia de temperaturas entre ambos lados de la ventana genera un flujo de calor
desde el lado de mayor temperatura hacia el lado de menor temperatura. La magnitud de
este flujo de calor se mide a travs del Coeficiente de Transmisin de calor (K). Un alto
valor K implica una alta transferencia de calor; valores bajos de K significa una alta
capacidad de aislamiento trmico.
II. Radiacin solar infrarroja
La radiacin infrarroja (radiacin de onda corta) representa el 50 por ciento de la radiacin
solar total, y el vidrio es prcticamente transparente a ella: la deja pasar en su totalidad. De
aqu la importancia de regular el ingreso de radiacin solar pues puede resultar una carga
trmica excesiva para el confort de la vivienda.
El coeficiente de sombra (C.S.) mide la mayor o menor capacidad de un vidrio para limitar
el ingreso de radiacin solar. A mayor CS ingresar mayor radiacin; a menor CS el vidrio
es ms refractivo a los rayos IR impidiendo su ingreso al interior de la vivienda. Esto
permite seleccionar el vidrio ms adecuado para cada necesidad.
Pero junto con el aumento de la capacidad reflectante (menor CS) se observa que
disminuye el porcentaje de luz visible. Este aspecto debe ser tenido en cuenta al
seleccionar vidrios de Control Solar.
III. Radiacin de los cuerpos calientes.
Los cuerpos calientes en el interior de las viviendas (paredes, muebles, personas, etc.)
emiten radiacin. Esta radiacin (calor) es de onda larga y escapar al exterior a travs de
los vidrios implicando un mayor consumo de energa de calefaccin para mantener la
temperatura en la vivienda. El vidrio Bajo Emisivo (o Low-e) est diseado para reflejar la
38

Memoria descriptiva

radiacin de onda larga hacia el interior de la habitacin. De este modo se impide la


prdida del calor almacenado, disminuye el valor K y, por lo tanto, los gastos de
calefaccin.

Seleccin del ancho de cmara


Debido a que la capacidad de aislamiento trmico del DVH est vinculada al volumen de
la cmara de aire, a mayor espesor de cmara se obtendr mejor aislacin. El valor K
decrece a medida que aumenta el espesor de la cmara, hasta alcanzar un valor mnimo a
partir del cual K aumenta. Esto se debe a las corrientes convectivas que se forman en el
interior de la cmara cuando el volumen de aire es grande. Estas corrientes convectivas
aceleran la transmisin de calor.
Explicadas las ventajas y la justificacin de porque su uso en la construccin, se pretende
modificar los acristalamientos de todo el edificio por otros de doble cristal con cmara de
aire. El acristalamiento del edificio de la INEFC de Lleida est constituido totalmente por
un acristalamiento sencillo de 4 mm. de espesor.
Para realizar la estimacin del ahorro energtico anual de calefaccin y refrigeracin se
aplica nuevamente el programa de clculo EnergyPlus en el modelo tridimensional
anteriormente. Los clculos se realizan substituyendo cada ventana actual por una ventana
de doble cristal de 4 mm. de cristal, 6 mm. de cmara de aire y 4 mm. de cristal. Con este
cambio se espera reducir el escape de energa a travs del intercambio de calor en las
ventanas, ya que un cristal simple aparte de tener un menor aislamiento sonoro tiene
tambin un menor aislamiento trmico.
Para realizar dicha modificacin, se toman los datos del Cdigo Tcnico de la Edificacin,
en su seccin de Vidrios, donde aparecen una gran cantidad de ejemplos. A continuacin se
transcribe los valores que posee el acristalado simple el cual es el original de INEFC
Lleida, y posteriormente se escriben las caractersticas de un acristalamiento doble aislante.
Acristalamientos
Composicin
Solar Factor g U Factor (W/m2K)
Tipo
Espesor (mm)
Vidrio sencillo
4
0.8 - 0.85
5.7
6
5.7
Unidades de vidrio aislante 4 6 (46)
0.7 - 0.75
3.3
4 9 (4...6)
3
4 12 (4...6)
2.8
Tabla 24. Caractersticas acristalamiento doble (Fuente: CTE)

Los valores de transmitncia han sido calculados segn la metodologa de la norma UNE
EN 673/A2:2003 Vidrio en la construccin. Determinacin del coeficiente de transmisin
trmica (valor U). Mtodo de clculo.
Los nmeros se separaran por guiones formando tres conjuntos indican el espesor de las
unidades de vidrio aislante o de doble acristalamiento. El primero se refiere al espesor del
vidrio, el segundo se refiere al espesor de la cmara y el ltimo conjunto de nmeros, que
figura entre parntesis, indica el rango de espesores de vidrio considerados.

39

Memoria descriptiva

7.1.12 Estudio de mejoras. Voladizo


Un simple voladizo puede disminuir la temperatura del recinto de 2 a 5 C en funcin de su
color y de la hora en la que ha sido abierto. As pues, el voladizo exterior se presenta como
una verdadera ventaja medioambiental y como una solucin para el futuro ahorro de
energa.
La tecnologa del voladizo es sencilla, un voladizo deja pasar la radiacin solar en inverno,
ya que el sol se encuentra mucho ms bajo que en los meses de verano. En los meses de
esto el sol est mucho ms alto, los rayos caen mucho ms perpendiculares al suelo y el
voladizo impide que entren.
Desde el ao 2002 el Parlamento Europeo considera la proteccin solar como una solucin
para reducir los gastos energticos de los edificios. La instalacin de un voladizo exterior
permite, en efecto, disminuir el consumo energtico y el efecto invernadero (de acuerdo
con el protocolo de Kioto).
En efecto, antes de poner en funcionamiento su climatizador, es preferible que abra el
voladizo para disminuir algunos grados el calor ambiental. Al final, este simple gesto
puede reducir del 30 a 50% el consumo elctrico de una climatizacin. Si su voladizo
tambin est equipado con un automatismo, puede regular la temperatura interior durante
el verano de este modo, sin climatizacin durante gran parte del da.
En paralelo, los conceptos arquitectnicos de estos ltimos aos (edificio pasivo, casa
positiva), utilizan mucho los ventanales para sacarle todo el partido al calor y a la luz
natural. Solamente deben canalizarse para suministrar los grados y los Lux necesarios en el
edificio. Los voladizos exteriores intervienen pues en esta fase para optimizar el impacto
de la radiacin solar y limitar as el uso de climatizacin o de iluminacin artificial.
La tensin mxima sobre un voladizo es acotada por:

PL
W min

(4)

Donde,
I. P, es la carga mxima sobre el voladizo.
II. L, es la longitud del voladizo.
III. Wmin, es el momento de la seccin menos resistente.
Si adems el voladizo tiene una seccin transversal constante y se comporta
elsticamente el desplazamiento vertical mximo se acota como:

PL3
3EI min

(5)

Donde,
I. P, es la carga mxima sobre el voladizo.
II. L, es la longitud del voladizo.

40

Memoria descriptiva

III. E, es el mdulo de Young del material del voladizo.


IV. Imin, es el segundo momento de rea de la seccin menos resistente.
Se justifica la mejora de voladizo porque en el estudio del edificio se observa que la cara
sur del recinto contiene un gran nmero de acristalamiento y ningn elemento para un
sombreado de las ventanas, de esta forma se conseguirn todas las ventajas comentadas
anteriormente.
Un esquema del uso del voladizo sera el siguiente:

Figura 5. Edificio con voladizo

En la imagen se observa como gracias al voladizo los rayos de sol no entran a travs de la
ventana, dichos rayos son absorbidos por el voladizo, proyectando una sombra en la
ventana. Esta operacin se realizar en toda la fachada sur del complejo, y como se ha
comentado anteriormente se conseguir reducir el aporte de cargas durante los meses
estivales.
En el siguiente apartado, se selecciona el tipo de climatizacin que se realizara con el
objetivo de poder cumplir el RITE con precisin, como son por ejemplo el tipo de sistema
y el tipo de conductos.

7.1.13 Exigencia de recuperacin de energa


7.1.13.1 Recuperacin del aire exterior
En los sistemas de climatizacin de los edificios en los que el caudal de aire expulsado al
exterior, se recuperar la energa del aire expulsado.
Las eficiencias mnimas en calor sensible sobre el aire exterior (%) y las prdidas de
presin mximas (Pa) en funcin del caudal de aire exterior (m3/s) y de las horas anuales
de funcionamiento del sistema deben ser como mnimo las indicadas en la tabla 2.4.5.1 de
RITE.
Horas anuales de
funcionamiento
2000
> 2000 4000
> 4000 6000
> 6000

Caudal de aire exterior (m3/s)


> 0,5 1,5
> 1,5 3,0
> 3,0 6,0
> 6,0 12
%
Pa
%
Pa
%
Pa
%
Pa
40
100
44
120
47
140
55
160
44
140
47
160
52
180
58
200
47
160
50
180
55
200
64
220
50
180
55
200
60
220
70
240
Tabla 25. Eficiencia de la recuperacin (Fuente: RITE)

> 12
%
60
64
70
75

Pa
180
220
240
260

41

Memoria descriptiva

7.1.14 Zonificacin
El diseo de la instalacin ha sido realizado teniendo en cuenta la zonificacin, para
obtener un elevado bienestar y ahorro de energa. Los sistemas se han dividido en
subsistemas, considerando los espacios interiores y su orientacin, as como su uso,
ocupacin y horario de funcionamiento.

7.1.15 Exigencia de limitacin de la utilizacin de energa


Se enumeran los puntos para justificar el cumplimiento de esta exigencia:
I. El sistema de calefaccin empleado no es un sistema centralizado que utilice la
energa elctrica por "efecto Joule".
II. No se ha climatizado ninguno de los recintos no habitables incluidos en el proyecto.
III. No se realizan procesos sucesivos de enfriamiento y calentamiento, ni se produce la
interaccionan de dos fluidos con temperatura de efectos opuestos.
IV. No se contempla en el proyecto el empleo de ningn combustible slido de origen
fsil en las instalaciones trmicas.

7.1.16 Eficiencia energtica en las redes de tuberas y conductos


7.1.16.1 Eficiencia energtica de los equipos para el transporte de
fluidos
Se describe a continuacin la potencia especfica de los equipos de propulsin de fluidos y
sus valores lmite segn la instruccin tcnica I.T. 1.2.4.2.5 de RITE. La seleccin de los
equipos de propulsin de los fluidos portadores se realizar de forma que su rendimiento
sea mximo en las condiciones calculadas de funcionamiento. Para sistemas de caudal
variable, el requisito anterior deber ser cumplido en las condiciones medias de
funcionamiento a lo largo de una temporada.
Se indicar la categora a la que pertenece cada sistema, considerando el ventilador de
impulsin y el de retorno, de acuerdo con la siguiente clasificacin:
I. SFP 1 y SFP 2 para sistemas de ventilacin y de extraccin.
II. SFP 3 y SFP 4 para sistemas de climatizacin, dependiendo de su complejidad.
Para los ventiladores, la potencia especfica absorbida por cada ventilador de un sistema de
climatizacin, ser la indicada en la tabla 2.4.2.7 de RITE.
Categora Potencia especifica W/(m3/s)
SFP 1
Wesp 500
SFP 2
500 < Wesp 750
SFP 3
750 < Wesp 1250
SFP 4
1250 < Wesp 2000
SFP 5
Wesp > 2000
Tabla 26. Potencia especifica de ventiladores (Fuente: RITE)

42

Memoria descriptiva

7.1.17 Control
7.1.17.1 Control de las instalaciones de climatizacin
Todas las instalaciones trmicas estarn dotadas de los sistemas de control automtico
necesarios para que se puedan mantener en los locales las condiciones de diseo previstas,
ajustando los consumos de energa a las variaciones de la carga trmica.
Los sistemas formados por diferentes subsistemas deben disponer de los dispositivos
necesarios para dejar fuera de servicio cada uno de estos en funcin del rgimen de
ocupacin, sin que se vea afectado el resto de las instalaciones.
Las vlvulas de control automtico se seleccionarn de manera que, al caudal mximo de
proyecto y con la vlvula abierta, la prdida de presin que se producir en la vlvula est
comprendida entre 0,6 y 1,3 veces la prdida del elemento controlado.
La variacin de la temperatura del agua en funcin de las condiciones exteriores se har en
los circuitos secundarios de los generadores de calor de tipo estndar y en el mismo
generador en el caso de generadores de baja temperatura y de condensacin, hasta el lmite
fijado por el fabricante.
La temperatura del fluido refrigerado a la salida de una central frigorfica de produccin
instantnea se mantendr constante, cualquiera que sea la demanda e independientemente
de las condiciones exteriores, salvo situaciones que deben estar justificadas.
El control de la secuencia de funcionamiento de los generadores de calor o fro se har
siguiendo estos criterios:
Cuando la eficiencia del generador disminuye al disminuir la demanda, los generadores
trabajarn en secuencia. Al disminuir la demanda se modular la potencia entregada por
cada generador (con continuidad o por escalones) hasta alcanzar el valor mnimo permitido
y parar una mquina; a continuacin, se actuar de la misma manera sobre los otros
generadores. Al aumentar la demanda se actuar de forma inversa.
Cuando la eficiencia del generador aumente al disminuir la demanda, los generadores se
mantendrn funcionando en paralelo. Al disminuir la demanda se modular la potencia
entregada por los generadores (con continuidad o por escalones) hasta alcanzar la
eficiencia mxima; a continuacin, se modular la potencia de un generador hasta llegar a
su parada y se actuar de la misma manera sobre los otros generadores. Al aumentar la
demanda se actuar de forma inversa.
Los ventiladores de ms de 5 m3/s llevarn incorporado un dispositivo indirecto para la
medicin y el control del caudal de aire.

7.1.17.2 Control de las condiciones termo-higromtricas


Los sistemas de climatizacin, centralizados o individuales, se disearn para controlar el
ambiente interior desde el punto de vista termo-higromtrico. De acuerdo con la capacidad
del sistema de climatizacin para controlar la temperatura y la humedad relativa de los

43

Memoria descriptiva

locales, los sistemas de control de las condiciones termo-higromtricas se clasificarn, en


las categoras indicadas de la tabla 2.4.3.1
Categora
THMC 0
THMC 1
THMC 2
THMC 3
THMC 4
THMC 5

Ventilacin Calentamiento
Refrigeracin Humidificacin Deshumidificacin
x

x
x

x
x

x
x
x

(x)
x
x
x
x
(x)
x
x
x
x
x
Tabla 27. Control de las condiciones termo-hidromtricas (Fuente: RITE)

THMC1: Variacin de la temperatura del fluido portador (agua-aire) en funcin de la


temperatura exterior y/o control de la temperatura del ambiente por zona trmica.
THMC2: Como THMC1, ms el control de la humedad relativa media o la del local ms
representativo.
THMC3: Como THMC1, ms variacin de la temperatura del fluido portador fro en
funcin de la temperatura exterior y/o control de la temperatura del ambiente por zona
trmica.
THMC4: Como THMC3, ms control de la humedad relativa media o la del recinto ms
representativo.
THMC5: Como THMC3, ms control de la humedad relativa en locales.

7.1.17.3 Control de la calidad de aire interior en las instalaciones de


climatizacin
Los sistemas de ventilacin y climatizacin, centralizados o individuales, se disearn para
controlar el ambiente interior, desde el punto de vista de la calidad de aire interior. La
calidad del aire interior ser controlada por uno de los mtodos enumerados en la tabla
2.4.3.2
Categora
IDAC1
IDAC2
IDAC3
IDAC4
IDAC5
IDAC6

Tipo
Control manual
Control por
tiempo
Control por
presencia
Control por
ocupacin

Descripcin
El sistema funciona continuamente.
El sistema funciona manualmente, controlado por un interruptor.
El sistema funciona de acuerdo a un determinado horario.
El sistema funciona por una seal de presencia (encendido de luces,
infrarrojos, etc.).
El sistema funciona dependiendo del nmero de personas presentes.

El sistema esta controlado por sensores que miden parmetros de calidad


del aire interior (CO2 o VOCs).
Tabla 28. Control de la calidad del aire interior (Fuente: RITE)

Control directo

El mtodo IDAC1 ser el utilizado con carcter general.


Los mtodos IDAC2, IDAC3 e IDAC4 se emplearn en locales no diseados para
ocupacin humana permanente.
Los mtodos IDAC5 e IDAC6 se emplearn para locales de gran ocupacin, como
teatros, cines, salones de actos, recintos para el deporte y similares.

44

Memoria descriptiva

7.2

Estudio de viabilidad energtica con EnergyPlus

7.2.1

Diseo del modelo con Google SketchUp y OpenStudio

Una vez se han determinado los parmetros relacionados con las cargas trmicas de cada
una de las salas del edificio se procede a la construccin del edificio en 3D mediante el
programa de dibujo Google SketchUp.

7.2.1.1

Introduccin

Desarrollado para las etapas conceptuales del diseo, SketchUp es un software de 3D fcil
de utilizar y extremadamente potente. Este software galardonado combina un conjunto de
herramientas sencillas y potentes que simplifican el diseo 3D en el equipo informtico.
OpenStudio es un plugin para el programa Google SketchUp 3D de dibujo. El plugin
facilita la creacin y edita la geometra de la construccin en los archivos de entrada
EnergyPlus. Aade una serie de herramientas de gran uso para el diseo del edificio en 3D.
El plugin tambin te permite lanzar simulaciones EnergyPlus y ver los resultados sin dejar
SketchUp.

7.2.1.2

Interfaz de Google SketchUp

Esta seccin est dedicada a la interfaz de Google SketchUp donde se incluyen los mens,
las barras de herramientas, los cuadros de dilogo y el rea de dibujo. El objetivo de este
apartado es dar a conocer el funcionamiento completo del programa de dibujo y llegar a
conocer todas sus herramientas y su uso.
Primero de todo se abre el programa una vez
descargado e instalado de la pgina Web anteriormente
nombrada. Aparecer la pantalla siguiente donde se
clica en Start using SketchUp.

Figura 6. Ventana inicial de Google SketchUp

45

Memoria descriptiva

Automticamente el programa se prepara para ser iniciado y poder trabajar con l,


apareciendo la siguiente pantalla.

Figura 7. Pantalla lista para dibujar de Google SketchUp

Se puede ver que aparecen todas las funciones que van a ser utilizadas, distribuidas en dos
barras de herramientas, la horizontal y la vertical. En el centro de la pantalla aparece
Shank, el cual se puede utilizarlo como referencia, aunque como se observa aparecen tres
ejes diferenciados por colores que indican una orientacin en concreto. SketchUp utiliza un
sistema de coordenadas 3D en el que los puntos se identifican en el espacio mediante su
posicin en tres niveles de suelo (cota zero): valores X, Y y Z positivos o negativos (por
encima o por debajo del suelo).
En SketchUp, el valor X positivo o negativo se representa mediante lneas rojas continuas o
punteadas, respectivamente; Y positivo o negativo se representa respectivamente mediante
lneas de eje verdes continuas o punteadas; y Z positivo o negativo (por encima o por
debajo del suelo) se representa mediante lneas azules continuas o punteadas. El plano en
el que descansan las lneas de eje rojas y verdes se denomina plano de suelo.
Por ltimo, el trmino origen se emplea para definir el lugar donde se inician todas las
lneas de eje. La imagen siguiente muestra los ejes de dibujo en SketchUp (las lneas se
muestran ms gruesas de lo normal para facilitar la lectura de los ejes). El crculo negro
representa el origen.

Figura 8. Ejes

La interfaz de usuario de SketchUp est diseada para que su uso resulte lo ms sencillo
posible. Los elementos principales de la interfaz de SketchUp son la barra de ttulo, los
mens, la barra de herramientas, el rea de dibujo, la barra de estado y el cuadro de control
de valores (CCV):

46

Memoria descriptiva

I. Barra de ttulo: asignar un nombre al proyecto.


II. Mens: aparecen bajo la barra de ttulo. La mayora de herramientas, comandos y
ajustes de SketchUp estn disponibles en estos mens. Los mens que aparecen de
forma predeterminada son: "Archivo", "Edicin", "Ver", "Cmara", "Dibujar",
"Herramientas", "Ventana" y "Ayuda".
III. Las barras de herramientas: aparecen bajo los mens y en el lado izquierdo de la
aplicacin, contienen un conjunto de herramientas y controles definidos por el
usuario.
IV. rea de dibujo: es el lugar donde se crea el modelo.
V. Barra de estado: rea gris situada en la parte inferior de la pantalla, ver figura.

Figura 9. Barra de estado

Seguidamente se habla con ms detalles de cada una de las pestaas que aparecen en el
Men.
I. Archivo: Contiene opciones relacionadas con los archivos
de modelos de SketchUp, como comandos para crear,
abrir, guardar, imprimir, importar y exportar archivos de
modelos:

Figura 10. Pestaa de archivo

Se pueden ver los mtodos abreviados des de el teclado como para abrir que es Control +
N, por ejemplo, entre otros. El submen "Exportar" se utiliza para acceder a las funciones
de exportacin de SketchUp, muy tiles para compartir el trabajo con otras personas o
exportar dibujos a otros programas. Puedes exportar tu modelo de SketchUp como modelo
3D, grfico 2D, lnea de seccin o animacin.

47

Memoria descriptiva

II. Edicin: ofrece diversas opciones que permiten llevar a


cabo funciones de edicin sobre las geometras de
SketchUp. Estas opciones incluyen elementos para crear
y editar grupos y componentes, funciones relacionadas
con la visibilidad, y los comandos estndar "Cortar",
"Copiar" y "Pegar":

Figura 11. Pestaa de edicin

III. Ver: ofrece opciones que permiten


modificar la visualizacin de las entidades
dentro del modelo. Dichas opciones afectan
a la visualizacin de las entidades.

Figura 12. Pestaa de ver

En el submen "Barras de herramientas" se incluyen todas las barras de herramientas.


Estas barras son: "Primeros pasos", "Conjunto grande de herramientas", "Cmara",
"Auxiliar", Dibujo", "Estilo de cara", "Google", "Modificacin", "Capas", "Principales",
"Secciones", "Sombras", "Estndar", "Vistas" y "Paseo", entre otros.

48

Memoria descriptiva

IV. Cmara: Ofrece opciones para modificar el punto


de vista del modelo.

Figura 13. Pestaa de cmara

V. Dibujo: contiene todas las herramientas de dibujo de SketchUp


y es una alternativa al uso de las barras de herramientas o a los
mtodos abreviados.

Figura 14. Pestaa de dibujo

VI. Herramientas: permite acceder a todas las herramientas de


modificacin de SketchUp. Es uno de los tres modos
disponibles a estas herramientas.

Figura 15. Pestaa de herramientas

49

Memoria descriptiva

VII. Ventana: contiene ajustes y utilidades de gestin de


los modelos. Los ajustes de un modelo son cuadros
de dilogo con parmetros que afectan al modelo,
como las sombras, la visualizacin en pantalla o
informacin sobre el mismo. Los gestores son
cuadros de dilogo que controlan determinados
aspectos del modelo, como las escenas, las capas, los
materiales o los componentes.

Figura 16. Pestaa de ventana

VIII. Plugins: En este caso se tiene el plugin de


OpenStudio:

Figura 17. Pestaa de plugins

IX. Ayuda: contiene artculos de ayuda sobre el producto.


Estos artculos incluyen la gua del usuario online de
SketchUp, una gua de referencia rpida y tutoriales en
vdeo.

Figura 18. Pestaa de ayuda

50

Memoria descriptiva

Una vez nombrados uno a uno todos los desplegables ofrecidos por SketchUp se va a
hablar de la barra de herramientas que es la base de todo programa para su funcionamiento
ms cmo, rpido o eficaz, como se le quiera decir. Estas barras de herramientas se pueden
separar haciendo clic y arrastrando el control de movimiento (lnea final de la parte
superior), se pueden cambiar de tamao arrastrando las esquinas y se pueden volver a
anclar en el margen del rea de dibujo segn prefiera el usuario. Activa o desactiva la
visibilidad de la barra de herramientas con el submen "Ver > Barras de herramientas".
I. Primeros pasos: contiene todas las herramientas y opciones necesarias para que un
nuevo usuario se familiarice con SketchUp. Estas herramientas y opciones son:
herramienta "Seleccionar", herramienta "Lnea", herramienta "Rectngulo",
herramienta "Crculo", herramienta "Arco", "Crear componente", herramienta
"Borrar", herramienta "Medir", herramienta "Pintar", herramienta "Empujar/tirar",
herramienta "Mover", herramienta "Rotar", herramienta "Equidistancia",
herramienta "Orbitar", herramienta "Desplazar", herramienta "Zoom", herramienta
"Ver modelo centrado", botn "Obtener vista actual", botn "Cambiar terreno",
botn "Colocar modelo", botn "Obtener modelos" y botn "Compartir modelo".

Figura 19. Primeros pasos

II. Conjunto grande de herramientas: El conjunto grande de herramientas contiene las


herramientas y opciones ms utilizadas para usuarios con experiencia. Estas
herramientas y opciones son: Herramienta "Seleccionar", "Crear componente",
herramienta "Pintar", herramienta "Borrar", herramienta "Rectngulo", herramienta
"Lnea", herramienta "Crculo", herramienta "Arco", herramienta "Polgono",
herramienta "Mano alzada", herramienta "Mover", herramienta "Empujar/tirar",
herramienta "Rotar", herramienta "Sgueme", herramienta "Escala", herramienta
"Equidistancia", herramienta "Medir", herramienta "Acotacin", herramienta
"Transportador", herramienta "Texto", herramienta "Ejes", herramienta "Texto
3D", herramienta "Orbitar", herramienta "Desplazar", herramienta "Zoom",
herramienta "Ver modelo centrado", "Anterior", "Siguiente", herramienta "Situar
cmara", herramienta "Girar", herramienta "Caminar", herramienta "Plano de
seccin".

Figura 20. Conjunto grande de herramientas

III. Barra de herramientas estndar: La barra de herramientas estndar agrupa diversas


opciones que ayudan en la gestin de archivos y dibujos, adems de mtodos
abreviados para imprimir y opciones de ayuda. Estas opciones son: "Nuevo",
Abrir", "Guardar", "Cortar", "Copiar", "Pegar", "Borrar", "Deshacer", "Rehacer",
"Imprimir" e "Informacin del modelo".

Figura 21. Barra de herramientas estndar

51

Memoria descriptiva

IV. Barra de herramientas principales: Los botones de la barra de herramientas


principales permiten activar la herramienta Seleccionar", "Crear componente", la
herramienta "Pintar" y la herramienta "Borrar".

Figura 22. Barra de herramientas principales

V. Barra de herramientas de dibujo: Los botones de la barra de herramientas de


dibujo permiten activar la herramienta "Rectngulo", la herramienta "Lnea", la
herramienta "Crculo", la herramienta "Arco", la herramienta "Polgono" y la
herramienta "Mano alzada".

Figura 23. Barra de herramientas de dibujo

VI. Barra de herramientas de modificacin: La barra de herramientas de modificacin


contiene utensilios que permiten editar y retocar las geometras. Las herramientas
de esta barra son: "Mover", "Empujar/Tirar", "Rotar", "Sgueme", "Escala" y
"Equidistancia".

Figura 24. Barra de herramientas de modificacin

VII. Barra de herramientas auxiliares: Los botones de la barra de herramientas


auxiliares activan las herramientas "Medir", "Acotaciones", "Transportador",
"Texto", "Ejes" y "Seccin".
Figura 25. Barra de herramientas auxiliares

VIII. Barra de herramientas de cmara: Los botones de la barra de herramientas de


cmara permiten activar las herramientas "Orbitar", "Desplazar", "Zoom",
"Ventana de zoom", "Anterior", "Siguiente", "Anterior" y "Ver modelo centrado".

Figura 26. Barra de herramientas de cmara

IX. Barra de herramientas de paseo: Los botones de la barra de herramientas de paseo


activan las herramientas "Situar cmara", "Caminar", "Girar" y "Seccin".

Figura 27. Barra de herramientas de paseo

X. Barra de herramientas "Estilo de cara": Los botones de la barra de herramientas


"Estilo de cara" permiten activar los estilos de visualizacin de caras de SketchUp
(transparencia de rayos X, alambre, lneas ocultas, slidas, slidas con textura y
monocromas).

Figura 28. Barra de herramientas Estilo de cara

52

Memoria descriptiva

XI. Barra de herramientas de vistas: Los botones de la barra de herramientas de vistas


permiten activar las vistas estndar de SketchUp (isomtrica, planta, frontal,
derecha, posterior e izquierda). La vista desde abajo o se incluye, pero est
disponible en el men "Cmara".

Figura 29. Barra de herramientas de vistas

XII. Barra de herramientas de sombras: La barra de herramientas de sombras se utiliza


para controlar las sombras. Sus botones permiten abrir el cuadro de dilogo
"Ajustes de sombras" (primer icono de la izquierda) y activar/desactivar las
sombras (segundo icono). Contiene tambin reguladores para controlar los ajustes
relacionados con la poca del ao (barra de la izquierda) y la hora del da (barra de
la derecha).

Figura 30. Barra de herramientas de sombra

XIII. Barra de herramientas de seccin: La barra de herramientas de seccin permite


ejecutar fcilmente operaciones de seccin habituales. Esta barra de herramientas
incluye controles para activar o desactivar el efecto de corte de seccin y la
visualizacin de los planos de seccin.
Figura 31. Barra de herramientas de seccin

XIV. Barra Google: Los botones de la barra Google se utilizan para funciones de
interaccin entre SketchUp y otros productos de Google. La barra de herramientas
incluye los botones "Obtener vista actual", "Cambiar terreno", "Colocar modelo",
"Obtener modelos" y "Compartir modelo".

Figura 32. Barra Google

SketchUp incorpora un mecanismo de anlisis geomtrico (el motor de inferencias) que


permite trabajar en un espacio 3D utilizando una pantalla y un dispositivo de entrada 2D.
Este mecanismo ayuda a dibujar con una gran precisin, infiriendo puntos a partir de otros
puntos y ofreciendo indicaciones visuales mientras se trabaja. El motor de inferencias
utiliza notas de ayuda que aparecen automticamente cuando se trabaja en el modelo para
identificar puntos significativos o condiciones geomtricas. Estas indicaciones hacen que
combinaciones de inferencias complejas resulten claras mientras se dibuja. El motor de
inferencias utiliza, adems, colores especficos para indicar el tipo de inferencia, como se
describe a continuacin.
Existen tres tipos principales de inferencia: de puntos, de lneas y de planos:
I. De puntos: Se basan en un punto exacto del cursor en el modelo:

53

Memoria descriptiva

a. Punto final: la inferencia verde de punto final identifica el extremo de una entidad
de lnea o una entidad de arco.
b. Punto medio: la inferencia cian de punto medio indica el punto medio de una lnea
o arista.
c. Interseccin: la inferencia negra de interseccin indica el punto exacto de
interseccin de una lnea con otra o con una cara.
d. En la cara: la inferencia azul identifica el punto situado sobre una entidad de cara.
e. En la arista: la inferencia roja en la arista identifica un punto situado en una arista.
f. Equidistante en la arista: la inferencia Equidistante en la arista seala un punto
equidistante cuando una lnea magenta aparece entre dos aristas conectadas.
g. Semicircunferencia: la inferencia se semicircunferencia aparece cuando se dibuja
un arco para indicar el punto en el que se forma la circunferencia exacta.

Figura 33. Tipos de puntos

II. De lneas: Se ajustan siguiendo lneas o direcciones en el espacio. Adems de las


notas de ayuda, este tipo de inferencias muestra a veces lneas discontinuas
temporales mientras se est dibujando.

Figura 34. Tipos de lnea

a. En el eje: indica la alineacin con uno de los ejes de dibujo. La lnea continua se
dibuja en el color asociado al eje correspondido (rojo, verde o azul).
b. Desde el punto: indica una alineacin desde un punto siguiendo las direcciones de
los ejes de dibujo. Tambin se dibuja en el color asociado al eje correspondido.
c. Perpendicular: la lnea
perpendicular a un eje.

perpendicular

magenta

indica

una

alineacin

d. Paralela: la lnea paralela magenta indica una alineacin en paralelo a una arista.
54

Memoria descriptiva

e. Tangente en el vrtice: cuando se dibuja desde el punto final de una entidad de


arco utilizando la herramienta Arco.

III. De planos: Se ajusta a un plano en el espacio.


h. Planos de dibujo: SketchUp se ajusta a los planos definidos por los ejes de dibujo
y por la vista seleccionada, cuando no puede ajustarse a la geometra del rea de
dibujo. Por ejemplo, SketchUp dibujar sobre el plano del suelo si ste es el punto
de vista.
i. En la cara: la interferencia azul en la cara identifica un punto situado en una cara.
Aunque inicialmente es una inferencia de puntos, la opcin En la cara tambin
puede emplearse como una alineacin de plano utilizando el bloqueo de
inferencias.

7.2.1.3

Funcionamiento

Una vez nombrados todos los elementos que componen la interfaz del programa se pasa a
explicar los pasos para la realizacin de un recinto.

7.2.1.4

Configuracin inicial y ejes de coordenadas

Los ejes de dibujo se pueden manipular (mover, girar, ocultar) mediante el men
contextual correspondiente. Para mover los ejes de dibujo hay que seguir los pasos
siguientes.
I. Abre el men contextual de los ejes de dibujo y selecciona la opcin "Situar". El
cursor se transformar en una serie de ejes.
II. Mueve el cursor hasta el punto del modelo que quieras definir como origen de las
coordenadas. Al moverte por el modelo, observars que los ejes se ajustan a las
alineaciones y los puntos inferidos.
III. Haz clic para aceptar el origen de las coordenadas.
IV. Aleja el cursor del origen, arrastrndolo, para definir la alineacin del eje rojo.
Sigue las notas de ayuda para asegurarte de que la alineacin sea precisa.
V. Haz clic para aceptar la alineacin.
VI. Aleja el cursor del origen para definir la alineacin del eje verde. Sigue nuevamente
las notas de inferencia para asegurarte de que la alineacin sea precisa.
Una vez entendido el sentido de los ejes con el cada color correspondido con la anchura, la
altura y la profundidad correspondiente, se procede a indicar las unidades.
Para ajustar las unidades de medida del proyecto, nos dirigimos al men Window (ventana)
y se selecciona el panel Model Info. A continuacin se selecciona la ltima opcin de la
lista: Units y se ajusta a como se desea. En este caso se usa esta configuracin:

55

Memoria descriptiva

Figura 35. Pantalla para seleccionar las unidades

7.2.1.5

Herramientas para la creacin del modelo

Conjunto grande
Para explicar el uso de las herramientas de Google SketchUp se realiza un recinto del
proyecto de 2x2x2 metros siguiendo los siguientes pasos.
I. Se selecciona la herramienta dibujar rectngulo.

Figura 36. Icono de rectngulo

II. Se hace clic en el origen de coordenadas (donde cruzan los 3 ejes, punto amarillo).

Figura 37. Origen de coordenadas

III. Una vez se hace clic en el origen de coordenadas, se pulsa un 2, seguido de


un punto y coma (Shift + [coma]) y posteriormente otro 2 y Enter.

Figura 38. Recinto construido en 2 ejes

Seguidamente se procede a dar volumen al recinto.


I. Para eso, se usa la herramienta de Empujar (Pull/Push).

56

Memoria descriptiva

Figura 39. Iconos de la herramienta del conjunto grande

II. Se ha situar encima del rectngulo, hasta que se vea que se ilumina con unos
pequeos puntos azules en toda su superficie.

Figura 40. Paso para dar volumen al recinto

III. Se hace clic en el rectngulo. Si se mueve el ratn hacia arriba, se ve cmo se


expande y se vuelve un cuerpo tridimensional. Igual que antes, para darle una altura
de 2 metros, se pulsa un dos.
IV. Se pulsa Enter. Y se observa el resultado final.

Figura 41. Recinto levantado

Auxiliares
Para comprobar que, efectivamente, nuestro recinto mide 2x2x2 metros, se usar la
herramienta de medicin:

Figura 42. Barra herramientas de medicin

Se hace clic para medir entre dos puntos:

Figura 43. Medicin de dos puntos

Como muestra en la figura la distancia es dos metros, tal y como se ha indicado en el


dibujo.

57

Memoria descriptiva

Ahora se imagina que se quiere dibujar algo dentro de un recinto inmenso, pero como las
caras del recinto son opacas, no se puede dibujar a travs de ellas. Esto se soluciona
seccionado el recinto; para eso, se usa esta herramienta figura 1. A hacer clic en ella, el
cursor se mostrar como en la figura 2. Al pasar el ratn por encima de las caras del
recinto, el "rectngulo" que representa la seccin, cambia de orientacin, se escoge su
orientacin tomando las flechas como la direccin en la que se va a querer ver a travs.
Cuando se tenga se puede hacer clic. Quedar el resultado de la figura 3.

[1]:

[2]:

[3]:

Si se selecciona la seccin (en naranja) con la herramienta de Seleccionar [ ] y, luego se


escoge la herramienta Mover (M), se puede desplazar la seccin a lo largo de la direccin
que indican las flechas:

Figura 44. Seccin de la figura

I. No se secciona nada, pues no est en contacto con el recinto.


II. Como se aprecia, se puede seleccionar objetos a travs de la seccin.

7.2.1.6

Herramientas de acabado

Una vez aprendido cmo dibujar, se puede aadir detalles a los modelos. Un ejemplo sera
ponerle el tipo de material a cada elemento, las sombras y el estilo:

Cmara
A continuacin, se proceder a explicar cmo movernos por el escenario, los comandos
son estos:
Figura 45. Iconos de la herramienta de cmara

I. Seleccionar (Espacio): Herramienta por defecto, selecciona cosas para despus


manipularlas con otras herramientas.

58

Memoria descriptiva

II. Orbitar (O): Cambia la orientacin de la cmara mientras se mantiene en el mismo


sitio.
III. Mano (H): Cambia la posicin de la cmara mientras enfoca en la misma direccin.
IV. Zoom (Z): Si se hace clic y se mueve arriba y abajo, se acerca o se aleja.
V. Zoom Extendido (Ctrl+Shift+E): En la posicin de la cmara, hace el zoom justo
para que todo el modelo dibujado se ajuste a la pantalla.
Con la herramienta

Seleccionar:

I. Clic simple en uno de las caras del recinto, se marca la superficie solamente.
II. Clic doble en la misma cara, se marca la superficie y los bordes.
III. Clic triple, se marca todo el cuerpo 3D.

Figura 46. Cuerpo 3D marcado entero

Esto es til por ejemplo para aumentar o reducir el tamao del recinto:
I. Se selecciona todo el recinto (ejemplo 3 de seleccionar, o bien creando un recuadro
con el mouse)
II. Mientras sigue marcado, se selecciona la herramienta de Escalar (S) [1], se ver
que el recinto se rodea de unos anclajes en cada esquina y puntos medios [2]:

[1]:

[2]:

Como se puede deducir dependiendo de qu anclajes se elija, la figura variar de una forma
u otra (solamente se puede seleccionar una anclaje, automticamente se seleccionar el
anclaje contrario). En este caso, se usa la diagonal respecto al origen de coordenadas (ver
imagen superior). Si se hace clic en el anclaje superior izquierda. Como antes, en la parte
inferior derecha de la pantalla se puede observar la escala en forma de nmeros (siempre
existe la opcin de hacerlo directamente con el mouse, pero si se hace as es ms preciso).
El 1, es el tamao original, el 0,5, reducir el tamao a la mitad y 2 duplicarlo.

59

Memoria descriptiva

Modificacin
Para rotar el recinto, se usa esta herramienta [1], al escogerla, el ratn se convertir en un
transportador de ngulos [2]:

[1]:

[2]:

El color de este transportador de ngulos, indica el plano al eje del cual es perpendicular;
en este caso, estara en el plano que se llamara "tierra. Para empezar, se rota respecto uno
de sus vrtices:
I. Se coloca el transportador en el plano perpendicular al eje azul (ver imagen
inferior).
II. Se hace clic en un vrtice del recinto para tomar a partir de ah el ngulo cero de la
rotacin.
III. Se mueve el mouse en la direccin deseada y se hace clic para aceptar.
IV. Opcionalmente si se pulsa Control, se crear una copia y se rotar la copia en vez
del original.

Figura 47. Rotacin de la copia

Evidentemente, se puede rotar en cualquier lugar de la figura y en cualquier direccin:

Figura 48. Rotacin de la figura

60

Memoria descriptiva

Ahora se usar la herramienta de traslacin, como su nombre indica, sirve para trasladar
cosas.

Figura 49. Iconos de modificacin

Como se ha visto, si se pulsa la tecla Control, se crear una copia del objeto original y se
mover la copia, dejando al original donde estaba. O bien si se mueve en una direccin un
poco y se pulsa la tecla Shift, se bloquear la direccin de movimiento, y as no se desva,
aunque se suba o se baje el mouse. Esto se puede aplicar, como en la imagen, para seguir
una lnea, o desplazar el objeto hasta un sitio que est relacionado (debajo, en paralelo,...)
con otro objeto, pero no en contacto.

Figura 50. Traslacin de un objeto por los ejes

Y como antes, tambin se puede mover simplemente algunas caras o lneas y no el cuerpo
entero. Seleccionando solamente la parte a mover:

Figura 51. Pasos para mover una cara del objeto

Materiales
SketchUp permite pintar las caras con materiales para darles ms detalle y un mayor
realismo. Los materiales son bsicamente pinturas que tienen un color y, opcionalmente,
una textura (definida en un archivo de imagen). Por ejemplo, un material para pared de
color gris y con una apariencia o textura similar a la de un acabado real. Aqu se ve una

61

Memoria descriptiva

vivienda con un acabado de placas grises en las paredes y tejas de madera gris. Tambin se
ha aplicado al suelo un material que simula el csped.

Figura 52. Casa con csped

Cuando se crea una geometra en SketchUp, se le asigna un material predeterminado.


Este material se puede cambiar pintando la geometra con otro material. Los materiales
tambin tienen una propiedad de opacidad (un nmero entre 0 y 100%), que permite crear
materiales transparentes, como el cristal. Puedes pintar una cara con uno de estos
materiales para crear una ventana.

Figura 53. Materiales

Estilos
Un estilo es un conjunto predefinido de ajustes de visualizacin que puede aplicarse a un
modelo y al rea de dibujo para darle una apariencia especfica. Un estilo puede consistir
en un tipo especfico de arista, cara, color del cielo y de fondo, marca de agua y otros
efectos del rea de dibujo (por ejemplo, el color utilizado para representar la geometra
seleccionada). SketchUp tiene varios estilos, unos se utilizan para dibujar un modelo
(porque no utilizan ningn efecto visual intenso) y, otros son mejores para la impresin o
presentacin de un modelo (porque utilizan efectos visuales para dar al modelo la
apariencia de estar dibujado a mano). Por ejemplo, un estilo predeterminado puede tener
un tipo de arista alterada, un tipo de cara de modo de lnea oculta, un color de fondo
blanco, un color de cielo azul, un color de suelo marrn, etc.

Sombras
SketchUp permite proyectar sombras en el modelo como si ste se encontrara en un
entorno real. Estas sombras se pueden generar teniendo en cuenta la hora del da y la
posicin virtual del modelo en un espacio real. Las sombras estn diseadas en SketchUp
para ofrecer una respuesta dinmica a los cambios en las geometras y en el punto de vista
de la cmara. Las sombras son una forma excelente de dar a los modelos mayor sensacin
de profundidad y de realismo en SketchUp.

62

Memoria descriptiva

Figura 54. Casa con sombra

7.2.1.7

Plugin OpenStudio

OpenStudio es un plugin gratuito para el programa Google SketchUp 3D de dibujo. El


plugin ayuda a crear y editar la geometra de la construccin en los archivos de entrada
EnergyPlus. El plugin tambin permite lanzar simulaciones EnergyPlus y ver los
resultados sin dejar de SketchUp. El plugin permite utilizar las herramientas de SketchUp
estndar para crear y editar las zonas EnergyPlus y superficies. Puede explorar los archivos
de entrada EnergyPlus utilizando todas las capacidades nativas de SketchUp 3D para ver la
geometra de cualquier punto de vista, aplicar diferentes estilos de reproduccin, y realizar
estudios precisos de sombreado. El plugin le permite mezclar el contenido con el contenido
de simulacin EnergyPlus decorativos como imgenes de fondo, paisajes, gente, acabado y
detalles arquitectnicos, todo ello en el mismo modelo de SketchUp.
Este plugin contiene los siguientes submens:

Figura 55. Iconos del plugin OpenStudio

I. Nuevo: Crea un archivo EnergyPlus nueva entrada. El nuevo archivo se genera de


un plantilla que incluye varios objetos de entrada que son necesarios para todos los
archivos de entrada EnergyPlus. Puede editar los objetos de forma predeterminada
en la plantilla de la modificacin del archivo de texto "New_File_Template.idf",
ubicado en el directorio de "Google SketchUp 7/Plugins/OpenStudio". Hasta que se
guarda el archivo, slo reside en la memoria y es vulnerable a la prdida. Este
comando tambin cierra cualquier archivo de entrada EnergyPlus que podra ser
abierto. Si hay son los cambios no guardados, se le preguntar si desea guardar el
archivo abierto en primer lugar. Nueva EnergyPlus objetos pueden ser creados
usando la zona nueva o Nueva sombreado del grupo herramientas.
II. Abrir: Abre un archivo de EnergyPlus existentes de entrada y lo hace utilizando del
SketchUp las entidades: los grupos, caras y aristas. El archivo de entrada est ahora
asociado con el corriente modelo de SketchUp. Cualquier cambio que haga a las
entidades de SketchUp con la norma herramientas (Mover, empujar / tirar, Escala,

63

Memoria descriptiva

goma de borrar, etc) se actualizar inmediatamente en EnergyPlus objetos en el


archivo de entrada. Los objetos nuevos de EnergyPlus pueden ser creados usando
la zona nueva o Nuevas herramientas de sombreado de grupos, o mediante la
edicin de un grupo de EnergyPlus existentes (zona o sombreado grupo) en que
inmediatamente se aaden nuevos objetos EnergyPlus en el archivo de entrada.
III. Guardar: Guarda la entrada de EnergyPlus archivo a su ruta actual. Si el archivo
no ha guardado antes, un cuadro de dilogo le pregunta si desea guardar el archivo
nuevo.
IV. Muestra errores y advertencias: Muestra los errores y advertencias de comandos
con una ventana de dilogo y un registro de errores y advertencias que se genera
cuando se abre un archivo de entrada EnergyPlus. Errores y advertencias pueden
incluir problemas de geometra comn o errores en la sintaxis de la entrada de
archivo. Muchos errores de geometra comn (por ejemplo, al revs de piso o
techo, en el interior por la ventana, no coplanarias superficies, etc) se fijan de
forma automtica y as puedes acabar abrir el archivo de entrada.

Figura 56. Ventana de errores y advertencias

V. Nueva Zona: Para seleccionar un punto que se convertir en la nueva zona de


origen haciendo clic en algn lugar de la vista. Un modelo de SketchUp vaco
resaltado con un rectngulo azul aparecer anclado en una esquina de un punto de
la construccin. Con el cursor todava situado sobre el punto de construccin, haga
doble clic en l para comenzar a editar de la zona. Cualquier entidad SketchUp
nueva que se dibuje dentro del grupo con el estndar herramientas (rectngulo,
polgono, lpiz, etc) inmediatamente agregar la transferencia de calor EnergyPlus
nuevas superficies (BuildingSurface: completo, FenestrationSurface: completo, y
Sombra: Zona: completo) para el archivo de entrada. Suelos, paredes, techos,
ventanas, puertas y sombreado adjunta superficies que son automticamente
deducidas de sus inclinaciones y posiciones.

Figura 57. Zona del Google SketchUp

64

Memoria descriptiva

VI. Sombreado: Esta herramienta funciona de manera casi idntica a la herramienta de


la zona nueva, a excepcin de que cualquier nuevo SketchUp entidad que se trace
en el interior del grupo, inmediatamente se agregar un sombreado independiente
de la nueva superficies (sombreado: Construccin: Sitio completo y Sombra:
completo) para el archivo de entrada, en lugar de las superficies de transferencia de
calor.
VII. Herramienta de informacin: Muestra informacin sobre la cara la cual se est
trabajando, aunque es una informacin momentnea.
VIII. Informacin de objetos: Muestra una ventana
de dilogo con informacin sobre el objeto que
est seleccionado actualmente. El contenido del
cuadro de dilogo Informacin de objetos de
cambios basados en el tipo de objeto
seleccionado. Seleccione un grupo de la zona
objeto de obtener la informacin sobre la
zona. Apertura de un grupo de la zona de
edicin (doble clic), y seleccionar un cara a
obtener informacin acerca de la superficie
objeto de la transferencia de calor. Abrir un
grupo de sombreado para la edicin y
seleccione un rostro para obtener informacin
acerca de la superficie objeto de sombreado
estn separados. Sin seleccin, se obtiene
informacin de los objetos sobre el objeto de
construccin. Cambio la seleccin abriendo el
cuadro de dilogo Informacin de objetos de
forma dinmica y la actualizacin de
contenidos con informacin acerca de la nueva
seleccin.
Figura 58. Informacin de objetos

65

Memoria descriptiva

IX. Perfilador: Te muestra todos los objetos que existen en el modelo. Des de la
persona objeto y todas las zonas diferentes existentes en el modelo.
X. Simular: Muestra una ventana de dilogo donde se le permite seleccionar ejecutar
opciones de control, seleccione un tiempo y ejecutar perodo, y elegir cmo desea
que los resultados sea. Pulsa el botn ejecutar para iniciar una simulacin del
archivo EnergyPlus corriente de entrada. El motor de EnergyPlus comenzar a
ejecutar en una ventana de comandos. Puedes continuar trabajando en SketchUp,
mientras que la simulacin se est ejecutando. Si decides no ejecutar la simulacin
en este momento, puedes pulsar el botn Aplicar para guardar los cambios en el
archivo de entrada. Las opciones para controlar el paso te permiten elegir si deseas
ejecutar simulaciones de diseo o de da, la simulacin de archivo del tiempo o de
ambos. Tambin puedes seleccionar la fecha inicial y final para el perodo de
tiempo aqu. El cambio de estas opciones se actualiza el objeto RunPeriod en el
archivo de entrada.

Figura 59. Ventana de simulacin

XI. Generador de archivos de ejemplo: Te conecta con el departamento de energa en


el caso que necesites ayuda eficaz.
XII. Procesamiento de color: Una vez que el archivo se ha cargado, el perodo de
ejecucin seleccionado, y los datos de la variable seleccionada el usuario puede ver
el modelo del color por el valor de datos utilizando el comando de procesamiento
de color. Las superficies o zonas estn coloreadas por el valor de la variable en un
instante determinado en el tiempo. Para cambiar el momento en que las variables se
muestran utilizar el control de SketchUp en Configuracin de sombra (Ventana->
Sombras). Si el tiempo est fuera del perodo de ejecucin actual entonces no
mostrar valores. El usuario puede mostrar una barra de color para hacer referencia
a los valores absolutos de la variable, o usar el cursor del valor de los datos.

66

Memoria descriptiva

XIII. Cuadro de dilogo: Permite a los usuarios seleccionar la salida de EnergyPlus


Estndar (ESO) de archivo correspondiente a su modelo actual de las IDF. Una vez
que la ESO se ha cargado, el usuario puede seleccionar a disposicin de los
perodos de ejecucin (tales como los das de diseo o simulaciones anuales) y, a
continuacin de la memoria disponible o variables metros. Escanear el "*. mdd",
"*. MTD", y "*. RDD" archivos en que puedes ver qu metros y variables de
informes estn disponibles para su modelo. Actualmente, slo de superficie o
medidores de nivel de zona y el informe variables son compatibles. Tenga en
cuenta que el archivo de ESO puede llegar a ser bastante grande para los modelos
con muchas variables de informes, anlisis, este fichero puede ser algo lento y
causa la interfaz de usuario se bloquee. Si es posible, limitar la cantidad de metros
y la variable de salida del informe solicitado, mirar los resultados de das de diseo
nico, o acortar el perodo de ejecucin de la simulacin para minimizar el tamao
de la ESO.
XIV.

Animacin: Una vez que el archivo de ESO se carga en memoria, el usuario puede
ver cmo las variables cambian con el tiempo a lo largo de su modelo utilizando el
comando Animacin. El perodo de tiempo para ejecutar se puede configurar y el
usuario puede configurar la animacin de bucle continuo. Pero no a la exportacin
directa de animacin que se ofrece. Sin embargo, una herramienta de captura de
pantalla puede ser utilizada para grabar un vdeo para su uso posterior.

XV. Rebobinar, marcha y avanzar: Dar paso a la simulacin durante el periodo de


tiempo exigido.

7.2.1.8

Diseo del edificio de oficinas INEF Lleida

Como se ha comentado en el apartado anterior se ha creado un recinto que puede servir


como ejemplo de nuestro edificio. Mediante la herramienta de medida del programa
AutoCAD se toma detalle de las distintas medidas para la construccin de los mdulos
constituyentes del edificio. Se inicia la construccin con el mdulo de la direccin, y, en su
medida van aadindose los distintos mdulos independientemente. A continuacin se
mostrar la evolucin hasta su construccin final aadiendo a cada nuevo recinto su
nombre y superficie til.
Primeramente, se muestran los recintos de la direccin, la secretaria direccin, la
subdireccin actividades y servicios y, por ltimo, la subdireccin de estudios.

Figura 60. Vista 1 paso

67

Memoria descriptiva

Inicialmente se construye la direccin, en que su superficie til de detalla en la tabla


siguiente. Seguidamente se aade el mdulo de secretara direccin y as sucesivamente
con los distintos mdulos o recintos. La tabla siguiente muestra las superficies tiles
mostradas en la figura anterior.
Superficie til (m2)
Subdireccin de estudios
27.34
Subdireccin de actividades
28.32
Secretaria direccin
28.26
Direccin
28.95
Tabla 29. Superficie paso 1

A continuacin se aade el mdulo de la sala de honor.

Figura 61. Vista 2 paso

La tabla muestra el recinto que se ha aadido con la superficie til en metros cuadrados.
Superficie til (m2)
Sala de honor
27.34
Tabla 30. Superficie paso 2

Una vez aadida la sala de honor se aaden la gerencia, la direccin OA y la subdireccin


Postgrado.

Figura 62. Vista 3 paso

68

Memoria descriptiva

Se han aadido dos recintos cuya superficie til se muestra en la tabla siguiente.
Superficie til (m2)
Direccin OA
25.37
Subdireccin postgrado
19.86
Tabla 31. Superficie paso 3

En la siguiente imagen se muestran la Cafetera, la sala de juntas y la sala audiovisuales.

Figura 63. Vista 4 paso

La cafetera ocupa la superficie til ms grande del edificio con 260.54 m2. La superficie
til de los otros dos recintos aadidos se muestra en la tabla siguiente.
Superficie til (m2)
Cafetera
260.54
Sala de juntas
77.08
Sala audiovisuales
96.21
Tabla 32. Superficie paso 4

Ya se ha iniciado con la planta 1 aadiendo unas cuantas oficinas.

Figura 64. Vista 5 paso

69

Memoria descriptiva

Se han adjuntado cuatro oficinas en un mismo grupo ya que la superficie til de cada una
de ellas es similar.
Superficie til (m2)
Oficinas 014-015-016-017
26.14 x 4
Cocina y limpieza
84.02
Comedor reservado
36.14
Tabla 33. Superficie paso 5

La siguiente imagen muestra por completo el diseo de la planta 1 formada por despachos
por completo.

Figura 65. Vista 6 paso

La superficie til de todos los despachos de la planta 1 es la siguiente:


Superficie til (m2)
Despacho 101
16.34
Despacho 102
13.78
Despacho 103-104
26.14
Despacho 105
13.41
Despacho 106
12.69
Despacho 107
14.72
Despacho 108
12.34
Despacho 109
27.85
Despacho 110
27.56
Despacho 111
14.13
Despacho 112
13.7
Despacho 113
27.75
Despacho 115
11.38
Despacho 116
15.06
Tabla 34. Superficie paso 6

70

Memoria descriptiva

Como vista final del diseo del edifico aadiendo los ltimos despachos que faltan para
completar la planta 1, y por lo tanto, el edificio se muestran en la figura siguiente.

Figura 66. Vista 7 paso

Y su superficie til se muestra en la tabla siguiente:


Superficie til (m2)
Despacho 117
41.66
Despacho 118
25.1
Despacho 119
17.92
Despacho 120
41.75
Despacho 121
12.38
Despacho 122
13.89
Despacho 123
18.65
Despacho 124
12.85
Tabla 35. Superficie paso 7

7.2.1.9

Resultados finales de la creacin del modelo del edificio de


oficinas INEF Lleida

En las siguientes figuras se muestran los resultados finales de las distintas vistas que
forman el edificio de la universidad en condiciones actuales.

Alzado

Figura 67. Vista del alzado en condiciones actuales

71

Memoria descriptiva

Planta

Figura 68. Vista de la planta en condiciones actuales

Perfil izquierdo

Figura 69. Vista del perfil izquierdo en condiciones actuales

Perfil derecho

Figura 70. Vista del perfil derecho en condiciones actuales

Posterior

Figura 71. Vista del posterior en condiciones actuales

72

Memoria descriptiva

Isomtrico

Figura 72. Vista isomtrica en condiciones actuales

7.2.2

Simulacin del modelo del edificio con EnergyPlus

En este apartado se someter el edificio a la simulacin mediante el programa de clculo


Energy Plus, usado en el presente proyecto para realizar el clculo de cargas y se mostrar
cmo se han ido introduciendo los parmetros de entrada segn el estudio del recinto
realizado anteriormente. Los distintos escenarios a simular sern los siguientes:
I. Condiciones actuales.
II. Mejora del acristalamiento doble.
III. Mejora del voladizo.
IV. Mejora mixta.

7.2.2.1

Introduccin

EnergyPlus tiene sus races en dos programas, el BLAST y DOE-2. BLAST, Building
Loads Analysis and System Thermodynamics y DOE-2 fueron desarrollados y liberados en
la dcada de 1970 y principios de 1980 como herramientas de simulacin de carga
energtica.
Lo emplean tanto ingenieros como arquitectos que desean dimensionar de manera optima
instalaciones HVAC (Heating Ventilating and Air Conditionated), estudios de adaptacin,
optimizar el rendimiento de la energa, etc.
Nacido de las preocupaciones por la crisis energtica de la dcada de 1970 y el
reconocimiento de que la energa en la construccin y el consumo es un componente
importante de la energa de Amrica, los dos programas intentaron resolver el mismo
problema desde dos perspectivas ligeramente diferentes. Ambos programas tienen sus
ventajas y deficiencias, sus partidarios y detractores, y las bases slidas de usuarios tanto a
nivel nacional e internacional.
Al igual que sus programas de padres, EnergyPlus es un programa de anlisis de la energa
trmica y de simulacin de carga.

73

Memoria descriptiva

Basado en la descripcin de de un edificio definido por el usuario desde la perspectiva de


la constitucin fsica (construccin), sistemas mecnicos, etc.
EnergyPlus calcula la calefaccin y la refrigeracin de cargas necesarias para mantener
puntos de ajuste de control trmico, condiciones en un sistema HVAC, y el consumo
energtico de los equipos de la planta primaria, as como muchos detalles de simulacin de
otro tipo que son necesarios para comprobar que la simulacin est funcionando como se
desea.
Muchas de las caractersticas de simulacin han sido heredadas de los programas BLAST y
DOE-2. A continuacin se listan algunas de las caractersticas de EnergyPlus. Si bien esta
lista no es exhaustiva, se pretende dar la idea y la aplicabilidad de EnergyPlus a la
simulacin.
I. Solucin integrada y simultnea, donde la respuesta del edificio y los sistemas
primario y secundario estn fuertemente acoplados (lleva a cabo iteraciones cuando
es necesario).
II. Muestras temporales, el usuario puede definir intervalos de tiempo para la
interaccin entre las zonas trmicas, temperatura ambiente, y de los sistemas.
III. Texto ASCII tanto el archivo de tiempo meteorolgico, entradas, y archivos de
salida, que incluyen las condiciones, la norma y los informes definibles por el
usuario, respectivamente.
IV. Balance trmico, tcnica de solucin de base para la construccin de cargas
trmicas que permite el clculo simultneo de los efectos de radiacin y
conveccin, tanto en la superficie interior y exterior.
V. Conduccin de calor transitoria a travs de elementos de construccin tales como
paredes, techos, pisos, etc., utilizando funciones de conduccin.
VI. Mejora de la transferencia de calor de modelado a travs del enlace al modelo
tridimensional y la simplificacin de las tcnicas analticas.
VII. Modelos de confort trmico basado en la actividad, humedad, etc.
VIII. Clculos de acristalamientos avanzado, incluyendo persianas controlables, cristales
mltiples capa por capa, balances trmicos que permiten la asignacin adecuada de
la energa solar absorbida por los cristales de las ventanas, y una biblioteca
(datasheet) de nmerosas ventanas disponibles en el mercado.
IX. Control del Daylighting, clculos de la iluminacin interior, simulacin y control
de luminarias, y el efecto de la iluminacin artificial en la reduccin de la
calefaccin y la refrigeracin.
X. Lazos configurables basado en los sistemas de HVAC (convencional y radiante)
que permite un modelo de sistemas tpicos y los sistemas ligeramente modificados
sin tener que recompilar el cdigo fuente del programa.
XI. Clculos de la contaminacin atmosfrica (partculas de CO2, SOx, NOx, CO).

74

Memoria descriptiva

Figura 73. EnergyPlus estructura simplificada

Ningn programa es capaz de manejar todas las situaciones de simulacin. Sin embargo
una de las grandezas de EnergyPlus es que intenta abarcar tantas construcciones como le es
posible y muchos diseos de HVAC a la hora de poder escoger la mejor opcin.
EnergyPlus no tiene una interfaz de usuario. Su objetivo es ser el motor de simulacin en
torno a una interfaz secundaria. Sus entradas y salidas son simple texto, claramente
descrito. Los diseadores de interfaz grafica crean herramientas de calidad para poder
interaccionar con EnergyPlus segn las preocupaciones del mercado y las demandas, estas
interfaces pueden observarse en la pgina principal de EnergyPlus, www.EnergyPlus.gov.
Entonces, liberada de la parte grafica, se liberan recursos para as potenciar la produccin y
los algoritmos, con el fin de mantener el ritmo del mercado y las demandas de los
profesionales, EnergyPlus saca al mercado una versin nueva y con mejoras cada seis
meses de manera gratuita.

7.2.2.2

EP-Launch

EP-Launch es un componente opcional de la instalacin de Windows EnergyPlus. Para los


usuarios que quieren una manera simple de seleccionar los archivos. Adems, EP-Launch
puede ayudar a abrir un editor de texto para modificar los archivos de entrada, abrir una
hoja de clculo para obtener los resultados postprocesados, un navegador web, y arrancar
un visor para el archivo grfico.

Figura 74. Ventana EP-Launch

75

Memoria descriptiva

EP-Launch est ubicado en el directorio principal de EnergyPlus. Adems, est disponible


en el men contextual de EnergyPlus.

7.2.2.3

Seleccin de archivos meteorolgicos y de entrada

El archivo de entrada y los archivos de tiempo meteorolgico pueden seleccionarse de


manera individual presionando el botn Browse, o presionando en la flecha se muestra un
listado de los archivos recientemente usados.

7.2.2.4

Simulacin de un archivo de entrada

Una vez creado y configurado el archivo de entrada, despus de seleccionar el tiempo,


basta con pulsar el botn Simulate para iniciar el motor de simulacin de EnergyPlus. En
este punto, una ventana de MS-DOS se despliega en la pantalla y muestra el progreso de la
simulacin. Este proceso ser rpido si se ha seleccionado un rango corto de das a simular.

7.2.2.5

Resultados de una simulacin

Despus de ejecutar la simulacin y que se cierre la ventana de MS-DOS, EnergyPlus


termina, y se muestra un mensaje de estado como este:

Figura 75. Resultados simulacin

En esta ventana se ensea una visin general rpida de si hay advertencias/warnings


(donde debes mirar que ha fallado, pero no es obligado arreglarlo), o grave/several (se
debe solucionar para poder simular correctamente), as como el tiempo que tom para la
simulacin.
Una forma de abrir los archivos con facilidad es utilizar el panel rpido para la simulacin
como se muestra en la figura:

Figura 76. Panel rpido de resultados

En este panel muestra los archivos disponibles, los que estn en gris no estn disponibles.
Ahora se describe de manera sencilla los archivos de salida ms importantes de este cuadro
de resultados.

76

Memoria descriptiva

Los archivos de salida ms importantes se muestran a continuacin:


I. ESO Informe de las variables de salida.
II. RDD Lista de las posibles salidas que puedes observar con tu simulacin.
III. MDD Lista de las posibles mediciones que observaras en la simulacin.
IV. ERR Listado de errores y avisos.
V. BND Informe detallado del sistema HVAC y sus nodos de conexin.
VI. MTR Informe de las medidas de salida.
VII. SVG - Diagrama HVAC.
VIII. DXF Archivo de dibujo en formato AutoCAD DXF.
IX. CSV Archivo tipo Microsoft Excel.

7.2.2.6

Visualizacin de parmetros

En EnergyPlus una vez terminada la simulacin se puede observar la salida que se desee.
Para visualizar la salida que se quiere, acudimos al archivo RDD y se copia el nombre de la
variable que se quiera en el archivo IDF en el text editor, como se observa en la figura:

Figura 77. Asignacin de salidas al archivo IDF

En esta imagen se muestra como abriendo el archivo RDD se escoge por ejemplo la
variable de salida de Wind Speed, es decir, la velocidad del viento, la cual nos da la
media en una zona concreta que se asigna, con una periodicidad horaria. Esta lnea, se
copia en el archivo IDF abrindolo con EP-Launch/Text Editor y copindolo en cualquiera
posicin del texto, no importa. Se cierra guardando y se le da al botn de simular.
Una vez lista la simulacin, se puede abrir nuestro fichero de salida con la variable que se
ha pedido, hay diferentes manera de ver estas salidas, una de ellas y la ms sencilla es a
partir de un fichero Microsoft Excel, es la primera opcin de la ventana rpida de
resultados, el botn CSV.
Se abrir de manera automtica un Excel, con los valores, donde en la primera columna se
observa el tiempo de muestra y en las siguientes columnas primero se observa el nombre

77

Memoria descriptiva

de la salida y las unidades que tiene, y las filas siguientes se pueden observar los
resultados.

Figura 78. Muestra del archivo CSV

Esto es muy til si solamente se tiene unas pocas salidas, y el periodo de simulacin es
corto, en cambio simular rangos de tiempo como semanales o mensuales supone miles de
filas de resultados, y es complicada su comprensin.
Por esta razn se han creado programas o plugins compatibles con EnergyPlus para poder
visualizar estas salidas de una manera ms eficaz y con todo detalle.
Para esta visualizacin grafica existen dos programas excelentes, xEsoView y Dview. A
continuacin se explica con detalle todo su potencial en el aspecto de visualizacin para
EnergyPlus.
XEsoView, es un visualizador de archivos, es un programa abierto al pblico, se puede
descargar directamente desde esta direccin Web http://sourceforge.net/projects/xesoview.
Con este programa se abren los archivos .ESO generados con EnergyPlus y da una visin
muy rpida de los resultados de la simulacin. xEsoView muestra todos los nombres de las
variables en una lista, que la persona puede ordenar, filtrar etc. Esto se observa en la zona
de la izquierda.

Figura 79. Lado izquierdo de la ventana de xEsoView

En el lado derecho de la pantalla se muestra la representacin grafica de la variable


seleccionada. El eje de tiempo se puede cambiar con intervalos predefinidos (hora, da,

78

Memoria descriptiva

semana, mes, total), xEsoView tambin tiene la funcin zoom para ampliar ms el nivel
del detalle.

Figura 80. Lado derecho de la ventana de xEsoView

Con un simple CTRL + C puedes copiar los datos de las variables en el portapapeles, y de
esta manera puedes pegarlos en tu hoja de clculo, para un anlisis posterior, o lo que
desees.
Bien, ahora se pasa a describir el otro programa grafico para leer los archivos de salidas, se
trata de Dview.
Dview, es un programa que muestra resultados en series de tiempo con una gran variedad
de formatos. Est diseado para observar archivos de tiempo con un muestreo horario, con
nfasis particularmente en datos de tipo ao. Dview abre archivos de texto y archivos de
Excel que contengan cualquier tipo de datos cada hora, y reconoce varios formatos de
archivo, incluyendo los EPW, que son los Energy Plus Weather File, archivos
meteorolgicos propios de EnergyPlus.
Este software es de libre distribucin, y puede ser descargado de su pgina principal, en
http://www.mistaya.ca/index.htm, dirigindose a la seccin software, y clicando en la
pestaa de Dview, la versin con la que se trabaja es la ms nueva, la versin 1.24.
Dview permite elegir dos ventanas y comparar resultados, solapando un grafico encima de
otro, abriendo dos ventanas a la vez, y hacer mltiples comparaciones. A continuacin se
enumeran las caractersticas importantes en la imagen siguiente.

79

Memoria descriptiva

Figura 81. Ventana de Dview

80

Memoria descriptiva

Con el nmero uno (1) est la comparacin de variables, como se puede ver se tiene dos
columnas de cuadrados, si se elige dos cuadrados de la misma columna automticamente
se solapa un grafico con otro, esto es muy bueno si se tiene variables de la misma magnitud
y se quiere ver por ejemplo el cambio de temperatura de una habitacin respecto con otra
adyacente. (3) Dview permite solapar al menos siete u ocho variables cada una con un
color diferente para su distincin.
En la parte del nmero dos (2) se tiene para elegir diferentes maneras de ver las salidas, se
trata de poder elegir el rango, tanto diario, mensual, horario, etc. En la pestaa profile se
puede ver las medias de cada mes del ao de la variable a elegir.

Figura 82. Pestaa profile de Dview

Otra gran caracterstica de Dview, es que ofrece un mapa de calor de cada variable, a
continuacin adjunto por ejemplo el mapa trmico de una habitacin con un rango de
temperatura mxima hasta 25 C.

Figura 83. Mapa trmico Dview

Se observa el mapa trmico del habitculo, en una escala anual, en la parte de la derecha se
puede ver la leyenda donde indica a lo que equivale cada color del mapa. Como se ha
dicho que la habitacin debe estar a una temperatura mxima de 25 C marca el color rojo
que es el ms alto como el mximo al que podr llegar.
La siguiente pestaa es la de boxplot, donde muestra dentro de cada mes la media alta
diaria y la media baja diaria, por ejemplo de temperatura. Y tambin se puede ver las
mximas y mnimas a las que se llegan con las lneas verticales que salen de los cuadrados
de colores, en que se ha limitado, porque se ha hecho un setpoint de temperatura haciendo
que en la habitacin no pase de 25 C y la temperatura no descienda de los 20C, a
continuacin se adjunta imagen.
81

Memoria descriptiva

Figura 84. Boxplot Dview

Estas son de las caractersticas ms importantes tanto de xEsoView como de Dview, una
vez trabajados con ellos, se llega a la conclusin que Dview tiene ms posibilidades y
mucho mas potencial, ya que permite trabajar con mas variables a la vez, xEsoView no lo
tiene y por lo tanto es un gran defecto porque se tiene que ir abriendo diferentes grficos
uno por uno, cerrando uno y abriendo otro, caso contrario de Dview que tiene como ya se
ha explicado la opcin de visualizar mltiples salidas.
Bien, por ahora se ha explicado cmo hacer funcionar el EP-Launch, y poder observar las
salidas de las que dispone nuestro modelo. Ahora se pasa a explicar cmo crear el modelo
desde el inicio con el IDF Editor, el otro programa que se instala con el ejecutable de
EnergyPlus.

7.2.2.7

IDF Editor

IDF Editor es donde se debe aadir todas las caractersticas del recinto a simular, se escoge
que elementos componen la estructura del modelo, se indicar tanto la situacin geogrfica
donde estar ubicado, como el material de que estarn hechas las ventanas, paredes,
tambin se puede aadir datos como el nmero medio de personas que pasaran por nuestro
modelo, y decir cul ser su actividad metablica para tambin tenerlo en cuenta en la
simulacin.

7.2.2.8

Introduccin de parmetros comunes del edificio

En este apartado se aadirn las variables comunes en todo el recinto y que se tienen que
cumplir para toda zona dentro del mismo. Se empieza abriendo el IDF Editor, donde se
observan variables de entrada, agrupadas en familias como por ejemplo: localizacin,
materiales, elementos constructivos de la superficie, etc.

82

Memoria descriptiva

Figura 85. Ventana inicial IDF Editor

Lo primero que se debe poner en el IDF Editor es la versin (Version) del programa, en
este caso es la 4.0.

SimulationControl
El segundo paso es ir a SimulationControl, donde aparecer este cuadro, se debe aadir un
New Object porque por defecto estar vaci, de esta manera al lado de SimulationControl
aparecer un 1, indicando que se ha aadido un objeto con datos dentro de esa variable de
entrada.

Figura 86. SimulationControl IDF Editor

Dentro de SimulationControl se debe poner en afirmativo la ltima opcin a la que hace


referencia a la simulacin meteorolgica. Ya que si no estuviera activado, se debera
introducir manualmente los valores de temperatura anual. Por este motivo se ha buscado el
archivo meteorolgico de la ciudad de Lleida, para que de manera automtica el motor de
clculo tome los valores necesarios para la simulacin.

83

Memoria descriptiva

Building
Una vez se ha configurado el control de simulacin, se proceder a aadir el edificio
accediendo a la pestaa Building, se asigna que est ubicado en una zona urbana, si esta
encarado al norte, y otros datos a continuacin explicados.

Figura 87. Building IDF Editor

Dentro de Building se tiene de aadir un nombre al edificio. Se seguir diciendo que esta a
0 del eje que marca el Norte ya que se trabaja con coordenadas absolutas y la orientacin
no se modifica aqu sino donde se cre el modelo 3D del edificio.
En la variable Terrain se deber de explicar donde estar situado nuestro modelo, si est en
una zona urbana, si esta a las afueras de la ciudad, el campo, etc. En la opcin de Solar
Distribution hace referencia a los algoritmos de la radiacin solar, Algoritmos de la
radiacin solar, puedes escoger opciones de radiacin exterior, interior o ambas. Teniendo
en cuenta que con la radiacin interior lo que no se absorbe en el primer impacto se pierde
en cuanto a objetos.
Y como ltimo, el nmero de das para el Warmup. sta opcin lo que hace es realizar un
calentamiento del edificio durante los das indicados para la puesta a punto de la
simulacin.

TimeStep
El ltimo parmetro que se crear dentro de la familia de Simulation Parameters es el
TimeStep el cual significa el nmero de muestras por hora. Aconsejable de 4 a 60: 6 es el
nmero sugerido porque debe ser uniformemente divisible en 60 valores. Se escogen 6
muestras en una hora porque la temperatura es una variable lineal que no tiene variaciones
bruscas. Los valores recomendados incluyen 4, 5, 6, 10, 12, 15, 20, 30, y 60. 6, tambin es
el valor mnimo, ya que con valores inferiores pueden causar inexactitudes.

Figura 88. Simulation Parameters IDF Editor

Figura 89. Timestep IDF Editor

84

Memoria descriptiva

SiteLocation
Seguidamente se dirige hacia la familia de Location and Climate, donde se encuentra el
primer parmetro a completar Site:Location en esta casilla se tendr que escribir un
nombre de la ubicacin del archivo, en nuestro caso como es la INEFC ser la ciudad de
Lleida. Tambin se deber aadir la latitud y la longitud del lugar, sin olvidar la elevacin.
Y para terminar decir que la zona horaria o Time Zone es GMT + 1.

Figura 90. Site:Location IDF Editor

RunPeriod
La siguiente variable de entrada que se incluir ser RunPeriod, sirve para decidir el
nmero de das que se desea realizar la simulacin, es muy importante definirla
correctamente.

Figura 91. RunPeriod IDF Editor

Como campos obligados hay que decir el mes donde se quiere que inicie la simulacin y el
da de inicio, y por supuesto el da y mes de la finalizacin. Otro valor importante es decir
que use el archivo temporal para decidir qu da de la semana empieza la simulacin.
Por lo que respecta a los das de vacaciones y das especiales se deja que tambin sea el
archivo de tiempo el que se encargue de marcarlos. Los das especiales son das como por
ejemplo fiestas nacionales, simulacros de incendios, etc. Son elementos para dar una
mayor realidad a la simulacin.

Material
Posteriormente, se selecciona la familia de parmetros llamada Surface Construction
Elements, en la cual se definir todos los materiales que compondrn nuestro edificio, tanto
las capas de los materiales que constituyen las paredes, tejados, las ventanas, incluso el aire
que haya entre ventanas si se trata de un acristalamiento doble, etc.

85

Memoria descriptiva

Figura 92. Surface Construction Elements IDF Editor

Se selecciona la primera pestaa, la llamada Material, donde se ir aadiendo todos los


materiales, se describir tanto el nombre que tienen, como sus caractersticas, ya sean
rugosidad, densidad, conductividad, grosor, etc.

Figura 93. Material IDF Editor

Como se observa en la imagen, hay que escribir un nombre para cada material, lo mejor es
aadir una breve descripcin de lo que ser, para as una vez aadido se pueda buscar
fcilmente cuando posteriormente se le asigna. Decir que se pueden aadir una gran
cantidad de elementos aunque luego no afectan a la simulacin, simplemente hay que tener
cuidado de no aadir ms de los que se necesitan porque pueden dar lugar a confusin.
Para las caractersticas de absorcin Thermal, Solar and Visible son propiedades radiantes
las cuales dependen del material. Por ejemplo, un metal pulido tiene una absorcin trmica
de 0.3. En cuanto a la absorcin solar los colores oscuros tienen 0.7, por lo contrario, los
claros tienen entre 0.1 y 0.3.

SimpleGlazingSystem & WindowsMaterialGlazing


Ahora se hace referencia al sistema simplificado de acristalamientos SimpleGlazingSystem,
el cual sirve para definir las ventanas de nuestro modelo. Tambin existe un modo ms
detallado que se comentar ms adelante, pero primero el modo simplificado, donde solo
se tiene que aadir un nombre y escribir unas pocas caractersticas globales de acristalado
que se desea colocar.

Figura 94. SimpleGlazingSystem IDF Editor

Este modelo debe ser usado con precaucin. Puede haber diferencias significativas en el
rendimiento entre el sistema simplificado y el habitual modelo ms detallado. Este objeto
de entrada difiere del de otros objetos WindowMaterial en que describe un sistema de

86

Memoria descriptiva

acristalamiento completo en lugar de las capas individuales. Esto se utiliza cuando se tiene
informacin muy limitada sobre las capas de vidrio.
Una vez explicado esto, en nuestro caso, el Cdigo Tcnico de la Edificacin, los valores
caractersticos de los acristalamientos estn muy limitados por lo cual se usa la opcin del
modelo simplificado, donde se aade como se aprecia en la figura 21 los valores obtenidos
en el estudio realizado anteriormente.
Despus de aadir el nombre est el segundo campo, este campo describe el valor UFactor para el sistema de ventanas, o coeficiente de transferencia de calor global. Las
unidades son en W/m2K. Este es el valor de U-factor en condiciones de calefaccin en
invierno. El U-factor se supone que es para los productos montados verticalmente.
Indistintamente a no emplear el modelo detallado para acristalamientos se pasa a comentar
sus caractersticas y la manera de completar sus variables.
Por lo que respecta al WindowMaterial:Glazing, es la versin detallada de acristalamientos
o ventanas. Cuando se habla de ventanas exteriores, la parte delantera es el lado del cristal
que da al exterior y la parte de atrs es el que queda ms cerca de la zona interior, para
ventanas que estn entre zonas, la parte delantera es el lado ms cercano a la zona
adyacente a la zona de la ventana y se define como la parte de atrs como el lado ms
cercano a la zona interior.

Figura 95. Glazing IDF Editor

Si el Optical Data Type es Spectral Average, los valores que introduzcas de transmitancia
y reflectancia son el promedio sobre el espectro solar, y los valores que introduzcas de
transmitancia y reflectancia visible se supone que son el promedio sobre el espectro solar y
se ponderar con la respuesta del ojo humano.
EnergyPlus tiene un banco de datos sobre este tema, donde contiene las propiedades
espectrales de muchos tipos diferentes de vidrio.
Algunas de las opciones curiosas que tiene EnergyPlus respecto a la configuracin de
cristales, es que puedes hacer un cristal translucido, mediante la opcin Solar Diffusing.

87

Memoria descriptiva

Figura 96. Solar Diffusing

WindowMaterialGas
Para terminar de hablar sobre el tema de acristalamientos se muestra a continuacin el
WindowMaterial:Gas. Aqu se habla del tipo de gas que hay en un cristal doble, entre
cristal y cristal.

Figura 97. Gas IDF Editor

Simplemente se indica el nombre, y se dice el tipo de gas, si se abre el desplegable, se


puede observar que se puede elegir entre unos cuantos tipos de gas como por ejemplo el
ms comn que es el aire, el xenn, el argn, etc. Si seleccionas Custom, entonces si que se
debe escribir las caractersticas de tu gas, en caso contrario se deja en blanco.
Otro campo obligado es el del grosor, en este caso se ha hecho una cmara de aire de
12mm que ir entre cristal y cristal. Como en Materials, pueden aadirse muchsimas ms
para tener una mayor variedad y as ajustarte ms a la realidad.

Construction
Para las paredes, techos, pisos, ventanas y puertas, se tiene que ir a la pestaa de
Construction, las construcciones son "construidas" a partir de los materiales incluidos en
Materials. Cada capa de la construccin es un nombre de material que figura en el orden
de afuera a dentro. Puedes incluir hasta diez capas (es una de las pocas limitaciones en
EnergyPlus).
Exterior es la capa que esta mas lejos de la zona (no necesariamente el medio exterior).
Interior es la capa junto a la zona. En la imagen ejemplo de abajo, por ejemplo, la capa
exterior es la baldosa, por debajo del suelo la siguiente capa es el espacio areo sobre el
azulejo, y la capa interior es la cubierta de hormign.

88

Memoria descriptiva

Figura 98. Ejemplo construccin de suelo IDF Editor

Las construcciones de ventanas son igualmente construidas a partir de los elementos de


ventana.

Figura 99. Ejemplo construccin de ventana IDF Editor

Est permitido un mximo de cuatro capas de vidrio y una capa de sombreado. Una capa
de gas siempre tiene que separar las capas de vidrio adyacentes en un sistema multi-panel.

Figura 100. Construction IDF Editor

GlobalGeometryRules
Dentro de la familia o grupo Thermal Zones and Surfaces, se desplaza hasta
GlobalGeometryRules donde se deber explicar en detalle la descripcin de los parmetros
geomtricos para que posteriormente lo utilice EnergyPlus.

89

Memoria descriptiva

Figura 101. GlobalGeometryRules IDF Editor

Con el fin de realizar los clculos de sombreado, la construccin de las superficies debe ser
especificada. EnergyPlus utiliza un sistema de coordenadas cartesianas para la
especificacin de la superficie de vrtice en tres dimensiones (3D). Este sistema de
coordenadas tiene a la derecha el eje X dirigido hacia el Este, el eje Y hacia el norte, y el
eje Z hacia arriba. La siguiente figura muestra lo explicado anteriormente.

Figura 102. Sistema de coordenadas IDF Editor

BuildingSurfaces
Las superficies del edificio se describen en el apartado BuildingSurfaces de manera
detallada.

Figura 103. Building Surfaces IDF Editor

Para la descripcin de las superficies se debe tener en cuenta hacia donde esta encarada la
superficie, para as aadir la mejor opcin, a continuacin se enumera las ms
significativas, dentro del campo Outside Boundary Condition.
El valor puede ser una de estas variables, dependiendo del tipo real de superficie.
Surface si la superficie es la superficie interior, entonces esta es la opcin. El valor o bien
ser una superficie en la zona de base o una superficie en otra zona. El balance de calor
entre dos zonas pueden ser simuladas con precisin mediante la especificacin de una
superficie en una zona adyacente. EnergyPlus simular un grupo de zonas de forma
simultnea e incluir la transferencia de calor entre las zonas.
Sin embargo, ya que esto incrementa la complejidad de los clculos, no es necesario
especificar la zona a menos que las dos zonas tengan una diferencia significativa de
temperatura:

90

Memoria descriptiva

Adiabatic una superficie interna de la misma zona. Fuera de Outside Boundary Condition
pueden dejar lo dems en blanco.
Zone Esto es similar a Surface, pero EnergyPlus crear automticamente la superficie
requerida en la zona adyacente cuando se introduce en la superficie. Si no hay ventanas o
puertas en la superficie, EnergyPlus crea automticamente sub-superficies adecuadas
tambin.
Outdoors Si esta superficie se expone a condiciones de temperatura exterior, entonces
esta es la opcin.
Ground Si la superficie se expone al suelo, entonces esta es la opcin habitual.
Si la superficie est expuesta al sol, entonces el campo SunExposed debe estar activo. De
lo contrario, NoSun debe ser la opcin correcta.
Si la superficie est expuesta al viento, a continuacin, WindExposed debe ser aplicado en
este campo. De lo contrario, NoWind.
Cuando una superficie se especifica con NoWind, esto tiene varias implicaciones. En el
cdigo de balance de calor, esta superficie se pondr por defecto a usar la ASHRAE
simples de conveccin exterior del coeficiente de correlacin con una velocidad de viento
cero.

FrameAndDivider
Una parte fundamental en la creacin real de ventanas es poder insertar marcos o divisores.
Un marco rodea el vidrio en una ventana. Se supone que todas las caractersticas de marco
como el ancho, la conductancia y absorcin solar son los mismos para la parte superior,
inferior y los elementos secundarios del marco.

Figura 104. Frame and divider 1 IDF Editor

EnergyPlus resta automticamente el rea del marco determinado de la pared que contiene
la ventana. As que se ha de tener mucho cuidado en el momento de definir las ventanas,
porque se tendrn que hacerlas teniendo en cuenta el rea del acristalado ms el rea del
marco.

91

Memoria descriptiva

Tambin decir que el marco resta rea a la pared, los divisores restan a la ventana, por lo
que tambin se deber tener mucho cuidado al definirlos, para que el rea resultante tanto
del cristal, el marco o el divisor que se quiera.
Un divisor, como se muestra en la Figura 31, Figura 32 y Figura 33, divide el cristal en
pequeas zonas por separado. Se supone que todos los elementos del divisor tienen las
mismas caractersticas. Si no, se debe ir al campo area-weighted average para darle la
media del conjunto, para as realizar los clculos.

Figura 105. Frame and divider 2 IDF Editor

Dentro de la creacin de divisores, se tiene la opcin Divider Type, la cual da dos tipos de
divisores para implementar en nuestra ventana.
El tipo de separador (ver figura) puede ser:

Figura 106. Frame and divider 3 IDF Editor

Divider Type = Suspended es aplicable nicamente a los cristales de varios paneles. Esto
significa que el divisor est suspendido entre los cristales. Si hay ms de dos capas de
vidrio, se supone que el divisor que se coloca entre las dos capas ms externas.
Divider Type = DividedLite significa que los elementos del separador se proyectan desde
el exterior y el interior de las superficies de los cristales y divide el acristalamiento en
zonas individuales. Para el multi-panel de vidrio, este tipo de divisor tambin tiene entre
los elementos de vidrio un separador.

92

Memoria descriptiva

Una vez explicados los campos ms importantes, solamente queda rellenarlos en su


seccin del IDF Editor de esta manera, aqu se ha hecho un ejemplo de marco simple.

Figura 107. Frame and divider IDF Editor

ZoneVentilation
En cuanto a la ventilacin, es el flujo de aire del ambiente en una zona termal con el fin de
proporcionar una cierta cantidad de refrigeracin no mecnica. En EnergyPlus la
ventilacin puede ser controlada por un programa y mediante la especificacin de mnimo,
mximo y las temperaturas del incremento como se describe a continuacin. Las
temperaturas pueden ser valores constantes para toda la simulacin u horarios que pueden
variar con el tiempo. La ecuacin bsica utilizada para calcular la ventilacin es:

I. Constant Term Coefficient


Este nmero es el parmetro "A" en la ecuacin. Esta parte es especificada por el usuario,
sirve para modificar los parmetros que estn en funcin de factores ambientales.
II. Temperature Term Coefficient
Este nmero es el parmetro "B" de la ecuacin. Este parmetro es modificado por la
diferencia de temperatura entre el aire exterior e interior las temperaturas de bulbo
seco. Las unidades de este parmetro son la inversa de Celsius.
III. Velocity Term Coefficient
Este nmero es el parmetro "C" de la ecuacin. Este parmetro es modificado por la
velocidad del viento que vive fuera del edificio. Las unidades de este parmetro son s/m.
IV. Velocity Squared Term Coefficient

93

Memoria descriptiva

Este nmero es el parmetro "D" de la ecuacin. Este parmetro es modificado por el


cuadrado de la velocidad del viento que vive fuera del edificio. Las unidades de este
parmetro son s2/m2.

Figura 108. Variables de ventilacin

Explicadas la configuracin de las variables de ventilacin, se establece el valor para la


ventilacin de la zona, con un valor de IDA 2 segn RITE, sinnimo de 12.5 litros por
segundo por cada persona en el recinto, en metros cbicos segundo por persona, el valor
asignado es 0.0125 m3/s persona.

HVAC:Thermostat
El termostato permite que los puntos de ajuste puedan ser especificados como una
constante para toda la simulacin o por horarios. Los horarios de referencia deben estar
definidos y el termostato de control debe ser de consigna dual, para tener un mximo y un
mnimo.
Se establecen dos tipos de horarios que nos marcaran el lmite superior e inferior, a
continuacin se muestra en la imagen.

Figura 109. Termostato en IDF editor

Se establecen dos intervalos de temperatura, se toman los meses de otoo e invierno con un
valor de temperatura marcado en la norma UNE 13779 y en el estudio realizado con
anterioridad o = 21 C, y para el intervalo de temperatura de los meses de verano se
establece la temperatura tpico normalizado de o = 26 C.

HVAC:IdealLoadsAirSystem
Este objeto proporciona un sistema ideal para el suministro de aire acondicionado a la zona
que cumple todos los requisitos de carga. Se utiliza para el clculo de la carga, es el primer
paso hacia el modelo realista del edificio. Se define a que zona est asignado el termostato
definido en el apartado anteriormente, posteriormente se podr visualizar la salida tanto de
la temperatura de la zona para comprobar el correcto funcionamiento del termostato, como
el gasto de energa de la carga.

94

Memoria descriptiva

Figura 110. HVAC IdealLoadsAirSystem IDF Editor

Una vez se han introducido todos los objetos comunes que compartirn todas las zonas del
recinto se hace un breve resumen de los valores ms importantes:
I. Se ha establecido la localizacin del recinto.
II. Se aplica una frecuencia de muestreo adecuada de 6 muestras cada hora.
III. Se han introducido los valores de los materiales y las estructuras que formaran el
complejo, segn los datos del estudio del edificio realizado anteriormente.
IV. Se ha establecido la ventilacin por zona marcada por RITE.
V. Se han establecido los intervalos de temperatura para el recinto designado por la
norma UNE EN 13779.

7.2.2.9

Introduccin de parmetros individuales del edificio

En este apartado se explican los objetos que son diferentes para cada tipo de zona del
recinto, como por ejemplo la ocupacin, el nivel de consumo elctrico, etc. Todos los
valores que se han escrito en el archivo IDF son extrados de nuestro estudio del recinto.

Oficinas
A continuacin se introducen los valores caractersticos para las zonas que tienen como
tipo de uso oficinas pequeas. Las zonas son: direccin, secretaria direccin,
subsecretaria de actividades y servicios, subdireccin de estudios, subduccin de
postgrado, gerencia, direccin OA, servicio de reprografa, sala de espera, secretara
administrativa, gestin, y todas las oficinas de la planta superior.
I. Internal gains
No toda la influencia del consumo de energa en el edificio se debe a las condiciones
ambientales. Este grupo de objetos describen otros beneficios internos (personas,
luminaria, equipamiento elctrico).

Figura 111. Ganancia interna

a. People
La declaracin de las personas se utiliza para modelar las condiciones que afectan al
espacio ocupado. Dicha definicin de ocupacin proporciona informacin que puede ser
utilizada para comunicar el confort trmico de un grupo de ocupantes.

95

Memoria descriptiva

Se asignan los parmetros en la seccin, se establece el valor del nmero de personas en


las zonas, se definen como oficinas pequeas, conforme la norma ISO 13779 y el estudio
anteriormente realizado se establece un valor de 10 m2/persona.

Figura 112. Ocupacin

Como perfil de ocupacin se establece el perfil para oficinas, previamente tambin creado
y estudiado en el apartado correspondiente del estudio de caractersticas del edificio.

Figura 113. Horario oficinas

Establecido estos datos, se aade el ltimo elemento, la actividad metablica, una actividad
de 134 W, sinnimo de la actividad de sedentaria en oficinas.

Figura 114. Actividad ocupacin humana

b. Lights
La declaracin de luces permite especificar informacin sobre el sistema de alumbrado
elctrico de una zona, incluido el nivel de diseo de energa y horario de operacin, y
cmo el calor de las luces se distribuye trmicamente.
Una zona puede tener mltiples luminarias declaradas. Por ejemplo, una declaracin puede
describir la iluminacin general de la zona y otro la iluminacin de la tarea. O puedes
utilizar mltiples luces declaradas para una zona que tiene dos o ms sistemas de
iluminacin general, que difieren en el nivel de diseo, programacin, etc.
Se aaden los valores del estudio previo realizado, con un valor de 500 lux, es sinnimo de
un valor por metro cuadrado de 10 W. Se establece ese valor de 10 W y se selecciona el
96

Memoria descriptiva

mismo esquema de ocupacin que el anterior, ya que la ocupacin est ligada con la
iluminacin.

Figura 115. Iluminacin

c. Electric equipment
Posteriormente se aade las cargas internas de equipos elctricos, Equipment Electric. Se
aade el mismo perfil de ocupacin y se selecciona un valor de 10 W/m2.

Figura 116. Equipo elctrico

Salas de reuniones
A continuacin se introducen los valores caractersticos para las zonas que tienen como
tipo de uso sala de reuniones. Las zonas son: Sala de juntas, sala de honor y sala de
audiovisual.
I. Internal gains
a. People
La declaracin de las personas se utiliza para modelar las condiciones que afectan al
espacio ocupado. La definicin de los siguientes efectos bsicos, como proporcionar
informacin que pueda ser utilizada para comunicar el confort trmico de un grupo de
ocupantes.
Se asignan los parmetros en la seccin, se establece el valor del nmero de personas en
las zonas, se defines como salas de reuniones, conforme la norma ISO 13779 y el estudio
anteriormente realizado se establece un valor de 3 m2/persona.

Figura 117. Ganancia interna sala de reuniones

Como perfil de ocupacin se establece el perfil de ocupacin, previamente tambin creado


y estudiado en el apartado correspondiente del estudio de caractersticas del edificio.

97

Memoria descriptiva

Establecido estos datos, se aade el ltimo elemento, la actividad metablica, una actividad
de 134 W, sinnimo de la actividad de reposo sentado.

Figura 118. Actividad metablica sala de reuniones

b. Lights
La declaracin de luces permite especificar informacin sobre el sistema de alumbrado
elctrico de una zona, incluido el nivel de diseo de energa y horario de operacin, y
cmo el calor de las luces se distribuye trmicamente.
Una zona puede tener mltiples luminarias declaradas. Por ejemplo, una declaracin puede
describir la iluminacin general de la zona y otro la iluminacin de la tarea. O puedes
utilizar mltiples luces declaradas para una zona que tiene dos o ms sistemas de
iluminacin general, que difieren en el nivel de diseo, programacin, etc.
Se aaden los valores del estudio previo realizado, con un valor de 500 lux, es sinnimo de
un valor por metro cuadrado de 10 W. Se establece ese valor de 10 W y se selecciona el
mismo esquema de ocupacin que el anterior, ya que la ocupacin est ligada con la
iluminacin.

Figura 119. Iluminacin sala de reuniones

c. Electric equipment
Posteriormente se aade las cargas internas de equipos elctricos, Equipment Electric. Se
aade el mismo perfil de ocupacin y se selecciona un valor de 10 W/m2.

Figura 120. Equipo elctrico sala de reuniones

Restaurantes
A continuacin se introducen los valores caractersticos para las zonas que tienen como
tipo de uso restauracin. Las zonas son: la cafetera y el comedor profesores.
I. Internal gains
98

Memoria descriptiva

a. People
La declaracin de las personas se utiliza para modelar las condiciones que afectan al
espacio ocupado. La definicin de los siguientes efectos bsicos, como proporcionar
informacin que pueda ser utilizada para comunicar el confort trmico de un grupo de
ocupantes.
Se asignan los parmetros en la seccin, se establece el valor del nmero de personas en
las zonas, se definen como restaurantes, conforme la norma ISO 13779 y el estudio
anteriormente realizado se establece un valor de 1.5 m2/persona.

Figura 121. Ocupacin restaurante

Como perfil de ocupacin se establece el perfil de ocupacin, el cual es el perfil para la


restauracin, previamente tambin creado y estudiado en el apartado correspondiente del
estudio de caractersticas del edificio.

Figura 122. Horario restaurantes

Establecido estos datos, se aade el ltimo elemento, la actividad metablica, una actividad
de 134 W, sinnimo de la actividad de reposo sentado.
b. Lights
La declaracin de luces permite especificar informacin sobre el sistema de alumbrado
elctrico de una zona, incluido el nivel de diseo de energa y horario de operacin, y
cmo el calor de las luces se distribuye trmicamente.

99

Memoria descriptiva

Una zona puede tener mltiples luminarias declaradas. Por ejemplo, una declaracin puede
describir la iluminacin general de la zona y otro la iluminacin de la tarea. O se puede
utilizar mltiples luces declaradas para una zona que tiene dos o ms sistemas de
iluminacin general, que difieren en el nivel de diseo, programacin, etc.
Se aaden los valores del estudio previo realizado, con un valor de 200 lux, es sinnimo de
un valor por metro cuadrado de 6 W. Se establece ese valor de 6 W y se selecciona el
mismo esquema de ocupacin que el anterior, ya que la ocupacin est ligada con la
iluminacin.

Figura 123. Iluminacin restaurante

c. Electric equipment

No se establece ningn valor en cuanto a equipamiento elctrico tales como ordenadores o


faxes en las zonas de restauracin, ya que se considera que no existe su uso dentro de
dichas zonas.
Con todas las variables escritas se realiza un breve resumen:
I. Se definen los tipos de zonas dentro del recinto segn la norma UNE EN 13779.
II. Se ha establecido las ganancias internas (ocupacin, luminaria y equipamiento
elctrico) por zona segn marca la norma UNE EN 13779.
Una vez finalizada la simulacin en el Anexo A se encuentran las distintas condiciones del
entorno que se han introducido a travs del programa Energy Plus.

7.2.3

Rediseo del modelo con las mejoras y simulacin

En este apartado se explica la forma de introducir en las condiciones actuales las dos
mejoras, ya sea del acristalamiento doble desde el programa del Energy Plus, como la
mejora del voladizo desde el programa de dibujo como es el Google SketchUp.

7.2.3.1

Acristalamiento doble

Se actualiza el modelo aadiendo ventanas con cristal doble, para realizar este cambio se
debe ir a EnergyPlus y modificar Windows Material Glazing y Construction con la
configuracin siguiente:

Figura 124. Acristalamiento doble desde el IDF editor

100

Memoria descriptiva

En la imagen se observa la ventana de Windows Material Glazing con los dos tipos de
acristalamiento que posee el diseo, el nombrado Sencillo_4mm es el que tiene
actualmente la INEF Lleida y con el cual se simularon las condiciones actuales, por otro
lado se tiene el llamado Doble 4-6-4 que es la mejora propuesta para reducir el gasto
innecesario de energa en la refrigeracin del edificio.
Una vez se tiene creado el acristalamiento de la mejora con sus valores caractersticos
adecuados, se procede a modificar todas las ventanas del modelo mediante Construction
seleccionando que las ventanas tanto exteriores como interiores sern del tipo doble tal y
como se indica en la siguiente figura:

Figura 125. Construccin para el acristalamiento doble en el IDF editor

7.2.3.2

Voladizo

A continuacin se describe como se introdujo la mejora del voladizo, la cual incorpora al


modelo del edificio voladizos con tal de evitar el contacto directo con los rayos del sol
durante los meses de esto.
Una manera sencilla para disminuir la radiacin directa solar en verano sobre la superficie
exterior de las diferentes zonas es realizar salientes que puedan cubrir en verano las
ventanas por donde entra la radiacin.
Primeramente se muestra una imagen del modelo original en su cara Sur, y como los rayos
solares inciden de manera directa en el edificio.

Figura 126. Edificio visto por Google SketchUp

Para realizar este cambio se debe ir a SketchUp a modificar el modelo, aadiendo Shading
Zone, es decir,

, las cuales crearan esos salientes para evitar esos rayos de Sol.

Se cubre con salientes la parte sur, para que cuando amanezca y el sol se ubique en la parte
ms alta del medioda las zonas de sombra puedan entrar en accin cubriendo las ventanas
y evitando as un exceso de calor. Las principales vistas del edificio con la mejora del
voladizo son las siguientes:

101

Memoria descriptiva

Alzado

Figura 127. Vista del alzado con la mejora del voladizo

Planta

Figura 128. Vista de la planta con la mejora del voladizo

102

Memoria descriptiva

Isomtrica

Figura 129. Vista isomtrica de la mejora del voladizo

A continuacin se muestra como queda la zona de oficinas sur con dicha modificacin. En
un primer lugar se muestra la mejora durante el mes de Octubre a las 12:00 h, cuando el
Sol est en su punto ms alto. Se comprueba que con este saliente se cumple lo comentado
en el estudio de mejoras, donde se dijo que en invierno el saliente no impide que los rayos
solares penetren en los recintos aprovechando as para calentar la zona.

Figura 130. Edificio con voladizo Octubre 12:00h

Contrariamente, la simulacin horaria siguiente es del mes de julio a las 12:00 h y se puede
apreciar como el voladizo cumple su funcin a la perfeccin haciendo de escudo contra los
rayos solares e impidiendo el calentamiento excesivo de la zona.

Figura 131. Edificio con voladizo Julio 12:00h

103

Memoria descriptiva

Todos los nuevos clculos de simulacin de los recintos y sus cargas se pueden observar
con todo detalle en el Anexo B.
Con las mejoras realizadas de acristalamiento doble y voladizos, se pasa a comparar los
resultados obtenidos en EnergyPlus tanto para las condiciones actuales como para las
mejoras implementadas.

7.2.4

Anlisis energtico

En este apartado se exponen los resultados obtenidos desde la simulacin mediante


EnergyPlus, es decir, las necesidades del edificio en cada una de las plantas, a partir de las
hojas de clculo que se detallan en las tablas del Anexo.
Como se ha comentado en los anexos esas tablas representan la evolucin horaria mensual,
para calcular la demanda energtica de cada mes y representar esos valores se ha
multiplicado por las horas de funcionamiento mensuales.

7.2.4.1

Resultados de simulacin. Necesidades actuales del edificio

Las condiciones actuales en las que se encuentra el edificio vienen definidas por un cristal
simple de 4 mm. en todas sus ventanas, y ningn elemento que impida proteger las
ventanas de la radiacin solar. stos resultados se utilizarn como referencia ya que
marcarn la lnea con la que se compararn las mejoras simuladas para obtener la mejor
solucin.

Planta 0
Por lo que representa a la planta 0, bajo las condiciones actuales en que se encuentra el
edificio, se ha aadido una tabla donde se muestran los siguientes resultados a lo largo del
ao:

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen Planta 0 (Condiciones normales)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
14,947,758.40
0.00
4,355.15
11,037,937.60
0.00
4,371.94
7,249,571.20
223,905.60
4,389.72
4,359,062.40
814,894.40
4,389.41
1,502,392.00
2,721,144.00
4,320.55
1,584,433.60
3,074,464.00
4,292.45
626,073.60
6,858,636.80
0
0.00
0.00
4,320.83
2,164,163.20
3,236,564.80
4,317.83
2,385,147.20
2,713,363.20
4,344.87
9,592,054.40
229,776.00
4,336.35
14,780,862.40
0.00

Tabla 36. Resumen mensual planta 0 condiciones normales

104

Memoria descriptiva

Anualmente los resultados son:

Anual

Resumen Planta 0 (Condiciones normales)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
70,229,456.00
19,872,768.00

Tabla 37. Resumen anual planta 0 condiciones normales

Como se puede observar el calculo de cargas de calefaccin supone ms de setenta


millones de W, asimismo el calculo de refrigeracin supone una cuarta parte de la
calefaccin. Por lo que respeta al caudal total de ventilacin se aproxima a los 50,000 l/s.
Con la ayuda de una grfica se podr ver de forma ms clara el uso de la calefaccin y la
refrigeracin durante el ao.

Potencia (W) planta 0


16 000 000,00
14 000 000,00
12 000 000,00
10 000 000,00
8 000 000,00
6 000 000,00
4 000 000,00
2 000 000,00
0,00

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 132. Grfica de potencia (W) planta 0

Como se observa en la figura anterior los puntos de potencia ms altos se sitan en los
meses de Enero y Diciembre, ms concretamente en Enero con un valor de 14,947,758.4
W. Por el contrario la potencia mnima (sin tener en cuenta el mes de Agosto ya que la
Universidad no se encuentra operativa) se encuentra en el mes de Julio con un valor de
626,073.6 W. La grfica adquiere una parbola con sus mximos en los extremos y el
mnimo en la parte central. A medida que avanzan los meses existe un descenso de la
potencia de calefaccin en los meses de verano.
Tal y como se puede observar sta grfica es totalmente contraria a la mostrada
anteriormente de calefaccin. La forma geomtrica de la grfica es una parbola con un
mximo en los meses estivales. Partiendo de los meses iniciales del ao en que
prcticamente es 0 e incluso llega a serlo, comienza un crecimiento en el mes de Marzo
con un valor mnimo de 223,905.6 W, sin tener en cuenta los 0 W de los meses de Enero,
Febrero y Diciembre. La potencia mxima de refrigeracin se sita en el mes de Julio con
un valor de 6,858,636.8 W. La demanda de la potencia de refrigeracin es bastante menor
al de la calefaccin.

Planta 1
Paralelamente se hace referencia a la planta superior donde la superficie es menor, la cual
cosa implica una menor demanda.

105

Memoria descriptiva
Resumen Planta 1 (Condiciones Normales)
Mes
Caudal (l/s) Calefaccin (W) Refrigeracin (W)
Enero
4,397.53
2,964,420.80
19,272.00
Febrero
4,355.15
2,030,080.00
41,536.00
Marzo
4,371.94
1,175,115.20
155,620.80
Abril
4,389.72
754,129.60
366,675.20
Mayo
4,389.41
159,366.40
1,054,136.00
Junio
4,320.55
168,334.40
1,059,132.80
Julio
4,292.45
59,827.20
1,906,088.00
Agosto
0
0.00
0.00
Septiembre
4,320.83
230,395.20
1,313,596.80
Octubre
4,317.83
298,182.40
1,083,444.80
Noviembre
4,344.87
1,805,156.80
163,419.20
Diciembre
4,336.35
2,889,387.20
23,483.20
Tabla 38. Resumen mensual planta 1 condiciones normales

Cmo se puede apreciar en la tabla anterior los valores obtenidos son bastante inferiores a
los de la planta inferior, pero como ya se ha comentado, la superficie es menor y, por lo
tanto, necesita una menor potencia para refrigerar y calefactar la zona.
Anualmente los resultados son:

Anual

Resumen Planta 1 (Condiciones normales)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
12,534,395.20
7,186,404.80

Tabla 39. Resumen anual planta 1 condiciones normales

En sta planta la diferencia de potencia de calefaccin y potencia de refrigeracin no es tan


abrumadora como en la planta inferior. El clculo tambin es menor, tanto que son cinco
veces ms grande la planta 0 que la planta 1. Se muestra las grficas de calefaccin y
refrigeracin para ver su evolucin anual.

Potencia (W) planta 1


3500000
3000000
2500000
2000000
1500000
1000000
500000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 133. Grfica de potencia (W) planta 1

En la grfica la forma de la parbola tiene menos pendiente ya que se hace referencia a


nmeros ms pequeos y el cambio en el mes de Agosto es menos arisco. Los puntos

106

Memoria descriptiva

mximos se sitan en los meses de Enero y Febrero, el cual destacan los 2,964,420.8 W en
el primer mes del ao. En el mes de Julio apenas existe calefaccin.
El mximo situado en el sptimo mes del ao rodea prcticamente los 1,920,000 W en su
mes con mximo valor. En los meses donde existe mximo por potencia de calefaccin se
puede contemplar cmo no existe demanda energtica de calefaccin. Hasta el mes de
Mayo crece de forma exponencial, para decrecer a partir de Julio, haciendo excepcin en
Agosto.

Conjunto
A modo resumen se detallan los clculos de cargas de refrigeracin y calefaccin bajo
condiciones actuales del edificio. Dichos resultados sern utilizados para evaluar las
mejoras propuestas, ya que est ser considerado como el escenario base. Resumiendo con
las condiciones normales se adjunta las tablas siguientes:

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen (Condiciones Normales)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
17,912,179.20
19,272.00
4,355.15
13,068,017.60
41,536.00
4,371.94
8,424,686.40
379,526.40
4,389.72
5,113,192.00
1,181,569.60
4,389.41
1,661,758.40
3,775,280.00
4,320.55
1,752,768.00
4,133,596.80
4,292.45
685,900.80
8,764,724.80
0
0.00
0.00
4,320.83
2,394,558.40
4,550,161.60
4,317.83
2,683,329.60
3,796,808.00
4,344.87
11,397,211.20
393,195.20
4,336.35
17,670,249.60
23,483.20

Tabla 40. Resumen mensual condiciones normales

Como es normal el pico por potencia por calefaccin sigue situndose en los meses de
Enero y Diciembre, y por potencia de refrigeracin en el mes de Julio destacando sobre el
mes de Junio.

Potencia (W)
20000000
18000000
16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 134. Grfica de potencia (W) condiciones normales

107

Memoria descriptiva

Finalmente, las necesidades anuales del edificio son:

Anual

Resumen (Condiciones normales)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
82,763,851.20
27,059,172.80
Tabla 41. Resumen anual condiciones normales

En sta tabla se detalla los watios del clculo de cargas total tanto por calefaccin, como
por refrigeracin, adems del caudal total de ventilacin en condiciones normales a lo
largo del ao. La suma de las dos potencias es 109,822,894.4 W anuales.

7.2.4.2

Resultados de simulacin. Acristalamiento doble

La primera de las mejoras propuestas, para reducir el clculo de cargas es la instalacin de


cristal doble en cada una de las ventanas que componen el edificio. El total es de 212.56
m2 de cristal doble en el edificio. Es la primera de las tres mejoras realizadas. sta mejora
incluye un acristalamiento doble de 4 mm. en cada cristal separadas por una cmara de aire
deshidratado de 6 mm. Estos acristalamientos mantienen la temperatura que se necesita en
el interior de una forma correcta y til. El tipo de cristal corresponde a la tipologa 4/6/4
con las siguientes caractersticas.

Planta 0
En referencia a la planta 0 se obtiene la tabla siguiente:
Resumen Planta 0 (Acristalamiento doble)
Mes
Caudal (l/s) Calefaccin (W) Refrigeracin (W)
Enero
4,397.53
14,585,075.20
9,760.00
Febrero
4,355.15
10,876,860.80
52,160.00
Marzo
4,371.94
7,190,128.00
211,755.20
Abril
4,389.72
4,366,632.00
741,896.00
Mayo
4,389.41
1,508,265.60
2,578,395.20
Junio
4,320.55
1,611,193.60
2,928,785.60
Julio
4,292.45
636,553.60
6,567,486.40
Agosto
0
0.00
0.00
Septiembre
4,320.83
2,164,425.60
3,101,758.40
Octubre
4,317.83
2,367,424.00
2,603,740.80
Noviembre
4,344.87
9,434,017.60
211,808.00
Diciembre
4,336.35
14,508,248.00
0.00
Tabla 42. Resumen mensual planta 0 acristalamiento doble

Se observa que en los primeros meses del ao ya no es 0 W la potencia por refrigeracin,


aunque su valor es prcticamente nulo, esto es debido a que la radiacin solar penetra en
las zonas a travs de sus cristaleras, pero con el acristalamiento doble se impide su prdida
hacia el exterior, siendo necesario el uso de refrigeracin.

108

Memoria descriptiva

El pico por potencia de calefaccin es de 14,585,075.2 W, y el pico por refrigeracin es de


6,567,486.4 W. El total anual es el siguiente:

Anual

Resumen Planta 0 (Acristalamiento doble)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
69,248,824.00
19,007,545.60

Tabla 43. Resumen anual planta 0 acristalamiento doble

Una grfica ayuda a ver la evolucin de cada potencia durante el ao.

Potencia (W) planta 0


16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 135. Grfica de potencia (W) planta 0

La forma que adquiere la grfica es de una parbola donde decrece por la parte central. El
mximo est situado en el mes de Enero, superando por pocos vatios la barrera de los
14,400,000 W. En el mes de Julio se obtiene el mnimo de calefaccin con unos 640,000
W.
En el mes de Julio se observa con claridad que se sita el pico de mxima demanda de
refrigeracin con un valor de unos 6,560,000 W destacando con diferencia sobre el resto de
los meses. Tanto en Junio como en Septiembre siguen decreciendo a medida que se va
alejando del mes de Julio. Hasta los inicios del mes de Abril no se observa un ascenso la
carga por refrigeracin en la planta 0.

Planta 1
Los resultados correspondientes a la planta 1, teniendo en cuenta la instalacin de
acristalamiento doble son:
Resumen Planta 1 (Acristalamiento doble)
Mes
Caudal (l/s) Calefaccin (W) Refrigeracin (W)
Enero
4,397.53
2,825,684.80
18,536.00
Febrero
4,355.15
1,894,744.00
44,635.20
Marzo
4,371.94
1,068,616.00
159,721.60
Abril
4,389.72
561,636.80
343,403.20
Mayo
4,389.41
151,694.40
999,280.00
Junio
4,320.55
162,448.00
1,051,881.60
Julio
4,292.45
61,875.20
1,822,969.60
Agosto
0
0.00
0.00

109

Memoria descriptiva
Septiembre
Octubre
Noviembre
Diciembre

4,320.83
4,317.83
4,344.87
4,336.35

217,276.80
310,494.40
1,697,416.00
2,531,520.00

1,289,422.40
1,049,736.00
162,728.00
30,982.40

Tabla 44. Resumen mensual planta 1 acristalamiento doble

A lo largo del ao el caudal total por ventilacin (l/s) es similar en todos los meses. Por
otra parte si se observa la tabla la potencia por calefaccin empieza con el valor mximo de
potencia y desciende hasta llegar al mes de Julio, donde vuelve ascender hasta el mes
anterior de Enero. Los resultados anuales son los siguientes:

Anual

Resumen Planta 1 (Acristalamiento doble)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
11,483,406.40
6,973,296.00

Tabla 45. Resumen anual planta 1 acristalamiento doble

Destaca la demanda de calefaccin por encima de la demanda energtica por refrigeracin.


Una de las razones por lo cual se produce es que uno de los meses ms clidos la
universidad se encuentra cerrada, lo cual contribuye en un descenso considerable.
Se acompaan las grficas de los resultados de calefaccin y refrigeracin dnde se
observa el clculo de cargas a lo largo del ao.

Potencia (W) planta 1


3000000
2500000
2000000
1500000
1000000
500000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 136. Grfica de potencia (W) planta 1

Al principio del ao es cuando existe el pico de potencia con un valor de 2,825,636.8 W. A


partir del mes de Mayo empieza a disminuir de forma considerable hasta ser prcticamente
0. Pasado el octavo mes del ao empieza su ascenso hasta el ltimo mes del ao creciendo
de forma considerable.
En el mes de Julio la potencia de refrigeracin llega a ser de unos 1,824,000 W alcanzados
despus de un ascenso agresivo a partir del mes de Junio. En el mes de Enero y Diciembre
es prcticamente nula la potencia por refrigeracin debido a las bajas temperaturas en las
que se encuentra.

110

Memoria descriptiva

Conjunto
Una vez ya diferenciadas las dos plantas, se unen de forma que se pueda ver un resultado
final con el acristalamiento doble y ver la demanda energtica a lo largo del ao.

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen (Acristalamiento doble)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
17,410,760.00
28,296.00
4,355.15
12,771,604.80
96,795.20
4,371.94
8,258,744.00
371,476.80
4,389.72
4,928,268.80
1,085,299.20
4,389.41
1,659,960.00
3,577,675.20
4,320.55
1,773,641.60
3,980,667.20
4,292.45
698,428.80
8,390,456.00
0
0.00
0.00
4,320.83
2,381,702.40
4,391,180.80
4,317.83
2,677,918.40
3,653,476.80
4,344.87
11,131,433.60
374,536.00
4,336.35
17,039,768.00
30,982.40

Tabla 46. Resumen mensual acristalamiento doble

El clculo de cargas por potencia sigue consumiendo unos setenta millones de vatios. En
cambio la potencia de refrigeracin representa una tercera parte del clculo anual total.
Seguidamente se muestran las grficas anuales del acristalamiento doble de potencia de
calefaccin y refrigeracin del conjunto:

Potencia (W)
20000000
18000000
16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 137. Grfica de potencia (W) acristalamiento doble

El valor mximo se sita en el mes de Enero con un 17,410,720 W situado por encima del
mes de Diciembre con 17,039,680 W anuales.
Y el resumen anual del acristalamiento doble es el siguiente:

Anual

Resumen (Acristalamiento doble)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
80,732,230.40
25,980,841.60
Tabla 47. Resumen anual acristalamiento doble

111

Memoria descriptiva

La demanda por potencia de calefaccin anual es de 80,732,230.40 W y de refrigeracin es


de 25,980,841.6 W, bastante inferior a la demanda por calefaccin. Las dos juntas alcanzan
la cantidad de 106,713,072 W anualmente.

7.2.4.3

Resultados de simulacin. Condiciones actuales y voladizo

La segunda de las mejoras consiste en aadir un voladizo a las condiciones actuales como
son el cristal simple de 4 mm. La finalidad de sta mejora es una reduccin energtica con
ms xito en la parte de refrigeracin. Tras haber tratado con la mejora del acristalamiento
doble se ha propuesto esta mejora. Una de sus caractersticas principales es el rechazo
directo de la radiacin solar durante los meses de verano. La finalidad principal de dicha
mejora es la reduccin en la carga de energa en refrigeracin.

Planta 0
A continuacin se observan los clculos de potencia de calefaccin y refrigeracin a lo
largo del ao. Se iniciar por la planta 0:

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen Planta 0 (Voladizo)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
14,942,720.00
0.00
4,355.15
11,175,200.00
43,040.00
4,371.94
7,380,480.00
164,640.00
4,389.72
4,495,040.00
655,040.00
4,389.41
1,545,600.00
2,509,600.00
4,320.55
1,638,560.00
2,889,760.00
4,292.45
645,120.00
6,550,400.00
0
0.00
0.00
4,320.83
2,216,640.00
2,954,560.00
4,317.83
2,415,040.00
2,502,400.00
4,344.87
9,655,360.00
181,600.00
4,336.35
14,811,200.00
0.00

Tabla 48. Resumen mensual planta 0 voladizo

Es la tabla de la planta inferior del edificio de la INEF de Lleida. Se va mostrando toda la


evolucin a lo largo del ao. Empezando por el primer mes donde se encuentra el pico de
potencia por calefaccin hasta el ltimo mes del ao donde, por unos vatios menos,
tambin posee el ms alto anual seguido del mes de Enero. Por lo que respecta a la
refrigeracin el mes de Julio es el mes ms alto.

Anual

Resumen Planta 0 (Voladizo)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
70,920,960.00
18,451,040.00
Tabla 49. Resumen anual planta 0 voladizo

Esta tabla refleja la demanda total de potencia por calefaccin anual, donde est por debajo
del medio milln de vatios. La refrigeracin es de 18,451,040 W. Todo esto se aprecia con
mejor entendimiento acompaado de las grficas de calefaccin y refrigeracin.

112

Memoria descriptiva

Potencia (W) planta 0


16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 138. Grfica de potencia (W) planta 0 voladizo

El pico del mes de Enero, el cual es el mximo anual, es de 14,942,720 W. Es el punto ms


alto de la parbola que nos da la potencia por calefaccin de la planta 0. Desciende de
forma lineal hasta el mes de Mayo donde adquiere unos vatios que son similares a los de
Septiembre, mes el cual se inicia el ascenso de calefaccin hasta finalizar el ao.
El triangulo superior, la punta del cual se encuentra en el mes de Julio, obtiene un valor de
6,550,400 W destacando sobre el resto del ao. Los meses iniciales del ao apenas tienen
potencia de refrigeracin.

Planta 1
Despus de la planta 0 se hace referencia a la planta 1:

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen Planta 1 (Voladizo)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
3,022,982.40
15,580.80
4,355.15
2,042,532.80
33,099.20
4,371.94
1,210,182.40
137,208.00
4,389.72
654,979.20
289,521.60
4,389.41
178,400.00
866,660.80
4,320.55
190,987.20
977,403.20
4,292.45
70,180.80
1,690,235.20
0
0.00
0.00
4,320.83
264,488.00
1,110,340.80
4,317.83
349,851.20
925,904.00
4,344.87
1,861,540.80
147,940.80
4,336.35
2,835,702.40
45,203.20

Tabla 50. Resumen mensual planta 1 voladizo

Y resumida en una tabla anual de la planta 1 con la mejora del voladizo:

Anual

Resumen Planta 1 (Voladizo)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
12,681,827.20
6,239,097.60
Tabla 51. Resumen anual planta 1 voladizo

113

Memoria descriptiva

En sta planta tambin los meses de Enero y Diciembre destacan con el valor mximo de
potencia por calefaccin anual ya que son los meses de temperaturas ms bajas
adquiriendo valores incluso bajo cero. El mes de Julio es el ms bajo en calefaccin. Por
contra, es el ms alto en potencia de refrigeracin, seguido de Septiembre y despus Junio.
Las grficas de la planta 1 correspondientes con voladizo son las siguientes:

Potencia (W) planta 1


3500000
3000000
2500000
2000000
1500000
1000000
500000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 139. Grfica de potencia (W) planta 1 voladizo

Cada vez adquiere ms forma de parbola sin destacar con ningn pico que hace ms
simtrica la grfica. El mximo se sita en el mes de Enero con un valor casi de 19,000 W,
descendiendo hasta los 77,280 W del mes de Julio. A partir de Septiembre vuelve ascender
hasta los 2,835,680 W del mes de Diciembre.
En la primera rea de la figura iniciada desde Enero hasta Agosto, mes no operativo de la
universidad, la figura asciende hasta los 1,690,080 W del mes de Julio, seguidamente
empieza el descenso. El siguiente valor con ms fuerza es en el mes de Septiembre con
casi 1,120,000 W de potencia por refrigeracin situado por detrs del mes de Julio.

Conjunto
Despus de mostrar las potencias de calefaccin y refrigeracin de las dos plantas, se
adjuntan en unas tablas y grficas en que dan una idea aproximada del edifico con
voladizo.

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre

Resumen (Voladizo)
Caudal (l/s) Calefaccin (W)
4,397.53
17,965,702.40
4,355.15
13,217,732.80
4,371.94
8,590,662.40
4,389.72
5,150,019.20
4,389.41
1,724,000.00
4,320.55
1,829,547.20
4,292.45
715,300.80
0
0.00
4,320.83
2,481,128.00

Refrigeracin (W)
15,580.80
76,139.20
301,848.00
944,561.60
3,376,260.80
3,867,163.20
8,240,635.20
0.00
4,064,900.80

114

Memoria descriptiva
Octubre
Noviembre
Diciembre

4,317.83
4,344.87
4,336.35

2,764,891.20
11,516,900.80
17,646,902.40

3,428,304.00
329,540.80
45,203.20

Tabla 52. Resumen mensual voladizo

Esta tabla engloba las dos plantas sumadas y divididas por potencia de calefaccin y por
potencia de refrigeracin en dos columnas. Como no poda ser diferente, los meses que
ms destacan por potencia de calefaccin siguen siendo Enero y Diciembre, y por el
contrario, de refrigeracin destaca Septiembre por detrs del mes de Julio.
El resumen anual es el siguiente:

Anual

Resumen (Voladizo)
Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
83,602,787.20
24,690,137.60
Tabla 53. Resumen anual voladizo

Con el voladizo la potencia de calefaccin es de 83,602,787.20 W, superando el medio


milln de W con creces. Por lo que respeta a la refrigeracin, el calculo de cargas se tasa
en 24,690,137.60 W anualmente. La finalidad de la mejora del voladizo era una reduccin
de la potencia por refrigeracin anualmente. La suma de las dos potencias es de
108,292,924.8 W.
La grfica por potencia de calefaccin anual con voladizo en condiciones normales es la
siguiente:

Potencia (W)
20000000
18000000
16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 140. Grfica de potencia (W) voladizo

El pico del mes de Enero llega alcanza los 13,440,000 W como punto ms alto de la
grfica. El mes de diciembre est un poco por debajo con 17,600,000 W donde apenas se
aprecia la diferencia. En el mes de Junio, Julio y Septiembre alcanza los valores mnimos.
La pendiente que empieza a crecer con agresividad a partir del mes de Junio obtiene un
valor mximo de 8,240,480 W, seguidamente desciende hasta 0 W en el mes de Agosto.
Pero en el mes de Septiembre asciende hasta el segundo puesto con valor mximo de
4,064,800 W.

115

Memoria descriptiva

7.2.4.4

Resultados de simulacin. Acristalamiento doble y voladizo

Es la tercera y ltima mejora. sta mejora es una mezcla de ambas mejoras anteriormente
explicadas. Consiste en un acristalamiento doble (4-6-4) combinado con voladizos situados
en la cara sur del edificio. Se puede decir que es el ms completo, solo queda mirar si es el
ms efectivo hablando del ahorro de energa al cabo del ao.

Planta 0
Una vez explicado en qu consiste la mejora mixta se va a empezar por la planta 0:

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen Planta 0 (Mixta)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
14,641,510.40
0.00
4,355.15
10,961,388.80
36,113.60
4,371.94
7,287,534.40
147,966.40
4,389.72
4,475,276.80
620,924.80
4,389.41
1,537,964.80
2,419,316.80
4,320.55
1,642,217.60
2,791,763.20
4,292.45
648,993.60
6,331,542.40
0
0.00
0.00
4,320.83
2,210,772.80
2,855,545.60
4,317.83
2,397,940.80
2,417,449.60
4,344.87
9,490,937.60
170,248.00
4,336.35
14,526,931.20
0.00
Tabla 54. Resumen mensual planta 0 mixta

En la tabla de la planta 0 se puede observar en el mes de Enero como adquiere el mximo


anual con 14,641,440 W, mientras que en el mes de Julio es todo lo contrario, adquiere el
valor mnimo con 640,000 W. El resumen anual de la planta 0 es el siguiente:

Anual

Resumen Planta 0 (Mixta)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
69,821,468.80
17,790,870.40
Tabla 55. Resumen anual planta 0 mixta

La potencia por calefaccin sigue siendo con creces inferior al medio milln, mientras que
la potencia por refrigeracin es un poco superior a los 16,000,000 W. Dichas tablas son
acompaadas por unas grficas que muestran la evolucin de la potencia de calefaccin y
refrigeracin a lo largo del ao:

116

Memoria descriptiva

Potencia (W) planta 0


16000000
14000000
12000000
10000000
8000000
6000000
4000000
2000000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 141. Grfica de potencia (W) planta 0 mixta

Con la grfica anterior no se puede aprecia con gran exactitud donde se encuentra el
mximo valor de potencia por calefaccin, ya que se diferencian de 11,937,920 W y en una
grfica con un rango de 0 a 16,000,000 W no se puede apreciar con tal exactitud. Enero
destaca con los 14,641,440 W.
En el mes de Julio se sita el pico mximo de potencia por refrigeracin con un valor muy
prximo a los 6,400,000 W. Seguidamente estn Junio y Septiembre con una diferencia de
ms de 3,200,000 W.

Planta 1
Una vez mostradas los datos y grficas de la planta 0, se mostraran los de la planta 1.

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre
Noviembre
Diciembre

Resumen Planta 1 (Mixta)


Caudal (l/s) Calefaccin (W) Refrigeracin (W)
4,397.53
2,908,081.60
16,139.20
4,355.15
1,933,892.80
33,520.00
4,371.94
1,145,600.00
139,360.00
4,389.72
627,568.00
296,088.00
4,389.41
171,984.00
880,171.20
4,320.55
187,350.40
992,000.00
4,292.45
68,656.00
1,696,156.80
0
0.00
0.00
4,320.83
255,723.20
1,127,892.80
4,317.83
332,280.00
929,315.20
4,344.87
1,876,100.80
156,900.80
4,336.35
2,803,313.60
49,419.20
Tabla 56. Resumen mensual planta 1 mixta

En la planta 1, como en la otra planta, en el mes de Enero se observa el mximo en


potencia por calefaccin, casi junto a Enero est situado el mes de Diciembre. El resto de
meses se encuentran bastante diferenciados en cuanto a potencia por calefaccin.
Anualmente es la siguiente tabla:

117

Memoria descriptiva
Resumen Planta 1 (Mixta)
Caudal (l/s) Calefaccin (W) Refrigeracin (W)
47,836.63
12,310,550.40
6,316,963.20

Anual

Tabla 57. Resumen anual planta 1 mixta

Se puede ver que lo que pertenece a la potencia por refrigeracin representa


aproximadamente la mitad de la potencia total anualmente en la planta 1 con la mejora
mixta. La grfica de la calefaccin es la siguiente:

Potencia (W) planta 1


3500000
3000000
2500000
2000000
1500000
1000000
500000
0

Potencia por calefaccin (W)

Potencia por refrigeracin (W)

Figura 142. Grfica de potencia (W) planta 1 mixta

En el mes de Enero se puede ver como sobrepasa un poco los 2,880,000 W, mientras que el
mes de Enero queda un poco por debajo de esa barrera, aproximadamente 76,800 W. En el
mes de Mayo ya comienza el descenso hasta tener valor nulo en el mes de Agosto.
Simtricamente en el mes de Septiembre ya empieza a crecer hasta Diciembre con fuerza.
Des de el mes de Marzo hasta Junio hay un notable ascenso de la carga. En el mes
siguiente sube con una pendiente pronunciada hasta conseguir el mximo de 1,696,000 W.
El mes de Diciembre se diferencia de ms de 480,000 W. El mes de Junio y Octubre tienen
valores semejantes.

Conjunto
Ya diferenciadas las dos plantas, se ha de hablar del conjunto.

Mes
Enero
Febrero
Marzo
Abril
Mayo
Junio
Julio
Agosto
Septiembre
Octubre

Resumen (Mixta)
Caudal (l/s) Calefaccin (W)
4,397.53
17,549,592.00
4,355.15
12,895,281.60
4,371.94
8,433,134.40
4,389.72
5,102,844.80
4,389.41
1,709,948.80
4,320.55
1,829,568.00
4,292.45
717,649.60
0
0.00
4,320.83
2,466,496.00
4,317.83
2,730,220.80

Refrigeracin (W)
16,139.20
69,633.60
287,326.40
917,012.80
3,299,488.00
3,783,763.20
8,027,699.20
0.00
3,983,438.40
3,346,764.80

118

Memoria descriptiva
Noviembre
Diciembre

4,344.87
4,336.35

11,367,038.40
17,330,244.80

327,148.80
49,419.20

Tabla 58. Resumen mensual mixto

Si se habla de la potencia de calefaccin destacan los meses de Enero y Diciembre,


inicialmente de lgica ya que son los meses de ms fro durante el invierno. Le siguen
Febrero y Noviembre aunque con una buena diferencia de vatios. Con la refrigeracin
destaca Julio, con unos 8,000,000 W, el doble que los meses de Junio y Septiembre. En
global:

Anual

Resumen (Mixta)
Caudal (l/s) Calefaccin (W)
47,836.63
82,132,019.20

Refrigeracin (W)
24,107,833.60

Tabla 59. Resumen anual mixta

El clculo de carga de la potencia por calefaccin supera el medio milln de vatios,


mientras que la potencia por refrigeracin es algo ms de una tercer parte de la potencia
por calefaccin. La suma en global es de 106,239,852.8 W. Con esta mejora la finalidad es
reducir el clculo de carga trmica por refrigeracin gracias al voladizo, y reducir la
calefaccin gracias al acristalamiento doble, el cual asla la temperatura del interior del
exterior.
Las grficas de calefaccin y refrigeracin acogen la misma forma que las anteriores,
sobretodo, ms parecida a la mejora del acristalamiento doble:

Figura 143. Grfica de potencia (W) mixta

En Enero se encuentra el mximo con un valor cercano a los 17,600,000 W, la mitad de la


ltima divisin de la grfica. Diciembre se encuentra muy cercano, pero hablando de vatios
se diferencian en algo ms de 160,000 W.
Se puede ver que el valor del mes de Julio pasa un poco por encima de los 8,000,000 W, de
la misma manera que en el mes de Octubre pasar tambin un poco por encima de los
3,200,000 W, donde los meses de Mayo, Junio y Septiembre se encuentran por encima.

119

Memoria descriptiva

7.2.4.5

Comparativa de
acristalamiento doble

resultados.

Condiciones

actuales

A continuacin se expone una comparativa entre los resultados de las condiciones actuales
y los resultados de la primera mejora del edificio referente al acristalamiento doble. Una
vez observados los resultados de simulacin anteriores se crean las distintas graficas que
ayudaran a ver la diferencia entre ambos.

Figura 144. Grfica de potencia de calefaccin (W ) comparativa C.N. y A.D

En la figura anterior se observa una reduccin de la potencia por calefaccin durante todo
el ao, el clculo total anual de las condiciones actuales es de 82,763,851.2 W, y por lo que
respeta a la mejora del acristalamiento doble adquiere un total anual de 80,732,230.4 W.
Con la mejora del acristalamiento se consigue un ahorro del 2.46 % anualmente.

Figura 145. Grfica de potencia de refrigeracin (W) comparativa C.N. y A.D

En la figura anterior representa el clculo anual de la potencia por refrigeracin entre las
condiciones actuales y la mejora del edificio con acristalamiento doble. El total en las
condiciones actuales es de 27,059,172.8 W y con la mejora del acristalamiento doble
(A.D.) es de 25,980,841.6 W cosa que representa un ahorro del 4% anual.
Mediante las grficas anteriores no se pueden apreciar los detalles a nivel mensual de
manera clara, ya que el rango de potencia es muy amplio. Por lo tanto, se acota el rango del

120

Memoria descriptiva

grfico y se crean las grficas siguientes donde se muestran los meses de mxima demanda
de potencia tanto de calefaccin y refrigeracin.

Figura 146. Grfica de potencia de calefaccin (W) comparativa picos C.N. y A.D

En el mes de Enero se sitan los dos picos de mxima potencia. Por lo que respecta a
nmeros existe una diferencia de 501,419.2 W de potencia por calefaccin entre los
resultados del edificio en condiciones actuales y el edificio con acristalamiento doble,
hecho que representa un ahorro del 2.8 % durante el mes de Enero. Por otro lado, el mes de
Diciembre, donde sus caractersticas son similares al mes de Enero, existe un ahorro del
3.56 % entre la potencia por calefaccin en condiciones actuales y la potencia por
calefaccin del edificio con la mejora del acristalamiento doble, que traducido a vatios es
630,481.6 W.

Figura 147. Grfica de potencia de refrigeracin (W) comparativa picos C.N. y A.D

La figura anterior muestra el mes de Julio el cual es el mes de mxima demanda por
potencia de refrigeracin. Entre los valores de potencia de refrigeracin en condiciones
actuales y la mejora del edificio con acristalamiento doble existe una diferencia de
374,268.8 W que representa un 4.28 % de ahorro.
Como se ha dicho en la teora, con la mejora del acristalamiento doble se busca un ahorro
ms amplio en cuanto a la potencia de calefaccin que a la potencia por refrigeracin, ya

121

Memoria descriptiva

que mantiene de forma ms efectiva la temperatura en su interior. El % tiene un valor ms


bajo pero se est hablando de un rango ms amplio en la potencia de calefaccin.

7.2.4.6

Comparativa de resultados. Condiciones actuales y voladizo

La siguiente comparativa hace referencia a los resultados de la simulacin del edificio en


condiciones actuales y a los resultados de la simulacin de la mejora del edifico con
voladizo. Se muestran en las grficas siguientes mediante un grfico de barras que ayuda
visualmente a la comparacin entre ambas.

Figura 148. Grfica de potencia de calefaccin (W) comparativa C.N. y Voladizo

En la figura anterior se muestra la comparativa de la potencia de calefaccin entre las


condiciones actuales y la mejora del edificio con voladizo. El calculo total en las
condiciones normales por potencia de calefaccin es de 82,763,851.2 W, mientras que para
la mejora del voladizo la potencia por calefaccin anual es de 83,602,787.2 W. Con la
mejora del voladizo se observa que existe un incremento de 838,936 W, que representa un
1.01 % sobre las condiciones normales en las que se encuentra el edificio.

Figura 149. Grfica de potencia de refrigeracin (W) comparativa C.N. y Voladizo

En la figura anterior se muestra la grfica comparativa de la potencia de refrigeracin entre


las condiciones normales y la mejora del edificio con voladizo. La diferencia es ms
apreciable que en la figura 18. El clculo total de la potencia por refrigeracin de las
122

Memoria descriptiva

condiciones normales es de 27,059,172.8 W anuales, por el contrario, con la mejora del


edificio con voladizo es de 24,690,137.6 W anuales. Con la mejora del voladizo se reduce
en 2,369,035.2 W, representando un 8.75 %, un alto porcentaje respecto los porcentajes
anteriores en la potencia por refrigeracin.
Con las grficas anteriores se muestran con un rango menor los valores mximos para cada
potencia a lo largo del ao, reducindolos al mes cuyo valor es el mximo anual.

Figura 150. Grfica de potencia de calefaccin (W) comparativa picos C.N. y Voladizo

Durante los meses de Enero y Diciembre se aprecia una diferencia entre ellas. El valor
mximo en el mes de Enero en condiciones normales es de 17,912,179.2 W, siendo inferior
a los 17,965,702.4 W del mes de Enero para la mejora del edificio con voladizo. La
diferencia es de 53,523.2 W, una diferencia pequea que representa el 0.3% de la potencia
de calefaccin en condiciones normales sobre la mejora del voladizo. Durante el mes de
Diciembre, como se observa en la grfica la diferencia aun es menor, por lo que respecta a
la potencia es de 23,347.22 W, 0.14 % sobre la mejora del voladizo.

Figura 151. Potencia de refrigeracin (W) comparativa picos C.N. y Voladizo

En la figura anterior la diferencia en la potencia por refrigeracin es ms apreciable que en


figuras anteriores. El valor de la potencia por refrigeracin durante el mes de mxima
potencia como es el mes de Julio es de 8,764,724.8 W, diferencindose de 524,089.6 W

123

Memoria descriptiva

con la potencia de refrigeracin de la mejora del edificio con voladizo. Dicha mejora
representar un ahorro de 6% sobre las condiciones actuales.
Con la mejora del edificio con voladizo se ha visto que en la grfica de calefaccin apenas
existe una variacin importante en el clculo de energa. Por el contrario, con la energa
por potencia de refrigeracin se puede observar una gran diferencia con la mejora anterior,
ya que el voladizo reduce la penetracin de radiacin solar dentro del edifico, haciendo
necesaria una menor demanda energtica por refrigeracin.

7.2.4.7

Comparativa de resultados. Voladizo y acristalamiento doble

La siguiente comparativa hace referencia a las dos mejoras del edificio por separado. La
figura siguiente representa la comparacin de la demanda de calefaccin de las dos
mejoras a lo largo del ao.

Figura 152. Grfica de potencia de calefaccin (W) comparativa Voladizo y A.D.

Como anteriormente se ha realizado la comparativa de ambas mejoras sabiendo la


demanda anual se busca la diferencia que existe entre ellas. Con la mejora del
acristalamiento doble se consume una potencia por calefaccin de 80,732,230.4 W y con la
mejora del voladizo se consumen 83,602,787.2 W anuales. La diferencia que existe entre
ellas es de 2,870,556.8 W respeto el acristalamiento doble del voladizo y representa un
3.34%.

124

Memoria descriptiva

Figura 153. Grfica de potencia de refrigeracin (W) comparativa Voladizo y A.D.

La figura anterior representa la comparativa entre la mejora del voladizo y la mejora del
acristalamiento doble en cuanto a la potencia por refrigeracin. El clculo de carga anual
de la mejora del acristalamiento doble es de 25,980,841.6 W y el calculo de carga anual de
la mejora del voladizo es de 24,690,137.6 W. La diferencia es de 1,290,704 W, es decir, un
5% de ahorro anual en la potencia por refrigeracin.
Con las grficas anteriores no se aprecia con claridad la diferencia mensual entre las dos
mejoras realizadas debido a los altos valores de potencia, por ello se aaden las grficas
siguientes que ayudan a diferenciarse.

Figura 154. Grfica de potencia de calefaccin (W) comparativa picos Voladizo y A.D.

En el mes de Enero se sitan los dos picos de mxima potencia. En cuanto a valores existe
una diferencia de 554,990.4 W de potencia por calefaccin entre la mejora del edificio con
voladizo y la mejora del edificio con acristalamiento doble, hecho que representa un ahorro
del 3.09 % durante el mes de Enero. Por otro lado, el mes de Diciembre, donde sus
caractersticas son similares al mes de Enero, existe un ahorro del 3.45 % entre ambas
mejoras, que traducido a vatios es 607,134.4 W.

125

Memoria descriptiva

Figura 155. Grfica de potencia de refrigeracin (W) comparativa picos voladizo y A.D.

La figura anterior muestra el mes de Julio el cual es el mes de mxima demanda por
potencia de refrigeracin. Existe una diferencia entre la potencia de refrigeracin de la
mejora del edificio con acristalamiento doble y potencia de refrigeracin de la mejora del
edificio con voladizo de 149,820.8 W que representa un 1.79 % durante el mes de Julio.
Como conclusin se puede ver que el voladizo aporta ms potencia por calefaccin, eso se
debe a que al provocar la sombra por el voladizo se calienta menos la zona, y por lo tanto
en los meses de invierno tiene que hacer un uso mayor de la potencia por calefaccin para
ambientar la zona en concreto. En cambio, el acristalamiento doble mantiene de forma ms
efectiva la temperatura en su interior.

7.2.4.8

Comparativa de resultados. Condiciones actuales y ambas


mejoras

Esta comparativa hace referencia a los resultados de las condiciones actuales del edificio y
a los resultados de las dos mejoras del edificio juntas.

Figura 156. Grfica de potencia de calefaccin (W) comparativa C.N. y Mixta

En la figura anterior se muestra la grafica de comparativa de calefaccin, sabiendo la


demanda anual se busca la diferencia que existe entre ellas. En condiciones actuales del

126

Memoria descriptiva

edifico se calcula una potencia por calefaccin de 82,763,851.2 W y con las mejoras del
edificio de voladizo y acristalamiento doble obtenemos 82,132,019.2 W anuales. La
diferencia que existe entre ellas es de 631,832 W respeto a las condiciones actuales y
representa un 0.21% de ahorro de carga trmica de calefaccin anual.

Figura 157. Grfica de potencia de refrigeracin (W) comparativa C.N. y Mixta

En la figura anterior se realiza la comparativa de los valores por refrigeracin a lo largo del
ao, marcando una demanda anual en condiciones actuales del edificio de 27,059,172.8 W,
y con un valor de 24,107,833.6 W para ambas mejoras del edificio, resultando un ahorro de
2,951,339.2 W con ambas mejoras, hecho que representa un ahorro energtico anual del
10.91 %.
Como no se aprecia con exactitud la diferencia que existe entre las condiciones normales y
la unin de ambas mejoras del edificio, se ha procedido a acotar el rango del eje de la
potencia para poder ver con ms claridad la diferencia en sus valores mximos mensuales.

Figura 158. Grfica de potencia de calefaccin (W) comparativa picos C.N. y Mixta

En la figura anterior se han adjuntado en una grfica los dos meses con valores ms
significativos de potencia por calefaccin. Enero contiene un valor ms alto que el mes de
Diciembre. Por lo que respeta a las condiciones normales en el mes de Enero tiene una
demanda de energa por calefaccin de 17,912,179.2 W, 362,587.2 W por encima del mes
de Enero para la mejora mixta, es decir, con la mejora se obtiene un ahorro de 2.03 %.
Como ltimo mes del ao se tiene un calculo de 17,670,249.6 W, y con ambas mejoras
17,330,244.8 W. Tienen una diferencia de potencia de calefaccin de 2,125.03 W,
127

Memoria descriptiva

representado un 1.93 % de ahorro con la mejora respeto las condiciones normales en las
que se encuentra el edificio.

Figura 159. Grfica de potencia de refrigeracin (W) comparativa picos C.N. y Mixta

En la figura anterior se observa una gran diferencia entre la potencia por refrigeracin de
las condiciones normales y la potencia por refrigeracin con ambas mejoras. Con la mejora
mixta existe un ahorro de 737,025.6 W, es decir, un ahorro energtico anual del 8.41 %
durante el mes de Julio.
Como conclusin a la ltima comparativa se puede decir que por un lado, con la mejora del
edificio del voladizo se obtiene una reduccin de la potencia por refrigeracin, y por otro
lado, con la mejora del edificio con acristalamiento doble se obtiene una reduccin de la
potencia por calefaccin, por el contrario, la potencia por calefaccin que se ahorra es muy
pequea, casi inapreciable. Esto es debido a que con el voladizo los meses de invierno la
zona recibe menos radiacin solar, por lo tanto, tarda ms tiempo en calentar la zona o
recinto.

7.2.5

Optimizacin energtica

De los estudios comparativos analizados en el apartado anterior, se desprende la solucin


que verifica el objetivo del proyecto: garantizar el clculo de cargas ptimo de un edificio.
Los resultados obtenidos para cada una de las propuestas de mejora, anteriormente
evaluados, se resumen en la tabla siguiente, donde se detalla el decremento del calculo
energtico respecto la situacin o escenario base que corresponde a las condiciones
constructivas y de aclimatacin actuales del edificio.
Esto es:
Tipo
Calefaccin
Refrigeracin
Total

A.D.
Voladizo
Mixta
2,031,620.80 W -2.46%
838,936.00 W
-1.01%
631,832.00 W
-0.21%
1,078,331.20 W -4.00% 2,369,035.20 W -8.75% 2,951,339.20 W -10.91%
3,109,952.00 W -6.46% 3,207,971.20 W -9.76% 3,583,171.20 W -11.12%
Tabla 60. Comparativa potencia respecto condiciones actuales

128

Memoria descriptiva

Los resultados obtenidos muestran que la mejor opcin para reducir el clculo de carga de
potencia de calefaccin es la sustitucin de cristales convencionales por el acristalamiento
doble, que incluye una cmara de aire en su espacio interior. Por otra parte, tambin se
observa en la tabla que, en cuanto refiere al clculo de cargas trmicas por refrigeracin la
solucin que presenta ms ventajas respecto las dems propuestas es la combinacin entre
acristalamiento doble y la incorporacin de voladizos, concretamente en la fachada sur del
edificio. Con esta ltima propuesta se reduce el clculo de la carga trmica por
refrigeracin en ms de un 10%.
Finalmente, si analizamos la reduccin total de ambas cargas trmicas (calefaccin y
refrigeracin), la mejor opcin en trmino de reduccin energtica es instalar cristal doble
en todas las ventanas del edificio y adems instalar voladizos en la fachada sur del edificio,
es decir, la propuesta que combina las dos anteriores. En ltimo lugar, se encuentra la
instalacin de cristal doble, producindose un decremento prximo al 6.5%. Sin embargo,
esta alternativa se presenta como la mejor opcin para reducir la demanda trmica de
calefaccin, como ya se adelant anteriormente. Cabe mencionar que para poder
determinar la alternativa ptima para reducir el clculo energtico tiene que ser contrastada
con un estudio de viabilidad econmica, ya que en este apartado nicamente se evala la
solucin teniendo en cuenta aspectos tcnicos, que para este caso particular, sera la
alternativa mixta.
Una conclusin que se desprende de este estudio energtico es que la instalacin de cristal
doble tiene mayor utilidad para reducir el calculo de cargas por calefaccin mientras que
los voladizos permiten mejorar el ahorro energtico por refrigeracin ya que este ltimo
evita que los rayos emitidos por el sol penetren en el interior de los edificios reducindose
as el incremento de la temperatura interior, sobre todo en los meses estivales.

7.3

Instalacin del sistema de climatizacin con CYPE Ingenieros

CYPE Ingenieros es un programa creado para crear y disear generalmente en Espaa,


donde sus clculos estn relacionados con reglamentaciones espaolas como por ejemplo
el CTE (Cdigo Tcnico de la Edificacin) o RITE (Reglamento de Instalaciones Trmicas
de los Edificios) y normativas europeas.
Adems de realizar el clculo de cargas, el cual debe cumplir las normativas adecuadas
marcadas por Espaa y Europa, posee un software capaz de realizar una instalacin
completa de climatizacin, donde se introducen desde las unidades exteriores de
climatizacin hasta las unidades interiores difusoras y las redes de conductos entre ellas,
todo ello adems se complementa con una interfaz grafica orientativa la cual nos avisa si
en algn tramo del proceso de creacin de la instalacin hemos infringido alguna
normativa vigente. CYPE Ingenieros, es tambin una empresa con ms de 25 aos de
experiencia en arquitectura, ingeniera y construccin que ofrece un software adaptado a
las necesidades de los profesionales del sector. Compaginan una intensa actividad en el
terreno de la ingeniera y el clculo de estructuras con la investigacin en el campo del
desarrollo informtico. Como resultado de este trabajo, CYPE Ingenieros es hoy en da
lder dentro del sector del software aplicado a la ingeniera, la arquitectura y la
construccin gracias al xito de sus programas.
CYPE Ingenieros conoce a fondo la realidad y eso se nota en sus programas, debido a su
gran actividad y uso, CYPE Ingenieros cuenta con una slida experiencia en la prctica del

129

Memoria descriptiva

clculo y la ingeniera, con ms de 6.500 proyectos y 45 millones de metros cuadrados de


estructuras calculadas, entre ellos el edificio ms alto de Espaa, el hotel Bali III de
Benidorm. Gracias a la colaboracin con las ms importantes constructoras, OCT
(Organismo de Control Tcnico) y estudios profesionales, se mantiene al corriente de los
nuevos mtodos de trabajo para actualizar sus productos de una forma peridica y efectiva.
Tambin participa en proyectos de colaboracin con asociaciones de reconocido prestigio,
como la Associaci de Consultors d'Estructures o la Asociacin de Investigacin de las
Industrias de la Construccin (AIDICO). La constante atencin al cliente son valores que
han reforzado a CYPE Ingenieros como empresa de software tcnico dirigido a los
profesionales de los sectores de la arquitectura, de la ingeniera y de la construccin. Esta
lnea de progreso al servicio de los clientes les ha llevado a ser la primera empresa
espaola del sector que obtiene la Certificacin ISO 9002, y ha ratificado la eficacia de su
sistema de calidad. CYPE Ingenieros obtiene tambin la certificacin de su Sistema de
Gestin de Calidad, auditado por Bureau Veritas Quality International y aprobado
siguiendo los requisitos establecidos por la norma ISO 9001:2000.

7.3.1

Tipos de climatizaciones

Existen cuatro sistemas diferentes para climatizar desde el punto de vista de que elemento
llega al local a climatizar.
Los sistemas son los siguientes:
Aire aire: el aire es utilizado para compensar las cargas trmicas en un recinto
climatizado, en el cual no recibe ningn tratamiento posterior, es decir, es capaz de
controlar las renovaciones de aire y la humedad del entorno mediante conductos que hacen
circular aire. Este elemento citado se denomina UTA, mueve aire el cual impulsamos o
retornamos modificando sus propiedades convenientemente.
Agua agua: son sistemas donde el encargado de compensar las cargas trmicas de los
recintos a climatizar es el agua. Estos sistemas son los de tipo de calefaccin por
radiadores o suelo trmico.
Aire agua: se trata de sistemas en que el recinto a climatizar llegan los dos elementos,
aire y agua, para as compensar las cargas de cada local. Es decir, cada uno de los
elementos puede aclimatar por medios diferentes la temperatura del recinto.
En el presente proyecto tratamos un edificio de publica concurrencia y deber cumplir
estrictamente la normativa vigente de RITE, el sistema mas indicado es el sistema aire
aire.

7.3.2

Tipos de UTA

Las unidades de tratamiento de aire se pueden configurar de muchas maneras de manera


que se pueda obtener los diferentes objetivos que se planteen, es decir, dependiendo de la
manera que se fabriquen tendrn propiedades para realizar objetivos diferentes.
Seguidamente se procede a observar las configuraciones ms utilizadas donde se vern
desde las ms sencillas hasta las ms sofisticadas.

130

Memoria descriptiva

La configuracin mas sencilla que se puede crear es la que solamente realiza un filtraje del
aire que queremos introducir al recinto mediante los intercambiadores de fri y calor. Esta
configuracin queda descartada ya que no se cumple la normativa de renovaciones de aire
que exige RITE.

Figura 160. Configuracin 1

La segunda configuracin aade un nuevo conducto el cual esta directamente conectado


con el exterior, en el caso que debamos introducir aire nuevo esta nueva va de acceso nos
facilitara el aire exterior adecuado. Esta solucin no es buena, ya que la UTA no se encarga
de la extraccin del aire de los recintos, con lo cual provocara que el aire interior se vicie.
En conclusin esta solucin tampoco es la ms indicada.

Figura 161. Configuracin 2

La tercera esta configurada de la misma manera que la anterior, pero podemos variar el
nivel de humedad del aire. Esta humidificacin esta constituida por un panel celular en el
interior de la UTA. Como las unidades de tratamientos son mdulos conectados
sucesivamente, podemos aprovechar esta parte de humidificacin para poder cumplir las
normativas de aire interior de RITE.

Figura 162. Configuracin 3

Tanto en la configuracin 4 como la 5 son las unidades de tratamiento de aire mas


completas que se pueden crear, ya que a parte de filtrar el aire procedente del interior del
local y el aire que deseamos introducir del exterior, a parte se aade vapor de agua con el
modulo de humidificacin y el acondicionamiento de la temperatura del aire con las
bateras de fri y calor. Podemos recuperar parte de la energa trmica que posee el aire
que ya hemos extrado, transfirindolo al nuevo aire que introduciremos al recinto.

Figura 163. Configuracin 4 y 5

131

Memoria descriptiva

Este aspecto tambin es un requisito fundamental de RITE, ya que no podemos hacer un


gasto desmesurado de la energa creada. En las dos figuras se diferencian de qu manera se
recupera esta energa trmica.
Llegados a este punto, con las configuraciones D y E, se cumplen las exigencias que se han
citado anteriormente, para elegir el tipo de recuperacin se tendr que realizar una
valoracin de rendimientos y costes de cada uno de los tipos que existen en el mercado.
Hay diferentes tipos de recuperadores, donde se comentaran los tres mas usados.
Recuperador por tubo de calor (Heat Pipe): en este recuperador, la captacin de energa se
produce a travs de una batera intercambiadora cargada con un fluido bifsico (gas o
lquido refrigerante). Esta batera contiene una separacin intermedia donde se divide dos
zonas y es por donde pasan los dos tipos de aire, el procedente del exterior y el aire del
interior, estos flujos de aire van en direcciones opuestas.
Al aplicar calor en un extremo de la batera, el lquido bifsico se evapora y en
consecuencia se desplaza hacia el otro extremo. En este otro extremo mucho mas fri se
condensa y se transfiere el calor, y as transfiere la energa trmica al aire introducido del
exterior.
El rendimiento de este sistema oscila entre el 50 y el 60 %, teniendo en cuanta la ventaja
de la no necesidad de aportaciones energticas y un funcionamiento del todo autnomo.
Recuperador esttico de calor: el intercambio de calor se produce a travs de un
intercambiador de placas, al producir los dos flujos de aire cruzados. Esto consiste en un
trazado de canales en el que una parte siempre esta en contacto con el aire que extraemos
del local, y otro con el aire que introducimos del exterior. La disposicin de los canales
est de manera que los dos tipos de aire nunca entran en contacto, pero se consigue la
transferencia de energa trmica entre ellos.
Los niveles de rendimiento estn situados entre un 55 y un 60%. Las ventajas ms
significativas son que al no tener elementos mviles no es necesario el mantenimiento
exhaustivo y el coste es menor a largo plazo. Este sistema recupera calor sensible, pero si
las placas estn fabricadas con materiales porosos tambin recupera calor latente.
Recuperador rotativo de calor: el intercambio energtico se produce por termoacumulacin a travs de una masa de aluminio resistente a la corrosin. Esta masa
acumuladora permeable capta el calor del flujo del aire caliente y al girar lo cede al flujo
de aire provinente del exterior. La eficiencia vara segn la velocidad de rotacin.
La velocidad de rotacin puede ser constante, marcada por el fabricante o variable
mediante regulacin electrnica. En este ltimo caso se optimiza ms la eficiencia
energtica, pero el coste aumenta.
Estos recuperadores captan tanto la temperatura como la humedad del aire, y su
rendimiento ronda sobre el 70 %. Normalmente no se utilizan como recuperadores de calor
sensible, pero si podra funcionar sin bajar su rendimiento.
Por rendimientos, vemos claramente que el recuperador rotativo es el que mas aprovecha la
energa trmica, recuperando tanto la temperatura como la humedad. Pero al ser un motor

132

Memoria descriptiva

el que provoca el giro, se necesita energa elctrica adicional, adems del control
electrnico, el cual necesitaremos para que el rendimiento citado sea cierto. Este resulta
muy caro, y como el aspecto econmico es importante para la posterior realizacin del
proyecto, utilizaremos el recuperador de calor esttico. Con este recuperador ahorramos los
motores adicionales de rotacin que aumentaran el coste sin renunciar a un buen
rendimiento.

7.3.3
7.3.3.1

Solucin adoptada
Climatizacin aire aire

Descripcin y principio de funcionamiento


Las unidades de tratamiento de aire son elementos que nos permiten mover el aire que
nosotros deseamos acondicionar, i posteriormente darle un numero de caractersticas
determinadas. De esta manera, podremos ofrecer a los usuarios aire de calidad con una
temperatura ptima. En la figura siguiente, podemos observar el funcionamiento de la
UTA mediante el recorrido que hace el aire, realizando diferentes acciones y modificando
sus propiedades segn el modo de funcionamiento elegido.

Figura 164. Modos UTA

En el modo A, se realiza un Free Cooling, es decir, se aprovecha la energa trmica que se


tiene en el exterior, en caso que la temperatura exterior est situada dentro de la consigna
de temperatura de los recintos del edificio, se introducir el aire a los locales
contribuyendo a una eficiencia mayor.
En el modo B, se usa cuando no debemos renovar el aire de los recintos y si se debe
aclimatar para obtener la temperatura deseada. El aire se filtra y se conduce hasta los
elementos que modifican las propiedades trmicas necesarias para adquirir la temperatura
de consigna.
Tanto el modo C como el D, el objetivo es renovar parcialmente o en su totalidad el aire
que extraemos de los recintos para climatizarlo, pero se debe extraer una parte del aire al
exterior para no viciar el aire, mediante este proceso transferimos energa trmica entre los

133

Memoria descriptiva

flujos de aire y as ahorrando energa, cumpliendo la normativa RITE, y contribuyendo a


un mejor rendimiento y una eficiencia energtica notable.
Para poder dimensionar una UTA, necesitamos proporcionar al fabricante la potencia que
debe disipar tanto en calor como en fri. Estas potencias han estado calculadas con el
programa CYPE Ingenieros. De esta manera el fabricante ya sabe que batera debe montar
en cada caso, tambin le deberemos comunicar como la queremos configurar o que
caractersticas son necesarias. Esta eleccin ser la que garantice el cumplimiento de las
normativas comentadas anteriormente y poder garantizar los objetivos del presente
proyecto.
En la siguiente figura se observa como esta constituida y, seguidamente se explicaran las
funciones que tienen cada una de sus partes.

Figura 165. Partes UTA

Ventiladores
La unidad de tratamiento de aire (UTA) contiene ventiladores situados en cada uno de los
conductos de impulsin y de retorno. Estos conductos sern los que darn acceso al aire
que tenemos en los recintos del edificio y as podremos tratarlo y devolverlo. Estos
ventiladores los controlaremos y debern de ser capaces de mover la cantidad especfica de
aire que contiene el local e impuesta por RITE.

Filtros
Como vemos en la figura anterior, tenemos dos filtros, uno situado en la entrada de aire
exterior despus de la compuerta de impulsin, y otro en la entrada del conducto de
retorno. Estos filtros capturan partculas que son arrastradas por el movimiento del aire,
dichas partculas pueden estar tanto en el interior de los recintos como en el exterior del
edificio, gracias a estos filtros ayudamos a que la UTA trabaje en un estado optimo y fuera
de riesgos.

Recuperador de calor
El recuperador de calor es encargado de que el aire interior de los recintos no se vicie y se
renueve, recuperando tambin toda la posible energa trmica que se produzca. Esta es una
manera efectiva de introducir aire que no este climatizado dentro de los locales del
edificio, tambin contribuye a no tener variaciones bruscas de temperatura dentro de la
circulacin de aire.
134

Memoria descriptiva

Compuertas
Las compuertas son las encargadas de dejar el paso del aire y crean el camino que deber
seguir el aire dependiendo la accin a realizar. Se posicionan estratgicamente, la
compuerta de compensacin sirve para la evacuacin de todo el aire proveniente del
conducto de retorno, para poder introducir de nuevo aire mediante la compuerta de
impulsin de aire exterior. Esto se realiza en el caso de que la temperatura exterior este
situada entre la consigna. De esta manera podemos aprovechar las caractersticas que el
aire posee y as contribuir en un ahorro energtico. Este caso no sucede casi nunca, pero no
esta de ms tenerlo en cuenta. Las otras dos compuertas, juntamente con la que nos permite
introducir aire exterior, actuaran de manera que nos permitirn renovar parte del aire y no
llegar a viciar el aire interior. Todas las compuertas estn dotadas de servos con un rango
de abertura de 0 90.

Bateras fro calor


Cuando el aire pasa a travs de las bateras adquiere las propiedades trmicas que ella les
proporciona. Normalmente, la batera que el aire se encuentra en primer lugar por temas de
condensacin es la batera de fro.

7.3.3.2

Caractersticas tcnicas de las UTAs seleccionadas

Cuando se sabe la configuracin y las necesidades que necesitamos, se solicita informacin


a la casa Mitsubishi, esta nos retorna todos los datos tcnicos de los aspectos de la UTA,
estos datos sern primordiales para disear el sistema de climatizacin. Seguidamente se
muestran los datos mas importantes de las unidades elegidas, en el apartado de
documentacin tcnica del capitulo de anexos, concretamente en el Anexo D se encuentran
estos datos ampliados.

Modelo
FDU 100VS

Caractersticas nominales
Dimensiones: 350x1370x650 mm.
Potencia frigorfica (velocidad media): 10 kW
Potencia calorfica (velocidad media): 11,2 kW
Nivel sonoro (velocidad baja): 37 dBA
Caudal de aire (velocidad alta): 2040 m3/h
Presin de aire (velocidad alta): 50 Pa
Retorno de aire: Posterior
Con filtro en impulsin
Con filtro en retorno
Velocidad del ventilador: media

135

Memoria descriptiva

Modelo
FDU 125VS

Caractersticas nominales
Dimensiones: 350x1370x650 mm.
Potencia frigorfica (velocidad media): 12.5 kW
Potencia calorfica (velocidad media): 14 kW
Nivel sonoro (velocidad baja): 38 dBA
Caudal de aire (velocidad alta): 2520 m3/h
Presin de aire (velocidad alta): 50 Pa
Retorno de aire: Posterior
Con filtro en impulsin
Con filtro en retorno
Velocidad del ventilador: media

Modelo
FDU 140VS

Caractersticas nominales
Dimensiones: 350x1370x650 mm.
Potencia frigorfica (velocidad media): 14 kW
Potencia calorfica (velocidad media): 16 kW
Nivel sonoro (velocidad baja): 38 dBA
Caudal de aire (velocidad alta): 2520 m3/h
Presin de aire (velocidad alta): 50 Pa
Retorno de aire: Posterior
Con filtro en impulsin
Con filtro en retorno
Velocidad del ventilador: media

Modelo
FDU 200VS

Caractersticas nominales
Dimensiones: 360x1570x830 mm.
Potencia frigorfica (velocidad media): 20 kW
Potencia calorfica (velocidad media): 22.4 kW
Nivel sonoro (velocidad baja): 51 dBA
Caudal de aire (velocidad alta): 3600 m3/h
Presin de aire (velocidad alta): 100 Pa
Retorno de aire: Posterior
Con filtro en retorno
Velocidad del ventilador: media

136

Memoria descriptiva

7.3.3.3

Caractersticas de los conductos y rejillas seleccionadas

Modelo

Caractersticas

CLIMAVER PLUS R

Aislamiento trmico
Conductividad trmica: 90/90 0,032 W/m K
Resistencia trmica: R 0,75 m2 K/W
**Propiedades referidas a 10 C
Permeabilidad al vapor de agua
Valor aproximado: 0,013 g/m2da mm. Hg.
Correspondiente al revestimiento exterior.
Reaccin al fuego
CLIMAVER PLUS R esta clasificado como B s1, d0.
Cumple con las exigencias normativas NBE-CPI-96
para conductos autoportantes.

Modelo

Caractersticas

CADB-D / DI / DC

Caudal
De 450 a 5.600 m3/h. Versiones Horizontal y Vertical,
ambas con posibilidad de By Pass y de Doble pared.
Dimetros de conducto
200, 250, 315, 355, 450 mm.
Ventiladores
Dos ventiladores centrfugos de doble odo con
motor incorporado. Paneles laterales intercambiables
que permiten mltiples combinaciones.

137

Memoria descriptiva

Modelo

Caractersticas

Serie WG
Rejilla de intemperie para instalaciones de ventilacin y
climatizacin, marco frontal y lamas de chapa perfilada de
acero galvanizado, tela metlica de acero galvanizado con
malla de 20x20 mm., con marco de montaje de chapa de
acero galvanizado.

Modelo

Caractersticas

Serie AT
Rejillas para retorno y extraccin. El marco frontal se
puede elegir con anchura de 27 23 mm., con lamas
horizontales regulables individualmente y sujecin
mediante fijacin oculta. Bajo demanda se puede
suministrar con sujecin por muelle con tornillos vistos
(taladros avellanados).
Las rejillas son de perfil de aluminio extrudo con acabado
anodizado en color natural.

Modelo

Caractersticas

Serie DQ 2
Difusor rectangular de lamas directrices fijas, de aluminio
extruido, con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra,
con junta de estanqueidad perimetral, con dos direcciones
de impulsin, anodinado color natural E6C0, con marco
de montaje de chapa de acero galvanizado, con regulacin
de caudal mediante lamas en oposicin ajustable desde la
parte frontal.

138

Memoria descriptiva

7.3.3.4

Modelo esquemtico de la instalacin

Una vez conocido el clculo de cargas trmicas, para la realizacin del tercer bloque se
realiza de manera esquemtica la ubicacin de los conductos y aparatos de impulsin y
extraccin de aire. Se han dividido las diferentes plantas por sectores para un mayor detalle
en las imgenes.
A continuacin se hace un resumen de los smbolos que se encuentran en las imgenes:

Punto de impulsin de aire procedente de la UTA hacia el recinto a climatizar.

Punto de extraccin de aire interior procedente del recinto climatizado hacia la


UTA.

139

Memoria descriptiva

Figura 166. Modelo esquemtico de climatizacin planta 0 seccin 1

140

Memoria descriptiva

Figura 167. Modelo esquemtico de climatizacin planta 0 seccin 2

141

Memoria descriptiva

Figura 168. Modelo esquemtico de climatizacin planta 0 seccin 3

142

Memoria descriptiva

Figura 169. Modelo esquemtico de climatizacin planta 0 seccin 4

143

Memoria descriptiva

Figura 170. Modelo esquemtico de climatizacin planta 1 seccin 1

144

Memoria descriptiva

Figura 171. Modelo esquemtico de climatizacin planta 1 seccin 2

145

Memoria descriptiva

7.3.4
7.3.4.1

Fase 1. Edificio
Creacin de la obra

Para crear una obra nueva se debe ir a men Archivo > Nuevo. A continuacin, aparecer
en pantalla la ventana Nueva obra, en la que se debe indicar el directorio donde se
guardar la obra, el nombre del fichero y, si se desea, una breve descripcin del mismo.

Figura 172. Creacin de nueva obra

Aceptando el panel, aparece una nueva pantalla donde se debe especificar si la obra que se
va a introducir parte de una obra vaca o ser importada de modelos de CAD/BIM. Para
realizar el presente proyecto, se comienza desde una obra vaca, tal y como se muestra en
la figura.

Figura 173. Creacin de nueva obra vaca

7.3.4.2

Introduccin de los datos generales de la obra

Una vez creada la obra, se inicia la introduccin de los datos generales de la obra. Dicha
introduccin consta de los siguientes apartados:
I. Tipo de edificio
II. Tipo de proyecto
III. Datos del proyecto
IV. Emplazamiento
V. Trmino municipal

146

Memoria descriptiva

VI. Unidades de uso


VII. Plantas/Grupos
VIII. Datos generales
IX. Proteccin frente al ruido procedente del exterior

Figura 174. Introduccin de datos generales de la obra

En primer lugar, como Tipo de edificio se selecciona Pblica concurrencia y como Tipo de
proyecto, Climatizacin, tal y como se muestra en las siguientes imgenes.

Figura 175. Tipo de edificio

Figura 176. Tipo de proyecto

Seguidamente, se sita geogrficamente la obra seleccionando el Emplazamiento y el


Trmino municipal. El presente proyecto, se selecciona la provincia de Lleida y a
continuacin, el trmino municipal de Lleida.
En Datos generales se selecciona tanto la verificacin del cumplimiento del DB HE 1
(Limitacin de demanda energtica) como del DB HR (Proteccin frente al ruido) y en el
apartado Proteccin frente al ruido procedente del exterior se indica el ndice de ruido da y
el tipo de ruido exterior dominante. Se elije como tipo de ruido exterior dominante,
automviles y como ndice de ruido da, Ld 60. Y finalmente, se pulsa Terminar.

7.3.4.3

Importacin de ficheros

Tras la introduccin de los datos generales de la obra, el programa pregunta si desea


introducir las plantillas de dibujo para cada planta. Despus de responder afirmativamente,
aparece la ventana Gestin de vistas de plantillas. Aqu se deben aadir los ficheros .dwg a
la lista, se pulsa el botn Aadir nuevo elemento a la lista y se abren los ficheros planta

147

Memoria descriptiva

baja.dwg y planta primera.dwg en la ruta donde se tienen almacenado los planos en


formato AutoCAD facilitados por la propiedad.

Figura 177. Importacin de ficheros

Pulsando Aceptar se vuelve a la ventana Gestin de vistas de plantillas, la cual debe ser
aceptada para finalizar la importacin de plantillas.

7.3.4.4

Determinacin de la orientacin

La orientacin del edificio es otro parmetro que se debe tener en cuenta, ya que los
cerramientos exteriores de los edificios necesitan tener definida la orientacin para calcular
la radiacin que incide sobre ellos. Por tanto, para definir la orientacin correcta nos
dirigimos a men Obra > Orientacin y, a continuacin, se marca dos puntos con el botn
izquierdo en el rea de introduccin de elementos. Para lograr una mejor definicin de la
orientacin, el programa muestra grficamente el ngulo que se est introduciendo.

7.3.4.5

Descripcin de puentes trmicos lineales

Para definir los puentes trmicos lineales se selecciona la opcin Puentes trmicos lineales
que se encuentra dentro del men Elementos constructivos. En la figura que aparece se
muestran los diferentes puentes trmicos lineales que existen en el edificio.

148

Memoria descriptiva

Figura 178. Puentes trmicos lineales

En el presente proyecto no se realiza ningn cambio en las caractersticas de los puentes


trmicos, por ello se pulsa Aceptar dejando los valores que vienen por defecto.

7.3.4.6

Introduccin de cerramientos de fachada

Para introducir los cerramientos de fachada se accede al men Elementos constructivos >
Muros y particiones y, en el men flotante que aparece, se pulsa el botn Cerramiento.

Figura 179. Muros y particiones

Se pueden utilizar cerramientos definidos en la librera del programa o crear cerramientos


nuevos. En el presente proyecto, se crea un cerramiento nuevo formado por los materiales
facilitados por la propiedad y que anteriormente se han descrito en el apartado de
requisitos de diseo y cumplimiento de normativa.
A partir del estudio y bsqueda de los materiales, los cuales se han buscado en el Cdigo
Tcnico de la Edificacin entramos en el men Edicin del tipo de cerramiento > Pared
por capas > Lista de elementos > Aadir material a la lista, una vez all introducimos los
valores de los materiales usados.
En la siguiente figura se muestra como se ha introducido un material con sus valores de
espesor, densidad, conductividad y calor especifico:

Figura 180. Introduccin de nuevo material

149

Memoria descriptiva

Finalizada la introduccin de materiales, se constituye el cerramiento exterior, en la


siguiente figura se muestra en primer lugar un nombre de referencia para identificar el
cerramiento de fachada, a continuacin se observa como es una construccin por capas de
materiales, y en ltimo lugar se muestra los materiales que esta compuesta la construccin:

Figura 181. Creacin cerramiento de fachada

Se pulsa el botn Terminar, y se observa de forma grafica lo anteriormente comentado en


la figura anterior.

Figura 182. Ventana grafica de creacin de cerramiento

Una vez se termina de crear el cerramiento de fachada, el paso siguiente es mediante el


botn izquierdo del ratn ir siguiendo las lneas exteriores del plano de planta del edificio
hasta completar su permetro. En las siguientes figuras se muestra el resultado:

150

Memoria descriptiva

Figura 183. Cerramiento de fachada planta 0 edificio INEF

Figura 184. Cerramiento de fachada planta 1 edificio INEF

7.3.4.7

Introduccin de tabiquera

Una vez introducidos los cerramientos, se procede a la definicin de la tabiquera. Para


ello, se pulsa el botn
Tabiquera que aparece en el men flotante Elementos
constructivos > Muros y particiones.

Figura 185. Muros y particiones

151

Memoria descriptiva

El tipo de tabique que se va a utilizar en este proyecto, es el tabique compuesto por por tres
capas: Enlucido de yeso, ladrillo hueco sencillo y enlucido de yeso. De la misma manera
que con los cerramientos de fachada abrimos el men Edicin del tipo de cerramiento >
Pared por capas > Lista de elementos > Aadir material a la lista, y una vez all
introducimos los valores de los materiales usados.

Figura 186. Materiales usados para la tabiquera

A continuacin, se pulsa Aceptar y se introduce la tabiquera en todo el edificio: planta


inferior y planta superior, tal y como muestran las siguiente figuras:

Figura 187. Tabiquera planta 0 edificio INEF

152

Memoria descriptiva

Figura 188. Tabiquera planta 1 edificio INEF

7.3.4.8

Introduccin de forjados

Una vez introducidos los cerramientos de fachada y la tabiquera, se procede a la


definicin de los forjados. Para ello, despus de situarse en planta baja, se selecciona la
opcin Elementos constructivos > Forjados, y en el men flotante que aparece, se pulsa el
botn

Forjado sanitario o solera.

Figura 189. Forjados

El tipo de forjado que se va a utilizar en el presente proyecto es el facilitado por la


propiedad, al cual se nombra como Cimientos o forjado, compuesto por los materiales
anteriormente descritos en el apartado de Elementos constructivos del edificio.

Figura 190. Introduccin de materiales en forjados para los cimientos

153

Memoria descriptiva

A continuacin, se introduce la geometra en planta del forjado marcando los puntos de la


poligonal que lo definen. Cuando se marca el ltimo punto de la poligonal, se pulsa el
botn derecho del ratn y se cerrar el polgono. El resultado se muestra en la siguiente
imagen:

Figura 191. Cimientos edificio INEF

Despus de definir los cimientos se introduce el forjado entre pisos. En la planta baja, se
pulsa el botn
entrepisos:

Forjado entre pisos y se crea el siguiente forjado: Entreplanta o forjado

Figura 192. Introduccin de materiales en forjados para la entreplanta

Tras crear el tipo de forjado, se introduce el contorno del forjado entre la planta baja y la
planta 1, teniendo en cuenta las zonas de cubierta y terraza, tal y como se muestra en la
siguiente imagen se puede observar tanto el forjado creado anteriormente Cimientos o
forjado en la planta baja, como la Entreplanta o forjado entre pisos en la planta 1:

154

Memoria descriptiva

Figura 193. Entreplanta edificio INEF

Para finalizar con la introduccin de forjados, se define la azotea. Para ello, nos situamos
en planta Cubierta, se pulsa el botn
Azotea que se encuentra en men Elementos
constructivos > Forjados, y se crea nuevamente el forjado con los materiales y se nombra
como: Cubierta o tejado.

Figura 194. Introduccin de materiales en forjados para la cubierta

A continuacin se muestra una imagen de la vista 3D del progreso del edificio del presente
proyecto (Obra > Vista 3D).

155

Memoria descriptiva

Figura 195. Cubierta edificio INEF

7.3.4.9

Introduccin de huecos en cerramientos y tabiqueras

Una vez definidos todos los elementos constructivos del edificio se colocan las puertas y
ventanas, que son elementos que realizan una aportacin importante a la carga trmica y
una disminucin del aislamiento acstico de un recinto.
En el presente apartado, se comienza introduciendo las puertas y, posteriormente, se
introducirn las ventanas. Para ello, se debe pulsar el botn
el men flotante Elementos constructivos > Huecos.

Puerta que se encuentra en

Figura 196. Huecos

Antes de introducir una puerta, se deben elegir las siguientes caractersticas:


Se selecciona la dimensin de la puerta opcin tres, y como
elemento de construccin de la puerta se usa el material De
madera o Genrico, ya que ambas poseen el mismo
Coeficiente de transmisin (UPuerta = 2.00).

Figura 197. Caractersticas de las puertas

156

Memoria descriptiva

Se acepta el dialogo anterior de propiedades y se


selecciona, con el botn izquierdo del ratn (teniendo
activada la opcin Ms cercano), el punto del cerramiento
o particin donde desea situar la puerta. Una vez pulsado
el botn izquierdo, se habr colocado el punto de inicio de
la puerta. Se desplaza el ratn hacia el lado del
cerramiento o tabiquera donde se quiere situar la puerta
con las dimensiones dadas y se vuelve a pulsar el botn
izquierdo para terminar con la introduccin de la puerta.

Figura 198. Capturas

Siguiendo el procedimiento descrito anteriormente, se introducen todas las puertas del


edificio. Para introducir la puerta de otro tipo de tamao no genrico, las cuales presenten
unas dimensiones mayores, se selecciona la opcin Sobre plano y se dibuja la puerta sobre
la plantilla, tal como se muestra en la imagen anterior.

Figura 199. Colocacin de puerta

Tras introducir las puertas, se va al men Elementos constructivos > Huecos, y se pulsa el
Ventana. A continuacin, aparece una pantalla donde se definen las
botn
caractersticas de cada tipo de ventana existente en el edificio. Como en este proyecto
todas las ventanas son del mismo tipo, los siguientes pasos slo se realizan una vez.
En la pestaa Cristal seleccione el tipo de acristalamiento de acuerdo a las opciones
indicadas:
I. Tipo: Acristalamiento sencillo.
II. Espesor de la hoja: 4 mm.
III. Color: Normal.
De la misma forma, en la pestaa Marco se seleccionan las siguientes opciones, tal y como
muestra la siguiente figura:

157

Memoria descriptiva

Figura 200. Caractersticas del marco de ventana

Despus de definir las caractersticas de las ventanas el programa pide, cada vez que se
vaya a introducir una ventana, la altura del hueco y su altura sobre el suelo.

Figura 201. Altura de ventana

Para introducir la ventana definida, se pulsa Aceptar y se selecciona con el botn izquierdo
del ratn el cerramiento y el punto de insercin donde se desea colocarla. Una vez pulsado
el botn izquierdo del ratn, se habr designado el punto de inicio de la ventana. Se
desplaza el ratn sobre el cerramiento para indicar el punto final de la ventana y se vuelva
a pulsar dicho botn para finalizar su creacin.

Figura 202. Colocacin de ventana

158

Memoria descriptiva

Se repite el procedimiento anterior y se introducen todas las ventanas del edificio, a


continuacin se muestra la imagen definitiva de la construccin del edificio:

Figura 203. Construccin final edificio INEF Lleida

7.3.4.10 Listado de resultados


De esta manera se ha realizado el modelo estructural del edificio de oficinas de INEF
Lleida mediante el software CYPE Ingenieros, dentro del Anexo A se pueden observar los
datos generados respecto a los materiales y elementos constructivos como pueden ser el
sistema envolvente, sistema de compartimentacin, el listado de todos los materiales que se
han empleado y la descripcin de los puentes trmicos.
En el siguiente bloque se realizar la zonificacin de recintos, la explicacin de su uso y, se
proceder a la explicacin de cmo se introduce dicha informacin de cada uno de los
recintos dentro de CYPE Ingenieros y la obtencin de los resultados de los listados de
cargas trmicas.

7.3.5

Fase 2. Cargas trmicas

Una vez realizado un anlisis preciso de cada local, se puede proceder a estimar la carga
teniendo en cuenta tanto el calor procedente del exterior como el que se genera en el
interior del local. Para ello se define el trmino da de proyecto, que sirve para definir las
condiciones climatolgicas que se suponen en un da de anlisis. CYPE Ingenieros
considera como tal aqul en el que las temperaturas de los termmetros seco y hmedo
(ver Glosario) alcanzan su mximo simultneamente, y apenas existe niebla en el aire que
reduzca la radiacin solar. En realidad, rara vez ocurre que todas las cargas internas y
externas alcancen su mximo a la misma hora, con lo cual se trabaja con unos factores
inferiores a la unidad que sirven para paliar este hecho.

159

Memoria descriptiva

7.3.5.1

Da de proyecto

A continuacin se definen las condiciones climatolgicas en las cuales se realiza el clculo


de cargas trmicas.
Trmino municipal: Lleida
Latitud (grados): 41.62 grados
Altitud sobre el nivel del mar: 155 m.
Percentil para verano: 5.0 %
Temperatura seca verano: 27.11 C
Temperatura hmeda verano: 22.50 C
Oscilacin media diaria: 8.4 C

7.3.5.2

Oscilacin media anual: 27.5 C


Percentil para invierno: 97.5 %
Temperatura seca en invierno: 1.20 C
Humedad relativa en invierno: 90 %
Velocidad del viento: 3.6 m/s
Temperatura del terreno: 6.40 C

Definicin de recintos

Una vez se han definido los elementos constructivos, es el momento de definir los recintos.
Para introducir recintos se pulsa men Recintos > Nuevo, donde aparecer una secuencia
de paneles para editar la descripcin del recinto, el suelo y el techo.
La biblioteca de recintos predefinidos de CYPE Ingenieros est clasificada en dos grupos:
I. Recintos de uso docente.
II. Resto de recintos.

Figura 204. Uso de recinto

A continuacin, se empieza definiendo las oficinas que se encuentran en Planta baja y


Planta alta. Para ello, se accede a men Recintos > Nuevo y se selecciona Resto de
recintos. Posteriormente, se activa la casilla de Condiciones interiores para climatizacin,
ahora es el momento donde se crearan los tres tipos de recintos que se encuentran en
nuestro edificio y estn definidos en la Norma UNE EN 13779, estos recintos son Oficinas,

160

Memoria descriptiva

Restauracin y Salas de reuniones, en la figura siguiente se muestra como se ha creado el


tipo de recinto Oficinas.

Figura 205. Descripcin de recinto

Editar recinto, un vez realizada la operacin se


A continuacin, se pulsa el botn
desplegara un nuevo men donde se deben seleccionar los parmetros Habitable y
Climatizado. Seguidamente se muestran cinco pestaas las cuales se deben rellenar con los
valores caractersticos de cada tipo de recinto y cumpliendo la normativa vigente
anteriormente explicada en los apartados Uso de recintos y Requisitos de los recintos.

Figura 206. Temperatura de recinto

En primer lugar se indican los valores mximo y mnimo de temperatura, como se ha


comentado anteriormente en los recintos de uso docente estos valores son 26 C en el

161

Memoria descriptiva

periodo del verano y 21 C en invierno. A continuacin en la siguiente figura se procede a


indicar el nivel de ocupacin.

Figura 207. Ocupacin de recinto

Despus de indicar la temperatura operativa, se introduce el valor de ocupacin mximo


permitido por tipo de recinto, en este caso nuestro espacio es una oficina y tal y como
indica la normativa UNE EN 13779 son 10 m2 por persona, tambin se aade que la tarea a
realizar por las personas dentro del recinto son actividades de oficina. Para finalizar este
apartado se usa la opcin de usar un porcentaje de mujeres para as crear un modelo ms
real.

Figura 208. Iluminacin de recinto

En cuanto a la iluminacin del recinto tambin se acude a la normativa UNE EN 13779 que
como ya se ha visto en el primer bloque se debe introducir el valor de 400 lux que es
equivalente a 10 W/m2.

162

Memoria descriptiva

Figura 209. Ventilacin de recinto

A diferencia de las tres figuras anteriores que se ha acudido a la normativa UNE EN 13779
para conocer el valor que se debe introducir, esta vez se utiliza el RITE para conocer el
valor del caudal que debe llevar nuestro recinto para una correcta gestin de la calidad del
aire interior. Una vez citada la fuente de obtencin de nuestros valores, se indica que
nuestro caudal de aire es un IDA 2 como indica en la figura.
Con estos valores se procede a continuacin a introducir la capa de techo y suelo de
recinto. En cuanto a tipo de suelo se describe como un suelo sencillo estndar (Tipo 1:
S.EPS50).

Figura 210. Suelo de recinto

Tras definir el suelo se indica el tipo de techo, para el caso de los recintos climatizados el
edificio consta de un falso techo de 30 cm. de altura recubierto de yeso, a continuacin se
observan las caractersticas de techo que compartirn todos los recintos climatizados.

Figura 211. Techo de recinto

Como se aprecia en la figura se observan dos tipos de techo, el primer techo de Tipo 1:
Enl15 es un elucido de yeso de 1,5 cm. para los recintos no climatizados, y como Tipo 2:
T02.MW es un falso techo para los edificios climatizados para poder introducir los
conductos de aire.

163

Memoria descriptiva

En la figura siguiente se muestran las caractersticas de este falso techo:

Figura 212. Falso techo de recinto

A continuacin, se pulsa Terminar y se selecciona con el botn izquierdo del ratn dentro
del espacio donde se encuentra cualquier de las oficinas del edificio, escribiendo una
referencia para cada nmero de recinto.

Figura 213. Nombre de recinto

Posteriormente de introducir la referencia, se selecciona con el botn izquierdo del ratn


todos los recintos que son del tipo Oficinas y se introducen las referencias siguiendo el
orden de cada recinto.
Una vez todos los recintos de Oficinas se han referenciado, se realizan los mismos pasos
descritos anteriormente para crear el resto de recintos, eligiendo las siguientes
caractersticas:

Salas de reuniones
I. Condiciones
Temperatura de verano: 26 C
Temperatura de invierno: 21 C
Humedad relativa: 50 %
II. Ocupacin
Por superficie: 3 m2, por persona.

164

Memoria descriptiva

III. Iluminacin
Potencia por superficie: 10 W/m2.
Tipo: Fluorescente con reactancia.
IV. Ventilacin
IDA 2: Aire de buena calidad.
V. Otras cargas
Por superficie: 10 W/m2.

Restauracin
I. Condiciones
Temperatura de verano: 26 C
Temperatura de invierno: 21 C
Humedad relativa: 50 %
II. Ocupacin
Por superficie: 1.5 m2, por persona.
III. Iluminacin
Potencia por superficie: 6 W/m2.
Tipo: Fluorescente con reactancia.
IV. Ventilacin
IDA 2: Aire de buena calidad.
V. Otras cargas
Por superficie: 4.4 W/m2.

7.3.5.3

Obtencin de los listados de resultados

Una vez asignados todos los recintos al conjunto INEF, se realiza el clculo de cargas
trmicas. Para ello, se pulsa men Resultados > Calcular o el botn
Calcular.
Cuando se finaliza el clculo se visualiza un listado de tablas donde aparecen las cargas
trmicas de cada recinto, dichas tablas trmicas de cada recinto se puede observar en el
Anexo B. A continuacin se muestra una tabla resumen de los listados:

165

Memoria descriptiva

7.3.5.4

Resumen de los resultados de clculo de cargas de los recintos

Refrigeracin

Recinto
OFICINA 014
OFICINA 015
OFICINA 016
OFICINA 017
OFICINA 018
REPROGRAFIA
GESTION
ATENCION
OFICINA 011
OFICINA 009
OFICINA 008
SALA DE JUNTAS
SALA HONOR
SALA
AUDIOVISUAL
SALA
DE ESPERA
CAFETERIA
COMEDOR
OFICINA 101
OFICINA 102
OFICINA 103/104
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109

Planta
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1

Estructural
(W)
1829.76
1839.78
1827.98
1740.49
1008.74
1334.07
4874.02
-32.41
29.50
13.09
-11.88
3744.84
609.85
2122.43
191.69
127.47
1893.86
362.78
3.01
41.35
23.20
23.87
18.92
-1.52
1720.44

Subtotales
Sensible
interior
(W)
776.18
760.79
787.16
756.98
751.62
1429.17
4910.75
999.53
704.34
391.01
585.15
2967.63
3482.51
3486.67
846.68
12267.73
1718.09
439.64
421.63
732.37
399.54
384.83
425.50
374.78
767.84

Total
interior
(W)
981.50
966.11
992.48
962.30
956.94
1839.81
6211.11
1273.29
909.66
527.89
790.47
4023.23
4781.71
4785.87
1171.48
19346.14
2717.87
576.52
558.51
937.69
536.42
521.71
562.38
511.66
973.16

Conjunto: INEF
Carga interna
Sensible
Total
(W)
(W)
2684.12
2889.44
2678.59
2883.91
2693.60
2898.92
2572.40
2777.72
1813.17
2018.49
2846.13
3256.77
10078.31 11378.67
996.13
1269.89
755.86
961.18
416.22
553.10
590.47
795.79
6913.84
7969.44
4215.14
5514.34
5777.37
7076.57
1069.52
1394.32
12767.06 19845.47
3720.31
4720.09
826.49
963.37
437.38
574.26
796.93
1002.25
435.42
572.30
420.96
557.84
457.75
594.63
384.45
521.33
2562.92
2768.24

Caudal
(m/h)
130.93
127.60
133.30
126.77
125.61
241.12
848.07
171.01
118.31
61.63
92.15
1142.17
1423.31
1426.48
337.60
7949.29
1081.74
72.30
68.35
124.46
63.50
60.27
69.20
58.07
129.12

Ventilacin
Sensible
(W)
-182.35
-177.71
-185.66
-176.56
-174.95
-470.45
-131.84
-26.58
-18.39
-9.58
-14.32
-322.50
-221.26
-221.75
-52.48
-1235.75
-168.16
-141.07
-10.63
-19.35
-9.87
-9.37
-10.76
-9.03
-179.83

Carga
total
(W)
234.96
228.98
239.22
227.51
225.42
287.31
3106.92
626.49
433.44
225.79
337.58
3858.32
5214.36
5225.96
1236.80
29122.59
3963.00
86.16
250.42
455.97
232.65
220.82
253.52
212.74
231.72

Potencia trmica
Por
Sensible
Total
superficie
(W)
(W)
(W/m)
107.39
2501.77
3124.39
109.78
2500.88
3112.90
105.94
2507.94
3138.14
106.67
2395.83
3005.22
80.39
1638.22
2243.91
66.14
2375.68
3544.08
76.86
9946.48 14485.59
49.90
969.54
1896.38
53.04
737.46
1394.62
56.87
406.64
778.89
55.35
576.14
1133.37
155.33
6591.35 11827.77
113.07
3993.88 10728.70
129.37
5555.62 12302.53
116.91
1017.04
2631.12
184.80
11531.31 48968.06
240.81
3552.15
8683.09
65.32
685.41
1049.52
54.29
426.75
824.68
52.72
777.58
1458.22
57.04
425.55
804.95
58.13
411.59
778.66
55.15
446.99
848.15
56.89
375.43
734.07
104.55
2383.09
2999.97

166

Memoria descriptiva
OFICINA 110
OFICINA 111
OFICINA 112
OFICINA 113
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1

1769.84
884.73
902.65
1759.91
844.72
801.95
816.87
1665.81
375.17
356.69
29.01
-39.44
41.81
396.61

723.10
402.27
397.38
742.65
387.61
408.76
1096.03
725.41
444.34
1104.76
345.05
364.41
477.12
343.57

928.42
539.15
534.26
947.97
524.49
545.64
1438.23
930.73
581.22
1446.96
481.93
501.29
614.00
480.45

2567.73
1325.61
1339.03
2577.64
1269.30
1247.03
1970.29
2462.95
844.10
1505.30
385.28
334.72
534.49
762.39

2773.05
1462.49
1475.91
2782.96
1406.18
1383.91
2312.49
2668.27
980.98
1847.50
522.16
471.60
671.37
899.27
Total

119.44
62.36
61.31
123.67
59.19
63.77
183.25
119.94
78.03
185.19
51.54
55.79
80.53
51.22
17477.6

-166.36
-86.86
-85.39
-172.24
-82.44
-88.82
6.40
-167.05
-12.13
6.46
-1.47
-8.67
-2.30
-99.93

214.35
111.92
110.02
221.94
106.23
114.44
669.73
215.25
285.88
676.80
152.76
204.39
238.68
61.03

112.55
113.60
116.41
109.34
114.98
105.73
73.23
108.18
73.06
61.34
58.92
54.52
50.85
84.37

2401.38
1238.75
1253.65
2405.39
1186.86
1158.22
1976.68
2295.90
831.97
1511.76
383.81
326.05
532.19
662.45

2987.41
1574.40
1585.94
3004.90
1512.41
1498.35
2982.22
2883.52
1266.85
2524.29
674.93
675.99
910.06
960.29

Carga total simultnea

156057.7

Tabla 61. Resumen del listado de cargas trmicas para edificio INEF

167

Memoria descriptiva

Calefaccin

Recinto

Planta

OFICINA 014
OFICINA 015
OFICINA 016
OFICINA 017
OFICINA 018
REPROGRAFIA
GESTION
ATENCION
OFICINA 011
OFICINA 009
OFICINA 008
SALA DE JUNTAS
SALA HONOR
SALA
AUDIOVISUAL
SALA
DE ESPERA
CAFETERIA
COMEDOR
OFICINA 101
OFICINA 102
OFICINA 103/104
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 111
OFICINA 112
OFICINA 113
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta baja
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1
Planta 1

Conjunto: INEF
Ventilacin
Potencia
Carga interna
Carga
Por
sensible(W) Caudal(m/h)
total(W)
superficie(W/m)
1167.09
130.93
822.43
68.38
1151.08
127.60
801.52
68.86
1178.41
133.30
837.36
68.05
1171.42
126.77
796.35
69.85
1115.96
125.61
789.06
68.25
2446.28
241.12
1514.62
73.92
6732.21
848.07
5327.23
63.99
1562.74
171.01
1074.20
69.39
1279.30
118.31
743.19
76.93
644.79
61.63
387.14
75.35
1172.78
92.15
578.83
85.54
2723.05
1142.17
7174.68
129.99
2238.58
1423.31
8940.70
117.82
2357.56
1426.48
8960.58
119.02
897.95
337.60
2120.65
134.12
6527.81
7949.29
49934.48
213.08
1864.56
1081.74
6795.08
240.16
1177.43
72.30
454.19
101.55
862.97
68.35
429.37
85.08
1393.94
124.46
781.83
78.67
718.52
63.50
398.91
79.18
691.99
60.27
378.62
79.93
747.26
69.20
434.70
76.86
1000.91
58.07
364.76
105.83
1481.66
129.12
811.10
79.90
1328.94
119.44
750.30
78.33
639.30
62.36
391.75
74.40
636.88
61.31
385.11
75.01
1269.20
123.67
776.86
74.45
602.61
59.19
371.83
74.08
808.92
63.77
400.58
85.35
2342.48
183.25
1151.14
85.79
1649.81
119.94
753.44
90.16
1033.27
78.03
490.17
87.85
2379.15
185.19
1163.29
86.08
1078.46
51.54
323.78
122.42
948.26
55.79
350.46
104.75
1608.07
80.53
505.88
118.12
1020.29
51.22
321.73
117.91
Total
17477.6
Carga total simultnea

Total(W)
1989.51
1952.60
2015.77
1967.77
1905.01
3960.90
12059.44
2636.95
2022.49
1031.93
1751.61
9897.73
11179.27
11318.14
3018.60
56462.29
8659.65
1631.62
1292.34
2175.77
1117.42
1070.61
1181.96
1365.68
2292.76
2079.24
1031.05
1021.99
2046.07
974.44
1209.50
3493.62
2403.25
1523.44
3542.44
1402.23
1298.72
2113.95
1342.02
171439.8

Tabla 62. Resumen del listado de cargas trmicas para edificio INEF

168

Memoria descriptiva

7.3.5.5

Resumen de los resultados para el conjunto del recinto INEF


Refrigeracin
Conjunto

Potencia por superficie (W/m)

Potencia total (W)

156057.7
INEF
70.5
Tabla 63. Resumen resultados refrigeracin para el edificio INEF
Calefaccin
Conjunto

Potencia por superficie (W/m)

Potencia total (W)

INEF
77.4
171439.8
Tabla 64. Resumen resultados calefaccin para el edificio INEF

7.3.6

Fase 3. Climatizacin

Una vez calculadas las cargas trmicas de climatizacin se introducen los elementos de la
instalacin que se va a realizar. En el presente proyecto se explica los procedimientos que
se debe seguir para realizar una instalacin de climatizacin de un edificio de pblica
concurrencia utilizando un sistema aire-aire. En este proyecto se climatizarn los recintos
del tipo Oficinas, Restauracin, y Salas de reuniones (ya que los baos y pasillos son
recintos sin climatizar) a travs de un sistema conducido.
La introduccin de los distintos elementos del sistema de climatizacin se va a realizar
segn el sentido del caudal de circulacin de aire.
El orden de introduccin de elementos es el siguiente:
I. Split conducido.
II. Recuperador de calor.
III. Unidad exterior de aire acondicionado.
IV. Lneas frigorficas.
V. Conductos de aire.
VI. Difusores.
VII. Rejillas de retorno.
VIII. Rejillas de tomas de aire exterior y extraccin de aire.

7.3.6.1

Introduccin de los splits conducidos

En Instalacin > Sistema de expansin directa, aparece la siguiente barra de herramientas:

Figura 214. Sistema de expansin directa

169

Memoria descriptiva

Para introducir un split conducido, se pulsa el botn


Split conducido dentro del men
Instalacin > Sistema de expansin directa. Aparece una ventana donde se puede definir el
split, se comprueba que hay dos pestaas para especificar la unidad interior y la unidad
exterior.

Se selecciona un split de la marca


Mitsubishi, el cual anteriormente se
han definido en el apartado de
Soluciones adoptadas y se pulsa
Aceptar. Se introduce el split en el
plano de la obra, para modificar la
270
orientacin se pulsa el botn
que se encuentra en el panel lateral.
Del mismo modo se introducen los
dems modelos Mitsubishi, los
cuales se colocan siguiendo el
Modelo esquemtico de instalacin.

Figura 215. Seleccin split conducido

Como se puede observar en la imagen, el split tiene 3 conexiones, dos flechas verticales
que son la entrada y salida de aire y una flecha horizontal, para realizar la conexin con la
bomba exterior.

Figura 216. Split conducido

7.3.6.2

Introduccin de la unidad recuperadora de calor

A continuacin se aade el modulo del recuperador de calor de la UTA, para ello se utiliza
el
Recuperador de calor esttico aire aire que se encuentra en el men Instalacin >
Sistemas de conduccin de aire.
Aparece una ventana emergente como la siguiente donde se selecciona el recuperador de
calor marca S&P (Soler & Palau) serie CADB-D/DI/DC y se pulsa Aceptar.

170

Memoria descriptiva

Figura 217. Seleccin unidad recuperadora de calor

Se ubican los Recuperadores de calor esttico prximos a los splits introducidos, ya que
ambos mdulos conforman la Unidad de tratamiento de aire. Una vez introducido dentro
de la obra, el recuperador tiene el siguiente aspecto:

Figura 218. Unidad recuperadora de calor

El recuperador de calor tiene cuatro flechas horizontales las cuales cada una tiene una
funcin diferente, a continuacin se citan:
I. Impulsin de aire: Conducto para impulsar aire a splits con conductos. Tambin
permite conectar los conductos a los recintos mediante elementos terminales tales
como rejillas o difusores.
II. Extraccin de aire: Conducto para circular aire hasta una rejilla de extraccin.
III. Entrada de aire exterior: Conducto para impulsar aire primario procedente de una
rejilla de toma de aire exterior.
IV. Retorno de aire: Conducto para extraer aire de los recintos a travs de rejillas de
retorno.

7.3.6.3

Introduccin de la unidad exterior de aire acondicionado

Una vez que se han definido todas las mquinas interiores se introducen las mquinas
exteriores en la cubierta. Para ello, despus de situarse en la cubierta, se selecciona el men
Instalacin > Sistema de expansin directa, y en la ventana flotante que aparece se pulsa

171

Memoria descriptiva

Unidad exterior de aire acondicionado 11. Como cada unidad va asociada al split,
no hay que definir nada.

7.3.6.4

Introduccin de lneas frigorficas

Como ya estn colocadas las mquinas interiores y exteriores, slo hay que conectarlas,
utilizando los dos ltimos botones de la barra a la que se accede a travs del men
Instalacin > Sistema de expansin directa:
I.
II.

Lnea frigorfica con tubera doble aislada horizontal.


Lnea frigorfica con tubera doble aislada vertical.

Al introducir la
Lnea frigorfica con tubera doble aislada vertical, aparece un men
contextual donde se tendr que definir el inicio y el comienzo de la tubera vertical, en este
caso el grupo inicial y final solo se puede definir de dos maneras, desde la cubierta hasta la
planta 1, o desde cubierta hasta la planta baja.

Figura 219. Seleccin lnea frigorfica

Despus de aceptar el panel anterior se pulsa el botn izquierdo del ratn donde se quiera
introducir la lnea. Para unir la lnea con la mquina exterior se selecciona
Lnea
frigorfica con tubera doble aislada horizontal y despus de situarse en Planta baja, se
vuelve a utilizar la tubera horizontal para conectar la montante con el split.
De esta manera se conectan las unidades exteriores con las interiores mediante la red de
tuberas, a continuacin se explica la conexin de la red de conductos.

7.3.6.5

Introduccin de conductos de aire

Al terminar de conectar las mquinas interiores y exteriores, se tendr que introducir los
conductos de aire, para ello se utiliza el
Conducto horizontal que se encuentra en el
men Instalacin > Sistemas de conduccin de aire.

Figura 220. Sistemas de conduccin de aire

172

Memoria descriptiva

Despus, se elije que Todos los conductos de


la obra son del mismo tipo y seleccionando
Tipo 1 se elije:
I. Conducto de lana mineral.
II. Lana de vidrio.
III. Espesor: 25 mm.

Figura 221. Seleccin conducto horizontal

Las dimensiones del conducto se pueden fijar para que el programa no las dimensione.
Para este proyecto se acepta el panel siguiente, permitiendo que el programa dimensione
tanto el ancho como el alto de los conductos.

Figura 222. Conducto horizontal

Seguidamente, se introduce la red de conductos de aire partiendo de los splits conducidos


anteriormente colocados. Para ello, con el botn izquierdo se selecciona el punto de inicio
de la red de conductos y se va realizando el diseo de la instalacin tal y como se
especifico en el esquema del apartado de Solucin adoptada.
En el siguiente apartado se completa la red de conductos mediante la introduccin de
rejillas y difusores.

7.3.6.6

Introduccin de rejillas y difusores

Una vez se ha terminada de colocar la red de conductos, esta no tienen puntos de


introduccin o expulsin de aire, para crear las rejillas y difusores se pulsa
Difusor en
el men Instalacin > Sistemas de conduccin de aire.

Figura 223. Sistemas de conduccin de aire

Como se ha comentado anteriormente en la seccin de Solucin adoptada, se selecciona el


difusor de la marca TROX serie ADQ/DQ tal como indica la figura.

173

Memoria descriptiva

Una vez seleccionado el difusor se pulsa con el botn izquierdo del ratn el punto del
circuito de impulsin de aire donde se quiere instalar el difusor para que el aire pueda
llegar a los recintos.
Para retirar el aire de los recintos es
necesario rejillas de retorno de aire, para
introducirlas se pulsa el botn
Rejilla de
retorno en el men Instalacin > Sistemas
de conduccin de aire. De la misma manera
que en la seleccin de los difusores, se elige
la casa comercial TROX y la serie AT, la
cual son rejillas de aluminio con lamas
horizontales. A continuacin, una vez se
selecciona la rejilla, se ubica dentro de la red
de
conductos
de
retorno
creada
anteriormente.

Figura 224. Seleccin difusor

7.3.6.7

Introduccin de rejillas de toma y extraccin de aire

Para finalizar la instalacin de climatizacin se necesitan rejillas de toma de aire del


exterior y rejillas para extraer el aire de la Unidad de tratamiento de aire (UTA) para que
el aire no se vicie. Para introducir estos elementos se pulsan los botones
Rejilla de
toma de aire y
Rejilla de extraccin del men Instalacin > Sistemas de conduccin de
aire.
Ambas rejillas, de toma de aire y de extraccin son de la misma casa comercial, TROX, y
la misma serie, WG, estas son rejillas de exterior para instalaciones de climatizacin. Tal y
como se indic en el Esquema de la instalacin de climatizacin en el apartado Solucin
adoptada se introducen las rejillas de toma de aire exterior y extraccin de aire al final de
los conductos de cada recuperador de calor (modulo de la UTA).

Figura 225. Rejillas de toma y extraccin de aire

174

Memoria descriptiva

Como se observa en la figura se introduce las rejillas de extraccin de aire (A88) y toma de
aire (A87). La simbologa es la siguiente, la flecha hacia fuera simboliza la expulsin de
aire, y la flecha hacia dentro del conducto simboliza la introduccin de aire exterior hacia
el recuperador de calor.

7.3.6.8

Obtencin de los resultados del clculo de la instalacin

Se han introducido los elementos para crear la instalacin de climatizacin, a continuacin


se generan los resultados y dimensionado de la instalacin: conductos, rejillas y difusores.
Calcular y el programa CYPE Ingenieros procede a calcular como se
Se pulsa el botn
aprecia en la siguiente imagen.
Si en algn momento se produce una infraccin de la normativa vigente el clculo de los
resultados es automticamente anulado.

Figura 226. Calculando

Una vez se finaliza el clculo de la instalacin, se visualiza un listado de tablas donde


aparecen las dimensiones de conductos y rejillas, dichas tablas se puede observar en el
Anexo D.

175

Memoria descriptiva

Planificacin

176

Memoria descriptiva

Dic '10
Actividad

Comienzo

Terminacin

Sin descripcin

13/12/10

06/05/11

1. Instalaciones

13/12/10

06/05/11

1.1. Calefaccin, climatizacin y A.

13/12/10

06/05/11

1.1.1. Unidades autnomas de cli

13/12/10

22/12/10

1.1.1.1. Lnea frigorfica doble realiza

13/12/10

14/12/10

1.1.1.2. Lnea frigorfica doble realiza

14/12/10

15/12/10

1.1.1.3. Equipo de aire acondicionad

15/12/10

16/12/10

1.1.1.4. Equipo de aire acondicionad

16/12/10

17/12/10

1.1.1.5. Equipo de aire acondicionad

17/12/10

18/12/10

1.1.1.6. Equipo de aire acondicionad

20/12/10

21/12/10

1.1.1.7. Equipo de aire acondicionad

21/12/10

22/12/10

1.1.2. Sistemas de conduccin de

22/12/10

06/05/11

1.1.2.1. Conducto autoportante recta

22/12/10

23/12/10

1.1.2.2. Difusor rectangular de lamas

23/12/10

24/12/10

1.1.2.3. Difusor rectangular de lamas

24/12/10

25/12/10

1.1.2.4. Difusor rectangular de lamas

27/12/10

28/12/10

1.1.2.5. Difusor rectangular de lamas

28/12/10

29/12/10

1.1.2.6. Difusor rectangular de lamas

29/12/10

30/12/10

1.1.2.7. Difusor rectangular de lamas

30/12/10

31/12/10

1.1.2.8. Difusor rectangular de lamas

31/12/10

01/01/11

1.1.2.9. Difusor rectangular de lamas

03/01/11

04/01/11

1.1.2.10. Difusor rectangular de lama

04/01/11

05/01/11

1.1.2.11. Difusor rectangular de lama

05/01/11

06/01/11

1.1.2.12. Difusor rectangular de lama

07/01/11

08/01/11

1.1.2.13. Difusor rectangular de lama

10/01/11

11/01/11

1.1.2.14. Difusor rectangular de lama

11/01/11

12/01/11

1.1.2.15. Difusor rectangular de lama

12/01/11

13/01/11

1.1.2.16. Difusor rectangular de lama

13/01/11

14/01/11

1.1.2.17. Difusor rectangular de lama

14/01/11

15/01/11

1.1.2.18. Difusor rectangular de lama

17/01/11

18/01/11

1.1.2.19. Difusor rectangular de lama

18/01/11

19/01/11

1.1.2.20. Difusor rectangular de lama

19/01/11

20/01/11

1.1.2.21. Difusor rectangular de lama

20/01/11

21/01/11

1.1.2.22. Difusor rectangular de lama

21/01/11

22/01/11

1.1.2.23. Difusor rectangular de lama

24/01/11

25/01/11

1.1.2.24. Difusor rectangular de lama

25/01/11

26/01/11

1.1.2.25. Difusor rectangular de lama

26/01/11

27/01/11

1.1.2.26. Difusor rectangular de lama

27/01/11

28/01/11

1.1.2.27. Difusor rectangular de lama

28/01/11

29/01/11

1.1.2.28. Difusor rectangular de lama

31/01/11

01/02/11

1.1.2.29. Difusor rectangular de lama

01/02/11

02/02/11

1.1.2.30. Difusor rectangular de lama

02/02/11

03/02/11

1.1.2.31. Difusor rectangular de lama

03/02/11

04/02/11

1.1.2.32. Difusor rectangular de lama

04/02/11

05/02/11

1.1.2.33. Difusor rectangular de lama

07/02/11

08/02/11

1.1.2.34. Difusor rectangular de lama

08/02/11

09/02/11

1.1.2.35. Difusor rectangular de lama

09/02/11

10/02/11

1.1.2.36. Difusor rectangular de lama

10/02/11

11/02/11

1.1.2.37. Difusor rectangular de lama

11/02/11

12/02/11

1.1.2.38. Difusor rectangular de lama

14/02/11

15/02/11

1.1.2.39. Difusor rectangular de lama

15/02/11

16/02/11

1.1.2.40. Difusor rectangular de lama

16/02/11

17/02/11

1.1.2.41. Difusor cuadrado de lamas

17/02/11

18/02/11

1.1.2.42. Difusor rectangular de lama

18/02/11

19/02/11

1.1.2.43. Rejilla de retorno, de alumin

21/02/11

22/02/11

1.1.2.44. Rejilla de retorno, de alumin

22/02/11

23/02/11

1.1.2.45. Rejilla de retorno, de alumin

23/02/11

24/02/11

1.1.2.46. Rejilla de retorno, de alumin

24/02/11

25/02/11

1.1.2.47. Rejilla de retorno, de alumin

25/02/11

26/02/11

1.1.2.48. Rejilla de retorno, de alumin

28/02/11

01/03/11

1.1.2.49. Rejilla de retorno, de alumin

01/03/11

02/03/11

1.1.2.50. Rejilla de retorno, de alumin

02/03/11

03/03/11

1.1.2.51. Rejilla de retorno, de alumin

03/03/11

04/03/11

1.1.2.52. Rejilla de retorno, de alumin

04/03/11

05/03/11

1.1.2.53. Rejilla de retorno, de alumin

07/03/11

08/03/11

1.1.2.54. Rejilla de retorno, de alumin

08/03/11

09/03/11

1.1.2.55. Rejilla de retorno, de alumin

09/03/11

10/03/11

1.1.2.56. Rejilla de retorno, de alumin

10/03/11

11/03/11

1.1.2.57. Rejilla de retorno, de alumin

11/03/11

12/03/11

1.1.2.58. Rejilla de retorno, de alumin

14/03/11

15/03/11

1.1.2.59. Rejilla de retorno, de alumin

15/03/11

16/03/11

1.1.2.60. Rejilla de retorno, de alumin

16/03/11

17/03/11

1.1.2.61. Rejilla de retorno, de alumin

17/03/11

18/03/11

1.1.2.62. Rejilla de retorno, de alumin

18/03/11

19/03/11

1.1.2.63. Rejilla de retorno, de alumin

21/03/11

22/03/11

1.1.2.64. Rejilla de retorno, de alumin

22/03/11

23/03/11

1.1.2.65. Rejilla de retorno, de alumin

23/03/11

24/03/11

1.1.2.66. Rejilla de retorno, de alumin

24/03/11

25/03/11

Ene '11

Feb '11

Mar '11

Abr '11

May '11

177

Memoria descriptiva

Dic '10
Actividad

Comienzo

Terminacin

1.1.2.67. Rejilla de retorno, de alumin

25/03/11

26/03/11

1.1.2.68. Rejilla de retorno, de alumin

28/03/11

29/03/11

1.1.2.69. Rejilla de retorno, de alumin

29/03/11

30/03/11

1.1.2.70. Rejilla de retorno, de alumin

30/03/11

31/03/11

1.1.2.71. Rejilla de retorno, de alumin

31/03/11

01/04/11

1.1.2.72. Rejilla de retorno, de alumin

01/04/11

02/04/11

1.1.2.73. Rejilla de retorno, de alumin

04/04/11

05/04/11

1.1.2.74. Rejilla de retorno, de alumin

05/04/11

06/04/11

1.1.2.75. Rejilla de retorno, de alumin

06/04/11

07/04/11

1.1.2.76. Rejilla de retorno, de alumin

07/04/11

08/04/11

1.1.2.77. Rejilla de retorno, de alumin

08/04/11

09/04/11

1.1.2.78. Rejilla de retorno, de alumin

11/04/11

12/04/11

1.1.2.79. Rejilla de retorno, de alumin

12/04/11

13/04/11

1.1.2.80. Rejilla de retorno, de alumin

13/04/11

14/04/11

1.1.2.81. Rejilla de retorno, de alumin

14/04/11

15/04/11

1.1.2.82. Rejilla de retorno, de alumin

15/04/11

16/04/11

1.1.2.83. Rejilla de retorno, de alumin

18/04/11

19/04/11

1.1.2.84. Rejilla de retorno, de alumin

19/04/11

20/04/11

1.1.2.85. Rejilla de intemperie para in

20/04/11

21/04/11

1.1.2.86. Rejilla de intemperie para in

21/04/11

22/04/11

1.1.2.87. Rejilla de intemperie para in

25/04/11

26/04/11

1.1.2.88. Rejilla de intemperie para in

26/04/11

27/04/11

1.1.2.89. Rejilla de intemperie para in

27/04/11

28/04/11

1.1.2.90. Rejilla de intemperie para in

28/04/11

29/04/11

1.1.2.91. Rejilla de intemperie para in

29/04/11

30/04/11

1.1.2.92. Recuperador de calor aire-a

02/05/11

03/05/11

1.1.2.93. Recuperador de calor aire-a

03/05/11

04/05/11

1.1.2.94. Recuperador de calor aire-a

04/05/11

05/05/11

1.1.2.95. Recuperador de calor aire-a

05/05/11

06/05/11

Ene '11

Feb '11

Mar '11

Abr '11

May '11

Plan de pagos

Cronograma de mano de obra

Pago mensual

151.959,37

2.513,37

4.128,77

1.053,03

8.672,46

33.061,01

Pagos acumulados

151.959,37

154.472,74

158.601,51

159.654,54

168.327,00

201.388,01

Dic '10

Ene '11

Feb '11

Mar '11

Abr '11

May '11

mo003 h Oficial 1 instalador de climatizacin.

594,396

5,148

7,463

4,373

9,516

10,319

mo054 h Ayudante instalador de climatizacin.

594,396

5,148

7,463

4,373

9,516

10,319

178

Memoria descriptiva

Orden de prioridad de los documentos


I. Planos
II. Presupuesto
III. Estudio de seguridad y salud
IV. Pliego de condiciones
V. Memoria
VI. Anexos

179

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

2. ANEXOS
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Anexos

ndice
0

HOJA DE IDENTIFICACIN............................................................................................................. 4

ENERGYPLUS ...................................................................................................................................... 5
1.1

CARACTERSTICAS DEL EDIFICIO ..................................................................................................... 5

1.1.1

General ...................................................................................................................................... 5

1.1.2

WindowWall Ratio Summary................................................................................................... 5

1.1.3

Zone Summary ........................................................................................................................... 5

1.1.4

Opaque Exterior Summary ........................................................................................................ 6

1.1.5

Fenestration Summary............................................................................................................... 7

1.1.6

Interior Lighting Summary ........................................................................................................ 7

1.1.7

Average Outdoor Air During Occupied Hours.......................................................................... 8

1.1.8

Surfaces By Class ...................................................................................................................... 8

1.1.9

HVAC......................................................................................................................................... 9

1.1.10
1.2

Input Fields........................................................................................................................... 9

CARGAS TRMICAS ......................................................................................................................... 9

1.2.1

Determinacin de las cargas trmicas del edificio.................................................................... 9

1.2.1.1

Tipos de cargas trmicas ................................................................................................................. 9

1.2.2

Hojas trmicas de calefaccin y refrigeracin ........................................................................ 11

1.2.3

Resultados simulacin del edificio en condiciones actuales ................................................... 12

1.2.3.1

Enero ............................................................................................................................................. 12

1.2.3.2

Febrero .......................................................................................................................................... 14

1.2.3.3

Marzo ............................................................................................................................................ 16

1.2.3.4

Abril .............................................................................................................................................. 18

1.2.3.5

Mayo ............................................................................................................................................. 20

1.2.3.6

Junio.............................................................................................................................................. 22

1.2.3.7

Julio............................................................................................................................................... 24

1.2.3.8

Septiembre .................................................................................................................................... 26

1.2.3.9

Octubre.......................................................................................................................................... 28

1.2.3.10

Noviembre..................................................................................................................................... 30

1.2.3.11

Diciembre...................................................................................................................................... 32

1.2.4

Resultados simulacin del edificio con la mejora de acristalamiento doble........................... 34

1.2.4.1

Enero ............................................................................................................................................. 34

1.2.4.2

Febrero .......................................................................................................................................... 36

1.2.4.3

Marzo ............................................................................................................................................ 38

1.2.4.4

Abril .............................................................................................................................................. 40

1.2.4.5

Mayo ............................................................................................................................................. 42

Anexos

1.2.4.6

Junio.............................................................................................................................................. 44

1.2.4.7

Julio............................................................................................................................................... 46

1.2.4.8

Septiembre .................................................................................................................................... 48

1.2.4.9

Octubre.......................................................................................................................................... 50

1.2.4.10

Noviembre..................................................................................................................................... 52

1.2.4.11

Diciembre...................................................................................................................................... 54

1.2.5

1.2.5.1

Enero ............................................................................................................................................. 56

1.2.5.2

Febrero .......................................................................................................................................... 58

1.2.5.3

Marzo ............................................................................................................................................ 60

1.2.5.4

Abril .............................................................................................................................................. 62

1.2.5.5

Mayo ............................................................................................................................................. 64

1.2.5.6

Junio.............................................................................................................................................. 66

1.2.5.7

Julio............................................................................................................................................... 68

1.2.5.8

Septiembre .................................................................................................................................... 70

1.2.5.9

Octubre.......................................................................................................................................... 72

1.2.5.10

Noviembre..................................................................................................................................... 74

1.2.5.11

Diciembre...................................................................................................................................... 76

1.2.6

Resultados simulacin del edificio con la mejora de voladizo ................................................ 56

Resultados de simulacin del edificio con las mejoras de acristalamiento doble y voladizo.. 78

1.2.6.1

Enero ............................................................................................................................................. 78

1.2.6.2

Febrero .......................................................................................................................................... 80

1.2.6.3

Marzo ............................................................................................................................................ 82

1.2.6.4

Abril .............................................................................................................................................. 84

1.2.6.5

Mayo ............................................................................................................................................. 86

1.2.6.6

Junio.............................................................................................................................................. 88

1.2.6.7

Julio............................................................................................................................................... 90

1.2.6.8

Septiembre .................................................................................................................................... 92

1.2.6.9

Octubre.......................................................................................................................................... 94

1.2.6.10

Noviembre..................................................................................................................................... 96

1.2.6.11

Diciembre...................................................................................................................................... 98

CYPE INGENIEROS ........................................................................................................................ 100


2.1

DESCRIPCIN DE MATERIALES Y ELEMENTOS CONSTRUCTIVOS................................................... 100

2.1.1

Sistema envolvente................................................................................................................. 100

2.1.1.1

Cerramientos exteriores............................................................................................................... 100

2.1.1.2

Suelos.......................................................................................................................................... 100

2.1.1.3

Cubiertas ..................................................................................................................................... 101

2.1.1.4

Huecos verticales ........................................................................................................................ 105

Anexos

2.1.2

Sistema de compartimentacin .............................................................................................. 107

2.1.2.1

Particiones verticales................................................................................................................... 107

2.1.2.2

Forjado entre pisos ...................................................................................................................... 107

2.1.2.3

Huecos verticales interiores......................................................................................................... 108

2.1.3

Materiales.............................................................................................................................. 109

2.1.4

Puentes trmicos.................................................................................................................... 110

2.2

LISTADO COMPLETO DE CARGAS TRMICAS ................................................................................ 111

2.2.1

Parmetros generales ........................................................................................................... 111

2.2.2

Resultados de clculo de los recintos ................................................................................... 112

2.2.2.1

Refrigeracin ............................................................................................................................... 112

2.2.2.2

Calefaccin ................................................................................................................................. 190

2.2.3

Resumen de los resultados de clculo de los recintos .......................................................... 268

2.2.4

Resumen de los resultados para conjuntos de recintos ........................................................ 271

2.3

CLCULO DE LA INSTALACIN .................................................................................................... 272

2.3.1

Sistemas de conduccin de aire. Conductos.......................................................................... 272

2.3.2

Sistemas de conduccin de aire. Difusores y rejillas ............................................................ 278

Anexos

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con
CYPE Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01

Data y firmas de los anteriormente citados

Reus, Mayo de 2011

Anexos

ENERGYPLUS

1.1

Caractersticas del edificio

1.1.1

General
Value
Program Version and Build
EnergyPlus 5.0.0.031
Weather
Lerida ESP SWEC WMO#=081710
Latitude [deg]
41.63
Longitude [deg]
0.6
Elevation [m]
263
Time Zone
1
North Axis Angle [deg]
29
Rotation for Appendix G [deg]
0
Hours Simulated [hrs]
8760

1.1.2

WindowWall Ratio Summary


Total

Gross Wall Area


[m2]
Window Opening
Area [m2]
Window-Wall
Ratio [%]

1.1.3

1345

North (315 to
45 deg)
353.82

East (45 to
135 deg)
347.93

South (135 to
225 deg)
336.97

West (225 to
315 deg)
306.27

212.56

83.2

17.56

77.58

34.22

15.8

23.51

5.05

23.02

11.17

Zone Summary
Area
[m2]

HONOR
OFI 001
JUNTAS
AUDIO
OFI 011
OFI 009
OFI 008
WC BAJA
ESPERA
SECRE
BAJA NO

90.69
114.96
77.53
96.42
25.59
13.73
19.84
77.43
26.85
26.16
323.77

Conditio
ned
(Y/N)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No

Volume
[m3]

Gross Wall
Area [m2]

Window Glass
Area [m2]

Lighting
[W/m2]

231.26
100.26
197.71
245.88
65.26
35.02
50.59
197.46
89.72
66.71
917.06

59.13
110.03
61.4
33.91
14.97
8.03
11.6
37.74
8.52
19.47
133.52

4.41
16.56
9.24
9.87
5.98
2.99
3.9
4.28
0.81
2.7
6.4

10
10
10
10
10
10
10
0
10
10
0

Anexos

VENT
GESTION
REPRO
CALDERA
COMEDOR
COCINA
CAFETERA
OFI 109
OFI 111
OFI 117
OFI 108
OFI 103
OFI 104
WC2_ALTA
OFI 123
OFI 122
OFI 121
WC_ALTA
OFI 120
OFI 119
OFI 118
OFI 124
ALTA_NO_
VENT
Total
Conditioned
Total
Uncondition
ed Total

1.1.4

218.84
49.92
25.8
36
102.3
259.75
85.92
57.36
37.28
63
25.9
15.21
4.83
20.98
20.56
12.65
13.25
45.91
24.06
25.17
17.8

Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes

554.94
127.31
65.8
91.8
260.87
662.37
484.69
228.24
111.83
763.5
77.88
45.62
14.49
62.94
61.67
37.96
39.76
137.74
72.09
75.51
53.41

128.98
16.45
0
15.3
54.12
76.75
82.5
79.05
53.82
82.59
17.86
8.7
0
28.39
17.34
10.71
11.22
55.97
16.52
17.28
19.35

23.46
5.5
0
2.92
5.64
19.67
17.52
12.27
1.12
12.91
5.19
2.07
0
4.6
2.83
3.3
2.2
6.19
2.31
5.5
2.33

10
10
0
6
0
6
10
10
10
10
10
10
0
10
10
10
0
10
10
10
10

162.77

No

488.56

53.76

7.9

2218.25

6715.9

1345

212.56

6.2653

1508.1

4731.9

1054.64

186.14

9.2156

710.16

1984

290.36

26.42

Opaque Exterior Summary


Construction

F1.1: DOBLE VISTA XPS 50MM


R=1.92:ZONA A-D
S:SOLERA HORMIGON 200MM XPS 70 MM
R=2.20: ZONA C
C5.3:CUB PLANA INV NO TRANS XPS
80MM FU 300MM BH R=2.72:ZONA C

Reflec
tance

U-Factor with
Film [W/m2-K]

U-Factor no
Film [W/m2-K]

0.3

0.584

0.64

0.4

0.41

0.456

0.4

0.344

0.367

Anexos

1.1.5

Fenestration Summary

Construction

Area of One
Opening [m2]

EXTERIOR
2.87
WINDOW
Total or Average
North Total or Average
Non-North Total or Average

1.1.6

Area of
Openings [m2]

U-Factor
[W/m2-K]

SHG
C

Visible
Transmittance

2.87

3.304

0.752

0.751

212.56
83.2
129.36

3.3
3.3
3.3

0.752
0.752
0.752

0.751
0.751
0.751

Interior Lighting Summary

Zone
OFI 120
OFI 119
OFI 118
OFI 124
OFI 109
AUDIO
CAFETERA
COMEDOR
ESPERA
OFI 001
GESTION
HONOR
JUNTAS
OFI 008
OFI 009
OFI 011
SECRE
REPRO
OFI 111
OFI 117
OFI 108
OFI 103
OFI 104
OFI 123
OFI 122
OFI 121
Interior Lighting
Total

Lighting
Power
Density
[W/m2]
10
10
10
10
10
10
6
6
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
9.2156

Zone Area
[m2]

Total Power
[W]

End Use
Subcate
gory

Average
Hours/Week [hr]

45.91
24.06
25.17
17.8
85.92
96.42
259.75
36
26.85
114.96
218.84
90.69
77.53
19.84
13.73
25.59
26.16
49.92
57.36
37.28
63
25.9
15.21
20.98
20.56
12.65

459.12
240.56
251.71
178.02
859.2
964.25
1558.53
216
268.5
1149.6
2188.43
906.89
775.32
198.38
137.34
255.93
261.6
499.23
573.6
372.78
630.02
258.98
152.08
209.8
205.55
126.52

Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights

44.93
44.93
44.93
44.93
44.93
44.93
23.96
23.96
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93
44.93

1508.1

13897.94

Anexos

1.1.7

Average Outdoor Air During Occupied Hours

HONOR
OFI 001
JUNTAS
AUDIO
OFI 011
OFI 009
OFI 008
ESPERA
SECRE
GESTION
REPRO
COMEDOR
CAFETERA
OFI 109
OFI 111
OFI 117
OFI 108
OFI 103
OFI 104
OFI 123
OFI 122
OFI 121
OFI 120
OFI 119
OFI 118
OFI 124

1.1.8

Average
Number of
Occupants
30
12
26
32
3
2
2
9
3
22
5
9.6
69.2
9
6
4
7
3
2
2
2
2
5
3
3
2

Nominal Number of
Occupants

Zone
Volume [m3]

Simple
Ventilation [ach]

30
12
26
32
3
2
2
9
3
22
5
24
173
9
6
4
7
3
2
2
2
2
5
3
3
2

231.26
100.26
197.71
245.88
65.26
35.02
50.59
89.72
66.71
554.94
127.31
91.8
662.37
484.69
228.24
111.83
763.5
77.88
45.62
62.94
61.67
37.96
137.74
72.09
75.51
53.41

6.009
5.589
6.08
6.02
2.139
2.658
1.841
4.655
2.097
1.845
1.83
12.061
12.036
0.868
1.229
1.667
0.426
1.793
2.042
1.48
1.512
2.452
1.692
1.941
1.854
1.746

Surfaces By Class
Class
Total Outdoors
Wall
310
92
Floor
72
30
Roof
84
42
Internal Mass
0
0
Building Detached Shading
68
68
Fixed Detached Shading
0
0
Window
103
95
Door
128
12

Anexos

1.1.9

HVAC

Conditioned Zones
Unconditioned Zones
Supply Plenums
Return Plenums

1.1.10

Count
26
7
0
0

Input Fields
Count
IDF Objects
905
Defaulted Fields
788
Fields with Defaults
2963
Autosized Fields
78
Autosizable Fields
78
Autocalculated Fields
325
Autocalculatable Fields 1028

1.2

Cargas Trmicas

1.2.1

Determinacin de las cargas trmicas del edificio

1.2.1.1

Tipos de cargas trmicas

o Transmisin de los cerramientos: Las superficies que delimitan cada zona de


clculo y la separan de otro ambiente con distinta temperatura transmiten un flujo
de potencia calorfica por conduccin. La carga referente a la transmisin por los n
cerramientos que delimitan una zona, EnergyPlus calcula de la siguiente manera:
n

i =1

i =1

QTRANS = QTRANS _ i = S i k i Ti

[W ]

La diferencia de temperatura es distinta si la superficie separa la zona de un


ambiente no climatizado o de uno que lo est. As pues, en el primer caso el
incremento se calcula entre las temperaturas interior y exterior de diseo. En
cambio, si el cerramiento separa ambientes climatizados se considera la mitad del
incremento de temperaturas del caso anterior.

o Radiacin solar: Los cerramientos transparentes permiten el paso de la radiacin


solar, transmitiendo as energa desde el exterior al interior del edificio. A este flujo

Anexos

de calor directo se le tiene que aadir el que procede de la radiacin denominada


indirecta, siendo sta la que absorbe el cerramiento y se transmite posteriormente al
interior del local. El porcentaje sobre el total de energa que es transmitido al
interior en forma de calor de manera directa e indirecta se denomina SHGC (Solar
Heat Gain Coefficient), y se da en tanto por uno. La carga trmica para una zona
debido a la radiacin solar se calcula mediante la frmula que sigue:
n

i =1

i =1

QRAD = QRAD _ i = G S i SHGC i

[W ]

o Ocupacin: Los seres vivos son un foco de generacin de energa trmica positiva
debido a su metabolismo. Tambin aportan vapor de agua al ambiente a travs de la
transpiracin. Se puede estimar la aportacin de los ocupantes de una zona en
funcin del tipo de actividad que desarrollan. En el caso de una oficina (individuos
estn sentados haciendo un trabajo muy ligero), los valores de la aportacin
sensible y latente se toman de 81.74 y 52.26 W por persona respectivamente. Se
calcula la potencia sensible y latente, siendo p la ocupacin de la zona que se trata:

Q S OCUP = 81.74 p [W ]
Q L OCUP = 52.26 p [W ]
o Ventilacin: La aportacin de aire de ventilacin a una zona se puede hacer
cogiendo aire del exterior del edificio o extrayndolo de otro local, sea ste o no
climatizado. Adems hay aportaciones de aire por infiltracin. El RITE considera
para oficinas un caudal de aire de ventilacin de 45 m3/h por persona.
Este aire aporta una carga sensible debido a la diferencia de temperaturas entre
ambientes y una carga latente por la diferencia de humedades absolutas. La carga
trmica sensible por ventilacin o infiltraciones de aire para una zona se calcula de
la siguiente forma:
Q S VENT = V p ce T

[W ]

La variable V designa el caudal de aire de ventilacin por persona, p la ocupacin


de la zona y ce el calor especfico del aire en base al volumen (1,21 kJ/m3K). El
incremento de temperaturas se ha tomado entre la temperatura exterior de diseo y
la interior. La carga trmica latente por ventilacin o infiltracin para una zona se
encuentra mediante el siguiente clculo:

Q L VENT = V p p a Lvap w

[W ]
10

Anexos

En este caso, el valor de la carga depende de la densidad del aire, del calor latente
de vaporizacin y de la diferencia de humedades absolutas entre el aire exterior y el
interior.
o Iluminacin y maquinaria: Las luminarias y la maquinaria presente en una zona
generan energa trmica debido a su funcionamiento. Esta aportacin de energa
trmica contribuye positivamente a la generacin de calor sensible. Para el edificio
se estiman unas ganancias debidas a la iluminacin de 10 W/m2 segn RITE. Por lo
tanto, la carga correspondiente en W para una zona de superficie S es la siguiente:
QILUM = 10 S

1.2.2

[W ]

Hojas trmicas de calefaccin y refrigeracin

A continuacin se exponen las hojas trmicas de refrigeracin y calefaccin para cada una
de las dependencias del recinto, a partir de las condiciones exteriores medias de cada mes,
de las condiciones interiores de diseo, la evolucin diaria de la radiacin solar y las
caractersticas arquitectnicas y de funcionamiento del edificio se calcula la evolucin
horaria de la carga trmica para cada mes del ao.
Se plasman los clculos y resultados obtenidos partir de la aplicacin de las ecuaciones
descritas en los anteriores apartados. Todas las ecuaciones descritas han sido extradas del
Manual de Funcionamiento de EnergyPlus.

11

Anexos

1.2.3

Resultados simulacin del edificio en condiciones actuales

1.2.3.1

Enero
Recinto

Carga interna (W)

Ventilacin

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

6791.98

409.67

4722.05

7620.28

Mxima puntual
(W)
21464

Oficina 008

696.6

25.72

370.12

1047.70

3217.44

Oficina 009

570.63

25.82

358.58

859.04

2684.01

Oficina 011

971.03

38.72

535.28

1360.70

4362.13

Sala de Juntas

4350.94

333.78

3807.41

7607.93

18018.60

Sala Honor

5174.58

385.90

4615.19

7842.62

19738.59

Oficina 014

1312.04

38.90

578.06

811.31

3258.47

Oficina 015

1312.04

38.90

578.06

811.31

3258.47

Oficina 016

1312.04

38.90

578.06

811.31

3258.47

Oficina 017

1312.04

38.90

578.06

811.31

3258.47

Oficina 018

1119

38.84

561.50

1033.43

3907.26

Cafetera y restaurante

24968.7

2214.32

21961.65

43900.26

83203.40

Gestin Acadmica, Econmica y de Postgrado

7922.52

284.17

3907.38

7995.47

26813.20

Comedor reservado

3475.97

307.51

3176.49

6455.18

11942.50

Sala de Espera

1786.01

112.50

436.85

2499.88

6705.75

Servicio Reprografa

1741.58

64.67

926.09

1955.76

5995.30

Sala Audiovisual

12

Anexos

Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)
Carga total (W)

Calefaccin
Media (W)
Mxima puntual (W)

OFICINA 103-104

990.78

38.75

547.66

619.26

4617.86

OFICINA 101

495.77

25.84

371.12

437.21

2885.77

OFICINA 102

1228.20

18.06

265.27

774

3974

OFICINA 105

1228.20

18.06

265.27

774

3974

OFICINA 106

1228.20

18.06

265.27

774

3974

OFICINA 107

1228.20

18.06

265.27

774

3974

OFICINA 108

1228.20

18.06

265.27

774

3974

OFICINA 109

2373.80

38.92

600.87

820.1

4763.3

OFICINA 110

2373.80

38.92

600.87

820.1

4763.3

OFICINA 113

2373.80

38.92

600.87

820.1

4763.3

OFICINA 111

351.25

19.47

303.74

780

4563.3

OFICINA 112

351.25

19.47

303.74

780

4563.3

OFICINA 115

351.25

19.47

303.74

780

4563.3

OFICINA 116

351.25

19.47

303.74

780

4563.3

OFICINA 117

1391.56

51.77

756.12

1319.5

5342.7

OFICINA 118

1362.97

38.88

577.22

842.21

3809.2

OFICINA 119

1103.87

38.88

569.82

856.8

3726.55

OFICINA 120

1896.94

64.44

990.73

1667.22

6958.11

OFICINA 121

474.18

25.82

699.42

742.07

2642.0

OFICINA 122

724.88

25.80

384.95

865.73

3415.0

OFICINA 123

770.78

25.88

450.70

923.66

3580

OFICINA 124

623.0

25.88

382.0

803.49

3105

13

Anexos

1.2.3.2

Febrero
Recinto

Ventilacin

Carga interna (W)

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

Sala Audiovisual

7045.53

409.67

4165.88

5224.55

Mxima puntual
(W)
21610.60

Oficina 008

706.36

25.72

324.94

747.55

3125.72

Oficina 009

578.91

25.82

314.36

621.85

2641.01

Oficina 011

987.47

38.72

469.40

969.62

4268.72

Sala de Juntas

4439.63

333.78

3341.96

5699.17

18308.10

Sala Honor

5240.17

385.90

4059.51

5784.65

19726.90

Oficina 014

1402.72

38.90

539.62

458.43

2563.37

Oficina 015

1402.72

38.90

539.62

458.43

2563.37

Oficina 016

1402.72

38.90

539.62

458.43

2563.37

Oficina 017

1402.72

38.90

539.62

458.43

2563.37

Oficina 018

1161.45

38.84

503.19

667.88

3550.74

Cafetera y restaurante

25043.54

2214.32

18877.49

34257.17

86886.9

Gestin Acadmica, Econmica y de Postgrado

8189.95

284.17

3462.16

5217.01

25410.50

Comedor reservado

3531.1

307.51

2749.63

5003.02

12739.50

Sala de Espera

1795.77

112.50

1287.22

1801.12

6608.87

Servicio Reprografa

1859.97

64.67

819.28

1159.80

5876.60

14

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1012.35
607.83
911.5
911.5
911.5
911.5
911.5
2552.8
2552.8
2552.8
1501.25
1501.25
1501.25
1501.25
1427
1515.41
1178.78
2001.41
592.04
740.4
800
624.04

Ventilacin
Caudal (l/s)
Carga total (W)
38.58
478.34
25.72
531
17.9
230.74
17.9
230.74
17.9
230.74
17.9
230.74
17.9
230.74
38.79
255.73
38.79
255.73
38.79
255.73
19.41
282.5
19.41
282.5
19.41
282.5
19.41
282.5
51.55
670.31
38.88
524.13
38.88
506.7
64.44
827.14
28.88
712.22
28.71
476.21
27.6
469.72
25.78
339.8

Media (W)
807.3
565.06
580.4
580.4
580.4
580.4
580.4
444
444
444
410
410
410
410
876.76
479.36
514.33
1068.2
522.84
865.73
600
514.42

Calefaccin
Mxima puntual (W)
4441.3
2705
3862.2
3862.2
3862.2
3862.2
3862.2
3811.3
3811.3
3811.3
3722.3
3722.3
3722.3
3722.3
4862.3
3365.2
3335.55
6336.11
2528.33
3415
3174
2812.42

Media (W)
0
0
1.67
1.67
1.67
1.67
1.67
37.74
37.74
37.74
29.77
29.77
29.77
29.77
0
16.19
2.34
0.42
0
0
0
0

Refrigeracin
Mxima puntual (W)
0.03
0.3
48
48
48
48
48
596
596
596
480
480
480
480
5
346.8
120.91
65.5
1.5
1.1
2.3

15

Anexos

1.2.3.3

Marzo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7044.55

409.67

3463.30

Media
(W)
3226.56

Mxima
puntual (W)
16405

Media (W)

Mxima puntual (W)

Oficina 008

718.79

25.72

270.60

450.35

2227.45

Oficina 009

589.24

25.82

261.48

387.40

1874.42

Oficina 011

1007.81

38.72

392.24

593.07

3023.24

Sala de Juntas

4591.59

333.78

2764.85

3648.49

13742.70

Sala Honor

5204.23

385.90

3319.46

3757.21

14754.40

Oficina 014

1390.16

38.90

462.41

220.35

1826.72

219.70

1042.76

Oficina 015

1390.16

38.90

462.41

220.35

1826.72

219.70

1042.76

Oficina 016

1390.16

38.90

462.41

220.35

1826.72

219.70

1042.76

Oficina 017

1390.16

38.90

462.41

220.35

1826.72

219.70

1042.76

Oficina 018

1154.61

38.84

427.57

383.60

2510.50

65.10

508.14

Cafetera y restaurante

25128.63

2214.32

14988.60

24004.94

69655.30

Gestin Acadmica, Econmica y de Postgrado

8470.35

284.17

3008.16

2889.10

17578.40

366.31

3296.85

Comedor reservado

3600.61

307.51

2206.38

3431.77

10041.70

Sala de Espera

1795.21

112.50

1060.01

1135.63

4820.76

Servicio Reprografa

1997.63

64.67

716.0

520.30

3627.62

89.20

598.91

16

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1038
660
1254
1254
1254
1254
1254
2548.2
2548.2
2548.2
1090.31
1090.31
1090.31
1090.31
1424.55
1525
881
2225.36
608
756
831
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.1
396.56
25.7
270.64
17.88
191.89
17.88
191.89
17.88
191.89
17.88
191.89
17.88
191.89
38.56
539.55
38.56
539.55
38.56
539.55
19.3
245
19.3
245
19.3
245
19.3
245
51.25
556.26
38.5
453.33
38.7
430
64.5
698.6
25.7
262.12
25.7
278.88
25.74
277.06
25.7
284.37

Media (W)
504.5
317.52
398.2
398.2
398.2
398.2
398.2
215.3
215.3
215.3
250
250
250
250
503.15
243.84
275.95
580.22
320.4
352.34
364.17
245.48

Calefaccin
Mxima puntual (W)
3183.62
1865.02
2858.6
2858.6
2858.6
2858.6
2858.6
2585.6
2585.6
2585.6
2951.01
2951.01
2951.01
2951.01
3481.3
2228.3
2253.6
4382.1
1763.21
2236.1
2322
1719.2

Media (W)
2.32
0.56
2.8
2.8
2.8
2.8
2.8
125.3
125.3
125.3
112
112
112
112
5.73
71.69
24
21.4
0.79
1.81
2.45
3.98

Refrigeracin
Mxima puntual (W)
103.6
45.12
197.2
197.2
197.2
197.2
197.2
904
904
904
848
848
848
848
178.72
637.87
311.93
423.72
41.9
72.1
92.66
117.34

17

Anexos

1.2.3.4

Abril
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6867.75

409.67

2478.51

Media
(W)
1974.64

Mxima
puntual (W)
13059.60

Media (W)

Mxima puntual (W)

606.90

4187.0

Oficina 008

736.95

25.72

201.82

234.70

1741.67

60.12

387.73

Oficina 009

603.19

25.82

192.67

211.87

1486.06

43.53

307.31

Oficina 011

1035.48

38.72

289.92

324.72

2413.23

86.74

556.60

Sala de Juntas

4743.17

333.78

2008.72

2062.20

10771.70

261.90

2561.10

Sala Honor

5117.96

385.90

2350.93

2288.60

11805.70

210.01

2192.95

Oficina 014

1303.54

38.90

336.79

134.89

1526.75

338.99

1304.04

Oficina 015

1303.54

38.90

336.79

134.89

1526.75

338.99

1304.04

Oficina 016

1303.54

38.90

336.79

134.89

1526.75

338.99

1304.04

Oficina 017

1303.54

38.90

336.79

134.89

1526.75

338.99

1304.04

Oficina 018

1116.89

38.84

312.56

224.21

2102.07

170.37

837.20

Cafetera y restaurante

25260.37

2214.32

9924.85

14932.03

54699.01

362.15

8581.10

Gestin Acadmica, Econmica y de Postgrado

8680.36

284.17

2287.93

1435.83

14095.01

1382.07

6350.54

Comedor reservado

3640.62

307.51

1498.79

2089.41

7871.17

55.82

1223.52

Sala de Espera

1786.87

112.50

767.17

668.41

3882.34

105.69

874.20

Servicio Reprografa

2065.66

64.67

553.20

257.96

2941.88

391.83

1318.52

18

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1077.46
736.27
1275
1275
1275
1275
1275
2394
2394
2394
1659
1659
1659
1659
1398.56
1411.72
1116.99
2016.9
633.8
782
888.6
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.12
299.77
25.7
212
17.77
142.5
17.77
142.5
17.77
142.5
17.77
142.5
17.77
142.5
38.2
365.73
38.2
365.73
38.2
365.73
19.1
183.57
19.1
183.57
19.1
183.57
19.1
183.57
50.9
422.82
38.5
345.36
38.05
329.2
63.8
539.5
26.5
199
25
213.65
26.5
215.45
25
226.51

Media (W)
241.3
123.31
404.6
404.6
404.6
404.6
404.6
119.6
119.6
119.6
130
130
130
130
264.1
128
277.76
205.66
150
162.69
156.43
102.26

Calefaccin
Mxima puntual (W)
2562
1404
2360.8
2360.8
2360.8
2360.8
2360.8
2317.3
2317.3
2317.3
2413.9
2413.9
2413.9
2413.9
3004.6
1933
3598.55
3110.11
1398.43
1764.2
1784.11
1404.8

Media (W)
52.01
41.94
17.6
17.6
17.6
17.6
17.6
205
205
205
195
195
195
195
77.83
152.43
142.52
142.52
31.18
46.33
55.8
66.16

Refrigeracin
Mxima puntual (W)
510
326.93
198.4
198.4
198.4
198.4
198.4
1258
1258
1258
1277
1277
1277
1277
677.8
1023.22
1090.81
2000
291.23
391.32
447.97
1401.8

19

Anexos

1.2.3.5

Mayo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

6705.77

409.67

Oficina 008

758.6

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
9388.94

Media (W)

Mxima puntual (W)

1852.07

Media
(W)
668.35

1933.06

7376.20

25.72

157.25

50.82

862.92

270.86

810.87

620.63

25.82

147.98

49.99

806.56

201.08

973.63

Oficina 011

1066.47

38.72

223.19

80.34

1337.23

358.21

1141.35

Sala de Juntas

4873.6

333.78

1570.05

593.20

7552.11

1292.30

6116.96

Sala Honor

5069.92

385.90

1738.13

732.20

8514.59

1149.35

5389.79

Oficina 014

1230.53

38.90

246.97

47.50

1044.0

573.50

1505.0

Oficina 015

1230.53

38.90

246.97

47.50

1044.0

573.50

1505.0

Oficina 016

1230.53

38.90

246.97

47.50

1044.0

573.50

1505.0

Oficina 017

1230.53

38.90

246.97

47.50

1044.0

573.50

1505.0

Oficina 018

1077.39

38.84

234.23

65.18

1204.84

412.60

1202.18

Cafetera y restaurante

25416.93

2214.32

8420.41

5569.43

40338.40

3432.62

24826.90

Gestin Acadmica, Econmica y de Postgrado

8849.29

284.17

1810.69

376.86

8119.61

3676.85

10731.90

Comedor reservado

3668.28

307.51

1083.18

757.24

5781.77

537.11

3557.75

Sala de Espera

1778.59

112.50

572.37

196.26

2642.56

473.20

1893.47

Servicio Reprografa

2108.79

64.67

427.46

60.08

1503.46

975.91

2445.09

Sala Audiovisual

20

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1122
780
1300
1300
1300
1300
1300
2267.2
2267.2
2267.2
1355.25
1355.25
1355.25
1355.25
1373
1295
1062
2010
677.91
818.51
957
623

Ventilacin
Caudal (l/s)
Carga total (W)
37.8
261.56
25.27
188.5
17.65
124.89
17.65
124.89
17.65
124.89
17.65
124.89
17.65
124.89
25.31
200.42
25.31
200.42
25.31
200.42
19
139.3
19
139.3
19
139.3
19
139.3
50.5
360.27
37.94
285.78
37.91
287.5
63.21
467.76
25.26
176
25.27
187.88
25.28
193.64
25
199

Media (W)
58.31
25.19
57.4
57.4
57.4
57.4
57.4
38
38
38
42
42
42
42
69.47
40.14
42.55
67.8
34.36
35.03
32.62
21.57

Calefaccin
Mxima puntual (W)
1229.1
591.14
1274
1274
1274
1274
1274
1309.3
1309.3
1309.3
1360.5
1360.5
1360.5
1360.5
1460.04
1053.81
1020.93
1802.05
707.3
786.65
801.28
593.06

Media (W)
266.32
214.48
108
108
108
108
108
460
460
460
420
420
420
420
339.75
381.73
298.08
544.44
168.44
230.3
269.76
275.05

Refrigeracin
Mxima puntual (W)
1190.1
782.96
565.5
565.5
565.5
565.5
565.5
1629
1629
1629
1559
1559
1559
1559
1396.3
1408.92
1177.79
2181.39
770.52
928.43
1055.73
941.13

21

Anexos

1.2.3.6

Junio
Recinto

Carga interna (W)

Ventilacin
Carga total (W)

Refrigeracin

Sala Audiovisual

6615.58

409.67

1586.73

Media
(W)
753.70

Oficina 008

776.36

25.72

136.87

54.03

742.26

294.66

775.13

Oficina 009

633.81

25.82

131.26

51.57

710.62

222.57

653.32

Oficina 011

1094.73

38.72

194.62

83.70

1201.77

392.99

1099.9

4961

333.78

1414.69

592.27

6489.65

1560.36

6366.96

Sala Honor

5064.17

385.90

1555.06

811.60

7687.60

1296.37

5355.35

Oficina 014

1196.87

38.90

205.61

59.75

959.50

550.0

1413.0

Oficina 015

1196.87

38.90

205.61

59.75

959.50

550.0

1413.0

Oficina 016

1196.87

38.90

205.61

59.75

959.50

550.0

1413.0

Oficina 017

1196.87

38.90

205.61

59.75

959.50

550.0

1413.0

Oficina 018

1064.86

38.84

198.87

82.97

1198.33

413.66

1148.41

Cafetera y restaurante

25537.68

2214.32

7117.98

5773.19

34697.40

4241.62

25146.90

Gestin Acadmica, Econmica y de Postgrado

9021.98

284.17

1485.84

387.44

6479.22

4138.92

10790.01

Comedor reservado

3697.04

307.51

961.15

785.56

4931.95

666.25

3581.98

Sala de Espera

1774.43

112.50

507.81

224.84

2392.93

532.21

1912.90

Servicio Reprografa

2153.06

64.67

464.10

62.84

894.01

1075.65

2287.09

Sala de Juntas

Caudal (l/s)

Calefaccin
Mxima
puntual (W)
8521.13

Media (W)

Mxima puntual (W)

2180.14

7468.81

22

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1157.26
806
1319
1319
1319
1319
1319
2202
2202
2202
1323
1323
1323
1323
1360
1235
1036
2023
709.75
846.58
1013
623

Ventilacin
Caudal (l/s)
Carga total (W)
37.92
229.65
25.32
165.41
17.68
105.04
17.68
105.04
17.68
105.04
17.68
105.04
17.68
105.04
38
250.16
38
250.16
38
250.16
19
125.31
19
125.31
19
125.31
19
125.31
50
309.88
37.8
242.33
37.9
238.9
63.3
409.71
25.6
157.27
25.32
165
25.33
169.12
25.2
174.38

Media (W)
58.98
24.34
60
60
60
60
60
49.2
49.2
49.2
38
38
38
38
84.5
47.69
50
70
32.56
35.48
30.34
18.6

Calefaccin
Mxima puntual (W)
1039.01
371.22
1274
1274
1274
1274
1274
1146.6
1146.6
1146.6
1201
1201
1201
1201
1385.77
924.67
906.2
1427.5
567.52
659.17
596.25
310.84

Refrigeracin
Media (W)
Mxima puntual (W)
294.04
1093.7
236.69
755.01
121.6
510.8
121.6
510.8
121.6
510.8
121.6
510.8
121.6
510.8
438.66
1495
438.66
1495
438.66
1495
430
1657
430
1657
430
1657
430
1657
361.85
1365.6
367.74
1300.79
302.28
1091.03
582.88
2035.1
183.95
695.82
248.14
843.13
296.5
974.42
301.53
310.84

23

Anexos

1.2.3.7

Julio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6663.38

409.67

1570.07

Media
(W)
300.88

Mxima
puntual (W)
6188.7

Media (W)

Mxima puntual (W)

4678.56

11773.0

Oficina 008

770.16

25.72

128.69

17.01

500.30

571.70

1236.16

Oficina 009

628.06

25.82

122.46

17.66

469.34

455.28

1043.17

Oficina 011

1082.11

38.72

183.60

29.38

777.12

767.74

1737.49

Sala de Juntas

4974.48

333.78

1390.41

225.42

4646.98

3592.29

10308.50

Sala Honor

5064.08

385.90

1542.73

303.72

5558.53

3346.48

9280.19

Oficina 014

1217.3

38.90

192.85

19.29

584.50

1009.70

2125.10

Oficina 015

1217.3

38.90

192.85

19.29

584.50

1009.70

2125.10

Oficina 016

1217.3

38.90

192.85

19.29

584.50

1009.70

2125.10

Oficina 017

1217.3

38.90

192.85

19.29

584.50

1009.70

2125.10

Oficina 018

1077.06

38.84

188.17

28.34

783.70

808.91

1794.92

Cafetera y restaurante

25498.71

2214.32

6715.04

2353.42

26566.60

12540.94

46201.30

Gestin Acadmica, Econmica y de Postgrado

9040.17

284.17

1459.91

145.52

4514.70

7065.40

15578.01

Comedor reservado

3702.85

307.51

1026.86

316.65

3765.75

1940.91

6680.06

Sala de Espera

1777.38

112.50

498.81

84.17

1755.31

1230.91

3156.16

Servicio Reprografa

2170.78

64.67

335.36

13.63

609.11

1828.56

3663.97

24

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1145
814.5
1312.42
1312.42
1312.42
1312.42
1312.42
2245.82
2245.82
2245.82
1347
1347
1347
1347
1371.33
1270
1053.72
1795.42
699
837
999.5
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.67
198.57
25.15
144.3
17.55
92.72
17.55
92.72
17.55
92.72
17.55
92.72
17.55
92.72
37.68
215.42
37.68
215.42
37.68
215.42
18.81
110
18.81
110
18.81
110
18.81
110
50
271.78
37.67
208.93
37.6
206.54
62.8
357.5
25.2
134.98
25.1
142.71
24.98
146.15
25
151.93

Media (W)
20.72
9.72
19.7
19.7
19.7
19.7
19.7
14.8
14.8
14.8
21
21
21
21
11.31
17.54
18.14
22
13.32
13.77
12
8.5

Calefaccin
Mxima puntual (W)
710.52
272.95
817.2
817.2
817.2
817.2
817.2
720
720
720
1100
1100
1100
1100
937.55
610.48
634.48
931
404.24
462.35
395.96
202.26

Refrigeracin
Media (W)
Mxima puntual (W)
550.41
710.52
445.84
1341.55
250.4
921.8
250.4
921.8
250.4
921.8
250.4
921.8
250.4
921.8
791.33
2427.8
791.33
2427.8
791.33
2427.8
580
1960
580
1960
580
1960
580
1960
685.3
2264
674.57
2129.83
680.11
2209.1
1058.56
3347.1
361.34
1185.05
452.5
1404.89
523.83
1592.74
534.6
1542.84

25

Anexos

1.2.3.8

Septiembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7041.9

406.32

1777.48

Media
(W)
895.72

Mxima
puntual (W)
11830.90

Media (W)

Mxima puntual (W)

2659.18

9513.50

Oficina 008

724.2

25.26

136.81

112.34

1340.96

249.72

799.66

Oficina 009

592.99

25.26

133.38

101.09

1184.77

192.40

671.12

Oficina 011

1014.97

37.87

198.15

154.88

1931.89

351.09

1142.21

Sala de Juntas

4674.74

327.60

1472.97

964.30

9730.0

1288.12

6473.40

Sala Honor

5180.36

378.18

1763.43

994.64

10627.20

1449.12

6616.05

Oficina 014

1384.67

38.04

236.83

49

1089.50

876.50

2187.75

Oficina 015

1384.67

38.04

236.83

49

1089.50

876.50

2187.75

Oficina 016

1384.67

38.04

236.83

49

1089.50

876.50

2187.75

Oficina 017

1384.67

38.04

236.83

49

1089.50

876.50

2187.75

Oficina 018

1164.1

37.89

214.98

93.96

1572.58

549.56

1585.35

Cafetera y restaurante

25129.55

2174.63

7060.09

7831.65

51348.10

4001.01

29395.70

Gestin Acadmica, Econmica y de Postgrado

8636.83

278.18

1524.75

688.55

11597.90

3849.0

11411.90

Comedor reservado

3632.39

301.96

1073.15

1091.05

3521.50

622.56

4231.92

Sala de Espera

1795.73

112.71

587.15

290.17

3447.90

575.80

2287.40

Servicio Reprografa

2056.42

62.81

363.87

111.67

1779.89

934.97

2191.98

26

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1049.8
706.14
1260
1260
1260
1260
1260
2537.4
2537.4
2537.4
1496
1496
1496
1496
1426.56
1527.42
1174.1
2048
619.04
766.7
852.31
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.77
207.4
25.31
148.72
17.68
95.26
17.68
95.26
17.68
95.26
17.68
95.26
17.68
95.26
38.11
262.26
38.11
262.26
38.11
262.26
19.02
134.24
19.02
134.24
19.02
134.24
19.02
134.24
50.64
301.57
37.8
245.21
37.8
234.55
63.33
378.24
25.34
140.82
25.6
147.88
25.6
145.22
25.35
157.7

Media (W)
103.87
48.62
91.2
91.2
91.2
91.2
91.2
33
33
33
60
60
60
60
90.88
45.28
51.54
101.8
62.24
65.3
36.77
38.17

Calefaccin
Mxima puntual (W)
1837.2
846.17
1786.2
1786.2
1786.2
1786.2
1786.2
1461
1461
1461
800
800
800
800
1884.14
1339
1316.21
2458
1072.39
1230.24
753.8
764

Refrigeracin
Media (W)
Mxima puntual (W)
254.58
1179.58
196
823.77
111
560
111
560
111
560
111
560
111
560
707
2446
707
2446
707
2446
580
1888
580
1888
580
1888
580
1888
415.94
1693.44
542.57
2043.66
393.3
1524.92
610.51
2475.57
156.56
742.77
216.12
909.24
234.74
984.54
276.74
1001

27

Anexos

1.2.3.9

Octubre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7072.2

403.32

1972.97

Media
(W)
949.95

Mxima
puntual (W)
11654.10

Media (W)

Mxima puntual (W)

2256.76

7951.99

Oficina 008

710.96

25.26

151.69

111.91

1424.07

209.12

639.84

Oficina 009

582.99

25.26

146.10

103.47

1261.22

156.38

521.94

Oficina 011

995.08

37.87

219.07

156.13

2032.41

289.68

911.56

Sala de Juntas

4500.94

327.60

1535.21

1133.22

10054.20

917.63

4585.0

Sala Honor

5239.22

378.18

1903.77

1060.12

10383.10

1223.50

5245.60

Oficina 014

1411.4

38.04

274.53

47.57

1074.25

882.0

2228.50

Oficina 015

1411.4

38.04

274.53

47.57

1074.25

882.0

2228.50

Oficina 016

1411.4

38.04

274.53

47.57

1074.25

882.0

2228.50

Oficina 017

1411.4

38.04

274.53

47.57

1074.25

882.0

2228.50

Oficina 018

1160.07

37.89

244.57

89.55

1603.23

511.96

1485.74

Cafetera y restaurante

25038.39

2174.63

7647.96

8690.21

50876.10

2964.0

22200.90

Gestin Acadmica, Econmica y de Postgrado

8293.27

278.18

1687.37

750.40

12140.80

3148.58

9408.57

Comedor reservado

3562.97

301.96

1143.96

1231.80

7265.03

447.69

3192.12

Sala de Espera

1796.73

112.71

609.19

302.50

3347.48

471.91

1799.38

Servicio Reprografa

1930.26

62.81

440.90

137.63

2365.69

833.31

2013.94

28

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1022
620
1246
1246
1246
1246
1246
2575
2575
2575
1514.5
1514.5
1514.5
1514.5
1432.02
1535
1188.8
2025
597.5
748
810.81
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.92
219.84
25.3
153.91
17.68
102.55
17.68
102.55
17.68
102.55
17.68
102.55
17.68
102.55
38.12
289.12
38.12
289.12
38.12
289.12
19.02
147
19.02
147
19.02
147
19.02
147
50.66
323.44
37.81
269.84
38.86
256.1
62.82
405.61
25
149.3
25.3
157
25.28
156.1
25
165.7

Media (W)
123.51
73.86
107.21
107.21
107.21
107.21
107.21
22.37
22.37
22.37
110
110
110
110
105.05
53.21
57
123.61
73.66
76.53
81.08
53.17

Calefaccin
Mxima puntual (W)
2049.52
1153
1941.2
1941.2
1941.2
1941.2
1941.2
1496.6
1496.6
1496.6
1050
1050
1050
1050
2098.45
1460.46
1408.9
2782.21
1129.85
1324.22
1413.37
1006

Refrigeracin
Media (W)
Mxima puntual (W)
190.31
884.57
124.33
561.71
73.13
406.4
73.13
406.4
73.13
406.4
73.13
406.4
73.13
406.4
655
2378.6
655
2378.6
655
2378.6
470
1800
470
1800
470
1800
470
1800
325.94
1345.44
482.32
1951.47
333.1
1334.75
472.26
2014
112.98
540
162.26
681.36
169.19
718.81
188.19
736.25

29

Anexos

1.2.3.10 Noviembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

6899.95

408.79

Oficina 008

699.5

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
19592.90

Media (W)

Mxima puntual (W)

3725.56

Media
(W)
4477.58

134.94

2647.42

25.68

286.70

614.29

2900.64

4.69

156.41

573.25

25.66

278.33

520.33

2433.95

3.44

131.93

Oficina 011

976.04

38.40

416.37

806.61

3940.52

9.09

266.41

Sala de Juntas

4370.74

331.90

2962.19

4966.56

16619.90

9.20

619.80

Sala Honor

5202.4

383.58

3910.78

4934.21

18009.0

25.11

1173.70

Oficina 014

1349.45

38.54

467.25

364.50

2519.25

207.50

1307.39

Oficina 015

1349.45

38.54

467.25

364.50

2519.25

207.50

1307.39

Oficina 016

1349.45

38.54

467.25

364.50

2519.25

207.50

1307.39

Oficina 017

1349.45

38.54

467.25

364.50

2519.25

207.50

1307.39

Oficina 018

1137.11

37.89

449.63

530.66

3361.18

73.39

710.96

Cafetera y restaurante

24652.25

2174.63

16693.15

30305.75

77854.80

23.03

3003.91

Gestin Acadmica, Econmica y de Postgrado

7992.91

278.18

3072.89

4349.50

24030.10

254.70

3776.48

Comedor reservado

3487.85

301.96

2420.41

4449.49

11453.10

2.65

368.47

Sala de Espera

1790.04

112.71

1147.14

1513.30

6086.66

13.34

471.28

Servicio Reprografa

1773.72

62.81

728.67

1024.06

5563.95

52.52

658.65

Sala Audiovisual

30

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


996.44
598
1130.82
1130.82
1130.82
1130.82
1130.82
2450
2450
2450
1446
1446
1446
1446
1407.47
1429
1136
1940
579
729
778.6
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.48
416.28
25.6
283.33
17.94
197
17.94
197
17.94
197
17.94
197
17.94
197
38.61
480
38.61
480
38.61
480
19.3
242.07
19.3
242.07
19.3
242.07
19.3
242.07
51.38
587.11
38.61
456.22
38.55
446.9
64.16
723.86
26.4
275.14
26.4
291.51
26.7
288.42
25.55
295.41

Media (W)
677.04
471.28
491
491
491
491
491
363.6
363.6
363.6
560.1
560.1
560.1
560.1
714.7
402.95
429.27
891.52
442.61
494.52
532.1
439.93

Calefaccin
Mxima puntual (W)
4185
2575
3644.4
3644.4
3644.4
3644.4
3644.4
3878.66
3878.66
3878.66
1880
1880
1880
1880
4746.06
3300
3254.71
6173.5
2390.46
3036.77
3793.6
2722.46

Refrigeracin
Media (W)
Mxima puntual (W)
9.15
174.18
7.13
59
5.74
233.2
5.74
233.2
5.74
233.2
5.74
233.2
5.74
233.2
125.82
1271.6
125.82
1271.6
125.82
1271.6
98
900
98
900
98
900
98
900
23.1
406
75.27
859.5
36.76
503.4
36
674
7.29
75.62
9.03
120.34
8.6
121.96
10.88
140

31

Anexos

1.2.3.11 Diciembre
Recinto

Ventilacin

Carga interna (W)

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

Mxima puntual (W)

Sala Audiovisual

6758.2

408.79

4754.91

7563.67

21375.02

Oficina 008

694.25

25.68

370.49

1005.31

3267.50

Oficina 009

568.71

25.66

359.55

831.26

2719.98

Oficina 011

966.8

38.40

536.44

1316.46

4397.41

Sala de Juntas

4334.82

331.90

3816.93

7530.80

18075.50

Sala Honor

5174.1

383.58

4643.79

7785.90

19814.40

Oficina 014

1313.72

38.54

582.06

775.15

3321.27

Oficina 015

1313.72

38.54

582.06

775.15

3321.27

Oficina 016

1313.72

38.54

582.06

775.15

3321.27

Oficina 017

1313.72

38.54

582.06

775.15

3321.27

Oficina 018

1124.16

37.89

566.45

978.34

3918.63

Cafetera y restaurante

24613.05

2174.63

22013.66

43776.34

83292.10

Gestin Acadmica, Econmica y de Postgrado

7880.14

278.18

3918.47

7711.30

26870.10

Comedor reservado

3467.59

301.96

3183.18

6449.80

12336.10

Sala de Espera

1788.04

112.71

1475.22

2437.94

6698.56

Servicio Reprografa

1726.99

62.81

927.84

1892.67

6321.50

32

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


984.31
1107
1724
1724
1724
1724
1724
2312
2312
2312
1624
1624
1624
1624
1816
968
946
1652
584
746
753
624

Caudal (l/s)
38.75
25.85
18.05
18.05
18.05
18.05
18.05
38.36
38.36
38.36
19.44
19.44
19.44
19.44
51.67
38.4
38.32
63.2
26.11
25.6
25.3
25.8

Ventilacin
Carga total (W)
541.11
366.1
257
257
257
257
257
591.11
591.11
591.11
302
302
302
302
756.1
573.08
566.82
928.22
355
373.9
372.84
377.1

Media (W)
1037.42
727.1
710.6
710.6
710.6
710.6
710.6
744
744
744
710
710
710
710
1185.5
1185
744.14
1517.97
680
782.2
842.2
731.82

Calefaccin
Mxima puntual (W)
4691.91
2916
4035.4
4035.4
4035.4
4035.4
4035.4
4904
4904
4904
4100
4100
4100
4100
5418.7
3952.4
3840.18
7075.61
2689
3449
3633
3150

33

Anexos

1.2.4

Resultados simulacin del edificio con la mejora de acristalamiento doble

1.2.4.1

Enero
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6807.80

409.67

4722.05

Media
(W)
7470.45

Mxima
puntual (W)
21302.60

Media (W)

Mxima puntual (W)

Oficina 008

696.60

25.72

370.12

959.60

3069.04

Oficina 009

570.63

25.82

358.58

788.86

2558.31

Oficina 011

971.03

38.72

535.28

1242.17

4163.30

Sala de Juntas

4350.94

333.78

3807.41

7402.70

17815.70

Sala Honor

5174.58

385.90

4615.19

7757.56

19727.0

Oficina 014

1312.04

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 015

1312.04

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 016

1312.04

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 017

1312.04

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 018

1119.0

38.84

561.50

998.18

3822.09

Cafetera y restaurante

24968.70

2214.32

21961.65

43239.29

82819.10

Gestin Acadmica, Econmica y de Postgrado

7922.52

284.17

3907.38

7550.58

25966.40

Comedor reservado

3475.97

307.51

3176.49

6370.23

12202.30

Sala de Espera

1786.01

112.50

436.85

2458.59

6644.31

Servicio Reprografa

1741.58

64.67

926.09

1852.67

6015.43

34

Anexos

Recinto
OFICINA 103-104

Carga interna (W)


974.96

Ventilacin
Caudal (l/s)
Carga total (W)
38.76
547

Calefaccin
Media (W)
Mxima puntual (W)
1002.86
4617.86

OFICINA 101

590

25.85

405

732.08

2772.85

OFICINA 102

1219

18.06

267

697.36

3841.6

OFICINA 105

1219

18.06

267

697.36

3841.6

OFICINA 106

1219

18.06

267

697.36

3841.6

OFICINA 107

1219

18.06

267

697.36

3841.6

OFICINA 108

1219

18.06

267

697.36

3841.6

OFICINA 109

2251.2

38.92

598

723.66

4528.65

OFICINA 110

2251.2

38.92

598

723.66

4528.65

OFICINA 113

2251.2

38.92

598

723.66

4528.65

OFICINA 111

1340.75

19.47

301.58

750

4377.3

OFICINA 112

1340.75

19.47

301.58

750

4377.3

OFICINA 115

1340.75

19.47

301.58

750

4377.3

OFICINA 116

1340.75

19.47

301.58

750

4377.3

OFICINA 117

1378.56

51.75

753

1240.33

5307.66

OFICINA 118

1270.42

38.89

573

750.25

3616.89

OFICINA 119

1059.1

38.88

766.68

792

3612.1

OFICINA 120

1832.24

64.68

935.64

1502.64

6681.81

OFICINA 121

562.27

25.84

359

658.92

2503

OFICINA 122

714.61

25.87

381.55

777.83

3259

OFICINA 123

753

25.86

378.94

814.4

3385.1

OFICINA 124

624

25.6

383.2

731.03

2993.06

35

Anexos

1.2.4.2

Febrero
Recinto

Ventilacin

Carga interna (W)

Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7061.35

409.67

4165.88

Media
(W)
5223.27

Mxima
puntual (W)
21472.80

Media (W)

Mxima puntual (W)

Oficina 008

706.36

25.72

324.94

679.30

2960.80

Oficina 009

578.91

25.82

314.36

568.41

2512.56

Oficina 011

987.47

38.72

469.40

881.03

4062.26

Sala de Juntas

4439.63

333.78

3341.96

5600.97

18101

Sala Honor

5240.17

385.90

4059.51

5758.65

19635.80

Oficina 014

1402.72

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 015

1402.72

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 016

1402.72

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 017

1402.72

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 018

1161.45

38.84

503.19

653.34

3489.36

Cafetera y restaurante

25043.54

2214.32

18877.49

34046.57

86507.40

Gestin Acadmica, Econmica y de Postgrado

8189.95

284.17

3462.16

4949.43

24628

Comedor reservado

3531.10

307.51

2749.63

4968.70

12653.60

Sala de Espera

1795.77

112.50

1287.22

1787.39

6571.80

Servicio Reprografa

1859.97

64.67

819.28

1097.60

5673.03

36

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


991.96
600
1229
1229
1229
1229
1229
2394
2394
2394
1416
1416
1416
1416
1398
1395
1120
1916
577
729
775
624.04

Ventilacin
Caudal (l/s)
Carga total (W)
38.61
484
25.75
329.1
18
232.7
18
232.7
18
232.7
18
232.7
18
232.7
38.81
559.34
38.81
559.34
38.81
559.34
19.41
282.32
19.41
282.32
19.41
282.32
19.41
282.32
51.56
669.3
38.75
524
38.71
508.6
64.45
832.1
25.73
320
25.77
337.1
25.76
335.47
25.8
341

Media (W)
733
530.02
546.8
546.8
546.8
546.8
546.8
411.6
411.6
411.6
430
430
430
430
865.62
443.26
491.14
1002.4
477.1
551.7
574.65
484.46

Calefaccin
Mxima puntual (W)
4189.03
2589.04
3714
3714
3714
3714
3714
3644
3644
3644
4105
4105
4105
4105
4830
3200
3247.4
6085.21
2376.74
3010.5
3136.76
2691.24

Media (W)
0
0
1.62
1.62
1.62
1.62
1.62
33.12
33.12
33.12
38.7
38.7
38.7
38.7
0
14.28
1.93
0.48
0
0
0.01
0.01

Refrigeracin
Mxima puntual (W)
1.26
0.3
49.6
49.6
49.6
49.6
49.6
500
500
500
517.6
517.6
517.6
517.6
5
301.8
104.3
66.31
1.5
1.1
2.3

37

Anexos

1.2.4.3

Marzo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7060.37

409.67

3463.30

Media
(W)
3262.13

Mxima
puntual (W)
16260.50

Media (W)

Mxima puntual (W)

Oficina 008

718.79

25.72

270.60

407.70

2124.28

Oficina 009

589.24

25.82

261.48

353.04

1793.16

Oficina 011

1007.81

38.72

392.24

538.35

2900.34

Sala de Juntas

4591.59

333.78

2764.85

3606.63

13539.20

Sala Honor

5204.23

385.90

3319.46

3770.23

14670.70

Oficina 014

1390.16

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 015

1390.16

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 016

1390.16

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 017

1390.16

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 018

1154.61

38.84

427.57

381.85

381.85

52.97

435.64

Cafetera y restaurante

25128.63

2214.32

14988.60

23895.25

69298.80

Gestin Acadmica, Econmica y de Postgrado

8470.35

284.17

3008.16

2765.51

17144.10

345.98

3031.67

Comedor reservado

3600.61

307.51

2206.38

3425.60

9976.62

Sala de Espera

1795.21

112.50

1060.01

1137.72

4798.40

Servicio Reprografa

1997.63

64.67

716.0

508.57

3493.57

80.99

573.84

38

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1012.96
642
1240
1240
1240
1240
1240
2365
2365
2365
1403
1403
1403
1403
1392.56
1381
1106
1932
589
740
803
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.4
402.3
25.62
272.56
17.9
193.85
17.9
193.85
17.9
193.85
17.9
193.85
17.9
193.85
38.56
482.5
38.56
482.5
38.56
482.5
19.3
242.1
19.3
242.1
19.3
242.1
19.3
242.1
51.25
546.42
38.5
452.3
38.41
430.1
64.1
698.2
25.6
265.9
25.63
280.87
25.63
279.3
25.66
285.92

Media (W)
442.5
296.06
361
361
361
361
361
200
200
200
214
214
214
214
494.14
227.19
267.76
533.54
284.9
318.03
320.3
233.43

Calefaccin
Mxima puntual (W)
3012
1789.22
2760.4
2760.4
2760.4
2760.4
2760.4
2412
2412
2412
2800
2800
2800
2800
3480.1
2128.12
2209.36
4230
1660
2124.73
2179.81
1652.67

Media (W)
9.22
6.96
3.93
3.93
3.93
3.93
3.93
104.7
104.7
104.7
121
121
121
121
11.27
65.65
26.42
26.29
7.28
8.42
9.16
9.84

Refrigeracin
Mxima puntual (W)
114.7
44.71
321.72
321.72
321.72
321.72
321.72
782.66
782.66
782.66
901
901
901
901
164.75
556.37
285.64
409.24
45.85
75.87
96.24
109.95

39

Anexos

1.2.4.4

Abril
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6883.57

409.67

2478.51

Media
(W)
2016.68

Mxima
puntual (W)
13015.90

Media (W)

Mxima puntual (W)

545.43

3843.13

Oficina 008

736.95

25.72

201.82

218.57

1712.65

61.12

376.90

Oficina 009

603.19

25.82

192.67

197.22

1459.10

44.31

300.48

Oficina 011

1035.48

38.72

289.92

301.32

2366.10

87.66

535.58

Sala de Juntas

4743.17

333.78

2008.72

2057.51

10578.90

240.73

2380.58

Sala Honor

5117.96

385.90

2350.93

2310.84

11769.10

200.08

2113.07

Oficina 014

1303.54

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 015

1303.54

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 016

1303.54

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 017

1303.54

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 018

1116.89

38.84

312.56

230.31

2149.80

147.33

740.10

Cafetera y restaurante

25260.37

2214.32

9924.85

14919.75

54514.80

356.98

8512.58

Gestin Acadmica, Econmica y de Postgrado

8680.36

284.17

2287.93

1421.03

14106.50

1310.75

5930.37

Comedor reservado

3640.62

307.51

1498.79

2100.28

7838.73

52.76

1195

Sala de Espera

1786.87

112.50

767.17

679.51

3952.50

100.26

838.50

Servicio Reprografa

2065.66

64.67

553.20

263.71

3002.37

358.24

1218.37

40

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1040.96
729
1255
1255
1255
1255
1255
2235
2235
2235
1336
1336
1336
1336
1370
1282
1057
1910
1403
762
844
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.22
303.9
25.46
211.1
17.77
144.1
17.77
144.1
17.77
144.1
17.77
144.1
17.77
144.1
38.26
358.6
38.26
358.6
38.26
358.6
19.13
180.55
19.13
180.55
19.13
180.55
19.13
180.55
50.88
419.88
38.24
340.1
38.2
325.1
63.88
538.7
25.43
200.7
25.46
214.5
25.46
216.5
25.5
225.61

Media (W)
223.4
123.1
194.57
194.57
194.57
194.57
194.57
120
120
120
117
117
117
117
273.57
126.52
148.7
271.22
139.13
155.48
145.23
103.03

Calefaccin
Mxima puntual (W)
2517.84
1421.72
2340
2340
2340
2340
2340
2348.33
2348.33
2348.33
2390.7
2390.7
2390.7
2390.7
3119.85
1908.66
1981.04
3611.14
1369.13
1757.89
1754.64
1423.35

Media (W)
53.61
40
17.3
17.3
17.3
17.3
17.3
181.46
181.46
181.46
198
198
198
198
73.02
136.05
85.3
139.31
31.5
46.4
56.32
62.31

Refrigeracin
Mxima puntual (W)
593.7
362.3
251.4
251.4
251.4
251.4
251.4
1101
1101
1101
1310
1310
1310
1310
732
897.85
647.98
1165.34
355.14
463
519
438.27

41

Anexos

1.2.4.5

Mayo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6721.59

409.67

1852.07

Media
(W)
679.03

Mxima
puntual (W)
9317.70

Media (W)

Mxima puntual (W)

1822.20

7020.40

Oficina 008

758.60

25.72

157.25

48.29

800.70

262.41

763

Oficina 009

620.63

25.82

147.98

47.16

754.37

194.51

635.99

Oficina 011

1066.47

38.72

223.19

75.59

1246.34

346.15

1073.13

Sala de Juntas

4873.60

333.78

1570.05

592.89

7451.24

1224.38

5777.77

Sala Honor

5069.92

385.90

1738.13

737.17

8453.75

1120.43

5285.60

Oficina 014

1230.53

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 015

1230.53

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 016

1230.53

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 017

1230.53

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 018

1077.39

38.84

234.23

66.47

1169.46

377.17

1096.25

Cafetera y restaurante

25416.93

2214.32

8420.41

5584.15

40250.60

3375.58

24552

Gestin Acadmica, Econmica y de Postgrado

8849.29

284.17

1810.69

375.42

7786.41

3488.85

10012.80

Comedor reservado

3668.28

307.51

1083.18

762.99

5749.89

515.88

3477.83

Sala de Espera

1778.59

112.50

572.37

199.70

2627.14

457.53

1839.41

Servicio Reprografa

2108.79

64.67

427.46

62.40

1429.62

905.04

2194.67

42

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1076.96
734
1274
1274
1274
1274
1274
2131
2131
2131
1282
1282
1282
1282
1348
1186
984
1904
640
785
895
623

Ventilacin
Caudal (l/s)
Carga total (W)
37.87
263.02
25.27
186.7
17.61
134.5
17.61
134.5
17.61
134.5
17.61
134.5
17.61
134.5
38
302.14
38
302.14
38
302.14
18.96
147.43
18.96
147.43
18.96
147.43
18.96
147.43
50.27
320.07
37.93
281.45
37.8
274.5
62.5
467.7
25.34
175.88
25.34
187.4
25.28
191.4
25.5
196.82

Media (W)
54.1
25
55
55
55
55
55
36.8
36.8
36.8
37
37
37
37
71.82
38.71
42.65
65.73
31.72
33.45
30.1
21.41

Calefaccin
Mxima puntual (W)
1411.54
673
1376
1376
1376
1376
1376
1533.97
1533.97
1533.97
1110.4
1110.4
1110.4
1110.4
1932
1317.86
1327.57
2104
793.12
1033
951
675.92

Media (W)
261.63
201.93
104
104
104
104
104
423.33
423.33
423.33
400
400
400
400
327.98
352.53
281.92
524.53
163.3
223.83
260.36
257.4

Refrigeracin
Mxima puntual (W)
1411.54
735.87
533.8
533.8
533.8
533.8
533.8
1489.66
1489.66
1489.66
1470
1470
1470
1470
1353.2
1297.06
1113.92
2072.36
724.86
880.76
989.43
881

43

Anexos

1.2.4.6

Junio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6631.40

402.75

1586.73

Media
(W)
772.36

Mxima
puntual (W)
8536.42

Media (W)

Mxima puntual (W)

2062.92

7155.72

Oficina 008

776.36

25.72

136.87

54.96

740.06

286.11

745.19

Oficina 009

633.81

25.26

131.26

51.81

705.95

215.98

627.01

Oficina 011

1094.73

37.88

194.62

84.08

1189.99

380.05

1054.65

Sala de Juntas

4961.0

327.61

1414.69

602.04

6478.64

1474.81

6020.82

Sala Honor

5064.17

377.75

1555.06

827.01

7721.66

1272.64

5278.53

Oficina 014

1196.87

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 015

1196.87

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 016

1196.87

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 017

1196.87

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 018

1064.86

37.89

198.87

87.27

1203.41

381.96

1059.04

Cafetera y restaurante

25537.68

2173.21

7117.98

5846.48

34849.10

4181.38

24945.90

Gestin Acadmica, Econmica y de Postgrado

9021.98

278.23

1485.84

386.94

6402.94

3928.79

10138.60

Comedor reservado

3697.04

301.81

961.15

799.67

4941.28

639.11

3516.45

Sala de Espera

1774.43

113.44

507.81

232.54

2416.79

517.60

1871.48

Servicio Reprografa

2153.06

63.26

464.10

69.72

923.21

999.40

2111.55

44

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1098.96
753
1287
1287
1287
1287
1287
2084
2084
2084
1259
1259
1259
1259
1341
1141
993
1911
662
803
931
623

Ventilacin
Caudal (l/s)
Carga total (W)
37.93
230.5
25.32
161.4
17.68
105.1
17.68
105.1
17.68
105.1
17.68
105.1
17.68
105.1
38
245.12
38
245.12
38
245.12
19
124.57
19
124.57
19
124.57
19
124.57
50.55
307.6
38
250.7
37.95
237.4
63.3
407.4
25.3
157.75
25.31
164.7
25.34
169.12
25
172

Media (W)
56.79
25.35
59.2
59.2
59.2
59.2
59.2
48.58
48.58
48.58
30
30
30
30
88.43
46.91
50.92
69.8
31.46
35.32
29.16
19.42

Calefaccin
Mxima puntual (W)
986.42
373.12
1101.4
1101.4
1101.4
1101.4
1101.4
1094
1094
1094
1340
1340
1340
1340
1414
877.9
889.15
1375.1
536.46
634
558.13
310.6

Media (W)
290.79
222.61
118.5
118.5
118.5
118.5
118.5
410
410
410
425
425
425
425
350.24
345
290.31
565.34
178.86
241.75
285.51
281.35

Refrigeracin
Mxima puntual (W)
1060
373.12
495.6
495.6
495.6
495.6
495.6
1377.6
1377.6
1377.6
1701
1701
1701
1701
1337.11
1200.43
1040
1955.22
655.93
812
926.82
848.37

45

Anexos

1.2.4.7

Julio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6679.20

400.48

1570.07

Media
(W)
306.84

Mxima
puntual (W)
6190.98

Media (W)

Mxima puntual (W)

4465.24

11339.50

Oficina 008

770.16

25.08

128.69

17.68

514.05

542.45

1164.09

Oficina 009

628.06

25.26

122.46

17.98

477.41

433.31

986.64

Oficina 011

1082.11

37.61

183.60

29.62

783.24

729.41

1632.87

Sala de Juntas

4974.48

325.78

1390.41

227.25

4623.89

3441.73

9874.36

Sala Honor

5064.08

375.49

1542.73

311.17

5593.12

3273.10

9123.14

Oficina 014

1217.30

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 015

1217.30

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 016

1217.30

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 017

1217.30

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 018

1077.06

37.89

188.17

29.82

809.13

746.99

1649.97

Cafetera y restaurante

25498.71

2162.11

6715.04

2380.76

26702.10

12353.97

45762.20

Gestin Acadmica, Econmica y de Postgrado

9040.17

276.33

1459.91

147.66

4564.34

6676.41

14663.10

Comedor reservado

3702.85

300.22

1026.86

321.67

3772.65

1878.69

6553.39

Sala de Espera

1777.38

112.71

498.81

88.17

1797.46

1192.78

3077.29

Servicio Reprografa

2170.78

62.81

335.36

16.56

677.06

1694.79

3353.43

46

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1088.96
759
1283
1283
1283
1283
1283
2114
2114
2114
1274
1274
1274
1274
1346.25
1164
1003
1915
653
800
922
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.67
197.7
25.14
142.1
17.55
92.58
17.55
92.58
17.55
92.58
17.55
92.58
17.55
92.58
37.72
212.62
37.72
212.62
37.72
212.62
18.86
107.3
18.86
107.3
18.86
107.3
18.86
107.3
50.21
258.4
37.7
206.1
37.68
203.54
62.86
354.12
25.34
135.06
25.14
141.07
25.34
145.45
25.17
149.47

Media (W)
20.35
10.16
19.6
19.6
19.6
19.6
19.6
14.7
14.7
14.7
20
20
20
20
27.81
17.57
18.73
22.2
13.18
13.97
11.82
8.83

Calefaccin
Mxima puntual (W)
696.82
285.15
816.4
816.4
816.4
816.4
816.4
720
720
720
1050
1050
1050
1050
976.74
634.97
651.43
931.95
393.6
464.3
381.9
220.34

Media (W)
529.63
418.08
240
240
240
240
240
734.3
734.3
734.3
601
601
601
601
660.31
626.25
537.73
1011.47
344.51
432.3
496.61
500.12

Refrigeracin
Mxima puntual (W)
1742.43
1252
874
874
874
874
874
2242.6
2242.6
2242.6
1999
1999
1999
1999
2194
1955.91
1710
3181.91
1116.75
1332.86
1494.36
1439.56

47

Anexos

1.2.4.8

Septiembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7057.72

406.32

1777.48

Media
(W)
911.43

Mxima
puntual (W)
11825.90

Media (W)

Mxima puntual (W)

2501.66

9021.35

Oficina 008

724.20

25.26

136.81

104.28

1250.16

250.17

778.37

Oficina 009

592.99

25.26

133.38

93.65

1109.46

193.05

653.19

Oficina 011

1014.97

37.87

198.15

143.49

1804.14

350.69

1106.43

Sala de Juntas

4674.74

327.60

1472.97

956.57

9604.84

1239.89

6237.11

Sala Honor

5180.36

378.18

1763.43

1007.85

10615.30

1395.94

6442.23

Oficina 014

1384.67

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 015

1384.67

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 016

1384.67

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 017

1384.67

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 018

1164.10

37.89

214.98

95.67

1546.57

506.94

1453.44

Cafetera y restaurante

25129.55

2174.63

7060.09

7819.27

51151.4

3961.50

29213.10

Gestin Acadmica, Econmica y de Postgrado

8636.83

278.18

1524.75

679.89

11196.20

3714.75

10780.60

Comedor reservado

3632.39

301.96

1073.15

1095.42

7274.77

599.95

4154.99

Sala de Espera

1795.73

112.71

587.15

295.44

3450.58

556.55

2222.21

Servicio Reprografa

2056.42

62.81

363.87

116.10

1833.69

983.70

2318.61

48

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1020.96
673
1244
1244
1244
1244
1244
2345
2345
2345
1393
1393
1393
1393
1389.56
1370
1100
1937
594
745
814
624

Ventilacin
Caudal (l/s)
Carga total (W)
38
210.4
25.31
148.72
17.68
96.51
17.68
96.51
17.68
96.51
17.68
96.51
17.68
96.51
38.1
258.67
38.1
258.67
38.1
258.67
19
130.43
19
130.43
19
130.43
19
130.43
50.63
298.8
38.05
242.51
38
243.74
63.34
349.5
25.3
142.88
25.6
149.12
25.34
149.61
25.35
158.07

Media (W)
94.21
47.3
86.25
86.25
86.25
86.25
86.25
32.05
32.05
32.05
57.3
57.3
57.3
57.3
94.3
44.01
52.06
97.61
56.4
60.82
58.77
35.5

Calefaccin
Mxima puntual (W)
1690.39
808.13
1694.6
1694.6
1694.6
1694.6
1694.6
1371.61
1371.61
1371.61
801.63
801.63
801.63
801.63
1891.7
1259.06
1286.13
2332.71
983.89
1145.3
1147.04
716.84

Refrigeracin
Media (W)
Mxima puntual (W)
258.07
1149.85
189.76
808.13
110
544.2
110
544.2
110
544.2
110
544.2
110
544.2
658.27
2230.78
658.27
2230.78
658.27
2230.78
585
1907.11
585
1907.11
585
1907.11
585
1907.11
400.04
1638.47
505.83
1877.13
372.43
1435.3
597.05
2368.08
156.18
715.47
215.43
883
234.84
949.26
264.45
955

49

Anexos

1.2.4.9

Octubre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7088.02

403.32

1972.97

Media
(W)
956.20

Mxima
puntual (W)
11609.80

Media (W)

Mxima puntual (W)

2138.87

7527.75

Oficina 008

710.96

25.26

151.69

100.99

1328.11

214.04

624.47

Oficina 009

582.99

25.26

146.10

93.60

1184.95

159.57

510.26

Oficina 011

995.08

37.87

219.07

141.39

1908.37

294.19

885.02

Sala de Juntas

4500.94

327.60

1535.21

1114.71

9930.03

865.98

4429.53

Sala Honor

5239.22

378.18

1903.77

1068.29

10390.80

1180.34

5084.59

Oficina 014

1411.40

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 015

1411.40

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 016

1411.40

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 017

1411.40

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 018

1160.07

37.89

244.57

89.12

1557.13

478.37

1361.21

Cafetera y restaurante

25038.39

2174.63

7647.96

8652.82

50658.50

2946.33

22089.90

Gestin Acadmica, Econmica y de Postgrado

8293.27

278.18

1687.37

723.65

11620.70

3087.57

8916.85

Comedor reservado

3562.97

301.96

1143.96

1228.61

7224.79

435.80

3140.19

Sala de Espera

1796.73

112.71

609.19

304.33

3339.96

461.07

1751.67

Servicio Reprografa

1930.26

62.81

440.90

134.33

2262.74

800.73

1902.46

50

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1000
607
1232
1232
1232
1232
1232
2409
2409
2409
1425
1425
1425
1425
1400.56
1409
1125
1932
583
729
782.54
624

Ventilacin
Caudal (l/s)
Carga total (W)
38
224.85
25.31
154.78
17.7
103.75
17.7
103.75
17.7
103.75
17.7
103.75
17.7
103.75
38.12
288.63
38.12
288.63
38.12
288.63
19.07
146.2
19.07
146.2
19.07
146.2
19.07
146.2
50.65
321.45
38.07
269.7
38
246.36
63.34
408.96
25.3
151.07
25.32
159.7
25.32
159.32
25.6
167.85

Media (W)
110.96
69.13
100.2
100.2
100.2
100.2
100.2
35.93
35.93
35.93
140.62
140.62
140.62
140.62
107.18
49.86
56.27
117.1
65.93
70.23
72.14
50.62

Calefaccin
Mxima puntual (W)
1901.81
1089.22
1851.8
1851.8
1851.8
1851.8
1851.8
1372.3
1372.3
1372.3
1141.17
1141.17
1141.17
1141.17
2089.61
1354.48
1357.12
2628.17
1037.9
1231.77
1287.86
945.84

Refrigeracin
Media (W)
Mxima puntual (W)
195.92
864.15
125.59
548.91
79.2
396.37
79.2
396.37
79.2
396.37
79.2
396.37
79.2
396.37
613.8
2201.6
613.8
2201.6
613.8
2201.6
451
1805.3
451
1805.3
451
1805.3
451
1805.3
318.92
1303.56
456.11
1787.88
317.97
1250.81
467.41
1922.39
115.64
523.74
165.25
665.25
173.07
696.72
183.57
703.26

51

Anexos

1.2.4.10 Noviembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6915.77

408.79

3725.56

Media
(W)
4459.09

Mxima
puntual (W)
19460.10

Media (W)

Mxima puntual (W)

120.35

2473.32

Oficina 008

699.50

25.68

286.70

553.61

2750.56

6.44

166.59

Oficina 009

573.25

25.66

278.33

472.20

2317.8

4.41

140.04

Oficina 011

976.04

38.40

416.37

727.80

3754.94

11.53

276.53

Sala de Juntas

4370.74

331.90

2962.19

4,865.02

16424.9

9.89

613.09

Sala Honor

5202.40

383.58

3910.78

4,907.31

17899.7

23.47

1116.16

Oficina 014

1349.45

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 015

1349.45

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 016

1349.45

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 017

1349.45

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 018

1137.11

37.89

449.63

516.95

3297.25

65.45

650.33

Cafetera y restaurante

24652.25

2174.63

16693.15

30,101.41

77504.6

23.24

3014.5

Gestin Acadmica, Econmica y de Postgrado

7992.91

278.18

3072.89

4,097.54

23268.6

255.90

3615.05

Comedor reservado

3487.85

301.96

2420.41

4,411.36

11372.5

2.55

363.71

Sala de Espera

1790.04

112.71

1147.14

1,499.39

6038.9

12.77

456.14

Servicio Reprografa

1773.72

62.81

728.67

956.93

5360.27

54.12

5360.27

52

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


977.96
591
1221
1221
1221
1221
1221
2315
2315
2315
1374
1374
1374
1374
1381.56
1323
1087
1867
564
716
758
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.2
423.65
25.68
287.1
17.95
200.4
17.95
200.4
17.95
200.4
17.95
200.4
17.95
200.4
38.65
483.78
38.65
483.78
38.65
483.78
19.33
244.17
19.33
244.17
19.33
244.17
19.33
244.17
51.4
589.6
38.61
460.78
38.58
448.5
64.25
733.4
25.6
281.7
25.9
294.78
25.34
293.46
25.4
299

Media (W)
610
439.22
459.2
459.2
459.2
459.2
459.2
334
334
334
550
550
550
550
703.12
370.14
412.56
831.57
400.8
453.55
477.8
411.74

Calefaccin
Mxima puntual (W)
3954.1
2462.3
3508.2
3508.2
3508.2
3508.2
3508.2
3708.3
3708.3
3708.3
1780.1
1780.1
1780.1
1780.1
4692.28
3134.87
3158.55
5927.64
2249.84
2880.83
2996.91
2602.51

Refrigeracin
Media (W)
Mxima puntual (W)
10.35
188.11
7.45
65
5.97
229
5.97
229
5.97
229
5.97
229
5.97
229
119.3
1195.6
119.3
1195.6
119.3
1195.6
101
981.3
101
981.3
101
981.3
101
981.3
22.63
386.84
72.17
807.71
35.79
468.09
37.9
653.31
7.63
81.72
10.11
127.7
9.73
130.57
11.54
138.12

53

Anexos

1.2.4.11 Diciembre
Recinto

Ventilacin

Carga interna (W)

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

Mxima puntual (W)

Sala Audiovisual

6774.02

408.79

4754.91

7,484.26

21215.7

Oficina 008

694.25

25.68

370.49

916.63

3107.26

Oficina 009

568.71

25.66

359.55

761.94

2596.02

Oficina 011

966.80

38.40

536.44

1199.01

4200.22

Sala de Juntas

4334.82

331.90

3816.93

7,374.81

17865.8

Sala Honor

5174.10

383.58

4643.79

7,713.87

19638.6

Oficina 014

1313.72

38.54

582.06

737.71

3200.65

Oficina 015

1313.72

38.54

582.06

737.71

3200.65

Oficina 016

1313.72

38.54

582.06

737.71

3200.65

Oficina 017

1313.72

38.54

582.06

737.71

3200.65

Oficina 018

1124.16

37.89

566.45

950.26

3826.97

Cafetera y restaurante

24613.05

2174.63

22013.66

43,468.61

82897

Gestin Acadmica, Econmica y de Postgrado

7880.14

278.18

3918.47

7,288.71

26052.7

Comedor reservado

3467.59

301.96

3183.18

6,387.32

12245.2

Sala de Espera

1788.04

112.71

1475.22

2,410.77

6628.92

Servicio Reprografa

1726.99

62.81

927.84

1,769.52

6093.33

54

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


968.96
588
1217
1217
1217
1217
1217
2245
2245
2245
1338
1338
1338
1338
1368.56
1269
1054
1824
558
709
745
624

Caudal (l/s)
38.8
25.86
18.08
18.08
18.08
18.08
18.08
38.96
38.96
38.96
19.5
19.5
19.5
19.5
51.8
38.89
38.89
64.72
25.83
25.89
25.88
25.9

Ventilacin
Carga total (W)
550
370.77
260.81
260.81
260.81
260.81
260.81
605.26
605.26
605.26
304.6
304.6
304.6
304.6
758.7
579.62
569.8
939.7
359.44
387.12
382.6
381.1

Media (W)
949.84
686.48
668.02
668.02
668.02
668.02
668.02
342
342
342
680.1
680.1
680.1
680.1
1165.7
705.86
745.88
1426
626.97
728.19
769.84
690.73

Calefaccin
Mxima puntual (W)
4446.44
2796.42
3890.6
3890.6
3890.6
3890.6
3890.6
4666.67
4666.67
4666.67
4010.18
4010.18
4010.18
4010.18
5343.6
3749.84
3714.92
6789.44
2540.8
3283.65
3425.62
3020.48

55

Anexos

1.2.5

Resultados simulacin del edificio con la mejora de voladizo

1.2.5.1

Enero
Recinto

Ventilacin

Carga interna (W)

Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6818.84

409.67

4722.05

Media
(W)
7470.45

Mxima
puntual (W)
21302.60

Media (W)

Mxima puntual (W)

Oficina 008

707.64

25.72

370.12

959.60

3069.04

Oficina 009

581.67

25.82

358.58

788.86

2558.31

Oficina 011

982.07

38.72

535.28

1242.17

4163.30

Sala de Juntas

4361.98

333.78

3807.41

7402.70

17815.70

Sala Honor

5185.62

385.90

4615.19

7757.56

19727.0

Oficina 014

1323.08

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 015

1323.08

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 016

1323.08

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 017

1323.08

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 018

1130.04

38.84

561.50

998.18

3822.09

Cafetera y restaurante

24979.74

2214.32

21961.65

43239.29

82819.10

Gestin Acadmica, Econmica y de Postgrado

7933.56

284.17

3907.38

7550.58

25966.40

Comedor reservado

3487.01

307.51

3176.49

6370.23

12202.30

Sala de Espera

1797.05

112.50

436.85

2458.59

6644.31

Servicio Reprografa

1752.62

64.67

926.09

1852.67

6015.43

56

Anexos

Recinto

Carga interna (W)

Ventilacin

Calefaccin

OFICINA 103-104

987

Caudal (l/s)
38.75

Carga total (W)


551.3

Media (W)
1083.95

Mxima puntual (W)


4606.91

OFICINA 101

593

25.84

372.8

774.73

2891.7

OFICINA 102

1226

18

264.110

735.6

3976.6

OFICINA 105

1226

18

264.110

735.6

3976.6

OFICINA 106

1226

18

264.110

735.6

3976.6

OFICINA 107

1226

18

264.110

735.6

3976.6

OFICINA 108

1226

18

264.110

735.6

3976.6

OFICINA 109

2249

38.88

594.61

788.2

4749.33

OFICINA 110

2249

38.88

594.61

788.2

4749.33

OFICINA 113

2249

38.88

594.61

788.2

4749.33

OFICINA 111

1340

19.45

300

810

4555.66

OFICINA 112

1340

19.45

300

810

4555.66

OFICINA 115

1340

19.45

300

810

4555.66

OFICINA 116

1340

19.45

300

810

4555.66

OFICINA 117

1367.56

51.76

763

1280.66

5394.61

OFICINA 118

1280

38.85

575.17

831.87

3856.08

OFICINA 119

1067

38.83

568.9

840.1

3767.43

OFICINA 120

1860

64.66

940.51

1602.75

6980.1

OFICINA 121

570

25.82

360.9

711.3

2641.54

OFICINA 122

750

25.88

383

832.13

3418.74

OFICINA 123

721

25.57

379

884.4

3578.14

OFICINA 124

624

25

382.62

768.87

3103.72

57

Anexos

1.2.5.2

Febrero
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

7072.39

409.67

Oficina 008

717.4

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
21472.80

Media (W)

Mxima puntual (W)

4165.88

Media
(W)
5223.27

25.72

324.94

679.30

2960.80

589.95

25.82

314.36

568.41

2512.56

Oficina 011

998.51

38.72

469.40

881.03

4062.26

Sala de Juntas

4450.67

333.78

3341.96

5600.97

18101

Sala Honor

5251.21

385.90

4059.51

5758.65

19635.80

Oficina 014

1413.76

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 015

1413.76

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 016

1413.76

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 017

1413.76

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 018

1172.49

38.84

503.19

653.34

3489.36

Cafetera y restaurante

25054.58

2214.32

18877.49

34046.57

86507.40

Gestin Acadmica, Econmica y de Postgrado

8200.99

284.17

3462.16

4949.43

24628

Comedor reservado

3542.14

307.51

2749.63

4968.70

12653.60

Sala de Espera

1806.81

112.50

1287.22

1787.39

6571.80

Servicio Reprografa

1871.01

64.67

819.28

1097.60

5673.03

Sala Audiovisual

58

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1008
606
1237
1237
1237
1237
1237
2349
2349
2349
1396
1396
1396
1396
1386
1384
1122
1944
590
736
794
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.61
483.64
25.74
329.61
18
234.52
18
234.52
18
234.52
18
234.52
18
234.52
38.76
540.74
38.76
540.74
38.76
540.74
19.4
272.5
19.4
272.5
19.4
272.5
19.4
272.5
51.56
557.4
38.72
517.3
38.7
505.3
64.43
832.9
25.72
319.1
25.76
337
25.75
335
25.74
342.1

Media (W)
802.05
566.16
578.72
578.72
578.72
578.72
578.72
489.23
489.23
489.23
430.1
430.1
430.1
430.1
907.73
515.5
541.62
1088.81
520.83
597.34
631.81
512.35

Calefaccin
Mxima puntual (W)
4437.1
2720.17
3865.2
3865.2
3865.2
3865.2
3865.2
4027.33
4027.33
4027.33
3877.41
3877.41
3877.41
3877.41
4955.53
3463.9
3409.62
6390.21
2532.73
3186.22
3352.54
2819.23

Media (W)
0
0
1.67
1.67
1.67
1.67
1.67
15.66
15.66
15.66
35.6
35.6
35.6
35.6
0.01
7.93
0.96
0.17
0
0
0.07
0

Refrigeracin
Mxima puntual (W)
0.2
48.1
48.1
48.1
48.1
48.1
337.6
337.6
337.6
504.1
504.1
504.1
504.1
4.61
225.93
76
34.3
0.84
1.05
-

59

Anexos

1.2.5.3

Marzo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7071.41

409.67

3463.30

Media
(W)
3262.13

Mxima
puntual (W)
16260.50

Media (W)

Mxima puntual (W)

Oficina 008

729.83

25.72

270.60

407.70

2124.28

Oficina 009

600.28

25.82

261.48

353.04

1793.16

Oficina 011

1018.85

38.72

392.24

538.35

2900.34

Sala de Juntas

4602.63

333.78

2764.85

3606.63

13539.20

Sala Honor

5215.27

385.90

3319.46

3770.23

14670.70

Oficina 014

1401.2

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 015

1401.2

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 016

1401.2

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 017

1401.2

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 018

1165.65

38.84

427.57

381.85

381.85

52.97

435.64

Cafetera y restaurante

25139.67

2214.32

14988.60

23895.25

69298.80

Gestin Acadmica, Econmica y de Postgrado

8481.39

284.17

3008.16

2765.51

17144.10

345.98

3031.67

Comedor reservado

3611.65

307.51

2206.38

3425.60

9976.62

Sala de Espera

1806.25

112.50

1060.01

1137.72

4798.40

Servicio Reprografa

2008.67

64.67

716.0

508.57

3493.57

80.99

573.84

60

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1033.96
656
1251
1251
1251
1251
1251
2260
2260
2260
1353
1353
1353
1353
1371
1338
1100
1955
608
764
829
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.37
391.6
25.6
268.9
17.88
189.66
17.88
189.66
17.88
189.66
17.88
189.66
17.88
189.66
38.5
449.14
38.5
449.14
38.5
449.14
19.25
226.1
19.25
226.1
19.25
226.1
19.25
226.1
51.25
545.7
38.47
433.08
38.46
420
64
698.64
25.58
259
25.61
274.6
25.61
274.3
25
280.77

Media (W)
491.31
321.35
386.76
386.76
386.76
386.76
386.76
277.78
277.78
277.78
250.9
250.9
250.9
250.9
538.07
281.04
299.93
591.08
313.16
349.47
357.84
249.75

Calefaccin
Mxima puntual (W)
3181.55
1874.66
2864.2
2864.2
2864.2
2864.2
2864.2
2805.56
2805.56
2805.56
3017.96
3017.96
3017.96
3017.96
3595.68
2355.9
2337.12
4439.06
1765.72
2245.71
2321.62
1718.77

Media (W)
2.49
0.46
2.93
2.93
2.93
2.93
2.93
46.2
46.2
46.2
131
131
131
131
3.45
135.58
14.38
15.92
0.78
1.68
2.45
3.11

Refrigeracin
Mxima puntual (W)
103.85
38.88
197.88
197.88
197.88
197.88
197.88
524.13
524.13
524.13
1112.67
1112.67
1112.67
1112.67
128.65
439.72
250.87
380.71
38.94
67.18
91.12
110.56

61

Anexos

1.2.5.4

Abril
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6894.61

409.67

2478.51

Media
(W)
2016.68

Mxima
puntual (W)
13015.90

Media (W)

Mxima puntual (W)

545.43

3843.13

Oficina 008

747.99

25.72

201.82

218.57

1712.65

61.12

376.90

Oficina 009

614.23

25.82

192.67

197.22

1459.10

44.31

300.48

Oficina 011

1046.52

38.72

289.92

301.32

2366.10

87.66

535.58

Sala de Juntas

4754.21

333.78

2008.72

2057.51

10578.90

240.73

2380.58

Sala Honor

5129

385.90

2350.93

2310.84

11769.10

200.08

2113.07

Oficina 014

1314.58

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 015

1314.58

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 016

1314.58

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 017

1314.58

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 018

1127.93

38.84

312.56

230.31

2149.80

147.33

740.10

Cafetera y restaurante

25271.41

2214.32

9924.85

14919.75

54514.80

356.98

8512.58

Gestin Acadmica, Econmica y de Postgrado

8691.4

284.17

2287.93

1421.03

14106.50

1310.75

5930.37

Comedor reservado

3651.66

307.51

1498.79

2100.28

7838.73

52.76

1195

Sala de Espera

1797.91

112.50

767.17

679.51

3952.50

100.26

838.50

Servicio Reprografa

2076.7

64.67

553.20

263.71

3002.37

358.24

1218.37

62

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1069.96
728
1270
1270
1270
1270
1270
2096
2096
2096
1267
1267
1267
1267
1342.56
1210
1038
1931
632
788
881
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.1
295.43
25.43
201.15
17.76
141.7
17.76
141.7
17.76
141.7
17.76
141.7
17.76
141.7
38.17
328.4
38.17
328.4
38.17
328.4
19.1
162.7
19.1
162.7
19.1
162.7
19.1
162.7
50.84
408.7
38.17
319.3
38.16
314.09
63.61
526
25.41
194.84
25
209.16
25.43
210.86
25.47
221.2

Media (W)
249.29
133.72
208.52
208.52
208.52
208.52
208.52
182.66
182.66
182.66
140
140
140
140
306.47
167.62
175.77
306.38
156.59
174.71
164.4
111.41

Calefaccin
Mxima puntual (W)
2687.27
1524.37
2459.2
2459.2
2459.2
2459.2
2459.2
2586
2586
2586
2555.8
2555.8
2555.8
2555.8
3326.44
2190.82
2168.35
3862.46
1485.03
1906.9
1900.34
1528.8

Media (W)
49.81
38.31
16.86
16.86
16.86
16.86
16.86
97.93
97.93
97.93
201
201
201
201
60.64
95.5
70.83
125.34
29.5
42.72
53.29
61.48

Refrigeracin
Mxima puntual (W)
606.12
365.55
257.43
257.43
257.43
257.43
257.43
768.88
768.88
768.88
1277
1277
1277
1277
683.08
754.07
616.53
1162.6
362.65
469
534.14
444.54

63

Anexos

1.2.5.5

Mayo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6732.63

409.67

1852.07

Media
(W)
679.03

Mxima
puntual (W)
9317.70

Media (W)

Mxima puntual (W)

1822.20

7020.40

Oficina 008

769.64

25.72

157.25

48.29

800.70

262.41

763

Oficina 009

631.67

25.82

147.98

47.16

754.37

194.51

635.99

Oficina 011

1077.51

38.72

223.19

75.59

1246.34

346.15

1073.13

Sala de Juntas

4884.64

333.78

1570.05

592.89

7451.24

1224.38

5777.77

Sala Honor

5080.96

385.90

1738.13

737.17

8453.75

1120.43

5285.60

Oficina 014

1241.57

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 015

1241.57

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 016

1241.57

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 017

1241.57

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 018

1088.43

38.84

234.23

66.47

1169.46

377.17

1096.25

Cafetera y restaurante

25427.97

2214.32

8420.41

5584.15

40250.60

3375.58

24552

Gestin Acadmica, Econmica y de Postgrado

8860.33

284.17

1810.69

375.42

7786.41

3488.85

10012.80

Comedor reservado

3679.32

307.51

1083.18

762.99

5749.89

515.88

3477.83

Sala de Espera

1789.63

112.50

572.37

199.70

2627.14

457.53

1839.41

Servicio Reprografa

2119.83

64.67

427.46

62.40

1429.62

905.04

2194.67

64

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1117
771
1295
1295
1295
1295
1295
2002
2002
2002
1219
1219
1219
1219
1323
1104
991
1930
671
813
950
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.85
261.45
25.27
186.29
17.65
124
17.65
124
17.65
124
17.65
124
17.65
124
37.87
274.15
37.87
274.15
37.87
274.15
18.94
136
18.94
136
18.94
136
18.94
136
50.47
352.54
37.5
269.1
37.88
268
63.17
462.7
25.25
174
25.26
186.47
25.27
189
25.3
196.07

Media (W)
59.05
26.46
58.52
58.52
58.52
58.52
58.52
59.5
59.5
59.5
45
45
45
45
79.56
50
48.87
72.46
35.05
36.55
33.13
22.77

Calefaccin
Mxima puntual (W)
1430.24
669.8
1381.6
1381.6
1381.6
1381.6
1381.6
1801.3
1801.3
1801.3
1405.3
1405.3
1405.3
1405.3
1994.86
1440.91
1389.63
2150.74
808.76
1049.81
961.61
673.35

Media (W)
261.8
205.29
105.16
105.16
105.16
105.16
105.16
300
300
300
311
311
311
311
306.4
290.04
257.24
510.68
164.13
222.94
265.21
263.1

Refrigeracin
Mxima puntual (W)
1176.74
758.31
559.48
559.48
559.48
559.48
559.48
1260
1260
1260
1577
1577
1577
1577
1319.5
1208.39
1079.15
2101
758.48
909.38
1043.85
911.23

65

Anexos

1.2.5.6

Junio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

6642.44

402.75

Oficina 008

787.4

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
8536.42

Media (W)

Mxima puntual (W)

1586.73

Media
(W)
772.36

2062.92

7155.72

25.72

136.87

54.96

740.06

286.11

745.19

644.85

25.26

131.26

51.81

705.95

215.98

627.01

Oficina 011

1105.77

37.88

194.62

84.08

1189.99

380.05

1054.65

Sala de Juntas

4972.04

327.61

1414.69

602.04

6478.64

1474.81

6020.82

Sala Honor

5075.21

377.75

1555.06

827.01

7721.66

1272.64

5278.53

Oficina 014

1207.91

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 015

1207.91

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 016

1207.91

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 017

1207.91

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 018

1075.9

37.89

198.87

87.27

1203.41

381.96

1059.04

Cafetera y restaurante

25548.72

2173.21

7117.98

5846.48

34849.10

4181.38

24945.90

Gestin Acadmica, Econmica y de Postgrado

9033.02

278.23

1485.84

386.94

6402.94

3928.79

10138.60

Comedor reservado

3708.08

301.81

961.15

799.67

4941.28

639.11

3516.45

Sala de Espera

1785.47

113.44

507.81

232.54

2416.79

517.60

1871.48

Servicio Reprografa

2164.1

63.26

464.10

69.72

923.21

999.40

2111.55

Sala Audiovisual

66

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1147.96
794
1313
1313
1313
1313
1313
1997
1997
1997
1215
1215
1215
1215
1322.17
1067
974
1950
701
839
1000
623

Ventilacin
Caudal (l/s)
Carga total (W)
37.91
225.07
25.31
161.58
17.67
102.4
17.67
102.4
17.67
102.4
17.67
102.4
17.67
102.4
37.92
227.3
37.92
227.3
37.92
227.3
19
114
19
114
19
114
19
114
50.54
299.66
37.92
227.1
37.92
228.75
63.27
396.77
25.3
153.6
25.31
160.22
25.32
165.1
25.34
170

Media (W)
59.01
25.35
60.32
60.32
60.32
60.32
60.32
70.5
70.5
70.5
47.3
47.3
47.3
47.3
96.31
59.12
57.85
74.24
32.79
36.48
30.18
19.74

Calefaccin
Mxima puntual (W)
1035.5
370.15
1122.19
1122.19
1122.19
1122.19
1122.19
1392.66
1392.66
1392.66
1444.29
1444.29
1444.29
1444.29
1491.62
1002.62
953.86
1446.83
559.35
656.88
580.32
308.76

Refrigeracin
Media (W)
Mxima puntual (W)
292.88
1085.33
229.72
736.8
120.32
506.32
120.32
506.32
120.32
506.32
120.32
506.32
120.32
506.32
320
1165.55
320
1165.55
320
1165.55
392
1611.2
392
1611.2
392
1611.2
392
1611.2
331.26
1310.79
290.45
1091.8
268.41
1006.19
554.18
1962.08
181.63
686.41
243.64
829.36
294.63
966.03
291.64
872.78

67

Anexos

1.2.5.7

Julio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

6690.24

400.48

Oficina 008

781.2

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
6190.98

Media (W)

Mxima puntual (W)

1570.07

Media
(W)
306.84

4465.24

11339.50

25.08

128.69

17.68

514.05

542.45

1164.09

639.1

25.26

122.46

17.98

477.41

433.31

986.64

Oficina 011

1093.15

37.61

183.60

29.62

783.24

729.41

1632.87

Sala de Juntas

4985.52

325.78

1390.41

227.25

4623.89

3441.73

9874.36

Sala Honor

5075.12

375.49

1542.73

311.17

5593.12

3273.10

9123.14

Oficina 014

1228.34

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 015

1228.34

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 016

1228.34

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 017

1228.34

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 018

1088.1

37.89

188.17

29.82

809.13

746.99

1649.97

Cafetera y restaurante

25509.75

2162.11

6715.04

2380.76

26702.10

12353.97

45762.20

Gestin Acadmica, Econmica y de Postgrado

9051.21

276.33

1459.91

147.66

4564.34

6676.41

14663.10

Comedor reservado

3713.89

300.22

1026.86

321.67

3772.65

1878.69

6553.39

Sala de Espera

1788.42

112.71

498.81

88.17

1797.46

1192.78

3077.29

Servicio Reprografa

2181.82

62.81

335.36

16.56

677.06

1694.79

3353.43

Sala Audiovisual

68

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1134.96
801
1306
1306
1306
1306
1306
1998
1998
1998
1217
1217
1217
1217
1325
1082
981
1949
689
839
987
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.67
195.13
25.15
140.8
17.56
90.44
17.56
90.44
17.56
90.44
17.56
90.44
17.56
90.44
37.67
199.88
37.67
199.88
37.67
199.88
18.84
100.11
18.84
100.11
18.84
100.11
18.84
100.11
50.2
262.15
37.68
197.85
37.68
198.04
62.86
348.52
25.13
132.4
25.13
139.18
25.15
142.75
25.17
148.3

Media (W)
20.78
9.99
19.87
19.87
19.87
19.87
19.87
21.84
21.84
21.84
25
25
25
25
30.01
21.14
20.53
23.2
13.42
14.1
11.93
8.66

Calefaccin
Mxima puntual (W)
701.61
275.84
815.2
815.2
815.2
815.2
815.2
922.3
922.3
922.3
1104.32
1104.32
1104.32
1104.32
1023.03
734.64
699.57
964.64
402
467.64
386.5
208.31

Media (W)
544.16
433.34
246.68
246.68
246.68
246.68
246.68
585.92
585.92
585.92
510
510
510
510
637.5
558.37
512.26
1012.37
355.53
442.22
518.16
518.89

Refrigeracin
Mxima puntual (W)
1818.55
1325.66
913
913
913
913
913
1166.2
1166.2
1166.2
1872.64
1872.64
1872.64
1872.64
2166.33
1851.02
1687.55
3251.4
1710.16
1381.82
1578.01
1523.25

69

Anexos

1.2.5.8

Septiembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7068.76

406.32

1777.48

Media
(W)
911.43

Mxima
puntual (W)
11825.90

Media (W)

Mxima puntual (W)

2501.66

9021.35

Oficina 008

735.24

25.26

136.81

104.28

1250.16

250.17

778.37

Oficina 009

604.03

25.26

133.38

93.65

1109.46

193.05

653.19

Oficina 011

1026.01

37.87

198.15

143.49

1804.14

350.69

1106.43

Sala de Juntas

4685.78

327.60

1472.97

956.57

9604.84

1239.89

6237.11

Sala Honor

5191.4

378.18

1763.43

1007.85

10615.30

1395.94

6442.23

Oficina 014

1395.71

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 015

1395.71

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 016

1395.71

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 017

1395.71

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 018

1175.14

37.89

214.98

95.67

1546.57

506.94

1453.44

Cafetera y restaurante

25140.59

2174.63

7060.09

7819.27

51151.4

3961.50

29213.10

Gestin Acadmica, Econmica y de Postgrado

8647.87

278.18

1524.75

679.89

11196.20

3714.75

10780.60

Comedor reservado

3643.43

301.96

1073.15

1095.42

7274.77

599.95

4154.99

Sala de Espera

1806.77

112.71

587.15

295.44

3450.58

556.55

2222.21

Servicio Reprografa

2067.46

62.81

363.87

116.10

1833.69

983.70

2318.61

70

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1043.96
697
1256
1256
1256
1256
1256
2211
2211
2211
1329
1329
1329
1329
1363.56
1310
1085
1954
614
760
842
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.9
203.65
25.3
145.1
17.67
93.4
17.67
93.4
17.67
93.4
17.67
93.4
17.67
93.4
38.03
234.52
38.03
234.52
38.03
234.52
19
119.7
19
119.7
19
119.7
19
119.7
50.61
292
38.02
229.66
38
245.55
63.3
369.8
25.28
138.1
25.3
145.14
25.3
145.07
25.34
154.87

Media (W)
107.11
52.65
94.34
94.34
94.34
94.34
94.34
57.52
57.52
57.52
68.1
68.1
68.1
68.1
106.35
58.46
60.21
110.45
65.0
69.72
67.78
38.66

Calefaccin
Mxima puntual (W)
1846.32
876.08
1802.76
1802.76
1802.76
1802.76
1802.76
1787.11
1787.11
1787.11
888.62
888.62
888.62
888.62
1993.14
1478.87
1404.83
2524.1
1078.04
1258.96
1276.74
768.18

Refrigeracin
Media (W)
Mxima puntual (W)
248.02
1158.28
184.21
795
107.48
549.1
107.48
549.1
107.48
549.1
107.48
549.1
107.48
549.1
472.76
1750.98
472.76
1750.98
472.76
1750.98
500
1811.42
500
1811.42
500
1811.42
500
1811.42
369.1
1578.72
427.64
1691.82
339.89
1383.22
569.92
2360.4
149.3
724.69
205.74
883.36
227.36
965
262.87
768.18

71

Anexos

1.2.5.9

Octubre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

7099.06

403.32

Oficina 008

722

Oficina 009

Calefaccin

Refrigeracin

Mxima
puntual (W)
11609.80

Media (W)

Mxima puntual (W)

1972.97

Media
(W)
956.20

2138.87

7527.75

25.26

151.69

100.99

1328.11

214.04

624.47

594.03

25.26

146.10

93.60

1184.95

159.57

510.26

Oficina 011

1006.12

37.87

219.07

141.39

1908.37

294.19

885.02

Sala de Juntas

4511.98

327.60

1535.21

1114.71

9930.03

865.98

4429.53

Sala Honor

5250.26

378.18

1903.77

1068.29

10390.80

1180.34

5084.59

Oficina 014

1422.44

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 015

1422.44

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 016

1422.44

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 017

1422.44

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 018

1171.11

37.89

244.57

89.12

1557.13

478.37

1361.21

Cafetera y restaurante

25049.43

2174.63

7647.96

8652.82

50658.50

2946.33

22089.90

Gestin Acadmica, Econmica y de Postgrado

8304.31

278.18

1687.37

723.65

11620.70

3087.57

8916.85

Comedor reservado

3574.01

301.96

1143.96

1228.61

7224.79

435.80

3140.19

Sala de Espera

1807.77

112.71

609.19

304.33

3339.96

461.07

1751.67

Servicio Reprografa

1941.3

62.81

440.90

134.33

2262.74

800.73

1902.46

Sala Audiovisual

72

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1016.96
616
1242
1242
1242
1242
1242
2345
2345
2345
1395
1395
1395
1395
1388
1386
1125
1957
593
742
804
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.94
226.78
25.32
158
17.7
105.9
17.7
105.9
17.7
105.9
17.7
105.9
17.7
105.9
38.1
279.84
38.1
279.84
38.1
279.84
19.05
141.57
19.05
141.57
19.05
141.57
19.05
141.57
50.67
327.4
38.06
267.53
38.04
258.61
63.35
413.07
25.3
152.11
25.32
161
25.32
160.47
25.35
170.8

Media (W)
125.87
77.91
109.57
109.57
109.57
109.57
109.57
53.78
53.78
53.78
151.62
151.62
151.62
151.62
117.31
61.13
63.4
130.57
75.78
80.09
83.1
55.88

Calefaccin
Mxima puntual (W)
2066.89
1177.63
1962.08
1962.08
1962.08
1962.08
1962.08
1670.85
1670.85
1670.85
1201.3
1201.3
1201.3
1201.3
2174.74
1542.73
1466.38
2819.6
1141.47
1347.22
1424.41
1021.91

Refrigeracin
Media (W)
Mxima puntual (W)
187.71
874.33
120
547.95
77.4
404.78
77.4
404.78
77.4
404.78
77.4
404.78
77.4
404.78
475.76
1803.34
475.76
1803.34
475.76
1803.34
400
1711.2
400
1711.2
400
1711.2
400
1711.2
301.7
1266.12
401.68
1668.15
295.65
1224.07
448.2
1925.45
110.67
529.87
157.98
667.99
166.78
708.44
182.25
1021.91

73

Anexos

1.2.5.10 Noviembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6926.81

408.79

3725.56

Media
(W)
4459.09

Mxima
puntual (W)
19460.10

Media (W)

Mxima puntual (W)

120.35

2473.32

Oficina 008

710.54

25.68

286.70

553.61

2750.56

6.44

166.59

Oficina 009

584.29

25.66

278.33

472.20

2317.8

4.41

140.04

Oficina 011

987.08

38.40

416.37

727.80

3754.94

11.53

276.53

Sala de Juntas

4381.78

331.90

2962.19

4,865.02

16424.9

9.89

613.09

Sala Honor

5213.44

383.58

3910.78

4,907.31

17899.7

23.47

1116.16

Oficina 014

1360.49

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 015

1360.49

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 016

1360.49

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 017

1360.49

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 018

1148.15

37.89

449.63

516.95

3297.25

65.45

650.33

Cafetera y restaurante

24663.29

2174.63

16693.15

30,101.41

77504.6

23.24

3014.5

Gestin Acadmica, Econmica y de Postgrado

8003.95

278.18

3072.89

4,097.54

23268.6

255.90

3615.05

Comedor reservado

3498.89

301.96

2420.41

4,411.36

11372.5

2.55

363.71

Sala de Espera

1801.08

112.71

1147.14

1,499.39

6038.9

12.77

456.14

Servicio Reprografa

1784.76

62.81

728.67

956.93

5360.27

54.12

5360.27

74

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


991.96
596
1229
1229
1229
1229
1229
2301
2301
2301
1369
1369
1369
1369
1376
1330
1094
1893
575
725
774
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.48
419.52
25.67
333.1
17.94
199.98
17.94
199.98
17.94
199.98
17.94
199.98
17.94
199.98
38.62
471.31
38.62
471.31
38.62
471.31
19.31
236.51
19.31
236.51
19.31
236.51
19.31
236.51
51.4
587.97
38.58
445.68
38.56
444.1
64.23
727.78
25.65
277
25.68
298.7
25.67
288
25.7
296.3

Media (W)
676.3
477.68
491.68
491.68
491.68
491.68
491.68
395.66
395.66
395.66
604
604
604
604
739.16
430.88
451.22
908.54
444.48
499.04
533.72
411.93

Calefaccin
Mxima puntual (W)
4177.86
2583.86
3643.4
3643.4
3643.4
3643.4
3643.4
4015.33
4015.33
4015.33
1841.09
1841.09
1841.09
1841.09
4810
3367.4
3306
6207.54
2390.89
3042.93
3192.84
2722.98

Refrigeracin
Media (W)
Mxima puntual (W)
9.02
169.18
6.97
50.46
5.72
233.6
5.72
233.6
5.72
233.6
5.72
233.6
5.72
233.6
84.66
901.66
84.66
901.66
84.66
901.66
113
999.63
113
999.63
113
999.63
113
999.63
19.25
362.58
57.5
710.37
31.01
449.5
32.39
637.11
7.23
70.44
8.53
112.15
8.34
116.37
10.11
130.85

75

Anexos

1.2.5.11 Diciembre
Recinto

Ventilacin

Carga interna (W)

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

Mxima puntual (W)

Sala Audiovisual

6785.06

408.79

4754.91

7,484.26

21215.7

Oficina 008

705.29

25.68

370.49

916.63

3107.26

Oficina 009

579.75

25.66

359.55

761.94

2596.02

Oficina 011

977.84

38.40

536.44

1199.01

4200.22

Sala de Juntas

4345.86

331.90

3816.93

7,374.81

17865.8

Sala Honor

5185.14

383.58

4643.79

7,713.87

19638.6

Oficina 014

1324.76

38.54

582.06

737.71

3200.65

Oficina 015

1324.76

38.54

582.06

737.71

3200.65

Oficina 016

1324.76

38.54

582.06

737.71

3200.65

Oficina 017

1324.76

38.54

582.06

737.71

3200.65

Oficina 018

1135.2

37.89

566.45

950.26

3826.97

Cafetera y restaurante

24624.09

2174.63

22013.66

43,468.61

82897

Gestin Acadmica, Econmica y de Postgrado

7891.18

278.18

3918.47

7,288.71

26052.7

Comedor reservado

3478.63

301.96

3183.18

6,387.32

12245.2

Sala de Espera

1799.08

112.71

1475.22

2,410.77

6628.92

Servicio Reprografa

1738.03

62.81

927.84

1,769.52

6093.33

76

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


980
591
1222.47
1222.47
1222.47
1222.47
1222.47
2248
2248
2248
1340
1340
1340
1340
1366
1285
1065
1850
565
717
759
624

Caudal (l/s)
38.73
25.83
18.05
18.05
18.05
18.05
18.05
38.9
38.9
38.9
19.45
19.45
19.45
19.45
51.75
38.84
38.82
64.65
25.81
25.86
25.83
25.87

Ventilacin
Carga total (W)
523.67
358
251.17
251.17
251.17
251.17
251.17
579.63
579.63
579.63
292.3
292.3
292.3
292.3
739.2
557.4
552.4
907.1
348.6
366.7
364.07
372

Media (W)
1034.86
731.51
707.8
707.8
707.8
707.8
707.8
750
750
750
702.6
702.6
702.6
702.6
1204.48
786.77
794.58
1529.84
682.03
785.23
843.27
732

Calefaccin
Mxima puntual (W)
4678.21
2918.95
4029.6
4029.6
4029.6
4029.6
4029.6
4909
4909
4909
4110.69
4110.69
4110.69
4110.69
5442.94
3967.84
3858.39
7077.4
2686.73
3450.89
3629.99
3146.38

77

Anexos

1.2.6

Resultados de simulacin del edificio con las mejoras de acristalamiento doble y voladizo

1.2.6.1

Enero
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6818.88

409.67

4722.05

Media
(W)
7470.45

Mxima
puntual (W)
21302.60

Media (W)

Mxima puntual (W)

Oficina 008

707.68

25.72

370.12

959.60

3069.04

Oficina 009

581.71

25.82

358.58

788.86

2558.31

Oficina 011

982.11

38.72

535.28

1242.17

4163.30

Sala de Juntas

4362.02

333.78

3807.41

7402.70

17815.70

Sala Honor

5185.66

385.90

4615.19

7757.56

19727.0

Oficina 014

1323.12

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 015

1323.12

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 016

1323.12

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 017

1323.12

38.90

578.06

766.46

3134.62

15.25

359.75

Oficina 018

1130.08

38.84

561.50

998.18

3822.09

Cafetera y restaurante

24979.78

2214.32

21961.65

43239.29

82819.10

Gestin Acadmica, Econmica y de Postgrado

7933.6

284.17

3907.38

7550.58

25966.40

Comedor reservado

3487.05

307.51

3176.49

6370.23

12202.30

Sala de Espera

1797.09

112.50

436.85

2458.59

6644.31

Servicio Reprografa

1752.66

64.67

926.09

1852.67

6015.43

78

Anexos

Recinto

Carga interna (W)

Ventilacin

Calefaccin

973.96

Caudal (l/s)
38.78

Carga total (W)


559.35

Media (W)
1077.77

Mxima puntual (W)


4450.8

OFICINA 101

589

25.86

376.91

740.42

2814.61

OFICINA 102

1219

18.07

267

700.22

3854.4

OFICINA 105

1219

18.07

267

700.22

3854.4

OFICINA 106

1219

18.07

267

700.22

3854.4

OFICINA 107

1219

18.07

267

700.22

3854.4

OFICINA 108

1219

18.07

267

700.22

3854.4

OFICINA 109

2167

38.91

599.86

746

4524.3

OFICINA 110

2167

38.91

599.86

746

4524.3

OFICINA 113

2167

38.91

599.86

746

4524.3

OFICINA 111

1297

19.46

302.4

801

4490.6

OFICINA 112

1297

19.46

302.4

801

4490.6

OFICINA 115

1297

19.46

302.4

801

4490.6

OFICINA 116

1297

19.46

302.4

801

4490.6

OFICINA 117

1351

51.77

764.55

1265.05

5496.06

OFICINA 118

1217

38.87

578.6

790.1

3704.89

OFICINA 119

1035

38.84

574.55

816.46

3707.92

OFICINA 120

1812

64.7

949.3

1530.33

6806.1

OFICINA 121

560

25.84

365.1

664.93

2516.93

OFICINA 122

712

25.88

381.04

786.48

3332.12

OFICINA 123

751

25.87

390.5

822.8

3440.86

OFICINA 124

624

25.89

388.09

736.07

3104.8

OFICINA 103-104

79

Anexos

1.2.6.2

Febrero
Recinto

Ventilacin

Carga interna (W)

Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7072.43

409.67

4165.88

Media
(W)
5223.27

Mxima
puntual (W)
21472.80

Media (W)

Mxima puntual (W)

Oficina 008

717.44

25.72

324.94

679.30

2960.80

Oficina 009

589.99

25.82

314.36

568.41

2512.56

Oficina 011

998.55

38.72

469.40

881.03

4062.26

Sala de Juntas

4450.71

333.78

3341.96

5600.97

18101

Sala Honor

5251.25

385.90

4059.51

5758.65

19635.80

Oficina 014

1413.8

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 015

1413.8

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 016

1413.8

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 017

1413.8

38.90

539.62

441.43

2500.92

81.50

661.16

Oficina 018

1172.53

38.84

503.19

653.34

3489.36

Cafetera y restaurante

25054.62

2214.32

18877.49

34046.57

86507.40

Gestin Acadmica, Econmica y de Postgrado

8201.03

284.17

3462.16

4949.43

24628

Comedor reservado

3542.18

307.51

2749.63

4968.70

12653.60

Sala de Espera

1806.85

112.50

1287.22

1787.39

6571.80

Servicio Reprografa

1871.05

64.67

819.28

1097.60

5673.03

80

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


990.96
599
1228
1228
1228
1228
1228
2247
2247
2247
1341
1341
1341
1341
1369.56
1300
1080
1877
574
735
774
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.62
491.95
25.76
333.1
18
236.6
18
236.6
18
236.6
18
236.6
18
236.6
38.77
542.11
38.77
542.11
38.77
542.11
19.4
273.6
19.4
273.6
19.4
273.6
19.4
273.6
51.56
674.5
38.73
520
38.7
507.3
64.46
840.9
25.74
321.07
25.78
341.7
25.77
340.65
25.8
343.07

Media (W)
726.48
530.1
538.88
538.88
538.88
538.88
538.88
450
450
450
451.25
451.25
451.25
451.25
883.11
478
521.26
1015
477.18
550.87
572.52
482.16

Calefaccin
Mxima puntual (W)
4205.68
2612.55
3729.06
3729.06
3729.06
3729.06
3729.06
3874.6
3874.6
3874.6
4001.6
4001.6
4001.6
4001.6
4919.54
3309.12
3326.44
6162.83
2939.73
3036.06
3158.6
2712.72

Media (W)
0
0
1.67
1.67
1.67
1.67
1.67
15.66
15.66
15.66
35.6
35.6
35.6
35.6
0.01
7.93
0.96
0.17
0
0
0.07
0

Refrigeracin
Mxima puntual (W)
0.2
48.1
48.1
48.1
48.1
48.1
337.6
337.6
337.6
504.1
504.1
504.1
504.1
4.61
225.93
76
34.3
0.84
1.05
-

81

Anexos

1.2.6.3

Marzo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7071.45

409.67

3463.30

Media
(W)
3262.13

Mxima
puntual (W)
16260.50

Media (W)

Mxima puntual (W)

Oficina 008

729.87

25.72

270.60

407.70

2124.28

Oficina 009

600.32

25.82

261.48

353.04

1793.16

Oficina 011

1018.89

38.72

392.24

538.35

2900.34

Sala de Juntas

4602.67

333.78

2764.85

3606.63

13539.20

Sala Honor

5215.31

385.90

3319.46

3770.23

14670.70

Oficina 014

1401.24

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 015

1401.24

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 016

1401.24

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 017

1401.24

38.90

462.41

221.43

1764.13

179.24

883.90

Oficina 018

1165.69

38.84

427.57

381.85

381.85

52.97

435.64

Cafetera y restaurante

25139.71

2214.32

14988.60

23895.25

69298.80

Gestin Acadmica, Econmica y de Postgrado

8481.43

284.17

3008.16

2765.51

17144.10

345.98

3031.67

Comedor reservado

3611.69

307.51

2206.38

3425.60

9976.62

Sala de Espera

1806.29

112.50

1060.01

1137.72

4798.40

Servicio Reprografa

2008.71

64.67

716.0

508.57

3493.57

80.99

573.84

82

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1011.86
640
1239
1239
1239
1239
1239
2165
2165
2165
1301
1301
1301
1301
1354.56
1254
1056
1881
589
739
802
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.4
397.6
25.61
270.9
17.9
191.3
17.9
191.3
17.9
191.3
17.9
191.3
17.9
191.3
38.5
449
38.5
449
38.5
449
19.26
225.36
19.26
225.36
19.26
225.36
19.26
225.36
51.25
545.08
38.48
434
38.46
418.4
64.08
695.3
25.6
262.68
25.62
277
25.62
278
25.65
283.28

Media (W)
446.64
302.87
364.44
364.44
364.44
364.44
364.44
265.33
265.33
265.33
241.9
241.9
241.9
241.9
533.5
270
297.15
536.82
298.27
324.56
325.03
239.35

Calefaccin
Mxima puntual (W)
3026
1805.67
2775
2775
2775
2775
2775
2757.85
2757.85
2757.85
2888.6
2888.6
2888.6
2888.6
3587.64
2355.9
2301.56
4312.86
1671.87
2143.33
2193.42
1673.26

Media (W)
2.49
0.46
2.93
2.93
2.93
2.93
2.93
46.2
46.2
46.2
131
131
131
131
3.45
135.58
14.38
15.92
0.78
1.68
2.45
3.11

Refrigeracin
Mxima puntual (W)
103.85
38.88
197.88
197.88
197.88
197.88
197.88
524.13
524.13
524.13
1112.67
1112.67
1112.67
1112.67
128.65
439.72
250.87
380.71
38.94
67.18
91.12
110.56

83

Anexos

1.2.6.4

Abril
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6894.65

409.67

2478.51

Media
(W)
2016.68

Mxima
puntual (W)
13015.90

Media (W)

Mxima puntual (W)

545.43

3843.13

Oficina 008

748.03

25.72

201.82

218.57

1712.65

61.12

376.90

Oficina 009

614.27

25.82

192.67

197.22

1459.10

44.31

300.48

Oficina 011

1046.56

38.72

289.92

301.32

2366.10

87.66

535.58

Sala de Juntas

4754.25

333.78

2008.72

2057.51

10578.90

240.73

2380.58

Sala Honor

5129.04

385.90

2350.93

2310.84

11769.10

200.08

2113.07

Oficina 014

1314.62

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 015

1314.62

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 016

1314.62

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 017

1314.62

38.90

336.79

143.68

1539.75

282.80

1099.26

Oficina 018

1127.97

38.84

312.56

230.31

2149.80

147.33

740.10

Cafetera y restaurante

25271.45

2214.32

9924.85

14919.75

54514.80

356.98

8512.58

Gestin Acadmica, Econmica y de Postgrado

8691.44

284.17

2287.93

1421.03

14106.50

1310.75

5930.37

Comedor reservado

3651.7

307.51

1498.79

2100.28

7838.73

52.76

1195

Sala de Espera

1797.95

112.50

767.17

679.51

3952.50

100.26

838.50

Servicio Reprografa

2076.74

64.67

553.20

263.71

3002.37

358.24

1218.37

84

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1040.96
700
1255
1255
1255
1255
1255
2027
2027
2027
1229
1229
1229
1229
1330
1144
1004
1860
612
761
841
623

Ventilacin
Caudal (l/s)
Carga total (W)
38.11
300.34
25.44
207.3
17.77
142.6
17.77
142.6
17.77
142.6
17.77
142.6
17.77
142.6
38.17
346.11
38.17
346.11
38.17
346.11
19.1
163
19.1
163
19.1
163
19.1
163
50.83
408.77
38.18
320.63
38.16
314.5
63.61
528.38
25.42
194.05
25.44
210.47
25.44
214.07
25.47
220

Media (W)
232.52
132.98
201.2
201.2
201.2
201.2
201.2
178.86
178.86
178.86
121
121
121
121
308.75
164.12
177.47
300
147
166.75
154.13
112

Calefaccin
Mxima puntual (W)
2606.23
1506.23
2417
2417
2417
2417
2417
2628.3
2628.3
2628.3
2505.6
2505.6
2505.6
2505.6
3342.43
2147.37
2160.13
3809.2
1433.21
1851.28
1832.9
1517.16

Media (W)
49.81
38.31
16.86
16.86
16.86
16.86
16.86
97.93
97.93
97.93
201
201
201
201
60.64
95.5
70.83
125.34
29.5
42.72
53.29
61.48

Refrigeracin
Mxima puntual (W)
606.12
365.55
257.43
257.43
257.43
257.43
257.43
768.88
768.88
768.88
1277
1277
1277
1277
683.08
754.07
616.53
1162.6
362.65
469
534.14
444.54

85

Anexos

1.2.6.5

Mayo
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6732.67

409.67

1852.07

Media
(W)
679.03

Mxima
puntual (W)
9317.70

Media (W)

Mxima puntual (W)

1822.20

7020.40

Oficina 008

769.68

25.72

157.25

48.29

800.70

262.41

763

Oficina 009

631.71

25.82

147.98

47.16

754.37

194.51

635.99

Oficina 011

1077.55

38.72

223.19

75.59

1246.34

346.15

1073.13

Sala de Juntas

4884.68

333.78

1570.05

592.89

7451.24

1224.38

5777.77

Sala Honor

5081

385.90

1738.13

737.17

8453.75

1120.43

5285.60

Oficina 014

1241.61

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 015

1241.61

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 016

1241.61

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 017

1241.61

38.90

246.97

48.85

1002.25

506.21

1316.42

Oficina 018

1088.47

38.84

234.23

66.47

1169.46

377.17

1096.25

Cafetera y restaurante

25428.01

2214.32

8420.41

5584.15

40250.60

3375.58

24552

Gestin Acadmica, Econmica y de Postgrado

8860.37

284.17

1810.69

375.42

7786.41

3488.85

10012.80

Comedor reservado

3679.36

307.51

1083.18

762.99

5749.89

515.88

3477.83

Sala de Espera

1789.67

112.50

572.37

199.70

2627.14

457.53

1839.41

Servicio Reprografa

2119.87

64.67

427.46

62.40

1429.62

905.04

2194.67

86

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1075.96
733
1275
1275
1275
1275
1275
1958
1958
1958
1192
1192
1192
1192
1315.56
1060
966
1858
640
785
897
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.86
262.53
25.27
185.3
17.65
125.52
17.65
125.52
17.65
125.52
17.65
125.52
17.65
125.52
37.88
275.3
37.88
275.3
37.88
275.3
18.94
137.66
18.94
137.66
18.94
137.66
18.94
137.66
50.47
351.24
37.88
271.33
37.88
263.77
63.17
463
25.25
175.4
25.26
186.3
25.28
190.3
25.3
194.55

Media (W)
56.05
27
57.2
57.2
57.2
57.2
57.2
56.77
56.77
56.77
40.8
40.8
40.8
40.8
80.67
47.82
48.67
71.16
33.23
35.61
31.6
23.07

Calefaccin
Mxima puntual (W)
1438.72
700.8
1400
1400
1400
1400
1400
1787.66
1787.66
1787.66
1444.9
1444.9
1444.9
1444.9
2018.55
1424.62
1397.07
2163.71
813.4
1064.15
974.84
706.62

Media (W)
261.8
205.29
105.16
105.16
105.16
105.16
105.16
300
300
300
311
311
311
311
306.4
290.04
257.24
510.68
164.13
222.94
265.21
263.1

Refrigeracin
Mxima puntual (W)
1176.74
758.31
559.48
559.48
559.48
559.48
559.48
1260
1260
1260
1577
1577
1577
1577
1319.5
1208.39
1079.15
2101
758.48
909.38
1043.85
911.23

87

Anexos

1.2.6.6

Junio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6642.48

402.75

1586.73

Media
(W)
772.36

Mxima
puntual (W)
8536.42

Media (W)

Mxima puntual (W)

2062.92

7155.72

Oficina 008

787.44

25.72

136.87

54.96

740.06

286.11

745.19

Oficina 009

644.89

25.26

131.26

51.81

705.95

215.98

627.01

Oficina 011

1105.81

37.88

194.62

84.08

1189.99

380.05

1054.65

Sala de Juntas

4972.08

327.61

1414.69

602.04

6478.64

1474.81

6020.82

Sala Honor

5075.25

377.75

1555.06

827.01

7721.66

1272.64

5278.53

Oficina 014

1207.95

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 015

1207.95

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 016

1207.95

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 017

1207.95

38.90

205.61

63.77

963.35

491.04

1249.88

Oficina 018

1075.94

37.89

198.87

87.27

1203.41

381.96

1059.04

Cafetera y restaurante

25548.76

2173.21

7117.98

5846.48

34849.10

4181.38

24945.90

Gestin Acadmica, Econmica y de Postgrado

9033.06

278.23

1485.84

386.94

6402.94

3928.79

10138.60

Comedor reservado

3708.12

301.81

961.15

799.67

4941.28

639.11

3516.45

Sala de Espera

1785.51

113.44

507.81

232.54

2416.79

517.60

1871.48

Servicio Reprografa

2164.14

63.26

464.10

69.72

923.21

999.40

2111.55

88

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1098.96
753
1287
1287
1287
1287
1287
1953.2
1953.2
1953.2
1075.96
1075.96
1075.96
1075.96
1315.66
1033
953
1872
660
803
933
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.92
226.53
25.31
161.17
17.68
101.4
17.68
101.4
17.68
101.4
17.68
101.4
17.68
101.4
37.92
230.6
37.92
230.6
37.92
230.6
18.96
116.55
18.96
116.55
18.96
116.55
18.96
116.55
50.54
298.1
37.93
229.3
37.92
228.34
63.27
399.66
25.3
153
25.31
160.09
25.32
166.22
25.33
169

Media (W)
58.45
27
61.1
61.1
61.1
61.1
61.1
67.8
67.8
67.8
42.01
42.01
42.01
42.01
97.89
56.89
57.82
74.9
32.61
37.04
30.24
20.96

Calefaccin
Mxima puntual (W)
1012.83
367.84
1125.3
1125.3
1125.3
1125.3
1125.3
1333.33
1333.33
1333.33
1388.91
1388.91
1388.91
1388.91
1504.27
935.45
935.36
1422
527.53
621.03
543.5
312.04

Refrigeracin
Media (W)
Mxima puntual (W)
292.88
1085.33
229.72
736.8
120.32
506.32
120.32
506.32
120.32
506.32
120.32
506.32
120.32
506.32
320
1165.55
320
1165.55
320
1165.55
392
1611.2
392
1611.2
392
1611.2
392
1611.2
331.26
1310.79
290.45
1091.8
268.41
1006.19
554.18
1962.08
181.63
686.41
243.64
829.36
294.63
966.03
291.64
872.78

89

Anexos

1.2.6.7

Julio
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6690.28

400.48

1570.07

Media
(W)
306.84

Mxima
puntual (W)
6190.98

Media (W)

Mxima puntual (W)

4465.24

11339.50

Oficina 008

781.24

25.08

128.69

17.68

514.05

542.45

1164.09

Oficina 009

639.14

25.26

122.46

17.98

477.41

433.31

986.64

Oficina 011

1093.19

37.61

183.60

29.62

783.24

729.41

1632.87

Sala de Juntas

4985.56

325.78

1390.41

227.25

4623.89

3441.73

9874.36

Sala Honor

5075.16

375.49

1542.73

311.17

5593.12

3273.10

9123.14

Oficina 014

1228.38

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 015

1228.38

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 016

1228.38

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 017

1228.38

37.67

192.85

20.82

587.70

904.48

1896.18

Oficina 018

1088.14

37.89

188.17

29.82

809.13

746.99

1649.97

Cafetera y restaurante

25509.79

2162.11

6715.04

2380.76

26702.10

12353.97

45762.20

Gestin Acadmica, Econmica y de Postgrado

9051.25

276.33

1459.91

147.66

4564.34

6676.41

14663.10

Comedor reservado

3713.93

300.22

1026.86

321.67

3772.65

1878.69

6553.39

Sala de Espera

1788.46

112.71

498.81

88.17

1797.46

1192.78

3077.29

Servicio Reprografa

2181.86

62.81

335.36

16.56

677.06

1694.79

3353.43

90

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1088.96
758
1281
1281
1281
1281
1281
1954
1954
1954
1191
1191
1191
1191
1315.56
1044
958
1871
652
797
922
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.66
195.08
25.14
138.91
17.56
91
17.56
91
17.56
91
17.56
91
17.56
91
37.67
199.18
37.67
199.18
37.67
199.18
18.84
101
18.84
101
18.84
101
18.84
101
50.19
262
37.67
197
37.67
198
62.85
345.29
25.12
131
25.13
139.06
25.15
141
25.16
145.9

Media (W)
21.04
10.6
20.44
20.44
20.44
20.44
20.44
21.14
21.14
21.14
21.3
21.3
21.3
21.3
31.2
20.9
20.92
23.95
13.68
14.63
12.23
9.12

Calefaccin
Mxima puntual (W)
711.37
296.65
831
831
831
831
831
913.66
913.66
913.66
1070.07
1070.07
1070.07
1070.07
1048.32
727.5
712.83
983.99
405.6
482.34
394.21
235

Refrigeracin
Media (W)
Mxima puntual (W)
544.16
1818.55
433.34
1325.66
246.68
913
246.68
913
246.68
913
246.68
913
246.68
913
585.92
1166.2
585.92
1166.2
585.92
1166.2
510
1872.64
510
1872.64
510
1872.64
510
1872.64
637.5
2166.33
558.37
1851.02
512.26
1687.55
1012.37
3251.4
355.53
1710.16
442.22
1381.82
518.16
1578.01
518.89
1523.25

91

Anexos

1.2.6.8

Septiembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7068.8

406.32

1777.48

Media
(W)
911.43

Mxima
puntual (W)
11825.90

Media (W)

Mxima puntual (W)

2501.66

9021.35

Oficina 008

735.28

25.26

136.81

104.28

1250.16

250.17

778.37

Oficina 009

604.07

25.26

133.38

93.65

1109.46

193.05

653.19

Oficina 011

1026.05

37.87

198.15

143.49

1804.14

350.69

1106.43

Sala de Juntas

4685.82

327.60

1472.97

956.57

9604.84

1239.89

6237.11

Sala Honor

5191.44

378.18

1763.43

1007.85

10615.30

1395.94

6442.23

Oficina 014

1395.75

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 015

1395.75

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 016

1395.75

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 017

1395.75

38.04

236.83

52.15

1085.56

782.80

1938.20

Oficina 018

1175.18

37.89

214.98

95.67

1546.57

506.94

1453.44

Cafetera y restaurante

25140.63

2174.63

7060.09

7819.27

51151.4

3961.50

29213.10

Gestin Acadmica, Econmica y de Postgrado

8647.91

278.18

1524.75

679.89

11196.20

3714.75

10780.60

Comedor reservado

3643.47

301.96

1073.15

1095.42

7274.77

599.95

4154.99

Sala de Espera

1806.81

112.71

587.15

295.44

3450.58

556.55

2222.21

Servicio Reprografa

2067.5

62.81

363.87

116.10

1833.69

983.70

2318.61

92

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


1019.96
673
1243
1243
1243
1243
1243
2122
2122
2122
1279
1279
1279
1279
1346
1227
1044
1881
594
754
814
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.91
207
25.3
146.22
17.68
93
17.68
93
17.68
93
17.68
93
17.68
93
38.03
234.82
38.03
234.82
38.03
234.82
19
119.1
19
119.1
19
119.1
19
119.1
50.6
289.66
38
229.41
38
224.6
63.31
370.91
25.28
140.24
25.3
145.78
25.31
146.56
25.34
155.43

Media (W)
99
52.1
90.3
90.3
90.3
90.3
90.3
57
57
57
65.32
65.32
65.32
65.32
109.16
57.21
61.34
107.9
60.22
66.03
62.7
38.83

Calefaccin
Mxima puntual (W)
1721.59
853.21
1722.62
1722.62
1722.62
1722.62
1722.62
1717.66
1717.66
1717.66
897.64
897.64
897.64
897.64
1994.56
1405
1386.95
2424.35
1010.35
1185
1180
753.21

Refrigeracin
Media (W)
Mxima puntual (W)
248.02
1158.28
184.21
795
107.48
549.1
107.48
549.1
107.48
549.1
107.48
549.1
107.48
549.1
472.76
1750.98
472.76
1750.98
472.76
1750.98
500
1811.42
500
1811.42
500
1811.42
500
1811.42
369.1
1578.72
427.64
1691.82
339.89
1383.22
569.92
2360.4
149.3
724.69
205.74
883.36
227.36
965
262.87
768.18

93

Anexos

1.2.6.9

Octubre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

7099.1

403.32

1972.97

Media
(W)
956.20

Mxima
puntual (W)
11609.80

Media (W)

Mxima puntual (W)

2138.87

7527.75

Oficina 008

722.04

25.26

151.69

100.99

1328.11

214.04

624.47

Oficina 009

594.07

25.26

146.10

93.60

1184.95

159.57

510.26

Oficina 011

1006.16

37.87

219.07

141.39

1908.37

294.19

885.02

Sala de Juntas

4512.02

327.60

1535.21

1114.71

9930.03

865.98

4429.53

Sala Honor

5250.3

378.18

1903.77

1068.29

10390.80

1180.34

5084.59

Oficina 014

1422.48

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 015

1422.48

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 016

1422.48

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 017

1422.48

38.04

274.53

47.09

1035.51

802.63

2007.20

Oficina 018

1171.15

37.89

244.57

89.12

1557.13

478.37

1361.21

Cafetera y restaurante

25049.47

2174.63

7647.96

8652.82

50658.50

2946.33

22089.90

Gestin Acadmica, Econmica y de Postgrado

8304.35

278.18

1687.37

723.65

11620.70

3087.57

8916.85

Comedor reservado

3574.05

301.96

1143.96

1228.61

7224.79

435.80

3140.19

Sala de Espera

1807.81

112.71

609.19

304.33

3339.96

461.07

1751.67

Servicio Reprografa

1941.34

62.81

440.90

134.33

2262.74

800.73

1902.46

94

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


997.96
607
1232
1232
1232
1232
1232
2240
2240
2240
1340
1340
1340
1340
1367.56
1300
1080
1888
579
729
781
624

Ventilacin
Caudal (l/s)
Carga total (W)
37.96
230.4
25.32
158.66
17.7
107.8
17.7
107.8
17.7
107.8
17.7
107.8
17.7
107.8
38.1
279.1
38.1
279.1
38.1
279.1
19.05
141.37
19.05
141.37
19.05
141.37
19.05
141.37
50.67
326.55
38.06
266.37
38.04
257.99
63.36
416.7
25.31
155.06
25.33
163.97
25.33
160.91
25.35
170.46

Media (W)
115.52
74.3
104.22
104.22
104.22
104.22
104.22
52.33
52.33
52.33
141.23
141.23
141.23
141.23
119.85
58.71
63.73
126.22
69.5
75.07
76.04
54.8

Calefaccin
Mxima puntual (W)
1937.15
1123.7
1885
1885
1885
1885
1885
1593.33
1593.33
1593.33
1040.6
1040.6
1040.6
1040.6
2167.56
1540.94
1428.66
2695.19
1060.74
1266.39
1316.88
983.14

Refrigeracin
Media (W)
Mxima puntual (W)
187.71
874.33
120
547.95
77.4
404.78
77.4
404.78
77.4
404.78
77.4
404.78
77.4
404.78
475.76
1803.34
475.76
1803.34
475.76
1803.34
400
1711.2
400
1711.2
400
1711.2
400
1711.2
301.7
1266.12
401.68
1668.15
295.65
1224.07
448.2
1925.45
110.67
529.87
157.98
667.99
166.78
708.44
182.25
1021.91

95

Anexos

1.2.6.10 Noviembre
Recinto

Carga interna (W)

Ventilacin
Caudal (l/s)

Carga total (W)

Calefaccin

Refrigeracin

Sala Audiovisual

6926.85

408.79

3725.56

Media
(W)
4459.09

Mxima
puntual (W)
19460.10

Media (W)

Mxima puntual (W)

120.35

2473.32

Oficina 008

710.58

25.68

286.70

553.61

2750.56

6.44

166.59

Oficina 009

584.33

25.66

278.33

472.20

2317.8

4.41

140.04

Oficina 011

987.12

38.40

416.37

727.80

3754.94

11.53

276.53

Sala de Juntas

4381.82

331.90

2962.19

4,865.02

16424.9

9.89

613.09

Sala Honor

5213.48

383.58

3910.78

4,907.31

17899.7

23.47

1116.16

Oficina 014

1360.53

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 015

1360.53

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 016

1360.53

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 017

1360.53

38.54

467.25

348.50

2452.93

183.42

1161.35

Oficina 018

1148.19

37.89

449.63

516.95

3297.25

65.45

650.33

Cafetera y restaurante

24663.33

2174.63

16693.15

30,101.41

77504.6

23.24

3014.5

Gestin Acadmica, Econmica y de Postgrado

8003.99

278.18

3072.89

4,097.54

23268.6

255.90

3615.05

Comedor reservado

3498.93

301.96

2420.41

4,411.36

11372.5

2.55

363.71

Sala de Espera

1801.12

112.71

1147.14

1,499.39

6038.9

12.77

456.14

Servicio Reprografa

1784.8

62.81

728.67

956.93

5360.27

54.12

5360.27

96

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


977.96
591
1221
1221
1221
1221
1221
2210
2210
2210
1321
1321
1321
1321
1360
1258
1058
1839
564
716
757
624

Ventilacin
Caudal (l/s)
Carga total (W)
38.51
539.89
25.68
294.31
17.95
202.8
17.95
202.8
17.95
202.8
17.95
202.8
17.95
202.8
38.63
476.1
38.63
476.1
38.63
476.1
19.32
240
19.32
240
19.32
240
19.32
240
51.41
590.66
38.6
457
38.58
447.1
64.25
735.82
25.7
282.1
25.7
296.1
25.7
295
25.71
299.55

Media (W)
616.12
448.75
463.73
463.73
463.73
463.73
463.73
370.33
370.33
370.33
620
620
620
620
728.59
402.67
437.52
857.17
407.26
462.34
485.61
418.6

Calefaccin
Mxima puntual (W)
3967.12
2480.68
3518.8
3518.8
3518.8
3518.8
3518.8
3863.3
3863.3
3863.3
1780.56
1780.56
1780.56
1780.56
4763.12
3215.63
3218.14
5985.63
2262.93
2900.57
3017.14
2618.28

Refrigeracin
Media (W)
Mxima puntual (W)
9.02
169.18
6.97
50.46
5.72
233.6
5.72
233.6
5.72
233.6
5.72
233.6
5.72
233.6
84.66
901.66
84.66
901.66
84.66
901.66
113
999.63
113
999.63
113
999.63
113
999.63
19.25
362.58
57.5
710.37
31.01
449.5
32.39
637.11
7.23
70.44
8.53
112.15
8.34
116.37
10.11
130.85

97

Anexos

1.2.6.11 Diciembre
Recinto

Ventilacin

Carga interna (W)

Calefaccin

Caudal (l/s)

Carga total (W)

Media (W)

Mxima puntual (W)

Sala Audiovisual

6785.1

408.79

4754.91

7,484.26

21215.7

Oficina 008

705.33

25.68

370.49

916.63

3107.26

Oficina 009

579.79

25.66

359.55

761.94

2596.02

Oficina 011

977.88

38.40

536.44

1199.01

4200.22

Sala de Juntas

4345.9

331.90

3816.93

7,374.81

17865.8

Sala Honor

5185.18

383.58

4643.79

7,713.87

19638.6

Oficina 014

1324.8

38.54

582.06

737.71

3200.65

Oficina 015

1324.8

38.54

582.06

737.71

3200.65

Oficina 016

1324.8

38.54

582.06

737.71

3200.65

Oficina 017

1324.8

38.54

582.06

737.71

3200.65

Oficina 018

1135.24

37.89

566.45

950.26

3826.97

Cafetera y restaurante

24624.13

2174.63

22013.66

43,468.61

82897

Gestin Acadmica, Econmica y de Postgrado

7891.22

278.18

3918.47

7,288.71

26052.7

Comedor reservado

3478.67

301.96

3183.18

6,387.32

12245.2

Sala de Espera

1799.12

112.71

1475.22

2,410.77

6628.92

Servicio Reprografa

1738.07

62.81

927.84

1,769.52

6093.33

98

Anexos

Recinto
OFICINA 103-104
OFICINA 101
OFICINA 102
OFICINA 105
OFICINA 106
OFICINA 107
OFICINA 108
OFICINA 109
OFICINA 110
OFICINA 113
OFICINA 111
OFICINA 112
OFICINA 115
OFICINA 116
OFICINA 117
OFICINA 118
OFICINA 119
OFICINA 120
OFICINA 121
OFICINA 122
OFICINA 123
OFICINA 124

Carga interna (W)


979.96
591
1222.47
1222.47
1222.47
1222.47
1222.47
2248
2248
2248
1340
1340
1340
1340
1366
1285
1065
1850
565
717
759
624

Caudal (l/s)
38.77
25.83
18.05
18.05
18.05
18.05
18.05
38.9
38.9
38.9
19.45
19.45
19.45
19.45
51.75
38.84
38.82
64.65
25.81
25.86
25.83
25.87

Ventilacin
Carga total (W)
539.61
358
251.17
251.17
251.17
251.17
251.17
579.63
579.63
579.63
292.3
292.3
292.3
292.3
739.2
557.4
552.4
907.1
348.6
366.7
364.07
372

Media (W)
1034.86
731.51
707.8
707.8
707.8
707.8
707.8
750
750
750
702.6
702.6
702.6
702.6
1204.48
786.77
794.58
1529.84
682.03
785.23
843.27
732

Calefaccin
Mxima puntual (W)
4678.21
2918.95
4029.6
4029.6
4029.6
4029.6
4029.6
4909
4909
4909
4110.69
4110.69
4110.69
4110.69
5442.94
3967.84
3858.39
7077.4
2686.73
3450.89
3629.99
3146.38

99

Anexos

CYPE INGENIEROS

2.1

Descripcin de materiales y elementos constructivos

2.1.1

Sistema envolvente

2.1.1.1

Cerramientos exteriores

Cerramiento exterior
Superficie total 977.95 m
Listado de capas:
1. Ladrillo cermico cataln
2. XPS Polestireno
3. Ladrillo cermico hueco
4. Enlucido de yeso
Espesor total:

12 cm.
4 cm.
11 cm.
1 cm.
28 cm.

Limitacin de demanda energtica: Um: 0.58 W/mK


Proteccin frente al ruido:
Masa superficial: 224.89 kg / m
Masa superficial del elemento base: 223.60 kg / m
Caracterizacin acstica, Rw(C; Ctr): 48.3(-1; -5) dB

2.1.1.2

Suelos

Solera - S.EPS50
Superficie total 1599.07 m
Listado de capas:
1. XPS Expandido con dixido de carbono CO2 [
0.034 W/[mK]]
2. Hormign armado d > 2500
Espesor total:

5 cm.
40 cm.
45 cm.

Limitacin de demanda energtica: Us: 0.27 W/mK


(Para una solera apoyada, con longitud caracterstica B' =
14.3 m)
Proteccin frente al ruido:
Masa superficial: 1041.88 kg / m
Masa superficial del elemento base: 1040.00 kg / m
Caracterizacin acstica, Rw(C; Ctr): 72.6(-1; -7) dB
Nivel global de presin de ruido de impactos normalizado,
Ln,w: 58.4 dB

100

Anexos

2.1.1.3

Cubiertas

T02.MW - Transitable Conv FU25


Superficie total 648.24 m
Falso techo suspendido (escayola (PES)) de 15 mm. de espesor con cmara de aire de 30 cm. de
altura y tendido de aislante trmico (lana mineral (MW)) de 20 mm. de espesor. Cubierta plana
transitable, no ventilada, tipo convencional, compuesta de forjado unidireccional de 25 cm. de
canto como elemento resistente, formacin de pendientes mediante hormign ligero de 10 cm. de
espesor medio, lmina bituminosa como barrera de vapor, lana mineral de 80 mm. de espesor como
aislante trmico, lmina bituminosa para impermeabilizacin, capa de mortero de 4 cm. y baldosa
cermica.
Listado de capas:
1. Plaqueta o baldosa cermica
1 cm.
2. Mortero de cemento o cal para albailera y
4 cm.
para revoco/enlucido 1250 < d < 1450
3. Betn fieltro o lmina
1 cm.
4. MW Lana mineral [0.04 W/[mK]]
8 cm.
5. Betn fieltro o lmina
1 cm.
6. Hormign con arcilla expandida como rido
10 cm.
principal d 1400
7. Forjado unidireccional (Elemento resistente)
25 cm.
8. Cmara de aire sin ventilar
30 cm.
9. MW Lana mineral [0.04 W/[mK]]
2 cm.
10. Placa de yeso o escayola 750 < d < 900
1.5 cm.
Espesor total:
83.5 cm.
Limitacin de demanda energtica: Uc refrigeracin: 0.29 W/mK
Uc calefaccin: 0.30 W/mK
Proteccin frente al ruido:
Masa superficial: 584.88 kg/m
Masa superficial del elemento base: 483.50 kg/m
Caracterizacin acstica, Rw(C; Ctr): 60.5(-1; -7) dB
Nivel global de presin de ruido de impactos normalizado,
Ln,w: 70.0 dB
Proteccin frente a la humedad:
Tipo de cubierta: Transitable, peatonal, con solado fijo.
Formacin de pendientes: Hormign ligero con arcilla
expandida. Tipo de impermeabilizacin: Material bituminoso
modificado.

101

Anexos

Enl15 - Transitable Conv FU25


Superficie total 311.94 m
Techo con enlucido de yeso. Cubierta plana transitable, no ventilada, tipo convencional, compuesta
de forjado unidireccional de 25 cm. de canto como elemento resistente, formacin de pendientes
mediante hormign ligero de 10 cm. de espesor medio, lmina bituminosa como barrera de vapor,
lana mineral de 80 mm. de espesor como aislante trmico, lmina bituminosa para
impermeabilizacin, capa de mortero de 4 cm. y baldosa cermica.
Listado de capas:
1. Plaqueta o baldosa cermica
1 cm.
2. Mortero de cemento o cal para albailera y para
4 cm.
revoco/enlucido 1250 < d < 1450
3. Betn fieltro o lmina
1 cm.
4. MW Lana mineral [0.04 W/[mK]]
8 cm.
5. Betn fieltro o lmina
1 cm.
6. Hormign con arcilla expandida como rido
10 cm.
principal d 1400
7. Forjado unidireccional (Elemento resistente)
25 cm.
8. Enlucido de yeso d < 1000
1.5 cm.
Espesor total:
51.5 cm.
Limitacin de demanda energtica: Uc refrigeracin: 0.37 W/mK
Uc calefaccin: 0.38 W/mK
Proteccin frente al ruido:
Masa superficial: 585.20 kg/m
Masa superficial del elemento base: 497.00 kg/m
Caracterizacin acstica, Rw(C; Ctr): 60.9(-1; -7) dB
Nivel global de presin de ruido de impactos normalizado,
Ln,w: 69.6 dB
Proteccin frente a la humedad:
Tipo de cubierta: Transitable, peatonal, con solado fijo.
Formacin de pendientes: Hormign ligero con arcilla
expandida. Tipo de impermeabilizacin: Material bituminoso
modificado.

102

Anexos

T02.MW - Gravas Conv Losa 20


Superficie total 430.50 m
Falso techo suspendido (escayola (PES)) de 15 mm. de espesor con cmara de aire de 30 cm. de
altura y tendido de aislante trmico (lana mineral (MW)) de 20 mm. de espesor. Cubierta plana no
transitable, no ventilada, tipo convencional, compuesta de losa maciza de 20 cm. de canto como
elemento resistente, formacin de pendientes mediante hormign ligero de 10 cm. de espesor
medio, lmina bituminosa como barrera de vapor, lana mineral de 60 mm. de espesor como aislante
trmico, lmina bituminosa para impermeabilizacin y capa de 10 cm. de grava.
Listado de capas:
1. Arena y grava [1700 < d < 2200]
10 cm.
2. Betn fieltro o lmina
1 cm.
3. MW Lana mineral [0.04 W/[mK]]
6 cm.
4. Betn fieltro o lmina
1 cm.
5. Hormign con arcilla expandida como rido
10 cm.
principal d 1400
6. Hormign armado d > 2500
20 cm.
7. Cmara de aire sin ventilar
30 cm.
8. MW Lana mineral [0.04 W/[mK]]
2 cm.
9. Placa de yeso o escayola 750 < d < 900
1.5 cm.
Espesor total:
81.5 cm.
Limitacin de demanda energtica: Uc refrigeracin: 0.36 W/mK
Uc calefaccin: 0.37 W/mK
Proteccin frente al ruido:
Masa superficial: 842.58 kg/m
Masa superficial del elemento base: 671.00 kg/m
Caracterizacin acstica, Rw(C; Ctr): 65.7(-1; -7) dB
Proteccin frente a la humedad:
Tipo de cubierta: No transitable, con gravas. Formacin de
pendientes: Hormign ligero con arcilla expandida. Tipo de
impermeabilizacin:
Material
bituminoso/bituminoso
modificado.

103

Anexos

Enl15 - Gravas Conv Losa 20


Superficie total 184.58 m
Techo con enlucido de yeso. Cubierta plana no transitable, no ventilada, tipo convencional,
compuesta de losa maciza de 20 cm. de canto como elemento resistente, formacin de pendientes
mediante hormign ligero de 10 cm. de espesor medio, lmina bituminosa como barrera de vapor,
lana mineral de 60 mm. de espesor como aislante trmico, lmina bituminosa para
impermeabilizacin y capa de 10 cm. de grava.
Listado de capas:
1. Arena y grava [1700 < d < 2200]
10 cm.
2. Betn fieltro o lmina
1 cm.
3. MW Lana mineral [0.04 W/[mK]]
6 cm.
4. Betn fieltro o lmina
1 cm.
5. Hormign con arcilla expandida como rido
10 cm.
principal d 1400
6. Hormign armado d > 2500
20 cm.
7. Enlucido de yeso d < 1000
1.5 cm.
Espesor total:
49.5 cm.
Limitacin de demanda energtica: Uc refrigeracin: 0.47 W/mK
Uc calefaccin: 0.49 W/mK
Proteccin frente al ruido:
Masa superficial: 842.90 kg/m
Masa superficial del elemento base: 684.50 kg/m
Caracterizacin acstica, Rw(C; Ctr): 66.0(-1; -7) dB
Proteccin frente a la humedad:
Tipo de cubierta: No transitable, con gravas. Formacin de
pendientes: Hormign ligero con arcilla expandida. Tipo de
impermeabilizacin:
Material
bituminoso/bituminoso
modificado.

104

Anexos

2.1.1.4

Huecos verticales

Tipo
Ventana de tipo 1 (x24)

Ventana de tipo 1 (x8)

Ventana de tipo 1 (x9)

Ventana de tipo 1 (x25)

Ventana de tipo 1 (x15)

Ventana de tipo 1 (x19)

Ventana de tipo 1
Ventana de tipo 1 (x4)

Ventana de tipo 1
Ventana de tipo 1 (x7)

Ventana de tipo 1

Acristalamiento
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x24)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x8)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x9)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x25)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x15)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x19)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x4)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x7)
Acristalamiento (U = 5.70

MM
Metlico

Ventanas
UMarco FM
5.70
0.07

Pa
Clase 2

CM
Intermedio
(0.60)

UHueco
5.70

FS
0.76

FH
0.61

Rw (C;Ctr)
27(-1;-1)

Metlico

5.70

0.08

Clase 2

Intermedio
(0.60)

5.70

0.76

0.60

27(-1;-1)

Metlico

5.70

0.07

Clase 2

Intermedio
(0.60)

5.70

0.86

0.69

27(-1;-1)

Metlico

5.70

0.08

Clase 2

Intermedio
(0.60)

5.70

1.00

0.79

27(-1;-1)

Metlico

5.70

0.07

Clase 2

Intermedio
(0.60)

5.70

1.00

0.80

27(-1;-1)

Metlico

5.70

0.08

Clase 2

Intermedio
(0.60)

5.70

0.86

0.68

27(-1;-1)

Metlico

5.70

0.10

Clase 2

5.70

0.67

0.52

27(-1;-1)

Metlico

5.70

0.14

Clase 2

Intermedio
(0.60)
Intermedio
(0.60)

5.70

0.76

0.57

27(-1;-1)

Metlico

5.70

0.16

Clase 2

5.70

1.00

0.73

27(-1;-1)

Metlico

5.70

0.10

Clase 2

Intermedio
(0.60)
Intermedio
(0.60)

5.70

1.00

0.78

27(-1;-1)

Metlico

5.70

0.10

Clase 2

Intermedio

5.70

0.82

0.64

27(-1;-1)

105

Anexos

Ventana de tipo 1 (x2)

W/(mK) / Factor solar = 0.85)


Acristalamiento (U = 5.70
W/(mK) / Factor solar = 0.85)
(x2)

MM Material del marco


UMarco Coeficiente de transmisin (W/mK)
FM Fraccin de marco
Pa
Permeabilidad al aire de la carpintera
CM Color del marco (absortividad)

Metlico

5.70

0.14

Clase 2

(0.60)
Intermedio
(0.60)

5.70

0.56

0.42

27(-1;-1)

Abreviaturas utilizadas
UHueco
Coeficiente de transmisin (W/mK)
FS
Factor de sombra
FH
Factor solar modificado
Rw (C;Ctr) Valores de aislamiento acstico (dB)

106

Anexos

Puertas
Tipo
Puerta genrica (x6)
Puerta de madera

UPuerta
2.00
2.00

Abreviaturas utilizadas
EI2 t-C5 Resistencia al fuego en minutos
g
Factor solar
UPuerta Coeficiente de transmisin (W/mK)
Rw (C;Ctr) Valores de aislamiento acstico (dB)

2.1.2

Sistema de compartimentacin

2.1.2.1

Particiones verticales

Superficie total 1362.86 m


Tabique LH
Particin de una hoja de ladrillo cermico hueco doble de 9 cm., con revestimiento de yeso de 2
cm. en cada cara.
Listado de capas:
1. Enlucido de yeso 1000 < d < 1300
2. Tabicn de LH doble [60 mm < E < 90 mm]
3. Enlucido de yeso 1000 < d < 1300
Espesor total:

1 cm.
8 cm.
1 cm.
10 cm.

Limitacin de demanda energtica: Um: 2.08 W/mK


Proteccin frente al ruido:
Masa superficial: 97.40 kg / m
Caracterizacin acstica, Rw(C; Ctr): 39.0(-1; -2) dB
Seguridad en caso de incendio:
Resistencia al fuego: EI 180

2.1.2.2

Forjado entre pisos

Enl15 - ENTRESUELO - S.EPS50

Superficie total 209.86 m

Listado de capas:
1. XPS Expandido con dixido de carbono CO2 [
5 cm.
0.034 W/[mK]]
2. Mortero de cemento
2 cm.
3. Entrevigado de hormign aligerado
30 cm.
4. Enlucido de yeso d < 1000
1.5 cm.
Espesor total:
38.5 cm.
Limitacin de demanda energtica: U (flujo descendente): 0.47 W/mK
U (flujo ascendente): 0.50 W/mK
(forjado expuesto a la intemperie, U: 0.52 W/mK)
Proteccin frente al ruido:
Masa superficial: 372.88 kg / m
Masa superficial del elemento base: 371.00 kg / m

107

Anexos

Caracterizacin acstica, Rw(C; Ctr): 56.2(-1; -7) dB


Nivel global de presin de ruido de impactos normalizado,
Ln,w: 74.1 dB

Superficie total 376.74 m

T02.MW - ENTRESUELO - S.EPS50

Listado de capas:
1 - XPS Expandido con dixido de carbono CO2 [
5 cm.
0.034 W/[mK]]
2 - MORTERO DE CEMENTO
2 cm.
3 - ENTREVIGADO HORMIGON ALIGERADO 30 cm.
4 - Cmara de aire sin ventilar
30 cm.
5 - MW Lana mineral [0.04 W/[mK]]
2 cm.
6 - Placa de yeso o escayola 750 < d < 900
1.5 cm.
Espesor total:
70.5 cm.
Limitacin de demanda energtica: U (flujo descendente): 0.35 W/mK
U (flujo ascendente): 0.37 W/mK
(forjado expuesto a la intemperie, U: 0.38 W/mK)
Proteccin frente al ruido:
Masa superficial: 372.55 kg / m
Masa superficial del elemento base: 357.50 kg / m
Caracterizacin acstica, Rw(C; Ctr): 55.7(-1; -7) dB
Nivel global de presin de ruido de impactos normalizado,
Ln,w: 74.6 dB

2.1.2.3

Huecos verticales interiores


Ventanas
UMar FM

Tipo

Acristalamiento

MM

Ventana
de tipo
1
Ventana
de tipo
1

Acristalamiento (U
= 5.70 W/(mK) /
Factor solar = 0.85)
Acristalamiento (U
= 5.70 W/(mK) /
Factor solar = 0.85)

Metlico

5.70

Metlico

5.70

Pa

CM

UHueco

0.08

Clas
e2

5.70

0.07

Clas
e2

Interme
dio
(0.60)
Interme
dio
(0.60)

co

5.70

Rw
(C;Ctr)
27(-1;1)
27(-1;1)

Abreviaturas utilizadas
MM Material del marco
CM
Color del marco (absortividad)
UMarc Coeficiente de transmisin
Coeficiente de transmisin
UHueco
(W/mK)
(W/mK)
o
Rw
Valores de aislamiento acstico
FM Fraccin de marco
(C;Ctr) (dB)
Permeabilidad al aire de la
Pa
carpintera

108

Anexos

Puertas
Tipo
Puerta genrica (x49)
Puerta genrica (x35)

UPuerta
2.00
2.00

Abreviaturas utilizadas
EI2 t-C5 Resistencia al fuego en minutos
Rw (C;Ctr) Valores de aislamiento acstico (dB)
UPuerta Coeficiente de transmisin (W/mK)

2.1.3

Materiales
Capas

Material
Arena y grava [1700 < d < 2200]
Betn fieltro o lmina
Enlucido de yeso 1000 < d < 1300
Enlucido de yeso d < 1000
Entrevigado de hormign aligerado
FU Entrevigado de hormign -Canto 250
mm.
Hormign armado d > 2500
Hormign armado d > 2500
Hormign con arcilla expandida como
rido principal d 1400
Ladrillo cermico cataln
Ladrillo cermico hueco
Mortero de cemento
Mortero de cemento o cal para albailera
y para revoco/enlucido 1250 < d < 1450
MW Lana mineral [0.04 W/[mK]]
MW Lana mineral [0.04 W/[mK]]
MW Lana mineral [0.04 W/[mK]]
Placa de yeso o escayola 750 < d < 900
Plaqueta o baldosa cermica
Tabicn de LH doble [60 mm. < E < 90
mm.]
XPS Expandido con dixido de carbono
CO2 [ 0.034 W/[mK]]
XPS Polestireno

e Espesor (cm)
Densidad (kg/m)
Conductividad (W/mK)

e
10
1
1
1.5
30
25

1450
1100
1150
900
1090
1330

2
0.23
0.57
0.4
1.13
1.32

RT
0.05
0.0435
0.0175
0.0375
0.266
0.189

Cp
1050
1000
1000
1000
1000
1000

50
50000
6
6
1
80

20
40
10

2600
2600
1400

2.5
2.5
0.55

0.08
0.16
0.182

1000
1000
1000

80
80
6

12
11
2
4

1020
920
1525
1350

0.567
0.435
1
0.7

0.212
0.253
0.02
0.0571

1000
1000
1000
1000

1
1
1
10

2
6
8
1.5
1
8

40
40
40
825
2000
930

0.041
0.041
0.041
0.25
1
0.432

0.488
1.46
1.95
0.06
0.01
0.185

1000
1000
1000
1000
800
1000

1
1
1
4
30
10

37.5

0.034

1.47

1000

100

30

0.038

1.05

1000

Abreviaturas utilizadas
RT Resistencia trmica (mK/W)
Cp Calor especfico (J/kgK)
Factor de resistencia a la difusin del vapor

de agua

109

Anexos

Vidrios
Material
Acristalamiento (U = 5.70 W/(mK) / Factor solar = 0.85)

UVidrio
5.70

g
0.85

Abreviaturas utilizadas
UVidrio Coeficiente de transmisin (W/mK)
g Factor solar

Marcos
Material
Metlico

UMarco
5.70

Abreviaturas utilizadas
UMarco Coeficiente de transmisin (W/mK)

2.1.4

Puentes trmicos

Puentes trmicos lineales


Nombre
Fachada en esquina vertical saliente
Fachada en esquina vertical entrante
Forjado en esquina horizontal saliente
Unin de solera con pared exterior
Forjado entre pisos
Ventana en fachada

Transmitancia lineal (W/mK)

0.08
-0.15
0.39
0.14
0.41
0.20

FRsi
0.84
0.91
0.72
0.75
0.76
0.76

Abreviaturas utilizadas
Factor de temperatura de la superficie
FRsi
interior

110

Anexos

2.2

Listado completo de cargas trmicas

2.2.1

Parmetros generales

Trmino municipal: Lleida


Latitud (grados): 41.62 grados
Altitud sobre el nivel del mar: 155 m
Percentil para verano: 5.0 %
Temperatura seca verano: 27.11 C
Temperatura hmeda verano: 22.50 C
Oscilacin media diaria: 8.4 C
Oscilacin media anual: 27.5 C
Percentil para invierno: 97.5 %
Temperatura seca en invierno: 1.20 C
Humedad relativa en invierno: 90 %
Velocidad del viento: 3.6 m/s
Temperatura del terreno: 6.40 C
Porcentaje de mayoracin por la orientacin N: 20 %
Porcentaje de mayoracin por la orientacin S: 0 %
Porcentaje de mayoracin por la orientacin E: 10 %
Porcentaje de mayoracin por la orientacin O: 10 %
Suplemento de intermitencia para calefaccin: 5 %
Porcentaje de cargas debido a la propia instalacin: 3 %
Porcentaje de mayoracin de cargas (Invierno): 0 %
Porcentaje de mayoracin de cargas (Verano): 0 %

111

Anexos

2.2.2

Resultados de clculo de los recintos

2.2.2.1

Refrigeracin

Planta baja

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 014 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.0

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

-39.85

19.8

Ventanas exteriores
Nm. ventanas
2

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1981.92

409.5

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

14.1

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

Teq. (C)
22.4

-104.96

23.8

-7.35
Total estructural

1829.76

Ocupantes

112

Anexos

Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

205.32

172.89

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

290.95

1.08

314.22

Instalaciones y otras cargas

290.95
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

776.18

Cargas interiores totales

981.50

3.0 %

0.93

Cargas internas totales

78.18
205.32

2684.12

Potencia trmica interna total

2889.44

Ventilacin
Caudal de ventilacin total (m/h)
130.9
Cargas de ventilacin

417.30

-182.35

417.30

-182.35

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 29.1 m

107.4 W/m

622.62

POTENCIA TRMICA TOTAL :

234.96
2501.77
3124.4 W

113

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 015 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

10.6

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-35.24

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1984.35

409.5

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

13.7

2.08

Hueco interior

1.7

2.00

Peso (kg/m)

Teq. (C)

97

22.4

-101.97

23.8

-7.35
Total estructural

1839.78

205.32

172.89

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

283.55

Coef. iluminacin
1.08

306.23

Instalaciones y otras cargas

283.55
Cargas interiores

205.32

760.79

Cargas interiores totales

966.11

114

Anexos

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.93

Cargas internas totales

78.02
205.32

2678.59

Potencia trmica interna total

2883.91

Ventilacin
Caudal de ventilacin total (m/h)
127.6
Cargas de ventilacin

406.70

-177.71

406.70

-177.71

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 28.4 m

109.8 W/m

612.02

POTENCIA TRMICA TOTAL :

228.98
2500.88
3112.9 W

115

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 016 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.3

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-37.38

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1979.80

409.5

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

14.4

2.08

Hueco interior

1.7

2.00

Peso (kg/m)

Teq. (C)

97

22.4

-107.09

23.8

-7.35
Total estructural

1827.98

205.32

172.89

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

296.23

Coef. iluminacin
1.08

319.93

Instalaciones y otras cargas

296.23
Cargas interiores

205.32

787.16

Cargas interiores totales

992.48

116

Anexos

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.93

Cargas internas totales

78.45
205.32

2693.60

Potencia trmica interna total

2898.92

Ventilacin
Caudal de ventilacin total (m/h)
133.3
Cargas de ventilacin

424.88

-185.66

424.88

-185.66

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 29.6 m

105.9 W/m

630.20

POTENCIA TRMICA TOTAL :

239.22
2507.94
3138.1 W

117

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 017 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

11.7

0.58

225

Intermedio

18.8

-49.09

Fachada

10.6

0.58

225

Intermedio

20.3

-35.29

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1900.33

409.1

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

10.2

Peso (kg/m)

2.08

Teq. (C)

97

-75.47

22.4
Total estructural

1740.49

205.32

172.89

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

281.72

Coef. iluminacin
1.08

304.26

Instalaciones y otras cargas

281.72
Cargas interiores

205.32

756.98

Cargas interiores totales

962.30

118

Anexos

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.93

Cargas internas totales

74.92
205.32

2572.40

Potencia trmica interna total

2777.72

Ventilacin
Caudal de ventilacin total (m/h)
126.8
Cargas de ventilacin

404.07

-176.56

404.07

-176.56

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 28.2 m

106.7 W/m

609.39

POTENCIA TRMICA TOTAL :

227.51
2395.83
3005.2 W

119

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 018 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

10.3

0.58

225

Intermedio

18.8

-43.50

Fachada

7.9

0.58

225

Intermedio

19.5

-29.72

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1218.14

404.1

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

17.4

2.08

Hueco interior

1.7

2.00

Peso (kg/m)

Teq. (C)

97

22.4

-128.83

23.8

-7.35
Total estructural

1008.74

205.32

172.89

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

279.14

Coef. iluminacin
1.08

301.47

Instalaciones y otras cargas

279.14
Cargas interiores

205.32

751.62

120

Anexos

Cargas interiores totales

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.90

956.94
52.81

205.32

1813.17

Potencia trmica interna total

2018.49

Cargas internas totales

Ventilacin
Caudal de ventilacin total (m/h)
125.6
Cargas de ventilacin

400.37

-174.95

400.37

-174.95

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 27.9 m

80.4 W/m

605.69

POTENCIA TRMICA TOTAL :

225.42
1638.22
2243.9 W

121

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

REPROGRAFIA (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 19.9 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 19.7 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 10h (8 hora solar) del da 1 de Junio


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

13.2

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

22.0

-31.02

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1849.12

386.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

57.7

2.08

97

22.3

-442.90

Forjado

27.2

0.35

373

23.9

-20.54

Hueco interior

3.3

2.00

22.9

-20.60
Total estructural

1334.07

410.64

334.50

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

55.75

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

535.82

Coef. iluminacin
1.05

562.61

Instalaciones y otras cargas

535.82
Cargas interiores

410.64

1429.17

122

Anexos

Cargas interiores totales

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.87

1839.81
82.90

410.64

2846.13

Potencia trmica interna total

3256.77

Cargas internas totales

Ventilacin
Caudal de ventilacin total (m/h)
241.1
Cargas de ventilacin

757.76

-470.45

757.76

-470.45

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 53.6 m

66.1 W/m

1168.40

POTENCIA TRMICA TOTAL :

287.31
2375.68
3544.1 W

123

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

GESTION (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

25.2

0.58

225

Intermedio

20.4

-82.27

Fachada

50.6

0.58

225

Intermedio

21.4

-136.94

Fachada

14.3

0.58

225

Intermedio

23.5

-20.93

Ventanas exteriores
Nm. ventanas
4

Orientacin

Superficie total (m)

U (W/(mK))

6.1

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
19.2

116.65

12.1

5.70

0.97

409.1

4964.24

1.5

5.70

0.97

70.3

105.44

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

130.1

Peso (kg/m)

0.29

585

Color

Teq. (C)

Intermedio

35.43

26.9

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

55.3

2.08

97

25.2

Forjado

12.0

0.35

373

23.6

-97.21
-10.39
Total estructural

4874.02

Ocupantes

124

Anexos

Actividad

N personas

Empleado de oficina

C.lat/per (W)

19

C.sen/per (W)

68.44

58.26

1300.36

1106.85

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

1884.59

1.05

1978.82

Instalaciones y otras cargas

1884.59
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

1300.36

4910.75

Cargas interiores totales

6211.11

3.0 %

0.89

Cargas internas totales

293.54
1300.36

10078.31

Potencia trmica interna total

11378.67

Ventilacin
Caudal de ventilacin total (m/h)
848.1

3238.76

-131.84

3238.76

-131.84

Potencia trmica de ventilacin total

3106.92

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 188.5 m

76.9 W/m

4539.12

POTENCIA TRMICA TOTAL :

9946.48
14485.6 W

125

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

ATENCION (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

19.1

0.58

225

Intermedio

23.1

-32.50

Fachada

12.0

0.58

225

Intermedio

20.4

-39.22

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
58.17

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

37.5

Peso (kg/m)

0.29

585

Color

Teq. (C)

Intermedio

1.73

26.2

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

10.6

2.08

Hueco interior

4.1

2.00

Peso (kg/m)

Teq. (C)

97

25.2

-18.60

25.8

-1.99
Total estructural

-32.41

273.76

233.02

Ocupantes
Actividad
Empleado de oficina

N personas
4

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

126

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

380.02

1.05

399.02

Instalaciones y otras cargas

380.02
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

273.76

999.53

Cargas interiores totales

1273.29

3.0 %
Cargas internas totales

0.78

29.01
273.76

996.13

Potencia trmica interna total

1269.89

Ventilacin
Caudal de ventilacin total (m/h)
171.0

653.08

-26.58

653.08

-26.58

Potencia trmica de ventilacin total

626.49

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 38.0 m

49.9 W/m

926.84

POTENCIA TRMICA TOTAL :

969.54
1896.4 W

127

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 011 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.1

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-36.28

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.7

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
90.61

19.2

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

14.1

Peso (kg/m)

2.08

Teq. (C)

97

-24.83

25.2
Total estructural

29.50

205.32

174.77

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

262.91

1.05

276.06

Instalaciones y otras cargas

262.91
Cargas interiores

Cargas debidas a la propia instalacin

205.32

704.34

Cargas interiores totales

909.66

3.0 %

22.02

128

Anexos

FACTOR CALOR SENSIBLE :

0.79

Cargas internas totales

205.32

755.86

Potencia trmica interna total

961.18

451.83

-18.39

Ventilacin
Caudal de ventilacin total (m/h)
118.3
Cargas de ventilacin

451.83

-18.39

Potencia trmica de ventilacin total

433.44

Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 26.3 m

53.0 W/m

657.15

POTENCIA TRMICA TOTAL :

737.46
1394.6 W

129

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 009 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-19.43

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
44.04

19.2

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

6.6

Peso (kg/m)

2.08

Teq. (C)

97

-11.52

25.2
Total estructural

13.09

136.88

116.51

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

136.96

1.05

143.80

Instalaciones y otras cargas

136.96
Cargas interiores

Cargas debidas a la propia instalacin

136.88

391.01

Cargas interiores totales

527.89

3.0 %

12.12

130

Anexos

FACTOR CALOR SENSIBLE :

0.75

Cargas internas totales

136.88

416.22

Potencia trmica interna total

553.10

235.37

-9.58

Ventilacin
Caudal de ventilacin total (m/h)
61.6
Cargas de ventilacin

235.37

-9.58

Potencia trmica de ventilacin total

225.79

Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 13.7 m

56.9 W/m

372.25

POTENCIA TRMICA TOTAL :

406.64
778.9 W

131

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 008 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.3

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-30.34

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
58.18

19.2

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

22.6

Peso (kg/m)

2.08

Teq. (C)

97

-39.73

25.2
Total estructural

-11.88

205.32

174.77

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

204.77

1.05

215.01

Instalaciones y otras cargas

204.77
Cargas interiores

Cargas debidas a la propia instalacin

205.32

585.15

Cargas interiores totales

790.47

3.0 %

17.20

132

Anexos

FACTOR CALOR SENSIBLE :

0.74

Cargas internas totales

205.32

590.47

Potencia trmica interna total

795.79

351.91

-14.32

Ventilacin
Caudal de ventilacin total (m/h)
92.1
Cargas de ventilacin

351.91

-14.32

Potencia trmica de ventilacin total

337.58

Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 20.5 m

55.3 W/m

557.23

POTENCIA TRMICA TOTAL :

576.14
1133.4 W

133

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA DE JUNTAS (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.1 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 21.8 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 22 de Mayo


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

34.7

0.58

225

Intermedio

25.6

-7.60

Fachada

24.0

0.58

225

Intermedio

20.9

-71.29

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

Coef. radiacin solar

Ganancia (W/m)

7.6

5.70

0.97

423.8

3203.20

1.5

5.70

0.97

390.4

570.20

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

71.5

Peso (kg/m)

0.29

585

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Intermedio

28.5

51.62

Cerramientos interiores
Tipo

Superficie (m)

Forjado

1.4

0.35

373

Teq. (C)
-1.29

23.4
Total estructural

3744.84

1055.60

1486.59

Ocupantes
Actividad
Sentado o en reposo

N personas
26

C.lat/per (W)
40.60

C.sen/per (W)
57.18

Iluminacin

134

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

761.45

1.05

799.52

Instalaciones y otras cargas

761.45
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

1055.60

2967.63

Cargas interiores totales

4023.23

3.0 %
Cargas internas totales

0.87

201.37
1055.60

6913.84

Potencia trmica interna total

7969.44

Ventilacin
Caudal de ventilacin total (m/h)
1142.2

4180.82

-322.50

4180.82

-322.50

Potencia trmica de ventilacin total

3858.32

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 76.1 m

155.3 W/m

5236.42

POTENCIA TRMICA TOTAL :

6591.35
11827.8 W

135

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA HONOR (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 16h (14 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

36.0

0.58

225

Intermedio

23.6

-51.03

Fachada

4.7

0.58

225

Intermedio

19.9

-16.71

Fachada

6.5

0.58

225

Intermedio

20.5

-20.81

Fachada

14.0

0.58

225

Intermedio

23.5

-20.61

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

Coef. radiacin solar

Ganancia (W/m)

1.4

5.70

0.97

16.4

23.11

2.5

5.70

0.97

302.0

755.44

Puertas exteriores
Nm. puertas

Tipo

Opaca

Orientacin

Superficie (m)

U (W/(mK))

1.7

2.00

Teq. (C)
25.5

-1.64

Cubiertas
Tipo
Azotea

Superficie (m)

U (W/(mK))

13.4

0.29

Peso (kg/m)
585

Color
Intermedio

Teq. (C)
26.5

1.92

Cerramientos interiores

136

Anexos

Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

10.4

2.08

97

24.2

-38.29

Forjado

23.2

0.35

373

23.6

-20.03

Hueco interior

3.0

2.00

25.8

-1.49
Total estructural

609.85

1299.20

1770.62

Ocupantes
Actividad

N personas

Sentado o en reposo

C.lat/per (W)

32

C.sen/per (W)

40.60

55.33

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

948.87

0.97

920.41

Instalaciones y otras cargas

948.87
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

1299.20

3482.51

Cargas interiores totales

4781.71

3.0 %

0.76

122.77
1299.20

4215.14

Potencia trmica interna total

5514.34

Cargas internas totales

Ventilacin
Caudal de ventilacin total (m/h)
1423.3

5435.62

-221.26

5435.62

-221.26

Potencia trmica de ventilacin total

5214.36

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 94.9 m

113.1 W/m

6734.82

POTENCIA TRMICA TOTAL :

3993.88
10728.7 W

137

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA AUDIOVISUAL (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 16h (14 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

29.0

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

23.0

-50.93

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

Coef. radiacin solar

Ganancia (W/m)

4.9

5.70

0.97

301.4

1480.25

2.3

5.70

0.97

300.1

703.53

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

95.1

Peso (kg/m)

0.29

Color

585

Teq. (C)

Intermedio

11.52

26.4

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

6.0

Peso (kg/m)

2.08

Teq. (C)

97

-21.93

24.2
Total estructural

2122.43

1299.20

1770.62

Ocupantes
Actividad

N personas

Sentado o en reposo

C.lat/per (W)

32

C.sen/per (W)

40.60

55.33

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
950.98

Coef. iluminacin
0.97

922.45

138

Anexos

Instalaciones y otras cargas

950.98
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

1299.20

3486.67

Cargas interiores totales

4785.87

3.0 %

0.82

Cargas internas totales

168.27
1299.20

5777.37

Potencia trmica interna total

7076.57

Ventilacin
Caudal de ventilacin total (m/h)
1426.5

5447.71

-221.75

5447.71

-221.75

Potencia trmica de ventilacin total

5225.96

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 95.1 m

129.4 W/m

6746.91

POTENCIA TRMICA TOTAL :

5555.62
12302.5 W

139

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA DE ESPERA (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 16h (14 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

4.0

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

21.1

-11.46

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.1

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
292.15

277.1

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

20.9

2.08

97

24.2

-76.66

Forjado

8.9

0.47

373

23.4

-10.85

Hueco interior

3.0

2.00

25.8

-1.49
Total estructural

191.69

324.80

442.66

Ocupantes
Actividad

N personas

Sentado o en reposo

C.lat/per (W)

C.sen/per (W)

40.60

55.33

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

225.06

Coef. iluminacin
0.97

218.31

Instalaciones y otras cargas

225.06
Cargas interiores

324.80

846.68

140

Anexos

Cargas interiores totales

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

3.0 %

0.77

1171.48
31.15

324.80

1069.52

Potencia trmica interna total

1394.32

Cargas internas totales

Ventilacin
Caudal de ventilacin total (m/h)
337.6

1289.28

-52.48

1289.28

-52.48

Potencia trmica de ventilacin total

1236.80

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 22.5 m

116.9 W/m

1614.08

POTENCIA TRMICA TOTAL :

1017.04
2631.1 W

141

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

CAFETERIA (Restauracin)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

43.8

0.58

225

Intermedio

25.2

-20.87

Fachada

28.3

0.58

225

Intermedio

20.4

-92.50

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

10.9

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
209.63

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

265.0

Peso (kg/m)

0.29

585

Color

Teq. (C)

Intermedio

120.28

27.5

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

49.8

2.08

Hueco interior

3.0

2.00

Peso (kg/m)

Teq. (C)

97

25.2

-87.58

25.8

-1.49
Total estructural

127.47

7078.41

9968.42

Ocupantes
Actividad
Sentado o en reposo

N personas
177

C.lat/per (W)
39.99

C.sen/per (W)
56.32

Iluminacin

142

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

1589.86

1.05

1669.35

Instalaciones y otras cargas

1165.90
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

7078.41

12267.73

Cargas interiores totales

19346.14

3.0 %
Cargas internas totales

0.64

371.86
7078.41

12767.06

Potencia trmica interna total

19845.47

Ventilacin
Caudal de ventilacin total (m/h)
7949.3

30358.35

-1235.75

30358.35

-1235.75

Potencia trmica de ventilacin total

29122.59

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 265.0 m

184.8 W/m

37436.75

POTENCIA TRMICA TOTAL :

11531.31
48968.1 W

143

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

COMEDOR (Restauracin)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.8

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

21.3

-32.50

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1967.31

409.0

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

35.7

Peso (kg/m)

Color

0.29

585

U (W/(mK))

Peso (kg/m)

Teq. (C)

Intermedio

16.72

27.6

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

32.8

2.08

Teq. (C)

97

-57.67

25.2
Total estructural

1893.86

999.77

1407.97

Ocupantes
Actividad

N personas

Sentado o en reposo

C.lat/per (W)

25

C.sen/per (W)

39.99

56.32

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

216.35

Coef. iluminacin
1.05

227.17

Instalaciones y otras cargas

158.66

144

Anexos

Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

999.77

1718.09

Cargas interiores totales

2717.87

3.0 %

0.79

Cargas internas totales

108.36
999.77

3720.31

Potencia trmica interna total

4720.09

Ventilacin
Caudal de ventilacin total (m/h)
1081.7

4131.16

-168.16

4131.16

-168.16

Potencia trmica de ventilacin total

3963.00

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 36.1 m

240.8 W/m

5130.94

POTENCIA TRMICA TOTAL :

3552.15
8683.1 W

145

Anexos

Planta 1

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 101 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 19.9 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 19.7 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 10h (8 hora solar) del da 1 de Junio


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.0

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

-13.73

22.1

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
610.07

382.4

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

16.1

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

30.3

24.83

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

28.8

2.08

97

22.3

-220.92

Forjado

15.8

0.50

373

23.8

-17.56

Hueco interior

2.9

2.20

22.9

-19.91
Total estructural

362.78

136.88

111.50

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
55.75

146

Anexos

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

160.68

1.05

168.71

Instalaciones y otras cargas

160.68
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

439.64

Cargas interiores totales

576.52

3.0 %

0.86

Cargas internas totales

24.07
136.88

826.49

Potencia trmica interna total

963.37

Ventilacin
Caudal de ventilacin total (m/h)
72.3
Cargas de ventilacin

227.23

-141.07

227.23

-141.07

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 16.1 m

65.3 W/m

86.16

364.11

POTENCIA TRMICA TOTAL :

685.41
1049.5 W

147

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 102 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.6

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-21.55

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
44.18

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

15.2

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

9.23

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

12.1

2.08

97

25.2

-21.22

Forjado

5.2

0.50

373

23.4

-6.73

Hueco interior

1.7

2.20

25.8

-0.90
Total estructural

3.01

136.88

116.51

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

148

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

151.90

1.05

159.49

Instalaciones y otras cargas

151.90
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

421.63

Cargas interiores totales

558.51

3.0 %
Cargas internas totales

0.76

12.74
136.88

437.38

Potencia trmica interna total

574.26

Ventilacin
Caudal de ventilacin total (m/h)
68.4

261.04

-10.63

261.04

-10.63

Potencia trmica de ventilacin total

250.42

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 15.2 m

54.3 W/m

397.92

POTENCIA TRMICA TOTAL :

426.75
824.7 W

149

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 103/104 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.6

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-37.87

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
88.46

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

27.7

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

16.81

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

12.8

2.08

97

25.2

-22.59

Forjado

1.3

0.50

373

23.4

-1.66

Hueco interior

3.3

2.20

25.8

-1.81
Total estructural

41.35

205.32

174.77

Ocupantes
Actividad
Empleado de oficina

N personas
3

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

150

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

276.58

1.05

290.41

Instalaciones y otras cargas

276.58
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

732.37

Cargas interiores totales

937.69

3.0 %
Cargas internas totales

0.80

23.21
205.32

796.93

Potencia trmica interna total

1002.25

Ventilacin
Caudal de ventilacin total (m/h)
124.5

475.32

-19.35

475.32

-19.35

Potencia trmica de ventilacin total

455.97

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 27.7 m

52.7 W/m

680.64

POTENCIA TRMICA TOTAL :

777.58
1458.2 W

151

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 105 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-19.13

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
46.24

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

14.1

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

8.58

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.6

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

25.2

-11.59

25.8

-0.90
Total estructural

23.20

136.88

116.51

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
141.12

Coef. iluminacin
1.05

148.18

152

Anexos

Instalaciones y otras cargas

141.12
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

399.54

Cargas interiores totales

536.42

3.0 %

0.76

Cargas internas totales

12.68
136.88

435.42

Potencia trmica interna total

572.30

Ventilacin
Caudal de ventilacin total (m/h)
63.5

242.52

-9.87

242.52

-9.87

Potencia trmica de ventilacin total

232.65

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 14.1 m

57.0 W/m

379.40

POTENCIA TRMICA TOTAL :

425.55
804.9 W

153

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 106 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.5

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-17.91

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
45.38

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.4

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

8.14

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.2

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

25.2

-10.85

25.8

-0.90
Total estructural

23.87

136.88

116.51

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
133.94

Coef. iluminacin
1.05

140.64

154

Anexos

Instalaciones y otras cargas

133.94
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

384.83

Cargas interiores totales

521.71

3.0 %

0.75

Cargas internas totales

12.26
136.88

420.96

Potencia trmica interna total

557.84

Ventilacin
Caudal de ventilacin total (m/h)
60.3

230.19

-9.37

230.19

-9.37

Potencia trmica de ventilacin total

220.82

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 13.4 m

58.1 W/m

367.07

POTENCIA TRMICA TOTAL :

411.59
778.7 W

155

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 107 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.7

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-21.74

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
45.11

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

15.4

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

9.34

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

7.3

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

25.2

-12.89

25.8

-0.90
Total estructural

18.92

136.88

116.51

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
153.78

Coef. iluminacin
1.05

161.47

156

Anexos

Instalaciones y otras cargas

153.78
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

425.50

Cargas interiores totales

562.38

3.0 %

0.77

Cargas internas totales

13.33
136.88

457.75

Potencia trmica interna total

594.63

Ventilacin
Caudal de ventilacin total (m/h)
69.2

264.28

-10.76

264.28

-10.76

Potencia trmica de ventilacin total

253.52

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 15.4 m

55.2 W/m

401.16

POTENCIA TRMICA TOTAL :

446.99
848.2 W

157

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 108 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.4

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-17.47

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.2

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
42.38

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.9

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

7.84

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

17.8

2.08

25.2

-31.28

Hueco interior

1.7

2.20

97

25.8

-0.90

Hueco interior

1.5

5.70

25.8

-2.08
Total estructural

-1.52

136.88

116.51

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

158

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

129.04

1.05

135.49

Instalaciones y otras cargas

129.04
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

374.78

Cargas interiores totales

511.66

3.0 %
Cargas internas totales

0.74

11.20
136.88

384.45

Potencia trmica interna total

521.33

Ventilacin
Caudal de ventilacin total (m/h)
58.1

221.76

-9.03

221.76

-9.03

Potencia trmica de ventilacin total

212.74

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 12.9 m

56.9 W/m

358.64

POTENCIA TRMICA TOTAL :

375.43
734.1 W

159

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 109 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

12.3

0.58

225

Intermedio

20.3

-40.90

Fachada

13.2

0.58

225

Intermedio

19.9

-47.01

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1953.59

409.4

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

28.7

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

-22.62

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

15.4

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-114.53

23.8

-8.09
Total estructural

1720.44

205.32

172.89

Ocupantes
Actividad
Empleado de oficina

N personas
3

C.lat/per (W)
68.44

C.sen/per (W)
57.63

Iluminacin

160

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

286.94

1.08

309.89

Instalaciones y otras cargas

286.94
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

767.84

Cargas interiores totales

973.16

3.0 %
Cargas internas totales

0.93

74.65
205.32

2562.92

Potencia trmica interna total

2768.24

Ventilacin
Caudal de ventilacin total (m/h)
129.1

411.56

-179.83

411.56

-179.83

Potencia trmica de ventilacin total

231.72

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 28.7 m

104.6 W/m

616.88

POTENCIA TRMICA TOTAL :

2383.09
3000.0 W

161

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 110 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.1

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-36.66

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1951.78

409.4

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

26.5

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

-20.93

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

11.9

2.08

Hueco interior

1.7

2.20

97

22.4
23.8

-88.60
-8.09

Hueco interior

2.2

5.70

23.8

-27.66
Total estructural

1769.84

205.32

172.89

Ocupantes
Actividad
Empleado de oficina

N personas
3

C.lat/per (W)
68.44

C.sen/per (W)
57.63

Iluminacin

162

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

265.43

1.08

286.67

Instalaciones y otras cargas

265.43
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

723.10

Cargas interiores totales

928.42

3.0 %
Cargas internas totales

0.93

74.79
205.32

2567.73

Potencia trmica interna total

2773.05

Ventilacin
Caudal de ventilacin total (m/h)
119.4

380.71

-166.36

380.71

-166.36

Potencia trmica de ventilacin total

214.35

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 26.5 m

112.5 W/m

586.03

POTENCIA TRMICA TOTAL :

2401.38
2987.4 W

163

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 111 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-19.52

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
972.24

409.3

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.9

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

-11.02

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.6

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-48.89

23.8

-8.09
Total estructural

884.73

136.88

115.26

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
138.59

Coef. iluminacin
1.08

149.68

164

Anexos

Instalaciones y otras cargas

138.59
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

402.27

Cargas interiores totales

539.15

3.0 %

0.91

Cargas internas totales

38.61
136.88

1325.61

Potencia trmica interna total

1462.49

Ventilacin
Caudal de ventilacin total (m/h)
62.4
Cargas de ventilacin

198.78

-86.86

198.78

-86.86

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 13.9 m

113.6 W/m

335.66

POTENCIA TRMICA TOTAL :

111.92
1238.75
1574.4 W

165

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 112 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.7

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-18.93

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
988.35

409.5

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.6

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

-10.83

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.4

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-47.85

23.8

-8.09
Total estructural

902.65

136.88

115.26

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
136.24

Coef. iluminacin
1.08

147.14

166

Anexos

Instalaciones y otras cargas

136.24
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

397.38

Cargas interiores totales

534.26

3.0 %

0.91

Cargas internas totales

39.00
136.88

1339.03

Potencia trmica interna total

1475.91

Ventilacin
Caudal de ventilacin total (m/h)
61.3
Cargas de ventilacin

195.41

-85.39

195.41

-85.39

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 13.6 m

116.4 W/m

332.29

POTENCIA TRMICA TOTAL :

110.02
1253.65
1585.9 W

167

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 113 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.7

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-38.66

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.7

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1933.16

409.3

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

27.5

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

-21.67

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

13.0

2.08

Hueco interior

3.3

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-96.74

23.8

-16.17
Total estructural

1759.91

205.32

172.89

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
274.83

Coef. iluminacin
1.08

296.81

168

Anexos

Instalaciones y otras cargas

274.83
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

742.65

Cargas interiores totales

947.97

3.0 %

0.93

Cargas internas totales

75.08
205.32

2577.64

Potencia trmica interna total

2782.96

Ventilacin
Caudal de ventilacin total (m/h)
123.7
Cargas de ventilacin

394.18

-172.24

394.18

-172.24

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 27.5 m

109.3 W/m

599.50

POTENCIA TRMICA TOTAL :

221.94
2405.39
3004.9 W

169

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 115 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.6

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.3

-18.49

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
926.94

408.9

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.4

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

-9.87

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.2

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-45.77

23.8

-8.09
Total estructural

844.72

136.88

115.26

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

57.63

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
131.54

Coef. iluminacin
1.08

142.06

170

Anexos

Instalaciones y otras cargas

131.54
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

387.61

Cargas interiores totales

524.49

3.0 %

0.90

Cargas internas totales

36.97
136.88

1269.30

Potencia trmica interna total

1406.18

Ventilacin
Caudal de ventilacin total (m/h)
59.2
Cargas de ventilacin

188.67

-82.44

188.67

-82.44

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 13.2 m

115.0 W/m

325.55

POTENCIA TRMICA TOTAL :

106.23
1186.86
1512.4 W

171

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 116 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

6.1

0.58

225

Intermedio

20.3

-20.29

Fachada

12.2

0.58

225

Intermedio

18.8

-51.29

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
944.89

409.1

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

14.2

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

-11.27

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

7.0

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.4

-52.01

23.8

-8.09
Total estructural

801.95

136.88

115.26

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
57.63

Iluminacin

172

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

141.71

1.08

153.05

Instalaciones y otras cargas

141.71
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

408.76

Cargas interiores totales

545.64

3.0 %
Cargas internas totales

0.90

36.32
136.88

1247.03

Potencia trmica interna total

1383.91

Ventilacin
Caudal de ventilacin total (m/h)
63.8

203.26

-88.82

203.26

-88.82

Potencia trmica de ventilacin total

114.44

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 14.2 m

105.7 W/m

340.14

POTENCIA TRMICA TOTAL :

1158.22
1498.4 W

173

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 117 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 26.1 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 17h (15 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

17.2

0.58

225

Intermedio

20.7

-53.09

Fachada

15.4

0.58

225

Intermedio

23.7

-20.84

Fachada

12.4

0.58

225

Intermedio

20.1

-42.90

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

Coef. radiacin solar

Ganancia (W/m)

1.6

5.70

0.97

343.6

538.26

1.6

5.70

0.97

210.5

332.83

4.5

5.70

0.97

20.9

94.97

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

40.7

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

7.57

26.5

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

15.3

Peso (kg/m)

2.08

Teq. (C)

97

-39.94

24.7
Total estructural

816.87

342.20

288.14

Ocupantes
Actividad
Empleado de oficina

N personas
5

C.lat/per (W)
68.44

C.sen/per (W)
57.63

174

Anexos

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

407.23

1.03

419.45

Instalaciones y otras cargas

407.23
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

342.20

1096.03

Cargas interiores totales

1438.23

3.0 %

0.85

Cargas internas totales

57.39
342.20

1970.29

Potencia trmica interna total

2312.49

Ventilacin
Caudal de ventilacin total (m/h)
183.3
Cargas de ventilacin

663.33

6.40

663.33

6.40

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 40.7 m

73.2 W/m

1005.53

POTENCIA TRMICA TOTAL :

669.73
1976.68
2982.2 W

175

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 118 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 21.6 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 20.3 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 13h (12 hora solar) del da 1 de Marzo


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.3

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

19.7

-41.61

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
1977.71

409.5

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

26.7

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

-21.01

23.8

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

28.6

2.08

97

22.4

-212.62

Forjado

16.3

0.50

373

22.5

-28.57

Hueco interior

1.7

2.20

23.8

-8.09
Total estructural

1665.81

205.32

172.89

Ocupantes
Actividad
Empleado de oficina

N personas
3

C.lat/per (W)
68.44

C.sen/per (W)
57.63

Iluminacin

176

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

266.54

1.08

287.86

Instalaciones y otras cargas

266.54
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

205.32

725.41

Cargas interiores totales

930.73

3.0 %
Cargas internas totales

0.92

71.74
205.32

2462.95

Potencia trmica interna total

2668.27

Ventilacin
Caudal de ventilacin total (m/h)
119.9

382.30

-167.05

382.30

-167.05

Potencia trmica de ventilacin total

215.25

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 26.7 m

108.2 W/m

587.62

POTENCIA TRMICA TOTAL :

2295.90
2883.5 W

177

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 119 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 16h (14 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.4

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

23.4

-14.20

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
478.92

292.3

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

17.3

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

3.40

26.5

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

18.9

2.08

97

24.2

-69.53

Forjado

16.9

0.50

373

23.3

-22.51

Hueco interior

1.7

2.20

25.8

-0.90
Total estructural

375.17

136.88

112.75

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
56.38

Iluminacin

178

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

173.41

0.97

168.20

Instalaciones y otras cargas

173.41
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

444.34

Cargas interiores totales

581.22

3.0 %
Cargas internas totales

0.86

24.59
136.88

844.10

Potencia trmica interna total

980.98

Ventilacin
Caudal de ventilacin total (m/h)
78.0

298.01

-12.13

298.01

-12.13

Potencia trmica de ventilacin total

285.88

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 17.3 m

73.1 W/m

434.89

POTENCIA TRMICA TOTAL :

831.97
1266.9 W

179

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 120 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 26.1 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 17h (15 hora solar) del da 22 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

7.4

0.58

225

Intermedio

20.1

-25.53

Fachada

26.5

0.58

225

Intermedio

20.7

-81.71

Fachada

9.8

0.58

225

Intermedio

24.6

-7.95

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
20.9

62.56

0.5

5.70

0.97

291.2

153.46

1.6

5.70

0.97

212.2

336.90

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

41.2

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

7.65

26.5

Cerramientos interiores
Tipo

Superficie (m)

Pared interior

U (W/(mK))

33.9

Peso (kg/m)

2.08

Teq. (C)

97

-88.69

24.7
Total estructural

356.69

342.20

288.14

Ocupantes
Actividad
Empleado de oficina

N personas
5

C.lat/per (W)
68.44

C.sen/per (W)
57.63

180

Anexos

Iluminacin
Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

411.53

1.03

423.88

Instalaciones y otras cargas

411.53
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

342.20

1104.76

Cargas interiores totales

1446.96

3.0 %

0.81

Cargas internas totales

43.84
342.20

1505.30

Potencia trmica interna total

1847.50

Ventilacin
Caudal de ventilacin total (m/h)
185.2
Cargas de ventilacin

670.34

6.46

670.34

6.46

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 41.2 m

61.3 W/m

1012.54

POTENCIA TRMICA TOTAL :

676.80
1511.76
2524.3 W

181

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 121 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.9 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 21.4 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 22 de Junio


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

7.3

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

21.5

-19.20

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.9

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
67.79

23.1

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

11.5

Peso (kg/m)

Color

0.36

843

U (W/(mK))

Peso (kg/m)

Teq. (C)

Intermedio

17.15

30.2

Cerramientos interiores
Tipo

Superficie (m)

Teq. (C)

Pared interior

17.3

2.08

97

25.4

Forjado

11.3

0.50

373

23.6

-23.27
-13.46
Total estructural

29.01

136.88

116.51

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

58.26

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
114.54

Coef. iluminacin
1.05

120.27

182

Anexos

Instalaciones y otras cargas

114.54
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

345.05

Cargas interiores totales

481.93

3.0 %

0.74

Cargas internas totales

11.22
136.88

385.28

Potencia trmica interna total

522.16

Ventilacin
Caudal de ventilacin total (m/h)
51.5

154.24

-1.47

154.24

-1.47

Potencia trmica de ventilacin total

152.76

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 11.5 m

58.9 W/m

291.12

POTENCIA TRMICA TOTAL :

383.81
674.9 W

183

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 122 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.5 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 22.0 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 1 de Septiembre


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.5

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

20.4

-30.98

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
30.29

19.2

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.4

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

7.53

27.7

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

16.5

2.08

97

25.2

-29.03

Forjado

11.9

0.50

373

23.4

-15.44

Hueco interior

3.3

2.20

25.8

-1.81
Total estructural

-39.44

136.88

116.51

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

184

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

123.98

1.05

130.18

Instalaciones y otras cargas

123.98
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

364.41

Cargas interiores totales

501.29

3.0 %
Cargas internas totales

0.71

9.75
136.88

334.72

Potencia trmica interna total

471.60

Ventilacin
Caudal de ventilacin total (m/h)
55.8

213.07

-8.67

213.07

-8.67

Potencia trmica de ventilacin total

204.39

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 12.4 m

54.5 W/m

349.95

POTENCIA TRMICA TOTAL :

326.05
676.0 W

185

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 123 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 25.9 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 21.4 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 18h (16 hora solar) del da 22 de Junio


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Teq. (C)

Fachada

8.8

0.58

225

Intermedio

26.5

2.61

Fachada

12.0

0.58

225

Intermedio

21.5

-31.50

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.0

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
92.69

23.1

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

17.9

Peso (kg/m)

0.36

843

Color

Teq. (C)

Intermedio

26.80

30.2

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Teq. (C)

Pared interior

23.1

2.08

97

25.4

-30.99

Forjado

14.9

0.50

373

23.6

-17.79
Total estructural

41.81

136.88

116.51

Ocupantes
Actividad
Empleado de oficina

N personas
2

C.lat/per (W)
68.44

C.sen/per (W)
58.26

Iluminacin

186

Anexos

Tipo

Potencia (W)

Fluorescente con reactancia

Coef. iluminacin

178.96

1.05

187.91

Instalaciones y otras cargas

178.96
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

477.12

Cargas interiores totales

614.00

3.0 %
Cargas internas totales

0.80

15.57
136.88

534.49

Potencia trmica interna total

671.37

Ventilacin
Caudal de ventilacin total (m/h)
80.5

240.98

-2.30

240.98

-2.30

Potencia trmica de ventilacin total

238.68

Cargas de ventilacin
Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 17.9 m

50.9 W/m

377.86

POTENCIA TRMICA TOTAL :

532.19
910.1 W

187

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 124 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 26.0 C

Temperatura exterior = 19.9 C

Humedad relativa interior = 50.0 %

Temperatura hmeda = 19.7 C

C.
C.
LATENTE(W) SENSIBLE(W)

Cargas de refrigeracin a las 10h (8 hora solar) del da 1 de Junio


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

10.8

Peso (kg/m)

0.58

Color

225

Teq. (C)

Intermedio

22.2

-24.18

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

Coef. radiacin solar

5.70

0.97

Ganancia (W/m)
607.21

382.3

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

11.4

Peso (kg/m)

0.36

Color

843

Teq. (C)

Intermedio

17.58

30.3

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

25.1

2.08

Hueco interior

1.7

2.20

Peso (kg/m)

Teq. (C)

97

22.3

-192.67

22.9

-11.33
Total estructural

396.61

136.88

111.50

Ocupantes
Actividad

N personas

Empleado de oficina

C.lat/per (W)

C.sen/per (W)

68.44

55.75

Iluminacin
Tipo
Fluorescente con reactancia

Potencia (W)
113.82

Coef. iluminacin
1.05

119.51

188

Anexos

Instalaciones y otras cargas

113.82
Cargas interiores

Cargas debidas a la propia instalacin


FACTOR CALOR SENSIBLE :

136.88

343.57

Cargas interiores totales

480.45

3.0 %

0.85

Cargas internas totales

22.21
136.88

762.39

Potencia trmica interna total

899.27

Ventilacin
Caudal de ventilacin total (m/h)
51.2
Cargas de ventilacin

160.96

-99.93

160.96

-99.93

Potencia trmica de ventilacin total


Potencia trmica
POTENCIA TRMICA POR SUPERFICIE 11.4 m

84.4 W/m

61.03

297.84

POTENCIA TRMICA TOTAL :

662.45
960.3 W

189

Anexos

2.2.2.2

Calefaccin

Planta baja

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 014 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.0

Peso (kg/m)

0.58

225

Color
Intermedio

126.89

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

546.23

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

29.1

Peso (kg/m)

0.27

1042

113.82

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

14.1

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

291.42
33.16
Total estructural

1111.51

Cargas interiores totales

190

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 55.58
Cargas internas totales

1167.09

Ventilacin
Caudal de ventilacin total (m/h)
130.9

822.43
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 29.1 m

68.4 W/m

POTENCIA TRMICA TOTAL :

822.43
1989.5 W

191

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 015 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

10.6

Peso (kg/m)

0.58

225

Color
Intermedio

122.17

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

546.89

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

28.4

Peso (kg/m)

0.27

1042

110.92

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

13.7

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

283.13
33.16
Total estructural

1096.27

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 54.81
Cargas internas totales

1151.08

192

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
127.6

801.52
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 28.4 m

68.9 W/m

POTENCIA TRMICA TOTAL :

801.52
1952.6 W

193

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 016 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.3

Peso (kg/m)

0.58

225

Color
Intermedio

130.26

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

545.66

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

29.6

Peso (kg/m)

0.27

1042

115.88

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

14.4

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

297.33
33.16
Total estructural

1122.30

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 56.11
Cargas internas totales

1178.41

194

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
133.3

837.36
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 29.6 m

68.0 W/m

POTENCIA TRMICA TOTAL :

837.36
2015.8 W

195

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 017 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

11.7

0.58

225

Intermedio

148.64

Fachada

10.6

0.58

225

Intermedio

123.03

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.6

524.22

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

28.2

Peso (kg/m)

0.27

1042

110.21

Cerramientos interiores
Tipo
Pared interior

Superficie (m)
10.2

U (W/(mK))
2.08

Peso (kg/m)
97

209.53
Total estructural

1115.64

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 55.78
Cargas internas totales

1171.42

196

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
126.8

796.35
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 28.2 m

69.8 W/m

POTENCIA TRMICA TOTAL :

796.35
1967.8 W

197

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 018 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

10.3

0.58

225

Intermedio

131.59

Fachada

7.9

0.58

225

Intermedio

90.97

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

340.19

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

27.9

Peso (kg/m)

0.27

1042

109.19

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

17.4

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

357.71
33.16
Total estructural

1062.81

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 53.14

198

Anexos

Cargas internas totales

1115.96

Ventilacin
Caudal de ventilacin total (m/h)
125.6

789.06
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 27.9 m

68.2 W/m

POTENCIA TRMICA TOTAL :

789.06
1905.0 W

199

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

REPROGRAFIA (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

13.2

Peso (kg/m)

0.58

225

Color
Intermedio

168.00

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

593.57

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

53.6

Peso (kg/m)

0.27

1042

209.60

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

57.7

2.08

97

1190.01

Forjado

27.7

0.37

373

102.29

Hueco interior

3.3

2.00

66.32
Total estructural

2329.79

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 116.49

200

Anexos

Cargas internas totales

2446.28

Ventilacin
Caudal de ventilacin total (m/h)
241.1

1514.62
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 53.6 m

73.9 W/m

POTENCIA TRMICA TOTAL :

1514.62
3960.9 W

201

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

GESTION (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

25.2

0.58

225

Intermedio

349.41

Fachada

50.6

0.58

225

Intermedio

643.14

Fachada

14.3

0.58

225

Intermedio

165.41

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

6.1

5.70

820.91

12.1

5.70

1506.34

1.5

5.70

169.18

Cubiertas
Tipo
Azotea

Superficie (m)

U (W/(mK))

130.1

0.30

Peso (kg/m)
585

Color
Intermedio

770.28

Forjados inferiores
Tipo
Solera

Superficie (m)

U (W/(mK))

188.5

0.27

Peso (kg/m)
1042

737.20

Cerramientos interiores

202

Anexos

Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

55.3

2.08

97

1139.02

Forjado

12.0

0.37

373

44.41

Hueco interior

3.3

2.00

66.32
Total estructural

6411.63

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 320.58
Cargas internas totales

6732.21

Ventilacin
Caudal de ventilacin total (m/h)
848.1

5327.23
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 188.5 m

64.0 W/m

POTENCIA TRMICA TOTAL :

5327.23
12059.4 W

203

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

ATENCION (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

19.1

0.58

225

Intermedio

243.48

Fachada

12.0

0.58

225

Intermedio

166.42

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

409.34

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

37.5

Peso (kg/m)

0.30

585

Color
Intermedio

222.11

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

38.0

Peso (kg/m)

0.27

1042

148.65

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

10.6

2.08

Hueco interior

4.1

2.00

Peso (kg/m)
97

217.94
80.39
Total estructural

1488.33

204

Anexos

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 74.42
Cargas internas totales

1562.74

Potencia trmica de ventilacin total

1074.20

Ventilacin
Caudal de ventilacin total (m/h)
171.0

POTENCIA TRMICA POR SUPERFICIE 38.0 m

1074.20

69.4 W/m

POTENCIA TRMICA TOTAL :

2636.9 W

205

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 011 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.1

Peso (kg/m)

0.58

225

Color
Intermedio

153.79

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.7

637.61

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

26.3

Peso (kg/m)

0.27

1042

102.85

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

14.1

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

290.97
33.16
Total estructural

1218.38

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 60.92
Cargas internas totales

1279.30

206

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
118.3

743.19
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 26.3 m

76.9 W/m

POTENCIA TRMICA TOTAL :

743.19
2022.5 W

207

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 009 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

225

Color
Intermedio

82.39

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

309.93

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

13.7

Peso (kg/m)

0.27

1042

53.57

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.6

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

135.03
33.16
Total estructural

614.08

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 30.70
Cargas internas totales

644.79

208

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
61.6

387.14
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 13.7 m

75.3 W/m

POTENCIA TRMICA TOTAL :

387.14
1031.9 W

209

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 008 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.3

Peso (kg/m)

0.58

225

Color
Intermedio

128.71

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

3.0

409.46

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

20.5

Peso (kg/m)

0.27

1042

80.11

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

22.6

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

465.50
33.16
Total estructural

1116.93

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 55.85
Cargas internas totales

1172.78

210

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
92.1

578.83
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 20.5 m

85.5 W/m

POTENCIA TRMICA TOTAL :

578.83
1751.6 W

211

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA DE JUNTAS (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

34.7

0.58

225

Intermedio

441.76

Fachada

24.0

0.58

225

Intermedio

305.75

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

9.0

1119.60

5.70

Cubiertas
Tipo
Azotea

Superficie (m)

U (W/(mK))

71.5

0.30

Peso (kg/m)
585

Color
Intermedio

423.31

Forjados inferiores
Tipo
Solera

Superficie (m)

U (W/(mK))

76.1

Peso (kg/m)

0.27

1042

U (W/(mK))

Peso (kg/m)

297.87

Cerramientos interiores
Tipo
Forjado

Superficie (m)
1.4

0.37

373

5.09
Total estructural

2593.38

Cargas interiores totales

212

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 129.67
Cargas internas totales

2723.05

Ventilacin
Caudal de ventilacin total (m/h)
1142.2

7174.68
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 76.1 m

130.0 W/m

POTENCIA TRMICA TOTAL :

7174.68
9897.7 W

213

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA HONOR (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

36.0

0.58

225

Intermedio

458.52

Fachada

4.7

0.58

225

Intermedio

65.11

Fachada

6.5

0.58

225

Intermedio

82.56

Fachada

14.0

0.58

225

Intermedio

162.45

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)


1.4

U (W/(mK))
5.70

190.38

2.5

5.70

282.29

Puertas exteriores
Nm. puertas

Tipo

Opaca

Orientacin

Superficie (m)

U (W/(mK))

1.7

2.00

79.58

Cubiertas
Tipo
Azotea

Superficie (m)
13.4

U (W/(mK))
0.30

Peso (kg/m)
585

Color
Intermedio

79.11

Forjados inferiores

214

Anexos

Tipo

Superficie (m)

Solera

U (W/(mK))

94.9

Peso (kg/m)

0.27

1042

371.19

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

10.4

2.08

97

215.04

Forjado

23.2

0.37

373

85.46

Hueco interior

3.0

2.00

60.29
Total estructural

2131.98

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 106.60
Cargas internas totales

2238.58

Potencia trmica de ventilacin total

8940.70

Ventilacin
Caudal de ventilacin total (m/h)
1423.3

POTENCIA TRMICA POR SUPERFICIE 94.9 m

8940.70

117.8 W/m

POTENCIA TRMICA TOTAL :

11179.3 W

215

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA AUDIOVISUAL (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

29.0

Peso (kg/m)

0.58

225

Color
Intermedio

335.09

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

7.3

818.80

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

95.1

Peso (kg/m)

0.30

585

Color
Intermedio

563.09

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

95.1

Peso (kg/m)

0.27

1042

372.00

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.0

2.08

Hueco interior

1.7

2.00

Peso (kg/m)
97

123.16
33.16
Total estructural

2245.29

Cargas interiores totales

216

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 112.26
Cargas internas totales

2357.56

Ventilacin
Caudal de ventilacin total (m/h)
1426.5

8960.58
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 95.1 m

119.0 W/m

POTENCIA TRMICA TOTAL :

8960.58
11318.1 W

217

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

SALA DE ESPERA (Salas de reuniones)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

4.0

Peso (kg/m)

0.58

225

Color
Intermedio

46.70

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.1

118.97

5.70

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

22.5

Peso (kg/m)

0.27

1042

88.04

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

20.9

2.08

97

430.50

373

44.38

Forjado

8.9

0.50

Hueco interior

3.3

2.00

66.32

Hueco interior

3.0

2.00

60.29
Total estructural

855.19

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 42.76

218

Anexos

Cargas internas totales

897.95

Ventilacin
Caudal de ventilacin total (m/h)
337.6

2120.65
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 22.5 m

134.1 W/m

POTENCIA TRMICA TOTAL :

2120.65
3018.6 W

219

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

CAFETERIA (Restauracin)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

43.8

0.58

225

Intermedio

557.55

Fachada

28.3

0.58

225

Intermedio

392.95

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

10.9

5.70

1475.23

Cubiertas
Tipo
Azotea

Superficie (m)

U (W/(mK))

265.0

0.30

Peso (kg/m)
585

Color
Intermedio

1568.99

Forjados inferiores
Tipo
Solera

Superficie (m)

U (W/(mK))

265.0

0.27

Peso (kg/m)
1042

1036.52

Cerramientos interiores

220

Anexos

Tipo

Superficie (m)

U (W/(mK))

Pared interior

49.8

2.08

Peso (kg/m)
97

1026.14

Hueco interior

3.3

2.00

66.32

Hueco interior

3.0

2.00

60.29

Hueco interior

1.7

2.00

32.96
Total estructural

6216.96

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 310.85
Cargas internas totales

6527.81

Potencia trmica de ventilacin total

49934.48

Ventilacin
Caudal de ventilacin total (m/h)
7949.3

POTENCIA TRMICA POR SUPERFICIE 265.0 m

49934.48

213.1 W/m

POTENCIA TRMICA TOTAL :

56462.3 W

221

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

COMEDOR (Restauracin)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.8

Peso (kg/m)

0.58

225

Color
Intermedio

150.46

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

597.09

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

35.7

Peso (kg/m)

0.30

585

Color
Intermedio

211.47

Forjados inferiores
Tipo

Superficie (m)

Solera

U (W/(mK))

36.1

Peso (kg/m)

0.27

1042

141.05

Cerramientos interiores
Tipo
Pared interior

Superficie (m)
32.8

U (W/(mK))
2.08

Peso (kg/m)
97

675.70
Total estructural

1775.77

Cargas interiores totales

222

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 88.79
Cargas internas totales

1864.56

Ventilacin
Caudal de ventilacin total (m/h)
1081.7

6795.08
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 36.1 m

240.2 W/m

POTENCIA TRMICA TOTAL :

6795.08
8659.6 W

223

Anexos

Planta 1

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 101 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.0

Peso (kg/m)

0.58

225

Color
Intermedio

75.79

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

198.08

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

16.1

Peso (kg/m)

0.37

843

Color
Intermedio

116.54

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

28.8

2.08

97

593.60

Forjado

15.8

0.47

373

73.25

Hueco interior

2.9

2.20

64.11
Total estructural

1121.36

Cargas interiores totales

224

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 56.07
Cargas internas totales

1177.43

Ventilacin
Caudal de ventilacin total (m/h)
72.3

454.19
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 16.1 m

101.5 W/m

POTENCIA TRMICA TOTAL :

454.19
1631.6 W

225

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 102 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.6

Peso (kg/m)

0.58

225

Color
Intermedio

91.52

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

310.93

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

15.2

Peso (kg/m)

0.37

843

Color
Intermedio

110.16

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

12.1

2.08

97

248.68

Forjado

5.2

0.47

373

24.11

Hueco interior

1.7

2.20

36.48
Total estructural

821.87

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 41.09

226

Anexos

Cargas internas totales

862.97

Ventilacin
Caudal de ventilacin total (m/h)
68.4

429.37
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 15.2 m

85.1 W/m

POTENCIA TRMICA TOTAL :

429.37
1292.3 W

227

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 103/104 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.6

Peso (kg/m)

0.58

225

Color
Intermedio

160.87

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.6

622.51

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

27.7

Peso (kg/m)

0.37

843

Color
Intermedio

200.62

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

12.8

2.08

97

Forjado

1.3

0.47

373

Hueco interior

3.3

2.20

264.67
5.94
72.95
Total estructural

1327.56

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 66.38

228

Anexos

Cargas internas totales

1393.94

Ventilacin
Caudal de ventilacin total (m/h)
124.5

781.83
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 27.7 m

78.7 W/m

POTENCIA TRMICA TOTAL :

781.83
2175.8 W

229

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 105 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

225

Color
Intermedio

81.28

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

325.41

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

14.1

Peso (kg/m)

0.37

843

Color
Intermedio

102.36

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

6.6

2.08

97

Forjado

0.7

0.47

373

Hueco interior

1.7

2.20

135.74
3.03
36.48
Total estructural

684.30

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 34.22

230

Anexos

Cargas internas totales

718.52

Ventilacin
Caudal de ventilacin total (m/h)
63.5

398.91
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 14.1 m

79.2 W/m

POTENCIA TRMICA TOTAL :

398.91
1117.4 W

231

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 106 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.5

Peso (kg/m)

0.58

225

Color
Intermedio

76.07

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

319.37

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.4

Peso (kg/m)

0.37

843

Color
Intermedio

97.15

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

6.2

2.08

97

Forjado

0.6

0.47

373

Hueco interior

1.7

2.20

127.09
2.88
36.48
Total estructural

659.03

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 32.95

232

Anexos

Cargas internas totales

691.99

Ventilacin
Caudal de ventilacin total (m/h)
60.3

378.62
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 13.4 m

79.9 W/m

POTENCIA TRMICA TOTAL :

378.62
1070.6 W

233

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 107 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

6.7

Peso (kg/m)

0.58

225

Color
Intermedio

92.39

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

317.44

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

15.4

Peso (kg/m)

0.37

843

Color
Intermedio

111.53

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

7.3

2.08

97

Forjado

0.6

0.47

373

Hueco interior

1.7

2.20

151.02
2.83
36.48
Total estructural

711.68

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 35.58

234

Anexos

Cargas internas totales

747.26

Ventilacin
Caudal de ventilacin total (m/h)
69.2

434.70
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 15.4 m

76.9 W/m

POTENCIA TRMICA TOTAL :

434.70
1182.0 W

235

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 108 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.4

Peso (kg/m)

0.58

225

Color
Intermedio

74.26

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.2

298.21

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.9

Peso (kg/m)

0.37

843

Color
Intermedio

93.60

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

17.8

2.08

97

366.52

Hueco interior

1.7

2.20

36.48

Hueco interior

1.5

5.70

84.19
Total estructural

953.25

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 47.66

236

Anexos

Cargas internas totales

1000.91

Ventilacin
Caudal de ventilacin total (m/h)
58.1

364.76
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 12.9 m

105.8 W/m

POTENCIA TRMICA TOTAL :

364.76
1365.7 W

237

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 109 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

12.3

0.58

225

Intermedio

142.59

Fachada

13.2

0.58

225

Intermedio

167.33

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

538.59

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

28.7

Peso (kg/m)

0.37

843

Color
Intermedio

208.12

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

15.4

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

318.00
36.48
Total estructural

1411.11

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 70.56

238

Anexos

Cargas internas totales

1481.66

Ventilacin
Caudal de ventilacin total (m/h)
129.1

811.10
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 28.7 m

79.9 W/m

POTENCIA TRMICA TOTAL :

811.10
2292.8 W

239

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 110 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.1

Peso (kg/m)

0.58

225

Color
Intermedio

127.81

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

538.10

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

26.5

Peso (kg/m)

0.37

843

Color
Intermedio

192.52

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

11.9

2.08

97

246.01

Hueco interior

1.7

2.20

36.48

Hueco interior

2.2

5.70

124.74
Total estructural

1265.66

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 63.28

240

Anexos

Cargas internas totales

1328.94

Ventilacin
Caudal de ventilacin total (m/h)
119.4

750.30
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 26.5 m

78.3 W/m

POTENCIA TRMICA TOTAL :

750.30
2079.2 W

241

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 111 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.9

Peso (kg/m)

0.58

225

Color
Intermedio

68.05

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

268.07

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.9

Peso (kg/m)

0.37

843

Color
Intermedio

100.52

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.6

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

135.74
36.48
Total estructural

608.86

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 30.44
Cargas internas totales

639.30

242

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
62.4

391.75
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 13.9 m

74.4 W/m

POTENCIA TRMICA TOTAL :

391.75
1031.1 W

243

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 112 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.7

Peso (kg/m)

0.58

225

Color
Intermedio

65.99

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.4

272.41

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

13.6

Peso (kg/m)

0.37

843

Color
Intermedio

98.81

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.4

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

132.86
36.48
Total estructural

606.55

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 30.33
Cargas internas totales

636.88

244

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
61.3

385.11
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 13.6 m

75.0 W/m

POTENCIA TRMICA TOTAL :

385.11
1022.0 W

245

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 113 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.7

Peso (kg/m)

0.58

225

Color
Intermedio

134.80

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.7

533.08

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

27.5

Peso (kg/m)

0.37

843

Color
Intermedio

199.33

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

13.0

2.08

Hueco interior

3.3

2.20

Peso (kg/m)
97

268.60
72.95
Total estructural

1208.76

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 60.44
Cargas internas totales

1269.20

246

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
123.7

776.86
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 27.5 m

74.4 W/m

POTENCIA TRMICA TOTAL :

776.86
2046.1 W

247

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 115 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

5.6

Peso (kg/m)

0.58

225

Color
Intermedio

64.45

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

255.85

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.4

Peso (kg/m)

0.37

843

Color
Intermedio

90.06

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

6.2

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

127.09
36.48
Total estructural

573.91

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 28.70
Cargas internas totales

602.61

248

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
59.2

371.83
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 13.2 m

74.1 W/m

POTENCIA TRMICA TOTAL :

371.83
974.4 W

249

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 116 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

6.1

0.58

225

Intermedio

70.75

Fachada

12.2

0.58

225

Intermedio

155.30

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.3

260.69

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

14.2

Peso (kg/m)

0.37

843

Color
Intermedio

102.78

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

7.0

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

144.40
36.48
Total estructural

770.40

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 38.52

250

Anexos

Cargas internas totales

808.92

Ventilacin
Caudal de ventilacin total (m/h)
63.8

400.58
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 14.2 m

85.3 W/m

POTENCIA TRMICA TOTAL :

400.58
1209.5 W

251

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 117 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

17.2

0.58

225

Intermedio

219.43

Fachada

15.4

0.58

225

Intermedio

177.94

Fachada

12.4

0.58

225

Intermedio

172.34

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

5.70

194.49

1.6

5.70

178.44

4.5

5.70

616.07

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

40.7

Peso (kg/m)

0.37

843

Color
Intermedio

295.36

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

15.3

2.08

Hueco interior

2.8

2.20

Peso (kg/m)
97

314.97
61.90
Total estructural

2230.93

252

Anexos

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 111.55
Cargas internas totales

2342.48

Potencia trmica de ventilacin total

1151.14

Ventilacin
Caudal de ventilacin total (m/h)
183.3

POTENCIA TRMICA POR SUPERFICIE 40.7 m

1151.14

85.8 W/m

POTENCIA TRMICA TOTAL :

3493.6 W

253

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 118 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

11.3

Peso (kg/m)

0.58

225

Color
Intermedio

130.33

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.8

545.10

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

26.7

Peso (kg/m)

0.37

843

Color
Intermedio

193.31

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

28.6

2.08

97

590.34

Forjado

16.3

0.47

373

75.70

Hueco interior

1.7

2.20

36.48
Total estructural

1571.25

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 78.56

254

Anexos

Cargas internas totales

1649.81

Ventilacin
Caudal de ventilacin total (m/h)
119.9

753.44
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 26.7 m

90.2 W/m

POTENCIA TRMICA TOTAL :

753.44
2403.2 W

255

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 119 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.4

Peso (kg/m)

0.58

225

Color
Intermedio

108.38

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

184.89

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

17.3

Peso (kg/m)

0.37

843

Color
Intermedio

125.76

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

18.9

2.08

97

390.47

373

78.40

Forjado

16.9

0.47

Hueco interior

1.7

2.20

36.48

Hueco interior

1.3

2.20

27.63

Hueco interior

1.5

2.20

32.05
Total estructural

984.06

Cargas interiores totales

256

Anexos

Cargas debidas a la intermitencia de uso

5.0 % 49.20
Cargas internas totales

1033.27

Ventilacin
Caudal de ventilacin total (m/h)
78.0

490.17
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 17.3 m

87.9 W/m

POTENCIA TRMICA TOTAL :

490.17
1523.4 W

257

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 120 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

7.4

0.58

225

Intermedio

102.57

Fachada

26.5

0.58

225

Intermedio

337.73

Fachada

9.8

0.58

225

Intermedio

113.10

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))
405.84

3.0

5.70

0.5

5.70

65.43

5.70

179.19

1.6

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

41.2

Peso (kg/m)

0.37

843

Color
Intermedio

298.47

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

33.9

2.08

97

699.41

Hueco interior

1.3

2.20

27.63

Hueco interior

1.7

2.20

36.48

258

Anexos

Total estructural

2265.86

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 113.29
Cargas internas totales

2379.15

Ventilacin
Caudal de ventilacin total (m/h)
185.2

1163.29
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 41.2 m

86.1 W/m

POTENCIA TRMICA TOTAL :

1163.29
3542.4 W

259

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 121 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

7.3

Peso (kg/m)

0.58

225

Color
Intermedio

101.16

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

2.9

396.89

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

11.5

Peso (kg/m)

0.37

843

Color
Intermedio

83.07

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

17.3

2.08

97

357.27

Forjado

11.3

0.47

373

52.24

Hueco interior

1.7

2.20

36.48
Total estructural

1027.10

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 51.36

260

Anexos

Cargas internas totales

1078.46

Ventilacin
Caudal de ventilacin total (m/h)
51.5

323.78
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 11.5 m

122.4 W/m

POTENCIA TRMICA TOTAL :

323.78
1402.2 W

261

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 122 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

9.5

Peso (kg/m)

0.58

225

Color
Intermedio

131.67

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

213.15

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

12.4

Peso (kg/m)

0.37

843

Color
Intermedio

89.92

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

16.5

2.08

97

340.11

Forjado

11.9

0.47

373

55.30

Hueco interior

3.3

2.20

72.95
Total estructural

903.11

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 45.16

262

Anexos

Cargas internas totales

948.26

Ventilacin
Caudal de ventilacin total (m/h)
55.8

350.46
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 12.4 m

104.8 W/m

POTENCIA TRMICA TOTAL :

350.46
1298.7 W

263

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 123 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Superficie (m)

U (W/(mK))

Peso (kg/m)

Color

Fachada

8.8

0.58

225

Intermedio

111.77

Fachada

12.0

0.58

225

Intermedio

165.99

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

4.0

542.65

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

17.9

Peso (kg/m)

0.37

843

Color
Intermedio

129.80

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Peso (kg/m)

Pared interior

23.1

2.08

97

475.76

Forjado

14.9

0.47

373

69.05

Hueco interior

1.7

2.20

36.48
Total estructural

1531.50

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 76.57

264

Anexos

Cargas internas totales

1608.07

Ventilacin
Caudal de ventilacin total (m/h)
80.5

505.88
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 17.9 m

118.1 W/m

POTENCIA TRMICA TOTAL :

505.88
2114.0 W

265

Anexos

CARGA MXIMA (RECINTO AISLADO)


Recinto

Conjunto de recintos

OFICINA 124 (Oficinas)

INEF

Condiciones de proyecto
Internas

Externas

Temperatura interior = 21.0 C

Temperatura exterior = 1.2 C

Humedad relativa interior = 50.0 %

Humedad relativa exterior = 90.0 %

C.
SENSIBLE(W
)

Cargas trmicas de calefaccin


Cerramientos exteriores
Tipo

Orientacin

Fachada

Superficie (m)

U (W/(mK))

10.8

Peso (kg/m)

0.58

225

Color
Intermedio

137.82

Ventanas exteriores
Nm. ventanas

Orientacin

Superficie total (m)

U (W/(mK))

1.6

197.18

5.70

Cubiertas
Tipo

Superficie (m)

Azotea

U (W/(mK))

11.4

Peso (kg/m)

0.37

843

Color
Intermedio

82.55

Cerramientos interiores
Tipo

Superficie (m)

U (W/(mK))

Pared interior

25.1

2.08

Hueco interior

1.7

2.20

Peso (kg/m)
97

517.68
36.48
Total estructural

971.71

Cargas interiores totales

Cargas debidas a la intermitencia de uso

5.0 % 48.59
Cargas internas totales

1020.29

266

Anexos

Ventilacin
Caudal de ventilacin total (m/h)
51.2

321.73
Potencia trmica de ventilacin total

POTENCIA TRMICA POR SUPERFICIE 11.4 m

117.9 W/m

POTENCIA TRMICA TOTAL :

321.73
1342.0 W

267

Anexos

2.2.3

Resumen de los resultados de clculo de los recintos

Refrigeracin
Conjunto: INEF
Subtotales
Recinto

Planta

Carga interna

Ventilacin

Potencia trmica

Estructural(
W)

Sensible
interior(W)

Total
interior(W)

Sensible(
W)

Caudal(m Sensible(
Total(W)
/h)
W)

Carga
total(W)

Por
superficie(W/

Sensible(
W)

Total(W)

OFICINA 014

Planta baja

1829.76

776.18

981.50

2684.12

2889.44

130.93

-182.35

234.96

107.39

2501.77

3124.39

OFICINA 015

Planta baja

1839.78

760.79

966.11

2678.59

2883.91

127.60

-177.71

228.98

109.78

2500.88

3112.90

OFICINA 016

Planta baja

1827.98

787.16

992.48

2693.60

2898.92

133.30

-185.66

239.22

105.94

2507.94

3138.14

OFICINA 017

Planta baja

1740.49

756.98

962.30

2572.40

2777.72

126.77

-176.56

227.51

106.67

2395.83

3005.22
2243.91

OFICINA 018

Planta baja

1008.74

751.62

956.94

1813.17

2018.49

125.61

-174.95

225.42

80.39

1638.22

REPROGRAFIA

Planta baja

1334.07

1429.17

1839.81

2846.13

3256.77

241.12

-470.45

287.31

66.14

2375.68

3544.08

GESTION

Planta baja

4874.02

4910.75

6211.11

10078.31

11378.67

848.07

-131.84

3106.92

76.86

9946.48

14485.59

ATENCION

Planta baja

-32.41

999.53

1273.29

996.13

1269.89

171.01

-26.58

626.49

49.90

969.54

1896.38

OFICINA 011

Planta baja

29.50

704.34

909.66

755.86

961.18

118.31

-18.39

433.44

53.04

737.46

1394.62

OFICINA 009

Planta baja

13.09

391.01

527.89

416.22

553.10

61.63

-9.58

225.79

56.87

406.64

778.89

OFICINA 008

Planta baja

-11.88

585.15

790.47

590.47

795.79

92.15

-14.32

337.58

55.35

576.14

1133.37

SALA DE JUNTAS

Planta baja

3744.84

2967.63

4023.23

6913.84

7969.44

1142.17

-322.50

3858.32

155.33

6591.35

11827.77

SALA HONOR

Planta baja

609.85

3482.51

4781.71

4215.14

5514.34

1423.31

-221.26

5214.36

113.07

3993.88

10728.70

SALA AUDIOVISUAL

Planta baja

2122.43

3486.67

4785.87

5777.37

7076.57

1426.48

-221.75

5225.96

129.37

5555.62

12302.53

SALA DE ESPERA

Planta baja

191.69

846.68

1171.48

1069.52

1394.32

337.60

-52.48

1236.80

116.91

1017.04

2631.12

CAFETERIA

Planta baja

127.47

12267.73

19346.14

12767.06

19845.47

7949.29

-1235.75

29122.59

184.80

11531.31

48968.06

COMEDOR

Planta baja

1893.86

1718.09

2717.87

3720.31

4720.09

1081.74

-168.16

3963.00

240.81

3552.15

8683.09

OFICINA 101

Planta 1

362.78

439.64

576.52

826.49

963.37

72.30

-141.07

86.16

65.32

685.41

1049.52

OFICINA 102

Planta 1

3.01

421.63

558.51

437.38

574.26

68.35

-10.63

250.42

54.29

426.75

824.68

OFICINA 103/104

Planta 1

41.35

732.37

937.69

796.93

1002.25

124.46

-19.35

455.97

52.72

777.58

1458.22

OFICINA 105

Planta 1

23.20

399.54

536.42

435.42

572.30

63.50

-9.87

232.65

57.04

425.55

804.95

OFICINA 106

Planta 1

23.87

384.83

521.71

420.96

557.84

60.27

-9.37

220.82

58.13

411.59

778.66

OFICINA 107

Planta 1

18.92

425.50

562.38

457.75

594.63

69.20

-10.76

253.52

55.15

446.99

848.15

OFICINA 108

Planta 1

-1.52

374.78

511.66

384.45

521.33

58.07

-9.03

212.74

56.89

375.43

734.07

OFICINA 109

Planta 1

1720.44

767.84

973.16

2562.92

2768.24

129.12

-179.83

231.72

104.55

2383.09

2999.97

268

Anexos

OFICINA 110

Planta 1

1769.84

723.10

928.42

2567.73

2773.05

119.44

-166.36

214.35

112.55

2401.38

2987.41

OFICINA 111

Planta 1

884.73

402.27

539.15

1325.61

1462.49

62.36

-86.86

111.92

113.60

1238.75

1574.40

OFICINA 112

Planta 1

902.65

397.38

534.26

1339.03

1475.91

61.31

-85.39

110.02

116.41

1253.65

1585.94

OFICINA 113

Planta 1

1759.91

742.65

947.97

2577.64

2782.96

123.67

-172.24

221.94

109.34

2405.39

3004.90

OFICINA 115

Planta 1

844.72

387.61

524.49

1269.30

1406.18

59.19

-82.44

106.23

114.98

1186.86

1512.41

OFICINA 116

Planta 1

801.95

408.76

545.64

1247.03

1383.91

63.77

-88.82

114.44

105.73

1158.22

1498.35

OFICINA 117

Planta 1

816.87

1096.03

1438.23

1970.29

2312.49

183.25

6.40

669.73

73.23

1976.68

2982.22

OFICINA 118

Planta 1

1665.81

725.41

930.73

2462.95

2668.27

119.94

-167.05

215.25

108.18

2295.90

2883.52

OFICINA 119

Planta 1

375.17

444.34

581.22

844.10

980.98

78.03

-12.13

285.88

73.06

831.97

1266.85

OFICINA 120

Planta 1

356.69

1104.76

1446.96

1505.30

1847.50

185.19

6.46

676.80

61.34

1511.76

2524.29

OFICINA 121

Planta 1

29.01

345.05

481.93

385.28

522.16

51.54

-1.47

152.76

58.92

383.81

674.93

OFICINA 122

Planta 1

-39.44

364.41

501.29

334.72

471.60

55.79

-8.67

204.39

54.52

326.05

675.99

OFICINA 123

Planta 1

41.81

477.12

614.00

534.49

671.37

80.53

-2.30

238.68

50.85

532.19

910.06

OFICINA 124

Planta 1

396.61

343.57

480.45

762.39

899.27

51.22

-99.93

61.03

84.37

662.45

960.29

Total

17477.6
Carga total simultnea

156057.7

Calefaccin
Conjunto: INEF
Planta

Carga interna
sensible(W)

OFICINA 014

Planta baja

OFICINA 015
OFICINA 016

Recinto

Ventilacin

Potencia

Caudal(m
/h)

Carga
total(W)

Por
superficie(W/

Total(W)

1167.09

130.93

822.43

68.38

1989.51

Planta baja

1151.08

127.60

801.52

68.86

1952.60

Planta baja

1178.41

133.30

837.36

68.05

2015.77

OFICINA 017

Planta baja

1171.42

126.77

796.35

69.85

1967.77

OFICINA 018

Planta baja

1115.96

125.61

789.06

68.25

1905.01

REPROGRAFIA

Planta baja

2446.28

241.12

1514.62

73.92

3960.90

GESTION

Planta baja

6732.21

848.07

5327.23

63.99

12059.44

ATENCION

Planta baja

1562.74

171.01

1074.20

69.39

2636.95

OFICINA 011

Planta baja

1279.30

118.31

743.19

76.93

2022.49

OFICINA 009

Planta baja

644.79

61.63

387.14

75.35

1031.93

269

Anexos

OFICINA 008

Planta baja

1172.78

92.15

578.83

85.54

1751.61

SALA DE JUNTAS

Planta baja

2723.05

1142.17

7174.68

129.99

9897.73

SALA HONOR

Planta baja

2238.58

1423.31

8940.70

117.82

11179.27

SALA AUDIOVISUAL Planta baja

2357.56

1426.48

8960.58

119.02

11318.14

SALA DE ESPERA

Planta baja

897.95

337.60

2120.65

134.12

3018.60

CAFETERIA

Planta baja

6527.81

7949.29

49934.48

213.08

56462.29

COMEDOR

Planta baja

1864.56

1081.74

6795.08

240.16

8659.65

OFICINA 101

Planta 1

1177.43

72.30

454.19

101.55

1631.62

OFICINA 102

Planta 1

862.97

68.35

429.37

85.08

1292.34

OFICINA 103/104

Planta 1

1393.94

124.46

781.83

78.67

2175.77

OFICINA 105

Planta 1

718.52

63.50

398.91

79.18

1117.42

OFICINA 106

Planta 1

691.99

60.27

378.62

79.93

1070.61

OFICINA 107

Planta 1

747.26

69.20

434.70

76.86

1181.96

OFICINA 108

Planta 1

1000.91

58.07

364.76

105.83

1365.68

OFICINA 109

Planta 1

1481.66

129.12

811.10

79.90

2292.76

OFICINA 110

Planta 1

1328.94

119.44

750.30

78.33

2079.24

OFICINA 111

Planta 1

639.30

62.36

391.75

74.40

1031.05

OFICINA 112

Planta 1

636.88

61.31

385.11

75.01

1021.99

OFICINA 113

Planta 1

1269.20

123.67

776.86

74.45

2046.07

OFICINA 115

Planta 1

602.61

59.19

371.83

74.08

974.44

OFICINA 116

Planta 1

808.92

63.77

400.58

85.35

1209.50

OFICINA 117

Planta 1

2342.48

183.25

1151.14

85.79

3493.62

OFICINA 118

Planta 1

1649.81

119.94

753.44

90.16

2403.25

OFICINA 119

Planta 1

1033.27

78.03

490.17

87.85

1523.44

OFICINA 120

Planta 1

2379.15

185.19

1163.29

86.08

3542.44

OFICINA 121

Planta 1

1078.46

51.54

323.78

122.42

1402.23

OFICINA 122

Planta 1

948.26

55.79

350.46

104.75

1298.72

OFICINA 123

Planta 1

1608.07

80.53

505.88

118.12

2113.95

OFICINA 124

Planta 1

1020.29

51.22

321.73

117.91

1342.02

Total 17477.6
Carga total simultnea 171439.8

270

Anexos

2.2.4

Resumen de los resultados para conjuntos de recintos


Refrigeracin
Conjunto
INEF

Potencia por
superficie(W/m)

Potencia
total(W)

70.5

156057.7

Calefaccin
Conjunto
INEF

Potencia por
superficie(W/m)

Potencia
total(W)

77.4

171439.8

271

Anexos

2.3

Clculo de la instalacin

2.3.1

Sistemas de conduccin de aire. Conductos

Tramo
Inicio
A1-Planta baja
A2-Planta baja
A2-Planta baja
A2-Planta baja
A2-Planta baja
N1-Planta baja
A10-Planta baja
N3-Planta baja
N3-Planta baja
A9-Planta baja
N5-Planta baja
N5-Planta baja
A8-Planta baja
N7-Planta baja
N7-Planta baja
A7-Planta baja
N9-Planta baja
A6-Planta baja
A6-Planta baja
A3-Planta baja
A4-Planta baja
A4-Planta baja
A5-Planta baja
A5-Planta baja
A13-Planta baja
A14-Planta baja
A14-Planta baja
A14-Planta baja
A14-Planta baja
A14-Planta baja
A14-Planta baja
A15-Planta baja
A16-Planta baja
A17-Planta baja
A17-Planta baja
A18-Planta baja
A18-Planta baja
A21-Planta baja
A22-Planta baja
A22-Planta baja
A22-Planta baja

Final
N9-Planta baja
A11-Planta baja
A1-Planta baja
N7-Planta baja
A12-Planta baja
A10-Planta baja
A10-Planta baja
N1-Planta baja
A9-Planta baja
A9-Planta baja
N3-Planta baja
A8-Planta baja
A8-Planta baja
N5-Planta baja
A7-Planta baja
A7-Planta baja
A6-Planta baja
A6-Planta baja
A5-Planta baja
A3-Planta baja
A4-Planta baja
A3-Planta baja
A5-Planta baja
A4-Planta baja
A18-Planta baja
A19-Planta baja
A13-Planta baja
A15-Planta baja
A15-Planta baja
A15-Planta baja
A20-Planta baja
A15-Planta baja
A16-Planta baja
A17-Planta baja
A16-Planta baja
A18-Planta baja
A17-Planta baja
N8-Planta baja
N24-Planta baja
A21-Planta baja
N17-Planta baja

Conductos
Q
wxh
V

L
P1
P
D
(m/h)
(mm) (m/s) (mm) (m) (Pa) (Pa)
(Pa)
3600.0 1200x200
5.3 489.8 2.66
-66.77
3600.0 1200x200
5.3 489.8 1.53 5.96 18.51
3600.0 1200x200
5.3 489.8 1.53
26.81
3600.0 1200x200
5.3 489.8 7.61
28.62
3600.0 1200x200
5.3 489.8 3.37 8.46 20.13
801.4 500x200
2.5 337.0 0.89
38.28
801.4 500x200
2.5 337.0 0.33 15.32 54.53
801.4 500x200
2.5 337.0 8.89
37.24
801.4 500x200
2.5 337.0 0.84
35.04
801.4 500x200
2.5 337.0 0.33 15.32 51.29
3.24
34.40
1602.7 600x200
4.2 365.3 3.45
998.6 800x200
2.1 413.5 0.74
31.73
998.6 800x200
2.1 413.5 0.33 13.38 45.79
8.74
2601.4 800x200
5.4 413.5 5.90
32.13
998.6 800x200
2.1 413.5 0.84
28.48
998.6 800x200
2.1 413.5 0.33 13.38 42.54 11.99
3600.0 1200x200
5.3 489.8 1.43
-63.45
998.6 800x200
2.1 413.5 0.30 19.39 -37.98 82.53
2601.4 800x200
5.4 413.5 2.90
-55.29
801.4 500x200
2.5 337.0 0.30 17.98 -28.63 73.19
801.4 500x200
2.5 337.0 0.30 17.98 -31.12 75.68
801.4 500x200
2.5 337.0 7.55
-47.53
998.6 800x200
2.1 413.5 0.30 19.39 -29.48 74.04
1602.7 600x200
4.2 365.3 4.75
-52.77
2520.0 800x200
5.2 413.5 10.85
-22.26
2520.0 400x400
4.7 437.3 1.25 2.92 7.68
2520.0 400x400
4.7 437.3 1.34
8.33
2520.0 800x200
5.2 413.5 14.84 16.84 47.32
4.43
1680.0 600x200
4.5 365.3 4.23 16.84 49.66
2.09
840.0 600x200
2.2 365.3 5.87
34.18
2520.0 400x400
4.7 437.3 2.86 4.15 8.01
840.0 600x200
2.2 365.3 0.33 16.84 51.75
840.0 600x200
2.2 365.3 0.30 8.65 -4.07 43.28
840.0 600x200
2.2 365.3 0.30 8.65 -2.46 41.67
840.0 600x200
2.2 365.3 4.07
-13.45
840.0 600x200
2.2 365.3 0.30 8.65 -9.19 48.40
1680.0 600x200
4.5 365.3 4.82
-14.78
3600.0 500x400
5.3 488.1 2.32
-7.26
3600.0 1200x200
5.3 489.8 11.28
10.29
3600.0 500x400
5.3 488.1 1.49
86.41
3600.0 500x400
5.3 488.1 9.08
29.12
272

Anexos

A22-Planta baja
A28-Planta baja
N8-Planta baja
N8-Planta baja
N8-Planta baja
N10-Planta baja
A32-Planta baja
A31-Planta baja
A31-Planta baja
A29-Planta baja
A30-Planta baja
A30-Planta baja
A25-Planta baja
A25-Planta baja
A27-Planta baja
A27-Planta baja
A27-Planta baja
N16-Planta baja
N16-Planta baja
A26-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A33-Planta baja
A35-Planta baja
N12-Planta baja
N13-Planta baja
N13-Planta baja
A37-Planta baja
A36-Planta baja
N18-Planta baja
N18-Planta baja
N18-Planta baja
A38-Planta baja
A39-Planta baja
N21-Planta baja
N21-Planta baja
N21-Planta baja
A41-Planta baja
A40-Planta baja
N24-Planta baja
A42-Planta baja
A43-Planta baja
A43-Planta baja

A24-Planta baja
A28-Planta baja
A28-Planta baja
N10-Planta baja
A32-Planta baja
A30-Planta baja
A32-Planta baja
A31-Planta baja
A30-Planta baja
A29-Planta baja
A30-Planta baja
A29-Planta baja
A25-Planta baja
N17-Planta baja
A27-Planta baja
N16-Planta baja
N16-Planta baja
N17-Planta baja
N17-Planta baja
N12-Planta baja
N24-Planta baja
A26-Planta baja
A35-Planta baja
A35-Planta baja
A35-Planta baja
A35-Planta baja
A35-Planta baja
A35-Planta baja
A34-Planta baja
A35-Planta baja
N21-Planta baja
A37-Planta baja
A36-Planta baja
A37-Planta baja
A36-Planta baja
N13-Planta baja
A38-Planta baja
A39-Planta baja
A38-Planta baja
A39-Planta baja
N18-Planta baja
A41-Planta baja
A40-Planta baja
A41-Planta baja
A40-Planta baja
A23-Planta baja
A54-Planta baja
A46-Planta baja
A58-Planta baja

3600.0
488.5
488.5
2422.7
688.8
2422.7
688.8
807.6
807.6
807.6
807.6
807.6
688.8
688.8
488.5
488.5
1699.9
1699.9
2911.2
2520.0
2520.0
2520.0
2520.0
2131.2
1871.2
1372.0
819.6
281.2
2520.0
281.2
2520.0
499.2
552.4
499.2
552.4
1051.6
260.0
538.4
260.0
538.4
1850.0
388.8
281.2
388.8
281.2
6120.0
3600.0
3600.0
3600.0

1200x200
300x200
300x200
800x200
500x200
800x200
500x200
600x200
600x200
600x200
600x200
600x200
500x200
500x200
300x200
300x200
600x200
600x200
1000x200
400x400
800x200
400x400
800x200
800x200
600x200
500x200
300x200
200x200
800x200
200x200
400x400
300x200
500x150
300x200
500x150
300x250
200x200
400x200
200x200
400x200
400x300
250x200
200x200
250x200
200x200
800x200
1200x200
1200x200
1200x200

5.3
2.4
2.4
5.0
2.1
5.0
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.4
2.4
4.5
4.5
5.0
4.7
5.2
4.7
5.2
4.4
5.0
4.3
4.1
2.1
5.2
2.1
4.7
2.5
2.4
2.5
2.4
4.2
1.9
2.1
1.9
2.1
4.6
2.3
2.1
2.3
2.1
12.7
5.3
5.3
5.3

489.8
266.4
266.4
413.5
337.0
413.5
337.0
365.3
365.3
365.3
365.3
365.3
337.0
337.0
266.4
266.4
365.3
365.3
454.2
437.3
413.5
437.3
413.5
413.5
365.3
337.0
266.4
218.6
413.5
218.6
437.3
266.4
286.8
266.4
286.8
299.1
218.6
304.7
218.6
304.7
377.7
244.1
218.6
244.1
218.6
413.5
489.8
489.8
489.8

15.32
0.30
2.39
3.29
10.33
0.32
0.30
0.30
8.87
0.30
0.30
6.65
0.33
14.37
0.33
17.38
2.58
6.44
8.87
6.79
4.79
1.33
14.18
3.39
5.10
10.39
3.82
5.72
16.58
0.33
5.18
1.37
1.38
0.30
0.30
5.32
1.42
1.38
0.30
0.30
4.50
1.47
1.51
0.30
0.30
4.22
1.69
0.74
1.00

8.46 20.90
10.44 9.91
-1.34
0.04
1.31
0.93
13.28 15.27
18.26 22.15
3.21
18.26 26.16
18.26 23.27
7.23
15.72 51.67
35.26
12.81 71.33
57.70
12.60 64.76
47.74
12.60 51.10
43.69
10.29
86.25
15.34 63.87
14.52 64.63
13.38 66.91
16.38 78.29
15.56 82.19
68.16
4.15 27.29
16.98 85.70
48.68
58.00
57.16
6.98 65.83
8.54 66.55
54.22
54.06
57.40
2.96 57.49
8.11 66.14
51.20
52.24
50.44
6.61 59.53
3.46 54.45
17.23 85.61
-75.72
18.98
-75.48

29.84

24.48
17.60
13.59
16.48
19.66

6.58
20.23

21.83
21.07
18.79
7.40
3.51

-35.53
-36.25

-27.19
-35.84

-29.23
-24.15

273

Anexos

A44-Planta baja
A44-Planta baja
A45-Planta baja
A45-Planta baja
A45-Planta baja
A46-Planta baja
A46-Planta baja
A46-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A47-Planta baja
A69-Planta baja
A69-Planta baja
A69-Planta baja
A69-Planta baja
A69-Planta baja
N15-Planta baja
N15-Planta baja
N15-Planta baja
N15-Planta baja
A57-Planta baja
A61-Planta baja
A63-Planta baja
A54-Planta baja
A54-Planta baja
A55-Planta baja
A55-Planta baja
A56-Planta baja
A56-Planta baja
A58-Planta baja
A58-Planta baja
A59-Planta baja
A59-Planta baja
A60-Planta baja
A60-Planta baja
A62-Planta baja
A62-Planta baja
A64-Planta baja
A64-Planta baja
A65-Planta baja
A65-Planta baja
A66-Planta baja
A66-Planta baja
A67-Planta baja

A45-Planta baja
A62-Planta baja
A50-Planta baja
N19-Planta baja
A51-Planta baja
A49-Planta baja
N15-Planta baja
A52-Planta baja
A48-Planta baja
A42-Planta baja
A71-Planta baja
A71-Planta baja
A71-Planta baja
A71-Planta baja
A71-Planta baja
A53-Planta baja
A69-Planta baja
N19-Planta baja
N19-Planta baja
N19-Planta baja
N19-Planta baja
A70-Planta baja
A70-Planta baja
A70-Planta baja
A70-Planta baja
A57-Planta baja
A61-Planta baja
A63-Planta baja
A54-Planta baja
A55-Planta baja
A55-Planta baja
A56-Planta baja
A56-Planta baja
A68-Planta baja
A58-Planta baja
A59-Planta baja
A59-Planta baja
A60-Planta baja
A60-Planta baja
A67-Planta baja
A62-Planta baja
A72-Planta baja
A64-Planta baja
A66-Planta baja
A65-Planta baja
A64-Planta baja
A66-Planta baja
A63-Planta baja
A67-Planta baja

3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
3600.0
2880.0
2160.0
1440.0
720.0
3600.0
770.5
770.5
1541.0
2570.5
3600.0
3600.0
2700.0
1800.0
900.0
720.0
720.0
754.9
720.0
2880.0
720.0
2160.0
720.0
1440.0
720.0
2880.0
720.0
2160.0
720.0
1440.0
754.9
2845.1
445.1
1509.7
445.1
1954.9
754.9
754.9
720.0

1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1200x200
1000x200
800x200
500x200
500x200
1200x200
500x200
500x200
600x200
800x200
1200x200
1200x200
1000x200
600x200
600x200
500x200
500x200
500x200
500x200
1000x200
500x200
800x200
500x200
500x200
500x200
1000x200
500x200
800x200
500x200
500x200
500x200
1000x200
300x200
600x200
300x200
800x200
500x200
500x200
500x200

5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
4.9
4.5
4.5
2.2
5.3
2.4
2.4
4.1
5.3
5.3
5.3
4.6
4.8
2.4
2.2
2.2
2.4
2.2
4.9
2.2
4.5
2.2
4.5
2.2
4.9
2.2
4.5
2.2
4.5
2.4
4.9
2.2
4.0
2.2
4.0
2.4
2.4
2.2

489.8
489.8
489.8
489.8
489.8
489.8
489.8
489.8
489.8
489.8
489.8
454.2
413.5
337.0
337.0
489.8
337.0
337.0
365.3
413.5
489.8
489.8
454.2
365.3
365.3
337.0
337.0
337.0
337.0
454.2
337.0
413.5
337.0
337.0
337.0
454.2
337.0
413.5
337.0
337.0
337.0
454.2
266.4
365.3
266.4
413.5
337.0
337.0
337.0

0.89
2.08
16.66
4.24
15.01
4.69
3.65
5.62
5.10
0.79
5.16
4.48
2.40
2.95
1.57
2.76
0.33
1.92
3.13
2.73
1.75
1.17
2.55
2.04
1.82
0.30
0.30
0.30
0.30
5.28
0.30
6.83
0.30
6.41
0.30
4.50
0.30
4.70
0.30
2.73
0.30
2.98
0.30
2.95
0.30
4.58
0.30
2.26
0.30

5.96
8.46
5.96
8.46
5.96
6.96
6.96
6.96
6.96
8.46
14.16
14.16
14.22
14.22
10.87
10.87
10.87
14.51
14.51
15.95
14.51
14.51
14.51
14.51
14.51
14.51
15.95
8.67
8.67
15.95
14.51

24.59
-74.30
24.12
23.00
16.46
18.59
26.23
20.01
17.96
18.38
23.91 12.74
29.90
6.76
31.05
5.61
35.62
1.03
28.95
9.93
46.89
31.87
45.64
1.24
44.22
2.67
42.43
4.46
41.99
3.62
43.16
2.45
44.43
1.18
33.89
-40.03 81.62
-33.21 81.02
-36.71 76.65
-54.67 96.26
-74.08
-56.33 97.92
-65.83
-48.37 89.96
-59.52
-54.43 102.23
-64.80
-47.05 94.86
-60.57
-43.12 90.92
-52.96
-55.51 95.45
-68.24
-45.46 85.40
-54.68
-47.63 87.57
-55.94
-35.47 75.41
-53.48
-34.72 82.53

274

Anexos

A67-Planta baja
A68-Planta baja
A68-Planta baja
A70-Planta baja
A71-Planta baja
A72-Planta baja
A72-Planta baja
A73-Planta baja
A74-Planta baja
A74-Planta baja
A74-Planta baja
A74-Planta baja
N14-Planta baja
N14-Planta baja
A79-Planta baja
N22-Planta baja
N22-Planta baja
N23-Planta baja
A84-Planta baja
A78-Planta baja
N27-Planta baja
N27-Planta baja
N27-Planta baja
N27-Planta baja
A77-Planta baja
A80-Planta baja
A80-Planta baja
N20-Planta baja
A82-Planta baja
A82-Planta baja
A83-Planta baja
A83-Planta baja
A28-Planta 1
A29-Planta 1
A29-Planta 1
A29-Planta 1
N23-Planta 1
N23-Planta 1
N24-Planta 1
N24-Planta 1
A35-Planta 1
N26-Planta 1
N26-Planta 1
N26-Planta 1
A32-Planta 1
A33-Planta 1
A34-Planta 1
A36-Planta 1
A36-Planta 1

A61-Planta baja
A68-Planta baja
A57-Planta baja
A70-Planta baja
A71-Planta baja
A72-Planta baja
A65-Planta baja
N22-Planta baja
A76-Planta baja
A73-Planta baja
N27-Planta baja
A75-Planta baja
A78-Planta baja
A78-Planta baja
A79-Planta baja
N20-Planta baja
A80-Planta baja
A83-Planta baja
A84-Planta baja
A78-Planta baja
N14-Planta baja
N14-Planta baja
A77-Planta baja
A77-Planta baja
A77-Planta baja
A80-Planta baja
A82-Planta baja
A79-Planta baja
A82-Planta baja
N23-Planta baja
A83-Planta baja
A84-Planta baja
N24-Planta 1
A5-Planta 1
A28-Planta 1
A30-Planta 1
N1-Planta 1
A34-Planta 1
N23-Planta 1
A35-Planta 1
A35-Planta 1
A32-Planta 1
A33-Planta 1
N2-Planta 1
A32-Planta 1
A33-Planta 1
A34-Planta 1
A36-Planta 1
A29-Planta 1

720.0
720.0
720.0
900.0
720.0
445.1
2400.0
2040.0
2040.0
2040.0
2040.0
2040.0
1439.1
390.2
207.1
207.1
1832.9
914.7
390.2
390.2
1636.0
1439.1
404.0
207.1
207.1
393.9
1439.1
207.1
524.4
914.7
524.4
390.2
2520.0
2520.0
2520.0
2520.0
1986.4
326.1
2312.6
207.4
207.4
242.9
225.9
1274.7
242.9
225.9
326.1
207.4
207.4

500x200
500x200
500x200
600x200
500x200
300x200
800x200
600x200
600x200
600x200
600x200
600x200
500x200
250x200
200x150
200x150
600x200
250x250
250x200
250x200
500x200
500x200
200x200
200x150
200x150
250x200
500x200
200x150
250x250
250x250
250x250
250x200
400x400
400x400
400x400
400x400
400x300
200x200
500x250
200x150
200x150
200x150
200x150
300x300
200x150
200x150
200x200
200x150
200x150

2.2
2.2
2.2
2.4
2.2
2.2
5.0
5.4
5.4
5.4
5.4
5.4
4.5
2.3
2.1
2.1
4.9
4.3
2.3
2.3
5.1
4.5
3.0
2.1
2.1
2.3
4.5
2.1
2.5
4.3
2.5
2.3
4.7
4.7
4.7
4.7
4.9
2.4
5.6
2.1
2.1
2.4
2.2
4.2
2.4
2.2
2.4
2.1
2.1

337.0
337.0
337.0
365.3
337.0
266.4
413.5
365.3
365.3
365.3
365.3
365.3
337.0
244.1
188.9
188.9
365.3
273.3
244.1
244.1
337.0
337.0
218.6
188.9
188.9
244.1
337.0
188.9
273.3
273.3
273.3
244.1
437.3
437.3
437.3
437.3
377.7
218.6
380.8
188.9
188.9
188.9
188.9
327.9
188.9
188.9
218.6
188.9
188.9

2.27
0.30
3.10
0.33
0.33
0.30
4.03
0.71
8.84
0.58
0.38
9.38
0.92
2.05
0.30
0.92
0.94
1.51
0.30
0.33
0.72
2.43
2.84
4.94
0.33
0.30
5.34
1.96
0.03
4.39
0.03
1.58
2.88
4.08
1.01
4.06
2.11
1.62
1.46
1.95
0.30
1.53
1.80
1.68
0.30
0.30
0.30
0.33
9.41

-48.47
14.51 -41.28
-55.29
10.87 45.61
6.96 36.65
8.67 -56.06
-61.67
-20.90
1.91 22.50
22.95
16.83
2.72 16.53
14.76 38.79
24.61
1.88 -16.03
-19.12
-16.79
3.68
6.66 12.20
15.45 40.75
8.33 27.54
20.71
8.33 28.73
21.96
9.21 31.78
6.79 -7.17
-8.87
-18.50
7.70 2.38
2.55
7.70 14.24
4.86
-32.08
2.92 11.89
12.38
4.15 8.97
-25.90
-28.33
-31.09
-23.15
1.88 -20.67
-18.87
-19.40
-23.20
2.58 -15.47
2.23 -16.45
4.65 -22.94
9.24 68.32
58.48

82.87

96.00

1.96
57.32

29.09
13.21
12.01
8.97
48.46

38.91
27.05

51.58

46.39
47.36
53.85

275

Anexos

A36-Planta 1
A36-Planta 1
A36-Planta 1
A36-Planta 1
A36-Planta 1
A36-Planta 1
N1-Planta 1
N1-Planta 1
A1-Planta 1
A4-Planta 1
N3-Planta 1
N3-Planta 1
N3-Planta 1
A3-Planta 1
N5-Planta 1
A2-Planta 1
A2-Planta 1
N2-Planta 1
A6-Planta 1
A7-Planta 1
A8-Planta 1
A8-Planta 1
A8-Planta 1
A8-Planta 1
N7-Planta 1
N7-Planta 1
A14-Planta 1
N9-Planta 1
N9-Planta 1
A13-Planta 1
N11-Planta 1
N11-Planta 1
A12-Planta 1
N13-Planta 1
N13-Planta 1
A11-Planta 1
N15-Planta 1
N15-Planta 1
A10-Planta 1
N17-Planta 1
N17-Planta 1
A9-Planta 1
A15-Planta 1
A15-Planta 1
A16-Planta 1
A16-Planta 1
A17-Planta 1
A17-Planta 1
A18-Planta 1

A29-Planta 1
A29-Planta 1
A29-Planta 1
A29-Planta 1
A29-Planta 1
A29-Planta 1
N26-Planta 1
A1-Planta 1
A1-Planta 1
A4-Planta 1
A4-Planta 1
A3-Planta 1
N5-Planta 1
A3-Planta 1
A2-Planta 1
A2-Planta 1
A6-Planta 1
N3-Planta 1
A6-Planta 1
A20-Planta 1
A22-Planta 1
A7-Planta 1
N17-Planta 1
A21-Planta 1
A14-Planta 1
N6-Planta 1
A14-Planta 1
N7-Planta 1
A13-Planta 1
A13-Planta 1
N4-Planta 1
A12-Planta 1
A12-Planta 1
N11-Planta 1
A11-Planta 1
A11-Planta 1
N13-Planta 1
A10-Planta 1
A10-Planta 1
N15-Planta 1
A9-Planta 1
A9-Planta 1
A15-Planta 1
A25-Planta 1
A16-Planta 1
A15-Planta 1
A17-Planta 1
A16-Planta 1
A18-Planta 1

533.6
759.5
968.3
1718.2
2034.3
2520.0
1743.6
242.9
242.9
208.7
208.7
316.0
750.0
316.0
750.0
375.0
375.0
1274.7
375.0
2520.0
2520.0
2520.0
2520.0
2520.0
246.3
920.8
246.3
1167.0
224.2
224.2
1615.5
228.8
228.8
1844.3
217.2
217.2
2061.5
249.3
249.3
2310.8
209.2
209.2
246.3
920.8
448.4
1167.0
228.8
1615.5
217.2

250x200
300x200
400x200
600x200
600x200
800x200
400x250
200x150
200x150
200x150
200x150
200x200
300x200
200x200
300x200
250x200
250x200
300x300
250x200
800x200
400x400
400x400
400x400
400x400
200x150
250x250
200x150
300x250
200x150
200x150
400x250
200x150
200x150
400x300
200x150
200x150
400x300
200x150
200x150
500x250
200x150
200x150
200x150
400x200
300x200
400x200
200x150
500x200
200x150

3.2
3.8
3.7
4.6
5.4
5.2
5.2
2.4
2.4
2.1
2.1
2.3
3.7
2.3
3.7
2.2
2.2
4.2
2.2
5.2
4.7
4.7
4.7
4.7
2.4
4.4
2.4
4.6
2.2
2.2
4.8
2.3
2.3
4.6
2.2
2.2
5.1
2.5
2.5
5.6
2.1
2.1
2.4
3.5
2.2
4.4
2.3
5.0
2.2

244.1
266.4
304.7
365.3
365.3
413.5
343.3
188.9
188.9
188.9
188.9
218.6
266.4
218.6
266.4
244.1
244.1
327.9
244.1
413.5
437.3
437.3
437.3
437.3
188.9
273.3
188.9
299.1
188.9
188.9
343.3
188.9
188.9
377.7
188.9
188.9
377.7
188.9
188.9
380.8
188.9
188.9
188.9
304.7
266.4
304.7
188.9
337.0
188.9

6.81
6.69
14.83
8.85
5.08
9.02
3.13
1.62
0.30
0.30
1.79
1.51
6.05
0.30
1.95
0.30
2.15
1.68
0.30
5.12
1.75
2.62
10.82
5.08
1.05
2.77
0.33
3.45
0.95
0.33
1.88
1.05
0.33
2.81
1.00
0.33
2.96
0.95
0.33
3.26
1.05
0.33
0.30
2.00
0.30
4.35
0.30
4.67
0.30

10.79
10.96
9.35
13.42
10.13
12.66

2.58
1.91

4.37
6.15

6.15
2.92

4.15

13.03

10.79

11.24

10.13

13.35

9.40
2.65
8.79
2.29
2.06

65.80
62.62
56.96
51.88
40.64
39.21
-23.56
-22.64
-19.24
-16.23
-18.74
-19.35
-18.90
-14.29
-16.93
-7.83
-13.49
-22.25
-6.71
-21.71
7.93
11.67
24.25
11.57
68.70
65.97
82.58
68.25
72.00
83.51
75.55
63.84
75.82
64.18
54.00
64.80
53.66
40.88
55.10
40.47
23.35
33.37
-3.92
-8.89
2.97
-9.30
-10.05
-11.34
-12.49

2.52
5.71
11.36
16.44
27.68
29.12

50.16
47.14

45.20
38.74

37.62

4.26

3.33

11.02

22.03

31.73

53.46
46.61
39.73
52.75
55.18

276

Anexos

A18-Planta 1
A19-Planta 1
A19-Planta 1
A20-Planta 1
A20-Planta 1
N4-Planta 1
N4-Planta 1
A23-Planta 1
A24-Planta 1
A25-Planta 1
A25-Planta 1
N6-Planta 1
N6-Planta 1
A27-Planta 1
A27-Planta 1
A26-Planta 1
A26-Planta 1
A31-Planta 1
A37-Planta 1
A38-Planta 1
A39-Planta 1
A39-Planta 1
A39-Planta 1
A39-Planta 1
N8-Planta 1
A55-Planta 1
N12-Planta 1
N12-Planta 1
A54-Planta 1
N16-Planta 1
N16-Planta 1
A53-Planta 1
N19-Planta 1
N19-Planta 1
A52-Planta 1
N21-Planta 1
N21-Planta 1
A51-Planta 1
N27-Planta 1
N27-Planta 1
A50-Planta 1
A48-Planta 1
N30-Planta 1
N30-Planta 1
A42-Planta 1
A42-Planta 1
A43-Planta 1
A43-Planta 1
A44-Planta 1

A17-Planta 1
A19-Planta 1
A18-Planta 1
A20-Planta 1
A19-Planta 1
N9-Planta 1
A23-Planta 1
A23-Planta 1
A24-Planta 1
A25-Planta 1
A26-Planta 1
A24-Planta 1
A27-Planta 1
A27-Planta 1
A31-Planta 1
A26-Planta 1
A37-Planta 1
A31-Planta 1
A37-Planta 1
N30-Planta 1
A41-Planta 1
A38-Planta 1
N8-Planta 1
A40-Planta 1
N29-Planta 1
A55-Planta 1
N10-Planta 1
A54-Planta 1
A54-Planta 1
N12-Planta 1
A53-Planta 1
A53-Planta 1
N16-Planta 1
A52-Planta 1
A52-Planta 1
N19-Planta 1
A51-Planta 1
A51-Planta 1
N21-Planta 1
A50-Planta 1
A50-Planta 1
A48-Planta 1
A48-Planta 1
A47-Planta 1
A42-Planta 1
A57-Planta 1
A43-Planta 1
A42-Planta 1
A44-Planta 1

1844.3
249.3
2061.5
209.2
2310.8
1391.3
224.2
224.2
260.5
260.5
660.3
260.5
660.3
330.1
330.1
330.1
330.1
330.1
330.1
2520.0
2520.0
2520.0
2520.0
2520.0
2520.0
262.9
525.8
486.4
486.4
1012.1
253.9
253.9
1266.1
249.6
249.6
1515.7
503.6
503.6
2019.3
241.0
241.0
259.7
259.7
2260.3
262.9
262.9
486.4
525.8
253.9

600x200
200x150
600x200
200x150
800x200
300x300
200x150
200x150
200x200
200x200
250x200
200x200
250x200
200x200
200x200
200x200
200x200
200x200
200x200
800x200
800x200
800x200
800x200
800x200
800x200
200x200
250x200
300x200
300x200
300x250
200x200
200x200
300x300
200x150
200x150
300x300
400x200
400x200
400x300
200x150
200x150
200x200
200x200
800x200
200x200
200x200
300x200
250x200
200x200

4.9
2.5
5.5
2.1
4.8
4.6
2.2
2.2
1.9
1.9
3.9
1.9
3.9
2.4
2.4
2.4
2.4
2.4
2.4
5.2
5.2
5.2
5.2
5.2
5.2
1.9
3.1
2.4
2.4
4.0
1.9
1.9
4.2
2.5
2.5
5.0
1.9
1.9
5.0
2.4
2.4
1.9
1.9
4.7
1.9
1.9
2.4
3.1
1.9

365.3
188.9
365.3
188.9
413.5
327.9
188.9
188.9
218.6
218.6
244.1
218.6
244.1
218.6
218.6
218.6
218.6
218.6
218.6
413.5
413.5
413.5
413.5
413.5
413.5
218.6
244.1
266.4
266.4
299.1
218.6
218.6
327.9
188.9
188.9
327.9
304.7
304.7
377.7
188.9
188.9
218.6
218.6
413.5
218.6
218.6
266.4
244.1
218.6

3.23
0.30
3.10
0.30
3.01
4.16
0.96
0.33
0.33
0.30
5.80
2.74
3.81
0.33
1.12
0.30
1.36
0.33
0.30
2.33
0.88
0.54
2.15
2.74
1.39
0.33
5.78
0.94
0.33
3.16
0.89
0.33
3.01
0.94
0.33
5.94
0.89
0.33
2.64
0.89
0.33
0.30
0.98
1.28
0.30
3.84
0.30
5.45
0.30

-14.74
2.72 -15.45
-16.72
1.91 -11.25
-20.21
72.22
75.33
10.79 86.84
14.57 81.45
2.97 -3.97
-4.90
66.40
68.14
11.06 80.84
68.99
4.77 3.24
-1.15
11.06 81.88
4.77 4.37
-30.23
2.92 8.67
9.02
10.36
4.15 9.00
15.87
14.84 61.94
46.12
42.37
12.70 55.89
41.94
43.91
13.84 58.21
43.79
46.37
13.38 60.63
46.66
43.14
13.61 57.31
43.22
31.12
12.47 44.41
2.95 -24.93
-28.35
-26.32
3.02 -9.65
-13.38
6.62 -7.59
-14.81
2.82 -12.91

58.14
53.95

5.39
46.67

6.00
39.46
4.96
38.33

1.77

7.83

5.50

3.08

6.41

19.30
58.33

43.04
40.98
46.31

277

Anexos

A44-Planta 1
A45-Planta 1
A45-Planta 1
A46-Planta 1
A46-Planta 1
A47-Planta 1
A47-Planta 1
N29-Planta 1
N29-Planta 1
A49-Planta 1
N10-Planta 1
N10-Planta 1
A56-Planta 1
A57-Planta 1

A43-Planta 1
A45-Planta 1
A44-Planta 1
A46-Planta 1
A45-Planta 1
A47-Planta 1
A46-Planta 1
N27-Planta 1
A49-Planta 1
A49-Planta 1
A55-Planta 1
A56-Planta 1
A56-Planta 1
A57-Planta 1

Q
Caudal
w x h Dimensiones (Ancho x Alto)
V
Velocidad

Dimetro equivalente.

2.3.2

1012.1
249.6
1266.1
503.6
1515.7
241.0
2019.3
2260.3
259.7
259.7
262.9
262.9
262.9
262.9

400x200
200x150
400x200
400x200
500x200
200x150
600x200
500x250
200x200
200x200
200x200
200x200
200x200
200x200

3.9
2.5
4.8
1.9
4.7
2.4
5.4
5.5
1.9
1.9
1.9
1.9
1.9
1.9

304.7
188.9
304.7
304.7
337.0
188.9
365.3
380.8
218.6
218.6
218.6
218.6
218.6
218.6

3.12
0.30
3.14
0.30
4.85
0.30
3.58
2.43
0.91
0.33
0.89
5.43
0.33
0.30

-17.14
2.73 -13.18
-18.04
7.10 -10.30
-20.32
2.54 -21.86
-22.58
30.75
15.35
14.48 30.31
46.61
48.38
14.84 63.71
3.02 -9.88

46.58
43.70
55.26

33.41

43.27

Abreviaturas utilizadas
L Longitud
P1 Prdida de presin
P Prdida de presin acumulada
Diferencia de presin respecto al difusor o
D
rejilla ms desfavorable

Sistemas de conduccin de aire. Difusores y rejillas


Difusores y rejillas
Tipo

(mm)

wx
h(mm)

Q(m/h) A(cm) X(m) P(dBA)

P1
(Pa)

P
D(Pa)
(Pa)

A10-Planta baja: Rejilla de


retorno
A9-Planta baja: Rejilla de

325x225

801.4

330.00

42.0 15.32 54.53 0.00

325x225

801.4

330.00

42.0 15.32 51.29 3.24

retorno
A8-Planta baja: Rejilla de
retorno
A7-Planta baja: Rejilla de
retorno
A6-Planta baja: Difusor

425x225

998.6

440.00

40.0 13.38 45.79 8.74

425x225

998.6

440.00

40.0 13.38 42.54 11.99

657x248

998.6

540.00

0.0

35.7 19.39

A3-Planta baja: Difusor

557x248

801.4

450.00

0.0

A4-Planta baja: Difusor

557x248

801.4

450.00

0.0

A5-Planta baja: Difusor

657x248

998.6

540.00

0.0

34.6 17.98 37.98


0.00
28.63
34.6 17.98 2.49
35.7 19.39 31.12
0.85

A12-Planta baja: Rejilla de


extraccin
A11-Planta baja: Rejilla de
toma de aire

9.34

1400x330 3600.0 2970.83

21.9

8.46 29.48
20.13 0.00

1400x330 3600.0 2376.66

27.7

5.96 18.51 0.00

A15-Planta baja: Rejilla de

325x225

840.0

330.00

A16-Planta baja: Difusor

448x448

840.0

680.00

0.0

23.5

8.65 -4.07 1.61

A17-Planta baja: Difusor

448x448

840.0

680.00

0.0

23.5

8.65 -2.46 0.00

A18-Planta baja: Difusor

448x448

840.0

680.00

0.0

23.5

8.65 -9.19 6.73

1400x330 2520.0 2376.66

16.8

2.92 7.68 0.00

1400x330 2520.0 2970.83

11.1

4.15 8.01 0.00

A19-Planta baja: Rejilla de


toma de aire
A20-Planta baja: Rejilla de
extraccin
A28-Planta baja: Difusor

43.5 16.84 51.75 0.00

457x248

488.5

360.00

0.0

26.3 10.44 9.91 16.25

A32-Planta baja: Difusor

557x248

688.8

450.00

0.0

30.0 13.28 15.27 10.89

A31-Planta baja: Difusor

557x248

807.6

450.00

0.0

34.8 18.26 22.15 4.01

A29-Planta baja: Difusor

557x248

807.6

450.00

0.0

34.8 18.26 26.16 0.00

278

Anexos

A30-Planta baja: Difusor

557x248

807.6

450.00

A25-Planta baja: Rejilla de


retorno
A24-Planta baja: Rejilla de
extraccin baja: Rejilla de
A23-Planta
toma de aire

525x125

688.8

280.00

A27-Planta baja: Rejilla de


retorno
A35-Planta baja: Rejilla de
retorno
A37-Planta
baja: Difusor

0.0

34.8 18.26 23.27 2.89


42.4 15.72 51.67 19.66

1400x330 3600.0 2970.83

21.9

8.46 20.90 0.00

1400x330 6120.0 2376.66

43.8 17.23 85.61 0.00

425x125

488.5

220.00

225x125

281.2

110.00

557x248

499.2

450.00

0.0

20.2

A36-Planta baja: Difusor

557x248

552.4

450.00

0.0

23.3

8.54 66.55 0.00

A38-Planta baja: Difusor

457x248

260.0

360.00

0.0

7.2

2.96 57.49 9.06

A39-Planta baja: Difusor

557x248

538.4

450.00

0.0

22.5

8.11 66.14 0.41

A41-Planta baja: Difusor

457x248

388.8

360.00

0.0

19.4

6.61 59.53 7.02

457x248

281.2

360.00

0.0

9.5

3.46 54.45 12.10

11.1

4.15 27.29 0.00

A40-Planta baja: Difusor


A34-Planta baja: Rejilla de
extraccin
A69-Planta baja: Rejilla de
retorno
A57-Planta baja: Difusor

39.3 12.81 71.33 0.00


43.6 16.98 85.70 0.00

1400x330 2520.0 2970.83

6.98 65.83 0.72

325x225

770.5

330.00

557x248

720.0

450.00

0.0

31.3 14.51

557x248

720.0

450.00

0.0

557x248

754.9

450.00

0.0

1400x330 3600.0 2970.83

31.3 14.51 40.03


0.00
33.21
32.8 15.95 1.24
36.71 0.00
21.9 8.46 16.46

1400x330 3600.0 2376.66

27.7

5.96 24.12 0.00

A52-Planta baja: Rejilla de

1400x330 3600.0 2970.83

21.9

8.46 20.01 0.00

A49-Planta baja: Rejilla de


toma de aire

1400x330 3600.0 2376.66

27.7

5.96 18.59 0.00

1400x330 3600.0 2970.83

21.9

8.46 9.93 0.00

1400x330 3600.0 2376.66

27.7

5.96 17.96 0.00

A61-Planta baja: Difusor


A63-Planta baja: Difusor
A51-Planta baja: Rejilla de
extraccin
A50-Planta baja: Rejilla de
toma de aire

A53-Planta baja: Rejilla de


extraccin
A48-Planta baja: Rejilla de
toma de aire

40.8 14.16 46.89 0.00


-

0.00

A54-Planta baja: Difusor

557x248

720.0

450.00

0.0

A55-Planta baja: Difusor

557x248

720.0

450.00

0.0

A56-Planta baja: Difusor

557x248

720.0

450.00

0.0

A58-Planta baja: Difusor

557x248

720.0

450.00

0.0

A59-Planta baja: Difusor

557x248

720.0

450.00

0.0

A60-Planta baja: Difusor

557x248

720.0

450.00

0.0

A62-Planta baja: Difusor

557x248

754.9

450.00

0.0

A64-Planta baja: Difusor

457x248

445.1

360.00

0.0

32.8 15.95 43.12


- 20.04
23.5 8.67 55.51
9.99

A65-Planta baja: Difusor

457x248

445.1

360.00

0.0

23.5

A66-Planta baja: Difusor

557x248

754.9

450.00

0.0

A67-Planta baja: Difusor

557x248

720.0

450.00

0.0

A68-Planta baja: Difusor

557x248

720.0

450.00

0.0

A70-Planta baja: Rejilla de


retorno
A71-Planta baja: Rejilla de
retorno
A72-Planta
baja: Difusor

425x225

900.0

440.00

31.3 14.51 34.72


1.24
41.28
36.8 10.87 45.61 0.00

425x225

720.0

440.00

30.0

6.96 36.65 0.00

457x248

445.1

360.00

0.0

23.5

8.67

A79-Planta baja: Difusor

457x248

207.1

360.00

0.0

0.3

A84-Planta baja: Difusor

457x248

390.2

360.00

0.0

19.5

A78-Planta baja: Rejilla de


retorno
A77-Planta baja: Rejilla de
retorno
A75-Planta baja: Rejilla de
extraccin
A76-Planta baja: Rejilla de

325x125

390.2

160.00

42.2 15.45 40.75 0.00

225x125

207.1

110.00

34.3

9.21 31.78 8.97

1400x330 2040.0 2970.83

4.6

2.72 16.53 0.00

1400x330 2040.0 2376.66

10.4

1.91 22.50 0.00

toma de aire

31.3 14.51

- 14.64
54.67
31.3 14.51 - 16.30
31.3 14.51 56.33
8.34
31.3 14.51 48.37
- 21.21
31.3 14.51 54.43
- 13.84
31.3 14.51 47.05
9.90

8.67 45.46
- 12.16
32.8 15.95 47.63
0.00
35.47
31.3 14.51 1.51

- 20.59
56.06
1.88
- 30.27
6.66 16.03
12.20 2.04

A80-Planta baja: Difusor

457x248

393.9

360.00

0.0

19.8

6.79 -7.17 21.41

A82-Planta baja: Difusor

557x248

524.4

450.00

0.0

21.7

7.70 2.38 11.86

279

Anexos

A83-Planta baja: Difusor


A30-Planta 1: Rejilla de
extraccin
A5-Planta 1: Rejilla de toma

557x248

524.4

450.00

0.0

1400x330 2520.0 2970.83


1400x330 2520.0 2376.66

21.7

7.70 14.24 0.00

11.1

4.15 8.97 0.00

16.8

2.92 11.89 0.00

de aire
A35-Planta
1: Difusor

457x248

207.4

360.00

0.0

0.3

A32-Planta 1: Difusor

457x248

242.9

360.00

0.0

5.1

A33-Planta 1: Difusor

457x248

225.9

360.00

0.0

2.9

A34-Planta 1: Difusor

457x248

326.1

360.00

0.0

14.1

- 13.96
20.67
2.58
8.76
2.23 15.47
9.74
16.45
4.65
- 16.23

A36-Planta 1: Rejilla de
retorno
A1-Planta 1: Difusor

225x125

207.4

110.00

34.3

9.24 22.94
68.32 0.00

457x248

242.9

360.00

0.0

A4-Planta 1: Difusor

457x248

208.7

360.00

0.0

0.5

A3-Planta 1: Difusor

457x248

316.0

360.00

0.0

13.1

A2-Planta 1: Difusor

457x248

375.0

360.00

0.0

18.3

- 12.53
19.24
1.91
9.51
4.37 16.23
7.57
14.29
6.15 -7.83 1.11

A6-Planta 1: Difusor

457x248

375.0

360.00

0.0

18.3

6.15 -6.71 0.00

1400x330 2520.0 2970.83

11.1

4.15 11.57 0.00

1400x330 2520.0 2376.66

16.8

2.92 7.93 0.00

A21-Planta 1: Rejilla de
extraccin
A22-Planta 1: Rejilla de toma
de
aire
A14-Planta
1: Rejilla de
retorno
A13-Planta 1: Rejilla de

5.1

1.88

2.58

225x125

246.3

110.00

39.6 13.03 82.58 4.26

225x125

224.2

110.00

36.7 10.79 83.51 3.33

retorno
A12-Planta 1: Rejilla de
retorno
A11-Planta 1: Rejilla de
retorno
A10-Planta
1: Rejilla de
retorno
A9-Planta 1: Rejilla de

225x125

228.8

110.00

37.3 11.24 75.82 11.02

225x125

217.2

110.00

35.7 10.13 64.80 22.03

225x125

249.3

110.00

39.9 13.35 55.10 31.73

225x125

209.2

110.00

34.6

9.40 33.37 53.46

retorno
A15-Planta
1: Difusor

457x248

246.3

360.00

0.0

5.5

2.65 -3.92 8.29

A16-Planta 1: Difusor

457x248

448.4

360.00

0.0

23.7

A17-Planta 1: Difusor

457x248

228.8

360.00

0.0

3.3

A18-Planta 1: Difusor

457x248

217.2

360.00

0.0

1.7

A19-Planta 1: Difusor

457x248

249.3

360.00

0.0

5.9

A20-Planta 1: Difusor

457x248

209.2

360.00

0.0

A23-Planta 1: Rejilla de
retorno
A24-Planta 1: Rejilla de
retorno
A25-Planta 1: Difusor

225x125

224.2

110.00

36.7 10.79 11.25


86.84 0.00

225x125

260.5

110.00

41.3 14.57 81.45 5.39

457x248

260.5

360.00

A27-Planta 1: Rejilla de
retorno
A26-Planta 1: Difusor

325x125

330.1

160.00

457x248

330.1

360.00

A31-Planta 1: Rejilla de
retorno
A37-Planta 1: Difusor

325x125

330.1

160.00

457x248

330.1

360.00

A55-Planta 1: Rejilla de
retorno
A54-Planta 1: Rejilla de
retorno
A53-Planta 1: Rejilla de
retorno
A52-Planta 1: Rejilla de

225x125

262.9

110.00

41.5 14.84 61.94 1.77

425x125

486.4

220.00

39.2 12.70 55.89 7.83

225x125

253.9

110.00

40.5 13.84 58.21 5.50

225x125

249.6

110.00

40.0 13.38 60.63 3.08

retorno
A51-Planta 1: Rejilla de
retorno
A50-Planta 1: Rejilla de
retorno
A41-Planta 1: Rejilla de toma
de aire
A40-Planta
1: Rejilla de

425x125

503.6

220.00

40.2 13.61 57.31 6.41

225x125

241.0

110.00

38.9 12.47 44.41 19.30

0.0

0.6

7.2

8.79 2.97 1.40


2.29

- 14.42
10.05
2.06
- 16.86
2.72 12.49
- 19.82
15.45
1.91
- 15.62

2.97 -3.97 8.34

37.1 11.06 80.84 6.00


0.0

14.4

4.77 3.24 1.13

37.1 11.06 81.88 4.96


0.0

14.4

4.77 4.37 0.00

1400x330 2520.0 2376.66

16.8

2.92 8.67 0.00

1400x330 2520.0 2970.83

11.1

4.15 9.00 0.00

extraccin
A48-Planta 1: Difusor

457x248

259.7

360.00

0.0

7.1

A42-Planta 1: Difusor

457x248

262.9

360.00

0.0

7.5

A43-Planta 1: Difusor

557x248

486.4

450.00

0.0

19.4

A44-Planta 1: Difusor

457x248

253.9

360.00

0.0

6.4

A45-Planta 1: Difusor

457x248

249.6

360.00

0.0

5.9

A46-Planta 1: Difusor

557x248

503.6

450.00

0.0

20.5

A47-Planta 1: Difusor

457x248

241.0

360.00

0.0

4.9

A49-Planta 1: Rejilla de
retorno

225x125

259.7

110.00

2.95

- 17.34
3.02 24.93
-9.65 2.06
6.62 -7.59 0.00
2.82

5.33
12.91
2.73
5.59
7.10 13.18
2.71
2.54 10.30
- 14.27

41.2 14.48 21.86


30.31 33.41

280

Anexos

A56-Planta 1: Rejilla de
retorno
A57-Planta 1: Difusor

225x125

262.9

110.00

457x248

262.9

360.00

41.5 14.84 63.71 0.00

A14 -> A15, (73.69, 29.74),


14.84 m: Rejilla de retorno

325x225

840.0

330.00

43.5 16.84 47.32 4.43

A14 -> A15, (73.70, 25.51),


19.07 m: Rejilla de retorno

325x225

840.0

330.00

43.5 16.84 49.66 2.09

A27 -> N16, (67.75, 59.42),


17.38 m: Rejilla de retorno

525x225 1211.3 550.00

39.1 12.60 64.76 6.58

N16 -> N17, (60.07, 58.15),


6.37 m: Rejilla de retorno

525x225 1211.3 550.00

39.1 12.60 51.10 20.23

A33 -> A35, (54.37, 30.99),


14.18 m: Rejilla de retorno

325x125

388.8

160.00

42.1 15.34 63.87 21.83

A33 -> A35, (54.37, 27.60),


17.57 m: Rejilla de retorno

225x125

260.0

110.00

41.2 14.52 64.63 21.07

A33 -> A35, (54.37, 22.50),


22.67 m: Rejilla de retorno

425x125

499.2

220.00

40.0 13.38 66.91 18.79

A33 -> A35, (44.68, 21.80),


33.06 m: Rejilla de retorno

425x125

552.4

220.00

43.0 16.38 78.29 7.40

A33 -> A35, (44.05, 24.98),


36.87 m: Rejilla de retorno

425x125

538.4

220.00

42.3 15.56 82.19 3.51

A47 -> A71, (68.13, 16.13),


5.16 m: Rejilla de retorno

425x225

720.0

440.00

30.0

6.96 23.91 12.74

A47 -> A71, (71.33, 17.40),


9.64 m: Rejilla de retorno

425x225

720.0

440.00

30.0

6.96 29.90 6.76

A47 -> A71, (73.74, 17.40),


12.04 m: Rejilla de retorno

425x225

720.0

440.00

30.0

6.96 31.05 5.61

A47 -> A71, (75.56, 18.53),


14.99 m: Rejilla de retorno

425x225

720.0

440.00

30.0

6.96 35.62 1.03

A69 -> N19, (75.70, 37.98),


1.92 m: Rejilla de retorno

325x225

770.5

330.00

40.8 14.16 45.64 1.24

A69 -> N19, (75.70, 34.85),


5.05 m: Rejilla de retorno

425x225 1029.5 440.00

40.9 14.22 44.22 2.67

A69 -> N19, (75.70, 32.12),


7.78 m: Rejilla de retorno

425x225 1029.5 440.00

40.9 14.22 42.43 4.46

N15 -> A70, (75.70, 22.43),


1.17 m: Rejilla de retorno

425x225

900.0

440.00

36.8 10.87 41.99 3.62

N15 -> A70, (75.70, 24.98),


3.72 m: Rejilla de retorno

425x225

900.0

440.00

36.8 10.87 43.16 2.45

N15 -> A70, (75.70, 27.02),


5.76 m: Rejilla de retorno

425x225

900.0

440.00

36.8 10.87 44.43 1.18

N14 -> A78, (48.94, 42.45),


0.92 m: Rejilla de retorno

425x225 1048.8 440.00

41.5 14.76 38.79 1.96

N27 -> N14, (46.51, 41.53),


0.72 m: Rejilla de retorno

225x125

196.9

110.00

32.8

8.33 27.54 13.21

N27 -> A77, (43.98, 40.51),


2.84 m: Rejilla de retorno

225x125

196.9

110.00

32.8

8.33 28.73 12.01

A36 -> A29, (70.03, 37.38),


9.41 m: Rejilla de retorno

325x125

326.1

160.00

36.7 10.79 65.80 2.52

A36 -> A29, (70.03, 44.19),


16.22 m: Rejilla de retorno

225x125

225.9

110.00

36.9 10.96 62.62 5.71

A36 -> A29, (70.03, 50.88),


22.91 m: Rejilla de retorno

225x125

208.7

110.00

34.5

A36 -> A29, (62.92, 58.60),


37.74 m: Rejilla de retorno

625x125

750.0

330.00

40.0 13.42 51.88 16.44

A36 -> A29, (61.35, 51.32),


46.59 m: Rejilla de retorno

325x125

316.0

160.00

35.7 10.13 40.64 27.68

0.0

7.5

3.02 -9.88 2.29

9.35 56.96 11.36

281

Anexos

A36 -> A29, (61.35, 46.23),


51.67 m: Rejilla de retorno

425x125

485.7

220.00

39.1 12.66 39.21 29.12

Abreviaturas utilizadas

Dimetro

Potencia sonora

wx
h
Q

Dimensiones (Ancho x Alto)

P1

Prdida de presin

Caudal

Prdida de presin acumulada

rea efectiva

Diferencia de presin respecto al difusor o rejilla ms


desfavorable

Alcance

282

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

3. PLANOS
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Planos

ndice
0

HOJA DE IDENTIFICACIN............................................................................................................. 2

SITUACIN Y EMPLAZAMIENTO.................................................................................................. 3

OFICINAS. PLANTA BAJA ................................................................................................................ 4

OFICINAS. PLANTA ALTA................................................................................................................ 5

SECCIN ALZADO Y POSTERIOR ................................................................................................. 6

SECCIN INTERIOR .......................................................................................................................... 7

INSTALACIN DE CLIMATIZACIN. PLANTA 0....................................................................... 8

INSTALACIN DE CLIMATIZACIN. PLANTA 1....................................................................... 9

INSTALACIN DEL EDIFICIO. VISTA 3D................................................................................... 10

Planos

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con
CYPE Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01

Data y firmas de los anteriormente citados

Reus, Mayo de 2011

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

4. PLIEGO DE CONDICIONES
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Pliego de condiciones

ndice
0

HOJA DE IDENTIFICACIN .................................................................................................................. 3

GENERALIDADES .................................................................................................................................... 4

PLIEGO DE CLUSULAS ADMINISTRATIVAS................................................................................. 5


2.1

DISPOSICIONES GENERALES ................................................................................................................. 5

2.2

DISPOSICIONES FACULTATIVAS ............................................................................................................ 5

2.2.1

Definicin y atribuciones de los agentes de la edificacin ............................................................. 5

2.2.1.1

El Promotor ........................................................................................................................................... 5

2.2.1.2

El Proyectista......................................................................................................................................... 5

2.2.1.3

El Constructor o Contratista .................................................................................................................. 6

2.2.1.4

El Director de Obra ............................................................................................................................... 6

2.2.1.5

El Director de la Ejecucin de la Obra .................................................................................................. 6

2.2.1.6

Las entidades y los laboratorios de control de calidad de la edificacin................................................ 6

2.2.1.7

Los suministradores de productos ......................................................................................................... 7

2.2.2

Agentes que intervienen en la obra segn Ley 38/99 (L.O.E.) ........................................................ 7

2.2.3

Agentes en materia de seguridad y salud segn R.D. 1627/97 ....................................................... 7

2.2.4

Agentes en materia de gestin de residuos segn R.D. 105/08. ...................................................... 7

2.2.5

La Direccin Facultativa ................................................................................................................ 7

2.2.6

Visitas facultativas .......................................................................................................................... 8

2.2.7

Obligaciones de los agentes intervinientes ..................................................................................... 8

2.2.7.1

El Promotor ........................................................................................................................................... 8

2.2.7.2

El Proyectista......................................................................................................................................... 9

2.2.7.3

El Constructor o Contratista ................................................................................................................ 10

2.2.7.4

El Director de Obra ............................................................................................................................. 12

2.2.7.5

El Director de la Ejecucin de la Obra ................................................................................................ 13

2.2.7.6

Las entidades y los laboratorios de control de calidad de la edificacin.............................................. 15

2.2.7.7

Los suministradores de productos ....................................................................................................... 16

2.2.7.8

Los propietarios y los usuarios ............................................................................................................ 16

Pliego de condiciones

2.2.8

Documentacin final de obra: Libro del Edificio ......................................................................... 16

2.2.8.1

2.3
3

Los propietarios y los usuarios ............................................................................................................ 16

DISPOSICIONES ECONMICAS ............................................................................................................. 17

PLIEGO DE CONDICIONES TCNICAS PARTICULARES............................................................ 17


3.1

PRESCRIPCIONES SOBRE LOS MATERIALES .......................................................................................... 17

3.1.1

Garantas de calidad (Marcado CE)............................................................................................. 18

3.1.2

Aislantes e impermeabilizantes ..................................................................................................... 21

3.1.2.1

3.2
3.2.1
3.3

Aislantes de lana mineral..................................................................................................................... 21

PRESCRIPCIONES EN CUANTO A LA EJECUCIN POR UNIDAD DE OBRA ............................................... 22


Instalaciones ................................................................................................................................. 27
PRESCRIPCIONES SOBRE VERIFICACIONES EN EL EDIFICIO TERMINADO ............................................... 66

Pliego de condiciones

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con CYPE
Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01
Data y firmas de los anteriormente citados

Reus, Mayo de 2011

Pliego de condiciones

Generalidades

Segn figura en el Cdigo Tcnico de la Edificacin (CTE), aprobado mediante Real Decreto
314/2006, de 17 de marzo, el proyecto definir las obras proyectadas con el detalle adecuado
a sus caractersticas, de modo que pueda comprobarse que las soluciones propuestas cumplen
las exigencias bsicas del CTE y dems normativa aplicable. Esta definicin incluir, al
menos, la siguiente informacin contenida en el Pliego de Condiciones:
I.

Las caractersticas tcnicas mnimas que deben reunir los productos, equipos y
sistemas que se incorporen de forma permanente al edificio proyectado, as como sus
condiciones de suministro, las garantas de calidad y el control de recepcin que deba
realizarse. Esta informacin se encuentra en el apartado correspondiente a las
Prescripciones sobre los materiales, del presente Pliego de Condiciones.

II.

Las caractersticas tcnicas de cada unidad de obra, con indicacin de las condiciones
para su ejecucin y las verificaciones y controles a realizar para comprobar su
conformidad con lo indicado en el proyecto. Se precisarn las medidas a adoptar
durante la ejecucin de las obras y en el uso y mantenimiento del edificio, para
asegurar la compatibilidad entre los diferentes productos, elementos y sistemas
constructivos. Esta informacin se encuentra en el apartado correspondiente a las
Prescripciones en cuanto a la ejecucin por unidades de obra, del presente Pliego de
Condiciones.

III.

Las verificaciones y las pruebas de servicio que, en su caso, deban realizarse para
comprobar las prestaciones finales del edificio. Esta informacin se encuentra en el
apartado correspondiente a las Prescripciones sobre verificaciones en el edificio
terminado, del presente Pliego de Condiciones.

Pliego de condiciones

Pliego de clusulas administrativas

2.1

Disposiciones Generales

Las disposiciones de carcter general, las relativas a trabajos y materiales, as como las
recepciones de edificios y obras anejas, se regirn por lo expuesto en el Pliego de Clusulas
Particulares para contratos con la Administracin Pblica correspondiente, segn lo dispuesto
en la Ley 30/2007, de Contratos del Sector Pblico (LCSP).

2.2

Disposiciones Facultativas

2.2.1

Definicin y atribuciones de los agentes de la edificacin

Las atribuciones de los distintos agentes intervinientes en la edificacin son las reguladas por
la Ley 38/99 de Ordenacin de la Edificacin (L.O.E.).
Se definen agentes de la edificacin todas las personas, fsicas o jurdicas, que intervienen en
el proceso de la edificacin. Sus obligaciones quedan determinadas por lo dispuesto en la
L.O.E. y dems disposiciones que sean de aplicacin y por el contrato que origina su
intervencin.
Las definiciones y funciones de los agentes que intervienen en la edificacin quedan
recogidas en el captulo III "Agentes de la edificacin", considerndose:

2.2.1.1

El Promotor

Es la persona fsica o jurdica, pblica o privada, que individual o colectivamente decide,


impulsa, programa y financia, con recursos propios o ajenos, las obras de edificacin para s o
para su posterior enajenacin, entrega o cesin a terceros bajo cualquier ttulo.
Asume la iniciativa de todo el proceso de la edificacin, impulsando la gestin necesaria para
llevar a cabo la obra inicialmente proyectada, y se hace cargo de todos los costes necesarios.
Segn la legislacin vigente, a la figura del promotor se equiparan tambin las de gestor de
sociedades cooperativas, comunidades de propietarios, u otras anlogas que asumen la gestin
econmica de la edificacin.
Cuando las Administraciones pblicas y los organismos sujetos a la legislacin de contratos
de las Administraciones pblicas acten como promotores, se regirn por la legislacin de
contratos de las Administraciones pblicas y, en lo no contemplado en la misma, por las
disposiciones de la L.O.E.

2.2.1.2

El Proyectista

Es el agente que, por encargo del promotor y con sujecin a la normativa tcnica y urbanstica

Pliego de condiciones

correspondiente, redacta el proyecto.


Podrn redactar proyectos parciales del proyecto, o partes que lo complementen, otros
tcnicos, de forma coordinada con el autor de ste.
Cuando el proyecto se desarrolle o complete mediante proyectos parciales u otros documentos
tcnicos segn lo previsto en el apartado 2 del artculo 4 de la L.O.E., cada proyectista
asumir la titularidad de su proyecto.

2.2.1.3

El Constructor o Contratista

Es el agente que asume, contractualmente ante el Promotor, el compromiso de ejecutar con


medios humanos y materiales, propios o ajenos, las obras o parte de las mismas con sujecin
al Proyecto y al Contrato de obra.
CABE EFECTUAR ESPECIAL MENCIN DE QUE LA LEY SEALA COMO
RESPONSABLE EXPLCITO DE LOS VICIOS O DEFECTOS CONSTRUCTIVOS AL
CONTRATISTA GENERAL DE LA OBRA, SIN PERJUICIO DEL DERECHO DE
REPETICIN DE STE HACIA LOS SUBCONTRATISTAS.

2.2.1.4

El Director de Obra

Es el agente que, formando parte de la direccin facultativa, dirige el desarrollo de la obra en


los aspectos tcnicos, estticos, urbansticos y medioambientales, de conformidad con el
proyecto que la define, la licencia de edificacin y dems autorizaciones preceptivas, y las
condiciones del contrato, con el objeto de asegurar su adecuacin al fin propuesto.
Podrn dirigir las obras de los proyectos parciales otros tcnicos, bajo la coordinacin del
Director de Obra.

2.2.1.5

El Director de la Ejecucin de la Obra

Es el agente que, formando parte de la Direccin Facultativa, asume la funcin tcnica de


dirigir la Ejecucin Material de la Obra y de controlar cualitativa y cuantitativamente la
construccin y calidad de lo edificado. Para ello es requisito indispensable el estudio y
anlisis previo del proyecto de ejecucin una vez redactado por el Arquitecto, procediendo a
solicitarle, con antelacin al inicio de las obras, todas aquellas aclaraciones, subsanaciones o
documentos complementarios que, dentro de su competencia y atribuciones legales, estimare
necesarios para poder dirigir de manera solvente la ejecucin de las mismas.

2.2.1.6

Las entidades y los laboratorios de control de calidad de la


edificacin

Son entidades de control de calidad de la edificacin aqullas capacitadas para prestar

Pliego de condiciones

asistencia tcnica en la verificacin de la calidad del proyecto, de los materiales y de la


ejecucin de la obra y sus instalaciones de acuerdo con el proyecto y la normativa aplicable.
Son laboratorios de ensayos para el control de calidad de la edificacin los capacitados para
prestar asistencia tcnica, mediante la realizacin de ensayos o pruebas de servicio de los
materiales, sistemas o instalaciones de una obra de edificacin.

2.2.1.7

Los suministradores de productos

Se consideran suministradores de productos los fabricantes, almacenistas, importadores o


vendedores de productos de construccin.
Se entiende por producto de construccin aquel que se fabrica para su incorporacin
permanente en una obra, incluyendo materiales, elementos semielaborados, componentes y
obras o parte de las mismas, tanto terminadas como en proceso de ejecucin.

2.2.2

Agentes que intervienen en la obra segn Ley 38/99 (L.O.E.)

La relacin de agentes intervinientes se encuentra en la memoria descriptiva del proyecto.

2.2.3

Agentes en materia de seguridad y salud segn R.D. 1627/97

La relacin de agentes intervinientes en materia de seguridad y salud se encuentra en la


memoria descriptiva del proyecto.

2.2.4

Agentes en materia de gestin de residuos segn R.D. 105/08.

La relacin de agentes intervinientes en materia de gestin de residuos, se encuentra en el


Estudio de Gestin de Residuos de Construccin y Demolicin.

2.2.5

La Direccin Facultativa

En correspondencia con la L.O.E., la Direccin Facultativa est compuesta por la Direccin


de Obra y la Direccin de Ejecucin de la Obra. A la Direccin Facultativa se integrar el
Coordinador en materia de Seguridad y Salud en fase de ejecucin de la obra, en el caso de
que se haya adjudicado dicha misin a facultativo distinto de los anteriores.
Representa tcnicamente los intereses del promotor durante la ejecucin de la obra, dirigiendo
el proceso de construccin en funcin de las atribuciones profesionales de cada tcnico
participante.

Pliego de condiciones

2.2.6

Visitas facultativas

Son las realizadas a la obra de manera conjunta o individual por cualquiera de los miembros
que componen la Direccin Facultativa. La intensidad y nmero de visitas depender de los
cometidos que a cada agente le son propios, pudiendo variar en funcin de los requerimientos
especficos y de la mayor o menor exigencia presencial requerible al tcnico al efecto en cada
caso y segn cada una de las fases de la obra. Debern adaptarse al proceso lgico de
construccin, pudiendo los agentes ser o no coincidentes en la obra en funcin de la fase
concreta que se est desarrollando en cada momento y del cometido exigible a cada cual.

2.2.7

Obligaciones de los agentes intervinientes

Las obligaciones de los agentes que intervienen en la edificacin son las contenidas en los
artculos 9, 10, 11, 12, 13, 14, 15 y 16, del captulo III de la L.O.E. y dems legislacin
aplicable.

2.2.7.1

El Promotor

Ostentar sobre el solar la titularidad de un derecho que le faculte para construir en l.


Facilitar la documentacin e informacin previa necesaria para la redaccin del proyecto, as
como autorizar al Director de Obra, al Director de la Ejecucin de la Obra y al Contratista
posteriores modificaciones del mismo que fueran imprescindibles para llevar a buen fin lo
proyectado.
Elegir y contratar a los distintos agentes, con la titulacin y capacitacin profesional
necesaria, que garanticen el cumplimiento de las condiciones legalmente exigibles para
realizar en su globalidad y llevar a buen fin el objeto de lo promovido, en los plazos
estipulados y en las condiciones de calidad exigibles mediante el cumplimiento de los
requisitos bsicos estipulados para los edificios.
Gestionar y hacerse cargo de las preceptivas licencias y dems autorizaciones administrativas
procedentes que, de conformidad con la normativa aplicable, conlleva la construccin de
edificios, la urbanizacin que procediera en su entorno inmediato, la realizacin de obras que
en ellos se ejecuten y su ocupacin.
Garantizar los daos materiales que el edificio pueda sufrir, para la adecuada proteccin de
los intereses de los usuarios finales, en las condiciones legalmente establecidas, asumiendo la
responsabilidad civil de forma personal e individualizada, tanto por actos propios como por
actos de otros agentes por los que, con arreglo a la legislacin vigente, se deba responder.
La suscripcin obligatoria de un seguro, de acuerdo a las normas concretas fijadas al efecto,
que cubra los daos materiales que ocasionen en el edificio el incumplimiento de las
condiciones de habitabilidad en tres aos o que afecten a la seguridad estructural en el plazo
de diez aos, con especial mencin a las viviendas individuales en rgimen de autopromocin,
que se regirn por lo especialmente legislado al efecto.

Pliego de condiciones

Contratar a los tcnicos redactores del preceptivo Estudio de Seguridad y Salud o Estudio
Bsico, en su caso, al igual que a los tcnicos coordinadores en la materia en la fase que
corresponda, todo ello segn lo establecido en el R.D. 1627/97, de 24 de octubre, por el que
se establecen las disposiciones mnimas en materia de seguridad y salud en las obras de
construccin.
El Promotor no podr dar orden de inicio de las obras hasta que el Contratista haya redactado
su Plan de Seguridad y, adems, ste haya sido aprobado por el Coordinador en Materia de
Seguridad y Salud en fase de Ejecucin de la obra, dejando constancia expresa en el Acta de
Aprobacin realizada al efecto.
Efectuar el denominado Aviso Previo a la autoridad laboral competente, haciendo constar los
datos de la obra, redactndolo de acuerdo a lo especificado en el Anexo III del RD 1627/97.
Copia del mismo deber exponerse en la obra de forma visible, actualizndolo si fuese
necesario.
Suscribir el acta de recepcin final de las obras, una vez concluidas stas, haciendo constar la
aceptacin de las obras, que podr efectuarse con o sin reservas y que deber abarcar la
totalidad de las obras o fases completas. En el caso de hacer mencin expresa a reservas para
la recepcin, debern mencionarse de manera detallada las deficiencias y se deber hacer
constar el plazo en que debern quedar subsanados los defectos observados.
Entregar al adquirente y usuario inicial, en su caso, el denominado Libro del Edificio que
contiene el manual de uso y mantenimiento del mismo y dems documentacin de obra
ejecutada, o cualquier otro documento exigible por las Administraciones competentes.

2.2.7.2

El Proyectista

Redactar el proyecto por encargo del Promotor, con sujecin a la normativa urbanstica y
tcnica en vigor y conteniendo la documentacin necesaria para tramitar tanto la licencia de
obras y dems permisos administrativos -proyecto bsico- como para ser interpretada y poder
ejecutar totalmente la obra, entregando al Promotor las copias autorizadas correspondientes,
debidamente visadas por su colegio profesional.
Definir el concepto global del proyecto de ejecucin con el nivel de detalle grfico y escrito
suficiente y calcular los elementos fundamentales del edificio, en especial la cimentacin y la
estructura. Concretar en el Proyecto el emplazamiento de cuartos de mquinas, de contadores,
hornacinas, espacios asignados para subida de conductos, reservas de huecos de ventilacin,
alojamiento de sistemas de telecomunicacin y, en general, de aquellos elementos necesarios
en el edificio para facilitar las determinaciones concretas y especificaciones detalladas que
son cometido de los proyectos parciales, debiendo stos adaptarse al Proyecto de Ejecucin,
no pudiendo contravenirlo en modo alguno. Deber entregarse necesariamente un ejemplar
del proyecto complementario al Arquitecto antes del inicio de las obras o instalaciones
correspondientes.
Acordar con el Promotor la contratacin de colaboraciones parciales de otros tcnicos
profesionales.

Pliego de condiciones

Facilitar la colaboracin necesaria para que se produzca la adecuada coordinacin con los
proyectos parciales exigibles por la legislacin o la normativa vigente y que sea necesario
incluir para el desarrollo adecuado del proceso edificatorio, que debern ser redactados por
tcnicos competentes, bajo su responsabilidad y suscritos por persona fsica. Los proyectos
parciales sern aquellos redactados por otros tcnicos cuya competencia puede ser distinta e
incompatible con las competencias del Arquitecto y, por tanto, de exclusiva responsabilidad
de stos.
Elaborar aquellos proyectos parciales o estudios complementarios exigidos por la legislacin
vigente en los que es legalmente competente para su redaccin, excepto declinacin expresa
del Arquitecto y previo acuerdo con el Promotor, pudiendo exigir la compensacin econmica
en concepto de cesin de derechos de autor y de la propiedad intelectual si se tuviera que
entregar a otros tcnicos, igualmente competentes para realizar el trabajo, documentos o
planos del proyecto por l redactado, en soporte papel o informtico.
Ostentar la propiedad intelectual de su trabajo, tanto de la documentacin escrita como de los
clculos de cualquier tipo, as como de los planos contenidos en la totalidad del proyecto y
cualquiera de sus documentos complementarios.

2.2.7.3

El Constructor o Contratista

Tener la capacitacin profesional o titulacin que habilita para el cumplimiento de las


condiciones legalmente exigibles para actuar como constructor.
Organizar los trabajos de construccin para cumplir con los plazos previstos, de acuerdo al
correspondiente Plan de Obra, efectuando las instalaciones provisionales y disponiendo de los
medios auxiliares necesarios.
Comunicar a la autoridad laboral competente la apertura del centro de trabajo en la que
incluir el Plan de Seguridad y Salud al que se refiere el artculo 7 del RD 1627/97 de 24 de
octubre.
Adoptar todas las medidas preventivas que cumplan los preceptos en materia de Prevencin
de Riesgos laborales y Seguridad y Salud que establece la legislacin vigente, redactando el
correspondiente Plan de Seguridad y ajustndose al cumplimiento estricto y permanente de lo
establecido en el Estudio de Seguridad y Salud, disponiendo de todos los medios necesarios y
dotando al personal del equipamiento de seguridad exigibles, as como cumplir las rdenes
efectuadas por el Coordinador en materia de Seguridad y Salud en la fase de Ejecucin de la
obra.
Supervisar de manera continuada el cumplimiento de las normas de seguridad, tutelando las
actividades de los trabajadores a su cargo y, en su caso, relevando de su puesto a todos
aquellos que pudieran menoscabar las condiciones bsicas de seguridad personales o
generales, por no estar en las condiciones adecuadas.
Examinar la documentacin aportada por los tcnicos redactores correspondientes, tanto del
Proyecto de Ejecucin como de los proyectos complementarios, as como del Estudio de
Seguridad y Salud, verificando que le resulta suficiente para la comprensin de la totalidad de

10

Pliego de condiciones

la obra contratada o, en caso contrario, solicitando las aclaraciones pertinentes


Facilitar la labor de la Direccin Facultativa, suscribiendo el Acta de Replanteo, ejecutando
las obras con sujecin al Proyecto de Ejecucin que deber haber examinado previamente, a
la legislacin aplicable, a las Instrucciones del Arquitecto Director de Obra y del Director de
la Ejecucin Material de la Obra, a fin de alcanzar la calidad exigida en el proyecto.
Efectuar las obras siguiendo los criterios al uso que son propios de la correcta construccin,
que tiene la obligacin de conocer y poner en prctica, as como de las leyes generales de los
materiales o lex artis, an cuando estos criterios no estuvieran especficamente reseados en
su totalidad en la documentacin de proyecto. A tal efecto, ostenta la jefatura de todo el
personal que intervenga en la obra y coordina las tareas de los subcontratistas.
Disponer de los medios materiales y humanos que la naturaleza y entidad de la obra
impongan, disponiendo del nmero adecuado de oficiales, suboficiales y peones que la obra
requiera en cada momento, bien por personal propio o mediante subcontratistas al efecto,
procediendo a solapar aquellos oficios en la obra que sean compatibles entre s y que permitan
acometer distintos trabajos a la vez sin provocar interferencias, contribuyendo con ello a la
agilizacin y finalizacin de la obra dentro de los plazos previstos.
Ordenar y disponer en cada momento de personal suficiente a su cargo para que efecte las
actuaciones pertinentes para ejecutar las obras con solvencia, diligentemente y sin
interrupcin, programndolas de manera coordinada con el Arquitecto Tcnico o Aparejador,
Director de Ejecucin Material de la Obra.
Supervisar personalmente y de manera continuada y completa la marcha de las obras, que
debern transcurrir sin dilacin y con adecuado orden y concierto, as como responder
directamente de los trabajos efectuados por sus trabajadores subordinados, exigindoles el
continuo autocontrol de los trabajos que efecten, y ordenando la modificacin de todas
aquellas tareas que se presenten mal efectuadas.
Asegurar la idoneidad de todos y cada uno de los materiales utilizados y elementos
constructivos, comprobando los preparados en obra y rechazando, por iniciativa propia o por
prescripcin facultativa del Director de la Ejecucin de la obra, los suministros de material o
prefabricados que no cuenten con las garantas, documentacin mnima exigible o
documentos de idoneidad requeridos por las normas de aplicacin, debiendo recabar de la
Direccin Facultativa la informacin que necesite para cumplir adecuadamente su cometido.
Dotar de material, maquinaria y utillajes adecuados a los operarios que intervengan en la obra,
para efectuar adecuadamente las instalaciones necesarias y no menoscabar con la puesta en
obra las caractersticas y naturaleza de los elementos constructivos que componen el edificio
una vez finalizado.
Poner a disposicin del Arquitecto Tcnico o Aparejador los medios auxiliares y personal
necesario para efectuar las pruebas pertinentes para el Control de Calidad, recabando de dicho
tcnico el plan a seguir en cuanto a las tomas de muestras, traslados, ensayos y dems
actuaciones necesarias.
Cuidar de que el personal de la obra guarde el debido respeto a la Direccin Facultativa.

11

Pliego de condiciones

Auxiliar al Director de la Ejecucin de la Obra en los actos de replanteo y firmar


posteriormente y una vez finalizado ste, el acta correspondiente de inicio de obra, as como
la de recepcin final.
Facilitar a los Arquitectos Directores de Obra los datos necesarios para la elaboracin de la
documentacin final de obra ejecutada.
Suscribir las garantas de obra que se sealan en el Artculo 19 de la Ley de Ordenacin de la
Edificacin y que, en funcin de su naturaleza, alcanzan perodos de 1 ao (daos por
defectos de terminacin o acabado de las obras), 3 aos (daos por defectos o vicios de
elementos constructivos o de instalaciones que afecten a la habitabilidad) o 10 aos (daos en
cimentacin o estructura que comprometan directamente la resistencia mecnica y la
estabilidad del edificio).

2.2.7.4

El Director de Obra

Dirigir la obra coordinndola con el Proyecto de Ejecucin, facilitando su interpretacin


tcnica, econmica y esttica a los agentes intervinientes en el proceso constructivo.
Detener la obra por causa grave y justificada, que se deber hacer constar necesariamente en
el Libro de rdenes y Asistencias, dando cuenta inmediata al Promotor.
Redactar las modificaciones, ajustes, rectificaciones o planos complementarios que se
precisen para el adecuado desarrollo de las obras. Es facultad expresa y nica la redaccin de
aquellas modificaciones o aclaraciones directamente relacionadas con la adecuacin de la
cimentacin y de la estructura proyectadas a las caractersticas geotcnicas del terreno; el
clculo o reclculo del dimensionado y armado de todos y cada uno de los elementos
principales y complementarios de la cimentacin y de la estructura vertical y horizontal; los
que afecten sustancialmente a la distribucin de espacios y las soluciones de fachada y
cubierta y dimensionado y composicin de huecos, as como la modificacin de los materiales
previstos.
Asesorar al Director de la Ejecucin de la Obra en aquellas aclaraciones y dudas que pudieran
acontecer para el correcto desarrollo de la misma, en lo que respecta a las interpretaciones de
las especificaciones de proyecto.
Asistir a las obras a fin de resolver las contingencias que se produzcan para asegurar la
correcta interpretacin y ejecucin del proyecto, as como impartir las soluciones aclaratorias
que fueran necesarias, consignando en el Libro de Ordenes y Asistencias las instrucciones
precisas que se estimara oportunas resear para la correcta interpretacin de lo proyectado, sin
perjuicio de efectuar todas las aclaraciones y rdenes verbales que estimare oportuno.
Firmar el Acta de replanteo o de comienzo de obra y el Certificado Final de Obra, as como
firmar el visto bueno de las certificaciones parciales referidas al porcentaje de obra efectuada
y, en su caso y a instancias del Promotor, la supervisin de la documentacin que se le
presente relativa a las unidades de obra realmente ejecutadas previa a su liquidacin final,
todo ello con los visados que en su caso fueran preceptivos.

12

Pliego de condiciones

Informar puntualmente al Promotor de aquellas modificaciones sustanciales que, por razones


tcnicas o normativas, conllevan una variacin de lo construido con respecto al proyecto
bsico y de ejecucin y que afecten o puedan afectar al contrato suscrito entre el promotor y
los destinatarios finales de las viviendas.
Redactar la documentacin final de obra, en lo que respecta a la documentacin grfica y
escrita del proyecto ejecutado, incorporando las modificaciones efectuadas. Para ello, los
tcnicos redactores de proyectos y/o estudios complementarios debern obligatoriamente
entregarle la documentacin final en la que se haga constar el estado final de las obras y/o
instalaciones por ellos redactadas, supervisadas y realmente ejecutadas, siendo
responsabilidad de los firmantes la veracidad y exactitud de los documentos presentados.
Al Proyecto Final de Obra se anexar el Acta de Recepcin Final; la relacin identificativa de
los agentes que han intervenido en el proceso de edificacin, incluidos todos los
subcontratistas y oficios intervinientes; las instrucciones de Uso y Mantenimiento del Edificio
y de sus instalaciones, de conformidad con la normativa que le sea de aplicacin.
La documentacin a la que se hace referencia en los dos apartados anteriores es parte
constituyente del Libro del Edificio y el Promotor deber entregar una copia completa a los
usuarios finales del mismo que, en el caso de edificios de viviendas plurifamiliares, se
materializa en un ejemplar que deber ser custodiado por el Presidente de la Comunidad de
Propietarios o por el Administrador, siendo stos los responsables de divulgar al resto de
propietarios su contenido y de hacer cumplir los requisitos de mantenimiento que constan en
la citada documentacin.
Adems de todas las facultades que corresponden al Arquitecto Director de Obra, expresadas
en los artculos precedentes, es misin especfica suya la direccin mediata, denominada alta
direccin en lo que al cumplimiento de las directrices generales del proyecto se refiere, y a la
adecuacin de lo construido a ste.
Cabe sealar expresamente que la resistencia al cumplimiento de las rdenes de los
Arquitectos Directores de Obra en su labor de alta direccin se considerar como falta grave
y, en caso de que, a su juicio, el incumplimiento de lo ordenado pusiera en peligro la obra o
las personas que en ella trabajan, podr recusar al Contratista y/o acudir a las autoridades
judiciales, siendo responsable el Contratista de las consecuencias legales y econmicas.

2.2.7.5

El Director de la Ejecucin de la Obra

Corresponde al Arquitecto Tcnico o Aparejador, segn se establece en el Artculo 13 de la


LOE y dems legislacin vigente al efecto, las atribuciones competenciales y obligaciones
que se sealan a continuacin:
La Direccin inmediata de la Obra.
Verificar personalmente la recepcin a pi de obra, previo a su acopio o colocacin definitiva,
de todos los productos y materiales suministrados necesarios para la ejecucin de la obra,
comprobando que se ajustan con precisin a las determinaciones del proyecto y a las normas
exigibles de calidad, con la plena potestad de aceptacin o rechazo de los mismos en caso de

13

Pliego de condiciones

que lo considerase oportuno y por causa justificada, ordenando la realizacin de pruebas y


ensayos que fueran necesarios.
Dirigir la ejecucin material de la obra de acuerdo con las especificaciones de la memoria y
de los planos del Proyecto, as como, en su caso, con las instrucciones complementarias
necesarias que recabara del Director de Obra.
Anticiparse con la antelacin suficiente a las distintas fases de la puesta en obra, requiriendo
las aclaraciones al Arquitecto o Arquitectos Directores de Obra que fueran necesarias y
planificando de manera anticipada y continuada con el Contratista principal y los
subcontratistas los trabajos a efectuar.
Comprobar los replanteos, los materiales, hormigones y dems productos suministrados,
exigiendo la presentacin de los oportunos certificados de idoneidad de los mismos.
Verificar la correcta ejecucin y disposicin de los elementos constructivos y de las
instalaciones, extendindose dicho cometido a todos los elementos de cimentacin y
estructura horizontal y vertical, con comprobacin de sus especificaciones concretas de
dimensionado de elementos, tipos de viguetas y adecuacin a ficha tcnica homologada,
dimetros nominales, longitudes de anclaje y adecuados solape y doblado de barras.
Observancia de los tiempos de encofrado y desencofrado de vigas, pilares y forjados
sealados por la Instruccin del Hormign vigente y de aplicacin.
Comprobacin del correcto dimensionado de rampas y escaleras y de su adecuado trazado y
replanteo con acuerdo a las pendientes, desniveles proyectados y al cumplimiento de todas las
normativas que son de aplicacin; a dimensiones parciales y totales de elementos, a su forma
y geometra especfica, as como a las distancias que deben guardarse entre ellos, tanto en
horizontal como en vertical.
Verificacin de la adecuada puesta en obra de fbricas y cerramientos, a su correcta y
completa trabazn y, en general, a lo que atae a la ejecucin material de la totalidad de la
obra y sin excepcin alguna, de acuerdo a los criterios y leyes de los materiales y de la
correcta construccin (lex artis) y a las normativas de aplicacin.
Asistir a la obra con la frecuencia, dedicacin y diligencia necesarias para cumplir
eficazmente la debida supervisin de la ejecucin de la misma en todas sus fases, desde el
replanteo inicial hasta la total finalizacin del edificio, dando las rdenes precisas de
ejecucin al Contratista y, en su caso, a los subcontratistas.
Consignar en el Libro de Ordenes y Asistencias las instrucciones precisas que considerara
oportuno resear para la correcta ejecucin material de las obras.
Supervisar posteriormente el correcto cumplimiento de las rdenes previamente efectuadas y
la adecuacin de lo realmente ejecutado a lo ordenado previamente.
Verificar el adecuado trazado de instalaciones, conductos, acometidas, redes de evacuacin y
su dimensionado, comprobando su idoneidad y ajuste tanto a la especificaciones del proyecto
de ejecucin como de los proyectos parciales, coordinando dichas actuaciones con los
tcnicos redactores correspondientes.

14

Pliego de condiciones

Detener la Obra si, a su juicio, existiera causa grave y justificada, que se deber hacer constar
necesariamente en el Libro de Ordenes y Asistencias, dando cuenta inmediata a los
Arquitectos Directores de Obra que debern necesariamente corroborarla para su plena
efectividad, y al Promotor.
Supervisar las pruebas pertinentes para el Control de Calidad, respecto a lo especificado por la
normativa vigente, en cuyo cometido y obligaciones tiene legalmente competencia exclusiva,
programando bajo su responsabilidad y debidamente coordinado y auxiliado por el
Contratista, las tomas de muestras, traslados, ensayos y dems actuaciones necesarias de
elementos estructurales, as como las pruebas de estanqueidad de fachadas y de sus elementos,
de cubiertas y sus impermeabilizaciones, comprobando la eficacia de las soluciones.
Informar con prontitud a los Arquitectos Directores de Obra de los resultados de los Ensayos
de Control conforme se vaya teniendo conocimiento de los mismos, proponindole la
realizacin de pruebas complementarias en caso de resultados adversos.
Tras la oportuna comprobacin, emitir las certificaciones parciales o totales relativas a las
unidades de obra realmente ejecutadas, con los visados que en su caso fueran preceptivos.
Colaborar activa y positivamente con los restantes agentes intervinientes, sirviendo de nexo
de unin entre stos, el Contratista, los Subcontratistas y el personal de la obra.
Elaborar y suscribir responsablemente la documentacin final de obra relativa a los resultados
del Control de Calidad y, en concreto, a aquellos ensayos y verificaciones de ejecucin de
obra realizados bajo su supervisin relativos a los elementos de la cimentacin, muros y
estructura, a las pruebas de estanqueidad y escorrenta de cubiertas y de fachadas, a las
verificaciones del funcionamiento de las instalaciones de saneamiento y desages de pluviales
y dems aspectos sealados en la normativa de Control de Calidad.
Suscribir conjuntamente el Certificado Final de Obra, acreditando con ello su conformidad a
la correcta ejecucin de las obras y a la comprobacin y verificacin positiva de los ensayos y
pruebas realizadas.
Si se hiciera caso omiso de las rdenes efectuadas por el Arquitecto Tcnico, Director de la
Ejecucin de las Obras, se considerara como falta grave y, en caso de que, a su juicio, el
incumplimiento de lo ordenado pusiera en peligro la obra o las personas que en ella trabajan,
podr acudir a las autoridades judiciales, siendo responsable el Contratista de las
consecuencias legales y econmicas.

2.2.7.6

Las entidades y los laboratorios de control de calidad de la


edificacin

Prestar asistencia tcnica y entregar los resultados de su actividad al agente autor del encargo
y, en todo caso, al director de la ejecucin de las obras.
Justificar la capacidad suficiente de medios materiales y humanos necesarios para realizar
adecuadamente los trabajos contratados, en su caso, a travs de la correspondiente
acreditacin oficial otorgada por las Comunidades Autnomas con competencia en la materia.

15

Pliego de condiciones

2.2.7.7

Los suministradores de productos

Realizar las entregas de los productos de acuerdo con las especificaciones del pedido,
respondiendo de su origen, identidad y calidad, as como del cumplimiento de las exigencias
que, en su caso, establezca la normativa tcnica aplicable.
Facilitar, cuando proceda, las instrucciones de uso y mantenimiento de los productos
suministrados, as como las garantas de calidad correspondientes, para su inclusin en la
documentacin de la obra ejecutada.

2.2.7.8

Los propietarios y los usuarios

Son obligaciones de los propietarios conservar en buen estado la edificacin mediante un


adecuado uso y mantenimiento, as como recibir, conservar y transmitir la documentacin de
la obra ejecutada y los seguros y garantas con que sta cuente.
Son obligaciones de los usuarios sean o no propietarios, la utilizacin adecuada de los
edificios o de parte de los mismos de conformidad con las instrucciones de uso y
mantenimiento contenidas en la documentacin de la obra ejecutada.

2.2.8

Documentacin final de obra: Libro del Edificio

De acuerdo al Artculo 7 de la Ley de Ordenacin de la Edificacin, una vez finalizada la


obra, el proyecto con la incorporacin, en su caso, de las modificaciones debidamente
aprobadas, ser facilitado al promotor por el Director de Obra para la formalizacin de los
correspondientes trmites administrativos.
A dicha documentacin se adjuntar, al menos, el acta de recepcin, la relacin identificativa
de los agentes que han intervenido durante el proceso de edificacin, as como la relativa a las
instrucciones de uso y mantenimiento del edificio y sus instalaciones, de conformidad con la
normativa que le sea de aplicacin.
Toda la documentacin a que hacen referencia los apartados anteriores, que constituir el
Libro del Edificio, ser entregada a los usuarios finales del edificio.

2.2.8.1

Los propietarios y los usuarios

Son obligaciones de los propietarios conservar en buen estado la edificacin mediante un


adecuado uso y mantenimiento, as como recibir, conservar y transmitir la documentacin de
la obra ejecutada y los seguros y garantas con que sta cuente.
Son obligaciones de los usuarios sean o no propietarios, la utilizacin adecuada de los
edificios o de parte de los mismos de conformidad con las instrucciones de uso y

16

Pliego de condiciones

mantenimiento contenidas en la documentacin de la obra ejecutada.

2.3

Disposiciones Econmicas

Se regirn por lo expuesto en el Pliego de Clusulas Administrativas Particulares para


contratos con la Administracin Pblica correspondiente, segn lo dispuesto en la Ley
30/2007, de Contratos del Sector Pblico (LCSP).

Pliego de condiciones tcnicas particulares

3.1

Prescripciones sobre los materiales

Para facilitar la labor a realizar, por parte del Director de la Ejecucin de la Obra, para el
control de recepcin en obra de los productos, equipos y sistemas que se suministren a la obra
de acuerdo con lo especificado en el artculo 7.2. del CTE, en el presente proyecto se
especifican las caractersticas tcnicas que debern cumplir los productos, equipos y sistemas
suministrados.
Los productos, equipos y sistemas suministrados debern cumplir las condiciones que sobre
ellos se especifican en los distintos documentos que componen el Proyecto. Asimismo, sus
calidades sern acordes con las distintas normas que sobre ellos estn publicadas y que
tendrn un carcter de complementariedad a este apartado del Pliego. Tendrn preferencia en
cuanto a su aceptabilidad aquellos materiales que estn en posesin de Documento de
Idoneidad Tcnica que avale sus cualidades, emitido por Organismos Tcnicos reconocidos.
Este control de recepcin en obra de productos, equipos y sistemas comprender segn el
artculo 7.2. del CTE:
I. El control de la documentacin de los suministros, realizado de acuerdo con el artculo
7.2.1.
II. El control mediante distintivos de calidad o evaluaciones tcnicas de idoneidad, segn
el artculo 7.2.2.
III. El control mediante ensayos, conforme al artculo 7.2.3.
Por parte del Constructor o Contratista debe existir obligacin de comunicar a los
suministradores de productos las cualidades que se exigen para los distintos materiales,
aconsejndose que previamente al empleo de los mismos se solicite la aprobacin del Director
de Ejecucin de la Obra y de las entidades y laboratorios encargados del control de calidad de
la obra.
El Contratista ser responsable de que los materiales empleados cumplan con las condiciones
exigidas, independientemente del nivel de control de calidad que se establezca para la
aceptacin de los mismos.
El Contratista notificar al Director de Ejecucin de la Obra, con suficiente antelacin, la

17

Pliego de condiciones

procedencia de los materiales que se proponga utilizar, aportando, cuando as lo solicite el


Director de Ejecucin de la Obra, las muestras y datos necesarios para decidir acerca de su
aceptacin.
Estos materiales sern reconocidos por el Director de Ejecucin de la Obra antes de su empleo
en obra, sin cuya aprobacin no podrn ser acopiados en obra ni se podr proceder a su
colocacin. As mismo, an despus de colocados en obra, aquellos materiales que presenten
defectos no percibidos en el primer reconocimiento, siempre que vaya en perjuicio del buen
acabado de la obra, sern retirados de la obra. Todos los gastos que ello ocasionase sern a
cargo del Contratista.
El hecho de que el Contratista subcontrate cualquier partida de obra no le exime de su
responsabilidad.
La simple inspeccin o examen por parte de los Tcnicos no supone la recepcin absoluta de
los mismos, siendo los oportunos ensayos los que determinen su idoneidad, no extinguindose
la responsabilidad contractual del Contratista a estos efectos hasta la recepcin definitiva de la
obra.

3.1.1

Garantas de calidad (Marcado CE)

El trmino producto de construccin queda definido como cualquier producto fabricado para
su incorporacin, con carcter permanente, a las obras de edificacin e ingeniera civil que
tengan incidencia sobre los siguientes requisitos esenciales:
I. Resistencia mecnica y estabilidad.
II. Seguridad en caso de incendio.
III. Higiene, salud y medio ambiente.
IV. Seguridad de utilizacin.
V. Proteccin contra el ruido.
VI. Ahorro de energa y aislamiento trmico.
El marcado CE de un producto de construccin indica:
I. Que ste cumple con unas determinadas especificaciones tcnicas relacionadas con los
requisitos esenciales contenidos en las Normas Armonizadas (EN) y en las Guas
DITE (Guas para el Documento de Idoneidad Tcnica Europeo).
II. Que se ha cumplido el sistema de evaluacin de la conformidad establecido por la
correspondiente Decisin de la Comisin Europea.
Siendo el fabricante el responsable de su fijacin y la Administracin competente en materia
de industria la que vele por la correcta utilizacin del marcado CE.
Es obligacin del Director de la Ejecucin de la Obra verificar si los productos que entran en

18

Pliego de condiciones

la obra estn afectados por el cumplimiento del sistema del marcado CE y, en caso de ser as,
si se cumplen las condiciones establecidas en el Real Decreto 1630/1992 por el que se
transpone a nuestro ordenamiento legal la Directiva de Productos de Construccin
89/106/CEE.
El marcado CE se materializa mediante el smbolo CE acompaado de una informacin
complementaria.
El fabricante debe cuidar de que el marcado CE figure, por orden de preferencia:
I. En el producto propiamente dicho.
II. En una etiqueta adherida al mismo.
III. En su envase o embalaje.
IV. En la documentacin comercial que le acompaa.
Las letras del smbolo CE se realizan segn el dibujo adjunto y deben tener una dimensin
vertical no inferior a 5 mm.

Adems del smbolo CE deben estar situadas en una de las cuatro posibles localizaciones una
serie de inscripciones complementarias, cuyo contenido especfico se determina en las normas
armonizadas y Guas DITE para cada familia de productos, entre las que se incluyen:
I. El nmero de identificacin del organismo notificado (cuando proceda)
II. El nombre comercial o la marca distintiva del fabricante
III. La direccin del fabricante
IV. El nombre comercial o la marca distintiva de la fbrica
V. Las dos ltimas cifras del ao en el que se ha estampado el marcado en el producto
VI. El nmero del certificado CE de conformidad (cuando proceda)
VII. El nmero de la norma armonizada y en caso de verse afectada por varias los nmeros
de todas ellas
VIII. La designacin del producto, su uso previsto y su designacin normalizada
IX. Informacin adicional que permita identificar las caractersticas del producto
atendiendo a sus especificaciones tcnicas

19

Pliego de condiciones

Las inscripciones complementarias del marcado CE no tienen por qu tener un formato, tipo
de letra, color o composicin especial, debiendo cumplir nicamente las caractersticas
reseadas anteriormente para el smbolo.

20

Pliego de condiciones

Ejemplo de marcado CE:

Smbolo
0123

N de organismo notificado

Empresa

Nombre del fabricante

Direccin registrada

Direccin del fabricante

Fbrica

Nombre de la fbrica

Ao

Dos ltimas cifras del ao

0123-CPD-0456

N del certificado de conformidad CE

EN 197-1

Norma armonizada

CEM I 42,5 R

Designacin normalizada

Lmite de cloruros (%)


Informacin adicional
Lmite de prdida por calcinacin de cenizas (%)
Nomenclatura normalizada de aditivos
Dentro de las caractersticas del producto podemos encontrar que alguna de ellas presente la
mencin "Prestacin no determinada" (PND).
La opcin PND es una clase que puede ser considerada si al menos un estado miembro no
tiene requisitos legales para una determinada caracterstica y el fabricante no desea facilitar el
valor de esa caracterstica.

3.1.2
3.1.2.1

Aislantes e impermeabilizantes
Aislantes de lana mineral

3.1.2.1.1 Condiciones de suministro


I. Los aislantes se deben suministrar en forma de paneles enrollados o mantas, envueltos
en films plsticos.
II. Los paneles o mantas se agruparn formando palets para su mejor almacenamiento y
transporte.
III. En caso de desmontar los palets, los paquetes resultantes deben transportarse de forma
que no se desplacen por la caja del transporte.
IV. Se procurar no aplicar pesos elevados sobre los mismos, para evitar su deterioro.

21

Pliego de condiciones

3.1.2.1.2 Recepcin y control


I. Inspecciones:
a. Este material debe estar provisto del marcado CE, que es una indicacin de que
cumple los requisitos esenciales y ha sido objeto de un procedimiento de
evaluacin de la conformidad.
II. Ensayos:
b. La comprobacin de las propiedades o caractersticas exigibles a este material
se realiza segn la normativa vigente.

3.1.2.1.3 Conservacin, almacenamiento y manipulacin


I. Conservar y almacenar preferentemente en el pale original, protegidos del sol y de la
intemperie, salvo cuando est prevista su aplicacin.
II. Los pales completos pueden almacenarse a la intemperie por un periodo limitado de
tiempo.
III. Los paneles deben almacenarse bajo cubierto, sobre superficies planas y limpias.
IV. Siempre que se manipule el panel de lana de roca se har con guantes.
V. Bajo ningn concepto debe emplearse para cortar el producto maquinaria que pueda
diseminar polvo, ya que ste produce irritacin de garganta y de ojos.

3.1.2.1.4 Recomendaciones para su uso en obra


VI. En aislantes utilizados en cubiertas, se recomienda evitar su aplicacin cuando las
condiciones climatolgicas sean adversas, en particular cuando est nevando o haya
nieve o hielo sobre la cubierta, cuando llueva o la cubierta est mojada, o cuando sople
viento fuerte.
VII. Los productos deben colocarse siempre secos.

3.2

Prescripciones en cuanto a la Ejecucin por Unidad de Obra

Las prescripciones para la ejecucin de cada una de las diferentes unidades de obra se
organizan en los siguientes apartados:
MEDIDAS PARA ASEGURAR LA COMPATIBILIDAD ENTRE LOS DIFERENTES
PRODUCTOS, ELEMENTOS Y SISTEMAS CONSTRUCTIVOS QUE COMPONEN
LA UNIDAD DE OBRA.
Se especifican, en caso de que existan, las posibles incompatibilidades, tanto fsicas como

22

Pliego de condiciones

qumicas, entre los diversos componentes que componen la unidad de obra, o entre el soporte
y los componentes.
CARACTERSTICAS TCNICAS.
Se describe la unidad de obra, detallando de manera pormenorizada los elementos que la
componen, con la nomenclatura especfica correcta de cada uno de ellos, de acuerdo a los
criterios que marca la propia normativa.
NORMATIVA DE APLICACIN.
Se especifican las normas que afectan a la realizacin de la unidad de obra.
CRITERIO DE MEDICIN EN PROYECTO.
Indica cmo se ha medido la unidad de obra en la fase de redaccin del proyecto, medicin
que luego ser comprobada en obra.
CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN
DE LAS UNIDADES DE OBRA.
Antes de iniciarse los trabajos de ejecucin de cada una de las unidades de obra, el Director
de la Ejecucin de la Obra habr recepcionado los materiales y los certificados acreditativos
exigibles, en base a lo establecido en la documentacin pertinente por el tcnico redactor del
proyecto. Ser preceptiva la aceptacin previa por parte del Director de la Ejecucin de la
Obra de todos los materiales que constituyen la unidad de obra.
As mismo, se realizarn una serie de comprobaciones previas sobre las condiciones del
soporte, las condiciones ambientales del entorno, y la cualificacin de la mano de obra, en su
caso.
DEL SOPORTE.
Se establecen una serie de requisitos previos sobre el estado de las unidades de obra
realizadas previamente, que pueden servir de soporte a la nueva unidad de obra.
AMBIENTALES.
En determinadas condiciones climticas (viento, lluvia, humedad, etc.) no podrn iniciarse
los trabajos de ejecucin de la unidad de obra, debern interrumpirse o ser necesario
adoptar una serie de medidas protectoras.
DEL CONTRATISTA.
En algunos casos, ser necesaria la presentacin al Director de la Ejecucin de la Obra de
una serie de documentos por parte del Contratista, que acrediten su cualificacin, o la de
la empresa por l subcontratada, para realizar cierto tipo de trabajos. Por ejemplo la puesta
en obra de sistemas constructivos en posesin de un Documento de Idoneidad Tcnica
(DIT), debern ser realizados por la propia empresa propietaria del DIT, o por empresas
especializadas y cualificadas, reconocidas por sta y bajo su control tcnico.
PROCESO DE EJECUCIN.
En este apartado se desarrolla el proceso de ejecucin de cada unidad de obra, asegurando en
cada momento las condiciones que permitan conseguir el nivel de calidad previsto para cada
elemento constructivo en particular.
FASES DE EJECUCIN.

23

Pliego de condiciones

Se enumeran, por orden de ejecucin, las fases de las que consta el proceso de ejecucin
de la unidad de obra.
CONDICIONES DE TERMINACIN.
En algunas unidades de obra se hace referencia a las condiciones en las que debe
finalizarse una determinada unidad de obra, para que no interfiera negativamente en el
proceso de ejecucin del resto de unidades.
Una vez terminados los trabajos correspondientes a la ejecucin de cada unidad de obra, el
Contratista retirar los medios auxiliares y proceder a la limpieza del elemento realizado y de
las zonas de trabajo, recogiendo los restos de materiales y dems residuos originados por las
operaciones realizadas para ejecutar la unidad de obra, siendo todos ellos clasificados,
cargados y transportados a centro de reciclaje, vertedero especfico o centro de acogida o
transferencia.
PRUEBAS DE SERVICIO
En aquellas unidades de obra que sea necesario, se indican las pruebas de servicio a realizar
por el propio Contratista o empresa instaladora, cuyo coste se encuentra incluido en el propio
precio de la unidad de obra.
Aquellas otras pruebas de servicio o ensayos que no estn incluidos en el precio de la unidad
de obra, y que es obligatoria su realizacin por medio de laboratorios acreditados se
encuentran detalladas y presupuestadas, en el correspondiente captulo X de Control de
Calidad y Ensayos, del Presupuesto de Ejecucin Material (PEM).
Por ejemplo, esto es lo que ocurre en la unidad de obra ADP010, donde se indica que no est
incluido en el precio de la unidad de obra el coste del ensayo de densidad y humedad "in situ".
CONSERVACIN Y MANTENIMIENTO
En algunas unidades de obra se establecen las condiciones en que deben protegerse para la
correcta conservacin y mantenimiento en obra, hasta su recepcin final.
COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN
PROYECTO Y ABONO DE LAS MISMAS.
Indica cmo se comprobarn en obra las mediciones de Proyecto, una vez superados todos los
controles de calidad y obtenida la aceptacin final por parte del Director de Ejecucin de la
Obra.
La medicin del nmero de unidades de obra que ha de abonarse se realizar, en su caso, de
acuerdo con las normas que establece este captulo, tendr lugar en presencia y con
intervencin del Contratista, entendiendo que ste renuncia a tal derecho si, avisado
oportunamente, no compareciese a tiempo. En tal caso, ser vlido el resultado que el Director
de Ejecucin de la Obra consigne.
Todas las unidades de obra se abonarn a los precios establecidos en el Presupuesto. Dichos
precios se abonarn por las unidades terminadas y ejecutadas con arreglo al presente Pliego de
Condiciones Tcnicas Particulares y Prescripciones en cuanto a la Ejecucin por Unidad de
Obra.

24

Pliego de condiciones

Estas unidades comprenden el suministro, cnones, transporte, manipulacin y empleo de los


materiales, maquinaria, medios auxiliares, mano de obra necesaria para su ejecucin y costes
indirectos derivados de estos conceptos, as como cuantas necesidades circunstanciales se
requieran para la ejecucin de la obra, tales como indemnizaciones por daos a terceros u
ocupaciones temporales y costos de obtencin de los permisos necesarios, as como de las
operaciones necesarias para la reposicin de servidumbres y servicios pblicos o privados
afectados tanto por el proceso de ejecucin de las obras como por las instalaciones auxiliares.
Igualmente, aquellos conceptos que se especifican en la definicin de cada unidad de obra, las
operaciones descritas en el proceso de ejecucin, los ensayos y pruebas de servicio y puesta
en funcionamiento, inspecciones, permisos, boletines, licencias, tasas o similares.
No ser de abono al Contratista mayor volumen de cualquier tipo de obra que el definido en
los planos o en las modificaciones autorizadas por la Direccin Facultativa. Tampoco le ser
abonado, en su caso, el coste de la restitucin de la obra a sus dimensiones correctas, ni la
obra que hubiese tenido que realizar por orden de la Direccin Facultativa para subsanar
cualquier defecto de ejecucin.
TERMINOLOGA APLICADA EN EL CRITERIO DE MEDICIN.
A continuacin, se detalla el significado de algunos de los trminos utilizados en los
diferentes captulos de obra.
ACONDICIONAMIENTO DEL TERRENO.
Volumen de tierras en perfil esponjado. La medicin se referir al estado de las tierras una
vez extradas. Para ello, la forma de obtener el volumen de tierras a transportar, ser la que
resulte de aplicar el porcentaje de esponjamiento medio que proceda, en funcin de las
caractersticas del terreno.
Volumen de relleno en perfil compactado. La medicin se referir al estado del relleno
una vez finalizado el proceso de compactacin.
Volumen terico ejecutado. Ser el volumen que resulte de considerar las dimensiones de
las secciones tericas especificadas en los planos de Proyecto, independientemente de que
las secciones excavadas hubieran quedado con mayores dimensiones.
CIMENTACIONES.
Superficie terica ejecutada. Ser la superficie que resulte de considerar las dimensiones
de las secciones tericas especificadas en los planos de Proyecto, independientemente de
que la superficie ocupada por el hormign hubiera quedado con mayores dimensiones.
Volumen terico ejecutado. Ser el volumen que resulte de considerar las dimensiones de
las secciones tericas especificadas en los planos de Proyecto, independientemente de que
las secciones de hormign hubieran quedado con mayores dimensiones.
ESTRUCTURAS.
Volumen terico ejecutado. Ser el volumen que resulte de considerar las dimensiones de
las secciones tericas especificadas en los planos de Proyecto, independientemente de que
las secciones de los elementos estructurales hubieran quedado con mayores dimensiones.

25

Pliego de condiciones

ESTRUCTURAS METLICAS.
Peso nominal medido. Sern los kg que resulten de aplicar a los elementos estructurales
metlicos los pesos nominales que, segn dimensiones y tipo de acero, figuren en tablas.
ESTRUCTURAS (FORJADOS).
Deduciendo los huecos de superficie mayor de X m. Se medir la superficie de los
forjados de cara exterior a cara exterior de los zunchos que delimitan el permetro de su
superficie, descontando nicamente los huecos o pasos de forjados que tengan una
superficie mayor de X m.
En los casos de dos paos formados por forjados diferentes, objeto de precios unitarios
distintos, que apoyen o empotren en una jcena o muro de carga comn a ambos paos,
cada una de las unidades de obra de forjado se medir desde fuera a cara exterior de los
elementos delimitadores al eje de la jcena o muro de carga comn.
En los casos de forjados inclinados se tomar en verdadera magnitud la superficie de la
cara inferior del forjado, con el mismo criterio anteriormente sealado para la deduccin
de huecos.
ESTRUCTURAS (MUROS).
Deduciendo los huecos de superficie mayor de X m. Se aplicar el mismo criterio que
para fachadas y particiones.
FACHADAS Y PARTICIONES.
Deduciendo los huecos de superficie mayor de X m. Se medirn los paramentos
verticales de fachadas y particiones descontando nicamente aquellos huecos cuya
superficie sea mayor de X m, lo que significa que:
Cuando los huecos sean menores de X m se medirn a cinta corrida como si no
hubiera huecos. Al no deducir ningn hueco, en compensacin de medir hueco por
macizo, no se medirn los trabajos de formacin de mochetas en jambas y dinteles.
Cuando los huecos sean mayores de X m, se deducir la superficie de estos huecos,
pero se sumar a la medicin la superficie de la parte interior del hueco,
correspondiente al desarrollo de las mochetas.
Deduciendo todos los huecos. Se medirn los paramentos verticales de fachadas y
particiones descontando la superficie de todos los huecos, pero se incluye la ejecucin de
todos los trabajos precisos para la resolucin del hueco, as como los materiales que
forman dinteles, jambas y vierteaguas.
A los efectos anteriores, se entender como hueco, cualquier abertura que tenga mochetas
y dintel para puerta o ventana. En caso de tratarse de un vaco en la fbrica sin dintel,
antepecho ni carpintera, se deducir siempre el mismo al medir la fbrica, sea cual fuere
su superficie.
En el supuesto de cerramientos de fachada donde las hojas, en lugar de apoyar
directamente en el forjado, apoyen en una o dos hiladas de regularizacin que abarquen
todo el espesor del cerramiento, al efectuar la medicin de las unidades de obra se medir

26

Pliego de condiciones

su altura desde el forjado y, en compensacin, no se medirn las hiladas de regularizacin.


INSTALACIONES.
Longitud realmente ejecutada. Medicin segn desarrollo longitudinal resultante,
considerando, en su caso, los tramos ocupados por piezas especiales.
REVESTIMIENTOS (YESOS Y ENFOSCADOS DE CEMENTO).
Deduciendo, en los huecos de superficie mayor de X m, el exceso sobre los X m. Los
paramentos verticales y horizontales se medirn a cinta corrida, sin descontar huecos de
superficie menor a X m. Para huecos de mayor superficie, se descontar nicamente el
exceso sobre esta superficie. En ambos casos se considerar incluida la ejecucin de
mochetas, fondos de dinteles y aristados. Los paramentos que tengan armarios empotrados
no sern objeto de descuento, sea cual fuere su dimensin.

3.2.1

Instalaciones

Unidad de obra ICN015a: Lnea frigorfica doble realizada con tubera flexible de cobre
sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de
espesor con aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y
0,8 mm de espesor con aislamiento de 10 mm de espesor.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de lnea frigorfica doble realizada con tubera flexible de cobre sin
soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con
aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor
con aislamiento de 10 mm de espesor, teniendo el cobre un contenido de aceite residual
inferior a 4 mg/m y siendo el aislamiento de coquilla flexible de espuma elastomrica con
revestimiento superficial de pelcula de polietileno, para una temperatura de trabajo entre -45
y 100C, suministrada en rollo, para conexin entre las unidades interior y exterior. Incluso
p/p de cortes, eliminacin de rebabas, proteccin de los extremos con cinta aislante,
realizacin de curvas, abocardado, vaciado del circuito, carga de gas refrigerante, accesorios,
sifones, soportes y fijaciones. Totalmente montada, conexionada y probada.

CRITERIO DE MEDICIN EN PROYECTO.


Longitud medida segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin y recorrido se corresponden con los de Proyecto.

PROCESO DE EJECUCIN.
FASES DE EJECUCIN.

27

Pliego de condiciones

Replanteo del recorrido de la lnea. Montaje y fijacin de la lnea. Montaje de


accesorios. Vaciado para su carga. Carga del gas refrigerante.
CONDICIONES DE TERMINACIN.
No presentar fugas.

CONSERVACIN Y MANTENIMIENTO.
Se protegern los terminales de la tubera hasta sus conexiones.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.

Unidad de obra ICN015: Lnea frigorfica doble realizada con tubera flexible de cobre
sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de
espesor con aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8
mm de espesor con aislamiento de 10 mm de espesor.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de lnea frigorfica doble realizada con tubera flexible de cobre sin
soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con
aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor
con aislamiento de 10 mm de espesor, teniendo el cobre un contenido de aceite residual
inferior a 4 mg/m y siendo el aislamiento de coquilla flexible de espuma elastomrica con
revestimiento superficial de pelcula de polietileno, para una temperatura de trabajo entre -45
y 100C, suministrada en rollo, para conexin entre las unidades interior y exterior. Incluso
p/p de cortes, eliminacin de rebabas, proteccin de los extremos con cinta aislante,
realizacin de curvas, abocardado, vaciado del circuito, carga de gas refrigerante, accesorios,
sifones, soportes y fijaciones. Totalmente montada, conexionada y probada.
EJECUCIN, MEDICIN Y ABONO.
Como la unidad de obra ICN015a

Unidad de obra ICN040a: Equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de
calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad
exterior trifsica 400V/50Hz, modelo FDU 100 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 10 kW, EER = 3,47 (clase A), potencia
calorfica nominal 11,2 kW, COP = 3,75 (clase A).
CARACTERSTICAS TCNICAS.
Suministro e instalacin de equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 100 VS "MITSUBISHI HEAVY INDUSTRIES", potencia

28

Pliego de condiciones

frigorfica nominal 10 kW (temperatura de bulbo seco en el interior 27C, temperatura de


bulbo hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura
de bulbo hmedo en el exterior 24C), potencia calorfica nominal 11,2 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura de
bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,47 (clase A), COP
(coeficiente energtico) 3,75 (clase A), formado por una unidad interior FDU 100 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 37 dBA, caudal de aire (velocidad alta)
2040 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta (ajuste
del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una unidad exterior
FDC 100 VS, con compresor DC PAM Inverter, de 845x970x370 mm, nivel sonoro 49 dBA y
caudal de aire 4500 m/h, con control de condensacin y posibilidad de integracin en un
sistema domtico KNX/EIB a travs de un interface (no incluido en este precio). Incluso
elementos antivibratorios y soportes de apoyo. Totalmente montado, conexionado y puesto en
marcha por la empresa instaladora para la comprobacin de su correcto funcionamiento.

CRITERIO DE MEDICIN EN PROYECTO.


Unidad proyectada, segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin se corresponde con la de Proyecto y que hay espacio
suficiente para su instalacin.

PROCESO DE EJECUCIN.
FASES DE EJECUCIN.
Replanteo de las unidades. Instalacin de la unidad interior. Instalacin de la unidad
exterior. Conexionado del equipo a las lneas frigorficas. Conexionado del equipo al
conducto. Conexionado del equipo a la red elctrica. Conexionado del equipo al
circuito de control. Conexionado del equipo a la red de desage. Puesta en marcha.
CONDICIONES DE TERMINACIN.
La fijacin al paramento soporte ser adecuada, evitndose ruidos y vibraciones.

CONSERVACIN Y MANTENIMIENTO.
Se proteger frente a golpes y salpicaduras.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

29

Pliego de condiciones

Unidad de obra ICN040b: Equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de
calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad
exterior trifsica 400V/50Hz, modelo FDU 125 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 12,5 kW, EER = 3,09 (clase B), potencia
calorfica nominal 14 kW, COP = 3,69 (clase A).
CARACTERSTICAS TCNICAS.
Suministro e instalacin de equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 125 VS "MITSUBISHI HEAVY INDUSTRIES", potencia
frigorfica nominal 12,5 kW (temperatura de bulbo seco en el interior 27C, temperatura de
bulbo hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura
de bulbo hmedo en el exterior 24C), potencia calorfica nominal 14 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura de
bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,09 (clase B), COP
(coeficiente energtico) 3,69 (clase A), formado por una unidad interior FDU 125 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta (ajuste
del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una unidad exterior
FDC 125 VS, con compresor DC PAM Inverter, de 845x970x370 mm, nivel sonoro 50 dBA y
caudal de aire 4500 m/h, con control de condensacin y posibilidad de integracin en un
sistema domtico KNX/EIB a travs de un interface (no incluido en este precio). Incluso
elementos antivibratorios y soportes de apoyo. Totalmente montado, conexionado y puesto en
marcha por la empresa instaladora para la comprobacin de su correcto funcionamiento.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICN040a

Unidad de obra ICN040c: Equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de
calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad
exterior trifsica 400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia
calorfica nominal 16 kW, COP = 3,61 (clase A).
CARACTERSTICAS TCNICAS.
Suministro e instalacin de equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia
frigorfica nominal 14 kW (temperatura de bulbo seco en el interior 27C, temperatura de
bulbo hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura
de bulbo hmedo en el exterior 24C), potencia calorfica nominal 16 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura de

30

Pliego de condiciones

bulbo hmedo en el exterior 6C), EER (calificacin energtica) 2,83 (clase C), COP
(coeficiente energtico) 3,61 (clase A), formado por una unidad interior FDU 140 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta (ajuste
del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una unidad exterior
FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm, nivel sonoro 51 dBA y
caudal de aire 4500 m/h, con control de condensacin y posibilidad de integracin en un
sistema domtico KNX/EIB a travs de un interface (no incluido en este precio). Incluso
elementos antivibratorios y soportes de apoyo. Totalmente montado, conexionado y puesto en
marcha por la empresa instaladora para la comprobacin de su correcto funcionamiento.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICN040a

Unidad de obra ICN040d: Equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de
calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad
exterior trifsica 400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia
calorfica nominal 16 kW, COP = 3,61 (clase A).
CARACTERSTICAS TCNICAS.
Suministro e instalacin de equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia
frigorfica nominal 14 kW (temperatura de bulbo seco en el interior 27C, temperatura de
bulbo hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura
de bulbo hmedo en el exterior 24C), potencia calorfica nominal 16 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura de
bulbo hmedo en el exterior 6C), EER (calificacin energtica) 2,83 (clase C), COP
(coeficiente energtico) 3,61 (clase A), formado por una unidad interior FDU 140 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta (ajuste
del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una unidad exterior
FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm, nivel sonoro 51 dBA y
caudal de aire 4500 m/h, con control de condensacin y posibilidad de integracin en un
sistema domtico KNX/EIB a travs de un interface (no incluido en este precio). Incluso
elementos antivibratorios y soportes de apoyo. Totalmente montado, conexionado y puesto en
marcha por la empresa instaladora para la comprobacin de su correcto funcionamiento.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICN040a

31

Pliego de condiciones

Unidad de obra ICN040: Equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de
calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad
exterior trifsica 400V/50Hz, modelo FDU 200 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 20 kW, EER = 3,03 (clase B), potencia
calorfica nominal 22,4 kW, COP = 3,68 (clase A).
CARACTERSTICAS TCNICAS.
Suministro e instalacin de equipo de aire acondicionado, sistema aire-aire split 1x1, con
distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 200 VS "MITSUBISHI HEAVY INDUSTRIES", potencia
frigorfica nominal 20 kW (temperatura de bulbo seco en el interior 27C, temperatura de
bulbo hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura
de bulbo hmedo en el exterior 24C), potencia calorfica nominal 22,4 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura de
bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,03 (clase B), COP
(coeficiente energtico) 3,68 (clase A), formado por una unidad interior FDU 200 V, de
360x1570x830 mm, nivel sonoro (velocidad baja) 51 dBA, caudal de aire (velocidad alta)
3600 m/h, presin de aire (velocidad alta) 100 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 200 Pa, control por cable modelo RC-E3, y una unidad
exterior FDC 200 VS, con compresor DC PAM Inverter, de 1300x970x370 mm, nivel sonoro
57 dBA y caudal de aire 9000 m/h, con control de condensacin y posibilidad de integracin
en un sistema domtico KNX/EIB a travs de un interface (no incluido en este precio).
Incluso elementos antivibratorios y soportes de apoyo. Totalmente montado, conexionado y
puesto en marcha por la empresa instaladora para la comprobacin de su correcto
funcionamiento.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICN040a

Unidad de obra ICR021: Conducto autoportante rectangular para la distribucin de


aire climatizado formado por panel rgido de lana de vidrio Ursa Air Zero "URSA
IBRICA AISLANTES", segn UNE-EN 13162, recubierto con un complejo kraftaluminio reforzado en su cara exterior y con un tejido absorbente acstico de color
negro, en su cara interior, con los bordes largos canteados, de 25 mm de espesor.
CARACTERSTICAS TCNICAS.
Formacin de conducto rectangular para la distribucin de aire climatizado formado por panel
rgido de lana de vidrio Ursa Air Zero "URSA IBRICA AISLANTES", segn UNE-EN
13162, recubierto con un complejo kraft-aluminio reforzado en su cara exterior y con un
tejido absorbente acstico de color negro, en su cara interior, con los bordes largos canteados,
de 25 mm de espesor, resistencia trmica 0,75 (mK)/W, conductividad trmica 0,033
W/(mK). Incluso p/p de cortes, codos y derivaciones, embocaduras, soportes metlicos
galvanizados, elementos de fijacin, sellado de tramos y uniones con cinta autoadhesiva de
aluminio, accesorios de montaje, piezas especiales, limpieza y retirada de los materiales

32

Pliego de condiciones

sobrantes a contenedor. Totalmente montado, conexionado y probado.

CRITERIO DE MEDICIN EN PROYECTO.


Superficie proyectada, segn documentacin grfica de Proyecto, calculada como producto
del permetro exterior por la longitud del tramo, medida entre los ejes de los elementos o de
los puntos a conectar, sin descontar las piezas especiales.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin y recorrido se corresponden con los de Proyecto, y
que hay espacio suficiente para su instalacin.

PROCESO DE EJECUCIN.
FASES DE EJECUCIN.
Replanteo del recorrido de los conductos. Marcado y posterior anclaje de los soportes
de los conductos. Montaje y fijacin de conductos. Sellado de las uniones. Limpieza
final.
CONDICIONES DE TERMINACIN.
Los conductos y embocaduras quedarn estancos y exentos de vibraciones.

CONSERVACIN Y MANTENIMIENTO.
No albergarn conducciones de otras instalaciones mecnicas o elctricas ni sern atravesados
por stas.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir la superficie realmente ejecutada segn especificaciones de Proyecto.

Unidad de obra ICR040a: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

33

Pliego de condiciones

CRITERIO DE MEDICIN EN PROYECTO.


Unidad proyectada, segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin se corresponde con la de Proyecto.

FASES DE EJECUCIN.
Replanteo. Montaje y fijacin del difusor.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Unidad de obra ICR040b: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a
Unidad de obra ICR040c: Difusor rectangular de lamas directrices fijas, de aluminio
extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

34

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040d: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040e: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040f: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

35

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040g: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040h: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040i: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

36

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040j: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040k: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040l: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

37

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040m: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040n: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040o: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

38

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040p: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040q: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040r: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.

39

Pliego de condiciones

Como la unidad de obra ICR040a

Unidad de obra ICR040s: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040t: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040u: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.
EJECUCIN, MEDICIN Y ABONO.
Como la unidad de obra ICR040a

40

Pliego de condiciones

Unidad de obra ICR040v: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040w: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040x: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

41

Pliego de condiciones

Unidad de obra ICR040y: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040z: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040ba: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a
Unidad de obra ICR040bb: Difusor rectangular de lamas directrices fijas, de aluminio

42

Pliego de condiciones

extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7


m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bc: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bd: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040be: Difusor rectangular de lamas directrices fijas, de aluminio

43

Pliego de condiciones

extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7


m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bf: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bg: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a
Unidad de obra ICR040bh: Difusor rectangular de lamas directrices fijas, de aluminio
extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7

44

Pliego de condiciones

m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bi: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bj: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bk: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.

45

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bl: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bm: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040bn: Difusor cuadrado de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7

46

Pliego de condiciones

m.

CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor cuadrado de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR040: Difusor rectangular de lamas directrices fijas, de aluminio


extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7
m.
CARACTERSTICAS TCNICAS.
Suministro y montaje de difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0, para instalar en alturas de
hasta 2,7 m. Incluso accesorios de montaje y elementos de fijacin. Totalmente montado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR040a

Unidad de obra ICR050a: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

CRITERIO DE MEDICIN EN PROYECTO.


Unidad proyectada, segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN

47

Pliego de condiciones

DE LAS UNIDADES DE OBRA.


DEL SOPORTE.
Se comprobar que su situacin se corresponde con la de Proyecto.
FASES DE EJECUCIN.
Replanteo. Montaje y fijacin de la rejilla.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Unidad de obra ICR050b: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050c: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050d: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

48

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050e: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050f: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050g: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

49

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050h: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050i: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050j: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

50

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050k: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050l: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050m: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

51

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050n: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050o: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050p: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

52

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050q: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050r: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050s: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm,
montada en conducto rectangular no metlico.

53

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 225x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050t: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050u: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050v: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm,
montada en conducto rectangular no metlico.

54

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050w: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050x: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050y: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.

55

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050z: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050ba: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bb: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.

56

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bc: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bd: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050be: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm,
montada en conducto rectangular no metlico.

57

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bf: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 525x125 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 525x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bg: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bh: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 625x125 mm,
montada en conducto rectangular no metlico.

58

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 625x125 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bi: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bj: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bk: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm,
montada en conducto rectangular no metlico.

59

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 325x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bl: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bm: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bn: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm,
montada en conducto rectangular no metlico.

60

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050bo: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 425x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR050: Rejilla de retorno, de aluminio extruido, anodizado color


natural E6-C-0, con lamas horizontales regulables individualmente, de 525x225 mm,
montada en conducto rectangular no metlico.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de retorno, de aluminio extruido, anodizado color natural E6C-0, con lamas horizontales regulables individualmente, de 525x225 mm, fijacin mediante
tornillos vistos (con marco de montaje de chapa de acero galvanizado), montada en conducto
rectangular no metlico. Incluso accesorios de montaje y elementos de fijacin. Totalmente
montada.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR050a

Unidad de obra ICR070a: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.

61

Pliego de condiciones

CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

CRITERIO DE MEDICIN EN PROYECTO.


Unidad proyectada, segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin se corresponde con la de Proyecto.

FASES DE EJECUCIN.
Replanteo. Montaje y fijacin de la rejilla en el cerramiento. Conexin al conducto.

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Unidad de obra ICR070b: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

Unidad de obra ICR070c: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.

62

Pliego de condiciones

Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

Unidad de obra ICR070d: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

Unidad de obra ICR070e: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

Unidad de obra ICR070f: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

63

Pliego de condiciones

Unidad de obra ICR070: Rejilla de intemperie para instalaciones de ventilacin, marco


frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
CARACTERSTICAS TCNICAS.
Suministro y montaje de rejilla de intemperie para instalaciones de ventilacin, marco frontal
y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero
galvanizado con malla de 20x20 mm. Incluso accesorios de montaje y elementos de fijacin.
Totalmente montada y conectada a la red de conductos.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR070a

Unidad de obra ICR110a: Recuperador de calor aire-aire, con intercambiador de flujo


cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%, para montaje horizontal
dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5
m.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de recuperador de calor aire-aire, con intercambiador de flujo
cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%, para montaje horizontal
dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m,
con caja de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn
UNE-EN 13501-1, soportes antivibratorios, embocaduras de 250 mm de dimetro con junta
estanca y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de 4
velocidades de 355 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa con
proteccin IP 55. Totalmente montado, conexionado y probado.

CRITERIO DE MEDICIN EN PROYECTO.


Unidad proyectada, segn documentacin grfica de Proyecto.

CONDICIONES PREVIAS QUE HAN DE CUMPLIRSE ANTES DE LA EJECUCIN


DE LAS UNIDADES DE OBRA.
DEL SOPORTE.
Se comprobar que su situacin se corresponde con la de Proyecto y que la zona de
ubicacin est completamente terminada.

FASES DE EJECUCIN.
Replanteo. Colocacin y fijacin del recuperador. Conexionado con la red elctrica.

64

Pliego de condiciones

COMPROBACIN EN OBRA DE LAS MEDICIONES EFECTUADAS EN


PROYECTO Y ABONO DE LAS MISMAS.
Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Unidad de obra ICR110b: Recuperador de calor aire-aire, con intercambiador de flujo


cruzado, caudal mximo de 1900 m/h, eficiencia sensible 51,6%, para montaje
horizontal dimensiones 1000x1000x500 mm y nivel de presin sonora de 48 dBA en
campo libre a 1,5 m.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de recuperador de calor aire-aire, con intercambiador de flujo
cruzado, caudal mximo de 1900 m/h, eficiencia sensible 51,6%, para montaje horizontal
dimensiones 1000x1000x500 mm y nivel de presin sonora de 48 dBA en campo libre a 1,5
m, con caja de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn
UNE-EN 13501-1, soportes antivibratorios, embocaduras de 315 mm de dimetro con junta
estanca y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de 3
velocidades de 373 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa con
proteccin IP 55. Totalmente montado, conexionado y probado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR110a

Unidad de obra ICR110c: Recuperador de calor aire-aire, con intercambiador de flujo


cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en
campo libre a 1,5 m.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de recuperador de calor aire-aire, con intercambiador de flujo
cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje horizontal
dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5
m, con caja de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn
UNE-EN 13501-1, soportes antivibratorios, embocaduras de 355 mm de dimetro con junta
estanca y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de 3
velocidades de 550 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa con
proteccin IP 55. Totalmente montado, conexionado y probado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR110a

Unidad de obra ICR110: Recuperador de calor aire-aire, con intercambiador de flujo

65

Pliego de condiciones

cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en
campo libre a 1,5 m.
CARACTERSTICAS TCNICAS.
Suministro e instalacin de recuperador de calor aire-aire, con intercambiador de flujo
cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje horizontal
dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5
m, con caja de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn
UNE-EN 13501-1, soportes antivibratorios, embocaduras de 355 mm de dimetro con junta
estanca y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de 3
velocidades de 550 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa con
proteccin IP 55. Totalmente montado, conexionado y probado.

EJECUCIN, MEDICIN Y ABONO.


Como la unidad de obra ICR110a

3.3

Prescripciones sobre verificaciones en el edificio terminado

De acuerdo con el artculo 7.4 del CTE, en la obra terminada, bien sobre el edificio en su
conjunto, o bien sobre sus diferentes partes y sus instalaciones, totalmente terminadas, deben
realizarse, adems de las que puedan establecerse con carcter voluntario, las comprobaciones
y pruebas de servicio previstas en el presente pliego, por parte del constructor, y a su cargo,
independientemente de las ordenadas por la Direccin Facultativa y las exigidas por la
legislacin aplicable, que sern realizadas por laboratorio acreditado y cuyo coste se
especifica detalladamente en el captulo de Control de Calidad y Ensayos, del Presupuesto de
Ejecucin material (PEM) del proyecto.

I. INSTALACIONES
Las pruebas finales de la instalacin se efectuarn, una vez est el edificio terminado, por la
empresa instaladora, que dispondr de los medios materiales y humanos necesarios para su
realizacin.
Todas las pruebas se efectuarn en presencia del instalador autorizado o del director de
Ejecucin de la Obra, que debe dar su conformidad tanto al procedimiento seguido como a los
resultados obtenidos.
Los resultados de las distintas pruebas realizadas a cada uno de los equipos, aparatos o
subsistemas, pasarn a formar parte de la documentacin final de la instalacin. Se indicarn
marca y modelo y se mostrarn, para cada equipo, los datos de funcionamiento segn
proyecto y los datos medidos en obra durante la puesta en marcha.
Cuando para extender el certificado de la instalacin sea necesario disponer de energa para
realizar pruebas, se solicitar a la empresa suministradora de energa un suministro

66

Pliego de condiciones

provisional para pruebas, por el instalador autorizado o por el director de la instalacin, y bajo
su responsabilidad.
Sern a cargo de la empresa instaladora todos los gastos ocasionados por la realizacin de
estas pruebas finales, as como los gastos ocasionados por el incumplimiento de las mismas.

67

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

5. PRESUPUESTO Y MEDICION
AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Presupuesto y medicin

ndice
0

HOJA DE IDENTIFICACIN................................................................................................................ 2

JUSTIFICACIN DE PRECIOS............................................................................................................ 3
1.1

CUADRO DE PRECIOS UNITARIOS. MANO DE OBRA ............................................................................ 3

1.2

CUADRO DE PRECIOS UNITARIOS. MATERIALES ................................................................................ 4

1.3

CUADRO DE PRECIOS AUXILIARES Y DESCOMPUESTOS...................................................................... 6

1.4

CUADRO DE PRECIOS N 1. EN LETRA ............................................................................................... 20

1.5

CUADRO DE PRECIOS N 2. MANO DE OBRA, MATERIALES, RESTOS DE OBRA, COSTES INDIRECTOS 25

PRESUPUESTO Y MEDICIN ........................................................................................................... 34

RESUMEN DE PRESUPUESTO .......................................................................................................... 41

PRESUPUESTO DE EJECUCIN POR CONTRATA ..................................................................... 42

Presupuesto y medicin

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con
CYPE Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01

Data y firmas de los anteriormente citados

Reus, Mayo de 2011

Presupuesto y medicin

1
1.1

Justificacin de Precios

Cuadro de Precios Unitarios. Mano de obra


Importe
Designacin

Precio
(euros)
1
2

Oficial 1 instalador de climatizacin.


Ayudante instalador de climatizacin.

16,91
14,25

Cantidad
(Horas)

Total
(euros)

631,215 h
631,215 h

10.673,85
8.994,81

Importe total:

19.668,66

Presupuesto y medicin

1.2

Cuadro de Precios Unitarios. Materiales


Importe

Designacin
Precio
(euros)

2
3
4

10

11

12

Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro


nominal, para canalizacin fija en superficie. Resistencia a la compresin 1250 N, resistencia
al impacto 2 julios, temperatura de trabajo -5C hasta 60C, con grado de proteccin IP 547
segn UNE 20324, propiedades elctricas: aislante, no propagador de la llama. Segn UNE-EN
61386-1 y UNE-EN 61386-22. Incluso p/p de abrazaderas, elementos de sujecin y accesorios
(Curvas, manguitos, tes, codos y curvas flexibles).
Cinta autoadhesiva de aluminio de 50 micras de espesor y 65 mm de ancho a base de resinas
acrlicas, para el sellado y fijacin del aislamiento.
Soporte metlico de acero galvanizado para sujecin al forjado de conducto rectangular de lana
mineral para la distribucin de aire en climatizacin.
Panel rgido de lana de vidrio Ursa Air Zero "URSA IBRICA AISLANTES", segn UNE-EN 13162,
recubierto con un complejo kraft-aluminio reforzado en su cara exterior y con un tejido
absorbente acstico de color negro, en su cara interior, con los bordes largos canteados, de
25 mm de espesor, para la formacin de conductos autoportantes para la distribucin de aire en
climatizacin, resistencia trmica 0,75 (mK)/W, conductividad trmica 0,033 W/(mK), Euroclase
B-s1 d0 de reaccin al fuego, con cdigo de designacin MW-UNE-EN 13162-T5-CS(10)5-Z100-SD10.
Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un
tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con aislamiento de 9 mm de espesor y
un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor con aislamiento de 10 mm de espesor,
teniendo el cobre un contenido de aceite residual inferior a 4 mg/m y siendo el aislamiento de
coquilla flexible de espuma elastomrica con revestimiento superficial de pelcula de
polietileno, para una temperatura de trabajo entre -45 y 100C, suministrada en rollo, segn
UNE-EN 12735-1.
Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un
tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con aislamiento de 9 mm de espesor y
un tubo para gas de 1" de dimetro y 0,8 mm de espesor con aislamiento de 10 mm de espesor,
teniendo el cobre un contenido de aceite residual inferior a 4 mg/m y siendo el aislamiento de
coquilla flexible de espuma elastomrica con revestimiento superficial de pelcula de
polietileno, para una temperatura de trabajo entre -45 y 100C, suministrada en rollo, segn
UNE-EN 12735-1.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter, gama
semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 100
VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 10 kW (temperatura de bulbo
seco en el interior 27C, temperatura de bulbo hmedo en el interior 19C, temperatura de
bulbo seco en el exterior 35C, temperatura de bulbo hmedo en el exterior 24C), potencia
calorfica nominal 11,2 kW (temperatura de bulbo seco en el interior 20C, temperatura de
bulbo seco en el exterior 7C, temperatura de bulbo hmedo en el exterior 6C), EER
(calificacin energtica) 3,47 (clase A), COP (coeficiente energtico) 3,75 (clase A), formado
por una unidad interior FDU 100 V, de 350x1370x650 mm, nivel sonoro (velocidad baja) 37 dBA,
caudal de aire (velocidad alta) 2040 m/h, presin de aire (velocidad alta) 50 Pa, presin de
aire a velocidad ultra alta (ajuste del ventilador a alta potencia) 130 Pa, control por cable
modelo RC-E3, y una unidad exterior FDC 100 VS, con compresor DC PAM Inverter, de 845x970x370
mm, nivel sonoro 49 dBA y caudal de aire 4500 m/h, con control de condensacin y posibilidad
de integracin en un sistema domtico KNX/EIB a travs de un interface (no incluido en este
precio).
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter, gama
semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 125
VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 12,5 kW (temperatura de bulbo
seco en el interior 27C, temperatura de bulbo hmedo en el interior 19C, temperatura de
bulbo seco en el exterior 35C, temperatura de bulbo hmedo en el exterior 24C), potencia
calorfica nominal 14 kW (temperatura de bulbo seco en el interior 20C, temperatura de bulbo
seco en el exterior 7C, temperatura de bulbo hmedo en el exterior 6C), EER (calificacin
energtica) 3,09 (clase B), COP (coeficiente energtico) 3,69 (clase A), formado por una
unidad interior FDU 125 V, de 350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de
aire (velocidad alta) 2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a
velocidad ultra alta (ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo
RC-E3, y una unidad exterior FDC 125 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 50 dBA y caudal de aire 4500 m/h, con control de condensacin y posibilidad de
integracin en un sistema domtico KNX/EIB a travs de un interface (no incluido en este
precio).
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter, gama
semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 140
VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW (temperatura de bulbo
seco en el interior 27C, temperatura de bulbo hmedo en el interior 19C, temperatura de
bulbo seco en el exterior 35C, temperatura de bulbo hmedo en el exterior 24C), potencia
calorfica nominal 16 kW (temperatura de bulbo seco en el interior 20C, temperatura de bulbo
seco en el exterior 7C, temperatura de bulbo hmedo en el exterior 6C), EER (calificacin
energtica) 2,83 (clase C), COP (coeficiente energtico) 3,61 (clase A), formado por una
unidad interior FDU 140 V, de 350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de
aire (velocidad alta) 2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a
velocidad ultra alta (ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo
RC-E3, y una unidad exterior FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 51 dBA y caudal de aire 4500 m/h, con control de condensacin y posibilidad de
integracin en un sistema domtico KNX/EIB a travs de un interface (no incluido en este
precio).
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter, gama
semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 140
VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW (temperatura de bulbo
seco en el interior 27C, temperatura de bulbo hmedo en el interior 19C, temperatura de
bulbo seco en el exterior 35C, temperatura de bulbo hmedo en el exterior 24C), potencia
calorfica nominal 16 kW (temperatura de bulbo seco en el interior 20C, temperatura de bulbo
seco en el exterior 7C, temperatura de bulbo hmedo en el exterior 6C), EER (calificacin
energtica) 2,83 (clase C), COP (coeficiente energtico) 3,61 (clase A), formado por una
unidad interior FDU 140 V, de 350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de
aire (velocidad alta) 2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a
velocidad ultra alta (ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo
RC-E3, y una unidad exterior FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 51 dBA y caudal de aire 4500 m/h, con control de condensacin y posibilidad de
integracin en un sistema domtico KNX/EIB a travs de un interface (no incluido en este
precio).
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter, gama
semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 200
VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 20 kW (temperatura de bulbo
seco en el interior 27C, temperatura de bulbo hmedo en el interior 19C, temperatura de
bulbo seco en el exterior 35C, temperatura de bulbo hmedo en el exterior 24C), potencia
calorfica nominal 22,4 kW (temperatura de bulbo seco en el interior 20C, temperatura de
bulbo seco en el exterior 7C, temperatura de bulbo hmedo en el exterior 6C), EER
(calificacin energtica) 3,03 (clase B), COP (coeficiente energtico) 3,68 (clase A), formado
por una unidad interior FDU 200 V, de 360x1570x830 mm, nivel sonoro (velocidad baja) 51 dBA,
caudal de aire (velocidad alta) 3600 m/h, presin de aire (velocidad alta) 100 Pa, presin de
aire a velocidad ultra alta (ajuste del ventilador a alta potencia) 200 Pa, control por cable
modelo RC-E3, y una unidad exterior FDC 200 VS, con compresor DC PAM Inverter, de 1300x970x370
mm, nivel sonoro 57 dBA y caudal de aire 9000 m/h, con control de condensacin y posibilidad
de integracin en un sistema domtico KNX/EIB a travs de un interface (no incluido en este
precio).
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo

Cantidad
Empleada

Total
(euros)

0,68

33,000 m

22,44

0,19

2.636,625 m

500,96

4,26

878,875 Ud

3.744,01

13,91

2.021,413 m

28.117,85

11,76

51,510 m

605,76

14,50

36,240 m

525,48

3.910,00

1,000 Ud

3.910,00

4.440,00

1,000 Ud

4.440,00

5.015,00

3,000 Ud

15.045,00

5.015,00

1,000 Ud

5.015,00

7.845,00
0,80

5,000 Ud
33,000 m

39.225,00
26,40

Presupuesto y medicin

Cuadro de Precios Unitarios. Materiales


Importe
N

Designacin
Precio
(euros)

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29
30

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900
m/h, eficiencia sensible 53,9%, para montaje horizontal dimensiones 800x800x330 mm y nivel de
presin sonora de 43 dBA en campo libre a 1,5 m, con caja de acero galvanizado y plastificado,
color marfil, con aislamiento, clase B segn UNE-EN 13501-1, soportes antivibratorios,
embocaduras de 250 mm de dimetro con junta estanca y filtros G4 con eficacia del 86%, clase D
segn UNE-EN 13501-1, 2 ventiladores centrfugos de doble odo de accionamiento directo con
motores elctricos monofsicos de 4 velocidades de 355 W cada uno, aislamiento F, proteccin
IP 20, caja de bornes externa con proteccin IP 55.
Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900
m/h, eficiencia sensible 51,6%, para montaje horizontal dimensiones 1000x1000x500 mm y nivel
de presin sonora de 48 dBA en campo libre a 1,5 m, con caja de acero galvanizado y
plastificado, color marfil, con aislamiento, clase B segn UNE-EN 13501-1, soportes
antivibratorios, embocaduras de 315 mm de dimetro con junta estanca y filtros G4 con eficacia
del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores centrfugos de doble odo de
accionamiento directo con motores elctricos monofsicos de 3 velocidades de 373 W cada uno,
aislamiento F, proteccin IP 20, caja de bornes externa con proteccin IP 55.
Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100
m/h, eficiencia sensible 52,5%, para montaje horizontal dimensiones 1250x1250x600 mm y nivel
de presin sonora de 52 dBA en campo libre a 1,5 m, con caja de acero galvanizado y
plastificado, color marfil, con aislamiento, clase B segn UNE-EN 13501-1, soportes
antivibratorios, embocaduras de 355 mm de dimetro con junta estanca y filtros G4 con eficacia
del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores centrfugos de doble odo de
accionamiento directo con motores elctricos monofsicos de 3 velocidades de 550 W cada uno,
aislamiento F, proteccin IP 20, caja de bornes externa con proteccin IP 55.
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 225x125 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 325x125 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 425x125 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 525x125 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 625x125 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 325x225 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 425x225 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 525x225 mm, fijacin mediante tornillos vistos
(con marco de montaje de chapa de acero galvanizado).
Difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0.
Difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0.
Difusor rectangular de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0.
Difusor cuadrado de lamas directrices fijas, de aluminio extruido,
ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad perimetral,
con una direccin de impulsin, anodizado color natural E6-C-0.
Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa
perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero galvanizado con malla
de 20x20 mm.
Material auxiliar para instalaciones de climatizacin.
Repercusin por m de material auxiliar para fijacin y confeccin de canalizaciones de aire
en instalaciones de climatizacin.

Cantidad
Empleada

Total
(euros)

2.017,24

8,000 Ud

16.137,92

2.621,96

1,000 Ud

2.621,96

3.793,48

2,000 Ud

7.586,96

24,43

22,000 Ud

537,46

29,12

6,000 Ud

174,72

34,40

7,000 Ud

240,80

40,07

1,000 Ud

40,07

46,05

1,000 Ud

46,05

36,36

7,000 Ud

254,52

43,11

14,000 Ud

603,54

50,23

2,000 Ud

100,46

71,80

34,000 Ud

2.441,20

88,80

26,000 Ud

2.308,80

94,00

2,000 Ud

188,00

119,40

3,000 Ud

358,20

265,98
1,45

21,000 Ud
11,877 Ud

5.585,58
17,22

13,30

175,775 Ud

2.337,81

Importe total:

142.759,17

Presupuesto y medicin

1.3
N

Cdigo

Ud

Cuadro de Precios Auxiliares y Descompuestos

Descripcin

Total

1 Instalaciones
1.1 Calefaccin, climatizacin y A.C.S.
1.1.1 Unidades autnomas de climatizacin
1.1.1.1 ICN015a

mt42lin020bc
mt42www010
mo003
mo054
%

Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8
mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor con aislamiento de 10
mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
1,000
0,010
0,181
0,181
2,000
3,000

m
Ud
h
h
%
%

Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

11,76
1,45
16,91
14,25
17,41
17,76

Precio total por m ..................................................

11,76
0,01
3,06
2,58
0,35
0,53
18,29

Son dieciocho euros con veintinueve cntimos


1.1.1.2 ICN015

mt42lin020be
mt42www010
mo003
mo054
%

Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8
mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor con aislamiento de 10 mm
de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
1,000
0,010
0,181
0,181
2,000
3,000

m
Ud
h
h
%
%

Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

14,50
1,45
16,91
14,25
20,15
20,55

Precio total por m ..................................................

14,50
0,01
3,06
2,58
0,40
0,62
21,17

Son veintiun euros con diecisiete cntimos


1.1.1.3 ICN040a

Ud

mt42mhi060
mt42mhi900
mt35aia090
mt42www010
mo003
mo054
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A,
bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU
100 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 10 kW, EER = 3,47 (clase A), potencia calorfica nominal 11,2 kW,
COP = 3,75 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
3,000
3,000
1,000
1,811
1,811
2,000
3,000

Ud
m
m
Ud
h
h
%
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta p
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo
Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro nominal, para c
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

3.910,00
0,80
0,68
1,45
16,91
14,25
3.972,32
4.051,77

Precio total por Ud ..................................................

3.910,00
2,40
2,04
1,45
30,62
25,81
79,45
121,55
4.173,32

Son cuatro mil ciento setenta y tres euros con treinta y dos cntimos
1.1.1.4 ICN040b

Ud

mt42mhi060
mt42mhi900
mt35aia090
mt42www010
mo003
mo054
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A,
bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU
125 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 12,5 kW, EER = 3,09 (clase B), potencia calorfica nominal 14 kW,
COP = 3,69 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
3,000
3,000
1,000
1,811
1,811
2,000
3,000

Ud
m
m
Ud
h
h
%
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta p
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo
Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro nominal, para c
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

4.440,00
0,80
0,68
1,45
16,91
14,25
4.502,32
4.592,37

Precio total por Ud ..................................................

4.440,00
2,40
2,04
1,45
30,62
25,81
90,05
137,77
4.730,14

Son cuatro mil setecientos treinta euros con catorce cntimos


1.1.1.5 ICN040c

Ud

mt42mhi060
mt42mhi900
mt35aia090
mt42www010
mo003
mo054
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A,
bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU
140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia calorfica nominal 16 kW,
COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
3,000
3,000
1,000
1,811
1,811
2,000
3,000

Ud
m
m
Ud
h
h
%
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta p
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo
Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro nominal, para c
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

5.015,00
0,80
0,68
1,45
16,91
14,25
5.077,32
5.178,87

Precio total por Ud ..................................................

5.015,00
2,40
2,04
1,45
30,62
25,81
101,55
155,37
5.334,24

Son cinco mil trescientos treinta y cuatro euros con veinticuatro cntimos
1.1.1.6 ICN040d

Ud

mt42mhi060
mt42mhi900
mt35aia090
mt42www010
mo003
mo054
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A,
bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU
140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia calorfica nominal 16 kW,
COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
3,000
3,000
1,000
1,811
1,811
2,000
3,000

Ud
m
m
Ud
h
h
%
%

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta p
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo
Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro nominal, para c
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

5.015,00
0,80
0,68
1,45
16,91
14,25
5.077,32
5.178,87

5.015,00
2,40
2,04
1,45
30,62
25,81
101,55
155,37
5.334,24

Son cinco mil trescientos treinta y cuatro euros con veinticuatro cntimos

Presupuesto y medicin

Cdigo

Ud

Descripcin

1.1.1.7 ICN040

Ud

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A,
bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU
200 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 20 kW, EER = 3,03 (clase B), potencia calorfica nominal 22,4 kW,
COP = 3,68 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42mhi060
mt42mhi900
mt35aia090
mt42www010
mo003
mo054
%

1,000
3,000
3,000
1,000
1,811
1,811
2,000
3,000

Ud
m
m
Ud
h
h
%
%

Total

Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta p
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo
Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de dimetro nominal, para c
Material auxiliar para instalaciones de climatizacin.
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

7.845,00
0,80
0,68
1,45
16,91
14,25
7.907,32
8.065,47

Precio total por Ud ..................................................

7.845,00
2,40
2,04
1,45
30,62
25,81
158,15
241,96
8.307,43

Son ocho mil trescientos siete euros con cuarenta y tres cntimos
1.1.2 Sistemas de conduccin de aire
1.1.2.1 ICR021

mt42cou010aa
mt42con020
mt42con025
mt42www011
mo003
mo054
%

Conducto autoportante rectangular para la distribucin de aire climatizado formado por panel rgido de lana de vidrio Ursa Air
Zero "URSA IBRICA AISLANTES", segn UNE-EN 13162, recubierto con un complejo kraft-aluminio reforzado en su cara exterior y
con un tejido absorbente acstico de color negro, en su cara interior, con los bordes largos canteados, de 25 mm de espesor.
Criterio de medicin de obra: Se medir la superficie realmente ejecutada segn especificaciones de Proyecto.
1,150
1,500
0,500
0,100
0,317
0,317
2,000
3,000

m
m
Ud
Ud
h
h
%
%

Panel rgido de lana de vidrio Ursa Air Zero "URSA IBRICA AISLANTES", segn UNE-EN 13162, recubierto
Cinta autoadhesiva de aluminio de 50 micras de espesor y 65 mm de ancho a base de resinas acrlicas, para
Soporte metlico de acero galvanizado para sujecin al forjado de conducto rectangular de lana mineral para
Repercusin por m de material auxiliar para fijacin y confeccin de canalizaciones de aire en instalaciones
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

13,91
0,19
4,26
13,30
16,91
14,25
29,63
30,22

Precio total por m ..................................................

16,00
0,29
2,13
1,33
5,36
4,52
0,59
0,91
31,13

Son treinta y un euros con trece cntimos


1.1.2.2 ICR040a

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.3 ICR040b

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.4 ICR040c

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.5 ICR040d

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.6 ICR040e

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

71,80
16,91
14,25
77,97
79,53

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos

Presupuesto y medicin

Cdigo

Ud

Descripcin

1.1.2.7 ICR040f

Ud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx245a
mo003
mo054
%

1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Total

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.8 ICR040g

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.9 ICR040h

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.10 ICR040i

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.11 ICR040j

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.12 ICR040k

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.13 ICR040l

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.14 ICR040m

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

71,80
16,91
14,25
77,97
79,53

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos

Presupuesto y medicin

Cdigo

1.1.2.15 ICR040n

Ud

Descripcin

Ud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx245a
mo003
mo054
%

1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Total

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.16 ICR040o

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.17 ICR040p

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.18 ICR040q

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.19 ICR040r

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.20 ICR040s

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.21 ICR040t

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.22 ICR040u

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

71,80
16,91
14,25
77,97
79,53

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos

Presupuesto y medicin

Cdigo

1.1.2.23 ICR040v

Ud

Descripcin

Ud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx245a
mo003
mo054
%

1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Total

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.24 ICR040w

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.25 ICR040x

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.26 ICR040y

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.27 ICR040z

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.28 ICR040ba

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

71,80
16,91
14,25
77,97
79,53

Precio total por Ud ..................................................

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos


1.1.2.29 ICR040bb

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.30 ICR040bc

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

71,80
16,91
14,25
77,97
79,53

71,80
3,35
2,82
1,56
2,39
81,92

Son ochenta y un euros con noventa y dos cntimos

10

Presupuesto y medicin

Cdigo

1.1.2.31 ICR040bd

Ud

Descripcin

Ud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx245a
mo003
mo054
%

1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Total

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.32 ICR040be

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.33 ICR040bf

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.34 ICR040bg

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.35 ICR040bh

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.36 ICR040bi

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.37 ICR040bj

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.38 ICR040bk

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

88,80
16,91
14,25
94,97
96,87

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos

11

Presupuesto y medicin

Cdigo

1.1.2.39 ICR040bl

Ud

Descripcin

Ud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx245a
mo003
mo054
%

1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Total

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.40 ICR040bm

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

88,80
16,91
14,25
94,97
96,87

Precio total por Ud ..................................................

88,80
3,35
2,82
1,90
2,91
99,78

Son noventa y nueve euros con setenta y ocho cntimos


1.1.2.41 ICR040bn

Ud

mt42trx245a
mo003
mo054
%

Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta
2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", co


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

119,40
16,91
14,25
125,57
128,08

Precio total por Ud ..................................................

119,40
3,35
2,82
2,51
3,84
131,92

Son ciento treinta y un euros con noventa y dos cntimos


1.1.2.42 ICR040

Ud

mt42trx245a
mo003
mo054
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", para instalar en alturas
de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,198
0,198
2,000
3,000

Ud
h
h
%
%

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX",


Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

94,00
16,91
14,25
100,17
102,17

Precio total por Ud ..................................................

94,00
3,35
2,82
2,00
3,07
105,24

Son ciento cinco euros con veinticuatro cntimos


1.1.2.43 ICR050a

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.44 ICR050b

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.45 ICR050c

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.46 ICR050d

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

24,43
16,91
14,25
29,44
30,03

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos

12

Presupuesto y medicin

Cdigo

1.1.2.47 ICR050e

Ud

Descripcin

Ud

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx010a
mo003
mo054
%

1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.48 ICR050f

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.49 ICR050g

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.50 ICR050h

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.51 ICR050i

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.52 ICR050j

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.53 ICR050k

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.54 ICR050l

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

24,43
16,91
14,25
29,44
30,03

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos

13

Presupuesto y medicin

Cdigo

1.1.2.55 ICR050m

Ud

Descripcin

Ud

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx010a
mo003
mo054
%

1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.56 ICR050n

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.57 ICR050o

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.58 ICR050p

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.59 ICR050q

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.60 ICR050r

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.61 ICR050s

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,161
0,161
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

24,43
16,91
14,25
29,44
30,03

Precio total por Ud ..................................................

24,43
2,72
2,29
0,59
0,90
30,93

Son treinta euros con noventa y tres cntimos


1.1.2.62 ICR050t

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,173
0,173
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

29,12
16,91
14,25
34,52
35,21

29,12
2,93
2,47
0,69
1,06
36,27

Son treinta y seis euros con veintisiete cntimos

14

Presupuesto y medicin

Cdigo

1.1.2.63 ICR050u

Ud

Descripcin

Ud

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx010a
mo003
mo054
%

1,000
0,173
0,173
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

29,12
16,91
14,25
34,52
35,21

Precio total por Ud ..................................................

29,12
2,93
2,47
0,69
1,06
36,27

Son treinta y seis euros con veintisiete cntimos


1.1.2.64 ICR050v

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,173
0,173
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

29,12
16,91
14,25
34,52
35,21

Precio total por Ud ..................................................

29,12
2,93
2,47
0,69
1,06
36,27

Son treinta y seis euros con veintisiete cntimos


1.1.2.65 ICR050w

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,173
0,173
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

29,12
16,91
14,25
34,52
35,21

Precio total por Ud ..................................................

29,12
2,93
2,47
0,69
1,06
36,27

Son treinta y seis euros con veintisiete cntimos


1.1.2.66 ICR050x

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,173
0,173
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

29,12
16,91
14,25
34,52
35,21

Precio total por Ud ..................................................

29,12
2,93
2,47
0,69
1,06
36,27

Son treinta y seis euros con veintisiete cntimos


1.1.2.67 ICR050y

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.68 ICR050z

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.69 ICR050ba

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.70 ICR050bb

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

34,40
16,91
14,25
40,13
40,93

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos

15

Presupuesto y medicin

Cdigo

1.1.2.71 ICR050bc

Ud

Descripcin

Ud

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx010a
mo003
mo054
%

1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.72 ICR050bd

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.73 ICR050be

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,184
0,184
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

34,40
16,91
14,25
40,13
40,93

Precio total por Ud ..................................................

34,40
3,11
2,62
0,80
1,23
42,16

Son cuarenta y dos euros con dieciseis cntimos


1.1.2.74 ICR050bf

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 525x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,195
0,195
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

40,07
16,91
14,25
46,15
47,07

Precio total por Ud ..................................................

40,07
3,30
2,78
0,92
1,41
48,48

Son cuarenta y ocho euros con cuarenta y ocho cntimos


1.1.2.75 ICR050bg

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,222
0,222
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

43,11
16,91
14,25
50,02
51,02

Precio total por Ud ..................................................

43,11
3,75
3,16
1,00
1,53
52,55

Son cincuenta y dos euros con cincuenta y cinco cntimos


1.1.2.76 ICR050bh

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 625x125
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,207
0,207
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

46,05
16,91
14,25
52,50
53,55

Precio total por Ud ..................................................

46,05
3,50
2,95
1,05
1,61
55,16

Son cincuenta y cinco euros con dieciseis cntimos


1.1.2.77 ICR050bi

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,202
0,202
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

36,36
16,91
14,25
42,66
43,51

Precio total por Ud ..................................................

36,36
3,42
2,88
0,85
1,31
44,82

Son cuarenta y cuatro euros con ochenta y dos cntimos


1.1.2.78 ICR050bj

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,202
0,202
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

36,36
16,91
14,25
42,66
43,51

36,36
3,42
2,88
0,85
1,31
44,82

Son cuarenta y cuatro euros con ochenta y dos cntimos

16

Presupuesto y medicin

Cdigo

1.1.2.79 ICR050bk

Ud

Descripcin

Ud

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx010a
mo003
mo054
%

1,000
0,202
0,202
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

36,36
16,91
14,25
42,66
43,51

Precio total por Ud ..................................................

36,36
3,42
2,88
0,85
1,31
44,82

Son cuarenta y cuatro euros con ochenta y dos cntimos


1.1.2.80 ICR050bl

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,222
0,222
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

43,11
16,91
14,25
50,02
51,02

Precio total por Ud ..................................................

43,11
3,75
3,16
1,00
1,53
52,55

Son cincuenta y dos euros con cincuenta y cinco cntimos


1.1.2.81 ICR050bm

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,222
0,222
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

43,11
16,91
14,25
50,02
51,02

Precio total por Ud ..................................................

43,11
3,75
3,16
1,00
1,53
52,55

Son cincuenta y dos euros con cincuenta y cinco cntimos


1.1.2.82 ICR050bn

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,222
0,222
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

43,11
16,91
14,25
50,02
51,02

Precio total por Ud ..................................................

43,11
3,75
3,16
1,00
1,53
52,55

Son cincuenta y dos euros con cincuenta y cinco cntimos


1.1.2.83 ICR050bo

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,222
0,222
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

43,11
16,91
14,25
50,02
51,02

Precio total por Ud ..................................................

43,11
3,75
3,16
1,00
1,53
52,55

Son cincuenta y dos euros con cincuenta y cinco cntimos


1.1.2.84 ICR050

Ud

mt42trx010a
mo003
mo054
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 525x225
mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,243
0,243
2,000
3,000

Ud
h
h
%
%

Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables in
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

50,23
16,91
14,25
57,80
58,96

Precio total por Ud ..................................................

50,23
4,11
3,46
1,16
1,77
60,73

Son sesenta euros con setenta y tres cntimos


1.1.2.85 ICR070a

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.86 ICR070b

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

265,98
16,91
14,25
271,53
276,96

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos

17

Presupuesto y medicin

Cdigo

1.1.2.87 ICR070c

Ud

Descripcin

Ud

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42trx370a
mo003
mo054
%

1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Total

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.88 ICR070d

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.89 ICR070e

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.90 ICR070f

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.91 ICR070

Ud
mt42trx370a
mo003
mo054
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,178
0,178
2,000
3,000

Ud
h
h
%
%

Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero gal
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

265,98
16,91
14,25
271,53
276,96

Precio total por Ud ..................................................

265,98
3,01
2,54
5,43
8,31
285,27

Son doscientos ochenta y cinco euros con veintisiete cntimos


1.1.2.92 ICR110a

Ud

mt42rsp020
mo003
mo054
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%, para montaje
horizontal dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,905
0,905
2,000
3,000

Ud
h
h
%
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900 m/h, eficiencia s
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

2.017,24
16,91
14,25
2.045,44
2.086,35

Precio total por Ud ..................................................

2.017,24
15,30
12,90
40,91
62,59
2.148,94

Son dos mil ciento cuarenta y ocho euros con noventa y cuatro cntimos
1.1.2.93 ICR110b

Ud

mt42rsp020
mo003
mo054
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900 m/h, eficiencia sensible 51,6%, para montaje
horizontal dimensiones 1000x1000x500 mm y nivel de presin sonora de 48 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
0,905
0,905
2,000
3,000

Ud
h
h
%
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900 m/h, eficiencia
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos

2.621,96
16,91
14,25
2.650,16
2.703,16

Precio total por Ud ..................................................

2.621,96
15,30
12,90
53,00
81,09
2.784,25

Son dos mil setecientos ochenta y cuatro euros con veinticinco cntimos
1.1.2.94 ICR110c

Ud

mt42rsp020
mo003
mo054
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
1,087
1,087
2,000
3,000

Ud
h
h
%
%

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

3.793,48
16,91
14,25
3.827,35
3.903,90

3.793,48
18,38
15,49
76,55
117,12
4.021,02

Son cuatro mil veintiun euros con dos cntimos

18

Presupuesto y medicin

Cdigo

1.1.2.95 ICR110

Ud

Descripcin

Ud

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

mt42rsp020
mo003
mo054
%

1,000
1,087
1,087
2,000
3,000

Ud
h
h
%
%

Total

Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia
Oficial 1 instalador de climatizacin.
Ayudante instalador de climatizacin.
Costes directos complementarios
Costes indirectos
Precio total por Ud ..................................................

3.793,48
16,91
14,25
3.827,35
3.903,90

3.793,48
18,38
15,49
76,55
117,12
4.021,02

Son cuatro mil veintiun euros con dos cntimos

19

Presupuesto y medicin

1.4

Cuadro de precios N 1. En letra


Importe

Designacin
En cifra
(euros)

En letra
(euros)

1 Instalaciones
1.1 Calefaccin, climatizacin y A.C.S.
1.1.1 Unidades autnomas de climatizacin
1.1.1.1

1.1.1.2

1.1.1.3

1.1.1.4

1.1.1.5

1.1.1.6

1.1.1.7

m Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro
y 0,8 mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor con
aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
m Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro
y 0,8 mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor
con aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas
R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 100 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 10 kW, EER = 3,47 (clase A),
potencia calorfica nominal 11,2 kW, COP = 3,75 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas
R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 125 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 12,5 kW, EER = 3,09 (clase B),
potencia calorfica nominal 14 kW, COP = 3,69 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas
R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C),
potencia calorfica nominal 16 kW, COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas
R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C),
potencia calorfica nominal 16 kW, COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas
R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica
400V/50Hz, modelo FDU 200 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica nominal 20 kW, EER = 3,03 (clase B),
potencia calorfica nominal 22,4 kW, COP = 3,68 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

18,29 DIECIOCHO EUROS CON


VEINTINUEVE CNTIMOS

21,17 VEINTIUN EUROS CON


DIECISIETE CNTIMOS

4.173,32 CUATRO MIL CIENTO SETENTA Y


TRES EUROS CON TREINTA Y
DOS CNTIMOS

4.730,14 CUATRO MIL SETECIENTOS


TREINTA EUROS CON CATORCE
CNTIMOS

5.334,24 CINCO MIL TRESCIENTOS


TREINTA Y CUATRO EUROS CON
VEINTICUATRO CNTIMOS

5.334,24 CINCO MIL TRESCIENTOS


TREINTA Y CUATRO EUROS CON
VEINTICUATRO CNTIMOS

8.307,43 OCHO MIL TRESCIENTOS SIETE


EUROS CON CUARENTA Y TRES
CNTIMOS

1.1.2 Sistemas de conduccin de aire


1.1.2.1

1.1.2.2

1.1.2.3

1.1.2.4

1.1.2.5

1.1.2.6

1.1.2.7

1.1.2.8

1.1.2.9

1.1.2.10

m Conducto autoportante rectangular para la distribucin de aire climatizado formado por panel rgido de lana de vidrio Ursa Air
Zero "URSA IBRICA AISLANTES", segn UNE-EN 13162, recubierto con un complejo kraft-aluminio reforzado en su cara exterior
y con un tejido absorbente acstico de color negro, en su cara interior, con los bordes largos canteados, de 25 mm de espesor.
Criterio de medicin de obra: Se medir la superficie realmente ejecutada segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

31,13 TREINTA Y UN EUROS CON


TRECE CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

20

Presupuesto y medicin

Cuadro de precios N 1. En letra


Importe
N

Designacin
En cifra
(euros)

1.1.2.11

1.1.2.12

1.1.2.13

1.1.2.14

1.1.2.15

1.1.2.16

1.1.2.17

1.1.2.18

1.1.2.19

1.1.2.20

1.1.2.21

1.1.2.22

1.1.2.23

1.1.2.24

1.1.2.25

1.1.2.26

1.1.2.27

1.1.2.28

1.1.2.29

1.1.2.30

1.1.2.31

1.1.2.32

1.1.2.33

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

En letra
(euros)

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

81,92 OCHENTA Y UN EUROS CON


NOVENTA Y DOS CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

21

Presupuesto y medicin

Cuadro de precios N 1. En letra


Importe
N

Designacin
En cifra
(euros)

1.1.2.34

1.1.2.35

1.1.2.36

1.1.2.37

1.1.2.38

1.1.2.39

1.1.2.40

1.1.2.41

1.1.2.42

1.1.2.43

1.1.2.44

1.1.2.45

1.1.2.46

1.1.2.47

1.1.2.48

1.1.2.49

1.1.2.50

1.1.2.51

1.1.2.52

1.1.2.53

1.1.2.54

1.1.2.55

1.1.2.56

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", para instalar
en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

En letra
(euros)

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

99,78 NOVENTA Y NUEVE EUROS CON


SETENTA Y OCHO CNTIMOS

131,92 CIENTO TREINTA Y UN EUROS


CON NOVENTA Y DOS
CNTIMOS

105,24 CIENTO CINCO EUROS CON


VEINTICUATRO CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

22

Presupuesto y medicin

Cuadro de precios N 1. En letra


Importe
N

Designacin
En cifra
(euros)

1.1.2.57

1.1.2.58

1.1.2.59

1.1.2.60

1.1.2.61

1.1.2.62

1.1.2.63

1.1.2.64

1.1.2.65

1.1.2.66

1.1.2.67

1.1.2.68

1.1.2.69

1.1.2.70

1.1.2.71

1.1.2.72

1.1.2.73

1.1.2.74

1.1.2.75

1.1.2.76

1.1.2.77

1.1.2.78

1.1.2.79

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
525x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
625x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

En letra
(euros)

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

30,93 TREINTA EUROS CON NOVENTA


Y TRES CNTIMOS

36,27 TREINTA Y SEIS EUROS CON


VEINTISIETE CNTIMOS

36,27 TREINTA Y SEIS EUROS CON


VEINTISIETE CNTIMOS

36,27 TREINTA Y SEIS EUROS CON


VEINTISIETE CNTIMOS

36,27 TREINTA Y SEIS EUROS CON


VEINTISIETE CNTIMOS

36,27 TREINTA Y SEIS EUROS CON


VEINTISIETE CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

42,16 CUARENTA Y DOS EUROS CON


DIECISEIS CNTIMOS

48,48 CUARENTA Y OCHO EUROS CON


CUARENTA Y OCHO CNTIMOS

52,55 CINCUENTA Y DOS EUROS CON


CINCUENTA Y CINCO CNTIMOS

55,16 CINCUENTA Y CINCO EUROS


CON DIECISEIS CNTIMOS

44,82 CUARENTA Y CUATRO EUROS


CON OCHENTA Y DOS
CNTIMOS

44,82 CUARENTA Y CUATRO EUROS


CON OCHENTA Y DOS
CNTIMOS

44,82 CUARENTA Y CUATRO EUROS


CON OCHENTA Y DOS
CNTIMOS

23

Presupuesto y medicin

Cuadro de precios N 1. En letra


Importe
N

Designacin
En cifra
(euros)

1.1.2.80

1.1.2.81

1.1.2.82

1.1.2.83

1.1.2.84

1.1.2.85

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de
525x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

En letra
(euros)

52,55 CINCUENTA Y DOS EUROS CON


CINCUENTA Y CINCO CNTIMOS

52,55 CINCUENTA Y DOS EUROS CON


CINCUENTA Y CINCO CNTIMOS

52,55 CINCUENTA Y DOS EUROS CON


CINCUENTA Y CINCO CNTIMOS

52,55 CINCUENTA Y DOS EUROS CON


CINCUENTA Y CINCO CNTIMOS

60,73 SESENTA EUROS CON SETENTA


Y TRES CNTIMOS

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

1.1.2.86
Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

1.1.2.87

1.1.2.88

1.1.2.89

1.1.2.90

1.1.2.91

1.1.2.92

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado,
de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

285,27 DOSCIENTOS OCHENTA Y


CINCO EUROS CON VEINTISIETE
CNTIMOS

2.148,94 DOS MIL CIENTO CUARENTA Y


OCHO EUROS CON NOVENTA Y
CUATRO CNTIMOS

1.1.2.93
Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%,
para montaje horizontal dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

2.784,25 DOS MIL SETECIENTOS


OCHENTA Y CUATRO EUROS
CON VEINTICINCO CNTIMOS

1.1.2.94
Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900 m/h, eficiencia sensible 51,6%,
para montaje horizontal dimensiones 1000x1000x500 mm y nivel de presin sonora de 48 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

4.021,02 CUATRO MIL VEINTIUN EUROS


CON DOS CNTIMOS

1.1.2.95
Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%,
para montaje horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

4.021,02 CUATRO MIL VEINTIUN EUROS


CON DOS CNTIMOS

Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%,
para montaje horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

24

Presupuesto y medicin

1.5

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe

Designacin
Parcial
(euros)

Total
(euros)

1 Instalaciones
1.1 Calefaccin, climatizacin y A.C.S.
1.1.1 Unidades autnomas de climatizacin
1.1.1.1

m Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con
aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor con aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,64
11,77
0,35
0,53
18,29

1.1.1.2

m Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con
aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor con aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,64
14,51
0,40
0,62
21,17

1.1.1.3

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 100 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 10 kW, EER = 3,47 (clase A), potencia calorfica nominal 11,2 kW, COP = 3,75 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

56,43
3.915,89
79,45
121,55
4.173,32

1.1.1.4

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 125 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 12,5 kW, EER = 3,09 (clase B), potencia calorfica nominal 14 kW, COP = 3,69 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

56,43
4.445,89
90,05
137,77
4.730,14

1.1.1.5

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia calorfica nominal 16 kW, COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

56,43
5.020,89
101,55
155,37
5.334,24

1.1.1.6

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 140 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C), potencia calorfica nominal 16 kW, COP = 3,61 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

56,43
5.020,89
101,55
155,37
5.334,24

1.1.1.7

Ud Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para gas R-410A, bomba de calor, con
tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz, modelo FDU 200 VS "MITSUBISHI HEAVY
INDUSTRIES", potencia frigorfica nominal 20 kW, EER = 3,03 (clase B), potencia calorfica nominal 22,4 kW, COP = 3,68 (clase A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

56,43
7.850,89
158,15
241,96
8.307,43

1.1.2 Sistemas de conduccin de aire


1.1.2.1

m Conducto autoportante rectangular para la distribucin de aire climatizado formado por panel rgido de lana de vidrio Ursa Air Zero "URSA
IBRICA AISLANTES", segn UNE-EN 13162, recubierto con un complejo kraft-aluminio reforzado en su cara exterior y con un tejido absorbente acstico de
color negro, en su cara interior, con los bordes largos canteados, de 25 mm de espesor.
Criterio de medicin de obra: Se medir la superficie realmente ejecutada segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

9,88
19,75
0,59
0,91
31,13

1.1.2.2

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.3

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

25

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.4

Total
(euros)

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.5

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.6

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.7

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.8

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.9

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.10

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.11

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.12

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.13

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.14

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.15

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.16

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.17

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

26

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.18

Total
(euros)

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.19

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.20

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.21

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.22

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.23

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.24

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.25

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.26

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.27

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.28

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.29

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.30

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
71,80
1,56
2,39
81,92

1.1.2.31

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

27

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.32

Total
(euros)

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.33

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.34

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.35

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.36

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.37

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.38

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.39

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.40

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
88,80
1,90
2,91
99,78

1.1.2.41

Ud Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
119,40
2,51
3,84
131,92

1.1.2.42

Ud Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", para instalar en alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,17
94,00
2,00
3,07
105,24

1.1.2.43

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.44

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

28

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.45

Total
(euros)

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.46

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.47

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.48

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.49

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.50

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.51

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.52

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.53

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.54

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.55

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.56

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

29

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.57

Total
(euros)

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.58

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.59

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.60

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.61

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 225x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,01
24,43
0,59
0,90
30,93

1.1.2.62

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,40
29,12
0,69
1,06
36,27

1.1.2.63

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,40
29,12
0,69
1,06
36,27

1.1.2.64

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,40
29,12
0,69
1,06
36,27

1.1.2.65

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,40
29,12
0,69
1,06
36,27

1.1.2.66

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,40
29,12
0,69
1,06
36,27

1.1.2.67

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.68

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

30

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.69

Total
(euros)

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.70

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.71

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.72

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.73

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,73
34,40
0,80
1,23
42,16

1.1.2.74

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 525x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,08
40,07
0,92
1,41
48,48

1.1.2.75

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,91
43,11
1,00
1,53
52,55

1.1.2.76

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 625x125 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,45
46,05
1,05
1,61
55,16

1.1.2.77

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,30
36,36
0,85
1,31
44,82

1.1.2.78

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,30
36,36
0,85
1,31
44,82

1.1.2.79

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 325x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,30
36,36
0,85
1,31
44,82

1.1.2.80

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,91
43,11
1,00
1,53
52,55

31

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.81

Total
(euros)

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,91
43,11
1,00
1,53
52,55

1.1.2.82

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,91
43,11
1,00
1,53
52,55

1.1.2.83

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 425x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

6,91
43,11
1,00
1,53
52,55

1.1.2.84

Ud Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente, de 525x225 mm, montada en
conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

7,57
50,23
1,16
1,77
60,73

1.1.2.85

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.86

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.87

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.88

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.89

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.90

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.91

Ud Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de 1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

5,55
265,98
5,43
8,31
285,27

1.1.2.92

Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%, para montaje
horizontal dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

28,20
2.017,24
40,91
62,59
2.148,94

1.1.2.93

Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900 m/h, eficiencia sensible 51,6%, para montaje
horizontal dimensiones 1000x1000x500 mm y nivel de presin sonora de 48 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

28,20
2.621,96
53,00
81,09
2.784,25

32

Presupuesto y medicin

Cuadro de Precios N 2. Mano de obra, Materiales, Restos de obra, Costes indirectos


Importe
N

Designacin
Parcial
(euros)

1.1.2.94

Total
(euros)

Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

33,87
3.793,48
76,55
117,12
4.021,02

1.1.2.95

Ud Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible 52,5%, para montaje
horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
Mano de obra
Materiales
Medios auxiliares
3 % Costes Indirectos

33,87
3.793,48
76,55
117,12
4.021,02

33

Presupuesto y medicin

34

Presupuesto y Medicin

35

Presupuesto y medicin

34

2
N

DESCRIPCION

Presupuesto y Medicin
UDS.

LARGO

ANCHO

ALTO

CANTIDAD

PRECIO

IMPORTE

18,29

942,12

21,17

767,20

4.173,32

4.173,32

4.730,14

4.730,14

5.334,24

16.002,72

5.334,24

5.334,24

8.307,43

41.537,15

31,13

54.718,76

81,92

81,92

81,92

81,92

81,92

81,92

81,92

81,92

81,92

81,92

1.1 Calefaccin, climatizacin y A.C.S.


1.1.1 Unidades autnomas de climatizacin
1.1.1.1

M. Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de
dimetro y 0,8 mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor
con aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
Planta baja
Planta 1
Cubierta

1.1.1.2

1
1
1

35,04
12,78
3,69

35,040
12,780
3,690
51,510

M. Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por un tubo para lquido de 3/8" de
dimetro y 0,8 mm de espesor con aislamiento de 9 mm de espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor
con aislamiento de 10 mm de espesor.
Criterio de medicin de obra: Se medir la longitud realmente ejecutada segn especificaciones de Proyecto.
Planta baja
Planta 1
Cubierta

1
1
1

28,06
6,00
2,18

28,060
6,000
2,180
36,240

1.1.1.3

Ud. Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para
gas R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior
trifsica
400V/50Hz,
modelonominal
FDU 10011,2
VS kW,
"MITSUBISHI
potencia frigorfica nominal 10 kW, EER = 3,47 (clase A),
potencia
calorfica
COP = 3,75HEAVY
(clase INDUSTRIES",
A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 017 (INEF)

1,000
1,000

1.1.1.4

Ud. Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para
gas R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior
trifsica potencia calorfica nominal 14 kW, COP = 3,69 (clase A).
WC (INEF)

1,000
1,000

1.1.1.5

Ud. Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para
gas R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior
trifsica
400V/50Hz,
modelonominal
FDU 14016VS
"MITSUBISHI
HEAVYA).INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C),
potencia calorfica
kW,
COP = 3,61 (clase
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
PASILLO PLANTA 1 (INEF)
OFICINA 116 (INEF)
WC_2 (INEF)

1.1.1.6

1
1
1

1,000
1,000
1,000
3,000

Ud. Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para
gas R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior
trifsica
400V/50Hz,
modelonominal
FDU 14016VS
"MITSUBISHI
HEAVYA).INDUSTRIES", potencia frigorfica nominal 14 kW, EER = 2,83 (clase C),
potencia
calorfica
kW,
COP = 3,61 (clase
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
PASILLO NORTE PLANTA 1 (INEF)

1,000
1,000

1.1.1.7

Ud. Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto rectangular, de alta presin, para
gas R-410A, bomba de calor, con tecnologa Inverter, gama semi-industrial (PAC), alimentacin a la unidad exterior
trifsica
400V/50Hz,
modelonominal
FDU 20022,4
VS kW,
"MITSUBISHI
potencia frigorfica nominal 20 kW, EER = 3,03 (clase B),
potencia
calorfica
COP = 3,68HEAVY
(clase INDUSTRIES",
A).
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA HONOR (INEF)
PASILLO (INEF)
CAFETERIA (INEF)

1
1
3

1,000
1,000
3,000
5,000

1.1.2 Sistemas de conduccin de aire


1.1.2.1

M. Conducto autoportante rectangular para la distribucin de aire climatizado formado por panel rgido de lana de vidrio Ursa
Air Zero "URSA IBRICA AISLANTES", segn UNE-EN 13162, recubierto con un complejo kraft-aluminio reforzado en su cara
exterior y con un tejido absorbente acstico de color negro, en su cara interior, con los bordes largos canteados, de 25 mm de
espesor.
Criterio de medicin de obra: Se medir la superficie realmente ejecutada segn especificaciones de Proyecto.
INEF

1.757,75

1.757,750
1.757,750

1.1.2.2

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 016

1,000
1,000

1.1.2.3

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 124

1,000
1,000

1.1.2.4

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 121

1,000
1,000

1.1.2.5

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 108

1,000
1,000

1.1.2.6

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 106

1,000
1,000

Suma y sigue ... 128.615,25

Presupuesto y medicin

35
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.7

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 122

UDS.

LARGO

ANCHO

ALTO

CANTIDAD

81,92

81,92

81,92

81,92

81,92

81,92

81,92

81,92

81,92

163,84

81,92

81,92

81,92

81,92

81,92

81,92

81,92

163,84

81,92

163,84

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 116

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 009

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 101

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 109

2,000
2,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 016

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 119

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 123

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 117

2,000
2,000

1.1.2.23

81,92

1,000
1,000

1.1.2.22

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 111

1.1.2.21

81,92

1,000
1,000

1.1.2.20

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 112

1.1.2.19

81,92

1,000
1,000

1.1.2.18

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 107

1.1.2.17

163,84

1,000
1,000

1.1.2.16

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 102

1.1.2.15

81,92

2,000
2,000

1.1.2.14

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 118

1.1.2.13

81,92

1,000
1,000

1.1.2.12

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 115

1.1.2.11

81,92

1,000
1,000

1.1.2.10

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 105

1.1.2.9

IMPORTE

1,000
1,000

1.1.2.8

PRECIO

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 120

2,000
2,000

Suma y sigue ... 130.335,57

Presupuesto y medicin

36
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.24

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 008

UDS.

LARGO

ANCHO

ALTO

CANTIDAD

99,78

99,78

99,78

99,78

99,78

199,56

99,78

99,78

99,78

99,78

99,78

99,78

99,78

997,80

99,78

299,34

99,78

199,56

99,78

299,34

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 113

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA DE ESPERA

2,000
2,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 015

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 014

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
REPROGRAFIA

1,000
1,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
CAFETERIA

10

10,000
10,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
CAFETERIA

3,000
3,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA DE JUNTAS

1.1.2.40

81,92

1,000
1,000

1.1.2.39

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 011

1.1.2.38

99,78

1,000
1,000

1.1.2.37

99,78

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
ATENCION

1.1.2.36

81,92

1,000
1,000

1.1.2.35

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 110

1.1.2.34

245,76

1,000
1,000

1.1.2.33

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 103/104

1.1.2.32

81,92

3,000
3,000

1.1.2.31

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
COMEDOR

1.1.2.30

81,92

1,000
1,000

1.1.2.29

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 017

1.1.2.28

81,92

1,000
1,000

1.1.2.27

81,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/473x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 018

1.1.2.26

IMPORTE

1,000
1,000

1.1.2.25

PRECIO

2,000
2,000

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/573x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
GESTION

3,000
3,000

Suma y sigue ... 133.585,21

Presupuesto y medicin

37
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.41

Ud. Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1-A/464x464/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA AUDIOVISUAL

UDS.

LARGO

ANCHO

ALTO

CANTIDAD

30,93

30,93

30,93

61,86

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 103/104

2,000
2,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 122

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 105

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 115

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 102

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 107

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 112

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 111

1,000
1,000

1.1.2.57

30,93

1,000
1,000

1.1.2.56

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 106

1.1.2.55

30,93

1,000
1,000

1.1.2.54

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 108

1.1.2.53

30,93

1,000
1,000

1.1.2.52

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 121

1.1.2.51

30,93

1,000
1,000

1.1.2.50

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 124

1.1.2.49

61,86

1,000
1,000

1.1.2.48

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 016

1.1.2.47

210,48

2,000
2,000

1.1.2.46

105,24

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 017

1.1.2.45

395,76

2,000
2,000

1.1.2.44

131,92

Ud. Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1-A/673x264/0/0/0/E6-C-0 "TROX", para instalar en
alturas de hasta 2,7 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA HONOR

1.1.2.43

IMPORTE

3,000
3,000

1.1.2.42

PRECIO

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 116

1,000
1,000

Suma y sigue ... 134.717,26

Presupuesto y medicin

38
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.58

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 009

UDS.

LARGO

ANCHO

ALTO

CANTIDAD

36,27

36,27

36,27

36,27

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

42,16

48,48

48,48

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 018

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 118

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 110

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
ATENCION

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 011

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 113

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 015

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 014

1,000
1,000

1.1.2.74

72,54

1,000
1,000

1.1.2.73

36,27

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 008

1.1.2.72

36,27

2,000
2,000

1.1.2.71

36,27

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 117

1.1.2.70

36,27

1,000
1,000

1.1.2.69

36,27

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 123

1.1.2.68

30,93

1,000
1,000

1.1.2.67

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 119

1.1.2.66

61,86

1,000
1,000

1.1.2.65

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 016

1.1.2.64

30,93

2,000
2,000

1.1.2.63

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 109

1.1.2.62

30,93

1,000
1,000

1.1.2.61

30,93

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 225x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 101

1.1.2.60

IMPORTE

1,000
1,000

1.1.2.59

PRECIO

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 525x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
REPROGRAFIA

1,000
1,000

Suma y sigue ... 135.433,13

Presupuesto y medicin

39
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.75

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
CAFETERIA

UDS.

LARGO

ANCHO

ALTO

CANTIDAD

52,55

210,20

52,55

105,10

52,55

105,10

52,55

52,55

60,73

121,46

285,27

285,27

285,27

285,27

285,27

1.426,35

285,27

1.141,08

285,27

1.426,35

285,27

1.141,08

285,27

285,27

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA HONOR

2,000
2,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
CAFETERIA

2,000
2,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA DE ESPERA

1,000
1,000

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 525x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
GESTION

2,000
2,000

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000
Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000

1.1.2.87

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

1.1.2.88

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

1.1.2.89

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

1.1.2.90

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.

5,000

4,000

5,000

4,000
1.1.2.91

134,46

4,000
4,000

1.1.2.86

44,82

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 425x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
CAFETERIA

1.1.2.85

89,64

3,000
3,000

1.1.2.84

44,82

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA AUDIOVISUAL

1.1.2.83

89,64

2,000
2,000

1.1.2.82

44,82

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA DE JUNTAS

1.1.2.81

55,16

2,000
2,000

1.1.2.80

55,16

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 325x225 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
COMEDOR

1.1.2.79

262,75

1,000
1,000

1.1.2.78

52,55

Ud. Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas horizontales regulables individualmente,
de 625x125 mm, montada en conducto rectangular no metlico.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 120

1.1.2.77

IMPORTE

5,000
5,000

1.1.2.76

PRECIO

Ud. Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa perfilada de acero galvanizado, de
1400x330 mm.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
1,000

Suma y sigue ... 142.649,86

Presupuesto y medicin

40
PRESUPUESTO PARCIAL N 1 Instalaciones

DESCRIPCION

1.1.2.92

Ud. Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 900 m/h, eficiencia sensible 53,9%,
para montaje horizontal dimensiones 800x800x330 mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
PASILLO PLANTA 1
WC
PASILLO
ESCALERAS
CAFETERIA
OFICINA 017

1.1.2.93

UDS.

1
1
1
1
3
1

LARGO

ANCHO

ALTO

CANTIDAD

1,000
1,000
1,000
1,000
3,000
1,000
8,000

2.148,94

17.191,52

2.784,25

2.784,25

4.021,02

4.021,02

4.021,02

4.021,02

1,000
1,000

Ud. Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible
52,5%, para montaje horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
ESCALERA PLANTA 1

1,000
1,000

1.1.2.95

IMPORTE

sensible
Ud. Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 1900 m/h,
51,6%, para montaje horizontal dimensiones 1000x1000x500eficiencia
mm y nivel de presin sonora de 48 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
SALA HONOR

1.1.2.94

PRECIO

Ud. Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de 3100 m/h, eficiencia sensible
52,5%, para montaje horizontal dimensiones 1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m.
Criterio de medicin de obra: Se medir el nmero de unidades realmente ejecutadas segn especificaciones de Proyecto.
OFICINA 116

1,000
1,000

Total presupuesto parcial n 1 ... 170.667,67

Presupuesto y medicin

Resumen de presupuesto

Estudio de viabilidad energtica con ENERGYPLUS e implementacin del sistema de climatizacin con CYPE INGENIEROS del edificio de
oficinas de INEF Lleida
RESUMEN POR CAPITULOS
CAPITULO INSTALACIONES

170.667,67
REDONDEO..............................
PRESUPUESTO DE EJECUCION MATERIAL.....

170.667,67

EL PRESUPUESTO DE EJECUCION MATERIAL ASCIENDE A LAS EXPRESADAS CIENTO SETENTA MIL SEISCIENTOS SESENTA Y SIETE EUROS
CON SESENTA Y SIETE CNTIMOS.

41

Presupuesto y medicin

Presupuesto de ejecucin por contrata

Proyecto: Estudio de viabilidad energtica con ENERGYPLUS e implementacin del sistema de climatizacin con CYPE INGENIEROS del edificio de
oficinas de INEF Lleida
Importe
Captulo
Captulo 1 Instalaciones
Captulo 1.1 Calefaccin, climatizacin y A.C.S.
Captulo 1.1.1 Unidades autnomas de climatizacin
Captulo 1.1.2 Sistemas de conduccin de aire

170.667,67
170.667,67
73.486,89
97.180,78

Presupuesto de ejecucin material


0% de gastos generales
0% de beneficio industrial

170.667,67
0,00
0,00

Suma
18% IVA

170.667,67
30.720,18

Presupuesto de ejecucin por contrata

201.387,85

Asciende el presupuesto de ejecucin por contrata a la expresada cantidad de DOSCIENTOS UN MIL TRESCIENTOS OCHENTA Y SIETE EUROS CON OCHENTA Y CINCO CNTIMOS.

42

Estudio energtico con EnergyPlus e


implementacin del sistema de
climatizacin con CYPE Ingenieros del
edificio de oficinas de INEF Lleida
TITULACIN: Ingeniera Tcnica Industrial Esp.
Electrnica Industrial

6. ESTUDIO DE SEGURIDAD Y SALUD


AUTOR: Fernando Pallars Cepero
DIRECTOR: Jos Ramn Lpez Lpez
CONVOCATORIA: Junio 2011

Estudio de Seguridad y Salud

ndice
0

HOJA DE IDENTIFICACIN............................................................................................................. 5

OBJETO DEL ESTUDIO DE SEGURIDAD Y SALUD.................................................................... 6

PROMOTOR PROPIETARIO ......................................................................................................... 6

AUTOR / ES DEL ESTUDIO DE SEGURIDAD Y SALUD ............................................................. 6

DATOS DEL PROYECTO ................................................................................................................... 7

4.1

AUTOR / ES DEL PROYECTO ............................................................................................................. 7

4.2

COORDINADOR DE SEGURIDAD DURANTE LA ELABORACIN DEL PROYECTO................................... 7

4.3

TIPOLOGA DE LA OBRA................................................................................................................... 7

4.4

SITUACIN ...................................................................................................................................... 7

4.5

PRESUPUESTO DE EJECUCIN MATERIAL DEL PROYECTO................................................................. 7

4.6

PLAZO DE EJECUCIN ...................................................................................................................... 7

4.7

MANO DE OBRA PREVISTA ............................................................................................................... 7

4.8

OFICIOS QUE INTERVIENEN EN EL DESARROLLO DE LA OBRA .......................................................... 8

4.9

TIPOLOGA DE LOS MATERIALES A UTILIZAR EN LA OBRA ............................................................... 8

INSTALACIONES PROVISIONALES............................................................................................. 12
5.1
5.1.1

Acometida ................................................................................................................................ 12

5.1.2

Cuadro General....................................................................................................................... 13

5.1.3

Conductores............................................................................................................................. 13

5.1.4

Conexiones de corriente .......................................................................................................... 13

5.1.5

Maquinaria elctrica ............................................................................................................... 13

5.1.6

Alumbrado provisional ............................................................................................................ 14

5.1.7

Alumbrado porttil .................................................................................................................. 14

5.2
5.2.1
6

INSTALACIN ELCTRICA PROVISIONAL DE OBRA ......................................................................... 12

OTRAS INSTALACIONES. PREVENCIN Y PROTECCIN CONTRA INCENDIOS ................................... 14


Emplazamiento y distribucin de los extintores obra.............................................................. 16

SERVICIOS DE SALUBRIDAD Y CONFORT DEL PERSONAL ............................................... 16


6.1

SERVICIOS HIGINICOS .................................................................................................................. 16

6.2

VESTUARIOS ................................................................................................................................. 17

6.3

COMEDOR ..................................................................................................................................... 17

6.4

LOCAL DE DESCANSO .................................................................................................................... 17

6.5

LOCAL DE ASISTENCIA A ACCIDENTADOS ...................................................................................... 17

Estudio de Seguridad y Salud

REAS AUXILIARES........................................................................................................................ 18
7.1

CENTRALES Y PLANTAS ................................................................................................................. 18

7.2

TALLERES ..................................................................................................................................... 19

7.3

ZONAS DE ACOPIO. ALMACENES ................................................................................................... 20

TRATAMIENTO DE RESIDUOS ..................................................................................................... 20

TRATAMIENTO DE MATERIALES Y / O SUSTANCIAS PELIGROSAS................................ 21

10

9.1

MANIPULACIN ............................................................................................................................ 21

9.2

DELIMITACIN / ACONDICIONAMIENTO DE ZONAS DE ACOPIO....................................................... 21

9.2.1

Txicos, muy txicos, nocivos, carcingenos, mutagnicos, txicos para la reproduccin .... 22

9.2.2

Corrosivos, Irritantes .............................................................................................................. 22

CONDICIONES DEL ENTORNO..................................................................................................... 22


10.1

EMPLEO DEL CIERRE DE LA OBRA .................................................................................................. 22

10.2

SITUACIN DE CASETAS Y CONTENEDORES ................................................................................... 23

10.3

SERVICIOS AFECTADOS ................................................................................................................. 23

10.4

NECESIDADES ............................................................................................................................... 23

10.5

CARACTERSTICAS DEL ENTORNO ................................................................................................. 24

11

UNIDADES CONSTRUCTIVAS ....................................................................................................... 24

12

DETERMINACIN DEL PROCESO CONSTRUCTIVO ............................................................. 24


12.1

PROCEDIMIENTOS DE EJECUCIN .................................................................................................. 24

12.2

ORDEN DE EJECUCIN DE LOS TRABAJOS ...................................................................................... 24

12.3

DETERMINACIN DEL TIEMPO EFECTIVO DE DURACIN. PLAN DE EJECUCIN ............................... 25

13 SISTEMAS Y / O ELEMENTOS DE SEGURIDAD Y SALUD INHERENTES O


INCORPORADOS AL MISMO PROCESO CONSTRUCTIVO............................................................. 25
14

15

MEDIO AMBIENTE LABORAL ...................................................................................................... 25


14.1

AGENTES ATMOSFRICOS .............................................................................................................. 25

14.2

ILUMINACIN ................................................................................................................................ 25

14.3

RUIDO ........................................................................................................................................... 26

14.4

POLVO ........................................................................................................................................... 27

14.5

ORDEN Y LIMPIEZA........................................................................................................................ 29

MANIPULACIN DE MATERIALES............................................................................................. 30
15.1

LOS PRINCIPIOS BSICOS DE LA MANIPULACIN DE MATERIALES .................................................. 31

15.2

MANEJO DE CARGAS SIN MEDIOS MECNICOS ............................................................................... 31

16

MEDIOS AUXILIARES DE UTILIDAD PREVENTIVA (MAUP) ............................................... 32

17

SISTEMAS DE PROTECCIN COLECTIVA (SPC)..................................................................... 34

18

CONDICIONES DE LOS EQUIPOS DE PROTECCIN INDIVIDUAL (EPI) .......................... 35

19

RECURSOS PREVENTIVOS ............................................................................................................ 35

Estudio de Seguridad y Salud

20

SEALIZACIN Y BALIZAMIENTO ............................................................................................ 37

21

CONDICIONES DE ACCESO DE LA VA PUBLICA................................................................... 38

22

NORMAS DE POLICA ..................................................................................................................... 39


22.1

CONTROL DE ACCESOS .................................................................................................................. 39

22.2

COORDINACIN DE INTERFERENCIAS Y SEGURIDAD A PIE DE OBRA ............................................... 39

22.3

MBITO DE OCUPACIN DE LA VA PUBLICA ................................................................................. 39

22.3.1

Empleo del cierre de la obra .............................................................................................. 39

22.3.2

Situacin de casetas y contenedores................................................................................... 40

22.3.3

Cambios de la Zona Ocupada............................................................................................. 40

22.4

22.4.1

Vallas .................................................................................................................................. 40

22.4.2

Acceso a la obra ................................................................................................................. 41

22.5

OPERACIONES QUE AFECTAN EL MBITO PBLICO ........................................................................ 41

22.5.1

Entradas y salidas de vehculos y maquinaria.................................................................... 41

22.5.2

Carga y descarga................................................................................................................ 41

22.5.3

Descarga, acopio y evacuacin de tierras y escombros ..................................................... 42

22.5.4

Protecciones para evitar la cada de objetos en la va pblica .......................................... 42

22.6

LIMPIEZA E INCIDENCIA SOBRE EL AMBIENTE QUE AFECTA EL MBITO PBLICO ........................... 43

22.6.1

Limpieza.............................................................................................................................. 43

22.6.2

Ruidos. Horario de trabajo................................................................................................. 43

22.6.3

Polvo ................................................................................................................................... 44

22.7

RESIDUOS QUE AFECTAN AL MBITO PUBLICO .............................................................................. 44

22.8

CIRCULACIN DE VEHCULOS Y PEATONES QUE AFECTAN EL MBITO PUBLICO ............................ 44

22.8.1

Sealizacin y proteccin ................................................................................................... 44

22.8.2

Dimensiones mnimas de itinerarios y pasos para peatones .............................................. 44

22.8.3

Elementos de proteccin ..................................................................................................... 44

22.8.4

Alumbrado y balizamiento luminoso................................................................................... 45

22.8.5

Balizamiento y defensa ....................................................................................................... 45

22.8.6

Accesibilidad de personas con movilidad reducida............................................................ 46

22.8.7

Retirada de sealizacin y balizamiento ............................................................................ 46

22.9

23

CERRAMIENTOS DE LA OBRA QUE AFECTAN EL MBITO PBLICO .................................................. 40

PROTECCIN Y TRASLADO DE ELEMENTOS EMPLAZADOS EN LA VA PBLICA ............................... 46

22.9.1

rboles y jardines ............................................................................................................... 46

22.9.2

Paradas de autobs ............................................................................................................ 47

RIESGOS DE DAOS A TERCEROS Y MEDIDAS DE PROTECCIN.................................... 47


23.1

RIESGOS DE DAOS A TERCEROS ................................................................................................... 47

23.2

MEDIDAS DE PROTECCIN A TERCEROS ......................................................................................... 47

Estudio de Seguridad y Salud

24

PREVENCIN DE RIESGOS CATASTRFICOS ........................................................................ 48

25

PREVISIONES DE SEGURIDAD POR TRABAJOS POSTERIORES ........................................ 48

Estudio de Seguridad y Salud

Hoja de identificacin

Titulo del proyecto


Estudio energtico con EnergyPlus e implementacin del sistema de climatizacin con
CYPE Ingenieros del edificio de oficinas de INEF Lleida

Cdigo de identificacin
48011825M

Situacin
Pda. Caparrella, s/n 25192 Lleida

Cliente
TECNOMEK INGEMECANICA S.L. NIF: 77609211 Q
C / Doctor Mallafr n16, 43002 (Tarragona)
Tel.: 977 23 15 33, Fax: 977 23 21 60
Correo electrnico: mail@tecnomecanica.com
Gerente: Antonio Jurado Lpez

Profesional
Pallars Cepero, Fernando
C / Mare Molas 6 8 43202 Reus (Tarragona)
Tel.: 977 33 00 62, Fax: 977 33 00 63
Correo electrnico: fernando.pallares@estudiants.urv.cat
Num. de colegiado: 1987

Empresa contratada
INEF Lleida
Pda. Caparrella, s/n 25192 Lleida
Correo electrnico: ineflleida@inef.cat
Tel.: 973 22 14 36, Fax: 973 15 11 01

Data y firmas de los anteriormente citados

Reus, Mayo de 2011

Estudio de Seguridad y Salud

Objeto del Estudio de Seguridad y Salud

El presente E.S.S. tiene como objetivo establecer las bases tcnicas, para fijar los
parmetros de la prevencin de riesgos profesionales durante la realizacin de los trabajos
de ejecucin de las obras del Proyecto objeto de este estudio, as como cumplir con las
obligaciones que se desprenden de la Ley 31/1995 y del RD 1627/1997, con el fin de
facilitar el control y el seguimiento de los compromisos adquiridos al respecto por parte del
/ los Contratista / as.
En el presente Estudio de Seguridad y Salud se ha llevado a cabo un estudio profundo de
los riesgos inherentes a la ejecucin de la obra y de las medidas preventivas y cautelares
consiguientes para garantizar la seguridad de las personas en la ejecucin de las obras en
cumplimiento de lo determina la Ley 3 / 2007 del 4 de julio de la obra pblica en su
artculo 18.3.h).
De esta manera, se integra en el Proyecto Ejecutivo / Constructivo, las premisas bsicas
para las que el / los Contratista / s constructor / es pueda / n prever y planificar, los
recursos tcnicos y humanos necesarios para el desempeo de las obligaciones preventivas
en este centro de trabajo, de conformidad a su Plan de Accin Preventiva propio de
empresa, su organizacin funcional y los medios a utilizar, debiendo quedar todo lo
recogido en el Plan de Seguridad y Salud, que deber / n de presentarse al Coordinador de
Seguridad y Salud en fase de Ejecucin, con antelacin al inicio de las obras, para su
aprobacin y el inicio de los trmites de Declaracin de Apertura ante la Autoridad
Laboral. En caso de que sea necesario implementar medidas de seguridad no previstas en
el presente Estudio, a peticin expresa del coordinador de seguridad y salud en fase de
ejecucin de la obra, el contratista elaborar el correspondiente anexo al Plan de Seguridad
y Salud de la obra que desarrollar y determinar las medidas de seguridad a llevar a cabo
con la memoria, pliego de condiciones, mediciones, precios y presupuesto que le sean de
aplicacin en su caso.

Promotor Propietario

Promotor: INEF Lleida


NIF: P-4316500-J
Direccin: Pda. Caparrella, s/n
Poblacin: Lleida

Autor / es del Estudio de Seguridad y Salud

Redactor E.S.S.: Fernando Pallars Cepero


Titulacin: Ingeniero tcnico industrial
Colegiado nm. : 1.987

Estudio de Seguridad y Salud

4
4.1

Datos del proyecto


Autor / es del proyecto

Redactor E.S.S.: Fernando Pallars Cepero


Titulacin: Ingeniero tcnico industrial
Colegiado nm. : 1.987

4.2

Coordinador de seguridad durante la elaboracin del proyecto

Coordinador de S & S designado por el promotor: Fernando Pallars Cepero


Titulacin: Ingeniero tcnico industrial
Colegiado nm. : 1.987

4.3

Tipologa de la obra

Los parmetros de la prevencin de riesgos profesionales descritos en el presente E.S.S.


son los relacionados con la realizacin de los trabajos de ejecucin de las instalaciones
descritas en el proyecto de climatizacin de un edificio de oficinas.

4.4

Situacin

Emplazamiento: Pda. Caparrella, s/n


Cdigo Postal: 25192
Poblacin: Lleida

4.5

Presupuesto de ejecucin material del proyecto

El Presupuesto de Ejecucin Material (PEM) estimado de referencia para este proyecto,


excluida la Seguridad y Salud complementaria, Gastos Generales, es de 170.667,67.
(CIENTO SETENTA MIL SEISCIENTOS SESENTA Y SIETE EUROS CON SESENTA
Y SIETE CNTIMOS).

4.6

Plazo de ejecucin

El plazo estimado de duracin de los trabajos de ejecucin de la obra es de 4 meses.

4.7

Mano de obra prevista

La estimacin de mano de obra en punta de ejecucin es de 2 personas.

Estudio de Seguridad y Salud

4.8

Oficios que intervienen en el desarrollo de la obra

Oficial 1 instalador de climatizacin.


Ayudante instalador de climatizacin.

4.9

Tipologa de los materiales a utilizar en la obra

Tubo rgido de PVC, enchufable, curvable en caliente, de color negro, de 16 mm de


dimetro nominal, para canalizacin fija en superficie. Resistencia a la compresin 1250
N, resistencia al impacto 2 julios, temperatura de trabajo -5C hasta 60C, con grado de
proteccin IP 547 segn UNE 20324, propiedades elctricas: aislante, no propagador de la
llama. Segn UNE-EN 61386-1 y UNE-EN 61386-22. Incluso p/p de abrazaderas,
elementos de sujecin y accesorios (Curvas, manguitos, tes, codos y curvas flexibles).
Cinta autoadhesiva de aluminio de 50 micras de espesor y 65 mm de ancho a base de
resinas acrlicas, para el sellado y fijacin del aislamiento.
Soporte metlico de acero galvanizado para sujecin al forjado de conducto rectangular de
lana mineral para la distribucin de aire en climatizacin.
Panel rgido de lana de vidrio Ursa Air Zero "URSA IBRICA AISLANTES", segn
UNE-EN 13162, recubierto con un complejo kraft-aluminio reforzado en su cara exterior y
con un tejido absorbente acstico de color negro, en su cara interior, con los bordes largos
canteados, de 25 mm de espesor, para la formacin de conductos autoportantes para la
distribucin de aire en climatizacin, resistencia trmica 0,75 (mK)/W, conductividad
trmica 0,033 W/(mK), Euroclase B-s1 d0 de reaccin al fuego, con cdigo de designacin
MW-UNE-EN 13162-T5-CS(10)5-Z100-SD10.
Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por
un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con aislamiento de 9 mm de
espesor y un tubo para gas de 5/8" de dimetro y 0,8 mm de espesor con aislamiento de 10
mm de espesor, teniendo el cobre un contenido de aceite residual inferior a 4 mg/m y
siendo el aislamiento de coquilla flexible de espuma elastomrica con revestimiento
superficial de pelcula de polietileno, para una temperatura de trabajo entre -45 y 100C,
suministrada en rollo, segn UNE-EN 12735-1.
Lnea frigorfica doble realizada con tubera flexible de cobre sin soldadura, formada por
un tubo para lquido de 3/8" de dimetro y 0,8 mm de espesor con aislamiento de 9 mm de
espesor y un tubo para gas de 1" de dimetro y 0,8 mm de espesor con aislamiento de 10
mm de espesor, teniendo el cobre un contenido de aceite residual inferior a 4 mg/m y
siendo el aislamiento de coquilla flexible de espuma elastomrica con revestimiento
superficial de pelcula de polietileno, para una temperatura de trabajo entre -45 y 100C,
suministrada en rollo, segn UNE-EN 12735-1.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter,
gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz,
modelo FDU 100 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica

Estudio de Seguridad y Salud

nominal 10 kW (temperatura de bulbo seco en el interior 27C, temperatura de bulbo


hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura de
bulbo hmedo en el exterior 24C), potencia calorfica nominal 11,2 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura
de bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,47 (clase A), COP
(coeficiente energtico) 3,75 (clase A), formado por una unidad interior FDU 100 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 37 dBA, caudal de aire (velocidad alta)
2040 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una
unidad exterior FDC 100 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 49 dBA y caudal de aire 4500 m/h, con control de condensacin y
posibilidad de integracin en un sistema domtico KNX/EIB a travs de un interface.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter,
gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz,
modelo FDU 125 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica
nominal 12,5 kW (temperatura de bulbo seco en el interior 27C, temperatura de bulbo
hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura de
bulbo hmedo en el exterior 24C), potencia calorfica nominal 14 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura
de bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,09 (clase B), COP
(coeficiente energtico) 3,69 (clase A), formado por una unidad interior FDU 125 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una
unidad exterior FDC 125 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 50 dBA y caudal de aire 4500 m/h, con control de condensacin y
posibilidad de integracin en un sistema domtico KNX/EIB a travs de un interface.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter,
gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz,
modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica
nominal 14 kW (temperatura de bulbo seco en el interior 27C, temperatura de bulbo
hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura de
bulbo hmedo en el exterior 24C), potencia calorfica nominal 16 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura
de bulbo hmedo en el exterior 6C), EER (calificacin energtica) 2,83 (clase C), COP
(coeficiente energtico) 3,61 (clase A), formado por una unidad interior FDU 140 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una
unidad exterior FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 51 dBA y caudal de aire 4500 m/h, con control de condensacin y
posibilidad de integracin en un sistema domtico KNX/EIB a travs de un interface.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter,
gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz,

Estudio de Seguridad y Salud

modelo FDU 140 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica


nominal 14 kW (temperatura de bulbo seco en el interior 27C, temperatura de bulbo
hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura de
bulbo hmedo en el exterior 24C), potencia calorfica nominal 16 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura
de bulbo hmedo en el exterior 6C), EER (calificacin energtica) 2,83 (clase C), COP
(coeficiente energtico) 3,61 (clase A), formado por una unidad interior FDU 140 V, de
350x1370x650 mm, nivel sonoro (velocidad baja) 38 dBA, caudal de aire (velocidad alta)
2520 m/h, presin de aire (velocidad alta) 50 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 130 Pa, control por cable modelo RC-E3, y una
unidad exterior FDC 140 VS, con compresor DC PAM Inverter, de 845x970x370 mm,
nivel sonoro 51 dBA y caudal de aire 4500 m/h, con control de condensacin y
posibilidad de integracin en un sistema domtico KNX/EIB a travs de un interface.
Equipo de aire acondicionado, sistema aire-aire split 1x1, con distribucin por conducto
rectangular, de alta presin, para gas R-410A, bomba de calor, con tecnologa Inverter,
gama semi-industrial (PAC), alimentacin a la unidad exterior trifsica 400V/50Hz,
modelo FDU 200 VS "MITSUBISHI HEAVY INDUSTRIES", potencia frigorfica
nominal 20 kW (temperatura de bulbo seco en el interior 27C, temperatura de bulbo
hmedo en el interior 19C, temperatura de bulbo seco en el exterior 35C, temperatura de
bulbo hmedo en el exterior 24C), potencia calorfica nominal 22,4 kW (temperatura de
bulbo seco en el interior 20C, temperatura de bulbo seco en el exterior 7C, temperatura
de bulbo hmedo en el exterior 6C), EER (calificacin energtica) 3,03 (clase B), COP
(coeficiente energtico) 3,68 (clase A), formado por una unidad interior FDU 200 V, de
360x1570x830 mm, nivel sonoro (velocidad baja) 51 dBA, caudal de aire (velocidad alta)
3600 m/h, presin de aire (velocidad alta) 100 Pa, presin de aire a velocidad ultra alta
(ajuste del ventilador a alta potencia) 200 Pa, control por cable modelo RC-E3, y una
unidad exterior FDC 200 VS, con compresor DC PAM Inverter, de 1300x970x370 mm,
nivel sonoro 57 dBA y caudal de aire 9000 m/h, con control de condensacin y
posibilidad de integracin en un sistema domtico KNX/EIB a travs de un interface.
Cable bus apantallado de 3 hilos, de 0,5 mm de seccin por hilo.
Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de
900 m/h, eficiencia sensible 53,9%, para montaje horizontal dimensiones 800x800x330
mm y nivel de presin sonora de 43 dBA en campo libre a 1,5 m, con caja de acero
galvanizado y plastificado, color marfil, con aislamiento, clase B segn UNE-EN 13501-1,
soportes antivibratorios, embocaduras de 250 mm de dimetro con junta estanca y filtros
G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores centrfugos de
doble odo de accionamiento directo con motores elctricos monofsicos de 4 velocidades
de 355 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa con proteccin
IP 55.
Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de
1900 m/h, eficiencia sensible 51,6%, para montaje horizontal dimensiones
1000x1000x500 mm y nivel de presin sonora de 48 dBA en campo libre a 1,5 m, con caja
de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn UNE-EN
13501-1, soportes antivibratorios, embocaduras de 315 mm de dimetro con junta estanca
y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de

10

Estudio de Seguridad y Salud

3 velocidades de 373 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa
con proteccin IP 55.
Recuperador de calor aire-aire, con intercambiador de flujo cruzado, caudal mximo de
3100 m/h, eficiencia sensible 52,5%, para montaje horizontal dimensiones
1250x1250x600 mm y nivel de presin sonora de 52 dBA en campo libre a 1,5 m, con caja
de acero galvanizado y plastificado, color marfil, con aislamiento, clase B segn UNE-EN
13501-1, soportes antivibratorios, embocaduras de 355 mm de dimetro con junta estanca
y filtros G4 con eficacia del 86%, clase D segn UNE-EN 13501-1, 2 ventiladores
centrfugos de doble odo de accionamiento directo con motores elctricos monofsicos de
3 velocidades de 550 W cada uno, aislamiento F, proteccin IP 20, caja de bornes externa
con proteccin IP 55.
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 225x125 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 325x125 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 425x125 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 525x125 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 625x125 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 325x225 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 425x225 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Rejilla de retorno, de aluminio extruido, anodizado color natural E6-C-0, con lamas
horizontales regulables individualmente, de 525x225 mm, fijacin mediante tornillos
vistos (con marco de montaje de chapa de acero galvanizado).
Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1A/473x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad
perimetral, con una direccin de impulsin, anodizado color natural E6-C-0.

11

Estudio de Seguridad y Salud

Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1A/573x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad
perimetral, con una direccin de impulsin, anodizado color natural E6-C-0.
Difusor rectangular de lamas directrices fijas, de aluminio extruido, ADQ-1A/673x264/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad
perimetral, con una direccin de impulsin, anodizado color natural E6-C-0.
Difusor cuadrado de lamas directrices fijas, de aluminio extruido, ADQ-1A/464x464/0/0/0/E6-C-0 "TROX", con marco frontal con perfiles cortados a inglete
provistos de agujeros avellanados para sujecin en obra, con junta de estanqueidad
perimetral, con una direccin de impulsin, anodizado color natural E6-C-0.
Rejilla de intemperie para instalaciones de ventilacin, marco frontal y lamas de chapa
perfilada de acero galvanizado, de 1400x330 mm, tela metlica de acero galvanizado con
malla de 20x20 mm.
Material auxiliar para instalaciones de climatizacin.

5
5.1

Instalaciones provisionales
Instalacin elctrica provisional de obra

Se harn los trmites oportunos, para que la compaa suministradora de electricidad o una
acreditada haga la conexin desde la lnea suministradora hasta los cuadros donde se ha de
instalar la caja general de proteccin y los contadores, desde los que los Contratistas
procedern a montar el resto de la instalacin elctrica de suministro provisional obra,
conforme al Reglamento Electrotcnico de Baja Tensin, segn el proyecto de un
instalador autorizado.
Se realizar una distribucin sectorizada, que garantice la adecuada suministro a todos los
cortes y puntos de consumo de la obra, con conductor tipo V -750 de cobre de secciones
adecuadas canalizadas en tubo de PVC, rgido blindado o flexible segn su recorrido, pero
siempre con el apantallamiento suficiente para resistir el paso de vehculos y trfico normal
de una obra. La instalacin elctrica tendr una red de proteccin de tierra mediante cable
de cobre desnudo que estar conectado a una jabalina, placas de conexin en el suelo,
segn clculo del proyectista y comprobacin del instalador. Las medidas generales de
seguridad en la instalacin elctrica son las siguientes:

5.1.1

Acometida

Se realizar de acuerdo con la compaa de suministro. Su seccin vendr determinada por


la potencia instalada. Existir un mdulo de proteccin (fusibles y limitadores de potencia).
Estar situada siempre fuera del alcance de la maquinaria de elevacin y las zonas sin paso
de vehculos.

12

Estudio de Seguridad y Salud

5.1.2

Cuadro General

Dispondr de proteccin hacia los contactos indirectos mediante diferencial de sensibilidad


mnima de 300 mA. Para alumbrado y herramientas elctricas de doble aislamiento su
sensibilidad deber ser de 30 mA.
Dispondr de proteccin hacia los contactos directos para que no existan partes en tensin
al descubierto (sumideros, tornillos de conexin, terminales automticos, etc.).
Dispondr de interruptores de corte magnetotrmicos para cada uno de los circuitos
independientes. Los de los aparatos de elevacin debern ser de corte omnipolar (cortarn
todos los conductores, incluido el neutro).
Ir conectado a tierra (resistencia mxima 78). Al inicio de la obra se realizar una
conexin en el suelo provisional que deber estar conectada al anillo de tierras, a
continuacin despus de realizados los fundamentos.
Estar protegida de la intemperie.
Es recomendable el uso de llave especial para su apertura.
Se sealizar con seal normalizada de advertencia de riesgo elctrico (RD 485/97).

5.1.3

Conductores

Dispondrn de un aislamiento de 1000 V de tensin nominal, que se puede reconocer por


su impresin sobre el mismo aislamiento.
Los conductores irn enterrados, o grapados los paramentos verticales o techos alejados de
las zonas de paso de vehculos y / o personas.
Los ensambles debern ser realizados mediante "juegos" de enchufes, nunca con regletas
de conexin.

5.1.4

Conexiones de corriente

Irn provistas de imbornales de conexin en el suelo, excepcin hecha para la conexin de


equipos de doble aislamiento.
Ampararn mediante un magnetotrmico que facilite su desconexin.

5.1.5

Maquinaria elctrica

Dispondr de conexin a tierra.


Los aparatos de elevacin irn provistos de interruptor de corte omnipolar.

13

Estudio de Seguridad y Salud

Se conectarn a tierra la gua de los elevadores y los carriles de gra o de otros aparatos de
elevacin fijos.
El establecimiento de conexin a las bases de corriente, se har siempre con clavija
normalizada.

5.1.6

Alumbrado provisional

El circuito dispondr de proteccin diferencial de alta sensibilidad, de 30 mA.


Los portalmparas debern ser de tipo aislante.
Se conectar la fase en el punto central del portalmparas y el neutro en el lateral ms
prximo al trompo.
Los puntos de luz en las zonas de paso se instalarn en los techos para garantizar su
inaccesibilidad a las personas.

5.1.7

Alumbrado porttil

La tensin de suministro no sobrepasar los 24 V o alternativamente dispondr de doble


aislamiento, Clase II de proteccin intrnseca en previsin de contactos indirectos.
Dispondr de mango aislante, carcasa de proteccin de la bombilla con capacidad antigolpes y soporte de sustentacin.

5.2

Otras instalaciones. Prevencin y proteccin contra incendios

Para los trabajos que comporten la introduccin de llama o de equipo productor de chispas
en zonas con riesgo de incendio o de explosin, habr que tener un permiso de forma
explcita, hecho por una persona responsable, donde junto a las fechas inicial y final , la
naturaleza y la localizacin del trabajo, el equipo a usar, se indicarn las precauciones a
adoptar respecto a los combustibles presentes (slidos, lquidos, gases, vapores, polvo),
limpieza previa de la zona y los medios adicionales de extincin, vigilancia y ventilacin
adecuados.
Las precauciones generales para la prevencin y la proteccin contra incendios sern las
siguientes
La instalacin elctrica deber estar de acuerdo con lo establecido en la Instruccin MIBT
026 del vigente Reglamento Electrotcnico de Baja Tensin para locales con riesgo de
incendios o explosiones.
Se limitar la presencia de productos inflamables en los lugares de trabajo en las
cantidades estrictamente necesarias para el proceso productivo no se detenga. El resto se
guardar en locales diferentes al de trabajo, y en caso de que esto no fuera posible se har
en recintos aislados y acondicionados. En todo caso, los locales y los recintos aislados
cumplirn lo especificado en la Norma Tcnica "MIE-APQ-001 Almacenamiento de
14

Estudio de Seguridad y Salud

Lquidos inflamables y combustibles" del Reglamento sobre Almacenamiento de


Productos Qumicos.
Se instalarn recipientes contenedores hermticos e incombustibles en que se debern
depositar los residuos inflamables, recortes, etc.
Se colocarn vlvulas anti retorno de llama al soplete o en las mangas del equipo de
soldadura oxiacetilnica.
El almacenamiento y uso de gases licuados cumplirn con todo lo establecido en la
instruccin MIE-AP7 del vigente Reglamento de Aparatos a presin en la norma 9,
apartados 3 y 4 en lo referente al almacenamiento, la utilizacin, el inicio del servicio y las
condiciones particulares de gases inflamables.
Los caminos de evacuacin estarn libres de obstculos. Existir una sealizacin
indicando los lugares de prohibicin de fumar, situacin de extintores, caminos de
evacuacin, etc.
Deben separarse claramente los materiales combustibles unos de otros, y todos ellos deben
evitar cualquier tipo de contacto con equipos y canalizaciones elctricas.
La maquinaria, tanto fija como mvil, accionada por energa elctrica, debe tener las
conexiones de corriente bien realizadas, y en los emplazamientos fijos, se le deber
proveer de aislamiento en el suelo. Todos desechos que se produzcan por el trabajo deben
ser retirados con regularidad, dejando limpios diariamente los alrededores de las mquinas.
Las operaciones de trasvase de combustible deben efectuarse con buena ventilacin, fuera
de la influencia de chispas y fuentes de ignicin. Deben preverse tambin las
consecuencias de posibles derrames durante la operacin, por lo que habr que tener a
mano, tierra o arena.
La prohibicin de fumar o encender cualquier tipo de llama debe formar parte de la
conducta a seguir en estos trabajos.
Cuando se trasvasen lquidos combustibles o se llenen depsitos debern pararse los
motores accionados con el combustible que se est trasvasando.
Cuando se hacen regatas o agujeros para permitir el paso de canalizaciones, deben obturar
rpidamente para evitar el paso de humo o llama de un recinto del edificio a otro, evitando
as la propagacin del incendio. Si estos agujeros han practicado en paredes cortafuegos o
en techos, la mencionada obturacin deber realizarse de forma inmediata y con productos
que aseguren la estanqueidad contra humo, calor y llamas.
En las situaciones descritas anteriormente (almacenes, maquinaria fija o mvil, trasvase de
combustible, montaje de instalaciones energticas) y en aquellas, otras en las que se
manipule una fuente de ignicin, hay que colocar extintores, la carga y capacidad se
encuentre en consonancia con la naturaleza del material combustible y con su volumen, as
como arena y tierra donde se manejen lquidos inflamables, con la herramienta propia para
extenderla. En el caso de grandes cantidades de acopios, almacenamiento o concentracin

15

Estudio de Seguridad y Salud

de embalajes o avalanchas, deben completarse los medios de proteccin con mangueras de


riego que proporcionen agua abundante.

5.2.1

Emplazamiento y distribucin de los extintores obra

Los principios bsicos para el emplazamiento de los extintores, son:


Los extintores manuales se colocarn, sealizados, sobre soportes fijados a paramentos
verticales o pilares, de forma que la parte superior del extintor quede como mximo a 1,70
m. del suelo.
En reas con posibilidades de fuegos "A", la distancia a recorrer horizontalmente, desde
cualquier punto del rea protegida hasta alcanzar el extintor adecuado ms prximo, no
exceder de 25 m.
En reas con posibilidades de fuegos "B", la distancia a recorrer horizontalmente, desde
cualquier punto del rea protegida hasta alcanzar el extintor adecuado ms prximo, no
exceder de 15 m.
Los extintores mviles debern colocarse en aquellos puntos donde se estime que existe
una mayor probabilidad de originarse un incendio, a ser posible, prximos a las salidas y
siempre en lugares de fcil visibilidad y acceso. En locales grandes o cuando existan
obstculos que dificulten su localizacin, se sealar convenientemente su ubicacin.

Servicios de salubridad y confort del personal

Las instalaciones provisionales de obra se adaptarn a las caractersticas especificadas en


los artculos 15 y ss del RD 1627/97, de 24 de octubre, relativo a las DISPOSICIONES
MNIMAS DE SEGURIDAD Y SALUD EN LAS OBRAS DE CONSTRUCCIN.
Para el servicio de limpieza de estas instalaciones higinicas, se responsabilizar a una
persona o un equipo, los cuales podrn alternar este trabajo con otros propios de la obra.
Para la ejecucin de esta obra, se dispondr de las instalaciones del personal que se definen
y detallan a continuacin:

6.1

Servicios higinicos

Aseos, Al menos uno para cada 10 personas.


Cabinas de evacuacin, Se debe instalar una cabina de 1, 5 m2 x 2,3 m de altura, dotada de
placa turca, como mnimo, para cada 25 personas
Local de duchas, Cada 10 trabajadores, dispondrn de una cabina de ducha de dimensiones
mnimas de 1, 5 m2 x 2,3 m de altura, dotada de agua fra-caliente, con suelo
antideslizante.

16

Estudio de Seguridad y Salud

6.2

Vestuarios

Superficie aconsejable 2 m2 por trabajador contratado.

6.3

Comedor

Diferente del local de vestuario. A efectos de clculo deber considerarse entre 1,5 y 2 m2
por trabajador que coma la obra.
Equipado con banco alargado o sillas, cercano a un punto de suministro de agua (1 grifo y
fregadero lavavajillas para cada 10 comensales), medios para calentar comidas (1
microondas para cada 10 comensales), y cubo hermtico (60 l de capacidad, con tapa) para
depositar la basura.

6.4

Local de descanso

En aquellas obras que se ocupan simultneamente ms de 50 trabajadores durante ms de 3


meses, es recomendable que se establezca un recinto destinado exclusivamente al descanso
del personal, situado lo ms prximo posible al comedor y servicios.
A efectos de clculo deber considerarse 3 m2 por usuario habitual.

6.5

Local de asistencia a accidentados

En aquellos centros de trabajo que ocupen simultneamente ms de 50 trabajadores durante


ms de un mes, se establecer un recinto destinado exclusivamente a los cuidados del
personal de obra. Los locales de primeros auxilios dispondrn, como mnimo, de:
I. Un botiqun.
II. Una litera.
III. Una fuente de agua potable.
El material y los locales de primeros auxilios debern estar claramente sealizados y
situados cerca de los puestos de trabajo. El suelo y las paredes del local de asistencia a
accidentados, deben ser impermeables, pintados preferiblemente en colores claros.
Luminoso, caldeado estacin fra, ventilado si fuera necesario de manera forzada en caso
de dependencias subterrneas. Deber tener a la vista el cuadro de direcciones y telfonos
de los centros asistenciales ms cercanos, ambulancias y bomberos.
En obras a las que el nivel de empleo simultneo est entre los 25 y los 50 trabajadores, el
local de asistencia a accidentados podr ser sustituido por un armario botiqun emplazado
oficina de obra. El armario botiqun, custodiado por el socorrista de la obra, deber estar
dotado como mnimo de: alcohol, agua oxigenada, pomada antisptica, gasas, vendas
sanitarias de diferentes tamaos, vendas elsticas compresivas auto-adherentes,
esparadrapo, tiritas, mercurocromo o antisptico equivalente, analgsicos, bicarbonato,
pomada para picaduras de insectos, pomada para quemaduras, tijeras, pinzas, ducha
porttil para ojos, termmetro clnico, caja de guantes esterilizados y torniquete.

17

Estudio de Seguridad y Salud

Para contrataciones inferiores, podr ser suficiente disponer de un botiqun de bolsillo o


porttil, custodiada por el encargado.
El Servicio de Prevencin de la empresa contratista establecer los medios materiales y
humanos adicionales para efectuar la Vigilancia de la Salud de acuerdo a lo que establece
la ley 31/95.
Adems, se dispondr de un botiqun porttil con el siguiente contenido:
I. Desinfectantes y antispticos autorizados.
II. Gasas estriles.
III. Algodn hidrfilo.
IV. Vendas.
V. Esparadrapo.
VI. Apsitos adhesivos.
VII. Tijeras.
VIII. Pinzas.
IX. Guantes de un solo uso.
El material de primeros auxilios se revisar peridicamente, y se repondr de forma
inmediata el material utilizado o caducado.

7
7.1

reas auxiliares
Centrales y plantas

Estarn ubicadas estratgicamente en funcin de las necesidades de la obra. En el trnsito


de vehculos en sus accesos se tendr mucho cuidado en cuanto al orden, balizamiento y
sealizacin, con una anchura mnima de la zona de rodadura de 6 m. y prtico de glibo
de limitacin en altura, mnima de 4 m.
El acceso a la instalacin resto restringida exclusivamente al personal necesario para su
explotacin, quedando expresamente balizada, sealizada y prohibida la presencia de toda
persona en el radio de giro de la dragalina. Todos los accesos o pasarelas situados a alturas
superiores a 2 m. sobre el suelo o plataforma de nivel inferior, dispondr de barandilla
reglamentaria de 1 m. de altura.
Los elementos mviles y transmisiones estarn apantallados en las zonas de trabajo o de
paso susceptibles de posibilitar atrapamientos o en su defecto se encontrarn debidamente
sealizados. Los huecos horizontales estarn condenados y, si no fuera posible como en el
caso de la fosa del skip, se dispondr de barandillas laterales reglamentarias de 1 m. de
altura y tope para rodadura de vehculos. La construccin de la estacada destinada a la
contencin y separacin de ridos, ser firme y arriostrada en previsin de vuelcos.

18

Estudio de Seguridad y Salud

Los silos de cemento no sern hermticos, para evitar el efecto de la presin. La boca de
recepcin del silo estar condenada con un slido emparrillado o religa metlica. La tapa
dispondr de barandilla perimetral reglamentaria de 1 m. de altura. El acceso mediante
escalera "de gato" estar protegido mediante argollas metlicas ( 0,80 m.) a partir de 2 m.
del arranque.
La instalacin elctrica cumplir con las especificaciones del Reglamento Electrotcnico
de Baja Tensin.
Las operaciones de mantenimiento preventivo se realizarn de conformidad a las
instrucciones del fabricante o importador.

7.2

Talleres

Estarn ubicados estratgicamente en funcin de las necesidades de la obra.


De forma general los locales destinados a talleres, tendrn las siguientes dimensiones
mnimas (descontados los espacios ocupados por mquinas, aparatos, instalaciones y / o
materiales): 3 m. de altura de piso a techo, 2 m2 de superficie y 10 m3 de volumen por
trabajador.
La circulacin del personal y los materiales estar ordenada con mucho cuidado, balizada y
sealizada, con una anchura mnima de la zona de paso de personal (sin carga) de 1,20 m2
para pasillos principales (1 m. en pasillos secundarios) independientes de las vas de
manutencin mecnica de materiales. En zonas de paso, la separacin entre mquinas y / o
equipos nunca ser inferior a 0,80 m. (contado desde el punto ms saliente del recorrido
del rgano mvil ms prximo). Alrededor de los equipos que generen calor radiante, se
mantendr un espacio libre no inferior a 1,50 m., estarn apantallados y dispondrn de
medios porttiles de extincin adecuados. Las instalaciones provisionales suspendidas
sobre zonas de paso estarn canalizadas a una altura mnima de 1, 90 m. sobre el nivel del
pavimento.
La intensidad mnima de iluminacin, en los lugares de operacin de las mquinas y
equipos, ser de 200 lux. La iluminacin de emergencia ser capaz de mantener, al menos
durante una hora, una intensidad de 5 lux, y su fuente de energa ser independiente del
sistema normal de iluminacin.
El acceso, los diferentes talleres provisionales de obra, debe quedar restringido
exclusivamente al personal adscrito a cada uno de ellos, quedando expresamente balizada,
sealizada y prohibida la presencia de toda persona en el radio de actuacin de cargas
suspendidas, as como en los de desplazamiento y servidumbres de mquinas y / o equipos.
Todos los accesos o pasarelas situadas a alturas superiores a 2 m sobre el suelo o
plataforma de nivel inferior, dispondr de barandilla reglamentaria de 1 m de altura.
Los elementos mviles y transmisiones estarn apantallados en las zonas de trabajo o de
paso susceptibles de posibilitar atrapamientos o en su defecto se encontrarn debidamente
sealizados. Los huecos horizontales sern condenados.
La instalacin elctrica cumplir con las especificaciones del Reglamento Electrotcnico
de Baja Tensin.

19

Estudio de Seguridad y Salud

Las operaciones de mantenimiento preventivo de la maquinaria se realizarn de


conformidad a las instrucciones del fabricante o importador.
Las emanaciones de polvo, fibras, humos, gases, vapores o neblinas dispondrn de
extraccin localizada, en la medida de lo posible, evitando su difusin por la atmsfera. En
los talleres cerrados, el suministro de aire fresco y limpio por hora y ocupante ser, al
menos, de 30 a 50 m3, salvo que se efecte una renovacin total de aire varias veces por
hora (no inferior a 10 veces).

7.3

Zonas de acopio. Almacenes

Los materiales almacenados obra, debern ser los comprendidos entre los valores
"mnimos-mximos", segn una adecuada planificacin, que impida estacionamientos de
materiales y / o equipos inactivos que puedan ser causa de accidente.
Los Medios Auxiliares de Utilidad Preventiva, necesarios para complementar la
manipulacin manual o mecnica de los materiales apilados, habrn sido previstos en la
planificacin de los trabajos. Las zonas de acopio provisional estarn balizadas,
sealizadas e iluminadas adecuadamente.
De forma general el personal de obra (tanto propio como subcontratado) habr recibido la
formacin adecuada respecto a los principios de manipulacin manual de materiales. De
forma ms singularizada, los trabajadores responsables de la realizacin de maniobras con
medios mecnicos, tendrn una formacin cualificada de sus cometidos y
responsabilidades durante las maniobras.

Tratamiento de residuos

El Contratista es responsable de gestionar los sobrantes de la obra de conformidad con las


directrices del D. 201/1994, de 26 de julio, y del R.D. 105/2008, de 1 de febrero, regulador
de los escombros y otros residuos de construccin, con el fin de minimizar la produccin
de residuos de construccin como resultado de la previsin de determinados aspectos del
proceso, que debe considerarse tanto en la fase de proyecto como en la de ejecucin
material de la obra y / o el derribo o deconstruccin.
En el proyecto se ha evaluado el volumen y las caractersticas de los residuos que
previsiblemente se originarn y las instalaciones de reciclaje ms cercanas para que el
Contratista elija el lugar donde llevar sus residuos de construccin. Los residuos se
entregarn a gestor autorizado, financiando el contratista, los costes que ello conlleve.
Si en las excavaciones y vaciados de tierras aparecen antiguos depsitos o tuberas, no
detectadas previamente, que contengan o hayan podido contener productos txicos y
contaminantes, se vaciarn previamente aislar los productos correspondientes de la
excavacin para ser evacuados independientemente del resto y se entregarn a gestor
autorizado.

20

Estudio de Seguridad y Salud

Tratamiento de materiales y / o sustancias peligrosas

La asesora de Higiene Industrial comprender la identificacin, cuantificacin, valoracin


y propuestas de correccin de los factores ambientales, fsicos, qumicos y biolgicos, los
materiales y / o sustancias peligrosas, para hacerlos compatibles con las posibilidades de
adaptacin de la mayora (casi totalidad) de los trabajadores y / o terceros ajenos
expuestos. A los efectos de este proyecto, los parmetros de medida se establecer
mediante la fijacin de los valores lmite TLV (Threshold Limits Values) que hacen
referencia a los niveles de contaminacin de agentes fsicos o qumicos, por debajo de los
cuales los trabajadores pueden estar expuestos sin peligro para su salud. El TLV se expresa
con un nivel de contaminacin media en el tiempo, para 8 h / da y 40 h / semana.

9.1

Manipulacin

En funcin del agente contaminante, de su TLV, los niveles de exposicin y de las posibles
vas de entrada al organismo humano, el Contratista deber reflejar en su Plan de
Seguridad y Salud las medidas correctoras pertinentes para establecer unas condiciones de
trabajo aceptables para los trabajadores y el personal expuesto, de forma singular a:
I. Amianto.
II. Plomo. Cromo, Mercurio, Nquel.
III. Silicio.
IV. Vinilo.
V. Urea formol.
VI. Cemento.
VII. Ruido.
VIII. Radiaciones.
IX. Productos tixotrpicos (bentonita).
X. Pinturas, disolventes, hidrocarburos, colas, resinas, grasas, aceites.
XI. Gases licuados del petrleo.
XII. Bajos niveles de oxgeno respirable.
XIII. Animales.
XIV. Entorno de drogodependencia habitual.

9.2

Delimitacin / acondicionamiento de zonas de acopio

Las sustancias y / o los preparados se recibirn obra etiquetados de forma clara, indeleble y
como mnimo con el texto en idioma espaol.
La etiqueta debe contener:

21

Estudio de Seguridad y Salud

I. Denominacin de la sustancia de acuerdo con la legislacin vigente o en su defecto


nomenclatura de la IUPAC. Si es un preparado, la denominacin o nombre
comercial.
II. Nombre comn, en su caso.
III. Concentracin de la sustancia, en su caso. Si se trata de un preparado, el nombre
qumico de las sustancias presentes.
IV. Nombre, direccin y telfono del fabricante, importador o distribuidor de la
sustancia o preparado peligroso.
V. Pictogramas e indicadores de peligro, de acuerdo con la legislacin vigente.
VI. Riesgos especficos, de acuerdo con la legislacin vigente.
VII. Consejos de prudencia, de acuerdo con la legislacin vigente.
VIII. El nmero CEE, si tiene.
IX. La cantidad nominal del contenido (por preparados).
El fabricante, el importador o el distribuidor deber facilitar al Contratista destinatario, la
ficha de seguridad del material y / o la sustancia peligrosa, antes o en el momento de la
primera entrega.
Las condiciones bsicas de almacenamiento, acopio y manipulacin de estos materiales y /
o sustancias peligrosas, estarn adecuadamente desarrolladas en el Plan de Seguridad del
Contratista, partiendo de las siguientes premisas:

9.2.1

Txicos, muy txicos, nocivos, carcingenos, mutagnicos,


txicos para la reproduccin

Estar adecuadamente sealizada su presencia y dispondr de ventilacin eficaz. Se


manipular con Equipos de Proteccin Individual adecuados que aseguren la estanqueidad
del usuario, en previsin de contactos con la piel.

9.2.2

Corrosivos, Irritantes

Estar adecuadamente sealizada su presencia. Se manipularn con Equipos de Proteccin


Individual adecuados (especialmente guantes, gafas y mscara de respiracin) que
aseguren la estanqueidad del usuario, en previsin de contactos con la piel y las mucosas
de las vas respiratorias.

10
10.1

Condiciones del entorno


Empleo del cierre de la obra

Se entiende por mbito de empleo lo realmente afectado, incluyendo cercas, elementos de


proteccin, barandillas, andamios, contenedores, casetas, etc. Hay que tener en cuenta que,
en este tipo de obras, el mbito puede ser permanente a lo largo de toda la obra o que
puede ser necesario distinguir entre el mbito de la obra (el de proyecto) y el mbito de los
22

Estudio de Seguridad y Salud

trabajos en sus diferentes fases, a fin de permitir la circulacin de vehculos y peatones o el


acceso a edificios y vados.
En el PLAN DE SEGURIDAD Y SALUD EN EL TRABAJO especificar la delimitacin
del mbito de empleo de la obra y se diferenciar claramente si este cambia en las
diferentes fases de la obra. El mbito o los mbitos de empleo quedarn claramente
dibujados en planos por fases e interrelacionados con el proceso constructivo.

10.2

Situacin de casetas y contenedores

Se colocarn, preferentemente, en el interior del mbito delimitado por el cierre de la obra.


Si por las especiales caractersticas de la obra no es posible la ubicacin de las casetas en el
interior del mbito delimitado por el cierre de la obra, ni es posible su traslado dentro de
este mbito, ya sea durante toda la obra o durante alguna de sus fases, se indicarn en el
PLAN DE SEGURIDAD Y SALUD las reas previstas para este fin. Las casetas, los
contenedores, los talleres provisionales aparcamiento de vehculos de obra, se situarn
segn se indica en el apartado "mbito de ocupacin de la va pblica".

10.3

Servicios afectados

Aqu hay que definir si existen servicios afectados, segn el que se describa en el proyecto
de ejecucin Los Planos y dems documentacin que el Proyecto incorpora relativos a la
existencia y la situacin de servicios, cables, tuberas, conducciones, arquetas, pozos y en
general, de instalaciones y estructuras de obra enterradas o areas tienen un carcter
informativo y no garantizan la exhaustividad ni la exactitud y por tanto no sern objeto de
reclamacin por carencias y / u omisiones. El Contratista viene obligado a su propia
investigacin para lo que solicitar de los titulares de obras y servicios, planos de situacin
y localizar y descubrir las conducciones y obras enterradas, por medio del detector de
conducciones o por calas. Las adopciones de medidas de seguridad o la disminucin de los
rendimientos se considerarn incluidos en los precios y, por tanto, no sern objeto de
abono independiente.

10.4

Necesidades

Aqu hay que definir si existen necesidades (de paso, de vuelo (gras), lneas elctricas,
etc.) segn el que se describa en el proyecto de ejecucin. En la documentacin del
Proyecto y en la facilitada por el Promotor, se incorporan los aspectos relativos a la
existencia de posibles servidumbres en materia de aguas, de paso, de medianera de luces y
vistas, de desage de los edificios o de las distancias y las obras intermedias para ciertas
construcciones y plantaciones, tienen un carcter informativo y no aseguran la
exhaustividad ni la exactitud y por tanto no podrn ser objeto de reclamaciones por
carencias y / u omisiones. Como con los indicados para los servicios afectados, el
Contratista est obligado a consultar en el Registro de la Propiedad dichos extremos. Los
gastos generados, las medidas suplementarias de seguridad o la disminucin de los
rendimientos se considerarn incluidos en los precios y, por tanto, no sern objeto de
abono independiente.

23

Estudio de Seguridad y Salud

10.5

Caractersticas del entorno

Definir las caractersticas ms relevantes (si la obra se encuentra dentro de un rea urbana,
zona rural, zona industrial, etc., viales de trfico, pendientes de los viales, presencia de
medianeras, prximo a la escuela o a hospital, etc.)

11

Unidades constructivas

INSTALACIN DE CALEFACCIN, CLIMATIZACIN Y A.C.S.


UNIDADES AUTNOMAS DE CLIMATIZACIN
TUBERAS PARA GASES Y FLUIDOS
SISTEMAS DE CONDUCCIN DE AIRE

12

Determinacin del proceso constructivo

El Contratista con antelacin suficiente al inicio de las actividades constructivas deber


perfilar el anlisis de cada una de acuerdo con los "Principios de la Accin Preventiva"
(Art. 15 L. 31/1995 de 8 de noviembre) y los "Principios Aplicables Durante la Ejecucin
de las Obras" (Art. 10 RD. 1627/1997 de 24 de octubre).

12.1

Procedimientos de ejecucin

Aqu se definirn las caractersticas constructivas y los procedimientos de ejecucin ms


relevantes (procedimientos de excavacin y los medios a utilizar, tipo de cimentacin y
medios a emplear, estructura metlica soldada, prefabricados, etc.). Los aspectos a
examinar para configurar cada uno de los procedimientos de ejecucin, debern ser
desarrollados por el Contratista y descritos en el Plan de Seguridad y Salud de la obra.

12.2

Orden de ejecucin de los trabajos

Aqu se describir la previsin de orden de ejecucin de los trabajos, si se prevn


diferentes fases de ejecucin (en casos de reforma y ampliacin), etc. Complementando los
planteamientos previos realizados en el mismo sentido por el autor del proyecto, a partir de
los supuestos tericos en fase de proyecto, el Contratista deber ajustarse, durante la
ejecucin de la obra, la organizacin y planificacin de los trabajos a sus especiales
caractersticas de gestin empresarial, de forma que quede garantizada la ejecucin de las
obras con criterios de calidad y de seguridad para cada una de las actividades constructivas
a realizar, en funcin del lugar, la sucesin, la persona o los medios a emplear.

24

Estudio de Seguridad y Salud

12.3

Determinacin del tiempo efectivo de duracin. Plan de


ejecucin

Para la programacin del tiempo material, necesario para el desarrollo de los distintos
cortes de la obra, se han tenido en cuenta los siguientes aspectos:
Lista de actividades: Relacin de unidades de obra.
Relaciones de dependencia: Prelacin temporal de realizacin material de unas unidades
respecto a otras.
Duracin de las actividades: Mediante la fijacin de plazos temporales para la ejecucin
de cada una de las unidades de obra.
De los datos as obtenidos, se ha establecido, en fase de proyecto, un programa general, en
el que ha tenido en cuenta, en principio, slo las grandes unidades (actividades
significativas), y una vez encajado el plazo de duracin, se ha realizado la programacin
previsible, reflejada en un cronograma de desarrollo.
El Contratista en su Plan de Seguridad y Salud deber reflejar, las variaciones introducidas
respecto, el proceso constructivo inicialmente previsto en el Proyecto Ejecutivo /
Constructivo y en el presente Estudio de Seguridad y Salud.

13

Sistemas y / o elementos de seguridad y salud inherentes o


incorporados al mismo proceso constructivo

Todo proyecto constructivo o diseo de equipo, medio auxiliar, mquina o herramienta a


utilizar la obra, objeto del presente Estudio de Seguridad y Salud, se integrar en el
proceso constructivo, siempre de acuerdo con los "Principios de la Accin Preventiva
"(Art. 15 L. 31/1995 de 8 de noviembre), los" Principios Aplicables Durante la Ejecucin
de las Obras "(Art. 10 RD. 1627/1997 de 24 de octubre)" Reglas generales de Seguridad
para mquinas "(Art.18 RD. 1495/1986 de 26 de mayo de 1986), y Normas Bsicas de la
Edificacin, entre otros reglamentos conexos, y atendiendo a las Normas Tecnolgicas de
la Edificacin, Instrucciones Tcnicas Complementarias y Normas UNE o Normas
Europeas, de aplicacin obligatoria y / o aconsejada.

14
14.1

Medio ambiente laboral


Agentes atmosfricos

Se indicar cules son los posibles agentes atmosfricos que pueden afectar a la obra y qu
condiciones debern tener en cuenta para prevenir los riesgos que se deriven.

14.2

Iluminacin

Aunque la generalidad de los trabajos de construccin se realiza con luz natural, debern
tenerse presentes en el Plan de Seguridad y Salud algunas consideraciones respecto a la
25

Estudio de Seguridad y Salud

utilizacin de iluminacin artificial, necesaria en cortes, talleres, trabajos nocturnos o bajo


rasante. Se procurar que la intensidad luminosa en cada zona de trabajo sea uniforme,
evitando los reflejos y deslumbramientos al trabajador as como las variaciones bruscas de
intensidad. En los locales con riesgo de explosin por el gnero de sus actividades,
sustancias almacenadas o ambientes peligrosos, la iluminacin elctrica ser
antideflagrante.
En los puestos de trabajo en los que un fallo del alumbrado normal suponga un riesgo para
los trabajadores, se dispondr de un alumbrado de emergencia de evacuacin y de
seguridad. Las intensidades mnimas de iluminacin artificial, segn los distintos trabajos
relacionados con la construccin, sern los siguientes:
25-50 lux: En patios de luces, galeras y otros lugares de paso en funcin del uso ocasional
- habitual.
100 lux: Operaciones en las que la distincin de detalles no sea esencial, tales como la
manipulacin de mercancas a granel, el acopio de materiales ol'amassat y atado de
conglomerados hidrulicos. Bajas exigencias visuales.
200 lux: Si es esencial una distincin moderada de detalles como en los montajes medios,
en trabajos sencillos en bancos de taller, trabajos en mquinas, fratasado de pavimentos y
cierre mecnico. Moderadas exigencias visuales.
300 lux: Siempre que sea esencial la distincin media de detalles, como trabajos medios en
bancos de taller o en mquinas y trabajos de oficina en general.
500 lux: Operaciones en las que sea necesaria una distincin media de detalles, tales como
trabajos de orden medio en bancos de taller o en mquinas y trabajos de oficina en general.
Altas exigencias visuales.
1000 lux: En trabajos donde sea indispensable una fina distincin de detalles bajo
condiciones de constante contraste, durante largos periodos de tiempo, tales como
montajes delicados, trabajos finos en banco de taller o mquina, mquinas de oficina y
dibujo artstico lineal. Exigencias visuales muy altas.
Los servicios de prevencin sern los encargados de estimar la magnitud o niveles del
riesgo, las situaciones en las que ste se produce, as como controlar peridicamente las
condiciones, la organizacin de los mtodos de trabajo y la salud de los trabajadores con el
fin de tomar las decisiones para eliminar, controlar o reducir el riesgo mediante medidas de
prevencin origen, organizativas, de prevencin colectiva, de proteccin individual,
formativas e informativas.

14.3

Ruido

Para facilitar su desarrollo el Plan de Seguridad y Salud del contratista, se reproduce un


cuadro sobre los niveles sonoros generados habitualmente en la industria.

26

Estudio de Seguridad y Salud

Nombre
Compresor
Equipo de clavar pilotos (15 m de distancia)
Hormigonera pequea <500 lts.
Hormigonera media> 500 lts.
Martillo neumtico (en recinto angosto
Martillo neumtico (aire libre)
Camiones y dumpers
Excavadora
Gra autoportante
Martillo perforador
Tractor
Pala cargadora
Pistolas fija clavos de impacto
Radial porttil

dB
82-94
82
72
60
103
94
80
95
90
110
100
95-100
150
105

Las medidas a adoptar, que debern ser adecuadamente tratadas en el Plan de Seguridad y
Salud por el contratista, para la prevencin de los riesgos producidos por el ruido sern, en
orden de eficacia:
I. Supresin del riesgo en origen.
II. Aislamiento de la parte sonora.
III. Equipo de Proteccin Individual (EPI) mediante tapones u orejeras.
Los servicios de prevencin sern los encargados de estimar la magnitud o los niveles de
riesgo, las situaciones en las que ste se produce, as como controlar peridicamente las
condiciones, la organizacin de los mtodos de trabajo y la salud de los trabajadores con el
fin de tomar las decisiones para eliminar, controlar o reducir el riesgo mediante medidas de
prevencin origen, organizativas, de prevencin colectiva, de proteccin individual,
formativas e informativas.

14.4

Polvo

La permanencia de operarios en ambientes polvorientos, puede dar lugar a las siguientes


afecciones:
I. Rinitis.
II. Asma bronquial.
III. Bronquitis destructiva.
IV. Bronquitis crnica.
V. Enfisema pulmonar.

27

Estudio de Seguridad y Salud

VI. Neumoconiosis.
VII. Asbestosis (asbesto - fibrocemento - amianto).
VIII. Cncer de pulmn (asbesto - fibrocemento - amianto).
IX. Mesotelioma (asbesto - fibrocemento - amianto).
En la construccin es frecuente la existencia de polvo con contenido de slice libre (Si O2)
que es el componente que lo hace especialmente nocivo, como causante de la
neumoconiosis. El problema de presencia masiva de fibras de amianto en suspensin,
necesitar de un Plan especfico de desamiantado que excede a las competencias del
presente Estudio de Seguridad y Salud, y que deber ser realizado por empresas
especializadas. La concentracin de polvo mxima admisible en un ambiente al que los
operarios se encuentren expuestos durante 8 horas diarias, 5 das a la semana, es en funcin
del contenido de slice en suspensin, lo que viene dado por la frmula:
C=

10
mg / m 3
% Si O2 + 2

Teniendo en cuenta que la muestra recogida deber responder a la denominada "fraccin


respirable", que corresponde al polvo realmente inhalada, ya que, de la existente en el
ambiente, las partculas ms gruesas son retenidas por la pituitaria y las ms finas son
expensas con el aire respirado, sin haberse fijado en los pulmones. Los trabajos en los que
es habitual la produccin de polvo, son fundamentalmente los siguientes:
I. Barrido y limpieza de locales
II. Manutencin de escombros
III. Demoliciones
IV. Trabajos de perforacin
V. Manipulacin de cemento
VI. Rayo de arena
VII. Corte de materiales cermicos y lticos con motosierra
VIII. Polvo y serrn por troncos mecnico de madera
IX. Esmerilado de materiales
X. Polvo y humos con partculas metlicas en suspensin, en trabajos de soldadura
XI. Plantas de machacan y clasificacin
XII. Movimientos de tierras
XIII. Circulacin de vehculos
XIV. Pulido de paramentos
XV. Plantas asflticas
Adems de los Equipos de Proteccin Individual necesarios, como mscaras y gafas contra
el polvo, conviene adoptar las siguientes medidas preventivas:

28

Estudio de Seguridad y Salud

Actividad
Limpieza de locales
Demoliciones
Trabajos de perforacin
Manipulacin de cemento
Rayo de arena
Cortar o pulir materiales cermicos
Trabajos sobre madera i soldadura
elctrica
Circulacin de vehculos
Plantas asfaltadotas

Medida preventiva
Uso de aspiradora y regado previo
Regado previo
Captacin localizada en carros perforados o inyeccin de
agua
Filtros en instalaciones confinadas
Equipos semi-autnomos de respiracin
Adicin de agua micronizada sobre la zona de corte
Aspiracin localizada
Regado de pistas
Aspiracin localizada

Los servicios de prevencin sern los encargados de estimar la magnitud o niveles del
riesgo, las situaciones en las que ste se produce, as como controlar peridicamente las
condiciones, la organizacin de los mtodos de trabajo y la salud de los trabajadores con el
fin de tomar las decisiones para eliminar, controlar o reducir el riesgo mediante medidas de
prevencin origen, organizativas, de prevencin colectiva, de proteccin individual,
formativas e informativas.

14.5

Orden y limpieza

El Plan de Seguridad y Salud del contratista deber indicar cmo piensa hacer frente a las
actuaciones bsicas de orden y limpieza en la materializacin de este proyecto,
especialmente en cuanto a:
I. Retirada de los objetos y cosas innecesarias.
II. Emplazamiento de las cosas necesarias en su respectivo lugar de acopio.
III. Normalizacin interna de obra de los tipos de recipientes y plataformas de
transporte de materiales a granel. Plan de manutencin interno de obra.
IV. Ubicacin de los bajantes de escombros y recipientes para acopio de residuos y su
utilizacin. Plan de evacuacin de residuos.
V. Limpieza de claves y restos de material de encofrado.
VI. Desalojo de las zonas de paso, de cables, mangueras, flejes y restos de materia.
Iluminacin suficiente.
VII. Retirada de equipos y herramientas, descansando simplemente sobre superficies de
apoyo provisionales.
VIII. Drenaje de derrames en forma de charcos de carburantes o grasas.
IX. Sealizacin de los riesgos puntuales por falta de orden y limpieza.
X. Mantenimiento diario de las condiciones de orden y limpieza.
XI. Informacin y formacin exigible a los gremios o los diferentes participantes en los
trabajos directos e indirectos de cada partida incluida en el proyecto en lo relativo
al mantenimiento del orden y limpieza inherentes a la operacin realizada.

29

Estudio de Seguridad y Salud

En los puntos de radiaciones el consultor debera identificar los posibles trabajos que se
pueden dar este tipo de radiaciones e indicar las medidas protectoras a tomar.

15

Manipulacin de materiales

Toda manutencin de material supone un riesgo, por lo tanto, desde el punto de vista
preventivo, se debe tender a evitar toda manipulacin que no sea estrictamente necesaria,
en virtud del conocido axioma de seguridad que dice que "el trabajo ms seguro es aquel
que no se realiza. Para manipular materiales es preceptivo tomar las siguientes
precauciones elementales:
I. Empezar por la carga o material que aparece ms superficialmente, es decir el
primero y ms accesible.
II. Entregar el material, no tirarlo.
III. Colocar el material ordenado y en caso de apilado estratificado, que este se realice
en pilas estables, lejos de pasillos o lugares donde pueda recibir golpes o
desgastarse.
IV. Utilizar guantes de trabajo y calzado de seguridad con puntera metlica y acolchada
en empeine y tobillos.
V. En el manejo de cargas largas entre dos o ms personas, la carga puede mantenerse
en la mano, con el brazo estirado a lo largo del cuerpo, o bien sobre el hombro.
VI. Se utilizarn las herramientas y medios auxiliares adecuados para el transporte de
cada tipo de material.
VII. En las operaciones de carga y descarga, se prohibir colocarse entre la parte
posterior del camin y una plataforma, palo, pilar o estructura vertical fija.
VIII. Si durante la descarga se utilizan herramientas, como brazos de palanca, uas, patas
de cabra o similar, disponer la maniobra de tal manera que se garantice el que no se
venga la carga encima y que no resbale.
En lo relativo a la manipulacin de materiales el contratista en la elaboracin del Plan de
Seguridad y Salud deber tener en cuenta las siguientes premisas:
Intentar evitar la manipulacin manual de cargas mediante:
I. Automatizacin y mecanizacin de los procesos.
II. Medidas organizativas que eliminen o minimicen el transporte.
Adoptar Medidas preventivas cuando no pueda evitarse la manipulacin como:
I. Utilizacin de ayudas mecnicas.
II. Reduccin o rediseo de la carga.
III. Actuacin sobre la organizacin del trabajo.
IV. Mejora del entorno de trabajo.

30

Estudio de Seguridad y Salud

Dotar a los trabajadores de la formacin e informacin en temas que incluyan:


I. Uso correcto de las ayudas mecnicas.
II. Uso correcto de los equipos de proteccin individual.
III. Tcnicas seguras para la manipulacin de cargas.
IV. Informacin sobre el peso y centro de gravedad.

15.1

Los principios bsicos de la manipulacin de materiales

I. El tiempo dedicado a la manipulacin de materiales es directamente proporcional a


la exposicin al riesgo de accidente derivado de dicha actividad.
II. Procurar que los diferentes materiales, as como la plataforma de apoyo y de trabajo
del operario, estn a la misma altura en que se debe trabajar con ellos.
III. Evitar el depositar los materiales directamente sobre el suelo, hacerlo siempre sobre
cangilones o contenedores que permitan su traslado a raudales.
IV. Acortar lo posible las distancias a recorrer por el material manipulado, evitando
estacionamientos intermedios entre el lugar de partida del material manipulado
evitando estacionamientos intermedios entre el lugar de partida del material y el
emplazamiento definitivo de su puesta en obra.
V. Trajinar siempre los materiales a granel, mediante contenedores o palees, en lugar
de llevarlos de uno en uno.
VI. No tratar de reducir el nmero de ayudantes que recojan y trajinan los materiales, si
ello conlleva ocupar los oficiales o jefes de equipo en operaciones de manutencin,
coincidiendo en franjas de tiempo perfectamente aprovechables por el avance de la
produccin.
VII. Mantener esclarecidos, sealizados y alumbrados, los lugares de paso de los
materiales a manipular.

15.2

Manejo de cargas sin medios mecnicos

Por izado manual de cargas la totalidad del personal de obra habr recibido la formacin
bsica necesaria, comprometindose a seguir los siguientes pasos:
I. Acercarse lo ms posible a la carga.
II. Asentar los pies firmemente.
III. Agacharse doblando las rodillas.
IV. Mantener la espalda derecha.
V. Sujetar el objeto firmemente.
VI. El esfuerzo de levantar la deben realizar los msculos de las piernas.
VII. Durante el transporte, la carga deber permanecer lo ms cerca posible del cuerpo.

31

Estudio de Seguridad y Salud

VIII. Para el manejo de piezas largas por una sola persona se actuar segn los siguientes
criterios preventivos:
a. Llevar la carga inclinada por uno de sus extremos, hasta la altura del
hombro.
b. Adelantar desplazando las manos a lo largo del objeto, hasta llegar al
centro de gravedad de la carga.
c. Se colocar la carga en equilibrio sobre el hombro.
d. Durante el transporte, mantendr la carga en posicin inclinada, con el
extremo delantero levantado.
IX. Es obligatoria la inspeccin visual del objeto pesado a levantar, para eliminar
aristas afiladas.
X. Est prohibido levantar ms de 50 kg. de forma individual. El valor lmite de 30
Kg. por hombres, puede superarse puntualmente a 50 Kg. cuando se trate de
descargar un material para colocarlo acerca un medio mecnico de manutencin.
En el caso de tratarse de mujeres, se reducen estos valores a 15 y 25 Kg.
respectivamente.
XI. Es obligatorio la utilizacin de un cdigo de seales cuando se ha de levantar un
objeto entre varios, para soportar el esfuerzo al mismo tiempo. Puede ser cualquier
sistema a condicin de que sea conocido o convenido por el equipo.

16

Medios auxiliares de utilidad preventiva (MAUP)

A los efectos del presente Estudio de Seguridad y Salud, tendrn la consideracin de


MAUP, todo Medio Auxiliar dotado de Proteccin, Resguardo, Dispositivo de Seguridad,
Operacin secuencial, Seguridad positiva o Sistema de Proteccin Colectiva, que
originariamente viene integrado, de fbrica, en el equipo, mquina o sistema, de forma
solidaria y indisociable, de tal manera que se interponga, o apantallamiento los riesgos de
alcance o simultaneidad de la energa fuera de control, y los trabajadores, personal ajeno a
la obra y / o materiales, mquinas, equipos o herramientas prximas a su rea de
influencia, anulando o reduciendo las consecuencias de accidente. Su operatividad queda
garantizada por el fabricante o distribuidor de cada uno de los componentes, en las
condiciones de utilizacin y mantenimiento por l prescritas. El contratista queda obligado
a su adecuada eleccin, seguimiento y control de uso. Los MAUP ms relevantes, previstos
para la ejecucin del presente proyecto son los indicados a continuacin:
Cdigo
HX11X000
HX11X001
HX11X002
HX11X003

Descripcin
Bastida modular con estructura tubular y sistema de seguridad con todos los requisitos
reglamentarios en previsin de cadas para la realizacin de estructuras, cerramientos,
cubiertas, y otros trabajos en altura.
Barandilla definitiva, prevista en proyecto, para proteccin de cadas a distinto nivel entre
montantes de escala y / o de altura por el hueco interior.
Escala modular de estructura porticada, para acceder a cotas de diferente nivel, superiores
a 7 m. con sistema de seguridad integrado.
Plataforma telescpica articulada, mvil, autopropulsada con sistema de seguridad
integrado.

32

Estudio de Seguridad y Salud

HX11X004

HX11X009

Plataforma motorizada sobre mstil con sistema de seguridad integrado.


Puente colgante metlico suspendido con barandillas reglamentarias, cabrestantes, con
doble cable de seguridad con dispositivo de auto retencin, sujeto a pescantes con anclajes
con sistema de seguridad integrado.
Andamio con caballetes y sistema de seguridad con todos los requisitos reglamentarios.
Equipo de corte oxiacetilnico reglamentario con sistema de seguridad integrado con
puerta-botellas, vlvulas reductoras de presin, manmetro, mangas, brocas y bridas
normalizadas.
Sierra circular reglamentaria con certificado CE, con sistema de seguridad integrado con
protector de disco inferior fijo, superior abatible, parada de emergencia con freno-motor,
cuchillo divisor, regla gua longitudinal y transversal.
Maquinaria con cabina de operario con sistema de resguardo y proteccin integrado.

HX11X010

Herramienta elctrica con sistema de doble aislamiento integrado.

HX11X011

HX11X016

Premarco metlico con sistema de seguridad integrado contra cadas a distinto nivel.
Elemento prefabricado de hormign con sistema de seguridad integrado con balaustre de
seguridad de reserva de anclaje de cable para amarre y deslizamiento de equipos de
proteccin individual, de altura 1 m.
Paletizado y empaquetado normalizado.
Marquesina de proteccin en voladizo en andamio tubular con sistema de seguridad con
todos los requisitos reglamentarios, normalizada e incorporada UNE-EN 12.810-1 (HD1000).
Pasillo de proteccin prefabricado metlico con sistema de seguridad con todos los
requisitos reglamentarios, de largo 2,5 m., de ancho 1,1 m., con pavimento de entramado
de pletinas metlicas y rampas articuladas, barandillas metlicas reglamentarias,
montantes de 2 m. de altura, techo de chapa de acero de 3 mm. de espesor.
Protector de manos para cincelar.

HX11X017

Conexin elctrica de seguridad tipo petaca.

HX11X018

Cortadora con agua con sistema de seguridad integrado.

HX11X019

Plataforma elevadora manual para suministro de material a nivel de andamio.

HX11X020

Carretilla manual equipada con dispositivos para el transporte de herramientas.

HX11X021

Gra mvil de accionamiento manual.

HX11X022

Carretilla ergonmica para servicio de material al nivel de trabajo, regulable en altura.

HX11X023

Sistema de ventilacin forzada en tneles y zonas cerradas.

HX11X024

Soporte de reposo para el disco radial porttil.

HX11X025

Saco de acopio de tejido de polipropileno con tapa de descarga inferior.

HX11X026

Sarcfago para el izado vertical de cargas largas con gra.

HX11X027

Carretilla manual lleva palees.

HX11X028

Anclaje con diseo especfico para la manipulacin de prefabricados.

HX11X029

Estriba de pozo circular con tensor.


Conexionado y cableado provisional de la instalacin elctrica de la obra con sistema de
proteccin integrado.
Cuadro elctrico secundario provisional de la obra con sistema de proteccin integrado.

HX11X005
HX11X006
HX11X007

HX11X008

HX11X012
HX11X013
HX11X014

HX11X015

HX11X030
HX11X031
HX11X032
HX11X033
HX11X034
HX11X035
HX11X036
HX11X037

Alumbrado provisional de la obra con un nivel lumnico mnimo de 250 lux.


Puente volado semi-prefabricado por trabajos en aleros con plataforma de trabajo y
barandilla perimetral con los requisitos reglamentarios con sistema de seguridad integrado.
Plataforma metlica en voladizo para descarga de material en fachadas con trampilla
practicable para el paso del cable de la gra con sistema de seguridad integrado.
Instalacin de puesta a tierra con conductor de cobre y electrodo conectado a tierra en
rieles de gra torre, masas metlicas, cuadros elctricos, conductores de proteccin.
Interruptor diferencial de sensibilidad media 300 mA., y 40 A. de intensidad nominal.
Malla electro-soldada de barras corrugadas de acero, elaborada en la obra de 10x10 cm. y
de 3-3 mm. de D embebida en hormign para protecciones horizontales de agujeros en

33

Estudio de Seguridad y Salud

techos de 5 m. de D como mximo, y con el desmontaje incluido.


HX11X038

Seal acstica de marcha atrs.

HX11X039

Cable de acero de guiado de material suspendido.

HX11X040

Encendedor de chispa con mango.

HX11X041

Cinturn portaherramientas.

HX11X042

Viga rgida de reparto de cargas suspendidas.

HX11X043

Gancho de gra con dispositivo de cierre.

HX11X044

HX11X047

Alfombra porttil de neopreno para trabajo en planos inclinados.


Recipiente metlico para la manutencin de materiales a granel para una carga mxima de
1200 kg.
Plataforma aislante de base para trabajo en cuadros elctricos de distribucin de 1x1 m y
de 3 mm. de espesor.
Equipo comprobador porttil completo de instalaciones. Instalaciones de baja tensin.

HX11X048

Anemmetro fijo con el desmontaje incluido.

HX11X049

Luxmetro porttil.

HX11X050

Detector de instalaciones. Instalaciones y servicios enterrados porttiles.

HX11X051

Termmetro / barmetro.

HX11X052

Transformador de seguridad de 24 V, colocado y con el desmontaje incluido.


Compuerta basculante para suministro de material, de estructura tubular acoplado a la
barandilla.
Banqueta aislante de patas fijas para trabajo en tensin.

HX11X045
HX11X046

HX11X053
HX11X054
HX11X055
HX11X056
HX11X057

17

Escala porttil dielctrica de fibra de vidrio y 3,2 m de longitud.


Andamio tubular dielctrica de polister y fibra de vidrio, de 2,5 m. de altura y 3,5 m. de
longitud.
Equipo de conexin a tierra de lnea elctrica area de distribucin, con 3 percha
telescpicas para conductores de 7 a 380 mm2 y una altura mxima de 11, 5 m., cable de
cobre de seccin 35 mm2 y piqueta de toma de tierra.

Sistemas de Proteccin Colectiva (SPC)

A los efectos del presente Estudio de Seguridad y Salud, tendrn la consideracin de


Sistemas de Proteccin Colectiva, el conjunto de elementos asociados, incorporados al
sistema constructivo, de forma provisional y adaptada a la ausencia de proteccin integrada
de mayor eficacia (MAUP) , destinados a apantallar o condonar la posibilidad de
coincidencia temporal de cualquier tipo de energa fuera de control, presente en el
ambiente laboral, con los trabajadores, personal ajeno a la obra y / o materiales, mquinas,
equipos o herramientas cercanas a la su rea de influencia, anulando o reduciendo las
consecuencias de accidente. Su operatividad garantiza la integridad de las personas u
objetos protegidos, sin necesidad de una participacin para asegurar su eficacia. Este
ltimo aspecto es el que establece su diferencia con un Equipo de Proteccin Individual
(EPI).
En ausencia de homologacin o certificacin de eficacia preventiva del conjunto de estos
Sistemas instalados, el contratista fijar en su Plan de Seguridad y Salud, referencia y
relacin de los Protocolos de Ensayo, Certificados o Homologaciones adoptadas y / o
requeridos los instaladores, fabricantes y / o proveedores, para el conjunto de dichos
Sistemas de Proteccin Colectiva.

34

Estudio de Seguridad y Salud

Los SPC ms relevantes previstos para la ejecucin del presente proyecto son los indicados
en el anexo de esta memoria que contendr las fichas con RIESGO-EVALUACINMEDIDAS.

18

Condiciones de los Equipos de Proteccin Individual (EPI)

A los efectos del presente Estudio de Seguridad y Salud, tendrn la consideracin de


Equipos de Proteccin Individual, aquellas piezas de trabajo que actan a modo de cubierta
o pantalla porttil, individualizada para cada usuario, destinados a reducir las
consecuencias derivadas del contacto de la zona del cuerpo protegida, con una energa
fuera de control, de intensidad inferior a la previsible resistencia fsica del EPI.
Su utilizacin deber quedar restringida la ausencia de garantas preventivas adecuadas,
por inexistencia de MAUP, o en su defecto SPC de eficacia equivalente. Todos los equipos
de proteccin individual estarn debidamente certificados, segn normas armonizadas CE.
Siempre de conformidad a los R.D. 1407/92, R.D.159/95 y R.D. 773/97.
El Contratista Principal llevar un control documental de su entrega individualizado al
personal (propio o subcontratado), con el correspondiente acuse de recibo firmado por el
beneficiario.
En los casos en que no existan normas de homologacin oficial, los equipos de proteccin
individual sern normalizados por el constructor, para su uso en esta obra, elegidos de
entre los que existan en el mercado y que renan una calidad adecuada a las respectivas
prestaciones. Por esta normalizacin interna deber contar con el visto bueno del tcnico
que supervisa el cumplimiento del Plan de Seguridad y Salud por parte de la Direccin de
Obra o Direccin Facultativa / Direccin de Ejecucin.
En el almacn de obra habr permanentemente una reserva de estos equipos de proteccin,
de manera que pueda garantizar el suministro a todo el personal sin que se produzca,
razonablemente, su carencia.
En esta previsin hay que tener en cuenta la rotacin del personal, la vida til de los
equipos y la fecha de caducidad, la necesidad de facilitar a las visitas de obra, etc.
Los EPI ms relevantes, previstos para la ejecucin material del presente proyecto son los
indicados en el anexo de esta memoria que contendr las fichas con RIESGO
EVALUACIN-MEDIDAS.

19

Recursos preventivos

La legislacin que se debe cumplir respecto a la presencia de recursos preventivos en las


obras de construccin est contemplada en la ley 54/2003. De acuerdo con esta ley, la
presencia de los recursos preventivos en las obras de construccin ser preceptiva en los
siguientes casos:
I. Cuando los riesgos puedan verse agravados o modificados en el desarrollo del
proceso o la actividad, por la concurrencia de operaciones diversas que se desarrollan
35

Estudio de Seguridad y Salud

sucesiva o simultneamente y que hagan preciso el control de la correcta aplicacin


de los mtodos de trabajo. La presencia de recursos preventivos de cada contratista
ser necesario cuando, durante la obra, se desarrollen trabajos con riesgos especiales,
como se definen en el real decreto 1627/97.
II. Cuando se realicen actividades o procesos que reglamentariamente se consideren
peligrosos o con riesgos especiales.
III. Cuando la necesidad de esta presencia sea requerida por la Inspeccin de Trabajo y
Seguridad Social, si las circunstancias del caso lo exigieran debido a las condiciones
de trabajo detectadas.
Cuando a las obras de construccin coexisten contratistas y subcontratistas que, de forma
sucesiva o simultnea, puedan constituir un riesgo especial por interferencia de
actividades, la presencia de los''Recursos preventivos''es, en estos casos, necesaria.
Los recursos preventivos son necesarios cuando se desarrollen trabajos con riesgos
especiales, definidos en el anexo II del RD 1627/97:
I. Trabajos con riesgos especialmente graves de enterramiento, hundimiento o cada de
altura, por las particulares caractersticas de la actividad desarrollada, los
procedimientos aplicados, o el entorno del puesto de trabajo.
II. Trabajos en los que la exposicin a agentes qumicos o biolgicos suponga un riesgo
de especial gravedad, o por que la vigilancia especfica de la salud de los trabajadores
sea legalmente exigible.
III. Trabajos con exposicin a radiaciones ionizantes para los que la normativa especfica
obliga a la delimitacin de zonas controladas o vigiladas.
IV. Trabajos en la proximidad de lneas elctricas de alta tensin.
V. Trabajos que expongan a riesgo de ahogamiento por inmersin.
VI. Obras de excavacin de tneles, pozos y otros trabajos que supongan movimientos de
tierra subterrneos.
VII. Trabajos realizados en inmersin con equipo subacutico.
VIII. Trabajos realizados en cajones de aire comprimido.
IX. Trabajos que impliquen el uso de explosivos.
X. Trabajos que requieran montar o desmontar elementos prefabricados pesados.
A continuacin se detallan, las actividades de la obra del presente estudio de seguridad y
salud, en base a la evaluacin de riesgos de este, que requieren la presencia de recurso
preventivo:
INSTALACIN DE CALEFACCIN, CLIMATIZACIN Y A.C.S.
UNIDADES AUTNOMAS DE CLIMATIZACIN
TUBERAS PARA GASES Y FLUIDOS
SISTEMAS DE CONDUCCIN DE AIRE

36

Estudio de Seguridad y Salud

20

Sealizacin y balizamiento

En cuanto a la sealizacin de la obra, es necesario distinguir entre la que se refiere a la


que demanda de la atencin por parte de los trabajadores y la que corresponde al trfico
exterior afectado por la obra. En el primer caso son de aplicacin las prescripciones
establecidas por el Real Decreto 485/1997, de 14 de abril. La sealizacin y el
balizamiento de trfico vienen regulados, entre otra normativa, por la Norma 8.3-IC de la
Direccin General de Carreteras y no es objeto del Estudio de Seguridad y Salud. Esta
distincin no excluye la posible complementacin de la sealizacin de trfico durante la
obra cuando esta misma se haga exigible para la seguridad de los trabajadores que trabajen
en la inmediacin de este trfico.
Hay que tener en cuenta que la sealizacin por s misma no elimina los riesgos, sin
embargo su observacin cuando es la apropiada y est bien colocada, hace que el individuo
adopte conductas seguras. No es suficiente con colocar un panel en las entradas de las
obras, si despus en la propia obra no se sealiza la obligatoriedad de utilizar cinturn de
seguridad al colocar las miras para realizar el cerramiento de fachada. La sealizacin
abundante no garantiza una buena sealizacin, ya que el trabajador termina haciendo caso
omiso de cualquier tipo de seal.
El RD485/97 establece que la sealizacin de seguridad y salud en el trabajo deber
utilizarse siempre que el anlisis de los riesgos existentes, las situaciones de emergencia
previsibles y las medidas preventivas adoptadas, pongan de manifiesto la necesidad de:
I. Llamar la atencin de los trabajadores sobre la existencia de determinados riesgos,
prohibiciones u obligaciones.
II. Alertar a los trabajadores cuando se produzca una determinada situacin de
emergencia que requiera medidas urgentes de proteccin o evacuacin.
III. Facilitar a los trabajadores la localizacin e identificacin de determinados medios
o instalaciones de proteccin, evacuacin, emergencia o primeros auxilios.
IV. Orientar o guiar a los trabajadores que realicen determinadas maniobras peligrosas.
La sealizacin no deber considerarse una medida sustitutiva de las medidas tcnicas y
organizativas de proteccin colectiva y deber utilizarse cuando, mediante estas ltimas,
no haya sido posible eliminar los riesgos o reducirlos suficientemente.
Tampoco deber considerarse una medida sustitutiva de la formacin e informacin de los
trabajadores en materia de seguridad y salud en el trabajo.
Asimismo, segn se establece en el R.D. 1627/97, se deber cumplir que:
I. Las vas y salidas especficas de emergencia debern sealizarse conforme al RD
485/97, teniendo en cuenta que esta sealizacin deber fijarse en los lugares
adecuados y tener la resistencia suficiente.
II. Los dispositivos no automticos de lucha contra incendios debern estar
sealizados conforme al RD 485/97, teniendo en cuenta que esta sealizacin
deber fijarse en los lugares adecuados y tener la resistencia suficiente.

37

Estudio de Seguridad y Salud

III. El color utilizado para la iluminacin artificial no podr alterar o influir en la


percepcin de las seales o paneles de sealizacin.
IV. Las puertas transparentes debern tener una sealizacin a la altura de la vista.
V. Cuando existan lneas de tendido elctrico reas, en caso de que vehculos la obra
tuvieran que circular bajo el tendido elctrico se utilizar una sealizacin de
advertencia.
La implantacin de la sealizacin y balizamiento debe definirse en los planos del Estudio
de Seguridad y Salud y se tendr en cuenta en las fichas de actividades, al menos respecto
a los riesgos que no hayan podido eliminar.

21

Condiciones de acceso de la va publica

Aqu hay que describir las condiciones de acceso y afectaciones de la va pblica


particulares de la obra (ancho calle, ancho acera, ocupacin de la acera y va pblica y
cmo se resuelve, accesos a la obra, etc.)
En el PLAN DE SEGURIDAD Y SALUD el Contratista definir las desviaciones y pasos
provisionales para vehculos y peatones, los circuitos y tramos de sealizacin, la
sealizacin, las medidas de proteccin y deteccin, los pavimentos provisionales, las
modificaciones que conlleve la implantacin del obra y su ejecucin, diferenciando, en
caso, las diferentes fases de ejecucin. A estos efectos, se tendr en cuenta lo que
determina la Normativa para la informacin y sealizacin de obras en el municipio y la
Instruccin Municipal sobre la instalacin de elementos urbanos en el espacio pblico de la
ciudad que corresponda.
Cuando corresponda, de acuerdo con las previsiones de ejecucin de las obras, se
diferenciar con claridad y por cada una de las distintas fases de la obra, los mbitos de
trabajo y los mbitos destinados a la circulacin de vehculos y peatones, de acceso a
edificios y vados, etc..., y se definirn las medidas de sealizacin y proteccin que
correspondan a cada una de las fases.
Es obligatorio comunicar el inicio, la extensin, la naturaleza de los trabajos y las
modificaciones de la circulacin de vehculos provocadas por las obras, a la Guardia
Municipal y los Bomberos o a la autoridad que corresponda.
Cuando sea necesario prohibir el estacionamiento en zonas donde habitualmente est
permitido, se colocar el cartel de "SEALIZACIN EXCEPCIONAL" (1050 X 600
mm.), con 10 das de antelacin al inicio de los trabajos, todo comunicndolo a la Guardia
Municipal o la Autoridad que corresponda.
En la desviacin o estrechamiento de pasos para peatones se colocar la sealizacin
correspondiente.
No se podr comenzar la ejecucin de las obras sin haber procedido a la implantacin de
los elementos de sealizacin y proteccin que correspondan, definidos en el PLAN DE
SEGURIDAD aprobado.

38

Estudio de Seguridad y Salud

El contratista de la obra ser responsable del mantenimiento de la sealizacin y elementos


de proteccin implantados.
Los accesos de peatones y vehculos, estarn claramente definidos, sealizados y
separados.

22
22.1

Normas de polica
Control de accesos

Una vez establecida la delimitacin del permetro de la obra, conformados los cierres y
accesos para los peatones y de vehculos, el contratista con la colaboracin de su servicio
de prevencin definir, dentro del Plan de Seguridad y Salud, el proceso para el control de
entrada y salida de vehculos en general (incluida la maquinaria como gras mviles,
retroexcavadoras) y de personal de forma que garantice el acceso nicamente a personas
autorizadas.
Cuando la delimitacin de la obra no se pueda llevar a cabo, por las propias circunstancias
de la obra, el contratista, al menos deber garantizar, el acceso controlado a las
instalaciones de uso comn de la obra, y deber asegurar que las entradas a la obra estn
sealizadas, y que queden cerradas las zonas que puedan presentar riesgos.

22.2

Coordinacin de interferencias y seguridad a pie de obra

El contratista, cuando sea necesario, dado el volumen de obra, el valor de los materiales
almacenados y otras circunstancias que as lo aconsejen, definir un proceso para
garantizar el acceso controlado a las instalaciones que supongan riesgo personal y / o
comn para obra intrusismo interior de la obra en talleres, almacenes, vestuarios y otras
instalaciones de uso comn o particular.

22.3

mbito de ocupacin de la va publica

22.3.1

Empleo del cierre de la obra

Se entiende por mbito de empleo lo realmente ocupado, incluyendo cercas, elementos de


proteccin, barandillas, andamios, contenedores, casetas, etc.
En el PLAN DE SEGURIDAD Y SALUD EN EL TRABAJO especificar la delimitacin
del mbito de empleo de la obra y se diferenciar claramente si este cambia en las
diferentes fases de la obra. El mbito o los mbitos de empleo quedarn claramente
dibujados en planos por fases e interrelacionados con el proceso constructivo.
La anchura mxima a ocupar ser proporcional a la anchura de la acera. El espacio libre
para paso de peatones no ser inferior a un tercio (1 / 3) de la anchura de la acera existente.
En ningn caso se podr ocupar una anchura superior a tres (3) metros medidos desde la
lnea de fachada, ni ms de dos tercios (2 / 3) de la anchura de la acera, si no queda al

39

Estudio de Seguridad y Salud

menos una franja de anchura mnima de un metro y cuarenta centmetros (1,40 m.) para
paso de peatones.
Cuando, por la anchura de la acera, no sea posible dejar un paso para peatones de un metro
y cuarenta centmetros (1,40 m.) se permitir, durante la ejecucin de los trabajos en planta
baja, la colocacin de vallas con un saliente mximo de sesenta centmetros (60 cm.)
dejando un paso mnimo para peatones de un metro (1 m.). Por derribo de las plantas
superiores a la planta baja, se colocar una valla en la lnea de fachada y se har una
proteccin volada por la retencin de objetos desprendidos de las cotas superiores. Si la
acera es inferior a un metro sesenta centmetros (1,60 cm.) durante los trabajos en la planta
baja, el paso para peatones de un metro (1 m.) de ancho podr ocupar parte de la calzada en
la medida que sea necesario. En este caso, se deber delimitar y proteger con vallas el
mbito del paso de peatones.

22.3.2

Situacin de casetas y contenedores

Se indicarn en el PLAN DE SEGURIDAD Y SALUD las reas previstas para este fin.
Las casetas, contenedores, talleres provisionales y aparcamiento de vehculos de obra, se
situarn en una zona cercana a la obra que permita aplicar los siguientes criterios:
Preferentemente, en la acera, dejando un paso mnimo de un metro y cuarenta centmetros
(1,40 m.) para paso de peatones por la acera. En la acera, dejando un paso mnimo de un
metro y cuarenta centmetros (1,40 m.) para paso de peatones por la zona de aparcamiento
de la calzada sin invadir ningn carril de circulacin. Si no hay suficiente espacio en la
acera, se colocarn en la zona de aparcamiento de la calzada procurando no invadir ningn
carril de circulacin y dejando siempre como mnimo un metro (1 m.) para paso de
peatones en la acera.
Se proteger el paso de peatones y se colocar la sealizacin correspondiente.

22.3.3

Cambios de la Zona Ocupada

Cualquier cambio en la zona ocupada que afecte al mbito de dominio pblico se


considerar una modificacin del PLAN DE SEGURIDAD Y SALUD EN EL TRABAJO
deber documentar y tramitar de acuerdo con el RD 1627/97.

22.4

Cerramientos de la obra que afectan el mbito pblico

22.4.1

Vallas

Situacin: Delimitarn el permetro del mbito de la obra o, en ordenacin entre


medianeras, cerrarn el frente de la obra o solar y los laterales de la parte de acera ocupada.
Tipo de vallas: Se formarn con chapa metlica opaca o a base de paneles prefabricados o
de obra de fbrica enfoscada y pintada. Las empresas promotoras podrn presentar en el

40

Estudio de Seguridad y Salud

Ayuntamiento para su homologacin, en su caso, su propio modelo de valla para emplearlo


en todas las obras que hagan.
Las vallas metlicas de 200 x 100 cm. slo se admiten para protecciones provisionales en
operaciones de carga, desviaciones momentneas de trfico o similares. En ningn caso se
admite como cierra el simple balizado con cinta de PVC, malla electro-soldada de
ferrallista, red tipo tenis de polipropileno (habitualmente de color naranja), o elementos
tradicionales de delimitaciones provisionales de zonas de riesgo.
Complementos: Todas las vallas tendrn balizamiento luminoso y elementos reflectantes en
todo su permetro.
Mantenimiento: El Contratista velar por el correcto estado de la valla, eliminando
grafittis, publicidad ilegal y cualquier otro elemento que deteriore su estado original.

22.4.2

Acceso a la obra

Puertas: Las vallas estarn dotadas de puertas de acceso independiente para vehculos y
para el personal de la obra. No se admite como solucin permanente de acceso la retirada
parcial del cierre.

22.5

Operaciones que afectan el mbito pblico

22.5.1

Entradas y salidas de vehculos y maquinaria

Vigilancia: Personal responsable de la obra se encargar de dirigir las operaciones de


entrada y salida, avisando a los peatones a fin de evitar accidentes.
Aparcamiento: Fuera del mbito del cierre de la obra no podrn estacionarse vehculos ni
maquinaria de la obra, excepto en la reserva de carga y descarga de la obra cuando exista
zona de aparcamiento en la calzada.
Camiones en espera: Si no hay espacio suficiente dentro del mbito del cierre de la obra
para acoger a los camiones en espera, habr que prever y habilitar un espacio adecuado a
este fin fuera de la obra. El PLAN DE SEGURIDAD prever esta necesidad, de acuerdo
con la programacin de los trabajos y los medios de carga, descarga y transporte interior de
la obra.

22.5.2

Carga y descarga

Las operaciones de carga y descarga se ejecutarn dentro del mbito del cierre de la obra.
Cuando esto no sea posible, se estacionar el vehculo en el punto ms cercano a la valla de
la obra, se desviarn los peatones fuera del mbito de actuacin, se ampliar el permetro
cerrado de la obra y se tomarn las siguientes medidas:
I. Se habilitar un paso peatonal. Se dejar un paso mnimo de un metro y cuarenta
centmetros (1,40 m.) de ancho para la acera o para la zona de aparcamiento de la

41

Estudio de Seguridad y Salud

calzada, sin invadir ningn carril de circulacin. Si no es suficiente y / o si hay que


invadir el carril de circulacin que corresponda y contactar previamente con la
Guardia Urbana.
II. Se proteger el paso de peatones con vallas metlicas de 200 x 100 cm.,
delimitando el camino por los dos lados y se colocar la sealizacin que
corresponda.
III. La separacin entre las vallas metlicas mbito de operaciones o el vehculo,
formar una franja de proteccin del ancho de la que depender del tipo de
productos a cargar o descargar y que establecer el Jefe de Obra previa consulta al
Coordinador de Seguridad de la obra.
IV. Terminadas las operaciones de carga y descarga, se retirarn las vallas metlicas se
limpiar el pavimento.
V. Se controlar la descarga de los camiones hormigonera para evitar vertidos sobre la
calzada.

22.5.3

Descarga, acopio y evacuacin de tierras y escombros

Descarga: La descarga de escombros desde los diferentes niveles de la obra, aprovechando


la fuerza de la gravedad, ser para tuberas (cotas superiores) o mecnicamente (cotas bajo
rasante), hasta los contenedores o tolvas, que debern ser cubiertas con lonas o plsticos
opacos para evitar polvo. Las tuberas o cintas de elevacin y transporte de material se
colocarn siempre por el interior del recinto de la obra.
Acopio: No se pueden acumular tierras, escombros y desperdicios en el mbito de dominio
pblico, excepto si es para un plazo corto y si se ha obtenido un permiso especial del
Ayuntamiento, y siempre se ha de depositar en tolvas o en contenedores homologados. Si
no se dispone de esta autorizacin ni de espacios adecuados, las tierras se cargarn
directamente sobre camiones para su evacuacin inmediata.
A falta de espacio para colocar los contenedores en el mbito del cierre de la obra, se
colocarn sobre la acera en el punto ms cercano a la valla, dejando un paso peatonal de un
metro y cuarenta centmetros (1,40 m.) de ancho como mnimo. Se evitar que haya
productos que sobresalgan del contenedor. Se limpiar diariamente la zona afectada y
despus de retirado el contenedor. Los contenedores, cuando no se utilicen, debern ser
retirados.
Evacuacin: Si los escombros se cargan sobre camiones, estos debern llevar la caja tapada
con una lona o un plstico opaco para evitar la produccin de polvo, y su transporte lo ser
a un vertedero autorizado. Lo mismo se har en los transportes de los contenedores.

22.5.4

Protecciones para evitar la cada de objetos en la va pblica

Al PLAN DE SEGURIDAD especificarn, para cada fase de obra, las medidas y


protecciones previstas para garantizar la seguridad de peatones y vehculos y evitar la cada
de objetos en la va pblica, teniendo en cuenta las distancias, en proyeccin vertical, entre
los trabajos en altura, el cierre de la obra y la acera o zona de paso de peatones o vehculos.

42

Estudio de Seguridad y Salud

Andamios: Se colocarn andamios perimetrales en todos los paramentos exteriores a la


construccin a realizar. Los andamios sern metlicos y modulares. Tendrn una
proteccin de la cada de materiales y elementos formando un entarimado horizontal a 2,80
m. de altura, preferentemente de piezas metlicas, fijado a la estructura vertical y
horizontal del andamio, as como una marquesina inclinada en voladizo que sobresalga 1,
50 m., como mnimo, del plan del andamio. Los andamios sern tapados perimetralmente
ya toda la altura de la obra, desde el entarimado de visera, con una red o lonas opacas que
evite la cada de objetos y la propagacin de polvo.
Redes: Siempre que se ejecuten trabajos que comporten peligro para los peatones, por el
riesgo de cada de materiales o elementos, se colocarn redes de proteccin entre las
plantas, con sistemas homologados, de forjado, perimetrales en todas las fachadas.

22.6

Limpieza e incidencia sobre el ambiente que afecta el mbito


pblico

22.6.1

Limpieza

Los contratistas limpiarn y regarn diariamente el espacio pblico afectado por la


actividad de la obra y especialmente despus de haber efectuado cargas y descargas u
operaciones productoras de polvo o desechos. Se vigilar especialmente la emisin de
partculas slidas (polvo, cemento, etc.).
Habr que tomar las medidas pertinentes para evitar las roderas de barro sobre la red viaria
en la salida de los camiones de la obra. A tal fin, se dispondr, antes de la salida del cierre
de la obra, una solera de hormign o planchas de 2 x 1 m., como mnimo, sobre la que
pararn los camiones y se limpiarn para riego con manguera cada pareja de ruedas.
Est prohibido efectuar la limpieza de hormigoneras al alcantarillado pblico.

22.6.2

Ruidos. Horario de trabajo

Las obras se realizarn entre las 8.00 y las 20.00 horas los das laborables.
Fuera de este horario, slo se permite realizar actividades que no produzcan ruidos ms
all de lo que establecen las OCAF. Las obras realizadas fuera de este horario debern ser
especficamente autorizadas por el Ayuntamiento.
Excepcionalmente y con el objeto de minimizar las molestias que determinadas
operaciones pueden producir sobre el mbito pblico y la circulacin o por motivos de
seguridad, el Ayuntamiento podr obligar a que algunos trabajos se ejecuten en das no
laborables o en un horario especfico.

43

Estudio de Seguridad y Salud

22.6.3

Polvo

Se regarn las pistas de circulacin de vehculos. Se regarn los elementos a derribar, los
escombros y todos los materiales que puedan producir polvo. En el corte de piezas con
disco se aadir agua. Los silos de cemento estarn dotados de filtro.

22.7

Residuos que afectan al mbito publico

El contratista, dentro del Plan de Seguridad y Salud, definir con la colaboracin de su


servicio de prevencin, los procedimientos de trabajo para el almacenamiento y retirada de
cada uno de los diferentes tipos de residuos que se puedan generar obra.
El contratista deber dar las oportunas instrucciones a los trabajadores y subcontratistas,
comprobando que lo comprenden y lo cumplen.

22.8

Circulacin de vehculos y peatones que afectan el mbito


publico

22.8.1

Sealizacin y proteccin

Si el plan de implantacin de la obra conlleva la desviacin del trfico rodado o la


reduccin de viales de circulacin, se aplicarn las medidas definidas en la Norma de
Sealizacin de Obras.
Est prohibida la colocacin de seales no autorizadas por los Servicios Municipales.

22.8.2

Dimensiones mnimas de itinerarios y pasos para peatones

Se respetarn las siguientes dimensiones mnimas:


I. En caso de restriccin de la acera, el ancho de paso para peatones no ser inferior a
un tercio (1 / 3) de la anchura de la acera existente.
II. La anchura mnima de itinerarios o de pasos para peatones ser de un metro y
cuarenta centmetros (1,40 m).

22.8.3

Elementos de proteccin

Paso peatonal: Todos los pasos de peatones que deban habilitar se protegern, por ambos
lados, con vallas o barandillas resistentes, ancladas o pegadas al suelo, de una altura
mnima de un metro (1 m.) con travesao intermedio y rodapis de veinte centmetros
(0,20 m.) en la base. La altura de la pasarela no sobrepasar los quince centmetros (0,15
m.).
Los elementos que formen las vallas o barandillas sern preferentemente continuos. Si son
calados, las separaciones mnimas no podrn ser superiores a quince centmetros (015 m.).

44

Estudio de Seguridad y Salud

Agujeros y zanjas: Si los peatones deben pasar por sobre los agujeros o las zanjas, se
colocarn chapas metlicas fijadas, de resistencia suficiente, totalmente planas y sin
resaltes. Si los agujeros o las zanjas deben ser evitados, las barandillas o vallas de
proteccin del paso se colocarn a 45 en el sentido de la marcha.

22.8.4

Alumbrado y balizamiento luminoso

Las seales y los elementos de balizamiento irn debidamente iluminados aunque haya
alumbrado pblico.
Se utilizar pintura y material reflectante, tanto para la sealizacin vertical y horizontal,
como para los elementos de balizamiento.
Los itinerarios y pasos de peatones estarn convenientemente iluminados a lo largo de todo
el tramo (intensidad mnima 20 lux).
Los andamios de paramentos verticales que ocupen acera o calzada tendrn balizamiento
luminoso y elementos reflectantes a todas las patas en todo su permetro exterior.
La delimitacin de itinerarios o pasos para peatones formada con vallas metlicas de 200 x
100 cm., tendrn balizamiento luminoso en todo su permetro.

22.8.5

Balizamiento y defensa

Los elementos de balizamiento y defensa a emplear para pasos para vehculos sern los
designados como tipo TB, TL y TD en la Norma de carreteras 8.3 - IC. con el siguiente
criterio de ubicacin de elementos de balizamiento y defensa:
I. En la delimitacin del borde del carril de circulacin de vehculos contiguo al cierre
de la obra.
II. En la delimitacin de bordes de pasos provisionales de circulacin de vehculos
contiguos a pasos provisionales para peatones.
III. Para impedir la circulacin de vehculos por una parte de un carril, por todo un
carril o por varios carriles, en estrechamientos de paso y / o disminucin del
nmero de carriles.
IV. En la delimitacin de bordes en la desviacin de carriles en el sentido de
circulacin, para salvar el obstculo de las obras.
V. En la delimitacin de bordes de nuevos carriles de circulacin para pasos
provisionales o para establecer una nueva ordenacin de la circulacin, diferente de
la que haba antes de las obras.
Se colocarn elementos de defensa TD - 1 cuando, en vas de alta densidad de circulacin,
en vas rpidas, en curvas pronunciadas, etc..., la posible desviacin de un vehculo del
itinerario sealado pueda producir accidentes en peatones o trabajadores (desplazamiento o
derribo del cierre de la obra o de barandillas de proteccin de paso de peatones, choque
contra objetos rgidos, volcar el vehculo por la existencia de desniveles, etc.).

45

Estudio de Seguridad y Salud

Cuando el espacio disponible sea mnimo, se admitir la colocacin de elementos de


defensa TD - 2.

22.8.6

Accesibilidad de personas con movilidad reducida

Si la va o vas del entorno de la obra estn adaptadas de acuerdo con lo dispuesto en el


Decreto 135/1995 de 24 de marzo, y no hay itinerario alternativo, los pasos o itinerarios
provisionales cumplirn las siguientes condiciones mnimas:
I. Altura libre de obstculos de 2,10 m.
II. En los cambios de direccin, la anchura mnima de paso deber permitir inscribir
un crculo de 1,5 m. de dimetro.
III. No podr haber escaleras ni peldaos aislados.
IV. La pendiente longitudinal ser como mximo del 8% y la pendiente transversal del
2%.
V. El pavimento ser duro, no deslizante y sin relieves diferentes a los propios del
grabado de piezas. Si es de tierras tendr una compactacin del 90% PM.
VI. Los vados tendrn una anchura mnima de un metro y veinte centmetros (1,20 m.)
y una pendiente mxima del 12%.
Si hay itinerario alternativo, se indicar, en los puntos de desviacin hacia el itinerario
alternativo, colocando una seal tipo D con el smbolo internacional de accesibilidad y una
flecha de sealizacin.

22.8.7

Retirada de sealizacin y balizamiento

Terminada la obra se retirarn todas las seales, elementos, dispositivos y balizamiento


implantados. El plazo mximo para la ejecucin de estas operaciones ser de una semana,
una vez acabada la obra o la parte de obra que exigiera su implantacin.

22.9

Proteccin y traslado de elementos emplazados en la va pblica

22.9.1

rboles y jardines

Al PLAN DE SEGURIDAD se sealarn todos los elementos vegetales y arbolado


existente en la va pblica que est en la zona de las obras ya su umbral. La Entidad
Municipal responsable de Parques y Jardines emitir informe previo preceptivo.
Mientras duren las obras se proteger el arbolado, los jardines y las especies vegetales que
puedan quedar afectadas, dejando a su alrededor una franja de un (1) metro de zona no
ocupada. El contratista velar porque los alcorques y zonas ajardinadas estn siempre
libres de elementos extraos, desechos, basura y escombros. Se regarn peridicamente,
siempre que ello no se pueda hacer normalmente desde el exterior de la zona de obras.

46

Estudio de Seguridad y Salud

Los alcorques que queden incluidos dentro del mbito de estrechamiento de paso para
peatones debern tapar de forma que la superficie sea continua y sin resaltes.

22.9.2

Paradas de autobs

Debido a la implantacin del cierre de la obra, ya sea, para que queden en su interior o para
quedar en zona de paso restringido, habr que prever el traslado provisional de paradas de
autobs, quioscos, buzones de Correos o elementos similares emplazados en espacio
pblico.
En este caso, habr que indicarlo en el PLAN DE SEGURIDAD, prever su emplazamiento
durante el tiempo que duren las obras y contactar con los servicios correspondientes para
coordinar las operaciones.

23

Riesgos de daos a terceros y medidas de proteccin

23.1

Riesgos de daos a terceros

Los riesgos que durante las sucesivas fases de ejecucin de la obra podran afectar a
personas u objetos anexos que dependan son los siguientes:
I. Cada al mismo nivel.
II. Atropellos.
III. Colisiones con obstculos en la acera.
IV. Cada de objetos.

23.2

Medidas de proteccin a terceros

Se considerarn las siguientes medidas de proteccin para cubrir el riesgo de las personas
que transitan por los alrededores de la obra:
I. Montaje de valla metlica a base de elementos prefabricados de 2 m. de altura,
separando el permetro de la obra, de las zonas de trnsito exterior.
II. Para la proteccin de personas y vehculos que transiten por las calles colindantes,
se instalar un pasillo de estructura consistente en el sealamiento, que deber ser
ptico y luminoso en la noche, para indicar el glibo de las protecciones al trfico
rodado. Ocasionalmente se podr instalar en el permetro de la fachada una
marquesina en voladizo de material resistente.
III. Si fuera necesario ocupar la acera durante la reunin de materiales en la obra,
mientras dure la maniobra de descarga, se canalizar el trfico de peatones por el
interior del pasillo de peatones y el de vehculos fuera de las zonas de afectacin de
la maniobra, con proteccin a base de rejas metlicas de separacin de reas y se
colocarn luces de glibo nocturnos y seales de transicin que avisen a los
vehculos de la situacin de peligro.

47

Estudio de Seguridad y Salud

IV. En funcin del nivel de intromisin de terceros la obra, se puede considerar la


conveniencia de contratar un servicio de control de accesos a la obra, a cargo de un
Servicio de Vigilancia patrimonial, expresamente para esta funcin.

24

Prevencin de riesgos catastrficos

Los principales riesgos catastrficos considerados como remotamente previsibles para esta
obra son:
I. Incendio, explosin y / o deflagracin.
II. Inundacin.
III. Colapso estructural por maniobras fallidas.
IV. Atentado patrimonial contra la Propiedad y / o contratistas.
V. Hundimiento de cargas o aparatos de elevacin.
Para cubrir las eventualidades pertinentes, el Contratista redactar e incluir como anexo a
su Plan de Seguridad y Salud un "Plan de Emergencia Interior", cobren las siguientes
medidas mnimas:
I. Orden y limpieza general.
II. Accesos y vas de circulacin interna de la obra.
III. Ubicacin de extintores y otros agentes extintores.
IV. Nombramiento y formacin de la Brigada de Primera Intervencin.
V. Puntos de encuentro.
VI. Asistencia Primeros Auxilios.

25

Previsiones de seguridad por trabajos posteriores

Previsiones e informaciones tiles para efectuar en su da, en las debidas condiciones de


seguridad y salud, los previsibles trabajos posteriores (mantenimiento) segn art. 5.6
RD.1627/97.

48

CLIMAVER PLUS R
Los conductos para distribucin de aire

CLIMAVER PLUS R
Los conductos de aire

Panel rgido de lana de vidrio de alta densidad para distribucin de


aire en climatizacin; con caractersticas aislantes trmicas y acsticas.
DESCRIPCIN
CLIMAVER PLUS R es un panel de lana de vidrio de alta densidad, revestido por una de sus caras con aluminio y kraft, y por
la otra, con aluminio reforzado y kraft. El alma del panel incorpora dos velos de vidrio que le otorgan una excepcional rigidez.
El aluminio proporciona una excelente barrera de vapor y
estanqueidad. Aporta un acabado liso y protege las superficies
interior y exterior del conducto.
La malla de refuerzo en el revestimiento exterior aumenta la
resistencia al desgarro y al punzonamiento del aluminio y
mejora la rigidez del panel.
El kraft de los revestimientos aporta un corte limpio y
sencillo y otorga rigidez.
El doble velo incorporado en el alma del panel aumenta
excepcionalmente la resistencia a la flexin.

Rebordeado exclusivo del canto macho.


El panel est canteado para facilitar y mejorar la unin
entre tramos de conducto. El canto macho est rebordeado por el revestimiento interior para que la unin entre
tramos sea limpiable y para que no exista discontinuidad
en el revestimiento.

Superficie interior conducto

Revestimiento exterior exclusivo con marcado MTR.


Marcado de lneas gua: Referencia para la construccin de
figuras de la red de conductos mediante el Mtodo del
Tramo Recto.
Este mtodo de montaje proporciona importantes
ventajas: precisin, resistencia y calidad, acabado
interior ptimo, y mnimos desperdicios.
CLIMAVER PLUS R se suministra en forma de paneles para construccin de conductos.
Espesor (mm)

Largo (m)

Ancho (m)

25

1,19

Superficie exterior conducto

CLIMAVER PLUS R
Los conductos de aire

AISLAMIENTO TRMICO
Conductividad trmica

90/90 0,032 W/m K

Resistencia trmica

R 0,75 m2 K/W
(Propiedades referidas a 10 C)

P E R M E A B I L I D A D A L VA P O R D E A G U A
Valor aproximado: 0,013 g/m2da mm Hg.
(Correspondiente al revestimiento exterior)

ABSORCIN ACSTICA
La lana de vidrio es un excelente absorbente acstico, por lo
que disminuye las molestias causadas por los ruidos generados en la instalacin.
Ej: Un metro de conducto Climaver Plus R de 40 cm x
30 cm atena 6,4 dB a 1.000 Hz.
La capacidad absorbente del panel, viene dada por sus coeficientes de absorcin ():
Frecuencia (Hz)
Coeficiente Sabine

125

250

500

1.000

2.000

0,20

0,20

0,20

0,60

0,50

Lo que implica las siguientes atenuaciones sonoras por metro lineal de conducto:
Straigh duct noise reduction (dB/m)
200 x 200

2,81

2,81

2,81

11,09

8,83

seccin

300 x 400

1,64

1,64

1,64

6,47

5,15

(mm)

400 x 500

1,26

1,26

1,26

4,99

3,97

400 x 700

1,10

1,10

1,10

4,36

3,47

500 x 1.000

0,84

0,84

0,84

3,33

2,65

CLIMAVER PLUS R
Los conductos de aire

REACCIN AL FUEGO
CLIMAVER PLUS R se clasifica como B s1, d0
(cumple con las exigencias normativas NBE-CPI-96 para conductos autoportantes)

RIGIDEZ MECNICA
Los paneles CLIMAVER PLUS R tienen rigidez clase R5 segn EN13403 (Norma Europea de
paneles no metlicos). Esta rigidez corresponde al mximo posible de los valores presentados
por esta norma.
Con respecto a la norma UNE-100-105-84, los paneles CLIMAVER PLUS R tienen rigidez clase III
(la mxima de los niveles establecidos por la misma).
Los paneles CLIMAVER PLUS R resisten sin problemas de fisuras o abombamientos presiones
estticas inferiores a los 800 Pa (ensayo segn EN 13403)

PRDIDAS DE CARGA
Prdidas de carga por metro lineal de conducto:
Debido al revestimiento interior liso, las prdidas de
carga son equivalentes a las producidas en el interior de un conducto metlico.

Dimetro equivalente (mm)

Velocidad del aire (m/s)


3

100

2500

10

2000

90
2 80
70
60
2000

50
40
30

20

Para evaluar las prdidas de carga en un conducto Climaver pueden utilizarse los bacos de
ASHRAE para conductos metlicos.

2000
2000

10
9
8
7

2000

2000

6
5
2000
4
2000

Prdidas de carga en figuras:

2
2000
1

1
0,9
0,8
0,7

2000

0,6
0,5
0,4
2000
0,3

0,2

90

90

90

90
90
90
90

90

90

90
90
90

Prdida de carga (Pa/m)

90

0,6

0,5

0,4

0,3

0,2

0,1

0,07
0,08
0,09

0,06

0,05

0,04

0,03

0,02

0,1
0,01

Las prdidas de carga en las figuras realizadas


segn el Mtodo del Tramo Recto para construccin
de conductos son similares a las de figuras con curvas. Para su clculo, pueden utilizarse las tablas de
ASHRAE para clculo de carga en figuras de conductos metlicos.

CLIMAVER PLUS R
Los conductos de aire

LIMPIEZA DE CONDUCTOS
Los paneles CLIMAVER PLUS R son limpiables, tras superar los ensayos realizados por los mtodos de aire a presin skeeper y por aire a presin con cepillado, sin presentar desgarros o roturas del revestimiento interior.
Deben instalarse aperturas de servicio en las redes de conductos para facilitar
su limpieza, a una distancia mxima de 10 m. Para que las puertas de acceso
queden perfectamente selladas, se ha diseado el montaje con la perfilera
Perfiver H, con sellado de la tapa con cinta CLIMAVER.

S I S T E M A C L I M A V E R M E TA L
Los paneles CLIMAVER PLUS R pueden utilizarse para el montaje del SISTEMA
CLIMAVER METAL. Este sistema combina los panles CLIMAVER con la perfilera
PERFIVER L, que se incorpora en las aristas longitudinales del producto.
El SISTEMACLIMAVER METAL proporciona:
Un sistema de montaje hermtico.
Limpieza.
Resistencia.
Montaje de calidad.

CERTIFICADOS
Producto marcado CE.
Marca de calidad N de AENOR.
Cumple con la norma EN-13403 para conductos no metlicos.
Cumple con la norma UNE-100-105-84 para conductos no metlicos.

CONDICIONES DE TRABAJO
De acuerdo con EN-13403, no se recomienda el uso de conductos Climaver en los siguientes casos:
Circulacin del aire con temperatura > 90C.
Transporte de slidos o lquidos corrosivos.
Conducciones verticales de altura superior a dos plantas, sin perfilera de sujecin; conducciones exteriores sin
recubrimiento adecuado, y conducciones enterradas.

CLIMAVER PLUS R
Los conductos de aire

M O N TA J E
Si bien existen otros mtodos de montaje, se recomienda emplear el Mtodo del Tramo Recto, MTR.
Este mtodo se basa en la utilizacin de un conducto recto como base para obtener las figuras de
la red de conductos.
La construccin de una red de conductos Climaver requiere dos tipos de accesorios:
- Herramientas Climaver. Existen dos tipos de herramientas Climaver: Clilmaver MM, utilizadas
para realizar las ranurar el panel de forma que pueda plegarse segn una seccin determinada de conducto; y las herramientas MTR, utilizadas para cortar un tramo recto y obtener las
piezas que darn lugar a las figuras.
- Cola y cinta Climaver. Se utilizan para unir y sellar las juntas de las piezas y de esta forma
obtener las figuras. La cola Climaver se ha desarrollado para permitir una unin perfecta de
lana de vidrio; la cinta Climaver debe ser de aluminio puro, de 50 micras de espesor y 65 mm
de ancho.

MTR, Mtodo del Tramo Recto.


Claras ventajas
Precisin.
Resistencia y calidad.
Menores prdidas de carga.
Mnimos desperdicios.
Las instrucciones para el montaje de conductos segn el Mtodo del Tramo Recto estn disponibles en el
Manual de Montaje Climaver y en la Gua Reducida MTR; disponibles tanto en formato papel como en la
pgina web, www.isover.net

CLIMAVER PLUS R
Los conductos de aire

MTODO DE MONTAJE. MTR, MTODO DEL TRAMO RECTO


CODO 45:

CODO 90:

Girar 180

Sellar con Cola


y Cinta Climaver

Separacin A (cm)
20
25
30
35
40
45
50
55
60

Distancia D (cm)
14,1
17,7
21,2
24,7
28,3
31,8
35,4
38,9
42,4

Sellar con Cola


y Cinta Climaver

RAMIFICACIN LATERAL: Zapato


(El ramal tiene menor altura que el conducto principal)

Sellar con Cola


y Cinta Climaver

Girar 180

DESVO o QUIEBRO:

Girar 180

Separacin A (cm)
20
25
30
35
40
45
50
55
60
65
70
75
80

Girar 180

Sellar con Cola


y Cinta Climaver

Distancia D (cm)
14,1
17,1
21,2
24,7
28,3
31,8
35,4
38,9
42,4
46
49,5
53
56,6

RAMIFICACIN SIMPLE o en R:
(Todos los conductos tienen la misma altura)

r1= A

r2= B

Principal
(de seccin disminuda)

Principal
B

Ramal
Principal

b
B

45

Girar 180
d
b

Ramal

Las instrucciones de montaje de conductos


segn el MTR se encuentran detalladas en el
Manual de Montaje Climaver, disponible en formato librillo y en la pgina web: www.isover.net

Principal

Sellar con Cola


y Cinta Climaver
45
Canto
hembra

MEDICIONES
Aunque cada instalacin presenta sus peculiaridades, pueden tomarse de forma orientativa las siguientes mediciones
para el consumo de Climaver en
una instalacin:

Conducto recto

S = 2 (a + b + 0,2) L

Reduccin

S = 2 (a + b + 0,2) L

Te

S = 2 (a1 + b1 + 0,2) L1 +

Codo a tres tramos

S = 3,2 (a + b + 0,2) L

Pantaln recto

S = 2 (a1 + b1 + 0,2) (L1 +L2 + L3)

SELECCIN DEL CONDUCTO CLIMAVER MS IDNEO


Exigencias
al fuego

Producto

Absorcin
acstica

Limpieza

Velocidad

Presentacin

SISTEMA CLIMAVER METAL (1)

**

**

Sistema

CLIMAVER PLUS R

**

Panel

CLIMAVER A2

**

**

Panel

CLIMAVER A2 NETO

**

**

Panel

CLIMAVER PLATA

**

Panel

CLIMAVER NETO

**

Panel

comunicacin y desarrollo, s.l. - Depsito Legal: M-28072-2003

(1) Puede realizarse con cualquier panel excepto Climaver Plata


Comportamiento ptimo
Leyenda:

**
* Buen comportamiento

SERVICIO

A CORUA
Mvil:
629 416 024
Tlfno./Fax: 98 117 70 08
e-mail:
felix.gonzalez@saint-gobain.com
BARCELONA
Mvil:
629 26 85 06
Fax:
93 419 30 63
e-mail:
jorge.rius@saint-gobain.com
Mvil:
639 180 396
Tlfno./Fax: 93 660 35 67
e-mail:
jordi.escobosa@saint-gobain.com
Mvil:
609 027 660
Tlfno./Fax: 93 750 72 18
e-mail:
diana.moller@saint-gobain.com
BILBAO
Mvil:
Tlfno.:
Fax:
e-mail:

619 406 995


94 448 39 24
94 447 22 48
josem.delaconcha@saint-gobain.com

MADRID
Mvil:
Tlfno.:
Fax:
e-mail:

639 767 985


91 397 20 28
91 397 24 05
miguelangel.maroto@saint-gobain.com

Mvil:
Tlfno.:
Fax:
e-mail:

629 315 873


91 397 22 56
91 397 24 05
jesus.sanchez@saint-gobain.com

MRIDA
Mvil:
629 509 075
Fax:
92 437 36 19
e-mail:
fernando.nieto@saint-gobain.com
MURCIA
Mvil:
Tlfno.:
Fax:
e-mail:

609 311 386


96 826 56 66
96 825 15 22
r.gomezalarcon@saint-gobain.com

SEVILLA
Mvil:
609 028 779
Tlfno./Fax: 95 457 80 88
e-mail:
victor.zamora@saint-gobain.com
VALENCIA
Mvil:
609 311 535
Tlfno./Fax: 96 371 54 85
e-mail:
joseluis.devicente@saint-gobain.com
VALLADOLID
Mvil:
649 975 180
Tlfno.:
98 334 20 99
Fax:
98 335 65 37
e-mail:
angel.lagunilla@saint-gobain.com
ZARAGOZA
Mvil:
629 914 560
Tlfno.:
97 629 36 42
Fax:
97 620 12 68
e-mail:
agustin.jimeno@saint-gobain.com

EXPORTACIN
GUADALAJARA
Tlfnos.: +34 949 26 83 63 / 64
Fax:
+34 949 26 83 84 / 85 / 86
e-mail: fernando.gimeno@saint-gobain.com

SERVICIO
COMERCIAL
DE LOGSTICA
GUADALAJARA
Mvil: +34 649 453 699
Tlfnos.: +34 94 926 83 62 / 64 / 65 / 67 / 68 / 98
Fax:
+34 94 926 83 84 / 85 / 86
e-mail: fernando.gimeno@saint-gobain.com

SG-C/DPP/06/CA2NETO/2003

ESPAA

PORTUGAL
LISBOA
E.N. 10 - Edificio Covina
2696-652 Sta Iria de Azia
Tlfne.:
+351 21 959 12 87
Fax:
+351 21 956 20 87
e-mail:
Telem.:
e-mail:
Telem.:

paulo.cabrita@saint-gobain.com
+351 938 71 55 51
pedro.soares@saint-gobain.com
+ 351 93 871 55 71

SAINT-GOBAIN CRISTALERA, S.A.


Paseo de la Castellana, 77
28046 MADRID

e-mail: isover.es@saint-gobain.com
www.isover.net

(BNB

@em\ik\i

4FNJJOEVTUSJBM1"$
s&$5-3PLITCONDUCTOS
s&$53PLITCONDUCTOSALTAPRESIN
s&$4#3PLITCASSETTEXMM
s&$43PLITCASSETTE
s&$%3PLITTECHO
s32+3PLITPARED
s-5,4) 6
s-ODELOSHASTAlNDEEXISTENCIAS

(BNB4FNJJOEVTUSJBM
0!#X)NVERTER

-ii

{7

x7

>?LV

 1

-
`V L>`iV>

@em\ik\i
V>Li
>?LV

 /

-
>ii
L>`iV>

@em\ik\i
V>Li
>?LV

-
>ii L>`iV>

@em\ik\i



 /

V>Li
>?LV

1`>`i
ii

-/iV L>`iV>

@em\ik\i
V>Li
>?LV

-*>i` L>`iV>

-,

@em\ik\i
V>Li
>?LV

-
`V>*i
L>`iV>

 1

@em\ik\i
V>Li

1`>`i
ii

-,

L>`iV>

@em\ik\i


UBSJGBAIRE

ACONDICIONADO



(BNB4FNJJOEVTUSJBM

x7

x7

{7

@em\ik\i

x7




n


n


n

n

n

UBSJGBAIRE

ACONDICIONADO



(BNB4FNJJOEVTUSJBM

0!#-ULTI 6)NVERTER

-ii

{7

 1

-
`V L>`iV>

@em\ik\i

 /

-
>ii
L>`iV>

@em\ik\i

 /

-
>ii L>`iV>

@em\ik\i

-/iV L>`iV>

@em\ik\i

-,

-*>i` L>`iV>

@em\ik\i

L>`iV>

@em\ik\i

x7

x7



V>Li

1`>`i
ii

1`>`i
ii

ii

@em\ik\i

,{

UBSJGBAIRE

ACONDICIONADO



(BNB4FNJJOEVTUSJBM

x7

{7

@em\ik\i

x7




n


n


n

n

n

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
,AGAMA0!#DE-ITSUBISHI(EAVY)NDUSTRIESESIDEALPARACLIMATIZAR
OlCINAS TIENDAS RESTAURANTES BARESxPARATODASAQUELLAS
INSTALACIONESDEUSOCOMERCIAL PRINCIPALMENTE,AVERSATILIDAD
DELAGAMA0!# LEOFRECEUNAAMPLIASELECCINDEMODELOSEN
FUNCINDELASNECESIDADESDEINSTALACINQUETENGA%LMODERNO
YATRACTIVODISEODENUESTRASUNIDADESINTERIORESSEINTEGRADE
FORMAARMONIOSAENLADECORACINCREANDOUNAMBIENTEAGRADABLE
YRELAJANTE

Q-UYSILENCIOSOS
3IELIGEELMODOSILENCIOSO LAUNIDADEXTERIORFUNCIONAR
CONUNAVELOCIDADREDUCIDADELVENTILADOR$EESTA
FORMA LAUNIDADGENERARUNNIVELDERUIDODED" UN
ESTNDARAMBIENTALPERFECTAMENTEADMISIBLEENUNAZONA
RESIDENCIALDURANTELANOCHE

4ODANUESTRAGAMAINCORPORAELREFRIGERANTEECOLGICO
2!QUE ADEMSDECUMPLIRCONNUESTROOBJETIVODERESPETAREL
MEDIOAMBIENTE HAPERMITIDOREDUCIRELTAMAODELASTUBERASY
CONSECUENTEMENTE SEHANREDUCIDOLOSCOSTESDEINSTALACIN

Q!LTOSCOElCIENTESDERENDIMIENTO
%%2Y#/0
%LALTOCOElCIENTEDERENDIMIENTOSEHAALCANZADOGRACIASA
LASMEJORASINTRODUCIDASENELINTERCAMBIADORDECALORYENEL
COMPRESOR



4RASCOMENZARAUTILIZARELNUEVOREFRIGERANTE2! LOS
INTERCAMBIADORESDECALORDELAUNIDADEXTERIORSEMEJORARON
ESENCIALMENTEEMPLEANDOUNTUBODEALTORENDIMIENTOQUE
DISMINUYELASPRDIDASDEPRESIN
!SMISMO ELmUJOUNIFORMEDEREFRIGERANTESECONSIGUECON
LAADOPCINDEUNNUEVODISTRIBUIDORYDEUNOSCIRCUITOS
MODIlCADOS
%NELCASODELCOMPRESOR SEUTILIZAUNMOTOR$#EQUIPADO
CONPOTENTESIMANESPERMANENTESDENEODIMIO'RACIASALA
SUMADELPARGENERADOPORELIMNPERMANENTEYELPARDE
RELUCTANCIA LAUNIDADHALOGRADOALCANZARUNALTOCOElCIENTEDE
RENDIMIENTO

Q4ODALAGAMACON4ECNOLOGA)NVERTER
4ODOSLOSMODELOSDESDE AFRIGORASENFROYDESDE
 ACALORASENCALOR INCORPORANLA4ECNOLOGA)NVERTER
#ONSEGUIMOSUNAMAYORElCIENCIAENERGTICAAHORRANDOHASTA
UNDELCONSUMOANUAL



-ODELOANTERIOR
.UEVOMODELO


















4ODASLASUNIDADESDELAGAMA0!# INCLUYENELCONTROLDE
CONDENSACINDESERIE ESDECIR PERMITENLAPOSIBILIDADDE
FUNCIONARENMODOFROCONUNATEMPERATURAEXTERIORINFERIORA
#HASTAUNMXIMODE #

Q %lCIENCIA REAL EN CONDICIONES DE


TEMPERATURAEXTREMAS
,OSEQUIPOS-ITSUBISHI(EAVY)NDUSTRIESALCANZANUNALTO
RENDIMIENTOENCONDICIONESCLIMATOLGICASADVERSAS

Q&ILTROSINCLUIDOSDESERIE
,ASUNIDADESINTERIORESDELAGAMA0!#
SPLITTECHO&$% SPLITCASSETTEVAS&$4 SPLICASSETTEXMM
&$4# SPLITCONDUCTOS&$5- INCLUYENlLTROSDEFBRICA

Q5NIDADES)NVERTER4RIFSICAS






Q#ONTROLDECONDENSACINDESERIE



,OSMODELOSDE Y(0CONTECNOLOGA)NVERTERESTN
DISPONIBLESCONALIMENTACINELCTRICAMONOFSICAYTRIFSICA



Q6ERSATILIDADDEINSTALACIN



{*

x*

*

n*

*

"ASADOEN*2!EN4OKIO

,ATECNOLOGA$#0!-)NVERTERBASASUFUNCIONAMIENTOENEVITAR
LOSCONTINUOSARRANQUESYPARADASDELCOMPRESOR DEFORMAQUE
MANTIENELATEMPERATURADECONSIGNACONMENOSmUCTUACIONES
REDUCIENDOELNIVELSONOROYGENERANDOIMPORTANTESAHORROSDE
CONSUMO%LCOMPRESORPUEDETRABAJARUNPORENCIMADE
SUPOTENCIALNOMINALYCONSEGUIRANTESLATEMPERATURADESEADA

UBSJGBAIRE

ACONDICIONADO



,AAMPLIAGAMADEUNIDADESINTERIORES LEPERMITEADAPTARSEA
CADANECESIDADDEINSTALACINQUESELEPLANTEE

Q#MOLEERELNOMBREDELMODELO

(BNB1"$*OWFSUFS
,ASDIMENSIONESDELASUNIDADESEXTERIORESSEHANREDUCIDOCONSIDERABLEMENTE
AHORRANDOUNIMPORTANTEESPACIODEINSTALACIN
2EDUCCINDEHASTAUNENELPESO UNENELVOLUMENYUNENEL
READELABASE RESPECTOAMODELOSANTERIORES
,AUNIDADEXTERIOR&$#6.HAREDUCIDOSUVOLUMENUN,ASMEDIDAS
CONSEGUIDASSONXXMMALTXANCHOXFONDO 

@em\ik\i

,AMAYORREDUCCINSEHACONSEGUIDOENLOSMODELOSDE
Y(0 MSDEUN
XXMMALTXANCHOXFONDO &$#63
XXMMALTXANCHOXFONDO &$#63

i>`i>L>i
n*
MODELOANTERIOR


MM

MM


MM

.UEVOMODELO

MM

MM
MM

,AUNIDADDELOSMODELOSDE Y(0PASADE
TENERDOSVENTILADORESAUNOSLO,ASDIMENSIONES
NUEVASSONXXMMALTXANCHOXFONDO
UNAREDUCCINDELRESPECTOALMODELOANTERIOR

Q&UNCIONESDELCONTROLPORCABLE

Q&UNCIONESDELCONTROLINALMBRICO



)NDICADORDE6ENTILACIN
)NDICADORDE#ONTROL#ENTRALIZADO
)NDICADORDE4EMPORIZADOR
)NDICADORDELATEMPERATURADECONSIGNA
"OTNDESELECCINDELATEMPERATURA
"OTNDEAJUSTEDELTEMPORIZADOR
"OTNDEREJILLAARRIBAABAJO
"OTNDEALARMADEMANTENIMIENTO
"OTNDEEJECUCINDECOMPROBACIONES
4EMPORIZADORSEMANAL
)NDICADORDELTIEMPO
)NDICADORDEVELOCIDADDEAIRE
)NDICADORDELMODODEFUNCIONAMIENTO
,MPARADEALARMADEFUNCIONAMIENTOMANTENIMIENTO
"OTNDEPUESTAENMARCHAYPARO
"OTNSELECTORDELMODODEFUNCIONAMIENTO
"OTNDEVENTILACIN
"OTNSELECTORDELAVELOCIDADDELAIRE
"OTNSELECTORDELADIRECCINDELAIRE
"OTNDECONlGURACIN
"OTNDECONlRMACINDEFUNCIN

3ELECTORDELMODODEOPERACIN!UTO #OOL $RY (EAT &AN 


3ELECTORDELAVELOCIDADDELVENTILADOR&!.30%%$ 
$IRECCINDELmUJODEAIRE!)2&,/7 
-ODODE4EMPORIZADOR4)-%2 
#ONMUTADORDEREPOSICINPARAREPONERELMICROORDENADOR
CUANDOOCURREALGUNAANORMALIDAD
3ELECTORTEMPERATURADELASALA
)NDICADORDEREPOSICINDELlLTRO
0ROGRAMACINDELAHORAPARAPONERLAHORAACTUALYLAHORA
DEOPERACINCONTEMPORIZADOR
!JUSTEDELAHORA
#ONMUTADORDERELOJ
.OTA#ONTROLINALMBRICOINCLUIDODESERIEPARALASUNIDADES
INTERIORES&$%/PCIONALPARALOSMODELOS&$4 &$4# &$52Y&$5

.OTA#ONTROLPORCABLEINCLUIDODESERIEPARALASUNIDADES
INTERIORES&$4 &$4# &$5- &$5
/PCIONALPARALOSMODELOS&$%

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
3ERIE&$5-3PLITCONDUCTOS)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

'%6.7/

?
 

'%6.7/

 1x6

 16

 16

 16

 1x6

 1{6

-,
x<8

-,
<8


6


6 -


x6 -


{6 -

6x

]x]x]

'%6.7/4 '%6.7/4 '%6.7/4

6xn6x

 6 ,/ ,

]nx]]

]]n]

{]]

x]]x{

x]{{]x

V> {{nx {{nxx{ x {xnx {xx {x{

>>V`>`

?

>

]xx]{]

]]]

]n]]

{]]]x

{]{

{]]x

V> x{xx{ xxn n {xxx {xxn {xn{

]x

]n

]n

]n

{]

]{

]n

{]n

n]

]x{]

n]]

]]{

]{{]

x]

]]{

,
>wV>V i}jV> 

"*
iwVii i}jV
>

]{

]x

]n

]n

]{

{]{

]n

i>`i`iwV>V
ii}jV>

!

"

!

!

"


>

!

"

!

!

!

ijVV>


?

>

i`>`>


>


i`>`?>`i>>i



'%6.7/

 1`i
iiV`>`L>>
1`ii

ii>>Vv`

` 

{{n

1`i

1`ii
1`i

*i

*ii?V>1`i

xx

n{x

{
{

1`ii

?`>

nxn]x

*>V>

?>
i>`i`

xn{

1`i

>`>`ii

xx

{n

`i`iiViiVViI

*iV>}>`i
iv}i>i

>}>>`V>`i
iv}i>i

}
}``ii>iVLi>V>}>

}`ii>v}wV>

>V>v}wV>

/>r>6iV>

6iV>

}``iLi>

xn

]x/

{//{ /n/{ /
,{

* 6 ,/ ,

]x

]n

V>``ii?>>

V>``ii?>>

V>``ii?L>>

xV>``ii?L>>


1 " - ,

`Vi`ivV>i

-/$%,/332#  &$#   

UBSJGBAIRE

ACONDICIONADO



]{

`iV`i>V

nxn]x

]x/

`i`i>i>V>>`iiiVViI

,iv}i>i

/`iVi

*}>`>

i>`i>

/Li>`iiv}i>i

"

{n

xxxx

}

1`ii

{]x

3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

(BNB1"$*OWFSUFS

@em\ik\i

2# %
&$5-  
  6

32#:)8
32#:(8

&$#6.

&$#  6.3


)  ))) 

3PLITCONDUCTOS)NVERTER"OMBADECALOR
&$5

s ,ASUNIDADESEXTERIORESMSCOMPACTASDELMERCADO

s 5NIDADESEXTERIORESCONALIMENTACINMONOFSICAYTRIFSICADE Y(0

s 4ECNOLOGA)NVERTERMAYORCONFORTABILIDAD AHORROENERGTICOYECONMICO

s !LTOCOElCIENTEDERENDIMIENTO#/0GRACIASALASMEJORASINTRODUCIDASENELINTERCAMBIADORDECALOR
YENELCOMPRESOR

s %QUIPOSMUYSILENCIOSOS



s &ILTROSINCLUIDOSDEFBRICA
s 0RESINESTTICASELECCIONABLEMX0AENA#6

s ,ASSERIES&$5-PUEDENCOMUNICARSEMEDIANTEUNSISTEMA3UPER,INK LOQUEPERMITEUTILIZARUN


SISTEMADECONTROLCENTRALIZADO0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO
3UPER,INK3# !$. %


s /PCIONAL0OSIBILIDADDECONTROLINALMBRICO2#. +)4 %#ONSULTAR


s 3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICO
NOINCLUIDODESERIEENELEQUIPO#ONSULTARPG

L>`i i>i



L`>`i`ii

)NCLUIDADESERIE

0RECIOSY#APACIDADES

`i

 1x6
 16
 16
 16
 16-

 1x6

 1x6-
 1{6
 1{6-

>>V`>`V>

>wV>Vij}iV>
,

*6,

>

"*
>

{
{nx

n
n

{x
xn

x
x

"
#

"
"

"
#

"
"

x]
]
]
x]
nxx]

x
x
x
x

x
x
n
n

#
#
$
$

"
"
#
#

{]
{x]
{n]
{n]

>\ -ONOFSICA) 6(Z


-4RIFSICA))) 6(Z

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
3ERIE&$53PLITCONDUCTOS!LTA0RESIN)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

 

i`>`>

'%67/4

'%67/4

'%674

 16

 1x6

 1{6

 16

 1x6


6


6 -


x6 -


{6 -


6-


x6-

V>

]]n

6xn6x n6x
x]]x{

x]{{]x

]{

]xn

{xnx

{xx

{x{

nx{

]n

{]]]x

{]{

{]]x

]]{x

]xn]x

{xxx

{xxn

{xn{

xxx

n{
]

]n

]nn

{]{

{]x

]x

{]{

]n

n]x

]{]

]n]

]]{

]n

x]

]{]{

]x]

]x]

{]{

]{

]{

]n

]x


>

]x

]n

!

"

#

"

!

!

!

!


>

!


i>`i`iwV>Vii}jV>

!

>

 1`iiV`>`L>>
i
` 
iV`>`L>>

{n
1`ii`v
1`i
ii
>>Vv`
1`ii



>`>`ii

/Li>`i
iv}i>i

xnxxxx

xn

n{x

1`ii

1`iiV`>`>>

xx

xn

}

1`ii`v
*>V>

?>
i>`i`

*}>`>

i>`i>

`i`iiViiVViI

xx

,{

/`iVi

}
*iV>}>`i
iv}i>i
}``ii>iVLi>V>}>


* 6 ,/ ,

]x

]n

V>``ii?>>

xV>``ii?L>>


1 " - ,

>}>>`V>
`iiv}i>i

}`ii>v}wV>

/>r>6iV>

6iV>

`iV`i>V


>V>
v}wV>

{//{ /n/{ / /

x]{

>\->}``i>i>v}wV>iVi`i`i>`iLi>`i``iii`in
->}``i>Li>V>iVi`i`i]iVii`iLi>`i`iiii>>}

->Li>V>ii}>`i]iVii`iLi>`i`niiii>>}
>\->Li>V>ii`iiVi(`iLi>`i}>`ini}>`i

}``iLi>

UBSJGBAIRE
ACONDICIONADO


]x/

`i`i>i>V>>`iiiVViI

,iv}i>i

nx

?`>

*ii?V>
1`i

xn{

1`i

{]]

i`>`?>`i>>i

*i

'%674

>

,
>wV>V i}jV>

"*
iwVii i}jV

'%67/4

 16

V>

ijVV 
>

>

'%67/

6x
7

>>V`>`

>

`Vi`ivV>i

3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

(BNB1"$*OWFSUFS

&$56

&$56

2# %

&$#6.

&$#  6.3


)  ))) 

@em\ik\i

&$#63

&$#63

L>`i i>i

3PLITCONDUCTOSALTAPRESIN)NVERTER"OMBADECALOR
&$5

-ODELOS&$5   6

s !MPLIACINDEGAMACONDUCTOSALTAPRESINDESDE AK7ENREFRIGERACINYDESDE


s ,ASUNIDADESEXTERIORESMSCOMPACTASDELMERCADO SEHAREDUCIDOHASTAUN

A K7ENMODOCALEFACCIN

s &ACILIDADDETRANSPORTE0ERMITESUBIRLOENASCENSORSINNECESIDADDECONTRATARUNAGRA


L`>`i`ii

s 4CNOLOGA)NVERTER

s #ONDUCTOSDEALTAPRESINESTTICA

s -AYORESLONGITUDESDETUBERAHASTAMDELONGITUDTOTAL
s #ONTROLDECONDENSACININCLUIDODESERIE PERMITEFUNCIONARENMODOREFRIGERACINHASTAUNMXIMODE #
s/PCIONAL0OSIBILIDADDECONTROLINALMBRICO2#. +)4 %#ONSULTAR
s 3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICO
NOINCLUIDODESERIEENELEQUIPO#ONSULTARPG

s,ASSERIES&$5PUEDENCOMUNICARSEMEDIANTEUNSISTEMA3UPER,INK LOQUEPERMITEUTILIZAR
-ODELOS&$5   6


UNSISTEMADECONTROLCENTRALIZADO0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO
3UPER,INK3# !$. %

1`>`iiiiV>V>

-iV]V>V}i
*ii
Li
>Vittt

-ODELO&$56.ULTRAPLANO PERMITEINSTALARUNSPLITCONDUCTOS
DEALTAPRESINENCUALQUIERTIPODEHABITACIN
,OSMODELOS&$5.63INCLUYENBOMBADE
DRENAJEDESERIEHASTAUNAALTURAMXIMADEMM

>
x

0ERFECTOPARAESPACIOSGRANDESY
ABIERTOSYAQUE GRACIASASUALTA
PRESINESTTICA SECONSIGUEUN
DISEOLIBREYmEXIBLE

MM

MM

MM

xMM
MM

xMM

0RECIOSY#APACIDADES

`i

 16
 16

>>V`>`V>


>

>wV>Vii}jV>
,

*6,

"*
>

]

n
n

x
x







nx]
]

x
x

x
x




{x]
{{{]

 1{6-
 16-

x
x

n
n





{n{]
xx]
n{x]

 1x6-

nn]

 16-
 1x6
 1x6-
 1{6

>\ -ONOFSICA, 6(Z-4RIFSICA,,, 6(Z


>\#ONSULTARDISPONIBILIDADYPLAZOSDEENTREGA
>\&ILTROSOPCIONALES SOLICITARLOSALREALIZARSUPEDIDO#ONSULTAR

UBSJGBAIRE

ACONDICIONADO






(BNB1"$*OWFSUFS
3ERIES&$4#3PLITCASSETTEXMM)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

>>V`>`

 


>



6x

]n{{]

]xx]

xx{x{x

{{n

{]xx]{

]xx]{]

x{x

x{xx{
]x
]{x

{]

{]

]{

]nx


>

{]

!

>

!




{nxx

{n

]x

1`ii

 1`i

]x

]x/

]x/

,{


* 6 ,/ ,
]{

1`i

` 

1`ii
1`>`

*>i

1`>`
}

*>i

1`ii
i>`i`

*}>`>

i>`i>
`i`iiViiVViI
`i`i>i>V>>`iiiVViI

,iv}i>i

/`iVi
}
}``ii>iVLi>V>}>

V>``ii?>>

V>``ii?L>>


1 " - ,

>}>>`V>`iiv}i>i }`ii>v}wV>
/>r>6iV>

`iV`i>V


1`i

>V>v}wV>

1`ii

*iV>}>`iiv}i>i

-,
x<8

1`i

/Li>`iiv}i>i

]{

ii>>Vv`

-,
{<8

i>`i`iwV>Vii}jV>


iiV`>`L>>

>`>`ii

 /
x6

'%5$ /
7/

i`>`?>`i>>i

*i

V>


>

,
>wV>V i}jV>

"*
iwVii i}jV

 /
{6


>

i`>`>

'%5$ /
7/

V>

ijVV>


6iV>

I/\V>Li`ii>

}``iLi>

`Vi`ivV>i

-/$%,/332#:I8



UBSJGBAIRE

ACONDICIONADO



3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

@em\ik\i

(BNB1"$*OWFSUFS

&$4# 6

2# %

32#:(8
32#:)8

3PLITCASSETTE)NVERTER"OMBADECALOR
&$4#XMM



s 4ECNOLOGA)NVERTERMAYORCONFORTABILIDAD AHORROENERGTICOYECONMICO

s )NCLUYETUBOmEXIBLEDEMMCOMOACCESORIOESTNDAR LOQUEMEJORALAMANIOBRABILIDADDELA

INSTALACINDELAUNIDADALAHORADETENDERLASTUBERASDEDRENAJE

s 3PLITCASSETTEVASXMMPARATECHOMODULAR

s !JUSTEDELAINSTALACINCONUNAHOLGURADEMMPARAPERMITIRLAROTACINDELPANEL

s ,ASSERIES&$4#PUEDENCOMUNICARSEMEDIANTEUNSISTEMA3UPER,INK LOQUEPERMITEUTILIZAR


UNSISTEMADECONTROLCENTRALIZADO0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO
3UPER,INK3# !$. %

s3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICO
NOINCLUIDODESERIEENELEQUIPO#ONSULTAR



L>`i i>i

"*
" \
,
/
{7 ,

)NCLUIDADESERIE

>`>`>V>v>V>0ARASUINSTALACINSLOREQUIEREUNKITRECEPTORQUESEPUEDE
COLOCARENCUALQUIERESQUINADELCASSETTE FACILITANDOLASLABORESDEINSTALACIN3EHANMEJORADOLASPRESTACIONES
DEESTEMANDOAMPLIANDOLASOPCIONESRESPECTOAMODELOSANTERIORES#ONSULTARPRECIOENPG

i>V`i>>V

0RECIOSY#APACIDADES

`i

>>V`>`V>

>wV>Vii}jV>

*6,

>

,

"*
>

 /
{6

{x

!

{]

 /
x6

{x

!

]

>\ 5NIDADESCONCONTROLINALMBRICOOPCIONAL EJ&$4#.6.0ARASOLICITARELEQUIPOCONCONTROLPORCABLE DEBEPEDIR

LAREFERENCIAQUENOINCLUYELA EJ&$4#6.

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
>>*

3ERIES&$43PLITCASSETTE)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

>>V`>`

 


>

ijVV 
>

>

i`>`> 

'%5 /
7/ '%5 /
7/

-,
{<8



ii
>>Vv`

-,
<8


6


6 -

 /x6

 /{6


x6 - 
{6 -

]nx]]

]]n {]] x]]x{ x]{{]x


x {xnx {xx {x{

]{]xx]{ ]xx]{]

]]]

V> x{x x{xx{

xxn

]n

{]]x

{{

{]x

n {xxx {xxn {xn{

]x

{]x

]x

]nx

]{

{]x

{]

x]

n]

]{]

]x]

]{

x]

x]

n]

]{]

]x]x

]]

{]

]nn

]x

]{

]n


>




{]n

{]

]n

{]

]x

!

!

!

!

!

"


>

!

!

!

!

!

!

"

 `iiV`>`L>>

` 

xn

1`ii`v

{{n

1`i

{n{n{

nn{n{

xxx

{n

xn{

n{x

1`>`

*>i

1`>`
}

*>i

*i
1`ii

x]x

{{

1`ii

i>`i`

xn

 1`i

*}>`>

i>`i>

`i`iiViiVViI

`i`i>i>V>>`iiiVViI

,iv}i>i

/`iVi
*iV>}>`i
iv}i>i

-,
x<8

'%5 /
7/4 '%5 /
7/4


1`i

/Li>`i
iv}i>i

 /6

{{nxx{

1`ii

>`>`ii

'%5 /
7/4

 /6

]n{]{] ]x]x]

i`>`?>`i>>i

i
iV`>`L>>

'%5 /
7/

 /6

V> xx{x{x {{n


>

i>`i
`iwV>V
ii}jV>

'%5 /
7/

 /x6

6x 6xn6x

,
>wV>V i}jV>

"*
iwVii i}jV

 /{6

]x/

]x/{//{ /

,{


* 6 ,/ ,

]{

]x

]n

}

}``ii>iVLi>V>}>

>}>>`V>`i }`ii>v}wV>
iv}i>i
/>r>6iV>
>V>


v}wV>
6iV>

`iV`i>V

/>`i>iii

V>``ii?>>

V>``ii?>>

V>``ii?L>>

xV>``ii?L>>


1 " - ,

*"- 

I/\V>Li`ii>

}``iLi>

`Vi`ivV>i

-/$%,/332#

UBSJGBAIRE
ACONDICIONADO


-/$%,/3&$#   Y32# 

3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

(BNB1"$*OWFSUFS

&$4   


  6

2# %

32# :(8
32#:)8

@em\ik\i

&$#  6.3


)  ))) 

&$#6.

3PLITCASSETTE)NVERTER"OMBADECALOR
&$4.

s .UEVODISEODELAUNIDADINTERIOR

s ,ASUNIDADESEXTERIORESMSCOMPACTASDELMERCADO



`i>>>iV>

3OLO&$4 

s 5NIDADESEXTERIORESCONALIMENTACINMONOFSICAYTRIFSICADE Y(0
s 4ECNOLOGA)NVERTERDESDEAK7ENFROYDESDE AK7ENCALOR

s !LTOCOElCIENTEDERENDIMIENTO#/0GRACIASALASMEJORASINTRODUCIDASENELINTERCAMBIADORDECALORYENELCOMPRESOR

s %QUIPOSMUYSILENCIOSOS

s )NCLUYETUBOmEXIBLEDEMMCOMOACCESORIOESTNDAR LOQUEMEJORALAMANIOBRABILIDADDELAINSTALACINDELA


s ,ASSERIES&$4PUEDENCOMUNICARSEMEDIANTEUNSISTEMA3UPER,INK LOQUEPERMITEUTILIZARUNSISTEMADE

UNIDADALAHORADETENDERLASTUBERASDEDRENAJE

CONTROLCENTRALIZADO0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO3UPER,INK3# !$. %

s3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICONOINCLUIDODESERIEENEL

EQUIPO#ONSULTARPG



/iV

>>`ii`ii

L>`i i>i
)NCLUIDADESERIE

0RECIOSY#APACIDADES

"*
" \
,
/7
>`>`>V>v>
V>0ARASUINSTALACIN
SLOREQUIEREUNKITRECEPTORQUESE
PUEDECOLOCARENCUALQUIERESQUINA
DELCASSETTE FACILITANDOLASLABORES
DEINSTALACIN3EHANMEJORADO
LASPRESTACIONESDEESTEMANDO
AMPLIANDOLASOPCIONESRESPECTOA
MODELOSANTERIORES#ONSULTARPRECIO
ENPG

`i

>

,v

"*
>

 / {6
 / x6

{x
{
{nx

{x
xn









x]
x]
]







{]
n]

n
x
x
x
x

x
x
x
n
n





{nx]
{{nx]
{x]
xx]
xx]

 /
 /
 /
 /

6
6
6
6-

 /
 /
 /
 /

x6
x6-
{6

{6-

>>V`>`V>

>wV>Vii}jV>

*6,

>\ 5NIDADESCONCONTROLINALMBRICOOPCIONAL EJ&$4.6.0ARASOLICITARELEQUIPOCONCONTROLPORCABLE DEBEPEDIR

LAREFERENCIAQUENOINCLUYELA EJ&$46.

>\ -ONOFSICA) 6(Z

-4RIFSICA))) 6(Z
>\#ONSULTARDISPONIBILIDADYPLAZOSDEENTREGA

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS

>>*

3ERIES&$%3PLITTECHO)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

'%& /
7/

'%& /
7/

'%& /
7/

 {6

 x6

 6

 6

-,
{<8

-,
x<8

-,
<8


6

6x

>>V`>`

 

6xn6x

 6 ,/ ,

x {xnx {xx {x{

]{]xx]{

]xx]{]

]]]

]n]] {]]]x

V> x{x

x{xx{

xxn

{xxx

{]{

{]]x

{xxn {xn{

]{

]x

]x

]nx

{]


>

]xn

]x

{]

{]

n]

n]

]x{]

n]]

]{

x]

]{

]n

{]

]x]{

]x]n


>
i`>`?>`i>>i

{]n

,
>wV>V i}jV>

"*
iwVii i}jV

]nx

]x

]n

]x

]x

]x

]n


>

]n

]{

]n{

]{

i>`i`iwV>V
ii}jV>

!

"

#

!

!

"


>

!

"

#

!

!

!

 1`i

i
iV`>`L>>



 {6

V> xx{x{x {{n {{nxx{

i`>`>

 x6

]]n] {]] x]]x{ x]{{]x

ijVV
>

 6


6 - 
x6 - 
{6 -

]n{]{] ]x]x] ]nx]]


>

'%& /
7/ '%& /
7/4 '%& /
7/4 '%& /
7/4

1`ii

{n

1`i

1`ii

n{x

1`i

1`ii

i>`i`

`i`iiViiVViI

]x/

`i`i>i>V>>`iiiVViI

,iv}i>i

/`iVi

]x/

{/

,{



* 6 ,/ ,

ii
>>Vv`
*i

}

1`ii
1`i

>`>`ii

/Li>`iiv}i>i

*}>`>

i>`i>

}

"

` 

xn{

{
n

x
n

xn

/{ /

]{

/>r>6iV>

>V>v}wV>
6iV>

`iV`i>V

V>``ii?>>

V>``ii?L>>

]x


}``ii>i

VLi>V>}>

>}>>`V>`iiv}i>i }`ii>v}wV>

*iV>}>`iiv}i>i

{n

]n

V>``ii?>>

xV>``ii?L>>


1 " - ,

I/\V>Li`ii>

}``iLi>

`Vi`ivV>i

-/$%,/332#

-/$%,/332#  &$#   

3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS

&$%.   


  6

32# :(8
32#:)8

2#. % 2

@em\ik\i

&$#6.

&$#  6.3


)  ))) 

3PLITTECHO)NVERTER"OMBADECALOR
&$%.

s ,ASUNIDADESEXTERIORESMSCOMPACTASDELMERCADO

s 5NIDADESEXTERIORESCONALIMENTACINMONOFSICAYTRIFSICADE Y(0

s !LTOCOElCIENTEDERENDIMIENTO#/0GRACIASALASMEJORASINTRODUCIDASENELINTERCAMBIADORDECALORYENEL

COMPRESOR#UANTOMAYORESEL#/0MAYORESLAElCIENCIAENERGTICADELEQUIPO

s 4ECNOLOGA)NVERTERMAYORCONFORTABILIDAD AHORROENERGTICOYECONMICO

s %QUIPOSMUYSILENCIOSOS

s 0RESTACIONESDEINSTALACINMEJORADASDISEOLIBREDELASTUBERASADAPTNDOSEATODASLASCONDICIONESDE

INSTALACIN

s $ISEOIDEALPARAINSTALARENOlCINAS RESTAURANTES TIENDASxSINFALSOTECHO


s ,ASSERIES&$%PUEDENCOMUNICARSEMEDIANTEUNSISTEMA3UPER,INK LOQUEPERMITEUTILIZARUNSISTEMA

DECONTROLCENTRALIZADO0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO3UPER,INK3# !$. %



s3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICONOINCLUIDO

DESERIEENELEQUIPO#ONSULTAR

"*
" \
,

>V`>``i>>V>ii

-ANDOPORCABLEQUEINCORPORAUNGRANCONJUNTODEFUNCIONES
PROGRAMADORSEMANALDEENCENDIDOAPAGADO CONTROLDE
TEMPERATURADECONSIGNA DISPLAYDEERRORESDELAUNIDAD SONDA
DETEMPERATURAINTEGRADA INDICADORYSELECTORDEVELOCIDADY
DIRECCINDELAIRECONTROLDELhSWINGv SELECTORDELMODODE
OPERACIN CONTROLDEPUESTAACEROTODOELLOCONUNINDICADORDE
,#$DEATRACTIVODISEO#ONSULTARPRECIOENPG

0RECIOSY#APACIDADES

`i


>>V`>`V>

>wV>Vii}jV>

*6,

>

,v

"*
>

 {6
 x6
 6

{x
{
{nx

{x
xn

x]
{x]
x]

 6
 6

n]

n]

 6-
 x6

n
x

x
x




x]
{x]

 x6-

{{]

 {6
 {6-

x
x

n
n

x]
xxx]

>\ 5NIDADESCONCONTROLINALMBRICOOPCIONAL EJ&$%.6.0ARASOLICITARELEQUIPOCONCONTROLPORCABLE DEBEPEDIR

LAREFERENCIAQUENOINCLUYELA EJ&$%6.
>\ -ONOFSICA) 6(Z

-4RIFSICA))) 6(Z

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
3ERIES32+3PLITPARED)NVERTER"OMBADECALOR

1`i

1` i

i>VijVV>>>`>` i

>>V`>`

i`>`>

-,<8

-,<

-,
x<8

-,
<8

-,
<

 


>

7
?

V>


>



>

i`>`?>`i>>i

nx

xnxn{x

]]]

]x]n]

]]]n

]]x]

]x]]

]]]x

x]

n]

x]




]n]]x

]n]n]

xx

xxnx

]]n]n

]]n]

]n]]n

{xx

6x

]x]]

]nx


>

{]{{

{]

i>`i`iwV>Vii}jV>

>

 1`i

,
>wV>V i}jV>

"*
iwVii i}jV

1`ii

{nx

1`ii

{nx

1`i

1`ii

1`i

1`ii

iiV`>`L>>

1`i

>



43,;)9

-,x<8

7
?
V>

ijVV>

43,;*9

43,;&

ii>>Vv`

*i

` 

}

nn{n

{n

n
x

1`iiV`>`>> ]x{]x

{]x
1`ii`v

>`>`ii

/Li>`iiv}i>i

i>`i`

i>`i>
`i`iiViiVViI
,iv}i>i

/`iVi
*iV>}>`iiv}i>i

xn

/]x

/]x

,{

}

]{]{

}``ii>iVLi>V>}>

>}>>`V>`iiv}i>i

]x

*}>`>

xnn{

/iV}>
*ii

}`ii>v}wV>

i}jV

i`>i

>V>v}wV>

/>6iV>>

?iV>

i>VijVV>>>`>`i 1`i

1`ii

`iV`i>V

]x


1 " - ,

I/\V>Li`ii>

}``iLi>

`Vi`ivV>i

"

UBSJGBAIRE

ACONDICIONADO



3EGNLASCONDICIONES
DELANORMA)3/ 4 )3"

(BNB1"$*OWFSUFS

@em\ik\i

32+:)8 32+:(8

32#:)8 32#:(8

32+:%

32#:%

V \/PTIMIZAALMXIMOLA
DISTRIBUCIN DEL AIRE APORTANDO MA
YORCONFORTASUHOGAR

>}>V>Vi\%LAIRELLEGAATO
DOSLOSRINCONESDELAHABITACIN

i>iV>`i
>>>\#ONSIGUEMSRPIDAMEN
TELATEMPERATURADESEADA

`i\-,<8-,<8
2EFRIGERACIN

#ALEFACCIN

3WING6ERTICAL

3WING

3WING


-OVIMIENTODELOSLABESENPOSICIONESVERTICALYHORIZONTALMENTE

3WING
3WING

#OOL3HOWER



&LOOR

3PLITPARED)NVERTER"OMBADECALOR
32+

i V >i> v>

`i>i\/PTIMIZALASALIDADEL
AIREYFACILITASULIMPIEZA

`i\-,<8]-,<8

s !LTOCOElCIENTEDERENDIMIENTO
s 4ECNOLOGA$#0!-)NVERTERSUPONEUNMAYORRENDIMIENTOYUNMENORCONSUMOENERGTICO
s &ILTROSALERGNICOSYDESODORIZANTEFOTOCATALTICOCAPTURAYELIMINAPARTCULASCOMOPELODEANIMALES

s -EJORDISTRIBUCINDELAIRE GRACIASALMOVIMIENTOHORIZONTALYVERTICALDELOSLABES






s 0OSIBILIDADDECOMUNICARSEMEDIANTEUNSISTEMA3UPERLINKYUTILIZARUNSISTEMADECONTROLCENTRALIZADO



POLEN VIRUS ETCYNEUTRALIZALOSMALOSOLORES

0ARAELLOESNECESARIOINCORPORARALAUNIDADINTERIORELCIRCUITO3UPERLINK3# !$. %,OSMODELOS


32+:)8Y32+:(8NECESITANELADAPTADOR3# ")+. % 

s #ONTROLDECONDENSACININCLUDODESERIEPERMITEFUNCIONARENMODOFROCONUNATEMPERATURAEXTERIOR

INFERIORAO#HASTAUNMXIMODE O#

s3ISTEMA$OMTICO%QUIPOSCOMPATIBLESCONELSISTEMA+8.%)"ATRAVSDEINTERFACEDOMTICONOINCLUIDO

DESERIEENELEQUIPO#ONSULTAR

"*
" \
,

-ANDOPORCABLEQUEINCORPORAUNGRANCONJUNTODEFUNCIONESPROGRAMADORSEMANALDEENCENDIDOAPAGADO
CONTROLDETEMPERATURADECONSIGNA DISPLAYDEERRORESDELAUNIDAD SONDADETEMPERATURAINTEGRADA
INDICADORYSELECTORDEVELOCIDADYDIRECCINDELAIRECONTROLDELhSWINGv SELECTORDELMODODEOPERACIN
CONTROLDEPUESTAACEROTODOELLOCONUNINDICADORDE,#$DEATRACTIVODISEO#ONSULTARPRECIOENPG

0RECIOSY#APACIDADES

`i

-,x<8
-,<8
-,<8

>>V`>`V>

>wV>Vii}jV>

>

,

"*
>

{
x

x
xnx

!
!
!

!
!
!

>\#ONSULTARDISPONIBILIDADYPLAZOSDEENTREGA

*6,

nn]
n]
x]

UBSJGBAIRE

ACONDICIONADO



(BNB1"$*OWFSUFS
-ODELOSHASTAlNDEEXISTENCIAS

3PLIT#ONDUCTOS"OMBADE#ALOR
`i

&$52!.

&$5-!.

,iv}i>i

2!

i>VijVV>>>1ii




>>V`>`

>

) 6(Z

 

V>



 

V>



ijVV>

 

>

 

1i
iiV`>`L>>

` 

1ii

1ii

XX

XX



}

1ii
i>`i`
/Li>`iiv}i>i

0RECIOSYCAPACIDADES

XX

1i>i

*i




1i
ii>>Vv`




v

*}>`>

i>`i}>

`i
>>V`>`V>*6,


>

 1, x]
 1 ]

v

3PLIT#ASSETTE"OMBADE#ALOR



`i

&$4. !.

,iv}i>i

i>VijVV>>>1ii


>>V`>`

>


ijVV>

 

V>



 

V>



1i

 


` 

1ii



1i`>`
ii>>Vv`

1i>i

XX
XX

1ii

XX

1i`>`
*i

1i>i


}

0RECIOSYCAPACIDADES

1ii



i>`i`

/Li>`iiv}i>i

 

>

iiV`>`L>>

2!

) 6(Z

`i
>>V`>`V>*6,


>

v
*}>`>

i>`i}>

v

 / 

]

3PLIT0ARED"OMBADE#ALOR
`i

&$+.0(

,iv}i>i

i>VijVV>>>1ii

>

 

V>



 

V>



 

1i



` 

1ii



1i
ii>>Vv`
*i

XX

1ii

XX

1i>i



i>`i`

v

*}>`>

i>`i}>

UBSJGBAIRE

ACONDICIONADO



0RECIOSYCAPACIDADES

 

}

1ii
/Li>`iiv}i>i

 

>

iiV`>`L>>

2#

) 6(Z

>>V`>`

ijVV>

v

`i
>>V`>`V>*6,


>

  *n

n]

(BNB1"$*OWFSUFS

@em\ik\i

3PLIT0ARED)NVERTER"OMBADE#ALOR

`i

&$+.6!

,iv}i>i

i>VijVV>>>1ii

7
V>

>>V`>`

>

7
V>

>

1i
iiV`>`L>>

1ii

` 

1i
ii>>Vv`

1ii

1i>i
*i
/Li>`iiv}i>i

1ii
i>`i`

}
*}>`>

i>`i}>

&$+.6!

2!

) 6(Z

/iV}>

ijVV>

&$+.6!

).6%24%2

    
  

    

    

  

  

    

     

     

  

  

     

     

     

     

     

     









XX

XX





v

  

v

0RECIOSYCAPACIDADES
`i
>>V`>`V>*6,


>

v

  6x {x ]
  6{{xn]
  6x{x{x]



-ULTI 6!
5NIDADEXTERIOR5NIDADESINTERIORES
`i

&$#!.

&$+.!

&$4!

iVV

5NIDADEXTERIOR

3PLITPARED

3PLITCASSETTE

,iv}i>i

i>VijVV>>>1ii




>>V`>`

>


ijVV>

>
1i

iiV`>`L>>

1ii

1i>i

 









 

 

 

V>







 

 





` 

1ii

*i

1i>i
1ii


V>

1i`>`

ii>>Vv`

2!
) 6(Z

}




XX

XX

XX

XX





/Li>`iiv}i>i

i>`i`

v

v

*ii?V>

i>`i}>

*}>`>

v

v



0RECIOSYCAPACIDADES
`i
>>V`>`V>*6,


>


 x]
  x{x{x]
 /x{xx]

UBSJGBAIRE

ACONDICIONADO



.VMUJ7*OWFSUFS
3ISTEMA-ULTI 6)NVERTER"OMBADECALOR
Q3ISTEMA-ULTI 6CONTECNOLOGA)NVERTER


,EOFRECELASMEJORESVENTAJASPARASUNEGOCIO%STESISTEMAESIDEALPARACLIMATIZAROlCINAS
TIENDAS RESTAURANTES BARES PARA TODAS AQUELLAS INSTALACIONES DE USO COMERCIAL DONDE EL
EQUIPOREQUIERAUNALTORENDIMIENTOYSEQUIERAAHORRARENERGA
1`>`iiiiV>V>
,A VERSATILIDAD DE LAS UNIDADES INTERIORES PERMITE ADAPTARSE A CUALQUIER NECESIDAD DE INS
TALACINQUESELEPLANTEE CONLAVENTAJAAADIDA DEQUELASDIMENSIONESDELASUNIDADES
EXTERIORESSEHANREDUCIDOCONSIDERABLEMENTEAHORRANDOUNIMPORTANTEESPACIOYTIEMPODE
INSTALACIN
%STESISTEMAPERMITECONECTARHASTAUNIDADESINTERIORESDIFERENTES
-iV>
%LDISEODELASUNIDADES TANTOINTERIORESCOMOEXTERIORES HALOGRADODISMINUIRELNIVEL
SONORO OFRECIENDOUNMAYORCONFORT

4ODASLASUNIDADESFUNCIONANALMISMOTIEMPOYSERNCONTROLADASPORUNMISMO
MANDOPORCABLE2# %

4ABLADE#OMBINACIONES
1` i

4IPO

L>Vi


6

{{


6 -

xx

`LV`iLi>

-7




x6 -

/
x
/

/i

xxx


{6 -/ -7I

-7
x


6/i

-/ -7 -7I

Li/

xxxx

-7i
-7 i

xx

-7

x
-7i
-7 i

/i


x6-

Li/

-7i
-7 i

5NIDADESINTERIORESCOMPATIBLES
#APACIDAD

-ODELO













3PLIT0ARED32+
3PLIT#ASSETTEVAS&$4
3PLIT#ASSETTEVASXMM&$4#
3PLIT4ECHO&$%.
3PLIT#ONDUCTOS&$5-
5NIDADESEXTERIORES


6 ]
6 -]
x6 -]
{6 -]
6-]
x6-

>\%SPOSIBLECOMBINARDIFERENTESMODELOSDEUNIDADESINTERIORES
>\$EBEUTILIZARLOSKITSDEDISTRIBUCINDETUBERASINDICADOSENCADACOMBINACIN
>\ -ONOFSICA) 6(Z

-4RIFSICA))) 6(Z

>{\%LMODELO&$4#NOESCOMBINABLECONOTROSMODELOS,OSMODELO32+3PLITPAREDNOSONCOMPATIBLESCONOTROSMODELOS YSLOPODRNCOMBINARSE

UNIDADESCONLASMISMAPOTENCIA
>x\0ARACOMBINACIONESCON3PLITCONDUCTOSALTAPRESIN MODELO&$5 CONSULTECONELFABRICANTE
>\$EPENDIENDODELADISTANCIAENTREELPRIMERDISTRIBUIDORYLASMQUINAS IRAUNOUOTRODISTRIBUIDORVERPG  

UBSJGBAIRE

ACONDICIONADO



.VMUJ7*OWFSUFS

&$#6.

@em\ik\i

&$#63

&$#  6.3


)  ))) 

&$#63

5NIDADESEXTERIORES

3ERIES&$#3ISTEMA-ULTI 6)NVERTER"OMBADECALOR
'%$7/'%$7/4

1` i

) 6(Z
7


 


>

>>V`>`

i`>`?>`i>>i

) 6(Z))) 6(Z))) 6(Z


   

  

   

    

    

  

  

   

  

    

    

        

  

 

 

 

 

 

 

 

 

 

 

 

 

  

  

  

 

 

 

  

  

  



 







}









X

v

v

v


 

 

 

}``ii>

iVLi>V>}>
}`ii>
v}wV>V>








}`ii>
v}wV>iV`>>

6i>`V>`>`
 i>`i`

*}>`>

i>`i>

`i`iiViiVViI

,iv}i>i

}
*iV>}>`iiv}i>i

XX



 



>`>`ii



XX XX





X

v
 




v

X  4
2!



I/\V>Li`ii>

>\3ILALONGITUDDELATUBERAPRINCIPALEXCEDEDEM ENTONCESDETUBERADELQUIDOvENLUGARDEv

   

        

XX

*i

>}>>`V>`iiv}i>i


   

ii>>Vv`

>}>>`V>`iiv}i>i

 '%$74

` 

iiV`>`L>>

'%$74

>\3ILALONGITUDDELATUBERAPRINCIPALEXCEDEDEM ENTONCESvYAPORTAGRMDECARGAADICIONAL

3ILATUBERAPRINCIPALESMENORDEM ENTONCESvYAPORTARSLOGRMDECARGAADICIONAL

>\3ILATUBERAPRINCIPALESMENORDEMENTONCESDETUBERADEGASDEvENLUGARDEv

UBSJGBAIRE

ACONDICIONADO



 





*iV>}>`iiv}i>i

    

V>   


i`>`>

>

/Li>`i
iv}i>i

     

V>   


7

ijVV 
>

>

'%$7/4'%$7/4

i>VijVV>`i>`>` i

.VMUJ7*OWFSUFS
3PLITTECHO
1`i

i>VijVV>


 

>>V`>`

>

>

iiV`>`L>>

&$%.

V>

*i

>`>`ii
 i>`i`

&$%.

&$%.

&$%.

) 6(Z





 

 



 











 

 

 

 

 

 





















XX

XX

}









*}>`>

i>`i>

&$%.



` 

ii>>Vv`

/Li>`iiv}i>i

&$%.

V>
7


>

XX



v

v



v

v

3PLITCASSETTEVAS
1`i

i>VijVV>

7
>

 

>>V`>`

iiV`>`L>>

1`>`

ii>>Vv`

/Li>`iiv}i>i

&$4

&$4





 

 



 













 

 

 

 













` 







}

*}>`>



XX

XX



v









v

v





 




i>`i>



XX


 i>`i`

&$4

) 6(Z

 

&$4



*>i

>`>`ii

&$4

V>

*>i
1`>`

*i

&$4

V>
7

>


>

v

3PLITCASSETTEVASXMM
1`i

i>VijVV>

 

>>V`>`

>


>

>

iiV`>`L>>
ii>>Vv`

1`>`

&$4#



V>





 

 

V>





` 



XX

XX



 

*>i
1`>`

*i

&$4#
) 6(Z

}

*>i

>`>`ii

/Li>`iiv}i>i  i>`i`

*}>`>

 

i>`i>

v

v

3PLITCONDUCTOS
1`i

i>VijVV>

 

>

>>V`>`


>


#ONSULTARSIEMPRE

LATUBERADELQUIDODE

ii>>Vv`

FABRICANTE%NELCASODE

*i

DELAUNIDADINTERIORFUERA

>`>`ii

DEvSERANECESARIO
HACERUNAREDUCCINDE

*ii?V>1`i

LALLAVEDESERVICIODELA
UNIDADINTERIOR

 ?`>
?>

vAvJUSTOANTESDE

/Li>`iiv}i>i

&$5-

&$5-

) 6(Z

V>

i>`i`
i>`i>

}

&$5-



 

 



 









 

 



 



















XXXX












*>
V>





 



v

v

v


XX

*}>`>



v

>\0ARACOMBINACIONESCON3PLITCONDUCTOSALTAPRESIN MODELO&$5 CONSULTECONELFABRICANTE

UBSJGBAIRE

ACONDICIONADO



&$5-



`  

iiV`>`L>>

LAUNIDADINTERIORCONEL
QUELATUBERADELQUIDO

&$5-

V>
7

>



 

.VMUJ7*OWFSUFS

@em\ik\i

3PLITPARED
1`i

i>VijVV>

>

 

>>V`>`

>

iiV`>`L>>
ii>>Vv`

1`>`

*i

1`>`

>`>`ii
/Li>`iiv}i>i

 i>`i`

32+:)8

32+:(8
) 6(Z



V>






>



 

V>





` 



XX

}



 

*}>`>

i>`i>

 

v
v

>\,OSMODELOS32+SPLITPAREDNOSONCOMBINABLESCONOTROSMODELOS YSLOPODRNCOMBINARSEUNIDADESCONLAMISMAPOTENCIA

5NIDADESEXTERIORES

+IT$ISTRIBUCINDE4UBERAS
0RECIOSYCAPACIDADES

0RECIOSYCAPACIDADES

`i
>>V`>`V>*6,


>


6

x]


6

nx]

`i

-7
-/
-7
-/


6-

{]


x6

n]


x6-

{6

n
x

x
n

n]
]


{6-

x]


6-

xx]


x6-

xx]

*6,
x]
x]
x]
]

5NIDADESINTERIORES

`i

>>V`>`V>


*6,

>

{x

 {
 x


{x
{

{nx

xn

]

nn

]

{]

 x

nx

xx]

3PLITCASSETTEVAS

n]
x]

0RECIOSYCAPACIDADES

`i

>>V`>`V>

*6,

>

 /{
 /x

{x
{

{x

]
x]

 /

{nx

xn

x]

 /
 /

x]

 /x

n
x

x
x

xx]
]

0RECIOSYCAPACIDADES

3PLITCASSETTEVASXMM

`i

 /
{
 /
x

>>V`>`V>


*6,

>

{x

nn]

{x

x]

3PLITCONDUCTOS

0RECIOSYCAPACIDADES

`i

 1x
 1
 1

{
{nx

 1
 1x

n
x

>>V`>`V>


*6,

>

{x

n{]

xx
nn

n]
{x]

x
x

x]
{x]

0RECIOSYCAPACIDADES

3PLITPARED

`i

-,x<8
-,<8

>>V`>`V>


{
x

*6,

>

x
xnx

x]
nx]

UBSJGBAIRE

ACONDICIONADO





0RECIOSYCAPACIDADES

3PLITTECHO

.VMUJ7*OWFSUFS
,MITESDEDISTANCIADETUBERADEREFRIGERANTE
#OMBINACIN&$#   

Q,MITESDEDISTANCIADETUBERA

>LrMTSOMENOS
>qLrMTSOMENOS

>rMTSOMENOS

LrMTSOMENOS
rMTSMXIMOSIUD%XTERIORPORENCIMADE
LASUDS)NTERIORES
rMTSMXIMOSIUD%XTERIORPORDEBAJODE
LASUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7!



Q #UANDO LA DIFERENCIA DE LA DISTANCIA ENTRE EL PRIMER


DISTRIBUIDORYLASUNIDADESINTERIORESESMENORDEM

#OMBINACIN&$#

>LVrMTSOMENOS

>qLrMTSOMENOS


>qVrMTSOMENOS


LqVrMTSOMENOS


>rMTSOMENOS


LrMTSOMENOS
VrMTSOMENOS
rMTSMXIMOSIUD%XTERIORPORENCIMADE
LASUDS)NTERIORES
rMTSMXIMOSIUD%XTERIORPORDEBAJODE
LASUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 4!

Q #UANDO LA DIFERENCIA DE LA DISTANCIA ENTRE EL PRIMER


DISTRIBUIDORYLASUNIDADESINTERIORESESDEMOMAYOR
>LVrMTSOMENOS
>qLrDESDEMAM

>qVrDESDEMAM

NLqVNrMOMENOS


>rMOMENOS


LrMOMENOS
VrMOMENOS
rMOMENOS
rMCUANDOLAUNIDADEXTERIORESTMSALTA
QUELASUNIDADESINTERIORES
rMCUANDOLAUNIDADEXTERIORESTMSBAJA
QUELASUNIDADESINTERIORES
rMTSMXIMOENTREUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
rMTSMXIMOENTREUDS)NTERIORES
.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7!X

UBSJGBAIRE

ACONDICIONADO



#OMBINACIN&$#





.VMUJ7*OWFSUFS

@em\ik\i

#OMBINACIN&$# 

Q,MITESDEDISTANCIADETUBERA
>rMTSOMENOS rMTSMXIMOSIUD%XTERIORPORENCIMA
LrMTSOMENOS DELASUDS)NTERIORES
>qLrMTSOMENOS rMTSMXIMOSIUD%XTERIORPORDEBAJO



>rMTSOMENOS

DELASUDS)NTERIORES
LrMTSOMENOS
rMTSMXIMOENTREUDS)NTERIORES

.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7"

Q #UANDO LA DIFERENCIA DE LA DISTANCIA ENTRE EL PRIMER


DISTRIBUIDORYLASUNIDADESINTERIORESESMENORDEM
>rMOMENOS
LrMOMENOS
VrMOMENOS
N>qLNrMENOSDEM
N>qVNrMENOSDEM
NLqVNrMENOSDEM
>rMOMENOS
LrMOMENOS
VrMOMENOS

#OMBINACIN&$#

(MCUANDOLAUDEXTERIORESTMSALTA
QUELASUDSINTERIORES
(MCUANDOLAUDEXTERIORESTMSBAJA
QUELASUDSINTERIORES
H MMXIMOENTREUNIDADESINTERIORES
H MMXIMOENTREUNIDADESINTERIORES
H MMXIMOENTREUNIDADESINTERIORES

.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 4"

Q #UANDO LA DIFERENCIA DE LA DISTANCIA ENTRE EL PRIMER


DISTRIBUIDORYLASUNIDADESINTERIORESESDEMOMAYOR
(MCUANDOLAUDEXTERIORESTMS
ALTA
QUELASUDSINTERIORES
(MCUANDOLAUDEXTERIORESTMS
BAJA
QUELASUDSINTERIORES
H MMXIMOENTREUNIDADESINTERIO
RES
H MMXIMOENTREUNIDADESINTERIO



>rMOMENOS
LrMOMENOS
VrMOMENOS
>qLrDESDEMAM
>qVrDESDEMAM
NLqVNrMOMENOS
>rMOMENOS
LrMOMENOS
VrMOMENOS
rMOMENOS

#OMBINACIN&$#

.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7" $)3 7!

Q #UANDO LA DIFERENCIA DE LA DISTANCIA ENTRE EL PRIMER


DISTRIBUIDORYLASUNIDADESINTERIORESESMENORDEM
, LAMOMENOS
, , LBMOMENOS
, , LCMOMENOS
LAn, LB MENOSDEM
LAn, LC MENOSDEM
\LBnLC\MENOSDEM
LAMOMENOS
, LBMOMENOS
, LCMOMENOS
,MOMENOS

#OMBINACIN&$#

(MCUANDOLAUDEXTERIORESTMS
ALTAQUELASUDSINTERIORES
(MCUANDOLAUDEXTERIORESTMS
BAJAQUELASUDSINTERIORES
H MMXIMOENTREUNIDADESINTERIORES
H MMXIMOENTREUNIDADESINTERIORES
H MMXIMOENTREUNIDADESINTERIORES

.OTA,ADIFERENCIADELADISTANCIAENTRELASUNIDADESINTERIORESALPRIMERDISTRIBUIDOR SLOPUEDESERINFERIORAM
3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7" $)3 7!

#OMBINACIN&$# 

Q,MITESDEDISTANCIADETUBERA
>rMTSOMENOS
LrMTSOMENOS
VrMTSOMENOS
`rMTSOMENOS
>qLrMTSOMENOS
>qVrMTSOMENOS
LqVrMTSOMENOS
>q`rMTSOMENOS
Lq`rMTSOMENOS

rMTSMXIMOSIUD%XTERIORPORENCIMA


DELASUDS)NTERIORES


rMTSMXIMOSIUD%XTERIORPORDEBAJO


DELASUDS)NTERIORES


rMTSMXIMOENTREUDS)NTERIORES




rMTSMXIMOENTREUDS)NTERIORES




rMTSMXIMOENTREUDS)NTERIORES



{rMTSMXIMOENTREUDS)NTERIORES


xrMTSMXIMOENTREUDS)NTERIORES

Vq`rMTSOMENOS
>rMTSOMENOS


LrMTSOMENOS


VrMTSOMENOS


`rMTSOMENOS


 rMTSOMENOS

rMTSOMENOS


.OTA3ERECOMIENDAUTILIZARELDISTRIBUIDOR$)3 7!XO$)3 7"X

UBSJGBAIRE

ACONDICIONADO



3/2/SP/4

Rejas de Intemperie
Series WG AWG WGE AWK WG-F

Contenido Descripcin
Descripcin
Ejecuciones
Detalles de montaje
Tamaos suministrables Taladros de las bridas
Programa de suministro
Datos tcnicos
Informacin para pedidos

2
3
5
7
8
9
10

WG AWG WGE

Las rejas de intemperie ofrecen una excelente proteccin


contra la lluvia y frente a la entrada de hojas de rbol y de
pjaros en las aberturas de extraccin y aspiracin en las
instalaciones de ventilacin. Por limitaciones fsicas no se
puede evitar que, bajo la accin de diversos factores, penetren pequeas cantidades de agua. Puede evitarse practicamente la entrada de agua montando posteriormente separadores de gotas.

AWK

WG-F

Ejecuciones
Series WG AWG WGE AWK
WG
Marco y lamas de chapa perfilada de acero galvanizado
Tela metlica de acero galvanizado,
con malla de 20 x 20 mm
Marco frontal taladrado

WGE
Marco, lamas y tela metlica (malla de 20 x 20 mm)
de acero inoxidable, n de material 1.4301
Marco frontal taladrado
AWK
Marco y lamas en perfiles de aluminio extrudo anodizado
en color natural (E6-C-0)
Tela metlica de acero galvanizado,
con malla de 6 x 6 mm
Marco frontal taladrado

AWG
Marco y lamas en perfiles de aluminio extrudo
Tela metlica de acero galvanizado,
con malla de 20 x 20 mm
Marco frontal taladrado

Series WG AWG WGE

AWG

50

50

WG
WGE

82,5

82,5

83

95

superficie libre 60 % aprox.


referida a B x (H - 0,085 m)

28

Serie AWK

Marco
Lama
Lama de cierre
Tela metlica

25

34

superficie libre 60 % aprox.


referida a B x (H - 0,028 m)

Ejecuciones
Serie WG-F
WG-F (ejecucin en acero)
Lamas y soportes de chapa perfilada de acero galvanizado; van pintados adems por el procedimiento de
electroinmersin en color negro (RAL 9005)
Los soportes estn taladrados lateralmente y por su parte
posterior para la unin de una reja con la inferior o bien
para su sujecin a la infraestructura
Tela metlica de acero galvanizado,
con malla de 20 x 20 mm

WG-F (ejecucin en aluminio)


Lamas de perfiles de aluminiu extrudo
Los soportes son de chapa perfilada de acero galvanizado; van pintados adems por el procedimiento de
electroinmersin en color negro (RAL 9005)
Los soportes estn taladrados lateralmente y por su parte
posterior para la unin de una reja con la inferior o bien
para su sujecin a la infraestructura
Tela metlica de acero galvanizado,
con malla de 20 x 20 mm

Serie WG-F
Pieza
de esquina

600

Pieza
parcial

150

4.1

125

37

630

120

180

nxB

n = cualquier nmero de piezas parciales


superficie libre 50 % aprox. referida a B x (H - 0,125 m)

Pieza de esquina

60

20

4.2

630

4.1

630

Dimensin = 600 x H

4.1

4.2

Lama
Lama de cierre
Tela metlica
Soporte a derechas
Soporte a izquierdas

4.2 se suministran como piezas individuales.


Las piezas a
Los elementos de sujecin estn incluidos en el alcance de
suministro.

Detalles de montaje
Marco de montaje

t2

Serie AWK
Marco de montaje nicamente para B 1197 mm y H 497 mm;
para otras combinaciones de dimensiones, se encuentran
disponibles marcos de montaje especiales bajo demanda.

35

Series WG AWG WGE

Anclaje
a la pared

t2

t2

H + 15

t2

Estado de
suministro

35

B + 15
t1

t1

35

Montaje

122,5

Medida de separacin t = Distancia entre taladros en la brida (pagina 7)


Material:
Anclaje
Series WG AWG: acero galvanizado
a la pared
Serie WGE:
acero inoxidable
Material: Chapa perfilada de acero galvanizado

Dimensiones de montaje
Serie AWK

83

28

95

abertura de montaje sin marco


de montaje B + 15 / H + 15

25

H/B

H + 26 / B + 26

H + 28 / B + 28

82,5

H/B

H + 15 / B + 15

H + 35 / B + 35

H/B

82,5

H + 15 / B + 15

H + 35 / B + 35

50

Serie AWG

50

Series WG
WGE

34

abertura de montaje sin marco


de montaje B + 15 / H + 15

abertura de montaje sin marco


de montaje B + 10 / H + 10

Serie WG-F
X

630

450

Infraestructura, por ejemplo perfil en ngulo (si es necesario)

Infraestructura, por ejemplo perfil en U (si es necesario)

x = (n x B) + 450
630

Detalles de montaje
Series WG AWG WGE (dimensin B o H dividida)
Si la dimensin B es mayor que 1985 mm o H mayor que
1980, se pueden colocar dos tomas de aire exterior yuxtapuestas o superpuestas, respectivamente. El montaje se
puede realizar con o sin marco de montaje.

Serie AWG (ejecucin en forma alargada)


Las rejas de intemperie de la serie AWG se pueden suministrar en ejecucin en forma alargada en caso de que la
dimension B sea mayor que 1985 mm. La anchura de la
pletina de separacin es de 2 x 20 mm.
Las rejas de intemperie en ejecucin alargada con una
anchura B > 1985-3985 mm constan de 2 piezas finales.
Las rejas de intemperie en ejecucin alargada con una
anchura B > 3985 mm constan de 2 piezas finales y un
nmero cualquiera de piezas intermedias.
El montaje se puede efectuar con o sin marco de montaje.

Series WG AWG WGE

Serie AWG

Dimensin B dividida (B1 = 2 B + 100)

40

100
B1

40
M

Dimensin H dividida (H1 = 2 H + 100)

E = Pieza final
= 1092-1992 mm en saltos de 100
M = Pieza intermedia = 2000 mm

100
H1

Detalle A

Pletina de separacin

40

Marco de montaje especial


representado con la dimensin B dividida

Marco de montaje especial


B + 35/H + 35
B + 15/H + 15

Abertura de montaje sin marco de montaje


B1 + 15 / H + 15 o H1 + 15 / B + 15

135

B1 + 35/H + 35 o H1 + 35/B + 35
B1 + 15/H + 15 o H1 + 15/B + 15

Abertura de montaje sin marco de montaje B + 15 / H + 15

Tamaos suministrables Taladros de las bridas

~9

t1

t1

E
130

t4

H
11,5

27,5

27,5

130

8,5
80

t2
45,5

t2
t3
27,5

4,5

H
t2
t3
27,5

t2

t2

20

28

t2

~9

Serie AWK

50

50

Serie AWG (ejecucin en


forma alargada)
t3

t3

Series WG AWG WGE

B
t1

t4

20

45,5

t1

11,5

20

100

600

27,5

~9

600

600
M = 2000

Series WG AWG WGE


B

en mm en mm
385
585
785
985
1185
1385
1585
1785
1985

Nmero de taladros

330
495
660
825
990
1155
1320
1485
1650
1815
1980

en mm en mm
1000
1200
1400
1600
1800
2000

1000
1125
1250

2500

t1

t2

t3

B
en mm

ca. lado ca. lado


B
H
en mm en mm en mm
2
2
2
3
3
3
4
4
4

1
1
1
1
2
2
2
2
3

Serie WG-F
B

Serie AWK

Pieza esquina a 90
en mm
600/600

225
425
625
413
513
613
475
542
608

445
500
555
610
499

9997-9247

330
413
495
578
437
492
547
602
491

9297-9397
9447-9497
9597-9797
9897-1297
1397-1697
1797-1997

Nmero de taladros
cada lado B

en saltos
de 50
en saltos
de 100

1
2
3
3
4
5
6

H
Nmero de taladros
en mm
cada lado H
en saltos
9997-9497

de 50
9597-9797
3
9897-1297 en saltos
4
de 100
1397-1697
5
1797-1997
6

Series WG AWG WGE

Serie AWG

(dimensiones B o H divididas)

(ejecucin en forma alargada)

B1

H1

en mm en mm en mm en mm
2070
2470
2870
3270
3670
4070

330
495
660
825
990
1155
1320
1485
1650
1815
1980

2080
2410
2740
3070
3400
3730
4060

385
585
785
985
1185
1385
1585
1785
1985

El nmero de taladros y las divisiones de


acuerdo con las tomas de aire individuales

B
en mm
2185

en saltos
de 200

t1
en mm
colocados
en el centro
262-362
206-231
281-381
287-421
341-416
352-392

en mm en mm
1197
1297
1397
1497
1597
1697
1897
1997

t2
en mm

1997
1597
1497
1397
1297
1197
1097
997

281-381
287-421
341-416
352-392

en mm en mm
330
495
660
825
990
1155
1320
1485
1650
1815
1980

Dimensiones
mximas
combinables

1092
1192
1292
1392
1492
1592
1692
1792
1892
1992

Nmero de taladros

t4

cada lado E

en mm

3
3
3
4
4
4
4
4
4
4

456
506
556
404
437
471
504
537
571
604

El nmero de taladros y las divisiones en cada lado H de acuerdo


con la serie AWG

Series WG AWG WGE WG-F: las dimensiones B, B1 y H, H1 son combinables de cualquier forma

Programa de suministro

Serie

Ejecucin

Marco
de
montaje

Superficie
P1
S2/S3
Pintada

WG 2)

Ejecucin bsica

11

WG 1 2)

WG con rejilla antiinsectos de acero galvanizado

11

Ejecucin bsica con la dimensin B dividida

12

WG-BM con rejilla antiinsectos de acero galvanizado

12

WG-HM

Ejecucin bsica con la dimensin H dividida

13

WG 1-HM

WG-HM con rejilla antiinsectos de acero galvanizado

13

AWG 2)

Ejecucin bsica

11

AWG 1 2)

AWG con rejilla antiinsectos de acero galvanizado

11

AWG 2 2)

AWG pero con tela metlica de acero inoxidable 1.4301

11

AWG 3 2)

AWG con rejilla antiinsectos de acero inoxidable 1.4301

11

AWG-BM

Ejecucin bsica con la dimensin B dividida

12

AWG 1-BM

AWG-BM con rejilla antiinsectos de acero galvanizado

12

AWG 2-BM

AWG-BM con tela metlica de acero inoxidable 1.4301

12

AWG 3-BM

AWG-BM con tela metlica y rejilla antiinsectos de acero inoxidable 1.4301

12

Ejecucin bsica con la dimensin H dividida

13

AWG 1-HM

AWG-HM con rejilla antiinsectos de acero galvanizado

13

AWG 2-HM

AWG-HM con rejilla de alambre ondulado de acero inoxidable 1.4301

13

AWG 3-HM

AWG-HM con rejilla de tela metlica y rejilla antiinsectos de acero inoxidable 1.4301

13

AWG-B

Ejecucin alargada

14

AWG 1-B

AWG-B con rejilla antiinsectos de acero galvanizado

14

AWG 2-B

AWG-B con tela metlica de acero inoxidable 1.4301

14

AWG 3-B

AWG-B con tela metlica y rejilla antiinsectos de acero inoxidable 1.4301

14

WGE

Ejecucin bsica

15

WGE 1

WGE con rejilla antiinsectos de acero inoxidable 1.4301

15

Ejecucin bsica con la dimensin B dividida

16

WGE-BM con rejilla antiinsectos de acero inoxidable 1.4301

16

WGE-HM

Ejecucin bsica con la dimensin H dividida

17

WGE 1-HM

WGE-HM con rejilla antiinsectos de acero inoxidable 1.4301

17

WG-BM
WG 1-BM

AWG-HM

WGE-BM
WGE 1-BM

Ejecucin
en acero

Ejecucin
en aluminio

Ejecucin
en acero
inoxidable

AWK

Ejecucin
en aluminio

Ejecucin bsica

WG-F-E

Ejecucin
en acero

Ejecucin bsica de pieza de esquina

1)

Ejecucin bsica de pieza intermedia

1)

WG-F-E-AL

Ejecucin bsica de pieza de esquina

1)

WG-F-E-AL 2

WG-F-E-AL pero con tela metlica de acero inoxidable 1.4301

1)

WG-F-T

WG-F-T-AL

Ejecucin
en aluminio

WG-F-T-AL 2

3)

18 3)

WG-F-T-AL pero con tela metlica de acero inoxidable 1.4301

1) Los soportes solo en RAL 9005

E6-C-0

1)
1)

1)
1)
1) 1)
1) 1)

Ejecucin bsica de pieza de intermedia

anodizada

2) Las rejas de intemperie se pueden utilizar tambin en combinacin con compuertas


de regulacin y con compuertas de sobrepresin (ver folleto no 3/4/SP/..)

Si se desea, superficie:
P1 = Pintado segn la escala de colores RAL
(espesor de capa de unas 60-80 m)
Consultar precios

S2/S3 = anodizada segn Euras-Standard


(espesor de capa de unas 20 m)
Ejecucin: superficie decapada (E6)

3) Marco de montaje nicamente para B 1197 mm y H 497 mm;


para otras combinaciones de dimensiones, se encuentran
disponibles marcos de montaje especiales bajo demanda.

Colores: C- 0 = color natural


C-31 = bronce ligero
C-32 = bronce claro
S2 = por ejemplo E6-C-33
S3 = E6-C-0

C-33 bronce mediano


C-34 bronce oscuro
C-35 negro

Datos tcnicos
Definiciones

Ejemplo

v
A

Dados:

en m/s: Velocidad del flujo de aire en dB(A)


en m2: Seccin paso de aire
WG WGE AWG: B x (H 0,085 m)
AWK:
B x (H 0,028 m)
WG-F:
B x (H 0,125 m)
(B y H medidas en m)
 pt
en Pa: Prdida total de carga
LW = LWO + K en dB/oct.: Nivel de potencia sonora por banda de
frecuencia en db(A)
en dB/oct.: Como el anterior, pero referido a A = 1,0 m2
LWO
LWA = LWAO + K en dB(A): Nivel de potencia sonora referido
a A en dB(A)
en dB(A): Como el anterior, pero referido a A = 1,0 m2
LWAO
LW NC = LW NCO + K
: Curva lmite del espectro de potencia sonora
referido a A
: Como el anterior, pero referido a A = 1,0 m2
LW NCO
K
: Correccin del nivel de potencia sonora por
banda de frecuencia en dB(A). Correccin
de la curva lmite del espectro de potencia
sonora para secciones de paso de aire mayores o menores a 1,0 m2
f
en Hz: Frecuencia media por banda de octava

en Hz

44

Serie

Serie WG-F

A+B
Tipo de montaje: D C

200

65

70

150

60

500

1000

250

29 26 29 27 18

45 44 42 40 37 30 18 12 52 48 45 48 46 37 25 13

54 55 54 51 50 43 35 20 63 62 57 57 59 54 44 31

59 63 62 60 58 56 48 36 70 70 66 63 66 64 56 43

63 72 73 72 69 68 61 53 75 81 80 75 75 77 72 62

26 23 22 19 11

41 43 44 44 39 31 22 10 51 48 45 48 46 37 25 13

50 52 54 54 54 47 40 30 63 62 57 57 59 54 44 31

55 59 62 62 62 57 49 40 70 70 66 63 66 64 56 43

63 68 70 72 72 72 65 60 75 81 80 75 75 77 72 62

26 23 22 19 11

45 44 41 40 37 29 18 11 50 46 43 46 44 35 23 11

54 55 54 51 50 43 35 20 60 59 54 54 56 52 41 28

59 63 62 60 58 56 48 36 67 68 64 61 64 62 53 41

63 72 73 72 69 68 61 53 73 79 77 73 72 75 69 60

26 23 22 19 11

41 43 44 44 39 31 22 10 50 53 53 53 49 41 31 19

50 52 54 54 54 47 40 30 59 62 63 64 63 57 49 37

55 59 62 62 62 57 49 40 65 68 70 71 71 67 59 49

63 68 70 72 72 72 65 60 72 77 80 81 82 81 75 67

125

26 23 22 19 11

f = 63

500

1000

125

29 26 29 27 18

27 24 27 25 16

35 35 35 31 23 14

10

+1

+2

+3

+5

+6

60
55

Tipos de montaje
55

50

Montaje
en plenum

50

Montaje en conducto

40

45
L

W
AO

en

30

HxB

45

5
dB 0
(A
)

NC
O

40

20

 pt

15
1,5

m/s
v

 pt

40

 pt

Nivel de potencia sonora (LWO en dB/oct., NO = 1012 W)

A en m2 0,10 0,12 0,25 0,30 0,40 0,50 0,60 1,00 1,25 1,60 2,00 3,00 4,00
K

Pa

WG-F

Valores de correccin para el nivel de potencia sonora

65

100

LW NC

24

8000

34

4000

m/s

41

2000

15
2

48

8000

40

20

1,5

48

4000

W
AO

40

45

en

30

48

2000

55

50

50
dB
(A
)

NC
O
W

45

 pt

40

v
en
m/s

f = 63

65

70

Tipo de
montaje

A
50

46

WG WGE
AWG AWK

65

55

Pa

LW

LW NC 52 6 = 46

60

60

100

LWA

63 125 250 500 1000 2000 4000 8000

LW en dB/oct.

A+C
150

 pt

Espectros de potencia sonora

Tipo de montaje: B + D

200

Se pide: Prdida total de carga


Nivel de potencia sonora valorado en dB(A)
Nivel de potencia sonora por banda
de octava del ruido del flujo de aire
Curva lmite del espectro de potencia
sonora
Resultado:
 pt = 50 Pa (del diagrama)
LWA = 55 6 = 49 dB(A)

250

Series WG WGE AWG AWK

Reja de Intemperie de la serie WG, tipo de


montaje B,
B = 585 mm, H = 495 mm, A 0,24 m2
v = 3 m/s

6
Todos los datos tcnicos se refieren a la ejecucin bsica.

Informacin para pedidos

Cdigo de pedido

sin datos para la ejecucines bsicas

AWG

585 x 1155

11

S2

E 6 - C - 31

TE RAL . . .
EE
ZE o E 6 - C - . .
EE (ver pgina 8)
U

Denominacin de la serie
(ver pgina 8)

Reservado el derecho de modificaciones Todos los derechos reservados Gebr. Trox GmbH (10/2000)

Tamaos suministrables
B x H en mm
B1 x H en mm
B x H1 en mm
600 x H en mm
(ver pgina 7)

TE
EE
EE
EE
ZE
EE
EE
EE
U

P1 = Pintado segn RAL . . .


S2 = Anodizado segn Euras-Estndar
E 6 - C - 31 hasta C - 35
S3 = Anodizado segn Euras-Estndar
E6-C-0
(ver pgina 8)

sin variantes
Marco de montaje (ver pgina 8)
0 = sin marco de montaje

Especificacin

Ejemplo de pedido

Rejas de intemperie para proteccin contra la lluvia y la


entrada de hojas de arboles y de pjaros en las aberturas de
extraccin y aspiracin en las instalaciones de ventilacin.
Esencialmente estn formadas por un marco, en el que se
montan las lamas para proteger contra la lluvia, y de una tela
metlica situada en la parte posterior.

Fabricante: TROX
Tipo:
AWG / 585 x 1155 / 11 / 0 / S2 / E6 - C - 31
Cantidad: 4

Ejecuciones y material:
Los datos correspondientes estn en las pginas 3 y 4
Marco de montaje y variantes de ejecucion,
por ejemplo ejecucin en forma alargada, superficie anodizada:
Los datos referentes a esto estn en la pgina 8
Fabricante: TROX
Serie:

10

Los datos correspondientes estn en la pgina 8

1/1/SP/5

Rejillas
Rejillas continuas

Contenido Descripcin

Descripcin
Rejillas de aluminio
Rejillas y parrillas de aluminio
Rejillas de aluminio
Rejillas de acero
Rejillas de acero inoxidable
Partes posteriores para regulacin de caudal
Rejillas de plstico
Marco de montaje con manta filtrante
Rejillas y parrillas (Dimensiones)
Rejillas continuas de aluminio y acero

2
3
4
5
6
7
7
8
9
10
11

Las rejillas y las rejillas continuas son adecuadas para el


montaje en conductos, paredes y suelos. Este montaje se
puede realizar directamente en el conducto o bien mediante
un marco de montaje, por ejemplo en un muro.
Para optimar la distribucin del aire pueden elegirse diferentes tipos de accesorios: ver pginas 14 y 15.

Tablas de seleccin de rejillas continuas


Partes posteriores
Marcos de montaje
Construccin Montaje
Definiciones
Datos acsticos
Datos acsticos para impulsin
Datos acsticos para el retorno
Datos aerodinmicos
Datos aerodinmicos para el retorno
Informacin para pedidos

12
14
16
18
19
19
20
22
24
31
32

Rejillas de aluminio
Ejecuciones Dimensiones Material
Ejecuciones
Serie ASL
Rejillas para impulsin y retorno. El marco frontal con diseo
de forma aerodinmica favorece la difusin, con lamas horizontales regulables individualmente y sujecin mediante
fijacin oculta. Bajo demanda, tambin se puede suministrar
con sujecin por muelle.
Serie AT
Rejillas para retorno y extraccin. El marco frontal se puede
elegir con anchura de 27 23 mm, con lamas horizontales
regulables individualmente y sujecin mediante fijacin
oculta. Bajo demanda se puede suministrar con sujecin
por muelle con tornillos vistos (taladros avellanados).

Serie VAT
Rejillas para impulsin y retorno. El marco frontal se puede
elegir con anchura de 27 23 mm, con lamas verticales
regulables individualmente y con sujecin mediante fijacin
oculta. Bajo demanda se puede suministrar con sujecin
por muelle con tornillos vistos (taladros avellanados en
marcos de 27 mm de anchura).

Material
Las rejillas son de perfil de aluminio extrudo con acabado
anodizado en color natural, E6 - C - 0.

38

16
28

16,7

H + 29 / L + 29

H/L

Serie ASL

17

11

Serie AT
23*

* para
dimensin ( )

11
38

17
27

16,7

H + 27(19) / L + 27(19)

H/L

38

11

Serie VAT

23*

* para
dimensin ( )

11
38

17
27

H + 27(19) / L + 27(19)

H/L

38

11

Separacin
de lamas
16,7 mm

Rejillas y parrillas de aluminio


Ejecuciones Dimensiones
Serie AH
Rejillas para impulsin y retorno. El marco frontal se puede
elegir con anchura de 28 20 mm, con lamas horizontales
fijas y sujecin mediante fijacin oculta. La salida del aire
puede ser tanto perpendicular a la rejilla 0 tipo AH - 0 -
como con una inclinacin de 15 tipo AH -15 - . Bajo
demanda se puede suministrar con sujecin por muelle o
con tornillos vistos (taladros avellanados).

Serie EH EF EHG EFG


Rejillas para impulsin y retorno, para montaje en paredes
y antepechos, con lamas horizontales fijas y con una separacin de 12,5 mm tipos EH- 0, EH -15, EF - 0 y EF -15
16,7 mm tipos EHG - 0, EHG -15, EFG - 0 y EFG -15 .
La salida del aire puede ser perpendicular a la rejilla de
0-tipos . . . 0 o con una inclinacin de 15-tipos. La construccin y las dimensiones son iguales a las de las series
AH AF.

Serie AF
Rejillas para impulsin y retorno para montaje en suelos y
paredes, con marco frontal y lamas horizontales fijas. La
salida del aire puede ser tanto perpendicular a la rejilla 0
tipo AF - 0 -. . . como con una inclinacin de 15 tipo
AF -15-. . . . La parte posterior se puede sujetar por medio
de un muelle. El montaje en muro se puede realizar
mediante una pata de anclaje.

* para dimensin ( )

Serie AH

18
5,5

20*

H + 29(13) / L + 29(13)

7
34
18

5,5

28

H/L

12,5
H/L

H + 29(13) / L + 29(13)

34

AH - 0

AH -15

Serie AF
H + 32 / L + 32
12,5
5,5

18

53

AF - 0

5,5

18

5,5

21

H/L

H + 32 / L + 32
12,5
26
H/L

AF - 15
Serie EH EF EHG EFG

10,5

Ha / La

10,5

. . . - 15

5,5

18

18

... -0
Ha / La
t

5,5

Rejillas de aluminio
Ejecuciones Dimensiones
Serie AWT
Rejilla de pared resistente a impactos de balones, para el
montaje en polideportivos (a prueba de balones segn
DIN 18 032 parte 3).
Rejillas para impulsin y retorno especialmente robustas
formadas por un marco frontal con lamas horizontales fijas y
sujecin mediante tornillos vistos (taladros avellanados).

Serie AGS
Rejillas para impulsin y retorno, con marco frontal y lamas
horizontales fijas en forma de V para sujecin mediante tornillos vistos (taladros avellanados). Las rejillas AGS pueden
suministrarse con contramarcos para montaje en puertas
tipo AGS -T as mismo la reja AGS - L pueden suministrarse
con contramarcos para montaje en puertas tipo AGS -TL
(ver pgina 18).
Los tipos AGS-L y AGS-TL van totalmente pintados en
negro para evitar los reflejos de la luz.

30

52
H+5
H + 27/ L + 27

H/L

16,7

Serie AWT

25
7

Serie AGS

30

22

6
H + 10
H + 34 / L + 28

H/L

20

36

32

Rejillas de acero
Ejecuciones Dimensiones Material
Ejecuciones

Material

Serie SL
Rejillas para impulsin y retorno. El marco frontal est
diseado de forma aerodinmica, que favorece la difusin
(perfil en L de 28 mm de anchura, perfil en H de 20 mm de
anchura), con lamas horizontales regulables individualmente y sujecin mediante fijacin oculta.

Series SL TR TRS
La rejilla frontal es de chapa de acero perfilada. La superficie, una vez tratada, se pinta en color blanco (RAL 9010)
con pintura en polvo.

Serie TR
Rejillas para impulsin y retorno, formadas por un marco
frontal con lamas horizontales regulables individualmente
y sujecin mediante tornillos vistos (taladros avellanados).
Bajo demanda, se puede suministrar con fijacin oculta
y en ejecucin galvanizada.

Series TR galvanizada
La rejilla frontal es de chapa de acero perfilada galvanizada.

Serie TRS
Rejillas para impulsin y retorno, formadas por un marco
frontal con lamas verticales regulables individualmente
y sujecin mediante tornillos vistos (taladros avellanados).
Bajo demanda, se puede suministrar con fijacin oculta.

Serie SL

H + 29 / L + 11

Perfil en H

11

38
16

19
28

20

H/L

20

38

Perfil en L

11

38

27

H+5

H + 27/ L + 27

H / L*

20

Serie TR

19
11

38
27

H + 27/ L + 27

H+5

H / L*

Serie TRS

19

Separacin
de lamas
20 mm
* Sin marco de montaje
Agujero paso de aire L H = 14 mm
11

Rejillas de acero inoxidable Partes posteriores para regulacin de caudal


Ejecuciones Dimensiones Material
Ejecuciones

Material

Serie TRE
Rejillas para impulsin y retorno formadas por un marco
frontal con lamas horizontales regulables individualmente
y sujecin mediante tornillos vistos (taladros avellanados).

Serie TRE
La rejilla frontal es de chapa de acero inoxidable (n de
material 1.4301). El acabado de la superficie es mate.
Bajo demanda, se suministra con acabado superficial
brillante.

Tipo AGW
Partes para regulacin del caudal de aire, para montaje en
conductos con marco de ngulo, con lamas acopladas en
oposicin accionables desde la parte frontal. Los tamaos
suministrables son los mismos que los de la serie VAT,
(ver pgina 10). L max = 1225 mm.

Tipos AGW DGW


La parte posterior para la regulacin de caudal es de chapa
perfilada de acero. El acabado superficial es fosfatado,
pintada en color negro (RAL 9005) por el procedimiento
de electroinmersin y secada al horno.

Tipo DGW
Partes para regulacin de caudal de aire, para montaje en
conductos con marco angular, con lamas en oposicin
accionables desde la parte frontal y con lamas deflectoras
verticales regulables individualmente. Los tamaos suministrables son los mismos que los de la serie VAT, (ver
pgina 10). L max = 1225 mm.

Serie TRE

Parte del marco

Lamas frontales
horizontales

taladro  4,8 x 90
tornillo con cabeza de gota de sebo
para chapa  3,9 x 13 (en obra)

40

25

19

225

325

425

525

625

283,5

F
37

L 58

775*

358,5

H 14/L 9

F
en mm
H

L
en mm

H + 25

Separacin entre lamas 16,7 mm

L + 25

* L = 775 Lamas frontales subdivididas por travesaos!


L 15 /H 15

80

Tipos AGW DGW


17
L + 10 / H + 10

80

L 15 / H 15

17
L + 10 / H + 10

Rejillas de plstico
Ejecuciones Dimensiones Material
Ejecuciones

Material

Serie KS
La rejilla serie KS es indicada tanto para impulsin como
retorno. El marco frontal est realizado con taladros para
sujecin mediante tornillos vistos ( 4,5 mm) atornillado en
obra.

La rejilla frontal y las piezas posteriores son de perfil de


plstico (PVC duro), con excelente resistencia a la corrosin, con una resistencia a la temperatura de hasta 50 C.
Rejilla frontal en color gris oscuro (similar a RAL 7011),
y las lamas curvadas para la regulacin de caudal en color
negro gris oscuro.

Tipo KS-A

con lamas horizontales orientables individualmente.

Tipo KS - C como el tipo KS-A pero con lamas adicionales


curvadas verticales orientables individualmente
para la regulacin del caudal.

Lamas curvadas
verticales C

Lamas frontales
horizontales
6

Serie KS

48

24

10

Tipo KS-A

25

H + 25

4,5

48

L + 25

45
Separacin entre lamas 20 mm

10

Tipo KS-C
Lamas curvadas C

25

H + 25

5
4,

48

F
L + 25

3
45
Separacin entre lamas 20 mm

L
en mm

F
en mm

325

425

625

277

825

377

L = 625 lamas frontales subdivididas por travesaos!


L = 825 lamas frontales x 2 subdivididas por travesaos!

Marco de montaje con manta filtrante


Ejecuciones Dimensiones Material
Ejecuciones

Material

Tipo. . .- EF
Las ejecuciones bsicas . . .- A de las rejillas serie AT, VAT,
AH, SL, TR y TRS se utilizan montadas en paredes
con marco de montaje con manta filtrante . . .-A - EF,
opcionalmente con accesorio especial de corredera del
tipo . . .-AS - EF (ejecuciones en la pgina 15).
La rejilla y el marco de montaje con filtro van unidos entre s
por medio de un muelle. El marco de montaje con filtro se
suministra desde H = 125 hasta H = 525 mm.
A solicitud, se pueden suministrar tambin repuestos de
mantas filtrantes E-EF.

El marco de montaje es de chapa de acero perfilada, y la


superficie va fosfatada, pintada en color negro (RAL 9005)
con secado al horno. La manta filtrante es de fibra qumica
de clase de calidad EU 4.

H2/L2

H/L

H + 21

Tipo...-EF

L + 21

 Manta filtrante
 Alambre de proteccin,

L2

84




desmontable para el cambio de manta filtrante,


este alambre de proteccin es necesario en la
ejecucin de rejillas ...-A-EF...
 Alambre de apoyo posterior no desmontable
 Muelle
(El cambio de la manta filtrante es posible
una vez retirada la rejilla)

15

Rejillas y parrillas
Dimensiones

Tamaos suministrables
LxH
en mm
225 x 75
325
425
525
625
825
1025
1225
1425
1625
1825
2025
225 x 125
325
425
525
625
775
825
1025
1225
1425
1625
1825
2025
225 x 225
325
425
525
625
775
825
1025
1225
1425
1625
1825
2025
325 x 325
425
525
625
775
825
1025
1225
1425
1625
1825
2025
625 x 425
825
1025
1225
1025 x 525
1225

10

Aluminio
ASL VAT AH AWT AGS
AT
AF

Parrillas de aluminio
SL

Acero
Acero inoxid.
TR TRS
TRE

Plstico
KS

L a x Ha en mm
EH EHG

EF EFG

196 x 46
296
396
496
596
796
996
1196

245 x 95
345
445
545
645
845
1045
1245

196 x 96
296
396
496
596
796
996
1196

245 x 145
345
445
545
645
845
1045
1245

296 x 196
396
496
596
796
996
1196

345 x 245
445
545
645
845
1045
1245

396 x 296
496
596
796
996
1196

445 x 345
545
645
845
1045
1245

596 x 396
796
996
1196

645 x 445
845
1045
1245

Datos acsticos para el retorno


Rejillas

Valores de correccin para A eff


Aeff en m2
0,005 0,01 0,02 0,05
L WA / L W NC
13 10
7
3
Valores del diagrama referidos a A eff = 0,1 m2
(lamas en posicin recta)

0,1

0,2
+3

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AG
posicin de la compuerta 50 %

posicin de la compuerta 25 %

100

50 %

45

80

45
40

25

15

30

W
A

6
5

en

NC

3
dB 5
(A
)

20

10

25

4
3
1,5

3
4
veff en m/s

45

Nivel de potencia sonora LW en dB/oct.

30

30
20

NC

100 %

35

pt

40

40
35
4

30

30
3

25

20
2,5
63

9 10

125

250

500

1000

2000

4000

20
8000

Espectro de frecuencia por banda de octava en Hz

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AG

12

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AG
posicin de la compuerta 25 %

50

50
v

10

45

40
7

40

35

30
3

25

20

20
63
125
250
500
1000
2000
Espectro de frecuencia por banda de octava en Hz

veff = 6 m
/s
NC

NC

m
/s

4000

8000

Nivel de potencia sonora LW en dB/oct.

ef
f

30

6
5

posicin de la compuerta 100 %

Nivel de potencia sonora LW en dB/oct.

m/s

40

veff

40

22

veff =
8

50

60

Prdida de carga pt en Pa

Diagrama 9:
Los valores del diagrama para la regulacin situada al 100 %
son asmismo vlidos para rejillas sin regulacin.

11

Potencia sonora y prdida de carga


para partes posteriores . . .-AG

10

0,4
+6

5
40

45

4
40

30

35

30

25

20
2
63
125
250
500
1000
2000
Espectro de frecuencia por banda de octava en Hz

4000

20
8000

Datos acsticos para el retorno


Rejillas

13

15

Potencia sonora y prdida de carga


para partes posteriores . . .-AS
posicin de la compuerta 25 %

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AS
posicin de la compuerta 50 %

50 %

45

150
100 %

100

ve

ff

50

40

veff

=5

m/s

80

45

30

Nivel de potencia sonora LW en dB/oct.

50

en

NC

20

35

20

30

dB
(A 40
)

25

40

W
A

25

10

30

Prdida de carga pt en Pa

NC

35

pt

60

7
5

1,5

40
3

30
2
25

20

63

125

250

500

16

ve
=6

ff

50

m/s

Nivel de potencia sonora LW en dB/oct.

4
40
35

3
30

30

25

20
2
63

125

250

500

=4

20
8000

m/s

NC

NC
45

40

4000

posicin de la compuerta 25 %

20
1000

2000

Espectro de frecuencia por banda de octava en Hz

4000

8000

Nivel de potencia sonora LW en dB/oct.

ff

2000

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AS

posicin de la compuerta 100 %

ve

1,5
1000

Espectro de frecuencia por banda de octava en Hz

Potencia sonora y espectro de frecuencia por


banda de octava para la pieza posterior . . .-AS

50

35

30

veff en m/s

14

45
40

45

3
40

40

35
30
2

30

1,5

25

20
1,2
63

125

250

500

1000

2000

4000

20
8000

Espectro de frecuencia por banda de octava en Hz

23

Datos aerodinmicos
Rejillas
Ejemplo
Datos conocidos:
Serie AT-A con efecto de techo
Caudal total de aire
Velocidad mxima del flujo de aire
Distancia a la rejilla
Diferencia entre la temperatura ambiente
y la del aire impulsado

.
Vt = 150 l/s
v = 0,5 m/s
L
L = 10 m

Tabla de la pgina 25:


= 0,041 m2
A eff
A eff
0,043 m2
L x H = 625 x 125 325 x 225

tZ = 4 K

Diagrama 17:
A eff
= 0,041 m2
veff
= 3,8 m/s
= 1,2 m
b 0,2
i
= 15
tL /tZ = 0,13
= 4 x 0,13 = 0,52 K
tL
B
 1,5 m

Factor de correccin para disposicin sin efecto


de techo
Por ser la distancia al techo 0,8 m los valores del
diagrama vL , b 0,2 , tL /tZ se deben multiplicar por el
factor 0,71.

Disposicin con efecto de techo

Disposicin sin efecto de techo

0,3 m
10

b0,2

0,8 m
v
L
tL

20

20

B 0,15 x L

24

20

B 0,2 x L

b0,2

v
L
tL

Datos aerodinmicos
Rejillas con efecto techo
Seccin efectiva de salida de aire Aeff en m2
H
en mm

L en mm

Series

75

125

225

325

425
525

225

325

425

525

625

AH AF

0,006

0,009

0,011

0,014

VAT TRS

0,007

0,011

0,014

0,018

AT VAT ASL SL TR TRS TRE KS

0,014

0,021

0,029

0,036

0,043

AH AF

0,011

0,017

0,022

0,028

AWT

0,010

0,015

0,020

AT VAT ASL SL TR TRS TRE KS

0,029

0,043

AH AF

775

825

1025

1225

0,017

0,022

0,028

0,034

0,021

0,029

0,036

0,043

0,057

0,072

0,086

0,034

0,044

0,055

0,066

0,025

0,031

0,040

0,050

0,060

0,057

0,072

0,086

0,114

0,142

0,172

0,034

0,044

0,055

0,066

0,087

0,108

0,129

AWT

0,031

0,040

0,050

0,060

0,078

0,097

0,116

AT VAT ASL SL TR TRS TRE

0,064

0,086

0,108

0,129

0,172

0,214

0,256

AH AF

0,066

0,081

0,096

0,129

0,169

0,193

AWT

0,060

0,073

0,086

0,116

0,152

0,174

AT VAT ASL SL TR

0,172

0,228

0,285

0,342

AH AF

0,129

0,169

0,214

0,256

0,355

0,427

0,054

0,107

0,161

AT VAT SL TR

ve

ff

1,
00

10

en
m/
s
4
3

en

m
/s

10
0

1,5

80
70

vL

15
0

40
0
/s
. en l 30
0
t
V
20
0

50
0

70
0

0,
75

.
V [m3/h] =
.
V [l/s] x 3,6

1
10 100
00

55
45

0,011

0,
0 0
30 ,40 ,50

Diagrama 17

1,0
0,9
0,8
0,7
b0,2 =
0,6
0,018

0,028 0,043
0,072 0,114 0,172 0,256 0,342
2
Aeff en m
0,014 0,021
0,036 0,057 0,086
0,142 0,214 0,285
0,6
0
0 35
0,4 ,50
30
0
t
L
0,3

0
tZ
20
i
0,2
15
0
0,1
5
10
8
0,1
0
6
0,0
5
8
4
0,0
6
0,0
3
5

3
3

5 6 8 10
L en m
4 5 6 8 10

15 20
15 20

tL
tZ

25

Datos aerodinmicos
Rejillas

Medicin del caudal de aire

El caudal de aire se puede determinar midiendo la velocidad


del aire para la posicin recta de las lamas, con un tubo de
Pitot o con el anemmetro de molinillo.
Tubo de Pitot (figura 1):
Midiendo la velocidad efectiva en varios puntos situados entre
las lamas puede obtenerse de estas mediciones el valor medio
aritmtico veff.med..
El caudal de aire se puede calcular de la siguiente forma:
.
V. t [l/s] = veff.med. [m/s] x A eff [m2 ] x 1000
Vt [m3/h] = veff.med. [m/s] x A eff [m2 ] x 3600
Anemmetro de molinillo (figura 2):
El valor medio de la veff.med. se obtiene mediante pasadas uniformes del anemmetro por toda la superficie transversal de la
rejilla. El caudal se obtiene:
.
V. t [l/s] = veff.med. [m/s] x A eff [m2 ] x 1,33 x 1000
Vt [m3/h] = veff.med. [m/s] x A eff [m2 ] x 1,33 x 3600

Factores de correccin (para L = const.)


con efecto de techo

26

sin efecto de techo

Figura 1

Figura 2

 109

Determinacin del caudal de aire

Datos aerodinmicos
Rejillas

Correccin a los diagramas 18 y 19


(para posiciones de lamas divergentes)

v
L
tL / tZ
i
y
con efecto de techo
sin efecto de techo

18

19

sin efecto de techo


Desviacin de la vena y por diferencia
de temperatura

45
35
x 0,7
x 0,7
x 1,4
x 1,4
L x 0,2
L x 0,25

B
B

90
60
x 0,5
x 0,5
x 2,0
x 2,0
L x 0,3
L x 0,3

con efecto de techo


Diferencia de temperatura mxima  tZ
funcionando con refrigeracin

0,50

15

0,30

10

ef
f

0,20

tz en K con funcionamiento
con refrigeracin

m/s
3
4

ve

5
0,04

10

0,02

m
/s

4
1,
5

3
1

0,01
1
0,005

0,01

0,02

0,05

0,1

0,2

0,5

Aeff en m2
1,00

15

Diagrama 19:
Para evitar la cada de la vena de aire del techo para una
superficie de impulsin y velocidad de salida de aire dadas,
no deben de sobrepasarse las diferencias mximas de temperatura indicadas en el diagrama.

0,60

L
=
10

0,40

9
8
7

0,20

6
5
4

0,10

0,06

y/ tz en m/K

Aeff en m2

0,06

2,
5

=2
ff

0,10

3,
5

veff
Aeff
tz

Calefaccin
y = tz x y/ tz

0,04
y
0,02

Refrigeracin
L

0,01

27

Datos aerodinmicos
Rejillas continuas con efecto de techo

Factor de correccin para disposicin sin efecto


de techo
Por ser la distancia al techo 0,8 m los valores del
diagrama vL , b 0,2 , tL /tZ se deben multiplicar por el
factor 0,71.

Disposicin con efecto de techo

Disposicin sin efecto de techo

0,3 m
10

0,8 m

b0,2
v
L
tL

20

b0,2

Disposicin de rejillas continuas

B
Varias rejillas individuales situadas
unas al lado de otras con
separacin B < 0,1 x L

Rejillas continuas con L1/H1 > 14


o rejillas individuales
de pared a pared
B

28

v
L
tL

Datos aerodinmicos
Rejillas continuas

Altura efectiva de la seleccin de aire


heff en m

H
en mm

SL

0,075
0,150
0,225

75
125
225
325

AH AF
0,030
0,057
0,115
0,170

Diagrama 20
.
V [m3/h] =
.
V [l/s] x 3,6

m
. en l/s3
0
V
0

400

500

600

0
1,5

6
5
4

veff e
nm
/s
3

0
1,0

s
m/
n
v L e

200

5
0,7

150

0
0,5
0
0,4

1,5
100
80
70
60

0
0,3
1,5

50

b0

,2

0,030 0,037
AH, AF
SL

0,030 0,037

0,2
5
0,2
0,1
5

0,057 0,075

0,115
heff en m

0,057 0,075
0,7
0,6
0,5
L
t

0,4
 tZ
0,3

0,170
0,150

0,225

0,225

1,0
0
0,7 ,8
0,6 m

5 6 7 8 10
L en m
5 6 7 8 10

15

20

15

20

6
5

i
4

3
2,5

tL
tZ

29

Datos aerodinmicos
Rejillas continuas
Determinacin del caudal

Medicin del caudal

El caudal de aire se puede determinar midiendo la velocidad


del aire para la posicin recta de las lamas, con el tubo de
Pitot o con el anemmetro de molinillo.

Figura 1

Figura 2

 109

Tubo de Pitot (figura1):


Midiendo la velocidad efectiva en varios puntos situados
entre las lamas puede obtenerse de estas mediciones el
valor medio aritmtico veff.med..
El caudal se puede calcular de la siguiente forma:
.
V. t [ l/s] = veff.med. [m/s] x heff [m] x L1 [m] x 1000
Vt [m3/h] = veff.med. [m/s] x heff [m] x L1 [m] x 3600
Anemmetro de molinillo (figura 2):
El valor medio de la veff.med. se obtiene mediante pasadas
uniformes del anmmetro por toda la seccin transversal
de la rejilla continua. Con ello, el caudal se obtiene:
.
V. t [ l/s] = veff.med. [m/s] x heff [m] x L1 [m] x 1,33 x 1000
Vt [m3/h] = veff.med. [m/s] x heff [m] x L1 [m] x 1,33 x 3600

21

Diagrama 22:
Para evitar la cada de la vena de aire del techo para una
superficie de impulsin y velocidad de salida de aire dadas,
no debe de sobreparse las diferencias mximas de temperatura indicadas en el diagrama.

sin efecto de techo


Desviacin de la vena de aire por diferencia
de temperatura

0,50
0,30
0,20
heff en m

0,10

=
f

/s
m

v ef

0,05

7 8

0,03
1,00
15
m

veff
Aeff
tz

0,50

Calefaccin

0,30
0,20

10
8

0,10

6
5

0,05

0,03
0,02

y = tz x y/ tz
y

y/ tz en m/K

L=

Refrigeracin
L

0,01

22

con efecto de techo


Diferencia mxima de temperatura  tZ
para funcionamiento con refrigeracin

Factores de correccin (para L = const.)

15

con efecto de techo

sin efecto de techo

3
5
2,

10

=
1
/s
m

tz en K para funcionamiento
en refrigeracin

2
1,

v ef

SL

30

Correccin a los diagramas 21 y 22


(para posiciones de lamas divergentes)

AH, AF

5
1,

1,5
0,030

0,057

0,115
0,075
heff en m

0,170
0,150

0,225

v
L
tL / tZ
i

45
35
x 0,7
x 0,7
x 1,4

90
60
x 0,5
x 0,5
x 2,0

Datos aerodinmicos para el retorno


Rejillas

 109

Medicin del caudal de aire

Anemmetro:
El valor medio de la veff.med. se obtiene mediante pasadas
uniformes del anemmetro por toda la seccin transversal
de la rejilla.
El caudal de aire se puede calcular de la siguiente forma:
.
V. [l/s] = veff.med. [m/s] x A eff [m2] x f x 1000
V [m3/h] = veff.med. [m/s] x A eff [m2] x f x 3600

Factor de correccin f
Series
ASL AT VAT SL TR TRS
AH AF AWT

f
1,6
1,9

Seccin efectiva de impulsin de aire


LxH
en mm

AH AF

225 x 75
325
425
525
625
825
1025
1225

0,004
0,006
0,009
0,011
0,013
0,017
0,021
0,026

A eff en m2
AT VAT
AWT
TR TRS
TRE KS
0,003
0,006
0,005
0,009
0,008
0,011
0,010
0,014
0,011
0,016
0,015
0,022
0,018
0,028
0,023
0,033

225 x 125
325
425
525
625
825
1025
1225

0,009
0,013
0,017
0,021
0,026
0,033
0,041
0,049

0,008
0,011
0,015
0,018
0,023
0,029
0,036
0,043

0,011
0,016
0,022
0,028
0,033
0,044
0,055
0,066

0,013
0,019
0,026
0,033
0,040
0,053
0,066
0,080

325 x 225
425
525
625
825
1025
1225

0,026
0,033
0,041
0,049
0,066
0,082
0,090

0,023
0,029
0,036
0,043
0,057
0,071
0,078

0,033
0,044
0,055
0,066
0,090
0,110
0,134

0,040
0,053
0,066
0,080
0,105
0,133
0,160

425 x 325
525
625
825
1025
1225

0,049
0,060
0,072
0,095
0,120
0,140

0,043
0,052
0,063
0,083
0,104
0,122

0,066
0,083
0,100
0,134
0,170
0,200

0,080
0,100
0,120
0,160
0,200
0,240

625 x 425
825
1025
1225

0,095
0,122
0,155
0,185

0,134
0,180
0,220
0,270

0,160
0,220
0,270
0,320

0,280
0,340

0,330
0,400

1025 x 525
1225

ASL SL

A eff para L = 775 mm puede interpolarse con suficiente exactitud!

31

Informacin para pedidos

Especificacin
Las rejillas, parrillas y rejillas continuas son adecuadas
para impulsin y retorno del aire, preferentemente para su
montaje en pared, suelo y antepechos de ventana. Estn
formadas por un marco frontal, con junta perimetral, con
lamas horizontales verticales orientables individualmente
o fijas; montaje en obra a eleccin con o sin marco de montaje, montaje mediante tornillos vistos, muelles fijaciones
invisibles. Para optimizar el reparto de aire se montan
accesorios en la parte posterior que pueden ser regulados
desde la parte frontal sin desmontar la rejilla.

Cdigo de pedido

Estos datos no se dan para las ejecuciones bsicas

E-SL-AG

1910 x 125

S1

RAL 9016

0 sin marco de montaje


. . . con marco de montaje
ver tabla de la
pgina 33

L xH
ver pgina 10
E xH
MxH
ver pginas 11 a 13

0 para la ejecucin bsica


y sin variantes de sujecin
. . . con variante de sujecin
ver tabla de la pgina 33

1) Solo para rejillas continuas

Regulacin de caudal
AGW
DGW
Z
Se ruega pedir aparte con los datos
relativos al tamao

Accesorios
Mantas filtrantes
de repuesto E-EF
AF-Pieza esquina-901)
ES - AF - 0 - A
ES - AF - 15 - A -1
ES - AF - 15 - A - 2
Se ruega pedir aparte pieza
esquina con los datos
relativos al la altura!

superficie standard E6-C-0


c
v
pintado segn RAL 9010
v
pintado segn RAL ...
u
v
anodizado segn la norma
v
b
Euras E4-C-31 a C-35
0 superficie standard segn RAL 9010 c
v
S1 pintado segn RAL ...
u
S 7 material base galvanizado
v
b
(solo la serie TR)
0 superficie standard acabado
c
en mate
u
S 8 superficie standard acabado brillanteb
c
0 superficie standard en PVC
u
b
similar a RAL 7011
0
P0
S1
S2

Ejemplo de pedido de rejilla


Fabricante: TROX
Tipo:
AT- AG / 825 x 225 / A 1

Ejemplo de pedido de rejilla continua


Fabricante: TROX
Tipo:
M - SL- AG / 2000 x 125 / E 1
E - SL- AG / 1910 x 125 / N 1
E - SL- AG / 1850 x 125 / N 1

Acero

Para piezas
posteriores,
ver tabla de la
pgina 15

Aluminio

Indicar el color

Pls- Acero
tico inoxidable

Para rejillas y
c
v
parrillas de
v
v
aluminio, ver
v
v
pginas 3 a 5
v
v
Para rejillas de acero, v
v
v
ver pgina 6
v
v
Para rejillas de acero u
inoxidable, ver pgina 7v
v
v
Para rejillas de plstico, v
v
v
ver pgina 8
v
v
v
Rejillas continuas
v
v
de aluminio y acero,
v
v
ver pginas 11 a 13
b

32

N1

E 1
)
M

c
v
v
v
v
v
v
v
v
v
v
v
u
v
v
v
v
v
v
v
v
v
v
b

Pieza final
Pieza
intermedia

Material:
Aluminio: Rejilla frontal de perfiles de aluminio extrudo,
anodizado en color natural E6 - C - 0.
Acero: Rejilla frontal de perfiles de acero, superficie tratada
y pintada en color blanco (RAL 9010) con pintura en polvo.
Acero galvanizado: Rejilla frontal de perfiles de chapa de
acero galvanizado.
Acero inoxidable: Rejilla frontal y piezas posteriores de
chapa perfilada de acero inoxidable, n de material 1.4301,
superficie acabada en mate, bajo demanda con brillo
(solamente la parte frontal).
Plstico: Rejilla frontal y piezas posteriores en perfiles
de plstico (PVC duro), en color gris oscuro (similar a
RAL 7011), resistente a temperaturas de hasta 50 C.
Lamas curvadas para regulacin de caudal en color negro
gris oscuro.

Informacin para pedidos

Piezas posteriores para rejilla frontal de aluminio, acero


acero galvanizado:
Piezas posteriores de chapa de acero perfilada con la
superficie fosfatada, pintada en color negro (RAL 9005) por
electroinmersin y secada al horno, con resistencia mnima
de 100 horas en cmara hmeda segn DIN 50 017 sin
variaciones.

Serie

Marco de montaje

Variantes de sujecin

Anchura del marco frontal


en mm

Anchura del marco frontal en mm

27 (28)

23 (20)

28 / 20

Sujecin con fijacin oculta Taladros avellanados


27 (28)

23

20

27 (28)
25 (TRE
y KS)

Sujecin con muelle


27 (28)

23

20

B 11

ASL

A1

AT

A1

B1

G 11

A 11

B 11

H 11

VAT

A1

B1

G 11

A 11

B 11

H 11

AH - 0 / AH -15

A1

B1

A 11

B 11

E 11

F 11

EH - 0, EF -0, EHG - 0, EFG - 0


EH -15, EF -15, EHG -15, EFG -15
AWT

A1

AGS

A1

0
M1

SL

TR

A1

C 11

TRS

A1

C 11

0
0

TRE

Pieza
final

C1

D1

E1

F1

E 11

A 11

E 11

A 11

E - AF - 0 / AF -15
N1

E - SL
Pieza
intermedia

Rejilla continua

KS
E - AH - 0 / AH -15

Reservado el derecho de modificaciones Todos los derechos reservados Gebr. Trox GmbH (09/2000)

Rejilla

AF - 0 / AF -15

M - AH - 0 / AH -15

0
0

M - AF - 0 / AF - 15
M - SL

E1

0
0 = ejecucin bsica

33

RECUPERADORES DE CALOR DE DOBLE FLUJO CONFIGURABLES

Serie CADB-D / DI / DC
Serie CADB-D
Recuperadores de calor montados en cajas de
acero galvanizado plastificado color marfil,
aislante termo acstico ignfugo clase M1,
bocas de entrada y salida configurables, versiones
para instalacin vertical u horizontal, embocaduras con junta estanca y filtros G4 con una
eficacia del 86%, aislamiento al fuego M3.
Serie CADB-DI
Recuperadores de calor montados en cajas de
acero galvanizado plastificado color marfil,
con resistencia elctrica de apoyo incorporada, aislante termo acstico ignfugo clase
M1, bocas de entrada y salida configurables,
versiones para instalacin vertical u horizontal, embocaduras con junta estanca y filtros
G4 con una eficacia del 86%, aislamiento al
fuego M3.
Serie CADB-DC
A

Recuperadores de calor montados en cajas de


acero galvanizado plastificado color marfil, con
batera de agua incorporada, aislante termo
acstico ignfugo clase M1, bocas de entrada
y salida configurables, versiones para instalacin

Hostelera

Salas de
fumadores

vertical u horizontal, embocaduras con junta


estanca y filtros G4 con una eficacia del 86%,
aislamiento al fuego M3.
Otros datos
Caudales de 450 a 5.600 m3/h.
Versiones Horizontal y Vertical, ambas con
posibilidad de By Pass y de Doble pared.
Motores:
IP20 (Gamas 05, 08, 18, 30 y 56).
IP55 (Gama 45).
Dimetros de conducto: 200, 250, 315, 355,
450 mm.
Paneles laterales intercambiables que permiten mltiples combinaciones.

CADB-D / DI / DC

Oficinas

Ventiladores
Dos ventiladores centrfugos de doble odo con
motor incorporado.

Recuperadores de calor

Locales
comerciales

509

Ventajas constructivas
Instalacin vertical

Bajo nivel sonoro

Fcil montaje

Modelos especficos para instala-

Caja con aislamiento acstico

Pies integrados que facilitan la

cin vertical

ignfugo M1 de 10 mm

sujecin y montaje

Versin con bypass

2 filtros
de gran eficacia

Caja estanca

Versin con by-pass que permite

2 filtros, de eficacia del 86%,

Juntas de goma en el cierre de

que el 35% del aire no pase a

aislamiento al fuego M3

la tapa y en las bridas de aspiracin y descarga que proporcio-

travs del intercambiador

nan gran estanqueidad

Evacuacin
de condensaciones

Tomas de presin

Acabados de gran calidad, con

Desage que permite la salida

Tomas de presin, anterior y

cantoneras de aluminio, que

de agua de las condensaciones

posterior a los filtros, para

CADB-D / DI / DC

Robustez

proporcionan gran robustez

controlar la limpeza de los


mismos

Recuperadores de calor

Caja de bornes
externa estanca

510

Montaje verstil

Caja de bornes externa

El diseo de estas unidades de recuperacin de calor permite su configuracin por

estanca, IP55

el propio usuario a pie de obra. Todos los paneles laterales son intercambiables lo
que permite posicionar las conexiones de impulsin y aspiracin directamente en
la obra en funcin de los requerimientos especficos

Fcil mantenimiento

Tapas de acceso rpido a los filtros y al intercambiador para facilitar la limpieza en los modelos
CADB- 05 / 08 / 18 / 30

Tapas de acceso rpido a los filtros y al intercambiador para facilitar la limpieza.

C A D B - D
1

I
2

3 0
3

A H
4

T R

D P

B P

1 - CADB: Serie

3 - Tamao

2 - D: Gama Standard

4 - A,D,E,G: Tipo de configuracin.

DI: Gama con resistencia incorporada


DC: Gama con batera de agua incorporada

6 - MONO: Resistencia de apoyo monofsica.


TRI: Resistencia de apoyo trifsica.

5 - H: Versin horizontal

7 - DP: Gama con doble pared aislante.

V: Versin vertical.

8 - BP: Versin con By Pass incorporado

Eficiencia Intercambiadores de calor*


Modelos
Eficiencia %
Potencia trmica recuperada kW/h
Temperatura del aire renovado C

CADB 05
50,7
2,2
7,7

CADB 08
53,9
3,7
8,5

CADB 18
51,6
8,4
7,9

CADB 30
52,5
13,4
8,1

CADB 45
54
20,3
8,5

* Valores en las siguientes condiciones: Temperatura aire exterior: -5; Temperatura ambiente: 20; H.R. Interior: 50%; Caudal: nominal.

CADB 56*
52,5
24,6
8,1

Recuperadores de calor

Referencia

CADB-D / DI / DC

En los modelos CADT-45 y CADT-56 los filtros se extraen por la parte superior

511

Caractersticas tcnicas
Modelos sin calefaccin aadida
"

Modelo

Tipo
Ventilador

Velocidad
r.p.m.

Velocidades

133/126
146/180
9/7
10/8
10/10
12/9
133/126
146/180
9/7
10/8
10/10
12/9

3000
3000
1500
1500
1500
1500
3000
3000
1500
1500
1500
1500

4
4
3
3
1
1
4
4
3
3
1
1

CADB-D 05
CADB-D 08
CADB-D 18
CADB-D 30
CADT-D 45
CADT-D 56
CADB-D 05 DP
CADB-D 08 DP
CADB-D 18 DP
CADB-D 30 DP
CADT-D 45 DP
CADT-D 56 DP

Potencia
Motor
kW
2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 0,750
2 x 1,500
2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 0,750
2 x 1,500

Intensidad
maxima absorbida
(A) a 230 V
2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2
2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2

Caudal
Mximo
m3/h
450
900
1900
3100
4500
5600
450
900
1900
3100
4500
5600

Proteccin
IP

Eficiencia
%

20
20
20
20
55
20
20
20
20
20
55
20

50,7
53,9
51,6
52,5
54
52,5
50,7
53,9
51,6
52,5
54
52,5

Peso
kg
*
25
39
85
108
160
175
33
52
109
134
220
235

* Los modelos con By Pass (BP) tienen un peso aproximado de 5 Kg ms.

Modelos con resistencia elctrica incorporada


Modelo

Tipo
Velocidad VeloVentilador r.p.m.
cida-

CADB-DI 05 MONO
CADB-DI 08 MONO
CADB-DI 18 MONO
CADB-DI 30 TRI
CADT-DI 45 TRI
CADT-DI 56 TRI
CADB-DI 05 DP MONO
CADB-DI 08 DP MONO
CADB-DI 18 DP MONO
CADB-DI 30 DP TRI
CADT-DI 45 DP TRI
CADT-DI 56 DP TRI

133/126
146/180
9/7
10/8
10/10
12/9
133/126
146/180
9/7
10/8
10/10
12/9

3000
3000
1500
1500
1500
1500
3000
3000
1500
1500
1500
1500

Potencia
Motor

Intensidad Caudal Proteccin Eficiencia Potencia Tensin Intensidad


absorbida Mximo
IP
%
resisten- resisten- absorbida

des

kW

motor (A)

m3/h

4
4
3
3
1
1
4
4
3
3
1
1

2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 0,750
2 x 1,500
2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 0,750
2 x 1,500

2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2
2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2

450
900
1900
3100
4500
5600
450
900
1900
3100
4500
5600

20
20
20
20
55
20
20
20
20
20
55
20

50,7
53,9
51,6
52,5
54
52,5
50,7
53,9
51,6
52,5
54
52,5

Intensidad
mxima

Peso
kg

cia kW

cia (V)

resistencia (A)

total (A)

2
4
6
8
12
12
2
4
6
8
12
12

230
230
230
350
380
380
230
230
230
350
380
380

8,5
17,5
26
12,17
31,6
31,6
8,5
17,5
26
12,17
31,6
31,6

9,82
20,80
35,36
24,77
37,80
42,00
9,82
20,80
35,36
24,77
37,80
42,00

32
46
97
108
188
208
41
61
126
151
268
288

Recuperadores de calor

CADB-D / DI / DC

* Los modelos con By Pass (BP) tienen un peso aproximado de 5 Kg ms.

512

Modelos con batera de agua incorporada


Modelo

CADB-DC 05
CADB-DC 08
CADB-DC 18
CADB-DC 30
CADT-DC 45
CADT-DC 56
CADB-DC 05 DP
CADB-DC 08 DP
CADB-DC 18 DP
CADB-DC 30 DP
CADT-DC 45 DP
CADT-DC 56 DP

Tipo
Velocidad
Ventilador
r.p.m.
133/126
146/180
9/7
10/8
10/10
12/9
133/126
146/180
9/7
10/8
10/10
12/9

3000
3000
1500
1500
1500
1500
3000
3000
1500
1500
1500
1500

Velocidades
4
4
3
3
1
1
4
4
3
3
1
1

Potencia
Motor
kW
2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 750
2 x 1500
2 x 0,150
2 x 0,355
2 x 0,373
2 x 0,550
2 x 750
2 x 1500

* Los modelos con By Pass (BP) tienen un peso aproximado de 5 kg ms.

Intensidad
absorbida
motor (A)
2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2
2 x 0,66
2 x 1,65
2 x 4,68
2 x 6,30
2 x 3,1
2 x 5,2

Caudal
Mximo
m3/h
450
900
1900
3100
4500
5600
450
900
1900
3100
4500
5600

Proteccin Eficiencia Rendimiento


IP
%
Trmico
kW
20
50,7
2,62
20
53,9
3,67
20
51,6
10,67
20
52,5
14,29
55
54
30
20
52,5
34,5
20
50,7
2,62
20
53,9
3,67
20
51,6
10,67
20
52,5
14,29
55
54
30
20
52,5
34,5

Peso
kg
*
34
48
102
116
195
215
43
63
129
156
275
295

Caudal aire
m3/h*

Aire ambiente
C

H.R. %

50
CADB-D 05

500

20
60

50
CADB-D 08

800

20
60

50
CADB-D 18

1.900

20
60

50
CADB-D 30

3.000

20
60

50
CADT-D 45

4.500

20
60

50
CADT-D 56

5.600

20
60

Aire exterior
C
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5
-10
-5
0
5

U.R. %
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60
80
80
70
60

Aire tratado

Eficiencia

Potencia

C
5,6
7,7
9,4
11,7
7
8,6
10,5
12,1
6,6
8,5
10
12,1
8
9,5
11,2
12,5
5,9
7,9
9,5
11,8
7,3
8,8
10,7
12,2
6,2
8,1
9,7
11,9
7,6
9,1
10,9
12,4
6,6
8,5
10,1
12,1
8,1
9,8
11,3
12,8
6,3
8,1
9,8
11,9
7,5
9,4
10,9
12,5

%
52,2
50,7
46,9
44,9
56,7
54,4
52,5
47,4
55,4
53,9
49,8
47,4
60,1
57,9
55,8
50,3
53,1
51,6
47,7
45,6
57,7
55,4
53,4
48,2
54
52,5
48,5
46,3
58,7
56,4
54,4
49,1
55,2
54
50,2
47,6
60,3
59,3
56,3
51,7
54,5
52,3
48,8
46,1
58,5
57,5
54,5
50

kW
2,7
2,2
1,6
1,2
2,9
2,3
1,8
1,2
4,5
3,7
2,7
1,9
4,9
4
3,1
2,1
10,3
8,4
6,2
4,4
11,2
9
6,9
4,7
16,6
13,4
9,9
7,1
18
14,5
11,2
7,5
25
20,3
15,2
10,7
27,3
22,3
17
11,7
31,7
25,4
18,9
13,4
34,1
27,9
21,2
14,6

Recuperadores de calor

Modelo

CADB-D / DI / DC

Rendimiento trmico recuperadores

513

Relacin completa de versiones estndar


CADB-D
Gama 05

Gama 08

Gama 18

Gama 30

Gama 45

Gama 56

CADB-D 05 AH

CADB-D 08 AH

CADB-D 18 AH

CADB-D 30 AH

CADT-D 45 AH

CADT-D 56 AH

CADB-D 05 AH BP

CADB-D 08 AH BP

CADB-D 18 AH BP

CADB-D 30 AH BP

CADT-D 45 AH BP

CADT-D 56 AH BP

CADB-D 05 AV

CADB-D 08 AV

CADB-D 18 AV

CADB-D 30 AV

CADT-D 45 AV

CADT-D 56 AV

CADB-D 05 AV BP

CADB-D 08 AV BP

CADB-D 18 AV BP

CADB-D 30 AV BP

CADT-D 45 AV BP

CADT-D 56 AV BP

CADB-D 05 AH DP

CADB-D 08 AH DP

CADB-D 18 AH DP

CADB-D 30 AH DP

CADT-D 45 AH DP

CADT-D 56 AH DP

CADB-D 05 AH BP DP

CADB-D 08 AH BP DP

CADB-D 18 AH BP DP

CADB-D 30 AH BP DP

CADT-D 45 AH BP DP

CADT-D 56 AH BP DP

CADB-D 05 AV DP

CADB-D 08 AV DP

CADB-D 18 AV DP

CADB-D 30 AV DP

CADT-D 45 AV DP

CADT-D 56 AV DP

CADB-D 05 AV BP DP

CADB-D 08 AV BP DP

CADB-D 18 AV BP DP

CADB-D 30 AV BP DP

CADT-D 45 AV BP DP

CADT-D 56 AV BP DP

Recuperadores de calor

CADB-D / DI / DC

CADB-DI

514

Gama 05

Gama 08

Gama 18

Gama 30

Gama 45

Gama 56

CADB-DI 05 AH MONO

CADB-DI 08 AH MONO

CADB-DI 18 AH MONO

CADB-DI 30 AH TRI

CADT-DI 45 AH TRI

CADT-DI 56 AH TRI

CADB-DI 05 DH MONO

CADB-DI 08 DH MONO

CADB-DI 18 DH MONO

CADB-DI 30 DH TRI

CADT-DI 45 DH TRI

CADT-DI 56 DH TRI

CADB-DI 05 EH MONO

CADB-DI 08 EH MONO

CADB-DI 18 EH MONO

CADB-DI 30 EH TRI

CADT-DI 45 EH TRI

CADT-DI 56 EH TRI

CADB-DI 05 GH MONO

CADB-DI 08 GH MONO

CADB-DI 18 GH MONO

CADB-DI 30 GH TRI

CADT-DI 45 GH TRI

CADT-DI 56 GH TRI

CADB-DI 05 AV MONO

CADB-DI 08 AV MONO

CADB-DI 18 AV MONO

CADB-DI 30 AV TRI

CADT-DI 45 AV TRI

CADT-DI 56 AV TRI

CADB-DI 05 CV MONO

CADB-DI 08 CV MONO

CADB-DI 18 CV MONO

CADB-DI 30 CV TRI

CADT-DI 45 CV TRI

CADT-DI 56 CV TRI

CADB-DI 05 EV MONO

CADB-DI 08 EV MONO

CADB-DI 18 EV MONO

CADB-DI 30 EV TRI

CADT-DI 45 EV TRI

CADT-DI 56 EV TRI

CADB-DI 05 AH MONO BP

CADB-DI 08 AH MONO BP

CADB-DI 18 AH MONO BP

CADB-DI 30 AH TRI BP

CADT-DI 45 AH TRI BP

CADT-DI 56 AH TRI BP

CADB-DI 05 DH MONO BP

CADB-DI 08 DH MONO BP

CADB-DI 18 DH MONO BP

CADB-DI 30 DH TRI BP

CADT-DI 45 DH TRI BP

CADT-DI 56 DH TRI BP

CADB-DI 05 EH MONO BP

CADB-DI 08 EH MONO BP

CADB-DI 18 EH MONO BP

CADB-DI 30 EH TRI BP

CADT-DI 45 EH TRI BP

CADT-DI 56 EH TRI BP

CADB-DI 05 GH MONO BP

CADB-DI 08 GH MONO BP

CADB-DI 18 GH MONO BP

CADB-DI 30 GH TRI BP

CADT-DI 45 GH TRI BP

CADT-DI 56 GH TRI BP

CADB-DI 05 AV MONO BP

CADB-DI 08 AV MONO BP

CADB-DI 18 AV MONO BP

CADB-DI 30 AV TRI BP

CADT-DI 45 AV TRI BP

CADT-DI 56 AV TRI BP

CADB-DI 05 CV MONO BP

CADB-DI 08 CV MONO BP

CADB-DI 18 CV MONO BP

CADB-DI 30 CV TRI BP

CADT-DI 45 CV TRI BP

CADT-DI 56 CV TRI BP

CADB-DI 05 EV MONO BP

CADB-DI 08 EV MONO BP

CADB-DI 18 EV MONO BP

CADB-DI 30 EV TRI BP

CADT-DI 45 EV TRI BP

CADT-DI 56 EV TRI BP

CADB-DI 05 AH MONO DP

CADB-DI 08 AH MONO DP

CADB-DI 18 AH MONO DP

CADB-DI 30 AH TRI DP

CADT-DI 45 AH TRI DP

CADT-DI 56 AH TRI DP

CADB-DI 05 DH MONO DP

CADB-DI 08 DH MONO DP

CADB-DI 18 DH MONO DP

CADB-DI 30 DH TRI DP

CADT-DI 45 DH TRI DP

CADT-DI 56 DH TRI DP

CADB-DI 05 EH MONO DP

CADB-DI 08 EH MONO DP

CADB-DI 18 EH MONO DP

CADB-DI 30 EH TRI DP

CADT-DI 45 EH TRI DP

CADT-DI 56 EH TRI DP

CADB-DI 05 GH MONO DP

CADB-DI 08 GH MONO DP

CADB-DI 18 GH MONO DP

CADB-DI 30 GH TRI DP

CADT-DI 45 GH TRI DP

CADT-DI 56 GH TRI DP

CADB-DI 05 AV MONO DP

CADB-DI 08 AV MONO DP

CADB-DI 18 AV MONO DP

CADB-DI 30 AV TRI DP

CADT-DI 45 AV TRI DP

CADT-DI 56 AV TRI DP

CADB-DI 05 CV MONO DP

CADB-DI 08 CV MONO DP

CADB-DI 18 CV MONO DP

CADB-DI 30 CV TRI DP

CADT-DI 45 CV TRI DP

CADT-DI 56 CV TRI DP

CADB-DI 05 EV MONO DP

CADB-DI 08 EV MONO DP

CADB-DI 18 EV MONO DP

CADB-DI 30 EV TRI DP

CADT-DI 45 EV TRI DP

CADT-DI 56 EV TRI DP

CADB-DI 05 AH MONO DP BP

CADB-DI 08 AH MONO DP BP

CADB-DI 18 AH MONO DP BP

CADB-DI 30 AH TRI DP BP

CADT-DI 45 AH TRI DP BP

CADT-DI 56 AH TRI DP BP

CADB-DI 05 DH MONO DP BP

CADB-DI 08 DH MONO DP BP

CADB-DI 18 DH MONO DP BP

CADB-DI 30 DH TRI DP BP

CADT-DI 45 DH TRI DP BP

CADT-DI 56 DH TRI DP BP

CADB-DI 05 EH MONO DP BP

CADB-DI 08 EH MONO DP BP

CADB-DI 18 EH MONO DP BP

CADB-DI 30 EH TRI DP BP

CADT-DI 45 EH TRI DP BP

CADT-DI 56 EH TRI DP BP

CADB-DI 05 GH MONO DP BP

CADB-DI 08 GH MONO DP BP

CADB-DI 18 GH MONO DP BP

CADB-DI 30 GH TRI DP BP

CADT-DI 45 GH TRI DP BP

CADT-DI 56 GH TRI DP BP

CADB-DI 05 AV MONO DP BP

CADB-DI 08 AV MONO DP BP

CADB-DI 18 AV MONO DP BP

CADB-DI 30 AV TRI DP BP

CADT-DI 45 AV TRI DP BP

CADT-DI 56 AV TRI DP BP

CADB-DI 05 CV MONO DP BP

CADB-DI 08 CV MONO DP BP

CADB-DI 18 CV MONO DP BP

CADB-DI 30 CV TRI DP BP

CADT-DI 45 CV TRI DP BP

CADT-DI 56 CV TRI DP BP

CADB-DI 05 EV MONO DP BP

CADB-DI 08 EV MONO DP BP

CADB-DI 18 EV MONO DP BP

CADB-DI 30 EV TRI DP BP

CADT-DI 45 EV TRI DP BP

CADT-DI 56 EV TRI DP BP

CADB-DC
Gama 05

Gama 08

Gama 18

Gama 30

Gama 45

Gama 56

CADB-DC 05 AH

CADB-DC 08 AH

CADB-DC 18 AH

CADB-DC 30 AH

CADT-DC 45 AH

CADT-DC 56 AH

CADB-DC 05 DH

CADB-DC 08 DH

CADB-DC 18 DH

CADB-DC 30 DH

CADT-DC 45 DH

CADT-DC 56 DH

CADB-DC 05 EH

CADB-DC 08 EH

CADB-DC 18 EH

CADB-DC 30 EH

CADT-DC 45 EH

CADT-DC 56 EH

CADB-DC 05 GH

CADB-DC 08 GH

CADB-DC 18 GH

CADB-DC 30 GH

CADT-DC 45 GH

CADT-DC 56 GH

CADB-DC 05 AV

CADB-DC 08 AV

CADB-DC 18 AV

CADB-DC 30 AV

CADT-DC 45 AV

CADT-DC 56 AV

CADB-DC 05 CV

CADB-DC 08 CV

CADB-DC 18 CV

CADB-DC 30 CV

CADT-DC 45 CV

CADT-DC 56 CV

CADB-DC 05 EV

CADB-DC 08 EV

CADB-DC 18 EV

CADB-DC 30 EV

CADT-DC 45 EV

CADT-DC 56 EV

CADB-DC 05 AH BP

CADB-DC 08 AH BP

CADB-DC 18 AH BP

CADB-DC 30 AH BP

CADT-DC 45 AH BP

CADT-DC 56 AH BP

CADB-DC 05 DH BP

CADB-DC 08 DH BP

CADB-DC 18 DH BP

CADB-DC 30 DH BP

CADT-DC 45 DH BP

CADT-DC 56 DH BP

CADB-DC 05 EH BP

CADB-DC 08 EH BP

CADB-DC 18 EH BP

CADB-DC 30 EH BP

CADT-DC 45 EH BP

CADT-DC 56 EH BP

CADB-DC 05 GH BP

CADB-DC 08 GH BP

CADB-DC 18 GH BP

CADB-DC 30 GH BP

CADT-DC 45 GH BP

CADT-DC 56 GH BP

CADB-DC 05 AV BP

CADB-DC 08 AV BP

CADB-DC 18 AV BP

CADB-DC 30 AV BP

CADT-DC 45 AV BP

CADT-DC 56 AV BP

CADB-DC 05 CV BP

CADB-DC 08 CV BP

CADB-DC 18 CV BP

CADB-DC 30 CV BP

CADT-DC 45 CV BP

CADT-DC 56 CV BP

CADB-DC 05 EV BP

CADB-DC 08 EV BP

CADB-DC 18 EV BP

CADB-DC 30 EV BP

CADT-DC 45 EV BP

CADT-DC 56 EV BP

CADB-DC 05 AH DP

CADB-DC 08 AH DP

CADB-DC 18 AH DP

CADB-DC 30 AH DP

CADT-DC 45 AH DP

CADT-DC 56 AH DP

CADB-DC 05 DH DP

CADB-DC 08 DH DP

CADB-DC 18 DH DP

CADB-DC 30 DH DP

CADT-DC 45 DH DP

CADT-DC 56 DH DP

CADB-DC 05 EH DP

CADB-DC 08 EH DP

CADB-DC 18 EH DP

CADB-DC 30 EH DP

CADT-DC 45 EH DP

CADT-DC 56 EH DP

CADB-DC 05 GH DP

CADB-DC 08 GH DP

CADB-DC 18 GH DP

CADB-DC 30 GH DP

CADT-DC 45 GH DP

CADT-DC 56 GH DP

CADB-DC 05 AV DP

CADB-DC 08 AV DP

CADB-DC 18 AV DP

CADB-DC 30 AV DP

CADT-DC 45 AV DP

CADT-DC 56 AV DP

CADB-DC 05 CV DP

CADB-DC 08 CV DP

CADB-DC 18 CV DP

CADB-DC 30 CV DP

CADT-DC 45 CV DP

CADT-DC 56 CV DP

CADB-DC 05 EV DP

CADB-DC 08 EV DP

CADB-DC 18 EV DP

CADB-DC 30 EV DP

CADT-DC 45 EV DP

CADT-DC 56 EV DP

CADB-DC 05 AH DP BP

CADB-DC 08 AH DP BP

CADB-DC 18 AH DP BP

CADB-DC 30 AH DP BP

CADT-DC 45 AH DP BP

CADT-DC 56 AH DP BP

CADB-DC 05 DH DP BP

CADB-DC 08 DH DP BP

CADB-DC 18 DH DP BP

CADB-DC 30 DH DP BP

CADT-DC 45 DH DP BP

CADT-DC 56 DH DP BP

CADB-DC 05 EH DP BP

CADB-DC 08 EH DP BP

CADB-DC 18 EH DP BP

CADB-DC 30 EH DP BP

CADT-DC 45 EH DP BP

CADT-DC 56 EH DP BP

CADB-DC 05 GH DP BP

CADB-DC 08 GH DP BP

CADB-DC 18 GH DP BP

CADB-DC 30 GH DP BP

CADT-DC 45 GH DP BP

CADT-DC 56 GH DP BP

CADB-DC 05 AV DP BP

CADB-DC 08 AV DP BP

CADB-DC 18 AV DP BP

CADB-DC 30 AV DP BP

CADT-DC 45 AV DP BP

CADT-DC 56 AV DP BP

CADB-DC 05 CV DP BP

CADB-DC 08 CV DP BP

CADB-DC 18 CV DP BP

CADB-DC 30 CV DP BP

CADT-DC 45 CV DP BP

CADT-DC 56 CV DP BP

CADB-DC 05 EV DP BP

CADB-DC 08 EV DP BP

CADB-DC 18 EV DP BP

CADB-DC 30 EV DP BP

CADT-DC 45 EV DP BP

CADT-DC 56 EV DP BP

Configuraciones estndar CADB-D/DI/DC


A partir de estas configuraciones hay mltiples variables que pueden ser realizadas por parte del profesional instalador de una forma rpida y
sencilla (ver pgina 18).

HORIZONTALES
CADB- D 05/08/18/30 AH
CADT - D 45/56 AH

CADB- D 05/08/18/30 AH BP
CADT- D 45/56 AH BP

CADB- D 05/08/18/30 AH DP
CADT - D 45/56 AH DP

CADB-D 05/08/18/30 AH BP DP
CADT -D 45/56 AH BP DP

VENTILADOR
CENTRFUGO

CADB-D / DI / DC

CADB-D

BATERA
ELCTRICA

VERTICALES
CADB- D 05/08/18/30 AV
CADT - D 45/56 AV

CADB- D 05/08/18/30 AV BP
CADT - D 45/56 AV BP

CADB- D 05/08/18/30 AV DP
CADT - D 45/56 AV DP

CADB- D 05/08/18/30 AV BP DP
CADT - D 45/56 AV BP DP

AIRE NUEVO

AIRE EXTRAIDO

FILTRO

DESAGE

Recuperadores de calor

BATERA
DE AGUA

515

CADB-DI

Recuperadores de calor

CADB-D / DI / DC

HORIZONTALES

516

CADB- DI 05/08/18 AH MONO


CADB- DI 30 AH TRI
CADT - DI 45/56 AH TRI

CADB- DI 05/08/18 DH MONO


CADB- DI 30 DH TRI
CADT - DI 45/56 DH TRI

CADB- DI 05/08/18 EH MONO


CADB- DI 30 EH TRI
CADT - DI 45/56 EH TRI

CADB- DI 05/08/18 GH MONO


CADB- DI 30 GH TRI
CADT - DI 45/56 GH TRI

CADB- DI 05/08/18 AH MONO BP


CADB- DI 30 AH TRI BP
CADT - DI 45/56 AH TRI BP

CADB- DI 05/08/18 DH MONO BP


CADB- DI 30 DH TRI BP
CADT - DI 45/56 DH TRI BP

CADB- DI 05/08/18 EH MONO BP


CADB- DI 30 EH TRI BP
CADT - DI 45/56 EH TRI BP

CADB- DI 05/08/18 GH MONO BP


CADB- DI 30 GH TRI BP
CADT - DI 45/56 GH TRI BP

CADB- DI 05/08/18 AH MONO DP


CADB- DI 30 AH TRI DP
CADT - DI 45/56 AH TRI DP

CADB- DI 05/08/18 DH MONO DP


CADB- DI 30 DH TRI DP
CADT - DI 45/56 DH TRI DP

CADB- DI 05/08/18 EH MONO DP


CADB- DI 30 EH TRI DP
CADT - DI 45/56 EH TRI DP

CADB- DI 05/08/18 GH MONO DP


CADB- DI 30 GH TRI DP
CADT - DI 45/56 GH TRI DP

CADB- DI 05/08/18 AH MONO DP BP


CADB- DI 30 AH TRI DP BP
CADT - DI 45/56 AH TRI DP BP

CADB- DI 05/08/18 DH MONO DP BP


CADB- DI 30 DH TRI DP BP
CADT - DI 45/56 DH TRI DP BP

CADB- DI 05/08/18 EH MONO DP BP


CADB- DI 30 EH TRI DP BP
CADT - DI 45/56 EH TRI DP BP

CADB- DI 05/08/18 GH MONO DP BP


CADB- DI 30 GH TRI DP BP
CADT - DI 45/56 GH TRI DP BP

CADB- DI 05/08/18 CV MONO


CADB- DI 30 CV TRI
CADT - DI 45/56 CV TRI

CADB- DI 05/08/18 EV MONO


CADB- DI 30 EV TRI
CADT - DI 45/56 EV TRI

CADB- DI 05/08/18 AV MONO BP


CADB- DI 30 AV TRI BP
CADT - DI 45/56 AV TRI BP

CADB- DI 05/08/18 CV MONO BP


CADB- DI 30 CV TRI BP
CADT - DI 45/56 CV TRI BP

CADB- DI 05/08/18 EV MONO BP


CADB- DI 30 EV TRI BP
CADT - DI 45/56 EV TRI BP

CADB- DI 05/08/18 AV MONO DP


CADB- DI 30 AV TRI DP
CADT - DI 45/56 AV TRI DP

CADB- DI 05/08/18 CV MONO DP


CADB- DI 30 CV TRI DP
CADT - DI 45/56 CV TRI DP

CADB- DI 05/08/18 EV MONO DP


CADB- DI 30 EV TRI DP
CADT - DI 45/56 EV TRI DP

CADB- DI 05/08/18 AV MONO DP BP


CADB- DI 30 AV TRI DP BP
CADT - DI 45/56 AV TRI DP BP

CADB- DI 05/08/18 CV MONO DP BP


CADB- DI 30 CV TRI DP BP
CADT - DI 45/56 CV TRI DP BP

CADB- DI 05/08/18 EV MONO DP BP


CADB- DI 30 EV TRI DP BP
CADT - DI 45/56 EV TRI DP BP

Recuperadores de calor

CADB- DI 05/08/18 AV MONO


CADB- DI 30 AV TRI
CADT - DI 45/56 AV TRI

CADB-D / DI / DC

VERTICALES

517

CADB-DC

Recuperadores de calor

CADB-D / DI / DC

HORIZONTALES

518

CADB- DC 05/08/18/30 AH
CADT - DC 45/56 AH

CADB- DC 05/08/18/30 DH
CADT - DC 45/56 DH

CADB- DC 05/08/18/30 EH
CADT - DC 45/56 EH

CADB- DC 05/08/18/30 GH
CADT - DC 45/56 GH

CADB- DC 05/08/18/30 AH BP
CADT - DC 45/56 AH BP

CADB- DC 05/08/18/30 DH BP
CADT - DC 45/56 DH P

CADB- DC 05/08/18/30 EH BP
CADT - DC 45/56 EH BP

CADB- DC 05/08/18/30 GH BP
CADT - DC 45/56 GH BP

CADB- DC 05/08/18/30 AH DP
CADT - DC 45/56 AH DP

CADB- DC 05/08/18/30 DH DP
CADT - DC 45/56 DH DP

CADB- DC 05/08/18/30 EH DP
CADT - DC 45/56 EH DP

CADB- DC 05/08/18/30 GH DP
CADT - DC 45/56 GH DP

CADB- DC 05/08/18/30 AH DP BP
CADT - DC 45/56 AH DP BP

CADB- DC 05/08/18/30 DH DP BP
CADT - DC 45/56 DH DP BP

CADB- DC 05/08/18/30 EH DP BP
CADT - DC 45/56 EH DP BP

CADB- DC 05/08/18/30 GH DP BP
CADT - DC 45/56 GH DP BP

CADB- DC 05/08/18/30 CV
CADT - DC 45/56 CV

CADB- DC 05/08/18/30 EV
CADT - DC 45/56 EV

CADB- DC 05/08/18/30 AV BP
CADT - DC 45/56 AV BP

CADB- DC 05/08/18/30 CV BP
CADT - DC 45/56 CV BP

CADB- DC 05/08/18/30 EV BP
CADT - DC 45/56 EV BP

CADB- DC 05/08/18/30 AV DP
CADT - DC 45/56 AV DP

CADB- DC 05/08/18/30 CV DP
CADT - DC 45/56 CV DP

CADB- DC 05/08/18/30 EV DP
CADT - DC 45/56 EV DP

CADB- DC 05/08/18/30 AV DP BP
CADT - DC 45/56 AV DP BP

CADB- DC 05/08/18/30 CV DP BP
CADT - DC 45/56 CV DP BP

CADB- DC 05/08/18/30 EV DP BP
CADT - DC 45/56 EV DP BP

Recuperadores de calor

CADB- DC 05/08/18/30 AV
CADT - DC 45/56 AV

CADB-D / DI / DC

VERTICALES

519

Dimensiones (mm)
CADB-D

Construccin horizontal

Construccin vertical

Modelo
CADB-D 05
CADB-D 08
CADB-D 18
CADB-D 30

200
250
315
355

CADB-D

L
700
900
1100
1350

H
310
330
500
600

P
600
800
1000
1250

A
150
210
260
322,5

B
280
380
480
605

D
145
162
201,5
255

E
50
50
50
50

D
455
455

E
50
50

Construccin horizontal

CADB-D / DI / DC

Construccin vertical

C
165
168
298,5
345

Recuperadores de calor

Modelo
CADT-D 45
CADT-D 56

520

450
450

L
1300
1300

H
820
820

P
1200
1200

A
300
300

B
600
600

C
365
365

Construccin vertical

CADB-DI/DC

200
250
315
355
450
450

L
700
900
1100
1350
1300
1300

Con bypass (montado en fbrica)

H
310
330
500
600
820
820

P
600
800
1000
1250
1200
1200

R
920
1220
1520
1895
1550
1550

F
600
800
1000
1250
1300
1300

S
320
420
520
645
250
250

Modelo
CADB-D/DI 05 HBP/VBP
CADB-D/DI 08 HBP/VBP
CADB-D/DI 18 HBP/VBP
CADB-D/DI 30 HBP/VBP

A
150
210
260
322,5
300
300

B
280
380
480
605
600
600
A
550
800
950
1280

C
165
168
298,5
345
365
365
B
100
150
200
250

D
145
162
201,5
255
455
455

E
50
50
50
50
50
50
C
180
200
320
360

El bypass funciona con un servomotor y es activado remotamente con


un conmutador manual

CADB-D / DI / DC

Recuperadores de calor

Modelo
CADB-DI/DC 05
CADB-DI/DC 08
CADB-DI/DC 18
CADB-DI/DC 30
CADT-DI/DC 45
CADT-DI/DC 56

Construccin horizontal

521

Curvas caractersticas
Qv = Caudal en m3/h y en m3/s.
Pe = Presin esttica en mm.c.d.a y Pa.
Pabs = Potencia absorbida a la velocidad mxima (W).
Aire seco normal a 20 C y 760 mm c.d. Hg.
Ensayos realizados de acuerdo a Normas UNE 100-212-89 BS 848,
Part 1; AMCA 210-85 y ASHRAE 51-1985.

Recuperadores de calor

CADB-D / DI / DC

CADB-D/DI/DC 05

522

Prdidas de carga adicionales


Resistencias: Todos los modelos 10 Pa.
Bateras: Gama 05 16Pa, Gama 08 13 Pa, Gama 18 31 Pa,
Gama 30 27 Pa, Gama 45 60 Pa, Gama 56 100 Pa.

CADB-D/DI/DC 08

CADB-D/DI/DC 18

CADB-D/DI/DC 30

CADB-D/DI/DC 45

CADB-D/DI/DC 56

Caractersticas acsticas
Presin sonora dB(A) a 1,5 m de distancia.
Modelo
Velocidad
CADB-D/DI/DC 05
CADB-D/DI/DC 08
CADB-D/DI/DC 18
CADB-D/DI/DC 30
CADB-D/DI/DC 45
CADB-D/DI/DC 56

Radiado
1
19
30
46
49
-

2
25
36
48
50
-

Transmitido por conducto


3
30
39
48
52
-

4
36
43
46
54

1
33
45
57
59
-

2
41
52
59
61
-

3
47
57
61
63
-

4
53
59
56
64

Montaje verstil

Todos los paneles laterales


son intercambiables

Recuperadores de calor

CADB-D / DI / DC

El diseo de estas unidades de recuperacin de calor permite su configuracin por el propio usuario a pie de obra. Todos los paneles laterales
son intercambiables lo que permite posicionar las conexiones de impulsin y aspiracin directamente en la obra en funcin de los requerimientos
especficos.

523

Accesorios de montaje
AFR
Recambio filtro
Modelo

Recambio filtro

CADB-D/DI/DC 05
CADB-D/DI/DC 08
CADB-D/DI/DC 18
CADB-D/DI/DC 30
CADB-D/DI/DC 45
CADB-D/DI/DC 56

AFR-D/DI/DC 05
AFR-D/DI/DC 08
AFR-D/DI/DC 18
AFR-D/DI/DC 30
AFR-D/DI/DC 45/56
AFR-D/DI/DC 45/56

TPP D-H
TPP D-V
Tejado antilluvia
Modelo
CADB-D 05 H
CADB-D 08 H
CADB-D 18 H
CADB-D 30 H
CADB-D 45 H
CADB-D 56 H

Tejado antilluvia

Modelo

Tejado antilluvia

TPP D-H 05
TPP D-H 08
TPP D-H 18
TPP D-H 30
TPP D-H 45/56
TPP D-H 45/56

CADB-D 05 V
CADB-D 08 V
CADB-D 18 V
CADB-D 30 V
CADB-D 45 V
CADB-D 56 V

TPP D-V 05
TPP D-V 08
TPP D-V 18
TPP D-V 30
TPP D-V 45/56
TPP D-V 45/56

Modelo

Tejado antilluvia

Modelo

Tejado antilluvia

CADB-DI/DC 05 H
CADB-DI/DC 08 H
CADB-DI/DC 18 H
CADB-DI/DC 30 H
CADB-DI/DC 45 H
CADB-DI/DC 56 H

TPP DI/DC-H 05
TPP DI/DC-H 08
TPP DI/DC-H 18
TPP DI/DC-H 30
TPP DI/DC-H 45/56
TPP DI/DC-H 45/56

CADB-DI/DC 05 V
CADB-DI/DC 08 V
CADB-DI/DC 18 V
CADB-DI/DC 30 V
CADB-DI/DC 45 V
CADB-DI/DC 56 V

TPP DI/DC-V 05
TPP DI/DC-V 08
TPP DI/DC-V 18
TPP DI/DC-V 30
TPP DI/DC-V 45/56
TPP DI/DC-V 45/56

TPP DI/DC-H
TPP DI/DC-V
Tejado antilluvia

CADB-D / DI / DC

MSO
Acoplamiento elstico
Modelo
CADB-D/DI/DC 05
CADB-D/DI/DC 08
CADB-D/DI/DC 18
CADB-D/DI/DC 30
CADB-D/DI/DC 45
CADB-D/DI/DC 56

APC
Visera descarga

Acoplamiento
elstico
MSO-200
MSO-250
MSO-315
MSO-355
MSO-450
MSO-450

Recuperadores de calor

COM3 / COM4
Conmutadores de 3 y 4 velocidades

524

Modelo
CADB-D/DI/DC 05
CADB-D/DI/DC 08
CADB-D/DI/DC 18
CADB-D/DI/DC 30

Conmutador
COM4
COM4
COM3
COM3

Modelo
CADB-D/DI/DC 05
CADB-D/DI/DC 08
CADB-D/DI/DC 18
CADB-D/DI/DC 30
CADB-D/DI/DC 45
CADB-D/DI/DC 56

Visera
descarga
APC-200
APC-250
APC-315
APC-355
APC-450
APC-450

RMT
Reguladores electromecnicos
Modelo
CADB-D/DI/DC 45
CADB-D/DI/DC 56

Conmutador
RMT-8
RMT-12

Accesorios acsticos
SIL
Atenuador acstico para montar en la aspiracin o la descarga

Modelo

A B
C
D
Atenuador (mm) (mm) (mm) (mm)

CADB-D/DI/DC 05

SIL 200

200

315

700

CADB-D/DI/DC 08

SIL 250

250

355

700

CADB-D/DI/DC 18

SIL 315

315

400

700

CADB-D/DI/DC 30

SIL 355

355

450

CADB-D/DI/DC 45

SIL 450

450

560

CADB-D/DI/DC 56

SIL 450

450

560

Atenuacin en dB
63
Hz

125
Hz

250
Hz

500
Hz

900

900

11

23

25

10

19

25

860

2,2

700

860

3,7

4,1

6,7

13,2

14,3

900

1050

14

16

13

13

900

1050

14

16

13

13

3,3

1000
Hz

21,2

2000
Hz

4000
Hz

8000
Hz

17

16

4,1

5,5

7,6
3,4

8,1

Sistemas de control de temperatura ambiente y del aire insuflado

Regulacin de la temperatura ambiente


Regulacin en el ambiente

Modelo

Alimentacin

Potencia Etapas
kW

Regulador

Regulador con
limitacin de
temperatura del
aire insuflado

Regulacin
Temperatura
de insuflacin

Regulacin en armario sobre carril DIN


Potencimetro
con sonda
de ambiente
0/30 C

Regulador

Sonda de
conducto
0/30 C

Opcional
Limitacin de
temperatura
de insuflado
con sonda
de conducto
0/60 C

Potencimetro
externo
sobre
armario
0/30 C

Temporizador

CADB-DI 05 Mono 230V

PULSER

PULSER M

TG-R430

PULSER D

TG-K330

TG-K360

TBI-30

MCR-1

CADB-DI 08 Mono 230V

PULSER + P.ADD*

PULSER M + P.ADD*

TG-R430

PULSER D + P.ADD*

TG-K330

TG-K360

TBI-30

MCR-1

CADB-DI 18 Mono 230V

PULSER + P.ADD*

PULSER M + P.ADD*

TG-R430

PULSER D + P.ADD*

TG-K330

TG-K360

TBI-30

MCR-1

CADB-DI 30

Tri 400V

TG-R430

TTC-25

TG-K330

TG-K360

TBI-30

MCR-1

CADT-DI 45

Tri 400V

12

TG-R430

TTC-25

TG-K330

TG-K360

TBI-30

MCR-1

CADT-DI 56

Tri 400V

12

TG-R430

TTC-25

TG-K330

TG-K360

TBI-30

MCR-1

El Pulser ADD se debe instalar con el Pulser M cuando la potencia es superior a 3,6 kW

Regulacin batera para evitar


acumulacin de escarcha
(Proteccin intercambiador)

Asociacin con Batera elctrica


externa adicional

Regulacin
de la temperatura
de insuflacin

CADB-D / DI / DC

Resistencia elctrica
incorporada

Regulador

Sonda de
conducto
-20/10 C

Potencimetro
externo
-20/30 C

BATE 200-2 mono

PULSER D

TG-K310

TBI-10

BATE 250-3 mono

PULSER D

TG-K310

TBI-10

BATE 315-4 mono PULSER D + P.ADD

TG-K310

BATE 355-7,5 tri

TTC-25

TG-K310

7,5

BATE 450-7,5 tri

TTC-25

7,5

BATE 450-7,5 tri

TTC-25

Alimentacin

mm

Potencia
kW

CADB-D 05

Mono 230V

200

CADB-D 08

Mono 230V

250

CADB-D 18

Mono 230V

315

CADB-D 30

Tri 400V

355

7,5

CADB-D 45

Tri 400V

450

CADB-D 56

Tri 400V

450

Regulador

Sonda de
conducto
0/30 C

Potencimetro
externo
0/30 C

PULSER D

TG-K330

TBI-30

PULSER D

TG-K330

TBI-30

TBI-10

PULSER D + P.ADD

TG-K330

TBI-30

TBI-10

TTC 25

TG-K330

TBI-30

TG-K310

TBI-10

TTC 25

TG-K330

TBI-30

TG-K310

TBI-10

TTC 25

TG-K330

TBI-30

Recuperadores de calor

Batera
Modelo

525

Accesorios elctricos: Bateras de calefaccin


El funcionamiento de las bateras debe estar supeditado al funcionamiento del ventilador. La instalacin debe incorporar un presostato que corte
la alimentacin de la batera en caso de fallo en la ventilacin.
ABE
Bateras de calefaccin
Funciones:
- Antiescarcha, para calentar el aire frio exterior
antes de entrar en el recuperador y evitar la formacin de escarcha en el intercambiador (en
caso de aire exterior muy frio).
- Precalentamiento, para calentar el aire exterior
despus del recuperador, para incrementar la
temperatura del aire impulsado al local.

Modelo

Batera

Caudal
mnimo (m3/h)

Potencia
(W)

CADB-D/DI/DC 05

ABE 200/2M

230

2000

CABD-D/DI/DC 08

ABE 250/3M

355

3000

CABD-D/DI/DC 18

ABE 315/4M

560

4000

CABD-D/DI/DC 30

ABE 355/7,5T

715

7500

CABD-D/DI/DC 45

ABE 450/7,5T

715

7500

CABD-D/DI/DC 56

ABE 450/7,5T

715

7500

Accesorios para bateras de calefaccin


Para controlar las bateras en la funcin de precalentamiento.

PULSER
Regulador electrnico monofsico de 16 A,
que se instala en el local a calentar. En funcin de la temperatura programada, accionar la batera para mantener dicha temperatura en el local. Temperatura de consigna
entre 0 y 30 C en funcin de la seal enviada por la sonda. ndice de proteccin IP-30.
Potencia mxima soportada 3,6 kW.

TTC-25
Regulador electrnico de 25 A para bateras trifsicas diseado para montar en armario sobre
carril DIN. Funciona tambin con seal externa de
0 a 10V. Consigna entre 0 y 30 C en funcin de
la seal enviada por la sonda. Admite dos sondas: La principal y una de lmite mnimo y mximo. ndice de proteccin IP-20.

Recuperadores de calor

CADB-D / DI / DC

PULSER-ADD
Regulador complementario del PULSER
para controlar bateras de potencia superior
a la capacidad del PULSER (3600W - 230V)

526

PULSER M
Regulador electrnico monofsico de 16 A,
que se instala en el local a calentar. En funcin de la temperatura programada, accionar la batera para mantener dicha temperatura en el local. Temperatura de consigna
entre 0 y 30 C en funcin de la seal enviada por la sonda. ndice de proteccin IP-30.
Con entrada de regulacin de mximo
y mnimo. Potencia mxima soportada
3,6 kW.

TG-R430
Sonda de ambiente con valores de consigna
entre 0 y 30 C.
El valor de consigna regulado, puede ser bloqueado mediante un tornillo situado detrs de
la tapa.

PULSER D
Regulador electrnico monofsico de 16 A.
En funcin de la temperatura programada,
accionar la batera para mantener dicha
temperatura en el local. Temperatura de
consigna entre 0 y 30 C en funcin de la
seal enviada por la sonda. Especialmente
diseado para montaje en armario sobre
carril DIN. ndice de proteccin IP-20.
Potencia mxima soportada 3,6 kW.

TBI-10
Potencimetro con valor de consigna entre -20
y +10 C. Utilizado con el Pulser D o TTC 25
montados en armario, para fijar la temperatura
mnima del aire antes de entrar en el intercambiador.

RMT-3,5
RMT-8
Reguladores electromecnicos por transformador, de 5 posiciones para modelos trifsicos.

TBI-30
Potencimetro con valor de consigna entre 0 y
30 C. Utilizado con el Pulser D o TTC 25 montados en armario, para fijar la temperatura de
consigna del aire impulsado al local.

MCR-1
Temporizador. Valor de consigna entre 1 seg. y
100 h. Se utiliza en sistemas de ventilacin
apoyados por resistencias para retardar el
apagado del ventilador despus de desconectar el sistema.

PRESOSTATO 4.30
Presostato para comprobar el buen estado
de los filtros o de las bateras. Detecta diferencias de presin de 4 a 30 mmcda.

TG-K310, TG-K330 y TG-K360


Sonda de temperatura para colocar en el conducto de aire caliente.
Temperatura de utilizacin:
TG-K310 de -20 a 10 C
TG-K330 de 0 a 30 C
TG-K360 de 0 a 60 C

SQA
Sonda de calidad de aire que pone en marcha automticamente el extractor cuando se
detecta una concentracin de humo, olor u
otro gas molesto superior al valor seleccionado. Incorpora temporizador.

Indice de Clase
proteccin
IP21

II (

Intensidad
mxima (A)

Temperatura
de utilizacin

Temporizacin

2*

0-50 C

1-25 min.

Recuperadores de calor

CADB-D / DI / DC

* Para consumos superiores deber ir asociada a un rel.

527