Bulletin 100S-C/104S-C Safety Contactors

Bulletin 700S-CF Safety Control Relays


Selection Guide

Table of Contents
Description

Page

Bulletin 100S-C/104S-C Safety Contactors


Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Bulletin 700S-CF Safety Control Relays


Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

Bulletin 100S-C/104S-C

Safety Contactors

Bulletin
100S-C/104S-C
Positively Guided/
Mechanically Linked
Auxiliary Contacts
Front-Mounted Auxiliary
Contacts:
Permanently Fixed
Protective Cover to
Prevent Manual
Operation
Red Contact Housing
for Easy Identification
Incorporates IEC
947-5-1 Mechanically
Linked Symbol
AC and DC Operating
Coils
SUVA Third-Party
Certification
Description
Bulletin 100S-C/104S-C safety contactors provide mechanically linked, positively guided
contacts, which are required in feedback circuits for modern safety applications. The
positively guided N.C. auxiliary contacts will not change state when a power contact welds.
For additional information and selection of overload relays, mounting systems, and other
MCS components, please see Publication 0100C-1.0.1. Consult your local sales office or
price list for pricing information.

Your order must include:


Conformity to Standards

Approvals

IEC 947-4

SUVA Third-Party Certified

IEC 947 Type 2 Coordination

CE

IEC 947-4-1 Annex H (Pending) Special


Requirements for Auxiliary Contacts
Mechanically Linked with Power Contacts
(Mirror Contacts)

CSA Certified (Cert. No. LR13908)

IEC 947-5-1 Annex L Special


Requirements for Mechanically Linked
Contact Elements
EN50205
UL 508
CSA 22.2 No. 14

UL Listed (File No. E3125, Guide No. NLDX)

Cat. No. of contactor selected


with coil voltage code.
If required, Cat. No. of any
accessories.
If required, Cat. No. of
replacement coils.

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection
3-Pole AC-Operated Contactors

AC Operating Mechanism
3 Main Contacts

Ie

Ratings for Switching AC Motors - AC-2, AC-3, AC-4

[A]

kW (50 Hz)

AC-3 AC-1 230V

380V
415V
400V

1
500V

Aux. Contacts

HP (60 Hz)

690V

115V

230V

200V

230V

460V

575V

32

1/3

7-1/2

12

32

5.5

5.5

5.5

1/2

7-1/2

10

16

32

5.5

7.5

7.5

7.5

10

10

23

32

7.5

11

11

11

7-1/2

15

15

30

50

10

15

15

15

7-1/2

10

20

20

37

50

11

18.5

18.5

18.5

10

10

25

25

43

85

13

22

22

22

7-1/2

10

15

30

30

60

100

18.5

30

30

30

10

15

20

40

40

72

100

22

37

37

37

15

20

25

50

50

85

100

25

45

45

45

7-1/2

15

25

30

60

60

N.O.

N.C.

Cat. No.

0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

5
4
5
4
5
4
5
4
4
4
4
4
4
4
4
4
4
4
4
4

100S-C0905C
100S-C0914C
100S-C1205C
100S-C1214C
100S-C1605C
100S-C1614C
100S-C2305C
100S-C2314C
100S-C3004C
100S-C3014C
100S-C3704C
100S-C3714C
100S-C4304C
100S-C4314C
100S-C6004C
100S-C6014C
100S-C7204C
100S-C7214C
100S-C8504C
100S-C8514C

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code and Terminal Position

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60Hz:
Cat. No. 100S-C0905C becomes Cat. No.100S-C09D05C.
V

Hz

100200208- 22023038040012 24 32 36 42 48 100 110 110 120 127 200 220 208 240 230 230 240 240 277 347 380 400 400 415 440 480 500 550 600

50Hz
60Hz
50/60

R K V
Q J
KJ

W
V

Y KP
X

KY KP

KP

KD

P
D

KG

KG

L
KG

KF

VA

T
A
KA

KN

B
N
KB

Coil Terminal Position

All contactors are delivered with the coil terminals located on the line side.
For load side coil terminations, insert a U prior to the coil voltage code. Ordering
example: Cat. No. 100S-C09UD05C.

Cat. No.
100S-C0905C
Line Side

Cat. No.
100S-C09U05C
Load Side

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection, Continued
4-Pole AC-Operated Contactors

AC Operating Mechanism
4 Main Contacts

Ratings for Switching AC Motors


Ie
[A]

kW (50 Hz)

AC-3 AC-1 230V


9

32

12

32

23

380V
415V
400V

32

16

Contact Configuration

AC-2, AC-3, AC-4

32

5.5

5.5

5.5

7.5

7.5

7.5

11

11

1/3

5.5

1/2

7.5
11

460V

575V

7-1/2

230V

Auxiliary
Contacts

Main Pole

500V 690V 115V 230V 200V

HP (60 Hz)

7-1/2

N.C.

N.O.

N.C.

Cat. No.

100S-C09404C

100S-C09304C

100S-C12404C

100S-C12304C

100S-C16404C

100S-C16304C

100S-C23404C

100S-C23304C

10

10

7-1/2

N.O.

10

15

15

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V, 60 Hz: Cat. No.
100S-C09404C becomes Cat. No. 100S-C09D404C.

Hz

100200208- 22023038040012 24 32 36 42 48 100 110 110 120 127 200 220 208 240 230 230 240 240 277 347 380 400 400 415 440 480 500 550 600

50 Hz

V W X

KP

KG

VA

60 Hz

KP

KG

50/60 Hz

KJ

KY KP

KD

KG

KF

KA

KN

KB

Accessories Page 12
Specifications Page 14
Approximate Dimensions Page 19

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection, Continued
3-Pole DC-Operated Contactors

DC Operating Mechanism
3 Main Contacts

Ie

Ratings for Switching AC Motors - AC-2, AC-3, AC-4

[A]

AC-3

kW (50 Hz)

AC-1

230V

380V
415V
400V

1
500V

Auxiliary Contacts

HP (60 Hz)

690V

115V

3
230V

200V

230V

460V

575V

32

1/3

7-1/2

12

32

5.5

5.5

5.5

1/2

7-1/2

10

16

32

5.5

7.5

7.5

7.5

10

10

23

32

7.5

11

11

11

7-1/2

15

15

30

50

10

15

15

15

7-1/2

10

20

20

37

50

11

18.5

18.5

18.5

10

10

25

25

43

85

13

22

22

22

7-1/2

10

15

30

30

60

100

18.5

30

30

30

10

15

20

40

40

72

100

22

37

37

37

15

20

25

50

50

85

100

25

45

45

45

7-1/2

15

25

30

60

60

N.O.

N.C.

Cat. No.

0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

5
4
5
4
5
4
5
4
4
4
4
4
4
4
4
4
4
4
4
4

100S-C0905C
100S-C0914C
100S-C1205C
100S-C1214C
100S-C1605C
100S-C1614C
100S-C2305C
100S-C2314C
100S-C3004C
100S-C3014C
100S-C3704C
100S-C3714C
100S-C4304C
100S-C4314C
100S-C6004C
100S-C6014C
100S-C7204C
100S-C7214C
100S-C8504C
100S-C8514C

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code and Terminal Position


The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 24V DC:
Cat. No. 100S-C0905C becomes Cat. No.100S-C09ZJ05C.
DC Voltages
100S-C09C43
100S-C60C85

Standard
with Integrated Diode
with Integrated Diode

12

24

36

48

60

64

72

80

110

115

125

220

230

250

ZR

DR

ZQ

DQ

ZJ
DJ
DJ

ZW

DW

ZY

DY

ZZ

DZ

ZB

DB

ZG

DG

ZE

DE

ZD

DD

ZP

DP

ZS

DS

ZA

DA

ZF

DF

ZT

DT

Coil Terminal Position

All contactors are delivered with the coil terminals located on the line side.
For load side coil terminations, insert a U prior to the coil voltage code. Ordering
example: Cat. No. 100S-C09UZJ05C.

Cat. No.
100SC09Z05C Line
Side

Cat. No.
100S-C09ZU05C
Load Side

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection, Continued
4-Pole DC-Operated Contactors

DC Operating Mechanism
4 Main Contacts

Ratings for Switching AC Motors


Ie

Contact Configuration

AC-2, AC-3, AC-4

[A]

kW (50 Hz)

HP (60 Hz)

380V
1
415V
AC-3 AC-1 230V 400V 500V 690V 115V 230V 200V
9
12

32
32

3
4

4
5.5

4
5.5

1/3

5.5

1/2

Auxiliary Contact

3
230V
2

Main Pole

460V
5

575V
7-1/2

7-1/2

10

16

32

5.5

7.5

7.5

7.5

10

10

23

32

7.5

11

11

11

7-1/2

15

15

N.O.

N.C.

N.O.

N.C.

Cat. No.

100S-C09404C

100S-C09304C

100S-C12404C

100S-C12304C

4
3

0
1

0
0

4
4

100S-C16404C
100S-C16304C

100S-C23404C

100S-C23304C

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 24V DC: Cat. No. 100SC09404C becomes Cat. No. 100S-C09ZJ404C.
DC Voltages

100S-C09C23

Standard
with Integrated
Diode

Accessories Page 12
Specifications Page 14
Approximate Dimensions Page 19

12

24

36

48

60

64

72

80

110

115

125

220

230

250

ZR

ZQ

ZJ

ZW

ZY

ZZ

ZB

ZG

ZE

ZD

ZP

ZS

ZA

ZF

ZT

DJ

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection, Continued
Reversing AC-Operated Contactors

AC Operating Mechanism, 3 Main Contacts


Includes Mechanical/Electrical Interlock
Includes Reversing Power Wiring

Ratings for Switching AC Motors


Ie
[A]

AC-3

Auxiliary Contacts
Installed per
Contactor

AC-2, AC-3, AC-4


kW (50 Hz)

AC-1

380V
415V
400V

230V

HP (60 Hz)

1
500V

690V

115V

3
230V

200V

230V

460V

575V

32

1/3

7-1/2

12

32

5.5

5.5

5.5

1/2

7-1/2

10

16

32

5.5

7.5

7.5

7.5

10

10

Cat. No.

N.O.

N.C.

104S-C09012C

1
0

5
6

104S-C09210C
104S-C12012C

1
0

5
6

104S-C12210C
104S-C16012C

104S-C16210C

6
5

104S-C23012C
104S-C23210C

23

32

7.5

11

11

11

7-1/2

15

15

0
1

30

50

10

15

15

15

7-1/2

10

20

20

0
1

5
5

104S-C30010C
104S-C30210C

37

50

11

18.5

18.5

18.5

10

10

25

25

0
1

5
5

104S-C37010C
104S-C37210C

43

85

13

22

22

22

7.5

10

15

30

30

0
1

5
5

104S-C43010C
104S-C43210C

60

100

18.5

30

30

30

10

15

20

40

40

0
1

5
5

104S-C60010C
104S-C60210C

72

100

22

37

37

37

15

20

25

50

50

0
1

5
5

104S-C72010C
104S-C72210C

85

100

25

45

45

45

7-1/2

15

25

30

60

60

0
1

5
5

104S-C85010C
104S-C85210C

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No.
104S-C09210C becomes Cat. No. 104S-C09D210C.

Standard
Coil
100200208- 220230380400Voltages 12 24 32 36 42 48 100 110 110 120 127 200 220 208 240 230 230 240 240 277 347 380 400 400 415 440 480 500 550 600
50 Hz

V W X

KP

KG

VA

60 Hz

KP

KG

KJ

KY KP

KD

KG

KF

KA

KN

KB

50/60 Hz

Accessories Page 12

Bulletin 100S-C/104S-C

Safety Contactors
Product Selection, Continued
Reversing DC-Operated Contactors

DC Operating Mechanism, 3 Main Contacts, Line Side Coil Terminations


Includes Mechanical/Electrical Interlock
Includes Reversing Power Wiring

Ratings for Switching AC Motors


Ie

AC-2, AC-3, AC-4

[A]

AC-3

Auxiliary
Contacts
Installed per
Contactor

kW (50 Hz)

AC-1

230V

380V
415V
400V

HP (60 Hz)

1
500V

690V

115V

3
230V

200V

230V

460V

Cat. No.

575V

N.O.

N.C.
6
5

104S-C09012C
104S-C09210C

32

1/3

7-1/2

0
1

12

32

5.5

5.5

5.5

1/2

7-1/2

10

0
1

6
5

104S-C12012C
104S-C12210C

16

32

5.5

7.5

7.5

7.5

10

10

104S-C16012C

23

32

7.5

11

11

11

7-1/2

15

15

1
0

5
6

104S-C16210C
104S-C23012C

30

50

10

15

15

15

7-1/2

10

20

20

1
0

5
5

104S-C23210C
104S-C30010C

37

50

11

18.5

18.5

18.5

10

10

25

25

1
0

5
5

104S-C30210C
104S-C37010C

43

85

13

22

22

22

7.5

10

15

30

30

1
0

5
5

104S-C37210C
104S-C43010C

60

100

18.5

30

30

30

10

15

20

40

40

1
0

5
5

104S-C43210C
104S-C60010C

72

100

22

37

37

37

15

20

25

50

50

1
0

5
5

104S-C60210C
104S-C72010C

85

100

25

45

45

45

7-1/2

15

25

30

60

60

1
0

5
5

104S-C72210C
104S-C85010C

104S-C85210C

For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office.

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: 120V 60 Hz: Cat. No.
104S-C09210C becomes Cat. No. 104S-C09ZJ210C.
DC Voltages

104SC09C43
104SC60C85

12

24

36

48

60

64

72

80

110

115

125

220

230

250

Standard
with Integrated Diode

ZR

ZQ

ZJ
DJ

ZW

ZY

ZZ

ZB

ZG

ZE

ZD

ZP

ZS

ZA

ZF

ZT

with Integrated Diode

DR

DQ

DJ

DW

DY

DZ

DB

DG

DE

DD

DP

DS

DA

DF

DT

Accessories Page 12
Specifications Page 14
Approximate Dimensions Page 19

Bulletin 700S-CF

Safety Control Relays

Bulletin 700S-CF
Positively Guided/
Mechanically Linked
Auxiliary Contacts
Front-Mounted Auxiliary
Contacts:
Permanently Fixed
Protective Cover to
Prevent Manual
Operation
Red Contact Housing
for Easy Identification
Incorporates IEC
947-5-1 Mechanically
Linked Symbol
AC and DC Operating
Coils
SUVA Third-Party
Certification
Description
Bulletin 700S-CF Safety Control Relays provide mechanically linked, positively
guided contacts, which are required in feedback circuits for modern safety
applications. The positively guided N.C. auxiliary contacts will not change state if a
N.O. contact welds. Consult your local sales office or price list for pricing information.

Your order must include:


Conformity to Standards

Approvals

IEC 947-5-1

SUVA Third-Party Certified

IEC 947-5-1 Annex L Special


Requirements for Mechanically Linked
Contact Elements

CE Certified
CSA Certified
UL Listed, File E14840, Guide NKCR

EN 50011, EN 50005, EN 50022

Cat. No. of the relays required, complete


with coil suffix.
Cat. No. of adder decks, timers and
accessories required.
If required, the part number of
replacement coils.

UL 508
VDE 0660
CSA C22.2 Part 14

Bulletin 700S-CF

Safety Control Relays


Product Selection
Type CF Control Relays 8-Pole AC Voltage

AC-1

AC-11 and AC-15

Ie [A]

Ie [A]

40C 60C

25

24/48V

20

120V

16

240V

14

400V

10

Connection Diagrams

500V

600V

2.5

1.8

Main
Contacts

690V

Contacts

Auxiliary
Contacts

N.O.

N.C.

Cat. No.

700S-CF440C

700S-CF530C

700S-CF620C

FA13

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 700-CF440C
becomes Cat. No. 700-CF440DC.

100200208- 220230380400Voltage 12 24 32 36 42 48 100 110 110 120 127 200 220 208 240 230 230 240 240 277 347 380 400 400 415 440 480 500 550 600
50 Hz

V W

KP

KG

VA

60 Hz

KP

KG

50/60 Hz KJ

KY KP

KD

KG

KF

KA

KN

KB

Accessories Page 12
Specifications Page 14
Approximate Dimensions Page 19

10

Bulletin 700S-CF

Safety Control Relays


Product Selection
Type CF Control Relays 8-Pole DC Voltage

AC-1

AC-11 and AC-15

Ie [A]

Ie [A]

40C 60C

25

24/48V

20

120V

16

240V

14

400V

10

500V

2.5

Connection Diagrams

600V

1.8

Auxiliary
Contacts

Main
Contacts

690V

Contacts

N.O.

N.C.

Cat. No.

700S-CF440ZC

700S-CF530ZC

700S-CF620ZC

Voltage Suffix Code

The Cat. No. as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Cat. No. Example: Cat. No. 700-CF440ZC
becomes Cat. No. 700-CF440ZJC for 24V DC.
Voltage

12

24

36

48

60

64

72

80

110

115

125

220

230

250

Standard

With diode
suppressor

DJ

When ordering DJ coil with built-in surge suppression, remove Z from the Cat. No. Example: Cat. No. 700S-CF440ZC
becomes Cat. No. 700S-CF440DJC

Accessories Page 12
Specifications Page 14
Approximate Dimensions Page 19

11

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Accessories
Auxiliary Contacts

Description

N.O.

N.C.

Auxiliary Contact Blocks for Side


Mounting without Sequence Terminal Designations
1- and 2-pole
Two-way numbering for right or
left mounting on the contactor
Quick and easy mounting without
tools
Electronic-compatible contacts
down to 17V, 5mA
Mutual positive guidance to the
main contactor poles (except for
L types)

Auxiliary Contact Blocks for Side


Mounting with Sequence Terminal
Designations
1- and 2-pole
Two-way numbering for right or
left mounting on the contactor
Quick and easy mounting without
tools
Electronic compatible contacts
down to 17V, 5 mA
Mutual positive guidance to the
main contactor poles (except for
L types)
L = Late break/Early make

Connection Diagrams

-SA20

For Use With Cat. No.

Cat. No.

100S-C all
700S-CF all

100-SA10

-SA10

100S-C AC only
700S-CF AC only

100-SA20

100S-C09C23
700S-CF all

100-SB10

-SB20

-SB10

100S-C09C23 AC only
100-SB20
700S-CF AC only

AC Coils: Max. 2 N.O. auxiliary contacts may be mounted on the side. DC coils: Max. 1 N.O. auxiliary contact may be mounted on the side. No
additional N.C. auxiliary contacts may be added to safety contactors and control relays listed in this publication. For additional contact
configurations, consult your local Allen-Bradley sales office.
Double Numbering Left-side mounting only is recommended for Cat. No. 700S-CF due to double numbering.

Marking Systems
Uniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers
Description

Cat. No.

Label Sheet
sheet with 105 self-adhesive paper labels, 6 x 17 mm

10

100-FMS

Marking Tag Sheet


sheet with 160 perforated paper labels, 6 x 17 mm
To be used with a transparent cover

10

100-FMP

Transparent Cover
To be used with marking tag sheets

100

100-FMC

100
100

100-FMA1
100-FMA2

Marking Tag Adapters


100 each
To be used with marking tag:

12

Pkg. Qty.

System V4 / V5
System Bul. 1492W

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Accessories, Continued
Control Modules

Description
DC Interface (electronic)
Interface between the DC control signal (PLC) and the contactor AC
operating mechanism.
Control voltage 1830V DC (24V DC nominal)
For coil voltages of 110 240V AC
Suitable for all 100S-C contactor sizes, 985 A
Requires no additional surge suppression for the coils
Power consumption
0.1 W at 18V DC
0.25 W at 24V DC
0.5 W at 30V DC
2448V, 50/60 Hz
RC Module
110280V, 50/60 Hz
AC Operating Mechanism
380480V, 50/60 Hz
Surge Suppressors
For limitation of coil
1255V AC/1277V
switching transients.
DC
Plug-in, coil
56136V AC /
Varistor Module
mounted
78180V DC
AC/DC Operating Mecha Suitable for all
nism
137277V
AC /
100S-C contactor
181350V DC
sizes, 985 A
278575V AC
RC, Varistor and
Diode Versions
Diode Module DC Operat12250V DC
ing Mechanism

Connection
Diagrams

For Use With


Cat. No.

Cat. No.

100S-C with
AC coils
100-JE
700S-CF with
AC coils

K1M

(K1M)

100S-C with 100-FSC48


AC coils
100-FSC280
700S-CF with
100-FSC480
AC coils
100-FSV55
100S-C all
700S-CF all

100-FSV136
100-FSV277
100-FSV575

100S-C with
DC coils
100-FSD250
700S-CF with
DC coils

13

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Contactor Specifications
General Ratings
Cat. No. 100S-C09...100S-C85
Rated Insulation Voltage Ui
IEC, AS, BS, SEV, VDE 0660
UL; CSA
Rated Impulse Voltage Uimp

690V
600V
8 kV

Rated Voltage Ue Main Contacts


AC 50/60Hz
DC
Operating Frequency for AC Loads

115, 200, 208, 230, 240, 380, 400, 415, 460, 500, 575, 690V
24, 48, 110, 115, 220, 230, 300, 440V
5060 Hz

Switching Motor Loads


Cat. No.
Standard Ratings
AC-2, AC-3, AC-4 - 50Hz
DOL & Reversing

100SC09

100SC12

100SC16

100SC23

100SC30

100SC37

100SC43

100SC60

100SC72

100SC85

230V
240V

[A]
[A]

11.5
11

14.5
14

20
19

26.5
25.5

34
32.5

37
36

42
41

62
60

72
70

85
82

380V
400V

[A]
[A]

9
9

12
12

16
16

23
23

30
30

37
37

43
43

62
62

72
72

85
85

415V
500V

[A]
[A]

9
7

12
10

15
13

22
18

29
24

36
30

41
34

58
50

69
56

82
68

690V
230V

[A]
[kW]

5
3

7
4

9.3
5.5

12
7.5

17
10

20
11

25
13

34
18.5

42
22

49
25

240V

[kW]

5.5

7.5

10

11

13

18.5

22

25

380V
400V

[kW]
[kW]

4
4

5.5
5.5

7.5
7.5

11
11

15
15

18.5
18.5

22
22

30
30

37
37

45
45

415V
500V

[kW]
[kW]

4
4

5.5
5.5

7.5
7.5

11
11

15
15

18.5
18.5

22
22

30
30

37
37

45
45

690V
AC-2, AC-3, AC-4 - 60Hz 1-Ph 115V

[kW]
[A]

4
7.2

5.5
9.8

7.5
16

11
24

15
24

18.5
34

22
34

30
56

37
56

45
80

230V
115 V

[A]
[HP]

8
1/3

12
0.5

17
1

17
2

28
2

28
3

40
3

50
5

68
5

68
7-1/2

230 V
3-Ph 200V

[HP]
[A]

1
7.8

2
11

3
17.5

3
17.5

5
25.3

5
32.2

7-1/2
32.2

10
48.3

15
62.1

15
78.2

230 V
460 V

[A]
[A]

6.8
7.6

9.6
11

15.2
14

22
24

28
27

28
34

42
40

54
52

68
65

80
77

575 V
200 V

[A]
[HP]

9
2

11
3

17
5

20
5

22
7-1/2

27
10

32
10

52
15

62
20

72
25

230 V

[HP]

7-1/2

10

10

15

20

25

30

460 V
575 V

[HP]
[HP]

5
7-1/2

7-1/2
10

10
10

15
15

20
20

25
25

30
30

40
40

50
50

60
60

AC2 (ops/hr)
AC3 (ops/hr)

500
700

500
700

500
700

400
600

400
600

400
600

400
600

300
500

250
500

200
500

AC4 (ops/hr)

200

150

120

80

80

70

70

70

60

50

IEC

DOL & Reversing


UL/CSA/IEC

Max. Operating Rate

Product Selection Page 2


Accessories Page 12
Approximate Dimensions Page 19

14

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Contactor Specifications, Continued
Coil Data
Cat. No.

100SC09

100SC12

100SC16

100SC23

100SC30

100SC37

100SC43

100SC60

100SC72

100SC85

Voltage Range
AC: 50 Hz, 60Hz, Pickup
50/60 Hz
DC

[x Us]

0.851.1

Dropout [x Us]

0.30.6

[x Us]

0.81.1

Dropout [x Us]

0.10.6

Pickup

Coil Consumption
AC: 50 Hz, 60 Hz, Pickup [VA/W]
50/60 Hz
Hold-in [VA/W]

70/50
8/2.6

70/50
8/2.7

70/50
8/2.8

70/50
9/3

70/50
9/3

80/60
9/3

130/90
10/3.2

200/110
16/4.5

200/110
16/4.5

200/110
16/4.5

[W]
[W]

6.75
6.75

6.75
6.75

6.75
6.75

9.2
9.2

9.2
9.2

9.2
9.2

10.1
10.1

200
4.5

200
4.5

200
4.5

AC: 50 Hz, 60 Hz, Pickup


50/60 Hz
Dropout

[ms]
[ms]

1530
1060

1530
1060

1530
1060

1530
1060

1530
1060

1530
1060

1530
1060

w/ RC Suppressor Dropout
DC
Pickup

[ms]
[ms]

1060
4070

1060
4070

1060
4070

1060
4070

1060
5080

1060
5080

1060
5080

1060
2040

1060
2040

1060
2040

Dropout
w/ Integ. Suppres. Dropout

[ms]
[ms]

715
1420

715
1420

715
1420

715
1723

715
1723

715
1723

715
1723

2035

2035

2035

w/ Diode Suppres. Dropout

[ms]

7095

7095

7095

80125

80...125

80...125

80...125

80...125

80...125

80...125

DC

Pickup
Hold-in

Operating Times
18.530 18.530 18.530
1060
1060
1060

DC-13 ratings of 100-F auxiliary contacts are the same as the ratings of the auxiliary contact in Cat. No. 100S-C09...100S-C23 contactors.

15

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Contactor Accessory Specifications
Auxiliary Contacts

Current Switching
AC-1 Ith

at 40C
at 60C

AC-15 at Rated Operating Voltage


DC-13 at Rated Operating Voltage
Short-Circuit Protection
gG Fuse
Type 2 Coordination
Rated Impulse Voltage Uimp
Insulation Voltage (between control and load circuit) per DIN, VDE 0106, Part 101
(NAMUR recommendation)
Contact reliability per DIN19240 without contamination, normal industrial atmosphere

Auxiliary Contacts in Contactor


Cat. No. 100S-C09...100S-C23

Auxiliary Contacts in Accessories


Cat. No. 100-S, 100-F , 100-MC

[A]
[A]
[V]
[A]
[V]
[A]

25
20
24,48, 120, 240, 400, 500, 600, 690
16, 16, 14, 10, 2.5, 1.8, 1
24, 48, 125, 220, 440
5, 2, 0.7, 0.25, 0.12

10
6
24, 48, 120, 240, 400, 500, 600, 690
6, 6, 6, 3, 2,1.5, 1.2, 0.7
24, 48, 125, 220, 440
3, 1.5, 0.6, 0.3, 0.2

[A]
[kV]

10
8

10
6
Between auxiliary circuits: 250 V,
Between load and direct-connected aux.
circuits: 690 V

400
[V]

Positively Guided Contacts

17V, 5 mA, >108 operations per error

17V, 5 mA, >108 operations per error

Yes, N.O. and N.C. mutually unrestricted

Yes, N.O. and N.C. mutually unrestricted,


including N.C. in relation to N.O. main
contacts.

2 x A4

2 x A4

Terminals
Terminal Type
Wire Size per IEC 947-1
Flexible with WireEnd Ferrule
Solid/Stranded

14

0.52.5

[mm ]

1 4

0.752.5

[mm2]

1.56

0.52.5

1 Conductor
2 Conductor

[mm2]

1 Conductor
2 Conductor

0.752.5
1.56
[mm ]
Conductor
11.5
Recommended Tightening Torque (min...max)
[Nm]
1...2.5
1814
Wire Size per UL/CSA
[AWG]
1610
Recommended Tightening Torque (min...max)
[lb-in]
8.922
8.913.3
DC-13 ratings of 100-F auxiliary contacts are the same as the ratings of the auxiliary contact in Cat. No. 100S-C09...100S-C23 contactors.

Product Selection Page 3


Specifications Page 14
Approximate Dimensions Page 19

16

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Control Relay Specifications
General
Cat. No.
700S-CF
A600,
P600

Contact Ratings NEMA


Minimum Contact Rating

17-19.9V
20-24V

AC-1 (Non-inductive,
or slightly inductive
loads, resistance furnaces)
60C
IEC 947, EN 60947

30 mA
20 mA
16A
16A

6A
6A

120V

14A

6A

240V
400V

10A
5A

5A
3A

480V/500V
600V

2.5A
1.8A

1.6A
1.2A

1A

1.0A

25A

10A

690V
40C

A600, Q600

24V
48V

Contact Ratings IEC


AC-15 (solenoids, contactors)
at rated voltage
IEC 947, EN 60947

Ith
230V

10 kW

400V
690V

17 kW
30 kW

Ith

20A

230V
400V

8 kW
14 kW

690V

24 kW

Cat. No.
700S-CF

Aux. Contact
(Frontmounted)

[Mil]

15

15

[Mil]

1.5

1.5

[g]

390

2 x A4

2 x A4

[mm2]
[mm2]

14
14

0.52.5
0.752.5

[mm2]
[mm2]

1.56
1.56

0.52.5
0.752.5

Aux. Contact
(Frontmounted)

6A

Mechanical Life
Electrical Life

AC-15
(240V,
3A)

Weight

AC Op.
Mechanism

Terminal Cross-Sections
Terminal Type
Terminal Size per IEC 947-1
1 ConFlexible
ductor
with Wire
2 ConEnd Ferrule
ductor
1 Conductor
Solid
2 Conductor
Max. Wire Size per UL/CSA
Tightening Torque
Tightening Torque

[AWG]

1610

1814

[lb-in]
[Nm]

8.922
12.5

8.913.3
11.5

Switching DC Loads
L

/R < 1ms, Resistive Loads

/R < 15ms, Inductive Loads


with economy resistor in
series

DC-13 IEC 947, EN 60947,


Solenoids and contactors

Mechanically
Linked
Contacts

24V

12A

12A

48V
110V

9A
3.5A

9A
3.5A

220V
440V

0.55A
0.2A

0.55A
0.2A

24V
48V

9A
5A

9A
5A

110V
220V

2A
0.4A

2A
0.4A

440V

0.16A

0.16A

24V

5A

5A

48V
125V

2A
0.7A

2A
0.7A

220V
440V

0.25A
0.12A

0.25A
0.12A

Yes
Yes
Location State of N.C. Contacts if N.O. contact welds
of welded
Front
Left side
N.O. con- Main
Right side aux.
aux.
aux.
tacts
Main
Open
Front aux. Open

Open
Open

Open
Open

Open
Open

Left side
aux.

Open

Open

Open

Open

Right side
Open
aux.

Open

Open

Open

Aux.Contact
(Side-mounted)
Contact Ratings IEC
AC-15 (solenoids, contactors) at
rated voltage
IEC 947, EN 60947
AC-1 (Non-inductive, or
slightly inductive loads,
resistance furnaces)
IEC 947, EN 60947

400V

480V/500V

40C

Ith

10A

60C

Ith

6A

DC-13 IEC 947, EN 60947, Solenoids and contactors

Max. Wire Size per UL/CSA


Tightening Torque
Tightening Torque

240V

24V

3A

48V

1.5A

110V
220V

0.6A
0.3A

440V
[AWG]

0.2A
1814

[lb-in]
[Nm]

8.913.3
11.5

If the accessory is a pneumatic timer or latch, there is no positive


guidance; the accessory contacts are independent
Defined in IEC 947-5-1 annex L. Positive guidance is a relationship
between contacts of opposite types (i.e., N.O. and N.C.).

17

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Control Relay Specifications, Continued
General

Control Circuit
Cat. No. 700S-CF
AC 50/60 Hz
DC

Cat. No. 700S-CF


Rated Insulation Voltage Ui

Operating Voltage
Pickup

[x U s]

0.851.1

Dropout

[x Us]

0.30.6

IEC
UL; CSA

690V
600V

Pickup

[x U s]

0.81.1

Rated Impulse Strength Uimp

8 kV

Dropout

[x Us]

0.10.6

High Test Voltage


1 minute (per IEC 947-4)

Coil Consumption
AC 50/60 Hz

Inrush

[VA/W]

70/50

Rated Voltage Ue

Seal

[VA/W]

8/2.6

DC

Inrush/Seal

[W]

6.75

AC
DC

[ms]
[ms]

1530
1060

Operating Times
AC- 50/60 Hz
DC

Pickup Time
Dropout Time
Pickup Time
Dropout Time

[ms]
[ms]

4070
715

For 9V DC, code ZR, use operating voltage 0.651.3 x Us.


For 24V DC, code ZJ or DJ, use operating voltage 0.71.25 x Us.

115, 230, 400, 500, 690V


24, 48, 110, 220, 440V

Short-Circuit Protection IEC 158-1


Fuse
Rated Frequency
Ambient Temperature
Storage
Operation at nominal current
Conditioned 15% current reduction
after AC-1 at > 60C
Corrosion Resistance
Altitude
Type of Protection
IP 2LX (IEC 529 and DIN 40050)
Finger Protection

18

2500V

50/60 Hz, DC
55+80 C (67176 F)
25+60 C (13140 F)
25+70 C (13158 F)
humid-alternating climate,
cyclic, per IEC 68-2-30 and
DIN 50 016, 56 cycles
2000m above mean sea level,
per IEC 947-4
in connected state
safe from touch by fingers and
back of hand per VDE 0106,
Part 100

Bulletin 100S-C/104S-C/700S-CF

Safety Contactors and Control Relays


Approximate Dimensions
Contactors, Control Relays, and Accessories
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Mounting
Position

c2

AC Contactors and Control Relays

c1
c

DC Contactors and Control Relays

AC Contactors and Control Relays


Cat. No.

c1

c2

d1

d2

100S-C09100S-C23, 700S-CF

45
(1-25/32)

81
(3-3/16)

119.5
(4-3/4)

114.5
(4-43/64)

6
(1/4)

2 - 4.5
(2 - 3/16)

60
(2-23/64)

35
(1-25/64)

45
(1-25/32)
54
(2-1/8)

81
(3-3/16)
81
(3-3/16)

136.5
(5-37/64)
139.5
(5-11/16)

131.6
(5-11/32)
134.6
(5-29/64)

6.5
(17/64)
6.5
(17/64)

2 - 4.5
(2 - 3/16)
2 - 4.5
(2 - 3/16)

60
(2-23/64)
60
(2-23/64)

35
(1-25/64)
45
(1-25/32)

72
(2-53/64)

122
(4-51/64)

156
(6-11/32)

150.5
(6-1/8)

8.5
(21/64)

4 - 5.4
(4 - 7/32)

100
(3-15/16)

55
(2-11/64)

100S-C30, 100S-C37
100S-C43
100S-C60100S-C85

DC Contactors and Control Relays


Cat. No.

c1

c2

d1

d2

100S-C09Z...100S-C16Z,
700S-CF

45
(1-25/32)

81
(3-3/16)

145.5
(5-49/64)

140.5
(5-37/64)

6
(1/4)

2 - 4.5
(2 -3/16)

60
(2-23/64)

35
(1-25/64)

45
(1-25/32)
45
(1-25/32)

81
(3-3/16)
81
(3-3/16)

162.5
(6-7/16)
180.5
(7-5/32)

158
(6-1/4)
175.5
(6-61/64)

6
(1/4)
6.5
(17/64)

2 - 4.5
(2 -3/16)
2 - 4.5
(2 -3/16)

60
(2-23/64)
60
(2-23/64)

35
(1-25/64)
35
(1-25/64)

100S-C43Z

54
(2-1/8)

81
(3-3/16)

183.5
(7-17/64)

179
(7-3/32)

6.5
(17/64)

2 - 4.5
(2 -3/16)

60
(2-23/64)

45
(1-25/32)

100S-C60D...100S-C85D

72
(2-53/64)

122
(4-51/64)

156
(6-11/32)

150.5
(6-1/8)

8.5
(21/64)

4 - 5.4
(4 -7/32)

100
(3-15/16)

55
(2-11/64)

100S-C23Z
100S-C30...100S-C37

Accessories
Contactors with

mm

(inches)

a+9
b + 24

(a + 23/64)
(b + 15/16)

on side of contactor

a+9

(a + 23/64)

on coil terminal side


on coil terminal side

b+9
b+3

(b + 23/64)
(b + 1/8)

label sheet
marking tag sheet with clear cover
marking tag adapter for System V4 / V5
marking tag adapter for System Bul. 1492W

+0
+0
+ 5.5
+ 5.5

(+ 0)
(+ 0)
(+ 7/32)
(+ 7/32)

Auxiliary contact block for side mounting


Electronic Timing Module

1- or 2-pole
on coil terminal side

Mechanical Interlock
Interface Module
Surge Suppressor
Labeling with

19

Terminal Markings
3-Pole Safety Contactors
51 61 71 81

51 61 71 81

11 21 31 41

52 62 72 82

52 62 72 82

12 22 32 42

21

13

22

14

100S-C0905C...C2305C

100S-C0914C...C2314C

100S-C3004C...C8504C

4-Pole Safety Contactors


11 21 31 41

11 21 31 41

12 22 32 42

12 22 32 42

R7

R8

100S-C09404C...C23404C

100S-C09304C...C23304C

Reversing Safety Contactors


51 61 71 81

21

51 61 71 81

11 21 31 41

21

11 21 31 41

52 62 72 82

22

52 62 72 82

12 22 32 42

22

12 22 32 42

13

21

13

21

14

22

14

22

104S-C09210C...C23210C

104S-C30010C...C85010C

Publication 100S-SG001A-US-P - November 1999