Up to 690 Vac
42 kA to 100 kA Icu
Product Focus
800 to 6300 A
IEC 60947-2
Proven Performance
Expanded Capabilities
High Withstand Ratings
Safety first
Through-the-door design
All controls, indicators, and the trip unit are visible and
can be safely accessed without opening the
compartment door.
Common height and depth
All three Magnum frame sizes have the same identical
height and depth to facilitate standardised designs in
low voltage assemblies.
1
2
3
4
11
10
12
13
14
contacts.
3 Trip flag (optional).
(open or closed).
7 Digitrip RMS trip unit.
8 Push On to close breaker button.
(charged or discharged).
15
device.
15 Colour-coded breaker position
indicators.
11 Drawout cassette.
1
10
11
2
12
3
13
14
10 Secondary contacts.
The right choice for low voltage assemblies anywhere in the world
Finger-proof (IP20)
secondary points with easy
access for customer wiring.
Through-the-window accessories
Internal Accessories
Auxiliary switch - Provides the capability to remotely
indicate if the breaker is open or closed. Up to six N/O
and six N/C auxiliary contacts are available for
customer use.
Overcurrent trip switch (bell alarm) - A set of N/O and N/C
contacts that indicate when a breaker trips.
Electrical operator - An electric motor, internally mounted
in the circuit breaker, that charges the closing springs
automatically, facilitating remote or local closing.
Connect
Test
Disconnect
Viewable through-the-window
electrical accessories are
identically sized, yet keyed for
error-free mounting.
Magnum modular
design allows customers
to mount accessories in
the field.
Digitrip 520/520M
Long and short delay curves
Digitrip 520i/520Mi
Ground curve
7000
4000
4000
1000
1000
60
60
10
10
Time in seconds
7000
Time in seconds
0.1
0.1
0.01
0.01
0.5
10
20
50 100
Current in multiples
of long delay setting Ir
0.05 0.1
0.2
10
Current in multiples
of rating In
Digitrip 520 LI
Ampere range
Interrupting rating at 690 V
Rms sensing
200 A - 3200 A
40 through 100 kA
Yes
200 A - 6300 A
40 through 100 kA
Yes
200 A - 6300 A
40 through 100 kA
Yes
200 A - 6300 A
40 through 100 kA
Yes
200 A - 6300 A
40 through 100 kA
Yes
LI
Yes
Yes
0.4 - 1.0 x (In)
2 - 24 seconds
No
Yes
No
No
No
No
No
200 - 1000% x (In)
and M1
Yes
No
No
No
No
No
No
No
Yes
LSI, LSIG
Yes
Yes
0.4 - 1.0 x (In)
2 - 24 seconds
No
Yes
No
200 - 1000% x (Ir)
and M1
100 - 500 ms
100 - 500 ms
Yes
200 - 1000% x (In)
and M1
Yes
Yes
No
25 - 100% x (In)
100 - 500 ms
100 - 500 ms
Yes
Yes
Model LSI only
Yes
No
No
No
Yes
No
No
No
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
4 char. LCD
Yes
No
No
No
No
No
No
No
No
4 char. LCD
Yes
No
No
No
No
No
No
No
No
24 char. LED
Yes +/- 1%
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Type
No
No
No
INCOM/PowerNet
Power supply
N/A
N/A
PRM in breaker
PRM in breaker
INCOM/PowerNet/
Trip Link
PRM in breaker 2)
No
No
Test set
No
No
No
Test set
No
No
No
Test set
No
No
No
Test set
No
Yes
Yes
Integral and test set
Yes
Long
delay
protection
(L)
Short
delay
protection
(S)
Ordering options
Fixed rate plug (In)
Overtemperature trip
Long delay pickup
Long delay time I2t at 6 x Ir
Long delay time I4t
Long delay thermal memory
High load alarm
Short delay pickup
Additional features
Trip log (3 events)
Electronic operations counter
Testing method 1)
Waveform capture
Characteristics table
Magnum characteristics,
dimensions and weights
Magnum frame
1) 2)
Narrow frame
Standard frame
Double-wide frame
(MWN)
(MWI)
(MWI)
MWN4
800
1000
1250
~
~
MWN5
800
1000
1250
1600
2000
MWN6
800
1000
1250
1600
2000
MWI6
~
~
~
~
2000
2500
3200
65/65
65/50
30
50
MWI8
800
1000
1250
1600
2000
2500
3200
85/85
85/65
30
50
MWIC
800
1000
1250
1600
2000
2500
3200
100/85 4)
85/65
30
50
MWI6
4000
MWI4
4000
5000
6300
MWIC
4000
5000
6300
65/65
65/40
30
50
MWI6
800
1000
1250
1600
~
~
~
65/65
65/~
30
50
40/40
40/~
30
50
50/50
50/~ 3)
30
50
65/65
65/~
40
70
85/85
85/~
40
70
100/100
100/~
40
70
425.7
371.9
317.7
413
524.3
474.2
336
431.3
425.7
371.9
317.7
413
524.3
474.2
336
431.3
425.7
371.9
317.7
413
524.3
474.2
336
431.3
425.7
371.9
410.2
537.2
524.3
474.2
431.8
558.8
425.7
371.9
410.2
537.2
524.3
474.2
431.8
558.8
425.7
371.9
410.2
537.2
524.3
474.2
431.8
558.8
425.7
371.9
410.2
537.2
524.3
474.2
431.8
558.8
425.7
371.9
886.5
1120
524.3
474.2
909
1036
425.7
371.9
886.5
1120
524.3
474.2
909
1036
425.7
371.9
886.5
1120
524.3
474.2
909
1036
43
54
48
62
28
32
43
54
48
62
28
32
43
54
48
62
28
32
58 - 68
72 - 86
70 - 86
88 - 112
53 - 56
55 - 68
58 - 68
72 - 86
70 - 86
88 - 112
53 - 56
55 - 68
58 - 68
72 - 86
70 - 86
88 - 112
53 - 56
55 - 68
58 - 68
72 - 86
70 - 86
88 - 112
53 - 56
55 - 68
107.5
144.7
138.8
166
90.3
113.4
125.2
163.3
157.4
200
96.2
120.7
125.2
163.3
157.4
200
96.2
120.7
40/40
40/~
to 1250
40
~
50/50
50/~ 3)
to 2000
50
~
65/65
65/40
to 2000
50
~
65/65
65/~
to 1600
50
~
~
~
~
65/65
65/~
to 4000
100
~
85/85
85/65
to 2000
59
2500 &
3200
80
7)
65/65
65/50
2000
50
2500 &
3200
80
85/85
85/~
to 4000
100
5000 &
6000
157
100/100
100/~
to 4000
100
5000 &
6000
157
20
20
20
20
20
20
20
15
15
15
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
2.5
2.5
2.5
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
IP20
IP54
2)
3)
4)
5)
6)
7)
8)
7)
Circuit breakers equipped with integral trip units have a making current release set to trip instantaneously at 25 x In peak current to prevent closing
on a fault current exceeding that magnitude.
Magnum ACBs carry an IT rating at 440 Vac per IEC 60947-2 Annex H. Contact Eaton for 690 Vac IT applications.
The Icw 1 sec/3 sec rating is 50/30 kA for 2000 A MWN 50 kA breaker.
Standard frame circuit breakers rated 100 kA are equipped with a high instantaneous trip set to protect above 85 kArms. Icu is 100 kA and Ics is 85 kA at 440 Vac.
Icu and Ics are 85 kA at 690 Vac.
The approximate weights and dimensions shown are based on horizontal terminals.
Non-automatic switches should be applied with a suitable external overcurrent device with very fast instantaneous trip to protect above the published close and latch rating.
If such a device is not used, a selective circuit breaker with trip unit and making current release should be used.
The maximum available instantaneous interrupting rating for the standard frame non-automatic switch is 85 kA.
Circuit breaker Icm values are equal to Icu times a constant. Value of the constant is either 2.1 or 2.2 as given in IEC 60947-2.
9
Dimensions (mm)
Fixed design
800 - 2000 A narrow frame
340
318
257
133
32
78
417
352
391
293
340
133
32
78
352
414
417
391
865
133
257
32
78
417
352
869
10
391
Withdrawable design
800 - 2000 A narrow frame
86
52
54
401
511
318
247
189
173
122
106
477
19
48
61
336 (3-pole)
431 (4-pole)
474
458
434
432
411
176
129
118
45
559
482
519
431
435
400
395
434
474
458
434
432
411
176
129
118
45
559
482
519
431
435
400
395
434
11
Eaton Corporation is a diversified power management company ranked among the largest Fortune 500
companies. The electrical group is Eaton's largest division and is a global leader in electrical control,
power distribution, power quality, automation, and monitoring products and services. Eaton's global
electrical brands, including Cutler-Hammer, MGE Office Protection Systems, Powerware, Holec,
MEM, Santak and Moeller, provide customer-driven PowerChain Management solutions to serve the
power system needs of the industrial, institutional, government, utility, commercial, residential, IT,
mission critical and OEM markets worldwide.
PowerChain Management solutions help enterprises achieve a competitive advantage through proactive
management of the power system as a strategic, integrated asset throughout its life cycle. With Eaton's
distribution, generation and power quality equipment; full-scale engineering services; and information
management systems, the power system is positioned to deliver powerful results: greater reliability,
operating cost efficiencies, effective use of capital, enhanced safety, and risk mitigation.
www.eatonelectrical.com