You are on page 1of 3

TJHU

Axial Jet Fans


Application

Jet fans to induce air movement in enclosed car parking, tunnels and large spaces.
TJHU: for ventilation and one off emergency smoke operation at F400, F300.
TJFU: for ventilation only.
0370-CPD-

Description

0370-CPD-1422

Diameters: 315, 355, 400 mm.


Uni-direction impeller for airflow in forward direction, Form B.
Impeller with 7 blades in cast aluminum alloy in accordance with EN 1706,
and balanced in accordance with ISO 14694: G 6.3.
Fan duct and 2 mounting feet are steel in accordance with EN 10130-99, and
hot dip galvanized in accordance with EN 1461: 1999.
Fan external electrical terminal box.
Two circular sound attenuators in galvanised sheet steel, with flared inlet and
acoustic media.
Supplied with inlet and outlet steel guard.
Complete fan assembly independently tested and approved in accordance
with EN12101-3 at F400120 min, F300-120 min.

Motors
IEC 80, 90 frame. 3phase/380V/60Hz. IP55.
Class H at F400, F300.
Two speed 2/4 pole Dalhander winding.
Ambient temperature range -20C to +40C

On request
External terminal box
for ease of connection

Version with single speed 2 pole motor.


Version with inlet guard and steel discharge deflector for uni-direction airflow.
Version with factory fitted IP65 isolator in place of fan electrical terminal box.
Isolator also available as an accessory for use with standard terminal box fan.
External painting to RAL colour.

Two protection guards on fan


inlet and outlet

APPLICATIONS
Optional deflector on outlet
for uni-direction

Optional electrical Isolator


fitted to fan for security,
or as accessory.

Fan reference
TJHU
1

2/4
2

315
3

C/I
4

1.1 /0.25kW
5

F300
6

380V
7

60Hz
8

1. Fan type
2. Motor speed (poles)
3. Nominal diameter
4. C= terminal box (standard). I=isolator (optional)
5. Motor power in kW
6. Emergency operation designation
7. Nominal electrical suppy (Volts)
8. Frequency (Hz)

Technical specifications for information only. Soler & Palau Sistemas de Ventilacin S.L.U, reserves the right to change data without prior notice

TJHU

Axial Jet Fans


Technical characteristics
Model

Speed

Speed

Thrust

Airflow

Air velocity

Motor*

FLC*

(rpm)

(N)

(m3/h)

(m/s)

(kW)

(A)

(poles)

TJHU/2-315-C

3265

TJHU/2-355-C

3400

TJHU/2-400-C

3450

UNI-DIRECTION - 1 speed 2 POLE


33
5300
19
57

7800

22

Sound
Weight
level**
Form B***
(Kg)
(LpA)

1.1

2.4

67

56

1.5

3.4

70

75

6.6

75

88

TJHU/2/4-315-C

2/4

89
11000
24
UNI-DIRECTION - 2 speed 2/4 POLE
3290/1620
33/8
5300
19/9

1.1/0.25

2.6/0.8

67/50

56

TJHU/2/4-355-C

2/4

3370/1670

57/14

7800

22/11

1.5/0.37

3.5/1.2

70/53

75

TJHU/2/4-400-C

2/4

3460/1715

89/22

11000

24/12

3.1/0.8

7.1/2.5

75/58

88

*May depend on motor used. **Sound pressure at 3m, hemispherical propagation, in free field conditions, for comparison. *** Form B: Impeller over Motor (uni-direction)

Dimensions (mm)

C/C: Dimension with terminal box


C/I: Dimension with isolator

Model

C/C

C/I

315

310

405

236

279

385

485

397

L1

1754

1797

355

310

445

259

302

425

525

437

1754

1797

400

310

506

283

326

486

586

498

1754

1797

Technical specifications for information only. Soler & Palau Sistemas de Ventilacin S.L.U, reserves the right to change data without prior notice

TJHU

Axial Jet Fans

Acoustic characteristics
Sound power levels LwA ref 1pW. Tested in accordance with ISO 13347:2004
2 pole

4 pole

Form B

63

125

250

500

1k

2k

4k

8k

LwA

315
355
400

66
61
72

66
69
74

68
72
73

79
82
82

78
82
86

79
81
87

71
74
80

66
68
75

84
87
91

Form B

63

125

250

500

1k

2k

4k

8k

LwA

315
355
400

45
48
51

54
58
62

58
62
65

61
65
70

61
67
67

54
58
64

50
54
60

43
47
52

66
71
74

Form B: air direction Impeller over Motor

Wiring diagrams
1 SPEED MOTOR

2 SPEED MOTOR (DALHANDER WINDING)

Technical specifications for information only. Soler & Palau Sistemas de Ventilacin S.L.U, reserves the right to change data without prior notice