You are on page 1of 5

3516B Generator Set ZAP00001-UP(SEBP4057 - 11)/Basic Search

Page 1 of 5

Shutdown SIS
Previous Screen
Product: GENERATOR SET
Model: 3516B GENERATOR SET ZAP
Configuration: 3516B Generator Set ZAP00001-UP

Operation and Maintenance Manual


3500 Generator Sets
Media Number -SEBU7789-06

Publication Date -01/08/2011

Date Updated -08/08/2011

i02324949

Parallel Operation
SMCS - 4450

Initial Start-Up
Preparing a generator for parallel operation requires special attention. Before you attempt to parallel
units for the first time, check all the units for the following three conditions.
same phase rotation
same alternating current frequency
same voltage adjustment
1. Check the phase rotation.
Units that operate in parallel must have the same phase rotation. There are two methods that
may be used in order to determine if the incoming unit and the unit that is on-line have the same
phase rotation. These methods are listed below:
using a phase rotation meter
using a set of three light bulbs
Use the procedure below to determine the proper phase rotation by using three light bulbs.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

6/12/2012

3516B Generator Set ZAP00001-UP(SEBP4057 - 11)/Basic Search

Illustration 1

Page 2 of 5

g00695380

When servicing or repairing electric power generation equipment:


Make sure the unit is off-line (disconnected from utility and/or other
generators power service), and either locked out or tagged DO NOT
OPERATE. Remove all fuses.

a. Connect the light bulbs with rated voltage between the generator leads and the
corresponding line phase. For example, connect terminal 1 to line 1 across the open
circuit breaker.
b. Start the units that will be in operating in parallel. Bring the units up to speed. As the
units approach the same speed, the lights will start to blink.
If the lights blink in sequence, one of the units is connected backward. In order to
correct the problem, stop the units. Remove generator leads 1 and 3 at the circuit
breaker. Exchange these generator leads. This reverses the direction of phase
rotation. Terminal 2 should always be connected to line 2. Go to 5.
Both generators have the same phase rotation when the lights blink in unison. The
first condition of "Initial Start-Up" has been met.
2. Adjust the frequency.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

6/12/2012

3516B Generator Set ZAP00001-UP(SEBP4057 - 11)/Basic Search

Page 3 of 5

The units that will be operating in parallel must operate at the same speed. Speed is
proportional to the alternating current frequency.
a. Allow each electric set to run under load for about 30 minutes.
b. Adjust the control in order to give the rated frequency at full load.
c. Remove the load and check the high idle speed. The high idle speed should be
approximately 2 to 5 percent above full load speed for generators that are equipped with
droop. If these speeds can not be obtained, contact your Caterpillar dealer.
d. For the most consistent results, repeat 2.b and 2.c until the second condition of "Initial
Start-Up" has been met.
3. Adjust the voltage.The potentiometers should be at the initial settings. Refer to Operation
and Maintenance Manual, "Voltage Regulators".
Note: Make sure that the speed droop is identical for all of the engines before
adjustments are made to the generator.
a. Preset the unit for parallel operation by connecting the current transformer to S1 and S2
of the connector J2. Set potentiometer P1 for quadrature droop in the center position.
Apply the rated load. The voltage should drop for 2% to 3%. Switch the positions of the
two incoming secondary wires of the current transformer if the voltage increases.
b. The no-load voltages should be identical for all the generators that are operating in
parallel. Connect the generators in parallel. Try to obtain a 0 kW power exchange by
adjusting the speed of the generator. Try to minimize the circulating currents between
generators by altering the voltage setting with potentiometer P2 or Rhe on one of the
generators.
Note: Do not change the voltage settings after this step.
c. Apply the available load. The setting is correct only if a reactive load is available.
Equalize the Kilowatts or divide the rated power of the units proportionally by altering
the speed. Alter the quadrature droop potentiometer (P1) in order to equalize the currents
or divide the currents.

Starting Multiple Units


Use the procedure for starting single units in order to start multiple units. Refer to Operation Section,
"Single Unit Operation".

Paralleling Multiple Units


Units may be paralleled at no load. Units may also be paralleled with units under load. After the initial
conditions for start-up are satisfied, verify for the following requirements:
Generators must have voltage droop compensation or cross current compensation.
1. Start the unit which will be paralleled.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

6/12/2012

3516B Generator Set ZAP00001-UP(SEBP4057 - 11)/Basic Search

Page 4 of 5

2. Turn on the synchronizer lights.


3. After the engine has run a few minutes, bring the engine up to synchronous speed. This means
that the frequency of the incoming unit will be the same frequency as the unit that is on-line.
The synchronizing lights will begin to blink.
Note: The frequency of the incoming unit should be slightly greater than the line frequency.
This will allow the incoming unit to assume some of the load instead of adding to the system
load.
4. By using the control, adjust the engine speed until the lights blink very slowly.
5. The lights are off when the voltages of the two units are in-phase. At this point, very quickly
close the breaker while the lights are out.
6. Use the controls in order to share kW load between engines.
7. Generator temperature will be stabilized in approximately one hour. After the generator
temperature has been stabilized, adjust the voltage droop rheostat of each generator. This will
share the reactive load and this will limit the circulating currents. Less droop increases the
reactive current that is carried by the generator. Adjusting the voltage droop rheostat in a
counterclockwise direction will decrease the droop. Adjusting the voltage droop rheostat in a
clockwise direction will increase droop.

Load Division and Speed Droop (If Equipped)


Once two units have been paralleled, the unit's share of the kW load is determined by the control
setting. If two units of the same capacity and the same characteristics have the same control settings,
the units will share the load equally. The total load must not exceed the capacity of the one engine.
In order to transfer the load from one engine to another engine, use the following procedure:
1. Increase the speed control of one unit in order to increase the load.
2. Reduce the speed control of the other unit in order to decrease the load on that unit.
3. Raise the speed control or lower the speed control of both units in order to change system
frequency.

Stopping
In order to remove a generator from the line, perform the following procedure.
1. Check the load. The load must be less than the rated capacity of the remaining units.
2. Be sure that the neutral of one of the remaining units is grounded.
3. Remove the load from the outgoing unit. See the Parallel Operation, "Load Division - Speed
Droop". The amperage may never go to zero due to circulating currents.
4. Open the circuit breaker.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

6/12/2012

3516B Generator Set ZAP00001-UP(SEBP4057 - 11)/Basic Search

Page 5 of 5

5. Allow the engine to cool for five minutes.


6. Stop the engine.

Circulating Current
s
Understanding the circulating currents becomes very important when you parallel the units. These
circulating currents are flowing between generators in parallel operation. The circulating currents are
caused by voltage differences between the generators. The circulating currents are not doing useful
work. The amount of the circulating current can be determined by subtracting the amperage which is
going to the load from the total generator amperage.
The circulating current may be as high as 25 percent of rated amperes with cold generator sets. Such
current may not even be considered harmful. The total generator current should not exceed the
amperage rating.
As the generators warm, the circulating currents will decrease. The ammeter readings should decrease
slightly, but the voltage meter readings should remain constant.
Copyright 1993 - 2012 Caterpillar Inc.

Tue Jun 12 12:39:33 UTC+0500 2012

All Rights Reserved.


Private Network For SIS Licensees.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe...

6/12/2012

You might also like