You are on page 1of 8

<Quoted from Contract>

The comments and/or approval of drawing, documents and inspection do not relieve Supplier from his obligation to
comply with contract specification. Any specification deviation found subsequent to approval shall be corrected to the
satisfaction of the Owner under Supplier's sole responsibility.
ENGINEER'S STAMP

CONTRACTOR'S STAMP

APPROVED
2015.04.20

FOR REVIEW

RH

JL

25/09/2014

FOR REVIEW

RH

JL

24/09/2014

FOR REVIEW

RH

JL

14/05/2014

FOR REVIEW

RH

JL

28/02/2014

FOR REVIEW

RH

JL

28/01/2014

RH

JL

31/10/2013

FOR REVIEW

REV.

DESCRIPTION

PREPARED CHECKED

DATE

MINERA ESCONDIDA Ltda


ESCONDIDA WATER SUPPLY PROJECT

CONTRACTOR

Project No
LOCATION
W13018
Escondida
SCALE

TITLE

PUMP DATA SHEET WITH EXPECTED PUMP PERFORMANCE CURVE ETC. FOR
FILTER BACKWASH PUMP
DOCUMENT No
REV. 5
W13018-YT01-GDF-457110

SUBCONTRACTOR
SHEET 1 OF 8

Pump size & type


Based on curve no.
Number of stages
Customer
Item number
Service
Flowserve Ref
Date

:
:
:
:
:

Doosan Heavy Industry


514162-PVE-03501/0203 & PVE-03601/02/03

Filter Back Wash


82382 Version 1
May 13, 2014

Capacity
Head
Specific gravity
Pump speed
Test tolerance

: 20SPM
: EC-2275
: 1

: 1325.0 m3/h
: 22.00 m
: 1.080
: 1300 rpm
: Hydraulic Institute Standard 14.6-2011 Table 14.6.3.4 Acceptance Grade 1U

CURVES ARE APPROXIMATE, PUMP IS GUARANTEED FOR ONE SET OF CONDITIONS; CAPACITY, HEAD, AND EFFICIENCY.

Bowl performance shown below is corrected for materials, viscosity and construction.

Bowl head of 22.38 m corresponds with 22.0 m head at low liquid level adjusted for elevation and friction losses.

Copyright 2009 Flowserve. All rights reserved.

FlowSelex v2.2

1 of 6

Hydraulic Datasheet
Customer
Customer reference
Item number
Service

Pump / Stages
Based on curve no.
Flowserve reference
Date

: Doosan Heavy Industry


:
: 514162-PVE-03501/02/03 & PVE-03601/02/03
: Filter Back Wash
Operating Conditions

Capacity
Water capacity (CQ=1.00)
Normal capacity
Total Developed Head
Water head
(CH=1.00)
NPSH available (NPSHa)
NPSHa less NPSH margin
Maximum suction pressure
Rated suction pressure

20SPM
EC-2275
82382 Version 1
May 13, 2014

/1

Materials / Specification

: 1325.0 m3/h
: 1325.0 m3/h
: : 22.00 m
: 22.00 m
: Ample
: : Not applicable
: Not applicable

Material column code

: SS
Other Requirements

Hydraulic selection : No specification


Construction : No specification
Test tolerance : Hydraulic Institute Standard 14.6-2011 Table 14.6.3.4
Acceptance Grade 1U
Speed Set : 1300 rpm
Driver Sizing : API 610
Noise Level: 85 dBA @ 1m**
Estimated wire-to-water efficiency: 76.8% *

Liquid
Liquid type
Liquid description
Temperature / Spec. Gravity
Viscosity / Vapor pressure

:
:
:
:

: Sea/salt water
:
: 23 C
/ 1.080
: 1.4 cP
/ -

Performance
Pump speed
: 1300 rpm
NPSH required (NPSHr)
: 5.6 m
Minimum submergence
: 1168.4 mm
Hydraulic power
: 85.6 kW
Efficiency (CE=1.00)
: 82.7 %
Power: (Rated / Max)
: 104 kW
/ 108 kW
Driver power
: 112 kW / 152 hp
Bowl Pressure
: 3.6 barg
(based on shut off and Rated specific gravity @ Cut dia)
Maximum allowable
: 15.9 barg
Bowl & column hydrotest
: 4.6 barg
Dischg Head Dischg Region MAWP
: 15.9 barg

**

Impeller diameter

: Rated
/ Maximum
/ Minimum
: 316.7 mm
323.1 mm
273.0 mm
Impeller dia ratio (rated/max)
: 98.0 %
Maximum head @ rated dia
: 34.45 m
Head rise to shut off
: 53.9 %
Total head ratio (rated/max)
: 93.2 %
Flow at BEP
: 1500.3 m3/h
Flow as % of BEP
: 88.3 %
Minimum continuous flow
: 1070.6 m3/h
Suction specific speed
: 11080 US units
Rated thrust (at Rated flow)
: 18382.1 N
Maximum thrust (at Shut off flow)
: 27638.0 N
Minimum thrust (at Runout flow)
: 12400.7 N
(A negative thrust value indicates an upthrust condition)

CURVES ARE APPROXIMATE, PUMP IS GUARANTEED FOR ONE SET OF CONDITIONS; CAPACITY, HEAD, AND EFFICIENCY.
Bowl performance shown below is corrected for materials, viscosity and construction.

Bowl head of 22.38 m corresponds with 22.0 m head at low liquid level adjusted for elevation and friction losses.

Copyright 2009 Flowserve. All rights reserved.

FlowSelex v2.2

2 of 6

Construction Datasheet
Customer
Customer reference
Item number
Service

Pump
Pump/ Stages
/ Stages
: Doosan Heavy Industry
Based on curve no.
:
Flowserve reference
: 514162-PVE-03501/02/03 & PVE-03601/02/03
Date
: Filter Back Wash

: 20SPM
: EC-2275
: 82382 Version 1
: May
13,13,
2014
: May
2014

Construction
Bowl construction / lined
: Flanged - Std Wall / Unlined bowls
Impeller type
: Semi-open
Impeller fastening
: Keyed
Suction strainer
: Basket
Column construction
: Flanged
Column flange spec'n
: Taneytown Specification
Column dia (nominal)
: 406.4 mm
Column pipe length
: 5.82 m
Column section length
: 3048.0 mm (Max)
Lineshaft brg spacing
: 3048.0 mm (Max)
Lineshaft diameter
: 42.9 mm
Lineshaft coupling type
: Keyed coupling
Lineshaft bearings, qty
: 2
Lineshaft construction
: Open
Lineshaft lubrication
: Pumpage
Enclosing tube diameter
: Disch size/rating/face
: 16 inch
/ 150# ANSI
/ RF
Pump/driver coupling
: Non-spacer coupling
"HF" - Fab'd / Above grade Dschg / Square base

Driver Information
Manufacturer
Power / SF (Req' / Act')
Vertical shaft type
Hollow shaft coupling
Driver Type
Frame size / Base dia
Enclosure
Duty type
Efficiency type
Hazardous area class
Explosion 'T' rating
Volts / Phase / Hz
Amps-full load/locked rotor
Motor starting
Insulation
Temperature rise
Bearings / Lubrication
Motor mounted by
Motor Thrust rating down/up

Materials
Bowl
Impeller
Bowl bearing
Bowl shaft
Bowl wear ring
Impeller wear ring
Suction strainer
Column
Lineshaft
Lineshaft bearing
Lineshaft sleeve
Discharge head
Support plate

:
:
:
:
:
:

ASTM A890 Gr 6A
ASTM A890 Gr 6A
GREENE TWEED
ASTM A479 S32750
None supplied
None supplied

: ASTM A240 Ty 2507


: ASTM A479 S32750

/1

: WEG
: 152 hp / 112 kW
: Solid

/ 1.15

: Electric motor
:504/5T
: IP55 (TEFC)

: N/A
: N/A
: 460 V
: -

/3
/-

/ 50

: VFD
: Class F
: 90C
: 7319BECB - 6316-C3 / Grease
: Customer
: /Seal Information

Arrangement
Size
Manufacturer / Type
Material code (Man'f/API)
Gland material
Auxiliary seal device
Seal flush plan
Seal flush construction

: GREENE TWEED

:
:
:
:
:
:
:
:

Packed Box
/ Packing
/N/A
N/A
N/A

Paint and Package

Pump paint
: ASTM A240Ty2507 / EN-100025-S275JR Support plate paint
: CARBON STEEL
Shipment type

: Only CS Parts
: Yes
: Sea Worthy Packing
Additional information

Complete pump
Mounting plate
Driver(nett)

Weights (Approx.)
: 3798 Kg
: 200 Kg
: 1400 Kg

Pit / sump depth


: 7.00 m
Pump length
: 6.883 m
mounting surface to bell/strainer bottom
Available well diameter
: 2540.0 mm
Max dia below mtg surface
: 698.5 mm

Testing
Hydrostatic test
Performance test
NPSH test

: One (1) W / Five (5) UW


: One (1) W / Five (5) UW
: None
Notes

* Estimated wire-to-water efficiency: 76.8% - Reference value not considered as a guarantee point during string test.
Construction Datasheet Information subjected to changes during engineering stage.

** Entire Pumping unit including the motor, due pumps installation in the Test Bench vibration and noise measurement will be for reference only

Copyright 2009 Flowserve. All rights reserved.

FlowSelex v2.2

3 of 6

Customer
Item number
Service
Flowserve Ref
Date

:
:
:
:
:

Pump size & type


Based on curve no.
Number of stages

Doosan Heavy Industry


514162-PVE-03501/02/03 & PVE-03601/02/03

Filter Back Wash


82382 Version 1
May 13, 2014

Capacity
Head

: 1325.0 m3/h
: 22.00 m

Specific gravity
Pump speed

: 20SPM
: EC-2275
: 1

: 1.080
: 1300 rpm

CURVES ARE APPROXIMATE, PUMP IS GUARANTEED FOR ONE SET OF CONDITIONS; CAPACITY, HEAD, AND EFFICIENCY.

Copyright 2009 Flowserve. All rights reserved.

FlowSelex v2.2

5 of 6

Customer
Item number
Service
Flowserve Ref
Date

:
:
:
:
:

Doosan Heavy Industry

Pump size & type


Based on curve no.
Number of stages

514162-PVE-03501/02/03 & PVE-03601/02/03

Filter Back Wash


82382 Version 1
May 13, 2014

Capacity
Head

: 1325.0 m3/h
: 22.00 m

Specific gravity
Pump speed

: 20SPM
: EC-2275
: 1

: 1.080
: 1300 rpm

Copyright 2009 Flowserve. All rights reserved.

FlowSelex v2.2

6 of 6

Customer Service OA EMA

PERFORMANCE CURVES
Customer:

Doosan Heavy Industries

Project:

Escondida Water Supply Project

End User:

BHP Billiton

Service:

3, Back Wash Pump

Location:

Chile

FLS ref.:

ADR-13-10D41862E

Pump Type:

20SPM

Quantity:

DESIGN POINT
Discharge flow:

1325 m/h

Design TDH:

22 m

RPM:

1.300

Curve number:

Density: 1080 kg/m

200

100%
Efficiency @Design
Speed1300rpm

180

80%

Efficiency @Min.Speed
750 rpm

Efficiency @Max.
Speed1315rpm

140
120

60%

100
80

40%

EFFICIENCY [%]

160

60
40

20%

20
0

0%

100

200

300

400

500

600

700

800

900 1.000 1.100 1.200 1.300 1.400 1.500 1.600 1.700 1.800 1.900 2.000

FLOW [m3/h]
50

100

90

40

80

30
TDH [m]

60
Min.Flow1084m3/h

20

50

NPSHr [m]

70

Max.Speed1315rpm

40

ContractualDesignPoint:
1325m3/h; 22m@1300
rpm

30

Min.Speed750 rpm

10

20
Min.Flow627 m3/h

10
NPSH@1315rpm

100

200

300

400

500

600

700

800

900 1.000 1.100 1.200 1.300 1.400 1.500 1.600 1.700 1.800 1.900 2.000

FLOW [m3/h]
Curves are approximate. Pump is guaranteed for one set of conditions. Capacity and head guarantees are based on shop test. Efficiency is being
calculated at design temperature. Avoid Sustained Pump Operation Out of the following range: From 1025 to 1315 rpm.

Revision:

Date:

24,01,14

Customer Service OA EMA

PERFORMANCE CURVES
Customer:

Doosan Heavy Industries

Project:

Escondida Water Supply Project

End User:

BHP Billiton

Service:

3, Back Wash Pump

Location:

Chile

FLS ref.:

ADR-13-10D41862E

Pump Type:

20SPM

Quantity:

Discharge flow:

1325 m/h

Design TDH:

22 m

RPM:

1.300

Curve number:

DESIGN POINT
Density: 1080 kg/m

100%

PumpDesign Efficiency
82,7%@1300rpm

140
120
100

PumpDesignPower104
kW@1300 rpm

80
60

60%

40%

40
20%

20
0

0%

100

200

300

400

500

600

700

800

900

1.000 1.100 1.200 1.300 1.400 1.500 1.600 1.700 1.800

FLOW [m3/h]
50

TDH [m]

40

30

20
ContractualDesignPoint:
1325m3/h; 22m@1300rpm
10

0
0

100

200

300

400

500

600

700

800

900 1.000 1.100 1.200 1.300 1.400 1.500 1.600 1.700 1.800

FLOW [m3/h]

Curves are approximate. Pump is guaranteed for one set of conditions. Capacity and head guarantees are based on shop test.
Efficiency is being calculated at design temperature.

Revision:

Date:

27/02/2014

EFFICIENCY [%]

80%

You might also like