Contents
1.2
Since version IGS-NT-3.0 Standard firmware is the Firmware differentiated for InteliGen NT GC and
InteliGen NT BaseBox type controllers. For suitable firmware for your controller please consult this
table. Some new features are available only for InteliGen NT Basebox, InteliGen NTC Basebox,
InteliSys NT Basebox and InteliSys NTC Basebox HW (in this case there is the note included in
description of the new feature).
1.2.1
Firmware (*.mhx)
InteliGen NT GC
InteliGen NT BaseBox
InteliSys NT BaseBox
InteliGen NTC GC
IG-NT-GC-3.0
IG-NT-BB-3.0
IS-NT-3.0
For IG-NT(C) GC
IG-GC-SPTM-3.0
IG-BB-SPTM-3.0
IS-SPTM-3.0
IG-GC-SPI-3.0
IG-BB-SPI-3.0
IS-SPI-3.0
IG-GC-MINT-3.0
IG-BB-MINT-3.0
IS-MINT-3.0
IG-GC-COMBI-3.0
IG-BB-COMBI-3.0
IS-COMBI-3.0
IG-GC-COX-3.0
IG-BB-COX-3.0
IS-COX-3.0
IG-GC-MINT-Marine-3.0
IG-BB-MINT-Marine-3.0
IS-MINT-Marine-3.0
1.2.2
Archives (*.ant)
NT
InteliGen , InteliSys
NT
SW version 3.0
1.3
Page 2 of 8
Description
NT
InteliGen , InteliSys
NT
SW version 3.0
1.4
Page 3 of 8
Upgrade Guidelines
Since the version 3.0 comes with major changes and bug repairs, update is recommended for
all users. Please, take a minute and go through all the New features and Bug repairs and consider
the upgrade to the latest version.
1.5
1.5.1
New Features
Firmware is now differentiated for InteliGen NT GC and InteliGen NT BaseBox type controllers
o
For suitable firmware for your controller please consult the table in the section 1.2.1
In InteliGen NT BaseBox, InteliGen NTC BaseBox (all archives IG-BB-xxxx-3.0) controller no longer shows the following setpoints and Logical Binary Inputs:
Comms settings:RS485(1)conv.
It is possible to define Mobus objects (registers 42873 to 43000). These objects than
can be read or written using their new register number. This can be particularly useful
for batch reading or writing or for standardizing the Modbus communication protocol.
User MODBUS definition in GenConfig can be exported to the file and then imported
to another archive which supports this function.
Command blocking is now available for groups of User Buttons 1-5, 6-8 and 9-16
separately. You can block these buttons with certain password level in GenConfig in
Commands tab.
NT
InteliGen , InteliSys
NT
SW version 3.0
Page 4 of 8
are evaluated based on the System Nominal Frequency witch is given by addition
Basic settings:Nominal freq + Basic settings:Nom frq offset.
ROCOF protection added to the SPI application and Combi application in SPI mode.
New Logical Binary Output ROCOF TRIP added. This LBO signalizes the activation of
the ROCOF protection (it remains active for 3s).
New Logical Binary Output ROCOF ACTIVE added. This LBO signalizes the activation
of the ROCOF protection in spite of the LBI Sd override is active (it remains active for
3s).
Mains protect:ROCOF df/dt range changed. New range is 0.1 Hz/s to 10.0 Hz/s. OFF
function is removed and its purpose is taken by Mains protect:ROCOF prot.
Title of the SCADA page of IB-COM or IB-NT for remote monitoring and control of the
controller changed to SCADA
0.01 MW MVAr MVA MX V Power Format added for sites with combined
HighPower/LowVoltage measurements.
Maximum number of AND/OR and XOR/RS blocks in IS-NT changed from 200 to 128
(in previous version adding more than 128 blocks was also not possible even though
200 available blocks were indicated).
In GenConfig, total counter of blocks with Binary Output and Analog Output added
(total maximum of Binary Outputs in PLC is 128 and Analog Outputs 64).
The new block offers the possibility of choice of time units of delay (s/min/h) with
resolution 0.1 for all possible units. The time accuracy for long delay has been
significantly increased.
The all 8 original PLC blocks Delay in IG-NT was replaced by new PLC blocks
Delay B. In IS-NT there was replaced only 8 blocks Delay from total number 24
available blocks.
The PLC block PID Ana C replaced the original block PID Ana
o
NT
The parameter of block Period is now possible to link to setpoint or analog value
(originally only constant was possible).
InteliGen , InteliSys
NT
SW version 3.0
New Interp. Fc B provides the possibility to define the interpolation by any analog
value available inside the controller (i.e. values, setpoints, PLC outputs etc. can be
used as inputs for the definition of the interpolation).
Interp. Fc B features two new Binary Outputs OutOfRange (Oor) and DataInvalid
(Err). Output Oor activates when the Input value is out of range of the limits given by
X1 and X2 inputs and the output of the block is saturated on the value given by
corresponding input Y1 or Y2. Output Err activates when there are invalid data on any
of the inputs of the PLC block.
Two new parameters of block, Low limit and High limit, has been added. If one of the
limits on output of regulator is reached, the integration (integral sum inside of
regulator) is stopped to prevent the saturation of regulator.
Page 5 of 8
Changed from 13 to 4.
LBI USER MASK X can be used to mask objects in InteliVision 5 and 8 and unmask
screens in InteliVision 5.
rd
Transmition of power from generator to mains: Conditions for opening of GCB has
been changed. GCB is opened when the power on gen-set is equal to level given by
setpoint Sync/Load ctrl:GCB open level at the least after delay given by setpoint
AMF settings:BreakerOverlap.
InteliGen , InteliSys
NT
SW version 3.0
Controller opens MCB and closes GCB after AMF settings:FwRet break.
For detailed description of Test on Load sequence please refer to the Reference
Guide of SPtM application.
Two new setpoints define limits for start and stop of the gen-set group and one new
setpoints defines the delay of the function (ProcessControl:Peak kVA Start,
Peak kVA Stop, PeakKVAS/S del). Adjust the delay to 0 (OFF) to disable the function.
Peak Shaving based on Apparent power can work together with Peak Shaving based
on Active power.
Conditions for running the gen-set based on Active or Apparent power are in OR
relation.
If inputs of PLC blocks Timer, Delay and Counter receive negative value, it is treated
as zero (i.e. Timer with zero time, Delay with zero delay and Counter with limit zero)
Note that Counter with limit zero activates its output after the first pulse (i.e. the same
behavior as when limit is set to 1)
Each controller can broadcast one set of eight Binary Outputs via CAN to all other
controllers on the same CAN.
Each controller can receive up to 32 sets of eight Binary Inputs via CAN (i.e. it can
also receive its own set of eight).
If the setpoint Basis settings:Gear teeth is set to zero (RPM are calculated
from frequency of generator voltage) the alarm Pickup fail is not
annunciated at all.
Page 6 of 8
Activation of any of LBI MINRUNPOWER caused starting of all gen-sets in the group
originaly. Later the gen-sets not needed for coverage of requested MinRunPower has
been stoped. The function has been changed that in case of activation of any LBI
MINRUNPOWER only the gen-sets needed for coverage of requested MinRunPower are
started.
InteliGen , InteliSys
NT
SW version 3.0
For more information about this function please refer to the new IGS-NT-PSC-1.5New features manual.
Use the LBI CLEANING to set the gen-set to cleaning mode. Under voltage and under
frequency protections are blocked in this mode (Gener protect:Gen>V BOC, Gen<V
BOC, Gen>f, Gen<f). It allows switch off the excitation of generator while the gen-set
is washed. Under voltage and under frequency protections are not active and do not
stop the engine. Yellow warning Cleaning appears in alarm list.
WARNING !!! Be aware that activation LBI Cleaning ensures only that under voltage
and under frequency protection is not active and allows gen-set to run with frequency
and voltage out of limits of protections. Activating of this input does not ensure that the
voltage excitation is really switched off. The excitation of the generator has to be
unconditionally switched off directly on the AVR of generator while the cleaning
function is in use!
Page 7 of 8
All setpoints of the controller has been moved to different part of memory (FRAM
14
allows up to 10 records). Thanks to it it is possible the cyclic rewriting of any
parameter of controller via Modbus without the risk of demage of memory.
CAUTION !!! This feature is available in HW InteliSys NTC Basebox (IS-NTC-BB)
only. The cyclic rewriting of setpoints in all other HW variations of InteliGen NT or
5
InteliSys NT can lead to the demage of memory (FLASH max. 10 records).
New fixed protection ANSI 51+51N - Earth Fault Current with IDMT reaction added
o
The original level protection with delay Earth fault current has been removed from
default archives. The protection is still possible to create as the user defined
protection in GenConfig or using the import function from older archive (FW upgrade
saves the settings of this protection).
New setpoint: Gener protect:2EthFltCurr del (the delay of reaction when the Earth
Fault Current is equal to double value of Gener protect:Nom EthFltCurr) added.
Default settings = 0 = OFF (the protection is not evaluated).
The protection type is BOC (breaker open and cooling). Alarm and history record
BOC Ieth IDMT is annunciated.
New setpoint: Gener protect:ExctLoss del (Delay of reaction of the protection) added.
Default settings = 0 = OFF (the protection is not evaluated).
The protection type is BOC (breaker open and cooling). Alarm and history record
ExctLoss is annunciated.
NT
50 records from fast history are automatically rewritten into the standard history in
case of 2nd level protection gets active only when engine is supposed to be running.
InteliGen , InteliSys
NT
SW version 3.0
Page 8 of 8
1.5.2
Repairs
Fixed bug bug when gen-set switched to Emergency MAN was not excluded from
powermanagement.
Reset of the controller during Modbus reading of the history records longer than 18 characters
prevented.
Force Value for setpoints Basic settings:ConvCoefPulse1-4 did not work properly. It was
removed.
This bug in previous versions may in some cases cause faulty message in
InteliMonitor Command currently not available even though it is available and it was
performed OK.
Fixed a bug when InternetBridge-NT did not see controller with bad configuration even though
it was possible to write new configuration into this controller via InternetBridge-NT.
Fixed a bug when SMS sender was defined by characters instead of number.
o
If the Mains protect:VS/ROCOF CBsel is set to MCB, the controller is trying to open
the MCB in spite of that the MCB control in SPI application is disabled. The bug has
been fixed. Controller does not care about the settings of Mains protect:VS/ROCOF
CBsel at all.
Alarms of type A + H indication and Off load are being viewed in alarmlist in WebSupervisor.
In some rare cases User 5 was rewritten to default name (U5) when upgrading the
firmware.
NT
This bug occurred when system password is different from default password and the
protection against breaking password is activated.
When setpoints for IP address settings (Comms settings:IP address, Net mask and
Gateway IP) are password protected and IP address is obtained automatically
(Comms settings:IP addr mode = AUTOMATIC) by IB-COM, controller gets locked
permanently displaying yellow warning PassInsertBlck. The timer of this protection
does not count down.
InteliGen , InteliSys
NT
SW version 3.0