Textile engineering Department Building was selected to install a Lightning protection
System. Building is L shaped and Hip roofed. It is a two story building with about 10 m height with roof. Four main views as Front View, Side View 1, Side View 2, and Rear View are used to present the Lightning risk areas according to the Rolling Sphere Method. Level I protection is assumed as the Rolling Sphere Radius is taken as 20m Surfaces with Direct Lightning risk are marked in Red in following Layout Drawings. Less vulnerable areas are shaded in grey.
Building Top View with Lightning Protection System
Air Termination Rods with lengths 3m
and 1.5 m are used in the design. Design is done considering the penetration depth of sphere for a distance between air-termination conductors. Distance between airtermination rods (m)
Due to the building
covered from a 16m
10 12 14 16 18 20
Sag of Rolling Sphere Level I (20m) 0.64 0.92 1.27 1.67 2.14 2.68
L shape there is a protected area
radius circle.
11 no of 1.5m Rods and 7 no of 3m rods are used in this LPS Design.