General Assumptions:
1- The calculation presented here below are for reference and guidance only,
as foam system is a pre-engineered system to come complete from the supplier.
2- The system used is an automatic sprinkler systems utilizing
foam/water sprinkler heads, integrated into a complete deluge system.
6.5
l/min.m2 =
0.16
Discharge Duration
10
min.
Foam Concentrate
Room Area =
207.3
m2
9
23.03
m2
24
Sprinklers
But for the maximum spacing between sprinklers not to exceed 3.7 m
(Refer to NFPA 16, section 4-3.7.2)
K0065-CLC-ME-02-REVA
25
Sprinklers
S08050
Date:
of
Computed by:
B.S.K
Checked by:
B.H
Approved by:
T.Q
And hence,
Flow of foam solution = Discharge Criteria x Room Area
(Refer to NFPA 16, section 4-3.3.1)
Flow of foam solution =
1348
l/min.
13480
404.4
107
Gallons
Hydraulic Calculations:
106.8 Gallons
207.6
kPa
30
psi
30
psi
1.011
=
g/ml
1.8
K0065-CLC-ME-02-REVA
8.31
m2 =
89.3548 ft2
S08050
Date:
of
Computed by:
B.S.K
Checked by:
B.H
Approved by:
T.Q
Since,
For open type sprinklers dedicated for foam/water deluge systems,
Q (gpm) = K P (psi)
And,
K=
and since we have two approaches, one is to satisfy the density and the other is to satisfy
the minimum pressure required; we'll calculate both and apply the one with the greater demand.
Q=
14.3
gpm
P=
22.7
psi
0.16
gpm/ft2
(refused)
P=
30.0
psi
Q=
16.4
gpm
Discharge Criteria
0.18
gpm/ft2
(accepted)
Therefore,
Sp. No.
Pf (psi/ft)
Pt (psi)
S1
16.40
0.500
8.00
120
3.33
57
N1-N2
32.80
1.000
28.00
120
0.41
68
N2-N3
65.60
1.500
18.00
120
0.21
72
N3-N4
98.40
2.000
9.00
120
0.11
73
N4System
outlet
98.40
2.000
15.00
120
0.11
74
K0065-CLC-ME-02-REVA
79
psi
S08050
Date:
of
Computed by:
B.S.K
Checked by:
B.H
Approved by:
T.Q
Assuming that the induction causes a pressure drop of 30 % of the required pressure:
Pt =
103
psi
Tank Capacity
123
Gal.
No. of Sprinklers =
25
Sprinklers
K0065-CLC-ME-02-REVA
103
psi
K0065
Date:
21/4/03
Sheet no.:
of
Computed by:
A.R
Checked by:
A.G
Approved by:
General Assumptions:
1- The calculation presented here below are for reference and guidance only,
as foam system is a pre-engineered system to come complete from the supplier.
2- The system used is an automatic sprinkler systems utilizing
foam/water sprinkler heads, integrated into a complete deluge system.
6.5
l/min.m2 =
0.16
Discharge Duration
10
min.
Foam Concentrate
Room Area =
38.7
m2
9.3
4.16
m2
Sprinklers
But for the maximum spacing between sprinklers not to exceed 3.7 m
(Refer to NFPA 16, section 4-3.7.2)
K0065-CLC-ME-02-REVA
Sprinklers
K0065
Date:
21/4/03
Sheet no.:
of
Computed by:
A.R
Checked by:
A.G
Approved by:
And hence,
Flow of foam solution = Discharge Criteria x Room Area
(Refer to NFPA 16, section 4-3.3.1)
Flow of foam solution =
252
l/min.
2520
75.6
20
Gallons
Hydraulic Calculations:
19.97 Gallons
207.6
kPa
30
psi
30
psi
1.011
=
g/ml
1.8
K0065-CLC-ME-02-REVA
6.3
m2 =
67.7419 ft2
K0065
Date:
21/4/03
Sheet no.:
of
Computed by:
A.R
Checked by:
A.G
Approved by:
Since,
For open type sprinklers dedicated for foam/water deluge systems,
Q (gpm) = K P (psi)
And,
K=
and since we have two approaches, one is to satisfy the density and the other is to satisfy
the minimum pressure required; we'll calculate both and apply the one with the greater demand.
Q=
10.8
gpm
P=
13.1
psi
0.16
gpm/ft2
(refused)
P=
30.0
psi
Q=
16.4
gpm
Discharge Criteria
0.24
gpm/ft2
(accepted)
Therefore,
Sp. No.
Pf (psi/ft)
Pt (psi)
S1
16.40
0.500
8.00
120
3.33
57
N1-N2
32.80
1.000
31.00
120
0.41
69
N2-N3
65.60
1.500
20.00
120
0.21
73
N3-N4
98.40
2.000
9.00
120
0.11
74
N4System
outlet
98.40
2.000
15.00
120
0.11
76
K0065-CLC-ME-02-REVA
81
psi
K0065
Date:
21/4/03
Sheet no.:
of
Computed by:
A.R
Checked by:
A.G
Approved by:
Assuming that the induction causes a pressure drop of 30 % of the required pressure:
Pt =
106
psi
Tank Capacity
31
Gal.
No. of Sprinklers =
Sprinklers
K0065-CLC-ME-02-REVA
106
psi