Twin radial blower DRG 1200

Content:
1
2
3
4
5
6
7
8

Safety advises
Usage
Construction of the DRG 1200
Function
Installation, dimension and hole pattern
Technical data
Characteristic curve
Validation

AURORA
Konrad G. Schulz GmbH & Co. KG
Tel.: 0 62 84 / 92 02-0
info@aurora-eos.com
www.aurora-eos.com
The information on this document and the copyrights are ownership of
AURORA Konrad G. Schulz GmbH & Co. KG, Joachim Schulz Str. 4, D-69427 Mudau.
Transmission or duplication of this document or the utilization of the contents are not allowed without the
agreement of AURORA Konrad G. Schulz GmbH & Co. KG otherwise it is explicit allowed. Violation will be
prosecuted. All rights of patents, industrial designs and trademarks are reserved.
Please pay attention to ISO 16016.
- we reserve the right to make technical modifications -

established: 11.01.07 KH

checked:

date/name

date/name

a) 14197 05.11.08 KH

b) 14718 18.02.09 KH

approved:
date/name
c) 17385 21.07.11 KH

d) 19627 29.01.13 KH

Technical Information

no.
912-100-0453

page
2/7

part no.:
131-601-0100 DRG 1200 12V basic version
131-602-0100 DRG 1200 24V basic version
131-601-0101 DRG 1200 12V 1-speed
131-602-0101 DRG 1200 24V 1-speed
131-601-0102 DRG 1200 12V 2-speed
131-602-0102 DRG 1200 24V 2-speed
131-601-0103 DRG 1200 12V 3-speed
131-602-0103 DRG 1200 24V 3-speed
131-602-0200 DRG 1200 24V 4-speed
other versions optionally

Safety advises

The blower is principle maintenance- and service-free. If there is maintenance work to do, make
sure it is to be carried out only when the motor is not running. In order to avoid injuries, the blower
is to be separated from the current circuit.
Make sure that maintenance work is only carried out by specialised personnel.
Do not reach into the blower and never stick objects into it.
Please do not get into contact with the resistor on the blower, if it has not completely cooled down.
Advice for installation and maintenance work:
The rules for the prevention of accidents as well as other recognises technical and labour medical
security regulations must be observed.

2.

Usage

The twin radial blower DRG 1200 is used for powerful usage in heaters, A/C units and ventilation systems.

3.

Construction of the twin radial blower DRG 1200

3.1. Parts
The twin radial blower DRG 1200 consists of the following parts
- motor, radial wheels, inner and outer rings = fan unit
- basic plate, half bowl, outer rings, motor holder
- Dropping resistor with micro-temperature-fuse MTS for versions with several speed level, clip
- housing clips, 2 screws
- cables
Optional with suppressor module
Information about the suppressor module can be seen in technical information 912-100-0398.

Technical Information

no.
912-100-0453

page
3/7

3.2. Material
The housing lower part is made out of plastic granulate polyamide PA6 GK30.
Housing upper part, motor holder, inlet rings and the wheels are made out of plastic granulate polyamide PA6, 35% glass-fibre-reinforcement.
This material is has a high temperature-resistant and because of the glass-fibre-reinforcement a high
stability. A safety data sheet about the granulate can be ordered by AURORA.
3.3. Speed control
The blower can be delivered in 1-speed-, 2-speed- or 3-speed level versions. (option: 4-speed)

Caution! The vehicle side fuse protection of 15 A at 24V or 30A at 12V has to be made
by the customer.
See circuit diagram blower.
The different blower speed are achieved using a dropping resistor. The dropping resistor is a cemented ceramic resistor.
The blower is protected from overload and a possible burning danger with a micro-temperature- fuse
(MTF) installed at the resistor.

3.4 cables
The used wires are unscreened low tensions wires with thin-wall isolation for road vehicles.
FLRY with colour marking of wires according to DIN IEC 304.

Technical Information
4.

no.
912-100-0453

page
4/7

Function

The air enters axial into the fan wheels, then the air will be radial turned round and leaves on the area
vertical to the suction direction.
Note: the blower carbon brush is a wearing part. If the carbon brushes are outworn, defective or contaminated, the motor will not run or not in a suitable way.
At any service interval (depending on usage situation) the blower function has to be checked and the
blower has to be changed, if necessary.
The check of the blower in a disconnected state:

optical check on
- physical damage on the housing, the air grille or the fan wheel
- contamination, dust, corrosion and other, that impair the function
stiffness

Then a function check is recommended


abnormal noises
uneven running
fluctuating current consumption
a decrease of air flow rate
blower dont run under voltage any more
If one or more of these impairments apply, the blower function is not given any more and the blower
has to be replaced.
During check pay attention to the necessary safety advises (chapter 1)

5.

Installation, dimensions and hole pattern

Dimensions:

Technical Information

no.
912-100-0453

page
5/7

Hole pattern:

Installation instructions:
For reliable operation of the DRG, the maximum fan bracing of 1 mm are not exceeded. Provision
shall be made for a suitably flat mounting surface.

to illustrate:

no.
912-100-0453

Technical Information

6.

Technical data

air flow volume


valid environmental temperature range
weight
double ball bearing
special air flow through the motor for
high lifetime (patented)
Vair in m3/h
Vair in cfm
Pel in W
Lp in dB(A)

speed 1
470
277
70
56

1200 m /h (736 cfm)


-40C to +85C
about 2,65 kg (basic version)

speed 2
800
471
150
68

speed 3
1250
736
307
77

power information assumes no system resistance (free-blowing)

7. Characteristic curve

page
6/7

Technical Information

no.
912-100-0453

page
7/7

8. Conducted validation tests for DRG-family (motors)


Test method

Standard basis

power measuring
Sound intensity level test

DIN IEC 651

dust test

AU standard

Short description

Validation

963-38T-0010

evaluation air characteristic curve

characteristics OK

963-38T-0011

sound intensity level free-blowing

OK

963-38T-0003

function at dust influence 1000h operation

OK

vibration test

according to DIN IEC 68


IVECO 18-2105

963-38T-0007

vibration test 30...100Hz / max 8g


10-200Hz/5g

OK
OK

salt spray test

DIN 50021

963-38T-0016

corrosion resistance 72h

OK

963-38T-0012

start-up test
over voltage 32V 60 min
polarity test
Insulation test/electric strength 500V
run behaviour with resistor

OK
OK
OK
OK

electr. Function test

balance quality

DIN ISO 1940

blower balanced

OK

temperature test storage

DIN IEC 68

storage 95h /2h

OK

temperature test operation


temperature test operation

DIN IEC 68
DIN IEC 68

72h at 85C
500h at 80C

OK

thermal shock test

IVECO 18-2105

10 cycles 2h at -30C/2h at 80C

OK

temperature cycling test

DIN IEC 68

35 cycles 8h between -40/+80C

OK

climate test humidity constant

DIN IEC 68

55C at 95% air humidity 21 days

OK

climate test humidity cyclical

DIN IEC 68

12 cycles of 24h at 10-80C / 95% humidity

OK

cold test

DIN IEC 68

function + storage at -40C/72h

OK

arctic test

MAN LH 259001

function + storage at -46C

OK

EMC tests

2006/28 EC directive

emitted interference / interference resistance

OK

electrostatic sensitive device tests

MAN LH 259 001

electrostatic discharge

OK

Continuous operation, free-blowing at 13/26V,


max. load

ca. 5000 h
laboratory conditons

lifetime test

963-38T-0008