Ref : LIPS/ABTSL/Quo/358

July 6, 2013

M/s Asa Bhanu Technical Services Ltd


Mahaveer Water Mark Building,
13th Floor (CII Building Lane)
Kondapur,Hyderabad- 500084
Kind Attn: Mr. G. SURESH MANAGER (TENDERING)
Subject: YOUR REQUIREMENT OF 132KV CTs/PTs FOR YOUR OPTCL PROJECT TENDER.

Dear Sir,
We have come to know from some reliable sources that you have some requirements of 132KV CTs/PTs for your
OPTCL Project Tender. We are pleased to submit our best & lowest OFFER for the same on the terms and
conditions as under:
PRICES
S No.

: The quoted Prices shall be FIRM.


PRODUCTS

FOR GENERATION STATION


1.
132KV 800-400-200/1 5 core CT for T/ F bay
2.
132KV 800-400-200/1 5 core CT for Bus Coupler
Bay
3.
132KV 800-400-200/1 5 core CT for Line Bay
with one 0.2s core
FOR 132KV BPPL Switching Station
4.
132KV 800-400-200/1 6 core CT for outgoing
Line Bay with one 0.2s core
5.
132KV 800-400-200/1 5 core CT for incoming
Line Bay
132KV 800-400-200/1 5 core CT for Bus Coupler
bay
FOR 132KV RAWMET EXISTING STATION
6.
132KV 800-400-200/1 5 core CT for Line Bay
with one 0.2s core
FOR 132KV BPPL Switching Station
7.
132KV PTs
FOR 132KV BPPL Switching Station bus sectionalizer bay
8.
132KV 800-400-200/1 5 core CT

QTY

Unit Rate (Rs.)

12Nos.
06Nos.

1,35,000/- each
1,35,000/- each

12Nos.

1,35,000/- each

06Nos.

1,35,000/- each

06Nos.

1,35,000/- each

03Nos.

1,35,000/- each

03Nos.

1,35,000/- each

18Nos.

1,20,000/- each

03Nos.

1,35,000/- each

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
FOR 132KV BPPL Switching Station
9.
132KV 2 core CT, Core-1: 800-400-200/1A, 0.2S
class, 50VA.
Core-2: 800-400-200/1A, 0.2S class, 50VA
10.
132/3 / 110V/3,110V/3,110V/3,3-Core,(Cl.
3P,3P,0.2,100VA),1-PH Outdoor hermetically
sealed Electro Magnetic Voltage Transformer
including Marshaling box and other as per TS
11.
132KV EMVT
EMVT details: 2 core EMVT
Core-1: 132kV/sqrt3 / 110V/sqrt3 / 110V/sqrt3, 0.2
class, 100VA.
Core-2: 132kV/sqrt3 / 110V/sqrt3 / 110V/sqrt3, 0.2
class, 100VA.
12.
13.

B-metallic Terminal Connectors


JB for CTs/PTs

06Nos.

1,35,000/- each

17Nos.

1,21,000/- each

06Nos.

1,18,000/- each

800/- each
7,500/- each

KINDLY NOTE THAT OUR OEM SUPPLIER(S) ARE ALREADY APPROVED IN OPTCL.
KINDLY NOTE THAT WE CAN SUPPLY YOU SUBSTATION COMPLETE MATERIALS UPTO
400KV. YOU ARE, THEREFORE, REQUESTED TO KINDLY SEND US COMPLETE BOQ SO TO
SEND YOU OUR BEST & COMPETITIVE OFFER ALONGWITH BEST QUALITY MATERIALS TOO.

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
COMMERCIAL TERMS
1.

PRICES: Prices quoted are net ex our works at G haziabad/Nasik/Rajasthan/Mumbai/Chennai.

2.

EXCISE DUTY: Shall be charged extra as applicable at the time of dispatch against excise gate pass. However present rate
of excise duty is 12.36%.

3.

SALES TAX: 2% against form C for dispatch outside U.P. 14.0% VAT within U.P. If form C is not available, then full rate of
tax will be applicable as per sales tax rules.

4.

DELIVERY: The delivery schedule shall be as per your delivery schedule.

5.

PAYMENTS: 30% as advance along with order; and balance 70% with full taxes and duties against Performa invoice and
prior to dispatch.

6.

VALIDITY: Offer is valid for a period of 180 days from the date of offer.

7.

PRICE ESCALATIONS: The prices have been quoted after taking into account prevailing discounted rates of the switchgear
suppliers mentioned in Bill of Material as on the date of this offer. Any subsequent increase in the rates of these switchgears
on account of price revisions or increase in taxes / duties / levies shall be charged extra to your account.

8. WARRANTEE: Our products are guaranteed for a period of 12 months against any manufacturing defects.
9.

INSPECTION & TESTING: Final testing of control panels shall be carried out at our works. We would welcome the deputation of
your authorized representative for witnessing the final testing at our works with prior appointment at mutually convenient
schedules.

10. Form C or any other applicable form shall be submitted at the time of taking delivery. If the form is not submitted then
difference of Tax amount shall be kept as a deposit until we receive the Form.
11. FREIGHT: Freight shall be charged extra as per actuals.
12. MAKE MEHRU / SCT / ITC / LAMCO
11. Painting :- The Rates quoted above are for, All ferrous parts exposed to the atmosphere shall be painted as per IS 5,

shade 631, however since these equipments are meant for Outdoor use, for rust free performance, we suggest Hot dip
galvanizing, charges for which are detailed below:For 132 kV: Rs. 5500/- per unit Extra
12. SPECIAL REMARK:The Equipments offered by MEHRU meets the Type Test requirement as per IS 2705/1992 / IEC 44-1 (For CTs) IS 3156/1992 / IEC 44-2
(For PTs), copies of the same can be provided on request

Hope you will find our offer in order and will favour us with your valued order.
Thanking you,
Yours faithfully,
FOR Lucky India Power Solutions
SHARAFAT ALI
Managing Director
Mob: +919868667484 / +919759381998
emails: info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
website: http://www.luckyindiapowersolution.com

http://www.indiamart.com/luckyindiapowersolutions/
linkedin: in.linkedin.com/in/luckyindiapowersolutions
H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
GUARANTEED TECHNICAL PARTICULARS FOR 132 KV CURRENT TRANSFORMER WITH
METERING WINDING OF ACCURACY CLASS 0.2
Ratio: 800-400-200/1-1-1-1-1A
1.

Bidders name and address

MEHRU / SCT / ITC / LAMCO

2.

MEHRU / SCT / ITC / LAMCO

3.

Name and address of the


manufacturer
Manufacturers type designation

4.

Standard applicable

: IS: 2705/1992

5.

Rated frequency (Hz)

: 50

6.

Rated voltage (KV)

: 132

7.

Rated current

7.1

Rated continuous current

: 800-400-200 Amp

7.2

Rated extended primary current

: 120% of the rated current

8.

Short time thermal current


withstand for 3 second
Dynamic current withstand

: 18.2 KA (rms)

: 650 KV (Peak)

12.

1.2/50 s impulse withstand


voltage
One minute dry and wet power
frequency withstand voltage
No. of cores per CT

13.

Transformation ratio

: 800-400-200/1-1-1-1-1A

14.

No. of secondary turns

: 400+400

9.
10.
11.

: Outdoor, Dead tank, oil filled, hermetically sealed

: 45.5 KA (Peak)

: 275 (KV rms) wet


275 (KV rms) dry
: 5

CORE :
15.
16.
17.

II

III

IV

Rated output at different taps


(VA)
Accuracy class

: -----

15

-----

-----

-----

: PS

0.2

PS

PS

PS

Knee point voltage at different


taps for all PS class cores (V)

: 800 at

------

800 at
800/1A
800 at
400/1A
400 at
200/1A

800 at
800/1A
800 at
400/1A
400 at
200/1A

800 at
800/1A
800 at
400/1A
400 at
200/1A

800/1A
800 at
400/1A
400 at
200/1A

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
18.

Secondary winding resistance


at different taps for all cores
(ohms) at 75C (max)

19.
19.1

Maximum exciting current at


(for all PS class cores)
100% KPV (Knee point
voltage) (mA)

: 4.0 at

------

4.0 at
800/1A
4.0 at
400/1A
2.0 at
200/1A

4.0 at
800/1A
4.0 at
400/1A
2.0 at
200/1A

4.0 at
800/1A
4.0 at
400/1A
2.0 at
200/1A

-------

20 on
800/1A
20 on
400/1A
20 on
200/1A
6 on
800/1A
6 on
400/1A
6 on
200/1A
5.0 on
800/1A
5.0 on
400/1A
5.0 on
200/1A
3.0 on
800/1A
3.0 on
400/1A
3.0 on
200/1A

20 on
800/1A
20 on
400/1A
20 on
200/1A
6 on
800/1A
6 on
400/1A
6 on
200/1A
5.0 on
800/1A
5.0 on
400/1A
5.0 on
200/1A
3.0 on
800/1A
3.0 on
400/1A
3.0 on
200/1A

20 on
800/1A
20 on
400/1A
20 on
200/1A
6 on
800/1A
6 on
400/1A
6 on
200/1A
5.0 on
800/1A
5.0 on
400/1A
5.0 on
200/1A
3.0 on
800/1A
3.0 on
400/1A
3.0 on
200/1A

800/1A
4.0 at
400/1A
2.0 at
200/1A

: 20 on
800/1A
20 on
400/1A
20 on
200/1A
6 on
800/1A
6 on
400/1A
6 on
200/1A
5.0 on
800/1A
5.0 on
400/1A
5.0 on
200/1A
3.0 on
800/1A
3.0 on
400/1A
3.0 on
200/1A

-------

19.2

25% KPV (Knee point voltage) :


(mA)

19.3

20% KPV (Knee point voltage) :


(mA)

19.4

10% KPV (Knee point voltage) :


(mA)

20.

: < 5 for metering core

24.

Instrument security factor at


different ratios
Radio interference voltage at
1.1/3 at 1.0 MHZ (microvolts)
Whether auxiliary CT
provided for metering winding
Corona extinction voltage (KV
rms)
Partial discharge level (pC)

25.

Total Creepage distance (mm)

: 3625

26.

Primary

26.1

No. of primary turns

: 1+1 = 2

26.2

Material and cross section of


primary

: Flexible copper bus-bar, 202 Sq. mm

21.

22.
23.

-------

-------

: 500

: Yes provided
: Not specified in ISS
: 10 (max)

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
26.3
27.
28.

Whether bar type or ring type


primary
Whether CT is suitable for
transportation horizontally
Percentage current (ratio) error
and phase displacement in
minutes at rated burden and at

: Ring Type
: Yes
Current Error/Ratio Error

II
0.35
%
0.2
%
0.2
%

III

Phase displacement

IV

II

III

IV

28.1

20% rated current

: ----

28.2

100% rated current

: 0.25

28.3

120% rated current

%
----

28.4

: Yes, 0.05 class

29.1

Accuracy class of standard CT


to be used during type test and
Routine Test (0.05 or less)
Percentage current (ratio) error
and phase displacement in
minutes at 25% rated burden
and
20% rated current

----

0.35

----

----

----

----

15

----

----

----

29.2

100% rated current

0.2

0.25
%
----

----

----

----

0.25
%
----

10

120% rated current

0.25
%
----

----

29.3

0.25
%
----

----

15

----

----

----

30.

Quantity of oil per CT


: 125 5%
(Littres/Kg)
Standard to which oil conforms : IS: 335
generally
Characteristics of oil (prior to
filling)
Breakdown voltage (KV)
: 60 (min)

29.

31.
32.
32.1
32.2

----

----

----

--- 15 --- --- ---

0.25
%
----

0.25
%
----

0.25
%
----

--- 10 --- --- ---

Current Error/Ratio Error

0.35

: 0.002 (max)

32.3

Di-electric dissipation constant


(tan-delta)
Water content (ppm)

32.4

Gas content

: As per ISS

32.5

: 0.04 (min)

32.6

Interfacial tension at 27C


(N/m)
Specific resistance

32.6.1

At 90C (ohm cm)

: 35 x 1012 (min)

32.6.2

At 27C (ohm cm)

: 1500 x 1012 (min)

--- 10 --- --- ---

Phase displacement

: 50 (max)

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
33.

Yes, through Nitrogen Gas Cushion

34.

Whether current transformers


are hermetically sealed. IF so,
how
Total weight (Kg)

450 5%

35.

Transport Weight (Kg)

500 5%

36.

36.1

Temperature rise over an


ambient temperature of 50C for
continuous operation at rated
continuous thermal current
Winding (C)

45

36.2

Oil (C)

40

36.3

45

37.1

External surface of the core,


metallic parts in contact with or
adjacent to insulation (C)
Whether CT characteristic
curves enclosed
Ratio and phase angle curves

Yes

37.2

Magnetization curves

Yes

37.3

Ratio correction factor curves

Yes

38.

Data on primary winding

38.1

Rated primary current (A)

960-480-240

38.2

No. of conductors in one turn

965 of 0.2043 mm2 each conductor

38.3

No. of turns of primary

1+1 = 2

38.4

Material of the primary


conductors
Size of the primary conductor
(Bare/Insulated) (mm)

Copper

Cross Sectional area of each


conductor (mm2)
Total cross sectional area of
primary winding (mm2)
Current density (A/mm2)

Cross sectional area is already furnished at Sl. No.


38.2. Since the primary consists of flexible conductors,
therefore, overall diameter is not applicable to us. All
related information pertaining to size is already
furnished.
0.2043 mm2 as already furnished above.

202 mm2

i)

At highest ratio

2.37

ii)

At intermediate ratio

2.17

iii)

At lowest ratio

1.18

37.

38.5

38.6
38.7
38.8

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
38.9

Short circuit current density


(A/mm2)
i)
At highest ratio

45

ii)

At intermediate ratio

90

iii)

At lowest ratio

90

38.10

Ampere turn of primary (AT)

(400+400) ATS

38.11

Length of primary conductor

12.0 meter (approx)

38.12

Weight of primary winding

22 Kg (approx)

39.

Core

39.1

Material and grade of the core

CRGO Silicon Steel, M4 Grade

39.2

Thickness of core (mm)

0.3

39.3
39.3.1

Net iron cross sectional area


of core (mm2)
Core 1 PS

1750

39.3.2

Core 2 Metering

2000

39.3.3

Core 3 PS

1750

39.3.4

Core 4 PS

1750

39.3.5

Core 5 PS

1750

39.4

Mean magnetic path length (cm) :

39.5

39.7

Whether B H curve for the


core material, used, furnished?
(B-wb/m2, H-AT/cm)
Whether specific loss vs. flux
density graph for the core
material used furnished?
Axial length of core (mm)

39.7.1

Core I

35

39.7.2

Core II

40

39.7.3

Core III

35

39.7.4

Core IV

35

39.7.5

Core V

35

39.8
39.8.1

Inside diameter/outside diameter


of the cores
Core I
:

170 mm/270 mm

39.8.2

Core II

170 mm/270 mm

39.8.3

Core III

170 mm/270 mm

39.6

22

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
39.8.4

Core IV

170 mm/270 mm

39.8.5

Core V

170 mm/270 mm

39.9

Weight of core

39.9.1

Core I

8.5 Kg (approx)

39.9.2

Core II

11 Kg (approx)

39.9.3

Core III

8.5 Kg (approx)

39.9.4

Core IV

8.5 Kg (approx)

39.9.5

Core V

8.5 Kg (approx)

40.

Secondary windings

40.1

Rated secondary current (A)

1.2

40.2

Copper

40.3.1

Material of the secondary


windings
Size of the secondary conductor
(Bare/Insulated) (mm)
Core I

1.42 mm dia / 1.51 mm dia

40.3.2

Core II

1.21 mm dia / 1.300 mm dia

40.3.3

Core III

1.42 mm dia / 1.51 mm dia

40.3.4

Core IV

1.42 mm dia / 1.51 mm dia

40.3.5

Core V

1.42 mm dia / 1.51 mm dia

40.4
40.4.1

Cross Sectional area of the


secondary conductor (mm2)
Core I

1.58

40.4.2

Core II

1.16

40.4.3

Core III

1.58

40.4.4

Core IV

1.58

40.4.5

Core V

1.58

40.5
40.5.1

Current density of secondary


windings (A/mm2)
Core I

0.75

40.5.2

Core II

1.03

40.5.3

Core III

0.75

40.5.4

Core IV

0.75

40.5.5

Core V

0.75

40.6

No. of secondary turns

40.6.1

Core I

400+400

40.6.2

Core II

400+400

40.3

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
40.6.3

Core III

400+400

40.6.4

Core IV

400+400

40.6.5

Core V

400+400

40.7

No. of layers

40.7.1

Core I

40.7.2

Core II

40.7.3

Core III

40.7.4

Core IV

40.7.5

Core V

40.8

No. of turns/layer

40.8.1

Core I

400

40.8.2

Core II

400

40.8.3

Core III

400

40.8.4

Core IV

400

40.8.5

Core V

400

40.9
40.9.1

Average length/turn of
secondary windings
Core I

170 mm

40.9.2

Core II

180 mm

40.9.3

Core III

170 mm

40.9.4

Core IV

170 mm

40.9.5

Core V

170 mm

40.10

0.011 conductor used for core I, III


0.017 conductor used for core II

40.11

Resistance of the conductor


used for secondary winding per
meter length at 75C (ohm per
meter)
Weight of secondary windings

40.11.1

Core I

6 Kg (approx)

40.11.2

Core II

4 Kg (approx)

40.11.3

Core III

6 Kg (approx)

40.11.4

Core IV

6 Kg (approx)

40.11.5

Core V

6 Kg (approx)

41.

Insulation

41.1

Name and class of insulating


material between core and
secondary winding

Electrical Grade Kraft Paper


Class A

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
41.2

Electrical Grade Kraft Paper & Crepe Paper

Electrical Grade Kraft Paper & Crepe Paper

42.1.1

Inside/outside diameter of
secondary windings (mm)
Core I

42.1.2

Core II

42.1.3

Core III

42.1.4

Core IV

42.1.5

Core V

42.2

Inside/outside diameter of
primary winding (mm)
Minimum clearance from
primary to tank

140 inside
300 outside
140 inside
300 outside
140 inside
300 outside
140 inside
300 outside
140 inside
300 outside
N. A. since flexible conductor are used

42.4

Minimum clearance from


secondary to tank

43.

Tank and secondary terminal


box
Material of the CT tank

41.3
42.
42.1

42.3

43.1
43.2
43.3
43.4
43.5

43.6

43.7

Name/s of insulating materials


between secondary winding and
primary winding
Insulating materials used to
achieve grading of capacitance
Diameter of winding

We use insulated primary by Electrical Grade Kraft


Paper, which meets the requirement of voltage stress
of 132 KV system level, therefore, clearance between
primary and tank is not applicable.
Secondary winding is insulated for 4 KV rms for
immersed voltage stress. This winding is earth during
power frequency and impulse voltage test. Therefore,
the clearance is not applicable to us.

M. S.

Material of the CT secondary


terminal box
Thickness of CT tank material

M. S.

3.14 mm

Thickness of the secondary


terminal box material
Zinc coating of the CT tank
(gm/m2) as per relevant up-todate ISS
Zinc coating of the CT
secondary terminal box
(gm/m2) as per the relevant upto-date ISS
Ingress protection rating of the

3.14 mm

550 (min)

550 (min)

IS 55

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
secondary terminal box
43.8

100 Kg (approx)

44.

Weight of the tank, fittings and


other accessories
TERMINAL CONNECTOR

44.1

Manufacturers name

Sheetal Engineering (P) Ltd.

44.2

Applicable standard

IS: 5621

44.3

Type

Suitable for Universal Takeoff.

44.4

Material of connector

44.4.1

Clamp body

LM 6

44.4.2

Bolts and nuts

S. S.

44.4.3

Spring washers

S. S.

44.5

Rated current (A)

1000

44.6

Rated terminal load (Kg)

50 (approx)

44.7

Factor of safety

44.8

12

1.5 Kg (approx)

Enclosed

44.11

Minimum thickness of any part


(mm)
Weight of clamp complete with
hardware
Type test report as per IS
enclosed
OGA drawing enclosed

Enclosed

45.

INSULATOR

45.1

Manufacturers name

JSI, Halol / MIL, Abu Road/IEC Bhopal

45.2

Type

Hollow Insulator / Condenser type

45.3

Applicable standard

IS: 5621

45.4

Height (mm)

1400 (approx)

45.5

Diameter (top) (mm)

130 I. D. (approx)

45.6

Diameter (bottom) (mm)

130 I. D. (approx)

45.7

Total Creepage distance (mm)

3625

45.8

Rated voltage (KV)

145

45.9

Power frequency withstand


:
voltage for 1 minute dry and wet

275

44.9
44.10

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
45.10

650

45.11

1.2/50 micro-second impulse


withstand voltage (KV Peak)
Corona extinction voltage (KV)

Not specified in ISS

45.12

Weight (Kg)

60 (approx)

45.13

Maximum allowable span (mm)

45.14

Cantilever strength (Kg)

45.15

The drawing enclosed

Enclosed

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
GUARANTEED TECHNICAL PARTICULARS FOR 132KV CURRENT TRANSFORMER WITH METERING
WINDING OF ACCURACY CLASS 0.2
Ratio: 800-800-200/1-1-1-1-1A
1.

Bidders name and address

MEHRU / SCT / ITC / LAMCO

2.

MEHRU / SCT / ITC / LAMCO

3.

Name and address of the


manufacturer
Manufacturers type designation

Outdoor, Dead tank, oil filled, hermetically sealed

4.

Standard applicable

IS: 2705/1992

5.

Rated frequency (Hz)

50

6.

Rated voltage (KV)

132

7.

Rated current

7.1

Rated continuous current

800-400-200 Amp

7.2

Rated extended primary current

120% of the rated current

8.

Short time thermal current


withstand for 3 second
Dynamic current withstand

23 KA (rms)

79.5 KA (Peak)

650 KV (Peak)

12.

1.2/50 s impulse withstand


voltage
One minute dry and wet power
frequency withstand voltage
No. of cores per CT

275 (KV rms) wet


275 (KV rms) dry
5

13.

Transformation ratio

800-400-200/1-1-1-1-1A

14.

No. of secondary turns

800

9.
10.
11.

15.
16.
17.
18.

19.
19.1
19.2
19.3
19.4

II

III

IV

Rated output at different taps


(VA)
Accuracy class

-----

-----

30

-----

-----

PS

PS

0.2

PS

PS

Knee point voltage at different


taps for all PS class cores (V)
Secondary winding resistance
at different taps for all cores
(ohms) at 75C (max)
Maximum exciting current at (for
all PS class cores)
100% KPV (Knee point voltage)
(mA)
25% KPV (Knee point voltage)
(mA)
20% KPV (Knee point voltage)
(mA)
10% KPV (Knee point voltage)
(mA)

400

400

-----

400

400

5.0 (max)

5.0 (max)

-----

5.0
(max)

5.0
(max)

25

25

-----

25

25

12

12

-----

12

12

-----

-----

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com

20.

< 5 for metering core

500

Yes provided

Not specified in ISS

24.

Instrument security factor at


different ratios
Radio interference voltage at
1.1/3 at 1.0 MHZ (micro-volts)
Whether auxiliary CT provided
for metering winding
Corona extinction voltage (KV
rms)
Partial discharge level (pC)

10 (max)

25.

Total Creepage distance (mm)

3625

26.

Primary

26.1

No. of primary turns

1+1+1+1 = 4

26.2

Material and cross section of


primary
Whether bar type or ring type
primary
Whether CT is suitable for
transportation horizontally
Percentage current (ratio) error
and phase displacement in
minutes at rated burden and at

Flexible copper bus-bar, 202 Sq. mm

Ring Type

Yes

21.
22.
23.

26.3
27.
28.

Current Error/Ratio Error

Phase
displacement

II

III

IV

(minutes)
I II III

28.1

20% rated current

---

---

0.35%

---

---

--

28.2

120% rated current

0.25%

0.25%

0.2%

0.25%

0.25%

--

---

IV

15

---

---

10

---

---

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com

29.

Percentage current (ratio)


error and phase displacement
in minutes at 25% rated
burden and

Current Error/Ratio Error

Phase
displacement
(minutes)

II

III

IV

II

III

IV

29.1

20% rated current

---

---

0.35
%

---

---

--

---

15

---

---

29.2

120% rated current

0.25
%

0.25
%

0.2%

0.25
%

0.25
%

--

---

10

---

---

30.

Quantity of oil per CT


(Littres/Kg)
Standard to which oil
conforms generally
Characteristics of oil (prior to
filling)
Breakdown voltage (KV)

: 125Kg 5%

: 0.002 (max)

32.3

Di-electric dissipation
constant
(tan-delta)
Water content (ppm)

32.4

Gas content

: As per ISS

32.5

: 0.04 (min)

32.6

Interfacial tension at 27C


(N/m)
Specific resistance

32.6.1

At 90C (ohm cm)

: 35 x 1012 (min)

32.6.2

At 27C (ohm cm)

: 1500 x 1012 (min)

33.

: Yes, through Nitrogen Gas Cushion

34.

Whether current transformers


are hermetically sealed. IF so,
how
Total weight (Kg)

35.

Transport Weight (Kg)

: 550 5%

36.

36.1

Temperature rise over an


ambient temperature of 50C
for continuous operation at
rated continuous thermal
current
Winding (C)

: 45

36.2

Oil (C)

: 40

31.
32.
32.1
32.2

: IS: 335

: 60 (min)

: 50 (max)

: 500 5%

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
36.3

45

37.1

External surface of the core,


metallic parts in contact with or
adjacent to insulation (C)
Whether CT characteristic
curves enclosed
Ratio and phase angle curves

Yes

37.2

Magnetization curves

Yes

37.3

Ratio correction factor curves

Yes

38.

Data on primary winding

38.1

Rated primary current (A)

800-400-200

38.2

No. of conductors in one turn

965 of 0.2043 mm2 each conductor

38.3

No. of turns of primary

1+1+1+1 = 4

38.4

Material of the primary


conductors
Size of the primary conductor
(Bare/Insulated) (mm)

Copper

Cross Sectional area of each


conductor (mm2)
Total cross sectional area of
primary winding (mm2)
Current density (A/mm2)

Cross sectional area is already furnished at Sl. No.


38.2. Since the primary consists of flexible
conductors, therefore, overall diameter is not
applicable to us. All related information pertaining to
size is already furnished.
0.2043 mm2 as already furnished above.

202 mm2

i)

At highest ratio

0.59

ii)

At intermediate ratio

0.59

iii)

At lowest ratio

0.59

Short circuit current density


(A/mm2)
i)
At highest ratio

90

ii)

At intermediate ratio

90

iii)

At lowest ratio

90

37.

38.5

38.6
38.7
38.8

38.9

38.10

Ampere turn of primary (AT)


i)

At highest ratio

400

ii)

At intermediate ratio

400

iii)

At lowest ratio

400

38.11

Length of primary conductor

12 meter (approx)

38.12

Weight of primary winding

22 Kg (approx)

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
39.

Core

39.1

Material and grade of the core

CRGO Silicon Steel, M4 Grade

39.2

Thickness of core (mm)

0.3

39.3
39.1

Net iron cross sectional area of


core (mm2)
Material and grade of the core
:

CRGO M4

39.2

Thickness of core (mm)

0.3

39.3
39.3.1

Net iron cross sectional area of


core (mm2)
Core 1
:

3250

39.3.2

Core 2

3250

39.3.3

Core 3

4000

39.3.4

Core 4

3250

39.3.5

Core 5

3250

39.4

Mean magnetic path length (cm)

39.4.1

Core 1

22

39.4.2

Core 2

22

39.4.3

Core 3

22

39.4.4

Core 4

22

39.4.5

Core 5

22

39.5

39.7

Whether B H curve for the core :


material, used, furnished?
(B-wb/m2, H-AT/cm)
Whether specific loss vs. flux
:
density graph for the core
material used furnished?
Axial length of core (mm)

39.7.1

Core I

65

39.7.2

Core II

65

39.7.3

Core III

80

39.7.4

Core IV

65

39.7.5

Core V

65

39.8
39.8.1

Inside diameter/outside diameter


of the cores
Core I

170 mm/270 mm

39.8.2

Core II

170 mm/270 mm

39.8.3

Core III

170 mm/270 mm

39.6

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
39.8.4

Core IV

170 mm/270 mm

39.8.5

Core V

170 mm/270 mm

39.9

Weight of core

39.9.1

Core I

17 Kg (approx)

39.9.2

Core II

17 Kg (approx)

39.9.3

Core III

21 Kg (approx)

39.9.4

Core IV

17 Kg (approx)

39.9.5

Core V

17 Kg (approx)

40.

Secondary windings

40.1

Rated secondary current (A)

1.2

40.2

Copper

40.3.1

Material of the secondary


windings
Size of the secondary conductor
(Bare/Insulated) (mm)
Core I

1.42 mm dia / 1.51 mm dia

40.3.2

Core II

1.42 mm dia / 1.51 mm dia

40.3.3

Core III

1.21 mm dia / 1.300 mm dia

40.3.4

Core IV

1.42 mm dia / 1.51 mm dia

40.3.5

Core V

1.42 mm dia / 1.51 mm dia

40.4
40.4.1

Cross Sectional area of the


secondary conductor (mm2)
Core I

1.58

40.4.2

Core II

1.58

40.4.3

Core III

1.16

40.4.4

Core IV

1.58

40.4.5

Core V

1.58

40.5
40.5.1

Current density of secondary


windings (A/mm2)
Core I

0.75

40.5.2

Core II

0.75

40.5.3

Core III

1.03

40.5.4

Core IV

0.75

40.5.5

Core V

0.75

40.6

No. of secondary turns

40.6.1

Core I

400

40.6.2

Core II

400

40.3

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
40.6.3

Core III

400

40.6.4

Core IV

400

40.6.5

Core V

400

40.7

No. of layers

40.7.1

Core I

40.7.2

Core II

40.7.3

Core III

40.7.4

Core IV

40.7.5

Core V

40.8

No. of turns/layer

40.8.1

Core I

400

40.8.2

Core II

400

40.8.3

Core III

400

40.8.4

Core IV

400

40.8.5

Core V

400

40.9
40.9.1

Average length/turn of
secondary windings
Core I

230 mm

40.9.2

Core II

230 mm

40.9.3

Core III

280 mm

40.9.4

Core IV

230 mm

40.9.5

Core V

230 mm

40.10

0.011 conductor used for core I, II, IV, V


0.017 conductor used for core III

40.11

Resistance of the conductor


used for secondary winding per
meter length at 75C (ohm per
meter)
Weight of secondary windings

40.11.1

Core I

6 Kg (approx)

40.11.2

Core II

6 Kg (approx)

40.11.3

Core III

4.5 Kg (approx)

40.11.4

Core IV

6 Kg (approx)

40.11.5

Core V

6 Kg (approx)

41.

Insulation

41.1

Name and class of insulating


material between core and
secondary winding

Electrical Grade Kraft Paper


Class A

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
41.2

Electrical Grade Kraft Paper & Crepe Paper

Electrical Grade Kraft Paper & Crepe Paper

42.1.1

Inside/outside diameter of
secondary windings (mm)
Core I

42.1.2

Core II

42.1.3

Core III

42.1.4

Core IV

42.1.5

Core V

42.2

Inside/outside diameter of
primary winding (mm)
Minimum clearance from primary
to tank

150 inside
290 outside
150 inside
290 outside
150 inside
290 outside
150 inside
290 outside
150 inside
290 outside
N. A. since flexible conductor are used

42.4

Minimum clearance from


secondary to tank

43.

Tank and secondary terminal


box
Material of the CT tank

41.3
42.
42.1

42.3

43.1
43.2
43.3
43.4
43.5

43.6

43.7
43.8

Name/s of insulating materials


between secondary winding and
primary winding
Insulating materials used to
achieve grading of capacitance
Diameter of winding

We use insulated primary by Electrical Grade Kraft


Paper, which meets the requirement of voltage stress
of 220KV system level, therefore, clearance between
primary and tank is not applicable.
Secondary winding is insulated for 4 KV rms for
immersed voltage stress. This winding is earth during
power frequency and impulse voltage test. Therefore,
the clearance is not applicable to us.

M. S.

Material of the CT secondary


terminal box
Thickness of CT tank material

M. S.

3.14 mm

Thickness of the secondary


terminal box material
Zinc coating of the CT tank
(gm/m2) as per relevant up-todate ISS
Zinc coating of the CT
secondary terminal box (gm/m2)
as per the relevant up-to-date
ISS
Ingress protection rating of the
secondary terminal box
Weight of the tank, fittings and
other accessories

3.14 mm

550 (min)

550 (min)

IS 55

100 Kg (approx)

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
44.

TERMINAL CONNECTOR

44.1

Manufacturers name

Sheetal Engineering (P) Ltd./other approved make

44.2

Applicable standard

IS: 5621

44.3

Type

Suitable for Universal Takeoff.

44.4

Material of connector

44.4.1

Clamp body

LM 6

44.4.2

Bolts and nuts

S. S.

44.4.3

Spring washers

S. S.

44.5

Rated current (A)

1000

44.6

Rated terminal load (Kg)

50 (approx)

44.7

Factor of safety

44.8

12

1.5 Kg (approx)

44.11

Minimum thickness of any part


(mm)
Weight of clamp complete with
hardware
Type test report as per IS
enclosed
OGA drawing enclosed

45.

INSULATOR

45.1

Manufacturers name

JSI, Halol / MIL, Abu Road

45.2

Type

Hollow Insulator / Condenser type

45.3

Applicable standard

IS: 5621

45.4

Height (mm)

1400 (approx)

45.5

Diameter (top) (mm)

130 I. D. (approx)

45.6

Diameter (bottom) (mm)

130 I. D. (approx)

45.7

Total Creepage distance (mm)

3625

45.8

Rated voltage (KV)

145

45.9

275

650

45.11

Power frequency withstand


voltage for 1 minute dry and wet
1.2/50 micro-second impulse
withstand voltage (KV Peak)
Corona extinction voltage (KV)

Not specified in ISS

45.12

Weight (Kg)

100 (approx)

45.13

Maximum allowable span (mm)

45.14

Cantilever strength (Kg)

45.15

The drawing enclosed

44.9
44.10

45.10

:
:

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
GUARANTEED TECHNICAL PARTICULARS FOR 132 KV POTENTIAL
TRANSFORMER WITH METERING WINDING OF ACCURACY CLASS OF 0.2
1.

Bidders name and address

MEHRU / SCT / ITC / LAMCO

2.

Name and address of the manufacturer

MEHRU / SCT / ITC / LAMCO

3.

Manufacturers type designation

4.

Standard applicable

Outdoor, Electromagnetic type, oil held,


hermetically sealed
IS: 3156/1992

5.

Type of inductive voltage transformer

Hermetically sealed

6.

Rated primary voltage (KV)

132 / 1.732

7.

Rated secondary voltage (V)


:

110 / 1.732

ii) Winding II

110 / 1.732

8.

Rated frequency (Hz)

50

9.

Rated burden
Winding I (Protection)

100 VA

ii) Winding II (Metering)

100 VA

10.

Number of secondary windings

11.

Accuracy class
Winding I (Protection)

0.2

ii) Winding II (Metering)

0.2

Rated voltage factor for continuous


operation at rated frequency
Rated voltage factor for 30 seconds at
rated frequency
One minute dry and wet power frequency
withstand voltage for primary winding
(KV rms)
One minute power frequency withstand
voltage for secondary winding (KV rms)
1.2/50 micro-second impulse withstand
test voltage
Temperature rise over an ambient
temperature of 50C

1.2 continuous

1.5 times

275 dry
275 wet on bushing only

650

i)

i)

i)

12.
13.
14.

15.
16.
17.

Winding I

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
a)

With 1.2 times rated primary voltage


at rated frequency and at rated
burdens
i) Winding (C)
:

45

ii)

40

iii Other parts (C)


:
)
With 1.5 times rated primary voltage
for 30 seconds at rated frequency
and at rated burdens
i) Winding (C)
:

40

ii)

40

40

18.

iii Other parts (C)


)
Class of insulation

19.

Total Creepage distance in (mm)

3625

20.

500

Not specified as per ISS

22.

Maximum radio interference voltage at


1.1 times maximum line to ground
voltage (micro-volts)
Corona inception and extinction voltage
(KV rms)
Partial discharge level (pico-coulombs)

10 (max)

23.

Primary

b)

21.

Oil (C)

45

a)

No. of primary turns

38325

b)

Material of primary

Copper Wire

c)

Size of the primary conductor


bare/insulated
Cross sectional area of primary
conductor (mm2)
Current density adopted for primary
winding (A/ mm2)
Type of primary winding

0.31 mm dia/0.37 mm dia

0.0754

0.030

Ring type

Name of the insulating materials


used for primary conductor
Weight of primary winding

Super Enameled

16 Kg

d)
e)
f)
g)
h)
24.

Oil (C)

Secondary
a)

No. of secondary turns

Winding I

Winding II

32

32

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
b)

Material of secondary

Copper

Copper

c)

Size of the secondary conductor


bare/insulated
Cross sectional area of secondary
conductor (mm2)
Current density adopted for
secondary winding (A/mm2)
Type of secondary winding

:
:

2.03 mm dia /
2.15 mm dia
3.24

2.03 mm dia /
2.15 mm dia
3.24

0.5

0.5

Ring type

Ring type

Super Enameled

Super Enameled

1.6 Kg

1.6 Kg

Winding I

Winding II

d)
e)
f)
g)
h)
25.

Name of the insulating material used :


for secondary conductor
Weight of secondary windings
:

Core
a)

Shape of the core

Rectangular type

b)

Material and grade of the core


laminations
Thickness of the core laminations
(mm)
Maximum flux density adopted
(tesla)
Net iron area of the core

:
:

CRGO Silicon
Steel M4 Grade
0.3

1.6

7552.5 sq. mm

Watt loss/Kg for the core materials


at the operating flux density (W/Kg)
Total weight of the core (Kg)

0.85

73 (approx)

Whether B H curve for core


materials enclosed?
i) Whether specific loss vrs. Flux
density curve enclosed?
Insulation

Yes enclosed

Yes

a)

Insulation between core and


secondaries
Insulation between secondaries

Electrical Grade Kraft Paper

Electrical Grade Kraft Paper

Insulation between secondary and


primary
Insulation between primary and core

Electrical Grade Kraft Paper & Crepe


Paper
Electrical Grade Kraft Paper & Crepe
Paper

c)
d)
e)
f)
g)
h)

26.

b)
c)
d)
27.

Dimensions of core and windings


a)

Diameter of the core (mm)

Not applicable, since it is shell type core

b)

Inner diameter of the secondary


windings (mm)

112

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
c)

28.

29.

30.

31.

Outer diameter of the secondary


windings (mm)
d) Inner diameter of the primary
windings (mm)
e) Outer diameter of the primary
windings (mm)
f) Minimum clearance from primary
winding to tank (mm)
g) Minimum clearance from secondary
winding to tank (mm)
Percentage voltage ratio (error)/phase
displacement (min.) at 100% rated burden
at 0.8 pf lagging for measuring winding
a) 80% of rated voltage at rated
frequency
b) 120% of rated voltage at rated
frequency
c) Accuracy of standard PT to be used
during determination of errors (0.05
or less)
Percentage voltage (ratio) error/phase
displacement (minutes) at 25% rated
burden at 0.8 pf lagging for measuring
winding
a) 80% of rated voltage at rated
frequency
b) 120% of rated voltage at rated
frequency
Percentage voltage (ratio) error /phase
displacement (minutes) at 100% rated
burden at 0.8 pf lagging for protection
winding
a) 5% of rated voltage

135

135

300

:
:

Not required because primary winding


insulated by Kraft Paper
Not required because secondary winding
insulated by Kraft Paper
Ratio Error
Phase Displacement

0.2%

20 minutes

0.2%

20 minutes

0.05 class

b)

Ratio Error

Phase Displacement

0.2%

10 minutes

0.2%

10 minutes

0.2%

10 minutes

1.2 times rated voltage

0.2%

10 minutes

c)

1.5 times rated voltage

0.2%

10 minutes

d)

2% of rated voltage

0.2%

20 minutes

Percentage voltage (ratio) error/phase


displacement (minutes) at 25% rated
burden at 0.8 pf lagging for protection
winding
a) 5% of rated voltage

0.2%

10 minutes

b)

0.2%

10 minutes

1.2 times rated voltage

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
c)

1.5 times rated voltage

0.2%

10 minutes

d)

2% of rated voltage

0.2%

20 minutes

Yes

33.

Whether IVT is suitable for horizontal


transportation
Quantity of oil per PT (ltrs/Kg)

125 Litres 5%

34.

Standard to which oil conforms

IS: 335

35.

Characteristics of oil (prior to filling)

35.1 Breakdown voltage (KV rms)

60 minutes

35.2

0.002 (max)

35.3

Di-electric dissipation constant


(tan-delta)
Water content (ppm)

50 (max)

35.4

Gas content (ppm)

As per IS: 335

35.5

Interfacial tension at 27C (N/m)

0.04 (min)

35.6

Specific resistance

35.6.1

At 90C (ohm cm)

35 x 1012 (min)

35.6.2

At 27C (ohm cm)

1500 x 1012 (min)

36.

Yes, through Nitrogen Gas Cushion

37.

Whether inductive transformers are


hermetically sealed? If so, how?
Total weight (Kg)

400 5%

38.

Transport weight (Kg)

450 5%

39.

Dimensional details

40.

Yes enclosed

41.

Whether IVT characteristic curves


enclosed?
Tank and secondary terminal box

41.1

Material of the IVT tank

M. S.

41.2

Material of the secondary terminal box

M. S.

41.3

Thickness of the IVT material

3.14 mm

41.4

Thickness of the secondary terminal


box material

3.14 mm

32.

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
41.5

Zinc coating of IVT tank (g/Sq. m2)

610

41.6

Zinc coating of the secondary terminal


box (g/Sq. m2)
Weather proof rating of secondary
terminal box
Weight of tank fittings and other
accessories

610

IP 55

100 Kg (approx)

41.7
41.8

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
TERMINAL CONNECTORS
1.

Manufacturers name

2.

Applicable standards

Shakunt Engineering (P) Ltd./other


approved make
IS: 5561

3.

Type

Universal type

4.

Material of connector
a)

Clamp body

LM 6

b)

Bolts and nuts

S. S.

c)

Spring washers

S. S.

5.

Rated current

800 Amp

6.

a)

Rated terminal load (Kg)

200 (approx)

b)

Factor of safety

1.2

7.

Minimum thickness of any part (mm)

12

8.

2.5 Kg

9.

Weight of connector complete with


hardware
Type test reports as per IS enclosed

Yes enclosed

10.

OGA drawing enclosed

Yes enclosed

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India

+91-986 866 7484


+91-975 938 1998
+91-1232-226182
Traders & Exporters of Power Equipments and Power Consultancy
Info@luckyindiapowersolution.com / luckyindiapowersolutions@gmail.com
BUSHING/SUPPORT INSULATOR
1.

Manufacturers name

JSI, Halol / MIL, Abu Road

2.

Type

Hollow Insulator

3.

Applicable standards

IS: 5621

4.

Dimensions
i)

Height (mm)

1400 (approx)

ii)

Diameter (top) (mm)

130 (approx)

iii) Diameter (bottom) (mm)

130 (approx)

5.

Total Creepage distance (mm)

3625

6.

Rated voltage (KV rms)

132

7.

275

650

9.

Power frequency withstand voltage for


1 min. dry and wet (KV rms)
1.2/50 micro-second impulse withstand
voltage (KV Peak)
Corona extinction voltage (KV)

Not specified in ISS

10.

Weight (Kg)

100 (approx)

11.

Maximum allowable span (mm)

12.

Cantilever strength (Kg)

13.

OGA drawing enclosed

8.

Yes

H. No. # 572, Gulshan Colony, Opposite OBC Bank, Near Roadways Bus Stand, Muradnagar, Dist. Ghaziabad-201 206, UP, India