Professional Documents
Culture Documents
Everyone knows (or should know) that boiler tubes containing deposits create long-term
reliability problems for the boiler. Deposits insulate the water in the tubes from the fire,
causing the metal temperature to increase dramatically between the deposit and the tube
metal. Long-term overheating of the metal will result from prolonged operation with heavy
tube deposits. The tubes will first bulge and then fail. Because the deposits tend to be
widespread, this generally means that large sections of boiler tubing will be damaged and
require replacement.
The deposits also concentrate any boiler water chemistry and contamination that collects
under them. The increased metal temperature caused by the deposit increases the rate of
corrosion caused by any phosphate, caustic, or chloride underneath the deposit. With the
exception of corrosion fatigue, all the water-side boiler tube failure mechanisms occur under
deposits. Get rid of the deposits and you also stop the water-side tube failures.
A change in the chemical treatment regime. Such changes would include moving from one
chemical treatment to another, say from all-volatile treatment to oxygenated treatment (OT).
1. To clean or not to clean? For cleaning with the bead blast method, this chart shows the recommended parameters for
immediate and near-term cleaning. Source: EPRI
There are three general recommendations on this figure. If the DWD result is in the top area,
a chemical cleaning should be performed as soon as it can be scheduled. The lowest area
represents a relatively clean tube. The middle area between the green and red line indicates
that deposits are beginning to accumulate to the point where cleaning should be considered
and probably budgeted for the next major outage or within the next two years. If that is the
case, grab another tube sample close to the next outage and see if the DWD has increased and
is close to or in the Cleaning recommended area. If not, you may be able to get by for
another year or two.
Although the heat flux in a heat-recovery steam generator (HRSG) is far lower, the
circulation issues can be far greater due to the multiple assemblies and configuration with the
drum. So the industry has applied close to the same DWD criteria for cleaning for an HRSG
as for a conventional fossil-fired unit.
As a general rule, the DWD criteria for HRSG tubes is about 20% higher than for a
conventional boiler.
Occasionally, a utility will want to take multiple tube samples and have them analyzed. In
these cases, the DWD result that should be used to determine the need to chemically clean is
the tube that is the most heavily deposited. Remember, what you are trying to determine is if
there is sufficient deposit anywhere in the boiler to cause under-deposit corrosion or
overheating. You are not trying to determine the average amount of deposit in the whole
boiler or even the average in the high-heat area. One isolated area of hydrogen damage or
overheated tubes is enough to cause a number of forced outages or extend a planned outage,
and certainly reason enough to chemically clean.
If the DWD results indicate the need to chemically clean, now is the time to do it.
Procrastination with cleaning is detrimental on a number of levels.
First and foremost is the damage done to the tubes. Under-deposit corrosion rates and longterm overheat damage are exponential, not linear. A delay of one or two years on a dirty
boiler can result in major tube damage.
Second, you dont save as much as you think. Cleaning a very dirty boiler is significantly
more expensive than cleaning a boiler that has just crossed into that Cleaning
recommended region. The additional costs in solvent (see sidebar), time to get the tubes
clean, multiple cleaning steps, startup delays, and dealing with excessive amounts of cleaning
wastes are all consequences of postponing a needed cleaning.
Gun-shy About Chemical Cleaning?Some plants have had bad experiences with chemical cleanings and so are reluctant to go
through that process again. They fear that the cleaning process will turn their boiler into a sprinkler system.The solvents
used in chemical cleaning are designed to minimize the corrosion of base tube metal anywhere in the boiler. When properly
applied by experienced cleaning vendors, the amount of base metal removed is very small. The vast majority of the iron that
is dissolved by the cleaning solvent originally came in from the condenser, feedwater heaters, deaerator and associated
pipingnot from the boiler tubes themselves.In some cases, the cleaning process removes the deposit that was preventing a
noticeable tube leak. If the cleaning had not occurred, the leak would have still happened.
Depending on the solvent and the size of the leak, a cleaning may be able to proceed anyway. Efforts will have to be made to
contain and collect the leaking solvent.
In other cases, the leak is so bad that the cleaning has to be terminated and the solvent drained to effect a tube repair.
Dealing with leaks during a cleaning can be difficult, but the alternativeleaving the deposit on the boiler tubes for another
year or twoguarantees that the under-deposit corrosion will continue. So, not only that tube, but also many of its neighbors,
will eventually leak during operation, leading to repeated forced outages.
The solvents discussed below are primarily for the iron removal stage. Another set of
chemicals is used specifically to remove copper in separate copper stages.
Inhibited Hydrochloric Acid. Inhibited HCl is still used, particularly in boilers where it is
difficult to ensure complete circulation of the solvent. It is very effective at removing silica
deposits from the tubes if ammonium bifluoride is added.
It is definitely not recommended on boilers with a history of corrosion fatigue failures, as it
has been shown to increase the failure rate following a cleaning.
If there is any copper in the boiler deposit, provision must be made for removing the copper,
which will otherwise plate-out on the bare steel tube.
In the past, thiourea was commonly added to complex the copper, and it is still used
occasionally. There have been times on some boilers where the thiourea has been inadequate
to remove copper in very localized areas of the boiler, and this causes problems. There may
also be environmental ramifications for using this chemical when attempting to dispose of the
cleaning wastes. For these reasons, a separate copper-removal stage is often recommended
before or after (or both) the acid stage, using a variety of copper-removal solvents.
The use of HCl can create problems on heavily deposited boilers, as the acid often undercuts
the deposits and causes sloughing of larger pieces of material that can plug drains. Removing
the acid when time is up is critical.
Hydroxyacetic Acid. Hydroxyacetic acid is used in boilers with stainless steel components
that will be in the cleaning path where any chloride in the solvent could create a problem.
This solvent is often used in supercritical and once-through boilers. It does not remove
copper, but this is usually not an issue in these boilers.
EDTA. Ethylenediaminetetraacetic acid (EDTA) is probably the most commonly used
operational cleaning chemical. For forced-circulation boilers, the use of diammonium EDTA
is practically a standard practice. The low temperature requirement (180F) of the
diammonium EDTA plus the general safety and ease of handling the solvent during the
cleaning process are all substantial advantages. The disadvantages may come when trying to
dispose of the cleaning wastes..
For natural circulation boilers, tetraammonium EDTA (pH 9) is still used. The boiler has to
be heated to 275F to 300F and repeatedly heated and cooled during the cleaning process.
EDTA has some capacity to dissolve and retain copper in solution when the chemistry of the
EDTA is changed and the iron in solution is oxidized. This is generally done at the end of the
iron stage of the EDTA cleaning process by the addition of oxygen gas. If there is excessive
copper in the deposits, a separate copper-removal step may be required.
EDTA is the most tolerant solvent and particularly good on tubes that are heavily deposited
with iron oxides, or where the iron deposits are particularly tenacious, as the cleaning can be
extended for a long time without risking any damage to the tubes (unlike HCl).
Ammoniated Citric Acid. Ammoniated citric acid is an excellent solvent and is often the
solvent of choice for pre-commissioning cleanings, where deposits are anticipated to be light
and composed exclusively of iron. It can also be used in a high-temperature (higher pH) and
low-temperature (lower pH) scenario, like EDTA. Chemical cleaning wastes containing citric
acid are often easier to dispose of than EDTA-containing wastes.
Inhibited Hydrofluoric Acid. Inhibited hydrofluoric acid (HF) is commonly used in Europe
and elsewhere around the world, but rarely in North America. The stigma to its use in the
U.S. is the very serious personnel risks associated with concentrated HF. However, when
diluted to concentrations typically used in the cleaning process, HF is considered no more
hazardous than an HCl solvent.
HF is fastprobably the fastest cleaning solventand very effective in removing iron and
any silica in the deposits. The potential for exposure to the concentrated acid is limited to the
time when the HF is diluted in preparation for adding it to the boiler. This is handled by the
chemical cleaning vendor, who is aware of the risks and whose personnel are properly
protected with personal protective equipment while transferring the concentrated acid.
Neutralization of the waste is typically done with lime slurry, which neutralizes the acid and
precipitates calcium fluoride and iron hydroxide.
sure that the vendor has extra solvent (50% extra is common) either on-site or very close to
the plant, so that it can be used if needed. Many a cleaning has been delayed hours, if not
days, while waiting for more chemical to arrive from the supplier.
A Good Procedure
There are few things more important to a smooth chemical cleaning than a well-thought-out
and well-documented cleaning procedure. This will require the time and effort of the plants
operation and engineering staff to customize and prepare a cleaning procedure for each unit.
Cleaning vendors can provide a general outline of the cleaning process, and a consulting
engineer can help also, but your operators know where the valves are and which leak-by and
which dont. There will be three classes of valves: those that stay closed the entire cleaning
process, those that must stay open the entire process, and those that need to be opened and
closed, depending on where you are in the cleaning process.
There are also valves that the cleaning vendor will be responsible for opening and closing,
such as those going to the waste disposal (frac) tanks and chemical injection points. Each
valve that comes in contact with the solvent (or potentially could come in contact with the
solvent) needs to fall into one of these groups and be tagged accordingly. Be on particular
lookout for possible contamination routes where the solvent can get to a place where it was
not designed to go. If a contamination route would be very serious, can a blank flange be
installed? If not, can a telltale be set up to provide early detection of contamination?
One more aspect of deciding when to clean is the actual schedulingdetermining whether a
plant should clean at the beginning, during, or at the end of an outage. Chemically cleaning at
any point except the very end of an outage leaves the tubes vulnerable to some general
corrosion. The passivation step at the end of the chemical cleaning is generally neither long
enough nor at a high enough temperature to create a robust protective layer. It is often
difficult to ensure that the boiler gets really dry after the cleaning or can be laid-up properly
in a wet condition. The superheater is always back-filled during cleaning to minimize the risk
of contamination. So, unless it can be drained and dried, this area will remain wet until the
unit is fired sufficiently to dry it out. Therefore, the typical recommendation is to perform the
chemical cleaning at the very end of an outage.
Heating the boiler for chemical cleaning using an auxiliary boiler or steam from another unit
adds complexity and cost to the cleaning. So, as a rule, it is best to wait until the unit can be
warmed using its own burners or igniters and when the fans and instrumentation associated
with the fuel system (such as flame scanners) are working properly and have been fully
tested. Many a utility has waited for days with the chemical cleaning vendor on site and ready
to go while its staff tried to get a fire in the boiler. For this reason, some utilities have decided
not to schedule chemical cleanings during an outage at all; instead, they take a weekend
outage separate from the overhaul for this purpose.
Similarly, pre-commissioning cleanings are optimally performed as close to the steam blow
as possible, to minimize the opportunity for corrosion to undo what was just done with the
cleaning.
The strongly acidic cleaning wastes are generally neutralized as they leave the boiler, and
then that waste is combined with neutralization and passivation steps and rinses to produce a
combined waste that is not characteristically hazardous for pH. The other chemical cleaning
solvents are not characteristically hazardous by pH to begin with.
The other way that a BCCW can be classified as a hazardous waste is if it contains a
concentration of one of the RCRA 8 toxic metals. The primary metal that is of concern is
chromium. Chromium comes from stainless steel feedwater heater and condenser tubes. This
accumulates in deposits in the boiler. The regulation is specifically aimed at hexavalent
chromium. Normally, utilities measure total chromium first, and only address the hexavalent
chromium issue if the total chromium is greater than the RCRA limit of 5 ppm.
EDTA solubilizes chromium in a reduced trivalent chrome (Cr III) state, and it is not
sufficiently oxidized by oxygen in the passivation stage of the cleaning to create a significant
amount of the hexavalent chromium. Some utilities have gone to their state environmental
agencies with analytical data showing that there is very little hexavalent chromium in their
BCCW, even if the total chrome is greater than 5 ppm, and have sought and received an
exemption for this waste so that it can be classified as nonhazardous.
For many years utilities have utilized an exemption provided by the Bevill Amendment and a
subsequent letter from the Environmental Protection Agency (EPA) to group BCCW with
other wastes that were uniquely associated with coal-fired utilities (such as fly ash and
bottom ash) and treat them as exempt from hazardous waste regulations. This allowed the
comingling of BCCW with fly ash or bottom ash and disposal in the ash pile without first
having to determine if they were characteristically hazardous.
In May 2000, the EPA made a regulatory determination that moved BCCW from the
uniquely associated to a not uniquely associated list, meaning that it would lose its Bevill
exemption. This determination was challenged by user groups such as the Utility Solid Waste
Activities Group and Edison Electric Institute, and comments were sent to the EPA. The EPA
has not responded to these comments in any formal way. However, the agencys general
counsel has produced documents that clearly assume that this change in the BCCW
determination has been implemented. This is still an open issue, and utilities should be aware
of these regulations when blending BCCW with a Bevill-exempted waste.
New regulations on coal combustion residuals are in the offing and may affect the way
utilities manage fly and bottom ash and how ash landfills are managed, and this may change
the discussion on comingling BCCW with ash yet again. It is important to note that a
nonhazardous BCCW could still be blended with ash, at least under current regulations.
For many years, coal-fired utilities have evaporated characteristically nonhazardous BCCW
(<5 ppm Cr) by spraying it directly into the fireball of an operating coal-fired boiler, typically
at a rate of 30 to 50 gpm, depending on the amount of coal going to the boiler. This was the
practice with EDTA wastes in particular. The water is evaporated, the organic EDTA is
consumed in the fireball, and metals are combined with the fly and bottom ash leaving the
boiler. The small rate at which the BCCW was being added versus the coal feed made no
measurable differences to any of the fly ash or bottom ash characteristics or stack gases.
Some even found a slight benefit to NOx emissions during the time the BCCW was being
evaporated. This practice had been successfully used for many years by coal-fired power
plants.
However, changes to the definition of a nonhazardous secondary material by the EPA,
together with changes to definitions of what constitutes a commercial industrial solid waste
incinerator, essentially will prohibit a conventional utility boiler from evaporating BCCW in
the future. These changes go into effect at the latest in 2015, but they may already be in place
in some states.
If both evaporation and comingling with fly ash go away, other options for properly
disposing of BCCW will need to be considered. The amount of BCCW generated with the
combined solvent drains and rinses can be very large, and off-site treatment or disposal costs
could double the cost of the cleaning. On-site treatment, particularly of EDTA wastes, can be
time-consuming and expensive. Other innovative recovery and beneficial reuse of these
wastes has been considered in the past but never commercialized. However, in the present
regulatory environment, these options may be in more demand as utilities strive to get their
boilers clean while controlling costs and liability.
David Daniels, is a POWER contributing editor and senior principal scientist at M&M
Engineering Associates Inc.