HT CAPACITOR BANK TECHNICAL COMPARISONS SHEET

Manufacturer's Name

CONSULTANT

ABB Ltd.

Crompton Greaves

Universal Cable Limited


04.02.09

Make : ABB Type : CHD

Make :Madav/Shreem/Equ.

APP type HT capacitors

IS 13925 1998 Part 1

IS 13925 1998 Part 1

IS 13925 1998 Part 1

IS-13925/1992

Purpose

PF Improvement

PF Improvement

PF Improvement

PF Improvement

Location

Indoor Plinth mounted type

Indoor Plinth mounted type

Indoor Plinth mounted type

Indoor Plinth mounted type

11KV
50 HZ

11 KV
50 Hz

11 KV
50 Hz

11 KV
50 Hz

50 oC
-5 oC

50 oC
-5 oC

50 oC
-5 oC

1
12.74
630
11
500
28
3
Externally delta
1
38 KV

1
12.87
644
11
500
26
3
Externally star
1

12.65
621
11
500
29
3
Externally star

28

28

75 KV

95
Vertical, Indoor SIKAP Type

75
vertical

75
vertical

Suitable for Cable Termination

Suitable for Cable Termination


NA

Suitable for Cable


Termination

Suitable for Cable Termination

198
6.92
28
external Fuse
0.2

214.54
7.43
29
external HRC Fuse
< 0.2 watt/KVAR

103.5
7.3
29
external HRC fuse
<0.15 watts/KVAr

All Polypropylene

All Polypropylene

All Polypropylene

All Polypropylene

28

38

28

28

Maker's Type Designation


Standard followed

System Specifications:
Voltage
Frequency
Ambient Temperature:
Maximum Temperature
Minimum Temperature
Capacitor Bank
Rated output (Installed)
KV
KVAR
Rated output (Effective)
KV
KVAR
Rated Current
Amps
No. of Phases
Type of connection
No. of units per bank
Power frequency withstand voltage, KV (RMS)
Impulse withstand voltage KV (PEAK)
Type of mounting
Terminal Arrangement
(a) Incoming
(b) Outgoing
Capacitor Unit
Rated Output (kVAr)
Rated Voltage (kV)
Rated Current (A)
Unit Protection
Losses (Watts / kVAr)
(after a few hours of energisation)
Di - electric type
Insulation level
(a) Power Frequency withstand voltage
KV(RMS)

12
11
500
3
Delta/Star

28 kV

external Fuse

(b) Impulse withstand voltage KV (PEAK)


Permissible load
(a) Voltage
(b) Current
(c) Output
Discharge device to discharge capacitor to 50V
or less in 600 secs after disconnection from
supply:
Creepage distance (mm/kV)
SERIES REACTOR

Type of series reactor


Construction
Service
Rated voltage & frequency
Series reactor for capacitor bank
Conductor material
Reactor noise level
Interlock with earthing switch and main
switch

75

95

75

75

1.1 times system voltage


1.3 times rated current

As per Table 2 of IS 13925 -1998

1.1 times system voltage


1.3 times rated current

1.1 times system voltage


1.3 times rated current

Yes

Yes

Yes

25 mm/ kV

25 mm/ kV

25mm/kv

25mm/kv

Iron cored, dry and Air cooled.

air core ,dry type copper wound

Air Cored, Dry type air cooled

Air Cored / Al. wound

YES

Single phase/Three phase unit


mounted on frame.
Indoor
11kV 10% , 50 Hz 3%
Estimated 2% to 6%
electrolytic grade copper conductor
50 dB(A)
Required

single phase

Air Cored

Indoor

Indoor

Indoor

6.0%
Copper

6%
Copper

6.0%
Copper

Ok

UNBALANCE PROTECTION

RVT (Residual Voltage Transformer)


Connection of RVT
RVT Secondary Voltage

Required
Open-Delta
110 V /3 (L-L)

Provided
three phase
11000/190 -110 volt

Dry type , Indoor


three phase
11000/190 -110 volt

Dry type , Indoor


three phase
11KV/110V/190V

1 Nos

391,000/-

6,70,000

3,98,800

Exluded

Exluded

Exluded

Price

11 KV 500 KVAR
Mandatory spares
Erection & Commissioning
6.92kv 198kvar capacitor units

2 Nos

42,000/-

17,000 Rs. Each

Not given

12 kv Insulators

2 Nos.

4000/-

300 Rs. Each

Not given

Murthy
9901491182

Ajay Pradhan
9893319306
Alpesh Jain
9822751543