You are on page 1of 24

1

CUSTOMER

: UHBVNL

CONTRACTOR

: M/s.FUJI ELECTRIC Co.,Ltd-Japan

PROJECT

: HR MISSION PANIPAT SMART GRID PROJECT

P.O. NO
LOCATION

: JA2267-BO-C002-001
:HPTI

AUX.SUPPLY

:24V DC-INTERNAL SOURCE

SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

D
D

SUPPLIER :

ASA BHANU
TECHNICAL SERVICES LIMITED

HYDERABAD

Contract Ref :

SCALE
N.T.S
0
Rev

30-03-16

FIRST ISSUE

Rev.Date

Purpose of revision
1

VG
Drawn

OSSS

CSR

DESIGNED
DRAWN
CHECKED

Checked Approved
2

OSSS
VG
OSSS

DATE
15-03-2016

FRONT SHEET
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

APPROVED
DRAWING. NO. :
CSR

AB1043-25-006

JA2267-BO-C002-001

DRW.TITLE :

Sht.
A3 Sht. 1 Rev. 0
24
Size
8

FUJI Electric owns the Copyright of this Document. It may not be reproduced or transmitted in any form or for any purpose, without the express written permission of FUJI Electric

INDEX
SHEET NO.
B

REVISION

DESCRIPTION

01

FRONT SHEET

02

INDEX

03

GENERAL ARRANGEMENT & GENERAL NOTES

04

OUTDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS,BOM

05

DETAILS OF OUTDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS

06

INDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS,BOM

07

DETAILS OF INDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS

08

BILL OF MATERIALS

09

BILL OF MATERIALS

10

SYMBOLS & DESCRIPTION

11

SINGLE LINE DIAGRAM

12

AC & DC CONTROL CONTROL SUPPLY DISTRIBUTION

13

HEATER & PANEL ILLUMINATION CIRCUIT

14

CT & PT UNIT 3-LINE POWER CIRCUIT

15

16

CT&PT UNIT METERING CIRCUIT

17

PT UNIT METERING CIRCUIT

18

PROTECTION CIRCUIT

19

LBS CLOSE & OPEN POWER CIRCUIT

20

LBS CLOSE & OPEN CONTROL CIRCUIT

LBS,CTR& PT UNIT 3-LINE POWER CIRCUIT

21

INDICATION CIRCUIT

22

DIGITAL INPUT TO FTU &DIGITAL OUTPUT FROM FTU & I/O LIST

23

COMPONENT TERMINAL LIST

24

I/O LIST

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING TITLE
INDEX SHEET
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

DRAWING No.
AB1043-25-006
2 of 24

Sht.

REV. No.
0

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

URKR

CSR

DESCRIPTION

NAME

APPROVED

DRAWN

URKR

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING TITLE
GENERAL ARRANGEMENT &GENERAL NOTES
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

DRAWING No.
AB1043-25-006
3 of 24

Sht.

REV. No.
0

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

URKR

CSR

DESCRIPTION

NAME

APPROVED

DRAWN

URKR

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

AB1043-25-006

OUTDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS, BOM


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

4 of 24

Sht.

REV. No.
0

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

URKR

CSR

DESCRIPTION

NAME

APPROVED

DRAWN

URKR

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING TITLE
DETAILS OF OUTDOOR POLE MOUNTING STRUCTURES &
EQUIPMENTS
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

DRAWING No.
AB1043-25-006
5 of 24

Sht.

REV. No.
0

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

URKR

CSR

DESCRIPTION

NAME

APPROVED

DRAWN

URKR

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

AB1043-25-006

INDOOR POLE MOUNTING STRUCTURES & EQUIPMENTS, BOM


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

6 of 24

Sht.

REV. No.
0

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

URKR

CSR

DESCRIPTION

NAME

APPROVED

DRAWN

URKR

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING TITLE
DETAILS OF INDOOR POLE MOUNTING STRUCTURES &
EQUIPMENTS
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

DRAWING No.
AB1043-25-006
7 of 24

Sht.

REV. No.
0

BILL OF MATERIAL
S.NO

ITEM CODE

ITEM DESCRIPTION

MAKE,MODEL & ORDERING CODE

A
1

MFR

MFM2

MAKE:REPUTED

Type : Numerical relay,3phase O/C+1E/F


Aux. Supply: 24V DC, CTR:630/1A,
Protection functions : 50, 51, 51N, 50N
With full program and logics as required. And with 6BI+6BO.

24V DC,100AH, VRLA Battery

INPUT :230V AC 15%,


OUTPUT :24V DC,
Suitable for load + charging 100Ah battery

MAKE: REPUTED

MAKE: RISHAB
MODEL: RISH Mater3428

DIGITAL MULTIFUNCTION METER

QTY/PANEL

MAKE: RISHAB
MODEL: RISH Mater3428

PTR :11kV/3/110V/3 AC,


Cl:0.5 , Aux.Supply:24V DC, 3-Phase, 4 Wire,
with RS485- MODBUS RTU Communication
(It will be used as digital voltmeter with in-built selector switch)

CRT:.../1A,PTR :11kV/3/110V/3 AC,


Cl:0.5 , Aux.Supply:24V DC, 3-Phase, 4 Wire,
with RS485- MODBUS RTU Communication

K1

REPEART RELAY FOR LBS STATUS

K2,K4

REPEART RELAY FOR LBS STATUS

80AC

AC SUPERVISION RELAY

10

LWS SUPPLY

LWS SUPPLY

FTU

BATTERY

MULTI FUNCTION METER 2

MFM1

MAKE: SEIMENS
MODEL :7SR10
ORDERING CODE:7SR1003-1JA20-2CA0

BATTERY CHARGER

BC

MULTI FUNCTION RELAY

TECHNICAL DETAILS

CONVERTER

MAKE: L&T
MODEL:MN0/MN0DC-22E
ORDERING CODE:SS94667
MAKE: L&T
MODEL:MN0/MN0DC-22E
ORDERING CODE:SS94667

Supply:24V DC,With 2NO+2NC

Supply:230V AC,4C/O

MAKE: REPUTED

INPUT : 24V DC
OUTPUT : 220V DC, Watt :400

230V AC, 25A, 2P Supply changover switch

11

MCO

MINIATURE SUPPLY CHANGEOVER


SWITCH

MAKE: HPL
MODEL :MCO 2P 25A

12

L/R SS

LOCAL/REMOTE SELECTOR SWITCH

MAKE: L&T
MODEL :S16-61626-B63-TD-YR

Supply:24V DC,With 2NO+2NC

MAKE: JYOTHI
MODEL:RE-400

CONVERTER

24V DC, 16A, 2Way,lockable type ,Without jumper type

13

H1

AC SUPPLY HEALTHY

MAKE: L&T
MODEL: TT01X1

RED,230V AC,Dia 22.5mm LED Indication lamp

14

H2

LBS CLOSE

MAKE: L&T
MODEL: TT01U1

RED,24V DC,Dia 22.5mm LED Indication lamp

15

H3

LBS OPEN

MAKE: L&T
MODEL: TT02U1

GREEN,24V DC,Dia 22.5mm LED Indication lamp

16

H4

PROTECTION OPERATED

MAKE: L&T
MODEL: TT07U1

AMBER, 24V DC,Dia 22.5mm LED Indication lamp

17

1R,2R

R-PHASE INDICATION LAMP

MAKE: L&T
MODEL: TB01R1

RED, 6-110V AC/DC,Dia 22.5mm LED Indication lamp

18

1Y,2Y

Y-PHASE INDICATION LAMP

MAKE: L&T
MODEL: TB04R1

YELLOW,6-110V AC/DC,Dia 22.5mm LED Indication lamp

1B,2B

B-PHASE INDICATION LAMP

MAKE: L&T
MODEL: TB06R1

BLUE,6-110V AC/DC,Dia 22.5mm LED Indication lamp

FUSES+HOLDERS

MAKE: L&T
MODEL:ST30725

MINIATURE CIRUIT BREAKER-AC

MAKE: L&T
MODEL : BB20160C

16A, DP, C-Series

SUPPLY INDICATION LAMP

MAKE:REPUTED

3ph, 415V, suitable to mount on the pole

19

20

21
22

F1-F6+NL1,NL2

MCB1-AC
LAMP

2A NS Type With holders+2Links

6+2

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING TITLE
BILL OF MATERIAL
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

DRAWING No.
AB1043-25-006
REV. No.
Sht. 8 of 24
0

BILL OF MATERIAL
S.NO

ITEM CODE

ITEM DESCRIPTION

A
23

MCB2-AC

24

MCB1-DC

TECHNICAL DETAILS

MINIATURE CIRUIT BREAKER-DC

MAKE: L&T
MODEL : BB20160C

16A, DP, C-Series

25

MCB2-DC TO MCB4-DC

MINIATURE CIRUIT BREAKER-DC

MAKE: L&T
MODEL : BB20060C

6A, DP, C-Series

26

MCB5-DC

MINIATURE CIRUIT BREAKER-DC

MAKE: L&T
MODEL : BB20060C

6A, DP, C-Series

27

Y1,Y4

DISCONNECTING TERMINALS

MAKE: CONNECTWELL
MODEL : STH4DT

Suitable up to 4sqmm cable

28

Y2,Y3

DISCONNECTING TERMINALS

MAKE: CONNECTWELL
MODEL : STH4DT

Suitable up to 4sqmm cable

29

X1,X2,X3

TERMINAL BLOCK

MAKE: CONNECTWELL
MODEL:CSB3/N3U

Suitable for 1.5 to 6sqmm cable

60

30

PB OPEN,PB CLOSE

PUSH BUTTON

MAKE: L&T
MODEL : HD15C1+HC61A2+HC61B2

24V DC, 1NO+1NC,


Flush head non illuminated type

31

PIL

PANEL ILLUMINATION LAMP

MAKE: PHILIPS/REPUTED

230V AC, 10W, CFL With holder

32

HA

SAPCE HEATER

MAKE: APT Controls/REPUTED

230V AC, 40W

TH

THERMOSTAT

MAKE: APT Controls/REPUTED

230V AC,6" stem type, (0-60Degree C)

34

PSS

3Pin Plug socket with switch

MAKE: ANCHOR/REPUTED

230V AC,15A

35

DLS

DOOR LIMIT SWITCH

MAKE: JANSON/REPUTED

230V AC,5A

36

EL1 & EL2

BOLTED EARTH LINKS

MAKE: SURAJ/REPUTED

2A

37

TSW

TOGGLE SWITCH

MAKE: SURAJ/REPUTED

230V AC,2A

38

H5

DC Supply healthy

MAKE: L&T
MODEL: TT01U1

RED,24V DC,Dia 22.5mm LED Indication lamp

39

EXAUST

EXAUST FAN

MAKE: HI-COOL
MODEL:12A230HBAC

230V AC,17Watt,0.1A

40

1ZJ,2ZJ

POWER CONTACTOR

MAKE: L&T
MODEL: MDX9
ORDERING CODE:CS96564+CS96569)

220V DC, 9A,3NO+2NC

MAKE: JYOTHI
MODEL:RE-400

Supply:24V DC,4C/O

80DC

DC SUPERVISION RELAY

LOAD BREAK SWITCH

MAKE: Electrolites/ System Control/


REPUTED

11KV, 630A, 16KA/1Sec,


Close & Open Operation :Manual & Electrical
Operating mechanism:220V DC, With AUX Contact :2NO+2NC

43

PT

OIL IMMERSED POTENTIAL


TRANSFORMER
(OUT DOOR POLE MOUNTED)

MAKE: REPUTED

11KV, 3-Phase, PTR :11kV/3kV /110/3V,


core 1: Class: 0.5, Burden: 30VA.
1.2 Times continuous & 1.9 times for 30sec

OIL IMMERSED CURRENT


TRANSFORMER
(OUT DOOR POLE MOUNTED)

MAKE: REPUTED

REVISION

CTR

CONTROL TRANSFORMER
(OUTDOOR POLE MOUNTED)

MAKE: REPUTED

1Phase6.6KV/230V,1KVA

46

SA

SURGE ARRESTER
(OUTDOOR POLE MOUNTED)

MAKE: ESWARI

'9kV, 5kA, Metal Oxide, Surge Arrester - Outdoor type

CABLES

CABLES

'12C X 2.5sqmm tinned copper multi strand PVC insulated armoured


cable (YWY)
'4C X 2.5sqmm tinned copper multi strand PVC insulated armoured
cable (YWY)
'2C X 2.5sqmm tinned copper multi strand PVC insulated armoured
cable (YWY)

MAKE: REPUTED

11KV, 3-Phase, Ratio: 630/1-1A,


Core 1: Class: 0.5, Burden: 15VA
Core 2: Class: 5P10, Burden: 15VA

45

47

DATE

LBS

CT

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

42

44

NO

20

33

41

30-03-2016

6A, DP, C-Series

QTY/PANEL

MAKE: L&T
MODEL : BB20060C

MINIATURE CIRUIT BREAKER-AC

MAKE,MODEL & ORDERING CODE

As Required
As Required

DRAWING No.

DRAWING TITLE

AB1043-25-006

BILL OF MATERIAL
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

As Required

9 of 24

Sht.

REV. No.
0

SYMBOLS & DESCRIPTION


A

A
50

INSTANTANEOUS OVER CURRENT PROTECTION

50N

INSTANTANEOUS EARTH FAULT PROTECTION

INDICATION LAMP

LOAD BREAK SWITCH

PUSH BUTTON
51

IDMT OVER CURRENT PROTECTION

51N

IDMT EARTH FAULT PROTECTION

CURRENT TRANSFORMER (CT)

MFR

MULTI FUNCTION RELAY

FUSE (F)

80AC

AC SUPPLY SUPERVISION RELAY

MFM

80DC

DC SUPPLY SUPERVISION RELAY

AMMETER

VOLTMETER

MULTI FUNCTION METER

MINIATURE CIRCUIT BREAKER


CONTACTOR COIL
CT DISCONNECTING TERMINAL

POWER SUPPLY SOCKET

X1, X2, X3

PANEL TERMINAL BLOCK

PROTECTIVE EARTH

CTR

CONTROL TRANSFORMER

LOCAL / REMOTE SELECTOR SWITCH

C
SWITCH (DOOR OPTD)

LIMIT SWITCH

NL

NEUTAL LINK

MOTOR

THERMOSTAT

NO CONTACT

ISOLATION LINK

NC CONTACT
TERMINAL BLOCK
CHANGE OVER CONTACT

SURGE ARRESTER

PLUG & SOCKET TYPE TERMINAL

HEATER

POTENTIAL TRANSFORMER

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

AB1043-25-006

SYMBOL & DESCRIPTION


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

10 of 24

Sht.

REV. No.
0

SINGLE LINE DIAGRAM


415V, 3Ph, 4Wire supply

CT & PT UNIT
SUPPLY INDICATION LAMPS

LBS AND SECTIONALISER

PT
3-Phase
PTR :11kV/3V /110V/3,
Core 1: Class: 0.5,30VA

2A

Y1

FUSE
(F1-F4)

1R/1Y/1B

P1

CORE - 1
CL:0.5,15VA
ISF5

Y2

MFM1

CT
630/1-1A,
16kA/1sec

CTR:630/1A,
PTR :11kV/3/110V/3 AC,
Cl:0.5
Y3

CORE - 2
CL:5P10,15VA

50

P2

51

50N 51N

LBS UNIT

80AC

LBS
11kV, 630A
16kA/1Sec

H1

H2

80DC

H3

H4

H5

PT UNIT

PT
3-Phase
PTR :11kV/3V /110V/3,
Core 1: Class: 0.5,30VA

2A

2R/2Y/2B

Y4
MFM2

FUSE
(F5-F8)

CTR UNIT
1Phase6.6KV/230V,1KVA

MCB AC
16A,DP

MCB DC
16A,DP

230V AC
24V DC

BATTERY CHARGER
INPUT:230V AC 15%,
OUTPUT: 24V DC, load
+charging 100Ah battery

SA 3 UNITS

CONVERTER
400Watt
24V DC
220V DC

BATTERY
24V, 100AH,
VRLA

SA
9kV, 10kA

* APPLICABLE ONLY
FOR SECTION-2,LBS-3

SUPPLY INDICATION LAMPS

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

SINGLE LINE DIAGRAM


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

11 of 24

Sht.

REV. No.
0

230V AC CONTROL SUPPLY DISTRIBUTION


-MCO DP
25A

-MCB1-AC
16A, DP

H1

/15.D7

230V AC FROM
CTR

H5

2
4
6

H2

/15.D7

-X1
230V AC FROM EXTERNAL
SOURCE FOR MAINTENANCE
PURPOUS

/23.C6

1
H6

BC
BATTERY CHARGER
INPUT:230V AC 15%,
OUTPUT: 24V DC

H7

H8

H8

/12.C2

J2

TO 24V DC CIRCUIT

/12.C2

'-'Ve

/23.C2

H3

'+'Ve

B
24V, 100AH,
VRLA
J1

2
/23.C2

/23.C6

H7

3
-MCB2-AC
6A, DP

H4
4
-H1
(RED)

/23.C3

/23.B3

-80AC
2

H9

/13.B3

1
3

H10

/13.D3

TO SPACE HEATER &


PANEL ILLUMINATION
CIRCUIT

/23.C3

AC SUPPLY
HEALTHY

24V DC CONTROL SUPPLY DISTRIBUTION


/12.A7

-MCB1-DC
16A, DP

J1

24V DC

-MCB2-DC
6A, DP

3
/23.C2

X1

/23.C4

J4
3

X2

/22.C3

-MCB3-DC
6A, DP

L101
/16.A8

2
/23.C4

TO FTU
(EXTERNAL UNIT)

/23.D4

1
-80DC
2

L102

/16.A8

TO
INDICATION&METERS,
RELAY &ANNUNCIATOR

/23.C4
/23.B4

-H5
(RED)

/22.C3

/23.C2

J2

/12.A7

J3

-MCB4-DC
6A, DP
1

/20.A2

2
/23.C5

DC SUPPLY
HEALTHY

K3
K2
/20.E2

4
/23.C5
-K2
13
13

/23.B5

TO
LBS CLOSING &OPENING CIRCUIT

CONVERTER
400Watt
14

J5

J7
'+'Ve 24V DC

14

/23.B4
-K1

'-'Ve

/12.E3

'+'Ve

220V DC

J6

TO
220V DC DISTRIBUTION CIRCUIT

/12.E3

'-'Ve

220V DC CONTROL SUPPLY DISTRIBUTION

-MCB5-DC
6A, DP

J7

/12.E7

E
K51

/19.A2

2
/23.C6

220V DC

J6

/12.E7

K52
3

/23.D6

TO
LBS MOTOR CONTROL CIRCUIT

/19.E2

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

AB1043-25-006

230V AC&24V DC,220V DC DISTRIBUTION


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

12 of 24

Sht.

REV. No.
0

HEATER &PANEL ILUMINATION CIRCUIT

/12.B7

H9

1
TSW
2
1
H11

DLS
2

P
S

230V AC
1
O

-TH
THERMOSTAT 2

H13

PSS

1
H12

PIL

PS N

1
-HA
(PANEL HEATER)
2

/12.B7

H10
SPACE HEATER
WITH SWITCH &
THERMOSTAT

PANEL ILLUMINATION
LAMP

POWER SWITCH
SOCKET

EXAUST FAN

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

HEATER &PANEL ILLUMINATION CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006
REV. No.
Sht. 13 of 24
0

CT & PT UNIT

11kV INCOMING

SUPPLY INDICATION LAMPS

-X1

PT
3-Phase
PTR :11kV/3V /110V/3,
Core 1: Class: 0.5, 30VA

1E11
5

1E12

1E13

1E10

B
/16.C2
/16.C2
/16.C2

TO
METERING CIRCUIT

/16.C2

P1
-X1

1S1

D11
9
D10

C
10

1S2
1S1

D31
11

CORE - 1
CL:0.5,15VA
ISF5

D30
12

1S2
1S1

D51
13
D50
14

1S2

CT
630/1-1A,
16kA/1sec

/16.D2
/16.D2

TO
METERING CIRCUIT

/16.D2

/16.E2
/16.E2

D
C11

2S1
15

C10
16

2S2
2S1

C31
17
C30
18

2S2
2S1

C51
19

/16.D2

CORE - 2
CL:5P10,15VA

/18.B2
/18.B2

TO
PROTECTION CIRCUIT

/18.B2
/18.C2

E
C50

20

2S2

/18.B2

/18.C2

P2

REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

/15.A2

/15.A2

/15.A2

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

CT & PT UNIT POWERCIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

14 of 24

Sht.

REV. No.
0

/14.F2

/14.F2

/14.F2

LBS UNIT
A

PT UNIT
-X1

PT
3-Phase
PTR :11kV/3V /110V/3,
Core 1: Class: 0.5, 30VA

2E11
21

2E12

22

2E13

23

2E10

24

/17.C2
/17.C2

TO
METERING CIRCUIT

/17.C2
/17.C2

CTR UNIT

CTR
6.6kV/230V AC,1KVA

-X1

D
230V AC
SUPPLY

H1
1
H2
2

/12.A1
/12.A1
TO 230V AC
DISTRIBUTION
CIRCUIT

SA 3 UNITS
SA
9kV,5kA

* APPLICABLE ONLY
FOR SECTION-2,LBS-3

SUPPLY INDICATION LAMPS

11kV OUTGOING
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

LBS,CTR &PT POWER CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

15 of 24

Sht.

REV. No.
0

TO FTU

METERING CIRCUIT
L101

/12.C7
24V DC

L102

/12.D7

LWS SUPPLY
L101
+

FUSE1-3
2A

1E11

/14.B7

1E12

11

-1R
1E31
1

-NL1

/14.B7

-1B

3
1E20

C
2

1E30
4

-Y2

D11

D12

1
D10

/14.C7

**

FROM CT&PT UNIT


PT-METERING CORE
CT-METERING CORE

1E33

2A

/14.C7

-1Y

1E32

1E23

1E10

Y1
1E21
1E22

1E13

/14.B7

/17.A8

L102

MFM

1
/14.B7

24V DC

13
14
+
AUX. SUPPLY

RS-485

/17.A8

3
D32

D31

/14.C7

4
D30

/14.C7

**

CT DISCONNECTING TERMINALS PROTECTION CORE-1 (**) :-Y2


6

D51

/14.D7

1. CLOSE LINKS 1,2,4,5,7,8,10 & OPEN LINKS 3,6,9 FOR NORMAL OPERATION.
2. CLOSE LINKS 3,6,9 & OPEN LINKS 1,2,4,5,7,8 TO BY PASS RELAY FROM CT
3. INJECT TEST CURRENT FROM 1,2,4,5,7,8 TOP TERMINALS FOR RELAY TESTING
4. #Supply of cables between VCB panel and FTU not included in the scope.

D52
7

D50

/14.D7

**

8
9
-EL1
T
B

D70
C90

10

C92

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

AB1043-25-006

CT&PT UNIT METERING CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

16 of 24

Sht.

REV. No.
0

METERING CIRCUIT

TO FTU

L101

L102
L101
+

FUSE4-6
2A
2E11

/15.C7

11

-2R
1
-2Y

2E32

2E23

2E10

-NL2

/15.C7

2E31

2E22

2E13

/15.C7

/21.D3

L102

Y4
2E21

2E12

/15.C7

/21.A3

MFM

1
FROM PT UNIT
PT-METERING CORE

24V DC
/16.B8

24V DC

13
14
+
AUX. SUPPLY

RS-485

/16.A8

-2B

2
2

2E33
1

3
2E20

2E30

2A

*MFM CAN BE USED AS DIGITAL VOLTMETER WITH RS-485 COMMUNICATION PORT


#Supply of cables between VCB panel and FTU not included in the scope.

REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

F
AB1043-25-006

PT UNIT METERING CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

17 of 24

Sht.

REV. No.
0

PTOTECTION CIRCUIT
A

A
MFR
7SR10

-Y3

C11

/14.D7

X5

REAR VIEW OF RELAY


MFR
7SR10

X5

X4
1

C12
3

BO1

2
3
4

BO2

5
6

C10

**

/14.D7

2
3

8
9

BO4

10

BO5

12
13

**

C71

BO6

6
C52

C50
X1

**

2
3

C70
-EL2
T
B

C90

14

10

10

TERM

A/+

GND

B/-

7
/14.E7

X2

C51

/14.E7

Sht.21

11

C30

/14.E7

BO3

C32
4

FROM CT
PROTECTION CORE

OC+E/F PROTECTION OPERATED

C31

/14.E7

PROTECTION OPERATED
Sht.22

12

C92

6
7
8
9

10
11
12

X2

+
-

BI 1

POWER SUPPLY

+
BI 2
+
BI 3
-

L101
L102

/21.B3

24V DC

/21.D3

+
BI 4
+
BI 5
-

+
BI 6
-

CT DISCONNECTING TERMINALS PROTECTION CORE-2 (**) :-Y3


1. CLOSE LINKS 1,2,4,5,7,8,10 & OPEN LINKS 3,6,9 FOR NORMAL OPERATION.
2. CLOSE LINKS 3,6,9 & OPEN LINKS 1,2,4,5,7,8 TO BY PASS RELAY FROM CT
3. INJECT TEST CURRENT FROM 1,2,4,5,7,8 TOP TERMINALS FOR RELAY TESTING

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

PROTECTION CIRCUIT
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

18 of 24

Sht.

REV. No.
0

LBS CLOSE & OPEN POWER CIRCUIT


A

A
K51

43
-1ZJ

44

43

/23.B2

-K2

/23.B5

43

/23.B4

43
-K1
44

-2ZJ

44

/23.B2

/12.E7

44
CZ1

K53

-X3

K56

-1ZJ
22

53
-2ZJ

220V DC

K54

K57

A1

A1

54

K60

53
/23.B2

/23.B2

21

/23.B2

21
-2ZJ
22

-X3
4

K59

/23.B2

-1ZJ
54

-1ZJ

-2ZJ

A2
K55
-X3 1

A2
K58
-X3

CZ1

/23.B2

C
/23.B2

C
K61
-X3
2

3
ST2

ST1

D
M

/12.E7

-X3

K52

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

LBS CLOSE & OPEN POWER CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

19 of 24

Sht.

REV. No.
0

LBS CLOSE & OPEN CONTROL CIRCUIT


/12.D7

Remote close

K3

Manual close

REMOTE

Remote open

Manual open

LOCAL

-LIR

/23.B6

-LIR

1
2

/23.B6

K4

K3
K4

12
K5

/22.B3

/22.B3

23
-PB-CLOSE
24

24V DC

13
-2ZJ
14

K10

OPEN PULSE 1Sec


FROM FTU

/23.A6

CLOSE PULSE 1Sec


FROM FTU

14

12

/23.B2

/22.B3

/23.B2

-1ZJ

-PB-CLOSE

/23.B6

-PB-OPEN
13

23
-PB-OPEN

/23.A7

/23.B7

11

K3

11

/22.B3

K3

24

K6

K8

K6

22

-K1

/23.B5

-K2

22

/23.B4

21
21

D
K9

A1

A1

/23.B4

K7

-K1
A2

-K2

/23.B5

A2

K2
/12.D7

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

AB1043-25-006

LBS CLOSE & OPEN CONTROL CIRCUIT


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

20 of 24

Sht.

REV. No.
0

INDICATION CIRCUIT

A
/17.A8

/18.C8

L101

L101
-X2
5

-X2
6

11

13

CJ1

B
MFR
7SR10

24V DC

10

12

-X2
7

-X2
8

(OC/EF
OPERATED)
Sht.18

5
6

L104

/18.C8

/17.B8

-H2
RED

L102

L105

-H3
GREEN
2

A1

/23.C7

L103

-K4
A2

-H4
AMBER
2

L102
LBS CLOSE

LBS OPEN

LBS STATUS
REPEAT RELAY

PROTECTION OPERATED

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

O / S NO.

DRAWING No.

DRAWING TITLE

AB1043-25-006

INDICATION CIRCUIT
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

21 of 24

Sht.

REV. No.
0

DIGITAL OUTPUTS FROM FTU


A

RTU
-X2

K3

/20.B3

1
LBS CLOSE

-X2

K6

/20.C3

B
-X2

K3

/20.B5

3
-X2

K8

/20.C5

LBS OPEN

DIGITAL INPUTS TO FTU


C
24V DC
TO FTU

9
-X2

X2

/12.C7

-X2

X3

11

/23.B3

12

-80DC
3
7

X5
X6

MFR
7SR10
(OC/EF OPERATED) X7
1

Sht.18

-X2
13
-X2

/23.B4

AC Supply fail

-X2

X4

24V DC

10

-80AC
11
3
7

11

-X2

X1

/12.C7

X8

DC Supply fail

14
-X2
15
-X2

Protection operated

16
-K4
X9
21

22
X10
-K4
X11

13

14

7
*1.FTU Shall be mounted outside the VCB panel.
2.FTU and mounting arrangements supply not included in the scope.
3.Supply of cables between LBS/SECTIONALISER panel and RTU not included in the scope.
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

/23.B6

17
-X2

LBS CLOSE

X12

-X2

X13

20
-X2

X14

21
-X2

LBS OPEN

REMOTE SELECTED

22

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

18
-X2
19

/23.D7

-LIR

-X2

AB1043-25-006

DIGITAL INPUS TO FTU & DIGITAL OUTPUTS FROM FTU


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

22 of 24

Sht.

REV. No.
0

COMPONENT LIST

-2ZJ

-1ZJ

MDX9+3NO+2NC
A1 A2
/19.C4
b 21 22 /19.B3

MDX9+3NO+2NC
A1 A2
/19.C3
b 21 22 /19.B4

b 31 32 SPARE

b 31 32 SPARE

a 13 14 /20.B2
a 43 44 /19.B5
a 53 54 /19.C6

a 13 14 /20.B7
a 43 44 /19.B6
a 53 54 /19.C5

-80AC
JYOTHI RE-400
1
2
/12.B4
3 /22.D3
C/O 11
7
4
SPARE
C/O 12
8
5
SPARE
C/O 13
9
6
C/O 14
10 SPARE

-K1

-80DC
JYOTHI RE-400
1
2
/12.D4
3 /22.D3
C/O 11
7
4
C/O 12
SPARE
8
5
SPARE
C/O 13
9
6
C/O 14
10 SPARE

-LIR

-K2

MN0/MN0DC-22E
A1 A2
/20.D4
b 21 22 /20.D6

MN0/MN0DC-22E
A1 A2
/20.D6
b 21 22 /20.D4

/20.A4

11 12

-PB-CLOSE
/20.B6

11 12

-PB-OPEN
/20.B4

/20.A3

23 24

/20.B4

23 24

/20.B4

31 32 SPARE

31 32 SPARE

SPARE

13 14 /12.E5

13 14 /12.E5

/22.F3

43 44 /19.B3

43 44 /19.B4

-MCB1-AC

-MCB1-DC

-MCB2-AC

-MCB3-DC

-MCB2-DC

-MCB4-DC

-K4

-MCO DP

-MCB5-DC

Ma 1

/12.A3

Ma 1

/12.C3

Ma 1

/12.B5

Ma 1

/12.C5

Ma 1

/12.D5

Ma 1

/12.D5

Ma 1

/12.E5

Ma 3

/12.A3

Ma 3

/12.C3

Ma 3

/12.B5

Ma 3

/12.C5

Ma 3

/12.D5

Ma 3

/12.D5

Ma 3

/12.F5

C/O

C/O

/12.A3

4
6

/12.A3

MN0/MN0DC-22E
A1 A2
/21.D6
b 21 22 /22.E3
b

31 32

13 14 /22.E3

SPARE

43 44

SPARE

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS

30-03-2016

APPROVED

CSR

30-03-2016

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED
JOB NO.

DATE

AB1043-25-006

COMPONENT LIST & I/O LIST


SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

23 of 24

Sht.

REV. No.
0

I/O list LBS panel


Metering to FTU (MODBUS)
SL.No

Communication Type

Signal
MFM-1

1
2
3
4
5
6
7
8
9
10

R,Y,B Phase Voltage line-1


R,Y,B Phase Currents
kW
kVA
kVAr
kWh
kVAh
kVArh
Power factor
Frequency

MODBUS RTU (RS485)

MFM-2
1

R,Y,B Phase Voltage line-2

SL.No

Signal

1
2
3
4
5
6

AC Supply fail
DC Supply fail
Protection operated
LBS CLOSE
LBS OPEN
REMOTE SELECTED

SL.No
1
2

MODBUS RTU (RS485)


Digital inputs to RTU
Signal Type

Channel No

High
High
High
High
High
High

DI-1
DI-2
DI-3
DI-4
DI-5
DI-6

Digital Outputs from RTU


Signal Type
High
High

Signal
LBS Close Command
LBS Open Command

Channel No
DO-1
DO-2
E

F
REVISION

NO

30-03-2016
DATE

FIRST ISSUE

VG

DESCRIPTION

NAME

CSR
APPROVED

DRAWN

VG

30-03-2016

CHECKED

OSSS
CSR

30-03-2016

APPROVED

SCALE
N.T.S

ASA BHANU
TECHNICAL SERVICES LIMITED

30-03-2016

JOB NO.

DATE

AB1043-25-006

I/O LIST
SCHEMATIC DIAGRAM FOR LBS / SECTIONALISER

O / S NO.

DRAWING No.

DRAWING TITLE

24 of 24

Sht.

REV. No.
0