EZ Meter-Pak Meter Centers

Class 4100
Catalog
4100CT0701

2008

EZMH114125

EZM32000CB

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Application Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

EZ Meter-Pak Meter Centers


Table of Contents

Table of Contents
EZ METER-PAK METER CENTERS
UL Listed Meter Center Short Circuit Current Ratings . . . . . . . . . . . . . . . . .4
EZM Typical Equipment Lineups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
EZ Meter-Pak (EZM) Meter Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Utility Company Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Equipment Short Circuit Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . .6
Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Main Device Ampere Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Main Circuit Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Main Fusible Switch Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Terminal Box Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Branch Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
125 A Maximum Residential Branch Units . . . . . . . . . . . . . . . . . . . . . . . .9
225 A Maximum Residential Branch Units . . . . . . . . . . . . . . . . . . . . . . . .9
225 A Maximum Commercial Branch Units . . . . . . . . . . . . . . . . . . . . . .10
400 A Maximum Commercial Branch Units . . . . . . . . . . . . . . . . . . . . . .10
Bussed Extension Sections (NEMA Type 3R) . . . . . . . . . . . . . . . . . . . . . .11
Bussed Corner Sections for Indoor (NEMA Type 1) Construction Only . . .11
Mounting Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Rotating Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Main Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Single-Phase Branch Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Three-Phase Branch Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Closing Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Closing PlatesMain Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Closing PlatesBranch Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Closing PlatesMain Devices and Branch Units . . . . . . . . . . . . . . . . . .17
Horizontal Cross Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Equipment Grounding Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Visi-Tite Nut Horizontal Cross Bus Connectors . . . . . . . . . . . . . . . . . .19
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Sealing Rings for Ring-Type Meter Sockets . . . . . . . . . . . . . . . . . . . . . .20
Circuit Breaker Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Individual Meter Socket Closing Plates. . . . . . . . . . . . . . . . . . . . . . . . . .20
Branch Unit Outer Covers for Tenant Circuit Breaker and
Individual Meter Socket Compartments . . . . . . . . . . . . . . . . . . . . . . . . .21
Branch Unit Load Neutral Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Branch Unit Load Equipment Grounding Terminals . . . . . . . . . . . . . . . .22
Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Branch Unit Tenant Circuit Breaker Types and
Meter Socket Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Ring-Type Residential Meter Socket Compartment Standard Features .23
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
125 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .26
225 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .26
Optional Ringless Residential Meter Socket Features . . . . . . . . . . . . . .26
400 A Tenant Circuit Breaker Compartment . . . . . . . . . . . . . . . . . . . . . .28
Optional Ringless Commercial Meter Socket Features . . . . . . . . . . . . .30
Factory Phase Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Phase Balancing Flexibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
EZM Main Device Types and Configurations . . . . . . . . . . . . . . . . . . . . . . .33
Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
2
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers

NEMA 3R Construction
240 Vac Maximum, for use on AC systems, suitable for
use as Service Equipment.
Utility Company Requirements: Review local utility
requirements to ensure that metering equipment meets
their standards.
EZ Meter-Pak meter center enclosures meet NEC wire
bending requirements, and are designed for wall mounting
only (not suitable for floor mounting). All unmetered
conductor compartments may be sealed by the utility
company.
EZ Meter-Pak meter centers have UL Listed short circuit
current ratings up to 100 kA at 240 Vac when properly
applied. For three-tier series ratings, refer to Data Bulletin
4100DB0301 and Instruction Bulletin 80043-303-19.
Suitable incoming services for an EZM main device and
available outgoing feeder(s) to downstream panelboards
from EZM branch section(s)
Incoming Service to Main Device 120/240 Vac, 13W
Available outgoing feeder(s) to downstream panelboards:

120/240 Vac, 13W (Fed from transformers A-Phase and


C-Phase only.) NOTE: Connection to High-Leg B-Phase
not permitted for this service.
(four-jaw ring type meter sockets, two-pole circuit breakers)
(five-jaw ringless meter sockets, two-pole circuit breakers)
Standard 3 IN/1 OUT branch units are not suitable for
use on this Delta System. Special branch units are
available for this System by adding suffix: CA to catalog
number (Typical Examples: EZM313125CA,
EZM313125XCA, EZM313125CUXCA, EZM314225CA,
EZM314225XCA, EZM314225CUXCA, EZM315225CA,
EZM314225CUCA, etc.).
240/120 Vac, 34W Delta (seven-jaw meter sockets, threepole circuit breakers)

Incoming Service to Main Device 208Y/120 Vac, 34W


Available outgoing feeder(s) to downstream panelboards:

120/240 Vac, 13W


(four-jaw ring type meter sockets, two-pole circuit breakers)
(five-jaw ringless meter sockets, two-pole circuit breakers)

Incoming Service to Main Device 240/120 Vac, 34W


Delta
Available outgoing feeder(s) to downstream panelboards:

Branch Units:

120/208 Vac, 13W (five-jaw meter sockets, two-pole circuit


breakers)
208Y/120 Vac, 34W (seven-jaw meter sockets, three-pole
circuit breakers)

Note: QO, QO-VH and QO-H tenant circuit breakers used


in 225 A branch units require the use of adapter
EZM125QOA (purchased separately).
400 A branch units are available in ringless type

mounted.

2000 A main disconnect or terminal box must be center


mounted and requires use of branch units having 1200 A
continuous horizontal cross bus.
400, 800 and 1200 A Type EZM-TBU tap boxes supplied with
lug landings to meet EUSERC requirements.

Main Circuit Breaker, ratings: 400, 600, 800, 1000, 1200,


1600 and 2000 A
Main Fusible Switch, ratings: 400, 600, 800, and 1200 A
(13W only)
Main Lugs Terminal Box, ratings:
225, 400, 600, 800, 1200, 1600 and 2000 A

Tenant circuit breakers must be ordered separately for these


branch units. 125 A max. units make use of Type QO, QO-VH
or QO-H two-pole tenant circuit breakers (40125 A). 225 A
max. units make use of Type QDP-TM, QBP-TM, QGP-TM
and QJP-TM two-pole tenant circuit breakers (70225 A), and
may also make use of two-pole Type QO (40125 A at 10 kA
max.), two-pole Type QO-VH (4060 A at 100 kA max.), or
two-pole Type QO-H (4060 A at 100 kA max.) tenant circuit
breakers.
225 A commercial branch units are available in ring type
or ringless type construction and are supplied with 1200 A
copper horizontal cross bus with aluminum vertical
connectors as standard (Example: EZML314225). For
optional 1200 A continuous all-copper bussing, add suffix
CU to catalog number (Example: EZML314225CU).
Plug-in style commercial meter sockets are available as ring
type EZMT with test block bypass (meets EUSERC
requirements), ringless type EZMR without bypass, and
ringless type EZML with lever bypass.
225 A max. units make use of type QDP-TM, QBP-TM, QGPTM and QJP-TM two-pole or three-pole tenant circuit breakers
(70 225 A), and may also make use of two-pole type QO
(40125 A at 10 kA max.), two-pole type QO-VH (4060 A at
100 kA max.), or two-pole type QO-H (4060 A at 100 kA
max.) tenant circuit breakers.

Main Devices:
400, 600 and 800 A main disconnects may be end mounted
with branch units having 800 A or 1200 A continuous
horizontal cross bus.
1000 and 1200 A main disconnect or terminal box must be
center mounted when used with branch devices with main
bus rated 800 A continuous.
1600 A main disconnect or terminal box must be center

125 A and 225 A residential branch units are available


in ring type or ringless type construction and are supplied with
800 A continuous aluminum horizontal cross bus as standard
(Example: EZM314125). For optional 1200 A continuous
copper horizontal cross bus with aluminum vertical
connectors, add suffix X to catalog number (Example:
EZM314125X). For optional 1200 A continuous all-copper
bussing, add suffix CUX to catalog number (Example:
EZM314125CUX). NOTE: Five-gang 225 A EZM, EZMR and
EZMH residential branch units are supplied with 1200 A
continuous cross bus as standard, do not add suffix X or
CUX to these units (Examples: EZMR315225 or
EZMR315225CU). Plug-in style residential meter sockets are
available as ring type EZM without bypass, ringless type
EZMR without bypass, and ringless type EZMH with horn
bypass.

construction only, and are supplied with 1200 A continuous


all-copper bussing as standard (Example: EZML332400).
These branch units are supplied with factory-installed type
DJM tenant circuit breakers that have a field adjustable
ampere rating trip setting from 160 A min. to 400 A max. A
tamper-evident seal kit is available where needed, order seal
kit 29375 (refer to NEC 240-6 [c]). 400 A branch units are
available as Type EZML with plug-in style lever bypass type
meter sockets, or Type EZMK with bolt-on style with manual
bypass type meter sockets.
Units having 800 A continuous horizontal cross bus
WILL CONNECT with units having 1200 A continuous
horizontal cross bus.
Single phase units (three bus bars in horizontal cross bus)
WILL NOT CONNECT with three phase units (four bus
bars in horizontal cross bus).

For Load Center Three-Tiered Series Ratings used


downstream from Metering Equipment, refer to Data
Bulletins 4100DB0301 and 2700DB9901.

3
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers

Review local utility requirements to ensure that metering


equipment meets their standards.
Check local utility to determine available fault current at the
meter center.

Using the SCCR table:

Select meter center configuration, main lugs only (Six


Disconnect Rule), or remote main, main circuit breaker, or
main fusible switch.
Read down to select SCCR equal to, or greater than desired
rating.
Read across to select branch unit tenant circuit breaker type.
Continue reading across to select EZM main device type.

UL Listed Meter Center Short Circuit Current Ratings (SCCR)


Tenant circuit breakers of same frame size having higher AIR values may replace tenant circuit breakers as listed in tables below and maintain the series rating.
EZM Meter Center Overcurrent Protection Devices
Short Circuit
EZM Branch Unit Tenant Circuit Breaker
Current Rating
EZM Main Device with Integral Mounted Main,
Types Available (Branch Unit Amperes max.,
(240 Vac
Remote Mounted Main or without an Upstream Mounted Main
Number of Poles, Tenant Circuit Breaker
Maximum) a b
(Six Disconnect Rule)
Amperes Rating Range)

Figures

EZM Branch Units

Load
Centers
(Main Lugs)

Service
Disconnects
(6 Max.)
T ransformer

EZM Main Lugs


Terminal Box

Figure 1

EZM Main Lugs Terminal Box


EZM Branch Units

Transformer

Tenant
Circuit
Breakers

EZ Meter-Pak (Six Disconnect Rule Applications)See Figure 1


QO (125 A, 2P, 40125 A)
10 kA
QO (225 A, 2P, 40125 A) d
QB (225 A, 2P or 3P, 70225 A)
QO-VH (125 A, 2P, 40125 A )
22 kA
QO-VH (225 A, 2P, 4060 A) d
4002000 A Main Lugs Terminal Box
25 kA
QD (225 A, 2P or 3P, 70225 A)
(Tenant Circuit Breakers used as Service Disconnects6 maximum)
QOH
(125
A,
2P
,
40125
A)
42 kA
QOH (225 A, 2P, 4060 A) d
65 kA
QG (225 A, 2P or 3P, 70225 A)
QJ (225 A, 2P or 3P, 70225 A) c
100 kA
DJM (400 A, 2P or 3P, 160400 A) c e
EZ Meter-Pak 2252000 A Main Lugs Terminal Box Applications Protected By Remote MainSee Figure 2
QO (125 A, 2P, 40125 A)
QO (225 A, 2P, 40125 A) d
10 kA
Must be protected by an upstream disconnecting means rated 10 k AIR minimum
QB (225 A 2P or 3P, 70225 A)
DJM (400 A, 2P or 3P 160400 A) e
QO-VH (125 A, 2P, 40125 A)
22 kA
QO-VH (225 A, 2P, 4060 A) d
Must be protected by an upstream disconnecting means rated 22 k AIR minimum
DJM (400 A, 2P or 3P, 160400 A) e
QD (225 A 2P or 3P, 70225 A)
25 kA
Must be protected by an upstream disconnecting means rated 25 k AIR minimum
DJM (400 A, 2P or 3P, 160400 A)e
QOH (125 A, 2P, 40125 A)
d
QOH (225 A, 2P, 4060 A)
Must be protected by an upstream disconnecting means rated 42 k AIR minimum
DJM (400 A, 2P or 3P, 160400 A) e
42 kA
QO-VH (125 A, 2P, 40125 A)
Must be protected by a Square D circuit breaker
QO-VH (225 A, 2P, 4060 A) d
Type LA (400 A max.) or MA (1000 A max.) Rated 42 k AIR minimum
QD (225 A 2P or 3P, 70225 A)

Load
Centers
(Main Lugs)

Upstream Disconnection
Means and Overcurrent
Protection as required

65 kA

Figure 2

QG (225 A 2P or 3P, 70225 A)


DJM (400 A, 2P or 3P, 160400 A) e
QO-VH (125 A, 2P, 40125 A)
QO-VH (225 A, 2P, 4060 A) d
QD (225 A 2P or 3P, 70225 A)

Must be protected by an upstream disconnecting means rated 65 k AIR minimum

QD (225 A 2P or 3P, 70225 A)

Must be protected by a Square D circuit breaker Type MG (800 A max.), PG (1200 A max.) or
RG (2000 A max.) rated 65 k AIR minimum

QJ (225 A 2P or 3P, 70225 A ) c


DJM (400 A 2P or 3P, 160400 A) c e
QO-VH (125 A, 2P, 40125 A)
QO-VH (225 A, 2P, 4060 A) d
QD (225 A 2P only, 70225 A)

EZM Circuit Breaker Main


or EZM Main Fusible Switch
EZM Branch Units

Transformer
Tenant
Circuit
Breakers

Figure 3

Load
Centers
(Main Lugs)

Must be protected by a Square D circuit breaker Type LH (400 A max.), MH (1000 A max.) or
PA (1600 A max.) rated 65 k AIR minimum

Must be protected by an upstream disconnecting means rated 100 k AIR minimum

Must be protected by an upstream disconnection means with Class R (600 A max.), or


Class T (300 Vac, 800 A maximum) fuses.
100 kA
Must be protected by an upstream disconnection means with Class J (600 A max.), Class L
(1200 A max.), Class R (600 A max.), Class T (300 Vac, 1200 A max.) or Class T (600 Vac,
800 A maximum) fuses; or protected by a Square D circuit breaker Type MJ (800 A max.), PJ
QD (225 A 3P only, 70225 A) c
(1200 A max.), PH (1600 A max.) or RJ (2000 A max.) rated 100 k AIR minimum.
EZ Meter-PakMain Circuit Breaker ApplicationsSee Figure 3
QO (125 A, 2P, 40125 A)
10 kA
QO (225 A, 2P, 40125 A) d
QB (225 A 2P or 3P, 70225 A)
4001600 A EZM Main Device with Type LH (400 A Max.), MH (1000 A max.) or PA (1600 A
QO-VH (125 A, 2P, 40125 A)
max.) circuit breaker.
d
QO-VH
(225
A,
2P
,
4060
A)
65 kA
QD (225 A 2P or 3P, 70225 A)
e
DJM (400 A, 2P or 3P, 160400 A)
65 kA
QD (225 A, 3P, 70225 A)
QO-VH (125 A, 2P, 40125 A)
10001200 A Main Device with catalog number suffix "CBU" supplied with
QO-VH (225 A, 2P, 4060 A) d
Type MHF circuit breaker.
QD (225 A 2P only, 70225 A)
QD (225 A 3P only, 70225 A) c
100 kA
DJM (400 A, 2P or 3P, 160400 A) c e
QD (225 A 2P only, 70225 A)
QD (225 A 3P only, 70225 A) c
2000 A EZM Main Device with Type RJ (2000 A) circuit breaker
DJM (400 A 2P or 3P, 160400 A) c e
EZ Meter-PakMain Fusible Switch ApplicationsSee Figure 3
QO (125 A, 2P, 40125 A)
400800 A EZM Main Device (1 or 3) with Class T (300 Vac) fuses installed. 1200 A EZM
10 kA
QO (225 A, 2P, 40125 A) d
Main Device (1 only) with Class T (300 Vac) fuses installed.
QB (225 A 2P or 3P, 70225 A)

QO-VH (125 A, 2P, 40125 A)


QO-VH (225 A, 2P, 4060 A) d
1200 A EZM Main Device (1 only) with Class T (300 Vac) fuses installed.
DJM (400 A, 2P, 160400 A) e
100 kA
QD (225 A 2P, 70225 A)
QO-VH (125 A, 2P, 40125 A)
QO-VH (225 A, 2P, 4060 A) d
100 kA
QD (225 A 2P, only, 70225 A)
400800 A EZM Main Device (1 or 3) with Class T (300 Vac) fuses installed.
QD (225 A 3P only, 70225 A) c
DJM (400 A, 2P or 3P, 160400 A) c e
Meter center short circuit current rating is equal to the lowest short circuit current rating given in table for any circuit breaker installed in any meter panelboard in the meter center.
Short circuit current rating is measured at the LINE SIDE terminals of the integral mounted or remote mounted main providing overcurrent protection for the EZM metering equipment lineup.
Three-pole only tenant circuit breaker(s) are limited to 208Y/120 Vac maximum.
Requires use of EZM125QOA adapter (order separately).
Supplied with factory installed circuit breaker(s), with an adjustable trip range of 160400 A.
42 kA

a
b
c
d
e

For three-tier series ratings refer to Data Bulletin 4100DB0301 and Instruction Bulletin 80043-303-19.
4
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers

EZM Typical Equipment Lineups

Typical Tenant
Circuit Breakers

QO2100
Two-Pole, Plug-On
QO Circuit Breaker

EZM114125
EZM1800TB

QDP22200TM Two-Pole Circuit Breaker (shown)


NOTE: The Q-Frame circuit breaker used with
EZM devices comes without line side lugs.

EZM114225
EZM1800CB

DJM32400E20
Circuit Breaker

EZML334225

EZML311400
EZM31600CB

NOTE: 1600 A main circuit breaker must be center mounted with branch units mounted on both sides.

5
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Application Data

Application Data
EZ Meter-Pak (EZM) Meter Centers

EZM1800CB

Enclosures are indoor/rainproof NEMA Type 3R meter centers for use


on ac systems.

Finish: ANSI gray, baked powder-coat epoxy electrodeposited over


cleaned phosphatized steel.

240 Vac maximum.

Enclosures meet NEC wire bending space requirements.

EZ Meter-Pak meter centers are UL Listed under File E-10582 and


File E-131840.

Suitable for use as service equipment and suitable for use on the line
side of service equipment.
Designed to be wall mounted only (not suitable for floor mounting).
All unmetered conductor compartments may be sealed by the utility
company.

Utility Company Requirements


Review local utility requirements to ensure that the metering equipment
selected meets local standards.
EZ Meter-Pak meter centers, to be complete, must include:

EZM main device, or terminal box;


EZM branch section(s), and
Square D brand branch circuit breakers (tenant mains).

Equipment Short Circuit Current Ratings


EZM3800FS

Available up to 100,000 RMS symmetrical amperes. Refer to pages 3 and 4.

Systems
Utility systems suitable for use as an incoming service to an EZM main
device:

System: 120/240 Vac, 13W

Available incoming service to main device:


120/240 Vac, 13W

System: 240/120 Vac, 34W delta

Available incoming services to main device: 240/120 Vac, 34W delta


120/240 Vac, 13W (fed from transformers A and C only).
EZM1800TB

NOTE: Connection to High-Leg B not permitted for this service. Standard


3-phase IN/1-phase OUT branch units are NOT suitable for use on this DELTA
System. Special branch units are available for this system by adding suffix "CA"
to catalog number (examples: EZM313125CA, EZM314225CA etc.)

System: 208Y/120 Vac, 34W

Available incoming services to main device:


120/208 Vac, 13W or 208Y/120 Vac, 34W

6
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Application Data
Services
The following are incoming services for an EZM main device and available
outgoing feeder(s) to downstream panelboards from EZM branch section(s):

120/240 Vac, 13W to main device. Available outgoing feeder(s) to


downstream panelboards 120/240 Vac, 13W.

120/208 Vac, 13W to main device (derived from a 208Y/120 Vac,


34W network). Available outgoing feeder(s) to downstream
panelboards 120/208 Vac, 13W.

240/120 Vac, 34W delta to main device. Available outgoing feeder(s)


to downstream panelboards:
120/240 Vac, 13W (fed from transformers A and C only).
Special branch units are available for this system by adding suffix
CA to catalog number, for example: EZM313125CA.

EZM314125

NOTE: Connection to High-Leg B not permitted for this service.


Standard 3 IN/1 OUT branch units are not suitable for use on this
delta system.
240/120 Vac, 34W delta

208Y/120 Vac, 34W to main device. Available outgoing feeder(s) to


downstream panelboards:
120/208 Vac, 13W (Fifth jaw required)
208Y/120 Vac, 34W

EZM114225

EZML311400

EZMR332225

7
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Main Device Ampere Ratings

Main Device Ampere Ratings


Main Circuit Breaker Ratings

400, 600, 800,1000, 1200,1600, and 2000 A combination


overhead/underground

400, 600, 800, 1000, and 1200 A underground only (meets EUSERC
standards)

1600 and 2000 A underground only (does not meet EUSERC standards).

Main Fusible Switch Ratings

EZM31600CB

400, 600, and 800 A (13W and 34W) and 1200 A (13W only)
combination overhead/underground

400, 600, and 800 A (13W and 34W) and 1200 A (13W only)
underground only (meets EUSERC standards).

Terminal Box Ratings


225, 400, 600, 800, 1600, and 2000 A combination overhead/underground.
400, 800, and 1200 A underground only (meets EUSERC standards).
Mounting Restrictions for Main Devices:

EZM1800CBU

EZM32000CB

400, 600, and 800 A main disconnects may be end mounted with branch
units having 800 or 1200 A continuous horizontal cross bus.

1000 and 1200 A main disconnect or terminal box must be center


mounted when used with branch devices with main bus rated 800 A
continuous.

1600 A main disconnect or terminal box must be center mounted.

400, 800, and 1200 A type EZM-TBU tap boxes supplied with lug
landings to meet EUSERC standards.

2000 A main disconnect or terminal box must be center mounted and


requires use of branch units having 1200 A continuous horizontal cross bus.

EZM3800FS

EZM1800TB

8
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Branch Units

Branch Units
UL Listed meter center short circuit current ratings (RMS symmetrical
amperes) are listed on pages 3 and 4.

125 A Maximum Residential Branch Units

Available in two cross bus configurations: 1 IN/1 OUT (includes three


horizontal cross bus bars), and 3 IN/1 OUT (includes four horizontal
cross bus bars).

Accepts 40125 A, two-pole, plug-on type QO, QO-VH, or QOH circuit


breakers (order circuit breakers separately).

Ring-type EZM branch units supplied with four-jaw (1 IN units), and


with five-jaw (3 IN units), 100 A continuous duty rated meter sockets,
without bypass (manual slider type bypass kit MM200MB can be ordered
separately and field-installed).

Ringless-type EZMR branch units supplied with five-jaw, 100 A


continuous duty rated meter sockets, without bypass (horn type bypass
kit MMHB can be ordered separately and field-installed).

Ringless-type EZMH branch units supplied with five-jaw, 100 A


continuous duty rated meter sockets and horn type bypass.

Supplied with 800 A horizontal main cross bus.

2000 A main device must be center located when used with 125 A
branch units with 1200 A main horizontal cross bus.

EZM115125
EZM316125

1000, 1200, or 1600 A main devices must be center located when used
with 125 A branch units with 800 A main cross bus.

225 A Maximum Residential Branch Units


EZMH114125

EZM113125

EZM114225

Available in two cross bus configurations: 1 IN/1 OUT (includes three


horizontal cross bus bars), and 3 IN/1 OUT (includes four horizontal
cross bus bars).

Accepts 70225 A, 2-pole, bolt-on type QB, QD, QG or QJ circuit


breakers, or with the use of plug-on adapter catalog number
EZM125QOA, these units will accept 40125 A, two-pole plug-on type
QO, 40-60 A two-pole plug-on type circuit breakers QO-VH or QOH
(order circuit breakers and adapters separately).

Ring-type EZM branch units supplied with four-jaw (1 IN units), and


with five-jaw (3 IN units), 200 A continuous duty rated meter sockets,
without bypass (manual slider type bypass kit MM200MB can be ordered
separately and field-installed).

Ringless-type EZMR branch units supplied with five-jaw, 200 A


continuous duty rated meter sockets without bypass (horn type bypass
kit MMHB can be ordered separately and field-installed).

Ringless-type EZMH branch units supplied with five-jaw, 200 A


continuous duty rated meter sockets and horn type bypass.

Two- through four-position units supplied with 800 A horizontal main


cross bus and five-position supplied with 1200 A horizontal cross bus.

1000, 1200, and 1600 A main device must be center located when used
with 225 A branch units with 800 A main horizontal cross bus.

2000 A main device must be center located when used with 225 A
branch units with 1200 A main horizontal cross bus.

9
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Branch Units

225 A Maximum Commercial Branch Units

EZMR333225

Available in two cross bus configurations: 1 IN/1 OUT (includes three


horizontal cross bus bars), 3 IN/1 OUT, and 3 IN/3 OUT (includes
four horizontal cross bus bars).

1 OUT branch units accept 70225 A type QB, QD, QG, and QJ,
two-pole, bolt-on circuit breakers (order circuit breakers separately).

3 OUT branch units accept 70225 A type QB, QD, QG, and QJ,
three-pole, bolt-on circuit breakers (order circuit breakers separately).

1 OUT ringless-type EZML branch units are supplied with five-jaw, 200 A
continuous duty 1 meter sockets with lever type bypass.

1 OUT ring-type EZMT branch units are supplied with five-jaw, 200 A
continuous duty 1 meter sockets with test block bypass (meets
EUSERC standards).

3 OUT ringless-type EZML branch units are supplied with seven-jaw,


200 A continuous duty 3 meter sockets with lever bypass.

3 OUT ringless-type EZMR branch units are supplied with seven-jaw,


200 A continuous duty 3 meter sockets without bypass.

3 OUT Ring-type EZMT branch units are supplied with seven-jaw, 200 A
continuous duty 3 meter sockets with test block bypass (meets EUSERC
standards).

Supplied with 1200 A horizontal main cross bus.


1600 and 2000 A main devices must be center located when used with
225 A commercial branch units.

400 A Maximum Commercial Branch Units

Available in two cross bus configurations: 1 IN/1 OUT (includes three


horizontal cross bus bars), and 3 IN/1 OUT (includes four horizontal
cross bus bars).

1 OUT branch units are supplied with factory-installed 400 A Type


DJM two-pole circuit breaker(s). DJM circuit breaker has adjustable trip
settings from 160400 A (seal kit catalog number 29375 available
separately).

3 OUT branch units are supplied with factory-installed 400 A Type DJM
three-pole circuit breaker(s). DJM circuit breaker has adjustable trip settings
from 160400 A (seal kit catalog number 29375 available separately).

Supplied with 1200 A horizontal main cross bus.

EZML334225

EZMT

1600 and 2000 A main devices must be center located when used with
400 A commercial branch units.

EZML331400

10
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Bussed Extension Sections (NEMA Type 3R)

Bussed Extension Sections (NEMA Type 3R)


Bussed extensions provide separation between enclosures where needed
to avoid building obstructions. The bussed extension occupies an area
19.25 in. (489 mm) H x 12.0 in. (304 mm) or 6.0 in. (152 mm) W positioned
vertically in line with the horizontal cross bus of main and branch unit
enclosures. Extensions provide additional space between the main device
and the branch unit where needed to meet local utility requirements. In this
case the main device is deeper than the branch unit, and the dimension
between the side of the main device and the centerline of the branch unit
meter socket is too close to meet minimum clear space requirements.

EZM3EXT

Bussed extensions are also used with bussed corner sections to provide
additional working space in inside corner areas.

Use EZM1EXT6 (6.0 in.) or EZM1EXT (12.0 in.) wide.


Use EZM3EXT6 (6.0 in.) or EZM3EXT (12.0 in.) wide.
Supplied with 1200 A horizontal main cross bus.
Provisions for padlocking or sealing by the utility.

Bussed Corner Sections for Indoor (NEMA Type 1)


Construction Only

Enables mounting of metering enclosures on two adjacent walls.


NEMA Type 1 construction for use indoors only.
Designed for inside and outside corners.
Use EZM1CORNER (inside corner) with 1 cross bus equipment.
Use EZM1ELBOW (outside corner) with 1 cross bus equipment.
Use EZM3CORNER (inside corner) with 3 cross bus equipment.
Use EZM3ELBOW (outside corner) with 3 cross bus equipment.
Supplied with 1200 A horizontal main cross bus.
Provisions for padlocking or sealing by the utility.

Mounting Channel (see page 12)

EZM3CORNER

EZM main and branch units are each supplied with a wall mounting
channel.

Mounting channel is packed externally to each device on top surface of


front cover inside each carton for easy access. Covers do not need to be
removed from device to access mounting channel.

Rotating Mounting Brackets (see page 12)

EZM sections are equipped with permanently attached swinging


mounting brackets that are easily rotated out of the way after marking
wall for drilling mounting holes. The rotating feature of the mounting
brackets will accommodate slight mounting hole misalignment.

Rotate mounting brackets to extended position before lifting device onto


mounting channel for ease of installation.

Rotating mounting brackets are provided at top and bottom of each unit
to secure device to the wall.
21.79
[553]

15.41
[391]

7.09
[180]

8.02
[204]

Common Corner
Application to Meet Utility
Clearance Requirements

14.88
[378]

8.50
[216]

Common Wall Application


to Meet Utility Clearance
Requirements

in.
Dimensions: [mm]

EZM3ELBOW

11
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Bussed Extension Sections (NEMA Type 3R)
Determine Mounting Channel Height for Metering Equipment Lineup

Chalk
Line

Contact your local utility to determine the following branch unit meter
socket mounting height restrictions:
Maximum dimension, centerline of top meter socket to floor or
finished grade level
Minimum dimension, centerline of bottom meter socket to floor or
finished grade level

56.51
[14.35]

Total branch unit meter socket height window (maximum dimension


less minimum dimension).
125 A and 225 A Residential
Branch Units (Typical)

in.
Dimensions: [mm]
Chalk line on wall at proper height and secure
mounting channel to wall.
Mounting channel is secured to wall and device is
hung on channel by bracket attached to rear of unit.

Main Circuit Breaker


Device (Typical)

225 A Commercial
Branch Units (Typical)

9.00
[229]
Typical
14.00
[356]
Typical

Maximum
Meter Socket Total
Height
Meter
Requirement Socket

Mounting Channel

C
C
See note below.

Window
Height

Top of
Mounting
Channel

Maximum
Meter Socket
Height
Total Meter Requirement
Socket
Window
Height

Minimum Meter
Socket Height
Requirement

Minimum Meter
Socket Height
Requirement

Minimum Height Requirement to Bottom of Main


Floor or Finished Grade Level

Mounting Channel

Mounting Channel Height Requirements Detail

in.
Dimensions: [mm]

NOTE: See pages 1416 for dimension C for each catalog number.

Contact your local utility to determine minimum dimension from bottom


of main device to floor or finished grade level.

Refer to drawings of main devices and branch units starting on page 40


and determine proper height to install mounting channels. Ensure
branch unit meter sockets are positioned within total branch unit meter
socket height window, and main device bottom is positioned far enough
above floor or finished grade level to comply with local requirements.

Once the mounting channel height is determined, chalk a level line on


wall at proper height.

Align top edge of mounting channels for each unit to wall in the order
that they will be installed.

Some EZM branch sections (five-position and six-position branch units)


may not fit within utilitys meter height window for outdoor applications,
although could be acceptable for use in indoor installations.

Rotating Mounting Brackets

12
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Main Devices

Main Devices
Width

T
Mounting
Channel
Height
56.51
[1435]
Mounting
Channel

in.
Dimensions: [mm]
Main Device (Typical)
NOTE: Mounting channel height of 56.51 in. (1435 mm) is for
reference only. Consult local utility for minimum and maximum
meter socket height requirements to properly position
mounting channel above grade level.

Height

Width

Depth

M1

Catalog
Number

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

EZM11000CB
EZM11000CBU
EZM11200CB
EZM11200CBU
EZM11200FS
EZM11200FSU
EZM11600CBU
EZM11200TBU
EZM11600CB
EZM11600TB
EZM12000CB
EZM12000CBU
EZM12000TB
EZM1225TB
EZM1400CB
EZM1400CBU
EZM1400FS
EZM1400FSU
EZM1400TB
EZM1400TBU
EZM1600CB
EZM1600CBU
EZM1600FS
EZM1600FSU
EZM1600TB
EZM1800CB
EZM1800CBU
EZM1800FS
EZM1800FSU
EZM1800TB
EZM1800TBCU
EZM1800TBU
EZM1EXT
EZM1EXT6

53.97
70.05
61.19
70.05
61.19
70.05
71.19
44.71
61.19
51.58
68.91
68.91
71.13
21.81
53.97
69.03
53.97
69.03
30.46
35.71
53.97
69.03
53.97
69.03
28.43
53.97
69.03
53.97
69.03
53.97
51.76
39.96
19.34
19.34

1371
1779
1554
1779
1554
1779
1808
1136
1554
1310
1750
1750
1807
554
1371
1753
1371
1753
774
907
1371
1753
1371
1753
722
1371
1753
1371
1753
1371
1315
1015
491
491

18.66
34.19
30.19
34.19
30.19
34.19
30.19
33.16
30.19
22.33
30.19
30.19
30.19
11.50
18.66
20.46
18.66
20.46
17.00
17.16
18.66
20.46
18.66
20.46
17.00
18.66
20.46
18.66
20.46
18.66
23.93
25.06
11.66
6.00

474
868
767
868
767
868
767
842
767
567
767
767
767
292
474
520
474
520
432
436
474
520
474
520
432
474
520
474
520
474
608
637
296
152

11.50
18.33
18.33
18.33
18.33
18.33
18.33
11.12
18.33
13.00
18.33
18.33
21.46
5.81
11.50
11.50
11.50
11.50
6.53
8.00
11.50
11.50
11.50
11.50
6.53
11.50
11.50
11.50
11.50
11.50
6.41
11.12
6.37
6.37

292
466
466
466
466
466
466
282
466
330
466
466
545
148
292
292
292
292
166
203
292
292
292
292
166
292
292
292
292
292
163
282
162
162

34.30
46.99
38.13
46.99
38.13
46.99
48.12
31.17
38.13
27.92
44.25
44.25
37.62
13.002
34.30
49.37
34.30
49.37
16.29
27.17
34.30
49.37
34.30
49.37
16.29
34.30
49.37
34.30
49.37
34.30
28.01
31.17
11.852
11.852

871
1194
969
1194
969
1193
1222
792
969
709
1124
1124
956
330
871
1254
871
1254
414
690
871
1254
871
1254
414
871
1254
871
1254
871

19.67
23.06
23.06
23.06
23.06
23.07
23.07
13.54
23.06
23.66
24.66
24.66
33.51
8.81
19.67
19.66
19.67
19.66
14.17
8.54
19.67
19.66
19.67
19.66
12.14
19.67
19.66
19.67
19.66
19.67

500
586
586
586
586
586
586
344
586
601
626
626
851
224
500
499
500
499
360
217
500
499
500
499
308
500
499
500
499
500

22.21
9.52
18.38
9.52
18.38
9.53
8.39
25.34
18.38
28.59
12.26
12.26
18.89
43.51
22.21
7.14
22.21
7.14
40.22
29.34
22.21
7.14
22.21
7.14
40.22
22.21
7.14
22.21
7.14
22.21

564
242
467
242
467
242
213
644
467
725
311
311
480
1105
564
181
564
181
1022
745
564
181
564
181
1022
564
181
564
181
564

711
792
301
301

23.75
8.79

603
223

28.50
25.34

724
644

19.50

495

14.40

366

8.02

204

11.852

301

EZM1CORNER
(indoor only) 3
EZM1ELBOW
(indoor only) 4
EZM31000CB
EZM31000CBU
EZM31200CB
EZM31200CBU
EZM31200TBU
EZM31600CB
EZM31600CBU
EZM31600TB
EZM32000CB

19.50

495

14.52

369

8.01

204

11.852

301

53.97
70.05
61.19
70.05
44.71
61.19
68.69
55.12
68.91

1371
1779
1554
1779
1136
1554
1745
1400
1750

18.66
34.19
30.19
34.19
33.16
30.19
27.69
22.40
30.19

474
868
767
868
842
767
707
569
767

11.50
18.33
18.33
18.33
11.12
18.33
18.45
12.94
18.33

292
466
466
466
282
466
471
329
466

34.30
46.99
38.13
46.99
31.17
38.13
49.12
29.67
44.25

871
1194
969
1194
792
969
1255
754
1124

19.67
23.06
23.06
23.06
13.54
23.06
19.57
25.45
24.66

500
586
586
586
344
586
525
646
626

22.21
9.52
18.38
9.52
25.34
18.38
7.39
26.84
12.26

564
242
467
242
644
467
189
682
311

EZM32000CBU
EZM32000TB
EZM3225TB
EZM3400CB
EZM3400CBU
EZM3400FS
EZM3400FSU
EZM3400TB
EZM3400TBU
EZM3600CB
EZM3600CBU
EZM3600FS
EZM3600FSU
EZM3600TB
EZM3800CB
EZM3800CBU
EZM3800FS
EZM3800FSU
EZM3800TB
EZM3800TBCU
EZM3800TBU

68.91
71.13
21.81
53.97
69.03
53.97
69.03
30.46
35.71
53.97
69.03
53.97
69.03
30.46
53.97
69.03
53.97
69.03
53.97
51.76
39.96

1750
1807
554
1371
1753
1371
1753
774
907
1371
1753
1371
1753
774
1371
1753
1371
1753
1371
1315
1015

30.19
30.19
11.50
18.66
20.46
18.66
20.46
17.15
17.16
18.66
26.19
18.66
26.19
17.15
18.66
26.19
18.66
26.19
18.66
23.93
25.06

767
767
292
474
520
474
520
436
436
474
665
474
665
436
474
665
474
665
474
608
637

18.33
21.46
5.81
11.50
11.50
11.50
11.50
7.09
8.00
11.50
11.65
11.50
11.65
7.09
11.50
11.65
11.50
11.65
11.50
6.41
11.12

466
545
148
292
292
292
292
180
203
292
296
292
296
180
292
296

44.25
37.62
13.002
34.30
49.37
34.30
49.37
16.29
27.17
34.30
49.37
34.30
49.37
16.29
34.30
49.37

1124
956
330
871
1254
871
1254
414
690
871
1254
871
1254
414
871
1254

24.66
33.51
8.81
19.67
19.66
19.67
19.66
14.17
8.54
19.67
19.66
19.67
19.66
14.17
19.67
19.66

626
851
224
500
499
500
499
360
217
500
499
500
499
360
500
499

12.26
18.89
43.51
22.21
7.14
22.21
7.14
40.22
29.34
22.21
7.14
22.21
7.14
40.22
22.21
7.14

311
480
1105
564
181
564
181
1022
745
564
181
564
181
1022
564
181

292
296
292
163
282

34.30
49.37
34.30
28.01
31.17

871
1254
871
711
792

19.67
19.66
19.67
23.75
8.79

500
499
500
603
223

22.21
7.14
22.21
28.50
25.34

564
181
564
724
644

EZM3EXT
EZM3EXT6
EZM3CORNER
(indoor only)3

19.34
19.34

491
491

11.66
6.00

296
152

6.37
6.37

162
162

11.852
11.852

301
301

19.50

495

14.40

366

8.02

204

11.852

301

19.50

495

14.52

369

8.01

204

11.852

301

EZM3ELBOW
(indoor only)4
1
2
3
4

If channel height is 56.51 in. (1435 mm) then M =


Device supplied without mounting channel, secure to wall by use of rotating mounting feet.
Each leg of this corner section measures 14.72 in. (373.89 mm) from wall to start of next enclosure.
Each leg of elbow section measures 6.17 in. (156.72 mm) corner of wall to start of next enclosure.

13
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Main Devices
125 A and 225 A Residential
Branch Units (Typical)

225 A Commercial
Branch Units (Typical)
Main Device (Typical)
U

R
C

S
Max.

S
Max.

B
B
L

S
Min.
Mounting
Channel

S
Min.
Mounting
Channel

Floor or Finished Grade Level

Determine Height for Mounting Channel


NOTE: S Max., S Min., and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Single-Phase Branch Devices

Catalog Number
(available suffix)

EZM112225 (X, CUX)


EZM113125 (X, CUX)
EZM113225 (X, CUX)
EZM114125 (X, CUX)
EZM114225 (X, CUX)
EZM115125 (X, CUX)
EZM115225 (CU)
EZM116125 (X, CUX)
EZMH112225 (X, CUX)
EZMH113125 (X, CUX)
EZMH113225 (X, CUX)
EZMH114125 (X, CUX)
EZMH114225 (X, CUX)
EZMH115125 (X, CUX)
EZMH115225 (CU)
EZMH116125 (X, CUX)
EZMK111400
EZMK112400
EZML111225 (CU)
EZML11225D
EZML111400
EZML112225 (CU)
EZML11225D
EZML112400
EZML113225 (CU)
EZML113225D
EZML114225 (CU)
EZML114225D
EZMR112225 (X, CUX)
EZMR113125 (X, CUX)
EZMR113225 (X, CUX)
EZMR114125 (X, CUX)
EZMR114225 (X, CUX)
EZMR115125 (X, CUX)
EZMR115225 (X, CUX)
EZMR116125 (X, CUX)
EZMT111225
EZMT112225
EZMT113225

Height

Width

Depth

Mtg.
Channel
(B)

Top Meter
(U)

if S Min. for Bottom


Meter = 30 then...

Bottom
Meter
(L)

(R)
Top Meter
is...

Mounting
Channel
Height

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

43.41
42.37
43.41
48.12
52.00
57.12
61.00
66.12
43.41
42.37
43.41
48.12
52.00
57.12
61.00
66.12
45.55
72.99
39.06
39.06
44.55
39.06
39.06
69.61
53.06
53.06
67.06
67.06
43.41
42.37
43.41
48.12
52.00
57.12
61.00
66.12
25.12
60.56
79.56

1103
1076
1103
1222
1321
1451
1549
1679
1103
1076
1103
1222
1321
1451
1549
1679
1157
1854
992
992
1132
992
992
1768
1348
1348
1703
1703
1103
1076
1103
1222
1321
1451
1549
1679
638
1538
2021

17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
27.56
27.56
19.44
19.44
23.21
19.44
19.44
23.21
19.44
19.44
19.44
19.44
17.38
12.25
17.38
12.25
17.38
12.25
17.38
12.25
22.42
22.42
22.42

441
311
441
311
441
311
441
311
441
311
441
311
441
311
441
311
700
700
494
494
590
494
494
590
494
494
494
494
441
311
441
311
441
311
441
311
570
570
570

8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
9.74
9.74
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
8.09
7.09
8.09
7.09
8.09
7.09
8.09
7.09
9.38
9.38
9.38

205
180
205
180
205
180
205
180
205
180
205
180
205
180
205
180
247
247
240
240
240
240
240
240
240
240
240
240
205
180
205
180
205
180
205
180
238
238
238

9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

29.69

14.00
14.00
27.44
14.00
14.00
14.00
14.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00
9.00

19.00
19.00

229
229
229
229
229
229
229
229
229
229
229
229
229
229
229
229

754

356
356
697
356
356
356
356
229
229
229
229
229
229
229
229

483
483

32.34
31.30
32.34
31.30
32.34
31.30
32.35
40.30
32.34
31.30
32.34
31.30
32.34
31.30
32.35
40.30
37.81
37.81
25.51
25.51
37.81
25.51
25.51
37.81
39.50
39.50
39.50
39.50
32.34
31.30
32.34
31.30
32.34
31.30
32.35
40.30
16.19
43.63
48.25

821
795
821
795
821
795
821
1024
821
795
821
795
821
795
822
1024
960
960
648
648
960
648
648
960
1003
1003
1003
1003
821
795
821
795
821
795
822
1024
411
1108
1226

20.11
20.11
20.11
20.11
20.11
20.11
20.12
29.11
20.11
20.11
20.11
20.11
20.11
20.11
20.12
29.11
16.77
16.77
12.12
12.12
16.28
12.12
12.12
16.28
26.16
26.16
26.16
26.16
20.11
20.11
20.11
20.11
20.11
20.11
20.12
29.11

14.74
19.36

511
511
511
511
511
511
511
739
511
511
511
511
511
511
511
739
426
426
308
308
414
308
308
414
664
664
664
664
511
511
511
511
511
511
511
739

374
492

11.07
11.07
11.07
16.82
19.66
25.82
28.65
25.82
11.07
11.07
11.07
16.82
19.66
25.82
28.65
25.82
7.74
35.18
13.55
13.55
6.74
13.55
13.55
31.80
13.56
13.56
27.56
27.56
11.07
11.07
11.07
16.82
19.66
25.82
28.65
25.82
8.93
16.93
31.31

281
281
281
427
499
656
728
656
281
281
281
427
499
656
728
656
197
894
344
344
171
344
344
808
344
344
700
700
281
281
281
427
499
656
728
656
227
430
795

22.18
13.18
13.18
9.93
12.77
9.93
12.77
9.93
22.18
13.18
13.18
9.93
12.77
9.93
12.77
9.93
24.51
22.26
25.67
25.67
24.02
11.67
11.67
20.64
11.72
11.72
11.72
11.72
22.18
13.18
13.18
9.93
12.77
9.93
12.77
9.93
4.67
12.67
12.67

563
335
335
252
324
252
324
252
563
335
335
252
324
252
324
252
622
565
652
652
610
296
296
524
298
298
298
298
563
335
335
252
324
252
324
252
119
322
322

12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
21.04
21.04
13.39
13.39
21.53
13.39
13.39
21.53
13.34
13.34
13.34
13.34
12.23
11.19
12.23
11.19
12.23
11.19
12.23
11.19
20.45
28.89
28.89

311
284
311
284
311
284
311
284
311
284
311
284
311
284
311
284
534
534
340
340
547
340
340
547
339
339
339
339
311
284
311
284
311
284
311
284
519
734
734

9.00
18.00
18.00
27.00
27.00
36.00
36.00
45.00
9.00
18.00
18.00
27.00
27.00
36.00
36.00
45.00

29.69

14.00
14.00
27.44
28.00
28.00
42.00
42.00
9.00
18.00
18.00
27.00
27.00
36.00
36.00
45.00

19.00
38.00

229
457
457
686
686
914
914
1143
229
457
457
686
686
914
914
1143

754

356
356
697
711
711
1067
1067
229
457
457
686
686
914
914
1143

483
965

39.00
48.00
48.00
57.00
57.00
66.00
66.00
75.00
39.00
48.00
48.00
57.00
57.00
66.00
66.00
75.00
30.00
59.69
30.00
30.00
30.00
44.00
44.00
57.44
58.00
58.00
72.00
72.00
39.00
48.00
48.00
57.00
57.00
66.00
66.00
75.00
30.00
49.00
68.00

991
1219
1219
1448
1448
1676
1676
1905
991
1219
1219
1448
1448
1676
1676
1905
762
1516
762
762
762
1118
1118
1459
1473
1473
1829
1829
991
1219
1219
1448
1448
1676
1676
1905
762
1245
1727

50.11
50.11
50.11
50.11
50.11
50.11
50.12
59.11
50.11
50.11
50.11
50.11
50.11
50.11
50.12
59.11
46.77
46.77
42.12
42.12
46.28
42.12
42.12
46.28
56.17
56.17
56.17
56.17
50.11
50.11
50.11
50.11
50.11
50.11
50.12
59.11
25.74
44.74
49.36

1273
1273
1273
1273
1273
1273
1273
1501
1273
1273
1273
1273
1273
1273
1273
1501
1188
1188
1070
1070
1176
1070
1070
1175
1427
1427
1427
1427
1273
1273
1273
1273
1273
1273
1273
1501
654
1136
1254

14
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Main Devices
125 A and 225 A Residential
Branch Units (Typical)

225 A Commercial
Branch Units (Typical)
Main Device (Typical)
U

R
C

S
Max.

S
Max.

B
B
L

S
Min.

S
Min.
Mounting
Channel

Mounting
Channel
M
Floor or Finished Grade Level

Determine Height for Mounting Channel


NOTE: S Max., S Min., and M dimensions are based on local utility requirements and will determine proper height for mounting channel.

Three-Phase Branch Devices

Catalog Number
(available suffix)

Height

in.
EZM312225 (X, CUX,
CA, XCA, CUXCA)
EZM313125 (X, CUX,
CA, XCA, CUXCA)
EZM313125M10
EZM313225 (X, CUX,
CA, XCA, CUXCA)
EZM314125 (X, CUX,
CA, XCA, CUXCA)
EZM314125M10
EZM314225 (X, CUX,
CA, XCA, CUXCA)
EZM315125 (X, CUX,
CA, XCA, CUXCA)
EZM315125M10
EZM315225 (CU, CA,
CUCA)
EZM316125 (X, CUX,
CA, XCA, CUXCA)
EZMH312225 (X, CUX,
CA, XCA, CUXCA)
EZMH313125 (X, CUX,
CA, XCA, CUXCA)
EZMH313225 (X, CUX,
CA, XCA, CUXCA)
EZMH314125 (X, CUX,
CA, XCA, CUXCA)
EZMH314225 (X, CUX,
CA, XCA, CUXCA)
EZMH315125 (X, CUX,
CA, XCA, CUXCA)
EZMH315225 (CU, CA,
CUCA)
EZMH316125 (X, CUX,
CA, XCA, CUXCA)
EZMK311400 (CA)

Width

Top Meter
(U)

if S Min. for Bottom


Meter = 30 then...

Bottom
Meter
(L)

(R)
Top Meter
is...

Mounting
Channel
Height

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

991

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

42.37 1076 12.25

311

7.09

180

10.00

254

24.29

617

12.10

307

18.08

459

10.18

259

12.19

310

20.00

508

50.00 1270 42.10 1069

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.11 1273

52.12 1324 12.25

311

7.09

180

10.00

254

34.29

871

22.10

561

17.83

453

9.93

252

12.19

310

30.00

762

60.00 1524 52.10 1323

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

62.12 1578 12.25

311

7.09

180

10.00

254

34.29

871

22.10

561

27.83

707

9.93

252

12.19

310

40.00 1016 70.00 1778 52.10 1323

61.00 1549 17.38

441

8.09

205

9.00

229

32.35

822

20.12

511

28.65

728

12.77

324

12.23

311

36.00

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.12 1273

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

61.00 1549 17.38

441

8.09

205

9.00

229

32.35

822

20.12

511

28.65

728

12.77

324

12.23

311

36.00

914

66.00 1676 50.12 1273

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

45.55 1157 27.56

700

9.74

247

30.60

426

7.74

197

24.51

623

21.04

534

[mm]

in.

Depth

Mtg.
Channel
(B)

777

16.77

914

in.

[mm]

50.11 1273

66.00 1676 50.12 1273

30.00

991

762

50.11 1273

46.77 1188

15
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Main Devices
Three-Phase Branch Devices

Catalog Number
(available suffix)

EZMK312400 (CA)
EZMK331400
EZMK332400
EZML311400 (CA)
EZML312225 (CU, CA,
CUCA)
EZML31225D (CA)
EZML312400 (CA)
EZML313225 (CU, CA,
CUCA)
EZML313225D (CA)
EZML314225 (CU, CA,
CUCA)
EZML314225D (CA)
EZML331225 (CU)
EZML331225D
EZML331400
EZML332225 (CU)
EZML332225D
EZML332400 (CU)
EZML333225 (CU)
EZML333225D
EZML334225 (CU)
EZML334225D
EZMR312225 (X, CUX,
CA, XCA, CUXCA)
EZMR313125 (X, CUX,
CA, XCA, CUXCA)
EZMR313225 (X, CUX,
CA, XCA, CUXCA)
EZMR314125 (X, CUX,
CA, XCA, CUXCA)
EZMR314225 (X, CUX,
CA, XCA, CUXCA)
EZMR315125 (X, CUX,
CA, XCA, CUXCA)
EZMR315225 (CU, CA,
CUXCA)
EZMR316125 (X, CUX,
CA, XCA, CUXCA)
EZMR332225 (CU)
EZMR333225 (CU)
EZMR334225 (CU)
EZMT311225 (CA)
EZMT312225 (CA)
EZMT313225 (CA)
EZMT331225
EZMT332225
EZMT333225

Height

Width

Depth

Mtg.
Channel
(B)

Top Meter
(U)

if S Min. for Bottom


Meter = 30 then...

Bottom
Meter
(L)

(R)
Top Meter
is...
in.

Mounting
Channel
Height

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

in.

[mm]

72.99
45.55
72.99
45.55

1854
1157
1854
1157

27.56
27.56
27.56
23.21

700
700
700
589

9.74
9.74
9.74
9.44

247
247
247
240

29.69

29.69

754

754

37.81
30.60
37.81
37.81

960
777
960
960

16.77
16.77
16.77
16.28

426
426
426
414

35.18
7.74
35.18
7.74

894
197
894
197

22.26
24.51
22.26
24.02

565
623
565
610

21.04
21.04
21.04
21.53

534
534
534
547

29.69

29.69

754

754

59.69 1516 46.77 1188


30.00 762 46.77 1188
59.69 1516 46.77 1188
30.00 762 46.28 1175

39.06

992

[mm]

in.

[mm]

19.44

494

9.44

240

14.00

356

25.50

648

12.17

309

13.56

344

11.73

298

13.33

339

14.00

356

44.00 1118 42.17 1071

39.06 992 19.44


69.61 1768 23.21

494
589

9.44
9.44

240
240

14.00
27.44

356
697

25.50
37.81

648
960

12.17
16.28

309
414

13.56
31.80

344
808

11.73
20.64

298
524

13.33
21.53

339
547

14.00
27.44

356
697

44.00 1118 42.17 1071


57.44 1459 46.28 1176

53.06 1348 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

13.56

344

11.72

298

13.34

339

28.00

711

58.00 1473 56.17 1427

53.06 1348 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

13.56

344

11.72

298

13.34

339

28.00

711

58.00 1473 56.17 1427

67.06 1703 19.44

494

9.44

240

14.00

356

39.50 1003 26.17

665

27.56

700

11.73

298

13.34

339

42.00 1067 72.00 1829 56.17 1427

67.06
39.06
39.06
45.55
39.06
39.06
69.61
53.06
53.06
67.06
67.06

19.44
19.44
19.44
23.21
19.44
19.44
23.21
19.44
19.44
19.44
19.44

494
494
494
590
494
494
590
494
494
494
494

9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44
9.44

240
240
240
240
240
240
240
240
240
240
240

14.00

14.00
14.00
27.44
14.00
14.00
14.00
14.00

356

356
356
697
356
356
356
356

39.50
25.50
25.50
37.81
25.50
25.50
37.81
39.50
39.50
39.50
39.50

1003
648
648
960
648
648
960
1003
1003
1003
1003

26.17
12.17
12.17
16.28
12.17
12.17
16.28
26.16
26.16
26.16
26.16

665
309
309
414
309
309
414
664
664
664
664

27.56
13.56
13.56
7.74
13.56
13.56
31.80
13.56
13.56
27.56
27.56

700
344
344
197
344
344
808
344
344
700
700

11.73
25.73
25.73
24.02
11.74
11.74
20.64
11.72
11.72
11.72
11.72

298
654
654
610
298
298
524
298
298
298
298

13.34
13.33
13.33
21.53
13.33
13.33
21.53
13.34
13.34
13.34
13.34

339
339
339
547
339
339
547
339
339
339
339

42.00 1067 72.00 1829 56.17 1427

30.00 762 42.17 1071

30.00 762 42.17 1071

30.00 762 46.28 1176


13.99 355 43.99 1117 42.17 1071
13.99 355 43.99 1117 42.17 1071
27.44 697 57.44 1459 46.28 1176
28.00 711 58.00 1473 56.17 1427
28.00 711 58.00 1473 56.17 1427
42.00 1067 72.00 1829 56.17 1427
42.00 1067 72.00 1829 56.17 1427

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

22.18

563

12.23

311

9.00

229

39.00

42.37 1076 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

11.07

281

13.18

335

11.19

284

18.00

457

48.00 1219 50.11 1273

43.41 1103 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

11.07

281

13.18

335

12.23

311

18.00

457

48.00 1219 50.11 1273

48.12 1222 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

16.82

427

9.93

252

11.19

284

27.00

686

57.00 1448 50.11 1273

52.00 1321 17.38

441

8.09

205

9.00

229

32.34

821

20.11

511

19.66

499

12.77

324

12.23

311

27.00

686

57.00 1448 50.11 1273

57.12 1451 12.25

311

7.09

180

9.00

229

31.30

795

20.11

511

25.82

656

9.93

252

11.19

284

36.00

914

66.00 1676 50.11 1273

60.94 1548 17.37

441

8.09

205

9.00

229

32.35

822

20.14

512

28.59

726

12.73

323

12.21

310

36.00

914

66.00 1676 50.14 1274

66.12 1679 12.25

311

7.09

180

9.00

229

40.30 1024 29.11

739

25.82

656

9.93

252

11.19

284

45.00 1143 75.00 1905 59.11 1501

39.06
53.06
67.06
25.12
60.56
79.56
25.12
60.56
79.56

494
494
494
569
569
569
569
569
569

9.44
9.44
9.44
9.38
9.38
9.38
9.38
9.38
9.38

240
240
240
238
238
238
238
238
238

14.00
14.00
14.00

19.00
19.00

19.00
19.00

356
356
356

483
483

483
483

25.50
39.50
39.50
16.19
43.63
48.25
16.19
43.63
48.25

309
664
664

374
492

374
492

13.56
13.56
27.56
8.93
16.93
31.31
8.93
16.93
31.31

344
344
700
227
430
795
227
430
795

11.74
11.72
11.72
4.67
12.67
12.67
4.67
12.67
12.67

298
298
298
119
322
322
119
322
322

13.33
13.34
13.34
20.45
28.89
28.89
20.45
28.89
28.89

339
339
339
519
734
734
519
734
734

13.99 355 43.99 1117 42.17 1071


28.00 711 58.00 1473 56.16 1426
42.00 1067 72.00 1829 56.16 1426

30.00 762 25.74 654


19.00 483 49.00 1245 44.74 1136
38.00 965 68.00 1727 49.36 1254

30.00 762 25.74 654


19.00 483 49.00 1245 44.74 1136
38.00 965 68.00 1727 49.36 1254

1703
992
992
1157
992
992
1768
1348
1348
1703
1703

992
1348
1703
638
1538
2021
638
1538
2021

19.44
19.44
19.44
22.42
22.42
22.42
22.42
22.42
22.42

648
1003
1003
411
1108
1226
411
1108
1226

12.17
26.16
26.16

14.74
19.36

14.74
19.36

991

50.11 1273

16
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Closing Plates

Closing Plates
Closing PlatesMain Devices

Closing Plates Provided with Main Device


for use at Each End of Metering Line-Up

EZM main devices are supplied with two closing plates, one on each side of
the enclosure, to cover and seal openings for horizontal cross bus.

Right-side closing plate is one inch deep and secured to the box side
using three 1/4-20 captive screws and three 1/4-inch hex nuts. Two
sealing wing nuts for this side are provided in the bag assembly packed
with each main device. Holes in wing nuts and lanced ears in closing
plates are provided to seal the closing plate to the box sides. Install one
wing nut on screw extending through closing plate at bottom of center
and the other wing nut on screw extending through the closing plate at
the top front to seal.

Left-side closing plate is two inches deep and secured to box side using
three 1/4-20 carriage head screws and three 1/4-inch hex nuts. Two
sealing wing nuts for this side are provided in the bag assembly packed
with each device. Holes in wing nuts and lanced ears in closing plates
are provided to seal the closing plate to the box sides. Install one wing
nut on screw extending through the closing plate at bottom center and
the other wing nut on screw extending through closing plate at the top
rear to seal. Where sealing is not required, install screws from outside to
inside of unit and secure with hex nuts.

Closing PlatesBranch Units


EZM branch units are shipped without closing plates, but are designed to
receive one from a main device. To install, remove closing plate from side of
main device before connecting branch unit to main device. After last branch
unit is installed in lineup, follow closing plate installation instructions for main
devices.

Closing PlatesMain Devices and Branch Units


When adding on to an existing EZM metering equipment line up, repeat the
above procedure by moving closing plate to end of lineup.

17
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Horizontal Cross Bus

Horizontal Cross Bus


800 A aluminum horizontal cross bus is standard for the following
devices:

Right End of 3
Horizontal Cross Bus,
Shown with Visi-Tite Nuts

Left End of 3 Horizontal


Cross Bus, Shown with
Slotted End Bus Bars

400, 600, 800, and 1000 A main circuit breaker devices

Left end of each horizontal cross bus bar has a slotted end

1 main and branch units have 3 horizontal cross bus bars (, and
neutral)

3 main and branch units have 4 horizontal cross bus bars (A, B,
C, and neutral)

1 main or branch units will not interconnect with 3 main or branch units.

400, 600, and 800 A main fusible switches


225, 400, 600, and 800 A main lugs terminal boxes
125 and 225 A residential branch units
Right end of each horizontal cross bus bar is supplied with 1/2-13
captive bolt and Visi-Tite nut
800 A horizontal cross bussed units will connect with 1200 A horizontal
cross bussed units

1200 A copper horizontal cross bus is standard in the following


devices:

1000 A CBU suffix main circuit breaker devices

1600 A CB and CBU suffix main circuit breaker devices (must always
be center mounted)

1200 A TBU suffix main lug terminal devices (must be center mounted
when used with branch devices with main bus rated 800 A)

1600 A TB suffix main lug terminal devices (must always be center


mounted)

2000 A "TB" suffix main lug terminal devices (must always be center
mounted and require the use of branch devices having 1200 A
horizontal cross bus)

125 A and 225 A CUX suffix residential branch devices

Left end of each horizontal cross bus bar has a slotted end

1 main and branch units have 3 horizontal cross bus bars (, and
neutral)

3 main and branch units have 4 horizontal cross bus bars (A, B,
C, and neutral)

1 main or branch units will not interconnect with 3 main or branch units.

1200 A CB and CBU suffix main circuit breaker devices (must be center
mounted when used with branch devices with main bus rated 800 A)

225 A commercial branch units


400 A commercial branch units
Right end of each horizontal cross bus bar is supplied with 1/2-13
captive bolt and Visi-Tite nut
1200 A horizontal cross bussed units will connect with 800 A horizontal
cross bussed units

18
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Equipment Grounding Procedure

Equipment Grounding Procedure


1. Install mounting channels to wall at proper height (refer to Mounting
Channel on page 11).
2. Remove closing plates from sides of EZM main device next to where
EZM branch sections are to be installed.
3. Position units on mounting channel next to each other, but do not secure
rotating mounting brackets to wall at this time.
4. Remove outer covers EZM main device and exterior covers from EZM
branch sections (refer to page 21 for outer covers on branch devices).
5. Remove individual meter socket cover from over horizontal cross bus
area of EZM branch sections (refer to Individual Meter Socket Covers
on page 21).

Captive Equipment Bonding


Screws are Located on Right
Side of Each EZM Main and
Branch Device

Install Hex Nuts with


Star Washers onto
Captive Screws

6. Bond enclosures together by sliding three captive screws from the


RIGHT side of unit through holes in box side (closing plate holes), and
through LEFT side of adjacent enclosure. Install three 1/4-20 hex nuts
with star washer provided onto 1/4-20 captive screws and torque to
50 lb-in. (5.6 Nm). Bonding for equipment ground path is complete, and
enclosure gaskets are compressed to seal connection between units.
7. Replace closing plates at each end of metering equipment lineup (refer
to Closing Plates on page 17).
At this point, the enclosures are connected together and a bonded
equipment ground path is established. The next installation step involves
connection of the horizontal cross bus assemblies.

Tighten Until Outer Head Twists Off and RED


Indicating Disc Falls Away

Shown with RED


Indicating Disc in Place

Shown with Outer Head


and RED Indicating Disc
Falling Away

Visi-Tite Nut Horizontal Cross Bus Connectors

The Visi-Tite nut horizontal cross bus connector is a high-strength


1/2-13 UNC double-headed torque indicating nut. Installed as an integral
part of the horizontal cross bus structure in every EZM main and branch
device, this unique nut makes it possible to ensure proper torque at each
connection without the need for a torque wrench.

The torque indicating Visi-Tite nut assembly also makes it possible to


reduce equipment installation time over other designs requiring the use
of a torque wrench.

When making EZM metering equipment cross bus connections, there is


no need for a torque wrench. Use a socket wrench with a long handle to
tighten the outer Visi-Tite nut head until it twists off and releases the
RED plastic warning disc.

If the RED disc remains visible during inspection, the horizontal cross
bus assembly has not yet been tightened.

Once the outer Visi-Tite nut head is twisted off, an inner hex-head nut
remains for use with a torque wrench on maintenance checks or
relocation of equipment (torque 50 lb-ft./600 lb-in. [68 Nm]).

All phase and neutral connections to the horizontal cross bus structure
are now completed.

The final step is to secure the rotating mounting brackets to the wall at
top and bottom of each EZM main and branch unit enclosure.

Shown After Installation of Cross


Bus Structure is Complete

19
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Accessories

Accessories
Sealing Rings for Ring-Type Meter Sockets

Snap-Type
Sealing Ring

Screw-Type
Sealing Ring

Standard Snap-Type Aluminum Sealing Ring, catalog number 29209-100-01,


is the standard sealing ring for all ring-type EZM branch sections.
Replacement sealing rings may be ordered separately.
Snap-Type Stainless Steel Sealing Ring, catalog number ARP00026, is a
non-standard sealing ring. Order separately and install when required by the
local utility.
Screw-Type Aluminum Sealing Ring, catalog number 29008W, is a
non-standard sealing ring. Order separately and install when required by the
local utility.

Circuit Breaker Doors


BCV Circuit Breaker Door
Shown with Door Closed

125, 225, and 400 A EZM branch sections are supplied with factor-installed
circuit breaker doors constructed of durable impact-resistant material. The
following replacement kits are available:

BCV replacement door for vertically operated circuit breaker handles:


125 A ring and ringless residential branch sections
225 A ring and ringless residential branch sections
225 A ringless commercial branch sections
Supplied with built-in latch with padlock provisions.

BCM replacement door for vertically operated circuit breaker handles:


400 A ringless commercial branch sections

BCM Circuit Breaker Cover


Shown with Door Open

400800 A standard and EUSERC fusible switch main devices


4001000 A standard circuit breaker main devices
4001200 A EUSERC circuit breaker main devices
Supplied with built-in latch with padlock provisions.

Individual Meter Socket Closing Plates


LEXAN Meter Socket Closing Plate for Residential Branch Units:

LEXAN Closing Plate

Order separately (catalog number 29007)

Closing plates have four LEXAN blades as a part of the molding used to
engage meter socket jaws.

For use with 125 and 200 A residential branch units


Molded of LEXAN #141-112 polycarbonate resin
LEXAN offers high-impact and tensile strength characteristics and
contains an ultra-violet inhibitor to ensure years of clear visibility

Metal Meter Socket Closing Plate for Ringless-Type Branch Units:

Ringless-Type Metal Closing Plate

Order separately (catalog number RSG4)

Closing plate cannot be removed from individual meter socket cover with
meter socket cover installed on branch unit.

For use with ringless-type branch units


Metal closing plate attaches to individual meter socket cover from the
backside with four hold-down screws

20
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Accessories
Branch Unit Outer Covers for Tenant Circuit Breaker and
Individual Meter Socket Compartments
125 and 225 A Ring-Type Residential Branch Unit Outer Covers for Tenant
Circuit Breaker Compartments and Individual Meter Socket Covers:

EZM113200 (Ring-Type)
EZM113125 (Ring-Type)
Outer Tenant Circuit Breaker Outer Tenant Circuit Breaker
Cover and Individual
Cover and Individual
Meter Socket Covers
Meter Socket Covers

Outer tenant circuit breaker covers can be removed without disturbing


sealed utility meters mounted to the individual meter socket cover.

All unmetered conductor compartments remain sealed and isolated


when outer tenant circuit breaker covers are removed.

Outer tenant circuit breaker covers are supplied with individual tenant
circuit breaker doors that may be locked with a padlock.

An individual meter socket cover is supplied for each meter socket


position.

Each ring-type meter socket cover has a rim formed into the cover to
support the base of the utility meter.

Aluminum snap-type sealing rings are standard and are used to attach
the base of the utility meter to the rim. A slot is provided in the tab of the
sealing ring for the local utility to install their seal to lock the meter into
place.

125, 225, and 400 A Ringless-Type Branch Unit Outer Covers for Tenant
Circuit Breaker Compartments and Individual Meter Socket Covers:

EZML113200
(Ringless-Type)
Outer Tenant Circuit
Breaker Cover and
Individual Meter
Socket Covers

EZML332200
(Ringless-Type)
Outer Tenant Circuit
Breaker Cover and
Individual Meter
Socket Covers

Outer tenant circuit breaker covers can be removed without disturbing


sealed utility meters secured under individual meter socket covers.

All unmetered conductor compartments remain sealed and isolated


when outer tenant circuit breaker covers are removed.

Outer tenant circuit breaker covers are supplied with individual tenant
circuit breaker doors that may be locked with a padlock.

Individual ringless-type meter socket covers are supplied with stainless


steel hasps that extend through cover and stainless steel latches for
sealing covers to branch unit while utility meter or closing plate is
mounted in meter socket.

Ringless meter socket covers have provisions to accept utility seals


including plastic padlocks, lead and wire seals, padlocks, and barrel
locks, to prevent unauthorized access to meter socket compartment.

21
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Accessories
Branch Unit Load Neutral Terminals
125 A branch unit load neutral terminals accept one 14-2/0 AWG copper or
one 12-2/0 AWG aluminum conductor per meter socket position.
225 A branch unit load neutral terminals accept one 6 AWG-300 kcmil
aluminum or copper conductor per meter socket position.
400 A branch unit load neutral terminals will accept one 1/0 AWG-600 kcmil
or two 1/0 AWG-250 kcmil aluminum or copper conductor(s) per meter
socket position.

Branch Unit Load Equipment Grounding Terminals


Branch units are supplied with load equipment grounding terminals for feeds
to downstream panelboards.

225 A Branch Unit Load Neutral Terminals

Grounding terminals on 125 and 225 A branch devices have provisions to


accept one 14-2/0 AWG copper, or one 12-2/0 AWG aluminum conductor
per meter socket position.
Grounding terminals on 400 A branch devices have provisions to accept
one 4 AWG-300 kcmil copper or aluminum conductor per meter socket
position.
Grounding terminals are factory-installed at the bottom of the wiring gutter
compartment, but may be relocated to the top of the wiring gutter
compartment when exiting out the top of the device.

225 A Branch Unit


Load Neutral Terminals

400 A Branch Unit


Load Neutral Terminals

Branch Unit Load Equipment Grounding Terminals

22
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Accessories

Meter Sockets
Branch Unit Tenant Circuit Breaker Types and Meter Socket
Configurations
EZM branch units are supplied with meter sockets and provisions for
mounting tenant circuit breakers to feed downstream type QO or HOM load
centers or type NQOD panelboards. The following table includes standard
and optional branch unit features along with tenant circuit breaker types and
meter socket configurations.
125 A and 225 A Ring-Type EZM Residential Branch Units (1 OUT)
Meter Socket
Ring-Type
(Quantity)

Four-Jaw Meter
Socket 1 IN

Five-Jaw Meter
Socket 3 IN

Catalog Number

Catalog Number

Circuit Breaker
Type
(Two-Pole Only)

125 A Ring-Type Residential without Bypass


Three-Position

EZM113125

EZM113125CUX

EZM313125
EZM313125M10
EZM313125CUX

QO, QO-VH, QOH

Four-Position

EZM114125

EZM114125CUX

EZM314125
EZM314125M10
EZM314125CUX

QO, QO-VH, QOH

Five-Position

EZM115125

EZM115125CUX

EZM315125
EZM315125M10
EZM315125CUX

QO, QO-VH, QOH

Six-Position

EZM116125
EZM116125CUX

EZM316125
EZM316125CUX

QO, QO-VH, QOH

225 A Ring-Type Residential without Bypass

EZM115125

EZM113225

Two-Position

EZM112225
EZM112225CUX

EZM312225
EZM312225CUX

QB, QD, QG, QJ

Three-Position

EZM113225
EZM113225CUX

EZM313225
EZM313225CUX

QB, QD, QG, QJ

Four-Position

EZM114225
EZM114225CUX

EZM314225
EZM314225CUX

QB, QD, QG, QJ

Five-Position

EZM115225
EZM115225CU

EZM315225
EZM315225CU

QB, QD, QG, QJ

Ring-Type Residential Meter Socket Compartment Standard


Features

1 IN, 1 OUT branch sections include three horizontal cross bus bars
and a four-jaw meter socket.

3 IN, 1 OUT branch sections include four horizontal cross bus bars
and a five-jaw meter socket.
120/208 Vac, 13W (derived from a 208Y/120 Vac, 34W network).
Standard 3 IN/1 OUT branch units are suitable for use on this
system.

125 A and 225 A Ring-Type 125 A and 225 A Ring-Type


Meter Socket, Four-Jaw Individual Meter Socket Cover
Shown without Sealing Ring
without Bypass

120/240 Vac, delta, 13W (fed from transformers A and C only).


Connection to high-leg B not permitted for use on this system.
Standard 3 IN/1 OUT branch units are not suitable for use on this
system. Special branch units are available for this system by adding
suffix CA to catalog number; for example: EZM313125CA.

Meter socket jaws are front removable and spring reinforced.

200 A continuous duty rated meter socket jaws supplied without bypass.

Meter blade guides are supplied as standard on both line and load side
meter socket jaws.
Aluminum snap-type sealing ring supplied with each meter socket as
standard.
23

07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Accessories
125 A Tenant Circuit Breaker Compartment

125 A maximum branch units will accept 40125 A two-pole plug-on


type QO, QO-VH, or QOH circuit breakers (order circuit breakers
separately).

Refer to pages 3 and 4 for meter center available short circuit current
ratings with the above tenant circuit breakers installed.

225 A Tenant Circuit Breaker Compartment

125 A Tenant Circuit


Breaker Base (Two-Pole)

225 A maximum branch units listed in this section will accept 100225 A
two-pole bolt-on type QB, QD, QG, or QJ circuit breakers.

With the use of plug-on adapter catalog number EZM125QOA, these


units will accept 40125 A two-pole plug-on type QO, and 4060 A
two-pole plug-on type QO-VH and QOH circuit breakers. (Order circuit
breakers and adapters separately.)

Refer to pages 3 and 4 for meter center available short circuit current
ratings with the above tenant circuit breakers installed.

QO2100 Tenant Circuit


Breaker Installed

Optional Ring-Type Residential Meter Socket Features

225 A Q2M Tenant


Circuit Breaker Base
(Two-Pole)

Five-jaw kit catalog number 5J (one kit required per meter socket) is
available for field installation and can be mounted on the meter socket base
assembly at three, six, or nine oclock positions. Used to convert a four-jaw
125 A or 225 A ring-type branch unit meter socket to a five-jaw meter
socket.

Five-jaw meter sockets are required for a 120/208 Vac, 13W service
derived from a 208Y/120 Vac, 34W system.

Manual slider type bypass kit catalog number MM200MB is available for
field installation. It includes manual slider-type bypass and replacement
individual meter socket cover (cover is notched to allow handle of slider
bypass to pass through rim with meter installed). Slider-type bypass is
intended for temporary use only (not continuous duty rated). Available short
circuit current rating of metering equipment is limited to 10,000 RMS
symmetrical amperes with slider-type bypass kits installed.

Plug-on adapter kit catalog number EZM125QOA available for use in


225 A branch units that use bolt-on type QB, QD, QG, or QJ two-pole
tenant circuit breakers. Kit will accept 40125 A two-pole plug-on type
QO, and 4060 A two-pole plug-on type QO-VH and QOH circuit
breakers. (Order circuit breakers and adapters separately.)

Five-Jaw Kit (5J) Installed at the 9 OClock Position

Manual Slider-Type
Bypass Shown in
Closed Position with
Handle Extending
through Notch in Rim of
Meter Socket Cover

Manual Slider-Type
Bypass Shown in Open
Position with Handle
Secured by Notch Meter
Socket Sealing Ring

EZM125QOA Two-Pole Plug-On Adapter Kit for use in


QB, QD, QG, or QJ Bolt-On Tenant Circuit Breaker Compartments

24
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Accessories
125 A and 225 A Ringless-Type EZMR and EZMH Residential Branch Units (1 OUT)

Meter Socket
Ringless-Type
(Qty.)

Five-Jaw Meter Socket


1 IN

Five-Jaw Meter
Socket 3 IN

Catalog Number

Catalog Number

Circuit Breaker
Type
(Two-Pole Only)

125 A Ringless without Bypass


Three-Position

EZMR113125
EZMR113125CUX

EZMR313125
EZMR313125CUX

QO, QO-VH or QOH

Four-Position

EZMR114125
EZMR114125CUX

EZMR314125
EZMR314125CUX

QO, QO-VH or QOH

Five-Position

EZMR115125
EZMR115125CUX

EZMR315125
EZMR315125CUX

QO, QO-VH or QOH

Six-Position

EZMR116125
EZMR116125CUX

EZMR316125
EZMR316125CUX

QO, QO-VH or QOH

225 A Ringless without Bypass

EZMH114125

Two-Position

EZMR112225
EZMR112225CUX

EZMR312225
EZMR312225CUX

QB, QD, QG or QJ

Three-Position

EZMR113225
EZMR113225CUX

EZMR313225
EZMR313225CUX

QB, QD, QG or QJ

Four-Position

EZMR114225
EZMR114225CUX

EZMR314225
EZMR314225CUX

QB, QD, QG or QJ

Five-Position

EZMR115225
EZMR115225CU

EZMR315225
EZMR315225CU

QB, QD, QG or QJ

125 A Ringless with Horn Bypass


Three-Position

EZMH113125
EZMH113125CUX

EZMH313125
EZMH313125CUX

QO, QO-VH or QOH

Four-Position

EZMH114125
EZMH114125CUX

EZMH314125
EZMH314125CUX

QO, QO-VH or QOH

Five-Position

EZMH115125
EZMH115125CUX

EZMH315125
EZMH315125CUX

QO, QO-VH or QOH

Six-Position

EZMH116125
EZMH116125CUX

EZMH316125
EZMH316125CUX

QO, QO-VH or QOH

225 A Ringless with Horn Bypass


125 A and 225 A
125 A and 225 A Ringless-Type
Ringless Meter Socket Individual Meter Socket Cover
with Horn Bypass
Shown with Stainless Steel
Hasp and Latch for use with
Utility Seals

Two-Position

EZMH112225
EZMH112225CUX

EZMH312225
EZMH312225CUX

QB, QD, QG or QJ

Three-Position

EZMH113225
EZMH113225CUX

EZMH313225
EZMH313225CUX

QB, QD, QG or QJ

Four-Position

EZMH114225
EZMH114225CUX

EZMH314225
EZMH314225CUX

QB, QD, QG or QJ

Five-Position

EZMH115225
EZMH115225CU

EZMH315225
EZMH315225CU

QB, QD, QG or QJ

Ringless Residential Meter Socket Compartment Standard Features

1 IN, 1 OUT branch sections (includes three horizontal cross bus bars).
Five-jaw meter sockets supplied as standard.

3 IN, 1 OUT branch sections (includes four horizontal cross bus bars).
Five-jaw meter sockets supplied as standard.
120/208 Vac, 13W (derived from a 208Y/120 Vac, 34W service).
Standard 3 IN/1 OUT branch units are suitable for use on this system.
120/240 Vac, 13W (fed from transformers A and C only).
Connection to high-leg B not permitted for use on this system.
Standard 3 IN/1 OUT branch units are available for this system by
adding suffix CA to catalog number (Examples: EZMR313125CA,
EZMH314125CA, EZMR313225CA and EZMH312225CA).

25
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers

General Information:

125 A QO Tenant
Circuit Breaker Base
(Two-Pole)

QO2100 Tenant
Circuit Breaker
Installed

Meter socket jaws are removable from the front and spring-reinforced.

200 A continuous duty rated meter socket jaws supplied with fifth jaw.

Ringless meter socket covers have provisions to accept utility seals


including plastic padlocks, lead and wire seals, and barrel locks to
prevent unauthorized access to meter socket compartment.

Meter blade guides supplied as standard on both line and load side
meter socket jaws.
Individual ringless-type meter socket covers are provided with stainless
steel hasps that extend through cover, and stainless steel latches for
sealing covers to branch unit. The utility meter or closing plate is
mounted in meter socket.

125 A Tenant Circuit Breaker Compartment

125 A maximum residential branch units will accept 40125 A, two-pole,


plug-on type QO, QO-VH, or QOH circuit breakers (order circuit
breakers separately).

Refer to pages 3 and 4 for meter center available short circuit current
ratings with the above tenant.

225 A Tenant Circuit Breaker Compartment

225 A Q-Frame Tenant


Circuit Breaker Base
(Three-Pole)

225 A maximum branch units listed in this section will accept 100225 A,
two-pole, bolt-on type QB, QD, QG, or QJ circuit breakers.

Or with the use of plug-on adapter catalog number EZM125QOA, these


units will accept 40125 A, two-pole plug-on type QO, and 4060 A
two-pole plug-on type QO-VH and QOH circuit breakers. (Order circuit
breakers and adapters separately.)

Refer to pages 3 and 4 for meter center available short circuit current
ratings with the above tenant circuit breakers installed.

Optional Ringless Residential Meter Socket Features

Ringless-Type Individual
Meter Socket Cover
Ringless-Type Individual
Shown with Barrel Lock
Meter Socket Cover
Shown with Barrel Lock Installed through Cover and
Lock Bracket
Head Protector
(Reverse View)
(Catalog Number MMBLC)

Barrel lock head protector kit, catalog number MMBLC (one kit covers
six meter sockets) is available for field-installation.
Knockout in individual meter socket cover is provided for barrel lock
head protector kit.
Secure head protector kit to cover with lock nut supplied.
Barrel lock not supplied.

Horn bypass kit catalog number MMHB (one kit required per meter
socket) is available for field-installation.
To install horn bypass kit remove one of four 1/4-inch hex nuts from
meter socket jaw assemblies and position horn bypass bus bar
connector on top of meter jaw. Secure with hex nut and torque to
75 lb-in. (8.5 Nm). Repeat this process for remaining three jaw
positions.
Horn bypass bus bars are of different shapes, and must be installed
as shown (refer to instructions provided with each kit).
Horn bypass factory-installed on EZMH device.

Residential Horn Type Bypass Kit Available for


Use on EZMR Ringless Branch Units, and
Standard on EZMH Ringless Branch Units

26
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


225 A Ring-Type EZMT Commercial Branch Units (1 OUT)
Meter Socket
Ringless-Type
(Qty)

Five-Jaw Meter
Socket 1 IN

Five-Jaw Meter
Socket 3 IN

Catalog Number

Catalog Number

Circuit Breaker
Type
(Two-Pole Only)

225 A Ring-Type with Test Block Bypass


One-Position

EZMT111225

EZMT311225

QB, QD, QG, or QJ

Two-Position

EZMT112225

EZMT312225

QB, QD, QG, or QJ

Three-Position

EZMT113225

EZMT313225

QB, QD, QG, or QJ

NOTE: EZMT devices are supplied with Test Block Bypass, which meets EUSERC requirements.

225 A and 400 A Ringless-Type EZML and EZMK Commercial Branch


Units (1 OUT)
Meter Socket
Ringless-Type
(Qty)

EZMT311225

Five-Jaw Meter
Socket 1 IN

Five-Jaw Meter
Socket 3 IN

Catalog Number

Catalog Number

Circuit Breaker
Type
(Two-Pole Only)

225 A Ringless with Lever Type Bypass and Jaw Release


One-Position

EZML111225
EZML111225CU
EZML111225D

QB, QD, QG, or QJ

Two-Position

EZML112225
EZML112225CU
EZML112225D

EZML312225
EZML312225CU
EZML312225D

QB, QD, QG, or QJ

Three-Position

EZML113225
EZML113225CU
EZML113225D

EZML313225
EZML313225CU
EZML313225D

QB, QD, QG, or QJ

Four-Position

EZML114225
EZML114225CU
EZML114225D

EZML314225
EZML314225CU
EZML314225D

QB, QD, QG, or QJ

400 A Ringless with Lever Type Bypass and Jaw Release


One-Position

EZML111400

EZML311400

DJM36400E201

Two-Position

EZML112400

EZML312400

DJM36400E201

400 A Ringless Type K Bolt-On with Manual Bypass

EZML113225

One-Position

EZMK1114002

EZMK311400

DJM36400E201

Two-Position

EZMK1124002

EZMK312400

DJM36400E201

Factory-installed.

Contains one four-jaw meter socket.

Ringless Commercial Meter Socket Compartment Standard Features

1 IN, 1 OUT branch units (include three horizontal cross bus bars). Fivejaw meter sockets supplied as standard. Not available in 400 A branch unit.

3 IN, 1 OUT branch units (include four horizontal cross bus bars). Fivejaw meter sockets supplied as standard.
120/208 Vac, 13W (derived from a 208Y/120 Vac, 34W service).
Standard 3 IN/1 OUT branch units are suitable for use on this
system.

225 A Ringless-Type Meter


Socket, Seven-Jaw with
Lever Type Bypass Shown
with Lexan Shield over Line
and Load Meter Jaws

120/240 Vac, 13W (fed from transformers A and C only).


Connection to high-leg B not permitted for use on this system.
Standard 3 IN/1 OUT branch units are not suitable for use on this
Delta system. Special branch units are available for this system by
adding suffix: CA to catalog number (Examples: EZML313125CA
and EZML312400CA).

400 A Ringless-Type Meter


Socket, Five-Jaw with Lever
Type Bypass Shown with
Lexan Shield over Line and
Load Meter Jaws

320 A continuous duty rated meter sockets supplied with lever bypass.
Lever bypass meter sockets are supplied with jaw release.
27

07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers

Lever bypass meter sockets are supplied with a Lexan shield as an


integral part of the meter socket assembly and used as a guide to assist
mounting of utility meter.

Ringless type K bolt-on meter sockets have a four-jaw socket and only
accept a bolt-on watt-hour meter.

Type K bolt-on meter sockets are supplied with a manual bypass.

Ringless meter socket covers have provisions to accept utility seals


including plastic padlocks, lead and wire seals, padlocks, and barrel
locks to prevent unauthorized access to meter socket compartment.

Individual ringless-type meter socket covers are supplied with a


stainless steel hasp that extends through cover and stainless steel
latches for sealing covers to branch unit while utility meter or closing
plate is mounted in meter socket.

400 A EZMK Bolt-On Meter Socket

225 A Tenant Circuit Breaker Compartment


225 A maximum commercial branch units accept 70225 A, two-pole,
bolt-on type QB, QD, QG, or QJ circuit breakers (order circuit breakers
separately). Refer to pages 3 and 4 for meter center available short circuit
current ratings.

400 A Tenant Circuit Breaker Compartment

DJM36400E20 circuit breakers are factory-installed into 400 A maximum


commercial branch units. Refer to pages 3 and 4 for meter center
available short circuit current ratings.

DJM circuit breaker has adjustable trip settings from 160400 A for field
adjustment.

Optional Ringless Commercial Meter Socket Features


Barrel lock head protector kit, catalog number MMBLC (one kit covers six
meter sockets) is available for field-installation.

DJM circuit breaker seal kit, catalog number 29375, is available for
field-installation.

Knockout in individual meter socket cover is provided for barrel lock


head protector kit.

Secure head protector kit to cover with lock nut provided.


Barrel lock not provided.

Ringless-Type Individual
Meter Socket Cover
Shown with Barrel Lock
Head Protector
(Catalog Number MMBLC)

Ringless-Type Individual
Meter Socket Cover
Shown with Barrel Lock
Installed through Cover and
Lock Bracket
(Reverse View)

28
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Ring-Type Commercial Meter Socket Compartment Standard Features

3 IN, 3 OUT branch units (include four horizontal cross bus bars). Seven-jaw
meter sockets supplied as standard.
EZMT meter sockets are supplied with Test Block Bypass.
EZMT branch devices are bondable to meet EUSERC specifications.

225 A Ring-Type EZMT Commercial Branch Units (3 OUT)


Meter Socket
Ringless-Type (Qty)

Seven-Jaw Meter Socket 3 IN


Catalog Number

Circuit Breaker Type


(Three-Pole Only)

225 A Ring Type with Test Block Bypass


EZMT311225

One-Position

EZMT331225

QB, QD, QG, or QJ

Two-Position

EZMT332225

QB, QD, QG, or QJ

Three-Position

EZMT333225

QB, QD, QG, or QJ

225 A and 400 A Ringless-Type Commercial Branch Units (3 OUT)


Meter Socket
Ringless-Type (Qty)

Seven-Jaw Meter Socket 3 IN


Catalog Number

Circuit Breaker Type


(Three-Pole Only)

225 A Ringless without Bypass


Two-Position

EZMR332225
EZMR332225CU

QB, QD, QG, or QJ

Three-Position

EZMR333225
EZMR333225CU

QB, QD, QG, or QJ

Four-Position

EZMR334225
EZMR334225CU

QB, QD, QG, or QJ

225 A Ringless with Lever Type Bypass and Jaw Release

EZML334225

EZML311400

One-Position

EZML331225
EZML331225CU
EZML331225D

QB, QD, QG, or QJ

Two-Position

EZML332325
EZML332225CU
EZML332225D

QB, QD, QG, or QJ

Three-Position

EZML333225
EZML333225CU
EZML333225D

QB, QD, QG, or QJ

Four-Position

EZML334225
EZML334225CU
EZML334225D

QB, QD, QG, or QJ

400 A Ringless with Lever Type Bypass and Jaw Release


One-Position

EZML331400

DJM36400E20 1

Two-Position

EZML332400

DJM36400E20 1

400 A Ringless Type K with Manual Bypass Provision


225 A Ringless-Type
Meter Socket, Seven-Jaw
without Bypass Shown
with Line and Load Side
Blade Guides

225 A Ringless-Type
Individual Meter Socket
Cover Shown with Stainless
Steel Hasp and Latch for
Use with Utility Seals

400 A Ringless-Type
Individual Meter
Socket Cover

EZMK331400

DJM36400E20 1

Two-Position

EZMK332400

DJM36400E20 1

Factory-installed.

Ringless Commercial Meter Socket Compartment Standard Features

400 A Ringless-Type Meter


Socket, Five-Jaw with
Lever Type Bypass Shown
with Lexan Shield over
Line and Load Meter Jaws

One-Position

3 IN, 3 OUT branch units (include four horizontal cross bus bars). Seven-jaw
meter sockets supplied as standard.
320 A continuous duty rated meter sockets are supplied with lever-type bypass.
Lever-type bypass meter socket is supplied with jaw release.
Lexan shield supplied as an integral part of meter socket assembly and used as a
guide to assist mounting of utility meter.
Individual ringless-type meter socket covers are supplied with stainless steel hasps
that extend through cover and stainless steel latches for sealing covers to branch unit
while utility meter or closing plate is mounted in meter socket.
Ringless meter socket covers have provisions to accept utility seals including
plastic padlocks, lead and wire seals, and barrel locks to prevent unauthorized
access to meter socket compartment.
400 A continuous duty rated meter sockets are supplied with a K-base bolt-on.
400 A K-base bolt-on are supplied with manual bypass provision.
29

07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


225 A Tenant Circuit Breaker Compartment
225 A maximum commercial branch units will accept 70225 A three-pole
bolt-on type QB, QD, QG, or QJ circuit breakers. (Order circuit breakers
separately.) Refer to pages 3 and 4 for meter center available short circuit
current ratings.

400 A Tenant Circuit Breaker Compartment

Q-Frame Circuit Breaker Installed

DJM36400E20 circuit breakers are factory-installed into 400 A maximum


commercial branch units. Refer to pages 3 and 4 for meter center
available short circuit current ratings.

DJM circuit breaker has adjustable trip settings from 160400 A.

Optional Ringless Commercial Meter Socket Features


Barrel lock head protector kit, catalog number MMBLC, (one kit covers six
meter sockets), is available for field-installation.

Knockout in individual meter socket cover is provided for barrel lock


head protector kit.

Secure head protector kit to cover with lock nut, provided.


Barrel lock not provided.

DJM Circuit Breaker Installed

Ringless-Type Individual
Meter Socket Cover
Ringless-Type Individual
Shown with Barrel Lock
Meter Socket Cover
Shown with Barrel Lock Installed through Cover and
Lock Bracket
Head Protector
(Reverse View)
(Catalog Number MMBLC)

30
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Factory Phase Balancing

Factory Phase Balancing


Branch unit meter sockets are phase balanced at the factory according to
the following table:
Meter Socket
(Quantity)

Catalog
Number

AB
(Quantity)

AC
(Quantity)

BC
(Quantity)

125 A Branch Units (used on 120/208 Vac, 13W service derived from a 208Y/120 Vac, 34W system)

Three-Position

EZM313125

Four-Position

EZM314125

Five-Position

EZM315125

Six-Position

EZM316125

Three-Position

EZMR313125

Four-Position

EZMR314125

Five-Position

EZMR315125

Six-Position

EZMR316125

Three-Position

EZMH313125

Four-Position

EZMH314125

Five-Position

EZMH315125

Six-Position

EZMH316125

225 A Branch Units (used on 120/208 Vac, 13W service derived from a 208Y/120 Vac, 34W system)

EZM314125

Two-Position

EZM312225

Three-Position

EZM313225

1
1

Four-Position

EZM314225

Two-Position

EZMR312225

Three-Position

EZMR313225

Four-Position

EZMR314225

Two-Position

EZMH312225

Three-Position

EZMH313225

Four-Position

EZMH314225

Two-Position

EZML312225

Three-Position

EZML313225

Four-Position

EZML314225

400 A Branch Units (used on 120/208 Vac, 13W service derived from a 208Y/120 Vac, 34W system)

One-Position

EZML311400

Two-Position

EZML312400

NOTE: Refer to page 27 for branch units in the field.

31
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Factory Phase Balancing
Phase Balancing Flexibility
The major benefit of factory phase balancing is that most jobs will not
require field phase balancing. To see if meter socket phase balancing in the
field is required (refer to wiring diagram for complete instructions):
A. Determine if the load in amperes on each phase of the transformer using
handle rating of tenant circuit breakers installed at each number of meter
sockets. Use Phase Balancing Chart to determine total number of
connections each meter socket makes on each phase of transformer.
B. If phase balancing is required, determine which meter sockets should be
changed to properly phase balance metering equipment lineup.
C. Once meter socket(s) is selected to be phase balanced, remove
individual meter socket cover from each meter socket to be phase
balanced. The vertical bus bars running top to bottom in the branch unit
behind each meter socket are phased: A, B, C, left to right.
D. By moving only the line side meter socket Z shaped connectors per
meter socket to be changed, phase balancing can easily be
accomplished on-site:
Possible Ending Position
(by moving only one Z connector)

Starting Position
A and B

can be changed to

A and C

A and C

can be changed to

A and B or B and C

B and C

can be changed to

A and C

To change an A and C meter socket to a B and C meter socket:

32
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations

EZM Main Device Types and Configurations


EZM main devices are available as main circuit breakers, main fusible
switches, or main lug terminal boxes; for use in single-phase or three-phase
applications. An EZM main device is required upstream from EZM branch
units even in the case of the NEC six Disconnect rule. EZM main devices
ending in -CB, -FS, or -TB are configured for overhead (top feed) or
underground (bottom feed) service, and are supplied with lugs. EZM main
devices ending in -CBU, -FSU, or -TBU are configured for underground
(bottom feed) service only, and are equipped with lug landing pads (lugs
must be ordered separately).
Circuit Breaker Main Devices (Fed from Overhead or Underground Service)

Service
Type

Ampere
Rating

Catalog
Number

Circuit
Breaker1

Service
Line Phase Line Neutral
Grounding
Terminal
Terminal
Terminal
Wire Range Wire Range
Wire Range
(AWG-kcmil, (AWG-kcmil,
(AWG-kcmil,
Al/Cu)
Al/Cu)
Al/Cu)

1 IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service)


EZM1400CB

LHP264002

600

EZM1600CB

MHP266002 (3) 3/05003

(4) 3/05005

(1) 6300

800

EZM1800CB

MHP268002 (3) 3/05003

(4) 3/05005

(1) 6300

1000

EZM11000CB MHP2610002 (3) 3/05003

(4) 3/05005

(1) 6300

1200

PAF2026 with (4) 1/0750 or (4) 1/0750 or


EZM11200CB
(1) 6300
PA21200RC (8) 1/0250
(8) 1/0250

1600

EZM11600CB

2000

EZM12000CB

EZM1800CB

13W,
120/240
Vac

(1) 1/0600 or (1) 1/0600 or


(1) 6300
(2) 1/02503
(2) 1/02504

400

PAF2026 with (6) 1/0750 or (6) 1/0750 or


(1) 6300
PA21600RC (12) 1/0250 (12) 1/0250
RJF26200

(6) 1/0750 or (6) 1/0750 or


(1) 6300
(12) 1/0250 (12) 1/0250

3 IN Circuit Breaker Main Devices (Fed from Overhead or Underground Service)

34W,
208Y/120
Vac
or
240/120
Vac
Delta
EZM31600CB

(1) 1/0600 or (1) 1/0600 or


(1) 6300
(2) 1/02503
(2) 1/02504

400

EZM3400CB

LHP364002

600

EZM3600CB

MHP366002 (3) 3/05003

(4) 3/05005

(1) 6300

800

EZM3800CB

MHP368002 (3) 3/05003

(4) 3/05005

(1) 6300

1000

EZM31000CB MHP3610002 (3) 3/05003

(4) 3/05005

(1) 6300

1200

PAF2036 with (4) 1/0750 or (4) 1/0750 or


EZM31200CB
(1) 6300
PA31200RC (8) 1/0250
(8) 1/0250

1600

EZM31600CB

2000

EZM32000CB

PAF2036 with (6) 1/0750 or (6) 1/0750 or


(1) 6300
PA31600RC (12) 1/0250 (12) 1/0250
RJF36200

(6) 1/0750 or (6) 1/0750 or


(1) 6300
(12) 1/0250 (12) 1/0250

Supplied factory-installed.

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under
door on cover.

Alternate lug kits are available for use on line side of circuit breaker (refer to most current Digest).

Alternate neutral lug available, order one MMLK500 for use of two 3/0 AWG500 kcmil Al/Cu
(includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only.

Alternate neutral lugs available, order one MMLK250 for use of one 1/0 AWG600 kcmil Al/Cu
or two 1/0 AWG250 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate two
two-barrel lugs only.

EZM32000CB

33
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations
Circuit Breaker Main Devices (Fed from Underground Service Only)

Service Type

Ampere
Catalog Number
Rating

Service
Line Phase and
Grounding
Neutral Lug Landing
Terminal
Pads provided for use
Wire
with Crimp-Type Lugs
Range
(Two-Hole Mounting)
(AWGQuantity of Lugs
kcmil,
permitted per Pad
Al/Cu)

Circuit
Breaker 1

1 IN Circuit Breaker Main Devices (Fed from Underground Service Only)

13W,
120/240 Vac

EZM1800CBU

400

EZM1400CBU 2

LHF26400 3

14

(1) 6300

600

EZM1600CBU

24

(1) 6300

800

EZM1800CBU 2

MHF26800 3

24

(1) 6300

1000

EZM11000CBU 2 MHF2210003

34

(1) 6300

1200

EZM11200CBU 2 MHF2212003

34

(1) 6300

(1) 6300

MHF26600

PA2026 with
PA21600RC

1600

EZM11600CBU

2000

EZM12000CBU 5 RJF26200

(6) 1/0750 or
(12) 1/0250

(1) 6300

3 IN Circuit Breaker Main Devices (Fed from Underground Service Only)

34W,
208Y/120 Vac
or 240/120
Vac Delta

400

EZM3400CBU 2

600

EZM3600CBU

800

EZM3800CBU 2

LHF36400 3

14

(1) 6300

24

(1) 6300

MHF36800 3

24

(1) 6300

1000

EZM31000CBU 2 MHF3210003

34

(1) 6300

1200

EZM31200CBU 2 MHF3212003

34

(1) 6300

PAF2036 with
PA31600RC

(1) 6300

MHF36600

1600

EZM31600CBU

2000

EZM32000CBU 5 RJF36200

(6) 1/0750 or
(12) 1/0250

(1) 6300

Supplied factory-installed.

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for
West Coast based utilities.

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under
door on cover.

Order lugs separately.

Does not meet EUSERC Standards.

Grounding Provisions
Service Grounding
EZM1800CBU

Each main device is equipped with a service grounding lug and


provisions to bond the neutral to the enclosure when required.

EZM main devices are suitable for use as service equipment.

Grounding Lug and Isolated Main


Neutral Bus as Installed at
Factory on Main Devices
EZM32000CBU

Service Grounding Lug, Bonding Strap,


and Bonded Main Neutral Bus as
installed on Main Devices at Job Site as
Required for use as Service Equipment

34
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations
Fusible Switch Main Devices (Fed from Overhead or Underground Service)

Service Ampere
Type
Rating

Catalog
Numbers 1

Line Phase
Terminal
Wire Range
(AWG-kcmil,
Al/Cu)

Molded Case
Switch 2

Service
Line Neutral
Grounding
Terminal
Terminal
Wire Range
Wire Range
(AWG-kcmil,
(AWG-kcmil,
Al/Cu)
Al/Cu)

1 IN Fusible Switch Main Devices (Fed from Overhead or Underground Service)

13W,
120/240
Vac

(1) 1/0600 or (1) 1/0600 or


(1) 6300
(2) 1/0250 4 (2) 1/0250 5

400

EZM1400FS

LHP26000M 3

600

EZM1600FS

MHP260006M 3 (3) 3/0500 4

(4) 3/0500 6

(1) 6300

800

EZM1800FS

MHP260008M 3 (3) 3/0500 4

(4) 3/0500 6

(1) 6300

1200

EZM11200FS PHF260000M

(4) 1/0750 or (4) 1/0750 or


(1) 6300
(8) 1/0250
(8) 1/0250

3 IN Fusible Switch Main Devices (Fed from Overhead or Underground Service)


34W,
208Y/120
Vac or
240/120
Vac Delta
EZM3800FS

(1) 1/0600 or (1) 1/0600 or


(1) 6300
(2) 1/0250 4 (2) 1/0250 5

400

EZM3400FS

LHP36000M 3

600

EZM3600FS

MHP360006M 3 (3) 3/0500 4

(4) 3/0500 6

(1) 6300

800

EZM3800FS

MHP360008M 3 (3) 3/0500 4

(4) 3/0500 6

(1) 6300

Fuses not included. Order 300 V Class T fuses.

Supplied factory-installed.

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under
door on cover.

Alternate lug kits are available for use on line side of molded case switch (refer to most current
Digest).

Alternate neutral lug available, order one MMLK500 for use of two 3/0 AWG-500 kcmil Al/Cu
(includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only.

Alternate neutral lugs available, order one MMLK250 for use on 1/0 AWG-600 kcmil Al/Cu or two
1/0 AWG-250 kcmil Al/Cu (includes three two-barrel lugs). Neutral will accommodate two
two-barrel lugs only.

Fusible Switch Main Devices (Fed from Underground Service Only)

Service Ampere
Type
Rating

Catalog
Numbers 1

Molded Case
Switch 2

Line Phase and Neutral


Lug Landing Pads
provided for use with
Crimp-Type Lugs
(Two-Hole Mounting)
Quantity of Lugs
Permitted per Pad

Service
Grounding
Terminal
Wire
Range
(AWGkcmil,
Al/Cu)

1 IN Fusible Switch Main Devices (Fed from Underground Service Only)


13W,
120/240
Vac

EZM3800FS

400

EZM1400FSU 3

LHF26000M 4

15

(1) 6300

600

EZM1600FSU 3

MHF260006M 4

25

(1) 6300

800

EZM1800FSU 3

MHF260008M 4

25

(1) 6300

1200

EZM11200FSU 3 PHF260000M

35

(1) 6300

3 IN Fusible Switch Main Devices (Fed from Underground Service Only)


34W,
208Y/120
Vac or
240/120
Vac Delta

400

EZM3400FSU 3 LHF36000M 4

15

(1) 6300

600

EZM3600FSU 3 MHF360006M 4

25

(1) 6300

800

EZM3800FSU 3 MHF360008M 4

25

(1) 6300

Fuses not included. Order 300 V Class T fuses.

Supplied factory-installed.

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for
West Coast based utilities.

Handle extension available, order kit AHEXLI. Handle is hinged, allowing it to be tucked under
door on cover.

Order lugs separately.

35
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations
Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)
Service Ampere
Type
Rating

Line Phase Neutral


Service Ground
Terminal Wire Range Terminal Wire Range
(AWG-kcmil, Al/Cu)
(AWG-kcmil, Al/Cu)

Catalog
Number

1 IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)

13W,
120/240
Vac

225

EZM1225TB

(1) 4300

(1) 6300

400

EZM1400TB

(2) 3/0500 1

(1) 6300

600

EZM1600TB

(2) 1/0750 or
(4) 1/0300

(1) 6300

800

EZM1800TB and
EZM1800TBCU

(4) 3/0500 2

(1) 6300

1600

EZM11600TB

(6) 1/0600 or
(12) 1/0300

(1) 6300

2000

EZM12000TB

(6)

(1) 6300

3 IN Main Lugs Terminal Boxes (Fed from Overhead or Underground Service)

EZM1800TB

34W,
208Y/120
Vac or
240/120
Vac Delta

225

EZM3225TB

(1) 4300

(1) 62/0

400

EZM3400TB

(2) 3/0500 1

(1) 6300

600

EZM3600TB

(2) 1/0750 or
(4) 1/0300

(1) 6300

(4) 3/0500

800

EZM3800TB

1600

EZM31600TB

(6) 2600

(1) 6300

2000

EZM32000TB

(6) 3

(1) 6300

(1) 6300

Alternate lug kits available with the use of lug landing kit EZMSK2.

Alternate lug kit available, order MMLK250 kits for two 1/0 AWG600 kcmil or four
1/0 AWG250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept two
two-barrel lugs. For 1 applications, order two kits. For 3 applications, order three kits.

Order lugs separately. Device provided with 6 lug landing pads per phase and neutral for use
with mechanical or crimp type lugs.

Main Lugs Terminal Boxes (Fed from Underground Service)

Service Ampere
Type
Rating

EZM1800TB

Line Phase and


Neutral Lug Landing
Pads provided for use
Service Ground
with Crimp-type Lugs Terminal Wire Range
(Two-hole Mounting) (AWG-kcmil, Al/Cu)
Quantity of Lugs
Permitted per Pad

Catalog
Number1 2 3

1 IN Main Lugs Terminal Boxes (Fed from Underground Service Only)


13W,
120/240
Vac

400

EZM1400TBU

1 (order lugs separately)

800

EZM1800TBU

2 (order lugs separately)

(1) 6300
(1) 6300

1200

EZM11200TBU 4

3 (order lugs separately)

(1) 6300

3 IN Main Lugs Terminal Boxes (Fed from Underground Service Only)


34W,
208Y/120
Vac or
240/120
Vac Delta

400

EZM3400TBU

1 (order lugs separately)

(1) 6300

800

EZM3800TBU

2 (order lugs separately)

(1) 6300

3 (order lugs separately

(1) 6300

1200

EZM31200TBU

For mechanical lugs (3/0 AWG600 kcmil) order kit CMELK4, kit includes four lugs only;
multiple kits may be required.

Meets Electrical Utility Service Equipment Requirements Committee (EUSERC) Standards for
West-coast based utilities.

Tap box is suitable for use on Line or Load side of service equipment. Supplied with isolated
neutral and provided with neutral bonding kit for use as required.

Supplied with copper horizontal bus bars and aluminum vertical bus bars.

EZM32000TB

36
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations
EZM Main Device Standard and Alternate Lugs
Alternate Lugs by Manufacturer, Catalog Number, Wire Range AWG-kcmil, Crimping Tool, and Quantity Per Line
Side Phase and Neutral (Order Lugs Separately)

TA-600-2N1

TA-800-2N

AU-600-2N
(Two-Barrel)

750-1000
Al

2-600
Al/Cu

300-800
Al/Cu

250-600
Al/Cu

2-600
Al/Cu

300-800
Al/Cu

(2) 2-600
Al/Cu

Mechanical

IDT-12

Mechanical

Mechanical

L1D2-800

2ACL-600

500-750
Cu

L1D2-600

LID2-800

250-600
Cu

2AB2-600
(Two-Barrel

LID2-600

Line Side
Neutral
Terminals

VACL-1000-12BN

Line Side
Phase
Terminals

CMC

VHCL-750-12BN

Catalog
Number

ILSCO

VHCL-600-12BN

ANDERSON

A1B2-600-2

Standard Lugs (FactoryInstalled)

(2) 2-600 2-600 (2) 2-600 300-800


Al/Cu Al/Cu Al/Cu
Al/Cu

VC-6

VC-7

VC-8

EZM1400CB2 3

(1) AL400LA

(1) MMLK250

Mechanical

Mechanical

EZM1600CB2 4

(1) AL900MA

(2) MMLK500

EZM1800CB2 4

(1) AL900MA

(2) MMLK500

EZM11000CB2 4 (1) AL900MA

(2) MMLK500

EZM11200CB5

(4) 40251-136-50 (4) 40251-136-50

EZM11600CB5

(6) 40251-136-50 (6) 40251-136-50

EZM12000CB5

(6) 40251-136-50 (6) 40251-136-50

EZM3400CB2 3

(1) AL400LA

(1) MMLK250

EZM3600CB2 4

(1) AL900MA

(2) MMLK500

EZM3800CB2 4

(1) AL900MA

(2) MMLK500

EZM31000CB2 4 (1) AL900MA

(2) MMLK500

EZM31200CB5

(4) 40251-136-50 (4) 40251-136-50

EZM31600CB5

(6) 40251-136-50 (6) 40251-136-50

EZM32000CB5

(6) 40251-136-50 (6) 40251-136-50

EZM1400CBU

Studs (1 lug)

Studs (1 lug)

EZM1600CBU

Studs (2 lugs)

Studs (2 lugs)

EZM1800CBU

Studs (2 lugs)

Studs (2 lugs)

EZM11000CBU

Studs (3 lugs)

Studs (3 lugs)

EZM11200CBU

Studs (3 lugs)

Studs (3 lugs)

EZM11600CBU

Studs (6 lugs)

Studs (6 lugs)

EZM12000CBU

Studs (6 lugs)

Studs (6 lugs)

66

66

66

EZM3400CBU

Studs (1 lug)

Studs (1 lug)

EZM3600CBU

Studs (2 lugs)

Studs (2 lugs)

EZM3800CBU

Studs (2 lugs)

Studs (2 lugs)

EZM31000CBU

Studs (3 lugs)

Studs (3 lugs)

EZM31200CBU

Studs (3 lugs)

Studs (3 lugs)

EZM31600CBU

Studs (6 lugs)

Studs (6 lugs)

EZM32000CBU

Studs (6 lugs)

Studs (6 lugs)

66

66

66

66

EZM1400FS2 3

(1) AL400LA

(1) MMLK250

EZM1600FS2 4

(1) AL900MA

(2) MMLK500

EZM1800FS2 4

(1) AL900MA

(2) MMLK500

EZM11200FS5

(4) 40251-136-50 (4) 40251-136-50

EZM3400FS2 3

(1) AL400LA

(1) MMLK250

EZM3600FS2 4

(1) AL900MA

(2) MMLK500

EZM3800FS2 4

(1) AL900MA

(2) MMLK500

EZM1400FSU

Studs (1 lug)

Studs (1 lug)

EZM1600FSU

Studs (2 lugs)

Studs (2 lugs)

EZM1800FSU

Studs (2 lugs)

Studs (2 lugs)

EZM11200FSU

Studs (3 lugs)

Studs (3 lugs)

EZM3400FSU

Studs (1 lug)

Studs (1 lug)

1
2
3
4
5
6

This lug is available from Schneider Electric. Order catalog number CMELK4; kit includes four lugs.
Alternate lug kits are available for use on line side terminals of molded case circuit breaker or molded case switch (refer to most current Digest).
Alternate neutral lugs available, order one kit MMLK500 for two 3/0 AWG500 kcmil Al/Cu (kit includes three two-barrel lugs). Neutral will accommodate one two-barrel lug only.
Alternate neutral lugs available, order one kit MMLK250 for one 1/0 AWG600 kcmil Al/Cu or two 1/0 AWG250 kcmil (kit includes three two-barrel lugs). Neutral will accommodate two two-barrel
lugs only.
Lugs are supplied factory-installed on the lug landing pads of this device. Alternate lugs are available.
Wire range is limited to 750 kcmil max. in this device to comply with wire bending space requirements.

37
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations
Alternate Lugs by Manufacturer, Catalog Number, Wire Range AWG-kcmil, Crimping Tool, and Quantity Per
Line Side Phase and Neutral (Order Lugs Separately)

AU-600-2N
(Two-Barrel)

250-600
Al/Cu

2-600
Al/Cu

300-800

(2) 2-600
Al/Cu

Mechanical

IDT-12

Mechanical

Mechanical

L1D2-800

TA-800-2N

300-800

L1D2-600

TA-600-2N1

2-600
Al/Cu

2AB2-600
(Two-Barrel

2ACL-600

CMC

LID2-800

250-600 500-750 750-1000


Cu
Cu
Al

ILSCO

LID2-600

Line Side
Neutral
Terminals

VACL-1000-12BN

Line Side Phase


Terminals

VHCL-750-12BN

Catalog Number

VHCL-600-12BN

ANDERSON

A1B2-600-2

Standard Lugs (FactoryInstalled)

(2) 2-600 2-600 (2) 2-600 300-800


Al/Cu Al/Cu
Al/Cu
Al/Cu

VC-6

VC-7

VC-8

EZM3600FSU

Studs (2 lugs)

Studs (2 lugs)

Mechanical
2

Mechanical

EZM3800FSU

Studs (2 lugs)

Studs (2 lugs)

EZM1225TB

(1) 40251-052-50

(1) 40251-052-50

EZM1400TB2 3 4

(1) MMLK500

(1) MMLK500

EZM1600TB2 5

(2) 40251-136-50

(2) 40251-136-50

EZM1800TB6

(2) MMLK500

(2) MMLK500

EZM11600TB

(6) 40251-136-50 (6) 40251-136-50

EZM3225TB

(1) 40251-052-50

(1) 40251-052-50

EZM3400TB2 3 7

(1) MMLK500

(1) MMLK500

EZM3600TB2 5

(2) 40251-136-50

(2) 40251-136-50

EZM3800TB8

(2) MMLK500

(2) MMLK500

EZM12000TB

Studs (6 lugs)

Studs (6 lugs)

EZM31600TB

(6) 40251-136-50 (6) 40251-136-50

EZM32000TB

Studs (6 lugs)

Studs (6 lugs)

EZM1400TBU5

Studs (1 lug)

Studs (1 lug)

EZM1800TBU5

Studs (2 lugs)

Studs (2 lugs)

EZM11200TBU5

Studs (3 lugs)

Studs (3 lugs)

EZM3400TBU/CU5

Studs (1 lug)

Studs (1 lug)

EZM3800TBU/CU5

Studs (2 lugs)

Studs (2 lugs)

EZM31200TBU/CU5 Studs (3 lugs)

Studs (3 lugs)

1
2
3
4
5
6
7
8

This lug kit is available from Schneider Electric. Order catalog number CMELK4; kit includes four lugs.
Alternate lug requires the use of lug landing kit part number EZMSK2 (order separately).
See pad drawing or wiring diagram for additional alternate lugs.
Alternate lug kit available from Schneider Electric. Order one kit MMLK250 for one 1/0 AWG600 kcmil or 2 1/0 AWG250 kcmil Al/Cu (kit includes three two-barrel lugs) each bus bar will accept
one two-barrel lug.
See pad drawing for additional alternate lugs.
Alternate lug kit available from Schneider Electric. Order two MMLK250 kits for two 1/0 AWG600 kcmil or four 1/0 AWG250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will
accept two two-barrel lugs.
Alternate lug kit available. order two MMLK250 kits for one 1/0 AWG250kcmil or two 1/0 AWG250kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept one two-barrel lug.
Alternate lug kit available. Order three MMLK250 kits for two 1/0 AWG600 kcmil or four 1/0 AWG250 kcmil Al/Cu (each kit includes three two-barrel lugs) each bus bar will accept two two-barrel lugs.

38
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


EZM Main Device Types and Configurations

EZM Mains Devices


Number Segment

Character

Device Name

Description

EZM

EZM

EZ Meter-Pak Meter Center

13W

1000

CB

CU

125

CU

Service Feed
3

34W
225 A
400 A
600 A
800 A

Mains Rating
1000 A
1200 A
1600 A
2000 A

Main Type

CB

Main Circuit Breaker

FS

Main Fusible Switch

TB

Terminal Box

Blank

Overhead/Underground

Underground Only, Meets EUSERC Standards up to 1200 A max.

Blank

Aluminum Horizontal Cross Bus Bar up to 1000 A max.

CU

Copper Horizontal Cross Bus Bar

Feed Direction

Special Construction

EZM Branch Units


Number Segment Character
Device Name

Description

EZM

EZM

EZ Meter-Pak Meter Center

Blank

Ring Type

Ringless Type with 5th Jaw

Ringless with Horn Bypass and 5th Jaw

Lever Bypass with 5th Jaw, 7th Jaw if Three-Phase

Ring Type Test-Block Bypass EUSERC

Socket/Bypass Type

K-Base Bolt-On Type

13W

34W

13W

34W

Meter
Sockets
Available

1, 2, 3, 4, 5, or 6

Service Feed

Load Feed
Number of Meter
Sockets
Maximum Tenant
Circuit Breaker
Amperage

125 A
225 A
400 A
Blank

Aluminum Horizontal Cross Bus Bar

CA

For 240/120 Vac Delta Systems

CU

Copper Horizontal Cross Bus Bar

Removable Drip Hood with Indoor Top Endwall with Knockouts

M10

10-Inch Meter Centers

1200 A Copper Horizontal Cross Bus Bar

Special Construction

39
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts

Dimensions and Knockouts


Box Side

18.66
[474]
14.50
[368]

11.50
[292]
Nut

Captive
Screw

Torque to
50 lb-in.

Omitted on
1 Units

Hanging
Mounting Rail
Hex
Nut (2)

3.44
[87]
Omitted on
1 Units

53.97
[1371]

Gasket
Top View

2.00
[51]

Square
Neck
Bolt

(1)
Sealing
Wing Nut

Line
Phase
Lugs Line
Neutral

(1)
Sealing
Wing Nut

Closing
Cap

Box
Side
Right

(1)
(1)

Closing
Cap

(1)

(1)
(1)

Gasket
14.50
[368]
18.48
[469]

E, F, G, H, I, J

9.13
[232]
11.06
[281]

5.09
[129]

3.00
[76]

Hex
Nut (2)

Captive
(2) Screw

Box
Side
Left

34.30
[871]
24.75
[629]

1.00
[25.5]

Gasket
Right Side Closing Cap

Left Side Closing Cap


30.19
[767]
24.00
[610]

18.33
[466]

A, B
11.06
[281]
Omitted on
1 Units

1.12
[28]
2.92
[74]

5.61 5.61
[142] [142]

0.91
[23]

Hanging
Mounting
Rail

3.44
[87]

EZM1400CB, EZM3400CB
EZM1600CB, EZM3600CB
EZM1800CB, EZM3800CB
EZM11000CB, EZM31000CB

Omitted on
1 Units

61.19
[1554]

38.13
[969]

19.38
[492]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

Line
Phase
Lugs

Line
Neutral

21.91
[557]

Symbol
A
B

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51
64

2.00

51

2.50

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

24.00
[610]
30.00
[762]

17.83
[453]

E, F, G,
H, I, J
3.07
[78]

17.83
A, B [453]

1.16
[29]
4.81
[122]

6.75
[171]

6.75
[171]

6.75
[171]

in.
Dimensions: [mm]

0.92
[23]

EZM11200CB, EZM31200CB
EZM11600CB, EZM31600CB

40
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

30.19
[767]
24.00
[610]

18.31
[465]

0.31
[8]

Nut

Captive
Screw

Omitted on
1 Units

Torque to
50 lb-in.

Hanging
Mounting Rail

3.44
[87]
Typ.
Omitted
on 1
Units

Gasket
Top View
2.00
[51]

Hex
Nut (2)

68.91
[1750]

Square
Neck
Bolt
(2)

(1)
Line
Phase
Lugs

44.50
[1130]
Line
Neutral

Sealing
Wing Nut

Box
Side
Left

31.35
[796]

27.35
[695]

Closing
Cap
(1)
Grounding Lug

24.00
[610]

17.89
[454]

(1)

(1)
Gasket

30.00
[762]

Left Side Closing Cap


1.00
[25.5]

17.89
[454]

Hex
Nut (2)

Captive
Screw

(1)

EZM12000CB, EZM32000CB
Sealing
Wing Nut

NOTE: No knockouts provided.


30.19
[767]
24.00
[610]

21.46
[545]

0.20
[5]

Box
Side
Right

Closing
Cap
(1)

30.67
[779]

Omitted on
1 Units

0.34
[9]
Top of
Mounting
Channel

3.44
[87]

(1)
Gasket
Right Side Closing Cap

71.09
[1806]

30.67
[779]

30.39
[772]

1/2-13 in. studs and keps nuts provided.


2.69
[68]
Typical

37.62
[956]
1.75
[44]

Lug Landing Pad Detail


1.81
[46]
See Detail B

20.73
[527]

EZM12000TB, EZM32000TB

NOTE: No knockouts provided.

in.
Dimensions: [mm]

41
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

18.66
[474]
14.50
[368]

11.50
[292]
Nut
Captive
Screw

Torque to
50 lb-in.

17.72
[450]
Omitted on
1 Units

Gasket
Top View

Hanging
Mounting Rail

3.44
[87]
Omitted on
1 Units

2.00
[51]

Hex
Nut (2)

53.97
[1371]

(1)
Sealing
34.30 Wing Nut
[871]

Line
Neutral
Lugs
Line
Phase
Lugs

Square
Neck Captive
Screw
Bolt
(2)

Hex
Nut (2)
(1)
Sealing
Wing Nut

Box
Side
Left
Box
Side
Right

Closing
Cap

16.50
[419]

1.00
[25.5]

Closing
Cap

(1)

14.50
[368]
18.48
[469]

E, F, G, H, I, J

(1)
Gasket

11.06
[281]

5.09
[129]

3.01
[76]

(1)

(1)

(1)

Gasket
Right Side Closing Cap

Left Side Closing Cap

30.19
[767]
24.00
[610]

A, B
11.06
[281]

18.33
[465]

1.12
[28]
2.92
[74]

5.61 5.61
[142] [142]

0.91
[23]

3.44
[87]

Hanging
Mounting
Rail

EZM1400FS, EZM3400FS
EZM1600FS, EZM3600FS
EZM1800FS, EZM3800FS
61.19
[1554]

38.13
[968]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

Symbol

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

19.38
[492]

21.91
[556]

Line
Neutral
Lugs

Line
Phase
Lugs
24.00
[610]
30.00
[762]

17.83
[453]

E, F, G,
H, I, J
3.07
[78]

4.81
[122]

17.83
A, B [453]

1.16
[29]
6.75
[171]

6.75
[171]

6.75
[171]

0.92
[23]

in.
Dimensions: [mm]

EZM11200FS

42
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

11.66
[296]
5.85
[149]

1.74
[44]

6.37
[162]

Nut
Captive
Screw

See detail C

3.44
[87]

21.81
[554]

Gasket
Top View

2.00
[51]

Hex
Nut (2)

Square
Neck
Bolt

(1)
Sealing
Wing Nut

Omitted on
1 Units

5.74
[146]

Torque to
50 lb-in.

0.34
[9]

(1)
5.81
[148]

1.80
[46]

0.27
[7]

Closing
Cap
(1)

(1)
(1)

Gasket
Gasket
Right Side Closing Cap

Left Side Closing Cap


A

See detail B

13.00
[330]

D, E, F, G

17.15
[436]
1.68
[43]

7.09
[180]
0.34
[9]

See detail C

1.21
[31]
0.75
[19]

4.45
[113]

Hex
Nut (2)
(1)
Sealing
Wing Nut

Box
Side
Right

(1)
11.50
[292]

Captive
Screw
(2)

Box
Side
Left

Closing
Cap

See detail A

1.00
[25.5]

0.32
[8]
Top of
Mounting
Channel

3.62
[92]
11.38
[289]
3.44
[87]

EZM1225TB, EZM3225TB

30.46
[774]

Omitted on
1 Units
16.29
[414]

1.00
[25]
0.25
[6]

R 0.19
[5]

9.03
[229]
See detail A

1.08
[27]
0.78
[20]

1.50
[38]

Detail A
Bottom Mounting Bracket
R 0.13
[3]
R 0.25
[6]

17.00
[432]
Detail B
Cover Sealing Latch

1.50
[38]

0.40
[10]

0.38
[10]
Detail C
Top Mounting Bracket

NOTE: For knockout dimensions,


see table on opposite page.

A
A, B

3.25
[83]

6.53
[166]

1.80
[46]

0.34
[9]

See detail B
E, F, G, H, I, J

6.53
[166]

2.00
[51]
0.89
[23]

5.50
5.75
[140]
[146]
17.00
[432]

2.84
[72]

2.86
[73]

EZM1400TB, EZM3400TB
EZM1600TB, EZM3600TB

43
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

18.66
[474]
14.50
[368]

11.50
[292]
Nut
Captive
Screw

16.12
[409]
Hanging
Mounting Rail

3.44
[87]
53.97
[1371]

Omitted
on 1
Units

2.00
[51]

Hex
Nut (2)

Torque to
50 lb-in.
Gasket
Top View
Square
Neck
Bolt

(1)
Sealing
Wing Nut

Hex
Nut (2)
(1)

Captive
Screw
(2)

Sealing
Wing Nut

Box
Side
Left

34.30
[871]

26.59
[675]

Line
Phase
Lugs
Line
Neutral

1.00
[25.5]

Box
Side
Right

Closing
Cap
(1)

Closing
Cap
(1)

(1)

(1)

(1)
Gasket
9.13
[232]
11.06
[281]

14.50
[368]
18.48
[469]

E, F, G,
H, I, J
3.00
[76]

Left Side Closing Cap

A, B
11.06
[281]

19.93
[506]

1.12
[28]
2.92
[74]

5.61 5.61
[142] [142]

24.00
[610]
1.68
[43]

Gasket
Right Side Closing Cap

7.09
[180]

See detail C
on page 43

0.91
[23]

EZM1800TB
EZM3800TB

0.33
[8]
Top of
Mounting
Channel

3.44
[87]
51.76
[1315]

Omitted
on 1
Units

20.71
[526]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

28.01
[712]
Line
Neutral

See detail A
on page 43

Symbol

Line
Phase
Lugs

0.34
[9]

23.93
[608]

1.81
[46]

6.53
[166]

See detail B on page 43


E, F, G, H, I, J

2.97
[75]

A, B

3.00
[76]

5.61
[143]
Typ.
EZM1800TBCU
EZM3800TBCU

0.87
[22]
3.12
[79]
in.
Dimensions: [mm]

44
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts

22.48
[571]

Box Side

18.33
[466]

12.94
[329]
Nut
Captive
Screw

See detail C
on page 43

Torque to
50 lb-in.

0.33
[8]

Gasket
Top of
Mounting
Channel

3.44
[87]

2.00
[51]

Hex
Nut (2)

55.12
[1400]

Square
Neck
Bolt
(2)

(1)

Omitted on
1 Units

Sealing
Wing Nut
Line Phase
Lugs

22.37
[568]

Line
Neutral

21.06
[535]

29.67
Closing
Cap[754]
(1)
(1)

1.81
[46]
A, B
3.80
[97]

Box
Side
Left

0.34
[9]

See detail A
on page 43

2.97
[75]

Top View

12.38
[314]

(1)
Gasket
Left Side Closing Cap
1.00
[25.5]

See detail B on page 43


E, F, G, H, I, J

Hex
Nut (2)
(1)

Captive
Screw
5.53
[140]

1.06
[27]

1.56
[40]

6.61
6.61
[168] [168]
22.33
[567]

5.06
[129]

Sealing
Wing Nut

3.90
[99]

Box
Side
Right

Closing
Cap
(1)

EZM11600TB
EZM31600TB

(1)
Gasket
Right Side Closing Cap

Knockouts
Conduit Size

Hole Diameter

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

in.
Dimensions: [mm]

45
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

20.46
[520]
16.30
[414]

11.50
[292]

Nut

Captive
Screw

Omitted on
1 Units

Hanging
Mounting
Rail Hex
Nut (2)

3.44
[87]

Torque to
50 lb-in.
Gasket
Top View

2.00
[51]

Square
Neck
Bolt

(1)
Omitted on
1 Units

Sealing
Wing Nut

Sealing
Wing Nut

Box
Side
Right

Closing
Cap

30.25
[768]

Line
Phase
Pads

49.37
[1254]

Line
Neutral
Pad

(1)

Closing
Cap
(1)

(1)

(1)

(1)
Gasket
Gasket
Right Side Closing Cap

Left Side Closing Cap


20.46
[520]
16.30
[414]

16.30
[414]
20.28
[515]

11.06
[281]

E, F, G, H, I, J
3.03
[77]

Hex
Nut (2)
(1)

Captive
Screw
(2)

Box
Side
Left

69.03
[1753]

4.00
[102]

1.00
[25.5]

11.50
[292]

3.44
[87]

Hanging
Mounting
Rail

A, B
11.06
[281]
69.03
[1753]

1.12
[28]
4.34
[110]

5.80 5.80
[147] [147]

0.91
[23]
4.00
[102]

EZM1400CBU
EZM3400CBU

49.36
[1254]

Line
Neutral
Pad

Line
Phase
Pads
31.16
[791]

Knockouts
Conduit Size

Hole Diameter

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

46
2008 Schneider Electric All Rights Reserved

11.06
[281]

16.30
[414]
20.28
[515]
E, F, G, H, I, J
3.03
[77]

A, B
11.06
[281]
1.12
[28]

4.34
[110]

5.80 5.80
[147] [147]

0.91
[23]
EZM1600CBU
EZM1800CBU

in.
Dimensions: [mm]

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

26.19
[665]
20.00
[508]

11.65
[296]

Nut

Captive
Screw

Torque to
50 lb-in.
Gasket
Top View

2.00
[51]

Hex
Hanging
Nut (2)
Mounting
Rail
(1)

3.44
[87]

Square
Neck
Bolt

Sealing
Wing Nut

69.03
[1753]

Line
Phase
Pads

Gasket
Right Side Closing Cap

Left Side Closing Cap


34.19
[868]
24.00
[610]

18.33
[466]

Omitted on
1 Units

E, F, G, H, I, J

Hanging
Mounting
Rail

3.44
[87]

A, B
11.10
[282]

Omitted on
1 Units

1.13
[29]
8.25
[209]

(1)

(1)

Gasket

11.10
[282]

3.04
[77]

4.75
[121]

Closing
Cap

(1)

31.16
[791]

20.00
[508]
26.00
[660]

Box
Side
Right
(1)

Line
Neutral
Pad

8.25
[209]

Hex
Nut (2)
(1)
Sealing
Wing Nut

(1)
49.36
[1254]

Captive
Screw
(2)

Box
Side
Left

Closing
Cap

4.00
[102]

1.00
[25.5]

70.07
[1780]

0.92
[23]

EZM3600CBU
EZM3800CBU

4.28
[109]
26.08
[662]

Line
Phase
Pads

46.99
[1193]

Line
Neutral
Pad

Knockouts
Conduit Size

Hole Diameter

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

17.83
[453]

24.00
[610]
34.00
[864]
E, F, G,
H, I, J
3.06
[78]

17.83
A, B [453]

1.16
[29]
5.37
[136]

7.75
[197]

7.75
[197]

7.75
[197]

0.92
[23]

in.
Dimensions: [mm]

EZM11000CBU, EZM31000CBU, EZM11200CBU, EZM31200CBU

47
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
30.19
[767]

1.88
[48]

Box Side

0.86
[22]

18.34
[466]

Nut
Captive
Screw

17.61
[447]

Torque to
50 lb-in.

37.08
[942]

Gasket
Top View
0.62
[16]

71.16
[1807]

29.04
[738]

2.00
[51]

6.75
[171]

1.75
[44]
5.32
[135]

0.97
[25]
6.40
[163]

33.16
[842]

Square
Neck
Bolt

1.75
[51]

Sealing
Wing Nut

1.75
[44]

4.73
[120]

[16]

(1)

1.75
[44]

2.00
[51]

Hex
0.62
Nut
(2)

Hex
Nut (2)
(1)
Sealing
Wing
Nut

Box
Side
Right

Cap

1.00
[25]

Captive
Screw
(2)

Box
Side
Left

2.00
2.00
[51]
[51]
0.69
0.69
[18] Closing
[18]

2.00
[51]

1.00
[25.5]

(1)

Closing
Cap
(1)

(1)

(1)

(1)
Gasket
Left Side Closing Cap

NOTE: No knockouts provided.

Gasket
Right Side Closing Cap

30.19
[767]

30.00
[762]

18.31
[465]

24.00
[610]

0.31
[8]

17.89
[454]
Hanging
Mounting
Rail

Omitted on
1 Units
EZM11600CBU
EZM31600CBU

3.44
[87]
Typ.

Omitted on
1 Units

68.91
[1750]

Line
Lug
Pads

44.50
[1130]

Line
Neutral

26.13
[664]

24.00
[610]

31.35
[796]

Grounding
Lug

17.89
[454]

30.00
[762]

17.89
[454]

NOTE: No knockouts provided.


EZM12000CBU, EZM32000CBU

in.
Dimensions: [mm]

48
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side
20.46
[520]
16.30
[414]

11.50
[292]

Nut
Captive
Screw

Omitted on
1 Units

Hanging
Mounting
Hex
Rail
0.62
Nut
(2)

3.44
[87]

[16]

(1)

Omitted on
1 Units

Gasket
Top View

2.00
[51]

Square
Neck
Bolt

1.75
[51]

Sealing
Wing Nut

49.37
[1254]
Line
Phase
Pads

5.00
[127]

Line
Neutral
Pad

11.06
[281]

16.31
[414]
20.29
[515]
E, F, G, H, I, J
3.03
[77]

1.00
[25.5]

Captive
Screw
(2)

Box
Side
Right

Cap

(1)

Hex
Nut (2)
Sealing
Wing
Nut

Box
Side
Left

2.00
[51]
0.69
Closing
[18]

69.03
[1753]

22.00
[559]

Torque to
50 lb-in.

Closing
Cap
(1)

(1)

(1)
20.46
[520]

(1)

Gasket
Left Side Closing Cap
16.30
[414]

Gasket
Right Side Closing Cap
11.50
[292]

3.44
[87]

Hanging
Mounting
Rail

A, B
11.06
[281]
1.12
[28]

4.34
[110]

5.80 5.80
[147] [147]

0.91
[23]

69.03
[1753]

EZM1400FSU
EZM3400FSU
Line
Phase
Pads

Line
Neutral
Pad

26.06
[662]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

49.36
[1254]

4.75
[121]

Symbol

E, F, G, H, I, J

11.06
[281]

16.30
[414]
20.28
[515]

3.03
[77]

A, B
11.06
[281]
1.12
[28]

4.34
[110]

5.80 5.80
[147] [147]

0.91
[23]
EZM1600FSU
EZM1800FSU

Dimensions:

in.
[mm]

49
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
\

Box Side

26.19
[665]
20.00
[508]

11.65
[296]

Nut

Captive
Screw

Gasket
Top View

Hanging
Mounting
Hex
Rail
Nut (2)

3.44
[87]

Torque to
50 lb-in.

2.00
[51]

1.00
[25.5]
(2)

(1)
Sealing
Wing
Nut
1.75

Square
Neck
Bolt

[51]

69.03
[1753]
49.36
[1254]

26.06
[662]

Line
Phase
Pads

Box
Side
Right

(1)

Closing
Cap
(1)

Gasket
Right Side Closing Cap

Left Side Closing Cap


34.26
[870]
24.00
[610]

18.32
[465]

11.10
[282]
E, F, G, H, I, J

3.04
[77]

3.44
[87]

Hanging
Mounting
Rail

A, B
11.10
[282]
1.13
[29]

4.75
[121]

Hex
Nut (2)
(1)
Sealing
Wing
Nut

(1)
Gasket

4.75
[121]

Line
Neutral
Pad

20.00
[508]
26.00
[660]

Box
Side
Left

Closing
Cap
2.00
[51]
(1)
0.69
[18]

Captive
Screw

8.25
[209]

8.25
[209]

70.05
[1779]

0.92
[23]

EZM3600FSU
EZM3800FSU

26.08
[662]

Line
Neutral
Pad

Line
Phase
Pads

46.99
[1193]

6.25
[159]

Knockouts
Conduit Size

Hole Diameter

Symbol
A

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

24.00
[610]
34.00
[864]

E, F, G,
H, I, J

17.83
[453]

3.09
[78]

17.83
A, B [453]

1.16
[29]
5.37
[136]

7.75
[197]

7.75
[197]

7.75
[197]

0.92
[23]

EZM11200FSU

Dimensions:

in.
[mm]

50
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side
17.16
[436]
13.00
[330]

2.08
[53]

8.00
[203]

0.34
[9]
Nut
Captive
Screw

Top of
Mounting
Channel

Omitted on
1 Units
3.44
[87]

Gasket
Top View

0.33
[8]

Omitted on
1 Units

35.72
[907]

1.75
[44]
19.88
[505]

27.17
[690]

22.36
[568]

2.00
[51]

Hex
0.62
Nut
(2)
[16]

(1)

Square
Neck
Bolt

1.75
[51]

Sealing
Wing Nut

2.00
[51]

7.44
[189]

13.00
[330]

Captive
Screw
(2)

(1)

Closing
Cap
(1)

(1)

(1)

(1)
Gasket
Gasket
Right Side Closing Cap

Left Side Closing Cap

A, B

8.00 8.72
[203] [221]

5.88
[149]

Hex
Nut (2)

Sealing
Wing
Nut
Box
Side
Right

Cap

E, F, G, H, I, J

1.18
[30] 1.14
[29]

1.00
[25.5]

Box
Side
Left

2.00
[51]
0.69
Closing
[18]

17.00
[432]

3.09
[78]

Torque to
50 lb-in.

25.16
[639]
21.00
[533]

5.40
[137]

11.68
[297]
Top of
Mounting
Channel

Omitted on
1 Units

EZM1400TBU, EZM3400TBU

3.44
[87]

0.33
[8]

Omitted on
1 Units
2.00
[51]

1.75
[44]

2.00
[51]

Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

21.00
[533]

11.12
[283]

25.00
[635]

Symbol

31.17
[792]

26.44
[672]

23.88
[607]

Knockouts

39.97
[1015]

E, F, G, H, I, J
11.68
[297]

A, B
3.09
[79]

1.19
[30]

12.05
[306]

1.19
[30]
9.92
[252]

5.40
[137]
EZM1800TBU, EZM3800TBU
in.
Dimensions: [mm]

51
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
Box Side

Nut

Captive
Screw

Gasket
Top View

2.00
[51]

Hex
Nut (2)

Torque to
50 lb-in.

Square
Neck
Bolt

(1)
Sealing
Wing Nut

1.00
[25.5]

Captive
Screw
(2)

Sealing
Wing Nut

Box
Side
Left
Box
Side
Right

Closing
Cap
(1)

Hex
Nut (2)
(1)

Closing
Cap

(1)

(1)

(1)
Gasket
Left Side Closing Cap

Gasket
Right Side Closing Cap

33.16
[842]
29.00
[737]

11.68
[297]

Omitted on
1 Units

Top of
Mounting
Channel

3.44
[87]
Omitted on
1 Units

44.71
[1136]

1.75
[44]

2.00
[51]

4.00
[102]

23.88
[607]

31.17
[792]

26.74
[679]

Knockouts
Conduit Size

Hole Diameter

2.00
[51]

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

29.00
[737]

11.12
[283]

33.00
[838]
E, F, G, H, I, J
A, B

3.09
[79]

1.19
[30]

5.40
[137]

1.19
[30]
11.22
[285]

5.40
[137]
EZM11200TBU, EZM31200TBU

in.
Dimensions: [mm]

52
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
12.25
[311]

2.21
[56]

1.56
[40]
Typ.

7.09
[180]

3.75
[95]

Hanging
Mounting Rail

3.44
[87]
Typ.

Omitted on
1 Units
42.37
[1076]

5.20
[132]
Typ.

9.00
[229]
Typ.
11.19
[284]

7.10
[180] 4.79
[122]

C, D, E
1.65
[42]

2.48
[63]4.59
[117]

1.78
[45]

3.00
[76]

31.30
[795]

6.59
[167]
2.21
[56]

7.54
[192]
10.48
[266]
12.12
[308]
8.50
[216]
5.75
[146]

A, B

3.75
[95]

1.56
[40]
Typ.

7.09
[180]

Hanging
Mounting Rail

3.44
[87]
Typ.

2.44
[62]

Omitted on
1 Units
48.12
[1222]

6.59
[167]
1.62
[41] 1.67

12.25
[311]

5.20
[132]
Typ.

9.00
[229]
Typ.

C, D, E

[42]
2.72
[69]
EZM113125 / X / CUX, EZM313125 / X / CUX
EZMR113125 / X / CUX, EZMR313125 / X / CUX
EZMH113125 / X / CUX, EZMH313125 / X / CUX

11.19
[284]

7.10
[180] 4.79
[122]

Knockouts
Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

Symbol

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

C, D, E
1.65
[42]

2.48
[63]

4.59
[117]

Conduit Size

1.78
[45]

31.30
[795]

3.00
[76]

7.54
[192]
10.48
[266]
12.12
[308]
8.50
[216]
5.75
[146]

6.59
[167]

A, B
2.44
[62]
6.59
[167]

1.62
[41] 1.67

C, D, E

[42]
2.72
[69]
EZM114125 / X / CUX, EZM314125 / X / CUX
EZMR114125 / X / CUX, EZMR314125 / X / CUX
EZMH114125 / X / CUX, EZMH314125 / X / CUX

in.
Dimensions: [mm]

53
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
12.25
[311]

2.21
[56]

7.09
[180]

3.75
[95]

3.44
[87]
Typ.

Hanging
Mounting Rail

57.12
[1451]
Omitted on
1 Units

2.21
[56]

5.20
[132]
Typ.

9.00
[229]
Typ.

12.25
[311]

7.09
[180]

3.75
[95]

1.56
[40]
Typ.

31.30
[795]

11.19
[284]

7.10
[180] 4.79
[122]

C, D, E
1.65
[42]

2.48
[63]
4.59
[117]

1.78
[45]

1.56
[40]
Typ.

7.54
[192]
10.48
[266]
12.12
[308]
8.50
[216]
5.75
[146]

3.00
[76]

3.44
[87]
Typ.

6.59
[167]

Hanging
Mounting
Rail

Omitted on
1 Units
66.12
[1679]

A, B

5.20
[132]
Typ.

2.44
[62]
6.59
[167]

1.62
[41] 1.67

11.19
[284]

7.10
[180] 4.79
[122]

C, D, E

[42]
2.72
[69]

EZM115125 / X / CUX, EZM315125 / X / CUX


EZMR115125 / X / CUX, EZMR315125 / X / CUX
EZMH115125 / X / CUX, EZMH315125 / X / CUX

2.48
[63]
4.59
[117]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

Symbol

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

1.78
[45]

40.30
[1024]

9.00
[229]
Typ.

3.00
[76]

C, D, E
1.65
[42]
7.54
[192]
10.48
[266]
12.12
[308]
8.50
[216]
5.75
[146]

6.59
[167]

A, B
2.44
[62]
6.59
[167]

1.62
[41] 1.67
[42]
2.72
[69]

C, D, E

EZM116125 / X / CUX, EZM316125 / X / CUX


EZMR116125 / X / CUX, EZMR316125 / X / CUX
EZMH116125 / X / CUX, EZMH316125 / X / CUX
in.
Dimensions: [mm]

54
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts

17.38
[441]

3.75
[95]
Top Meter
Position
Omitted on
2-Position
Devices
Omitted on
1 Units

3.44
[87]
Typ.

1.56
[40]
Typ.

8.09
[205]

Hanging
Mounting Rail

43.41
[1103]
9.00
[229]
Typ.

2.12
[54]

17.38
[442]

12.23
[311]

6.00
[152]

2.25
[57]

32.34
[821]

8.30
[211]

2.18
[55]
C, D, E, F

5.75
[146]
6.75
[171]
10.50
[267]
15.00
[381]
17.25
[438]
6.59
[167]
A, B

1.56
[40]
Typ.

8.09
[205]

7.50
[190]

3.44
[87]
Typ.

Hanging
Mounting Rail
Omitted on
1 Units
52.00
[1321]

C, D, E, F
7.50
[190]

4.12
[105]

9.00
[229]
Typ.

2.12
[54]

1.93
[49]

1.61
[41]
3.34
[85]

2.25
[57]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

Symbol

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

32.34
[821]

12.23
[311]

6.00
[152]

EZM112225 / X / CUX, EZM312225 / X / CUX


EZM113225 / X / CUX, EZM313225 / X / CUX
EZMR112225 / X / CUX, EZMR312225 / X / CUX
EZMR113225 / X / CUX, EZMR313225 / X / CUX|
EZMH112225 / X / CUX, EZMH312225 / X / CUX
EZMH113225 / X / CUX, EZMH313225 / X / CUX

3.75
[95]

5.30
[211]
5.75
[146]
6.75
[171]
10.50
[267]
15.00
[381]
17.25
[438]
6.59
A, B
[167]

2.18
[55]
C, D, E, F

7.50
[190]

C, D, E, F
7.50
[190]

4.18
[106]
1.61
[41]
3.34
[85]

1.93
[49]

EZM114225 / X / CUX, EZM314225 / X / CUX


EZMR114225 / X / CUX, EZMR314225 / X / CUX
EZMH114225 / X / CUX, EZMH314225 / X / CUX
in.
Dimensions: [mm]

55
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts

8.69
[221]

17.37
[441]

8.09
[208]

1.74
[44]

12.73
[323]
28.59
[728]

3.44
[87]
Typ.

Omitted
on 1
Units 60.94
[1548]

9.00
[229]
Typ.

25.09
[837]
C, D, E, F
Knockouts in
Rear of Box

32.35
[822]

12.21
[310]

7.53
[191]

17.25
[438]

NOTE: Shown with


covers removed.

A, B
2.18
[55]

Top of
Mounting
Channel

2.27
[58]

C, D, E, F

2.35
[60]

1.72
3.32 [44]
[84] 1.66
[42]

1.67
[42]

3.32
[84]

3.33
[85]

EZM115225 / CU, EZM315225 / CU


EZMR115225 / CU, EZMR315225 / CU
EZMH115225 / CU, EZMH315225 / CU

Knockouts
Conduit Size

Hole Diameter

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

in.
Dimensions: [mm]

56
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
19.44
[494]
12.09
[307]

5.50
[140]

9.44
[240]

Top Meter
Position Omitted
on Single
Position Device

3.44
[87] 6.00
Typ. [152]

3.44
[87]
Typ.

12.09
[307]

67.06
[1703]

D, E, F, G

8.83
[224]

14.00
[356]
Typ.

EZML111225 / CU / D, EZML312225 / CU / D
EZML112225 / CU / D, EZML331225 / CU / D
EZMR332225 / CU / D, EZML332225 / CU / D

5.86
[149]
9.65
[245]
13.45
[342]
17.24
[438]

3.44
[87]
Typ.

3.20
[81]

2.07
[53]
3.97
[101]
9.44
[240]

5.50
[140]

Top of
Mounting
Channel

Omitted on
1 Units

3.91
[99]

53.06
[1348]

D, E, F, G

12.09
[307]

5.86
[149]
9.65
[245]
13.45
[342]
17.24
[438]
19.31
[490]

3.20
[81]

39.50
[1003]

2.00
[51]
3.79
[96]

D, E, F, G

A, B
8.83
[224]
2.24
[57]

12.09
[307]

D, E, F, G

Knockouts
Conduit Size
8.83
[224]

5.86
[149]
9.65
[245]
13.45
[342]
17.24
[438]
EZML113225 / CU / D, EZML313225 / CU / D
EZMR333225 / CU, EZML333225 / CU / D
(See Typical Bottom View)

in.
Dimensions: [mm]

Typical Bottom View

13.34
[339]

6.62
[168]

8.83
[224]

EZML114225 / CU / D, EZML314225 / CU / D
EZMR334225 / CU, EZML334225 / CU / D

4.60
[117]
14.00
[356]
Typ.

39.50
[1003]

13.34
[339]

6.62
[168]

(See Typical Bottom View)


19.44
[494]
12.09
[307]

Top of
Mounting
Channel

Omitted on
1 Units

13.34
[339]

6.62
[168]

2.07
[53]
3.97
[101]

9.44
[240]

39.06
[992]
25.50
[648]

3.20
[81]

5.50
[140]

Top of
Mounting
Channel

Omitted on
1 Units
13.99
[355]

2.07
[53]
3.97
[101]

19.44
[494]
12.09
[307]

Hole Diameter

Symbol
in.

[mm]

in.

[mm]

0.50

13

0.88

22

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

3.00

76

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

57
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
22.42
[570]

22.42
[570]

18.31
[465]
9.16
[233]

C, D, E, F,G, H
Knockouts in
Rear of Box

2.06
[52]

9.38
[238]
1.68
[43]

3.44
[87]
Typ.

25.12
[638]

Omitted on
1 Units

18.31
[465]
9.16
[233]

0.38
[10]
Top of
Mounting
Channel

2.06
[52]

1.68
[43]

9.38
[238]

8.80
[224]

3.44
[87]
16.19 Typ.
[411]

20.45
[519]

0.38
[10]

Top of
Mounting
Channel

8.97
[228]

19.00
[483]

2.77
[70]

5.15
[131]

7.25
[184]

22.31
[567]

1.81
[46]

C, D, E, F, G, H

A, B

8.94
[227]

C, D, E,
F,G, H
Knockouts
in Rear of
Box

60.56
[570]
43.63
[1108]

28.89
[734]

2.30
[58]
1.00
[25]

36.40
[925]

3.09
[79]

5.78
[147]

4.27
[108]
8.44
[214]

EZMT111225, EZMT311225, EZMT331225


4.31
[110]
C, D, E, F, G, H

A, B

2.36
[60]
2.41
[61]

2.41
[61]

4.27
[108]

22.42
[570]

18.31
[465]
9.16
[233]

2.47
[63]

2.06
[52]

9.38
[238]

0.38
[10]

19.00
[483]

3.44
[87]
Typ.

79.56
[2021]

Omitted on
1 Units

19.00
[483]

Knockouts
Conduit Size

Hole Diameter

in.

[mm]

in.

[mm]

0.50

13

0.88

22

Symbol

0.75

19

1.25

32

1.00

25

1.38

35

1.25

32

1.75

44

1.50

38

2.00

51

2.00

51

2.50

64

2.50

64

3.00

76

76

8.94
[227]

8.80
[224]

Typical endwall for 2 and 3 positions.

1.80
[46]

EZMT112225, EZMT312225, EZMT332225


1.40
[36]

4.27
[108]

22.31
[567]

3.00

3.63

92

3.50

89

4.13

105

4.00

102

4.63

118

41.03
[1042]
C, D, E,
F,G, H
Knockouts
in Rear of
Box
4.31
[110]
2.41
[61]

4.27
[108]
Typ.

48.25
[1226]
28.89
[734]
8.44
[214]
1.81
[46]

8.94
[227]
22.31
[567]
EZMT113225, EZMT313225, EZMT333225
in.
Dimensions: [mm]
7.25
[184]

58
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Dimensions and Knockouts
23.21
[590]
12.09
[307]

3.44
[87]
(Typ.)

5.50
[140]

23.21
[590]
12.09
[307]

9.44
[590]
Top of
Mounting
Channel

Omitted on
1 Units

5.50
[140]

9.44
[240]

14.58
[370]

45.55
[1157]
37.81
[960]

Top of
Mounting
Channel

3.44
[87]
(Typ.)
27.44 69.61
[697] [1768]

21.53
[547]

16.60
[422]

Omitted on
1 Units

37.81
[960]

10.11
[257]
EZML111400, EZML311400, EZML331400
27.56
[700]

15.68
[398]
11.12
[282]

21.53
[547]

16.60
[422]

5.82
[148]
1.68
[43]

9.74
[247]

0.34
[9]
Top of
Mounting
Channel

Omitted on
1 Units
3.44
[87]
Typ.

10.11
[257]
EZML112400, EZML312400, EZML332400
27.56
[700]

45.55
[1157]

37.81
[960]

30.58
[777]

15.68
[398]
11.12
[282]

21.04
[534]

27.48
[698]

1.80
[46]

EZMK111400, EZMK311400, EZMK331400

5.82
[148]

1.68
[43]

9.74
[247]

0.34
[9]

7.59
[193]

72.99
[1854]

9.23
[235]
3.44
[87]
Typ.

Top of
Mounting
Channel

29.69
[754]
Omitted on
1 Units

37.81
[960]

30.58
[777]

21.04
[534]

27.44
[697]

1.80
[46]

9.23
[235]

EZMK112400, EZMK312400, EZMK332400


NOTE: No knockouts provided on EZMK and
400 A EZML devices.

in.
Dimensions: [mm]

59
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Dimensions and Knockouts

1.71
[43]

14.40
[366]
8.02
[204]

1.80
[46]

14.40
[366]

11.66
[296]

Omitted on
1 Units

6.37
[162]

19.34
[491]

1.74
[44]

7.20
[183]

5.87
[149]

11.50
[292]
19.50
[495]

Omitted on
1 Units

EZM1EXT
EZM3EXT

1.69
[43]

EZM1CORNER
EZM3CORNER
NEMA Type 1
(Indoor Only)

1.71
[43]

8.07
[205]

6.00
[152]

Omitted on
1 Units

6.37
[162]

19.34
[491]

1.74
[44]

6.51
[165]

8.06
[205]

6.48
[165]

11.50
[292]

5.87
[149]
EZM1EXT6
EZM3EXT6

1.80
[46]

Omitted on
1 Units

1.67
[42]

0.34
[9]
EZM1ELBOW
EZM3ELBOW

in.
Dimensions: [mm]

60
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

Wiring Diagrams

Load

Load
N

Circuit
Breaker

Omitted on 400 A Device


Main Bonding Jumper
(when required)

Load

Load

C
N

Ground
(when
required)

Line

Main Bonding Strap


(when required)

EZM1400CB, EZM1600CB, EZM1800CB, EZM11000CB

Circuit
Breaker

Ground (when required)


Line
EZM12000CB

A
Load B
C
N

Load
Omitted on 400 A Device
Main Bonding Jumper
(when required)

Circuit
Breaker
N
A

Load

Ground
(when
required)

Line

A
B

Load

C
N

Main Bonding Strap


(when required)

EZM3400CB, EZM3600CB, EZM3800CB, EZM31000CB


Circuit
Breaker

Ground (when required)


A

Line
Load

Load

EZM32000CB

Omitted on 1200 A Device


Main Bonding Jumper
(when required)

Circuit
Breaker

Omitted
on 1200 A
Device

Ground
(when
required)

Line

Load

Load
N

Use 300 V
Class T Fuses
(order separately)

EZM11200CB, EZM11600CB,

Molded Case
Switch
A

Line

Load B

Omitted on 400 A Device


Main Bonding Jumper
(when required)

Ground
(when
required)

Load

C
N

EZM1400FS, EZM1600FS, EZM1800FS


Omitted on 1200 A Device
Main Bonding Jumper
(when required)

Circuit
Breaker
N

Omitted
on 1200 A
Device

Ground
(when
required)

Line

EZM31200CB, EZM31600CB

61
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams

Load B

Load

C
N

Use 300 V
Class T Fuses
(order separately)

Omitted on 400 A Device


Main Bonding
Jumper (when
required)

Molded Case
Switch
A

Ground
(when
required)

Line

EZM3400FS, EZM3600FS, EZM3800FS

Omitted on 400 A
and 600 A Devices

Main Bonding
Jumper (when
required)

Ground
(when
required)
Load

Load
N

Use 300 V
Class T Fuses
(order separately)

Molded Case
Switch

EZM1400TB, EZM1600TB,
EZM1800TB, EZM1800TBCU

Main Bonding
Jumper (when
required)

Ground
(when
required)
A
B
C
N

Line
EZM11200FS

Main Bonding
Jumper (when
required)

Omitted on 400 A
and 600 A Devices
A

Ground
(when
required)
N

EZM3400TB, EZM3600TB, EZM3800TB


N

Ground
(when
required)
EZM1225TB
N

Main Bonding
Jumper (when
required)
N

A
B
C
N

Ground
(when
required)
EZM11600TB
A

Ground
(when
required)
EZM3225TB

62
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

A
B
C
N

Main Bonding
Jumper (when
required)

Ground
(when
required)

Load

Load
N

EZM31600TB

Circuit
Breaker

Load

Load

Line

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Circuit
Breaker

Line

Service
Grounding Lugs
(when required)

A
B
Load C
N

Load

Load B

Load

Circuit
Breaker

Line

EZM1600CBU, EZM1800CBU

Circuit
Breaker

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Service
Grounding Lugs
(when required)

EZM1400CBU

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Service
Grounding Lugs
(when required)

Line

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Service
Grounding Lugs
(when required)

EZM3600CBU, EZM3800CBU

EZM3400CBU

63
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams

Load

Load
N

Circuit
Breaker

Line

Load

Load A
B

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Service
Grounding Lugs
(when required)

N
A

Line

EZM11000CBU, EZM11200CBU

A
B
Load C
N

Main Bonding Strap


(when required)

Circuit
Breaker

Ground
(when required)

EZM31600CBU, EZM32000CBU

Load
Load

Circuit
Breaker

Line

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
C
required)

Service
Grounding Lugs
(when required)

Load
N

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Use 300 V
Class T Fuses
(order separately)
Molded Case
Switch

Service
Grounding Lugs
(when required)

Line
EZM31000CBU, EZM31200CBU

EZM1400FSU

A
B
C
Load
N

Load

Load

Main Bonding Strap


(when required)

Circuit
Breaker
N

Ground
(when required)

Load
Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Use 300 V
Class T Fuses
(order separately)
Molded Case
Switch

Service
Grounding Lugs
(when required)

Line
EZM11600CBU, EZM12000CBU

EZM3400FSU

64
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

Load

Load
N

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Use 300 V
Class T Fuses
(order separately)
Molded Case
Switch

Service
Grounding Lugs
(when required)

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Line
N

Line
EZM1600FSU, EZM1800FSU
A
B
Load C
N

Load
Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Use 300 V
Class T Fuses
(order separately)
Molded Case
Switch

Tenant
Circuit Breaker
125 A Max.

Service
Grounding Lugs
(when required)

Neutral and
Service Ground N

Equipment
Grounding

EZM113125 / X / CUX
EZMR113125 / X / CUX
EZMH113125 / X / CUX

Line
EZM3600FSU, EZM3800FSU

Load

Load
N

Use 300 V
Class T Fuses
(order separately)
Molded Case
Switch

Line

Neutral
Disconnect
Link
Box
Bonding
(when
required)
Ground
(when
required)

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A
B
C
N

Service
Grounding Lugs
(when required)

B C

EZM11200FSU
Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Tenant
Circuit Breaker
125 A Max.

Box Bonding
(when required)
Equipment
Grounding
N Terminal

Neutral and
Service Ground N

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, and AC,
top to bottom.

Equipment
Grounding
EZM313125 / X / CUX
EZMR313125 / X / CUX
EZMH313125 / X / CUX

EZM1400TBU, EZM1800TBU, EZM11200TBU, EZM12000TB


A
B
C
N

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)
Box Bonding
(when required)
A

Equipment
Grounding
Terminal

EZM3400TBU, EZM3800TBU, EZM31200TBU, EZM32000TB

65
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Line
N

Tenant
Circuit Breaker
125 A Max.

A
B
C
Line
N

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)
A

Equipment
Grounding

Neutral

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, AC, and
AC, top to bottom.

Tenant
Circuit Breaker
125 A Max.

Neutral

Equipment
Grounding

EZM314125 / X / CUX
EZMR314125 / X / CUX
EZMH314125 / X / CUX

EZM114125 / X / CUX
EZMR114125 / X / CUX
EZMH114125 / X / CUX

Tenant
Circuit Breaker
125 A Max.

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Line
N

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Line B

C
N

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, AC, AB
and BC, top to bottom.

Tenant
Circuit Breaker
125 A Max.

Neutral

B C

Equipment
Grounding

EZM115125 / X / CUX
EZMR115125 / X / CUX
EZMH115125 / X / CUX

Neutral
N

Equipment
Grounding

EZM315125 / X / CUX
EZMR315125 / X / CUX
EZMH315125 / X / CUX

66
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

B C

Tenant
Circuit Breaker
125 A Max.

Tenant
Circuit Breaker
125 A Max.

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A
B
C
N

Neutral
N

Equipment
Grounding

EZM112225 / X / CUX
EZMR112225 / X / CUX
EZMH112225 / X / CUX

A B C

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, AC, AB,
BC and AC, top to bottom.

Equipment
Grounding

Neutral
N

Neutral
N

Equipment
Grounding

EZM316125 / X / CUX
EZMR316125 / X / CUX
EZMH316125 / X / CUX

EZM116125 / X / CUX
EZMR116125 / X / CUX
EZMH116125 / X / CUX

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.

Torque to
50 lb-ft.
(600 lb-in. A B C
or 68 Nm)

A
B
C
N

Tenant
Circuit Breaker
225 A Max.

Equipment
Grounding

Neutral

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB and BC, top
to bottom.

Neutral
N

Equipment
Grounding

EZM312225 / X / CUX
EZMR312225 / X / CUX
EZMH312225 / X / CUX

EZM113225 / X / CUX
EZMR113225 / X / CUX
EZMH113225 / X / CUX

67
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams
A

A B

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A
B
Line C
N

A B

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A
B
C
Line
N

Tenant
Circuit Breaker
225 A Max.

Tenant
Circuit Breaker
225 A Max.

A B C

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, and AC,
top to bottom.

Neutral
N

Equipment
Grounding
Neutral

EZM313225 / X / CUX
EZMR313225 / X / CUX
EZMH313225 / X / CUX

Equipment
Grounding
EZM314225 / X / CUX
EZMR314225 / X / CUX
EZMH314225 / X / CUX

Each socket line connector may be


moved to balance loading. Phase
AC, BC, or AB. This device leaves
the factory phased AB, BC, AC and
AC, top to bottom.

A B C

Tenant
Circuit Breaker
225 A Max.

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.

B C

Tenant
Circuit Breaker
225 A Max.

Each socket line


connector may be
moved to balance
loading. Phase AC, BC,
or AB. This device
leavesthe factory
phased AB, BC, AC, AB
and BC, top to bottom.

N
A

Line

B
C
N

Neutral

Equipment
Grounding

EZM114225 / X / CUX
EZMR114225 / X / CUX
EZMH114225 / X / CUX

Neutral

Equipment
Grounding

EZM115225 / CU
EZMR115225 / CU
EZMH115225 / CU
Neutral

Equipment
Grounding

EZM315225 / CU
EZMR315225 / CU
EZMH315225 / CU

68
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams
A B

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line

N
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line
N

Tenant
Circuit Breaker
225 A Max.

Tenant
Circuit Breaker
225 A Max.

Line

A B

Neutral

EZML112225 / CU / D
A

Equipment
Grounding
EZML312225 / CU / D

C B

High Leg
(Power Leg)
for 34W Delta
System
Torque to
50 lb-ft. Line
(600 lb-in.
or 68 Nm)

Line B
C
N

Tenant
Circuit Breaker
225 A Max.
High Leg
(Power Leg)
for 34W
Delta System

Equipment
Grounding
Neutral

A
B
C
N

A BC

B
C
N

High Leg
(Power Leg)
for 34W
Delta System

Tenant

Neutral

High Leg
(Power Leg) for
34W Delta
System (All
Tenant Circuit
Breaker
Positions)

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line

High Leg
(Power Leg)
for 34W
Delta System

High Leg (Power Leg)


Torque to
for 34W Delta System
50 lb-ft.
(All Tenant Circuit
(600 lb-in.
Breaker Positions)
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.

EZML331225 / CU / D
A

A B

A BC

Each socket line connector


may be moved to balance
loading. Phase AC, BC, or
AB. This device leaves the
factory phased AB and
BC,top to bottom.

EZML111225 / CU / D
Equipment
Grounding

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A
B
C
N

Tenant
Equipment Circuit Breaker
225 A Max.
Grounding

Neutral

Neutral

High Leg
(Power Leg)
for 34W
Delta System

Each socket line Circuit Breaker


225 A Max.
connector may be
moved to balance
loading. Phase AC,
BC, or AB. This device
leaves the factory
phased AB, BC, and
Equipment AC, top to bottom.

Grounding
EZML313225 / CU / D

A BC

Equipment
Grounding
Neutral

EZML33225 / CU / D
EZML33225 / CU
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A BC

Line

B
C
N

High Leg
(Power Leg)
for 34W
Delta System

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.
A BC

Tenant
Circuit Breaker
225 A Max.
A BC

Neutral

Equipment
Grounding

EZML333225 / CU / D
EZMR333225 / CU

Neutral
Equipment
Grounding
EZML113225 / CU / D

69
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams
A

Tenant
Circuit Breaker
225 A Max.
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line
N

Line B

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

C
N

Tenant
Circuit Breaker
225 A Max.
Each socket line connector may be
moved to balance loading. Phase AC,
BC, or AB. This device leaves the factory
phased AB, BC, and AC, top to bottom.

Neutral
Equipment
Grounding

Neutral

Equipment
Grounding

EZML314225 / CU / D

EZML114225 / CU / D
A

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

Line
N

High Leg (Power


Leg) for 34W
Delta System (All
Tenant Circuit
Breaker
Positions)

A
Line B
C
N

Equipment
Grounding
Terminal

High Leg
(Power Leg)
for 34W
Delta System

A BC

Tenant
Circuit Breaker
225 A Max.
Service Grounding Lugs
when Required
Neutral Terminals

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A BC

Box Bonding
(when required)
EZMT111225

High Leg
(Power Leg)
for 34W
Delta System

Line

A
B
C
N

Tenant
Circuit Breaker
225 A Max.

A BC

Service Grounding Lugs


when Required
A BC

Equipment
Grounding
Neutral

NOTE: This device is shipped with


line side meter socket bus
connectors phased A and C.
These connectors may be moved
to balance loading for B and C, or
for A and B phasing in the field.

Equipment
Grounding
Terminal

Tenant
Circuit Breaker
225 A Max.

Each socket line


connector may be moved
to balance loading. Phase
AC, BC, or AB. This
device leaves the factory
phased AC.

Neutral Terminals
Box Bonding
(when required)

EZML334225 / CU / D
EZMR334225 / CU

EZMT311225

70
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

A C

Line

High Leg
(Power Leg)
for 34W
Delta System

A B

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A
B
C
N

A B

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A
B
Line
C
N

High Leg
(Power Leg)
for 34W
Delta System

A BC

Tenant
Circuit Breaker
400 A Max.

Tenant
Circuit Breaker
400 A Max.

Neutral

Equipment
Grounding

High Leg
(Power Leg)
for 34W
Delta System

Each socket line connector


may be moved to balance
loading. Phase AC, BC, or
AB. This device leaves the
factory phased AC.

EZML311400

Equipment
Grounding

Neutral
N
EZML331400

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line
High Leg
(Power Leg)
for 34W
Delta System

N
A

Line

A
B
C
N

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)
Line
High Leg
(Power Leg)
for 34W
Delta System

Equipment Grounding
Terminal

L
I
N
E

High Leg
(Power Leg)
for 34W
Delta System

L
O
A
D

Service Ground Lugs A B C


(when required)

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

High Leg
(Power Leg)
for 34W
Delta System

Tenant
Circuit Breaker
225 A Max.

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

Box Bonding
(when required)
Service Ground Lugs
(when required)
Neutral
Disconnect Link

Neutral Terminals

Neutral Terminal
Box Bonding
(when required)

L
I
N
E

EZMT331225

L
O
A
D

Equipment Grounding
Terminal
EZMT112225

71
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams

B C

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

A
B
C
N
B

A
N

Each socket line connector may


be moved to balance loading.
Phase AC, BC, or AB. This
device leaves the factory phased
AB and BC top to bottom.

L
I
N
E

Tenant
Circuit Breaker
225 A Max.

L
O
A
D

L
I
N
E

L
O
A
D

Box Bonding
(when required)
Service Ground Lugs
(when required)

B
N

Neutral
Disconnect Link
Neutral Terminals
L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

Equipment Grounding
Terminal
EZMT312225

High Leg (Power


Leg) for 34W
Delta System

Line

Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A
B
C
N

High Leg (Power Leg) for


34W Delta System (All
Meter Positions)

A
C

High Leg (Power Leg) for 34W


Delta System (All Tenant Circuit
Breaker Positions)

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

L
O
A
D

L
I
N
E

High Leg (Power Leg)


for 34W Delta System

A B C

Box Bonding (when required)


Service Ground Lugs (when required)

A
C

Neutral Disconnect Link


Neutral Terminals

N
L
I
N
E

Tenant
Circuit Breaker
225 A Max.

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

A B C

Equipment Grounding Terminal


EZMT332225

72
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams
N
B

L
I
N
E

L
I
N
E

L
O
A
D

A
N

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

A B

Line

Line
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Tenant
Circuit Breaker
225 A Max.
Box Bonding
(when required)

L
I
N
E

L
I
N
E

L
O
A
D

L
I
N
E

L
I
N
E

L
O
A
D

Line
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

L
O
A
D

Box Bonding
B C
(when required)

Service Grounding Lugs


(when required)
Neutral Disconnect Link

B
N

Tenant
Circuit Breaker
225 A Max.

L
O
A
D

B
C
N

Each socket line connector


may be moved to balance
loading. Phase AC, BC or
AB. This device leaves the
factory phased AB, BC and
AC top to bottom.

N
N

Line A

Service Grounding Lugs


(when required)
Neutral Disconnect Link

Neutral Terminals

A
N

Neutral Terminals

L
I
N
E

L
I
N
E

L
O
A
D

L
O
A
D

A
C

Equipment Grounding Terminal

L
I
N
E

High Leg (Power Leg)


for 34W Delta System
(All Meter Positions)

EZMT113225
High Leg (Power Leg) for 34W Delta System
(All Tenant Circuit Breaker Positions)

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

A C

N
L
I
N
E

L
O
A
D

Equipment Grounding Terminal


EZMT313225

Tenant Circuit Breaker


225 A Max.
High Leg (Power Leg)
for 34W Delta System

A B C
A
B
Line C
N

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Line
N

N
L
I
N
E

Box Bonding (when required)

Line
Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

L
O
A
D

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

Equipment
Grounding

Tenant
Circuit
Breaker
400 A
Max.

High Leg (Power Leg)


for 34W Delta System

A B C
B

Service Grounding Lugs (when required)

Neutral Disconnect Link

Neutral

EZML111400
N

Neutral Terminals

L
I
N
E

L
O
A
D

Tenant Circuit Breaker


225 A Max.

L
I
N
E

L
O
A
D

L
I
N
E

L
O
A
D

Equipment Grounding Terminal


A B C

EZMT333225

73
07/2008

2008 Schneider Electric All Rights Reserved

EZ Meter-Pak Meter Centers


Wiring Diagrams
High Leg (Power Leg)
for 34W Delta System

A
B
C
N

Neutral

Line

Line

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)
Line

High Leg (Power Leg)


for 34W Delta System

B
A

Tenant Circuit
Breaker 400 A Max.

Equipment Grounding
Terminal

K-7 Bolt-On
Meter Socket

Line

High Leg (Power Leg)


for 34W Delta System

Tenant Circuit
Breaker 400 A Max.

EZMK331400
Torque to 50 lb-ft.
(600 lb-in. or 68 Nm)

A
B
Line C
N
Neutral

Tenant Circuit
Breaker 400 A Max.
Neutral

Line
C

Equipment Grounding Terminal

Each socket line connector may be


moved to balance loading. Phase AC,
BC, or AB. (B phase line connector is
provided). This device leaves the
factory phased AC.

EZML112400

Tenant Circuit
Breaker 400 A Max.
K-5 Bolt-On
Meter Socket

Line

Line

Neutral

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)

EZMK311400
A

Equipment Grounding
Terminal
Tenant Circuit
Breaker 400 A Max.

Tenant Circuit
Breaker 400 A Max.

K-4 Bolt-On
Meter Socket

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)
Line

A
B

EZMK111400

Line C
N
B
A

Neutral

Each meter socket line connector


may be moved to balance
loading. Phasing may be
connected AC, BC, or AB. This
device leaves the factory phased
AB and BC top to bottom.

Equipment Grounding
Terminal
Tenant Circuit
Breaker 400 A Max.
Tenant Circuit
Breaker 400 A Max.

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)
Line

Line
N

K-5 Bolt-On
Meter Socket

EZMK312400
A

High Leg (Power Leg)


for 34W Delta System
(Both Tenant Circuit
Breaker Positions)

High Leg (Power Leg)


for 34W Delta System
(Both Tenant Circuit
Breaker Positions)

A B C

Neutral

Tenant Circuit Breaker


400 A Max.

Equipment Grounding
Terminal
Tenant Circuit
Breaker 400 A Max.

High Leg (Power Leg)


for 34W Delta System
K-4 Bolt-On
Meter Socket

EZMK112400

Torque to
50 lb-ft.
(600 lb-in.
or 68 Nm)
Line

A
B
C
Line N
C
A

Neutral

Equipment Grounding
Terminal
A B C
Tenant Circuit
Breaker 400 A Max.
K-7 Bolt-On
Meter Socket
EZMK332400

74
2008 Schneider Electric All Rights Reserved

07/2008

EZ Meter-Pak Meter Centers


Wiring Diagrams

75
07/2008

2008 Schneider Electric All Rights Reserved

Schneider Electric USA


1601 Mercer Road
Lexington, KY 40511 USA
1-888-Square D
1-888-778-2733
www.us.SquareD.com

Square D, EZ Meter-Pak, Visi-Tite, and QO are trademarks or registered trademarks of Schneider


Electric and/or its affiliates in the United States and/or other countries. Other marks used herein
are the property of their respective owners.