You are on page 1of 48

Logix Add-On Instructions and Graphics:

Controller CPU Utilization (L_CPU)

Compatible with the Plant-wide Integrated Architecture


Reference Manual

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office
or online at http://rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired
electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application
of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in
this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING

IMPORTANT
ATTENTION

Identifies information about practices or circumstances that can cause an explosion in a


hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.

Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence.

SHOCK HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.

Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation, Plant PAx Process Automation System, and TechConnect are property of their respective companies.

Summary of Changes

Introduction

This release of this document is updated throughout for version 2.0 of the
Logix CPU Utilization (L_CPU) Add-On Instruction and Graphics. Please
refer to the Release Notes that are distributed with version 2.0 of the Library.

Updated Information

This document contains the following changes:

iiiPublication SYSLIB-RM017C-EN-E - October 2011

Change:

See:

Version 2.0 of instruction

All

iii

Summary of Changes

Notes:

iv

Publication SYSLIB-RM017C-EN-E - October 2011

Table of Contents
Preface

Use of this Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii


Conventions and Related Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Set and Clear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Edge and Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Relay Ladder Rung Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Pre-Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Function Block States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Entering Text in FactoryTalk View SE . . . . . . . . . . . . . . . . . . . . . . . . . xii

Chapter 1
Overview

Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Primary Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Revision Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Chapter 2
Configuration Options

Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 3
Instruction Data Reference

Publication SYSLIB-RM017C-EN-E - October 2011

L_CPU_Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configurations (Cfg_). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Commands, Maintenance Commands, Command Readies
(OCmd, MCmd_, Rdy_) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status (Sts_) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11
17
18
19
19
19
21
21

Table of Contents

Chapter 4
HMI Reference

vi

Graphic Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Graphic Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Faceplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPU Usage Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Logix CPU Faceplate Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23
24
25
25
27
28
29
30
31
33

Publication SYSLIB-RM017C-EN-E - October 2011

Preface

Use of this Document

This document provides a programmer with details on the L_CPU instruction


for a Logix-based controller. You should already be familiar with how the
Logix-based controller stores and processes data.
Novice programmers should read all the details about an instruction before
using the instruction. Experienced programmers can refer to the instruction
information to verify details.

Conventions and Related


Terms

Set and Clear


This manual uses set and clear to define the status of bits (booleans) and values
(non-booleans):

viiPublication SYSLIB-RM017C-EN-E - October 2011

This term:

Means:

Set

The bit is set to 1 (ON)


A value is set to any non-zero number

Clear

The bit is cleared to 0 (OFF)


All the bits in a value are cleared to 0

vii

Preface

Edge and Level


This manual uses Edge and Level to describe how bit (BOOL) Commands,
Settings, Configurations, and Inputs to this instruction are sent by other logic
and processed by this instruction.
Send/Receive Method: Description:
Edge

Action is triggered by rising edge transition of input (0-1)


Separate inputs are provided for complementary functions
(such as enable and disable)
Sending logic SETS the bit (writes a 1) to initiate the
action; this instruction CLEARS the bit (to 0) immediately,
then acts on the request, if possible
Ladder Diagram (LD): use conditioned OTL (Latch) to send
Structured Text (ST): use conditional assignment [if
(condition) then bit:=1;] to send
Function Block Diagram (FBD): OREF writes a 1 or 0 every
scan, should use Level, not Edge
Edge-triggering allows multiple senders per Command,
Setting, Configuration, or Input (many-to-one relationship).

Level

Action (enable) is triggered by input being at a level (in a


state, usually 1)
Opposite action (disable) is triggered by input being in
opposite state (0)
Sending logic SETS the bit (writes a 1) or CLEARS the bit
(writes a 0); this instruction does not change the bit
LD: use OTE (Energize) to send
ST: use unconditional assignment
[bit:= expression_resulting_in_1_or_0;] or
if-then-else logic [if (condition) then bit:= 1; else bit:= 0;]
FBD: use OREF to the input bit
Level triggering allows only one sender to drive each Level
input on the instruction (one-to-one relationship restriction).

IMPORTANT

viii

All Operator Commands (OCmd_) and Maintenance Commands


(MCmd_) are Edge triggered. The HMI Graphic Symbol or
Faceplate SETS (writes a 1 to) each Command bit and the
Instruction CLEARS (writes a 0 to) the Command bit, then
performs the function, if possible.

Publication SYSLIB-RM017C-EN-E - October 2011

Preface

IMPORTANT

This instruction has Program Commands (PCmd_) which are


selectable as Edge or Level, depending on the Configuration
Parameter Cfg_PCmdClear. If Cfg_PCmdClear is 1 (the default),
all Program Commands are CLEARED when received (edge). If
Cfg_PCmdClear is 0, Program Commands as noted in the
Instruction Data Reference become Level triggered, and
opposite functions are triggered by the primary Program
Command being CLEARED to 0.

Relay Ladder Rung Condition


The controller evaluates ladder instructions based on the rung condition
preceding the instruction (rung-in condition). Based on the rung-in condition
and the instruction, the controller sets the rung condition following the
instruction (rung-out condition), which in turn, affects any subsequent
instruction.

If the rung-in condition to an input instruction is true, the controller evaluates


the instruction and sets the rung-out condition based on the results of the
instruction. If the instruction evaluates to true, the rung-out condition is true;
if the instruction evaluates to false, the rung-out condition is false.
IMPORTANT

The rung-in condition is reflected in the EnableIn parameter and


determines how the system performs each Process Add-On
Instruction. If the EnableIn signal is TRUE, the system performs
the instructions main logic routine. Conversely, if the EnableIn
signal is FALSE, the system performs the instructions
EnableInFalse routine.
The instructions main logic routine sets/clears the EnableOut
parameter, which then determines the rung-out condition. The
EnableInFalse routine cannot set the EnableOut parameter. If
the rung-in condition is FALSE, then the EnableOut parameter
and the rung-out condition will also be FALSE.

Publication SYSLIB-RM017C-EN-E - October 2011

ix

Preface

Pre-Scan
During the transition into RUN, the controller performs a Pre-scan before the
first logic scan. Pre-scan is a special scan of all routines in the controller. The
controller scans all main routines and subroutines during Pre-scan, but ignores
jumps that could skip the execution of instructions. The controller executes all
FOR loops and subroutine calls. If a subroutine is called more than once, it is
executed each time it is called. The controller uses Pre-scan instructions to
reset non-retentive data values.
During Pre-scan, input values are not current and outputs are not written. The
following conditions generate Pre-scan:
toggle from Program to Run mode.
automatically enter Run mode from a power-up condition.
Pre-scan does not occur for a program when:
the program becomes scheduled while the controller is running.
the program is unscheduled when the controller enters Run mode.
IMPORTANT

The Pre-scan process performs the Process Add-On Instructions


logic routine as all FALSE and then performs its Pre-scan
routine as TRUE.

Publication SYSLIB-RM017C-EN-E - October 2011

Preface

Function Block States


The controller evaluates function block instructions based on the state of
different conditions.
Possible Condition:

Description:

Pre-scan

Pre-scan for function block routines is the same as for relay


ladder routines. The only difference is that the Enableln
parameter for each function block instruction is cleared during
Pre-scan.

Instruction first scan

Instruction first scan refers to the first time an instruction is


executed after Pre-scan. The controller uses instruction first
scan to read current inputs and determine the appropriate
state to be in.

Instruction first run

Instruction first run refers to the first time the instruction


executes with a new instance of a data structure. The
controller uses instruction first run to generate coefficients
and other data stores that do not change for a function block
after initial download.

Every function block instruction also includes EnableIn and EnableOut


parameters.
If the EnableIn parameter is not wired, the instruction always executes as
normal and EnableIn remains set. If you clear EnableIn, it changes to set the
next time the instruction executes.
IMPORTANT

Publication SYSLIB-RM017C-EN-E - October 2011

When programming in function block, restrict the range


of engineering units to 1015 because internal floating
point calculations are done using single precision floating
point. Engineering units outside of this range may result in
a loss of accuracy if results approach the limitations of
single precision floating point (1038).

xi

Preface

Entering Text in FactoryTalk View SE


When entering data into String Input fields in FactoryTalk View SE, the data is
not saved to the tag until the user presses the Enter key. When the Input Field
is enabled, its border changes based on the state of the input:
When the Input Field is Active (the cursor is in the field), the Input Field border is a
solid line.

EXAMPLE

If the user modifies the data in the Input Field and moves to a different field without
pressing the Enter key, the border remains a solid line indicating that the data has not
been saved to the tag.

EXAMPLE

If the data in the Input Field has not changed or has been written to the controller
tag, the border is a dashed line.

EXAMPLE

xii

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter

Overview

The L_CPU (Logix Controller CPU Utilization) Add-On Instruction monitors


the Logix controller executing it and provides information on controller CPU
utilization, communication usage, memory usage, task scan times and other
information. The data provided by the L_CPU Instruction can be useful in
diagnosing communication or control responsiveness issues or in tuning the
performance of control Tasks for optimum controller performance.
The L_CPU Instruction can be loaded as part of a control application and left
disabled (the default) until needed. Or it can be enabled at a slow update rate
for general controller monitoring. The instruction can be enabled or the
update rate can be quickened if necessary as directed by a Rockwell
Automation Technical Support specialist to aid in diagnosing controller
performance issues.
The L_CPU Instruction includes Graphic Symbols and a Faceplate display to
use in building your human-machine interface (HMI).
Use when:
You want to monitor general controller resource utilization: processor
utilization, task performance, task scan time, memory usage,
communication capacity, networking performance or connection usage
on a Logix controller.
You need to gather data as directed by a Rockwell Automation Technical
Support specialist to aid in resolving a specific issue.
You want to tune the periods or priorities of multiple Tasks in your
controller to optimize control and you want to see how changes in Task
configuration affect CPU and other resource usage in the controller.
Do NOT use:
At a high update rate on a continuing basis. The L_CPU Instruction
increases the communication load on the controller when it is polling
for performance data. At high update rates, the resource load generated
by the L_CPU Instruction polling can impact control performance,
especially if you already have a fully-loaded controller.

1Publication SYSLIB-RM017C-EN-E - October 2011

Chapter 1

Overview

Functional Description

The L_CPU instruction collects and summarizes a variety of data from the
Logix controller it is monitoring, including:
Processor Identity information
Catalog Number and Description
Major and Minor firmware revision numbers
Communication Responsiveness information
CPU% available for responding to communications requests
CPU% used for responding to communications requests
Optimized Packets used for responding to communications requests
Memory Usage (total and for each of several classes of memory)
Total memory size
Memory used
Memory available
Largest contiguous block of available memory
Scan Times (for a selected Task)
Maximum scan time
Most recent scan time
CPU Utilization (%) for:
The Continuous Task (or unused CPU, if no Continuous Task)
Periodic and Event Tasks
Motion/Synchronization
Safety Tasks
Redundancy
Sending Messages (MSG)
Responding to communications requests (such as from HMI)
System (I/O scan, timer updates, everything else)
Communication Connection usage:
Total connections available
Connections used for each of several classes of communication
Unconnected Buffers and Cached Messages
I/O Forcing status
Controller Minor Faults
Communication Timeslice setting

Publication SYSLIB-RM017C-EN-E - October 2011

Overview

Chapter 1

These items are displayed on several Faceplate tabs, with summary


information on the main (home) tab.
TIP
It's a good idea to call up the L_CPU Faceplate when you call Rockwell
Automation Technical Support. The information on the Operator (home) tab is
often asked for up front by the Technical Support specialist when you call. You'll
also likely need your RSLogix 5000 software serial number or other license or
support contract information. The Maintenance tab of the Faceplate has a space
for you to record this information for reference.

Primary Operations

The instruction sets up a monitoring window over which CPU utilization


metrics are collected. For example, if the window time is 1.0 second, the CPU
utilization number will show what percentage of CPU was used for each
purpose (continuous task scanning, periodic/event task scanning, and so
forth) over a 1.0 second window.
The instruction waits for the configured update time (default is 5 seconds),
then collects all the metrics in its L_CPU_Out In/Out parameter tag. The
instruction gathers data every update time as long as it is enabled.
IMPORTANT

The L_CPU Instruction logic is firmware version dependent. There are different
versions of the instruction for each major release (18.x, 19.x, etc.) of Logix
firmware. Be sure to load the right version.
The L_CPU Instruction does not support SoftLogix controllers or the
emulated controller in RSLogix Emulate 5000. If the L_CPU Instruction
identifies the controller as the wrong firmware version or as an unsupported
controller, it will not poll, but rather will assert the Sts_WrongVersion status
flag.
IMPORTANT

The L_CPU Instruction must be configured with the slot number of the controller.
If the Instruction is asserting the Sts_MsgErr flag, that means it cannot
communicate via MSG to the controller. Check the Cfg_SlotNumber
configuration. If you change Cfg_SlotNumber, it may be necessary to cycle the
controller mode to Program, then back to Run, for the change to take effect.

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter 1

Overview

TIP
You can find the correct slot number using RSLogix 5000 software. In the
Controller Organizer, select the controller (top item). Right-click and select
Properties. The controller slot number is shown near the bottom of the properties
window. For controllers where the slot number is not configurable, this item will
be disabled (grayed out); regardless, it still displays the correct number to use to
configure the L_CPU Instruction.

Publication SYSLIB-RM017C-EN-E - October 2011

Overview

Chapter 1

Operating Modes

The L_CPU Instruction has no commands or outputs intended to control


equipment and so does not have any Modes.

Alarms

The L_CPU Instruction does not generate any alarms. If an alarm is needed
when a specific metric crosses a threshold, you will need to add logic to do the
checking. The logic can be as simple as a comparison (CMP, GRT, GEQ, LES,
LEQ or LIM instruction) plus a P_Alarm Add-On Instruction.
Refer to the Process Add-On Instructions and Graphics: Alarm (P_Alarm)
Reference Manual, publication SYSLIB-RM002, for more information.

Execution

The following table explains the handling of instruction execution conditions.


Condition

Description

EnableIn False (False Rung)

The L_CPU Instruction has no EnableInFalse


logic and does nothing on a false rung. Data
associated with the instruction are left in
their last state.

Powerup (Pre-Scan, First Scan)

Logic is set up to ensure the Window Time


is sent to the controller when it transitions
to RUN mode. Previously active polling
(prior to power down or transition to PROG
mode) is cancelled. High-water data stored
in the instruction (not built in to the
controller status registers) are cleared.

Postscan (SFC Transition)

No SFC Postscan logic is provided.

Refer to the Logix5000 Controllers Add-On Instructions Programming


Manual, publication 1756-PM010, for more information on Add-On
Instruction execution condition handling.

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter 1

Overview

Revision Compatibility

The L_CPU Add-On Instruction in RSLogix 5000 software and the Faceplate
in FactoryTalk View software are marked with revision information as shown
in the following table:.
Component

Example

The Add-On Instruction in RSLogix 5000 has


revision information visible when the
instruction is selected in the Controller
Organizer.

The Faceplate in FactoryTalk View has


revision information visible when the
pointer is paused just inside the lower
left-hand corner of the Faceplate when
called up on a running HMI Client.

The Instruction and Faceplate are compatible if they have the same Major and
Minor Revision numbers.
The Major Revision is the first number, before the period.
The Minor Revision is the second number, after the period and before the
hyphen or space.
Information after the hyphen or space indicates the Tweak Revision. The
Instruction and Faceplate do not have to have the same Tweak Revision to be
compatible.
In the table above, the Add-On Instruction and Faceplate shown are
compatible because they have the same Major.Minor (1.1).

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter

Configuration Options

Configuration Parameters

Enter the appropriate values from the following table into the L_CPU
Instructions configuration parameters to configure it for your application.
Use the HMI Faceplate or the RSLogix 5000 Tag Monitor function to set the
applicable configuration parameter(s).
TIP
To install the L_CPU instruction, import the entire L_CPU Ladder Diagram rung
(not just the instruction). When you import the rung, all the User-Defined Data
Types, Tags and their values required by the instruction are imported as well,
including MSG configurations, data required to be sent by the Messages, and
default instruction configuration, Your application will have the Controller Tag
L_CPU_Out created and placed in the L_CPU instruction's Ref_Out InOut
Parameter. In the Associated Parameters column below, references to
L_CPU_Out mean the Tag referenced in the Ref_Out InOut Parameter.

Parameter:

Default:

Cfg_MainTaskInstance 1

Faceplate Tab Usage:


Location:
This parameter determines which Task
in the controller has its Scan Time
(Use GSV to get (Max, Last) monitored by the L_CPU
Instruction. Usually this is the
Task instance
MainTask, but any task can be chosen.
number and
write to this
parameter in
IMPORTANT
logic.)

None

Associated Parameters:
L_CPU_Out.ScanTimes.ScanTimeMax
L_CPU_Out.ScanTimes.ScanTimeLast

This parameter's value should be set


programmatically using data returned
by a GSV instruction. The GSV
instruction should be executed before
the L_CPU instruction, and set up as
follows:
Class: Task
Instance: (name of Task to monitor)
Attribute: Instance
Destination:
L_CPU.Cfg_MainTaskInstance
If you imported the entire L_CPU rung,
not just the instruction, the required
GSV has been placed for you. Just
enter the name of the Task to monitor.

7Publication SYSLIB-RM017C-EN-E - October 2011

Chapter 2

Configuration Options

Parameter:

Default:

Faceplate Tab Usage:


Location:

Cfg_SlotNumber

None
(Obtain this
value from
RSLogix 5000
software, then
code a MOV to
move it to this
parameter in
logic.)

Enter the slot number of the controller


executing the L_CPU instruction.

TIP

Associated Parameters:
If this parameter is set incorrectly, the
Message (MSG) instructions
contained in the L_CPU instruction
will error. This is reflected in the
Sts_MsgErr status bit of the L_CPU
instruction.

To determine the value to enter:


Open your application in RSLogix
5000 software
In the Controller Organizer,
right-click on the Controller at the
top and select Properties
In the General tab of the Controller
Properties dialog, find the Slot
number on the lower left.
The Slot selection may be grayed out
for certain controller families, but the
correct Slot number is still displayed.
If you imported the entire L_CPU rung,
not just the instruction, the required
MOV instruction has been placed for
you. Just enter the proper slot number
in the Source parameter of the MOV.

Cfg_SupportInfo

Enter
Software
S/N or
Support
Contract
Number

Maintenance

Enter your RSLogix 5000 software


serial number, your TechConnect
Support contract number, or other
information that Maintenance or
Engineering personnel will need if
they call Rockwell Automation
Technical Support. On the L_CPU
faceplate, this text can only be
changed by an engineer or
administrator, and it will not be visible
to operator-level users

None

Publication SYSLIB-RM017C-EN-E - October 2011

Configuration Options

Parameter:

Default:

Faceplate Tab Usage:


Location:

Cfg_UpdateT

5 sec

Maintenance

This parameter determines how often


the L_CPU instruction polls the
controller for performance data.

Chapter 2

Associated Parameters:
Sts_Timing
All metrics in L_CPU_Out will be updated
at this interval.

This time should be greater than or


equal to the Cfg_WindowT time if the
(Ref_Out tag).CPUUse data are
being used.
IMPORTANT
Setting this parameter too low will
result in a flood of Messages (MSG) to
the controller, possibly impacting
control performance. Do not use a
value less than 5 seconds unless
instructed to do so by a Rockwell
Automation Technical Support
specialist.
Cfg_WindowT

1.0 sec

None

This parameter determines the


timeframe over which controller CPU
use metrics are collected.

CPU Use metrics:


L_CPU_Out.CPUUse.Comms
L_CPU_Out.CPUUse.Messaging

IMPORTANT
Setting this parameter too low may
result in CPU usage data that are
imprecise, or not meaningful
averages, because they are collected
over too short a time to see all tasks
the controller is performing. Setting
this parameter too high may result in
averaged CPU usage data that may not
capture bursts in certain activities. It is
recommended you keep this
parameter at its default value unless
instructed to change it by Rockwell
Automation Technical Support.

Publication SYSLIB-RM017C-EN-E - October 2011

L_CPU_Out.CPUUse.Motion
L_CPU_Out.CPUUse.Redundancy
L_CPU_Out.CPUUse.Safety
L_CPU_Out.CPUUse.System
L_CPU_Out.CPUUse.PeriodicAndEvent
L_CPU_Out.CPUUse.ContinuousOrFree

Chapter 2

Configuration Options

Notes:

10

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter

Instruction Data Reference

This chapter describes the L_CPU Instructions public parameters.


The descriptions in the table below show how these data elements are used
with the L_CPU Add-On Instruction.

L_CPU_Out

Name:

Substructure:

This section shows the L_CPU Instructions Ref_Out (reference output) tags
data structure. This structure is contained in the L_CPU_Out User-Defined
Data Type (UDT). This UDT is imported if you import the entire L_CPU
rung rather than just the Add-On Instruction.
Type:

Element:

Style:

L_CPU_Out

Description:

Associated Parameter:

L_CPU Output Data


Identity

Device Identity
SINT[33]

Name

ASCII

INT

VendorID

Decimal Vendor ID (1 = Rockwell


Automation)

INT

ProductType

Decimal Product Type (14 =


Controller)

INT

ProductCode

Decimal Identifies Model of


Controller (e.g., 96 =
1756-L75)

SINT

Major

Decimal Major Firmware Revision


(> = 18)

SINT

Minor

Decimal Minor Firmware Revision

DINT

Serial

Hex

Controller Serial Number

INT

Status

Binary

Device Status (bit


mapped, see
documentation)

11Publication SYSLIB-RM017C-EN-E - October 2011

Controller and memory


Catalog Number. The first
byte is the number of
characters, which are
contained in the following
32 bytes.

11

Chapter 3

Name:

Instruction Data Reference

Substructure:

Type:

Element:

Style:

CommUse

12

Description:

Associated Parameter:

Communication usage
REAL

RespCPUAvail

Float

Available CPU for


responding to Messages
(HMI, etc.)

REAL

RespCPUAct

Float

CPU in use by Comm Task


(responding to Messages
(HMI, etc.)

DINT

MaxTrendInstance

Decimal Highest current Optimized


Packet (Trend Object)
Instance Number

DINT

NumTrendInstances

Decimal Current number of


Optimized Packet (Trend
Object) Instances

DINT

TrendHighWater

Decimal High water mark of


Optimized Packet (Trend
Object) Instance count

Publication SYSLIB-RM017C-EN-E - October 2011

Instruction Data Reference

Name:

Substructure:

Type:

Element:

Style:

MemUse

Description:

Chapter 3

Associated Parameter:

Memory usage
DINT

FreeIO

Decimal Free bytes of I/O memory

DINT

FreeDataLogic

Decimal Free bytes of Data and


Logic memory

DINT

FreeGen

Decimal Free bytes of General


memory

DINT

FreeSafety

Decimal Free bytes of Safety


memory

DINT

TotalIO

Decimal Total bytes of I/O memory

DINT

TotalDataLogic

Decimal Total bytes of Data and


Logic memory

DINT

TotalGen

Decimal Total bytes of General


memory

DINT

TotalSafety

Decimal Total bytes of Safety


memory

DINT

MinIO

Decimal Low water free bytes of


I/O memory

DINT

MinDataLogic

Decimal Low water free bytes of


Data and Logic memory

DINT

MinGen

Decimal Low water free bytes of


General memory

DINT

MinSafety

Decimal Low water free bytes of


Safety memory

DINT

MaxBlockIO

Decimal Largest available block of


I/O memory

DINT

MaxBlockDataLogic Decimal Largest available block of


Data and Logic memory

DINT

MaxBlockGen

Decimal Largest Available block of


General memory

DINT

MaxBlockSafety

Decimal Largest Available block of


Safety memory

ScanTimes

Scan Times
REAL

ScanTimeMax

Float

Maximum Scan Time (ms)


for selected Task instance

REAL

ScanTimeLast

Float

Most Recent Scan Time


(ms) for selected Task
instance

Publication SYSLIB-RM017C-EN-E - October 2011

13

Chapter 3

Name:

Instruction Data Reference

Substructure:

Type:

Element:

Style:

CPUUse

14

Description:

Associated Parameter:

CPU usage
REAL

Comms

Float

Communications
(responding to HMI and
MSGs) %CPU

REAL

Messaging

Float

Sending Messages (MSG


instructions) %CPU

REAL

Motion

Float

Motion Axes %CPU

REAL

Redundancy

Float

Redundancy
Communication and
Synchronization %CPU

REAL

Safety

Float

Safety Processes %CPU

REAL

System

Float

System Processes %CPU

REAL

PeriodicAndEvent

Float

User Periodic and Event


Tasks %CPU

REAL

ContinuousOrFree

Float

Continuous Task (if any) or


Free (if none) %CPU

Publication SYSLIB-RM017C-EN-E - October 2011

Instruction Data Reference

Name:

Substructure:

Type:

Element:

ConnUse

Style:

Description:

Chapter 3

Associated Parameter:

Connection usage
INT

TotalAllow

Decimal Total Connections


Supported

INT

TotalCurr

Decimal Total Connections


Currently Active

INT

TotalHiWater

Decimal High water mark of Total


Connections Active

INT

IOAllow

Decimal I/O Connections Allocated

INT

IOCurr

Decimal I/O Connections Currently


Active

INT

IOHiWater

Decimal High water mark of I/O


Connections Active

INT

ProdAllow

Decimal Produced Tag


Connections Allocated

INT

ProdCurr

Decimal Produced Tag Connections


Currently Active

INT

ProdHiWater

Decimal High water mark of


Produced Tag Connections
Active

INT

ConsAllow

Decimal Consumed Tag


Connections Allocated

INT

ConsCurr

Decimal Consumed Tag


Connections Currently
Active

INT

ConsHiWater

Decimal High water mark of


Consumed Tag
Connections Active

INT

MSGCurr

Decimal Message/Block Transfer


Connections Currently
Active

INT

MSGHiWater

Decimal High water mark of


Message/Block Transfer
Connections Active

INT

IncomCurr

Decimal Incoming Connections


Currently Active

INT

IncomHiWater

Decimal High water mark of


Incoming Connections
Active

DINT

UCBsAllow

Decimal Unconnected Buffers


Allocated

DINT

UCBsCurr

Decimal Unconnected Buffers


Currently Active

DINT

UCBsHiWater

Decimal High water mark of


Unconnected Buffers
Active

Publication SYSLIB-RM017C-EN-E - October 2011

15

Chapter 3

Name:

16

Instruction Data Reference

Substructure:

Type:

Element:

Style:

Description:

INT

MCacheAllow

Decimal MSG/BT Cache Entries


Allocated

INT

MCacheCurr

Decimal MSG/BT Cache Entries


Currently In Use

INT

MCacheHiWater

Decimal High water mark of


MSG/BT Cache Entries In
Use

TimeSlice

INT

Decimal Controller Timeslice: % of


continuous task time for
communications

IOLEDStatus

INT

Decimal I/O LED Status


0 = Off
1 = RedBlink
2 = GreenBlink
3 = Solid Green

ForceStatus

INT

Decimal Force Status:


bit .0 = force installed
bit .1 = force active

MinorFaultCount

DINT

Decimal Number of Minor Fault


occurrences since last
reset. This is a 16-bit
unsigned value, so it
loops from 65,535 back to
zero.

MinorFaultProg

BOOL

Minor Fault: Program


Logic Problem

MinorFaultTask

BOOL

Minor Fault: Task Overlap

MinorFaultPort

BOOL

Minor Fault: Serial Port


Problem

MinorFaultBatt

BOOL

Minor Fault: Replace /


Reconnect Battery

Associated Parameter:

Publication SYSLIB-RM017C-EN-E - October 2011

Instruction Data Reference

Execution

Chapter 3

Execution parameters are included with every Add-On Instruction. See the
Logix5000 Controllers Add-On Instructions Programming Manual,
publication 1756-PM010, for more information on these data elements.

Name:

Data Type:

Usage:

Default:

EnableIn

BOOL

Input

Enable Input:
1 = Normal Scan: monitor Logix CPU
utilization
0 = No action (no EnableInFalse logic is
provided)

EnableOut

BOOL

Output

Enable Output: The EnableOut signal is


not manipulated by this instruction. Its
output state always reflects the EnableIn
input state.

Inf_Tab

SINT

Tab to display (FTView ME)

Inf_Type

STRING_16

L_CPU

Must contain AOI name, used for HMI and


Information S/W

L_CPU

BOOL

Unique Parameter Name for auto discovery

Output

Publication SYSLIB-RM017C-EN-E - October 2011

Style: Description:

Associated
Configuration
Parameter

17

Chapter 3

Instruction Data Reference

Configurations
(Cfg_)

Configuration data elements are used to set configurable capabilities, features,


and functions of the L_CPU Instruction.
The following Configuration data may be modified by controller application
logic, using the HMI Faceplate, or using the Tag Monitor in
RSLogix 5000 software.

Name:

Data Type:

Associated
Configuration
Parameter

Usage:

Default:

Style:

Description:

Cfg_MainTaskInstance DINT

Input

Decimal

Instance Number (from GSV) of Main


Task (or any other task to monitor for
scan time) (0 ...31)

Cfg_SlotNumber

DINT

Input

Decimal

Controller Slot Number in local


chassis

Cfg_UpdateT

DINT

Input

5 sec

Decimal

Refresh (poll and display) time for all


CPU data

Cfg_WindowT

REAL

Input

1.0 sec

Float

Window time for collecting Task data


(sec)

Because they use arrayed or structured data types, the following Configuration
data elements use L_CPU Add-On Instruction Local Tags. These may be
modified using RSLogix 5000 software or using the HMI Faceplates, but
cannot be modified using controller logic.

Name:

Data Type:

Cfg_Desc

STRING_40

'Logix CPU STRING


Utilization
Monitor'

Description for display on HMI

Cfg_Label

STRING_20

'CPU
STRING
Utilization'

Label for graphic symbol displayed on


HMI

Cfg_SupportInfo

STRING_40

Cfg_Tag

STRING_20

18

Usage:

Local

Default:

Style:

Associated
Configuration
Parameter

Description:

Enter
Software
S/N or
Support
Contract
#

ASCII

Enter your RSLogix 5000 software


serial number or your support contract
number for reference in case you call
Rockwell Automation Technical
Support.

'L_CPU'

STRING

Tagname for display on HMI

Publication SYSLIB-RM017C-EN-E - October 2011

Instruction Data Reference

Operator Commands,
Maintenance Commands,
Command Readies
(OCmd, MCmd_, Rdy_)

Chapter 3

Maintenance Commands are used by the maintenance personnel at the HMI to


request instruction actions. These Commands are set (latched) by the HMI and
are read and then cleared (unlatched) and acted upon by the L_CPU
instruction, allowing a many-to-one relationship between HMI requestors and
each Command. Commands are implemented as public Input Parameters of
the L_CPU instruction.

Operator Commands

Name:

Data Type:

Usage:

Default:

Style: Description:

OCmd_Enable

BOOL

Input

Edge

Operator Command to enable


collection of data

OCmd_Disable

BOOL

Input

Edge

Operator Command to disable


collection of data

Associated
Configuration
Parameter

Maintenance Commands

Name:

Data Type:

Usage:

Default:

Style: Description:

MCmd_Enable

BOOL

Input

Edge

Maintenance Command to enable


collection of data

MCmd_Disable

BOOL

Input

Edge

Maintenance Command to disable


collection of data

Publication SYSLIB-RM017C-EN-E - October 2011

Associated
Configuration
Parameter

19

Chapter 3

Instruction Data Reference

Maintenance Command Readies


Each Maintenance Command has a corresponding Ready bit which indicates
whether the Command will be accepted and acted upon when received. The
Ready bit is used to enable (1) or gray-out (0) the Maintenance Command
button on the Faceplate.
Associated
Configuration
Parameter

Name:

Data Type:

Usage:

Default:

Rdy_Enable

BOOL

Output

1 = Ready to receive MCmd_Enable


(enable button)

Rdy_Disable

BOOL

Output

1 = Ready to receive MCmd_Disable


(enable button)

20

Style: Description:

Publication SYSLIB-RM017C-EN-E - October 2011

Instruction Data Reference

Status
(Sts_)

Chapter 3

Status data elements contain device status. The HMI displays these Status
points, and they are available for use by other application logic.

Device Status

Style: Description:

Associated
Configuration
Parameter

Name:

Data Type:

Usage:

Default:

Sts_Enabled

BOOL

Output

1 = CPU data collection has been


Enabled

Sts_Timing

BOOL

Output

1 = Instruction is waiting for Update


Time to complete

Sts_Busy

BOOL

Output

1 = Instruction is getting CPU data from


the controller

Sts_Done

BOOL

Output

1 = Data collection complete, updated


CPU data are in the Ref_Out tag

Sts_MsgErr

BOOL

Output

1 = Message Error, unable to read at


least one metric

Sts_WrongVersion

BOOL

Output

1 = Wrong firmware version (must be


18.x) or controller is not supported

Sts_Timing

BOOL

Output

1 = The instruction is waiting for the


Update Time to complete before
gathering CPU data

Cfg_UpdateT

Sts_MsgErr

BOOL

Output

1 = Message Error, unable to read at


least one metric. Check that the
configured Controller Slot Number
is correct.

Cfg_SlotNumber

Sts_WrongVersion

BOOL

Output

1 = Wrong firmware version or


controller is not supported.
IMPORTANT
The L_CPU Add-On Instruction is
firmware major revision dependent.
You must use the L_CPU_18 instruction
with Revision 18.xx firmware, the
L_CPU_19 instruction with Revision
19.xx firmware, and so on.
SoftLogix controllers and
RSLogixEmulate 5000 controllers are
not supported by the L_CPU Instruction.

Publication SYSLIB-RM017C-EN-E - October 2011

21

Chapter 3

Instruction Data Reference

Notes:

22

Publication SYSLIB-RM017C-EN-E - October 2011

Chapter

HMI Reference

This chapter describes the HMI Graphic Symbols and Faceplate provided for
human-machine interface (HMI) for the L_CPU Instruction.

Graphic Symbols

Graphic Symbols are provided for use on end-user process graphic displays.
L_CPU Graphic Symbols have the following common attributes:
L_CPU Graphic Symbol

Other module Graphic Symbols

Status Indicators
Touch Field to
recall Faceplate

Tooltip with Controller


Name and Path

The L_CPU Graphic Symbol looks like a physical controller and is intended to
be used in a chassis view or network view display with symbols for other
modules including I/O, communication cards and others. The L_CPU
Graphic Symbol has indicators that match the status on the face of the actual
controller and use the same colors and blink states.
The L_CPU Graphic Symbol includes a touch field; clicking the Symbol will
call up the L_CPU Faceplate. Hovering the pointing device pointer over the
Symbol will display its tooltip, giving the Controller name and
communication path.

23Publication SYSLIB-RM017C-EN-E - October 2011

23

Chapter 4

HMI Reference

Graphic Representation
The Status Indicators on the Graphic Symbol change color and blink state
depending on the controller status.
Indicator

State

Run (Upper Left for ControlLogix 1756)

Green Steady: The controller is in Run or


Remote Run mode
Off: The controller is in Program, Remote
Program or Remote Test Mode

Force (Center Left for ControlLogix 1756)

Off: There are no forces in the Controller


Yellow Blinking: There are forces in the
Controller but forcing is not active
Yellow Steady: Forcing is active (I/O being
forced)

Bat (Lower Left for ControlLogix 1756)

Off: The memory battery is installed and OK


Red Steady: The memory battery is low,
missing or not properly connected

I/O (Upper Right for Control Logix 1756)

Green Steady: Communication with all


configured I/O modules is OK
Green Blinking: The controller is not
communicating with one or more configured
I/O modules
Red Blinking: The controller cannot
communicate with the chassis in which it is
installed
Off: No I/O modules are configured in the
application, or no application is loaded into
the controller

RS232 (Center Right for ControlLogix 1756)

Not used: the L_CPU Instruction does not


monitor serial port activity

OK (Lower Right for ControlLogix 1756)

Green Steady: The controller is OK


Red Steady: The controller has a Major
Fault

24

Publication SYSLIB-RM017C-EN-E - October 2011

HMI Reference

Faceplate

Chapter 4

The Logix Control Processor Utilization Faceplate consists of six tabbed


pages. The Operator tab is displayed when the Faceplate is initially called up.
Click the appropriate icon at the top of the Faceplate to access a specific tab.
Communications

Operator

Memory

CPU Usage

Maintenace

Connections

Exit

Help

Operator Tab

Controller Mode
Controller Status

Controller Catalog
Number
Controller Clock
Date and Time
Minor Fault Count

Status of HMI
Communication with
Controller
I/O Communication and I/O
Forcing Status Indicators
Redundant Controller
Status
Controller firmware version
(Major. Minor)

Minor Fault Indicators

Controllers configured
Communication Timeslice
Communication Bar graph
Data Values

Optimized Packet Counts


Communication Bar
graph

Publication SYSLIB-RM017C-EN-E - October 2011

25

Chapter 4

HMI Reference

The Operator tab shows the following information:

Controller Mode
Controller Status
Status of HMI Communication with the Controller
I/O Communication and I/O forcing status indicators
The Controllers redundancy status (only displayed for a Controller in a
redundant configuration)
Controller identity information, including catalog number and firmware
major and minor revision
Count of Minor Fault occurrences, and indicators for currently active
Minor Faults of specific classes
The Controllers configured Communication Timeslice value
A nested bar graph and numeric displays showing the approximate
percent CPU available for responding to communications requests (such
as from HMI) (outer bar), and the approximate percent CPU actually
being used for responding to communications requests (inner bar). The
outer bar graph changes color from green to yellow when CPU available
for communications is low, and the inner bar graph changes color from
blue to red when nearly all CPU available for communications is being
used.
Count of RSLinx Optimized Packets currently used, the high-water
value of Optimized Packets used, and the largest Optimized Packet
Instance Number used in the controller.
TIP

The Operator (Home) Tab displays the information most commonly requested by
Rockwell Automation Technical Support when you place a call for support for a Logix
controller. You will also need your software serial number or technical support
contract number. A space is provided for you to record this information on the
Maintenance Tab for ready reference when you call. The Technical Support
Specialist may or may not require information from the other tabs depending on the
nature of the issue.

26

Publication SYSLIB-RM017C-EN-E - October 2011

HMI Reference

Chapter 4

Communications Tab

The Communications tab displays diagnostic counters for the RSLinx


Enterprise driver used by the HMI to communicate with the controller.

Publication SYSLIB-RM017C-EN-E - October 2011

27

Chapter 4

HMI Reference

CPU Usage Tab

The CPU Usage tab displays the approximate CPU percentage used by each
of the controllers major activities. If there is a Continuous Task running in the
controller, the top segment of the bar graph shows the CPU used by the
Continuous Task. If there is no Continuous Task, the top segment shows the
percentage CPU free (unused).
Note: The usage values may not sum to 100%.
The Main Task Scan Times are for the Task whose instance number is passed
into the L_CPU instruction. This instance number is obtained using a GSV
(built-in) Instruction on the rung which executes the L_CPU Instruction. This
GSV is included if you installed the L_CPU instruction using a Rung Import.
Just enter the name of the controller Task you want to monitor into the GSV
Instruction. (The Task name in the GSV can be changed by online editing.)

28

Publication SYSLIB-RM017C-EN-E - October 2011

HMI Reference

Chapter 4

Memory Tab

Total Controller Memory


Usage Bar Graph and
Values

I/O Memory Usage


Bar Graph and Values

Data and Logic Memory


Usage Bar Graph and
Values

Safety Memory Usage


Bar Graph and Values
(Visible if Safety
Memory is used

General Memory Usage


Bar Graph and Values

Note: Only those memory sections that exist (have non-zero size) are shown
in the graphic above. Each section (I/O Memory, Data and Logic Memory,
General Memory, and Safety Memory) is visible only if the controller returns a
size for it that is non-zero.
The Memory tab displays the size of overall controller memory and the
amount free. For each memory section displayed, the Memory Tab shows:

Publication SYSLIB-RM017C-EN-E - October 2011

The total memory allocated to that section


The amount of memory in that section which is used
The amount of memory in that section which is unused
The maximum (high-water) amount of memory used
The largest contiguous block of unused memory

29

Chapter 4

HMI Reference

Connections Tab

Controller
Connection Statistics

Message (MSG) and


Block Transfer
Statistics

The Connections tab displays the number of connections currently being


used, the highest number used, and the total available connections for several
types of data transfers, plus statistics for Message (MSG) instructions using
Unconnected Buffers and Message Cache Entries.

30

Publication SYSLIB-RM017C-EN-E - October 2011

HMI Reference

Chapter 4

Maintenance Tab

Data Collection Enable


and Disable Buttons

Data Collection Enabled /


Disabled Status Indicator
Data Collection Progress and
Error Indicators

Data Collection Update


(Poll) Interval (in
seconds)

Other Configuration
data (display only)

Free-format text entry for


recording software serial number,
support contract number or other
support information

The Maintenance tab shows the following information:


An indicator to show whether L_CPU data collection (polling) is
Enabled or Disabled.
An indicator to show when the L_CPU instruction is waiting before the
next data collection (poll) and when a poll is in progress
An indicator to show when a poll is busy or the result of the last poll
(Data Received or Error)
Configuration values, some of which cannot be changed from the
Faceplate

Publication SYSLIB-RM017C-EN-E - October 2011

31

Chapter 4

HMI Reference

The following table lists the functions on the Maintenance tab.


Button / Field

Action

Security
Required

Click to enable collection of


controller data.

Code C

IMPORTANT
The L_CPU Instruction
accomplishes its data collection
using Message (MSG) instructions
to the controller (MSG to self),
which uses some controller
communication resources. You
may wish to leave data collection
disabled until it is needed. Some
Faceplate data are monitored
without using the polling
messages and will still be
displayed.
Click to disable collection of
controller data.

Code C

Only data collection via MSG


instructions is disabled. Other data
will still be updated and displayed
on the Faceplate. Data not
updated when collection is
disabled are not displayed.
Update (poll) time for CPU data
(sec)

Enter the interval at which to


collect and update data displayed
on the other Faceplate tabs.

Code C

IMPORTANT
Setting this parameter too low will
result in a flood of Messages
(MSG) to the controller, possibly
impacting control performance. Do
not use a value less than 5
seconds unless instructed to do so
by a Rockwell Automation
Technical Support specialist.
Support Information (Serial # or
Contract #)

32

Enter the Serial Number for your


RSLogix 5000 software or the
contract number for your
TechConnect or other technical
support contract so it is available
for ready reference if you call
Rockwell Automation Technical
Support.

Code E or P

Publication SYSLIB-RM017C-EN-E - October 2011

HMI Reference

Chapter 4

Logix CPU Faceplate Help

Publication SYSLIB-RM017C-EN-E - October 2011

33

Chapter 4

HMI Reference

Notes:

34

Publication SYSLIB-RM017C-EN-E - October 2011

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/.

Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada

1.440.646.3434

Outside United States or


Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact


your local Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Publication SYSLIB-RM017C-EN-E - October 201136


Copyright 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like