Professional Documents
Culture Documents
Frequency inverters DF
(50/60Hz g5%)
1 AC 180…264 V g 0% – K – –
3 AC 180…264 V g 0% K K – –
Frequency inverters
3 AC 342…528 V g 0% – – K K
Rated operational current 15.9…32 A 1.4…10 A 1.5…16 A 22 … 230 A
Assigned motor rating at rated voltage 4…7.5 kW 0.25…7.5 kW 0.37…7.5 kW 11 … 132 kW
PID controller K K K K
Built-in braking chopper (external braking resistance) – – – Only DF6-340-11K
and DF6-340-15K
Keypad K K K K
Communication interface RS 485, Modbus RTU (optionally PROFIBUS-DP, CANopen) RS 422, RS 485, (optionally
PROFIBUS-DP)
Product standard EN 50178, IEC 61800-3
Approvals CE, UL, c-UL, cTick CE, UL, c-UL,CSA, cTick
Degree of protection IP20
Ambient temperature
Operating temperature °C -10 to +40 with rated current Ie at a clock frequency of 5 kHz; up to +50 °C at a reduced clock frequency of 2 kHz
and reduced output current of 80 % Ie.
Storage °C –25…+70
Mechanical shock resistance Vibration and impact, max. 5.9 m/s2 (0.6 g) at 10 to 55 Hz
Pollution degree VDE 0110 Part 2, pollution degree 2
Climatic proofing Class 3K3 according to EN 50178 (non-condensing, average relative humidity 20 to 90 %)
Altitude m 0 to 1000 m a.s.l., above 1000 m with reduced current (2.5 %/100 m)
Mounting position Vertically suspended
Free surrounding areas 100 mm above and below device
Emitted interference IEC/EN 61800-3 (EN 55011 group 1 class B)
Noise immunity IEC/EN 61800-3, industrial environment
Insulation resistance Overvoltage category III according to VDE 0110
Leakage current to PE mA < 3.5 (to EN 50178)
Contact protection Finger and back-of-hand proof
Protective isolation from switching Safe isolation from the mains. Double basic isolation (to EN 50178)
circuitry
Protective measures Overcurrent, earth fault, overvoltage, undervoltage, overload, overtemperature, electronic overload protection:
I2t monitoring and PTC input (thermistor or thermostat)
Notes If the frequency inverter is to be installed in an enclosure, control panel or similar housing, the ambient temperature Ta is
taken to be the temperature inside this enclosure or control panel.
All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and an ambient temperature
of +40 °C, for operation of a four-pole three-phase asynchronous motor.
Frequency Inverters – Overview 15/3
Frequency inverters
3 AC 342…528 V g 0 % – – K K
Rated operational current 17.5…32 A 1.6…11 A 1.5…16 A 2.8…286 A
Assigned motor rating at rated voltage 4…7.5 kW 0.25…7.5 kW 0,37…7.5 kW 0.75 … 132 kW
PID controller K K K K
Built-in braking chopper (external braking resistance) K K K DV6-340-075 …
DV6-340-11K
Keypad Option DEX-KEY-6…, DEX-KEY-10 K
Communication interface RS 485, Modbus RTU (optionally PROFIBUS-DP, CANopen) RS 422, RS 485, (optionally
PROFIBUS-DP)
Product standard EN 50178, IEC 61800-3
Approvals CE, UL, c-UL, cTick CE, UL, c-UL,CSA, cTick
Degree of protection IP20
Ambient temperature
Operating temperature °C -10 to +40 with rated current Ie at a clock frequency of 5 kHz; up to +50 °C at a reduced clock frequency of 2 kHz
and reduced output current of 80 % Ie.
Storage °C –25…+70
Mechanical shock resistance Vibration and impact, max. 5.9 m/s2 (0.6 g) at 10 to 55 Hz
Pollution degree VDE 0110 Part 2, pollution degree 2
Climatic proofing Class 3K3 according to EN 50178 (non-condensing, average relative humidity 20 to 90 %)
Altitude m 0 to 1000 m a.s.l., above 1000 m with reduced current (2.5 %/100 m)
Mounting position Vertically suspended
Free surrounding areas 100 mm above and below device
Emitted interference IEC/EN 61800-3 (EN 55011 group 1 class B)
Noise immunity IEC/EN 61800-3, industrial environment
Insulation resistance Overvoltage category III according to VDE 0110
Leakage current to PE mA < 3.5 (to EN 50178)
Contact protection Finger and back-of-hand proof
Protective isolation from switching Safe isolation from the mains. Double basic isolation (to EN 50178)
circuitry
Protective measures Overcurrent, earth fault, overvoltage, undervoltage, overload, overtemperature, electronic overload protection:
I2t monitoring and PTC input (thermistor or thermostat)
Notes If the frequency inverter is to be installed in an enclosure, control panel or similar housing, the ambient temperature Ta is
taken to be the temperature inside this enclosure or control panel.
All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and an ambient temperature
of +40 °C, for operation of a four-pole three-phase asynchronous motor.
15/4 System overview
Frequency inverters
DF51 Moeller HPL0211-2007/2008 http://catalog.moeller.net
8
9
Vector frequency inverters
POWER
2
Hz ALARM
A
Frequency inverters
RUN
PRG
1
PRG
ENTER
POWER
Hz Hz ALARM
7 POWER
A A
ALARM RUN
PRG
RUN RUN
PRG
PRG
ENTER
RMT
READ
COPY
COPY
MNT
PRG
ENTER
FWD
REV
6 3
The frequency inverters of the DF51 series provide infinitely variable speed control Comprehensive protective functions guarantee safe operation and protect
of three-phase motors. They are especially suitable for applications where simple frequency inverters and motors:
operation and economic efficiency are important. • Overcurrent, earth fault
The assigned performance range for four-pole three-phase asynchronous motors • Overload, electronic motor protection
ranges from: • Overtemperature
• 0.25 to 2.2 kW with single-phase power supply (230 V) • Overvoltage, undervoltage
• 0.25 to 7.5 kW with three-phase power supply (230 V) • Restart inhibit
• 0.37 to 7.5 kW with three-phase power supply (400 V) Additional operational functions:
The frequency inverter DF51 can be used as a stand-alone drive or incorporated in • > 100 % starting torque from about 6 Hz
automation systems. With its / (voltage/frequency) characteristic control, it can be • PID controller
used in wide range of applications, from simple pump and fan drives through • Automatic voltage control (boost)
standard transportation and conveying applications to flexible use the machine tool • Min./max. frequency limitation
and packaging machine industry. • Electronic motor potentiometer function
• Frequency hopping (frequency masking)
Features • DC braking to motor standstill
• Up to 16 fixed speeds
• PLC functionality: Linkage of digital in- and outputs
• Compact construction due to highly-integrated module technology
• Integrated keypad with four-character seven-segment display, LEDs, six
function keys and a setpoint value potentiometer Documentation
• Serial interface (RS 485, Modbus RTU)
• Five digital inputs (24 V DC) • Each DF51 vector frequency inverter is supplied with installation instructions
• Two digital outputs (24 V DC) and a CD.
• Two analog inputs (0 to +10 V, 4 to 20 mA) • The AWA contains a short description with illustrations and information about
• One analog output (0 to +10 V) correct handling, installation and electrical connection of the device. The
• A relay (changeover contact: 24 V DC/230 V AC) information supplied is printed in seven languages (English, Chinese, French,
• Thermistor input German, Italian, Russian, and Spanish).
• User-friendly direct operation without prior configuration. • The CD contains a detailed manual (at least English, German) and configuration
• Conformance to global standards CE, UL, c-UL and cTick software with help text.
• Documentation and parameterization software are also available for download
from the Internet:www.moeller.net/support
Note:
The software on the CD can be run on PCs with the current Windows operating
systems (from 98 to XP). For connecting a PC (RS 232) to a DF51 frequency inverter,
you will need the connection cable DEX-CBL-2M0-PC.
15/6 Ordering
Frequency inverters
DF51 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Rated voltage Max. rated Rated power for Part no. Price Std. pack
operational current motors Article no. see price list
Ue Ie
Vector frequency inverters
V A P
Frequency inverters
kW
Notes 1) All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and an ambient temperature of +40 °C, for
operation of a four-pole three-phase asynchronous motor.
Engineering 15/7
Frequency inverters
http://catalog.moeller.net Moeller HPL0211-2007/2008 DF51
Frequency inverters
Without
mains
reactor/
filter
P Ie IN
kW A A
Frequency inverters DF51
Single-phase power supply (230 V AC)
Notes: 1) Mains chokes reduce the line currents by up to 30 % and extend the frequency inverters’ lifespan.
2) No device assigned yet.
3) Where single-phase frequency inverters are used on mains without line reactor (for example with reactive-power compensation equipment or UPS),
current peaks can occur when the mains contactor is switched on, and these can cause the FAZ-B... to trip prematurely. Remedy: fit a mains reactor
upstream or use a FAZ-C…
Line protection with FAZ, PKM or PKZM (PKZM0 can be used instead of PKM0) a section 12, 8
Mains contactors DIL a section 5
Main chokes DEX-LN… a page15/36
Motor chokes DEX-LM3-… a page 15/37
SFB400/... sine-wave filters please enquire
15/8 Engineering
Connection example
DF51 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Terminal 4: FF2 = Fixed frequency 2
Block diagram DF51
Terminal 5: RST = Reset, can be configured as thermistor input with
parameter C005.
In their default configuration, the DF51 frequency inverters can be used at their
assigned supply voltage and motor rating (four-pole, three-phase asynchronous Terminal 11: FA1 = Frequency arrival, type 1 (output frequency actual value
Vector frequency inverters
motor) without any parameter changes. Their acceleration and deceleration times = reference input)
are set to 15 seconds. The control signal inputs and outputs have the following Terminal 12: RUN = Running
assigned functions:
Terminals K11- Relay, fault signal (K11-K14 ready for operation)
Frequency inverters
11
FA1
CM2
12
RUN
+24 V
P24
+
–
0V
OI
4...20 mA
O
0...10 V
+
–
+10 V
AM
0...10 V
1
FWD
* PNU C005 = 19 (PTC)
2
REV
L
0V
3
FF1
4
FF2
5
*
i
PE K12 K14 K11
RST
e
1
3
PE
PE
L3
W
N
3~
L2
M
V
L1
U
L
DC+
DC–
L+
Engineering 15/9
Connection example
http://catalog.moeller.net Moeller HPL0211-2007/2008 DF51
Connection example for a 0.75 kW motor with the ratings plate illustrated below.
Variant A: Motor connected in a delta circuit, DF51 with single-phase Variant B: Motor connected in a star circuit, DF51 with three-phase mains
mains supply (230 V). supply (400 V).
Frequency inverters
Mains: 3/N/PE 400 V, 50/60 Hz A) or star-connected to a 400 V mains.
Depending on the mains voltage, a DF5-322 frequency inverter is selected for 230 V single-phase
EMC-conformant connection examples: power section AC, or a DF5-340 for 400 V 3-phase AC, together with the corresponding accessories.
3 h 400 V, 50/60 Hz
1 h 230 V, 50/60 Hz L1
L L2
N L3
PE PE
Q1
FAZ-1N-B16 F1 PKM0-6,3
I I I
PE
R1 R1
PE
DEX-LN1-009 DEX-LN3-004
2 U2 V2 W2
L N L1 L2 L3
PE PE
K1 K1
DE51-LZ1-012-V2 DE51-LZ3-007-V4
L N PE L1 L2 L3 PE
DF51-322-075 DF51-340-075
L+ DC+ DC– U V W PE L+ DC+ DC– U V W PE
T1 T1
PES PES
PES PES
X1 X1
PES PES
PES PES
M M1 M
M1 3~ 3~
e e
U1 V1 W1 U1 V1 W1
W2 U2 V2 W2 U2 V2
230 V 400 V
3.5 A 2A
0.75 kW 0.75 kW
11
Vector frequency inverters
POWER 2
Hz ALARM
A
Frequency inverters
RUN
PRG
10
7 PRG 1
ENTER
POWER
ALARM
PRG
9
RUN
POWER
ALARM
RUN
RMT
READ
COPY
COPY
MNT
PRG
ENTER
FWD
REV
8
5
OPE
POWER RBUS
1 2
ALARM
RUN
6
OFF
With their sensorless vector control, the DV51 frequency inverters offer excellent Comprehensive protective functions guarantee safe operation and protect
torque levels for three-phase motors with cage rotors. They are especially suitable frequency inverters and motors:
for demanding applications in which maximum torque and smooth running are • Overcurrent, earth fault
required at the lower speed range. • Overload, electronic motor protection
The assigned performance range for four-pole three-phase asynchronous motors • Overtemperature
ranges from: • Overvoltage, undervoltage
• 0.25 to 2.2 kW with single-phase power supply (230 V) • Restart inhibit
• 0.25 to 7.5 kW with three-phase power supply (230 V) Additional operational functions:
• 0.37 to 7.5 kW with three-phase power supply (400 V) • Sensorless Vector Control
The vector frequency inverters DV51 can be used as a stand-alone drive or • 200 % starting torque from approx 1 Hz
incorporated in automation systems. The adaptable modules allow flexible • Dynamic braking (external braking resistor)
communication. With the sensorless vector control, applications in the plastics and • Electronic motor potentiometer function
metal processing, textile, paper and printing industries and in crane and lift • PID controller
installations are possible. • Automatic voltage control (boost)
• Min./max. frequency limitation
Features • Frequency hopping (frequency masking)
• DC braking to motor standstill
• Up to 16 fixed speeds
• Compact construction due to highly-integrated module technology • PLC functionality: Linkage of digital in- and outputs
• Internal braking transistor
• Optional keypads DEX-KEY-6…
• Optional fieldbus module (CAN, PROFIBUS DP) Documentation
• Serial interface (RS 485, Modbus RTU)
• Six digital inputs (24 V DC) • Each vector frequency inverter DV51 is supplied with an installation instruction
• Two digital outputs (24 V DC) (AWA) and a CD.
• Two analog inputs (0 to +10 V, 4 to 20 mA) • The installation instruction contains a short description with illustrations and
• One analog output (0 to +10 V) information about correct handling, installation and electrical connection of the
• A relay (changeover contact: 24 V DC/230 V AC) device. The information supplied is printed in seven languages (English,
• Thermistor input Chinese, French, German, Italian, Russian, and Spanish).
• User-friendly direct operation without prior configuration. • The CD contains a detailed manual (at least English, German) and configuration
• Conformance to global standards CE, UL, c-UL and cTick software with help text.
• Documentation and parameterization software are also available for download
from the Internet:www.moeller.net/support
Note:
The software on the CD can be run on PCs with the current Windows operating
systems (from 98 to XP). For connecting a PC (RS 232) to a vector frequency inverter
DV51, you will need the connection cable DEX-CBL-2M0-PC (with integrated
interface converter).
15/12 Ordering
Vector frequency inverters
DV51 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Rated voltage Max. rated operational Rated power for motors Part no. Price Std. pack
current Article no. see price list
Ue Ie at 230 V 3-phase AC
Vector frequency inverters
V A P
Frequency inverters
kW
Notes All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and an ambient temperature of +40 °C, for operation
of a four-pole three-phase asynchronous motor.
Engineering 15/13
Assigned switching and protective elements
http://catalog.moeller.net Moeller HPL0211-2007/2008 DV51
Frequency inverters
mains re-
actor/filter
P Ie IN
kW A A
Frequency inverter DV51, single-phase
mains connection(230 V AC)
DV51-322-025 0.25 1.6 3.5 FAZ-B10/1N1) DILM7 DEX-LN1-006 DE51-LZ1-007-V2 DEX-LM3-005
DV51-322-037 0.37 2.6 5.8 FAZ-B10/1N1) DILM7 DEX-LN1-006 DE51-LZ1-007-V2 DEX-LM3-005
DV51-322-055 0.55 3 6.7 FAZ-B10/1N1) DILM7 DEX-LN1-009 DE51-LZ1-007-V2 DEX-LM3-005
DV51-322-075 0.75 4 9 FAZ-B16/1N1) DILM7 DEX-LN1-009 DE51-LZ1-012-V2 DEX-LM3-005
DV51-322-1K1 1.1 5 11.2 FAZ-B16/1N1) DILM7 DEX-LN1-013 DE51-LZ1-012-V2 DEX-LM3-005
DV51-322-1K5 1.5 8 17.5 FAZ-B20/1N1) DILM7 DEX-LN1-018 DE51-LZ1-024-V2 DEX-LM3-008
DV51-322-2K2 2.2 11 24 FAZ-B32/1N1) DILM7+DILM12-XP1 DEX-LN1-024 DE51-LZ1-024-V2 DEX-LM3-011
Frequency inverter DV51 Three-phase
power supply (230 V AC)
DV51-322-025 0.25 1.6 2 PKM0-10 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-322-037 0.37 2.6 3.4 PKM0-10 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-322-055 0.55 3 3.9 PKM0-10 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-322-075 0.75 4 5.2 PKM0-16 DILM7 DEX-LN3-006 DE51-LZ3-007-V4 DEX-LM3-005
DV51-322-1K1 1.1 5 6.5 PKM0-16 DILM7 DEX-LN3-006 DE51-LZ3-007-V4 DEX-LM3-005
DV51-322-1K5 1.5 8 10 PKM0-16 DILM7 DEX-LN3-010 DE51-LZ3-011-V4 DEX-LM3-008
DV51-322-2K2 2.2 11 14 PKM0-20 DILM7 DEX-LN3-016 DE51-LZ3-020-V4 DEX-LM3-011
DV51-320-4K0 4 17.5 22 PKZM0-32 DILM17 DEX-LN3-025 – 2) DEX-LM3-035
DV51-320-5K5 5.5 24 30 PKZM0-40 DILM17 DEX-LN3-040 – 2) DEX-LM3-035
DV51-320-7K5 7.5 32 40 PKZM0-50 DILM25 DEX-LN3-040 – 2) DEX-LM3-035
Frequency inverter DV51 Three-phase
power supply (400 V AC)
DV51-340-037 0.37 1.5 2 PKM0-4 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-340-075 0.75 2.5 3.3 PKM0-6,3 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-340-1K5 1.5 3.8 5 PKM0-10 DILM7 DEX-LN3-004 DE51-LZ3-007-V4 DEX-LM3-005
DV51-340-2K2 2.2 5.5 7 PKM0-10 DILM7 DEX-LN3-006 DE51-LZ3-007-V4 DEX-LM3-008
DV51-340-3K0 3 7.8 10 PKM0-16 DILM7 DEX-LN3-010 DE51-LZ3-011-V4 DEX-LM3-008
DV51-340-4K0 4 8.6 11 PKM0-16 DILM7 DEX-LN3-010 DE51-LZ3-011-V4 DEX-LM3-011
DV51-340-5K5 5.5 13 16.5 PKM0-20 DILM7 DEX-LN3-016 DE51-LZ3-020-V4 DEX-LM3-016
DV51-340-7K5 7.5 16 20 PKM0-25 DILM17 DEX-LN3-025 DE51-LZ3-020-V4 DEX-LM3-016
Notes: 1)Mains chokes reduce the line currents by up to 30 % and extend the frequency inverters’ lifespan.
2)No device assigned yet.
3)Where single-phase frequency inverters are used on mains without mains choke (for example with reactive-power compensation equipment or UPS),
current peaks can occur when the mains contactor is switched on, and these can cause the FAZ-B… to trip prematurely. Remedy: fit a mains reactor
upstream or use a FAZ-C…
Line protection with FAZ, PKM or PKZM (PKZM0 can be used instead of PKM0) a section 8 or 16
DIL mains contactors a section 5
Main chokes DEX-LN… a page 15/36
Motor chokes DEX-LM3-… a page 15/37
SFB400/… sine-wave filters please enquire
15/14 Engineering
Connection example
DV51 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Terminal 5: RST = Reset, can be configured as thermistor input with
Block diagram DV51 parameter C005.
Terminal 6: 2CH = Second parameter set
In their default configuration, the DV51 vector frequency inverters can be used at
their assigned supply voltage and motor rating (four-pole, three-phase Terminal 11: FA1 = Frequency arrival, type 1 (output frequency actual value
Vector frequency inverters
asynchronous motor) without any parameter changes. Their acceleration and = reference input)
deceleration times are set to 15 seconds. The control signal inputs and outputs Terminal 12: RUN = Running
have the following assigned functions:
Terminals K11- Relay, fault signal (K11-K14 ready for operation)
Frequency inverters
1 +24 V
L N PE
FWD
REV
2CH
3
FF2
FF1
L1 L2 L3 PE 6 4 3 2 1 P24 CM2
RJ 45
ModBus
+
L+ –
DC+
RBr DC–
BR –
+
0...10 V
+10 V
0...10 V
4...20 mA
0V
RUN
FA1
*
M e
i
3~
RST
Actuation
Frequency inverters
1 2 OPE
RBUS RBUS
RBUS 1 2
1 2
SN
OFF 5
OFF
Host computer OFF
Q1
S1 POWER
ALARM 1 2
OPE
RBUS
POWER
ALARM 1 2
OPE
RBUS POWER
ALARM 1 2
OPE
RBUS
6 5 6 5 6 5
6 5 6 5 6 5
S2 Q11
1 2 32
Host
computer
Q11
M1 M2 Mn
Wiring
3 h 400 V, 50/60 Hz
L1
L2
L3
PE
Q1
PE
I I I
Q11
L1 L2 L3
PE
K1
L1 L2 L3 PE
FWD
M1 M
3~
e
15/16 System overview
Frequency inverters
DF6 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Vector frequency inverters
1
Frequency inverters
A
B
C
6789 D 6
AB
45
CD
23
E F 01
TM1
2
SEQ
CMB
CMB
TM2
ALARM
PRG
POWER
RUN
5
RMT
READ
COPY
COPY
MNT
PRG
ENTER
FWD
REV
Communication modules 6
PROFIBUS DP interface
Encoder interfacing assembly
a page 15/34
Description 15/17
Frequency inverter
http://catalog.moeller.net Moeller HPL0211-2007/2008 DF6
The DF6 frequency inverters provide economic speed control of three-phase motors Comprehensive protective functions guarantee safe operation and protect
in standard applications with square-law load characteristics (pumps, fans). frequency inverters and motors:
The assigned performance range for four-pole three-phase asynchronous motors • Overcurrent, earth fault
ranges from 11 kW to 132 kW at 400 V. • Overload, electronic motor protection
The DF6 units can be used as stand-alone drives or incorporated in automation • Overtemperature
systems. Their U/f(voltage/frequency) characteristic control allows their use in a • Overvoltage, undervoltage
broad range of applications in pump, fan, heating and air conditioning systems as • Phase failure
well as all areas of process engineering with flow control.
Two parameter sets with a wide range of functions:
Features • PID controller
• Automatic energy saving mode
• Compact construction • Motor synchronization and flying restart circuit
• Plug-in keypad (external installation possible) with four-character seven- • User macro storage
segment display, six function keys and a setpoint value potentiometer • Automatic restart after a power failure
• RS 485 and RS 422 serial interface • Electronic motor potentiometer function
• Six digital inputs (24 V DC) • 16 fixed frequencies
• 3 analog inputs (0 to +10 V, g10 V, 4 to 20 mA) • Min./max. frequency limitation
• Three relays (a changeover contact, two make contacts: 24 V DC/230 V AC)
• Thermistor input Documentation
• Bus interface (PROFIBUS DP) can be integrated.
• Global standards conforming to CE, UL, cUL, CSA and cTick
• Each DF6 vector frequency inverter is supplied with installation instructions and
Note: a CD.
The DF6-340-11K and DF6-340-15K frequency inverters have an integrated braking • The AWA contains a short description with illustrations and information about
chopper and allow direct connection to the braking resistors DE4-BR1-…. For more correct handling, installation and electrical connection of the device. The
than 15 kW the braking device DE4-BU4-1 is necessary for actuating the braking information supplied is printed in seven languages (English, Chinese, French,
resistors. German, Italian, Russian, and Spanish).
• The CD contains a detailed manual (at least English, German) and configuration
software with help text.
• Documentation and parameterization software are also available for download
from the Internet:www.moeller.net/support
Note:
The software on the CD can be run on PCs with the current Windows operating
systems (from 98 to XP).
For connecting a PC (RS 232) to a DF6 frequency inverter (RS 422), you will need the
DEX-CBL-2M0-PC connection cable.
15/18 Ordering
DF6 frequency inverter
DF6 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Rated voltage Max. rated Rated power for Part no. Price Std. pack
operational current motors Article no. see price list
Vector frequency inverters
Ue Ie at 400 V 3-phase AC
Frequency inverters
V A P
kW
37 18.5 DF6-340-18K5
231386
43 22 DF6-340-22K
231387
57 30 DF6-340-30K
231388
70 37 DF6-340-37K
231389
85 45 DF6-340-45K
231390
105 55 DF6-340-55K
231391
135 75 DF6-340-75K
231392
160 90 DF6-340-90K
231393
195 110 DF6-340-110K
231394
230 132 DF6-340-132K
231395
Notes Rated operational current with a switching frequency of 5 kHz and an ambient temperature of +40 °C.
Engineering 15/19
Assigned switching and protective elements
http://catalog.moeller.net Moeller HPL0211-2007/2008 DF6
Frequency inverters
filter fuse 4) suppression filter
P Ie IN
kW A A
Frequency inverter DF6
Three-phase power supply (400 V AC)
DF6-340-11K 11 22 24 PKM0-25 2) DILM17 DEX-LN3-025 DE6-LZ3-032-V4 DEX-LM3-035
DF6-340-15K 15 29 32 PKZM4-40 DILM17 DEX-LN3-040 DE6-LZ3-032-V4 DEX-LM3-035
DF6-340-18K5 18.5 37 41 PKZM4-50 DILM17 DEX-LN3-040 DE6-LZ3-064-V4 DEX-LM3-050
DF6-340-22K 22 43 47 PKZM4-50 DILM25 DEX-LN3-050 DE6-LZ3-064-V4 DEX-LM3-050
DF6-340-30K 30 57 63 PKZM4-63 DILM40 DEX-LN3-060 DE6-LZ3-064-V4 DEX-LM3-063
DF6-340-37K 37 70 77 NZM...1-S80 2) DILM50 DEX-LN3-080 DE6-LZ3-080-V4 DEX-LM3-080
DF6-340-45K 45 85 94 NZM...1-S100 2) DILM65 DEX-LN3-100 DE6-LZ3-115-V4 DEX-LM3-100
DF6-340-55K 55 105 116 NZM...1-S125 2) DILM80 DEX-LN3-120 DE6-LZ3-115-V4 DEX-LM3-150
DF6-340-75K 75 135 149 NZM...1-S160 2) DILM115 DEX-LN3-160 DE6-LZ3-150-V4 DEX-LM3-150
DF6-340-90K 90 160 176 NZM...2-S200 2) DILM150 DEX-LN3-1605) DE6-LZ3-220-V4 DEX-LM3-180
DF6-340-110K 110 195 215 NZM...3-ME220 3) DILM185 DEX-LN3-200 DE6-LZ3-220-V4 DEX-LM3-220
DF6-340-132K 132 230 253 NZM...3-ME350 3) DILM185 DEX-LN3-250 DE6-LZ3-260-V4 DEX-LM3-260
Notes 1) Mains chokes reduce the harmonic currents by up to 30 % and extend the frequency inverters’ lifespan.
2) Short-circuit protection for mounting in control panel (no overload release required).
3) Applications without electronic overload release: set I = infinite.
r
4) Switching capacity (kA) according to power supply rating.
5) At continuous, 100 percent motor load, the DEX-LN3-200 must be used here.
functions:
Frequency inverters
RS 485 SN
SN
RP
SP
Terminal 2: AT = change over to analog input OI
RJ 45
RS 422
O2
Terminal 4: FF1 = Fixed frequency 1
Terminal 5: REV = Anticlockwise rotating field
L
0V enable (Reverse)
Terminal FW: FWD = Clockwise rotating field
enable (Forward)
OI
4...20 mA
Terminal FM: Output frequency (PWM signal)
O
0...10 V Terminal AMI: Output frequency (analog signal
4...20 mA)
Terminal AM: Output frequency (analog signal
+
H
–
+10 V
0...10 V)
Terminal 11: FA1 = frequency reaches set point
AM
4...20 mA reached
Terminal K33-K34: Relay, RUN, in operation
Note:
FM
PLC CM1
P24
+
–
FW
FWD
PE K12 K14 K11 K23 K24 K33 K34
K3
5
REV
4
FF1
K2
3
FF2
2
AT
1
RST
K1
e
3 AC 400 V, 50/60 Hz
PE
L3
3~
L2
M
V
L1
U
DC+
BR*
DC–
L+
RBr
System overview 15/21
Vector frequency inverters
http://catalog.moeller.net Moeller HPL0211-2007/2008 DV6
Frequency inverters
A
B
C
6789 D 6
AB
45
CD
23
E F 01
TM1
2
SEQ
CMB
CMB
TM2
ALARM
PRG
POWER
RUN
5
RMT
READ
COPY
COPY
MNT
PRG
ENTER
FWD
REV
Communication modules 6
PROFIBUS DP interface
Encoder interfacing assembly
a page 15/34
15/22 Description
Vector frequency inverters
Moeller HPL0211-2007/2008 http://catalog.moeller.net
Vector frequency inverters
Frequency inverters
Application Function
The DV6 is the most powerful vector control frequency inverter of its class, with Comprehensive protective functions guarantee safe operation and protect
more than 200 % starting torque and virtually full static torque without feedback frequency inverters and motors:
(sensorless). It guarantees the highest levels of smooth operation and is particularly • Overcurrent, earth fault
suited to highly-dynamic applications in the packaging, printing and textile • Overload, electronic motor protection
industries, for machine tools, and in material handling with elevator systems and • Overtemperature
hoists. • Overvoltage, undervoltage
The DV6 can be used as a stand-alone drive or incorporated in complex automation • Phase failure
systems. • Configurable delay with emergency-off and voltage failure
The assigned performance range for four-pole three-phase asynchronous motors
ranges from 0.75 kW to 132 kW at 400 V. Three parameter sets with a wide range of functions:
• P/PI controller and PID closed-loop controller
Features • Automatic voltage regulation
• Motor synchronization and flying restart circuit
• Sensorless Vector Control (closed/open loop) • Rapid stop function
• Motor autotuning (online/offline) • User macro storage
• Built-in braking transistor (DV6-340-075 to DV6-340-11K) • Electronic motor potentiometer function
• 32-bit processor • 16 fixed frequencies (bit/binary)
• Plug-in keypad (external installation possible) with four-character seven- • Min./max. frequency limitation
segment display, six function keys and a setpoint value potentiometer
• RS 485 and RS 422 serial interface Documentation
• Nine digital inputs (24 V DC)
• 3 analog inputs (0 to +10 V, g10 V, 4 to 20 mA)
• Thermistor input • Each vector frequency inverter DV6 is supplied with an installation instruction
• Five digital outputs (24 V DC) (AWA) and a CD.
• Two analog outputs (0/+10 V, 4 – 20 mA) • The AWA contains a short description with illustrations and information about
• Relay (changeover contact: 24 V DC/230 V AC) correct handling, installation and electrical connection of the device. The
• Bus interface (PROFIBUS DP) can be integrated. information supplied is printed in seven languages (English, Chinese, French,
• Global standards conforming to CE, UL, cUL, CSA and cTick German, Italian, Russian, and Spanish).
• The CD contains a detailed manual and configuration software with help text.
Note: • Documentation and parameterisation software is also available for download
The DV6-340-075 to DV6-340-15K frequency inverters have an integrated braking from the Internet:www.moeller.net/support
chopper and allow direct connection to the braking resistors DE4-BR1-…. Over
15 KW the DE4-BU4-1 braking unit is necessary to actuate the braking resistors. Note:
The software on the CD can be run on PCs with the current Windows operating
systems (from 98 to XP).
For connecting a PC (RS 232) to a DV6 frequency inverter (RS 422), you will need the
DEX-CBL-2M0-PC connection cable.
Ordering 15/23
Vector frequency inverter
http://catalog.moeller.net Moeller HPL0211-2007/2008 DV6
Rated voltage Max. rated Rated power for Part no. Price Std. pack
operational current motors Article no. see price list
Frequency inverters
V A P
kW
32 15 DV6-340-15K
231403
38 18.5 DV6-340-18K5
231404
48 22 DV6-340-22K
231405
58 30 DV6-340-30K
231406
75 37 DV6-340-37K
231407
90 45 DV6-340-45K
231408
110 55 DV6-340-55K
231409
149 75 DV6-340-75K
231410
176 90 DV6-340-90K
231411
217 110 DV6-340-110K
231412
260 132 DV6-340-132K
231413
Notes 1) Rated operational current at an operating frequency of 5 kHz and an ambient temperature of +40°C.
15/24 Engineering
Assigned switching and protective elements
DV6 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Motor Frequency inverters Power supply Mains Mains reactor1) Radio Motor reactor
contactor interference
suppression filter
Assigned Rated Mains current
Vector frequency inverters
filter
P Ie IN
kW A A
Frequency inverters DV6
Three-phase power supply (400 V AC)
DV6-340-075 0.75 2.5 2.8 PKM0-6,3 2) DILM7 DEX-LN3-004 DE6-LZ3-013-V4 DEX-LM3-005
DV6-340-1K5 1.5 3.8 4.2 PKM0-6,3 2) DILM7 DEX-LN3-004 DE6-LZ3-013-V4 DEX-LM3-005
DV6-340-2K2 2.2 5.3 5.8 PKM0-10 2) DILM7 DEX-LN3-006 DE6-LZ3-013-V4 DEX-LM3-008
DV6-340-4K0 4 8.6 9.5 PKM0-10 2) DILM7 DEX-LN3-010 DE6-LZ3-013-V4 DEX-LM3-011
DV6-340-5K5 5.5 12 13 PKM0-16 2) DILM7 DEX-LN3-016 DE6-LZ3-013-V4 DEX-LM3-016
DV6-340-7K5 7.5 16 18 PKM0-20 2) DILM7 DEX-LN3-025 DE6-LZ3-032-V4 DEX-LM3-016
DV6-340-11K 11 23 25 PKZM4-40 DILM17 DEX-LN3-025 DE6-LZ3-032-V4 DEX-LM3-035
DV6-340-15K 15 32 35 PKZM4-40 DILM17 DEX-LN3-040 DE6-LZ3-064-V4 DEX-LM3-035
DV6-340-18K5 18.5 38 42 PKZM4-50 DILM25 DEX-LN3-040 DE6-LZ3-064-V4 DEX-LM3-035
DV6-340-22K 22 48 53 PKZM4-58 DILM40 DEX-LN3-050 DE6-LZ3-064-V4 DEX-LM3-050
DV6-340-30K 30 58 63 NZM...1-S80 2) DILM40 DEX-LN3-060 DE6-LZ3-080-V4 DEX-LM3-063
DV6-340-37K 37 75 83 NZM...1-S100 2) DILM50 DEX-LN3-080 DE6-LZ3-115-V4 DEX-LM3-080
DV6-340-45K 45 90 99 NZM...1-S100 2) DILM65 DEX-LN3-100 DE6-LZ3-115-V4 DEX-LM3-100
DV6-340-55K 55 110 121 NZM...1-S125 2) DILM95 DEX-LN3-120 DE6-LZ3-125-V4 DEX-LM3-150
DV6-340-75K 75 149 164 NZM...2-S200 2)5) DILM115 DEX-LN3-160 DE6-LZ3-220-V4 DEX-LM3-150
DV6-340-90K 90 176 194 NZM...2-S200 2) DILM150 DEX-LN3-200 DE6-LZ3-220-V4 DEX-LM3-180
DV6-340-110K 110 217 239 NZM...3-ME350 3) DILM185 DEX-LN3-250 DE6-LZ3-260-V4 DEX-LM3-220
DV6-340-132K 132 260 286 NZM...3-ME350 3) DILM185 DEX-LN3-300 DE6-LZ3-260-V4 DEX-LM3-260
Notes 1) Mains chokes reduce the harmonic currents by up to 30 % and extend the frequency inverters’ lifespan.
2) Short-circuit protection for mounting in control panel (no overload release required).
3) Applications without electronic overload release: set I = infinite.
r
4) Switching capacity (kA) according to power supply rating.
5) When using with DEX-LN3-160 mains choke, you can use NZM...2-S160.
Frequency inverters
Terminal 1: RST = Reset
RS 485 SN
SN
RP
SP
Terminal 2: AT = change over to analog input
OI
RJ 45
RS 422
O2
–10 V...+10 V
Terminal 3: JOG = inching duty
Terminal 4: FRS = free run stop of motor
L
0V (controller inhibit)
Terminal 5: 2CH = Second parameter set
Terminal 6: FF2 = Fixed frequency 2
OI
4...20 mA
Terminal 7: FF1 = Fixed frequency 1
O
0...10 V
Terminal 8: REV = Anticlockwise rotating field
enable (Reverse)
Terminal FW: FWD = Clockwise rotating field
+
H
–
+10 V
enable (Forward)
Terminal FM: Output frequency (PWM signal)
AM
4...20 mA
0...10 V)
Terminal 11: FA1 = frequency reaches set point
Terminal 12: RUN = Running
FM
PTC signal
i
for operation)
PLC CM1
P24
+
–
Note:
Terminal BR*: Brake resistor; for DV6-320-11K
and DV6-340-075K to DV6-340-
15K only
FW
FWD
CM2
P24
REV
7
FF1
+24 V
15
6
FF2 IP
14
5
2CH QTQ
13
4
FRS OL
12
3
JOG RUN
11
FA1
2
AT
1
RST
PE K12 K14 K11
RO TO
J51
K1
e
3
PE
L3
3~
L2
M
V
L1
U
DC+
BR*
DC–
L+
RBr
15/26 Description
Keypads
DEX-KEY6..., DEX-KEY-10 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Vector frequency inverters
Frequency inverters
DEX-KEY-6 DEX-KEY-10
DEX-KEY-61 External keypad with configuration memory
Application Application
• Operating unit with set point potentiometer (valid for DEX-KEY 6 only) Optional keypad with non-volatile configuration memory for the DF51, DV51, DF6
• Remote keypad for the DF51, DF6, DV51 and DV6 frequency inverters. and DV6 frequency inverters as well as the RA-SP speed control unit.
• Instead of the LED display, these keypads can be slotted into the DV51 DEX-KEY-10 can be mounted in a control panel enclosure or fitted instead of the
frequency inverters or, with adapter DEV51-MNT-K60, snapped onto interface standard keypad of the DF6 and DV6 frequency inverters.
modules DE51-NET-CAN and DE51-NET-DP. The frequency inverter is connected via the RJ 45 interface.
Note: Note:
For remote flush mounting in an enclosure (e.g. control panel door), mounting frame The connectors must be connected and disconnected only under no-voltage
DEX-MNT-K6 and connection cable DEX-CBL-...-ICS or DNW-PC... are required. conditions.
For external mounting, a connection cable with RJ 45 plugs (DEX-CBL-...-ICS or
Features DNW-PC respectively) is required.
DEV51-NET-TC DEV51-MNT-K60
T adapter for RS 485/Modbus connection Adapter for the operating unit DEX-KEY 6…
DEX-CBL-…-ICS DEX-MNT-K6
DWN-PC-… Mounting frame for the operating unit DEX-KEY 6…
Connecting cable with RS 45 plug
Application
DEX-CBL-2M0-PC
Interface converter with connection cable • Adapter DEV51-MNT-K60 allows the installation and connection of keypad
DEX-KEY-6… in combination with a fieldbus module DE51-NET-CAN or DE51-
NET-DP and DV51 frequency inverters.
Application • Mounting frame DEX-MNT-K6 allows the seperate mounting of DEX-KEY-6 and
DEX-KEY61 keypads in an enclosure (e.g. control panel door)
Connection and extension of the system interface for frequency inverters DF51, DF6,
DV51 and DV6, and speed control unit RA-SP.
Features
Features Adapter DV51-MNT-K60 and mounting frame DEX-MNT-K6 are supplied with all
accessories required for application, such as self-adhesive rubber seals and
Prefabricated for immediate use. connectors.
Functions Functions
• The DEV51-NET-TC T-adapter doubles the RJ 45 connector of the DV51 • Mounting frame and cover are purely mechanical components without separate
(T piece). It is required to connect multiple DV51 frequency inverters as slaves functionality.
to a system with the open RS 485 and Modbus RTU communication protocol. The mounting frame can be fitted as follows:
• The connection cable allows the point-to-point connection of the RJ-45 slot. • A: in a control panel door or enclosure with standard punching tool (square
• Interface converter DEX-CLB-2MO-PC allows a direct point-to-point connection 67 x 67 mm)
of a PC with 9-pin RS232 (Sub-D) socket to the RJ-45 interface (RS 422/RS 485) • B: Flush mounting in a water-resistant enclosure (IP 54, NEMA 4). Permissible
of a DF51, DF6, DV51 or DV6 frequency inverter or on RA-SP. only with DEX-KEY-61 keypad without potentiometer.
Documentation
Installation and mounting are described in the installation instructions of keypad
DEX-KEY-6... They are described in the XSoft manual (AWB2700-1437GB). The
documentation is contained on the CD supplied with each frequency inverter.
The documentation is also available on the Internet:
www.moeller.net/support
15/28 Description
Interface cards
DE51-NET-DP, DE51-NET-CAN Moeller HPL0211-2007/2008 http://catalog.moeller.net
Vector frequency inverters
Frequency inverters
POWER
ALARM
I O
PRG
ENTER
DE51-NET-DP DE51-NET-CAN
Interface for connecting to PROFIBUS DP • Communications protocol: DS-301 V4.01
• Device profile: DS-402 V2.0
• Bus address: 1 to 127
DE51-NET-CAN • Max. cable length: 5000 m
Interface for connecting to CANopen • Data transfer rate: 10 kbit/s to 1 Mbit/s, depending on cable length and amplifier
• Isolated interface
• address and baud rate adjustable through DIP switches
DEX-MNT-NET
• Five status LEDs
Mounting frame for the external arrangement of interface modules • Clip-on to DV51, remote connection to DF51 (connection cable DEX-CBL-…-ICS
required).
Application
DE51-NET-DP
DE51-NET-… allows the connection of DF51 and DV51 series frequency inverters as • Network topology: PROFIBUS DP line (DIN 19245 part 1 and 3)
slaves to systems with standardised field bus (CANopen, PROFIBUS-DP). • DRIVECOM profile drive control technology 20
On the DV51 the interface modules can be front-mounted; on the DF51, they are • Bus address: 1 to 127
mounted separately in mounting frame DEX-MNT-NET. A prefabricated connecting • max. cable length: 10 000 m
cable (DEX-CBL... or DWN-PC...) is required to connect the DF51. • Data transfer rate: 93.7 kbit/s to 12 Mbit/s, depending on cable length and
amplifier
• Isolated interface
• address and baud rate adjustable through DIP switches
• Five status LEDs
• Clip-on to DV51, remote connection to DF51 (connection cable DEX-CBL-…-ICS
required).
Documentation
Installation instructions are supplied with each module. Further documentation for
this module is also available on the Internet at:
www.moeller.net/support.
Description 15/29
Interface cards
http://catalog.moeller.net Moeller HPL0211-2007/2008 DE6-NET-DP, DE6-IOM-ENC
DE6-NET-DP DE6-IOM-ENC
Interface for PROFIBUS DP networks Encoder card for DV6 frequency inverters
Application Application
The DE6-IOM-ENC card can be used in conjunction with the DV6 vector frequency
Features
inverters and enables speed control of three-phase motors with a directly connected
encoder.
• Installation in slot 2 of DF6 or DV6 frequency inverter Further application features are:
• Intelligent modules with their own processor and with potential isolation • Synchro control and ratio control
• RS 485 interface (9-pin, D-SUB socket) • Motor standstill recognition
• Device address set with two rotary switches • Torque regulation
• Data transfer: 9.6 Kbit/s (at 1,200 m) to 12 Mbit/s (at 100 m) with automatic
baud rate detection
• PROFIDrive profile, drive engineering version 2 Features
• Output voltage (power supply) for the encoder: 5 V DC, 150 mA.
• Max. number of input pulses: 65,000
• Input: two TTL signals offset by 90° (5 V DC, RS 422 standard) with zero pulse
and inverted signals.
EAP
EAN
EBP
M
EBN
EZP
EZN
90˚
Documentation
DEX-LN1... DEX-LM3...
Mains chokes, single-phase Motor chokes, three-phase
DEX-LN3... Application
Mains chokes, three-phase
Motor chokes are used on the output of the frequency inverters in series with the
motor.
Application
Mains chokes – also called commutating chokes – are connected in series on the Function
mains input side of electronic equipment e.g. frequency inverters.
Motor chokes reduce the slew rate of the output voltage (/ < 500 V/ms) as well as
motor noise and heating.
Function The use of motor chokes enables the permissible motor cable lengths to be extended
up to 200 m.
Mains chokes limit the inrush current and dampen current harmonics and any With parallel operation of several motors from the output of a frequency inverter the
additional current peaks. By dampening the harmonic currents, the r.m.s value of use of motor chokes is recommended. They reduce the higher capacitive reactive
the input current can be reduced by up to 30 %. In addition, they allow the often currents.
mandatory short-circuit voltage (k value) of about 4 % to the mains.
Mains chokes extend components’ lifespan (rectifier diodes, DC link capacitors) on
equipment with input-side DC link (frequency inverters, UPS). Features
The motor chokes are vacuum-impregnated for low-noise operation. They offer low-
Features fatigue, magnetically and metallically neutral air-gap bypasses.
Because of their flux distribution, the clearance to metal parts and neighbouring
The mains chokes are vacuum-impregnated for low-noise operation. They offer low- components must be at least 50 mm.
fatigue, magnetically and metallically neutral air-gap bypasses.
Because of their flux distribution, the clearance to metal parts and neighbouring
components must be at least 50 mm. Documentation
Installation instructions are supplied with each choke. The documentation is also
available on the Internet:
www.moeller.net/support
Description 15/31
Brake units, brake resistances
http://catalog.moeller.net Moeller HPL0211-2007/2008 DE4-BU4-1, DE4-BR1...
Application Application
Braking units with assigned braking resistors are used for rapid braking of An external braking resistor is required when braking large moments of inertia or
frequency-controlled three-phase drives. when operating in extended regenerative mode. It converts the mechanical braking
With its integrated synchronization, the DE4-BU4-1 allows several braking units to energy to heat.
be operated in parallel, for example for large loads (lifting gear).
Function
Features
The integral braking transistor of the frequency inverter automatically diverts energy
• Braking transistor with automatic control (adjustable response value) to the connected braking resistor when the threshold value of the DC bus voltage is
• Braking resistors (DE4-BR1...) are not supplied with the device. The lowest exceeded. This prevents overvoltages in the DC link, which would otherwise cause
permissible resistance is: 18 Ω an “overvoltage” fault message and activate the pulse inhibitor of the frequency
• Synchronization for parallel operation of several DE4-BU... at high braking inverter. The drive coasts to a stop.
power.
• Continuous braking power up to 18 kW T1 2 1
• Maximum braking power 30 kW, with 15 s make time and 150 s pause time
Function i
With short braking times, the frequency controlled motor operates in regenerative RB
(oversynchronous) mode. In this mode, it feeds power into the frequency inverter’s T2
DC link, which results in an increased DC bus voltage. If the voltage exceeds the PE
permitted limit value, the frequency inverter control logic disables the frequency
inverter’s power inverter and the motor coasts to a stop.
If one or more braking units are connected in parallel to the internal DC link, the Features
recovered energy can be diverted through the assigned braking resistors, where it is
dissipated as heat. The resistors are built into a perforated sheet-metal enclosure and are fitted with an
overtemperature protection switch (230 V, 1A, AC-1). The enclosure is made from
galvanized perforated sheet metal, The enclosures are open at the bottom and fullfil
Documentation protection IP20 only when mounted.
By combining several resistances in series and/or parallel higher braking capacities
Installation instructions are supplied with each braking unit. The documentation is can be obtained.
also available on the Internet: The braking resistors can be directly connected to the brake chopper of the
www.moeller.net/support frequency inverter DV51, DF6-340-11K, DF6-340-15K, DV6-340-075…11K and the
braking unit DE4-BU4-1.
Documentation
Installation instructions are supplied with each braking unit. The documentation is
also available on the Internet:
www.moeller.net/support
15/32 Engineering
Connection examples
Moeller HPL0211-2007/2008 http://catalog.moeller.net
DV51
Vector frequency inverters
DE51-NET-CAN
DE51-NET...
Frequency inverters
POWER
ALARM
A POWER
RUN Hz ALARM
I O
PRG A
RUN
PRG I O
PRG
ENTER
PRG
ENTER
Hz
POWER
ALARM
DEX-CBL...
DWN-PC...
A
RUN
I O PRG
DE51-NET-CA
N
PRG
ENTER
a Keypad and bus connection in combination with b Bus connectionin combination with frequency c Side mounting of RFI filter
frequency inverter DV51 inverter
DEX-KEY-6...
POWER
Hz ALARM
RUN
I O
PRG
PRG
ENTER
DEX-MNT-K6
DEX-CBL...ICS
DWN-PC... DF6, DV6
DF51, DV51
d Footprint application of RFI filter e Flush mounting of keypad in a control panel door
DE4-BR1-... DV6-340
DF6-340
DE4-BU4-1
DC+ +UG
DC– –UG
Frequency inverters
LCD keypad with potentiometer. Flush mounting DF51-… DEX-KEY-6 1 off
POWER
Hz
A
ALARM
in DV51 frequency inverters possible. For DF6-... 289943
I O
RUN
PRG
separate application, a connection cable (DEX- DV51-...
PRG
ENTER
CBL-…ICS, DNW-PC…) is required. DV6-...
DEX-KEY-10
LCD keypad with non-volatile memory. Flush DF51-... DEX-KEY-10 1 off
mounting in DF6 and DV6 frequency inverters DF6-... 231421
ALARM
PRG
POWER
RUN possible. For remote operation, a connection DV51-...
cable (DEX-CBL-…ICS, DNW-PC...) is required. DV6-...
RA-SP
RMT READ COPY
FWD
REV
Interface modules
T adapter DEV51-NET-TC
T adapter. Flush mounting in DV51 frequency DV51-… DEV51-NET-TC 1 off
POWER
ALARM
1 2
OPE
RBUS inverters possible. Interface (T connector) with 289948
RUN
OFF RJ45 sockets for the built-in RS 485/Modbus RTU
interface.
Connection cables
Interface converter RS332/RJ45 with connection DF51-... DEX-CBL-2M0-PC 1 off
cable (2 m) with RJ45 plug and 9-pin Sub-D plug DF6-... 233184
DV51-...
DV6-...
RA-SP
Connection cables
Connection cable (1.0 m) with RJ-45 plugs DEX-KEY-10 DEX-CBL-1M0-ICS 1 off
DEX-KEY-6 232375
Connection cable (3.0 m) with RJ-45 plugs DEX-KEY-61 DEX-CBL-3M0-ICS 1 off
DEV51-NET-TC 232376
DE51-NET-DP
Connection cable (0.5 m) with RJ 45 plug DE51-NET-CAN DNW-PC/0050/RJ45/RJ45/5E/CSUTP/GR 10 off
237146
Connection cable (1.0 m) with RJ 45 plug DNW-PC/0100/RJ45/RJ45/5E/CSUTP/GR 10 off
237147
Connection cable (1.0 m) with RJ 45 plug DNW-PC/0300/RJ45/RJ45/5E/CSUTP/GR 1 off
237154
15/34 Ordering
Interface modules
DE51-NET-…, DE6-… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Interface modules
Frequency inverters
Mounting frames
Mounting frame with connection cable for the external DF51... DEX-MNT-NET 1 off
arrangement of interface modules DE51-NET-CAN and DE51- DV51... 106265
NET-DP
Mounting frame for LCD keypads DEX-KEY-6… on interface D51-NET… DEV51-MNT-K60 1 off
modules DE51-NET-CAN and DE51-NET-DP for vector frequency 292382
inverters DV51…
Ordering 15/35
Radio interference suppression filter
http://catalog.moeller.net Moeller HPL0211-2007/2008 DE... - LZ...
Rated voltage Assigned frequency inverter Part no. Price Std. pack Notes
Article no. see price list
Ue DF DV
Frequency inverters
Radio interference suppression filter
1 AC 250 V DF51-322-025 DV51-322-025 DE51-LZ1-007-V2 1 off The radio interference
DF51-322-037 DV51-322-037 289960 suppression filters can
DF51-322-055 DV51-322-055 be side- or footprint
1 AC 250 V DF51-322-075 DV51-322-075 DE51-LZ1-012-V2 mounted to the
DF51-322-1K1 DV51-322-1K1 289961 frequency inverter.
1 AC 250 V DF51-322-1K5 DV51-322-1K5 DE51-LZ1-024-V2
DF51-322-2K2 DV51-322-2K2 289962
3 AC 480 V DF51-340-037 DV51-340-037 DE51-LZ3-007-V4
DF51-340-075 DV51-340-075 289963
DF51-340-1K5 DV51-340-1K5
DF51-340-2K2 DV51-340-2K2
3 AC 480 V DF51-340-3K0 DV51-340-3K0 DE51-LZ3-011-V4
DF51-340-4K0 DV51-340-4K0 289964
3 AC 480 V DF51-320-4K0 DV51-320-4K0 DE51-LZ3-020-V4
DF51-340-5K5 DV51-340-5K5 289965
DF51-340-7K5 DV51-340-7K5
3 AC 342…528 V g 0 % DV6-340-075 DE6-LZ3-013-V4
DV6-340-1K5 232358
DV6-340-2K2
DV6-340-4K0
DV6-340-5K5
3 AC 342…528 V g 0 % DF6-340-11K DE6-LZ3-032-V4
DF6-340-15K 232359
3 AC 342…528 V g 0 % DF6-340-18K5 DV6-340-15K DE6-LZ3-064-V4
DF6-340-22K DV6-340-18K5 232360
DF6-340-30K DV6-340-22K
3 AC 342…528 V g 0 % DF6-340-37K DV6-340-30K DE6-LZ3-080-V4 Only side mounting
232361 beside frequency
3 AC 342…528 V g 0 % DF6-340-45K DV6-340-37K DE6-LZ3-115-V4 inverter possible.
DF6-340-55K DV6-340-45K 232362
3 AC 342…528 V g 0 % DV6-340-55K DE6-LZ3-125-V4
232363
3 AC 342…528 V g 0 % DF6-340-75K DE6-LZ3-150-V4
233181
3 AC 342…528 V g 0 % DF6-340-90K DV6-340-75K DE6-LZ3-220-V4
DF6-340-110K DV6-340-90K 233182
3 AC 342…528 V g 0 % DF6-340-132K DV6-340-110K DE6-LZ3-260-V4
DV6-340-132K 233183
15/36 Ordering
Mains chokes
DEX-LN... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Inductance Rated current Maximum Part no. Price Std. pack Notes
power loss Article no. see price list
Vector frequency inverters
L I Pv
Frequency inverters
mH A W
Frequency inverters
2 5 24 DEX-LM3-005 1 off Motor reactors
269538 reduce the du/dt
4.1 8 54 DEX-LM3-008 value of the output
269539 voltage and
3 11 71 DEX-LM3-011 therefore the motor
269541 noise and heating.
Motor chokes have
1.5 16 78 DEX-LM3-016
larger dimension
269542
than mains chokes
1 35 116 DEX-LM3-035 with the same rated
269543 current.
0.6 50 168 DEX-LM3-050
269544
0.5 63 193 DEX-LM3-063
269545
0.5 80 206 DEX-LM3-080
269546
0.45 100 294 DEX-LM3-100
269547
0.35 150 424 DEX-LM3-150
269548
0.3 180 439 DEX-LM3-180
269549
0.2 220 517 DEX-LM3-220
269560
0.15 260 520 DEX-LM3-260
269561
Notes The rating applies for an operating time of 15 s and an off period of 150 s.
Impedance Rated braking Peak braking Part no. Price Std. pack Notes
power power Article no. see price list
R Pnom PPeak
O W W
DE4-BR1... braking resistors
82 245 1700 DE4-BR1-082-245 1 off The braking resistors are designed for a load
219485 cycle of:
100 200 1400 DE4-BR1-100-200 • max. 15 s braking at peak braking power
219489 • min. 150 s recovery time after braking
200 100 700 DE4-BR1-200-100 The resistors are built into a perforated sheet-
219490 metal enclosure and are fitted with an
overtemperature protection switch (230 V, 1A,
240 285 2000 DE4-BR1-240-285 AC-1).
219492 Enclosure: galvanized perforated brass, open
370 215 1500 DE4-BR1-370-215 bottom.
219494 Degree of protection IP20 is achieved only in
470 50 300 DE4-BR1-470-050 installed state.
219495
470 140 1000 DE4-BR1-470-140
219497
15/38 Technical Data Technical Data 15/39
Frequency inverters Frequency inverters
DF51 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net DF51
DF51-322-025 DF51-322-037 DF51-322-055 DF51-322-075 DF51-322-1K1 DF51-322-1K5 DF51-322-2K2 DF51-320-4K0 DF51-320-5K5 DF51-320-7K5
General
Heat dissipation with rated operational current Ie W 19 29 32 41 51 79 107 0 0 0
Vector frequency inverters
Frequency inverters
Power section
Rated operating voltage V AC 230 230 230 230 230 230 230 230 230 230
Rated voltage Ue V 1 AC 180…264 V g 0 % 1 AC 180…264 V 0 % 3 AC 180…264 V 0%
3 AC 180…264 V 0 % 3 AC 180…264 V 0 %
Supply frequency Hz 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %) 50/60 (47…63 0 %)
Mains current
i = 230 V AC monoph. A 3.1 5.8 6.7 9 11.2 17.5 24 – – –
i = 230 V AC triph. A 1.8 3.4 3.9 5.2 6.5 9.3 13 20 30 40
Alternative DC supply DC V DC 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0% 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0% 260…370 0% 260…370 0%
Modulation method sinusoidal pulse-width modulation (PWM), /f characteristic control sinusoidal pulse-width modulation (PWM), U/f characteristic control
Switching frequency 5 kHz, can be selected between 2 and 14 kHz 5 kHz, can be selected between 2 and 14 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0 to 50, max. 400 0 to 50, max. 400
Frequency resolution kHz 0.1 with digital setpoint values, maximum frequency/1000 with analog setpoint values 0.1 with digital setpoint values, maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C 10 K 0.01 % of maximum frequency for digital reference values, 0.2 % of maximum frequency for 0.01 % of maximum frequency for digital reference values, 0.2 % of maximum frequency for analog reference values
analog reference values
Max. rated operational current e A 1.4 2.6 3 4 5 7.1 10 15.9 24 32
Permissible overcurrent 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s
Torque during start From 6 Hz 100 % or higher with torque boost activated From 6 Hz 100 % or higher with torque boost activated
Apparent power at 240 V kVA 0.5 1 1.2 1.6 2 2.9 4.1 6.6 9.9 13.2
Standard operation at 150 % overload Assigned
motor rating (4-pole ASM)
230 V kW 0.25 0.37 0.55 0.75 1.1 1.5 2.2 4 5.5 7.5
240 V HP k m o m m
Control circuit
1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A 1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A inductive load, 3 A resistive load
inductive load, 3 A resistive load
Serial interface RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485
Control voltage
Output setpoint voltage V +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA
Output control voltage V +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA
Parameterization 1 parameter set (online/offline parameterization), parameter protection (programmable) 1 parameter set (online/offline parameterization), parameter protection (programmable)
Inputs
digital (parameters can be defined) 5 +24 V DC, configurable 5 +24 V DC, configurable
Analog Inputs Amount 2 0 to +10 V DC (input impedance 10 kO, 4 to 20 mA (load impedance 250 O), resolution 10 2 x 0 to +10 V DC (input impedance 10 kO, 4 to 20 mA (load impedance 250 O), resolution 10 bit
bit
Outputs
Digital 2 x 24 V DC transistor (open-collector, configurable) 2 x 24 V DC transistor (open-collector, configurable)
analog (parameters can be defined) 1 x 0 to +10 V DC, 1 mA (configurable), resolution 10 bit 1 x 0 to +10 V DC, 1 mA (configurable), resolution 10 bit
Terminal capacities
Notes
Ta is taken to be the temperature inside this enclosure or control panel.
All rating data of the power section is based on a switching frequency of 5 kHz (default setting)
and an ambient temperature of +40 °C, for operation of a four-pole three-phase asynchronous
motor.
15/40 Technical Data Technical Data 15/41
Frequency inverters Frequency inverters
DF51 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 DF51
General
Vector frequency inverters
Frequency inverters
Dimensions (W x H x D) mm 110 x 130 x 141 110 x 130 x 168 110 x 130 x 168 110 x 130 x 168 110 x 130 x 168 110 x 130 x 168 180 x 220 x 167 180 x 220 x 167
Weight kg 1.4 1.8 1.9 1.9 1.9 1.9 5.5 5.7
Power section
Rated operating voltage V AC 400 400 400 400 400 400 400 400
Rated voltage Ue V 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 %
Supply frequency Hz 50/60 (47…63 g 0 %) 50/60 (47…63 g 0 %)
Mains current
Ui = 3-phase, 400 V AC I A 2 3.3 5 7 10 11 16.5 20
Alternative DC supply UDC V DC 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 %
Modulation method sinusoidal pulse-width modulation (PWM), U/f characteristic control sinusoidal pulse-width modulation (PWM), U/f characteristic control
Switching frequency 5 kHz, can be selected between 2 and 14 kHz 5 kHz, can be selected between 2 and 14 kHz
Output voltage V 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue
Output frequency Hz 0 to 50, max. 400 0 to 50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C g 10 K g 0.01 % of maximum frequency for digital reference values, g 0.2 % of maximum frequency for analog g 0.01 % of maximum frequency for digital reference values, g 0.2 % of maximum frequency for analog reference values
reference values
Max. rated operational current Ie A 1.5 2.5 3.8 5.5 7.8 8.6 13 16
Permissible overcurrent 150 % for 60 s, every 150 % for 60 s, every 150 % for 60 s, every 150 % for 60 s, every 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s
600 s 600 s 600 s 600 s
Torque during start From 6 Hz 100 % or higher with torque boost activated From 6 Hz 100 % or higher with torque boost activated
Apparent power at 460 V kVA 1.1 1.9 2.9 4.2 6.2 6.6 10.3 12.7
Resistor R B at 100 % c.d.f.
400 V kW 0.37 0.75 1.5 2.2 3 4 5.5 7.5
460 V HP m 1 2 3 4 5 7m 10
Control circuit
Relay 1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A inductive 1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A inductive load, 3 A resistive load
load, 3 A resistive load
Serial interface RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485
Control voltage
Output setpoint voltage V +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA
Output control voltage V +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA
Parameterization 1 parameter set (online/offline parameterization), parameter protection (programmable) 1 parameter set (online/offline parameterization), parameter protection (programmable)
Inputs
digital (parameters can be defined) 5 x +24 V DC, configurable 5 x +24 V DC, configurable
Analog Inputs Amount 2 x 0 to +10 V DC (input impedance 10 kO, 4 to 20 mA (load impedance 250 O), resolution 10 bit 2 x 0 to +10 V DC (input impedance 10 kO, 4 to 20 mA (load impedance 250 O), resolution 10 bit
Outputs
Digital 2 x 24 V DC transistor (open-collector, configurable) 2 x 24 V DC transistor (open-collector, configurable)
analog (parameters can be defined) 1 x 0 to +10 V DC, 1 mA (configurable), resolution 10 bit 1 x 0 to +10 V DC, 1 mA (configurable), resolution 10 bit
Terminal capacities
Cable lengths
mm2 1.5 1.5 1.5 2.5 2.5 4 4 4
AWG 16 16 16 14 14 12 12 12
Relay connection
mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
AWG 6 6 6 6 6 6 6 6
Control circuit
mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
AWG 6 6 6 6 6 6 6 6
Notes If the frequency inverter is to be installed in an enclosure, control panel or similar housing, the ambient
temperature Ta is taken to be the temperature inside this enclosure or control panel.
All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and an
ambient temperature of +40 °C, for operation of a four-pole three-phase asynchronous motor.
15/42 Technical Data Technical Data
Vector frequency inverters Vector frequency inverters
DV51 DV51
DV51-322-025 DV51-322-037 DV51-322-055 DV51-322-075 DV51-322-1K1 DV51-322-1K5 DV51-322-2K2 DV51-320-4K0 DV51-320-5K5 DV51-320-7K5
General
Heat dissipation with rated operational current Ie W 21 26 29 41 55 90 105 0 0 0
Vector frequency inverters
Frequency inverters
Rated operating voltage V AC 230 230 230 230 230 230 230 230 230 230
Rated voltage e V 1 AC 180…264 V 0 % 1 AC 180…264 V 0 % 3 AC 180…264 V 0%
3 AC 180…264 V 0 % 3 AC 180…264 V 0 %
Supply frequency Hz 50/60 (47…63 0 %) 50/60 (47…63 0 %)
Mains current
i = 230 V AC monoph. A 3.5 5.8 6.7 9 11.2 17.5 24 – – –
i = 230 V AC triph. A 2 3.4 3.9 5.2 6.5 10 14 22 30 40
Alternative DC supply DC V DC 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0 % 260…370 0% 260…370 0%
Modulation method Sensorless vector control, pulse width modulation (PWM) Sensorless vector control, pulse width modulation (PWM)
Switching frequency 5 kHz, can be selected between 2 and 14 kHz 5 kHz, can be selected between 2 and 14 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0 to 50, max. 400 0 to 50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C 10 K 0.01 % of maximum frequency for digital reference values, 0.2 % of maximum frequency for 0.01 % of maximum frequency for digital reference values, 0.2 % of maximum frequency for analog reference values
analog reference values
230 V kW 0.25 0.37 0.55 0.75 1.1 1.5 2.2 4 5.5 7.5
240 V HP 1 1 2 3 5 7.5 10
Brake transistor
Switching threshold DC V DC 380 380 380 380 380 380 380 380 380 380
Lowest impedance B 100 100 100 100 70 70 70 70 70 70
Duty factor % DF 40 54 36 53 44 40 36 40 36 36
Relay 1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A 1 changeover contact, 230 V AC, 0.2 A inductive load, 2.5 A resistive load; or 24 V DC, 0.7 A inductive load, 3 A resistive load
inductive load, 3 A resistive load
Serial interface RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485 RS485
Control voltage
Output setpoint voltage V +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA +10 DC, 10 mA
Output control voltage V +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA +24 DC, 30 mA
Parameterization 2 2
Inputs
digital (parameters can be defined) 6 +24 V DC, configurable 6 +24 V DC, configurable
Analog Inputs Amount 2 0 to +10 V DC (input impedance 10 k , 4 to 20 mA (load impedance 250 ), resolution 10 bit 2 0 to +10 V DC (input impedance 10 k , 4 to 20 mA (load impedance 250 ), resolution 10 bit
Outputs
Digital 2 24 V DC transistor (open-collector, configurable) 2 24 V DC transistor (open-collector, configurable)
analog (parameters can be defined) 1 0 to +10 V DC, 1 mA (configurable), resolution 10 bit 1 0 to +10 V DC, 1 mA (configurable), resolution 10 bit
Cable lengths
mm2 1.5 1.5 1.5 2.5 2.5 4 4 2.5 4 4
AWG 16 16 16 14 14 12 12 14 12 12
Relay connection
mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
AWG 6 6 6 6 6 6 6 6 6 6
Control circuit
mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
AWG 6 6 6 6 6 6 6 6 6 6
If the frequency inverter is to be installed in an enclosure, control panel or similar housing, the
ambient temperature a is taken to be the temperature inside this enclosure or control panel.
All rating data of the power section is based on a switching frequency of 5 kHz (default setting) and
an ambient temperature of +40 °C, for operation of a four-pole three-phase asynchronous motor.
15/44 Technical Data Technical Data 15/45
Vector frequency inverters Vector frequency inverters
DV51 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 DV51
operational current Ie
Frequency inverters
Power section
Rated operating voltage V AC 400 400 400 400 400 400 400 400
Rated voltage Ue V 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 %
Supply frequency Hz 50/60 (47…63 g 0 %) 50/60 (47…63 g 0 %)
Mains current
Ui = 3-phase, 400 V AC I A 2 3.3 5 7 10 11 16.5 20
Alternative DC supply UDC V DC 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 % 480…740 g 0 %
Modulation method Sensorless vector control, pulse width modulation (PWM) Sensorless vector control, pulse width modulation (PWM)
Switching frequency 5 kHz, can be selected between 2 and 14 kHz 5 kHz, can be selected between 2 and 14 kHz
Output voltage V 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue 3 AC Ue
Output frequency Hz 0 to 50, max. 400 0 to 50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C g 10 K g 0.01 % of maximum frequency for digital reference values, g 0.2 % of maximum frequency for analog reference g 0.01 % of maximum frequency for digital reference values, g 0.2 % of maximum frequency for analog reference values
values
Max. rated operational current Ie A 1.5 2.5 3.8 5.5 7.8 8.6 13 16
Permissible overcurrent 150 % for 60 s, every 600 s 150 % for 60 s, every 600 s
Torque during start From 1 Hz: more than 200 % with sensorless vector control From 1 Hz: more than 200 % with sensorless vector control
Apparent power at 460 V kVA 1.1 1.9 2.9 4.2 6.2 6.6 10.3 12.2
Resistor R B at 100 % c.d.f.
400 V kW 0.37 0.75 1.5 2.2 3 4 5.5 7.5
460 V HP m 1 2 3 4 5 7m 10
Brake transistor
Switching threshold UDC V DC 760 760 760 760 760 760 760 760
Standard operation at 150 % R O 500 300 200 150 100 100 70 70
overload Assigned motor
rating (4-pole ASM)
Frequency inverters
Weight kg 5 5 12 12 12 20
Power section
Rated operating voltage V AC 400 400 400 400 400 400
Rated voltage e V 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC
Supply frequency Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)
Mains current
i = 3-phase, 400 V AC A 24 32 41 47 63 77
Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760
Modulation method Pulse width modulation (PWM), / -predetermined control Pulse width modulation (PWM), / -predetermined control
Switching frequency 5 kHz, can be selected between 0.5 and 12 kHz 5 kHz, can be selected between 0.5 and 12 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C g 10 K g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency with analog setpoint values
with analog setpoint values
Max. rated operational current e A 22 29 37 43 57 70
Permissible overcurrent 120 % for 60 s/150 % for 0.5 s, every 600 s 120 % for 60 s/150 % for 0.5 s, every 600 s
Torque during start Quadratic, linear load characteristic (base frequency 30 – 400 Hz) Quadratic, linear load characteristic (base frequency 30 – 400 Hz)
Apparent power at 400 V kVA 15.2 20 25.6 29.7 39.4 48.4
Apparent power at 480 V kVA 18.2 24.1 30 35.7 47.3 58.1
Standard operation with 120 % overload. Assigned
motor rating (4-pole ASM)
400 V kW 11 15 18.5 22 30 37
460 V HP 15 20 25 30 40 50
Brake transistor
Switching threshold DC V DC 740 740 – – – –
Resistor B at 100 % c.d.f. O 150 150 – – – –
Lowest impedance B O 50 50 – – – –
Max. duty factor (c.d.f.) with lowest % DF 10 10 – – – –
impedance B
Control circuit
Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch
Relay 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive load/3 A resistive load,2 x make contacts, 230 V AC/1 A
load/3 A resistive load,2 x make contacts, 230 V AC/1 A inductive load/5 A resistive load or 24 V DC/ inductive load/5 A resistive load or 24 V DC/1 A inductive load/5 A resistive load
1 A inductive load/5 A resistive load
Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485
Control voltage
Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA
Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA
Parameterization 2 parameter sets (online/offline parameterization), parameter protection (programmable) 2 parameter sets (online/offline parameterization), parameter protection (programmable)
Inputs
digital (parameters can be defined) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field)
analog, 8 bit resolution Amount 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O) 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O)
Outputs
analog (parameters can be defined), 8 bit 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA
resolution 4 – 20 mA (load impedance max. 250 O) 4 – 20 mA (load impedance max. 250 O)
PWM (parameters can be defined) 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA
Terminal capacities
Cable lengths
mm2 6 10 16 25 25 35
AWG 8 6 6 4 3 1
Relay connection
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16
Control circuit
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 16… 6 16… 6 16… 6 16… 6 16… 6 16… 6
Notes If the frequency inverter is to be installed in a control panel, enclosure or similar installation, the
prevalent ambient within these enclosuresor control panels is considered to be the ambient
temperature a.
All rating data of the power section are based on a switching frequency of 5 kHz (default setting) and
an ambient temperature of +40 °C, with operation of a four pole three-phase asynchronous motor.
15/48 Technical Data Technical Data 15/49
Frequency inverters Frequency inverters
DF6 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 DF6
DF6-340-45K DF6-340-55K DF6-340-75K DF6-340-90K DF6-340-110K DF6-340-132K
Power loss
at 100 % e W 2300 2800 3800 4800 5500 6650
Vector frequency inverters
Frequency inverters
Dimensions (W x H x D) mm 396 x 556 x 270.5 396 x 556 x 270.5 396 x 556 x 270.5 396 x 706 x 290.5 396 x 706 x 290.5 486 x 746 x 282
Weight kg 30 30 30 60 60 80
Power section
Rated operating voltage V AC 400 400 400 400 400 400
Rated voltage e V 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC
Supply frequency Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)
Mains current
i = 3-phase, 400 V AC A 94 116 149 176 215 253
Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760
Modulation method Pulse width modulation (PWM), / -predetermined control Pulse width modulation (PWM), / -predetermined control
Switching frequency 5 kHz, can be selected between 0.5 and 12 kHz 5 kHz, can be selected between 0.5 and 8 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5 – 50, max. 400 0.5…50, max. 360 0.5…50, max. 360
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
Frequency error limit at 20 C g 10 K g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency with analog setpoint values
with analog setpoint values
Max. rated operational current e A 85 105 135 160 195 230
Permissible overcurrent 120 % for 60 s/150 % for 0.5 s, every 600 s 120 % for 60 s/150 % for 0.5 s, every 600 s
Torque during start Quadratic, linear load characteristic (base frequency 30 – 400 Hz) Quadratic, linear load characteristic (base frequency 30 – 400 Hz)
Apparent power at 400 V kVA 58.8 72.7 93.5 111 135 159
Apparent power at 480 V kVA 70.1 87.1 112 133 162 191
Standard operation with 120 % overload. Assigned
motor rating (4-pole ASM)
400 V kW 45 55 75 90 110 132
460 V HP 60 75 100 125 150 175
Brake transistor
Switching threshold DC V DC – – – – – –
Resistor B at 100 % c.d.f. O – – – – – –
Lowest impedance B O – – – – – –
Max. duty factor (c.d.f.) with lowest % DF – – – – – –
impedance B
Control circuit
Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch
Relay 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive load/3 A resistive load,2 x make contacts, 230 V AC/1 A
load/3 A resistive load,2 x make contacts, 230 V AC/1 A inductive load/5 A resistive load or 24 V DC/ inductive load/5 A resistive load or 24 V DC/1 A inductive load/5 A resistive load
1 A inductive load/5 A resistive load
Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485
Control voltage
Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA
Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA
Parameterization 2 parameter sets (online/offline parameterization), parameter protection (programmable) 2 parameter sets (online/offline parameterization), parameter protection (programmable)
Inputs
digital (parameters can be defined) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field) 6 x +24 V DC (5 x parameterizable, 1 x FWD) (clockwise rotating field)
analog, 8 bit resolution Amount 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O) 2 x 0/+10 V DC (input impedance 10 kO, 4 – 20 mA (load impedance 100 O)
Outputs
analog (parameters can be defined), 8 bit resolution 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA 1 x 0/+10 V DC, 2 mA
4 – 20 mA (load impedance max. 250 O) 4 – 20 mA (load impedance max. 250 O)
PWM (parameters can be defined) 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA 0…10 V, max. 1.2 mA
Terminal capacities
Cable lengths
mm2 35 50 2 x 35 2 x 35 2 x 50 2 x 70
AWG 1 1/0 2x1 2x1 2 x 1/0 2 x 1/0
Relay connection
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16
Control circuit
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 16… 6 16… 6 16… 6 16… 6 16… 6 16… 6
Notes If the frequency inverter is to be installed in a control panel, enclosure or similar installation, the
prevalent ambient within these enclosuresor control panels is considered to be the ambient
temperature a.
All rating data of the power section are based on a switching frequency of 5 kHz (default setting) and
an ambient temperature of +40 °C, with operation of a four pole three-phase asynchronous motor.
15/50 Technical Data Technical Data 15/51
Vector frequency inverters Vector frequency inverters
DV6 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 DV6
Power loss
Vector frequency inverters
Frequency inverters
Efficiency % 91.5 92.3 93.2 94 94.4 94.5 94.5 94.6 94.7
Dimensions (W x H x D) mm 159 x 260,5 x 152 159 x 260,5 x 152 159 x 260,5 x 152 159 x 260,5 x 152 159 x 260,5 x 152 216 x 266 x 182 216 x 266 x 182 256 x 396 x 210 256 x 396 x 210
Weight kg 3.5 3.5 3.5 3.5 3.5 5 5 12 12
Power section
Rated operating voltage V AC 400 400 400 400 400 400 400 400 400
Rated voltage e V 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3- 342 – 528 V g 0 % 3-
phase AC phase AC phase AC phase AC phase AC phase AC phase AC phase AC phase AC
Supply frequency Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)
Mains current
i = 3-phase, 400 V AC A 2.8 4.2 5.8 9.5 13 18 25 35 42
Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760 420…760 420…760 420…760
Modulation method Sensorless vector control, pulse width modulation (PWM) Sensorless vector control, pulse width modulation (PWM)
Switching frequency 5 kHz, can be selected between 0.5 and 15 kHz 5 kHz, can be selected between 0.5 and 15 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
values
Frequency error limit at 20 C g 10 K g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency with analog setpoint values
maximum frequency with analog setpoint values
Max. rated operational current e A 2.5 3.8 5.3 8.6 12 16 23 32 38
Permissible overcurrent 150 % for 60 s/200 % for 0.5 s, every 600 s 150 % for 60 s/200 % for 0.5 s, every 600 s
Torque during start 200 % at 0.5 Hz (sensorless vector control mode) 200 % at 0.5 Hz (sensorless vector control mode)
Apparent power at 400 V kVA 1.7 2.6 3.6 5.9 8.3 11 15.9 22.1 26.3
Apparent power at 480 V kVA 2 3.1 4.4 7.1 9.9 13.3 19.1 26.6 31.5
Standard operation with 150 % overload. Assigned motor rating (4-pole ASM)
Control circuit
Vector frequency inverters
Frequency inverters
Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485
Control voltage
Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA
Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA
Parameterization 3 parameter sets (online/offline parameterization), parameter protection 3 parameter sets (online/offline parameterization), parameter protection (programmable)
(programmable)
Inputs
Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch
Clockwise rotating field enable (FWD) 1 x +24 V DC (input impedance 4.7 kO) 1 x +24 V DC (input impedance 4.7 kO)
digital (parameters can be defined) 8 x +24 V DC (input impedance 4.7 kO) 8 x +24 V DC (input impedance 4.7 kO)
analog, 12 bit resolution Amount 3 x 0 – +10 V DC, g10 V DC (input impedance 10 kO), 4…20 mA (load 3 x 0 – +10 V DC, g10 V DC (input impedance 10 kO), 4…20 mA (load impedance 100 O)
impedance 100 O)
Outputs
Digital 5 x 24 V DC transistor (open-collector, configurable) 5 x 24 V DC transistor (open-collector, configurable)
analog (parameters can be defined), 8 bit 3 x 0…+10 V DC (max. 2 mA), 4…20 mA (max. load impedance 250 O) 3 x 0…+10 V DC (max. 2 mA), 4…20 mA (max. load impedance 250 O)
resolution
PWM (parameters can be defined) 1 x 0…10 V, max. 1.2 mA 1 x 0…10 V, max. 1.2 mA
Terminal capacities
Cable lengths
mm2 1.5 2.5 2.5 2.5 2.5 4 6 10 16
AWG 20 18 16 14 12 10 8 6 6
Relay connection
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16
Control circuit
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16
Power loss
Vector frequency inverters
Frequency inverters
Efficiency % 94.8 94.8 94.9 94.9 94.9 95 95 95 95.1
Dimensions (W x H x D) mm 256 x 396 x 210 310 x 540 x 202,2 390 x 550 x 255,2 390 x 550 x 255,2 390 x 550 x 255,2 390 x 700 x 275,2 390 x 700 x 275,2 480 x 740 x 293,2 480 x 740 x 293,2
Weight kg 12 20 30 30 30 60 60 80 80
Power section
Rated operating voltage V AC 400 400 400 400 400 400 400 400 400
Rated voltage e V 342 – 528 V g 0 % 3-phase AC 342 – 528 V g 0 % 3-phase AC
Supply frequency Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)
Mains current
i = 3-phase, 400 V AC A 53 63 83 99 121 164 194 239 286
Alternative DC supply DC V DC 420…760 420…760 420…760 420…760 420…760 420…760 420…760 420…760 420…760
Modulation method Sensorless vector control, pulse width modulation (PWM) Sensorless vector control, pulse width modulation (PWM)
Switching frequency 5 kHz, can be selected between 0.5 and 15 kHz 5 kHz, can be selected between 0.5 and 15 kHz
Output voltage V 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e 3 AC e
Output frequency Hz 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400 0.5…50, max. 400
Frequency resolution Hz 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint 0.1, with digital setpoint values/maximum frequency/1000 with analog setpoint values
values
Frequency error limit at 20 C g 10 K g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the g0.01 % of the maximum frequency with digital setpoint values, g0.2 % of the maximum frequency with analog setpoint values
maximum frequency with analog setpoint values
Max. rated operational current e A 48 58 75 90 110 149 176 217 260
Permissible overcurrent 150 % for 60 s/200 % for 0.5 s, every 600 s 150 % for 60 s/200 % for 0.5 s, every 600 s
Torque during start 200 % at 0.5 Hz (sensorless vector control mode) 200 % at 0.5 Hz (sensorless vector control mode)
Apparent power at 400 V kVA 33.2 40.1 51.9 62.3 76.2 103.2 121.9 150.3 180.1
Apparent power at 480 V kVA 39.9 48.2 62.3 74.8 91.4 123.8 146.3 180.4 216.1
Standard operation with 150 % overload. Assigned motor
rating (4-pole ASM)
400 V kW 22 30 37 45 55 75 90 110 132
460 V HP 30 40 50 60 75 100 125 150 175
Control circuit
Relay 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 1 x changeover contact, 230 V AC/0.2 A inductive load/2.5 A resistive load or 24 V DC/0.7 A inductive load/3 A resistive load
V DC/0.7 A inductive load/3 A resistive load
Serial interface RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485 RS 422, RS 485
Control voltage
Output setpoint voltage V +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA +10 DC, 20 mA
Output control voltage V +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA +24 DC, 100 mA
Parameterization 3 parameter sets (online/offline parameterization), parameter protection 3 parameter sets (online/offline parameterization), parameter protection (programmable)
(programmable)
Inputs
Thermistor input 1 x PTC thermistor, temperature switch 1 x PTC thermistor, temperature switch
Clockwise rotating field enable (FWD) 1 x +24 V DC (input impedance 4.7 kO) 1 x +24 V DC (input impedance 4.7 kO)
digital (parameters can be defined) 8 x +24 V DC (input impedance 4.7 kO) 8 x +24 V DC (input impedance 4.7 kO)
analog, 12 bit resolution Amount 3 x 0 – +10 V DC, g10 V DC (input impedance 10 kO), 4…20 mA (load 3 x 0 – +10 V DC, g10 V DC (input impedance 10 kO), 4…20 mA (load impedance 100 O)
impedance 100 O)
Outputs
Digital 5 x 24 V DC transistor (open-collector, configurable) 5 x 24 V DC transistor (open-collector, configurable)
analog (parameters can be defined), 8 bit resolution 3 x 0…+10 V DC (max. 2 mA), 4…20 mA (max. load impedance 250 O) 3 x 0…+10 V DC (max. 2 mA), 4…20 mA (max. load impedance 250 O)
PWM (parameters can be defined) 1 x 0…10 V, max. 1.2 mA 1 x 0…10 V, max. 1.2 mA
Terminal capacities
Cable lengths
mm2 16 25 35 35 2 x 35 2 x 35 2 x 50 2 x 70 2 x 70
AWG 4 3 1 1 1/0 2x1 2x1 2 x 1/0 2 x 2/0
Relay connection
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16
Control circuit
mm2 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5 0.14…1.5
AWG 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16 26…16
Notes 1) If
the frequency inverter is to be installed in a control panel, enclosure or similar installation, the prevalent ambient within these
enclosuresor control panels is considered to be the ambient temperature a.
All rating data of the power section are based on a switching frequency of 5 kHz (default setting) and an ambient temperature of
+40 °C, with operation of a four pole three-phase asynchronous motor.
15/56 Technical Data Technical Data 15/57
Radio interference suppression filters Radio interference suppression filter
DE6-LZ3... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 DE6-LZ3...
General
Vector frequency inverters
Frequency inverters
Operating temperature °C –25…+85 –25…+85 –25…+85 –25…+85 –25…+85 –25…+85 –25…+85 – –25…+85
Altitude m 0…1000 a.s.l., derating above 1000: e…2 %/1000 m 0…1000 a.s.l., derating above 1000: e…2 %/1000 m
Mounting position As required, vertically suspended preferred As required, vertically suspended preferred
Free surrounding areas In connection area (cable, terminals): 100 mm In connection area (cable, terminals): 100 mm
Humidity class C C C C C C C C C
Climatic class (IEC) – – – – – –
Protection type IP20 (terminal) IP20 (terminal)
Dimensions (W x H x D) mm 143 x 255 x 29 203 x 260 x 43 244 x 390 x 45 60 x 400 x 87 70 x 440 x 110 70 x 440 x 110 130 x 525 x 94 130 x 525 x 94 142 x 620 x 116
Weight kg 1.4 2.5 4.5 4.3 6.4 6.7 8.8 9.3 13.7
Electrical data
Test voltage in V DC, 2 s
Phase/neutral pole V 2064 2064 2064 2064 2064 2064 2064 2064 2064
Phase/PE V 2064 2064 2064 2064 2064 2064 2064 2064 2064
Leakage current
Max. leakage current in operation mA 30 30 30 30 30 30 30 30 30
Max. leakage current PE and 2 external conductors mA 180 280 550 690 750 750 380 380 600
disconnected
Rated operating voltage V AC 400 400 400 400 400 400 400 400 400
Rated voltage e V 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 % 3 AC 342…528 V g 0 %
Supply frequency Hz 50/60 (47 -0 %…63 +0 %) 50/60 (47 -0 %…63 +0 %)
Rated operational current
i = 1-phase, 230 V AC A – – – – – – – – –
i = 3-phase, 400 V AC A 13 32 64 80 115 125 150 220 260
Permissible overcurrent 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes 150 % for 10 minutes
General
Standards EN 50178, IEC 61800-3, EN 61800-3 incl. A11
Frequency inverters
Environmental conditions
Operating temperature °C –25…+100
Altitude m 0…1000 a.s.l., derating above 1000: Ie…2 %/1000 m
Mounting position As required, vertically suspended preferred
Free surrounding areas In connection area (cable, terminals): 80 mm
Humidity class C
Climatic class (IEC) 25/085/21
Protection type IP 20 (terminals)
Dimensions (W x H x D) mm 80 x 170 x 27 110 x 180 x 35 110 x 180 x 35 110 x 285 x 40
Weight kg 0.45 0.5 0.67 0.7 0.75 1.2
Electrical data
Test voltage in V DC, 2 s
Phase/neutral pole V 1100 1100 1100 2100 2100 2100
Phase/PE V 2550 2550 2550 2650 2650 2650
Leakage current
Max. leakage current in operation mA <6 <6 <6 < 11 < 35 < 46
Max. leakage current when PE mA < 25 < 26 < 24 <4 <5 < 5.5
disconnected
Max. leakage current when PE and N mA < 47 < 51 < 48 – – –
disconnected
Max. leakage current PE and 2 external mA – – – < 156 < 198 < 210
conductors disconnected
Rated operating voltage V AC 230 230 230 400 400 400
Rated voltage Ue V 1 AC 250 V 3 AC 480 V
Supply frequency Hz 50/60 (47…63 g 0 %)
Rated operational current
Ui = 1-phase, 230 V AC I A 7 12 24 – – –
Ui = 3-phase, 400 V AC I A – – – 7 11 20
Permissible overcurrent 150 % for 60 s, every 30 minutes
Heat dissipation with rated operational W 5 7 12 4 7 12
current Ie
Terminal capacities
Solid mm2 0.2…4
flexible mm2 0.2…4
Cables to frequency inverter mm2 2 x 1.5, 180 mm 2 x 2.5, 250 mm
AWG 18 16 12 18 16 12
PE stud M5 x 15
General
Frequency inverters
Operating temperature °C –25…+40, up to 70 with current reduction (see notes)
Storage temperature °C –25…+85 –25…+85 –25…+85
Shock resistance 11 ms2/15 g, 3 impacts 11 ms2/15 g, 3 impacts 11 ms2/15 g, 3 impacts
Vibration resistance g 1 (at 0…150 Hz) 1 (at 0…150 Hz) 1 (at 0…150 Hz)
Vibration 0.35 mm at 10…55 Hz 0.35 mm at 10…55 Hz 0.35 mm at 10…55 Hz
Pollution degree 1 (VDE 0160) 1 (VDE 0160) 1 (VDE 0160)
Altitude m 0 to 1000 above sea level, up to 5000 with current derating (see notes)
Mounting position Standing vertically, suspended horizontally
Free surrounding areas < 50 < 50 < 50
Degree of protection (terminals) IP20 IP20 up to 40 A IP20 up to 50 A
IP 00 from 50 A IP20 from 63 A
Rated duty factor % DF 100 100 100
Overload cycle 1.5 x Ie for 60 s every 600 s 1.5 x Ie for 60 s every 600 s 1.5 x Ie for 60 s every 600 s (< 24 A)
1.2 x Ie for 60 s every 600 s (> 24 A)
Notes 1) The following applies for the installation altitude: Derating with respect to the rated current Ie:
I 1.0
Ie
0.9
0.8
0.7
0.6
0.5
0 1000 2000 3000 4000 5000
h [m]
15/60 Technical Data
Line reactors, motor reactors
DEX-LN, DEX-LM3 Moeller HPL0211-2007/2008 http://catalog.moeller.net
L Ie PVCU uk torque
mH A W % mm² AWG mm Nm
Frequency inverters
Part no. Inductance Rated current Heat dissipation (clock frequency) Connection
b1
b
o o
b2
b2
a1 a1
a a
b2
o
a1
C
a
a DF51 only
Braking resistors
DE4-BR1-…
Part no. a a1 b b1 c d Weight
mm mm mm mm mm mm kg
DE4-BR1-470-050 205 185 70 50 95 6x15 0.4
c
54.8
3
RUN
59
PRG
I O
Frequency inverters
PRG ENTER
69.5 10 12 q 18
DEX-KEY-61
123
103
POWER
ALARM
Hz
A
54.8
RUN
59
PRG
I O
o4
6.5
PRG ENTER
69.5 10
5
Mounting frame
DEX-MNT-K6
83.4
63.4
66.5
74
o 4.2
50 5 2
94.4 7
3 9
12
Interface module
DE51-NET-CAN DE51-NET-DP
120
120
129
125
82 22.5
82 22.5
34
34
Mounting frames
DEX-MNT-NET DEV51-MNT-K60
118
121
142
78 18
22
85 23
15/64 Dimensions
Radio interference suppression filter
DE51-..., DE6-... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Radio interference suppression filter
DE51-LZ3-...-V4 DE51-LZ1-...-V2
c2 c2
d d
Vector frequency inverters
PE
M5 x 15
Frequency inverters
d1 d1
b1
b
b2
b3
b1
b2
b3
l
d
c1 a1 l
d
c a
c1 a1
c a
Part no. a a1 b b1 b2 b3 c c1 c2 d d1 l
mm mm mm mm mm mm mm mm mm mm mm kg mm
DE51-LZ1-007-V2 80 67 170 160 110 120 27 20 13.5 5 2x6 0.45 160
DE51-LZ1-012-V2 110 98 180 170 118 130 35 28 17.5 5 4x6 0.5 180
DE51-LZ1-024-V2 110 98 180 170 118 130 35 28 17.5 5 4x6 0.67 180
DE51-LZ3-007-V4 110 98 180 170 118 130 35 28 17.5 5 4x6 0.7 180
DE51-LZ3-011-V4 110 98 180 170 118 130 35 28 17.5 5 4x6 0.75 180
DE51-LZ3-020-V4 180 164 285 269 205 220 40 31 20 6.3 4x6.5 1.2 250
DE6-LZ3-...-V4
PE d
PE
b1
b
b1
b
c a1
c a1
a
c1 ± 5
DEX-LN1-009 66 50 71 44 55 80 61 4.5x8 0.7
Frequency inverters
DEX-LN1-013 84 64 67 47 60 90 75 4.8x8 1.5
DEX-LN1-018 84 64 90 70 83 90 75 4.8x8 1.5
d b1 DEX-LN1-024 84 64 67 47 60 90 75 4.8x8 2
a1
b2
a
b±5
c1± 5
a1 d b1
DEX-LM3-005 115 100 66 50 66 118 84 5x10 1.5
a b2
b±5 DEX-LM3-008 195 175 104 50 76.5 175 134 8x13 4.8
DEX-LM3-011 195 175 104 50 76.5 175 134 8x13 4.8
DEX-LM3-016 195 175 104 50 76.5 175 134 8x13 4.8
DEX-LM3-035 220 200 132 75 101.5 195 160 8x13 7.3
DEX-LM3-050 270 250 106 75 96 228 198 8x13 12.3