You are on page 1of 44

http://catalog.moeller.

net Contents A1/1


Moeller HPL0211-2007/2008

Approvals and certificates

Approvals for world markets


Page Page Page

Approvals for world markets Motor-protective circuit-breakers NZM circuit-breakers, Chapter 10


For the world wide use of the Industrial Switchgear in many switch-disconnectors
Overview A1/2 PKZM motor-protective circuit- A1/29
countries and for shipboard use national approvals are breakers
Country-specific approvals A1/4
required. The approvals are partly connected with special Compact starters PKZM0, Insulated A1/30
Shipping classifications A1/8 enclosures
technical data. This part of the catalogue gives you the
Switchgear for North America Accessories A1/31
necessary information of the appropriate foreign approvals
for export. There is also information of which approvals the Type E starters A1/32
Approvals A1/13
Moeller products have. Type F starter combinations A1/33
Selection of devices A1/14
Motor-protective circuit-breakers, A1/34
Switching duty auxiliary contacts, A1/16
circuit-breakers
rating data of AC contactors
according to NEMA. Self-protected starters PKZ2/S-SP A1/35
Selection and usage of fuses A1/17 Direct-on-line starters, reversing A1/35
starters
Enclosure protection types to NEC A1/18
(NFPA 70), UL, CSA, NEMA PKZ2 motor-protective circuit- A1/36
breakers, insulated enclosures
Contactor relays
Accessories A1/37
DILER, DILR contactor relays; DILET, A1/19 FAZ miniature circuit-breakers
ETR4 timing relays
Display and operator units, control Supplementary Protector A1/38
circuit devices
CI insulated enclosures
Operator panels, RMQ16, RMQ-Titan A1/20
Position switches, pressure switches Empty enclosures A1/39
Panel enclosures A1/40
Position switches, proximity switches,
pressure switches A1/21 Individual enclosures A1/41
Contactors CI…-NA accessories A1/42
Cable glands for wiring conduits A1/44
DILM contactors, complete units A1/22
Glossary
DILM/Z motor-starter combinations A1/23
Overload relays A1/24
Rotary switches, switch-disconnectors

Miscellaneous switches with A1/25


disconnect function
Switch-disconnectors A1/26
Auxiliary contacts A1/28
A1/2 Approvals for world markets
Overview
Moeller HPL0211-2007/2008 http://catalog.moeller.net

The standard versions of most Moeller devices Since January 1996, all devices sold within the Austria
are approved for use throughout the world, European union must comply with the Electromagnetic Österreichischer Verband
including the USA and Canada. Compatibility (EMC) Directive. Moeller has passed the für Elektrotechnik
Approvals for world markets

As such, they can be used without restriction as required tests for all products subject to these (ÖVE)
devices for world markets. Directives, and the devices carry the CE mark,
demonstrating compliance with the EMC Directive.
The standard versions of some devices, such as Because devices bearing the CE mark comply with the
circuit-breakers, can be used worldwide except in harmonized standards, approval and the associated Switzerland
the USA and Canada. marking is no longer required in the following Schweizerischer
Such devices are available in special UL- and CSA- countries: Elektrotechnischer
approved versions for export to these countries. Verein
Belgium (SEV)
Comité Electro-
Moeller low-voltage switchgear and switchgear technique Belge
assemblies conform to national and international Devices for export to the USA and Canada have either
Belgisch Elektro-
specifications, making it possible to construct control additional UL and CSA approval or are available in a
technisch Comité
systems that will conform to the national international separate version with UL and CSA approval.
(CEBEC)
specifications of any country in the world. USA
This, of course, means that due consideration must be Denmark Underwriters Laboratories
given to the particular national standards of the Danmarks Elektriske (UL)
country in question, such as those concerning Materielkontrol Listing
installation, operation, installation materials and (DEMKO) Recognition
methods, as well as any pertaining to circumstances
such as severe environmental conditions.
The component rating data for 220 … 240 V, 380 – Finland
440 V, 500 V, 600 V and 690 V given in this catalogue (FIMKO)
cover virtually all existing three-phase systems
worldwide. Canada
Ratings are also given for the supply voltages in Canadian
common use in the USA and in Canada. Standards
France Association
In addition to the widely differing system conditions, Union Technique (CSA)
special installation standards and approval de l‘Electricité
requirements also have to be observed for the (UTE) Recently introduced is the mandatory approval of
worldwide use of switchgear:
electrical products for
Where screw fuses have to be used in a control system,
• Slovakia
some European countries – such as Denmark, Finland,
Netherlands • Poland
the Netherlands, Norway and Sweden – require gauge
Naamloze Vennootschap • South Africa
screws. In this case , „FORM P“ fuse bess must be
tot Keuring van • China
used. Switzerland no longer requires the use of gauge
Electrotechnische • Russia
screws, but they are often still requested by customers.
Materialien • Turkey
(KEMA) • Argentina
The majority of countries permit the import of
switchgear assemblies and devices on the Norway Marking is partly mandatory for these countries. The
manufacturer’s undertaking that they have been Norges Elektriske IEC rating data is accepted as in other European
constructed in accordance with the pertinent Materiellkontrol countries.
specifications. In some countries, such as the USA and (NEMKO)
Canada, however, there is a legal obligation to obtain
Approval is not mandatory in the Czech Republic and
official approval.
Hungary. The manufacturer’s declaration of
In these countries, devices and enclosures – sometimes Sweden conformity is sufficient here.
even complete control systems – are tested and Svenska
approved by independent bodies. Elektriska Materiel- Romania requires that components that are to be used
kontrollanstalten in public buildings must be approved by the Romanian
To a certain extent, there also used to be a legal (SEMKO) test authority ICECON.
obligation to obtain official approval for low-voltage
switchgear and controlgear in Scandinavia and in
Switzerland Russia
Switzerland. For industrial switchgear, this legal
Schweizerischer Devices for Russia must bear the appropriate marking.
obligation has now been abolished, provided the
devices have been manufactured and tested in Elektrotechnischer Russia
accordance with harmonized European standards Verein Goststandart
(such as IEC/EN 60947). There is then no longer a (SEV) (GOST-R)
requirement for them to carry their country's own
aprroval mark. Moeller develops switchgear to An exception is equipment for service installations. The
international standards, such as IEC/EN 60947 and device group of miniature circuit-breakers and South Africa
applies the corresponding marks. residual-current circuit-breakers in certain areas is still Approval is mandatory in South Africa for circuit-
subject to mandatory marking and therefore provided breakers and busbar trunking systems. These devices
Since January 1997, all devices must conform to the with the appropriate approval marks: must bear the appropriate marking.
European Low-Voltage Directive and, where intended Belgium South Africa
for sale within the European Union, must carry the CE Comité Electro- ZA
mark. technique Belge SABS
Europe Belgisch Elektro-
Conformité Européen technisch Comité Argentina
(CE) (CEBEC) In Argentina, mandatory approval is based on
Resolution 92/98. From 01/04/2001, miniature circuit-
Germany breakers and residual-current circuit-breakers are
Verband subject to mandatory approval. From 01/04/2002,
This mark denotes that the device carrying it conforms Deutscher
to all relevant requirements and specifications. The protective switches up to Ie = 63 A and Ue max = 440 V
Elektrotechniker are subject to mandatory approval and must bear the
mandatory application of this mark therefore enables (VDE)
the unrestricted use of marked devices within the following markings:
European economic area. France
Union Technique
de l‘Electricité
(UTE)
Approvals for world markets A1/3
Overview
http://catalog.moeller.net Moeller HPL0211-2007/2008
Selection of devices
“Selection appropriate for export” does not mean • For contactors • For overcurrent protective devices
merely meeting the requisite approvals and conformity Use contactors whose entire range provides consist- Always use circuit-breakers and motor-protective cir-
to relevant specifications. The meaning of the term ently reliable operation in the event of voltage drops cuit-breakers. Avoid fuses as far as possible.

Approvals for world markets


goes a great deal further by even including that (80% Un should be aimed for) and whose contact sys- Advantage:
equipment and installations must be designed to a tem will not assume an indeterminate position either – The operational reliability of a system is especially
concept with export in mind. on closing or on opening in such conditions. important for export contracts. Circuit-breakers and
The following are important criteria for selecting Advantage: motor-protective circuit-breakers provide this relia-
switchgear suitable for export: – During the electrification work in areas such as Afri- bility in full measure since they can be immediately
• For motor-protective circuit-breakers ca and the Middle East, an insufficient voltage sta- reclosed once a fault has been cleared, they discon-
Use inherently short-circuit proof switches capable of bility is – at least for a certain time – likely in many nect all poles, they have ideal protection through
controlling the highest prospective fault levels at the applications (for example due to long spur lines or high tripping accuracy and they can be used for se-
point of installation without the need for back-up small local generators). The use of devices that full- lective operation. Because they have no fuses or
protection. fill the above requirements will eliminate one of the other consumables, they also greatly reduce the
Advantage: maim failure causes related to contactors. problem of obtaining replacement parts. The ad-
– No restrictions whatsoever for installation • For enclosures vantages of fuseless design for export are especially
– Complete independence from the on-site protective Use insulated enclosures with transparent covers (i.e. evident in this case. No complicated investigation is
system “totally insulated” enclosures). needed to find out which fusing system is used in
– No problems getting spare parts Advantage: the respective location and which specifications
• For circuit-breakers – Total insulation is the best possible protective meas- have to be followed to select the correct fuses. Of-
Use types with visible contacts, quick-make and ure from the user’s point of view, avoiding, reliance ten several different fuse systems with widely vary-
quick-break operation as standard. Use current-limit- on the possibly doubtful skills of unknown installa- ing characteristics are used side-by-side in the same
ing circuit-breakers for high short-circuit levels. Selec- tion personnel. Furthermore, protective measures country. For the uninitiated, it may be almost im-
tive switches are recommended for the selective based on earthing are often extremely difficult, if possible to find the right fuse in these circumstanc-
graduation of networks. not impossible (in the Middle East, for example, due es. These problems do not arise where a circuit-
Advantage: to the dryness of the ground). breaker is used.
– Independence from local accident prevention regu- – Insulated enclosures completely eliminate the need • For main switches and safety switches
lations requiring visible contacts, and safety fro for any additional protection against corrosion. The Use devices with positive contact separation and
faults caused by inexperienced operating person- transparent covers contribute significantly to the clear switch position indication.
nel. correct operation of a system, because switchgear Advantage:
– The effects of short-circuits are kept to a minimum. operation can be monitored even with the doors or – The mechanical coupling of the actuating element
– Fuseless installations offer greater safety and relia- covers closed, thus virtually eliminating the possibil- with the contacts ensues that the Off position is in-
bility in plant operation. In the event of a fault, only ity of these being left open through carelessness. dicated only when all main contacts are separated
the faulty section of the system is isolated. The transparent cover is an important contribution by the prescribed distance, and only in this position
to safety, especially where exports to areas of un- can the switch be padlocked. This ensures safety
certain skills are concerned. when carrying out maintenance and repair work on
the installation or machinery.

Test authorities Shipping classifications


Moeller devices have the approvals required for use in Moeller devices have been approved by the following
the following countries; shipping classification societies:
For details a from Page A1/4 For details a from Page A1/8
USA Slovakia Germany
UL SK Germanischer
SKTC Lloyd
GL
Canada Poland United Kingdom
CDN PL Lloyd´s Register of
CSA BBJ-SEP Shipping
LR
Romania ML PAT Turkey France
RO TR Bureau
ICECON TSE Veritas
BV

Russia China Russia


RUS PRC Russian Maritime
GOST-R CCC Register of Shipping
RS

South Africa Ukraine Italy


ZA UA Registro Italiano
SABS Ukrain-GOST Navale
RINA
Norway
Det Norske Veritas
DNV

Poland
Polski Rejestr
Statkow
PRS
A1/4 Approvals for world markets
Country-specific approvals
RMQ, SL, MSC(N), EASY, EC4P Moeller HPL0211-2007/2008 http://catalog.moeller.net
Country
Test authorities

USA CDN AUS RUS ZA PRC UA


Approvals for world markets

UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST


Control Circuit Devices
RMQ16 K K K N – K
RMQ-Titan K K K N K K
FAK.../I K K K N K K
SL signal towers K K K N – K
Position switch
LS... K K K N K –
LS-...-...-ZB, LS-...-...-ZBZ/... K K K N – K
Pressure switches
MCS..., MCSN... – K1) N N – K
easy Relay
EASY512-AB-RC(X) K K K K N N K
EASY512-AC-R K K K K N N K
EASY512-AC-RC(X) K K K K N N K
EASY512-DA-RC(X) K K K K N N K
EASY512-DC-R K K K K N N K
EASY512-DC-RC(X) K K K K N N K
EASY512-DC-TC(X) K K K K N N K
EASY719-AB-RC(X) K K K K N N K
EASY719-AC-RC(X) K K K K N N K
EASY719-DA-RC(X) K K K K N N K
EASY719-DC-RC(X) K K K K N N K
EASY721-DC-TC(X) K K K K N N K
EASY819-AC-RC(X) K K K K N N K
EASY819-DC-RC(X) K K K K N N K
EASY820-DC-RC(X) K K K K N N K
EASY821-DC-TC(X) K K K K N N K
EASY822-DC-TC(X) K K K K N N K
easy Control
EC4P-221-MTXD1 k k k k N N k
EC4P-221-MTXX1 k k k k N N k
EC4P-221-MRXD1 k k k k N N k
EC4P-221-MRXX1 k k k k N N k
EC4P-221-MTAD1 k k k k N N k
EC4P-221-MTAX1 k k k k N N k
EC4P-221-MRAD1 k k k k N N k
EC4P-221-MRAX1 k k k k N N k
EC4P-222-MTXD1 k k k k N N k
EC4P-222-MTXX1 k k k k N N k
EC4P-222-MRXD1 k k k k N N k
EC4P-222-MRXX1 k k k k N N k
EC4P-222-MTAD1 k k k k N N k
EC4P-222-MTAX1 k k k k N N k
EC4P-222-MRAD1 k k k k N N k
EC4P-222-MRAX1 k k k k N N k
Input/output expansion
EASY618-AC-RE K K K K N N K
EASY618-DC-RE K K K K N N K
EASY620-DC-TE K K K K N N K
EASY202-RE K K K K N N K
Coupling module
EASY200-EASY K K K K N N K
Notes K Approved or accepted N Approval or acceptance not
k Approval applied for required
– Not approved or accepted
1) Form CDN
Approvals for world markets A1/5
Country-specific approvals
http://catalog.moeller.net Moeller HPL0211-2007/2008 EASY, MFD, DIL, ETR, ESR, EMR
Country
Test authorities

USA CDN OFF RUS ZA PRC UA

Approvals for world markets


UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST
Gateways
EASY204-DP K K K K N N K
EASY205-ASI K K K K N N K
EASY221-CO K K K K N N K
EASY222-DN K K K K N N K
EASY223-SWIRE k k k k N N k
Ethernet module K K
EASY209-SE K K k k N N k
easy MFD
MFD-80-B K K K K N N K
MFD-80-B-X K K K K N N K
MFD-80 K K K K N N K
MFD-80-X K K K K N N K

MFD-AC-CP8-ME K K K K N N K
MFD-AC-CP8-NT K K K K N N K
MFD-CP8-ME K K K K N N K
MFD-CP8-NT K K K K N N K

MFD-CP4 K K K K N N K
MFD-CP4-500 K K K K N N K
MFD-CP4-800 K K K K N N K
MFD-AC-CP4 K K K K N N K
MFD-AC-CP4-500 K K K K N N K
MFD-AC-CP4-800 K K K K N N K

MFD-R16 K K K K N N K
MFD-T16 K K K K N N K
MFD-RA17 K K K K N N K
MFD-TA17 K K K K N N K
MFD-AC-R16 K K K K N N K

MFD-TP12-PT-A k k k k N N k
MFD-TP12-PT-B k k k k N N k
MFD-TP12-NI-A k k k k N N k
MFD-TAP13-PT-A k k k k N N k
MFD-TAP13-PT-B k k k k N N k
MFD-TAP13-NI-A k k k k N N k
Accessories
EASY200-POW K K K K N N K
EASY400-POW K K K K N N K
EASY256-HCI K K K K N N K
Contactor relays
DILER K K N K N – K
DILA K K N k k k k
DILA-XHI K K N k k k k
Electronic timing relays
ETR 4-... K K K N K K
DIL ET K K – N – K
Safety relay
ESR... K K – N K K
Measuring and Monitoring
Relays
EMR4... K K – N – –
Notes K Approved or accepted N Approval or acceptance not
k Approval applied for required
– Not approved or accepted
A1/6 Approvals for world markets
Country-specific approvals
DIL, Z, EMT, PKZ, NZM, (P)N Moeller HPL0211-2007/2008 http://catalog.moeller.net
Country
Test authorities

USA CDN OFF RUS ZA PRC UA


Approvals for world markets

UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST


Contactors
DILM7, DILM9, DILM12, DILM15 K K N K K K K
DILM17, DILM25, DILM32 K K K K K K K
DILM40, DILM50, DILM65 K K K K K K K
DILM80, DILM95, DILM115, DILM150 K K K K K K K
DILMP20 K K N K K K K
DILM…-XHI K K N K K K K
DILM…-XMV K K N K K K K
DILM...-XVB K K N K K K K
DILM...-XSP… K K K K K K K
DILM...-XS1 K K N K K K K
DILM...-XP1 K K N K K K K
DILM...-XSP K K K K K K K
DILEM(-G) K K N K K K K
DILM185, DILM225, DILM250 K K K K K K K
DILM300, DILM400, DILM500 K K K K K K K
DILM580, DILM650, DILM750, DILM820, K K K – K K K
DILM1000, DILM1600
DILH1400, DILH2000 K K K – N K K
DILL K K N – N – –
DILMF K K – – N – –
DILK12 … DILK50 K K N – N – –
Overload relays
ZB12 K K N K K K K
ZB32 K K N K K K K
ZB65 K K N K k K K
ZB150 K K N K k k K
ZE-... K K N K N K K
Z5-.../FF250 K K N K K K K
ZW7-... K K N K N – K
ZW7-630 – – N K N – K
ZEV K K – K N K K
Thermistor relay for machine protection
EMT 6 K K – K N – K
Motor-protective circuit-breakers
PKZM01 K K N K K K K
PKZM0... K K N K K K K
PKZM0-T K K N – N – K
PKZ2.../ZM... K K N K K K K
PKZ2/.../S-SP... K1) K1) N N N – K
PKZM4-... K K N K – K K
Circuit-breaker, Switch-disconnector
P1, P3 K3) K3) N K – K 2)

P5 K K N 2) – 2) 2)

NZM1 K1) K1) K K K 2)

NZM2 K1) K1) K K K 2)

NZM3 K1) K1) K K K 2)

NZM4 K1) K1) K K K 2)

PN1 – – K – – 2)

PN2 – – K – – 2)

PN3 – – K – – 2)

N1 K1) K1) K – K 2)

N2 K1) K1) K – K 2)

N3 K1) K1) K – K 2)

N4 K1) K1) K – K 2)

Notes K Approved or accepted N Approval or acceptance not


k Approval applied for required
1) Switchgear for North America – Not approved or accepted
2) On request
3) Switchgear for North America In surface
mounting enclosure
Approvals for world markets A1/7
Country-specific approvals
http://catalog.moeller.net Moeller HPL0211-2007/2008 T, IZM, FAZ, CI, DM, DS, DE, DF, DV
Country
Test authorities

USA CDN OFF RUS ZA PRC UA

Approvals for world markets


UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST
Rotary switches
T0-..., T3-..., T5-... K K K K K
Circuit-breakers
IZMB(N)(H)2(4)...-800 – – K – K1) K
IZMB(N)(H)2(4)...-1000 – – K – K1) K
IZMB(N)(H)2(4)...-1250 – – K – K1) K
IZMB(N)(H)2(4)...-1600 – – K – K1) K
IZMB(N)(H)2(4)...-2000 – – K – K1) K
IZMB(N)(H)2(4)...-2500 – – K – K1) K
IZMB(N)(H)2(4)...-3200 – – K – K1) K
IZMH3(4)...-4000 – – K – K1) K
IZMH3(4)...-5000 – – K – K1) K
IZMH3(4)...-6300 – – K – K1) K
Supplementary Protectors2)
FAZB..., FAZC..., FAZR..., FAZS... K K – – – –
Miniature circuit-breakers
FAZ, B characteristic K K K – K K
FAZ, C characteristic K K K – K K
FAZ, D characteristic K K K – K K
FAZ-HK K K K – K –
FI... – – – – k k
FI-HK... – – – – k –
ASA, USA K K – – – –
Transformers
STI/STZ K K N N N – K
DTI/DTZ K K N N N – K
UTI K K N N N – –
CI insulated enclosures
CI..-...-NA, CI..-.../(2)T-NA K K – N3) on request K3)
CI..X-...-NA, CI..X-.../T-NA K K – N3) on request K3)
D...-CI..-NA, T-CI...-NA K K – N3) on request K3)
STB...ZOLL K K – N3) on request K3)
FL...-X-NA K K – N3) on request K3)
ZRF3-NA K K – N3) on request K3)
CI-K small enclosure
CI-K...-NA K K – N3) – – K3)
Drives
Soft starters and accessories
DM4-340 K K – – – – –
DS4-340 K K – – – k –
DS6-340 K K – – – k –
DE4-KEY-2 K K – – – – –
DE4-COM-2X K K – – – – –
DE4-NET-DP2 K K – – – – –
Frequency inverters and accessories
DF51-320 K – K – – – –
DF51-322 K – K – – – –
DF51-340 K – K – – – –
DV51-320 K – K – – – –
DV51-322 K – K – – – –
DV51-340 K – – – – – –
DF6-340 K K – – – – –
DV6-340 K K – – – – –

Notes K Approved or accepted N Approval or acceptance not


k Approval applied for required
1) IN switch-disconnectors also have approvals – Not approved or accepted
2) As supplementary protectors up to 40 A only
3) Applies only for standard CI types; not for NA
(North America) versions
A1/8 Approvals for world markets
Shipping classifications
RMQ, FAK, SL, EASY, EC4P Moeller HPL0211-2007/2008 http://catalog.moeller.net
Classification body
GB D N F I RUS PL
Lloyd’s German. Det Bureau Veritas Registro Russian Polski
Approvals for world markets

Register Lloyd Norske Italiano Maritime Rejestr


of Shipping Veritas Navale Register Statków
of Shipping

LR GL DNV BV RINA RS PRS


Control Circuit Devices
RMQ16 K K K K K K K
RMQ-Titan K K K K K k K
FAK…/I – – K K – – –
SL signal towers K K k k N k K
Position switch
LS… K K K K – – –
LS-ZB – K – – – – –
Control relays
EASY512-AB-RC(X) K K K K – – –
EASY512-AC-R K K K K – – –
EASY512-AC-RC(X) K K K K – – –
EASY512-DA-RC(X) K K K K – – –
EASY512-DC-R K K K K – – –
EASY512-DC-RC(X) K K K K – – –
EASY512-DC-TC(X) K K K K – – –
EASY719-AB-RC(X) K K K K – – –
EASY719-AC-RC(X) K K K K – – –
EASY719-DA-RC(X) K K K K – – –
EASY719-DC-RC(X) K K K K – – –
EASY721-DC-TC(X) K K K K – – –
EASY819-AC-RC(X) K K K K – – –
EASY819-DC-RC(X) K K K K – – –
EASY820-DC-RC(X) K K K K – – –
EASY821-DC-TC(X) K K K K – – –
EASY822-DC-TC(X) K K K K – – –
Programmable logic controller – –
EC4P-221-MTXD1 k k k k – – –
EC4P-221-MTXX1 k k k k – – –
EC4P-221-MRXD1 k k k k – – –
EC4P-221-MRXX1 k k k k – – –
EC4P-221-MTAD1 k k k k – – –
EC4P-221-MTAX1 k k k k – – –
EC4P-221-MRAD1 k k k k – – –
EC4P-221-MRAX1 k k k k – – –
EC4P-222-MTXD1 k k k k – – –
EC4P-222-MTXX1 k k k k – – –
EC4P-222-MRXD1 k k k k – – –
EC4P-222-MRXX1 k k k k – – –
EC4P-222-MTAD1 k k k k – – –
EC4P-222-MTAX1 k k k k – – –
EC4P-222-MRAD1 k k k k – – –
EC4P-222-MRAX1 k k k k – – –
Input/output expansion
EASY618-AC-RE K K K K K – –
EASY618-DC-RE K K K K K – –
EASY620-DC-TE – K K K – – –
EASY202-RE – – – – – – –
Coupling device
EASY200-EASY – – – – – – –
Gateways
EASY204-DP – – – – – – –
EASY205-ASI – – – – – – –
EASY221-CO – – K – – – –
EASY222-DN – – – – – – –
EASY223-SWIRE – – – – – – –
Approvals for world markets A1/9
Shipping classifications
http://catalog.moeller.net Moeller HPL0211-2007/2008 EASY, MFD, DIL, ETR, EMR, EMT
Classification body
GB D N F I RUS PL
Lloyd’s German. Det Bureau Registro Russian Polski

Approvals for world markets


Register Lloyd Norske Veritas Italiano Maritime Rejestr
of Shipping Veritas Navale Register Statków
of Shipping

LR GL DNV BV RINA RS PRS


Ethernet module
EASY209-SE – – – – – – –
Multi-function-Display
MFD-80-B K K K K – – –
MFD-80-B-X K K K K – – –
MFD-80 K K K K – – –
MFD-80-X K K K K – – –
MFD-AC-CP8-ME – – – – – – –
MFD-AC-CP8-NT – – – – – – –
MFD-CP8-ME K K K K – – –
MFD-CP8-NT K K K K – – –
MFD-CP4 – – – – – – –
MFD-CP4-500 – – – – – – –
MFD-CP4-800 – – – – – – –
MFD-AC-CP4 – – – – – – –
MFD-AC-CP4-500 – – – – – – –
MFD-AC-CP4-800 – – – – – – –
MFD-R16 K K K K – – –
MFD-T16 K K K K – – –
MFD-RA17 K K K K – – –
MFD-TA17 K K K K – – –
MFD-AC-R16 – – – – – – –
MFD-TP12-PT-A – – – – – – –
MFD-TP12-PT-B – – – – – – –
MFD-TP12-NI-A – – – – – – –
MFD-TAP13-PT-A – – – – – – –
MFD-TAP13-PT-B – – – – – – –
MFD-TAP13-NI-A – – – – – – –
Accessories
EASY200-POW – – – – – – –
EASY400-POW – – – – – – –
EASY256-HCI – – – – – – –
Contactor relays1)
DILER K K K K K K K
DILA, DILA-XHI k k k k – – –
Electronic timing relays
ETR4-… – K – – – – –
EMR4-… – – – – – – –
Contactors2)
DILM7 … DILM15 K K K k – – –
DILM17 … DILM32 K K K k – – –
DILM40 … DILM65 K K K k – – –
DILM80 … DILM150 K K K k – – –
DILMP20 K K K k – – –
DILEM(-G) K K K K K K K
DILM185, DILM225, DILM2503) K K K K K K K
DILM300, DILM400, DILM5003) K K K K K K K
DILM580, DILM650, DILM750, DILM820, K K K K – – –
DILM10003)
DILM1600, DILH1400, DILH2000 K K K k – – –
Thermistor relay for machine
protection
EMT6 – K – – – – –

Notes 1) Switchgear for North America K Approved or accepted


2) The approvals also cover the relevant product accessories. k Approval applied for
3) RA 110, RA 250 N Approval or acceptance not required
– Not approved or accepted
A1/10 Approvals for world markets
Shipping classifications
ZB, T, PKZ, NZM, (P)N, IZM, FAZ, CI Moeller HPL0211-2007/2008 http://catalog.moeller.net

Classification body

GB D N F I RUS PL
Approvals for world markets

Lloyd’s German. Det Bureau Veritas Registro Russian Polski


Register Lloyd Norske Italiano Maritime Rejestr
of Shipping Veritas Navale Register Statków
of Shipping

LR GL DNV BV RINA RS PRS


Overload relays1)
ZB12 K K k k – – –
ZB32 K K k k – – –
ZB65 k K k k – – –
ZB150 k K k k – – –
ZE-... K K K K K K K
Z5-... K K K K K K K
ZW7-..., ZW7-630 – K – – – K K
Rotary switches1)
T0..., T3 K K – K – K –
T 5..., T5B K – – K – – –
Motor-protective circuit-breakers1)
PKZM01 K K k k k k k
PKZM0..., PKZ2.../ZM... K K K K K K K
PKZM4-... K K K k k k K
Circuit-breakers, switch-
disconnectors1)
NZM1, NZM2, NZM3, NZM4 K K K k – – –
PN1, PN2, PN3 – – – k – – –
N1, N2, N3, N4 – K – k – – –
P1, P3 K K – K – – K
P5 2) 2) – 2) – – 2)

Circuit-breakers1)
IZMB(N)1(-4)-…-630 K K K – – – –
IZMB(N)1(-4)-…-800 K K K – – – –
IZMB(N)1(-4)-…-1000 K K K – – – –
IZMB(N)1(-4)-…-1250 K K K – – – –
IZMB(N)1(-4)-…-1600 K K K – – – –
IZMB(N)(H)2(-4)-…-800 K K K – – – –
IZMB(N)(H)2(-4)-…-1000 K K K – – – –
IZMB(N)(H)2(-4)-…-1250 K K K – – – –
IZMB(N)(H)2(-4)-…-1600 K K K – – – –
IZMB(N)(H)2(-4)-…-2000 K K K – – – –
IZMB(N)(H)2(-4)-…-2500 K K K – – – –
IZMB(N)(H)2(-4)-…-3200 K K K – – – –
IZMH3(-4)-…-4000 K K K – – – –
IZMH3(-4)-…-5000 K K K – – – –
IZMH3(-4)-…-6300 K K K – – – –
Switch-disconnectors1)
IN... – – K – – – –
Miniature circuit-breakers1)
FAZ, B characteristic K k K K K – –
FAZ, C characteristic K k K K K – –
FAZ, D characteristic K k K K K – –
FIM K – – – – – –
CI distribution boards
ID – K – – – – –
Notes K Approved or accepted – Not approved or accepted
k Approval applied for N Approval or acceptance not required
1) The approvals also cover the relevant product accessories.
2) On request
Approvals for world markets A1/11
Shipping classifications
http://catalog.moeller.net Moeller HPL0211-2007/2008 RMQ, LS, DIL, ETR, EMR, NZM, (P)N, FAZ

Classification body

GB D N F I RUS PL

Approvals for world markets


Lloyd’s German. Det Norske Bureau Veritas Registro Russian Polski
Register Lloyd Veritas Italiano Maritime Rejestr
of Shipping Navale Register Statków
of Shipping

LR GL DNV1) BV RINA RS PRS


Envi- Volt- Unin- Envi- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin-
ron- age ter- ron- age ter- age ter- age ter- age ter- age ter- age ter-
ment rupted ment rupted rupted rupted rupted rupted rupted
current current current current current current current
V A V A V A V A V A V A V A
Control Circuit
Devices
RMQ16 1, 2, 3 C
Contact elements
E10, E01 – 250 4 – 250 4 250 4 250 4 250 4 250 4 250 4
Indicator lights,
illuminated
pushbuttons,
illuminated selector
switch actuators
Q18(25)L... 24 1W C 24 1W 24 1W 24 1W 24 1W 24 1W 24 1W
RMQ-Titan 1, 2, 3 C on request on request on request on request on request
Contact elements
M22-(C)K(C)... – 500 6 – 500 6 500 6 500 6 500 6 500 6 500 6
LED elements
M22-(C)LED... 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W
230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W
Position switches
LS... – – – C 500 10 – – – – – – – – – –
LS-ZB
Contactor relays
DILA... 1,2,3 500 10 C 500 10 500 10 500 10 – – – – – –
DILER...(-G) 1,2,3 600 10 C 500 10 500 10 500 10 600 10 500 10 500 10
DILR...(-G)TP... 1,2,3 500 10 C 500 10 500 10 500 10 500 10 500 10 500 10
Timing and
monitoring relays
EMT6 – – – A 400 3 – – – – – – – – – –
EMR4 – – – D – – – – – – – – – – – –
ETR4 – – – A 440 – – – – – – – – – – –
Circuit-breakers,
switch-
disconnectors
NZM1 1,2,3 690 1602) C 690 1602) 630 125 3) 3) – – – – – –
NZM2 1,2,3 690 2502) C 690 2502) 690 250 3) 3) – – – – – –
NZM3 1,2,3 690 6302) C 690 6302) 690 630 3) 3) – – – – – –
NZM4 1,2,3 690 16002) C 690 16002) 690 1600 3) 3) – – – – – –
PN1 1,2,3 690 1602) C 690 1602) 690 125 3) 3) – – – – – –
PN2 1,2,3 690 2502) C 690 2502) 690 250 3) 3) – – – – – –
PN3 1,2,3 690 6302) C 690 6302) 690 630 3) 3) – – – – – –
N1 1,2,3 690 1602) C 690 1602) 690 125 3) 3) – – – – – –
N2 1,2,3 690 2502) C 690 2502) 690 250 3) 3) – – – – – –
N3 1,2,3 690 6302) C 690 6302) 690 630 3) 3) – – – – – –
N4 1,2,3 690 16002) C 690 16002) 690 1600 3) 3) – – – – – –
Miniature circuit-
breakers
FAZ, B, C, D 1,2,3 440 63 C 440 63 440 63 440 63 400 63 – – – –
characteristic

Notes 1) For installations inside switchboards/enclosures onboard ships and offshore unit
2) 50 °C Ambient temperature
3) On request
A1/12 Approvals for world markets
Shipping classifications
DIL, Z, T, P, PKZ, Moeller HPL0211-2007/2008 http://catalog.moeller.net

Classification body

GB D N F I RUS PL
Approvals for world markets

Lloyd’s German. Det Norske Bureau Veritas Registro Russian Polski


Register Lloyd Veritas Italiano Maritime Rejestr
of Shipping Navale Register Statków
of Shipping

LR GL DNV1) BV RINA RS PRS


Envi- Volt- Unin- Envi- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin- Volt- Unin-
ron- age ter- ron- age ter- age ter- age ter- age ter- age ter- age ter-
ment rupted ment rupted rupted rupted rupted rupted rupted
current current current current current current current
V A V A V A V A V A V A V A
Contactors
DILEM...(-G) 1,2,3 690 20 C 690 20 690 20 690 20 690 20 690 20 690 16
DILM7-12 1,2,3 690 20 C 690 20 690 20 690 20 – – – – – –
DILM17 1,2,3 690 35 C 690 35 690 35 690 35 – – – – – –
DILM25, 32 1,2,3 690 40 C 690 40 690 40 690 40 – – – – – –
DILM40 1,2,3 690 50 C 690 50 690 50 690 50 – – – – – –
DILM50 1,2,3 690 65 C 690 65 690 65 690 65 – – – – – –
DILM65 1,2,3 690 80 C 690 80 690 80 690 80 – – – – – –
DILM80(…) 1,2,3 690 90 C 690 90 690 90 690 90 – – – – – –
DILM95 1,2,3 690 110 C 690 110 690 110 690 110 – – – – – –
DILM115 1,2,3 690 130 C 690 130 690 130 690 130 – – – – – –
DILM150 1,2,3 690 160 C 690 160 690 160 690 160 – – – – – –
DILM185 1,2,3 1000 225 C 1000 225 1000 225 1000 225 1000 225 1000 225 1000 225
DILM225 1,2,3 1000 250 C 1000 250 1000 250 1000 250 1000 250 1000 250 1000 250
DILM250 1,2,3 1000 300 C 1000 300 1000 300 1000 300 1000 300 1000 300 1000 300
DILM300 1,2,3 1000 350 C 1000 350 1000 350 1000 350 1000 350 1000 350 1000 350
DILM400 1,2,3 1000 450 C 1000 450 1000 450 1000 450 1000 450 1000 450 1000 450
DILM500 1,2,3 1000 550 C 1000 550 1000 550 1000 550 1000 550 1000 550 1000 550
DILM580 1,2,3 1000 800 C 1000 800 1000 800 1000 800 – – – – – –
DILM650 1,2,3 1000 850 C 1000 850 1000 850 1000 850 – – – – – –
DILM750 1,2,3 1000 900 C 1000 900 1000 900 1000 900 – – – – – –
DILM820 1,2,3 1000 1000 C 1000 1000 1000 1000 1000 1000 – – – – – –
DILM1000 1,2,3 1000 1000 C 1000 1000 1000 1000 1000 1000 – – – – – –
DILH1400 1,2,3 1000 1400 C 1000 1400 1000 1400 1000 1400 – – – – – –
DILH2000 1,2,3 1000 2000 C 1000 2000 1000 2000 1000 2000 – – – – – –
Motor protection relay
ZB12 1,2 690 12 A 690 12 690 12 690 12 – – – – – –
ZB32 1,2 690 32 A 690 32 690 32 690 32 – – – – – –
ZB65 1,2 690 65 A 690 65 690 65 690 65 – – – – – –
ZB150 1,2 690 150 A 690 150 690 150 690 150 – – – – – –
ZE-... 1,2 690 9 A 690 9 690 9 690 9 690 9 690 9 690 9
Z5-... – – – A – – 1000 220 – – – – – – – –
ZW7-... – – – A 750 630 – – – – – – 690 630 690 630
T rotary switches, with "disconnect function"
T0-... 1,2,3 690 20 A 660 20 – – 690 20 – – 660 20 – –
T3-... 1,2,3 690 32 A 660 32 – – 690 32 – – 660 32 – –
T5-... – – – – – – – – 690 100 – – – – – –
P switch-disconnector (Miscellaneous switches) with "disconnect function"
P1-... 1,2,3,4 690 32 C 690 32 – – 690 32 – – – – 690 32
P3-... 1,2,3,4 690 100 C 690 100 – – 690 100 – – – – 690 100
Motor-protective circuit-breakers
PKZM01 1,2,3 690 12 A 690 12 690 12 690 12 – – – – – –
PKZM0-...S(E)00... 1,2,3 690 10 A 690 10 690 10 690 10 690 10 690 10 690 10
PKZ 2... 1,2 690 40 A 690 40 660 40 690 40 690 40 690 40 690 40
PKZM4-... 1,2,3 690 63 A 690 63 690 63 690 63 690 63 690 63 690 63

Notes 1) For installations inside switchboards/enclosures onboards ships and offshore units
Switchgear for North America A1/13
Approvals
http://catalog.moeller.net Moeller HPL0211-2007/2008
In the USA, the legally established OSHA (Occupational These devices have smaller physical dimensions and
Safety and Health Act) and the NEC (National Electrical Type Type of approval Approval mark the insulating clearances are not as great as those of
Code) require the use of approved devices and suffix the devices for power distribution. Running production
systems. is also monitored by test authority inspectors, but the

Approvals for world markets


inspection requirements are not as extensive as those
In Canada, all electrical apparatus must comply with for circuit-breakers.
the CEC (Canadian Electrical Code), which requires -NA The device is UL-
that all equipment and installations have CSA and CSA-approved This industrial control equipment is used mainly in
approval. as discrete device. electrical controllers, motor circuits and consumer
circuits of all types, in motor control centres (MCC) and
In view of these requirements, and because US and in power distribution systems. In controllers, they can
Canadian standards deviate widely from those of other FORM The device is CSA- be combined directly with devices for power
industrial countries and the IEC, Moeller has, until CDN approved as discrete distribution, for example with circuit-breakers as main
recently, modified product series to bring them in line device. switches or in a motor feeder.
with North American standards.
FORM The device is UL Performance data for industrial control
New developments are designed as “devices for world USA approved as discrete
markets” from the outset, which means that they meet device. Similar to the “utilization categories for low-voltage
all requirements – including those of the USA and switchgear” of the IEC and other national standards,
Canada – without the need for any additional “duty types” for the various types of switched loads
equipment or modifications. -CNA The device contains have been defined for industrial control equipment in
UL-approved Canada and the USA. The type of load for each duty
In addition to the normal UL and CSA approvals, the components; its type is indicated on the device’s ratings plate or in its
trade regulations originating from the NAFTA approval conditions technical specifications and defines is application
agreements allow the application for a joint UL and must be maintained purpose. The table below provides an overview of this
CSA approval. The devices then carry a logo that is in use. The device is assignment.
recognized in both countries. CSA-approved as
Because market acceptance of the joint approval is still discrete device. Duty type
quite low, Moeller has not made use of this facility until
now. Some local inspectors and end users still refuse to
accept the joint listing. This section of the Catalogue Load type
contains two group of switching devices for North indicated on the
America: ratings plate
Device types in North America
1) Devices for world markets with the following 1) Motors Horsepower
main characteristics: In Canada and the USA, a distinction is made between (HP)
distribution equipment and industrial control
They have all required approvals including the UL and
equipment: 2) Coils Code Designation,
CSA approval (UL = Underwriters Laboratories,
CSA = Canadian Standards Association) and can be Voltampere, Standard
used throughout the world. Distribution equipment (in auxiliary and Pilot Duty or Heavy Pilot
control circuits) Duty
They have ratings plates with all important data for
worldwide use as well as their use in the USA and in This includes, for example
Canada. • Circuit-breakers
For unrestricted sale in European Union member • Disconnectors
states, the devices contain the CE mark. • Switch-disconnector:
• Fuses
• Fused interrupters 3) Resistance (heating) Amperes, resistance only
2) Devices for North America with the following
main characteristics: These devices are of a rugged design and have larger
insulating clearances than other switching devices (for
• They are UL- and/or CSA-approved and can be used
301 … 600 V: 1 inch = 25.4 mm clearance and
in the USA, in Canada and in any country in which
2 inches = 50.8 mm creepage distance). 4) Incandescent lamps Amperes or Watts,
UL- and CSA-approval or conformance with North
In power distribution switchgear (switchgear, tungsten
American standards are required.
switchboards, panelboards), only these devices must Amperes or Watts,
be used for power supply and tap-off. In addition, they tungsten
• They have ratings plates containing all important
are also used as main switches or circuit-breakers in
data for use in the USA and in Canada.
motor and other load circuits in industrial control. 5) Ballast (electric Amperes, ballast
• Except for occasional differences in their design discharge lamps)
Testing of these devices is especially stringent, with
detail required for approval, they are largely
running production being subject to regular checks by
identical with the normal devices of the same
test authority inspectors. The type tests for circuit-
series.
breakers with UL- and CSA-approval are among the
world’s strictest tests.
• Approvals for the USA and for Canada are
indicated by a suffix in the device’s type 6) General Use1) Amperes
Circuit-breakers from Moeller have passed all of these
designation. The type of approval for a device is (A)
tests.
indicated on the ratings plates by the following
type suffixes and approval marks:
Industrial control equipment
• As a rule, devices for North America also carry IEC 1) The “General Use” group corresponds with IEC
or CE-..., for example NZM...-NA circuit-breakers. This includes, for example Category AC-1.
• Contactors
• Contactor relays
• Overload relays
• Motor-protective circuit-breakers
• Rotary switches
• Control circuit devices
• Electronic devices and systems
• User-programmable controllers
A1/14 Switchgear for North America
Selection of devices
Moeller HPL0211-2007/2008 http://catalog.moeller.net
Contactors The “manual self-protected starters” are implemented NZM...OBI circuit-breakers
with a PKZM0 or PKZM4 with an additional, special
In North America, these devices are industrial control BK25/3-PKZ0-E or BK50/3-PKZ4-E incoming terminal. In North America, these devices are circuit-breakers
equipment according to UL 508 and CSA-C 22-2 On the PKZM4, the HB-PKZ4 terminal shroud can be (molded case circuit breakers according to UL 489 or
Approvals for world markets

No. 14). For the North American market, contactors used instead of the incoming terminal. For use in service entrance branch circuit breakers according to
must have so-called “NEMA-sizes”, unless they are Canada, these devices must also be lockable, meaning CSA-C 22.2 No.5.1) and are used mainly in motor
used for switching motors, for which orders will specify that starters must be fitted with the AK-PKZ0 rotary control centres (MCC), controllers and enclosed
ratings in HP. handle. discrete equipment. They are rated in A and – if they
a Page A1/32 are equipped with auxiliary contacts – contain duty
NEMA=National Electrical Manufacturers Association type information (pilot duties, a Page A1/16).
(USA). Type F starters
The devices have adjustable magnetic short-circuit
This part of the Main Catalogue lists the contactors From the combination of a “manual type E starter” releases for short-circuit protection. They can be used
with the HP ratings approved for North America. with a contactor, you can build “type F combination for switching motor circuits and other main circuits,
motor controllers”. These, too do not need an and their auxiliary contacts for switching control
The table on a Page A1/16 provides an overview of additional short-circuit protection device. circuits.
the NEMA sizes in relation to the HP ratings and
continuous currents. Type F starters can be combined and used as per NZM...OBI circuit-breakers are not used as discrete
a Page A1/33. devices; they are always combined to a “combination
“Contactor and overcurrent relay” combinations motor starter” with a downstream contactor and
(“non-combination motor starters”) PKZM motor-protective circuit-breakers overload relay, in which the contactor performs
operational switching and regulation of the motor
First of all, it is important to know that when North In North America, these devices are industrial control current, the overload relay acts as overload protective
American customers speak of “non-combination motor equipment to UL 508 and CSA-C 22.2 No. 14) and are device and the motor-protective circuit-breaker acting
starters” they mean what in Europe is referred to as a used as manually operated motor starters in controllers as short-circuit protection device. This combination
“contactor and overcurrent relay” and will give the or separately as discrete devices. They are rated in HP allows a separate indication of trips caused by
same ordering information as for contactors. Complete and – if they are equipped with auxiliary contacts – overload and by short-circuits through the auxiliary
contactor and overcurrent relay combinations can be they contain duty type information (pilot duties, contact of the overload relay and the motor-protective
assembled as per a Page A1/23. a Page A1/16). The devices have fixed or adjustable circuit-breaker. In North America, combinations of this
magnetic short-circuit releases for short-circuit type are used in motor control centres (MCC) and as
Motor starters protection and adjustable overload relays for motor discrete starters in separate enclosures.
(“Combination motor starter”) overload protection. They can be used for switching
motor circuits, and their auxiliary contacts for At locations with short-circuit currents up to the
Motor starters, which in Europe combine all devices for switching control circuits. switching capacity specified for the complete
short-circuit protection, overload protection and “combination motor starter”, they can be used
operational switching of the motor (such as circuit- In combination with a downstream contactor, they without upstream short-circuit protection device.
breaker, contactor and overcurrent relay), are termed become a “motor starter combination”, in which the
“combination motor starter” in North America. This contactor, acting as “motor controller” switches and In motor starter outputs, they can be used as main
type of motor starter must be configured like a small regulates the motor current and the PKZM provides switches.
control system complete with all relevant individual protection. Although PKZM motor-protective circuit-
devices. Contactor and overcurrent relay are selected breakers have an inherent short-circuit withstand NZM...A circuit-breakers
as previously described. capability, they must, according to North American
standards, always be operated with an upstream short- These devices are circuit-breakers (molded case circuit
Motor starters without additional short-circuit circuit protection device. With most devices, the breakers according to UL 489, service entrance branch
protection specified short-circuit protection device can also be circuit breakers according to CSA-C 22.2 No. 5.1) in
Type E starters used for protecting a group of PKZMs. This property is North America, where they are the normal switches for
referred to as “group-protection” in North America. power distribution systems, but can also be used in
According to UL 508 and CSA C 22.2 No. 14, approved Some devices can be used only for individual motor control centres (MCC) and controllers. They are
motor starters must be short-circuit-protected with UL- protection. rated in A, their short-circuit switching capacity is
or CSA-approved circuit-breakers or fuses. This short- given in kA and – if they are equipped with auxiliary
circuit protection is fitted separately. NZM motor-protective circuit-breakers contacts – contain duty type information (pilot duties,
a Page A1/16).
According to a supplement to UL 508, motor starters In North America, these devices are industrial control
can now also be tested as “combination motor equipment to UL 508 and CSA-C 22.2 No. 14) and are These devices have adjustable magnetic short-circuit
controller type E” for which an additional short-circuit used mainly in controllers and motor control centres releases for short-circuit protection and fixed-current
protection is not required (self-protected starter). This (MCC). They are rated in HP, their short-circuit strength or adjustable overload relays for overload protection
test is also accepted by CSA. is given in kA and – if they are equipped with auxiliary for non-motor-driven outgoing circuits. They can be
contacts – contain duty type information (pilot duties, used as short-circuit protection devices and for
All components for a complete motor starter, including a Page A1/16). switching motor circuits, and their auxiliary contacts
full short-circuit protection, are contained in a single for switching control circuits. At mounting locations
device. This reduces the required space and eliminates The devices have adjustable magnetic short-circuit with short-circuit currents up to their switching
the wiring between the components. These devices releases for short-circuit protection and adjustable capacity, they can be used without upstream short-
are used in motor control centres (MCC), in controllers overload relays for motor overload protection. They circuit protection device.
and as discrete starters in separate enclosures. Up to can be used for switching motor circuits, and their In main current outgoing and incoming lines, they can
the specified switching capacity, these devices do not auxiliary contacts for switching control circuits. be used as main switches.
need additional short-circuit protection.
In combination with a downstream contactor, they T rotary switches, P 1 and P 3 switch-
In the PKZ2 system, these devices are available with become a “motor starter combination”, in which the disconnectors
type designation PKZ2/ZM-../S-SP. contactor, acting as “motor controller” switches and
regulates the motor current and the NZM provides In North America, these devices are industrial control
Manual type E starters protection. equipment to UL 508 and CSA-C 22.2 No. 14) and are
used mainly in controllers and as discrete devices in
In addition, the “type E combination motor NZM motor-protective circuit-breakers can be used in motor circuits. They are rated in HP, their rated current
controllers” comprise the “manual self-protected motor circuits up to the specified short-circuit rating, is given in A and – if they are equipped with auxiliary
starters”, which require larger clearances and whereby the inclusion of a short-circuit protective contacts – they contain duty type information (pilot
creepage distances according to UL 508 or CSA-C 22.2 device in the main incoming supply (for example a duties, a Page A1/16).
No. 5.2 if no upstream short-circuit protective devices motor control centre) is assumed.
are to be used. These devices are suitable for manual The devices can be used for switching motor circuits
switching of motors. and other main circuits, and their auxiliary contacts for
switching control circuits.
Switchgear for North America A1/15
Selection of devices
http://catalog.moeller.net Moeller HPL0211-2007/2008
P 1 and P 3 can be used as main switches in motor To ensure both trouble-free motor starting and short- 3) To some extent, the requirement for NEMA types
circuits and in controllers. The required line fuses are circuit protection of all devices within a circuit, select also covers design details, such as hinged doors or
detailed on the devices’ ratings plates. the smallest fuse required according to criteria 2b), 2c) covers that can be opened and locks only with a
and 2d). tool, external fixing strips for wall-mounting

Approvals for world markets


N switch-disconnectors enclosures, etc. To fulfill the NEMA requirement,
Supplementary Protectors FAZ consult Moeller about the intended application.
In North America, these devices are industrial control 4) Degrees of protection:
equipment to UL 508 and CSA-C 22.2 No. 14) and are In North America, these devices are industrial control The IEC standards define the ingress protection of
used mainly in controllers and motor control centres equipment and protectors (supplementary protectors enclosures against solids and water. The
(MCC). They are rated in HP, their rated current is given according to UL 1077 and CSA-C22.2 No. 235). They comparable standards in Canada and the USA go
in A and – if they are equipped with auxiliary contacts are used mainly in controllers. They can also be used further, also covering protection against ingress of
– they contain duty type information (pilot duties, as additional protective device in electrical devices oil and coolant, and corrosion protection of the
a Page A1/16). whose incomer is already short-circuit protected or enclosure; they also define its place of
does not need short-circuit protection. installation. The table on a Page A1/18 provides
The devices can be used for switching motor circuits an overview of the requirements in Canada and
and other main circuits, and their auxiliary contacts for These devices’ rated current is given in A. They have the USA and a comparison with the IP ratings.
switching control circuits. non-adjustable magnetic short-circuit releases for 5) Sheet steel enclosures:
short-circuit protection and fixed-current or adjustable Sheet steel enclosures can be used for all types of
N switch-disconnectors require an upstream short- overload relays for overload protection for non-motor- controllers. In North America, cables are still laid
circuit protection device. driven outgoing circuits. mainly in metal conduits that act as continuous
earth conductor at the same time. They are
In main current outgoing and incoming lines, both They can be used as overload and short-circuit connected to the enclosure flanges with suitable
devices can be used as main switches. protection devices in single-phase control circuits with metal screwed glands, while flanged enclosures
or without additional neutral pole. They must in ensure continuous conductivity between incoming
Fuse bases and fuses addition be fitted with an upstream short-circuit and outgoing conduits. All enclosures used must
protection device as per device specifications therefore contain metal flanges, and are included
1) Avoid the use of fuses by using fuseless devices, (technical data a Page A1/38). in the protective earthing. Sheet steel enclosures
such as motor-protective circuit-breakers, with metal flanges are also suitable for connecting
observing the selection criteria (a Page A1/17). FAZ supplementary protectors are especially well plastic conduits and cables, which are connected
The reasons for this are as follows: suited for fuseless protection of control circuits on the with commercial glands. In this configuration, an
a) Fuse bases for North American fuses are very secondary side of transformers whose primary side is earth conductor routed with the cabling provides
large and take up a lot of space. already short-circuit protected or does not need short- the protective earthing. The metal flanges can be
circuit protection. taken off for drilling the holes for the glands.
b) NZM circuit-breakers provide current isolation,
short-circuit protection and overload protection
in a single device and are much less expensive Auxiliary contacts, voltage releases Insulated enclosures:
and smaller than a combination of fuse base, The CI enclosures fulfill the North American
fuses and overload relay. For the practice common in Europe of making it statutory design and ingress protection
possible for customers to retrofit devices with auxiliary requirements (laid out by UL 508 and NEMA 250
c) In the USA and in Canada, many different fuse contacts, undervoltage releases, shunt releases and for the USA, in CSA 22.2 No.14 for Canada), and
systems are in use. For non-American vendors, it other accessories, the corresponding UL and CSA are therefore suitable for the assembly of motor
may be almost impossible to find out the fuse approvals can now be issued. starters and miniature and small control systems
system used by the end customer (who may not The modular method makes it possible to extend the for plants and machines. Their absolute corrosion
be known at all to the vendor). range of applications of contactors, circuit-breakers, resistance makes them ideal for use in humid or
d) The plant or machine becomes independent of the PKZ2 system and control circuit devices by fitting corrosive environments. The enclosures are
the locally used fuse system. add-on modules. For detailed information, see the suitable for the connection of both metal conduits
device data. and plastic conduits and cables, which are
2) Because no replacement fuses are needed, spare connected with commercial screwed glands.
parts management is simplified. If the use of fuses Continuous currents and switching duties for auxiliary Because “total insulation” is usually not
is unavoidable, we recommend that you observe the switches according to the tables for auxiliary switches recognized for insulated enclosures in the USA and
following points: on a Page A1/16 are assigned to the code Canada, protective earthing must be implemented
a) North American fuses are classified according to designations and switching duty types indicated in the when these conduits and cables are connected to
physical size, switching capacity and current– devices’ technical specifications and on their ratings them. The earth conductor must be routed through
time characteristics. The table on Seite 17/18 plates. The auxiliary contacts of Moeller devices the enclosures as described in the attached
(Enclosure protection types...) provides a rough approved mainly for “heavy pilot duty”, and on some installation instructions.
overview. It is best, however, to always ask the devices for “standard pilot duty”. For detailed The CI-...-NA enclosures are approved both with
end customer about the required fuse types. information, see the technical data for the devices. The and without insulated flanges. For a full selection
b) Motor circuits: ratings plate for some auxiliary switches contains of UL/CSA-approved CI enclosure types, contact
Where slow fuses (“dual element time delay information such as “600 V, same polarity”. This your regional Moeller sales office. The table on
fuses” or “time delay fuses”) are used: means that adjacent auxiliary contacts of the same a Page A1/18 provides an overview of ingress
Rated current of max. line fuse F 1.75 × rated auxiliary switch or switch block must be connected protection to NEC (National Electrical Code), UL,
motor current or next-higher fuse rated current only to the same control voltage source. NEMA and CSA.
(max. 2.25 ×rated motor current).
Where fast fuses (“non-time delay fuses”) are Enclosures
used:
Rated current of max. line fuse F 3 × rated Requirements:
motor current or next-higher rated fuse current 1) In North America, enclosures are often classified
(max. 4 × rated motor current). and ordered by NEMA type, and in Canada by
EEMAC type, even though the binding design,
c) Circuits with non-motor loads: Select the line
ingress protection, etc. requirements of enclosures
fuse specified by the manufacturer.
are today contained in NEC NFPA 70, UL 508 and
d) Switchgear: UL 50 for the USA, and in CSA-22.2 No. 14 and
For switchgear requiring line fuses for their own CSA-C 22.2 No. 94 for Canada.
short-circuit protection, select fuses according
to the information in the device’s technical data 2) The enclosures used by Moeller are accepted for
or on the ratings plate. For short-circuit use in North America, since they are UL- and CSA-
protection of the combination of Moeller approved and meet the most important NEMA
contactor and overcurrent relay, requirements regarding contact protection,
see a Page A1/23 for the max. line fuses. corrosion protection and ingress protection against
solids and liquids.
A1/16 Switchgear for North America
Switching capacities of auxiliary switches, ratings of 3-phase contactors to NEMA
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Code Conventional Max. switching duty


Designation1) free air thermal
current 120 V AC 240 V AC 480 V AC 600 V AC  600 V AC
Approvals for world markets

Ith

On Off On Off On Off On Off On Off

A A A A A A A A A VA VA
Auxiliary switches in
AC control circuits
Heavy A 150 10 60 6 – – – – – – 7200 720
pilot A 300 10 60 6 30 3 – – – – 7200 720
duty2)
A 600 10 60 6 30 3 15 1.5 12 1.2 7200 720

Standard B 150 5 30 3 – – – – – – 3600 360


pilot B 300 5 30 3 15 1.5 – – – – 3600 360
duty3)
B 600 5 30 3 15 1.5 7.5 0.75 6 0.6 3600 360
E 150 0.5 1.8 0.3 – – – – – – 216 36

Code Conventional Max. switching duty


Designation1) free air thermal
current 125 V DC 250 V DC 310  600 V DC  600 V DC
Ith On/Off On/Off On/Off On/Off

A A A A VA
Auxiliary switches in
DC circuits
Heavy N 150 10 2.2 – – 275
pilot N 300 10 2.2 1.1 – 275
duty2)
N 600 10 2.2 1.1 0.4 275

Standard P 150 1.1 – – 138 –


pilot P 300 5 1.1 0.55 – 138
duty3)
P 600 5 1.1 0.55 0.2 138

– Q 150 2.5 0.55 – – 69


Q 300 2.5 0.55 0.27 – 69
Q 600 2.5 0.55 0.27 0.1 69

– R 150 1 0.22 – – 28
R 300 1 0.22 0.11 – 28

Continuous Rating data4)


current
200 V/60 Hz 230 V/60 Hz 460 V/60 Hz Highest
575 V/60 Hz permissible
A HP HP HP A
Three-phase
contactors to NEMA
00 9 1½ 1½ 2 11
0 18 3 3 5 21
1 27 7½ 7½ 10 32
2 45 10 15 25 52
3 90 25 30 50 104
4 135 40 50 100 156
5 270 75 100 200 311
6 540 150 200 400 621
7 810 – 300 600 932
8 1215 – 450 900 1400
9 2250 – 800 1600 2590

Notes 1) The values 150, 300 and 600 2) “Heavy Pilot Duty” 4) Rating data for 3-phase
indicate the maximum voltage = high switching capacity contactors, for single-speed
for which an auxiliary switch “Standard Pilot Duty” motors, without inching,
can be used. 3) = normal switching capacity reversing or plugging.
PS = HP
Switchgear for North America A1/17
Selection and usage of fuses
http://catalog.moeller.net Moeller HPL0211-2007/2008

Type1) constrution1) Tripping Switching Applications1) For use in


in charac- capacity
teristic1)

Approvals for world markets


USA Canada kAeff
H – Fast 10 Primarily domestic USA, Types H, K and No. 59 “Code”
Canada fit the same bases and are therefore
No. 59 Fast 10 Primarily domestic Canada,USA interchangeable. In the USA,
“Code” the K types are therefore being
increasingly replaced by the RK
types.
Rated current: 1 … 600 A
K K1/K5 – Fast 100 … 200 Protection of circuits for heating, lighting and USA
feeders and outgoers for mixed loads.

– Slow 100 … 200 Protection of circuits for motors, transformers, USA


heating and lighting.

J – Fast 200 See item 2 above USA,Canada Compact design. Types J and
HRCI-J fit the same bases, all other
– Slow 200 See item 3 above. USA,Canada fuse types do not fit into these
bases.
Rated current: 1 … 600 A
HRCI-J Fast 200 See item 2 above USA,Canada

Slow 200 See item 3 above. USA,Canada

RK RK1/RK5 – Fast 100 … 200 See item 2 above USA,Canada Types RK1, RK5 and HRCI-R fit the
same bases, all other fuse types do
– Slow 100 … 200 See item 3 above. USA,Canada not fit into these bases.
Rated current: 1 … 600 A
HRCI-R Fast 100 … 200 See item 2 above Canada,USA

Slow 100 … 200 See item 3 above. Canada,USA

HRCII-R Slow – fast 100 … 200 5. Protection of motor circuits Canada All other fuse types do not fit into
bases for HRCII-R.

CC(CD) – Fast 200 See item 2 above USA,Canada Very compact design; all other fuse
Slow 200 See item 3 above. USA,Canada types do not fit into these bases.
Rated current:
CC 1 … 30 A
CD 31 … 60 A
L – Fast 200 See item 2 above USA,Canada “Code” fuses for higher ratings
Slow 200 See item 3 above. USA,Canada Rated current: 601 … 6000 A

Notes 1) The tripping characteristics data and the assigned applications are a rough overview only.
The practice, it is always advisable to find out both this information and the required fusel
type from the North American end customer.
A1/18 Switchgear for North America
Enclosure protection types to NEC (NFPA 70), UL, CSA, NEMA
Moeller HPL0211-2007/2008 http://catalog.moeller.net
Enclosures Installation site Type of protection Comparable
IP rating3)
Enclosure and ingress protection marking to
Approvals for world markets

NEC NFPA 701)


NEMA No. 250–1997, Appendix A2)
UL 50
CSA-C 22.2 No. 94
Type 1 Indoor installation Protection against accidental contact with live parts and againsta IP20
General use limited amount of falling dirt.

Type 2 Indoor installation Protection against limited amounts of falling water and dirt IP 22
Drip-tight
Type 3 Outdoor installation Protection against falling rain; undamaged by formation of ice on the IP54
Dust-tight, rain-tight,resistant to hail and ice enclosure

Type 3R Outdoor installation Protection against falling rain; undamaged by formation of ice on the IP54
rain-tight,resistant to hail and ice, dust-tight enclosure

Type 3S Outdoor installation Protection against hail; wind-blown dust and wind-blown rain; IP54
dust-tight, rain-tight,resistant to hail and ice External mechanisms remain operable while ice laden.

Type 4 Indoor or outdoor Protection against falling rain, splashing water and hosed water; IP 56
Dust-tight, water-tight, rain-tight installation undamaged by formation of ice on the enclosure

Type 4X Indoor or outdoor Protection against falling rain, splashing water and hosed water; IP 56
dust-tight, water-tight,corrosion-resistant, installation undamaged by formation of ice on the enclosure, corrosion protection
rain-tight

Type 6 Indoor or outdoor Protection against dust and hosed water; IP67
Rain-tight, water-tight, immersible, resistant to installation Protection against entry of water during
hail and ice temporary limited submersion;
Undamaged by formation of ice on the enclosure.
Type 6P Indoor or outdoor Protection against entry of water during prolonged submersion at IP67
Rain-tight, water-tight, submersible, installation limited depths; corrosion-resistant
corrosion-resistant
Type 5 Indoor installation Protection against limited amounts of falling water and dirt; IP 52
Drip-tight, dust-tight, corrosion-resistant corrosion-resistant
Type 12F Indoor installation Protection against dust and dripping water IP 52
or use in industry, drip-tight, dust-tight

Typ 12K4) Indoor installation As Type 12 IP 52


As Type 12
Type 13 Indoor installation Protection against entry of dust, splashing water, IP54
Dust-tight, oil-tight oil and non-corrosive fluids.

Notes 1) NEC = National Electrical Code


2) NEMA = National Electrical Manufacturers Association
3) The IP rating provided as an approximate comparison. A more accurate comparison is not possible, since different
ingress protection tests and assessment criteria apply. The NEMA types cover the corresponding IP ratings but not
the other way round. In general, NEMA/UL enclosure protection testing is subject to stricter criteria.
4) For enclosures with knockouts.
Contactor relay A1/19
DILER, DILR contactor relays, DILET, ETR4 timing relays
http://catalog.moeller.net Moeller HPL0211-2007/2008 DIL(E)R, DILET, ETR4

Rating data for approved Pilot Duty General Use


types1)
UL-File No. E29184

Approvals for world markets


contactor relay
DILER-40(31)(22) A 600, P 300 10 A – 600 V AC,
...(D)DILE 0.5 A – 250 V DC
DILA… A 600, P 300 15 A – 600 V AC,
DILA-XHI 1 A – 250 V DC
Timing relay
DILET, ETR4 B 300 6 A – 250 V AC

Note 1) devices for world markets IEC q UL/CSA

Circuit diagram for North America


ETR4-11, DILET11 ETR4-69 DILET70 ETR4-70
Z1 Z2 Z1 Z2 Z1 Z2
A1 15
A1 15 A1 15 A1 15 25 21
A1 15

A2 16 18
A2 16 18 A2 16 18 X1 A2 16 18 26 28 X1 A2 16 18
22 24

ON-DELAY Function: 11 ON-DELAY Function: 11 ON-DELAY


21 FLEETING CONTACT ON 21 FLEETING CONTACT ON
21 ENERGIZATION 21 ENERGIZATION
42 FLASHING 42 FLASHING
81 PULSE GENERATING CONTACT 81 PULSE GENERATING CONTACT

ETR4-51
Z1 Z2 Z1 Z2 Z1 Z2
A1 17 B1 A1 21
15 Y1 A1 15 B1 A1 15 25 B1 A1 15

A2 18 28 A2 16 18 Y2 A2 16 18 X1 A2 16 18 26 28 X1 A2 16 18
22 24

ON-DELAY Function: 12 OFF-DELAY Function: 12 OFF-DELAY


16 ON- and OFF-DELAY 16 ON- and OFF-DELAY
22 FLEETING CONTACT ON 22 FLEETING CONTACT ON
DE-ENERGIZATION DE-ENERGIZATION
82 PULSE SHAPING CONTACT 82 PULSE SHAPING CONTACT
A1/20 Display and operator units, control circuit devices
Operator panel, RMQ16, RMQ-Titan
MI4, M22, FAK, SL Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved Function Power supply Inputs Outputs Quantity
types1) External Bus side Rated values Rated values Digital
Approvals for world markets

Display and –
operator units
MI42)
MI4-110-KC1 Text operator panel 24 V DC – – – –
MI4-117-KC1 Text operator panel 24 V DC – – – –
MI4-117-KD1 Text operator panel 24 V DC – – – –
MI4-110-KD1 Text operator panel 24 V DC – – – –
MI4-110-KG1 Text operator panel 24 V DC – – – –
MI4-110-KG2 Text operator panel 24 V DC – – – –
MI4-130-TA1 Touch operator panel 24 V DC – – – –
MI4-137-TA1 Touch operator panel 24 V DC – – – –

General technical data


Maximum operating temperature 50 °C (max. 45 °C: MI4-150/160/450/550/570/580/590-TA1)
Terminal cross-section 2 x 1,5 mm2

Notes 1) Devices for world markets IEC q UL/CSA


2) cULus Approval

UL-File No. 29184 Pilot Duty General Use Terminal cross-section

Rating data for


approved types to UL/CSA 1)
RMQ16 contact elements
E10 C 300, Q 300 Cu cable min. AWG 18, max.
E01 C 300, R 300 AWG 14
RMQ-Titan contact elements
M22-K... A 600, Q 300, 10 A –600 V AC 2 x 14 … 18 AWG
M22-CK...  300 V AC 1 A –250 V DC 2 x 12 … 22 AWG
same polarity
RMQ-Titan LED elements
M22-LED... 2 x 14 … 18 AWG
M22-CLED... 2 x 12 … 22 AWG
M22-LC(H) 2 x 16 … 20 AWG
M22-AMC 2 x 16 … 20 AWG

UL 508 requirements NEMA recommendation

UL 4X NEMA 13
Degrees of protection, RMQ-Titan
All front elements M22(S)-... K K
Legend plates M22S-ST... K K
Emergency-Stop labels M22-XAK... K K
M22-XZK... K K
M22-XBK... K K
M22-XYK... K K
Foot and palm switches FAK-... K K
Signal towers SL-... K –

Notes
1) Devices for world markets IEC q UL/CSA and
• For North America, the following order in flush STOP q e. g. M22-D-X + M22-XD-R-GB0
mounting plates and surface mounting START
enclosures: START q e.g. M22-D-X + M22-XD-G-GB1
STOP

START STOP

• For details of degrees of protection, a Page A1/18


Pressure switches, Position switches A1/21
Pressure switches, position switches, conduit adapter
http://catalog.moeller.net Moeller HPL0211-2007/2008 MCS(N), LS
Rating data for approved types to UL/CSA1)
Max. pressure Rated-iinsula Max motor rating HP = PS Rated Part no. Price Std.
tion-voltage operational Article no. See Price pack

Approvals for world markets


to UL/CSA current List
Ui 115 V 200 230 460 575 Ie
V V V
psi2) V AC HP HP HP HP HP A

MCS(N) pressure switches, IP55


With transparent hood
1-pole, for single-phase motors only 4)
65 300 0.253) 0.53) – – – 10 MCS4FORMCDN 1 off
024457
160 0.253) 0.53) – – – MCS11FORMCDN
093273
315 0.253) 0.53) – – – MCS22FORMCDN
014965
MCS(N) pressure switches, IP55
With transparent hood
3 pole4)
65 600 – 3 3 5 7.5 10 MCSN4FORMCDN 1 off
064798
160 – 3 3 5 7.5 MCSN11FORMCDN
036322
230 – 3 3 5 7.5 MCSN16FORMCDN
045814

Notes 1) Devices for world markets: IEC q UL/CSA


2) InNorth America, pressure is stated in pounds/inch (psi) (1 bar = 14.5 psi)
3) Heavy Pilot Duty = High switching capacity
4) Selection data and application notes a Chapter Pressure switches

UL-File No. E29184 Pilot Duty General Use

Rating data for approved types to UL/CSA 1)


Position switches
LS... A 300, Q 300 When using a metal gland
(e.g. V1/2“-M20-NA), this must be earthed
(not total insulation)
Safety interlocks
LS-ZBZ A 300, Q 300 10 A – 300 V AC

UL-approved degrees of protection


NEMA 4 NEMA12 NEMA 13
Position switches
Position switches
LS... K K K
Safety position switches
LS-...-...-ZB K K
Safety interlocks
LS-...-...-ZBZ K K K

Notes 1) Devices for world markets IEC = UL/CSA


For details of degrees of protection a A1/18

For use with Part no. Price Std. pack Notes


Article no. See Price
List

m" conduit adapter


LS V1/2"/M20-NA 10 off The screw connection is for earthing; no total
M20 LSM 225269 insulation
for use with american pipe
thread, metal
1/2"
A1/22 Contactors
DILM contactors – complete units
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved types1) Contactors


GENERAL USE
Maximum AC Maximumm
Approvals for world markets

current- motor-
motor rating rated current
Single-phase Three-phase Ith NEMA size
Open/enclosed

115 V 230 V 200 V 230 V 460 V 575 V


120 V 240 V 208 V 240 V 480 V 600 V
HP HP HP HP HP HP A Part no.
½ 1½ 2 3 5 5 15/13,5 DILEM(4) 00
k 1 1½ 2 3 5 20 DILM7 00
½ 1½ 3 3 5 7½ 20 DILM9 00
1 2 3 3 10 10 20 DILM12 0
1 3 5 10 10 20 DILM15 0
2 3 5 7½ 10 15 35 DILM17 0
2 5 7½ 7½ 15 20 35 DILM25 1
3 5 10 10 20 25 40 DILM32 1
3 7½ 10 15 30 40 55 DILM40 2
3 10 15 20 40 50 65 DILM50 2
5 15 20 25 40 60 80 DILM65 2
7½ 15 25 30 60 75 125 DILM80(…) 3
7½ 15 25 40 75 100 125 DILM95 3
10 25 40 50 100 125 160 DILM115 4
15 30 40 60 125 125 160 DILM150 4
– – 50 60 125 150 225/2) DILM185 4
– – 60 75 150 200 250/2) DILM225 4
– – 75 100 200 250 350/2) DILM250 5
– – 100 125 250 300 350/2) DILM300 5
– – 125 150 300 400 450/2) DILM400 5
– – 150 200 400 500 550/2) DILM500 6
– – 200 200 400 600 630/2) DILM580 6
– – 200 250 500 600 700/2) DILM650 6
– – 250 300 600 700 800/2) DILM750 6
– – 290 350 700 860 850/2) DILM820 6
– – 350 400 800 1000 1000 DILM1000
– – 560 640 1200 1300 1600 DILM1600

Note 1) devices for world markets IEC  UL/CSA


2) please inquire

Please enquire for approvals for:


• Elevator Control
• Refrigeration Control
• Resistance Air Heating
• Incandescent Lamps
• Electrical Discharge Lamps
• Capacitor Switching

Set of connection terminals consisting of three individual


terminals

Conductor material Cross-sections For use with Part no. Price See Price Notes
Article no. see price list List

Cu, Al 2 x (AWG4 to MCM500) DILM500/22 DILM500-XK-CNA 1 off incl- cover with control cable
232192 connection
Cu, Al 2 x (AWG2 to MCM500) DILM580/22 DILM650-XK-CNA incl- cover with control cable
DILM650/22 232193 connection
Cu, Al 4 x (AWG2 to MCM500) DILM750/ DILM820-XK-CNA Incl. terminal cover
22DILM820/22 232194
Cu, Al 1 x (AWG6 to 350MCM) Z5-.../FF250 Z5-FF250-XK-CNA –
229314
Contactors A1/23
Motor starter combinations, DILM/Z
http://catalog.moeller.net Moeller HPL0211-2007/2008

Rating data for approved types1) Contactors Overload


relays Maximum short-circuit protection for North
America

Approvals for world markets


maximum three-phase current Maximumm Fuse Circuit-breaker2)
motor rating motor rated CEC or NEC
PS = HP current
200 V 230 V 460 V 575 V Continuous Short-circuit
208 V 240 V 480 V 600 V current release, non-
delayed
HP HP HP HP A Part no. Part no. 3) A A A
– – ½ ½ 1 DILEM ZE-1 3 15 –
– – ¾ 1 1.4 DILEM ZE-1,6 6 15 –
½ ½ 1 1½ 2.3 DILEM ZE-2,4 6 15 –
– 1 2 3 3.9 DILEM ZE-4 15 15 –
1½ 1½ 3 – 6 DILEM ZE-6 20 15 –
– 2 – – 6.8 DILEM ZE-9 35 15 –
2 2 5 5 7.8 DILEM ZE-9 35 15 –
2 3 5 5 9.6 DILEM ZE-12 45 – –

– – ½ ½ 1 DILM7 ZB-12-1 3 25 200


– – o 1 1.4 DILM7 ZB-12-1,6 6 25 200
½ ½ 1 1½ 2.3 DILM7 ZB-12-2,4 6 25 200
1 1 2 3 3.9 DILM7 ZB-12-4 15 25 200
1½ 1½ 3 – 6 DILM7 ZB-12-6 20 25 200
– – 7½ 9 DILM9 ZB-12-10 25 25 200
– 3 5 7½ 9.6 DILM12 ZB-12-10 25 25 200
– – 7½ 10 11 DILM12 ZB-12-12 45 25 200
– 5 10 – 15.2 DILM15 ZB-12-16 60 40 320

– – ½ ½ 1 DILM17 ZB-32-1 3 25 200


– – o 1 1.4 DILM17 ZB-32-1,6 6 25 200
½ ½ 1 1½ 2.3 DILM17 ZB-32-2,4 6 25 200
1 1 2 3 3.9 DILM17 ZB-32-4 15 25 200
½ 1½ 3 – 6 DILM17 ZB-32-6 20 25 200
– 3 5 7½ 9.6 DILM17 ZB-32-10 25 25 200
– – 7½ 10 11 DILM17 ZB-32-12 40 30 320
– 5 10 – 15.2 DILM17 ZB-32-16 40 30 320
– 7½ 15 20 22 DILM25 ZB-32-24 90 100 1200
– 10 20 25 32.2 DILM32 ZB-32-32 125 125 1200

– 3 5 7.5 9.6 DILM40 ZB-65-10 40 40 380


– 5 10 10 15.2 DILM40 ZB-65-16 60 60 760
– 7½ 20 25 32.2 DILM40 ZB-65-24 90 90 1200
– 10 20 30 34 DILM40 ZB-65-40 125 125 1200
– 20 40 50 54 DILM50 ZB-65-57 200 150 2000
– 20 50 50 63 DILM65 ZB-65-65 200 160 2000

– 25 50 60 68 DILM80 ZB150-70 250 250 2500


– 30 75 100 99 DILM90 ZB150-100 400 400 3200
– 40 100 100 124 DILM115 ZB150-125 500 500 4000
– 60 125 125 156 DILM150 ZB150-150 600 600 4800

50 60 125 150 156 DILM185 Z5-160 600 CLASS J 600 7200


60 75 150 200 192 DILM225 Z5-220 800 CLASS J 800 16000
75 100 200 250 248 DILM250 Z5-250 700 CLASS L 600 –
100 125 250 300 312 DILM300 ZW7-400 1000 1000 –
125 150 300 400 382 DILM400 ZW7-400 1000 1000 –
150 200 400 500 480 DILM500 ZW7-540 1000 600 –

Note 1) devices for world markets IEC  UL/CSA


2) Circuit-breaker a Section 10
3) On request, the ZEV can alternatively be fitted.
A1/24 Contactors
Overload relays
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Auxiliary contacts
Approvals for world markets

Pilot Duty General Use

AC DC AC DC
Type V A V A

DIL(E)EM-10(-01) A600 P300 600 10 250 0.5


...(D)DIL E

DILM7-10(-01) A600 P300 600 15 250 1


to
DILM32-10(-01)

DILA-XHI... A600 P300 600 15 250 1


DILM32-XHI...
DILM1000-XHI11-SI A600 P600 600 10 – –
DILM1000-XHI11-SA
DILM1000-XHI11V-SI

ETS4-VS3 B300 R300 600 – – –

ZE D300 R300 240 1.5 – –


600 0.6 – –

ZB12, ZB32, ZB65, B3001) R300 – – – –


ZB150,Z5, ZW7 B6002) R300 – – – –

Notes 1) at opposite polarity


2) at same polarity

Overload release Contact sequence Auxiliary contacts For use with Short-circuit Part no. Price Std. pack
setting range protection, Article no. See Price
Ir N/O = N/C = CEC/NEC fuse List
A normally normally
open contact closed
contact

ZE overload relay
• Direct mounting
• Approved for North America only
9…12 95 97 1S 1 N/C DILEM 45 ZE-12 1 off
014752

T1 T2 T3 96 98
Rotary Switches, Switch-Disconnector A1/25
Miscellaneous switches with "disconnect function"
http://catalog.moeller.net Moeller HPL0211-2007/2008 T

Rating data for approved types1)


UL-File No. E36332 T0-... T3-... T5B-...

Approvals for world markets


Contacts
Rated operational voltage Ue V AC 600 600 600
Rated uninterrupted current Iu
Current rating A 16 25 65
Pilot Duty A 600 A 600
P 600
Switching capacity
AC-3; max. rated power
40 – 60 Hz AC motors
3-phase 200 V AC HP 3 5 15
230 V AC HP 3 7½ 15
460 V AC HP 10 15 40
575 V AC HP 10 15 50
Single-phase 120 V AC HP ¾ 1½ 3
200 V AC HP 2 3 7½
230 V AC HP 2 3 10
Short-circuit rating
Standard 600 V AC kA 5 5 5
With back-up A 50 80 CLASS J
fuse
with Circuit-breakers Type NZMH6 NZMH6 –
Current setting A 50 125 –
Disconnect in motor circuits 600 V AC kA 10 10 –
With back-up fuse Class 20 A/J 40 A/J –
Terminal cross-section
Terminal cross-section
Cu cable min. AWG 18 14 12
max. AWG 14 10 4
Tightening torque max. Nm 1 2 4

Notes 1)devices for world markets IEC  UL/CSA.


Accessories a Rotary switches for the German market
Do not use AW extension terminals where UL/CSA approval is required.

UL-approved degrees of protection


UL/NEMA 1 UL/NEMA 3R UL/NEMA 12

Rotary switches
T0-.../E; /Z; /SVB K K K
T3-.../E; /Z; /SVB K K K

Notes For details of degrees of protection, a Page A1/18

T rotary switches in NA version

In the NA version the rotary switch has an English text and/or a non-IEC terminal designation. Switches in style
12 to 15 have an extra text on the front of the enclosure (e.g. part no. and degree of protection). Not possible in
connection with key operation S-T0, SVA-T3 and SVC-T3.

An available overview found in the installation instructions 1150…2327.

Type: T0 T3 T5B P1 P3-63 P3-100


construction type
/E; /EA; /EZ +NA +NA
/Z; /V; /IVS 105864 105864
/I2 +NA-I2 +NA-I2
105866 105866
/I4 +NA-I4 +NA-I4
105868 105868
/I5 +NA-I5
105869
A1/26 Rotary switches,Switch-Disconnectors
Switch-disconnectors
P1, P3 Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved types1)


UL-File No. E36332 P1-25 P1-32 P3-63 P3-100
Approvals for world markets

Contacts
Rated operational voltage Ue V AC 600 600 600 600
Rated uninterrupted current Iu
Current rating A 20 30 60 100
Pilot Duty A 600 A 600 – –
P 600 P 600
Switching capacity
AC-3; max. rated power 40 … 60 Hz AC
motors
3-phase 200 V AC HP 5 7½ 15 20
230 V AC HP 5 10 15 25
460 V AC HP 10 20 40 60
575 V AC HP 15 25 50 75
Single-phase 120 V AC HP 1½ 2 3 5
200 V AC HP 3 3 7½ 10
230 V AC HP 3 5 10 15
Short-circuit rating
Standard 600 V AC kA 5 5 10 10
With back-up fuse A 110 110 150 150
with Circuit-breakers Type NZMH6 NZMH6 NZMH6 NZMH9
Current setting A 125 125 125 125
Disconnect in motor circuits 600 V AC kA 10 10 10 –
With back-up fuse Class 50 A/J 50 A/J 100 A 100 A
Terminal capacity
Terminal capacity
Cu cable min./ AWG 14 14 14 14
max. AWG 8 8 3 3
Tightening torque max. Nm 1.6 1.6 3 3

HI 11

Auxiliary switch (1 N/O + 1 N/O contact)


Pilot Duty P 600
Heavy Pilot Duty A 600
General Use 10 A – 600 V AC

Notes 1) Devices for world markets IEC  UL/CSA

UL-File-No:
UL-approved degrees of protection
E 36332 UL/NEMA 3R1) UL/NEMA 12 UL/NEMA 13

Switch-disconnectors
P1-.../EA /SVB K K –
P1-.../V /SVB K K –
P3-.../EA/SVB K K K
P3-.../V/SVB K K K

Notes Details of degrees of protection


1) NEMA recommendation
Rotary switches, Switch-Disconnectors A1/27
Switch-disconnectors
http://catalog.moeller.net Moeller HPL0211-2007/2008 P5

Rating data for approved types P5-125 P5-160 P5-250 P5-315


UL-File No. E36332

Approvals for world markets


Contacts
Rated operational voltage Ui V 600 600 600 600
Rated impulse withstand voltage1) Uimp V AC 8000 8000 8000 8000
Rated uninterrupted current2) Iu A 125 160 250 300
Rated operational current
Ampere-Rating On/Off switches Ie A 1252) 1602) 2502) 3002)
Changeover Ie A 1252) 1602) – –
switches
Non inductive and slightly inductive loads
rated Switching duty
DOL-Rating (similar to AC-3)
3-phase, 3 polig
120 V HP 15 20 30 40
240 V HP 30 40 60 75
480 V HP 60 60 75 100
600 V HP 60 60 75 100
Short-circuit rating
max. back-up fuse, gL characteristic A 125 160 250 315
rated short-time withstand current (1-s-current) A 2500 3000 4600 5800
Terminal capacity
Cu cable
Solid or stranded to box AWG 3/0 3/0 – –
terminal MCM – – 350 350
Flexible without ferrule AWG 2/0 2/0 – –
MCM – – 300 300
Connection with cable lug or busbar M10 x M10 x M12 x M12 x
Terminal screw mm 20 20 20 20
max. Width mm 20 20 25 25
max. width with terminal cover mm 25 25 34 34
Ambient temperature open on 100 % Iu/Ith 50 °C over 24 hours with peaks up to 55 °C
enclosed on 100% Ithe 35 °C over 24 hours with peaks up to 40 °C

Notes 1) valid for mains with earth star point, overvoltage category III, pollution degree 3
2) valid for connection with cables for 75°C

Rating data for approved types P3-30…MCS P3-60…MCS P3-90…MCS


UL-File No. E14
CSA-File No. 1342868 (LR12528)
Switching capacity 1)
Sym. rms (60 Hz)
480 V kA 10 10 10
Terminal capacity
Cu cable AWG 10 4 2
Torque Nm 3 3 3

Notes 1) with
protection by CLASS H fuses of max 100 A.
Caution no overvoltage protection

P3… P3…/N P3…/3N/HI11 P3…/HI11 P3…/2HI11


L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
1 3 5 N 1 3 5 N 13 21 1 3 5 13 21 1 3 5 13 21 31 43

2 4 6 N 2 4 6 N 14 22 2 4 6 14 22 2 4 6 14 22 32 44

T1 T2 T3 T1 T2 T3 T1 T2 T3 T1 T2 T3 T1 T2 T3
I I I I I
0 0 0 0 0
A1/28 Rotary switches, Switch-Disconnectors
Auxiliary contacts
HI11, HI21 Moeller HPL0211-2007/2008 http://catalog.moeller.net

HI11 HI21-P5-125(160) HI21-P5-250(315)


Approvals for world markets

Auxiliary contacts
Standards and regulations
Rated insulation voltage Ui V AC 600 600
Rated uninterrupted current Iu A 10 10
Rated operational current Ie
Pilot Duty P600 P600 P600
Heavy Pilot Duty A600 A600 A600
General Use 10 A - 600 V AC – –
Ampere-Rating
Non inductive and slightly inductive loads – 10 10
Short-circuit rating
max. fuse gL-characteristic A – 16 16
Terminal capacity
Solid/stranded AWG – 12 12
flexible without ferrule AWG – 14 14

Notes 1) Devices for world markets IEC q UL/CSA


Motor-protective circuit-breakers A1/29
PKZM motor-protective circuit-breakers
http://catalog.moeller.net Moeller HPL0211-2007/2008 PKZM01, PKZM0, PKZM4

Rating data for approved types1) Maximum motor rating Setting ranges Maximum protective device to UL/CSA
UL 508/CSA C 22.2 No. 14 AC Group protection2)
HP = PS

Approvals for world markets


Overload Short-circuit to max. short- Maximum fuse Maximum
Releases release circuit current circuit-breaker
200 V 230 V 460 V 575 V 600 V with with with
CL CL CL

HP HP HP HP A A kA kA A A A A
PKZM01 “Manual Motor Starter with thermal and magnetic trip”
motor-protective circuit-breakers
PKZM01-0,16 3) 0.1 – 0.16 2.2 50 600 600
PKZM01-0,25 0.16 – 0.25 3.4 50 600 600
PKZM01-0,4 0.25 – 0.4 5.6 50 600 600
PKZM01-0,63 0.4 – 0.63 8.8 50 600 600
PKZM01-1 ½ ½ 0.63 – 1 14 50 600 600
PKZM01-1,6 ¾ 1 1 – 1.6 22 50 600 600
PKZM01-2,5 ½ ½ 1 1½ 1.6 – 2.5 35 50 600 600
PKZM01-4 1 1 2 3 2.5 – 4 56 50 600 600
PKZM01-6,3 1½ 1½ 3 5 4 – 6.3 88 50 600 600
PKZM01-10 3 3 7½ 10 6.3 – 11 140 22 50 150 600 125 600
PKZM01-12 3 3 7½ 10 9 – 12 168 18 50 150 600 125 600
PKZM01-16 3 5 10 10 10 – 16 224 10 50 150 600 125 600
PKZM0 “Manual Motor Starter with thermal and magnetic trip”
motor-protective circuit-breaker
PKZM0-0,16 3) 0.1 – 0.16 2.2 50 600 600
PKZM0-0,25 0.16 – 0.25 3.4 50 600 600
PKZM0-0,4 0.25 – 0.4 5.6 50 600 600
PKZM0-0,63 0.4 – 0.63 8.8 50 600 600
PKZM0-1 ½ ½ 0.63 – 1 14 50 600 600
PKZM0-1,6 ¾ 1 1 – 1.6 22 50 600 600
PKZM0-2,5 ½ ½ 1 1½ 1.6 – 2.5 35 50 600 600
PKZM0-4 1 1 2 3 2.5 – 4 56 50 600 600
PKZM0-6,3 1½ 1½ 3 5 4 – 6.3 88 50 600 600
PKZM0-10 3 3 7½ 10 6.3 – 11 140 22 50 150 600 125 600
PKZM0-12 3 3 7½ 10 9 – 12 168 18 50 150 600 125 600
PKZM0-16 3 5 10 10 10 – 16 224 10 50 150 600 125 600
PKZM0-20 5 5 10 15 16 – 20 280 10 18 150 600 125 600
PKZM0-25 5 7½ 15 15 20 – 25 350 10 18 150 600 125 600
PKZM0-32 7½ 10 20 20 24 – 32 448 10 18 150 600 125 600
PKZM4
motor-protective circuit-breakers
PKZM4-16 3 5 10 15 10 … 16 224 50 600 600
PKZM4-25 7½ 7½ 20 25 16 … 25 350 50 600 600
PKZM4-32 10 10 25 30 25 … 34 448 50 600 600
PKZM4-40 10 15 30 40 32 … 42 560 50 600 600
PKZM4-50 10 15 30 40 40 … 52 700 10 600 600
PKZM4-58 15 15 40 50 50 … 56 812 10 600 600
PKZM4-63 15 15 40 50 52 … 58 882 10 600 600

Notes Service Factor (SF) 1) Devices for world markets IEC  UL/CSA
Set value Ir, on the current scale, depending on the load factor 2) Attention: Changed requirements for group protection
SF = 1.15 l Ir = 1 x In mot 3) Calculate motor power in this range according to the rated current.
SF = 1 l Ir = 0,9 x In mot Stated values to NEC Table 430 … 150
A1/30 Motor-protective circuit-breakers
Compact starters PKZM0, Insulated enclosures
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved types1) Maximum motor rating Setting ranges Maximum protective device to UL/CSA
UL 508/CSA C 22.2 No. 14 AC Group protection2)
HP = PS Overload Short-circuit to max. short- Maximum Maximum
Approvals for world markets

Releases releases circuit current fuse circuit-


200 V 230 V 460 V 575 V breaker
PKZM...
HP HP HP HP A A kA A A
Compact starter PKZM “Manual Motor Starter with thermal, magnetic trip and contactor”
PKZM0-0,16/SE00-11(...) 3) 0.1 … 0.16 2.2 50 600 600
PKZM0-0,25/SE00-11(...) 0.16 – 0.25 3.4 50 600 600
PKZM0-0,4/SE00-11(...) 0.25 – 0.4 5.6 50 600 600
PKZM0-0,63/SE00-11(...) 0.4 – 0.63 8.8 50 600 600
PKZM0-1/SE00-11(...) ½ ½ 0.63 … 1 14 50 600 600
PKZM0-1,6/SE00-11(...) ¾ 1 1 … 1.6 22 50 600 600
PKZM0-2,5/SE00-11(...) ½ ½ 1 1½ 1.6 – 2.5 35 50 600 600
PKZM0-4/SE00-11(...) 1 1 2 3 2.5 – 4 56 50 600 600
PKZM0-6,3/SE00-11(...) 1½ 1½ 3 5 4 – 6.3 88 504) 600 600
PKZM0-10/SE00-11(...) 3 3 7½ 10 6.3 – 11 140 10 150 1255)
Contact module for PKZM0 “Contact Module”
AC or DC operated
SE00-11-PKZ0(...) 2 3 5 5 Auxiliary
contacts
Pilot Duty: A 600, Q 300 General Use: 10 A/600 V AC, 1 A/250 V DC
Notes Service Factor (SF) 1) Devices for world markets IEC  UL/CSA .
Set value Ir, on the current scale, depending on the load 2)Attention: Changed requirements for group protection
factor 3) Calculate motor power in this range according to the rated current.
SF = 1.15 l Ir = 1x In mot Stated values to NEC Table 430 … 150
SF = 1 l Ir = 0,9 x In mot 4) up to 6,3 A combination no welding of SE00
5) 22 kA 600 V AC

Degree of For use with Part no. Price


protection Article no. see price Std. pack
list

Insulated enclosures for surface mounting


For PKZM01 motor-protective circuit-breakers
IP41 PKZM01-... CI-PKZ01-NA 2 off Intergrated terminal for
+NHI or U or A 281408 PE(N)
+NHI-E or VHI
+L (2 off)

With operating membrane IP65 CI-PKZ01-NA-G 2 off


281409

Can be locked in O position IP65 PKZM01-... CI-PKZ01-NA-SVB1) 2 off


+U or A 281630
Lockable in off position, in IP65 +NHI-E or VHI CI-PKZ01-NA-SVB-V1) 2 off
combination with VHI-PKZ01 +L (2 off) 281945
With Emergency-Stop mushroom- IP65 CI-PKZ01-NA-PVT1) 2 off
headed pushbutton, stay-put 281631
with EMERGENCY STOP mushroom IP65 CI-PKZ01-NA-PVS1) 2 off
button, released by key 281632
For PKZM0 motor-protective circuit-breakers
With black-grey rotary knob IP55 PKZM0-... CI-K2-PKZ0-NA-G 2 off Integrated N and PE(N)
+NHI+NHI-E or 262680 terminal, base without
with red-yellow rotary knob, for use IP55 U+NHI-E or A+NHI-E CI-K2-PKZ0-NA-GR 2 off knock-outs
as EMERGENCY STOP switch in +L-PKZ0 (2 off) 262681
accordance with VDE 0113
For PKZM0 motor-protective circuit-breakers with early-make auxiliary contacts
With black-grey rotary knob IP55 PKZM0-... CI-K2-PKZ0-NA-GV 2 off Integrated N and PE(N)
+VHI... + U... 262682 terminal, base without
with red-yellow rotary knob, for use IP55 +L-PKZ0 (2 off) CI-K2-PKZ0-NA-GRV 2 off knock-outs
as EMERGENCY STOP switch in 262683
accordance with VDE 0113

UL-approved degrees of protection


UL/NEMA 1 UL/NEMA 12 UL/NEMA 3R
Insulated enclosures
CI-K2-PKZ0-NA-G(R) K K K
CI-K2-PKZ0-NA-G(R)V K K K
E-PKZ0-G(R)1) K K K

Notes 1) NEMA recommendation


For details of degrees of protection, a Page A1/18
Motor-protective circuit-breakers A1/31
Accessories
http://catalog.moeller.net Moeller HPL0211-2007/2008 PKZM

Rating data for approved types1) For use with Pilot Duty General Use
UL 508/CSA C 22.2 No. 14

Approvals for world markets


Accessories
Standard auxiliary contacts NHI11-PKZ0 PKZM0(-T) A 600, Q 300 5 A – 600 V AC –
NHI12-PKZ0 PKZM4 1 A – 250 V DC
NHI21-PKZ0
NHI2-11S-PKZ0
NHI-E-11-PKZ0 E150 0,5 A – 250 V AC –
NHI-E-10-PKZ0
Early-make auxiliary contacts VHI20-PKZ0 PKZM0(-T) E150 0,5 A – 250 V AC –
VHI20-PKZ01 PKZM01
Trip-indicating auxiliary contacts AGM2-10-PKZ0 PKZM0(-T) A 600, Q 300 5 A – 600 V AC –
AGM2-01-PKZ0 PKZM4 1 A – 250 V DC

Voltage releases A-PKZ0(...) PKZM0(-T) – – Actuating voltages and ordering


U-PKZ0(...) PKZM4 information a Products for the
German market
Auxiliary switches for contact HI11-S/EZ-PKZ0 PKZM0 A 600, Q 300 5 A – 600 V AC –
module 1 A – 250 V DC

Notes 1) Devices for world markets IEC = UL/CSA

Seperate mounting for contact Extension shaft


module A-H-PKZ0 –
EZ-PKZ0 –
Current limiter
Mechanical interlock for contact CL-PKZ0 –
module
MV-PKZ0 – Lockable rotary handle
AK-PKZM0 –
Suppressors for (high-capacity)
contact module in AC version Terminal, three-phase commoning
RC-S PKZ0 RC suppressor, CSA-approved link
VG-S PKZ0 Varistor suppressor, CSA-approved BK25/3-PKZ0 Maximum continuous current 63 A
BK25/3-PKZ0-E Maximum continuous current 60 A, for
Clip plates surface mounting of type E starters
C-PKZ0 – BK50/3-PKZ4-E Maximum continuous current 120 A,
Door coupling handles for surface mounting of type E starters
H-PKZ0 A-H-PKZ0 extension shaft included as Reversing starter wiring kits
RH-PKZ0 standard MVS-WB-... –
PKZM0 three-phase commoning Star-delta wiring kits
links MVS-SB-... –
B3...-PKZ0 –
PKZM4 three-phase commoning
links
B3...-PKZ4 –
Shroud for unused terminals
H-B3-PKZ4 –
A1/32 Motor-protective circuit-breakers
Type E Starters
PKZM0 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Type E starters to UL 508 are
assembled from a standard PKZM and
a special incoming terminal or
terminal shroud: Maximum motor
Approvals for world markets

rating
Setting ranges
AC Overload Short-circuit Rated short-circuit breaking Type Type
HP = PS Releases releases capacity Motor-protective Incoming-
200 V 230 V 460 V 575 V 240 V 480 V 600 V circuit-breaker terminal
277 V2) 347 V2)

HP HP HP HP A A kA kA kA

PKZM0 motor-protective circuit-breakers “Manual self-protected motor starters”


1) 0.1 – 0.16 2.2 50 50 50 PKZM0-0,16 BK25/3-PKZ0-E
0.16 – 0.25 3.4 50 50 50 PKZM0-0,25 BK25/3-PKZ0-E
0.25 – 0.4 5.6 50 50 50 PKZM0-0,4 BK25/3-PKZ0-E
0.4 – 0.63 8.8 50 50 50 PKZM0-0,63 BK25/3-PKZ0-E
½ ½ 0.63 – 1 14 50 50 50 PKZM0-1 BK25/3-PKZ0-E
¾ 1 1 – 1.6 22 50 50 50 PKZM0-1,6 BK25/3-PKZ0-E
½ ½ 1 1½ 1.6 – 2.5 35 50 50 50 PKZM0-2,5 BK25/3-PKZ0-E
1 1 2 3 2.5 – 4 56 50 50 50 PKZM0-4 BK25/3-PKZ0-E
1½ 1½ 3 5 4 – 6.3 88 50 50 50 PKZM0-6,3 BK25/3-PKZ0-E
3 3 7½ 10 6.3 – 11 140 50 50 50 PKZM0-10 BK25/3-PKZ0-E
3 3 7½ 10 9 … 12 168 42 42 18 PKZM0-12 BK25/3-PKZ0-E
3 5 10 10 10 – 16 224 42 42 18 PKZM0-16 BK25/3-PKZ0-E
5 5 10 – 16 … 20 280 18 18 – PKZM0-20 BK25/3-PKZ0-E
5 7½ 15 – 20 … 25 350 18 18 – PKZM0-25 BK25/3-PKZ0-E
7½ 10 20 – 24 … 32 448 18 18 – PKZM0-32 BK25/3-PKZ0-E
3 5 10 15 10 … 16 224 50 50 25 PKZM4-16 BK50/3-PKZ4-E
5 7½ 15 20 16 … 27 350 50 50 25 PKZM4-25 BK50/3-PKZ4-E
7½ 10 25 30 24 … 34 448 50 50 25 PKZM4-32 BK50/3-PKZ4-E
10 15 30 30 32 … 40 560 50 50 25 PKZM4-40 BK50/3-PKZ4-E
10 15 30 – 40 … 52 700 50 50 – PKZM4-50 BK50/3-PKZ4-E
15 15 40 – 50 … 56 812 50 50 – PKZM4-58 BK50/3-PKZ4-E
15 15 40 – 52 … 58 882 50 50 – PKZM4-63 BK50/3-PKZ4-E

Price
For use with See Price Std. pack
List

Incoming terminal
For surface mounting type E starters for North Part no.
America
PKZM0 BK25/3-PKZ0-E 5 off For three-phase commoning link,
262518 finger and back-of-hand-proof,
Ue = 690 V, Iu = 60 A
for conductor cross-sections:
2.5 … 25 mm2 flexible
2.5 … 16 mm2 flexible with ferrule
AWG 14 … 6
PKZM4 BK50/3-PKZ4-E Can be combined with B3...-PKZ4
272165 three-phase commoning link
Terminal shroud
For surface mounting type E starters for North America
PKZM4 HB-PKZ4
256581

Notes Type E starters do not need an upstream protective device. 1) Calculatemotor power in this range according to the rated current.
For use in Canada, the PKZM0/PKZM4 must be fitted with an Stated values to NEC Table 430 … 150
AK-PKZ0. 2) Suitable
for networks with earthed star-point

Service Factor (SF)


Set value Ir, on the current scale, depending on the load
factor
SF = 1.15 l Ir = 1 x In mot
SF = 1 l Ir = 0.9 x In mot
Motor-protective circuit-breakers A1/33
Type F starter combinations
http://catalog.moeller.net Moeller HPL0211-2007/2008 PKZM0

Maximum motor rating Setting ranges


AC Overload Short-circuit Rated short-circuit breaking

Approvals for world markets


HP = PS Releases release capacity
200 V 230 V 460 V 575 V 240 V 480 V 600 V Incoming terminal Motor- Contactor
277 V2) 347 V2) protective
circuit-breakers
HP HP HP HP A A kA kA kA

1) 0.1 – 0.16 2.2 50 50 50 BK25/3-PKZ0-E PKZM0-0,16 DILEM-... or DILM7-…

0.16 – 0.25 3.4 50 50 50 BK25/3-PKZ0-E PKZM0-0,25 DILEM-... or DILM7-…

0.25 – 0.4 5.6 50 50 50 BK25/3-PKZ0-E PKZM0-0,4 DILEM-... or DILM7-…

0.4 – 0.63 8.8 50 50 50 BK25/3-PKZ0-E PKZM0-0,63 DILEM-... or DILM7-…

½ ½ 0.63 – 1 14 50 50 50 BK25/3-PKZ0-E PKZM0-1 DILEM-... or DILM7-…

¾ 1 1 – 1.6 22 50 50 50 BK25/3-PKZ0-E PKZM0-1,6 DILEM-... or DILM7-…

½ ½ 1 1½ 1.6 – 2.5 35 50 50 50 BK25/3-PKZ0-E PKZM0-2,5 DILEM-... or DILM7-…

1 1 2 3 2.5 – 4 56 50 50 50 BK25/3-PKZ0-E PKZM0-4 DILEM-... or DILM7-…

1½ 1½ 3 5 4 – 6.3 88 50 50 50 BK25/3-PKZ0-E PKZM0-6,3 DILEM-... or DILM7-…

3 3 7½ 10 6.3 – 11 140 50 50 50 BK25/3-PKZ0-E PKZM0-10 DILM9-…

3 3 7½ – 9 – 12 168 18 18 – BK25/3-PKZM0-E PKZM0-12 DILM12-…

3 5 10 – 10 – 16 224 18 18 – BK25/3-PKZ0-E PKZM0-16 DILM17-…

5 5 10 – 16 … 20 280 18 18 – BK25/3-PKZ0-E PKZM0-20 DILM25-…

5 7½ 15 – 20 … 25 350 18 18 – BK25/3-PKZ0-E PKZM0-25 DILM25-…

7½ 10 20 – 25 … 32 448 18 18 – BK25/3-PKZ0-E PKZM0-32 DILM32-…

3 5 10 15 10 – 16 224 50 50 50 BK50/3-PKZM4-E PKZM4-16 DILM17-…

5 7½ 15 20 16 … 27 350 50 50 50 BK50/3-PKZM4-E PKZM4-25 DILM25-…

7½ 10 25 30 24 … 34 448 50 50 50 BK50/3-PKZM4-E PKZM4-32 DILM32-…

10 15 30 30 32 … 40 560 50 50 50 BK50/3-PKZM4-E PKZM4-40 DILM40

1) 0.1 – 0.16 2.2 18 18 18 BK25/3-PKZ0-E PKZM0-0,16 SE00-...-PKZ0(...)

0.16 – 0.25 3.4 18 18 18 BK25/3-PKZ0-E PKZM0-0,25 SE00-...-PKZ0(...)

0.25 – 0.4 5.6 18 18 18 BK25/3-PKZ0-E PKZM0-0,4 SE00-...-PKZ0(...)

0.4 – 0.63 8.8 18 18 18 BK25/3-PKZ0-E PKZM0-0,63 SE00-...-PKZ0(...)

½ ½ 0.63 – 1 14 18 18 18 BK25/3-PKZ0-E PKZM0-1 SE00-...-PKZ0(...)

¾ 1 1 – 1.6 22 18 18 18 BK25/3-PKZ0-E PKZM0-1,6 SE00-...-PKZ0(...)

½ ½ 1 1½ 1.6 – 2.5 35 18 18 18 BK25/3-PKZ0-E PKZM0-2,5 SE00-...-PKZ0(...)

1 1 2 3 2.5 – 4 56 18 18 18 BK25/3-PKZ0-E PKZM0-4 SE00-...-PKZ0(...)

1½ 1½ 3 5 4 – 6.3 88 18 18 18 BK25/3-PKZ0-E PKZM0-6,3 SE00-...-PKZ0(...)

3 3 7½ 10 6.3 – 11 140 18 18 18 BK25/3-PKZ0-E PKZM0-10 SE00-...-PKZ0(...)

Notes Type F starter combinations do not need an upstream protective device. For 1) Calculate motor power in this range according to the rated current.
use in Canada, the switch must be fitted with an AK-PKZ0. Stated values to NEC Table 430 … 150
2) Suitable for networks with earthed star-point
Service Factor (SF)
Set value Ir on the current scale, depending on the load factor
SF = 1.15 l Ir = 1 x In mot
SF = 1 l Ir = 0.9 x In mot
A1/34 Motor-protective circuit-breakers
Motor-protective circuit-breakers,Circuit-breakers
PKZ2, PKZ2…-CB Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved types1) Maximum motor rating Setting ranges Maximum protective device to UL/CSA
UL 508/CSA C 22.2 No. 14
AC Overload short-
Approvals for world markets

HP = PS Releases circuit Group protection1)


releases
up to max. Maximum Maximum
short-circuit fuse circuit-
current breaker
200 V 230 V 460 V 575 V 480 V 600 V
HP HP HP HP A A kA kA A A
PKZ2 motor-protective “Manual Motor Starter with thermal and magnetic trip”
circuit-breaker
PKZ2/ZM-0,6 2) 0.4 … 0.6 5…8 65 42 500 600
PKZ2/ZM-1 ½ ½ 0.6 … 1 8 … 14 65 42 500 600
PKZ2/ZM-1,6 ¾ 1 1 … 1.6 14 … 22 65 42 500 600
PKZ2/ZM-2,4 ½ ½ 1 1½ 1.6 … 2.4 20 … 35 65 42 500 600
PKZ2/ZM-4 1 1 2 3 2.4 … 4 35 … 55 65 42 500 600
PKZ2/ZM-6 1½ 1½ 3 5 4…6 50 … 80 65 42 500 600
PKZ2/ZM-10 2 3 5 7½ 6 … 10 80 … 140 65 42 500 600
PKZ2/ZM-16 3 5 10 10 10 … 16 130 … 220 65 42 500 600
PKZ2/ZM-25 7½ 7½ 20 25 16 … 27 200 … 350 65 42 500 600
PKZ2/ZM-32 10 10 20 30 24 … 32 275 … 425 65 42 500 600
PKZ2/ZM-40 10 15 30 30 32 … 42 350 … 500 65 42 500 600
High-capacity “Manual Motor Starter with thermal, magnetic trip and contactor”
compact starter PKZ2
PKZ2/ZM-0,6/S(...) 2) 0.4 … 0.6 5…8 65 42 2000 2000
PKZ2/ZM-1/S(...) ½ ½ 0.6 … 1 8 … 14 65 42 2000 2000
PKZ2/ZM-1.6/S(...) ¾ 1 1 … 1.6 14 … 22 65 42 2000 2000
PKZ2/ZM-2,4/S(...) ½ ½ 1 1½ 1.6 … 2.4 20 … 35 65 42 2000 2000
PKZ2/ZM-4/S(...) 1 1 2 3 2.4 … 4 35 … 55 65 42 2000 2000
PKZ2/ZM-6/S(...) 1½ 1½ 3 5 4…6 50 … 80 65 42 2000 2000
PKZ2/ZM-10/ 2 3 5 7½ 6 … 10 80 … 140 65 42 2000 2000
PKZ2/ZM-16/S(...) 3 5 10 10 10 … 16 130 … 220 65 42 2000 2000
PKZ2/ZM-25/S(...) 7½ 7½ 20 25 16 … 27 200 … 350 65 42 2000 2000
PKZ2/ZM-32/S(...) 10 10 20 30 24 … 32 275 … 425 65 42 2000 2000
PKZ2/ZM-40/S(...) 10 15 30 30 32 … 42 350 … 500 65 42 2000 2000
High-capacity contact module "Contact module" in combination with PKZ2/ZM(R)-...
motor-protective circuit-breaker or base for separate mounting of EZ-PKZ2
S-PKZ2(...) 10 15 30 30
S/HI20-S-PKZ2(...) 10 15 30 30
S-G-PKZ2(...) 10 15 30 30
Reversing combination "Reversing combination" in combination with ZM-...PKZ2 trip block for motor protection
PKZ2/SW-MV-11(...) 10 15 30 30
Reversing busbar system 42 A 600 V AC
For UL/CSA-conformance, oder a BK50/3-PKZ2 terminal separately.
1)Attention:
Changed requirements for 2)Calculatemotor power in this range
group protection according to the rated current.

Setting range Group protection Part no. Price Std. pack Notes
Overload releases Short-circuit releases Short-circuit power Article no. See Price
at 240 V List
Ir Irm
A A kA

PKZ2 circuit-breaker
Rating data for approved types
UL 489
10…16 130…220 10 PKZ2/ZM-16-CB 1 off Service Factor (SF)
264044 Set value Ir on the current scale,
depending on the load factor
SF = 1.15 a Ir = 1 x In mot
SF = 1 a Ir = 0.9 x In mot
PKZ2/S-SP Self-Protected Starter A1/35
DOL starters, reversing starters
http://catalog.moeller.net Moeller HPL0211-2007/2008 PKZ2

Maximum motor rating Rated short-circuit breaking Part no. Price


Three-phase current capacity Article no. see price Std. pack
HP = PS list

Approvals for world markets


200 V 230 V 460 V 575 V 240 V 480 V 600 V
HP HP HP HP kA kA kA

Basic unit
In combination with ZM-...-PKZ2 trip block for motor protection
a Industrial Swithchgesr Catalogue, Sect. 8
The given values are maximum values that depend on the trip block.

Direct-on-line starter
10 15 30 25 100 65 42 PKZ2/S-SP(120V60HZ) 1 off
050940

Reversing starters 2)
10 15 30 25 100 65 42 PKZ2/S-SP-FVR(*V*HZ) 1 off
925109

Notes 1) Calculate motor power in this range according to the rated current. Stated values to NEC Table 430 … 150
2) Specify actuating voltage in the range 24 – 600 V 50 oder 60 Hz.

Main system application up to 27 A 600 Y/347 V AC


480 Y/277 V AC
27 A up to 42 A 480 Y/277 V AC

Service Factor (SF) Setting range Ir of curent scale in dependence on load factor
SF = 1.15 r Ir = 1 x In mot
SF = 1 r Ir = 0.9 x In mot

Terminal capacities PKZ2/ZM.../S high-capacity compact starters


Main terminals
Cables Cu 75 °C, min. AWG 14, max. AWG 6
Torque1.8 Nm
Control circuit terminals
Cables min. AWG 20, max. AWG 16 (0.5 … 1 mm2)
with insulated/uninsulated blade terminal, nominal size 2.8
A1/36 Motor-protective circuit-breakers
PKZ2 motor-protective circuit-breakers,insulated enclosures
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Rating data for approved types1) Maximum motor rating Setting ranges
UL 508/CSA C 22.2 No. 14
AC Overload short-
Approvals for world markets

HP = PS Releases circuit
releases
200 V 230 V 460 V 575 V
208 V 240 V 480 V 600 V A A
HP HP HP HP
Basic unit "Basic unit"
in combination with ZM-...-PKZ2 ZMR -...-PKZ2
trip block for motor protection
PKZ2 10 15 30 30
trip block for motor protection „Motor Protection Trip Module with overload relay function“
with overload relay function

ZMR-0,6-PKZ2 2) 0.4 … 0.6 5…8


ZMR-1-PKZ2 ½ ½ 0.6 … 1 8 … 14
ZMR-1.6-PKZ2 ¾ 1 1 … 1.6 14 … 22
ZMR-2,4-PKZ2 ½ ½ 1 1½ 1.6 … 2.4 20 … 35
ZMR-4-PKZ2 1 1 2 3 2.4 … 4 35 … 55
ZMR-6-PKZ2 1½ 1½ 3 5 4…6 50 … 80
ZMR-10-PKZ2 2 3 5 7½ 6 … 10 80 … 140
ZMR-16-PKZ2 3 5 10 10 10 … 16 130 … 220
ZMR-25-PKZ2 7½ 7½ 20 25 16 … 27 200 … 350
ZMR-32-PKZ2 10 10 20 30 24 … 32 275 … 425
ZMR-40-PKZ2 10 15 30 30 32 … 42 350 … 500

ZMB Auxiliary switch Pilot Duty D 300, R 300


General Purpose 1,5 A 240 V AC
0,6 A 600 V AC
Terminal capacity AWG 18 … 14
Torque 1 Nm/9 LB.-IN
Trip block
for motor protection
ZM-0,6-PKZ2 2) 0.4 … 0.6 5…8
ZM-1-PKZ2 ½ ½ 0.6 … 1 8 … 14
ZM-1,6-PKZ2 ¾ 1 1 … 1.6 14 … 22
ZM-2,4-PKZ2 ½ ½ 1 1½ 1.6 … 2.4 20 … 35
ZM-4-PKZ2 1 1 2 3 2.4 … 4 35 … 55
ZM-6-PKZ2 1½ 1½ 3 5 4…6 50 … 80
ZM-10-PKZ2 2 3 5 7½ 6 … 10 80 … 140
ZM-16-PKZ2 3 5 10 10 10 … 16 130 … 220
ZM-25-PKZ2 7½ 7½ 20 25 16 … 27 200 … 350
ZM-32-PKZ2 10 10 20 30 24 … 32 275 … 425
ZM-40-PKZ2 10 15 30 30 32 … 42 350 … 500

Notes Service Factor (SF) Setting Ir of current scale in dependence on load factor 1) Devices for world markets IEC q
SF = 1.15 r Ir = 1 x In mot UL/CSA.
2) In this range, calculate motor
SF = 1 r Ir = 0.9 x In mot
rating according to rated current
Terminal capacity PKZ2/ZM-.../S high-capacity compact starter, Stated values to NEC
PKZ2/ZM-...motor-protective circuit-breaker Table 430 … 150.
Cables Cu 75 °C, min. AWG 14, max.
AWG 6
Torque 1.8 Nm

Part no. Price


Article no. see price Std. pack
list

Insulated enclosures for


PKZ2/ZM overload relays 1)
Degree of protection NEMA 12
Prepared for mounting a door CI19EE-PKZ2-NA 1 off Built-in mounting rail to IEC/EN 60715
coupling handle (R)H-PKZ2 003183 for connecting conduits
and continuous earthing
With mounting plate without CI19E-125/M-NA 1 off For connection of conduit and continuous earthing
apertures 033451

Notes 1) Not usable for PKZ2/ZM...S(-SP).


Motor-protective circuit-breakers A1/37
Accessories
http://catalog.moeller.net Moeller HPL0211-2007/2008 PKZ2

Rating data for approved types1) For use with Pilot Duty General Use
Ordering information PKZ2/S-SP motor-protective
circuit-breaker

Approvals for world markets


„Self-Protected Starter” a Page A1/35
AC DC

Accessories
Standard auxiliary contacts NHI11-PKZ2 PKZ2/ZM..., PKZ2...SP A 600. R 300 5 A – 600 V 0.5 A – 250 V
NHI22-PKZ2 PKZ2/ZM..., PKZ2...SP 10 A – 300 V
NHI11S-PKZ2 PKZ2/ZM-...
NHI22S-PKZ2 PKZ2/ZM-...
NHI2-11S-PKZ2 PKZ2/ZM-...
Trip-indicating auxiliary contacts AGM2-11-PKZ2 PKZ2/ZM..., PKZ2...SP A 600. R 300 10 A – 600 V 0.5 A – 250 V2)

Short-circuit indicators K-AGM-PKZ2 PKZ2/ZM..., PKZ2...SP

Voltage releases A-PKZ2-... PKZ2/ZM..., PKZ2...SP 24 – 600 V 24 – 250 V


U-PKZ2(...) PKZ2/ZM..., PKZ2...SP 24 – 600 V 24 – 125 V
U-HI20-PKZ2(...) PKZ2/ZM..., PKZ2...SP 24 – 600 V 24 – 125 V
B 600. R 300 10 A – 600 V 0.5 A – 250 V
UVHI-PKZ2(...) PKZ2/ZM..., PKZ2...SP 24 – 600 V 24 – 125 V
B 600. R 300 10 A – 600 V 0.5 A – 250 V
Auxiliary switches for contact HI11-S-PKZ2 PKZ2/ZM-... A 600. R 300 10 A – 600 V 0.5 A – 250 V2)
HI20-S-PKZ2 PKZ2/ZM-... A 600 10 A – 600 V
HI11-S/EZ-PKZ2 PKZ2/ZM-... A 600. R 300 5 A – 600 V 0.5 A – 250 V2)
10 A – 300 V
Remote operator RE-PKZ2 PKZ2/ZM..., PKZ2...SP 3)

RS-PKZ2 PKZ2/ZM..., PKZ2...SP D 300 – R 300 1.5 A – 240 V AC


0.6 A – 600 V AC
Amplifier module for ETS4-VS3 PKZ2/ZM..., PKZ2...SP B 300 – R 300 5 A – 250 V AC
Remote operator
Clip plates C-PKZ2 PKZ2/ZM-...

Door coupling handle H-PKZ2 PKZ2/ZM..., PKZ2...SP


RH-PKZ2 PKZ2/ZM..., PKZ2...SP
Extension shaft A-H-PKZ2 PKZ2/ZM..., PKZ2...SP

Bases for separate mounting EZ-PKZ2 –

Three-phase commoning link B3.1/3-PKZ2 PKZ2/ZM..., PKZ2...SP max. 100 A


B3.1/2-PKZ2 PKZ2/ZM..., PKZ2...SP max. 85 A
Terminals for BK50/3-PKZ2 PKZ2/ZM..., PKZ2...SP max. 100 A
three-phase commoning link Terminal capacity AWG 14-0
Torque 4.5 Nm
SVB-PKZ2 PKZ2/ZM..., PKZ2...SP
Padlocking feature
Mechanical interlock MV-PKZ2 –

Coding pins CS-PKZ2 PKZ2/ZM..., PKZ2...SP

Busbar adapter AD-... PKZ2/ZM..., PKZ2...SP

Notes Terminal capacities for all PKZ2 system add-on modules:


• Cables min. AWG 18, max. AWG 14
• Torque 1.0 Nm
1) Device for world markets IEC  UL/CSA.
2) >150 V same polarity.
3) Maximum actuating voltage
120 V 60 Hz or. 120 V DC.
A1/38 FAZ miniature circuit-breakers
Supplementary Protector
FAZ Moeller HPL0211-2007/2008 http://catalog.moeller.net

UL 1077/CSA 22.2 No. 235


Approvals for world markets

Supplementary Protector FAZ Miniature circuit-breakers are approved as "Supplementary Protectors“ with
the appropriate upstream protection device according to UL 1077.
FAZ; B-charakteristic; 6 … 63 A
FAZ; C-charakteristic; 0,5 … 63 A
FAZ; D-charakteristic; 1 … 40 A
FAZ; R-charakteristic; 6 … 40 A
FAZ; S-charakteristic; 1 … 16 A
Switching capacity
5 kA – 277 V 60 Hz; without upstream protection device
multi-pole 5 kA – 480/277 V 60 Hz; in conjunction with an upstream protection device
(Fuse 100 A or max. 4 × In)
10 kA 48 V DC
2 pole 10 kA 125 V DC
Tripping current 155 % In at 30 °C
Accessories
Auxiliary contacts
FAZ-XHI/FAZ-XRHI
General Use
230 V AC/240 V AC 2 A/2 A
110 V DC/120 V DC 0,5 A/0,5 A
Pilot Duty A 600
Q 300
Voltage release
Shunt release FAZ-XAA
Rated operational voltage
FAZ-XAA(110-415 V AC) V AC 110 … 415
V DC 110 … 230
FAZ-XAA(12-110 V AC) V AC 12 … 110
V DC 24 … 60
FAZ-XUA Undervoltage releases
Rated operational voltage
FAZ-XUA(115 V AC) V AC 115
FAZ-XUA(230 V AC) V AC 230
FAZ-XUA(400 V AC) V AC 400
Terminal capacity
Supplementary Protector
FAZ-B
FAZ-C
FAZ-D
FAZ-XAA
FAZ-R
FAZ-S
Cables Cu 75 °C, min. AWG 18, max. AWG 4
Torque Nm 2,4
Accessories
Cables Cu 75 °C, min. AWG 18, max. AWG 14
Torque
FAZ-XHI Nm 0,8
FAZ-XRHI
FAZ-XUA Nm 0,8
CI insulated enclosures A1/39
Basic enclosures
http://catalog.moeller.net Moeller HPL0211-2007/2008 CI-K

Dimensions Mounting Features Part no. Price Std. pack


depth Article no. see price list

Approvals for world markets


Width Height Depth

mm mm mm mm

CI-K basic enclosures


• Degree of protection IP65
• Enclosure base RAL 9005, black/enclosure top RAL 7035, light grey
• Approved for UL, CSA
• CI-K2X...: 4 x m inch knockouts
• CI-K3X..., CI-K4X..., CI-K5X...: smooth overall with sharp corners
100 160 100 73 With mounting rail CI-K2X-100-TS-NA 1 off
231220
79 With mounting plate CI-K2X-100-M-NA
231228
145 118 With mounting rail CI-K2X-145-TS-NA
231221
124 With mounting plate CI-K2X-145-M-NA
231229
120 200 125 93 With mounting rail CI-K3X-125-TS-NA
231222
98 With mounting plate CI-K3X-125-M-NA
231230
160 128 With mounting rail CI-K3X-160-TS-NA
231223
133 With mounting plate CI-K3X-160-M-NA
231231
160 240 125 93 With mounting rail CI-K4X-125-TS-NA
231224
98 With mounting plate CI-K4X-125-M-NA
231232
160 128 With mounting rail CI-K4X-160-TS-NA
231225
133 With mounting plate CI-K4X-160-M-NA
231233
200 280 125 93 With mounting rail CI-K5X-125-TS-NA
231226
160 128 With mounting rail CI-K5X-160-TS-NA
231227
280 125 98 With mounting plate CI-K5X-125-M-NA
231234
160 133 With mounting plate CI-K5X-160-M-NA
231236

Notes Degrees of protection of enclosures to NEC (NFPA 70), NEMA, UL, CSA: UL-File No. E54120
Type 1, 3R, 4X, 12, 13 a degrees of protection
A1/40 CI insulated enclosures
Panel enclosures
CI Moeller HPL0211-2007/2008 http://catalog.moeller.net

Dimensions Mounting depth Part no. Price


Article no. see price list Std. pack
Approvals for world markets

Width Height Depth


mm mm
Panel enclosures
• Degree of protection IP65
• Enclosure base RAL 7032, removable smooth flanges on all 4 sides
• Fixing straps for wall fixing
• Approved for UL, CSA
Panel enclosures with cover and flanges
• Transparent cover, cover fasteners can be sealed.
234 296 150 125 CI23-125-NA1) 1 off
002234
175 150 CI23-150-NA1)
002237
421 296 150 125 CI43-125-NA1)
002238
175 150 CI43-150-NA1)
002241
225 200 CI43-200-NA1)
002242
421 150 125 CI44-125-NA1)
002245
175 150 CI44-150-NA1)
002246
225 200 CI44-200-NA1)
002249
275 225 CI44-250-NA1)
002250
546 225 200 CI45-200-NA1)
264024
796 225 200 CI48-200-NA2)
002253
275 250 CI48-250-NA2)
002254
Panel enclosures with door and flanges
• Transparent cover, cover locks can be sealed
• Transparent door with handle catches and 180° door opening
• Door hinges can be subsequently altered to left, right, up or down
234 296 166 125 CI23-125/T-NA2) 1 off
002235
191 150 CI23-150/T-NA2)
002236
421 296 166 125 CI43-125/T-NA2)
002239
191 150 CI43-150/T-NA2)
002240
241 200 CI43-200/T-NA2)
002243
421 166 125 CI44-125/T-NA2)
002244
191 150 CI44-150/T-NA2)
002247
241 200 CI44-200/T-NA2)
002248
291 250 CI44-250/T-NA2)
002251
796 241 200 CI48-200/T-NA2)
002252
291 250 CI48-250/T-NA2)
002255
241 200 CI48-200/2T-NA2)
002256
291 250 CI48-250/2T-NA2)
002257

Notes • Degrees of protection • UL-Approbation


1) IEC/EN 60 529: IP65; NEMA, UL 508: Type 12, Type 13 File No. E 54120, Vol. 2, Sec. 4; Guide No. NITW
4 X indoor; CSA-C 22.2 No.94: Enclosure 4, Enclosure 5 • CSA-Approbation
2) IEC/EN 60 529: IP65; NEMA, UL 508: Type 12, Type 13 Report-No. LR 27130-5; Class-No. 321107
CSA-C 22.2 No. 94: Enclosure 5
CI insulated enclosures A1/41
Individual enclosures
http://catalog.moeller.net Moeller HPL0211-2007/2008

Dimensions Mounting depth Part no. Price


Article no. see price list Std. pack

Approvals for world markets


Width Height Depth
mm mm
Individual enclosures
• Degree of protection IP65
• Enclosure base RAL 7032 with smooth sides
• Fixing straps for wall fixing
• Approved for UL, CSA
Individual enclosures with covers
• Transparent cover, cover fasteners can be sealed.
187.5 250 150 125 CI23X-125-NA 1 off
002209
175 150 CI23X-150-NA
002212
375 250 150 125 CI43X-125-NA
002213
175 150 CI43X-150-NA
002232
225 200 CI43X-200-NA
002217
375 150 125 CI44X-125-NA
002218
175 150 CI44X-150-NA
002219
225 200 CI44X-200-NA
002220
275 250 CI44X-250-NA
002224
500 225 200 CI45X-200-NA
264023
Individual enclosures with cover and doors
• Transparent cover, cover fasteners can be sealed.
• Transparent door with quick-release fasteners and 180° door opening angle
• Door hinges can be subsequently changed to left, right, top or bottom.
187.5 250 166 125 CI23X-125/T-NA 1 off
002210
191 150 CI23X-150/T-NA
002211
375 250 166 125 CI43X-125/T-NA
002214
191 150 CI43X-150/T-NA
002215
241 200 CI43X-200/T-NA
002216
375 166 125 CI44X-125/T-NA
002233
191 150 CI44X-150/T-NA
002222
241 200 CI44X-200/T-NA
002221
291 200 CI44X-250/T-NA
002223

Notes • Degrees of protection • UL-Approbation


IEC/EN 60529: IP65 File No. E 54120, Vol. 2, Sec. 4
NEMA, UL 508: Type 12, Type 13 Guide No. NITW
4 X indoor • CSA-Approbation
CSA-C 22.2 No. 94: Enclosure 4, Enclosure 5 Report-No. LR 27130-5
Class-No. 321107
A1/42 CI insulated enclosures
Accessories for CI…-NA
Moeller HPL0211-2007/2008 http://catalog.moeller.net

For use with Part no. Price


Mounting depth Article no. see price list Std. pack
Approvals for world markets

mm

Covers, transparent
• Sealable cover fasteners
• Gaskets

U-CI23... 125 D125-CI23-NA 10 off


014286
150 D150-CI23-NA 4 off
014334
125 D125-CI43-NA 5 off
U-CI43... 014433
150 D150-CI43-NA 2 off
014480
200 D200-CI43-NA 2 off
014771
U-CI44... 125 D125-CI44-NA 5 off
014838
150 D150-CI44-NA 2 off
010937
200 D200-CI44-NA 2 off
010985
250 D250-CI44-NA 1 off
011049
U-CI45... 200 D200-CI45-NA
264022
U-CI48... 200 D200-CI48-NA
011878
250 D250-CI48-NA
011906

For use with Part no. Price


Article no. see price list Std. pack

Doors
• Degree of protection IP65
• Door opening angle to 180°
• Door hinges can be subsequently changed to right, left,
top or bottom.
• Adhesive film for marking the cutout
• Fixing screws
• Transparent

Surface mounting on all enclosure covers T-CI23-NA 1 off


D...-CI23-NA 011925
Surface mounting on all enclosure covers T-CI43-NA
D...-CI43-NA 011957
Surface mounting on all enclosure covers T-CI44-NA
D...-CI44-NA and D...-CI48-NA 012001
CI insulated enclosures A1/43
Accessories for CI…-NA
http://catalog.moeller.net Moeller HPL0211-2007/2008

For use with Part no. Price


Mounting depth Article no. see price list Std. pack

Approvals for world markets


mm

Covers with door


• Degree of protection IP65

U-CI23... 125 D125-CI23/T-NA 1 off


012038
150 D150-CI23/T-NA
012097
U-CI43... 125 D125-CI43/T-NA
012115
150 D150-CI43/T-NA
012147
200 D200-CI43/T-NA
012195
U-CI44... 125 D125-CI44/T-NA
012335
150 D150-CI44/T-NA
012357
200 D200-CI44/T-NA
012780
250 D250-CI44/T-NA
012809
U-CI48... 200 D200-CI48/T-NA
012842
205 D250-CI48/T-NA
012863
200 D200-CI48/2T-NA
012392
205 D250-CI48/2T-NA
012411

For use with Part no. Price


Article no. see price list Std. pack

Flanges
For enclosure dimension 187.5 mm FL2-X-NA 10 off
208310
For enclosure dimension 250 mm FL3-X-NA
012462
For enclosure dimension 375 mm FL4-X-NA
208309
Spacers
For enlarging the cable entry space in combination with ZRF3-NA 20 off
FL3-X-NA 012479
A1/44 CI insulated enclosures
Cable glands for conduits
Moeller HPL0211-2007/2008 http://catalog.moeller.net

Suitable for commercial conduits Part no. Price


Article no. see price list Std. pack
Approvals for world markets

PG cable glands
• Conduit union and lock nut with earthing screw
• Sutiable for all CI...-NA enclosures
• Approved for UL, CSA

½″ STB1/2ZOLL 1 off
045878
¾″ STB3/4ZOLL
060116
1″ STB1ZOLL
052997
1¼″ STB1-1/4ZOLL
043505
1½″ STB1-1/2ZOLL
041132
2″ STB2ZOLL
002203

Notes • UL-Approbation • CSA-Approbation


File No. E 23018 Report No. LR 636
File No. E 3060 Report No. LR 2884

This glossary contains brief explanations of the terms used in this section. For further
definitions, see the main glossary in section 20.
Abbreviations

AWG American Wire Gauge An American unit of measurement, the AWG or MCM value indicates
wire thickness. For a conversion to mm and inches, see http://
www.coilcraft.com/awg.html
HP Horsepower 1 HP = 0.75 kW; 1 PS = 0.986 HP

Organizations

CSA Canadian Standards Association Further information at: http://www.csa.ca


NEC National Electrical Code Further information at: http://www.nfpa.org
NEMA National Electrical Manufacturers Association Further information at: http://www.nema.org
NFPA National Fire Protection Association Further information at: http://www.nfpa.org
OSHA Occupational Safety and Health Administration Further information at: http://www.osha.gov
UL Underwriters Laboratories Further information at: http://ultesting.com

Note A600, Q300, B300


Indicate magnitude and type of switching capacity in control circuits.