Professional Documents
Culture Documents
HomeMotorcontrolSoftstarterwiring
Category
Products
Softstarterwiring
Tags:Installation
Contactus
Thesoftstarterhasfollowingwiringconnections:
Maincircuitconnection:Itcontainsthewiringof3phasepowersourceinput,theoutputtomotor,andthe
bypasscontactorconnection.
Externalterminalconnection:thatisthewirecomesfrom12externalterminalswhichincludingcontrol
signalandanalogueoutputsignal.
Chinasoftstarters
manufacturer
Softstarter@gozuk.com
Softstarterexternalterminalsconnection
Terminalarebypassoutput,areusedtocontrolthebypasscontactor.Theyarenormalopen
contactsandareclosedwhenfinishingstarting.TheterminalcontactcapacityisAC250V/5A.
Terminalareprogrammablerelayoutput:ThedelaytimeissetbyP4code.Theoutput
commandtypeissetbyPJcode.Theyarenormalopennopowerterminals,beingclosewhen
outputvalid.ThisterminalcontactcapacityisAC250V/5A.
Terminalarefaultoutput,theywillbeclosedwhenthereareanyfaultmattershappenedtothe
softstarterorelectricitylost,whileatnormalcasetheyareopen.ThisterminalcontactCapacityis
AC250V/0.3A.
Terminalareinstantaneousstopinput,thisterminalmustbeconnectedwithterminalwhenthe
starterworksnormally.Butifthesetwoterminalsareopen,thesoftstarterwillstop,andatthistime
themotorstarterisatthestateoffaultprotection.Thisterminalcanbecontrolledbythenormally
closedoutputterminalsofexternalprotectiondevice,anditisuselesswhenthePCcodeissetto
0(basicprotection).
Terminalarestartuporstopinput.Therearetwowaysofconnectionsforyourselection
thoseare3wireconnectionand2wireconnection,see:
http://www.softstarter.org/softstarterwiring437407.html 1/4
11/2/2016 Softstarterwiring
TerminalareDC4~20mAanalogueoutput,theyindicatethecurrentvalueofthemotoratreal
timeworking.The20mAisfullscalevalueandthatisfourtimesthanratedcurrentofnominalpower
ofsoftstarter,andwecanconnecta4~20mADCcurrentmetertocheck.Themaxvalueofoutput
loadresistanceis300.
Note:Pleasemakesurethatexternalterminalsareinrightconnection,otherwise,thesoftstartermaybe
damaged.
Softstartermaincircuitwiring
Thesoftstarterisinstalledbetweenthemainsandcabletothemotor.Ifamainsorisolationcontactoris
useditisbestcontrolledbythesoftstarter"Linerelay".
3Wire/6wire:Thestandardconnectionofanelectronicsoft
starteris3wire.Analternativeconnectionis6wireorinsidedelta
connection.Thisiscommonlyusedwhenreplacingastar/delta
typemotorstarter.
Bypass/Continuous:Thesoftstartercanoperatewithor
withoutabypasscontactor.Somemodelsincludeanintegral
bypasscontactor.Thebypasscontactorreducestheheat
dissipationofthesoftstarterasthesemiconductorsarebypassed
aftertheramptime.
MotorProtection
Thesoftstarterprovidesadvancedmotorprotectionwithuser
selectableoverloadclasses,over&undercurrentprotection,
phaseimbalanceandthermistorprotection.Itisimportantthatthe
powerwiringisfollowedcorrectlytoensureproperprotectionand
starterperformance.
Semiconductorfusesarerecommendedforallelectronicsoft
starterstoprovideprotectionofthethyristorsintheeventofan
outputshortcircuit.Semiconductorfusesarestrongly
recommendedforapplicationssuchassubmersiblepumps.
Semiconductorfusesareoptionalwithallsoftstarters.
Averygoodarticle.Itprovidedaclearunderstandingofhowasoftstartfunctions.ThankYou.
http://www.softstarter.org/softstarterwiring437407.html 2/4
11/2/2016 Softstarterwiring
>by:JimReid
indtolearnmoreaboutsoftstartersitsanewthingtome
>by:blessuskataya
AverygoodThankYou.
>by:mohammedrami
PostaComment:
Name* Website(option)
PlzCalculate(41)= (Yourcommentwillshowafterapproved.)
Youmayalsolike:
Doessoftstartersuitableforcrane?
SoftstartershavenoHzregulationcapabilities.Theycanboostcurrentandvoltageatstart,butit'savoltageboostto
initiatemovementifthemotorbogsatstart,afterwhichtheboostvoltage...
howasoftstarterworks?
TheFCMASoftstarterachievesthisthroughauniquesystemoffluxcompensatednonsaturatedmagneticamplifierfor
controllingthemotorcurrentandhencethemotortorqueduringacceleration.The...
Softstarterandfrequencyinverter
Thedifferencebetweenlinestartingamotorandrampstartingthemotorwithafrequencyinverteristhatthemotor/load
doesnotpullthe67timesratedcurrentofthemotor,becausethemotor...
Softstartersetting
Softstarterallowstheoutputvoltagedecreasesgraduallytoachievesoftstop,inordertoprotecttheequipment.Suchas
theimpactofthewaterpump,whenthepumpstopssuddenly,thewaterflow...
Whybunkeringpumpmotortripinthemorning?
Sidenote:Softstarterswilltripoutifthemotorspeedhasnotreachedatleast85%ofnominalbytheendofthestartramp
cycle.So,thatiswhyyoursoftstarterisprobablytripping.Thesoft...
Copyright2016SoftStarter GetaPrice|Sitemap
http://www.softstarter.org/softstarterwiring437407.html 3/4
11/2/2016 Softstarterwiring
http://www.softstarter.org/softstarterwiring437407.html 4/4