You are on page 1of 2

TEST

YOUR TANKS
CATHODIC
PROTECTION
SYSTEM
Steel Facts WWW.STEELTANK.COM

N U M B E R 1
ITS EASY

Cathodic protection is
a common technique
used to provide life

Cathodic Protected Tank Inspection


extending protection
from corrosion for steel
tanks and pipelines.

Two (2) basic methods:


sacrificial anode and

Its easy!
impressed current.

The most common,


sacrificial anode system
has an anode that There are two basic methods
operates exactly like used to provide cathodic pro-
one in a home hot tection to steel tanks. By far
water heater. the most common and sim-
plest method of protection is
Cathodic protection a sacrificial anode system. Most
systems need a simple states require a simple in-
inspection at least spection of this system every
every three (3) years. three years by a qualified in- operate the unit. Be sure underground tank. Amps
spector. will fluctuate depending on
that it is ON.
Its easy to provide An impressed current cathodic Generally, there are two weather, climate, and
monthly inspections of protection system is the second meters inside the rectifier, changes in the level of pro-
impressed current type. Typically, it requires a a voltmeter and an ammeter. tection, but cannot be ad-
cathodic protection detailed inspection every Both volt and amp readings justed. If the amp value on
systems (see back). three years and a bi-monthly should be collected and re- the meter changes more
inspection of the power sup- than 10% from the previ-
Remote monitoring of ply (called a rectifier). In order corded monthly:
ous month, contact your
cathodic protection to insure the system is oper- The volt meter indicates corrosion control repre-
systems by trained ating within its design pa- there is AC power being sentative and follow their
corrosion engineers is rameters, you should per- supplied to the rectifier. instructions.
readily available. form certain tests: The value displayed on
The rectifier requires an the volt meter indicates A properly installed cathodic
uninterrupted supply of the amount of power protection system can prevent
electricity, so always check being supplied to the an- corrosion on steel tanks and
to see that the circuit odes. The volts can be pipelines. By performing routine
adjusted by trained per- testing and complying with fed-
ON THE breaker that supplies elec-
OTHER SIDE...
sonnel, if necessary. eral, state, and local regulations
tricity to the rectifier isON. you can sustain the life of steel
The amp meter indicates
Inside the rectifier, there is the amount of current tanks and pipelines, indefinitely.
Impressed another circuit breaker
current: rectifier (amps) that is flowing
that allows electricity to from the anodes to the
monthly check list.

Volts and of volts and amps is easy, and


applies no matter where electri-
son is to the pressure (psi) that
exists in a pressured water pipeline.
cal power is used.
Amps A volt is a unit of electricity that
is a measure of the electro-
Amps are the units that measure the
current being pushed through the
system, similar to the gallons per
Understanding the difference motive force that exists in the minute you receive as a result of
between the electrical measures wire circuit. A simple compari- water pressure.
WWW . RECY CL E - ST EEL . ORG
Continued other side

STI-SPFA 944 Donata Court Lake Zurich IL 60047


847-438-8265 info@steeltank.com www.steeltank.com

2012 STI/SPFA
Volts and Amps cont.
Therefore, the greater the number of volts, the more amps
are delivered. This is true of both alternating current (AC),
which is used in your home, office, and to power street
lights; and direct current (DC), which is used in batteries,
battery chargersand cathodic protection systems.
A properly installed cathodic protection system can pre-
vent corrosion on steel tanks and pipelines, By performing
routine testing and complying with federal, state, and local
regulations, you can sustain the life of steel tanks indefi-
nitely.

Image courtesy of Corrpro Companies, Inc.

RECTIFIER MONTHLY INSPECTION CHECK LIST

DATE__________ INSPECTED BY_______________________________


Please read the document associated with this check list.

Checked Item
Check AC circuit breaker to insure the power to the rectifier is ON.

Check the circuit breaker within the rectifier to ensure it is ON.

Record the monthly VOLT reading. This is the power being supplied to the anodes. Compare this reading
with last months reading.

Record monthly AMP reading. This indicates the amount of electricity (DC) that is flowing from your an-
odes.
Compare this value with last months reading.
If it is LESS than 10% of last months reading, contact your corrosion control professional.
Only a qualified professional should make adjustments to the unit.

NOTE: IF THERE HAS BEEN RECENT CONSTRUCTION AT THE SITE,


BE SURE TO INFORM YOUR CORROSION CONTROL PROFESSIONAL.

RECTIFIER NUMBER IF AVAILABLE:

RECTIFIER OUTPUT RATING IF AVAILABLE:


VOLTS AMPS

TESTERS NAME: