Instruction Manual
Copyright 2012 ABB. All rights reserved.
All rights with respect to this document, including applications for patent and registration
of other industrial property rights, are reserved. Unauthorized use, in particular
reproduction or making available to third parties without our explicit consent in writing, is
prohibited.
The use is only allowed for the purpose laid down in the contract.
This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, she/he is requested to inform us at her/his earliest convenience.
The data contained herein purport solely to describe the product and are not a warranty
of performance or characteristic. It is with the best interest of our customers in mind that
we constantly strive to improve our products and keep them abreast of advances in
technology. This may, however, lead to discrepancies between between the product and
the product description or the instruction manual.
1. Introduction
2. Safety Instructions
7. Commissioning
9. Troubleshooting
11. Options
Annex
ETL600 1KHW001489-EN ABB Switzerland Ltd
Contents
1. INTRODUCTION................................................................................1-1
7. COMMISSIONING .............................................................................7-1
9. TROUBLESHOOTING.......................................................................9-1
9.2. Fuses.................................................................................................9-5
10.2. Storage............................................................................................10-2
List of Figures
Fig. 3-28 The two possible topologies of the RF front end .........3-39
Fig. 3-29 Block diagram of the Rx filter P4RX ............................3-40
Fig. 3-30 Block diagram of P7LA equipped with B5LA, E5TX,
P1LA, P3LE.................................................................3-42
Fig. 3-31 Front plate O4CV ........................................................3-44
Fig. 3-32 Point to point hot line...................................................3-46
Fig. 3-33 2-wire remote subscriber.............................................3-46
Fig. 3-34 4-wire remote subscriber.............................................3-47
Fig. 3-35 4-wire PAX connection with E&M................................3-47
Fig. 3-36 2/4-wire PAX connection with E&M and hybrid control3-48
Fig. 3-37 Service phone .............................................................3-48
Fig. 3-38 State of LEDs corresponding to internal E&M.............3-49
Fig. 3-39 State of LEDs showing to internal E&M when one
PAX is not working correctly........................................3-49
Fig. 3-40 Transit filter cutoff frequencies selectable in steps of
60 Hz ...........................................................................3-51
Fig. 3-41 Transit connection .......................................................3-52
Fig. 3-42 MUX600 block diagram ...............................................3-59
Fig. 3-43 DPLC channel multiplexer framing..............................3-60
Fig. 3-44 Point to point hot line...................................................3-65
Fig. 3-45 2-wire remote subscriber.............................................3-66
Fig. 3-46 4-wire remote subscriber.............................................3-66
Fig. 3-47 4-wire PAX connection with E&M................................3-67
Fig. 3-48 Service phone .............................................................3-67
Fig. 3-49 Redundant protection of a dual-circuit line ..................3-79
Fig. 3-50 Duplicated protection for a single-circuit line...............3-81
Fig. 3-51 Examples for allocation of the 4 kHz band with
speech and the ETL600 pilot as NSD600 guard
signal ...........................................................................3-91
Fig. 3-52 Examples for allocation of the 4 kHz band with
speech and an own NSD600 guard signal ..................3-91
Fig. 3-53 Dual-tone principle ......................................................3-92
Fig. 3-54 Input/output command handling parameters...............3-96
Fig. 4-1 Communication via cable ..............................................4-3
Fig. 4-2 Communication via phone modems ..............................4-5
Fig. 4-3 Communication via intranet/internet using R1LA ..........4-8
Fig. 4-4 RS-485 station bus with R7AP ....................................4-10
Fig. 9-1 The six major fault location areas of a PLC link ............9-5
Fig. 9-2 Alarm processing block diagram ................................9-7
Fig. 9-3 Grouping of alarms........................................................9-8
Fig. 9-4 Derivation of high-level alarms ....................................9-10
List of Tables
Abbreviations
O4LE AF interface
OFDM Orthogonal Frequency Division Multiplex
P1LA Power Amplifier 40 W
P3LE ETL600 RF Hybrid
P3LK Dummy Load 80 W
P3LG ETL600 Carrier Combiner
P3LL Transmit filter tuning adapter
P4LM Receive filter tuning adapter
P4LT DSP module without LAN ports
P4LU DSP module with optional LAN port and additional
serial ports
P4LV DSP module with LAN ports and digital transit ports
P4LX DSP module with LAN ports, digital transit ports and
additional serial ports
P4RX ETL600 Rx filter
P7LA ETL Power rack
P7LC ETL Channel rack
PAR Peak to Average Ratio
PAX Private Automatic telephony eXchange
PC Personal Computer
PCB Printed Circuit Board
PDH Plesiochronous Digital Hierarchy
PE Protective Earth
PE Peak Envelope
PEP Peak Envelope Power
PEV Peak Envelope Voltage
PLC Power Line Carrier
PLL Phased Locked Loop
PSK Phase Shift Keying
R1BC Alarm Relay Module
R1LA LAN Interface (piggyback for P4LU)
R7AP Remote Inquiry Kit
R9AL Earth Rail
RAM Random Access Memory
RD Receive Data
RFC Request For Comments
RMS Root Mean Square
RS-485 Data interface standard
RT Receive Timing
RTP Real-Time Transport Protocol
1. INTRODUCTION
The new ETL600 Power Line Carrier (PLC) equipment combines the
advantages of legacy analog power line carrier systems (APLC
systems) and digital power line carrier systems (DPLC systems) to
achieve high dependability and easy adaptability to all requirements in
the field of communication with power line carrier.
ETL640 and ETL680 are the members of the ETL600 family. They are
assembled in standard 19 racks, one with 6 ASA-units carrying the
signal processing modules and one or two with 3 ASA-units housing
the 40 W power amplifier and associated modules.
Normally ETL600 is mounted in ABBs standard cabinet E40A with a
hinged 19 frame. External connections are wired to the front and to
the back of the cabinet, providing easy access during installation,
commissioning and maintenance. Even if ETL600 is normally mounted
in the standard cabinet type E40A, it can be mounted in any 19 rack
or cabinet providing the required protection and air circulation.
ETL600 provides the necessary RF-filters, hybrids and coaxial
connectors for connection to the line matching and coupling devices.
With a wide range of interfaces it allows configurations and assemblies
which meet the clients individual requirements best. These
configurations are documented and explained in this manual.
1.1. Using the manual
The manual is written for service and operation personnel in the high
voltage (HV) power line environment. All existing safety instructions in
the client's environment have to be observed and only trained and
instructed personnel should work with the equipment. The manual
provides the necessary instructions for all the steps in the life-cycle of
the equipment, e.g. from transport, storage, commissioning to
maintenance, decommissioning and disposal. Please refer to the
appropriate section for the particular step or function.
The different steps of transport, installation, testing and commissioning
are normally made by various people. Safety instructions are therefore
included in all the corresponding chapters and may so appear as
double information.
In this manual, two types of persons dealing with the equipment are
distinguished: Service personnel and operator.
The software version referred to in this instruction manual is 'HMI600
Version 3.xy'. Please refer to the document 'Compatibility
requirements' in the annex for compatibility between Hardware,
Firmware and Software of ETL600.
1.2. Application of the ETL600
The ETL600 Power Line Carrier system is used for communication on
power lines between power system control centers, power stations and
2. SAFETY INSTRUCTIONS
2.1. Safety information
The ETL600 equipment itself is safe and without any risk. This is not
valid for its containment and the peripheral surrounding, like the high
voltage area and lines. Only service personnel is therefore allowed to
execute all the steps and manipulations described in this manual.
Some of the operations may also be carried out by operators, refer to
section 1.
2.1.1. In this instruction manual
In this manual the safety instructions are marked as follows:
Instruction manual
The instruction manual should be read and clearly
DANGER understood before working on the equipment.
Alteration
Alteration of the equipment is not allowed.
DANGER
Warning labels
Precautions and indications to hazardous voltages
DANGER and hazardous energy level must be strictly
observed.
PCB Extenders
For measuring purposes only the original PCB
DANGER extenders P4LM, P3LL and I9BK, designed to work
with ETL600 equipment, must be used.
ESD protection
Transportation
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
Electrical Installation
This is a Class equipment as specified in
DANGER IEC 60950-1. The equipment and the cabinet must
be earthed.
The equipment must be supplied over the circuit
breaker for the power supply, type B9AS.
Back cover
Hazardous voltages and/or hazardous energy level
DANGER behind the back cover. Before removing the back
cover, the isolating terminals of the external cables
must be opened or the cables to the terminals must
be disconnected.
Unused slots
Unused slots in the equipment subracks must be
DANGER covered with blanking plates.
EMC
External cables
The shields of the external cables V9OD, V9OI,
DANGER V9OS and V9OF must be earthed at both cable
ends using the shield clamps supplied with the
cables.
B5LC
Make sure that the power supply B5LC is
DANGER programmed to the correct voltage of 230 VAC or
115 VAC as described in 1KHL015788 before
connecting the equipment to the power source.
P1LA
Hazardous voltages and/or hazardous energy level
DANGER at the heat sink.
Do not touch during operation.
P4LT/P4LU/P4LV/P4LX
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
R1BC
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
O4LE, O4CV
The phone interfaces on the modules O4LE and
DANGER O4CV generate dangerous voltages up to 100 V.
Dont use the modules without upper and lower
cover plates. Do not touch the open pins of the
service phone connector, the leads of its cable, the
pins of the external cable connector and the leads of
the external cable.
G4AI
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
Commissioning
telephony,
teleoperation,
data,
teleprotection
simultaneously by combining all information into one single signal,
which occupies a predefined bandwidth in the Radio Frequency
(subsequently = RF) frequency range from typically 40 to 500 kHz,
suitable for transmission via a power line. The amount of information
which can be transmitted is limited by the bandwidth of the RF signal,
which is typically 4 kHz or a multiple thereof. This is called the nominal
bandwidth Bn of the PLC equipment. For the backwards channel, a
distinct frequency band also of size Bn is used. This band is usually
adjacent to the one of the forward channel, refer to Fig. 3-2 a. X
For increased capacity and for redundancy, several PLC links can be
operated in distinct frequency bands over the same power line, sharing
the coupling devices.
The standard high frequency power output of the basic ETL600 unit is
40 W. This is for most cases adequate to ensure the required
transmission quality. For severe operating conditions with high
attenuation or high noise levels - e.g. on Extra High Voltage lines - the
output can be raised to 80 W by connecting a second power
equipment in parallel with the first. Redundancy is obtained by
coupling the two output amplifiers via an RF combiner and supplying
each from an independent power source. Two types of equipment are
thus distinguished:
ETL640: 40 W terminal,
ETL680: 80 W terminal.
For lines with low attenuation and low noise levels, the output power of
both types may be decreased to 20 W, 10 W or lower.
Power line carriers are used in almost all the countries of the world to
transfer information via HV transmission lines and have become an
important instrument for the management and safety of electrical
power systems. Of the possible PLC techniques, single sideband
modulation with a 4 kHz spacing makes the best use of the available
frequency bands and transmitting powers. This PLC technique has
become widely used in Europe, mainly for reasons of cost and its
capability of providing channels capable to carry speech, data and
teleprotection signals simultaneously. International recommendations
for the characteristics of line traps, coupling capacitors, PLC coupling
devices and single sideband PLC equipment (IEC Publications 60353,
60358, 60481 and 60495) and also for the design of PLC links (IEC
Publication 60663) have come into force. All the relevant CCIR and
ITU-T recommendations in IEC Publication 60495 were taken into
account. This ensures reliable coupling of channels at the Audio
Frequency (subsequently = AF) interfaces in power system control
centers, power stations and transformer stations between power utility
PLC, normal radio, point-to-point radio and leased back-up links.
3.1.1. APLC and DPLC services
Around the year 1990, digital PLC (DPLC) equipment using highly
bandwidth efficient modulation techniques appeared on the market.
Compared to traditional analog PLC (APLC), DPLC offers a number of
advantages:
Enhanced transmission capacity for a given bandwidth
data channels running at a higher rate,
more speech channels.
Easy integration of the PLC network into a larger digital network
64 kbps channel as a tributary channel of a digital telecom
network,
Digital data interfaces for lower speed data avoiding intermediate
modems.
a Ch 1 Ch 2 Ch 3
Fn Frequency
Bn
DPLC
b
Fn Frequency
Bn
APLC DPLC
c Ch 1 Ch 2 Ch 3
Fn Frequency
Bn
Fig. 3-3 Use of nominal frequency band for pure APLC (a), pure
DPLC (b) or mixed APLC/DPLC (c) operation in ETL600
erect mode
Fig. 3-4 Use of nominal frequency band for pure APLC (a), pure
DPLC (b) or mixed APLC/DPLC (c) operation in ETL600
inverted mode
Spectrum
Setting No.
Bn [kHz]
APLC APLC
(NSD600#1) (NSD600#1)
1 1 0 4 Ch1 Ch1
fn fn+Bn fn-Bn fn
DPLC DPLC
(NSD600#1) (NSD600#1)
4 4
2 0 to to
32 32
fn fn+Bn fn-Bn fn
APLC DPLC DPLC APLC
(NSD600#1) (NSD600#2) (NSD600#2) (NSD600#1)
4 8
3 1 to to
Ch1 Ch1
28 32
fn fn+Bn fn-Bn fn
APLC APLC
(NSD600#1)(NSD600#2) (NSD600#2) (NSD600#1)
fn fn+Bn fn-Bn fn
APLC DPLC DPLC APLC
(NSD600#1)(NSD600#2) (NSD600#2) (NSD600#1)
4 12
5 2 to to Ch1 Ch2 Ch2 Ch1
24 32
fn fn+Bn fn-Bn fn
APLC APLC
(NSD600#1) Remark: Gross (NSD600#1) Remark: Gross
bandwidths are bandwidths are
6 3 0 8 3.2 kHz for Ch1,
2.4 kHz for Ch2,
3.2 kHz for Ch1,
2.4 kHz for Ch2,
Ch1 Ch2 Ch3 Ch3 Ch2 Ch1
2.4 kHz for Ch3. 2.4 kHz for Ch3.
fn fn+Bn fn-Bn fn
APLC APLC
(NSD600#1)(NSD600#2) (NSD600#2) (NSD600#1)
7 3 0 12
Ch1 Ch2 Ch3 Ch3 Ch2 Ch1
fn fn+Bn fn-Bn fn
9 1 0 2 Ch1 Ch1
fn fn+Bn fn-Bn fn
APLC DPLC DPLC APLC
(Speech, Speech,
2 4 NSD600#1) NSD600#1
10 1 or or
6 8
Ch1 Ch1
fn fn+Bn fn+Bn fn
APLC DPLC DPLC APLC
Speech, Speech,
2 8 NSD600#1 NSD600#2 NSD600#2 NSD600#1
11 2 or or
6 12 Ch1 Ch1
Ch2 Ch2
fn fn+Bn fn+Bn fn
2 12
12 3 or or
6 16
band, must be kept free because it is used by the PLC equipment for
an auxiliary signal called 'pilot'. The pilot serves several purposes such
as:
frequency synchronization,
automatic gain control (AGC),
transmission of E- and M-telephone-signaling over the link,
embedded operation channel (EOC) of the link,
guard signal for the integrated teleprotection equipment NSD600.
Data Pilot
Speech Data 600 Bd 100 Bd band
Many possibilities exist for the frequency allocation of the services into
an AF channel due to:
programmable speech bandwidth,
programmable bandwidths for AF data channels depending on the
required data rates,
programmable center frequencies for AF data channels,
programmable pilot frequencies.
Fig. 3-6 shows all relevant possibilities for the frequency allocation in a
1
The frequency allocation possibilities for the 3.2 and 2.4 kHz AF
channels for the case 3 APLC channels in 8 kHz (Setting No. 6 in
Table 3-1) are shown in Fig. 3-7 and Fig. 3-8.
1
Fig. 3-9 shows the case of 2 kHz nominal bandwidth (Setting No. 9 in
1
Table 3-1).
1
3-11.
780
Fig. 3-6
900
1020
1140
1260
2520 2520
2580
2700
2820
2940
June 2012
3060
3180
3300
3-9
ABB Switzerland Ltd
ABB Switzerland Ltd 1KHL015946-EN ETL600
2880
3000
3120
2120
3350
2000
2200
2320
2400
2520
Hz
300
ETL600: Usable bandwidth of a 3.2kHz AF channel
Speech 2000 Hz
ETL600 Pilot
Speech 2200 Hz
Standard
Speech 2400 Hz
Pilot
Speech 2600 Hz 3120 Hz
Speech 2800 Hz
50 Bd/120Hz
1020
1140
1260
1380
1500
1620
1740
1860
1980
2100
2220
2340
2460
2580
2700
2820
2940
3060
3180
420
540
660
780
900
(R.35)
External modem
480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 100 Bd/240 Hz
(R.37)
540 900 1260 1620 1980 2340 2700 3060 200 Bd/360 Hz
(R.38b)
2880
3000
3350
2000
2200
2320
2400
2520
300
Hz
Hz
Standard
Speech 2000 Hz Pilot
2280 Hz
50 Bd/120Hz
(R.35)
External modem
Hz
Fig. 3-8 Use of ETL bandwidth for channels 2 and 3 of the configurarion
3 APLC channels in 8 kHz
1800
300
1600
2000
Fig. 3-9 Use of ETL bandwidth for nominal bandwidth of 2.0 kHz
2000
2400
2160
300
Fig. 3-10 Use of ETL bandwidth for the 2 kHz AF channel adjacent to
MOD600 2 kHz
2000
2200
2400
2580
2700
300
Fig. 3-11 Use of ETL bandwidth for the 2 kHz AF channel adjacent to
MOD600 6 kHz
with Rx-filter (Fig. 3-28 a) and without Rx-filter (Fig. 3-28 b).
Legend for the figures in this section:
1: AF interface type O4LE (optional for telephony, teleoperation and
external teleprotection)
2: NSD600 teleprotection interface type G4AI (optional)
3: DSP module type P4LT
4: DSP module type P4LU, with additional serial ports and an
optional LAN port
5: Alarm relay module type R1BC (optional, in the rear)
6: DC-DC-converter type B4LE
7: Channel subrack type P7LC
8: 40 W power amplifier type P1LA (mounted in the rear)
9: Transmit filter type E5TX
10: Carrier combiner type P3LG
11: RF hybrid type P3LE or optional for testing dummy load
P3LK
12: Receive filter type P4RX (optional)
13: Power supply type B5LA or B5LC
14: Power subrack type P7LA
15: Compressed telephony interface type O4CV
16: DSP module type P4LV, with LAN and digital transit ports
17: DSP module type P4LX, with LAN, digital transit and additional
serial ports
All modules are plugged from the front except where otherwise noted.
13 9 10 8 14
13 9 11 8 14
6 1 1 1 3 1 1 12
or or or or or or 5
2 2 2 2 4 2 2 2
or or or or or or or or
7
15* 15* 15* 15* 16 15* 15* 15*
or
17
9R 6R 5R 6R 6R 6R 14R 6R 5R 6R 6R 9R
N01 N11 N22 N28 N34 N45 N54 N65 N71 N78
B: Basic equipment
ORF: Optional RF equipment
OLF: Optional LF equipment (depending on desired services)
Interface boards 16 (O4CV), 1 (O4LE) and 2 (G4AI) are required to
support the DPLC service compressed telephony and the APLC
services telephony, teleoperation and teleprotection. These boards
have to be inserted in the foreseen slots OLF of the channel subrack 7.
Up to seven interface boards may be inserted in an ETL640 or
ETL680. They galvanically separate the interface signals from the
equipment and transform these signals into a form suitable
for transmission over the equipments Time Division Multiplexing
(TDM) bus and
for Frequency Division Multiplexing (FDM) into the AF-channel(s),
refer to Fig. 3-5.
1
TDM bus 7
Telephony compressed P7LC
16
O4CV Supply
Telephony
1
14
optional
Teleoperation 6 13 P7LA
1 B5LA
O4LE B4LE
B5LC
Ext. teleprotection
(e.g. NSD570)
Teleprotection 8
2 P1LA
G4AI
IRIG-B
9
Data V.11, V.24 3 E5TX
P4LT
4
P4LU
Data G.703.1
or
RF
optional
Digital transit 16 11
P4LV P3LE
Coax
or cable
LAN
17
P4LX
Alarm contacts
5
R1BC
Alarm contacts
12
HMI P4RX
TDM bus
7
Telephony compressed P7LC
16
O4CV Supply
Telephony
1
14
Teleoperation 1 6 13 P7LA
B4LE B5LA
O4LE B5LC
Ext. teleprotection
(e.g. NSD570)
Teleprotection 8
2 P1LA
G4AI
IRIG-B
Data G.703.1 4
P4LU RF
11 9
or E5TX
Digital transit P3LE
Coax
16 cable
P4LV
LAN
or
17
Alarm contacts P4LX
5
R1BC
Alarm contacts
HMI
8
Teleprotection
2 P1LA
G4AI
8
P1LA
IRIG-B
9
E5TX
Data V.11, V.24
3 9
E5TX
P4LT
Data V.11, V.24
or 10
P3LG
Data G.703.1 4
P4LU
or
Digital transit
16
P4LV
LAN
or
11 RF
17 P3LE
Alarm contacts P4LX Coax
5 cable
R1BC
Alarm contacts
HMI 12
P4RX
SERVICE-PHONE:
RESET
12 'RDY' LED green: Service phone ready
On if the speech channel is available for the service
phone.
'ENA' LED green: Service phone enabled
On if the service phone is enabled on the module.
Flashes if the service phone is ringing.
'RESET' Push button: Reset
When pressed, the module resets and fetches
configuration data from flash EPROM.
SERVICE-
PHONE
Socket for the service phone
AF
O4LE
synchronization
DSP
P4LT
P4LU
LEDs:
LEDs:
DSP
P4LX
User alarm 1
From DSP module User alarm 2
User alarm 3
2 X40
R1BC 6
4
k5 CA-5 CA-1 k1
k6 CA-6 CA-2 k2
k7 CA-7 CA-3 k3
k8 CA-8 CA-4 k4
TXFIL-OUT
TXFIL-OUT
HYB-IN
GND
X174
X171
X168
X165
X177
X176
X178
X110 Us +38V to 45V
+
42V to 58V
X107
- DD
to X183 Us
X182
+26V
B/D/Z16
HYB-IN
B/D/Z14
GND
X184
B/D/Z28
1 ZFFILT-IN
TXRF12-A
B/D/Z26
2 ZFFILT-GND
TXRF12-B
B/D/Z30
PAMPOUT-A
3
TXRF34-A nom. 50W
20 Ohm
4 Imax BIAS B/D/Z32
TXRF34-B PAMPOUT-B
AA
0 ... 2 dBu
24 - 500kHz
150 Ohm
EE FF
Z2
CFB B2 RF-RELAY
VFB
Us
Z8
SUPER-
VISION TX-ALARM
Z10
RF LINE
Tx Alarm X175
Level adj. Tx B/D/Z20
CH CL BB
Alarm
B/D/Z22
B/D/Z24
X179
X180
X181
GND
TXRF40W
TXRF80W
Fig. 3-23 P1LA Block Diagram
+
P1LA E5TX
-
Tx-Filter
(upper HPA)
RF
Combiner P3LG P3LE
(lower HPA)
Hybrid
Tx-Filter
+
Tx P1LA E5TX
-
Rx-Filter
Rx P4RX
+12.8V
Regulator +5V
z6
TX filter 1
d/b/z16
JR
7.33 select R
80W to hybrid
resistors on 15.67 d/b/z24
heat sink
26.67
T202
GND
d/b/z14 d8
plug-out
TXRF-40W d10
TX filter 2
d/b/z22
+5V
TX Alarm
Amplifier 2
d/b/z30
TA1 relay shown not energized
TX filter 2
d/b/z28 TA2 WARN
TA3 b8
TB1 K201 OPTO-AL TX RF AL
Alarm logic
d6
TB2 TXAL
TB3
HF signal d/b/z32
GND T201
d/b/z26
RX RF relay GND-CE
z6
z2 / b2
OPTO-AL
z8
TXAL default jumpers shown
b6
T3B2 hybrid
transformer
T2 selective
T3B3 supervision
S2 z12
T3
S1
d/b/z14 T1
d12
d8 RX RF signal
plug out RX level
R125 b12
d10
RF Line Monitor
100W=0dBm
divider, frequency compensation
@ 50 Ohm
RD RA RP (50dB below line
park position 45 Ohm
TX Filter M1 dbz20)
75 Ohm
d/b/z28 R228 M2
125 Ohm
T4A1 M3
T4A2
T4A3 L1
T4B1
Amplifier LA LN LP K1, K2, K3,
d/b/z30 T4B2 45 75 125
K1 park position Ohm Ohm Ohm
T4B3 +12.8V
Amplifier z6
T4 CA CB CD CE CL
d/b/z32
common Line Balancing Network
TX Filter
Tx ALARM
d7b/z26
TX relay
TXRF Power Alarm
z2 / b2 Alarm circuit
d6
Amplifier alarm
z8 GND P7LB (CE)
z10
Default jumpers shown, K1 not energized
With the jumpers H1 to H6, S1 and S2, two topologies of the RF front
end can be selected:
Inserting jumpers H1, H2, H3, S1 selects the topology according to
Fig. 3-28 a, while
Inserting jumpers H4, H5, H6, S2 selects the topology according to
Fig. 3-28 b.
1
Power Power
Amplifier Tx-Filter
+ + Amplifier
Tx P1LA E5TX Tx P1LA
- -
RF Tx-Filter
Hybrid P3LE RF
Hybrid P3LE E5TX
Rx-Filter
Rx P4RX Rx
a b
Analog front end with Rx-filter Analog front end without Rx-filter
(Fig. 3-28 a)
1 (Fig. 3-28 b)
1
Table 3-2 Comparison of RF front end topologies with and without Rx-filter
RXRF-IN-B C1
1.) Rx-filter 2.)
A2 50
TUNE- F2 not used
RxRF IN
A4 A27
T-OUT
2.) V-IN
C4
TUNE- F1
Rx-filter
termination
resistor
50
A8
diff amplifier amplifier PLUG-OUT4
RxRF OUT
C9 TXRF-A
not used C10
B5 TXRF-B
RXRF-OUT-A
B7
RXRF-OUT-B
+12.8V A/C/22/23
+ 5V
power supply GND see backplane P1LC
voltage regulators
-12.8V A/C/24/25
- 5V
chassis
1.) A1 and C1 used for Rx filter test with tuning adapter P4LM
X177
X176
X178
P1LA
L2 L1
X74 X60:1 X2:1 X2:3 X60:3 X39:3 X1.3 X1:1 X39:1 X65
X165
P3LE
Fig. 3-30
X100/02
DD
X2:2 X1:2
B/D/Z16
BACK PLANE
PCB NB
GND
100W=0dBm
X68
X71 X60:2 X39:2 T3
X168 B/D/Z14
B/D/Z20
X179 RF-LINE
ABB Switzerland Ltd
X174 B/D/Z28
X171 B/D/Z26
P1LA T4
Us +38 V to 45 V B/D/Z30
B/D/Z32
2nd amplifier
+26V
X184/01 TXRF-A
Z02
X184/02 TXRF-B
X184/03
CFB RF Relay
B02
X184/04
AA Imax BIAS Z10 Tx Alarm
June 2012
EE D06
1
Z06
+12V
Z08
Tx-Alarm
VFB
FF
D08
Plug out
D10 supervision
Rx Level
Super- D12
R116 vision
Rx-RF
Tx B12
BB ALARM
10V
yw/gn X17
P7LA
SERVICE-PHONE:
'RDY' LED green: Service phone ready
On if the speech channel is available for the service
phone.
'ENA' LED green: Service phone enabled
On if the service phone is enabled on the module.
Flashes if the service phone is ringing.
SERVICE-
PHONE
AF
O4CV
Telephony
Point-to-point hot line (direct phone),
Remote subscriber,
4-wire PAX connection with E&M signaling,
2/4-wire PAX connection with E&M signaling and hybrid control,
E&M signaling,
Service phone.
Teleoperation
Transmission of AF data signals from modems
Programmable transit filters
The ports for all these applications are located on the O4LE board(s).
3.4.1. Telephony
One APLC channel of the ETL can carry one telephony channel, its
upper edge frequency being programmable to 2.0, 2.2, 2.4, 2.6, 2.8,
3.0, 3.2 or 3.4 kHz 2 . The speech signal is scaled to the nominal level
1
2 For the case of 3 APLC channels in 8 kHz, the range of available speech
bandwidths is restricted. For 2 kHz nominal bandwidth, the upper edge
frequency of the speech band is 1.6 kHz.
ETL600 ETL600
a/b
O4LE O4LE a/b
Direct Direct
Phone Phone
ETL600 ETL600
ETL600 ETL600
Local/Transit
E&M, PAX Blocking
a/b O4LE O4LE
Subscriber 4
PAX
ETL600 ETL600
Local/Transit Local/Transit
E&M, PAX Blocking E&M, PAX Blocking
O4LE O4LE
4 4
PAX PAX
3.4.1.4. 2/4-wire PAX connection with E&M signaling and hybrid control
ETL600 ETL600
Local/Transit Local/Transit
E&M, PAX Blocking E&M, PAX Blocking
4 O4LE O4LE 4
2 2
PAX PAX
Fig. 3-36 2/4-wire PAX connection with E&M and hybrid control
ETL600 ETL600
a/b
O4LE O4LE a/b
Service Service
Phone Phone
The phone is plugged into the socket on the O4LE front plate. As soon
as the handset is picked up, a buzzer on O4LE in the opposite
equipment generates an intermittent audible tone. If a phone is
plugged on the opposite O4LE, it will generate an intermittent ringing
signal simultaneously. The ringing stops as soon as the service phone
on the opposite side is picked up.
In- and output speech levels and ringer frequency for the service
phone are programmable.
During periods of excessive line noise, the speech signal is not
squelched in contrast to the other telephony operation modes.
Compandor is always active for service phone.
3.4.1.7. Display E&M signaling at front LEDs
The internal state of E&M signaling wires can be monitored by
uploading the status with HMI600 or by watching the LEDs on the
O4LE front panel. Inverting one or both of these wires has no effect on
the LEDs.
An example of a successful establishment of a connection is shown in
Fig. 3-38.
Fig. 3-39 State of LEDs showing to internal E&M when one PAX
is not working correctly
3.4.2. Teleoperation
3.4.2.1. Ports
Three galvanically isolated teleoperation 4-wire ports AF2, AF3 and
AF4 are provided on each O4LE board. A fourth port AF1 is available if
no 4-wire telephony is configured. Each port consists of an input and
an output port with an impedance of 600 Ohms. The frequency range
of the ports is between 300 and 4000 Hz. Signals within this frequency
range are transmitted transparently over the link. Each output port can
be squelched individually during periods of excessive line noise. Each
port can be connected individually to either one of two AF-channels.
Each port may be used either in mode 'disconnectable' or mode 'non-
disconnectable':
In mode 'disconnectable', the signal applied to the input port is
suppressed during the transmission of teleprotection command
signals. This allows to assign more power to the teleprotection
signal during command transmission.
In mode 'non-disconnectable', the signal applied to the input port
is not suppressed during the transmission of teleprotection
command signals. This mode has to be chosen when the short
signal interruptions (typically less than 100 ms) caused by
teleprotection command transmission in mode 'disconnectable'
cannot be tolerated. As a consequence, the available power for
teleprotection command signals is reduced accordingly.
For more information on the management of signal levels for
teleprotection, refer to section 3.4.3 External teleprotection' and to
1 1
SPEECH BAND
0 1 2 3 4 kHz
ETL600 ETL600
4 If one or more of the modems are configured for 9600 bps, only three
NSK600 modems are supported.
9.6, 11 5, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64, 72,
76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2,
320 kbps,
the upper limit being restricted by the choice of the DPLC bandwidth,
refer to Table 3-3. The MOD600 bandwidths of 2*), 4, 6*), 8, 12, 16, 20,
1
5 Only for MOD600 bandwidth 2 kHz, not available for ETL600 Rel.3.1 or
earlier.
to die off before the next data packet starts. Data throughput is
decreased while data delay is increased with increasing length of the
guard interval. The tradeoff between delay and data throughput is
evident from Table 3-3.
1
1) MUX600
LAN traffic
V.11 Port 1
V.11 Port 2
6)
Compressed
telephony DPLC Channel MOD600
channels Multiplexer Modem
1 16
V.24 Port
Sharing
Device
3) 3) 2)
NSK600
V.24 Port 1
Modem 1
3)
NSK600
V.24 Port 2
Modem 2
4)
NSK600
V.24 Port 3
Modem 3
4)
NSK600
V.24 Port 4
Modem 4
5)
V.24 Port 5
5)
V.24 Port 6
UDF ADJ
The required gross data rate for each MOD600 profile can be
calculated according to the following formula:
GrossDatarate bit/s NetDatarate bit/s 1000
9 bit 2 bit Channels
10 ms
where:
GrossDatarate is the required aggregate rate of MOD600 modem;
NetDatarate is the sum of all individual channel data transfer rates;
10 ms is the frame length;
9 bit is the preamble for synchronization of the frame;
2 bit are used for speed adjustment per each channel;
Channels is the number of configured channels other than
compressed telephony channels.
The multiplexer detects the data transfer rate being used by MOD600
and automatically adjusts its own operation accordingly.
If the DPLC modem reduces its data transfer rate due to poor
transmission conditions (fallback), the data transfer rate of the
aggregate channel also has to be reduced and this means that the
data transfer rates of individual channels have to be reduced or the
channels switched off. Five different data transfer rate profiles for the
aggregate channel and each individual channel can be defined for this
purpose.
External data terminals can be connected to the channels as follows:
Up to one G.703.1 interface for synchronous data transfer at 64
kbps (not available for ETL600 Rel.1.0);
Up to one LAN interface for Ethernet traffic at data transfer rates
from 9600 bps up maximum available data rate for MOD600 (not
available for ETL600 Rel.1.0);
One or two V.11 interfaces for synchronous data transfer at data
transfer rates from 9600 bps up to maximum available data rate
for MOD600;
Two to six V.24 interfaces for asynchronous data transfer at data
transfer rates from 1200 to 19200 bps 6.
Up to 16 compressed telephony interfaces, all at data transfer
rates of either 5300 or 6300 bps.
For details about the different data terminals refer to section 3.5.4. For
1
ETL600 ETL600
O4CV O4CV
a/b a/b
Subscriber
PAX
shown in Fig. 3-45 as it has only one 2-wire section instead of two.
1
As long as the subscriber loop is idle, the service phone may utilize the
compressed telephony channel. In any case, the subscriber loop has
priority over the service phone.
All local and remote equipment features and parameters are selected
and programmed by means of the user interface type HMI600. All
status-, configuration- und alarm-messages are also accessible from
remote.
An integrated event recorder and trip counters are provided (command
start/stop events, alarm events and manipulation events are recorded
and stored with time stamp in a non-volatile memory).
3.7.3. Structure of NSD600
The NSD600 signals are processed completely digitally by a DSP
(Digital Signal Processor) on the DSP module type P4LT/U/V/X of the
basic ETL600 equipment and by a DSP on the Teleprotection Interface
type G4AI, so the firmware for the NSD600 resides on both modules.
The NSD600 comprises at least one teleprotection interface type
G4AI. As contact multipliers or to exploit all possible NSD600
functions, additional interface modules can be directly plugged into
reserved slots of the PLC equipment. However the user will not be
allowed to select the position of the modules. He must only select the
number of required inputs/outputs and the HMI600 will first check the
possibility of using the selected modules and then allocates the
positions for them.
Commands of the two TPE can not be mixed on the same
teleprotection interface type G4AI, i.e. there is at least one G4AI
module necessary for each of the two possible TPE. The tabs of the
HMI600 user interface software for configuration of the teleprotection
interfaces G4AI are correspondingly assigned as G4AI TPE1 and
G4AI TPE2.
3.7.4. Features
Modular design
Appropriate grouping of the functions into the signal processing
module and protection interface modules. The teleprotection
interface type G4AI is inserted into the rack type P7LC of the
ETL600 PLC equipment.
Two individual NSD600 teleprotection equipment are configurable
in the APLC and DPLC channels of the ETL600 system.
Advanced technology, digital signal processing
High equipment availability and reliability due to carefully selected
components which have passed rigorous qualification tests.
Using digital signal processing technologies, the NSD600 meets
the stringent requirements for command transmission over PLC
links even under adverse channel conditions. Algorithms optimized
for PLC channels ensure safe and reliable operation as well as
short transmission times even under extremely difficult conditions.
Up to 4 independent commands per NSD600
Duplex transmission of permissive tripping or blocking commands
and direct transfer tripping commands in protection schemes for
single or dual circuit lines including breaker failure protection.
In its minimum configuration with one teleprotection interface type
G4AI, the NSD600 can convey up to four commands.
Versatile application
The independent commands of the NSD600 can individually be
configured for direct transfer tripping, for blocking or for permissive
tripping schemes. Due to a patented dynamic adaptation, the
command signals are received at the remote end in the shortest
possible time, even if the channel is disturbed.
Adaptive algorithms especially developed for this type of
teleprotection equipment adjust themselves continuously to the
prevailing channel conditions and achieve even under worst-case
conditions the high degree of security against loss of genuine,
respectively acceptance of false tripping commands.
Signal boosting
By switching off speech and data communication for a short time,
the best use is made of the available transmitter power to
guarantee reliable transmission of every tripping signal sequence.
Two tripping criteria
Incorrect operation due to a single fault is prevented by processing
guard and active signals separately.
No additional bandwidth required
NSD600 requires no extra bandwidth in its default configuration
because it uses the pilot of the corresponding PLC channel as
guard signal and the speech band as command channel.
Easy to configure and to service
A serial interface port is provided on the front plate of the DSP
module P4LT/U/V/X for connecting a PC which enables operating
and equipment information to be viewed.
Configuration, supervision and adapting to the field requirements of
both the local and remote equipment is done by means of the user
interface HMI600 which operates under the MS-Windows
platform.
Integrated event recorder and trip counters
More than 2500 command start/stop and more than 2500 alarm &
manipulation events can be recorded and stored with time stamp in
a non-volatile memory. The event recorder can be synchronized to
an external time signal (e.g. GPS receiver) for accurate time
stamping. The display of command events is possible in text and
graphical views on the HMI600.
In addition to the event recorder integrated trip counters for each
sent and received command support investigations in case of faults
or abnormal conditions in the high voltage network.
Command outputs during channel failure
By means of the HMI600 interface, the user can program how the
command outputs respond to a link alarm, i.e. to SNR alarm or Rx
level alarm:
alarm does not influence the command outputs
(state according current trip signal evaluation),
alarm sets command outputs to guard state (blocked),
alarm sets command outputs for direct tripping to guard state
and command outputs for permissive tripping or blocking to
command state,
received commands are frozen at the outputs in case of an
interrupted or disturbed link.
Command prolongation: 10 ms
The corresponding configuration, setup and further programming
instructions are to be found in section 5.3.7.
According to IEC 60834-1, Figure 21, the requirements for permissive
tripping commands are:
transmission time Tac of less or equal than 20 ms,
with a dependability Pmc of less than 1E-03,
at a signal-to-noise ratio SNR of 6 dB,
with a security Puc of less than 1E-04.
The NSD600 performance is even better (see annex, Technical Data).
3.7.5.2. Direct Transfer Tripping
Typical applications for direct transfer tripping are breaker back-up
protection, compensator protection and power transformer protection;
line protection with direct transfer tripping would be an exception. The
requirements with respect to transmission time are generally not too
demanding.
In the case of direct transfer tripping, the tripping command from the
teleprotection equipment goes directly to the circuit-breaker tripping
coil. Thus a spurious tripping signal resulting either from interference
or human error will cause unwanted, usually three-phase tripping of
the line and will block the operation of any auto-reclosure relay.
A genuine transfer tripping signal, on the other hand, must on no
account be lost whether there is interference on the communications
channel or not, because then a line fault would not be isolated with
correspondingly serious consequences.
Extremely high security and high dependability are therefore more
important than transmission time for direct transfer tripping.
In order to fulfill these requirements, the NSD600 uses dual tone
tripping signals. Dual tone signals provide the necessary additional
security against incorrect interpretation of speech, audio signals
coupled into the system and incorrect manipulations on the equipment.
signals. All commands can be transmitted and received with one single
teleprotection interface type G4AI.
Important dual-circuit lines (132 kV to 400 kV) are often equipped with
1st and 2nd main protections supported by breaker failure protection
on each circuit. Logically, redundant communication channels should
also be installed such that the protection of both circuits remains fully
intact should one set of equipment fail due to a defect or human error,
or be out of commission for servicing.
The NSD600 with its four transfer tripping signals is especially well
equipped to efficiently handle the tripping commands generated by
redundant main and breaker failure protection schemes for a dual-
circuit line. An extremely reliable overall scheme would comprise two
sets of PLC and NSD600 equipment, the NSD600's having the need of
only one relay interface for four transfer tripping signals each. A
corresponding example of a redundant teleprotection scheme can be
seen in Fig. 3-49.
LINE 1
B PHASE
ETL600
MP1 Line 1 A
CF 1
MP2 Line 2 B
BFP Line 1 C
BFP Line 2 D NSD600
ETL600
MP1 Line 2 A CF 2
MP2 Line 1 B
C
D NSD600
LINE 2
MP1: 1st main protection B PHASE
MP2: 2nd main protection
section 3.7.5.2.
1
A PHASE
ETL600
MP1 A
CF 1
MP2 B
BFP C
GSD/LS D NSD600
ETL600
A CF 2
B
C
D NSD600
B PHASE
MP1: 1st main protection GSD: generator shut down
MP2: 2nd main protection LS: load shedding
T0 = TI/O + Tg + Tev
'Dependability').
The actual transmission time of the NSD600 is measured, for example,
by means of the manual or cyclic loop tests, refer to section 3.7.8.13
1
and 3.7.8.14.
1
3.7.6.3. Security
The NSD600 with its dynamic adaptation of the receiver provides the
best security / dependability trade-off for the chosen command
application at lowest possible transmission time.
Security is expressed as the "worst case" false signal rate (probability
of unwanted commands Puc) for blocks of noise of 200 ms duration.
"Worst case" is defined as the level of interference at which the guard
signal is completely suppressed.
The security level Puc is fixed for each of the possible command
applications.
Security Measurements
All security measurements were performed according to the
procedures prescribed in IEC 60834-1.
Noise burst 200 ms
Duration of pause 200 ms
Noise bandwidth 4 kHz
SNR 0 dB -30 dB
Security is determined by coupling bursts of white noise of high
amplitude into the communications channel. The number of bursts
injected and the number of false commands they cause at the
receiving end are counted.
Puc = Nuc / NB
3.7.6.4. Dependability
For analog channels, dependability is expressed as the signal-to-noise
ratio (SNR) for a noise bandwidth of 4 kHz, which must be maintained
during the transmission of a tripping signal to enable that it can be
received within a given actual transmission time Tac (usually a multiple
of T0). The probability of missing a command Pmc at that SNR and
Tac must be < 1E-03 for blocking and permissive tripping commands
and < 1E-04 for direct tripping commands.
Dependability Measurements
All dependability measurements were performed according to the
procedures prescribed in IEC 60834-1.
Command duration 3 T0
Duration of pause 2 command duration
Noise bandwidth 4 kHz
SNR -10 dB +20 dB
continuous white noise
Dependability is determined by sending a large number of commands
to the remote station. The number of commands transmitted and the
number of commands received within a specified time (normally 1.3 x
T0, 1.5 x T0, 2 x T0 and 3 x T0) are recorded. The lower the signal-to-
noise ratio at the input of the receiving NSD600, the fewer the
commands which will be received in the prescribed time.
The following applies for a sufficiently high number of transmitted
commands:
In conjunction with one APLC channel, the DPLC channel requires its
own guard signal for the NSD600 (which is not necessary without TPE
in the DPLC).
A detailed description of the ETL600 operating principle and the
various channel allocations can be found in sections 3.1 and 3.2.
1 1
Default setting for the NSD600 guard signal in the 3.2 kHz APLC
channel is the ETL600 pilot at 3120 Hz. The disposable teleoperation
band is then limited from 120 Hz above selected speech up to 2880 Hz
(refer to Fig. 3-7).
1
If the ETL600 pilot signal is shifted from its default value to lower
frequencies, teleoperation channels may only be allocated with a
frequency margin of 240 Hz from the center of the pilot channel.
For special purpose, e.g. transit relaying of NSD600 signals in a
repeater station, a separate guard signal for the teleprotection may be
programmed in the 3.2 kHz and in 4 kHz APLC channels. It is then
located above the chosen speech frequency band. This is however
possible only for the following speech channels: 2.0, 2.2 or 2.4 kHz
(example for 4 kHz APLC channel see Fig. 3-52).
1
A gap of 480 Hz has to be reserved for the own guard signal of the
NSD600. The disposable teleoperation band is therefore limited from
480 Hz above selected speech up to 3000 Hz in the 3.2 kHz APLC
channel and up to 3720 Hz in 4 kHz APLC channels.
If no speech is configured in the 3.2 kHz or 4 kHz APLC channel, the
own guard signal is allocated in the band 2000 Hz to 2480 Hz. Please
note that also in this case the band 300 Hz to 2000 Hz must not be
occupied by other services (refer to sections 3.7.8.19 and 3.7.8.20).
1 1
2320 Hz 3600 Hz
NSD600 Guardfilter 2120 Hz 2520 Hz 3840 Hz
Fig. 3-51 Examples for allocation of the 4 kHz band with speech
and the ETL600 pilot as NSD600 guard signal
2680 Hz 3720 Hz
2480 Hz 2880 Hz 3840 Hz
Fig. 3-52 Examples for allocation of the 4 kHz band with speech
and an own NSD600 guard signal
If two TPE are configured, one in the APLC and one in the DPLC
channel, a band of 500 Hz is always reserved in the DPLC channel for
the guard of TPE2. The trip frequencies of TPE2 are located in the
DPLC channel at the same AF band as in a standard APLC channel of
4 kHz (at the upper or at the lower end of the DPLC channel,
depending whether it is configured as erected or inverted; refer to
section 3.1.1 for details). The same applies for TPE1 in the DPLC
1
4 kHz APLC channels as well as in the DPLC channel, i.e. with seven
trip frequencies in the band 300 to 2000 Hz.
The single purpose teleprotection NSD600 in 2 kHz nominal bandwidth
also uses the dual-tone principle with five trip frequencies in the band
of 300 to 1600 Hz.
Guard signal
Trip
signal
F1 F2 F3 F4 F5 F6 F7 G Frequency Time
3.7.8.5. Boosting
Signal boosting in connection with a PLC channel means that the
power used for transmitting tripping signals is stepped up in relation to
the quiescent state (i.e. the guard signal).
During the transmission of tripping signals, the communication of the
DPLC as well as the communication of speech, teleoperation channels
(set as 'disconnectable') and modem signals superimposed on the
speech in all channels is switched off (this includes the pilot signals in
APLC channels without TPE). The total transmitter power is available
now for the tripping signals. This ensures the best possible signal-to-
noise ratio at the receiving NSD600. The ratio between the powers of
the boosted transfer tripping signals and the guard signal is referred to
as the boost ratio and is normally expressed in decibel (dB).
The boost ratio which can be achieved depends on what other service
signals can be switched off while tripping signals are being
transmitted. This in turn is dependent on just how many signals the
ETL600 has to handle and for this reason, the boost ratio is calculated
automatically by the HMI600 after configuring the equipment.
It may be necessary to select some teleoperation channels to be 'not
disconnectable' later, the boost ratio is accordingly decreased then by
the HMI600 (a corresponding warning note will appear on the screen).
Since both TPE interrupt the DPLC channel and all disconnectable
signals in all channels for command transmission (including speech
and pilot signals that are not used as TPE guard signals), much higher
boost ratios are possible compared to earlier PLC systems. However,
the maximum boost ratio is limited to 18 dB, it can be decreased via
HMI600 to a value between the minimum boost ratio (which depends
on the difference between the guard and the test tone level; can vary
from 0 dB to 6 dB) and the calculated boost ratio established by the
HMI600 (depends on the services that are configured and can be
switched off; can vary from the minimum boost ratio up to 18 dB).
If two internal TPE are configured, both NSD600 have the same
weight, i.e. they can use half of the disconnectable weight for boosting
their signals.
With single purpose teleprotection NSD600 in 2 kHz nominal
bandwidth the boost ratio setting range is from 6 dB to 18 dB without
optional service phone enabled and from 12 dB to 18 dB with service
phone.
Further information on boosting is to be found in section 5.2.16 in this
instruction manual.
Local Command
at G4AI Input
Local Command
e.g. 5 ms
with Tx Input Delay
Local Command
with Tx Input e.g. 20 ms
Prolongation
T0, e.g. 10 ms
Remote Command
as received of TPE
(DSP on P4LT)
Remote Command
with fixed Rx Output
Duration at G4AI Output e.g. 150 ms
Remote Command
with Rx Output Prolon- e.g. 30 ms
gation at G4AI Output
Note: Start inputs are not needed for the operating mode
Single purpose teleprotection NSD600 in 2 kHz
nominal bandwidth because no speech is supported
and the optional service phone is normally not used
during command signal transmission (but while
commissioning or maintaining the equipment as
examples).
3.7.8.8. Unblocking
An unblocking command used in directional comparison or in
permissive tripping schemes with overreaching first zone can be
allocated to one or more outputs on the teleprotection interface
module. Note that unblocking commands are not transmitted from the
remote end, but automatically produced by certain types of line faults
(PLC channels).
At time when neither tripping nor guard signals are being received, or
when the total signal level in the 2 kHz band is lower than the
configured unblocking threshold (range from 20 dB to 10 dB; default
14 dB from nominal level), an unblocking pulse of a predefined
duration is generated which can be signaled by one or more outputs
on the relay interface type G4AI.
The internal signal evaluation time to detect the unblocking condition is
typical less than 20 ms. It is possible to define an extra on-delay via
HMI600 in the range of 0 to 100 ms (default 20 ms).
The unblocking pulse duration is set to 200 ms per default but can be
varied in the range of 50 to 500 ms.
The unblocking threshold is valid for both, the signal level in the
speech band as well as the signal level in the guard channel (i.e. the
unblocking signal is only released if both levels are below the threshold
and the condition neither tripping nor guard signals being received is
fulfilled too).
3.7.8.9. Command Outputs During Link Failure
By means of the HMI600, the user can program how the command
outputs respond to a channel failure, i.e. to SNR alarm or Rx level
alarm in the corresponding channel of the TPE. The following
alternatives are available:
a) All command outputs assume states in accordance with current
input tripping signal processing, i.e. they disregard the TPE link
alarm (default setting).
b) All command outputs are set to their quiescent/guard states (i.e.
blocked).
c) The outputs configured for direct tripping are set to guard state and
the outputs configured for permissive tripping or blocking are set to
command state.
d) Received commands are immediately frozen at the command
outputs in case of an interrupted or disturbed link.
These settings apply to all signals in the case of units equipped for
several commands.
The corresponding HMI600 settings are given in section 5.3.7.
Alternative a) is the default setting when the units are supplied from
the works. With this setting the NSD600 responds normally to changes
3-100 June 2012 Structure and Function
ETL600 1KHW001489-EN ABB Switzerland Ltd
that the corresponding solid state output is closed or the coil of the
selected relay contact is energized.
If the TPE uses the ETL pilot as guard signal, it will be switched off
by the cyclic loop test.
In case the TPE is operated in the DPLC channel, the MOD600 signal
and the pilot/guard signal in the DPLC channel are switched off during
the cyclic loop test.
Providing the cyclic loop test is enabled by HMI600, a test signal with
its own frequency is transmitted to the opposite station and reflected
back - depending on the programming - once every 1/3/6/12/24 hours.
The test signal is processed in the same way as a normal tripping
signal (interruption of the guard signal and transmission of a test
frequency for 36 ms). The reception of the reflected signal must take
place between 6 ms and 120 ms after sending it, which ensures that
all the functions required for transmitting a tripping signal are fully
tested.
Whenever an automatically initiated loop test is not correctly received,
the next automatically initiated loop test will be performed 5 minutes
later and the warning Loop test failed once or twice is issued
immediately. When more than two consecutive loop tests fail, the
alarm Loop test failed more than twice is issued and the warning
Loop test failed once or twice is removed. As long as the loop tests
fail, the interval between automatically initiated loop tests will stay at 5
minutes. The first successful loop test after one or more failed loop
tests will remove the above mentioned warning or alarm immediately,
and the next automatically initiated loop test will take place after the
configured loop test interval time. Note that, quality of the transmission
channel permitted, the loop test can be correctly executed even if the
guard signal is permanently lost. The loss of the guard signal is,
however, signaled by both ETL600 and NSD600.
The testing facilities impair in no way the ability of the equipment to
respond to a protection command, i.e. a genuine tripping command is
always given priority over all tests.
If a cyclic loop test can not be sent regularly due to a command being
transmitted at that time, the NSD600 will try to resend it in intervals of
1 minute. An event recorder entry does only take place when the loop
test could actually be released, i.e. after the command transmission
has stopped.
The loop test includes automated measurement of the transmission
time, i.e. half the measured transmission time for both directions there
and back plus a delay for one relay interface input and output circuit is
recorded.
The signal used for this test has the same parameters as the
command with the highest application requirements regarding security.
3.7.8.14. Manual Loop Test
The loop test can also be initiated manually from any station via the
HMI600. The result of the test can be viewed in a window. The actual
measured transmission time is displayed (half the value of both
directions there and back, plus a delay for one input and one output
circuit of a teleprotection interface type G4AI, which can not be
included in this test).
If the reflection of a manually transmitted test signal is not correctly
received, it is correspondingly displayed in the loop test window.
transmission time !
The signal used for this test has the same parameters as the
command with the highest application requirements regarding security.
A manually initiated loop test is transmitted in the same way as the
cyclic loop test.
3.7.8.15. Local Test Mode
Each NSD600 can separately be set via HMI600 to a local operating
mode for checking the relay interfaces, e.g. for measuring the
command prolongation.
In this operating mode, which is indicated by the 'warning' LEDs and
via the HMI600 by the alarm message 'LOCAL TEST MODE', the
command input signal is looped via the TDM-bus by the TPE
processor on the DSP module P4LT/U/V/X back to the corresponding
command output of the same local teleprotection equipment.
Commands can for example be initiated from the protection relay
(separated from the protected objects!) or with the help of external
contact and battery voltage.
The relay contacts on G4AI are operated in the same way than the
alarm relays of the R1BC interface, i.e. the alarm condition is the
same as the power off state of the equipment (relay coil not
energized). On both modules the user can still choose by using the
corresponding output contacts - whether the alarm contact shall be
normally open or normally closed.
The solid-state outputs on G4AI are operated differently. An alarm
condition is signaled with a conducting (energized) FET. Therefore the
alarm condition is not the same as the power off state of the
equipment. For this reason it is recommended to configure alarm
signals on relay contacts only.
Both type of output contacts are activated only after the programmed
alarm delay time has elapsed. The same applies for the alarm hold
time. The LEDs of the outputs on G4AI correspond with the state of
the contacts, i.e. they also light up only if the alarm delay time has
elapsed and they will light on for the duration of the alarm hold time.
The maximum number of events per block is 2600 (i.e. 2600 command
events and 2600 alarm & manipulation events). If more than 2600
events per block occur, the eldest events are deleted and the 1000
newest events of each block are preserved.
The timing information for the event recorder is provided by the real
time clock (RTC) on the DSP module type P4LT/U/V/X. The date and
time is set via the user interface HMI600. If the accuracy of this time
setting procedure and the RTC is not sufficient, an external
synchronization source can be used (e.g. from a GPS receiver).
In case of a power supply failure the RTC is buffered for more than 24
hours.
The events are displayed by means of the HMI600. There are two
views available: a text based view and a graphic view. The graphic
view gives the possibility to compare files with command event
information from different equipment on one display.
3.8.2. NSD600 Command Events
The event recorder acquires the timing information of all commands
when they appear on the TPE DSP on the P4LT/U/V/X interface (delay
of inputs/outputs Teleprotection Interface and TDM-bus not considered
!). This means that the commands are recorded as they appear on the
transmission channel (Tx/Rx). The times when the commands appear
at the I/Os of G4AI may be calculated, if required (according to the
programmed input on-delay/prolongation times and output
prolongation time of the command).
The command entry in the event recorder listing is Tx/Rx Command
A/B/C/D On/Off. In order to distinguish between two teleprotection
equipment TPE1 and TPE2, the corresponding designation is added
beforehand (i.e. TPE1 Rx Command A off.
The following events are recorded as NSD600 command events:
Start time and end time of all commands transmitted
Start time and end time of all commands received
Start and end time of an unblocking pulse
Start time and end time of the activation of the configured Start
input(s)
The following events of the local device are recorded as alarm &
manipulation events:
Start time, end time and time of a change in any PLC low level
alarm or warning
Start time, end time and time of a change in any DATA low level
alarm or warning
Start time end time and time of a change of the TPE1 low level
alarm or warning
Start time, end time and time of a change of the TPE2 low level
alarm or warning
Start time, end time and time of a change of communication errors
on the TDM-bus
Time when a loop test was sent, was reflected or failed
Time when a manual loop test was initiated (by means of HMI600)
Time when the configuration was downloaded or stored to EPROM
Time when a firmware version was downloaded
Time when switched back to the previous configuration
Time when a new date and time was set
Time when the equipment started up
Time when a manual reset was conducted
Number of lost events in case of overload
All these events are stored in the same block. The maximum number
of alarm & manipulation events is 2600.
To upload the alarm events from the ETL600 equipment use:
Equipment / Commissioning and maintenance / Event recorder /
Upload events.
3.8.4. Upload events
To upload and display the events in the user interface HMI600 use:
Equipment / Commissioning and maintenance / Event recorder /
Upload events
The user can choose between uploading the command events or the
alarm events or both of them. Further he has the choice to read all
events or only from a certain date and thereafter. Date and time are
entered in the form: DD MM YY and HH MM.
Uploading and processing the events can take quite some time
depending on the number of events which has to be read. The
progress of the uploading can be seen in the status bar of the user
interface HMI600. The upload may be interrupted by pressing the red
stop button in the tool bar.
view for the command events. The graphic view gives the possibility to
analyze files with command event information from different equipment
on one display.
3.8.9.1. Text view
There are two ways to switch to the text view. If the events are already
uploaded, use View / Display Events to change to the event recorder
text view.
If no events have been uploaded so far, use:
Equipment / Commissioning and maintenance / Event recorder /
Upload events
to read the events. When the upload has finished, the HMI600
switches to the event recorder text view.
The events are displayed in chronological order. The command events
and the alarm events are listed in two different tables, one below the
other. The information is given as follows: DATE / TIME / EVENT.
By pressing the right mouse button the following menu appears:
Extend alarms:
This will extend the alarm text and the exact information about
what alarm condition occurred is given. The extension of the
alarms can take some time. The status bar will inform about the
progress.
Graphic view:
This will switch to the graphic view. Refer to Section Graphic view
for more information.
3.8.9.2. Graphic view
The graphic view displays the sequence of command events in the
time domain. The user can specify which events he wants to see in
one view. It is possible to analyze files with command event
information from different equipment in one display.
It is possible to zoom or scroll in the time domain.
The graphic view display is subdivided into 4 views (view 1 to 4). In the
lower part of each view the information about date and time is
provided. In the upper left corner the following information can be
seen:
View number
Time per division in Days / Hours / Minutes / Seconds /
Milliseconds per division
Zoom Mode: In/Out
First of all, the user has to set up his views. After that zoom out
enables faster finding of the events. Then zoom in to analyze the
command event information in more detail.
4.2. Installation
4.2.1. System requirements
The PC on which HMI600 is to be installed must have one of the
operating systems Windows XP, Windows Vista or Windows 7
installed. A screen resolution of at least 1024 x 768 resolution is
recommended.
For communication with the ETL600 via cable or modem, one of the
COM ports or USB ports of the PC should be free or the PC should
have internet/intranet access via network card. In case of a USB port,
a USB to RS-232 converter is required (refer to section 4.4.2).
4.2.2. Install HMI600
1. Insert installation disk into the CD drive of your PC.
2. From the Windows Start menu, choose Run , Browse ,
change to the CD drive, double click the program setup.exe on
the CD and click OK.
3. Follow the instructions given by the installation program.
4.4.3.1.2. Cables
For the connection between modem and ETL600, a 9 pin null modem
cable has to be used:
Connector 1 (9 pin male) Connector 2 (9 pin male)
pin pin
1 not connected
2 3
3 2
4 6
5 5
6 4
7 8
8 7
9 not connected
11 P4LV or P4LX or P4LU equipped with LAN interface R1LA required. Not
available with P4LT.
Control Center
Substation A Substation B
HMI600 RS232-
connection EOC of
Dial up PSTN Dial up
PLC link RS232-
modem modem ETL600 ETL600 connection
Terminal A1 Terminal B1
R7AP HMI600
Substation C
EOC of
PLC link EOC of
ETL600 RS485-
PLC link
bus ETL600 ETL600
Terminal C1
Terminal A2 Terminal B2
RS485-
bus
R7AP
Data-
channel ETL600
Data (9600bps)
Data
R7AP comm. comm.
eqpt. eqpt.
Terminal B3
RS485-
bus EOC of
PLC link
EOC
of
PLC link
(100 bps)
EOC of ETL600 ETL600
PLC link
ETL600
Terminal C3 Terminal A3
Terminal C2
Control Center
Substation A
SNMP
Mgr HMI600 RS232-
EOC of
connection Dial up PSTN Dial up
PLC link
modem modem ETL600
Terminal A1
SNMP R7AP
Substation C
SNMP
Internet, Mgr
SNMP EOC of
Intranet, RS485-
PLC link
bus ETL600
LAN ,
WAN
EOC of
PLC link Terminal A2
ETL600
SNMP R7AP
Terminal C1
LAN600 Data-
channel
Data (9600bps) Data
R7AP comm. comm.
SNMP eqpt. eqpt.
Agent
RS485-
bus
Alarm
Polling
4.6. Operation
All functions of the HMI600 are accessible via the following 8 menu-
items, displayed at the top of the program window: File, Edit, View,
Equipment, Configuration, Network, Options, Window and Help.
Off line operation is covered mainly by the menus Configuration and
File, while On line operation is addressed mainly with the menus
Equipment and Network. The functions offered by menu Equipment
are only available after an equipment has been connected to the
HMI600 as described in section 4.4.
Important procedures for tuning and testing, for commissioning and
maintenance of the equipment are described in separate documents.
These documents can be found in the annex of this instruction manual.
HMI600
RAM
of Equipment
en PC Flash
Op EPROM
Up
loa t
d se
Re
ve
Sa Do
wn
loa
d e
File or
Equipment St
RAM
The procedures for transferring data between the locations all have
distinct names. As shown in the figure, there is no direct possibility of
data transfer from equipment EPROM to file: The operations Reset,
Upload and Save have to be executed in sequence. To transfer data
from file to EPROM, the operations Open, Download, Store have to
be executed.
Due to safety reasons, the HMI600 program treats the download
procedure as a temporary operation: After a predefined timeout to be
specified by the user, the equipment automatically performs a reset
operation, so that the system is rebooted, thereby undoing all changes
caused by the download operation by fetching the complete system
configuration data saved in EPROM previously. Should faulty settings
have been downloaded, resulting in loss of a PLC link, this feature
brings back the link into life automatically after the specified timeout.
4.8. Compatibility
The ETL600 system consists of
1. Hardware, consisting of a number of modules;
2. Firmware, residing on some of the modules and making the
processors on these modules execute various functions such as
modulation, digital filtering etc.;
3. PC based software HMI600, implementing the user interface for
configuration, monitoring and testing of the equipment.
The compatibility aspects explained in this section are coupled to
exchange of data between two items such as modules, terminals,
links, configuration files or HMI600 programs. Compatibility regarding
the exchange of operational information like speech, teleoperation
signals, teleprotection signals, is not addressed here.
The compatibility rules and relations for the present and all previous
ETL600 releases are summarized in the document 'Compatibility
requirements for ETL600'.
4.8.1. ETL600 releases, release numbers, version numbers, type codes
To understand the explanations in the following sections, the terms
'ETL600 release', 'release number', 'version number', 'type code' need
to be explained.
An ETL600 system release, identified by a release number, is a
product of defined functionality comprising hardware modules,
firmware and software. Firmware and software are identified with
version numbers of the form NN.nn., e.g. 5.08 (leading zeros may be
omitted). Releases are identified by release numbers of the form
RR.r, e.g. 3.1 (leading zeros may be omitted). Hardware modules are
identified with type codes consisting of 4 characters like P7LC, G4AI
or P4LT. Sometimes, a fifth character the revision index - is
appended to identify an upgraded version of a module. Example:
P4LTA would be an upgraded version of P4LT; P4LTB would be an
upgraded version of P4LTA and so on.
Release N.N
HMI600
for Rel. N.N
Up- Down-
load load
ETL600 terminal ETL600 terminal ETL600 terminal ETL600 terminal ETL600 terminal
Rel. << N.N Rel. < N.N Rel. N.N update of Rel. N.N Rel. > N.N
Update of
HMI600 HMI600 HMI600 HMI600
for Release << N.N for Release < N.N for Release > N.N
for Release N.N
File/
Release N.N Save
Configuration file Configuration file Configuration file Configuration file Configuration file
File/ File/
Open Save
HMI600
for Release N.N
Testing is done with the equipment powered, and all test procedures
are supported by HMI600, menu 'Equipment / Tuning and Testing'.
1 1 T 2
Pmean ( x ) lim
R0 T T T 2
x 2 (t )dt
(1)
Ppeak ( x)
1
R0
max x 2 (t ), t (2)
1
PPE ( x) Ppeak ( x)
2
1
2 R0
max x 2 (t ), t (3)
1 T 2
U RMS ( x ) lim
T T T 2
x 2 (t ) dt
(4)
1
U PE ( x) U peak ( x)
2
max x(t ) , t .
1
(6)
2
P ( x)
L dBm 10 log mean , . (7)
1 mW
where Pmean(x) is given by equation (1).
5.2.3.2. Absolute peak power level
The absolute peak power level defines by how many dB the peak
power P of a signal x is greater or smaller than the reference power of
1 mW:
P ( x)
L dBm peak 10 log peak , (8)
1 mW
where Ppeak(x) is given by equation (2).
P ( x)
L dBm PE 10 log PE , (9)
1 mW
where PPE(x) is given by equation (3).
5.2.3.4. Absolute voltage level
The absolute voltage level defines by how many dB the RMS voltage
U of a signal x is greater or smaller than the reference voltage of
775 mV:
U ( x)
Lu dBu 20 log RMS , (10)
775 mV
where URMS(x) is given by equation (4).
5.2.3.5. Absolute peak voltage level
The absolute peak voltage level defines by how many dB the peak
voltage U of a signal x is greater or smaller than the reference voltage
of 775 mV:
U ( x)
Lu dBu peak 20 log peak , (11)
775 mV
where Upeak(x) is given by equation (5).
5.2.3.6. Absolute peak envelope voltage level
The absolute peak envelope voltage level defines by how many dB the
peak envelope voltage U of a signal x is greater or smaller than the
reference voltage of 775 mV:
U ( x)
Lu dBu PE 20 log PE , (12)
775 mV
where UPE(x) is given by equation (6).
1 n 2
L dBm 20 log lim X 2 ( n)
n n n 2
1 n 2 2
10 log lim X ( n)
. (13)
n n n 2
L dBm peak 20 log max X ( n) , n
10 * log max X 2 ( n) , n . (14)
L dBm PE 3 20 log max X ( n) , n
3 10 * log max X 2 ( n) , n . (15)
As the signal samples X(n) are dimensionless values, the levels given
above are neither voltage nor power levels. But in analogy to the levels
defined for analog signals, we use the terms voltage level or power
level according to the above formulas also for digital signals.
5.2.5. Absolute psophometrically weighted level L0p [dBm0p]
This is basically the same as L0, but the index "p" indicates a
psophometrically-weighted level, which is generally defined according
to ITU-T. This weighting is only used in connection with the
specification of noise levels on speech channels. The equivalent noise
bandwidth of the psophometrically-weighted filter is 1.74 kHz.
1mW R0
Lu dBu L dBm 10 log
2
(775mV )
L dBm 10 log
R0
. (16)
600 Ohm
where R0 is the impedance of the measuring point.
Thus for an impedance of 600 Ohms, the voltage level Lu is equal to
the power level L.
Example:
The power level at the 75 Ohm RF output of a PLC equipment is 40 dBm. What is the
voltage level LU?
75 Ohm
Lu 40 dBm 10 log
600 Ohm
31 dBu .
Example:
For the test socket on the RF hybrid, we have Ats = 50 dB and the input impedance of
the measuring set is specified to 50 Ohms. A measured voltage level Lu|ts of -10 dBu
indicates a power level L of 50 - 10 = 40 dBm equivalent to 10 Watts at the RF
connector, which is the measuring point. If the measurement was made with a test
tone of level L0 = 0 dBm0, the signal at the RF connector is shown to have a relative
level of Lrel = 40 dBr. This follows from equation (17).
Table 5-1 lists the peak envelope system levels [dBm0 PE] and their
associated weights for ETL600. It also gives the PE to mean level
difference. All entries except NSD600 test command signal and
MOD600 must appear also in the signal selection dialog box for
O4LE teleoperation ports of HMI600.
Level
System level difference
Types of AF signals [dBm0 PE]
Weight PE to mean
[dB]
Speech with 3 dB safety margin +3 1.41 3
VFT channels and modems
50 Bd or
-12 0.25 2
100 Bd channel
200 or 300 Bd channel -9 0.35 2
600 Bd channel -3 0.71 2
1200 Bd-above-speech
-3 0.71 1.5
channel
1200 Bd-V.23 channel 1) 2) 0 1.0 1.5
NSK5 2400 Bd channel 1) 0 1.0 1.5
NSK600 2400 bps channel -3 0.7 7
NSK600 4800 bps channel +3 1.4 7
NSK600 9600 bps channel +9 2.8 7
Pilot tone not used as NSD600
guard signal or default -6 0.5 0
NSD570/NSD70C guard signal
Pilot tone used as NSD600
guard or 20*log(WNSD600guard) WNSD600guard 0
NSD600-own-guard 3)
AMX500 2 kHz +3 1.4 10
AMX500 4 kHz +9 2.8 10
MOD600 4) 20*log(WMOD600) WMOD600 10
Remarks:
1) For single channel equipment with 2400 Bd VFT channels or with 1200 Bd-V.23
channels operated in stand alone mode (no speech or other low speed VFT
channels being used) the weighting factor can be raised to 2 in order to fully exploit
the available transmit power.
2) If in a single channel equipment a 1200 Bd-V.23 channel is operated in parallel
with other low speed VFT channels, the weighting factor 1 (as for 1200 Bd V.23
operation in dual-channel equipment) has to be used.
3) Refer to section 5.2.13.
4) Refer to section 5.2.12.
It turns out that the 100 Bd VFT channel is superior to the speech channel mainly in
two aspects: It has a smaller noise bandwidth and requires a lower SNR. The
differences of all contributions add up to 15 dB, so that for the 100 Bd VFT channel, a
weight of 0.25 should be chosen: 20*log(1.41/0.25)= 15 dB.
To increase the level of the MOD600 signal in case the weight of the
sum of the APLC signals is low, (22) is replaced by the formula
4 (23)
wMOD 600 v D 2 A max , S APLC .
1 vD 2 A
This ensures that the weight of the MOD600 signal is always at least
8 1 v D 2 A times higher than the weight of the ETL600 pilot or
NSD600 guard signal.
5.2.13. Weight of the NSD600 guard signal
When a DPLC is configured, it can take a considerable amount of the
available RF power as explained in 5.2.12. When teleprotection
commands are transmitted, the MOD600 signal and other
disconnectable signals are switched off, so that more power can be
given to the teleprotection. This is called boosting, refer to section
5.2.16. The additional power improves the dependability of
teleprotection. However, there are limits to this technique: The
teleprotection guard signal, which is transmitted when the
teleprotection is inactive i.e. during the quiescent state, doesnt profit
S
wNSD 600 guard BR , (24)
20
10
where BR is the NSD600 boost ratio in dB set by HMI600. This
formula agrees with (25) (page 5-14) for wi 0 .
non disc .
When the ETL600 pilot acts as NSD600 guard, it obtains the weight of
the NSD600 guard signal, else the ETL600 pilot has the standard
weight of 0.5.
5.2.14. Internal teleprotection devices NSD600
Regarding internal teleprotection equipment (TPE), the following cases
can be distinguished:
1. No internal TPE,
2. One NSD600 (called TPE1 or NSD600#1),
3. Two NSD600 (called TPE1 or NSD600#1 and TPE2 or
NSD600#2).
Each internal TPE operates in one of the channels APLC1, APLC2 or
DPLC. The association to the channels is fixed. Thus, operation of
TPE2 is only possible if ETL600 is configured for at least two
channels. The following cases are possible:
Available Channels Channel of TPE 1 Channel of TPE 2
APLC1 APLC1 -
DPLC DPLC -
APLC1, DPLC APLC1 DPLC 1)
APLC1, APLC2 APLC1 APLC2
APLC1, APLC2, DPLC APLC1 APLC2
APLC1, APLC2, APLC3 APLC1 APLC2 2)
APLC1, APLC2, APLC3, DPLC APLC1 APLC2
BRx 20 log S wi 20 log wTPEx guard , (25)
non disc .
where
5.3.1.6. LAN
This tab depends on the type of DSP module: P4LU or P4LV/X (refer
to section 5.3.1.2).
In case of P4LU, the checkbox Bridging / IP Routing is inactive
unless DPLC channel multiplexing has been enabled in the tab Data
communication (refer to section 5.3.1.2). For LAN traffic to be
forwarded over the link, Bridging / IP Routing must be enabled.
In case of P4LV/X, when LAN over PLC is disabled, LAN traffic is not
forwarded via PLC link and the LAN ports operate in Switch (Layer 2)
mode. For LAN traffic to be forwarded over the link, LAN over PLC
must be enabled. The mode Router (Layer 3) cant be selected unless
LAN over PLC is enabled.
The functions SNMP and/or HMI over LAN can be enabled or
disabled independently.
5.3.2. System
Point to Configuration / System to get a dialog box with the 4 tabs
Equipment settings, Channel settings, Alarm settings and Alarm
relays on R1BC.
5.3.2.1. Equipment Settings
Remarks for tab Equipment settings:
All data entered into the fields Link No., Equipment name,
Cabinet No., Equipment No., Equipment type are interpreted as
character strings.
In the field Equipment address a number between 0 and 65000
must be entered. The default value of 0 can be used as long as
just one single link is accessible from HMI600. However, if several
20 log(S-value)
Input level
Relative
Terminal
...
dBm (PEP)
other 0
dBm (RMS) signals
Legend:
System Level of the input signal
is determined by selection of
: Selection inHMI600
Upeak
dBm (PEP ) dBm (RMS) 20 log( )
2 Urms
valid for 600 Ohm.
For each type of signal, an associated system power level expressed
in dBm0 PE is defined as explained in section 5.2.10. System levels
and associated weights are given in Table 5-1 on page 5-8. The
following relation holds between a weight and the associated system
level:
dBm 0 PE 20 log( weight )
The difference between dBm PE levels and dBm0 PE levels is called
relative level and expressed in dBr as explained in section 5.2.8. In the
configuration text generated by the HMI600, the relative level is given
for each configured teleoperation in- and output-port. The sum of the
weightings of all signals to be transmitted by the ETL600, called the S-
value, is also given in the configuration text. Refer to section 5.2.11 for
more information about the S-value.
5.3.3.3. Teleoperation port not used for transit operation
From menu Configuration click Configuration / Teleoperation, ext.
teleprotection
Switch a port on:
1. Select the port you want to configure.
2. If the service(s), which run(s) over the port, can be interrupted
when a teleprotection command is transmitted or received locally:
Click On disconnectable.
In case the service mustnt be interrupted by a teleprotection
command, click On - non disconnectable.
3. Activate Squelch at SNR alarm, if the output of port should be
muted in case of low signal to noise ratio. Typically the squelch
function is activated for modem applications.
The signal to noise ratio is calculated in the pilot channel. The limit
for activating the link alarm and for squelching the AF ports can be
configured in Configuration / System / Alarm settings.
7. Select either the unit dBm (RMS) or dBm (PEP). In the HMI600,
the peak to average ratio for many signal types are stored.
If you are not sure, you should select dBm (RMS).
8. If the input signal consists of a superposition of the reference
signal and other signals, check these signals in the list named
Signals after selected filter considered for input level and
input weight.
L0 dBm0 PE 20 logweight .
10. All signals routed via this port must be selected in the list Signals
after selected filter in the Input sheet. Signals, which are
rejected by the transit filter must not selected. E.g. dont select the
pilot!
11. Select the correct Input level for the signal, which in the
configuration printout appears as 'Reference signal level input'. It is
the output level of the external device. Recommended values are
6.0 dBm or less.
12. Select either the unit dBm (RMS) or dBm (PEP). HMI600 knows
and considers the peak to average ratio for many applications.
If you are not sure of selection, you should select dBm (RMS).
The edge setting has to be adjusted to suit the data terminal, if there
are too many bit errors or any slipping occurs.
ETL600 ETL600
V.11 V.11
TxD
T T
TxD
RxD RxD
R R
TxClk TxClk
RxClk RxClk
S S
Codirectional Codirectional
(default) (default)
Fig. 5-3 V.11 data transmission over one single PLC link
From ETL, Clock slave From ETL, Clock slave From ETL, Clock slave From ETL, Clock slave
(default)
Fig. 5-4 V.11 data transmission transit over two PLC links
activated for port sharing. All shared ports have identical parameter
configuration. By clicking the Port 1 button in the frame V.24, these
parameters can be configured exclusively on port 1 and will be
automatically transferred to the other shared ports.
The following parameter can be configured for each enabled V.24 port
with the respective selection from the concerned drop down list:
Data rate [bps]:
100, 200, 600, 1200, 2400, 4800 and 9600 for NSK600.
The FSK modems with datarates of 200 and 1200 bps are
available in two versions with different bandwidths.
200, 300, 600 14, 1200, 2400, 4800, 9600 and 19200 for
MOD600 modem.
Data bits: 5, 6, 7 or 8.
Stop bits: 1 or 2.
Parity: None, Odd, Even
Protocol:
Character based protocol: this is the configuration for general
asynchronous data communication based on individual
character transmission. This selection allows unrestricted
parameter configuration for the number of data bits, stop bits
and parity mode;
RP570/RP571 / FT1.2: this is the configuration for SCADA
applications using the ABB proprietary protocol RP570/RP571
based on IEC60870-1-5 FT1.2 with 8 data bits, 1 stop bit and
even parity;
Asynchronous DNP 3.0: this is the configuration for SCADA
applications using the proprietary implementation of
asynchronous DNP3.0 based on IEC60870-1-5 FT3 with 8 data
bits, 1 stop bit and no parity.
Three different flow control modes are available:
Hardware-Handshake:
An RTS request from DTE (e.g. RTU) to the V.24 port is
granted CTS when the corresponding transmission channel is
available in transmit direction (multiplexer frame is
synchronized for MOD600 or data carrier is operational for
NSK600). As soon as CTS is granted, dataflow is permitted
14 With HMI600 Version 4.00 or lower: 200, 300, 600 not supported
data (flow control set to Data sensitive). If RTS is active for more
than 100 s (flow control set to Hardware handshake) or the DTE
continuously sends data for more than 100 s (flow control set to
Data sensitive), dataflow to the transmission channel is
interrupted, CTS cleared, Jabber Halt Alarm activated and for
FSK modems the carrier signal switched off. This condition is
restored as soon as RTS turns inactive or the DTE stops sending.
Note: Except for special cases, use jabber timeout only when AF
channel sharing or V.24 port sharing is used.
Data regeneration:
This feature allows regeneration of transparent transmitted data for
data transfer rates lower than 2400 bps (i.e. FSK modems). For
2400, 4800 and 9600 bps (DAPSK modems), data recovery is
automatically done. The following possibilities are available:
On;
Off.
High: DPLC signal has three times the PEP of the APLC
signal;
Proportional: PE voltage is distributed proportionally to the
bandwidth taken by DPLC and APLC signals
(BWDPLC / BWAPLC = PEVDPLC / PEVAPLC)
Interrupt timeout: Low (0.3 s), High (1.5 s)
This parameter defines the time for the modem to perform a restart
when a channel interruption occurs.
Transmission optimized for: Low delay, , High efficiency
A trade-off between highest possible datarate and lowest possible
transmission delay time can be configured.
The configurations of the data rate for the MOD600 modems for the 5
fallback/fall-forward profiles must be done in descending order with the
highest selected data rate on the left and the lowest on the right. The
efficiency curve in the technical data, section Broadband data
(MOD600) can be used to select the lowest and highest data rate
according to the expected lowest and highest SNR.
Example:
The bandwidth of the DPLC channel is 8 kHz and the SNR in 4 kHz is between 21 and
39 dB. The difference between SNR in 4 kHz and in band SNR is
10*log(8 kHz/4 kHz) dB, i.e. 3 dB. Thus, the in band SNR range is 18 to 36 dB. To
ensure reliable operation at these SNR, we specify an SNR margin of 3 dB. From the
efficiency curve, the efficiency is 2 bps/Hz at 18-3=15 dB and 7 bps/Hz at 36-3=33 dB
in band SNR, corresponding to data rates of 8 kHz*2 bps/Hz = 16 kbps at 15 dB and
8 kHz*7 bps/Hz = 56 kbps at 33 dB.
For V.11, data rate selection from 9600 bps to the maximum
datarate allowed for the configured MOD600 bandwidth is possible,
or the port can be turned Off.
For V.24 data rate selection refer to section 5.3.4.8. Here the data
transmission can just be turned On with its configured transmission
rate or turned Off.
The settings for compressed telephony can be made after pressing
the button Compressed telephony. Each telephony channel may
be turned On or Off for each data rate profile.
Note: Pickup times for link and user alarms must be set to
values higher than the configured Max Tx Trip
Monitoring time.
Note: Pickup times for link and user alarms must be set to
values higher than the configured Max Rx Trip
Monitoring time.
alarm threshold of the pilot levels; even if the NSD600 uses the
ETL-pilot as guard signal).
Transportation
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
Electrical Installation
This is a Class equipment as specified in
DANGER IEC 60950-1. The equipment and the cabinet must
be earthed.
The equipment must be supplied over the circuit
breaker for the power supply, type B9AS.
Back cover
Hazardous voltages and/or hazardous energy level
DANGER behind the back cover. Before removing the back
cover, the isolating terminals of the external cables
must be opened or the cables to the terminals must
be disconnected.
Unused slots
Unused slots in the equipment subracks must be
DANGER covered with blanking plates.
External cables
The shields of the external cables V9OD, V9OI,
DANGER V9OS and V9OF must be earthed at both cable
ends using the shield clamps supplied with the
cables.
PCB Extenders
For measuring purposes only the original PCB
DANGER extenders P4LM, P3LL and I9BK, designed to work
with ETL600 equipment, must be used.
ESD protection
B5LC
Make sure that the power supply B5LC is
DANGER programmed to the correct voltage of 230 VAC or
115 VAC as described in 1KHL015788 before
connecting the equipment to the power source.
P4LT/P4LU/P4LV/P4LX
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
R1BC
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
P1LA
Hazardous voltages and/or hazardous energy level
DANGER at the heat sink.
Do not touch during operation.
O4LE, O4CV
The phone interfaces on the modules O4LE and
DANGER O4CV generate dangerous voltages up to 100 V.
Dont use the modules without upper and lower
cover plates. Do not touch the open pins of the
service phone connector, the leads of its cable, the
pins of the external cable connector and the leads of
the external cable.
G4AI
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
Commissioning
6.5. Photographs
The following photographs may be used for reference when
assembling an ETL600 equipment. The installation is shown for an
E40A type cabinet, but other installation schemes are possible.
Fig. 6-1 Front view of the ETL640 equipment equipped with interfaces O4LE
(slots N11 and N22), G4AI (slots N28 and N71)
V9MX RF cable
Optional alarm
module R1BC
Channel rack
P7LC, with rear
cover opened
RF connector (80 W)
Lower power rack P7LA
Fig. 6-6 Side plate of power subrack P7LA with supply connections for ETL640
Fig. 6-7 Side plate of power subracks P7LA with supply connections for ETL680
Fig. 6-8 The plate A9CS for connection of external RF coaxial cable
Fig. 6-12 Krone type terminal block used for data or telephony interfaces
All cables are mechanically secured to the earth plate by plastic cable
binders. Shield clamps are used to galvanically connect the cable
shields to the earth plate.
Fig. 6-13 Earth rail R9AL mounted in the bottom rear of the channel subrack P7LC
All cables are mechanically secured to the earth rail by plastic cable
binders. Shield clamps are used to galvanically connect the cable
shields to the earth rail.
The ETL600 can be equipped with the unit B5LA for 48 VDC supply or
with the unit B5LC for 115/230 V, 50/60 Hz AC supply.
The connections will be accordingly, either to the DC or the AC
terminals:
+ positive battery pole DC supply
- negative battery pole DC supply
L phase conductor of an AC supply
N neutral conductor of an AC supply
PE protective earth conductor
Symbol protective earth conductor
6.6.3. Interfaces
Connections to the various interfaces are made with cables equipped
with connectors or connector blocks that are normally mounted in the
back of the cabinet. The following table lists the interfaces and the
corresponding cables. The length of the cables is 2.5 m except when
otherwise noted. The table also lists the recommended wire sizes for
the connector blocks.
Table 6-1 List of cables with wire sizes for connector blocks
*) Also available without LSA Plus Quick Connector with various lengths to
be used for terminating on main distribution frame.
**) The shields of these cables must be earthed at both cable ends using the
LSA Quick Plus quick connect is manufactured by KRONE. With this
system the connections to the AF interfaces can be made quickly
without soldering. A push-on tool (referred to as a KRONE tool), which
is supplied as an accessory, permits insulation displacement,
connection and cutting of the wire at the same time. For best results, a
solid wire of 0.5 mm diameter with a PVC insulation of 0.2 mm
thickness should be used.
6.6.3.1. AF Interface O4LE
The AF universal interface module O4LE has following main functions:
telephony
teleoperation
external teleprotection equipment
The external connections are divided on two Krone connection strips:
Telephony and Teleoperation.
The cable V9OD consists of 2 cables of 10 pairs each. The new cable
V9OS consists of a single cable with 16 pairs.
6.6.3.1.1. Analog Telephony
The first connection strip is for telephony connections as shown in Fig.
6-14.
The interface programmed for 2 wire subscriber, for point-to-point
operation or remote end subscriber or PAX side subscriber should be
connected to terminals 0a / 0b.
The interface programmed for 2 Wire / 4 Wire, E&M operation should
be connected as follows:
- 2 wire speech to terminals 8a / 8b.
- 4 wire speech Tx to terminals 1a / 1b.
- 4 wire speech Rx to terminals 2a / 2b.
- M wire to terminals 4a / 4b.
It is activated by positive potential provided on terminal 4b, i.e. PAX
should provide a potential free contact.
- E signal to terminals 3a / 3b.
- Transit connection / compandor control to terminals 5a / 4b.
It is activated by positive potential provided on terminal 4b, i.e. PAX
should provide a potential free contact.
- PAX blocking to terminals 6a, 6b and 7a.
These changeover relay contacts indicate bad SNR.
The interface programmed for 4 Wire, E&M operation should be
connected as follows:.
M-WIRE PAX2
Service Phone AF1-IN AF1-OUT E-WIRE M-WIRE LOCAL/ LOCAL/TRANSIT PAX SUBSCRIBER
W
6-18
TRANSIT BLOCKING
ETL6..
K1901
AF INTERF.
O4LE
0V -24V
A B B A B A B - + - NO NC A B A B
X4 3 4 2 X.. a16 c16 a18 c18 a12 c12 c6 c4 a6 c2 a2 a4 a14 c14 a32 c32
ABB Switzerland Ltd
V9OD
RD 8 BN 8 BK 9 BU 9 RD 6 OG 6 GN 3 OG 2 WH 3 BU 1 WH 1 WH 2 RD 7 GN 7 YE 16 BN 16 V9OS
Fig. 6-14
RD 8 GN 8 RD 9 BN 9 RD 6 BU 6 GN 3 OG 2 WH 3 BU 1 WH 1 WH 2 RD 7 OG 7 YE 16 BU 16 V9OSa
X.. (10 pair terminal 1) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b
X..
X.. (16 pair terminal) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b
June 2012
TELEOPERATION
ETL6..
AF INTERF.
O4LE
1KHW001489-EN
0V +24V
A B A B A B A B A B A B - + + -
X.. a20 c20 a22 c22 a24 c24 a26 c26 a28 c28 a30 c30 a8 c8 a10 c10 GND
V9OD
BK 10 OG 10 BK 11 GN 11 BK 12 BN 12 YE 13 BU 13 YE 14 OG 14 YE 15 GN 15 WH 4 BN 4 RD 5 BU 5 V9OS
RD 10 GY 10 BK 11 BU 11 BK 12 OG 12 BK 13 GN 13 BK 14 BN 14 BK 15 GY 15 WH 4 BN 4 WH 5 GY 5 V9OSa
X.. (10 pair terminal 2) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b GND
X..
X.. (16 pair terminal) .9a .9b .10a .10b .11a .11b .12a .12b .13a .13b .14a .14b .15a .15b .16a .16b
EMV
Two terminals of 10 pairs each are used for V9OS and V9OD cables.
ETL600
6-20
AF INTERF.
M-WIRE
O4CV Service Phone 4-WIRE IN 4-WIRE OUT E-WIRE M-WIRE 4-WIRE IN 4-WIRE OUT E-WIRE M-WIRE 4-WIRE IN 4-WIRE OUT
CH1 & 2
Fig. 6-15
0V +24V
USA
EUROPE
ABB Switzerland Ltd
A B B A B A B A B A B A B A B A B A B A B A B
RJ14 3 4 2 X.. a23 a22 c22 c23 c11 c10 c4 c3 a26 a25 c25 c26 a10 a11 c6 c5 a17 a16 c16 c17
V9OI
WH 1 BU 1 WH 2 OG 2 WH 3 GN 3 WH 4 BN 4 WH 5 GY 5 RD 6 BU 6 RD 7 OG 7 RD 8 GN 8 RD 9 BN 9 RD 10 GY 10
X.. (Strips 1) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b
June 2012
ETL6..
SPEECH 4-WIRE CH3 SPEECH 4-WIRE CH4 SPEECH 2-WIRE CH1 CH4 EMV CABLE
SHIELD CONTACT
AF INTERF.
M-WIRE
O4CV E-WIRE M-WIRE 4-WIRE IN 4-WIRE OUT E-WIRE M-WIRE 2-WIRE 1 2-WIRE 2 2-WIRE 3 2-WIRE 4 R9AL
CH3 & 4
1KHW001489-EN
0V +24V
A B A B A B A B A B A B A B A B A B A B
X.. c14 c13 a5 a6 a20 a19 c19 c20 a13 a14 a7 a8 a32 a31 c32 c31 a29 a28 c29 c28 GND
V9OI
BK 11 BU 11 BK 12 OG 12 BK 13 GN 13 BK 14 BN 14 BK 15 GY 15 YE 16 BU 16 YE 17 OG 17 YE 18 GN 18 YE 19 BN 19 YE 20 GY 20
EMV
X.. (Strips 2) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b CABLE GND
SHIELD
Fig. 6-16
0V -24V
USA
EUROPE
A B B A B A B A B A B A B A B A B A B A B A B
V9OI
WH 1 BU 1 WH 2 OG 2 WH 3 GN 3 WH 4 BN 4 WH 5 GY 5 RD 6 BU 6 RD 7 OG 7 RD 8 GN 8 RD 9 BN 9 RD 10 GY 10
X.. (Strips 1) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b
ETL6..
SPEECH 4-WIRE CH3 SPEECH 4-WIRE CH4 SPEECH 2-WIRE CH1 CH4 EMV CABLE
1KHW001489-EN
SHIELD CONTACT
AF INTERF.
M-WIRE
O4CVa E-WIRE M-WIRE 4-WIRE IN 4-WIRE OUT E-WIRE M-WIRE 2-WIRE 1 2-WIRE 2 2-WIRE 3 2-WIRE 4 R9AL
CH3 & 4
June 2012
0V -24V
A B A B A B A B A B A B A B A B A B A B
X.. c14 c13 a5 a6 a20 a19 c19 c20 a13 a14 a7 a8 a32 a31 c32 c31 a29 a28 c29 c28 GND
V9OI
BK 11 BU 11 BK 12 OG 12 BK 13 GN 13 BK 14 BN 14 BK 15 GY 15 YE 16 BU 16 YE 17 OG 17 YE 18 GN 18 YE 19 BN 19 YE 20 GY 20
EMV
X.. (Strips 2) .1a .1b .2a .2b .3a .3b .4a .4b .5a .5b .6a .6b .7a .7b .8a .8b .9a .9b .0a .0b CABLE GND
SHIELD
6-21
ABB Switzerland Ltd
ABB Switzerland Ltd 1KHW001489-EN ETL600
Input 1 Input 2
Terminal 1 (negative potential) Terminal 3 (negative potential)
Terminal 2 (positive potential) Terminal 4 (positive potential)
Input 3 Input 4
Terminal 5 (negative potential) Terminal 7 (negative potential)
Terminal 6 (positive potential) Terminal 8 (positive potential)
Output 1 Output 2
Terminal 9 (negative potential) Terminal 11 (negative potential)
Terminal 10 (positive potential) Terminal 12 (positive potential)
Output 3 Output 4
Terminal 13 (negative potential) Terminal 15 (negative potential)
Terminal 14 (positive potential) Terminal 16 (positive potential)
Relay 1 Relay 2
Terminal 17 (negative potential) Terminal 19 (negative potential)
Terminal 18 (positive potential) Terminal 20 (positive potential)
CONTACT
CONTACT
SHIELD
SHIELD
CABLE
CABLE
Casing
EMV
EMV
GND
1KHW001554R0001
(Patch panel)
V9OY
Fig. 6-21 RS-485 / IRIG-B cable V9OV connected to HMI port (RS 485 ABB
CONTACT
GND
SHIELD
CABLE
EMV
8
8
7
7
5
5
4
4
TX-
2
2
Tx Data
Digital transit, to master port
TX+
1
1
RX-
6
6
Rx Data
RX+
3
3
Dig. transit X..
V9OH
(RJ-45)
(RJ-45)
X..
CONVERTER
TRANSIT IF.)
(DIGITAL
P4LV/X
ETL6..
RF
4 4 4 4 4
4
7. COMMISSIONING
7.1. Safety instructions
Personnel qualification
An authorized and properly trained personnel only is
DANGER admitted to carry out installing, programming,
commissioning, maintenance, troubleshooting and
work of the equipment.
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
Unused slots
Unused slots in the equipment subracks must be
DANGER covered with blanking plates.
Back cover
Hazardous voltages and/or hazardous energy level
DANGER behind the back cover. Before removing the back
cover, the isolating terminals of the external cables
must be opened or the cables to the terminals must
be disconnected.
PCB Extenders
For measuring purposes only the original PCB
DANGER extenders P4LM, P3LL and I9BK designed to work
with ETL600 equipment, must be used.
ESD protection
B5LC
Make sure that the power supply B5LC is
DANGER programmed to the correct voltage of 230 VAC or
115 VAC as described in 1KHL015788 before
connecting the equipment to the power source.
P1LA
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch during operation.
P4LT/P4LU/P4LV/P4LX
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
R1BC
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads
O4LE, O4CV
The phone interfaces on the modules O4LE and
DANGER O4CV generate dangerous voltages up to 100 V.
Dont use the modules without upper and lower
cover plates. Do not touch the open pins of the
service phone connector, the leads of its cable, the
pins of the external cable connector and the leads of
the external cable.
G4AI
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
Z0 Z
Ar 20 log
Z0 Z
Z0 rated impedance
Z actual input impedance
A low value signifies a poor match, which results in a reduced transfer
of power from the PLC transmitter onto the transmission line. The main
disadvantage, however is the intermodulation phenomenon and
associated cross-talk it causes.
The level of return loss should be measured in the equipment room at
the coaxial cable input. The instruments used and the test set-up can
be seen from Fig. 7-1 and Fig. 7-2. A typical return loss characteristic
is shown in Fig. 7-3. In the case of short lines (line attenuation
< 15 dB), the remote end must be terminated at rated impedance.
The measurement of the return loss over the total bandwidth of the
coupling filter and the PLC line traps is recommended. Wherever
possible, the measurements should be carried out twice under the
following conditions:
HV transmission line grounded behind the line trap
HV transmission line open behind the line trap
If the minimum return loss is in the range 6 to 12 dB, the value of the
input impedance should also be measured. In cases where the
magnitude of the system impedance is too low or too high, an
SELECTIVE LEVEL
METER SPM 32/33
Input Dummy load
impedance RN Nominal output
Rec.
appr. 5 kOhm impedance:
e.g. 75 Ohm
Output Gen. RX
impedance Coaxial cable
approx. 10 Ohm to coupling unit
Return loss
GENERATOR PS 33 measuring bridge
Instruments: e.g.:
1. Signal generator Acterna PS 33
2. Selective level meter Acterna SPM 32/33
Fig. 7-1 Instruments and test circuit for measuring return loss
CF CF CF
BT
R e turn R e tu rn
lo s s lo s s
ar ar
Fig. 7-2 Test circuit for measuring return loss under practical
conditions with the transmission line as load
ar
Return loss ar
28 dB
26
24
22
20
18
16
14
12
10
ar
Return loss ar
20 dB
18
16
14
12
10
CF
CF coupling filter
Z0 + Z
Return loss a r = 20 log
Z0 - Z
and
impedance meter Z0 rated impedance
Z actual input impedance
Fig. 7-5 Test circuit using a dummy load for measuring return
loss in the case of single-phase coupling
2ZL
2) 2)
C' k C' k
1) 1)
CF CF
BT
Remarks
1) short connection
2) unscreened insulated lead
1 m above ground
Z0 + Z
ar = 20 log
Z0 - Z
Z0 rated impedance
Z actual input impedance
Return loss
meter CF coupling filter
BT balancing transformer
Fig. 7-6 Test circuit using a dummy load for measuring return
loss in the case of phase-to-phase coupling
grounded behind the line traps. The test circuit is shown in Fig. 7-7
and Fig. 7-8.
Unexpectedly high attenuation or fluctuations of attenuation of several
dB's within just a few kHz would indicate a defective line trap or
extremely unusual characteristics of the line itself. It is essential that
the cause is found and corrected before the PLC equipment is finally
commissioned.
Line attenuation
Phase-to-ground
CF CF
R0
V1 R1
CF coupling filter V0 V0 R1
BT balancing transformer a tot = 20 log
2V1
+ 10 log
( R0 )
Fig. 7-7 Test circuit for measuring line attenuation in the case
of single-phase coupling
CF CF CF CF
BT BT
R0 V1 R1
CF coupling filter V0 V0
a = 20 log
BT balancing transformer 2V1
Fig. 7-8 Test circuit for measuring line attenuation in the case
of phase-to-phase coupling
Warning labels
Precautions and indications to hazardous voltages
DANGER and hazardous energy level must be strictly
observed.
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
Electrical Installation
The isolating terminals of the external cables must
DANGER be kept open during installation, maintenance and
before storage, decommissioning and disposal.
Alteration
Alteration of the equipment is not allowed.
DANGER
Back cover
Hazardous voltages and/or hazardous energy level
DANGER behind the back cover. Before removing the back
cover, the isolating terminals of the external cables
must be opened or the cables to the terminals must
be disconnected.
Unused slots
Unused slots in the equipment subracks must be
DANGER covered with blanking plates.
PCB Extenders
For measuring purposes only the original PCB
DANGER extenders P4LM, P3LL and I9BK, designed to work
with ETL600 equipment, must be used.
ESD protection
B5LC
Make sure that the power supply B5LC is
DANGER programmed to the correct voltage of 230 VAC or
115 VAC as described in 1KHL015788 before
connecting the equipment to the power source.
P1LA
Hazardous voltages and/or hazardous energy level
DANGER at the heat sink.
Do not touch during operation.
P4LT/P4LU/P4LV/P4LX
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
R1BC
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads
O4LE, O4CV
The phone interfaces on the modules O4LE and
DANGER O4CV generate dangerous voltages up to 100 V.
Dont use the modules without upper and lower
cover plates. Do not touch the open pins of the
service phone connector, the leads of its cable, the
pins of the external cable connector and the leads of
the external cable.
G4AI
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
The red LED (SYS, System or Cabinet alarm) at the middle right
side: It operates when either the hardware alarm (HW) or the link
alarm (LNK) operates or when an interface alarm is present.
Refer to chapter 9, section 9.6 'List of alarms and corrective actions'
for details about causes of alarms and remedies.
In case the optional alarm module R1BC is used, the contacts will also
operate for the above criteria if the corresponding high level alarms of
the subsystems were selected by means of the HMI600.
The alarm polling or event recorder functions of the HMI600 can be
used to see the details of the alarms.
8.3. Maintenance
All the modules of ETL600 are subjected to a comprehensive final
functional testing after manufacturing. The complete PLC equipment is
then calibrated and tested as a unit before leaving the works.
Most functions such as generation of pilot, AF filtering, AF to RF
conversion, RF filtering before power amplifier, RF & AF channel
settings etc. are performed digitally by software using DSPs. Hence
these operations are not subject to ageing. The processor includes a
number of self-monitoring functions which - together with the NSD600
loop test performed at periodic intervals - check the operation of the
DSP module and the availability of the communications channel as a
whole.
The parameters governing the operating characteristics are all
determined by the HMI600. The stability of these settings and thus
also of the equipment as a whole is assured over a long period of time.
Nevertheless, testing at periodic intervals is recommended. The
frequency of testing depends very much on the operating conditions in
the particular installation, but should not be less than once every two
years. The following periodic measurements are recommended.
8.3.1. Periodic functional checks
It is important that the reasons for readings, which diverge widely from
values recorded during commissioning, are found, even if this means
checking the entire equipment.
Checking and testing must be carried out by qualified and authorized
personnel only, using suitable instruments. Incorrect settings can
impair the proper operation of the equipment.
8.3.1.1. Check input power supply voltage
Verify that the internal power supply voltage of 48 VDC on the test
point of B5LA/B5LC is within tolerance.
Note: TPE trip signals can be viewed only at the Rx side but
not at the Tx side.
Parameter Explanation
SNR at startup The value SNR at startup is an estimation of the inband signal to
noise ratio in dB taken at start-up/restart time of the modem.
EPSM The EPSM value is an estimation of the inband signal to noise ratio
in dB.
While the SNR value is estimated only at startup/restart of the
modem, the EPSM value is permanently updated during data
transmission.
In contrast to the Delta sigma value, the EPSM value is basically
independent of the selected datarate.
Block error rate The block error rate is the ratio between the number of blocks with
one or more errors and the number of transmitted blocks.
MOD600 transmits the data in blocks, adding a checksum to each
block in the transmitter, enabling the receiver to distinguish
errorless blocks from blocks with one or more errors.
The value is rounded down to the next power of 10, i.e. a value of -
4 means a block error rate between 1E-3 and 1E-4.
The bit error rate is typically 100 to 1000 times smaller than the
block error rate.
The length of a block roughly equals N/B, where N is the
orthogonality interval (explained in section 3.5.2) and B is the
modem bandwidth.
The value is permanently updated during data transmission.
The value is used as a criterion to restart the modem when
fallback/fall-forward is activated.
Maximal data The maximum possible data rate, measured at start-up/restart time
rate of the modem. This value is independent of the configured
MOD600 data rates.
Current data The current data rate is the selected data rate of the modem, which
rate must be equal to or lower than the maximal data rate. Unless the
communication is interrupted, the value is equal to the configured
data rate or in case fallback/fall-forward is activated to one of
the 5 configured data rates.
Delta sigma Delta sigma is a positive number indicating the quality of the
received modem signal. The higher the value, the better the quality
and the smaller the bit error rate.
A value > 10 means good quality.
The value increases when the data rate is lowered.
The value is permanently updated during data transmission.
The value is used as a criterion to restart the modem when
fallback/fall-forward is activated.
Synchronization The synchronisation state of the modem is a number between 0
state and 15.
A value of 0 means that data transmission is currently interrupted.
A value of 15 means that data transmission is ongoing.
During startup/restart, the modem state runs through all numbers
between 0 and 15 in ascending order.
If the loop test fails in at least two consecutive attempts, the equipment
must be taken out of service and tested according to b) below.
9. TROUBLESHOOTING
In case of failure of communications between the two stations of the
PLC link, the fault could either be caused by the power line itself,
either or both of the PLC equipment or the coupling arrangement. A
systematic approach helps in tracking the fault in the shortest possible
time.
9.1. Safety instructions
Personnel qualification
An authorized and properly trained personnel only is
DANGER admitted to carry out installing, programming,
commissioning, maintenance, troubleshooting and
work of the equipment.
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
Alteration
Alteration of the equipment is not allowed.
DANGER
Back cover
Hazardous voltages and/or hazardous energy level
DANGER behind the back cover. Before removing the back
cover, the isolating terminals of the external cables
must be opened or the cables to the terminals must
be disconnected.
Unused slots
Unused slots in the equipment subracks must be
DANGER covered with blanking plates.
PCB Extenders
For measuring purposes only the original PCB
DANGER extenders P4LM, P3LL and I9BK designed to work
with ETL600 equipment, must be used.
ESD protection
B5LC
Make sure that the power supply B5LC is
DANGER programmed to the correct voltage of 230 VAC or
115 VAC as described in 1KHL015788 before
connecting the equipment to the power source.
P1LA
Hazardous voltages and/or hazardous energy level
DANGER at the heat sink.
Do not touch during operation.
P4LT/P4LU/P4LV/P4LX
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
R1BC
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads
O4LE, O4CV
The phone interfaces on the modules O4LE and
DANGER O4CV generate dangerous voltages up to 100 V.
Dont use the modules without upper and lower
cover plates. Do not touch the open pins of the
service phone connector, the leads of its cable, the
pins of the external cable connector and the leads of
the external cable.
G4AI
Hazardous voltages and/or hazardous energy level
DANGER on the module and the cable.
Do not touch the module and the cable leads.
9.2. Fuses
Module Type of Fuse
B5LA T 6.3 A/250 V
B5LC (115 VAC) T 4 A/250 V
B5LC (230 VAC) T 2 A/250 V
B4LE T 6.3 A/250 V
9.3. Alarms
The alarm concept of the ETL600 system is designed to
detect and locate the sources responsible for abnormal operation
of the system,
provide information about the kind of problems detected.
Fig. 9-1 shows the six major fault locations of a PLC link. By combining
the alarm information of both terminals of the link, it is possible to
locate the source of a problem (Table 9-2).
Equipment A Equipment B
RF channel A to B
Equipment Equipment
connected to ETL600 ETL600 connected to
A RF channel B to A B
Fig. 9-1 The six major fault location areas of a PLC link
Equipment A Equipment B
Hardware
Hardware
Interface
Interface
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Link
Link
Error caused by:
- - - - - - -
- - - - - Channel B to A
- - - - - Channel A to B
- - - - - Equipment connected to A
- - - - - Equipment connected to B
x x - - x Equipment A
- - x x x Equipment B
Remote
Alarms, Warnings from ETL600 Alarms, Warnings to
remote terminal (via EOC) terminal remote terminal (via EOC)
High-level
alarms
LEDs
Voltages,
Hardware Currents High-level Relay contacts on
components alarms
Alarm P4LT/U/V/X,
processing R1BC, G4AI, O4LE
Low-level
alarms Polled alarm
Alarms, messages
Software Warnings
processes Low-level +
Detail alarms Alarm display in
system status
Low-level
alarms
9.3.2. Warnings
Warnings are used to signal that an equipment is not in normal
operation state, but otherwise working properly. Examples:
Measurement of frequency response
Tuning of RF filters
Equipment running with temporary configuration
Dummy load plugged
Warnings are collected and reported via the same mechanisms as
alarms.
Warning LEDs are provided on the front panels of P4LT/U/V/X, O4LE,
O4CV and G4AI. Their color is yellow.
9.3.3. Grouping of alarms
Alarms and warnings can be grouped acc. to several criteria (Fig. 9-3):
Service: PLC, TPE1, TPE2, DATA
Hardware: Circuit boards of the ETL600 terminal
Alarm source: Hardware, Link, Interface
In Fig. 9-3,
alarm groups are indicated with frames,
Link alarms: Pickup and hold times for link alarms can be
entered via HMI600.
Warnings: A pickup time of 10 s and a hold time of 1 s
are used for warnings.
Low-level alarms
1
Pick up time Hold time
High-level alarm
Question: The PLC link doesn't work. What can I do to correct this
problem?
Answer: Check the alarms: If there is a hardware alarm at either side
of the link, the reason of it must be found and the problem corrected.
Upload the equipment status and study the alarm messages given by
the HMI600. One single problem can produce a number of such
messages.
If for both equipments of the link no hardware alarms are reported
(anymore), the problem has to be sought in the link. Upload the
equipment status and study the alarm messages given by the HMI600.
It is helpful if it is possible to restrict the problem to one of the following
3 cases:
1. Excessive signal attenuation,
2. Excessive line noise,
3. Excessive distortion.
Case 1: Check the RF settings (Configuration / System / Channel
settings) and the hardware on the RF-side. Check the tuning of the
RF transmit and receive filters and the adjustment of the Rx RF level
9.6.2. Data
9.6.2.1. Data hardware alarms
HMI600 Alarm Text Explanation and corrective actions
(the latter in italics)
NSK600 DSP The NSK600 DSP / MOD600 DSP on P4LT/U/V/X stopped
stopped working working for more than 1 s longer than the configured
pickup time for hardware alarms, followed by an automatic
MOD600 DSP
reset of the system. The reason can be faulty P4LT/U/V/X
stopped working
hardware or excessive EMI, possibly in combination with
poor substation grounding and/or not properly grounded
cable shields.
Connect the shields of cables to ETL600 to ground as
described in chapter 6. Improve the grounding of ETL600,
specially the connections between the buried earth grid
and substation ground, substation ground and cabinet,
cabinet and (swing) frame, (swing) frame and equipment
rack.
If external EMI effects can be excluded and the error
message appears repeatedly, replace P4LT/U/V/X.
NSK600 DSP A memory error has been detected in the memory of the
program memory NSK600 DSP / MOD600 DSP on P4LT/U/V/X. The reason
CRC error can be faulty P4LT/U/V/X hardware or excessive EMI,
possibly in combination with poor substation grounding
MOD600 DSP
and/or not properly grounded cable shields.
program memory
CRC error Connect the shields of cables to ETL600 to ground as
described in chapter 6. Improve the grounding of ETL600,
specially the connections between the buried earth grid
and substation ground, substation ground and cabinet,
cabinet and (swing) frame, (swing) frame and equipment
rack.
If external EMI effects can be excluded and the error
message appears repeatedly, replace P4LT/U/V/X.
FPGA not The FPGA on P4LT/U/V/X is not operational.
operational Reset the system. If the error persists, replace
P4LT/U/V/X.
Piggyback on The Piggyback board on P4LU/V/X is required but cant be
P4LU/V/X missing detected.
Make sure that the piggyback board is present and
correctly mounted on P4LU/V/X. If the error persists,
replace P4LU/V/X.
N.a.
9.6.3. TPE
The alarm and warning messages in the following tables are shown for
one TPE. An identical set of messages is implemented for each TPE.
9.6.3.1. TPE hardware alarms
HMI600 Alarm Text Explanation and corrective actions
(the latter in italics)
DSP stopped The TPE DSP on P4LT/U/V/X stopped working for more
working than 2 s longer than the configured pickup time for
hardware alarms, followed by an automatic reset of the
system. The reason can be faulty P4LT/U/V/X hardware or
excessive EMI, possibly in combination with poor
substation grounding and/or not properly grounded cable
shields.
Connect the shields of cables to ETL600 to ground as
described in chapter 6. Improve the grounding of ETL600,
specially the connections between the buried earth grid
and substation ground, substation ground and cabinet,
cabinet and (swing) frame, (swing) frame and equipment
rack.
If external EMI effects can be excluded and the error
message appears repeatedly, replace P4LT/U/V/X.
DSP program A memory error has been detected in the memory of the
memory CRC error TPE DSP on P4LT/U/V/X. The reason can be faulty
P4LT/U/V/X hardware or excessive EMI, possibly in
combination with poor substation grounding and/or not
properly grounded cable shields.
Connect the shields of cables to ETL600 to ground as
described in chapter 6. Improve the grounding of ETL600,
specially the connections between the buried earth grid
and substation ground, substation ground and cabinet,
cabinet and (swing) frame, (swing) frame and equipment
rack.
If external EMI effects can be excluded and the error
message appears repeatedly, replace P4LT/U/V/X.
G4AI board missing At least one configured G4AI board doesnt answer or is
not plugged at the correct position in the rack.
Verify if all boards are firmly plugged in at the correct
positions in the P7LC subrack according to HMI600 (View
/ Display configuration). Switch off the power to ETL600
and switch it on again after some seconds. If the error
persists, find the faulty G4AI board(s) by studying the TDM
bus communication alarms (section 9.6.4). Replace the
faulty G4AI board(s).
9.9. Support
Mechanical Installation
The equipment must be mounted in a cabinet.
DANGER
ESD protection
Electrical Installation
The circuit breaker for the power supply (B9AS) of
DANGER the equipment must be switch OFF.
The circuit breakers for optional equipment in the
cabinet must be switch OFF.
10.2. Storage
The specified conditions for storage are stated in the Technical Data
ETL600.
The cabinet should be stored in its original wooden frame and plastic
cover. Make sure that the plastic cover is undamaged. Where the
equipment has to be stored for a long period, precautions to prevent
corrosion must be taken. This is especially important in humid
climates.
Storage of modules should be preferably in the original packing or in
antistatic bags with additional mechanical protection.
10.3. Decommissioning
The decommissioning of the equipment should be done in the
following steps.
First of all the application, in which the equipment is used, must be
disabled. This is of special importance when protection signaling is
used.
Switch OFF the equipment. Isolate and disconnect the external
power supply given to the equipment.
Open the isolating terminals from the external cables.
Disconnect the external wiring of the equipment. This should be
done carefully using the plant drawings so that some other wiring
does not get disconnected by mistake.
Disconnect the RF coaxial cable. In case the cabinet is to be
dismounted, unstrap the RF cable and remove it from the cabinet.
In case the complete cabinet is to be dismounted, the bolts for
fastening the cabinet to the base frame or floor must be carefully
removed giving support to the cabinet at the same time. The
cabinet can now be lifted and dismounted. It is preferable to keep
the cabinet in horizontal position if no external support can be
given to the cabinet in vertical position.
In case only the ETL600 subrack is to be removed from the
cabinet, first disconnect the internal wiring and power supply
between the ETL600 subrack and the terminal blocks. Now
dismount the subrack by unscrewing the screws from the front.
If the ETL600 subrack or its modules are to be reused, they should
be handled and packed properly following precautions for ESD
protection.
10.4. Disposal
For disposal, the regional and national regulations for electrical and
electronic waste have to be observed.
The modularity of the equipment allows to separate component boards
and casing, thus giving the opportunity for recycling.
11. OPTIONS
11.1. Basic equipment
The basic ETL600 equipment with a minimal set of interfaces consists
of the following racks and modules:
Remark:
1) Twice for ETL680
11.2. Optional equipment
11.2.1. Optional modules
11.2.1.1. AF interface type O4LE
This is the interface for telephony (2 and 4 wire), for teleoperation and
for external teleprotection.
11.2.1.2. Teleprotection interface type G4AI
This is the interface module for the optional internal teleprotection
equipment type NSD600.
11.2.1.3. Compressed telephony interface type O4CV
This is the interface module for digitally compressed telephony.
11.2.1.4. LAN interface module R1LA
This piggyback module to the DSP module P4LU offers a LAN port.
For information how to install R1LA onto an existing P4LU module,
consult document 1KHW001757 Upgrade Options for P4LT and
P4LU in the annex.
Module / Application
Cable(s)
O4LE / The cable is required for external wiring of the
V9OD, teleoperation inputs & outputs.
V9OS The cable is also used for transit operation or to
connect the NSD570 / NSD70C protection equipment.
Module / Application
Cable(s)
V9OV This cable is required for connection of external devices
to the HMI port (when used as RS-485 station bus port)
and to the IRIG-B port on the front plate.
V9OX This cable is required for transit connection of V.11
ports.
V9OY This patch panel for a Sub-D 9 pole male connector can
be used for IRIG-B or RS-485 signals.
V9OZ This patch panel can be used for LAN, G.703.1 and
digital transit ports.
P7LA In addition to the AC/DC power supply cable, the RF
coaxial cable is also required.
For 80 W operation, a jumper cable is required between
the upper and lower P7LA.
P7LC A flat cable is required for connection between P7LA
and P7LC. Also a small power supply cable is required
for extension of DC supply from P7LA to P7LC.
Contents
Contents
1 Purpose of document...................................................................................... 1
2 Safety instructions .......................................................................................... 1
3 Changing from 230 VAC to 115 VAC ............................................................. 2
4 Changing from 115 VAC to 230 VAC ............................................................. 2
1 Purpose of document
This document describes how to change the input voltage of the AC power supply type B5LC from
230 VAC to 115 VAC or vice versa.
2 Safety instructions
Caution Follow the instruction below carefully and do not modify anything.
Caution Wrong programming can damage the module and the equipment.
Check if programmed input voltage of the module is equal to the mains
voltage.
Verify the programming information on the right side of the module.
Caution Operate the module only in the condition specified by the manufacturer.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Revision: Language: Page:
A EN 2/2 1KHL015788-EN
Contents
1 Purpose of document 2
2 General 2
3 Upgrade procedure for a nominal carrier frequency bandwidth BN of 8 kHz or 4 kHz 2
3.1 General description 2
3.2 Hardware required for upgrading 2
3.3 Procedure 3
4 Upgrade procedure for a nominal carrier frequency bandwidth BN greater than 8 kHz 4
4.1 General description 4
4.2 Hardware required for upgrading 4
4.3 Procedure 4
5 Manual Firmware upgrade using MMI500 5
List of equipment:
PC with Windows 2000 or XP
MMI500 software
HMI600 software
ETL600 firmware download files
PC P4LT/P4LU cable (1:1 serial RS-232)
Operational ETL500 terminal
Replacement board for P4LQ: P4LT or P4LU
Optional E5TX, P4RX, P3LE for bandwidth > 8 kHz
Optional P3LG and second E5TX for 80 W and bandwidth > 8 kHz
Set of additional connecting cables, if required
Note:
Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Revision: Language: Page:
B EN 2/5 1KHW001508-EN
1 Purpose of document
This document describes the upgrade process from the equipment ETL500 Rel.3 to ETL600.
2 General
The new ETL600 boards are designed in a way that they could be inserted in an operational
ETL500 Rel.3 system in order to upgrade the ETL500 into an ETL600 by replacing a minimal
amount of cards.
For ETL500 to ETL600 upgrade system with a nominal carrier frequency bandwidth BN of 8 kHz or
4 kHz, the central processor card P4LQ has to be replaced either by a P4LT or a P4LU. The
existing Tx-filter, Rx-filter and RF-hybrid may be reused. This is also valid for the 80 W option.
For ETL500 to ETL600 upgrade system with a nominal carrier frequency bandwidth BN of more
than 8 kHz, the central processor card P4LQ has to be replaced either by a P4LT or a P4LU.
Additionally the Tx filter E5LA/E5LB has to be replaced by E5TX, the Rx filter P4LR by P4RX, the
RF-hybrid P3LB/P3DA by P3LE.
If an ETL580 (80 W) is upgraded to an ETL600 with a nominal carrier frequency bandwidth BN of
more than 8 kHz, the second Tx filter E5LA/E5LB has to be replaced by E5TX and the combiner
P3LC/P3LD by P3LG.
NSK5 modules in the ETL600 rack are no longer supported and have to be removed. The NSK600
modems integrated on P4LT/P4LU may be used instead.
ESD protection
Caution The modules in this equipment contain devices, which can be damaged by
ESD electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on modules
are grounding straps for technical personnel and the provision of anti-static
workbenches. Modules may only be shipped either in their original packing
or installed in equipment racks.
3.3 Procedure
1. Check the tuning according to Appendix in ETL500 manual: "Tuning Instructions for RxRF
Filter P4LR" (1KHL015117-EN), "Tuning Instructions for TxRF Filter E5LA/E5LB"
(1KHL015570-EN) and "Tune RF hybrid P3LB, if present" according to "Programming and
Testing Instructions ETL500" (1KHL015940-EN). Adjust if necessary.
2. Produce a config file *.mmi for the existing ETL500 by means of the MMI500. A hardcopy on a
printer might be helpful.
3. If G4AI (teleprotection) is used: make a firmware upgrade of all G4AI by means of MMI500
version 3.20 or higher.
See instructions in paragraph 5. Manual Firmware upgrade using MMI500.
4. If O4LE is used: make a firmware upgrade of all O4LE by means of MMI500 version 3.20 or
higher.
See instructions in paragraph 5. Manual Firmware upgrade using MMI500.
5. Start the HMI600 and enter offline the configuration of ETL600 (re-enter data manually from
step 2 as far as applicable).
Note: If as receive filter P4LR instead of P4RX is used, please select P4RX in
HMI600, Configure system / Equipment settings.
Note: The 5R and the 3R blanking plates on the left and right side of P4LQ must
be removed. They are no longer used, as the front plate P4LT/P4LU is 14R
wide.
7. Remove all G4AI and O4LE and re-insert them at the corresponding slot positions of ETL600
as given by the HMI600 (see also ETL600 manual).
8. For all O4LE cables: Change the wiring according to the new port assignment of the
teleoperation ports.
9. Remove all NSK5 modules, if any. They have to be replaced by 6R blanking plates. Change
the wiring to the P4LT/P4LU according to the configuration shown in the HMI600.
10. Download the ETL600 configuration onto the ETL600 by means of the HMI600.
11. Tune and test according to ETL600 Tuning and Testing instructions as per ETL600 manual,
except Tx- and Rx filters. Especially the Adjust Tx RF level, Adjust Tx Alarm level and
Adjust Rx RF level procedures have to be performed.
Note: "Tuning Instructions for ETL600 Rx RF filter P4RX", "Tuning Instructions for
ETL600 Tx RF filter E5TX" and "Settings for ETL600 RF hybrid P3LE / Tune RF
hybrid P3LE" are not applicable if the ETL500 Tx filter E5LA/E5LB, Rx filter P4LR
and hybrid P3LB are re-used. The tuning was already done in step 1.
Revision: Language: Page:
B EN 4/5 1KHW001508-EN
Note: For adjusting the Tx RF level: measure the test tone level at the RF line socket
(X175) via an attenuator with impedance according to the ETL system impedance
(75 of 125 Ohm) and a level meter set to the same input impedance (the
attenuator is required to prevent overdriving of the level meter). The RF line
monitor socket on the front plate of the hybrid P3LB has not the same impedance
and level as the RF line monitor socket of the hybrid P4LE.
Note: When performing Adjust Rx RF level with HMI600 tuning and testing, check the
box Rx Filter P4RX plugged if the receive filter P4LR is used. Remove P4LR
when P4RX is required to be removed during the adjustment. Do the adjustment
at the potentiometer Rx Level on P3LB instead of P3LE as described by
HMI600.
12. If necessary, perform a firmware update to the latest ETL600 release according to
1KHW001496: Firmware Download for ETL600.
4.3 Procedure
1. Produce a config file *.mmi for the existing ETL500 by means of the MMI500.
2. If G4AI (teleprotection) is used: make a firmware upgrade of all G4AI by means of MMI500,
version 3.20 or higher.
See instructions in paragraph 5. Manual Firmware upgrade using MMI500.
3. If O4LE is used: make a firmware upgrade of all O4LE by means of MMI500, version 3.20 or
higher.
See instructions in paragraph 5. Manual Firmware upgrade using MMI500.
4. Start the HMI600 and enter offline the configuration of ETL600 (re-enter data manually from
step 1 as far as applicable).
5. Replace P4LQ by P4LT or P4LU.
Replace existing RF set by new E5TX, P4RX, P3LE, and for 80 W only: P3LG.
6. Remove all G4AI and O4LE and re-insert them at the corresponding slot positions of ETL600
as given by the HMI600 (see also ETL600 manual).
7. For all O4LE cables: change the wiring according to the new port assignment of the
teleoperation ports.
8. Download the ETL600 configuration onto the ETL600 by means of the HMI600.
9. Tune and test according to ETL600 Tuning and Testing Instructions, refer to ETL600 manual.
10. If necessary, perform a firmware update to the latest ETL600 release according to
1KHW001496: Firmware Download for ETL600.
Revision: Language: Page:
B EN 5/5 1KHW001508-EN
Note: The firmware upgrade of the existing modules G4AI and O4LE may also be
effected with the HMI600 according to document 1KHW001496-EN
Firmware Download for ETL600 in the annex of the ETL600 manual.
ABB Switzerland Ltd 1KHW001757-EN
Archive No.: Rev. Date:
Upgrade Options for P4LT and P4LU - _
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PSND 2006-11-15 M. Dick 2007-02-14 Ch.Leeb - EN 1/5
Valid for: Derived from: Replaces: Classification-No.: File:
- - - 1KHW001757_e Upgrade Options
for P4LT and P4LU.doc
Contents
1 Purpose of document 2
2 Safety instructions 2
3 Upgrade P4LU with R1LA 2
List of equipment:
PC with Windows 2000 or XP
HMI600 software
PC P4LT/P4LU cable 1:1 serial RS-232
Torx screwdriver Size: 8
Note:
Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. ABB Switzerland Ltd
Revision: Language: Page:
_ EN 2/5 1KHW001757-EN
1 Purpose of document
This document describes mounting of upgrade options for P4LT and P4LU.
2 Safety instructions
ESD protection
Caution The modules in this equipment contain devices, which can be damaged
ESD by electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on
modules are grounding straps for technical personnel and the provision of
anti-static workbenches. Modules may only be shipped either in their
original packing or installed in equipment racks.
Note: For new projects and systems the module P4LU with R1LA has to be
ordered if LAN600 functions are required, i.e. R1LA is already assembled
on P4LU ex works.
In the exceptional case when a P4LU shall be upgraded with R1LA (using
the optional R1LA upgrade kit), the following - rather unusual - procedure
may be applied to avoid completely disassembling of the module P4LU.
Note: The module R1LA is only compatible with P4LUa, not with P4LU and
P4LT/P4LTa.
Max
25mm!
Contents
1 Purpose of document 2
2 General 2
3 Release and Version Management 2
4 Compatibility rules 2
4.1 Compatibility between Rel. 3 and Rel. 4 3
5 ETL600 Releases 3
6 Release notes 9
6.1 Release 1.0.2 9
6.2 Release 1.0.3 9
6.3 Release 1.0.4 9
6.4 Release 2.0.0 9
6.5 Release 2.1.0 9
6.6 Release 2.1.1 9
6.7 Release 2.2.0 10
6.8 Release 3.0.0 10
6.9 Release 3.1.0 10
6.10 Release 3.2.0 10
6.11 Release 3.2.1 10
6.12 Release 3.2.2 10
6.13 Release 3.2.3 11
6.14 Release 3.4.0 11
6.15 Release 3.4.1 11
6.16 Release 3.4.2 11
6.17 Release 3.4.3 11
6.18 Release 3.5.0 11
6.19 Release 4.0.0 12
6.20 Release 4.0.1 12
6.21 Release 4.1.0 12
6.22 Release 4.1.1 12
6.23 Release 4.1.2 12
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2014 ABB
Revision: Language: Page:
R EN 2/12 1KHW01490-EN
1 Purpose of document
This document describes the compatibility requirements for the ETL600 system.
2 General
The ETL600 system consists of
1. Hardware, consisting of a number of modules;
2. Firmware, residing on some of the modules and making the processors on these modules execute
various functions such as modulation, digital filtering etc.;
3. PC based software, implementing the user interface for configuration, testing and monitoring of the
equipment.
Note: The information content of type codes in case of modules containing firmware
depends on the possibility to download firmware from HMI600 into the module:
If for a component firmware download is not possible, the type code of that
component identifies the hardware including the firmware version.
Example: Microcontroller on P4LT/U/V/X
If for a module firmware download is possible, the type code of that module
identifies the hardware excluding the firmware version. The download files
for the firmware of such modules are included on the HMI600 Software &
Documentation CD.
Example: O4LE
4 Compatibility rules
Rule Nr. 1:
The modules of an ETL600 terminal and the firmware on these modules must belong to the same
release as given by Table 1.
If an equipment contains modules of different releases, it will generally not work correctly.
Rule Nr. 2:
Apart from the exceptions described in section 4.1, the two ETL600 terminals of a link must belong to
the same release.
If this rule is violated, the EOC of the link will generally not work correctly. Corresponding warning
messages will be generated by HMI600.
Rule Nr. 3:
The HMI600 software must have full or restricted compatibility to the ETL600 terminals being
connected to.
The term "restricted compatibility" is used when the functionality has been changed between releases
as long as the HMI600 program can handle these changes in a reasonable way.
Revision: Language: Page:
R EN 3/12 1KHW01490-EN
5 ETL600 Releases
1)
Notes:
The module R1LA is only compatible with P4LUa, not with P4LU and P4LT/P4LTa.
1)
Notes:
ETL600 Releases 3.0.0 and higher do no longer support the hardware modules P4LT
and P4LU. Modules of type P4LTa or P4LUa are required.
2)
The module R1LA is only compatible with P4LUa, not with P4LTa.
3)
R9AL is an integrated part of channel subrack P7LC since mid of 2010.
1)
Notes:
ETL600 Releases 3.0.0 and higher do no longer support the hardware modules P4LT
and P4LU. Modules of type P4LTa or P4LUa are required.
2)
The module R1LA is only compatible with P4LUa, not with P4LTa.
3)
R9AL is an integrated part of channel subrack P7LC since mid of 2010.
Notes:
For the latest HMI600 and firmware versions, please refer to the latest
ETL600 Rel. 4.
1)
Firmware ETL600 versions 4.00 and higher do no longer support the hardware
modules P4LTa and P4LUa. Modules of type P4LTb, P4LV or P4LX are required.
2)
The module R1LB is an integrated part of P4LV and P4LX.
3)
R9AL is an integrated part of channel subrack P7LC since mid of 2010.
Revision: Language: Page:
R EN 8/12 1KHW01490-EN
1)
Notes:
Firmware ETL600 versions 4.00 and higher do no longer support the hardware
modules P4LTa and P4LUa. Modules of type P4LTb, P4LV or P4LX are required.
2)
The module R1LB is an integrated part of P4LV and P4LX
Table 1
Revision: Language: Page:
R EN 9/12 1KHW01490-EN
6 Release notes
Compared to the RF-Converter module P4LUa, the modules P4LV and P4LX provide the following
features:
Four port Ethernet/IP switch/router (R1LB).
Digital transit for compressed voice.
If the above features are required, existing ETL600 Release 3 equipment can be upgraded with
P4LV or P4LX to Release 3.5.0, allowing a link to be composed of ETL600 Release 3 and ETL600
Release 4 equipment.
Contents
1 General ........................................................................................................... 2
2 Programming .................................................................................................. 2
2.1 Steps for determining the required jumper positions............................ 2
3 Tuning the filter circuits individually ................................................................ 3
3.1 Steps for tuning the coils L1 and L2 ..................................................... 3
4 Checking the gain and frequency response of the filter ................................. 4
4.1 Steps to check the gain setting ............................................................ 4
4.2 Steps to check the frequency response ............................................... 5
5 Test circuits..................................................................................................... 6
Test conditions:
Temperature range: 10 C to 40 C.
Notes:
Level measurements during tuning & checking frequency response of P4RX are relative. Hence any ordinary
wide band or selective level meter with a frequency range 10 kHz to 1000 kHz can be used. Normally a wide
band level meter will be sensitive enough. If more sensitivity is required, use a selective one. Be careful when
using a wide band meter, as unwanted signals may disturb the measurement.
The same Rx tuning adapter P4LM used for ETL 41 and ETL500 can be used for ETL600. However, if two
shorting wires are present on the P4LM, they must be removed. The position of these 2 shorting wires - if
present - will be across C1-C9 & C2-C10, under the sub-board.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. ABB
Revision: Language: Page:
D EN 2/7 1KHW001491-EN
1 General
In the ETL600 the Rx filter P4RX is tuned using the Rx tuning adapter P4LM, the Tx tuning adapter P3LL
and the HMI600. However before starting tuning, the filter programming jumpers must be set in
accordance with the programming tables, shown in the HMI600. Using HMI600, the P4LT generates the
test frequencies required for tuning P4RX.
2 Programming
The filter must be programmed with jumpers. With the jumpers, the mode of the coils (series or parallel
connection), the required capacitors and the required filter termination resistors are selected. Also the
amplifier gain is set by jumpers.
The required jumper settings for the P4RX board are generated by the HMI600 program, according to the
chosen center frequency and nominal bandwidth. To set the jumpers, the top shielding cover of the P4RX
board must be removed.
To remove the top shielding cover from the P4RX board: loosen the two mounting screws and carefully
pull-off the top cover. A screwdriver may be inserted in the slot adjacent to the screw to help lifting the
cover.
) 5.
Note: Once the filter has been selected, in order not to loose the filter settings, the
checkbox Auto-select standard filter must not be activated anymore.
Check if the correct filter center frequency f0 and bandwidth is shown. If these values shall be
modified, select them from the drop down lists.
6. Place the jumpers according to the table shown in the HMI: 0 means no jumper, 1 means jumper
placed.
7. Click Ok to add the filter settings to the equipment configuration, to discard them click Cancel.
The jumpers are stored in a plastic (anti static) bag fixed to the PCB. Put the jumpers on the indicated
positions, with the open side of the jumpers on top. Carefully check the jumper positions with the
HMI600 table, as wrong positioned jumpers may cause problems in tuning the filter. A wrong
positioned jumper may not always be detected by the filter verification check!
Put the remaining (spare) jumpers back into the plastic bag for future use. Put the top cover back into its
place and fasten the screws. Now the filter is ready for tuning.
Revision: Language: Page:
D EN 3/7 1KHW001491-EN
The tuning adapter P4LM supports also older 3-stage filters. But as the filter has 2 stages, the L2 jumper
setting on the P4LM tuning adapter is not used. Use the L3 setting on the P4LM to tune the L2 coil on
the P4RX filter!
) Note: The adjuster screws in the coils L1 and L2 must be handled very carefully.
Never turn these screws beyond their stop position! The screws have
plastic M2 threads, which may be damaged easily! Only very little force is
needed to break the screws at the lower end of the adjustment range when
turning-in the screws.
To remove a damaged screw, first remove the top and bottom shield covers.
With a small screwdriver (1.5 mm), try to turn the remaining part of the adjuster
screw out of the coil (from the bottom side). Replace the adjuster screw with a
new one of the same type, and reassemble the shield covers before tuning.
2.
) Note: The RF hybrid must not be plugged on top of P3LL.
11. Using a plastic screwdriver, slowly turn the adjuster screw of coil L1, until the voltage at the level
meter is minimized.
The coil L1 is tuned now.
12. Select coil L2 by setting jumper S3 on P4LM to position L3(!) and repeat the procedure by clicking
Activate f2 to tune coil L2 of P4RX. Note that jumper position L2 of S3 is not used for P4RX.
13. Click Deactivate frequency.
14. Click Cancel.
The filter is tuned now.
The P4RX board may be checked when plugged in the rack, e.g. without the Rx tuning adapter P4LM. This
way the influence of the tuning adapter on the filter is eliminated. Only the Tx tuning adapter P3LL is
required to deliver the required test signals. The RF hybrid must not be plugged onto the Tx tuning
adapter, so that the input of P4RX is disconnected from the system.
For these tests the mini coax (SSMB) connectors on the P4RX front panel are used. The upper connector,
labelled RX RF-IN is now used as a test input. The lower one, labeled RX RF-OUT is connected to the
level meter (50 Ohm input). Refer to chapter 5 Test circuits, Figure 2.
For these tests the level meter should preferably have an input impedance of 50 Ohm, but a 75 Ohm type
may also be used. Correction factors for this case are given below. As the test signal from P3LL is now
terminated with 50 Ohm, its level is quite low. In case a wide band level meter is not sensitive enough, use
a more sensitive selective level, but in general a wide band level meter will be adequate.
A level meter like the SPM-33 can also be set to high impedance input (e.g. approx. 6 kOhm). Now a
50 Ohm BNC feed-through termination directly on the level meter input converts it into a 50 Ohm
instrument. Set scale units to dB.
3.
) Note: The RF hybrid must not be plugged on top of P3LL.
The P3LL tuning adapter is set as follows during the entire process:
FUNCTION A
Position of S1 L2
Position of S2 FILTER
Position of S3 Don't care
Position of LOAD Don't care
4. Connect the BNC connector OUT of P3LL to the 50 Ohm (or 75 Ohm) input of the level meter.
Because the P3LL output is a high impedance source, the signal level at 50 Ohm will be quite small.
But mostly a wide band level meter still will be sensitive enough. If not, use a more sensitive selective
level meter to get reliable measurements.
5. In the Tuning Rx RF filter dialog box, click Check Rx RF filter to get the dialog box Check filter.
Click Activate f0. Read the level in dB.
If a 50 Ohm instrument is used, designate this measured level as A.
If a 75 Ohm instrument is used, subtract 2.61 dB from the measured level (the P3LL output is a
high impedance source). Designate this result as A.
Revision: Language: Page:
D EN 5/7 1KHW001491-EN
6. Connect the BNC connector OUT of P3LL with the RX RF-IN (50 Ohm input) SSMB connector on the
P4RX board.
7. Connect the level meter 50 Ohm (or 75 Ohm) to the RX RF-OUT (50 Ohm output) SSMB connector of
the P4RX board. Read the indicated level in dB.
If a 50 Ohm instrument is used, designate this measured level as B.
If a 75 Ohm instrument is used, subtract 1.58 dB from the measured level.
Designate this result as B.
8. (B-A) is the gain of the P4RX board. Now the following condition should be fulfilled:
for F0 500 kHz: (B-A) = 0 dB 1.5 dB
for F0 > 500 kHz: (B-A) = 0 dB +1.5 dB / -3.0 dB
) Note: Do not use any of the previously measured values for the process described
hereafter.
2.
) Note: The RF hybrid must not be plugged on top of P3LL.
The P3LL tuning adapter is set as follows for the entire process:
FUNCTION A
Position of S1 L2
Position of S2 FILTER
Position of S3 Don't care
Position of LOAD Don't care
3. The P4RX module is plugged directly into the rack.
4. Connect the BNC connector OUT of P3LL with the RX RF-IN connector on P4RX.
Connect the level meter (50 or 75 Ohm) to the RX RF-OUT connector of P4RX.
Because the P3LL output is a high impedance source, the signal level at 50/75 Ohm will be quite
small. But mostly a wide band level meter still will be sensitive enough. If not, use a more sensitive
selective level meter to get reliable measurements.
5. In the Tuning Rx RF filter dialog box, click Check Rx RF filter to get the dialog box Check filter.
6. Click Activate f0 and follow the instructions given in the dialog box.
7. Click Activate f0 0.5BRx (BRx = 4, 8, 16 or 32 kHz). Measure the voltage at RX RF-OUT in dB and
check the pass condition given in dialog box.
8. Click Activate f0 + 0.5BRx (BRx = 4, 8, 16 or 32 kHz). Measure the voltage at RX RF-OUT in dB and
check the pass condition given in dialog box.
9. If the conditions checked in steps 7 and 8 are fulfilled, the pass band ripple of the filter is within
specifications.
10. With the next tests, the filter selectivity is checked.
Click Activate f0 2BRx (BRx = 4, 8, 16 or 32 kHz). Measure the voltage at RX RF-OUT in dB and
check the pass condition given in dialog box.
11. Click Activate f0 + 2BRx. (BRx = 4, 8, 16 or 32 kHz). Measure the voltage at RX RF-OUT in dB and
check the pass condition given in dialog box.
12. If the conditions checked in steps 10 and 11 are fulfilled, the selectivity of the filter is within
specifications
13. Click Deactivate frequency and Close.
Revision: Language: Page:
D EN 6/7 1KHW001491-EN
5 Test circuits
P1LA
ON OFF L2
L1
RF Hybrid
not to be S1 FILTER P4LT
plugged S3 TUNE
FILTER
A B S2
FUNCTION
OUT
P3LL
Ext.Coaxial Cable
S3
L1
L1
L2
IN
L3
L2
OUT
SET TUNE
NORM FILTER
S1 S2
P4RX
P4LM P7LC
UOUTPUT 50 / 75/
Notes:
1. For checking the signal path from P4LT to BNC IN of P4LM, switch S1 of P4LM can be put to
position SET. Then BNC IN of P4LM is directly connected to BNC OUT of P4LM.
2. Normally S1 of P4LM is set to NORM.
3. On P4LM, jumper S3 has to be in position L1 to tune P4RX coil L1 and in position L3(!) to tune
P4RX coil L2. Position L2 of jumper S3 on P4LM is not used!
Revision: Language: Page:
D EN 7/7 1KHW001491-EN
P1LA
ON OFF L2
L1
RF Hybrid
not to be S1 FILTER P4LT
plugged S3 TUNE
FILTER
A B S2
FUNCTION
OUT
P3LL
RX RF-OUT
External coaxial cable
BNC-SSMB
P7LC
UOUTPUT 50/75 (selective)
Figure 2: Test circuit for verifying the P4RX filter and gain settings
The P4RX board is plugged directly in the rack, without tuning adapter.
ABB Switzerland Ltd 1KHW001492-EN
Archive No. Rev. Date
Tuning Instructions for ETL600 Tx RF Filter E5TX - E 2009-10-15
Responsible Department: Prepared: Approved: Distribution: Lang. Page
PSND 2005-07-04 H. Hoitink 2012-04-24 H. Benninger - EN 1/7
Valid for: Derived from: Replaces: Classification-No.: File:
1KHL015570-EN - - 1KHW001492EE Tuning of
ETL600 Tx RF Filter E5TX
Contents
1 General ..................................................................................................................................2
1.1 Designations................................................................................................................2
2 Filter programming.................................................................................................................2
2.1 Steps for determining the required jumper positions ..................................................2
3 Tuning the filter circuits individually .......................................................................................2
3.1 Use the following steps in case of the 40 W units.......................................................3
3.2 Use the following steps in case of the 80 W units.......................................................3
4 Checking the frequency response on 40 W or 80 W unit......................................................5
5 Test circuits............................................................................................................................6
5.1 Test circuit for 40 W units............................................................................................6
5.2 Test circuits for 80 W units ..........................................................................................6
Test conditions:
Temperature range: 10 C to 40 C.
List of equipment:
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2012 ABB
Revision: Language: Page:
E EN 2/7 1KHW001492-EN
1 General
In the ETL600, the Tx filter E5TX is tuned using the Tx tuning adapter P3LL and the HMI600.
However before starting tuning, the filter has to be programmed using the correct jumper combi-
nation (given by HMI600) to get the required frequency response. The frequency response of the
filter depends on whether the Tx and Rx channels are adjacent or separate and whether the equip-
ment is a single channel device or provides more than one channel. The HMI600 suggests the
corresponding configuration for the Tx filter according to the mentioned cases above.
Refer to section 5 of the ETL600 instruction manual for more details on configuration.
1.1 Designations
BTx = Tx filter bandwidth (4, 8, 16 or 32 kHz)
Fo = Tx filter center frequency
2 Filter programming
The filter must be programmed with jumpers. With the jumpers, the mode of the coils (series or
parallel connection) and the required capacitors are selected.
The required jumper settings for the Tx filter are generated in the HMI600, according to the chosen
center frequency and nominal bandwidth. To set the required jumpers, the two filter prints have to
be taken out of their housings.
On the back side of the E5TX unit: remove the four small screws in the corners of both filter print
covers. Carefully pulling at the cover, take out the filter prints.
Note:
5.
Once the filter has been selected, in order not to loose the filter settings, the
checkbox Auto-select standard filter must not be activated anymore.
Check if the correct filter center frequency f0 and bandwidth are shown. If these values shall
be modified, select them from the drop down lists.
6. Place the jumpers according to the table Jumper settings E5TX (Transmit filter) shown in
the HMI600. Cs1 settings are for the L1 filter board and Cs2 for the L2 filter board. Settings
Cp and L-mode apply for both prints. 0 means no jumper, 1 means jumper placed.
7. Click Ok to add the filter settings to the equipment configuration, to discard them click Cancel.
generate and inject the tuning frequency into the transmitter filter via the output amplifier stage
P1LA. The Tx tuning adapter provides facility for checking the selectivity.
Note: Keep the tuned Tx filter always together with the hybrid and combiner used
during the tuning procedure. Exchanging a hybrid or combiner requires tuning
the Tx filter again!
1. The Tx tuning adapter is inserted in place of the RF hybrid (P3LE) and the RF hybrid is
plugged on top of it. The Uoutput of the adapter P3LL is connected to the selective level meter in
the wideband range and in high input impedance mode.
2. If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on
to the local ETL600 using equipment ID 0 and upload configuration and status of the
equipment.
3. Choose the Equipment menu and click Tuning & testing.
4. A warning dialog box appears, click OK.
5. Click Tune Tx RF filter to get the Tuning Tx RF filter dialog box.
6. Check if the correct filter center frequency f0 and bandwidth are shown.
7. For tuning the coil L1 set the adapter P3LL to:
FUNCTION :A
Position of S1 : L1, FILTER
Position of S2 : TUNE
Position of S3 : OFF
Position of LOAD : LINE
Click Activate f1. Using coil L1, Uoutput is tuned to a minimum or if an end stop is reached go
to Step A1.
8. For tuning the coil L2 set the adapter P3LL to:
FUNCTION :A
Position of S1 : L2, -
Position of S2 : TUNE
Position of S3 : OFF
Position of LOAD : LINE
Click Activate f2. Using coil L2, Uoutput is tuned to a minimum or if an end stop is reached go
to Step A1.
9. Terminate the action by clicking deactivate frequency and to return to the Tuning & testing
main menu click Cancel.
1. The Tx tuning adapter is inserted in place of the RF hybrid (P3LE) in the lower rack and the
RF hybrid is plugged on top of it. The Tx RF filter (E5TX) in the upper rack must be removed.
The other units in both racks remain in place. The Uoutput of the adapter P3LL is connected to
the selective level meter in the wideband range and in high input impedance mode.
2. If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on
to the local ETL600 using equipment ID 0 and upload configuration and status of the
equipment.
3. Choose the Equipment menu and click Tuning & testing.
Revision: Language: Page:
E EN 4/7 1KHW001492-EN
Step A1
If one of the coils has reached its end stop, then one should select an alternative connection
scheme for the capacitors. If the tuning coil is at its left end-stop, then the next non identical
capacitor combination for a lower frequency is to be selected.
Click on the button left end-stop reached and the new jumper settings appear. Use the same
procedure in case of all other end-stop has been reached events.
To undo the end-stop reached modifications, click on the Default button in the Coil L1 or in
the Coil L2 field respectively.
Click Ok to add the new filter settings to the equipment configuration, to discard them click
Cancel in the Tuning Tx RF filter dialog box.
5 Test circuits
The following circuits should be used for tuning the Tx RF filter using the tuning adapter P3LL and
the HMI600. The P4LT/P4LU generates the required tuning tones.
P1LA E5TX
L2 OFF ON
L1
FILTER
S1
S3
OUT P3LE
TUNE S2
FILTER
UOUTPUT
P4LT/U P3LL
600134A3.VSD
Fig. 1: Test circuit for tuning 40 W units. Tuning coil L1 or L2 dependent on switch S1.
P1LA E5TX
L2 OFF ON
L1
FILTER S1 S3
P4LT/U
OUT P3LE
TUNE S2
FILTER
U P3LL
OUTPUT
600134A4.VSD
Fig. 2: Test circuit for tuning L1 in the lower power amplifier rack.
Revision: Language: Page:
E EN 7/7 1KHW001492-EN
P1LA
P1LA E5TX
L2 OFF ON
L1
FILTER S1 S3
P4LT/U
OUT P3LE
TUNE S2
FILTER
U P3LL
OUTPUT
600134A5.VSD
Fig. 3: Test circuit for tuning L2 in the lower power amplifier rack.
P1LA
L2 OFF ON
L1
FILTER S1 S3
P4LT/U OUT
P3LE
TUNE S2
FILTER
U P3LL
OUTPUT
600134A6.VSD
Fig. 4: Test circuit for tuning L1 in the upper power amplifier rack.
P1LA E5TX
L2 OFF ON
L1
FILTER S1 S3
P1LA OUT
P3LG
TUNE S2
FILTER
P4LT/U U P3LL
OUTPUT
600134A7.VSD
Fig. 5: Test circuit for tuning L2 in the upper power amplifier rack.
ABB Switzerland Ltd 1KHW001493-EN
Archive No.: Rev. Date:
Programming and Testing Instructions ETL600 - J 2012-04-24
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PSND 2005-09-13 H. Benninger 2012-04-24 C. Leeb - EN 1/24+3
Valid for: Derived from: Replaces: Classification-No.: File:
- 1KHL015940-EN - - 1KHW001493JE Programming and Testing of ETL600
This document describes programming and testing of power line carrier equipment ETL640 and ETL680,
including the teleprotection system NSD600.
Contents
A Programming Instructions for the ETL600 Equipment 3
A.1 General 3
A.2 Create a configuration for the equipment using HMI600 3
A.3 Hardware 3
A.4 Settings for basic equipment ETL640/680 4
A.5 Settings for alarm unit R1BC, if present 4
A.6 Settings for NSD600 interface G4AI, if present 4
A.7 Check service keys 5
B Testing Instructions for the ETL600 Equipment. 7
B.1 General 7
B.2 Check power supply B5LA/B5LC 7
B.3 Connect to the equipment, download configuration and prepare for tuning
& testing 8
B.4 Change configuration, if necessary 8
B.5 Transmitter 8
B.6 Receiver 9
B.7 Equalization of APLC channels 11
B.8 Testing of R1BC, if present 12
B.9 Configure Real Time Clock (RTC) 12
B.10 Testing of NSD600 with interface G4AI, if present 13
B.11 Testing of O4LE, if present 14
B.12 Testing of the V.11 ports 19
B.13 Testing of the V.24 ports 19
B.14 Testing of G.703.1 port 20
B.15 Testing of LAN ports 20
B.16 Testing of O4CV, if present 20
B.17 Documentation 24
B.18 Manual reset 24
ETL600 Hardware Checks: .......................................................................... A1 - A3
ETL600 System Test Report: .............................. Refer to document 1KHD626826
The terminal designations in this document apply to terminals blocks for 10 wire pairs.
Test conditions:
Temperature range: 10 C to 40 C.
The connections for the tests can be made either at the test sockets on the front of the
equipment or at the terminals.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2012 ABB
Revision: Language: Page:
J EN 2 1KHW001493-EN
Notes:
Designation Meaning
___________ Measured value
[ ... ] Programmed value
[ ]D Preferred setting (default)
[X ] Test passed or jumper is set
[ ] Not tested or jumper is not set
B5LA Module type
BER Bit Error Ratio
Def. Default value
equ. Equipment
fLo Lower frequency, usually meant as low cut-off frequency
LED Light Emitting Diode found on the front panel
HMI600 User Interface Program for ETL600 running on a PC
N11, , N71 Position in rack. Slot number N11, , N71
Rx Receiver
Tx Transmitter
PC Personal Computer
(T.22/..1) Connector 1 of terminal block connected to board at rack position N22
Revision: Language: Page:
J EN 3 1KHW001493-EN
A.1 General
All RF channel settings, all settings of telephony- and teleoperation-ports, most settings of the
integrated teleprotection system NSD600 are performed with the configuration program HMI600.
Typically this data are configured off-line and stored as a file on a disk. All these settings are
loaded from a file the ETL600 configuration file *.et6 and downloaded to the equipment. The
download of hardware settings such as jumpers or the presence or absence of modules without
access to the TDM bus is just for documentation and the correctness of this information must be
verified in the course of this instruction.
The most important settings are the RF Tx and Rx carrier. A few settings have to be adjusted with
the equipment e.g. the Tx RF level. Most of these tuning, testing and adjustment procedures are
supported by HMI600.
First the hardware settings of the analogous passive modules, such as the Tx- and Rx-Filters must
be done. For these hardware settings, refer to the applicable instructions and use the settings
specified in chapter system settings at the end of this document on page A1 and following.
Follow conscientiously and step-by-step this instruction and the equipment will work properly!
A.3 Hardware
J EN 4 1KHW001493-EN
Caution Before switching ON for the first time, check the wiring of protective earth and
power supply polarity. Also check the voltage source for the power supply.
J EN 5 1KHW001493-EN
Check if the data key mounted on the P4LT/U/V/X board is valid according to the table above.
Please ask your local representative about the update procedure if the data key is not sufficient or
if no data key is installed on P4LT/U/V/X.
When the new data keys are available, proceed as described in the procedure Replace data key
below.
J EN 6 1KHW001493-EN
Check if the voice keys mounted on the O4CV boards are valid as given by the HMI600
configuration view.
Please ask your local representative about the update procedure if the voice key is not sufficient or
if no voice key is installed on one or more of the O4CV boards.
When the required voice keys are available, proceed as described in the procedure Replace voice
key below.
ESD protection
Caution The modules in this equipment contain devices, which can be damaged by
ESD electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on modules
are grounding straps for technical personnel and the provision of anti-static
workbenches. Modules may only be shipped either in their original packing
or installed in equipment racks.
J EN 7 1KHW001493-EN
B.1 General
Most of the testing for the ETL600 system can be done with assistance of HMI600. For some
adjustments like Tx RF level, Rx RF level etc. the permissible limits are calculated by the HMI600
and displayed in the dialog boxes.
The pilot signal is QPSK modulated to accommodate both Signaling and Embedded Operations
Channel. As a result, the level of the pilot signal changes continuously so that its exact level cannot
be measured.
The Tx filter E5TX and the Rx filter P4RX (if used) have to be tuned before testing.
An attenuator with impedance 45, 75 or 125 Ohm and a minimum attenuation of 15 dB is inserted
between two equipments to simulate a power line. For testing, the attenuation between the two
equipments is kept as follows:
In case of battery supply: Check if the positive pole (+) of the battery is grounded. If it is, place an
earth jumper to the positive pole of the cubicle supply.
J EN 8 1KHW001493-EN
B.3 Connect to the equipment, download configuration and prepare for tuning &
testing
1. Start the HMI600, open the preconfigured file and connect to the equipment as described
in the instruction manual, 1KHW001489, chapter 4, section Communication to the
ETL600.
2. From the Equipment menu, click Download configuration. The service keys are
checked and error messages appear if not sufficient. Compatibility checks are performed
to verify that the firmware versions in the equipment belong to the same release as the
HMI600. If not, an error message pops up. Depending on the message, an earlier version
of HMI600 must be used and/or the firmware of some modules must be upgraded. The
latter is described in the document Firmware Download for ETL600, 1KHW001496.
3. If the download operation is possible, a message box appears, which informs you that the
link will be cut off for a few seconds.
Click Yes
4. The Test configuration time dialog box has been opened.
Click OK.
5. The HMI600 now compares the equipment identification from the file with the
identification in the equipment. If it is different, a warning message box appears.
Click OK. This starts the download configuration process.
6. A dialog box informs you, that the configuration has not been stored in the nonvolatile
flash EPROM and asks you if you want to do so.
Click Yes.
The configuration data are now stored in the flash EPROMs. This process needs some
seconds. Please wait until the color of the stop button in the toolbar changes from red to
grey. The actual status of the process is displayed in the status bar.
7. From the equipment menu, click Tuning & testing. This opens a dialog box, which
informs you that activating tests in the following dialog boxes may cause malfunctions of
the PLC-link.
8. Click OK and the Tuning & testing dialog box appears.
B.5 Transmitter
The frequency in the AF band when converted in to the RF band will have an additional offset of
150 Hz. This has been done to simplify the filtering by DSP. The frequency shift when reconverted
to the AF band will be restored.
J EN 9 1KHW001493-EN
Note: When measuring at the test socket RF line monitor, the following tolerances apply:
- 0.4 dB for frequencies between 16 kHz and 500 kHz
- 1.0 dB for frequencies between 500 kHz and 1 MHz.
Alternatively, measure the test tone level at the RF line socket (X175) via an attenuator
with impedance 45, 75 or 125 Ohm and a level meter set to the same input impedance
(The attenuator is required in order not to overdrive the input of the level meter).
5. Adjust the value in the Tx RF level [dB] field, download it by clicking Set and measure
the test tone level again. Continue until the measurement corresponds to the permissible
value displayed in the dialog box.
B.6 Receiver
J EN 10 1KHW001493-EN
Note: The number of adjustment steps depends on the presence of the Rx filter P4RX
(configured with Configuration / System / Equipment settings / Assemblies in
rack P7LC).
3. After all adjustment steps have been executed, click Close to close the dialog box.
Note: The tuning is not necessary when the ETL600 is operated without Rx filter
P4RX.
5.
Note: It is possible that the operator phone of remote equipment is ringing during
the measurement. This has no effect on the measurement.
The HMI600 selectively measures the level of the RF signal from the own transmitter.
This level is set to a minimum with the aid of a balancing network (resistance with jumper
RA/RB/RC/RD/RP and potentiometer R228, inductance with jumper LA LN/LP and
capacitance with jumpers CA to CL, CP) as described below.
6. Reduce the measured Rx RF level moving the R-jumper between RA, RB, RC, RD and
RP. When the best jumper position has been found, turn potentiometer R228 until a first
minimum is reached.
7. Search for the next minimum by moving the L-jumper sequentially to LA, LB, LC, , LN.
If, however, jumper LA does not produce any reduction, set Jumper LP. (LA produces the
smallest inductive current and LN the largest).
Note: Only one L jumper (LA LN) may be inserted at any one time
Revision: Language: Page:
J EN 11 1KHW001493-EN
Note: The transhybrid loss that has been achieved by tuning the hybrid is
equal to the increase of the measured RF level when the RF cable is
unplugged. If it is higher than 20 dB, the tuning can be considered as
successful and may be terminated.
J EN 12 1KHW001493-EN
5. Exit.
J EN 13 1KHW001493-EN
B.10.1 Inputs
B.10.2 Outputs
Depending upon the programmed criteria, activate the required action using the following table.
Check the contact closure of the programmed outputs on G4AI.
Set the link back to an alarm free operation after this test.
J EN 14 1KHW001493-EN
Note: The nominal transmission time as given in the technical data shall serve as a
guideline for the mean value of several commands.
EUT:
Connector X2
O4LE
remote 5.5 H R
110 F
110 F Audio Analyzer
A32 0a 5.5 H
C32 0b Generator Analyzer
110 F
Terminal, telephony
EUT:
Connector X2
O4LE
local 5.5 H R
110 F
110 F
A32 0a 5.5 H
C32 0b
110 F
SUBSCR_Mess3.dsf
Figure 2
J EN 15 1KHW001493-EN
Connect a 2.2 kOhm resistor between PAX2W input and generator! The generator
neednt be programmed with a special ringing sequence. Now the phone should ring in a
typical sequence.
2. Check the Output level of subscriber:
Use coupling bridges similar to that, shown in Figure 3. The resistor R should be chosen
to 500 Ohm, included the resistance of the two coils. If the coupling bridge has polarity.
Check first polarity at external cable of appropriate O4LE, terminal telephony, 0a-0b and
observe polarity of external voltage source.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
EUT:
Connector X2
O4LE
remote 5.5 H R = 2k2
110 F
110 F Audio Analyzer
A14 8a 5.5 H
C14 8b Generator Analyzer
110 F
U = 50 V
Terminial, telephony
EUT:
Connector X2
O4LE
local 5.5 H R
110 F
110 F
A32 0a 5.5 H
C32 0b
110 F
SUBSCR_Mess4.dsf
Figure 3
J EN 16 1KHW001493-EN
2. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
3. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open. Check it.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed. Check it.
4. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
Terminal, telephony
EUT:
Connector X2
O4LE
remote 5.5 H R
110 F
110 F Audio Analyzer
A32 0a 5.5 H
C32 0b Generator Analyzer
110 F
Terminal, telephony
EUT:
Connector X2
O4LE
local 5.5 H
R = 2k2
110 F
110 F
A14 8a 5.5 H
C14 8b
110 F
U = 50 V
PAX2W_Mess5.dsf
Figure 4
J EN 17 1KHW001493-EN
J EN 18 1KHW001493-EN
First method:
This method only works, if identical Reference signal and identical level unit for the reference
signal, dBm (RMS) or dBm (PEP) is selected on both sides of link.
1. Determine the correct input level fed into the remote equipment.
The Reference signal level input, listed in the configuration printout of the remote
equipment should be fed into AFx-IN of the remote equipment.
2. Determine expected output level of AFx-OUT of local equipment.
The Reference signal level output of AFx-OUT of the local equipment is the expected
output level.
3. Take the measurement with a selective level meter.
Second method:
This method works with any configuration of AF ports, which are switched on.
1. Determine the correct input level fed into the remote equipment.
The Reference signal level input, listed in the configuration printout of the remote
equipment should be fed into AFx-IN of the remote equipment.
2. Calculate expected output level of AFx-OUT of local equipment.
L(out) local L(in) remote L( Rel. Input Level) remote L( Rel. Output Level) local
3. Take the measurement with a selective level meter.
Example:
Applying the first method to the configuration given below, a sinus with 9.0 dBm is fed into remote
equipment. The tone is expected with 6.0 dBm at AFx-OUT of local equipment.
Applying the second method to the configuration given below, a sinus with 9.0 dBm is fed into
remote equipment. Calculating the expected output level at local equipment with the formula above
results to:
Lout = -9.0 dBm (-4.00 dBr) + (-1.00 dBr)
The expected output level Lout is just as applying the first method 6.0 dBm.
Equipment REMOTE
TELEOPERATION
Port AFx: Disconnectable at CH1
Squelch: Disabled
Reference signal: 600 Bd FSK
Reference signal level input: -9.00 dBm (RMS)
Reference signal level output: -9.00 dBm (RMS)
Weight of port: 0.71
Max. output level: -7.00 dBm (PEP)
Relative input level: -4.0 dBr
Relative output level: -4.0 dBr
Input filter: None
Output filter: None
Equipment LOCAL
TELEOPERATION
Port AFx: Disconnectable at CH1
Squelch: Disabled
Reference signal: 600 Bd FSK
Reference signal level input: -6.00 dBm (RMS)
Reference signal level output: -6.00 dBm (RMS)
Weight of port: 0.71
Max. output level: -4.00 dBm (PEP)
Relative input level: -1.0 dBr
Relative output level: -1.0 dBr
Input filter: None
Output filter: None
J EN 19 1KHW001493-EN
1. Check the port settings in the configuration (Configuration / Data port to modem
assignment) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test during the required time. The recommended number of bits to transmit
is 107.
J EN 20 1KHW001493-EN
1. Connect the data testers to the G.703.1 ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped at the remote equipment.
2. Perform a BER test during the required time. The recommended number of bits to transmit
is 107.
J EN 21 1KHW001493-EN
Figure 5
J EN 22 1KHW001493-EN
EUT:
O4CV
remote 5.5 H R = 2k2
110 F
110 F Audio Analyzer
PAX 2-Wire 5.5 H
interface
Generator Analyzer
110 F
U = 50 V
EUT:
O4CV
local 5.5 H R
110 F
110 F
Subscriber 5.5 H
interface
110 F
Figure 6
EUT:
O4CV
remote
PAX 4-wire
Audio Analyzer
interface,
4-wire input Generator Analyzer
EUT:
O4CV
local 5.5 H R
110 F
110 F
Subscriber 5.5 H
interface
110 F
Figure 7
Revision: Language: Page:
J EN 23 1KHW001493-EN
EUT:
O4CV
remote 5.5 H R
110 F
110 F Audio Analyzer
Subscriber 5.5 H
interface
Generator Analyzer
110 F
EUT:
O4CV
local 5.5 H
R = 2k2
110 F
110 F
PAX 2-Wire 5.5 H
interface
110 F
U = 50 V
Figure 8
J EN 24 1KHW001493-EN
B.17 Documentation
After the testing is complete, take a printout of the configuration and status data.
1. Click the green Upload arrow in the HMI600 toolbar with the left mouse button. This
starts configuration and status upload from the equipment. The status is displayed in the
window.
2. From the File menu, click Print to print the status data.
3. From the View menu, click Display configuration.
4. From the File menu, click Print to print the configuration data.
5. From the File menu, click Save As to save the active document to disk with the Serial
No. of the ETL600 coded in the file name, e.g. HE400327B0.ET6. All settings you have
made while working in the document will be saved to the new file, including the last
measured AF and frequency response.
Item to be Selected
No. Action Rack or programmed or alternative Remarks
module fitted or setting
A.1 General
A.3 Hardware
*
Upper und Lower stands for upper rack / lower rack and applies to 80 W equipment ETL680 only.
Doc. no. Lang. Rev. ind. Page
Item to be Selected
No. Action Rack or programmed or alternative Remarks
module fitted or setting
Item to be
No. Action Rack or programme Remarks
module d or fitted
Item to be
No. Action Rack or programme Remarks
module d or fitted
A.6.4 Cover at component side N11 N22 N28 N34 N54 N65 N71
Mounted G4AI [ ] [ ] [ ] [ ] [ ] [ ] [ ]
A.7.2 O4CV voice keys N11 N22 N28 N34 N54 N65 N71
Slots not occupied with O4CV [ ] [ ] [ ] [ ] [ ] [ ] [ ]
boards
Valid voice keys mounted O4CV [ ] [ ] [ ] [ ] [ ] [ ] [ ]
Project : ..
ABB Order N : ..
Station : ..
Link : ..
Equipment N : ..
Direction : ..
.. Pages .............
Rev. ind:
Type des. Part no.
No. of p.
Prep. A. Bemsel / PSNEX 2005-11-12 Doc.kind
Appr. H. Benninger / PSND 2012-04-27 Title System Test Report ETL600 18+
Resp.dept. PSNEX
Doc. no. Lang. Rev. ind. Page
REVISION
Rev. Page (p.) Description Date
ind. Chapter (c.) Dept./Init.
a Complete document Exctracted from document 1KHW001993-EN, Rev. A. 2005-11-21,
PTUKX1/AB
b c. Safety instructions Text modified 2006-02-17,
c. Designations and Added PTUKT/Be
abbreviations
Complete document Added fields for revision index referring to the contents of the test report
Complete table of tests Changed text size to 9
Steps B.5.2 and B.5.3 Added. => Previous steps B.5.2 to B.5.4 renumbered to B.5.4 to B.5.6
Steps B.5.1 and B.6.1 Added lines for the bandwidth 4 kHz
c. Customer acceptance Modified
(last page)
c Section B7 Inserted. Previous sections B7 B14 renumbered to B8 B15 2006-04-26,
PTUKT/Be
Step B10.4 (earlier B9.4) Replaced T22 by T71
Step B4 Checkbox added
d Steps B12, B13 Changed acceptance limits 2006-06-30,
PSND/Be
e p. 1, p. 13 Updated department designations 2006-09-19,
p. 1 Inserted line for link designation PSND/Be
f Steps B14, B15 Tests of G.703.1 and LAN ports added 2007-02-01,
( previous sections B14, B15 renumbered to B16, B17). PSND/Be
Replaced entry fields for telephony levels by checkboxes
g Steps B11.3, B11.5 Corrected default levels 2007-05-21,
PSND/Be
h p. 8, p. 9 Corrected PAX-BLOCKING closed / open 2007-10-07,
Steps B11.5, B11.6 PSND/Be
B11.7, B11.8
i Added checkboxes Mark All subsections of B5, B7, B8, B9, B10, B11, B12, B13, B14, B15 2007-11-05,
if not configured PSND/Be
j Added section for testing New section B16 ( previous sections B16, B17 renumbered to B17, B18). 2007-11-15,
of O4CV board PSND/Be
k Inserted line Test ETL600 List of used Test-instruments and spare line 2008-06-18,
Added test HMI over LAN. PSND/Be
Corrected various checkboxes Mark if not configured
l B.5.1, B.5.4, B.6.1, B.6.2 Added checkboxes for the case that the testing is done without filter 2010-01-25,
programming and tuning PSND/Be
m B.15 Added test of LAN ports 2, 3 and 4 2012-04-24,
PSND/Be
B.1 General
Upper* Lower
B.2 Check power supply B5LA/B5LC
B.5 Transmitter
Upper* Lower
B.5.1 Programming of Tx RF filter
Refer to Tuning of ETL600 Tx RF Filter Mark if not programmed 1 [ ] [ ]D
E5TX 1KHW001492-EN
Bandwidth = 4 kHz E5TX Refer [ ] [ ]D
Bandwidth = 8 kHz E5TX to [ ] [ ]D
Bandwidth = 16 kHz E5TX document [ ] [ ]D
Bandwidth = 32 kHz E5TX 1KHW001492 [ ] [ ]D
Center frequency E5TX fTx=________ kHz
1
As the channel frequencies were not known at test time, the system was tested with temporarily inserted factory-owned
filter(s), programmed and tuned to a standard frequency and bandwidth.
Doc. no. Lang. Rev. ind. Page
Upper* Lower
B.5.4 Tune Tx RF filter Mark if not configured: [ ] [ ]D
2
Mark if not tuned : [ ] [ ]D
Dialog box 'Tune Tx RF filter' E5TX Refer to doc. [ ] [ ]D
1KHW001492
B.6 Receiver
2
As the channel frequencies were not known at test time, the system was tested with temporarily inserted factory-owned
filter(s), programmed and tuned to a standard frequency and bandwidth.
Doc. no. Lang. Rev. ind. Page
Ch 1 Ch 2 Ch 3
B.7.1 Measure frequency response Mark if not configured: [ ] [ ] [ ]
B.10.2 Outputs
TPE1 TPE2
Command A Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command A (T71/1) (T71/2) [ ] Mean value
(T/...) (T.../) [ ]
T0 ms ________ ________
Rx command A (T71/9) (T71/10) [ ]
(T/...) (T.../) [ ]
TPE1 TPE2
Command B Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command B (T71/3) (T71/4) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command B (T71/11) (T71/12) [ ]
(T/...) (T.../) [ ]
TPE1 TPE2
Command C Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command C (T71/5) (T71/6) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command C (T71/13) (T71/14) [ ]
(T/...) (T.../) [ ]
TPE1 TPE2
Command D Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command D (T71/7) (T71/8) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command D (T71/15) (T71/16) [ ]
(T/...) (T.../) [ ]
Pick up the phones and talk. Service phone, at front Remote service N11 N22 N54
panel phone rings, buzzer
drones, talk is [ ] [ ] [ ]
possible
B.11.2 Hot line direct phone Mark if not configured: N11 N22 N54
[ ] [ ] [ ]
Pick up the phone, wait, pick Direct phone Remote direct N11 N22 N54
up remote phone phone rings until
phone is picked up. [ ] [ ] [ ]
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 0a-0b level 1 dB (600 )
(Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote Measure at terminal
subscriber (Def.: 0.0 dBm). telephony 0a-0b
Test Ringer: Feed ringing Feed into rem. equ. at Subscriber must N11 N22 N54
voltage (25 VAC, 25 Hz, R = terminal telephony 8a-8b ring
[ ] [ ] [ ]
2.2 k) into remote PAX 2-
Wire
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 8a-8b level 1 dB (600 )
(Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote Measure at terminal
PAX.(Def.: 0.0 dBm) telephony 0a-0b
Test Ringer: Activate at Remote equ. Subscriber must N11 N22 N54
Activate M-WIRE of remote at terminal telephony 4a- ring
4b [ ] [ ] [ ]
Pax 4-wire.
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 1a-1b level 1 dB (600 )
(Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote Measure at terminal
PAX.(Def.: -3.5 dBm) telephony 0a-0b
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 0a-0b level 1 dB (600 )
(Def.: -7.0 dBm) [ ] [ ] [ ]
input level of remote Measure at terminal
subscriber.(Def.: 0.0 dBm) telephony 8a-8b
B.11.6 Pax 4-wire. At remote equ. is Mark if not configured: N11 N22 N54
Pax 4-wire [ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open at Remote [ ] [ ] [ ]
equ. at terminal telephony
4a-4b
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 1a-1b level 1 dB (600 )
(Def.: -3.5 dBm) [ ] [ ] [ ]
input level of remote PAX Measure at terminal
(Def.: -3.5 dBm). telephony 2a-2b
(Activate at terminal telephony
4a-4b on both equ.)
B.11.7 Pax 4-wire. At remote equ. is Mark if not configured: N11 N22 N54
Remote subscriber [ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Toggle hook of phone. [ ] [ ] [ ]
(Close and open at Remote
equ. at terminal telephony
0a-0b)
Measure Output level. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 0a-0b level 1 dB (600 ) [ ] [ ] [ ]
input level of remote Measure at terminal (Def.: -3.5 dBm)
subscriber.(Def.: 0.0 dBm) telephony 2a-2b
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open at Remote
[ ] [ ] [ ]
equ. at terminal telephony
4a-4b
Measure Output level of AF1. Feed into rem. equ. at Configured Output dBm N11 N22 N54
Feed 800 Hz with configured terminal telephony 1a-1b level 1 dB (600 ) [ ] [ ] [ ]
input level of remote PAX Measure at terminal (Def.: -3.5 dBm)
(Def.: -3.5 dBm). telephony 2a-2b
Activate at terminal telephony
4a-4b on both equ..
Measure Output level of Feed into rem. equ. at Configured Output dBm N11 N22 N54
PAX2W. terminal telephony 1a-1b level 1 dB (600 ) [ ] [ ] [ ]
Feed 800 Hz with configured Measure at terminal (Def.: -7.0 dBm)
input level of remote PAX telephony 8a-8b
(Def.: -3.5 dBm).
(Activate at terminal telephony
4a-4b on both equ.)
Test Local/Transit: Feed into rem. equ. at Configured Output dBm N11 N22 N54
Measure Output level at AF1. terminal telephony 8a-8b level 1.5 dB (600 ) [ ] [ ] [ ]
Feed 800 Hz with configured Measure at terminal (Def.: -7.0 dBm)
input level of remote PAX2W telephony 8a-8b
(Def.: -0.0 dBm).
Activate at terminal telephony
5a-4b of remote equ..
(Activate at terminal,
telephony 4a-4b on both equ.)
B.11.9 Transit mode for E&M wire Mark if not configured: N11 N22 N54
[ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open at Remote [ ] [ ] [ ]
equ. at terminal telephony
4a-4b
B.11.11 Teleoperation AF1, if not Mark if not configured: N11 N22 N34 N54 N65
used for telephony [ ] [ ] [ ] [ ] [ ]
B.11.12 Teleoperation AF2 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
B.11.13 Teleoperation AF3 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
B.11.14 Teleoperation AF4 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
B.11.15 Teleoperation AF4 used for Mark if not configured: N11 N22 N54
ext. teleprotection [ ] [ ] [ ]
Fed input level, [dBm], Feed into rem. equ. at Expected Output Measured Output level at
@ 800 Hz at AF4-IN terminal teleop. 7a-7b level at AF4-OUT AF4-OUT
N11: ___________ Measure at terminal N11: _______1 dBm N11: ___________
teleop. 8a-8b (600 )
N22: ___________ N22: _______1 N22: ___________
N54: ___________ N54: _______1 N54: ___________
O4CV#2: N_____
O4CV#3: N_____
O4CV#4: N_____
B.17 Documentation
CUSTOMER ACCEPTANCE
The acceptance form is completed by ABB and the customer representative once all equipment tests
detailed in this document have been performed successfully. Customer acceptance form is part of the
test report.
Date:
Supervisor: _____________________________
FAT Witnessed
Date: _____________________________
Engineer: _____________________________
... _____________________________
Contents
1 Purpose of document 2
2 Abbreviations and Definitions 2
3 Equalizer concept 2
3.1 None (no equalizer) 3
3.2 Short equalizer 3
3.3 Medium equalizer 3
3.4 Long equalizer 4
4 Establishing a new equalizer 4
5 Equalizing a channel 4
6 Changing the length or mode of a running equalizer 5
7 Remote equalizer manipulation 6
8 Application specific equalizer choices 6
8.1 Rules if external teleprotection in the selected channel is used 6
8.2 Equalizer for NSK600 modems with data rates of 2.4, 4.8 and 9.6 kbps 6
8.2.1 ETL600 Rel.3.0 or earlier ETL600 releases 6
8.2.2 ETL600 Rel.3.1 or later ETL600 releases 6
9 Recommended procedure to equalize a channel 7
10 Recommended procedure to change the equalizer settings 7
List of equipment:
PC with Windows XP, Vista or Windows 7
HMI600 software
PC P4LT/U/V/X cable 1:1 serial RS-232
Note:
Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2013 ABB
Revision: Language: Page:
F EN 2/7 1KHW001494-EN
1 Purpose of document
This document describes the equalization process for the equipment ETL600, supported by the PC
program HMI600.
Note: To access the remote equipment, log ON using the equipment address of the
remote equipment. This is especially applicable for chapters 4, 5, 6, 8.2.2 and
10.
Channel: An ETL600 PLC link offers up to three AF channels for transmission of analog
signals. Each channel is equalized separately.
Equalizer: A filter that flattens the amplitude and/or group delay response of a channel.
BER: Bit error ratio
3 Equalizer concept
The ETL600 has an integrated equalizer separately for each configured channel. Two operation
modes are available: Amplitude equalization only and combined amplitude with group delay
equalization. The resulting amplitude response of each channel (with the selected equalizer and
none) can be viewed with the HMI600 software before activation and during operation without
interrupting services on the link.
It is possible to change later an active equalizer with amplitude equalization only to one with
combined amplitude and group delay equalization and vice versa (with short interruption of the link
due to equipment reset).
Instructed personnel can choose between 4 possible equalizer settings: None (no equalizer),
short, medium or long equalizer.
Note: After changing RF settings (Tx, Rx nominal frequency or overall channel mode),
all active equalizers have to be updated.
Note: After changing the number of APLC channels from or to 3 channels in 8 kHz, all
active equalizers have to be updated.
Note: In case of nominal bandwidth Bn = 2 kHz or 2.5 kHz (only available in ETL600
R4), the resulting equalizer is not useful. Do not activate any equalizer.
Note: The equalizer is applied on the receive signal whereas the allpass filter is
applied on the transmit signal. As a consequence the equalizer has to be
configured on the receiving equipment and the allpass filter on the transmitting
equipment.
5 Equalizing a channel
In this section the letter 'X' names the channel to equalize. This can be channel 1, 2 or channel 3.
Do not mix up the channel during the whole equalization process. The selected channel from the
remote to the connected ETL600 system will be equalized.
Revision: Language: Page:
F EN 5/7 1KHW001494-EN
Please note that equalizing a channel over the EOC network or on the remote side may take
several 10 minutes.
Make a connect with write access to the desired ETL600 equipment and upload the configuration.
Select in the menu bar 'Equipment' / 'Commissioning and maintenance' / 'Frequency
response' / 'APLC channel X'. A dialog box appears telling the user that he is going to disable the
system. By pressing the 'Cancel' button, no channel measurement will be started. By selecting the
'Yes' button, a channel measurement on channel X from the remote to the local ETL600 terminal
will be started. This is also the last chance to abort an equalizer selection process without
interrupting normal services.
After up to 5 minutes, the measurement is finished and the dialog box 'Select equalizer' appears.
The amplitude response of the link from remote equipment to the connected ETL600 can be
viewed for channel X.
With the help of the 'Select equalizer' dialog box, it is possible to select the best possible equalizer
for a specific purpose. When this dialog box first appears, the active equalizer is easily recognised
in the 'Actual equalizer' field. The equalizer delay describes the additional delay added by the
equalizer. The less this delay is, the better it is for applications with external teleprotection
equipment. Please note that the internal teleprotection NSD600 is working independently from this
equalizer delay. The average ripple describes the average ripple left in the complete AF band by
the equalizer. By selecting the desired equalizer before pressing the 'View' button, the frequency
response is visible with and without the equalizer.
In order to return to the 'Select Equalizer' dialog box, select 'Equipment' / 'Commissioning and
maintenance' / 'Select equalizer' / 'APLC channel X' again. It is possible to repeat this procedure
again and again.
If the amplitude response with the equalizer is quite 'noisy', the measurement went wrong due to
sporadic noise on the high voltage line during the measurement. In this case repeat the
measurement by selecting 'Equipment' / 'Commissioning and maintenance' / 'Frequency
response' / 'APLC channel X'.
Discarding a new equalizer: If after several measurements all new equalizers have worse results
than the actual equalizer, it is better to leave the old equalizer unchanged by quitting 'Select
equalizer' with the 'Cancel' button.
Activating a new equalizer: After finding a new equalizer suitable, select the new desired equalizer
in 'Equipment' / 'Commissioning and maintenance' / 'Select Equalizer' / 'APLC channel X'.
Then press the 'Download' button. A dialog box appears which warns the user of an ETL600
system reset. By pressing 'Yes', the selected equalizer settings will be downloaded, stored in the
EPROM and after the restart the new equalizer will be activated.
equalizer you would like to view and click on the 'View' button. By pressing 'Cancel' the window
can be closed without further action.
Changing the equalizer length or equalizer mode: Select the length and mode of the desired
equalizer and press the 'Download' button. A dialog box appears which warns the user of an
ETL600 system reset. By pressing 'Yes', the selected equalizer settings will be downloaded, stored
in the EPROM and after the restart the new equalizer will be activated.
Select the shortest possible equalizer (smallest additional added delay) with flat amplitude
response in the external teleprotection channel. If possible use 'Amplitude response equalization
only'.
8.2 Equalizer for NSK600 modems with data rates of 2.4, 4.8 and 9.6 kbps
Starting with ETL600 Rel.3.1, an adaptive equalizer is available for 2.4, 4.8 and 9.6 kbps NSK600
modems.
equalizer' / 'On'). The static channel equalizer and the all-pass filter should they be enabled - are
bypassed. The advantage of the adaptive equalizer is that it adapts to changing channel
characteristics.
If for some reason the adaptive equalizer needs to be disabled, the channel equalization procedure
as described in section 8.2.1 is required. However, the adaptive equalizer will usually be the better
choice, as for most transmission channels encountered in practice it outperforms the static channel
equalizer.
This document describes programming and testing of power line carrier equipment ETL640 and ETL680,
including the teleprotection system NSD600.
Contents
C Commissioning Instructions for the ETL600 Equipment 3
C.1 General 3
C.2 Power supply for channel rack P7LA 4
C.3 Connect to equipment, upload configuration 4
C.4 Change configuration, if necessary 4
C.5 Transmitter 5
C.6 Receiver 6
C.7 Equalization 9
C.8 Testing of R1BC, if present 10
C.9 Configure Real Time Clock (RTC) 11
C.10 Testing of NSD600 with interface G4AI, if present 11
C.11 Testing of O4LE, if present 12
C.12 V.11 ports 15
C.13 V.24 ports 15
C.14 Testing of G.703.1 port 16
C.15 Testing of LAN ports 16
C.16 Testing of O4CV, if present 16
C.17 Manual reset 17
C.18 Documentation 17
ETL600 Commissioning Report: ......................... Refer to document 1KHD626830
The terminal designations in this document apply to terminals blocks for 10 wire pairs.
Test conditions:
Temperature range: 10 C to 40 C.
The connections for the tests can be made either at the test sockets on the front of the
equipment or at the terminals.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2012 ABB
Revision: Language: Page:
I EN 2/17 1KHW001495-EN
Notes:
Designation Meaning
___________ Measured value
[ ... ] Programmed value
[ ]D Preferred setting (default)
[X ] Test passed or jumper is set
[ ] Not tested or jumper is not set
B5LA Module type
BER Bit Error Ratio
Def. Default value
EOC Embedded Operation Channel
equ. Equipment
fLo Lower frequency, usually meant as low cut-off frequency
LED Light Emitting Diode found on the front panel
HMI600 User Interface Program for ETL600 running on a PC
N11, , N71 Position in rack. Slot number N11, , N71
Rx Receiver
Tx Transmitter
PC Personal Computer
X11, , X71 Position in rack. Equivalent to N11, , N71
Revision: Language: Page:
I EN 3/17 1KHW001495-EN
C.1 General
Most of the commissioning tests (including fully automatic equalization) for the ETL600 system can
be done with the help of PC based software HMI600. It is assumed, that all assembled Tx filters
and Rx filter are tuned. Under normal conditions only level adjustments will be done during
commissioning. It is required to work through the document Programming and Testing of ETL600,
1KHW001493, which is dispatched along with the equipment, before starting the commissioning.
In case of some adjustments like Tx RF level, Rx RF level etc. the permissible limits are calculated
by the HMI600 and displayed in the dialog boxes.
The pilot signal is QPSK modulated to accommodate both Signalling and Embedded Operations
Channel. As a result, the level of the pilot signal changes continuously (by about 3 dB) due to
which its exact level cannot be measured.
The equipment must be tested using a standard cable impedance or in local loop mode before
connecting the equipment via the coupling device to the power line.
ESD protection
Caution The modules in this equipment contain devices, which can be damaged by
ESD electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on modules
are grounding straps for technical personnel and the provision of anti-static
workbenches. Modules may only be shipped either in their original packing
or installed in equipment racks.
The local loop can be established or interrupted with the following operation:
Remove hybrid P3LE, insert dummy load P3LK and wait
until Link Alarm disappears.
When MOD600 is configured, it must be configured as
Establish local loop Master. The configuration must be changed temporarily
for local loop operation in case it is configured as Slave.
The alarm Both MOD600 configured as Master that will
be generated during local loop operation can be ignored.
Interrupt local loop Unplug dummy load P3LK.
Remove dummy load P3LK, insert hybrid P3LE and
connect RF-cable to X175 at P1LA.
Return to normal operation For MOD600 operation, if - for local loop operation - the
configuration of MOD600 had to be changed from Slave to
Master, change the configuration back to its original state.
Note: After plugging in the dummy load P3LK, wait until Link Alarm disappears.
Revision: Language: Page:
I EN 4/17 1KHW001495-EN
Caution Activating a Tuning tone, simulating alarms, get the equipment to local loop
operation, etc. disturbs the link.
In case of battery supply: Check if the positive pole (+) of the battery is grounded. If it is, place an
earth jumper to the positive pole of the cubicle supply.
Ar min
Ared 3 ,
4
Ar min and Ared in [dB].
2. Determine the new value for max output power by using the table:
3. On the Configuration menu click System... and then click the Channel settings tab.
Enter the new value in the Max. power (PEP) field.
4. Click OK.
5. On the Equipment menu click Download configuration
6. Store configuration to the flash eprom. On the Equipment menu click Store
configuration to FLASH. Answer all dialogs with Yes or OK.
C.5 Transmitter
The Tx RF level and the Tx alarm threshold levels were adjusted during final testing in the works.
They need to be changed only if the return loss is too low.
Note: This step is required only if the Tx filter had to be retuned or exchanged after the
final testing in the works.
The Tx RF level is adjusted using the HMI600, a level meter 50 Ohm (or 75 Ohm) and a
termination resistor or attenuator.
1. In the Tuning & testing dialog box click Adjust Tx RF level. This opens the Adjust Tx
RF level dialog box.
2. Remove the remote equipment by disconnecting the coaxial cable. The local equipment
has to be terminated with 45, 75 or 125 Ohm, depending on the application.
3. Click Start.
4. Measure RF test tone level in dBm at the measuring point RF LINE MONITOR on the
front plate of the RF hybrid P3LE with a level meter set to an input impedance of 50 Ohm.
If a 75 Ohm level meter (indicating in dBm) is used, apply a correction of +0.2 dBm to the
measured value.
Note: When measuring at the test socket RF line monitor, the following tolerances apply:
0.4 dB for frequencies between 16 kHz and 500 kHz
1.0 dB for frequencies between 500 kHz and 1 MHz.
Alternatively, measure the test tone level at the RF line socket (X175) via an attenuator
with impedance 45, 75 or 125 Ohm and a level meter set to the same input impedance
(The attenuator is required in order not to overdrive the input of the level meter).
5. Adjust the value in the Tx RF level [dB] field, download it by clicking Set and measure
the test tone level again. Continue until the measurement corresponds to the permissible
value displayed in the dialog box.
Revision: Language: Page:
I EN 6/17 1KHW001495-EN
C.6 Receiver
Note: It is really necessary to disconnect the RF line coaxial cable of the local equipment
as well as to plug out the Rx filter P4RX!!!
Note: The number of adjustment steps depends on the presence of the Rx filter P4RX
(configured with Configuration / System / Equipment settings / Assemblies in
rack P7LC).
Note: If in doubt about the effective line attenuation, enter the lowest possible attenuation.
Revision: Language: Page:
I EN 7/17 1KHW001495-EN
Note: The increase of the receive level due to parallel PLC links can be calculated as
follows:
N ( Pi P0 )
G dB 20 log 1 10 20 H ( d i )
i 1
Each term of the summation is the contribution of one parallel PLC link and is given
by
Pi = PEP of the local transmitter of the i-th parallel link,
P0 = PEP of the local ETL600 transmitter,
2 K
H (di )
2 ,
(1 d i K 2 ) 2 4 d i
2
f f f0
d i i 0 ,
f0 f i 1.5 B0
f i = Lower edge frequency of the nominal Tx band of the local transmitter of the
i-th parallel link, if this band is above the frequency band of the local ETL600
receiver
or
Upper edge frequency of the nominal Tx band of the local transmitter of the
i-th parallel link, if this band is below the frequency band of the local ETL600
receiver,
f0 = Center frequency of the Rx-filter of the local ETL600 terminal
or if no Rx-filter is used
Center frequency of the Tx-filter of the local ETL600 terminal,
B0 = Bandwidth of the Rx-filter of the local ETL600 terminal
or if no Rx-filter is used
Bandwidth of the Tx-filter of the local ETL600 terminal,
K 0 .9 .
3. After all adjustment steps have been executed, click Close to close the dialog box.
Revision: Language: Page:
I EN 8/17 1KHW001495-EN
Note: The tuning is not necessary when the ETL600 is operated without Rx filter
P4RX. In this case, default settings must be used:
- Jumpers RA, LP, CD and CE set and the remaining C-jumpers in P position.
- Hybrid impedance chosen nearest to the impedance of the coupling filter, i.e.
45, 75 or 125 Ohm with jumpers LNx, Mx and Nx, where x=1 for 45 Ohm,
x=2 for 75 Ohm and x= 3 for 125 Ohm.
Note: The transhybrid loss that has been achieved by tuning the hybrid is equal to the
increase of the measured RF level when the RF cable is unplugged. If it is
higher than 20 dB, the tuning can be considered as successful and may be
terminated.
The RF line coaxial cable is connected to the equipment. The PCB extender type I9BK or the Tx
tuning adapter P3LL is inserted in place of the RF hybrid P3LE and the RF hybrid is plugged on top
of it.
5.
Note: It is possible that the operator phone of remote equipment is ringing during
the measurement. This has no effect on the measurement.
The HMI600 selectively measures the level of the RF signal from the own transmitter.
This level is set to a minimum with the aid of a balancing network (resistance with jumper
RA/RB/RC/RD/RP and potentiometer R228, inductance with jumper LA LN/LP and
capacitance with jumpers CA to CL, CP) as described below.
6. Reduce the measured Rx RF level moving the R-jumper between RA, RB, RC, RD and
RP. When the best jumper position has been found, turn potentiometer R228 until a first
minimum is reached.
7. Search for the next minimum by moving the L-jumper sequentially to LA, LB, LC, , LN.
If, however, jumper LA does not produce any reduction, set Jumper LP. (LA produces the
smallest inductive current and LN the largest).
8.
Note: Only one L jumper (LA LN) may be inserted at any time
C.7 Equalization
Refer to 1KHW001494 APLC Channel Equalization for ETL600. The document is put into a short
instruction, printed in the following chapters C.7.1 and C.7.2.
Note: The equalization routine can also be done at the remote equipment via EOC
communication.
Note: If telephony is configured with a speech cut off frequency of 3400 Hz in any of
the APLC channels, the equalizer must be enabled for each of these channels.
When configuring the equalizer (dialog box Equipment / Commissioning and
maintenance / Select equalizer), press the radio buttons Long and Amplitude
equalization only.
The NSD600 transmission time is tested by sending a loop test over the link.
NSD600 with interfaces G4AI is tested by applying test commands at the G4AI inputs and
measuring these test commands at the G4AI outputs.
To get back the input commands at the outputs of the local equipment, a local loop is necessary.
The local loop can be established according to chapter C.1.
Make a printout of the actual configuration of the equipment using HMI600 and test all G4AI inputs
and outputs.
Note: Transmission times of twice the nominal transmission time as given in the
technical data shall serve as a guideline for the upper limit.
Transmit at few commands with a command / pause duration of about 100ms / 1000ms and
measure the nominal transmission time (Tnominal) of the local looped command.
Note: The measured transmission time (Tnominal) does not include the channel delay.
Note: The nominal transmission time as given in the instruction manual shall serve
as a guideline for the mean value of several commands.
Example:
Applying above method to the configuration given below, a sinus with 9.0 dBm is fed into AFx-IN.
The tone is expected with 9.0 dBm at AFx-OUT of local equipment.
Equipment:
TELEOPERATION
Port AFx: Disconnectable at CH1
Squelch: Disabled
Reference signal: 600 Bd FSK
Reference signal level input: -9.00 dBm (RMS)
Reference signal level output: -9.00 dBm (RMS)
Weight of port: 0.71
Max. output level: 4.34 dBm (PEP)
Relative input level: -4.0 dBr
Relative output level: -4.0 dBr
Input filter: None
Output filter: None
1. Check the port settings in the configuration (Configuration / Data port to modem
assignment) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test (recommended number of bits to transmit: 106).
1. Check the port settings in the configuration (Configuration / Data port to modem
assignment) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test (recommended number of bits to transmit: 106).
1. Connect the data testers to the G.703.1 ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped at the remote equipment.
2. Perform a BER test during the required time. The recommended number of bits to transmit
is 107.
C.18 Documentation
After the testing is complete, take a printout of the configuration and status data.
1. Click the green Upload arrow in the toolbar with the left mouse button. This starts the
upload configuration and upload status from the equipment. The status is displayed in the
window.
2. From the File menu, click Print. This prints the status data.
3. From the View menu, click Display configuration.
4. From the File menu, click Print.
Save the 'et6' file on a disk with the Serial No. of ETL coded in the file name. e.g.HE400327C0.et6.
We reserve all rights in this document and in the information contained therein. Reproduction,use or disclosure to third parties without express authority is strictly forbidden.
2012 ABB
COMMISSIONING REPORT
Project : ..
ABB Order N : ..
Station : ..
Link : ..
Equipment N : ..
Direction : ..
.. Pages ................
Rev. ind:
..
SAFETY INSTRUCTIONS
Designation Meaning
___________ Measured value
[ ... ] Programmed value
[ ]D Preferred setting (default)
[X ] Test passed or jumper is set
[ ] Not tested or jumper is not set
B5LA Module type
BER Bit Error Ratio
Def. Default value
equ. Equipment
fLo Lower frequency, usually meant as low cut-off frequency
LED Light Emitting Diode found on the front panel
HMI600 User Interface Program for ETL600 running on a PC
N11, , N71 Position in rack. Slot number N11, , N71
Rx Receiver
Tx Transmitter
PC Personal Computer
X11, , X71 Position in rack. Equivalent to N11, , N71
(T.22/..1) Connector 1 of terminal block connected to board at rack position N22
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
REVISION
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
C.1. General
C.2. Power supply for channel rack P7LA Mark if not configured: upper* lower
[ ] [ ]D
C.2.1 Battery supply 48V DC B5LA (BAT-0V) -46 to 56 V DC [ ] [ ]D
C.2.2 Mains supply 230V AC B5LC (UR-0V) -46 to 52 V DC [ ] [ ]D
C.2.3 Mains supply 115V AC B5LC (UR-0V) -46 to 52 V DC [ ] [ ]D
C.2.4 Ripple on 48V DC B5LA (BAT-0V) <1 V rms [ ] [ ]D
C.2.5 Ripple on UR (Mains) B5LC (UR-0V) <1 V rms [ ] [ ]D
upper und lower stands for upper rack / lower rack and applies to 80 W equipment ETL680 only.
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
C.5. Transmitter
C.6. Receiver
1
If the remote equipment is operational
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
2
C.6.4 Tune hybrid P3LE
RF Coaxial cable to be connected.
Dialog box: Tune RF hybrid Dialog box Till minimum is [ ]
Press 'Start measurement' & adjust the read by HMI.
balancing network (Resistance with jumper
RA/RB/RC/RD/RP and potentiometer
R228, inductance with jumper LA LN/LP
and capacitance with jumpers CA to CL,
CP)
Ch 1 Ch 2 Ch 3
C.6.5 SNR pilot Mark if not configured: [ ] [ ] [ ]
Upload status data of local equipment
SNR pilot HMI600 > 15 dB [ ] [ ] [ ]
C.7. Equalization
Ch 1 Ch 2 Ch 3
C.7.1 Measure frequency response Mark if not configured: [ ] [ ] [ ]
2
The tuning is not necessary when the ETL600 is operated without Rx filter P4RX.
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
TPE1 TPE2
C.10.1 NSD600 loop test Mark if not configured: [ ] [ ]
TPE1 TPE2
Command A Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command A (T71/1) (T71/2) [ ] Mean value
(T/...) (T.../) [ ]
T0 ms ________ ________
Rx command A (T71/9) (T71/10) [ ]
(T/...) (T.../) [ ]
TPE1 TPE2
Command B Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command B (T71/3) (T71/4) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command B (T71/11) (T71/12) [ ]
(T/...) (T.../) [ ]
TPE1 TPE2
Command C Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command C (T71/5) (T71/6) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command C (T71/13) (T71/14) [ ]
(T/...) (T.../) [ ]
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
TPE1 TPE2
Command D Mark if not configured: [ ] [ ]
Terminal: Refer HMI600
Tx command D (T71/7) (T71/8) [ ] Mean value
(T/...) (T.../) [ ] ms
T0 ________ ________
Rx command D (T71/15) (T71/16) [ ]
(T/...) (T.../) [ ]
Pick up the phone and talk. Service phone, at front Own voice is N11 N22 N54
panel audible without
feedback or [ ] [ ] [ ]
excessive echo
C.11.2 Hot line direct phone Mark if not configured: N11 N22 N54
[ ] [ ] [ ]
N22: ___________
N54: ___________
Pick up the phone and talk Direct telephone Own voice is N11 N22 N54
audible without
feedback or [ ] [ ] [ ]
excessive echo
N22: ___________
N54: ___________
Pick up the phone and talk Suscriber telephone Own voice is N11 N22 N54
audible without
feedback or [ ] [ ] [ ]
excessive echo
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open M-wire at [ ] [ ] [ ]
terminal telephony 4a-4b
Measure Output level. Feed into terminal Configured Output dBm N11 N22 N54
Feed 800 Hz with configured telephony 1a-1b level 1 dB (600 )
(Def.: -3.5 dBm) [ ] [ ] [ ]
input level of Pax Measure at terminal
(Default: -3.5 dBm). telephony 2a-2b
(Activate at terminal telephony
4a-4b)
PAX-BLOCKING normal Measure at terminal 6a-6b is open N11 N22 N54
telephony 6a-6b, 6b-7a 6b-7a is closed
[ ] [ ] [ ]
PAX-BLOCKING blocked Measure at terminal 6a-6b is closed N11 N22 N54
Interrupt local loop, wait about telephony 6a-6b, 6b-7a 6b-7a is open
[ ] [ ] [ ]
30 sec.
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open M-wire at
[ ] [ ] [ ]
terminal telephony 4a-4b
Measure Output level at AF1. Feed into terminal Configured Output dBm N11 N22 N54
Feed 800 Hz with configured telephony 1a-1b level 1 dB (600 ) [ ] [ ] [ ]
input level (Def.: -3.5 dBm). Measure at terminal (Def.: -3.5 dBm)
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
C.11.7 Transit mode for E&M wire Mark if not configured: N11 N22 N54
[ ] [ ] [ ]
Test E-Wire: Terminal telephony 3a-3b E-Wire must toggle N11 N22 N54
Close and open M-wire at [ ] [ ] [ ]
terminal telephony 4a-4b
C.11.9 Teleoperation AF1, if not Mark if not configured: N11 N22 N34 N54 N65
used for telephony
[ ] [ ] [ ] [ ] [ ]
C.11.10 Teleoperation AF2 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
C.11.11 Teleoperation AF3 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
C.11.12 Teleoperation AF4 Mark if not configured: N11 N22 N34 N54 N65
[ ] [ ] [ ] [ ] [ ]
C.11.13 Teleoperation AF4 used for Mark if not configured: N11 N22 N54
ext. teleprotection [ ] [ ] [ ]
Fed input level, [dBm], Feed into terminal teleop. Expected Output Measured Output level at
@ 800 Hz at AF4-IN 7a-7b level at AF4-OUT AF4-OUT
N11: ___________ Measure at terminal N11: _______1 dBm N11: ___________
teleop. 8a-8b (600 )
N22: ___________ N22: _______1 N22: ___________
N54: ___________ N54: _______1 N54: ___________
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
O4CV#2: N_____
O4CV#3: N_____
O4CV#4: N_____
Pick up the phone and talk. Service phone, at front Own voice is [ ]
panel of O4CV#1 audible without
feedback or
excessive echo
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
C.18. Documentation
Notes:
..............................................................................................................................................................
..............................................................................................................................................................
..............................................................................................................................................................
Sign Commissioning Eng.: Sign Witness Eng.:
Doc. no. Lang. Rev. ind. Page
Issue Description
YES NO YES NO
Commissioning Approved: Exceptions Noted:
Name PSNP3
of responsible
Signature &
Date
Company ABB Switzerland Ltd Consultant Customer
Contents
1 Purpose of document 2
2 General 2
2.1 Necessity for a firmware download 2
2.2 Risks of a firmware download 2
2.3 Firmware download files 3
2.4 Firmware download parameters 4
2.4.1 Automatic firmware download 4
2.4.2 User controlled firmware download 4
3 Firmware download 4
3.1 Update of non-configured equipment 4
3.2 Update of already configured equipment 5
3.3 HMI600 detects an incompatibility while downloading the configuration 5
3.4 HMI600 detects an incompatibility after extending the equipment 6
3.5 HMI600 detects an incompatibility after exchanging a module 6
3.6 Unsuccessful or incomplete firmware download to P4LT/P4LU 7
3.7 R1LA firmware recovery 7
List of equipment:
PC with Windows 2000 or XP
HMI600 software
Firmware download files
PC P4LT/P4LU cable (1:1 serial RS-232)
Note:
Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2008 ABB
Revision: Language: Page:
F EN 2/9 1KHW001496-EN
1 Purpose of document
This document describes the firmware download process for the equipment ETL600 Rel.1,
supported by the PC program HMI600.
2 General
The HMI600 supports firmware download for the modules P4LT/P4LU, R1LA, O4LE and G4AI.
The firmware download gives the opportunity to update the equipment to the latest release or to
modify a module ordered from stock to the actual release in the clients equipment.
The automatic release detection in the HMI600 identifies incompatibilities between firmware
versions on the modules in an equipment before the configuration upload or download process is
executed. If any incompatibility is recognized, the HMI600 will indicate that a firmware update has
to be executed. In this case a configuration download is not possible. The automatic release
detection doesnt detect if the latest release is installed. For information about available releases
and about compatibility between software, firmware and hardware of the ETL600 system please
refer to the document Compatibility Requirements for ETL600 (1KHW001490).
The firmware of module P4LT/P4LU is stored in a non-replaceable FLASH memory and will be
checked for integrity during the start-up procedure. Therefore, if a firmware download failed due to
a power or communication failure, this will be detected and a so-called emergency firmware will
be activated. This emergency firmware supports a firmware download only and is indicated by
sequentially blinking (in anticlockwise direction) of all LEDs of the module P4LT/P4LU.
Caution Firmware download should only be executed from PCs with a correctly
installed Windows operating system. Do not use PCs that show signs of
instability such as premature abnormal terminations of programs.
Caution Hands should be kept away from keyboard and mouse while a firmware
download is in progress except when HMI600 prompts for interaction.
Caution If the new firmware is incompatible with an already stored configuration, then
the P4LT/P4LU module will use the default configuration after completion of
the firmware download.
The serial data rate of the P4LT/P4LU default configuration is 57600 bps. If
any other serial data rate was configured before the firmware download (on
the P4LT/P4LU module and in the HMI600) and the module starts up with the
default configuration, no further access via the HMI-COM port will be possible
until the serial data rate of the HMI600 is readapted to this default data rate of
the module (i.e. 57600 bps).
The user controlled firmware download provides the opportunity to modify one selected module in a
system. Deactivating the checkbox for automatic firmware download enables the button Reset
system. Please follow the instruction in the Download status & progress instruction window.
3 Firmware download
10. Wait until the Close button changes to the active state.
11. Click Close to leave the firmware download dialog box.
12. From the Equipment menu, click Download configuration. The license is checked and an
error message appears if it is not sufficient. Compatibility checks are performed to verify that
the firmware versions on the different modules in the equipment belong to the same release
as the HMI600. If not, an error message pops up. Depending on the message, an earlier
version of HMI600 must be used and/or the firmware of some modules must be upgraded.
Revision: Language: Page:
F EN 5/9 1KHW001496-EN
13. If the Download configuration operation is possible, a message box appears, which
indicates that the link will be cut off for a few seconds.
Click Yes.
14. The Test configuration time dialog box has been opened by the HMI600.
Click OK.
15. The HMI600 now compares the equipment identification from the file with the identification
stored in the equipment. If it is different, a warning message box appears.
Click OK. This starts the download configuration process.
16. A dialog box indicates, that the configuration has not been stored in the non-volatile flash
EPROM and asks to do so.
Click Yes.
The configuration data are now stored in the flash EPROMs. This process needs some
seconds. Please wait until the color of the stop button in the toolbar changes from red to grey.
The actual status of the process is displayed in the status bar.
11. Wait until the Close button changes to the active state.
12. Click Close to leave the firmware download dialog box.
13. Click Download Configuration.
1. The HMI600 alerts the incompatibility; in some cases the configuration is modified and
correspondingly indicated by the HMI600.
2. On the Equipment menu, click Commissioning and maintenance and then click Firmware
download
3. In the following message box click Yes if a malfunction of the PLC link is acceptable. This
opens the Firmware download dialog box. Otherwise click No.
4. The checkbox Automatic firmware download has to be ticked.
Revision: Language: Page:
F EN 6/9 1KHW001496-EN
proceed with chapter 3.3. If not, the firmware is fully compatible to the other modules in the
equipment.
1. On the File menu click New. This opens the Connect dialog box.
2. Click Logon, Equipment address: 0
3. Click Read & Write access.
4. Click OK. This opens a HMI600 child window.
5. On the Equipment menu, click Commissioning and maintenance and then click Firmware
download
6. In the following message box click Yes if a malfunction of the PLC link is acceptable. This
opens the Firmware download dialog box. Otherwise click No.
7. Uncheck the checkbox Automatic firmware download.
8. Verify that the Slot ID: is set to N45 [P4LT/P4LU].
9. Click Start firmware download to start the operation.
10. This opens a Select firmware file for module P4LT dialog box. Browse to the folder where
the firmware download files are stored refer to 2.3. Select the file P4LT_***.ldr and click
Open.
11. Wait approx. 10 minutes until the message box Firmware download successful will appear
and click OK.
12. Click Reset system and wait until the Close button is accessible.
13. Click Close to leave the firmware download dialog box.
Caution Disconnect your PC from the LAN before launching the program
Tftpd32.exe! Otherwise the PC will start to distribute IP addresses,
which disables other PCs from properly accessing the LAN.
Step-by-step instructions:
1. Turn off the ETL600 terminal.
2. Disconnect the PC from the LAN and connect it directly to the LAN port of the ETL600 using a
cross-over Ethernet cable.
3. Disable any running firewall on the PC.
4. Turn on the ETL600 terminal and wait 8 seconds.
5. Start Tftpd32.exe found in the folder R1LA Firmware Recovery in the HMI600 installation
directory.
6. Select the tab DHCP server, see Fig. 1.
Revision: Language: Page:
F EN 8/9 1KHW001496-EN
7. Make sure the Server interfaces field shows an IP address different from 127.0.0.1
(otherwise this might indicate that the Ethernet cable is not properly connected the LAN port of
the ETL600).
8. Set the IP pool starting address to the same address as displayed in the Server interfaces
field, but increment the last digit by one.
9. Turn off the ETL600 terminal.
14. Stop Tftpd32.exe by pressing the close button (X) in the upper right corner of the window.
15. Reset the ETL600 device.
16. The R1LA is again ready for downloading the finally desired firmware via the regular HMI600
firmware download.
ABB Switzerland Ltd 1KHW001497-EN
Archive No. Rev. Date:
Anomaly List for ETL600 - T 2013-11-11
Responsible Department: Prepared: Approved: Distribution: Lang. Page
PSND 2005-09-29 C. Leeb 2013-11-11 H.-J. Maag - EN 1/8
Valid for: Derived from: Replaces: Classification-No.: File:
- 1KHL016399-EN - - 1KHW001497TE Anomaly List for ETL600.doc
Contents
1 Purpose........................................................................................................................... 1
2 Anomalies ....................................................................................................................... 2
2.1 Deviation of level measured at the socket RF LINE MONITOR on P3LE ......... 2
2.2 Incorrect SNR evaluation for high weights of NSD600 guard signal.................... 4
2.3 Time-limited persistent commands of NSD600 in 2 kHz APLC channel ........... 5
2.4 Configuration file incompatibility ........................................................................... 6
2.5 Limited fax transmission in photo mode with O4CV............................................. 6
2.6 Unreliable fax transmission in transit operation with O4CV ................................. 7
2.7 HMI600 displays incorrect permissible RF line monitor levels ............................. 7
2.8 LAN600 router mode maloperation ...................................................................... 8
2.9 HMI600 displays corrupt slot numbers for ETL600-050-2 and ETL600-100-2 .... 8
1 Purpose
This document describes the currently known anomalies in the behavior of the ETL600 system.
Such anomalies express themselves in unexpected system behavior not described in the instruction
manual ETL600 Rel.3 (1KHW001489-EN) or ETL600 Rel.4 (1KHW002582-EN).
This document is updated immediately after a new anomaly has been discovered and verified.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. 2013 ABB
Revision: Language: Page:
T EN 2/8 1KHW001497-EN
2 Anomalies
For each anomaly, the following information is given:
- the types of the hardware modules and/or the versions of firmware or software taken to be
responsible for the observed anomaly,
- a description of the anomaly,
- a workaround (if any).
Note: This anomaly only applies to the initial version of the RF hybrid,
designated P3LE, not P3LEa or later.
To find out the version, remove the RF hybrid and check the sticker on its backplane connector:
Sticker
Revision: Language: Page:
T EN 3/8 1KHW001497-EN
2.1.2 Description
The level measured at the socket "RF line monitor" deviates from its rated level (50 dB below the
power at the RF output) as follows:
Impedance Deviation Measured level at RF line monitor socket [dBm @ 50 Ohm]
45 Ohm -1.1 dB RF output power [dBm] 51.1 dB
75 Ohm +1.2 dB RF output power [dBm] 48.8 dB
125 Ohm +3.5 dB RF output power [dBm] 46.5 dB
Note: As indicated in the documents 1KHW001493 and 1KHW001495, where the Tx level
adjustment procedure is described, the adjustment precision for the Tx level is
limited by the tolerance for levels measured at the coax socket RF line monitor.
Revision: Language: Page:
T EN 4/8 1KHW001497-EN
2.2 Incorrect SNR evaluation for high weights of NSD600 guard signal
2.2.2 Description
The weight of the NSD600 guard signal can be much higher than the weight of the ETL600 pilot not
used as NSD600 guard signal. The SNR evaluation is not correct for SNR above a limit that depends
on the weight of the guard signal. This limit is shown in Fig. 2-1. When the SNR level alarm threshold
is set above the limit, an SNR alarm will be generated although the actual SNR in the channel might
be below the alarm threshold.
Note that in APLC channels where no NSD600 is configured, the SNR evaluation is correct.
25
for correct SNR detection [dB]
20
Upper SNR limit
15
10
0
0 1 2 3 4 5 6 7 8
Weight of TPE1, Weight of TPE2
Fig. 2-1
2.3.2 Description
The single purpose teleprotection NSD600 in 2 kHz APLC allows transmitting of persistent commands
without alarm if the Max Tx Trip Duration monitoring checkbox is not marked (as shown in Fig. 2-2).
In release 2.0 the maximum Tx trip duration of the correspondingly configured command is time-
limited to 55 hours and 55 minutes instead of infinite. After this time, alarm is raised and the guard
signal is sent instead of the trip signal.
Fig. 2-2
2.4.2 Description
The HMI600 version 2.08 (release 2.1.0) cannot open configuration files generated with HMI600 1.41
(release 2.0.0). Instead, a message box appears:
2.5.2 Description
When transmitting a fax document in continuous tone grey-scale or color mode (according to ITU-T
Recommendation T.30, Annex E) via a compressed telephony channel of interface O4CV, the
transmission is stopped after the first page of the document or after 30 minutes when the first page
has not been transmitted within this time.
2.6.2 Description
In transit operation, i.e. when telephony channels of an ETL600 link are relayed to a second link by
interconnecting the outputs and inputs of the corresponding O4CV modules, fax transmission does not
work reliably.
2.7.2 Description
For ETL600 Rel.4, i.e. for equipment types ETL600-050-1, ETL600-050-2 or ETL600-100-2, unless
PEP is set to 50 W corresponding to 47 dBm, HMI600 displays incorrect permissible levels for
RF line monitor (on E5TH) in the frame Test point and permissible values of the Dialog
Equipment / Tuning and testing / Adjust Tx RF level:
However, the displayed permissible level for the socket RF line (on E5TH) is correct.
2.8.2 Description
The LAN600 router mode does not work correctly if the LAN1 port is disabled.
2.9 HMI600 displays corrupt slot numbers for ETL600-050-2 and ETL600-100-2
2.9.2 Description
For ETL600 Rel.4 double rack equipment, i.e. equipment types ETL600-050-2 and ETL600-100-2, the
configuration view of HMI600 displays corrupt slot numbers for the optional modules O4LE, O4CV and
G4AI in the rack P7LF.
FAULT REPORT Please fill-in a separate FAULT REPORT for each Item and send to PSNP4 !
A. GENERAL
All of ABBs equipment and parts are warranted against defects in material and workmanship for a period as agreed in the
ORDER or in the SERVICE CONTRACT.
Please do always include a FAULT REPORT when sending any item(s) to ABB for Repair & Return.
5. Repair Item(s)
Completely fill-in all 5 sections of a separate FAULT REPORT for each Item.
Include FAULT REPORT with Item(s) when returned to PSNP4.
E-Mail or FAX copy of FAULT REPORT to PSNP4 - and also Airway Bill (AWB) No. if sent by airfreight.
Include name and contact details of a technical person who can be contacted by the PSNP4 repair engineers
to discuss technical issues related to the fault. This information shall be stated at Section 4 of the FAULT
REPORT.
Note down the equipment type to which the Item belongs to (e.g. FOX515, ETL600, NSD570) on the FAULT
REPORT, Section 1.
Note down serial number and release number (if any) of the faulty Item on the FAULT REPORT, Section 1.
In case of SERVICE CONTRACT in force, the number of the SERVICE CONTRACT shall be indicated on the
FAULT REPORT, Section 3.
Advance Replacement:
If you need an Advance Replacement, tick the respective field on the FAULT REPORT.
A purchase order is required before shipment of the Advance Replacement. The customer will be invoiced for
the full price of the Advance Replacement unit.
Please note that PSNP4 does not guarantee that Replacement Iitems will be available, except for Replacement
Items defined in a SERVICE CONTRACT.
Unit for Checking:
This service will be charged with US$ 500.00 for each unit.
E. Packing
When packing the Item(s) anti-static bags shall be used to wrap-in item(s) carefully. Please ensure that the
packing is sufficient to avoid damages during shipment. Ideally, item(s) shall be returned in the same packaging as
it was supplied.
Any Item(s) received in damaged conditions, appearing to be caused from inadequate packing, will not be
repaired until a purchase order covering repair cost of the additional damage is received by PSNP4.
Questions,
Technical
Support
1. Support
request
2. Formal acceptance of
price and delivery terms
3. Service delivery
ETL600 complies with or exceeds the requirements according to IEC publication 60495, second
edition, Sept. 1993, with reference to single sideband PLC equipment.
The integrated teleprotection equipment NSD600 complies with or exceeds the requirements
according to IEC publication 60834-1 "Teleprotection Equipment of Power Systems - Performance
and Testing Part 1: Command Systems.
SYSTEM DATA
Operating mode 2 - wire frequency duplex
Nominal bandwidth 2, 4, 8, 12, 16, 20, 24, 28, 32 kHz (each direction)
Edge frequencies at multiples of 500 Hz
Standards compliance IEC 60495, IEC 60834-1, IEC 60950-1, IEC 61000-6-2,
IEC 61000-6-4 (EN 55022 / CISPR22, Class A)
Nominal transmit output power (PEP) ETL640: 10, 20, 40 W, programmable via HMI
ETL680: 80 W (option)
2 kHz nominal bandwidth (not available for ETL600 Rel 1.0):
- 40 W for carrier frequencies between 40 and 150 kHz,
- 10 W for carrier frequency 500 kHz,
- linearly decreasing between 150 and 500 kHz.
RF frequency range 24 to 1000 kHz for nominal output power = 10, 20, 40 W
24 to 500 kHz for nominal output power = 80 W
38 to 500 kHz for 2 kHz nominal bandwidth
Tapping loss 1.5 dB at and beyond +/- 1.5 x bandwidth from Tx filter center frequency
(for Tx filter center frequencies 750 kHz: +/- 1.7 x bandwidth)
Available power (PEP) at coaxial output for nominal bandwidth of 2 kHz (not available for ETL600 Rel.1.0):
Bandwidth ETL640 ETL680
Tx center frequency
of Tx Filter 75 / 125 Ohm 75 / 125 Ohm
4 kHz 40 to 150 kHz +46 dBm +49 dBm
4 kHz 150 to 500 kHz +46 to +40 dBm * +49 to +43 dBm *
* linearly decreasing in W
Frequency gap between equipment connected in parallel to the same coupling equipment:
Nominal bandwidth [kHz]: 2* 2* 4 8 12, 16 12, 16 16 16
Tx center frequency [kHz]: 200 200 750 750 750 750
- Transmitter to its own receiver [kHz]: 0 0 0 0 0 0 0 0
- Transmitter to adjacent transmitter [kHz]: 4 8 10 8 16 20 32 40
- Transmitter to adjacent receiver [kHz]: 2 4 6 4 8 10 16 20
- Receiver to adjacent receiver [kHz]: 0 0 0 0 0 0 0 0
* not available for ETL600 Rel.1.0
Receiver selectivity
- at 300 Hz / 4 kHz from the band edges 65 dB / 75 dB for nominal bandwidth 2 kHz
- at 300 Hz / 2 kHz from the band edges 55 dB / 65 dB for nominal bandwidth 2 kHz
Image rejection 75 dB
Event recording 2600 time-stamped alarm & manipulation events, stored in non-volatile memory
Clock synchronizing input for IRIG-B available
Number of AF channels for the transparent transmission of speech plus superimposed teleoperation signals:
- 0, 1, 2 or 3 channels with 4 kHz bandwidth each, or
- 3 channels of 3.2, 2.4 and 2.4 kHz bandwidth respectively, in 8 kHz total bandwidth,
Frequency offset 0 Hz
Speech low-pass filter cut-off frequency - 2.0 kHz to 3.4 kHz, programmable in steps of 200 Hz, limited by AF channel bandwidth
- 1.6 kHz for nominal bandwidth of 2 kHz
Telephony (analog)
No telephony services except service phone available for nominal bandwidth of 2 kHz
Service telephone
Connector for 2-wire telephone set RJ11 on front panel
Digital transit
Number of transit connections up to 5 (i.e. 6 telephony links in a chain)
Number of links per node up to 5 (1 master, up to 4 slaves)
Service telephone
Connector for 2-wire telephone set RJ11 on front panel
Programmable impedances for 2-wire interfaces (FXS, FXO and service phone)
Rs [] Rp [] Cp [nF]
600 0 infinite
220 820 115
300 1000 220
600 infinite 1000
900 infinite 1160
270 750 150
Teleoperation
Number of ports 20
Impedance 600 Ohms, balanced
Input level -20 to +4 dBm
Output level -20 to +8 dBm
Transit filters
Number of filters 20
Standard filters Programmable bandpass filters with cut-off frequencies selectable in steps of 60 Hz
Group delay equalized filters - bandpass filters for teleoperation band above speech 2000, 2200 or 2400 Hz, or
- 3600 Hz lowpass filter
DATA SERVICES
No data services available for nominal bandwidth of 2 kHz
Data ports
V.11 ports
Number of V.11/X.24 ports 1 or 2 (option), depending on configuration
Data rates 9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,
72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2, 320 kbps
Clock direction - From ETL600
- Codirectional (not available for ETL600 Rel.1.0)
V.24 ports
Number of V.24/RS-232 ports 2, 4 (option) or 6 (option), depending on configuration;
with optional port sharing and jabber timeout for point-multipoint operation
Programmable data rates 9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,
(including multiplexer overhead) 72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2 kbps
Programmable data rates 9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,
72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2 kbps
Connector electrical: 10/100BaseT: shielded twisted pair (STP), connector type RJ-45
optical: 100 Mbps (SFP 850 nm MM or 1310 nm SM), connector type LC
Services Switch (layer 2) or router (layer 3), SNMP, HMI over LAN
VLAN support according to IEEE 802.1q for switch
Link fault pass through
Up to 16 static routes
Flow control
4 priority queues
Max. data rates above 2 kHz speech band 1 x 1200 Bd (asynchronous, transparent), or
2 x 2400 bps, or 1 x 4800 bps (asynchronous, UART)
Typical efficiency (data rate divided by bandwidth) in relation to SNR for default Delay/Efficiency setting:
10
Efficiency for BER=1E-6 [bps/Hz]
0
10 15 20 25 30 35 40 45
SNR in band [dB]
Multiplexer (MUX600)
Application Time-division multiplexing of a number of data and compressed telephony channels into
an aggregate data stream
Multiplexing method TDM, with data flow control and speed adaptation according to aggregate capacity
TELEPROTECTION (NSD600)
Application Transmission of protection commands for line- and objects protection
Number of commands for each NSD600 in 3.2 kHz or 4 kHz APLC channels:
4 independent commands A, B, C, D, simultaneously transmitted,
individually configurable for blocking, permissive or direct tripping,
plus 1 test command T per NSD600.
Unblocking output Unblocking output contact closes for a predefined time (e.g. 200 ms) upon
loss of Rx-signal (no trip and no guard)
Bandwidth requirement Nil; command signal transmission in-band (alternate purpose, with signal boosting)
Guard signal ETL-pilot signal, or own guard signal above speech band 2000, 2200 or 2400 Hz
Processing of received signal Adaptive (to prevailing channel condition, always ensuring shortest transmission times)
Number and type of outputs 4 solid state relays and 2 mechanical relay contacts per Teleprotection Interface G4AI
Tripping voltage 5 to 250 VDC nominal
Tripping current 1 A carry / 2 A peak solid state
5 A carry / 20 A peak mechanical relay
Event logging 2600 time-stamped command events, command counters; stored in non-volatile memory
Clock synchronizing input for IRIG-B available
Teleprotection performance
NSD600 in 2 kHz, 3.2 kHz or 4 kHz APLC channels:
Performance criteria, description of measurement Abbrev. Blocking Permissive tripping Direct tripping
Nominal transmission time (back-to-back operation,
1) 2) . .
including PLC equipment delay and operating times of T0 10 ms 11 ms 12 ms
the teleprotection interface I/Os; noise free channel)
Security - probability of an unwanted command
Puc < 1E-04 < 1E-06 < 1E-09
(200 ms noise, 200 ms pause, worst case SNR)
Dependability - probability of missing a command Pmc < 1E-03 < 1E-03 < 1E-04
required channel condition SNR 6 dB / 5 dB 6 dB / 4 dB 6 dB / 4 dB
1)
for maximum actual transmission time Tac 14 ms / 15 ms 17 ms / 20 ms 22 ms / 26 ms
1)
Valid for the solid state command outputs, add 58 ms for the relay contact command outputs.
With own NSD600 guard. Add 1 ms for ETL600 pilot with frequency 3600 Hz as guard signal.
2)
Add 1 ms for NSD600 in 2 kHz APLC channel plus 2 kHz DPLC channel.
Performance criteria, description of measurement Abbrev. Blocking Permissive tripping Direct tripping
Nominal transmission time (back-to-back operation,
1) . .
including PLC equipment delay and operating times of T0 11 ms 12 ms 13 ms
the teleprotection interface I/Os; noise free channel)
Security - probability of an unwanted command
Puc < 1E-03 < 1E-06 < 1E-09
(200 ms noise, 200 ms pause, worst case SNR)
Dependability - probability of missing a command Pmc < 1E-03 < 1E-03 < 1E-04
required channel condition SNR 6 dB 6 dB 6 dB
1)
for maximum actual transmission time Tac 15 ms 17 ms 22 ms
1)
Valid for the solid state command outputs, add 58 ms for the relay contact command outputs.
Single purpose teleprotection NSD600 in 2 kHz APLC channel (not available for ETL600 Rel.1.0):
Performance criteria, description of measurement Abbrev. Blocking Permissive tripping Direct tripping
Nominal transmission time (back-to-back operation,
1)
including PLC equipment delay and operating times of T0 11 ms 12 ms 14 ms
the teleprotection interface I/Os; noise free channel)
Security - probability of an unwanted command
Puc < 1E-03 < 1E-06 < 1E-09
(200 ms noise, 200 ms pause, worst case SNR)
Dependability - probability of missing a command Pmc < 1E-03 < 1E-03 < 1E-04
required channel condition SNR 6 dB 6 dB 6 dB
1)
for maximum actual transmission time Tac 17 ms 19 ms 30 ms
1)
Valid for the solid state command outputs, add 58 ms for the relay contact command outputs.
AMBIENT CONDITIONS
Operation
Climatic conditions IEC 60721-3-3, Class 3K5
Temperature range Within specification: -5 to +55 C
Humidity 95%, < 28 g/m3, non-condensing
Mechanical conditions IEC 60721-3-3, Class 3M1
Vibration and shock IEC 60068-2-6, IEC 60068-2-27
Transport
Climatic conditions IEC 60721-3-2, Class 2K4
Temperature range -30 to +70 C
Humidity 95%, < 28 g/m3, non-condensing
Mechanical conditions IEC 60721-3-2, Class 2M1
Vibration sinusoidal IEC 60068-2-6
Shock and free fall IEC 60068-2-27, IEC 60068-2-32 0.25 m / equipment is packed
Storage
Climatic conditions IEC 60721-3-1, Class 1K5
Temperature range -30 to +70 C
Humidity 95%, < 28 g/m3, non-condensing
Mechanical conditions IEC 60721-3-1, Class 1M1
www.abb.com/utilitycommunications
Do you find the publication readily understandable and logically structured? Can you
make any suggestions to improve it?
Is the information sufficient for the purpose of the publication? If not, what is missing
and where should it be included?
Name Date
Company
www.abb.com/utilitycommunications